Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2020-06-03 19:11:52
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1001.06 | 207.04 | 207.04 |
Net Site Energy | 1001.06 | 207.04 | 207.04 |
Total Source Energy | 2720.09 | 562.57 | 562.57 |
Net Source Energy | 2720.09 | 562.57 | 562.57 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 216.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 98.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 41.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.79 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 784.89 | 216.17 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 216.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 3.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 98.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 41.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25.79 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 118.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 14.58 | 44.71 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 162.33 | 44.71 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 118.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 14.58 | 44.71 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 162.33 | 44.71 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 784.894 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 784.894 | 100.00 |
Total On-Site and Utility Electric Sources | 784.894 | 100.00 |
Total Electricity End Uses | 784.894 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 49.17 |
Time Setpoint Not Met During Occupied Cooling | 1.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1811.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.6337 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.5069 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.5069 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-14:00 | 19-FEB-06:49 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 137688.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 8565.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3159.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1756.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 58783.16 | 137688.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 137688.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 8565.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 3159.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1756.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 234.33 | 0.00 | 0.00 | 0.00 |
Cooling | 11.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1507.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 313.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 130.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 81.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2485.76 | 234.33 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 48.46 | 0.00 | 0.00 | 0.00 |
Cooling | 2.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 64.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 514.10 | 48.46 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 48.46 | 0.00 | 0.00 | 0.00 |
Cooling | 2.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 64.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 514.10 | 48.46 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.958617 |
ZONE2 FINE STORAGE DIRECT AIR | 1.89 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 2.03 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 2.03 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 83218.51 |
PSZ-OFFICE HEATING COIL | 24748.25 |
PSZ-FINE STORAGE HEATING COIL | 65072.56 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 83218.51 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.958617 | 0.958617 | 0.958617 | 0.958617 | 0.958617 | 0.958617 | 1.00 | 1.000000 | 0.958617 |
PSZ-FINE STORAGE | 1.89 | 1.89 | 1.89 | 1.89 | 1.89 | 1.89 | 1.00 | 1.00 | 1.89 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 0.958617 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 1.89 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.958617 | 0.958617 | 0.958617 | 0.958617 | 15868.52 | 24748.25 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 1.89 | 1.89 | 1.89 | 1.89 | 37731.14 | 65072.56 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.958620 | 0.479310 | 0.958620 | 15868.56 | 15868.52 | 7934.26 | 15868.52 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 1.89 | 0.944260 | 1.89 | 35735.54 | 37731.14 | 18865.57 | 37731.14 | 0.735617 | 0.735620 | 0.735620 | 0.735620 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.958617 | 1092.93 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.89 | 2067.00 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.634 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.707 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.507 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.507 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.507 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.066 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2518.900 | 10.634 | 503.780 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2518.900 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11853.648 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11853.648 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27263.390 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27263.390 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3263 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3263 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.4128 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.4128 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.4128 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.065 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.065 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.323 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.323 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.323 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.38866262E-07 | 0.77198350E-12 | 0.86409618E-13 | 0.0000000 |
2 | 1 | -5.2160226 | 0.42725752E-04 | -0.49098391E-04 | 0.74579932E-08 |
3 | 0 | 5.5423254 | 0.32626013 | 0.32635195 | |
4 | 2 | 0.38866262E-07 | 0.77198350E-12 | 0.86409618E-13 | 0.0000000 |
5 | 1 | -5.2160226 | 0.42725752E-04 | -0.49098391E-04 | 0.74579932E-08 |
6 | 0 | 5.5423254 | 0.32626013 | 0.32635195 | |
7 | 4 | 0.79581057E-12 | 0.97316148E-16 | -0.20714918E-14 | 0.11395926E-15 |
8 | 3 | -0.38950733E-03 | 0.29153728E-06 | -0.56547345E-04 | 0.15269480E-12 |
9 | 2 | 1.7508611 | 0.63413892E-02 | 1.1490629 | -0.74675203E-04 |
10 | 1 | -7.1137977 | 0.16376069 | -17.153076 | 0.33557628 |
11 | 0 | 5.6376123 | 0.10418388 | 16.278356 | |
12 | 4 | 0.79581057E-12 | 0.97316148E-16 | -0.20714918E-14 | 0.11395926E-15 |
13 | 3 | -0.38950733E-03 | 0.29153728E-06 | -0.56547345E-04 | 0.15269480E-12 |
14 | 2 | 1.7508611 | 0.63413892E-02 | 1.1490629 | -0.74675203E-04 |
15 | 1 | -7.1137977 | 0.16376069 | -17.153076 | 0.33557628 |
16 | 0 | 5.6376123 | 0.10418388 | 16.278356 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.8391346 | 2.8391346 | 2.8391346 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8391346 | 2.8391346 | 2.8391346 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.20714918E-14 | 0.97316148E-16 | 0.79581057E-12 | 0.11395926E-15 |
85 | 3 | -0.56547345E-04 | 0.29153728E-06 | -0.38950733E-03 | 0.15269480E-12 |
86 | 2 | 1.1490629 | 0.63413892E-02 | 1.7508611 | -0.74675203E-04 |
87 | 1 | -17.153076 | 0.16376069 | -7.1137977 | 0.33557628 |
88 | 0 | 16.278356 | 0.10418388 | 5.6376123 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.52_SHGC_0.4 | 28 | 1 | VerySmooth | 2.956 | 0.395 | 0.315 | 0.401 |
2 | SKYLIGHT_U_0.6_SHGC_0.4 | 29 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 30 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.66926E-002 | 0.31435 | 0.46310 | 0.46310 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 9.92378E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9571.99475 | 11486.39370 | 0.79885 | 0.95862 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.79438E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 9260.03339 | 11112.04007 | 0.26359 | 0.31630 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -4.20000 | 2.69032E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 24191.32140 | 29029.58568 | 1.57377 | 1.88852 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.79438E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 33466.84650 | 40160.21580 | 0.80270 | 0.96324 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40000 | 8.79438E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 69348.75720 | 83218.50864 | 1.69380 | 2.03256 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | -4.20000 | 2.69032E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 14099.31 | 0.95862 | 0.95862 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 10229.93 | 0.31630 | 0.31630 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 34479.74 | 1.88852 | 1.88852 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 38093.17 | 0.96324 | 0.96324 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.95862 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.88852 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.03256 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 2.03256 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 83218.51141 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 83218.50864 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.95862 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.95862 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.95862 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.95862 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.95862 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.95862 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.88852 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.88852 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.88852 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.88852 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.88852 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.88852 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.95862 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.88852 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.95862 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.95862 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.95862 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.95862 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.95862 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.95862 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47931 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.95862 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 15868.56481 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 15868.52000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 7934.26000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 15868.52000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15868.52000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24748.25017 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.95862 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1092.92910 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 24748.25017 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.88852 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.88852 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.88852 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.88852 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.88852 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.88852 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.94426 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.88852 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 35735.54350 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 37731.14000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 18865.57000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 37731.14000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73562 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73562 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73562 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73562 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 37731.14000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 65072.55637 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.88852 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2066.99570 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 65072.55637 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 15124.7 | 11.07 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 36264.7 | 14.69 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 14 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1466123464 | 0.1750907610 | Pass | Pass | 9.2874425000E-002 | 0.3592025948 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.4643438832 | 0.4291073726 | Pass | Pass | 0.3851818434 | 0.6240527876 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.6319878850E-005 | 2.3610634882E-005 | Pass | Pass | 7.1606269259E-002 | 9.1806711131E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.312 | 0.326 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.389 | 0.413 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.389 | 0.413 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.389 | 0.413 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.312 | 0.326 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.52_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.956 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.52_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.956 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.52_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.956 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.52_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.956 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.164 | 0.395 | 0.401 | ||||||||||||
North Total or Average | 6.51 | 2.956 | 0.395 | 0.401 | ||||||||||||
Non-North Total or Average | 26.02 | 3.216 | 0.395 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.6337 | 236.88 | 2518.90 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.62 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.5069 | 1393.41 | 11853.65 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 135.00 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.5069 | 3204.84 | 27263.39 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 310.50 |
Interior Lighting Total | 8.6111 | 4835.13 | 41635.94 | 476.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 6311.00 | AstronomicalClock | - | 83.55 | 83.55 | 98.97 | |
Exterior Lighting Total | 6311.00 | 98.97 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15868.52 | 12673.55 | 3194.97 | 0.80 | 3.91 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 37731.14 | 27755.78 | 9975.36 | 0.74 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 15124.7 | 11.07 | ||||
PSZ-FINE STORAGE COOLING COIL | 36264.7 | 14.69 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 83218.51 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 24748.25 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 65072.56 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.03 | 188.85 | 92.91 | 1.00 | 3.57 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 0.96 | 1092.93 | 1140.11 | 1.00 | 1.37 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 1.89 | 2067.00 | 1094.51 | 1.00 | 1.29 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9571.99 | 11486.39 | 48.49 | 0.799 | 0.959 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23.90 | 23.90 | 0.00815 | 27.94 | 0.00879 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 24191.32 | 29029.59 | 20.83 | 1.574 | 1.889 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.70 | 26.70 | 0.00811 | 29.40 | 0.00879 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00383 | 29.40 | 0.00879 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9260.03 | 11112.04 | 46.91 | 0.264 | 0.316 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00727 | -4.20 | 0.00269 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 33466.85 | 40160.22 | 28.82 | 0.803 | 0.963 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15.56 | 15.55 | 0.00557 | -4.20 | 0.00269 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 69348.76 | 83218.51 | 25.97 | 1.694 | 2.033 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 10.00 | 9.99 | 0.00774 | -4.20 | 0.00269 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.96 | 0.96 | 0.32 | 0.32 | 0.9586 | 0.9586 | 0.9586 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.89 | 1.89 | 0.96 | 0.96 | 1.8885 | 1.8885 | 1.8885 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 83218.511 | 83218.511 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 83218.51 | 83218.51 | 2.032557 | 3.17 | 3.17 | 0.00531301 | 43.33 | 26.92 | 0.01600000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 9.99 | 0.00773974 | 99.9999 | 83218.51 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 15868.520 | 0.000 | 0.958620 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 15868.52 | 15262.12 | 0.958620 | 24.33 | 16.10 | 0.00822037 | 12.00 | 11.13 | 0.00800000 | 27.94 | 0.00879438 | 17.82 | 10.6700 | 23.90 | 0.00815181 | 43.5421 | 9571.99 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 24748.250 | 24748.250 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 24748.25 | 24748.25 | 0.958617 | 12.88 | 9.16 | 0.00579208 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 10.6700 | 21.10 | 0.00727449 | 46.1324 | 9260.03 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 37731.140 | 0.000 | 1.888520 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 37731.14 | 36323.86 | 1.888520 | 27.31 | 17.17 | 0.00826049 | 12.00 | 11.13 | 0.00800000 | 29.40 | 0.00879438 | 18.30 | 22.4892 | 26.70 | 0.00810559 | 36.6552 | 24191.32 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 65072.556 | 65072.556 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 65072.56 | 65072.56 | 1.888520 | 6.84 | 4.45 | 0.00430097 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 22.4892 | 15.55 | 0.00557122 | 50.1745 | 33466.85 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 83218.511 | 83218.511 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1870 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 2.032557 | 2.41262654 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 83218.51 | 83218.51 | 1.0000 | 2.41262654 | 2.032557 | 3.17 | 3.17 | 0.00531301 | 16506.3 | 43.33 | 26.92 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 83218.51 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 9.99 | 0.00773974 | 9.99 | 0.00773974 | 99.9999 | 83218.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15868.520 | 0.000 | 0.958620 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1213 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 15868.52 | 15262.12 | 1.0000 | 1.13787310 | 0.958620 | 24.33 | 16.10 | 0.00822037 | 45379.3 | 12.00 | 11.13 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15868.52 | 27.94 | 0.00879438 | 17.82 | 0.10228487 | 10.6700 | 23.90 | 0.00815181 | 23.90 | 0.00815181 | 43.5421 | 9571.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24748.250 | 24748.250 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.958617 | 1.13786993 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 24748.25 | 24748.25 | 1.0000 | 1.13786993 | 0.958617 | 12.88 | 9.16 | 0.00579208 | 27571.3 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24748.25 | -4.20 | 0.00269032 | -4.20 | 0.10228487 | 10.6700 | 21.05 | 0.00727449 | 21.10 | 0.00727449 | 46.1324 | 9260.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 37731.140 | 0.000 | 1.888520 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1958 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 37731.14 | 36323.86 | 1.0000 | 2.24165583 | 1.888520 | 27.31 | 17.17 | 0.00826049 | 48517.5 | 12.00 | 11.13 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37731.14 | 29.40 | 0.00879438 | 18.30 | 0.42471267 | 22.4892 | 26.70 | 0.00810559 | 26.70 | 0.00810559 | 36.6552 | 24191.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 65072.556 | 65072.556 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.888520 | 2.24165603 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 65072.56 | 65072.56 | 1.0000 | 2.24165603 | 1.888520 | 6.84 | 4.45 | 0.00430097 | 17688.4 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 65072.56 | -4.20 | 0.00269032 | -4.20 | 0.42471267 | 22.4892 | 15.55 | 0.00557122 | 15.55 | 0.00557122 | 50.1745 | 33466.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE OA CONTROLLER | DifferentialDryBulb | 0.10 | 0.96 | - | |||
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 1.89 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2115.67 | 2992.83 | 1811.83 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2115.67 | 2992.83 | 1811.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 52.83 | 1.17 | 49.17 | 1.17 |
ZONE2 FINE STORAGE | 321.00 | 0.67 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 362.50 | 1.83 | 49.17 | 1.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.673 | 0.396 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 784.89 | 5421.86 | 22-JAN-12:00 | 58783.16 | 10-AUG-15:00 |
Electricity:Building | 615.41 | 4938.86 | 01-JAN-00:10 | 45301.66 | 02-JAN-09:10 |
Electricity:Zone:ZONE1 OFFICE | 62.57 | 1027.15 | 01-JAN-00:10 | 3852.05 | 02-JAN-08:10 |
InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.62 | 453.40 | 01-JAN-00:10 | 1939.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 417.84 | 2726.34 | 01-JAN-00:10 | 31374.00 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 310.51 | 2726.34 | 01-JAN-00:10 | 23173.88 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 25.79 | 483.00 | 11-MAR-06:10 | 2336.99 | 10-FEB-12:20 |
WaterSystems:Electricity | 25.79 | 483.00 | 11-MAR-06:10 | 2336.99 | 10-FEB-12:20 |
Water Heater:WaterSystems:Electricity | 25.79 | 483.00 | 11-MAR-06:10 | 2336.99 | 10-FEB-12:20 |
Fans:Electricity | 41.06 | 0.00 | 02-JAN-18:40 | 3348.77 | 13-JAN-08:40 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 784.89 | 5421.86 | 22-JAN-12:00 | 58783.16 | 10-AUG-15:00 |
ElectricityPurchased:Plant | 784.89 | 5421.86 | 22-JAN-12:00 | 58783.16 | 10-AUG-15:00 |
Cogeneration:ElectricityPurchased | 784.89 | 5421.86 | 22-JAN-12:00 | 58783.16 | 10-AUG-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 784.89 | 5421.86 | 22-JAN-12:00 | 58783.16 | 10-AUG-15:00 |
ElectricityNet:Plant | 784.89 | 5421.86 | 22-JAN-12:00 | 58783.16 | 10-AUG-15:00 |
Cogeneration:ElectricityNet | 784.89 | 5421.86 | 22-JAN-12:00 | 58783.16 | 10-AUG-15:00 |
Electricity:HVAC | 44.72 | 0.00 | 02-JAN-18:40 | 11909.60 | 10-AUG-15:10 |
General:Fans:Electricity | 41.06 | 0.00 | 02-JAN-18:40 | 3348.77 | 13-JAN-08:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 3.66 | 0.00 | 01-JAN-00:10 | 8749.67 | 10-AUG-15:10 |
ExteriorLights:Electricity | 98.97 | 0.00 | 01-JAN-08:10 | 6311.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 98.97 | 0.00 | 01-JAN-08:10 | 6311.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 216.17 | 0.00 | 02-JAN-18:40 | 137688.75 | 19-FEB-06:50 |
Gas:HVAC | 216.17 | 0.00 | 02-JAN-18:40 | 137688.75 | 19-FEB-06:50 |
Heating:Gas | 216.17 | 0.00 | 02-JAN-18:40 | 137688.75 | 19-FEB-06:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 356.75 | 0.00 | 02-JAN-18:40 | 217805.35 | 19-FEB-06:50 |
EnergyTransfer:Building | 185.39 | 0.00 | 02-JAN-18:40 | 109411.69 | 19-FEB-06:50 |
EnergyTransfer:Zone:ZONE1 OFFICE | 36.76 | 0.00 | 01-JAN-00:40 | 17526.91 | 17-JAN-06:10 |
Heating:EnergyTransfer | 154.13 | 0.00 | 02-JAN-18:40 | 109411.69 | 19-FEB-06:50 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 24.23 | 0.00 | 01-JAN-00:40 | 17526.91 | 17-JAN-06:10 |
Cooling:EnergyTransfer | 31.26 | 0.00 | 01-JAN-00:10 | 24206.33 | 10-AUG-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 12.52 | 0.00 | 01-JAN-00:10 | 9128.98 | 10-AUG-17:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 92.65 | 0.00 | 01-JAN-00:40 | 41877.58 | 19-FEB-06:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 73.91 | 0.00 | 01-JAN-00:40 | 41877.58 | 19-FEB-06:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 18.74 | 0.00 | 01-JAN-00:10 | 16669.53 | 10-AUG-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 55.99 | 0.00 | 02-JAN-08:10 | 65284.50 | 19-FEB-07:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 55.99 | 0.00 | 02-JAN-08:10 | 65284.50 | 19-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 171.35 | 0.00 | 02-JAN-18:40 | 108393.66 | 19-FEB-06:50 |
HeatingCoils:EnergyTransfer | 156.93 | 0.00 | 02-JAN-18:40 | 108393.66 | 19-FEB-06:50 |
CoolingCoils:EnergyTransfer | 14.42 | 0.00 | 01-JAN-00:10 | 32254.40 | 10-AUG-15:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 24.232 | -12.525 | 0.000 | 0.000 | 3.946 | 30.619 | 31.946 | 8.139 | 0.000 | 0.209 | 0.000 | 0.000 | -8.914 | 0.000 | -23.363 | -54.289 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 73.914 | -18.736 | 0.000 | 0.000 | 0.000 | 135.003 | 0.000 | 0.000 | 0.000 | 0.350 | 0.003 | 0.000 | 0.000 | 0.000 | -119.263 | -71.269 |
ZONE3 BULK STORAGE | 55.986 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 310.507 | 107.336 | 16.719 | 0.000 | 3.798 | 0.000 | 0.000 | -7.790 | 0.000 | -378.532 | -108.025 |
Total Facility | 55.986 | 0.000 | 98.146 | -31.260 | 0.000 | 0.000 | 3.946 | 476.129 | 139.282 | 24.858 | 0.000 | 4.358 | 0.003 | 0.000 | -16.704 | 0.000 | -521.158 | -233.583 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 15-AUG-05:02 | 0.00 | 0.00 | 0.00 | -19099.63 | 0.00 | 0.00 | 34.18 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 19220.06 | 0.00 | -531.43 | 0.00 | -776.28 | 0.00 |
ZONE2 FINE STORAGE | 23-JUL-17:11 | 0.00 | 0.00 | 0.00 | -35443.88 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 34474.16 | 0.00 | -0.00 | 0.00 | -215.64 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 23-JUL-17:11 | 0.00 | 0.00 | 0.00 | -35443.88 | 0.00 | 0.00 | 0.00 | 4365.11 | 573.75 | 4092.17 | 0.00 | 538.60 | 26189.19 | 0.00 | 0.00 | 0.00 | -314.94 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 14-FEB-06:32 | 0.00 | 0.00 | 26249.23 | 0.00 | 0.00 | 0.00 | 53.60 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -724.07 | 0.00 | -1567.47 | -25164.40 |
ZONE2 FINE STORAGE | 19-FEB-07:22 | 0.00 | 0.00 | 68131.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -14799.06 | -54517.48 |
ZONE3 BULK STORAGE | 19-FEB-06:55 | 65284.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -794.59 | 0.00 | -48130.32 | -19085.76 |
Total Facility | 19-FEB-06:42 | 64814.65 | 0.00 | 81713.48 | 0.00 | 0.00 | 0.00 | 0.00 | 4365.11 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1683.45 | 0.00 | -63086.34 | -86697.21 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9586 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.9586 | 0.1067 | 1.0000 | 0.1023 | 0.1067 | ||
PSZ-FINE STORAGE | 1.8885 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.8885 | 0.2249 | 1.0000 | 0.4247 | 0.2249 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9586 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.9586 | 1.0000 | 1.0000 | 0.1023 | 0.1067 | ||
PSZ-FINE STORAGE | 1.8885 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.8885 | 1.0000 | 1.0000 | 0.4247 | 0.2249 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.9586 | 0.9586 | 0.9586 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.8885 | 1.8885 | 1.8885 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9586 | 0.9586 | 0.9586 | 0.9586 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.8885 | 1.8885 | 1.8885 | 1.8885 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.9586 | 0.9586 | 0.9586 | 0.1023 | 0.3234 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.8885 | 1.8885 | 1.8885 | 0.4247 | 0.4409 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9586 | 0.9586 | 0.9586 | 0.9586 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.8885 | 1.8885 | 1.8885 | 1.8885 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:52
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 49.17 |
Number of hours cooling loads not met | 1.17 |
Number of hours not met | 50.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 216.17 | 137688.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 3.66 | 8749.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 476.13 | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 98.97 | 6311.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 41.06 | 3348.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 25.79 | 2336.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 784.89 |
Natural Gas | 0.00 | 216.17 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1001.06 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 98.47 |
Space Heating | 0.00 |
Space Cooling | 0.76 |
Fans (All) | 8.49 |
Service Water Heating | 5.33 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 162.33 |
Subtotal | 162.33 |
Natural Gas [MJ/m2] | |
Space Heating | 44.71 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 44.71 |
Subtotal | 44.71 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 47.56 |
Space Heating | 21.59 |
Space Cooling | 0.37 |
Fans (All) | 4.10 |
Service Water Heating | 2.58 |
Receptacle Equipment | 13.91 |
Miscellaneous | 9.89 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.715781E+11 |
February | 0.000 | 0.521303E+11 |
March | 0.000 | 0.155665E+11 |
April | 0.000 | 0.606411E+10 |
May | 0.000 | 0.585692E+09 |
June | 0.000 | 0.114811E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.490332E+08 |
October | 0.000 | 0.326303E+10 |
November | 0.000 | 0.188945E+11 |
December | 0.000 | 0.479216E+11 |
Annual Sum or Average | 0.216168E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.715781E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.715781E+11 |
February | 0.000 | 0.521303E+11 |
March | 0.000 | 0.155665E+11 |
April | 0.000 | 0.606411E+10 |
May | 0.000 | 0.585692E+09 |
June | 0.000 | 0.114811E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.490332E+08 |
October | 0.000 | 0.326303E+10 |
November | 0.000 | 0.188945E+11 |
December | 0.000 | 0.479216E+11 |
Annual Sum or Average | 0.216168E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.715781E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Meter
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.715781E+11 |
February | 0.000 | 0.521303E+11 |
March | 0.000 | 0.155665E+11 |
April | 0.000 | 0.606411E+10 |
May | 0.000 | 0.585692E+09 |
June | 0.000 | 0.114811E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.490332E+08 |
October | 0.000 | 0.326303E+10 |
November | 0.000 | 0.188945E+11 |
December | 0.000 | 0.479216E+11 |
Annual Sum or Average | 0.216168E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.715781E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.715781E+11 |
February | 0.000 | 0.521303E+11 |
March | 0.000 | 0.155665E+11 |
April | 0.000 | 0.606411E+10 |
May | 0.000 | 0.585692E+09 |
June | 0.000 | 0.114811E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.490332E+08 |
October | 0.000 | 0.326303E+10 |
November | 0.000 | 0.188945E+11 |
December | 0.000 | 0.479216E+11 |
Annual Sum or Average | 0.216168E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.715781E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.715781E+11 |
February | 0.000 | 0.521303E+11 |
March | 0.000 | 0.155665E+11 |
April | 0.000 | 0.606411E+10 |
May | 0.000 | 0.585692E+09 |
June | 0.000 | 0.114811E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.490332E+08 |
October | 0.000 | 0.326303E+10 |
November | 0.000 | 0.188945E+11 |
December | 0.000 | 0.479216E+11 |
Annual Sum or Average | 0.216168E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.715781E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.715781E+11 |
February | 0.000 | 0.521303E+11 |
March | 0.000 | 0.155665E+11 |
April | 0.000 | 0.606411E+10 |
May | 0.000 | 0.585692E+09 |
June | 0.000 | 0.114811E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.490332E+08 |
October | 0.000 | 0.326303E+10 |
November | 0.000 | 0.188945E+11 |
December | 0.000 | 0.479216E+11 |
Annual Sum or Average | 0.216168E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.715781E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.715781E+11 |
February | 0.000 | 0.521303E+11 |
March | 0.000 | 0.155665E+11 |
April | 0.000 | 0.606411E+10 |
May | 0.000 | 0.585692E+09 |
June | 0.000 | 0.114811E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.490332E+08 |
October | 0.000 | 0.326303E+10 |
November | 0.000 | 0.188945E+11 |
December | 0.000 | 0.479216E+11 |
Annual Sum or Average | 0.216168E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.715781E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Meter
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.715781E+11 |
February | 0.000 | 0.521303E+11 |
March | 0.000 | 0.155665E+11 |
April | 0.000 | 0.606411E+10 |
May | 0.000 | 0.585692E+09 |
June | 0.000 | 0.114811E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.490332E+08 |
October | 0.000 | 0.326303E+10 |
November | 0.000 | 0.188945E+11 |
December | 0.000 | 0.479216E+11 |
Annual Sum or Average | 0.216168E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.715781E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Meter
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.715781E+11 |
February | 0.000 | 0.521303E+11 |
March | 0.000 | 0.155665E+11 |
April | 0.000 | 0.606411E+10 |
May | 0.000 | 0.585692E+09 |
June | 0.000 | 0.114811E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.490332E+08 |
October | 0.000 | 0.326303E+10 |
November | 0.000 | 0.188945E+11 |
December | 0.000 | 0.479216E+11 |
Annual Sum or Average | 0.216168E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.715781E+11 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 | 4.99 | 0.194997E+09 | 236.59 | 09-JAN-08:30 | 0.30 | -0.7 |
February | 633386.04 | 141.43 | 28-FEB-11:40 | 11.50 | 10.36 | 0.180391E+09 | 284.62 | 27-FEB-16:10 | 19.32 | 12.37 |
March | 16463290.96 | 470.60 | 11-MAR-15:00 | 8.30 | 7.17 | 0.213373E+09 | 299.29 | 18-MAR-15:00 | 20.60 | 10.40 |
April | 0.180752E+09 | 3327.83 | 27-APR-16:00 | 27.20 | 16.88 | 0.207769E+09 | 301.60 | 29-APR-15:30 | 21.10 | 14.84 |
May | 0.769599E+09 | 4210.70 | 15-MAY-16:00 | 23.90 | 12.83 | 0.241053E+09 | 301.60 | 06-MAY-09:39 | 20.20 | 15.82 |
June | 0.180796E+10 | 5876.93 | 28-JUN-16:00 | 26.10 | 16.27 | 0.253498E+09 | 301.60 | 26-JUN-15:09 | 20.60 | 14.34 |
July | 0.339169E+10 | 18348.42 | 24-JUL-05:01 | 15.87 | 13.14 | 0.248010E+09 | 301.61 | 22-JUL-13:50 | 24.03 | 16.14 |
August | 0.407150E+10 | 19101.88 | 15-AUG-05:02 | 13.05 | 11.44 | 0.268196E+09 | 301.63 | 09-AUG-10:09 | 23.92 | 15.99 |
September | 0.204481E+10 | 17992.95 | 15-SEP-05:03 | 11.60 | 11.30 | 0.244521E+09 | 301.61 | 11-SEP-15:50 | 23.30 | 16.08 |
October | 0.222305E+09 | 2896.35 | 04-OCT-16:00 | 21.10 | 11.38 | 0.211817E+09 | 301.58 | 12-OCT-15:00 | 14.40 | 9.93 |
November | 18535463.79 | 907.21 | 04-NOV-15:50 | 20.18 | 15.91 | 0.189587E+09 | 301.58 | 04-NOV-14:09 | 21.10 | 15.93 |
December | 593400.56 | 133.14 | 02-DEC-15:50 | 10.78 | 4.71 | 0.195025E+09 | 239.47 | 02-DEC-15:20 | 11.33 | 5.19 |
Annual Sum or Average | 0.125248E+11 | 0.264824E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | 5.92 | 4.71 | 0.180391E+09 | 236.59 | 0.30 | -0.7 | ||
Maximum of Months | 0.407150E+10 | 19101.88 | 27.20 | 16.88 | 0.268196E+09 | 301.63 | 24.03 | 16.14 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.500972E+09 | 3362.88 | 19-JAN-14:40 | 4.80 | 2.55 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.684738E+09 | 4388.06 | 28-FEB-07:10 | 10.60 | 9.78 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.127172E+10 | 4629.43 | 11-MAR-07:10 | 10.00 | 9.66 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.108601E+10 | 6701.63 | 27-APR-06:10 | 11.88 | 9.03 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.139973E+10 | 7227.68 | 11-MAY-06:10 | 5.97 | 5.05 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.150336E+10 | 7815.21 | 28-JUN-15:00 | 26.10 | 15.52 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.338988E+10 | 35443.71 | 23-JUL-17:11 | 26.50 | 15.67 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.415385E+10 | 35021.43 | 15-AUG-17:11 | 25.90 | 16.31 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.196395E+10 | 8291.17 | 14-SEP-14:40 | 23.90 | 17.00 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.103941E+10 | 4798.34 | 14-OCT-06:10 | 8.90 | 7.91 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.939169E+09 | 4185.69 | 07-NOV-07:10 | 11.70 | 9.90 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.802900E+09 | 4385.04 | 06-DEC-12:00 | 3.30 | 3.23 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.187357E+11 | 0.00 | ||||||||
Minimum of Months | 0.500972E+09 | 3362.88 | 3.30 | 2.55 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.415385E+10 | 35443.71 | 26.50 | 17.00 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 | 4.99 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 | 6.66 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.00 | 0.00 | 01-APR-00:05 | 7.93 | 7.13 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 | 3.48 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.00 | 0.00 | 17.17 | 13.74 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.523311E+10 | 25431.37 | 09-JAN-06:22 | -1.1 |
February | 0.406181E+10 | 26249.14 | 14-FEB-06:32 | 0.20 |
March | 0.321148E+10 | 25275.48 | 06-MAR-06:12 | 6.70 |
April | 0.180660E+10 | 25115.51 | 19-APR-05:01 | 1.78 |
May | 0.533936E+09 | 24903.21 | 20-MAY-05:01 | 7.88 |
June | 0.197722E+09 | 8588.58 | 15-JUN-05:03 | 8.98 |
July | 77829509.62 | 2470.12 | 24-JUL-06:05 | 17.48 |
August | 76452787.70 | 1562.99 | 01-AUG-06:02 | 11.32 |
September | 0.140975E+09 | 6898.31 | 28-SEP-06:05 | 8.40 |
October | 0.129516E+10 | 25102.05 | 16-OCT-05:01 | 7.12 |
November | 0.310706E+10 | 25284.08 | 13-NOV-06:12 | 1.70 |
December | 0.448961E+10 | 25417.61 | 26-DEC-06:22 | -1.1 |
Annual Sum or Average | 0.242318E+11 | |||
Minimum of Months | 76452787.70 | 1562.99 | -1.1 | |
Maximum of Months | 0.523311E+10 | 26249.14 | 17.48 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.209246E+11 | 67330.69 | 14-JAN-20:42 | 0.68 |
February | 0.153269E+11 | 68130.85 | 19-FEB-07:22 | -5.0 |
March | 0.735425E+10 | 66350.03 | 24-MAR-05:53 | 1.70 |
April | 0.269229E+10 | 66115.87 | 11-APR-04:03 | 5.10 |
May | 0.230137E+09 | 2257.36 | 17-MAY-07:00 | 8.90 |
June | 0.196892E+09 | 2140.74 | 13-JUN-07:00 | 11.70 |
July | 0.161026E+09 | 2111.90 | 28-JUL-06:50 | 15.50 |
August | 0.188561E+09 | 2259.66 | 31-AUG-07:00 | 14.00 |
September | 0.177716E+09 | 2287.44 | 27-SEP-07:00 | 8.90 |
October | 0.117277E+10 | 51734.80 | 31-OCT-20:33 | 7.20 |
November | 0.875617E+10 | 66452.59 | 29-NOV-21:23 | 5.00 |
December | 0.167331E+11 | 66480.55 | 22-DEC-22:42 | 1.30 |
Annual Sum or Average | 0.739144E+11 | |||
Minimum of Months | 0.161026E+09 | 2111.90 | -5.0 | |
Maximum of Months | 0.209246E+11 | 68130.85 | 15.50 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248579E+11 | 43780.04 | 15-JAN-01:52 | -1.7 |
February | 0.181962E+11 | 65284.61 | 19-FEB-07:00 | -5.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:05 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.698786E+09 | 19639.21 | 30-NOV-18:08 | 4.90 |
December | 0.122336E+11 | 34014.22 | 22-DEC-23:00 | 1.10 |
Annual Sum or Average | 0.559865E+11 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.248579E+11 | 65284.61 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.256100E+10 | 1939.55 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.233575E+10 | 1939.55 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.266872E+10 | 1939.55 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.252182E+10 | 1939.55 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.261486E+10 | 1939.55 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.257569E+10 | 1939.55 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.256100E+10 | 1939.55 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.266872E+10 | 1939.55 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.252182E+10 | 1939.55 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.256100E+10 | 1939.55 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.246796E+10 | 1939.55 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.256100E+10 | 1939.55 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.306193E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.233575E+10 | 1939.55 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.266872E+10 | 1939.55 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112294E+11 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102778E+11 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.118738E+11 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.111270E+11 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.115516E+11 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.114492E+11 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112294E+11 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.118738E+11 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.111270E+11 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112294E+11 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108048E+11 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112294E+11 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135003E+12 | ||||
Minimum of Months | 0.102778E+11 | 10075.60 | 0.00 | 0.00 | |
Maximum of Months | 0.118738E+11 | 10075.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.258277E+11 | 23173.88 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.236390E+11 | 23173.88 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.273097E+11 | 23173.88 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.255921E+11 | 23173.88 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.265687E+11 | 23173.88 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.263332E+11 | 23173.88 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.258277E+11 | 23173.88 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.273097E+11 | 23173.88 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.255921E+11 | 23173.88 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.258277E+11 | 23173.88 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.248511E+11 | 23173.88 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.258277E+11 | 23173.88 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.236390E+11 | 23173.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.273097E+11 | 23173.88 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296604E+10 |
February | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248616E+10 |
March | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245940E+10 |
April | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10805725.97 | 0.193379E+10 |
May | 0.565842E+09 | 0.261486E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1143335.57 | 0.176884E+10 |
June | 0.565842E+09 | 0.257569E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8776818.59 | 0.147220E+10 |
July | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50102859.73 | 0.109049E+10 |
August | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136219E+09 | 0.103882E+10 |
September | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2004373.48 | 0.118241E+10 |
October | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187806E+10 |
November | 0.522316E+09 | 0.246796E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238844E+10 |
December | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269830E+10 |
Annual Sum or Average | 0.659424E+10 | 0.306193E+11 | 0.319458E+11 | 0.209052E+09 | 0.233629E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103882E+10 |
Maximum of Months | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136219E+09 | 0.296604E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149529E+11 |
February | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126130E+11 |
March | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109460E+11 |
April | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112216E+09 | 0.968048E+10 |
May | 0.00 | 0.115516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.963103E+10 |
June | 0.00 | 0.114492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913330E+10 |
July | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59428503.06 | 0.837123E+10 |
August | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178589E+09 | 0.768212E+10 |
September | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545774E+10 |
October | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.854407E+10 |
November | 0.00 | 0.108048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100859E+11 |
December | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121650E+11 |
Annual Sum or Average | 0.135003E+12 | 0.350234E+09 | 0.119263E+12 | ||||||
Minimum of Months | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545774E+10 |
Maximum of Months | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178589E+09 | 0.149529E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79440672.89 | 0.254357E+11 |
February | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356899E+09 | 0.219373E+11 |
March | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251834E+09 | 0.224575E+11 |
April | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146295E+10 | 0.220331E+11 |
May | 0.00 | 0.265687E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181281E+09 | 0.277913E+11 |
June | 0.00 | 0.263332E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18137696.29 | 0.257736E+11 |
July | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116594E+09 | 0.262466E+11 |
August | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319736E+09 | 0.274117E+11 |
September | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200159E+11 |
October | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257743E+11 |
November | 0.00 | 0.248511E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58122867.91 | 0.201596E+11 |
December | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26786546.43 | 0.190954E+11 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | 0.287179E+10 | 0.284132E+12 | |||||
Minimum of Months | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190954E+11 |
Maximum of Months | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146295E+10 | 0.277913E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1939.55 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9252.74 | 06-JAN-07:10 |
February | 659.25 | 01-FEB-08:09 | 1939.55 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 8842.40 | 09-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1939.55 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 8463.16 | 24-MAR-06:10 |
April | 659.25 | 01-APR-07:10 | 1939.55 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1168.53 | 27-APR-16:10 | 7567.11 | 19-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1939.55 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.65 | 05-MAY-16:10 | 6256.42 | 18-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1939.55 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1034.86 | 28-JUN-17:00 | 4780.23 | 13-JUN-11:03 |
July | 659.25 | 01-JUL-07:10 | 1939.55 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1864.70 | 31-JUL-16:10 | 4306.34 | 12-JUL-06:02 |
August | 659.25 | 01-AUG-07:10 | 1939.55 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2809.13 | 10-AUG-17:00 | 4938.18 | 01-AUG-06:01 |
September | 659.25 | 01-SEP-07:10 | 1939.55 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.83 | 14-SEP-17:00 | 4806.05 | 27-SEP-07:00 |
October | 659.25 | 02-OCT-07:10 | 1939.55 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 6148.15 | 16-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1939.55 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7966.94 | 24-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1939.55 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 9162.43 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4306.34 | |||||
Maximum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2809.13 | 9252.74 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 20718.50 | 28-JAN-08:00 |
February | 0.00 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 17959.39 | 13-FEB-08:00 |
March | 0.00 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 16377.80 | 24-MAR-06:10 |
April | 0.00 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4908.35 | 01-APR-16:00 | 13781.94 | 08-APR-07:00 |
May | 0.00 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 15252.22 | 10-MAY-15:05 |
June | 0.00 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 13790.59 | 13-JUN-03:00 |
July | 0.00 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2082.75 | 24-JUL-15:10 | 9687.79 | 03-JUL-15:05 |
August | 0.00 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3590.71 | 08-AUG-17:00 | 13168.33 | 11-AUG-04:00 |
September | 0.00 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 10313.67 | 26-SEP-15:10 |
October | 0.00 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 12586.89 | 31-OCT-19:57 |
November | 0.00 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 19433.93 | 29-NOV-18:00 |
December | 0.00 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 14389.65 | 22-DEC-21:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9687.79 | |||
Maximum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4908.35 | 20718.50 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23173.88 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7470.74 | 11-JAN-14:00 | 29089.76 | 14-JAN-19:52 |
February | 0.00 | 23173.88 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6157.51 | 27-FEB-15:00 | 36638.83 | 13-FEB-11:00 |
March | 0.00 | 23173.88 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11088.44 | 18-MAR-16:00 | 35828.15 | 22-MAR-09:00 |
April | 0.00 | 23173.88 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33919.34 | 01-APR-16:00 | 27749.37 | 08-APR-07:10 |
May | 0.00 | 23173.88 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3856.48 | 14-MAY-15:00 | 37519.08 | 10-MAY-15:00 |
June | 0.00 | 23173.88 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1763.96 | 20-JUN-17:00 | 41058.26 | 13-JUN-10:00 |
July | 0.00 | 23173.88 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4640.55 | 23-JUL-13:55 | 27749.28 | 03-JUL-16:00 |
August | 0.00 | 23173.88 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5635.72 | 08-AUG-17:00 | 39984.84 | 11-AUG-04:00 |
September | 0.00 | 23173.88 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 32200.40 | 26-SEP-15:40 |
October | 0.00 | 23173.88 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 24784.26 | 14-OCT-11:00 |
November | 0.00 | 23173.88 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5374.90 | 27-NOV-03:55 | 27823.71 | 29-NOV-14:00 |
December | 0.00 | 23173.88 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6049.70 | 14-DEC-12:00 | 37341.89 | 26-DEC-14:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24784.26 | ||||
Maximum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 33919.34 | 41058.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1813.61 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.30 |
February | 141.43 | 28-FEB-11:40 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 497.45 |
March | 470.60 | 11-MAR-15:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.34 |
April | 3327.83 | 27-APR-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 296.34 | 0.00 |
May | 4210.70 | 15-MAY-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
June | 5876.93 | 28-JUN-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 210.36 | 0.00 |
July | 18348.42 | 24-JUL-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 520.44 |
August | 19101.88 | 15-AUG-05:02 | 435.11 | 3476.08 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 776.28 |
September | 17992.95 | 15-SEP-05:03 | 290.07 | 2317.39 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 651.26 |
October | 2896.35 | 04-OCT-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.12 |
November | 907.21 | 04-NOV-15:50 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.57 |
December | 133.14 | 02-DEC-15:50 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.36 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 1813.61 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19101.88 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 296.34 | 776.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3362.88 | 19-JAN-14:40 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1880.38 |
February | 4388.06 | 28-FEB-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2037.79 |
March | 4629.43 | 11-MAR-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2763.36 |
April | 6701.63 | 27-APR-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2003.29 |
May | 7227.68 | 11-MAY-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6560.81 |
June | 7815.21 | 28-JUN-15:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.46 |
July | 35443.71 | 23-JUL-17:11 | 0.00 | 8297.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.64 |
August | 35021.43 | 15-AUG-17:11 | 0.00 | 8297.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.83 |
September | 8291.17 | 14-SEP-14:40 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.42 |
October | 4798.34 | 14-OCT-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4241.75 |
November | 4185.69 | 07-NOV-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5037.71 |
December | 4385.04 | 06-DEC-12:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1402.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3362.88 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.46 | |
Maximum of Months | 35443.71 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6560.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 10905.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13224.71 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5120.88 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10173.16 |
April | 0.00 | 01-APR-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7554.93 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16460.49 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5612.15 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7869.19 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10647.44 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13439.89 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8558.49 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10576.72 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 8179.02 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5487.34 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5120.88 | |
Maximum of Months | 0.00 | 0.00 | 10905.36 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16460.49 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.682289E+11 | 52665.35 | 18-JAN-16:00 | 0.715781E+11 | 99310.88 | 14-JAN-20:49 |
February | 0.613027E+11 | 50456.60 | 13-FEB-13:09 | 0.521303E+11 | 137688.75 | 19-FEB-06:49 |
March | 0.687680E+11 | 50266.42 | 01-MAR-13:09 | 0.155665E+11 | 47659.69 | 24-MAR-05:00 |
April | 0.633547E+11 | 51238.42 | 27-APR-14:09 | 0.606411E+10 | 37769.10 | 18-APR-05:10 |
May | 0.646164E+11 | 51590.79 | 06-MAY-12:00 | 0.585692E+09 | 10123.98 | 24-MAY-06:10 |
June | 0.634812E+11 | 54347.51 | 28-JUN-14:00 | 0.114811E+09 | 5076.69 | 14-JUN-06:10 |
July | 0.636231E+11 | 57910.21 | 24-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.686438E+11 | 58783.16 | 10-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.640662E+11 | 54025.42 | 14-SEP-14:39 | 49033166.73 | 6238.10 | 28-SEP-06:10 |
October | 0.658167E+11 | 50716.24 | 04-OCT-14:00 | 0.326303E+10 | 27852.09 | 30-OCT-05:10 |
November | 0.647195E+11 | 52472.42 | 30-NOV-16:49 | 0.188945E+11 | 62063.21 | 29-NOV-20:10 |
December | 0.682731E+11 | 52663.78 | 26-DEC-16:30 | 0.479216E+11 | 79990.40 | 22-DEC-22:49 |
Annual Sum or Average | 0.784894E+12 | 0.216168E+12 | ||||
Minimum of Months | 0.613027E+11 | 50266.42 | 0.00 | 0.00 | ||
Maximum of Months | 0.687680E+11 | 58783.16 | 0.715781E+11 | 137688.75 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.396181E+11 | 0.107615E+11 | 0.115358E+11 | 0.00 | 0.408400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222949E+10 | 0.00 |
February | 0.362526E+11 | 0.887200E+10 | 0.105871E+11 | 0.00 | 0.355878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203220E+10 | 0.00 |
March | 0.418523E+11 | 0.865995E+10 | 0.123357E+11 | 0.00 | 0.363405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228602E+10 | 0.00 |
April | 0.392410E+11 | 0.721347E+10 | 0.114862E+11 | 0.00 | 0.322678E+10 | 0.00 | 0.00 | 34901033.62 | 0.00 | 0.00 | 0.00 | 0.215235E+10 | 0.00 |
May | 0.407352E+11 | 0.640693E+10 | 0.119357E+11 | 0.00 | 0.325977E+10 | 0.00 | 0.00 | 85638162.89 | 0.00 | 0.00 | 0.00 | 0.219314E+10 | 0.00 |
June | 0.403581E+11 | 0.563825E+10 | 0.118862E+11 | 0.00 | 0.325402E+10 | 0.00 | 0.00 | 0.231978E+09 | 0.00 | 0.00 | 0.00 | 0.211278E+10 | 0.00 |
July | 0.396181E+11 | 0.608507E+10 | 0.115358E+11 | 0.00 | 0.315045E+10 | 0.00 | 0.00 | 0.112748E+10 | 0.00 | 0.00 | 0.00 | 0.210619E+10 | 0.00 |
August | 0.418523E+11 | 0.698628E+10 | 0.123357E+11 | 0.00 | 0.340703E+10 | 0.00 | 0.00 | 0.190825E+10 | 0.00 | 0.00 | 0.00 | 0.215426E+10 | 0.00 |
September | 0.392410E+11 | 0.787234E+10 | 0.114862E+11 | 0.00 | 0.312970E+10 | 0.00 | 0.00 | 0.269918E+09 | 0.00 | 0.00 | 0.00 | 0.206705E+10 | 0.00 |
October | 0.396181E+11 | 0.934154E+10 | 0.115358E+11 | 0.00 | 0.317430E+10 | 0.00 | 0.00 | 3850562.72 | 0.00 | 0.00 | 0.00 | 0.214307E+10 | 0.00 |
November | 0.381239E+11 | 0.100989E+11 | 0.110862E+11 | 0.00 | 0.330967E+10 | 0.00 | 0.00 | 112.77 | 0.00 | 0.00 | 0.00 | 0.210081E+10 | 0.00 |
December | 0.396181E+11 | 0.110379E+11 | 0.115358E+11 | 0.00 | 0.387320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220808E+10 | 0.00 |
Annual Sum or Average | 0.476129E+12 | 0.989742E+11 | 0.139282E+12 | 0.410617E+11 | 0.00 | 0.366202E+10 | 0.257854E+11 | ||||||
Minimum of Months | 0.362526E+11 | 0.563825E+10 | 0.105871E+11 | 0.00 | 0.312970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203220E+10 | 0.00 |
Maximum of Months | 0.418523E+11 | 0.110379E+11 | 0.123357E+11 | 0.00 | 0.408400E+10 | 0.00 | 0.00 | 0.190825E+10 | 0.00 | 0.00 | 0.00 | 0.228602E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.715781E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.521303E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.155665E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.606411E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.585692E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.114811E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 49033166.73 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.326303E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.188945E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.479216E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216168E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.715781E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35189.04 | 02-JAN-09:09 | 6311.00 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 3348.77 | 13-JAN-08:39 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35189.04 | 01-FEB-09:09 | 6311.00 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 3348.77 | 06-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35189.04 | 01-MAR-09:09 | 6311.00 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 3159.92 | 22-MAR-09:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35189.04 | 01-APR-08:09 | 6311.00 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 3159.92 | 01-APR-07:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35189.04 | 01-MAY-08:09 | 6311.00 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 3159.92 | 01-MAY-06:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35189.04 | 01-JUN-08:09 | 6311.00 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 3159.92 | 21-JUN-13:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35189.04 | 01-JUL-08:09 | 6311.00 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 3159.92 | 08-JUL-14:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35189.04 | 01-AUG-08:09 | 6311.00 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 3159.92 | 01-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35189.04 | 01-SEP-08:09 | 6311.00 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 3159.92 | 09-SEP-14:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35189.04 | 02-OCT-08:09 | 6311.00 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 3159.92 | 02-OCT-13:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35189.04 | 01-NOV-08:09 | 6311.00 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 3348.77 | 29-NOV-17:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35189.04 | 01-DEC-09:09 | 6311.00 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 3348.77 | 05-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35189.04 | 6311.00 | 10112.62 | 0.00 | 3159.92 | 0.00 | 0.00 | |||||
Maximum of Months | 35189.04 | 6311.00 | 10112.62 | 0.00 | 3348.77 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2331.39 | 31-JAN-12:09 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2336.99 | 10-FEB-12:20 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2319.64 | 02-MAR-12:00 | 0.00 |
April | 1258.80 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 | 2219.20 | 04-APR-11:00 | 0.00 |
May | 1345.83 | 06-MAY-12:00 | 0.00 | 0.00 | 0.00 | 2030.09 | 09-MAY-11:20 | 0.00 |
June | 4123.00 | 28-JUN-14:00 | 0.00 | 0.00 | 0.00 | 1812.61 | 01-JUN-11:00 | 0.00 |
July | 7836.85 | 24-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1799.93 | 01-JUL-11:09 | 0.00 |
August | 8749.67 | 10-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1794.61 | 31-AUG-11:09 | 0.00 |
September | 3803.70 | 14-SEP-14:39 | 0.00 | 0.00 | 0.00 | 1802.29 | 28-SEP-11:39 | 0.00 |
October | 519.23 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 1934.90 | 30-OCT-11:20 | 0.00 |
November | 0.04 | 04-NOV-13:00 | 0.00 | 0.00 | 0.00 | 2103.74 | 28-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2227.76 | 23-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1794.61 | 0.00 | ||
Maximum of Months | 8749.67 | 0.00 | 0.00 | 0.00 | 2336.99 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 52665.35 | 18-JAN-16:00 | 31277.33 | 10112.62 | 6311.00 | 0.00 | 3348.77 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 50456.60 | 13-FEB-13:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3348.77 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 50266.42 | 01-MAR-13:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3159.92 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 51238.42 | 27-APR-14:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3159.92 | 0.00 | 0.00 | 990.21 | 0.00 |
May | 51590.79 | 06-MAY-12:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3159.92 | 0.00 | 0.00 | 1345.83 | 0.00 |
June | 54347.51 | 28-JUN-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3159.92 | 0.00 | 0.00 | 4123.00 | 0.00 |
July | 57910.21 | 24-JUL-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3159.92 | 0.00 | 0.00 | 7691.12 | 0.00 |
August | 58783.16 | 10-AUG-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3159.92 | 0.00 | 0.00 | 8565.31 | 0.00 |
September | 54025.42 | 14-SEP-14:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3159.92 | 0.00 | 0.00 | 3803.70 | 0.00 |
October | 50716.24 | 04-OCT-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3159.92 | 0.00 | 0.00 | 519.23 | 0.00 |
November | 52472.42 | 30-NOV-16:49 | 31277.33 | 10112.62 | 6311.00 | 0.00 | 3159.92 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 52663.78 | 26-DEC-16:30 | 31277.33 | 10112.62 | 6311.00 | 0.00 | 3348.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 50266.42 | 31277.33 | 10112.62 | 0.00 | 0.00 | 3159.92 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 58783.16 | 35189.04 | 10112.62 | 6311.00 | 0.00 | 3348.77 | 0.00 | 0.00 | 8565.31 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 99310.88 | 14-JAN-20:49 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 137688.75 | 19-FEB-06:49 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 47659.69 | 24-MAR-05:00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 37769.10 | 18-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 10123.98 | 24-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 5076.69 | 14-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 6238.10 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 27852.09 | 30-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 62063.21 | 29-NOV-20:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 79990.40 | 22-DEC-22:49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 137688.75 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.67 | 18.67 | 8.50 | 19.61 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8.67 | 19.15 | 7.67 | 19.70 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8.17 | 20.01 | 8.17 | 20.01 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5.33 | 20.13 | 5.33 | 20.13 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.50 | 20.45 | 0.50 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.50 | 20.52 | 0.50 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.53 | 0.33 | 24.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.51 | 0.83 | 24.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3.50 | 20.30 | 3.50 | 20.30 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.50 | 20.04 | 6.50 | 20.04 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9.00 | 19.49 | 8.50 | 19.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.83 | 19.55 | 49.17 | 19.89 | 1.17 | 24.51 | 1.17 | 24.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.67 | 20.52 | 8.50 | 20.52 | 0.83 | 24.53 | 0.83 | 24.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 98.17 | 14.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 66.83 | 14.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 25.50 | 14.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8.83 | 14.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3.50 | 14.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 37.50 | 14.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 80.67 | 14.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 321.00 | 14.74 | 0.00 | 0.67 | 27.27 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 98.17 | 14.95 | 0.00 | 0.00 | 0.33 | 27.28 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.06 | 300.00 | 21.06 | 300.00 | 21.06 |
February | 276.00 | 21.11 | 263.83 | 21.06 | 263.83 | 21.06 |
March | 324.00 | 21.19 | 299.67 | 21.11 | 299.67 | 21.11 |
April | 300.00 | 21.67 | 198.50 | 21.13 | 198.50 | 21.13 |
May | 299.83 | 22.74 | 41.00 | 21.13 | 41.00 | 21.13 |
June | 245.83 | 23.31 | 6.50 | 23.47 | 1.00 | 21.08 |
July | 95.17 | 23.58 | 99.67 | 23.90 | 0.00 | 0.00 |
August | 61.67 | 23.55 | 161.33 | 23.90 | 0.00 | 0.00 |
September | 202.33 | 23.34 | 38.00 | 23.84 | 0.67 | 20.85 |
October | 300.00 | 21.85 | 151.83 | 21.11 | 151.83 | 21.11 |
November | 288.00 | 21.19 | 255.33 | 21.08 | 255.33 | 21.08 |
December | 300.00 | 21.06 | 300.00 | 21.06 | 300.00 | 21.06 |
Annual Sum or Average | 2992.83 | 21.87 | 2115.67 | 21.49 | 1811.83 | 21.08 |
Minimum of Months | 61.67 | 21.06 | 6.50 | 21.06 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 23.58 | 300.00 | 23.90 | 300.00 | 21.13 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.140493E+09 | 34901033.62 | 20.50 | 0.135942E+09 | 4551271.91 | 0.00 | 0.36 | 27-APR-16:00 | 0.00 | 01-APR-00:05 | 5042.87 | 27-APR-16:00 | 4836.55 | 27-APR-16:00 | 313.36 | 29-APR-15:00 | 1258.80 | 27-APR-16:00 | 0.00 | 01-APR-00:05 |
May | 0.359021E+09 | 85638162.89 | 69.58 | 0.323928E+09 | 35092564.57 | 0.00 | 0.38 | 15-MAY-16:00 | 0.00 | 01-MAY-00:10 | 5775.90 | 06-MAY-13:00 | 5303.25 | 15-MAY-16:00 | 1169.89 | 06-MAY-13:00 | 1345.83 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.782163E+09 | 0.187206E+09 | 145.92 | 0.754364E+09 | 27799252.05 | 0.00 | 0.51 | 28-JUN-16:00 | 0.00 | 01-JUN-00:10 | 7337.12 | 28-JUN-16:00 | 7244.93 | 28-JUN-16:00 | 492.30 | 21-JUN-17:00 | 1754.68 | 28-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.249846E+10 | 0.592671E+09 | 188.80 | 0.217380E+10 | 0.324660E+09 | 0.00 | 1.00 | 20-JUL-05:03 | 0.00 | 01-JUL-00:10 | 15966.20 | 31-JUL-05:01 | 11969.43 | 24-JUL-06:00 | 5619.24 | 25-JUL-05:02 | 3378.28 | 31-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.364211E+10 | 0.871522E+09 | 228.65 | 0.315912E+10 | 0.482988E+09 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 16272.65 | 30-AUG-05:01 | 11718.90 | 09-AUG-05:02 | 6350.59 | 26-AUG-05:50 | 3436.70 | 30-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.944991E+09 | 0.222047E+09 | 124.79 | 0.785480E+09 | 0.159511E+09 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 15516.04 | 01-SEP-05:03 | 10746.26 | 01-SEP-05:03 | 5559.14 | 14-SEP-05:03 | 3288.79 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 |
October | 15755197.01 | 3850562.72 | 23.08 | 15754995.72 | 201.29 | 0.00 | 0.17 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2136.57 | 04-OCT-15:00 | 2136.57 | 04-OCT-15:00 | 0.02 | 06-OCT-12:30 | 519.23 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 454.91 | 112.77 | 1.33 | 356.00 | 98.91 | 0.00 | 0.00 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.16 | 04-NOV-14:00 | 0.13 | 04-NOV-14:00 | 0.03 | 04-NOV-14:00 | 0.04 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.838299E+10 | 0.199784E+10 | 802.65 | 0.734839E+10 | 0.103460E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.364211E+10 | 0.871522E+09 | 228.65 | 0.315912E+10 | 0.482988E+09 | 0.00 | 1.00 | 0.00 | 16272.65 | 11969.43 | 6350.59 | 3436.70 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.161327E+09 | 44772065.39 | 19.50 | 0.154950E+09 | 6377355.53 | 0.00 | 0.27 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 | 8921.18 | 28-JUN-15:00 | 8921.18 | 28-JUN-15:00 | 398.61 | 28-JUN-13:20 | 2476.83 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.195355E+10 | 0.534811E+09 | 84.55 | 0.171805E+10 | 0.235508E+09 | 0.00 | 1.00 | 20-JUL-17:21 | 0.00 | 01-JUL-00:10 | 41342.16 | 27-JUL-17:21 | 37476.32 | 23-JUL-16:30 | 10541.14 | 27-JUL-17:40 | 9878.66 | 31-JUL-17:10 | 0.00 | 01-JUL-00:10 |
August | 0.374736E+10 | 0.103673E+10 | 104.77 | 0.330292E+10 | 0.444443E+09 | 0.00 | 1.00 | 08-AUG-17:10 | 0.00 | 01-AUG-00:10 | 40479.64 | 13-AUG-13:42 | 36443.63 | 08-AUG-17:10 | 7603.94 | 13-AUG-11:36 | 10009.95 | 10-AUG-17:08 | 0.00 | 01-AUG-00:10 |
September | 0.176131E+09 | 47871141.32 | 22.17 | 0.138565E+09 | 37566451.19 | 0.00 | 0.21 | 14-SEP-14:30 | 0.00 | 01-SEP-00:10 | 7516.46 | 14-SEP-14:30 | 5928.92 | 14-SEP-14:40 | 1647.74 | 14-SEP-14:00 | 2009.98 | 14-SEP-14:30 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.603838E+10 | 0.166419E+10 | 230.98 | 0.531448E+10 | 0.723894E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.374736E+10 | 0.103673E+10 | 104.77 | 0.330292E+10 | 0.444443E+09 | 0.00 | 1.00 | 0.00 | 41342.16 | 37476.32 | 10541.14 | 10009.95 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.15 | 11.92 | 28.22 | 11.33 | 135.69 | 0.00 | 0.00 | 744.00 |
February | 71.32 | 26.57 | 44.76 | 40.36 | 114.75 | 0.00 | 0.00 | 672.00 |
March | 100.46 | 33.94 | 66.52 | 72.69 | 90.13 | 0.00 | 0.00 | 744.00 |
April | 152.51 | 58.19 | 94.32 | 137.32 | 72.51 | 0.00 | 0.00 | 720.00 |
May | 196.69 | 79.98 | 116.71 | 189.14 | 68.81 | 0.00 | 0.00 | 744.00 |
June | 189.10 | 73.42 | 115.68 | 179.01 | 60.29 | 0.00 | 0.00 | 720.00 |
July | 234.01 | 123.17 | 110.84 | 247.04 | 62.07 | 0.00 | 0.00 | 744.00 |
August | 193.20 | 98.54 | 94.66 | 206.33 | 63.04 | 0.00 | 0.00 | 744.00 |
September | 157.93 | 75.98 | 81.95 | 152.10 | 80.69 | 0.00 | 0.00 | 720.00 |
October | 89.94 | 36.79 | 53.14 | 70.06 | 85.13 | 0.00 | 0.00 | 744.00 |
November | 44.75 | 12.75 | 32.00 | 19.47 | 104.52 | 0.00 | 0.00 | 720.00 |
December | 37.97 | 13.32 | 24.65 | 15.27 | 136.36 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 126.00 | 53.92 | 72.08 | 112.15 | 89.40 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 37.97 | 11.92 | 24.65 | 11.33 | 60.29 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 234.01 | 123.17 | 116.71 | 247.04 | 136.36 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.15 | 11.92 | 28.22 | 11.33 | 135.69 | 0.00 | 0.00 | 744.00 |
February | 71.32 | 26.57 | 44.76 | 40.36 | 114.75 | 0.00 | 0.00 | 672.00 |
March | 100.46 | 33.94 | 66.52 | 72.69 | 90.13 | 0.00 | 0.00 | 744.00 |
April | 152.51 | 58.19 | 94.32 | 137.32 | 72.51 | 0.00 | 0.00 | 720.00 |
May | 196.69 | 79.98 | 116.71 | 189.14 | 68.81 | 0.00 | 0.00 | 744.00 |
June | 189.10 | 73.42 | 115.68 | 179.01 | 60.29 | 0.00 | 0.00 | 720.00 |
July | 234.01 | 123.17 | 110.84 | 247.04 | 62.07 | 0.00 | 0.00 | 744.00 |
August | 193.20 | 98.54 | 94.66 | 206.33 | 63.04 | 0.00 | 0.00 | 744.00 |
September | 157.93 | 75.98 | 81.95 | 152.10 | 80.69 | 0.00 | 0.00 | 720.00 |
October | 89.94 | 36.79 | 53.14 | 70.06 | 85.13 | 0.00 | 0.00 | 744.00 |
November | 44.75 | 12.75 | 32.00 | 19.47 | 104.52 | 0.00 | 0.00 | 720.00 |
December | 37.97 | 13.32 | 24.65 | 15.27 | 136.36 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 126.00 | 53.92 | 72.08 | 112.15 | 89.40 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 37.97 | 11.92 | 24.65 | 11.33 | 60.29 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 234.01 | 123.17 | 116.71 | 247.04 | 136.36 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.76 | 0.00 | 13.76 | 0.28 | 83.35 | 0.00 | 0.00 | 744.00 |
February | 21.40 | 0.00 | 21.40 | 3.32 | 71.42 | 0.00 | 0.00 | 672.00 |
March | 31.54 | 0.00 | 31.54 | 10.93 | 54.48 | 0.00 | 0.00 | 744.00 |
April | 44.70 | 0.21 | 44.48 | 25.62 | 42.51 | 0.00 | 0.00 | 720.00 |
May | 57.39 | 1.67 | 55.72 | 36.57 | 39.31 | 0.00 | 0.00 | 744.00 |
June | 60.37 | 3.97 | 56.40 | 38.50 | 33.26 | 0.00 | 0.00 | 720.00 |
July | 57.43 | 4.51 | 52.91 | 39.12 | 34.52 | 0.00 | 0.00 | 744.00 |
August | 46.65 | 1.42 | 45.23 | 34.49 | 35.90 | 0.00 | 0.00 | 744.00 |
September | 36.10 | 0.02 | 36.08 | 18.68 | 48.18 | 0.00 | 0.00 | 720.00 |
October | 24.72 | 0.00 | 24.72 | 8.55 | 50.98 | 0.00 | 0.00 | 744.00 |
November | 15.57 | 0.00 | 15.57 | 1.69 | 63.67 | 0.00 | 0.00 | 720.00 |
December | 11.69 | 0.00 | 11.69 | 0.17 | 82.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 35.18 | 0.99 | 34.19 | 18.25 | 53.29 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 11.69 | 0.00 | 11.69 | 0.17 | 33.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 60.37 | 4.51 | 56.40 | 39.12 | 83.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.75 | 0.00 | 13.75 | 0.28 | 83.35 | 0.00 | 0.00 | 744.00 |
February | 21.40 | 0.00 | 21.40 | 3.32 | 71.42 | 0.00 | 0.00 | 672.00 |
March | 31.54 | 0.00 | 31.54 | 10.93 | 54.48 | 0.00 | 0.00 | 744.00 |
April | 44.70 | 0.21 | 44.48 | 25.62 | 42.51 | 0.00 | 0.00 | 720.00 |
May | 57.39 | 1.67 | 55.71 | 36.57 | 39.31 | 0.00 | 0.00 | 744.00 |
June | 60.37 | 3.97 | 56.40 | 38.50 | 33.26 | 0.00 | 0.00 | 720.00 |
July | 57.42 | 4.51 | 52.91 | 39.12 | 34.52 | 0.00 | 0.00 | 744.00 |
August | 46.65 | 1.42 | 45.23 | 34.49 | 35.90 | 0.00 | 0.00 | 744.00 |
September | 36.10 | 0.02 | 36.08 | 18.68 | 48.18 | 0.00 | 0.00 | 720.00 |
October | 24.72 | 0.00 | 24.72 | 8.55 | 50.98 | 0.00 | 0.00 | 744.00 |
November | 15.57 | 0.00 | 15.57 | 1.69 | 63.67 | 0.00 | 0.00 | 720.00 |
December | 11.69 | 0.00 | 11.69 | 0.17 | 82.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 35.18 | 0.99 | 34.19 | 18.25 | 53.29 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 11.69 | 0.00 | 11.69 | 0.17 | 33.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 60.37 | 4.51 | 56.40 | 39.12 | 83.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.94 | 2.72 | 11.22 | 6.11 | 27.86 | 0.00 | 0.00 | 744.00 |
February | 24.94 | 8.29 | 16.66 | 17.00 | 25.56 | 25.17 | 0.00 | 672.00 |
March | 43.67 | 18.74 | 24.93 | 40.23 | 22.46 | 0.00 | 0.00 | 744.00 |
April | 69.54 | 35.42 | 34.13 | 73.05 | 19.68 | 0.00 | 0.00 | 720.00 |
May | 90.34 | 46.61 | 43.73 | 96.53 | 21.86 | 0.00 | 0.00 | 744.00 |
June | 98.99 | 58.09 | 40.90 | 106.94 | 20.09 | 0.00 | 0.00 | 720.00 |
July | 103.26 | 68.17 | 35.09 | 112.50 | 23.24 | 0.00 | 0.00 | 744.00 |
August | 82.81 | 52.68 | 30.12 | 86.31 | 25.83 | 0.00 | 0.00 | 744.00 |
September | 58.23 | 32.34 | 25.89 | 53.26 | 31.23 | 0.00 | 0.00 | 720.00 |
October | 34.37 | 16.05 | 18.32 | 27.72 | 27.11 | 0.00 | 0.00 | 744.00 |
November | 16.75 | 4.10 | 12.65 | 9.43 | 23.56 | 8.50 | 0.00 | 720.00 |
December | 12.04 | 2.90 | 9.14 | 4.61 | 27.87 | 7.50 | 0.00 | 744.00 |
Annual Sum or Average | 54.24 | 28.97 | 25.27 | 53.02 | 24.70 | 41.17 | 0.00 | 8760.00 |
Minimum of Months | 12.04 | 2.72 | 9.14 | 4.61 | 19.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.26 | 68.17 | 43.73 | 112.50 | 31.23 | 25.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.94 | 2.72 | 11.22 | 6.11 | 27.86 | 0.00 | 0.00 | 744.00 |
February | 24.94 | 8.29 | 16.66 | 17.00 | 25.56 | 25.17 | 0.00 | 672.00 |
March | 43.67 | 18.74 | 24.93 | 40.23 | 22.46 | 0.00 | 0.00 | 744.00 |
April | 69.54 | 35.42 | 34.13 | 73.05 | 19.68 | 0.00 | 0.00 | 720.00 |
May | 90.34 | 46.61 | 43.73 | 96.53 | 21.86 | 0.00 | 0.00 | 744.00 |
June | 98.99 | 58.09 | 40.90 | 106.94 | 20.09 | 0.00 | 0.00 | 720.00 |
July | 103.26 | 68.17 | 35.09 | 112.50 | 23.24 | 0.00 | 0.00 | 744.00 |
August | 82.81 | 52.68 | 30.12 | 86.31 | 25.83 | 0.00 | 0.00 | 744.00 |
September | 58.23 | 32.34 | 25.89 | 53.26 | 31.23 | 0.00 | 0.00 | 720.00 |
October | 34.37 | 16.05 | 18.32 | 27.72 | 27.11 | 0.00 | 0.00 | 744.00 |
November | 16.75 | 4.10 | 12.65 | 9.43 | 23.56 | 8.50 | 0.00 | 720.00 |
December | 12.04 | 2.90 | 9.14 | 4.61 | 27.87 | 7.50 | 0.00 | 744.00 |
Annual Sum or Average | 54.24 | 28.97 | 25.27 | 53.02 | 24.70 | 41.17 | 0.00 | 8760.00 |
Minimum of Months | 12.04 | 2.72 | 9.14 | 4.61 | 19.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.26 | 68.17 | 43.73 | 112.50 | 31.23 | 25.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.94 | 2.72 | 11.22 | 6.11 | 27.86 | 0.00 | 0.00 | 744.00 |
February | 24.94 | 8.29 | 16.66 | 17.00 | 25.56 | 25.17 | 0.00 | 672.00 |
March | 43.67 | 18.74 | 24.93 | 40.23 | 22.46 | 0.00 | 0.00 | 744.00 |
April | 69.54 | 35.42 | 34.13 | 73.05 | 19.68 | 0.00 | 0.00 | 720.00 |
May | 90.34 | 46.61 | 43.73 | 96.53 | 21.86 | 0.00 | 0.00 | 744.00 |
June | 98.99 | 58.09 | 40.90 | 106.94 | 20.09 | 0.00 | 0.00 | 720.00 |
July | 103.26 | 68.17 | 35.09 | 112.50 | 23.24 | 0.00 | 0.00 | 744.00 |
August | 82.81 | 52.68 | 30.12 | 86.31 | 25.83 | 0.00 | 0.00 | 744.00 |
September | 58.23 | 32.34 | 25.89 | 53.26 | 31.23 | 0.00 | 0.00 | 720.00 |
October | 34.37 | 16.05 | 18.32 | 27.72 | 27.11 | 0.00 | 0.00 | 744.00 |
November | 16.75 | 4.10 | 12.65 | 9.43 | 23.56 | 8.50 | 0.00 | 720.00 |
December | 12.04 | 2.90 | 9.14 | 4.61 | 27.87 | 7.50 | 0.00 | 744.00 |
Annual Sum or Average | 54.24 | 28.97 | 25.27 | 53.02 | 24.70 | 41.17 | 0.00 | 8760.00 |
Minimum of Months | 12.04 | 2.72 | 9.14 | 4.61 | 19.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.26 | 68.17 | 43.73 | 112.50 | 31.23 | 25.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.94 | 2.72 | 11.22 | 6.11 | 27.86 | 0.00 | 0.00 | 744.00 |
February | 24.94 | 8.29 | 16.66 | 17.00 | 25.56 | 25.17 | 0.00 | 672.00 |
March | 43.67 | 18.74 | 24.93 | 40.23 | 22.46 | 0.00 | 0.00 | 744.00 |
April | 69.54 | 35.42 | 34.13 | 73.05 | 19.68 | 0.00 | 0.00 | 720.00 |
May | 90.34 | 46.61 | 43.73 | 96.53 | 21.86 | 0.00 | 0.00 | 744.00 |
June | 98.99 | 58.09 | 40.90 | 106.94 | 20.09 | 0.00 | 0.00 | 720.00 |
July | 103.26 | 68.17 | 35.09 | 112.50 | 23.24 | 0.00 | 0.00 | 744.00 |
August | 82.81 | 52.68 | 30.12 | 86.31 | 25.83 | 0.00 | 0.00 | 744.00 |
September | 58.23 | 32.34 | 25.89 | 53.26 | 31.23 | 0.00 | 0.00 | 720.00 |
October | 34.37 | 16.05 | 18.32 | 27.72 | 27.11 | 0.00 | 0.00 | 744.00 |
November | 16.75 | 4.10 | 12.65 | 9.43 | 23.56 | 8.50 | 0.00 | 720.00 |
December | 12.04 | 2.90 | 9.14 | 4.61 | 27.87 | 7.50 | 0.00 | 744.00 |
Annual Sum or Average | 54.24 | 28.97 | 25.27 | 53.02 | 24.70 | 41.17 | 0.00 | 8760.00 |
Minimum of Months | 12.04 | 2.72 | 9.14 | 4.61 | 19.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.26 | 68.17 | 43.73 | 112.50 | 31.23 | 25.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.94 | 2.72 | 11.22 | 6.11 | 27.86 | 0.00 | 0.00 | 744.00 |
February | 24.94 | 8.29 | 16.66 | 17.00 | 25.56 | 25.17 | 0.00 | 672.00 |
March | 43.67 | 18.74 | 24.93 | 40.23 | 22.46 | 0.00 | 0.00 | 744.00 |
April | 69.54 | 35.42 | 34.13 | 73.05 | 19.68 | 0.00 | 0.00 | 720.00 |
May | 90.34 | 46.61 | 43.73 | 96.53 | 21.86 | 0.00 | 0.00 | 744.00 |
June | 98.99 | 58.09 | 40.90 | 106.94 | 20.09 | 0.00 | 0.00 | 720.00 |
July | 103.26 | 68.17 | 35.09 | 112.50 | 23.24 | 0.00 | 0.00 | 744.00 |
August | 82.81 | 52.68 | 30.12 | 86.31 | 25.83 | 0.00 | 0.00 | 744.00 |
September | 58.23 | 32.34 | 25.89 | 53.26 | 31.23 | 0.00 | 0.00 | 720.00 |
October | 34.37 | 16.05 | 18.32 | 27.72 | 27.11 | 0.00 | 0.00 | 744.00 |
November | 16.75 | 4.10 | 12.65 | 9.43 | 23.56 | 8.50 | 0.00 | 720.00 |
December | 12.04 | 2.90 | 9.14 | 4.61 | 27.87 | 7.50 | 0.00 | 744.00 |
Annual Sum or Average | 54.24 | 28.97 | 25.27 | 53.02 | 24.70 | 41.17 | 0.00 | 8760.00 |
Minimum of Months | 12.04 | 2.72 | 9.14 | 4.61 | 19.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.26 | 68.17 | 43.73 | 112.50 | 31.23 | 25.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.94 | 2.72 | 11.22 | 6.11 | 27.86 | 0.00 | 0.00 | 744.00 |
February | 24.94 | 8.29 | 16.66 | 17.00 | 25.56 | 25.17 | 0.00 | 672.00 |
March | 43.67 | 18.74 | 24.93 | 40.23 | 22.46 | 0.00 | 0.00 | 744.00 |
April | 69.54 | 35.42 | 34.13 | 73.05 | 19.68 | 0.00 | 0.00 | 720.00 |
May | 90.34 | 46.61 | 43.73 | 96.53 | 21.86 | 0.00 | 0.00 | 744.00 |
June | 98.99 | 58.09 | 40.90 | 106.94 | 20.09 | 0.00 | 0.00 | 720.00 |
July | 103.26 | 68.17 | 35.09 | 112.50 | 23.24 | 0.00 | 0.00 | 744.00 |
August | 82.81 | 52.68 | 30.12 | 86.31 | 25.83 | 0.00 | 0.00 | 744.00 |
September | 58.23 | 32.34 | 25.89 | 53.26 | 31.23 | 0.00 | 0.00 | 720.00 |
October | 34.37 | 16.05 | 18.32 | 27.72 | 27.11 | 0.00 | 0.00 | 744.00 |
November | 16.75 | 4.10 | 12.65 | 9.43 | 23.56 | 8.50 | 0.00 | 720.00 |
December | 12.04 | 2.90 | 9.14 | 4.61 | 27.87 | 7.50 | 0.00 | 744.00 |
Annual Sum or Average | 54.24 | 28.97 | 25.27 | 53.02 | 24.70 | 41.17 | 0.00 | 8760.00 |
Minimum of Months | 12.04 | 2.72 | 9.14 | 4.61 | 19.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.26 | 68.17 | 43.73 | 112.50 | 31.23 | 25.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.94 | 2.72 | 11.22 | 6.11 | 27.86 | 0.00 | 0.00 | 744.00 |
February | 24.94 | 8.29 | 16.66 | 17.00 | 25.56 | 25.17 | 0.00 | 672.00 |
March | 43.67 | 18.74 | 24.93 | 40.23 | 22.46 | 0.00 | 0.00 | 744.00 |
April | 69.54 | 35.42 | 34.13 | 73.05 | 19.68 | 0.00 | 0.00 | 720.00 |
May | 90.34 | 46.61 | 43.73 | 96.53 | 21.86 | 0.00 | 0.00 | 744.00 |
June | 98.99 | 58.09 | 40.90 | 106.94 | 20.09 | 0.00 | 0.00 | 720.00 |
July | 103.26 | 68.17 | 35.09 | 112.50 | 23.24 | 0.00 | 0.00 | 744.00 |
August | 82.81 | 52.68 | 30.12 | 86.31 | 25.83 | 0.00 | 0.00 | 744.00 |
September | 58.23 | 32.34 | 25.89 | 53.26 | 31.23 | 0.00 | 0.00 | 720.00 |
October | 34.37 | 16.05 | 18.32 | 27.72 | 27.11 | 0.00 | 0.00 | 744.00 |
November | 16.75 | 4.10 | 12.65 | 9.43 | 23.56 | 8.50 | 0.00 | 720.00 |
December | 12.04 | 2.90 | 9.14 | 4.61 | 27.87 | 7.50 | 0.00 | 744.00 |
Annual Sum or Average | 54.24 | 28.97 | 25.27 | 53.02 | 24.70 | 41.17 | 0.00 | 8760.00 |
Minimum of Months | 12.04 | 2.72 | 9.14 | 4.61 | 19.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.26 | 68.17 | 43.73 | 112.50 | 31.23 | 25.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.94 | 2.72 | 11.22 | 6.11 | 27.86 | 0.00 | 0.00 | 744.00 |
February | 24.94 | 8.29 | 16.66 | 17.00 | 25.56 | 25.17 | 0.00 | 672.00 |
March | 43.67 | 18.74 | 24.93 | 40.23 | 22.46 | 0.00 | 0.00 | 744.00 |
April | 69.54 | 35.42 | 34.13 | 73.05 | 19.68 | 0.00 | 0.00 | 720.00 |
May | 90.34 | 46.61 | 43.73 | 96.53 | 21.86 | 0.00 | 0.00 | 744.00 |
June | 98.99 | 58.09 | 40.90 | 106.94 | 20.09 | 0.00 | 0.00 | 720.00 |
July | 103.26 | 68.17 | 35.09 | 112.50 | 23.24 | 0.00 | 0.00 | 744.00 |
August | 82.81 | 52.68 | 30.12 | 86.31 | 25.83 | 0.00 | 0.00 | 744.00 |
September | 58.23 | 32.34 | 25.89 | 53.26 | 31.23 | 0.00 | 0.00 | 720.00 |
October | 34.37 | 16.05 | 18.32 | 27.72 | 27.11 | 0.00 | 0.00 | 744.00 |
November | 16.75 | 4.10 | 12.65 | 9.43 | 23.56 | 8.50 | 0.00 | 720.00 |
December | 12.04 | 2.90 | 9.14 | 4.61 | 27.87 | 7.50 | 0.00 | 744.00 |
Annual Sum or Average | 54.24 | 28.97 | 25.27 | 53.02 | 24.70 | 41.17 | 0.00 | 8760.00 |
Minimum of Months | 12.04 | 2.72 | 9.14 | 4.61 | 19.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.26 | 68.17 | 43.73 | 112.50 | 31.23 | 25.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.94 | 2.72 | 11.22 | 6.11 | 27.86 | 0.00 | 0.00 | 744.00 |
February | 24.94 | 8.29 | 16.66 | 17.00 | 25.56 | 25.17 | 0.00 | 672.00 |
March | 43.67 | 18.74 | 24.93 | 40.23 | 22.46 | 0.00 | 0.00 | 744.00 |
April | 69.54 | 35.42 | 34.13 | 73.05 | 19.68 | 0.00 | 0.00 | 720.00 |
May | 90.34 | 46.61 | 43.73 | 96.53 | 21.86 | 0.00 | 0.00 | 744.00 |
June | 98.99 | 58.09 | 40.90 | 106.94 | 20.09 | 0.00 | 0.00 | 720.00 |
July | 103.26 | 68.17 | 35.09 | 112.50 | 23.24 | 0.00 | 0.00 | 744.00 |
August | 82.81 | 52.68 | 30.12 | 86.31 | 25.83 | 0.00 | 0.00 | 744.00 |
September | 58.23 | 32.34 | 25.89 | 53.26 | 31.23 | 0.00 | 0.00 | 720.00 |
October | 34.37 | 16.05 | 18.32 | 27.72 | 27.11 | 0.00 | 0.00 | 744.00 |
November | 16.75 | 4.10 | 12.65 | 9.43 | 23.56 | 8.50 | 0.00 | 720.00 |
December | 12.04 | 2.90 | 9.14 | 4.61 | 27.87 | 7.50 | 0.00 | 744.00 |
Annual Sum or Average | 54.24 | 28.97 | 25.27 | 53.02 | 24.70 | 41.17 | 0.00 | 8760.00 |
Minimum of Months | 12.04 | 2.72 | 9.14 | 4.61 | 19.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.26 | 68.17 | 43.73 | 112.50 | 31.23 | 25.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.94 | 2.72 | 11.22 | 6.11 | 27.86 | 0.00 | 0.00 | 744.00 |
February | 24.94 | 8.29 | 16.66 | 17.00 | 25.56 | 25.17 | 0.00 | 672.00 |
March | 43.67 | 18.74 | 24.93 | 40.23 | 22.46 | 0.00 | 0.00 | 744.00 |
April | 69.54 | 35.42 | 34.13 | 73.05 | 19.68 | 0.00 | 0.00 | 720.00 |
May | 90.34 | 46.61 | 43.73 | 96.53 | 21.86 | 0.00 | 0.00 | 744.00 |
June | 98.99 | 58.09 | 40.90 | 106.94 | 20.09 | 0.00 | 0.00 | 720.00 |
July | 103.26 | 68.17 | 35.09 | 112.50 | 23.24 | 0.00 | 0.00 | 744.00 |
August | 82.81 | 52.68 | 30.12 | 86.31 | 25.83 | 0.00 | 0.00 | 744.00 |
September | 58.23 | 32.34 | 25.89 | 53.26 | 31.23 | 0.00 | 0.00 | 720.00 |
October | 34.37 | 16.05 | 18.32 | 27.72 | 27.11 | 0.00 | 0.00 | 744.00 |
November | 16.75 | 4.10 | 12.65 | 9.43 | 23.56 | 8.50 | 0.00 | 720.00 |
December | 12.04 | 2.90 | 9.14 | 4.61 | 27.87 | 7.50 | 0.00 | 744.00 |
Annual Sum or Average | 54.24 | 28.97 | 25.27 | 53.02 | 24.70 | 41.17 | 0.00 | 8760.00 |
Minimum of Months | 12.04 | 2.72 | 9.14 | 4.61 | 19.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.26 | 68.17 | 43.73 | 112.50 | 31.23 | 25.17 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107530E+09 | 31932813.31 | 75597140.08 | 30336726.51 | 0.363445E+09 |
February | 0.172548E+09 | 64274480.72 | 0.108273E+09 | 97637256.77 | 0.277599E+09 |
March | 0.269085E+09 | 90916379.26 | 0.178169E+09 | 0.194703E+09 | 0.241409E+09 |
April | 0.395301E+09 | 0.150836E+09 | 0.244465E+09 | 0.355931E+09 | 0.187944E+09 |
May | 0.526813E+09 | 0.214221E+09 | 0.312592E+09 | 0.506605E+09 | 0.184305E+09 |
June | 0.490142E+09 | 0.190293E+09 | 0.299849E+09 | 0.463986E+09 | 0.156266E+09 |
July | 0.626759E+09 | 0.329887E+09 | 0.296872E+09 | 0.661678E+09 | 0.166241E+09 |
August | 0.517457E+09 | 0.263931E+09 | 0.253526E+09 | 0.552642E+09 | 0.168854E+09 |
September | 0.409354E+09 | 0.196946E+09 | 0.212407E+09 | 0.394236E+09 | 0.209138E+09 |
October | 0.240883E+09 | 98546732.52 | 0.142336E+09 | 0.187660E+09 | 0.228009E+09 |
November | 0.115997E+09 | 33047661.25 | 82949087.15 | 50468086.36 | 0.270909E+09 |
December | 0.101696E+09 | 35678686.50 | 66017323.83 | 40890273.34 | 0.365237E+09 |
Annual Sum or Average | 0.397356E+10 | 0.170051E+10 | 0.227305E+10 | 0.353677E+10 | 0.281936E+10 |
Minimum of Months | 0.101696E+09 | 31932813.31 | 66017323.83 | 30336726.51 | 0.156266E+09 |
Maximum of Months | 0.626759E+09 | 0.329887E+09 | 0.312592E+09 | 0.661678E+09 | 0.365237E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107530E+09 | 31932813.31 | 75597140.08 | 30336726.51 | 0.363445E+09 |
February | 0.172548E+09 | 64274480.72 | 0.108273E+09 | 97637256.77 | 0.277599E+09 |
March | 0.269085E+09 | 90916379.26 | 0.178169E+09 | 0.194703E+09 | 0.241409E+09 |
April | 0.395301E+09 | 0.150836E+09 | 0.244465E+09 | 0.355931E+09 | 0.187944E+09 |
May | 0.526813E+09 | 0.214221E+09 | 0.312592E+09 | 0.506605E+09 | 0.184305E+09 |
June | 0.490142E+09 | 0.190293E+09 | 0.299849E+09 | 0.463986E+09 | 0.156266E+09 |
July | 0.626759E+09 | 0.329887E+09 | 0.296872E+09 | 0.661678E+09 | 0.166241E+09 |
August | 0.517457E+09 | 0.263931E+09 | 0.253526E+09 | 0.552642E+09 | 0.168854E+09 |
September | 0.409354E+09 | 0.196946E+09 | 0.212407E+09 | 0.394236E+09 | 0.209138E+09 |
October | 0.240883E+09 | 98546732.52 | 0.142336E+09 | 0.187660E+09 | 0.228009E+09 |
November | 0.115997E+09 | 33047661.25 | 82949087.15 | 50468086.36 | 0.270909E+09 |
December | 0.101696E+09 | 35678686.50 | 66017323.83 | 40890273.34 | 0.365237E+09 |
Annual Sum or Average | 0.397356E+10 | 0.170051E+10 | 0.227305E+10 | 0.353677E+10 | 0.281936E+10 |
Minimum of Months | 0.101696E+09 | 31932813.31 | 66017323.83 | 30336726.51 | 0.156266E+09 |
Maximum of Months | 0.626759E+09 | 0.329887E+09 | 0.312592E+09 | 0.661678E+09 | 0.365237E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36842037.10 | 0.00 | 36842037.10 | 751214.43 | 0.223254E+09 |
February | 51779429.29 | 0.00 | 51779429.29 | 8040757.25 | 0.172768E+09 |
March | 84474702.76 | 1613.93 | 84473088.83 | 29267101.67 | 0.145925E+09 |
April | 0.115855E+09 | 556829.82 | 0.115298E+09 | 66415175.83 | 0.110195E+09 |
May | 0.153715E+09 | 4484182.11 | 0.149231E+09 | 97947889.76 | 0.105285E+09 |
June | 0.156481E+09 | 10281295.54 | 0.146200E+09 | 99784980.50 | 86209488.14 |
July | 0.153810E+09 | 12086982.54 | 0.141723E+09 | 0.104770E+09 | 92457096.75 |
August | 0.124946E+09 | 3796729.99 | 0.121149E+09 | 92381527.36 | 96152724.56 |
September | 93576000.29 | 59143.22 | 93516857.08 | 48427079.14 | 0.124876E+09 |
October | 66218358.03 | 0.00 | 66218358.03 | 22909316.81 | 0.136536E+09 |
November | 40365490.15 | 0.00 | 40365490.15 | 4368497.39 | 0.165035E+09 |
December | 31306230.85 | 0.00 | 31306230.85 | 458788.13 | 0.221706E+09 |
Annual Sum or Average | 0.110937E+10 | 31266777.14 | 0.107810E+10 | 0.575523E+09 | 0.168040E+10 |
Minimum of Months | 31306230.85 | 0.00 | 31306230.85 | 458788.13 | 86209488.14 |
Maximum of Months | 0.156481E+09 | 12086982.54 | 0.149231E+09 | 0.104770E+09 | 0.223254E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36840747.14 | 0.00 | 36840747.14 | 751083.90 | 0.223254E+09 |
February | 51777702.37 | 0.00 | 51777702.37 | 8040098.03 | 0.172769E+09 |
March | 84471960.57 | 1613.86 | 84470346.71 | 29265091.22 | 0.145925E+09 |
April | 0.115851E+09 | 556803.72 | 0.115294E+09 | 66412041.69 | 0.110194E+09 |
May | 0.153710E+09 | 4483971.93 | 0.149226E+09 | 97943437.98 | 0.105285E+09 |
June | 0.156476E+09 | 10280813.64 | 0.146196E+09 | 99780598.04 | 86209306.05 |
July | 0.153805E+09 | 12086416.00 | 0.141719E+09 | 0.104767E+09 | 92456919.80 |
August | 0.124942E+09 | 3796552.03 | 0.121145E+09 | 92378490.75 | 96152401.95 |
September | 93573172.24 | 59140.44 | 93514031.80 | 48424757.53 | 0.124876E+09 |
October | 66216244.03 | 0.00 | 66216244.03 | 22907788.15 | 0.136535E+09 |
November | 40364087.23 | 0.00 | 40364087.23 | 4368023.18 | 0.165035E+09 |
December | 31305150.45 | 0.00 | 31305150.45 | 458727.45 | 0.221706E+09 |
Annual Sum or Average | 0.110933E+10 | 31265311.63 | 0.107807E+10 | 0.575497E+09 | 0.168040E+10 |
Minimum of Months | 31305150.45 | 0.00 | 31305150.45 | 458727.45 | 86209306.05 |
Maximum of Months | 0.156476E+09 | 12086416.00 | 0.149226E+09 | 0.104767E+09 | 0.223254E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37338545.83 | 7289164.64 | 30049381.18 | 16362242.96 | 74612114.31 |
February | 60337538.71 | 20043618.21 | 40293920.50 | 41116666.54 | 61836978.57 |
March | 0.116969E+09 | 50199886.07 | 66769444.36 | 0.107741E+09 | 60168010.61 |
April | 0.180251E+09 | 91796712.14 | 88454369.30 | 0.189358E+09 | 51007604.97 |
May | 0.241978E+09 | 0.124846E+09 | 0.117132E+09 | 0.258552E+09 | 58540380.77 |
June | 0.256573E+09 | 0.150567E+09 | 0.106006E+09 | 0.277179E+09 | 52074769.14 |
July | 0.276571E+09 | 0.182598E+09 | 93972880.80 | 0.301331E+09 | 62236969.41 |
August | 0.221787E+09 | 0.141109E+09 | 80678481.64 | 0.231163E+09 | 69183607.33 |
September | 0.150926E+09 | 83827044.47 | 67098812.38 | 0.138062E+09 | 80942912.50 |
October | 92069048.84 | 42992934.59 | 49076114.25 | 74236905.56 | 72610950.65 |
November | 43407313.17 | 10621967.01 | 32785346.16 | 24432940.85 | 61079831.19 |
December | 32255910.17 | 7771725.19 | 24484184.97 | 12350751.69 | 74643168.22 |
Annual Sum or Average | 0.171046E+10 | 0.913663E+09 | 0.796800E+09 | 0.167188E+10 | 0.778937E+09 |
Minimum of Months | 32255910.17 | 7289164.64 | 24484184.97 | 12350751.69 | 51007604.97 |
Maximum of Months | 0.276571E+09 | 0.182598E+09 | 0.117132E+09 | 0.301331E+09 | 80942912.50 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37338545.83 | 7289164.64 | 30049381.18 | 16362242.96 | 74612114.31 |
February | 60337538.71 | 20043618.21 | 40293920.50 | 41116666.54 | 61836978.57 |
March | 0.116969E+09 | 50199886.07 | 66769444.36 | 0.107741E+09 | 60168010.61 |
April | 0.180251E+09 | 91796712.14 | 88454369.30 | 0.189358E+09 | 51007604.97 |
May | 0.241978E+09 | 0.124846E+09 | 0.117132E+09 | 0.258552E+09 | 58540380.77 |
June | 0.256573E+09 | 0.150567E+09 | 0.106006E+09 | 0.277179E+09 | 52074769.14 |
July | 0.276571E+09 | 0.182598E+09 | 93972880.80 | 0.301331E+09 | 62236969.41 |
August | 0.221787E+09 | 0.141109E+09 | 80678481.64 | 0.231163E+09 | 69183607.33 |
September | 0.150926E+09 | 83827044.47 | 67098812.38 | 0.138062E+09 | 80942912.50 |
October | 92069048.84 | 42992934.59 | 49076114.25 | 74236905.56 | 72610950.65 |
November | 43407313.17 | 10621967.01 | 32785346.16 | 24432940.85 | 61079831.19 |
December | 32255910.17 | 7771725.19 | 24484184.97 | 12350751.69 | 74643168.22 |
Annual Sum or Average | 0.171046E+10 | 0.913663E+09 | 0.796800E+09 | 0.167188E+10 | 0.778937E+09 |
Minimum of Months | 32255910.17 | 7289164.64 | 24484184.97 | 12350751.69 | 51007604.97 |
Maximum of Months | 0.276571E+09 | 0.182598E+09 | 0.117132E+09 | 0.301331E+09 | 80942912.50 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37338545.83 | 7289164.64 | 30049381.18 | 16362242.96 | 74612114.31 |
February | 60337538.71 | 20043618.21 | 40293920.50 | 41116666.54 | 61836978.57 |
March | 0.116969E+09 | 50199886.07 | 66769444.36 | 0.107741E+09 | 60168010.61 |
April | 0.180251E+09 | 91796712.14 | 88454369.30 | 0.189358E+09 | 51007604.97 |
May | 0.241978E+09 | 0.124846E+09 | 0.117132E+09 | 0.258552E+09 | 58540380.77 |
June | 0.256573E+09 | 0.150567E+09 | 0.106006E+09 | 0.277179E+09 | 52074769.14 |
July | 0.276571E+09 | 0.182598E+09 | 93972880.80 | 0.301331E+09 | 62236969.41 |
August | 0.221787E+09 | 0.141109E+09 | 80678481.64 | 0.231163E+09 | 69183607.33 |
September | 0.150926E+09 | 83827044.47 | 67098812.38 | 0.138062E+09 | 80942912.50 |
October | 92069048.84 | 42992934.59 | 49076114.25 | 74236905.56 | 72610950.65 |
November | 43407313.17 | 10621967.01 | 32785346.16 | 24432940.85 | 61079831.19 |
December | 32255910.17 | 7771725.19 | 24484184.97 | 12350751.69 | 74643168.22 |
Annual Sum or Average | 0.171046E+10 | 0.913663E+09 | 0.796800E+09 | 0.167188E+10 | 0.778937E+09 |
Minimum of Months | 32255910.17 | 7289164.64 | 24484184.97 | 12350751.69 | 51007604.97 |
Maximum of Months | 0.276571E+09 | 0.182598E+09 | 0.117132E+09 | 0.301331E+09 | 80942912.50 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37338545.83 | 7289164.64 | 30049381.18 | 16362242.96 | 74612114.31 |
February | 60337538.71 | 20043618.21 | 40293920.50 | 41116666.54 | 61836978.57 |
March | 0.116969E+09 | 50199886.07 | 66769444.36 | 0.107741E+09 | 60168010.61 |
April | 0.180251E+09 | 91796712.14 | 88454369.30 | 0.189358E+09 | 51007604.97 |
May | 0.241978E+09 | 0.124846E+09 | 0.117132E+09 | 0.258552E+09 | 58540380.77 |
June | 0.256573E+09 | 0.150567E+09 | 0.106006E+09 | 0.277179E+09 | 52074769.14 |
July | 0.276571E+09 | 0.182598E+09 | 93972880.80 | 0.301331E+09 | 62236969.41 |
August | 0.221787E+09 | 0.141109E+09 | 80678481.64 | 0.231163E+09 | 69183607.33 |
September | 0.150926E+09 | 83827044.47 | 67098812.38 | 0.138062E+09 | 80942912.50 |
October | 92069048.84 | 42992934.59 | 49076114.25 | 74236905.56 | 72610950.65 |
November | 43407313.17 | 10621967.01 | 32785346.16 | 24432940.85 | 61079831.19 |
December | 32255910.17 | 7771725.19 | 24484184.97 | 12350751.69 | 74643168.22 |
Annual Sum or Average | 0.171046E+10 | 0.913663E+09 | 0.796800E+09 | 0.167188E+10 | 0.778937E+09 |
Minimum of Months | 32255910.17 | 7289164.64 | 24484184.97 | 12350751.69 | 51007604.97 |
Maximum of Months | 0.276571E+09 | 0.182598E+09 | 0.117132E+09 | 0.301331E+09 | 80942912.50 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37338545.83 | 7289164.64 | 30049381.18 | 16362242.96 | 74612114.31 |
February | 60337538.71 | 20043618.21 | 40293920.50 | 41116666.54 | 61836978.57 |
March | 0.116969E+09 | 50199886.07 | 66769444.36 | 0.107741E+09 | 60168010.61 |
April | 0.180251E+09 | 91796712.14 | 88454369.30 | 0.189358E+09 | 51007604.97 |
May | 0.241978E+09 | 0.124846E+09 | 0.117132E+09 | 0.258552E+09 | 58540380.77 |
June | 0.256573E+09 | 0.150567E+09 | 0.106006E+09 | 0.277179E+09 | 52074769.14 |
July | 0.276571E+09 | 0.182598E+09 | 93972880.80 | 0.301331E+09 | 62236969.41 |
August | 0.221787E+09 | 0.141109E+09 | 80678481.64 | 0.231163E+09 | 69183607.33 |
September | 0.150926E+09 | 83827044.47 | 67098812.38 | 0.138062E+09 | 80942912.50 |
October | 92069048.84 | 42992934.59 | 49076114.25 | 74236905.56 | 72610950.65 |
November | 43407313.17 | 10621967.01 | 32785346.16 | 24432940.85 | 61079831.19 |
December | 32255910.17 | 7771725.19 | 24484184.97 | 12350751.69 | 74643168.22 |
Annual Sum or Average | 0.171046E+10 | 0.913663E+09 | 0.796800E+09 | 0.167188E+10 | 0.778937E+09 |
Minimum of Months | 32255910.17 | 7289164.64 | 24484184.97 | 12350751.69 | 51007604.97 |
Maximum of Months | 0.276571E+09 | 0.182598E+09 | 0.117132E+09 | 0.301331E+09 | 80942912.50 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37338545.83 | 7289164.64 | 30049381.18 | 16362242.96 | 74612114.31 |
February | 60337538.71 | 20043618.21 | 40293920.50 | 41116666.54 | 61836978.57 |
March | 0.116969E+09 | 50199886.07 | 66769444.36 | 0.107741E+09 | 60168010.61 |
April | 0.180251E+09 | 91796712.14 | 88454369.30 | 0.189358E+09 | 51007604.97 |
May | 0.241978E+09 | 0.124846E+09 | 0.117132E+09 | 0.258552E+09 | 58540380.77 |
June | 0.256573E+09 | 0.150567E+09 | 0.106006E+09 | 0.277179E+09 | 52074769.14 |
July | 0.276571E+09 | 0.182598E+09 | 93972880.80 | 0.301331E+09 | 62236969.41 |
August | 0.221787E+09 | 0.141109E+09 | 80678481.64 | 0.231163E+09 | 69183607.33 |
September | 0.150926E+09 | 83827044.47 | 67098812.38 | 0.138062E+09 | 80942912.50 |
October | 92069048.84 | 42992934.59 | 49076114.25 | 74236905.56 | 72610950.65 |
November | 43407313.17 | 10621967.01 | 32785346.16 | 24432940.85 | 61079831.19 |
December | 32255910.17 | 7771725.19 | 24484184.97 | 12350751.69 | 74643168.22 |
Annual Sum or Average | 0.171046E+10 | 0.913663E+09 | 0.796800E+09 | 0.167188E+10 | 0.778937E+09 |
Minimum of Months | 32255910.17 | 7289164.64 | 24484184.97 | 12350751.69 | 51007604.97 |
Maximum of Months | 0.276571E+09 | 0.182598E+09 | 0.117132E+09 | 0.301331E+09 | 80942912.50 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37338545.83 | 7289164.64 | 30049381.18 | 16362242.96 | 74612114.31 |
February | 60337538.71 | 20043618.21 | 40293920.50 | 41116666.54 | 61836978.57 |
March | 0.116969E+09 | 50199886.07 | 66769444.36 | 0.107741E+09 | 60168010.61 |
April | 0.180251E+09 | 91796712.14 | 88454369.30 | 0.189358E+09 | 51007604.97 |
May | 0.241978E+09 | 0.124846E+09 | 0.117132E+09 | 0.258552E+09 | 58540380.77 |
June | 0.256573E+09 | 0.150567E+09 | 0.106006E+09 | 0.277179E+09 | 52074769.14 |
July | 0.276571E+09 | 0.182598E+09 | 93972880.80 | 0.301331E+09 | 62236969.41 |
August | 0.221787E+09 | 0.141109E+09 | 80678481.64 | 0.231163E+09 | 69183607.33 |
September | 0.150926E+09 | 83827044.47 | 67098812.38 | 0.138062E+09 | 80942912.50 |
October | 92069048.84 | 42992934.59 | 49076114.25 | 74236905.56 | 72610950.65 |
November | 43407313.17 | 10621967.01 | 32785346.16 | 24432940.85 | 61079831.19 |
December | 32255910.17 | 7771725.19 | 24484184.97 | 12350751.69 | 74643168.22 |
Annual Sum or Average | 0.171046E+10 | 0.913663E+09 | 0.796800E+09 | 0.167188E+10 | 0.778937E+09 |
Minimum of Months | 32255910.17 | 7289164.64 | 24484184.97 | 12350751.69 | 51007604.97 |
Maximum of Months | 0.276571E+09 | 0.182598E+09 | 0.117132E+09 | 0.301331E+09 | 80942912.50 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37338545.83 | 7289164.64 | 30049381.18 | 16362242.96 | 74612114.31 |
February | 60337538.71 | 20043618.21 | 40293920.50 | 41116666.54 | 61836978.57 |
March | 0.116969E+09 | 50199886.07 | 66769444.36 | 0.107741E+09 | 60168010.61 |
April | 0.180251E+09 | 91796712.14 | 88454369.30 | 0.189358E+09 | 51007604.97 |
May | 0.241978E+09 | 0.124846E+09 | 0.117132E+09 | 0.258552E+09 | 58540380.77 |
June | 0.256573E+09 | 0.150567E+09 | 0.106006E+09 | 0.277179E+09 | 52074769.14 |
July | 0.276571E+09 | 0.182598E+09 | 93972880.80 | 0.301331E+09 | 62236969.41 |
August | 0.221787E+09 | 0.141109E+09 | 80678481.64 | 0.231163E+09 | 69183607.33 |
September | 0.150926E+09 | 83827044.47 | 67098812.38 | 0.138062E+09 | 80942912.50 |
October | 92069048.84 | 42992934.59 | 49076114.25 | 74236905.56 | 72610950.65 |
November | 43407313.17 | 10621967.01 | 32785346.16 | 24432940.85 | 61079831.19 |
December | 32255910.17 | 7771725.19 | 24484184.97 | 12350751.69 | 74643168.22 |
Annual Sum or Average | 0.171046E+10 | 0.913663E+09 | 0.796800E+09 | 0.167188E+10 | 0.778937E+09 |
Minimum of Months | 32255910.17 | 7289164.64 | 24484184.97 | 12350751.69 | 51007604.97 |
Maximum of Months | 0.276571E+09 | 0.182598E+09 | 0.117132E+09 | 0.301331E+09 | 80942912.50 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37338545.83 | 7289164.64 | 30049381.18 | 16362242.96 | 74612114.31 |
February | 60337538.71 | 20043618.21 | 40293920.50 | 41116666.54 | 61836978.57 |
March | 0.116969E+09 | 50199886.07 | 66769444.36 | 0.107741E+09 | 60168010.61 |
April | 0.180251E+09 | 91796712.14 | 88454369.30 | 0.189358E+09 | 51007604.97 |
May | 0.241978E+09 | 0.124846E+09 | 0.117132E+09 | 0.258552E+09 | 58540380.77 |
June | 0.256573E+09 | 0.150567E+09 | 0.106006E+09 | 0.277179E+09 | 52074769.14 |
July | 0.276571E+09 | 0.182598E+09 | 93972880.80 | 0.301331E+09 | 62236969.41 |
August | 0.221787E+09 | 0.141109E+09 | 80678481.64 | 0.231163E+09 | 69183607.33 |
September | 0.150926E+09 | 83827044.47 | 67098812.38 | 0.138062E+09 | 80942912.50 |
October | 92069048.84 | 42992934.59 | 49076114.25 | 74236905.56 | 72610950.65 |
November | 43407313.17 | 10621967.01 | 32785346.16 | 24432940.85 | 61079831.19 |
December | 32255910.17 | 7771725.19 | 24484184.97 | 12350751.69 | 74643168.22 |
Annual Sum or Average | 0.171046E+10 | 0.913663E+09 | 0.796800E+09 | 0.167188E+10 | 0.778937E+09 |
Minimum of Months | 32255910.17 | 7289164.64 | 24484184.97 | 12350751.69 | 51007604.97 |
Maximum of Months | 0.276571E+09 | 0.182598E+09 | 0.117132E+09 | 0.301331E+09 | 80942912.50 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37338545.83 | 7289164.64 | 30049381.18 | 16362242.96 | 74612114.31 |
February | 60337538.71 | 20043618.21 | 40293920.50 | 41116666.54 | 61836978.57 |
March | 0.116969E+09 | 50199886.07 | 66769444.36 | 0.107741E+09 | 60168010.61 |
April | 0.180251E+09 | 91796712.14 | 88454369.30 | 0.189358E+09 | 51007604.97 |
May | 0.241978E+09 | 0.124846E+09 | 0.117132E+09 | 0.258552E+09 | 58540380.77 |
June | 0.256573E+09 | 0.150567E+09 | 0.106006E+09 | 0.277179E+09 | 52074769.14 |
July | 0.276571E+09 | 0.182598E+09 | 93972880.80 | 0.301331E+09 | 62236969.41 |
August | 0.221787E+09 | 0.141109E+09 | 80678481.64 | 0.231163E+09 | 69183607.33 |
September | 0.150926E+09 | 83827044.47 | 67098812.38 | 0.138062E+09 | 80942912.50 |
October | 92069048.84 | 42992934.59 | 49076114.25 | 74236905.56 | 72610950.65 |
November | 43407313.17 | 10621967.01 | 32785346.16 | 24432940.85 | 61079831.19 |
December | 32255910.17 | 7771725.19 | 24484184.97 | 12350751.69 | 74643168.22 |
Annual Sum or Average | 0.171046E+10 | 0.913663E+09 | 0.796800E+09 | 0.167188E+10 | 0.778937E+09 |
Minimum of Months | 32255910.17 | 7289164.64 | 24484184.97 | 12350751.69 | 51007604.97 |
Maximum of Months | 0.276571E+09 | 0.182598E+09 | 0.117132E+09 | 0.301331E+09 | 80942912.50 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 18.02 | 432.91 | 107.80 | 23.84 | 83.96 | 0.00 | 0.00 |
February | 81.69 | 366.65 | 185.45 | 53.14 | 132.32 | 0.00 | 0.00 |
March | 164.27 | 286.26 | 264.01 | 67.89 | 196.12 | 0.00 | 0.00 |
April | 324.44 | 228.60 | 394.41 | 116.82 | 277.59 | 0.00 | 0.00 |
May | 450.62 | 215.43 | 508.16 | 163.31 | 344.85 | 0.00 | 0.00 |
June | 433.43 | 185.51 | 498.94 | 154.76 | 344.17 | 0.00 | 0.00 |
July | 571.52 | 192.38 | 582.86 | 255.36 | 327.50 | 0.00 | 0.00 |
August | 480.92 | 197.15 | 479.69 | 199.92 | 279.77 | 0.00 | 0.00 |
September | 339.47 | 255.64 | 388.06 | 152.01 | 236.05 | 0.00 | 0.00 |
October | 154.49 | 269.47 | 229.32 | 73.59 | 155.73 | 0.00 | 0.00 |
November | 39.07 | 333.13 | 120.65 | 25.50 | 95.15 | 0.00 | 0.00 |
December | 25.50 | 432.90 | 99.31 | 26.64 | 72.67 | 0.00 | 0.00 |
Annual Sum or Average | 258.10 | 282.67 | 322.36 | 109.83 | 212.53 | 0.00 | 0.00 |
Minimum of Months | 18.02 | 185.51 | 99.31 | 23.84 | 72.67 | 0.00 | 0.00 |
Maximum of Months | 571.52 | 432.91 | 582.86 | 255.36 | 344.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 61.09 | 278.57 | 139.41 | 27.21 | 112.19 | 0.00 | 0.00 |
February | 169.96 | 255.61 | 249.41 | 82.85 | 166.56 | 0.00 | 0.00 |
March | 402.26 | 224.64 | 436.71 | 187.42 | 249.29 | 0.00 | 0.00 |
April | 730.55 | 196.79 | 695.41 | 354.15 | 341.26 | 0.00 | 0.00 |
May | 965.32 | 218.56 | 903.44 | 466.12 | 437.32 | 0.00 | 0.00 |
June | 1069.36 | 200.91 | 989.86 | 580.89 | 408.97 | 0.00 | 0.00 |
July | 1125.04 | 232.37 | 1032.60 | 681.74 | 350.85 | 0.00 | 0.00 |
August | 863.06 | 258.30 | 828.06 | 526.84 | 301.22 | 0.00 | 0.00 |
September | 532.65 | 312.28 | 582.28 | 323.41 | 258.87 | 0.00 | 0.00 |
October | 277.17 | 271.10 | 343.75 | 160.52 | 183.23 | 0.00 | 0.00 |
November | 94.26 | 235.65 | 167.47 | 40.98 | 126.49 | 0.00 | 0.00 |
December | 46.11 | 278.69 | 120.43 | 29.02 | 91.41 | 0.00 | 0.00 |
Annual Sum or Average | 530.15 | 247.00 | 542.38 | 289.72 | 252.66 | 0.00 | 0.00 |
Minimum of Months | 46.11 | 196.79 | 120.43 | 27.21 | 91.41 | 0.00 | 0.00 |
Maximum of Months | 1125.04 | 312.28 | 1032.60 | 681.74 | 437.32 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 48277111.57 | 0.115950E+10 | 0.288743E+09 | 63865626.63 | 0.224877E+09 | 0.00 | 0.00 |
February | 0.197620E+09 | 0.887000E+09 | 0.448653E+09 | 0.128549E+09 | 0.320104E+09 | 0.00 | 0.00 |
March | 0.439994E+09 | 0.766723E+09 | 0.707117E+09 | 0.181836E+09 | 0.525281E+09 | 0.00 | 0.00 |
April | 0.840953E+09 | 0.592541E+09 | 0.102231E+10 | 0.302786E+09 | 0.719522E+09 | 0.00 | 0.00 |
May | 0.120694E+10 | 0.577020E+09 | 0.136105E+10 | 0.437411E+09 | 0.923642E+09 | 0.00 | 0.00 |
June | 0.112344E+10 | 0.480852E+09 | 0.129324E+10 | 0.401147E+09 | 0.892095E+09 | 0.00 | 0.00 |
July | 0.153076E+10 | 0.515258E+09 | 0.156113E+10 | 0.683948E+09 | 0.877185E+09 | 0.00 | 0.00 |
August | 0.128808E+10 | 0.528051E+09 | 0.128480E+10 | 0.535455E+09 | 0.749346E+09 | 0.00 | 0.00 |
September | 0.879913E+09 | 0.662617E+09 | 0.100586E+10 | 0.394011E+09 | 0.611846E+09 | 0.00 | 0.00 |
October | 0.413786E+09 | 0.721739E+09 | 0.614200E+09 | 0.197093E+09 | 0.417107E+09 | 0.00 | 0.00 |
November | 0.101270E+09 | 0.863484E+09 | 0.312723E+09 | 66095322.50 | 0.246628E+09 | 0.00 | 0.00 |
December | 68296243.32 | 0.115949E+10 | 0.266003E+09 | 71357373.01 | 0.194646E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.813933E+10 | 0.891427E+10 | 0.101658E+11 | 0.346355E+10 | 0.670228E+10 | 0.00 | 0.00 |
Minimum of Months | 48277111.57 | 0.480852E+09 | 0.266003E+09 | 63865626.63 | 0.194646E+09 | 0.00 | 0.00 |
Maximum of Months | 0.153076E+10 | 0.115950E+10 | 0.156113E+10 | 0.683948E+09 | 0.923642E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.163622E+09 | 0.746121E+09 | 0.373385E+09 | 72891646.44 | 0.300494E+09 | 0.00 | 0.00 |
February | 0.411167E+09 | 0.618370E+09 | 0.603375E+09 | 0.200436E+09 | 0.402939E+09 | 0.00 | 0.00 |
March | 0.107741E+10 | 0.601680E+09 | 0.116969E+10 | 0.501999E+09 | 0.667694E+09 | 0.00 | 0.00 |
April | 0.189358E+10 | 0.510074E+09 | 0.180251E+10 | 0.917967E+09 | 0.884544E+09 | 0.00 | 0.00 |
May | 0.258552E+10 | 0.585404E+09 | 0.241978E+10 | 0.124846E+10 | 0.117132E+10 | 0.00 | 0.00 |
June | 0.277179E+10 | 0.520747E+09 | 0.256573E+10 | 0.150567E+10 | 0.106006E+10 | 0.00 | 0.00 |
July | 0.301331E+10 | 0.622367E+09 | 0.276571E+10 | 0.182598E+10 | 0.939729E+09 | 0.00 | 0.00 |
August | 0.231163E+10 | 0.691835E+09 | 0.221787E+10 | 0.141109E+10 | 0.806785E+09 | 0.00 | 0.00 |
September | 0.138062E+10 | 0.809429E+09 | 0.150926E+10 | 0.838270E+09 | 0.670988E+09 | 0.00 | 0.00 |
October | 0.742367E+09 | 0.726109E+09 | 0.920690E+09 | 0.429929E+09 | 0.490761E+09 | 0.00 | 0.00 |
November | 0.244329E+09 | 0.610798E+09 | 0.434073E+09 | 0.106220E+09 | 0.327853E+09 | 0.00 | 0.00 |
December | 0.123507E+09 | 0.746431E+09 | 0.322559E+09 | 77717251.95 | 0.244842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.167188E+11 | 0.778937E+10 | 0.171046E+11 | 0.913663E+10 | 0.796800E+10 | 0.00 | 0.00 |
Minimum of Months | 0.123507E+09 | 0.510074E+09 | 0.322559E+09 | 72891646.44 | 0.244842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.301331E+10 | 0.809429E+09 | 0.276571E+10 | 0.182598E+10 | 0.117132E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.11 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.09 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.03 | 5.25 | 4.23 | 1.21 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.01 | 7.49 | 3.85 | 3.74 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.79 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.40 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.56 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.54 | 10.74 | 2.23 | 5.46 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.18 | 7.19 | 4.02 | 2.09 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.12 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.11 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.56 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.48 | 7.20 | 8.40 | 3.88 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.15 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.40 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.20 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.35 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.72 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.76 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.67 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.67 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.47 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.93 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.42 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.42 | 0.00 | 0.00 | 3.88 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.76 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -1.9 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.18 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.56 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.56 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.48 | 11-JAN-21:00 | 11.10 | 10.00 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 12.41 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.44 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.27 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.57 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.72 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.16 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.12 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.96 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.04 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.70 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.48 | 11.10 | 6.70 | 0.00 | 6.35 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 28.90 | 15.70 | 6.70 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.48 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.34 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.09 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.76 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.92 | 2.10 | 6.88 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.00 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.09 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.936035E+09 | -848753584.2 | 0.00 | 0.00 | 744.00 | 0.00 | -87281913.8 | 58.99 | 0.00 | 0.00 |
February | 0.863404E+09 | -785127884.8 | 0.00 | 0.00 | 672.00 | 0.00 | -78276090.6 | 58.99 | 0.00 | 0.00 |
March | 0.992534E+09 | -907299456.8 | 0.00 | 0.00 | 744.00 | 0.00 | -85234420.3 | 59.00 | 0.00 | 0.00 |
April | 0.900123E+09 | -819647717.5 | 0.00 | 0.00 | 720.00 | 0.00 | -80475133.2 | 58.99 | 0.00 | 0.00 |
May | 0.899816E+09 | -820652493.4 | 0.00 | 0.00 | 744.00 | 0.00 | -79163249.4 | 58.99 | 0.00 | 0.00 |
June | 0.860413E+09 | -786771615.6 | 0.00 | 0.00 | 720.00 | 0.00 | -73641174.3 | 58.99 | 0.00 | 0.00 |
July | 0.812804E+09 | -739274555.8 | 0.00 | 0.00 | 744.00 | 0.00 | -73529362.2 | 59.00 | 0.00 | 0.00 |
August | 0.860488E+09 | -787243501.4 | 0.00 | 0.00 | 744.00 | 0.00 | -73244221.3 | 58.99 | 0.00 | 0.00 |
September | 0.814570E+09 | -741669946.2 | 0.00 | 0.00 | 720.00 | 0.00 | -72899921.9 | 58.99 | 0.00 | 0.00 |
October | 0.849456E+09 | -767229252.4 | 0.00 | 0.00 | 744.00 | 0.00 | -82226798.4 | 58.99 | 0.00 | 0.00 |
November | 0.848925E+09 | -766214086.1 | 0.00 | 0.00 | 720.00 | 0.00 | -82710696.5 | 58.99 | 0.00 | 0.00 |
December | 0.913985E+09 | -827203198.2 | 0.00 | 0.00 | 744.00 | 0.00 | -86782170.8 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105526E+11 | -.959709E+10 | 8760.00 | -955465152.7 | 58.99 | |||||
Minimum of Months | 0.812804E+09 | -907299456.8 | 0.00 | 0.00 | 672.00 | 0.00 | -87281913.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.992534E+09 | -739274555.8 | 0.00 | 0.00 | 744.00 | 0.00 | -72899921.9 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 237.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 301.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 242.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | ||||||||||
Minimum of Months | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.584850E+10 | 24748.25 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.444601E+10 | 24748.25 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.336266E+10 | 24748.25 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.176695E+10 | 24748.25 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.396745E+09 | 24748.25 | 11-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 75258310.93 | 8423.69 | 15-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32291804.56 | 6298.12 | 28-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121668E+10 | 24748.25 | 11-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.335676E+10 | 24748.25 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.500697E+10 | 24748.25 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.255088E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.584850E+10 | 24748.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.225627E+11 | 65072.56 | 01-JAN-00:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161572E+11 | 65072.56 | 07-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.729278E+10 | 65072.56 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237845E+10 | 65072.56 | 11-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.989611E+09 | 51267.09 | 31-OCT-20:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.902008E+10 | 65072.56 | 14-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177758E+11 | 65072.56 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.761766E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.225627E+11 | 65072.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.245505E+11 | 43591.24 | 15-JAN-01:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.180016E+11 | 65095.77 | 19-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.684609E+09 | 19449.85 | 30-NOV-18:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120113E+11 | 33825.36 | 22-DEC-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.552480E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.245505E+11 | 65095.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.140493E+09 | 0.135942E+09 | 5042.87 | 27-APR-16:00 | 4836.55 | 0.00 |
May | 0.00 | 0.00 | 0.359021E+09 | 0.323928E+09 | 5775.90 | 06-MAY-13:00 | 4606.01 | 0.00 |
June | 0.00 | 0.00 | 0.782163E+09 | 0.754364E+09 | 7337.12 | 28-JUN-16:00 | 7244.93 | 0.00 |
July | 0.00 | 0.00 | 0.249846E+10 | 0.217380E+10 | 15966.20 | 31-JUL-05:01 | 11368.61 | 0.00 |
August | 0.00 | 0.00 | 0.364211E+10 | 0.315912E+10 | 16272.65 | 30-AUG-05:01 | 10425.00 | 0.00 |
September | 0.00 | 0.00 | 0.944991E+09 | 0.785480E+09 | 15516.04 | 01-SEP-05:03 | 10746.26 | 0.00 |
October | 0.00 | 0.00 | 15755197.01 | 15754995.72 | 2136.57 | 04-OCT-15:00 | 2136.57 | 0.00 |
November | 0.00 | 0.00 | 454.91 | 356.00 | 0.16 | 04-NOV-14:00 | 0.13 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.838299E+10 | 0.734839E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.364211E+10 | 0.315912E+10 | 16272.65 | 11368.61 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.161327E+09 | 0.154950E+09 | 8921.18 | 28-JUN-15:00 | 8921.18 | 0.00 |
July | 0.00 | 0.00 | 0.195355E+10 | 0.171805E+10 | 41342.16 | 27-JUL-17:21 | 30982.36 | 0.00 |
August | 0.00 | 0.00 | 0.374736E+10 | 0.330292E+10 | 40479.64 | 13-AUG-13:42 | 33438.43 | 0.00 |
September | 0.00 | 0.00 | 0.176131E+09 | 0.138565E+09 | 7516.46 | 14-SEP-14:30 | 5914.34 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.603838E+10 | 0.531448E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.374736E+10 | 0.330292E+10 | 41342.16 | 33438.43 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.306695E+09 | 0.05 | 188.85 | 01-JAN-00:03 | 0.08 |
February | 0.193973E+09 | 0.03 | 188.85 | 01-FEB-00:05 | 0.08 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 14135107.39 | 0.00 | 188.85 | 29-NOV-17:20 | 0.08 |
December | 0.221629E+09 | 0.03 | 188.85 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.736432E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.306695E+09 | 0.05 | 188.85 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112603E+10 | 0.42 | 1092.93 | 02-JAN-09:10 | 0.95 |
February | 0.103178E+10 | 0.41 | 1092.93 | 01-FEB-08:30 | 0.95 |
March | 0.119914E+10 | 0.41 | 1092.93 | 25-MAR-10:20 | 0.95 |
April | 0.110309E+10 | 0.38 | 1092.93 | 01-APR-07:40 | 0.95 |
May | 0.113160E+10 | 0.37 | 1092.93 | 01-MAY-07:00 | 0.94 |
June | 0.112584E+10 | 0.38 | 1092.93 | 01-JUN-06:05 | 0.94 |
July | 0.108627E+10 | 0.35 | 1092.93 | 01-JUL-06:40 | 0.94 |
August | 0.117835E+10 | 0.38 | 1092.93 | 01-AUG-07:10 | 0.94 |
September | 0.108337E+10 | 0.36 | 1092.93 | 01-SEP-08:30 | 0.94 |
October | 0.109631E+10 | 0.37 | 1092.93 | 02-OCT-13:20 | 0.94 |
November | 0.106443E+10 | 0.37 | 1092.93 | 01-NOV-08:20 | 0.94 |
December | 0.111505E+10 | 0.38 | 1092.93 | 01-DEC-07:10 | 0.95 |
Annual Sum or Average | 0.133413E+11 | 0.38 | |||
Minimum of Months | 0.103178E+10 | 0.35 | 1092.93 | 0.94 | |
Maximum of Months | 0.119914E+10 | 0.42 | 1092.93 | 0.95 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.265127E+10 | 0.77 | 2067.00 | 03-JAN-11:00 | 0.91 |
February | 0.233302E+10 | 0.71 | 2067.00 | 03-FEB-09:00 | 0.91 |
March | 0.243492E+10 | 0.61 | 2067.00 | 22-MAR-09:50 | 0.91 |
April | 0.212369E+10 | 0.44 | 2067.00 | 01-APR-06:20 | 0.91 |
May | 0.212818E+10 | 0.35 | 2067.00 | 01-MAY-06:10 | 0.91 |
June | 0.212818E+10 | 0.36 | 2067.00 | 21-JUN-13:10 | 0.90 |
July | 0.206418E+10 | 0.34 | 2067.00 | 08-JUL-14:20 | 0.90 |
August | 0.222869E+10 | 0.37 | 2067.00 | 09-AUG-09:00 | 0.91 |
September | 0.204633E+10 | 0.35 | 2067.00 | 09-SEP-14:40 | 0.90 |
October | 0.207798E+10 | 0.38 | 2067.00 | 02-OCT-06:05 | 0.91 |
November | 0.223110E+10 | 0.61 | 2067.00 | 02-NOV-06:30 | 0.91 |
December | 0.253651E+10 | 0.75 | 2067.00 | 07-DEC-10:10 | 0.91 |
Annual Sum or Average | 0.269840E+11 | 0.50 | |||
Minimum of Months | 0.204633E+10 | 0.34 | 2067.00 | 0.90 | |
Maximum of Months | 0.265127E+10 | 0.77 | 2067.00 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.37 | 0.00 |
February | 2.43 | 0.02 |
March | 1.24 | 0.13 |
April | 1.00 | 1.29 |
May | 2.33 | 1.83 |
June | 1.68 | 3.15 |
July | 2.19 | 1.25 |
August | 2.93 | 0.87 |
September | 1.92 | 3.15 |
October | 0.82 | 0.76 |
November | 2.86 | 0.05 |
December | 2.47 | 0.01 |
Annual Sum or Average | 24.23 | 0.96 |
Minimum of Months | 0.82 | 0.00 |
Maximum of Months | 2.93 | 3.15 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.08 | 0.00 |
June | 0.00 | 0.00 |
July | 0.72 | 0.00 |
August | 0.34 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 1.14 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.72 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.112603E+10 | 0.849149E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.103178E+10 | 0.645253E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.119914E+10 | 0.490885E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.113799E+10 | 0.257866E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.121723E+10 | 0.585692E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.131305E+10 | 0.114811E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.167894E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.204987E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.130542E+10 | 49033166.73 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.110017E+10 | 0.179340E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.106443E+10 | 0.490439E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.111505E+10 | 0.727702E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.153391E+11 | 0.371559E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.103178E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.204987E+10 | 0.849149E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.265127E+10 | 0.323985E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.233302E+10 | 0.231758E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.243492E+10 | 0.106577E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.212369E+10 | 0.348545E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.212818E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.217295E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.259899E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.326542E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.209420E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.207798E+10 | 0.146963E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.223110E+10 | 0.131343E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.253651E+10 | 0.256304E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.286482E+11 | 0.109952E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.207798E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.326542E+10 | 0.323985E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.112603E+10 | 0.00 | 0.584850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103178E+10 | 0.00 | 0.444601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119914E+10 | 0.00 | 0.336266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110309E+10 | 0.140493E+09 | 0.176695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113160E+10 | 0.359021E+09 | 0.396745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112584E+10 | 0.782163E+09 | 75258310.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108627E+10 | 0.249846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117835E+10 | 0.364211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108337E+10 | 0.944991E+09 | 32291804.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109631E+10 | 15755197.01 | 0.121668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106443E+10 | 454.91 | 0.335676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111505E+10 | 0.00 | 0.500697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133413E+11 | 0.838299E+10 | 0.255088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119914E+10 | 0.364211E+10 | 0.584850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.265127E+10 | 0.00 | 0.225627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.233302E+10 | 0.00 | 0.161572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.243492E+10 | 0.00 | 0.729278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.212369E+10 | 0.00 | 0.237845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.212818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.212818E+10 | 0.161327E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.206418E+10 | 0.195355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.222869E+10 | 0.374736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.204633E+10 | 0.176131E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.207798E+10 | 0.00 | 0.989611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223110E+10 | 0.00 | 0.902008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.253651E+10 | 0.00 | 0.177758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269840E+11 | 0.603838E+10 | 0.761766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.204633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.265127E+10 | 0.374736E+10 | 0.225627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.112603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.849149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110309E+10 | 0.00 | 0.00 | 0.00 | 34901033.62 | 0.00 | 0.257866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113160E+10 | 0.00 | 0.00 | 0.00 | 85638162.89 | 0.00 | 0.585692E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112584E+10 | 0.00 | 0.00 | 0.00 | 0.187206E+09 | 0.00 | 0.114811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108627E+10 | 0.00 | 0.00 | 0.00 | 0.592671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117835E+10 | 0.00 | 0.00 | 0.00 | 0.871522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108337E+10 | 0.00 | 0.00 | 0.00 | 0.222047E+09 | 0.00 | 49033166.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109631E+10 | 0.00 | 0.00 | 0.00 | 3850562.72 | 0.00 | 0.179340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106443E+10 | 0.00 | 0.00 | 0.00 | 112.77 | 0.00 | 0.490439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133413E+11 | 0.00 | 0.00 | 0.00 | 0.199784E+10 | 0.00 | 0.371559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.103178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119914E+10 | 0.00 | 0.00 | 0.00 | 0.871522E+09 | 0.00 | 0.849149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.265127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.233302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.243492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.212369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.212818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.212818E+10 | 0.00 | 0.00 | 0.00 | 44772065.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.206418E+10 | 0.00 | 0.00 | 0.00 | 0.534811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.222869E+10 | 0.00 | 0.00 | 0.00 | 0.103673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.204633E+10 | 0.00 | 0.00 | 0.00 | 47871141.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.207798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.253651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269840E+11 | 0.00 | 0.00 | 0.00 | 0.166419E+10 | 0.00 | 0.109952E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.204633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.265127E+10 | 0.00 | 0.00 | 0.00 | 0.103673E+10 | 0.00 | 0.323985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179544E+10 | 0.00 | 0.00 | 0.12 |
February | 58951699.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141253E+10 | 0.00 | 0.00 | 0.13 |
March | 0.287244E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115678E+10 | 0.00 | 0.00 | 0.13 |
April | 0.496110E+09 | 7455477.34 | 0.00 | 139845.33 | 26774.45 | 0.572195E+09 | 0.123915E+09 | 0.00 | 0.15 |
May | 0.660236E+09 | 9730530.02 | 0.00 | 987458.34 | 0.00 | 40030499.82 | 0.831619E+09 | 0.00 | 0.27 |
June | 0.249237E+09 | 7344834.96 | 0.00 | 2827218.27 | 0.00 | 0.00 | 0.198757E+10 | 0.00 | 0.47 |
July | 30409790.54 | 79820988.44 | 0.00 | 4624324.89 | 0.00 | 0.00 | 0.220768E+10 | 0.00 | 0.60 |
August | 22870151.96 | 0.178816E+09 | 0.00 | 4996757.65 | 0.00 | 0.00 | 0.207200E+10 | 0.00 | 0.58 |
September | 0.218079E+09 | 20447872.03 | 0.00 | 2946220.14 | 0.00 | 0.00 | 0.208858E+10 | 0.00 | 0.47 |
October | 0.614133E+09 | 0.00 | 0.00 | 254600.88 | 0.00 | 0.404563E+09 | 0.300294E+09 | 0.00 | 0.16 |
November | 0.195656E+09 | 0.00 | 0.00 | 9537.17 | 0.00 | 0.117191E+10 | 17355680.95 | 0.00 | 0.13 |
December | 10631603.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168194E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.284356E+10 | 0.303616E+09 | 0.00 | 16785962.66 | 26774.45 | 0.823538E+10 | 0.962901E+10 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.660236E+09 | 0.178816E+09 | 0.00 | 4996757.65 | 26774.45 | 0.179544E+10 | 0.220768E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.169718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287682E+10 | 0.00 | 0.00 | 0.17 |
February | 0.190835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178155E+10 | 0.00 | 0.00 | 0.18 |
March | 0.299686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516948E+09 | 0.00 | 0.00 | 0.19 |
April | 0.271038E+10 | 0.00 | 0.00 | 0.00 | 52046835.04 | 0.117176E+09 | 0.00 | 0.00 | 0.18 |
May | 0.314098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
June | 0.292502E+10 | 3838373.84 | 0.00 | 422121.93 | 104976.52 | 0.00 | 0.324836E+09 | 0.00 | 0.22 |
July | 0.186517E+10 | 93873239.93 | 0.00 | 2628520.47 | 0.00 | 0.00 | 0.146683E+10 | 0.00 | 0.28 |
August | 0.189600E+10 | 0.269044E+09 | 0.00 | 2118892.70 | 0.00 | 0.00 | 0.943346E+09 | 0.00 | 0.28 |
September | 0.297302E+10 | 0.00 | 0.00 | 783309.60 | 0.00 | 0.00 | 0.546044E+09 | 0.00 | 0.22 |
October | 0.278857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62379814.87 | 0.00 | 0.00 | 0.18 |
November | 0.232253E+10 | 0.00 | 0.00 | 0.00 | 296978.90 | 0.951909E+09 | 0.00 | 0.00 | 0.17 |
December | 0.202966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214978E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.292537E+11 | 0.366756E+09 | 0.00 | 5952844.70 | 52448790.46 | 0.845656E+10 | 0.328105E+10 | 0.00 | 0.20 |
Minimum of Months | 0.169718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.314098E+10 | 0.269044E+09 | 0.00 | 2628520.47 | 52046835.04 | 0.287682E+10 | 0.146683E+10 | 0.00 | 0.28 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |