Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2020-06-03 19:11:27
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1099.79 | 227.46 | 227.46 |
Net Site Energy | 1099.79 | 227.46 | 227.46 |
Total Source Energy | 2871.27 | 593.83 | 593.83 |
Net Source Energy | 2871.27 | 593.83 | 593.83 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 293.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.23 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 806.09 | 293.70 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 293.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 2.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 38.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.23 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 123.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 13.95 | 60.74 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 166.72 | 60.74 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 123.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 13.95 | 60.74 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 166.72 | 60.74 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 806.095 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 806.095 | 100.00 |
Total On-Site and Utility Electric Sources | 806.095 | 100.00 |
Total Electricity End Uses | 806.095 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 55.33 |
Time Setpoint Not Met During Occupied Cooling | 0.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2063.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.6337 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.5069 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.5069 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-14:00 | 10-JAN-06:10 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 118135.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7030.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2986.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1777.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 57096.48 | 118135.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 118135.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 7030.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2986.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1777.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 318.37 | 0.00 | 0.00 | 0.00 |
Cooling | 8.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1507.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 390.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 121.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 83.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2552.90 | 318.37 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 65.84 | 0.00 | 0.00 | 0.00 |
Cooling | 1.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 527.99 | 65.84 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 65.84 | 0.00 | 0.00 | 0.00 |
Cooling | 1.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 527.99 | 65.84 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.899022 |
ZONE2 FINE STORAGE DIRECT AIR | 1.79 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 1.34 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 1.34 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 54870.58 |
PSZ-OFFICE HEATING COIL | 24085.62 |
PSZ-FINE STORAGE HEATING COIL | 60859.24 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 54870.58 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.899022 | 0.899022 | 0.899022 | 0.899022 | 0.899022 | 0.899022 | 1.00 | 1.00 | 0.899022 |
PSZ-FINE STORAGE | 1.79 | 1.79 | 1.79 | 1.79 | 1.79 | 1.79 | 1.00 | 1.00 | 1.79 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 0.899022 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 1.79 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.899022 | 0.899022 | 0.899022 | 0.899022 | 14882.01 | 24085.62 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 1.79 | 1.79 | 1.79 | 1.79 | 33021.51 | 60859.24 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.899020 | 0.449510 | 0.899020 | 14881.97 | 14882.01 | 7441.01 | 14882.01 | 0.798654 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 1.79 | 0.896155 | 1.79 | 31136.21 | 33021.51 | 16510.76 | 33021.51 | 0.761330 | 0.761330 | 0.761330 | 0.761330 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.899022 | 1024.98 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.79 | 1961.70 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.634 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.707 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.507 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.507 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.507 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.066 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2518.900 | 10.634 | 503.780 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2518.900 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11853.648 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11853.648 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27263.390 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27263.390 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.3378 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.3378 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.3378 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.861 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.861 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.861 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
5 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
6 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
7 | 4 | 0.81105908E-12 | -0.61566660E-16 | 0.53970606E-14 | 0.11182789E-15 |
8 | 3 | -0.39455327E-03 | 0.24003309E-06 | -0.57329053E-04 | 0.15561420E-12 |
9 | 2 | 1.7627212 | 0.51935632E-02 | 1.1580856 | -0.75642783E-04 |
10 | 1 | -7.0983380 | 0.13367505 | -17.210522 | 0.33785533 |
11 | 0 | 5.5597362 | 0.84856002E-01 | 16.276219 | |
12 | 4 | 0.81105908E-12 | -0.61566660E-16 | 0.53970606E-14 | 0.11182789E-15 |
13 | 3 | -0.39455327E-03 | 0.24003309E-06 | -0.57329053E-04 | 0.15561420E-12 |
14 | 2 | 1.7627212 | 0.51935632E-02 | 1.1580856 | -0.75642783E-04 |
15 | 1 | -7.0983380 | 0.13367505 | -17.210522 | 0.33785533 |
16 | 0 | 5.5597362 | 0.84856002E-01 | 16.276219 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.53970606E-14 | -0.61566660E-16 | 0.81105908E-12 | 0.11182789E-15 |
85 | 3 | -0.57329053E-04 | 0.24003309E-06 | -0.39455327E-03 | 0.15561420E-12 |
86 | 2 | 1.1580856 | 0.51935632E-02 | 1.7627212 | -0.75642783E-04 |
87 | 1 | -17.210522 | 0.13367505 | -7.0983380 | 0.33785533 |
88 | 0 | 16.276219 | 0.84856002E-01 | 5.5597362 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 28 | 1 | VerySmooth | 2.843 | 0.395 | 0.315 | 0.401 |
2 | SKYLIGHT_U_0.6_SHGC_0.4 | 29 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 30 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9010.24756 | 10812.29707 | 0.74918 | 0.89902 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.12600 | 8.38408E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 8561.45127 | 10273.74153 | 0.24278 | 0.29133 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -4.30000 | 2.65759E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 23044.09179 | 27652.91015 | 1.49360 | 1.79231 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 26.40000 | 8.38408E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 23800.81332 | 28560.97598 | 0.56882 | 0.68259 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40000 | 8.38408E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 45725.48207 | 54870.57848 | 1.11278 | 1.33534 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 12984.01 | 0.89902 | 0.89902 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 10269.55 | 0.29133 | 0.29133 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 31414.40 | 1.79231 | 1.79231 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 28387.22 | 0.68259 | 0.68259 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.89902 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.79231 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.33534 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.33534 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 54870.58035 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 54870.57848 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.89902 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.89902 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.89902 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.89902 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.89902 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.89902 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.79231 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.79231 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.79231 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.79231 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.79231 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.79231 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.89902 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.79231 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.89902 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.89902 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.89902 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.89902 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.89902 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.89902 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.44951 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.89902 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 14881.97318 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 14882.01000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 7441.00500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 14882.01000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 14882.01000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24085.62120 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.89902 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1024.98379 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 24085.62120 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.79231 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.79231 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.79231 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.79231 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.79231 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.79231 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.89616 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.79231 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 31136.21261 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 33021.51000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16510.75500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 33021.51000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.76133 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.76133 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.76133 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.76133 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33021.51000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 60859.23512 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.79231 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1961.69755 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 60859.23512 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 14184.4 | 9.21 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 31630.2 | 14.85 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 16 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1311968645 | 0.1688609129 | Pass | Pass | 0.4763571219 | 4.1038657560 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.3922741313 | 0.3732682821 | Pass | Pass | 0.4439085956 | 1.3172593404 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 7.8191639137E-005 | 2.2634686490E-004 | Pass | Pass | 5.7366670855E-002 | 4.9740789935E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.322 | 0.338 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.322 | 0.338 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.322 | 0.338 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.369 | 0.389 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.102 | 0.395 | 0.401 | ||||||||||||
North Total or Average | 6.51 | 2.843 | 0.395 | 0.401 | ||||||||||||
Non-North Total or Average | 26.02 | 3.167 | 0.395 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.6337 | 236.88 | 2518.90 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.62 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.5069 | 1393.41 | 11853.65 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 135.00 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.5069 | 3204.84 | 27263.39 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 310.50 |
Interior Lighting Total | 8.6111 | 4835.13 | 41635.94 | 476.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.00 | AstronomicalClock | - | 83.54 | 83.54 | 123.21 | |
Exterior Lighting Total | 7857.00 | 123.21 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 14882.01 | 11885.67 | 2996.34 | 0.80 | 3.15 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33021.51 | 25140.27 | 7881.24 | 0.76 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 14184.4 | 9.21 | ||||
PSZ-FINE STORAGE COOLING COIL | 31630.2 | 14.85 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 54870.58 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 24085.62 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 60859.24 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.34 | 124.07 | 92.91 | 1.00 | 3.87 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 0.90 | 1024.98 | 1140.11 | 1.00 | 1.39 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 1.79 | 1961.70 | 1094.51 | 1.00 | 1.30 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9010.25 | 10812.30 | 45.64 | 0.749 | 0.899 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23.90 | 23.90 | 0.00814 | 25.13 | 0.00838 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 23044.09 | 27652.91 | 19.85 | 1.494 | 1.792 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 26.70 | 26.70 | 0.00803 | 26.40 | 0.00838 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00382 | 26.40 | 0.00838 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8561.45 | 10273.74 | 43.37 | 0.243 | 0.291 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00782 | -4.30 | 0.00266 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 23800.81 | 28560.98 | 20.50 | 0.569 | 0.683 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.56 | 0.00673 | -4.30 | 0.00266 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 45725.48 | 54870.58 | 17.12 | 1.113 | 1.335 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00771 | -4.30 | 0.00266 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.90 | 0.90 | 0.29 | 0.29 | 0.8990 | 0.8990 | 0.8990 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.79 | 1.79 | 0.68 | 0.68 | 1.7923 | 1.7923 | 1.7923 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 54870.580 | 54870.580 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 54870.58 | 54870.58 | 1.335337 | 1.28 | 1.28 | 0.00463080 | 43.33 | 26.97 | 0.01600000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 10.00 | 0.00771204 | 99.9996 | 54870.58 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 14882.010 | 0.000 | 0.899020 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 14882.01 | 14426.01 | 0.899020 | 24.06 | 16.00 | 0.00817127 | 12.00 | 11.16 | 0.00800000 | 25.13 | 0.00838408 | 16.56 | 13.3852 | 23.90 | 0.00813839 | 43.6309 | 9010.25 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 24085.621 | 24085.621 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 24085.62 | 24085.62 | 0.899022 | 10.55 | 8.00 | 0.00568565 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 13.3851 | 21.10 | 0.00781659 | 49.7050 | 8561.45 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 33021.510 | 0.000 | 1.792310 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 33021.51 | 32518.29 | 1.792310 | 26.64 | 16.84 | 0.00809964 | 12.00 | 11.16 | 0.00800000 | 26.40 | 0.00838408 | 17.00 | 19.7470 | 26.70 | 0.00802964 | 36.4497 | 23044.09 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 60859.235 | 60859.235 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 60859.24 | 60859.24 | 1.792314 | 5.26 | 4.05 | 0.00461904 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 19.7470 | 15.56 | 0.00673129 | 60.7141 | 23800.81 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 54870.580 | 54870.580 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1914 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 1.335337 | 1.59088325 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 54870.58 | 54870.58 | 1.0000 | 1.59088325 | 1.335337 | 1.28 | 1.28 | 0.00463080 | 12879.5 | 43.33 | 26.97 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54870.58 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 10.00 | 0.00771204 | 10.00 | 0.00771204 | 99.9996 | 54870.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 14882.010 | 0.000 | 0.899020 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0300 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 14882.01 | 14426.01 | 1.0000 | 1.07106727 | 0.899020 | 24.06 | 16.00 | 0.00817127 | 44981.7 | 12.00 | 11.16 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14882.01 | 25.13 | 0.00838408 | 16.56 | 0.12033533 | 13.3852 | 23.90 | 0.00813839 | 23.90 | 0.00813839 | 43.6309 | 9010.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24085.621 | 24085.621 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.899022 | 1.07106956 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 24085.62 | 24085.62 | 1.0000 | 1.07106956 | 0.899022 | 10.55 | 8.00 | 0.00568565 | 24937.1 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24085.62 | -4.30 | 0.00265759 | -4.30 | 0.12033533 | 13.3851 | 21.01 | 0.00781659 | 21.10 | 0.00781659 | 49.7050 | 8561.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33021.510 | 0.000 | 1.792310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.8968 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 33021.51 | 32518.29 | 1.0000 | 2.13530797 | 1.792310 | 26.64 | 16.84 | 0.00809964 | 47427.5 | 12.00 | 11.16 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33021.51 | 26.40 | 0.00838408 | 17.00 | 0.35392745 | 19.7470 | 26.70 | 0.00802964 | 26.70 | 0.00802964 | 36.4497 | 23044.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 60859.235 | 60859.235 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.792314 | 2.13531277 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 60859.24 | 60859.24 | 1.0000 | 2.13531277 | 1.792314 | 5.26 | 4.05 | 0.00461904 | 16883.9 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 60859.24 | -4.30 | 0.00265759 | -4.30 | 0.35392745 | 19.7470 | 15.56 | 0.00673129 | 15.56 | 0.00673129 | 60.7141 | 23800.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.35 | 1.79 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2123.33 | 3335.00 | 2063.67 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2123.33 | 3335.00 | 2063.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 56.50 | 0.17 | 55.33 | 0.17 |
ZONE2 FINE STORAGE | 255.67 | 0.17 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 302.50 | 0.33 | 55.33 | 0.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.404 | 0.366 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 806.09 | 5421.86 | 15-JAN-10:50 | 57096.48 | 22-JUL-15:00 |
Electricity:Building | 615.41 | 4938.86 | 01-JAN-00:10 | 45301.66 | 02-JAN-09:10 |
Electricity:Zone:ZONE1 OFFICE | 62.57 | 1027.15 | 01-JAN-00:10 | 3852.05 | 02-JAN-08:10 |
InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.62 | 453.40 | 01-JAN-00:10 | 1939.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 417.84 | 2726.34 | 01-JAN-00:10 | 31374.00 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 310.51 | 2726.34 | 01-JAN-00:10 | 23173.88 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 26.23 | 483.00 | 19-APR-05:10 | 2433.56 | 14-FEB-12:50 |
WaterSystems:Electricity | 26.23 | 483.00 | 19-APR-05:10 | 2433.56 | 14-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 26.23 | 483.00 | 19-APR-05:10 | 2433.56 | 14-FEB-12:50 |
Fans:Electricity | 38.47 | 0.00 | 04-JAN-18:40 | 3110.75 | 07-JAN-09:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 806.09 | 5421.86 | 15-JAN-10:50 | 57096.48 | 22-JUL-15:00 |
ElectricityPurchased:Plant | 806.09 | 5421.86 | 15-JAN-10:50 | 57096.48 | 22-JUL-15:00 |
Cogeneration:ElectricityPurchased | 806.09 | 5421.86 | 15-JAN-10:50 | 57096.48 | 22-JUL-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 806.09 | 5421.86 | 15-JAN-10:50 | 57096.48 | 22-JUL-15:00 |
ElectricityNet:Plant | 806.09 | 5421.86 | 15-JAN-10:50 | 57096.48 | 22-JUL-15:00 |
Cogeneration:ElectricityNet | 806.09 | 5421.86 | 15-JAN-10:50 | 57096.48 | 22-JUL-15:00 |
Electricity:HVAC | 41.25 | 0.00 | 04-JAN-18:40 | 10077.30 | 22-JUL-15:10 |
General:Fans:Electricity | 38.47 | 0.00 | 04-JAN-18:40 | 3110.75 | 07-JAN-09:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 2.77 | 0.00 | 01-JAN-00:10 | 7090.62 | 22-JUL-15:10 |
ExteriorLights:Electricity | 123.21 | 0.00 | 01-JAN-08:20 | 7857.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.21 | 0.00 | 01-JAN-08:20 | 7857.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 293.70 | 3250.00 | 04-JAN-18:40 | 118135.61 | 10-JAN-06:10 |
Gas:HVAC | 293.70 | 3250.00 | 04-JAN-18:40 | 118135.61 | 10-JAN-06:10 |
Heating:Gas | 293.70 | 3250.00 | 04-JAN-18:40 | 118135.61 | 10-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 304.33 | 0.00 | 04-JAN-18:40 | 180922.37 | 10-JAN-06:10 |
EnergyTransfer:Building | 155.45 | 0.00 | 04-JAN-18:40 | 89708.85 | 10-JAN-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 34.23 | 0.00 | 01-JAN-00:10 | 17531.61 | 10-JAN-07:10 |
Heating:EnergyTransfer | 132.17 | 0.00 | 04-JAN-18:40 | 89708.85 | 10-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 25.90 | 0.00 | 01-JAN-00:10 | 17531.61 | 10-JAN-07:10 |
Cooling:EnergyTransfer | 23.28 | 0.00 | 01-JAN-00:10 | 19780.94 | 22-JUL-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 8.32 | 0.00 | 01-JAN-00:10 | 6596.34 | 21-JUL-17:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 80.02 | 0.00 | 01-JAN-00:40 | 34221.76 | 30-DEC-00:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 65.07 | 0.00 | 01-JAN-00:40 | 34221.76 | 30-DEC-00:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 14.96 | 0.00 | 01-JAN-00:10 | 13547.50 | 22-JUL-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 41.20 | 0.00 | 02-JAN-08:10 | 45271.97 | 30-DEC-01:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 41.20 | 0.00 | 02-JAN-08:10 | 45271.97 | 30-DEC-01:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 148.88 | 0.00 | 04-JAN-18:40 | 91213.51 | 10-JAN-06:10 |
HeatingCoils:EnergyTransfer | 139.50 | 0.00 | 04-JAN-18:40 | 91213.51 | 10-JAN-06:10 |
CoolingCoils:EnergyTransfer | 9.38 | 0.00 | 01-JAN-00:10 | 24497.59 | 22-JUL-15:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 25.903 | -8.325 | 0.000 | 0.000 | 3.994 | 30.619 | 31.946 | 7.935 | 0.000 | 0.024 | 0.000 | 0.000 | -9.675 | 0.000 | -22.641 | -59.780 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 65.066 | -14.956 | 0.000 | 0.000 | 0.000 | 135.003 | 0.000 | 0.000 | 0.000 | 0.019 | 0.000 | 0.000 | 0.000 | 0.000 | -83.547 | -101.585 |
ZONE3 BULK STORAGE | 41.199 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 310.507 | 107.336 | 16.489 | 0.000 | 0.398 | 0.000 | 0.000 | -8.797 | 0.000 | -291.860 | -175.271 |
Total Facility | 41.199 | 0.000 | 90.969 | -23.281 | 0.000 | 0.000 | 3.994 | 476.129 | 139.282 | 24.424 | 0.000 | 0.441 | 0.000 | 0.000 | -18.471 | 0.000 | -398.049 | -336.637 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 24-JUL-05:03 | 0.00 | 0.00 | 0.00 | -12719.92 | 0.00 | 0.00 | 35.88 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 12864.78 | 0.00 | -452.83 | 0.00 | -881.01 | 0.00 |
ZONE2 FINE STORAGE | 23-JUL-11:31 | 0.00 | 0.00 | 0.00 | -33152.92 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 34289.35 | 0.00 | -0.00 | 0.00 | -2321.80 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 23-JUL-11:31 | 0.00 | 0.00 | 0.00 | -33152.92 | 0.00 | 0.00 | 0.00 | 4365.11 | 573.75 | 4985.89 | 0.00 | 0.00 | 32891.81 | 0.00 | 0.00 | 0.00 | -9663.63 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 24-NOV-06:01 | 0.00 | 0.00 | 23473.31 | 0.00 | 0.00 | 0.00 | 55.70 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -348.54 | 0.00 | -376.23 | -23957.35 |
ZONE2 FINE STORAGE | 30-DEC-01:22 | 0.00 | 0.00 | 63085.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -10219.19 | -54051.44 |
ZONE3 BULK STORAGE | 30-DEC-00:55 | 45272.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -700.03 | 0.00 | -30424.93 | -18923.57 |
Total Facility | 10-JAN-06:01 | 43293.31 | 0.00 | 83507.27 | 0.00 | 0.00 | 0.00 | 58.78 | 4491.05 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1554.17 | 0.00 | -35468.50 | -96951.52 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.8990 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 0.8990 | 0.1339 | 1.0000 | 0.1203 | 0.1339 | ||
PSZ-FINE STORAGE | 1.7923 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 1.7923 | 0.1975 | 1.0000 | 0.3539 | 0.1975 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.8990 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 0.8990 | 1.0000 | 1.0000 | 0.1203 | 0.1339 | ||
PSZ-FINE STORAGE | 1.7923 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 1.7923 | 1.0000 | 1.0000 | 0.3539 | 0.1975 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.8990 | 0.8990 | 0.8990 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.7923 | 1.7923 | 1.7923 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.8990 | 0.8990 | 0.8990 | 0.8990 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 1.7923 | 1.7923 | 1.7923 | 1.7923 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.8990 | 0.8990 | 0.8990 | 0.1203 | 0.4131 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.7923 | 1.7923 | 1.7923 | 0.3539 | 0.5185 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.8990 | 0.8990 | 0.8990 | 0.8990 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 1.7923 | 1.7923 | 1.7923 | 1.7923 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 55.33 |
Number of hours cooling loads not met | 0.17 |
Number of hours not met | 55.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 293.70 | 118135.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 2.77 | 7090.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 476.13 | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.21 | 7857.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 38.47 | 3110.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.23 | 2433.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 806.09 |
Natural Gas | 0.00 | 293.70 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1099.79 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 98.47 |
Space Heating | 0.00 |
Space Cooling | 0.57 |
Fans (All) | 7.96 |
Service Water Heating | 5.42 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 166.72 |
Subtotal | 166.72 |
Natural Gas [MJ/m2] | |
Space Heating | 60.74 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 60.74 |
Subtotal | 60.74 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 43.29 |
Space Heating | 26.70 |
Space Cooling | 0.25 |
Fans (All) | 3.50 |
Service Water Heating | 2.38 |
Receptacle Equipment | 12.66 |
Miscellaneous | 11.20 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.522550E+11 |
February | 0.000 | 0.389865E+11 |
March | 0.000 | 0.267730E+11 |
April | 0.000 | 0.121068E+11 |
May | 0.000 | 0.112259E+11 |
June | 0.000 | 0.877379E+10 |
July | 0.000 | 0.879831E+10 |
August | 0.000 | 0.874560E+10 |
September | 0.000 | 0.886782E+10 |
October | 0.000 | 0.145334E+11 |
November | 0.000 | 0.310698E+11 |
December | 0.000 | 0.715600E+11 |
Annual Sum or Average | 0.293696E+12 | |
Minimum of Months | 0.000 | 0.874560E+10 |
Maximum of Months | 0.000 | 0.715600E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.522550E+11 |
February | 0.000 | 0.389865E+11 |
March | 0.000 | 0.267730E+11 |
April | 0.000 | 0.121068E+11 |
May | 0.000 | 0.112259E+11 |
June | 0.000 | 0.877379E+10 |
July | 0.000 | 0.879831E+10 |
August | 0.000 | 0.874560E+10 |
September | 0.000 | 0.886782E+10 |
October | 0.000 | 0.145334E+11 |
November | 0.000 | 0.310698E+11 |
December | 0.000 | 0.715600E+11 |
Annual Sum or Average | 0.293696E+12 | |
Minimum of Months | 0.000 | 0.874560E+10 |
Maximum of Months | 0.000 | 0.715600E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.522550E+11 |
February | 0.000 | 0.389865E+11 |
March | 0.000 | 0.267730E+11 |
April | 0.000 | 0.121068E+11 |
May | 0.000 | 0.112259E+11 |
June | 0.000 | 0.877379E+10 |
July | 0.000 | 0.879831E+10 |
August | 0.000 | 0.874560E+10 |
September | 0.000 | 0.886782E+10 |
October | 0.000 | 0.145334E+11 |
November | 0.000 | 0.310698E+11 |
December | 0.000 | 0.715600E+11 |
Annual Sum or Average | 0.293696E+12 | |
Minimum of Months | 0.000 | 0.874560E+10 |
Maximum of Months | 0.000 | 0.715600E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.522550E+11 |
February | 0.000 | 0.389865E+11 |
March | 0.000 | 0.267730E+11 |
April | 0.000 | 0.121068E+11 |
May | 0.000 | 0.112259E+11 |
June | 0.000 | 0.877379E+10 |
July | 0.000 | 0.879831E+10 |
August | 0.000 | 0.874560E+10 |
September | 0.000 | 0.886782E+10 |
October | 0.000 | 0.145334E+11 |
November | 0.000 | 0.310698E+11 |
December | 0.000 | 0.715600E+11 |
Annual Sum or Average | 0.293696E+12 | |
Minimum of Months | 0.000 | 0.874560E+10 |
Maximum of Months | 0.000 | 0.715600E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.522550E+11 |
February | 0.000 | 0.389865E+11 |
March | 0.000 | 0.267730E+11 |
April | 0.000 | 0.121068E+11 |
May | 0.000 | 0.112259E+11 |
June | 0.000 | 0.877379E+10 |
July | 0.000 | 0.879831E+10 |
August | 0.000 | 0.874560E+10 |
September | 0.000 | 0.886782E+10 |
October | 0.000 | 0.145334E+11 |
November | 0.000 | 0.310698E+11 |
December | 0.000 | 0.715600E+11 |
Annual Sum or Average | 0.293696E+12 | |
Minimum of Months | 0.000 | 0.874560E+10 |
Maximum of Months | 0.000 | 0.715600E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.522550E+11 |
February | 0.000 | 0.389865E+11 |
March | 0.000 | 0.267730E+11 |
April | 0.000 | 0.121068E+11 |
May | 0.000 | 0.112259E+11 |
June | 0.000 | 0.877379E+10 |
July | 0.000 | 0.879831E+10 |
August | 0.000 | 0.874560E+10 |
September | 0.000 | 0.886782E+10 |
October | 0.000 | 0.145334E+11 |
November | 0.000 | 0.310698E+11 |
December | 0.000 | 0.715600E+11 |
Annual Sum or Average | 0.293696E+12 | |
Minimum of Months | 0.000 | 0.874560E+10 |
Maximum of Months | 0.000 | 0.715600E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.522550E+11 |
February | 0.000 | 0.389865E+11 |
March | 0.000 | 0.267730E+11 |
April | 0.000 | 0.121068E+11 |
May | 0.000 | 0.112259E+11 |
June | 0.000 | 0.877379E+10 |
July | 0.000 | 0.879831E+10 |
August | 0.000 | 0.874560E+10 |
September | 0.000 | 0.886782E+10 |
October | 0.000 | 0.145334E+11 |
November | 0.000 | 0.310698E+11 |
December | 0.000 | 0.715600E+11 |
Annual Sum or Average | 0.293696E+12 | |
Minimum of Months | 0.000 | 0.874560E+10 |
Maximum of Months | 0.000 | 0.715600E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.522550E+11 |
February | 0.000 | 0.389865E+11 |
March | 0.000 | 0.267730E+11 |
April | 0.000 | 0.121068E+11 |
May | 0.000 | 0.112259E+11 |
June | 0.000 | 0.877379E+10 |
July | 0.000 | 0.879831E+10 |
August | 0.000 | 0.874560E+10 |
September | 0.000 | 0.886782E+10 |
October | 0.000 | 0.145334E+11 |
November | 0.000 | 0.310698E+11 |
December | 0.000 | 0.715600E+11 |
Annual Sum or Average | 0.293696E+12 | |
Minimum of Months | 0.000 | 0.874560E+10 |
Maximum of Months | 0.000 | 0.715600E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.522550E+11 |
February | 0.000 | 0.389865E+11 |
March | 0.000 | 0.267730E+11 |
April | 0.000 | 0.121068E+11 |
May | 0.000 | 0.112259E+11 |
June | 0.000 | 0.877379E+10 |
July | 0.000 | 0.879831E+10 |
August | 0.000 | 0.874560E+10 |
September | 0.000 | 0.886782E+10 |
October | 0.000 | 0.145334E+11 |
November | 0.000 | 0.310698E+11 |
December | 0.000 | 0.715600E+11 |
Annual Sum or Average | 0.293696E+12 | |
Minimum of Months | 0.000 | 0.874560E+10 |
Maximum of Months | 0.000 | 0.715600E+11 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3227926.10 | 802.37 | 19-JAN-16:20 | 7.33 | 6.98 | 0.195013E+09 | 236.59 | 10-JAN-11:09 | -1.8 | -1.8 |
February | 3757322.73 | 840.68 | 04-FEB-16:30 | 7.00 | 5.54 | 0.179415E+09 | 236.59 | 18-FEB-10:09 | 5.00 | 4.09 |
March | 11132023.40 | 480.23 | 25-MAR-16:00 | 11.00 | 9.40 | 0.210760E+09 | 248.70 | 25-MAR-13:39 | 12.67 | 9.93 |
April | 0.350121E+09 | 3290.32 | 29-APR-15:50 | 20.00 | 12.38 | 0.208264E+09 | 301.59 | 28-APR-15:09 | 20.08 | 13.46 |
May | 0.536445E+09 | 2940.54 | 25-MAY-16:00 | 18.00 | 13.89 | 0.222625E+09 | 301.60 | 25-MAY-15:30 | 17.50 | 13.69 |
June | 0.139920E+10 | 5196.00 | 13-JUN-16:00 | 26.50 | 17.68 | 0.247958E+09 | 301.60 | 13-JUN-15:39 | 26.33 | 17.73 |
July | 0.226133E+10 | 12721.47 | 24-JUL-05:03 | 13.00 | 13.00 | 0.245333E+09 | 301.60 | 22-JUL-09:09 | 24.33 | 16.68 |
August | 0.241187E+10 | 5125.26 | 19-AUG-16:00 | 20.00 | 15.65 | 0.266097E+09 | 301.60 | 19-AUG-15:00 | 20.00 | 15.65 |
September | 0.119220E+10 | 4200.93 | 13-SEP-16:00 | 23.00 | 16.21 | 0.239431E+09 | 302.85 | 19-SEP-12:09 | 18.50 | 14.60 |
October | 0.138292E+09 | 1398.60 | 07-OCT-16:00 | 18.00 | 9.64 | 0.203255E+09 | 301.58 | 06-OCT-15:00 | 17.00 | 9.19 |
November | 17132027.28 | 677.60 | 04-NOV-14:50 | 9.00 | 6.58 | 0.187342E+09 | 246.69 | 10-NOV-15:39 | 11.33 | 8.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.00 | 3.53 | 0.195005E+09 | 236.59 | 04-DEC-16:10 | 8.00 | 5.78 |
Annual Sum or Average | 0.832471E+10 | 0.260050E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.00 | 3.53 | 0.179415E+09 | 236.59 | -1.8 | -1.8 | ||
Maximum of Months | 0.241187E+10 | 12721.47 | 26.50 | 17.68 | 0.266097E+09 | 302.85 | 26.33 | 17.73 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.873185E+09 | 3430.16 | 20-JAN-09:30 | 3.00 | 2.58 | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 | 1.45 |
February | 0.124746E+10 | 3568.15 | 17-FEB-09:50 | 2.67 | 1.90 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 5.79 |
March | 0.149318E+10 | 3473.26 | 15-MAR-13:50 | 2.83 | 2.14 | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 | 3.71 |
April | 0.147501E+10 | 8798.12 | 28-APR-06:10 | 7.72 | 6.32 | 0.00 | 0.00 | 01-APR-00:10 | 4.23 | 1.83 |
May | 0.157415E+10 | 7246.66 | 04-MAY-06:10 | 7.33 | 7.17 | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 | 8.15 |
June | 0.160442E+10 | 7156.85 | 06-JUN-06:10 | 9.75 | 8.07 | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 | 7.38 |
July | 0.208798E+10 | 33155.12 | 23-JUL-11:31 | 21.00 | 15.98 | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 | 9.95 |
August | 0.126223E+10 | 5671.66 | 15-AUG-06:10 | 17.00 | 12.89 | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 | 9.82 |
September | 0.900069E+09 | 7108.62 | 23-SEP-06:10 | 12.17 | 10.03 | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 | 10.95 |
October | 0.894828E+09 | 6232.02 | 13-OCT-06:10 | 10.00 | 10.00 | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 | 5.82 |
November | 0.959439E+09 | 2994.11 | 16-NOV-09:00 | 4.00 | 3.53 | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 | 4.28 |
December | 0.583884E+09 | 3169.49 | 06-DEC-09:50 | 3.67 | 2.86 | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 |
Annual Sum or Average | 0.149558E+11 | 0.00 | ||||||||
Minimum of Months | 0.583884E+09 | 2994.11 | 2.67 | 1.90 | 0.00 | 0.00 | 1.92 | 1.45 | ||
Maximum of Months | 0.208798E+10 | 33155.12 | 21.00 | 15.98 | 0.00 | 0.00 | 12.43 | 10.95 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.92 | 1.45 | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 | 1.45 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 | 5.79 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 5.79 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 3.80 | 3.71 | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 | 3.71 |
April | 0.00 | 0.00 | 01-APR-00:05 | 4.23 | 1.83 | 0.00 | 0.00 | 01-APR-00:10 | 4.23 | 1.83 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 | 8.15 | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 | 8.15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 | 7.38 | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 | 7.38 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 | 9.95 | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 | 9.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 | 9.82 | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 | 9.82 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 | 10.95 | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 | 10.95 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 | 5.82 | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 | 5.82 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 | 4.28 | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 | 4.28 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.00 | 3.53 | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.92 | 1.45 | 0.00 | 0.00 | 1.92 | 1.45 | ||
Maximum of Months | 0.00 | 0.00 | 12.43 | 10.95 | 0.00 | 0.00 | 12.43 | 10.95 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.471512E+10 | 23067.17 | 17-JAN-06:01 | 6.07 |
February | 0.390938E+10 | 23085.07 | 22-FEB-06:01 | 6.83 |
March | 0.398581E+10 | 23269.76 | 18-MAR-05:01 | 9.00 |
April | 0.154532E+10 | 22886.64 | 10-APR-05:01 | 6.17 |
May | 0.114739E+10 | 23200.25 | 19-MAY-05:01 | 9.00 |
June | 0.219870E+09 | 22519.41 | 08-JUN-05:01 | 6.17 |
July | 63912862.83 | 22336.08 | 05-JUL-05:02 | 7.33 |
August | 29120281.94 | 3142.07 | 24-AUG-06:10 | 8.83 |
September | 0.266374E+09 | 22304.02 | 07-SEP-05:02 | 8.83 |
October | 0.178639E+10 | 23443.52 | 20-OCT-05:01 | 11.00 |
November | 0.340942E+10 | 23473.19 | 24-NOV-06:01 | 10.17 |
December | 0.482528E+10 | 22952.05 | 05-DEC-06:01 | 6.00 |
Annual Sum or Average | 0.259034E+11 | |||
Minimum of Months | 29120281.94 | 3142.07 | 6.00 | |
Maximum of Months | 0.482528E+10 | 23473.19 | 11.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131833E+11 | 62364.04 | 11-JAN-03:23 | -3.0 |
February | 0.118106E+11 | 62304.75 | 17-FEB-04:12 | -2.0 |
March | 0.716250E+10 | 61717.89 | 16-MAR-05:01 | 1.08 |
April | 0.760098E+09 | 61655.92 | 17-APR-05:01 | 3.83 |
May | 0.532011E+09 | 61658.55 | 17-MAY-05:01 | 6.00 |
June | 0.159323E+09 | 2016.46 | 22-JUN-07:00 | 12.00 |
July | 0.160925E+09 | 2124.43 | 11-JUL-06:50 | 12.83 |
August | 0.162022E+09 | 2120.78 | 19-AUG-07:00 | 12.00 |
September | 0.202952E+09 | 2049.02 | 27-SEP-06:50 | 9.67 |
October | 0.197723E+10 | 58947.32 | 16-OCT-05:04 | 7.00 |
November | 0.970814E+10 | 62337.40 | 29-NOV-04:03 | -0.8 |
December | 0.192472E+11 | 63085.11 | 30-DEC-01:22 | -2.0 |
Annual Sum or Average | 0.650663E+11 | |||
Minimum of Months | 0.159323E+09 | 2016.46 | -3.0 | |
Maximum of Months | 0.192472E+11 | 63085.11 | 12.83 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121854E+11 | 44669.95 | 10-JAN-05:52 | -4.0 |
February | 0.561748E+10 | 29656.78 | 19-FEB-22:00 | 0.00 |
March | 0.207880E+09 | 11860.31 | 04-MAR-06:00 | 3.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.195758E+10 | 26816.38 | 29-NOV-03:55 | -1.0 |
December | 0.212307E+11 | 45272.26 | 30-DEC-00:55 | -2.0 |
Annual Sum or Average | 0.411990E+11 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 0.212307E+11 | 45272.26 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.256100E+10 | 1939.55 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.233575E+10 | 1939.55 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.266872E+10 | 1939.55 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.252182E+10 | 1939.55 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.261486E+10 | 1939.55 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.257569E+10 | 1939.55 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.256100E+10 | 1939.55 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.266872E+10 | 1939.55 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.252182E+10 | 1939.55 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.256100E+10 | 1939.55 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.246796E+10 | 1939.55 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.256100E+10 | 1939.55 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.306193E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.233575E+10 | 1939.55 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.266872E+10 | 1939.55 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112294E+11 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102778E+11 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.118738E+11 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.111270E+11 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.115516E+11 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.114492E+11 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112294E+11 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.118738E+11 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.111270E+11 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112294E+11 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108048E+11 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112294E+11 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135003E+12 | ||||
Minimum of Months | 0.102778E+11 | 10075.60 | 0.00 | 0.00 | |
Maximum of Months | 0.118738E+11 | 10075.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.258277E+11 | 23173.88 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.236390E+11 | 23173.88 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.273097E+11 | 23173.88 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.255921E+11 | 23173.88 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.265687E+11 | 23173.88 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.263332E+11 | 23173.88 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.258277E+11 | 23173.88 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.273097E+11 | 23173.88 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.255921E+11 | 23173.88 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.258277E+11 | 23173.88 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.248511E+11 | 23173.88 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.258277E+11 | 23173.88 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.236390E+11 | 23173.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.273097E+11 | 23173.88 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235428E+10 |
February | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213923E+10 |
March | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224137E+10 |
April | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162174E+10 |
May | 0.565842E+09 | 0.261486E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3455.52 | 0.209555E+10 |
June | 0.565842E+09 | 0.257569E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6398046.76 | 0.163400E+10 |
July | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12519814.45 | 0.136784E+10 |
August | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4691235.50 | 0.127756E+10 |
September | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133439E+10 |
October | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173382E+10 |
November | 0.522316E+09 | 0.246796E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221520E+10 |
December | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262623E+10 |
Annual Sum or Average | 0.659424E+10 | 0.306193E+11 | 0.319458E+11 | 23612552.24 | 0.226412E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127756E+10 |
Maximum of Months | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12519814.45 | 0.262623E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423466E+10 |
February | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588209E+10 |
March | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381001E+10 |
April | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431447E+10 |
May | 0.00 | 0.115516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103356E+11 |
June | 0.00 | 0.114492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519552.96 | 0.929125E+10 |
July | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17773545.66 | 0.911866E+10 |
August | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1011057.05 | 0.761374E+10 |
September | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644685E+10 |
October | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524558E+10 |
November | 0.00 | 0.108048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698969E+10 |
December | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102644E+11 |
Annual Sum or Average | 0.135003E+12 | 19304155.67 | 0.835470E+11 | ||||||
Minimum of Months | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381001E+10 |
Maximum of Months | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17773545.66 | 0.103356E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18084508.06 | 0.875033E+10 |
February | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116494E+11 |
March | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.843349E+10 |
April | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25430405.79 | 0.123605E+11 |
May | 0.00 | 0.265687E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60158836.55 | 0.302880E+11 |
June | 0.00 | 0.263332E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87534801.76 | 0.269413E+11 |
July | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61069277.06 | 0.276882E+11 |
August | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14461975.93 | 0.241109E+11 |
September | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2788804.51 | 0.205647E+11 |
October | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158043E+11 |
November | 0.00 | 0.248511E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22622493.38 | 0.140440E+11 |
December | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9360622.61 | 0.183087E+11 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | 0.301512E+09 | 0.218944E+12 | |||||
Minimum of Months | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.843349E+10 |
Maximum of Months | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87534801.76 | 0.302880E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1939.55 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 10254.10 | 10-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1939.55 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 9474.68 | 17-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1939.55 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 8076.74 | 08-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1939.55 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 6707.33 | 20-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1939.55 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.76 | 22-MAY-15:00 | 6626.74 | 02-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1939.55 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1146.02 | 13-JUN-17:00 | 5647.79 | 08-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 1939.55 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1829.00 | 21-JUL-17:00 | 4587.65 | 05-JUL-06:10 |
August | 659.25 | 01-AUG-07:10 | 1939.55 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1132.98 | 14-AUG-17:00 | 4702.54 | 24-AUG-06:05 |
September | 659.25 | 01-SEP-07:10 | 1939.55 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 5894.65 | 20-SEP-06:05 |
October | 659.25 | 02-OCT-07:10 | 1939.55 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 7161.88 | 04-OCT-06:10 |
November | 659.25 | 01-NOV-07:10 | 1939.55 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9138.76 | 29-NOV-08:00 |
December | 659.25 | 01-DEC-08:09 | 1939.55 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 9343.48 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4587.65 | |||||
Maximum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1829.00 | 10254.10 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 14734.97 | 10-JAN-18:00 |
February | 0.00 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 9306.45 | 01-FEB-16:10 |
March | 0.00 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 14858.84 | 31-MAR-08:00 |
April | 0.00 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 9154.87 | 24-APR-15:05 |
May | 0.00 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 19211.93 | 01-MAY-15:03 |
June | 0.00 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.55 | 12-JUN-18:00 | 12709.66 | 07-JUN-15:05 |
July | 0.00 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.46 | 22-JUL-15:10 | 9853.68 | 30-JUL-19:00 |
August | 0.00 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.74 | 14-AUG-18:00 | 11691.95 | 22-AUG-16:00 |
September | 0.00 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 12188.55 | 29-SEP-15:05 |
October | 0.00 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 8833.57 | 20-OCT-15:05 |
November | 0.00 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 12996.39 | 15-NOV-07:10 |
December | 0.00 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 21636.45 | 02-DEC-18:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8833.57 | |||
Maximum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.46 | 21636.45 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23173.88 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3241.82 | 29-JAN-06:00 | 31515.13 | 10-JAN-16:00 |
February | 0.00 | 23173.88 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 18868.60 | 01-FEB-16:00 |
March | 0.00 | 23173.88 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 30138.28 | 31-MAR-08:00 |
April | 0.00 | 23173.88 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1653.84 | 30-APR-19:00 | 22116.38 | 24-APR-12:10 |
May | 0.00 | 23173.88 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3844.70 | 22-MAY-15:00 | 49442.42 | 01-MAY-13:00 |
June | 0.00 | 23173.88 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4262.34 | 13-JUN-15:50 | 32923.74 | 07-JUN-15:00 |
July | 0.00 | 23173.88 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2675.07 | 22-JUL-19:00 | 28277.29 | 30-JUL-19:00 |
August | 0.00 | 23173.88 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2203.18 | 14-AUG-18:00 | 31589.81 | 22-AUG-16:00 |
September | 0.00 | 23173.88 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 533.73 | 24-SEP-16:00 | 27067.89 | 19-SEP-15:00 |
October | 0.00 | 23173.88 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 24164.38 | 01-OCT-24:00 |
November | 0.00 | 23173.88 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5303.17 | 24-NOV-12:00 | 22117.76 | 03-NOV-07:10 |
December | 0.00 | 23173.88 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5088.49 | 23-DEC-11:00 | 28139.61 | 02-DEC-17:55 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18868.60 | ||||
Maximum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 5303.17 | 49442.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 802.37 | 19-JAN-16:20 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 715.98 |
February | 840.68 | 04-FEB-16:30 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.32 |
March | 480.23 | 25-MAR-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3290.32 | 29-APR-15:50 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.05 |
May | 2940.54 | 25-MAY-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.27 |
June | 5196.00 | 13-JUN-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 235.39 | 0.00 |
July | 12721.47 | 24-JUL-05:03 | 290.07 | 2317.39 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 881.01 |
August | 5125.26 | 19-AUG-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.81 |
September | 4200.93 | 13-SEP-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.61 |
October | 1398.60 | 07-OCT-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 677.60 | 04-NOV-14:50 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.67 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 906.80 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.19 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 906.80 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12721.47 | 659.25 | 2317.39 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.39 | 881.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3430.16 | 20-JAN-09:30 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3568.15 | 17-FEB-09:50 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3473.26 | 15-MAR-13:50 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8798.12 | 28-APR-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7246.66 | 04-MAY-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.58 |
June | 7156.85 | 06-JUN-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6652.01 |
July | 33155.12 | 23-JUL-11:31 | 0.00 | 8297.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2321.80 |
August | 5671.66 | 15-AUG-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1960.86 |
September | 7108.62 | 23-SEP-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2860.66 |
October | 6232.02 | 13-OCT-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2994.11 | 16-NOV-09:00 | 0.00 | 8890.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3169.49 | 06-DEC-09:50 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2994.11 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33155.12 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6652.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 8179.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3955.68 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4053.27 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 01-APR-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4951.73 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9527.38 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11492.54 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20404.26 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9587.13 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11529.67 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16331.85 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7070.62 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3193.35 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 8179.02 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20404.26 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.703855E+11 | 54009.63 | 07-JAN-08:09 | 0.522550E+11 | 118135.61 | 10-JAN-06:10 |
February | 0.631803E+11 | 50197.99 | 16-FEB-13:39 | 0.389865E+11 | 79781.90 | 24-FEB-06:10 |
March | 0.707575E+11 | 50190.30 | 01-MAR-13:09 | 0.267730E+11 | 53867.72 | 04-MAR-06:19 |
April | 0.648906E+11 | 51156.79 | 29-APR-14:00 | 0.121068E+11 | 38571.72 | 11-APR-06:10 |
May | 0.660038E+11 | 51212.50 | 22-MAY-14:00 | 0.112259E+11 | 30548.06 | 06-MAY-05:10 |
June | 0.648863E+11 | 54308.96 | 13-JUN-14:00 | 0.877379E+10 | 14999.22 | 08-JUN-06:10 |
July | 0.647385E+11 | 57096.48 | 22-JUL-14:00 | 0.879831E+10 | 12156.66 | 05-JUL-06:10 |
August | 0.691207E+11 | 52769.01 | 14-AUG-14:39 | 0.874560E+10 | 7283.33 | 24-AUG-06:19 |
September | 0.659661E+11 | 51637.76 | 13-SEP-14:50 | 0.886782E+10 | 13953.33 | 21-SEP-06:10 |
October | 0.680360E+11 | 50549.15 | 07-OCT-14:00 | 0.145334E+11 | 35037.54 | 23-OCT-05:10 |
November | 0.671611E+11 | 53848.23 | 30-NOV-16:30 | 0.310698E+11 | 84296.95 | 28-NOV-06:10 |
December | 0.709685E+11 | 54008.92 | 28-DEC-08:09 | 0.715600E+11 | 103661.98 | 28-DEC-07:10 |
Annual Sum or Average | 0.806095E+12 | 0.293696E+12 | ||||
Minimum of Months | 0.631803E+11 | 50190.30 | 0.874560E+10 | 7283.33 | ||
Maximum of Months | 0.709685E+11 | 57096.48 | 0.715600E+11 | 118135.61 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.396181E+11 | 0.134685E+11 | 0.115358E+11 | 0.00 | 0.351404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224913E+10 | 0.00 |
February | 0.362526E+11 | 0.110831E+11 | 0.105871E+11 | 0.00 | 0.320637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205114E+10 | 0.00 |
March | 0.418523E+11 | 0.107861E+11 | 0.123357E+11 | 0.00 | 0.347078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231263E+10 | 0.00 |
April | 0.392410E+11 | 0.893812E+10 | 0.114862E+11 | 0.00 | 0.299851E+10 | 0.00 | 0.00 | 44275706.82 | 0.00 | 0.00 | 0.00 | 0.218249E+10 | 0.00 |
May | 0.407352E+11 | 0.791986E+10 | 0.119357E+11 | 0.00 | 0.310270E+10 | 0.00 | 0.00 | 74402653.63 | 0.00 | 0.00 | 0.00 | 0.223595E+10 | 0.00 |
June | 0.403581E+11 | 0.696287E+10 | 0.118862E+11 | 0.00 | 0.307731E+10 | 0.00 | 0.00 | 0.440427E+09 | 0.00 | 0.00 | 0.00 | 0.216151E+10 | 0.00 |
July | 0.396181E+11 | 0.750501E+10 | 0.115358E+11 | 0.00 | 0.296737E+10 | 0.00 | 0.00 | 0.953455E+09 | 0.00 | 0.00 | 0.00 | 0.215874E+10 | 0.00 |
August | 0.418523E+11 | 0.865056E+10 | 0.123357E+11 | 0.00 | 0.319336E+10 | 0.00 | 0.00 | 0.878543E+09 | 0.00 | 0.00 | 0.00 | 0.221027E+10 | 0.00 |
September | 0.392410E+11 | 0.978668E+10 | 0.114862E+11 | 0.00 | 0.295876E+10 | 0.00 | 0.00 | 0.378386E+09 | 0.00 | 0.00 | 0.00 | 0.211505E+10 | 0.00 |
October | 0.396181E+11 | 0.116535E+11 | 0.115358E+11 | 0.00 | 0.303997E+10 | 0.00 | 0.00 | 3991182.70 | 0.00 | 0.00 | 0.00 | 0.218459E+10 | 0.00 |
November | 0.381239E+11 | 0.126246E+11 | 0.110862E+11 | 0.00 | 0.319451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213177E+10 | 0.00 |
December | 0.396181E+11 | 0.138315E+11 | 0.115358E+11 | 0.00 | 0.375057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223254E+10 | 0.00 |
Annual Sum or Average | 0.476129E+12 | 0.123210E+12 | 0.139282E+12 | 0.384742E+11 | 0.00 | 0.277348E+10 | 0.262258E+11 | ||||||
Minimum of Months | 0.362526E+11 | 0.696287E+10 | 0.105871E+11 | 0.00 | 0.295876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205114E+10 | 0.00 |
Maximum of Months | 0.418523E+11 | 0.138315E+11 | 0.123357E+11 | 0.00 | 0.375057E+10 | 0.00 | 0.00 | 0.953455E+09 | 0.00 | 0.00 | 0.00 | 0.231263E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.522550E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.389865E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.267730E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.121068E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.112259E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.877379E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.879831E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.874560E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.886782E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.145334E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.310698E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.715600E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293696E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.874560E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.715600E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35189.04 | 02-JAN-09:09 | 7857.00 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 3110.75 | 07-JAN-08:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35189.04 | 01-FEB-09:09 | 7857.00 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 3110.75 | 23-FEB-07:19 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35189.04 | 01-MAR-09:09 | 7857.00 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 2986.68 | 01-MAR-07:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35189.04 | 01-APR-08:09 | 7857.00 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 2986.68 | 01-APR-06:19 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35189.04 | 01-MAY-08:09 | 7857.00 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 2986.68 | 05-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35189.04 | 01-JUN-08:09 | 7857.00 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 2986.68 | 13-JUN-16:40 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35189.04 | 01-JUL-08:09 | 7857.00 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 2986.68 | 19-JUL-13:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35189.04 | 01-AUG-08:09 | 7857.00 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 2986.68 | 17-AUG-12:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35189.04 | 01-SEP-08:09 | 7857.00 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 2986.68 | 01-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35189.04 | 02-OCT-08:09 | 7857.00 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 2986.68 | 17-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35189.04 | 01-NOV-08:09 | 7857.00 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 3110.75 | 20-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35189.04 | 01-DEC-09:09 | 7857.00 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 3110.75 | 13-DEC-07:19 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35189.04 | 7857.00 | 10112.62 | 0.00 | 2986.68 | 0.00 | 0.00 | |||||
Maximum of Months | 35189.04 | 7857.00 | 10112.62 | 0.00 | 3110.75 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2424.33 | 30-JAN-12:30 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2433.56 | 14-FEB-12:50 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2426.25 | 01-MAR-12:00 | 0.00 |
April | 1110.85 | 29-APR-15:50 | 0.00 | 0.00 | 0.00 | 2363.15 | 03-APR-11:30 | 0.00 |
May | 1162.52 | 22-MAY-15:50 | 0.00 | 0.00 | 0.00 | 2267.67 | 01-MAY-11:00 | 0.00 |
June | 4445.40 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | 2138.03 | 01-JUN-11:00 | 0.00 |
July | 7090.62 | 22-JUL-15:09 | 0.00 | 0.00 | 0.00 | 2004.94 | 06-JUL-11:50 | 0.00 |
August | 3206.82 | 14-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1950.33 | 01-AUG-11:00 | 0.00 |
September | 1641.98 | 13-SEP-15:00 | 0.00 | 0.00 | 0.00 | 2018.07 | 30-SEP-11:00 | 0.00 |
October | 491.06 | 07-OCT-15:30 | 0.00 | 0.00 | 0.00 | 2114.51 | 25-OCT-11:00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2238.52 | 24-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2366.34 | 30-DEC-12:20 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1950.33 | 0.00 | ||
Maximum of Months | 7090.62 | 0.00 | 0.00 | 0.00 | 2433.56 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 54009.63 | 07-JAN-08:09 | 31277.33 | 10112.62 | 7857.00 | 0.00 | 3110.75 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 50197.99 | 16-FEB-13:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2986.68 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 50190.30 | 01-MAR-13:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2986.68 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 51156.79 | 29-APR-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2986.68 | 0.00 | 0.00 | 1068.19 | 0.00 |
May | 51212.50 | 22-MAY-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2986.68 | 0.00 | 0.00 | 1131.20 | 0.00 |
June | 54308.96 | 13-JUN-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2986.68 | 0.00 | 0.00 | 4234.94 | 0.00 |
July | 57096.48 | 22-JUL-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2986.68 | 0.00 | 0.00 | 7030.62 | 0.00 |
August | 52769.01 | 14-AUG-14:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2986.68 | 0.00 | 0.00 | 2704.97 | 0.00 |
September | 51637.76 | 13-SEP-14:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2986.68 | 0.00 | 0.00 | 1571.64 | 0.00 |
October | 50549.15 | 07-OCT-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2986.68 | 0.00 | 0.00 | 477.43 | 0.00 |
November | 53848.23 | 30-NOV-16:30 | 31277.33 | 10112.62 | 7857.00 | 0.00 | 2986.68 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 54008.92 | 28-DEC-08:09 | 31277.33 | 10112.62 | 7857.00 | 0.00 | 3110.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 50190.30 | 31277.33 | 10112.62 | 0.00 | 0.00 | 2986.68 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 57096.48 | 35189.04 | 10112.62 | 7857.00 | 0.00 | 3110.75 | 0.00 | 0.00 | 7030.62 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 118135.61 | 10-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 79781.90 | 24-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 53867.72 | 04-MAR-06:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 38571.72 | 11-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 30548.06 | 06-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 14999.22 | 08-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 12156.66 | 05-JUL-06:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 7283.33 | 24-AUG-06:19 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 13953.33 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 35037.54 | 23-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 84296.95 | 28-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 103661.98 | 28-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 7283.33 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 118135.61 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.33 | 19.33 | 8.50 | 19.75 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7.67 | 19.75 | 7.67 | 19.75 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9.00 | 19.91 | 9.00 | 19.91 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5.33 | 20.23 | 5.33 | 20.23 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3.17 | 20.31 | 3.17 | 20.31 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.17 | 20.45 | 0.17 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.17 | 20.50 | 0.17 | 20.50 | 0.17 | 24.61 | 0.17 | 24.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5.17 | 20.24 | 5.17 | 20.24 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7.67 | 19.97 | 7.67 | 19.97 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8.83 | 19.42 | 8.50 | 19.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.50 | 19.81 | 55.33 | 19.91 | 0.17 | 24.61 | 0.17 | 24.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.33 | 20.50 | 9.00 | 20.50 | 0.17 | 24.61 | 0.17 | 24.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 47.50 | 14.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 56.50 | 14.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19.33 | 14.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2.50 | 14.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1.33 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.36 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4.17 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 40.83 | 14.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 83.50 | 14.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 255.67 | 14.77 | 0.00 | 0.17 | 27.36 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.50 | 14.98 | 0.00 | 0.00 | 0.17 | 27.36 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.06 | 300.00 | 21.06 | 300.00 | 21.06 |
February | 276.00 | 21.06 | 276.00 | 21.06 | 276.00 | 21.06 |
March | 324.00 | 21.07 | 324.00 | 21.07 | 324.00 | 21.07 |
April | 300.00 | 21.69 | 201.83 | 21.15 | 201.83 | 21.15 |
May | 312.00 | 21.95 | 136.00 | 21.11 | 136.00 | 21.11 |
June | 274.33 | 23.01 | 19.17 | 21.90 | 13.83 | 21.13 |
July | 168.83 | 23.31 | 44.83 | 23.68 | 3.33 | 21.03 |
August | 207.67 | 23.45 | 12.83 | 23.90 | 0.00 | 0.00 |
September | 284.17 | 23.11 | 12.00 | 21.08 | 12.00 | 21.08 |
October | 300.00 | 21.46 | 209.33 | 21.10 | 209.33 | 21.10 |
November | 288.00 | 21.07 | 287.33 | 21.07 | 287.33 | 21.07 |
December | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
Annual Sum or Average | 3335.00 | 21.84 | 2123.33 | 21.16 | 2063.67 | 21.08 |
Minimum of Months | 168.83 | 21.05 | 12.00 | 21.05 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 23.45 | 324.00 | 23.90 | 324.00 | 21.15 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.146804E+09 | 44275706.82 | 24.50 | 0.146773E+09 | 30731.38 | 0.00 | 0.29 | 29-APR-15:50 | 0.00 | 01-APR-00:05 | 3746.55 | 29-APR-15:50 | 3746.55 | 29-APR-15:50 | 10.73 | 28-APR-10:10 | 1110.85 | 29-APR-15:50 | 0.00 | 01-APR-00:05 |
May | 0.246965E+09 | 74402653.63 | 40.42 | 0.226652E+09 | 20313088.46 | 0.00 | 0.29 | 22-MAY-15:50 | 0.00 | 01-MAY-00:10 | 3934.27 | 22-MAY-15:50 | 3648.66 | 22-MAY-16:00 | 461.51 | 23-MAY-16:00 | 1162.52 | 22-MAY-15:50 | 0.00 | 01-MAY-00:10 |
June | 0.137930E+10 | 0.411228E+09 | 156.14 | 0.121826E+10 | 0.161036E+09 | 0.00 | 0.52 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 | 7304.14 | 13-JUN-16:00 | 6624.58 | 13-JUN-16:00 | 1339.36 | 27-JUN-07:30 | 2170.16 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.261709E+10 | 0.776825E+09 | 215.90 | 0.233139E+10 | 0.285696E+09 | 0.00 | 1.00 | 24-JUL-05:03 | 0.00 | 01-JUL-00:10 | 15632.54 | 24-JUL-05:03 | 12877.02 | 24-JUL-05:03 | 2755.52 | 24-JUL-05:03 | 4090.45 | 24-JUL-05:03 | 0.00 | 01-JUL-00:10 |
August | 0.292599E+10 | 0.866371E+09 | 249.69 | 0.260094E+10 | 0.325052E+09 | 0.00 | 0.49 | 14-AUG-16:00 | 0.00 | 01-AUG-00:10 | 6636.49 | 14-AUG-16:00 | 6413.53 | 14-AUG-16:00 | 1068.14 | 17-AUG-07:30 | 1973.32 | 14-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.126483E+10 | 0.378386E+09 | 162.72 | 0.113157E+10 | 0.133255E+09 | 0.00 | 0.41 | 13-SEP-16:00 | 0.00 | 01-SEP-00:10 | 5666.60 | 13-SEP-16:00 | 5113.53 | 13-SEP-16:00 | 753.26 | 12-SEP-14:20 | 1641.98 | 13-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 13069703.06 | 3991182.70 | 4.50 | 13069703.06 | 0.00 | 0.00 | 0.13 | 07-OCT-15:30 | 0.00 | 01-OCT-00:10 | 1615.71 | 07-OCT-15:30 | 1615.71 | 07-OCT-15:30 | 0.00 | 07-OCT-15:20 | 491.06 | 07-OCT-15:30 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.859405E+10 | 0.255548E+10 | 853.87 | 0.766867E+10 | 0.925383E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.292599E+10 | 0.866371E+09 | 249.69 | 0.260094E+10 | 0.325052E+09 | 0.00 | 1.00 | 0.00 | 15632.54 | 12877.02 | 2755.52 | 4090.45 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 0.106032E+09 | 29199382.86 | 6.00 | 91889522.37 | 14142138.62 | 0.00 | 0.27 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 | 8238.09 | 13-JUN-16:00 | 7386.49 | 13-JUN-16:00 | 1100.91 | 13-JUN-15:00 | 2275.24 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.637815E+09 | 0.176630E+09 | 28.29 | 0.622699E+09 | 15115571.64 | 0.00 | 1.00 | 21-JUL-17:21 | 0.00 | 01-JUL-00:10 | 35158.29 | 23-JUL-15:51 | 32982.09 | 21-JUL-17:21 | 8843.14 | 23-JUL-15:57 | 8256.55 | 23-JUL-15:51 | 0.00 | 01-JUL-00:10 |
August | 43350360.24 | 12172339.00 | 14.33 | 41411111.83 | 1939248.42 | 0.00 | 0.15 | 14-AUG-16:00 | 0.00 | 01-AUG-00:10 | 4378.48 | 14-AUG-16:00 | 4378.48 | 14-AUG-16:00 | 312.05 | 14-AUG-14:30 | 1233.51 | 14-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.787197E+09 | 0.218002E+09 | 48.62 | 0.756000E+09 | 31196958.68 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.637815E+09 | 0.176630E+09 | 28.29 | 0.622699E+09 | 15115571.64 | 0.00 | 1.00 | 0.00 | 35158.29 | 32982.09 | 8843.14 | 8256.55 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.08 | 15.38 | 31.69 | 22.19 | 132.50 | 0.00 | 0.00 | 744.00 |
February | 83.27 | 35.37 | 47.90 | 54.46 | 124.80 | 0.00 | 0.00 | 672.00 |
March | 75.05 | 14.43 | 60.62 | 39.02 | 98.58 | 0.00 | 0.00 | 744.00 |
April | 176.59 | 69.97 | 106.62 | 161.38 | 84.85 | 0.00 | 0.00 | 720.00 |
May | 207.09 | 83.94 | 123.15 | 185.94 | 74.01 | 0.00 | 0.00 | 744.00 |
June | 224.06 | 92.43 | 131.63 | 212.92 | 65.15 | 0.00 | 0.00 | 720.00 |
July | 228.20 | 100.66 | 127.55 | 224.06 | 65.38 | 0.00 | 0.00 | 744.00 |
August | 191.54 | 82.84 | 108.71 | 187.96 | 72.75 | 0.00 | 0.00 | 744.00 |
September | 155.05 | 70.08 | 84.97 | 146.52 | 84.82 | 0.00 | 0.00 | 720.00 |
October | 82.34 | 29.71 | 52.63 | 61.38 | 96.45 | 0.00 | 0.00 | 744.00 |
November | 44.57 | 13.12 | 31.45 | 20.89 | 117.21 | 0.00 | 0.00 | 720.00 |
December | 25.03 | 5.21 | 19.82 | 5.12 | 150.57 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 128.45 | 51.11 | 77.34 | 110.33 | 97.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 25.03 | 5.21 | 19.82 | 5.12 | 65.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 228.20 | 100.66 | 131.63 | 224.06 | 150.57 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.08 | 15.38 | 31.69 | 22.19 | 132.50 | 0.00 | 0.00 | 744.00 |
February | 83.27 | 35.37 | 47.90 | 54.46 | 124.80 | 0.00 | 0.00 | 672.00 |
March | 75.05 | 14.43 | 60.62 | 39.02 | 98.58 | 0.00 | 0.00 | 744.00 |
April | 176.59 | 69.97 | 106.62 | 161.38 | 84.85 | 0.00 | 0.00 | 720.00 |
May | 207.09 | 83.94 | 123.15 | 185.94 | 74.01 | 0.00 | 0.00 | 744.00 |
June | 224.06 | 92.43 | 131.63 | 212.92 | 65.15 | 0.00 | 0.00 | 720.00 |
July | 228.20 | 100.66 | 127.55 | 224.06 | 65.38 | 0.00 | 0.00 | 744.00 |
August | 191.54 | 82.84 | 108.71 | 187.96 | 72.75 | 0.00 | 0.00 | 744.00 |
September | 155.05 | 70.08 | 84.97 | 146.52 | 84.82 | 0.00 | 0.00 | 720.00 |
October | 82.34 | 29.71 | 52.63 | 61.38 | 96.45 | 0.00 | 0.00 | 744.00 |
November | 44.57 | 13.12 | 31.45 | 20.89 | 117.21 | 0.00 | 0.00 | 720.00 |
December | 25.03 | 5.21 | 19.82 | 5.12 | 150.57 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 128.45 | 51.11 | 77.34 | 110.33 | 97.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 25.03 | 5.21 | 19.82 | 5.12 | 65.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 228.20 | 100.66 | 131.63 | 224.06 | 150.57 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.74 | 0.00 | 13.74 | 0.74 | 81.85 | 0.00 | 0.00 | 744.00 |
February | 21.45 | 0.00 | 21.45 | 1.77 | 76.43 | 0.00 | 0.00 | 672.00 |
March | 29.69 | 0.00 | 29.69 | 7.58 | 60.23 | 0.00 | 0.00 | 744.00 |
April | 48.40 | 0.26 | 48.14 | 25.62 | 50.27 | 0.00 | 0.00 | 720.00 |
May | 60.68 | 3.13 | 57.55 | 29.17 | 41.84 | 0.00 | 0.00 | 744.00 |
June | 66.61 | 4.07 | 62.54 | 38.71 | 36.34 | 0.00 | 0.00 | 720.00 |
July | 63.32 | 3.57 | 59.75 | 38.12 | 36.51 | 0.00 | 0.00 | 744.00 |
August | 50.03 | 0.97 | 49.06 | 30.93 | 42.14 | 0.00 | 0.00 | 744.00 |
September | 37.93 | 0.02 | 37.91 | 20.92 | 50.65 | 0.00 | 0.00 | 720.00 |
October | 24.29 | 0.00 | 24.29 | 7.77 | 57.59 | 0.00 | 0.00 | 744.00 |
November | 14.59 | 0.00 | 14.59 | 0.94 | 70.39 | 0.00 | 0.00 | 720.00 |
December | 9.94 | 0.00 | 9.94 | 0.01 | 89.35 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 36.79 | 1.01 | 35.78 | 16.93 | 57.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 9.94 | 0.00 | 9.94 | 0.01 | 36.34 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 66.61 | 4.07 | 62.54 | 38.71 | 89.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.74 | 0.00 | 13.74 | 0.74 | 81.85 | 0.00 | 0.00 | 744.00 |
February | 21.45 | 0.00 | 21.45 | 1.77 | 76.43 | 0.00 | 0.00 | 672.00 |
March | 29.68 | 0.00 | 29.68 | 7.58 | 60.23 | 0.00 | 0.00 | 744.00 |
April | 48.39 | 0.26 | 48.13 | 25.62 | 50.27 | 0.00 | 0.00 | 720.00 |
May | 60.68 | 3.13 | 57.54 | 29.17 | 41.84 | 0.00 | 0.00 | 744.00 |
June | 66.61 | 4.07 | 62.54 | 38.71 | 36.34 | 0.00 | 0.00 | 720.00 |
July | 63.32 | 3.57 | 59.75 | 38.12 | 36.51 | 0.00 | 0.00 | 744.00 |
August | 50.03 | 0.97 | 49.06 | 30.93 | 42.14 | 0.00 | 0.00 | 744.00 |
September | 37.93 | 0.02 | 37.91 | 20.92 | 50.65 | 0.00 | 0.00 | 720.00 |
October | 24.29 | 0.00 | 24.29 | 7.77 | 57.59 | 0.00 | 0.00 | 744.00 |
November | 14.59 | 0.00 | 14.59 | 0.94 | 70.39 | 0.00 | 0.00 | 720.00 |
December | 9.94 | 0.00 | 9.94 | 0.01 | 89.35 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 36.79 | 1.01 | 35.78 | 16.93 | 57.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 9.94 | 0.00 | 9.94 | 0.01 | 36.34 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 66.61 | 4.07 | 62.54 | 38.71 | 89.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.15 | 3.40 | 10.75 | 6.46 | 30.41 | 53.33 | 0.00 | 744.00 |
February | 24.96 | 8.31 | 16.66 | 16.00 | 29.12 | 4.50 | 0.00 | 672.00 |
March | 32.21 | 5.99 | 26.22 | 26.80 | 23.60 | 2.67 | 0.00 | 744.00 |
April | 78.72 | 42.16 | 36.56 | 80.96 | 27.01 | 0.00 | 0.00 | 720.00 |
May | 94.93 | 52.74 | 42.19 | 97.11 | 24.61 | 0.00 | 0.00 | 744.00 |
June | 101.20 | 54.92 | 46.28 | 105.71 | 21.86 | 0.00 | 0.00 | 720.00 |
July | 102.65 | 60.09 | 42.56 | 107.12 | 24.18 | 0.00 | 0.00 | 744.00 |
August | 88.20 | 53.42 | 34.79 | 90.26 | 29.29 | 0.00 | 0.00 | 744.00 |
September | 63.99 | 37.85 | 26.14 | 60.41 | 32.97 | 0.00 | 0.00 | 720.00 |
October | 32.46 | 13.85 | 18.60 | 24.47 | 31.90 | 6.00 | 0.00 | 744.00 |
November | 15.64 | 4.13 | 11.51 | 7.31 | 27.95 | 4.33 | 0.00 | 720.00 |
December | 9.88 | 2.07 | 7.81 | 2.75 | 31.88 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 55.05 | 28.34 | 26.72 | 52.28 | 27.89 | 72.00 | 0.00 | 8760.00 |
Minimum of Months | 9.88 | 2.07 | 7.81 | 2.75 | 21.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.65 | 60.09 | 46.28 | 107.12 | 32.97 | 53.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.15 | 3.40 | 10.75 | 6.46 | 30.41 | 53.33 | 0.00 | 744.00 |
February | 24.96 | 8.31 | 16.66 | 16.00 | 29.12 | 4.50 | 0.00 | 672.00 |
March | 32.21 | 5.99 | 26.22 | 26.80 | 23.60 | 2.67 | 0.00 | 744.00 |
April | 78.72 | 42.16 | 36.56 | 80.96 | 27.01 | 0.00 | 0.00 | 720.00 |
May | 94.93 | 52.74 | 42.19 | 97.11 | 24.61 | 0.00 | 0.00 | 744.00 |
June | 101.20 | 54.92 | 46.28 | 105.71 | 21.86 | 0.00 | 0.00 | 720.00 |
July | 102.65 | 60.09 | 42.56 | 107.12 | 24.18 | 0.00 | 0.00 | 744.00 |
August | 88.20 | 53.42 | 34.79 | 90.26 | 29.29 | 0.00 | 0.00 | 744.00 |
September | 63.99 | 37.85 | 26.14 | 60.41 | 32.97 | 0.00 | 0.00 | 720.00 |
October | 32.46 | 13.85 | 18.60 | 24.47 | 31.90 | 6.00 | 0.00 | 744.00 |
November | 15.64 | 4.13 | 11.51 | 7.31 | 27.95 | 4.33 | 0.00 | 720.00 |
December | 9.88 | 2.07 | 7.81 | 2.75 | 31.88 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 55.05 | 28.34 | 26.72 | 52.28 | 27.89 | 72.00 | 0.00 | 8760.00 |
Minimum of Months | 9.88 | 2.07 | 7.81 | 2.75 | 21.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.65 | 60.09 | 46.28 | 107.12 | 32.97 | 53.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.15 | 3.40 | 10.75 | 6.46 | 30.41 | 53.33 | 0.00 | 744.00 |
February | 24.96 | 8.31 | 16.66 | 16.00 | 29.12 | 4.50 | 0.00 | 672.00 |
March | 32.21 | 5.99 | 26.22 | 26.80 | 23.60 | 2.67 | 0.00 | 744.00 |
April | 78.72 | 42.16 | 36.56 | 80.96 | 27.01 | 0.00 | 0.00 | 720.00 |
May | 94.93 | 52.74 | 42.19 | 97.11 | 24.61 | 0.00 | 0.00 | 744.00 |
June | 101.20 | 54.92 | 46.28 | 105.71 | 21.86 | 0.00 | 0.00 | 720.00 |
July | 102.65 | 60.09 | 42.56 | 107.12 | 24.18 | 0.00 | 0.00 | 744.00 |
August | 88.20 | 53.42 | 34.79 | 90.26 | 29.29 | 0.00 | 0.00 | 744.00 |
September | 63.99 | 37.85 | 26.14 | 60.41 | 32.97 | 0.00 | 0.00 | 720.00 |
October | 32.46 | 13.85 | 18.60 | 24.47 | 31.90 | 6.00 | 0.00 | 744.00 |
November | 15.64 | 4.13 | 11.51 | 7.31 | 27.95 | 4.33 | 0.00 | 720.00 |
December | 9.88 | 2.07 | 7.81 | 2.75 | 31.88 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 55.05 | 28.34 | 26.72 | 52.28 | 27.89 | 72.00 | 0.00 | 8760.00 |
Minimum of Months | 9.88 | 2.07 | 7.81 | 2.75 | 21.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.65 | 60.09 | 46.28 | 107.12 | 32.97 | 53.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.15 | 3.40 | 10.75 | 6.46 | 30.41 | 53.33 | 0.00 | 744.00 |
February | 24.96 | 8.31 | 16.66 | 16.00 | 29.12 | 4.50 | 0.00 | 672.00 |
March | 32.21 | 5.99 | 26.22 | 26.80 | 23.60 | 2.67 | 0.00 | 744.00 |
April | 78.72 | 42.16 | 36.56 | 80.96 | 27.01 | 0.00 | 0.00 | 720.00 |
May | 94.93 | 52.74 | 42.19 | 97.11 | 24.61 | 0.00 | 0.00 | 744.00 |
June | 101.20 | 54.92 | 46.28 | 105.71 | 21.86 | 0.00 | 0.00 | 720.00 |
July | 102.65 | 60.09 | 42.56 | 107.12 | 24.18 | 0.00 | 0.00 | 744.00 |
August | 88.20 | 53.42 | 34.79 | 90.26 | 29.29 | 0.00 | 0.00 | 744.00 |
September | 63.99 | 37.85 | 26.14 | 60.41 | 32.97 | 0.00 | 0.00 | 720.00 |
October | 32.46 | 13.85 | 18.60 | 24.47 | 31.90 | 6.00 | 0.00 | 744.00 |
November | 15.64 | 4.13 | 11.51 | 7.31 | 27.95 | 4.33 | 0.00 | 720.00 |
December | 9.88 | 2.07 | 7.81 | 2.75 | 31.88 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 55.05 | 28.34 | 26.72 | 52.28 | 27.89 | 72.00 | 0.00 | 8760.00 |
Minimum of Months | 9.88 | 2.07 | 7.81 | 2.75 | 21.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.65 | 60.09 | 46.28 | 107.12 | 32.97 | 53.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.15 | 3.40 | 10.75 | 6.46 | 30.41 | 53.33 | 0.00 | 744.00 |
February | 24.96 | 8.31 | 16.66 | 16.00 | 29.12 | 4.50 | 0.00 | 672.00 |
March | 32.21 | 5.99 | 26.22 | 26.80 | 23.60 | 2.67 | 0.00 | 744.00 |
April | 78.72 | 42.16 | 36.56 | 80.96 | 27.01 | 0.00 | 0.00 | 720.00 |
May | 94.93 | 52.74 | 42.19 | 97.11 | 24.61 | 0.00 | 0.00 | 744.00 |
June | 101.20 | 54.92 | 46.28 | 105.71 | 21.86 | 0.00 | 0.00 | 720.00 |
July | 102.65 | 60.09 | 42.56 | 107.12 | 24.18 | 0.00 | 0.00 | 744.00 |
August | 88.20 | 53.42 | 34.79 | 90.26 | 29.29 | 0.00 | 0.00 | 744.00 |
September | 63.99 | 37.85 | 26.14 | 60.41 | 32.97 | 0.00 | 0.00 | 720.00 |
October | 32.46 | 13.85 | 18.60 | 24.47 | 31.90 | 6.00 | 0.00 | 744.00 |
November | 15.64 | 4.13 | 11.51 | 7.31 | 27.95 | 4.33 | 0.00 | 720.00 |
December | 9.88 | 2.07 | 7.81 | 2.75 | 31.88 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 55.05 | 28.34 | 26.72 | 52.28 | 27.89 | 72.00 | 0.00 | 8760.00 |
Minimum of Months | 9.88 | 2.07 | 7.81 | 2.75 | 21.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.65 | 60.09 | 46.28 | 107.12 | 32.97 | 53.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.15 | 3.40 | 10.75 | 6.46 | 30.41 | 53.33 | 0.00 | 744.00 |
February | 24.96 | 8.31 | 16.66 | 16.00 | 29.12 | 4.50 | 0.00 | 672.00 |
March | 32.21 | 5.99 | 26.22 | 26.80 | 23.60 | 2.67 | 0.00 | 744.00 |
April | 78.72 | 42.16 | 36.56 | 80.96 | 27.01 | 0.00 | 0.00 | 720.00 |
May | 94.93 | 52.74 | 42.19 | 97.11 | 24.61 | 0.00 | 0.00 | 744.00 |
June | 101.20 | 54.92 | 46.28 | 105.71 | 21.86 | 0.00 | 0.00 | 720.00 |
July | 102.65 | 60.09 | 42.56 | 107.12 | 24.18 | 0.00 | 0.00 | 744.00 |
August | 88.20 | 53.42 | 34.79 | 90.26 | 29.29 | 0.00 | 0.00 | 744.00 |
September | 63.99 | 37.85 | 26.14 | 60.41 | 32.97 | 0.00 | 0.00 | 720.00 |
October | 32.46 | 13.85 | 18.60 | 24.47 | 31.90 | 6.00 | 0.00 | 744.00 |
November | 15.64 | 4.13 | 11.51 | 7.31 | 27.95 | 4.33 | 0.00 | 720.00 |
December | 9.88 | 2.07 | 7.81 | 2.75 | 31.88 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 55.05 | 28.34 | 26.72 | 52.28 | 27.89 | 72.00 | 0.00 | 8760.00 |
Minimum of Months | 9.88 | 2.07 | 7.81 | 2.75 | 21.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.65 | 60.09 | 46.28 | 107.12 | 32.97 | 53.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.15 | 3.40 | 10.75 | 6.46 | 30.41 | 53.33 | 0.00 | 744.00 |
February | 24.96 | 8.31 | 16.66 | 16.00 | 29.12 | 4.50 | 0.00 | 672.00 |
March | 32.21 | 5.99 | 26.22 | 26.80 | 23.60 | 2.67 | 0.00 | 744.00 |
April | 78.72 | 42.16 | 36.56 | 80.96 | 27.01 | 0.00 | 0.00 | 720.00 |
May | 94.93 | 52.74 | 42.19 | 97.11 | 24.61 | 0.00 | 0.00 | 744.00 |
June | 101.20 | 54.92 | 46.28 | 105.71 | 21.86 | 0.00 | 0.00 | 720.00 |
July | 102.65 | 60.09 | 42.56 | 107.12 | 24.18 | 0.00 | 0.00 | 744.00 |
August | 88.20 | 53.42 | 34.79 | 90.26 | 29.29 | 0.00 | 0.00 | 744.00 |
September | 63.99 | 37.85 | 26.14 | 60.41 | 32.97 | 0.00 | 0.00 | 720.00 |
October | 32.46 | 13.85 | 18.60 | 24.47 | 31.90 | 6.00 | 0.00 | 744.00 |
November | 15.64 | 4.13 | 11.51 | 7.31 | 27.95 | 4.33 | 0.00 | 720.00 |
December | 9.88 | 2.07 | 7.81 | 2.75 | 31.88 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 55.05 | 28.34 | 26.72 | 52.28 | 27.89 | 72.00 | 0.00 | 8760.00 |
Minimum of Months | 9.88 | 2.07 | 7.81 | 2.75 | 21.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.65 | 60.09 | 46.28 | 107.12 | 32.97 | 53.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.15 | 3.40 | 10.75 | 6.46 | 30.41 | 53.33 | 0.00 | 744.00 |
February | 24.96 | 8.31 | 16.66 | 16.00 | 29.12 | 4.50 | 0.00 | 672.00 |
March | 32.21 | 5.99 | 26.22 | 26.80 | 23.60 | 2.67 | 0.00 | 744.00 |
April | 78.72 | 42.16 | 36.56 | 80.96 | 27.01 | 0.00 | 0.00 | 720.00 |
May | 94.93 | 52.74 | 42.19 | 97.11 | 24.61 | 0.00 | 0.00 | 744.00 |
June | 101.20 | 54.92 | 46.28 | 105.71 | 21.86 | 0.00 | 0.00 | 720.00 |
July | 102.65 | 60.09 | 42.56 | 107.12 | 24.18 | 0.00 | 0.00 | 744.00 |
August | 88.20 | 53.42 | 34.79 | 90.26 | 29.29 | 0.00 | 0.00 | 744.00 |
September | 63.99 | 37.85 | 26.14 | 60.41 | 32.97 | 0.00 | 0.00 | 720.00 |
October | 32.46 | 13.85 | 18.60 | 24.47 | 31.90 | 6.00 | 0.00 | 744.00 |
November | 15.64 | 4.13 | 11.51 | 7.31 | 27.95 | 4.33 | 0.00 | 720.00 |
December | 9.88 | 2.07 | 7.81 | 2.75 | 31.88 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 55.05 | 28.34 | 26.72 | 52.28 | 27.89 | 72.00 | 0.00 | 8760.00 |
Minimum of Months | 9.88 | 2.07 | 7.81 | 2.75 | 21.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.65 | 60.09 | 46.28 | 107.12 | 32.97 | 53.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.15 | 3.40 | 10.75 | 6.46 | 30.41 | 53.33 | 0.00 | 744.00 |
February | 24.96 | 8.31 | 16.66 | 16.00 | 29.12 | 4.50 | 0.00 | 672.00 |
March | 32.21 | 5.99 | 26.22 | 26.80 | 23.60 | 2.67 | 0.00 | 744.00 |
April | 78.72 | 42.16 | 36.56 | 80.96 | 27.01 | 0.00 | 0.00 | 720.00 |
May | 94.93 | 52.74 | 42.19 | 97.11 | 24.61 | 0.00 | 0.00 | 744.00 |
June | 101.20 | 54.92 | 46.28 | 105.71 | 21.86 | 0.00 | 0.00 | 720.00 |
July | 102.65 | 60.09 | 42.56 | 107.12 | 24.18 | 0.00 | 0.00 | 744.00 |
August | 88.20 | 53.42 | 34.79 | 90.26 | 29.29 | 0.00 | 0.00 | 744.00 |
September | 63.99 | 37.85 | 26.14 | 60.41 | 32.97 | 0.00 | 0.00 | 720.00 |
October | 32.46 | 13.85 | 18.60 | 24.47 | 31.90 | 6.00 | 0.00 | 744.00 |
November | 15.64 | 4.13 | 11.51 | 7.31 | 27.95 | 4.33 | 0.00 | 720.00 |
December | 9.88 | 2.07 | 7.81 | 2.75 | 31.88 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 55.05 | 28.34 | 26.72 | 52.28 | 27.89 | 72.00 | 0.00 | 8760.00 |
Minimum of Months | 9.88 | 2.07 | 7.81 | 2.75 | 21.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.65 | 60.09 | 46.28 | 107.12 | 32.97 | 53.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.15 | 3.40 | 10.75 | 6.46 | 30.41 | 53.33 | 0.00 | 744.00 |
February | 24.96 | 8.31 | 16.66 | 16.00 | 29.12 | 4.50 | 0.00 | 672.00 |
March | 32.21 | 5.99 | 26.22 | 26.80 | 23.60 | 2.67 | 0.00 | 744.00 |
April | 78.72 | 42.16 | 36.56 | 80.96 | 27.01 | 0.00 | 0.00 | 720.00 |
May | 94.93 | 52.74 | 42.19 | 97.11 | 24.61 | 0.00 | 0.00 | 744.00 |
June | 101.20 | 54.92 | 46.28 | 105.71 | 21.86 | 0.00 | 0.00 | 720.00 |
July | 102.65 | 60.09 | 42.56 | 107.12 | 24.18 | 0.00 | 0.00 | 744.00 |
August | 88.20 | 53.42 | 34.79 | 90.26 | 29.29 | 0.00 | 0.00 | 744.00 |
September | 63.99 | 37.85 | 26.14 | 60.41 | 32.97 | 0.00 | 0.00 | 720.00 |
October | 32.46 | 13.85 | 18.60 | 24.47 | 31.90 | 6.00 | 0.00 | 744.00 |
November | 15.64 | 4.13 | 11.51 | 7.31 | 27.95 | 4.33 | 0.00 | 720.00 |
December | 9.88 | 2.07 | 7.81 | 2.75 | 31.88 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 55.05 | 28.34 | 26.72 | 52.28 | 27.89 | 72.00 | 0.00 | 8760.00 |
Minimum of Months | 9.88 | 2.07 | 7.81 | 2.75 | 21.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.65 | 60.09 | 46.28 | 107.12 | 32.97 | 53.33 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126092E+09 | 41204924.50 | 84886801.74 | 59427862.39 | 0.354880E+09 |
February | 0.201451E+09 | 85573389.59 | 0.115877E+09 | 0.131758E+09 | 0.301916E+09 |
March | 0.201005E+09 | 38641101.58 | 0.162364E+09 | 0.104507E+09 | 0.264047E+09 |
April | 0.457729E+09 | 0.181361E+09 | 0.276368E+09 | 0.418296E+09 | 0.219926E+09 |
May | 0.554673E+09 | 0.224832E+09 | 0.329841E+09 | 0.498014E+09 | 0.198239E+09 |
June | 0.580765E+09 | 0.239577E+09 | 0.341189E+09 | 0.551895E+09 | 0.168858E+09 |
July | 0.611216E+09 | 0.269595E+09 | 0.341621E+09 | 0.600113E+09 | 0.175103E+09 |
August | 0.513028E+09 | 0.221867E+09 | 0.291161E+09 | 0.503433E+09 | 0.194843E+09 |
September | 0.401901E+09 | 0.181659E+09 | 0.220242E+09 | 0.379769E+09 | 0.219859E+09 |
October | 0.220527E+09 | 79566066.80 | 0.140961E+09 | 0.164395E+09 | 0.258340E+09 |
November | 0.115518E+09 | 34010839.60 | 81506837.19 | 54151658.51 | 0.303800E+09 |
December | 67036011.80 | 13950708.21 | 53085303.59 | 13725819.08 | 0.403284E+09 |
Annual Sum or Average | 0.405094E+10 | 0.161184E+10 | 0.243910E+10 | 0.347949E+10 | 0.306310E+10 |
Minimum of Months | 67036011.80 | 13950708.21 | 53085303.59 | 13725819.08 | 0.168858E+09 |
Maximum of Months | 0.611216E+09 | 0.269595E+09 | 0.341621E+09 | 0.600113E+09 | 0.403284E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126092E+09 | 41204924.50 | 84886801.74 | 59427862.39 | 0.354880E+09 |
February | 0.201451E+09 | 85573389.59 | 0.115877E+09 | 0.131758E+09 | 0.301916E+09 |
March | 0.201005E+09 | 38641101.58 | 0.162364E+09 | 0.104507E+09 | 0.264047E+09 |
April | 0.457729E+09 | 0.181361E+09 | 0.276368E+09 | 0.418296E+09 | 0.219926E+09 |
May | 0.554673E+09 | 0.224832E+09 | 0.329841E+09 | 0.498014E+09 | 0.198239E+09 |
June | 0.580765E+09 | 0.239577E+09 | 0.341189E+09 | 0.551895E+09 | 0.168858E+09 |
July | 0.611216E+09 | 0.269595E+09 | 0.341621E+09 | 0.600113E+09 | 0.175103E+09 |
August | 0.513028E+09 | 0.221867E+09 | 0.291161E+09 | 0.503433E+09 | 0.194843E+09 |
September | 0.401901E+09 | 0.181659E+09 | 0.220242E+09 | 0.379769E+09 | 0.219859E+09 |
October | 0.220527E+09 | 79566066.80 | 0.140961E+09 | 0.164395E+09 | 0.258340E+09 |
November | 0.115518E+09 | 34010839.60 | 81506837.19 | 54151658.51 | 0.303800E+09 |
December | 67036011.80 | 13950708.21 | 53085303.59 | 13725819.08 | 0.403284E+09 |
Annual Sum or Average | 0.405094E+10 | 0.161184E+10 | 0.243910E+10 | 0.347949E+10 | 0.306310E+10 |
Minimum of Months | 67036011.80 | 13950708.21 | 53085303.59 | 13725819.08 | 0.168858E+09 |
Maximum of Months | 0.611216E+09 | 0.269595E+09 | 0.341621E+09 | 0.600113E+09 | 0.403284E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36791156.70 | 0.00 | 36791156.70 | 1992739.95 | 0.219235E+09 |
February | 51891179.80 | 0.00 | 51891179.80 | 4291118.87 | 0.184908E+09 |
March | 79510218.25 | 1082.28 | 79509135.97 | 20300114.47 | 0.161315E+09 |
April | 0.125442E+09 | 672185.46 | 0.124770E+09 | 66407739.10 | 0.130300E+09 |
May | 0.162527E+09 | 8394302.97 | 0.154133E+09 | 78131605.17 | 0.112055E+09 |
June | 0.172646E+09 | 10541371.11 | 0.162105E+09 | 0.100339E+09 | 94197958.79 |
July | 0.169605E+09 | 9572638.44 | 0.160033E+09 | 0.102109E+09 | 97776446.05 |
August | 0.133998E+09 | 2586120.74 | 0.131412E+09 | 82852542.00 | 0.112871E+09 |
September | 98322315.72 | 57709.22 | 98264606.49 | 54230383.51 | 0.131296E+09 |
October | 65057880.40 | 0.00 | 65057880.40 | 20809705.08 | 0.154248E+09 |
November | 37829128.19 | 0.00 | 37829128.19 | 2433688.46 | 0.182442E+09 |
December | 26620254.24 | 0.00 | 26620254.24 | 22384.50 | 0.239325E+09 |
Annual Sum or Average | 0.116024E+10 | 31825410.22 | 0.112841E+10 | 0.533919E+09 | 0.181997E+10 |
Minimum of Months | 26620254.24 | 0.00 | 26620254.24 | 22384.50 | 94197958.79 |
Maximum of Months | 0.172646E+09 | 10541371.11 | 0.162105E+09 | 0.102109E+09 | 0.239325E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36789895.72 | 0.00 | 36789895.72 | 1992445.85 | 0.219235E+09 |
February | 51889446.94 | 0.00 | 51889446.94 | 4290473.74 | 0.184908E+09 |
March | 79507385.95 | 1082.23 | 79506303.72 | 20298065.38 | 0.161315E+09 |
April | 0.125438E+09 | 672153.95 | 0.124766E+09 | 66404301.67 | 0.130300E+09 |
May | 0.162522E+09 | 8393909.51 | 0.154128E+09 | 78127195.68 | 0.112055E+09 |
June | 0.172641E+09 | 10540877.02 | 0.162100E+09 | 0.100333E+09 | 94197764.76 |
July | 0.169600E+09 | 9572189.75 | 0.160028E+09 | 0.102104E+09 | 97776207.96 |
August | 0.133994E+09 | 2585999.52 | 0.131408E+09 | 82849123.39 | 0.112870E+09 |
September | 98319441.92 | 57706.52 | 98261735.41 | 54228016.51 | 0.131296E+09 |
October | 65055758.06 | 0.00 | 65055758.06 | 20808239.57 | 0.154247E+09 |
November | 37827828.36 | 0.00 | 37827828.36 | 2433302.41 | 0.182442E+09 |
December | 26619327.93 | 0.00 | 26619327.93 | 22372.57 | 0.239325E+09 |
Annual Sum or Average | 0.116020E+10 | 31823918.52 | 0.112838E+10 | 0.533891E+09 | 0.181997E+10 |
Minimum of Months | 26619327.93 | 0.00 | 26619327.93 | 22372.57 | 94197764.76 |
Maximum of Months | 0.172641E+09 | 10540877.02 | 0.162100E+09 | 0.102104E+09 | 0.239325E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37905444.23 | 9101672.39 | 28803771.84 | 17310979.74 | 81458995.12 |
February | 60393569.87 | 20098472.06 | 40295097.81 | 38695566.14 | 70451970.71 |
March | 86281033.05 | 16043003.32 | 70238029.73 | 71780059.79 | 63200918.26 |
April | 0.204044E+09 | 0.109291E+09 | 94753445.94 | 0.209854E+09 | 69998416.50 |
May | 0.254247E+09 | 0.141247E+09 | 0.113000E+09 | 0.260102E+09 | 65916525.47 |
June | 0.262301E+09 | 0.142344E+09 | 0.119957E+09 | 0.273993E+09 | 56650071.77 |
July | 0.274945E+09 | 0.160950E+09 | 0.113995E+09 | 0.286913E+09 | 64761716.18 |
August | 0.236248E+09 | 0.143067E+09 | 93180774.06 | 0.241761E+09 | 78460852.33 |
September | 0.165854E+09 | 98109706.64 | 67744235.98 | 0.156580E+09 | 85460779.44 |
October | 86938865.76 | 37109153.57 | 49829712.19 | 65553004.38 | 85431206.09 |
November | 40549651.45 | 10711270.07 | 29838381.38 | 18936952.94 | 72441137.41 |
December | 26457630.01 | 5550370.93 | 20907259.09 | 7375921.88 | 85385179.57 |
Annual Sum or Average | 0.173617E+10 | 0.893623E+09 | 0.842543E+09 | 0.164886E+10 | 0.879618E+09 |
Minimum of Months | 26457630.01 | 5550370.93 | 20907259.09 | 7375921.88 | 56650071.77 |
Maximum of Months | 0.274945E+09 | 0.160950E+09 | 0.119957E+09 | 0.286913E+09 | 85460779.44 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37905444.23 | 9101672.39 | 28803771.84 | 17310979.74 | 81458995.12 |
February | 60393569.87 | 20098472.06 | 40295097.81 | 38695566.14 | 70451970.71 |
March | 86281033.05 | 16043003.32 | 70238029.73 | 71780059.79 | 63200918.26 |
April | 0.204044E+09 | 0.109291E+09 | 94753445.94 | 0.209854E+09 | 69998416.50 |
May | 0.254247E+09 | 0.141247E+09 | 0.113000E+09 | 0.260102E+09 | 65916525.47 |
June | 0.262301E+09 | 0.142344E+09 | 0.119957E+09 | 0.273993E+09 | 56650071.77 |
July | 0.274945E+09 | 0.160950E+09 | 0.113995E+09 | 0.286913E+09 | 64761716.18 |
August | 0.236248E+09 | 0.143067E+09 | 93180774.06 | 0.241761E+09 | 78460852.33 |
September | 0.165854E+09 | 98109706.64 | 67744235.98 | 0.156580E+09 | 85460779.44 |
October | 86938865.76 | 37109153.57 | 49829712.19 | 65553004.38 | 85431206.09 |
November | 40549651.45 | 10711270.07 | 29838381.38 | 18936952.94 | 72441137.41 |
December | 26457630.01 | 5550370.93 | 20907259.09 | 7375921.88 | 85385179.57 |
Annual Sum or Average | 0.173617E+10 | 0.893623E+09 | 0.842543E+09 | 0.164886E+10 | 0.879618E+09 |
Minimum of Months | 26457630.01 | 5550370.93 | 20907259.09 | 7375921.88 | 56650071.77 |
Maximum of Months | 0.274945E+09 | 0.160950E+09 | 0.119957E+09 | 0.286913E+09 | 85460779.44 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37905444.23 | 9101672.39 | 28803771.84 | 17310979.74 | 81458995.12 |
February | 60393569.87 | 20098472.06 | 40295097.81 | 38695566.14 | 70451970.71 |
March | 86281033.05 | 16043003.32 | 70238029.73 | 71780059.79 | 63200918.26 |
April | 0.204044E+09 | 0.109291E+09 | 94753445.94 | 0.209854E+09 | 69998416.50 |
May | 0.254247E+09 | 0.141247E+09 | 0.113000E+09 | 0.260102E+09 | 65916525.47 |
June | 0.262301E+09 | 0.142344E+09 | 0.119957E+09 | 0.273993E+09 | 56650071.77 |
July | 0.274945E+09 | 0.160950E+09 | 0.113995E+09 | 0.286913E+09 | 64761716.18 |
August | 0.236248E+09 | 0.143067E+09 | 93180774.06 | 0.241761E+09 | 78460852.33 |
September | 0.165854E+09 | 98109706.64 | 67744235.98 | 0.156580E+09 | 85460779.44 |
October | 86938865.76 | 37109153.57 | 49829712.19 | 65553004.38 | 85431206.09 |
November | 40549651.45 | 10711270.07 | 29838381.38 | 18936952.94 | 72441137.41 |
December | 26457630.01 | 5550370.93 | 20907259.09 | 7375921.88 | 85385179.57 |
Annual Sum or Average | 0.173617E+10 | 0.893623E+09 | 0.842543E+09 | 0.164886E+10 | 0.879618E+09 |
Minimum of Months | 26457630.01 | 5550370.93 | 20907259.09 | 7375921.88 | 56650071.77 |
Maximum of Months | 0.274945E+09 | 0.160950E+09 | 0.119957E+09 | 0.286913E+09 | 85460779.44 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37905444.23 | 9101672.39 | 28803771.84 | 17310979.74 | 81458995.12 |
February | 60393569.87 | 20098472.06 | 40295097.81 | 38695566.14 | 70451970.71 |
March | 86281033.05 | 16043003.32 | 70238029.73 | 71780059.79 | 63200918.26 |
April | 0.204044E+09 | 0.109291E+09 | 94753445.94 | 0.209854E+09 | 69998416.50 |
May | 0.254247E+09 | 0.141247E+09 | 0.113000E+09 | 0.260102E+09 | 65916525.47 |
June | 0.262301E+09 | 0.142344E+09 | 0.119957E+09 | 0.273993E+09 | 56650071.77 |
July | 0.274945E+09 | 0.160950E+09 | 0.113995E+09 | 0.286913E+09 | 64761716.18 |
August | 0.236248E+09 | 0.143067E+09 | 93180774.06 | 0.241761E+09 | 78460852.33 |
September | 0.165854E+09 | 98109706.64 | 67744235.98 | 0.156580E+09 | 85460779.44 |
October | 86938865.76 | 37109153.57 | 49829712.19 | 65553004.38 | 85431206.09 |
November | 40549651.45 | 10711270.07 | 29838381.38 | 18936952.94 | 72441137.41 |
December | 26457630.01 | 5550370.93 | 20907259.09 | 7375921.88 | 85385179.57 |
Annual Sum or Average | 0.173617E+10 | 0.893623E+09 | 0.842543E+09 | 0.164886E+10 | 0.879618E+09 |
Minimum of Months | 26457630.01 | 5550370.93 | 20907259.09 | 7375921.88 | 56650071.77 |
Maximum of Months | 0.274945E+09 | 0.160950E+09 | 0.119957E+09 | 0.286913E+09 | 85460779.44 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37905444.23 | 9101672.39 | 28803771.84 | 17310979.74 | 81458995.12 |
February | 60393569.87 | 20098472.06 | 40295097.81 | 38695566.14 | 70451970.71 |
March | 86281033.05 | 16043003.32 | 70238029.73 | 71780059.79 | 63200918.26 |
April | 0.204044E+09 | 0.109291E+09 | 94753445.94 | 0.209854E+09 | 69998416.50 |
May | 0.254247E+09 | 0.141247E+09 | 0.113000E+09 | 0.260102E+09 | 65916525.47 |
June | 0.262301E+09 | 0.142344E+09 | 0.119957E+09 | 0.273993E+09 | 56650071.77 |
July | 0.274945E+09 | 0.160950E+09 | 0.113995E+09 | 0.286913E+09 | 64761716.18 |
August | 0.236248E+09 | 0.143067E+09 | 93180774.06 | 0.241761E+09 | 78460852.33 |
September | 0.165854E+09 | 98109706.64 | 67744235.98 | 0.156580E+09 | 85460779.44 |
October | 86938865.76 | 37109153.57 | 49829712.19 | 65553004.38 | 85431206.09 |
November | 40549651.45 | 10711270.07 | 29838381.38 | 18936952.94 | 72441137.41 |
December | 26457630.01 | 5550370.93 | 20907259.09 | 7375921.88 | 85385179.57 |
Annual Sum or Average | 0.173617E+10 | 0.893623E+09 | 0.842543E+09 | 0.164886E+10 | 0.879618E+09 |
Minimum of Months | 26457630.01 | 5550370.93 | 20907259.09 | 7375921.88 | 56650071.77 |
Maximum of Months | 0.274945E+09 | 0.160950E+09 | 0.119957E+09 | 0.286913E+09 | 85460779.44 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37905444.23 | 9101672.39 | 28803771.84 | 17310979.74 | 81458995.12 |
February | 60393569.87 | 20098472.06 | 40295097.81 | 38695566.14 | 70451970.71 |
March | 86281033.05 | 16043003.32 | 70238029.73 | 71780059.79 | 63200918.26 |
April | 0.204044E+09 | 0.109291E+09 | 94753445.94 | 0.209854E+09 | 69998416.50 |
May | 0.254247E+09 | 0.141247E+09 | 0.113000E+09 | 0.260102E+09 | 65916525.47 |
June | 0.262301E+09 | 0.142344E+09 | 0.119957E+09 | 0.273993E+09 | 56650071.77 |
July | 0.274945E+09 | 0.160950E+09 | 0.113995E+09 | 0.286913E+09 | 64761716.18 |
August | 0.236248E+09 | 0.143067E+09 | 93180774.06 | 0.241761E+09 | 78460852.33 |
September | 0.165854E+09 | 98109706.64 | 67744235.98 | 0.156580E+09 | 85460779.44 |
October | 86938865.76 | 37109153.57 | 49829712.19 | 65553004.38 | 85431206.09 |
November | 40549651.45 | 10711270.07 | 29838381.38 | 18936952.94 | 72441137.41 |
December | 26457630.01 | 5550370.93 | 20907259.09 | 7375921.88 | 85385179.57 |
Annual Sum or Average | 0.173617E+10 | 0.893623E+09 | 0.842543E+09 | 0.164886E+10 | 0.879618E+09 |
Minimum of Months | 26457630.01 | 5550370.93 | 20907259.09 | 7375921.88 | 56650071.77 |
Maximum of Months | 0.274945E+09 | 0.160950E+09 | 0.119957E+09 | 0.286913E+09 | 85460779.44 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37905444.23 | 9101672.39 | 28803771.84 | 17310979.74 | 81458995.12 |
February | 60393569.87 | 20098472.06 | 40295097.81 | 38695566.14 | 70451970.71 |
March | 86281033.05 | 16043003.32 | 70238029.73 | 71780059.79 | 63200918.26 |
April | 0.204044E+09 | 0.109291E+09 | 94753445.94 | 0.209854E+09 | 69998416.50 |
May | 0.254247E+09 | 0.141247E+09 | 0.113000E+09 | 0.260102E+09 | 65916525.47 |
June | 0.262301E+09 | 0.142344E+09 | 0.119957E+09 | 0.273993E+09 | 56650071.77 |
July | 0.274945E+09 | 0.160950E+09 | 0.113995E+09 | 0.286913E+09 | 64761716.18 |
August | 0.236248E+09 | 0.143067E+09 | 93180774.06 | 0.241761E+09 | 78460852.33 |
September | 0.165854E+09 | 98109706.64 | 67744235.98 | 0.156580E+09 | 85460779.44 |
October | 86938865.76 | 37109153.57 | 49829712.19 | 65553004.38 | 85431206.09 |
November | 40549651.45 | 10711270.07 | 29838381.38 | 18936952.94 | 72441137.41 |
December | 26457630.01 | 5550370.93 | 20907259.09 | 7375921.88 | 85385179.57 |
Annual Sum or Average | 0.173617E+10 | 0.893623E+09 | 0.842543E+09 | 0.164886E+10 | 0.879618E+09 |
Minimum of Months | 26457630.01 | 5550370.93 | 20907259.09 | 7375921.88 | 56650071.77 |
Maximum of Months | 0.274945E+09 | 0.160950E+09 | 0.119957E+09 | 0.286913E+09 | 85460779.44 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37905444.23 | 9101672.39 | 28803771.84 | 17310979.74 | 81458995.12 |
February | 60393569.87 | 20098472.06 | 40295097.81 | 38695566.14 | 70451970.71 |
March | 86281033.05 | 16043003.32 | 70238029.73 | 71780059.79 | 63200918.26 |
April | 0.204044E+09 | 0.109291E+09 | 94753445.94 | 0.209854E+09 | 69998416.50 |
May | 0.254247E+09 | 0.141247E+09 | 0.113000E+09 | 0.260102E+09 | 65916525.47 |
June | 0.262301E+09 | 0.142344E+09 | 0.119957E+09 | 0.273993E+09 | 56650071.77 |
July | 0.274945E+09 | 0.160950E+09 | 0.113995E+09 | 0.286913E+09 | 64761716.18 |
August | 0.236248E+09 | 0.143067E+09 | 93180774.06 | 0.241761E+09 | 78460852.33 |
September | 0.165854E+09 | 98109706.64 | 67744235.98 | 0.156580E+09 | 85460779.44 |
October | 86938865.76 | 37109153.57 | 49829712.19 | 65553004.38 | 85431206.09 |
November | 40549651.45 | 10711270.07 | 29838381.38 | 18936952.94 | 72441137.41 |
December | 26457630.01 | 5550370.93 | 20907259.09 | 7375921.88 | 85385179.57 |
Annual Sum or Average | 0.173617E+10 | 0.893623E+09 | 0.842543E+09 | 0.164886E+10 | 0.879618E+09 |
Minimum of Months | 26457630.01 | 5550370.93 | 20907259.09 | 7375921.88 | 56650071.77 |
Maximum of Months | 0.274945E+09 | 0.160950E+09 | 0.119957E+09 | 0.286913E+09 | 85460779.44 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37905444.23 | 9101672.39 | 28803771.84 | 17310979.74 | 81458995.12 |
February | 60393569.87 | 20098472.06 | 40295097.81 | 38695566.14 | 70451970.71 |
March | 86281033.05 | 16043003.32 | 70238029.73 | 71780059.79 | 63200918.26 |
April | 0.204044E+09 | 0.109291E+09 | 94753445.94 | 0.209854E+09 | 69998416.50 |
May | 0.254247E+09 | 0.141247E+09 | 0.113000E+09 | 0.260102E+09 | 65916525.47 |
June | 0.262301E+09 | 0.142344E+09 | 0.119957E+09 | 0.273993E+09 | 56650071.77 |
July | 0.274945E+09 | 0.160950E+09 | 0.113995E+09 | 0.286913E+09 | 64761716.18 |
August | 0.236248E+09 | 0.143067E+09 | 93180774.06 | 0.241761E+09 | 78460852.33 |
September | 0.165854E+09 | 98109706.64 | 67744235.98 | 0.156580E+09 | 85460779.44 |
October | 86938865.76 | 37109153.57 | 49829712.19 | 65553004.38 | 85431206.09 |
November | 40549651.45 | 10711270.07 | 29838381.38 | 18936952.94 | 72441137.41 |
December | 26457630.01 | 5550370.93 | 20907259.09 | 7375921.88 | 85385179.57 |
Annual Sum or Average | 0.173617E+10 | 0.893623E+09 | 0.842543E+09 | 0.164886E+10 | 0.879618E+09 |
Minimum of Months | 26457630.01 | 5550370.93 | 20907259.09 | 7375921.88 | 56650071.77 |
Maximum of Months | 0.274945E+09 | 0.160950E+09 | 0.119957E+09 | 0.286913E+09 | 85460779.44 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37905444.23 | 9101672.39 | 28803771.84 | 17310979.74 | 81458995.12 |
February | 60393569.87 | 20098472.06 | 40295097.81 | 38695566.14 | 70451970.71 |
March | 86281033.05 | 16043003.32 | 70238029.73 | 71780059.79 | 63200918.26 |
April | 0.204044E+09 | 0.109291E+09 | 94753445.94 | 0.209854E+09 | 69998416.50 |
May | 0.254247E+09 | 0.141247E+09 | 0.113000E+09 | 0.260102E+09 | 65916525.47 |
June | 0.262301E+09 | 0.142344E+09 | 0.119957E+09 | 0.273993E+09 | 56650071.77 |
July | 0.274945E+09 | 0.160950E+09 | 0.113995E+09 | 0.286913E+09 | 64761716.18 |
August | 0.236248E+09 | 0.143067E+09 | 93180774.06 | 0.241761E+09 | 78460852.33 |
September | 0.165854E+09 | 98109706.64 | 67744235.98 | 0.156580E+09 | 85460779.44 |
October | 86938865.76 | 37109153.57 | 49829712.19 | 65553004.38 | 85431206.09 |
November | 40549651.45 | 10711270.07 | 29838381.38 | 18936952.94 | 72441137.41 |
December | 26457630.01 | 5550370.93 | 20907259.09 | 7375921.88 | 85385179.57 |
Annual Sum or Average | 0.173617E+10 | 0.893623E+09 | 0.842543E+09 | 0.164886E+10 | 0.879618E+09 |
Minimum of Months | 26457630.01 | 5550370.93 | 20907259.09 | 7375921.88 | 56650071.77 |
Maximum of Months | 0.274945E+09 | 0.160950E+09 | 0.119957E+09 | 0.286913E+09 | 85460779.44 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 39.51 | 422.35 | 121.63 | 30.77 | 90.86 | 0.00 | 0.00 |
February | 106.55 | 396.55 | 209.44 | 70.75 | 138.70 | 0.00 | 0.00 |
March | 89.65 | 314.08 | 209.46 | 28.85 | 180.61 | 0.00 | 0.00 |
April | 371.58 | 267.82 | 449.98 | 140.46 | 309.52 | 0.00 | 0.00 |
May | 428.64 | 230.13 | 535.54 | 174.15 | 361.39 | 0.00 | 0.00 |
June | 501.77 | 201.48 | 581.33 | 192.99 | 388.34 | 0.00 | 0.00 |
July | 522.78 | 202.18 | 583.05 | 208.46 | 374.59 | 0.00 | 0.00 |
August | 436.45 | 228.44 | 483.14 | 167.60 | 315.54 | 0.00 | 0.00 |
September | 332.33 | 268.41 | 385.97 | 140.21 | 245.76 | 0.00 | 0.00 |
October | 135.84 | 305.63 | 213.25 | 59.41 | 153.84 | 0.00 | 0.00 |
November | 40.22 | 371.75 | 118.32 | 26.24 | 92.08 | 0.00 | 0.00 |
December | 7.94 | 477.52 | 69.93 | 10.42 | 59.52 | 0.00 | 0.00 |
Annual Sum or Average | 251.63 | 306.79 | 330.49 | 104.24 | 226.25 | 0.00 | 0.00 |
Minimum of Months | 7.94 | 201.48 | 69.93 | 10.42 | 59.52 | 0.00 | 0.00 |
Maximum of Months | 522.78 | 477.52 | 583.05 | 208.46 | 388.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 64.63 | 304.13 | 141.52 | 33.98 | 107.54 | 0.00 | 0.00 |
February | 159.95 | 291.22 | 249.64 | 83.08 | 166.56 | 0.00 | 0.00 |
March | 268.00 | 235.96 | 322.14 | 59.90 | 262.24 | 0.00 | 0.00 |
April | 809.62 | 270.06 | 787.21 | 421.65 | 365.56 | 0.00 | 0.00 |
May | 971.11 | 246.10 | 949.25 | 527.36 | 421.89 | 0.00 | 0.00 |
June | 1057.07 | 218.56 | 1011.97 | 549.17 | 462.80 | 0.00 | 0.00 |
July | 1071.21 | 241.79 | 1026.53 | 600.92 | 425.61 | 0.00 | 0.00 |
August | 902.63 | 292.94 | 882.05 | 534.15 | 347.90 | 0.00 | 0.00 |
September | 604.09 | 329.71 | 639.87 | 378.51 | 261.36 | 0.00 | 0.00 |
October | 244.75 | 318.96 | 324.59 | 138.55 | 186.04 | 0.00 | 0.00 |
November | 73.06 | 279.48 | 156.44 | 41.32 | 115.12 | 0.00 | 0.00 |
December | 27.54 | 318.79 | 98.78 | 20.72 | 78.06 | 0.00 | 0.00 |
Annual Sum or Average | 522.85 | 278.92 | 550.53 | 283.37 | 267.17 | 0.00 | 0.00 |
Minimum of Months | 27.54 | 218.56 | 98.78 | 20.72 | 78.06 | 0.00 | 0.00 |
Maximum of Months | 1071.21 | 329.71 | 1026.53 | 600.92 | 462.80 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105828E+09 | 0.113122E+10 | 0.325765E+09 | 82409848.99 | 0.243355E+09 | 0.00 | 0.00 |
February | 0.257774E+09 | 0.959324E+09 | 0.506682E+09 | 0.171147E+09 | 0.335535E+09 | 0.00 | 0.00 |
March | 0.240125E+09 | 0.841238E+09 | 0.561028E+09 | 77284367.67 | 0.483744E+09 | 0.00 | 0.00 |
April | 0.963136E+09 | 0.694185E+09 | 0.116634E+10 | 0.364067E+09 | 0.802271E+09 | 0.00 | 0.00 |
May | 0.114807E+10 | 0.616374E+09 | 0.143439E+10 | 0.466452E+09 | 0.967942E+09 | 0.00 | 0.00 |
June | 0.130059E+10 | 0.522240E+09 | 0.150682E+10 | 0.500235E+09 | 0.100658E+10 | 0.00 | 0.00 |
July | 0.140021E+10 | 0.541532E+09 | 0.156164E+10 | 0.558335E+09 | 0.100330E+10 | 0.00 | 0.00 |
August | 0.116899E+10 | 0.611852E+09 | 0.129405E+10 | 0.448906E+09 | 0.845141E+09 | 0.00 | 0.00 |
September | 0.861402E+09 | 0.695715E+09 | 0.100044E+10 | 0.363434E+09 | 0.637010E+09 | 0.00 | 0.00 |
October | 0.363832E+09 | 0.818600E+09 | 0.571168E+09 | 0.159132E+09 | 0.412036E+09 | 0.00 | 0.00 |
November | 0.104251E+09 | 0.963565E+09 | 0.306692E+09 | 68021679.19 | 0.238671E+09 | 0.00 | 0.00 |
December | 21260961.27 | 0.127898E+10 | 0.187312E+09 | 27901416.42 | 0.159410E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.793548E+10 | 0.967482E+10 | 0.104223E+11 | 0.328733E+10 | 0.713500E+10 | 0.00 | 0.00 |
Minimum of Months | 21260961.27 | 0.522240E+09 | 0.187312E+09 | 27901416.42 | 0.159410E+09 | 0.00 | 0.00 |
Maximum of Months | 0.140021E+10 | 0.127898E+10 | 0.156164E+10 | 0.558335E+09 | 0.100658E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.173107E+09 | 0.814590E+09 | 0.379054E+09 | 91016723.91 | 0.288038E+09 | 0.00 | 0.00 |
February | 0.386956E+09 | 0.704520E+09 | 0.603936E+09 | 0.200985E+09 | 0.402951E+09 | 0.00 | 0.00 |
March | 0.717801E+09 | 0.632007E+09 | 0.862810E+09 | 0.160430E+09 | 0.702380E+09 | 0.00 | 0.00 |
April | 0.209854E+10 | 0.699984E+09 | 0.204044E+10 | 0.109291E+10 | 0.947534E+09 | 0.00 | 0.00 |
May | 0.260102E+10 | 0.659163E+09 | 0.254247E+10 | 0.141247E+10 | 0.113000E+10 | 0.00 | 0.00 |
June | 0.273993E+10 | 0.566500E+09 | 0.262301E+10 | 0.142344E+10 | 0.119957E+10 | 0.00 | 0.00 |
July | 0.286913E+10 | 0.647617E+09 | 0.274945E+10 | 0.160950E+10 | 0.113995E+10 | 0.00 | 0.00 |
August | 0.241761E+10 | 0.784609E+09 | 0.236248E+10 | 0.143067E+10 | 0.931808E+09 | 0.00 | 0.00 |
September | 0.156580E+10 | 0.854607E+09 | 0.165854E+10 | 0.981097E+09 | 0.677442E+09 | 0.00 | 0.00 |
October | 0.655529E+09 | 0.854311E+09 | 0.869389E+09 | 0.371092E+09 | 0.498297E+09 | 0.00 | 0.00 |
November | 0.189367E+09 | 0.724411E+09 | 0.405497E+09 | 0.107113E+09 | 0.298384E+09 | 0.00 | 0.00 |
December | 73758344.61 | 0.853852E+09 | 0.264576E+09 | 55503709.26 | 0.209073E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.164885E+11 | 0.879617E+10 | 0.173617E+11 | 0.893623E+10 | 0.842543E+10 | 0.00 | 0.00 |
Minimum of Months | 73758344.61 | 0.566500E+09 | 0.264576E+09 | 55503709.26 | 0.209073E+09 | 0.00 | 0.00 |
Maximum of Months | 0.286913E+10 | 0.854607E+09 | 0.274945E+10 | 0.160950E+10 | 0.119957E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.24 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -2.0 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.23 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.06 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.26 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.48 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.74 | 10.65 | 2.92 | 3.94 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.42 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.65 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.74 | 10.65 | 3.35 | 4.48 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.36 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.21 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.10 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.06 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.51 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.77 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.15 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.21 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.08 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.62 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.62 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.51 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -6.9 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.8 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.04 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.4 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -6.9 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.06 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.29 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.04 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.53 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.00 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.94 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.44 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.53 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.955928E+09 | -869201507.3 | 0.00 | 0.00 | 744.00 | 0.00 | -86726475.6 | 58.99 | 0.00 | 0.00 |
February | 0.882086E+09 | -803823704.8 | 0.00 | 0.00 | 672.00 | 0.00 | -78262236.6 | 58.99 | 0.00 | 0.00 |
March | 0.101895E+10 | -933231258.5 | 0.00 | 0.00 | 744.00 | 0.00 | -85715874.6 | 59.00 | 0.00 | 0.00 |
April | 0.930426E+09 | -850509906.6 | 0.00 | 0.00 | 720.00 | 0.00 | -79915688.7 | 58.99 | 0.00 | 0.00 |
May | 0.942509E+09 | -860906110.9 | 0.00 | 0.00 | 744.00 | 0.00 | -81603141.5 | 58.99 | 0.00 | 0.00 |
June | 0.909345E+09 | -834454335.0 | 0.00 | 0.00 | 720.00 | 0.00 | -74890910.0 | 58.99 | 0.00 | 0.00 |
July | 0.865071E+09 | -789601084.0 | 0.00 | 0.00 | 744.00 | 0.00 | -75470006.8 | 58.99 | 0.00 | 0.00 |
August | 0.916547E+09 | -841417062.9 | 0.00 | 0.00 | 744.00 | 0.00 | -75130041.1 | 58.99 | 0.00 | 0.00 |
September | 0.863234E+09 | -787979324.4 | 0.00 | 0.00 | 720.00 | 0.00 | -75254276.0 | 58.99 | 0.00 | 0.00 |
October | 0.890472E+09 | -806775094.4 | 0.00 | 0.00 | 744.00 | 0.00 | -83697181.9 | 58.99 | 0.00 | 0.00 |
November | 0.879840E+09 | -796612388.7 | 0.00 | 0.00 | 720.00 | 0.00 | -83227881.5 | 58.99 | 0.00 | 0.00 |
December | 0.938904E+09 | -851919072.3 | 0.00 | 0.00 | 744.00 | 0.00 | -86984951.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.109933E+11 | -.100264E+11 | 8760.00 | -966878665.9 | 58.99 | |||||
Minimum of Months | 0.863234E+09 | -933231258.5 | 0.00 | 0.00 | 672.00 | 0.00 | -86984951.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.101895E+10 | -787979324.4 | 0.00 | 0.00 | 744.00 | 0.00 | -74890910.0 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 195.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 217.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 215.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 417.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 410.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 396.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 234.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 171.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3515.67 | ||||||||||
Minimum of Months | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.606294E+10 | 24085.62 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.503786E+10 | 24085.62 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.509293E+10 | 24085.62 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191989E+10 | 24085.62 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136530E+10 | 24085.62 | 02-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.235708E+09 | 24085.62 | 06-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 62567946.47 | 24085.62 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 26554681.68 | 3719.52 | 24-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.298840E+09 | 24085.62 | 07-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.217885E+10 | 24085.62 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.430483E+10 | 24085.62 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.614312E+10 | 24085.62 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327294E+11 | |||||||
Minimum of Months | 26554681.68 | 3719.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.614312E+10 | 24085.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.141586E+11 | 60859.24 | 01-JAN-16:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119779E+11 | 60859.24 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.713786E+10 | 60859.24 | 04-MAR-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.607512E+09 | 60859.24 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.354085E+09 | 60859.24 | 17-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179087E+10 | 58086.75 | 16-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.976358E+10 | 60859.24 | 14-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201893E+11 | 60859.24 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.659798E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.201893E+11 | 60859.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120697E+11 | 44545.91 | 10-JAN-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.554874E+10 | 29532.70 | 19-FEB-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.200627E+09 | 11736.28 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193273E+10 | 26692.31 | 29-NOV-03:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.210395E+11 | 45148.19 | 30-DEC-00:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.407912E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.210395E+11 | 45148.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.146804E+09 | 0.146773E+09 | 3746.55 | 29-APR-15:50 | 3746.55 | 0.00 |
May | 0.00 | 0.00 | 0.246965E+09 | 0.226652E+09 | 3934.27 | 22-MAY-15:50 | 3646.79 | 0.00 |
June | 0.00 | 0.00 | 0.137930E+10 | 0.121826E+10 | 7304.14 | 13-JUN-16:00 | 6624.58 | 0.00 |
July | 0.00 | 0.00 | 0.261709E+10 | 0.233139E+10 | 15632.54 | 24-JUL-05:03 | 12877.02 | 0.00 |
August | 0.00 | 0.00 | 0.292599E+10 | 0.260094E+10 | 6636.49 | 14-AUG-16:00 | 6413.53 | 0.00 |
September | 0.00 | 0.00 | 0.126483E+10 | 0.113157E+10 | 5666.60 | 13-SEP-16:00 | 5113.53 | 0.00 |
October | 0.00 | 0.00 | 13069703.06 | 13069703.06 | 1615.71 | 07-OCT-15:30 | 1615.71 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.859405E+10 | 0.766867E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.292599E+10 | 0.260094E+10 | 15632.54 | 12877.02 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.106032E+09 | 91889522.37 | 8238.09 | 13-JUN-16:00 | 7386.49 | 0.00 |
July | 0.00 | 0.00 | 0.637815E+09 | 0.622699E+09 | 35158.29 | 23-JUL-15:51 | 26428.36 | 0.00 |
August | 0.00 | 0.00 | 43350360.24 | 41411111.83 | 4378.48 | 14-AUG-16:00 | 4378.48 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.787197E+09 | 0.756000E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.637815E+09 | 0.622699E+09 | 35158.29 | 26428.36 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.115510E+09 | 0.03 | 124.07 | 01-JAN-00:03 | 0.08 |
February | 68116377.61 | 0.02 | 124.07 | 04-FEB-02:00 | 0.08 |
March | 7245499.25 | 0.00 | 124.07 | 03-MAR-22:50 | 0.08 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 24695490.16 | 0.01 | 124.07 | 19-NOV-07:50 | 0.08 |
December | 0.190393E+09 | 0.04 | 124.07 | 01-DEC-00:45 | 0.08 |
Annual Sum or Average | 0.405960E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.190393E+09 | 0.04 | 124.07 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.105263E+10 | 0.39 | 1024.98 | 02-JAN-06:01 | 0.95 |
February | 0.967151E+09 | 0.39 | 1024.98 | 01-FEB-06:01 | 0.94 |
March | 0.113043E+10 | 0.41 | 1024.98 | 01-MAR-06:01 | 0.94 |
April | 0.103426E+10 | 0.38 | 1024.98 | 04-APR-13:50 | 0.94 |
May | 0.106990E+10 | 0.38 | 1024.98 | 01-MAY-06:05 | 0.94 |
June | 0.105755E+10 | 0.38 | 1024.98 | 01-JUN-06:05 | 0.94 |
July | 0.101644E+10 | 0.35 | 1024.98 | 06-JUL-09:10 | 0.94 |
August | 0.109591E+10 | 0.37 | 1024.98 | 08-AUG-16:20 | 0.94 |
September | 0.101668E+10 | 0.36 | 1024.98 | 19-SEP-14:40 | 0.94 |
October | 0.103485E+10 | 0.37 | 1024.98 | 20-OCT-12:40 | 0.94 |
November | 0.100306E+10 | 0.37 | 1024.98 | 01-NOV-05:01 | 0.94 |
December | 0.105261E+10 | 0.38 | 1024.98 | 01-DEC-06:01 | 0.94 |
Annual Sum or Average | 0.125315E+11 | 0.38 | |||
Minimum of Months | 0.967151E+09 | 0.35 | 1024.98 | 0.94 | |
Maximum of Months | 0.113043E+10 | 0.41 | 1024.98 | 0.95 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.234590E+10 | 0.71 | 1961.70 | 05-JAN-09:20 | 0.91 |
February | 0.217110E+10 | 0.73 | 1961.70 | 01-FEB-08:20 | 0.90 |
March | 0.233310E+10 | 0.64 | 1961.70 | 01-MAR-07:30 | 0.91 |
April | 0.196425E+10 | 0.38 | 1961.70 | 03-APR-06:10 | 0.91 |
May | 0.203280E+10 | 0.37 | 1961.70 | 05-MAY-06:10 | 0.91 |
June | 0.201976E+10 | 0.36 | 1961.70 | 13-JUN-16:40 | 0.90 |
July | 0.195092E+10 | 0.34 | 1961.70 | 22-JUL-16:40 | 0.90 |
August | 0.209745E+10 | 0.36 | 1961.70 | 17-AUG-12:20 | 0.90 |
September | 0.194208E+10 | 0.34 | 1961.70 | 01-SEP-06:05 | 0.90 |
October | 0.200512E+10 | 0.42 | 1961.70 | 16-OCT-07:10 | 0.90 |
November | 0.216676E+10 | 0.64 | 1961.70 | 18-NOV-07:40 | 0.91 |
December | 0.250757E+10 | 0.77 | 1961.70 | 01-DEC-15:50 | 0.91 |
Annual Sum or Average | 0.255368E+11 | 0.50 | |||
Minimum of Months | 0.194208E+10 | 0.34 | 1961.70 | 0.90 | |
Maximum of Months | 0.250757E+10 | 0.77 | 1961.70 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.99 | 0.00 |
February | 2.78 | 0.00 |
March | 2.33 | 0.00 |
April | 0.90 | 1.05 |
May | 1.06 | 2.89 |
June | 2.72 | 2.85 |
July | 2.58 | 3.08 |
August | 2.44 | 3.73 |
September | 1.42 | 2.75 |
October | 0.83 | 1.45 |
November | 1.81 | 0.00 |
December | 2.95 | 0.00 |
Annual Sum or Average | 24.81 | 1.37 |
Minimum of Months | 0.83 | 0.00 |
Maximum of Months | 2.99 | 3.73 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.08 | 0.00 |
June | 0.17 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.25 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.17 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.105263E+10 | 0.867912E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.967151E+09 | 0.726137E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.113043E+10 | 0.736057E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.107854E+10 | 0.278259E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.114430E+10 | 0.199331E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.146878E+10 | 0.349787E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.179327E+10 | 93510847.80 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.196228E+10 | 40800797.51 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.139506E+10 | 0.443816E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.103884E+10 | 0.317126E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.100306E+10 | 0.622869E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.105261E+10 | 0.882640E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.150869E+11 | 0.472312E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.967151E+09 | 40800797.51 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.196228E+10 | 0.882640E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.234590E+10 | 0.204989E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.217110E+10 | 0.172554E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.233310E+10 | 0.104688E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.196425E+10 | 0.900252E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.203280E+10 | 0.527774E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.204896E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.212755E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.210962E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.194208E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.200512E+10 | 0.265730E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.216676E+10 | 0.141156E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.250757E+10 | 0.289757E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.257548E+11 | 0.953997E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.194208E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.250757E+10 | 0.289757E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.105263E+10 | 0.00 | 0.606294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.967151E+09 | 0.00 | 0.503786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113043E+10 | 0.00 | 0.509293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103426E+10 | 0.146804E+09 | 0.191989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106990E+10 | 0.246965E+09 | 0.136530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.105755E+10 | 0.137930E+10 | 0.235708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101644E+10 | 0.261709E+10 | 62567946.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109591E+10 | 0.292599E+10 | 26554681.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101668E+10 | 0.126483E+10 | 0.298840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.103485E+10 | 13069703.06 | 0.217885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100306E+10 | 0.00 | 0.430483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105261E+10 | 0.00 | 0.614312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125315E+11 | 0.859405E+10 | 0.327294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.967151E+09 | 0.00 | 26554681.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113043E+10 | 0.292599E+10 | 0.614312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.234590E+10 | 0.00 | 0.141586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217110E+10 | 0.00 | 0.119779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.233310E+10 | 0.00 | 0.713786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196425E+10 | 0.00 | 0.607512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.203280E+10 | 0.00 | 0.354085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.201976E+10 | 0.106032E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195092E+10 | 0.637815E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.209745E+10 | 43350360.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.194208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.200512E+10 | 0.00 | 0.179087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.216676E+10 | 0.00 | 0.976358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.250757E+10 | 0.00 | 0.201893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.255368E+11 | 0.787197E+09 | 0.659798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.194208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.250757E+10 | 0.637815E+09 | 0.201893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.105263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.867912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.967151E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103426E+10 | 0.00 | 0.00 | 0.00 | 44275706.82 | 0.00 | 0.278259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106990E+10 | 0.00 | 0.00 | 0.00 | 74402653.63 | 0.00 | 0.199331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.105755E+10 | 0.00 | 0.00 | 0.00 | 0.411228E+09 | 0.00 | 0.349787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101644E+10 | 0.00 | 0.00 | 0.00 | 0.776825E+09 | 0.00 | 93510847.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109591E+10 | 0.00 | 0.00 | 0.00 | 0.866371E+09 | 0.00 | 40800797.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101668E+10 | 0.00 | 0.00 | 0.00 | 0.378386E+09 | 0.00 | 0.443816E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.103485E+10 | 0.00 | 0.00 | 0.00 | 3991182.70 | 0.00 | 0.317126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125315E+11 | 0.00 | 0.00 | 0.00 | 0.255548E+10 | 0.00 | 0.472312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.967151E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40800797.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113043E+10 | 0.00 | 0.00 | 0.00 | 0.866371E+09 | 0.00 | 0.882640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.234590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.233310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900252E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.203280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527774E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.201976E+10 | 0.00 | 0.00 | 0.00 | 29199382.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195092E+10 | 0.00 | 0.00 | 0.00 | 0.176630E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.209745E+10 | 0.00 | 0.00 | 0.00 | 12172339.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.194208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.200512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.216676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.250757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.255368E+11 | 0.00 | 0.00 | 0.00 | 0.218002E+09 | 0.00 | 0.953997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.194208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.250757E+10 | 0.00 | 0.00 | 0.00 | 0.176630E+09 | 0.00 | 0.289757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 26154425.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245359E+10 | 0.00 | 0.00 | 0.16 |
February | 26258877.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213704E+10 | 0.00 | 0.00 | 0.17 |
March | 77973965.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225727E+10 | 0.00 | 0.00 | 0.18 |
April | 0.770653E+09 | 0.00 | 0.00 | 225389.51 | 435055.89 | 0.811509E+09 | 0.101626E+09 | 0.00 | 0.17 |
May | 0.965315E+09 | 117005.95 | 0.00 | 368914.78 | 0.00 | 0.515668E+09 | 0.173545E+09 | 0.00 | 0.17 |
June | 0.553565E+09 | 13810554.74 | 0.00 | 1803423.03 | 0.00 | 97046484.38 | 0.621377E+09 | 0.00 | 0.17 |
July | 0.236549E+09 | 21051549.55 | 0.00 | 3209247.00 | 0.00 | 31565014.98 | 0.664434E+09 | 0.00 | 0.16 |
August | 0.157847E+09 | 1135579.96 | 0.00 | 3959821.10 | 0.00 | 27172342.71 | 0.653492E+09 | 0.00 | 0.17 |
September | 0.424770E+09 | 146145.60 | 0.00 | 1771148.68 | 0.00 | 0.124987E+09 | 0.547505E+09 | 0.00 | 0.17 |
October | 0.608871E+09 | 0.00 | 0.00 | 20332.68 | 0.00 | 0.990259E+09 | 26763255.35 | 0.00 | 0.16 |
November | 94336286.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188798E+10 | 0.00 | 0.00 | 0.16 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243492E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.394229E+10 | 36260835.80 | 0.00 | 11358276.78 | 435055.89 | 0.137690E+11 | 0.278874E+10 | 0.00 | 0.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27172342.71 | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.965315E+09 | 21051549.55 | 0.00 | 3959821.10 | 435055.89 | 0.245359E+10 | 0.664434E+09 | 0.00 | 0.18 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.212415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193107E+10 | 0.00 | 0.00 | 0.14 |
February | 0.256314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.832523E+09 | 0.00 | 0.00 | 0.15 |
March | 0.322326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437713E+09 | 0.00 | 0.00 | 0.16 |
April | 0.311690E+10 | 0.00 | 0.00 | 0.00 | 6189903.02 | 2576760.04 | 0.00 | 0.00 | 0.15 |
May | 0.321143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2021223.54 | 0.00 | 0.00 | 0.15 |
June | 0.299918E+10 | 14268.95 | 0.00 | 259094.15 | 1354359.35 | 0.00 | 0.120793E+09 | 0.00 | 0.17 |
July | 0.232642E+10 | 8621426.20 | 0.00 | 1419582.62 | 1432522.77 | 0.00 | 0.746998E+09 | 0.00 | 0.18 |
August | 0.235531E+10 | 0.00 | 0.00 | 560678.35 | 0.00 | 0.00 | 0.557110E+09 | 0.00 | 0.18 |
September | 0.234414E+10 | 0.00 | 0.00 | 549.50 | 0.00 | 0.00 | 5024914.17 | 0.00 | 0.15 |
October | 0.249255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48692887.88 | 0.00 | 0.00 | 0.15 |
November | 0.231636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669703E+09 | 0.00 | 0.00 | 0.14 |
December | 0.146112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233168E+10 | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.305340E+11 | 8635695.15 | 0.00 | 2239904.62 | 8976785.14 | 0.625598E+10 | 0.142993E+10 | 0.00 | 0.16 |
Minimum of Months | 0.146112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.322326E+10 | 8621426.20 | 0.00 | 1419582.62 | 6189903.02 | 0.233168E+10 | 0.746998E+09 | 0.00 | 0.18 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |