Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2020-06-03 19:11:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 903.80 | 186.92 | 186.92 |
Net Site Energy | 903.80 | 186.92 | 186.92 |
Total Source Energy | 2802.47 | 579.61 | 579.61 |
Net Source Energy | 2802.47 | 579.61 | 579.61 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 28.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 63.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 99.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 72.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.26 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 875.06 | 28.73 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 28.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 63.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 99.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 12.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 60.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.26 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 119.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 33.18 | 5.94 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 180.98 | 5.94 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 119.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 33.18 | 5.94 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 180.98 | 5.94 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 875.063 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 875.063 | 100.00 |
Total On-Site and Utility Electric Sources | 875.063 | 100.00 |
Total Electricity End Uses | 875.063 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 21.83 |
Time Setpoint Not Met During Occupied Cooling | 16.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 858.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.6337 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.5069 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.5069 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-JUN-14:39 | 28-JAN-06:10 | - | - | - | 15-AUG-11:30 |
Heating | 0.00 | 47402.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 19012.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7077.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1705.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 73096.56 | 47402.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 47402.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 19012.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4771.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1705.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 31.15 | 0.00 | 0.00 | 0.00 |
Cooling | 200.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1507.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 314.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 230.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 76.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2771.33 | 31.15 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 6.44 | 0.00 | 0.00 | 0.00 |
Cooling | 41.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 47.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 573.16 | 6.44 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 6.44 | 0.00 | 0.00 | 0.00 |
Cooling | 41.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 47.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 573.16 | 6.44 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.23 |
ZONE2 FINE STORAGE DIRECT AIR | 3.08 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 1.70 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 1.70 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 61375.72 |
PSZ-OFFICE HEATING COIL | 27326.57 |
PSZ-FINE STORAGE HEATING COIL | 88151.95 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 61375.72 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.00 | 1.00 | 1.23 |
PSZ-FINE STORAGE | 3.08 | 3.08 | 3.08 | 3.08 | 3.08 | 3.08 | 1.00 | 1.00 | 3.08 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.23 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 3.08 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.23 | 1.23 | 1.23 | 1.23 | 20485.11 | 27326.57 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 3.08 | 3.08 | 3.08 | 3.08 | 64437.64 | 88151.95 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.23 | 0.616250 | 1.23 | 20402.25 | 20485.11 | 10242.56 | 20485.11 | 0.797168 | 0.797170 | 0.797170 | 0.797170 |
PSZ-FINE STORAGE COOLING COIL | 3.08 | 1.54 | 3.08 | 58480.83 | 64437.64 | 32218.82 | 64437.64 | 0.721514 | 0.721510 | 0.721510 | 0.721510 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.23 | 1405.19 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.08 | 3366.62 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.634 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.707 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.507 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.507 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.507 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.066 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2518.900 | 10.634 | 503.780 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2518.900 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11853.648 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11853.648 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27263.390 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27263.390 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3263 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3263 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.5084 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.5084 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.5084 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.065 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.065 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.867 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.867 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.867 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.38866262E-07 | 0.77198350E-12 | 0.86409618E-13 | 0.0000000 |
2 | 1 | -5.2160226 | 0.42725752E-04 | -0.49098391E-04 | 0.74579932E-08 |
3 | 0 | 5.5423254 | 0.32626013 | 0.32635195 | |
4 | 2 | 0.38866262E-07 | 0.77198350E-12 | 0.86409618E-13 | 0.0000000 |
5 | 1 | -5.2160226 | 0.42725752E-04 | -0.49098391E-04 | 0.74579932E-08 |
6 | 0 | 5.5423254 | 0.32626013 | 0.32635195 | |
7 | 4 | 0.77647315E-12 | 0.13408001E-15 | -0.22253071E-14 | 0.11703322E-15 |
8 | 3 | -0.38306226E-03 | 0.35631809E-06 | -0.55549669E-04 | 0.14899307E-12 |
9 | 2 | 1.7356375 | 0.78038605E-02 | 1.1374847 | -0.73439249E-04 |
10 | 1 | -7.1338263 | 0.20239632 | -17.079215 | 0.33264924 |
11 | 0 | 5.7379043 | 0.12913194 | 16.281118 | |
12 | 4 | 0.77647315E-12 | 0.13408001E-15 | -0.22253071E-14 | 0.11703322E-15 |
13 | 3 | -0.38306226E-03 | 0.35631809E-06 | -0.55549669E-04 | 0.14899307E-12 |
14 | 2 | 1.7356375 | 0.78038605E-02 | 1.1374847 | -0.73439249E-04 |
15 | 1 | -7.1338263 | 0.20239632 | -17.079215 | 0.33264924 |
16 | 0 | 5.7379043 | 0.12913194 | 16.281118 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.22253071E-14 | 0.13408001E-15 | 0.77647315E-12 | 0.11703322E-15 |
85 | 3 | -0.55549669E-04 | 0.35631809E-06 | -0.38306226E-03 | 0.14899307E-12 |
86 | 2 | 1.1374847 | 0.78038605E-02 | 1.7356375 | -0.73439249E-04 |
87 | 1 | -17.079215 | 0.20239632 | -7.1338263 | 0.33264924 |
88 | 0 | 16.281118 | 0.12913194 | 5.7379043 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.63_SHGC_0.25 | 28 | 1 | VerySmooth | 3.582 | 0.253 | 0.153 | 0.250 |
2 | SKYLIGHT_U_0.65_SHGC_0.35 | 29 | 1 | VerySmooth | 3.695 | 0.347 | 0.243 | 0.351 |
3 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 30 | 1 | VerySmooth | 3.695 | 0.347 | 0.243 | 0.351 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.15304 | 0.57918 | 0.57918 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.81224E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.24267 | 0.45800 | 0.45800 | 0.35000 | 0.14371 | 0.19477 | 0.00000 | 0.84000 | 0.84000 | 1.96142E-002 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.24267 | 0.45800 | 0.45800 | 0.35000 | 0.14371 | 0.19477 | 0.00000 | 0.84000 | 0.84000 | 1.96142E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10827.81799 | 12993.38158 | 1.02708 | 1.23250 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 36.28000 | 6.82376E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 8814.38719 | 10577.26462 | 0.28524 | 0.34229 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20000 | 2.80840E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 34668.21172 | 41601.85406 | 2.56327 | 3.07592 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 36.28000 | 6.82376E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 26733.12248 | 32079.74698 | 0.72883 | 0.87460 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10000 | 6.82375E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 51146.43569 | 61375.72283 | 1.41994 | 1.70393 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 16723.93 | 1.23250 | 1.23250 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 9624.33 | 0.34229 | 0.34229 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 52432.37 | 3.07592 | 3.07592 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 31685.51 | 0.87460 | 0.87460 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.23250 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.07592 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.70393 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.70393 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 61375.72431 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 61375.72283 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.23250 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.23250 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.23250 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.23250 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.23250 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.23250 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.07592 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.07592 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.07592 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.07592 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.07592 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.07592 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.23250 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.07592 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.23250 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.23250 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.23250 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.23250 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.23250 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.23250 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61625 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.23250 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 20402.25128 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 20485.11000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10242.55500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 20485.11000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79717 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79717 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79717 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79717 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20485.11000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27326.57487 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.23250 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1405.18545 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 27326.57487 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.07592 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.07592 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.07592 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.07592 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.07592 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.07592 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.53796 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.07592 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 58480.83078 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 64437.64000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 32218.82000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 64437.64000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72151 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72151 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72151 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72151 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 64437.64000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 88151.94863 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.07592 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3366.61586 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 88151.94863 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 19528.7 | 10.09 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 62048.7 | 13.03 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 12 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.3009358652E-002 | 2.9476595576E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1280999685 | 0.1410700044 | Pass | Pass | 9.5559030524E-002 | 0.7310673591 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 4.7092869160E-002 | 3.4164143215E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.472 | 0.508 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.472 | 0.508 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.472 | 0.508 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.472 | 0.508 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.472 | 0.508 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.472 | 0.508 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.472 | 0.508 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.312 | 0.326 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.472 | 0.508 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.472 | 0.508 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.472 | 0.508 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.312 | 0.326 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.63_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.582 | 0.253 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.63_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.582 | 0.253 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.63_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.582 | 0.253 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.63_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.582 | 0.253 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.634 | 0.296 | 0.296 | ||||||||||||
North Total or Average | 6.51 | 3.582 | 0.253 | 0.250 | ||||||||||||
Non-North Total or Average | 26.02 | 3.647 | 0.307 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.6337 | 236.88 | 2518.90 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.62 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.5069 | 1393.41 | 11853.65 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 135.00 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.5069 | 3204.84 | 27263.39 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 310.50 |
Interior Lighting Total | 8.6111 | 4835.13 | 41635.94 | 476.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 6311.00 | AstronomicalClock | - | 83.77 | 83.77 | 99.24 | |
Exterior Lighting Total | 6311.00 | 99.24 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20485.11 | 16330.12 | 4154.99 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 64437.64 | 46492.40 | 17945.24 | 0.72 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 19528.7 | 10.09 | ||||
PSZ-FINE STORAGE COOLING COIL | 62048.7 | 13.03 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 61375.72 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 27326.57 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 88151.95 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.70 | 158.31 | 92.91 | 1.00 | 3.69 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.23 | 1405.19 | 1140.11 | 1.00 | 1.32 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 3.08 | 3366.62 | 1094.51 | 1.00 | 1.23 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10827.82 | 12993.38 | 54.85 | 1.027 | 1.233 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00807 | 36.28 | 0.00682 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 34668.21 | 41601.85 | 29.86 | 2.563 | 3.076 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 26.70 | 26.70 | 0.00780 | 36.28 | 0.00682 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00436 | 38.10 | 0.00682 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8814.39 | 10577.26 | 44.65 | 0.285 | 0.342 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00771 | -5.20 | 0.00281 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 26733.12 | 32079.75 | 23.02 | 0.729 | 0.875 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15.56 | 15.56 | 0.00636 | -5.20 | 0.00281 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 51146.44 | 61375.72 | 19.15 | 1.420 | 1.704 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00881 | -5.20 | 0.00281 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.23 | 1.23 | 0.34 | 0.34 | 1.2325 | 1.2325 | 1.2325 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.08 | 3.08 | 0.87 | 0.87 | 3.0759 | 3.0759 | 3.0759 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 61375.724 | 61375.724 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 61375.72 | 61375.72 | 1.703931 | 1.28 | 1.28 | 0.00537070 | 43.33 | 25.24 | 0.01600000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 10.00 | 0.00881312 | 100.0000 | 61375.72 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 20485.110 | 0.000 | 1.232500 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 20485.11 | 20485.11 | 1.232500 | 24.94 | 14.79 | 0.00796995 | 12.00 | 10.00 | 0.00800000 | 36.45 | 0.00682375 | 17.60 | 8.2990 | 23.90 | 0.00807285 | 37.9422 | 10817.63 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 27326.575 | 27326.575 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 27326.57 | 27326.57 | 1.232500 | 13.21 | 8.71 | 0.00624381 | 40.00 | 19.50 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 8.2990 | 21.10 | 0.00770790 | 42.9731 | 8814.39 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 64437.640 | 0.000 | 3.075920 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 64437.64 | 64437.64 | 3.075920 | 28.28 | 15.74 | 0.00775774 | 12.00 | 10.00 | 0.00800000 | 38.10 | 0.00682375 | 18.10 | 13.8077 | 26.70 | 0.00779677 | 31.0345 | 34595.03 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 88151.949 | 88151.949 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 88151.95 | 88151.95 | 3.075924 | 5.48 | 3.28 | 0.00463518 | 40.00 | 19.50 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 13.8076 | 15.56 | 0.00635976 | 50.3184 | 26733.12 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 61375.724 | 61375.724 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.0443 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 1.703931 | 1.77946950 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 61375.72 | 61375.72 | 1.0000 | 1.77946950 | 1.703931 | 1.28 | 1.28 | 0.00537070 | 14734.9 | 43.33 | 25.24 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61375.72 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 10.00 | 0.00881312 | 10.00 | 0.00881312 | 100.0000 | 61375.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20485.110 | 0.000 | 1.232500 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6557 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 20485.11 | 20485.11 | 1.0000 | 1.28713886 | 1.232500 | 24.94 | 14.79 | 0.00796995 | 45365.1 | 12.00 | 10.00 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20485.11 | 36.45 | 0.00682375 | 17.60 | 0.10228487 | 8.2990 | 23.90 | 0.00807379 | 23.90 | 0.00807285 | 37.9422 | 10817.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27326.575 | 27326.575 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.232500 | 1.28713887 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 27326.57 | 27326.57 | 1.0000 | 1.28713887 | 1.232500 | 13.21 | 8.71 | 0.00624381 | 29039.0 | 40.00 | 19.50 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27326.57 | -5.20 | 0.00280840 | -5.20 | 0.10228487 | 8.2990 | 21.05 | 0.00770790 | 21.10 | 0.00770790 | 42.9731 | 8814.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 64437.640 | 0.000 | 3.075920 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2612 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 64437.64 | 64437.64 | 1.0000 | 3.21228086 | 3.075920 | 28.28 | 15.74 | 0.00775774 | 48224.0 | 12.00 | 10.00 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 64437.64 | 38.10 | 0.00682375 | 18.10 | 0.42471267 | 13.8077 | 26.70 | 0.00790772 | 26.70 | 0.00779677 | 31.0345 | 34595.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 88151.949 | 88151.949 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.075924 | 3.21228517 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 88151.95 | 88151.95 | 1.0000 | 3.21228517 | 3.075924 | 5.48 | 3.28 | 0.00463518 | 17143.0 | 40.00 | 19.50 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 88151.95 | -5.20 | 0.00280840 | -5.20 | 0.42471267 | 13.8076 | 15.56 | 0.00635976 | 15.56 | 0.00635976 | 50.3184 | 26733.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE OA CONTROLLER | DifferentialDryBulb | 0.10 | 1.23 | - | |||
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 3.08 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2238.83 | 1890.50 | 858.83 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2238.83 | 1890.50 | 858.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 21.83 | 17.67 | 21.83 | 16.67 |
ZONE2 FINE STORAGE | 64.83 | 131.33 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 83.83 | 149.00 | 21.83 | 16.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.906 | 0.387 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 875.06 | 5421.86 | 01-JAN-07:20 | 73096.56 | 15-JUN-14:40 |
Electricity:Building | 627.64 | 4938.86 | 01-JAN-00:10 | 47606.95 | 21-APR-14:10 |
Electricity:Zone:ZONE1 OFFICE | 62.57 | 1027.15 | 01-JAN-00:10 | 3852.05 | 02-JAN-08:10 |
InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.62 | 453.40 | 01-JAN-00:10 | 1939.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 430.07 | 2726.34 | 01-JAN-00:10 | 33679.30 | 21-APR-14:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 310.51 | 2726.34 | 01-JAN-00:10 | 23173.88 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 24.26 | 483.00 | 12-JAN-06:10 | 1974.05 | 31-JAN-12:40 |
WaterSystems:Electricity | 24.26 | 483.00 | 12-JAN-06:10 | 1974.05 | 31-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 24.26 | 483.00 | 12-JAN-06:10 | 1974.05 | 31-JAN-12:40 |
Fans:Electricity | 72.71 | 0.00 | 01-JAN-00:10 | 7077.10 | 12-MAY-13:50 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 12.23 | 0.00 | 01-JAN-00:10 | 2305.29 | 11-MAY-14:50 |
Ventilation (simple):Fans:Electricity | 12.23 | 0.00 | 01-JAN-00:10 | 2305.29 | 11-MAY-14:50 |
ElectricityPurchased:Facility | 875.06 | 5421.86 | 01-JAN-07:20 | 73096.56 | 15-JUN-14:40 |
ElectricityPurchased:Plant | 875.06 | 5421.86 | 01-JAN-07:20 | 73096.56 | 15-JUN-14:40 |
Cogeneration:ElectricityPurchased | 875.06 | 5421.86 | 01-JAN-07:20 | 73096.56 | 15-JUN-14:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 875.06 | 5421.86 | 01-JAN-07:20 | 73096.56 | 15-JUN-14:40 |
ElectricityNet:Plant | 875.06 | 5421.86 | 01-JAN-07:20 | 73096.56 | 15-JUN-14:40 |
Cogeneration:ElectricityNet | 875.06 | 5421.86 | 01-JAN-07:20 | 73096.56 | 15-JUN-14:40 |
Electricity:HVAC | 123.93 | 0.00 | 01-JAN-00:10 | 26079.44 | 15-JUN-15:10 |
General:Fans:Electricity | 60.48 | 0.00 | 01-JAN-00:10 | 4771.80 | 02-JAN-07:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 63.45 | 0.00 | 01-JAN-00:10 | 21307.64 | 15-JUN-15:10 |
ExteriorLights:Electricity | 99.24 | 0.00 | 01-JAN-07:20 | 6311.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 99.24 | 0.00 | 01-JAN-07:20 | 6311.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 28.73 | 0.00 | 01-JAN-00:10 | 47402.37 | 28-JAN-06:10 |
Gas:HVAC | 28.73 | 0.00 | 01-JAN-00:10 | 47402.37 | 28-JAN-06:10 |
Heating:Gas | 28.73 | 0.00 | 01-JAN-00:10 | 47402.37 | 28-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-AUG-11:30 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-AUG-11:30 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-AUG-11:30 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-AUG-11:30 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-AUG-11:30 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-AUG-11:30 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-AUG-11:30 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 15-AUG-11:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 428.05 | 0.00 | 01-JAN-00:10 | 111027.66 | 15-JUN-16:10 |
EnergyTransfer:Building | 199.19 | 0.00 | 01-JAN-00:10 | 49914.33 | 15-JUN-16:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 56.46 | 0.00 | 01-JAN-00:10 | 15161.17 | 02-FEB-07:10 |
Heating:EnergyTransfer | 26.35 | 0.00 | 01-JAN-00:10 | 35951.80 | 27-DEC-06:30 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 8.23 | 0.00 | 01-JAN-00:10 | 15161.17 | 02-FEB-07:10 |
Cooling:EnergyTransfer | 172.84 | 0.00 | 01-JAN-00:10 | 49914.33 | 15-JUN-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 48.23 | 0.00 | 01-JAN-00:10 | 13014.95 | 07-AUG-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 142.74 | 0.00 | 01-JAN-00:10 | 38655.30 | 15-JUN-15:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 18.12 | 0.00 | 01-JAN-00:10 | 30534.95 | 09-FEB-01:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 124.62 | 0.00 | 01-JAN-00:10 | 38655.30 | 15-JUN-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 228.86 | 0.00 | 01-JAN-00:10 | 61113.33 | 15-JUN-16:10 |
HeatingCoils:EnergyTransfer | 19.49 | 0.00 | 01-JAN-00:10 | 35197.50 | 27-DEC-06:30 |
CoolingCoils:EnergyTransfer | 209.36 | 0.00 | 01-JAN-00:10 | 61113.33 | 15-JUN-16:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 8.232 | -48.224 | 0.000 | 0.000 | 3.721 | 30.619 | 31.946 | 10.901 | 0.000 | 3.023 | 0.000 | 0.000 | -8.901 | 0.000 | -12.095 | -19.222 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 18.118 | -124.612 | 0.000 | 0.000 | 0.000 | 135.003 | 0.000 | 0.000 | 0.000 | 10.785 | 28.004 | 0.000 | 0.000 | 0.000 | -67.298 | -0.003 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 310.507 | 107.336 | 28.068 | 0.000 | 28.686 | 0.015 | 0.000 | -10.849 | 0.000 | -442.240 | -21.508 |
Total Facility | 0.000 | 0.000 | 26.350 | -172.836 | 0.000 | 0.000 | 3.721 | 476.129 | 139.282 | 38.969 | 0.000 | 42.494 | 28.019 | 0.000 | -19.749 | 0.000 | -521.634 | -40.733 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | -27872.93 | 0.00 | 0.00 | 33.68 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 27705.22 | 0.00 | -850.64 | 0.00 | -168.42 | 0.00 |
ZONE2 FINE STORAGE | 11-SEP-19:11 | 0.00 | 0.00 | 0.00 | -63013.36 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 62514.80 | 0.00 | -0.00 | 0.00 | -686.80 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-SEP-18:01 | 0.00 | 0.00 | 0.00 | -70777.07 | 0.00 | 0.00 | 0.00 | 4365.11 | 573.75 | 309.92 | 0.00 | 498.79 | 125503.89 | 0.00 | -242.21 | 0.00 | -60232.18 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 02-MAR-06:01 | 0.00 | 0.00 | 27720.58 | 0.00 | 0.00 | 0.00 | 56.82 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -980.83 | 0.00 | -1352.32 | -26597.35 |
ZONE2 FINE STORAGE | 28-JAN-06:22 | 0.00 | 0.00 | 89564.14 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -10754.87 | -79994.64 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-MAR-06:01 | 0.00 | 0.00 | 116543.97 | 0.00 | 0.00 | 0.00 | 56.82 | 4491.05 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1916.77 | 0.00 | -26720.74 | -95078.12 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2325 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.2325 | 0.0830 | 1.0000 | 0.1023 | 0.0830 | ||
PSZ-FINE STORAGE | 3.0759 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 3.0759 | 0.1381 | 1.0000 | 0.4247 | 0.1381 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2325 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.2325 | 1.0000 | 1.0000 | 0.1023 | 0.0830 | ||
PSZ-FINE STORAGE | 3.0759 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 3.0759 | 1.0000 | 1.0000 | 0.4247 | 0.1381 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.2325 | 1.2325 | 1.2325 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.0759 | 3.0759 | 3.0759 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2325 | 1.2325 | 1.2325 | 1.2325 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.0759 | 3.0759 | 3.0759 | 3.0759 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.2325 | 1.2325 | 1.2325 | 0.1023 | 0.2988 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.0759 | 3.0759 | 3.0759 | 0.4247 | 0.4856 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2325 | 1.2325 | 1.2325 | 1.2325 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.0759 | 3.0759 | 3.0759 | 3.0759 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 21.83 |
Number of hours cooling loads not met | 16.67 |
Number of hours not met | 38.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 28.73 | 47402.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 63.45 | 21307.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 476.13 | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 99.24 | 6311.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 12.23 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 60.48 | 4771.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.26 | 1974.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 875.06 |
Natural Gas | 0.00 | 28.73 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 903.80 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 98.47 |
Space Heating | 0.00 |
Space Cooling | 13.12 |
Fans (All) | 15.04 |
Service Water Heating | 5.02 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 180.98 |
Subtotal | 180.98 |
Natural Gas [MJ/m2] | |
Space Heating | 5.94 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 5.94 |
Subtotal | 5.94 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 52.68 |
Space Heating | 3.18 |
Space Cooling | 7.02 |
Fans (All) | 8.04 |
Service Water Heating | 2.68 |
Receptacle Equipment | 15.41 |
Miscellaneous | 10.98 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.905722E+10 |
February | 0.000 | 0.530641E+10 |
March | 0.000 | 0.194754E+10 |
April | 0.000 | 0.620783E+08 |
May | 0.000 | 365398.782 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.144776E+10 |
December | 0.000 | 0.109124E+11 |
Annual Sum or Average | 0.287337E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.109124E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.905722E+10 |
February | 0.000 | 0.530641E+10 |
March | 0.000 | 0.194754E+10 |
April | 0.000 | 0.620783E+08 |
May | 0.000 | 365398.782 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.144776E+10 |
December | 0.000 | 0.109124E+11 |
Annual Sum or Average | 0.287337E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.109124E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.905722E+10 |
February | 0.000 | 0.530641E+10 |
March | 0.000 | 0.194754E+10 |
April | 0.000 | 0.620783E+08 |
May | 0.000 | 365398.782 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.144776E+10 |
December | 0.000 | 0.109124E+11 |
Annual Sum or Average | 0.287337E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.109124E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.905722E+10 |
February | 0.000 | 0.530641E+10 |
March | 0.000 | 0.194754E+10 |
April | 0.000 | 0.620783E+08 |
May | 0.000 | 365398.782 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.144776E+10 |
December | 0.000 | 0.109124E+11 |
Annual Sum or Average | 0.287337E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.109124E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.905722E+10 |
February | 0.000 | 0.530641E+10 |
March | 0.000 | 0.194754E+10 |
April | 0.000 | 0.620783E+08 |
May | 0.000 | 365398.782 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.144776E+10 |
December | 0.000 | 0.109124E+11 |
Annual Sum or Average | 0.287337E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.109124E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.905722E+10 |
February | 0.000 | 0.530641E+10 |
March | 0.000 | 0.194754E+10 |
April | 0.000 | 0.620783E+08 |
May | 0.000 | 365398.782 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.144776E+10 |
December | 0.000 | 0.109124E+11 |
Annual Sum or Average | 0.287337E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.109124E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.905722E+10 |
February | 0.000 | 0.530641E+10 |
March | 0.000 | 0.194754E+10 |
April | 0.000 | 0.620783E+08 |
May | 0.000 | 365398.782 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.144776E+10 |
December | 0.000 | 0.109124E+11 |
Annual Sum or Average | 0.287337E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.109124E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.905722E+10 |
February | 0.000 | 0.530641E+10 |
March | 0.000 | 0.194754E+10 |
April | 0.000 | 0.620783E+08 |
May | 0.000 | 365398.782 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.144776E+10 |
December | 0.000 | 0.109124E+11 |
Annual Sum or Average | 0.287337E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.109124E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.905722E+10 |
February | 0.000 | 0.530641E+10 |
March | 0.000 | 0.194754E+10 |
April | 0.000 | 0.620783E+08 |
May | 0.000 | 365398.782 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.144776E+10 |
December | 0.000 | 0.109124E+11 |
Annual Sum or Average | 0.287337E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.109124E+11 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15269334.74 | 945.56 | 12-JAN-15:40 | 18.90 | 10.10 | 0.208762E+09 | 301.59 | 03-JAN-16:00 | 20.60 | 6.82 |
February | 95003537.33 | 2105.87 | 23-FEB-14:40 | 21.47 | 7.27 | 0.199899E+09 | 301.59 | 25-FEB-16:30 | 14.40 | 4.96 |
March | 0.621896E+09 | 3583.67 | 16-MAR-15:50 | 22.30 | 8.40 | 0.249391E+09 | 301.59 | 18-MAR-15:09 | 20.68 | 8.59 |
April | 0.323930E+10 | 24445.24 | 28-APR-05:03 | 14.22 | 8.84 | 0.246993E+09 | 301.61 | 25-APR-14:00 | 22.20 | 12.41 |
May | 0.629837E+10 | 27807.38 | 17-MAY-05:01 | 14.08 | 5.17 | 0.258775E+09 | 301.62 | 19-MAY-07:40 | 23.17 | 14.68 |
June | 0.839615E+10 | 27298.02 | 13-JUN-05:01 | 15.18 | 4.56 | 0.258957E+09 | 301.61 | 19-JUN-08:00 | 27.20 | 17.86 |
July | 0.833997E+10 | 21219.97 | 11-JUL-05:01 | 21.70 | 15.04 | 0.249078E+09 | 301.69 | 08-JUL-14:50 | 22.25 | 19.21 |
August | 0.855475E+10 | 23646.69 | 23-AUG-05:01 | 20.00 | 11.76 | 0.268964E+09 | 301.63 | 24-AUG-07:30 | 23.05 | 16.43 |
September | 0.725877E+10 | 27876.40 | 30-SEP-05:02 | 9.72 | 6.49 | 0.249039E+09 | 301.67 | 23-SEP-15:50 | 20.88 | 18.63 |
October | 0.435955E+10 | 25756.02 | 20-OCT-05:03 | 11.60 | 7.27 | 0.248399E+09 | 301.61 | 23-OCT-10:09 | 20.87 | 13.60 |
November | 0.103145E+10 | 4883.48 | 03-NOV-16:00 | 23.90 | 13.43 | 0.225463E+09 | 301.59 | 03-NOV-12:00 | 21.70 | 13.54 |
December | 14786809.26 | 844.78 | 16-DEC-16:00 | 15.00 | 4.15 | 0.209501E+09 | 301.58 | 23-DEC-16:00 | 14.40 | 5.03 |
Annual Sum or Average | 0.482253E+11 | 0.287322E+10 | ||||||||
Minimum of Months | 14786809.26 | 844.78 | 9.72 | 4.15 | 0.199899E+09 | 301.58 | 14.40 | 4.96 | ||
Maximum of Months | 0.855475E+10 | 27876.40 | 23.90 | 15.04 | 0.268964E+09 | 301.69 | 27.20 | 19.21 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.577580E+09 | 6524.41 | 14-JAN-07:10 | 8.80 | 2.51 | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 3.91 |
February | 0.445206E+09 | 7006.24 | 21-FEB-07:10 | 4.68 | -0.0 | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 | 1.83 |
March | 0.465408E+09 | 7813.51 | 06-MAR-07:10 | 6.57 | 1.52 | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.39 |
April | 0.391601E+10 | 62092.11 | 30-APR-09:51 | 22.20 | 13.27 | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.38 |
May | 0.150373E+11 | 61647.08 | 21-MAY-08:31 | 23.90 | 10.58 | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.38 |
June | 0.274783E+11 | 59970.97 | 11-JUN-07:51 | 24.40 | 10.31 | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 | 11.53 |
July | 0.272878E+11 | 55784.69 | 16-JUL-03:01 | 25.50 | 15.41 | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 | 17.05 |
August | 0.247854E+11 | 59099.24 | 27-AUG-23:11 | 25.37 | 14.56 | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.10 |
September | 0.177970E+11 | 63012.37 | 11-SEP-19:11 | 23.30 | 11.87 | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.17 |
October | 0.549360E+10 | 62207.03 | 01-OCT-09:31 | 23.67 | 13.33 | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.65 |
November | 0.603224E+09 | 7578.37 | 22-NOV-07:10 | 5.97 | 0.46 | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.63 |
December | 0.730435E+09 | 6096.50 | 11-DEC-07:10 | 11.10 | 6.11 | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.45 |
Annual Sum or Average | 0.124617E+12 | 0.00 | ||||||||
Minimum of Months | 0.445206E+09 | 6096.50 | 4.68 | -0.0 | 0.00 | 0.00 | 6.42 | 1.83 | ||
Maximum of Months | 0.274783E+11 | 63012.37 | 25.50 | 15.41 | 0.00 | 0.00 | 27.63 | 18.10 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 3.91 | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 3.91 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 | 1.83 | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 | 1.83 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.39 | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.39 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.38 | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.38 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.38 | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 | 11.53 | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 | 11.53 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 | 17.05 | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 | 17.05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.10 | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.17 | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.17 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.65 | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.65 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.63 | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.45 | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.45 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 6.42 | 1.83 | 0.00 | 0.00 | 6.42 | 1.83 | ||
Maximum of Months | 0.00 | 0.00 | 27.63 | 18.10 | 0.00 | 0.00 | 27.63 | 18.10 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.223458E+10 | 27709.17 | 06-JAN-06:01 | 0.10 |
February | 0.163402E+10 | 27716.63 | 02-FEB-06:01 | -3.5 |
March | 0.103775E+10 | 27720.59 | 02-MAR-06:01 | -3.5 |
April | 0.150867E+09 | 8029.69 | 01-APR-05:03 | 11.10 |
May | 31274023.49 | 2509.81 | 19-MAY-06:05 | 20.28 |
June | 3188706.16 | 2621.85 | 01-JUN-06:05 | 19.37 |
July | 202284.12 | 597.69 | 13-JUL-06:03 | 22.38 |
August | 1911729.08 | 2269.66 | 25-AUG-06:05 | 19.18 |
September | 7665617.65 | 1438.60 | 25-SEP-06:04 | 10.55 |
October | 84878327.21 | 2292.75 | 03-OCT-06:05 | 18.90 |
November | 0.743207E+09 | 27702.62 | 28-NOV-06:01 | 1.02 |
December | 0.230276E+10 | 27716.68 | 19-DEC-06:01 | -2.8 |
Annual Sum or Average | 0.823232E+10 | |||
Minimum of Months | 202284.12 | 597.69 | -3.5 | |
Maximum of Months | 0.230276E+10 | 27720.59 | 22.38 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.488490E+10 | 89563.97 | 28-JAN-06:22 | -3.3 |
February | 0.318830E+10 | 88771.72 | 10-FEB-06:01 | -2.8 |
March | 0.173664E+10 | 88823.39 | 02-MAR-06:01 | -3.5 |
April | 0.492242E+09 | 4441.43 | 01-APR-17:00 | 28.90 |
May | 0.221219E+09 | 3365.85 | 01-MAY-07:00 | 15.00 |
June | 36222691.88 | 3155.36 | 02-JUN-06:11 | 21.10 |
July | 10668642.44 | 3009.60 | 05-JUL-06:15 | 18.33 |
August | 60270548.16 | 3394.44 | 15-AUG-07:00 | 18.90 |
September | 0.144288E+09 | 3149.78 | 27-SEP-06:10 | 11.65 |
October | 0.285973E+09 | 3633.62 | 13-OCT-07:00 | 14.40 |
November | 0.116732E+10 | 78378.71 | 28-NOV-05:03 | -0.3 |
December | 0.589013E+10 | 88173.03 | 27-DEC-06:23 | -3.9 |
Annual Sum or Average | 0.181182E+11 | |||
Minimum of Months | 10668642.44 | 3009.60 | -3.9 | |
Maximum of Months | 0.589013E+10 | 89563.97 | 28.90 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.256100E+10 | 1939.55 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.233575E+10 | 1939.55 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.266872E+10 | 1939.55 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.252182E+10 | 1939.55 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.261486E+10 | 1939.55 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.257569E+10 | 1939.55 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.256100E+10 | 1939.55 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.266872E+10 | 1939.55 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.252182E+10 | 1939.55 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.256100E+10 | 1939.55 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.246796E+10 | 1939.55 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.256100E+10 | 1939.55 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.306193E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.233575E+10 | 1939.55 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.266872E+10 | 1939.55 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112294E+11 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102778E+11 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.118738E+11 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.111270E+11 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.115516E+11 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.114492E+11 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112294E+11 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.118738E+11 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.111270E+11 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112294E+11 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108048E+11 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112294E+11 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135003E+12 | ||||
Minimum of Months | 0.102778E+11 | 10075.60 | 0.00 | 0.00 | |
Maximum of Months | 0.118738E+11 | 10075.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.258277E+11 | 23173.88 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.236390E+11 | 23173.88 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.273097E+11 | 23173.88 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.255921E+11 | 23173.88 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.265687E+11 | 23173.88 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.263332E+11 | 23173.88 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.258277E+11 | 23173.88 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.273097E+11 | 23173.88 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.255921E+11 | 23173.88 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.258277E+11 | 23173.88 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.248511E+11 | 23173.88 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.258277E+11 | 23173.88 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.236390E+11 | 23173.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.273097E+11 | 23173.88 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198693E+10 |
February | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 796522.04 | 0.166699E+10 |
March | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2698663.54 | 0.166407E+10 |
April | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165744E+09 | 0.900921E+09 |
May | 0.565842E+09 | 0.261486E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421794E+09 | 0.469421E+09 |
June | 0.565842E+09 | 0.257569E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819920E+09 | 0.181354E+09 |
July | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637908E+09 | 0.141265E+09 |
August | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546064E+09 | 0.236612E+09 |
September | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348514E+09 | 0.328267E+09 |
October | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79585519.10 | 0.906198E+09 |
November | 0.522316E+09 | 0.246796E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160399E+10 |
December | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200902E+10 |
Annual Sum or Average | 0.659424E+10 | 0.306193E+11 | 0.319458E+11 | 0.302302E+10 | 0.120950E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141265E+09 |
Maximum of Months | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819920E+09 | 0.200902E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.910718E+10 |
February | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22094251.16 | 0.798027E+10 |
March | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1509055.16 | 0.871734E+10 |
April | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507621E+09 | 0.648055E+10 |
May | 0.00 | 0.115516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166729E+10 | 0.426181E+10 |
June | 0.00 | 0.114492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345837E+10 | 0.167124E+10 |
July | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249849E+10 | 0.139640E+10 |
August | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196025E+10 | 0.193796E+10 |
September | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528468E+09 | 0.229454E+10 |
October | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140892E+09 | 0.657804E+10 |
November | 0.00 | 0.108048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864075E+10 |
December | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823232E+10 |
Annual Sum or Average | 0.135003E+12 | 0.107850E+11 | 0.672984E+11 | ||||||
Minimum of Months | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139640E+10 |
Maximum of Months | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345837E+10 | 0.910718E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98060750.88 | 0.221974E+11 |
February | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114439E+10 | 0.189754E+11 |
March | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.960886E+09 | 0.230706E+11 |
April | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225267E+10 | 0.204127E+11 |
May | 0.00 | 0.265687E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239285E+09 | 0.197279E+11 |
June | 0.00 | 0.263332E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400216E+09 | 0.105956E+11 |
July | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195836E+09 | 0.939505E+10 |
August | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104636E+09 | 0.111571E+11 |
September | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10014208.54 | 0.114797E+11 |
October | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21941950.09 | 0.249843E+11 |
November | 0.00 | 0.248511E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11357645.30 | 0.264595E+11 |
December | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41325920.02 | 0.203171E+11 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | 0.548062E+10 | 0.218772E+12 | |||||
Minimum of Months | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10014208.54 | 0.939505E+10 |
Maximum of Months | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225267E+10 | 0.264595E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1939.55 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 9352.04 | 27-JAN-07:10 |
February | 659.25 | 01-FEB-08:09 | 1939.55 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.81 | 19-FEB-14:00 | 9056.71 | 03-FEB-07:03 |
March | 659.25 | 01-MAR-08:09 | 1939.55 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 349.88 | 21-MAR-16:10 | 8145.12 | 02-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1939.55 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2915.36 | 21-APR-16:10 | 5865.73 | 12-APR-06:03 |
May | 659.25 | 01-MAY-07:10 | 1939.55 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3852.79 | 19-MAY-16:10 | 4829.47 | 02-MAY-06:02 |
June | 659.25 | 01-JUN-07:10 | 1939.55 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5008.13 | 05-JUN-17:00 | 2260.40 | 29-JUN-06:03 |
July | 659.25 | 01-JUL-07:10 | 1939.55 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4929.30 | 03-JUL-17:00 | 2003.50 | 05-JUL-06:10 |
August | 659.25 | 01-AUG-07:10 | 1939.55 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4398.89 | 07-AUG-16:10 | 2386.27 | 31-AUG-06:03 |
September | 659.25 | 01-SEP-07:10 | 1939.55 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3011.56 | 19-SEP-16:10 | 4446.51 | 25-SEP-06:02 |
October | 659.25 | 02-OCT-07:10 | 1939.55 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2318.17 | 05-OCT-16:10 | 5496.06 | 25-OCT-06:03 |
November | 659.25 | 01-NOV-07:10 | 1939.55 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7476.35 | 28-NOV-07:05 |
December | 659.25 | 01-DEC-08:09 | 1939.55 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9026.08 | 27-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2003.50 | |||||
Maximum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 5008.13 | 9352.04 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 17762.65 | 25-JAN-23:15 |
February | 0.00 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 980.11 | 20-FEB-16:00 | 24394.35 | 08-FEB-18:00 |
March | 0.00 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.36 | 03-MAR-16:10 | 20109.44 | 27-MAR-06:55 |
April | 0.00 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11697.41 | 21-APR-15:10 | 23758.73 | 22-APR-07:00 |
May | 0.00 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10100.83 | 19-MAY-17:00 | 11809.32 | 01-MAY-08:00 |
June | 0.00 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14410.77 | 05-JUN-17:00 | 9536.98 | 28-JUN-02:00 |
July | 0.00 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11467.32 | 03-JUL-17:00 | 6593.64 | 18-JUL-21:00 |
August | 0.00 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9980.04 | 26-AUG-15:10 | 7828.63 | 14-AUG-01:00 |
September | 0.00 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3299.33 | 18-SEP-17:00 | 7340.49 | 23-SEP-17:00 |
October | 0.00 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4203.62 | 01-OCT-14:58 | 12268.30 | 06-OCT-08:00 |
November | 0.00 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 14224.41 | 10-NOV-16:03 |
December | 0.00 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 20108.77 | 18-DEC-08:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6593.64 | |||
Maximum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14410.77 | 24394.35 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23173.88 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9927.89 | 03-JAN-17:00 | 32494.29 | 05-JAN-09:00 |
February | 0.00 | 23173.88 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12217.78 | 06-FEB-14:00 | 50851.83 | 09-FEB-00:53 |
March | 0.00 | 23173.88 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19605.82 | 03-MAR-16:00 | 53228.58 | 27-MAR-07:05 |
April | 0.00 | 23173.88 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24279.35 | 01-APR-15:00 | 70273.07 | 22-APR-07:10 |
May | 0.00 | 23173.88 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5472.17 | 08-MAY-12:40 | 39836.98 | 01-MAY-08:00 |
June | 0.00 | 23173.88 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3690.54 | 05-JUN-17:00 | 37170.88 | 28-JUN-02:00 |
July | 0.00 | 23173.88 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3426.48 | 02-JUL-21:42 | 26294.17 | 18-JUL-21:00 |
August | 0.00 | 23173.88 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.32 | 07-AUG-16:00 | 29811.73 | 14-AUG-01:00 |
September | 0.00 | 23173.88 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 680.10 | 10-SEP-14:32 | 22057.84 | 23-SEP-17:00 |
October | 0.00 | 23173.88 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1684.22 | 01-OCT-14:53 | 48294.37 | 06-OCT-09:00 |
November | 0.00 | 23173.88 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1747.51 | 23-NOV-16:00 | 40885.42 | 15-NOV-09:00 |
December | 0.00 | 23173.88 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3392.91 | 10-DEC-15:00 | 43105.80 | 18-DEC-08:70 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 680.10 | 22057.84 | ||||
Maximum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 24279.35 | 70273.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 945.56 | 12-JAN-15:40 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.54 |
February | 2105.87 | 23-FEB-14:40 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.22 |
March | 3583.67 | 16-MAR-15:50 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.06 |
April | 24445.24 | 28-APR-05:03 | 290.07 | 2317.39 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.07 |
May | 27807.38 | 17-MAY-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 555.78 |
June | 27298.02 | 13-JUN-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.92 |
July | 21219.97 | 11-JUL-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.46 |
August | 23646.69 | 23-AUG-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.77 |
September | 27876.40 | 30-SEP-05:02 | 435.11 | 3476.08 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.42 |
October | 25756.02 | 20-OCT-05:03 | 290.07 | 2317.39 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788.40 |
November | 4883.48 | 03-NOV-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
December | 844.78 | 16-DEC-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 |
Annual Sum or Average | |||||||||||
Minimum of Months | 844.78 | 290.07 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | |
Maximum of Months | 27876.40 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6524.41 | 14-JAN-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3984.45 |
February | 7006.24 | 21-FEB-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2356.89 |
March | 7813.51 | 06-MAR-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 62092.11 | 30-APR-09:51 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 833.37 |
May | 61647.08 | 21-MAY-08:31 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.65 |
June | 59970.97 | 11-JUN-07:51 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 726.79 |
July | 55784.69 | 16-JUL-03:01 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 692.33 |
August | 59099.24 | 27-AUG-23:11 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.26 |
September | 63012.37 | 11-SEP-19:11 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 686.80 |
October | 62207.03 | 01-OCT-09:31 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7578.37 | 22-NOV-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4710.90 |
December | 6096.50 | 11-DEC-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1823.73 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6096.50 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 63012.37 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4710.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8777.89 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17023.07 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12004.44 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5460.94 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5071.23 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9658.81 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.31 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2777.35 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9717.19 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4162.99 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14313.81 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5504.44 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.31 | |
Maximum of Months | 0.00 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17023.07 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.679757E+11 | 51852.10 | 26-JAN-13:09 | 0.905722E+10 | 47402.37 | 28-JAN-06:10 |
February | 0.616126E+11 | 52424.50 | 21-FEB-15:50 | 0.530641E+10 | 43607.47 | 02-FEB-06:10 |
March | 0.701805E+11 | 53006.32 | 14-MAR-14:00 | 0.194754E+10 | 40875.87 | 02-MAR-06:10 |
April | 0.674433E+11 | 65134.37 | 21-APR-14:39 | 62078334.14 | 5566.33 | 12-APR-06:10 |
May | 0.761770E+11 | 69112.10 | 19-MAY-13:00 | 365398.78 | 600.25 | 27-MAY-05:49 |
June | 0.836903E+11 | 73096.56 | 15-JUN-14:39 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.837807E+11 | 72466.20 | 26-JUL-14:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.848525E+11 | 70731.16 | 08-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.765045E+11 | 68336.62 | 01-SEP-14:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.696067E+11 | 67547.28 | 03-OCT-14:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.651021E+11 | 54073.72 | 25-NOV-16:00 | 0.144776E+10 | 35299.75 | 28-NOV-06:10 |
December | 0.681374E+11 | 54076.16 | 09-DEC-16:00 | 0.109124E+11 | 46803.98 | 27-DEC-06:30 |
Annual Sum or Average | 0.875063E+12 | 0.287337E+11 | ||||
Minimum of Months | 0.616126E+11 | 51852.10 | 0.00 | 0.00 | ||
Maximum of Months | 0.848525E+11 | 73096.56 | 0.109124E+11 | 47402.37 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.396181E+11 | 0.974671E+10 | 0.115358E+11 | 0.00 | 0.491465E+10 | 0.00 | 0.00 | 7.29 | 0.00 | 0.00 | 0.00 | 0.216040E+10 | 0.00 |
February | 0.362526E+11 | 0.833809E+10 | 0.105871E+11 | 0.00 | 0.445934E+10 | 0.00 | 0.00 | 13671625.58 | 0.00 | 0.00 | 0.00 | 0.196183E+10 | 0.00 |
March | 0.418523E+11 | 0.856908E+10 | 0.123357E+11 | 0.00 | 0.513682E+10 | 0.00 | 0.00 | 0.103829E+09 | 0.00 | 0.00 | 0.00 | 0.218279E+10 | 0.00 |
April | 0.392410E+11 | 0.762621E+10 | 0.114862E+11 | 0.00 | 0.482612E+10 | 0.00 | 0.00 | 0.223841E+10 | 0.00 | 0.00 | 0.00 | 0.202533E+10 | 0.00 |
May | 0.407352E+11 | 0.730814E+10 | 0.119357E+11 | 0.00 | 0.663214E+10 | 0.00 | 0.00 | 0.753108E+10 | 0.00 | 0.00 | 0.00 | 0.203467E+10 | 0.00 |
June | 0.403581E+11 | 0.678559E+10 | 0.118862E+11 | 0.00 | 0.879086E+10 | 0.00 | 0.00 | 0.139352E+11 | 0.00 | 0.00 | 0.00 | 0.193448E+10 | 0.00 |
July | 0.396181E+11 | 0.713774E+10 | 0.115358E+11 | 0.00 | 0.858497E+10 | 0.00 | 0.00 | 0.149761E+11 | 0.00 | 0.00 | 0.00 | 0.192805E+10 | 0.00 |
August | 0.418523E+11 | 0.762621E+10 | 0.123357E+11 | 0.00 | 0.828821E+10 | 0.00 | 0.00 | 0.127796E+11 | 0.00 | 0.00 | 0.00 | 0.197051E+10 | 0.00 |
September | 0.392410E+11 | 0.799730E+10 | 0.114862E+11 | 0.00 | 0.656108E+10 | 0.00 | 0.00 | 0.930456E+10 | 0.00 | 0.00 | 0.00 | 0.191440E+10 | 0.00 |
October | 0.396181E+11 | 0.895910E+10 | 0.115358E+11 | 0.00 | 0.499237E+10 | 0.00 | 0.00 | 0.248808E+10 | 0.00 | 0.00 | 0.00 | 0.201330E+10 | 0.00 |
November | 0.381239E+11 | 0.925066E+10 | 0.110862E+11 | 0.00 | 0.456167E+10 | 0.00 | 0.00 | 74813656.25 | 0.00 | 0.00 | 0.00 | 0.200481E+10 | 0.00 |
December | 0.396181E+11 | 0.989060E+10 | 0.115358E+11 | 0.00 | 0.496164E+10 | 0.00 | 0.00 | 567.36 | 0.00 | 0.00 | 0.00 | 0.213129E+10 | 0.00 |
Annual Sum or Average | 0.476129E+12 | 0.992354E+11 | 0.139282E+12 | 0.727099E+11 | 0.00 | 0.634453E+11 | 0.242619E+11 | ||||||
Minimum of Months | 0.362526E+11 | 0.678559E+10 | 0.105871E+11 | 0.00 | 0.445934E+10 | 0.00 | 0.00 | 7.29 | 0.00 | 0.00 | 0.00 | 0.191440E+10 | 0.00 |
Maximum of Months | 0.418523E+11 | 0.989060E+10 | 0.123357E+11 | 0.00 | 0.879086E+10 | 0.00 | 0.00 | 0.149761E+11 | 0.00 | 0.00 | 0.00 | 0.218279E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.905722E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.530641E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.194754E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 62078334.14 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 365398.78 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.144776E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.109124E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.287337E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.109124E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35189.04 | 02-JAN-09:09 | 6311.00 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4771.80 | 02-JAN-07:19 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35189.04 | 01-FEB-09:09 | 6311.00 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 4771.80 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35189.04 | 01-MAR-09:09 | 6311.00 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4771.80 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35189.04 | 01-APR-08:09 | 6311.00 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 7077.10 | 21-APR-14:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35189.04 | 01-MAY-08:09 | 6311.00 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 7077.10 | 12-MAY-13:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35189.04 | 01-JUN-08:09 | 6311.00 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 7077.10 | 02-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35189.04 | 01-JUL-08:09 | 6311.00 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 7077.10 | 01-JUL-11:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35189.04 | 01-AUG-08:09 | 6311.00 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 7077.10 | 01-AUG-10:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35189.04 | 01-SEP-08:09 | 6311.00 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 7077.10 | 07-SEP-14:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35189.04 | 02-OCT-08:09 | 6311.00 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 7077.10 | 03-OCT-11:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35189.04 | 01-NOV-08:09 | 6311.00 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 4771.80 | 01-NOV-06:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35189.04 | 01-DEC-09:09 | 6311.00 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4771.80 | 01-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35189.04 | 6311.00 | 10112.62 | 0.00 | 4771.80 | 0.00 | 0.00 | |||||
Maximum of Months | 35189.04 | 6311.00 | 10112.62 | 0.00 | 7077.10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.01 | 13-JAN-14:00 | 0.00 | 0.00 | 0.00 | 1974.05 | 31-JAN-12:39 | 0.00 |
February | 596.86 | 21-FEB-15:00 | 0.00 | 0.00 | 0.00 | 1972.63 | 03-FEB-12:20 | 0.00 |
March | 1299.81 | 21-MAR-15:00 | 0.00 | 0.00 | 0.00 | 1813.18 | 10-MAR-12:30 | 0.00 |
April | 12868.63 | 21-APR-15:09 | 0.00 | 0.00 | 0.00 | 1790.46 | 03-APR-11:09 | 0.00 |
May | 15924.96 | 19-MAY-16:10 | 0.00 | 0.00 | 0.00 | 1767.46 | 01-MAY-11:09 | 0.00 |
June | 21307.64 | 15-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1742.51 | 01-JUN-11:30 | 0.00 |
July | 18565.89 | 27-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1725.54 | 01-JUL-11:20 | 0.00 |
August | 19392.54 | 07-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1725.67 | 31-AUG-11:00 | 0.00 |
September | 14588.95 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1742.69 | 30-SEP-11:09 | 0.00 |
October | 13628.27 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 1767.45 | 31-OCT-11:09 | 0.00 |
November | 1660.23 | 03-NOV-15:00 | 0.00 | 0.00 | 0.00 | 1793.28 | 30-NOV-12:30 | 0.00 |
December | 0.04 | 16-DEC-14:00 | 0.00 | 0.00 | 0.00 | 1811.99 | 30-DEC-12:50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.01 | 0.00 | 0.00 | 0.00 | 1725.54 | 0.00 | ||
Maximum of Months | 21307.64 | 0.00 | 0.00 | 0.00 | 1974.05 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 51852.10 | 26-JAN-13:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4771.80 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52424.50 | 21-FEB-15:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4771.80 | 0.00 | 0.00 | 576.94 | 0.00 |
March | 53006.32 | 14-MAR-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4771.80 | 0.00 | 0.00 | 1166.84 | 0.00 |
April | 65134.37 | 21-APR-14:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 7077.10 | 0.00 | 0.00 | 11014.38 | 0.00 |
May | 69112.10 | 19-MAY-13:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 7077.10 | 0.00 | 0.00 | 15040.43 | 0.00 |
June | 73096.56 | 15-JUN-14:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 7077.10 | 0.00 | 0.00 | 19012.24 | 0.00 |
July | 72466.20 | 26-JUL-14:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 7077.10 | 0.00 | 0.00 | 18393.78 | 0.00 |
August | 70731.16 | 08-AUG-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 7077.10 | 0.00 | 0.00 | 16658.22 | 0.00 |
September | 68336.62 | 01-SEP-14:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 7077.10 | 0.00 | 0.00 | 14258.51 | 0.00 |
October | 67547.28 | 03-OCT-14:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 7077.10 | 0.00 | 0.00 | 13452.81 | 0.00 |
November | 54073.72 | 25-NOV-16:00 | 31277.33 | 10112.62 | 6311.00 | 0.00 | 4771.80 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 54076.16 | 09-DEC-16:00 | 31277.33 | 10112.62 | 6311.00 | 0.00 | 4771.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 51852.10 | 31277.33 | 10112.62 | 0.00 | 0.00 | 4771.80 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 73096.56 | 35189.04 | 10112.62 | 6311.00 | 0.00 | 7077.10 | 0.00 | 0.00 | 19012.24 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 47402.37 | 28-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 43607.47 | 02-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 40875.87 | 02-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 5566.33 | 12-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 600.25 | 27-MAY-05:49 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 35299.75 | 28-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 46803.98 | 27-DEC-06:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 47402.37 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.50 | 20.05 | 6.50 | 20.05 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4.50 | 20.06 | 4.50 | 20.06 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.83 | 20.27 | 2.83 | 20.27 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.50 | 20.52 | 0.50 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.73 | 0.67 | 24.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.98 | 2.83 | 24.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 24.93 | 6.00 | 24.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 25.00 | 4.00 | 24.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 25.21 | 2.67 | 24.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.54 | 0.50 | 24.54 |
November | 1.50 | 20.21 | 1.50 | 20.21 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.00 | 20.01 | 6.00 | 20.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.83 | 20.09 | 21.83 | 20.09 | 17.67 | 25.03 | 16.67 | 24.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.50 | 20.52 | 6.50 | 20.52 | 6.17 | 25.73 | 6.00 | 24.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.67 | 14.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10.17 | 14.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3.33 | 14.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.52 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 27.58 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 27.70 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 37.67 | 27.68 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 27.65 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.57 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.48 | 0.00 | 0.00 |
November | 2.00 | 14.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28.67 | 14.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 64.83 | 14.79 | 0.00 | 131.33 | 27.65 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 28.67 | 14.81 | 0.00 | 0.00 | 37.67 | 27.70 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.70 | 215.50 | 21.21 | 215.50 | 21.21 |
February | 276.00 | 22.11 | 155.50 | 21.25 | 155.50 | 21.25 |
March | 324.00 | 22.77 | 107.50 | 21.26 | 107.50 | 21.26 |
April | 209.67 | 23.61 | 30.50 | 23.10 | 9.00 | 21.20 |
May | 50.83 | 23.77 | 152.17 | 23.90 | 0.00 | 0.00 |
June | 3.00 | 23.74 | 266.83 | 23.90 | 0.83 | 24.53 |
July | 42.17 | 23.98 | 300.00 | 23.91 | 42.17 | 23.98 |
August | 17.17 | 24.04 | 321.50 | 23.90 | 17.17 | 24.04 |
September | 19.33 | 23.94 | 276.00 | 23.90 | 18.33 | 23.96 |
October | 79.83 | 23.69 | 124.00 | 23.89 | 3.50 | 23.91 |
November | 268.50 | 22.89 | 71.50 | 21.22 | 71.50 | 21.22 |
December | 300.00 | 21.72 | 217.83 | 21.23 | 217.83 | 21.23 |
Annual Sum or Average | 1890.50 | 22.56 | 2238.83 | 22.98 | 858.83 | 21.50 |
Minimum of Months | 3.00 | 21.70 | 30.50 | 21.21 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 24.04 | 321.50 | 23.91 | 217.83 | 24.53 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 26.16 | 7.29 | 0.50 | 26.16 | 0.00 | 0.00 | 0.00 | 13-JAN-15:00 | 0.00 | 01-JAN-00:10 | 0.02 | 13-JAN-15:00 | 0.02 | 13-JAN-15:00 | 0.00 | 01-JAN-00:10 | 0.01 | 13-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 49800495.99 | 13671625.58 | 23.00 | 49800495.99 | 0.00 | 0.00 | 0.13 | 21-FEB-16:00 | 0.00 | 01-FEB-00:10 | 2186.53 | 21-FEB-16:00 | 2186.53 | 21-FEB-16:00 | 0.00 | 23-FEB-14:20 | 596.86 | 21-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.381664E+09 | 0.103829E+09 | 96.92 | 0.381663E+09 | 139.62 | 0.00 | 0.29 | 14-MAR-16:00 | 0.00 | 01-MAR-00:10 | 4805.06 | 14-MAR-16:00 | 4805.06 | 14-MAR-16:00 | 0.02 | 11-MAR-13:10 | 1299.81 | 21-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.310969E+10 | 0.869787E+09 | 197.52 | 0.310143E+10 | 8253985.19 | 0.00 | 1.00 | 20-APR-05:01 | 0.00 | 01-APR-00:10 | 18995.59 | 29-APR-05:01 | 18844.76 | 20-APR-05:01 | 2002.18 | 29-APR-05:02 | 4499.74 | 29-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.735415E+10 | 0.206525E+10 | 272.11 | 0.715724E+10 | 0.196903E+09 | 0.00 | 1.00 | 01-MAY-05:02 | 0.00 | 01-MAY-00:10 | 20464.69 | 23-MAY-05:01 | 19569.09 | 30-MAY-05:41 | 7256.90 | 25-MAY-05:02 | 4843.13 | 23-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.106933E+11 | 0.314552E+10 | 301.85 | 0.102441E+11 | 0.449176E+09 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 21220.40 | 28-JUN-05:01 | 19927.10 | 17-JUN-05:01 | 7975.37 | 28-JUN-05:15 | 5174.54 | 05-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.123736E+11 | 0.345361E+10 | 300.20 | 0.102016E+11 | 0.217203E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 24284.45 | 22-JUL-05:01 | 20526.38 | 03-JUL-05:01 | 14169.81 | 21-JUL-05:20 | 5638.50 | 16-JUL-14:45 | 0.00 | 01-JUL-00:10 |
August | 0.114852E+11 | 0.319645E+10 | 314.29 | 0.996120E+10 | 0.152401E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 23440.17 | 03-AUG-05:01 | 20292.07 | 24-AUG-05:01 | 11167.54 | 02-AUG-05:09 | 5416.97 | 03-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.931066E+10 | 0.255701E+10 | 270.45 | 0.814754E+10 | 0.116312E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 22848.17 | 22-SEP-05:01 | 21022.98 | 04-SEP-16:40 | 11368.92 | 22-SEP-05:47 | 5614.43 | 03-SEP-13:50 | 0.00 | 01-SEP-00:10 |
October | 0.383540E+10 | 0.102998E+10 | 203.29 | 0.347750E+10 | 0.357899E+09 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 21616.92 | 04-OCT-05:01 | 20030.75 | 02-OCT-05:01 | 9418.03 | 04-OCT-05:15 | 5083.87 | 04-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.277594E+09 | 74811526.84 | 79.89 | 0.275909E+09 | 1685224.89 | 0.00 | 0.36 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 | 6288.01 | 03-NOV-16:00 | 6288.01 | 03-NOV-16:00 | 222.61 | 03-NOV-12:50 | 1660.23 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 |
December | 2036.75 | 567.36 | 5.50 | 2036.75 | 0.00 | 0.00 | 0.00 | 16-DEC-15:00 | 0.00 | 01-DEC-00:10 | 0.16 | 16-DEC-15:00 | 0.16 | 16-DEC-15:00 | 0.00 | 01-DEC-00:10 | 0.04 | 16-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.588710E+11 | 0.165099E+11 | 2065.52 | 0.529979E+11 | 0.587307E+10 | 0.00 | ||||||||||||||
Minimum of Months | 26.16 | 7.29 | 0.50 | 26.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 0.02 | 0.00 | 0.01 | 0.00 | |||||||
Maximum of Months | 0.123736E+11 | 0.345361E+10 | 314.29 | 0.102441E+11 | 0.217203E+10 | 0.00 | 1.00 | 0.00 | 24284.45 | 21022.98 | 14169.81 | 5638.50 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.439331E+10 | 0.136863E+10 | 116.35 | 0.438138E+10 | 11929177.21 | 0.00 | 1.00 | 27-APR-17:50 | 0.00 | 01-APR-00:10 | 61907.44 | 30-APR-09:51 | 60971.10 | 30-APR-10:41 | 5949.70 | 30-APR-09:51 | 16766.70 | 30-APR-15:23 | 0.00 | 01-APR-00:10 |
May | 0.174415E+11 | 0.546584E+10 | 279.50 | 0.169655E+11 | 0.475965E+09 | 0.00 | 1.00 | 07-MAY-11:41 | 0.00 | 01-MAY-00:10 | 68962.16 | 28-MAY-09:01 | 60413.14 | 29-MAY-20:21 | 20831.04 | 28-MAY-09:07 | 18012.39 | 28-MAY-13:02 | 0.00 | 01-MAY-00:10 |
June | 0.331092E+11 | 0.107896E+11 | 398.93 | 0.319532E+11 | 0.115601E+10 | 0.00 | 1.00 | 01-JUN-17:05 | 0.00 | 01-JUN-00:10 | 71693.64 | 19-JUN-17:55 | 61240.77 | 21-JUN-23:11 | 27816.26 | 19-JUN-17:55 | 18616.01 | 18-JUN-16:03 | 0.00 | 01-JUN-00:10 |
July | 0.372182E+11 | 0.115224E+11 | 410.04 | 0.313998E+11 | 0.581847E+10 | 0.00 | 1.00 | 01-JUL-17:06 | 0.00 | 01-JUL-00:20 | 76181.97 | 21-JUL-20:31 | 59433.06 | 24-JUL-17:42 | 37269.41 | 21-JUL-20:38 | 19168.47 | 02-JUL-15:52 | 0.00 | 01-JUL-00:10 |
August | 0.310069E+11 | 0.958318E+10 | 380.08 | 0.275695E+11 | 0.343736E+10 | 0.00 | 1.00 | 01-AUG-00:30 | 0.00 | 01-AUG-00:15 | 73747.42 | 03-AUG-00:21 | 61578.74 | 25-AUG-21:51 | 32037.79 | 03-AUG-01:21 | 18645.73 | 06-AUG-15:12 | 0.00 | 01-AUG-00:10 |
September | 0.224408E+11 | 0.674754E+10 | 277.39 | 0.197128E+11 | 0.272799E+10 | 0.00 | 1.00 | 01-SEP-17:06 | 0.00 | 01-SEP-00:10 | 73231.89 | 03-SEP-23:01 | 61391.95 | 10-SEP-20:11 | 37562.00 | 03-SEP-23:01 | 18132.27 | 10-SEP-10:41 | 0.00 | 01-SEP-00:10 |
October | 0.488133E+10 | 0.145810E+10 | 134.73 | 0.433668E+10 | 0.544649E+09 | 0.00 | 1.00 | 01-OCT-09:31 | 0.00 | 01-OCT-00:10 | 70991.85 | 03-OCT-18:01 | 61611.32 | 22-OCT-14:10 | 24719.55 | 03-OCT-18:10 | 17795.19 | 03-OCT-18:01 | 0.00 | 01-OCT-00:10 |
November | 7204.39 | 2129.40 | 2.83 | 6589.90 | 614.50 | 0.00 | 0.00 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 1.14 | 03-NOV-14:00 | 1.04 | 03-NOV-14:00 | 0.10 | 03-NOV-14:00 | 0.34 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.150491E+12 | 0.469354E+11 | 1999.87 | 0.136319E+12 | 0.141724E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.372182E+11 | 0.115224E+11 | 410.04 | 0.319532E+11 | 0.581847E+10 | 0.00 | 1.00 | 0.00 | 76181.97 | 61611.32 | 37562.00 | 19168.47 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.57 | 37.54 | 29.03 | 72.84 | 136.20 | 0.00 | 0.00 | 744.00 |
February | 74.90 | 39.75 | 35.15 | 88.86 | 122.34 | 0.00 | 0.00 | 672.00 |
March | 102.06 | 54.65 | 47.41 | 134.05 | 109.04 | 0.00 | 0.00 | 744.00 |
April | 117.16 | 63.14 | 54.02 | 176.24 | 78.70 | 0.00 | 0.00 | 720.00 |
May | 126.17 | 67.36 | 58.81 | 211.44 | 57.60 | 0.00 | 0.00 | 744.00 |
June | 123.17 | 66.16 | 57.01 | 235.94 | 34.89 | 0.00 | 0.00 | 720.00 |
July | 109.39 | 54.38 | 55.01 | 207.80 | 31.33 | 0.00 | 0.00 | 744.00 |
August | 105.68 | 53.75 | 51.93 | 192.24 | 41.21 | 0.00 | 0.00 | 744.00 |
September | 108.36 | 60.40 | 47.95 | 186.01 | 70.18 | 0.00 | 0.00 | 720.00 |
October | 93.08 | 54.28 | 38.80 | 134.23 | 98.58 | 0.00 | 0.00 | 744.00 |
November | 77.69 | 47.11 | 30.57 | 91.96 | 135.95 | 0.00 | 0.00 | 720.00 |
December | 63.08 | 34.29 | 28.79 | 63.78 | 155.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 97.36 | 52.77 | 44.59 | 149.87 | 89.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 63.08 | 34.29 | 28.79 | 63.78 | 31.33 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 126.17 | 67.36 | 58.81 | 235.94 | 155.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.57 | 37.54 | 29.03 | 72.84 | 136.20 | 0.00 | 0.00 | 744.00 |
February | 74.90 | 39.75 | 35.15 | 88.86 | 122.34 | 0.00 | 0.00 | 672.00 |
March | 102.06 | 54.65 | 47.41 | 134.05 | 109.04 | 0.00 | 0.00 | 744.00 |
April | 117.16 | 63.14 | 54.02 | 176.24 | 78.70 | 0.00 | 0.00 | 720.00 |
May | 126.17 | 67.36 | 58.81 | 211.44 | 57.60 | 0.00 | 0.00 | 744.00 |
June | 123.17 | 66.16 | 57.01 | 235.94 | 34.89 | 0.00 | 0.00 | 720.00 |
July | 109.39 | 54.38 | 55.01 | 207.80 | 31.33 | 0.00 | 0.00 | 744.00 |
August | 105.68 | 53.75 | 51.93 | 192.24 | 41.21 | 0.00 | 0.00 | 744.00 |
September | 108.36 | 60.40 | 47.95 | 186.01 | 70.18 | 0.00 | 0.00 | 720.00 |
October | 93.08 | 54.28 | 38.80 | 134.23 | 98.58 | 0.00 | 0.00 | 744.00 |
November | 77.69 | 47.11 | 30.57 | 91.96 | 135.95 | 0.00 | 0.00 | 720.00 |
December | 63.08 | 34.29 | 28.79 | 63.78 | 155.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 97.36 | 52.77 | 44.59 | 149.87 | 89.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 63.08 | 34.29 | 28.79 | 63.78 | 31.33 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 126.17 | 67.36 | 58.81 | 235.94 | 155.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.76 | 0.00 | 13.76 | 2.50 | 84.69 | 0.00 | 0.00 | 744.00 |
February | 16.80 | 0.00 | 16.80 | 7.25 | 75.13 | 0.00 | 0.00 | 672.00 |
March | 22.00 | 0.00 | 21.99 | 13.79 | 66.47 | 0.00 | 0.00 | 744.00 |
April | 25.50 | 0.30 | 25.20 | 25.59 | 47.02 | 0.00 | 0.00 | 720.00 |
May | 30.28 | 2.34 | 27.94 | 41.07 | 32.15 | 0.00 | 0.00 | 744.00 |
June | 32.14 | 4.06 | 28.08 | 60.42 | 19.33 | 0.00 | 0.00 | 720.00 |
July | 29.60 | 2.88 | 26.72 | 55.09 | 17.51 | 0.00 | 0.00 | 744.00 |
August | 25.15 | 0.69 | 24.46 | 43.43 | 23.49 | 0.00 | 0.00 | 744.00 |
September | 21.80 | 0.02 | 21.78 | 32.21 | 41.26 | 0.00 | 0.00 | 720.00 |
October | 18.08 | 0.00 | 18.08 | 13.49 | 59.71 | 0.00 | 0.00 | 744.00 |
November | 14.59 | 0.00 | 14.59 | 2.80 | 84.99 | 0.00 | 0.00 | 720.00 |
December | 13.65 | 0.00 | 13.65 | 1.39 | 97.73 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 21.97 | 0.86 | 21.11 | 25.00 | 54.02 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.65 | 0.00 | 13.65 | 1.39 | 17.51 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 32.14 | 4.06 | 28.08 | 60.42 | 97.73 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.76 | 0.00 | 13.76 | 2.50 | 84.69 | 0.00 | 0.00 | 744.00 |
February | 16.80 | 0.00 | 16.80 | 7.25 | 75.13 | 0.00 | 0.00 | 672.00 |
March | 22.00 | 0.00 | 21.99 | 13.79 | 66.47 | 0.00 | 0.00 | 744.00 |
April | 25.50 | 0.30 | 25.20 | 25.59 | 47.02 | 0.00 | 0.00 | 720.00 |
May | 30.28 | 2.34 | 27.94 | 41.07 | 32.15 | 0.00 | 0.00 | 744.00 |
June | 32.13 | 4.06 | 28.08 | 60.42 | 19.33 | 0.00 | 0.00 | 720.00 |
July | 29.60 | 2.88 | 26.72 | 55.09 | 17.50 | 0.00 | 0.00 | 744.00 |
August | 25.15 | 0.69 | 24.46 | 43.43 | 23.49 | 0.00 | 0.00 | 744.00 |
September | 21.80 | 0.02 | 21.78 | 32.21 | 41.26 | 0.00 | 0.00 | 720.00 |
October | 18.08 | 0.00 | 18.08 | 13.48 | 59.71 | 0.00 | 0.00 | 744.00 |
November | 14.59 | 0.00 | 14.59 | 2.80 | 84.99 | 0.00 | 0.00 | 720.00 |
December | 13.65 | 0.00 | 13.65 | 1.39 | 97.73 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 21.97 | 0.86 | 21.11 | 25.00 | 54.02 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.65 | 0.00 | 13.65 | 1.39 | 17.50 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 32.13 | 4.06 | 28.08 | 60.42 | 97.73 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.40 | 28.10 | 12.30 | 40.20 | 37.93 | 0.00 | 0.00 | 744.00 |
February | 52.48 | 37.05 | 15.44 | 58.90 | 35.88 | 0.00 | 0.00 | 672.00 |
March | 74.16 | 52.50 | 21.66 | 89.86 | 36.23 | 0.00 | 0.00 | 744.00 |
April | 92.74 | 69.05 | 23.69 | 118.05 | 32.18 | 0.00 | 0.00 | 720.00 |
May | 102.52 | 76.54 | 25.97 | 131.75 | 32.15 | 0.00 | 0.00 | 744.00 |
June | 108.52 | 84.53 | 23.99 | 143.56 | 26.87 | 0.00 | 0.00 | 720.00 |
July | 93.76 | 67.97 | 25.80 | 124.68 | 21.87 | 0.00 | 0.00 | 744.00 |
August | 87.55 | 63.46 | 24.10 | 114.21 | 25.92 | 0.00 | 0.00 | 744.00 |
September | 79.78 | 59.83 | 19.95 | 100.22 | 35.44 | 0.00 | 0.00 | 720.00 |
October | 59.62 | 43.29 | 16.33 | 67.31 | 39.16 | 0.00 | 0.00 | 744.00 |
November | 46.01 | 33.97 | 12.03 | 45.10 | 44.99 | 0.00 | 0.00 | 720.00 |
December | 37.24 | 24.48 | 12.76 | 32.96 | 44.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.97 | 53.44 | 19.53 | 89.00 | 34.40 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 37.24 | 24.48 | 12.03 | 32.96 | 21.87 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.52 | 84.53 | 25.97 | 143.56 | 44.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.40 | 28.10 | 12.30 | 40.20 | 37.93 | 0.00 | 0.00 | 744.00 |
February | 52.48 | 37.05 | 15.44 | 58.90 | 35.88 | 0.00 | 0.00 | 672.00 |
March | 74.16 | 52.50 | 21.66 | 89.86 | 36.23 | 0.00 | 0.00 | 744.00 |
April | 92.74 | 69.05 | 23.69 | 118.05 | 32.18 | 0.00 | 0.00 | 720.00 |
May | 102.52 | 76.54 | 25.97 | 131.75 | 32.15 | 0.00 | 0.00 | 744.00 |
June | 108.52 | 84.53 | 23.99 | 143.56 | 26.87 | 0.00 | 0.00 | 720.00 |
July | 93.76 | 67.97 | 25.80 | 124.68 | 21.87 | 0.00 | 0.00 | 744.00 |
August | 87.55 | 63.46 | 24.10 | 114.21 | 25.92 | 0.00 | 0.00 | 744.00 |
September | 79.78 | 59.83 | 19.95 | 100.22 | 35.44 | 0.00 | 0.00 | 720.00 |
October | 59.62 | 43.29 | 16.33 | 67.31 | 39.16 | 0.00 | 0.00 | 744.00 |
November | 46.01 | 33.97 | 12.03 | 45.10 | 44.99 | 0.00 | 0.00 | 720.00 |
December | 37.24 | 24.48 | 12.76 | 32.96 | 44.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.97 | 53.44 | 19.53 | 89.00 | 34.40 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 37.24 | 24.48 | 12.03 | 32.96 | 21.87 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.52 | 84.53 | 25.97 | 143.56 | 44.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.40 | 28.10 | 12.30 | 40.20 | 37.93 | 0.00 | 0.00 | 744.00 |
February | 52.48 | 37.05 | 15.44 | 58.90 | 35.88 | 0.00 | 0.00 | 672.00 |
March | 74.16 | 52.50 | 21.66 | 89.86 | 36.23 | 0.00 | 0.00 | 744.00 |
April | 92.74 | 69.05 | 23.69 | 118.05 | 32.18 | 0.00 | 0.00 | 720.00 |
May | 102.52 | 76.54 | 25.97 | 131.75 | 32.15 | 0.00 | 0.00 | 744.00 |
June | 108.52 | 84.53 | 23.99 | 143.56 | 26.87 | 0.00 | 0.00 | 720.00 |
July | 93.76 | 67.97 | 25.80 | 124.68 | 21.87 | 0.00 | 0.00 | 744.00 |
August | 87.55 | 63.46 | 24.10 | 114.21 | 25.92 | 0.00 | 0.00 | 744.00 |
September | 79.78 | 59.83 | 19.95 | 100.22 | 35.44 | 0.00 | 0.00 | 720.00 |
October | 59.62 | 43.29 | 16.33 | 67.31 | 39.16 | 0.00 | 0.00 | 744.00 |
November | 46.01 | 33.97 | 12.03 | 45.10 | 44.99 | 0.00 | 0.00 | 720.00 |
December | 37.24 | 24.48 | 12.76 | 32.96 | 44.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.97 | 53.44 | 19.53 | 89.00 | 34.40 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 37.24 | 24.48 | 12.03 | 32.96 | 21.87 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.52 | 84.53 | 25.97 | 143.56 | 44.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.40 | 28.10 | 12.30 | 40.20 | 37.93 | 0.00 | 0.00 | 744.00 |
February | 52.48 | 37.05 | 15.44 | 58.90 | 35.88 | 0.00 | 0.00 | 672.00 |
March | 74.16 | 52.50 | 21.66 | 89.86 | 36.23 | 0.00 | 0.00 | 744.00 |
April | 92.74 | 69.05 | 23.69 | 118.05 | 32.18 | 0.00 | 0.00 | 720.00 |
May | 102.52 | 76.54 | 25.97 | 131.75 | 32.15 | 0.00 | 0.00 | 744.00 |
June | 108.52 | 84.53 | 23.99 | 143.56 | 26.87 | 0.00 | 0.00 | 720.00 |
July | 93.76 | 67.97 | 25.80 | 124.68 | 21.87 | 0.00 | 0.00 | 744.00 |
August | 87.55 | 63.46 | 24.10 | 114.21 | 25.92 | 0.00 | 0.00 | 744.00 |
September | 79.78 | 59.83 | 19.95 | 100.22 | 35.44 | 0.00 | 0.00 | 720.00 |
October | 59.62 | 43.29 | 16.33 | 67.31 | 39.16 | 0.00 | 0.00 | 744.00 |
November | 46.01 | 33.97 | 12.03 | 45.10 | 44.99 | 0.00 | 0.00 | 720.00 |
December | 37.24 | 24.48 | 12.76 | 32.96 | 44.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.97 | 53.44 | 19.53 | 89.00 | 34.40 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 37.24 | 24.48 | 12.03 | 32.96 | 21.87 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.52 | 84.53 | 25.97 | 143.56 | 44.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.40 | 28.10 | 12.30 | 40.20 | 37.93 | 0.00 | 0.00 | 744.00 |
February | 52.48 | 37.05 | 15.44 | 58.90 | 35.88 | 0.00 | 0.00 | 672.00 |
March | 74.16 | 52.50 | 21.66 | 89.86 | 36.23 | 0.00 | 0.00 | 744.00 |
April | 92.74 | 69.05 | 23.69 | 118.05 | 32.18 | 0.00 | 0.00 | 720.00 |
May | 102.52 | 76.54 | 25.97 | 131.75 | 32.15 | 0.00 | 0.00 | 744.00 |
June | 108.52 | 84.53 | 23.99 | 143.56 | 26.87 | 0.00 | 0.00 | 720.00 |
July | 93.76 | 67.97 | 25.80 | 124.68 | 21.87 | 0.00 | 0.00 | 744.00 |
August | 87.55 | 63.46 | 24.10 | 114.21 | 25.92 | 0.00 | 0.00 | 744.00 |
September | 79.78 | 59.83 | 19.95 | 100.22 | 35.44 | 0.00 | 0.00 | 720.00 |
October | 59.62 | 43.29 | 16.33 | 67.31 | 39.16 | 0.00 | 0.00 | 744.00 |
November | 46.01 | 33.97 | 12.03 | 45.10 | 44.99 | 0.00 | 0.00 | 720.00 |
December | 37.24 | 24.48 | 12.76 | 32.96 | 44.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.97 | 53.44 | 19.53 | 89.00 | 34.40 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 37.24 | 24.48 | 12.03 | 32.96 | 21.87 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.52 | 84.53 | 25.97 | 143.56 | 44.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.40 | 28.10 | 12.30 | 40.20 | 37.93 | 0.00 | 0.00 | 744.00 |
February | 52.48 | 37.05 | 15.44 | 58.90 | 35.88 | 0.00 | 0.00 | 672.00 |
March | 74.16 | 52.50 | 21.66 | 89.86 | 36.23 | 0.00 | 0.00 | 744.00 |
April | 92.74 | 69.05 | 23.69 | 118.05 | 32.18 | 0.00 | 0.00 | 720.00 |
May | 102.52 | 76.54 | 25.97 | 131.75 | 32.15 | 0.00 | 0.00 | 744.00 |
June | 108.52 | 84.53 | 23.99 | 143.56 | 26.87 | 0.00 | 0.00 | 720.00 |
July | 93.76 | 67.97 | 25.80 | 124.68 | 21.87 | 0.00 | 0.00 | 744.00 |
August | 87.55 | 63.46 | 24.10 | 114.21 | 25.92 | 0.00 | 0.00 | 744.00 |
September | 79.78 | 59.83 | 19.95 | 100.22 | 35.44 | 0.00 | 0.00 | 720.00 |
October | 59.62 | 43.29 | 16.33 | 67.31 | 39.16 | 0.00 | 0.00 | 744.00 |
November | 46.01 | 33.97 | 12.03 | 45.10 | 44.99 | 0.00 | 0.00 | 720.00 |
December | 37.24 | 24.48 | 12.76 | 32.96 | 44.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.97 | 53.44 | 19.53 | 89.00 | 34.40 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 37.24 | 24.48 | 12.03 | 32.96 | 21.87 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.52 | 84.53 | 25.97 | 143.56 | 44.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.40 | 28.10 | 12.30 | 40.20 | 37.93 | 0.00 | 0.00 | 744.00 |
February | 52.48 | 37.05 | 15.44 | 58.90 | 35.88 | 0.00 | 0.00 | 672.00 |
March | 74.16 | 52.50 | 21.66 | 89.86 | 36.23 | 0.00 | 0.00 | 744.00 |
April | 92.74 | 69.05 | 23.69 | 118.05 | 32.18 | 0.00 | 0.00 | 720.00 |
May | 102.52 | 76.54 | 25.97 | 131.75 | 32.15 | 0.00 | 0.00 | 744.00 |
June | 108.52 | 84.53 | 23.99 | 143.56 | 26.87 | 0.00 | 0.00 | 720.00 |
July | 93.76 | 67.97 | 25.80 | 124.68 | 21.87 | 0.00 | 0.00 | 744.00 |
August | 87.55 | 63.46 | 24.10 | 114.21 | 25.92 | 0.00 | 0.00 | 744.00 |
September | 79.78 | 59.83 | 19.95 | 100.22 | 35.44 | 0.00 | 0.00 | 720.00 |
October | 59.62 | 43.29 | 16.33 | 67.31 | 39.16 | 0.00 | 0.00 | 744.00 |
November | 46.01 | 33.97 | 12.03 | 45.10 | 44.99 | 0.00 | 0.00 | 720.00 |
December | 37.24 | 24.48 | 12.76 | 32.96 | 44.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.97 | 53.44 | 19.53 | 89.00 | 34.40 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 37.24 | 24.48 | 12.03 | 32.96 | 21.87 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.52 | 84.53 | 25.97 | 143.56 | 44.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.40 | 28.10 | 12.30 | 40.20 | 37.93 | 0.00 | 0.00 | 744.00 |
February | 52.48 | 37.05 | 15.44 | 58.90 | 35.88 | 0.00 | 0.00 | 672.00 |
March | 74.16 | 52.50 | 21.66 | 89.86 | 36.23 | 0.00 | 0.00 | 744.00 |
April | 92.74 | 69.05 | 23.69 | 118.05 | 32.18 | 0.00 | 0.00 | 720.00 |
May | 102.52 | 76.54 | 25.97 | 131.75 | 32.15 | 0.00 | 0.00 | 744.00 |
June | 108.52 | 84.53 | 23.99 | 143.56 | 26.87 | 0.00 | 0.00 | 720.00 |
July | 93.76 | 67.97 | 25.80 | 124.68 | 21.87 | 0.00 | 0.00 | 744.00 |
August | 87.55 | 63.46 | 24.10 | 114.21 | 25.92 | 0.00 | 0.00 | 744.00 |
September | 79.78 | 59.83 | 19.95 | 100.22 | 35.44 | 0.00 | 0.00 | 720.00 |
October | 59.62 | 43.29 | 16.33 | 67.31 | 39.16 | 0.00 | 0.00 | 744.00 |
November | 46.01 | 33.97 | 12.03 | 45.10 | 44.99 | 0.00 | 0.00 | 720.00 |
December | 37.24 | 24.48 | 12.76 | 32.96 | 44.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.97 | 53.44 | 19.53 | 89.00 | 34.40 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 37.24 | 24.48 | 12.03 | 32.96 | 21.87 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.52 | 84.53 | 25.97 | 143.56 | 44.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.40 | 28.10 | 12.30 | 40.20 | 37.93 | 0.00 | 0.00 | 744.00 |
February | 52.48 | 37.05 | 15.44 | 58.90 | 35.88 | 0.00 | 0.00 | 672.00 |
March | 74.16 | 52.50 | 21.66 | 89.86 | 36.23 | 0.00 | 0.00 | 744.00 |
April | 92.74 | 69.05 | 23.69 | 118.05 | 32.18 | 0.00 | 0.00 | 720.00 |
May | 102.52 | 76.54 | 25.97 | 131.75 | 32.15 | 0.00 | 0.00 | 744.00 |
June | 108.52 | 84.53 | 23.99 | 143.56 | 26.87 | 0.00 | 0.00 | 720.00 |
July | 93.76 | 67.97 | 25.80 | 124.68 | 21.87 | 0.00 | 0.00 | 744.00 |
August | 87.55 | 63.46 | 24.10 | 114.21 | 25.92 | 0.00 | 0.00 | 744.00 |
September | 79.78 | 59.83 | 19.95 | 100.22 | 35.44 | 0.00 | 0.00 | 720.00 |
October | 59.62 | 43.29 | 16.33 | 67.31 | 39.16 | 0.00 | 0.00 | 744.00 |
November | 46.01 | 33.97 | 12.03 | 45.10 | 44.99 | 0.00 | 0.00 | 720.00 |
December | 37.24 | 24.48 | 12.76 | 32.96 | 44.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.97 | 53.44 | 19.53 | 89.00 | 34.40 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 37.24 | 24.48 | 12.03 | 32.96 | 21.87 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.52 | 84.53 | 25.97 | 143.56 | 44.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.40 | 28.10 | 12.30 | 40.20 | 37.93 | 0.00 | 0.00 | 744.00 |
February | 52.48 | 37.05 | 15.44 | 58.90 | 35.88 | 0.00 | 0.00 | 672.00 |
March | 74.16 | 52.50 | 21.66 | 89.86 | 36.23 | 0.00 | 0.00 | 744.00 |
April | 92.74 | 69.05 | 23.69 | 118.05 | 32.18 | 0.00 | 0.00 | 720.00 |
May | 102.52 | 76.54 | 25.97 | 131.75 | 32.15 | 0.00 | 0.00 | 744.00 |
June | 108.52 | 84.53 | 23.99 | 143.56 | 26.87 | 0.00 | 0.00 | 720.00 |
July | 93.76 | 67.97 | 25.80 | 124.68 | 21.87 | 0.00 | 0.00 | 744.00 |
August | 87.55 | 63.46 | 24.10 | 114.21 | 25.92 | 0.00 | 0.00 | 744.00 |
September | 79.78 | 59.83 | 19.95 | 100.22 | 35.44 | 0.00 | 0.00 | 720.00 |
October | 59.62 | 43.29 | 16.33 | 67.31 | 39.16 | 0.00 | 0.00 | 744.00 |
November | 46.01 | 33.97 | 12.03 | 45.10 | 44.99 | 0.00 | 0.00 | 720.00 |
December | 37.24 | 24.48 | 12.76 | 32.96 | 44.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.97 | 53.44 | 19.53 | 89.00 | 34.40 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 37.24 | 24.48 | 12.03 | 32.96 | 21.87 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.52 | 84.53 | 25.97 | 143.56 | 44.99 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.178306E+09 | 0.100558E+09 | 77747281.13 | 0.195103E+09 | 0.364808E+09 |
February | 0.181192E+09 | 96155890.82 | 85035801.96 | 0.214971E+09 | 0.295954E+09 |
March | 0.273356E+09 | 0.146381E+09 | 0.126975E+09 | 0.359048E+09 | 0.292054E+09 |
April | 0.303668E+09 | 0.163648E+09 | 0.140020E+09 | 0.456826E+09 | 0.203994E+09 |
May | 0.337944E+09 | 0.180425E+09 | 0.157519E+09 | 0.566329E+09 | 0.154276E+09 |
June | 0.319260E+09 | 0.171488E+09 | 0.147771E+09 | 0.611569E+09 | 90433159.39 |
July | 0.292985E+09 | 0.145648E+09 | 0.147337E+09 | 0.556584E+09 | 83923471.70 |
August | 0.283060E+09 | 0.143971E+09 | 0.139088E+09 | 0.514896E+09 | 0.110381E+09 |
September | 0.280863E+09 | 0.156566E+09 | 0.124297E+09 | 0.482127E+09 | 0.181894E+09 |
October | 0.249316E+09 | 0.145390E+09 | 0.103926E+09 | 0.359532E+09 | 0.264031E+09 |
November | 0.201362E+09 | 0.122113E+09 | 79248559.55 | 0.238367E+09 | 0.352379E+09 |
December | 0.168962E+09 | 91854239.58 | 77107517.22 | 0.170831E+09 | 0.417012E+09 |
Annual Sum or Average | 0.307027E+10 | 0.166420E+10 | 0.140607E+10 | 0.472618E+10 | 0.281114E+10 |
Minimum of Months | 0.168962E+09 | 91854239.58 | 77107517.22 | 0.170831E+09 | 83923471.70 |
Maximum of Months | 0.337944E+09 | 0.180425E+09 | 0.157519E+09 | 0.611569E+09 | 0.417012E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.178306E+09 | 0.100558E+09 | 77747281.13 | 0.195103E+09 | 0.364808E+09 |
February | 0.181192E+09 | 96155890.82 | 85035801.96 | 0.214971E+09 | 0.295954E+09 |
March | 0.273356E+09 | 0.146381E+09 | 0.126975E+09 | 0.359048E+09 | 0.292054E+09 |
April | 0.303668E+09 | 0.163648E+09 | 0.140020E+09 | 0.456826E+09 | 0.203994E+09 |
May | 0.337944E+09 | 0.180425E+09 | 0.157519E+09 | 0.566329E+09 | 0.154276E+09 |
June | 0.319260E+09 | 0.171488E+09 | 0.147771E+09 | 0.611569E+09 | 90433159.39 |
July | 0.292985E+09 | 0.145648E+09 | 0.147337E+09 | 0.556584E+09 | 83923471.70 |
August | 0.283060E+09 | 0.143971E+09 | 0.139088E+09 | 0.514896E+09 | 0.110381E+09 |
September | 0.280863E+09 | 0.156566E+09 | 0.124297E+09 | 0.482127E+09 | 0.181894E+09 |
October | 0.249316E+09 | 0.145390E+09 | 0.103926E+09 | 0.359532E+09 | 0.264031E+09 |
November | 0.201362E+09 | 0.122113E+09 | 79248559.55 | 0.238367E+09 | 0.352379E+09 |
December | 0.168962E+09 | 91854239.58 | 77107517.22 | 0.170831E+09 | 0.417012E+09 |
Annual Sum or Average | 0.307027E+10 | 0.166420E+10 | 0.140607E+10 | 0.472618E+10 | 0.281114E+10 |
Minimum of Months | 0.168962E+09 | 91854239.58 | 77107517.22 | 0.170831E+09 | 83923471.70 |
Maximum of Months | 0.337944E+09 | 0.180425E+09 | 0.157519E+09 | 0.611569E+09 | 0.417012E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36857004.76 | 0.00 | 36857004.76 | 6683707.91 | 0.226833E+09 |
February | 40650861.33 | 0.00 | 40650861.33 | 17541727.95 | 0.181764E+09 |
March | 58918365.05 | 7469.43 | 58910895.62 | 36940777.27 | 0.178032E+09 |
April | 66098155.95 | 773908.19 | 65324247.76 | 66338192.80 | 0.121880E+09 |
May | 81110663.58 | 6280402.56 | 74830261.02 | 0.109993E+09 | 86105337.64 |
June | 83295495.23 | 10513332.86 | 72782162.37 | 0.156601E+09 | 50093354.62 |
July | 79290157.87 | 7712107.14 | 71578050.73 | 0.147542E+09 | 46885859.49 |
August | 67370407.03 | 1846240.70 | 65524166.33 | 0.116323E+09 | 62924764.17 |
September | 56505936.74 | 59249.37 | 56446687.36 | 83484263.01 | 0.106948E+09 |
October | 48422085.50 | 0.00 | 48422085.50 | 36118853.65 | 0.159930E+09 |
November | 37829908.95 | 0.00 | 37829908.95 | 7261190.68 | 0.220298E+09 |
December | 36571559.54 | 0.00 | 36571559.54 | 3718534.36 | 0.261756E+09 |
Annual Sum or Average | 0.692921E+09 | 27192710.26 | 0.665728E+09 | 0.788547E+09 | 0.170345E+10 |
Minimum of Months | 36571559.54 | 0.00 | 36571559.54 | 3718534.36 | 46885859.49 |
Maximum of Months | 83295495.23 | 10513332.86 | 74830261.02 | 0.156601E+09 | 0.261756E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36856015.13 | 0.00 | 36856015.13 | 6683238.54 | 0.226831E+09 |
February | 40649791.77 | 0.00 | 40649791.77 | 17541169.35 | 0.181763E+09 |
March | 58916844.09 | 7469.08 | 58909375.01 | 36939602.22 | 0.178030E+09 |
April | 66096528.93 | 773871.92 | 65322657.01 | 66337084.74 | 0.121878E+09 |
May | 81108515.27 | 6280108.19 | 74828407.08 | 0.109991E+09 | 86104083.45 |
June | 83293270.51 | 10512840.09 | 72780430.42 | 0.156600E+09 | 50092321.01 |
July | 79287954.77 | 7711745.67 | 71576209.10 | 0.147540E+09 | 46885040.62 |
August | 67368664.94 | 1846154.17 | 65522510.77 | 0.116321E+09 | 62923878.81 |
September | 56504568.91 | 59246.59 | 56445322.32 | 83483111.22 | 0.106946E+09 |
October | 48420839.83 | 0.00 | 48420839.83 | 36117907.30 | 0.159929E+09 |
November | 37828943.99 | 0.00 | 37828943.99 | 7260932.21 | 0.220297E+09 |
December | 36570544.81 | 0.00 | 36570544.81 | 3718249.13 | 0.261755E+09 |
Annual Sum or Average | 0.692902E+09 | 27191435.70 | 0.665711E+09 | 0.788533E+09 | 0.170343E+10 |
Minimum of Months | 36570544.81 | 0.00 | 36570544.81 | 3718249.13 | 46885040.62 |
Maximum of Months | 83293270.51 | 10512840.09 | 74828407.08 | 0.156600E+09 | 0.261755E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108216E+09 | 75274506.49 | 32941507.45 | 0.107677E+09 | 0.101594E+09 |
February | 0.126970E+09 | 89621293.39 | 37349040.95 | 0.142487E+09 | 86798845.69 |
March | 0.198634E+09 | 0.140628E+09 | 58005836.25 | 0.240686E+09 | 97050663.99 |
April | 0.240383E+09 | 0.178979E+09 | 61403251.88 | 0.305974E+09 | 83420445.80 |
May | 0.274579E+09 | 0.205009E+09 | 69570387.29 | 0.352870E+09 | 86109016.73 |
June | 0.281284E+09 | 0.219110E+09 | 62173778.36 | 0.372095E+09 | 69649694.36 |
July | 0.251137E+09 | 0.182041E+09 | 69095869.58 | 0.333933E+09 | 58571270.22 |
August | 0.234496E+09 | 0.169959E+09 | 64536652.57 | 0.305888E+09 | 69420580.59 |
September | 0.206796E+09 | 0.155087E+09 | 51709334.96 | 0.259760E+09 | 91867469.57 |
October | 0.159685E+09 | 0.115948E+09 | 43736998.18 | 0.180293E+09 | 0.104899E+09 |
November | 0.119252E+09 | 88060714.76 | 31191739.09 | 0.116895E+09 | 0.116607E+09 |
December | 99751282.81 | 65580051.47 | 34171231.34 | 88275400.26 | 0.118736E+09 |
Annual Sum or Average | 0.230118E+10 | 0.168530E+10 | 0.615886E+09 | 0.280683E+10 | 0.108472E+10 |
Minimum of Months | 99751282.81 | 65580051.47 | 31191739.09 | 88275400.26 | 58571270.22 |
Maximum of Months | 0.281284E+09 | 0.219110E+09 | 69570387.29 | 0.372095E+09 | 0.118736E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108216E+09 | 75274506.49 | 32941507.45 | 0.107677E+09 | 0.101594E+09 |
February | 0.126970E+09 | 89621293.39 | 37349040.95 | 0.142487E+09 | 86798845.69 |
March | 0.198634E+09 | 0.140628E+09 | 58005836.25 | 0.240686E+09 | 97050663.99 |
April | 0.240383E+09 | 0.178979E+09 | 61403251.88 | 0.305974E+09 | 83420445.80 |
May | 0.274579E+09 | 0.205009E+09 | 69570387.29 | 0.352870E+09 | 86109016.73 |
June | 0.281284E+09 | 0.219110E+09 | 62173778.36 | 0.372095E+09 | 69649694.36 |
July | 0.251137E+09 | 0.182041E+09 | 69095869.58 | 0.333933E+09 | 58571270.22 |
August | 0.234496E+09 | 0.169959E+09 | 64536652.57 | 0.305888E+09 | 69420580.59 |
September | 0.206796E+09 | 0.155087E+09 | 51709334.96 | 0.259760E+09 | 91867469.57 |
October | 0.159685E+09 | 0.115948E+09 | 43736998.18 | 0.180293E+09 | 0.104899E+09 |
November | 0.119252E+09 | 88060714.76 | 31191739.09 | 0.116895E+09 | 0.116607E+09 |
December | 99751282.81 | 65580051.47 | 34171231.34 | 88275400.26 | 0.118736E+09 |
Annual Sum or Average | 0.230118E+10 | 0.168530E+10 | 0.615886E+09 | 0.280683E+10 | 0.108472E+10 |
Minimum of Months | 99751282.81 | 65580051.47 | 31191739.09 | 88275400.26 | 58571270.22 |
Maximum of Months | 0.281284E+09 | 0.219110E+09 | 69570387.29 | 0.372095E+09 | 0.118736E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108216E+09 | 75274506.49 | 32941507.45 | 0.107677E+09 | 0.101594E+09 |
February | 0.126970E+09 | 89621293.39 | 37349040.95 | 0.142487E+09 | 86798845.69 |
March | 0.198634E+09 | 0.140628E+09 | 58005836.25 | 0.240686E+09 | 97050663.99 |
April | 0.240383E+09 | 0.178979E+09 | 61403251.88 | 0.305974E+09 | 83420445.80 |
May | 0.274579E+09 | 0.205009E+09 | 69570387.29 | 0.352870E+09 | 86109016.73 |
June | 0.281284E+09 | 0.219110E+09 | 62173778.36 | 0.372095E+09 | 69649694.36 |
July | 0.251137E+09 | 0.182041E+09 | 69095869.58 | 0.333933E+09 | 58571270.22 |
August | 0.234496E+09 | 0.169959E+09 | 64536652.57 | 0.305888E+09 | 69420580.59 |
September | 0.206796E+09 | 0.155087E+09 | 51709334.96 | 0.259760E+09 | 91867469.57 |
October | 0.159685E+09 | 0.115948E+09 | 43736998.18 | 0.180293E+09 | 0.104899E+09 |
November | 0.119252E+09 | 88060714.76 | 31191739.09 | 0.116895E+09 | 0.116607E+09 |
December | 99751282.81 | 65580051.47 | 34171231.34 | 88275400.26 | 0.118736E+09 |
Annual Sum or Average | 0.230118E+10 | 0.168530E+10 | 0.615886E+09 | 0.280683E+10 | 0.108472E+10 |
Minimum of Months | 99751282.81 | 65580051.47 | 31191739.09 | 88275400.26 | 58571270.22 |
Maximum of Months | 0.281284E+09 | 0.219110E+09 | 69570387.29 | 0.372095E+09 | 0.118736E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108216E+09 | 75274506.49 | 32941507.45 | 0.107677E+09 | 0.101594E+09 |
February | 0.126970E+09 | 89621293.39 | 37349040.95 | 0.142487E+09 | 86798845.69 |
March | 0.198634E+09 | 0.140628E+09 | 58005836.25 | 0.240686E+09 | 97050663.99 |
April | 0.240383E+09 | 0.178979E+09 | 61403251.88 | 0.305974E+09 | 83420445.80 |
May | 0.274579E+09 | 0.205009E+09 | 69570387.29 | 0.352870E+09 | 86109016.73 |
June | 0.281284E+09 | 0.219110E+09 | 62173778.36 | 0.372095E+09 | 69649694.36 |
July | 0.251137E+09 | 0.182041E+09 | 69095869.58 | 0.333933E+09 | 58571270.22 |
August | 0.234496E+09 | 0.169959E+09 | 64536652.57 | 0.305888E+09 | 69420580.59 |
September | 0.206796E+09 | 0.155087E+09 | 51709334.96 | 0.259760E+09 | 91867469.57 |
October | 0.159685E+09 | 0.115948E+09 | 43736998.18 | 0.180293E+09 | 0.104899E+09 |
November | 0.119252E+09 | 88060714.76 | 31191739.09 | 0.116895E+09 | 0.116607E+09 |
December | 99751282.81 | 65580051.47 | 34171231.34 | 88275400.26 | 0.118736E+09 |
Annual Sum or Average | 0.230118E+10 | 0.168530E+10 | 0.615886E+09 | 0.280683E+10 | 0.108472E+10 |
Minimum of Months | 99751282.81 | 65580051.47 | 31191739.09 | 88275400.26 | 58571270.22 |
Maximum of Months | 0.281284E+09 | 0.219110E+09 | 69570387.29 | 0.372095E+09 | 0.118736E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108216E+09 | 75274506.49 | 32941507.45 | 0.107677E+09 | 0.101594E+09 |
February | 0.126970E+09 | 89621293.39 | 37349040.95 | 0.142487E+09 | 86798845.69 |
March | 0.198634E+09 | 0.140628E+09 | 58005836.25 | 0.240686E+09 | 97050663.99 |
April | 0.240383E+09 | 0.178979E+09 | 61403251.88 | 0.305974E+09 | 83420445.80 |
May | 0.274579E+09 | 0.205009E+09 | 69570387.29 | 0.352870E+09 | 86109016.73 |
June | 0.281284E+09 | 0.219110E+09 | 62173778.36 | 0.372095E+09 | 69649694.36 |
July | 0.251137E+09 | 0.182041E+09 | 69095869.58 | 0.333933E+09 | 58571270.22 |
August | 0.234496E+09 | 0.169959E+09 | 64536652.57 | 0.305888E+09 | 69420580.59 |
September | 0.206796E+09 | 0.155087E+09 | 51709334.96 | 0.259760E+09 | 91867469.57 |
October | 0.159685E+09 | 0.115948E+09 | 43736998.18 | 0.180293E+09 | 0.104899E+09 |
November | 0.119252E+09 | 88060714.76 | 31191739.09 | 0.116895E+09 | 0.116607E+09 |
December | 99751282.81 | 65580051.47 | 34171231.34 | 88275400.26 | 0.118736E+09 |
Annual Sum or Average | 0.230118E+10 | 0.168530E+10 | 0.615886E+09 | 0.280683E+10 | 0.108472E+10 |
Minimum of Months | 99751282.81 | 65580051.47 | 31191739.09 | 88275400.26 | 58571270.22 |
Maximum of Months | 0.281284E+09 | 0.219110E+09 | 69570387.29 | 0.372095E+09 | 0.118736E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108216E+09 | 75274506.49 | 32941507.45 | 0.107677E+09 | 0.101594E+09 |
February | 0.126970E+09 | 89621293.39 | 37349040.95 | 0.142487E+09 | 86798845.69 |
March | 0.198634E+09 | 0.140628E+09 | 58005836.25 | 0.240686E+09 | 97050663.99 |
April | 0.240383E+09 | 0.178979E+09 | 61403251.88 | 0.305974E+09 | 83420445.80 |
May | 0.274579E+09 | 0.205009E+09 | 69570387.29 | 0.352870E+09 | 86109016.73 |
June | 0.281284E+09 | 0.219110E+09 | 62173778.36 | 0.372095E+09 | 69649694.36 |
July | 0.251137E+09 | 0.182041E+09 | 69095869.58 | 0.333933E+09 | 58571270.22 |
August | 0.234496E+09 | 0.169959E+09 | 64536652.57 | 0.305888E+09 | 69420580.59 |
September | 0.206796E+09 | 0.155087E+09 | 51709334.96 | 0.259760E+09 | 91867469.57 |
October | 0.159685E+09 | 0.115948E+09 | 43736998.18 | 0.180293E+09 | 0.104899E+09 |
November | 0.119252E+09 | 88060714.76 | 31191739.09 | 0.116895E+09 | 0.116607E+09 |
December | 99751282.81 | 65580051.47 | 34171231.34 | 88275400.26 | 0.118736E+09 |
Annual Sum or Average | 0.230118E+10 | 0.168530E+10 | 0.615886E+09 | 0.280683E+10 | 0.108472E+10 |
Minimum of Months | 99751282.81 | 65580051.47 | 31191739.09 | 88275400.26 | 58571270.22 |
Maximum of Months | 0.281284E+09 | 0.219110E+09 | 69570387.29 | 0.372095E+09 | 0.118736E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108216E+09 | 75274506.49 | 32941507.45 | 0.107677E+09 | 0.101594E+09 |
February | 0.126970E+09 | 89621293.39 | 37349040.95 | 0.142487E+09 | 86798845.69 |
March | 0.198634E+09 | 0.140628E+09 | 58005836.25 | 0.240686E+09 | 97050663.99 |
April | 0.240383E+09 | 0.178979E+09 | 61403251.88 | 0.305974E+09 | 83420445.80 |
May | 0.274579E+09 | 0.205009E+09 | 69570387.29 | 0.352870E+09 | 86109016.73 |
June | 0.281284E+09 | 0.219110E+09 | 62173778.36 | 0.372095E+09 | 69649694.36 |
July | 0.251137E+09 | 0.182041E+09 | 69095869.58 | 0.333933E+09 | 58571270.22 |
August | 0.234496E+09 | 0.169959E+09 | 64536652.57 | 0.305888E+09 | 69420580.59 |
September | 0.206796E+09 | 0.155087E+09 | 51709334.96 | 0.259760E+09 | 91867469.57 |
October | 0.159685E+09 | 0.115948E+09 | 43736998.18 | 0.180293E+09 | 0.104899E+09 |
November | 0.119252E+09 | 88060714.76 | 31191739.09 | 0.116895E+09 | 0.116607E+09 |
December | 99751282.81 | 65580051.47 | 34171231.34 | 88275400.26 | 0.118736E+09 |
Annual Sum or Average | 0.230118E+10 | 0.168530E+10 | 0.615886E+09 | 0.280683E+10 | 0.108472E+10 |
Minimum of Months | 99751282.81 | 65580051.47 | 31191739.09 | 88275400.26 | 58571270.22 |
Maximum of Months | 0.281284E+09 | 0.219110E+09 | 69570387.29 | 0.372095E+09 | 0.118736E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108216E+09 | 75274506.49 | 32941507.45 | 0.107677E+09 | 0.101594E+09 |
February | 0.126970E+09 | 89621293.39 | 37349040.95 | 0.142487E+09 | 86798845.69 |
March | 0.198634E+09 | 0.140628E+09 | 58005836.25 | 0.240686E+09 | 97050663.99 |
April | 0.240383E+09 | 0.178979E+09 | 61403251.88 | 0.305974E+09 | 83420445.80 |
May | 0.274579E+09 | 0.205009E+09 | 69570387.29 | 0.352870E+09 | 86109016.73 |
June | 0.281284E+09 | 0.219110E+09 | 62173778.36 | 0.372095E+09 | 69649694.36 |
July | 0.251137E+09 | 0.182041E+09 | 69095869.58 | 0.333933E+09 | 58571270.22 |
August | 0.234496E+09 | 0.169959E+09 | 64536652.57 | 0.305888E+09 | 69420580.59 |
September | 0.206796E+09 | 0.155087E+09 | 51709334.96 | 0.259760E+09 | 91867469.57 |
October | 0.159685E+09 | 0.115948E+09 | 43736998.18 | 0.180293E+09 | 0.104899E+09 |
November | 0.119252E+09 | 88060714.76 | 31191739.09 | 0.116895E+09 | 0.116607E+09 |
December | 99751282.81 | 65580051.47 | 34171231.34 | 88275400.26 | 0.118736E+09 |
Annual Sum or Average | 0.230118E+10 | 0.168530E+10 | 0.615886E+09 | 0.280683E+10 | 0.108472E+10 |
Minimum of Months | 99751282.81 | 65580051.47 | 31191739.09 | 88275400.26 | 58571270.22 |
Maximum of Months | 0.281284E+09 | 0.219110E+09 | 69570387.29 | 0.372095E+09 | 0.118736E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108216E+09 | 75274506.49 | 32941507.45 | 0.107677E+09 | 0.101594E+09 |
February | 0.126970E+09 | 89621293.39 | 37349040.95 | 0.142487E+09 | 86798845.69 |
March | 0.198634E+09 | 0.140628E+09 | 58005836.25 | 0.240686E+09 | 97050663.99 |
April | 0.240383E+09 | 0.178979E+09 | 61403251.88 | 0.305974E+09 | 83420445.80 |
May | 0.274579E+09 | 0.205009E+09 | 69570387.29 | 0.352870E+09 | 86109016.73 |
June | 0.281284E+09 | 0.219110E+09 | 62173778.36 | 0.372095E+09 | 69649694.36 |
July | 0.251137E+09 | 0.182041E+09 | 69095869.58 | 0.333933E+09 | 58571270.22 |
August | 0.234496E+09 | 0.169959E+09 | 64536652.57 | 0.305888E+09 | 69420580.59 |
September | 0.206796E+09 | 0.155087E+09 | 51709334.96 | 0.259760E+09 | 91867469.57 |
October | 0.159685E+09 | 0.115948E+09 | 43736998.18 | 0.180293E+09 | 0.104899E+09 |
November | 0.119252E+09 | 88060714.76 | 31191739.09 | 0.116895E+09 | 0.116607E+09 |
December | 99751282.81 | 65580051.47 | 34171231.34 | 88275400.26 | 0.118736E+09 |
Annual Sum or Average | 0.230118E+10 | 0.168530E+10 | 0.615886E+09 | 0.280683E+10 | 0.108472E+10 |
Minimum of Months | 99751282.81 | 65580051.47 | 31191739.09 | 88275400.26 | 58571270.22 |
Maximum of Months | 0.281284E+09 | 0.219110E+09 | 69570387.29 | 0.372095E+09 | 0.118736E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108216E+09 | 75274506.49 | 32941507.45 | 0.107677E+09 | 0.101594E+09 |
February | 0.126970E+09 | 89621293.39 | 37349040.95 | 0.142487E+09 | 86798845.69 |
March | 0.198634E+09 | 0.140628E+09 | 58005836.25 | 0.240686E+09 | 97050663.99 |
April | 0.240383E+09 | 0.178979E+09 | 61403251.88 | 0.305974E+09 | 83420445.80 |
May | 0.274579E+09 | 0.205009E+09 | 69570387.29 | 0.352870E+09 | 86109016.73 |
June | 0.281284E+09 | 0.219110E+09 | 62173778.36 | 0.372095E+09 | 69649694.36 |
July | 0.251137E+09 | 0.182041E+09 | 69095869.58 | 0.333933E+09 | 58571270.22 |
August | 0.234496E+09 | 0.169959E+09 | 64536652.57 | 0.305888E+09 | 69420580.59 |
September | 0.206796E+09 | 0.155087E+09 | 51709334.96 | 0.259760E+09 | 91867469.57 |
October | 0.159685E+09 | 0.115948E+09 | 43736998.18 | 0.180293E+09 | 0.104899E+09 |
November | 0.119252E+09 | 88060714.76 | 31191739.09 | 0.116895E+09 | 0.116607E+09 |
December | 99751282.81 | 65580051.47 | 34171231.34 | 88275400.26 | 0.118736E+09 |
Annual Sum or Average | 0.230118E+10 | 0.168530E+10 | 0.615886E+09 | 0.280683E+10 | 0.108472E+10 |
Minimum of Months | 99751282.81 | 65580051.47 | 31191739.09 | 88275400.26 | 58571270.22 |
Maximum of Months | 0.281284E+09 | 0.219110E+09 | 69570387.29 | 0.372095E+09 | 0.118736E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 142.06 | 433.17 | 160.66 | 75.09 | 85.58 | 0.00 | 0.00 |
February | 185.62 | 388.33 | 183.40 | 79.49 | 103.91 | 0.00 | 0.00 |
March | 290.78 | 346.11 | 248.11 | 109.31 | 138.80 | 0.00 | 0.00 |
April | 401.30 | 249.07 | 285.31 | 126.87 | 158.44 | 0.00 | 0.00 |
May | 504.32 | 178.79 | 312.91 | 139.42 | 173.50 | 0.00 | 0.00 |
June | 591.45 | 107.16 | 310.61 | 140.43 | 170.18 | 0.00 | 0.00 |
July | 524.56 | 96.46 | 277.98 | 114.52 | 163.47 | 0.00 | 0.00 |
August | 471.03 | 129.10 | 261.67 | 108.88 | 152.79 | 0.00 | 0.00 |
September | 435.79 | 222.24 | 260.31 | 120.85 | 139.46 | 0.00 | 0.00 |
October | 292.31 | 313.45 | 222.32 | 108.56 | 113.76 | 0.00 | 0.00 |
November | 180.84 | 433.19 | 184.56 | 94.22 | 90.34 | 0.00 | 0.00 |
December | 119.71 | 496.22 | 153.47 | 68.59 | 84.89 | 0.00 | 0.00 |
Annual Sum or Average | 345.66 | 282.24 | 238.66 | 107.27 | 131.39 | 0.00 | 0.00 |
Minimum of Months | 119.71 | 96.46 | 153.47 | 68.59 | 84.89 | 0.00 | 0.00 |
Maximum of Months | 591.45 | 496.22 | 312.91 | 140.43 | 173.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 402.02 | 379.31 | 404.03 | 281.04 | 122.99 | 0.00 | 0.00 |
February | 588.98 | 358.79 | 524.84 | 370.46 | 154.39 | 0.00 | 0.00 |
March | 898.62 | 362.35 | 741.61 | 525.05 | 216.57 | 0.00 | 0.00 |
April | 1180.46 | 321.84 | 927.40 | 690.51 | 236.90 | 0.00 | 0.00 |
May | 1317.47 | 321.49 | 1025.16 | 765.42 | 259.75 | 0.00 | 0.00 |
June | 1435.55 | 268.71 | 1085.20 | 845.33 | 239.87 | 0.00 | 0.00 |
July | 1246.76 | 218.68 | 937.64 | 679.66 | 257.97 | 0.00 | 0.00 |
August | 1142.05 | 259.19 | 875.51 | 634.55 | 240.95 | 0.00 | 0.00 |
September | 1002.16 | 354.43 | 797.82 | 598.33 | 199.50 | 0.00 | 0.00 |
October | 673.14 | 391.65 | 596.20 | 432.90 | 163.30 | 0.00 | 0.00 |
November | 450.98 | 449.87 | 460.08 | 339.74 | 120.34 | 0.00 | 0.00 |
December | 329.58 | 443.31 | 372.43 | 244.85 | 127.58 | 0.00 | 0.00 |
Annual Sum or Average | 890.04 | 343.96 | 729.70 | 534.40 | 195.30 | 0.00 | 0.00 |
Minimum of Months | 329.58 | 218.68 | 372.43 | 244.85 | 120.34 | 0.00 | 0.00 |
Maximum of Months | 1435.55 | 449.87 | 1085.20 | 845.33 | 259.75 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.380506E+09 | 0.116021E+10 | 0.430324E+09 | 0.201117E+09 | 0.229208E+09 | 0.00 | 0.00 |
February | 0.449046E+09 | 0.939456E+09 | 0.443684E+09 | 0.192312E+09 | 0.251372E+09 | 0.00 | 0.00 |
March | 0.778835E+09 | 0.927027E+09 | 0.664546E+09 | 0.292776E+09 | 0.371770E+09 | 0.00 | 0.00 |
April | 0.104018E+10 | 0.645600E+09 | 0.739531E+09 | 0.328843E+09 | 0.410687E+09 | 0.00 | 0.00 |
May | 0.135076E+10 | 0.478882E+09 | 0.838108E+09 | 0.373411E+09 | 0.464697E+09 | 0.00 | 0.00 |
June | 0.153305E+10 | 0.277759E+09 | 0.805108E+09 | 0.364003E+09 | 0.441105E+09 | 0.00 | 0.00 |
July | 0.140499E+10 | 0.258355E+09 | 0.744548E+09 | 0.306720E+09 | 0.437828E+09 | 0.00 | 0.00 |
August | 0.126161E+10 | 0.345784E+09 | 0.700858E+09 | 0.291635E+09 | 0.409223E+09 | 0.00 | 0.00 |
September | 0.112958E+10 | 0.576037E+09 | 0.674736E+09 | 0.313251E+09 | 0.361485E+09 | 0.00 | 0.00 |
October | 0.782925E+09 | 0.839546E+09 | 0.595475E+09 | 0.290780E+09 | 0.304695E+09 | 0.00 | 0.00 |
November | 0.468737E+09 | 0.112283E+10 | 0.478383E+09 | 0.244227E+09 | 0.234156E+09 | 0.00 | 0.00 |
December | 0.320644E+09 | 0.132908E+10 | 0.411066E+09 | 0.183708E+09 | 0.227357E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109009E+11 | 0.890057E+10 | 0.752637E+10 | 0.338278E+10 | 0.414358E+10 | 0.00 | 0.00 |
Minimum of Months | 0.320644E+09 | 0.258355E+09 | 0.411066E+09 | 0.183708E+09 | 0.227357E+09 | 0.00 | 0.00 |
Maximum of Months | 0.153305E+10 | 0.132908E+10 | 0.838108E+09 | 0.373411E+09 | 0.464697E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.107677E+10 | 0.101594E+10 | 0.108216E+10 | 0.752745E+09 | 0.329415E+09 | 0.00 | 0.00 |
February | 0.142487E+10 | 0.867988E+09 | 0.126970E+10 | 0.896213E+09 | 0.373490E+09 | 0.00 | 0.00 |
March | 0.240686E+10 | 0.970506E+09 | 0.198634E+10 | 0.140628E+10 | 0.580058E+09 | 0.00 | 0.00 |
April | 0.305974E+10 | 0.834204E+09 | 0.240383E+10 | 0.178979E+10 | 0.614033E+09 | 0.00 | 0.00 |
May | 0.352870E+10 | 0.861089E+09 | 0.274579E+10 | 0.205009E+10 | 0.695704E+09 | 0.00 | 0.00 |
June | 0.372095E+10 | 0.696494E+09 | 0.281284E+10 | 0.219110E+10 | 0.621738E+09 | 0.00 | 0.00 |
July | 0.333933E+10 | 0.585712E+09 | 0.251137E+10 | 0.182041E+10 | 0.690959E+09 | 0.00 | 0.00 |
August | 0.305888E+10 | 0.694201E+09 | 0.234496E+10 | 0.169959E+10 | 0.645367E+09 | 0.00 | 0.00 |
September | 0.259760E+10 | 0.918674E+09 | 0.206796E+10 | 0.155087E+10 | 0.517093E+09 | 0.00 | 0.00 |
October | 0.180292E+10 | 0.104899E+10 | 0.159685E+10 | 0.115948E+10 | 0.437370E+09 | 0.00 | 0.00 |
November | 0.116895E+10 | 0.116607E+10 | 0.119252E+10 | 0.880607E+09 | 0.311917E+09 | 0.00 | 0.00 |
December | 0.882754E+09 | 0.118736E+10 | 0.997513E+09 | 0.655801E+09 | 0.341712E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.280683E+11 | 0.108472E+11 | 0.230118E+11 | 0.168530E+11 | 0.615886E+10 | 0.00 | 0.00 |
Minimum of Months | 0.882754E+09 | 0.585712E+09 | 0.997513E+09 | 0.655801E+09 | 0.311917E+09 | 0.00 | 0.00 |
Maximum of Months | 0.372095E+10 | 0.118736E+10 | 0.281284E+10 | 0.219110E+10 | 0.695704E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.32 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.73 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.69 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.47 | -2.7 | 4.72 | 3.37 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.20 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.01 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.90 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.10 | 12.00 | 3.28 | 15.47 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.80 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.00 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.23 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.89 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.89 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.90 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.36 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.84 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.49 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.18 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.19 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.18 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.16 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.85 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.82 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.87 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.43 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.94 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.94 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.16 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.3 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.4 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.3 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.5 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.97 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.40 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.97 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.88 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -2.9 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.0 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.4 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.97 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.15 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.74 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.71 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.10 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.18 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.87 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.16 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.64 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.62 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.55 | 03-NOV-13:20 | 22.07 | 7.93 | 2.10 | 9.59 | 80.17 | 943.83 |
December | 8.27 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.27 | 12.80 | -0.6 | 1.50 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.87 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 943.83 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.70 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.39 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.10 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.27 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.867087E+09 | -782880957.3 | 0.00 | 0.00 | 744.00 | 0.00 | -84206179.6 | 59.00 | 0.00 | 0.00 |
February | 0.793275E+09 | -718606355.2 | 0.00 | 0.00 | 672.00 | 0.00 | -74668566.1 | 59.00 | 0.00 | 0.00 |
March | 0.888917E+09 | -809049496.1 | 0.00 | 0.00 | 744.00 | 0.00 | -79867600.9 | 58.99 | 0.00 | 0.00 |
April | 0.773327E+09 | -701664380.2 | 0.00 | 0.00 | 720.00 | 0.00 | -71662440.9 | 58.99 | 0.00 | 0.00 |
May | 0.741121E+09 | -670062249.4 | 0.00 | 0.00 | 744.00 | 0.00 | -71058309.5 | 58.99 | 0.00 | 0.00 |
June | 0.682227E+09 | -614656711.1 | 0.00 | 0.00 | 720.00 | 0.00 | -67569845.3 | 58.98 | 0.00 | 0.00 |
July | 0.634042E+09 | -564843577.3 | 0.00 | 0.00 | 744.00 | 0.00 | -69198756.8 | 58.99 | 0.00 | 0.00 |
August | 0.677037E+09 | -607224808.4 | 0.00 | 0.00 | 744.00 | 0.00 | -69811880.2 | 58.98 | 0.00 | 0.00 |
September | 0.662402E+09 | -594507126.4 | 0.00 | 0.00 | 720.00 | 0.00 | -67895331.4 | 58.99 | 0.00 | 0.00 |
October | 0.719240E+09 | -646629505.8 | 0.00 | 0.00 | 744.00 | 0.00 | -72610077.4 | 58.99 | 0.00 | 0.00 |
November | 0.752604E+09 | -676110578.8 | 0.00 | 0.00 | 720.00 | 0.00 | -76493393.3 | 58.99 | 0.00 | 0.00 |
December | 0.837603E+09 | -753468107.1 | 0.00 | 0.00 | 744.00 | 0.00 | -84135350.9 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.902888E+10 | -.813970E+10 | 8760.00 | -889177732.5 | 58.99 | |||||
Minimum of Months | 0.634042E+09 | -809049496.1 | 0.00 | 0.00 | 672.00 | 0.00 | -84206179.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.888917E+09 | -564843577.3 | 0.00 | 0.00 | 744.00 | 0.00 | -67569845.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 373.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 398.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 400.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 377.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 365.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 295.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4125.67 | ||||||||||
Minimum of Months | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.194232E+10 | 27326.57 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131386E+10 | 27326.57 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.755152E+09 | 27326.57 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40795884.93 | 7847.84 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 235487.21 | 773.76 | 27-MAY-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.525826E+09 | 27326.57 | 20-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209616E+10 | 27326.57 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.667435E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.209616E+10 | 27326.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.418905E+10 | 88151.95 | 27-JAN-06:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.229891E+10 | 88151.95 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.571488E+09 | 88151.95 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.452875E+09 | 78088.22 | 28-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.530798E+10 | 88151.95 | 26-DEC-01:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128203E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.530798E+10 | 88151.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 26.16 | 26.16 | 0.02 | 13-JAN-15:00 | 0.02 | 0.00 |
February | 0.00 | 0.00 | 49800495.99 | 49800495.99 | 2186.53 | 21-FEB-16:00 | 2186.53 | 0.00 |
March | 0.00 | 0.00 | 0.381664E+09 | 0.381663E+09 | 4805.06 | 14-MAR-16:00 | 4805.06 | 0.00 |
April | 0.00 | 0.00 | 0.310969E+10 | 0.310143E+10 | 18995.59 | 29-APR-05:01 | 17104.74 | 0.00 |
May | 0.00 | 0.00 | 0.735415E+10 | 0.715724E+10 | 20464.69 | 23-MAY-05:01 | 16481.39 | 0.00 |
June | 0.00 | 0.00 | 0.106933E+11 | 0.102441E+11 | 21220.40 | 28-JUN-05:01 | 13545.21 | 0.00 |
July | 0.00 | 0.00 | 0.123736E+11 | 0.102016E+11 | 24284.45 | 22-JUL-05:01 | 11078.84 | 0.00 |
August | 0.00 | 0.00 | 0.114852E+11 | 0.996120E+10 | 23440.17 | 03-AUG-05:01 | 13699.38 | 0.00 |
September | 0.00 | 0.00 | 0.931066E+10 | 0.814754E+10 | 22848.17 | 22-SEP-05:01 | 12437.88 | 0.00 |
October | 0.00 | 0.00 | 0.383540E+10 | 0.347750E+10 | 21616.92 | 04-OCT-05:01 | 12355.12 | 0.00 |
November | 0.00 | 0.00 | 0.277594E+09 | 0.275909E+09 | 6288.01 | 03-NOV-16:00 | 6288.01 | 0.00 |
December | 0.00 | 0.00 | 2036.75 | 2036.75 | 0.16 | 16-DEC-15:00 | 0.16 | 0.00 |
Annual Sum or Average | 0.588710E+11 | 0.529979E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 26.16 | 26.16 | 0.02 | 0.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.123736E+11 | 0.102441E+11 | 24284.45 | 17104.74 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.439331E+10 | 0.438138E+10 | 61907.44 | 30-APR-09:51 | 55957.74 | 0.00 |
May | 0.00 | 0.00 | 0.174415E+11 | 0.169655E+11 | 68962.16 | 28-MAY-09:01 | 48201.56 | 0.00 |
June | 0.00 | 0.00 | 0.331092E+11 | 0.319532E+11 | 71693.64 | 19-JUN-17:55 | 43877.38 | 0.00 |
July | 0.00 | 0.00 | 0.372182E+11 | 0.313998E+11 | 76181.97 | 21-JUL-20:31 | 39141.49 | 0.00 |
August | 0.00 | 0.00 | 0.310069E+11 | 0.275695E+11 | 73747.42 | 03-AUG-00:21 | 41824.35 | 0.00 |
September | 0.00 | 0.00 | 0.224408E+11 | 0.197128E+11 | 73231.89 | 03-SEP-23:01 | 35669.89 | 0.00 |
October | 0.00 | 0.00 | 0.488133E+10 | 0.433668E+10 | 70991.85 | 03-OCT-18:01 | 46396.31 | 0.00 |
November | 0.00 | 0.00 | 7204.39 | 6589.90 | 1.14 | 03-NOV-14:00 | 1.04 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.150491E+12 | 0.136319E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.372182E+11 | 0.319532E+11 | 76181.97 | 55957.74 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142064E+10 | 0.43 | 1405.19 | 04-JAN-12:15 | 1.08 |
February | 0.130226E+10 | 0.43 | 1405.19 | 01-FEB-09:30 | 1.08 |
March | 0.151547E+10 | 0.45 | 1405.19 | 01-MAR-10:30 | 1.08 |
April | 0.139609E+10 | 0.42 | 1405.19 | 01-APR-06:05 | 1.08 |
May | 0.147955E+10 | 0.43 | 1405.19 | 01-MAY-10:40 | 1.08 |
June | 0.149772E+10 | 0.46 | 1405.19 | 01-JUN-16:00 | 1.08 |
July | 0.145104E+10 | 0.44 | 1405.19 | 03-JUL-10:40 | 1.07 |
August | 0.156449E+10 | 0.47 | 1405.19 | 01-AUG-15:00 | 1.07 |
September | 0.144710E+10 | 0.44 | 1405.19 | 01-SEP-06:40 | 1.06 |
October | 0.140395E+10 | 0.40 | 1405.19 | 03-OCT-06:40 | 1.07 |
November | 0.134391E+10 | 0.41 | 1405.19 | 01-NOV-12:10 | 1.07 |
December | 0.142119E+10 | 0.43 | 1405.19 | 29-DEC-09:30 | 1.08 |
Annual Sum or Average | 0.172434E+11 | 0.43 | |||
Minimum of Months | 0.130226E+10 | 0.40 | 1405.19 | 1.06 | |
Maximum of Months | 0.156449E+10 | 0.47 | 1405.19 | 1.08 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.349401E+10 | 0.56 | 3366.62 | 05-JAN-08:50 | 1.04 |
February | 0.315708E+10 | 0.49 | 3366.62 | 03-FEB-07:10 | 1.04 |
March | 0.362135E+10 | 0.43 | 3366.62 | 01-MAR-08:50 | 1.04 |
April | 0.336641E+10 | 0.41 | 3366.62 | 03-APR-15:00 | 1.04 |
May | 0.371515E+10 | 0.50 | 3366.62 | 01-MAY-14:00 | 1.04 |
June | 0.402274E+10 | 0.62 | 3366.62 | 01-JUN-07:42 | 1.03 |
July | 0.401583E+10 | 0.61 | 3366.62 | 01-JUL-07:40 | 1.02 |
August | 0.410227E+10 | 0.59 | 3366.62 | 01-AUG-07:47 | 1.02 |
September | 0.360670E+10 | 0.48 | 3366.62 | 02-SEP-08:45 | 1.02 |
October | 0.337919E+10 | 0.40 | 3366.62 | 02-OCT-09:45 | 1.02 |
November | 0.321776E+10 | 0.40 | 3366.62 | 03-NOV-13:40 | 1.03 |
December | 0.354045E+10 | 0.59 | 3366.62 | 26-DEC-07:50 | 1.04 |
Annual Sum or Average | 0.432389E+11 | 0.51 | |||
Minimum of Months | 0.315708E+10 | 0.40 | 3366.62 | 1.02 | |
Maximum of Months | 0.410227E+10 | 0.62 | 3366.62 | 1.04 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.28 | 1.27 |
February | 0.89 | 1.35 |
March | 0.81 | 2.53 |
April | 1.61 | 0.78 |
May | 3.84 | 0.22 |
June | 5.72 | 0.26 |
July | 4.64 | 0.19 |
August | 4.90 | 0.19 |
September | 4.54 | 0.18 |
October | 2.37 | 0.90 |
November | 1.47 | 1.99 |
December | 0.75 | 0.92 |
Annual Sum or Average | 32.82 | 0.51 |
Minimum of Months | 0.75 | 0.18 |
Maximum of Months | 5.72 | 2.53 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.33 | 0.00 |
May | 1.10 | 0.00 |
June | 4.33 | 0.00 |
July | 6.53 | 0.00 |
August | 5.66 | 0.00 |
September | 4.25 | 0.00 |
October | 1.08 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 23.28 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 6.53 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.08 | 0.00 |
May | 1.49 | 0.00 |
June | 12.00 | 0.00 |
July | 9.51 | 0.00 |
August | 7.10 | 0.00 |
September | 5.19 | 0.00 |
October | 0.22 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 35.61 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 12.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.142064E+10 | 0.283352E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.131593E+10 | 0.191421E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.161930E+10 | 0.110626E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.226587E+10 | 62078334.14 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.354480E+10 | 365398.78 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.464325E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.490465E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.476094E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.400412E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.243393E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.141872E+10 | 0.773277E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.142119E+10 | 0.305412E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.337533E+11 | 0.974383E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.131593E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.490465E+10 | 0.305412E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.349401E+10 | 0.622371E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.315708E+10 | 0.339219E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.362135E+10 | 0.841282E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.473504E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.918099E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.148124E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.155383E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.136854E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.103542E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.483729E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.321776E+10 | 0.674481E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.354045E+10 | 0.785824E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.901743E+11 | 0.189899E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.315708E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.155383E+11 | 0.785824E+10 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.142064E+10 | 26.16 | 0.194232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130226E+10 | 49800495.99 | 0.131386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151547E+10 | 0.381664E+09 | 0.755152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139609E+10 | 0.310969E+10 | 40795884.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147955E+10 | 0.735415E+10 | 235487.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149772E+10 | 0.106933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145104E+10 | 0.123736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156449E+10 | 0.114852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144710E+10 | 0.931066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140395E+10 | 0.383540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134391E+10 | 0.277594E+09 | 0.525826E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142119E+10 | 2036.75 | 0.209616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172434E+11 | 0.588710E+11 | 0.667435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130226E+10 | 26.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.156449E+10 | 0.123736E+11 | 0.209616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.349401E+10 | 0.00 | 0.418905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.315708E+10 | 0.00 | 0.229891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.362135E+10 | 0.00 | 0.571488E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.336641E+10 | 0.439331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.371515E+10 | 0.174415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.402274E+10 | 0.331092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.401583E+10 | 0.372182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.410227E+10 | 0.310069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.360670E+10 | 0.224408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.337919E+10 | 0.488133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.321776E+10 | 7204.39 | 0.452875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.354045E+10 | 0.00 | 0.530798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.432389E+11 | 0.150491E+12 | 0.128203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.315708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.410227E+10 | 0.372182E+11 | 0.530798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.142064E+10 | 0.00 | 0.00 | 0.00 | 7.29 | 0.00 | 0.283352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130226E+10 | 0.00 | 0.00 | 0.00 | 13671625.58 | 0.00 | 0.191421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151547E+10 | 0.00 | 0.00 | 0.00 | 0.103829E+09 | 0.00 | 0.110626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139609E+10 | 0.00 | 0.00 | 0.00 | 0.869787E+09 | 0.00 | 62078334.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147955E+10 | 0.00 | 0.00 | 0.00 | 0.206525E+10 | 0.00 | 365398.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149772E+10 | 0.00 | 0.00 | 0.00 | 0.314552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145104E+10 | 0.00 | 0.00 | 0.00 | 0.345361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156449E+10 | 0.00 | 0.00 | 0.00 | 0.319645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144710E+10 | 0.00 | 0.00 | 0.00 | 0.255701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140395E+10 | 0.00 | 0.00 | 0.00 | 0.102998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134391E+10 | 0.00 | 0.00 | 0.00 | 74811526.84 | 0.00 | 0.773277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142119E+10 | 0.00 | 0.00 | 0.00 | 567.36 | 0.00 | 0.305412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172434E+11 | 0.00 | 0.00 | 0.00 | 0.165099E+11 | 0.00 | 0.974383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.130226E+10 | 0.00 | 0.00 | 0.00 | 7.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.156449E+10 | 0.00 | 0.00 | 0.00 | 0.345361E+10 | 0.00 | 0.305412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.349401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.315708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.362135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.336641E+10 | 0.00 | 0.00 | 0.00 | 0.136863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.371515E+10 | 0.00 | 0.00 | 0.00 | 0.546584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.402274E+10 | 0.00 | 0.00 | 0.00 | 0.107896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.401583E+10 | 0.00 | 0.00 | 0.00 | 0.115224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.410227E+10 | 0.00 | 0.00 | 0.00 | 0.958318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.360670E+10 | 0.00 | 0.00 | 0.00 | 0.674754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.337919E+10 | 0.00 | 0.00 | 0.00 | 0.145810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.321776E+10 | 0.00 | 0.00 | 0.00 | 2129.40 | 0.00 | 0.674481E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.354045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.432389E+11 | 0.00 | 0.00 | 0.00 | 0.469354E+11 | 0.00 | 0.189899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.315708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.410227E+10 | 0.00 | 0.00 | 0.00 | 0.115224E+11 | 0.00 | 0.785824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.583468E+09 | 0.00 | 0.00 | 12994.51 | 0.00 | 0.586094E+09 | 38565084.59 | 0.00 | 0.13 |
February | 0.555725E+09 | 0.00 | 0.00 | 153772.09 | 0.00 | 0.339003E+09 | 0.226020E+09 | 0.00 | 0.21 |
March | 0.554669E+09 | 218633.82 | 0.00 | 965596.09 | 0.00 | 0.112665E+09 | 0.939888E+09 | 0.00 | 0.40 |
April | 86527387.46 | 94465775.70 | 0.00 | 2970142.41 | 0.00 | 0.00 | 0.153942E+10 | 0.00 | 0.51 |
May | 14071402.85 | 0.340209E+09 | 0.00 | 6173891.81 | 0.00 | 0.00 | 0.890496E+09 | 0.00 | 0.46 |
June | 318897.94 | 0.733021E+09 | 0.00 | 8153992.60 | 0.00 | 0.00 | 0.232553E+09 | 0.00 | 0.33 |
July | 0.00 | 0.166565E+10 | 0.00 | 3447425.35 | 0.00 | 0.00 | 25418214.97 | 0.00 | 0.32 |
August | 0.00 | 0.977854E+09 | 0.00 | 7637234.05 | 258708.86 | 0.00 | 0.324266E+09 | 0.00 | 0.46 |
September | 6103028.10 | 0.752479E+09 | 0.00 | 7268405.19 | 0.00 | 0.00 | 0.613044E+09 | 0.00 | 0.46 |
October | 16519911.92 | 0.152824E+09 | 0.00 | 6149496.16 | 0.00 | 0.00 | 0.233057E+10 | 0.00 | 0.68 |
November | 0.382450E+09 | 0.00 | 0.00 | 1731533.00 | 0.00 | 96546432.84 | 0.149995E+10 | 0.00 | 0.41 |
December | 0.607804E+09 | 0.00 | 0.00 | 14568.80 | 0.00 | 0.643899E+09 | 51632774.59 | 0.00 | 0.13 |
Annual Sum or Average | 0.280766E+10 | 0.471672E+10 | 0.00 | 44679052.04 | 258708.86 | 0.177821E+10 | 0.871183E+10 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 12994.51 | 0.00 | 0.00 | 25418214.97 | 0.00 | 0.13 |
Maximum of Months | 0.607804E+09 | 0.166565E+10 | 0.00 | 8153992.60 | 258708.86 | 0.643899E+09 | 0.233057E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.296817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229289E+09 | 0.00 | 0.00 | 0.17 |
February | 0.253375E+10 | 0.00 | 0.00 | 0.00 | 5237.89 | 85100173.69 | 0.00 | 0.00 | 0.18 |
March | 0.263941E+10 | 0.00 | 0.00 | 0.00 | 2133201.85 | 34354862.10 | 0.00 | 0.00 | 0.19 |
April | 0.140890E+10 | 0.166333E+09 | 0.00 | 2281392.17 | 17831995.82 | 0.00 | 0.922643E+09 | 0.00 | 0.34 |
May | 0.313103E+09 | 0.888923E+09 | 0.00 | 6861440.35 | 0.00 | 0.00 | 0.168643E+10 | 0.00 | 0.45 |
June | 42406866.63 | 0.215307E+10 | 0.00 | 8642933.36 | 486017.97 | 0.00 | 0.122652E+10 | 0.00 | 0.44 |
July | 13912090.69 | 0.365642E+10 | 0.00 | 5951062.08 | 389719.51 | 0.00 | 0.104622E+10 | 0.00 | 0.46 |
August | 49068477.41 | 0.231448E+10 | 0.00 | 11233416.72 | 41047.48 | 0.00 | 0.196385E+10 | 0.00 | 0.52 |
September | 0.131152E+09 | 0.170382E+10 | 0.00 | 10603464.34 | 0.00 | 0.00 | 0.175076E+10 | 0.00 | 0.49 |
October | 0.134254E+10 | 0.307123E+09 | 0.00 | 5083849.93 | 0.00 | 0.00 | 0.289873E+10 | 0.00 | 0.45 |
November | 0.277805E+10 | 0.00 | 0.00 | 30409.10 | 0.00 | 18937479.77 | 71706556.86 | 0.00 | 0.18 |
December | 0.324242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275551E+09 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.174629E+11 | 0.111902E+11 | 0.00 | 50687968.05 | 20887220.51 | 0.643233E+09 | 0.115669E+11 | 0.00 | 0.34 |
Minimum of Months | 13912090.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.324242E+10 | 0.365642E+10 | 0.00 | 11233416.72 | 17831995.82 | 0.275551E+09 | 0.289873E+10 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |