Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2020-06-03 19:11:57
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 919.18 | 190.10 | 190.10 |
Net Site Energy | 919.18 | 190.10 | 190.10 |
Total Source Energy | 2906.15 | 601.05 | 601.05 |
Net Source Energy | 2906.15 | 601.05 | 601.05 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 113.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 99.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 65.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 23.38 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 916.83 | 2.35 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 2.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 113.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 99.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 13.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 51.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 23.38 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 118.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 41.83 | 0.49 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 189.62 | 0.49 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 118.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 41.83 | 0.49 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 189.62 | 0.49 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 916.832 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 916.832 | 100.00 |
Total On-Site and Utility Electric Sources | 916.832 | 100.00 |
Total Electricity End Uses | 916.832 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 2.50 |
Time Setpoint Not Met During Occupied Cooling | 52.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 411.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.6337 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.5069 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.5069 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-AUG-14:50 | 10-JAN-07:10 | - | - | - | 31-MAY-11:00 |
Heating | 0.00 | 27564.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 20363.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6322.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1679.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 73666.80 | 27564.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 27564.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 20363.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4016.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1679.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2.54 | 0.00 | 0.00 | 0.00 |
Cooling | 360.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1507.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 314.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 206.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 74.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2903.61 | 2.54 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.53 | 0.00 | 0.00 | 0.00 |
Cooling | 74.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 64.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 600.52 | 0.53 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.53 | 0.00 | 0.00 | 0.00 |
Cooling | 74.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 64.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 600.52 | 0.53 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.09 |
ZONE2 FINE STORAGE DIRECT AIR | 2.53 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 0.976839 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 0.976839 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 40534.27 |
PSZ-OFFICE HEATING COIL | 27155.25 |
PSZ-FINE STORAGE HEATING COIL | 80387.12 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 27496.91 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.00 | 1.00 | 1.09 |
PSZ-FINE STORAGE | 2.53 | 2.53 | 2.53 | 2.53 | 2.53 | 2.53 | 1.00 | 1.00 | 2.53 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.09 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 2.53 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.09 | 1.09 | 1.09 | 1.09 | 21824.88 | 27155.25 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.53 | 2.53 | 2.53 | 2.53 | 62824.24 | 80387.12 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.09 | 0.547245 | 1.09 | 21312.25 | 21824.88 | 10912.44 | 21824.88 | 0.736205 | 0.736210 | 0.736210 | 0.736210 |
PSZ-FINE STORAGE COOLING COIL | 2.53 | 1.26 | 2.53 | 62449.72 | 62824.24 | 31412.12 | 62824.24 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.09 | 1247.84 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.53 | 2769.02 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.634 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.707 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.507 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.507 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.507 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.066 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2518.900 | 10.634 | 503.780 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2518.900 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11853.648 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11853.648 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27263.390 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27263.390 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3263 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3263 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.5669 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.5669 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.5669 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.065 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.065 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.665 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.665 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.665 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.38866262E-07 | 0.77198350E-12 | 0.86409618E-13 | 0.0000000 |
2 | 1 | -5.2160226 | 0.42725752E-04 | -0.49098391E-04 | 0.74579932E-08 |
3 | 0 | 5.5423254 | 0.32626013 | 0.32635195 | |
4 | 2 | 0.38866262E-07 | 0.77198350E-12 | 0.86409618E-13 | 0.0000000 |
5 | 1 | -5.2160226 | 0.42725752E-04 | -0.49098391E-04 | 0.74579932E-08 |
6 | 0 | 5.5423254 | 0.32626013 | 0.32635195 | |
7 | 4 | 0.76473447E-12 | 0.16134122E-15 | -0.23523330E-14 | 0.11950429E-15 |
8 | 3 | -0.37912003E-03 | 0.39537906E-06 | -0.54939862E-04 | 0.14674673E-12 |
9 | 2 | 1.7262835 | 0.86963410E-02 | 1.1303724 | -0.72683208E-04 |
10 | 1 | -7.1462370 | 0.22614561 | -17.033763 | 0.33084980 |
11 | 0 | 5.7997145 | 0.14453958 | 16.282827 | |
12 | 4 | 0.76473447E-12 | 0.16134122E-15 | -0.23523330E-14 | 0.11950429E-15 |
13 | 3 | -0.37912003E-03 | 0.39537906E-06 | -0.54939862E-04 | 0.14674673E-12 |
14 | 2 | 1.7262835 | 0.86963410E-02 | 1.1303724 | -0.72683208E-04 |
15 | 1 | -7.1462370 | 0.22614561 | -17.033763 | 0.33084980 |
16 | 0 | 5.7997145 | 0.14453958 | 16.282827 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.23523330E-14 | 0.16134122E-15 | 0.76473447E-12 | 0.11950429E-15 |
85 | 3 | -0.54939862E-04 | 0.39537906E-06 | -0.37912003E-03 | 0.14674673E-12 |
86 | 2 | 1.1303724 | 0.86963410E-02 | 1.7262835 | -0.72683208E-04 |
87 | 1 | -17.033763 | 0.22614561 | -7.1462370 | 0.33084980 |
88 | 0 | 16.282827 | 0.14453958 | 5.7997145 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.73_SHGC_0.25 | 28 | 1 | VerySmooth | 4.149 | 0.255 | 0.127 | 0.250 |
2 | SKYLIGHT_U_0.75_SHGC_0.35 | 29 | 1 | VerySmooth | 4.262 | 0.355 | 0.203 | 0.351 |
3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 30 | 1 | VerySmooth | 4.262 | 0.355 | 0.203 | 0.351 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.12629 | 0.51106 | 0.51106 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 2.73817E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.20312 | 0.36283 | 0.36283 | 0.35000 | 0.14371 | 0.19477 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.20312 | 0.36283 | 0.36283 | 0.35000 | 0.14371 | 0.19477 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11077.11506 | 13292.53808 | 0.91207 | 1.09449 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65138E-002 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 7420.12584 | 8904.15100 | 0.20827 | 0.24992 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 4.60000 | 5.25715E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 32844.39657 | 39413.27589 | 2.10828 | 2.52993 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 33.90000 | 1.65138E-002 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 16779.75744 | 20135.70893 | 0.39710 | 0.47652 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90000 | 1.65138E-002 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 22914.09354 | 27496.91224 | 0.55221 | 0.97684 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 16845.41 | 1.09449 | 1.09449 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 7766.98 | 0.24992 | 0.24992 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 48654.80 | 2.52993 | 2.52993 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 19708.17 | 0.47652 | 0.47652 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.09449 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.52993 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97684 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 0.97684 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 40534.26505 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 27496.91224 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.09449 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.09449 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.09449 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.09449 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.09449 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.09449 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.52993 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.52993 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.52993 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.52993 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.52993 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.52993 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.09449 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.52993 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.09449 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.09449 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.09449 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.09449 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.09449 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.09449 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54725 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.09449 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21312.24670 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 21824.88000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10912.44000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 21824.88000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73621 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73621 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73621 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73621 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21824.88000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27155.25022 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.09449 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1247.83882 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 27155.25022 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.52993 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.52993 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.52993 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.52993 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.52993 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.52993 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.26497 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.52993 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 62449.72254 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 62824.24000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 31412.12000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 62824.24000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 62824.24000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 80387.12257 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.52993 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2769.02479 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 80387.12257 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 20975.0 | 10.37 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 60857.8 | 13.58 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 7 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.2678636723E-002 | 3.2761088297E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 9.5957587562E-002 | 0.1211035659 | Pass | Pass | 2.9954880428 | 31.7814083685 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 4.3266451286E-002 | 3.6386415257E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.523 | 0.567 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.523 | 0.567 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.523 | 0.567 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.523 | 0.567 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.523 | 0.567 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.523 | 0.567 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.523 | 0.567 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.312 | 0.326 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.523 | 0.567 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.523 | 0.567 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.523 | 0.567 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.312 | 0.326 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.73_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 4.149 | 0.255 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.73_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 4.149 | 0.255 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.73_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 4.149 | 0.255 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.73_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 4.149 | 0.255 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 4.201 | 0.301 | 0.296 | ||||||||||||
North Total or Average | 6.51 | 4.149 | 0.255 | 0.250 | ||||||||||||
Non-North Total or Average | 26.02 | 4.213 | 0.312 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.6337 | 236.88 | 2518.90 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.62 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.5069 | 1393.41 | 11853.65 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 135.00 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.5069 | 3204.84 | 27263.39 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 310.50 |
Interior Lighting Total | 8.6111 | 4835.13 | 41635.94 | 476.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 6311.00 | AstronomicalClock | - | 83.73 | 83.73 | 99.19 | |
Exterior Lighting Total | 6311.00 | 99.19 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21824.88 | 16067.69 | 5757.19 | 0.74 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 62824.24 | 42474.21 | 20350.03 | 0.68 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 20975.0 | 10.37 | ||||
PSZ-FINE STORAGE COOLING COIL | 60857.8 | 13.58 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 40534.27 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 27155.25 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 80387.12 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.98 | 90.76 | 92.91 | 1.00 | 4.17 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.09 | 1247.84 | 1140.11 | 1.00 | 1.34 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.53 | 2769.02 | 1094.51 | 1.00 | 1.25 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11077.12 | 13292.54 | 56.12 | 0.912 | 1.094 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23.90 | 23.90 | 0.00833 | 32.79 | 0.01651 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 32844.40 | 39413.28 | 28.29 | 2.108 | 2.530 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.70 | 26.70 | 0.00865 | 33.90 | 0.01651 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00378 | 33.90 | 0.01651 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7420.13 | 8904.15 | 37.59 | 0.208 | 0.250 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00774 | 4.60 | 0.00526 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 16779.76 | 20135.71 | 14.45 | 0.397 | 0.477 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.56 | 0.00670 | 4.60 | 0.00526 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 22914.09 | 27496.91 | 8.58 | 0.552 | 0.977 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00764 | 4.60 | 0.00526 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.09 | 1.09 | 0.25 | 0.25 | 1.0945 | 1.0945 | 1.0945 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.53 | 2.53 | 0.48 | 0.48 | 2.5299 | 2.5299 | 2.5299 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 40534.265 | 40534.265 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 40534.27 | 40534.27 | 0.976839 | 4.60 | 4.60 | 0.00525715 | 43.33 | 27.10 | 0.01600000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 10.00 | 0.00763665 | 99.9999 | 27496.91 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 21824.880 | 0.000 | 1.094490 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 21824.88 | 18280.27 | 1.094490 | 24.73 | 17.12 | 0.00909040 | 12.00 | 11.25 | 0.00800000 | 32.79 | 0.01651377 | 24.82 | 9.3454 | 23.90 | 0.00832514 | 45.0634 | 11077.12 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 27155.250 | 27155.250 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 27155.25 | 27155.25 | 1.094490 | 14.30 | 10.89 | 0.00672222 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 9.3454 | 21.10 | 0.00773723 | 49.6941 | 7420.13 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 62824.240 | 0.000 | 2.529930 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 62824.24 | 48858.27 | 2.529930 | 27.91 | 18.89 | 0.00996643 | 12.00 | 11.25 | 0.00800000 | 33.90 | 0.01651378 | 25.10 | 16.7875 | 26.70 | 0.00864555 | 39.6002 | 32163.66 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 80387.123 | 80387.123 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 80387.12 | 80387.12 | 2.529932 | 5.79 | 5.41 | 0.00541364 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 16.7875 | 15.56 | 0.00669661 | 60.9997 | 16779.76 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 40534.265 | 40534.265 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.2032 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.976839 | 1.17530051 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 40534.27 | 40534.27 | 1.0000 | 1.17530051 | 0.976839 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 43.33 | 27.10 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40534.27 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 10.00 | 0.00763665 | 10.00 | 0.00763665 | 99.9999 | 27496.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21824.880 | 0.000 | 1.094490 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.7386 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 21824.88 | 18280.27 | 1.0000 | 1.31685414 | 1.094490 | 24.73 | 17.12 | 0.00909040 | 48002.5 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21824.88 | 32.79 | 0.01651377 | 24.82 | 0.10228487 | 9.3454 | 23.90 | 0.00832514 | 23.90 | 0.00832514 | 45.0634 | 11077.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27155.250 | 27155.250 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.094490 | 1.31685408 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 27155.25 | 27155.25 | 1.0000 | 1.31685408 | 1.094490 | 14.30 | 10.89 | 0.00672222 | 31355.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27155.25 | 4.60 | 0.00525715 | 4.60 | 0.10228487 | 9.3454 | 21.01 | 0.00773723 | 21.10 | 0.00773723 | 49.6941 | 7420.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 62824.240 | 0.000 | 2.529930 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.3671 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 62824.24 | 48858.27 | 1.0000 | 3.04392803 | 2.529930 | 27.91 | 18.89 | 0.00996643 | 53484.5 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 62824.24 | 33.90 | 0.01651378 | 25.10 | 0.42471267 | 16.7875 | 26.70 | 0.00864555 | 26.70 | 0.00864555 | 39.6002 | 32163.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 80387.123 | 80387.123 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.529932 | 3.04393078 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 80387.12 | 80387.12 | 1.0000 | 3.04393078 | 2.529932 | 5.79 | 5.41 | 0.00541364 | 19416.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 80387.12 | 4.60 | 0.00525715 | 4.60 | 0.42471267 | 16.7875 | 15.56 | 0.00669661 | 15.56 | 0.00669661 | 60.9997 | 16779.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2583.67 | 1170.83 | 411.50 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2583.67 | 1170.83 | 411.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 2.50 | 55.67 | 2.50 | 52.50 |
ZONE2 FINE STORAGE | 0.33 | 165.83 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 2.83 | 221.50 | 2.50 | 52.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.349 | 0.369 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 916.83 | 5421.86 | 01-JAN-07:30 | 73666.80 | 03-AUG-14:50 |
Electricity:Building | 628.97 | 4938.86 | 01-JAN-00:10 | 47606.95 | 15-APR-12:40 |
Electricity:Zone:ZONE1 OFFICE | 62.57 | 1027.15 | 01-JAN-00:10 | 3852.05 | 02-JAN-08:10 |
InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.62 | 453.40 | 01-JAN-00:10 | 1939.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 431.40 | 2726.34 | 01-JAN-00:10 | 33679.30 | 14-APR-15:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 310.51 | 2726.34 | 01-JAN-00:10 | 23173.88 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 23.38 | 483.00 | 28-APR-05:10 | 1774.82 | 26-JAN-12:40 |
WaterSystems:Electricity | 23.38 | 483.00 | 28-APR-05:10 | 1774.82 | 26-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 23.38 | 483.00 | 28-APR-05:10 | 1774.82 | 26-JAN-12:40 |
Fans:Electricity | 65.08 | 0.00 | 01-JAN-00:10 | 6322.16 | 25-MAY-13:40 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 13.56 | 0.00 | 01-JAN-00:10 | 2305.29 | 07-MAY-14:30 |
Ventilation (simple):Fans:Electricity | 13.56 | 0.00 | 01-JAN-00:10 | 2305.29 | 07-MAY-14:30 |
ElectricityPurchased:Facility | 916.83 | 5421.86 | 01-JAN-07:30 | 73666.80 | 03-AUG-14:50 |
ElectricityPurchased:Plant | 916.83 | 5421.86 | 01-JAN-07:30 | 73666.80 | 03-AUG-14:50 |
Cogeneration:ElectricityPurchased | 916.83 | 5421.86 | 01-JAN-07:30 | 73666.80 | 03-AUG-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 916.83 | 5421.86 | 01-JAN-07:30 | 73666.80 | 03-AUG-14:50 |
ElectricityNet:Plant | 916.83 | 5421.86 | 01-JAN-07:30 | 73666.80 | 03-AUG-14:50 |
Cogeneration:ElectricityNet | 916.83 | 5421.86 | 01-JAN-07:30 | 73666.80 | 03-AUG-14:50 |
Electricity:HVAC | 165.29 | 0.00 | 01-JAN-00:10 | 26631.01 | 03-AUG-16:10 |
General:Fans:Electricity | 51.52 | 0.00 | 01-JAN-00:10 | 4016.86 | 04-JAN-17:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 113.77 | 0.00 | 01-JAN-00:10 | 22614.15 | 03-AUG-16:10 |
ExteriorLights:Electricity | 99.19 | 0.00 | 01-JAN-07:30 | 6311.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 99.19 | 0.00 | 01-JAN-07:30 | 6311.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 2.35 | 0.00 | 01-JAN-00:10 | 27564.89 | 10-JAN-07:10 |
Gas:HVAC | 2.35 | 0.00 | 01-JAN-00:10 | 27564.89 | 10-JAN-07:10 |
Heating:Gas | 2.35 | 0.00 | 01-JAN-00:10 | 27564.89 | 10-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 31-MAY-12:00 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 31-MAY-12:00 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 31-MAY-12:00 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 31-MAY-12:00 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 31-MAY-12:00 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 31-MAY-12:00 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 31-MAY-12:00 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 31-MAY-12:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 629.35 | 0.00 | 01-JAN-00:10 | 120026.56 | 03-AUG-16:10 |
EnergyTransfer:Building | 226.48 | 0.00 | 01-JAN-00:10 | 45474.60 | 03-AUG-16:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 68.98 | 0.00 | 01-JAN-00:10 | 13568.42 | 24-JUL-05:10 |
Heating:EnergyTransfer | 2.64 | 0.00 | 01-JAN-00:10 | 17985.25 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 1.52 | 0.00 | 01-JAN-00:10 | 11166.04 | 06-FEB-06:10 |
Cooling:EnergyTransfer | 223.84 | 0.00 | 01-JAN-00:10 | 45474.60 | 03-AUG-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 67.46 | 0.00 | 01-JAN-00:10 | 13568.42 | 24-JUL-05:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 157.49 | 0.00 | 01-JAN-00:10 | 34401.38 | 03-AUG-15:30 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 1.12 | 0.00 | 01-JAN-00:10 | 16151.77 | 05-FEB-07:30 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 156.38 | 0.00 | 01-JAN-00:10 | 34401.38 | 03-AUG-15:30 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 402.88 | 0.00 | 01-JAN-00:10 | 75128.52 | 03-JUL-16:30 |
HeatingCoils:EnergyTransfer | 1.60 | 0.00 | 01-JAN-00:10 | 19129.84 | 06-FEB-06:10 |
CoolingCoils:EnergyTransfer | 401.28 | 0.00 | 01-JAN-00:10 | 75128.52 | 03-JUL-16:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 1.521 | -67.460 | 0.000 | 0.000 | 3.616 | 30.619 | 31.946 | 10.960 | 0.000 | 3.877 | 0.002 | 0.000 | -6.859 | 0.000 | -7.437 | -0.782 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 1.116 | -156.366 | 0.000 | 0.000 | 0.000 | 135.003 | 0.000 | 0.000 | 0.000 | 7.633 | 61.333 | 0.000 | 0.000 | 0.000 | -48.719 | -0.004 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 310.507 | 107.336 | 27.146 | 0.000 | 8.538 | 16.002 | 0.000 | -9.072 | 0.000 | -460.457 | -0.015 |
Total Facility | 0.000 | 0.000 | 2.637 | -223.827 | 0.000 | 0.000 | 3.616 | 476.129 | 139.282 | 38.107 | 0.000 | 20.048 | 77.336 | 0.000 | -15.932 | 0.000 | -516.613 | -0.801 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 27-OCT-05:01 | 0.00 | 0.00 | 0.00 | -20357.05 | 0.00 | 0.00 | 33.47 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 20801.46 | 0.00 | -689.52 | 0.00 | -941.46 | 0.00 |
ZONE2 FINE STORAGE | 01-OCT-16:23 | 0.00 | 0.00 | 0.00 | -50934.07 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 199.04 | 49549.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-SEP-05:01 | 0.00 | 0.00 | 0.00 | -62024.76 | 0.00 | 0.00 | 26.65 | 4491.05 | 2623.78 | 0.00 | 0.00 | 0.00 | 55658.42 | 0.00 | -775.14 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 07-FEB-06:01 | 0.00 | 0.00 | 26078.45 | 0.00 | 0.00 | 0.00 | 52.22 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -623.02 | 0.00 | -924.12 | -25736.63 |
ZONE2 FINE STORAGE | 06-FEB-06:01 | 0.00 | 0.00 | 59459.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2987.46 | -57656.99 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-FEB-06:01 | 0.00 | 0.00 | 85179.49 | 0.00 | 0.00 | 0.00 | 54.07 | 4491.05 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1645.67 | 0.00 | -16603.44 | -74099.27 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0945 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.0945 | 0.0935 | 1.0000 | 0.1023 | 0.0935 | ||
PSZ-FINE STORAGE | 2.5299 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.5299 | 0.1679 | 1.0000 | 0.4247 | 0.1679 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0945 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.0945 | 1.0000 | 1.0000 | 0.1023 | 0.0935 | ||
PSZ-FINE STORAGE | 2.5299 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.5299 | 1.0000 | 1.0000 | 0.4247 | 0.1679 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0945 | 1.0945 | 1.0945 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.5299 | 2.5299 | 2.5299 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0945 | 1.0945 | 1.0945 | 1.0945 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.5299 | 2.5299 | 2.5299 | 2.5299 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0945 | 1.0945 | 1.0945 | 0.1023 | 0.4093 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.5299 | 2.5299 | 2.5299 | 0.4247 | 0.8913 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0945 | 1.0945 | 1.0945 | 1.0945 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.5299 | 2.5299 | 2.5299 | 2.5299 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 2.50 |
Number of hours cooling loads not met | 52.50 |
Number of hours not met | 55.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 2.35 | 27564.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 113.77 | 22614.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 476.13 | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 99.19 | 6311.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 13.56 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 51.52 | 4016.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 23.38 | 1774.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 916.83 |
Natural Gas | 0.00 | 2.35 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 919.18 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 98.47 |
Space Heating | 0.00 |
Space Cooling | 23.53 |
Fans (All) | 13.46 |
Service Water Heating | 4.84 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 189.62 |
Subtotal | 189.62 |
Natural Gas [MJ/m2] | |
Space Heating | 0.49 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.49 |
Subtotal | 0.49 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 51.80 |
Space Heating | 0.26 |
Space Cooling | 12.38 |
Fans (All) | 7.08 |
Service Water Heating | 2.54 |
Receptacle Equipment | 15.15 |
Miscellaneous | 10.79 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.888763E+09 |
February | 0.000 | 0.622468E+09 |
March | 0.000 | 0.341890E+09 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.242438E+08 |
December | 0.000 | 0.469743E+09 |
Annual Sum or Average | 0.234711E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.888763E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.888763E+09 |
February | 0.000 | 0.622468E+09 |
March | 0.000 | 0.341890E+09 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.242438E+08 |
December | 0.000 | 0.469743E+09 |
Annual Sum or Average | 0.234711E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.888763E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.888763E+09 |
February | 0.000 | 0.622468E+09 |
March | 0.000 | 0.341890E+09 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.242438E+08 |
December | 0.000 | 0.469743E+09 |
Annual Sum or Average | 0.234711E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.888763E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.888763E+09 |
February | 0.000 | 0.622468E+09 |
March | 0.000 | 0.341890E+09 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.242438E+08 |
December | 0.000 | 0.469743E+09 |
Annual Sum or Average | 0.234711E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.888763E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.888763E+09 |
February | 0.000 | 0.622468E+09 |
March | 0.000 | 0.341890E+09 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.242438E+08 |
December | 0.000 | 0.469743E+09 |
Annual Sum or Average | 0.234711E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.888763E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.888763E+09 |
February | 0.000 | 0.622468E+09 |
March | 0.000 | 0.341890E+09 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.242438E+08 |
December | 0.000 | 0.469743E+09 |
Annual Sum or Average | 0.234711E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.888763E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.888763E+09 |
February | 0.000 | 0.622468E+09 |
March | 0.000 | 0.341890E+09 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.242438E+08 |
December | 0.000 | 0.469743E+09 |
Annual Sum or Average | 0.234711E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.888763E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.888763E+09 |
February | 0.000 | 0.622468E+09 |
March | 0.000 | 0.341890E+09 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.242438E+08 |
December | 0.000 | 0.469743E+09 |
Annual Sum or Average | 0.234711E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.888763E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.888763E+09 |
February | 0.000 | 0.622468E+09 |
March | 0.000 | 0.341890E+09 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.242438E+08 |
December | 0.000 | 0.469743E+09 |
Annual Sum or Average | 0.234711E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.888763E+09 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129698E+10 | 16354.41 | 02-JAN-06:02 | 16.00 | 15.39 | 0.234796E+09 | 301.60 | 28-JAN-16:00 | 22.00 | 14.38 |
February | 0.188752E+10 | 16830.49 | 27-FEB-06:02 | 17.70 | 17.70 | 0.221218E+09 | 304.06 | 08-FEB-10:50 | 19.72 | 14.20 |
March | 0.276748E+10 | 15852.17 | 01-MAR-06:02 | 15.52 | 13.83 | 0.261304E+09 | 302.32 | 01-MAR-13:09 | 15.68 | 13.90 |
April | 0.507664E+10 | 20132.42 | 18-APR-05:02 | 17.10 | 15.03 | 0.248579E+09 | 301.61 | 21-APR-15:00 | 31.10 | 20.07 |
May | 0.813335E+10 | 17206.73 | 05-MAY-05:01 | 23.30 | 20.65 | 0.259061E+09 | 301.60 | 04-MAY-15:00 | 32.80 | 21.56 |
June | 0.864634E+10 | 17362.03 | 14-JUN-05:01 | 25.00 | 22.88 | 0.259075E+09 | 301.61 | 10-JUN-15:09 | 33.40 | 21.67 |
July | 0.854154E+10 | 15825.88 | 19-JUL-05:01 | 27.12 | 24.30 | 0.249133E+09 | 301.60 | 07-JUL-15:00 | 34.40 | 24.79 |
August | 0.933553E+10 | 18441.08 | 31-AUG-05:01 | 24.13 | 22.97 | 0.269060E+09 | 301.60 | 21-AUG-15:00 | 34.00 | 23.37 |
September | 0.803656E+10 | 16590.11 | 01-SEP-05:01 | 24.42 | 23.28 | 0.249119E+09 | 301.58 | 16-SEP-08:00 | 25.50 | 23.54 |
October | 0.726714E+10 | 20357.38 | 27-OCT-05:01 | 15.00 | 7.94 | 0.249042E+09 | 301.61 | 17-OCT-15:00 | 24.00 | 16.58 |
November | 0.398537E+10 | 17288.54 | 06-NOV-06:01 | 18.80 | 17.70 | 0.237801E+09 | 301.60 | 14-NOV-16:00 | 17.20 | 13.07 |
December | 0.248767E+10 | 14859.17 | 16-DEC-06:01 | 20.83 | 19.18 | 0.240317E+09 | 303.46 | 27-DEC-10:39 | 19.00 | 15.33 |
Annual Sum or Average | 0.674621E+11 | 0.297850E+10 | ||||||||
Minimum of Months | 0.129698E+10 | 14859.17 | 15.00 | 7.94 | 0.221218E+09 | 301.58 | 15.68 | 13.07 | ||
Maximum of Months | 0.933553E+10 | 20357.38 | 27.12 | 24.30 | 0.269060E+09 | 304.06 | 34.40 | 24.79 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146628E+10 | 21092.17 | 01-JAN-13:55 | 26.00 | 17.86 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.197477E+10 | 20897.23 | 26-FEB-13:40 | 26.43 | 19.29 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.265981E+10 | 24514.08 | 26-MAR-14:05 | 28.97 | 20.04 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.859920E+10 | 46479.06 | 23-APR-12:33 | 27.20 | 20.83 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.210948E+11 | 48905.21 | 03-MAY-17:42 | 31.20 | 21.90 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.248074E+11 | 49162.70 | 12-JUN-17:42 | 31.28 | 22.13 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.259854E+11 | 46410.65 | 12-JUL-17:08 | 23.90 | 22.65 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.259091E+11 | 46063.48 | 30-AUG-17:42 | 33.73 | 23.71 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.200485E+11 | 46467.96 | 22-SEP-17:06 | 30.32 | 21.05 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.166682E+11 | 50938.21 | 01-OCT-16:23 | 27.35 | 18.19 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.424883E+10 | 35851.20 | 02-NOV-17:10 | 27.35 | 23.65 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.291461E+10 | 20736.20 | 10-DEC-15:20 | 27.67 | 20.08 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.156377E+12 | 0.00 | ||||||||
Minimum of Months | 0.146628E+10 | 20736.20 | 23.90 | 17.86 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.259854E+11 | 50938.21 | 33.73 | 23.71 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 | 24.22 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 14.12 | 12.36 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 24.22 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.567776E+09 | 26009.71 | 11-JAN-06:01 | 8.00 |
February | 0.340274E+09 | 26078.43 | 07-FEB-06:01 | 8.62 |
March | 0.256418E+09 | 25858.17 | 13-MAR-05:01 | 6.68 |
April | 14386304.73 | 744.90 | 06-APR-06:10 | 17.88 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 4646847.00 | 679.46 | 31-OCT-06:10 | 18.00 |
November | 32355739.06 | 3754.45 | 15-NOV-07:20 | 7.90 |
December | 0.304913E+09 | 25503.24 | 22-DEC-06:02 | 10.00 |
Annual Sum or Average | 0.152077E+10 | |||
Minimum of Months | 0.00 | 0.00 | 6.68 | |
Maximum of Months | 0.567776E+09 | 26078.43 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.315620E+09 | 26743.62 | 10-JAN-06:40 | 3.00 |
February | 0.348254E+09 | 59459.16 | 06-FEB-06:01 | 2.88 |
March | 0.189300E+09 | 2127.65 | 14-MAR-15:10 | 24.12 |
April | 6981324.58 | 608.35 | 04-APR-09:50 | 23.43 |
May | 1994859.16 | 2096.68 | 30-MAY-06:05 | 25.18 |
June | 1974569.65 | 2139.39 | 27-JUN-06:05 | 25.10 |
July | 1152484.91 | 2392.05 | 06-JUL-06:07 | 25.68 |
August | 778886.22 | 955.03 | 16-AUG-06:10 | 23.92 |
September | 1066682.69 | 686.85 | 13-SEP-06:10 | 23.48 |
October | 8732568.60 | 780.14 | 21-OCT-06:10 | 23.95 |
November | 92403240.50 | 1736.86 | 24-NOV-16:10 | 23.43 |
December | 0.148150E+09 | 2282.45 | 23-DEC-17:20 | 21.33 |
Annual Sum or Average | 0.111641E+10 | |||
Minimum of Months | 778886.22 | 608.35 | 2.88 | |
Maximum of Months | 0.348254E+09 | 59459.16 | 25.68 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.256100E+10 | 1939.55 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.233575E+10 | 1939.55 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.266872E+10 | 1939.55 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.252182E+10 | 1939.55 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.261486E+10 | 1939.55 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.257569E+10 | 1939.55 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.256100E+10 | 1939.55 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.266872E+10 | 1939.55 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.252182E+10 | 1939.55 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.256100E+10 | 1939.55 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.246796E+10 | 1939.55 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.256100E+10 | 1939.55 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.306193E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.233575E+10 | 1939.55 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.266872E+10 | 1939.55 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112294E+11 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102778E+11 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.118738E+11 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.111270E+11 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.115516E+11 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.114492E+11 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112294E+11 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.118738E+11 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.111270E+11 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112294E+11 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108048E+11 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112294E+11 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135003E+12 | ||||
Minimum of Months | 0.102778E+11 | 10075.60 | 0.00 | 0.00 | |
Maximum of Months | 0.118738E+11 | 10075.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.258277E+11 | 23173.88 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.236390E+11 | 23173.88 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.273097E+11 | 23173.88 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.255921E+11 | 23173.88 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.265687E+11 | 23173.88 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.263332E+11 | 23173.88 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.258277E+11 | 23173.88 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.273097E+11 | 23173.88 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.255921E+11 | 23173.88 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.258277E+11 | 23173.88 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.248511E+11 | 23173.88 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.258277E+11 | 23173.88 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.236390E+11 | 23173.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.273097E+11 | 23173.88 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13465977.29 | 0.159337E+10 |
February | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22764075.01 | 0.107031E+10 |
March | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59247388.07 | 0.123342E+10 |
April | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182143E+09 | 0.505506E+09 |
May | 0.565842E+09 | 0.261486E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604653E+09 | 91168345.27 |
June | 0.565842E+09 | 0.257569E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708920E+09 | 72322084.83 |
July | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641082E+09 | 53888238.33 |
August | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716852E+09 | 0.104838E+09 |
September | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381548E+09 | 0.155509E+09 |
October | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401890E+09 | 0.420564E+09 |
November | 0.522316E+09 | 0.246796E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97987794.07 | 0.787782E+09 |
December | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46145312.86 | 0.134834E+10 |
Annual Sum or Average | 0.659424E+10 | 0.306193E+11 | 0.319458E+11 | 0.387670E+10 | 0.743702E+10 | ||||
Minimum of Months | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13465977.29 | 53888238.33 |
Maximum of Months | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716852E+09 | 0.159337E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12696509.78 | 0.822558E+10 |
February | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13935391.36 | 0.611637E+10 |
March | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28257221.30 | 0.756541E+10 |
April | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204856E+09 | 0.407315E+10 |
May | 0.00 | 0.115516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106533E+10 | 0.125561E+10 |
June | 0.00 | 0.114492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123260E+10 | 0.811048E+09 |
July | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148790E+10 | 0.494139E+09 |
August | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158433E+10 | 0.120080E+10 |
September | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103728E+10 | 0.185013E+10 |
October | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892511E+09 | 0.411704E+10 |
November | 0.00 | 0.108048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47571333.39 | 0.536242E+10 |
December | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25915425.90 | 0.764714E+10 |
Annual Sum or Average | 0.135003E+12 | 0.763318E+10 | 0.487188E+11 | ||||||
Minimum of Months | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12696509.78 | 0.494139E+09 |
Maximum of Months | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158433E+10 | 0.822558E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401258E+09 | 0.259885E+11 |
February | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365328E+09 | 0.184823E+11 |
March | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250940E+09 | 0.246976E+11 |
April | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6867984.91 | 0.163698E+11 |
May | 0.00 | 0.265687E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23491223.68 | 0.100107E+11 |
June | 0.00 | 0.263332E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11452989.25 | 0.653482E+10 |
July | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28480684.89 | 0.582169E+10 |
August | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65983361.83 | 0.950667E+10 |
September | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66082851.33 | 0.124470E+11 |
October | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8285338.18 | 0.215603E+11 |
November | 0.00 | 0.248511E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40033863.03 | 0.199799E+11 |
December | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168248E+09 | 0.269182E+11 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | 0.143645E+10 | 0.198317E+12 | |||||
Minimum of Months | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6867984.91 | 0.582169E+10 |
Maximum of Months | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401258E+09 | 0.269182E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1939.55 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 736.47 | 02-JAN-13:00 | 8344.88 | 05-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1939.55 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1617.72 | 02-FEB-13:00 | 7818.14 | 17-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1939.55 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1566.20 | 30-MAR-12:00 | 8473.35 | 09-MAR-07:05 |
April | 659.25 | 01-APR-07:10 | 1939.55 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3032.12 | 28-APR-16:10 | 5164.39 | 11-APR-06:03 |
May | 659.25 | 01-MAY-07:10 | 1939.55 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3331.92 | 10-MAY-16:10 | 678.37 | 02-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1939.55 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3438.89 | 28-JUN-16:10 | 975.61 | 07-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 1939.55 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4086.47 | 21-JUL-16:10 | 368.73 | 13-JUL-11:10 |
August | 659.25 | 01-AUG-07:10 | 1939.55 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4402.89 | 03-AUG-16:10 | 803.03 | 16-AUG-17:00 |
September | 659.25 | 01-SEP-07:10 | 1939.55 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3052.00 | 06-SEP-16:10 | 1571.86 | 07-SEP-16:52 |
October | 659.25 | 02-OCT-07:10 | 1939.55 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3256.67 | 05-OCT-17:00 | 3952.59 | 27-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1939.55 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1925.65 | 02-NOV-12:00 | 5537.82 | 15-NOV-07:03 |
December | 659.25 | 01-DEC-08:09 | 1939.55 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1472.80 | 13-DEC-13:00 | 8536.56 | 20-DEC-08:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 736.47 | 368.73 | |||||
Maximum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4402.89 | 8536.56 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 967.99 | 16-JAN-15:00 | 14667.45 | 03-JAN-09:00 |
February | 0.00 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1188.73 | 20-FEB-15:00 | 17728.53 | 16-FEB-18:00 |
March | 0.00 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1617.95 | 27-MAR-15:10 | 15388.37 | 09-MAR-09:00 |
April | 0.00 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4486.58 | 28-APR-15:10 | 11495.33 | 15-APR-17:00 |
May | 0.00 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4826.59 | 18-MAY-16:35 | 3608.43 | 05-MAY-06:10 |
June | 0.00 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6649.83 | 08-JUN-15:10 | 4462.54 | 06-JUN-20:00 |
July | 0.00 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6094.81 | 06-JUL-15:10 | 2310.91 | 12-JUL-15:10 |
August | 0.00 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7681.62 | 03-AUG-16:40 | 4748.06 | 25-AUG-24:00 |
September | 0.00 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7366.41 | 09-SEP-17:00 | 4669.73 | 19-SEP-19:00 |
October | 0.00 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6846.95 | 09-OCT-14:00 | 10459.14 | 27-OCT-08:00 |
November | 0.00 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1599.65 | 02-NOV-15:10 | 11146.78 | 09-NOV-07:03 |
December | 0.00 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 954.09 | 13-DEC-16:10 | 12698.62 | 04-DEC-07:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 954.09 | 2310.91 | |||
Maximum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7681.62 | 17728.53 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23173.88 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5659.91 | 16-JAN-15:00 | 47921.22 | 03-JAN-09:00 |
February | 0.00 | 23173.88 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9667.00 | 02-FEB-13:10 | 54888.60 | 04-FEB-11:00 |
March | 0.00 | 23173.88 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5376.63 | 26-MAR-13:55 | 53091.19 | 09-MAR-09:00 |
April | 0.00 | 23173.88 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1671.13 | 15-APR-12:00 | 33743.79 | 01-APR-16:00 |
May | 0.00 | 23173.88 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1829.79 | 27-MAY-13:53 | 24289.21 | 26-MAY-15:00 |
June | 0.00 | 23173.88 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 712.14 | 09-JUN-14:00 | 20230.27 | 01-JUN-13:00 |
July | 0.00 | 23173.88 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2403.83 | 02-JUL-10:53 | 25962.79 | 31-JUL-11:00 |
August | 0.00 | 23173.88 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1861.98 | 20-AUG-14:00 | 19181.11 | 25-AUG-24:00 |
September | 0.00 | 23173.88 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2160.80 | 09-SEP-17:00 | 20839.97 | 14-SEP-17:55 |
October | 0.00 | 23173.88 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1377.30 | 08-OCT-13:53 | 40750.61 | 27-OCT-11:00 |
November | 0.00 | 23173.88 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4122.25 | 28-NOV-13:10 | 37645.25 | 09-NOV-08:10 |
December | 0.00 | 23173.88 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3250.44 | 13-DEC-15:00 | 47664.53 | 19-DEC-12:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 712.14 | 19181.11 | ||||
Maximum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 9667.00 | 54888.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16354.41 | 02-JAN-06:02 | 435.11 | 3476.08 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 575.90 |
February | 16830.49 | 27-FEB-06:02 | 435.11 | 3476.08 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.54 |
March | 15852.17 | 01-MAR-06:02 | 362.59 | 2896.74 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 737.01 |
April | 20132.42 | 18-APR-05:02 | 435.11 | 3476.08 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.16 |
May | 17206.73 | 05-MAY-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.83 |
June | 17362.03 | 14-JUN-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.15 |
July | 15825.88 | 19-JUL-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.61 |
August | 18441.08 | 31-AUG-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.78 |
September | 16590.11 | 01-SEP-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.87 |
October | 20357.38 | 27-OCT-05:01 | 507.62 | 4055.43 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 941.46 |
November | 17288.54 | 06-NOV-06:01 | 652.66 | 5214.12 | 5163.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.65 |
December | 14859.17 | 16-DEC-06:01 | 580.14 | 4634.78 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.70 |
Annual Sum or Average | |||||||||||
Minimum of Months | 14859.17 | 362.59 | 2896.74 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.61 | |
Maximum of Months | 20357.38 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 941.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21092.17 | 01-JAN-13:55 | 0.00 | 2370.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.17 |
February | 20897.23 | 26-FEB-13:40 | 0.00 | 2370.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.55 |
March | 24514.08 | 26-MAR-14:05 | 0.00 | 2370.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1028.47 | 0.00 |
April | 46479.06 | 23-APR-12:33 | 0.00 | 3556.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.46 | 0.00 |
May | 48905.21 | 03-MAY-17:42 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 49162.70 | 12-JUN-17:42 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1173.29 | 0.00 |
July | 46410.65 | 12-JUL-17:08 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.44 |
August | 46063.48 | 30-AUG-17:42 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 675.45 | 0.00 |
September | 46467.96 | 22-SEP-17:06 | 0.00 | 5926.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1708.89 | 0.00 |
October | 50938.21 | 01-OCT-16:23 | 0.00 | 3556.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.04 | 0.00 |
November | 35851.20 | 02-NOV-17:10 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.16 | 0.00 |
December | 20736.20 | 10-DEC-15:20 | 0.00 | 2370.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.44 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 20736.20 | 0.00 | 2370.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50938.21 | 0.00 | 5926.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1708.89 | 159.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8202.14 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3592.75 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6516.53 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7144.00 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4763.09 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3046.69 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2775.39 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4699.03 |
September | 0.00 | 01-SEP-00:03 | 0.00 | 10905.36 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.40 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9687.26 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4523.67 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9598.12 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.40 | |
Maximum of Months | 0.00 | 0.00 | 10905.36 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9687.26 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.674691E+11 | 57605.55 | 19-JAN-15:09 | 0.888763E+09 | 27564.89 | 10-JAN-07:10 |
February | 0.621145E+11 | 59912.89 | 27-FEB-14:00 | 0.622468E+09 | 25686.90 | 06-FEB-07:10 |
March | 0.713879E+11 | 60737.74 | 30-MAR-12:00 | 0.341890E+09 | 14034.10 | 13-MAR-06:10 |
April | 0.710088E+11 | 69884.39 | 28-APR-14:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.839462E+11 | 70731.37 | 25-MAY-14:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.857277E+11 | 72492.78 | 28-JUN-14:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.867867E+11 | 73334.82 | 19-JUL-13:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.901825E+11 | 73666.80 | 03-AUG-14:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.817451E+11 | 71672.33 | 09-SEP-14:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.795873E+11 | 72445.15 | 07-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.678651E+11 | 67237.18 | 03-NOV-12:00 | 24243798.15 | 4228.52 | 15-NOV-07:00 |
December | 0.690108E+11 | 62803.40 | 15-DEC-13:50 | 0.469743E+09 | 27311.39 | 21-DEC-07:10 |
Annual Sum or Average | 0.916832E+12 | 0.234711E+10 | ||||
Minimum of Months | 0.621145E+11 | 57605.55 | 0.00 | 0.00 | ||
Maximum of Months | 0.901825E+11 | 73666.80 | 0.888763E+09 | 27564.89 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.396181E+11 | 0.952709E+10 | 0.115358E+11 | 0.00 | 0.398935E+10 | 0.00 | 0.00 | 0.738799E+09 | 0.00 | 0.00 | 0.00 | 0.205999E+10 | 0.00 |
February | 0.362526E+11 | 0.822828E+10 | 0.105871E+11 | 0.00 | 0.367327E+10 | 0.00 | 0.00 | 0.150781E+10 | 0.00 | 0.00 | 0.00 | 0.186544E+10 | 0.00 |
March | 0.418523E+11 | 0.854257E+10 | 0.123357E+11 | 0.00 | 0.430715E+10 | 0.00 | 0.00 | 0.227599E+10 | 0.00 | 0.00 | 0.00 | 0.207424E+10 | 0.00 |
April | 0.392410E+11 | 0.771709E+10 | 0.114862E+11 | 0.00 | 0.441556E+10 | 0.00 | 0.00 | 0.621249E+10 | 0.00 | 0.00 | 0.00 | 0.193643E+10 | 0.00 |
May | 0.407352E+11 | 0.747854E+10 | 0.119357E+11 | 0.00 | 0.665746E+10 | 0.00 | 0.00 | 0.151810E+11 | 0.00 | 0.00 | 0.00 | 0.195824E+10 | 0.00 |
June | 0.403581E+11 | 0.696734E+10 | 0.118862E+11 | 0.00 | 0.735833E+10 | 0.00 | 0.00 | 0.172827E+11 | 0.00 | 0.00 | 0.00 | 0.187511E+10 | 0.00 |
July | 0.396181E+11 | 0.734222E+10 | 0.115358E+11 | 0.00 | 0.755166E+10 | 0.00 | 0.00 | 0.188570E+11 | 0.00 | 0.00 | 0.00 | 0.188185E+10 | 0.00 |
August | 0.418523E+11 | 0.774360E+10 | 0.123357E+11 | 0.00 | 0.748469E+10 | 0.00 | 0.00 | 0.188384E+11 | 0.00 | 0.00 | 0.00 | 0.192784E+10 | 0.00 |
September | 0.392410E+11 | 0.803517E+10 | 0.114862E+11 | 0.00 | 0.616072E+10 | 0.00 | 0.00 | 0.149514E+11 | 0.00 | 0.00 | 0.00 | 0.187068E+10 | 0.00 |
October | 0.396181E+11 | 0.887958E+10 | 0.115358E+11 | 0.00 | 0.555887E+10 | 0.00 | 0.00 | 0.120375E+11 | 0.00 | 0.00 | 0.00 | 0.195752E+10 | 0.00 |
November | 0.381239E+11 | 0.907269E+10 | 0.110862E+11 | 0.00 | 0.393435E+10 | 0.00 | 0.00 | 0.371342E+10 | 0.00 | 0.00 | 0.00 | 0.193452E+10 | 0.00 |
December | 0.396181E+11 | 0.965204E+10 | 0.115358E+11 | 0.00 | 0.398841E+10 | 0.00 | 0.00 | 0.217603E+10 | 0.00 | 0.00 | 0.00 | 0.204037E+10 | 0.00 |
Annual Sum or Average | 0.476129E+12 | 0.991862E+11 | 0.139282E+12 | 0.650798E+11 | 0.00 | 0.113773E+12 | 0.233822E+11 | ||||||
Minimum of Months | 0.362526E+11 | 0.696734E+10 | 0.105871E+11 | 0.00 | 0.367327E+10 | 0.00 | 0.00 | 0.738799E+09 | 0.00 | 0.00 | 0.00 | 0.186544E+10 | 0.00 |
Maximum of Months | 0.418523E+11 | 0.965204E+10 | 0.123357E+11 | 0.00 | 0.755166E+10 | 0.00 | 0.00 | 0.188570E+11 | 0.00 | 0.00 | 0.00 | 0.207424E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.888763E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.622468E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.341890E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 24243798.15 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.469743E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234711E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.888763E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35189.04 | 02-JAN-09:09 | 6311.00 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4016.86 | 04-JAN-17:19 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35189.04 | 01-FEB-09:09 | 6311.00 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 4016.86 | 02-FEB-11:39 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35189.04 | 01-MAR-09:09 | 6311.00 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4016.86 | 04-MAR-12:39 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35189.04 | 01-APR-08:09 | 6311.00 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 6322.16 | 19-APR-14:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35189.04 | 01-MAY-08:09 | 6311.00 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 6322.16 | 25-MAY-13:39 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35189.04 | 01-JUN-08:09 | 6311.00 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 6322.16 | 03-JUN-15:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35189.04 | 01-JUL-08:09 | 6311.00 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6322.16 | 24-JUL-11:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35189.04 | 01-AUG-08:09 | 6311.00 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6322.16 | 10-AUG-13:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35189.04 | 01-SEP-08:09 | 6311.00 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 6322.16 | 09-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35189.04 | 02-OCT-08:09 | 6311.00 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 6322.16 | 03-OCT-16:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35189.04 | 01-NOV-08:09 | 6311.00 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 6322.16 | 03-NOV-14:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35189.04 | 01-DEC-09:09 | 6311.00 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4016.86 | 02-DEC-15:39 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35189.04 | 6311.00 | 10112.62 | 0.00 | 4016.86 | 0.00 | 0.00 | |||||
Maximum of Months | 35189.04 | 6311.00 | 10112.62 | 0.00 | 6322.16 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 6551.42 | 19-JAN-14:00 | 0.00 | 0.00 | 0.00 | 1774.82 | 26-JAN-12:39 | 0.00 |
February | 8890.56 | 27-FEB-14:00 | 0.00 | 0.00 | 0.00 | 1774.08 | 01-FEB-12:00 | 0.00 |
March | 9961.20 | 30-MAR-11:00 | 0.00 | 0.00 | 0.00 | 1766.96 | 01-MAR-12:09 | 0.00 |
April | 17665.35 | 28-APR-15:50 | 0.00 | 0.00 | 0.00 | 1751.41 | 01-APR-11:50 | 0.00 |
May | 17967.02 | 25-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1733.08 | 01-MAY-11:50 | 0.00 |
June | 20173.62 | 28-JUN-15:30 | 0.00 | 0.00 | 0.00 | 1715.80 | 01-JUN-11:39 | 0.00 |
July | 20989.08 | 03-JUL-16:30 | 0.00 | 0.00 | 0.00 | 1705.04 | 01-JUL-11:39 | 0.00 |
August | 22614.15 | 03-AUG-16:10 | 0.00 | 0.00 | 0.00 | 1709.45 | 31-AUG-11:30 | 0.00 |
September | 21834.03 | 09-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1723.35 | 30-SEP-11:00 | 0.00 |
October | 20289.53 | 06-OCT-11:00 | 0.00 | 0.00 | 0.00 | 1742.10 | 31-OCT-11:39 | 0.00 |
November | 13962.23 | 07-NOV-12:00 | 0.00 | 0.00 | 0.00 | 1759.47 | 30-NOV-12:20 | 0.00 |
December | 11771.12 | 15-DEC-13:00 | 0.00 | 0.00 | 0.00 | 1771.71 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6551.42 | 0.00 | 0.00 | 0.00 | 1705.04 | 0.00 | ||
Maximum of Months | 22614.15 | 0.00 | 0.00 | 0.00 | 1774.82 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 57605.55 | 19-JAN-15:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4016.86 | 0.00 | 0.00 | 6546.82 | 0.00 |
February | 59912.89 | 27-FEB-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4016.86 | 0.00 | 0.00 | 8890.56 | 0.00 |
March | 60737.74 | 30-MAR-12:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4016.86 | 0.00 | 0.00 | 9697.27 | 0.00 |
April | 69884.39 | 28-APR-14:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6322.16 | 0.00 | 0.00 | 16553.76 | 0.00 |
May | 70731.37 | 25-MAY-14:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6322.16 | 0.00 | 0.00 | 17413.51 | 0.00 |
June | 72492.78 | 28-JUN-14:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6322.16 | 0.00 | 0.00 | 19186.81 | 0.00 |
July | 73334.82 | 19-JUL-13:20 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6322.16 | 0.00 | 0.00 | 20053.47 | 0.00 |
August | 73666.80 | 03-AUG-14:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6322.16 | 0.00 | 0.00 | 20363.40 | 0.00 |
September | 71672.33 | 09-SEP-14:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6322.16 | 0.00 | 0.00 | 18360.17 | 0.00 |
October | 72445.15 | 07-OCT-12:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6322.16 | 0.00 | 0.00 | 19120.83 | 0.00 |
November | 67237.18 | 03-NOV-12:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6322.16 | 0.00 | 0.00 | 13898.44 | 0.00 |
December | 62803.40 | 15-DEC-13:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4016.86 | 0.00 | 0.00 | 11751.53 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 57605.55 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4016.86 | 0.00 | 0.00 | 6546.82 | 0.00 | |
Maximum of Months | 73666.80 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6322.16 | 0.00 | 0.00 | 20363.40 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 27564.89 | 10-JAN-07:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 25686.90 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 14034.10 | 13-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 4228.52 | 15-NOV-07:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 27311.39 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 27564.89 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 20.40 | 1.17 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.67 | 20.33 | 0.67 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.50 | 20.42 | 0.50 | 20.42 | 0.50 | 24.48 | 0.50 | 24.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.62 | 1.50 | 24.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 25.28 | 8.50 | 24.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 25.26 | 8.50 | 24.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 25.63 | 8.00 | 25.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 25.42 | 8.83 | 25.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 25.24 | 8.83 | 25.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 25.26 | 6.17 | 25.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.60 | 1.67 | 24.60 |
December | 0.17 | 20.30 | 0.17 | 20.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.50 | 20.38 | 2.50 | 20.38 | 55.67 | 25.30 | 52.50 | 25.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 20.42 | 1.17 | 20.42 | 9.33 | 25.63 | 8.83 | 25.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 0.00 |
February | 0.33 | 14.97 | 0.00 | 0.00 | 0.33 | 27.28 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.39 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 27.50 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 27.48 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 | 27.51 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 27.49 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 27.57 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 27.53 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.31 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 14.97 | 0.00 | 165.83 | 27.50 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 14.97 | 0.00 | 0.00 | 35.67 | 27.57 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 249.00 | 22.78 | 92.67 | 22.35 | 60.67 | 21.53 |
February | 173.50 | 22.96 | 98.67 | 23.05 | 35.83 | 21.57 |
March | 180.50 | 23.03 | 120.33 | 23.42 | 25.83 | 21.68 |
April | 39.50 | 23.63 | 218.00 | 23.91 | 8.17 | 24.05 |
May | 31.83 | 24.16 | 312.00 | 23.93 | 31.83 | 24.16 |
June | 31.67 | 24.17 | 312.00 | 23.93 | 31.67 | 24.17 |
July | 48.67 | 24.15 | 300.00 | 23.94 | 48.67 | 24.15 |
August | 51.83 | 24.15 | 324.00 | 23.94 | 51.83 | 24.15 |
September | 41.33 | 24.16 | 300.00 | 23.94 | 41.33 | 24.16 |
October | 34.33 | 24.07 | 266.83 | 23.93 | 26.17 | 24.16 |
November | 88.67 | 23.49 | 123.00 | 23.91 | 9.83 | 24.00 |
December | 200.00 | 23.00 | 116.17 | 23.30 | 39.67 | 22.13 |
Annual Sum or Average | 1170.83 | 23.25 | 2583.67 | 23.79 | 411.50 | 23.19 |
Minimum of Months | 31.67 | 22.78 | 92.67 | 22.35 | 8.17 | 21.53 |
Maximum of Months | 249.00 | 24.17 | 324.00 | 23.94 | 60.67 | 24.17 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.206047E+10 | 0.547931E+09 | 142.89 | 0.156474E+10 | 0.495727E+09 | 0.00 | 1.00 | 02-JAN-06:02 | 0.00 | 01-JAN-00:10 | 24340.66 | 02-JAN-06:02 | 17265.91 | 02-JAN-06:02 | 9455.26 | 20-JAN-06:03 | 5662.38 | 02-JAN-06:02 | 0.00 | 01-JAN-00:10 |
February | 0.316893E+10 | 0.840303E+09 | 171.31 | 0.237161E+10 | 0.797316E+09 | 0.00 | 1.00 | 03-FEB-06:03 | 0.00 | 01-FEB-00:10 | 25706.11 | 03-FEB-06:03 | 18019.61 | 27-FEB-06:02 | 11504.72 | 03-FEB-06:03 | 5889.42 | 03-FEB-06:03 | 0.00 | 01-FEB-00:10 |
March | 0.451488E+10 | 0.119950E+10 | 222.39 | 0.348616E+10 | 0.102872E+10 | 0.00 | 1.00 | 01-MAR-06:02 | 0.00 | 01-MAR-00:10 | 25850.23 | 07-MAR-06:02 | 17023.98 | 30-MAR-05:01 | 10931.64 | 07-MAR-06:02 | 5911.66 | 07-MAR-06:02 | 0.00 | 01-MAR-00:10 |
April | 0.813170E+10 | 0.217840E+10 | 274.01 | 0.634121E+10 | 0.179049E+10 | 0.00 | 1.00 | 01-APR-05:02 | 0.00 | 01-APR-00:10 | 26645.37 | 29-APR-05:01 | 21509.98 | 18-APR-05:02 | 10902.06 | 29-APR-05:06 | 6028.47 | 29-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.143089E+11 | 0.387582E+10 | 313.02 | 0.102322E+11 | 0.407671E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 28272.14 | 23-MAY-05:01 | 18454.73 | 05-MAY-05:01 | 14312.52 | 23-MAY-05:04 | 6273.43 | 24-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.152219E+11 | 0.415696E+10 | 313.12 | 0.108823E+11 | 0.433961E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 27980.74 | 05-JUN-05:01 | 18761.24 | 14-JUN-05:01 | 12891.71 | 05-JUN-05:06 | 6202.36 | 05-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.156818E+11 | 0.423649E+10 | 304.39 | 0.107071E+11 | 0.497471E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 28359.79 | 31-JUL-05:01 | 17392.26 | 19-JUL-05:01 | 14541.03 | 03-JUL-05:05 | 6309.37 | 03-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.168841E+11 | 0.453286E+10 | 325.52 | 0.116150E+11 | 0.526917E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 28400.20 | 11-AUG-05:01 | 19777.30 | 31-AUG-05:01 | 14199.84 | 11-AUG-05:04 | 6309.37 | 14-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.144892E+11 | 0.381738E+10 | 308.09 | 0.991117E+10 | 0.457807E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:03 | 28483.75 | 05-SEP-05:01 | 17886.47 | 01-SEP-05:01 | 15109.28 | 05-SEP-05:05 | 6281.60 | 18-SEP-05:01 | 0.00 | 01-SEP-00:03 |
October | 0.122939E+11 | 0.327409E+10 | 296.84 | 0.891303E+10 | 0.338086E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 28304.51 | 23-OCT-05:01 | 21271.68 | 27-OCT-05:01 | 14233.61 | 25-OCT-05:05 | 6321.15 | 25-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.637772E+10 | 0.168868E+10 | 248.89 | 0.494000E+10 | 0.143772E+10 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 26879.66 | 02-NOV-05:01 | 18128.86 | 06-NOV-06:01 | 12408.62 | 08-NOV-06:04 | 6061.00 | 02-NOV-05:01 | 0.00 | 01-NOV-00:10 |
December | 0.402640E+10 | 0.106715E+10 | 187.15 | 0.304132E+10 | 0.985086E+09 | 0.00 | 1.00 | 11-DEC-06:02 | 0.00 | 01-DEC-00:10 | 26218.86 | 15-DEC-06:01 | 15952.43 | 16-DEC-06:01 | 10998.79 | 15-DEC-06:04 | 5967.05 | 15-DEC-06:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.117160E+12 | 0.314156E+11 | 3107.61 | 0.840058E+11 | 0.331542E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.206047E+10 | 0.547931E+09 | 142.89 | 0.156474E+10 | 0.495727E+09 | 0.00 | 1.00 | 0.00 | 24340.66 | 15952.43 | 9455.26 | 5662.38 | 0.00 | |||||||
Maximum of Months | 0.168841E+11 | 0.453286E+10 | 325.52 | 0.116150E+11 | 0.526917E+10 | 0.00 | 1.00 | 0.00 | 28483.75 | 21509.98 | 15109.28 | 6321.15 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.662161E+09 | 0.190867E+09 | 23.08 | 0.439084E+09 | 0.223077E+09 | 0.00 | 0.51 | 01-JAN-13:55 | 0.00 | 01-JAN-00:10 | 28484.74 | 01-JAN-13:55 | 22743.43 | 01-JAN-13:55 | 6079.70 | 01-JAN-13:20 | 8515.63 | 01-JAN-13:55 | 0.00 | 01-JAN-00:10 |
February | 0.234090E+10 | 0.667509E+09 | 56.25 | 0.157179E+10 | 0.769105E+09 | 0.00 | 0.52 | 26-FEB-13:40 | 0.00 | 01-FEB-00:10 | 29905.16 | 26-FEB-13:40 | 23021.23 | 26-FEB-13:40 | 7360.28 | 26-FEB-15:40 | 8927.13 | 26-FEB-13:40 | 0.00 | 01-FEB-00:10 |
March | 0.376011E+10 | 0.107649E+10 | 91.14 | 0.248261E+10 | 0.127751E+10 | 0.00 | 0.62 | 26-MAR-14:05 | 0.00 | 01-MAR-00:10 | 36025.92 | 26-MAR-14:05 | 27500.34 | 26-MAR-14:05 | 9016.40 | 07-MAR-11:30 | 10875.11 | 26-MAR-14:05 | 0.00 | 01-MAR-00:10 |
April | 0.139316E+11 | 0.403409E+10 | 221.91 | 0.100952E+11 | 0.383635E+10 | 0.00 | 1.00 | 23-APR-11:53 | 0.00 | 01-APR-00:10 | 73385.58 | 29-APR-17:43 | 51806.48 | 27-APR-17:08 | 29137.26 | 29-APR-17:43 | 18752.93 | 28-APR-17:08 | 0.00 | 01-APR-00:10 |
May | 0.386168E+11 | 0.113052E+11 | 411.98 | 0.259686E+11 | 0.126482E+11 | 0.00 | 1.00 | 01-MAY-17:08 | 0.00 | 01-MAY-00:10 | 76478.35 | 24-MAY-17:10 | 54252.77 | 03-MAY-17:42 | 35196.91 | 24-MAY-17:10 | 19399.92 | 28-MAY-09:53 | 0.00 | 01-MAY-00:10 |
June | 0.446301E+11 | 0.131258E+11 | 450.40 | 0.303574E+11 | 0.142727E+11 | 0.00 | 1.00 | 01-JUN-17:08 | 0.00 | 01-JUN-00:10 | 74718.45 | 29-JUN-05:05 | 54738.46 | 12-JUN-17:06 | 31218.43 | 15-JUN-05:01 | 19298.47 | 28-JUN-17:45 | 0.00 | 01-JUN-00:10 |
July | 0.502648E+11 | 0.146206E+11 | 493.28 | 0.316575E+11 | 0.186073E+11 | 0.00 | 1.00 | 01-JUL-17:08 | 0.00 | 01-JUL-00:10 | 79960.68 | 06-JUL-05:01 | 49045.29 | 12-JUL-17:43 | 42904.78 | 06-JUL-05:01 | 19668.74 | 02-JUL-10:53 | 0.00 | 01-JUL-00:10 |
August | 0.493580E+11 | 0.143056E+11 | 480.30 | 0.315309E+11 | 0.178272E+11 | 0.00 | 1.00 | 01-AUG-17:06 | 0.00 | 01-AUG-00:10 | 78158.81 | 05-AUG-05:06 | 52441.05 | 30-AUG-17:06 | 38905.08 | 05-AUG-05:06 | 19701.02 | 20-AUG-14:13 | 0.00 | 01-AUG-00:10 |
September | 0.389882E+11 | 0.111340E+11 | 401.55 | 0.242013E+11 | 0.147869E+11 | 0.00 | 1.00 | 01-SEP-17:08 | 0.00 | 01-SEP-00:20 | 77645.87 | 04-SEP-10:23 | 51859.95 | 22-SEP-17:06 | 38169.58 | 04-SEP-10:23 | 20252.16 | 10-SEP-13:43 | 0.00 | 01-SEP-00:03 |
October | 0.305822E+11 | 0.876339E+10 | 329.05 | 0.198335E+11 | 0.107488E+11 | 0.00 | 1.00 | 01-OCT-12:23 | 0.00 | 01-OCT-00:10 | 80751.86 | 06-OCT-05:04 | 55481.43 | 01-OCT-16:23 | 46401.58 | 06-OCT-05:04 | 19898.90 | 08-OCT-13:53 | 0.00 | 01-OCT-00:10 |
November | 0.709635E+10 | 0.202474E+10 | 135.46 | 0.475115E+10 | 0.234520E+10 | 0.00 | 0.91 | 02-NOV-17:10 | 0.00 | 01-NOV-00:10 | 63173.34 | 02-NOV-17:10 | 39776.49 | 02-NOV-17:10 | 25611.12 | 03-NOV-17:10 | 16592.25 | 02-NOV-17:10 | 0.00 | 01-NOV-00:10 |
December | 0.388602E+10 | 0.110888E+10 | 75.17 | 0.253065E+10 | 0.135537E+10 | 0.00 | 0.55 | 10-DEC-15:20 | 0.00 | 01-DEC-00:10 | 31556.15 | 10-DEC-15:20 | 23275.03 | 10-DEC-15:20 | 10612.83 | 15-DEC-12:00 | 9492.21 | 10-DEC-15:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.284117E+12 | 0.823570E+11 | 3169.55 | 0.185420E+12 | 0.986976E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.662161E+09 | 0.190867E+09 | 23.08 | 0.439084E+09 | 0.223077E+09 | 0.00 | 0.51 | 0.00 | 28484.74 | 22743.43 | 6079.70 | 8515.63 | 0.00 | |||||||
Maximum of Months | 0.502648E+11 | 0.146206E+11 | 493.28 | 0.316575E+11 | 0.186073E+11 | 0.00 | 1.00 | 0.00 | 80751.86 | 55481.43 | 46401.58 | 20252.16 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 59.34 | 32.09 | 27.25 | 94.40 | 124.72 | 1.33 | 0.00 | 744.00 |
February | 67.08 | 33.92 | 33.16 | 111.12 | 107.42 | 0.00 | 0.00 | 672.00 |
March | 66.11 | 29.20 | 36.91 | 114.47 | 98.04 | 0.00 | 0.00 | 744.00 |
April | 81.85 | 37.45 | 44.40 | 160.35 | 72.22 | 0.00 | 0.00 | 720.00 |
May | 68.39 | 22.25 | 46.14 | 167.23 | 30.80 | 0.00 | 0.00 | 744.00 |
June | 76.02 | 26.70 | 49.33 | 191.43 | 28.69 | 0.00 | 0.00 | 720.00 |
July | 69.37 | 19.27 | 50.10 | 171.01 | 23.35 | 0.00 | 0.00 | 744.00 |
August | 70.03 | 21.32 | 48.70 | 174.78 | 29.67 | 0.00 | 0.00 | 744.00 |
September | 64.51 | 22.10 | 42.42 | 150.41 | 38.14 | 0.00 | 0.00 | 720.00 |
October | 65.91 | 28.38 | 37.53 | 147.55 | 56.03 | 0.00 | 0.00 | 744.00 |
November | 56.77 | 28.58 | 28.18 | 100.44 | 98.66 | 0.00 | 0.00 | 720.00 |
December | 54.67 | 29.15 | 25.52 | 90.36 | 116.16 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.63 | 27.47 | 39.16 | 139.57 | 68.44 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 54.67 | 19.27 | 25.52 | 90.36 | 23.35 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.85 | 37.45 | 50.10 | 191.43 | 124.72 | 1.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 59.34 | 32.09 | 27.25 | 94.40 | 124.72 | 1.33 | 0.00 | 744.00 |
February | 67.08 | 33.92 | 33.16 | 111.12 | 107.42 | 0.00 | 0.00 | 672.00 |
March | 66.11 | 29.20 | 36.91 | 114.47 | 98.04 | 0.00 | 0.00 | 744.00 |
April | 81.85 | 37.45 | 44.40 | 160.35 | 72.22 | 0.00 | 0.00 | 720.00 |
May | 68.39 | 22.25 | 46.14 | 167.23 | 30.80 | 0.00 | 0.00 | 744.00 |
June | 76.02 | 26.70 | 49.33 | 191.43 | 28.69 | 0.00 | 0.00 | 720.00 |
July | 69.37 | 19.27 | 50.10 | 171.01 | 23.35 | 0.00 | 0.00 | 744.00 |
August | 70.03 | 21.32 | 48.70 | 174.78 | 29.67 | 0.00 | 0.00 | 744.00 |
September | 64.51 | 22.10 | 42.42 | 150.41 | 38.14 | 0.00 | 0.00 | 720.00 |
October | 65.91 | 28.38 | 37.53 | 147.55 | 56.03 | 0.00 | 0.00 | 744.00 |
November | 56.77 | 28.58 | 28.18 | 100.44 | 98.66 | 0.00 | 0.00 | 720.00 |
December | 54.67 | 29.15 | 25.52 | 90.36 | 116.16 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.63 | 27.47 | 39.16 | 139.57 | 68.44 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 54.67 | 19.27 | 25.52 | 90.36 | 23.35 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.85 | 37.45 | 50.10 | 191.43 | 124.72 | 1.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.64 | 0.00 | 12.64 | 10.31 | 79.03 | 1.50 | 0.00 | 744.00 |
February | 14.91 | 0.00 | 14.91 | 13.98 | 67.04 | 0.00 | 0.00 | 672.00 |
March | 17.31 | 0.00 | 17.31 | 20.37 | 60.00 | 0.00 | 0.00 | 744.00 |
April | 20.52 | 0.17 | 20.35 | 31.31 | 43.66 | 0.00 | 0.00 | 720.00 |
May | 23.40 | 1.10 | 22.30 | 56.28 | 17.44 | 0.00 | 0.00 | 744.00 |
June | 26.66 | 2.18 | 24.48 | 67.34 | 16.28 | 0.00 | 0.00 | 720.00 |
July | 25.75 | 1.19 | 24.56 | 64.07 | 13.44 | 0.00 | 0.00 | 744.00 |
August | 23.02 | 0.31 | 22.71 | 58.89 | 17.03 | 0.00 | 0.00 | 744.00 |
September | 19.76 | 0.01 | 19.75 | 45.32 | 22.61 | 0.00 | 0.00 | 720.00 |
October | 17.16 | 0.00 | 17.16 | 35.54 | 33.90 | 0.00 | 0.00 | 744.00 |
November | 13.03 | 0.00 | 13.03 | 14.13 | 60.81 | 0.00 | 0.00 | 720.00 |
December | 11.75 | 0.00 | 11.75 | 10.26 | 73.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 18.84 | 0.41 | 18.43 | 35.78 | 41.89 | 1.50 | 0.00 | 8760.00 |
Minimum of Months | 11.75 | 0.00 | 11.75 | 10.26 | 13.44 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 26.66 | 2.18 | 24.56 | 67.34 | 79.03 | 1.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.64 | 0.00 | 12.64 | 10.31 | 79.03 | 1.50 | 0.00 | 744.00 |
February | 14.91 | 0.00 | 14.91 | 13.98 | 67.04 | 0.00 | 0.00 | 672.00 |
March | 17.31 | 0.00 | 17.30 | 20.37 | 60.00 | 0.00 | 0.00 | 744.00 |
April | 20.52 | 0.17 | 20.35 | 31.31 | 43.65 | 0.00 | 0.00 | 720.00 |
May | 23.40 | 1.10 | 22.30 | 56.28 | 17.44 | 0.00 | 0.00 | 744.00 |
June | 26.66 | 2.18 | 24.48 | 67.33 | 16.28 | 0.00 | 0.00 | 720.00 |
July | 25.75 | 1.19 | 24.56 | 64.07 | 13.44 | 0.00 | 0.00 | 744.00 |
August | 23.02 | 0.31 | 22.71 | 58.88 | 17.03 | 0.00 | 0.00 | 744.00 |
September | 19.76 | 0.01 | 19.75 | 45.32 | 22.61 | 0.00 | 0.00 | 720.00 |
October | 17.16 | 0.00 | 17.16 | 35.54 | 33.90 | 0.00 | 0.00 | 744.00 |
November | 13.03 | 0.00 | 13.03 | 14.13 | 60.80 | 0.00 | 0.00 | 720.00 |
December | 11.75 | 0.00 | 11.75 | 10.26 | 73.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 18.84 | 0.41 | 18.43 | 35.78 | 41.89 | 1.50 | 0.00 | 8760.00 |
Minimum of Months | 11.75 | 0.00 | 11.75 | 10.26 | 13.44 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 26.66 | 2.18 | 24.56 | 67.33 | 79.03 | 1.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.87 | 25.37 | 12.50 | 55.64 | 38.85 | 40.00 | 0.00 | 744.00 |
February | 47.96 | 32.94 | 15.02 | 73.68 | 34.36 | 72.50 | 0.00 | 672.00 |
March | 52.70 | 32.87 | 19.82 | 82.43 | 32.42 | 0.33 | 0.00 | 744.00 |
April | 66.94 | 43.58 | 23.36 | 107.02 | 31.33 | 0.00 | 0.00 | 720.00 |
May | 64.17 | 36.71 | 27.46 | 106.79 | 20.68 | 0.00 | 0.00 | 744.00 |
June | 70.84 | 40.98 | 29.86 | 120.22 | 20.30 | 0.00 | 0.00 | 720.00 |
July | 65.97 | 34.02 | 31.96 | 110.14 | 18.15 | 0.00 | 0.00 | 744.00 |
August | 61.62 | 30.95 | 30.67 | 103.40 | 20.11 | 5.50 | 0.00 | 744.00 |
September | 52.57 | 26.24 | 26.32 | 85.37 | 23.25 | 0.00 | 0.00 | 720.00 |
October | 49.95 | 29.70 | 20.25 | 80.43 | 28.09 | 1.33 | 0.00 | 744.00 |
November | 40.48 | 27.66 | 12.82 | 58.74 | 39.04 | 0.17 | 0.00 | 720.00 |
December | 34.35 | 22.68 | 11.67 | 48.80 | 39.07 | 9.83 | 0.00 | 744.00 |
Annual Sum or Average | 53.79 | 31.94 | 21.85 | 86.08 | 28.76 | 129.67 | 0.00 | 8760.00 |
Minimum of Months | 34.35 | 22.68 | 11.67 | 48.80 | 18.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 70.84 | 43.58 | 31.96 | 120.22 | 39.07 | 72.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.87 | 25.37 | 12.50 | 55.64 | 38.85 | 40.00 | 0.00 | 744.00 |
February | 47.96 | 32.94 | 15.02 | 73.68 | 34.36 | 72.50 | 0.00 | 672.00 |
March | 52.70 | 32.87 | 19.82 | 82.43 | 32.42 | 0.33 | 0.00 | 744.00 |
April | 66.94 | 43.58 | 23.36 | 107.02 | 31.33 | 0.00 | 0.00 | 720.00 |
May | 64.17 | 36.71 | 27.46 | 106.79 | 20.68 | 0.00 | 0.00 | 744.00 |
June | 70.84 | 40.98 | 29.86 | 120.22 | 20.30 | 0.00 | 0.00 | 720.00 |
July | 65.97 | 34.02 | 31.96 | 110.14 | 18.15 | 0.00 | 0.00 | 744.00 |
August | 61.62 | 30.95 | 30.67 | 103.40 | 20.11 | 5.50 | 0.00 | 744.00 |
September | 52.57 | 26.24 | 26.32 | 85.37 | 23.25 | 0.00 | 0.00 | 720.00 |
October | 49.95 | 29.70 | 20.25 | 80.43 | 28.09 | 1.33 | 0.00 | 744.00 |
November | 40.48 | 27.66 | 12.82 | 58.74 | 39.04 | 0.17 | 0.00 | 720.00 |
December | 34.35 | 22.68 | 11.67 | 48.80 | 39.07 | 9.83 | 0.00 | 744.00 |
Annual Sum or Average | 53.79 | 31.94 | 21.85 | 86.08 | 28.76 | 129.67 | 0.00 | 8760.00 |
Minimum of Months | 34.35 | 22.68 | 11.67 | 48.80 | 18.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 70.84 | 43.58 | 31.96 | 120.22 | 39.07 | 72.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.87 | 25.37 | 12.50 | 55.64 | 38.85 | 40.00 | 0.00 | 744.00 |
February | 47.96 | 32.94 | 15.02 | 73.68 | 34.36 | 72.50 | 0.00 | 672.00 |
March | 52.70 | 32.87 | 19.82 | 82.43 | 32.42 | 0.33 | 0.00 | 744.00 |
April | 66.94 | 43.58 | 23.36 | 107.02 | 31.33 | 0.00 | 0.00 | 720.00 |
May | 64.17 | 36.71 | 27.46 | 106.79 | 20.68 | 0.00 | 0.00 | 744.00 |
June | 70.84 | 40.98 | 29.86 | 120.22 | 20.30 | 0.00 | 0.00 | 720.00 |
July | 65.97 | 34.02 | 31.96 | 110.14 | 18.15 | 0.00 | 0.00 | 744.00 |
August | 61.62 | 30.95 | 30.67 | 103.40 | 20.11 | 5.50 | 0.00 | 744.00 |
September | 52.57 | 26.24 | 26.32 | 85.37 | 23.25 | 0.00 | 0.00 | 720.00 |
October | 49.95 | 29.70 | 20.25 | 80.43 | 28.09 | 1.33 | 0.00 | 744.00 |
November | 40.48 | 27.66 | 12.82 | 58.74 | 39.04 | 0.17 | 0.00 | 720.00 |
December | 34.35 | 22.68 | 11.67 | 48.80 | 39.07 | 9.83 | 0.00 | 744.00 |
Annual Sum or Average | 53.79 | 31.94 | 21.85 | 86.08 | 28.76 | 129.67 | 0.00 | 8760.00 |
Minimum of Months | 34.35 | 22.68 | 11.67 | 48.80 | 18.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 70.84 | 43.58 | 31.96 | 120.22 | 39.07 | 72.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.87 | 25.37 | 12.50 | 55.64 | 38.85 | 40.00 | 0.00 | 744.00 |
February | 47.96 | 32.94 | 15.02 | 73.68 | 34.36 | 72.50 | 0.00 | 672.00 |
March | 52.70 | 32.87 | 19.82 | 82.43 | 32.42 | 0.33 | 0.00 | 744.00 |
April | 66.94 | 43.58 | 23.36 | 107.02 | 31.33 | 0.00 | 0.00 | 720.00 |
May | 64.17 | 36.71 | 27.46 | 106.79 | 20.68 | 0.00 | 0.00 | 744.00 |
June | 70.84 | 40.98 | 29.86 | 120.22 | 20.30 | 0.00 | 0.00 | 720.00 |
July | 65.97 | 34.02 | 31.96 | 110.14 | 18.15 | 0.00 | 0.00 | 744.00 |
August | 61.62 | 30.95 | 30.67 | 103.40 | 20.11 | 5.50 | 0.00 | 744.00 |
September | 52.57 | 26.24 | 26.32 | 85.37 | 23.25 | 0.00 | 0.00 | 720.00 |
October | 49.95 | 29.70 | 20.25 | 80.43 | 28.09 | 1.33 | 0.00 | 744.00 |
November | 40.48 | 27.66 | 12.82 | 58.74 | 39.04 | 0.17 | 0.00 | 720.00 |
December | 34.35 | 22.68 | 11.67 | 48.80 | 39.07 | 9.83 | 0.00 | 744.00 |
Annual Sum or Average | 53.79 | 31.94 | 21.85 | 86.08 | 28.76 | 129.67 | 0.00 | 8760.00 |
Minimum of Months | 34.35 | 22.68 | 11.67 | 48.80 | 18.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 70.84 | 43.58 | 31.96 | 120.22 | 39.07 | 72.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.87 | 25.37 | 12.50 | 55.64 | 38.85 | 40.00 | 0.00 | 744.00 |
February | 47.96 | 32.94 | 15.02 | 73.68 | 34.36 | 72.50 | 0.00 | 672.00 |
March | 52.70 | 32.87 | 19.82 | 82.43 | 32.42 | 0.33 | 0.00 | 744.00 |
April | 66.94 | 43.58 | 23.36 | 107.02 | 31.33 | 0.00 | 0.00 | 720.00 |
May | 64.17 | 36.71 | 27.46 | 106.79 | 20.68 | 0.00 | 0.00 | 744.00 |
June | 70.84 | 40.98 | 29.86 | 120.22 | 20.30 | 0.00 | 0.00 | 720.00 |
July | 65.97 | 34.02 | 31.96 | 110.14 | 18.15 | 0.00 | 0.00 | 744.00 |
August | 61.62 | 30.95 | 30.67 | 103.40 | 20.11 | 5.50 | 0.00 | 744.00 |
September | 52.57 | 26.24 | 26.32 | 85.37 | 23.25 | 0.00 | 0.00 | 720.00 |
October | 49.95 | 29.70 | 20.25 | 80.43 | 28.09 | 1.33 | 0.00 | 744.00 |
November | 40.48 | 27.66 | 12.82 | 58.74 | 39.04 | 0.17 | 0.00 | 720.00 |
December | 34.35 | 22.68 | 11.67 | 48.80 | 39.07 | 9.83 | 0.00 | 744.00 |
Annual Sum or Average | 53.79 | 31.94 | 21.85 | 86.08 | 28.76 | 129.67 | 0.00 | 8760.00 |
Minimum of Months | 34.35 | 22.68 | 11.67 | 48.80 | 18.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 70.84 | 43.58 | 31.96 | 120.22 | 39.07 | 72.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.87 | 25.37 | 12.50 | 55.64 | 38.85 | 40.00 | 0.00 | 744.00 |
February | 47.96 | 32.94 | 15.02 | 73.68 | 34.36 | 72.50 | 0.00 | 672.00 |
March | 52.70 | 32.87 | 19.82 | 82.43 | 32.42 | 0.33 | 0.00 | 744.00 |
April | 66.94 | 43.58 | 23.36 | 107.02 | 31.33 | 0.00 | 0.00 | 720.00 |
May | 64.17 | 36.71 | 27.46 | 106.79 | 20.68 | 0.00 | 0.00 | 744.00 |
June | 70.84 | 40.98 | 29.86 | 120.22 | 20.30 | 0.00 | 0.00 | 720.00 |
July | 65.97 | 34.02 | 31.96 | 110.14 | 18.15 | 0.00 | 0.00 | 744.00 |
August | 61.62 | 30.95 | 30.67 | 103.40 | 20.11 | 5.50 | 0.00 | 744.00 |
September | 52.57 | 26.24 | 26.32 | 85.37 | 23.25 | 0.00 | 0.00 | 720.00 |
October | 49.95 | 29.70 | 20.25 | 80.43 | 28.09 | 1.33 | 0.00 | 744.00 |
November | 40.48 | 27.66 | 12.82 | 58.74 | 39.04 | 0.17 | 0.00 | 720.00 |
December | 34.35 | 22.68 | 11.67 | 48.80 | 39.07 | 9.83 | 0.00 | 744.00 |
Annual Sum or Average | 53.79 | 31.94 | 21.85 | 86.08 | 28.76 | 129.67 | 0.00 | 8760.00 |
Minimum of Months | 34.35 | 22.68 | 11.67 | 48.80 | 18.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 70.84 | 43.58 | 31.96 | 120.22 | 39.07 | 72.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.87 | 25.37 | 12.50 | 55.64 | 38.85 | 40.00 | 0.00 | 744.00 |
February | 47.96 | 32.94 | 15.02 | 73.68 | 34.36 | 72.50 | 0.00 | 672.00 |
March | 52.70 | 32.87 | 19.82 | 82.43 | 32.42 | 0.33 | 0.00 | 744.00 |
April | 66.94 | 43.58 | 23.36 | 107.02 | 31.33 | 0.00 | 0.00 | 720.00 |
May | 64.17 | 36.71 | 27.46 | 106.79 | 20.68 | 0.00 | 0.00 | 744.00 |
June | 70.84 | 40.98 | 29.86 | 120.22 | 20.30 | 0.00 | 0.00 | 720.00 |
July | 65.97 | 34.02 | 31.96 | 110.14 | 18.15 | 0.00 | 0.00 | 744.00 |
August | 61.62 | 30.95 | 30.67 | 103.40 | 20.11 | 5.50 | 0.00 | 744.00 |
September | 52.57 | 26.24 | 26.32 | 85.37 | 23.25 | 0.00 | 0.00 | 720.00 |
October | 49.95 | 29.70 | 20.25 | 80.43 | 28.09 | 1.33 | 0.00 | 744.00 |
November | 40.48 | 27.66 | 12.82 | 58.74 | 39.04 | 0.17 | 0.00 | 720.00 |
December | 34.35 | 22.68 | 11.67 | 48.80 | 39.07 | 9.83 | 0.00 | 744.00 |
Annual Sum or Average | 53.79 | 31.94 | 21.85 | 86.08 | 28.76 | 129.67 | 0.00 | 8760.00 |
Minimum of Months | 34.35 | 22.68 | 11.67 | 48.80 | 18.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 70.84 | 43.58 | 31.96 | 120.22 | 39.07 | 72.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.87 | 25.37 | 12.50 | 55.64 | 38.85 | 40.00 | 0.00 | 744.00 |
February | 47.96 | 32.94 | 15.02 | 73.68 | 34.36 | 72.50 | 0.00 | 672.00 |
March | 52.70 | 32.87 | 19.82 | 82.43 | 32.42 | 0.33 | 0.00 | 744.00 |
April | 66.94 | 43.58 | 23.36 | 107.02 | 31.33 | 0.00 | 0.00 | 720.00 |
May | 64.17 | 36.71 | 27.46 | 106.79 | 20.68 | 0.00 | 0.00 | 744.00 |
June | 70.84 | 40.98 | 29.86 | 120.22 | 20.30 | 0.00 | 0.00 | 720.00 |
July | 65.97 | 34.02 | 31.96 | 110.14 | 18.15 | 0.00 | 0.00 | 744.00 |
August | 61.62 | 30.95 | 30.67 | 103.40 | 20.11 | 5.50 | 0.00 | 744.00 |
September | 52.57 | 26.24 | 26.32 | 85.37 | 23.25 | 0.00 | 0.00 | 720.00 |
October | 49.95 | 29.70 | 20.25 | 80.43 | 28.09 | 1.33 | 0.00 | 744.00 |
November | 40.48 | 27.66 | 12.82 | 58.74 | 39.04 | 0.17 | 0.00 | 720.00 |
December | 34.35 | 22.68 | 11.67 | 48.80 | 39.07 | 9.83 | 0.00 | 744.00 |
Annual Sum or Average | 53.79 | 31.94 | 21.85 | 86.08 | 28.76 | 129.67 | 0.00 | 8760.00 |
Minimum of Months | 34.35 | 22.68 | 11.67 | 48.80 | 18.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 70.84 | 43.58 | 31.96 | 120.22 | 39.07 | 72.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.87 | 25.37 | 12.50 | 55.64 | 38.85 | 40.00 | 0.00 | 744.00 |
February | 47.96 | 32.94 | 15.02 | 73.68 | 34.36 | 72.50 | 0.00 | 672.00 |
March | 52.70 | 32.87 | 19.82 | 82.43 | 32.42 | 0.33 | 0.00 | 744.00 |
April | 66.94 | 43.58 | 23.36 | 107.02 | 31.33 | 0.00 | 0.00 | 720.00 |
May | 64.17 | 36.71 | 27.46 | 106.79 | 20.68 | 0.00 | 0.00 | 744.00 |
June | 70.84 | 40.98 | 29.86 | 120.22 | 20.30 | 0.00 | 0.00 | 720.00 |
July | 65.97 | 34.02 | 31.96 | 110.14 | 18.15 | 0.00 | 0.00 | 744.00 |
August | 61.62 | 30.95 | 30.67 | 103.40 | 20.11 | 5.50 | 0.00 | 744.00 |
September | 52.57 | 26.24 | 26.32 | 85.37 | 23.25 | 0.00 | 0.00 | 720.00 |
October | 49.95 | 29.70 | 20.25 | 80.43 | 28.09 | 1.33 | 0.00 | 744.00 |
November | 40.48 | 27.66 | 12.82 | 58.74 | 39.04 | 0.17 | 0.00 | 720.00 |
December | 34.35 | 22.68 | 11.67 | 48.80 | 39.07 | 9.83 | 0.00 | 744.00 |
Annual Sum or Average | 53.79 | 31.94 | 21.85 | 86.08 | 28.76 | 129.67 | 0.00 | 8760.00 |
Minimum of Months | 34.35 | 22.68 | 11.67 | 48.80 | 18.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 70.84 | 43.58 | 31.96 | 120.22 | 39.07 | 72.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.87 | 25.37 | 12.50 | 55.64 | 38.85 | 40.00 | 0.00 | 744.00 |
February | 47.96 | 32.94 | 15.02 | 73.68 | 34.36 | 72.50 | 0.00 | 672.00 |
March | 52.70 | 32.87 | 19.82 | 82.43 | 32.42 | 0.33 | 0.00 | 744.00 |
April | 66.94 | 43.58 | 23.36 | 107.02 | 31.33 | 0.00 | 0.00 | 720.00 |
May | 64.17 | 36.71 | 27.46 | 106.79 | 20.68 | 0.00 | 0.00 | 744.00 |
June | 70.84 | 40.98 | 29.86 | 120.22 | 20.30 | 0.00 | 0.00 | 720.00 |
July | 65.97 | 34.02 | 31.96 | 110.14 | 18.15 | 0.00 | 0.00 | 744.00 |
August | 61.62 | 30.95 | 30.67 | 103.40 | 20.11 | 5.50 | 0.00 | 744.00 |
September | 52.57 | 26.24 | 26.32 | 85.37 | 23.25 | 0.00 | 0.00 | 720.00 |
October | 49.95 | 29.70 | 20.25 | 80.43 | 28.09 | 1.33 | 0.00 | 744.00 |
November | 40.48 | 27.66 | 12.82 | 58.74 | 39.04 | 0.17 | 0.00 | 720.00 |
December | 34.35 | 22.68 | 11.67 | 48.80 | 39.07 | 9.83 | 0.00 | 744.00 |
Annual Sum or Average | 53.79 | 31.94 | 21.85 | 86.08 | 28.76 | 129.67 | 0.00 | 8760.00 |
Minimum of Months | 34.35 | 22.68 | 11.67 | 48.80 | 18.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 70.84 | 43.58 | 31.96 | 120.22 | 39.07 | 72.50 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158942E+09 | 85956566.93 | 72985498.66 | 0.252832E+09 | 0.334049E+09 |
February | 0.162283E+09 | 82058444.83 | 80224115.42 | 0.268825E+09 | 0.259868E+09 |
March | 0.177070E+09 | 78203010.93 | 98866754.38 | 0.306600E+09 | 0.262581E+09 |
April | 0.212156E+09 | 97063708.52 | 0.115092E+09 | 0.415634E+09 | 0.187205E+09 |
May | 0.183181E+09 | 59591310.41 | 0.123590E+09 | 0.447918E+09 | 82499375.00 |
June | 0.197048E+09 | 69196449.51 | 0.127852E+09 | 0.496184E+09 | 74355344.99 |
July | 0.185795E+09 | 51610424.16 | 0.134184E+09 | 0.458037E+09 | 62534821.84 |
August | 0.187557E+09 | 57111991.93 | 0.130445E+09 | 0.468124E+09 | 79476293.12 |
September | 0.167220E+09 | 57270784.81 | 0.109949E+09 | 0.389871E+09 | 98855986.24 |
October | 0.176532E+09 | 76024645.26 | 0.100507E+09 | 0.395191E+09 | 0.150082E+09 |
November | 0.147137E+09 | 74088443.52 | 73048996.70 | 0.260328E+09 | 0.255719E+09 |
December | 0.146426E+09 | 78083806.79 | 68341911.33 | 0.242026E+09 | 0.311121E+09 |
Annual Sum or Average | 0.210135E+10 | 0.866260E+09 | 0.123509E+10 | 0.440157E+10 | 0.215835E+10 |
Minimum of Months | 0.146426E+09 | 51610424.16 | 68341911.33 | 0.242026E+09 | 62534821.84 |
Maximum of Months | 0.212156E+09 | 97063708.52 | 0.134184E+09 | 0.496184E+09 | 0.334049E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158942E+09 | 85956566.93 | 72985498.66 | 0.252832E+09 | 0.334049E+09 |
February | 0.162283E+09 | 82058444.83 | 80224115.42 | 0.268825E+09 | 0.259868E+09 |
March | 0.177070E+09 | 78203010.93 | 98866754.38 | 0.306600E+09 | 0.262581E+09 |
April | 0.212156E+09 | 97063708.52 | 0.115092E+09 | 0.415634E+09 | 0.187205E+09 |
May | 0.183181E+09 | 59591310.41 | 0.123590E+09 | 0.447918E+09 | 82499375.00 |
June | 0.197048E+09 | 69196449.51 | 0.127852E+09 | 0.496184E+09 | 74355344.99 |
July | 0.185795E+09 | 51610424.16 | 0.134184E+09 | 0.458037E+09 | 62534821.84 |
August | 0.187557E+09 | 57111991.93 | 0.130445E+09 | 0.468124E+09 | 79476293.12 |
September | 0.167220E+09 | 57270784.81 | 0.109949E+09 | 0.389871E+09 | 98855986.24 |
October | 0.176532E+09 | 76024645.26 | 0.100507E+09 | 0.395191E+09 | 0.150082E+09 |
November | 0.147137E+09 | 74088443.52 | 73048996.70 | 0.260328E+09 | 0.255719E+09 |
December | 0.146426E+09 | 78083806.79 | 68341911.33 | 0.242026E+09 | 0.311121E+09 |
Annual Sum or Average | 0.210135E+10 | 0.866260E+09 | 0.123509E+10 | 0.440157E+10 | 0.215835E+10 |
Minimum of Months | 0.146426E+09 | 51610424.16 | 68341911.33 | 0.242026E+09 | 62534821.84 |
Maximum of Months | 0.212156E+09 | 97063708.52 | 0.134184E+09 | 0.496184E+09 | 0.334049E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33861408.58 | 0.00 | 33861408.58 | 27604744.35 | 0.211671E+09 |
February | 36082321.66 | 0.00 | 36082321.66 | 33814470.35 | 0.162192E+09 |
March | 46354484.78 | 3575.08 | 46350909.71 | 54547226.81 | 0.160709E+09 |
April | 53198617.36 | 441072.73 | 52757544.64 | 81159870.61 | 0.113154E+09 |
May | 62679542.69 | 2951194.12 | 59728348.57 | 0.150744E+09 | 46718201.23 |
June | 69097649.92 | 5642484.26 | 63455165.66 | 0.174533E+09 | 42203322.39 |
July | 68960463.16 | 3179366.13 | 65781097.03 | 0.171613E+09 | 35987111.39 |
August | 61645724.73 | 829306.48 | 60816418.25 | 0.157718E+09 | 45624095.10 |
September | 51209845.83 | 15623.79 | 51194222.04 | 0.117476E+09 | 58599942.75 |
October | 45957508.77 | 0.00 | 45957508.77 | 95189581.13 | 90810512.31 |
November | 33763655.28 | 0.00 | 33763655.28 | 36618746.55 | 0.157607E+09 |
December | 31478029.14 | 0.00 | 31478029.14 | 27479657.55 | 0.195916E+09 |
Annual Sum or Average | 0.594289E+09 | 13062622.59 | 0.581227E+09 | 0.112850E+10 | 0.132119E+10 |
Minimum of Months | 31478029.14 | 0.00 | 31478029.14 | 27479657.55 | 35987111.39 |
Maximum of Months | 69097649.92 | 5642484.26 | 65781097.03 | 0.174533E+09 | 0.211671E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33860475.71 | 0.00 | 33860475.71 | 27603816.80 | 0.211670E+09 |
February | 36081361.95 | 0.00 | 36081361.95 | 33813547.54 | 0.162191E+09 |
March | 46353172.74 | 3574.91 | 46349597.83 | 54545625.34 | 0.160709E+09 |
April | 53197174.13 | 441052.05 | 52756122.07 | 81157900.04 | 0.113153E+09 |
May | 62677642.39 | 2951055.80 | 59726586.59 | 0.150741E+09 | 46717437.06 |
June | 69095517.18 | 5642219.79 | 63453297.39 | 0.174529E+09 | 42202531.38 |
July | 68958301.19 | 3179217.11 | 65779084.08 | 0.171609E+09 | 35986317.15 |
August | 61643840.91 | 829267.61 | 60814573.31 | 0.157715E+09 | 45623324.68 |
September | 51208284.33 | 15623.05 | 51192661.28 | 0.117473E+09 | 58599133.53 |
October | 45956183.62 | 0.00 | 45956183.62 | 95187420.86 | 90809662.02 |
November | 33762741.30 | 0.00 | 33762741.30 | 36617769.58 | 0.157606E+09 |
December | 31477154.35 | 0.00 | 31477154.35 | 27478875.95 | 0.195915E+09 |
Annual Sum or Average | 0.594272E+09 | 13062010.32 | 0.581210E+09 | 0.112847E+10 | 0.132118E+10 |
Minimum of Months | 31477154.35 | 0.00 | 31477154.35 | 27478875.95 | 35986317.15 |
Maximum of Months | 69095517.18 | 5642219.79 | 65779084.08 | 0.174529E+09 | 0.211670E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101438E+09 | 67954766.92 | 33483049.68 | 0.149031E+09 | 0.104059E+09 |
February | 0.116027E+09 | 79678332.43 | 36348314.08 | 0.178254E+09 | 83114418.99 |
March | 0.141140E+09 | 88042130.48 | 53097998.20 | 0.220782E+09 | 86832151.77 |
April | 0.173504E+09 | 0.112950E+09 | 60553689.09 | 0.277405E+09 | 81201488.26 |
May | 0.171863E+09 | 98321771.46 | 73541282.67 | 0.286027E+09 | 55397483.25 |
June | 0.183624E+09 | 0.106219E+09 | 77405675.27 | 0.311620E+09 | 52622525.75 |
July | 0.176697E+09 | 91106075.26 | 85591017.63 | 0.294992E+09 | 48601108.55 |
August | 0.165046E+09 | 82909019.27 | 82136748.78 | 0.276941E+09 | 53855243.73 |
September | 0.136251E+09 | 68019128.59 | 68232142.84 | 0.221278E+09 | 60263777.66 |
October | 0.133785E+09 | 79559894.33 | 54225128.81 | 0.215425E+09 | 75235157.62 |
November | 0.104931E+09 | 71689753.60 | 33240855.91 | 0.152266E+09 | 0.101183E+09 |
December | 92003614.94 | 60759074.38 | 31244540.56 | 0.130697E+09 | 0.104653E+09 |
Annual Sum or Average | 0.169631E+10 | 0.100721E+10 | 0.689100E+09 | 0.271472E+10 | 0.907019E+09 |
Minimum of Months | 92003614.94 | 60759074.38 | 31244540.56 | 0.130697E+09 | 48601108.55 |
Maximum of Months | 0.183624E+09 | 0.112950E+09 | 85591017.63 | 0.311620E+09 | 0.104653E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101438E+09 | 67954766.92 | 33483049.68 | 0.149031E+09 | 0.104059E+09 |
February | 0.116027E+09 | 79678332.43 | 36348314.08 | 0.178254E+09 | 83114418.99 |
March | 0.141140E+09 | 88042130.48 | 53097998.20 | 0.220782E+09 | 86832151.77 |
April | 0.173504E+09 | 0.112950E+09 | 60553689.09 | 0.277405E+09 | 81201488.26 |
May | 0.171863E+09 | 98321771.46 | 73541282.67 | 0.286027E+09 | 55397483.25 |
June | 0.183624E+09 | 0.106219E+09 | 77405675.27 | 0.311620E+09 | 52622525.75 |
July | 0.176697E+09 | 91106075.26 | 85591017.63 | 0.294992E+09 | 48601108.55 |
August | 0.165046E+09 | 82909019.27 | 82136748.78 | 0.276941E+09 | 53855243.73 |
September | 0.136251E+09 | 68019128.59 | 68232142.84 | 0.221278E+09 | 60263777.66 |
October | 0.133785E+09 | 79559894.33 | 54225128.81 | 0.215425E+09 | 75235157.62 |
November | 0.104931E+09 | 71689753.60 | 33240855.91 | 0.152266E+09 | 0.101183E+09 |
December | 92003614.94 | 60759074.38 | 31244540.56 | 0.130697E+09 | 0.104653E+09 |
Annual Sum or Average | 0.169631E+10 | 0.100721E+10 | 0.689100E+09 | 0.271472E+10 | 0.907019E+09 |
Minimum of Months | 92003614.94 | 60759074.38 | 31244540.56 | 0.130697E+09 | 48601108.55 |
Maximum of Months | 0.183624E+09 | 0.112950E+09 | 85591017.63 | 0.311620E+09 | 0.104653E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101438E+09 | 67954766.92 | 33483049.68 | 0.149031E+09 | 0.104059E+09 |
February | 0.116027E+09 | 79678332.43 | 36348314.08 | 0.178254E+09 | 83114418.99 |
March | 0.141140E+09 | 88042130.48 | 53097998.20 | 0.220782E+09 | 86832151.77 |
April | 0.173504E+09 | 0.112950E+09 | 60553689.09 | 0.277405E+09 | 81201488.26 |
May | 0.171863E+09 | 98321771.46 | 73541282.67 | 0.286027E+09 | 55397483.25 |
June | 0.183624E+09 | 0.106219E+09 | 77405675.27 | 0.311620E+09 | 52622525.75 |
July | 0.176697E+09 | 91106075.26 | 85591017.63 | 0.294992E+09 | 48601108.55 |
August | 0.165046E+09 | 82909019.27 | 82136748.78 | 0.276941E+09 | 53855243.73 |
September | 0.136251E+09 | 68019128.59 | 68232142.84 | 0.221278E+09 | 60263777.66 |
October | 0.133785E+09 | 79559894.33 | 54225128.81 | 0.215425E+09 | 75235157.62 |
November | 0.104931E+09 | 71689753.60 | 33240855.91 | 0.152266E+09 | 0.101183E+09 |
December | 92003614.94 | 60759074.38 | 31244540.56 | 0.130697E+09 | 0.104653E+09 |
Annual Sum or Average | 0.169631E+10 | 0.100721E+10 | 0.689100E+09 | 0.271472E+10 | 0.907019E+09 |
Minimum of Months | 92003614.94 | 60759074.38 | 31244540.56 | 0.130697E+09 | 48601108.55 |
Maximum of Months | 0.183624E+09 | 0.112950E+09 | 85591017.63 | 0.311620E+09 | 0.104653E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101438E+09 | 67954766.92 | 33483049.68 | 0.149031E+09 | 0.104059E+09 |
February | 0.116027E+09 | 79678332.43 | 36348314.08 | 0.178254E+09 | 83114418.99 |
March | 0.141140E+09 | 88042130.48 | 53097998.20 | 0.220782E+09 | 86832151.77 |
April | 0.173504E+09 | 0.112950E+09 | 60553689.09 | 0.277405E+09 | 81201488.26 |
May | 0.171863E+09 | 98321771.46 | 73541282.67 | 0.286027E+09 | 55397483.25 |
June | 0.183624E+09 | 0.106219E+09 | 77405675.27 | 0.311620E+09 | 52622525.75 |
July | 0.176697E+09 | 91106075.26 | 85591017.63 | 0.294992E+09 | 48601108.55 |
August | 0.165046E+09 | 82909019.27 | 82136748.78 | 0.276941E+09 | 53855243.73 |
September | 0.136251E+09 | 68019128.59 | 68232142.84 | 0.221278E+09 | 60263777.66 |
October | 0.133785E+09 | 79559894.33 | 54225128.81 | 0.215425E+09 | 75235157.62 |
November | 0.104931E+09 | 71689753.60 | 33240855.91 | 0.152266E+09 | 0.101183E+09 |
December | 92003614.94 | 60759074.38 | 31244540.56 | 0.130697E+09 | 0.104653E+09 |
Annual Sum or Average | 0.169631E+10 | 0.100721E+10 | 0.689100E+09 | 0.271472E+10 | 0.907019E+09 |
Minimum of Months | 92003614.94 | 60759074.38 | 31244540.56 | 0.130697E+09 | 48601108.55 |
Maximum of Months | 0.183624E+09 | 0.112950E+09 | 85591017.63 | 0.311620E+09 | 0.104653E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101438E+09 | 67954766.92 | 33483049.68 | 0.149031E+09 | 0.104059E+09 |
February | 0.116027E+09 | 79678332.43 | 36348314.08 | 0.178254E+09 | 83114418.99 |
March | 0.141140E+09 | 88042130.48 | 53097998.20 | 0.220782E+09 | 86832151.77 |
April | 0.173504E+09 | 0.112950E+09 | 60553689.09 | 0.277405E+09 | 81201488.26 |
May | 0.171863E+09 | 98321771.46 | 73541282.67 | 0.286027E+09 | 55397483.25 |
June | 0.183624E+09 | 0.106219E+09 | 77405675.27 | 0.311620E+09 | 52622525.75 |
July | 0.176697E+09 | 91106075.26 | 85591017.63 | 0.294992E+09 | 48601108.55 |
August | 0.165046E+09 | 82909019.27 | 82136748.78 | 0.276941E+09 | 53855243.73 |
September | 0.136251E+09 | 68019128.59 | 68232142.84 | 0.221278E+09 | 60263777.66 |
October | 0.133785E+09 | 79559894.33 | 54225128.81 | 0.215425E+09 | 75235157.62 |
November | 0.104931E+09 | 71689753.60 | 33240855.91 | 0.152266E+09 | 0.101183E+09 |
December | 92003614.94 | 60759074.38 | 31244540.56 | 0.130697E+09 | 0.104653E+09 |
Annual Sum or Average | 0.169631E+10 | 0.100721E+10 | 0.689100E+09 | 0.271472E+10 | 0.907019E+09 |
Minimum of Months | 92003614.94 | 60759074.38 | 31244540.56 | 0.130697E+09 | 48601108.55 |
Maximum of Months | 0.183624E+09 | 0.112950E+09 | 85591017.63 | 0.311620E+09 | 0.104653E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101438E+09 | 67954766.92 | 33483049.68 | 0.149031E+09 | 0.104059E+09 |
February | 0.116027E+09 | 79678332.43 | 36348314.08 | 0.178254E+09 | 83114418.99 |
March | 0.141140E+09 | 88042130.48 | 53097998.20 | 0.220782E+09 | 86832151.77 |
April | 0.173504E+09 | 0.112950E+09 | 60553689.09 | 0.277405E+09 | 81201488.26 |
May | 0.171863E+09 | 98321771.46 | 73541282.67 | 0.286027E+09 | 55397483.25 |
June | 0.183624E+09 | 0.106219E+09 | 77405675.27 | 0.311620E+09 | 52622525.75 |
July | 0.176697E+09 | 91106075.26 | 85591017.63 | 0.294992E+09 | 48601108.55 |
August | 0.165046E+09 | 82909019.27 | 82136748.78 | 0.276941E+09 | 53855243.73 |
September | 0.136251E+09 | 68019128.59 | 68232142.84 | 0.221278E+09 | 60263777.66 |
October | 0.133785E+09 | 79559894.33 | 54225128.81 | 0.215425E+09 | 75235157.62 |
November | 0.104931E+09 | 71689753.60 | 33240855.91 | 0.152266E+09 | 0.101183E+09 |
December | 92003614.94 | 60759074.38 | 31244540.56 | 0.130697E+09 | 0.104653E+09 |
Annual Sum or Average | 0.169631E+10 | 0.100721E+10 | 0.689100E+09 | 0.271472E+10 | 0.907019E+09 |
Minimum of Months | 92003614.94 | 60759074.38 | 31244540.56 | 0.130697E+09 | 48601108.55 |
Maximum of Months | 0.183624E+09 | 0.112950E+09 | 85591017.63 | 0.311620E+09 | 0.104653E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101438E+09 | 67954766.92 | 33483049.68 | 0.149031E+09 | 0.104059E+09 |
February | 0.116027E+09 | 79678332.43 | 36348314.08 | 0.178254E+09 | 83114418.99 |
March | 0.141140E+09 | 88042130.48 | 53097998.20 | 0.220782E+09 | 86832151.77 |
April | 0.173504E+09 | 0.112950E+09 | 60553689.09 | 0.277405E+09 | 81201488.26 |
May | 0.171863E+09 | 98321771.46 | 73541282.67 | 0.286027E+09 | 55397483.25 |
June | 0.183624E+09 | 0.106219E+09 | 77405675.27 | 0.311620E+09 | 52622525.75 |
July | 0.176697E+09 | 91106075.26 | 85591017.63 | 0.294992E+09 | 48601108.55 |
August | 0.165046E+09 | 82909019.27 | 82136748.78 | 0.276941E+09 | 53855243.73 |
September | 0.136251E+09 | 68019128.59 | 68232142.84 | 0.221278E+09 | 60263777.66 |
October | 0.133785E+09 | 79559894.33 | 54225128.81 | 0.215425E+09 | 75235157.62 |
November | 0.104931E+09 | 71689753.60 | 33240855.91 | 0.152266E+09 | 0.101183E+09 |
December | 92003614.94 | 60759074.38 | 31244540.56 | 0.130697E+09 | 0.104653E+09 |
Annual Sum or Average | 0.169631E+10 | 0.100721E+10 | 0.689100E+09 | 0.271472E+10 | 0.907019E+09 |
Minimum of Months | 92003614.94 | 60759074.38 | 31244540.56 | 0.130697E+09 | 48601108.55 |
Maximum of Months | 0.183624E+09 | 0.112950E+09 | 85591017.63 | 0.311620E+09 | 0.104653E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101438E+09 | 67954766.92 | 33483049.68 | 0.149031E+09 | 0.104059E+09 |
February | 0.116027E+09 | 79678332.43 | 36348314.08 | 0.178254E+09 | 83114418.99 |
March | 0.141140E+09 | 88042130.48 | 53097998.20 | 0.220782E+09 | 86832151.77 |
April | 0.173504E+09 | 0.112950E+09 | 60553689.09 | 0.277405E+09 | 81201488.26 |
May | 0.171863E+09 | 98321771.46 | 73541282.67 | 0.286027E+09 | 55397483.25 |
June | 0.183624E+09 | 0.106219E+09 | 77405675.27 | 0.311620E+09 | 52622525.75 |
July | 0.176697E+09 | 91106075.26 | 85591017.63 | 0.294992E+09 | 48601108.55 |
August | 0.165046E+09 | 82909019.27 | 82136748.78 | 0.276941E+09 | 53855243.73 |
September | 0.136251E+09 | 68019128.59 | 68232142.84 | 0.221278E+09 | 60263777.66 |
October | 0.133785E+09 | 79559894.33 | 54225128.81 | 0.215425E+09 | 75235157.62 |
November | 0.104931E+09 | 71689753.60 | 33240855.91 | 0.152266E+09 | 0.101183E+09 |
December | 92003614.94 | 60759074.38 | 31244540.56 | 0.130697E+09 | 0.104653E+09 |
Annual Sum or Average | 0.169631E+10 | 0.100721E+10 | 0.689100E+09 | 0.271472E+10 | 0.907019E+09 |
Minimum of Months | 92003614.94 | 60759074.38 | 31244540.56 | 0.130697E+09 | 48601108.55 |
Maximum of Months | 0.183624E+09 | 0.112950E+09 | 85591017.63 | 0.311620E+09 | 0.104653E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101438E+09 | 67954766.92 | 33483049.68 | 0.149031E+09 | 0.104059E+09 |
February | 0.116027E+09 | 79678332.43 | 36348314.08 | 0.178254E+09 | 83114418.99 |
March | 0.141140E+09 | 88042130.48 | 53097998.20 | 0.220782E+09 | 86832151.77 |
April | 0.173504E+09 | 0.112950E+09 | 60553689.09 | 0.277405E+09 | 81201488.26 |
May | 0.171863E+09 | 98321771.46 | 73541282.67 | 0.286027E+09 | 55397483.25 |
June | 0.183624E+09 | 0.106219E+09 | 77405675.27 | 0.311620E+09 | 52622525.75 |
July | 0.176697E+09 | 91106075.26 | 85591017.63 | 0.294992E+09 | 48601108.55 |
August | 0.165046E+09 | 82909019.27 | 82136748.78 | 0.276941E+09 | 53855243.73 |
September | 0.136251E+09 | 68019128.59 | 68232142.84 | 0.221278E+09 | 60263777.66 |
October | 0.133785E+09 | 79559894.33 | 54225128.81 | 0.215425E+09 | 75235157.62 |
November | 0.104931E+09 | 71689753.60 | 33240855.91 | 0.152266E+09 | 0.101183E+09 |
December | 92003614.94 | 60759074.38 | 31244540.56 | 0.130697E+09 | 0.104653E+09 |
Annual Sum or Average | 0.169631E+10 | 0.100721E+10 | 0.689100E+09 | 0.271472E+10 | 0.907019E+09 |
Minimum of Months | 92003614.94 | 60759074.38 | 31244540.56 | 0.130697E+09 | 48601108.55 |
Maximum of Months | 0.183624E+09 | 0.112950E+09 | 85591017.63 | 0.311620E+09 | 0.104653E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101438E+09 | 67954766.92 | 33483049.68 | 0.149031E+09 | 0.104059E+09 |
February | 0.116027E+09 | 79678332.43 | 36348314.08 | 0.178254E+09 | 83114418.99 |
March | 0.141140E+09 | 88042130.48 | 53097998.20 | 0.220782E+09 | 86832151.77 |
April | 0.173504E+09 | 0.112950E+09 | 60553689.09 | 0.277405E+09 | 81201488.26 |
May | 0.171863E+09 | 98321771.46 | 73541282.67 | 0.286027E+09 | 55397483.25 |
June | 0.183624E+09 | 0.106219E+09 | 77405675.27 | 0.311620E+09 | 52622525.75 |
July | 0.176697E+09 | 91106075.26 | 85591017.63 | 0.294992E+09 | 48601108.55 |
August | 0.165046E+09 | 82909019.27 | 82136748.78 | 0.276941E+09 | 53855243.73 |
September | 0.136251E+09 | 68019128.59 | 68232142.84 | 0.221278E+09 | 60263777.66 |
October | 0.133785E+09 | 79559894.33 | 54225128.81 | 0.215425E+09 | 75235157.62 |
November | 0.104931E+09 | 71689753.60 | 33240855.91 | 0.152266E+09 | 0.101183E+09 |
December | 92003614.94 | 60759074.38 | 31244540.56 | 0.130697E+09 | 0.104653E+09 |
Annual Sum or Average | 0.169631E+10 | 0.100721E+10 | 0.689100E+09 | 0.271472E+10 | 0.907019E+09 |
Minimum of Months | 92003614.94 | 60759074.38 | 31244540.56 | 0.130697E+09 | 48601108.55 |
Maximum of Months | 0.183624E+09 | 0.112950E+09 | 85591017.63 | 0.311620E+09 | 0.104653E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 199.72 | 397.81 | 143.97 | 64.19 | 79.78 | 0.00 | 0.00 |
February | 243.12 | 341.85 | 163.99 | 67.84 | 96.15 | 0.00 | 0.00 |
March | 266.05 | 312.45 | 166.83 | 58.40 | 108.44 | 0.00 | 0.00 |
April | 380.69 | 229.12 | 204.75 | 75.24 | 129.51 | 0.00 | 0.00 |
May | 446.44 | 95.90 | 183.59 | 46.70 | 136.89 | 0.00 | 0.00 |
June | 516.81 | 89.22 | 205.36 | 57.75 | 147.61 | 0.00 | 0.00 |
July | 469.69 | 73.09 | 190.23 | 40.91 | 149.32 | 0.00 | 0.00 |
August | 467.05 | 93.14 | 186.08 | 43.27 | 142.82 | 0.00 | 0.00 |
September | 391.08 | 121.10 | 168.54 | 44.20 | 124.34 | 0.00 | 0.00 |
October | 365.07 | 178.78 | 166.14 | 56.77 | 109.37 | 0.00 | 0.00 |
November | 224.35 | 314.15 | 139.58 | 57.17 | 82.42 | 0.00 | 0.00 |
December | 194.41 | 371.78 | 132.84 | 58.31 | 74.54 | 0.00 | 0.00 |
Annual Sum or Average | 347.55 | 217.51 | 170.96 | 55.77 | 115.19 | 0.00 | 0.00 |
Minimum of Months | 194.41 | 73.09 | 132.84 | 40.91 | 74.54 | 0.00 | 0.00 |
Maximum of Months | 516.81 | 397.81 | 205.36 | 75.24 | 149.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 556.42 | 388.51 | 378.73 | 253.71 | 125.01 | 0.00 | 0.00 |
February | 736.83 | 343.56 | 479.61 | 329.36 | 150.25 | 0.00 | 0.00 |
March | 824.30 | 324.19 | 526.96 | 328.71 | 198.25 | 0.00 | 0.00 |
April | 1070.23 | 313.28 | 669.38 | 435.76 | 233.62 | 0.00 | 0.00 |
May | 1067.90 | 206.83 | 641.66 | 367.09 | 274.57 | 0.00 | 0.00 |
June | 1202.24 | 203.02 | 708.43 | 409.79 | 298.63 | 0.00 | 0.00 |
July | 1101.37 | 181.45 | 659.71 | 340.15 | 319.56 | 0.00 | 0.00 |
August | 1033.98 | 201.07 | 616.21 | 309.55 | 306.66 | 0.00 | 0.00 |
September | 853.69 | 232.50 | 525.66 | 262.42 | 263.24 | 0.00 | 0.00 |
October | 804.30 | 280.90 | 499.50 | 297.04 | 202.45 | 0.00 | 0.00 |
November | 587.44 | 390.37 | 404.82 | 276.58 | 128.24 | 0.00 | 0.00 |
December | 487.96 | 390.73 | 343.50 | 226.85 | 116.65 | 0.00 | 0.00 |
Annual Sum or Average | 860.83 | 287.61 | 537.90 | 319.38 | 218.51 | 0.00 | 0.00 |
Minimum of Months | 487.96 | 181.45 | 343.50 | 226.85 | 116.65 | 0.00 | 0.00 |
Maximum of Months | 1202.24 | 390.73 | 708.43 | 435.76 | 319.56 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.534935E+09 | 0.106550E+10 | 0.385606E+09 | 0.171913E+09 | 0.213693E+09 | 0.00 | 0.00 |
February | 0.588161E+09 | 0.827001E+09 | 0.396729E+09 | 0.164117E+09 | 0.232612E+09 | 0.00 | 0.00 |
March | 0.712583E+09 | 0.836871E+09 | 0.446847E+09 | 0.156413E+09 | 0.290434E+09 | 0.00 | 0.00 |
April | 0.986741E+09 | 0.593871E+09 | 0.530708E+09 | 0.195010E+09 | 0.335699E+09 | 0.00 | 0.00 |
May | 0.119575E+10 | 0.256859E+09 | 0.491720E+09 | 0.125085E+09 | 0.366635E+09 | 0.00 | 0.00 |
June | 0.133958E+10 | 0.231269E+09 | 0.532290E+09 | 0.149678E+09 | 0.382613E+09 | 0.00 | 0.00 |
July | 0.125803E+10 | 0.195773E+09 | 0.509508E+09 | 0.109579E+09 | 0.399929E+09 | 0.00 | 0.00 |
August | 0.125094E+10 | 0.249456E+09 | 0.498403E+09 | 0.115883E+09 | 0.382520E+09 | 0.00 | 0.00 |
September | 0.101368E+10 | 0.313904E+09 | 0.436859E+09 | 0.114573E+09 | 0.322286E+09 | 0.00 | 0.00 |
October | 0.977812E+09 | 0.478837E+09 | 0.444977E+09 | 0.152049E+09 | 0.292928E+09 | 0.00 | 0.00 |
November | 0.581525E+09 | 0.814283E+09 | 0.361801E+09 | 0.148177E+09 | 0.213624E+09 | 0.00 | 0.00 |
December | 0.520707E+09 | 0.995769E+09 | 0.355807E+09 | 0.156168E+09 | 0.199639E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109604E+11 | 0.685939E+10 | 0.539126E+10 | 0.175864E+10 | 0.363261E+10 | 0.00 | 0.00 |
Minimum of Months | 0.520707E+09 | 0.195773E+09 | 0.355807E+09 | 0.109579E+09 | 0.199639E+09 | 0.00 | 0.00 |
Maximum of Months | 0.133958E+10 | 0.106550E+10 | 0.532290E+09 | 0.195010E+09 | 0.399929E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.149031E+10 | 0.104059E+10 | 0.101438E+10 | 0.679548E+09 | 0.334830E+09 | 0.00 | 0.00 |
February | 0.178253E+10 | 0.831144E+09 | 0.116027E+10 | 0.796783E+09 | 0.363483E+09 | 0.00 | 0.00 |
March | 0.220782E+10 | 0.868322E+09 | 0.141140E+10 | 0.880421E+09 | 0.530980E+09 | 0.00 | 0.00 |
April | 0.277405E+10 | 0.812015E+09 | 0.173504E+10 | 0.112950E+10 | 0.605537E+09 | 0.00 | 0.00 |
May | 0.286027E+10 | 0.553975E+09 | 0.171863E+10 | 0.983218E+09 | 0.735413E+09 | 0.00 | 0.00 |
June | 0.311620E+10 | 0.526225E+09 | 0.183624E+10 | 0.106219E+10 | 0.774057E+09 | 0.00 | 0.00 |
July | 0.294992E+10 | 0.486009E+09 | 0.176697E+10 | 0.911061E+09 | 0.855910E+09 | 0.00 | 0.00 |
August | 0.276941E+10 | 0.538549E+09 | 0.165046E+10 | 0.829090E+09 | 0.821367E+09 | 0.00 | 0.00 |
September | 0.221278E+10 | 0.602634E+09 | 0.136251E+10 | 0.680191E+09 | 0.682321E+09 | 0.00 | 0.00 |
October | 0.215425E+10 | 0.752351E+09 | 0.133785E+10 | 0.795599E+09 | 0.542251E+09 | 0.00 | 0.00 |
November | 0.152264E+10 | 0.101183E+10 | 0.104931E+10 | 0.716898E+09 | 0.332409E+09 | 0.00 | 0.00 |
December | 0.130696E+10 | 0.104653E+10 | 0.920036E+09 | 0.607591E+09 | 0.312445E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.271471E+11 | 0.907018E+10 | 0.169631E+11 | 0.100721E+11 | 0.689100E+10 | 0.00 | 0.00 |
Minimum of Months | 0.130696E+10 | 0.486009E+09 | 0.920036E+09 | 0.607591E+09 | 0.312445E+09 | 0.00 | 0.00 |
Maximum of Months | 0.311620E+10 | 0.104653E+10 | 0.183624E+10 | 0.112950E+10 | 0.855910E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.01 | 8.64 | 3.24 | 3.12 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.57 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.53 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.81 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.36 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.89 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.01 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.46 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.87 | 10.53 | 3.17 | 6.00 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.01 | 8.64 | 2.44 | 3.12 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.65 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.77 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.86 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.04 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.75 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.93 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.95 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.72 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.63 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.03 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.82 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.65 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.63 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.2 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -1.8 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.94 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.57 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 17.99 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.55 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.11 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.8 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.2 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.10 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.48 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.76 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.54 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.83 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.16 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.78 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.48 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.10 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.54 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.08 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.78 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.766458E+09 | -688258271.8 | 0.00 | 0.00 | 744.00 | 0.00 | -78199829.1 | 58.99 | 0.00 | 0.00 |
February | 0.696848E+09 | -627190721.6 | 0.00 | 0.00 | 672.00 | 0.00 | -69657287.5 | 58.99 | 0.00 | 0.00 |
March | 0.780660E+09 | -705018840.7 | 0.00 | 0.00 | 744.00 | 0.00 | -75641529.9 | 58.99 | 0.00 | 0.00 |
April | 0.684441E+09 | -614747177.7 | 0.00 | 0.00 | 720.00 | 0.00 | -69693639.0 | 58.99 | 0.00 | 0.00 |
May | 0.664292E+09 | -594411379.1 | 0.00 | 0.00 | 744.00 | 0.00 | -69880979.9 | 58.99 | 0.00 | 0.00 |
June | 0.622842E+09 | -555347745.9 | 0.00 | 0.00 | 720.00 | 0.00 | -67494100.7 | 58.99 | 0.00 | 0.00 |
July | 0.588612E+09 | -519495833.5 | 0.00 | 0.00 | 744.00 | 0.00 | -69115698.7 | 58.99 | 0.00 | 0.00 |
August | 0.633587E+09 | -564061934.9 | 0.00 | 0.00 | 744.00 | 0.00 | -69525513.7 | 58.99 | 0.00 | 0.00 |
September | 0.618854E+09 | -551540742.5 | 0.00 | 0.00 | 720.00 | 0.00 | -67313148.3 | 58.99 | 0.00 | 0.00 |
October | 0.663694E+09 | -593486685.5 | 0.00 | 0.00 | 744.00 | 0.00 | -70207286.4 | 58.99 | 0.00 | 0.00 |
November | 0.682187E+09 | -611316224.7 | 0.00 | 0.00 | 720.00 | 0.00 | -70870739.3 | 58.99 | 0.00 | 0.00 |
December | 0.747141E+09 | -671023063.2 | 0.00 | 0.00 | 744.00 | 0.00 | -76117991.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.814962E+10 | -.729590E+10 | 8760.00 | -853717743.6 | 58.99 | |||||
Minimum of Months | 0.588612E+09 | -705018840.7 | 0.00 | 0.00 | 672.00 | 0.00 | -78199829.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.780660E+09 | -519495833.5 | 0.00 | 0.00 | 744.00 | 0.00 | -67313148.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 307.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 295.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 353.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 390.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 380.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 342.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 330.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 308.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4027.67 | ||||||||||
Minimum of Months | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.558070E+09 | 27155.25 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.307685E+09 | 27155.25 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.232435E+09 | 27155.25 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15852009.21 | 3993.96 | 15-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.306098E+09 | 27155.25 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142014E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.558070E+09 | 27155.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 49242985.77 | 28352.62 | 10-JAN-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116435E+09 | 63340.41 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12104611.02 | 6748.68 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177782E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116435E+09 | 63340.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.206047E+10 | 0.156474E+10 | 24340.66 | 02-JAN-06:02 | 17265.91 | 0.00 |
February | 0.00 | 0.00 | 0.316893E+10 | 0.237161E+10 | 25706.11 | 03-FEB-06:03 | 14201.39 | 0.00 |
March | 0.00 | 0.00 | 0.451488E+10 | 0.348616E+10 | 25850.23 | 07-MAR-06:02 | 14918.59 | 0.00 |
April | 0.00 | 0.00 | 0.813170E+10 | 0.634121E+10 | 26645.37 | 29-APR-05:01 | 16108.36 | 0.00 |
May | 0.00 | 0.00 | 0.143089E+11 | 0.102322E+11 | 28272.14 | 23-MAY-05:01 | 13973.76 | 0.00 |
June | 0.00 | 0.00 | 0.152219E+11 | 0.108823E+11 | 27980.74 | 05-JUN-05:01 | 15271.90 | 0.00 |
July | 0.00 | 0.00 | 0.156818E+11 | 0.107071E+11 | 28359.79 | 31-JUL-05:01 | 14108.51 | 0.00 |
August | 0.00 | 0.00 | 0.168841E+11 | 0.116150E+11 | 28400.20 | 11-AUG-05:01 | 14296.47 | 0.00 |
September | 0.00 | 0.00 | 0.144892E+11 | 0.991117E+10 | 28483.75 | 05-SEP-05:01 | 13716.08 | 0.00 |
October | 0.00 | 0.00 | 0.122939E+11 | 0.891303E+10 | 28304.51 | 23-OCT-05:01 | 14766.23 | 0.00 |
November | 0.00 | 0.00 | 0.637772E+10 | 0.494000E+10 | 26879.66 | 02-NOV-05:01 | 15419.48 | 0.00 |
December | 0.00 | 0.00 | 0.402640E+10 | 0.304132E+10 | 26218.86 | 15-DEC-06:01 | 15429.85 | 0.00 |
Annual Sum or Average | 0.117160E+12 | 0.840058E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.206047E+10 | 0.156474E+10 | 24340.66 | 13716.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.168841E+11 | 0.116150E+11 | 28483.75 | 17265.91 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.662161E+09 | 0.439084E+09 | 28484.74 | 01-JAN-13:55 | 22743.43 | 0.00 |
February | 0.00 | 0.00 | 0.234090E+10 | 0.157179E+10 | 29905.16 | 26-FEB-13:40 | 23021.23 | 0.00 |
March | 0.00 | 0.00 | 0.376011E+10 | 0.248261E+10 | 36025.92 | 26-MAR-14:05 | 27500.34 | 0.00 |
April | 0.00 | 0.00 | 0.139316E+11 | 0.100952E+11 | 73385.58 | 29-APR-17:43 | 44248.32 | 0.00 |
May | 0.00 | 0.00 | 0.386168E+11 | 0.259686E+11 | 76478.35 | 24-MAY-17:10 | 41281.44 | 0.00 |
June | 0.00 | 0.00 | 0.446301E+11 | 0.303574E+11 | 74718.45 | 29-JUN-05:05 | 43587.23 | 0.00 |
July | 0.00 | 0.00 | 0.502648E+11 | 0.316575E+11 | 79960.68 | 06-JUL-05:01 | 37055.91 | 0.00 |
August | 0.00 | 0.00 | 0.493580E+11 | 0.315309E+11 | 78158.81 | 05-AUG-05:06 | 39253.73 | 0.00 |
September | 0.00 | 0.00 | 0.389882E+11 | 0.242013E+11 | 77645.87 | 04-SEP-10:23 | 39476.29 | 0.00 |
October | 0.00 | 0.00 | 0.305822E+11 | 0.198335E+11 | 80751.86 | 06-OCT-05:04 | 34350.28 | 0.00 |
November | 0.00 | 0.00 | 0.709635E+10 | 0.475115E+10 | 63173.34 | 02-NOV-17:10 | 39776.49 | 0.00 |
December | 0.00 | 0.00 | 0.388602E+10 | 0.253065E+10 | 31556.15 | 10-DEC-15:20 | 23275.03 | 0.00 |
Annual Sum or Average | 0.284117E+12 | 0.185420E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.662161E+09 | 0.439084E+09 | 28484.74 | 22743.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.502648E+11 | 0.316575E+11 | 80751.86 | 44248.32 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.124298E+10 | 0.36 | 1247.84 | 21-JAN-11:50 | 0.94 |
February | 0.114262E+10 | 0.36 | 1247.84 | 03-FEB-09:50 | 0.93 |
March | 0.134099E+10 | 0.38 | 1247.84 | 15-MAR-15:40 | 0.93 |
April | 0.125150E+10 | 0.37 | 1247.84 | 03-APR-08:25 | 0.93 |
May | 0.133651E+10 | 0.39 | 1247.84 | 22-MAY-17:00 | 0.92 |
June | 0.133853E+10 | 0.41 | 1247.84 | 01-JUN-05:01 | 0.92 |
July | 0.129564E+10 | 0.38 | 1247.84 | 06-JUL-16:50 | 0.92 |
August | 0.139784E+10 | 0.41 | 1247.84 | 01-AUG-16:40 | 0.92 |
September | 0.129780E+10 | 0.40 | 1247.84 | 06-SEP-06:30 | 0.92 |
October | 0.127956E+10 | 0.38 | 1247.84 | 02-OCT-05:01 | 0.93 |
November | 0.119658E+10 | 0.35 | 1247.84 | 10-NOV-16:40 | 0.93 |
December | 0.124375E+10 | 0.35 | 1247.84 | 01-DEC-09:40 | 0.93 |
Annual Sum or Average | 0.153643E+11 | 0.38 | |||
Minimum of Months | 0.114262E+10 | 0.35 | 1247.84 | 0.92 | |
Maximum of Months | 0.139784E+10 | 0.41 | 1247.84 | 0.94 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.274637E+10 | 0.33 | 2769.02 | 02-JAN-10:50 | 0.89 |
February | 0.253066E+10 | 0.34 | 2769.02 | 02-FEB-11:40 | 0.88 |
March | 0.296617E+10 | 0.36 | 2769.02 | 04-MAR-12:40 | 0.89 |
April | 0.280402E+10 | 0.37 | 2769.02 | 01-APR-14:40 | 0.89 |
May | 0.322661E+10 | 0.51 | 2769.02 | 01-MAY-10:50 | 0.89 |
June | 0.332895E+10 | 0.58 | 2769.02 | 01-JUN-12:20 | 0.89 |
July | 0.342500E+10 | 0.62 | 2769.02 | 01-JUL-07:00 | 0.88 |
August | 0.351697E+10 | 0.60 | 2769.02 | 03-AUG-06:20 | 0.88 |
September | 0.317547E+10 | 0.51 | 2769.02 | 05-SEP-07:00 | 0.88 |
October | 0.303865E+10 | 0.45 | 2769.02 | 02-OCT-08:50 | 0.89 |
November | 0.265323E+10 | 0.34 | 2769.02 | 01-NOV-08:30 | 0.88 |
December | 0.274465E+10 | 0.33 | 2769.02 | 02-DEC-15:40 | 0.89 |
Annual Sum or Average | 0.361568E+11 | 0.45 | |||
Minimum of Months | 0.253066E+10 | 0.33 | 2769.02 | 0.88 | |
Maximum of Months | 0.351697E+10 | 0.62 | 2769.02 | 0.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.39 | 2.19 |
February | 1.16 | 1.97 |
March | 1.72 | 1.86 |
April | 2.64 | 0.91 |
May | 3.59 | 0.00 |
June | 3.16 | 0.00 |
July | 3.70 | 0.02 |
August | 3.89 | 0.02 |
September | 3.29 | 0.02 |
October | 3.47 | 0.14 |
November | 1.92 | 2.45 |
December | 1.72 | 2.41 |
Annual Sum or Average | 31.65 | 0.65 |
Minimum of Months | 1.16 | 0.00 |
Maximum of Months | 3.89 | 2.45 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.08 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.17 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.03 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.28 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.17 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.26 | 0.00 |
May | 2.87 | 0.00 |
June | 6.36 | 0.00 |
July | 7.10 | 0.00 |
August | 6.16 | 0.00 |
September | 4.23 | 0.00 |
October | 1.14 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 28.13 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 7.10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.179091E+10 | 0.813952E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.198292E+10 | 0.449869E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.254048E+10 | 0.341890E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.342990E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.521234E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.549550E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.553213E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.593070E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.511518E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.455365E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.288526E+10 | 24243798.15 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.231090E+10 | 0.451076E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.467799E+11 | 0.208103E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.179091E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.593070E+10 | 0.813952E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.293724E+10 | 74811592.67 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.319817E+10 | 0.172599E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.404266E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.683812E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.145318E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.164547E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.180456E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.178225E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.143095E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.118020E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.467797E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.385354E+10 | 18666922.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.118514E+12 | 0.266077E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.293724E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.180456E+11 | 0.172599E+09 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.124298E+10 | 0.206047E+10 | 0.558070E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114262E+10 | 0.316893E+10 | 0.307685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134099E+10 | 0.451488E+10 | 0.232435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125150E+10 | 0.813170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133651E+10 | 0.143089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133853E+10 | 0.152219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129564E+10 | 0.156818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139784E+10 | 0.168841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129780E+10 | 0.144892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127956E+10 | 0.122939E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119658E+10 | 0.637772E+10 | 15852009.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.124375E+10 | 0.402640E+10 | 0.306098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153643E+11 | 0.117160E+12 | 0.142014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.114262E+10 | 0.206047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139784E+10 | 0.168841E+11 | 0.558070E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.274637E+10 | 0.662161E+09 | 49242985.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.253066E+10 | 0.234090E+10 | 0.116435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.296617E+10 | 0.376011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.280402E+10 | 0.139316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.322661E+10 | 0.386168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.332895E+10 | 0.446301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.342500E+10 | 0.502648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.351697E+10 | 0.493580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.317547E+10 | 0.389882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.303865E+10 | 0.305822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.265323E+10 | 0.709635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.274465E+10 | 0.388602E+10 | 12104611.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.361568E+11 | 0.284117E+12 | 0.177782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.253066E+10 | 0.662161E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.351697E+10 | 0.502648E+11 | 0.116435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.124298E+10 | 0.00 | 0.00 | 0.00 | 0.547931E+09 | 0.00 | 0.813952E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114262E+10 | 0.00 | 0.00 | 0.00 | 0.840303E+09 | 0.00 | 0.449869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134099E+10 | 0.00 | 0.00 | 0.00 | 0.119950E+10 | 0.00 | 0.341890E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125150E+10 | 0.00 | 0.00 | 0.00 | 0.217840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133651E+10 | 0.00 | 0.00 | 0.00 | 0.387582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133853E+10 | 0.00 | 0.00 | 0.00 | 0.415696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129564E+10 | 0.00 | 0.00 | 0.00 | 0.423649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139784E+10 | 0.00 | 0.00 | 0.00 | 0.453286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129780E+10 | 0.00 | 0.00 | 0.00 | 0.381738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127956E+10 | 0.00 | 0.00 | 0.00 | 0.327409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119658E+10 | 0.00 | 0.00 | 0.00 | 0.168868E+10 | 0.00 | 24243798.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.124375E+10 | 0.00 | 0.00 | 0.00 | 0.106715E+10 | 0.00 | 0.451076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153643E+11 | 0.00 | 0.00 | 0.00 | 0.314156E+11 | 0.00 | 0.208103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.114262E+10 | 0.00 | 0.00 | 0.00 | 0.547931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139784E+10 | 0.00 | 0.00 | 0.00 | 0.453286E+10 | 0.00 | 0.813952E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.274637E+10 | 0.00 | 0.00 | 0.00 | 0.190867E+09 | 0.00 | 74811592.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.253066E+10 | 0.00 | 0.00 | 0.00 | 0.667509E+09 | 0.00 | 0.172599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.296617E+10 | 0.00 | 0.00 | 0.00 | 0.107649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.280402E+10 | 0.00 | 0.00 | 0.00 | 0.403409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.322661E+10 | 0.00 | 0.00 | 0.00 | 0.113052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.332895E+10 | 0.00 | 0.00 | 0.00 | 0.131258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.342500E+10 | 0.00 | 0.00 | 0.00 | 0.146206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.351697E+10 | 0.00 | 0.00 | 0.00 | 0.143056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.317547E+10 | 0.00 | 0.00 | 0.00 | 0.111340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.303865E+10 | 0.00 | 0.00 | 0.00 | 0.876339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.265323E+10 | 0.00 | 0.00 | 0.00 | 0.202474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.274465E+10 | 0.00 | 0.00 | 0.00 | 0.110888E+10 | 0.00 | 18666922.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.361568E+11 | 0.00 | 0.00 | 0.00 | 0.823570E+11 | 0.00 | 0.266077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.253066E+10 | 0.00 | 0.00 | 0.00 | 0.190867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.351697E+10 | 0.00 | 0.00 | 0.00 | 0.146206E+11 | 0.00 | 0.172599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.495629E+09 | 0.161731E+09 | 0.00 | 999680.22 | 0.00 | 0.196492E+09 | 0.321599E+09 | 0.00 | 0.14 |
February | 0.265393E+09 | 0.280630E+09 | 0.00 | 996498.55 | 168162.18 | 0.104889E+09 | 0.243520E+09 | 0.00 | 0.14 |
March | 0.304632E+09 | 0.432439E+09 | 0.00 | 1711780.28 | 242149.92 | 79381686.69 | 0.271576E+09 | 0.00 | 0.15 |
April | 36692545.69 | 0.888656E+09 | 0.00 | 2007506.52 | 255085.25 | 0.00 | 0.101122E+09 | 0.00 | 0.14 |
May | 0.00 | 0.244416E+10 | 0.00 | 164239.13 | 0.00 | 0.00 | 2727.54 | 0.00 | 0.15 |
June | 0.00 | 0.277715E+10 | 0.00 | 379333.71 | 0.00 | 0.00 | 36995.77 | 0.00 | 0.15 |
July | 0.00 | 0.310696E+10 | 0.00 | 192616.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
August | 0.00 | 0.308544E+10 | 0.00 | 134982.95 | 0.00 | 0.00 | 59514.18 | 0.00 | 0.16 |
September | 0.00 | 0.254590E+10 | 0.00 | 496209.93 | 0.00 | 0.00 | 2664.03 | 0.00 | 0.15 |
October | 14305708.97 | 0.190897E+10 | 0.00 | 3195473.03 | 0.00 | 0.00 | 0.118604E+09 | 0.00 | 0.14 |
November | 82420329.64 | 0.645708E+09 | 0.00 | 2608478.30 | 0.00 | 14487231.74 | 0.222987E+09 | 0.00 | 0.14 |
December | 0.365492E+09 | 0.449631E+09 | 1051.88 | 1273267.20 | 75689.72 | 0.128485E+09 | 0.254062E+09 | 11660.27 | 0.14 |
Annual Sum or Average | 0.156456E+10 | 0.187274E+11 | 1051.88 | 14160066.15 | 741087.07 | 0.523735E+09 | 0.153357E+10 | 11660.27 | 0.15 |
Minimum of Months | 0.00 | 0.161731E+09 | 0.00 | 134982.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.495629E+09 | 0.310696E+10 | 1051.88 | 3195473.03 | 255085.25 | 0.196492E+09 | 0.321599E+09 | 11660.27 | 0.16 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.323796E+10 | 38139204.52 | 0.00 | 143460.64 | 3834170.89 | 22515093.04 | 10940818.37 | 0.00 | 0.19 |
February | 0.228346E+10 | 0.255447E+09 | 0.00 | 267381.59 | 1947659.02 | 21025669.31 | 48665187.77 | 0.00 | 0.20 |
March | 0.254310E+10 | 0.517735E+09 | 0.00 | 414117.21 | 3327824.89 | 0.00 | 0.100799E+09 | 0.00 | 0.21 |
April | 0.845055E+09 | 0.185985E+10 | 0.00 | 2318833.89 | 0.00 | 0.00 | 0.506079E+09 | 0.00 | 0.21 |
May | 2349683.32 | 0.726286E+10 | 0.00 | 354305.57 | 3161659.90 | 0.00 | 24827483.43 | 0.00 | 0.23 |
June | 10290796.40 | 0.966641E+10 | 0.00 | 168050.94 | 1546738.46 | 0.00 | 17995968.64 | 0.00 | 0.25 |
July | 0.00 | 0.112389E+11 | 0.00 | 47382.50 | 1697138.81 | 0.00 | 1577619.29 | 0.00 | 0.24 |
August | 1724116.54 | 0.102638E+11 | 0.00 | 223603.18 | 1035859.81 | 0.00 | 17771938.95 | 0.00 | 0.25 |
September | 2902104.62 | 0.767933E+10 | 0.00 | 556039.46 | 2358911.43 | 0.00 | 74512867.53 | 0.00 | 0.24 |
October | 0.514251E+09 | 0.538655E+10 | 0.00 | 2851057.88 | 141075.12 | 0.00 | 0.253249E+09 | 0.00 | 0.22 |
November | 0.151199E+10 | 0.124826E+10 | 0.00 | 1329786.92 | 5247870.92 | 0.00 | 0.389737E+09 | 0.00 | 0.20 |
December | 0.259692E+10 | 0.628617E+09 | 0.00 | 441098.69 | 10551848.43 | 4662164.47 | 73021023.53 | 0.00 | 0.19 |
Annual Sum or Average | 0.135500E+11 | 0.560459E+11 | 0.00 | 9115118.47 | 34850757.68 | 48202926.83 | 0.151918E+10 | 0.00 | 0.22 |
Minimum of Months | 0.00 | 38139204.52 | 0.00 | 47382.50 | 0.00 | 0.00 | 1577619.29 | 0.00 | 0.19 |
Maximum of Months | 0.323796E+10 | 0.112389E+11 | 0.00 | 2851057.88 | 10551848.43 | 22515093.04 | 0.506079E+09 | 0.00 | 0.25 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |