Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2020-06-03 19:11:19
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1071.60 | 221.63 | 221.63 |
Net Site Energy | 1071.60 | 221.63 | 221.63 |
Total Source Energy | 3393.74 | 701.89 | 701.89 |
Net Source Energy | 3393.74 | 701.89 | 701.89 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 241.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 99.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 93.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.11 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1071.60 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 241.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 99.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 32.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 60.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22.11 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 119.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 73.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 221.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 119.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 73.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 221.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1071.595 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1071.595 | 100.00 |
Total On-Site and Utility Electric Sources | 1071.595 | 100.00 |
Total Electricity End Uses | 1071.595 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 105.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 670.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.6337 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.5069 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.5069 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 06-MAY-14:00 | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 25675.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6648.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1671.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 79296.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 25675.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4342.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1671.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 765.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1507.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 314.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 294.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 70.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3393.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 158.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 60.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 701.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 158.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 60.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 701.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.15 |
ZONE2 FINE STORAGE DIRECT AIR | 2.77 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 0.976839 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 0.976839 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 40545.96 |
PSZ-OFFICE HEATING COIL | 26472.55 |
PSZ-FINE STORAGE HEATING COIL | 123538.01 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.00 | 1.00 | 1.15 |
PSZ-FINE STORAGE | 2.77 | 2.77 | 2.77 | 2.77 | 2.77 | 2.77 | 1.00 | 1.00 | 2.77 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.15 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 2.77 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.15 | 1.15 | 1.15 | 1.15 | 23456.00 | 26472.55 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.77 | 2.77 | 2.77 | 2.77 | 68712.00 | 123538.01 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.15 | 0.576395 | 1.15 | 22908.14 | 23456.00 | 11728.00 | 23456.00 | 0.730108 | 0.730110 | 0.730110 | 0.730110 |
PSZ-FINE STORAGE COOLING COIL | 2.77 | 1.38 | 2.77 | 68711.94 | 68712.00 | 34356.00 | 68712.00 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.15 | 1314.31 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.77 | 3028.53 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.634 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.707 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.507 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.507 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.507 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.066 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2518.900 | 10.634 | 503.780 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2518.900 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11853.648 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11853.648 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27263.390 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27263.390 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.5669 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.5669 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.5669 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.665 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.665 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.665 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
5 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
6 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
7 | 4 | 0.76473447E-12 | 0.16134122E-15 | -0.23523330E-14 | 0.11950429E-15 |
8 | 3 | -0.37912003E-03 | 0.39537906E-06 | -0.54939862E-04 | 0.14674673E-12 |
9 | 2 | 1.7262835 | 0.86963410E-02 | 1.1303724 | -0.72683208E-04 |
10 | 1 | -7.1462370 | 0.22614561 | -17.033763 | 0.33084980 |
11 | 0 | 5.7997145 | 0.14453958 | 16.282827 | |
12 | 4 | 0.76473447E-12 | 0.16134122E-15 | -0.23523330E-14 | 0.11950429E-15 |
13 | 3 | -0.37912003E-03 | 0.39537906E-06 | -0.54939862E-04 | 0.14674673E-12 |
14 | 2 | 1.7262835 | 0.86963410E-02 | 1.1303724 | -0.72683208E-04 |
15 | 1 | -7.1462370 | 0.22614561 | -17.033763 | 0.33084980 |
16 | 0 | 5.7997145 | 0.14453958 | 16.282827 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.23523330E-14 | 0.16134122E-15 | 0.76473447E-12 | 0.11950429E-15 |
85 | 3 | -0.54939862E-04 | 0.39537906E-06 | -0.37912003E-03 | 0.14674673E-12 |
86 | 2 | 1.1303724 | 0.86963410E-02 | 1.7262835 | -0.72683208E-04 |
87 | 1 | -17.033763 | 0.22614561 | -7.1462370 | 0.33084980 |
88 | 0 | 16.282827 | 0.14453958 | 5.7997145 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.11_SHGC_0.25 | 28 | 1 | VerySmooth | 5.826 | 0.251 | 0.110 | 0.250 |
2 | SKYLIGHT_U_0.75_SHGC_0.35 | 29 | 1 | VerySmooth | 4.262 | 0.355 | 0.203 | 0.351 |
3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 30 | 1 | VerySmooth | 4.262 | 0.355 | 0.203 | 0.351 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41448 | 0.41448 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.37958 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.20312 | 0.36283 | 0.36283 | 0.35000 | 0.14371 | 0.19477 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.20312 | 0.36283 | 0.36283 | 0.35000 | 0.14371 | 0.19477 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11671.37409 | 14005.64890 | 0.96066 | 1.15279 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 34.46333 | 1.71339E-002 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 1691.43080 | 2029.71696 | 4.69556E-002 | 0.10228 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 20.10000 | 1.47983E-002 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 35933.04333 | 43119.65199 | 2.30586 | 2.76703 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 35.20000 | 1.71339E-002 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.42471 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10000 | 1.47983E-002 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 | |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20000 | 1.71339E-002 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.97684 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10000 | 1.47983E-002 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 17896.99 | 1.15279 | 1.15279 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 2461.78 | 0.10228 | 0.10228 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 53552.38 | 2.76703 | 2.76703 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 10221.95 | 0.42471 | 0.42471 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.15279 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.76703 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97684 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 0.97684 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 40545.96106 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 0.00000 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.15279 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.15279 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.15279 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.15279 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.15279 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.15279 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.76703 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.76703 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.76703 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.76703 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.76703 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.76703 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.15279 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.76703 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.15279 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.15279 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.15279 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.15279 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.15279 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.15279 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57640 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.15279 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22908.14031 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 23456.00000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11728.00000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 23456.00000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73011 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73011 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73011 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73011 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23456.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26472.54649 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.15279 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1314.30753 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26472.54649 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.76703 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.76703 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.76703 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.76703 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.76703 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.76703 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.38352 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.76703 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 68711.94438 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 68712.00000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 34356.00000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 68712.00000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 68712.00000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 123538.00964 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.76703 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3028.53211 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 123538.00964 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 22560.8 | 10.39 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 66561.2 | 13.53 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 6 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 3.3310896617E-002 | 6.3596125262E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1814964682 | 0.2372386781 | Pass | Pass | 0.2491693307 | 0.8436252962 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 2.1095999395E-002 | 1.9170400121E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.523 | 0.567 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.523 | 0.567 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.523 | 0.567 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.523 | 0.567 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.523 | 0.567 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.523 | 0.567 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.523 | 0.567 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.523 | 0.567 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.523 | 0.567 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.523 | 0.567 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.369 | 0.389 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_1.11_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 5.826 | 0.251 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_1.11_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 5.826 | 0.251 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_1.11_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 5.826 | 0.251 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_1.11_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 5.826 | 0.251 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 5.111 | 0.298 | 0.296 | ||||||||||||
North Total or Average | 6.51 | 5.826 | 0.251 | 0.250 | ||||||||||||
Non-North Total or Average | 26.02 | 4.933 | 0.310 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.6337 | 236.88 | 2518.90 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.62 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.5069 | 1393.41 | 11853.65 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 135.00 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.5069 | 3204.84 | 27263.39 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 310.50 |
Interior Lighting Total | 8.6111 | 4835.13 | 41635.94 | 476.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 6311.00 | AstronomicalClock | - | 83.83 | 83.83 | 99.31 | |
Exterior Lighting Total | 6311.00 | 99.31 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23456.00 | 17125.46 | 6330.54 | 0.73 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 68712.00 | 46454.81 | 22257.19 | 0.68 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 22560.8 | 10.39 | ||||
PSZ-FINE STORAGE COOLING COIL | 66561.2 | 13.53 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 40545.96 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26472.55 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 123538.01 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.98 | 90.76 | 92.91 | 1.00 | 4.17 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.15 | 1314.31 | 1140.11 | 1.00 | 1.33 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.77 | 3028.53 | 1094.51 | 1.00 | 1.24 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11671.37 | 14005.65 | 59.13 | 0.961 | 1.153 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 23.90 | 23.90 | 0.00827 | 34.46 | 0.01713 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 35933.04 | 43119.65 | 30.95 | 2.306 | 2.767 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 26.70 | 26.70 | 0.00882 | 35.20 | 0.01713 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00378 | 35.20 | 0.01713 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 1691.43 | 2029.72 | 8.57 | 0.047 | 0.102 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.01235 | 20.10 | 0.01480 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.425 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 0.00 | 15.56 | 0.00800 | 20.10 | 0.01480 | 0.425 | 0.00 | |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 0.00 | 10.00 | 0.01600 | 20.10 | 0.01480 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.15 | 1.15 | 0.10 | 0.10 | 1.1528 | 1.1528 | 1.1528 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.77 | 2.77 | 0.42 | 0.42 | 2.7670 | 2.7670 | 2.7670 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 40545.961 | 40545.961 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 40545.96 | 40545.96 | 0.976839 | 10.00 | 10.00 | 0.01600000 | 43.33 | 27.10 | 0.01600000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 10.00 | 0.01600000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 23456.000 | 0.000 | 1.152790 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 23456.00 | 19770.43 | 1.152790 | 24.84 | 17.13 | 0.00905575 | 12.00 | 11.25 | 0.00800000 | 34.46 | 0.01713393 | 25.62 | 8.8728 | 23.90 | 0.00826920 | 44.7797 | 11615.00 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26472.546 | 26472.546 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 26472.55 | 26472.55 | 1.152790 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 8.8728 | 21.10 | 0.01234831 | 78.7473 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 68712.000 | 0.000 | 2.767030 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 68712.00 | 52729.16 | 2.767030 | 28.00 | 19.02 | 0.01009594 | 12.00 | 11.25 | 0.00800000 | 35.20 | 0.01713393 | 25.80 | 15.3490 | 26.70 | 0.00881980 | 40.4035 | 34027.90 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 123538.010 | 123538.010 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 123538.01 | 67581.07 | 2.767032 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 15.3490 | 15.56 | 0.00800000 | 72.7370 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 40545.961 | 40545.961 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.2036 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.976839 | 1.17571868 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 40545.96 | 40545.96 | 1.0000 | 1.17571868 | 0.976839 | 10.00 | 10.00 | 0.01600000 | 50360.9 | 43.33 | 27.10 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40545.96 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 10.00 | 0.01600000 | 10.00 | 0.01600000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23456.000 | 0.000 | 1.152790 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6742 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 23456.00 | 19770.43 | 1.0000 | 1.38749226 | 1.152790 | 24.84 | 17.13 | 0.00905575 | 48022.6 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23456.00 | 34.46 | 0.01713393 | 25.62 | 0.10228487 | 8.8728 | 23.90 | 0.00826920 | 23.90 | 0.00826920 | 44.7797 | 11615.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26472.546 | 26472.546 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.152790 | 1.38749252 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 26472.55 | 26472.55 | 1.0000 | 1.38749252 | 1.152790 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26472.55 | 20.10 | 0.01479830 | 20.10 | 0.10228487 | 8.8728 | 21.10 | 0.00000000 | 21.10 | 0.01234831 | 78.7473 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 68712.000 | 0.000 | 2.767030 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6078 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 68712.00 | 52729.16 | 1.0000 | 3.33038342 | 2.767030 | 28.00 | 19.02 | 0.01009594 | 53912.6 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 68712.00 | 35.20 | 0.01713393 | 25.80 | 0.42471267 | 15.3490 | 26.70 | 0.00881980 | 26.70 | 0.00881980 | 40.4035 | 34027.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 123538.010 | 123538.010 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.767032 | 3.33038625 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 123538.01 | 67581.07 | 1.0000 | 3.33038625 | 2.767032 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 123538.01 | 20.10 | 0.01479830 | 20.10 | 0.42471267 | 15.3490 | 0.00 | 0.00000000 | 15.56 | 0.00800000 | 72.7370 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3636.00 | 670.17 | 670.17 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 3636.00 | 670.17 | 670.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.00 | 111.17 | 0.00 | 105.33 |
ZONE2 FINE STORAGE | 0.00 | 326.17 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 437.33 | 0.00 | 105.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.359 | 0.352 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1071.60 | 5421.86 | 01-JAN-06:20 | 79296.71 | 06-MAY-15:00 |
Electricity:Building | 648.05 | 4938.86 | 01-JAN-00:10 | 47606.95 | 02-JAN-12:00 |
Electricity:Zone:ZONE1 OFFICE | 62.57 | 1027.15 | 01-JAN-00:10 | 3852.05 | 02-JAN-08:10 |
InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.62 | 453.40 | 01-JAN-00:10 | 1939.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 450.49 | 2726.34 | 01-JAN-00:10 | 33679.30 | 02-JAN-11:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 310.51 | 2726.34 | 01-JAN-00:10 | 23173.88 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 22.11 | 483.00 | 02-JAN-06:10 | 1704.71 | 12-JAN-12:30 |
WaterSystems:Electricity | 22.11 | 483.00 | 02-JAN-06:10 | 1704.71 | 12-JAN-12:30 |
Water Heater:WaterSystems:Electricity | 22.11 | 483.00 | 02-JAN-06:10 | 1704.71 | 12-JAN-12:30 |
Fans:Electricity | 93.06 | 0.00 | 01-JAN-00:10 | 6648.13 | 11-JAN-08:30 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 32.64 | 0.00 | 01-JAN-00:10 | 2305.29 | 02-JAN-15:20 |
Ventilation (simple):Fans:Electricity | 32.64 | 0.00 | 01-JAN-00:10 | 2305.29 | 02-JAN-15:20 |
ElectricityPurchased:Facility | 1071.60 | 5421.86 | 01-JAN-06:20 | 79296.71 | 06-MAY-15:00 |
ElectricityPurchased:Plant | 1071.60 | 5421.86 | 01-JAN-06:20 | 79296.71 | 06-MAY-15:00 |
Cogeneration:ElectricityPurchased | 1071.60 | 5421.86 | 01-JAN-06:20 | 79296.71 | 06-MAY-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1071.60 | 5421.86 | 01-JAN-06:20 | 79296.71 | 06-MAY-15:00 |
ElectricityNet:Plant | 1071.60 | 5421.86 | 01-JAN-06:20 | 79296.71 | 06-MAY-15:00 |
Cogeneration:ElectricityNet | 1071.60 | 5421.86 | 01-JAN-06:20 | 79296.71 | 06-MAY-15:00 |
Electricity:HVAC | 302.12 | 0.00 | 01-JAN-00:10 | 31884.65 | 06-MAY-15:30 |
General:Fans:Electricity | 60.42 | 0.00 | 01-JAN-00:10 | 4342.84 | 02-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 241.70 | 0.00 | 01-JAN-00:10 | 27541.81 | 06-MAY-15:30 |
ExteriorLights:Electricity | 99.31 | 0.00 | 01-JAN-06:20 | 6311.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 99.31 | 0.00 | 01-JAN-06:20 | 6311.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Gas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1283.50 | 0.00 | 01-JAN-00:10 | 143370.88 | 06-MAY-15:40 |
EnergyTransfer:Building | 436.87 | 0.00 | 01-JAN-00:10 | 52750.67 | 06-MAY-15:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 110.39 | 0.00 | 01-JAN-00:10 | 13662.75 | 12-JUN-16:10 |
Heating:EnergyTransfer | 0.01 | 0.00 | 01-JAN-00:10 | 819.53 | 15-SEP-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 436.86 | 0.00 | 01-JAN-00:10 | 52750.67 | 06-MAY-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 110.39 | 0.00 | 01-JAN-00:10 | 13662.75 | 12-JUN-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 326.48 | 0.00 | 01-JAN-00:10 | 41344.01 | 06-MAY-15:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.01 | 0.00 | 01-JAN-00:10 | 819.53 | 15-SEP-06:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 326.47 | 0.00 | 01-JAN-00:10 | 41344.01 | 06-MAY-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 846.64 | 0.00 | 01-JAN-00:10 | 95000.20 | 16-JUN-15:40 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 846.64 | 0.00 | 01-JAN-00:10 | 95000.20 | 16-JUN-15:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.000 | -110.387 | 0.000 | 0.000 | 3.575 | 30.619 | 31.946 | 17.275 | 0.000 | 8.175 | 23.196 | 0.000 | -3.612 | 0.000 | -0.787 | -0.000 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 0.007 | -326.454 | 0.000 | 0.000 | 0.000 | 135.003 | 0.000 | 0.000 | 0.000 | 19.392 | 178.967 | 0.000 | 0.000 | 0.000 | -6.915 | -0.001 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 310.507 | 107.336 | 29.863 | 0.000 | 14.266 | 149.116 | 0.000 | -6.349 | 0.000 | -604.738 | -0.017 |
Total Facility | 0.000 | 0.000 | 0.007 | -436.841 | 0.000 | 0.000 | 3.575 | 476.129 | 139.282 | 47.139 | 0.000 | 41.832 | 351.278 | 0.000 | -9.961 | 0.000 | -612.440 | -0.019 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 23-FEB-06:01 | 0.00 | 0.00 | 0.00 | -20088.70 | 0.00 | 0.00 | 26.51 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 19640.75 | 0.00 | -440.18 | 0.00 | -291.47 | 0.00 |
ZONE2 FINE STORAGE | 16-JAN-16:03 | 0.00 | 0.00 | 0.00 | -53351.93 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 1068.69 | 51097.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-FEB-06:01 | 0.00 | 0.00 | 0.00 | -66121.78 | 0.00 | 0.00 | 25.71 | 4491.05 | 2623.78 | 0.00 | 0.00 | 0.00 | 60641.84 | 0.00 | -876.70 | 0.00 | -783.90 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 28-JUL-06:05 | 0.00 | 0.00 | 2493.13 | 0.00 | 0.00 | 0.00 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -488.18 | -9117.15 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-JUL-06:05 | -5976.70 | 5976.70 | 2493.13 | -5976.70 | 0.00 | 0.00 | 75.12 | 24528.16 | 3006.28 | 116.64 | 0.00 | 457.51 | 0.00 | 0.00 | -222.49 | 0.00 | -4469.40 | -20008.25 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1528 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.1528 | 0.0887 | 1.0000 | 0.1023 | 0.0887 | ||
PSZ-FINE STORAGE | 2.7670 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.7670 | 0.1535 | 1.0000 | 0.4247 | 0.1535 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1528 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.1528 | 1.0000 | 1.0000 | 0.1023 | 0.0887 | ||
PSZ-FINE STORAGE | 2.7670 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.7670 | 1.0000 | 1.0000 | 0.4247 | 0.1535 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.1528 | 1.1528 | 1.1528 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.7670 | 2.7670 | 2.7670 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1528 | 1.1528 | 1.1528 | 1.1528 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.7670 | 2.7670 | 2.7670 | 2.7670 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.1528 | 1.1528 | 1.1528 | 0.1023 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.7670 | 2.7670 | 2.7670 | 0.4247 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1528 | 1.1528 | 1.1528 | 1.1528 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.7670 | 2.7670 | 2.7670 | 2.7670 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 4835.13 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 105.33 |
Number of hours not met | 105.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 241.70 | 27541.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 476.13 | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 99.31 | 6311.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 32.64 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 60.42 | 4342.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 22.11 | 1704.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 1071.60 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1071.60 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 98.47 |
Space Heating | 0.00 |
Space Cooling | 49.99 |
Fans (All) | 19.25 |
Service Water Heating | 4.57 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 221.63 |
Subtotal | 221.63 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 44.43 |
Space Heating | 0.00 |
Space Cooling | 22.56 |
Fans (All) | 8.68 |
Service Water Heating | 2.06 |
Receptacle Equipment | 13.00 |
Miscellaneous | 9.27 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.866710E+10 | 18463.78 | 24-JAN-06:01 | 19.57 | 17.62 | 0.249110E+09 | 301.62 | 28-JAN-16:10 | 31.42 | 22.49 |
February | 0.840383E+10 | 20090.07 | 23-FEB-06:01 | 22.85 | 19.63 | 0.229199E+09 | 301.62 | 21-FEB-15:00 | 31.90 | 23.95 |
March | 0.102115E+11 | 17407.82 | 04-MAR-06:01 | 24.10 | 20.00 | 0.269065E+09 | 301.62 | 04-MAR-16:10 | 32.83 | 22.26 |
April | 0.971710E+10 | 15854.19 | 27-APR-05:01 | 26.00 | 23.87 | 0.249150E+09 | 301.58 | 01-APR-12:09 | 33.78 | 26.51 |
May | 0.101018E+11 | 15802.60 | 31-MAY-05:01 | 24.17 | 24.17 | 0.259129E+09 | 303.83 | 01-MAY-12:09 | 34.40 | 26.30 |
June | 0.103267E+11 | 15713.80 | 20-JUN-05:01 | 24.00 | 24.00 | 0.259146E+09 | 307.06 | 16-JUN-12:09 | 35.17 | 28.23 |
July | 0.910300E+10 | 17643.47 | 17-JUL-05:01 | 24.08 | 23.27 | 0.249141E+09 | 301.58 | 22-JUL-07:10 | 23.75 | 23.01 |
August | 0.968322E+10 | 15636.96 | 30-AUG-05:01 | 24.00 | 23.38 | 0.269061E+09 | 301.71 | 15-AUG-12:09 | 33.32 | 27.85 |
September | 0.900212E+10 | 16091.43 | 06-SEP-05:01 | 25.08 | 24.21 | 0.249137E+09 | 301.58 | 30-SEP-10:00 | 32.80 | 30.05 |
October | 0.851179E+10 | 15718.13 | 11-OCT-05:01 | 24.00 | 23.32 | 0.249120E+09 | 301.58 | 14-OCT-12:09 | 30.33 | 26.72 |
November | 0.832204E+10 | 17357.26 | 25-NOV-06:01 | 20.58 | 18.85 | 0.239155E+09 | 301.58 | 25-NOV-15:09 | 25.82 | 22.38 |
December | 0.833954E+10 | 17841.75 | 21-DEC-06:01 | 18.07 | 17.39 | 0.249099E+09 | 301.58 | 16-DEC-16:10 | 28.50 | 24.76 |
Annual Sum or Average | 0.110390E+12 | 0.301951E+10 | ||||||||
Minimum of Months | 0.832204E+10 | 15636.96 | 18.07 | 17.39 | 0.229199E+09 | 301.58 | 23.75 | 22.26 | ||
Maximum of Months | 0.103267E+11 | 20090.07 | 26.00 | 24.21 | 0.269065E+09 | 307.06 | 35.17 | 30.05 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237299E+11 | 53353.95 | 16-JAN-16:03 | 30.92 | 22.09 | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 | 23.60 |
February | 0.253445E+11 | 51411.92 | 22-FEB-18:06 | 30.72 | 20.90 | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 | 22.46 |
March | 0.317590E+11 | 48038.95 | 29-MAR-17:06 | 30.83 | 22.31 | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 | 22.97 |
April | 0.324647E+11 | 46710.57 | 23-APR-17:03 | 31.75 | 24.83 | 0.00 | 0.00 | 01-APR-00:10 | 27.53 | 25.10 |
May | 0.321786E+11 | 45564.43 | 29-MAY-17:12 | 33.67 | 26.67 | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 | 26.40 |
June | 0.334820E+11 | 43613.00 | 18-JUN-17:03 | 29.33 | 26.20 | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 | 23.91 |
July | 0.273827E+11 | 49730.47 | 16-JUL-16:03 | 24.83 | 23.31 | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 | 24.33 |
August | 0.264637E+11 | 41439.72 | 27-AUG-17:53 | 30.00 | 26.93 | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 | 24.75 |
September | 0.264672E+11 | 44695.86 | 13-SEP-17:06 | 31.83 | 25.54 | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 | 25.66 |
October | 0.229015E+11 | 46094.43 | 08-OCT-15:32 | 30.37 | 25.44 | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 | 25.35 |
November | 0.224123E+11 | 49995.25 | 05-NOV-13:32 | 30.83 | 23.73 | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 | 24.37 |
December | 0.218841E+11 | 51509.49 | 03-DEC-15:32 | 30.00 | 22.23 | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 | 23.43 |
Annual Sum or Average | 0.326470E+12 | 0.00 | ||||||||
Minimum of Months | 0.218841E+11 | 41439.72 | 24.83 | 20.90 | 0.00 | 0.00 | 23.80 | 22.46 | ||
Maximum of Months | 0.334820E+11 | 53353.95 | 33.67 | 26.93 | 0.00 | 0.00 | 28.62 | 26.40 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 | 23.60 | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 | 23.60 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 26.43 | 22.46 | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 | 22.46 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 | 22.97 | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 | 22.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 | 25.10 | 0.00 | 0.00 | 01-APR-00:10 | 27.53 | 25.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 | 26.40 | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 | 26.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 | 23.91 | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 | 23.91 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 | 24.33 | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 | 24.33 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 | 24.75 | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 | 24.75 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 | 25.66 | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 | 25.66 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 | 25.35 | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 | 25.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 | 24.37 | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 | 24.37 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 | 23.43 | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 | 23.43 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 23.80 | 22.46 | 0.00 | 0.00 | 23.80 | 22.46 | ||
Maximum of Months | 0.00 | 0.00 | 28.62 | 26.40 | 0.00 | 0.00 | 28.62 | 26.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10963.95 | 36.55 | 09-JAN-07:10 | 24.00 |
February | 221203.88 | 1843.37 | 06-FEB-07:04 | 24.00 |
March | 903377.14 | 1927.72 | 22-MAR-06:05 | 24.37 |
April | 617760.91 | 2323.92 | 24-APR-06:05 | 24.93 |
May | 1314000.04 | 2191.73 | 17-MAY-06:04 | 24.07 |
June | 912506.76 | 1898.03 | 26-JUN-06:05 | 24.40 |
July | 1178384.25 | 2493.31 | 28-JUL-06:05 | 25.17 |
August | 519823.43 | 2089.21 | 16-AUG-06:05 | 24.42 |
September | 871023.94 | 2458.59 | 15-SEP-06:07 | 25.23 |
October | 255168.78 | 471.06 | 10-OCT-06:10 | 23.95 |
November | 312498.96 | 2083.33 | 22-NOV-07:05 | 24.33 |
December | 3073.61 | 5.12 | 22-DEC-07:10 | 23.08 |
Annual Sum or Average | 7119785.65 | |||
Minimum of Months | 3073.61 | 5.12 | 23.08 | |
Maximum of Months | 1314000.04 | 2493.31 | 25.23 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.256100E+10 | 1939.55 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.233575E+10 | 1939.55 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.266872E+10 | 1939.55 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.252182E+10 | 1939.55 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.261486E+10 | 1939.55 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.257569E+10 | 1939.55 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.256100E+10 | 1939.55 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.266872E+10 | 1939.55 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.252182E+10 | 1939.55 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.256100E+10 | 1939.55 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.246796E+10 | 1939.55 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.256100E+10 | 1939.55 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.306193E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.233575E+10 | 1939.55 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.266872E+10 | 1939.55 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112294E+11 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102778E+11 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.118738E+11 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.111270E+11 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.115516E+11 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.114492E+11 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112294E+11 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.118738E+11 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.111270E+11 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112294E+11 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108048E+11 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112294E+11 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135003E+12 | ||||
Minimum of Months | 0.102778E+11 | 10075.60 | 0.00 | 0.00 | |
Maximum of Months | 0.118738E+11 | 10075.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.258277E+11 | 23173.88 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.236390E+11 | 23173.88 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.273097E+11 | 23173.88 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.255921E+11 | 23173.88 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.265687E+11 | 23173.88 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.263332E+11 | 23173.88 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.258277E+11 | 23173.88 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.273097E+11 | 23173.88 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.255921E+11 | 23173.88 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.258277E+11 | 23173.88 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.248511E+11 | 23173.88 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.258277E+11 | 23173.88 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.236390E+11 | 23173.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.273097E+11 | 23173.88 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578172E+09 | 0.118063E+09 |
February | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629103E+09 | 62235627.07 |
March | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.896288E+09 | 81419283.00 |
April | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839461E+09 | 34980893.53 |
May | 0.565842E+09 | 0.261486E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.907876E+09 | 43801284.84 |
June | 0.565842E+09 | 0.257569E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.919892E+09 | 48939460.96 |
July | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552443E+09 | 47212892.35 |
August | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727092E+09 | 72404520.09 |
September | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598673E+09 | 44819916.63 |
October | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519741E+09 | 60189241.44 |
November | 0.522316E+09 | 0.246796E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533398E+09 | 62232679.95 |
December | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472870E+09 | 0.110773E+09 |
Annual Sum or Average | 0.659424E+10 | 0.306193E+11 | 0.319458E+11 | 0.817501E+10 | 0.787072E+09 | ||||
Minimum of Months | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472870E+09 | 34980893.53 |
Maximum of Months | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.919892E+09 | 0.118063E+09 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892774E+09 | 0.107723E+10 |
February | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145656E+10 | 0.423884E+09 |
March | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247545E+10 | 0.628305E+09 |
April | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251982E+10 | 0.131539E+09 |
May | 0.00 | 0.115516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290908E+10 | 0.323443E+09 |
June | 0.00 | 0.114492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265169E+10 | 0.290232E+09 |
July | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143238E+10 | 0.385749E+09 |
August | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163286E+10 | 0.698556E+09 |
September | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125741E+10 | 0.409933E+09 |
October | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.886964E+09 | 0.631748E+09 |
November | 0.00 | 0.108048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663409E+09 | 0.699713E+09 |
December | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613431E+09 | 0.121449E+10 |
Annual Sum or Average | 0.135003E+12 | 0.193918E+11 | 0.691482E+10 | ||||||
Minimum of Months | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613431E+09 | 0.131539E+09 |
Maximum of Months | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290908E+10 | 0.121449E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47564854.78 | 0.713639E+10 |
February | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40502642.22 | 0.458528E+10 |
March | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83096601.66 | 0.781156E+10 |
April | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47494284.30 | 0.412575E+10 |
May | 0.00 | 0.265687E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134621E+09 | 0.502005E+10 |
June | 0.00 | 0.263332E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61954544.22 | 0.491789E+10 |
July | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7737117.11 | 0.468891E+10 |
August | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41110872.89 | 0.771713E+10 |
September | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13646856.38 | 0.476165E+10 |
October | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3982951.09 | 0.584492E+10 |
November | 0.00 | 0.248511E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5822939.35 | 0.567572E+10 |
December | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5274196.71 | 0.757687E+10 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | 0.492809E+09 | 0.698621E+11 | |||||
Minimum of Months | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3982951.09 | 0.412575E+10 |
Maximum of Months | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134621E+09 | 0.781156E+10 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1939.55 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3606.10 | 04-JAN-13:00 | 1600.08 | 24-JAN-07:10 |
February | 659.25 | 01-FEB-08:09 | 1939.55 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3655.29 | 28-FEB-13:00 | 952.87 | 02-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1939.55 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3856.04 | 21-MAR-12:00 | 375.50 | 03-MAR-06:01 |
April | 659.25 | 01-APR-07:10 | 1939.55 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3966.85 | 11-APR-16:10 | 241.14 | 13-APR-05:01 |
May | 659.25 | 01-MAY-07:10 | 1939.55 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4578.82 | 05-MAY-12:00 | 354.30 | 08-MAY-21:55 |
June | 659.25 | 01-JUN-07:10 | 1939.55 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4175.17 | 13-JUN-16:10 | 411.60 | 26-JUN-18:00 |
July | 659.25 | 01-JUL-07:10 | 1939.55 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3412.49 | 26-JUL-17:00 | 263.60 | 31-JUL-05:01 |
August | 659.25 | 01-AUG-07:10 | 1939.55 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3389.11 | 09-AUG-16:10 | 319.58 | 23-AUG-19:55 |
September | 659.25 | 01-SEP-07:10 | 1939.55 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3159.82 | 12-SEP-12:00 | 395.88 | 15-SEP-17:00 |
October | 659.25 | 02-OCT-07:10 | 1939.55 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3026.84 | 04-OCT-12:00 | 365.65 | 23-OCT-05:01 |
November | 659.25 | 01-NOV-07:10 | 1939.55 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2834.30 | 10-NOV-12:10 | 656.24 | 27-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1939.55 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2851.82 | 26-DEC-13:00 | 1947.78 | 21-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2834.30 | 241.14 | |||||
Maximum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4578.82 | 1947.78 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4221.71 | 31-JAN-16:10 | 8895.38 | 07-JAN-04:55 |
February | 0.00 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6531.59 | 28-FEB-16:10 | 2902.46 | 01-FEB-07:10 |
March | 0.00 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9886.73 | 19-MAR-16:00 | 2244.11 | 14-MAR-22:00 |
April | 0.00 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6782.11 | 11-APR-16:00 | 2054.80 | 14-APR-16:00 |
May | 0.00 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11546.52 | 06-MAY-15:10 | 3820.88 | 08-MAY-21:55 |
June | 0.00 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9308.50 | 16-JUN-15:30 | 4077.44 | 20-JUN-23:00 |
July | 0.00 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5706.89 | 13-JUL-16:00 | 2965.15 | 19-JUL-19:10 |
August | 0.00 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6519.73 | 09-AUG-16:00 | 3759.79 | 23-AUG-19:55 |
September | 0.00 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6623.03 | 10-SEP-14:55 | 5993.73 | 15-SEP-17:00 |
October | 0.00 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5768.65 | 29-OCT-13:00 | 2712.61 | 30-OCT-16:20 |
November | 0.00 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3002.20 | 04-NOV-15:10 | 2548.93 | 25-NOV-08:00 |
December | 0.00 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2712.93 | 13-DEC-16:10 | 3791.88 | 21-DEC-07:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2712.93 | 2054.80 | |||
Maximum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11546.52 | 8895.38 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23173.88 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1923.38 | 11-JAN-10:55 | 43571.85 | 07-JAN-04:55 |
February | 0.00 | 23173.88 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.10 | 12-FEB-12:55 | 10417.27 | 01-FEB-07:00 |
March | 0.00 | 23173.88 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3474.06 | 19-MAR-11:53 | 11936.99 | 14-MAR-22:00 |
April | 0.00 | 23173.88 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1921.30 | 17-APR-09:43 | 10552.32 | 14-APR-16:00 |
May | 0.00 | 23173.88 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5026.20 | 01-MAY-13:53 | 19340.89 | 08-MAY-22:00 |
June | 0.00 | 23173.88 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2173.32 | 18-JUN-13:55 | 20437.55 | 20-JUN-23:00 |
July | 0.00 | 23173.88 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1124.80 | 04-JUL-12:52 | 22624.41 | 03-JUL-12:52 |
August | 0.00 | 23173.88 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1822.18 | 06-AUG-11:35 | 24293.89 | 25-AUG-11:00 |
September | 0.00 | 23173.88 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1780.84 | 22-SEP-15:55 | 22816.64 | 15-SEP-17:00 |
October | 0.00 | 23173.88 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1109.58 | 06-OCT-10:55 | 18184.10 | 11-OCT-13:00 |
November | 0.00 | 23173.88 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1075.87 | 18-NOV-12:55 | 11628.39 | 25-NOV-08:70 |
December | 0.00 | 23173.88 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 833.35 | 31-DEC-09:53 | 17093.69 | 20-DEC-08:50 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 833.35 | 10417.27 | ||||
Maximum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 5026.20 | 43571.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18463.78 | 24-JAN-06:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.86 |
February | 20090.07 | 23-FEB-06:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.47 |
March | 17407.82 | 04-MAR-06:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.23 |
April | 15854.19 | 27-APR-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.12 |
May | 15802.60 | 31-MAY-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.57 |
June | 15713.80 | 20-JUN-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.95 |
July | 17643.47 | 17-JUL-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.05 |
August | 15636.96 | 30-AUG-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.94 |
September | 16091.43 | 06-SEP-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.58 |
October | 15718.13 | 11-OCT-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.24 |
November | 17357.26 | 25-NOV-06:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.54 |
December | 17841.75 | 21-DEC-06:01 | 580.14 | 4634.78 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.87 |
Annual Sum or Average | |||||||||||
Minimum of Months | 15636.96 | 580.14 | 4634.78 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.23 | |
Maximum of Months | 20090.07 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 53353.95 | 16-JAN-16:03 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1068.69 | 0.00 |
February | 51411.92 | 22-FEB-18:06 | 0.00 | 5926.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2080.63 | 0.00 |
March | 48038.95 | 29-MAR-17:06 | 0.00 | 5926.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2974.80 | 0.00 |
April | 46710.57 | 23-APR-17:03 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.79 | 0.00 |
May | 45564.43 | 29-MAY-17:12 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2087.78 | 0.00 |
June | 43613.00 | 18-JUN-17:03 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 755.10 | 0.00 |
July | 49730.47 | 16-JUL-16:03 | 0.00 | 3556.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 41439.72 | 27-AUG-17:53 | 0.00 | 3556.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1136.67 | 0.00 |
September | 44695.86 | 13-SEP-17:06 | 0.00 | 5926.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1415.23 | 0.00 |
October | 46094.43 | 08-OCT-15:32 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1423.34 | 0.00 |
November | 49995.25 | 05-NOV-13:32 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 552.50 | 0.00 |
December | 51509.49 | 03-DEC-15:32 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 953.90 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 41439.72 | 0.00 | 3556.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53353.95 | 0.00 | 5926.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2974.80 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 935.74 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2921.67 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3758.51 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4108.50 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1370.12 |
June | 0.00 | 01-JUN-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4485.28 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3039.66 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4666.93 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2926.99 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1106.08 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1844.76 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2738.88 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 935.74 | |
Maximum of Months | 0.00 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4666.93 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.848792E+11 | 72959.00 | 04-JAN-13:20 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.801751E+11 | 74940.33 | 28-FEB-14:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.949693E+11 | 75389.60 | 27-MAR-13:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.930800E+11 | 75957.40 | 18-APR-14:39 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.974126E+11 | 79296.71 | 06-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.970636E+11 | 79134.43 | 16-JUN-13:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.880098E+11 | 73483.52 | 28-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.939441E+11 | 76347.16 | 11-AUG-14:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.885840E+11 | 75291.49 | 06-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.867036E+11 | 74310.97 | 04-OCT-12:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.827448E+11 | 72856.40 | 10-NOV-13:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.840293E+11 | 71736.97 | 12-DEC-13:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.107160E+13 | 0.00 | ||||
Minimum of Months | 0.801751E+11 | 71736.97 | 0.00 | 0.00 | ||
Maximum of Months | 0.974126E+11 | 79296.71 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.396181E+11 | 0.884550E+10 | 0.115358E+11 | 0.00 | 0.687290E+10 | 0.00 | 0.00 | 0.161213E+11 | 0.00 | 0.00 | 0.00 | 0.188563E+10 | 0.00 |
February | 0.362526E+11 | 0.786477E+10 | 0.105871E+11 | 0.00 | 0.691878E+10 | 0.00 | 0.00 | 0.168429E+11 | 0.00 | 0.00 | 0.00 | 0.170896E+10 | 0.00 |
March | 0.418523E+11 | 0.844033E+10 | 0.123357E+11 | 0.00 | 0.846416E+10 | 0.00 | 0.00 | 0.219642E+11 | 0.00 | 0.00 | 0.00 | 0.191271E+10 | 0.00 |
April | 0.392410E+11 | 0.797458E+10 | 0.114862E+11 | 0.00 | 0.900006E+10 | 0.00 | 0.00 | 0.235602E+11 | 0.00 | 0.00 | 0.00 | 0.181795E+10 | 0.00 |
May | 0.407352E+11 | 0.809954E+10 | 0.119357E+11 | 0.00 | 0.927888E+10 | 0.00 | 0.00 | 0.254930E+11 | 0.00 | 0.00 | 0.00 | 0.187029E+10 | 0.00 |
June | 0.403581E+11 | 0.774738E+10 | 0.118862E+11 | 0.00 | 0.913992E+10 | 0.00 | 0.00 | 0.261146E+11 | 0.00 | 0.00 | 0.00 | 0.181748E+10 | 0.00 |
July | 0.396181E+11 | 0.806924E+10 | 0.115358E+11 | 0.00 | 0.755066E+10 | 0.00 | 0.00 | 0.193942E+11 | 0.00 | 0.00 | 0.00 | 0.184176E+10 | 0.00 |
August | 0.418523E+11 | 0.817148E+10 | 0.123357E+11 | 0.00 | 0.784694E+10 | 0.00 | 0.00 | 0.218563E+11 | 0.00 | 0.00 | 0.00 | 0.188147E+10 | 0.00 |
September | 0.392410E+11 | 0.811090E+10 | 0.114862E+11 | 0.00 | 0.758159E+10 | 0.00 | 0.00 | 0.203551E+11 | 0.00 | 0.00 | 0.00 | 0.180924E+10 | 0.00 |
October | 0.396181E+11 | 0.859937E+10 | 0.115358E+11 | 0.00 | 0.705917E+10 | 0.00 | 0.00 | 0.180258E+11 | 0.00 | 0.00 | 0.00 | 0.186532E+10 | 0.00 |
November | 0.381239E+11 | 0.848956E+10 | 0.110862E+11 | 0.00 | 0.665650E+10 | 0.00 | 0.00 | 0.165764E+11 | 0.00 | 0.00 | 0.00 | 0.181220E+10 | 0.00 |
December | 0.396181E+11 | 0.890230E+10 | 0.115358E+11 | 0.00 | 0.669452E+10 | 0.00 | 0.00 | 0.153947E+11 | 0.00 | 0.00 | 0.00 | 0.188390E+10 | 0.00 |
Annual Sum or Average | 0.476129E+12 | 0.993149E+11 | 0.139282E+12 | 0.930641E+11 | 0.00 | 0.241699E+12 | 0.221069E+11 | ||||||
Minimum of Months | 0.362526E+11 | 0.774738E+10 | 0.105871E+11 | 0.00 | 0.665650E+10 | 0.00 | 0.00 | 0.153947E+11 | 0.00 | 0.00 | 0.00 | 0.170896E+10 | 0.00 |
Maximum of Months | 0.418523E+11 | 0.890230E+10 | 0.123357E+11 | 0.00 | 0.927888E+10 | 0.00 | 0.00 | 0.261146E+11 | 0.00 | 0.00 | 0.00 | 0.191271E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35189.04 | 02-JAN-09:09 | 6311.00 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 6648.13 | 11-JAN-08:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35189.04 | 01-FEB-09:09 | 6311.00 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 6648.13 | 06-FEB-11:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35189.04 | 01-MAR-09:09 | 6311.00 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 6648.13 | 02-MAR-15:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35189.04 | 01-APR-08:09 | 6311.00 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 6648.13 | 07-APR-13:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35189.04 | 01-MAY-08:09 | 6311.00 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 6648.13 | 01-MAY-06:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35189.04 | 01-JUN-08:09 | 6311.00 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 6648.13 | 02-JUN-15:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35189.04 | 01-JUL-08:09 | 6311.00 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6648.13 | 01-JUL-14:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35189.04 | 01-AUG-08:09 | 6311.00 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6648.13 | 05-AUG-13:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35189.04 | 01-SEP-08:09 | 6311.00 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 6648.13 | 15-SEP-10:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35189.04 | 02-OCT-08:09 | 6311.00 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 6648.13 | 13-OCT-13:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35189.04 | 01-NOV-08:09 | 6311.00 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 6648.13 | 02-NOV-14:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35189.04 | 01-DEC-09:09 | 6311.00 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 6648.13 | 08-DEC-13:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35189.04 | 6311.00 | 10112.62 | 0.00 | 6648.13 | 0.00 | 0.00 | |||||
Maximum of Months | 35189.04 | 6311.00 | 10112.62 | 0.00 | 6648.13 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 20272.34 | 04-JAN-12:00 | 0.00 | 0.00 | 0.00 | 1704.71 | 12-JAN-12:30 | 0.00 |
February | 21333.34 | 28-FEB-14:00 | 0.00 | 0.00 | 0.00 | 1704.16 | 01-FEB-12:30 | 0.00 |
March | 23039.98 | 20-MAR-15:30 | 0.00 | 0.00 | 0.00 | 1701.74 | 01-MAR-12:09 | 0.00 |
April | 23693.93 | 11-APR-15:00 | 0.00 | 0.00 | 0.00 | 1697.73 | 01-APR-11:20 | 0.00 |
May | 27541.81 | 06-MAY-15:30 | 0.00 | 0.00 | 0.00 | 1693.32 | 01-MAY-11:09 | 0.00 |
June | 27146.22 | 13-JUN-15:39 | 0.00 | 0.00 | 0.00 | 1689.51 | 01-JUN-11:20 | 0.00 |
July | 20204.39 | 05-JUL-15:39 | 0.00 | 0.00 | 0.00 | 1687.66 | 31-JUL-11:50 | 0.00 |
August | 23808.14 | 09-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1690.06 | 31-AUG-11:20 | 0.00 |
September | 21991.73 | 06-SEP-11:00 | 0.00 | 0.00 | 0.00 | 1693.91 | 30-SEP-11:39 | 0.00 |
October | 21500.27 | 04-OCT-11:00 | 0.00 | 0.00 | 0.00 | 1698.56 | 31-OCT-11:30 | 0.00 |
November | 19764.72 | 10-NOV-12:00 | 0.00 | 0.00 | 0.00 | 1702.24 | 30-NOV-12:09 | 0.00 |
December | 18637.47 | 12-DEC-12:00 | 0.00 | 0.00 | 0.00 | 1704.43 | 30-DEC-12:30 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18637.47 | 0.00 | 0.00 | 0.00 | 1687.66 | 0.00 | ||
Maximum of Months | 27541.81 | 0.00 | 0.00 | 0.00 | 1704.71 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 72959.00 | 04-JAN-13:20 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6648.13 | 0.00 | 0.00 | 19327.90 | 0.00 |
February | 74940.33 | 28-FEB-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6648.13 | 0.00 | 0.00 | 21333.34 | 0.00 |
March | 75389.60 | 27-MAR-13:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6648.13 | 0.00 | 0.00 | 21785.36 | 0.00 |
April | 75957.40 | 18-APR-14:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6648.13 | 0.00 | 0.00 | 22334.26 | 0.00 |
May | 79296.71 | 06-MAY-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6648.13 | 0.00 | 0.00 | 25675.75 | 0.00 |
June | 79134.43 | 16-JUN-13:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6648.13 | 0.00 | 0.00 | 25537.41 | 0.00 |
July | 73483.52 | 28-JUL-12:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6648.13 | 0.00 | 0.00 | 19866.82 | 0.00 |
August | 76347.16 | 11-AUG-14:30 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6648.13 | 0.00 | 0.00 | 22730.14 | 0.00 |
September | 75291.49 | 06-SEP-13:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6648.13 | 0.00 | 0.00 | 21692.57 | 0.00 |
October | 74310.97 | 04-OCT-12:20 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6648.13 | 0.00 | 0.00 | 20688.55 | 0.00 |
November | 72856.40 | 10-NOV-13:30 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6648.13 | 0.00 | 0.00 | 19229.35 | 0.00 |
December | 71736.97 | 12-DEC-13:20 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6648.13 | 0.00 | 0.00 | 18106.96 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 71736.97 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6648.13 | 0.00 | 0.00 | 18106.96 | 0.00 | |
Maximum of Months | 79296.71 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6648.13 | 0.00 | 0.00 | 25675.75 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 25.11 | 8.50 | 24.92 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 25.42 | 7.67 | 25.02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 25.37 | 9.50 | 25.13 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 25.46 | 9.00 | 25.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 25.67 | 10.00 | 25.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 25.49 | 10.00 | 25.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 25.53 | 8.50 | 25.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 25.40 | 9.83 | 25.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 25.24 | 8.00 | 25.24 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 25.63 | 8.33 | 25.11 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 25.44 | 8.17 | 25.06 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 25.27 | 7.83 | 24.87 |
Annual Sum or Average | 0.00 | 0.00 | 111.17 | 25.43 | 105.33 | 25.17 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 25.11 | 7.67 | 24.87 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 25.67 | 10.00 | 25.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 27.55 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 27.58 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 27.63 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 33.67 | 27.59 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 | 27.58 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 27.59 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 32.00 | 27.52 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 27.50 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 | 27.51 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 27.49 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 | 27.51 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 27.57 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 326.17 | 27.55 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 27.49 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 27.63 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.67 | 24.20 | 300.00 | 23.93 | 21.67 | 24.20 |
February | 14.33 | 24.36 | 276.00 | 23.93 | 14.33 | 24.36 |
March | 41.50 | 24.21 | 324.00 | 23.94 | 41.50 | 24.21 |
April | 58.33 | 24.17 | 300.00 | 23.95 | 58.33 | 24.17 |
May | 89.00 | 24.10 | 312.00 | 23.96 | 89.00 | 24.10 |
June | 84.33 | 24.11 | 312.00 | 23.96 | 84.33 | 24.11 |
July | 40.50 | 24.18 | 300.00 | 23.94 | 40.50 | 24.18 |
August | 97.00 | 24.06 | 324.00 | 23.95 | 97.00 | 24.06 |
September | 73.67 | 24.08 | 300.00 | 23.94 | 73.67 | 24.08 |
October | 76.83 | 24.06 | 300.00 | 23.94 | 76.83 | 24.06 |
November | 47.00 | 24.12 | 288.00 | 23.94 | 47.00 | 24.12 |
December | 26.00 | 24.17 | 300.00 | 23.93 | 26.00 | 24.17 |
Annual Sum or Average | 670.17 | 24.12 | 3636.00 | 23.94 | 670.17 | 24.12 |
Minimum of Months | 14.33 | 24.06 | 276.00 | 23.93 | 14.33 | 24.06 |
Maximum of Months | 97.00 | 24.36 | 324.00 | 23.96 | 97.00 | 24.36 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.146412E+11 | 0.400087E+10 | 305.69 | 0.107714E+11 | 0.386979E+10 | 0.00 | 1.00 | 02-JAN-06:01 | 0.00 | 01-JAN-00:10 | 30612.53 | 02-JAN-06:01 | 19445.11 | 24-JAN-06:01 | 15353.38 | 02-JAN-06:03 | 6728.54 | 02-JAN-06:01 | 0.00 | 01-JAN-00:10 |
February | 0.140880E+11 | 0.389183E+10 | 284.76 | 0.104463E+11 | 0.364170E+10 | 0.00 | 1.00 | 01-FEB-06:01 | 0.00 | 01-FEB-00:05 | 29572.16 | 15-FEB-06:01 | 21444.83 | 23-FEB-06:01 | 13276.30 | 16-FEB-06:07 | 6653.26 | 16-FEB-06:01 | 0.00 | 01-FEB-00:05 |
March | 0.177308E+11 | 0.492234E+10 | 333.60 | 0.127783E+11 | 0.495245E+10 | 0.00 | 1.00 | 01-MAR-06:01 | 0.00 | 01-MAR-00:10 | 30062.69 | 27-MAR-05:01 | 18861.63 | 04-MAR-06:01 | 14195.33 | 25-MAR-05:04 | 6799.10 | 28-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.179353E+11 | 0.493866E+10 | 314.09 | 0.121950E+11 | 0.574034E+10 | 0.00 | 1.00 | 01-APR-05:01 | 0.00 | 01-APR-00:10 | 30261.12 | 10-APR-05:01 | 17355.34 | 27-APR-05:01 | 15050.45 | 03-APR-05:04 | 6810.73 | 03-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.200209E+11 | 0.544438E+10 | 326.48 | 0.127195E+11 | 0.730140E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 30583.56 | 17-MAY-05:01 | 17041.54 | 31-MAY-05:01 | 18573.14 | 22-MAY-05:08 | 6864.82 | 05-MAY-12:00 | 0.00 | 01-MAY-00:10 |
June | 0.203212E+11 | 0.552809E+10 | 326.20 | 0.129600E+11 | 0.736118E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:05 | 30555.98 | 21-JUN-05:01 | 16934.40 | 20-JUN-05:01 | 17441.47 | 10-JUN-05:09 | 6881.90 | 15-JUN-12:00 | 0.00 | 01-JUN-00:05 |
July | 0.164320E+11 | 0.440481E+10 | 311.46 | 0.112615E+11 | 0.517045E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 29862.37 | 03-JUL-05:01 | 18946.57 | 17-JUL-05:01 | 13730.80 | 01-JUL-05:06 | 6712.24 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.195023E+11 | 0.518339E+10 | 329.85 | 0.121516E+11 | 0.735074E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 30583.56 | 04-AUG-05:01 | 16915.53 | 30-AUG-05:01 | 17320.80 | 07-AUG-05:06 | 7192.76 | 13-AUG-13:17 | 0.00 | 01-AUG-00:10 |
September | 0.174438E+11 | 0.466319E+10 | 309.17 | 0.112625E+11 | 0.618128E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:05 | 30353.39 | 18-SEP-05:01 | 17458.67 | 06-SEP-05:01 | 15666.76 | 25-SEP-05:05 | 6804.85 | 05-SEP-05:01 | 0.00 | 01-SEP-00:05 |
October | 0.165601E+11 | 0.438973E+10 | 305.84 | 0.106594E+11 | 0.590074E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 30612.53 | 23-OCT-05:01 | 16987.35 | 11-OCT-05:01 | 15848.04 | 30-OCT-05:03 | 6774.25 | 05-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.153099E+11 | 0.409506E+10 | 292.26 | 0.103636E+11 | 0.494624E+10 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 30288.28 | 13-NOV-06:01 | 18337.21 | 25-NOV-06:01 | 15524.69 | 13-NOV-06:04 | 6754.29 | 13-NOV-06:01 | 0.00 | 01-NOV-00:10 |
December | 0.143738E+11 | 0.389620E+10 | 305.26 | 0.103949E+11 | 0.397893E+10 | 0.00 | 1.00 | 01-DEC-06:01 | 0.00 | 01-DEC-00:10 | 30076.14 | 11-DEC-06:01 | 18838.87 | 21-DEC-06:01 | 13940.77 | 11-DEC-06:06 | 6666.41 | 11-DEC-06:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.204359E+12 | 0.553586E+11 | 3744.66 | 0.137964E+12 | 0.663952E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.140880E+11 | 0.389183E+10 | 284.76 | 0.103636E+11 | 0.364170E+10 | 0.00 | 1.00 | 0.00 | 29572.16 | 16915.53 | 13276.30 | 6653.26 | 0.00 | |||||||
Maximum of Months | 0.203212E+11 | 0.552809E+10 | 333.60 | 0.129600E+11 | 0.736118E+10 | 0.00 | 1.00 | 0.00 | 30612.53 | 21444.83 | 18573.14 | 7192.76 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.411421E+11 | 0.121204E+11 | 409.26 | 0.287569E+11 | 0.123852E+11 | 0.00 | 1.00 | 04-JAN-18:10 | 0.00 | 01-JAN-00:10 | 81521.00 | 11-JAN-18:10 | 58789.57 | 16-JAN-15:23 | 36569.22 | 11-JAN-18:10 | 20704.00 | 08-JAN-13:02 | 0.00 | 01-JAN-00:10 |
February | 0.436298E+11 | 0.129510E+11 | 412.08 | 0.305932E+11 | 0.130367E+11 | 0.00 | 1.00 | 05-FEB-09:43 | 0.00 | 01-FEB-00:05 | 83307.69 | 18-FEB-06:01 | 57944.76 | 22-FEB-18:06 | 37078.31 | 18-FEB-06:01 | 21268.98 | 26-FEB-14:43 | 0.00 | 01-FEB-00:05 |
March | 0.575167E+11 | 0.170418E+11 | 497.23 | 0.386964E+11 | 0.188203E+11 | 0.00 | 1.00 | 05-MAR-09:33 | 0.00 | 01-MAR-00:20 | 85418.83 | 29-MAR-05:04 | 56108.44 | 19-MAR-13:53 | 44283.09 | 27-MAR-05:11 | 21613.10 | 19-MAR-15:53 | 0.00 | 01-MAR-00:10 |
April | 0.634191E+11 | 0.186215E+11 | 528.60 | 0.396337E+11 | 0.237854E+11 | 0.00 | 1.00 | 01-APR-05:10 | 0.00 | 01-APR-00:15 | 87989.16 | 22-APR-05:01 | 53410.94 | 02-APR-13:43 | 48043.38 | 01-APR-05:10 | 21748.05 | 02-APR-15:02 | 0.00 | 01-APR-00:10 |
May | 0.692422E+11 | 0.200486E+11 | 538.14 | 0.397640E+11 | 0.294782E+11 | 0.00 | 1.00 | 01-MAY-17:05 | 0.00 | 01-MAY-00:15 | 88065.65 | 13-MAY-05:19 | 52781.58 | 07-MAY-13:02 | 52487.65 | 04-MAY-05:08 | 22095.55 | 21-MAY-11:03 | 0.00 | 01-MAY-00:10 |
June | 0.714109E+11 | 0.205865E+11 | 539.79 | 0.411119E+11 | 0.302989E+11 | 0.00 | 1.00 | 01-JUN-05:03 | 0.00 | 01-JUN-00:10 | 88065.65 | 06-JUN-05:06 | 49676.78 | 18-JUN-14:23 | 52069.95 | 10-JUN-05:11 | 22281.01 | 18-JUN-13:43 | 0.00 | 01-JUN-00:05 |
July | 0.517715E+11 | 0.149894E+11 | 505.18 | 0.328733E+11 | 0.188982E+11 | 0.00 | 1.00 | 01-JUL-17:08 | 0.00 | 01-JUL-00:10 | 85291.37 | 15-JUL-05:01 | 54359.33 | 14-JUL-17:06 | 41865.35 | 15-JUL-05:01 | 21266.45 | 26-JUL-17:06 | 0.00 | 01-JUL-00:10 |
August | 0.588928E+11 | 0.166729E+11 | 481.06 | 0.327615E+11 | 0.261313E+11 | 0.00 | 1.00 | 01-AUG-17:06 | 0.00 | 01-AUG-00:10 | 88065.65 | 25-AUG-05:05 | 49459.34 | 27-AUG-15:53 | 51559.66 | 25-AUG-05:05 | 22087.93 | 13-AUG-14:43 | 0.00 | 01-AUG-00:10 |
September | 0.547502E+11 | 0.156919E+11 | 487.31 | 0.323185E+11 | 0.224317E+11 | 0.00 | 1.00 | 01-SEP-17:08 | 0.00 | 01-SEP-00:10 | 86847.40 | 02-SEP-05:10 | 52183.24 | 10-SEP-13:53 | 45855.87 | 02-SEP-05:10 | 21681.29 | 24-SEP-12:53 | 0.00 | 01-SEP-00:05 |
October | 0.478239E+11 | 0.136361E+11 | 453.71 | 0.281222E+11 | 0.197017E+11 | 0.00 | 1.00 | 01-OCT-09:23 | 0.00 | 01-OCT-00:15 | 85707.84 | 17-OCT-05:07 | 51013.34 | 08-OCT-14:13 | 43009.37 | 17-OCT-05:07 | 21527.84 | 29-OCT-12:32 | 0.00 | 01-OCT-00:10 |
November | 0.433000E+11 | 0.124814E+11 | 418.88 | 0.272984E+11 | 0.160017E+11 | 0.00 | 1.00 | 01-NOV-17:10 | 0.00 | 01-NOV-00:10 | 88466.01 | 13-NOV-06:09 | 54632.19 | 05-NOV-13:32 | 48992.09 | 13-NOV-06:09 | 21113.56 | 11-NOV-14:13 | 0.00 | 01-NOV-00:10 |
December | 0.393778E+11 | 0.114985E+11 | 392.76 | 0.266818E+11 | 0.126959E+11 | 0.00 | 1.00 | 03-DEC-09:33 | 0.00 | 01-DEC-00:10 | 85448.51 | 09-DEC-06:06 | 56572.10 | 03-DEC-14:53 | 41765.16 | 09-DEC-06:06 | 20917.43 | 31-DEC-12:43 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.642277E+12 | 0.186340E+12 | 5663.99 | 0.398612E+12 | 0.243665E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.393778E+11 | 0.114985E+11 | 392.76 | 0.266818E+11 | 0.123852E+11 | 0.00 | 1.00 | 0.00 | 81521.00 | 49459.34 | 36569.22 | 20704.00 | 0.00 | |||||||
Maximum of Months | 0.714109E+11 | 0.205865E+11 | 539.79 | 0.411119E+11 | 0.302989E+11 | 0.00 | 1.00 | 0.00 | 88466.01 | 58789.57 | 52487.65 | 22281.01 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 59.31 | 20.90 | 38.41 | 189.10 | 50.77 | 0.00 | 0.00 | 744.00 |
February | 64.95 | 22.93 | 42.02 | 214.18 | 42.73 | 0.00 | 0.00 | 672.00 |
March | 72.73 | 28.62 | 44.11 | 245.67 | 35.52 | 0.00 | 0.00 | 744.00 |
April | 72.91 | 27.71 | 45.20 | 243.17 | 23.35 | 0.00 | 0.00 | 720.00 |
May | 62.19 | 18.32 | 43.87 | 211.33 | 25.00 | 0.00 | 0.00 | 744.00 |
June | 67.38 | 23.12 | 44.27 | 226.47 | 26.01 | 0.00 | 0.00 | 720.00 |
July | 57.51 | 13.49 | 44.02 | 183.51 | 35.23 | 0.00 | 0.00 | 744.00 |
August | 62.51 | 18.41 | 44.09 | 187.18 | 32.12 | 0.00 | 0.00 | 744.00 |
September | 58.40 | 16.02 | 42.38 | 187.19 | 31.65 | 0.00 | 0.00 | 720.00 |
October | 54.94 | 14.05 | 40.89 | 163.31 | 37.99 | 0.00 | 0.00 | 744.00 |
November | 53.59 | 14.52 | 39.06 | 165.17 | 40.27 | 0.00 | 0.00 | 720.00 |
December | 55.00 | 18.01 | 36.99 | 173.69 | 54.02 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.75 | 19.64 | 42.10 | 198.97 | 36.23 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.59 | 13.49 | 36.99 | 163.31 | 23.35 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 72.91 | 28.62 | 45.20 | 245.67 | 54.02 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 59.31 | 20.90 | 38.41 | 189.10 | 50.77 | 0.00 | 0.00 | 744.00 |
February | 64.95 | 22.93 | 42.02 | 214.18 | 42.73 | 0.00 | 0.00 | 672.00 |
March | 72.73 | 28.62 | 44.11 | 245.67 | 35.52 | 0.00 | 0.00 | 744.00 |
April | 72.91 | 27.71 | 45.20 | 243.17 | 23.35 | 0.00 | 0.00 | 720.00 |
May | 62.19 | 18.32 | 43.87 | 211.33 | 25.00 | 0.00 | 0.00 | 744.00 |
June | 67.38 | 23.12 | 44.27 | 226.47 | 26.01 | 0.00 | 0.00 | 720.00 |
July | 57.51 | 13.49 | 44.02 | 183.51 | 35.23 | 0.00 | 0.00 | 744.00 |
August | 62.51 | 18.41 | 44.09 | 187.18 | 32.12 | 0.00 | 0.00 | 744.00 |
September | 58.40 | 16.02 | 42.38 | 187.19 | 31.65 | 0.00 | 0.00 | 720.00 |
October | 54.94 | 14.05 | 40.89 | 163.31 | 37.99 | 0.00 | 0.00 | 744.00 |
November | 53.59 | 14.52 | 39.06 | 165.17 | 40.27 | 0.00 | 0.00 | 720.00 |
December | 55.00 | 18.01 | 36.99 | 173.69 | 54.02 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.75 | 19.64 | 42.10 | 198.97 | 36.23 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.59 | 13.49 | 36.99 | 163.31 | 23.35 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 72.91 | 28.62 | 45.20 | 245.67 | 54.02 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.68 | 0.00 | 17.68 | 56.69 | 29.77 | 0.00 | 0.00 | 744.00 |
February | 18.86 | 0.00 | 18.86 | 65.09 | 24.94 | 0.00 | 0.00 | 672.00 |
March | 19.38 | 0.01 | 19.37 | 71.94 | 20.72 | 0.00 | 0.00 | 744.00 |
April | 21.61 | 0.67 | 20.93 | 79.03 | 13.62 | 0.00 | 0.00 | 720.00 |
May | 28.22 | 4.09 | 24.13 | 99.97 | 14.52 | 0.00 | 0.00 | 744.00 |
June | 34.73 | 8.41 | 26.32 | 122.22 | 15.16 | 0.00 | 0.00 | 720.00 |
July | 29.21 | 3.81 | 25.39 | 93.89 | 20.16 | 0.00 | 0.00 | 744.00 |
August | 24.10 | 1.73 | 22.37 | 75.14 | 18.53 | 0.00 | 0.00 | 744.00 |
September | 19.94 | 0.05 | 19.89 | 68.08 | 18.62 | 0.00 | 0.00 | 720.00 |
October | 19.16 | 0.00 | 19.16 | 57.65 | 22.50 | 0.00 | 0.00 | 744.00 |
November | 18.13 | 0.00 | 18.13 | 56.67 | 23.80 | 0.00 | 0.00 | 720.00 |
December | 17.18 | 0.00 | 17.18 | 54.39 | 31.67 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 22.36 | 1.57 | 20.79 | 75.07 | 21.17 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 17.18 | 0.00 | 17.18 | 54.39 | 13.62 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 34.73 | 8.41 | 26.32 | 122.22 | 31.67 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.68 | 0.00 | 17.68 | 56.69 | 29.76 | 0.00 | 0.00 | 744.00 |
February | 18.86 | 0.00 | 18.86 | 65.09 | 24.94 | 0.00 | 0.00 | 672.00 |
March | 19.38 | 0.01 | 19.37 | 71.94 | 20.71 | 0.00 | 0.00 | 744.00 |
April | 21.61 | 0.67 | 20.93 | 79.03 | 13.62 | 0.00 | 0.00 | 720.00 |
May | 28.22 | 4.09 | 24.13 | 99.97 | 14.52 | 0.00 | 0.00 | 744.00 |
June | 34.72 | 8.41 | 26.32 | 122.22 | 15.16 | 0.00 | 0.00 | 720.00 |
July | 29.20 | 3.81 | 25.39 | 93.89 | 20.16 | 0.00 | 0.00 | 744.00 |
August | 24.10 | 1.73 | 22.37 | 75.14 | 18.53 | 0.00 | 0.00 | 744.00 |
September | 19.94 | 0.05 | 19.89 | 68.08 | 18.62 | 0.00 | 0.00 | 720.00 |
October | 19.16 | 0.00 | 19.16 | 57.65 | 22.50 | 0.00 | 0.00 | 744.00 |
November | 18.13 | 0.00 | 18.13 | 56.67 | 23.80 | 0.00 | 0.00 | 720.00 |
December | 17.18 | 0.00 | 17.18 | 54.39 | 31.67 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 22.36 | 1.57 | 20.79 | 75.07 | 21.17 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 17.18 | 0.00 | 17.18 | 54.39 | 13.62 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 34.72 | 8.41 | 26.32 | 122.22 | 31.67 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.62 | 24.74 | 26.87 | 85.53 | 24.22 | 0.00 | 0.00 | 744.00 |
February | 59.43 | 30.81 | 28.62 | 100.14 | 25.29 | 0.00 | 0.00 | 672.00 |
March | 69.04 | 40.48 | 28.55 | 117.61 | 22.33 | 0.00 | 0.00 | 744.00 |
April | 69.78 | 39.07 | 30.72 | 118.77 | 18.19 | 0.00 | 0.00 | 720.00 |
May | 58.44 | 25.40 | 33.05 | 98.37 | 16.89 | 34.83 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 107.01 | 16.48 | 4.00 | 0.00 | 720.00 |
July | 53.18 | 17.62 | 35.55 | 88.81 | 18.01 | 0.00 | 0.00 | 744.00 |
August | 58.72 | 25.20 | 33.52 | 95.02 | 17.82 | 7.67 | 0.00 | 744.00 |
September | 54.30 | 21.10 | 33.20 | 90.99 | 17.57 | 0.00 | 0.00 | 720.00 |
October | 49.64 | 17.61 | 32.03 | 79.67 | 18.72 | 0.17 | 0.00 | 744.00 |
November | 47.28 | 17.85 | 29.42 | 77.18 | 20.90 | 0.00 | 0.00 | 720.00 |
December | 47.84 | 21.50 | 26.35 | 78.30 | 25.24 | 1.67 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 94.70 | 20.12 | 48.33 | 0.00 | 8760.00 |
Minimum of Months | 47.28 | 17.61 | 26.35 | 77.18 | 16.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.78 | 40.48 | 35.55 | 118.77 | 25.29 | 34.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.62 | 24.74 | 26.87 | 85.53 | 24.22 | 0.00 | 0.00 | 744.00 |
February | 59.43 | 30.81 | 28.62 | 100.14 | 25.29 | 0.00 | 0.00 | 672.00 |
March | 69.04 | 40.48 | 28.55 | 117.61 | 22.33 | 0.00 | 0.00 | 744.00 |
April | 69.78 | 39.07 | 30.72 | 118.77 | 18.19 | 0.00 | 0.00 | 720.00 |
May | 58.44 | 25.40 | 33.05 | 98.37 | 16.89 | 34.83 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 107.01 | 16.48 | 4.00 | 0.00 | 720.00 |
July | 53.18 | 17.62 | 35.55 | 88.81 | 18.01 | 0.00 | 0.00 | 744.00 |
August | 58.72 | 25.20 | 33.52 | 95.02 | 17.82 | 7.67 | 0.00 | 744.00 |
September | 54.30 | 21.10 | 33.20 | 90.99 | 17.57 | 0.00 | 0.00 | 720.00 |
October | 49.64 | 17.61 | 32.03 | 79.67 | 18.72 | 0.17 | 0.00 | 744.00 |
November | 47.28 | 17.85 | 29.42 | 77.18 | 20.90 | 0.00 | 0.00 | 720.00 |
December | 47.84 | 21.50 | 26.35 | 78.30 | 25.24 | 1.67 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 94.70 | 20.12 | 48.33 | 0.00 | 8760.00 |
Minimum of Months | 47.28 | 17.61 | 26.35 | 77.18 | 16.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.78 | 40.48 | 35.55 | 118.77 | 25.29 | 34.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.62 | 24.74 | 26.87 | 85.53 | 24.22 | 0.00 | 0.00 | 744.00 |
February | 59.43 | 30.81 | 28.62 | 100.14 | 25.29 | 0.00 | 0.00 | 672.00 |
March | 69.04 | 40.48 | 28.55 | 117.61 | 22.33 | 0.00 | 0.00 | 744.00 |
April | 69.78 | 39.07 | 30.72 | 118.77 | 18.19 | 0.00 | 0.00 | 720.00 |
May | 58.44 | 25.40 | 33.05 | 98.37 | 16.89 | 34.83 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 107.01 | 16.48 | 4.00 | 0.00 | 720.00 |
July | 53.18 | 17.62 | 35.55 | 88.81 | 18.01 | 0.00 | 0.00 | 744.00 |
August | 58.72 | 25.20 | 33.52 | 95.02 | 17.82 | 7.67 | 0.00 | 744.00 |
September | 54.30 | 21.10 | 33.20 | 90.99 | 17.57 | 0.00 | 0.00 | 720.00 |
October | 49.64 | 17.61 | 32.03 | 79.67 | 18.72 | 0.17 | 0.00 | 744.00 |
November | 47.28 | 17.85 | 29.42 | 77.18 | 20.90 | 0.00 | 0.00 | 720.00 |
December | 47.84 | 21.50 | 26.35 | 78.30 | 25.24 | 1.67 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 94.70 | 20.12 | 48.33 | 0.00 | 8760.00 |
Minimum of Months | 47.28 | 17.61 | 26.35 | 77.18 | 16.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.78 | 40.48 | 35.55 | 118.77 | 25.29 | 34.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.62 | 24.74 | 26.87 | 85.53 | 24.22 | 0.00 | 0.00 | 744.00 |
February | 59.43 | 30.81 | 28.62 | 100.14 | 25.29 | 0.00 | 0.00 | 672.00 |
March | 69.04 | 40.48 | 28.55 | 117.61 | 22.33 | 0.00 | 0.00 | 744.00 |
April | 69.78 | 39.07 | 30.72 | 118.77 | 18.19 | 0.00 | 0.00 | 720.00 |
May | 58.44 | 25.40 | 33.05 | 98.37 | 16.89 | 34.83 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 107.01 | 16.48 | 4.00 | 0.00 | 720.00 |
July | 53.18 | 17.62 | 35.55 | 88.81 | 18.01 | 0.00 | 0.00 | 744.00 |
August | 58.72 | 25.20 | 33.52 | 95.02 | 17.82 | 7.67 | 0.00 | 744.00 |
September | 54.30 | 21.10 | 33.20 | 90.99 | 17.57 | 0.00 | 0.00 | 720.00 |
October | 49.64 | 17.61 | 32.03 | 79.67 | 18.72 | 0.17 | 0.00 | 744.00 |
November | 47.28 | 17.85 | 29.42 | 77.18 | 20.90 | 0.00 | 0.00 | 720.00 |
December | 47.84 | 21.50 | 26.35 | 78.30 | 25.24 | 1.67 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 94.70 | 20.12 | 48.33 | 0.00 | 8760.00 |
Minimum of Months | 47.28 | 17.61 | 26.35 | 77.18 | 16.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.78 | 40.48 | 35.55 | 118.77 | 25.29 | 34.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.62 | 24.74 | 26.87 | 85.53 | 24.22 | 0.00 | 0.00 | 744.00 |
February | 59.43 | 30.81 | 28.62 | 100.14 | 25.29 | 0.00 | 0.00 | 672.00 |
March | 69.04 | 40.48 | 28.55 | 117.61 | 22.33 | 0.00 | 0.00 | 744.00 |
April | 69.78 | 39.07 | 30.72 | 118.77 | 18.19 | 0.00 | 0.00 | 720.00 |
May | 58.44 | 25.40 | 33.05 | 98.37 | 16.89 | 34.83 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 107.01 | 16.48 | 4.00 | 0.00 | 720.00 |
July | 53.18 | 17.62 | 35.55 | 88.81 | 18.01 | 0.00 | 0.00 | 744.00 |
August | 58.72 | 25.20 | 33.52 | 95.02 | 17.82 | 7.67 | 0.00 | 744.00 |
September | 54.30 | 21.10 | 33.20 | 90.99 | 17.57 | 0.00 | 0.00 | 720.00 |
October | 49.64 | 17.61 | 32.03 | 79.67 | 18.72 | 0.17 | 0.00 | 744.00 |
November | 47.28 | 17.85 | 29.42 | 77.18 | 20.90 | 0.00 | 0.00 | 720.00 |
December | 47.84 | 21.50 | 26.35 | 78.30 | 25.24 | 1.67 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 94.70 | 20.12 | 48.33 | 0.00 | 8760.00 |
Minimum of Months | 47.28 | 17.61 | 26.35 | 77.18 | 16.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.78 | 40.48 | 35.55 | 118.77 | 25.29 | 34.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.62 | 24.74 | 26.87 | 85.53 | 24.22 | 0.00 | 0.00 | 744.00 |
February | 59.43 | 30.81 | 28.62 | 100.14 | 25.29 | 0.00 | 0.00 | 672.00 |
March | 69.04 | 40.48 | 28.55 | 117.61 | 22.33 | 0.00 | 0.00 | 744.00 |
April | 69.78 | 39.07 | 30.72 | 118.77 | 18.19 | 0.00 | 0.00 | 720.00 |
May | 58.44 | 25.40 | 33.05 | 98.37 | 16.89 | 34.83 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 107.01 | 16.48 | 4.00 | 0.00 | 720.00 |
July | 53.18 | 17.62 | 35.55 | 88.81 | 18.01 | 0.00 | 0.00 | 744.00 |
August | 58.72 | 25.20 | 33.52 | 95.02 | 17.82 | 7.67 | 0.00 | 744.00 |
September | 54.30 | 21.10 | 33.20 | 90.99 | 17.57 | 0.00 | 0.00 | 720.00 |
October | 49.64 | 17.61 | 32.03 | 79.67 | 18.72 | 0.17 | 0.00 | 744.00 |
November | 47.28 | 17.85 | 29.42 | 77.18 | 20.90 | 0.00 | 0.00 | 720.00 |
December | 47.84 | 21.50 | 26.35 | 78.30 | 25.24 | 1.67 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 94.70 | 20.12 | 48.33 | 0.00 | 8760.00 |
Minimum of Months | 47.28 | 17.61 | 26.35 | 77.18 | 16.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.78 | 40.48 | 35.55 | 118.77 | 25.29 | 34.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.62 | 24.74 | 26.87 | 85.53 | 24.22 | 0.00 | 0.00 | 744.00 |
February | 59.43 | 30.81 | 28.62 | 100.14 | 25.29 | 0.00 | 0.00 | 672.00 |
March | 69.04 | 40.48 | 28.55 | 117.61 | 22.33 | 0.00 | 0.00 | 744.00 |
April | 69.78 | 39.07 | 30.72 | 118.77 | 18.19 | 0.00 | 0.00 | 720.00 |
May | 58.44 | 25.40 | 33.05 | 98.37 | 16.89 | 34.83 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 107.01 | 16.48 | 4.00 | 0.00 | 720.00 |
July | 53.18 | 17.62 | 35.55 | 88.81 | 18.01 | 0.00 | 0.00 | 744.00 |
August | 58.72 | 25.20 | 33.52 | 95.02 | 17.82 | 7.67 | 0.00 | 744.00 |
September | 54.30 | 21.10 | 33.20 | 90.99 | 17.57 | 0.00 | 0.00 | 720.00 |
October | 49.64 | 17.61 | 32.03 | 79.67 | 18.72 | 0.17 | 0.00 | 744.00 |
November | 47.28 | 17.85 | 29.42 | 77.18 | 20.90 | 0.00 | 0.00 | 720.00 |
December | 47.84 | 21.50 | 26.35 | 78.30 | 25.24 | 1.67 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 94.70 | 20.12 | 48.33 | 0.00 | 8760.00 |
Minimum of Months | 47.28 | 17.61 | 26.35 | 77.18 | 16.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.78 | 40.48 | 35.55 | 118.77 | 25.29 | 34.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.62 | 24.74 | 26.87 | 85.53 | 24.22 | 0.00 | 0.00 | 744.00 |
February | 59.43 | 30.81 | 28.62 | 100.14 | 25.29 | 0.00 | 0.00 | 672.00 |
March | 69.04 | 40.48 | 28.55 | 117.61 | 22.33 | 0.00 | 0.00 | 744.00 |
April | 69.78 | 39.07 | 30.72 | 118.77 | 18.19 | 0.00 | 0.00 | 720.00 |
May | 58.44 | 25.40 | 33.05 | 98.37 | 16.89 | 34.83 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 107.01 | 16.48 | 4.00 | 0.00 | 720.00 |
July | 53.18 | 17.62 | 35.55 | 88.81 | 18.01 | 0.00 | 0.00 | 744.00 |
August | 58.72 | 25.20 | 33.52 | 95.02 | 17.82 | 7.67 | 0.00 | 744.00 |
September | 54.30 | 21.10 | 33.20 | 90.99 | 17.57 | 0.00 | 0.00 | 720.00 |
October | 49.64 | 17.61 | 32.03 | 79.67 | 18.72 | 0.17 | 0.00 | 744.00 |
November | 47.28 | 17.85 | 29.42 | 77.18 | 20.90 | 0.00 | 0.00 | 720.00 |
December | 47.84 | 21.50 | 26.35 | 78.30 | 25.24 | 1.67 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 94.70 | 20.12 | 48.33 | 0.00 | 8760.00 |
Minimum of Months | 47.28 | 17.61 | 26.35 | 77.18 | 16.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.78 | 40.48 | 35.55 | 118.77 | 25.29 | 34.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.62 | 24.74 | 26.87 | 85.53 | 24.22 | 0.00 | 0.00 | 744.00 |
February | 59.43 | 30.81 | 28.62 | 100.14 | 25.29 | 0.00 | 0.00 | 672.00 |
March | 69.04 | 40.48 | 28.55 | 117.61 | 22.33 | 0.00 | 0.00 | 744.00 |
April | 69.78 | 39.07 | 30.72 | 118.77 | 18.19 | 0.00 | 0.00 | 720.00 |
May | 58.44 | 25.40 | 33.05 | 98.37 | 16.89 | 34.83 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 107.01 | 16.48 | 4.00 | 0.00 | 720.00 |
July | 53.18 | 17.62 | 35.55 | 88.81 | 18.01 | 0.00 | 0.00 | 744.00 |
August | 58.72 | 25.20 | 33.52 | 95.02 | 17.82 | 7.67 | 0.00 | 744.00 |
September | 54.30 | 21.10 | 33.20 | 90.99 | 17.57 | 0.00 | 0.00 | 720.00 |
October | 49.64 | 17.61 | 32.03 | 79.67 | 18.72 | 0.17 | 0.00 | 744.00 |
November | 47.28 | 17.85 | 29.42 | 77.18 | 20.90 | 0.00 | 0.00 | 720.00 |
December | 47.84 | 21.50 | 26.35 | 78.30 | 25.24 | 1.67 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 94.70 | 20.12 | 48.33 | 0.00 | 8760.00 |
Minimum of Months | 47.28 | 17.61 | 26.35 | 77.18 | 16.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.78 | 40.48 | 35.55 | 118.77 | 25.29 | 34.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.62 | 24.74 | 26.87 | 85.53 | 24.22 | 0.00 | 0.00 | 744.00 |
February | 59.43 | 30.81 | 28.62 | 100.14 | 25.29 | 0.00 | 0.00 | 672.00 |
March | 69.04 | 40.48 | 28.55 | 117.61 | 22.33 | 0.00 | 0.00 | 744.00 |
April | 69.78 | 39.07 | 30.72 | 118.77 | 18.19 | 0.00 | 0.00 | 720.00 |
May | 58.44 | 25.40 | 33.05 | 98.37 | 16.89 | 34.83 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 107.01 | 16.48 | 4.00 | 0.00 | 720.00 |
July | 53.18 | 17.62 | 35.55 | 88.81 | 18.01 | 0.00 | 0.00 | 744.00 |
August | 58.72 | 25.20 | 33.52 | 95.02 | 17.82 | 7.67 | 0.00 | 744.00 |
September | 54.30 | 21.10 | 33.20 | 90.99 | 17.57 | 0.00 | 0.00 | 720.00 |
October | 49.64 | 17.61 | 32.03 | 79.67 | 18.72 | 0.17 | 0.00 | 744.00 |
November | 47.28 | 17.85 | 29.42 | 77.18 | 20.90 | 0.00 | 0.00 | 720.00 |
December | 47.84 | 21.50 | 26.35 | 78.30 | 25.24 | 1.67 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 94.70 | 20.12 | 48.33 | 0.00 | 8760.00 |
Minimum of Months | 47.28 | 17.61 | 26.35 | 77.18 | 16.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.78 | 40.48 | 35.55 | 118.77 | 25.29 | 34.83 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158849E+09 | 55982360.59 | 0.102867E+09 | 0.506490E+09 | 0.135996E+09 |
February | 0.157130E+09 | 55469701.08 | 0.101660E+09 | 0.518140E+09 | 0.103380E+09 |
March | 0.194802E+09 | 76662019.87 | 0.118140E+09 | 0.657992E+09 | 95125349.84 |
April | 0.188992E+09 | 71828623.30 | 0.117164E+09 | 0.630289E+09 | 60515344.83 |
May | 0.166569E+09 | 49066205.86 | 0.117503E+09 | 0.566036E+09 | 66957775.27 |
June | 0.174651E+09 | 59915364.64 | 0.114736E+09 | 0.587000E+09 | 67418013.08 |
July | 0.154028E+09 | 36129135.52 | 0.117899E+09 | 0.491511E+09 | 94368395.21 |
August | 0.167424E+09 | 49321519.30 | 0.118102E+09 | 0.501338E+09 | 86018165.38 |
September | 0.151382E+09 | 41525917.38 | 0.109856E+09 | 0.485184E+09 | 82044510.73 |
October | 0.147149E+09 | 37628021.32 | 0.109521E+09 | 0.437420E+09 | 0.101761E+09 |
November | 0.138895E+09 | 37640548.35 | 0.101254E+09 | 0.428123E+09 | 0.104379E+09 |
December | 0.147325E+09 | 48250125.10 | 99074415.80 | 0.465214E+09 | 0.144678E+09 |
Annual Sum or Average | 0.194719E+10 | 0.619420E+09 | 0.132778E+10 | 0.627474E+10 | 0.114264E+10 |
Minimum of Months | 0.138895E+09 | 36129135.52 | 99074415.80 | 0.428123E+09 | 60515344.83 |
Maximum of Months | 0.194802E+09 | 76662019.87 | 0.118140E+09 | 0.657992E+09 | 0.144678E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158849E+09 | 55982360.59 | 0.102867E+09 | 0.506490E+09 | 0.135996E+09 |
February | 0.157130E+09 | 55469701.08 | 0.101660E+09 | 0.518140E+09 | 0.103380E+09 |
March | 0.194802E+09 | 76662019.87 | 0.118140E+09 | 0.657992E+09 | 95125349.84 |
April | 0.188992E+09 | 71828623.30 | 0.117164E+09 | 0.630289E+09 | 60515344.83 |
May | 0.166569E+09 | 49066205.86 | 0.117503E+09 | 0.566036E+09 | 66957775.27 |
June | 0.174651E+09 | 59915364.64 | 0.114736E+09 | 0.587000E+09 | 67418013.08 |
July | 0.154028E+09 | 36129135.52 | 0.117899E+09 | 0.491511E+09 | 94368395.21 |
August | 0.167424E+09 | 49321519.30 | 0.118102E+09 | 0.501338E+09 | 86018165.38 |
September | 0.151382E+09 | 41525917.38 | 0.109856E+09 | 0.485184E+09 | 82044510.73 |
October | 0.147149E+09 | 37628021.32 | 0.109521E+09 | 0.437420E+09 | 0.101761E+09 |
November | 0.138895E+09 | 37640548.35 | 0.101254E+09 | 0.428123E+09 | 0.104379E+09 |
December | 0.147325E+09 | 48250125.10 | 99074415.80 | 0.465214E+09 | 0.144678E+09 |
Annual Sum or Average | 0.194719E+10 | 0.619420E+09 | 0.132778E+10 | 0.627474E+10 | 0.114264E+10 |
Minimum of Months | 0.138895E+09 | 36129135.52 | 99074415.80 | 0.428123E+09 | 60515344.83 |
Maximum of Months | 0.194802E+09 | 76662019.87 | 0.118140E+09 | 0.657992E+09 | 0.144678E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 47356040.84 | 0.00 | 47356040.84 | 0.151839E+09 | 79723548.86 |
February | 45627293.46 | 0.00 | 45627293.46 | 0.157457E+09 | 60335368.33 |
March | 51896300.46 | 18257.31 | 51878043.15 | 0.192686E+09 | 55483883.56 |
April | 56002884.19 | 1739798.02 | 54263086.17 | 0.204847E+09 | 35303037.68 |
May | 75582452.44 | 10962496.64 | 64619955.80 | 0.267771E+09 | 38897425.14 |
June | 90010081.75 | 21792916.29 | 68217165.47 | 0.316791E+09 | 39295264.10 |
July | 78223258.59 | 10211550.70 | 68011707.89 | 0.251476E+09 | 53992863.64 |
August | 64551330.50 | 4623618.60 | 59927711.90 | 0.201247E+09 | 49634391.92 |
September | 51686267.98 | 132783.94 | 51553484.04 | 0.176463E+09 | 48270460.74 |
October | 51311374.35 | 0.00 | 51311374.35 | 0.154400E+09 | 60266896.27 |
November | 46985672.13 | 0.00 | 46985672.13 | 0.146900E+09 | 61678400.18 |
December | 46005736.81 | 0.00 | 46005736.81 | 0.145683E+09 | 84836211.40 |
Annual Sum or Average | 0.705239E+09 | 49481421.49 | 0.655757E+09 | 0.236756E+10 | 0.667718E+09 |
Minimum of Months | 45627293.46 | 0.00 | 45627293.46 | 0.145683E+09 | 35303037.68 |
Maximum of Months | 90010081.75 | 21792916.29 | 68217165.47 | 0.316791E+09 | 84836211.40 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 47354580.59 | 0.00 | 47354580.59 | 0.151835E+09 | 79722321.01 |
February | 45625938.29 | 0.00 | 45625938.29 | 0.157454E+09 | 60333934.99 |
March | 51894855.67 | 18256.46 | 51876599.22 | 0.192682E+09 | 55482486.13 |
April | 56001228.12 | 1739716.48 | 54261511.64 | 0.204843E+09 | 35301934.28 |
May | 75579760.18 | 10961982.81 | 64617777.37 | 0.267764E+09 | 38896565.46 |
June | 90006748.40 | 21791894.82 | 68214853.58 | 0.316782E+09 | 39294478.90 |
July | 78220373.67 | 10211072.07 | 68009301.60 | 0.251469E+09 | 53991954.61 |
August | 64549158.84 | 4623401.88 | 59925756.96 | 0.201242E+09 | 49633512.27 |
September | 51684612.67 | 132777.71 | 51551834.95 | 0.176459E+09 | 48269632.51 |
October | 51309699.92 | 0.00 | 51309699.92 | 0.154396E+09 | 60266111.90 |
November | 46984147.09 | 0.00 | 46984147.09 | 0.146897E+09 | 61677420.30 |
December | 46004288.51 | 0.00 | 46004288.51 | 0.145679E+09 | 84835043.81 |
Annual Sum or Average | 0.705215E+09 | 49479102.23 | 0.655736E+09 | 0.236750E+10 | 0.667705E+09 |
Minimum of Months | 45625938.29 | 0.00 | 45625938.29 | 0.145679E+09 | 35301934.28 |
Maximum of Months | 90006748.40 | 21791894.82 | 68214853.58 | 0.316782E+09 | 84835043.81 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138256E+09 | 66275299.73 | 71980549.25 | 0.229083E+09 | 64878490.77 |
February | 0.143772E+09 | 74537664.27 | 69233957.81 | 0.242251E+09 | 61192205.89 |
March | 0.184904E+09 | 0.108435E+09 | 76469118.23 | 0.314995E+09 | 59806913.71 |
April | 0.180876E+09 | 0.101262E+09 | 79613982.98 | 0.307861E+09 | 47137411.34 |
May | 0.156538E+09 | 68020802.84 | 88517511.72 | 0.263476E+09 | 45244942.58 |
June | 0.163763E+09 | 81002889.06 | 82760074.06 | 0.277367E+09 | 42709129.85 |
July | 0.142429E+09 | 47204980.34 | 95223757.14 | 0.237857E+09 | 48248253.23 |
August | 0.157285E+09 | 67495056.73 | 89789612.58 | 0.254489E+09 | 47725402.46 |
September | 0.140742E+09 | 54681936.50 | 86060542.30 | 0.235856E+09 | 45531148.44 |
October | 0.132962E+09 | 47164698.97 | 85797576.23 | 0.213384E+09 | 50151254.59 |
November | 0.122541E+09 | 46277500.99 | 76263905.51 | 0.200055E+09 | 54170911.17 |
December | 0.128148E+09 | 57572763.17 | 70574790.87 | 0.209719E+09 | 67594533.32 |
Annual Sum or Average | 0.179222E+10 | 0.819931E+09 | 0.972285E+09 | 0.298639E+10 | 0.634391E+09 |
Minimum of Months | 0.122541E+09 | 46277500.99 | 69233957.81 | 0.200055E+09 | 42709129.85 |
Maximum of Months | 0.184904E+09 | 0.108435E+09 | 95223757.14 | 0.314995E+09 | 67594533.32 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138256E+09 | 66275299.73 | 71980549.25 | 0.229083E+09 | 64878490.77 |
February | 0.143772E+09 | 74537664.27 | 69233957.81 | 0.242251E+09 | 61192205.89 |
March | 0.184904E+09 | 0.108435E+09 | 76469118.23 | 0.314995E+09 | 59806913.71 |
April | 0.180876E+09 | 0.101262E+09 | 79613982.98 | 0.307861E+09 | 47137411.34 |
May | 0.156538E+09 | 68020802.84 | 88517511.72 | 0.263476E+09 | 45244942.58 |
June | 0.163763E+09 | 81002889.06 | 82760074.06 | 0.277367E+09 | 42709129.85 |
July | 0.142429E+09 | 47204980.34 | 95223757.14 | 0.237857E+09 | 48248253.23 |
August | 0.157285E+09 | 67495056.73 | 89789612.58 | 0.254489E+09 | 47725402.46 |
September | 0.140742E+09 | 54681936.50 | 86060542.30 | 0.235856E+09 | 45531148.44 |
October | 0.132962E+09 | 47164698.97 | 85797576.23 | 0.213384E+09 | 50151254.59 |
November | 0.122541E+09 | 46277500.99 | 76263905.51 | 0.200055E+09 | 54170911.17 |
December | 0.128148E+09 | 57572763.17 | 70574790.87 | 0.209719E+09 | 67594533.32 |
Annual Sum or Average | 0.179222E+10 | 0.819931E+09 | 0.972285E+09 | 0.298639E+10 | 0.634391E+09 |
Minimum of Months | 0.122541E+09 | 46277500.99 | 69233957.81 | 0.200055E+09 | 42709129.85 |
Maximum of Months | 0.184904E+09 | 0.108435E+09 | 95223757.14 | 0.314995E+09 | 67594533.32 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138256E+09 | 66275299.73 | 71980549.25 | 0.229083E+09 | 64878490.77 |
February | 0.143772E+09 | 74537664.27 | 69233957.81 | 0.242251E+09 | 61192205.89 |
March | 0.184904E+09 | 0.108435E+09 | 76469118.23 | 0.314995E+09 | 59806913.71 |
April | 0.180876E+09 | 0.101262E+09 | 79613982.98 | 0.307861E+09 | 47137411.34 |
May | 0.156538E+09 | 68020802.84 | 88517511.72 | 0.263476E+09 | 45244942.58 |
June | 0.163763E+09 | 81002889.06 | 82760074.06 | 0.277367E+09 | 42709129.85 |
July | 0.142429E+09 | 47204980.34 | 95223757.14 | 0.237857E+09 | 48248253.23 |
August | 0.157285E+09 | 67495056.73 | 89789612.58 | 0.254489E+09 | 47725402.46 |
September | 0.140742E+09 | 54681936.50 | 86060542.30 | 0.235856E+09 | 45531148.44 |
October | 0.132962E+09 | 47164698.97 | 85797576.23 | 0.213384E+09 | 50151254.59 |
November | 0.122541E+09 | 46277500.99 | 76263905.51 | 0.200055E+09 | 54170911.17 |
December | 0.128148E+09 | 57572763.17 | 70574790.87 | 0.209719E+09 | 67594533.32 |
Annual Sum or Average | 0.179222E+10 | 0.819931E+09 | 0.972285E+09 | 0.298639E+10 | 0.634391E+09 |
Minimum of Months | 0.122541E+09 | 46277500.99 | 69233957.81 | 0.200055E+09 | 42709129.85 |
Maximum of Months | 0.184904E+09 | 0.108435E+09 | 95223757.14 | 0.314995E+09 | 67594533.32 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138256E+09 | 66275299.73 | 71980549.25 | 0.229083E+09 | 64878490.77 |
February | 0.143772E+09 | 74537664.27 | 69233957.81 | 0.242251E+09 | 61192205.89 |
March | 0.184904E+09 | 0.108435E+09 | 76469118.23 | 0.314995E+09 | 59806913.71 |
April | 0.180876E+09 | 0.101262E+09 | 79613982.98 | 0.307861E+09 | 47137411.34 |
May | 0.156538E+09 | 68020802.84 | 88517511.72 | 0.263476E+09 | 45244942.58 |
June | 0.163763E+09 | 81002889.06 | 82760074.06 | 0.277367E+09 | 42709129.85 |
July | 0.142429E+09 | 47204980.34 | 95223757.14 | 0.237857E+09 | 48248253.23 |
August | 0.157285E+09 | 67495056.73 | 89789612.58 | 0.254489E+09 | 47725402.46 |
September | 0.140742E+09 | 54681936.50 | 86060542.30 | 0.235856E+09 | 45531148.44 |
October | 0.132962E+09 | 47164698.97 | 85797576.23 | 0.213384E+09 | 50151254.59 |
November | 0.122541E+09 | 46277500.99 | 76263905.51 | 0.200055E+09 | 54170911.17 |
December | 0.128148E+09 | 57572763.17 | 70574790.87 | 0.209719E+09 | 67594533.32 |
Annual Sum or Average | 0.179222E+10 | 0.819931E+09 | 0.972285E+09 | 0.298639E+10 | 0.634391E+09 |
Minimum of Months | 0.122541E+09 | 46277500.99 | 69233957.81 | 0.200055E+09 | 42709129.85 |
Maximum of Months | 0.184904E+09 | 0.108435E+09 | 95223757.14 | 0.314995E+09 | 67594533.32 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138256E+09 | 66275299.73 | 71980549.25 | 0.229083E+09 | 64878490.77 |
February | 0.143772E+09 | 74537664.27 | 69233957.81 | 0.242251E+09 | 61192205.89 |
March | 0.184904E+09 | 0.108435E+09 | 76469118.23 | 0.314995E+09 | 59806913.71 |
April | 0.180876E+09 | 0.101262E+09 | 79613982.98 | 0.307861E+09 | 47137411.34 |
May | 0.156538E+09 | 68020802.84 | 88517511.72 | 0.263476E+09 | 45244942.58 |
June | 0.163763E+09 | 81002889.06 | 82760074.06 | 0.277367E+09 | 42709129.85 |
July | 0.142429E+09 | 47204980.34 | 95223757.14 | 0.237857E+09 | 48248253.23 |
August | 0.157285E+09 | 67495056.73 | 89789612.58 | 0.254489E+09 | 47725402.46 |
September | 0.140742E+09 | 54681936.50 | 86060542.30 | 0.235856E+09 | 45531148.44 |
October | 0.132962E+09 | 47164698.97 | 85797576.23 | 0.213384E+09 | 50151254.59 |
November | 0.122541E+09 | 46277500.99 | 76263905.51 | 0.200055E+09 | 54170911.17 |
December | 0.128148E+09 | 57572763.17 | 70574790.87 | 0.209719E+09 | 67594533.32 |
Annual Sum or Average | 0.179222E+10 | 0.819931E+09 | 0.972285E+09 | 0.298639E+10 | 0.634391E+09 |
Minimum of Months | 0.122541E+09 | 46277500.99 | 69233957.81 | 0.200055E+09 | 42709129.85 |
Maximum of Months | 0.184904E+09 | 0.108435E+09 | 95223757.14 | 0.314995E+09 | 67594533.32 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138256E+09 | 66275299.73 | 71980549.25 | 0.229083E+09 | 64878490.77 |
February | 0.143772E+09 | 74537664.27 | 69233957.81 | 0.242251E+09 | 61192205.89 |
March | 0.184904E+09 | 0.108435E+09 | 76469118.23 | 0.314995E+09 | 59806913.71 |
April | 0.180876E+09 | 0.101262E+09 | 79613982.98 | 0.307861E+09 | 47137411.34 |
May | 0.156538E+09 | 68020802.84 | 88517511.72 | 0.263476E+09 | 45244942.58 |
June | 0.163763E+09 | 81002889.06 | 82760074.06 | 0.277367E+09 | 42709129.85 |
July | 0.142429E+09 | 47204980.34 | 95223757.14 | 0.237857E+09 | 48248253.23 |
August | 0.157285E+09 | 67495056.73 | 89789612.58 | 0.254489E+09 | 47725402.46 |
September | 0.140742E+09 | 54681936.50 | 86060542.30 | 0.235856E+09 | 45531148.44 |
October | 0.132962E+09 | 47164698.97 | 85797576.23 | 0.213384E+09 | 50151254.59 |
November | 0.122541E+09 | 46277500.99 | 76263905.51 | 0.200055E+09 | 54170911.17 |
December | 0.128148E+09 | 57572763.17 | 70574790.87 | 0.209719E+09 | 67594533.32 |
Annual Sum or Average | 0.179222E+10 | 0.819931E+09 | 0.972285E+09 | 0.298639E+10 | 0.634391E+09 |
Minimum of Months | 0.122541E+09 | 46277500.99 | 69233957.81 | 0.200055E+09 | 42709129.85 |
Maximum of Months | 0.184904E+09 | 0.108435E+09 | 95223757.14 | 0.314995E+09 | 67594533.32 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138256E+09 | 66275299.73 | 71980549.25 | 0.229083E+09 | 64878490.77 |
February | 0.143772E+09 | 74537664.27 | 69233957.81 | 0.242251E+09 | 61192205.89 |
March | 0.184904E+09 | 0.108435E+09 | 76469118.23 | 0.314995E+09 | 59806913.71 |
April | 0.180876E+09 | 0.101262E+09 | 79613982.98 | 0.307861E+09 | 47137411.34 |
May | 0.156538E+09 | 68020802.84 | 88517511.72 | 0.263476E+09 | 45244942.58 |
June | 0.163763E+09 | 81002889.06 | 82760074.06 | 0.277367E+09 | 42709129.85 |
July | 0.142429E+09 | 47204980.34 | 95223757.14 | 0.237857E+09 | 48248253.23 |
August | 0.157285E+09 | 67495056.73 | 89789612.58 | 0.254489E+09 | 47725402.46 |
September | 0.140742E+09 | 54681936.50 | 86060542.30 | 0.235856E+09 | 45531148.44 |
October | 0.132962E+09 | 47164698.97 | 85797576.23 | 0.213384E+09 | 50151254.59 |
November | 0.122541E+09 | 46277500.99 | 76263905.51 | 0.200055E+09 | 54170911.17 |
December | 0.128148E+09 | 57572763.17 | 70574790.87 | 0.209719E+09 | 67594533.32 |
Annual Sum or Average | 0.179222E+10 | 0.819931E+09 | 0.972285E+09 | 0.298639E+10 | 0.634391E+09 |
Minimum of Months | 0.122541E+09 | 46277500.99 | 69233957.81 | 0.200055E+09 | 42709129.85 |
Maximum of Months | 0.184904E+09 | 0.108435E+09 | 95223757.14 | 0.314995E+09 | 67594533.32 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138256E+09 | 66275299.73 | 71980549.25 | 0.229083E+09 | 64878490.77 |
February | 0.143772E+09 | 74537664.27 | 69233957.81 | 0.242251E+09 | 61192205.89 |
March | 0.184904E+09 | 0.108435E+09 | 76469118.23 | 0.314995E+09 | 59806913.71 |
April | 0.180876E+09 | 0.101262E+09 | 79613982.98 | 0.307861E+09 | 47137411.34 |
May | 0.156538E+09 | 68020802.84 | 88517511.72 | 0.263476E+09 | 45244942.58 |
June | 0.163763E+09 | 81002889.06 | 82760074.06 | 0.277367E+09 | 42709129.85 |
July | 0.142429E+09 | 47204980.34 | 95223757.14 | 0.237857E+09 | 48248253.23 |
August | 0.157285E+09 | 67495056.73 | 89789612.58 | 0.254489E+09 | 47725402.46 |
September | 0.140742E+09 | 54681936.50 | 86060542.30 | 0.235856E+09 | 45531148.44 |
October | 0.132962E+09 | 47164698.97 | 85797576.23 | 0.213384E+09 | 50151254.59 |
November | 0.122541E+09 | 46277500.99 | 76263905.51 | 0.200055E+09 | 54170911.17 |
December | 0.128148E+09 | 57572763.17 | 70574790.87 | 0.209719E+09 | 67594533.32 |
Annual Sum or Average | 0.179222E+10 | 0.819931E+09 | 0.972285E+09 | 0.298639E+10 | 0.634391E+09 |
Minimum of Months | 0.122541E+09 | 46277500.99 | 69233957.81 | 0.200055E+09 | 42709129.85 |
Maximum of Months | 0.184904E+09 | 0.108435E+09 | 95223757.14 | 0.314995E+09 | 67594533.32 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138256E+09 | 66275299.73 | 71980549.25 | 0.229083E+09 | 64878490.77 |
February | 0.143772E+09 | 74537664.27 | 69233957.81 | 0.242251E+09 | 61192205.89 |
March | 0.184904E+09 | 0.108435E+09 | 76469118.23 | 0.314995E+09 | 59806913.71 |
April | 0.180876E+09 | 0.101262E+09 | 79613982.98 | 0.307861E+09 | 47137411.34 |
May | 0.156538E+09 | 68020802.84 | 88517511.72 | 0.263476E+09 | 45244942.58 |
June | 0.163763E+09 | 81002889.06 | 82760074.06 | 0.277367E+09 | 42709129.85 |
July | 0.142429E+09 | 47204980.34 | 95223757.14 | 0.237857E+09 | 48248253.23 |
August | 0.157285E+09 | 67495056.73 | 89789612.58 | 0.254489E+09 | 47725402.46 |
September | 0.140742E+09 | 54681936.50 | 86060542.30 | 0.235856E+09 | 45531148.44 |
October | 0.132962E+09 | 47164698.97 | 85797576.23 | 0.213384E+09 | 50151254.59 |
November | 0.122541E+09 | 46277500.99 | 76263905.51 | 0.200055E+09 | 54170911.17 |
December | 0.128148E+09 | 57572763.17 | 70574790.87 | 0.209719E+09 | 67594533.32 |
Annual Sum or Average | 0.179222E+10 | 0.819931E+09 | 0.972285E+09 | 0.298639E+10 | 0.634391E+09 |
Minimum of Months | 0.122541E+09 | 46277500.99 | 69233957.81 | 0.200055E+09 | 42709129.85 |
Maximum of Months | 0.184904E+09 | 0.108435E+09 | 95223757.14 | 0.314995E+09 | 67594533.32 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138256E+09 | 66275299.73 | 71980549.25 | 0.229083E+09 | 64878490.77 |
February | 0.143772E+09 | 74537664.27 | 69233957.81 | 0.242251E+09 | 61192205.89 |
March | 0.184904E+09 | 0.108435E+09 | 76469118.23 | 0.314995E+09 | 59806913.71 |
April | 0.180876E+09 | 0.101262E+09 | 79613982.98 | 0.307861E+09 | 47137411.34 |
May | 0.156538E+09 | 68020802.84 | 88517511.72 | 0.263476E+09 | 45244942.58 |
June | 0.163763E+09 | 81002889.06 | 82760074.06 | 0.277367E+09 | 42709129.85 |
July | 0.142429E+09 | 47204980.34 | 95223757.14 | 0.237857E+09 | 48248253.23 |
August | 0.157285E+09 | 67495056.73 | 89789612.58 | 0.254489E+09 | 47725402.46 |
September | 0.140742E+09 | 54681936.50 | 86060542.30 | 0.235856E+09 | 45531148.44 |
October | 0.132962E+09 | 47164698.97 | 85797576.23 | 0.213384E+09 | 50151254.59 |
November | 0.122541E+09 | 46277500.99 | 76263905.51 | 0.200055E+09 | 54170911.17 |
December | 0.128148E+09 | 57572763.17 | 70574790.87 | 0.209719E+09 | 67594533.32 |
Annual Sum or Average | 0.179222E+10 | 0.819931E+09 | 0.972285E+09 | 0.298639E+10 | 0.634391E+09 |
Minimum of Months | 0.122541E+09 | 46277500.99 | 69233957.81 | 0.200055E+09 | 42709129.85 |
Maximum of Months | 0.184904E+09 | 0.108435E+09 | 95223757.14 | 0.314995E+09 | 67594533.32 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 491.49 | 160.99 | 153.98 | 41.80 | 112.17 | 0.00 | 0.00 |
February | 558.52 | 135.34 | 167.62 | 45.86 | 121.77 | 0.00 | 0.00 |
March | 635.12 | 112.37 | 184.21 | 57.26 | 126.95 | 0.00 | 0.00 |
April | 644.13 | 73.67 | 189.04 | 56.77 | 132.27 | 0.00 | 0.00 |
May | 622.24 | 78.67 | 180.82 | 44.82 | 135.99 | 0.00 | 0.00 |
June | 696.84 | 81.81 | 204.21 | 63.05 | 141.17 | 0.00 | 0.00 |
July | 554.12 | 110.10 | 173.42 | 34.60 | 138.82 | 0.00 | 0.00 |
August | 524.15 | 100.81 | 173.22 | 40.28 | 132.94 | 0.00 | 0.00 |
September | 510.28 | 100.30 | 156.69 | 32.14 | 124.54 | 0.00 | 0.00 |
October | 441.63 | 120.70 | 148.19 | 28.10 | 120.09 | 0.00 | 0.00 |
November | 443.36 | 127.80 | 143.43 | 29.04 | 114.38 | 0.00 | 0.00 |
December | 456.08 | 171.29 | 144.36 | 36.03 | 108.33 | 0.00 | 0.00 |
Annual Sum or Average | 547.80 | 114.52 | 168.22 | 42.42 | 125.79 | 0.00 | 0.00 |
Minimum of Months | 441.63 | 73.67 | 143.43 | 28.10 | 108.33 | 0.00 | 0.00 |
Maximum of Months | 696.84 | 171.29 | 204.21 | 63.05 | 141.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 855.30 | 242.23 | 516.19 | 247.44 | 268.74 | 0.00 | 0.00 |
February | 1001.37 | 252.94 | 594.29 | 308.11 | 286.19 | 0.00 | 0.00 |
March | 1176.06 | 223.29 | 690.35 | 404.85 | 285.50 | 0.00 | 0.00 |
April | 1187.74 | 181.86 | 697.82 | 390.67 | 307.15 | 0.00 | 0.00 |
May | 983.71 | 168.92 | 584.45 | 253.96 | 330.49 | 0.00 | 0.00 |
June | 1070.09 | 164.77 | 631.80 | 312.51 | 319.29 | 0.00 | 0.00 |
July | 888.05 | 180.14 | 531.77 | 176.24 | 355.52 | 0.00 | 0.00 |
August | 950.15 | 178.19 | 587.23 | 252.00 | 335.24 | 0.00 | 0.00 |
September | 909.94 | 175.66 | 542.99 | 210.96 | 332.02 | 0.00 | 0.00 |
October | 796.68 | 187.24 | 496.42 | 176.09 | 320.33 | 0.00 | 0.00 |
November | 771.82 | 208.99 | 472.77 | 178.54 | 294.23 | 0.00 | 0.00 |
December | 783.00 | 252.37 | 478.45 | 214.95 | 263.50 | 0.00 | 0.00 |
Annual Sum or Average | 946.98 | 201.16 | 568.31 | 260.00 | 308.31 | 0.00 | 0.00 |
Minimum of Months | 771.82 | 164.77 | 472.77 | 176.09 | 263.50 | 0.00 | 0.00 |
Maximum of Months | 1187.74 | 252.94 | 697.82 | 404.85 | 355.52 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.131642E+10 | 0.431203E+09 | 0.412409E+09 | 0.111965E+09 | 0.300445E+09 | 0.00 | 0.00 |
February | 0.135117E+10 | 0.327412E+09 | 0.405513E+09 | 0.110939E+09 | 0.294574E+09 | 0.00 | 0.00 |
March | 0.170110E+10 | 0.300961E+09 | 0.493395E+09 | 0.153361E+09 | 0.340035E+09 | 0.00 | 0.00 |
April | 0.166958E+10 | 0.190946E+09 | 0.489989E+09 | 0.147137E+09 | 0.342852E+09 | 0.00 | 0.00 |
May | 0.166662E+10 | 0.210720E+09 | 0.484300E+09 | 0.120057E+09 | 0.364243E+09 | 0.00 | 0.00 |
June | 0.180621E+10 | 0.212061E+09 | 0.529319E+09 | 0.163416E+09 | 0.365904E+09 | 0.00 | 0.00 |
July | 0.148415E+10 | 0.294903E+09 | 0.464500E+09 | 92680893.81 | 0.371819E+09 | 0.00 | 0.00 |
August | 0.140388E+10 | 0.270019E+09 | 0.463948E+09 | 0.107890E+09 | 0.356058E+09 | 0.00 | 0.00 |
September | 0.132264E+10 | 0.259979E+09 | 0.406134E+09 | 83317396.40 | 0.322817E+09 | 0.00 | 0.00 |
October | 0.118287E+10 | 0.323291E+09 | 0.396918E+09 | 75256042.65 | 0.321662E+09 | 0.00 | 0.00 |
November | 0.114918E+10 | 0.331247E+09 | 0.371759E+09 | 75281096.70 | 0.296478E+09 | 0.00 | 0.00 |
December | 0.122156E+10 | 0.458796E+09 | 0.386659E+09 | 96500250.19 | 0.290159E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.172754E+11 | 0.361154E+10 | 0.530484E+10 | 0.133780E+10 | 0.396704E+10 | 0.00 | 0.00 |
Minimum of Months | 0.114918E+10 | 0.190946E+09 | 0.371759E+09 | 75256042.65 | 0.290159E+09 | 0.00 | 0.00 |
Maximum of Months | 0.180621E+10 | 0.458796E+09 | 0.529319E+09 | 0.163416E+09 | 0.371819E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.229083E+10 | 0.648781E+09 | 0.138256E+10 | 0.662753E+09 | 0.719805E+09 | 0.00 | 0.00 |
February | 0.242250E+10 | 0.611921E+09 | 0.143772E+10 | 0.745377E+09 | 0.692340E+09 | 0.00 | 0.00 |
March | 0.314995E+10 | 0.598066E+09 | 0.184904E+10 | 0.108435E+10 | 0.764691E+09 | 0.00 | 0.00 |
April | 0.307861E+10 | 0.471374E+09 | 0.180876E+10 | 0.101262E+10 | 0.796140E+09 | 0.00 | 0.00 |
May | 0.263476E+10 | 0.452445E+09 | 0.156538E+10 | 0.680208E+09 | 0.885175E+09 | 0.00 | 0.00 |
June | 0.277366E+10 | 0.427088E+09 | 0.163763E+10 | 0.810029E+09 | 0.827601E+09 | 0.00 | 0.00 |
July | 0.237857E+10 | 0.482482E+09 | 0.142429E+10 | 0.472050E+09 | 0.952238E+09 | 0.00 | 0.00 |
August | 0.254489E+10 | 0.477254E+09 | 0.157285E+10 | 0.674951E+09 | 0.897896E+09 | 0.00 | 0.00 |
September | 0.235856E+10 | 0.455307E+09 | 0.140742E+10 | 0.546819E+09 | 0.860605E+09 | 0.00 | 0.00 |
October | 0.213384E+10 | 0.501510E+09 | 0.132962E+10 | 0.471647E+09 | 0.857976E+09 | 0.00 | 0.00 |
November | 0.200055E+10 | 0.541707E+09 | 0.122541E+10 | 0.462775E+09 | 0.762639E+09 | 0.00 | 0.00 |
December | 0.209719E+10 | 0.675941E+09 | 0.128148E+10 | 0.575728E+09 | 0.705748E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.298639E+11 | 0.634388E+10 | 0.179222E+11 | 0.819931E+10 | 0.972285E+10 | 0.00 | 0.00 |
Minimum of Months | 0.200055E+10 | 0.427088E+09 | 0.122541E+10 | 0.462775E+09 | 0.692340E+09 | 0.00 | 0.00 |
Maximum of Months | 0.314995E+10 | 0.675941E+09 | 0.184904E+10 | 0.108435E+10 | 0.952238E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.65 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.90 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.36 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 22.99 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.54 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.00 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.13 | 23.20 | 1.94 | 20.28 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.59 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 22.99 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.66 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.00 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 22.99 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.95 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.41 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.58 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.62 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.85 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.50 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.22 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.33 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.21 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.00 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.85 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.93 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.52 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.16 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.27 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.92 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.69 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.10 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.42 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.05 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.55 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.52 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.86 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.10 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.05 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.03 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.55 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.10 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.592440E+09 | -522975051.6 | 0.00 | 0.00 | 744.00 | 0.00 | -69465332.4 | 58.98 | 0.00 | 0.00 |
February | 0.540066E+09 | -477408018.2 | 0.00 | 0.00 | 672.00 | 0.00 | -62657732.3 | 58.99 | 0.00 | 0.00 |
March | 0.618736E+09 | -549207569.9 | 0.00 | 0.00 | 744.00 | 0.00 | -69528326.0 | 58.99 | 0.00 | 0.00 |
April | 0.565927E+09 | -499169277.5 | 0.00 | 0.00 | 720.00 | 0.00 | -66757285.7 | 58.98 | 0.00 | 0.00 |
May | 0.576790E+09 | -507774119.6 | 0.00 | 0.00 | 744.00 | 0.00 | -69016256.1 | 58.99 | 0.00 | 0.00 |
June | 0.565142E+09 | -498269675.2 | 0.00 | 0.00 | 720.00 | 0.00 | -66872803.5 | 58.99 | 0.00 | 0.00 |
July | 0.548105E+09 | -479125614.7 | 0.00 | 0.00 | 744.00 | 0.00 | -68978915.8 | 58.99 | 0.00 | 0.00 |
August | 0.587849E+09 | -518261952.8 | 0.00 | 0.00 | 744.00 | 0.00 | -69586641.8 | 58.99 | 0.00 | 0.00 |
September | 0.557051E+09 | -490051884.1 | 0.00 | 0.00 | 720.00 | 0.00 | -66998933.0 | 58.99 | 0.00 | 0.00 |
October | 0.571613E+09 | -502306213.6 | 0.00 | 0.00 | 744.00 | 0.00 | -69306861.5 | 58.99 | 0.00 | 0.00 |
November | 0.559852E+09 | -492724207.8 | 0.00 | 0.00 | 720.00 | 0.00 | -67127403.3 | 58.99 | 0.00 | 0.00 |
December | 0.590193E+09 | -520536013.6 | 0.00 | 0.00 | 744.00 | 0.00 | -69656929.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.687376E+10 | -.605781E+10 | 8760.00 | -815953420.7 | 58.99 | |||||
Minimum of Months | 0.540066E+09 | -549207569.9 | 0.00 | 0.00 | 672.00 | 0.00 | -69656929.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.618736E+09 | -477408018.2 | 0.00 | 0.00 | 744.00 | 0.00 | -62657732.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 350.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 361.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 376.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 370.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 383.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 357.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 356.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 349.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4292.33 | ||||||||||
Minimum of Months | 321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 383.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.146412E+11 | 0.107714E+11 | 30612.53 | 02-JAN-06:01 | 15473.58 | 0.00 |
February | 0.00 | 0.00 | 0.140880E+11 | 0.104463E+11 | 29572.16 | 15-FEB-06:01 | 16578.02 | 0.00 |
March | 0.00 | 0.00 | 0.177308E+11 | 0.127783E+11 | 30062.69 | 27-MAR-05:01 | 16200.96 | 0.00 |
April | 0.00 | 0.00 | 0.179353E+11 | 0.121950E+11 | 30261.12 | 10-APR-05:01 | 15823.80 | 0.00 |
May | 0.00 | 0.00 | 0.200209E+11 | 0.127195E+11 | 30583.56 | 17-MAY-05:01 | 14412.51 | 0.00 |
June | 0.00 | 0.00 | 0.203212E+11 | 0.129600E+11 | 30555.98 | 21-JUN-05:01 | 15402.68 | 0.00 |
July | 0.00 | 0.00 | 0.164320E+11 | 0.112615E+11 | 29862.37 | 03-JUL-05:01 | 16895.52 | 0.00 |
August | 0.00 | 0.00 | 0.195023E+11 | 0.121516E+11 | 30583.56 | 04-AUG-05:01 | 14507.18 | 0.00 |
September | 0.00 | 0.00 | 0.174438E+11 | 0.112625E+11 | 30353.39 | 18-SEP-05:01 | 15635.46 | 0.00 |
October | 0.00 | 0.00 | 0.165601E+11 | 0.106594E+11 | 30612.53 | 23-OCT-05:01 | 14868.99 | 0.00 |
November | 0.00 | 0.00 | 0.153099E+11 | 0.103636E+11 | 30288.28 | 13-NOV-06:01 | 15177.97 | 0.00 |
December | 0.00 | 0.00 | 0.143738E+11 | 0.103949E+11 | 30076.14 | 11-DEC-06:01 | 16366.54 | 0.00 |
Annual Sum or Average | 0.204359E+12 | 0.137964E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.140880E+11 | 0.103636E+11 | 29572.16 | 14412.51 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.203212E+11 | 0.129600E+11 | 30612.53 | 16895.52 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.411421E+11 | 0.287569E+11 | 81521.00 | 11-JAN-18:10 | 44951.78 | 0.00 |
February | 0.00 | 0.00 | 0.436298E+11 | 0.305932E+11 | 83307.69 | 18-FEB-06:01 | 46229.38 | 0.00 |
March | 0.00 | 0.00 | 0.575167E+11 | 0.386964E+11 | 85418.83 | 29-MAR-05:04 | 42382.17 | 0.00 |
April | 0.00 | 0.00 | 0.634191E+11 | 0.396337E+11 | 87989.16 | 22-APR-05:01 | 40128.25 | 0.00 |
May | 0.00 | 0.00 | 0.692422E+11 | 0.397640E+11 | 88065.65 | 13-MAY-05:19 | 37311.30 | 0.00 |
June | 0.00 | 0.00 | 0.714109E+11 | 0.411119E+11 | 88065.65 | 06-JUN-05:06 | 38371.25 | 0.00 |
July | 0.00 | 0.00 | 0.517715E+11 | 0.328733E+11 | 85291.37 | 15-JUL-05:01 | 43426.02 | 0.00 |
August | 0.00 | 0.00 | 0.588928E+11 | 0.327615E+11 | 88065.65 | 25-AUG-05:05 | 36505.98 | 0.00 |
September | 0.00 | 0.00 | 0.547502E+11 | 0.323185E+11 | 86847.40 | 02-SEP-05:10 | 40991.53 | 0.00 |
October | 0.00 | 0.00 | 0.478239E+11 | 0.281222E+11 | 85707.84 | 17-OCT-05:07 | 42698.47 | 0.00 |
November | 0.00 | 0.00 | 0.433000E+11 | 0.272984E+11 | 88466.01 | 13-NOV-06:09 | 39473.92 | 0.00 |
December | 0.00 | 0.00 | 0.393778E+11 | 0.266818E+11 | 85448.51 | 09-DEC-06:06 | 43683.35 | 0.00 |
Annual Sum or Average | 0.642277E+12 | 0.398612E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.393778E+11 | 0.266818E+11 | 81521.00 | 36505.98 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.714109E+11 | 0.411119E+11 | 88466.01 | 46229.38 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135366E+10 | 0.38 | 1314.31 | 02-JAN-06:01 | 0.91 |
February | 0.125168E+10 | 0.40 | 1314.31 | 01-FEB-06:01 | 0.92 |
March | 0.147748E+10 | 0.42 | 1314.31 | 01-MAR-06:01 | 0.92 |
April | 0.137894E+10 | 0.41 | 1314.31 | 04-APR-16:10 | 0.93 |
May | 0.143926E+10 | 0.41 | 1314.31 | 02-MAY-12:00 | 0.92 |
June | 0.143801E+10 | 0.42 | 1314.31 | 05-JUN-11:40 | 0.92 |
July | 0.136654E+10 | 0.39 | 1314.31 | 01-JUL-05:01 | 0.92 |
August | 0.147942E+10 | 0.41 | 1314.31 | 22-AUG-11:30 | 0.92 |
September | 0.136967E+10 | 0.40 | 1314.31 | 05-SEP-11:20 | 0.92 |
October | 0.136341E+10 | 0.38 | 1314.31 | 04-OCT-17:00 | 0.92 |
November | 0.130645E+10 | 0.38 | 1314.31 | 01-NOV-05:01 | 0.92 |
December | 0.135217E+10 | 0.38 | 1314.31 | 01-DEC-06:01 | 0.92 |
Annual Sum or Average | 0.165767E+11 | 0.40 | |||
Minimum of Months | 0.125168E+10 | 0.38 | 1314.31 | 0.91 | |
Maximum of Months | 0.147942E+10 | 0.42 | 1314.31 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.338256E+10 | 0.51 | 3028.53 | 17-JAN-09:00 | 0.88 |
February | 0.323503E+10 | 0.57 | 3028.53 | 18-FEB-08:40 | 0.88 |
March | 0.389101E+10 | 0.62 | 3028.53 | 28-MAR-06:50 | 0.88 |
April | 0.387553E+10 | 0.69 | 3028.53 | 13-APR-06:20 | 0.88 |
May | 0.403346E+10 | 0.67 | 3028.53 | 09-MAY-07:40 | 0.88 |
June | 0.405058E+10 | 0.70 | 3028.53 | 20-JUN-07:55 | 0.88 |
July | 0.368010E+10 | 0.64 | 3028.53 | 03-JUL-09:10 | 0.88 |
August | 0.383787E+10 | 0.60 | 3028.53 | 12-AUG-07:00 | 0.88 |
September | 0.365673E+10 | 0.63 | 3028.53 | 01-SEP-06:40 | 0.88 |
October | 0.352909E+10 | 0.57 | 3028.53 | 11-OCT-07:45 | 0.88 |
November | 0.332118E+10 | 0.54 | 3028.53 | 06-NOV-08:15 | 0.88 |
December | 0.335026E+10 | 0.49 | 3028.53 | 09-DEC-17:15 | 0.88 |
Annual Sum or Average | 0.438434E+11 | 0.60 | |||
Minimum of Months | 0.323503E+10 | 0.49 | 3028.53 | 0.88 | |
Maximum of Months | 0.405058E+10 | 0.70 | 3028.53 | 0.88 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.14 | 0.01 |
February | 2.82 | 0.00 |
March | 4.29 | 0.01 |
April | 5.17 | 0.06 |
May | 4.29 | 0.08 |
June | 4.46 | 0.05 |
July | 3.83 | 0.02 |
August | 4.24 | 0.04 |
September | 3.88 | 0.03 |
October | 2.98 | 0.02 |
November | 2.68 | 0.00 |
December | 3.44 | 0.01 |
Annual Sum or Average | 45.21 | 0.03 |
Minimum of Months | 2.68 | 0.00 |
Maximum of Months | 5.17 | 0.08 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.25 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.25 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.25 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 2.86 | 0.00 |
February | 6.83 | 0.00 |
March | 8.11 | 0.00 |
April | 10.60 | 0.00 |
May | 10.89 | 0.00 |
June | 10.47 | 0.00 |
July | 8.93 | 0.00 |
August | 6.06 | 0.00 |
September | 6.36 | 0.00 |
October | 2.08 | 0.00 |
November | 4.58 | 0.00 |
December | 2.89 | 0.00 |
Annual Sum or Average | 80.67 | |
Minimum of Months | 2.08 | 0.00 |
Maximum of Months | 10.89 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.535453E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.514351E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.639982E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.631759E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.688364E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.696610E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.577135E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.666281E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.603286E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.575314E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.540152E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.524838E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.719352E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.514351E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.696610E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.155029E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.161861E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.209328E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.224971E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.240821E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.246371E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.186695E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.205107E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.193486E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.171652E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.158025E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.148487E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.230183E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.148487E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.246371E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135366E+10 | 0.146412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125168E+10 | 0.140880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147748E+10 | 0.177308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137894E+10 | 0.179353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143926E+10 | 0.200209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143801E+10 | 0.203212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136654E+10 | 0.164320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147942E+10 | 0.195023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136967E+10 | 0.174438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136341E+10 | 0.165601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130645E+10 | 0.153099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135217E+10 | 0.143738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165767E+11 | 0.204359E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125168E+10 | 0.140880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147942E+10 | 0.203212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.338256E+10 | 0.411421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.323503E+10 | 0.436298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.389101E+10 | 0.575167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.387553E+10 | 0.634191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.403346E+10 | 0.692422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.405058E+10 | 0.714109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.368010E+10 | 0.517715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.383787E+10 | 0.588928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.365673E+10 | 0.547502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.352909E+10 | 0.478239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.332118E+10 | 0.433000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.335026E+10 | 0.393778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438434E+11 | 0.642277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.323503E+10 | 0.393778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.405058E+10 | 0.714109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.135366E+10 | 0.00 | 0.00 | 0.00 | 0.400087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125168E+10 | 0.00 | 0.00 | 0.00 | 0.389183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147748E+10 | 0.00 | 0.00 | 0.00 | 0.492234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137894E+10 | 0.00 | 0.00 | 0.00 | 0.493866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143926E+10 | 0.00 | 0.00 | 0.00 | 0.544438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143801E+10 | 0.00 | 0.00 | 0.00 | 0.552809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136654E+10 | 0.00 | 0.00 | 0.00 | 0.440481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147942E+10 | 0.00 | 0.00 | 0.00 | 0.518339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136967E+10 | 0.00 | 0.00 | 0.00 | 0.466319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136341E+10 | 0.00 | 0.00 | 0.00 | 0.438973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130645E+10 | 0.00 | 0.00 | 0.00 | 0.409506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135217E+10 | 0.00 | 0.00 | 0.00 | 0.389620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165767E+11 | 0.00 | 0.00 | 0.00 | 0.553586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.125168E+10 | 0.00 | 0.00 | 0.00 | 0.389183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147942E+10 | 0.00 | 0.00 | 0.00 | 0.552809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.338256E+10 | 0.00 | 0.00 | 0.00 | 0.121204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.323503E+10 | 0.00 | 0.00 | 0.00 | 0.129510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.389101E+10 | 0.00 | 0.00 | 0.00 | 0.170418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.387553E+10 | 0.00 | 0.00 | 0.00 | 0.186215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.403346E+10 | 0.00 | 0.00 | 0.00 | 0.200486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.405058E+10 | 0.00 | 0.00 | 0.00 | 0.205865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.368010E+10 | 0.00 | 0.00 | 0.00 | 0.149894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.383787E+10 | 0.00 | 0.00 | 0.00 | 0.166729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.365673E+10 | 0.00 | 0.00 | 0.00 | 0.156919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.352909E+10 | 0.00 | 0.00 | 0.00 | 0.136361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.332118E+10 | 0.00 | 0.00 | 0.00 | 0.124814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.335026E+10 | 0.00 | 0.00 | 0.00 | 0.114985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438434E+11 | 0.00 | 0.00 | 0.00 | 0.186340E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.323503E+10 | 0.00 | 0.00 | 0.00 | 0.114985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.405058E+10 | 0.00 | 0.00 | 0.00 | 0.205865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.237704E+10 | 0.00 | 1466273.72 | 0.00 | 0.00 | 752580.81 | 0.00 | 0.14 |
February | 0.00 | 0.236839E+10 | 0.00 | 260110.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
March | 0.00 | 0.307810E+10 | 0.00 | 211253.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
April | 0.00 | 0.358595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
May | 0.00 | 0.429166E+10 | 0.00 | 34123.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
June | 0.00 | 0.444380E+10 | 0.00 | 31869.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
July | 0.00 | 0.311022E+10 | 0.00 | 8804.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
August | 0.00 | 0.420345E+10 | 0.00 | 61455.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
September | 0.00 | 0.375029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.343732E+10 | 0.00 | 108029.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
November | 0.00 | 0.290604E+10 | 0.00 | 549680.21 | 0.00 | 0.00 | 8827.40 | 0.00 | 0.14 |
December | 0.00 | 0.250535E+10 | 0.00 | 1126040.60 | 0.00 | 0.00 | 158684.80 | 0.00 | 0.14 |
Annual Sum or Average | 0.00 | 0.400576E+11 | 0.00 | 3857641.27 | 0.00 | 0.00 | 920093.00 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.236839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.00 | 0.444380E+10 | 0.00 | 1466273.72 | 0.00 | 0.00 | 752580.81 | 0.00 | 0.16 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 12547445.15 | 0.778426E+10 | 0.00 | 1383087.78 | 0.00 | 0.00 | 0.102907E+09 | 0.00 | 0.22 |
February | 0.00 | 0.838239E+10 | 0.00 | 766035.96 | 380601.83 | 0.00 | 46131684.63 | 0.00 | 0.23 |
March | 0.00 | 0.105899E+11 | 0.00 | 243266.11 | 1727146.80 | 0.00 | 8021386.25 | 0.00 | 0.26 |
April | 0.00 | 0.137591E+11 | 0.00 | 0.00 | 1753729.09 | 0.00 | 0.00 | 0.00 | 0.26 |
May | 0.00 | 0.163332E+11 | 0.00 | 39513.60 | 2338335.78 | 0.00 | 34463.24 | 0.00 | 0.27 |
June | 0.00 | 0.172960E+11 | 0.00 | 33890.00 | 1913012.12 | 0.00 | 66646.86 | 0.00 | 0.28 |
July | 0.00 | 0.112036E+11 | 0.00 | 0.00 | 3018407.99 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.143170E+11 | 0.00 | 87622.44 | 1968116.47 | 0.00 | 2880803.76 | 0.00 | 0.25 |
September | 0.00 | 0.136628E+11 | 0.00 | 73098.74 | 3012095.90 | 0.00 | 258343.35 | 0.00 | 0.25 |
October | 0.00 | 0.116975E+11 | 0.00 | 89369.44 | 2036259.38 | 0.00 | 5033645.85 | 0.00 | 0.23 |
November | 88263.96 | 0.100592E+11 | 0.00 | 257357.15 | 0.00 | 0.00 | 16597199.24 | 0.00 | 0.23 |
December | 11958032.92 | 0.819167E+10 | 0.00 | 934078.07 | 0.00 | 0.00 | 69028272.18 | 0.00 | 0.22 |
Annual Sum or Average | 24593742.03 | 0.143276E+12 | 0.00 | 3907319.28 | 18147705.37 | 0.00 | 0.250959E+09 | 0.00 | 0.24 |
Minimum of Months | 0.00 | 0.778426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
Maximum of Months | 12547445.15 | 0.172960E+11 | 0.00 | 1383087.78 | 3018407.99 | 0.00 | 0.102907E+09 | 0.00 | 0.28 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |