Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2020-06-03 19:11:47
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2463.11 | 509.42 | 509.42 |
Net Site Energy | 2463.11 | 509.42 | 509.42 |
Total Source Energy | 4308.52 | 891.09 | 891.09 |
Net Source Energy | 4308.52 | 891.09 | 891.09 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1676.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 98.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 28.43 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 786.61 | 1676.50 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1676.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 2.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 98.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 42.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 28.43 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 118.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 15.06 | 346.73 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 162.69 | 346.73 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 118.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 15.06 | 346.73 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 162.69 | 346.73 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 786.608 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 786.608 | 100.00 |
Total On-Site and Utility Electric Sources | 786.608 | 100.00 |
Total Electricity End Uses | 786.608 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 164.83 |
Time Setpoint Not Met During Occupied Cooling | 0.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2579.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.6337 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.5069 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.5069 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 11-JAN-15:50 | 30-JAN-06:19 | - | - | - | 11-JAN-12:09 |
Heating | 0.00 | 248358.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 6311.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2836.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2692.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 57141.15 | 248358.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 248358.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 6311.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2836.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 2692.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1817.33 | 0.00 | 0.00 | 0.00 |
Cooling | 6.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1507.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 311.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 133.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2491.19 | 1817.33 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 375.86 | 0.00 | 0.00 | 0.00 |
Cooling | 1.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 64.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 515.23 | 375.86 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 375.86 | 0.00 | 0.00 | 0.00 |
Cooling | 1.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 64.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 515.23 | 375.86 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.891240 |
ZONE2 FINE STORAGE DIRECT AIR | 1.46 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 2.43 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 2.43 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 99427.36 |
PSZ-OFFICE HEATING COIL | 27786.55 |
PSZ-FINE STORAGE HEATING COIL | 71473.09 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 99427.35 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.891240 | 0.891240 | 0.891240 | 0.891240 | 0.891240 | 0.891240 | 1.00 | 1.00 | 0.891240 |
PSZ-FINE STORAGE | 1.46 | 1.46 | 1.46 | 1.46 | 1.46 | 1.46 | 1.00 | 1.000000 | 1.46 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 0.891240 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 1.46 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.891240 | 0.891240 | 0.891240 | 0.891240 | 14753.19 | 27786.55 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 1.46 | 1.46 | 1.46 | 1.46 | 27192.65 | 71473.09 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.891240 | 0.445620 | 0.891240 | 14753.19 | 14753.19 | 7376.60 | 14753.19 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 1.46 | 0.728230 | 1.46 | 24109.58 | 27192.65 | 13596.33 | 27192.65 | 0.756971 | 0.756970 | 0.756970 | 0.756970 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.891240 | 1016.11 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.46 | 1594.10 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.634 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.707 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.507 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.507 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.507 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.066 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2518.900 | 10.634 | 503.780 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2518.900 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11853.648 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11853.648 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27263.390 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27263.390 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2043 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2043 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.3378 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.3378 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1360 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.5623E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.5264E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.3378 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.894 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.861 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.861 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.276 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 17.71 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 18.92 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.861 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
2 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
3 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
4 | 2 | 0.93400083E-12 | 0.71827744E-17 | 0.33026303E-17 | 0.0000000 |
5 | 1 | -5.2160660 | 0.53236032E-04 | -0.78408200E-04 | 0.17906231E-12 |
6 | 0 | 5.4203831 | 0.20426382 | 0.20439547 | |
7 | 4 | 0.81105908E-12 | -0.61566660E-16 | 0.53970606E-14 | 0.11182789E-15 |
8 | 3 | -0.39455327E-03 | 0.24003309E-06 | -0.57329053E-04 | 0.15561420E-12 |
9 | 2 | 1.7627212 | 0.51935632E-02 | 1.1580856 | -0.75642783E-04 |
10 | 1 | -7.0983380 | 0.13367505 | -17.210522 | 0.33785533 |
11 | 0 | 5.5597362 | 0.84856002E-01 | 16.276219 | |
12 | 4 | 0.81105908E-12 | -0.61566660E-16 | 0.53970606E-14 | 0.11182789E-15 |
13 | 3 | -0.39455327E-03 | 0.24003309E-06 | -0.57329053E-04 | 0.15561420E-12 |
14 | 2 | 1.7627212 | 0.51935632E-02 | 1.1580856 | -0.75642783E-04 |
15 | 1 | -7.0983380 | 0.13367505 | -17.210522 | 0.33785533 |
16 | 0 | 5.5597362 | 0.84856002E-01 | 16.276219 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.8391346 | 2.8391346 | 2.8391346 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.8391346 | 2.8391346 | 2.8391346 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.8391346 | 2.8391346 | 2.8391346 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8391346 | 2.8391346 | 2.8391346 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.31240856E-08 | -0.21887765E-14 | 0.14182747E-14 | -0.45258500E-16 |
55 | 6 | 0.39303604E-05 | 0.26006625E-08 | 0.31948254E-02 | -0.26800873E-04 |
56 | 5 | -0.27546567E-03 | 0.15375372E-05 | -0.22400621 | 0.19586362E-02 |
57 | 4 | 0.62896480E-02 | 0.69930755E-04 | 4.8342361 | -0.45310069E-01 |
58 | 3 | -0.55086064E-01 | 0.55565958E-03 | -38.047911 | 0.39894661 |
59 | 2 | 0.19539610 | 0.92379386E-03 | 116.53551 | -1.4186290 |
60 | 1 | -0.28189481 | 0.28115072E-03 | -143.93766 | 2.0495388 |
61 | 0 | 0.13740557 | 0.68297879E-05 | 60.838472 | |
62 | 7 | -0.76172223E-08 | 0.19992769E-15 | -0.36679418E-14 | 0.15936503E-16 |
63 | 6 | 0.20832875E-05 | 0.10921259E-08 | 0.32010154E-02 | -0.26852800E-04 |
64 | 5 | -0.12434769E-03 | 0.63986796E-06 | -0.22435781 | 0.19617397E-02 |
65 | 4 | 0.26900562E-02 | 0.28962460E-04 | 4.8400881 | -0.45366326E-01 |
66 | 3 | -0.23075003E-01 | 0.22921474E-03 | -38.080948 | 0.39931181 |
67 | 2 | 0.81154666E-01 | 0.37960809E-03 | 116.59978 | -1.4194888 |
68 | 1 | -0.11662584 | 0.11498440E-03 | -143.97548 | 2.0501605 |
69 | 0 | 0.56734574E-01 | 0.27738523E-05 | 60.838472 | |
70 | 7 | -0.81392023E-08 | 0.28718252E-15 | -0.25842544E-14 | 0.71742475E-17 |
71 | 6 | 0.20245979E-05 | 0.10259199E-08 | 0.32012942E-02 | -0.26855138E-04 |
72 | 5 | -0.11816234E-03 | 0.60006224E-06 | -0.22437362 | 0.19618793E-02 |
73 | 4 | 0.25345016E-02 | 0.27140048E-04 | 4.8403509 | -0.45368853E-01 |
74 | 3 | -0.21665828E-01 | 0.21464768E-03 | -38.082430 | 0.39932820 |
75 | 2 | 0.76088909E-01 | 0.35527252E-03 | 116.60266 | -1.4195273 |
76 | 1 | -0.10927342 | 0.10751462E-03 | -143.97718 | 2.0501884 |
77 | 0 | 0.53139756E-01 | 0.25964760E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.53970606E-14 | -0.61566660E-16 | 0.81105908E-12 | 0.11182789E-15 |
85 | 3 | -0.57329053E-04 | 0.24003309E-06 | -0.39455327E-03 | 0.15561420E-12 |
86 | 2 | 1.1580856 | 0.51935632E-02 | 1.7627212 | -0.75642783E-04 |
87 | 1 | -17.210522 | 0.13367505 | -7.0983380 | 0.33785533 |
88 | 0 | 16.276219 | 0.84856002E-01 | 5.5597362 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.43_SHGC_0.45 | 28 | 1 | VerySmooth | 2.443 | 0.445 | 0.367 | 0.451 |
2 | SKYLIGHT_U_0.6_SHGC_0.4 | 29 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 30 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.91147E-002 | 0.36619 | 0.42642 | 0.42642 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12243 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 8887.79565 | 10665.35478 | 0.74270 | 0.89124 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 25.80200 | 6.97981E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 11896.95197 | 14276.34236 | 0.33931 | 0.40717 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90000 | 6.45023E-005 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 18633.09894 | 22359.71873 | 1.21371 | 1.45646 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 26.99200 | 6.97981E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 37091.02843 | 44509.23412 | 0.89091 | 1.06909 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40000 | 6.97982E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 82856.12630 | 99427.35155 | 2.02628 | 2.43154 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 12881.91 | 0.89124 | 0.89124 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 16860.50 | 0.40717 | 0.40717 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 25707.12 | 1.45646 | 1.45646 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 60195.31 | 1.06909 | 1.06909 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.89124 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.45646 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.43154 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 2.43154 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 99427.35666 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 99427.35155 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.89124 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.89124 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.89124 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.89124 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.89124 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.89124 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.45646 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.45646 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.45646 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.45646 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.45646 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.45646 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.89124 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.45646 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.89124 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.89124 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.89124 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.89124 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.89124 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.89124 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.44562 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.89124 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 14753.18656 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 14753.19000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 7376.59500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 14753.19000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 14753.19000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27786.55417 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.89124 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1016.11197 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 27786.55417 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.45646 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.45646 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.45646 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.45646 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.45646 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.45646 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.72823 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.45646 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 24109.58451 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 27192.65000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13596.32500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 27192.65000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.75697 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.75697 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.75697 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.75697 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27192.65000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 71473.09442 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.45646 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1594.10118 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 71473.09442 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 14061.6 | 11.07 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 26062.0 | 15.81 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 7 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.3743479772 | 0.3608932178 | Pass | Pass | 0.8340780719 | 0.8135637572 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.9579705341 | 0.8617250191 | Pass | Pass | 0.6458937567 | 0.6102442648 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 2.4025375660E-003 | 9.5802378180E-003 | Pass | Pass | 3.8468565625E-002 | 4.4319774643E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.199 | 0.204 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.322 | 0.338 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.322 | 0.338 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.322 | 0.338 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.199 | 0.204 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.136 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.056 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.053 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.43_SHGC_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.443 | 0.445 | 0.451 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.43_SHGC_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.443 | 0.445 | 0.451 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.43_SHGC_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.443 | 0.445 | 0.451 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.43_SHGC_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.443 | 0.445 | 0.451 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 2.886 | 0.423 | 0.428 | ||||||||||||
North Total or Average | 6.51 | 2.443 | 0.445 | 0.451 | ||||||||||||
Non-North Total or Average | 26.02 | 2.996 | 0.417 | 0.422 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.992 | 2.839 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.992 | 2.839 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.992 | 2.839 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.992 | 2.839 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.992 | 2.839 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.6337 | 236.88 | 2518.90 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.62 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.5069 | 1393.41 | 11853.65 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 135.00 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.5069 | 3204.84 | 27263.39 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 310.50 |
Interior Lighting Total | 8.6111 | 4835.13 | 41635.94 | 476.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 6311.00 | AstronomicalClock | - | 83.06 | 83.06 | 98.39 | |
Exterior Lighting Total | 6311.00 | 98.39 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 14753.19 | 11782.78 | 2970.41 | 0.80 | 3.91 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27192.65 | 20584.02 | 6608.63 | 0.76 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 14061.6 | 11.07 | ||||
PSZ-FINE STORAGE COOLING COIL | 26062.0 | 15.81 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 99427.36 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 27786.55 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 71473.09 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.43 | 225.92 | 92.91 | 1.00 | 3.47 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 0.89 | 1016.11 | 1140.11 | 1.00 | 1.39 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 1.46 | 1594.10 | 1094.51 | 1.00 | 1.34 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8887.80 | 10665.35 | 45.02 | 0.743 | 0.891 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 23.90 | 23.90 | 0.00809 | 25.80 | 0.00698 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 18633.10 | 22359.72 | 16.05 | 1.214 | 1.456 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 26.70 | 26.70 | 0.00787 | 26.99 | 0.00698 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00384 | 27.40 | 0.00698 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11896.95 | 14276.34 | 60.27 | 0.339 | 0.407 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00806 | -41.90 | 0.00006 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 37091.03 | 44509.23 | 31.94 | 0.891 | 1.069 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.56 | 0.00756 | -41.90 | 0.00006 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 82856.13 | 99427.35 | 31.02 | 2.026 | 2.432 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 9.99 | 0.00775 | -41.90 | 0.00006 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.89 | 0.89 | 0.41 | 0.41 | 0.8912 | 0.8912 | 0.8912 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.46 | 1.46 | 1.07 | 1.07 | 1.4565 | 1.4565 | 1.4565 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 99427.357 | 99427.357 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 99427.36 | 99427.36 | 2.431539 | -10.85 | -10.85 | 0.00466209 | 43.33 | 26.90 | 0.01600000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 9.99 | 0.00774940 | 100.0000 | 99427.35 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 14753.190 | 0.000 | 0.891240 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 14753.19 | 14753.19 | 0.891240 | 24.14 | 15.81 | 0.00797440 | 12.00 | 11.12 | 0.00800000 | 25.97 | 0.00697981 | 15.59 | 11.4767 | 23.90 | 0.00809258 | 43.1725 | 8885.07 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 27786.554 | 27786.554 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 27786.55 | 27786.55 | 0.891240 | 5.24 | 5.24 | 0.00605369 | 40.00 | 20.97 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 11.4767 | 21.10 | 0.00806297 | 50.9939 | 11896.95 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 27192.650 | 0.000 | 1.456460 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 27192.65 | 27192.65 | 1.456460 | 26.85 | 16.45 | 0.00760778 | 12.00 | 11.12 | 0.00800000 | 27.20 | 0.00697982 | 16.03 | 29.1606 | 26.70 | 0.00786737 | 35.5439 | 18598.34 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 71473.094 | 71473.094 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 71473.09 | 71473.09 | 1.456458 | -7.27 | -7.27 | 0.00458234 | 40.00 | 20.97 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 29.1607 | 15.56 | 0.00756004 | 67.7540 | 37091.03 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 99427.357 | 99427.357 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1854 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 2.431539 | 2.88244142 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 99427.36 | 99427.36 | 1.0000 | 2.88244142 | 2.431539 | -10.85 | -10.85 | 0.00466209 | 658.2 | 43.33 | 26.90 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 99427.36 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 9.99 | 0.00774940 | 9.99 | 0.00774940 | 100.0000 | 99427.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 14753.190 | 0.000 | 0.891240 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6640 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 14753.19 | 14753.19 | 1.0000 | 1.05651092 | 0.891240 | 24.14 | 15.81 | 0.00797440 | 44555.8 | 12.00 | 11.12 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14753.19 | 25.97 | 0.00697981 | 15.59 | 0.10228487 | 11.4767 | 23.90 | 0.00810339 | 23.90 | 0.00809258 | 43.1725 | 8885.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27786.554 | 27786.554 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.891240 | 1.05651137 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 27786.55 | 27786.55 | 1.0000 | 1.05651137 | 0.891240 | 5.24 | 5.24 | 0.00605369 | 20461.9 | 40.00 | 20.97 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27786.55 | -41.90 | 0.00006450 | -41.90 | 0.10228487 | 11.4767 | 21.05 | 0.00806297 | 21.10 | 0.00806297 | 50.9939 | 11896.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27192.650 | 0.000 | 1.456460 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.9825 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 27192.65 | 27192.65 | 1.0000 | 1.72654491 | 1.456460 | 26.85 | 16.45 | 0.00760778 | 46381.3 | 12.00 | 11.12 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27192.65 | 27.20 | 0.00697982 | 16.03 | 0.42471267 | 29.1606 | 26.70 | 0.00786696 | 26.70 | 0.00786737 | 35.5439 | 18598.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 71473.094 | 71473.094 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.456458 | 1.72654243 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 71473.09 | 71473.09 | 1.0000 | 1.72654243 | 1.456458 | -7.27 | -7.27 | 0.00458234 | 4095.6 | 40.00 | 20.97 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 71473.09 | -41.90 | 0.00006450 | -41.90 | 0.42471267 | 29.1607 | 15.56 | 0.00756004 | 15.56 | 0.00756004 | 67.7540 | 37091.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2620.50 | 3347.67 | 2579.83 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2620.50 | 3347.67 | 2579.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 260.83 | 0.17 | 164.83 | 0.17 |
ZONE2 FINE STORAGE | 837.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 195.17 | 0.00 | 0.00 | 0.00 |
Facility | 1105.33 | 0.17 | 164.83 | 0.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.349 | 0.384 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 786.61 | 5421.86 | 19-MAR-12:20 | 57141.15 | 11-JAN-15:50 |
Electricity:Building | 615.41 | 4938.86 | 01-JAN-00:10 | 45301.66 | 02-JAN-09:10 |
Electricity:Zone:ZONE1 OFFICE | 62.57 | 1027.15 | 01-JAN-00:10 | 3852.05 | 02-JAN-08:10 |
InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.62 | 453.40 | 01-JAN-00:10 | 1939.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 417.84 | 2726.34 | 01-JAN-00:10 | 31374.00 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 310.51 | 2726.34 | 01-JAN-00:10 | 23173.88 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 28.43 | 483.00 | 01-JAN-19:20 | 3135.02 | 27-FEB-12:50 |
WaterSystems:Electricity | 28.43 | 483.00 | 01-JAN-19:20 | 3135.02 | 27-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 28.43 | 483.00 | 01-JAN-19:20 | 3135.02 | 27-FEB-12:50 |
Fans:Electricity | 42.24 | 0.00 | 18-MAR-17:10 | 2836.13 | 06-JAN-12:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 786.61 | 5421.86 | 19-MAR-12:20 | 57141.15 | 11-JAN-15:50 |
ElectricityPurchased:Plant | 786.61 | 5421.86 | 19-MAR-12:20 | 57141.15 | 11-JAN-15:50 |
Cogeneration:ElectricityPurchased | 786.61 | 5421.86 | 19-MAR-12:20 | 57141.15 | 11-JAN-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 786.61 | 5421.86 | 19-MAR-12:20 | 57141.15 | 11-JAN-15:50 |
ElectricityNet:Plant | 786.61 | 5421.86 | 19-MAR-12:20 | 57141.15 | 11-JAN-15:50 |
Cogeneration:ElectricityNet | 786.61 | 5421.86 | 19-MAR-12:20 | 57141.15 | 11-JAN-15:50 |
Electricity:HVAC | 44.37 | 0.00 | 18-MAR-17:10 | 8405.22 | 21-JUL-16:00 |
General:Fans:Electricity | 42.24 | 0.00 | 18-MAR-17:10 | 2836.13 | 06-JAN-12:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 2.14 | 0.00 | 01-JAN-00:10 | 5795.01 | 21-JUL-16:00 |
ExteriorLights:Electricity | 98.39 | 0.00 | 01-JAN-11:20 | 6311.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 98.39 | 0.00 | 01-JAN-11:20 | 6311.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1676.50 | 0.00 | 18-MAR-17:10 | 248358.76 | 30-JAN-06:20 |
Gas:HVAC | 1676.50 | 0.00 | 18-MAR-17:10 | 248358.76 | 30-JAN-06:20 |
Heating:Gas | 1676.50 | 0.00 | 18-MAR-17:10 | 248358.76 | 30-JAN-06:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2445.74 | 0.00 | 18-MAR-17:10 | 378334.85 | 23-FEB-17:10 |
EnergyTransfer:Building | 1150.54 | 0.00 | 18-MAR-17:10 | 179647.85 | 23-FEB-17:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 87.71 | 0.00 | 01-JAN-00:40 | 24595.18 | 02-JAN-07:10 |
Heating:EnergyTransfer | 1132.04 | 0.00 | 18-MAR-17:10 | 179647.85 | 23-FEB-17:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 80.96 | 0.00 | 01-JAN-00:40 | 24595.18 | 02-JAN-07:10 |
Cooling:EnergyTransfer | 18.50 | 0.00 | 01-JAN-00:10 | 16540.98 | 21-JUL-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 6.75 | 0.00 | 01-JAN-00:10 | 6151.41 | 21-JUL-16:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 313.97 | 0.00 | 01-JAN-00:40 | 59246.53 | 01-APR-19:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 302.21 | 0.00 | 01-JAN-00:40 | 59246.53 | 01-APR-19:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 11.75 | 0.00 | 01-JAN-00:10 | 10389.57 | 21-JUL-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 748.87 | 0.00 | 21-JAN-13:10 | 100500.13 | 25-FEB-12:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 748.87 | 0.00 | 21-JAN-13:10 | 100500.13 | 25-FEB-12:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1295.20 | 0.00 | 18-MAR-17:10 | 198687.01 | 30-JAN-06:20 |
HeatingCoils:EnergyTransfer | 1286.43 | 0.00 | 18-MAR-17:10 | 198687.01 | 30-JAN-06:20 |
CoolingCoils:EnergyTransfer | 8.77 | 0.00 | 01-JAN-00:10 | 21204.35 | 21-JUL-16:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 80.954 | -6.752 | 0.000 | 0.000 | 4.065 | 30.619 | 31.946 | 7.026 | 0.000 | 0.047 | 0.000 | 0.000 | -18.479 | 0.000 | -45.212 | -84.215 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 302.214 | -11.750 | 0.000 | 0.000 | 0.000 | 135.003 | 0.000 | 0.000 | 0.000 | 0.062 | 0.002 | 0.000 | 0.000 | 0.000 | -163.765 | -261.764 |
ZONE3 BULK STORAGE | 748.865 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 310.507 | 107.336 | 9.436 | 0.000 | 1.909 | 0.000 | 0.000 | -19.610 | 0.000 | -591.598 | -566.846 |
Total Facility | 748.865 | 0.000 | 383.169 | -18.503 | 0.000 | 0.000 | 4.065 | 476.129 | 139.282 | 16.463 | 0.000 | 2.018 | 0.002 | 0.000 | -38.089 | 0.000 | -800.574 | -912.825 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 14-JUL-05:02 | 0.00 | 0.00 | 0.00 | -14470.76 | 0.00 | 0.00 | 34.73 | 579.35 | 573.75 | 287.04 | 0.00 | 0.00 | 13650.98 | 0.00 | -0.00 | 0.00 | -655.08 | 0.00 |
ZONE2 FINE STORAGE | 23-JUL-14:45 | 0.00 | 0.00 | 0.00 | -12089.42 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 11339.69 | 0.00 | -0.00 | 0.00 | -435.64 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-JUL-16:00 | 0.00 | 0.00 | 0.00 | -16539.02 | 0.00 | 0.00 | 357.67 | 31277.33 | 10112.62 | 2961.61 | 0.00 | 22182.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -50352.91 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 01-MAY-05:01 | 0.00 | 0.00 | 26963.79 | 0.00 | 0.00 | 0.00 | 57.07 | 579.35 | 573.75 | 298.30 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -736.33 | -27735.93 |
ZONE2 FINE STORAGE | 09-FEB-02:62 | 0.00 | 0.00 | 67490.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -12899.41 | -55776.31 |
ZONE3 BULK STORAGE | 27-FEB-15:05 | 100622.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1315.79 | 0.00 | -107043.59 | -23636.97 |
Total Facility | 25-MAR-05:01 | 99655.39 | 0.00 | 84285.29 | 0.00 | 0.00 | 0.00 | 58.01 | 4491.05 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1961.57 | 0.00 | -106818.51 | -82333.44 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.8912 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.8912 | 0.1148 | 1.0000 | 0.1023 | 0.1148 | ||
PSZ-FINE STORAGE | 1.4565 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.4565 | 0.2916 | 1.0000 | 0.4247 | 0.2916 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.8912 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.8912 | 1.0000 | 1.0000 | 0.1023 | 0.1148 | ||
PSZ-FINE STORAGE | 1.4565 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.4565 | 1.0000 | 1.0000 | 0.4247 | 0.2916 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.8912 | 0.8912 | 0.8912 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.4565 | 1.4565 | 1.4565 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.8912 | 0.8912 | 0.8912 | 0.8912 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.4565 | 1.4565 | 1.4565 | 1.4565 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.8912 | 0.8912 | 0.8912 | 0.1023 | 0.2512 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.4565 | 1.4565 | 1.4565 | 0.4247 | 0.3973 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.8912 | 0.8912 | 0.8912 | 0.8912 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.4565 | 1.4565 | 1.4565 | 1.4565 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 164.83 |
Number of hours cooling loads not met | 0.17 |
Number of hours not met | 165.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 1676.50 | 248358.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 2.14 | 5795.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 476.13 | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 98.39 | 6311.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 42.24 | 2836.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 28.43 | 3135.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 786.61 |
Natural Gas | 0.00 | 1676.50 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 2463.11 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 98.47 |
Space Heating | 0.00 |
Space Cooling | 0.44 |
Fans (All) | 8.74 |
Service Water Heating | 5.88 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 162.69 |
Subtotal | 162.69 |
Natural Gas [MJ/m2] | |
Space Heating | 346.73 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 346.73 |
Subtotal | 346.73 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 19.33 |
Space Heating | 68.06 |
Space Cooling | 0.09 |
Fans (All) | 1.71 |
Service Water Heating | 1.15 |
Receptacle Equipment | 5.65 |
Miscellaneous | 3.99 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.316601E+12 |
February | 0.000 | 0.270109E+12 |
March | 0.000 | 0.262311E+12 |
April | 0.000 | 0.124999E+12 |
May | 0.000 | 0.692831E+10 |
June | 0.000 | 0.210591E+09 |
July | 0.000 | 0.471547E+08 |
August | 0.000 | 0.437072E+09 |
September | 0.000 | 0.112919E+11 |
October | 0.000 | 0.148668E+12 |
November | 0.000 | 0.223922E+12 |
December | 0.000 | 0.310980E+12 |
Annual Sum or Average | 0.167650E+13 | |
Minimum of Months | 0.000 | 0.471547E+08 |
Maximum of Months | 0.000 | 0.316601E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.316601E+12 |
February | 0.000 | 0.270109E+12 |
March | 0.000 | 0.262311E+12 |
April | 0.000 | 0.124999E+12 |
May | 0.000 | 0.692831E+10 |
June | 0.000 | 0.210591E+09 |
July | 0.000 | 0.471547E+08 |
August | 0.000 | 0.437072E+09 |
September | 0.000 | 0.112919E+11 |
October | 0.000 | 0.148668E+12 |
November | 0.000 | 0.223922E+12 |
December | 0.000 | 0.310980E+12 |
Annual Sum or Average | 0.167650E+13 | |
Minimum of Months | 0.000 | 0.471547E+08 |
Maximum of Months | 0.000 | 0.316601E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.316601E+12 |
February | 0.000 | 0.270109E+12 |
March | 0.000 | 0.262311E+12 |
April | 0.000 | 0.124999E+12 |
May | 0.000 | 0.692831E+10 |
June | 0.000 | 0.210591E+09 |
July | 0.000 | 0.471547E+08 |
August | 0.000 | 0.437072E+09 |
September | 0.000 | 0.112919E+11 |
October | 0.000 | 0.148668E+12 |
November | 0.000 | 0.223922E+12 |
December | 0.000 | 0.310980E+12 |
Annual Sum or Average | 0.167650E+13 | |
Minimum of Months | 0.000 | 0.471547E+08 |
Maximum of Months | 0.000 | 0.316601E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.316601E+12 |
February | 0.000 | 0.270109E+12 |
March | 0.000 | 0.262311E+12 |
April | 0.000 | 0.124999E+12 |
May | 0.000 | 0.692831E+10 |
June | 0.000 | 0.210591E+09 |
July | 0.000 | 0.471547E+08 |
August | 0.000 | 0.437072E+09 |
September | 0.000 | 0.112919E+11 |
October | 0.000 | 0.148668E+12 |
November | 0.000 | 0.223922E+12 |
December | 0.000 | 0.310980E+12 |
Annual Sum or Average | 0.167650E+13 | |
Minimum of Months | 0.000 | 0.471547E+08 |
Maximum of Months | 0.000 | 0.316601E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.316601E+12 |
February | 0.000 | 0.270109E+12 |
March | 0.000 | 0.262311E+12 |
April | 0.000 | 0.124999E+12 |
May | 0.000 | 0.692831E+10 |
June | 0.000 | 0.210591E+09 |
July | 0.000 | 0.471547E+08 |
August | 0.000 | 0.437072E+09 |
September | 0.000 | 0.112919E+11 |
October | 0.000 | 0.148668E+12 |
November | 0.000 | 0.223922E+12 |
December | 0.000 | 0.310980E+12 |
Annual Sum or Average | 0.167650E+13 | |
Minimum of Months | 0.000 | 0.471547E+08 |
Maximum of Months | 0.000 | 0.316601E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.316601E+12 |
February | 0.000 | 0.270109E+12 |
March | 0.000 | 0.262311E+12 |
April | 0.000 | 0.124999E+12 |
May | 0.000 | 0.692831E+10 |
June | 0.000 | 0.210591E+09 |
July | 0.000 | 0.471547E+08 |
August | 0.000 | 0.437072E+09 |
September | 0.000 | 0.112919E+11 |
October | 0.000 | 0.148668E+12 |
November | 0.000 | 0.223922E+12 |
December | 0.000 | 0.310980E+12 |
Annual Sum or Average | 0.167650E+13 | |
Minimum of Months | 0.000 | 0.471547E+08 |
Maximum of Months | 0.000 | 0.316601E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.316601E+12 |
February | 0.000 | 0.270109E+12 |
March | 0.000 | 0.262311E+12 |
April | 0.000 | 0.124999E+12 |
May | 0.000 | 0.692831E+10 |
June | 0.000 | 0.210591E+09 |
July | 0.000 | 0.471547E+08 |
August | 0.000 | 0.437072E+09 |
September | 0.000 | 0.112919E+11 |
October | 0.000 | 0.148668E+12 |
November | 0.000 | 0.223922E+12 |
December | 0.000 | 0.310980E+12 |
Annual Sum or Average | 0.167650E+13 | |
Minimum of Months | 0.000 | 0.471547E+08 |
Maximum of Months | 0.000 | 0.316601E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.316601E+12 |
February | 0.000 | 0.270109E+12 |
March | 0.000 | 0.262311E+12 |
April | 0.000 | 0.124999E+12 |
May | 0.000 | 0.692831E+10 |
June | 0.000 | 0.210591E+09 |
July | 0.000 | 0.471547E+08 |
August | 0.000 | 0.437072E+09 |
September | 0.000 | 0.112919E+11 |
October | 0.000 | 0.148668E+12 |
November | 0.000 | 0.223922E+12 |
December | 0.000 | 0.310980E+12 |
Annual Sum or Average | 0.167650E+13 | |
Minimum of Months | 0.000 | 0.471547E+08 |
Maximum of Months | 0.000 | 0.316601E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.316601E+12 |
February | 0.000 | 0.270109E+12 |
March | 0.000 | 0.262311E+12 |
April | 0.000 | 0.124999E+12 |
May | 0.000 | 0.692831E+10 |
June | 0.000 | 0.210591E+09 |
July | 0.000 | 0.471547E+08 |
August | 0.000 | 0.437072E+09 |
September | 0.000 | 0.112919E+11 |
October | 0.000 | 0.148668E+12 |
November | 0.000 | 0.223922E+12 |
December | 0.000 | 0.310980E+12 |
Annual Sum or Average | 0.167650E+13 | |
Minimum of Months | 0.000 | 0.471547E+08 |
Maximum of Months | 0.000 | 0.316601E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 | -15.4 | 0.193597E+09 | 236.59 | 21-JAN-08:20 | -7.0 | -7.3 |
February | 12289.28 | 143.37 | 27-FEB-13:06 | -29.8 | -30.0 | 0.178565E+09 | 236.59 | 14-FEB-13:30 | -2.5 | -3.9 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -28.9 | -29.1 | 0.209992E+09 | 236.59 | 21-MAR-14:09 | 1.60 | 0.56 |
April | 3415445.04 | 225.37 | 29-APR-15:50 | 10.37 | 4.77 | 0.195522E+09 | 268.72 | 22-APR-15:00 | 15.00 | 6.58 |
May | 46216257.14 | 1269.54 | 13-MAY-15:50 | 20.00 | 9.29 | 0.215609E+09 | 303.27 | 11-MAY-15:39 | 18.90 | 8.70 |
June | 0.172280E+10 | 13830.12 | 22-JUN-05:03 | 14.08 | 11.46 | 0.252994E+09 | 301.60 | 24-JUN-10:39 | 12.80 | 12.15 |
July | 0.294058E+10 | 14470.61 | 14-JUL-05:02 | 11.88 | 10.56 | 0.246829E+09 | 301.61 | 03-JUL-14:00 | 19.40 | 18.27 |
August | 0.195904E+10 | 14174.65 | 05-AUG-05:02 | 13.98 | 12.00 | 0.259752E+09 | 301.60 | 12-AUG-15:09 | 20.40 | 15.08 |
September | 80116281.97 | 1034.16 | 02-SEP-16:00 | 16.70 | 10.41 | 0.200872E+09 | 301.58 | 02-SEP-14:00 | 16.70 | 10.79 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.11 | 0.194949E+09 | 236.59 | 07-OCT-07:19 | 4.63 | 3.88 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -10.0 | -10.8 | 0.186507E+09 | 236.59 | 18-NOV-08:09 | -11.6 | -12.0 |
December | 19488.65 | 324.81 | 15-DEC-13:06 | -32.7 | -32.9 | 0.193811E+09 | 236.59 | 23-DEC-08:20 | -2.4 | -3.8 |
Annual Sum or Average | 0.675220E+10 | 0.252900E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -32.7 | -32.9 | 0.178565E+09 | 236.59 | -11.6 | -12.0 | ||
Maximum of Months | 0.294058E+10 | 14470.61 | 20.00 | 12.00 | 0.259752E+09 | 303.27 | 20.40 | 18.27 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 0.189365E+09 | 4365.84 | 22-MAR-12:30 | 3.85 | 1.25 | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.1 |
April | 0.117956E+10 | 7585.01 | 27-APR-06:07 | -1.5 | -3.0 | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.2 |
May | 0.123194E+10 | 6505.91 | 27-MAY-06:07 | 0.50 | -0.6 | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.17 |
June | 0.163479E+10 | 5028.12 | 17-JUN-06:10 | 9.08 | 7.63 | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.13 |
July | 0.233083E+10 | 12089.64 | 23-JUL-14:45 | 25.50 | 15.45 | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 |
August | 0.262418E+10 | 6887.42 | 31-AUG-06:05 | -1.5 | -2.7 | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.82 |
September | 0.217702E+10 | 7608.24 | 25-SEP-06:07 | -1.8 | -2.8 | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 |
October | 0.382653E+09 | 7230.66 | 03-OCT-06:07 | -0.9 | -1.3 | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.11 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -10.0 | -10.8 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.8 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.117503E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.00 | 0.00 | -28.9 | -29.1 | ||
Maximum of Months | 0.262418E+10 | 12089.64 | 25.50 | 15.45 | 0.00 | 0.00 | 16.35 | 13.77 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -28.9 | -29.1 | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.1 |
April | 0.00 | 0.00 | 01-APR-00:05 | -11.7 | -13.2 | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 | 2.17 | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.13 | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.13 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.82 | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.82 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.11 | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.11 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -10.0 | -10.8 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.8 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.1 | 0.00 | 0.00 | -28.9 | -29.1 | ||
Maximum of Months | 0.00 | 0.00 | 16.35 | 13.77 | 0.00 | 0.00 | 16.35 | 13.77 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143064E+11 | 25885.26 | 19-JAN-06:11 | -2.8 |
February | 0.121559E+11 | 26194.52 | 09-FEB-06:01 | 0.00 |
March | 0.117220E+11 | 26565.51 | 23-MAR-05:32 | -2.8 |
April | 0.587949E+10 | 26224.68 | 15-APR-05:42 | -3.8 |
May | 0.176615E+10 | 26963.73 | 01-MAY-05:01 | 7.30 |
June | 0.156703E+09 | 25876.56 | 01-JUN-05:02 | 7.20 |
July | 34513367.68 | 3313.08 | 05-JUL-06:20 | 8.30 |
August | 0.243757E+09 | 25362.91 | 31-AUG-05:01 | -1.2 |
September | 0.240957E+10 | 26922.42 | 19-SEP-05:01 | 9.60 |
October | 0.698502E+10 | 26910.72 | 04-OCT-05:01 | 7.70 |
November | 0.116600E+11 | 25562.74 | 10-NOV-06:31 | -16.1 |
December | 0.136356E+11 | 25748.25 | 23-DEC-06:11 | -3.7 |
Annual Sum or Average | 0.809551E+11 | |||
Minimum of Months | 34513367.68 | 3313.08 | -16.1 | |
Maximum of Months | 0.143064E+11 | 26963.73 | 9.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.570935E+11 | 64062.68 | 06-JAN-22:02 | -3.7 |
February | 0.476001E+11 | 67490.52 | 09-FEB-02:62 | 2.70 |
March | 0.448974E+11 | 65947.99 | 22-MAR-21:23 | 1.95 |
April | 0.248117E+11 | 66095.50 | 09-APR-18:33 | 2.23 |
May | 0.245399E+10 | 65453.91 | 28-MAY-03:23 | 1.15 |
June | 64038418.21 | 1393.50 | 29-JUN-16:20 | 25.93 |
July | 14139143.90 | 1053.97 | 06-JUL-17:00 | 23.90 |
August | 49727474.57 | 1748.22 | 23-AUG-17:00 | 25.00 |
September | 0.308831E+10 | 64029.36 | 30-SEP-21:53 | -0.2 |
October | 0.282759E+11 | 65336.84 | 16-OCT-01:02 | -1.1 |
November | 0.405527E+11 | 64162.38 | 03-NOV-18:22 | -5.6 |
December | 0.533133E+11 | 65668.88 | 24-DEC-00:42 | -0.2 |
Annual Sum or Average | 0.302215E+12 | |||
Minimum of Months | 14139143.90 | 1053.97 | -5.6 | |
Maximum of Months | 0.570935E+11 | 67490.52 | 25.93 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143621E+12 | 100494.59 | 28-JAN-09:40 | -20.4 |
February | 0.124536E+12 | 100622.38 | 27-FEB-15:05 | -28.1 |
March | 0.123786E+12 | 100115.85 | 16-MAR-08:00 | -21.7 |
April | 0.567416E+11 | 99982.23 | 01-APR-18:45 | -6.3 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 24957663.32 | 11087.04 | 30-SEP-04:55 | -4.4 |
October | 0.652397E+11 | 99673.43 | 27-OCT-04:00 | -17.8 |
November | 0.926922E+11 | 99702.20 | 10-NOV-01:50 | -20.3 |
December | 0.142225E+12 | 100328.29 | 22-DEC-14:00 | -23.9 |
Annual Sum or Average | 0.748866E+12 | |||
Minimum of Months | 0.00 | 0.00 | -28.1 | |
Maximum of Months | 0.143621E+12 | 100622.38 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.256100E+10 | 1939.55 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.233575E+10 | 1939.55 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.266872E+10 | 1939.55 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.252182E+10 | 1939.55 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.261486E+10 | 1939.55 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.257569E+10 | 1939.55 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.256100E+10 | 1939.55 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.266872E+10 | 1939.55 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.252182E+10 | 1939.55 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.256100E+10 | 1939.55 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.246796E+10 | 1939.55 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.256100E+10 | 1939.55 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.306193E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.233575E+10 | 1939.55 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.266872E+10 | 1939.55 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112294E+11 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102778E+11 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.118738E+11 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.111270E+11 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.115516E+11 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.114492E+11 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112294E+11 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.118738E+11 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.111270E+11 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112294E+11 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108048E+11 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112294E+11 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135003E+12 | ||||
Minimum of Months | 0.102778E+11 | 10075.60 | 0.00 | 0.00 | |
Maximum of Months | 0.118738E+11 | 10075.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.258277E+11 | 23173.88 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.236390E+11 | 23173.88 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.273097E+11 | 23173.88 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.255921E+11 | 23173.88 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.265687E+11 | 23173.88 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.263332E+11 | 23173.88 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.258277E+11 | 23173.88 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.273097E+11 | 23173.88 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.255921E+11 | 23173.88 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.258277E+11 | 23173.88 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.248511E+11 | 23173.88 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.258277E+11 | 23173.88 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.236390E+11 | 23173.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.273097E+11 | 23173.88 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650220E+10 |
February | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509333E+10 |
March | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582852E+10 |
April | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359902E+10 |
May | 0.565842E+09 | 0.261486E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192994E+10 |
June | 0.565842E+09 | 0.257569E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15142119.76 | 0.124066E+10 |
July | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26078644.84 | 0.999569E+09 |
August | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5747979.51 | 0.161505E+10 |
September | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215762E+10 |
October | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426023E+10 |
November | 0.522316E+09 | 0.246796E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562734E+10 |
December | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635821E+10 |
Annual Sum or Average | 0.659424E+10 | 0.306193E+11 | 0.319458E+11 | 46968744.11 | 0.452117E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.999569E+09 |
Maximum of Months | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26078644.84 | 0.650220E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202553E+11 |
February | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168307E+11 |
March | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245992E+11 |
April | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216151E+11 |
May | 0.00 | 0.115516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6150382.38 | 0.962999E+10 |
June | 0.00 | 0.114492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5929445.06 | 0.698050E+10 |
July | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41916399.81 | 0.636810E+10 |
August | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7873227.12 | 0.779345E+10 |
September | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710091E+10 |
October | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191155E+11 |
November | 0.00 | 0.108048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772607E+10 |
December | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157500E+11 |
Annual Sum or Average | 0.135003E+12 | 61869454.37 | 0.163765E+12 | ||||||
Minimum of Months | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636810E+10 |
Maximum of Months | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41916399.81 | 0.245992E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567243E+11 |
February | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466793E+11 |
March | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658538E+11 |
April | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60319246.53 | 0.478980E+11 |
May | 0.00 | 0.265687E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795919E+09 | 0.216409E+11 |
June | 0.00 | 0.263332E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337558E+09 | 0.177356E+11 |
July | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119274E+09 | 0.206164E+11 |
August | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100390E+09 | 0.277068E+11 |
September | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224414E+11 |
October | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21602832.81 | 0.473887E+11 |
November | 0.00 | 0.248511E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217002E+11 |
December | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473323E+11 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | 0.143506E+10 | 0.443718E+12 | |||||
Minimum of Months | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177356E+11 |
Maximum of Months | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795919E+09 | 0.658538E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1939.55 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 25204.53 | 12-JAN-07:03 |
February | 659.25 | 01-FEB-08:09 | 1939.55 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 22955.60 | 27-FEB-07:01 |
March | 659.25 | 01-MAR-08:09 | 1939.55 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 21299.85 | 01-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1939.55 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 18249.84 | 03-APR-06:03 |
May | 659.25 | 01-MAY-07:10 | 1939.55 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 7739.03 | 16-MAY-07:00 |
June | 659.25 | 01-JUN-07:10 | 1939.55 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 793.81 | 29-JUN-16:10 | 5151.28 | 02-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 1939.55 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2233.00 | 21-JUL-16:10 | 5535.28 | 17-JUL-06:03 |
August | 659.25 | 01-AUG-07:10 | 1939.55 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 677.28 | 11-AUG-16:10 | 9176.73 | 31-AUG-06:05 |
September | 659.25 | 01-SEP-07:10 | 1939.55 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 10659.99 | 29-SEP-07:00 |
October | 659.25 | 02-OCT-07:10 | 1939.55 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 17572.01 | 31-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1939.55 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 20626.71 | 29-NOV-07:03 |
December | 659.25 | 01-DEC-08:09 | 1939.55 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 23261.66 | 15-DEC-12:02 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5151.28 | |||||
Maximum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2233.00 | 25204.53 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 68812.19 | 28-JAN-16:02 |
February | 0.00 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 43310.26 | 23-FEB-17:00 |
March | 0.00 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 32926.70 | 25-MAR-15:10 |
April | 0.00 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 36968.11 | 01-APR-18:51 |
May | 0.00 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1243.24 | 30-MAY-18:00 | 19033.00 | 27-MAY-08:00 |
June | 0.00 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 694.59 | 30-JUN-15:10 | 14561.81 | 24-JUN-21:00 |
July | 0.00 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5671.32 | 21-JUL-16:00 | 8944.39 | 04-JUL-17:00 |
August | 0.00 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1182.82 | 23-AUG-18:00 | 14371.10 | 29-AUG-20:00 |
September | 0.00 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 10573.92 | 29-SEP-07:00 |
October | 0.00 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 24581.45 | 27-OCT-06:10 |
November | 0.00 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 24069.39 | 03-NOV-20:00 |
December | 0.00 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 27946.11 | 21-DEC-18:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8944.39 | |||
Maximum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5671.32 | 68812.19 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23173.88 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 154695.15 | 28-JAN-15:00 |
February | 0.00 | 23173.88 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 107995.47 | 25-FEB-12:00 |
March | 0.00 | 23173.88 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 86417.19 | 25-MAR-09:00 |
April | 0.00 | 23173.88 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2668.10 | 22-APR-14:00 | 81187.31 | 01-APR-18:51 |
May | 0.00 | 23173.88 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12721.49 | 30-MAY-18:00 | 53118.65 | 27-MAY-11:00 |
June | 0.00 | 23173.88 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8867.82 | 03-JUN-16:00 | 40965.52 | 24-JUN-21:00 |
July | 0.00 | 23173.88 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12216.00 | 21-JUL-16:00 | 25560.64 | 04-JUL-17:00 |
August | 0.00 | 23173.88 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5718.61 | 23-AUG-18:00 | 51096.78 | 31-AUG-09:00 |
September | 0.00 | 23173.88 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 27491.55 | 21-SEP-14:00 |
October | 0.00 | 23173.88 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2410.99 | 01-OCT-15:40 | 61480.77 | 31-OCT-09:00 |
November | 0.00 | 23173.88 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 62430.64 | 01-NOV-09:00 |
December | 0.00 | 23173.88 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 87385.51 | 22-DEC-14:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25560.64 | ||||
Maximum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 12721.49 | 154695.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 3173.81 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788.86 |
February | 143.37 | 27-FEB-13:06 | 4614.75 | 13576.87 | 13387.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2992.04 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 1813.61 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.80 |
April | 225.37 | 29-APR-15:50 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 761.90 |
May | 1269.54 | 13-MAY-15:50 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.62 |
June | 13830.12 | 22-JUN-05:03 | 290.07 | 2317.39 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 642.17 |
July | 14470.61 | 14-JUL-05:02 | 362.59 | 2896.74 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 655.08 |
August | 14174.65 | 05-AUG-05:02 | 362.59 | 2896.74 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.22 |
September | 1034.16 | 02-SEP-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.62 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 453.40 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.06 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 906.80 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 660.92 |
December | 324.81 | 15-DEC-13:06 | 6592.50 | 19395.53 | 19125.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3662.81 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 453.40 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.62 | |
Maximum of Months | 14470.61 | 6592.50 | 19395.53 | 19125.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3662.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 8297.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13451.47 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 5926.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10047.37 |
March | 4365.84 | 22-MAR-12:30 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 930.79 |
April | 7585.01 | 27-APR-06:07 | 0.00 | 21336.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8398.38 |
May | 6505.91 | 27-MAY-06:07 | 0.00 | 21336.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15324.17 |
June | 5028.12 | 17-JUN-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12089.64 | 23-JUL-14:45 | 0.00 | 2370.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.64 |
August | 6887.42 | 31-AUG-06:05 | 0.00 | 14224.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8738.91 |
September | 7608.24 | 25-SEP-06:07 | 0.00 | 21336.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7083.43 |
October | 7230.66 | 03-OCT-06:07 | 0.00 | 21336.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9142.44 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 2370.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11387.37 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 5926.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2370.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12089.64 | 0.00 | 21336.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15324.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 19084.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32523.69 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 13631.69 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24987.92 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 10905.36 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12746.07 |
April | 0.00 | 01-APR-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44238.20 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5938.14 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3881.92 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6309.65 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12416.11 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7955.36 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13848.22 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25993.98 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 13631.69 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 19084.37 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44238.20 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.716976E+11 | 57141.15 | 11-JAN-15:50 | 0.316601E+12 | 248358.76 | 30-JAN-06:19 |
February | 0.633118E+11 | 56179.61 | 10-FEB-09:09 | 0.270109E+12 | 248358.76 | 24-FEB-06:10 |
March | 0.700045E+11 | 52220.32 | 16-MAR-07:10 | 0.262311E+12 | 241272.43 | 14-MAR-06:10 |
April | 0.628734E+11 | 50830.21 | 04-APR-12:50 | 0.124999E+12 | 218844.92 | 02-APR-23:49 |
May | 0.619839E+11 | 51005.07 | 13-MAY-14:00 | 0.692831E+10 | 47155.89 | 27-MAY-06:10 |
June | 0.600835E+11 | 53559.15 | 30-JUN-14:00 | 0.210591E+09 | 9503.86 | 01-JUN-06:10 |
July | 0.603231E+11 | 54865.38 | 29-JUL-14:00 | 47154678.24 | 5837.23 | 05-JUL-06:19 |
August | 0.653442E+11 | 52354.42 | 04-AUG-14:39 | 0.437072E+09 | 23263.01 | 31-AUG-06:19 |
September | 0.632598E+11 | 50233.47 | 02-SEP-14:20 | 0.112919E+11 | 59129.94 | 30-SEP-05:10 |
October | 0.673787E+11 | 56161.72 | 31-OCT-08:09 | 0.148668E+12 | 219387.85 | 31-OCT-05:10 |
November | 0.678155E+11 | 56992.36 | 30-NOV-15:39 | 0.223922E+12 | 232031.98 | 29-NOV-07:00 |
December | 0.725322E+11 | 57140.59 | 30-DEC-15:39 | 0.310980E+12 | 236563.61 | 01-DEC-17:00 |
Annual Sum or Average | 0.786608E+12 | 0.167650E+13 | ||||
Minimum of Months | 0.600835E+11 | 50233.47 | 47154678.24 | 5837.23 | ||
Maximum of Months | 0.725322E+11 | 57141.15 | 0.316601E+12 | 248358.76 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.396181E+11 | 0.135787E+11 | 0.115358E+11 | 0.00 | 0.452953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243538E+10 | 0.00 |
February | 0.362526E+11 | 0.101594E+11 | 0.105871E+11 | 0.00 | 0.409672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221590E+10 | 0.00 |
March | 0.418523E+11 | 0.886443E+10 | 0.123357E+11 | 0.00 | 0.443899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251316E+10 | 0.00 |
April | 0.392410E+11 | 0.624032E+10 | 0.114862E+11 | 0.00 | 0.351875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238719E+10 | 0.00 |
May | 0.407352E+11 | 0.407817E+10 | 0.119357E+11 | 0.00 | 0.276477E+10 | 0.00 | 0.00 | 8421204.11 | 0.00 | 0.00 | 0.00 | 0.246160E+10 | 0.00 |
June | 0.403581E+11 | 0.227196E+10 | 0.118862E+11 | 0.00 | 0.268883E+10 | 0.00 | 0.00 | 0.511303E+09 | 0.00 | 0.00 | 0.00 | 0.236723E+10 | 0.00 |
July | 0.396181E+11 | 0.315802E+10 | 0.115358E+11 | 0.00 | 0.259012E+10 | 0.00 | 0.00 | 0.108499E+10 | 0.00 | 0.00 | 0.00 | 0.233611E+10 | 0.00 |
August | 0.418523E+11 | 0.544892E+10 | 0.123357E+11 | 0.00 | 0.279372E+10 | 0.00 | 0.00 | 0.528976E+09 | 0.00 | 0.00 | 0.00 | 0.238465E+10 | 0.00 |
September | 0.392410E+11 | 0.757699E+10 | 0.114862E+11 | 0.00 | 0.268060E+10 | 0.00 | 0.00 | 1566623.47 | 0.00 | 0.00 | 0.00 | 0.227345E+10 | 0.00 |
October | 0.396181E+11 | 0.102200E+11 | 0.115358E+11 | 0.00 | 0.366305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234173E+10 | 0.00 |
November | 0.381239E+11 | 0.122572E+11 | 0.110862E+11 | 0.00 | 0.405469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229340E+10 | 0.00 |
December | 0.396181E+11 | 0.145405E+11 | 0.115358E+11 | 0.00 | 0.441962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241816E+10 | 0.00 |
Annual Sum or Average | 0.476129E+12 | 0.983948E+11 | 0.139282E+12 | 0.422394E+11 | 0.00 | 0.213525E+10 | 0.284280E+11 | ||||||
Minimum of Months | 0.362526E+11 | 0.227196E+10 | 0.105871E+11 | 0.00 | 0.259012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221590E+10 | 0.00 |
Maximum of Months | 0.418523E+11 | 0.145405E+11 | 0.123357E+11 | 0.00 | 0.452953E+10 | 0.00 | 0.00 | 0.108499E+10 | 0.00 | 0.00 | 0.00 | 0.251316E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.316601E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.270109E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.262311E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.124999E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.692831E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.210591E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 47154678.24 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.437072E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.112919E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.148668E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.223922E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.310980E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167650E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 47154678.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.316601E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35189.04 | 02-JAN-09:09 | 6311.00 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 2836.13 | 02-JAN-07:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35189.04 | 01-FEB-09:09 | 6311.00 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 2836.13 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35189.04 | 01-MAR-09:09 | 6311.00 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 2836.13 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35189.04 | 01-APR-08:09 | 6311.00 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 2836.13 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35189.04 | 01-MAY-08:09 | 6311.00 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 2610.21 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35189.04 | 01-JUN-08:09 | 6311.00 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 2610.21 | 21-JUN-14:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35189.04 | 01-JUL-08:09 | 6311.00 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 2610.21 | 11-JUL-11:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35189.04 | 01-AUG-08:09 | 6311.00 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 2610.21 | 02-AUG-12:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35189.04 | 01-SEP-08:09 | 6311.00 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 2610.21 | 05-SEP-06:49 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35189.04 | 02-OCT-08:09 | 6311.00 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 2836.13 | 03-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35189.04 | 01-NOV-08:09 | 6311.00 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 2836.13 | 01-NOV-06:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35189.04 | 01-DEC-09:09 | 6311.00 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 2836.13 | 01-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35189.04 | 6311.00 | 10112.62 | 0.00 | 2610.21 | 0.00 | 0.00 | |||||
Maximum of Months | 35189.04 | 6311.00 | 10112.62 | 0.00 | 2836.13 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 3134.96 | 12-JAN-12:09 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 3135.02 | 27-FEB-12:50 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 3131.62 | 04-MAR-12:09 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 3131.63 | 20-APR-11:50 | 0.00 |
May | 440.32 | 13-MAY-15:50 | 0.00 | 0.00 | 0.00 | 3131.55 | 02-MAY-11:20 | 0.00 |
June | 3219.94 | 30-JUN-14:00 | 0.00 | 0.00 | 0.00 | 3040.87 | 01-JUN-11:20 | 0.00 |
July | 5795.01 | 21-JUL-15:00 | 0.00 | 0.00 | 0.00 | 2881.35 | 03-JUL-11:30 | 0.00 |
August | 2596.28 | 04-AUG-14:39 | 0.00 | 0.00 | 0.00 | 2759.50 | 03-AUG-11:00 | 0.00 |
September | 286.28 | 02-SEP-15:00 | 0.00 | 0.00 | 0.00 | 2747.02 | 30-SEP-11:39 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 2842.42 | 28-OCT-11:00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2991.42 | 28-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 3131.45 | 28-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2747.02 | 0.00 | ||
Maximum of Months | 5795.01 | 0.00 | 0.00 | 0.00 | 3135.02 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 57141.15 | 11-JAN-15:50 | 35189.04 | 10112.62 | 6311.00 | 0.00 | 2836.13 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 56179.61 | 10-FEB-09:09 | 35189.04 | 10112.62 | 6311.00 | 0.00 | 2836.13 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 52220.32 | 16-MAR-07:10 | 31277.33 | 10112.62 | 6311.00 | 0.00 | 2836.13 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 50830.21 | 04-APR-12:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2836.13 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 51005.07 | 13-MAY-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2610.21 | 0.00 | 0.00 | 410.14 | 0.00 |
June | 53559.15 | 30-JUN-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2610.21 | 0.00 | 0.00 | 3219.94 | 0.00 |
July | 54865.38 | 29-JUL-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2610.21 | 0.00 | 0.00 | 4662.37 | 0.00 |
August | 52354.42 | 04-AUG-14:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2610.21 | 0.00 | 0.00 | 2596.28 | 0.00 |
September | 50233.47 | 02-SEP-14:20 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2610.21 | 0.00 | 0.00 | 102.80 | 0.00 |
October | 56161.72 | 31-OCT-08:09 | 35189.04 | 10112.62 | 6311.00 | 0.00 | 2836.13 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 56992.36 | 30-NOV-15:39 | 35189.04 | 10112.62 | 6311.00 | 0.00 | 2836.13 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 57140.59 | 30-DEC-15:39 | 35189.04 | 10112.62 | 6311.00 | 0.00 | 2836.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 50233.47 | 31277.33 | 10112.62 | 0.00 | 0.00 | 2610.21 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 57141.15 | 35189.04 | 10112.62 | 6311.00 | 0.00 | 2836.13 | 0.00 | 0.00 | 4662.37 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 248358.76 | 30-JAN-06:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 248358.76 | 24-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 241272.43 | 14-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 218844.92 | 02-APR-23:49 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 47155.89 | 27-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 9503.86 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 5837.23 | 05-JUL-06:19 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 23263.01 | 31-AUG-06:19 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 59129.94 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 219387.85 | 31-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 232031.98 | 29-NOV-07:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 236563.61 | 01-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 5837.23 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 248358.76 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 61.50 | 16.88 | 30.83 | 18.93 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52.83 | 16.56 | 22.33 | 18.88 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 38.00 | 17.47 | 22.83 | 19.12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15.00 | 18.04 | 10.50 | 19.35 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5.50 | 20.21 | 5.50 | 20.21 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.17 | 20.51 | 0.17 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.17 | 24.48 |
August | 0.33 | 20.47 | 0.33 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5.17 | 20.12 | 5.17 | 20.12 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10.50 | 19.04 | 9.67 | 19.39 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28.17 | 18.73 | 23.67 | 19.45 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 43.67 | 18.46 | 33.83 | 19.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 260.83 | 17.66 | 164.83 | 19.27 | 0.17 | 24.48 | 0.17 | 24.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.50 | 20.51 | 33.83 | 20.51 | 0.17 | 24.48 | 0.17 | 24.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 160.50 | 13.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 138.50 | 13.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 113.33 | 14.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78.83 | 14.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10.83 | 14.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13.67 | 14.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 91.50 | 14.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 112.50 | 14.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 118.00 | 14.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 837.67 | 14.02 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.50 | 14.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 98.17 | 6.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 85.83 | 7.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.00 | 9.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5.83 | 9.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.33 | 9.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 195.17 | 7.42 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 98.17 | 9.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.86 | 300.00 | 20.86 | 300.00 | 20.86 |
February | 276.00 | 20.90 | 276.00 | 20.90 | 276.00 | 20.90 |
March | 324.00 | 20.95 | 324.00 | 20.95 | 324.00 | 20.95 |
April | 300.00 | 21.06 | 298.00 | 21.06 | 298.00 | 21.06 |
May | 312.00 | 21.65 | 225.00 | 21.22 | 225.00 | 21.22 |
June | 276.00 | 23.36 | 8.83 | 21.16 | 8.83 | 21.16 |
July | 122.17 | 23.44 | 31.17 | 23.90 | 0.00 | 0.00 |
August | 249.50 | 23.13 | 27.17 | 22.11 | 17.67 | 21.15 |
September | 300.00 | 21.36 | 242.33 | 21.11 | 242.33 | 21.11 |
October | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
November | 288.00 | 20.95 | 288.00 | 20.95 | 288.00 | 20.95 |
December | 300.00 | 20.89 | 300.00 | 20.89 | 300.00 | 20.89 |
Annual Sum or Average | 3347.67 | 21.51 | 2620.50 | 21.04 | 2579.83 | 20.99 |
Minimum of Months | 122.17 | 20.86 | 8.83 | 20.86 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 23.44 | 324.00 | 23.90 | 324.00 | 21.22 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 34273833.24 | 8421204.11 | 11.00 | 34273833.24 | 0.00 | 0.00 | 0.15 | 13-MAY-15:50 | 0.00 | 01-MAY-00:05 | 1807.60 | 13-MAY-15:50 | 1807.60 | 13-MAY-15:50 | 0.00 | 12-MAY-14:30 | 440.32 | 13-MAY-15:50 | 0.00 | 01-MAY-00:05 |
June | 0.202072E+10 | 0.485977E+09 | 206.32 | 0.196269E+10 | 58027072.37 | 0.00 | 1.00 | 22-JUN-05:03 | 0.00 | 01-JUN-00:10 | 14499.93 | 22-JUN-05:03 | 14499.93 | 22-JUN-05:03 | 962.46 | 30-JUN-12:00 | 3073.90 | 22-JUN-05:03 | 0.00 | 01-JUN-00:10 |
July | 0.357410E+10 | 0.850076E+09 | 241.62 | 0.336248E+10 | 0.211619E+09 | 0.00 | 1.00 | 12-JUL-05:02 | 0.00 | 01-JUL-00:10 | 15576.75 | 25-JUL-05:02 | 14705.10 | 22-JUL-05:02 | 2339.42 | 25-JUL-05:02 | 3276.84 | 25-JUL-05:02 | 0.00 | 01-JUL-00:10 |
August | 0.211090E+10 | 0.503570E+09 | 194.98 | 0.200306E+10 | 0.107837E+09 | 0.00 | 1.00 | 03-AUG-05:02 | 0.00 | 01-AUG-00:10 | 15213.50 | 04-AUG-05:03 | 14652.01 | 03-AUG-05:02 | 1827.99 | 04-AUG-05:03 | 3210.92 | 04-AUG-05:03 | 0.00 | 01-AUG-00:10 |
September | 6354257.07 | 1566623.47 | 2.33 | 6354257.07 | 0.00 | 0.00 | 0.09 | 02-SEP-16:00 | 0.00 | 01-SEP-00:10 | 1164.11 | 02-SEP-16:00 | 1164.11 | 02-SEP-16:00 | 0.00 | 02-SEP-14:30 | 286.28 | 02-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.774634E+10 | 0.184961E+10 | 656.26 | 0.736886E+10 | 0.377483E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.357410E+10 | 0.850076E+09 | 241.62 | 0.336248E+10 | 0.211619E+09 | 0.00 | 1.00 | 0.00 | 15576.75 | 14705.10 | 2339.42 | 3276.84 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 |
June | 89676190.28 | 25326343.40 | 11.33 | 86056172.54 | 3620017.74 | 0.00 | 0.23 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 | 5606.39 | 30-JUN-15:00 | 5544.86 | 30-JUN-15:00 | 502.55 | 30-JUN-12:30 | 1618.15 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.844107E+09 | 0.234911E+09 | 59.58 | 0.830104E+09 | 14002830.36 | 0.00 | 0.56 | 23-JUL-14:45 | 0.00 | 01-JUL-00:10 | 13361.49 | 21-JUL-16:00 | 13361.49 | 21-JUL-16:00 | 586.99 | 22-JUL-11:00 | 3809.04 | 21-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 93168520.76 | 25405982.14 | 11.17 | 87889819.21 | 5278701.55 | 0.00 | 0.19 | 04-AUG-14:30 | 0.00 | 01-AUG-00:10 | 4586.00 | 04-AUG-14:30 | 4413.67 | 04-AUG-14:30 | 369.91 | 04-AUG-12:00 | 1238.14 | 04-AUG-14:30 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.102695E+10 | 0.285644E+09 | 82.08 | 0.100405E+10 | 22901549.65 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.844107E+09 | 0.234911E+09 | 59.58 | 0.830104E+09 | 14002830.36 | 0.00 | 0.56 | 0.00 | 13361.49 | 13361.49 | 586.99 | 3809.04 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5.52 | 0.96 | 4.56 | 0.00 | 364.57 | 0.00 | 0.00 | 744.00 |
February | 32.88 | 11.52 | 21.36 | 2.17 | 314.09 | 0.00 | 0.00 | 672.00 |
March | 98.83 | 42.80 | 56.03 | 40.78 | 226.39 | 0.00 | 0.00 | 744.00 |
April | 233.16 | 120.88 | 112.28 | 199.09 | 115.92 | 0.00 | 0.00 | 720.00 |
May | 226.38 | 103.11 | 123.27 | 214.59 | 50.63 | 0.00 | 0.00 | 744.00 |
June | 248.22 | 105.92 | 142.30 | 242.94 | 33.61 | 0.00 | 0.00 | 720.00 |
July | 207.44 | 78.40 | 129.04 | 197.51 | 42.90 | 0.00 | 0.00 | 744.00 |
August | 171.03 | 72.68 | 98.36 | 152.26 | 60.23 | 0.00 | 0.00 | 744.00 |
September | 103.07 | 43.03 | 60.04 | 71.87 | 95.04 | 0.00 | 0.00 | 720.00 |
October | 40.36 | 12.09 | 28.27 | 9.54 | 194.29 | 0.00 | 0.00 | 744.00 |
November | 16.18 | 5.86 | 10.32 | 0.48 | 351.48 | 0.00 | 0.00 | 720.00 |
December | 1.46 | 0.16 | 1.30 | 0.00 | 387.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 115.67 | 49.89 | 65.79 | 94.65 | 185.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1.46 | 0.16 | 1.30 | 0.00 | 33.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 248.22 | 120.88 | 142.30 | 242.94 | 387.50 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5.52 | 0.96 | 4.56 | 0.00 | 364.57 | 0.00 | 0.00 | 744.00 |
February | 32.88 | 11.52 | 21.36 | 2.17 | 314.09 | 0.00 | 0.00 | 672.00 |
March | 98.83 | 42.80 | 56.03 | 40.78 | 226.39 | 0.00 | 0.00 | 744.00 |
April | 233.16 | 120.88 | 112.28 | 199.09 | 115.92 | 0.00 | 0.00 | 720.00 |
May | 226.38 | 103.11 | 123.27 | 214.59 | 50.63 | 0.00 | 0.00 | 744.00 |
June | 248.22 | 105.92 | 142.30 | 242.94 | 33.61 | 0.00 | 0.00 | 720.00 |
July | 207.44 | 78.40 | 129.04 | 197.51 | 42.90 | 0.00 | 0.00 | 744.00 |
August | 171.03 | 72.68 | 98.36 | 152.26 | 60.23 | 0.00 | 0.00 | 744.00 |
September | 103.07 | 43.03 | 60.04 | 71.87 | 95.04 | 0.00 | 0.00 | 720.00 |
October | 40.36 | 12.09 | 28.27 | 9.54 | 194.29 | 0.00 | 0.00 | 744.00 |
November | 16.18 | 5.86 | 10.32 | 0.48 | 351.48 | 0.00 | 0.00 | 720.00 |
December | 1.46 | 0.16 | 1.30 | 0.00 | 387.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 115.67 | 49.89 | 65.79 | 94.65 | 185.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1.46 | 0.16 | 1.30 | 0.00 | 33.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 248.22 | 120.88 | 142.30 | 242.94 | 387.50 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.33 | 0.00 | 2.33 | 0.00 | 214.41 | 0.00 | 0.00 | 744.00 |
February | 10.30 | 0.00 | 10.30 | 0.00 | 193.26 | 0.00 | 0.00 | 672.00 |
March | 27.64 | 0.01 | 27.63 | 0.78 | 145.85 | 0.00 | 0.00 | 744.00 |
April | 50.28 | 1.40 | 48.88 | 14.20 | 72.48 | 0.00 | 0.00 | 720.00 |
May | 77.07 | 12.44 | 64.63 | 49.75 | 25.52 | 0.00 | 0.00 | 744.00 |
June | 99.37 | 21.81 | 77.56 | 77.65 | 14.34 | 0.00 | 0.00 | 720.00 |
July | 83.86 | 13.80 | 70.06 | 63.09 | 20.85 | 0.00 | 0.00 | 744.00 |
August | 53.87 | 2.91 | 50.96 | 29.64 | 33.47 | 0.00 | 0.00 | 744.00 |
September | 29.97 | 0.09 | 29.88 | 7.97 | 58.71 | 0.00 | 0.00 | 720.00 |
October | 14.50 | 0.00 | 14.50 | 0.52 | 119.42 | 0.00 | 0.00 | 744.00 |
November | 4.50 | 0.00 | 4.50 | 0.00 | 210.98 | 0.00 | 0.00 | 720.00 |
December | 0.71 | 0.00 | 0.71 | 0.00 | 226.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.00 | 4.39 | 33.61 | 20.42 | 110.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 0.71 | 0.00 | 0.71 | 0.00 | 14.34 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.37 | 21.81 | 77.56 | 77.65 | 226.64 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.33 | 0.00 | 2.33 | 0.00 | 214.41 | 0.00 | 0.00 | 744.00 |
February | 10.30 | 0.00 | 10.30 | 0.00 | 193.26 | 0.00 | 0.00 | 672.00 |
March | 27.64 | 0.01 | 27.63 | 0.78 | 145.85 | 0.00 | 0.00 | 744.00 |
April | 50.28 | 1.40 | 48.87 | 14.20 | 72.48 | 0.00 | 0.00 | 720.00 |
May | 77.07 | 12.44 | 64.62 | 49.75 | 25.52 | 0.00 | 0.00 | 744.00 |
June | 99.36 | 21.81 | 77.56 | 77.64 | 14.34 | 0.00 | 0.00 | 720.00 |
July | 83.86 | 13.80 | 70.06 | 63.09 | 20.85 | 0.00 | 0.00 | 744.00 |
August | 53.87 | 2.91 | 50.96 | 29.63 | 33.47 | 0.00 | 0.00 | 744.00 |
September | 29.97 | 0.09 | 29.88 | 7.97 | 58.71 | 0.00 | 0.00 | 720.00 |
October | 14.50 | 0.00 | 14.50 | 0.52 | 119.42 | 0.00 | 0.00 | 744.00 |
November | 4.50 | 0.00 | 4.50 | 0.00 | 210.98 | 0.00 | 0.00 | 720.00 |
December | 0.71 | 0.00 | 0.71 | 0.00 | 226.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.00 | 4.39 | 33.61 | 20.42 | 110.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 0.71 | 0.00 | 0.71 | 0.00 | 14.34 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.36 | 21.81 | 77.56 | 77.64 | 226.64 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.69 | 0.10 | 1.59 | 0.00 | 117.34 | 0.00 | 0.00 | 744.00 |
February | 8.27 | 1.58 | 6.69 | 0.00 | 104.97 | 0.00 | 0.00 | 672.00 |
March | 29.50 | 11.62 | 17.88 | 7.70 | 72.96 | 0.00 | 0.00 | 744.00 |
April | 60.86 | 32.04 | 28.82 | 46.37 | 37.52 | 0.00 | 0.00 | 720.00 |
May | 80.84 | 45.65 | 35.19 | 77.84 | 19.54 | 0.00 | 0.00 | 744.00 |
June | 88.31 | 43.90 | 44.41 | 86.27 | 14.39 | 0.00 | 0.00 | 720.00 |
July | 79.08 | 38.04 | 41.04 | 73.02 | 19.57 | 0.00 | 0.00 | 744.00 |
August | 58.90 | 28.10 | 30.80 | 47.57 | 26.92 | 0.00 | 0.00 | 744.00 |
September | 31.20 | 11.67 | 19.52 | 15.82 | 35.63 | 0.00 | 0.00 | 720.00 |
October | 12.63 | 2.58 | 10.05 | 2.52 | 56.89 | 0.00 | 0.00 | 744.00 |
November | 3.22 | 0.17 | 3.05 | 0.00 | 117.17 | 0.00 | 0.00 | 720.00 |
December | 0.49 | 0.00 | 0.48 | 0.00 | 126.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.07 | 18.04 | 20.03 | 29.92 | 62.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 0.49 | 0.00 | 0.48 | 0.00 | 14.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 88.31 | 45.65 | 44.41 | 86.27 | 126.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.69 | 0.10 | 1.59 | 0.00 | 117.34 | 0.00 | 0.00 | 744.00 |
February | 8.27 | 1.58 | 6.69 | 0.00 | 104.97 | 0.00 | 0.00 | 672.00 |
March | 29.50 | 11.62 | 17.88 | 7.70 | 72.96 | 0.00 | 0.00 | 744.00 |
April | 60.86 | 32.04 | 28.82 | 46.37 | 37.52 | 0.00 | 0.00 | 720.00 |
May | 80.84 | 45.65 | 35.19 | 77.84 | 19.54 | 0.00 | 0.00 | 744.00 |
June | 88.31 | 43.90 | 44.41 | 86.27 | 14.39 | 0.00 | 0.00 | 720.00 |
July | 79.08 | 38.04 | 41.04 | 73.02 | 19.57 | 0.00 | 0.00 | 744.00 |
August | 58.90 | 28.10 | 30.80 | 47.57 | 26.92 | 0.00 | 0.00 | 744.00 |
September | 31.20 | 11.67 | 19.52 | 15.82 | 35.63 | 0.00 | 0.00 | 720.00 |
October | 12.63 | 2.58 | 10.05 | 2.52 | 56.89 | 0.00 | 0.00 | 744.00 |
November | 3.22 | 0.17 | 3.05 | 0.00 | 117.17 | 0.00 | 0.00 | 720.00 |
December | 0.49 | 0.00 | 0.48 | 0.00 | 126.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.07 | 18.04 | 20.03 | 29.92 | 62.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 0.49 | 0.00 | 0.48 | 0.00 | 14.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 88.31 | 45.65 | 44.41 | 86.27 | 126.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.69 | 0.10 | 1.59 | 0.00 | 117.34 | 0.00 | 0.00 | 744.00 |
February | 8.27 | 1.58 | 6.69 | 0.00 | 104.97 | 0.00 | 0.00 | 672.00 |
March | 29.50 | 11.62 | 17.88 | 7.70 | 72.96 | 0.00 | 0.00 | 744.00 |
April | 60.86 | 32.04 | 28.82 | 46.37 | 37.52 | 0.00 | 0.00 | 720.00 |
May | 80.84 | 45.65 | 35.19 | 77.84 | 19.54 | 0.00 | 0.00 | 744.00 |
June | 88.31 | 43.90 | 44.41 | 86.27 | 14.39 | 0.00 | 0.00 | 720.00 |
July | 79.08 | 38.04 | 41.04 | 73.02 | 19.57 | 0.00 | 0.00 | 744.00 |
August | 58.90 | 28.10 | 30.80 | 47.57 | 26.92 | 0.00 | 0.00 | 744.00 |
September | 31.20 | 11.67 | 19.52 | 15.82 | 35.63 | 0.00 | 0.00 | 720.00 |
October | 12.63 | 2.58 | 10.05 | 2.52 | 56.89 | 0.00 | 0.00 | 744.00 |
November | 3.22 | 0.17 | 3.05 | 0.00 | 117.17 | 0.00 | 0.00 | 720.00 |
December | 0.49 | 0.00 | 0.48 | 0.00 | 126.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.07 | 18.04 | 20.03 | 29.92 | 62.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 0.49 | 0.00 | 0.48 | 0.00 | 14.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 88.31 | 45.65 | 44.41 | 86.27 | 126.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.69 | 0.10 | 1.59 | 0.00 | 117.34 | 0.00 | 0.00 | 744.00 |
February | 8.27 | 1.58 | 6.69 | 0.00 | 104.97 | 0.00 | 0.00 | 672.00 |
March | 29.50 | 11.62 | 17.88 | 7.70 | 72.96 | 0.00 | 0.00 | 744.00 |
April | 60.86 | 32.04 | 28.82 | 46.37 | 37.52 | 0.00 | 0.00 | 720.00 |
May | 80.84 | 45.65 | 35.19 | 77.84 | 19.54 | 0.00 | 0.00 | 744.00 |
June | 88.31 | 43.90 | 44.41 | 86.27 | 14.39 | 0.00 | 0.00 | 720.00 |
July | 79.08 | 38.04 | 41.04 | 73.02 | 19.57 | 0.00 | 0.00 | 744.00 |
August | 58.90 | 28.10 | 30.80 | 47.57 | 26.92 | 0.00 | 0.00 | 744.00 |
September | 31.20 | 11.67 | 19.52 | 15.82 | 35.63 | 0.00 | 0.00 | 720.00 |
October | 12.63 | 2.58 | 10.05 | 2.52 | 56.89 | 0.00 | 0.00 | 744.00 |
November | 3.22 | 0.17 | 3.05 | 0.00 | 117.17 | 0.00 | 0.00 | 720.00 |
December | 0.49 | 0.00 | 0.48 | 0.00 | 126.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.07 | 18.04 | 20.03 | 29.92 | 62.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 0.49 | 0.00 | 0.48 | 0.00 | 14.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 88.31 | 45.65 | 44.41 | 86.27 | 126.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.69 | 0.10 | 1.59 | 0.00 | 117.34 | 0.00 | 0.00 | 744.00 |
February | 8.27 | 1.58 | 6.69 | 0.00 | 104.97 | 0.00 | 0.00 | 672.00 |
March | 29.50 | 11.62 | 17.88 | 7.70 | 72.96 | 0.00 | 0.00 | 744.00 |
April | 60.86 | 32.04 | 28.82 | 46.37 | 37.52 | 0.00 | 0.00 | 720.00 |
May | 80.84 | 45.65 | 35.19 | 77.84 | 19.54 | 0.00 | 0.00 | 744.00 |
June | 88.31 | 43.90 | 44.41 | 86.27 | 14.39 | 0.00 | 0.00 | 720.00 |
July | 79.08 | 38.04 | 41.04 | 73.02 | 19.57 | 0.00 | 0.00 | 744.00 |
August | 58.90 | 28.10 | 30.80 | 47.57 | 26.92 | 0.00 | 0.00 | 744.00 |
September | 31.20 | 11.67 | 19.52 | 15.82 | 35.63 | 0.00 | 0.00 | 720.00 |
October | 12.63 | 2.58 | 10.05 | 2.52 | 56.89 | 0.00 | 0.00 | 744.00 |
November | 3.22 | 0.17 | 3.05 | 0.00 | 117.17 | 0.00 | 0.00 | 720.00 |
December | 0.49 | 0.00 | 0.48 | 0.00 | 126.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.07 | 18.04 | 20.03 | 29.92 | 62.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 0.49 | 0.00 | 0.48 | 0.00 | 14.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 88.31 | 45.65 | 44.41 | 86.27 | 126.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.69 | 0.10 | 1.59 | 0.00 | 117.34 | 0.00 | 0.00 | 744.00 |
February | 8.27 | 1.58 | 6.69 | 0.00 | 104.97 | 0.00 | 0.00 | 672.00 |
March | 29.50 | 11.62 | 17.88 | 7.70 | 72.96 | 0.00 | 0.00 | 744.00 |
April | 60.86 | 32.04 | 28.82 | 46.37 | 37.52 | 0.00 | 0.00 | 720.00 |
May | 80.84 | 45.65 | 35.19 | 77.84 | 19.54 | 0.00 | 0.00 | 744.00 |
June | 88.31 | 43.90 | 44.41 | 86.27 | 14.39 | 0.00 | 0.00 | 720.00 |
July | 79.08 | 38.04 | 41.04 | 73.02 | 19.57 | 0.00 | 0.00 | 744.00 |
August | 58.90 | 28.10 | 30.80 | 47.57 | 26.92 | 0.00 | 0.00 | 744.00 |
September | 31.20 | 11.67 | 19.52 | 15.82 | 35.63 | 0.00 | 0.00 | 720.00 |
October | 12.63 | 2.58 | 10.05 | 2.52 | 56.89 | 0.00 | 0.00 | 744.00 |
November | 3.22 | 0.17 | 3.05 | 0.00 | 117.17 | 0.00 | 0.00 | 720.00 |
December | 0.49 | 0.00 | 0.48 | 0.00 | 126.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.07 | 18.04 | 20.03 | 29.92 | 62.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 0.49 | 0.00 | 0.48 | 0.00 | 14.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 88.31 | 45.65 | 44.41 | 86.27 | 126.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.69 | 0.10 | 1.59 | 0.00 | 117.34 | 0.00 | 0.00 | 744.00 |
February | 8.27 | 1.58 | 6.69 | 0.00 | 104.97 | 0.00 | 0.00 | 672.00 |
March | 29.50 | 11.62 | 17.88 | 7.70 | 72.96 | 0.00 | 0.00 | 744.00 |
April | 60.86 | 32.04 | 28.82 | 46.37 | 37.52 | 0.00 | 0.00 | 720.00 |
May | 80.84 | 45.65 | 35.19 | 77.84 | 19.54 | 0.00 | 0.00 | 744.00 |
June | 88.31 | 43.90 | 44.41 | 86.27 | 14.39 | 0.00 | 0.00 | 720.00 |
July | 79.08 | 38.04 | 41.04 | 73.02 | 19.57 | 0.00 | 0.00 | 744.00 |
August | 58.90 | 28.10 | 30.80 | 47.57 | 26.92 | 0.00 | 0.00 | 744.00 |
September | 31.20 | 11.67 | 19.52 | 15.82 | 35.63 | 0.00 | 0.00 | 720.00 |
October | 12.63 | 2.58 | 10.05 | 2.52 | 56.89 | 0.00 | 0.00 | 744.00 |
November | 3.22 | 0.17 | 3.05 | 0.00 | 117.17 | 0.00 | 0.00 | 720.00 |
December | 0.49 | 0.00 | 0.48 | 0.00 | 126.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.07 | 18.04 | 20.03 | 29.92 | 62.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 0.49 | 0.00 | 0.48 | 0.00 | 14.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 88.31 | 45.65 | 44.41 | 86.27 | 126.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.69 | 0.10 | 1.59 | 0.00 | 117.34 | 0.00 | 0.00 | 744.00 |
February | 8.27 | 1.58 | 6.69 | 0.00 | 104.97 | 0.00 | 0.00 | 672.00 |
March | 29.50 | 11.62 | 17.88 | 7.70 | 72.96 | 0.00 | 0.00 | 744.00 |
April | 60.86 | 32.04 | 28.82 | 46.37 | 37.52 | 0.00 | 0.00 | 720.00 |
May | 80.84 | 45.65 | 35.19 | 77.84 | 19.54 | 0.00 | 0.00 | 744.00 |
June | 88.31 | 43.90 | 44.41 | 86.27 | 14.39 | 0.00 | 0.00 | 720.00 |
July | 79.08 | 38.04 | 41.04 | 73.02 | 19.57 | 0.00 | 0.00 | 744.00 |
August | 58.90 | 28.10 | 30.80 | 47.57 | 26.92 | 0.00 | 0.00 | 744.00 |
September | 31.20 | 11.67 | 19.52 | 15.82 | 35.63 | 0.00 | 0.00 | 720.00 |
October | 12.63 | 2.58 | 10.05 | 2.52 | 56.89 | 0.00 | 0.00 | 744.00 |
November | 3.22 | 0.17 | 3.05 | 0.00 | 117.17 | 0.00 | 0.00 | 720.00 |
December | 0.49 | 0.00 | 0.48 | 0.00 | 126.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.07 | 18.04 | 20.03 | 29.92 | 62.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 0.49 | 0.00 | 0.48 | 0.00 | 14.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 88.31 | 45.65 | 44.41 | 86.27 | 126.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.69 | 0.10 | 1.59 | 0.00 | 117.34 | 0.00 | 0.00 | 744.00 |
February | 8.27 | 1.58 | 6.69 | 0.00 | 104.97 | 0.00 | 0.00 | 672.00 |
March | 29.50 | 11.62 | 17.88 | 7.70 | 72.96 | 0.00 | 0.00 | 744.00 |
April | 60.86 | 32.04 | 28.82 | 46.37 | 37.52 | 0.00 | 0.00 | 720.00 |
May | 80.84 | 45.65 | 35.19 | 77.84 | 19.54 | 0.00 | 0.00 | 744.00 |
June | 88.31 | 43.90 | 44.41 | 86.27 | 14.39 | 0.00 | 0.00 | 720.00 |
July | 79.08 | 38.04 | 41.04 | 73.02 | 19.57 | 0.00 | 0.00 | 744.00 |
August | 58.90 | 28.10 | 30.80 | 47.57 | 26.92 | 0.00 | 0.00 | 744.00 |
September | 31.20 | 11.67 | 19.52 | 15.82 | 35.63 | 0.00 | 0.00 | 720.00 |
October | 12.63 | 2.58 | 10.05 | 2.52 | 56.89 | 0.00 | 0.00 | 744.00 |
November | 3.22 | 0.17 | 3.05 | 0.00 | 117.17 | 0.00 | 0.00 | 720.00 |
December | 0.49 | 0.00 | 0.48 | 0.00 | 126.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.07 | 18.04 | 20.03 | 29.92 | 62.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 0.49 | 0.00 | 0.48 | 0.00 | 14.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 88.31 | 45.65 | 44.41 | 86.27 | 126.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.69 | 0.10 | 1.59 | 0.00 | 117.34 | 0.00 | 0.00 | 744.00 |
February | 8.27 | 1.58 | 6.69 | 0.00 | 104.97 | 0.00 | 0.00 | 672.00 |
March | 29.50 | 11.62 | 17.88 | 7.70 | 72.96 | 0.00 | 0.00 | 744.00 |
April | 60.86 | 32.04 | 28.82 | 46.37 | 37.52 | 0.00 | 0.00 | 720.00 |
May | 80.84 | 45.65 | 35.19 | 77.84 | 19.54 | 0.00 | 0.00 | 744.00 |
June | 88.31 | 43.90 | 44.41 | 86.27 | 14.39 | 0.00 | 0.00 | 720.00 |
July | 79.08 | 38.04 | 41.04 | 73.02 | 19.57 | 0.00 | 0.00 | 744.00 |
August | 58.90 | 28.10 | 30.80 | 47.57 | 26.92 | 0.00 | 0.00 | 744.00 |
September | 31.20 | 11.67 | 19.52 | 15.82 | 35.63 | 0.00 | 0.00 | 720.00 |
October | 12.63 | 2.58 | 10.05 | 2.52 | 56.89 | 0.00 | 0.00 | 744.00 |
November | 3.22 | 0.17 | 3.05 | 0.00 | 117.17 | 0.00 | 0.00 | 720.00 |
December | 0.49 | 0.00 | 0.48 | 0.00 | 126.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.07 | 18.04 | 20.03 | 29.92 | 62.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 0.49 | 0.00 | 0.48 | 0.00 | 14.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 88.31 | 45.65 | 44.41 | 86.27 | 126.01 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 14795537.47 | 2572899.80 | 12222637.67 | 0.00 | 0.976453E+09 |
February | 79538233.44 | 27863042.85 | 51675190.59 | 5250075.46 | 0.759838E+09 |
March | 0.264703E+09 | 0.114633E+09 | 0.150071E+09 | 0.109231E+09 | 0.606369E+09 |
April | 0.604347E+09 | 0.313327E+09 | 0.291019E+09 | 0.516035E+09 | 0.300452E+09 |
May | 0.606330E+09 | 0.276170E+09 | 0.330160E+09 | 0.574767E+09 | 0.135608E+09 |
June | 0.643383E+09 | 0.274553E+09 | 0.368830E+09 | 0.629711E+09 | 87123102.03 |
July | 0.555613E+09 | 0.209980E+09 | 0.345633E+09 | 0.529007E+09 | 0.114900E+09 |
August | 0.458090E+09 | 0.194653E+09 | 0.263437E+09 | 0.407807E+09 | 0.161309E+09 |
September | 0.267155E+09 | 0.111525E+09 | 0.155630E+09 | 0.186279E+09 | 0.246344E+09 |
October | 0.108106E+09 | 32374035.93 | 75731683.82 | 25562209.49 | 0.520390E+09 |
November | 41932593.88 | 15187642.92 | 26744950.96 | 1249591.10 | 0.911034E+09 |
December | 3897426.12 | 416495.85 | 3480930.26 | 0.00 | 0.103788E+10 |
Annual Sum or Average | 0.364789E+10 | 0.157326E+10 | 0.207463E+10 | 0.298490E+10 | 0.585770E+10 |
Minimum of Months | 3897426.12 | 416495.85 | 3480930.26 | 0.00 | 87123102.03 |
Maximum of Months | 0.643383E+09 | 0.313327E+09 | 0.368830E+09 | 0.629711E+09 | 0.103788E+10 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 14795537.47 | 2572899.80 | 12222637.67 | 0.00 | 0.976453E+09 |
February | 79538233.44 | 27863042.85 | 51675190.59 | 5250075.46 | 0.759838E+09 |
March | 0.264703E+09 | 0.114633E+09 | 0.150071E+09 | 0.109231E+09 | 0.606369E+09 |
April | 0.604347E+09 | 0.313327E+09 | 0.291019E+09 | 0.516035E+09 | 0.300452E+09 |
May | 0.606330E+09 | 0.276170E+09 | 0.330160E+09 | 0.574767E+09 | 0.135608E+09 |
June | 0.643383E+09 | 0.274553E+09 | 0.368830E+09 | 0.629711E+09 | 87123102.03 |
July | 0.555613E+09 | 0.209980E+09 | 0.345633E+09 | 0.529007E+09 | 0.114900E+09 |
August | 0.458090E+09 | 0.194653E+09 | 0.263437E+09 | 0.407807E+09 | 0.161309E+09 |
September | 0.267155E+09 | 0.111525E+09 | 0.155630E+09 | 0.186279E+09 | 0.246344E+09 |
October | 0.108106E+09 | 32374035.93 | 75731683.82 | 25562209.49 | 0.520390E+09 |
November | 41932593.88 | 15187642.92 | 26744950.96 | 1249591.10 | 0.911034E+09 |
December | 3897426.12 | 416495.85 | 3480930.26 | 0.00 | 0.103788E+10 |
Annual Sum or Average | 0.364789E+10 | 0.157326E+10 | 0.207463E+10 | 0.298490E+10 | 0.585770E+10 |
Minimum of Months | 3897426.12 | 416495.85 | 3480930.26 | 0.00 | 87123102.03 |
Maximum of Months | 0.643383E+09 | 0.313327E+09 | 0.368830E+09 | 0.629711E+09 | 0.103788E+10 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6242543.39 | 0.00 | 6242543.39 | 0.00 | 0.574279E+09 |
February | 24924571.43 | 0.00 | 24924571.43 | 0.00 | 0.467546E+09 |
March | 74024404.27 | 24119.60 | 74000284.67 | 2089220.40 | 0.390645E+09 |
April | 0.130317E+09 | 3632441.26 | 0.126684E+09 | 36810324.93 | 0.187874E+09 |
May | 0.206426E+09 | 33332414.96 | 0.173094E+09 | 0.133251E+09 | 68364372.42 |
June | 0.257560E+09 | 56524461.99 | 0.201036E+09 | 0.201256E+09 | 37168095.34 |
July | 0.224614E+09 | 36957267.76 | 0.187657E+09 | 0.168993E+09 | 55835217.25 |
August | 0.144295E+09 | 7793310.77 | 0.136502E+09 | 79376531.70 | 89651138.64 |
September | 77681748.17 | 222120.81 | 77459627.36 | 20671186.94 | 0.152181E+09 |
October | 38847535.24 | 0.00 | 38847535.24 | 1392865.45 | 0.319857E+09 |
November | 11666868.70 | 0.00 | 11666868.70 | 0.00 | 0.546873E+09 |
December | 1893660.17 | 0.00 | 1893660.17 | 0.00 | 0.607029E+09 |
Annual Sum or Average | 0.119849E+10 | 0.138486E+09 | 0.106001E+10 | 0.643840E+09 | 0.349730E+10 |
Minimum of Months | 1893660.17 | 0.00 | 1893660.17 | 0.00 | 37168095.34 |
Maximum of Months | 0.257560E+09 | 56524461.99 | 0.201036E+09 | 0.201256E+09 | 0.607029E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6242317.75 | 0.00 | 6242317.75 | 0.00 | 0.574278E+09 |
February | 24923727.57 | 0.00 | 24923727.57 | 0.00 | 0.467546E+09 |
March | 74022047.32 | 24118.47 | 73997928.85 | 2088916.14 | 0.390646E+09 |
April | 0.130313E+09 | 3632271.00 | 0.126681E+09 | 36808113.41 | 0.187875E+09 |
May | 0.206419E+09 | 33330852.62 | 0.173088E+09 | 0.133244E+09 | 68364276.62 |
June | 0.257551E+09 | 56521812.61 | 0.201029E+09 | 0.201246E+09 | 37168054.16 |
July | 0.224606E+09 | 36955535.52 | 0.187651E+09 | 0.168985E+09 | 55835281.54 |
August | 0.144290E+09 | 7792945.49 | 0.136497E+09 | 79372275.14 | 89651110.21 |
September | 77679181.44 | 222110.40 | 77457071.05 | 20669695.20 | 0.152181E+09 |
October | 38846204.45 | 0.00 | 38846204.45 | 1392661.07 | 0.319857E+09 |
November | 11666447.01 | 0.00 | 11666447.01 | 0.00 | 0.546872E+09 |
December | 1893588.72 | 0.00 | 1893588.72 | 0.00 | 0.607027E+09 |
Annual Sum or Average | 0.119845E+10 | 0.138480E+09 | 0.105997E+10 | 0.643808E+09 | 0.349730E+10 |
Minimum of Months | 1893588.72 | 0.00 | 1893588.72 | 0.00 | 37168054.16 |
Maximum of Months | 0.257551E+09 | 56521812.61 | 0.201029E+09 | 0.201246E+09 | 0.607027E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4522112.89 | 261014.35 | 4261098.55 | 0.00 | 0.314297E+09 |
February | 20017506.10 | 3823150.72 | 16194355.39 | 1159.59 | 0.253933E+09 |
March | 79012322.88 | 31110726.97 | 47901595.91 | 20622753.07 | 0.195419E+09 |
April | 0.157746E+09 | 83034907.46 | 74711087.83 | 0.120198E+09 | 97238935.33 |
May | 0.216510E+09 | 0.122257E+09 | 94253100.08 | 0.208474E+09 | 52345532.40 |
June | 0.228909E+09 | 0.113795E+09 | 0.115115E+09 | 0.223613E+09 | 37293225.12 |
July | 0.211807E+09 | 0.101888E+09 | 0.109919E+09 | 0.195574E+09 | 52408351.20 |
August | 0.157760E+09 | 75271101.09 | 82489253.70 | 0.127410E+09 | 72110582.75 |
September | 80858376.75 | 30251368.62 | 50607008.13 | 40995595.27 | 92341996.47 |
October | 33824691.04 | 6911263.22 | 26913427.82 | 6741489.08 | 0.152383E+09 |
November | 8352982.49 | 447821.41 | 7905161.08 | 0.00 | 0.303714E+09 |
December | 1302235.19 | 13207.38 | 1289027.81 | 0.00 | 0.337499E+09 |
Annual Sum or Average | 0.120062E+10 | 0.569064E+09 | 0.631559E+09 | 0.943630E+09 | 0.196098E+10 |
Minimum of Months | 1302235.19 | 13207.38 | 1289027.81 | 0.00 | 37293225.12 |
Maximum of Months | 0.228909E+09 | 0.122257E+09 | 0.115115E+09 | 0.223613E+09 | 0.337499E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4522112.89 | 261014.35 | 4261098.55 | 0.00 | 0.314297E+09 |
February | 20017506.10 | 3823150.72 | 16194355.39 | 1159.59 | 0.253933E+09 |
March | 79012322.88 | 31110726.97 | 47901595.91 | 20622753.07 | 0.195419E+09 |
April | 0.157746E+09 | 83034907.46 | 74711087.83 | 0.120198E+09 | 97238935.33 |
May | 0.216510E+09 | 0.122257E+09 | 94253100.08 | 0.208474E+09 | 52345532.40 |
June | 0.228909E+09 | 0.113795E+09 | 0.115115E+09 | 0.223613E+09 | 37293225.12 |
July | 0.211807E+09 | 0.101888E+09 | 0.109919E+09 | 0.195574E+09 | 52408351.20 |
August | 0.157760E+09 | 75271101.09 | 82489253.70 | 0.127410E+09 | 72110582.75 |
September | 80858376.75 | 30251368.62 | 50607008.13 | 40995595.27 | 92341996.47 |
October | 33824691.04 | 6911263.22 | 26913427.82 | 6741489.08 | 0.152383E+09 |
November | 8352982.49 | 447821.41 | 7905161.08 | 0.00 | 0.303714E+09 |
December | 1302235.19 | 13207.38 | 1289027.81 | 0.00 | 0.337499E+09 |
Annual Sum or Average | 0.120062E+10 | 0.569064E+09 | 0.631559E+09 | 0.943630E+09 | 0.196098E+10 |
Minimum of Months | 1302235.19 | 13207.38 | 1289027.81 | 0.00 | 37293225.12 |
Maximum of Months | 0.228909E+09 | 0.122257E+09 | 0.115115E+09 | 0.223613E+09 | 0.337499E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4522112.89 | 261014.35 | 4261098.55 | 0.00 | 0.314297E+09 |
February | 20017506.10 | 3823150.72 | 16194355.39 | 1159.59 | 0.253933E+09 |
March | 79012322.88 | 31110726.97 | 47901595.91 | 20622753.07 | 0.195419E+09 |
April | 0.157746E+09 | 83034907.46 | 74711087.83 | 0.120198E+09 | 97238935.33 |
May | 0.216510E+09 | 0.122257E+09 | 94253100.08 | 0.208474E+09 | 52345532.40 |
June | 0.228909E+09 | 0.113795E+09 | 0.115115E+09 | 0.223613E+09 | 37293225.12 |
July | 0.211807E+09 | 0.101888E+09 | 0.109919E+09 | 0.195574E+09 | 52408351.20 |
August | 0.157760E+09 | 75271101.09 | 82489253.70 | 0.127410E+09 | 72110582.75 |
September | 80858376.75 | 30251368.62 | 50607008.13 | 40995595.27 | 92341996.47 |
October | 33824691.04 | 6911263.22 | 26913427.82 | 6741489.08 | 0.152383E+09 |
November | 8352982.49 | 447821.41 | 7905161.08 | 0.00 | 0.303714E+09 |
December | 1302235.19 | 13207.38 | 1289027.81 | 0.00 | 0.337499E+09 |
Annual Sum or Average | 0.120062E+10 | 0.569064E+09 | 0.631559E+09 | 0.943630E+09 | 0.196098E+10 |
Minimum of Months | 1302235.19 | 13207.38 | 1289027.81 | 0.00 | 37293225.12 |
Maximum of Months | 0.228909E+09 | 0.122257E+09 | 0.115115E+09 | 0.223613E+09 | 0.337499E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4522112.89 | 261014.35 | 4261098.55 | 0.00 | 0.314297E+09 |
February | 20017506.10 | 3823150.72 | 16194355.39 | 1159.59 | 0.253933E+09 |
March | 79012322.88 | 31110726.97 | 47901595.91 | 20622753.07 | 0.195419E+09 |
April | 0.157746E+09 | 83034907.46 | 74711087.83 | 0.120198E+09 | 97238935.33 |
May | 0.216510E+09 | 0.122257E+09 | 94253100.08 | 0.208474E+09 | 52345532.40 |
June | 0.228909E+09 | 0.113795E+09 | 0.115115E+09 | 0.223613E+09 | 37293225.12 |
July | 0.211807E+09 | 0.101888E+09 | 0.109919E+09 | 0.195574E+09 | 52408351.20 |
August | 0.157760E+09 | 75271101.09 | 82489253.70 | 0.127410E+09 | 72110582.75 |
September | 80858376.75 | 30251368.62 | 50607008.13 | 40995595.27 | 92341996.47 |
October | 33824691.04 | 6911263.22 | 26913427.82 | 6741489.08 | 0.152383E+09 |
November | 8352982.49 | 447821.41 | 7905161.08 | 0.00 | 0.303714E+09 |
December | 1302235.19 | 13207.38 | 1289027.81 | 0.00 | 0.337499E+09 |
Annual Sum or Average | 0.120062E+10 | 0.569064E+09 | 0.631559E+09 | 0.943630E+09 | 0.196098E+10 |
Minimum of Months | 1302235.19 | 13207.38 | 1289027.81 | 0.00 | 37293225.12 |
Maximum of Months | 0.228909E+09 | 0.122257E+09 | 0.115115E+09 | 0.223613E+09 | 0.337499E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4522112.89 | 261014.35 | 4261098.55 | 0.00 | 0.314297E+09 |
February | 20017506.10 | 3823150.72 | 16194355.39 | 1159.59 | 0.253933E+09 |
March | 79012322.88 | 31110726.97 | 47901595.91 | 20622753.07 | 0.195419E+09 |
April | 0.157746E+09 | 83034907.46 | 74711087.83 | 0.120198E+09 | 97238935.33 |
May | 0.216510E+09 | 0.122257E+09 | 94253100.08 | 0.208474E+09 | 52345532.40 |
June | 0.228909E+09 | 0.113795E+09 | 0.115115E+09 | 0.223613E+09 | 37293225.12 |
July | 0.211807E+09 | 0.101888E+09 | 0.109919E+09 | 0.195574E+09 | 52408351.20 |
August | 0.157760E+09 | 75271101.09 | 82489253.70 | 0.127410E+09 | 72110582.75 |
September | 80858376.75 | 30251368.62 | 50607008.13 | 40995595.27 | 92341996.47 |
October | 33824691.04 | 6911263.22 | 26913427.82 | 6741489.08 | 0.152383E+09 |
November | 8352982.49 | 447821.41 | 7905161.08 | 0.00 | 0.303714E+09 |
December | 1302235.19 | 13207.38 | 1289027.81 | 0.00 | 0.337499E+09 |
Annual Sum or Average | 0.120062E+10 | 0.569064E+09 | 0.631559E+09 | 0.943630E+09 | 0.196098E+10 |
Minimum of Months | 1302235.19 | 13207.38 | 1289027.81 | 0.00 | 37293225.12 |
Maximum of Months | 0.228909E+09 | 0.122257E+09 | 0.115115E+09 | 0.223613E+09 | 0.337499E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4522112.89 | 261014.35 | 4261098.55 | 0.00 | 0.314297E+09 |
February | 20017506.10 | 3823150.72 | 16194355.39 | 1159.59 | 0.253933E+09 |
March | 79012322.88 | 31110726.97 | 47901595.91 | 20622753.07 | 0.195419E+09 |
April | 0.157746E+09 | 83034907.46 | 74711087.83 | 0.120198E+09 | 97238935.33 |
May | 0.216510E+09 | 0.122257E+09 | 94253100.08 | 0.208474E+09 | 52345532.40 |
June | 0.228909E+09 | 0.113795E+09 | 0.115115E+09 | 0.223613E+09 | 37293225.12 |
July | 0.211807E+09 | 0.101888E+09 | 0.109919E+09 | 0.195574E+09 | 52408351.20 |
August | 0.157760E+09 | 75271101.09 | 82489253.70 | 0.127410E+09 | 72110582.75 |
September | 80858376.75 | 30251368.62 | 50607008.13 | 40995595.27 | 92341996.47 |
October | 33824691.04 | 6911263.22 | 26913427.82 | 6741489.08 | 0.152383E+09 |
November | 8352982.49 | 447821.41 | 7905161.08 | 0.00 | 0.303714E+09 |
December | 1302235.19 | 13207.38 | 1289027.81 | 0.00 | 0.337499E+09 |
Annual Sum or Average | 0.120062E+10 | 0.569064E+09 | 0.631559E+09 | 0.943630E+09 | 0.196098E+10 |
Minimum of Months | 1302235.19 | 13207.38 | 1289027.81 | 0.00 | 37293225.12 |
Maximum of Months | 0.228909E+09 | 0.122257E+09 | 0.115115E+09 | 0.223613E+09 | 0.337499E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4522112.89 | 261014.35 | 4261098.55 | 0.00 | 0.314297E+09 |
February | 20017506.10 | 3823150.72 | 16194355.39 | 1159.59 | 0.253933E+09 |
March | 79012322.88 | 31110726.97 | 47901595.91 | 20622753.07 | 0.195419E+09 |
April | 0.157746E+09 | 83034907.46 | 74711087.83 | 0.120198E+09 | 97238935.33 |
May | 0.216510E+09 | 0.122257E+09 | 94253100.08 | 0.208474E+09 | 52345532.40 |
June | 0.228909E+09 | 0.113795E+09 | 0.115115E+09 | 0.223613E+09 | 37293225.12 |
July | 0.211807E+09 | 0.101888E+09 | 0.109919E+09 | 0.195574E+09 | 52408351.20 |
August | 0.157760E+09 | 75271101.09 | 82489253.70 | 0.127410E+09 | 72110582.75 |
September | 80858376.75 | 30251368.62 | 50607008.13 | 40995595.27 | 92341996.47 |
October | 33824691.04 | 6911263.22 | 26913427.82 | 6741489.08 | 0.152383E+09 |
November | 8352982.49 | 447821.41 | 7905161.08 | 0.00 | 0.303714E+09 |
December | 1302235.19 | 13207.38 | 1289027.81 | 0.00 | 0.337499E+09 |
Annual Sum or Average | 0.120062E+10 | 0.569064E+09 | 0.631559E+09 | 0.943630E+09 | 0.196098E+10 |
Minimum of Months | 1302235.19 | 13207.38 | 1289027.81 | 0.00 | 37293225.12 |
Maximum of Months | 0.228909E+09 | 0.122257E+09 | 0.115115E+09 | 0.223613E+09 | 0.337499E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4522112.89 | 261014.35 | 4261098.55 | 0.00 | 0.314297E+09 |
February | 20017506.10 | 3823150.72 | 16194355.39 | 1159.59 | 0.253933E+09 |
March | 79012322.88 | 31110726.97 | 47901595.91 | 20622753.07 | 0.195419E+09 |
April | 0.157746E+09 | 83034907.46 | 74711087.83 | 0.120198E+09 | 97238935.33 |
May | 0.216510E+09 | 0.122257E+09 | 94253100.08 | 0.208474E+09 | 52345532.40 |
June | 0.228909E+09 | 0.113795E+09 | 0.115115E+09 | 0.223613E+09 | 37293225.12 |
July | 0.211807E+09 | 0.101888E+09 | 0.109919E+09 | 0.195574E+09 | 52408351.20 |
August | 0.157760E+09 | 75271101.09 | 82489253.70 | 0.127410E+09 | 72110582.75 |
September | 80858376.75 | 30251368.62 | 50607008.13 | 40995595.27 | 92341996.47 |
October | 33824691.04 | 6911263.22 | 26913427.82 | 6741489.08 | 0.152383E+09 |
November | 8352982.49 | 447821.41 | 7905161.08 | 0.00 | 0.303714E+09 |
December | 1302235.19 | 13207.38 | 1289027.81 | 0.00 | 0.337499E+09 |
Annual Sum or Average | 0.120062E+10 | 0.569064E+09 | 0.631559E+09 | 0.943630E+09 | 0.196098E+10 |
Minimum of Months | 1302235.19 | 13207.38 | 1289027.81 | 0.00 | 37293225.12 |
Maximum of Months | 0.228909E+09 | 0.122257E+09 | 0.115115E+09 | 0.223613E+09 | 0.337499E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4522112.89 | 261014.35 | 4261098.55 | 0.00 | 0.314297E+09 |
February | 20017506.10 | 3823150.72 | 16194355.39 | 1159.59 | 0.253933E+09 |
March | 79012322.88 | 31110726.97 | 47901595.91 | 20622753.07 | 0.195419E+09 |
April | 0.157746E+09 | 83034907.46 | 74711087.83 | 0.120198E+09 | 97238935.33 |
May | 0.216510E+09 | 0.122257E+09 | 94253100.08 | 0.208474E+09 | 52345532.40 |
June | 0.228909E+09 | 0.113795E+09 | 0.115115E+09 | 0.223613E+09 | 37293225.12 |
July | 0.211807E+09 | 0.101888E+09 | 0.109919E+09 | 0.195574E+09 | 52408351.20 |
August | 0.157760E+09 | 75271101.09 | 82489253.70 | 0.127410E+09 | 72110582.75 |
September | 80858376.75 | 30251368.62 | 50607008.13 | 40995595.27 | 92341996.47 |
October | 33824691.04 | 6911263.22 | 26913427.82 | 6741489.08 | 0.152383E+09 |
November | 8352982.49 | 447821.41 | 7905161.08 | 0.00 | 0.303714E+09 |
December | 1302235.19 | 13207.38 | 1289027.81 | 0.00 | 0.337499E+09 |
Annual Sum or Average | 0.120062E+10 | 0.569064E+09 | 0.631559E+09 | 0.943630E+09 | 0.196098E+10 |
Minimum of Months | 1302235.19 | 13207.38 | 1289027.81 | 0.00 | 37293225.12 |
Maximum of Months | 0.228909E+09 | 0.122257E+09 | 0.115115E+09 | 0.223613E+09 | 0.337499E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4522112.89 | 261014.35 | 4261098.55 | 0.00 | 0.314297E+09 |
February | 20017506.10 | 3823150.72 | 16194355.39 | 1159.59 | 0.253933E+09 |
March | 79012322.88 | 31110726.97 | 47901595.91 | 20622753.07 | 0.195419E+09 |
April | 0.157746E+09 | 83034907.46 | 74711087.83 | 0.120198E+09 | 97238935.33 |
May | 0.216510E+09 | 0.122257E+09 | 94253100.08 | 0.208474E+09 | 52345532.40 |
June | 0.228909E+09 | 0.113795E+09 | 0.115115E+09 | 0.223613E+09 | 37293225.12 |
July | 0.211807E+09 | 0.101888E+09 | 0.109919E+09 | 0.195574E+09 | 52408351.20 |
August | 0.157760E+09 | 75271101.09 | 82489253.70 | 0.127410E+09 | 72110582.75 |
September | 80858376.75 | 30251368.62 | 50607008.13 | 40995595.27 | 92341996.47 |
October | 33824691.04 | 6911263.22 | 26913427.82 | 6741489.08 | 0.152383E+09 |
November | 8352982.49 | 447821.41 | 7905161.08 | 0.00 | 0.303714E+09 |
December | 1302235.19 | 13207.38 | 1289027.81 | 0.00 | 0.337499E+09 |
Annual Sum or Average | 0.120062E+10 | 0.569064E+09 | 0.631559E+09 | 0.943630E+09 | 0.196098E+10 |
Minimum of Months | 1302235.19 | 13207.38 | 1289027.81 | 0.00 | 37293225.12 |
Maximum of Months | 0.228909E+09 | 0.122257E+09 | 0.115115E+09 | 0.223613E+09 | 0.337499E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1157.95 | 15.71 | 1.92 | 13.79 | 0.00 | 0.00 |
February | 0.56 | 1010.92 | 86.36 | 23.03 | 63.33 | 0.00 | 0.00 |
March | 66.41 | 727.77 | 252.93 | 85.62 | 167.32 | 0.00 | 0.00 |
April | 416.61 | 366.83 | 566.87 | 244.57 | 322.30 | 0.00 | 0.00 |
May | 514.58 | 138.20 | 606.89 | 231.11 | 375.78 | 0.00 | 0.00 |
June | 626.06 | 80.79 | 695.17 | 255.46 | 439.71 | 0.00 | 0.00 |
July | 509.15 | 115.43 | 582.60 | 184.39 | 398.21 | 0.00 | 0.00 |
August | 357.99 | 181.60 | 449.81 | 151.17 | 298.64 | 0.00 | 0.00 |
September | 154.89 | 302.72 | 266.08 | 86.22 | 179.85 | 0.00 | 0.00 |
October | 15.63 | 622.93 | 109.73 | 24.17 | 85.56 | 0.00 | 0.00 |
November | 0.13 | 1124.10 | 41.36 | 11.72 | 29.64 | 0.00 | 0.00 |
December | 0.00 | 1228.27 | 4.32 | 0.31 | 4.01 | 0.00 | 0.00 |
Annual Sum or Average | 222.80 | 585.96 | 307.35 | 108.56 | 198.80 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 80.79 | 4.32 | 0.31 | 4.01 | 0.00 | 0.00 |
Maximum of Months | 626.06 | 1228.27 | 695.17 | 255.46 | 439.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1173.45 | 16.88 | 0.97 | 15.91 | 0.00 | 0.00 |
February | 0.00 | 1049.66 | 82.74 | 15.80 | 66.94 | 0.00 | 0.00 |
March | 77.00 | 729.61 | 295.00 | 116.15 | 178.84 | 0.00 | 0.00 |
April | 463.73 | 375.15 | 608.59 | 320.35 | 288.24 | 0.00 | 0.00 |
May | 778.35 | 195.44 | 808.35 | 456.45 | 351.90 | 0.00 | 0.00 |
June | 862.71 | 143.88 | 883.14 | 439.02 | 444.12 | 0.00 | 0.00 |
July | 730.19 | 195.67 | 790.80 | 380.41 | 410.39 | 0.00 | 0.00 |
August | 475.69 | 269.23 | 589.01 | 281.03 | 307.98 | 0.00 | 0.00 |
September | 158.16 | 356.26 | 311.95 | 116.71 | 195.24 | 0.00 | 0.00 |
October | 25.17 | 568.93 | 126.29 | 25.80 | 100.48 | 0.00 | 0.00 |
November | 0.00 | 1171.73 | 32.23 | 1.73 | 30.50 | 0.00 | 0.00 |
December | 0.00 | 1260.08 | 4.86 | 0.05 | 4.81 | 0.00 | 0.00 |
Annual Sum or Average | 299.22 | 621.82 | 380.72 | 180.45 | 200.27 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 143.88 | 4.86 | 0.05 | 4.81 | 0.00 | 0.00 |
Maximum of Months | 862.71 | 1260.08 | 883.14 | 456.45 | 444.12 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.310146E+10 | 42075936.09 | 5145799.60 | 36930136.48 | 0.00 | 0.00 |
February | 1358917.96 | 0.244563E+10 | 0.208925E+09 | 55726085.70 | 0.153199E+09 | 0.00 | 0.00 |
March | 0.177866E+09 | 0.194926E+10 | 0.677453E+09 | 0.229314E+09 | 0.448139E+09 | 0.00 | 0.00 |
April | 0.107985E+10 | 0.950819E+09 | 0.146932E+10 | 0.633919E+09 | 0.835404E+09 | 0.00 | 0.00 |
May | 0.137825E+10 | 0.370165E+09 | 0.162550E+10 | 0.619003E+09 | 0.100650E+10 | 0.00 | 0.00 |
June | 0.162274E+10 | 0.209400E+09 | 0.180188E+10 | 0.662153E+09 | 0.113972E+10 | 0.00 | 0.00 |
July | 0.136370E+10 | 0.309175E+09 | 0.156045E+10 | 0.493873E+09 | 0.106657E+10 | 0.00 | 0.00 |
August | 0.958851E+09 | 0.486408E+09 | 0.120476E+10 | 0.404893E+09 | 0.799872E+09 | 0.00 | 0.00 |
September | 0.401487E+09 | 0.784639E+09 | 0.689671E+09 | 0.223494E+09 | 0.466177E+09 | 0.00 | 0.00 |
October | 41872987.94 | 0.166846E+10 | 0.293905E+09 | 64748071.85 | 0.229157E+09 | 0.00 | 0.00 |
November | 348090.15 | 0.291366E+10 | 0.107199E+09 | 30375285.84 | 76823217.62 | 0.00 | 0.00 |
December | 0.00 | 0.328981E+10 | 11582101.12 | 832991.70 | 10749109.41 | 0.00 | 0.00 |
Annual Sum or Average | 0.702632E+10 | 0.184789E+11 | 0.969273E+10 | 0.342348E+10 | 0.626925E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.209400E+09 | 11582101.12 | 832991.70 | 10749109.41 | 0.00 | 0.00 |
Maximum of Months | 0.162274E+10 | 0.328981E+10 | 0.180188E+10 | 0.662153E+09 | 0.113972E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.314297E+10 | 45221128.95 | 2610143.49 | 42610985.45 | 0.00 | 0.00 |
February | 11595.91 | 0.253933E+10 | 0.200175E+09 | 38231507.16 | 0.161944E+09 | 0.00 | 0.00 |
March | 0.206226E+09 | 0.195419E+10 | 0.790123E+09 | 0.311107E+09 | 0.479016E+09 | 0.00 | 0.00 |
April | 0.120198E+10 | 0.972389E+09 | 0.157746E+10 | 0.830349E+09 | 0.747111E+09 | 0.00 | 0.00 |
May | 0.208474E+10 | 0.523455E+09 | 0.216510E+10 | 0.122257E+10 | 0.942531E+09 | 0.00 | 0.00 |
June | 0.223613E+10 | 0.372932E+09 | 0.228909E+10 | 0.113795E+10 | 0.115115E+10 | 0.00 | 0.00 |
July | 0.195574E+10 | 0.524084E+09 | 0.211807E+10 | 0.101888E+10 | 0.109919E+10 | 0.00 | 0.00 |
August | 0.127410E+10 | 0.721105E+09 | 0.157760E+10 | 0.752711E+09 | 0.824893E+09 | 0.00 | 0.00 |
September | 0.409956E+09 | 0.923420E+09 | 0.808584E+09 | 0.302514E+09 | 0.506070E+09 | 0.00 | 0.00 |
October | 67414760.73 | 0.152383E+10 | 0.338247E+09 | 69112632.15 | 0.269134E+09 | 0.00 | 0.00 |
November | 0.00 | 0.303714E+10 | 83529824.93 | 4478214.13 | 79051610.80 | 0.00 | 0.00 |
December | 0.00 | 0.337499E+10 | 13022351.93 | 132073.82 | 12890278.11 | 0.00 | 0.00 |
Annual Sum or Average | 0.943629E+10 | 0.196098E+11 | 0.120062E+11 | 0.569064E+10 | 0.631559E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.372932E+09 | 13022351.93 | 132073.82 | 12890278.11 | 0.00 | 0.00 |
Maximum of Months | 0.223613E+10 | 0.337499E+10 | 0.228909E+10 | 0.122257E+10 | 0.115115E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.5 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.6 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.24 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.87 | 6.41 | 3.45 | 5.65 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.84 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.69 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.46 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.84 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.6 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.5 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.58 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.01 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.76 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.27 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.32 | 11.70 | 4.67 | 18.87 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.74 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.88 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 7.99 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.5 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.0 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.5 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.32 | 11.70 | 6.20 | 18.87 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.1 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.2 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.0 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.8 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.6 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.23 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.64 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.01 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.94 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.32 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.33 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.28 | 141.00 | 225.33 |
August | 16.13 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.81 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 7.99 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.5 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.0 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.5 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.33 | 29.07 | 14.40 | 8.80 | 19.28 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.6 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.77 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.74 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.40 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.29 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.0 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.4 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.0 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.114193E+10 | -.105363E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -88302754.2 | 59.00 | 0.00 | 0.00 |
February | 0.104760E+10 | -967993018.7 | 0.00 | 0.00 | 672.00 | 0.00 | -79604318.1 | 59.00 | 0.00 | 0.00 |
March | 0.121924E+10 | -.113151E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87730019.4 | 59.00 | 0.00 | 0.00 |
April | 0.113493E+10 | -.105104E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -83889504.7 | 59.00 | 0.00 | 0.00 |
May | 0.116829E+10 | -.108503E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -83258054.7 | 59.00 | 0.00 | 0.00 |
June | 0.111515E+10 | -.104139E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -73758847.7 | 59.00 | 0.00 | 0.00 |
July | 0.104240E+10 | -968511153.9 | 0.00 | 0.00 | 744.00 | 0.00 | -73893763.0 | 59.00 | 0.00 | 0.00 |
August | 0.109076E+10 | -.101498E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -75782093.5 | 58.99 | 0.00 | 0.00 |
September | 0.102103E+10 | -939962412.2 | 0.00 | 0.00 | 720.00 | 0.00 | -81063483.4 | 58.99 | 0.00 | 0.00 |
October | 0.104819E+10 | -960936408.3 | 0.00 | 0.00 | 744.00 | 0.00 | -87254206.6 | 58.99 | 0.00 | 0.00 |
November | 0.104130E+10 | -955947240.4 | 0.00 | 0.00 | 720.00 | 0.00 | -85355087.8 | 58.99 | 0.00 | 0.00 |
December | 0.112449E+10 | -.103625E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -88240451.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.131953E+11 | -.122072E+11 | 8760.00 | -988132584.0 | 59.00 | |||||
Minimum of Months | 0.102103E+10 | -.113151E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -88302754.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.121924E+10 | -939962412.2 | 0.00 | 0.00 | 744.00 | 0.00 | -73758847.7 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 108.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 205.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 329.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 421.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 545.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 583.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 562.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 467.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 356.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 265.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 135.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | ||||||||||
Minimum of Months | 71.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 583.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.185764E+11 | 27786.55 | 01-JAN-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155753E+11 | 27786.55 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148963E+11 | 27786.55 | 01-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.721914E+10 | 27786.55 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.189533E+10 | 27786.55 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140356E+09 | 27786.55 | 01-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30874464.66 | 3865.76 | 05-JUL-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.278821E+09 | 27786.55 | 31-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.309064E+10 | 27786.55 | 01-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.898498E+10 | 27786.55 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155395E+11 | 27786.55 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180974E+11 | 27786.55 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104325E+12 | |||||||
Minimum of Months | 30874464.66 | 3865.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.185764E+11 | 27786.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.831533E+11 | 71473.09 | 01-JAN-00:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.690811E+11 | 71473.09 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.636309E+11 | 71473.09 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.316920E+11 | 71473.09 | 01-APR-00:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.285878E+10 | 71473.09 | 27-MAY-00:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15698025.29 | 4416.25 | 31-AUG-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.460524E+10 | 71473.09 | 28-SEP-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.390552E+11 | 71473.09 | 10-OCT-21:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.628564E+11 | 71473.09 | 01-NOV-00:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.799028E+11 | 71473.09 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.436851E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.831533E+11 | 71473.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.143013E+12 | 99427.36 | 01-JAN-18:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124003E+12 | 99427.36 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123226E+12 | 99427.36 | 01-MAR-23:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.564282E+11 | 99427.36 | 01-APR-18:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 22132461.42 | 10861.10 | 30-SEP-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.648255E+11 | 99427.36 | 27-OCT-03:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.921174E+11 | 99427.36 | 10-NOV-01:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141619E+12 | 99427.36 | 01-DEC-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.745255E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.143013E+12 | 99427.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 34273833.24 | 34273833.24 | 1807.60 | 13-MAY-15:50 | 1807.60 | 0.00 |
June | 0.00 | 0.00 | 0.202072E+10 | 0.196269E+10 | 14499.93 | 22-JUN-05:03 | 14499.93 | 0.00 |
July | 0.00 | 0.00 | 0.357410E+10 | 0.336248E+10 | 15576.75 | 25-JUL-05:02 | 13237.33 | 0.00 |
August | 0.00 | 0.00 | 0.211090E+10 | 0.200306E+10 | 15213.50 | 04-AUG-05:03 | 13385.51 | 0.00 |
September | 0.00 | 0.00 | 6354257.07 | 6354257.07 | 1164.11 | 02-SEP-16:00 | 1164.11 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.774634E+10 | 0.736886E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.357410E+10 | 0.336248E+10 | 15576.75 | 14499.93 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 89676190.28 | 86056172.54 | 5606.39 | 30-JUN-15:00 | 5544.86 | 0.00 |
July | 0.00 | 0.00 | 0.844107E+09 | 0.830104E+09 | 13361.49 | 21-JUL-16:00 | 13361.49 | 0.00 |
August | 0.00 | 0.00 | 93168520.76 | 87889819.21 | 4586.00 | 04-AUG-14:30 | 4413.67 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.102695E+10 | 0.100405E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.844107E+09 | 0.830104E+09 | 13361.49 | 13361.49 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.604143E+09 | 0.08 | 225.92 | 01-JAN-00:01 | 0.08 |
February | 0.537046E+09 | 0.08 | 225.92 | 01-FEB-00:02 | 0.08 |
March | 0.558847E+09 | 0.07 | 225.92 | 01-MAR-00:03 | 0.08 |
April | 0.312576E+09 | 0.04 | 225.92 | 01-APR-00:05 | 0.08 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 2710984.09 | 0.00 | 225.92 | 30-SEP-04:50 | 0.08 |
October | 0.412872E+09 | 0.05 | 225.92 | 01-OCT-00:10 | 0.08 |
November | 0.574593E+09 | 0.08 | 225.92 | 01-NOV-00:05 | 0.08 |
December | 0.605092E+09 | 0.08 | 225.92 | 01-DEC-00:02 | 0.08 |
Annual Sum or Average | 0.360788E+10 | 0.04 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.605092E+09 | 0.08 | 225.92 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.119339E+10 | 0.74 | 1016.11 | 21-JAN-16:00 | 0.95 |
February | 0.109294E+10 | 0.73 | 1016.11 | 01-FEB-08:50 | 0.96 |
March | 0.121929E+10 | 0.68 | 1016.11 | 02-MAR-09:30 | 0.96 |
April | 0.106839E+10 | 0.48 | 1016.11 | 03-APR-08:00 | 0.96 |
May | 0.106516E+10 | 0.39 | 1016.11 | 01-MAY-09:20 | 0.95 |
June | 0.104754E+10 | 0.38 | 1016.11 | 02-JUN-14:00 | 0.95 |
July | 0.101103E+10 | 0.36 | 1016.11 | 22-JUL-06:20 | 0.94 |
August | 0.108930E+10 | 0.38 | 1016.11 | 01-AUG-09:10 | 0.94 |
September | 0.102580E+10 | 0.39 | 1016.11 | 01-SEP-11:40 | 0.95 |
October | 0.106302E+10 | 0.46 | 1016.11 | 03-OCT-13:20 | 0.95 |
November | 0.108448E+10 | 0.65 | 1016.11 | 01-NOV-06:40 | 0.96 |
December | 0.116406E+10 | 0.74 | 1016.11 | 02-DEC-11:30 | 0.96 |
Annual Sum or Average | 0.131244E+11 | 0.53 | |||
Minimum of Months | 0.101103E+10 | 0.36 | 1016.11 | 0.94 | |
Maximum of Months | 0.121929E+10 | 0.74 | 1016.11 | 0.96 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.273201E+10 | 0.81 | 1594.10 | 06-JAN-12:10 | 0.92 |
February | 0.246673E+10 | 0.80 | 1594.10 | 03-FEB-11:00 | 0.92 |
March | 0.266085E+10 | 0.81 | 1594.10 | 06-MAR-08:08 | 0.92 |
April | 0.213779E+10 | 0.73 | 1594.10 | 01-APR-06:10 | 0.92 |
May | 0.169961E+10 | 0.43 | 1594.10 | 01-MAY-07:20 | 0.91 |
June | 0.164129E+10 | 0.36 | 1594.10 | 21-JUN-16:50 | 0.91 |
July | 0.157909E+10 | 0.34 | 1594.10 | 11-JUL-12:50 | 0.91 |
August | 0.170441E+10 | 0.36 | 1594.10 | 02-AUG-14:10 | 0.91 |
September | 0.165209E+10 | 0.45 | 1594.10 | 06-SEP-06:40 | 0.91 |
October | 0.218716E+10 | 0.77 | 1594.10 | 21-OCT-07:20 | 0.92 |
November | 0.239562E+10 | 0.81 | 1594.10 | 01-NOV-11:00 | 0.92 |
December | 0.265047E+10 | 0.82 | 1594.10 | 01-DEC-08:00 | 0.92 |
Annual Sum or Average | 0.255071E+11 | 0.62 | |||
Minimum of Months | 0.157909E+10 | 0.34 | 1594.10 | 0.91 | |
Maximum of Months | 0.273201E+10 | 0.82 | 1594.10 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.82 | 0.38 |
February | 3.53 | 0.14 |
March | 5.51 | 0.14 |
April | 2.12 | 0.03 |
May | 1.04 | 0.77 |
June | 2.06 | 3.50 |
July | 2.72 | 2.41 |
August | 3.26 | 2.82 |
September | 1.47 | 0.65 |
October | 3.50 | 0.00 |
November | 3.94 | 0.00 |
December | 3.04 | 0.22 |
Annual Sum or Average | 36.01 | 0.78 |
Minimum of Months | 1.04 | 0.00 |
Maximum of Months | 5.51 | 3.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 4.00 | 0.00 |
February | 3.89 | 0.00 |
March | 0.59 | 0.00 |
April | 0.50 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.36 | 0.00 |
Annual Sum or Average | 9.35 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 4.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.119339E+10 | 0.254985E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.109294E+10 | 0.215449E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.121929E+10 | 0.207783E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.106839E+10 | 0.103203E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.107358E+10 | 0.276558E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.153352E+10 | 0.210591E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.186111E+10 | 47154678.24 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.159287E+10 | 0.412766E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.102737E+10 | 0.450491E+10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.106302E+10 | 0.127247E+11 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.108448E+10 | 0.213365E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.116406E+10 | 0.247499E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.149740E+11 | 0.144894E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.102737E+10 | 47154678.24 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.186111E+10 | 0.254985E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.273201E+10 | 0.112336E+12 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.246673E+10 | 0.935602E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.266085E+10 | 0.875002E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.213779E+10 | 0.441437E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.169961E+10 | 0.416273E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.166661E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.181400E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.172982E+10 | 24306246.56 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.165209E+10 | 0.675930E+10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.218716E+10 | 0.549115E+11 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.239562E+10 | 0.874384E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.265047E+10 | 0.109206E+12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.257928E+11 | 0.600042E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.165209E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.273201E+10 | 0.112336E+12 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.119339E+10 | 0.00 | 0.185764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109294E+10 | 0.00 | 0.155753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121929E+10 | 0.00 | 0.148963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106839E+10 | 0.00 | 0.721914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106516E+10 | 34273833.24 | 0.189533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104754E+10 | 0.202072E+10 | 0.140356E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101103E+10 | 0.357410E+10 | 30874464.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108930E+10 | 0.211090E+10 | 0.278821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102580E+10 | 6354257.07 | 0.309064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106302E+10 | 0.00 | 0.898498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108448E+10 | 0.00 | 0.155395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116406E+10 | 0.00 | 0.180974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131244E+11 | 0.774634E+10 | 0.104325E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101103E+10 | 0.00 | 30874464.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.121929E+10 | 0.357410E+10 | 0.185764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.273201E+10 | 0.00 | 0.831533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.246673E+10 | 0.00 | 0.690811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.266085E+10 | 0.00 | 0.636309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.213779E+10 | 0.00 | 0.316920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169961E+10 | 0.00 | 0.285878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164129E+10 | 89676190.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157909E+10 | 0.844107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170441E+10 | 93168520.76 | 15698025.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165209E+10 | 0.00 | 0.460524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.218716E+10 | 0.00 | 0.390552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.239562E+10 | 0.00 | 0.628564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.265047E+10 | 0.00 | 0.799028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.255071E+11 | 0.102695E+10 | 0.436851E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.273201E+10 | 0.844107E+09 | 0.831533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.119339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106516E+10 | 0.00 | 0.00 | 0.00 | 8421204.11 | 0.00 | 0.276558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104754E+10 | 0.00 | 0.00 | 0.00 | 0.485977E+09 | 0.00 | 0.210591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101103E+10 | 0.00 | 0.00 | 0.00 | 0.850076E+09 | 0.00 | 47154678.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108930E+10 | 0.00 | 0.00 | 0.00 | 0.503570E+09 | 0.00 | 0.412766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102580E+10 | 0.00 | 0.00 | 0.00 | 1566623.47 | 0.00 | 0.450491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131244E+11 | 0.00 | 0.00 | 0.00 | 0.184961E+10 | 0.00 | 0.144894E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.101103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47154678.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.121929E+10 | 0.00 | 0.00 | 0.00 | 0.850076E+09 | 0.00 | 0.254985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.273201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112336E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.246673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.266085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.213779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164129E+10 | 0.00 | 0.00 | 0.00 | 25326343.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157909E+10 | 0.00 | 0.00 | 0.00 | 0.234911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170441E+10 | 0.00 | 0.00 | 0.00 | 25405982.14 | 0.00 | 24306246.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.218716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.239562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.265047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109206E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.255071E+11 | 0.00 | 0.00 | 0.00 | 0.285644E+09 | 0.00 | 0.600042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.157909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.273201E+10 | 0.00 | 0.00 | 0.00 | 0.234911E+09 | 0.00 | 0.112336E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552188E+10 | 0.00 | 0.00 | 0.16 |
February | 536564.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456296E+10 | 0.00 | 0.00 | 0.16 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445089E+10 | 0.00 | 0.00 | 0.16 |
April | 87816474.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237964E+10 | 0.00 | 0.00 | 0.15 |
May | 0.538879E+09 | 0.00 | 0.00 | 25227.36 | 0.00 | 0.712338E+09 | 19205896.87 | 0.00 | 0.14 |
June | 0.264745E+09 | 7208594.43 | 0.00 | 2611921.32 | 0.00 | 57822848.97 | 0.574309E+09 | 0.00 | 0.15 |
July | 0.146264E+09 | 24078518.88 | 0.00 | 4499816.84 | 0.00 | 24166836.19 | 0.451623E+09 | 0.00 | 0.14 |
August | 0.434429E+09 | 879965.41 | 0.00 | 3153728.39 | 0.00 | 0.120999E+09 | 0.582438E+09 | 0.00 | 0.15 |
September | 0.461752E+09 | 0.00 | 0.00 | 9106.28 | 0.00 | 0.138613E+10 | 8897581.58 | 0.00 | 0.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313106E+10 | 0.00 | 0.00 | 0.14 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503309E+10 | 0.00 | 0.00 | 0.15 |
December | 397160.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.569642E+10 | 0.00 | 0.00 | 0.15 |
Annual Sum or Average | 0.193482E+10 | 32167078.72 | 0.00 | 10299800.18 | 0.00 | 0.330774E+11 | 0.163647E+10 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24166836.19 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.538879E+09 | 24078518.88 | 0.00 | 4499816.84 | 0.00 | 0.569642E+10 | 0.582438E+09 | 0.00 | 0.16 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284709E+11 | 0.00 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236134E+11 | 0.00 | 0.00 | 0.32 |
March | 0.544933E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207423E+11 | 0.00 | 0.00 | 0.31 |
April | 0.228790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768390E+10 | 0.00 | 0.00 | 0.26 |
May | 0.262484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562778E+09 | 0.00 | 0.00 | 0.21 |
June | 0.308672E+10 | 754248.61 | 0.00 | 99657.22 | 0.00 | 0.00 | 87054380.92 | 0.00 | 0.21 |
July | 0.266639E+10 | 24986938.12 | 0.00 | 996756.79 | 7617555.68 | 0.00 | 0.353454E+09 | 0.00 | 0.20 |
August | 0.400365E+10 | 0.00 | 0.00 | 184612.63 | 0.00 | 0.00 | 0.112844E+09 | 0.00 | 0.21 |
September | 0.396896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125348E+10 | 0.00 | 0.00 | 0.21 |
October | 0.112124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120525E+11 | 0.00 | 0.00 | 0.26 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245273E+11 | 0.00 | 0.00 | 0.29 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289874E+11 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.203046E+11 | 25741186.73 | 0.00 | 1281026.64 | 7617555.68 | 0.147894E+12 | 0.553352E+09 | 0.00 | 0.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.400365E+10 | 24986938.12 | 0.00 | 996756.79 | 7617555.68 | 0.289874E+11 | 0.353454E+09 | 0.00 | 0.32 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |