Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2020-06-03 19:11:46
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 895.99 | 185.31 | 185.31 |
Net Site Energy | 895.99 | 185.31 | 185.31 |
Total Source Energy | 2698.84 | 558.17 | 558.17 |
Net Source Energy | 2698.84 | 558.17 | 558.17 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 66.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 47.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.69 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 829.38 | 66.61 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 66.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 18.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 47.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.69 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 124.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 18.70 | 13.78 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 171.53 | 13.78 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 124.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 18.70 | 13.78 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 171.53 | 13.78 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 829.376 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 829.376 | 100.00 |
Total On-Site and Utility Electric Sources | 829.376 | 100.00 |
Total Electricity End Uses | 829.376 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 6.50 |
Time Setpoint Not Met During Occupied Cooling | 3.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 226.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.6337 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.5069 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.5069 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-SEP-12:00 | 03-JAN-06:10 | - | - | - | 28-JUN-11:09 |
Heating | 0.00 | 34336.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 13895.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6187.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1739.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 67123.63 | 34336.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 34336.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 13895.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 3881.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1739.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 72.21 | 0.00 | 0.00 | 0.00 |
Cooling | 57.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1507.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 391.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 150.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 78.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2626.63 | 72.21 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 14.93 | 0.00 | 0.00 | 0.00 |
Cooling | 11.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 31.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 543.24 | 14.93 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 14.93 | 0.00 | 0.00 | 0.00 |
Cooling | 11.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 31.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 543.24 | 14.93 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.04 |
ZONE2 FINE STORAGE DIRECT AIR | 2.46 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 0.936197 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 0.936197 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 38158.19 |
PSZ-OFFICE HEATING COIL | 25937.38 |
PSZ-FINE STORAGE HEATING COIL | 76405.18 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 38158.19 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.00 | 1.00 | 1.04 |
PSZ-FINE STORAGE | 2.46 | 2.46 | 2.46 | 2.46 | 2.46 | 2.46 | 1.00 | 1.000000 | 2.46 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.04 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 2.46 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 1.04 | 17377.56 | 25937.38 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.46 | 2.46 | 2.46 | 2.46 | 48963.19 | 76405.18 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.04 | 0.520550 | 1.04 | 17233.90 | 17377.56 | 8688.78 | 17377.56 | 0.795616 | 0.795610 | 0.795610 | 0.795610 |
PSZ-FINE STORAGE COOLING COIL | 2.46 | 1.23 | 2.46 | 46284.22 | 48963.19 | 24481.60 | 48963.19 | 0.737030 | 0.737030 | 0.737030 | 0.737030 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.04 | 1186.96 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.46 | 2694.76 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.634 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.707 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.507 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.507 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.507 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.066 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2518.900 | 10.634 | 503.780 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2518.900 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11853.648 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11853.648 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27263.390 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27263.390 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
5 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
6 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
13 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
14 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
15 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
16 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.14714251E-14 | -0.15793949E-15 | 0.73826229E-12 | 0.12610148E-15 |
85 | 3 | -0.53553847E-04 | 0.48261894E-06 | -0.37015163E-03 | 0.14168247E-12 |
86 | 2 | 1.1141045 | 0.10720623E-01 | 1.7048811 | -0.70963114E-04 |
87 | 1 | -16.929564 | 0.28051356 | -7.1749370 | 0.32672988 |
88 | 0 | 16.286769 | 0.18002168 | 5.9416824 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.63_SHGC_0.25 | 28 | 1 | VerySmooth | 3.582 | 0.253 | 0.153 | 0.250 |
2 | SKYLIGHT_U_0.9_SHGC_0.4 | 29 | 1 | VerySmooth | 5.108 | 0.400 | 0.232 | 0.401 |
3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.4 | 30 | 1 | VerySmooth | 5.108 | 0.400 | 0.232 | 0.401 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.15304 | 0.57918 | 0.57918 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.81224E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.23173 | 0.24680 | 0.24680 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.23173 | 0.24680 | 0.24680 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10349.98222 | 12419.97866 | 0.86758 | 1.04110 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 30.29133 | 8.20219E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 8130.64880 | 9756.77856 | 0.23241 | 0.27889 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 3.80000 | 5.05843E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 31400.50457 | 37680.60549 | 2.05174 | 2.46208 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30000 | 8.20219E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 21506.81513 | 25808.17816 | 0.51817 | 0.62180 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30000 | 8.20219E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 31798.49469 | 38158.19363 | 0.78016 | 0.93620 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 15626.73 | 1.04110 | 1.04110 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 8748.64 | 0.27889 | 0.27889 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 44912.69 | 2.46208 | 2.46208 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 22989.98 | 0.62180 | 0.62180 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04110 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.46208 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.93620 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 0.93620 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 38158.19422 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 38158.19363 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04110 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04110 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04110 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04110 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04110 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.04110 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.46208 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.46208 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.46208 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.46208 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.46208 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.46208 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.04110 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.46208 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04110 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04110 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04110 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04110 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.04110 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04110 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52055 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.04110 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17233.90167 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17377.56000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8688.78000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 17377.56000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79562 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79561 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79561 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79561 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17377.56000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25937.38445 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04110 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1186.96476 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 25937.38445 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.46208 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.46208 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.46208 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.46208 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.46208 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.46208 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.23104 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.46208 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 46284.21801 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 48963.19000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 24481.59500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 48963.19000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73703 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73703 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73703 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73703 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 48963.19000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 76405.17591 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.46208 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2694.76487 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 76405.17591 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 16569.7 | 9.22 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 47051.4 | 13.31 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 11 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 2.3384849874E-002 | 1.9379677693E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1185937797 | 0.1544035231 | Pass | Pass | 0.4055177841 | 2.5243905957 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 2.7197536926E-002 | 2.8299514367E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.369 | 0.389 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.63_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.582 | 0.253 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.63_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 3.582 | 0.253 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.63_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.582 | 0.253 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.63_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 3.582 | 0.253 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.400 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.400 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.400 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.400 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.400 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.400 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.400 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.400 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.400 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.400 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 4.279 | 0.320 | 0.319 | ||||||||||||
North Total or Average | 6.51 | 3.582 | 0.253 | 0.250 | ||||||||||||
Non-North Total or Average | 26.02 | 4.454 | 0.337 | 0.336 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.6337 | 236.88 | 2518.90 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.62 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.5069 | 1393.41 | 11853.65 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 135.00 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.5069 | 3204.84 | 27263.39 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 310.50 |
Interior Lighting Total | 8.6111 | 4835.13 | 41635.94 | 476.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.00 | AstronomicalClock | - | 83.75 | 83.75 | 123.53 | |
Exterior Lighting Total | 7857.00 | 123.53 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17377.56 | 13825.76 | 3551.80 | 0.80 | 3.15 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 48963.19 | 36087.34 | 12875.85 | 0.74 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 16569.7 | 9.22 | ||||
PSZ-FINE STORAGE COOLING COIL | 47051.4 | 13.31 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 38158.19 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 25937.38 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 76405.18 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.94 | 86.98 | 92.91 | 1.00 | 4.22 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.04 | 1186.96 | 1140.11 | 1.00 | 1.35 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.46 | 2694.76 | 1094.51 | 1.00 | 1.26 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10349.98 | 12419.98 | 52.43 | 0.868 | 1.041 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 23.90 | 23.90 | 0.00812 | 30.29 | 0.00820 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 31400.50 | 37680.61 | 27.04 | 2.052 | 2.462 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.70 | 26.70 | 0.00802 | 31.30 | 0.00820 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00385 | 31.30 | 0.00820 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8130.65 | 9756.78 | 41.19 | 0.232 | 0.279 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00772 | 3.80 | 0.00506 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 21506.82 | 25808.18 | 18.52 | 0.518 | 0.622 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15.56 | 15.56 | 0.00665 | 3.80 | 0.00506 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 31798.49 | 38158.19 | 11.91 | 0.780 | 0.936 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00778 | 3.80 | 0.00506 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.04 | 1.04 | 0.28 | 0.28 | 1.0411 | 1.0411 | 1.0411 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.46 | 2.46 | 0.62 | 0.62 | 2.4621 | 2.4621 | 2.4621 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 38158.194 | 38158.194 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 38158.19 | 38158.19 | 0.936197 | 4.61 | 4.61 | 0.00541307 | 43.33 | 26.86 | 0.01600000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 10.00 | 0.00777619 | 100.0000 | 38158.19 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 17377.560 | 0.000 | 1.041100 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 17377.56 | 16996.76 | 1.041100 | 24.65 | 16.09 | 0.00812771 | 12.00 | 11.09 | 0.00800000 | 30.41 | 0.00820219 | 18.11 | 11.5585 | 23.90 | 0.00811813 | 43.1739 | 10339.20 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 25937.384 | 25937.384 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 25937.38 | 25937.38 | 1.041097 | 13.58 | 10.27 | 0.00657164 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 11.5585 | 21.10 | 0.00772009 | 48.7043 | 8130.65 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 48963.190 | 0.000 | 2.462080 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 48963.19 | 48627.27 | 2.462080 | 27.36 | 16.96 | 0.00804678 | 12.00 | 11.09 | 0.00800000 | 31.30 | 0.00820219 | 18.40 | 14.3751 | 26.70 | 0.00802069 | 36.1164 | 31400.50 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 76405.176 | 76405.176 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 76405.18 | 76405.18 | 2.462084 | 8.87 | 7.20 | 0.00574409 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 14.3751 | 15.56 | 0.00664999 | 59.5053 | 21506.82 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 38158.194 | 38158.194 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1818 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.936197 | 1.10637821 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 38158.19 | 38158.19 | 1.0000 | 1.10637821 | 0.936197 | 4.61 | 4.61 | 0.00541307 | 18215.1 | 43.33 | 26.86 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38158.19 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 10.00 | 0.00777619 | 10.00 | 0.00777619 | 100.0000 | 38158.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17377.560 | 0.000 | 1.041100 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9490 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 17377.56 | 16996.76 | 1.0000 | 1.23034977 | 1.041100 | 24.65 | 16.09 | 0.00812771 | 45471.6 | 12.00 | 11.09 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17377.56 | 30.41 | 0.00820219 | 18.11 | 0.12033533 | 11.5585 | 23.90 | 0.00811797 | 23.90 | 0.00811813 | 43.1739 | 10339.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25937.384 | 25937.384 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.041097 | 1.23034599 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 25937.38 | 25937.38 | 1.0000 | 1.23034599 | 1.041097 | 13.58 | 10.27 | 0.00657164 | 30251.1 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25937.38 | 3.80 | 0.00505843 | 3.80 | 0.12033533 | 11.5585 | 21.01 | 0.00772009 | 21.10 | 0.00772009 | 48.7043 | 8130.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 48963.190 | 0.000 | 2.462080 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7986 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 48963.19 | 48627.27 | 1.0000 | 2.90963361 | 2.462080 | 27.36 | 16.96 | 0.00804678 | 48027.4 | 12.00 | 11.09 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 48963.19 | 31.30 | 0.00820219 | 18.40 | 0.35392745 | 14.3751 | 26.70 | 0.00802069 | 26.70 | 0.00802069 | 36.1164 | 31400.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 76405.176 | 76405.176 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.462084 | 2.90963878 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 76405.18 | 76405.18 | 1.0000 | 2.90963878 | 2.462084 | 8.87 | 7.20 | 0.00574409 | 23368.5 | 40.00 | 20.93 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 76405.18 | 3.80 | 0.00505843 | 3.80 | 0.35392745 | 14.3751 | 15.56 | 0.00664999 | 15.56 | 0.00664999 | 59.5053 | 21506.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE OA CONTROLLER | DifferentialDryBulb | 0.12 | 1.04 | - | |||
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.35 | 2.46 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 1510.50 | 1912.83 | 226.83 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 1510.50 | 1912.83 | 226.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 6.50 | 3.00 | 6.50 | 3.00 |
ZONE2 FINE STORAGE | 2.00 | 3.67 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 8.50 | 6.67 | 6.50 | 3.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 1.438 | 0.374 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 829.38 | 5421.86 | 01-JAN-07:10 | 67123.63 | 29-SEP-13:00 |
Electricity:Building | 615.76 | 4938.86 | 01-JAN-00:10 | 47606.95 | 31-JUL-12:10 |
Electricity:Zone:ZONE1 OFFICE | 62.57 | 1027.15 | 01-JAN-00:10 | 3852.05 | 02-JAN-08:10 |
InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.62 | 453.40 | 01-JAN-00:10 | 1939.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 418.19 | 2726.34 | 01-JAN-00:10 | 33679.30 | 19-JUL-10:40 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 310.51 | 2726.34 | 01-JAN-00:10 | 23173.88 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 24.69 | 483.00 | 05-JAN-06:10 | 1799.45 | 09-FEB-12:30 |
WaterSystems:Electricity | 24.69 | 483.00 | 05-JAN-06:10 | 1799.45 | 09-FEB-12:30 |
Water Heater:WaterSystems:Electricity | 24.69 | 483.00 | 05-JAN-06:10 | 1799.45 | 09-FEB-12:30 |
Fans:Electricity | 47.50 | 0.00 | 01-JAN-00:10 | 6187.02 | 16-OCT-14:50 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.35 | 0.00 | 01-JAN-00:10 | 2305.29 | 16-OCT-14:50 |
Ventilation (simple):Fans:Electricity | 0.35 | 0.00 | 01-JAN-00:10 | 2305.29 | 16-OCT-14:50 |
ElectricityPurchased:Facility | 829.38 | 5421.86 | 01-JAN-07:10 | 67123.63 | 29-SEP-13:00 |
ElectricityPurchased:Plant | 829.38 | 5421.86 | 01-JAN-07:10 | 67123.63 | 29-SEP-13:00 |
Cogeneration:ElectricityPurchased | 829.38 | 5421.86 | 01-JAN-07:10 | 67123.63 | 29-SEP-13:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 829.38 | 5421.86 | 01-JAN-07:10 | 67123.63 | 29-SEP-13:00 |
ElectricityNet:Plant | 829.38 | 5421.86 | 01-JAN-07:10 | 67123.63 | 29-SEP-13:00 |
Cogeneration:ElectricityNet | 829.38 | 5421.86 | 01-JAN-07:10 | 67123.63 | 29-SEP-13:00 |
Electricity:HVAC | 65.40 | 0.00 | 01-JAN-00:10 | 18718.34 | 16-OCT-11:10 |
General:Fans:Electricity | 47.15 | 0.00 | 01-JAN-00:10 | 3881.73 | 03-JAN-08:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 18.25 | 0.00 | 01-JAN-00:10 | 14836.61 | 16-OCT-11:10 |
ExteriorLights:Electricity | 123.53 | 0.00 | 01-JAN-07:00 | 7857.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.53 | 0.00 | 01-JAN-07:00 | 7857.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 66.61 | 2000.00 | 30-APR-11:10 | 34336.40 | 03-JAN-06:10 |
Gas:HVAC | 66.61 | 2000.00 | 30-APR-11:10 | 34336.40 | 03-JAN-06:10 |
Heating:Gas | 66.61 | 2000.00 | 30-APR-11:10 | 34336.40 | 03-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 28-JUN-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 154.18 | 0.00 | 01-JAN-00:10 | 75442.40 | 16-OCT-12:00 |
EnergyTransfer:Building | 87.67 | 0.00 | 01-JAN-00:10 | 32932.61 | 16-OCT-12:00 |
EnergyTransfer:Zone:ZONE1 OFFICE | 37.38 | 0.00 | 01-JAN-00:10 | 13451.54 | 03-JAN-06:10 |
Heating:EnergyTransfer | 7.75 | 0.00 | 01-JAN-00:10 | 24354.76 | 03-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 3.02 | 0.00 | 01-JAN-00:10 | 13451.54 | 03-JAN-06:10 |
Cooling:EnergyTransfer | 79.92 | 0.00 | 01-JAN-00:10 | 32932.61 | 16-OCT-12:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 34.36 | 0.00 | 01-JAN-00:10 | 10489.19 | 16-OCT-11:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 50.29 | 0.00 | 01-JAN-00:10 | 24038.78 | 30-SEP-13:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 4.73 | 0.00 | 01-JAN-00:10 | 15931.62 | 03-JAN-02:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 45.56 | 0.00 | 01-JAN-00:10 | 24038.78 | 30-SEP-13:50 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 66.51 | 0.00 | 01-JAN-00:10 | 44604.44 | 18-AUG-14:40 |
HeatingCoils:EnergyTransfer | 2.39 | 0.00 | 01-JAN-00:10 | 23920.56 | 03-JAN-06:10 |
CoolingCoils:EnergyTransfer | 64.11 | 0.00 | 01-JAN-00:10 | 44604.44 | 18-AUG-14:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 3.021 | -34.356 | 0.000 | 0.000 | 3.642 | 30.619 | 31.946 | 8.603 | 0.000 | 0.216 | 0.000 | 0.000 | -9.045 | 0.000 | -12.413 | -22.233 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 4.729 | -45.562 | 0.000 | 0.000 | 0.000 | 135.003 | 0.000 | 0.000 | 0.000 | 0.386 | 0.001 | 0.000 | 0.000 | 0.000 | -68.583 | -25.972 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 310.507 | 107.336 | 32.902 | 0.000 | 5.694 | 0.002 | 0.000 | -12.750 | 0.000 | -334.512 | -109.177 |
Total Facility | 0.000 | 0.000 | 7.750 | -79.919 | 0.000 | 0.000 | 3.642 | 476.129 | 139.282 | 41.505 | 0.000 | 6.297 | 0.004 | 0.000 | -21.794 | 0.000 | -415.509 | -157.382 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 17-OCT-05:01 | 0.00 | 0.00 | 0.00 | -21491.25 | 0.00 | 0.00 | 34.93 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 21432.24 | 0.00 | -519.79 | 0.00 | -609.23 | 0.00 |
ZONE2 FINE STORAGE | 04-JUL-16:51 | 0.00 | 0.00 | 0.00 | -49043.41 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 47858.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-JUL-16:51 | 0.00 | 0.00 | 0.00 | -49043.41 | 0.00 | 0.00 | 0.00 | 4365.11 | 573.75 | 2488.46 | 0.00 | 0.00 | 41616.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 09-JAN-06:42 | 0.00 | 0.00 | 26359.10 | 0.00 | 0.00 | 0.00 | 50.62 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -810.88 | 0.00 | -1362.22 | -25389.72 |
ZONE2 FINE STORAGE | 02-JAN-06:07 | 0.00 | 0.00 | 61022.91 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2432.91 | -59775.36 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-JAN-06:01 | 0.00 | 0.00 | 86836.52 | 0.00 | 0.00 | 0.00 | 56.06 | 4491.05 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1523.97 | 0.00 | -13512.14 | -78971.30 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0411 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.0411 | 0.1156 | 1.0000 | 0.1203 | 0.1156 | ||
PSZ-FINE STORAGE | 2.4621 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.4621 | 0.1438 | 1.0000 | 0.3539 | 0.1438 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0411 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.0411 | 1.0000 | 1.0000 | 0.1203 | 0.1156 | ||
PSZ-FINE STORAGE | 2.4621 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.4621 | 1.0000 | 1.0000 | 0.3539 | 0.1438 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0411 | 1.0411 | 1.0411 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.4621 | 2.4621 | 2.4621 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0411 | 1.0411 | 1.0411 | 1.0411 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.4621 | 2.4621 | 2.4621 | 2.4621 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0411 | 1.0411 | 1.0411 | 0.1203 | 0.4315 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.4621 | 2.4621 | 2.4621 | 0.3539 | 0.5692 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0411 | 1.0411 | 1.0411 | 1.0411 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.4621 | 2.4621 | 2.4621 | 2.4621 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:46
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 6.50 |
Number of hours cooling loads not met | 3.00 |
Number of hours not met | 9.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 66.61 | 34336.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 18.25 | 14836.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 476.13 | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.53 | 7857.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.35 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 47.15 | 3881.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.69 | 1799.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 829.38 |
Natural Gas | 0.00 | 66.61 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 895.99 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 98.47 |
Space Heating | 0.00 |
Space Cooling | 3.78 |
Fans (All) | 9.82 |
Service Water Heating | 5.11 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 171.53 |
Subtotal | 171.53 |
Natural Gas [MJ/m2] | |
Space Heating | 13.78 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 13.78 |
Subtotal | 13.78 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 53.14 |
Space Heating | 7.43 |
Space Cooling | 2.04 |
Fans (All) | 5.30 |
Service Water Heating | 2.76 |
Receptacle Equipment | 15.55 |
Miscellaneous | 13.79 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.695926E+10 |
February | 0.000 | 0.527422E+10 |
March | 0.000 | 0.616579E+10 |
April | 0.000 | 0.523659E+10 |
May | 0.000 | 0.536177E+10 |
June | 0.000 | 0.518400E+10 |
July | 0.000 | 0.535680E+10 |
August | 0.000 | 0.535680E+10 |
September | 0.000 | 0.518400E+10 |
October | 0.000 | 0.535755E+10 |
November | 0.000 | 0.532881E+10 |
December | 0.000 | 0.584895E+10 |
Annual Sum or Average | 0.666146E+11 | |
Minimum of Months | 0.000 | 0.518400E+10 |
Maximum of Months | 0.000 | 0.695926E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.695926E+10 |
February | 0.000 | 0.527422E+10 |
March | 0.000 | 0.616579E+10 |
April | 0.000 | 0.523659E+10 |
May | 0.000 | 0.536177E+10 |
June | 0.000 | 0.518400E+10 |
July | 0.000 | 0.535680E+10 |
August | 0.000 | 0.535680E+10 |
September | 0.000 | 0.518400E+10 |
October | 0.000 | 0.535755E+10 |
November | 0.000 | 0.532881E+10 |
December | 0.000 | 0.584895E+10 |
Annual Sum or Average | 0.666146E+11 | |
Minimum of Months | 0.000 | 0.518400E+10 |
Maximum of Months | 0.000 | 0.695926E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Meter
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.695926E+10 |
February | 0.000 | 0.527422E+10 |
March | 0.000 | 0.616579E+10 |
April | 0.000 | 0.523659E+10 |
May | 0.000 | 0.536177E+10 |
June | 0.000 | 0.518400E+10 |
July | 0.000 | 0.535680E+10 |
August | 0.000 | 0.535680E+10 |
September | 0.000 | 0.518400E+10 |
October | 0.000 | 0.535755E+10 |
November | 0.000 | 0.532881E+10 |
December | 0.000 | 0.584895E+10 |
Annual Sum or Average | 0.666146E+11 | |
Minimum of Months | 0.000 | 0.518400E+10 |
Maximum of Months | 0.000 | 0.695926E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.695926E+10 |
February | 0.000 | 0.527422E+10 |
March | 0.000 | 0.616579E+10 |
April | 0.000 | 0.523659E+10 |
May | 0.000 | 0.536177E+10 |
June | 0.000 | 0.518400E+10 |
July | 0.000 | 0.535680E+10 |
August | 0.000 | 0.535680E+10 |
September | 0.000 | 0.518400E+10 |
October | 0.000 | 0.535755E+10 |
November | 0.000 | 0.532881E+10 |
December | 0.000 | 0.584895E+10 |
Annual Sum or Average | 0.666146E+11 | |
Minimum of Months | 0.000 | 0.518400E+10 |
Maximum of Months | 0.000 | 0.695926E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.695926E+10 |
February | 0.000 | 0.527422E+10 |
March | 0.000 | 0.616579E+10 |
April | 0.000 | 0.523659E+10 |
May | 0.000 | 0.536177E+10 |
June | 0.000 | 0.518400E+10 |
July | 0.000 | 0.535680E+10 |
August | 0.000 | 0.535680E+10 |
September | 0.000 | 0.518400E+10 |
October | 0.000 | 0.535755E+10 |
November | 0.000 | 0.532881E+10 |
December | 0.000 | 0.584895E+10 |
Annual Sum or Average | 0.666146E+11 | |
Minimum of Months | 0.000 | 0.518400E+10 |
Maximum of Months | 0.000 | 0.695926E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.695926E+10 |
February | 0.000 | 0.527422E+10 |
March | 0.000 | 0.616579E+10 |
April | 0.000 | 0.523659E+10 |
May | 0.000 | 0.536177E+10 |
June | 0.000 | 0.518400E+10 |
July | 0.000 | 0.535680E+10 |
August | 0.000 | 0.535680E+10 |
September | 0.000 | 0.518400E+10 |
October | 0.000 | 0.535755E+10 |
November | 0.000 | 0.532881E+10 |
December | 0.000 | 0.584895E+10 |
Annual Sum or Average | 0.666146E+11 | |
Minimum of Months | 0.000 | 0.518400E+10 |
Maximum of Months | 0.000 | 0.695926E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.695926E+10 |
February | 0.000 | 0.527422E+10 |
March | 0.000 | 0.616579E+10 |
April | 0.000 | 0.523659E+10 |
May | 0.000 | 0.536177E+10 |
June | 0.000 | 0.518400E+10 |
July | 0.000 | 0.535680E+10 |
August | 0.000 | 0.535680E+10 |
September | 0.000 | 0.518400E+10 |
October | 0.000 | 0.535755E+10 |
November | 0.000 | 0.532881E+10 |
December | 0.000 | 0.584895E+10 |
Annual Sum or Average | 0.666146E+11 | |
Minimum of Months | 0.000 | 0.518400E+10 |
Maximum of Months | 0.000 | 0.695926E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Meter
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.695926E+10 |
February | 0.000 | 0.527422E+10 |
March | 0.000 | 0.616579E+10 |
April | 0.000 | 0.523659E+10 |
May | 0.000 | 0.536177E+10 |
June | 0.000 | 0.518400E+10 |
July | 0.000 | 0.535680E+10 |
August | 0.000 | 0.535680E+10 |
September | 0.000 | 0.518400E+10 |
October | 0.000 | 0.535755E+10 |
November | 0.000 | 0.532881E+10 |
December | 0.000 | 0.584895E+10 |
Annual Sum or Average | 0.666146E+11 | |
Minimum of Months | 0.000 | 0.518400E+10 |
Maximum of Months | 0.000 | 0.695926E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Meter
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.695926E+10 |
February | 0.000 | 0.527422E+10 |
March | 0.000 | 0.616579E+10 |
April | 0.000 | 0.523659E+10 |
May | 0.000 | 0.536177E+10 |
June | 0.000 | 0.518400E+10 |
July | 0.000 | 0.535680E+10 |
August | 0.000 | 0.535680E+10 |
September | 0.000 | 0.518400E+10 |
October | 0.000 | 0.535755E+10 |
November | 0.000 | 0.532881E+10 |
December | 0.000 | 0.584895E+10 |
Annual Sum or Average | 0.666146E+11 | |
Minimum of Months | 0.000 | 0.518400E+10 |
Maximum of Months | 0.000 | 0.695926E+10 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.836691E+09 | 3677.16 | 21-JAN-15:30 | 14.00 | 10.94 | 0.234318E+09 | 301.61 | 18-JAN-15:00 | 22.00 | 15.38 |
February | 0.734323E+09 | 3658.83 | 03-FEB-15:10 | 22.67 | 9.05 | 0.216609E+09 | 301.63 | 01-FEB-13:50 | 19.83 | 15.74 |
March | 0.966457E+09 | 4725.41 | 23-MAR-16:00 | 21.00 | 17.18 | 0.252900E+09 | 301.60 | 24-MAR-14:09 | 18.83 | 15.80 |
April | 0.248089E+10 | 17752.58 | 28-APR-05:03 | 14.00 | 12.23 | 0.245730E+09 | 301.62 | 13-APR-13:30 | 20.50 | 15.06 |
May | 0.299064E+10 | 17771.75 | 04-MAY-05:03 | 14.33 | 12.38 | 0.257321E+09 | 301.64 | 24-MAY-10:00 | 21.00 | 15.41 |
June | 0.427460E+10 | 18998.63 | 23-JUN-05:02 | 15.17 | 12.71 | 0.258647E+09 | 301.61 | 03-JUN-15:09 | 19.00 | 14.24 |
July | 0.553316E+10 | 19045.49 | 10-JUL-05:01 | 17.00 | 13.93 | 0.248960E+09 | 301.63 | 29-JUL-15:20 | 23.67 | 19.77 |
August | 0.576383E+10 | 18403.36 | 22-AUG-05:02 | 15.00 | 13.18 | 0.268864E+09 | 301.63 | 15-AUG-15:50 | 23.33 | 19.56 |
September | 0.437813E+10 | 19412.28 | 29-SEP-05:01 | 18.30 | 11.31 | 0.248877E+09 | 301.62 | 09-SEP-13:30 | 23.00 | 18.41 |
October | 0.393569E+10 | 21492.81 | 17-OCT-05:01 | 17.00 | 8.53 | 0.247980E+09 | 301.64 | 18-OCT-12:20 | 23.67 | 17.92 |
November | 0.143087E+10 | 3924.50 | 18-NOV-15:30 | 23.50 | 13.89 | 0.233573E+09 | 301.62 | 30-NOV-15:09 | 20.50 | 12.90 |
December | 0.103101E+10 | 3913.26 | 05-DEC-15:20 | 24.33 | 12.94 | 0.238617E+09 | 301.61 | 20-DEC-14:39 | 19.40 | 11.33 |
Annual Sum or Average | 0.343563E+11 | 0.295240E+10 | ||||||||
Minimum of Months | 0.734323E+09 | 3658.83 | 14.00 | 8.53 | 0.216609E+09 | 301.60 | 18.83 | 11.33 | ||
Maximum of Months | 0.576383E+10 | 21492.81 | 24.33 | 17.18 | 0.268864E+09 | 301.64 | 23.67 | 19.77 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.274632E+09 | 6276.16 | 06-JAN-07:10 | 9.00 | 2.50 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.277475E+09 | 6942.19 | 28-FEB-07:10 | 11.33 | 9.16 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.549786E+09 | 10317.85 | 10-MAR-07:10 | 10.67 | 7.38 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.195315E+10 | 45468.15 | 30-APR-14:21 | 23.50 | 16.60 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.226382E+10 | 13307.82 | 03-MAY-13:00 | 24.00 | 15.03 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.592450E+10 | 44639.69 | 25-JUN-14:21 | 21.50 | 16.68 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.117179E+11 | 49047.36 | 04-JUL-16:51 | 19.00 | 15.26 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.114804E+11 | 43846.30 | 19-AUG-17:51 | 23.00 | 17.25 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.604747E+10 | 46040.32 | 03-SEP-12:41 | 22.00 | 16.40 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.437984E+10 | 45118.57 | 15-OCT-17:01 | 26.33 | 14.08 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.355007E+09 | 6891.38 | 09-NOV-07:10 | 14.67 | 8.44 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.338445E+09 | 7937.40 | 27-DEC-07:10 | 9.50 | 2.95 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.455624E+11 | 0.00 | ||||||||
Minimum of Months | 0.274632E+09 | 6276.16 | 9.00 | 2.50 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.117179E+11 | 49047.36 | 26.33 | 17.25 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 | 8.36 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.63 | 5.43 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.00 | 0.00 | 18.42 | 17.39 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.779417E+09 | 26358.83 | 09-JAN-06:42 | 2.83 |
February | 0.436408E+09 | 26071.81 | 28-FEB-06:01 | 10.17 |
March | 0.639023E+09 | 26286.11 | 30-MAR-05:01 | 4.97 |
April | 0.142821E+09 | 26057.53 | 01-APR-05:01 | 7.83 |
May | 0.104321E+09 | 3989.86 | 15-MAY-06:05 | 11.33 |
June | 57101885.34 | 1594.57 | 22-JUN-06:03 | 14.50 |
July | 6237784.66 | 2616.23 | 18-JUL-06:05 | 16.33 |
August | 15973233.74 | 2154.98 | 19-AUG-06:05 | 18.33 |
September | 55550197.98 | 1874.04 | 30-SEP-06:05 | 23.78 |
October | 63529834.38 | 1933.21 | 30-OCT-06:30 | 11.50 |
November | 0.230597E+09 | 25515.40 | 27-NOV-06:02 | 10.67 |
December | 0.489745E+09 | 26094.31 | 15-DEC-06:01 | 6.00 |
Annual Sum or Average | 0.302073E+10 | |||
Minimum of Months | 6237784.66 | 1594.57 | 2.83 | |
Maximum of Months | 0.779417E+09 | 26358.83 | 23.78 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121741E+10 | 61023.43 | 02-JAN-06:07 | 11.00 |
February | 0.351994E+09 | 2907.33 | 27-FEB-08:00 | 9.00 |
March | 0.405670E+09 | 43666.07 | 30-MAR-05:01 | 4.97 |
April | 0.302175E+09 | 2591.39 | 21-APR-07:00 | 13.00 |
May | 0.218576E+09 | 2857.89 | 25-MAY-07:00 | 14.00 |
June | 0.197983E+09 | 2676.57 | 06-JUN-07:00 | 17.00 |
July | 0.141687E+09 | 2536.66 | 08-JUL-07:00 | 17.00 |
August | 0.200865E+09 | 2559.40 | 21-AUG-07:00 | 17.00 |
September | 0.204947E+09 | 2671.03 | 27-SEP-07:00 | 16.00 |
October | 0.277134E+09 | 3098.52 | 14-OCT-08:65 | 27.67 |
November | 0.460206E+09 | 2726.34 | 01-NOV-07:00 | 11.00 |
December | 0.750532E+09 | 2887.84 | 16-DEC-13:00 | 26.00 |
Annual Sum or Average | 0.472918E+10 | |||
Minimum of Months | 0.141687E+09 | 2536.66 | 4.97 | |
Maximum of Months | 0.121741E+10 | 61023.43 | 27.67 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.256100E+10 | 1939.55 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.233575E+10 | 1939.55 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.266872E+10 | 1939.55 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.252182E+10 | 1939.55 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.261486E+10 | 1939.55 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.257569E+10 | 1939.55 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.256100E+10 | 1939.55 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.266872E+10 | 1939.55 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.252182E+10 | 1939.55 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.256100E+10 | 1939.55 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.246796E+10 | 1939.55 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.256100E+10 | 1939.55 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.306193E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.233575E+10 | 1939.55 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.266872E+10 | 1939.55 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112294E+11 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102778E+11 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.118738E+11 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.111270E+11 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.115516E+11 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.114492E+11 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112294E+11 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.118738E+11 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.111270E+11 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112294E+11 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108048E+11 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112294E+11 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135003E+12 | ||||
Minimum of Months | 0.102778E+11 | 10075.60 | 0.00 | 0.00 | |
Maximum of Months | 0.118738E+11 | 10075.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.258277E+11 | 23173.88 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.236390E+11 | 23173.88 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.273097E+11 | 23173.88 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.255921E+11 | 23173.88 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.265687E+11 | 23173.88 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.263332E+11 | 23173.88 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.258277E+11 | 23173.88 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.273097E+11 | 23173.88 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.255921E+11 | 23173.88 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.258277E+11 | 23173.88 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.248511E+11 | 23173.88 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.258277E+11 | 23173.88 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.236390E+11 | 23173.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.273097E+11 | 23173.88 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3614234.76 | 0.125323E+10 |
February | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1410821.22 | 0.129694E+10 |
March | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17214.15 | 0.164548E+10 |
April | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4656433.43 | 0.108974E+10 |
May | 0.565842E+09 | 0.261486E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63806.98 | 0.119686E+10 |
June | 0.565842E+09 | 0.257569E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1204824.26 | 0.847475E+09 |
July | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30662884.16 | 0.554062E+09 |
August | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31054602.24 | 0.631549E+09 |
September | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48219495.19 | 0.731323E+09 |
October | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89334875.70 | 0.768135E+09 |
November | 0.522316E+09 | 0.246796E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1404096.30 | 0.120749E+10 |
December | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4833716.09 | 0.119089E+10 |
Annual Sum or Average | 0.659424E+10 | 0.306193E+11 | 0.319458E+11 | 0.216477E+09 | 0.124132E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17214.15 | 0.554062E+09 |
Maximum of Months | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89334875.70 | 0.164548E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16891060.47 | 0.506359E+10 |
February | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31511.92 | 0.632637E+10 |
March | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769486E+10 |
April | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1022232.19 | 0.632833E+10 |
May | 0.00 | 0.115516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772146E+10 |
June | 0.00 | 0.114492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547824E+10 |
July | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7080054.59 | 0.423665E+10 |
August | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4297826.60 | 0.484505E+10 |
September | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96499748.28 | 0.443660E+10 |
October | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243048E+09 | 0.538533E+10 |
November | 0.00 | 0.108048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9820882.79 | 0.569228E+10 |
December | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7291980.58 | 0.537471E+10 |
Annual Sum or Average | 0.135003E+12 | 0.385983E+09 | 0.685835E+11 | ||||||
Minimum of Months | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423665E+10 |
Maximum of Months | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243048E+09 | 0.772146E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470230E+09 | 0.139828E+11 |
February | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31281633.90 | 0.195688E+11 |
March | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52849535.97 | 0.237593E+11 |
April | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107665E+09 | 0.200838E+11 |
May | 0.00 | 0.265687E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264721E+11 |
June | 0.00 | 0.263332E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213962E+11 |
July | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211357E+11 |
August | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230257E+11 |
September | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70135475.43 | 0.189430E+11 |
October | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545378E+09 | 0.215626E+11 |
November | 0.00 | 0.248511E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130747E+09 | 0.187586E+11 |
December | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446846E+09 | 0.164495E+11 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | 0.185513E+10 | 0.245138E+12 | |||||
Minimum of Months | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139828E+11 |
Maximum of Months | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545378E+09 | 0.264721E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1939.55 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 735.98 | 18-JAN-13:00 | 6898.48 | 09-JAN-07:10 |
February | 659.25 | 01-FEB-08:09 | 1939.55 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 626.11 | 01-FEB-12:10 | 5384.23 | 09-FEB-07:05 |
March | 659.25 | 01-MAR-08:09 | 1939.55 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 11-MAR-14:00 | 6320.07 | 30-MAR-06:10 |
April | 659.25 | 01-APR-07:10 | 1939.55 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 741.54 | 26-APR-11:10 | 4449.01 | 17-APR-16:05 |
May | 659.25 | 01-MAY-07:10 | 1939.55 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.31 | 04-MAY-12:00 | 4297.71 | 26-MAY-06:03 |
June | 659.25 | 01-JUN-07:10 | 1939.55 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.66 | 29-JUN-11:10 | 3779.74 | 05-JUN-06:02 |
July | 659.25 | 01-JUL-07:10 | 1939.55 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1449.34 | 19-JUL-12:00 | 3230.77 | 17-JUL-06:10 |
August | 659.25 | 01-AUG-07:10 | 1939.55 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1435.75 | 18-AUG-12:00 | 3565.65 | 28-AUG-07:00 |
September | 659.25 | 01-SEP-07:10 | 1939.55 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4123.48 | 29-SEP-12:00 | 4017.95 | 20-SEP-06:01 |
October | 659.25 | 02-OCT-07:10 | 1939.55 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4498.53 | 16-OCT-11:10 | 4822.51 | 19-OCT-06:01 |
November | 659.25 | 01-NOV-07:10 | 1939.55 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.75 | 19-NOV-13:00 | 5111.43 | 30-NOV-07:05 |
December | 659.25 | 01-DEC-08:09 | 1939.55 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 738.96 | 19-DEC-13:00 | 6034.94 | 22-DEC-07:05 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 3230.77 | |||||
Maximum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4498.53 | 6898.48 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1710.89 | 15-JAN-10:00 | 8436.59 | 27-JAN-05:00 |
February | 0.00 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.52 | 01-FEB-12:00 | 9634.64 | 25-FEB-16:05 |
March | 0.00 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 14112.69 | 28-MAR-15:05 |
April | 0.00 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.07 | 02-APR-12:00 | 14344.03 | 17-APR-16:25 |
May | 0.00 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 13258.79 | 12-MAY-16:00 |
June | 0.00 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 8384.54 | 12-JUN-16:00 |
July | 0.00 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.46 | 31-JUL-13:00 | 8115.86 | 20-JUL-17:00 |
August | 0.00 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.46 | 17-AUG-14:00 | 6423.50 | 21-AUG-17:00 |
September | 0.00 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4615.77 | 29-SEP-15:10 | 7658.14 | 02-SEP-15:10 |
October | 0.00 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4454.37 | 14-OCT-15:10 | 8894.84 | 23-OCT-15:05 |
November | 0.00 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 796.96 | 19-NOV-13:00 | 8447.08 | 30-NOV-07:10 |
December | 0.00 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 978.27 | 25-DEC-12:00 | 8515.81 | 12-DEC-16:05 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6423.50 | |||
Maximum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4615.77 | 14344.03 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23173.88 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8387.65 | 14-JAN-11:00 | 25144.15 | 27-JAN-05:00 |
February | 0.00 | 23173.88 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5274.78 | 01-FEB-12:00 | 32625.99 | 25-FEB-13:05 |
March | 0.00 | 23173.88 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2902.38 | 11-MAR-13:10 | 37691.51 | 28-MAR-08:00 |
April | 0.00 | 23173.88 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5474.63 | 01-APR-12:10 | 41683.90 | 17-APR-15:55 |
May | 0.00 | 23173.88 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 40771.05 | 12-MAY-16:00 |
June | 0.00 | 23173.88 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 23558.26 | 12-JUN-16:00 |
July | 0.00 | 23173.88 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 30218.83 | 20-JUL-09:00 |
August | 0.00 | 23173.88 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 21722.19 | 22-AUG-16:00 |
September | 0.00 | 23173.88 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6649.35 | 29-SEP-10:12 | 27453.14 | 02-SEP-15:00 |
October | 0.00 | 23173.88 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18772.32 | 14-OCT-12:10 | 30617.03 | 07-OCT-08:00 |
November | 0.00 | 23173.88 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5479.68 | 19-NOV-13:00 | 24390.13 | 01-NOV-08:00 |
December | 0.00 | 23173.88 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11321.09 | 18-DEC-11:00 | 29992.24 | 12-DEC-13:05 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21722.19 | ||||
Maximum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 18772.32 | 41683.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3677.16 | 21-JAN-15:30 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.21 |
February | 3658.83 | 03-FEB-15:10 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.37 |
March | 4725.41 | 23-MAR-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.32 |
April | 17752.58 | 28-APR-05:03 | 217.55 | 1738.04 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 657.89 |
May | 17771.75 | 04-MAY-05:03 | 217.55 | 1738.04 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 609.47 |
June | 18998.63 | 23-JUN-05:02 | 362.59 | 2896.74 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.01 |
July | 19045.49 | 10-JUL-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.65 |
August | 18403.36 | 22-AUG-05:02 | 362.59 | 2896.74 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 686.93 |
September | 19412.28 | 29-SEP-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.07 |
October | 21492.81 | 17-OCT-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 609.23 |
November | 3924.50 | 18-NOV-15:30 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.29 |
December | 3913.26 | 05-DEC-15:20 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 27.05 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3658.83 | 217.55 | 1738.04 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21492.81 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 27.05 | 686.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6276.16 | 06-JAN-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3218.00 |
February | 6942.19 | 28-FEB-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3087.88 |
March | 10317.85 | 10-MAR-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.30 |
April | 45468.15 | 30-APR-14:21 | 0.00 | 9482.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2441.39 |
May | 13307.82 | 03-MAY-13:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 787.10 |
June | 44639.69 | 25-JUN-14:21 | 0.00 | 8297.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3402.59 |
July | 49047.36 | 04-JUL-16:51 | 0.00 | 10668.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43846.30 | 19-AUG-17:51 | 0.00 | 10668.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1124.23 |
September | 46040.32 | 03-SEP-12:41 | 0.00 | 10668.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2844.77 |
October | 45118.57 | 15-OCT-17:01 | 0.00 | 10668.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.30 |
November | 6891.38 | 09-NOV-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1509.88 |
December | 7937.40 | 27-DEC-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2792.55 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6276.16 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49047.36 | 0.00 | 10668.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3402.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 5452.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8237.44 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8232.47 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12271.29 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8111.53 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6278.20 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5149.19 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6938.80 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7718.13 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11947.95 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9339.21 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 5452.68 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12271.29 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.694309E+11 | 54731.81 | 13-JAN-16:00 | 0.695926E+10 | 34336.40 | 03-JAN-06:10 |
February | 0.627409E+11 | 52091.27 | 03-FEB-14:50 | 0.527422E+10 | 11606.23 | 28-FEB-06:10 |
March | 0.712577E+11 | 52663.39 | 23-MAR-14:09 | 0.616579E+10 | 26946.04 | 30-MAR-05:10 |
April | 0.665438E+11 | 57926.15 | 26-APR-12:00 | 0.523659E+10 | 11966.06 | 01-APR-05:10 |
May | 0.682855E+11 | 56377.03 | 04-MAY-12:09 | 0.536177E+10 | 4694.98 | 15-MAY-06:10 |
June | 0.687008E+11 | 59229.16 | 29-JUN-12:20 | 0.518400E+10 | 2000.00 | 01-JUN-00:10 |
July | 0.711117E+11 | 64795.41 | 31-JUL-13:09 | 0.535680E+10 | 2000.00 | 01-JUL-00:10 |
August | 0.754408E+11 | 65371.56 | 17-AUG-13:00 | 0.535680E+10 | 2000.00 | 01-AUG-00:10 |
September | 0.688901E+11 | 67123.63 | 29-SEP-12:00 | 0.518400E+10 | 2000.00 | 01-SEP-00:10 |
October | 0.707732E+11 | 66964.89 | 16-OCT-10:00 | 0.535755E+10 | 3112.83 | 30-OCT-06:30 |
November | 0.665800E+11 | 54729.95 | 29-NOV-16:00 | 0.532881E+10 | 8484.35 | 27-NOV-06:10 |
December | 0.696204E+11 | 55424.52 | 05-DEC-16:40 | 0.584895E+10 | 12809.75 | 15-DEC-07:10 |
Annual Sum or Average | 0.829376E+12 | 0.666146E+11 | ||||
Minimum of Months | 0.627409E+11 | 52091.27 | 0.518400E+10 | 2000.00 | ||
Maximum of Months | 0.754408E+11 | 67123.63 | 0.695926E+10 | 34336.40 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.396181E+11 | 0.121721E+11 | 0.115358E+11 | 0.00 | 0.387388E+10 | 0.00 | 0.00 | 0.115420E+09 | 0.00 | 0.00 | 0.00 | 0.211565E+10 | 0.00 |
February | 0.362526E+11 | 0.104042E+11 | 0.105871E+11 | 0.00 | 0.354077E+10 | 0.00 | 0.00 | 33025070.65 | 0.00 | 0.00 | 0.00 | 0.192319E+10 | 0.00 |
March | 0.418523E+11 | 0.106635E+11 | 0.123357E+11 | 0.00 | 0.416057E+10 | 0.00 | 0.00 | 82870026.63 | 0.00 | 0.00 | 0.00 | 0.216279E+10 | 0.00 |
April | 0.392410E+11 | 0.948026E+10 | 0.114862E+11 | 0.00 | 0.384788E+10 | 0.00 | 0.00 | 0.445344E+09 | 0.00 | 0.00 | 0.00 | 0.204308E+10 | 0.00 |
May | 0.407352E+11 | 0.905126E+10 | 0.119357E+11 | 0.00 | 0.399802E+10 | 0.00 | 0.00 | 0.469127E+09 | 0.00 | 0.00 | 0.00 | 0.209617E+10 | 0.00 |
June | 0.403581E+11 | 0.839128E+10 | 0.118862E+11 | 0.00 | 0.405322E+10 | 0.00 | 0.00 | 0.198151E+10 | 0.00 | 0.00 | 0.00 | 0.203061E+10 | 0.00 |
July | 0.396181E+11 | 0.883441E+10 | 0.115358E+11 | 0.00 | 0.412881E+10 | 0.00 | 0.00 | 0.495500E+10 | 0.00 | 0.00 | 0.00 | 0.203957E+10 | 0.00 |
August | 0.418523E+11 | 0.946140E+10 | 0.123357E+11 | 0.00 | 0.433852E+10 | 0.00 | 0.00 | 0.536344E+10 | 0.00 | 0.00 | 0.00 | 0.208944E+10 | 0.00 |
September | 0.392410E+11 | 0.996110E+10 | 0.114862E+11 | 0.00 | 0.400026E+10 | 0.00 | 0.00 | 0.219868E+10 | 0.00 | 0.00 | 0.00 | 0.200288E+10 | 0.00 |
October | 0.396181E+11 | 0.111632E+11 | 0.115358E+11 | 0.00 | 0.401479E+10 | 0.00 | 0.00 | 0.237671E+10 | 0.00 | 0.00 | 0.00 | 0.206460E+10 | 0.00 |
November | 0.381239E+11 | 0.115639E+11 | 0.110862E+11 | 0.00 | 0.369061E+10 | 0.00 | 0.00 | 0.100202E+09 | 0.00 | 0.00 | 0.00 | 0.201505E+10 | 0.00 |
December | 0.396181E+11 | 0.123795E+11 | 0.115358E+11 | 0.00 | 0.384908E+10 | 0.00 | 0.00 | 0.133154E+09 | 0.00 | 0.00 | 0.00 | 0.210480E+10 | 0.00 |
Annual Sum or Average | 0.476129E+12 | 0.123526E+12 | 0.139282E+12 | 0.474964E+11 | 0.00 | 0.182545E+11 | 0.246879E+11 | ||||||
Minimum of Months | 0.362526E+11 | 0.839128E+10 | 0.105871E+11 | 0.00 | 0.354077E+10 | 0.00 | 0.00 | 33025070.65 | 0.00 | 0.00 | 0.00 | 0.192319E+10 | 0.00 |
Maximum of Months | 0.418523E+11 | 0.123795E+11 | 0.123357E+11 | 0.00 | 0.433852E+10 | 0.00 | 0.00 | 0.536344E+10 | 0.00 | 0.00 | 0.00 | 0.216279E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.695926E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.527422E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.616579E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.523659E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.536177E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.518400E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.535680E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.535680E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.518400E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.535755E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.532881E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.584895E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.666146E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.518400E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.695926E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35189.04 | 02-JAN-09:09 | 7857.00 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 3881.73 | 03-JAN-08:20 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35189.04 | 01-FEB-09:09 | 7857.00 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 3881.73 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35189.04 | 01-MAR-09:09 | 7857.00 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 3881.73 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35189.04 | 01-APR-08:09 | 7857.00 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 3881.73 | 04-APR-14:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35189.04 | 01-MAY-08:09 | 7857.00 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 3881.73 | 01-MAY-09:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35189.04 | 01-JUN-08:09 | 7857.00 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 4458.05 | 29-JUN-10:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35189.04 | 01-JUL-08:09 | 7857.00 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6187.02 | 19-JUL-10:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35189.04 | 01-AUG-08:09 | 7857.00 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6187.02 | 14-AUG-11:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35189.04 | 01-SEP-08:09 | 7857.00 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 6187.02 | 29-SEP-10:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35189.04 | 02-OCT-08:09 | 7857.00 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 6187.02 | 14-OCT-12:39 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35189.04 | 01-NOV-08:09 | 7857.00 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 3881.73 | 01-NOV-06:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35189.04 | 01-DEC-09:09 | 7857.00 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 3881.73 | 20-DEC-11:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35189.04 | 7857.00 | 10112.62 | 0.00 | 3881.73 | 0.00 | 0.00 | |||||
Maximum of Months | 35189.04 | 7857.00 | 10112.62 | 0.00 | 6187.02 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 1429.18 | 24-JAN-15:20 | 0.00 | 0.00 | 0.00 | 1799.13 | 30-JAN-12:39 | 0.00 |
February | 1291.25 | 01-FEB-12:09 | 0.00 | 0.00 | 0.00 | 1799.45 | 09-FEB-12:30 | 0.00 |
March | 1723.49 | 23-MAR-14:09 | 0.00 | 0.00 | 0.00 | 1797.52 | 01-MAR-12:39 | 0.00 |
April | 7008.96 | 26-APR-13:09 | 0.00 | 0.00 | 0.00 | 1791.54 | 01-APR-11:09 | 0.00 |
May | 5446.32 | 04-MAY-12:09 | 0.00 | 0.00 | 0.00 | 1783.26 | 03-MAY-11:39 | 0.00 |
June | 8327.75 | 29-JUN-13:09 | 0.00 | 0.00 | 0.00 | 1775.55 | 01-JUN-11:09 | 0.00 |
July | 12199.77 | 31-JUL-14:20 | 0.00 | 0.00 | 0.00 | 1769.32 | 01-JUL-11:00 | 0.00 |
August | 12259.37 | 18-AUG-14:39 | 0.00 | 0.00 | 0.00 | 1768.41 | 30-AUG-11:39 | 0.00 |
September | 14256.75 | 29-SEP-11:00 | 0.00 | 0.00 | 0.00 | 1773.94 | 30-SEP-11:00 | 0.00 |
October | 14836.61 | 16-OCT-11:09 | 0.00 | 0.00 | 0.00 | 1781.25 | 30-OCT-11:09 | 0.00 |
November | 1568.31 | 18-NOV-13:00 | 0.00 | 0.00 | 0.00 | 1789.75 | 29-NOV-12:09 | 0.00 |
December | 1572.29 | 05-DEC-14:00 | 0.00 | 0.00 | 0.00 | 1796.03 | 28-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1291.25 | 0.00 | 0.00 | 0.00 | 1768.41 | 0.00 | ||
Maximum of Months | 14836.61 | 0.00 | 0.00 | 0.00 | 1799.45 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 54731.81 | 13-JAN-16:00 | 31277.33 | 10112.62 | 7857.00 | 0.00 | 3881.73 | 0.00 | 0.00 | 0.03 | 0.00 |
February | 52091.27 | 03-FEB-14:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3881.73 | 0.00 | 0.00 | 1182.62 | 0.00 |
March | 52663.39 | 23-MAR-14:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3881.73 | 0.00 | 0.00 | 1723.49 | 0.00 |
April | 57926.15 | 26-APR-12:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3881.73 | 0.00 | 0.00 | 6993.67 | 0.00 |
May | 56377.03 | 04-MAY-12:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3881.73 | 0.00 | 0.00 | 5446.32 | 0.00 |
June | 59229.16 | 29-JUN-12:20 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4342.79 | 0.00 | 0.00 | 7848.24 | 0.00 |
July | 64795.41 | 31-JUL-13:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6187.02 | 0.00 | 0.00 | 11603.71 | 0.00 |
August | 65371.56 | 17-AUG-13:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6187.02 | 0.00 | 0.00 | 12216.31 | 0.00 |
September | 67123.63 | 29-SEP-12:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6187.02 | 0.00 | 0.00 | 13895.59 | 0.00 |
October | 66964.89 | 16-OCT-10:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6187.02 | 0.00 | 0.00 | 13765.38 | 0.00 |
November | 54729.95 | 29-NOV-16:00 | 31277.33 | 10112.62 | 7857.00 | 0.00 | 3881.73 | 0.00 | 0.00 | 0.09 | 0.00 |
December | 55424.52 | 05-DEC-16:40 | 31277.33 | 10112.62 | 7857.00 | 0.00 | 3881.73 | 0.00 | 0.00 | 694.47 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 52091.27 | 31277.33 | 10112.62 | 0.00 | 0.00 | 3881.73 | 0.00 | 0.00 | 0.03 | 0.00 | |
Maximum of Months | 67123.63 | 35189.04 | 10112.62 | 7857.00 | 0.00 | 6187.02 | 0.00 | 0.00 | 13895.59 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 34336.40 | 03-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 11606.23 | 28-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 26946.04 | 30-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 11966.06 | 01-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 4694.98 | 15-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 2000.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 2000.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 2000.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 2000.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 3112.83 | 30-OCT-06:30 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 8484.35 | 27-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 12809.75 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 2000.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 34336.40 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 20.26 | 2.50 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.67 | 20.49 | 0.67 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.83 | 20.37 | 1.83 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.33 | 20.49 | 0.33 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.51 | 0.67 | 24.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.53 | 0.17 | 24.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.53 | 1.83 | 24.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.51 | 0.33 | 24.51 |
November | 0.33 | 20.45 | 0.33 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.43 | 0.83 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6.50 | 20.36 | 6.50 | 20.36 | 3.00 | 24.52 | 3.00 | 24.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 20.49 | 2.50 | 20.49 | 1.83 | 24.53 | 1.83 | 24.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 14.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 14.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.26 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.28 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.55 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.00 | 14.97 | 0.00 | 3.67 | 27.38 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 14.99 | 0.00 | 0.00 | 1.50 | 27.55 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 294.00 | 22.85 | 59.83 | 21.20 | 59.83 | 21.20 |
February | 273.50 | 22.89 | 30.83 | 21.17 | 30.83 | 21.17 |
March | 306.17 | 22.81 | 49.50 | 21.64 | 40.00 | 21.11 |
April | 167.17 | 23.31 | 63.33 | 23.73 | 3.83 | 21.11 |
May | 134.17 | 23.46 | 81.83 | 23.89 | 0.00 | 0.00 |
June | 32.67 | 23.60 | 210.33 | 23.90 | 0.00 | 0.00 |
July | 7.00 | 23.81 | 293.00 | 23.90 | 5.67 | 23.92 |
August | 14.00 | 23.88 | 314.67 | 23.90 | 13.50 | 23.91 |
September | 17.67 | 23.76 | 233.67 | 23.90 | 8.50 | 23.90 |
October | 98.33 | 23.54 | 117.17 | 23.89 | 9.50 | 23.91 |
November | 271.50 | 23.25 | 14.83 | 21.38 | 13.67 | 21.17 |
December | 296.67 | 23.06 | 41.50 | 21.21 | 41.50 | 21.21 |
Annual Sum or Average | 1912.83 | 23.09 | 1510.50 | 23.56 | 226.83 | 21.62 |
Minimum of Months | 7.00 | 22.81 | 14.83 | 21.17 | 0.00 | 0.00 |
Maximum of Months | 306.17 | 23.88 | 314.67 | 23.90 | 59.83 | 23.92 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.381916E+09 | 0.115420E+09 | 73.17 | 0.365735E+09 | 16181745.88 | 0.00 | 0.32 | 14-JAN-15:00 | 0.00 | 01-JAN-00:05 | 4787.07 | 24-JAN-15:30 | 4742.37 | 24-JAN-15:20 | 744.97 | 17-JAN-14:00 | 1429.18 | 24-JAN-15:20 | 0.00 | 01-JAN-00:05 |
February | 0.109315E+09 | 33025070.65 | 54.33 | 0.108805E+09 | 510132.31 | 0.00 | 0.29 | 03-FEB-15:00 | 0.00 | 01-FEB-00:10 | 4203.37 | 01-FEB-12:10 | 4203.37 | 01-FEB-12:10 | 220.74 | 01-FEB-13:40 | 1291.25 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 |
March | 0.277270E+09 | 82869986.56 | 72.33 | 0.236274E+09 | 40996209.97 | 0.00 | 0.36 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 | 5928.24 | 23-MAR-14:10 | 4544.96 | 23-MAR-14:00 | 1683.82 | 23-MAR-15:30 | 1723.49 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.112902E+10 | 0.335005E+09 | 164.10 | 0.923508E+09 | 0.205512E+09 | 0.00 | 1.00 | 27-APR-05:03 | 0.00 | 01-APR-00:10 | 17478.32 | 27-APR-05:03 | 11429.63 | 28-APR-05:03 | 7114.50 | 27-APR-05:03 | 4596.53 | 27-APR-05:03 | 0.00 | 01-APR-00:10 |
May | 0.124745E+10 | 0.370139E+09 | 199.12 | 0.104358E+10 | 0.203864E+09 | 0.00 | 1.00 | 03-MAY-05:03 | 0.00 | 01-MAY-00:10 | 17400.02 | 03-MAY-05:03 | 11666.59 | 04-MAY-05:03 | 7424.76 | 03-MAY-05:03 | 4577.57 | 03-MAY-05:03 | 0.00 | 01-MAY-00:10 |
June | 0.379906E+10 | 0.109652E+10 | 232.73 | 0.285602E+10 | 0.943042E+09 | 0.00 | 1.00 | 06-JUN-05:03 | 0.00 | 01-JUN-00:10 | 18461.83 | 30-JUN-05:01 | 12286.91 | 21-JUN-05:01 | 8594.02 | 28-JUN-05:13 | 4822.18 | 30-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.703177E+10 | 0.199908E+10 | 250.91 | 0.505067E+10 | 0.198110E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 19056.82 | 29-JUL-05:01 | 15078.35 | 06-JUL-05:04 | 9172.72 | 29-JUL-05:04 | 4947.76 | 29-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.774264E+10 | 0.219531E+10 | 271.51 | 0.544900E+10 | 0.229364E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 19317.81 | 07-AUG-05:01 | 12039.56 | 30-AUG-05:01 | 9914.59 | 07-AUG-05:04 | 5000.31 | 07-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.414302E+10 | 0.122587E+10 | 227.01 | 0.311560E+10 | 0.102741E+10 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 18788.82 | 22-SEP-05:01 | 17217.91 | 30-SEP-05:01 | 8678.88 | 23-SEP-05:03 | 4892.19 | 22-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.397491E+10 | 0.119237E+10 | 231.17 | 0.329947E+10 | 0.675436E+09 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 19662.99 | 05-OCT-05:01 | 15986.03 | 16-OCT-05:01 | 9298.99 | 05-OCT-05:08 | 5067.45 | 05-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.332241E+09 | 0.100202E+09 | 103.42 | 0.324894E+09 | 7347161.00 | 0.00 | 0.34 | 18-NOV-14:10 | 0.00 | 01-NOV-00:10 | 5174.38 | 18-NOV-14:30 | 5174.38 | 18-NOV-14:30 | 677.97 | 10-NOV-13:10 | 1568.31 | 18-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.440400E+09 | 0.133154E+09 | 92.17 | 0.437665E+09 | 2735169.43 | 0.00 | 0.35 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 | 5238.74 | 05-DEC-15:00 | 5238.74 | 05-DEC-15:00 | 463.88 | 07-DEC-14:00 | 1572.29 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.306090E+11 | 0.887895E+10 | 1971.97 | 0.232112E+11 | 0.739778E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.109315E+09 | 33025070.65 | 54.33 | 0.108805E+09 | 510132.31 | 0.00 | 0.29 | 0.00 | 4203.37 | 4203.37 | 220.74 | 1291.25 | 0.00 | |||||||
Maximum of Months | 0.774264E+10 | 0.219531E+10 | 271.51 | 0.544900E+10 | 0.229364E+10 | 0.00 | 1.00 | 0.00 | 19662.99 | 17217.91 | 9914.59 | 5067.45 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 137.54 | 40.07 | 0.33 | 102.70 | 34.85 | 0.00 | 0.00 | 23-MAR-15:10 | 0.00 | 01-MAR-00:10 | 0.17 | 23-MAR-15:10 | 0.12 | 23-MAR-15:10 | 0.04 | 23-MAR-15:10 | 0.05 | 23-MAR-15:10 | 0.00 | 01-MAR-00:10 |
April | 0.388182E+09 | 0.110339E+09 | 39.13 | 0.327846E+09 | 60336330.63 | 0.00 | 1.00 | 30-APR-11:01 | 0.00 | 01-APR-00:10 | 51738.01 | 30-APR-12:41 | 44949.25 | 30-APR-11:01 | 9734.47 | 30-APR-14:29 | 13127.01 | 30-APR-11:01 | 0.00 | 01-APR-00:10 |
May | 0.345563E+09 | 98988121.87 | 44.50 | 0.288099E+09 | 57463932.80 | 0.00 | 0.27 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 | 12075.15 | 04-MAY-12:00 | 10423.39 | 03-MAY-13:00 | 2060.48 | 04-MAY-12:30 | 3412.11 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 |
June | 0.319081E+10 | 0.884990E+09 | 120.56 | 0.224569E+10 | 0.945121E+09 | 0.00 | 1.00 | 18-JUN-11:21 | 0.00 | 01-JUN-00:10 | 54777.83 | 29-JUN-17:51 | 40396.79 | 25-JUN-12:20 | 21039.80 | 29-JUN-17:51 | 13504.42 | 29-JUN-17:51 | 0.00 | 01-JUN-00:10 |
July | 0.108658E+11 | 0.295592E+10 | 212.85 | 0.737387E+10 | 0.349192E+10 | 0.00 | 1.00 | 01-JUL-17:12 | 0.00 | 01-JUL-00:10 | 56727.67 | 31-JUL-17:10 | 39517.77 | 04-JUL-09:21 | 25265.03 | 29-JUL-17:11 | 14054.90 | 23-JUL-10:57 | 0.00 | 01-JUL-00:10 |
August | 0.116057E+11 | 0.316813E+10 | 220.39 | 0.771700E+10 | 0.388869E+10 | 0.00 | 1.00 | 03-AUG-17:12 | 0.00 | 01-AUG-00:10 | 56618.05 | 13-AUG-10:10 | 39822.00 | 19-AUG-17:10 | 25001.29 | 18-AUG-17:12 | 14064.83 | 06-AUG-13:02 | 0.00 | 01-AUG-00:10 |
September | 0.324003E+10 | 0.972811E+09 | 134.86 | 0.270459E+10 | 0.535440E+09 | 0.00 | 1.00 | 03-SEP-12:41 | 0.00 | 01-SEP-00:10 | 54620.54 | 10-SEP-10:51 | 42970.49 | 30-SEP-17:11 | 19741.22 | 10-SEP-11:51 | 13474.97 | 10-SEP-10:51 | 0.00 | 01-SEP-00:10 |
October | 0.386890E+10 | 0.118434E+10 | 120.61 | 0.347231E+10 | 0.396588E+09 | 0.00 | 1.00 | 01-OCT-10:51 | 0.00 | 01-OCT-00:10 | 56890.40 | 01-OCT-11:55 | 47430.10 | 15-OCT-17:01 | 23401.92 | 01-OCT-15:40 | 14214.71 | 01-OCT-11:55 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.335050E+11 | 0.937552E+10 | 893.24 | 0.241294E+11 | 0.937556E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.116057E+11 | 0.316813E+10 | 220.39 | 0.771700E+10 | 0.388869E+10 | 0.00 | 1.00 | 0.00 | 56890.40 | 47430.10 | 25265.03 | 14214.71 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.49 | 31.05 | 30.44 | 75.44 | 105.79 | 0.00 | 0.00 | 744.00 |
February | 73.18 | 33.75 | 39.43 | 85.26 | 97.25 | 0.00 | 0.00 | 672.00 |
March | 83.83 | 37.04 | 46.79 | 100.29 | 101.47 | 0.00 | 0.00 | 744.00 |
April | 115.39 | 59.92 | 55.48 | 153.06 | 92.92 | 0.00 | 0.00 | 720.00 |
May | 113.39 | 52.19 | 61.20 | 141.69 | 88.64 | 0.00 | 0.00 | 744.00 |
June | 120.36 | 60.14 | 60.23 | 160.24 | 74.27 | 0.00 | 0.00 | 720.00 |
July | 127.43 | 68.15 | 59.28 | 179.99 | 71.31 | 0.00 | 0.00 | 744.00 |
August | 119.38 | 64.58 | 54.80 | 172.60 | 73.84 | 0.00 | 0.00 | 744.00 |
September | 102.22 | 54.60 | 47.62 | 142.24 | 80.99 | 0.00 | 0.00 | 720.00 |
October | 78.28 | 42.75 | 35.53 | 112.65 | 87.52 | 0.00 | 0.00 | 744.00 |
November | 70.64 | 36.90 | 33.73 | 86.78 | 104.63 | 0.00 | 0.00 | 720.00 |
December | 62.33 | 33.37 | 28.96 | 77.12 | 110.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 94.08 | 47.93 | 46.14 | 124.14 | 90.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 61.49 | 31.05 | 28.96 | 75.44 | 71.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 127.43 | 68.15 | 61.20 | 179.99 | 110.70 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.49 | 31.05 | 30.44 | 75.44 | 105.79 | 0.00 | 0.00 | 744.00 |
February | 73.18 | 33.75 | 39.43 | 85.26 | 97.25 | 0.00 | 0.00 | 672.00 |
March | 83.83 | 37.04 | 46.79 | 100.29 | 101.47 | 0.00 | 0.00 | 744.00 |
April | 115.39 | 59.92 | 55.48 | 153.06 | 92.92 | 0.00 | 0.00 | 720.00 |
May | 113.39 | 52.19 | 61.20 | 141.69 | 88.64 | 0.00 | 0.00 | 744.00 |
June | 120.36 | 60.14 | 60.23 | 160.24 | 74.27 | 0.00 | 0.00 | 720.00 |
July | 127.43 | 68.15 | 59.28 | 179.99 | 71.31 | 0.00 | 0.00 | 744.00 |
August | 119.38 | 64.58 | 54.80 | 172.60 | 73.84 | 0.00 | 0.00 | 744.00 |
September | 102.22 | 54.60 | 47.62 | 142.24 | 80.99 | 0.00 | 0.00 | 720.00 |
October | 78.28 | 42.75 | 35.53 | 112.65 | 87.52 | 0.00 | 0.00 | 744.00 |
November | 70.64 | 36.90 | 33.73 | 86.78 | 104.63 | 0.00 | 0.00 | 720.00 |
December | 62.33 | 33.37 | 28.96 | 77.12 | 110.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 94.08 | 47.93 | 46.14 | 124.14 | 90.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 61.49 | 31.05 | 28.96 | 75.44 | 71.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 127.43 | 68.15 | 61.20 | 179.99 | 110.70 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.95 | 0.00 | 13.95 | 7.55 | 64.42 | 0.00 | 0.00 | 744.00 |
February | 17.51 | 0.00 | 17.51 | 8.10 | 59.67 | 0.00 | 0.00 | 672.00 |
March | 21.46 | 0.00 | 21.46 | 12.56 | 61.86 | 0.00 | 0.00 | 744.00 |
April | 24.80 | 0.16 | 24.64 | 15.48 | 56.62 | 0.00 | 0.00 | 720.00 |
May | 29.97 | 1.63 | 28.34 | 17.47 | 51.57 | 0.00 | 0.00 | 744.00 |
June | 31.74 | 3.18 | 28.56 | 21.51 | 42.32 | 0.00 | 0.00 | 720.00 |
July | 30.05 | 2.58 | 27.47 | 22.48 | 41.10 | 0.00 | 0.00 | 744.00 |
August | 25.02 | 0.62 | 24.40 | 20.42 | 44.08 | 0.00 | 0.00 | 744.00 |
September | 21.07 | 0.01 | 21.07 | 16.15 | 49.77 | 0.00 | 0.00 | 720.00 |
October | 16.71 | 0.00 | 16.71 | 15.57 | 52.97 | 0.00 | 0.00 | 744.00 |
November | 15.13 | 0.00 | 15.13 | 7.28 | 64.20 | 0.00 | 0.00 | 720.00 |
December | 12.99 | 0.00 | 12.99 | 6.34 | 67.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 21.72 | 0.69 | 21.03 | 14.28 | 54.67 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 12.99 | 0.00 | 12.99 | 6.34 | 41.10 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 31.74 | 3.18 | 28.56 | 22.48 | 67.76 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.95 | 0.00 | 13.95 | 7.55 | 64.42 | 0.00 | 0.00 | 744.00 |
February | 17.51 | 0.00 | 17.51 | 8.10 | 59.67 | 0.00 | 0.00 | 672.00 |
March | 21.46 | 0.00 | 21.46 | 12.56 | 61.86 | 0.00 | 0.00 | 744.00 |
April | 24.80 | 0.16 | 24.64 | 15.48 | 56.62 | 0.00 | 0.00 | 720.00 |
May | 29.97 | 1.63 | 28.34 | 17.46 | 51.57 | 0.00 | 0.00 | 744.00 |
June | 31.73 | 3.18 | 28.56 | 21.50 | 42.32 | 0.00 | 0.00 | 720.00 |
July | 30.05 | 2.58 | 27.47 | 22.48 | 41.10 | 0.00 | 0.00 | 744.00 |
August | 25.02 | 0.62 | 24.40 | 20.42 | 44.08 | 0.00 | 0.00 | 744.00 |
September | 21.07 | 0.01 | 21.06 | 16.15 | 49.77 | 0.00 | 0.00 | 720.00 |
October | 16.71 | 0.00 | 16.71 | 15.57 | 52.97 | 0.00 | 0.00 | 744.00 |
November | 15.13 | 0.00 | 15.13 | 7.28 | 64.20 | 0.00 | 0.00 | 720.00 |
December | 12.99 | 0.00 | 12.99 | 6.34 | 67.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 21.72 | 0.69 | 21.03 | 14.28 | 54.67 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 12.99 | 0.00 | 12.99 | 6.34 | 41.10 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 31.73 | 3.18 | 28.56 | 22.48 | 67.76 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.79 | 26.28 | 13.51 | 60.19 | 43.32 | 6.83 | 0.00 | 744.00 |
February | 45.22 | 25.47 | 19.75 | 65.82 | 38.88 | 0.00 | 0.00 | 672.00 |
March | 58.41 | 33.03 | 25.38 | 90.91 | 38.24 | 11.17 | 0.00 | 744.00 |
April | 87.18 | 62.91 | 24.27 | 140.05 | 37.52 | 0.00 | 0.00 | 720.00 |
May | 86.96 | 55.33 | 31.63 | 135.05 | 37.10 | 0.00 | 0.00 | 744.00 |
June | 92.20 | 62.90 | 29.31 | 145.04 | 32.88 | 0.00 | 0.00 | 720.00 |
July | 101.04 | 75.17 | 25.87 | 159.03 | 37.23 | 0.00 | 0.00 | 744.00 |
August | 93.67 | 71.38 | 22.29 | 148.00 | 38.69 | 0.00 | 0.00 | 744.00 |
September | 72.28 | 51.13 | 21.15 | 112.28 | 40.15 | 0.00 | 0.00 | 720.00 |
October | 51.96 | 35.86 | 16.10 | 78.63 | 45.53 | 0.00 | 0.00 | 744.00 |
November | 42.38 | 27.21 | 15.17 | 61.18 | 46.52 | 0.00 | 0.00 | 720.00 |
December | 37.13 | 25.33 | 11.80 | 53.40 | 48.79 | 1.33 | 0.00 | 744.00 |
Annual Sum or Average | 67.47 | 46.11 | 21.35 | 104.33 | 40.43 | 19.33 | 0.00 | 8760.00 |
Minimum of Months | 37.13 | 25.33 | 11.80 | 53.40 | 32.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 101.04 | 75.17 | 31.63 | 159.03 | 48.79 | 11.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.79 | 26.28 | 13.51 | 60.19 | 43.32 | 6.83 | 0.00 | 744.00 |
February | 45.22 | 25.47 | 19.75 | 65.82 | 38.88 | 0.00 | 0.00 | 672.00 |
March | 58.41 | 33.03 | 25.38 | 90.91 | 38.24 | 11.17 | 0.00 | 744.00 |
April | 87.18 | 62.91 | 24.27 | 140.05 | 37.52 | 0.00 | 0.00 | 720.00 |
May | 86.96 | 55.33 | 31.63 | 135.05 | 37.10 | 0.00 | 0.00 | 744.00 |
June | 92.20 | 62.90 | 29.31 | 145.04 | 32.88 | 0.00 | 0.00 | 720.00 |
July | 101.04 | 75.17 | 25.87 | 159.03 | 37.23 | 0.00 | 0.00 | 744.00 |
August | 93.67 | 71.38 | 22.29 | 148.00 | 38.69 | 0.00 | 0.00 | 744.00 |
September | 72.28 | 51.13 | 21.15 | 112.28 | 40.15 | 0.00 | 0.00 | 720.00 |
October | 51.96 | 35.86 | 16.10 | 78.63 | 45.53 | 0.00 | 0.00 | 744.00 |
November | 42.38 | 27.21 | 15.17 | 61.18 | 46.52 | 0.00 | 0.00 | 720.00 |
December | 37.13 | 25.33 | 11.80 | 53.40 | 48.79 | 1.33 | 0.00 | 744.00 |
Annual Sum or Average | 67.47 | 46.11 | 21.35 | 104.33 | 40.43 | 19.33 | 0.00 | 8760.00 |
Minimum of Months | 37.13 | 25.33 | 11.80 | 53.40 | 32.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 101.04 | 75.17 | 31.63 | 159.03 | 48.79 | 11.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.79 | 26.28 | 13.51 | 60.19 | 43.32 | 6.83 | 0.00 | 744.00 |
February | 45.22 | 25.47 | 19.75 | 65.82 | 38.88 | 0.00 | 0.00 | 672.00 |
March | 58.41 | 33.03 | 25.38 | 90.91 | 38.24 | 11.17 | 0.00 | 744.00 |
April | 87.18 | 62.91 | 24.27 | 140.05 | 37.52 | 0.00 | 0.00 | 720.00 |
May | 86.96 | 55.33 | 31.63 | 135.05 | 37.10 | 0.00 | 0.00 | 744.00 |
June | 92.20 | 62.90 | 29.31 | 145.04 | 32.88 | 0.00 | 0.00 | 720.00 |
July | 101.04 | 75.17 | 25.87 | 159.03 | 37.23 | 0.00 | 0.00 | 744.00 |
August | 93.67 | 71.38 | 22.29 | 148.00 | 38.69 | 0.00 | 0.00 | 744.00 |
September | 72.28 | 51.13 | 21.15 | 112.28 | 40.15 | 0.00 | 0.00 | 720.00 |
October | 51.96 | 35.86 | 16.10 | 78.63 | 45.53 | 0.00 | 0.00 | 744.00 |
November | 42.38 | 27.21 | 15.17 | 61.18 | 46.52 | 0.00 | 0.00 | 720.00 |
December | 37.13 | 25.33 | 11.80 | 53.40 | 48.79 | 1.33 | 0.00 | 744.00 |
Annual Sum or Average | 67.47 | 46.11 | 21.35 | 104.33 | 40.43 | 19.33 | 0.00 | 8760.00 |
Minimum of Months | 37.13 | 25.33 | 11.80 | 53.40 | 32.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 101.04 | 75.17 | 31.63 | 159.03 | 48.79 | 11.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.79 | 26.28 | 13.51 | 60.19 | 43.32 | 6.83 | 0.00 | 744.00 |
February | 45.22 | 25.47 | 19.75 | 65.82 | 38.88 | 0.00 | 0.00 | 672.00 |
March | 58.41 | 33.03 | 25.38 | 90.91 | 38.24 | 11.17 | 0.00 | 744.00 |
April | 87.18 | 62.91 | 24.27 | 140.05 | 37.52 | 0.00 | 0.00 | 720.00 |
May | 86.96 | 55.33 | 31.63 | 135.05 | 37.10 | 0.00 | 0.00 | 744.00 |
June | 92.20 | 62.90 | 29.31 | 145.04 | 32.88 | 0.00 | 0.00 | 720.00 |
July | 101.04 | 75.17 | 25.87 | 159.03 | 37.23 | 0.00 | 0.00 | 744.00 |
August | 93.67 | 71.38 | 22.29 | 148.00 | 38.69 | 0.00 | 0.00 | 744.00 |
September | 72.28 | 51.13 | 21.15 | 112.28 | 40.15 | 0.00 | 0.00 | 720.00 |
October | 51.96 | 35.86 | 16.10 | 78.63 | 45.53 | 0.00 | 0.00 | 744.00 |
November | 42.38 | 27.21 | 15.17 | 61.18 | 46.52 | 0.00 | 0.00 | 720.00 |
December | 37.13 | 25.33 | 11.80 | 53.40 | 48.79 | 1.33 | 0.00 | 744.00 |
Annual Sum or Average | 67.47 | 46.11 | 21.35 | 104.33 | 40.43 | 19.33 | 0.00 | 8760.00 |
Minimum of Months | 37.13 | 25.33 | 11.80 | 53.40 | 32.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 101.04 | 75.17 | 31.63 | 159.03 | 48.79 | 11.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.79 | 26.28 | 13.51 | 60.19 | 43.32 | 6.83 | 0.00 | 744.00 |
February | 45.22 | 25.47 | 19.75 | 65.82 | 38.88 | 0.00 | 0.00 | 672.00 |
March | 58.41 | 33.03 | 25.38 | 90.91 | 38.24 | 11.17 | 0.00 | 744.00 |
April | 87.18 | 62.91 | 24.27 | 140.05 | 37.52 | 0.00 | 0.00 | 720.00 |
May | 86.96 | 55.33 | 31.63 | 135.05 | 37.10 | 0.00 | 0.00 | 744.00 |
June | 92.20 | 62.90 | 29.31 | 145.04 | 32.88 | 0.00 | 0.00 | 720.00 |
July | 101.04 | 75.17 | 25.87 | 159.03 | 37.23 | 0.00 | 0.00 | 744.00 |
August | 93.67 | 71.38 | 22.29 | 148.00 | 38.69 | 0.00 | 0.00 | 744.00 |
September | 72.28 | 51.13 | 21.15 | 112.28 | 40.15 | 0.00 | 0.00 | 720.00 |
October | 51.96 | 35.86 | 16.10 | 78.63 | 45.53 | 0.00 | 0.00 | 744.00 |
November | 42.38 | 27.21 | 15.17 | 61.18 | 46.52 | 0.00 | 0.00 | 720.00 |
December | 37.13 | 25.33 | 11.80 | 53.40 | 48.79 | 1.33 | 0.00 | 744.00 |
Annual Sum or Average | 67.47 | 46.11 | 21.35 | 104.33 | 40.43 | 19.33 | 0.00 | 8760.00 |
Minimum of Months | 37.13 | 25.33 | 11.80 | 53.40 | 32.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 101.04 | 75.17 | 31.63 | 159.03 | 48.79 | 11.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.79 | 26.28 | 13.51 | 60.19 | 43.32 | 6.83 | 0.00 | 744.00 |
February | 45.22 | 25.47 | 19.75 | 65.82 | 38.88 | 0.00 | 0.00 | 672.00 |
March | 58.41 | 33.03 | 25.38 | 90.91 | 38.24 | 11.17 | 0.00 | 744.00 |
April | 87.18 | 62.91 | 24.27 | 140.05 | 37.52 | 0.00 | 0.00 | 720.00 |
May | 86.96 | 55.33 | 31.63 | 135.05 | 37.10 | 0.00 | 0.00 | 744.00 |
June | 92.20 | 62.90 | 29.31 | 145.04 | 32.88 | 0.00 | 0.00 | 720.00 |
July | 101.04 | 75.17 | 25.87 | 159.03 | 37.23 | 0.00 | 0.00 | 744.00 |
August | 93.67 | 71.38 | 22.29 | 148.00 | 38.69 | 0.00 | 0.00 | 744.00 |
September | 72.28 | 51.13 | 21.15 | 112.28 | 40.15 | 0.00 | 0.00 | 720.00 |
October | 51.96 | 35.86 | 16.10 | 78.63 | 45.53 | 0.00 | 0.00 | 744.00 |
November | 42.38 | 27.21 | 15.17 | 61.18 | 46.52 | 0.00 | 0.00 | 720.00 |
December | 37.13 | 25.33 | 11.80 | 53.40 | 48.79 | 1.33 | 0.00 | 744.00 |
Annual Sum or Average | 67.47 | 46.11 | 21.35 | 104.33 | 40.43 | 19.33 | 0.00 | 8760.00 |
Minimum of Months | 37.13 | 25.33 | 11.80 | 53.40 | 32.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 101.04 | 75.17 | 31.63 | 159.03 | 48.79 | 11.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.79 | 26.28 | 13.51 | 60.19 | 43.32 | 6.83 | 0.00 | 744.00 |
February | 45.22 | 25.47 | 19.75 | 65.82 | 38.88 | 0.00 | 0.00 | 672.00 |
March | 58.41 | 33.03 | 25.38 | 90.91 | 38.24 | 11.17 | 0.00 | 744.00 |
April | 87.18 | 62.91 | 24.27 | 140.05 | 37.52 | 0.00 | 0.00 | 720.00 |
May | 86.96 | 55.33 | 31.63 | 135.05 | 37.10 | 0.00 | 0.00 | 744.00 |
June | 92.20 | 62.90 | 29.31 | 145.04 | 32.88 | 0.00 | 0.00 | 720.00 |
July | 101.04 | 75.17 | 25.87 | 159.03 | 37.23 | 0.00 | 0.00 | 744.00 |
August | 93.67 | 71.38 | 22.29 | 148.00 | 38.69 | 0.00 | 0.00 | 744.00 |
September | 72.28 | 51.13 | 21.15 | 112.28 | 40.15 | 0.00 | 0.00 | 720.00 |
October | 51.96 | 35.86 | 16.10 | 78.63 | 45.53 | 0.00 | 0.00 | 744.00 |
November | 42.38 | 27.21 | 15.17 | 61.18 | 46.52 | 0.00 | 0.00 | 720.00 |
December | 37.13 | 25.33 | 11.80 | 53.40 | 48.79 | 1.33 | 0.00 | 744.00 |
Annual Sum or Average | 67.47 | 46.11 | 21.35 | 104.33 | 40.43 | 19.33 | 0.00 | 8760.00 |
Minimum of Months | 37.13 | 25.33 | 11.80 | 53.40 | 32.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 101.04 | 75.17 | 31.63 | 159.03 | 48.79 | 11.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.79 | 26.28 | 13.51 | 60.19 | 43.32 | 6.83 | 0.00 | 744.00 |
February | 45.22 | 25.47 | 19.75 | 65.82 | 38.88 | 0.00 | 0.00 | 672.00 |
March | 58.41 | 33.03 | 25.38 | 90.91 | 38.24 | 11.17 | 0.00 | 744.00 |
April | 87.18 | 62.91 | 24.27 | 140.05 | 37.52 | 0.00 | 0.00 | 720.00 |
May | 86.96 | 55.33 | 31.63 | 135.05 | 37.10 | 0.00 | 0.00 | 744.00 |
June | 92.20 | 62.90 | 29.31 | 145.04 | 32.88 | 0.00 | 0.00 | 720.00 |
July | 101.04 | 75.17 | 25.87 | 159.03 | 37.23 | 0.00 | 0.00 | 744.00 |
August | 93.67 | 71.38 | 22.29 | 148.00 | 38.69 | 0.00 | 0.00 | 744.00 |
September | 72.28 | 51.13 | 21.15 | 112.28 | 40.15 | 0.00 | 0.00 | 720.00 |
October | 51.96 | 35.86 | 16.10 | 78.63 | 45.53 | 0.00 | 0.00 | 744.00 |
November | 42.38 | 27.21 | 15.17 | 61.18 | 46.52 | 0.00 | 0.00 | 720.00 |
December | 37.13 | 25.33 | 11.80 | 53.40 | 48.79 | 1.33 | 0.00 | 744.00 |
Annual Sum or Average | 67.47 | 46.11 | 21.35 | 104.33 | 40.43 | 19.33 | 0.00 | 8760.00 |
Minimum of Months | 37.13 | 25.33 | 11.80 | 53.40 | 32.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 101.04 | 75.17 | 31.63 | 159.03 | 48.79 | 11.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.79 | 26.28 | 13.51 | 60.19 | 43.32 | 6.83 | 0.00 | 744.00 |
February | 45.22 | 25.47 | 19.75 | 65.82 | 38.88 | 0.00 | 0.00 | 672.00 |
March | 58.41 | 33.03 | 25.38 | 90.91 | 38.24 | 11.17 | 0.00 | 744.00 |
April | 87.18 | 62.91 | 24.27 | 140.05 | 37.52 | 0.00 | 0.00 | 720.00 |
May | 86.96 | 55.33 | 31.63 | 135.05 | 37.10 | 0.00 | 0.00 | 744.00 |
June | 92.20 | 62.90 | 29.31 | 145.04 | 32.88 | 0.00 | 0.00 | 720.00 |
July | 101.04 | 75.17 | 25.87 | 159.03 | 37.23 | 0.00 | 0.00 | 744.00 |
August | 93.67 | 71.38 | 22.29 | 148.00 | 38.69 | 0.00 | 0.00 | 744.00 |
September | 72.28 | 51.13 | 21.15 | 112.28 | 40.15 | 0.00 | 0.00 | 720.00 |
October | 51.96 | 35.86 | 16.10 | 78.63 | 45.53 | 0.00 | 0.00 | 744.00 |
November | 42.38 | 27.21 | 15.17 | 61.18 | 46.52 | 0.00 | 0.00 | 720.00 |
December | 37.13 | 25.33 | 11.80 | 53.40 | 48.79 | 1.33 | 0.00 | 744.00 |
Annual Sum or Average | 67.47 | 46.11 | 21.35 | 104.33 | 40.43 | 19.33 | 0.00 | 8760.00 |
Minimum of Months | 37.13 | 25.33 | 11.80 | 53.40 | 32.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 101.04 | 75.17 | 31.63 | 159.03 | 48.79 | 11.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.79 | 26.28 | 13.51 | 60.19 | 43.32 | 6.83 | 0.00 | 744.00 |
February | 45.22 | 25.47 | 19.75 | 65.82 | 38.88 | 0.00 | 0.00 | 672.00 |
March | 58.41 | 33.03 | 25.38 | 90.91 | 38.24 | 11.17 | 0.00 | 744.00 |
April | 87.18 | 62.91 | 24.27 | 140.05 | 37.52 | 0.00 | 0.00 | 720.00 |
May | 86.96 | 55.33 | 31.63 | 135.05 | 37.10 | 0.00 | 0.00 | 744.00 |
June | 92.20 | 62.90 | 29.31 | 145.04 | 32.88 | 0.00 | 0.00 | 720.00 |
July | 101.04 | 75.17 | 25.87 | 159.03 | 37.23 | 0.00 | 0.00 | 744.00 |
August | 93.67 | 71.38 | 22.29 | 148.00 | 38.69 | 0.00 | 0.00 | 744.00 |
September | 72.28 | 51.13 | 21.15 | 112.28 | 40.15 | 0.00 | 0.00 | 720.00 |
October | 51.96 | 35.86 | 16.10 | 78.63 | 45.53 | 0.00 | 0.00 | 744.00 |
November | 42.38 | 27.21 | 15.17 | 61.18 | 46.52 | 0.00 | 0.00 | 720.00 |
December | 37.13 | 25.33 | 11.80 | 53.40 | 48.79 | 1.33 | 0.00 | 744.00 |
Annual Sum or Average | 67.47 | 46.11 | 21.35 | 104.33 | 40.43 | 19.33 | 0.00 | 8760.00 |
Minimum of Months | 37.13 | 25.33 | 11.80 | 53.40 | 32.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 101.04 | 75.17 | 31.63 | 159.03 | 48.79 | 11.17 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.164704E+09 | 83161027.17 | 81543204.66 | 0.202064E+09 | 0.283349E+09 |
February | 0.177026E+09 | 81641732.75 | 95384754.49 | 0.206267E+09 | 0.235277E+09 |
March | 0.224538E+09 | 99211238.17 | 0.125327E+09 | 0.268607E+09 | 0.271774E+09 |
April | 0.299101E+09 | 0.155309E+09 | 0.143792E+09 | 0.396735E+09 | 0.240845E+09 |
May | 0.303701E+09 | 0.139795E+09 | 0.163907E+09 | 0.379495E+09 | 0.237415E+09 |
June | 0.311985E+09 | 0.155880E+09 | 0.156106E+09 | 0.415331E+09 | 0.192501E+09 |
July | 0.341316E+09 | 0.182529E+09 | 0.158787E+09 | 0.482088E+09 | 0.191006E+09 |
August | 0.319737E+09 | 0.172965E+09 | 0.146773E+09 | 0.462283E+09 | 0.197765E+09 |
September | 0.264966E+09 | 0.141531E+09 | 0.123435E+09 | 0.368698E+09 | 0.209934E+09 |
October | 0.209668E+09 | 0.114507E+09 | 95160416.82 | 0.301726E+09 | 0.234422E+09 |
November | 0.183087E+09 | 95651696.21 | 87435329.09 | 0.224923E+09 | 0.271207E+09 |
December | 0.166939E+09 | 89369873.17 | 77569015.99 | 0.206553E+09 | 0.296497E+09 |
Annual Sum or Average | 0.296677E+10 | 0.151155E+10 | 0.145522E+10 | 0.391477E+10 | 0.286199E+10 |
Minimum of Months | 0.164704E+09 | 81641732.75 | 77569015.99 | 0.202064E+09 | 0.191006E+09 |
Maximum of Months | 0.341316E+09 | 0.182529E+09 | 0.163907E+09 | 0.482088E+09 | 0.296497E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.164704E+09 | 83161027.17 | 81543204.66 | 0.202064E+09 | 0.283349E+09 |
February | 0.177026E+09 | 81641732.75 | 95384754.49 | 0.206267E+09 | 0.235277E+09 |
March | 0.224538E+09 | 99211238.17 | 0.125327E+09 | 0.268607E+09 | 0.271774E+09 |
April | 0.299101E+09 | 0.155309E+09 | 0.143792E+09 | 0.396735E+09 | 0.240845E+09 |
May | 0.303701E+09 | 0.139795E+09 | 0.163907E+09 | 0.379495E+09 | 0.237415E+09 |
June | 0.311985E+09 | 0.155880E+09 | 0.156106E+09 | 0.415331E+09 | 0.192501E+09 |
July | 0.341316E+09 | 0.182529E+09 | 0.158787E+09 | 0.482088E+09 | 0.191006E+09 |
August | 0.319737E+09 | 0.172965E+09 | 0.146773E+09 | 0.462283E+09 | 0.197765E+09 |
September | 0.264966E+09 | 0.141531E+09 | 0.123435E+09 | 0.368698E+09 | 0.209934E+09 |
October | 0.209668E+09 | 0.114507E+09 | 95160416.82 | 0.301726E+09 | 0.234422E+09 |
November | 0.183087E+09 | 95651696.21 | 87435329.09 | 0.224923E+09 | 0.271207E+09 |
December | 0.166939E+09 | 89369873.17 | 77569015.99 | 0.206553E+09 | 0.296497E+09 |
Annual Sum or Average | 0.296677E+10 | 0.151155E+10 | 0.145522E+10 | 0.391477E+10 | 0.286199E+10 |
Minimum of Months | 0.164704E+09 | 81641732.75 | 77569015.99 | 0.202064E+09 | 0.191006E+09 |
Maximum of Months | 0.341316E+09 | 0.182529E+09 | 0.163907E+09 | 0.482088E+09 | 0.296497E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37362038.68 | 0.00 | 37362038.68 | 20225389.83 | 0.172553E+09 |
February | 42360664.79 | 0.00 | 42360664.79 | 19595208.91 | 0.144349E+09 |
March | 57478292.74 | 2044.22 | 57476248.52 | 33642235.86 | 0.165678E+09 |
April | 64282328.51 | 415081.34 | 63867247.17 | 40112957.21 | 0.146748E+09 |
May | 80274667.20 | 4373903.32 | 75900763.88 | 46778389.52 | 0.138123E+09 |
June | 82257438.06 | 8232399.16 | 74025038.89 | 55742454.66 | 0.109685E+09 |
July | 80490241.17 | 6923384.08 | 73566857.09 | 60203854.90 | 0.110078E+09 |
August | 67021876.97 | 1664277.73 | 65357599.24 | 54703043.39 | 0.118054E+09 |
September | 54622769.71 | 21529.06 | 54601240.65 | 41866298.52 | 0.128992E+09 |
October | 44759735.36 | 0.00 | 44759735.36 | 41715197.87 | 0.141885E+09 |
November | 39219397.29 | 0.00 | 39219397.29 | 18868438.41 | 0.166417E+09 |
December | 34780879.84 | 0.00 | 34780879.84 | 16992449.17 | 0.181479E+09 |
Annual Sum or Average | 0.684910E+09 | 21632618.92 | 0.663278E+09 | 0.450446E+09 | 0.172404E+10 |
Minimum of Months | 34780879.84 | 0.00 | 34780879.84 | 16992449.17 | 0.109685E+09 |
Maximum of Months | 82257438.06 | 8232399.16 | 75900763.88 | 60203854.90 | 0.181479E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37361001.61 | 0.00 | 37361001.61 | 20224661.96 | 0.172551E+09 |
February | 42359404.44 | 0.00 | 42359404.44 | 19594108.49 | 0.144348E+09 |
March | 57476589.15 | 2044.12 | 57474545.02 | 33640476.12 | 0.165678E+09 |
April | 64280718.47 | 415061.89 | 63865656.59 | 40111655.75 | 0.146747E+09 |
May | 80272338.28 | 4373698.31 | 75898639.97 | 46776173.31 | 0.138123E+09 |
June | 82255047.39 | 8232013.30 | 74023034.09 | 55739900.57 | 0.109685E+09 |
July | 80488119.64 | 6923059.58 | 73565060.07 | 60201906.54 | 0.110077E+09 |
August | 67020270.40 | 1664199.72 | 65356070.68 | 54701799.76 | 0.118054E+09 |
September | 54621373.68 | 21528.05 | 54599845.62 | 41865005.00 | 0.128991E+09 |
October | 44758538.18 | 0.00 | 44758538.18 | 41714194.41 | 0.141884E+09 |
November | 39218295.25 | 0.00 | 39218295.25 | 18867618.28 | 0.166415E+09 |
December | 34779932.83 | 0.00 | 34779932.83 | 16992010.28 | 0.181477E+09 |
Annual Sum or Average | 0.684892E+09 | 21631604.97 | 0.663260E+09 | 0.450430E+09 | 0.172403E+10 |
Minimum of Months | 34779932.83 | 0.00 | 34779932.83 | 16992010.28 | 0.109685E+09 |
Maximum of Months | 82255047.39 | 8232013.30 | 75898639.97 | 60201906.54 | 0.181477E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106565E+09 | 70382459.31 | 36182293.37 | 0.161211E+09 | 0.116016E+09 |
February | 0.109395E+09 | 61622301.54 | 47772768.95 | 0.159240E+09 | 94046834.53 |
March | 0.156444E+09 | 88477380.12 | 67966341.33 | 0.243486E+09 | 0.102433E+09 |
April | 0.225961E+09 | 0.163052E+09 | 62909289.69 | 0.363009E+09 | 97240213.64 |
May | 0.232906E+09 | 0.148200E+09 | 84705141.50 | 0.361727E+09 | 99365393.09 |
June | 0.238995E+09 | 0.163031E+09 | 75964007.54 | 0.375937E+09 | 85220908.12 |
July | 0.270618E+09 | 0.201338E+09 | 69279611.62 | 0.425954E+09 | 99726444.12 |
August | 0.250882E+09 | 0.191173E+09 | 59708936.75 | 0.396402E+09 | 0.103640E+09 |
September | 0.187356E+09 | 0.132542E+09 | 54814013.04 | 0.291021E+09 | 0.104060E+09 |
October | 0.139178E+09 | 96051541.34 | 43126106.46 | 0.210608E+09 | 0.121939E+09 |
November | 0.109855E+09 | 70537149.55 | 39317397.83 | 0.158577E+09 | 0.120584E+09 |
December | 99451657.33 | 67840676.74 | 31610980.59 | 0.143016E+09 | 0.130692E+09 |
Annual Sum or Average | 0.212761E+10 | 0.145425E+10 | 0.673357E+09 | 0.329019E+10 | 0.127496E+10 |
Minimum of Months | 99451657.33 | 61622301.54 | 31610980.59 | 0.143016E+09 | 85220908.12 |
Maximum of Months | 0.270618E+09 | 0.201338E+09 | 84705141.50 | 0.425954E+09 | 0.130692E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106565E+09 | 70382459.31 | 36182293.37 | 0.161211E+09 | 0.116016E+09 |
February | 0.109395E+09 | 61622301.54 | 47772768.95 | 0.159240E+09 | 94046834.53 |
March | 0.156444E+09 | 88477380.12 | 67966341.33 | 0.243486E+09 | 0.102433E+09 |
April | 0.225961E+09 | 0.163052E+09 | 62909289.69 | 0.363009E+09 | 97240213.64 |
May | 0.232906E+09 | 0.148200E+09 | 84705141.50 | 0.361727E+09 | 99365393.09 |
June | 0.238995E+09 | 0.163031E+09 | 75964007.54 | 0.375937E+09 | 85220908.12 |
July | 0.270618E+09 | 0.201338E+09 | 69279611.62 | 0.425954E+09 | 99726444.12 |
August | 0.250882E+09 | 0.191173E+09 | 59708936.75 | 0.396402E+09 | 0.103640E+09 |
September | 0.187356E+09 | 0.132542E+09 | 54814013.04 | 0.291021E+09 | 0.104060E+09 |
October | 0.139178E+09 | 96051541.34 | 43126106.46 | 0.210608E+09 | 0.121939E+09 |
November | 0.109855E+09 | 70537149.55 | 39317397.83 | 0.158577E+09 | 0.120584E+09 |
December | 99451657.33 | 67840676.74 | 31610980.59 | 0.143016E+09 | 0.130692E+09 |
Annual Sum or Average | 0.212761E+10 | 0.145425E+10 | 0.673357E+09 | 0.329019E+10 | 0.127496E+10 |
Minimum of Months | 99451657.33 | 61622301.54 | 31610980.59 | 0.143016E+09 | 85220908.12 |
Maximum of Months | 0.270618E+09 | 0.201338E+09 | 84705141.50 | 0.425954E+09 | 0.130692E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106565E+09 | 70382459.31 | 36182293.37 | 0.161211E+09 | 0.116016E+09 |
February | 0.109395E+09 | 61622301.54 | 47772768.95 | 0.159240E+09 | 94046834.53 |
March | 0.156444E+09 | 88477380.12 | 67966341.33 | 0.243486E+09 | 0.102433E+09 |
April | 0.225961E+09 | 0.163052E+09 | 62909289.69 | 0.363009E+09 | 97240213.64 |
May | 0.232906E+09 | 0.148200E+09 | 84705141.50 | 0.361727E+09 | 99365393.09 |
June | 0.238995E+09 | 0.163031E+09 | 75964007.54 | 0.375937E+09 | 85220908.12 |
July | 0.270618E+09 | 0.201338E+09 | 69279611.62 | 0.425954E+09 | 99726444.12 |
August | 0.250882E+09 | 0.191173E+09 | 59708936.75 | 0.396402E+09 | 0.103640E+09 |
September | 0.187356E+09 | 0.132542E+09 | 54814013.04 | 0.291021E+09 | 0.104060E+09 |
October | 0.139178E+09 | 96051541.34 | 43126106.46 | 0.210608E+09 | 0.121939E+09 |
November | 0.109855E+09 | 70537149.55 | 39317397.83 | 0.158577E+09 | 0.120584E+09 |
December | 99451657.33 | 67840676.74 | 31610980.59 | 0.143016E+09 | 0.130692E+09 |
Annual Sum or Average | 0.212761E+10 | 0.145425E+10 | 0.673357E+09 | 0.329019E+10 | 0.127496E+10 |
Minimum of Months | 99451657.33 | 61622301.54 | 31610980.59 | 0.143016E+09 | 85220908.12 |
Maximum of Months | 0.270618E+09 | 0.201338E+09 | 84705141.50 | 0.425954E+09 | 0.130692E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106565E+09 | 70382459.31 | 36182293.37 | 0.161211E+09 | 0.116016E+09 |
February | 0.109395E+09 | 61622301.54 | 47772768.95 | 0.159240E+09 | 94046834.53 |
March | 0.156444E+09 | 88477380.12 | 67966341.33 | 0.243486E+09 | 0.102433E+09 |
April | 0.225961E+09 | 0.163052E+09 | 62909289.69 | 0.363009E+09 | 97240213.64 |
May | 0.232906E+09 | 0.148200E+09 | 84705141.50 | 0.361727E+09 | 99365393.09 |
June | 0.238995E+09 | 0.163031E+09 | 75964007.54 | 0.375937E+09 | 85220908.12 |
July | 0.270618E+09 | 0.201338E+09 | 69279611.62 | 0.425954E+09 | 99726444.12 |
August | 0.250882E+09 | 0.191173E+09 | 59708936.75 | 0.396402E+09 | 0.103640E+09 |
September | 0.187356E+09 | 0.132542E+09 | 54814013.04 | 0.291021E+09 | 0.104060E+09 |
October | 0.139178E+09 | 96051541.34 | 43126106.46 | 0.210608E+09 | 0.121939E+09 |
November | 0.109855E+09 | 70537149.55 | 39317397.83 | 0.158577E+09 | 0.120584E+09 |
December | 99451657.33 | 67840676.74 | 31610980.59 | 0.143016E+09 | 0.130692E+09 |
Annual Sum or Average | 0.212761E+10 | 0.145425E+10 | 0.673357E+09 | 0.329019E+10 | 0.127496E+10 |
Minimum of Months | 99451657.33 | 61622301.54 | 31610980.59 | 0.143016E+09 | 85220908.12 |
Maximum of Months | 0.270618E+09 | 0.201338E+09 | 84705141.50 | 0.425954E+09 | 0.130692E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106565E+09 | 70382459.31 | 36182293.37 | 0.161211E+09 | 0.116016E+09 |
February | 0.109395E+09 | 61622301.54 | 47772768.95 | 0.159240E+09 | 94046834.53 |
March | 0.156444E+09 | 88477380.12 | 67966341.33 | 0.243486E+09 | 0.102433E+09 |
April | 0.225961E+09 | 0.163052E+09 | 62909289.69 | 0.363009E+09 | 97240213.64 |
May | 0.232906E+09 | 0.148200E+09 | 84705141.50 | 0.361727E+09 | 99365393.09 |
June | 0.238995E+09 | 0.163031E+09 | 75964007.54 | 0.375937E+09 | 85220908.12 |
July | 0.270618E+09 | 0.201338E+09 | 69279611.62 | 0.425954E+09 | 99726444.12 |
August | 0.250882E+09 | 0.191173E+09 | 59708936.75 | 0.396402E+09 | 0.103640E+09 |
September | 0.187356E+09 | 0.132542E+09 | 54814013.04 | 0.291021E+09 | 0.104060E+09 |
October | 0.139178E+09 | 96051541.34 | 43126106.46 | 0.210608E+09 | 0.121939E+09 |
November | 0.109855E+09 | 70537149.55 | 39317397.83 | 0.158577E+09 | 0.120584E+09 |
December | 99451657.33 | 67840676.74 | 31610980.59 | 0.143016E+09 | 0.130692E+09 |
Annual Sum or Average | 0.212761E+10 | 0.145425E+10 | 0.673357E+09 | 0.329019E+10 | 0.127496E+10 |
Minimum of Months | 99451657.33 | 61622301.54 | 31610980.59 | 0.143016E+09 | 85220908.12 |
Maximum of Months | 0.270618E+09 | 0.201338E+09 | 84705141.50 | 0.425954E+09 | 0.130692E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106565E+09 | 70382459.31 | 36182293.37 | 0.161211E+09 | 0.116016E+09 |
February | 0.109395E+09 | 61622301.54 | 47772768.95 | 0.159240E+09 | 94046834.53 |
March | 0.156444E+09 | 88477380.12 | 67966341.33 | 0.243486E+09 | 0.102433E+09 |
April | 0.225961E+09 | 0.163052E+09 | 62909289.69 | 0.363009E+09 | 97240213.64 |
May | 0.232906E+09 | 0.148200E+09 | 84705141.50 | 0.361727E+09 | 99365393.09 |
June | 0.238995E+09 | 0.163031E+09 | 75964007.54 | 0.375937E+09 | 85220908.12 |
July | 0.270618E+09 | 0.201338E+09 | 69279611.62 | 0.425954E+09 | 99726444.12 |
August | 0.250882E+09 | 0.191173E+09 | 59708936.75 | 0.396402E+09 | 0.103640E+09 |
September | 0.187356E+09 | 0.132542E+09 | 54814013.04 | 0.291021E+09 | 0.104060E+09 |
October | 0.139178E+09 | 96051541.34 | 43126106.46 | 0.210608E+09 | 0.121939E+09 |
November | 0.109855E+09 | 70537149.55 | 39317397.83 | 0.158577E+09 | 0.120584E+09 |
December | 99451657.33 | 67840676.74 | 31610980.59 | 0.143016E+09 | 0.130692E+09 |
Annual Sum or Average | 0.212761E+10 | 0.145425E+10 | 0.673357E+09 | 0.329019E+10 | 0.127496E+10 |
Minimum of Months | 99451657.33 | 61622301.54 | 31610980.59 | 0.143016E+09 | 85220908.12 |
Maximum of Months | 0.270618E+09 | 0.201338E+09 | 84705141.50 | 0.425954E+09 | 0.130692E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106565E+09 | 70382459.31 | 36182293.37 | 0.161211E+09 | 0.116016E+09 |
February | 0.109395E+09 | 61622301.54 | 47772768.95 | 0.159240E+09 | 94046834.53 |
March | 0.156444E+09 | 88477380.12 | 67966341.33 | 0.243486E+09 | 0.102433E+09 |
April | 0.225961E+09 | 0.163052E+09 | 62909289.69 | 0.363009E+09 | 97240213.64 |
May | 0.232906E+09 | 0.148200E+09 | 84705141.50 | 0.361727E+09 | 99365393.09 |
June | 0.238995E+09 | 0.163031E+09 | 75964007.54 | 0.375937E+09 | 85220908.12 |
July | 0.270618E+09 | 0.201338E+09 | 69279611.62 | 0.425954E+09 | 99726444.12 |
August | 0.250882E+09 | 0.191173E+09 | 59708936.75 | 0.396402E+09 | 0.103640E+09 |
September | 0.187356E+09 | 0.132542E+09 | 54814013.04 | 0.291021E+09 | 0.104060E+09 |
October | 0.139178E+09 | 96051541.34 | 43126106.46 | 0.210608E+09 | 0.121939E+09 |
November | 0.109855E+09 | 70537149.55 | 39317397.83 | 0.158577E+09 | 0.120584E+09 |
December | 99451657.33 | 67840676.74 | 31610980.59 | 0.143016E+09 | 0.130692E+09 |
Annual Sum or Average | 0.212761E+10 | 0.145425E+10 | 0.673357E+09 | 0.329019E+10 | 0.127496E+10 |
Minimum of Months | 99451657.33 | 61622301.54 | 31610980.59 | 0.143016E+09 | 85220908.12 |
Maximum of Months | 0.270618E+09 | 0.201338E+09 | 84705141.50 | 0.425954E+09 | 0.130692E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106565E+09 | 70382459.31 | 36182293.37 | 0.161211E+09 | 0.116016E+09 |
February | 0.109395E+09 | 61622301.54 | 47772768.95 | 0.159240E+09 | 94046834.53 |
March | 0.156444E+09 | 88477380.12 | 67966341.33 | 0.243486E+09 | 0.102433E+09 |
April | 0.225961E+09 | 0.163052E+09 | 62909289.69 | 0.363009E+09 | 97240213.64 |
May | 0.232906E+09 | 0.148200E+09 | 84705141.50 | 0.361727E+09 | 99365393.09 |
June | 0.238995E+09 | 0.163031E+09 | 75964007.54 | 0.375937E+09 | 85220908.12 |
July | 0.270618E+09 | 0.201338E+09 | 69279611.62 | 0.425954E+09 | 99726444.12 |
August | 0.250882E+09 | 0.191173E+09 | 59708936.75 | 0.396402E+09 | 0.103640E+09 |
September | 0.187356E+09 | 0.132542E+09 | 54814013.04 | 0.291021E+09 | 0.104060E+09 |
October | 0.139178E+09 | 96051541.34 | 43126106.46 | 0.210608E+09 | 0.121939E+09 |
November | 0.109855E+09 | 70537149.55 | 39317397.83 | 0.158577E+09 | 0.120584E+09 |
December | 99451657.33 | 67840676.74 | 31610980.59 | 0.143016E+09 | 0.130692E+09 |
Annual Sum or Average | 0.212761E+10 | 0.145425E+10 | 0.673357E+09 | 0.329019E+10 | 0.127496E+10 |
Minimum of Months | 99451657.33 | 61622301.54 | 31610980.59 | 0.143016E+09 | 85220908.12 |
Maximum of Months | 0.270618E+09 | 0.201338E+09 | 84705141.50 | 0.425954E+09 | 0.130692E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106565E+09 | 70382459.31 | 36182293.37 | 0.161211E+09 | 0.116016E+09 |
February | 0.109395E+09 | 61622301.54 | 47772768.95 | 0.159240E+09 | 94046834.53 |
March | 0.156444E+09 | 88477380.12 | 67966341.33 | 0.243486E+09 | 0.102433E+09 |
April | 0.225961E+09 | 0.163052E+09 | 62909289.69 | 0.363009E+09 | 97240213.64 |
May | 0.232906E+09 | 0.148200E+09 | 84705141.50 | 0.361727E+09 | 99365393.09 |
June | 0.238995E+09 | 0.163031E+09 | 75964007.54 | 0.375937E+09 | 85220908.12 |
July | 0.270618E+09 | 0.201338E+09 | 69279611.62 | 0.425954E+09 | 99726444.12 |
August | 0.250882E+09 | 0.191173E+09 | 59708936.75 | 0.396402E+09 | 0.103640E+09 |
September | 0.187356E+09 | 0.132542E+09 | 54814013.04 | 0.291021E+09 | 0.104060E+09 |
October | 0.139178E+09 | 96051541.34 | 43126106.46 | 0.210608E+09 | 0.121939E+09 |
November | 0.109855E+09 | 70537149.55 | 39317397.83 | 0.158577E+09 | 0.120584E+09 |
December | 99451657.33 | 67840676.74 | 31610980.59 | 0.143016E+09 | 0.130692E+09 |
Annual Sum or Average | 0.212761E+10 | 0.145425E+10 | 0.673357E+09 | 0.329019E+10 | 0.127496E+10 |
Minimum of Months | 99451657.33 | 61622301.54 | 31610980.59 | 0.143016E+09 | 85220908.12 |
Maximum of Months | 0.270618E+09 | 0.201338E+09 | 84705141.50 | 0.425954E+09 | 0.130692E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106565E+09 | 70382459.31 | 36182293.37 | 0.161211E+09 | 0.116016E+09 |
February | 0.109395E+09 | 61622301.54 | 47772768.95 | 0.159240E+09 | 94046834.53 |
March | 0.156444E+09 | 88477380.12 | 67966341.33 | 0.243486E+09 | 0.102433E+09 |
April | 0.225961E+09 | 0.163052E+09 | 62909289.69 | 0.363009E+09 | 97240213.64 |
May | 0.232906E+09 | 0.148200E+09 | 84705141.50 | 0.361727E+09 | 99365393.09 |
June | 0.238995E+09 | 0.163031E+09 | 75964007.54 | 0.375937E+09 | 85220908.12 |
July | 0.270618E+09 | 0.201338E+09 | 69279611.62 | 0.425954E+09 | 99726444.12 |
August | 0.250882E+09 | 0.191173E+09 | 59708936.75 | 0.396402E+09 | 0.103640E+09 |
September | 0.187356E+09 | 0.132542E+09 | 54814013.04 | 0.291021E+09 | 0.104060E+09 |
October | 0.139178E+09 | 96051541.34 | 43126106.46 | 0.210608E+09 | 0.121939E+09 |
November | 0.109855E+09 | 70537149.55 | 39317397.83 | 0.158577E+09 | 0.120584E+09 |
December | 99451657.33 | 67840676.74 | 31610980.59 | 0.143016E+09 | 0.130692E+09 |
Annual Sum or Average | 0.212761E+10 | 0.145425E+10 | 0.673357E+09 | 0.329019E+10 | 0.127496E+10 |
Minimum of Months | 99451657.33 | 61622301.54 | 31610980.59 | 0.143016E+09 | 85220908.12 |
Maximum of Months | 0.270618E+09 | 0.201338E+09 | 84705141.50 | 0.425954E+09 | 0.130692E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 161.11 | 335.55 | 150.89 | 62.10 | 88.79 | 0.00 | 0.00 |
February | 181.41 | 308.53 | 181.37 | 67.49 | 113.88 | 0.00 | 0.00 |
March | 220.71 | 321.67 | 210.58 | 74.08 | 136.50 | 0.00 | 0.00 |
April | 332.45 | 294.45 | 280.39 | 120.16 | 160.23 | 0.00 | 0.00 |
May | 316.10 | 278.21 | 286.72 | 107.65 | 179.07 | 0.00 | 0.00 |
June | 361.65 | 231.34 | 304.20 | 126.63 | 177.57 | 0.00 | 0.00 |
July | 402.78 | 222.66 | 314.97 | 141.47 | 173.50 | 0.00 | 0.00 |
August | 383.35 | 233.14 | 288.80 | 130.40 | 158.40 | 0.00 | 0.00 |
September | 312.04 | 256.76 | 246.60 | 109.22 | 137.37 | 0.00 | 0.00 |
October | 252.75 | 277.30 | 189.98 | 85.50 | 104.48 | 0.00 | 0.00 |
November | 182.05 | 331.61 | 171.53 | 73.81 | 97.73 | 0.00 | 0.00 |
December | 161.49 | 351.48 | 150.63 | 66.73 | 83.89 | 0.00 | 0.00 |
Annual Sum or Average | 272.80 | 286.80 | 231.59 | 97.23 | 134.35 | 0.00 | 0.00 |
Minimum of Months | 161.11 | 222.66 | 150.63 | 62.10 | 83.89 | 0.00 | 0.00 |
Maximum of Months | 402.78 | 351.48 | 314.97 | 141.47 | 179.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 601.89 | 433.15 | 397.87 | 262.78 | 135.09 | 0.00 | 0.00 |
February | 658.23 | 388.75 | 452.20 | 254.72 | 197.47 | 0.00 | 0.00 |
March | 909.07 | 382.44 | 584.09 | 330.34 | 253.76 | 0.00 | 0.00 |
April | 1400.50 | 375.15 | 871.77 | 629.06 | 242.71 | 0.00 | 0.00 |
May | 1350.53 | 370.99 | 869.57 | 553.32 | 316.25 | 0.00 | 0.00 |
June | 1450.37 | 328.78 | 922.05 | 628.98 | 293.07 | 0.00 | 0.00 |
July | 1590.33 | 372.34 | 1010.37 | 751.71 | 258.66 | 0.00 | 0.00 |
August | 1479.99 | 386.95 | 936.69 | 713.76 | 222.93 | 0.00 | 0.00 |
September | 1122.77 | 401.46 | 722.82 | 511.35 | 211.47 | 0.00 | 0.00 |
October | 786.32 | 455.26 | 519.63 | 358.62 | 161.01 | 0.00 | 0.00 |
November | 611.79 | 465.21 | 423.82 | 272.13 | 151.69 | 0.00 | 0.00 |
December | 533.96 | 487.95 | 371.31 | 253.29 | 118.02 | 0.00 | 0.00 |
Annual Sum or Average | 1043.31 | 404.29 | 674.66 | 461.14 | 213.52 | 0.00 | 0.00 |
Minimum of Months | 533.96 | 328.78 | 371.31 | 253.29 | 118.02 | 0.00 | 0.00 |
Maximum of Months | 1590.33 | 487.95 | 1010.37 | 751.71 | 316.25 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.431517E+09 | 0.898741E+09 | 0.404132E+09 | 0.166322E+09 | 0.237809E+09 | 0.00 | 0.00 |
February | 0.438862E+09 | 0.746390E+09 | 0.438773E+09 | 0.163283E+09 | 0.275490E+09 | 0.00 | 0.00 |
March | 0.591158E+09 | 0.861567E+09 | 0.564031E+09 | 0.198427E+09 | 0.365604E+09 | 0.00 | 0.00 |
April | 0.861714E+09 | 0.763203E+09 | 0.726765E+09 | 0.311449E+09 | 0.415316E+09 | 0.00 | 0.00 |
May | 0.846630E+09 | 0.745161E+09 | 0.767950E+09 | 0.288337E+09 | 0.479612E+09 | 0.00 | 0.00 |
June | 0.937403E+09 | 0.599630E+09 | 0.788483E+09 | 0.328223E+09 | 0.460259E+09 | 0.00 | 0.00 |
July | 0.107880E+10 | 0.596380E+09 | 0.843611E+09 | 0.378905E+09 | 0.464706E+09 | 0.00 | 0.00 |
August | 0.102676E+10 | 0.624429E+09 | 0.773517E+09 | 0.349258E+09 | 0.424259E+09 | 0.00 | 0.00 |
September | 0.808810E+09 | 0.665533E+09 | 0.639175E+09 | 0.283104E+09 | 0.356071E+09 | 0.00 | 0.00 |
October | 0.676978E+09 | 0.742710E+09 | 0.508854E+09 | 0.229015E+09 | 0.279839E+09 | 0.00 | 0.00 |
November | 0.471869E+09 | 0.859533E+09 | 0.444612E+09 | 0.191303E+09 | 0.253308E+09 | 0.00 | 0.00 |
December | 0.432540E+09 | 0.941401E+09 | 0.403439E+09 | 0.178740E+09 | 0.224699E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.860304E+10 | 0.904468E+10 | 0.730334E+10 | 0.306637E+10 | 0.423697E+10 | 0.00 | 0.00 |
Minimum of Months | 0.431517E+09 | 0.596380E+09 | 0.403439E+09 | 0.163283E+09 | 0.224699E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107880E+10 | 0.941401E+09 | 0.843611E+09 | 0.378905E+09 | 0.479612E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.161210E+10 | 0.116016E+10 | 0.106565E+10 | 0.703825E+09 | 0.361823E+09 | 0.00 | 0.00 |
February | 0.159240E+10 | 0.940465E+09 | 0.109395E+10 | 0.616223E+09 | 0.477728E+09 | 0.00 | 0.00 |
March | 0.243485E+10 | 0.102433E+10 | 0.156444E+10 | 0.884774E+09 | 0.679663E+09 | 0.00 | 0.00 |
April | 0.363009E+10 | 0.972401E+09 | 0.225961E+10 | 0.163052E+10 | 0.629093E+09 | 0.00 | 0.00 |
May | 0.361727E+10 | 0.993654E+09 | 0.232906E+10 | 0.148200E+10 | 0.847051E+09 | 0.00 | 0.00 |
June | 0.375937E+10 | 0.852203E+09 | 0.238995E+10 | 0.163031E+10 | 0.759640E+09 | 0.00 | 0.00 |
July | 0.425954E+10 | 0.997263E+09 | 0.270618E+10 | 0.201338E+10 | 0.692796E+09 | 0.00 | 0.00 |
August | 0.396401E+10 | 0.103639E+10 | 0.250882E+10 | 0.191173E+10 | 0.597089E+09 | 0.00 | 0.00 |
September | 0.291021E+10 | 0.104059E+10 | 0.187356E+10 | 0.132542E+10 | 0.548140E+09 | 0.00 | 0.00 |
October | 0.210608E+10 | 0.121938E+10 | 0.139178E+10 | 0.960515E+09 | 0.431261E+09 | 0.00 | 0.00 |
November | 0.158575E+10 | 0.120584E+10 | 0.109855E+10 | 0.705371E+09 | 0.393174E+09 | 0.00 | 0.00 |
December | 0.143016E+10 | 0.130692E+10 | 0.994517E+09 | 0.678407E+09 | 0.316110E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.329018E+11 | 0.127496E+11 | 0.212761E+11 | 0.145425E+11 | 0.673357E+10 | 0.00 | 0.00 |
Minimum of Months | 0.143016E+10 | 0.852203E+09 | 0.994517E+09 | 0.616223E+09 | 0.316110E+09 | 0.00 | 0.00 |
Maximum of Months | 0.425954E+10 | 0.130692E+10 | 0.270618E+10 | 0.201338E+10 | 0.847051E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.60 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.19 | 7.03 | 3.12 | 2.95 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.60 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.61 | 10.61 | 2.62 | 4.75 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.64 | 10.56 | 2.92 | 6.16 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.02 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.75 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.61 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.49 | 13.65 | 2.19 | 8.98 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.71 | 9.60 | 2.71 | 7.73 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.42 | 6.22 | 2.47 | 2.40 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.80 | 3.19 | 2.50 | 0.04 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.75 | 10.02 | 2.59 | 5.48 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.80 | 3.19 | 2.19 | 0.04 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.44 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.65 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.80 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.11 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.03 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.58 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.48 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.18 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.88 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.83 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.94 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.06 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.06 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.18 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.2 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.20 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.32 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.55 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.53 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.2 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.02 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.40 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.31 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.58 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.18 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.18 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.84 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.08 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.63 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.63 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.84 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.84 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.33 | 3.77 | 8.01 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.02 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.46 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.91 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.63 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.91 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.822422E+09 | -742376443.9 | 0.00 | 0.00 | 744.00 | 0.00 | -80045621.8 | 58.99 | 0.00 | 0.00 |
February | 0.754626E+09 | -682807476.1 | 0.00 | 0.00 | 672.00 | 0.00 | -71818248.3 | 58.99 | 0.00 | 0.00 |
March | 0.868582E+09 | -789365977.1 | 0.00 | 0.00 | 744.00 | 0.00 | -79216381.8 | 58.99 | 0.00 | 0.00 |
April | 0.791167E+09 | -718019440.7 | 0.00 | 0.00 | 720.00 | 0.00 | -73147705.2 | 58.99 | 0.00 | 0.00 |
May | 0.802279E+09 | -727623928.8 | 0.00 | 0.00 | 744.00 | 0.00 | -74655336.7 | 58.99 | 0.00 | 0.00 |
June | 0.778955E+09 | -708294945.1 | 0.00 | 0.00 | 720.00 | 0.00 | -70659849.8 | 58.99 | 0.00 | 0.00 |
July | 0.745843E+09 | -674421755.3 | 0.00 | 0.00 | 744.00 | 0.00 | -71421186.1 | 58.99 | 0.00 | 0.00 |
August | 0.795278E+09 | -723276161.0 | 0.00 | 0.00 | 744.00 | 0.00 | -72001412.1 | 58.99 | 0.00 | 0.00 |
September | 0.750973E+09 | -680511177.1 | 0.00 | 0.00 | 720.00 | 0.00 | -70461800.6 | 58.99 | 0.00 | 0.00 |
October | 0.771150E+09 | -697681455.0 | 0.00 | 0.00 | 744.00 | 0.00 | -73468552.6 | 58.99 | 0.00 | 0.00 |
November | 0.762811E+09 | -687597542.0 | 0.00 | 0.00 | 720.00 | 0.00 | -75213296.4 | 58.99 | 0.00 | 0.00 |
December | 0.811303E+09 | -732057404.2 | 0.00 | 0.00 | 744.00 | 0.00 | -79245119.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.945539E+10 | -.856403E+10 | 8760.00 | -891354511.3 | 58.99 | |||||
Minimum of Months | 0.745843E+09 | -789365977.1 | 0.00 | 0.00 | 672.00 | 0.00 | -80045621.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.868582E+09 | -674421755.3 | 0.00 | 0.00 | 744.00 | 0.00 | -70461800.6 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 293.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 338.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 393.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 381.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 390.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 328.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 300.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 297.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4065.67 | ||||||||||
Minimum of Months | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.606050E+09 | 25937.38 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.294035E+09 | 25937.38 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.495935E+09 | 25937.38 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35294849.32 | 25937.38 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3227257.08 | 3057.22 | 15-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 484846.67 | 717.14 | 30-OCT-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 96248664.36 | 25937.38 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.334014E+09 | 25937.38 | 13-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186529E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.606050E+09 | 25937.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.477598E+09 | 59982.25 | 02-JAN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 52100232.12 | 42627.26 | 30-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.529698E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.477598E+09 | 59982.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.381916E+09 | 0.365735E+09 | 4787.07 | 24-JAN-15:30 | 4738.83 | 0.00 |
February | 0.00 | 0.00 | 0.109315E+09 | 0.108805E+09 | 4203.37 | 01-FEB-12:10 | 4203.37 | 0.00 |
March | 0.00 | 0.00 | 0.277270E+09 | 0.236274E+09 | 5928.24 | 23-MAR-14:10 | 4494.89 | 0.00 |
April | 0.00 | 0.00 | 0.112902E+10 | 0.923508E+09 | 17478.32 | 27-APR-05:03 | 10363.82 | 0.00 |
May | 0.00 | 0.00 | 0.124745E+10 | 0.104358E+10 | 17400.02 | 03-MAY-05:03 | 9975.26 | 0.00 |
June | 0.00 | 0.00 | 0.379906E+10 | 0.285602E+10 | 18461.83 | 30-JUN-05:01 | 10362.09 | 0.00 |
July | 0.00 | 0.00 | 0.703177E+10 | 0.505067E+10 | 19056.82 | 29-JUL-05:01 | 9992.34 | 0.00 |
August | 0.00 | 0.00 | 0.774264E+10 | 0.544900E+10 | 19317.81 | 07-AUG-05:01 | 9538.16 | 0.00 |
September | 0.00 | 0.00 | 0.414302E+10 | 0.311560E+10 | 18788.82 | 22-SEP-05:01 | 10171.73 | 0.00 |
October | 0.00 | 0.00 | 0.397491E+10 | 0.329947E+10 | 19662.99 | 05-OCT-05:01 | 10530.44 | 0.00 |
November | 0.00 | 0.00 | 0.332241E+09 | 0.324894E+09 | 5174.38 | 18-NOV-14:30 | 5174.38 | 0.00 |
December | 0.00 | 0.00 | 0.440400E+09 | 0.437665E+09 | 5238.74 | 05-DEC-15:00 | 5238.74 | 0.00 |
Annual Sum or Average | 0.306090E+11 | 0.232112E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.109315E+09 | 0.108805E+09 | 4203.37 | 4203.37 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.774264E+10 | 0.544900E+10 | 19662.99 | 10530.44 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 137.54 | 102.70 | 0.17 | 23-MAR-15:10 | 0.12 | 0.00 |
April | 0.00 | 0.00 | 0.388182E+09 | 0.327846E+09 | 51738.01 | 30-APR-12:41 | 42456.49 | 0.00 |
May | 0.00 | 0.00 | 0.345563E+09 | 0.288099E+09 | 12075.15 | 04-MAY-12:00 | 10128.76 | 0.00 |
June | 0.00 | 0.00 | 0.319081E+10 | 0.224569E+10 | 54777.83 | 29-JUN-17:51 | 33738.04 | 0.00 |
July | 0.00 | 0.00 | 0.108658E+11 | 0.737387E+10 | 56727.67 | 31-JUL-17:10 | 34166.92 | 0.00 |
August | 0.00 | 0.00 | 0.116057E+11 | 0.771700E+10 | 56618.05 | 13-AUG-10:10 | 34591.60 | 0.00 |
September | 0.00 | 0.00 | 0.324003E+10 | 0.270459E+10 | 54620.54 | 10-SEP-10:51 | 35844.37 | 0.00 |
October | 0.00 | 0.00 | 0.386890E+10 | 0.347231E+10 | 56890.40 | 01-OCT-11:55 | 35331.18 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.335050E+11 | 0.241294E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.116057E+11 | 0.771700E+10 | 56890.40 | 42456.49 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.118605E+10 | 0.36 | 1186.96 | 03-JAN-08:20 | 0.95 |
February | 0.108638E+10 | 0.37 | 1186.96 | 01-FEB-09:10 | 0.95 |
March | 0.127717E+10 | 0.39 | 1186.96 | 01-MAR-07:20 | 0.95 |
April | 0.117632E+10 | 0.36 | 1186.96 | 01-APR-06:40 | 0.95 |
May | 0.122349E+10 | 0.36 | 1186.96 | 20-MAY-16:00 | 0.95 |
June | 0.123686E+10 | 0.38 | 1186.96 | 01-JUN-07:20 | 0.94 |
July | 0.121148E+10 | 0.36 | 1186.96 | 01-JUL-07:10 | 0.94 |
August | 0.130449E+10 | 0.39 | 1186.96 | 01-AUG-06:50 | 0.94 |
September | 0.119066E+10 | 0.37 | 1186.96 | 14-SEP-09:00 | 0.94 |
October | 0.118715E+10 | 0.35 | 1186.96 | 02-OCT-14:00 | 0.94 |
November | 0.112950E+10 | 0.35 | 1186.96 | 01-NOV-10:20 | 0.95 |
December | 0.118126E+10 | 0.36 | 1186.96 | 20-DEC-11:50 | 0.96 |
Annual Sum or Average | 0.143908E+11 | 0.37 | |||
Minimum of Months | 0.108638E+10 | 0.35 | 1186.96 | 0.94 | |
Maximum of Months | 0.130449E+10 | 0.39 | 1186.96 | 0.96 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.268783E+10 | 0.36 | 2694.76 | 03-JAN-07:10 | 0.91 |
February | 0.245439E+10 | 0.34 | 2694.76 | 01-FEB-07:05 | 0.91 |
March | 0.288340E+10 | 0.37 | 2694.76 | 30-MAR-06:10 | 0.91 |
April | 0.267157E+10 | 0.35 | 2694.76 | 14-APR-12:50 | 0.91 |
May | 0.277453E+10 | 0.35 | 2694.76 | 01-MAY-12:20 | 0.91 |
June | 0.281307E+10 | 0.37 | 2694.76 | 06-JUN-09:50 | 0.91 |
July | 0.286596E+10 | 0.36 | 2694.76 | 01-JUL-10:44 | 0.90 |
August | 0.298364E+10 | 0.38 | 2694.76 | 01-AUG-14:10 | 0.91 |
September | 0.269180E+10 | 0.35 | 2694.76 | 05-SEP-14:40 | 0.90 |
October | 0.270364E+10 | 0.35 | 2694.76 | 02-OCT-09:30 | 0.90 |
November | 0.256110E+10 | 0.33 | 2694.76 | 01-NOV-06:03 | 0.91 |
December | 0.266782E+10 | 0.34 | 2694.76 | 01-DEC-07:03 | 0.91 |
Annual Sum or Average | 0.327588E+11 | 0.35 | |||
Minimum of Months | 0.245439E+10 | 0.33 | 2694.76 | 0.90 | |
Maximum of Months | 0.298364E+10 | 0.38 | 2694.76 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.54 | 1.88 |
February | 0.88 | 1.00 |
March | 1.00 | 1.94 |
April | 1.31 | 3.61 |
May | 1.97 | 2.11 |
June | 2.66 | 0.24 |
July | 3.98 | 0.25 |
August | 4.73 | 0.28 |
September | 2.08 | 0.30 |
October | 1.43 | 1.33 |
November | 0.92 | 3.00 |
December | 1.76 | 1.72 |
Annual Sum or Average | 24.26 | 1.07 |
Minimum of Months | 0.88 | 0.24 |
Maximum of Months | 4.73 | 3.61 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.08 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.99 | 0.00 |
July | 4.78 | 0.00 |
August | 2.72 | 0.00 |
September | 0.64 | 0.00 |
October | 0.47 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 9.70 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 4.78 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.08 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.08 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.08 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.130147E+10 | 0.882736E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.111941E+10 | 0.435825E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.136004E+10 | 0.729968E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.151132E+10 | 52587827.82 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.159363E+10 | 4972390.87 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.233338E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.321055E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.349979E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.241653E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.237952E+10 | 752882.99 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.122970E+10 | 0.144806E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.131442E+10 | 0.492151E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.232698E+11 | 0.274380E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.111941E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.349979E+10 | 0.882736E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.268783E+10 | 0.719729E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.245439E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.288340E+10 | 79024444.69 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.278191E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.287352E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.369806E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.582188E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.615177E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.366461E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.388798E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.256110E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.266782E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.421343E+11 | 0.798754E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.245439E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.615177E+10 | 0.719729E+09 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.118605E+10 | 0.381916E+09 | 0.606050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108638E+10 | 0.109315E+09 | 0.294035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127717E+10 | 0.277270E+09 | 0.495935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117632E+10 | 0.112902E+10 | 35294849.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122349E+10 | 0.124745E+10 | 3227257.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.123686E+10 | 0.379906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121148E+10 | 0.703177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130449E+10 | 0.774264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119066E+10 | 0.414302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118715E+10 | 0.397491E+10 | 484846.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112950E+10 | 0.332241E+09 | 96248664.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118126E+10 | 0.440400E+09 | 0.334014E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143908E+11 | 0.306090E+11 | 0.186529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.108638E+10 | 0.109315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130449E+10 | 0.774264E+10 | 0.606050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.268783E+10 | 0.00 | 0.477598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.245439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.288340E+10 | 137.54 | 52100232.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.267157E+10 | 0.388182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.277453E+10 | 0.345563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.281307E+10 | 0.319081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.286596E+10 | 0.108658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.298364E+10 | 0.116057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.269180E+10 | 0.324003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.270364E+10 | 0.386890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.256110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.266782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327588E+11 | 0.335050E+11 | 0.529698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.245439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.298364E+10 | 0.116057E+11 | 0.477598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.118605E+10 | 0.00 | 0.00 | 0.00 | 0.115420E+09 | 0.00 | 0.882736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108638E+10 | 0.00 | 0.00 | 0.00 | 33025070.65 | 0.00 | 0.435825E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127717E+10 | 0.00 | 0.00 | 0.00 | 82869986.56 | 0.00 | 0.729968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117632E+10 | 0.00 | 0.00 | 0.00 | 0.335005E+09 | 0.00 | 52587827.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122349E+10 | 0.00 | 0.00 | 0.00 | 0.370139E+09 | 0.00 | 4972390.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.123686E+10 | 0.00 | 0.00 | 0.00 | 0.109652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121148E+10 | 0.00 | 0.00 | 0.00 | 0.199908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130449E+10 | 0.00 | 0.00 | 0.00 | 0.219531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119066E+10 | 0.00 | 0.00 | 0.00 | 0.122587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118715E+10 | 0.00 | 0.00 | 0.00 | 0.119237E+10 | 0.00 | 752882.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112950E+10 | 0.00 | 0.00 | 0.00 | 0.100202E+09 | 0.00 | 0.144806E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118126E+10 | 0.00 | 0.00 | 0.00 | 0.133154E+09 | 0.00 | 0.492151E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143908E+11 | 0.00 | 0.00 | 0.00 | 0.887895E+10 | 0.00 | 0.274380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.108638E+10 | 0.00 | 0.00 | 0.00 | 33025070.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130449E+10 | 0.00 | 0.00 | 0.00 | 0.219531E+10 | 0.00 | 0.882736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.268783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.245439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.288340E+10 | 0.00 | 0.00 | 0.00 | 40.07 | 0.00 | 79024444.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.267157E+10 | 0.00 | 0.00 | 0.00 | 0.110339E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.277453E+10 | 0.00 | 0.00 | 0.00 | 98988121.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.281307E+10 | 0.00 | 0.00 | 0.00 | 0.884990E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.286596E+10 | 0.00 | 0.00 | 0.00 | 0.295592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.298364E+10 | 0.00 | 0.00 | 0.00 | 0.316813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.269180E+10 | 0.00 | 0.00 | 0.00 | 0.972811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.270364E+10 | 0.00 | 0.00 | 0.00 | 0.118434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.256110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.266782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327588E+11 | 0.00 | 0.00 | 0.00 | 0.937552E+10 | 0.00 | 0.798754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.245439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.298364E+10 | 0.00 | 0.00 | 0.00 | 0.316813E+10 | 0.00 | 0.719729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.418969E+09 | 14157517.22 | 0.00 | 1257672.20 | 0.00 | 0.100083E+09 | 0.102877E+10 | 0.00 | 0.32 |
February | 0.520873E+09 | 7231969.96 | 0.00 | 1111346.83 | 0.00 | 24404094.38 | 0.106323E+10 | 0.00 | 0.31 |
March | 0.596714E+09 | 1227818.04 | 0.00 | 1469992.54 | 0.00 | 65187342.70 | 0.125391E+10 | 0.00 | 0.33 |
April | 0.119663E+09 | 15184264.20 | 0.00 | 3978957.00 | 0.00 | 0.00 | 0.251102E+10 | 0.00 | 0.65 |
May | 60695493.29 | 13180842.96 | 0.00 | 5004990.38 | 0.00 | 0.00 | 0.303050E+10 | 0.00 | 0.73 |
June | 22803508.33 | 0.216606E+09 | 0.00 | 6569928.39 | 0.00 | 0.00 | 0.221592E+10 | 0.00 | 0.90 |
July | 14997235.67 | 0.764501E+09 | 0.00 | 8798314.24 | 0.00 | 0.00 | 0.107263E+10 | 0.00 | 0.76 |
August | 15162690.49 | 0.100054E+10 | 0.00 | 6817796.74 | 35604.91 | 0.00 | 0.991398E+09 | 0.00 | 0.81 |
September | 23313885.82 | 0.250983E+09 | 0.00 | 6077647.31 | 0.00 | 0.00 | 0.194598E+10 | 0.00 | 0.83 |
October | 37053081.32 | 0.396503E+09 | 0.00 | 5131818.57 | 0.00 | 0.00 | 0.166315E+10 | 0.00 | 0.67 |
November | 0.254940E+09 | 5834499.86 | 0.00 | 2358822.09 | 0.00 | 0.00 | 0.192555E+10 | 0.00 | 0.45 |
December | 0.426643E+09 | 7074499.50 | 0.00 | 1617765.32 | 0.00 | 28723397.82 | 0.118175E+10 | 0.00 | 0.39 |
Annual Sum or Average | 0.251183E+10 | 0.269302E+10 | 0.00 | 50195051.61 | 35604.91 | 0.218398E+09 | 0.198838E+11 | 0.00 | 0.60 |
Minimum of Months | 14997235.67 | 1227818.04 | 0.00 | 1111346.83 | 0.00 | 0.00 | 0.991398E+09 | 0.00 | 0.31 |
Maximum of Months | 0.596714E+09 | 0.100054E+10 | 0.00 | 8798314.24 | 35604.91 | 0.100083E+09 | 0.303050E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.188967E+10 | 0.00 | 0.00 | 0.00 | 31843246.39 | 0.00 | 0.00 | 0.00 | 0.15 |
February | 0.206701E+10 | 0.00 | 0.00 | 0.00 | 7793268.89 | 0.00 | 0.00 | 0.00 | 0.15 |
March | 0.261627E+10 | 0.00 | 0.00 | 107985.06 | 443893.63 | 0.00 | 0.138394E+09 | 0.00 | 0.17 |
April | 0.190199E+10 | 2256251.60 | 0.00 | 2598642.57 | 1775190.81 | 0.00 | 0.186005E+10 | 0.00 | 0.26 |
May | 0.186238E+10 | 2506897.84 | 0.00 | 3082477.10 | 0.00 | 0.00 | 0.241612E+10 | 0.00 | 0.27 |
June | 0.945873E+09 | 12911176.82 | 0.00 | 10272705.94 | 0.00 | 0.00 | 0.449042E+10 | 0.00 | 0.50 |
July | 0.156376E+09 | 0.643419E+09 | 0.00 | 20382352.35 | 0.00 | 0.00 | 0.484593E+10 | 0.00 | 0.68 |
August | 0.272721E+09 | 0.739484E+09 | 0.00 | 17558711.96 | 0.00 | 0.00 | 0.391805E+10 | 0.00 | 0.70 |
September | 0.692264E+09 | 0.184418E+09 | 0.00 | 7831118.21 | 92165.21 | 0.00 | 0.472069E+10 | 0.00 | 0.46 |
October | 0.990621E+09 | 0.449110E+09 | 0.00 | 3179768.14 | 4315240.46 | 0.00 | 0.204430E+10 | 0.00 | 0.33 |
November | 0.217416E+10 | 0.00 | 0.00 | 0.00 | 4603111.66 | 0.00 | 0.00 | 0.00 | 0.15 |
December | 0.182079E+10 | 0.00 | 0.00 | 0.00 | 25836755.56 | 0.00 | 0.00 | 0.00 | 0.15 |
Annual Sum or Average | 0.173901E+11 | 0.203410E+10 | 0.00 | 65013761.35 | 76702872.61 | 0.00 | 0.244339E+11 | 0.00 | 0.33 |
Minimum of Months | 0.156376E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
Maximum of Months | 0.261627E+10 | 0.739484E+09 | 0.00 | 20382352.35 | 31843246.39 | 0.00 | 0.484593E+10 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |