Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2020-06-03 19:11:56
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2609.15 | 539.62 | 539.62 |
Net Site Energy | 2609.15 | 539.62 | 539.62 |
Total Source Energy | 4532.41 | 937.39 | 937.39 |
Net Source Energy | 4532.41 | 937.39 | 937.39 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1791.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 99.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 62.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.84 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 818.10 | 1791.05 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1791.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 99.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 61.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.84 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 118.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 21.43 | 370.42 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 169.20 | 370.42 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 118.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 21.43 | 370.42 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 169.20 | 370.42 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 818.097 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 818.097 | 100.00 |
Total On-Site and Utility Electric Sources | 818.097 | 100.00 |
Total Electricity End Uses | 818.097 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 85.67 |
Time Setpoint Not Met During Occupied Cooling | 1.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2249.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.6337 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.5069 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.5069 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-14:00 | 18-JAN-17:10 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 477107.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 17327.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6079.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1769.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 70478.61 | 477107.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 477107.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 17327.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 3774.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1769.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1941.50 | 0.00 | 0.00 | 0.00 |
Cooling | 46.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1507.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 313.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 196.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 85.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2590.91 | 1941.50 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 401.54 | 0.00 | 0.00 | 0.00 |
Cooling | 9.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 64.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 40.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 535.85 | 401.54 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 401.54 | 0.00 | 0.00 | 0.00 |
Cooling | 9.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 64.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 40.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 535.85 | 401.54 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.03 |
ZONE2 FINE STORAGE DIRECT AIR | 2.37 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 6.71 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 6.71 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 266081.87 |
PSZ-OFFICE HEATING COIL | 28148.66 |
PSZ-FINE STORAGE HEATING COIL | 87455.11 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 266081.85 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.00 | 1.000000 | 1.03 |
PSZ-FINE STORAGE | 2.37 | 2.37 | 2.37 | 2.37 | 2.37 | 2.37 | 1.00 | 1.00 | 2.37 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.03 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 2.37 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 1.03 | 19366.99 | 28148.66 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.37 | 2.37 | 2.37 | 2.37 | 58943.30 | 87455.11 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.03 | 0.515945 | 1.03 | 18887.91 | 19366.99 | 9683.50 | 19366.99 | 0.755267 | 0.755270 | 0.755270 | 0.755270 |
PSZ-FINE STORAGE COOLING COIL | 2.37 | 1.19 | 2.37 | 57419.63 | 58943.30 | 29471.65 | 58943.30 | 0.676084 | 0.676080 | 0.676080 | 0.676080 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.03 | 1176.47 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.37 | 2597.97 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.634 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.707 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.507 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.507 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.507 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.066 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2518.900 | 10.634 | 503.780 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2518.900 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11853.648 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11853.648 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27263.390 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27263.390 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2893 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2893 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.4128 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.4128 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1413 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.5841E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.5469E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.4128 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.457 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.457 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.323 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.323 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.998 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 17.04 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 18.21 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.323 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.87112823E-12 | 0.85080972E-17 | 0.21755189E-17 | 0.0000000 |
2 | 1 | -5.2160329 | 0.44465164E-04 | -0.55377147E-04 | 0.16700973E-12 |
3 | 0 | 5.5053245 | 0.28924715 | 0.28934699 | |
4 | 2 | 0.87112823E-12 | 0.85080972E-17 | 0.21755189E-17 | 0.0000000 |
5 | 1 | -5.2160329 | 0.44465164E-04 | -0.55377147E-04 | 0.16700973E-12 |
6 | 0 | 5.5053245 | 0.28924715 | 0.28934699 | |
7 | 4 | 0.79581057E-12 | 0.97316148E-16 | -0.20714918E-14 | 0.11395926E-15 |
8 | 3 | -0.38950733E-03 | 0.29153728E-06 | -0.56547345E-04 | 0.15269480E-12 |
9 | 2 | 1.7508611 | 0.63413892E-02 | 1.1490629 | -0.74675203E-04 |
10 | 1 | -7.1137977 | 0.16376069 | -17.153076 | 0.33557628 |
11 | 0 | 5.6376123 | 0.10418388 | 16.278356 | |
12 | 4 | 0.79581057E-12 | 0.97316148E-16 | -0.20714918E-14 | 0.11395926E-15 |
13 | 3 | -0.38950733E-03 | 0.29153728E-06 | -0.56547345E-04 | 0.15269480E-12 |
14 | 2 | 1.7508611 | 0.63413892E-02 | 1.1490629 | -0.74675203E-04 |
15 | 1 | -7.1137977 | 0.16376069 | -17.153076 | 0.33557628 |
16 | 0 | 5.6376123 | 0.10418388 | 16.278356 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.8391346 | 2.8391346 | 2.8391346 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8391346 | 2.8391346 | 2.8391346 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.30042996E-08 | -0.19492532E-14 | 0.18571942E-14 | -0.50265421E-16 |
55 | 6 | 0.40686135E-05 | 0.27025218E-08 | 0.31944093E-02 | -0.26797382E-04 |
56 | 5 | -0.28598357E-03 | 0.15982348E-05 | -0.22398257 | 0.19584275E-02 |
57 | 4 | 0.65354345E-02 | 0.72696005E-04 | 4.8338424 | -0.45306284E-01 |
58 | 3 | -0.57256805E-01 | 0.57768437E-03 | -38.045688 | 0.39892203 |
59 | 2 | 0.20312160 | 0.96045137E-03 | 116.53119 | -1.4185711 |
60 | 1 | -0.29305691 | 0.29236276E-03 | -143.93511 | 2.0494970 |
61 | 0 | 0.14285049 | 0.70905046E-05 | 60.838472 | |
62 | 7 | -0.73310212E-08 | 0.16277859E-15 | -0.15558641E-14 | 0.17403554E-16 |
63 | 6 | 0.21213446E-05 | 0.11327280E-08 | 0.32008460E-02 | -0.26851379E-04 |
64 | 5 | -0.12816801E-03 | 0.66411688E-06 | -0.22434819 | 0.19616548E-02 |
65 | 4 | 0.27852559E-02 | 0.30072908E-04 | 4.8399282 | -0.45364789E-01 |
66 | 3 | -0.23934818E-01 | 0.23808113E-03 | -38.080046 | 0.39930184 |
67 | 2 | 0.84241938E-01 | 0.39442809E-03 | 116.59803 | -1.4194653 |
68 | 1 | -0.12110434 | 0.11951395E-03 | -143.97445 | 2.0501436 |
69 | 0 | 0.58923671E-01 | 0.28881054E-05 | 60.838472 | |
70 | 7 | -0.78336681E-08 | 0.23380828E-15 | -0.37470831E-14 | 0.17001158E-16 |
71 | 6 | 0.20573783E-05 | 0.10635783E-08 | 0.32011355E-02 | -0.26853807E-04 |
72 | 5 | -0.12166809E-03 | 0.62270931E-06 | -0.22436462 | 0.19617998E-02 |
73 | 4 | 0.26229018E-02 | 0.28177105E-04 | 4.8402013 | -0.45367414E-01 |
74 | 3 | -0.22467346E-01 | 0.22293819E-03 | -38.081586 | 0.39931887 |
75 | 2 | 0.78971204E-01 | 0.36912476E-03 | 116.60102 | -1.4195054 |
76 | 1 | -0.11345740 | 0.11176675E-03 | -143.97621 | 2.0501725 |
77 | 0 | 0.55185584E-01 | 0.26976542E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.20714918E-14 | 0.97316148E-16 | 0.79581057E-12 | 0.11395926E-15 |
85 | 3 | -0.56547345E-04 | 0.29153728E-06 | -0.38950733E-03 | 0.15269480E-12 |
86 | 2 | 1.1490629 | 0.63413892E-02 | 1.7508611 | -0.74675203E-04 |
87 | 1 | -17.153076 | 0.16376069 | -7.1137977 | 0.33557628 |
88 | 0 | 16.278356 | 0.10418388 | 5.6376123 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 28 | 1 | VerySmooth | 2.843 | 0.395 | 0.315 | 0.401 |
2 | SKYLIGHT_U_0.6_SHGC_0.4 | 29 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 30 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9969.09804 | 11962.91764 | 0.85991 | 1.03189 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 29.71600 | 1.53444E-002 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 14119.08595 | 16942.90313 | 0.41572 | 0.49886 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20000 | 3.61342E-004 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 26276.06864 | 31531.28237 | 1.76705 | 2.12047 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53444E-002 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 79818.76065 | 95782.51279 | 1.97804 | 2.37365 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20000 | 1.53444E-002 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 221734.87118 | 266081.84541 | 5.59466 | 6.71359 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -26.20000 | 3.61342E-004 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 14857.31 | 1.03189 | 1.03189 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 16489.42 | 0.49886 | 0.49886 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 38174.16 | 2.12047 | 2.12047 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 87455.11 | 2.37365 | 2.37365 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03189 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.37365 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.71359 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 6.71359 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 266081.86980 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 266081.84541 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03189 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03189 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03189 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03189 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.03189 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.03189 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.37365 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.37365 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.37365 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.37365 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.37365 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.37365 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.03189 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.37365 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.03189 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.03189 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.03189 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.03189 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.03189 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.03189 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51595 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.03189 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18887.91341 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 19366.99000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9683.49500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 19366.99000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.75527 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.75527 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.75527 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.75527 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19366.99000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28148.66141 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.03189 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1176.47289 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28148.66141 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.37365 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.37365 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.37365 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.37365 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.37365 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.37365 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.18683 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.37365 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 57419.62952 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 58943.30000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 29471.65000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 58943.30000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 58943.30000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 87455.10662 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.37365 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2597.96940 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 87455.10662 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 18565.9 | 10.28 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 57098.3 | 13.39 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 10 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.2242084993 | 0.2016518930 | Pass | Pass | 0.6744959538 | 0.9745832820 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.6974114353 | 0.6565158380 | Pass | Pass | 0.7340021549 | 0.8839916759 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 4.2583831822E-005 | 1.0999970567E-004 | Pass | Pass | 2.3648320215E-002 | 2.7736093472E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.278 | 0.289 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.389 | 0.413 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.389 | 0.413 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.389 | 0.413 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.278 | 0.289 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.141 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.058 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.055 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.102 | 0.395 | 0.401 | ||||||||||||
North Total or Average | 6.51 | 2.843 | 0.395 | 0.401 | ||||||||||||
Non-North Total or Average | 26.02 | 3.167 | 0.395 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.6337 | 236.88 | 2518.90 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.62 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.5069 | 1393.41 | 11853.65 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 135.00 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.5069 | 3204.84 | 27263.39 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 310.50 |
Interior Lighting Total | 8.6111 | 4835.13 | 41635.94 | 476.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 6311.00 | AstronomicalClock | - | 83.63 | 83.63 | 99.07 | |
Exterior Lighting Total | 6311.00 | 99.07 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19366.99 | 14627.31 | 4739.68 | 0.76 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 58943.30 | 39850.39 | 19092.91 | 0.68 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 18565.9 | 10.28 | ||||
PSZ-FINE STORAGE COOLING COIL | 57098.3 | 13.39 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 266081.87 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28148.66 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 87455.11 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 6.71 | 623.76 | 92.91 | 1.00 | 3.07 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.03 | 1176.47 | 1140.11 | 1.00 | 1.35 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.37 | 2597.97 | 1094.51 | 1.00 | 1.26 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9969.10 | 11962.92 | 50.50 | 0.860 | 1.032 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00854 | 29.72 | 0.01534 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 26276.07 | 31531.28 | 22.63 | 1.767 | 2.120 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.70 | 0.00929 | 31.20 | 0.01534 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00396 | 31.20 | 0.01534 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 14119.09 | 16942.90 | 71.53 | 0.416 | 0.499 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00714 | -26.20 | 0.00036 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 79818.76 | 95782.51 | 68.74 | 1.978 | 2.374 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.54 | 0.00542 | -26.20 | 0.00036 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 221734.87 | 266081.85 | 83.02 | 5.595 | 6.714 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 10.00 | 9.98 | 0.00799 | -26.20 | 0.00036 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.03 | 1.03 | 0.50 | 0.50 | 1.0319 | 1.0319 | 1.0319 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.12 | 2.12 | 2.37 | 2.37 | 2.3736 | 2.3736 | 2.3736 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 266081.870 | 266081.870 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 266081.87 | 266081.87 | 6.713593 | 4.72 | 4.72 | 0.00688400 | 43.33 | 26.49 | 0.01600000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 9.98 | 0.00799466 | 100.0000 | 266081.85 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 19366.990 | 0.000 | 1.031890 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 19366.99 | 16019.62 | 1.031890 | 24.48 | 16.65 | 0.00921209 | 12.00 | 10.84 | 0.00800000 | 29.72 | 0.01534435 | 22.70 | 9.9124 | 23.90 | 0.00853735 | 44.1014 | 9969.10 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28148.661 | 28148.661 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 28148.66 | 28148.66 | 1.031894 | 11.36 | 8.16 | 0.00575317 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 9.9123 | 21.10 | 0.00714384 | 43.8508 | 14119.09 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 58943.300 | 0.000 | 2.373650 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 58943.30 | 43463.23 | 2.373650 | 27.60 | 18.70 | 0.01050575 | 12.00 | 10.84 | 0.00800000 | 31.20 | 0.01534436 | 23.10 | 17.8928 | 26.70 | 0.00929388 | 40.5993 | 26055.31 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 87455.107 | 87455.107 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 87455.11 | 87455.11 | 2.373647 | 8.08 | 5.12 | 0.00451535 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 17.8928 | 15.54 | 0.00542060 | 47.2826 | 79818.76 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 266081.870 | 266081.870 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1486 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 6.713593 | 7.71093636 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 266081.87 | 266081.87 | 1.0000 | 7.71093636 | 6.713593 | 4.72 | 4.72 | 0.00688400 | 22015.2 | 43.33 | 26.49 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 266081.87 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 9.98 | 0.00799466 | 9.98 | 0.00799466 | 100.0000 | 266081.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19366.990 | 0.000 | 1.031890 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9648 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 19366.99 | 16019.62 | 1.0000 | 1.18518327 | 1.031890 | 24.48 | 16.65 | 0.00921209 | 48051.7 | 12.00 | 10.84 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19366.99 | 29.72 | 0.01534435 | 22.70 | 0.10228487 | 9.9124 | 23.90 | 0.00853735 | 23.90 | 0.00853735 | 44.1014 | 9969.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28148.661 | 28148.661 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.031894 | 1.18518820 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 28148.66 | 28148.66 | 1.0000 | 1.18518820 | 1.031894 | 11.36 | 8.16 | 0.00575317 | 25925.1 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28148.66 | -26.20 | 0.00036134 | -26.20 | 0.10228487 | 9.9123 | 21.05 | 0.00714384 | 21.10 | 0.00714384 | 43.8508 | 14119.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 58943.300 | 0.000 | 2.373650 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3697 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 58943.30 | 43463.23 | 1.0000 | 2.72626954 | 2.373650 | 27.60 | 18.70 | 0.01050575 | 54545.3 | 12.00 | 10.84 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58943.30 | 31.20 | 0.01534436 | 23.10 | 0.42471267 | 17.8928 | 26.70 | 0.00929388 | 26.70 | 0.00929388 | 40.5993 | 26055.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 87455.107 | 87455.107 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.373647 | 2.72626579 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 87455.11 | 87455.11 | 1.0000 | 2.72626579 | 2.373647 | 8.08 | 5.12 | 0.00451535 | 19475.9 | 40.00 | 20.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87455.11 | -26.20 | 0.00036134 | -26.20 | 0.42471267 | 17.8928 | 15.55 | 0.00542060 | 15.54 | 0.00542060 | 47.2826 | 79818.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE OA CONTROLLER | DifferentialDryBulb | 0.10 | 1.03 | - | |||
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 2.37 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2899.50 | 2833.83 | 2249.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2899.50 | 2833.83 | 2249.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 212.67 | 1.83 | 85.67 | 1.83 |
ZONE2 FINE STORAGE | 748.50 | 10.33 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 44.83 | 0.00 | 0.00 | 0.00 |
Facility | 908.33 | 12.17 | 85.67 | 1.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.651 | 0.447 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 818.10 | 5421.86 | 19-MAR-08:50 | 70478.61 | 04-AUG-15:00 |
Electricity:Building | 615.80 | 4938.86 | 01-JAN-00:10 | 47606.95 | 26-JUN-14:00 |
Electricity:Zone:ZONE1 OFFICE | 62.57 | 1027.15 | 01-JAN-00:10 | 3852.05 | 02-JAN-08:10 |
InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.62 | 453.40 | 01-JAN-00:10 | 1939.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 418.24 | 2726.34 | 01-JAN-00:10 | 33679.30 | 26-JUN-13:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 310.51 | 2726.34 | 01-JAN-00:10 | 23173.88 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 26.84 | 483.00 | 02-JAN-06:40 | 2940.29 | 17-FEB-12:50 |
WaterSystems:Electricity | 26.84 | 483.00 | 02-JAN-06:40 | 2940.29 | 17-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 26.84 | 483.00 | 02-JAN-06:40 | 2940.29 | 17-FEB-12:50 |
Fans:Electricity | 62.12 | 0.00 | 18-MAR-17:10 | 6079.74 | 29-JUL-14:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.39 | 0.00 | 01-JAN-00:10 | 2305.29 | 26-JUN-18:00 |
Ventilation (simple):Fans:Electricity | 0.39 | 0.00 | 01-JAN-00:10 | 2305.29 | 26-JUN-18:00 |
ElectricityPurchased:Facility | 818.10 | 5421.86 | 19-MAR-08:50 | 70478.61 | 04-AUG-15:00 |
ElectricityPurchased:Plant | 818.10 | 5421.86 | 19-MAR-08:50 | 70478.61 | 04-AUG-15:00 |
Cogeneration:ElectricityPurchased | 818.10 | 5421.86 | 19-MAR-08:50 | 70478.61 | 04-AUG-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 818.10 | 5421.86 | 19-MAR-08:50 | 70478.61 | 04-AUG-15:00 |
ElectricityNet:Plant | 818.10 | 5421.86 | 19-MAR-08:50 | 70478.61 | 04-AUG-15:00 |
Cogeneration:ElectricityNet | 818.10 | 5421.86 | 19-MAR-08:50 | 70478.61 | 04-AUG-15:00 |
Electricity:HVAC | 76.38 | 0.00 | 18-MAR-17:10 | 22691.03 | 04-AUG-15:50 |
General:Fans:Electricity | 61.73 | 0.00 | 18-MAR-17:10 | 4398.21 | 02-JAN-09:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 14.66 | 0.00 | 01-JAN-00:10 | 18916.59 | 04-AUG-15:50 |
ExteriorLights:Electricity | 99.07 | 0.00 | 01-JAN-08:00 | 6311.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 99.07 | 0.00 | 01-JAN-08:00 | 6311.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1791.05 | 0.00 | 18-MAR-14:40 | 477107.05 | 18-JAN-17:10 |
Gas:HVAC | 1791.05 | 0.00 | 18-MAR-14:40 | 477107.05 | 18-JAN-17:10 |
Heating:Gas | 1791.05 | 0.00 | 18-MAR-14:40 | 477107.05 | 18-JAN-17:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2838.41 | 0.00 | 18-MAR-17:10 | 761649.28 | 09-DEC-06:20 |
EnergyTransfer:Building | 1400.61 | 0.00 | 18-MAR-17:10 | 382336.66 | 09-DEC-06:20 |
EnergyTransfer:Zone:ZONE1 OFFICE | 78.71 | 0.00 | 01-JAN-00:40 | 29939.22 | 03-FEB-07:10 |
Heating:EnergyTransfer | 1360.58 | 0.00 | 18-MAR-17:10 | 382336.66 | 09-DEC-06:20 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 61.36 | 0.00 | 01-JAN-00:40 | 29939.22 | 03-FEB-07:10 |
Cooling:EnergyTransfer | 40.03 | 0.00 | 01-JAN-00:10 | 33626.05 | 04-AUG-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 17.35 | 0.00 | 01-JAN-00:10 | 9960.60 | 04-AUG-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 368.64 | 0.00 | 01-JAN-00:40 | 90115.52 | 09-DEC-07:20 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 345.95 | 0.00 | 01-JAN-00:40 | 90115.52 | 09-DEC-07:20 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 22.68 | 0.00 | 01-JAN-00:10 | 24828.97 | 04-AUG-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 953.26 | 0.00 | 24-FEB-09:40 | 269239.36 | 09-DEC-08:40 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 953.26 | 0.00 | 24-FEB-09:40 | 269239.36 | 09-DEC-08:40 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1437.80 | 0.00 | 18-MAR-14:40 | 381685.64 | 18-JAN-17:10 |
HeatingCoils:EnergyTransfer | 1385.12 | 0.00 | 18-MAR-14:40 | 381685.64 | 18-JAN-17:10 |
CoolingCoils:EnergyTransfer | 52.67 | 0.00 | 01-JAN-00:10 | 64113.37 | 04-AUG-16:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 61.362 | -17.351 | 0.000 | 0.000 | 3.976 | 30.619 | 31.946 | 8.999 | 0.000 | 0.661 | 0.000 | 0.000 | -13.903 | 0.000 | -42.760 | -63.548 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 345.954 | -22.682 | 0.000 | 0.000 | 0.000 | 135.003 | 0.000 | 0.000 | 0.000 | 1.779 | 0.003 | 0.000 | 0.000 | 0.000 | -310.172 | -149.882 |
ZONE3 BULK STORAGE | 953.260 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 310.507 | 107.336 | 17.880 | 0.000 | 19.098 | 0.000 | 0.000 | -12.309 | 0.000 | -1102.509 | -293.263 |
Total Facility | 953.260 | 0.000 | 407.315 | -40.033 | 0.000 | 0.000 | 3.976 | 476.129 | 139.282 | 26.878 | 0.000 | 21.539 | 0.003 | 0.000 | -26.212 | 0.000 | -1455.441 | -506.692 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 19-JUL-05:02 | 0.00 | 0.00 | 0.00 | -20366.95 | 0.00 | 0.00 | 35.47 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 20447.65 | 0.00 | -378.67 | 0.00 | -890.60 | 0.00 |
ZONE2 FINE STORAGE | 18-JUL-18:41 | 0.00 | 0.00 | 0.00 | -50417.77 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 49552.95 | 0.00 | -0.00 | 0.00 | -320.55 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-JUL-18:41 | 0.00 | 0.00 | 0.00 | -50417.77 | 0.00 | 0.00 | 0.00 | 4365.11 | 2623.78 | 1384.07 | 0.00 | 0.00 | 44183.15 | 0.00 | -310.65 | 0.00 | -1827.69 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 01-FEB-06:31 | 0.00 | 0.00 | 31269.32 | 0.00 | 0.00 | 0.00 | 58.36 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1904.42 | 0.00 | -4676.87 | -25899.49 |
ZONE2 FINE STORAGE | 09-DEC-06:41 | 0.00 | 0.00 | 96374.91 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -56184.22 | -41376.06 |
ZONE3 BULK STORAGE | 09-DEC-08:13 | 269955.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20447.54 | 8200.12 | 0.00 | 0.00 | 0.00 | 29538.41 | 0.00 | -1250.24 | 0.00 | -326891.32 | 0.00 |
Total Facility | 09-DEC-07:03 | 266570.99 | 0.00 | 119135.03 | 0.00 | 0.00 | 0.00 | 88.76 | 24528.16 | 3006.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3023.72 | 0.00 | -341791.44 | -68514.07 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0319 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.0319 | 0.0991 | 1.0000 | 0.1023 | 0.0991 | ||
PSZ-FINE STORAGE | 2.3736 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.3736 | 0.2003 | 1.0000 | 0.4247 | 0.1789 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0319 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.0319 | 1.0000 | 1.0000 | 0.1023 | 0.0991 | ||
PSZ-FINE STORAGE | 2.3736 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.3736 | 1.0000 | 1.0000 | 0.4247 | 0.1789 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0319 | 1.0319 | 1.0319 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.3736 | 2.3736 | 2.3736 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0319 | 1.0319 | 1.0319 | 1.0319 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.3736 | 2.3736 | 2.3736 | 2.3736 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0319 | 1.0319 | 1.0319 | 0.1023 | 0.2050 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.3736 | 2.3736 | 2.3736 | 0.4247 | 0.1789 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0319 | 1.0319 | 1.0319 | 1.0319 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.3736 | 2.3736 | 2.3736 | 2.3736 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 85.67 |
Number of hours cooling loads not met | 1.83 |
Number of hours not met | 87.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 1791.05 | 477107.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 14.66 | 18916.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 476.13 | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 99.07 | 6311.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.39 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 61.73 | 4398.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.84 | 2940.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 818.10 |
Natural Gas | 0.00 | 1791.05 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 2609.15 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 98.47 |
Space Heating | 0.00 |
Space Cooling | 3.03 |
Fans (All) | 12.85 |
Service Water Heating | 5.55 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 169.20 |
Subtotal | 169.20 |
Natural Gas [MJ/m2] | |
Space Heating | 370.42 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 370.42 |
Subtotal | 370.42 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 18.25 |
Space Heating | 68.65 |
Space Cooling | 0.56 |
Fans (All) | 2.38 |
Service Water Heating | 1.03 |
Receptacle Equipment | 5.34 |
Miscellaneous | 3.80 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.519595E+12 |
February | 0.000 | 0.357012E+12 |
March | 0.000 | 0.208987E+12 |
April | 0.000 | 0.599358E+11 |
May | 0.000 | 0.346342E+10 |
June | 0.000 | 0.125252E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.230334E+10 |
October | 0.000 | 0.230406E+11 |
November | 0.000 | 0.214925E+12 |
December | 0.000 | 0.401667E+12 |
Annual Sum or Average | 0.179105E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.519595E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.519595E+12 |
February | 0.000 | 0.357012E+12 |
March | 0.000 | 0.208987E+12 |
April | 0.000 | 0.599358E+11 |
May | 0.000 | 0.346342E+10 |
June | 0.000 | 0.125252E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.230334E+10 |
October | 0.000 | 0.230406E+11 |
November | 0.000 | 0.214925E+12 |
December | 0.000 | 0.401667E+12 |
Annual Sum or Average | 0.179105E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.519595E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.519595E+12 |
February | 0.000 | 0.357012E+12 |
March | 0.000 | 0.208987E+12 |
April | 0.000 | 0.599358E+11 |
May | 0.000 | 0.346342E+10 |
June | 0.000 | 0.125252E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.230334E+10 |
October | 0.000 | 0.230406E+11 |
November | 0.000 | 0.214925E+12 |
December | 0.000 | 0.401667E+12 |
Annual Sum or Average | 0.179105E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.519595E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.519595E+12 |
February | 0.000 | 0.357012E+12 |
March | 0.000 | 0.208987E+12 |
April | 0.000 | 0.599358E+11 |
May | 0.000 | 0.346342E+10 |
June | 0.000 | 0.125252E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.230334E+10 |
October | 0.000 | 0.230406E+11 |
November | 0.000 | 0.214925E+12 |
December | 0.000 | 0.401667E+12 |
Annual Sum or Average | 0.179105E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.519595E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.519595E+12 |
February | 0.000 | 0.357012E+12 |
March | 0.000 | 0.208987E+12 |
April | 0.000 | 0.599358E+11 |
May | 0.000 | 0.346342E+10 |
June | 0.000 | 0.125252E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.230334E+10 |
October | 0.000 | 0.230406E+11 |
November | 0.000 | 0.214925E+12 |
December | 0.000 | 0.401667E+12 |
Annual Sum or Average | 0.179105E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.519595E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.519595E+12 |
February | 0.000 | 0.357012E+12 |
March | 0.000 | 0.208987E+12 |
April | 0.000 | 0.599358E+11 |
May | 0.000 | 0.346342E+10 |
June | 0.000 | 0.125252E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.230334E+10 |
October | 0.000 | 0.230406E+11 |
November | 0.000 | 0.214925E+12 |
December | 0.000 | 0.401667E+12 |
Annual Sum or Average | 0.179105E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.519595E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.519595E+12 |
February | 0.000 | 0.357012E+12 |
March | 0.000 | 0.208987E+12 |
April | 0.000 | 0.599358E+11 |
May | 0.000 | 0.346342E+10 |
June | 0.000 | 0.125252E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.230334E+10 |
October | 0.000 | 0.230406E+11 |
November | 0.000 | 0.214925E+12 |
December | 0.000 | 0.401667E+12 |
Annual Sum or Average | 0.179105E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.519595E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.519595E+12 |
February | 0.000 | 0.357012E+12 |
March | 0.000 | 0.208987E+12 |
April | 0.000 | 0.599358E+11 |
May | 0.000 | 0.346342E+10 |
June | 0.000 | 0.125252E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.230334E+10 |
October | 0.000 | 0.230406E+11 |
November | 0.000 | 0.214925E+12 |
December | 0.000 | 0.401667E+12 |
Annual Sum or Average | 0.179105E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.519595E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.519595E+12 |
February | 0.000 | 0.357012E+12 |
March | 0.000 | 0.208987E+12 |
April | 0.000 | 0.599358E+11 |
May | 0.000 | 0.346342E+10 |
June | 0.000 | 0.125252E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.230334E+10 |
October | 0.000 | 0.230406E+11 |
November | 0.000 | 0.214925E+12 |
December | 0.000 | 0.401667E+12 |
Annual Sum or Average | 0.179105E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.519595E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -2.8 | -3.2 | 0.194514E+09 | 236.59 | 21-JAN-13:20 | -5.7 | -6.5 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -24.1 | -24.4 | 0.178785E+09 | 236.59 | 09-FEB-11:09 | 0.87 | 0.26 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -11.0 | -11.9 | 0.210889E+09 | 266.77 | 25-MAR-15:30 | 18.35 | 10.44 |
April | 0.205626E+09 | 4393.48 | 18-APR-15:10 | 27.75 | 20.45 | 0.203490E+09 | 301.59 | 18-APR-08:50 | 22.23 | 18.41 |
May | 0.598014E+09 | 5616.91 | 31-MAY-17:00 | 28.90 | 19.82 | 0.239041E+09 | 301.59 | 27-MAY-15:00 | 20.00 | 16.12 |
June | 0.363140E+10 | 18739.90 | 20-JUN-05:03 | 13.17 | 11.99 | 0.253995E+09 | 301.63 | 12-JUN-13:39 | 23.33 | 20.86 |
July | 0.513144E+10 | 20371.39 | 19-JUL-05:02 | 12.48 | 11.50 | 0.248884E+09 | 301.61 | 29-JUL-07:10 | 19.87 | 17.84 |
August | 0.515448E+10 | 19123.16 | 30-AUG-05:03 | 13.90 | 12.57 | 0.268642E+09 | 301.62 | 12-AUG-14:50 | 22.25 | 17.58 |
September | 0.260482E+10 | 19419.99 | 08-SEP-05:02 | 14.32 | 13.31 | 0.235555E+09 | 301.61 | 08-SEP-07:30 | 18.90 | 16.49 |
October | 24842049.25 | 524.45 | 07-OCT-16:00 | 6.80 | 3.53 | 0.200913E+09 | 303.10 | 20-OCT-14:39 | 23.07 | 13.23 |
November | 1054644.26 | 289.74 | 04-NOV-17:00 | 7.80 | 3.62 | 0.189107E+09 | 284.75 | 04-NOV-15:50 | 13.07 | 6.30 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -0.7 | -1.2 | 0.194860E+09 | 236.59 | 02-DEC-11:09 | 4.08 | 2.07 |
Annual Sum or Average | 0.173517E+11 | 0.261867E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.178785E+09 | 236.59 | -5.7 | -6.5 | ||
Maximum of Months | 0.515448E+10 | 20371.39 | 28.90 | 20.45 | 0.268642E+09 | 303.10 | 23.33 | 20.86 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 842185.27 | 839.24 | 12-JAN-13:00 | 2.20 | 0.51 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 65616180.30 | 2606.24 | 25-FEB-14:40 | 5.40 | 2.61 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.195257E+09 | 2601.02 | 27-MAR-14:00 | 6.10 | 2.66 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.700993E+09 | 5037.06 | 22-APR-13:40 | 2.03 | -0.2 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.560385E+09 | 8219.47 | 31-MAY-15:10 | 29.72 | 19.53 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.505521E+10 | 42920.75 | 30-JUN-19:34 | 24.23 | 18.62 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.717789E+10 | 50421.73 | 18-JUL-18:41 | 22.88 | 16.12 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.525450E+10 | 44878.26 | 05-AUG-17:11 | 25.03 | 17.78 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.269092E+10 | 49261.68 | 09-SEP-17:21 | 25.80 | 16.12 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.808150E+09 | 5550.69 | 21-OCT-06:10 | 10.28 | 8.14 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.166028E+09 | 4259.27 | 08-NOV-07:10 | 12.30 | 11.30 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 7268290.82 | 1631.01 | 02-DEC-15:30 | 5.85 | 3.24 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.226831E+11 | 0.00 | ||||||||
Minimum of Months | 842185.27 | 839.24 | 2.03 | -0.2 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.717789E+10 | 50421.73 | 29.72 | 19.53 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -2.8 | -3.2 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -24.1 | -24.4 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -11.0 | -11.9 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 | 5.14 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 | 1.38 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -0.7 | -1.2 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.00 | 0.00 | 18.93 | 17.82 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150439E+11 | 31243.81 | 27-JAN-06:31 | -17.9 |
February | 0.109060E+11 | 31269.19 | 01-FEB-06:31 | -31.5 |
March | 0.838655E+10 | 31117.95 | 06-MAR-06:31 | -13.3 |
April | 0.409261E+10 | 29856.44 | 25-APR-05:31 | 1.10 |
May | 0.962960E+09 | 28569.79 | 02-MAY-05:12 | 2.20 |
June | 0.163319E+09 | 28045.91 | 05-JUN-05:01 | 9.32 |
July | 22867003.59 | 1575.70 | 19-JUL-06:03 | 14.37 |
August | 59169989.74 | 2420.01 | 23-AUG-06:05 | 17.88 |
September | 0.542457E+09 | 28437.54 | 29-SEP-05:01 | 0.92 |
October | 0.275869E+10 | 28535.48 | 17-OCT-05:12 | 0.83 |
November | 0.680011E+10 | 30665.20 | 27-NOV-06:31 | -9.4 |
December | 0.116237E+11 | 31147.74 | 11-DEC-06:31 | -21.9 |
Annual Sum or Average | 0.613624E+11 | |||
Minimum of Months | 22867003.59 | 1575.70 | -31.5 | |
Maximum of Months | 0.150439E+11 | 31269.19 | 17.88 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.906366E+11 | 95844.17 | 19-JAN-06:41 | -27.8 |
February | 0.647532E+11 | 95309.59 | 28-FEB-06:01 | -16.7 |
March | 0.425384E+11 | 94748.25 | 06-MAR-06:01 | -14.1 |
April | 0.171679E+11 | 90450.58 | 02-APR-10:22 | -1.1 |
May | 0.182463E+10 | 87997.35 | 02-MAY-04:33 | 2.40 |
June | 0.278909E+09 | 2892.77 | 14-JUN-07:00 | 17.80 |
July | 0.190276E+09 | 2576.10 | 20-JUL-07:00 | 20.00 |
August | 0.218313E+09 | 2580.59 | 25-AUG-07:00 | 13.90 |
September | 0.135374E+10 | 87555.16 | 30-SEP-05:23 | 0.30 |
October | 0.111090E+11 | 89227.57 | 24-OCT-03:42 | 1.87 |
November | 0.433421E+11 | 93779.33 | 21-NOV-06:01 | -9.5 |
December | 0.725410E+11 | 96374.91 | 09-DEC-06:41 | -22.8 |
Annual Sum or Average | 0.345954E+12 | |||
Minimum of Months | 0.190276E+09 | 2576.10 | -27.8 | |
Maximum of Months | 0.906366E+11 | 96374.91 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.290914E+12 | 268509.05 | 18-JAN-13:20 | -16.3 |
February | 0.195699E+12 | 265215.80 | 01-FEB-20:53 | -28.9 |
March | 0.106303E+12 | 210181.44 | 06-MAR-08:70 | -11.8 |
April | 0.227492E+11 | 116384.17 | 02-APR-23:57 | -5.6 |
May | 0.486740E+09 | 21861.48 | 02-MAY-03:00 | 2.80 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.264621E+10 | 31400.74 | 24-OCT-06:00 | 2.20 |
November | 0.113154E+12 | 207497.98 | 25-NOV-11:00 | -17.2 |
December | 0.221310E+12 | 269955.64 | 09-DEC-08:13 | -22.8 |
Annual Sum or Average | 0.953261E+12 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.290914E+12 | 269955.64 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.256100E+10 | 1939.55 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.233575E+10 | 1939.55 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.266872E+10 | 1939.55 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.252182E+10 | 1939.55 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.261486E+10 | 1939.55 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.257569E+10 | 1939.55 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.256100E+10 | 1939.55 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.266872E+10 | 1939.55 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.252182E+10 | 1939.55 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.256100E+10 | 1939.55 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.246796E+10 | 1939.55 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.256100E+10 | 1939.55 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.306193E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.233575E+10 | 1939.55 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.266872E+10 | 1939.55 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112294E+11 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102778E+11 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.118738E+11 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.111270E+11 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.115516E+11 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.114492E+11 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112294E+11 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.118738E+11 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.111270E+11 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112294E+11 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108048E+11 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112294E+11 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135003E+12 | ||||
Minimum of Months | 0.102778E+11 | 10075.60 | 0.00 | 0.00 | |
Maximum of Months | 0.118738E+11 | 10075.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.258277E+11 | 23173.88 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.236390E+11 | 23173.88 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.273097E+11 | 23173.88 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.255921E+11 | 23173.88 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.265687E+11 | 23173.88 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.263332E+11 | 23173.88 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.258277E+11 | 23173.88 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.273097E+11 | 23173.88 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.255921E+11 | 23173.88 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.258277E+11 | 23173.88 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.248511E+11 | 23173.88 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.258277E+11 | 23173.88 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.236390E+11 | 23173.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.273097E+11 | 23173.88 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837172E+10 |
February | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622373E+10 |
March | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 204922.49 | 0.517145E+10 |
April | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32577250.05 | 0.302500E+10 |
May | 0.565842E+09 | 0.261486E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39747746.01 | 0.162380E+10 |
June | 0.565842E+09 | 0.257569E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162628E+09 | 0.101141E+10 |
July | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128662E+09 | 0.656797E+09 |
August | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188027E+09 | 0.909852E+09 |
September | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109382E+09 | 0.157046E+10 |
October | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272652E+10 |
November | 0.522316E+09 | 0.246796E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471386E+10 |
December | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675566E+10 |
Annual Sum or Average | 0.659424E+10 | 0.306193E+11 | 0.319458E+11 | 0.661228E+09 | 0.427603E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656797E+09 |
Maximum of Months | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188027E+09 | 0.837172E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622121E+11 |
February | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461017E+11 |
March | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14453494.33 | 0.360382E+11 |
April | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324530E+09 | 0.192251E+11 |
May | 0.00 | 0.115516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104028E+09 | 0.938635E+10 |
June | 0.00 | 0.114492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693715E+09 | 0.750956E+10 |
July | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174396E+09 | 0.653674E+10 |
August | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266018E+09 | 0.864681E+10 |
September | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193881E+09 | 0.105625E+11 |
October | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7958739.22 | 0.161410E+11 |
November | 0.00 | 0.108048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361577E+11 |
December | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516537E+11 |
Annual Sum or Average | 0.135003E+12 | 0.177898E+10 | 0.310172E+12 | ||||||
Minimum of Months | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653674E+10 |
Maximum of Months | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693715E+09 | 0.622121E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179374E+12 |
February | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125028E+12 |
March | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134428E+10 | 0.846233E+11 |
April | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547749E+10 | 0.409073E+11 |
May | 0.00 | 0.265687E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307218E+10 | 0.200619E+11 |
June | 0.00 | 0.263332E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182811E+10 | 0.230395E+11 |
July | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47651322.06 | 0.264551E+11 |
August | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105803E+09 | 0.315606E+11 |
September | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487923E+09 | 0.351875E+11 |
October | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133974E+10 | 0.310432E+11 |
November | 0.00 | 0.248511E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154069E+09 | 0.877253E+11 |
December | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140317E+12 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | 0.138573E+11 | 0.825323E+12 | |||||
Minimum of Months | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200619E+11 |
Maximum of Months | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547749E+10 | 0.179374E+12 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1939.55 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 23196.45 | 19-JAN-07:02 |
February | 659.25 | 01-FEB-08:09 | 1939.55 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 25335.63 | 02-FEB-07:25 |
March | 659.25 | 01-MAR-08:09 | 1939.55 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.14 | 19-MAR-14:00 | 17158.88 | 06-MAR-08:00 |
April | 659.25 | 01-APR-07:10 | 1939.55 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1466.00 | 18-APR-12:00 | 12899.03 | 03-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1939.55 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1888.51 | 31-MAY-17:00 | 8162.31 | 02-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1939.55 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2884.01 | 26-JUN-16:10 | 5798.29 | 02-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 1939.55 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2273.23 | 25-JUL-16:10 | 4384.91 | 24-JUL-06:01 |
August | 659.25 | 01-AUG-07:10 | 1939.55 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3424.30 | 04-AUG-16:10 | 5658.55 | 07-AUG-06:03 |
September | 659.25 | 01-SEP-07:10 | 1939.55 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2743.07 | 06-SEP-16:10 | 8579.77 | 29-SEP-06:10 |
October | 659.25 | 02-OCT-07:10 | 1939.55 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 9845.00 | 23-OCT-06:10 |
November | 659.25 | 01-NOV-07:10 | 1939.55 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 16363.63 | 28-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1939.55 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 21704.65 | 08-DEC-17:05 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4384.91 | |||||
Maximum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 3424.30 | 25335.63 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 94529.73 | 18-JAN-16:02 |
February | 0.00 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 65563.27 | 04-FEB-17:55 |
March | 0.00 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1426.44 | 19-MAR-16:00 | 67037.92 | 06-MAR-08:00 |
April | 0.00 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8639.97 | 15-APR-15:10 | 41877.66 | 25-APR-06:10 |
May | 0.00 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2895.29 | 31-MAY-15:10 | 17819.45 | 01-MAY-23:55 |
June | 0.00 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8940.83 | 11-JUN-15:00 | 15303.47 | 02-JUN-08:00 |
July | 0.00 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4874.53 | 25-JUL-16:00 | 10773.57 | 10-JUL-15:10 |
August | 0.00 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6091.40 | 04-AUG-16:15 | 13092.03 | 30-AUG-15:05 |
September | 0.00 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5329.06 | 06-SEP-15:40 | 14855.45 | 18-SEP-16:00 |
October | 0.00 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1132.89 | 20-OCT-15:10 | 28672.86 | 24-OCT-06:10 |
November | 0.00 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 60878.98 | 25-NOV-16:10 |
December | 0.00 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 93900.18 | 09-DEC-08:55 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10773.57 | |||
Maximum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8940.83 | 94529.73 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23173.88 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 235985.02 | 18-JAN-13:10 |
February | 0.00 | 23173.88 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 173498.59 | 28-FEB-10:00 |
March | 0.00 | 23173.88 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25458.94 | 25-MAR-15:00 | 158164.68 | 06-MAR-08:70 |
April | 0.00 | 23173.88 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56747.51 | 15-APR-15:00 | 75165.04 | 02-APR-23:57 |
May | 0.00 | 23173.88 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37940.19 | 04-MAY-14:00 | 46622.53 | 13-MAY-12:55 |
June | 0.00 | 23173.88 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27942.19 | 11-JUN-15:00 | 45378.28 | 02-JUN-08:00 |
July | 0.00 | 23173.88 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3720.17 | 25-JUL-16:00 | 45221.37 | 10-JUL-14:00 |
August | 0.00 | 23173.88 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4540.05 | 21-AUG-13:00 | 40706.49 | 30-AUG-14:55 |
September | 0.00 | 23173.88 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13170.25 | 06-SEP-14:00 | 46667.63 | 18-SEP-16:00 |
October | 0.00 | 23173.88 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23880.63 | 20-OCT-15:00 | 43698.71 | 24-OCT-07:10 |
November | 0.00 | 23173.88 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11948.76 | 20-NOV-10:00 | 170475.14 | 25-NOV-11:00 |
December | 0.00 | 23173.88 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 272816.94 | 09-DEC-08:55 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40706.49 | ||||
Maximum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 56747.51 | 272816.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 2720.41 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 882.63 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 2267.01 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1764.72 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 2267.01 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1985.01 |
April | 4393.48 | 18-APR-15:10 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 641.08 | 0.00 |
May | 5616.91 | 31-MAY-17:00 | 210.96 | 1536.53 | 956.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1888.51 | 0.00 |
June | 18739.90 | 20-JUN-05:03 | 217.55 | 1738.04 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 752.47 |
July | 20371.39 | 19-JUL-05:02 | 362.59 | 2896.74 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 890.60 |
August | 19123.16 | 30-AUG-05:03 | 290.07 | 2317.39 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 714.45 |
September | 19419.99 | 08-SEP-05:02 | 435.11 | 3476.08 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 722.35 |
October | 524.45 | 07-OCT-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.88 |
November | 289.74 | 04-NOV-17:00 | 421.92 | 3073.06 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.11 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 2267.01 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 946.87 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 1536.53 | 956.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20371.39 | 659.25 | 3476.08 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1888.51 | 1985.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 839.24 | 12-JAN-13:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3533.46 |
February | 2606.24 | 25-FEB-14:40 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4258.15 |
March | 2601.02 | 27-MAR-14:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4522.87 |
April | 5037.06 | 22-APR-13:40 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1643.78 |
May | 8219.47 | 31-MAY-15:10 | 0.00 | 8890.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2895.29 | 0.00 |
June | 42920.75 | 30-JUN-19:34 | 0.00 | 8297.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 880.05 |
July | 50421.73 | 18-JUL-18:41 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.55 |
August | 44878.26 | 05-AUG-17:11 | 0.00 | 9482.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2185.22 |
September | 49261.68 | 09-SEP-17:21 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 545.26 |
October | 5550.69 | 21-OCT-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4120.21 |
November | 4259.27 | 08-NOV-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2344.98 |
December | 1631.01 | 02-DEC-15:30 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3083.72 |
Annual Sum or Average | |||||||||||
Minimum of Months | 839.24 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50421.73 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2895.29 | 4522.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 16358.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31062.88 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 13631.69 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76232.85 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 13631.69 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78901.01 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14328.46 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7965.71 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11100.18 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10782.18 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12429.47 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15116.33 |
October | 0.00 | 01-OCT-00:05 | 0.00 | 5452.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14530.71 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9879.33 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 13631.69 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31919.05 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7965.71 | |
Maximum of Months | 0.00 | 0.00 | 16358.03 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78901.01 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.715088E+11 | 53729.89 | 20-JAN-16:00 | 0.519595E+12 | 477107.05 | 18-JAN-17:10 |
February | 0.641789E+11 | 52178.30 | 18-FEB-13:50 | 0.357012E+12 | 450483.09 | 01-FEB-21:10 |
March | 0.716261E+11 | 52172.46 | 01-MAR-15:50 | 0.208987E+12 | 392495.39 | 06-MAR-08:09 |
April | 0.651041E+11 | 55021.44 | 18-APR-14:00 | 0.599358E+11 | 224859.48 | 02-APR-23:00 |
May | 0.658797E+11 | 57822.83 | 31-MAY-14:00 | 0.346342E+10 | 74747.72 | 02-MAY-05:19 |
June | 0.679803E+11 | 65936.72 | 27-JUN-14:39 | 0.125252E+09 | 8402.83 | 05-JUN-05:10 |
July | 0.685293E+11 | 66832.47 | 03-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.719985E+11 | 70478.61 | 04-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.661919E+11 | 60682.82 | 08-SEP-13:00 | 0.230334E+10 | 41510.14 | 30-SEP-05:10 |
October | 0.668130E+11 | 51380.22 | 24-OCT-08:09 | 0.230406E+11 | 101378.41 | 24-OCT-05:10 |
November | 0.669937E+11 | 53720.36 | 30-NOV-16:40 | 0.214925E+12 | 370936.71 | 25-NOV-16:10 |
December | 0.712925E+11 | 53726.47 | 29-DEC-16:40 | 0.401667E+12 | 477107.05 | 08-DEC-17:10 |
Annual Sum or Average | 0.818097E+12 | 0.179105E+13 | ||||
Minimum of Months | 0.641789E+11 | 51380.22 | 0.00 | 0.00 | ||
Maximum of Months | 0.719985E+11 | 70478.61 | 0.519595E+12 | 477107.05 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.396181E+11 | 0.104662E+11 | 0.115358E+11 | 0.00 | 0.753029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235848E+10 | 0.00 |
February | 0.362526E+11 | 0.872054E+10 | 0.105871E+11 | 0.00 | 0.645436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216434E+10 | 0.00 |
March | 0.418523E+11 | 0.864102E+10 | 0.123357E+11 | 0.00 | 0.635666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244044E+10 | 0.00 |
April | 0.392410E+11 | 0.732328E+10 | 0.114862E+11 | 0.00 | 0.467681E+10 | 0.00 | 0.00 | 96486450.66 | 0.00 | 0.00 | 0.00 | 0.228031E+10 | 0.00 |
May | 0.407352E+11 | 0.666063E+10 | 0.119357E+11 | 0.00 | 0.395285E+10 | 0.00 | 0.00 | 0.295895E+09 | 0.00 | 0.00 | 0.00 | 0.229935E+10 | 0.00 |
June | 0.403581E+11 | 0.599040E+10 | 0.118862E+11 | 0.00 | 0.414552E+10 | 0.00 | 0.00 | 0.341563E+10 | 0.00 | 0.00 | 0.00 | 0.218448E+10 | 0.00 |
July | 0.396181E+11 | 0.638421E+10 | 0.115358E+11 | 0.00 | 0.393219E+10 | 0.00 | 0.00 | 0.490881E+10 | 0.00 | 0.00 | 0.00 | 0.215015E+10 | 0.00 |
August | 0.418523E+11 | 0.716803E+10 | 0.123357E+11 | 0.00 | 0.420308E+10 | 0.00 | 0.00 | 0.425272E+10 | 0.00 | 0.00 | 0.00 | 0.218672E+10 | 0.00 |
September | 0.392410E+11 | 0.789885E+10 | 0.114862E+11 | 0.00 | 0.378230E+10 | 0.00 | 0.00 | 0.168520E+10 | 0.00 | 0.00 | 0.00 | 0.209835E+10 | 0.00 |
October | 0.396181E+11 | 0.923552E+10 | 0.115358E+11 | 0.00 | 0.422973E+10 | 0.00 | 0.00 | 722103.57 | 0.00 | 0.00 | 0.00 | 0.219317E+10 | 0.00 |
November | 0.381239E+11 | 0.986409E+10 | 0.110862E+11 | 0.00 | 0.574679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217266E+10 | 0.00 |
December | 0.396181E+11 | 0.107199E+11 | 0.115358E+11 | 0.00 | 0.710785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231084E+10 | 0.00 |
Annual Sum or Average | 0.476129E+12 | 0.990726E+11 | 0.139282E+12 | 0.621184E+11 | 0.00 | 0.146555E+11 | 0.268393E+11 | ||||||
Minimum of Months | 0.362526E+11 | 0.599040E+10 | 0.105871E+11 | 0.00 | 0.378230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209835E+10 | 0.00 |
Maximum of Months | 0.418523E+11 | 0.107199E+11 | 0.123357E+11 | 0.00 | 0.753029E+10 | 0.00 | 0.00 | 0.490881E+10 | 0.00 | 0.00 | 0.00 | 0.244044E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.519595E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.357012E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.208987E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.599358E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.346342E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.125252E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.230334E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.230406E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.214925E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.401667E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179105E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.519595E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35189.04 | 02-JAN-09:09 | 6311.00 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4398.21 | 02-JAN-09:39 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35189.04 | 01-FEB-09:09 | 6311.00 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 4398.21 | 04-FEB-08:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35189.04 | 01-MAR-09:09 | 6311.00 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4398.21 | 01-MAR-13:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35189.04 | 01-APR-08:09 | 6311.00 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 4398.21 | 03-APR-14:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35189.04 | 01-MAY-08:09 | 6311.00 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 4398.21 | 02-MAY-06:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35189.04 | 01-JUN-08:09 | 6311.00 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 6079.74 | 26-JUN-13:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35189.04 | 01-JUL-08:09 | 6311.00 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6079.74 | 29-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35189.04 | 01-AUG-08:09 | 6311.00 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6079.74 | 02-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35189.04 | 01-SEP-08:09 | 6311.00 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 3774.44 | 01-SEP-11:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35189.04 | 02-OCT-08:09 | 6311.00 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 4398.21 | 24-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35189.04 | 01-NOV-08:09 | 6311.00 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 4398.21 | 13-NOV-16:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35189.04 | 01-DEC-09:09 | 6311.00 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4398.21 | 01-DEC-13:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35189.04 | 6311.00 | 10112.62 | 0.00 | 3774.44 | 0.00 | 0.00 | |||||
Maximum of Months | 35189.04 | 6311.00 | 10112.62 | 0.00 | 6079.74 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2915.95 | 30-JAN-12:20 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2940.29 | 17-FEB-12:50 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2934.41 | 01-MAR-12:20 | 0.00 |
April | 4098.64 | 18-APR-15:09 | 0.00 | 0.00 | 0.00 | 2837.46 | 01-APR-11:00 | 0.00 |
May | 7331.81 | 31-MAY-15:09 | 0.00 | 0.00 | 0.00 | 2639.76 | 01-MAY-11:39 | 0.00 |
June | 13675.95 | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 | 2350.95 | 01-JUN-11:39 | 0.00 |
July | 14426.56 | 26-JUL-15:00 | 0.00 | 0.00 | 0.00 | 2029.14 | 05-JUL-11:00 | 0.00 |
August | 18916.59 | 04-AUG-15:50 | 0.00 | 0.00 | 0.00 | 1851.07 | 03-AUG-11:00 | 0.00 |
September | 10635.19 | 06-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1983.82 | 30-SEP-11:30 | 0.00 |
October | 292.33 | 20-OCT-14:00 | 0.00 | 0.00 | 0.00 | 2258.03 | 31-OCT-11:00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2544.59 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2768.74 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1851.07 | 0.00 | ||
Maximum of Months | 18916.59 | 0.00 | 0.00 | 0.00 | 2940.29 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 53729.89 | 20-JAN-16:00 | 31277.33 | 10112.62 | 6311.00 | 0.00 | 4398.21 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52178.30 | 18-FEB-13:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4398.21 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 52172.46 | 01-MAR-15:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4398.21 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 55021.44 | 18-APR-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3774.44 | 0.00 | 0.00 | 4038.44 | 0.00 |
May | 57822.83 | 31-MAY-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3774.44 | 0.00 | 0.00 | 6938.83 | 0.00 |
June | 65936.72 | 27-JUN-14:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6079.74 | 0.00 | 0.00 | 12767.78 | 0.00 |
July | 66832.47 | 03-JUL-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6079.74 | 0.00 | 0.00 | 13667.50 | 0.00 |
August | 70478.61 | 04-AUG-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6079.74 | 0.00 | 0.00 | 17327.48 | 0.00 |
September | 60682.82 | 08-SEP-13:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3774.44 | 0.00 | 0.00 | 9873.63 | 0.00 |
October | 51380.22 | 24-OCT-08:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4398.21 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 53720.36 | 30-NOV-16:40 | 31277.33 | 10112.62 | 6311.00 | 0.00 | 4398.21 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 53726.47 | 29-DEC-16:40 | 31277.33 | 10112.62 | 6311.00 | 0.00 | 4398.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 51380.22 | 31277.33 | 10112.62 | 0.00 | 0.00 | 3774.44 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 70478.61 | 35189.04 | 10112.62 | 6311.00 | 0.00 | 6079.74 | 0.00 | 0.00 | 17327.48 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 477107.05 | 18-JAN-17:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 450483.09 | 01-FEB-21:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 392495.39 | 06-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 224859.48 | 02-APR-23:00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 74747.72 | 02-MAY-05:19 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 8402.83 | 05-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 41510.14 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 101378.41 | 24-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 370936.71 | 25-NOV-16:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 477107.05 | 08-DEC-17:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 477107.05 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 69.67 | 15.95 | 19.17 | 19.15 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 44.00 | 16.52 | 18.17 | 19.11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22.17 | 16.94 | 10.50 | 19.20 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10.17 | 18.37 | 7.50 | 19.59 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2.50 | 20.17 | 2.50 | 20.17 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.33 | 20.51 | 0.33 | 20.51 | 0.33 | 24.48 | 0.33 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.50 | 0.83 | 24.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.57 | 0.50 | 24.57 |
September | 1.33 | 20.20 | 1.33 | 20.20 | 0.17 | 24.64 | 0.17 | 24.64 |
October | 6.83 | 20.03 | 6.83 | 20.03 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23.17 | 16.39 | 7.33 | 19.59 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 32.50 | 16.28 | 12.00 | 19.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 212.67 | 16.60 | 85.67 | 19.34 | 1.83 | 24.53 | 1.83 | 24.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 69.67 | 20.51 | 19.17 | 20.51 | 0.83 | 24.64 | 0.83 | 24.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 167.50 | 12.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 126.00 | 13.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 97.00 | 13.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 54.83 | 14.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5.00 | 14.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.43 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.37 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.29 | 0.00 | 0.00 |
September | 4.50 | 14.75 | 0.00 | 0.00 | 0.17 | 27.27 | 0.00 | 0.00 |
October | 52.50 | 14.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 91.00 | 13.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 150.17 | 13.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 748.50 | 13.51 | 0.00 | 10.33 | 27.39 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.50 | 14.75 | 0.00 | 0.00 | 5.17 | 27.43 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.33 | 8.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22.50 | 7.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.83 | 8.25 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.50 | 8.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.97 | 300.00 | 20.97 | 300.00 | 20.97 |
February | 276.00 | 20.96 | 276.00 | 20.96 | 276.00 | 20.96 |
March | 324.00 | 21.05 | 322.50 | 21.04 | 322.50 | 21.04 |
April | 294.67 | 21.41 | 235.17 | 21.08 | 235.17 | 21.08 |
May | 296.50 | 22.64 | 71.17 | 21.46 | 66.83 | 21.30 |
June | 144.67 | 23.22 | 165.83 | 23.80 | 48.33 | 23.56 |
July | 60.00 | 23.84 | 278.83 | 23.89 | 53.00 | 23.88 |
August | 88.83 | 23.82 | 278.33 | 23.89 | 73.00 | 23.89 |
September | 161.17 | 22.42 | 156.83 | 22.87 | 59.33 | 21.19 |
October | 300.00 | 21.35 | 251.83 | 21.10 | 251.83 | 21.10 |
November | 288.00 | 21.15 | 263.00 | 21.07 | 263.00 | 21.07 |
December | 300.00 | 21.01 | 300.00 | 21.01 | 300.00 | 21.01 |
Annual Sum or Average | 2833.83 | 21.61 | 2899.50 | 21.85 | 2249.00 | 21.26 |
Minimum of Months | 60.00 | 20.96 | 71.17 | 20.96 | 48.33 | 20.96 |
Maximum of Months | 324.00 | 23.84 | 322.50 | 23.89 | 322.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.301898E+09 | 83998227.92 | 22.50 | 0.218948E+09 | 82949960.57 | 0.00 | 0.44 | 18-APR-15:10 | 0.00 | 01-APR-00:10 | 8228.71 | 18-APR-12:00 | 6106.85 | 18-APR-15:10 | 2627.33 | 18-APR-12:00 | 2246.48 | 18-APR-12:00 | 0.00 | 01-APR-00:10 |
May | 0.641920E+09 | 0.176596E+09 | 64.83 | 0.489151E+09 | 0.152769E+09 | 0.00 | 0.51 | 31-MAY-17:00 | 0.00 | 01-MAY-00:05 | 9097.16 | 31-MAY-17:00 | 7452.34 | 31-MAY-17:00 | 2399.33 | 30-MAY-10:50 | 2542.95 | 31-MAY-17:00 | 0.00 | 01-MAY-00:05 |
June | 0.481827E+10 | 0.127918E+10 | 201.40 | 0.350960E+10 | 0.130867E+10 | 0.00 | 1.00 | 12-JUN-05:01 | 0.00 | 01-JUN-00:10 | 22851.98 | 26-JUN-05:01 | 12985.23 | 24-JUN-05:03 | 12113.64 | 26-JUN-05:06 | 5232.50 | 26-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.733063E+10 | 0.190582E+10 | 250.48 | 0.507887E+10 | 0.225176E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 22519.64 | 27-JUL-05:01 | 14164.14 | 14-JUL-05:03 | 12611.89 | 27-JUL-05:01 | 5180.10 | 27-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.733779E+10 | 0.192607E+10 | 260.87 | 0.508040E+10 | 0.225739E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 24644.13 | 04-AUG-05:01 | 12414.94 | 04-AUG-16:10 | 15302.21 | 04-AUG-05:06 | 5481.34 | 04-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.269041E+10 | 0.736093E+09 | 147.43 | 0.230397E+10 | 0.386435E+09 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 20953.43 | 11-SEP-05:01 | 13952.99 | 18-SEP-05:03 | 9764.04 | 12-SEP-05:03 | 4906.43 | 11-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 2608803.16 | 722103.57 | 1.50 | 2608800.00 | 3.16 | 0.00 | 0.07 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 | 1058.84 | 20-OCT-15:00 | 1058.84 | 20-OCT-15:00 | 0.01 | 21-OCT-15:50 | 292.33 | 20-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.231235E+11 | 0.610848E+10 | 949.01 | 0.166836E+11 | 0.643998E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.733779E+10 | 0.192607E+10 | 260.87 | 0.508040E+10 | 0.225739E+10 | 0.00 | 1.00 | 0.00 | 24644.13 | 14164.14 | 15302.21 | 5481.34 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 41442606.22 | 12488222.74 | 3.00 | 25790239.04 | 15652367.17 | 0.00 | 0.11 | 18-APR-15:10 | 0.00 | 01-APR-00:10 | 6231.43 | 18-APR-15:10 | 3951.94 | 18-APR-15:10 | 2279.48 | 18-APR-15:10 | 1868.17 | 18-APR-15:10 | 0.00 | 01-APR-00:10 |
May | 0.389709E+09 | 0.119299E+09 | 12.00 | 0.288527E+09 | 0.101182E+09 | 0.00 | 0.29 | 31-MAY-15:10 | 0.00 | 01-MAY-00:05 | 15832.88 | 31-MAY-15:10 | 12465.83 | 31-MAY-15:10 | 3367.06 | 31-MAY-15:10 | 4889.99 | 31-MAY-15:10 | 0.00 | 01-MAY-00:05 |
June | 0.724167E+10 | 0.213646E+10 | 135.46 | 0.494882E+10 | 0.229285E+10 | 0.00 | 1.00 | 11-JUN-14:43 | 0.00 | 01-JUN-00:10 | 69004.60 | 26-JUN-20:14 | 45513.16 | 26-JUN-17:08 | 30375.20 | 26-JUN-20:14 | 18245.76 | 11-JUN-14:43 | 0.00 | 01-JUN-00:10 |
July | 0.106472E+11 | 0.300299E+10 | 187.38 | 0.671908E+10 | 0.392808E+10 | 0.00 | 1.00 | 01-JUL-17:10 | 0.00 | 01-JUL-00:10 | 72136.81 | 03-JUL-20:02 | 48349.89 | 18-JUL-17:15 | 37408.38 | 03-JUL-20:02 | 17824.05 | 26-JUL-17:10 | 0.00 | 01-JUL-00:10 |
August | 0.810289E+10 | 0.232665E+10 | 158.50 | 0.518844E+10 | 0.291445E+10 | 0.00 | 1.00 | 01-AUG-18:31 | 0.00 | 01-AUG-00:10 | 74280.72 | 03-AUG-19:22 | 48135.43 | 10-AUG-17:15 | 42274.16 | 03-AUG-19:22 | 18047.20 | 03-AUG-19:10 | 0.00 | 01-AUG-00:10 |
September | 0.312559E+10 | 0.949104E+09 | 74.59 | 0.253669E+10 | 0.588901E+09 | 0.00 | 1.00 | 09-SEP-17:20 | 0.00 | 01-SEP-00:10 | 65114.21 | 11-SEP-17:17 | 51350.34 | 09-SEP-17:20 | 21408.63 | 11-SEP-17:23 | 16656.94 | 11-SEP-17:17 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.295485E+11 | 0.854699E+10 | 570.94 | 0.197073E+11 | 0.984112E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.106472E+11 | 0.300299E+10 | 187.38 | 0.671908E+10 | 0.392808E+10 | 0.00 | 1.00 | 0.00 | 74280.72 | 51350.34 | 42274.16 | 18245.76 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.65 | 28.66 | 41.99 | 19.14 | 311.87 | 0.00 | 0.00 | 744.00 |
February | 102.76 | 50.41 | 52.36 | 49.20 | 243.13 | 0.00 | 0.00 | 672.00 |
March | 123.39 | 45.97 | 77.42 | 74.79 | 147.02 | 0.00 | 0.00 | 744.00 |
April | 179.89 | 88.90 | 90.99 | 164.12 | 98.51 | 0.00 | 0.00 | 720.00 |
May | 180.34 | 72.04 | 108.30 | 181.15 | 57.11 | 0.00 | 0.00 | 744.00 |
June | 211.27 | 91.37 | 119.90 | 230.24 | 52.24 | 0.00 | 0.00 | 720.00 |
July | 227.33 | 108.01 | 119.31 | 252.01 | 52.24 | 0.00 | 0.00 | 744.00 |
August | 198.15 | 90.62 | 107.53 | 221.44 | 59.36 | 0.00 | 0.00 | 744.00 |
September | 160.81 | 76.25 | 84.57 | 163.02 | 85.96 | 0.00 | 0.00 | 720.00 |
October | 112.55 | 50.17 | 62.38 | 89.08 | 106.17 | 0.00 | 0.00 | 744.00 |
November | 67.33 | 25.01 | 42.32 | 30.58 | 180.33 | 0.00 | 0.00 | 720.00 |
December | 52.00 | 24.74 | 27.27 | 17.92 | 272.89 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 140.69 | 62.69 | 78.00 | 124.76 | 138.43 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.00 | 24.74 | 27.27 | 17.92 | 52.24 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 227.33 | 108.01 | 119.90 | 252.01 | 311.87 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.65 | 28.66 | 41.99 | 19.14 | 311.87 | 0.00 | 0.00 | 744.00 |
February | 102.76 | 50.41 | 52.36 | 49.20 | 243.13 | 0.00 | 0.00 | 672.00 |
March | 123.39 | 45.97 | 77.42 | 74.79 | 147.02 | 0.00 | 0.00 | 744.00 |
April | 179.89 | 88.90 | 90.99 | 164.12 | 98.51 | 0.00 | 0.00 | 720.00 |
May | 180.34 | 72.04 | 108.30 | 181.15 | 57.11 | 0.00 | 0.00 | 744.00 |
June | 211.27 | 91.37 | 119.90 | 230.24 | 52.24 | 0.00 | 0.00 | 720.00 |
July | 227.33 | 108.01 | 119.31 | 252.01 | 52.24 | 0.00 | 0.00 | 744.00 |
August | 198.15 | 90.62 | 107.53 | 221.44 | 59.36 | 0.00 | 0.00 | 744.00 |
September | 160.81 | 76.25 | 84.57 | 163.02 | 85.96 | 0.00 | 0.00 | 720.00 |
October | 112.55 | 50.17 | 62.38 | 89.08 | 106.17 | 0.00 | 0.00 | 744.00 |
November | 67.33 | 25.01 | 42.32 | 30.58 | 180.33 | 0.00 | 0.00 | 720.00 |
December | 52.00 | 24.74 | 27.27 | 17.92 | 272.89 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 140.69 | 62.69 | 78.00 | 124.76 | 138.43 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.00 | 24.74 | 27.27 | 17.92 | 52.24 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 227.33 | 108.01 | 119.90 | 252.01 | 311.87 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.33 | 0.00 | 19.33 | 0.00 | 197.86 | 0.00 | 0.00 | 744.00 |
February | 24.51 | 0.00 | 24.51 | 0.32 | 156.63 | 0.00 | 0.00 | 672.00 |
March | 36.74 | 0.00 | 36.74 | 7.35 | 93.27 | 0.00 | 0.00 | 744.00 |
April | 42.51 | 0.29 | 42.22 | 19.16 | 60.21 | 0.00 | 0.00 | 720.00 |
May | 55.39 | 2.14 | 53.25 | 39.96 | 32.61 | 0.00 | 0.00 | 744.00 |
June | 64.59 | 5.83 | 58.76 | 53.92 | 28.62 | 0.00 | 0.00 | 720.00 |
July | 60.59 | 4.06 | 56.53 | 50.59 | 28.96 | 0.00 | 0.00 | 744.00 |
August | 50.93 | 1.06 | 49.87 | 45.65 | 34.19 | 0.00 | 0.00 | 744.00 |
September | 38.95 | 0.03 | 38.93 | 26.85 | 51.39 | 0.00 | 0.00 | 720.00 |
October | 28.93 | 0.00 | 28.93 | 9.90 | 64.97 | 0.00 | 0.00 | 744.00 |
November | 20.24 | 0.00 | 20.24 | 2.02 | 112.05 | 0.00 | 0.00 | 720.00 |
December | 13.13 | 0.00 | 13.13 | 0.00 | 169.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.06 | 1.12 | 36.94 | 21.44 | 85.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.13 | 0.00 | 13.13 | 0.00 | 28.62 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.59 | 5.83 | 58.76 | 53.92 | 197.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.33 | 0.00 | 19.33 | 0.00 | 197.86 | 0.00 | 0.00 | 744.00 |
February | 24.51 | 0.00 | 24.51 | 0.32 | 156.63 | 0.00 | 0.00 | 672.00 |
March | 36.74 | 0.00 | 36.74 | 7.35 | 93.27 | 0.00 | 0.00 | 744.00 |
April | 42.50 | 0.29 | 42.22 | 19.16 | 60.21 | 0.00 | 0.00 | 720.00 |
May | 55.39 | 2.14 | 53.25 | 39.96 | 32.61 | 0.00 | 0.00 | 744.00 |
June | 64.58 | 5.83 | 58.76 | 53.92 | 28.62 | 0.00 | 0.00 | 720.00 |
July | 60.59 | 4.06 | 56.53 | 50.59 | 28.96 | 0.00 | 0.00 | 744.00 |
August | 50.93 | 1.06 | 49.87 | 45.65 | 34.19 | 0.00 | 0.00 | 744.00 |
September | 38.95 | 0.03 | 38.93 | 26.85 | 51.39 | 0.00 | 0.00 | 720.00 |
October | 28.93 | 0.00 | 28.93 | 9.90 | 64.97 | 0.00 | 0.00 | 744.00 |
November | 20.24 | 0.00 | 20.24 | 2.02 | 112.05 | 0.00 | 0.00 | 720.00 |
December | 13.13 | 0.00 | 13.13 | 0.00 | 169.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.06 | 1.12 | 36.94 | 21.44 | 85.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.13 | 0.00 | 13.13 | 0.00 | 28.62 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.58 | 5.83 | 58.76 | 53.92 | 197.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.92 | 9.64 | 14.28 | 3.57 | 81.76 | 0.00 | 0.00 | 744.00 |
February | 33.32 | 15.99 | 17.33 | 15.00 | 63.21 | 0.00 | 0.00 | 672.00 |
March | 54.33 | 25.92 | 28.41 | 47.91 | 35.48 | 1.33 | 0.00 | 744.00 |
April | 74.53 | 45.02 | 29.51 | 77.14 | 23.77 | 8.33 | 0.00 | 720.00 |
May | 89.98 | 51.07 | 38.92 | 101.60 | 17.86 | 5.67 | 0.00 | 744.00 |
June | 102.48 | 60.55 | 41.94 | 113.87 | 20.44 | 0.00 | 0.00 | 720.00 |
July | 103.13 | 63.96 | 39.17 | 110.79 | 25.32 | 1.33 | 0.00 | 744.00 |
August | 85.59 | 49.09 | 36.50 | 92.50 | 25.57 | 0.00 | 0.00 | 744.00 |
September | 65.90 | 38.27 | 27.63 | 64.67 | 34.08 | 0.00 | 0.00 | 720.00 |
October | 40.93 | 19.82 | 21.10 | 36.37 | 28.40 | 1.33 | 0.00 | 744.00 |
November | 24.03 | 8.30 | 15.73 | 12.61 | 44.17 | 0.33 | 0.00 | 720.00 |
December | 15.91 | 7.17 | 8.73 | 1.63 | 69.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 59.64 | 32.98 | 26.66 | 56.70 | 39.03 | 18.33 | 0.00 | 8760.00 |
Minimum of Months | 15.91 | 7.17 | 8.73 | 1.63 | 17.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.13 | 63.96 | 41.94 | 113.87 | 81.76 | 8.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.92 | 9.64 | 14.28 | 3.57 | 81.76 | 0.00 | 0.00 | 744.00 |
February | 33.32 | 15.99 | 17.33 | 15.00 | 63.21 | 0.00 | 0.00 | 672.00 |
March | 54.33 | 25.92 | 28.41 | 47.91 | 35.48 | 1.33 | 0.00 | 744.00 |
April | 74.53 | 45.02 | 29.51 | 77.14 | 23.77 | 8.33 | 0.00 | 720.00 |
May | 89.98 | 51.07 | 38.92 | 101.60 | 17.86 | 5.67 | 0.00 | 744.00 |
June | 102.48 | 60.55 | 41.94 | 113.87 | 20.44 | 0.00 | 0.00 | 720.00 |
July | 103.13 | 63.96 | 39.17 | 110.79 | 25.32 | 1.33 | 0.00 | 744.00 |
August | 85.59 | 49.09 | 36.50 | 92.50 | 25.57 | 0.00 | 0.00 | 744.00 |
September | 65.90 | 38.27 | 27.63 | 64.67 | 34.08 | 0.00 | 0.00 | 720.00 |
October | 40.93 | 19.82 | 21.10 | 36.37 | 28.40 | 1.33 | 0.00 | 744.00 |
November | 24.03 | 8.30 | 15.73 | 12.61 | 44.17 | 0.33 | 0.00 | 720.00 |
December | 15.91 | 7.17 | 8.73 | 1.63 | 69.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 59.64 | 32.98 | 26.66 | 56.70 | 39.03 | 18.33 | 0.00 | 8760.00 |
Minimum of Months | 15.91 | 7.17 | 8.73 | 1.63 | 17.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.13 | 63.96 | 41.94 | 113.87 | 81.76 | 8.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.92 | 9.64 | 14.28 | 3.57 | 81.76 | 0.00 | 0.00 | 744.00 |
February | 33.32 | 15.99 | 17.33 | 15.00 | 63.21 | 0.00 | 0.00 | 672.00 |
March | 54.33 | 25.92 | 28.41 | 47.91 | 35.48 | 1.33 | 0.00 | 744.00 |
April | 74.53 | 45.02 | 29.51 | 77.14 | 23.77 | 8.33 | 0.00 | 720.00 |
May | 89.98 | 51.07 | 38.92 | 101.60 | 17.86 | 5.67 | 0.00 | 744.00 |
June | 102.48 | 60.55 | 41.94 | 113.87 | 20.44 | 0.00 | 0.00 | 720.00 |
July | 103.13 | 63.96 | 39.17 | 110.79 | 25.32 | 1.33 | 0.00 | 744.00 |
August | 85.59 | 49.09 | 36.50 | 92.50 | 25.57 | 0.00 | 0.00 | 744.00 |
September | 65.90 | 38.27 | 27.63 | 64.67 | 34.08 | 0.00 | 0.00 | 720.00 |
October | 40.93 | 19.82 | 21.10 | 36.37 | 28.40 | 1.33 | 0.00 | 744.00 |
November | 24.03 | 8.30 | 15.73 | 12.61 | 44.17 | 0.33 | 0.00 | 720.00 |
December | 15.91 | 7.17 | 8.73 | 1.63 | 69.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 59.64 | 32.98 | 26.66 | 56.70 | 39.03 | 18.33 | 0.00 | 8760.00 |
Minimum of Months | 15.91 | 7.17 | 8.73 | 1.63 | 17.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.13 | 63.96 | 41.94 | 113.87 | 81.76 | 8.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.92 | 9.64 | 14.28 | 3.57 | 81.76 | 0.00 | 0.00 | 744.00 |
February | 33.32 | 15.99 | 17.33 | 15.00 | 63.21 | 0.00 | 0.00 | 672.00 |
March | 54.33 | 25.92 | 28.41 | 47.91 | 35.48 | 1.33 | 0.00 | 744.00 |
April | 74.53 | 45.02 | 29.51 | 77.14 | 23.77 | 8.33 | 0.00 | 720.00 |
May | 89.98 | 51.07 | 38.92 | 101.60 | 17.86 | 5.67 | 0.00 | 744.00 |
June | 102.48 | 60.55 | 41.94 | 113.87 | 20.44 | 0.00 | 0.00 | 720.00 |
July | 103.13 | 63.96 | 39.17 | 110.79 | 25.32 | 1.33 | 0.00 | 744.00 |
August | 85.59 | 49.09 | 36.50 | 92.50 | 25.57 | 0.00 | 0.00 | 744.00 |
September | 65.90 | 38.27 | 27.63 | 64.67 | 34.08 | 0.00 | 0.00 | 720.00 |
October | 40.93 | 19.82 | 21.10 | 36.37 | 28.40 | 1.33 | 0.00 | 744.00 |
November | 24.03 | 8.30 | 15.73 | 12.61 | 44.17 | 0.33 | 0.00 | 720.00 |
December | 15.91 | 7.17 | 8.73 | 1.63 | 69.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 59.64 | 32.98 | 26.66 | 56.70 | 39.03 | 18.33 | 0.00 | 8760.00 |
Minimum of Months | 15.91 | 7.17 | 8.73 | 1.63 | 17.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.13 | 63.96 | 41.94 | 113.87 | 81.76 | 8.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.92 | 9.64 | 14.28 | 3.57 | 81.76 | 0.00 | 0.00 | 744.00 |
February | 33.32 | 15.99 | 17.33 | 15.00 | 63.21 | 0.00 | 0.00 | 672.00 |
March | 54.33 | 25.92 | 28.41 | 47.91 | 35.48 | 1.33 | 0.00 | 744.00 |
April | 74.53 | 45.02 | 29.51 | 77.14 | 23.77 | 8.33 | 0.00 | 720.00 |
May | 89.98 | 51.07 | 38.92 | 101.60 | 17.86 | 5.67 | 0.00 | 744.00 |
June | 102.48 | 60.55 | 41.94 | 113.87 | 20.44 | 0.00 | 0.00 | 720.00 |
July | 103.13 | 63.96 | 39.17 | 110.79 | 25.32 | 1.33 | 0.00 | 744.00 |
August | 85.59 | 49.09 | 36.50 | 92.50 | 25.57 | 0.00 | 0.00 | 744.00 |
September | 65.90 | 38.27 | 27.63 | 64.67 | 34.08 | 0.00 | 0.00 | 720.00 |
October | 40.93 | 19.82 | 21.10 | 36.37 | 28.40 | 1.33 | 0.00 | 744.00 |
November | 24.03 | 8.30 | 15.73 | 12.61 | 44.17 | 0.33 | 0.00 | 720.00 |
December | 15.91 | 7.17 | 8.73 | 1.63 | 69.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 59.64 | 32.98 | 26.66 | 56.70 | 39.03 | 18.33 | 0.00 | 8760.00 |
Minimum of Months | 15.91 | 7.17 | 8.73 | 1.63 | 17.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.13 | 63.96 | 41.94 | 113.87 | 81.76 | 8.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.92 | 9.64 | 14.28 | 3.57 | 81.76 | 0.00 | 0.00 | 744.00 |
February | 33.32 | 15.99 | 17.33 | 15.00 | 63.21 | 0.00 | 0.00 | 672.00 |
March | 54.33 | 25.92 | 28.41 | 47.91 | 35.48 | 1.33 | 0.00 | 744.00 |
April | 74.53 | 45.02 | 29.51 | 77.14 | 23.77 | 8.33 | 0.00 | 720.00 |
May | 89.98 | 51.07 | 38.92 | 101.60 | 17.86 | 5.67 | 0.00 | 744.00 |
June | 102.48 | 60.55 | 41.94 | 113.87 | 20.44 | 0.00 | 0.00 | 720.00 |
July | 103.13 | 63.96 | 39.17 | 110.79 | 25.32 | 1.33 | 0.00 | 744.00 |
August | 85.59 | 49.09 | 36.50 | 92.50 | 25.57 | 0.00 | 0.00 | 744.00 |
September | 65.90 | 38.27 | 27.63 | 64.67 | 34.08 | 0.00 | 0.00 | 720.00 |
October | 40.93 | 19.82 | 21.10 | 36.37 | 28.40 | 1.33 | 0.00 | 744.00 |
November | 24.03 | 8.30 | 15.73 | 12.61 | 44.17 | 0.33 | 0.00 | 720.00 |
December | 15.91 | 7.17 | 8.73 | 1.63 | 69.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 59.64 | 32.98 | 26.66 | 56.70 | 39.03 | 18.33 | 0.00 | 8760.00 |
Minimum of Months | 15.91 | 7.17 | 8.73 | 1.63 | 17.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.13 | 63.96 | 41.94 | 113.87 | 81.76 | 8.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.92 | 9.64 | 14.28 | 3.57 | 81.76 | 0.00 | 0.00 | 744.00 |
February | 33.32 | 15.99 | 17.33 | 15.00 | 63.21 | 0.00 | 0.00 | 672.00 |
March | 54.33 | 25.92 | 28.41 | 47.91 | 35.48 | 1.33 | 0.00 | 744.00 |
April | 74.53 | 45.02 | 29.51 | 77.14 | 23.77 | 8.33 | 0.00 | 720.00 |
May | 89.98 | 51.07 | 38.92 | 101.60 | 17.86 | 5.67 | 0.00 | 744.00 |
June | 102.48 | 60.55 | 41.94 | 113.87 | 20.44 | 0.00 | 0.00 | 720.00 |
July | 103.13 | 63.96 | 39.17 | 110.79 | 25.32 | 1.33 | 0.00 | 744.00 |
August | 85.59 | 49.09 | 36.50 | 92.50 | 25.57 | 0.00 | 0.00 | 744.00 |
September | 65.90 | 38.27 | 27.63 | 64.67 | 34.08 | 0.00 | 0.00 | 720.00 |
October | 40.93 | 19.82 | 21.10 | 36.37 | 28.40 | 1.33 | 0.00 | 744.00 |
November | 24.03 | 8.30 | 15.73 | 12.61 | 44.17 | 0.33 | 0.00 | 720.00 |
December | 15.91 | 7.17 | 8.73 | 1.63 | 69.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 59.64 | 32.98 | 26.66 | 56.70 | 39.03 | 18.33 | 0.00 | 8760.00 |
Minimum of Months | 15.91 | 7.17 | 8.73 | 1.63 | 17.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.13 | 63.96 | 41.94 | 113.87 | 81.76 | 8.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.92 | 9.64 | 14.28 | 3.57 | 81.76 | 0.00 | 0.00 | 744.00 |
February | 33.32 | 15.99 | 17.33 | 15.00 | 63.21 | 0.00 | 0.00 | 672.00 |
March | 54.33 | 25.92 | 28.41 | 47.91 | 35.48 | 1.33 | 0.00 | 744.00 |
April | 74.53 | 45.02 | 29.51 | 77.14 | 23.77 | 8.33 | 0.00 | 720.00 |
May | 89.98 | 51.07 | 38.92 | 101.60 | 17.86 | 5.67 | 0.00 | 744.00 |
June | 102.48 | 60.55 | 41.94 | 113.87 | 20.44 | 0.00 | 0.00 | 720.00 |
July | 103.13 | 63.96 | 39.17 | 110.79 | 25.32 | 1.33 | 0.00 | 744.00 |
August | 85.59 | 49.09 | 36.50 | 92.50 | 25.57 | 0.00 | 0.00 | 744.00 |
September | 65.90 | 38.27 | 27.63 | 64.67 | 34.08 | 0.00 | 0.00 | 720.00 |
October | 40.93 | 19.82 | 21.10 | 36.37 | 28.40 | 1.33 | 0.00 | 744.00 |
November | 24.03 | 8.30 | 15.73 | 12.61 | 44.17 | 0.33 | 0.00 | 720.00 |
December | 15.91 | 7.17 | 8.73 | 1.63 | 69.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 59.64 | 32.98 | 26.66 | 56.70 | 39.03 | 18.33 | 0.00 | 8760.00 |
Minimum of Months | 15.91 | 7.17 | 8.73 | 1.63 | 17.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.13 | 63.96 | 41.94 | 113.87 | 81.76 | 8.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.92 | 9.64 | 14.28 | 3.57 | 81.76 | 0.00 | 0.00 | 744.00 |
February | 33.32 | 15.99 | 17.33 | 15.00 | 63.21 | 0.00 | 0.00 | 672.00 |
March | 54.33 | 25.92 | 28.41 | 47.91 | 35.48 | 1.33 | 0.00 | 744.00 |
April | 74.53 | 45.02 | 29.51 | 77.14 | 23.77 | 8.33 | 0.00 | 720.00 |
May | 89.98 | 51.07 | 38.92 | 101.60 | 17.86 | 5.67 | 0.00 | 744.00 |
June | 102.48 | 60.55 | 41.94 | 113.87 | 20.44 | 0.00 | 0.00 | 720.00 |
July | 103.13 | 63.96 | 39.17 | 110.79 | 25.32 | 1.33 | 0.00 | 744.00 |
August | 85.59 | 49.09 | 36.50 | 92.50 | 25.57 | 0.00 | 0.00 | 744.00 |
September | 65.90 | 38.27 | 27.63 | 64.67 | 34.08 | 0.00 | 0.00 | 720.00 |
October | 40.93 | 19.82 | 21.10 | 36.37 | 28.40 | 1.33 | 0.00 | 744.00 |
November | 24.03 | 8.30 | 15.73 | 12.61 | 44.17 | 0.33 | 0.00 | 720.00 |
December | 15.91 | 7.17 | 8.73 | 1.63 | 69.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 59.64 | 32.98 | 26.66 | 56.70 | 39.03 | 18.33 | 0.00 | 8760.00 |
Minimum of Months | 15.91 | 7.17 | 8.73 | 1.63 | 17.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.13 | 63.96 | 41.94 | 113.87 | 81.76 | 8.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.92 | 9.64 | 14.28 | 3.57 | 81.76 | 0.00 | 0.00 | 744.00 |
February | 33.32 | 15.99 | 17.33 | 15.00 | 63.21 | 0.00 | 0.00 | 672.00 |
March | 54.33 | 25.92 | 28.41 | 47.91 | 35.48 | 1.33 | 0.00 | 744.00 |
April | 74.53 | 45.02 | 29.51 | 77.14 | 23.77 | 8.33 | 0.00 | 720.00 |
May | 89.98 | 51.07 | 38.92 | 101.60 | 17.86 | 5.67 | 0.00 | 744.00 |
June | 102.48 | 60.55 | 41.94 | 113.87 | 20.44 | 0.00 | 0.00 | 720.00 |
July | 103.13 | 63.96 | 39.17 | 110.79 | 25.32 | 1.33 | 0.00 | 744.00 |
August | 85.59 | 49.09 | 36.50 | 92.50 | 25.57 | 0.00 | 0.00 | 744.00 |
September | 65.90 | 38.27 | 27.63 | 64.67 | 34.08 | 0.00 | 0.00 | 720.00 |
October | 40.93 | 19.82 | 21.10 | 36.37 | 28.40 | 1.33 | 0.00 | 744.00 |
November | 24.03 | 8.30 | 15.73 | 12.61 | 44.17 | 0.33 | 0.00 | 720.00 |
December | 15.91 | 7.17 | 8.73 | 1.63 | 69.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 59.64 | 32.98 | 26.66 | 56.70 | 39.03 | 18.33 | 0.00 | 8760.00 |
Minimum of Months | 15.91 | 7.17 | 8.73 | 1.63 | 17.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.13 | 63.96 | 41.94 | 113.87 | 81.76 | 8.33 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189225E+09 | 76770258.35 | 0.112455E+09 | 51266807.90 | 0.835310E+09 |
February | 0.248603E+09 | 0.121942E+09 | 0.126661E+09 | 0.119024E+09 | 0.588188E+09 |
March | 0.330496E+09 | 0.123125E+09 | 0.207371E+09 | 0.200312E+09 | 0.393767E+09 |
April | 0.466263E+09 | 0.230425E+09 | 0.235838E+09 | 0.425395E+09 | 0.255329E+09 |
May | 0.483032E+09 | 0.192957E+09 | 0.290075E+09 | 0.485194E+09 | 0.152970E+09 |
June | 0.547616E+09 | 0.236823E+09 | 0.310793E+09 | 0.596795E+09 | 0.135412E+09 |
July | 0.608868E+09 | 0.289304E+09 | 0.319564E+09 | 0.674972E+09 | 0.139920E+09 |
August | 0.530728E+09 | 0.242720E+09 | 0.288008E+09 | 0.593117E+09 | 0.158981E+09 |
September | 0.416829E+09 | 0.197631E+09 | 0.219199E+09 | 0.422544E+09 | 0.222821E+09 |
October | 0.301444E+09 | 0.134369E+09 | 0.167075E+09 | 0.238596E+09 | 0.284370E+09 |
November | 0.174513E+09 | 64823607.24 | 0.109690E+09 | 79254496.80 | 0.467420E+09 |
December | 0.139289E+09 | 66253391.04 | 73035246.63 | 47989390.71 | 0.730901E+09 |
Annual Sum or Average | 0.443691E+10 | 0.197714E+10 | 0.245976E+10 | 0.393446E+10 | 0.436539E+10 |
Minimum of Months | 0.139289E+09 | 64823607.24 | 73035246.63 | 47989390.71 | 0.135412E+09 |
Maximum of Months | 0.608868E+09 | 0.289304E+09 | 0.319564E+09 | 0.674972E+09 | 0.835310E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189225E+09 | 76770258.35 | 0.112455E+09 | 51266807.90 | 0.835310E+09 |
February | 0.248603E+09 | 0.121942E+09 | 0.126661E+09 | 0.119024E+09 | 0.588188E+09 |
March | 0.330496E+09 | 0.123125E+09 | 0.207371E+09 | 0.200312E+09 | 0.393767E+09 |
April | 0.466263E+09 | 0.230425E+09 | 0.235838E+09 | 0.425395E+09 | 0.255329E+09 |
May | 0.483032E+09 | 0.192957E+09 | 0.290075E+09 | 0.485194E+09 | 0.152970E+09 |
June | 0.547616E+09 | 0.236823E+09 | 0.310793E+09 | 0.596795E+09 | 0.135412E+09 |
July | 0.608868E+09 | 0.289304E+09 | 0.319564E+09 | 0.674972E+09 | 0.139920E+09 |
August | 0.530728E+09 | 0.242720E+09 | 0.288008E+09 | 0.593117E+09 | 0.158981E+09 |
September | 0.416829E+09 | 0.197631E+09 | 0.219199E+09 | 0.422544E+09 | 0.222821E+09 |
October | 0.301444E+09 | 0.134369E+09 | 0.167075E+09 | 0.238596E+09 | 0.284370E+09 |
November | 0.174513E+09 | 64823607.24 | 0.109690E+09 | 79254496.80 | 0.467420E+09 |
December | 0.139289E+09 | 66253391.04 | 73035246.63 | 47989390.71 | 0.730901E+09 |
Annual Sum or Average | 0.443691E+10 | 0.197714E+10 | 0.245976E+10 | 0.393446E+10 | 0.436539E+10 |
Minimum of Months | 0.139289E+09 | 64823607.24 | 73035246.63 | 47989390.71 | 0.135412E+09 |
Maximum of Months | 0.608868E+09 | 0.289304E+09 | 0.319564E+09 | 0.674972E+09 | 0.835310E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51785475.02 | 0.00 | 51785475.02 | 0.00 | 0.529946E+09 |
February | 59300287.05 | 0.00 | 59300287.05 | 762870.02 | 0.378914E+09 |
March | 98412437.69 | 2555.31 | 98409882.39 | 19685213.73 | 0.249819E+09 |
April | 0.110175E+09 | 742859.63 | 0.109432E+09 | 49669757.93 | 0.156073E+09 |
May | 0.148348E+09 | 5729827.66 | 0.142618E+09 | 0.107023E+09 | 87346935.45 |
June | 0.167408E+09 | 15102811.99 | 0.152306E+09 | 0.139759E+09 | 74175177.00 |
July | 0.162282E+09 | 10865282.36 | 0.151417E+09 | 0.135499E+09 | 77569284.39 |
August | 0.136413E+09 | 2828771.71 | 0.133584E+09 | 0.122265E+09 | 91571519.23 |
September | 0.100963E+09 | 65724.61 | 0.100898E+09 | 69604030.47 | 0.133207E+09 |
October | 77497403.21 | 0.00 | 77497403.21 | 26520183.44 | 0.174022E+09 |
November | 52461463.12 | 0.00 | 52461463.12 | 5248789.99 | 0.290443E+09 |
December | 35164001.71 | 0.00 | 35164001.71 | 0.00 | 0.454382E+09 |
Annual Sum or Average | 0.120021E+10 | 35337833.27 | 0.116487E+10 | 0.676036E+09 | 0.269747E+10 |
Minimum of Months | 35164001.71 | 0.00 | 35164001.71 | 0.00 | 74175177.00 |
Maximum of Months | 0.167408E+09 | 15102811.99 | 0.152306E+09 | 0.139759E+09 | 0.529946E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51783807.94 | 0.00 | 51783807.94 | 0.00 | 0.529947E+09 |
February | 59298441.20 | 0.00 | 59298441.20 | 762719.80 | 0.378915E+09 |
March | 98409312.96 | 2555.19 | 98406757.77 | 19683678.75 | 0.249820E+09 |
April | 0.110172E+09 | 742824.81 | 0.109429E+09 | 49667801.89 | 0.156073E+09 |
May | 0.148344E+09 | 5729559.10 | 0.142614E+09 | 0.107019E+09 | 87346739.64 |
June | 0.167403E+09 | 15102104.10 | 0.152301E+09 | 0.139754E+09 | 74174866.94 |
July | 0.162277E+09 | 10864773.09 | 0.151412E+09 | 0.135494E+09 | 77568698.07 |
August | 0.136409E+09 | 2828639.12 | 0.133580E+09 | 0.122261E+09 | 91571082.70 |
September | 0.100960E+09 | 65721.53 | 0.100895E+09 | 69601665.55 | 0.133206E+09 |
October | 77494965.54 | 0.00 | 77494965.54 | 26518486.46 | 0.174021E+09 |
November | 52459712.13 | 0.00 | 52459712.13 | 5248342.61 | 0.290444E+09 |
December | 35162889.56 | 0.00 | 35162889.56 | 0.00 | 0.454382E+09 |
Annual Sum or Average | 0.120017E+10 | 35336176.94 | 0.116484E+10 | 0.676011E+09 | 0.269747E+10 |
Minimum of Months | 35162889.56 | 0.00 | 35162889.56 | 0.00 | 74174866.94 |
Maximum of Months | 0.167403E+09 | 15102104.10 | 0.152301E+09 | 0.139754E+09 | 0.529947E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64066661.92 | 25820067.05 | 38246594.86 | 9561017.16 | 0.218984E+09 |
February | 80601999.45 | 38676957.68 | 41925041.76 | 36295411.14 | 0.152916E+09 |
March | 0.145514E+09 | 69431308.17 | 76082991.09 | 0.128327E+09 | 95025635.82 |
April | 0.193177E+09 | 0.116695E+09 | 76481455.27 | 0.199938E+09 | 61599149.64 |
May | 0.241011E+09 | 0.136773E+09 | 0.104239E+09 | 0.272123E+09 | 47840932.94 |
June | 0.265633E+09 | 0.156935E+09 | 0.108697E+09 | 0.295155E+09 | 52982020.53 |
July | 0.276232E+09 | 0.171321E+09 | 0.104911E+09 | 0.296729E+09 | 67812103.78 |
August | 0.229244E+09 | 0.131488E+09 | 97755922.95 | 0.247756E+09 | 68496339.85 |
September | 0.170825E+09 | 99195894.74 | 71629561.99 | 0.167629E+09 | 88344040.85 |
October | 0.109619E+09 | 53092650.22 | 56526826.74 | 97408028.87 | 76064102.05 |
November | 62287078.26 | 21525206.90 | 40761871.36 | 32679079.87 | 0.114480E+09 |
December | 42600948.72 | 19206670.47 | 23394278.25 | 4371248.96 | 0.186309E+09 |
Annual Sum or Average | 0.188081E+10 | 0.104016E+10 | 0.840651E+09 | 0.178797E+10 | 0.123085E+10 |
Minimum of Months | 42600948.72 | 19206670.47 | 23394278.25 | 4371248.96 | 47840932.94 |
Maximum of Months | 0.276232E+09 | 0.171321E+09 | 0.108697E+09 | 0.296729E+09 | 0.218984E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64066661.92 | 25820067.05 | 38246594.86 | 9561017.16 | 0.218984E+09 |
February | 80601999.45 | 38676957.68 | 41925041.76 | 36295411.14 | 0.152916E+09 |
March | 0.145514E+09 | 69431308.17 | 76082991.09 | 0.128327E+09 | 95025635.82 |
April | 0.193177E+09 | 0.116695E+09 | 76481455.27 | 0.199938E+09 | 61599149.64 |
May | 0.241011E+09 | 0.136773E+09 | 0.104239E+09 | 0.272123E+09 | 47840932.94 |
June | 0.265633E+09 | 0.156935E+09 | 0.108697E+09 | 0.295155E+09 | 52982020.53 |
July | 0.276232E+09 | 0.171321E+09 | 0.104911E+09 | 0.296729E+09 | 67812103.78 |
August | 0.229244E+09 | 0.131488E+09 | 97755922.95 | 0.247756E+09 | 68496339.85 |
September | 0.170825E+09 | 99195894.74 | 71629561.99 | 0.167629E+09 | 88344040.85 |
October | 0.109619E+09 | 53092650.22 | 56526826.74 | 97408028.87 | 76064102.05 |
November | 62287078.26 | 21525206.90 | 40761871.36 | 32679079.87 | 0.114480E+09 |
December | 42600948.72 | 19206670.47 | 23394278.25 | 4371248.96 | 0.186309E+09 |
Annual Sum or Average | 0.188081E+10 | 0.104016E+10 | 0.840651E+09 | 0.178797E+10 | 0.123085E+10 |
Minimum of Months | 42600948.72 | 19206670.47 | 23394278.25 | 4371248.96 | 47840932.94 |
Maximum of Months | 0.276232E+09 | 0.171321E+09 | 0.108697E+09 | 0.296729E+09 | 0.218984E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64066661.92 | 25820067.05 | 38246594.86 | 9561017.16 | 0.218984E+09 |
February | 80601999.45 | 38676957.68 | 41925041.76 | 36295411.14 | 0.152916E+09 |
March | 0.145514E+09 | 69431308.17 | 76082991.09 | 0.128327E+09 | 95025635.82 |
April | 0.193177E+09 | 0.116695E+09 | 76481455.27 | 0.199938E+09 | 61599149.64 |
May | 0.241011E+09 | 0.136773E+09 | 0.104239E+09 | 0.272123E+09 | 47840932.94 |
June | 0.265633E+09 | 0.156935E+09 | 0.108697E+09 | 0.295155E+09 | 52982020.53 |
July | 0.276232E+09 | 0.171321E+09 | 0.104911E+09 | 0.296729E+09 | 67812103.78 |
August | 0.229244E+09 | 0.131488E+09 | 97755922.95 | 0.247756E+09 | 68496339.85 |
September | 0.170825E+09 | 99195894.74 | 71629561.99 | 0.167629E+09 | 88344040.85 |
October | 0.109619E+09 | 53092650.22 | 56526826.74 | 97408028.87 | 76064102.05 |
November | 62287078.26 | 21525206.90 | 40761871.36 | 32679079.87 | 0.114480E+09 |
December | 42600948.72 | 19206670.47 | 23394278.25 | 4371248.96 | 0.186309E+09 |
Annual Sum or Average | 0.188081E+10 | 0.104016E+10 | 0.840651E+09 | 0.178797E+10 | 0.123085E+10 |
Minimum of Months | 42600948.72 | 19206670.47 | 23394278.25 | 4371248.96 | 47840932.94 |
Maximum of Months | 0.276232E+09 | 0.171321E+09 | 0.108697E+09 | 0.296729E+09 | 0.218984E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64066661.92 | 25820067.05 | 38246594.86 | 9561017.16 | 0.218984E+09 |
February | 80601999.45 | 38676957.68 | 41925041.76 | 36295411.14 | 0.152916E+09 |
March | 0.145514E+09 | 69431308.17 | 76082991.09 | 0.128327E+09 | 95025635.82 |
April | 0.193177E+09 | 0.116695E+09 | 76481455.27 | 0.199938E+09 | 61599149.64 |
May | 0.241011E+09 | 0.136773E+09 | 0.104239E+09 | 0.272123E+09 | 47840932.94 |
June | 0.265633E+09 | 0.156935E+09 | 0.108697E+09 | 0.295155E+09 | 52982020.53 |
July | 0.276232E+09 | 0.171321E+09 | 0.104911E+09 | 0.296729E+09 | 67812103.78 |
August | 0.229244E+09 | 0.131488E+09 | 97755922.95 | 0.247756E+09 | 68496339.85 |
September | 0.170825E+09 | 99195894.74 | 71629561.99 | 0.167629E+09 | 88344040.85 |
October | 0.109619E+09 | 53092650.22 | 56526826.74 | 97408028.87 | 76064102.05 |
November | 62287078.26 | 21525206.90 | 40761871.36 | 32679079.87 | 0.114480E+09 |
December | 42600948.72 | 19206670.47 | 23394278.25 | 4371248.96 | 0.186309E+09 |
Annual Sum or Average | 0.188081E+10 | 0.104016E+10 | 0.840651E+09 | 0.178797E+10 | 0.123085E+10 |
Minimum of Months | 42600948.72 | 19206670.47 | 23394278.25 | 4371248.96 | 47840932.94 |
Maximum of Months | 0.276232E+09 | 0.171321E+09 | 0.108697E+09 | 0.296729E+09 | 0.218984E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64066661.92 | 25820067.05 | 38246594.86 | 9561017.16 | 0.218984E+09 |
February | 80601999.45 | 38676957.68 | 41925041.76 | 36295411.14 | 0.152916E+09 |
March | 0.145514E+09 | 69431308.17 | 76082991.09 | 0.128327E+09 | 95025635.82 |
April | 0.193177E+09 | 0.116695E+09 | 76481455.27 | 0.199938E+09 | 61599149.64 |
May | 0.241011E+09 | 0.136773E+09 | 0.104239E+09 | 0.272123E+09 | 47840932.94 |
June | 0.265633E+09 | 0.156935E+09 | 0.108697E+09 | 0.295155E+09 | 52982020.53 |
July | 0.276232E+09 | 0.171321E+09 | 0.104911E+09 | 0.296729E+09 | 67812103.78 |
August | 0.229244E+09 | 0.131488E+09 | 97755922.95 | 0.247756E+09 | 68496339.85 |
September | 0.170825E+09 | 99195894.74 | 71629561.99 | 0.167629E+09 | 88344040.85 |
October | 0.109619E+09 | 53092650.22 | 56526826.74 | 97408028.87 | 76064102.05 |
November | 62287078.26 | 21525206.90 | 40761871.36 | 32679079.87 | 0.114480E+09 |
December | 42600948.72 | 19206670.47 | 23394278.25 | 4371248.96 | 0.186309E+09 |
Annual Sum or Average | 0.188081E+10 | 0.104016E+10 | 0.840651E+09 | 0.178797E+10 | 0.123085E+10 |
Minimum of Months | 42600948.72 | 19206670.47 | 23394278.25 | 4371248.96 | 47840932.94 |
Maximum of Months | 0.276232E+09 | 0.171321E+09 | 0.108697E+09 | 0.296729E+09 | 0.218984E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64066661.92 | 25820067.05 | 38246594.86 | 9561017.16 | 0.218984E+09 |
February | 80601999.45 | 38676957.68 | 41925041.76 | 36295411.14 | 0.152916E+09 |
March | 0.145514E+09 | 69431308.17 | 76082991.09 | 0.128327E+09 | 95025635.82 |
April | 0.193177E+09 | 0.116695E+09 | 76481455.27 | 0.199938E+09 | 61599149.64 |
May | 0.241011E+09 | 0.136773E+09 | 0.104239E+09 | 0.272123E+09 | 47840932.94 |
June | 0.265633E+09 | 0.156935E+09 | 0.108697E+09 | 0.295155E+09 | 52982020.53 |
July | 0.276232E+09 | 0.171321E+09 | 0.104911E+09 | 0.296729E+09 | 67812103.78 |
August | 0.229244E+09 | 0.131488E+09 | 97755922.95 | 0.247756E+09 | 68496339.85 |
September | 0.170825E+09 | 99195894.74 | 71629561.99 | 0.167629E+09 | 88344040.85 |
October | 0.109619E+09 | 53092650.22 | 56526826.74 | 97408028.87 | 76064102.05 |
November | 62287078.26 | 21525206.90 | 40761871.36 | 32679079.87 | 0.114480E+09 |
December | 42600948.72 | 19206670.47 | 23394278.25 | 4371248.96 | 0.186309E+09 |
Annual Sum or Average | 0.188081E+10 | 0.104016E+10 | 0.840651E+09 | 0.178797E+10 | 0.123085E+10 |
Minimum of Months | 42600948.72 | 19206670.47 | 23394278.25 | 4371248.96 | 47840932.94 |
Maximum of Months | 0.276232E+09 | 0.171321E+09 | 0.108697E+09 | 0.296729E+09 | 0.218984E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64066661.92 | 25820067.05 | 38246594.86 | 9561017.16 | 0.218984E+09 |
February | 80601999.45 | 38676957.68 | 41925041.76 | 36295411.14 | 0.152916E+09 |
March | 0.145514E+09 | 69431308.17 | 76082991.09 | 0.128327E+09 | 95025635.82 |
April | 0.193177E+09 | 0.116695E+09 | 76481455.27 | 0.199938E+09 | 61599149.64 |
May | 0.241011E+09 | 0.136773E+09 | 0.104239E+09 | 0.272123E+09 | 47840932.94 |
June | 0.265633E+09 | 0.156935E+09 | 0.108697E+09 | 0.295155E+09 | 52982020.53 |
July | 0.276232E+09 | 0.171321E+09 | 0.104911E+09 | 0.296729E+09 | 67812103.78 |
August | 0.229244E+09 | 0.131488E+09 | 97755922.95 | 0.247756E+09 | 68496339.85 |
September | 0.170825E+09 | 99195894.74 | 71629561.99 | 0.167629E+09 | 88344040.85 |
October | 0.109619E+09 | 53092650.22 | 56526826.74 | 97408028.87 | 76064102.05 |
November | 62287078.26 | 21525206.90 | 40761871.36 | 32679079.87 | 0.114480E+09 |
December | 42600948.72 | 19206670.47 | 23394278.25 | 4371248.96 | 0.186309E+09 |
Annual Sum or Average | 0.188081E+10 | 0.104016E+10 | 0.840651E+09 | 0.178797E+10 | 0.123085E+10 |
Minimum of Months | 42600948.72 | 19206670.47 | 23394278.25 | 4371248.96 | 47840932.94 |
Maximum of Months | 0.276232E+09 | 0.171321E+09 | 0.108697E+09 | 0.296729E+09 | 0.218984E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64066661.92 | 25820067.05 | 38246594.86 | 9561017.16 | 0.218984E+09 |
February | 80601999.45 | 38676957.68 | 41925041.76 | 36295411.14 | 0.152916E+09 |
March | 0.145514E+09 | 69431308.17 | 76082991.09 | 0.128327E+09 | 95025635.82 |
April | 0.193177E+09 | 0.116695E+09 | 76481455.27 | 0.199938E+09 | 61599149.64 |
May | 0.241011E+09 | 0.136773E+09 | 0.104239E+09 | 0.272123E+09 | 47840932.94 |
June | 0.265633E+09 | 0.156935E+09 | 0.108697E+09 | 0.295155E+09 | 52982020.53 |
July | 0.276232E+09 | 0.171321E+09 | 0.104911E+09 | 0.296729E+09 | 67812103.78 |
August | 0.229244E+09 | 0.131488E+09 | 97755922.95 | 0.247756E+09 | 68496339.85 |
September | 0.170825E+09 | 99195894.74 | 71629561.99 | 0.167629E+09 | 88344040.85 |
October | 0.109619E+09 | 53092650.22 | 56526826.74 | 97408028.87 | 76064102.05 |
November | 62287078.26 | 21525206.90 | 40761871.36 | 32679079.87 | 0.114480E+09 |
December | 42600948.72 | 19206670.47 | 23394278.25 | 4371248.96 | 0.186309E+09 |
Annual Sum or Average | 0.188081E+10 | 0.104016E+10 | 0.840651E+09 | 0.178797E+10 | 0.123085E+10 |
Minimum of Months | 42600948.72 | 19206670.47 | 23394278.25 | 4371248.96 | 47840932.94 |
Maximum of Months | 0.276232E+09 | 0.171321E+09 | 0.108697E+09 | 0.296729E+09 | 0.218984E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64066661.92 | 25820067.05 | 38246594.86 | 9561017.16 | 0.218984E+09 |
February | 80601999.45 | 38676957.68 | 41925041.76 | 36295411.14 | 0.152916E+09 |
March | 0.145514E+09 | 69431308.17 | 76082991.09 | 0.128327E+09 | 95025635.82 |
April | 0.193177E+09 | 0.116695E+09 | 76481455.27 | 0.199938E+09 | 61599149.64 |
May | 0.241011E+09 | 0.136773E+09 | 0.104239E+09 | 0.272123E+09 | 47840932.94 |
June | 0.265633E+09 | 0.156935E+09 | 0.108697E+09 | 0.295155E+09 | 52982020.53 |
July | 0.276232E+09 | 0.171321E+09 | 0.104911E+09 | 0.296729E+09 | 67812103.78 |
August | 0.229244E+09 | 0.131488E+09 | 97755922.95 | 0.247756E+09 | 68496339.85 |
September | 0.170825E+09 | 99195894.74 | 71629561.99 | 0.167629E+09 | 88344040.85 |
October | 0.109619E+09 | 53092650.22 | 56526826.74 | 97408028.87 | 76064102.05 |
November | 62287078.26 | 21525206.90 | 40761871.36 | 32679079.87 | 0.114480E+09 |
December | 42600948.72 | 19206670.47 | 23394278.25 | 4371248.96 | 0.186309E+09 |
Annual Sum or Average | 0.188081E+10 | 0.104016E+10 | 0.840651E+09 | 0.178797E+10 | 0.123085E+10 |
Minimum of Months | 42600948.72 | 19206670.47 | 23394278.25 | 4371248.96 | 47840932.94 |
Maximum of Months | 0.276232E+09 | 0.171321E+09 | 0.108697E+09 | 0.296729E+09 | 0.218984E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64066661.92 | 25820067.05 | 38246594.86 | 9561017.16 | 0.218984E+09 |
February | 80601999.45 | 38676957.68 | 41925041.76 | 36295411.14 | 0.152916E+09 |
March | 0.145514E+09 | 69431308.17 | 76082991.09 | 0.128327E+09 | 95025635.82 |
April | 0.193177E+09 | 0.116695E+09 | 76481455.27 | 0.199938E+09 | 61599149.64 |
May | 0.241011E+09 | 0.136773E+09 | 0.104239E+09 | 0.272123E+09 | 47840932.94 |
June | 0.265633E+09 | 0.156935E+09 | 0.108697E+09 | 0.295155E+09 | 52982020.53 |
July | 0.276232E+09 | 0.171321E+09 | 0.104911E+09 | 0.296729E+09 | 67812103.78 |
August | 0.229244E+09 | 0.131488E+09 | 97755922.95 | 0.247756E+09 | 68496339.85 |
September | 0.170825E+09 | 99195894.74 | 71629561.99 | 0.167629E+09 | 88344040.85 |
October | 0.109619E+09 | 53092650.22 | 56526826.74 | 97408028.87 | 76064102.05 |
November | 62287078.26 | 21525206.90 | 40761871.36 | 32679079.87 | 0.114480E+09 |
December | 42600948.72 | 19206670.47 | 23394278.25 | 4371248.96 | 0.186309E+09 |
Annual Sum or Average | 0.188081E+10 | 0.104016E+10 | 0.840651E+09 | 0.178797E+10 | 0.123085E+10 |
Minimum of Months | 42600948.72 | 19206670.47 | 23394278.25 | 4371248.96 | 47840932.94 |
Maximum of Months | 0.276232E+09 | 0.171321E+09 | 0.108697E+09 | 0.296729E+09 | 0.218984E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.04 | 1003.21 | 179.97 | 57.33 | 122.64 | 0.00 | 0.00 |
February | 77.95 | 778.44 | 254.55 | 100.81 | 153.74 | 0.00 | 0.00 |
March | 153.26 | 469.56 | 320.27 | 91.94 | 228.33 | 0.00 | 0.00 |
April | 362.07 | 312.94 | 444.78 | 178.37 | 266.41 | 0.00 | 0.00 |
May | 441.41 | 178.65 | 471.46 | 148.36 | 323.10 | 0.00 | 0.00 |
June | 566.43 | 159.82 | 551.71 | 194.39 | 357.33 | 0.00 | 0.00 |
July | 603.85 | 161.07 | 575.83 | 224.14 | 351.69 | 0.00 | 0.00 |
August | 533.27 | 186.18 | 498.16 | 183.35 | 314.81 | 0.00 | 0.00 |
September | 377.40 | 272.37 | 399.53 | 152.54 | 246.99 | 0.00 | 0.00 |
October | 192.77 | 337.10 | 282.96 | 100.34 | 182.62 | 0.00 | 0.00 |
November | 57.11 | 576.68 | 175.13 | 50.02 | 125.12 | 0.00 | 0.00 |
December | 23.61 | 872.84 | 130.27 | 49.47 | 80.79 | 0.00 | 0.00 |
Annual Sum or Average | 285.34 | 440.87 | 357.50 | 127.63 | 229.87 | 0.00 | 0.00 |
Minimum of Months | 22.04 | 159.82 | 130.27 | 49.47 | 80.79 | 0.00 | 0.00 |
Maximum of Months | 603.85 | 1003.21 | 575.83 | 224.14 | 357.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 35.70 | 817.59 | 239.20 | 96.40 | 142.80 | 0.00 | 0.00 |
February | 150.03 | 632.10 | 333.18 | 159.87 | 173.30 | 0.00 | 0.00 |
March | 479.12 | 354.78 | 543.29 | 259.23 | 284.06 | 0.00 | 0.00 |
April | 771.36 | 237.65 | 745.28 | 450.21 | 295.07 | 0.00 | 0.00 |
May | 1015.99 | 178.62 | 899.83 | 510.65 | 389.18 | 0.00 | 0.00 |
June | 1138.71 | 204.41 | 1024.82 | 605.46 | 419.36 | 0.00 | 0.00 |
July | 1107.86 | 253.18 | 1031.33 | 639.64 | 391.69 | 0.00 | 0.00 |
August | 925.01 | 255.74 | 855.90 | 490.92 | 364.98 | 0.00 | 0.00 |
September | 646.72 | 340.83 | 659.05 | 382.70 | 276.35 | 0.00 | 0.00 |
October | 363.68 | 283.99 | 409.27 | 198.23 | 211.05 | 0.00 | 0.00 |
November | 126.08 | 441.67 | 240.31 | 83.04 | 157.26 | 0.00 | 0.00 |
December | 16.32 | 695.60 | 159.05 | 71.71 | 87.34 | 0.00 | 0.00 |
Annual Sum or Average | 566.96 | 390.30 | 596.40 | 329.83 | 266.57 | 0.00 | 0.00 |
Minimum of Months | 16.32 | 178.62 | 159.05 | 71.71 | 87.34 | 0.00 | 0.00 |
Maximum of Months | 1138.71 | 817.59 | 1031.33 | 639.64 | 419.36 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 59023964.46 | 0.268700E+10 | 0.482020E+09 | 0.153541E+09 | 0.328480E+09 | 0.00 | 0.00 |
February | 0.188573E+09 | 0.188321E+10 | 0.615804E+09 | 0.243884E+09 | 0.371920E+09 | 0.00 | 0.00 |
March | 0.410490E+09 | 0.125767E+10 | 0.857814E+09 | 0.246255E+09 | 0.611559E+09 | 0.00 | 0.00 |
April | 0.938473E+09 | 0.811149E+09 | 0.115287E+10 | 0.462335E+09 | 0.690537E+09 | 0.00 | 0.00 |
May | 0.118228E+10 | 0.478483E+09 | 0.126276E+10 | 0.397373E+09 | 0.865383E+09 | 0.00 | 0.00 |
June | 0.146819E+10 | 0.414263E+09 | 0.143004E+10 | 0.503851E+09 | 0.926192E+09 | 0.00 | 0.00 |
July | 0.161736E+10 | 0.431401E+09 | 0.154230E+10 | 0.600339E+09 | 0.941956E+09 | 0.00 | 0.00 |
August | 0.142832E+10 | 0.498659E+09 | 0.133428E+10 | 0.491098E+09 | 0.843181E+09 | 0.00 | 0.00 |
September | 0.978210E+09 | 0.705973E+09 | 0.103558E+10 | 0.395393E+09 | 0.640190E+09 | 0.00 | 0.00 |
October | 0.516326E+09 | 0.902879E+09 | 0.757881E+09 | 0.268739E+09 | 0.489143E+09 | 0.00 | 0.00 |
November | 0.148027E+09 | 0.149475E+10 | 0.453948E+09 | 0.129647E+09 | 0.324301E+09 | 0.00 | 0.00 |
December | 63233564.39 | 0.233782E+10 | 0.348904E+09 | 0.132507E+09 | 0.216397E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.899850E+10 | 0.139033E+11 | 0.112742E+11 | 0.402496E+10 | 0.724924E+10 | 0.00 | 0.00 |
Minimum of Months | 59023964.46 | 0.414263E+09 | 0.348904E+09 | 0.129647E+09 | 0.216397E+09 | 0.00 | 0.00 |
Maximum of Months | 0.161736E+10 | 0.268700E+10 | 0.154230E+10 | 0.600339E+09 | 0.941956E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 95609060.31 | 0.218984E+10 | 0.640667E+09 | 0.258201E+09 | 0.382466E+09 | 0.00 | 0.00 |
February | 0.362953E+09 | 0.152916E+10 | 0.806020E+09 | 0.386770E+09 | 0.419250E+09 | 0.00 | 0.00 |
March | 0.128327E+10 | 0.950256E+09 | 0.145514E+10 | 0.694313E+09 | 0.760830E+09 | 0.00 | 0.00 |
April | 0.199938E+10 | 0.615991E+09 | 0.193177E+10 | 0.116695E+10 | 0.764815E+09 | 0.00 | 0.00 |
May | 0.272123E+10 | 0.478408E+09 | 0.241011E+10 | 0.136773E+10 | 0.104239E+10 | 0.00 | 0.00 |
June | 0.295155E+10 | 0.529819E+09 | 0.265633E+10 | 0.156935E+10 | 0.108697E+10 | 0.00 | 0.00 |
July | 0.296729E+10 | 0.678121E+09 | 0.276232E+10 | 0.171321E+10 | 0.104911E+10 | 0.00 | 0.00 |
August | 0.247755E+10 | 0.684962E+09 | 0.229244E+10 | 0.131488E+10 | 0.977559E+09 | 0.00 | 0.00 |
September | 0.167629E+10 | 0.883440E+09 | 0.170825E+10 | 0.991959E+09 | 0.716296E+09 | 0.00 | 0.00 |
October | 0.974078E+09 | 0.760641E+09 | 0.109619E+10 | 0.530927E+09 | 0.565268E+09 | 0.00 | 0.00 |
November | 0.326791E+09 | 0.114480E+10 | 0.622871E+09 | 0.215252E+09 | 0.407619E+09 | 0.00 | 0.00 |
December | 43712489.62 | 0.186309E+10 | 0.426009E+09 | 0.192067E+09 | 0.233943E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.178797E+11 | 0.123085E+11 | 0.188081E+11 | 0.104016E+11 | 0.840651E+10 | 0.00 | 0.00 |
Minimum of Months | 43712489.62 | 0.478408E+09 | 0.426009E+09 | 0.192067E+09 | 0.233943E+09 | 0.00 | 0.00 |
Maximum of Months | 0.296729E+10 | 0.218984E+10 | 0.276232E+10 | 0.171321E+10 | 0.108697E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.3 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.42 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.29 | 8.94 | 5.14 | 4.69 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.70 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.86 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 16.99 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.23 | 8.10 | 4.97 | 3.17 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.70 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.4 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.18 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.86 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.61 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.92 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.10 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.68 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.80 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.66 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.30 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.17 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.34 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.46 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.93 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.66 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.0 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.87 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.92 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.93 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.92 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.80 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.63 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.17 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.83 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.03 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.93 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.93 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.63 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.87 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.92 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.34 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.63 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.78 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.78 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.63 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.106536E+10 | -977156520.8 | 0.00 | 0.00 | 744.00 | 0.00 | -88200087.0 | 58.99 | 0.00 | 0.00 |
February | 0.995192E+09 | -915649417.9 | 0.00 | 0.00 | 672.00 | 0.00 | -79542738.3 | 58.99 | 0.00 | 0.00 |
March | 0.114670E+10 | -.105956E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87134803.6 | 58.99 | 0.00 | 0.00 |
April | 0.102855E+10 | -946409272.7 | 0.00 | 0.00 | 720.00 | 0.00 | -82135850.9 | 59.00 | 0.00 | 0.00 |
May | 0.100588E+10 | -926228251.4 | 0.00 | 0.00 | 744.00 | 0.00 | -79654931.0 | 58.99 | 0.00 | 0.00 |
June | 0.932284E+09 | -860518132.0 | 0.00 | 0.00 | 720.00 | 0.00 | -71765850.0 | 58.99 | 0.00 | 0.00 |
July | 0.856227E+09 | -784687001.1 | 0.00 | 0.00 | 744.00 | 0.00 | -71540019.8 | 59.00 | 0.00 | 0.00 |
August | 0.892951E+09 | -820486028.4 | 0.00 | 0.00 | 744.00 | 0.00 | -72465336.4 | 59.00 | 0.00 | 0.00 |
September | 0.846741E+09 | -773127559.8 | 0.00 | 0.00 | 720.00 | 0.00 | -73613029.8 | 58.99 | 0.00 | 0.00 |
October | 0.899335E+09 | -814225544.3 | 0.00 | 0.00 | 744.00 | 0.00 | -85108974.8 | 58.99 | 0.00 | 0.00 |
November | 0.920151E+09 | -835951969.9 | 0.00 | 0.00 | 720.00 | 0.00 | -84199167.8 | 58.99 | 0.00 | 0.00 |
December | 0.101729E+10 | -929159373.6 | 0.00 | 0.00 | 744.00 | 0.00 | -88128027.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.116067E+11 | -.106432E+11 | 8760.00 | -963488816.9 | 58.99 | |||||
Minimum of Months | 0.846741E+09 | -.105956E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -88200087.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.114670E+10 | -773127559.8 | 0.00 | 0.00 | 744.00 | 0.00 | -71540019.8 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 214.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 334.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 285.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 400.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 414.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 410.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 326.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 254.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3807.33 | ||||||||||
Minimum of Months | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.172839E+11 | 28148.66 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124786E+11 | 28148.66 | 01-FEB-00:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.928623E+10 | 28148.66 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.442175E+10 | 28148.66 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.763687E+09 | 28148.66 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 83719210.11 | 28148.66 | 05-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.478741E+09 | 28148.66 | 25-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.282692E+10 | 28148.66 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.756565E+10 | 28148.66 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133034E+11 | 28148.66 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.684926E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172839E+11 | 28148.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.992249E+11 | 87455.11 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.706294E+11 | 87455.11 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.455840E+11 | 87455.11 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178561E+11 | 87455.11 | 01-APR-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121667E+10 | 87455.11 | 01-MAY-20:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108720E+10 | 87455.11 | 30-SEP-03:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108391E+11 | 87455.11 | 08-OCT-02:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.459927E+11 | 87455.11 | 09-NOV-18:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.787349E+11 | 87455.11 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.371165E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.992249E+11 | 87455.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.289237E+12 | 266081.87 | 18-JAN-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.194222E+12 | 264592.04 | 01-FEB-20:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105044E+12 | 209557.33 | 06-MAR-08:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.222705E+11 | 115760.41 | 02-APR-23:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.463838E+09 | 21237.64 | 02-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.248890E+10 | 30776.93 | 24-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112086E+12 | 206874.41 | 25-NOV-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219655E+12 | 266081.87 | 08-DEC-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.945467E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.289237E+12 | 266081.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.301898E+09 | 0.218948E+09 | 8228.71 | 18-APR-12:00 | 5601.39 | 0.00 |
May | 0.00 | 0.00 | 0.641920E+09 | 0.489151E+09 | 9097.16 | 31-MAY-17:00 | 7452.34 | 0.00 |
June | 0.00 | 0.00 | 0.481827E+10 | 0.350960E+10 | 22851.98 | 26-JUN-05:01 | 10786.54 | 0.00 |
July | 0.00 | 0.00 | 0.733063E+10 | 0.507887E+10 | 22519.64 | 27-JUL-05:01 | 9907.76 | 0.00 |
August | 0.00 | 0.00 | 0.733779E+10 | 0.508040E+10 | 24644.13 | 04-AUG-05:01 | 9383.80 | 0.00 |
September | 0.00 | 0.00 | 0.269041E+10 | 0.230397E+10 | 20953.43 | 11-SEP-05:01 | 12681.69 | 0.00 |
October | 0.00 | 0.00 | 2608803.16 | 2608800.00 | 1058.84 | 20-OCT-15:00 | 1058.84 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.231235E+11 | 0.166836E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.733779E+10 | 0.508040E+10 | 24644.13 | 12681.69 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 41442606.22 | 25790239.04 | 6231.43 | 18-APR-15:10 | 3951.94 | 0.00 |
May | 0.00 | 0.00 | 0.389709E+09 | 0.288527E+09 | 15832.88 | 31-MAY-15:10 | 12465.83 | 0.00 |
June | 0.00 | 0.00 | 0.724167E+10 | 0.494882E+10 | 69004.60 | 26-JUN-20:14 | 38629.40 | 0.00 |
July | 0.00 | 0.00 | 0.106472E+11 | 0.671908E+10 | 72136.81 | 03-JUL-20:02 | 34728.43 | 0.00 |
August | 0.00 | 0.00 | 0.810289E+10 | 0.518844E+10 | 74280.72 | 03-AUG-19:22 | 32006.56 | 0.00 |
September | 0.00 | 0.00 | 0.312559E+10 | 0.253669E+10 | 65114.21 | 11-SEP-17:17 | 43725.91 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.295485E+11 | 0.197073E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.106472E+11 | 0.671908E+10 | 74280.72 | 43725.91 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.167069E+10 | 0.08 | 623.76 | 01-JAN-00:02 | 0.08 |
February | 0.147682E+10 | 0.08 | 623.76 | 01-FEB-00:02 | 0.08 |
March | 0.125716E+10 | 0.06 | 623.76 | 01-MAR-00:02 | 0.08 |
April | 0.477615E+09 | 0.02 | 623.76 | 01-APR-00:10 | 0.08 |
May | 22736158.84 | 0.00 | 623.76 | 01-MAY-21:00 | 0.08 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.157045E+09 | 0.01 | 623.76 | 15-OCT-21:30 | 0.08 |
November | 0.106794E+10 | 0.05 | 623.76 | 09-NOV-23:16 | 0.08 |
December | 0.166021E+10 | 0.08 | 623.76 | 01-DEC-00:02 | 0.08 |
Annual Sum or Average | 0.779022E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.167069E+10 | 0.08 | 623.76 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139454E+10 | 0.79 | 1176.47 | 09-JAN-11:10 | 0.98 |
February | 0.122210E+10 | 0.70 | 1176.47 | 24-FEB-14:00 | 0.98 |
March | 0.135107E+10 | 0.58 | 1176.47 | 18-MAR-12:20 | 0.98 |
April | 0.120168E+10 | 0.44 | 1176.47 | 07-APR-09:50 | 0.98 |
May | 0.122166E+10 | 0.39 | 1176.47 | 04-MAY-16:20 | 0.97 |
June | 0.122359E+10 | 0.39 | 1176.47 | 10-JUN-15:50 | 0.97 |
July | 0.118990E+10 | 0.37 | 1176.47 | 10-JUL-09:30 | 0.97 |
August | 0.127884E+10 | 0.40 | 1176.47 | 05-AUG-11:00 | 0.97 |
September | 0.117551E+10 | 0.38 | 1176.47 | 25-SEP-16:20 | 0.98 |
October | 0.119087E+10 | 0.39 | 1176.47 | 13-OCT-13:40 | 0.98 |
November | 0.120669E+10 | 0.55 | 1176.47 | 06-NOV-09:40 | 0.97 |
December | 0.132385E+10 | 0.71 | 1176.47 | 07-DEC-11:40 | 0.99 |
Annual Sum or Average | 0.149803E+11 | 0.51 | |||
Minimum of Months | 0.117551E+10 | 0.37 | 1176.47 | 0.97 | |
Maximum of Months | 0.139454E+10 | 0.79 | 1176.47 | 0.99 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.446507E+10 | 0.84 | 2597.97 | 02-JAN-07:30 | 0.94 |
February | 0.375544E+10 | 0.84 | 2597.97 | 01-FEB-08:15 | 0.95 |
March | 0.374842E+10 | 0.79 | 2597.97 | 16-MAR-12:20 | 0.95 |
April | 0.299751E+10 | 0.64 | 2597.97 | 01-APR-06:10 | 0.94 |
May | 0.270846E+10 | 0.39 | 2597.97 | 01-MAY-06:20 | 0.94 |
June | 0.274724E+10 | 0.40 | 2597.97 | 09-JUN-10:40 | 0.93 |
July | 0.265245E+10 | 0.37 | 2597.97 | 21-JUL-11:40 | 0.93 |
August | 0.279638E+10 | 0.38 | 2597.97 | 01-AUG-08:40 | 0.92 |
September | 0.260679E+10 | 0.39 | 2597.97 | 01-SEP-10:00 | 0.93 |
October | 0.288181E+10 | 0.63 | 2597.97 | 04-OCT-06:05 | 0.94 |
November | 0.347215E+10 | 0.74 | 2597.97 | 22-NOV-12:00 | 0.95 |
December | 0.412379E+10 | 0.84 | 2597.97 | 29-DEC-13:50 | 0.94 |
Annual Sum or Average | 0.389555E+11 | 0.60 | |||
Minimum of Months | 0.260679E+10 | 0.37 | 2597.97 | 0.92 | |
Maximum of Months | 0.446507E+10 | 0.84 | 2597.97 | 0.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.65 | 0.04 |
February | 3.14 | 0.37 |
March | 3.52 | 0.01 |
April | 1.59 | 0.42 |
May | 1.32 | 1.05 |
June | 2.75 | 0.84 |
July | 4.34 | 0.36 |
August | 4.02 | 0.29 |
September | 1.47 | 1.33 |
October | 1.22 | 0.35 |
November | 2.89 | 0.05 |
December | 3.36 | 0.00 |
Annual Sum or Average | 32.27 | 0.34 |
Minimum of Months | 1.22 | 0.00 |
Maximum of Months | 4.34 | 1.33 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 3.28 | 0.00 |
February | 1.65 | 0.00 |
March | 0.02 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.39 | 0.00 |
July | 2.51 | 0.00 |
August | 0.47 | 0.00 |
September | 0.18 | 0.00 |
October | 0.00 | 0.00 |
November | 0.08 | 0.00 |
December | 1.90 | 0.00 |
Annual Sum or Average | 10.49 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.28 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.03 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.03 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.03 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.139454E+10 | 0.240216E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.122210E+10 | 0.175273E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.135107E+10 | 0.133173E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.128568E+10 | 0.643140E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.139825E+10 | 0.111749E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.250276E+10 | 0.125252E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.309572E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.320492E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.191161E+10 | 0.706103E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.119159E+10 | 0.414067E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.120669E+10 | 0.108224E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.132385E+10 | 0.187858E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.210888E+11 | 0.969953E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.119159E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.320492E+10 | 0.240216E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.446507E+10 | 0.134027E+12 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.375544E+10 | 0.967072E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.374842E+10 | 0.643643E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.301000E+10 | 0.256663E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.282776E+10 | 0.176612E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.488370E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.565544E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.512303E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.355589E+10 | 0.159723E+10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.288181E+10 | 0.157888E+11 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.347215E+10 | 0.639951E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.412379E+10 | 0.108312E+12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.475025E+11 | 0.512224E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.282776E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.565544E+10 | 0.134027E+12 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.139454E+10 | 0.00 | 0.172839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122210E+10 | 0.00 | 0.124786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135107E+10 | 0.00 | 0.928623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120168E+10 | 0.301898E+09 | 0.442175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122166E+10 | 0.641920E+09 | 0.763687E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122359E+10 | 0.481827E+10 | 83719210.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118990E+10 | 0.733063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127884E+10 | 0.733779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.117551E+10 | 0.269041E+10 | 0.478741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119087E+10 | 2608803.16 | 0.282692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120669E+10 | 0.00 | 0.756565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132385E+10 | 0.00 | 0.133034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149803E+11 | 0.231235E+11 | 0.684926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139454E+10 | 0.733779E+10 | 0.172839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.446507E+10 | 0.00 | 0.992249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.375544E+10 | 0.00 | 0.706294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.374842E+10 | 0.00 | 0.455840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.299751E+10 | 41442606.22 | 0.178561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.270846E+10 | 0.389709E+09 | 0.121667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.274724E+10 | 0.724167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.265245E+10 | 0.106472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.279638E+10 | 0.810289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.260679E+10 | 0.312559E+10 | 0.108720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.288181E+10 | 0.00 | 0.108391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.347215E+10 | 0.00 | 0.459927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.412379E+10 | 0.00 | 0.787349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389555E+11 | 0.295485E+11 | 0.371165E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.260679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.446507E+10 | 0.106472E+11 | 0.992249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.139454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120168E+10 | 0.00 | 0.00 | 0.00 | 83998227.92 | 0.00 | 0.643140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122166E+10 | 0.00 | 0.00 | 0.00 | 0.176596E+09 | 0.00 | 0.111749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122359E+10 | 0.00 | 0.00 | 0.00 | 0.127918E+10 | 0.00 | 0.125252E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118990E+10 | 0.00 | 0.00 | 0.00 | 0.190582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127884E+10 | 0.00 | 0.00 | 0.00 | 0.192607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.117551E+10 | 0.00 | 0.00 | 0.00 | 0.736093E+09 | 0.00 | 0.706103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119087E+10 | 0.00 | 0.00 | 0.00 | 722103.57 | 0.00 | 0.414067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149803E+11 | 0.00 | 0.00 | 0.00 | 0.610848E+10 | 0.00 | 0.969953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.117551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139454E+10 | 0.00 | 0.00 | 0.00 | 0.192607E+10 | 0.00 | 0.240216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.446507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134027E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.375544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.967072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.374842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.299751E+10 | 0.00 | 0.00 | 0.00 | 12488222.74 | 0.00 | 0.256663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.270846E+10 | 0.00 | 0.00 | 0.00 | 0.119299E+09 | 0.00 | 0.176612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.274724E+10 | 0.00 | 0.00 | 0.00 | 0.213646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.265245E+10 | 0.00 | 0.00 | 0.00 | 0.300299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.279638E+10 | 0.00 | 0.00 | 0.00 | 0.232665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.260679E+10 | 0.00 | 0.00 | 0.00 | 0.949104E+09 | 0.00 | 0.159723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.288181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.347215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.412379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108312E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389555E+11 | 0.00 | 0.00 | 0.00 | 0.854699E+10 | 0.00 | 0.512224E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.260679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.446507E+10 | 0.00 | 0.00 | 0.00 | 0.300299E+10 | 0.00 | 0.134027E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365920E+10 | 0.00 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283016E+10 | 0.00 | 0.00 | 0.13 |
March | 21027078.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225369E+10 | 0.00 | 0.00 | 0.13 |
April | 0.181009E+09 | 47579518.62 | 0.00 | 77738.30 | 6476066.50 | 0.130889E+10 | 94323516.32 | 0.00 | 0.15 |
May | 0.469779E+09 | 60424757.08 | 0.00 | 503166.26 | 699315.87 | 0.140484E+09 | 0.548931E+09 | 0.00 | 0.26 |
June | 0.159606E+09 | 0.664256E+09 | 0.00 | 3452940.05 | 0.00 | 8784206.32 | 0.110634E+10 | 0.00 | 0.49 |
July | 10389321.34 | 0.974958E+09 | 0.00 | 5713099.48 | 596046.03 | 0.00 | 0.960178E+09 | 0.00 | 0.57 |
August | 9254241.45 | 0.104264E+10 | 0.00 | 4201756.34 | 24276.13 | 0.00 | 0.102975E+10 | 0.00 | 0.62 |
September | 0.265921E+09 | 0.206710E+09 | 0.00 | 2573903.29 | 0.00 | 0.152033E+09 | 0.114393E+10 | 0.00 | 0.38 |
October | 0.324791E+09 | 0.00 | 0.00 | 5298.78 | 0.00 | 0.990100E+09 | 16149827.37 | 0.00 | 0.13 |
November | 0.156036E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188005E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303852E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.159781E+10 | 0.299657E+10 | 0.00 | 16527902.49 | 7795704.52 | 0.162619E+11 | 0.489959E+10 | 0.00 | 0.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.469779E+09 | 0.104264E+10 | 0.00 | 5713099.48 | 6476066.50 | 0.365920E+10 | 0.114393E+10 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 11398180.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123725E+11 | 0.00 | 0.00 | 0.17 |
February | 0.176169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.902385E+10 | 0.00 | 0.00 | 0.18 |
March | 0.827615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578086E+10 | 0.00 | 0.00 | 0.19 |
April | 0.183897E+10 | 3351453.29 | 0.00 | 0.00 | 78003814.01 | 0.235095E+10 | 0.00 | 0.00 | 0.18 |
May | 0.203417E+10 | 60105077.58 | 0.00 | 6696.42 | 25605256.41 | 63349681.22 | 1166607.74 | 0.00 | 0.19 |
June | 0.139227E+10 | 0.935994E+09 | 0.00 | 1457864.03 | 5073904.70 | 0.00 | 0.990022E+09 | 0.00 | 0.32 |
July | 0.587491E+09 | 0.183303E+10 | 0.00 | 4094536.96 | 0.00 | 0.00 | 0.174534E+10 | 0.00 | 0.46 |
August | 0.774875E+09 | 0.133273E+10 | 0.00 | 2575740.06 | 2910775.62 | 0.00 | 0.153612E+10 | 0.00 | 0.40 |
September | 0.203477E+10 | 0.400637E+09 | 0.00 | 881237.16 | 727106.81 | 84678105.88 | 0.461112E+09 | 0.00 | 0.24 |
October | 0.257257E+10 | 0.00 | 0.00 | 0.00 | 7202651.14 | 0.659957E+09 | 0.00 | 0.00 | 0.17 |
November | 0.950525E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503732E+10 | 0.00 | 0.00 | 0.17 |
December | 27706691.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976752E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.132285E+11 | 0.456585E+10 | 0.00 | 9016074.63 | 0.119524E+09 | 0.451410E+11 | 0.473376E+10 | 0.00 | 0.24 |
Minimum of Months | 11398180.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.257257E+10 | 0.183303E+10 | 0.00 | 4094536.96 | 78003814.01 | 0.123725E+11 | 0.174534E+10 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |