Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2020-06-03 19:11:49
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1022.46 | 211.46 | 211.46 |
Net Site Energy | 1022.46 | 211.46 | 211.46 |
Total Source Energy | 2886.85 | 597.06 | 597.06 |
Net Source Energy | 2886.85 | 597.06 | 597.06 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 168.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 55.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 99.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 59.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.57 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 853.82 | 168.64 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 168.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 55.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 99.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 7.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 52.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.57 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 119.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 28.78 | 34.88 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 176.59 | 34.88 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 119.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 28.78 | 34.88 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 176.59 | 34.88 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 853.816 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 853.816 | 100.00 |
Total On-Site and Utility Electric Sources | 853.816 | 100.00 |
Total Electricity End Uses | 853.816 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 27.00 |
Time Setpoint Not Met During Occupied Cooling | 26.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1121.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.6337 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.5069 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.5069 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 08-JUL-14:50 | 12-FEB-06:10 | - | - | - | 01-SEP-11:39 |
Heating | 0.00 | 233992.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 19287.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6342.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1705.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 72637.05 | 233992.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 233992.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 19287.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4037.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1705.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 182.81 | 0.00 | 0.00 | 0.00 |
Cooling | 174.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1507.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 314.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 188.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 77.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2704.04 | 182.81 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 37.81 | 0.00 | 0.00 | 0.00 |
Cooling | 36.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 559.25 | 37.81 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 37.81 | 0.00 | 0.00 | 0.00 |
Cooling | 36.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 559.25 | 37.81 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.06 |
ZONE2 FINE STORAGE DIRECT AIR | 2.58 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 2.83 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 2.83 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 113243.91 |
PSZ-OFFICE HEATING COIL | 26792.40 |
PSZ-FINE STORAGE HEATING COIL | 84418.65 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 113243.91 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 1.00 | 1.06 |
PSZ-FINE STORAGE | 2.58 | 2.58 | 2.58 | 2.58 | 2.58 | 2.58 | 1.00 | 1.000000 | 2.58 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.06 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 2.58 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 1.06 | 20420.56 | 26792.40 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.58 | 2.58 | 2.58 | 2.58 | 63268.85 | 84418.65 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.06 | 0.532130 | 1.06 | 19908.62 | 20420.56 | 10210.28 | 20420.56 | 0.748185 | 0.748180 | 0.748180 | 0.748180 |
PSZ-FINE STORAGE COOLING COIL | 2.58 | 1.29 | 2.58 | 60636.16 | 63268.85 | 31634.42 | 63268.85 | 0.679199 | 0.679200 | 0.679200 | 0.679200 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.06 | 1213.37 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.58 | 2824.08 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.634 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.707 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.507 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.507 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.507 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.066 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2518.900 | 10.634 | 503.780 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2518.900 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11853.648 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11853.648 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27263.390 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27263.390 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3263 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3263 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.5084 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.5084 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.5084 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.065 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.065 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.867 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.867 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.867 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.38866262E-07 | 0.77198350E-12 | 0.86409618E-13 | 0.0000000 |
2 | 1 | -5.2160226 | 0.42725752E-04 | -0.49098391E-04 | 0.74579932E-08 |
3 | 0 | 5.5423254 | 0.32626013 | 0.32635195 | |
4 | 2 | 0.38866262E-07 | 0.77198350E-12 | 0.86409618E-13 | 0.0000000 |
5 | 1 | -5.2160226 | 0.42725752E-04 | -0.49098391E-04 | 0.74579932E-08 |
6 | 0 | 5.5423254 | 0.32626013 | 0.32635195 | |
7 | 4 | 0.77647315E-12 | 0.13408001E-15 | -0.22253071E-14 | 0.11703322E-15 |
8 | 3 | -0.38306226E-03 | 0.35631809E-06 | -0.55549669E-04 | 0.14899307E-12 |
9 | 2 | 1.7356375 | 0.78038605E-02 | 1.1374847 | -0.73439249E-04 |
10 | 1 | -7.1338263 | 0.20239632 | -17.079215 | 0.33264924 |
11 | 0 | 5.7379043 | 0.12913194 | 16.281118 | |
12 | 4 | 0.77647315E-12 | 0.13408001E-15 | -0.22253071E-14 | 0.11703322E-15 |
13 | 3 | -0.38306226E-03 | 0.35631809E-06 | -0.55549669E-04 | 0.14899307E-12 |
14 | 2 | 1.7356375 | 0.78038605E-02 | 1.1374847 | -0.73439249E-04 |
15 | 1 | -7.1338263 | 0.20239632 | -17.079215 | 0.33264924 |
16 | 0 | 5.7379043 | 0.12913194 | 16.281118 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.22253071E-14 | 0.13408001E-15 | 0.77647315E-12 | 0.11703322E-15 |
85 | 3 | -0.55549669E-04 | 0.35631809E-06 | -0.38306226E-03 | 0.14899307E-12 |
86 | 2 | 1.1374847 | 0.78038605E-02 | 1.7356375 | -0.73439249E-04 |
87 | 1 | -17.079215 | 0.20239632 | -7.1338263 | 0.33264924 |
88 | 0 | 16.281118 | 0.12913194 | 5.7379043 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.63_SHGC_0.25 | 28 | 1 | VerySmooth | 3.582 | 0.253 | 0.153 | 0.250 |
2 | SKYLIGHT_U_0.65_SHGC_0.35 | 29 | 1 | VerySmooth | 3.695 | 0.347 | 0.243 | 0.351 |
3 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 30 | 1 | VerySmooth | 3.695 | 0.347 | 0.243 | 0.351 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.15304 | 0.57918 | 0.57918 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.81224E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.24267 | 0.45800 | 0.45800 | 0.35000 | 0.14371 | 0.19477 | 0.00000 | 0.84000 | 0.84000 | 1.96142E-002 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.24267 | 0.45800 | 0.45800 | 0.35000 | 0.14371 | 0.19477 | 0.00000 | 0.84000 | 0.84000 | 1.96142E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10393.42389 | 12472.10866 | 0.88688 | 1.06426 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.07000 | 1.44457E-002 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10376.41054 | 12451.69265 | 0.30208 | 0.36249 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -6.30000 | 2.29779E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 32320.91395 | 38785.09673 | 2.15019 | 2.58023 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.07000 | 1.44457E-002 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 42471.90027 | 50966.28032 | 1.04145 | 1.24974 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40000 | 1.44457E-002 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 94369.92508 | 113243.91009 | 2.35641 | 2.82769 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -6.30000 | 2.29779E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 15867.94 | 1.06426 | 1.06426 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 11277.62 | 0.36249 | 0.36249 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 47442.27 | 2.58023 | 2.58023 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 46471.46 | 1.24974 | 1.24974 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.06426 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.58023 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.82769 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 2.82769 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 113243.91491 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 113243.91009 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.06426 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.06426 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.06426 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.06426 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06426 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.06426 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.58023 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.58023 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.58023 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.58023 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.58023 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.58023 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.06426 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.58023 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06426 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06426 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06426 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06426 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.06426 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06426 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53213 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.06426 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 19908.61529 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 20420.56000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10210.28000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 20420.56000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74818 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74818 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74818 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74818 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20420.56000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26792.39962 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06426 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1213.36841 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26792.39962 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.58023 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.58023 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.58023 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.58023 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.58023 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.58023 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.29012 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.58023 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 60636.16297 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 63268.85000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 31634.42500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 63268.85000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67920 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67920 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67920 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67920 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 63268.85000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 84418.64999 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.58023 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2824.07758 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 84418.64999 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 19594.3 | 10.31 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 61263.4 | 13.32 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 11 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 2.4289646269E-002 | 2.5510919183E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.2597571125 | 0.2962615473 | Pass | Pass | 2.3674506154 | 6.0878645435 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.4259955302E-002 | 3.9606790564E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.472 | 0.508 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.472 | 0.508 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.472 | 0.508 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.472 | 0.508 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.472 | 0.508 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.472 | 0.508 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.472 | 0.508 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.312 | 0.326 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.472 | 0.508 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.472 | 0.508 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.472 | 0.508 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.312 | 0.326 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.63_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.582 | 0.253 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.63_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.582 | 0.253 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.63_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.582 | 0.253 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.63_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.582 | 0.253 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.65_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.347 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.634 | 0.296 | 0.296 | ||||||||||||
North Total or Average | 6.51 | 3.582 | 0.253 | 0.250 | ||||||||||||
Non-North Total or Average | 26.02 | 3.647 | 0.307 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.6337 | 236.88 | 2518.90 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.62 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.5069 | 1393.41 | 11853.65 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 135.00 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.5069 | 3204.84 | 27263.39 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 310.50 |
Interior Lighting Total | 8.6111 | 4835.13 | 41635.94 | 476.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 6311.00 | AstronomicalClock | - | 83.77 | 83.77 | 99.24 | |
Exterior Lighting Total | 6311.00 | 99.24 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20420.56 | 15278.25 | 5142.31 | 0.75 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 63268.85 | 42972.20 | 20296.65 | 0.68 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 19594.3 | 10.31 | ||||
PSZ-FINE STORAGE COOLING COIL | 61263.4 | 13.32 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 113243.91 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26792.40 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 84418.65 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.83 | 262.72 | 92.91 | 1.00 | 3.39 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.06 | 1213.37 | 1140.11 | 1.00 | 1.35 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.58 | 2824.08 | 1094.51 | 1.00 | 1.25 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10393.42 | 12472.11 | 52.65 | 0.887 | 1.064 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00833 | 33.07 | 0.01445 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 32320.91 | 38785.10 | 27.83 | 2.150 | 2.580 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 26.70 | 26.70 | 0.00929 | 33.07 | 0.01445 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00392 | 34.40 | 0.01445 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10376.41 | 12451.69 | 52.57 | 0.302 | 0.362 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00723 | -6.30 | 0.00230 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 42471.90 | 50966.28 | 36.58 | 1.041 | 1.250 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.55 | 0.00544 | -6.30 | 0.00230 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 94369.93 | 113243.91 | 35.34 | 2.356 | 2.828 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 10.00 | 9.99 | 0.00792 | -6.30 | 0.00230 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.06 | 1.06 | 0.36 | 0.36 | 1.0643 | 1.0643 | 1.0643 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.58 | 2.58 | 1.25 | 1.25 | 2.5802 | 2.5802 | 2.5802 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 113243.915 | 113243.915 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 113243.91 | 113243.91 | 2.827693 | 4.36 | 4.36 | 0.00597709 | 43.33 | 26.63 | 0.01600000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 9.99 | 0.00791894 | 100.0000 | 113243.91 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 20420.560 | 0.000 | 1.064260 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 20420.56 | 17653.93 | 1.064260 | 24.78 | 16.62 | 0.00891793 | 12.00 | 10.94 | 0.00800000 | 33.07 | 0.01444567 | 23.16 | 9.6109 | 23.90 | 0.00833017 | 43.5091 | 10393.42 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26792.400 | 26792.400 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 26792.40 | 26792.40 | 1.064256 | 13.33 | 9.22 | 0.00583548 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 9.6109 | 21.10 | 0.00722610 | 44.8259 | 10376.41 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 63268.850 | 0.000 | 2.580230 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 63268.85 | 51735.38 | 2.580230 | 27.98 | 18.23 | 0.00958796 | 12.00 | 10.94 | 0.00800000 | 34.40 | 0.01444567 | 23.51 | 16.4603 | 26.70 | 0.00928970 | 41.0211 | 32320.91 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 84418.650 | 84418.650 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 84418.65 | 84418.65 | 2.580232 | 8.13 | 5.04 | 0.00436925 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 16.4603 | 15.55 | 0.00543560 | 47.8986 | 42471.90 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 113243.915 | 113243.915 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1610 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 2.827693 | 3.28288474 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 113243.91 | 113243.91 | 1.0000 | 3.28288474 | 2.827693 | 4.36 | 4.36 | 0.00597709 | 19381.3 | 43.33 | 26.63 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 113243.91 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 9.99 | 0.00791894 | 9.99 | 0.00791894 | 100.0000 | 113243.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20420.560 | 0.000 | 1.064260 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4180 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 20420.56 | 17653.93 | 1.0000 | 1.23558089 | 1.064260 | 24.78 | 16.62 | 0.00891793 | 47614.4 | 12.00 | 10.94 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20420.56 | 33.07 | 0.01444567 | 23.16 | 0.10228487 | 9.6109 | 23.90 | 0.00833017 | 23.90 | 0.00833017 | 43.5091 | 10393.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26792.400 | 26792.400 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.064256 | 1.23557587 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 26792.40 | 26792.40 | 1.0000 | 1.23557587 | 1.064256 | 13.33 | 9.22 | 0.00583548 | 28135.4 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26792.40 | -6.30 | 0.00229779 | -6.30 | 0.10228487 | 9.6109 | 21.05 | 0.00722610 | 21.10 | 0.00722610 | 44.8259 | 10376.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 63268.850 | 0.000 | 2.580230 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.6635 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 63268.85 | 51735.38 | 1.0000 | 2.99558650 | 2.580230 | 27.98 | 18.23 | 0.00958796 | 52596.8 | 12.00 | 10.94 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 63268.85 | 34.40 | 0.01444567 | 23.51 | 0.42471267 | 16.4603 | 26.70 | 0.00861458 | 26.70 | 0.00928970 | 41.0211 | 32320.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 84418.650 | 84418.650 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.580232 | 2.99558827 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 84418.65 | 84418.65 | 1.0000 | 2.99558827 | 2.580232 | 8.13 | 5.04 | 0.00436925 | 19158.5 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 84418.65 | -6.30 | 0.00229779 | -6.30 | 0.42471267 | 16.4603 | 15.55 | 0.00543560 | 15.55 | 0.00543560 | 47.8986 | 42471.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE OA CONTROLLER | DifferentialEnthalpy | 0.10 | 1.06 | - | |||
PSZ-FINE STORAGE OA CONTROLLER | DifferentialEnthalpy | 0.42 | 2.58 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2503.50 | 2020.67 | 1121.17 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2503.50 | 2020.67 | 1121.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 31.17 | 27.00 | 27.00 | 26.00 |
ZONE2 FINE STORAGE | 187.83 | 86.33 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 1.00 | 0.00 | 0.00 | 0.00 |
Facility | 214.33 | 113.33 | 27.00 | 26.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.639 | 0.397 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 853.82 | 5421.86 | 01-JAN-08:00 | 72637.05 | 08-JUL-14:50 |
Electricity:Building | 622.63 | 4938.86 | 01-JAN-00:10 | 47606.95 | 18-MAY-14:50 |
Electricity:Zone:ZONE1 OFFICE | 62.57 | 1027.15 | 01-JAN-00:10 | 3852.05 | 02-JAN-08:10 |
InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.62 | 453.40 | 01-JAN-00:10 | 1939.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 425.06 | 2726.34 | 01-JAN-00:10 | 33679.30 | 18-MAY-12:40 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 310.51 | 2726.34 | 01-JAN-00:10 | 23173.88 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 24.57 | 483.00 | 11-FEB-24:00 | 2122.67 | 30-JAN-12:30 |
WaterSystems:Electricity | 24.57 | 483.00 | 11-FEB-24:00 | 2122.67 | 30-JAN-12:30 |
Water Heater:WaterSystems:Electricity | 24.57 | 483.00 | 11-FEB-24:00 | 2122.67 | 30-JAN-12:30 |
Fans:Electricity | 59.43 | 0.00 | 01-JAN-00:40 | 6342.74 | 19-MAY-14:50 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 7.22 | 0.00 | 01-JAN-00:10 | 2305.29 | 19-MAY-14:50 |
Ventilation (simple):Fans:Electricity | 7.22 | 0.00 | 01-JAN-00:10 | 2305.29 | 19-MAY-14:50 |
ElectricityPurchased:Facility | 853.82 | 5421.86 | 01-JAN-08:00 | 72637.05 | 08-JUL-14:50 |
ElectricityPurchased:Plant | 853.82 | 5421.86 | 01-JAN-08:00 | 72637.05 | 08-JUL-14:50 |
Cogeneration:ElectricityPurchased | 853.82 | 5421.86 | 01-JAN-08:00 | 72637.05 | 08-JUL-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 853.82 | 5421.86 | 01-JAN-08:00 | 72637.05 | 08-JUL-14:50 |
ElectricityNet:Plant | 853.82 | 5421.86 | 01-JAN-08:00 | 72637.05 | 08-JUL-14:50 |
Cogeneration:ElectricityNet | 853.82 | 5421.86 | 01-JAN-08:00 | 72637.05 | 08-JUL-14:50 |
Electricity:HVAC | 107.38 | 0.00 | 01-JAN-00:40 | 24736.26 | 01-AUG-17:00 |
General:Fans:Electricity | 52.21 | 0.00 | 01-JAN-00:40 | 4300.17 | 05-JAN-10:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 55.17 | 0.00 | 01-JAN-00:10 | 20698.82 | 01-AUG-17:00 |
ExteriorLights:Electricity | 99.24 | 0.00 | 01-JAN-07:50 | 6311.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 99.24 | 0.00 | 01-JAN-07:50 | 6311.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 168.64 | 0.00 | 01-JAN-00:40 | 233992.28 | 12-FEB-06:10 |
Gas:HVAC | 168.64 | 0.00 | 01-JAN-00:40 | 233992.28 | 12-FEB-06:10 |
Heating:Gas | 168.64 | 0.00 | 01-JAN-00:40 | 233992.28 | 12-FEB-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 01-SEP-11:40 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 01-SEP-11:40 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 01-SEP-11:40 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 01-SEP-11:40 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 01-SEP-11:40 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 01-SEP-11:40 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 01-SEP-11:40 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 01-SEP-11:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 571.88 | 0.00 | 01-JAN-00:40 | 369279.56 | 12-FEB-06:10 |
EnergyTransfer:Building | 255.77 | 0.00 | 01-JAN-00:40 | 184978.15 | 12-FEB-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 53.93 | 0.00 | 01-JAN-00:10 | 20867.52 | 13-FEB-07:10 |
Heating:EnergyTransfer | 127.12 | 0.00 | 01-JAN-00:40 | 184978.15 | 12-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 13.82 | 0.00 | 01-JAN-00:10 | 20867.52 | 13-FEB-07:10 |
Cooling:EnergyTransfer | 128.65 | 0.00 | 01-JAN-00:10 | 41670.09 | 03-AUG-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 40.12 | 0.00 | 01-JAN-00:10 | 11701.44 | 07-JUL-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 143.77 | 0.00 | 01-JAN-00:40 | 67839.60 | 12-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 55.23 | 0.00 | 01-JAN-00:40 | 67839.60 | 12-FEB-06:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 88.54 | 0.00 | 01-JAN-00:10 | 31687.76 | 03-AUG-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 58.07 | 0.00 | 01-JAN-00:10 | 113731.53 | 12-FEB-01:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 58.07 | 0.00 | 01-JAN-00:10 | 113731.53 | 12-FEB-01:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 316.11 | 0.00 | 01-JAN-00:40 | 184301.41 | 12-FEB-06:10 |
HeatingCoils:EnergyTransfer | 124.66 | 0.00 | 01-JAN-00:40 | 184301.41 | 12-FEB-06:10 |
CoolingCoils:EnergyTransfer | 191.45 | 0.00 | 01-JAN-00:10 | 67913.35 | 03-AUG-16:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 13.817 | -40.116 | 0.000 | 0.000 | 3.774 | 30.619 | 31.946 | 8.578 | 0.000 | 2.223 | 0.000 | 0.000 | -9.050 | 0.000 | -16.491 | -25.300 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 55.232 | -88.532 | 0.000 | 0.000 | 0.000 | 135.003 | 0.000 | 0.000 | 0.000 | 5.718 | 0.000 | 0.000 | 0.000 | 0.000 | -104.288 | -3.132 |
ZONE3 BULK STORAGE | 58.066 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 310.507 | 107.336 | 22.498 | 0.000 | 15.335 | 0.007 | 0.000 | -9.057 | 0.000 | -477.642 | -27.044 |
Total Facility | 58.066 | 0.000 | 69.049 | -128.648 | 0.000 | 0.000 | 3.774 | 476.129 | 139.282 | 31.076 | 0.000 | 23.276 | 0.007 | 0.000 | -18.107 | 0.000 | -598.420 | -55.477 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 08-JUN-05:02 | 0.00 | 0.00 | 0.00 | -24549.88 | 0.00 | 0.00 | 35.37 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 25006.08 | 0.00 | -756.06 | 0.00 | -888.60 | 0.00 |
ZONE2 FINE STORAGE | 08-JUN-19:11 | 0.00 | 0.00 | 0.00 | -62335.68 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 62027.53 | 0.00 | -0.00 | 0.00 | -877.22 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 08-JUN-19:11 | 0.00 | 0.00 | 0.00 | -62335.68 | 0.00 | 0.00 | 0.00 | 4365.11 | 2623.78 | 518.59 | 0.00 | 0.00 | 62683.17 | 0.00 | -505.71 | 0.00 | -7349.26 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 13-FEB-06:41 | 0.00 | 0.00 | 29154.27 | 0.00 | 0.00 | 0.00 | 54.98 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1135.52 | 0.00 | -2911.79 | -26315.03 |
ZONE2 FINE STORAGE | 14-JAN-06:41 | 0.00 | 0.00 | 88691.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -19575.87 | -70301.48 |
ZONE3 BULK STORAGE | 12-FEB-01:05 | 113835.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1117.11 | 0.00 | -108704.59 | -6740.43 |
Total Facility | 13-FEB-06:51 | 91099.39 | 0.00 | 111993.90 | 0.00 | 0.00 | 0.00 | 46.49 | 4491.05 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2150.37 | 0.00 | -102077.62 | -106026.63 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0643 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.0643 | 0.0961 | 1.0000 | 0.1023 | 0.0961 | ||
PSZ-FINE STORAGE | 2.5802 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.5802 | 0.1646 | 1.0000 | 0.4247 | 0.1646 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0643 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.0643 | 1.0000 | 1.0000 | 0.1023 | 0.0961 | ||
PSZ-FINE STORAGE | 2.5802 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.5802 | 1.0000 | 1.0000 | 0.4247 | 0.1646 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0643 | 1.0643 | 1.0643 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.5802 | 2.5802 | 2.5802 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0643 | 1.0643 | 1.0643 | 1.0643 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.5802 | 2.5802 | 2.5802 | 2.5802 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0643 | 1.0643 | 1.0643 | 0.1023 | 0.2822 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.5802 | 2.5802 | 2.5802 | 0.4247 | 0.3398 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0643 | 1.0643 | 1.0643 | 1.0643 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.5802 | 2.5802 | 2.5802 | 2.5802 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:49
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 27.00 |
Number of hours cooling loads not met | 26.00 |
Number of hours not met | 53.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 168.64 | 233992.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 55.17 | 20698.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 476.13 | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 99.24 | 6311.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 7.22 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 52.21 | 4300.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.57 | 2122.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 853.82 |
Natural Gas | 0.00 | 168.64 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1022.46 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 98.47 |
Space Heating | 0.00 |
Space Cooling | 11.41 |
Fans (All) | 12.29 |
Service Water Heating | 5.08 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 176.59 |
Subtotal | 176.59 |
Natural Gas [MJ/m2] | |
Space Heating | 34.88 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 34.88 |
Subtotal | 34.88 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 46.57 |
Space Heating | 16.49 |
Space Cooling | 5.40 |
Fans (All) | 5.81 |
Service Water Heating | 2.40 |
Receptacle Equipment | 13.62 |
Miscellaneous | 9.71 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.841823E+11 |
February | 0.000 | 0.546767E+11 |
March | 0.000 | 0.198976E+10 |
April | 0.000 | 0.240071E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.204916E+09 |
November | 0.000 | 0.440888E+10 |
December | 0.000 | 0.229421E+11 |
Annual Sum or Average | 0.168645E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.841823E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.841823E+11 |
February | 0.000 | 0.546767E+11 |
March | 0.000 | 0.198976E+10 |
April | 0.000 | 0.240071E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.204916E+09 |
November | 0.000 | 0.440888E+10 |
December | 0.000 | 0.229421E+11 |
Annual Sum or Average | 0.168645E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.841823E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Meter
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.841823E+11 |
February | 0.000 | 0.546767E+11 |
March | 0.000 | 0.198976E+10 |
April | 0.000 | 0.240071E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.204916E+09 |
November | 0.000 | 0.440888E+10 |
December | 0.000 | 0.229421E+11 |
Annual Sum or Average | 0.168645E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.841823E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.841823E+11 |
February | 0.000 | 0.546767E+11 |
March | 0.000 | 0.198976E+10 |
April | 0.000 | 0.240071E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.204916E+09 |
November | 0.000 | 0.440888E+10 |
December | 0.000 | 0.229421E+11 |
Annual Sum or Average | 0.168645E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.841823E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.841823E+11 |
February | 0.000 | 0.546767E+11 |
March | 0.000 | 0.198976E+10 |
April | 0.000 | 0.240071E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.204916E+09 |
November | 0.000 | 0.440888E+10 |
December | 0.000 | 0.229421E+11 |
Annual Sum or Average | 0.168645E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.841823E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.841823E+11 |
February | 0.000 | 0.546767E+11 |
March | 0.000 | 0.198976E+10 |
April | 0.000 | 0.240071E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.204916E+09 |
November | 0.000 | 0.440888E+10 |
December | 0.000 | 0.229421E+11 |
Annual Sum or Average | 0.168645E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.841823E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.841823E+11 |
February | 0.000 | 0.546767E+11 |
March | 0.000 | 0.198976E+10 |
April | 0.000 | 0.240071E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.204916E+09 |
November | 0.000 | 0.440888E+10 |
December | 0.000 | 0.229421E+11 |
Annual Sum or Average | 0.168645E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.841823E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Meter
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.841823E+11 |
February | 0.000 | 0.546767E+11 |
March | 0.000 | 0.198976E+10 |
April | 0.000 | 0.240071E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.204916E+09 |
November | 0.000 | 0.440888E+10 |
December | 0.000 | 0.229421E+11 |
Annual Sum or Average | 0.168645E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.841823E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Meter
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.841823E+11 |
February | 0.000 | 0.546767E+11 |
March | 0.000 | 0.198976E+10 |
April | 0.000 | 0.240071E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.204916E+09 |
November | 0.000 | 0.440888E+10 |
December | 0.000 | 0.229421E+11 |
Annual Sum or Average | 0.168645E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.841823E+11 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4631128.28 | 421.18 | 21-JAN-13:30 | 7.75 | 4.18 | 0.197380E+09 | 294.04 | 31-JAN-15:00 | 20.00 | 13.57 |
February | 65560761.51 | 2650.56 | 28-FEB-16:30 | 23.60 | 12.71 | 0.189442E+09 | 301.59 | 27-FEB-16:49 | 22.30 | 11.40 |
March | 0.702847E+09 | 5237.72 | 30-MAR-16:00 | 27.80 | 17.45 | 0.244494E+09 | 301.59 | 11-MAR-11:00 | 21.70 | 14.17 |
April | 0.236908E+10 | 20394.12 | 18-APR-05:03 | 14.22 | 12.17 | 0.243295E+09 | 301.61 | 18-APR-14:00 | 25.60 | 16.91 |
May | 0.454393E+10 | 20725.71 | 17-MAY-05:01 | 16.70 | 13.07 | 0.258275E+09 | 301.62 | 16-MAY-07:00 | 20.00 | 16.78 |
June | 0.714661E+10 | 24554.63 | 08-JUN-05:02 | 11.70 | 8.45 | 0.258970E+09 | 301.61 | 03-JUN-13:09 | 28.98 | 18.69 |
July | 0.763563E+10 | 18964.84 | 03-JUL-05:01 | 17.88 | 16.40 | 0.249089E+09 | 301.61 | 08-JUL-14:50 | 36.60 | 23.98 |
August | 0.856622E+10 | 18810.00 | 26-AUG-05:01 | 21.70 | 17.14 | 0.269034E+09 | 301.61 | 26-AUG-14:50 | 31.38 | 21.10 |
September | 0.603051E+10 | 22443.84 | 14-SEP-05:02 | 12.20 | 10.90 | 0.249005E+09 | 301.62 | 28-SEP-15:00 | 18.30 | 16.51 |
October | 0.246161E+10 | 16723.81 | 11-OCT-05:01 | 18.72 | 16.68 | 0.241801E+09 | 301.60 | 17-OCT-09:20 | 19.63 | 18.92 |
November | 0.537746E+09 | 3588.87 | 06-NOV-16:00 | 20.60 | 10.45 | 0.215487E+09 | 301.59 | 01-NOV-15:50 | 21.02 | 15.55 |
December | 52848037.00 | 1087.66 | 13-DEC-13:10 | 20.22 | 17.27 | 0.204185E+09 | 301.59 | 12-DEC-16:40 | 21.87 | 16.07 |
Annual Sum or Average | 0.401172E+11 | 0.282046E+10 | ||||||||
Minimum of Months | 4631128.28 | 421.18 | 7.75 | 4.18 | 0.189442E+09 | 294.04 | 18.30 | 11.40 | ||
Maximum of Months | 0.856622E+10 | 24554.63 | 27.80 | 17.45 | 0.269034E+09 | 301.62 | 36.60 | 23.98 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.731015E+09 | 4789.55 | 26-JAN-13:00 | 0.00 | -3.7 | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 | 4.97 |
February | 0.390351E+09 | 4001.30 | 02-FEB-13:10 | 1.88 | -1.3 | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 |
March | 0.823019E+09 | 5982.46 | 24-MAR-06:10 | 10.50 | 9.67 | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.50 |
April | 0.225053E+10 | 54926.89 | 16-APR-16:41 | 26.70 | 15.60 | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.81 |
May | 0.722091E+10 | 51462.78 | 19-MAY-20:01 | 25.32 | 17.09 | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 |
June | 0.180516E+11 | 62334.72 | 08-JUN-19:11 | 23.90 | 13.03 | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 |
July | 0.217739E+11 | 49124.77 | 04-JUL-15:13 | 31.47 | 22.94 | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 |
August | 0.235785E+11 | 50014.69 | 25-AUG-17:06 | 30.92 | 19.41 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 21.87 |
September | 0.104913E+11 | 56890.02 | 14-SEP-17:11 | 24.43 | 15.05 | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.45 |
October | 0.188385E+10 | 12235.97 | 09-OCT-15:15 | 27.80 | 19.55 | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 |
November | 0.677888E+09 | 6980.49 | 14-NOV-07:10 | 3.03 | 0.84 | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.59 |
December | 0.664372E+09 | 5993.13 | 12-DEC-07:10 | 12.20 | 12.20 | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 |
Annual Sum or Average | 0.885372E+11 | 0.00 | ||||||||
Minimum of Months | 0.390351E+09 | 4001.30 | 0.00 | -3.7 | 0.00 | 0.00 | 1.80 | 1.51 | ||
Maximum of Months | 0.235785E+11 | 62334.72 | 31.47 | 22.94 | 0.00 | 0.00 | 25.13 | 21.87 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.70 | 4.97 | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 | 4.97 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.50 | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.81 | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.81 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 21.87 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 21.87 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.45 | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.45 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.59 | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.59 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.80 | 1.51 | 0.00 | 0.00 | 1.80 | 1.51 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 21.87 | 0.00 | 0.00 | 25.13 | 21.87 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.503221E+10 | 28320.06 | 17-JAN-06:32 | 3.87 |
February | 0.342272E+10 | 29154.22 | 13-FEB-06:41 | -5.6 |
March | 0.977850E+09 | 27127.74 | 20-MAR-05:01 | 5.00 |
April | 0.275979E+09 | 26791.98 | 07-APR-05:01 | 3.22 |
May | 60537083.01 | 1574.65 | 11-MAY-06:20 | 8.53 |
June | 11091508.53 | 2072.05 | 06-JUN-06:05 | 19.27 |
July | 68530.10 | 228.43 | 29-JUL-06:10 | 17.80 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 16264106.42 | 1443.13 | 29-SEP-06:03 | 12.88 |
October | 0.246915E+09 | 26601.23 | 26-OCT-05:02 | 2.20 |
November | 0.108813E+10 | 27214.31 | 22-NOV-06:12 | -3.3 |
December | 0.268528E+10 | 27327.66 | 18-DEC-06:12 | -5.0 |
Annual Sum or Average | 0.138170E+11 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 0.503221E+10 | 29154.22 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233082E+11 | 88691.76 | 14-JAN-06:41 | -6.7 |
February | 0.144096E+11 | 87786.33 | 13-FEB-00:12 | -2.6 |
March | 0.122960E+10 | 55085.45 | 07-MAR-06:01 | 5.50 |
April | 0.517433E+09 | 2922.78 | 10-APR-07:00 | 8.90 |
May | 0.243860E+09 | 3161.65 | 02-MAY-07:00 | 15.00 |
June | 0.127413E+09 | 2830.30 | 19-JUN-07:00 | 21.10 |
July | 43871380.64 | 2795.56 | 29-JUL-07:00 | 17.80 |
August | 35449488.04 | 2962.03 | 03-AUG-06:04 | 23.90 |
September | 0.156717E+09 | 2955.81 | 20-SEP-07:00 | 16.10 |
October | 0.308571E+09 | 3151.80 | 13-OCT-07:00 | 5.60 |
November | 0.260342E+10 | 85016.15 | 25-NOV-06:01 | 0.68 |
December | 0.122477E+11 | 87572.38 | 17-DEC-03:42 | 0.78 |
Annual Sum or Average | 0.552318E+11 | |||
Minimum of Months | 35449488.04 | 2795.56 | -6.7 | |
Maximum of Months | 0.233082E+11 | 88691.76 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334132E+11 | 96783.71 | 07-JAN-10:00 | -3.9 |
February | 0.231662E+11 | 113836.10 | 12-FEB-01:05 | -10.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.148706E+10 | 23361.93 | 03-DEC-09:00 | -1.1 |
Annual Sum or Average | 0.580664E+11 | |||
Minimum of Months | 0.00 | 0.00 | -10.1 | |
Maximum of Months | 0.334132E+11 | 113836.10 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.256100E+10 | 1939.55 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.233575E+10 | 1939.55 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.266872E+10 | 1939.55 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.252182E+10 | 1939.55 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.261486E+10 | 1939.55 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.257569E+10 | 1939.55 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.256100E+10 | 1939.55 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.266872E+10 | 1939.55 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.252182E+10 | 1939.55 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.256100E+10 | 1939.55 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.246796E+10 | 1939.55 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.256100E+10 | 1939.55 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.306193E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.233575E+10 | 1939.55 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.266872E+10 | 1939.55 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112294E+11 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102778E+11 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.118738E+11 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.111270E+11 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.115516E+11 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.114492E+11 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112294E+11 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.118738E+11 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.111270E+11 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112294E+11 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108048E+11 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112294E+11 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135003E+12 | ||||
Minimum of Months | 0.102778E+11 | 10075.60 | 0.00 | 0.00 | |
Maximum of Months | 0.118738E+11 | 10075.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.258277E+11 | 23173.88 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.236390E+11 | 23173.88 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.273097E+11 | 23173.88 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.255921E+11 | 23173.88 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.265687E+11 | 23173.88 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.263332E+11 | 23173.88 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.258277E+11 | 23173.88 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.273097E+11 | 23173.88 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.255921E+11 | 23173.88 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.258277E+11 | 23173.88 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.248511E+11 | 23173.88 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.258277E+11 | 23173.88 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.236390E+11 | 23173.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.273097E+11 | 23173.88 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331131E+10 |
February | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3057739.01 | 0.253050E+10 |
March | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17543412.66 | 0.175426E+10 |
April | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75570758.69 | 0.112720E+10 |
May | 0.565842E+09 | 0.261486E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177881E+09 | 0.723544E+09 |
June | 0.565842E+09 | 0.257569E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539672E+09 | 0.339039E+09 |
July | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545688E+09 | 0.245246E+09 |
August | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614187E+09 | 0.172964E+09 |
September | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207684E+09 | 0.461239E+09 |
October | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41118667.06 | 0.140808E+10 |
November | 0.522316E+09 | 0.246796E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 921648.91 | 0.191371E+10 |
December | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250345E+10 |
Annual Sum or Average | 0.659424E+10 | 0.306193E+11 | 0.319458E+11 | 0.222332E+10 | 0.164906E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172964E+09 |
Maximum of Months | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614187E+09 | 0.331131E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10372533.23 | 0.197571E+11 |
February | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47649926.08 | 0.155414E+11 |
March | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30814597.72 | 0.951183E+10 |
April | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45524811.31 | 0.753290E+10 |
May | 0.00 | 0.115516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221797E+09 | 0.577582E+10 |
June | 0.00 | 0.114492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158925E+10 | 0.341022E+10 |
July | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167833E+10 | 0.252340E+10 |
August | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168582E+10 | 0.190592E+10 |
September | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310738E+09 | 0.389776E+10 |
October | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24607825.21 | 0.906495E+10 |
November | 0.00 | 0.108048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72515345.90 | 0.989945E+10 |
December | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275246.08 | 0.154674E+11 |
Annual Sum or Average | 0.135003E+12 | 0.571769E+10 | 0.104288E+12 | ||||||
Minimum of Months | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275246.08 | 0.190592E+10 |
Maximum of Months | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168582E+10 | 0.197571E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137535E+10 | 0.419129E+11 |
February | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199930E+10 | 0.318952E+11 |
March | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156746E+10 | 0.257092E+11 |
April | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.786679E+09 | 0.237410E+11 |
May | 0.00 | 0.265687E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63347281.88 | 0.212551E+11 |
June | 0.00 | 0.263332E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86950304.27 | 0.171796E+11 |
July | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54482042.15 | 0.137743E+11 |
August | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47902158.41 | 0.121205E+11 |
September | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 576043.05 | 0.193661E+11 |
October | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116341E+09 | 0.315290E+11 |
November | 0.00 | 0.248511E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100012E+10 | 0.271118E+11 |
December | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970600E+09 | 0.297449E+11 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | 0.806911E+10 | 0.295340E+12 | |||||
Minimum of Months | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 576043.05 | 0.121205E+11 |
Maximum of Months | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199930E+10 | 0.419129E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1939.55 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 11909.19 | 27-JAN-07:10 |
February | 659.25 | 01-FEB-08:09 | 1939.55 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 164.96 | 26-FEB-13:00 | 13149.91 | 03-FEB-08:00 |
March | 659.25 | 01-MAR-08:09 | 1939.55 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1483.70 | 30-MAR-16:10 | 7457.71 | 06-MAR-08:00 |
April | 659.25 | 01-APR-07:10 | 1939.55 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.42 | 17-APR-16:10 | 8142.60 | 06-APR-06:05 |
May | 659.25 | 01-MAY-07:10 | 1939.55 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2511.24 | 19-MAY-16:10 | 5585.03 | 11-MAY-06:03 |
June | 659.25 | 01-JUN-07:10 | 1939.55 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3972.39 | 06-JUN-17:00 | 4514.04 | 08-JUN-06:01 |
July | 659.25 | 01-JUL-07:10 | 1939.55 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4042.71 | 07-JUL-16:10 | 2080.77 | 28-JUL-17:00 |
August | 659.25 | 01-AUG-07:10 | 1939.55 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4249.76 | 01-AUG-17:00 | 2071.18 | 25-AUG-06:03 |
September | 659.25 | 01-SEP-07:10 | 1939.55 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2741.27 | 07-SEP-16:10 | 4420.51 | 14-SEP-06:03 |
October | 659.25 | 02-OCT-07:10 | 1939.55 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2138.49 | 10-OCT-16:10 | 7658.96 | 26-OCT-06:10 |
November | 659.25 | 01-NOV-07:10 | 1939.55 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.96 | 19-NOV-15:00 | 10183.30 | 22-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1939.55 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 10813.00 | 18-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2071.18 | |||||
Maximum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4249.76 | 13149.91 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.74 | 19-JAN-23:00 | 36856.65 | 07-JAN-18:00 |
February | 0.00 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2327.37 | 26-FEB-13:00 | 41177.74 | 11-FEB-17:40 |
March | 0.00 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1327.37 | 30-MAR-16:00 | 18377.71 | 18-MAR-08:00 |
April | 0.00 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1106.46 | 15-APR-16:00 | 17854.86 | 05-APR-15:05 |
May | 0.00 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3426.53 | 19-MAY-16:00 | 11703.56 | 10-MAY-07:00 |
June | 0.00 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10109.36 | 06-JUN-15:10 | 11294.49 | 07-JUN-07:00 |
July | 0.00 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6088.79 | 10-JUL-15:10 | 9229.10 | 28-JUL-17:00 |
August | 0.00 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8595.28 | 01-AUG-17:00 | 5127.98 | 28-AUG-07:00 |
September | 0.00 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3842.79 | 08-SEP-16:00 | 8870.59 | 28-SEP-17:00 |
October | 0.00 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2002.13 | 10-OCT-16:00 | 18379.49 | 25-OCT-08:00 |
November | 0.00 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2913.37 | 19-NOV-15:00 | 18969.15 | 21-NOV-09:00 |
December | 0.00 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.28 | 24-DEC-10:00 | 32878.48 | 02-DEC-08:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.28 | 5127.98 | |||
Maximum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10109.36 | 41177.74 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23173.88 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20066.40 | 19-JAN-16:00 | 88444.43 | 07-JAN-10:00 |
February | 0.00 | 23173.88 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19881.12 | 16-FEB-17:00 | 88249.52 | 11-FEB-17:00 |
March | 0.00 | 23173.88 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16322.60 | 11-MAR-16:00 | 54546.13 | 18-MAR-09:00 |
April | 0.00 | 23173.88 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10416.99 | 07-APR-15:00 | 68108.56 | 05-APR-11:00 |
May | 0.00 | 23173.88 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.36 | 06-MAY-16:00 | 39422.64 | 10-MAY-08:00 |
June | 0.00 | 23173.88 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2267.62 | 06-JUN-15:00 | 41271.91 | 07-JUN-07:10 |
July | 0.00 | 23173.88 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1107.04 | 22-JUL-10:55 | 33493.42 | 28-JUL-12:10 |
August | 0.00 | 23173.88 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1791.36 | 01-AUG-17:00 | 23172.45 | 31-AUG-09:00 |
September | 0.00 | 23173.88 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 388.14 | 25-SEP-13:55 | 33536.95 | 28-SEP-14:00 |
October | 0.00 | 23173.88 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4339.51 | 10-OCT-16:00 | 62807.02 | 25-OCT-08:00 |
November | 0.00 | 23173.88 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15474.76 | 27-NOV-13:10 | 56551.65 | 20-NOV-09:00 |
December | 0.00 | 23173.88 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13230.79 | 11-DEC-14:00 | 67697.56 | 02-DEC-08:70 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 388.14 | 23172.45 | ||||
Maximum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 20066.40 | 88444.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 421.18 | 21-JAN-13:30 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.56 |
February | 2650.56 | 28-FEB-16:30 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.09 |
March | 5237.72 | 30-MAR-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 462.25 | 0.00 |
April | 20394.12 | 18-APR-05:03 | 290.07 | 2317.39 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 648.82 |
May | 20725.71 | 17-MAY-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.47 |
June | 24554.63 | 08-JUN-05:02 | 362.59 | 2896.74 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 888.60 |
July | 18964.84 | 03-JUL-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.23 |
August | 18810.00 | 26-AUG-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.43 |
September | 22443.84 | 14-SEP-05:02 | 435.11 | 3476.08 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 944.89 |
October | 16723.81 | 11-OCT-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507.95 |
November | 3588.87 | 06-NOV-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.40 |
December | 1087.66 | 13-DEC-13:10 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.29 |
Annual Sum or Average | |||||||||||
Minimum of Months | 421.18 | 290.07 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24554.63 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 462.25 | 944.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4789.55 | 26-JAN-13:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4839.07 |
February | 4001.30 | 02-FEB-13:10 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8397.34 |
March | 5982.46 | 24-MAR-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3450.91 |
April | 54926.89 | 16-APR-16:41 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 | 0.00 |
May | 51462.78 | 19-MAY-20:01 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 829.50 |
June | 62334.72 | 08-JUN-19:11 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 877.22 |
July | 49124.77 | 04-JUL-15:13 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1492.87 | 0.00 |
August | 50014.69 | 25-AUG-17:06 | 0.00 | 5926.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1817.41 | 0.00 |
September | 56890.02 | 14-SEP-17:11 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 966.60 |
October | 12235.97 | 09-OCT-15:15 | 0.00 | 2370.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 621.80 | 0.00 |
November | 6980.49 | 14-NOV-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1257.70 |
December | 5993.13 | 12-DEC-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2267.96 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4001.30 | 0.00 | 2370.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 62334.72 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1817.41 | 8397.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 10905.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11931.81 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8331.11 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6034.21 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12155.01 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6854.48 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8108.28 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8617.25 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3749.51 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10239.32 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16697.45 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16837.58 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32857.53 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3749.51 | |
Maximum of Months | 0.00 | 0.00 | 10905.36 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32857.53 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.681901E+11 | 51387.02 | 07-JAN-13:39 | 0.841823E+11 | 185770.67 | 07-JAN-17:00 |
February | 0.615373E+11 | 52171.94 | 28-FEB-15:30 | 0.546767E+11 | 233992.28 | 12-FEB-06:10 |
March | 0.695260E+11 | 56857.81 | 30-MAR-14:00 | 0.198976E+10 | 34101.55 | 22-MAR-05:19 |
April | 0.656881E+11 | 59026.61 | 17-APR-14:00 | 0.240071E+09 | 12097.98 | 06-APR-06:10 |
May | 0.707429E+11 | 65524.92 | 30-MAY-14:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.786969E+11 | 70215.81 | 06-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.811549E+11 | 72637.05 | 08-JUL-14:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.866630E+11 | 71655.09 | 02-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.721118E+11 | 69211.18 | 06-SEP-13:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.672234E+11 | 60383.61 | 11-OCT-14:09 | 0.204916E+09 | 11321.72 | 26-OCT-06:10 |
November | 0.645320E+11 | 52217.96 | 02-NOV-14:09 | 0.440888E+10 | 49880.93 | 22-NOV-07:19 |
December | 0.677501E+11 | 51481.77 | 12-DEC-14:50 | 0.229421E+11 | 87840.67 | 02-DEC-08:09 |
Annual Sum or Average | 0.853816E+12 | 0.168645E+12 | ||||
Minimum of Months | 0.615373E+11 | 51387.02 | 0.00 | 0.00 | ||
Maximum of Months | 0.866630E+11 | 72637.05 | 0.841823E+11 | 233992.28 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.396181E+11 | 0.982244E+10 | 0.115358E+11 | 0.00 | 0.502500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218875E+10 | 0.00 |
February | 0.362526E+11 | 0.838353E+10 | 0.105871E+11 | 0.00 | 0.430616E+10 | 0.00 | 0.00 | 19412389.04 | 0.00 | 0.00 | 0.00 | 0.198854E+10 | 0.00 |
March | 0.418523E+11 | 0.857286E+10 | 0.123357E+11 | 0.00 | 0.434193E+10 | 0.00 | 0.00 | 0.209049E+09 | 0.00 | 0.00 | 0.00 | 0.221417E+10 | 0.00 |
April | 0.392410E+11 | 0.758835E+10 | 0.114862E+11 | 0.00 | 0.400658E+10 | 0.00 | 0.00 | 0.131008E+10 | 0.00 | 0.00 | 0.00 | 0.205587E+10 | 0.00 |
May | 0.407352E+11 | 0.722483E+10 | 0.119357E+11 | 0.00 | 0.438888E+10 | 0.00 | 0.00 | 0.439305E+10 | 0.00 | 0.00 | 0.00 | 0.206521E+10 | 0.00 |
June | 0.403581E+11 | 0.672122E+10 | 0.118862E+11 | 0.00 | 0.624131E+10 | 0.00 | 0.00 | 0.115289E+11 | 0.00 | 0.00 | 0.00 | 0.196127E+10 | 0.00 |
July | 0.396181E+11 | 0.704686E+10 | 0.115358E+11 | 0.00 | 0.691987E+10 | 0.00 | 0.00 | 0.140829E+11 | 0.00 | 0.00 | 0.00 | 0.195129E+10 | 0.00 |
August | 0.418523E+11 | 0.756184E+10 | 0.123357E+11 | 0.00 | 0.714123E+10 | 0.00 | 0.00 | 0.157792E+11 | 0.00 | 0.00 | 0.00 | 0.199268E+10 | 0.00 |
September | 0.392410E+11 | 0.798973E+10 | 0.114862E+11 | 0.00 | 0.470237E+10 | 0.00 | 0.00 | 0.675882E+10 | 0.00 | 0.00 | 0.00 | 0.193371E+10 | 0.00 |
October | 0.396181E+11 | 0.898939E+10 | 0.115358E+11 | 0.00 | 0.400246E+10 | 0.00 | 0.00 | 0.104360E+10 | 0.00 | 0.00 | 0.00 | 0.203404E+10 | 0.00 |
November | 0.381239E+11 | 0.934154E+10 | 0.110862E+11 | 0.00 | 0.391294E+10 | 0.00 | 0.00 | 42138860.60 | 0.00 | 0.00 | 0.00 | 0.202521E+10 | 0.00 |
December | 0.396181E+11 | 0.999662E+10 | 0.115358E+11 | 0.00 | 0.444162E+10 | 0.00 | 0.00 | 2811312.82 | 0.00 | 0.00 | 0.00 | 0.215514E+10 | 0.00 |
Annual Sum or Average | 0.476129E+12 | 0.992392E+11 | 0.139282E+12 | 0.594304E+11 | 0.00 | 0.551701E+11 | 0.245659E+11 | ||||||
Minimum of Months | 0.362526E+11 | 0.672122E+10 | 0.105871E+11 | 0.00 | 0.391294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193371E+10 | 0.00 |
Maximum of Months | 0.418523E+11 | 0.999662E+10 | 0.123357E+11 | 0.00 | 0.714123E+10 | 0.00 | 0.00 | 0.157792E+11 | 0.00 | 0.00 | 0.00 | 0.221417E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.841823E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.546767E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.198976E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.240071E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.204916E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.440888E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.229421E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168645E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.841823E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35189.04 | 02-JAN-09:09 | 6311.00 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4300.17 | 05-JAN-10:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35189.04 | 01-FEB-09:09 | 6311.00 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 4300.17 | 03-FEB-07:40 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35189.04 | 01-MAR-09:09 | 6311.00 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4037.45 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35189.04 | 01-APR-08:09 | 6311.00 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 4037.45 | 15-APR-16:49 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35189.04 | 01-MAY-08:09 | 6311.00 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 6342.74 | 19-MAY-14:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35189.04 | 01-JUN-08:09 | 6311.00 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 6342.74 | 05-JUN-10:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35189.04 | 01-JUL-08:09 | 6311.00 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6342.74 | 11-JUL-15:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35189.04 | 01-AUG-08:09 | 6311.00 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6342.74 | 03-AUG-11:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35189.04 | 01-SEP-08:09 | 6311.00 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 6342.74 | 05-SEP-16:40 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35189.04 | 02-OCT-08:09 | 6311.00 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 4037.45 | 17-OCT-12:39 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35189.04 | 01-NOV-08:09 | 6311.00 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 4037.45 | 22-NOV-08:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35189.04 | 01-DEC-09:09 | 6311.00 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4300.17 | 04-DEC-08:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35189.04 | 6311.00 | 10112.62 | 0.00 | 4037.45 | 0.00 | 0.00 | |||||
Maximum of Months | 35189.04 | 6311.00 | 10112.62 | 0.00 | 6342.74 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2122.67 | 30-JAN-12:30 | 0.00 |
February | 1098.18 | 28-FEB-15:20 | 0.00 | 0.00 | 0.00 | 2121.09 | 06-FEB-12:39 | 0.00 |
March | 5750.76 | 30-MAR-14:00 | 0.00 | 0.00 | 0.00 | 2050.59 | 01-MAR-12:00 | 0.00 |
April | 8331.37 | 16-APR-12:39 | 0.00 | 0.00 | 0.00 | 1805.64 | 01-APR-11:09 | 0.00 |
May | 12506.63 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1779.74 | 01-MAY-11:09 | 0.00 |
June | 18808.90 | 06-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1753.54 | 01-JUN-11:09 | 0.00 |
July | 20029.12 | 07-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1735.45 | 01-JUL-11:09 | 0.00 |
August | 20698.82 | 01-AUG-16:00 | 0.00 | 0.00 | 0.00 | 1733.71 | 31-AUG-11:50 | 0.00 |
September | 16835.59 | 07-SEP-15:50 | 0.00 | 0.00 | 0.00 | 1750.65 | 30-SEP-11:00 | 0.00 |
October | 9343.63 | 11-OCT-13:00 | 0.00 | 0.00 | 0.00 | 1776.87 | 31-OCT-11:50 | 0.00 |
November | 1149.50 | 02-NOV-13:00 | 0.00 | 0.00 | 0.00 | 1803.23 | 30-NOV-12:09 | 0.00 |
December | 408.45 | 12-DEC-14:50 | 0.00 | 0.00 | 0.00 | 1964.89 | 22-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1733.71 | 0.00 | ||
Maximum of Months | 20698.82 | 0.00 | 0.00 | 0.00 | 2122.67 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 51387.02 | 07-JAN-13:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4300.17 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52171.94 | 28-FEB-15:30 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4037.45 | 0.00 | 0.00 | 1048.85 | 0.00 |
March | 56857.81 | 30-MAR-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4037.45 | 0.00 | 0.00 | 5750.76 | 0.00 |
April | 59026.61 | 17-APR-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4037.45 | 0.00 | 0.00 | 7931.96 | 0.00 |
May | 65524.92 | 30-MAY-14:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6342.74 | 0.00 | 0.00 | 12155.91 | 0.00 |
June | 70215.81 | 06-JUN-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6342.74 | 0.00 | 0.00 | 16851.51 | 0.00 |
July | 72637.05 | 08-JUL-14:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6342.74 | 0.00 | 0.00 | 19287.43 | 0.00 |
August | 71655.09 | 02-AUG-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6342.74 | 0.00 | 0.00 | 18309.27 | 0.00 |
September | 69211.18 | 06-SEP-13:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6342.74 | 0.00 | 0.00 | 15885.06 | 0.00 |
October | 60383.61 | 11-OCT-14:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4037.45 | 0.00 | 0.00 | 9317.02 | 0.00 |
November | 52217.96 | 02-NOV-14:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4037.45 | 0.00 | 0.00 | 1135.64 | 0.00 |
December | 51481.77 | 12-DEC-14:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4037.45 | 0.00 | 0.00 | 408.45 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 51387.02 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4037.45 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 72637.05 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6342.74 | 0.00 | 0.00 | 19287.43 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 185770.67 | 07-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 233992.28 | 12-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 34101.55 | 22-MAR-05:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 12097.98 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 11321.72 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 49880.93 | 22-NOV-07:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 87840.67 | 02-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 233992.28 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.50 | 18.46 | 8.33 | 19.36 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8.17 | 18.54 | 6.17 | 19.70 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.33 | 20.32 | 2.33 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.50 | 20.44 | 0.50 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.51 | 0.50 | 24.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 24.68 | 5.50 | 24.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 25.08 | 7.33 | 24.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 25.34 | 8.50 | 24.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.73 | 4.00 | 24.73 |
October | 0.33 | 20.50 | 0.33 | 20.50 | 0.17 | 24.54 | 0.17 | 24.54 |
November | 2.50 | 20.26 | 2.50 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.83 | 19.91 | 6.83 | 19.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.17 | 19.14 | 27.00 | 19.78 | 27.00 | 25.02 | 26.00 | 24.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.50 | 20.50 | 8.33 | 20.50 | 9.17 | 25.34 | 8.50 | 24.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 82.67 | 14.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 44.33 | 14.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.50 | 14.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.32 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.54 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 | 27.58 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 27.55 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.35 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8.50 | 14.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 50.83 | 14.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 187.83 | 14.46 | 0.00 | 86.33 | 27.53 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.67 | 14.89 | 0.00 | 0.00 | 30.50 | 27.58 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.00 | 9.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 9.40 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 9.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.16 | 275.83 | 21.06 | 275.83 | 21.06 |
February | 276.00 | 21.58 | 205.00 | 21.10 | 205.00 | 21.10 |
March | 305.83 | 22.50 | 104.83 | 21.22 | 102.83 | 21.16 |
April | 189.50 | 23.22 | 67.83 | 23.18 | 21.67 | 21.67 |
May | 76.83 | 23.63 | 213.83 | 23.89 | 34.00 | 23.89 |
June | 21.50 | 24.05 | 287.33 | 23.91 | 18.00 | 24.10 |
July | 34.50 | 24.05 | 299.83 | 23.93 | 34.50 | 24.05 |
August | 38.67 | 24.15 | 324.00 | 23.93 | 38.67 | 24.15 |
September | 7.67 | 24.11 | 282.33 | 23.91 | 6.33 | 24.23 |
October | 183.50 | 23.13 | 90.83 | 23.56 | 33.00 | 22.99 |
November | 286.67 | 22.45 | 111.83 | 21.27 | 111.33 | 21.26 |
December | 300.00 | 21.48 | 240.00 | 21.20 | 240.00 | 21.20 |
Annual Sum or Average | 2020.67 | 22.26 | 2503.50 | 22.85 | 1121.17 | 21.55 |
Minimum of Months | 7.67 | 21.16 | 67.83 | 21.06 | 6.33 | 21.06 |
Maximum of Months | 305.83 | 24.15 | 324.00 | 23.93 | 275.83 | 24.23 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 70972952.71 | 19412389.04 | 12.83 | 70972952.71 | 0.00 | 0.00 | 0.23 | 28-FEB-15:20 | 0.00 | 01-FEB-00:10 | 4039.27 | 28-FEB-15:20 | 4039.27 | 28-FEB-15:20 | 0.00 | 28-FEB-12:40 | 1098.18 | 28-FEB-15:20 | 0.00 | 01-FEB-00:10 |
March | 0.596848E+09 | 0.162728E+09 | 74.42 | 0.495208E+09 | 0.101640E+09 | 0.00 | 0.43 | 30-MAR-16:00 | 0.00 | 01-MAR-00:10 | 7689.56 | 30-MAR-16:00 | 6949.37 | 30-MAR-16:00 | 1772.18 | 30-MAR-11:50 | 2150.38 | 30-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.242137E+10 | 0.658922E+09 | 162.28 | 0.211845E+10 | 0.302918E+09 | 0.00 | 1.00 | 18-APR-05:03 | 0.00 | 01-APR-00:10 | 21157.25 | 22-APR-05:05 | 13694.08 | 18-APR-05:03 | 8913.20 | 22-APR-05:05 | 4988.73 | 22-APR-05:05 | 0.00 | 01-APR-00:10 |
May | 0.581729E+10 | 0.156604E+10 | 234.22 | 0.462281E+10 | 0.119448E+10 | 0.00 | 1.00 | 05-MAY-05:03 | 0.00 | 01-MAY-00:10 | 23198.97 | 31-MAY-05:01 | 16805.41 | 19-MAY-05:04 | 12416.55 | 26-MAY-05:55 | 5371.71 | 31-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.112343E+11 | 0.305597E+10 | 295.81 | 0.864379E+10 | 0.259050E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 25066.87 | 26-JUN-05:01 | 18154.34 | 12-JUN-05:01 | 13693.70 | 23-JUN-05:03 | 5659.55 | 26-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.125349E+11 | 0.341689E+10 | 299.02 | 0.923057E+10 | 0.330431E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 25451.74 | 27-JUL-05:01 | 18045.40 | 18-JUL-05:01 | 15206.95 | 27-JUL-05:02 | 5711.57 | 27-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.145993E+11 | 0.393110E+10 | 324.18 | 0.105758E+11 | 0.402342E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 25835.39 | 12-AUG-05:01 | 17948.68 | 26-AUG-05:04 | 15366.30 | 21-AUG-05:04 | 5760.96 | 12-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.859819E+10 | 0.227545E+10 | 260.72 | 0.658110E+10 | 0.201710E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 24449.63 | 05-SEP-05:01 | 18760.46 | 16-SEP-05:01 | 13027.99 | 05-SEP-05:05 | 5570.93 | 05-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.235824E+10 | 0.622434E+09 | 153.88 | 0.175656E+10 | 0.601688E+09 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 24829.77 | 19-OCT-05:01 | 12575.51 | 11-OCT-05:01 | 15043.92 | 19-OCT-05:01 | 5626.26 | 19-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.155329E+09 | 42138860.60 | 54.25 | 0.122463E+09 | 32866128.53 | 0.00 | 0.23 | 02-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4303.51 | 02-NOV-14:00 | 3189.11 | 02-NOV-14:00 | 1415.66 | 04-NOV-16:00 | 1149.50 | 02-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 10243403.04 | 2811312.82 | 4.17 | 7740599.31 | 2502803.73 | 0.00 | 0.08 | 12-DEC-15:00 | 0.00 | 01-DEC-00:10 | 1491.83 | 12-DEC-14:50 | 1152.14 | 12-DEC-15:00 | 370.15 | 12-DEC-14:30 | 408.45 | 12-DEC-14:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.583969E+11 | 0.157539E+11 | 1875.79 | 0.442255E+11 | 0.141714E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.145993E+11 | 0.393110E+10 | 324.18 | 0.105758E+11 | 0.402342E+10 | 0.00 | 1.00 | 0.00 | 25835.39 | 18760.46 | 15366.30 | 5760.96 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.152588E+09 | 46321267.40 | 5.17 | 0.124589E+09 | 27998945.07 | 0.00 | 0.22 | 30-MAR-15:00 | 0.00 | 01-MAR-00:10 | 12204.15 | 30-MAR-15:00 | 10563.15 | 30-MAR-15:00 | 2222.86 | 30-MAR-13:40 | 3708.59 | 30-MAR-15:00 | 0.00 | 01-MAR-00:10 |
April | 0.216204E+10 | 0.651162E+09 | 61.44 | 0.195294E+10 | 0.209096E+09 | 0.00 | 1.00 | 16-APR-11:51 | 0.00 | 01-APR-00:10 | 62192.61 | 16-APR-16:41 | 59777.33 | 16-APR-12:40 | 4116.90 | 16-APR-16:50 | 16662.74 | 16-APR-12:40 | 0.00 | 01-APR-00:10 |
May | 0.955864E+10 | 0.282701E+10 | 177.15 | 0.741165E+10 | 0.214699E+10 | 0.00 | 1.00 | 19-MAY-17:08 | 0.00 | 01-MAY-00:10 | 72898.51 | 21-MAY-11:21 | 54842.02 | 19-MAY-17:43 | 30608.32 | 21-MAY-11:26 | 18311.73 | 29-MAY-10:51 | 0.00 | 01-MAY-00:10 |
June | 0.284602E+11 | 0.847293E+10 | 319.18 | 0.208183E+11 | 0.764184E+10 | 0.00 | 1.00 | 02-JUN-19:11 | 0.00 | 01-JUN-00:10 | 76190.16 | 25-JUN-08:21 | 59836.88 | 08-JUN-17:10 | 41743.37 | 22-JUN-20:45 | 18897.23 | 25-JUN-13:02 | 0.00 | 01-JUN-00:10 |
July | 0.356339E+11 | 0.106660E+11 | 375.94 | 0.252003E+11 | 0.104336E+11 | 0.00 | 1.00 | 02-JUL-11:23 | 0.00 | 01-JUL-00:10 | 80306.79 | 30-JUL-10:41 | 52648.96 | 03-JUL-18:23 | 44868.70 | 30-JUL-10:41 | 19426.52 | 30-JUL-10:41 | 0.00 | 01-JUL-00:10 |
August | 0.402266E+11 | 0.118481E+11 | 418.59 | 0.274841E+11 | 0.127425E+11 | 0.00 | 1.00 | 01-AUG-17:06 | 0.00 | 01-AUG-00:10 | 82271.70 | 20-AUG-07:41 | 54657.05 | 25-AUG-17:43 | 52046.05 | 20-AUG-07:41 | 19270.24 | 20-AUG-07:41 | 0.00 | 01-AUG-00:10 |
September | 0.154052E+11 | 0.448337E+10 | 230.57 | 0.109742E+11 | 0.443100E+10 | 0.00 | 1.00 | 03-SEP-11:01 | 0.00 | 01-SEP-00:10 | 78313.47 | 17-SEP-11:01 | 55586.84 | 14-SEP-17:11 | 42162.24 | 10-SEP-08:51 | 19029.75 | 17-SEP-11:01 | 0.00 | 01-SEP-00:10 |
October | 0.145017E+10 | 0.421166E+09 | 57.92 | 0.957617E+09 | 0.492550E+09 | 0.00 | 0.36 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 | 22434.26 | 11-OCT-14:00 | 15699.37 | 10-OCT-14:00 | 8088.02 | 18-OCT-14:10 | 6534.63 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.133049E+12 | 0.394161E+11 | 1645.96 | 0.949237E+11 | 0.381256E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.402266E+11 | 0.118481E+11 | 418.59 | 0.274841E+11 | 0.127425E+11 | 0.00 | 1.00 | 0.00 | 82271.70 | 59836.88 | 52046.05 | 19426.52 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.67 | 24.11 | 27.55 | 40.08 | 168.14 | 0.00 | 0.00 | 744.00 |
February | 58.86 | 27.52 | 31.34 | 62.01 | 136.53 | 0.00 | 0.00 | 672.00 |
March | 86.49 | 41.69 | 44.80 | 111.20 | 88.56 | 0.00 | 0.00 | 744.00 |
April | 97.26 | 44.37 | 52.88 | 140.35 | 83.21 | 0.00 | 0.00 | 720.00 |
May | 98.03 | 37.14 | 60.89 | 152.92 | 63.40 | 0.00 | 0.00 | 744.00 |
June | 103.22 | 39.83 | 63.39 | 184.15 | 48.14 | 0.00 | 0.00 | 720.00 |
July | 97.07 | 35.93 | 61.14 | 179.67 | 37.77 | 0.00 | 0.00 | 744.00 |
August | 95.11 | 35.50 | 59.62 | 178.40 | 34.19 | 0.00 | 0.00 | 744.00 |
September | 77.75 | 32.44 | 45.31 | 121.80 | 62.64 | 0.00 | 0.00 | 720.00 |
October | 68.87 | 35.64 | 33.23 | 90.46 | 105.44 | 0.00 | 0.00 | 744.00 |
November | 54.90 | 24.50 | 30.40 | 60.89 | 118.66 | 0.00 | 0.00 | 720.00 |
December | 45.69 | 20.08 | 25.61 | 38.44 | 139.19 | 0.33 | 0.00 | 744.00 |
Annual Sum or Average | 78.01 | 33.25 | 44.75 | 113.64 | 90.24 | 0.33 | 0.00 | 8760.00 |
Minimum of Months | 45.69 | 20.08 | 25.61 | 38.44 | 34.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.22 | 44.37 | 63.39 | 184.15 | 168.14 | 0.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.67 | 24.11 | 27.55 | 40.08 | 168.14 | 0.00 | 0.00 | 744.00 |
February | 58.86 | 27.52 | 31.34 | 62.01 | 136.53 | 0.00 | 0.00 | 672.00 |
March | 86.49 | 41.69 | 44.80 | 111.20 | 88.56 | 0.00 | 0.00 | 744.00 |
April | 97.26 | 44.37 | 52.88 | 140.35 | 83.21 | 0.00 | 0.00 | 720.00 |
May | 98.03 | 37.14 | 60.89 | 152.92 | 63.40 | 0.00 | 0.00 | 744.00 |
June | 103.22 | 39.83 | 63.39 | 184.15 | 48.14 | 0.00 | 0.00 | 720.00 |
July | 97.07 | 35.93 | 61.14 | 179.67 | 37.77 | 0.00 | 0.00 | 744.00 |
August | 95.11 | 35.50 | 59.62 | 178.40 | 34.19 | 0.00 | 0.00 | 744.00 |
September | 77.75 | 32.44 | 45.31 | 121.80 | 62.64 | 0.00 | 0.00 | 720.00 |
October | 68.87 | 35.64 | 33.23 | 90.46 | 105.44 | 0.00 | 0.00 | 744.00 |
November | 54.90 | 24.50 | 30.40 | 60.89 | 118.66 | 0.00 | 0.00 | 720.00 |
December | 45.69 | 20.08 | 25.61 | 38.44 | 139.19 | 0.33 | 0.00 | 744.00 |
Annual Sum or Average | 78.01 | 33.25 | 44.75 | 113.64 | 90.24 | 0.33 | 0.00 | 8760.00 |
Minimum of Months | 45.69 | 20.08 | 25.61 | 38.44 | 34.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.22 | 44.37 | 63.39 | 184.15 | 168.14 | 0.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.25 | 0.00 | 13.25 | 2.21 | 108.56 | 0.00 | 0.00 | 744.00 |
February | 14.68 | 0.00 | 14.68 | 6.69 | 86.41 | 0.00 | 0.00 | 672.00 |
March | 20.62 | 0.00 | 20.62 | 13.47 | 54.57 | 0.00 | 0.00 | 744.00 |
April | 24.97 | 0.14 | 24.83 | 25.44 | 49.99 | 0.00 | 0.00 | 720.00 |
May | 29.87 | 0.98 | 28.89 | 37.01 | 36.48 | 0.00 | 0.00 | 744.00 |
June | 32.80 | 2.15 | 30.65 | 54.29 | 26.49 | 0.00 | 0.00 | 720.00 |
July | 31.04 | 1.58 | 29.46 | 54.96 | 21.09 | 0.00 | 0.00 | 744.00 |
August | 27.63 | 0.37 | 27.26 | 51.52 | 19.62 | 0.00 | 0.00 | 744.00 |
September | 20.83 | 0.01 | 20.82 | 26.60 | 37.40 | 0.00 | 0.00 | 720.00 |
October | 15.83 | 0.00 | 15.83 | 10.56 | 63.94 | 0.00 | 0.00 | 744.00 |
November | 14.16 | 0.00 | 14.16 | 6.23 | 72.77 | 0.00 | 0.00 | 720.00 |
December | 12.24 | 0.00 | 12.24 | 1.86 | 87.23 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 21.53 | 0.44 | 21.09 | 24.34 | 55.22 | 0.50 | 0.00 | 8760.00 |
Minimum of Months | 12.24 | 0.00 | 12.24 | 1.86 | 19.62 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 32.80 | 2.15 | 30.65 | 54.96 | 108.56 | 0.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.24 | 0.00 | 13.24 | 2.21 | 108.56 | 0.00 | 0.00 | 744.00 |
February | 14.68 | 0.00 | 14.68 | 6.69 | 86.41 | 0.00 | 0.00 | 672.00 |
March | 20.62 | 0.00 | 20.62 | 13.47 | 54.57 | 0.00 | 0.00 | 744.00 |
April | 24.97 | 0.14 | 24.83 | 25.44 | 49.99 | 0.00 | 0.00 | 720.00 |
May | 29.87 | 0.98 | 28.89 | 37.00 | 36.48 | 0.00 | 0.00 | 744.00 |
June | 32.80 | 2.15 | 30.65 | 54.29 | 26.49 | 0.00 | 0.00 | 720.00 |
July | 31.04 | 1.58 | 29.46 | 54.96 | 21.09 | 0.00 | 0.00 | 744.00 |
August | 27.63 | 0.37 | 27.25 | 51.52 | 19.62 | 0.00 | 0.00 | 744.00 |
September | 20.83 | 0.01 | 20.82 | 26.60 | 37.40 | 0.00 | 0.00 | 720.00 |
October | 15.83 | 0.00 | 15.83 | 10.56 | 63.94 | 0.00 | 0.00 | 744.00 |
November | 14.16 | 0.00 | 14.16 | 6.23 | 72.77 | 0.00 | 0.00 | 720.00 |
December | 12.24 | 0.00 | 12.24 | 1.86 | 87.23 | 0.50 | 0.00 | 744.00 |
Annual Sum or Average | 21.53 | 0.44 | 21.09 | 24.34 | 55.22 | 0.50 | 0.00 | 8760.00 |
Minimum of Months | 12.24 | 0.00 | 12.24 | 1.86 | 19.62 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 32.80 | 2.15 | 30.65 | 54.96 | 108.56 | 0.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.74 | 18.16 | 14.58 | 30.35 | 35.65 | 18.33 | 0.00 | 744.00 |
February | 40.01 | 24.50 | 15.51 | 44.06 | 30.39 | 35.00 | 0.00 | 672.00 |
March | 59.48 | 36.47 | 23.02 | 71.62 | 26.83 | 0.00 | 0.00 | 744.00 |
April | 74.54 | 46.02 | 28.52 | 94.43 | 28.74 | 0.00 | 0.00 | 720.00 |
May | 83.23 | 48.13 | 35.10 | 106.75 | 25.14 | 0.00 | 0.00 | 744.00 |
June | 88.91 | 52.47 | 36.44 | 115.66 | 25.00 | 0.00 | 0.00 | 720.00 |
July | 82.86 | 46.99 | 35.87 | 108.22 | 21.82 | 0.00 | 0.00 | 744.00 |
August | 76.27 | 41.83 | 34.44 | 99.78 | 21.48 | 0.00 | 0.00 | 744.00 |
September | 55.98 | 30.93 | 25.05 | 65.74 | 29.82 | 0.00 | 0.00 | 720.00 |
October | 48.59 | 32.73 | 15.86 | 54.90 | 34.67 | 0.00 | 0.00 | 744.00 |
November | 35.01 | 19.40 | 15.61 | 35.78 | 33.83 | 16.00 | 0.00 | 720.00 |
December | 28.92 | 15.52 | 13.40 | 27.04 | 31.45 | 31.00 | 0.00 | 744.00 |
Annual Sum or Average | 58.98 | 34.48 | 24.50 | 71.34 | 28.72 | 100.33 | 0.00 | 8760.00 |
Minimum of Months | 28.92 | 15.52 | 13.40 | 27.04 | 21.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 88.91 | 52.47 | 36.44 | 115.66 | 35.65 | 35.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.74 | 18.16 | 14.58 | 30.35 | 35.65 | 18.33 | 0.00 | 744.00 |
February | 40.01 | 24.50 | 15.51 | 44.06 | 30.39 | 35.00 | 0.00 | 672.00 |
March | 59.48 | 36.47 | 23.02 | 71.62 | 26.83 | 0.00 | 0.00 | 744.00 |
April | 74.54 | 46.02 | 28.52 | 94.43 | 28.74 | 0.00 | 0.00 | 720.00 |
May | 83.23 | 48.13 | 35.10 | 106.75 | 25.14 | 0.00 | 0.00 | 744.00 |
June | 88.91 | 52.47 | 36.44 | 115.66 | 25.00 | 0.00 | 0.00 | 720.00 |
July | 82.86 | 46.99 | 35.87 | 108.22 | 21.82 | 0.00 | 0.00 | 744.00 |
August | 76.27 | 41.83 | 34.44 | 99.78 | 21.48 | 0.00 | 0.00 | 744.00 |
September | 55.98 | 30.93 | 25.05 | 65.74 | 29.82 | 0.00 | 0.00 | 720.00 |
October | 48.59 | 32.73 | 15.86 | 54.90 | 34.67 | 0.00 | 0.00 | 744.00 |
November | 35.01 | 19.40 | 15.61 | 35.78 | 33.83 | 16.00 | 0.00 | 720.00 |
December | 28.92 | 15.52 | 13.40 | 27.04 | 31.45 | 31.00 | 0.00 | 744.00 |
Annual Sum or Average | 58.98 | 34.48 | 24.50 | 71.34 | 28.72 | 100.33 | 0.00 | 8760.00 |
Minimum of Months | 28.92 | 15.52 | 13.40 | 27.04 | 21.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 88.91 | 52.47 | 36.44 | 115.66 | 35.65 | 35.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.74 | 18.16 | 14.58 | 30.35 | 35.65 | 18.33 | 0.00 | 744.00 |
February | 40.01 | 24.50 | 15.51 | 44.06 | 30.39 | 35.00 | 0.00 | 672.00 |
March | 59.48 | 36.47 | 23.02 | 71.62 | 26.83 | 0.00 | 0.00 | 744.00 |
April | 74.54 | 46.02 | 28.52 | 94.43 | 28.74 | 0.00 | 0.00 | 720.00 |
May | 83.23 | 48.13 | 35.10 | 106.75 | 25.14 | 0.00 | 0.00 | 744.00 |
June | 88.91 | 52.47 | 36.44 | 115.66 | 25.00 | 0.00 | 0.00 | 720.00 |
July | 82.86 | 46.99 | 35.87 | 108.22 | 21.82 | 0.00 | 0.00 | 744.00 |
August | 76.27 | 41.83 | 34.44 | 99.78 | 21.48 | 0.00 | 0.00 | 744.00 |
September | 55.98 | 30.93 | 25.05 | 65.74 | 29.82 | 0.00 | 0.00 | 720.00 |
October | 48.59 | 32.73 | 15.86 | 54.90 | 34.67 | 0.00 | 0.00 | 744.00 |
November | 35.01 | 19.40 | 15.61 | 35.78 | 33.83 | 16.00 | 0.00 | 720.00 |
December | 28.92 | 15.52 | 13.40 | 27.04 | 31.45 | 31.00 | 0.00 | 744.00 |
Annual Sum or Average | 58.98 | 34.48 | 24.50 | 71.34 | 28.72 | 100.33 | 0.00 | 8760.00 |
Minimum of Months | 28.92 | 15.52 | 13.40 | 27.04 | 21.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 88.91 | 52.47 | 36.44 | 115.66 | 35.65 | 35.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.74 | 18.16 | 14.58 | 30.35 | 35.65 | 18.33 | 0.00 | 744.00 |
February | 40.01 | 24.50 | 15.51 | 44.06 | 30.39 | 35.00 | 0.00 | 672.00 |
March | 59.48 | 36.47 | 23.02 | 71.62 | 26.83 | 0.00 | 0.00 | 744.00 |
April | 74.54 | 46.02 | 28.52 | 94.43 | 28.74 | 0.00 | 0.00 | 720.00 |
May | 83.23 | 48.13 | 35.10 | 106.75 | 25.14 | 0.00 | 0.00 | 744.00 |
June | 88.91 | 52.47 | 36.44 | 115.66 | 25.00 | 0.00 | 0.00 | 720.00 |
July | 82.86 | 46.99 | 35.87 | 108.22 | 21.82 | 0.00 | 0.00 | 744.00 |
August | 76.27 | 41.83 | 34.44 | 99.78 | 21.48 | 0.00 | 0.00 | 744.00 |
September | 55.98 | 30.93 | 25.05 | 65.74 | 29.82 | 0.00 | 0.00 | 720.00 |
October | 48.59 | 32.73 | 15.86 | 54.90 | 34.67 | 0.00 | 0.00 | 744.00 |
November | 35.01 | 19.40 | 15.61 | 35.78 | 33.83 | 16.00 | 0.00 | 720.00 |
December | 28.92 | 15.52 | 13.40 | 27.04 | 31.45 | 31.00 | 0.00 | 744.00 |
Annual Sum or Average | 58.98 | 34.48 | 24.50 | 71.34 | 28.72 | 100.33 | 0.00 | 8760.00 |
Minimum of Months | 28.92 | 15.52 | 13.40 | 27.04 | 21.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 88.91 | 52.47 | 36.44 | 115.66 | 35.65 | 35.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.74 | 18.16 | 14.58 | 30.35 | 35.65 | 18.33 | 0.00 | 744.00 |
February | 40.01 | 24.50 | 15.51 | 44.06 | 30.39 | 35.00 | 0.00 | 672.00 |
March | 59.48 | 36.47 | 23.02 | 71.62 | 26.83 | 0.00 | 0.00 | 744.00 |
April | 74.54 | 46.02 | 28.52 | 94.43 | 28.74 | 0.00 | 0.00 | 720.00 |
May | 83.23 | 48.13 | 35.10 | 106.75 | 25.14 | 0.00 | 0.00 | 744.00 |
June | 88.91 | 52.47 | 36.44 | 115.66 | 25.00 | 0.00 | 0.00 | 720.00 |
July | 82.86 | 46.99 | 35.87 | 108.22 | 21.82 | 0.00 | 0.00 | 744.00 |
August | 76.27 | 41.83 | 34.44 | 99.78 | 21.48 | 0.00 | 0.00 | 744.00 |
September | 55.98 | 30.93 | 25.05 | 65.74 | 29.82 | 0.00 | 0.00 | 720.00 |
October | 48.59 | 32.73 | 15.86 | 54.90 | 34.67 | 0.00 | 0.00 | 744.00 |
November | 35.01 | 19.40 | 15.61 | 35.78 | 33.83 | 16.00 | 0.00 | 720.00 |
December | 28.92 | 15.52 | 13.40 | 27.04 | 31.45 | 31.00 | 0.00 | 744.00 |
Annual Sum or Average | 58.98 | 34.48 | 24.50 | 71.34 | 28.72 | 100.33 | 0.00 | 8760.00 |
Minimum of Months | 28.92 | 15.52 | 13.40 | 27.04 | 21.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 88.91 | 52.47 | 36.44 | 115.66 | 35.65 | 35.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.74 | 18.16 | 14.58 | 30.35 | 35.65 | 18.33 | 0.00 | 744.00 |
February | 40.01 | 24.50 | 15.51 | 44.06 | 30.39 | 35.00 | 0.00 | 672.00 |
March | 59.48 | 36.47 | 23.02 | 71.62 | 26.83 | 0.00 | 0.00 | 744.00 |
April | 74.54 | 46.02 | 28.52 | 94.43 | 28.74 | 0.00 | 0.00 | 720.00 |
May | 83.23 | 48.13 | 35.10 | 106.75 | 25.14 | 0.00 | 0.00 | 744.00 |
June | 88.91 | 52.47 | 36.44 | 115.66 | 25.00 | 0.00 | 0.00 | 720.00 |
July | 82.86 | 46.99 | 35.87 | 108.22 | 21.82 | 0.00 | 0.00 | 744.00 |
August | 76.27 | 41.83 | 34.44 | 99.78 | 21.48 | 0.00 | 0.00 | 744.00 |
September | 55.98 | 30.93 | 25.05 | 65.74 | 29.82 | 0.00 | 0.00 | 720.00 |
October | 48.59 | 32.73 | 15.86 | 54.90 | 34.67 | 0.00 | 0.00 | 744.00 |
November | 35.01 | 19.40 | 15.61 | 35.78 | 33.83 | 16.00 | 0.00 | 720.00 |
December | 28.92 | 15.52 | 13.40 | 27.04 | 31.45 | 31.00 | 0.00 | 744.00 |
Annual Sum or Average | 58.98 | 34.48 | 24.50 | 71.34 | 28.72 | 100.33 | 0.00 | 8760.00 |
Minimum of Months | 28.92 | 15.52 | 13.40 | 27.04 | 21.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 88.91 | 52.47 | 36.44 | 115.66 | 35.65 | 35.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.74 | 18.16 | 14.58 | 30.35 | 35.65 | 18.33 | 0.00 | 744.00 |
February | 40.01 | 24.50 | 15.51 | 44.06 | 30.39 | 35.00 | 0.00 | 672.00 |
March | 59.48 | 36.47 | 23.02 | 71.62 | 26.83 | 0.00 | 0.00 | 744.00 |
April | 74.54 | 46.02 | 28.52 | 94.43 | 28.74 | 0.00 | 0.00 | 720.00 |
May | 83.23 | 48.13 | 35.10 | 106.75 | 25.14 | 0.00 | 0.00 | 744.00 |
June | 88.91 | 52.47 | 36.44 | 115.66 | 25.00 | 0.00 | 0.00 | 720.00 |
July | 82.86 | 46.99 | 35.87 | 108.22 | 21.82 | 0.00 | 0.00 | 744.00 |
August | 76.27 | 41.83 | 34.44 | 99.78 | 21.48 | 0.00 | 0.00 | 744.00 |
September | 55.98 | 30.93 | 25.05 | 65.74 | 29.82 | 0.00 | 0.00 | 720.00 |
October | 48.59 | 32.73 | 15.86 | 54.90 | 34.67 | 0.00 | 0.00 | 744.00 |
November | 35.01 | 19.40 | 15.61 | 35.78 | 33.83 | 16.00 | 0.00 | 720.00 |
December | 28.92 | 15.52 | 13.40 | 27.04 | 31.45 | 31.00 | 0.00 | 744.00 |
Annual Sum or Average | 58.98 | 34.48 | 24.50 | 71.34 | 28.72 | 100.33 | 0.00 | 8760.00 |
Minimum of Months | 28.92 | 15.52 | 13.40 | 27.04 | 21.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 88.91 | 52.47 | 36.44 | 115.66 | 35.65 | 35.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.74 | 18.16 | 14.58 | 30.35 | 35.65 | 18.33 | 0.00 | 744.00 |
February | 40.01 | 24.50 | 15.51 | 44.06 | 30.39 | 35.00 | 0.00 | 672.00 |
March | 59.48 | 36.47 | 23.02 | 71.62 | 26.83 | 0.00 | 0.00 | 744.00 |
April | 74.54 | 46.02 | 28.52 | 94.43 | 28.74 | 0.00 | 0.00 | 720.00 |
May | 83.23 | 48.13 | 35.10 | 106.75 | 25.14 | 0.00 | 0.00 | 744.00 |
June | 88.91 | 52.47 | 36.44 | 115.66 | 25.00 | 0.00 | 0.00 | 720.00 |
July | 82.86 | 46.99 | 35.87 | 108.22 | 21.82 | 0.00 | 0.00 | 744.00 |
August | 76.27 | 41.83 | 34.44 | 99.78 | 21.48 | 0.00 | 0.00 | 744.00 |
September | 55.98 | 30.93 | 25.05 | 65.74 | 29.82 | 0.00 | 0.00 | 720.00 |
October | 48.59 | 32.73 | 15.86 | 54.90 | 34.67 | 0.00 | 0.00 | 744.00 |
November | 35.01 | 19.40 | 15.61 | 35.78 | 33.83 | 16.00 | 0.00 | 720.00 |
December | 28.92 | 15.52 | 13.40 | 27.04 | 31.45 | 31.00 | 0.00 | 744.00 |
Annual Sum or Average | 58.98 | 34.48 | 24.50 | 71.34 | 28.72 | 100.33 | 0.00 | 8760.00 |
Minimum of Months | 28.92 | 15.52 | 13.40 | 27.04 | 21.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 88.91 | 52.47 | 36.44 | 115.66 | 35.65 | 35.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.74 | 18.16 | 14.58 | 30.35 | 35.65 | 18.33 | 0.00 | 744.00 |
February | 40.01 | 24.50 | 15.51 | 44.06 | 30.39 | 35.00 | 0.00 | 672.00 |
March | 59.48 | 36.47 | 23.02 | 71.62 | 26.83 | 0.00 | 0.00 | 744.00 |
April | 74.54 | 46.02 | 28.52 | 94.43 | 28.74 | 0.00 | 0.00 | 720.00 |
May | 83.23 | 48.13 | 35.10 | 106.75 | 25.14 | 0.00 | 0.00 | 744.00 |
June | 88.91 | 52.47 | 36.44 | 115.66 | 25.00 | 0.00 | 0.00 | 720.00 |
July | 82.86 | 46.99 | 35.87 | 108.22 | 21.82 | 0.00 | 0.00 | 744.00 |
August | 76.27 | 41.83 | 34.44 | 99.78 | 21.48 | 0.00 | 0.00 | 744.00 |
September | 55.98 | 30.93 | 25.05 | 65.74 | 29.82 | 0.00 | 0.00 | 720.00 |
October | 48.59 | 32.73 | 15.86 | 54.90 | 34.67 | 0.00 | 0.00 | 744.00 |
November | 35.01 | 19.40 | 15.61 | 35.78 | 33.83 | 16.00 | 0.00 | 720.00 |
December | 28.92 | 15.52 | 13.40 | 27.04 | 31.45 | 31.00 | 0.00 | 744.00 |
Annual Sum or Average | 58.98 | 34.48 | 24.50 | 71.34 | 28.72 | 100.33 | 0.00 | 8760.00 |
Minimum of Months | 28.92 | 15.52 | 13.40 | 27.04 | 21.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 88.91 | 52.47 | 36.44 | 115.66 | 35.65 | 35.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.74 | 18.16 | 14.58 | 30.35 | 35.65 | 18.33 | 0.00 | 744.00 |
February | 40.01 | 24.50 | 15.51 | 44.06 | 30.39 | 35.00 | 0.00 | 672.00 |
March | 59.48 | 36.47 | 23.02 | 71.62 | 26.83 | 0.00 | 0.00 | 744.00 |
April | 74.54 | 46.02 | 28.52 | 94.43 | 28.74 | 0.00 | 0.00 | 720.00 |
May | 83.23 | 48.13 | 35.10 | 106.75 | 25.14 | 0.00 | 0.00 | 744.00 |
June | 88.91 | 52.47 | 36.44 | 115.66 | 25.00 | 0.00 | 0.00 | 720.00 |
July | 82.86 | 46.99 | 35.87 | 108.22 | 21.82 | 0.00 | 0.00 | 744.00 |
August | 76.27 | 41.83 | 34.44 | 99.78 | 21.48 | 0.00 | 0.00 | 744.00 |
September | 55.98 | 30.93 | 25.05 | 65.74 | 29.82 | 0.00 | 0.00 | 720.00 |
October | 48.59 | 32.73 | 15.86 | 54.90 | 34.67 | 0.00 | 0.00 | 744.00 |
November | 35.01 | 19.40 | 15.61 | 35.78 | 33.83 | 16.00 | 0.00 | 720.00 |
December | 28.92 | 15.52 | 13.40 | 27.04 | 31.45 | 31.00 | 0.00 | 744.00 |
Annual Sum or Average | 58.98 | 34.48 | 24.50 | 71.34 | 28.72 | 100.33 | 0.00 | 8760.00 |
Minimum of Months | 28.92 | 15.52 | 13.40 | 27.04 | 21.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 88.91 | 52.47 | 36.44 | 115.66 | 35.65 | 35.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138384E+09 | 64583452.34 | 73800131.69 | 0.107350E+09 | 0.450359E+09 |
February | 0.142393E+09 | 66576850.52 | 75815909.33 | 0.150026E+09 | 0.330287E+09 |
March | 0.231659E+09 | 0.111670E+09 | 0.119989E+09 | 0.297828E+09 | 0.237188E+09 |
April | 0.252088E+09 | 0.115015E+09 | 0.137072E+09 | 0.363785E+09 | 0.215678E+09 |
May | 0.262567E+09 | 99476376.90 | 0.163090E+09 | 0.409584E+09 | 0.169821E+09 |
June | 0.267541E+09 | 0.103235E+09 | 0.164306E+09 | 0.477322E+09 | 0.124779E+09 |
July | 0.259983E+09 | 96236371.95 | 0.163746E+09 | 0.481215E+09 | 0.101154E+09 |
August | 0.254749E+09 | 95074112.11 | 0.159675E+09 | 0.477836E+09 | 91563623.11 |
September | 0.201522E+09 | 84083729.15 | 0.117438E+09 | 0.315696E+09 | 0.162355E+09 |
October | 0.184470E+09 | 95468165.88 | 89001864.99 | 0.242297E+09 | 0.282401E+09 |
November | 0.142312E+09 | 63508020.16 | 78804475.92 | 0.157825E+09 | 0.307556E+09 |
December | 0.122373E+09 | 53788665.86 | 68584593.09 | 0.102952E+09 | 0.372819E+09 |
Annual Sum or Average | 0.246004E+10 | 0.104872E+10 | 0.141132E+10 | 0.358372E+10 | 0.284596E+10 |
Minimum of Months | 0.122373E+09 | 53788665.86 | 68584593.09 | 0.102952E+09 | 91563623.11 |
Maximum of Months | 0.267541E+09 | 0.115015E+09 | 0.164306E+09 | 0.481215E+09 | 0.450359E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138384E+09 | 64583452.34 | 73800131.69 | 0.107350E+09 | 0.450359E+09 |
February | 0.142393E+09 | 66576850.52 | 75815909.33 | 0.150026E+09 | 0.330287E+09 |
March | 0.231659E+09 | 0.111670E+09 | 0.119989E+09 | 0.297828E+09 | 0.237188E+09 |
April | 0.252088E+09 | 0.115015E+09 | 0.137072E+09 | 0.363785E+09 | 0.215678E+09 |
May | 0.262567E+09 | 99476376.90 | 0.163090E+09 | 0.409584E+09 | 0.169821E+09 |
June | 0.267541E+09 | 0.103235E+09 | 0.164306E+09 | 0.477322E+09 | 0.124779E+09 |
July | 0.259983E+09 | 96236371.95 | 0.163746E+09 | 0.481215E+09 | 0.101154E+09 |
August | 0.254749E+09 | 95074112.11 | 0.159675E+09 | 0.477836E+09 | 91563623.11 |
September | 0.201522E+09 | 84083729.15 | 0.117438E+09 | 0.315696E+09 | 0.162355E+09 |
October | 0.184470E+09 | 95468165.88 | 89001864.99 | 0.242297E+09 | 0.282401E+09 |
November | 0.142312E+09 | 63508020.16 | 78804475.92 | 0.157825E+09 | 0.307556E+09 |
December | 0.122373E+09 | 53788665.86 | 68584593.09 | 0.102952E+09 | 0.372819E+09 |
Annual Sum or Average | 0.246004E+10 | 0.104872E+10 | 0.141132E+10 | 0.358372E+10 | 0.284596E+10 |
Minimum of Months | 0.122373E+09 | 53788665.86 | 68584593.09 | 0.102952E+09 | 91563623.11 |
Maximum of Months | 0.267541E+09 | 0.115015E+09 | 0.164306E+09 | 0.481215E+09 | 0.450359E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 35476364.81 | 0.00 | 35476364.81 | 5923037.21 | 0.290762E+09 |
February | 35516733.54 | 0.00 | 35516733.54 | 16178663.37 | 0.209048E+09 |
March | 55222265.91 | 3322.88 | 55218943.04 | 36066616.34 | 0.146167E+09 |
April | 64729453.36 | 367120.83 | 64362332.54 | 65938815.87 | 0.129579E+09 |
May | 80004606.69 | 2632613.54 | 77371993.15 | 99114814.33 | 97710243.90 |
June | 85011219.57 | 5574313.20 | 79436906.37 | 0.140710E+09 | 68666983.97 |
July | 83148207.11 | 4240128.07 | 78908079.03 | 0.147200E+09 | 56479091.86 |
August | 73999102.88 | 998613.38 | 73000489.51 | 0.137998E+09 | 52562909.09 |
September | 53989896.25 | 24452.61 | 53965443.64 | 68937619.32 | 96937917.40 |
October | 42387610.65 | 0.00 | 42387610.65 | 28278899.85 | 0.171260E+09 |
November | 36711640.74 | 0.00 | 36711640.74 | 16157489.22 | 0.188616E+09 |
December | 32795260.47 | 0.00 | 32795260.47 | 4985430.53 | 0.233635E+09 |
Annual Sum or Average | 0.678992E+09 | 13840564.51 | 0.665152E+09 | 0.767489E+09 | 0.174142E+10 |
Minimum of Months | 32795260.47 | 0.00 | 32795260.47 | 4985430.53 | 52562909.09 |
Maximum of Months | 85011219.57 | 5574313.20 | 79436906.37 | 0.147200E+09 | 0.290762E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 35475297.24 | 0.00 | 35475297.24 | 5922730.19 | 0.290761E+09 |
February | 35515715.84 | 0.00 | 35515715.84 | 16178098.63 | 0.209048E+09 |
March | 55220677.65 | 3322.72 | 55217354.93 | 36065177.80 | 0.146166E+09 |
April | 64727617.06 | 367103.62 | 64360513.44 | 65936880.57 | 0.129579E+09 |
May | 80002220.39 | 2632490.15 | 77369730.24 | 99112026.64 | 97709725.90 |
June | 85008640.31 | 5574051.92 | 79434588.38 | 0.140707E+09 | 68666306.61 |
July | 83145670.63 | 4239929.33 | 78905741.30 | 0.147196E+09 | 56478406.84 |
August | 73996890.79 | 998566.57 | 72998324.22 | 0.137995E+09 | 52562108.44 |
September | 53988280.40 | 24451.46 | 53963828.94 | 68935742.12 | 96937053.72 |
October | 42386453.83 | 0.00 | 42386453.83 | 28277979.92 | 0.171259E+09 |
November | 36710532.43 | 0.00 | 36710532.43 | 16156723.27 | 0.188615E+09 |
December | 32794263.26 | 0.00 | 32794263.26 | 4985074.53 | 0.233635E+09 |
Annual Sum or Average | 0.678972E+09 | 13839915.78 | 0.665132E+09 | 0.767469E+09 | 0.174142E+10 |
Minimum of Months | 32794263.26 | 0.00 | 32794263.26 | 4985074.53 | 52562108.44 |
Maximum of Months | 85008640.31 | 5574051.92 | 79434588.38 | 0.147196E+09 | 0.290761E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 87704170.15 | 48652953.15 | 39051217.00 | 81283981.36 | 95489429.08 |
February | 96783496.58 | 59270767.04 | 37512729.54 | 0.106596E+09 | 73531676.63 |
March | 0.159323E+09 | 97674104.03 | 61648837.30 | 0.191832E+09 | 71860420.50 |
April | 0.193210E+09 | 0.119273E+09 | 73936730.70 | 0.244752E+09 | 74502976.58 |
May | 0.222912E+09 | 0.128902E+09 | 94009439.24 | 0.285924E+09 | 67335263.54 |
June | 0.230445E+09 | 0.136000E+09 | 94445045.15 | 0.299784E+09 | 64806642.87 |
July | 0.221940E+09 | 0.125866E+09 | 96073878.21 | 0.289858E+09 | 58432778.83 |
August | 0.204278E+09 | 0.112046E+09 | 92231094.31 | 0.267244E+09 | 57521898.79 |
September | 0.145104E+09 | 80176006.56 | 64927501.42 | 0.170389E+09 | 77280576.40 |
October | 0.130132E+09 | 87663618.92 | 42468431.75 | 0.147046E+09 | 92872640.62 |
November | 90757630.77 | 50286251.89 | 40471378.88 | 92732730.16 | 87691985.33 |
December | 77469905.37 | 41566646.27 | 35903259.10 | 72418218.57 | 84248001.11 |
Annual Sum or Average | 0.186006E+10 | 0.108738E+10 | 0.772680E+09 | 0.224986E+10 | 0.905574E+09 |
Minimum of Months | 77469905.37 | 41566646.27 | 35903259.10 | 72418218.57 | 57521898.79 |
Maximum of Months | 0.230445E+09 | 0.136000E+09 | 96073878.21 | 0.299784E+09 | 95489429.08 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 87704170.15 | 48652953.15 | 39051217.00 | 81283981.36 | 95489429.08 |
February | 96783496.58 | 59270767.04 | 37512729.54 | 0.106596E+09 | 73531676.63 |
March | 0.159323E+09 | 97674104.03 | 61648837.30 | 0.191832E+09 | 71860420.50 |
April | 0.193210E+09 | 0.119273E+09 | 73936730.70 | 0.244752E+09 | 74502976.58 |
May | 0.222912E+09 | 0.128902E+09 | 94009439.24 | 0.285924E+09 | 67335263.54 |
June | 0.230445E+09 | 0.136000E+09 | 94445045.15 | 0.299784E+09 | 64806642.87 |
July | 0.221940E+09 | 0.125866E+09 | 96073878.21 | 0.289858E+09 | 58432778.83 |
August | 0.204278E+09 | 0.112046E+09 | 92231094.31 | 0.267244E+09 | 57521898.79 |
September | 0.145104E+09 | 80176006.56 | 64927501.42 | 0.170389E+09 | 77280576.40 |
October | 0.130132E+09 | 87663618.92 | 42468431.75 | 0.147046E+09 | 92872640.62 |
November | 90757630.77 | 50286251.89 | 40471378.88 | 92732730.16 | 87691985.33 |
December | 77469905.37 | 41566646.27 | 35903259.10 | 72418218.57 | 84248001.11 |
Annual Sum or Average | 0.186006E+10 | 0.108738E+10 | 0.772680E+09 | 0.224986E+10 | 0.905574E+09 |
Minimum of Months | 77469905.37 | 41566646.27 | 35903259.10 | 72418218.57 | 57521898.79 |
Maximum of Months | 0.230445E+09 | 0.136000E+09 | 96073878.21 | 0.299784E+09 | 95489429.08 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 87704170.15 | 48652953.15 | 39051217.00 | 81283981.36 | 95489429.08 |
February | 96783496.58 | 59270767.04 | 37512729.54 | 0.106596E+09 | 73531676.63 |
March | 0.159323E+09 | 97674104.03 | 61648837.30 | 0.191832E+09 | 71860420.50 |
April | 0.193210E+09 | 0.119273E+09 | 73936730.70 | 0.244752E+09 | 74502976.58 |
May | 0.222912E+09 | 0.128902E+09 | 94009439.24 | 0.285924E+09 | 67335263.54 |
June | 0.230445E+09 | 0.136000E+09 | 94445045.15 | 0.299784E+09 | 64806642.87 |
July | 0.221940E+09 | 0.125866E+09 | 96073878.21 | 0.289858E+09 | 58432778.83 |
August | 0.204278E+09 | 0.112046E+09 | 92231094.31 | 0.267244E+09 | 57521898.79 |
September | 0.145104E+09 | 80176006.56 | 64927501.42 | 0.170389E+09 | 77280576.40 |
October | 0.130132E+09 | 87663618.92 | 42468431.75 | 0.147046E+09 | 92872640.62 |
November | 90757630.77 | 50286251.89 | 40471378.88 | 92732730.16 | 87691985.33 |
December | 77469905.37 | 41566646.27 | 35903259.10 | 72418218.57 | 84248001.11 |
Annual Sum or Average | 0.186006E+10 | 0.108738E+10 | 0.772680E+09 | 0.224986E+10 | 0.905574E+09 |
Minimum of Months | 77469905.37 | 41566646.27 | 35903259.10 | 72418218.57 | 57521898.79 |
Maximum of Months | 0.230445E+09 | 0.136000E+09 | 96073878.21 | 0.299784E+09 | 95489429.08 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 87704170.15 | 48652953.15 | 39051217.00 | 81283981.36 | 95489429.08 |
February | 96783496.58 | 59270767.04 | 37512729.54 | 0.106596E+09 | 73531676.63 |
March | 0.159323E+09 | 97674104.03 | 61648837.30 | 0.191832E+09 | 71860420.50 |
April | 0.193210E+09 | 0.119273E+09 | 73936730.70 | 0.244752E+09 | 74502976.58 |
May | 0.222912E+09 | 0.128902E+09 | 94009439.24 | 0.285924E+09 | 67335263.54 |
June | 0.230445E+09 | 0.136000E+09 | 94445045.15 | 0.299784E+09 | 64806642.87 |
July | 0.221940E+09 | 0.125866E+09 | 96073878.21 | 0.289858E+09 | 58432778.83 |
August | 0.204278E+09 | 0.112046E+09 | 92231094.31 | 0.267244E+09 | 57521898.79 |
September | 0.145104E+09 | 80176006.56 | 64927501.42 | 0.170389E+09 | 77280576.40 |
October | 0.130132E+09 | 87663618.92 | 42468431.75 | 0.147046E+09 | 92872640.62 |
November | 90757630.77 | 50286251.89 | 40471378.88 | 92732730.16 | 87691985.33 |
December | 77469905.37 | 41566646.27 | 35903259.10 | 72418218.57 | 84248001.11 |
Annual Sum or Average | 0.186006E+10 | 0.108738E+10 | 0.772680E+09 | 0.224986E+10 | 0.905574E+09 |
Minimum of Months | 77469905.37 | 41566646.27 | 35903259.10 | 72418218.57 | 57521898.79 |
Maximum of Months | 0.230445E+09 | 0.136000E+09 | 96073878.21 | 0.299784E+09 | 95489429.08 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 87704170.15 | 48652953.15 | 39051217.00 | 81283981.36 | 95489429.08 |
February | 96783496.58 | 59270767.04 | 37512729.54 | 0.106596E+09 | 73531676.63 |
March | 0.159323E+09 | 97674104.03 | 61648837.30 | 0.191832E+09 | 71860420.50 |
April | 0.193210E+09 | 0.119273E+09 | 73936730.70 | 0.244752E+09 | 74502976.58 |
May | 0.222912E+09 | 0.128902E+09 | 94009439.24 | 0.285924E+09 | 67335263.54 |
June | 0.230445E+09 | 0.136000E+09 | 94445045.15 | 0.299784E+09 | 64806642.87 |
July | 0.221940E+09 | 0.125866E+09 | 96073878.21 | 0.289858E+09 | 58432778.83 |
August | 0.204278E+09 | 0.112046E+09 | 92231094.31 | 0.267244E+09 | 57521898.79 |
September | 0.145104E+09 | 80176006.56 | 64927501.42 | 0.170389E+09 | 77280576.40 |
October | 0.130132E+09 | 87663618.92 | 42468431.75 | 0.147046E+09 | 92872640.62 |
November | 90757630.77 | 50286251.89 | 40471378.88 | 92732730.16 | 87691985.33 |
December | 77469905.37 | 41566646.27 | 35903259.10 | 72418218.57 | 84248001.11 |
Annual Sum or Average | 0.186006E+10 | 0.108738E+10 | 0.772680E+09 | 0.224986E+10 | 0.905574E+09 |
Minimum of Months | 77469905.37 | 41566646.27 | 35903259.10 | 72418218.57 | 57521898.79 |
Maximum of Months | 0.230445E+09 | 0.136000E+09 | 96073878.21 | 0.299784E+09 | 95489429.08 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 87704170.15 | 48652953.15 | 39051217.00 | 81283981.36 | 95489429.08 |
February | 96783496.58 | 59270767.04 | 37512729.54 | 0.106596E+09 | 73531676.63 |
March | 0.159323E+09 | 97674104.03 | 61648837.30 | 0.191832E+09 | 71860420.50 |
April | 0.193210E+09 | 0.119273E+09 | 73936730.70 | 0.244752E+09 | 74502976.58 |
May | 0.222912E+09 | 0.128902E+09 | 94009439.24 | 0.285924E+09 | 67335263.54 |
June | 0.230445E+09 | 0.136000E+09 | 94445045.15 | 0.299784E+09 | 64806642.87 |
July | 0.221940E+09 | 0.125866E+09 | 96073878.21 | 0.289858E+09 | 58432778.83 |
August | 0.204278E+09 | 0.112046E+09 | 92231094.31 | 0.267244E+09 | 57521898.79 |
September | 0.145104E+09 | 80176006.56 | 64927501.42 | 0.170389E+09 | 77280576.40 |
October | 0.130132E+09 | 87663618.92 | 42468431.75 | 0.147046E+09 | 92872640.62 |
November | 90757630.77 | 50286251.89 | 40471378.88 | 92732730.16 | 87691985.33 |
December | 77469905.37 | 41566646.27 | 35903259.10 | 72418218.57 | 84248001.11 |
Annual Sum or Average | 0.186006E+10 | 0.108738E+10 | 0.772680E+09 | 0.224986E+10 | 0.905574E+09 |
Minimum of Months | 77469905.37 | 41566646.27 | 35903259.10 | 72418218.57 | 57521898.79 |
Maximum of Months | 0.230445E+09 | 0.136000E+09 | 96073878.21 | 0.299784E+09 | 95489429.08 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 87704170.15 | 48652953.15 | 39051217.00 | 81283981.36 | 95489429.08 |
February | 96783496.58 | 59270767.04 | 37512729.54 | 0.106596E+09 | 73531676.63 |
March | 0.159323E+09 | 97674104.03 | 61648837.30 | 0.191832E+09 | 71860420.50 |
April | 0.193210E+09 | 0.119273E+09 | 73936730.70 | 0.244752E+09 | 74502976.58 |
May | 0.222912E+09 | 0.128902E+09 | 94009439.24 | 0.285924E+09 | 67335263.54 |
June | 0.230445E+09 | 0.136000E+09 | 94445045.15 | 0.299784E+09 | 64806642.87 |
July | 0.221940E+09 | 0.125866E+09 | 96073878.21 | 0.289858E+09 | 58432778.83 |
August | 0.204278E+09 | 0.112046E+09 | 92231094.31 | 0.267244E+09 | 57521898.79 |
September | 0.145104E+09 | 80176006.56 | 64927501.42 | 0.170389E+09 | 77280576.40 |
October | 0.130132E+09 | 87663618.92 | 42468431.75 | 0.147046E+09 | 92872640.62 |
November | 90757630.77 | 50286251.89 | 40471378.88 | 92732730.16 | 87691985.33 |
December | 77469905.37 | 41566646.27 | 35903259.10 | 72418218.57 | 84248001.11 |
Annual Sum or Average | 0.186006E+10 | 0.108738E+10 | 0.772680E+09 | 0.224986E+10 | 0.905574E+09 |
Minimum of Months | 77469905.37 | 41566646.27 | 35903259.10 | 72418218.57 | 57521898.79 |
Maximum of Months | 0.230445E+09 | 0.136000E+09 | 96073878.21 | 0.299784E+09 | 95489429.08 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 87704170.15 | 48652953.15 | 39051217.00 | 81283981.36 | 95489429.08 |
February | 96783496.58 | 59270767.04 | 37512729.54 | 0.106596E+09 | 73531676.63 |
March | 0.159323E+09 | 97674104.03 | 61648837.30 | 0.191832E+09 | 71860420.50 |
April | 0.193210E+09 | 0.119273E+09 | 73936730.70 | 0.244752E+09 | 74502976.58 |
May | 0.222912E+09 | 0.128902E+09 | 94009439.24 | 0.285924E+09 | 67335263.54 |
June | 0.230445E+09 | 0.136000E+09 | 94445045.15 | 0.299784E+09 | 64806642.87 |
July | 0.221940E+09 | 0.125866E+09 | 96073878.21 | 0.289858E+09 | 58432778.83 |
August | 0.204278E+09 | 0.112046E+09 | 92231094.31 | 0.267244E+09 | 57521898.79 |
September | 0.145104E+09 | 80176006.56 | 64927501.42 | 0.170389E+09 | 77280576.40 |
October | 0.130132E+09 | 87663618.92 | 42468431.75 | 0.147046E+09 | 92872640.62 |
November | 90757630.77 | 50286251.89 | 40471378.88 | 92732730.16 | 87691985.33 |
December | 77469905.37 | 41566646.27 | 35903259.10 | 72418218.57 | 84248001.11 |
Annual Sum or Average | 0.186006E+10 | 0.108738E+10 | 0.772680E+09 | 0.224986E+10 | 0.905574E+09 |
Minimum of Months | 77469905.37 | 41566646.27 | 35903259.10 | 72418218.57 | 57521898.79 |
Maximum of Months | 0.230445E+09 | 0.136000E+09 | 96073878.21 | 0.299784E+09 | 95489429.08 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 87704170.15 | 48652953.15 | 39051217.00 | 81283981.36 | 95489429.08 |
February | 96783496.58 | 59270767.04 | 37512729.54 | 0.106596E+09 | 73531676.63 |
March | 0.159323E+09 | 97674104.03 | 61648837.30 | 0.191832E+09 | 71860420.50 |
April | 0.193210E+09 | 0.119273E+09 | 73936730.70 | 0.244752E+09 | 74502976.58 |
May | 0.222912E+09 | 0.128902E+09 | 94009439.24 | 0.285924E+09 | 67335263.54 |
June | 0.230445E+09 | 0.136000E+09 | 94445045.15 | 0.299784E+09 | 64806642.87 |
July | 0.221940E+09 | 0.125866E+09 | 96073878.21 | 0.289858E+09 | 58432778.83 |
August | 0.204278E+09 | 0.112046E+09 | 92231094.31 | 0.267244E+09 | 57521898.79 |
September | 0.145104E+09 | 80176006.56 | 64927501.42 | 0.170389E+09 | 77280576.40 |
October | 0.130132E+09 | 87663618.92 | 42468431.75 | 0.147046E+09 | 92872640.62 |
November | 90757630.77 | 50286251.89 | 40471378.88 | 92732730.16 | 87691985.33 |
December | 77469905.37 | 41566646.27 | 35903259.10 | 72418218.57 | 84248001.11 |
Annual Sum or Average | 0.186006E+10 | 0.108738E+10 | 0.772680E+09 | 0.224986E+10 | 0.905574E+09 |
Minimum of Months | 77469905.37 | 41566646.27 | 35903259.10 | 72418218.57 | 57521898.79 |
Maximum of Months | 0.230445E+09 | 0.136000E+09 | 96073878.21 | 0.299784E+09 | 95489429.08 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 87704170.15 | 48652953.15 | 39051217.00 | 81283981.36 | 95489429.08 |
February | 96783496.58 | 59270767.04 | 37512729.54 | 0.106596E+09 | 73531676.63 |
March | 0.159323E+09 | 97674104.03 | 61648837.30 | 0.191832E+09 | 71860420.50 |
April | 0.193210E+09 | 0.119273E+09 | 73936730.70 | 0.244752E+09 | 74502976.58 |
May | 0.222912E+09 | 0.128902E+09 | 94009439.24 | 0.285924E+09 | 67335263.54 |
June | 0.230445E+09 | 0.136000E+09 | 94445045.15 | 0.299784E+09 | 64806642.87 |
July | 0.221940E+09 | 0.125866E+09 | 96073878.21 | 0.289858E+09 | 58432778.83 |
August | 0.204278E+09 | 0.112046E+09 | 92231094.31 | 0.267244E+09 | 57521898.79 |
September | 0.145104E+09 | 80176006.56 | 64927501.42 | 0.170389E+09 | 77280576.40 |
October | 0.130132E+09 | 87663618.92 | 42468431.75 | 0.147046E+09 | 92872640.62 |
November | 90757630.77 | 50286251.89 | 40471378.88 | 92732730.16 | 87691985.33 |
December | 77469905.37 | 41566646.27 | 35903259.10 | 72418218.57 | 84248001.11 |
Annual Sum or Average | 0.186006E+10 | 0.108738E+10 | 0.772680E+09 | 0.224986E+10 | 0.905574E+09 |
Minimum of Months | 77469905.37 | 41566646.27 | 35903259.10 | 72418218.57 | 57521898.79 |
Maximum of Months | 0.230445E+09 | 0.136000E+09 | 96073878.21 | 0.299784E+09 | 95489429.08 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 71.03 | 539.86 | 129.82 | 48.23 | 81.60 | 0.00 | 0.00 |
February | 128.36 | 436.83 | 147.08 | 55.04 | 92.04 | 0.00 | 0.00 |
March | 245.64 | 282.58 | 214.22 | 83.39 | 130.83 | 0.00 | 0.00 |
April | 328.60 | 263.42 | 244.46 | 89.03 | 155.43 | 0.00 | 0.00 |
May | 379.31 | 199.23 | 255.80 | 76.25 | 179.56 | 0.00 | 0.00 |
June | 475.98 | 148.37 | 272.03 | 83.96 | 188.07 | 0.00 | 0.00 |
July | 468.42 | 116.88 | 256.22 | 75.03 | 181.19 | 0.00 | 0.00 |
August | 459.71 | 107.48 | 245.48 | 71.74 | 173.74 | 0.00 | 0.00 |
September | 295.79 | 199.08 | 197.15 | 64.90 | 132.26 | 0.00 | 0.00 |
October | 198.61 | 335.32 | 169.40 | 71.29 | 98.11 | 0.00 | 0.00 |
November | 130.26 | 378.86 | 138.14 | 49.00 | 89.13 | 0.00 | 0.00 |
December | 73.01 | 445.26 | 115.87 | 40.16 | 75.70 | 0.00 | 0.00 |
Annual Sum or Average | 272.00 | 286.98 | 199.08 | 67.39 | 131.69 | 0.00 | 0.00 |
Minimum of Months | 71.03 | 107.48 | 115.87 | 40.16 | 75.70 | 0.00 | 0.00 |
Maximum of Months | 475.98 | 539.86 | 272.03 | 89.03 | 188.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 303.48 | 356.52 | 327.45 | 181.65 | 145.80 | 0.00 | 0.00 |
February | 440.62 | 303.95 | 400.06 | 245.00 | 155.06 | 0.00 | 0.00 |
March | 716.22 | 268.30 | 594.84 | 364.67 | 230.17 | 0.00 | 0.00 |
April | 944.26 | 287.43 | 745.41 | 460.16 | 285.25 | 0.00 | 0.00 |
May | 1067.52 | 251.40 | 832.26 | 481.27 | 350.99 | 0.00 | 0.00 |
June | 1156.57 | 250.02 | 889.06 | 524.69 | 364.37 | 0.00 | 0.00 |
July | 1082.20 | 218.16 | 828.63 | 469.93 | 358.70 | 0.00 | 0.00 |
August | 997.78 | 214.76 | 762.68 | 418.33 | 344.35 | 0.00 | 0.00 |
September | 657.37 | 298.15 | 559.81 | 309.32 | 250.49 | 0.00 | 0.00 |
October | 549.01 | 346.75 | 485.86 | 327.30 | 158.56 | 0.00 | 0.00 |
November | 357.76 | 338.32 | 350.15 | 194.01 | 156.14 | 0.00 | 0.00 |
December | 270.38 | 314.55 | 289.24 | 155.19 | 134.05 | 0.00 | 0.00 |
Annual Sum or Average | 713.43 | 287.16 | 589.82 | 344.81 | 245.02 | 0.00 | 0.00 |
Minimum of Months | 270.38 | 214.76 | 289.24 | 155.19 | 134.05 | 0.00 | 0.00 |
Maximum of Months | 1156.57 | 356.52 | 889.06 | 524.69 | 364.37 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.190255E+09 | 0.144595E+10 | 0.347719E+09 | 0.129167E+09 | 0.218552E+09 | 0.00 | 0.00 |
February | 0.310518E+09 | 0.105678E+10 | 0.355818E+09 | 0.133154E+09 | 0.222664E+09 | 0.00 | 0.00 |
March | 0.657930E+09 | 0.756851E+09 | 0.573762E+09 | 0.223347E+09 | 0.350414E+09 | 0.00 | 0.00 |
April | 0.851726E+09 | 0.682794E+09 | 0.633633E+09 | 0.230765E+09 | 0.402867E+09 | 0.00 | 0.00 |
May | 0.101595E+10 | 0.533616E+09 | 0.685140E+09 | 0.204218E+09 | 0.480922E+09 | 0.00 | 0.00 |
June | 0.123374E+10 | 0.384573E+09 | 0.705102E+09 | 0.217617E+09 | 0.487484E+09 | 0.00 | 0.00 |
July | 0.125461E+10 | 0.313054E+09 | 0.686259E+09 | 0.200953E+09 | 0.485307E+09 | 0.00 | 0.00 |
August | 0.123129E+10 | 0.287875E+09 | 0.657494E+09 | 0.192145E+09 | 0.465348E+09 | 0.00 | 0.00 |
September | 0.766687E+09 | 0.516007E+09 | 0.511022E+09 | 0.168216E+09 | 0.342805E+09 | 0.00 | 0.00 |
October | 0.531957E+09 | 0.898128E+09 | 0.453714E+09 | 0.190936E+09 | 0.262778E+09 | 0.00 | 0.00 |
November | 0.337627E+09 | 0.982006E+09 | 0.358047E+09 | 0.127016E+09 | 0.231031E+09 | 0.00 | 0.00 |
December | 0.195537E+09 | 0.119257E+10 | 0.310336E+09 | 0.107577E+09 | 0.202759E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.857783E+10 | 0.905020E+10 | 0.627805E+10 | 0.212511E+10 | 0.415293E+10 | 0.00 | 0.00 |
Minimum of Months | 0.190255E+09 | 0.287875E+09 | 0.310336E+09 | 0.107577E+09 | 0.202759E+09 | 0.00 | 0.00 |
Maximum of Months | 0.125461E+10 | 0.144595E+10 | 0.705102E+09 | 0.230765E+09 | 0.487484E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.812840E+09 | 0.954894E+09 | 0.877042E+09 | 0.486530E+09 | 0.390512E+09 | 0.00 | 0.00 |
February | 0.106596E+10 | 0.735315E+09 | 0.967835E+09 | 0.592708E+09 | 0.375127E+09 | 0.00 | 0.00 |
March | 0.191832E+10 | 0.718604E+09 | 0.159323E+10 | 0.976741E+09 | 0.616488E+09 | 0.00 | 0.00 |
April | 0.244752E+10 | 0.745030E+09 | 0.193210E+10 | 0.119273E+10 | 0.739367E+09 | 0.00 | 0.00 |
May | 0.285924E+10 | 0.673352E+09 | 0.222912E+10 | 0.128902E+10 | 0.940094E+09 | 0.00 | 0.00 |
June | 0.299784E+10 | 0.648065E+09 | 0.230445E+10 | 0.136000E+10 | 0.944450E+09 | 0.00 | 0.00 |
July | 0.289858E+10 | 0.584323E+09 | 0.221940E+10 | 0.125866E+10 | 0.960739E+09 | 0.00 | 0.00 |
August | 0.267244E+10 | 0.575218E+09 | 0.204278E+10 | 0.112046E+10 | 0.922311E+09 | 0.00 | 0.00 |
September | 0.170389E+10 | 0.772806E+09 | 0.145104E+10 | 0.801760E+09 | 0.649275E+09 | 0.00 | 0.00 |
October | 0.147046E+10 | 0.928725E+09 | 0.130132E+10 | 0.876636E+09 | 0.424684E+09 | 0.00 | 0.00 |
November | 0.927327E+09 | 0.876919E+09 | 0.907576E+09 | 0.502863E+09 | 0.404714E+09 | 0.00 | 0.00 |
December | 0.724182E+09 | 0.842480E+09 | 0.774699E+09 | 0.415666E+09 | 0.359033E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.224986E+11 | 0.905573E+10 | 0.186006E+11 | 0.108738E+11 | 0.772680E+10 | 0.00 | 0.00 |
Minimum of Months | 0.724182E+09 | 0.575218E+09 | 0.774699E+09 | 0.415666E+09 | 0.359033E+09 | 0.00 | 0.00 |
Maximum of Months | 0.299784E+10 | 0.954894E+09 | 0.230445E+10 | 0.136000E+10 | 0.960739E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.45 | -3.0 | 4.56 | -7.9 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.23 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.96 | 3.80 | 4.89 | 2.24 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.53 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.43 | 13.69 | 3.50 | 11.45 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.34 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.67 | 19.85 | 3.24 | 17.63 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.41 | 20.72 | 3.39 | 18.20 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.43 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.01 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.21 | 4.17 | 4.16 | 0.29 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.67 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.28 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.45 | -3.0 | 3.06 | -7.9 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.41 | 20.72 | 5.19 | 18.20 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.95 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.72 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.85 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.53 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.47 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.37 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.89 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.82 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.04 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.54 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.94 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.76 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.72 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.89 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.7 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.7 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.4 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.0 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.44 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.1 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.7 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.80 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.15 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.00 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.33 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.31 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.05 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.12 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.09 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.19 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.87 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.80 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.12 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.80 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.78 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.09 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.88 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.80 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.895066E+09 | -808229869.4 | 0.00 | 0.00 | 744.00 | 0.00 | -86836258.3 | 58.99 | 0.00 | 0.00 |
February | 0.820448E+09 | -744050494.7 | 0.00 | 0.00 | 672.00 | 0.00 | -76397927.2 | 58.99 | 0.00 | 0.00 |
March | 0.920191E+09 | -840343837.0 | 0.00 | 0.00 | 744.00 | 0.00 | -79846819.4 | 58.99 | 0.00 | 0.00 |
April | 0.803885E+09 | -730859332.9 | 0.00 | 0.00 | 720.00 | 0.00 | -73026015.1 | 58.99 | 0.00 | 0.00 |
May | 0.771569E+09 | -699067807.2 | 0.00 | 0.00 | 744.00 | 0.00 | -72500911.2 | 58.99 | 0.00 | 0.00 |
June | 0.709324E+09 | -641060153.8 | 0.00 | 0.00 | 720.00 | 0.00 | -68263541.3 | 58.99 | 0.00 | 0.00 |
July | 0.657221E+09 | -587554914.0 | 0.00 | 0.00 | 744.00 | 0.00 | -69666316.8 | 58.99 | 0.00 | 0.00 |
August | 0.698701E+09 | -628941532.0 | 0.00 | 0.00 | 744.00 | 0.00 | -69759304.6 | 58.99 | 0.00 | 0.00 |
September | 0.681704E+09 | -613205524.1 | 0.00 | 0.00 | 720.00 | 0.00 | -68498139.7 | 58.99 | 0.00 | 0.00 |
October | 0.740534E+09 | -665354995.7 | 0.00 | 0.00 | 744.00 | 0.00 | -75179315.5 | 58.99 | 0.00 | 0.00 |
November | 0.773259E+09 | -695381173.7 | 0.00 | 0.00 | 720.00 | 0.00 | -77878221.9 | 58.99 | 0.00 | 0.00 |
December | 0.860945E+09 | -775887587.6 | 0.00 | 0.00 | 744.00 | 0.00 | -85057080.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.933285E+10 | -.842994E+10 | 8760.00 | -902909851.5 | 58.99 | |||||
Minimum of Months | 0.657221E+09 | -840343837.0 | 0.00 | 0.00 | 672.00 | 0.00 | -86836258.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.920191E+09 | -587554914.0 | 0.00 | 0.00 | 744.00 | 0.00 | -68263541.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 290.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 263.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 369.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 407.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 411.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 411.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 390.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 293.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 299.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 285.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4071.00 | ||||||||||
Minimum of Months | 263.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 411.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.550222E+10 | 26792.40 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.356641E+10 | 26792.40 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.819779E+09 | 26792.40 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162203E+09 | 26792.40 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137032E+09 | 26792.40 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.982423E+09 | 26792.40 | 01-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.269186E+10 | 26792.40 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138619E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.550222E+10 | 26792.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.242540E+11 | 84418.65 | 03-JAN-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145799E+11 | 84418.65 | 01-FEB-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.519920E+09 | 54155.46 | 07-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.203124E+10 | 84418.65 | 21-NOV-03:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118819E+11 | 84418.65 | 01-DEC-03:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.532670E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.242540E+11 | 84418.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.331101E+11 | 96521.04 | 07-JAN-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.229781E+11 | 113243.91 | 12-FEB-00:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144754E+10 | 23097.62 | 03-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.575357E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.331101E+11 | 113243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 70972952.71 | 70972952.71 | 4039.27 | 28-FEB-15:20 | 4039.27 | 0.00 |
March | 0.00 | 0.00 | 0.596848E+09 | 0.495208E+09 | 7689.56 | 30-MAR-16:00 | 6949.37 | 0.00 |
April | 0.00 | 0.00 | 0.242137E+10 | 0.211845E+10 | 21157.25 | 22-APR-05:05 | 12244.05 | 0.00 |
May | 0.00 | 0.00 | 0.581729E+10 | 0.462281E+10 | 23198.97 | 31-MAY-05:01 | 11584.57 | 0.00 |
June | 0.00 | 0.00 | 0.112343E+11 | 0.864379E+10 | 25066.87 | 26-JUN-05:01 | 12064.22 | 0.00 |
July | 0.00 | 0.00 | 0.125349E+11 | 0.923057E+10 | 25451.74 | 27-JUL-05:01 | 10263.39 | 0.00 |
August | 0.00 | 0.00 | 0.145993E+11 | 0.105758E+11 | 25835.39 | 12-AUG-05:01 | 10756.73 | 0.00 |
September | 0.00 | 0.00 | 0.859819E+10 | 0.658110E+10 | 24449.63 | 05-SEP-05:01 | 11505.99 | 0.00 |
October | 0.00 | 0.00 | 0.235824E+10 | 0.175656E+10 | 24829.77 | 19-OCT-05:01 | 9785.85 | 0.00 |
November | 0.00 | 0.00 | 0.155329E+09 | 0.122463E+09 | 4303.51 | 02-NOV-14:00 | 3189.11 | 0.00 |
December | 0.00 | 0.00 | 10243403.04 | 7740599.31 | 1491.83 | 12-DEC-14:50 | 1140.14 | 0.00 |
Annual Sum or Average | 0.583969E+11 | 0.442255E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.145993E+11 | 0.105758E+11 | 25835.39 | 12244.05 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.152588E+09 | 0.124589E+09 | 12204.15 | 30-MAR-15:00 | 10563.15 | 0.00 |
April | 0.00 | 0.00 | 0.216204E+10 | 0.195294E+10 | 62192.61 | 16-APR-16:41 | 58211.52 | 0.00 |
May | 0.00 | 0.00 | 0.955864E+10 | 0.741165E+10 | 72898.51 | 21-MAY-11:21 | 42303.23 | 0.00 |
June | 0.00 | 0.00 | 0.284602E+11 | 0.208183E+11 | 76190.16 | 25-JUN-08:21 | 38567.38 | 0.00 |
July | 0.00 | 0.00 | 0.356339E+11 | 0.252003E+11 | 80306.79 | 30-JUL-10:41 | 35438.09 | 0.00 |
August | 0.00 | 0.00 | 0.402266E+11 | 0.274841E+11 | 82271.70 | 20-AUG-07:41 | 30225.65 | 0.00 |
September | 0.00 | 0.00 | 0.154052E+11 | 0.109742E+11 | 78313.47 | 17-SEP-11:01 | 36771.73 | 0.00 |
October | 0.00 | 0.00 | 0.145017E+10 | 0.957617E+09 | 22434.26 | 11-OCT-14:00 | 15656.70 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.133049E+12 | 0.949237E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.402266E+11 | 0.274841E+11 | 82271.70 | 58211.52 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.301813E+09 | 0.03 | 262.72 | 03-JAN-10:10 | 0.08 |
February | 0.187239E+09 | 0.02 | 262.72 | 01-FEB-06:38 | 0.08 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 39121960.23 | 0.00 | 262.72 | 02-DEC-07:20 | 0.08 |
Annual Sum or Average | 0.528174E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.301813E+09 | 0.03 | 262.72 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.125064E+10 | 0.43 | 1213.37 | 02-JAN-10:00 | 0.97 |
February | 0.114454E+10 | 0.43 | 1213.37 | 01-FEB-07:03 | 0.97 |
March | 0.130838E+10 | 0.40 | 1213.37 | 01-MAR-07:40 | 0.97 |
April | 0.120460E+10 | 0.37 | 1213.37 | 03-APR-08:70 | 0.96 |
May | 0.126622E+10 | 0.38 | 1213.37 | 01-MAY-13:20 | 0.96 |
June | 0.128380E+10 | 0.41 | 1213.37 | 01-JUN-06:40 | 0.96 |
July | 0.124843E+10 | 0.39 | 1213.37 | 01-JUL-06:10 | 0.96 |
August | 0.135210E+10 | 0.42 | 1213.37 | 01-AUG-06:15 | 0.96 |
September | 0.123525E+10 | 0.39 | 1213.37 | 01-SEP-06:40 | 0.95 |
October | 0.120625E+10 | 0.36 | 1213.37 | 02-OCT-08:40 | 0.95 |
November | 0.116384E+10 | 0.37 | 1213.37 | 02-NOV-06:40 | 0.96 |
December | 0.122921E+10 | 0.38 | 1213.37 | 01-DEC-11:50 | 0.97 |
Annual Sum or Average | 0.148932E+11 | 0.40 | |||
Minimum of Months | 0.114454E+10 | 0.36 | 1213.37 | 0.95 | |
Maximum of Months | 0.135210E+10 | 0.43 | 1213.37 | 0.97 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.347255E+10 | 0.72 | 2824.08 | 02-JAN-10:00 | 0.93 |
February | 0.297438E+10 | 0.58 | 2824.08 | 01-FEB-10:40 | 0.93 |
March | 0.303355E+10 | 0.39 | 2824.08 | 18-MAR-07:10 | 0.93 |
April | 0.280198E+10 | 0.36 | 2824.08 | 11-APR-13:20 | 0.93 |
May | 0.296394E+10 | 0.39 | 2824.08 | 03-MAY-12:30 | 0.92 |
June | 0.317798E+10 | 0.49 | 2824.08 | 01-JUN-10:10 | 0.92 |
July | 0.325398E+10 | 0.54 | 2824.08 | 01-JUL-08:50 | 0.91 |
August | 0.347100E+10 | 0.56 | 2824.08 | 01-AUG-10:10 | 0.92 |
September | 0.292405E+10 | 0.42 | 2824.08 | 01-SEP-10:40 | 0.92 |
October | 0.279621E+10 | 0.34 | 2824.08 | 02-OCT-10:40 | 0.92 |
November | 0.274911E+10 | 0.40 | 2824.08 | 21-NOV-07:20 | 0.93 |
December | 0.317329E+10 | 0.63 | 2824.08 | 01-DEC-08:70 | 0.93 |
Annual Sum or Average | 0.367920E+11 | 0.48 | |||
Minimum of Months | 0.274911E+10 | 0.34 | 2824.08 | 0.91 | |
Maximum of Months | 0.347255E+10 | 0.72 | 2824.08 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.55 | 0.01 |
February | 1.69 | 0.27 |
March | 0.94 | 2.59 |
April | 1.71 | 1.96 |
May | 2.73 | 0.86 |
June | 4.07 | 0.17 |
July | 3.71 | 0.08 |
August | 3.89 | 0.04 |
September | 2.32 | 0.13 |
October | 3.37 | 1.50 |
November | 0.51 | 1.64 |
December | 1.42 | 0.16 |
Annual Sum or Average | 28.91 | 0.56 |
Minimum of Months | 0.51 | 0.01 |
Maximum of Months | 4.07 | 2.59 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.17 | 0.00 |
May | 0.38 | 0.00 |
June | 0.51 | 0.00 |
July | 0.08 | 0.00 |
August | 0.00 | 0.00 |
September | 0.33 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 1.47 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.51 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 1.74 | 0.00 |
July | 4.40 | 0.00 |
August | 5.08 | 0.00 |
September | 0.22 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 11.45 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 5.08 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.125064E+10 | 0.794961E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.116395E+10 | 0.516302E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.147110E+10 | 0.120848E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.186352E+10 | 0.240071E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.283226E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.433977E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.466532E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.528320E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.351071E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.182868E+10 | 0.204916E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.120597E+10 | 0.144078E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.123202E+10 | 0.391508E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.306472E+11 | 0.201220E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.116395E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.528320E+10 | 0.794961E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.347255E+10 | 0.348451E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.297438E+10 | 0.207911E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.307987E+10 | 0.781287E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.345315E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.579096E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.116509E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.139200E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.153191E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.740742E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.321738E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.274911E+10 | 0.296810E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.317329E+10 | 0.172176E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.762082E+11 | 0.766031E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.274911E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.153191E+11 | 0.348451E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.125064E+10 | 0.00 | 0.550222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114454E+10 | 70972952.71 | 0.356641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130838E+10 | 0.596848E+09 | 0.819779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120460E+10 | 0.242137E+10 | 0.162203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126622E+10 | 0.581729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128380E+10 | 0.112343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.124843E+10 | 0.125349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135210E+10 | 0.145993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.123525E+10 | 0.859819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120625E+10 | 0.235824E+10 | 0.137032E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116384E+10 | 0.155329E+09 | 0.982423E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122921E+10 | 10243403.04 | 0.269186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148932E+11 | 0.583969E+11 | 0.138619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.114454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135210E+10 | 0.145993E+11 | 0.550222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.347255E+10 | 0.00 | 0.242540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.297438E+10 | 0.00 | 0.145799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.303355E+10 | 0.152588E+09 | 0.519920E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.280198E+10 | 0.216204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.296394E+10 | 0.955864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.317798E+10 | 0.284602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.325398E+10 | 0.356339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.347100E+10 | 0.402266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.292405E+10 | 0.154052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.279621E+10 | 0.145017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.274911E+10 | 0.00 | 0.203124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.317329E+10 | 0.00 | 0.118819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.367920E+11 | 0.133049E+12 | 0.532670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.274911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.347255E+10 | 0.402266E+11 | 0.242540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.125064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114454E+10 | 0.00 | 0.00 | 0.00 | 19412389.04 | 0.00 | 0.516302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130838E+10 | 0.00 | 0.00 | 0.00 | 0.162728E+09 | 0.00 | 0.120848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120460E+10 | 0.00 | 0.00 | 0.00 | 0.658922E+09 | 0.00 | 0.240071E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126622E+10 | 0.00 | 0.00 | 0.00 | 0.156604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128380E+10 | 0.00 | 0.00 | 0.00 | 0.305597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.124843E+10 | 0.00 | 0.00 | 0.00 | 0.341689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135210E+10 | 0.00 | 0.00 | 0.00 | 0.393110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.123525E+10 | 0.00 | 0.00 | 0.00 | 0.227545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120625E+10 | 0.00 | 0.00 | 0.00 | 0.622434E+09 | 0.00 | 0.204916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116384E+10 | 0.00 | 0.00 | 0.00 | 42138860.60 | 0.00 | 0.144078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122921E+10 | 0.00 | 0.00 | 0.00 | 2811312.82 | 0.00 | 0.391508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148932E+11 | 0.00 | 0.00 | 0.00 | 0.157539E+11 | 0.00 | 0.201220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.114454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135210E+10 | 0.00 | 0.00 | 0.00 | 0.393110E+10 | 0.00 | 0.794961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.347255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.297438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.303355E+10 | 0.00 | 0.00 | 0.00 | 46321267.40 | 0.00 | 0.781287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.280198E+10 | 0.00 | 0.00 | 0.00 | 0.651162E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.296394E+10 | 0.00 | 0.00 | 0.00 | 0.282701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.317798E+10 | 0.00 | 0.00 | 0.00 | 0.847293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.325398E+10 | 0.00 | 0.00 | 0.00 | 0.106660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.347100E+10 | 0.00 | 0.00 | 0.00 | 0.118481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.292405E+10 | 0.00 | 0.00 | 0.00 | 0.448337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.279621E+10 | 0.00 | 0.00 | 0.00 | 0.421166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.274911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.317329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.367920E+11 | 0.00 | 0.00 | 0.00 | 0.394161E+11 | 0.00 | 0.766031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.274911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.347255E+10 | 0.00 | 0.00 | 0.00 | 0.118481E+11 | 0.00 | 0.348451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167446E+10 | 0.00 | 0.00 | 0.12 |
February | 0.218889E+09 | 727529.96 | 0.00 | 83268.05 | 0.00 | 0.102805E+10 | 81373078.13 | 0.00 | 0.17 |
March | 0.557045E+09 | 25077911.02 | 0.00 | 674911.05 | 333161.84 | 0.219141E+09 | 0.616378E+09 | 0.00 | 0.29 |
April | 0.181465E+09 | 0.105453E+09 | 0.00 | 1829099.70 | 0.00 | 20332794.63 | 0.121805E+10 | 0.00 | 0.39 |
May | 22480728.12 | 0.491417E+09 | 0.00 | 4251968.73 | 0.00 | 0.00 | 0.114421E+10 | 0.00 | 0.45 |
June | 4238091.51 | 0.149247E+10 | 0.00 | 6326548.83 | 0.00 | 0.00 | 0.308914E+09 | 0.00 | 0.23 |
July | 149332.24 | 0.190171E+10 | 0.00 | 4420678.57 | 0.00 | 0.00 | 0.170718E+09 | 0.00 | 0.19 |
August | 0.00 | 0.223855E+10 | 0.00 | 3470679.18 | 0.00 | 0.00 | 33702185.17 | 0.00 | 0.15 |
September | 14957366.75 | 0.994296E+09 | 0.00 | 6149313.92 | 0.00 | 0.00 | 0.793905E+09 | 0.00 | 0.32 |
October | 0.253944E+09 | 0.194356E+09 | 0.00 | 2955266.01 | 0.00 | 28589380.73 | 0.160175E+10 | 0.00 | 0.42 |
November | 0.536088E+09 | 0.00 | 0.00 | 812700.80 | 156608.75 | 0.247666E+09 | 0.780576E+09 | 0.00 | 0.30 |
December | 0.408996E+09 | 0.00 | 0.00 | 44492.06 | 444216.90 | 0.829536E+09 | 71964122.78 | 0.00 | 0.14 |
Annual Sum or Average | 0.230601E+10 | 0.744405E+10 | 0.00 | 31018926.92 | 933987.48 | 0.404777E+10 | 0.682155E+10 | 0.00 | 0.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.557045E+09 | 0.223855E+10 | 0.00 | 6326548.83 | 444216.90 | 0.167446E+10 | 0.160175E+10 | 0.00 | 0.45 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.222361E+10 | 0.00 | 0.00 | 0.00 | 13801.19 | 0.266881E+10 | 0.00 | 0.00 | 0.17 |
February | 0.161128E+10 | 0.00 | 0.00 | 0.00 | 10647283.79 | 0.164920E+10 | 0.00 | 0.00 | 0.18 |
March | 0.266741E+10 | 8027643.78 | 0.00 | 18837.24 | 22329531.51 | 78160358.99 | 12064811.22 | 0.00 | 0.20 |
April | 0.186325E+10 | 74344124.87 | 0.00 | 1235519.61 | 3485347.35 | 0.00 | 0.458832E+09 | 0.00 | 0.26 |
May | 0.820751E+09 | 0.929441E+09 | 0.00 | 3113240.50 | 0.00 | 0.00 | 0.156037E+10 | 0.00 | 0.34 |
June | 0.175127E+09 | 0.387370E+10 | 0.00 | 4166017.38 | 0.00 | 0.00 | 0.110914E+10 | 0.00 | 0.32 |
July | 0.128046E+09 | 0.526633E+10 | 0.00 | 2857638.77 | 0.00 | 0.00 | 0.917529E+09 | 0.00 | 0.27 |
August | 57880563.06 | 0.619610E+10 | 0.00 | 2751679.14 | 0.00 | 0.00 | 0.871850E+09 | 0.00 | 0.30 |
September | 0.545413E+09 | 0.191652E+10 | 0.00 | 5175321.19 | 0.00 | 0.00 | 0.157792E+10 | 0.00 | 0.36 |
October | 0.234535E+10 | 0.176692E+09 | 0.00 | 883986.30 | 297730.50 | 0.00 | 0.923196E+09 | 0.00 | 0.25 |
November | 0.257364E+10 | 0.00 | 0.00 | 0.00 | 7193048.52 | 0.138940E+09 | 0.00 | 0.00 | 0.17 |
December | 0.253502E+10 | 0.00 | 0.00 | 0.00 | 14388511.41 | 0.665417E+09 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.175468E+11 | 0.184412E+11 | 0.00 | 20202240.14 | 58355254.28 | 0.520053E+10 | 0.743090E+10 | 0.00 | 0.25 |
Minimum of Months | 57880563.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.266741E+10 | 0.619610E+10 | 0.00 | 5175321.19 | 22329531.51 | 0.266881E+10 | 0.157792E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |