Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2020-06-03 19:11:47
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2113.82 | 437.18 | 437.18 |
Net Site Energy | 2113.82 | 437.18 | 437.18 |
Total Source Energy | 4037.77 | 835.09 | 835.09 |
Net Source Energy | 4037.77 | 835.09 | 835.09 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1275.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 11.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 61.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.70 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 838.40 | 1275.42 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1275.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 11.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 1.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 60.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.70 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 123.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 20.63 | 263.78 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 173.40 | 263.78 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 123.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 20.63 | 263.78 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 173.40 | 263.78 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 838.402 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 838.402 | 100.00 |
Total On-Site and Utility Electric Sources | 838.402 | 100.00 |
Total Electricity End Uses | 838.402 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 66.00 |
Time Setpoint Not Met During Occupied Cooling | 0.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2239.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.6337 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.5069 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.5069 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-14:09 | 05-JAN-17:10 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 354041.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14463.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6317.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1774.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 67856.88 | 354041.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 354041.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 14463.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4011.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1774.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1382.55 | 0.00 | 0.00 | 0.00 |
Cooling | 35.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1507.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 390.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 195.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 84.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2655.22 | 1382.55 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 285.94 | 0.00 | 0.00 | 0.00 |
Cooling | 7.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 40.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 549.15 | 285.94 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 285.94 | 0.00 | 0.00 | 0.00 |
Cooling | 7.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 40.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 549.15 | 285.94 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.09 |
ZONE2 FINE STORAGE DIRECT AIR | 2.53 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 4.71 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 4.71 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 171176.92 |
PSZ-OFFICE HEATING COIL | 28082.48 |
PSZ-FINE STORAGE HEATING COIL | 81581.77 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 171176.91 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.00 | 1.00 | 1.09 |
PSZ-FINE STORAGE | 2.53 | 2.53 | 2.53 | 2.53 | 2.53 | 2.53 | 1.00 | 1.00 | 2.53 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.09 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 2.53 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.09 | 1.09 | 1.09 | 1.09 | 18066.54 | 28082.48 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.53 | 2.53 | 2.53 | 2.53 | 49086.12 | 81581.77 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.09 | 0.545700 | 1.09 | 18066.55 | 18066.54 | 9033.27 | 18066.54 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 2.53 | 1.26 | 2.53 | 43077.95 | 49086.12 | 24543.06 | 49086.12 | 0.744511 | 0.744510 | 0.744510 | 0.744510 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.09 | 1244.32 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.53 | 2767.57 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.634 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.707 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.507 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.507 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.507 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.066 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2518.900 | 10.634 | 503.780 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2518.900 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11853.648 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11853.648 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27263.390 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27263.390 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.3378 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.3378 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.3378 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.861 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.861 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.861 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
5 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
6 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
7 | 4 | 0.81105908E-12 | -0.61566660E-16 | 0.53970606E-14 | 0.11182789E-15 |
8 | 3 | -0.39455327E-03 | 0.24003309E-06 | -0.57329053E-04 | 0.15561420E-12 |
9 | 2 | 1.7627212 | 0.51935632E-02 | 1.1580856 | -0.75642783E-04 |
10 | 1 | -7.0983380 | 0.13367505 | -17.210522 | 0.33785533 |
11 | 0 | 5.5597362 | 0.84856002E-01 | 16.276219 | |
12 | 4 | 0.81105908E-12 | -0.61566660E-16 | 0.53970606E-14 | 0.11182789E-15 |
13 | 3 | -0.39455327E-03 | 0.24003309E-06 | -0.57329053E-04 | 0.15561420E-12 |
14 | 2 | 1.7627212 | 0.51935632E-02 | 1.1580856 | -0.75642783E-04 |
15 | 1 | -7.0983380 | 0.13367505 | -17.210522 | 0.33785533 |
16 | 0 | 5.5597362 | 0.84856002E-01 | 16.276219 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.8391346 | 2.8391346 | 2.8391346 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8391346 | 2.8391346 | 2.8391346 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.53970606E-14 | -0.61566660E-16 | 0.81105908E-12 | 0.11182789E-15 |
85 | 3 | -0.57329053E-04 | 0.24003309E-06 | -0.39455327E-03 | 0.15561420E-12 |
86 | 2 | 1.1580856 | 0.51935632E-02 | 1.7627212 | -0.75642783E-04 |
87 | 1 | -17.210522 | 0.13367505 | -7.0983380 | 0.33785533 |
88 | 0 | 16.276219 | 0.84856002E-01 | 5.5597362 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 28 | 1 | VerySmooth | 2.843 | 0.395 | 0.315 | 0.401 |
2 | SKYLIGHT_U_0.6_SHGC_0.4 | 29 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 30 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9669.16272 | 11602.99526 | 0.90950 | 1.09140 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.16000 | 6.26593E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 12285.25506 | 14742.30607 | 0.39449 | 0.47338 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60000 | 3.41898E-004 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 28740.13879 | 34488.16654 | 2.10717 | 2.52860 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40000 | 6.26594E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 57379.52325 | 68855.42790 | 1.55109 | 1.86131 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40000 | 6.26594E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 142647.42242 | 171176.90691 | 3.92615 | 4.71138 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -27.60000 | 3.41898E-004 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 14668.51 | 1.09140 | 1.09140 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 15688.68 | 0.47338 | 0.47338 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 41846.86 | 2.52860 | 2.52860 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 64317.71 | 1.86131 | 1.86131 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.09140 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.52860 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 4.71138 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 4.71138 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 171176.91662 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 171176.90691 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.09140 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.09140 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.09140 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.09140 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.09140 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.09140 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.52860 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.52860 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.52860 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.52860 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.52860 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.52860 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.09140 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.52860 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.09140 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.09140 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.09140 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.09140 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.09140 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.09140 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54570 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.09140 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18066.54527 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 18066.54000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9033.27000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 18066.54000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18066.54000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28082.48183 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.09140 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1244.31558 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28082.48183 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.52860 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.52860 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.52860 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.52860 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.52860 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.52860 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.26430 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.52860 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 43077.94768 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 49086.12000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 24543.06000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 49086.12000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74451 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74451 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74451 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74451 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 49086.12000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 81581.77036 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.52860 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2767.57135 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 81581.77036 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 17219.7 | 9.21 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 47122.9 | 13.40 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 12 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1810700046 | 0.1789434938 | Pass | Pass | 0.5180608656 | 1.1912989278 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.5903396207 | 0.5867788262 | Pass | Pass | 0.5189541983 | 0.7380272086 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 2.7898116569E-004 | 1.2706859866E-003 | Pass | Pass | 7.4651962466E-002 | 0.1291482085 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.322 | 0.338 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.322 | 0.338 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.322 | 0.338 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.369 | 0.389 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.102 | 0.395 | 0.401 | ||||||||||||
North Total or Average | 6.51 | 2.843 | 0.395 | 0.401 | ||||||||||||
Non-North Total or Average | 26.02 | 3.167 | 0.395 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.6337 | 236.88 | 2518.90 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.62 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.5069 | 1393.41 | 11853.65 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 135.00 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.5069 | 3204.84 | 27263.39 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 310.50 |
Interior Lighting Total | 8.6111 | 4835.13 | 41635.94 | 476.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.00 | AstronomicalClock | - | 83.57 | 83.57 | 123.25 | |
Exterior Lighting Total | 7857.00 | 123.25 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18066.54 | 14429.02 | 3637.52 | 0.80 | 3.15 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 49086.12 | 36545.11 | 12541.01 | 0.74 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 17219.7 | 9.21 | ||||
PSZ-FINE STORAGE COOLING COIL | 47122.9 | 13.40 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 171176.92 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28082.48 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 81581.77 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 4.71 | 437.74 | 92.91 | 1.00 | 3.18 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.09 | 1244.32 | 1140.11 | 1.00 | 1.34 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.53 | 2767.57 | 1094.51 | 1.00 | 1.25 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9669.16 | 11603.00 | 48.98 | 0.909 | 1.091 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00805 | 31.16 | 0.00627 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 28740.14 | 34488.17 | 24.75 | 2.107 | 2.529 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.70 | 0.00780 | 33.40 | 0.00627 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00432 | 33.40 | 0.00627 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12285.26 | 14742.31 | 62.24 | 0.394 | 0.473 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00761 | -27.60 | 0.00034 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 57379.52 | 68855.43 | 49.42 | 1.551 | 1.861 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.55 | 0.00621 | -27.60 | 0.00034 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 142647.42 | 171176.91 | 53.41 | 3.926 | 4.711 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 10.00 | 9.99 | 0.00873 | -27.60 | 0.00034 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.09 | 1.09 | 0.47 | 0.47 | 1.0914 | 1.0914 | 1.0914 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.53 | 2.53 | 1.86 | 1.86 | 2.5286 | 2.5286 | 2.5286 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 171176.917 | 171176.917 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 171176.92 | 171176.92 | 4.711378 | 3.49 | 3.49 | 0.00728367 | 43.33 | 25.35 | 0.01600000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 9.99 | 0.00873359 | 100.0000 | 171176.91 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 18066.540 | 0.000 | 1.091400 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 18066.54 | 18066.54 | 1.091400 | 24.70 | 14.70 | 0.00785095 | 12.00 | 10.08 | 0.00800000 | 31.16 | 0.00626593 | 15.56 | 11.0258 | 23.90 | 0.00804737 | 38.1427 | 9669.16 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28082.482 | 28082.482 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 28082.48 | 28082.48 | 1.091400 | 8.68 | 6.25 | 0.00575923 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 11.0258 | 21.10 | 0.00760571 | 42.7699 | 12285.26 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 49086.120 | 0.000 | 2.528600 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 49086.12 | 49086.12 | 2.528600 | 27.64 | 15.47 | 0.00758331 | 12.00 | 10.08 | 0.00800000 | 33.40 | 0.00626594 | 16.30 | 13.9970 | 26.70 | 0.00779772 | 31.3001 | 28740.14 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 81581.770 | 81581.770 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 81581.77 | 81581.77 | 2.528604 | 7.35 | 4.84 | 0.00509596 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 13.9969 | 15.55 | 0.00621220 | 49.5946 | 57379.52 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 171176.917 | 171176.917 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.0531 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 4.711378 | 4.96173973 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 171176.92 | 171176.92 | 1.0000 | 4.96173973 | 4.711378 | 3.49 | 3.49 | 0.00728367 | 21773.1 | 43.33 | 25.35 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 171176.92 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 9.99 | 0.00873359 | 9.99 | 0.00873359 | 100.0000 | 171176.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18066.540 | 0.000 | 1.091400 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4345 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 18066.54 | 18066.54 | 1.0000 | 1.14939687 | 1.091400 | 24.70 | 14.70 | 0.00785095 | 44815.0 | 12.00 | 10.08 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18066.54 | 31.16 | 0.00626593 | 15.56 | 0.12033533 | 11.0258 | 23.90 | 0.00804737 | 23.90 | 0.00804737 | 38.1427 | 9669.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28082.482 | 28082.482 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.091400 | 1.14939654 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 28082.48 | 28082.48 | 1.0000 | 1.14939654 | 1.091400 | 8.68 | 6.25 | 0.00575923 | 23221.4 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28082.48 | -27.60 | 0.00034190 | -27.60 | 0.12033533 | 11.0258 | 21.05 | 0.00760571 | 21.10 | 0.00760571 | 42.7699 | 12285.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 49086.120 | 0.000 | 2.528600 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.9370 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 49086.12 | 49086.12 | 1.0000 | 2.66296950 | 2.528600 | 27.64 | 15.47 | 0.00758331 | 47127.1 | 12.00 | 10.08 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 49086.12 | 33.40 | 0.00626594 | 16.30 | 0.35392745 | 13.9970 | 26.70 | 0.00779772 | 26.70 | 0.00779772 | 31.3001 | 28740.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 81581.770 | 81581.770 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.528604 | 2.66297407 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 81581.77 | 81581.77 | 1.0000 | 2.66297407 | 2.528604 | 7.35 | 4.84 | 0.00509596 | 20197.0 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 81581.77 | -27.60 | 0.00034190 | -27.60 | 0.35392745 | 13.9969 | 15.55 | 0.00621220 | 15.55 | 0.00621220 | 49.5946 | 57379.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE OA CONTROLLER | DifferentialDryBulb | 0.12 | 1.09 | - | |||
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.35 | 2.53 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2516.33 | 3037.00 | 2239.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2516.33 | 3037.00 | 2239.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 131.67 | 0.67 | 66.00 | 0.67 |
ZONE2 FINE STORAGE | 646.33 | 15.67 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5.17 | 0.00 | 0.00 | 0.00 |
Facility | 738.00 | 16.33 | 66.00 | 0.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.646 | 0.436 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 838.40 | 5421.86 | 01-JAN-14:00 | 67856.88 | 17-JUL-14:10 |
Electricity:Building | 616.81 | 4938.86 | 01-JAN-00:10 | 47606.95 | 14-JUL-13:40 |
Electricity:Zone:ZONE1 OFFICE | 62.57 | 1027.15 | 01-JAN-00:10 | 3852.05 | 02-JAN-08:10 |
InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.62 | 453.40 | 01-JAN-00:10 | 1939.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 419.24 | 2726.34 | 01-JAN-00:10 | 33679.30 | 14-JUL-13:40 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 310.51 | 2726.34 | 01-JAN-00:10 | 23173.88 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 26.70 | 483.00 | 06-JAN-22:00 | 2853.98 | 17-FEB-12:50 |
WaterSystems:Electricity | 26.70 | 483.00 | 06-JAN-22:00 | 2853.98 | 17-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 26.70 | 483.00 | 06-JAN-22:00 | 2853.98 | 17-FEB-12:50 |
Fans:Electricity | 61.76 | 0.00 | 01-JAN-14:00 | 6317.18 | 17-JUL-16:30 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 1.40 | 0.00 | 01-JAN-00:10 | 2305.29 | 15-JUL-17:20 |
Ventilation (simple):Fans:Electricity | 1.40 | 0.00 | 01-JAN-00:10 | 2305.29 | 15-JUL-17:20 |
ElectricityPurchased:Facility | 838.40 | 5421.86 | 01-JAN-14:00 | 67856.88 | 17-JUL-14:10 |
ElectricityPurchased:Plant | 838.40 | 5421.86 | 01-JAN-14:00 | 67856.88 | 17-JUL-14:10 |
Cogeneration:ElectricityPurchased | 838.40 | 5421.86 | 01-JAN-14:00 | 67856.88 | 17-JUL-14:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 838.40 | 5421.86 | 01-JAN-14:00 | 67856.88 | 17-JUL-14:10 |
ElectricityNet:Plant | 838.40 | 5421.86 | 01-JAN-14:00 | 67856.88 | 17-JUL-14:10 |
Cogeneration:ElectricityNet | 838.40 | 5421.86 | 01-JAN-14:00 | 67856.88 | 17-JUL-14:10 |
Electricity:HVAC | 71.64 | 0.00 | 01-JAN-14:00 | 20977.55 | 17-JUL-16:10 |
General:Fans:Electricity | 60.36 | 0.00 | 01-JAN-14:00 | 4449.62 | 12-DEC-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 11.28 | 0.00 | 01-JAN-00:10 | 16965.66 | 17-JUL-16:10 |
ExteriorLights:Electricity | 123.25 | 0.00 | 01-JAN-08:20 | 7857.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.25 | 0.00 | 01-JAN-08:20 | 7857.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1275.42 | 6500.00 | 25-JUN-13:40 | 354041.51 | 05-JAN-17:10 |
Gas:HVAC | 1275.42 | 6500.00 | 25-JUN-13:40 | 354041.51 | 05-JAN-17:10 |
Heating:Gas | 1275.42 | 6500.00 | 25-JUN-13:40 | 354041.51 | 05-JAN-17:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1716.79 | 0.00 | 01-JAN-14:00 | 546784.85 | 05-JAN-17:50 |
EnergyTransfer:Building | 855.86 | 0.00 | 01-JAN-14:00 | 267213.70 | 06-JAN-07:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 61.51 | 0.00 | 01-JAN-00:10 | 29519.93 | 09-JAN-07:10 |
Heating:EnergyTransfer | 819.12 | 0.00 | 01-JAN-14:00 | 267213.70 | 06-JAN-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 47.80 | 0.00 | 01-JAN-00:10 | 29519.93 | 09-JAN-07:10 |
Cooling:EnergyTransfer | 36.74 | 0.00 | 01-JAN-00:10 | 39262.26 | 17-JUL-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 13.71 | 0.00 | 01-JAN-00:10 | 11323.79 | 17-JUL-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 270.26 | 0.00 | 01-JAN-00:40 | 80810.92 | 05-JAN-19:40 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 247.23 | 0.00 | 01-JAN-00:40 | 80810.92 | 05-JAN-19:40 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 23.03 | 0.00 | 01-JAN-00:10 | 29444.86 | 17-JUL-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 524.09 | 0.00 | 01-JAN-13:30 | 173079.95 | 05-JAN-15:30 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 524.09 | 0.00 | 01-JAN-13:30 | 173079.95 | 05-JAN-15:30 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 860.93 | 0.00 | 01-JAN-13:20 | 280841.17 | 05-JAN-17:10 |
HeatingCoils:EnergyTransfer | 824.74 | 0.00 | 01-JAN-13:20 | 280841.17 | 05-JAN-17:10 |
CoolingCoils:EnergyTransfer | 36.19 | 0.00 | 01-JAN-00:10 | 48864.88 | 17-JUL-16:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 47.798 | -13.710 | 0.000 | 0.000 | 3.994 | 30.619 | 31.946 | 9.616 | 0.000 | 0.724 | 0.000 | 0.000 | -13.065 | 0.000 | -33.366 | -64.557 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 247.225 | -23.030 | 0.000 | 0.000 | 0.000 | 135.003 | 0.000 | 0.000 | 0.000 | 2.283 | 0.001 | 0.000 | 0.000 | 0.000 | -214.150 | -147.331 |
ZONE3 BULK STORAGE | 524.092 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 310.507 | 107.336 | 18.566 | 0.000 | 27.265 | 0.000 | 0.000 | -12.135 | 0.000 | -700.502 | -275.129 |
Total Facility | 524.092 | 0.000 | 295.023 | -36.740 | 0.000 | 0.000 | 3.994 | 476.129 | 139.282 | 28.183 | 0.000 | 30.272 | 0.001 | 0.000 | -25.200 | 0.000 | -948.018 | -487.016 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 12-AUG-05:01 | 0.00 | 0.00 | 0.00 | -24900.54 | 0.00 | 0.00 | 32.58 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 24513.27 | 0.00 | -599.04 | 0.00 | -199.37 | 0.00 |
ZONE2 FINE STORAGE | 25-JUN-13:11 | 0.00 | 0.00 | 0.00 | -49981.72 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 50205.54 | 0.00 | -0.00 | 0.00 | -1409.18 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-JUN-13:11 | 0.00 | 0.00 | 0.00 | -49981.72 | 0.00 | 0.00 | 0.00 | 4365.11 | 573.75 | 4659.88 | 0.00 | 0.00 | 46120.97 | 0.00 | 0.00 | 0.00 | -5737.98 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 09-JAN-06:31 | 0.00 | 0.00 | 31086.35 | 0.00 | 0.00 | 0.00 | 58.32 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1638.51 | 0.00 | -3359.03 | -27300.22 |
ZONE2 FINE STORAGE | 06-JAN-06:01 | 0.00 | 0.00 | 88340.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -25826.60 | -63698.85 |
ZONE3 BULK STORAGE | 05-JAN-15:45 | 173298.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 12429.22 | 0.00 | -966.05 | 0.00 | -216135.46 | 0.00 |
Total Facility | 06-JAN-06:42 | 170027.44 | 0.00 | 109871.82 | 0.00 | 0.00 | 0.00 | 46.49 | 4491.05 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3304.14 | 0.00 | -154739.07 | -129017.37 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0914 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.0914 | 0.1103 | 1.0000 | 0.1203 | 0.1103 | ||
PSZ-FINE STORAGE | 2.5286 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.5286 | 0.1400 | 1.0000 | 0.3539 | 0.1400 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0914 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.0914 | 1.0000 | 1.0000 | 0.1203 | 0.1103 | ||
PSZ-FINE STORAGE | 2.5286 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.5286 | 1.0000 | 1.0000 | 0.3539 | 0.1400 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0914 | 1.0914 | 1.0914 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.5286 | 2.5286 | 2.5286 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0914 | 1.0914 | 1.0914 | 1.0914 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.5286 | 2.5286 | 2.5286 | 2.5286 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.0914 | 1.0914 | 1.0914 | 0.1203 | 0.2542 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.5286 | 2.5286 | 2.5286 | 0.3539 | 0.1901 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0914 | 1.0914 | 1.0914 | 1.0914 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.5286 | 2.5286 | 2.5286 | 2.5286 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:47
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 66.00 |
Number of hours cooling loads not met | 0.67 |
Number of hours not met | 66.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 1275.42 | 354041.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 11.28 | 16965.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 476.13 | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.25 | 7857.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 1.40 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 60.36 | 4449.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.70 | 2853.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 838.40 |
Natural Gas | 0.00 | 1275.42 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 2113.82 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 98.47 |
Space Heating | 0.00 |
Space Cooling | 2.33 |
Fans (All) | 12.77 |
Service Water Heating | 5.52 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 173.40 |
Subtotal | 173.40 |
Natural Gas [MJ/m2] | |
Space Heating | 263.78 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 263.78 |
Subtotal | 263.78 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 22.52 |
Space Heating | 60.34 |
Space Cooling | 0.53 |
Fans (All) | 2.92 |
Service Water Heating | 1.26 |
Receptacle Equipment | 6.59 |
Miscellaneous | 5.83 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.357802E+12 |
February | 0.000 | 0.204750E+12 |
March | 0.000 | 0.152356E+12 |
April | 0.000 | 0.487803E+11 |
May | 0.000 | 0.392333E+11 |
June | 0.000 | 0.170550E+11 |
July | 0.000 | 0.174096E+11 |
August | 0.000 | 0.174459E+11 |
September | 0.000 | 0.196655E+11 |
October | 0.000 | 0.299487E+11 |
November | 0.000 | 0.120286E+12 |
December | 0.000 | 0.250686E+12 |
Annual Sum or Average | 0.127542E+13 | |
Minimum of Months | 0.000 | 0.170550E+11 |
Maximum of Months | 0.000 | 0.357802E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.357802E+12 |
February | 0.000 | 0.204750E+12 |
March | 0.000 | 0.152356E+12 |
April | 0.000 | 0.487803E+11 |
May | 0.000 | 0.392333E+11 |
June | 0.000 | 0.170550E+11 |
July | 0.000 | 0.174096E+11 |
August | 0.000 | 0.174459E+11 |
September | 0.000 | 0.196655E+11 |
October | 0.000 | 0.299487E+11 |
November | 0.000 | 0.120286E+12 |
December | 0.000 | 0.250686E+12 |
Annual Sum or Average | 0.127542E+13 | |
Minimum of Months | 0.000 | 0.170550E+11 |
Maximum of Months | 0.000 | 0.357802E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.357802E+12 |
February | 0.000 | 0.204750E+12 |
March | 0.000 | 0.152356E+12 |
April | 0.000 | 0.487803E+11 |
May | 0.000 | 0.392333E+11 |
June | 0.000 | 0.170550E+11 |
July | 0.000 | 0.174096E+11 |
August | 0.000 | 0.174459E+11 |
September | 0.000 | 0.196655E+11 |
October | 0.000 | 0.299487E+11 |
November | 0.000 | 0.120286E+12 |
December | 0.000 | 0.250686E+12 |
Annual Sum or Average | 0.127542E+13 | |
Minimum of Months | 0.000 | 0.170550E+11 |
Maximum of Months | 0.000 | 0.357802E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.357802E+12 |
February | 0.000 | 0.204750E+12 |
March | 0.000 | 0.152356E+12 |
April | 0.000 | 0.487803E+11 |
May | 0.000 | 0.392333E+11 |
June | 0.000 | 0.170550E+11 |
July | 0.000 | 0.174096E+11 |
August | 0.000 | 0.174459E+11 |
September | 0.000 | 0.196655E+11 |
October | 0.000 | 0.299487E+11 |
November | 0.000 | 0.120286E+12 |
December | 0.000 | 0.250686E+12 |
Annual Sum or Average | 0.127542E+13 | |
Minimum of Months | 0.000 | 0.170550E+11 |
Maximum of Months | 0.000 | 0.357802E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.357802E+12 |
February | 0.000 | 0.204750E+12 |
March | 0.000 | 0.152356E+12 |
April | 0.000 | 0.487803E+11 |
May | 0.000 | 0.392333E+11 |
June | 0.000 | 0.170550E+11 |
July | 0.000 | 0.174096E+11 |
August | 0.000 | 0.174459E+11 |
September | 0.000 | 0.196655E+11 |
October | 0.000 | 0.299487E+11 |
November | 0.000 | 0.120286E+12 |
December | 0.000 | 0.250686E+12 |
Annual Sum or Average | 0.127542E+13 | |
Minimum of Months | 0.000 | 0.170550E+11 |
Maximum of Months | 0.000 | 0.357802E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.357802E+12 |
February | 0.000 | 0.204750E+12 |
March | 0.000 | 0.152356E+12 |
April | 0.000 | 0.487803E+11 |
May | 0.000 | 0.392333E+11 |
June | 0.000 | 0.170550E+11 |
July | 0.000 | 0.174096E+11 |
August | 0.000 | 0.174459E+11 |
September | 0.000 | 0.196655E+11 |
October | 0.000 | 0.299487E+11 |
November | 0.000 | 0.120286E+12 |
December | 0.000 | 0.250686E+12 |
Annual Sum or Average | 0.127542E+13 | |
Minimum of Months | 0.000 | 0.170550E+11 |
Maximum of Months | 0.000 | 0.357802E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.357802E+12 |
February | 0.000 | 0.204750E+12 |
March | 0.000 | 0.152356E+12 |
April | 0.000 | 0.487803E+11 |
May | 0.000 | 0.392333E+11 |
June | 0.000 | 0.170550E+11 |
July | 0.000 | 0.174096E+11 |
August | 0.000 | 0.174459E+11 |
September | 0.000 | 0.196655E+11 |
October | 0.000 | 0.299487E+11 |
November | 0.000 | 0.120286E+12 |
December | 0.000 | 0.250686E+12 |
Annual Sum or Average | 0.127542E+13 | |
Minimum of Months | 0.000 | 0.170550E+11 |
Maximum of Months | 0.000 | 0.357802E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.357802E+12 |
February | 0.000 | 0.204750E+12 |
March | 0.000 | 0.152356E+12 |
April | 0.000 | 0.487803E+11 |
May | 0.000 | 0.392333E+11 |
June | 0.000 | 0.170550E+11 |
July | 0.000 | 0.174096E+11 |
August | 0.000 | 0.174459E+11 |
September | 0.000 | 0.196655E+11 |
October | 0.000 | 0.299487E+11 |
November | 0.000 | 0.120286E+12 |
December | 0.000 | 0.250686E+12 |
Annual Sum or Average | 0.127542E+13 | |
Minimum of Months | 0.000 | 0.170550E+11 |
Maximum of Months | 0.000 | 0.357802E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.357802E+12 |
February | 0.000 | 0.204750E+12 |
March | 0.000 | 0.152356E+12 |
April | 0.000 | 0.487803E+11 |
May | 0.000 | 0.392333E+11 |
June | 0.000 | 0.170550E+11 |
July | 0.000 | 0.174096E+11 |
August | 0.000 | 0.174459E+11 |
September | 0.000 | 0.196655E+11 |
October | 0.000 | 0.299487E+11 |
November | 0.000 | 0.120286E+12 |
December | 0.000 | 0.250686E+12 |
Annual Sum or Average | 0.127542E+13 | |
Minimum of Months | 0.000 | 0.170550E+11 |
Maximum of Months | 0.000 | 0.357802E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.38 | -1.1 | 0.194876E+09 | 236.59 | 11-JAN-09:20 | -8.5 | -9.8 |
February | 663158.39 | 123.52 | 28-FEB-16:50 | 10.18 | 4.38 | 0.179663E+09 | 265.79 | 27-FEB-16:10 | 17.78 | 6.89 |
March | 746482.22 | 128.77 | 02-MAR-16:00 | 10.60 | 4.72 | 0.210566E+09 | 240.07 | 18-MAR-15:09 | 12.12 | 4.17 |
April | 4845872.76 | 238.10 | 26-APR-16:00 | 9.40 | 4.23 | 0.199793E+09 | 301.59 | 07-APR-15:20 | 21.50 | 8.81 |
May | 0.325402E+09 | 3982.07 | 19-MAY-16:00 | 27.80 | 14.51 | 0.221672E+09 | 301.59 | 20-MAY-10:20 | 21.47 | 13.26 |
June | 0.242627E+10 | 21091.91 | 26-JUN-05:03 | 9.87 | 8.82 | 0.252154E+09 | 301.62 | 20-JUN-10:50 | 23.43 | 14.99 |
July | 0.481817E+10 | 23189.90 | 22-JUL-05:03 | 8.77 | 7.16 | 0.248490E+09 | 301.62 | 03-JUL-12:30 | 21.20 | 14.36 |
August | 0.424716E+10 | 24900.72 | 12-AUG-05:01 | 13.07 | 6.76 | 0.266778E+09 | 301.62 | 01-AUG-12:00 | 22.20 | 14.62 |
September | 0.176670E+10 | 21719.02 | 02-SEP-05:03 | 14.40 | 8.77 | 0.232427E+09 | 301.61 | 07-SEP-10:50 | 17.62 | 16.50 |
October | 0.112085E+09 | 2357.71 | 18-OCT-16:00 | 24.40 | 10.99 | 0.210257E+09 | 301.59 | 16-OCT-13:39 | 21.10 | 9.67 |
November | 8003263.77 | 386.11 | 09-NOV-15:30 | 8.85 | 3.68 | 0.188459E+09 | 282.27 | 04-NOV-15:09 | 16.60 | 7.87 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -2.1 | -4.1 | 0.194941E+09 | 236.59 | 14-DEC-11:09 | -6.2 | -6.7 |
Annual Sum or Average | 0.137101E+11 | 0.260008E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.1 | -4.1 | 0.179663E+09 | 236.59 | -8.5 | -9.8 | ||
Maximum of Months | 0.481817E+10 | 24900.72 | 27.80 | 14.51 | 0.266778E+09 | 301.62 | 23.43 | 16.50 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1949762.44 | 535.49 | 02-JAN-14:20 | 6.50 | 1.41 | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 | -1.1 |
February | 81231236.84 | 2818.45 | 23-FEB-15:40 | -1.0 | -3.7 | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 | -13.8 |
March | 0.334024E+09 | 3649.99 | 25-MAR-11:00 | -0.6 | -2.6 | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.0 |
April | 0.279759E+09 | 2473.60 | 29-APR-13:00 | 3.30 | -1.9 | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.54 |
May | 0.421291E+09 | 7470.96 | 13-MAY-06:10 | 8.45 | 4.49 | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -2.9 |
June | 0.281238E+10 | 49982.77 | 25-JUN-13:11 | 23.33 | 13.12 | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.35 |
July | 0.924079E+10 | 48586.19 | 23-JUL-12:31 | 24.40 | 13.75 | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.31 |
August | 0.673857E+10 | 45299.45 | 10-AUG-20:01 | 24.95 | 10.61 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.94 |
September | 0.241307E+10 | 41344.59 | 04-SEP-13:43 | 30.18 | 15.72 | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.58 |
October | 0.416826E+09 | 4157.03 | 13-OCT-06:10 | 12.12 | 6.47 | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.93 |
November | 0.257347E+09 | 2630.81 | 06-NOV-09:40 | 1.20 | -0.9 | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.53 |
December | 33985928.18 | 2025.65 | 21-DEC-14:00 | 1.70 | -2.7 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.1 |
Annual Sum or Average | 0.230312E+11 | 0.00 | ||||||||
Minimum of Months | 1949762.44 | 535.49 | -1.0 | -3.7 | 0.00 | 0.00 | -12.4 | -13.8 | ||
Maximum of Months | 0.924079E+10 | 49982.77 | 30.18 | 15.72 | 0.00 | 0.00 | 19.45 | 13.31 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.38 | -1.1 | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 | -1.1 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -12.4 | -13.8 | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 | -13.8 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -3.0 | -4.0 | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.54 | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.54 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 | -2.9 | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -2.9 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.35 | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.31 | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.31 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.94 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.94 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.58 | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.58 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.93 | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.53 | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.53 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -2.1 | -4.1 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.1 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -12.4 | -13.8 | 0.00 | 0.00 | -12.4 | -13.8 | ||
Maximum of Months | 0.00 | 0.00 | 19.45 | 13.31 | 0.00 | 0.00 | 19.45 | 13.31 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113985E+11 | 31086.26 | 09-JAN-06:31 | -27.2 |
February | 0.758406E+10 | 28849.12 | 02-FEB-06:31 | -13.5 |
March | 0.678860E+10 | 30203.46 | 03-MAR-06:31 | -12.8 |
April | 0.358587E+10 | 28555.40 | 29-APR-05:22 | -7.5 |
May | 0.242498E+10 | 29183.18 | 22-MAY-05:42 | -0.6 |
June | 0.249087E+09 | 28132.77 | 17-JUN-05:01 | 2.35 |
July | 49712511.89 | 2035.67 | 18-JUL-06:05 | 20.15 |
August | 0.109405E+09 | 8852.67 | 18-AUG-05:03 | 7.30 |
September | 0.749133E+09 | 28390.50 | 19-SEP-05:01 | 2.20 |
October | 0.195647E+10 | 28578.98 | 10-OCT-05:12 | -6.1 |
November | 0.475379E+10 | 28650.82 | 13-NOV-06:22 | -5.8 |
December | 0.814879E+10 | 30596.82 | 28-DEC-06:31 | -22.8 |
Annual Sum or Average | 0.477984E+11 | |||
Minimum of Months | 49712511.89 | 2035.67 | -27.2 | |
Maximum of Months | 0.113985E+11 | 31086.26 | 20.15 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.668388E+11 | 88340.08 | 06-JAN-06:01 | -25.1 |
February | 0.404124E+11 | 84521.39 | 10-FEB-20:02 | -12.9 |
March | 0.320390E+11 | 87361.66 | 06-MAR-06:01 | -16.3 |
April | 0.129731E+11 | 84872.50 | 29-APR-05:41 | -7.3 |
May | 0.813304E+10 | 84559.48 | 07-MAY-23:12 | -2.4 |
June | 0.515532E+09 | 2986.92 | 01-JUN-07:00 | 11.70 |
July | 0.244171E+09 | 2657.90 | 08-JUL-07:00 | 11.70 |
August | 0.393011E+09 | 2681.68 | 01-AUG-07:00 | 14.40 |
September | 0.202519E+10 | 81910.29 | 20-SEP-05:53 | 3.30 |
October | 0.686009E+10 | 83362.49 | 11-OCT-05:52 | 0.00 |
November | 0.272358E+11 | 87243.01 | 27-NOV-06:01 | -14.5 |
December | 0.495554E+11 | 85448.65 | 01-DEC-00:41 | -1.5 |
Annual Sum or Average | 0.247225E+12 | |||
Minimum of Months | 0.244171E+09 | 2657.90 | -25.1 | |
Maximum of Months | 0.668388E+11 | 88340.08 | 14.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.183655E+12 | 173299.93 | 05-JAN-15:45 | -19.2 |
February | 0.961106E+11 | 124813.23 | 03-FEB-19:00 | -16.7 |
March | 0.636362E+11 | 128555.91 | 04-MAR-02:00 | -18.3 |
April | 0.677920E+10 | 59409.05 | 29-APR-04:51 | -7.8 |
May | 0.624468E+10 | 54593.47 | 08-MAY-05:52 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 0.580655E+09 | 22495.37 | 11-OCT-05:56 | 0.00 |
November | 0.467555E+11 | 113267.64 | 27-NOV-04:57 | -15.6 |
December | 0.120331E+12 | 171809.50 | 31-DEC-03:03 | -24.5 |
Annual Sum or Average | 0.524092E+12 | |||
Minimum of Months | 0.00 | 0.00 | -24.5 | |
Maximum of Months | 0.183655E+12 | 173299.93 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.256100E+10 | 1939.55 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.233575E+10 | 1939.55 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.266872E+10 | 1939.55 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.252182E+10 | 1939.55 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.261486E+10 | 1939.55 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.257569E+10 | 1939.55 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.256100E+10 | 1939.55 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.266872E+10 | 1939.55 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.252182E+10 | 1939.55 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.256100E+10 | 1939.55 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.246796E+10 | 1939.55 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.256100E+10 | 1939.55 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.306193E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.233575E+10 | 1939.55 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.266872E+10 | 1939.55 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112294E+11 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102778E+11 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.118738E+11 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.111270E+11 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.115516E+11 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.114492E+11 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112294E+11 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.118738E+11 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.111270E+11 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112294E+11 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108048E+11 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112294E+11 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135003E+12 | ||||
Minimum of Months | 0.102778E+11 | 10075.60 | 0.00 | 0.00 | |
Maximum of Months | 0.118738E+11 | 10075.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.258277E+11 | 23173.88 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.236390E+11 | 23173.88 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.273097E+11 | 23173.88 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.255921E+11 | 23173.88 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.265687E+11 | 23173.88 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.263332E+11 | 23173.88 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.258277E+11 | 23173.88 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.273097E+11 | 23173.88 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.255921E+11 | 23173.88 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.258277E+11 | 23173.88 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.248511E+11 | 23173.88 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.258277E+11 | 23173.88 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.236390E+11 | 23173.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.273097E+11 | 23173.88 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586708E+10 |
February | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417940E+10 |
March | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388111E+10 |
April | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 495516.14 | 0.238609E+10 |
May | 0.565842E+09 | 0.261486E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14873744.91 | 0.229377E+10 |
June | 0.565842E+09 | 0.257569E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125805E+09 | 0.125326E+10 |
July | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302674E+09 | 0.702145E+09 |
August | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226562E+09 | 0.101438E+10 |
September | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50346588.30 | 0.165225E+10 |
October | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2809784.90 | 0.224399E+10 |
November | 0.522316E+09 | 0.246796E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334265E+10 |
December | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455010E+10 |
Annual Sum or Average | 0.659424E+10 | 0.306193E+11 | 0.319458E+11 | 0.723566E+09 | 0.333662E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702145E+09 |
Maximum of Months | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302674E+09 | 0.586708E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383092E+11 |
February | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267900E+11 |
March | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239566E+11 |
April | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12938431.16 | 0.139115E+11 |
May | 0.00 | 0.115516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71139986.33 | 0.137212E+11 |
June | 0.00 | 0.114492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255581E+09 | 0.895198E+10 |
July | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808902E+09 | 0.662999E+10 |
August | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730140E+09 | 0.766797E+10 |
September | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346061E+09 | 0.108120E+11 |
October | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58241377.30 | 0.124739E+11 |
November | 0.00 | 0.108048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210145E+11 |
December | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299104E+11 |
Annual Sum or Average | 0.135003E+12 | 0.228300E+10 | 0.214150E+12 | ||||||
Minimum of Months | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662999E+10 |
Maximum of Months | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808902E+09 | 0.383092E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100120E+12 |
February | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699368E+09 | 0.586521E+11 |
March | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72158478.65 | 0.519917E+11 |
April | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228233E+10 | 0.265264E+11 |
May | 0.00 | 0.265687E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311859E+10 | 0.274966E+11 |
June | 0.00 | 0.263332E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112949E+10 | 0.246184E+11 |
July | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487007E+09 | 0.257759E+11 |
August | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405147E+09 | 0.300349E+11 |
September | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165638E+10 | 0.343561E+11 |
October | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239951E+10 | 0.287713E+11 |
November | 0.00 | 0.248511E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128603E+10 | 0.433428E+11 |
December | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219092E+09 | 0.686627E+11 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | 0.137551E+11 | 0.520349E+12 | |||||
Minimum of Months | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246184E+11 |
Maximum of Months | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311859E+10 | 0.100120E+12 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1939.55 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 19924.89 | 27-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1939.55 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 17452.51 | 01-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1939.55 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 15690.49 | 06-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1939.55 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.61 | 16-APR-14:00 | 8838.06 | 28-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1939.55 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1518.83 | 19-MAY-16:10 | 10476.71 | 22-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1939.55 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2562.10 | 29-JUN-16:10 | 6786.10 | 16-JUN-07:00 |
July | 659.25 | 01-JUL-07:10 | 1939.55 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4342.04 | 17-JUL-16:10 | 4705.59 | 05-JUL-06:03 |
August | 659.25 | 01-AUG-07:10 | 1939.55 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2950.94 | 10-AUG-17:00 | 5606.88 | 17-AUG-11:03 |
September | 659.25 | 01-SEP-07:10 | 1939.55 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1590.98 | 01-SEP-16:10 | 7184.00 | 19-SEP-06:10 |
October | 659.25 | 02-OCT-07:10 | 1939.55 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.47 | 15-OCT-14:00 | 10397.70 | 10-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1939.55 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13756.63 | 27-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1939.55 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 17880.28 | 29-DEC-08:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4705.59 | |||||
Maximum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4342.04 | 19924.89 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 70153.74 | 05-JAN-16:05 |
February | 0.00 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 37807.40 | 01-FEB-17:00 |
March | 0.00 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 32889.45 | 30-MAR-08:00 |
April | 0.00 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 704.05 | 07-APR-14:00 | 23846.50 | 28-APR-16:00 |
May | 0.00 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3355.27 | 20-MAY-16:00 | 43867.17 | 22-MAY-06:10 |
June | 0.00 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.93 | 29-JUN-15:10 | 18333.89 | 06-JUN-16:53 |
July | 0.00 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8825.49 | 25-JUL-15:10 | 12061.19 | 08-JUL-07:00 |
August | 0.00 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7596.83 | 09-AUG-17:00 | 24046.81 | 17-AUG-15:03 |
September | 0.00 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8172.99 | 02-SEP-15:10 | 21991.53 | 18-SEP-16:00 |
October | 0.00 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3185.26 | 15-OCT-14:00 | 19527.00 | 31-OCT-16:00 |
November | 0.00 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 32367.05 | 28-NOV-08:00 |
December | 0.00 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 36965.91 | 31-DEC-03:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12061.19 | |||
Maximum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8825.49 | 70153.74 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23173.88 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 174547.57 | 05-JAN-15:55 |
February | 0.00 | 23173.88 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13171.25 | 27-FEB-13:10 | 97811.92 | 01-FEB-15:00 |
March | 0.00 | 23173.88 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6410.56 | 14-MAR-12:10 | 79121.33 | 03-MAR-09:00 |
April | 0.00 | 23173.88 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25216.79 | 07-APR-12:10 | 55635.53 | 27-APR-11:00 |
May | 0.00 | 23173.88 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31819.41 | 19-MAY-16:00 | 86850.05 | 22-MAY-08:00 |
June | 0.00 | 23173.88 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14590.62 | 29-JUN-13:00 | 46544.12 | 14-JUN-08:00 |
July | 0.00 | 23173.88 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10167.47 | 13-JUL-16:00 | 39370.89 | 08-JUL-10:00 |
August | 0.00 | 23173.88 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9174.01 | 25-AUG-16:00 | 84225.91 | 17-AUG-12:05 |
September | 0.00 | 23173.88 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16959.74 | 23-SEP-14:00 | 66248.72 | 12-SEP-11:00 |
October | 0.00 | 23173.88 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25764.13 | 12-OCT-12:10 | 41396.40 | 03-OCT-09:00 |
November | 0.00 | 23173.88 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15008.99 | 17-NOV-17:00 | 73054.46 | 27-NOV-11:00 |
December | 0.00 | 23173.88 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13611.85 | 10-DEC-01:55 | 127307.25 | 27-DEC-14:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39370.89 | ||||
Maximum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 31819.41 | 174547.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1813.61 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.05 |
February | 123.52 | 28-FEB-16:50 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 979.93 |
March | 128.77 | 02-MAR-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 665.77 |
April | 238.10 | 26-APR-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1128.21 |
May | 3982.07 | 19-MAY-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 637.09 | 0.00 |
June | 21091.91 | 26-JUN-05:03 | 290.07 | 2317.39 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 927.20 |
July | 23189.90 | 22-JUL-05:03 | 290.07 | 2317.39 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 24900.72 | 12-AUG-05:01 | 507.62 | 4055.43 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.37 |
September | 21719.02 | 02-SEP-05:03 | 290.07 | 2317.39 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.13 |
October | 2357.71 | 18-OCT-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 56.22 | 0.00 |
November | 386.11 | 09-NOV-15:30 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 704.13 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 2720.41 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1257.80 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 1813.61 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24900.72 | 659.25 | 4055.43 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 637.09 | 1257.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 535.49 | 02-JAN-14:20 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4675.96 |
February | 2818.45 | 23-FEB-15:40 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2593.44 |
March | 3649.99 | 25-MAR-11:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2473.60 | 29-APR-13:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3245.41 |
May | 7470.96 | 13-MAY-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 814.85 |
June | 49982.77 | 25-JUN-13:11 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1409.18 |
July | 48586.19 | 23-JUL-12:31 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1401.09 |
August | 45299.45 | 10-AUG-20:01 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 845.60 |
September | 41344.59 | 04-SEP-13:43 | 0.00 | 3556.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2628.54 | 0.00 |
October | 4157.03 | 13-OCT-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3720.86 |
November | 2630.81 | 06-NOV-09:40 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2082.15 |
December | 2025.65 | 21-DEC-14:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4252.40 |
Annual Sum or Average | |||||||||||
Minimum of Months | 535.49 | 0.00 | 3556.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49982.77 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2628.54 | 4675.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 10905.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7271.97 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 19084.37 | 14350.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56574.12 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 8179.02 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11640.13 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14933.21 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15453.48 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2416.26 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9767.31 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8397.65 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9489.10 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20188.31 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17543.08 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 16358.03 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43258.70 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2416.26 | |
Maximum of Months | 0.00 | 0.00 | 19084.37 | 14350.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56574.12 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.737590E+11 | 55364.54 | 21-JAN-08:09 | 0.357802E+12 | 354041.51 | 05-JAN-17:10 |
February | 0.657364E+11 | 52133.86 | 17-FEB-15:39 | 0.204750E+12 | 246247.75 | 01-FEB-17:00 |
March | 0.735045E+11 | 52123.03 | 03-MAR-13:39 | 0.152356E+12 | 247713.02 | 06-MAR-04:10 |
April | 0.665588E+11 | 51830.74 | 28-APR-14:39 | 0.487803E+11 | 142460.33 | 29-APR-05:19 |
May | 0.675783E+11 | 53683.78 | 20-MAY-14:00 | 0.392333E+11 | 144251.14 | 08-MAY-05:19 |
June | 0.673161E+11 | 60875.23 | 29-JUN-14:00 | 0.170550E+11 | 15879.44 | 17-JUN-05:10 |
July | 0.704585E+11 | 67856.88 | 17-JUL-14:09 | 0.174096E+11 | 6500.00 | 16-JUL-10:20 |
August | 0.736536E+11 | 66506.82 | 10-AUG-14:00 | 0.174459E+11 | 12007.08 | 18-AUG-06:10 |
September | 0.679046E+11 | 64567.58 | 02-SEP-14:39 | 0.196655E+11 | 49322.71 | 20-SEP-05:00 |
October | 0.691890E+11 | 54905.36 | 30-OCT-07:10 | 0.299487E+11 | 88828.57 | 11-OCT-05:00 |
November | 0.691062E+11 | 55316.40 | 30-NOV-16:49 | 0.120286E+12 | 233067.33 | 27-NOV-06:10 |
December | 0.736368E+11 | 55359.62 | 29-DEC-08:09 | 0.250686E+12 | 315767.66 | 31-DEC-02:00 |
Annual Sum or Average | 0.838402E+12 | 0.127542E+13 | ||||
Minimum of Months | 0.657364E+11 | 51830.74 | 0.170550E+11 | 6500.00 | ||
Maximum of Months | 0.737590E+11 | 67856.88 | 0.357802E+12 | 354041.51 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.396181E+11 | 0.133695E+11 | 0.115358E+11 | 0.00 | 0.689663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233903E+10 | 0.00 |
February | 0.362526E+11 | 0.110454E+11 | 0.105871E+11 | 0.00 | 0.570932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214200E+10 | 0.00 |
March | 0.418523E+11 | 0.107861E+11 | 0.123357E+11 | 0.00 | 0.611431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241610E+10 | 0.00 |
April | 0.392410E+11 | 0.898055E+10 | 0.114862E+11 | 0.00 | 0.458924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226180E+10 | 0.00 |
May | 0.407352E+11 | 0.798585E+10 | 0.119357E+11 | 0.00 | 0.451798E+10 | 0.00 | 0.00 | 0.117445E+09 | 0.00 | 0.00 | 0.00 | 0.228610E+10 | 0.00 |
June | 0.403581E+11 | 0.705244E+10 | 0.118862E+11 | 0.00 | 0.415177E+10 | 0.00 | 0.00 | 0.169064E+10 | 0.00 | 0.00 | 0.00 | 0.217702E+10 | 0.00 |
July | 0.396181E+11 | 0.759929E+10 | 0.115358E+11 | 0.00 | 0.482711E+10 | 0.00 | 0.00 | 0.473141E+10 | 0.00 | 0.00 | 0.00 | 0.214683E+10 | 0.00 |
August | 0.418523E+11 | 0.869770E+10 | 0.123357E+11 | 0.00 | 0.502609E+10 | 0.00 | 0.00 | 0.355533E+10 | 0.00 | 0.00 | 0.00 | 0.218653E+10 | 0.00 |
September | 0.392410E+11 | 0.980082E+10 | 0.114862E+11 | 0.00 | 0.411063E+10 | 0.00 | 0.00 | 0.116653E+10 | 0.00 | 0.00 | 0.00 | 0.209942E+10 | 0.00 |
October | 0.396181E+11 | 0.116252E+11 | 0.115358E+11 | 0.00 | 0.420721E+10 | 0.00 | 0.00 | 15036325.69 | 0.00 | 0.00 | 0.00 | 0.218767E+10 | 0.00 |
November | 0.381239E+11 | 0.125681E+11 | 0.110862E+11 | 0.00 | 0.516446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216348E+10 | 0.00 |
December | 0.396181E+11 | 0.137419E+11 | 0.115358E+11 | 0.00 | 0.644484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229615E+10 | 0.00 |
Annual Sum or Average | 0.476129E+12 | 0.123253E+12 | 0.139282E+12 | 0.617596E+11 | 0.00 | 0.112764E+11 | 0.267021E+11 | ||||||
Minimum of Months | 0.362526E+11 | 0.705244E+10 | 0.105871E+11 | 0.00 | 0.411063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209942E+10 | 0.00 |
Maximum of Months | 0.418523E+11 | 0.137419E+11 | 0.123357E+11 | 0.00 | 0.689663E+10 | 0.00 | 0.00 | 0.473141E+10 | 0.00 | 0.00 | 0.00 | 0.241610E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.357802E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.204750E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.152356E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.487803E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.392333E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.170550E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.174096E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.174459E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.196655E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.299487E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.120286E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.250686E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127542E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.170550E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.357802E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35189.04 | 02-JAN-09:09 | 7857.00 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4449.62 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35189.04 | 01-FEB-09:09 | 7857.00 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 4449.62 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35189.04 | 01-MAR-09:09 | 7857.00 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4449.62 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35189.04 | 01-APR-08:09 | 7857.00 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 4449.62 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35189.04 | 01-MAY-08:09 | 7857.00 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 4449.62 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35189.04 | 01-JUN-08:09 | 7857.00 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 4011.89 | 20-JUN-16:19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35189.04 | 01-JUL-08:09 | 7857.00 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6317.18 | 17-JUL-16:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35189.04 | 01-AUG-08:09 | 7857.00 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6317.18 | 10-AUG-12:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35189.04 | 01-SEP-08:09 | 7857.00 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 6317.18 | 02-SEP-15:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35189.04 | 02-OCT-08:09 | 7857.00 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 4449.62 | 10-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35189.04 | 01-NOV-08:09 | 7857.00 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 4449.62 | 10-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35189.04 | 01-DEC-09:09 | 7857.00 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4449.62 | 01-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35189.04 | 7857.00 | 10112.62 | 0.00 | 4011.89 | 0.00 | 0.00 | |||||
Maximum of Months | 35189.04 | 7857.00 | 10112.62 | 0.00 | 6317.18 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2834.25 | 31-JAN-12:50 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2853.98 | 17-FEB-12:50 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2848.45 | 01-MAR-12:50 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 2736.40 | 04-APR-11:50 | 0.00 |
May | 3538.22 | 20-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2562.62 | 01-MAY-11:20 | 0.00 |
June | 11029.55 | 29-JUN-15:09 | 0.00 | 0.00 | 0.00 | 2255.91 | 05-JUN-11:09 | 0.00 |
July | 16965.66 | 17-JUL-16:10 | 0.00 | 0.00 | 0.00 | 2029.71 | 01-JUL-11:00 | 0.00 |
August | 13857.78 | 10-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1840.45 | 03-AUG-11:00 | 0.00 |
September | 12612.78 | 02-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1953.22 | 28-SEP-11:00 | 0.00 |
October | 1104.48 | 18-OCT-15:50 | 0.00 | 0.00 | 0.00 | 2218.96 | 30-OCT-11:00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2474.42 | 28-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2693.14 | 28-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1840.45 | 0.00 | ||
Maximum of Months | 16965.66 | 0.00 | 0.00 | 0.00 | 2853.98 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 55364.54 | 21-JAN-08:09 | 31277.33 | 10112.62 | 7857.00 | 0.00 | 4449.62 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52133.86 | 17-FEB-15:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4449.62 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 52123.03 | 03-MAR-13:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4449.62 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 51830.74 | 28-APR-14:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4449.62 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 53683.78 | 20-MAY-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4011.89 | 0.00 | 0.00 | 2499.01 | 0.00 |
June | 60875.23 | 29-JUN-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4011.89 | 0.00 | 0.00 | 9778.48 | 0.00 |
July | 67856.88 | 17-JUL-14:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6317.18 | 0.00 | 0.00 | 14463.48 | 0.00 |
August | 66506.82 | 10-AUG-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6317.18 | 0.00 | 0.00 | 13120.04 | 0.00 |
September | 64567.58 | 02-SEP-14:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6317.18 | 0.00 | 0.00 | 11180.28 | 0.00 |
October | 54905.36 | 30-OCT-07:10 | 31277.33 | 10112.62 | 7857.00 | 0.00 | 4011.89 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 55316.40 | 30-NOV-16:49 | 31277.33 | 10112.62 | 7857.00 | 0.00 | 4449.62 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 55359.62 | 29-DEC-08:09 | 31277.33 | 10112.62 | 7857.00 | 0.00 | 4449.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 51830.74 | 31277.33 | 10112.62 | 0.00 | 0.00 | 4011.89 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 67856.88 | 35189.04 | 10112.62 | 7857.00 | 0.00 | 6317.18 | 0.00 | 0.00 | 14463.48 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 354041.51 | 05-JAN-17:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 246247.75 | 01-FEB-17:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 247713.02 | 06-MAR-04:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 142460.33 | 29-APR-05:19 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 144251.14 | 08-MAY-05:19 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 15879.44 | 17-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 6500.00 | 16-JUL-10:20 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 12007.08 | 18-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 49322.71 | 20-SEP-05:00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 88828.57 | 11-OCT-05:00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 233067.33 | 27-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 315767.66 | 31-DEC-02:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 6500.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 354041.51 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 43.83 | 15.88 | 10.67 | 19.21 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 19.17 | 16.78 | 8.17 | 19.21 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16.67 | 17.55 | 9.83 | 19.41 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8.50 | 19.44 | 8.00 | 19.72 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6.17 | 19.39 | 5.67 | 19.78 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.33 | 20.50 | 0.33 | 20.50 | 0.17 | 24.51 | 0.17 | 24.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.53 | 0.50 | 24.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1.50 | 20.18 | 1.50 | 20.18 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4.67 | 20.11 | 4.67 | 20.11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.67 | 18.16 | 8.00 | 19.63 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19.17 | 17.07 | 9.17 | 19.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 131.67 | 17.20 | 66.00 | 19.52 | 0.67 | 24.52 | 0.67 | 24.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.83 | 20.50 | 10.67 | 20.50 | 0.50 | 24.53 | 0.50 | 24.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 126.83 | 13.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 97.17 | 13.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 104.50 | 14.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 59.83 | 14.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29.50 | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.31 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.49 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.57 | 0.00 | 0.00 |
September | 5.83 | 14.77 | 0.00 | 0.00 | 3.50 | 27.53 | 0.00 | 0.00 |
October | 26.17 | 14.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 82.33 | 14.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 114.17 | 13.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 646.33 | 14.01 | 0.00 | 15.67 | 27.51 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 126.83 | 14.77 | 0.00 | 0.00 | 6.83 | 27.57 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.17 | 8.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5.17 | 8.56 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.17 | 8.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.03 | 300.00 | 21.03 | 300.00 | 21.03 |
February | 276.00 | 21.06 | 276.00 | 21.06 | 276.00 | 21.06 |
March | 324.00 | 21.05 | 324.00 | 21.05 | 324.00 | 21.05 |
April | 300.00 | 21.30 | 271.67 | 21.13 | 271.67 | 21.13 |
May | 312.00 | 21.92 | 199.00 | 21.14 | 199.00 | 21.14 |
June | 218.00 | 23.17 | 52.00 | 22.99 | 17.00 | 21.12 |
July | 59.83 | 23.61 | 130.17 | 23.89 | 0.00 | 0.00 |
August | 129.17 | 23.43 | 72.83 | 23.82 | 2.00 | 21.08 |
September | 230.00 | 22.62 | 110.83 | 22.29 | 69.50 | 21.33 |
October | 300.00 | 21.79 | 198.00 | 21.16 | 198.00 | 21.16 |
November | 288.00 | 21.12 | 281.83 | 21.09 | 281.83 | 21.09 |
December | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
Annual Sum or Average | 3037.00 | 21.66 | 2516.33 | 21.40 | 2239.00 | 21.09 |
Minimum of Months | 59.83 | 21.03 | 52.00 | 21.03 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 23.61 | 324.00 | 23.89 | 324.00 | 21.33 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.338527E+09 | 0.104913E+09 | 46.67 | 0.337630E+09 | 897803.42 | 0.00 | 0.39 | 20-MAY-16:00 | 0.00 | 01-MAY-00:05 | 5795.58 | 20-MAY-16:00 | 5795.58 | 20-MAY-16:00 | 99.11 | 20-MAY-11:00 | 1914.39 | 20-MAY-16:00 | 0.00 | 01-MAY-00:05 |
June | 0.231748E+10 | 0.717408E+09 | 178.19 | 0.223033E+10 | 87158928.46 | 0.00 | 1.00 | 22-JUN-05:03 | 0.00 | 01-JUN-00:10 | 17175.36 | 22-JUN-05:03 | 15026.58 | 23-JUN-05:03 | 4941.26 | 24-JUN-05:03 | 4526.70 | 22-JUN-05:03 | 0.00 | 01-JUN-00:10 |
July | 0.519099E+10 | 0.161736E+10 | 239.27 | 0.503494E+10 | 0.156045E+09 | 0.00 | 1.00 | 01-JUL-05:02 | 0.00 | 01-JUL-00:10 | 18869.82 | 19-JUL-05:01 | 16827.02 | 25-JUL-05:01 | 6605.24 | 19-JUL-05:10 | 5068.95 | 17-JUL-16:10 | 0.00 | 01-JUL-00:10 |
August | 0.417574E+10 | 0.130506E+10 | 226.44 | 0.414551E+10 | 30231747.99 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 16646.65 | 08-AUG-05:01 | 16619.85 | 07-AUG-05:01 | 3897.20 | 14-AUG-05:03 | 4382.76 | 08-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.150712E+10 | 0.459891E+09 | 112.00 | 0.138974E+10 | 0.117381E+09 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 17708.07 | 07-SEP-05:01 | 16258.44 | 05-SEP-05:01 | 6139.52 | 07-SEP-05:03 | 4664.52 | 07-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 49239133.48 | 15036325.69 | 15.00 | 49239133.48 | 0.00 | 0.00 | 0.25 | 18-OCT-16:00 | 0.00 | 01-OCT-00:10 | 3665.95 | 18-OCT-16:00 | 3665.95 | 18-OCT-16:00 | 0.00 | 18-OCT-12:30 | 1104.48 | 18-OCT-15:50 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.135791E+11 | 0.421967E+10 | 817.57 | 0.131874E+11 | 0.391715E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.519099E+10 | 0.161736E+10 | 239.27 | 0.503494E+10 | 0.156045E+09 | 0.00 | 1.00 | 0.00 | 18869.82 | 16827.02 | 6605.24 | 5068.95 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 39019063.85 | 12532122.88 | 5.00 | 39019063.85 | 0.00 | 0.00 | 0.13 | 20-MAY-16:00 | 0.00 | 01-MAY-00:05 | 4952.69 | 20-MAY-16:00 | 4952.69 | 20-MAY-16:00 | 0.00 | 20-MAY-16:10 | 1623.83 | 20-MAY-16:00 | 0.00 | 01-MAY-00:05 |
June | 0.317293E+10 | 0.973230E+09 | 76.52 | 0.306207E+10 | 0.110852E+09 | 0.00 | 1.00 | 22-JUN-18:11 | 0.00 | 01-JUN-00:10 | 51243.62 | 22-JUN-18:11 | 47306.75 | 23-JUN-19:31 | 10000.56 | 22-JUN-18:20 | 13200.37 | 22-JUN-18:11 | 0.00 | 01-JUN-00:10 |
July | 0.100193E+11 | 0.311405E+10 | 208.03 | 0.982043E+10 | 0.198857E+09 | 0.00 | 1.00 | 02-JUL-10:31 | 0.00 | 01-JUL-00:10 | 51580.38 | 16-JUL-09:51 | 47787.92 | 19-JUL-17:41 | 12810.16 | 16-JUL-09:57 | 14008.12 | 17-JUL-17:42 | 0.00 | 01-JUL-00:10 |
August | 0.712437E+10 | 0.225027E+10 | 161.52 | 0.709970E+10 | 24677530.49 | 0.00 | 1.00 | 03-AUG-17:31 | 0.00 | 01-AUG-00:10 | 46708.00 | 07-AUG-19:50 | 46708.00 | 07-AUG-19:50 | 2148.19 | 08-AUG-12:00 | 13827.21 | 06-AUG-15:55 | 0.00 | 01-AUG-00:10 |
September | 0.225875E+10 | 0.706637E+09 | 54.68 | 0.209795E+10 | 0.160806E+09 | 0.00 | 1.00 | 02-SEP-17:08 | 0.00 | 01-SEP-00:10 | 52675.56 | 06-SEP-17:40 | 45660.48 | 04-SEP-13:43 | 13907.12 | 06-SEP-17:40 | 13543.59 | 06-SEP-17:11 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.226144E+11 | 0.705671E+10 | 505.75 | 0.221192E+11 | 0.495192E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.100193E+11 | 0.311405E+10 | 208.03 | 0.982043E+10 | 0.198857E+09 | 0.00 | 1.00 | 0.00 | 52675.56 | 47787.92 | 13907.12 | 14008.12 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.37 | 24.52 | 35.84 | 21.15 | 278.05 | 0.00 | 0.00 | 744.00 |
February | 102.27 | 50.33 | 51.94 | 64.32 | 191.79 | 0.00 | 0.00 | 672.00 |
March | 131.29 | 48.22 | 83.07 | 87.64 | 152.10 | 0.00 | 0.00 | 744.00 |
April | 171.10 | 75.58 | 95.51 | 153.37 | 99.17 | 0.00 | 0.00 | 720.00 |
May | 211.63 | 96.52 | 115.10 | 207.84 | 80.81 | 0.00 | 0.00 | 744.00 |
June | 230.06 | 105.62 | 124.45 | 244.67 | 64.58 | 0.00 | 0.00 | 720.00 |
July | 235.92 | 119.25 | 116.68 | 271.33 | 61.99 | 0.00 | 0.00 | 744.00 |
August | 199.93 | 97.85 | 102.08 | 221.08 | 66.03 | 0.00 | 0.00 | 744.00 |
September | 160.99 | 81.35 | 79.64 | 163.71 | 83.78 | 0.00 | 0.00 | 720.00 |
October | 115.28 | 57.30 | 57.98 | 97.34 | 108.96 | 0.00 | 0.00 | 744.00 |
November | 81.47 | 40.42 | 41.05 | 51.53 | 156.40 | 0.00 | 0.00 | 720.00 |
December | 54.65 | 23.03 | 31.62 | 19.70 | 229.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 146.45 | 68.40 | 78.05 | 133.99 | 130.94 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 54.65 | 23.03 | 31.62 | 19.70 | 61.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 235.92 | 119.25 | 124.45 | 271.33 | 278.05 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.37 | 24.52 | 35.84 | 21.15 | 278.05 | 0.00 | 0.00 | 744.00 |
February | 102.27 | 50.33 | 51.94 | 64.32 | 191.79 | 0.00 | 0.00 | 672.00 |
March | 131.29 | 48.22 | 83.07 | 87.64 | 152.10 | 0.00 | 0.00 | 744.00 |
April | 171.10 | 75.58 | 95.51 | 153.37 | 99.17 | 0.00 | 0.00 | 720.00 |
May | 211.63 | 96.52 | 115.10 | 207.84 | 80.81 | 0.00 | 0.00 | 744.00 |
June | 230.06 | 105.62 | 124.45 | 244.67 | 64.58 | 0.00 | 0.00 | 720.00 |
July | 235.92 | 119.25 | 116.68 | 271.33 | 61.99 | 0.00 | 0.00 | 744.00 |
August | 199.93 | 97.85 | 102.08 | 221.08 | 66.03 | 0.00 | 0.00 | 744.00 |
September | 160.99 | 81.35 | 79.64 | 163.71 | 83.78 | 0.00 | 0.00 | 720.00 |
October | 115.28 | 57.30 | 57.98 | 97.34 | 108.96 | 0.00 | 0.00 | 744.00 |
November | 81.47 | 40.42 | 41.05 | 51.53 | 156.40 | 0.00 | 0.00 | 720.00 |
December | 54.65 | 23.03 | 31.62 | 19.70 | 229.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 146.45 | 68.40 | 78.05 | 133.99 | 130.94 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 54.65 | 23.03 | 31.62 | 19.70 | 61.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 235.92 | 119.25 | 124.45 | 271.33 | 278.05 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.83 | 0.00 | 16.83 | 0.19 | 169.99 | 0.00 | 0.00 | 744.00 |
February | 23.76 | 0.00 | 23.76 | 2.87 | 120.51 | 0.00 | 0.00 | 672.00 |
March | 38.60 | 0.00 | 38.59 | 8.95 | 91.88 | 0.00 | 0.00 | 744.00 |
April | 44.13 | 0.33 | 43.80 | 20.11 | 59.02 | 0.00 | 0.00 | 720.00 |
May | 57.74 | 3.37 | 54.36 | 34.69 | 46.39 | 0.00 | 0.00 | 744.00 |
June | 67.20 | 7.67 | 59.53 | 50.25 | 33.92 | 0.00 | 0.00 | 720.00 |
July | 61.38 | 5.66 | 55.71 | 54.59 | 33.05 | 0.00 | 0.00 | 744.00 |
August | 49.76 | 1.79 | 47.97 | 42.34 | 37.65 | 0.00 | 0.00 | 744.00 |
September | 36.93 | 0.03 | 36.89 | 25.17 | 49.35 | 0.00 | 0.00 | 720.00 |
October | 26.91 | 0.00 | 26.91 | 9.54 | 65.63 | 0.00 | 0.00 | 744.00 |
November | 18.29 | 0.00 | 18.29 | 2.38 | 97.51 | 0.00 | 0.00 | 720.00 |
December | 14.11 | 0.00 | 14.11 | 0.11 | 141.96 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.04 | 1.58 | 36.47 | 21.04 | 78.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 14.11 | 0.00 | 14.11 | 0.11 | 33.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.20 | 7.67 | 59.53 | 54.59 | 169.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.82 | 0.00 | 16.82 | 0.19 | 169.99 | 0.00 | 0.00 | 744.00 |
February | 23.76 | 0.00 | 23.76 | 2.87 | 120.51 | 0.00 | 0.00 | 672.00 |
March | 38.59 | 0.00 | 38.59 | 8.95 | 91.89 | 0.00 | 0.00 | 744.00 |
April | 44.13 | 0.33 | 43.80 | 20.11 | 59.02 | 0.00 | 0.00 | 720.00 |
May | 57.73 | 3.37 | 54.36 | 34.69 | 46.39 | 0.00 | 0.00 | 744.00 |
June | 67.19 | 7.67 | 59.53 | 50.25 | 33.92 | 0.00 | 0.00 | 720.00 |
July | 61.37 | 5.66 | 55.71 | 54.59 | 33.05 | 0.00 | 0.00 | 744.00 |
August | 49.76 | 1.79 | 47.97 | 42.34 | 37.65 | 0.00 | 0.00 | 744.00 |
September | 36.93 | 0.03 | 36.89 | 25.17 | 49.35 | 0.00 | 0.00 | 720.00 |
October | 26.91 | 0.00 | 26.91 | 9.54 | 65.63 | 0.00 | 0.00 | 744.00 |
November | 18.29 | 0.00 | 18.29 | 2.38 | 97.51 | 0.00 | 0.00 | 720.00 |
December | 14.11 | 0.00 | 14.11 | 0.11 | 141.96 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.04 | 1.58 | 36.46 | 21.04 | 78.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 14.11 | 0.00 | 14.11 | 0.11 | 33.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.19 | 7.67 | 59.53 | 54.59 | 169.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.71 | 7.35 | 12.35 | 3.62 | 74.03 | 0.00 | 0.00 | 744.00 |
February | 33.14 | 17.43 | 15.70 | 18.61 | 50.53 | 0.00 | 0.00 | 672.00 |
March | 56.61 | 26.71 | 29.90 | 49.80 | 39.40 | 0.00 | 0.00 | 744.00 |
April | 70.97 | 39.74 | 31.22 | 71.69 | 26.34 | 0.00 | 0.00 | 720.00 |
May | 91.82 | 52.78 | 39.05 | 100.50 | 21.70 | 0.00 | 0.00 | 744.00 |
June | 110.96 | 71.77 | 39.19 | 123.00 | 23.30 | 0.00 | 0.00 | 720.00 |
July | 114.90 | 80.87 | 34.03 | 125.76 | 29.21 | 0.00 | 0.00 | 744.00 |
August | 95.33 | 65.30 | 30.03 | 100.73 | 30.67 | 0.00 | 0.00 | 744.00 |
September | 65.27 | 41.31 | 23.97 | 65.30 | 29.97 | 0.00 | 0.00 | 720.00 |
October | 39.36 | 21.25 | 18.11 | 31.57 | 33.27 | 0.00 | 0.00 | 744.00 |
November | 23.08 | 10.53 | 12.55 | 10.71 | 41.91 | 0.00 | 0.00 | 720.00 |
December | 15.25 | 5.16 | 10.09 | 2.43 | 61.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.53 | 36.80 | 24.73 | 58.87 | 38.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.25 | 5.16 | 10.09 | 2.43 | 21.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.90 | 80.87 | 39.19 | 125.76 | 74.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.71 | 7.35 | 12.35 | 3.62 | 74.03 | 0.00 | 0.00 | 744.00 |
February | 33.14 | 17.43 | 15.70 | 18.61 | 50.53 | 0.00 | 0.00 | 672.00 |
March | 56.61 | 26.71 | 29.90 | 49.80 | 39.40 | 0.00 | 0.00 | 744.00 |
April | 70.97 | 39.74 | 31.22 | 71.69 | 26.34 | 0.00 | 0.00 | 720.00 |
May | 91.82 | 52.78 | 39.05 | 100.50 | 21.70 | 0.00 | 0.00 | 744.00 |
June | 110.96 | 71.77 | 39.19 | 123.00 | 23.30 | 0.00 | 0.00 | 720.00 |
July | 114.90 | 80.87 | 34.03 | 125.76 | 29.21 | 0.00 | 0.00 | 744.00 |
August | 95.33 | 65.30 | 30.03 | 100.73 | 30.67 | 0.00 | 0.00 | 744.00 |
September | 65.27 | 41.31 | 23.97 | 65.30 | 29.97 | 0.00 | 0.00 | 720.00 |
October | 39.36 | 21.25 | 18.11 | 31.57 | 33.27 | 0.00 | 0.00 | 744.00 |
November | 23.08 | 10.53 | 12.55 | 10.71 | 41.91 | 0.00 | 0.00 | 720.00 |
December | 15.25 | 5.16 | 10.09 | 2.43 | 61.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.53 | 36.80 | 24.73 | 58.87 | 38.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.25 | 5.16 | 10.09 | 2.43 | 21.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.90 | 80.87 | 39.19 | 125.76 | 74.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.71 | 7.35 | 12.35 | 3.62 | 74.03 | 0.00 | 0.00 | 744.00 |
February | 33.14 | 17.43 | 15.70 | 18.61 | 50.53 | 0.00 | 0.00 | 672.00 |
March | 56.61 | 26.71 | 29.90 | 49.80 | 39.40 | 0.00 | 0.00 | 744.00 |
April | 70.97 | 39.74 | 31.22 | 71.69 | 26.34 | 0.00 | 0.00 | 720.00 |
May | 91.82 | 52.78 | 39.05 | 100.50 | 21.70 | 0.00 | 0.00 | 744.00 |
June | 110.96 | 71.77 | 39.19 | 123.00 | 23.30 | 0.00 | 0.00 | 720.00 |
July | 114.90 | 80.87 | 34.03 | 125.76 | 29.21 | 0.00 | 0.00 | 744.00 |
August | 95.33 | 65.30 | 30.03 | 100.73 | 30.67 | 0.00 | 0.00 | 744.00 |
September | 65.27 | 41.31 | 23.97 | 65.30 | 29.97 | 0.00 | 0.00 | 720.00 |
October | 39.36 | 21.25 | 18.11 | 31.57 | 33.27 | 0.00 | 0.00 | 744.00 |
November | 23.08 | 10.53 | 12.55 | 10.71 | 41.91 | 0.00 | 0.00 | 720.00 |
December | 15.25 | 5.16 | 10.09 | 2.43 | 61.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.53 | 36.80 | 24.73 | 58.87 | 38.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.25 | 5.16 | 10.09 | 2.43 | 21.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.90 | 80.87 | 39.19 | 125.76 | 74.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.71 | 7.35 | 12.35 | 3.62 | 74.03 | 0.00 | 0.00 | 744.00 |
February | 33.14 | 17.43 | 15.70 | 18.61 | 50.53 | 0.00 | 0.00 | 672.00 |
March | 56.61 | 26.71 | 29.90 | 49.80 | 39.40 | 0.00 | 0.00 | 744.00 |
April | 70.97 | 39.74 | 31.22 | 71.69 | 26.34 | 0.00 | 0.00 | 720.00 |
May | 91.82 | 52.78 | 39.05 | 100.50 | 21.70 | 0.00 | 0.00 | 744.00 |
June | 110.96 | 71.77 | 39.19 | 123.00 | 23.30 | 0.00 | 0.00 | 720.00 |
July | 114.90 | 80.87 | 34.03 | 125.76 | 29.21 | 0.00 | 0.00 | 744.00 |
August | 95.33 | 65.30 | 30.03 | 100.73 | 30.67 | 0.00 | 0.00 | 744.00 |
September | 65.27 | 41.31 | 23.97 | 65.30 | 29.97 | 0.00 | 0.00 | 720.00 |
October | 39.36 | 21.25 | 18.11 | 31.57 | 33.27 | 0.00 | 0.00 | 744.00 |
November | 23.08 | 10.53 | 12.55 | 10.71 | 41.91 | 0.00 | 0.00 | 720.00 |
December | 15.25 | 5.16 | 10.09 | 2.43 | 61.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.53 | 36.80 | 24.73 | 58.87 | 38.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.25 | 5.16 | 10.09 | 2.43 | 21.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.90 | 80.87 | 39.19 | 125.76 | 74.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.71 | 7.35 | 12.35 | 3.62 | 74.03 | 0.00 | 0.00 | 744.00 |
February | 33.14 | 17.43 | 15.70 | 18.61 | 50.53 | 0.00 | 0.00 | 672.00 |
March | 56.61 | 26.71 | 29.90 | 49.80 | 39.40 | 0.00 | 0.00 | 744.00 |
April | 70.97 | 39.74 | 31.22 | 71.69 | 26.34 | 0.00 | 0.00 | 720.00 |
May | 91.82 | 52.78 | 39.05 | 100.50 | 21.70 | 0.00 | 0.00 | 744.00 |
June | 110.96 | 71.77 | 39.19 | 123.00 | 23.30 | 0.00 | 0.00 | 720.00 |
July | 114.90 | 80.87 | 34.03 | 125.76 | 29.21 | 0.00 | 0.00 | 744.00 |
August | 95.33 | 65.30 | 30.03 | 100.73 | 30.67 | 0.00 | 0.00 | 744.00 |
September | 65.27 | 41.31 | 23.97 | 65.30 | 29.97 | 0.00 | 0.00 | 720.00 |
October | 39.36 | 21.25 | 18.11 | 31.57 | 33.27 | 0.00 | 0.00 | 744.00 |
November | 23.08 | 10.53 | 12.55 | 10.71 | 41.91 | 0.00 | 0.00 | 720.00 |
December | 15.25 | 5.16 | 10.09 | 2.43 | 61.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.53 | 36.80 | 24.73 | 58.87 | 38.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.25 | 5.16 | 10.09 | 2.43 | 21.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.90 | 80.87 | 39.19 | 125.76 | 74.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.71 | 7.35 | 12.35 | 3.62 | 74.03 | 0.00 | 0.00 | 744.00 |
February | 33.14 | 17.43 | 15.70 | 18.61 | 50.53 | 0.00 | 0.00 | 672.00 |
March | 56.61 | 26.71 | 29.90 | 49.80 | 39.40 | 0.00 | 0.00 | 744.00 |
April | 70.97 | 39.74 | 31.22 | 71.69 | 26.34 | 0.00 | 0.00 | 720.00 |
May | 91.82 | 52.78 | 39.05 | 100.50 | 21.70 | 0.00 | 0.00 | 744.00 |
June | 110.96 | 71.77 | 39.19 | 123.00 | 23.30 | 0.00 | 0.00 | 720.00 |
July | 114.90 | 80.87 | 34.03 | 125.76 | 29.21 | 0.00 | 0.00 | 744.00 |
August | 95.33 | 65.30 | 30.03 | 100.73 | 30.67 | 0.00 | 0.00 | 744.00 |
September | 65.27 | 41.31 | 23.97 | 65.30 | 29.97 | 0.00 | 0.00 | 720.00 |
October | 39.36 | 21.25 | 18.11 | 31.57 | 33.27 | 0.00 | 0.00 | 744.00 |
November | 23.08 | 10.53 | 12.55 | 10.71 | 41.91 | 0.00 | 0.00 | 720.00 |
December | 15.25 | 5.16 | 10.09 | 2.43 | 61.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.53 | 36.80 | 24.73 | 58.87 | 38.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.25 | 5.16 | 10.09 | 2.43 | 21.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.90 | 80.87 | 39.19 | 125.76 | 74.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.71 | 7.35 | 12.35 | 3.62 | 74.03 | 0.00 | 0.00 | 744.00 |
February | 33.14 | 17.43 | 15.70 | 18.61 | 50.53 | 0.00 | 0.00 | 672.00 |
March | 56.61 | 26.71 | 29.90 | 49.80 | 39.40 | 0.00 | 0.00 | 744.00 |
April | 70.97 | 39.74 | 31.22 | 71.69 | 26.34 | 0.00 | 0.00 | 720.00 |
May | 91.82 | 52.78 | 39.05 | 100.50 | 21.70 | 0.00 | 0.00 | 744.00 |
June | 110.96 | 71.77 | 39.19 | 123.00 | 23.30 | 0.00 | 0.00 | 720.00 |
July | 114.90 | 80.87 | 34.03 | 125.76 | 29.21 | 0.00 | 0.00 | 744.00 |
August | 95.33 | 65.30 | 30.03 | 100.73 | 30.67 | 0.00 | 0.00 | 744.00 |
September | 65.27 | 41.31 | 23.97 | 65.30 | 29.97 | 0.00 | 0.00 | 720.00 |
October | 39.36 | 21.25 | 18.11 | 31.57 | 33.27 | 0.00 | 0.00 | 744.00 |
November | 23.08 | 10.53 | 12.55 | 10.71 | 41.91 | 0.00 | 0.00 | 720.00 |
December | 15.25 | 5.16 | 10.09 | 2.43 | 61.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.53 | 36.80 | 24.73 | 58.87 | 38.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.25 | 5.16 | 10.09 | 2.43 | 21.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.90 | 80.87 | 39.19 | 125.76 | 74.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.71 | 7.35 | 12.35 | 3.62 | 74.03 | 0.00 | 0.00 | 744.00 |
February | 33.14 | 17.43 | 15.70 | 18.61 | 50.53 | 0.00 | 0.00 | 672.00 |
March | 56.61 | 26.71 | 29.90 | 49.80 | 39.40 | 0.00 | 0.00 | 744.00 |
April | 70.97 | 39.74 | 31.22 | 71.69 | 26.34 | 0.00 | 0.00 | 720.00 |
May | 91.82 | 52.78 | 39.05 | 100.50 | 21.70 | 0.00 | 0.00 | 744.00 |
June | 110.96 | 71.77 | 39.19 | 123.00 | 23.30 | 0.00 | 0.00 | 720.00 |
July | 114.90 | 80.87 | 34.03 | 125.76 | 29.21 | 0.00 | 0.00 | 744.00 |
August | 95.33 | 65.30 | 30.03 | 100.73 | 30.67 | 0.00 | 0.00 | 744.00 |
September | 65.27 | 41.31 | 23.97 | 65.30 | 29.97 | 0.00 | 0.00 | 720.00 |
October | 39.36 | 21.25 | 18.11 | 31.57 | 33.27 | 0.00 | 0.00 | 744.00 |
November | 23.08 | 10.53 | 12.55 | 10.71 | 41.91 | 0.00 | 0.00 | 720.00 |
December | 15.25 | 5.16 | 10.09 | 2.43 | 61.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.53 | 36.80 | 24.73 | 58.87 | 38.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.25 | 5.16 | 10.09 | 2.43 | 21.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.90 | 80.87 | 39.19 | 125.76 | 74.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.71 | 7.35 | 12.35 | 3.62 | 74.03 | 0.00 | 0.00 | 744.00 |
February | 33.14 | 17.43 | 15.70 | 18.61 | 50.53 | 0.00 | 0.00 | 672.00 |
March | 56.61 | 26.71 | 29.90 | 49.80 | 39.40 | 0.00 | 0.00 | 744.00 |
April | 70.97 | 39.74 | 31.22 | 71.69 | 26.34 | 0.00 | 0.00 | 720.00 |
May | 91.82 | 52.78 | 39.05 | 100.50 | 21.70 | 0.00 | 0.00 | 744.00 |
June | 110.96 | 71.77 | 39.19 | 123.00 | 23.30 | 0.00 | 0.00 | 720.00 |
July | 114.90 | 80.87 | 34.03 | 125.76 | 29.21 | 0.00 | 0.00 | 744.00 |
August | 95.33 | 65.30 | 30.03 | 100.73 | 30.67 | 0.00 | 0.00 | 744.00 |
September | 65.27 | 41.31 | 23.97 | 65.30 | 29.97 | 0.00 | 0.00 | 720.00 |
October | 39.36 | 21.25 | 18.11 | 31.57 | 33.27 | 0.00 | 0.00 | 744.00 |
November | 23.08 | 10.53 | 12.55 | 10.71 | 41.91 | 0.00 | 0.00 | 720.00 |
December | 15.25 | 5.16 | 10.09 | 2.43 | 61.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.53 | 36.80 | 24.73 | 58.87 | 38.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.25 | 5.16 | 10.09 | 2.43 | 21.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.90 | 80.87 | 39.19 | 125.76 | 74.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.71 | 7.35 | 12.35 | 3.62 | 74.03 | 0.00 | 0.00 | 744.00 |
February | 33.14 | 17.43 | 15.70 | 18.61 | 50.53 | 0.00 | 0.00 | 672.00 |
March | 56.61 | 26.71 | 29.90 | 49.80 | 39.40 | 0.00 | 0.00 | 744.00 |
April | 70.97 | 39.74 | 31.22 | 71.69 | 26.34 | 0.00 | 0.00 | 720.00 |
May | 91.82 | 52.78 | 39.05 | 100.50 | 21.70 | 0.00 | 0.00 | 744.00 |
June | 110.96 | 71.77 | 39.19 | 123.00 | 23.30 | 0.00 | 0.00 | 720.00 |
July | 114.90 | 80.87 | 34.03 | 125.76 | 29.21 | 0.00 | 0.00 | 744.00 |
August | 95.33 | 65.30 | 30.03 | 100.73 | 30.67 | 0.00 | 0.00 | 744.00 |
September | 65.27 | 41.31 | 23.97 | 65.30 | 29.97 | 0.00 | 0.00 | 720.00 |
October | 39.36 | 21.25 | 18.11 | 31.57 | 33.27 | 0.00 | 0.00 | 744.00 |
November | 23.08 | 10.53 | 12.55 | 10.71 | 41.91 | 0.00 | 0.00 | 720.00 |
December | 15.25 | 5.16 | 10.09 | 2.43 | 61.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.53 | 36.80 | 24.73 | 58.87 | 38.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.25 | 5.16 | 10.09 | 2.43 | 21.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.90 | 80.87 | 39.19 | 125.76 | 74.03 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161686E+09 | 65681865.97 | 96004513.48 | 56657030.04 | 0.744725E+09 |
February | 0.247411E+09 | 0.121762E+09 | 0.125649E+09 | 0.155607E+09 | 0.463981E+09 |
March | 0.351654E+09 | 0.129165E+09 | 0.222489E+09 | 0.234741E+09 | 0.407392E+09 |
April | 0.443479E+09 | 0.195911E+09 | 0.247568E+09 | 0.397546E+09 | 0.257059E+09 |
May | 0.566819E+09 | 0.258528E+09 | 0.308290E+09 | 0.556670E+09 | 0.216438E+09 |
June | 0.596326E+09 | 0.273763E+09 | 0.322563E+09 | 0.634187E+09 | 0.167386E+09 |
July | 0.631901E+09 | 0.319397E+09 | 0.312504E+09 | 0.726727E+09 | 0.166044E+09 |
August | 0.535480E+09 | 0.262075E+09 | 0.273405E+09 | 0.592132E+09 | 0.176855E+09 |
September | 0.417296E+09 | 0.210868E+09 | 0.206428E+09 | 0.424335E+09 | 0.217162E+09 |
October | 0.308771E+09 | 0.153481E+09 | 0.155290E+09 | 0.260709E+09 | 0.291839E+09 |
November | 0.211168E+09 | 0.104778E+09 | 0.106390E+09 | 0.133561E+09 | 0.405391E+09 |
December | 0.146384E+09 | 61686720.27 | 84697559.08 | 52768591.87 | 0.615020E+09 |
Annual Sum or Average | 0.461837E+10 | 0.215710E+10 | 0.246128E+10 | 0.422564E+10 | 0.412929E+10 |
Minimum of Months | 0.146384E+09 | 61686720.27 | 84697559.08 | 52768591.87 | 0.166044E+09 |
Maximum of Months | 0.631901E+09 | 0.319397E+09 | 0.322563E+09 | 0.726727E+09 | 0.744725E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161686E+09 | 65681865.97 | 96004513.48 | 56657030.04 | 0.744725E+09 |
February | 0.247411E+09 | 0.121762E+09 | 0.125649E+09 | 0.155607E+09 | 0.463981E+09 |
March | 0.351654E+09 | 0.129165E+09 | 0.222489E+09 | 0.234741E+09 | 0.407392E+09 |
April | 0.443479E+09 | 0.195911E+09 | 0.247568E+09 | 0.397546E+09 | 0.257059E+09 |
May | 0.566819E+09 | 0.258528E+09 | 0.308290E+09 | 0.556670E+09 | 0.216438E+09 |
June | 0.596326E+09 | 0.273763E+09 | 0.322563E+09 | 0.634187E+09 | 0.167386E+09 |
July | 0.631901E+09 | 0.319397E+09 | 0.312504E+09 | 0.726727E+09 | 0.166044E+09 |
August | 0.535480E+09 | 0.262075E+09 | 0.273405E+09 | 0.592132E+09 | 0.176855E+09 |
September | 0.417296E+09 | 0.210868E+09 | 0.206428E+09 | 0.424335E+09 | 0.217162E+09 |
October | 0.308771E+09 | 0.153481E+09 | 0.155290E+09 | 0.260709E+09 | 0.291839E+09 |
November | 0.211168E+09 | 0.104778E+09 | 0.106390E+09 | 0.133561E+09 | 0.405391E+09 |
December | 0.146384E+09 | 61686720.27 | 84697559.08 | 52768591.87 | 0.615020E+09 |
Annual Sum or Average | 0.461837E+10 | 0.215710E+10 | 0.246128E+10 | 0.422564E+10 | 0.412929E+10 |
Minimum of Months | 0.146384E+09 | 61686720.27 | 84697559.08 | 52768591.87 | 0.166044E+09 |
Maximum of Months | 0.631901E+09 | 0.319397E+09 | 0.322563E+09 | 0.726727E+09 | 0.744725E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45064288.41 | 0.00 | 45064288.41 | 512339.57 | 0.455301E+09 |
February | 57470429.67 | 0.00 | 57470429.67 | 6941699.82 | 0.291532E+09 |
March | 0.103373E+09 | 5154.92 | 0.103368E+09 | 23971414.07 | 0.246105E+09 |
April | 0.114392E+09 | 857486.23 | 0.113534E+09 | 52124766.36 | 0.152988E+09 |
May | 0.154641E+09 | 9033514.49 | 0.145607E+09 | 92908402.77 | 0.124264E+09 |
June | 0.174172E+09 | 19871915.09 | 0.154300E+09 | 0.130259E+09 | 87932334.54 |
July | 0.164389E+09 | 15169360.03 | 0.149219E+09 | 0.146227E+09 | 88522528.16 |
August | 0.133290E+09 | 4794192.82 | 0.128496E+09 | 0.113411E+09 | 0.100848E+09 |
September | 95713512.75 | 81737.00 | 95631775.75 | 65238344.15 | 0.127924E+09 |
October | 72072435.85 | 0.00 | 72072435.85 | 25548644.29 | 0.175791E+09 |
November | 47415011.88 | 0.00 | 47415011.88 | 6158619.98 | 0.252741E+09 |
December | 37788945.48 | 0.00 | 37788945.48 | 293191.65 | 0.380216E+09 |
Annual Sum or Average | 0.119978E+10 | 49813360.58 | 0.114997E+10 | 0.663594E+09 | 0.248416E+10 |
Minimum of Months | 37788945.48 | 0.00 | 37788945.48 | 293191.65 | 87932334.54 |
Maximum of Months | 0.174172E+09 | 19871915.09 | 0.154300E+09 | 0.146227E+09 | 0.455301E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45062835.23 | 0.00 | 45062835.23 | 512241.64 | 0.455301E+09 |
February | 57468698.97 | 0.00 | 57468698.97 | 6941302.76 | 0.291532E+09 |
March | 0.103370E+09 | 5154.68 | 0.103365E+09 | 23969563.29 | 0.246105E+09 |
April | 0.114389E+09 | 857446.04 | 0.113531E+09 | 52122338.39 | 0.152988E+09 |
May | 0.154636E+09 | 9033091.07 | 0.145603E+09 | 92904643.35 | 0.124264E+09 |
June | 0.174167E+09 | 19870983.66 | 0.154296E+09 | 0.130255E+09 | 87932155.09 |
July | 0.164384E+09 | 15168649.02 | 0.149215E+09 | 0.146223E+09 | 88521926.89 |
August | 0.133286E+09 | 4793968.11 | 0.128492E+09 | 0.113408E+09 | 0.100847E+09 |
September | 95710774.52 | 81733.17 | 95629041.36 | 65236258.43 | 0.127923E+09 |
October | 72070253.22 | 0.00 | 72070253.22 | 25547353.32 | 0.175791E+09 |
November | 47413524.99 | 0.00 | 47413524.99 | 6158149.35 | 0.252740E+09 |
December | 37787710.35 | 0.00 | 37787710.35 | 293148.84 | 0.380216E+09 |
Annual Sum or Average | 0.119975E+10 | 49811025.76 | 0.114993E+10 | 0.663571E+09 | 0.248416E+10 |
Minimum of Months | 37787710.35 | 0.00 | 37787710.35 | 293148.84 | 87932155.09 |
Maximum of Months | 0.174167E+09 | 19870983.66 | 0.154296E+09 | 0.146223E+09 | 0.455301E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52780164.69 | 19696094.93 | 33084069.76 | 9706391.55 | 0.198280E+09 |
February | 80169482.78 | 42176459.88 | 37993022.91 | 45021072.50 | 0.122244E+09 |
March | 0.151622E+09 | 71536362.23 | 80085864.37 | 0.133396E+09 | 0.105527E+09 |
April | 0.183943E+09 | 0.103017E+09 | 80926353.75 | 0.185824E+09 | 68276020.20 |
May | 0.245940E+09 | 0.141353E+09 | 0.104587E+09 | 0.269191E+09 | 58109684.79 |
June | 0.287621E+09 | 0.186037E+09 | 0.101585E+09 | 0.318804E+09 | 60403786.05 |
July | 0.307739E+09 | 0.216594E+09 | 91144959.21 | 0.336832E+09 | 78246322.69 |
August | 0.255337E+09 | 0.174912E+09 | 80425238.16 | 0.269784E+09 | 82143737.96 |
September | 0.169191E+09 | 0.107067E+09 | 62123521.16 | 0.169266E+09 | 77678718.28 |
October | 0.105426E+09 | 56914896.08 | 48511255.61 | 84569540.87 | 89110946.80 |
November | 59812672.88 | 27291670.98 | 32521001.91 | 27750694.02 | 0.108639E+09 |
December | 40841095.77 | 13813438.40 | 27027657.37 | 6505626.43 | 0.164807E+09 |
Annual Sum or Average | 0.194042E+10 | 0.116041E+10 | 0.780014E+09 | 0.185665E+10 | 0.121347E+10 |
Minimum of Months | 40841095.77 | 13813438.40 | 27027657.37 | 6505626.43 | 58109684.79 |
Maximum of Months | 0.307739E+09 | 0.216594E+09 | 0.104587E+09 | 0.336832E+09 | 0.198280E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52780164.69 | 19696094.93 | 33084069.76 | 9706391.55 | 0.198280E+09 |
February | 80169482.78 | 42176459.88 | 37993022.91 | 45021072.50 | 0.122244E+09 |
March | 0.151622E+09 | 71536362.23 | 80085864.37 | 0.133396E+09 | 0.105527E+09 |
April | 0.183943E+09 | 0.103017E+09 | 80926353.75 | 0.185824E+09 | 68276020.20 |
May | 0.245940E+09 | 0.141353E+09 | 0.104587E+09 | 0.269191E+09 | 58109684.79 |
June | 0.287621E+09 | 0.186037E+09 | 0.101585E+09 | 0.318804E+09 | 60403786.05 |
July | 0.307739E+09 | 0.216594E+09 | 91144959.21 | 0.336832E+09 | 78246322.69 |
August | 0.255337E+09 | 0.174912E+09 | 80425238.16 | 0.269784E+09 | 82143737.96 |
September | 0.169191E+09 | 0.107067E+09 | 62123521.16 | 0.169266E+09 | 77678718.28 |
October | 0.105426E+09 | 56914896.08 | 48511255.61 | 84569540.87 | 89110946.80 |
November | 59812672.88 | 27291670.98 | 32521001.91 | 27750694.02 | 0.108639E+09 |
December | 40841095.77 | 13813438.40 | 27027657.37 | 6505626.43 | 0.164807E+09 |
Annual Sum or Average | 0.194042E+10 | 0.116041E+10 | 0.780014E+09 | 0.185665E+10 | 0.121347E+10 |
Minimum of Months | 40841095.77 | 13813438.40 | 27027657.37 | 6505626.43 | 58109684.79 |
Maximum of Months | 0.307739E+09 | 0.216594E+09 | 0.104587E+09 | 0.336832E+09 | 0.198280E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52780164.69 | 19696094.93 | 33084069.76 | 9706391.55 | 0.198280E+09 |
February | 80169482.78 | 42176459.88 | 37993022.91 | 45021072.50 | 0.122244E+09 |
March | 0.151622E+09 | 71536362.23 | 80085864.37 | 0.133396E+09 | 0.105527E+09 |
April | 0.183943E+09 | 0.103017E+09 | 80926353.75 | 0.185824E+09 | 68276020.20 |
May | 0.245940E+09 | 0.141353E+09 | 0.104587E+09 | 0.269191E+09 | 58109684.79 |
June | 0.287621E+09 | 0.186037E+09 | 0.101585E+09 | 0.318804E+09 | 60403786.05 |
July | 0.307739E+09 | 0.216594E+09 | 91144959.21 | 0.336832E+09 | 78246322.69 |
August | 0.255337E+09 | 0.174912E+09 | 80425238.16 | 0.269784E+09 | 82143737.96 |
September | 0.169191E+09 | 0.107067E+09 | 62123521.16 | 0.169266E+09 | 77678718.28 |
October | 0.105426E+09 | 56914896.08 | 48511255.61 | 84569540.87 | 89110946.80 |
November | 59812672.88 | 27291670.98 | 32521001.91 | 27750694.02 | 0.108639E+09 |
December | 40841095.77 | 13813438.40 | 27027657.37 | 6505626.43 | 0.164807E+09 |
Annual Sum or Average | 0.194042E+10 | 0.116041E+10 | 0.780014E+09 | 0.185665E+10 | 0.121347E+10 |
Minimum of Months | 40841095.77 | 13813438.40 | 27027657.37 | 6505626.43 | 58109684.79 |
Maximum of Months | 0.307739E+09 | 0.216594E+09 | 0.104587E+09 | 0.336832E+09 | 0.198280E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52780164.69 | 19696094.93 | 33084069.76 | 9706391.55 | 0.198280E+09 |
February | 80169482.78 | 42176459.88 | 37993022.91 | 45021072.50 | 0.122244E+09 |
March | 0.151622E+09 | 71536362.23 | 80085864.37 | 0.133396E+09 | 0.105527E+09 |
April | 0.183943E+09 | 0.103017E+09 | 80926353.75 | 0.185824E+09 | 68276020.20 |
May | 0.245940E+09 | 0.141353E+09 | 0.104587E+09 | 0.269191E+09 | 58109684.79 |
June | 0.287621E+09 | 0.186037E+09 | 0.101585E+09 | 0.318804E+09 | 60403786.05 |
July | 0.307739E+09 | 0.216594E+09 | 91144959.21 | 0.336832E+09 | 78246322.69 |
August | 0.255337E+09 | 0.174912E+09 | 80425238.16 | 0.269784E+09 | 82143737.96 |
September | 0.169191E+09 | 0.107067E+09 | 62123521.16 | 0.169266E+09 | 77678718.28 |
October | 0.105426E+09 | 56914896.08 | 48511255.61 | 84569540.87 | 89110946.80 |
November | 59812672.88 | 27291670.98 | 32521001.91 | 27750694.02 | 0.108639E+09 |
December | 40841095.77 | 13813438.40 | 27027657.37 | 6505626.43 | 0.164807E+09 |
Annual Sum or Average | 0.194042E+10 | 0.116041E+10 | 0.780014E+09 | 0.185665E+10 | 0.121347E+10 |
Minimum of Months | 40841095.77 | 13813438.40 | 27027657.37 | 6505626.43 | 58109684.79 |
Maximum of Months | 0.307739E+09 | 0.216594E+09 | 0.104587E+09 | 0.336832E+09 | 0.198280E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52780164.69 | 19696094.93 | 33084069.76 | 9706391.55 | 0.198280E+09 |
February | 80169482.78 | 42176459.88 | 37993022.91 | 45021072.50 | 0.122244E+09 |
March | 0.151622E+09 | 71536362.23 | 80085864.37 | 0.133396E+09 | 0.105527E+09 |
April | 0.183943E+09 | 0.103017E+09 | 80926353.75 | 0.185824E+09 | 68276020.20 |
May | 0.245940E+09 | 0.141353E+09 | 0.104587E+09 | 0.269191E+09 | 58109684.79 |
June | 0.287621E+09 | 0.186037E+09 | 0.101585E+09 | 0.318804E+09 | 60403786.05 |
July | 0.307739E+09 | 0.216594E+09 | 91144959.21 | 0.336832E+09 | 78246322.69 |
August | 0.255337E+09 | 0.174912E+09 | 80425238.16 | 0.269784E+09 | 82143737.96 |
September | 0.169191E+09 | 0.107067E+09 | 62123521.16 | 0.169266E+09 | 77678718.28 |
October | 0.105426E+09 | 56914896.08 | 48511255.61 | 84569540.87 | 89110946.80 |
November | 59812672.88 | 27291670.98 | 32521001.91 | 27750694.02 | 0.108639E+09 |
December | 40841095.77 | 13813438.40 | 27027657.37 | 6505626.43 | 0.164807E+09 |
Annual Sum or Average | 0.194042E+10 | 0.116041E+10 | 0.780014E+09 | 0.185665E+10 | 0.121347E+10 |
Minimum of Months | 40841095.77 | 13813438.40 | 27027657.37 | 6505626.43 | 58109684.79 |
Maximum of Months | 0.307739E+09 | 0.216594E+09 | 0.104587E+09 | 0.336832E+09 | 0.198280E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52780164.69 | 19696094.93 | 33084069.76 | 9706391.55 | 0.198280E+09 |
February | 80169482.78 | 42176459.88 | 37993022.91 | 45021072.50 | 0.122244E+09 |
March | 0.151622E+09 | 71536362.23 | 80085864.37 | 0.133396E+09 | 0.105527E+09 |
April | 0.183943E+09 | 0.103017E+09 | 80926353.75 | 0.185824E+09 | 68276020.20 |
May | 0.245940E+09 | 0.141353E+09 | 0.104587E+09 | 0.269191E+09 | 58109684.79 |
June | 0.287621E+09 | 0.186037E+09 | 0.101585E+09 | 0.318804E+09 | 60403786.05 |
July | 0.307739E+09 | 0.216594E+09 | 91144959.21 | 0.336832E+09 | 78246322.69 |
August | 0.255337E+09 | 0.174912E+09 | 80425238.16 | 0.269784E+09 | 82143737.96 |
September | 0.169191E+09 | 0.107067E+09 | 62123521.16 | 0.169266E+09 | 77678718.28 |
October | 0.105426E+09 | 56914896.08 | 48511255.61 | 84569540.87 | 89110946.80 |
November | 59812672.88 | 27291670.98 | 32521001.91 | 27750694.02 | 0.108639E+09 |
December | 40841095.77 | 13813438.40 | 27027657.37 | 6505626.43 | 0.164807E+09 |
Annual Sum or Average | 0.194042E+10 | 0.116041E+10 | 0.780014E+09 | 0.185665E+10 | 0.121347E+10 |
Minimum of Months | 40841095.77 | 13813438.40 | 27027657.37 | 6505626.43 | 58109684.79 |
Maximum of Months | 0.307739E+09 | 0.216594E+09 | 0.104587E+09 | 0.336832E+09 | 0.198280E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52780164.69 | 19696094.93 | 33084069.76 | 9706391.55 | 0.198280E+09 |
February | 80169482.78 | 42176459.88 | 37993022.91 | 45021072.50 | 0.122244E+09 |
March | 0.151622E+09 | 71536362.23 | 80085864.37 | 0.133396E+09 | 0.105527E+09 |
April | 0.183943E+09 | 0.103017E+09 | 80926353.75 | 0.185824E+09 | 68276020.20 |
May | 0.245940E+09 | 0.141353E+09 | 0.104587E+09 | 0.269191E+09 | 58109684.79 |
June | 0.287621E+09 | 0.186037E+09 | 0.101585E+09 | 0.318804E+09 | 60403786.05 |
July | 0.307739E+09 | 0.216594E+09 | 91144959.21 | 0.336832E+09 | 78246322.69 |
August | 0.255337E+09 | 0.174912E+09 | 80425238.16 | 0.269784E+09 | 82143737.96 |
September | 0.169191E+09 | 0.107067E+09 | 62123521.16 | 0.169266E+09 | 77678718.28 |
October | 0.105426E+09 | 56914896.08 | 48511255.61 | 84569540.87 | 89110946.80 |
November | 59812672.88 | 27291670.98 | 32521001.91 | 27750694.02 | 0.108639E+09 |
December | 40841095.77 | 13813438.40 | 27027657.37 | 6505626.43 | 0.164807E+09 |
Annual Sum or Average | 0.194042E+10 | 0.116041E+10 | 0.780014E+09 | 0.185665E+10 | 0.121347E+10 |
Minimum of Months | 40841095.77 | 13813438.40 | 27027657.37 | 6505626.43 | 58109684.79 |
Maximum of Months | 0.307739E+09 | 0.216594E+09 | 0.104587E+09 | 0.336832E+09 | 0.198280E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52780164.69 | 19696094.93 | 33084069.76 | 9706391.55 | 0.198280E+09 |
February | 80169482.78 | 42176459.88 | 37993022.91 | 45021072.50 | 0.122244E+09 |
March | 0.151622E+09 | 71536362.23 | 80085864.37 | 0.133396E+09 | 0.105527E+09 |
April | 0.183943E+09 | 0.103017E+09 | 80926353.75 | 0.185824E+09 | 68276020.20 |
May | 0.245940E+09 | 0.141353E+09 | 0.104587E+09 | 0.269191E+09 | 58109684.79 |
June | 0.287621E+09 | 0.186037E+09 | 0.101585E+09 | 0.318804E+09 | 60403786.05 |
July | 0.307739E+09 | 0.216594E+09 | 91144959.21 | 0.336832E+09 | 78246322.69 |
August | 0.255337E+09 | 0.174912E+09 | 80425238.16 | 0.269784E+09 | 82143737.96 |
September | 0.169191E+09 | 0.107067E+09 | 62123521.16 | 0.169266E+09 | 77678718.28 |
October | 0.105426E+09 | 56914896.08 | 48511255.61 | 84569540.87 | 89110946.80 |
November | 59812672.88 | 27291670.98 | 32521001.91 | 27750694.02 | 0.108639E+09 |
December | 40841095.77 | 13813438.40 | 27027657.37 | 6505626.43 | 0.164807E+09 |
Annual Sum or Average | 0.194042E+10 | 0.116041E+10 | 0.780014E+09 | 0.185665E+10 | 0.121347E+10 |
Minimum of Months | 40841095.77 | 13813438.40 | 27027657.37 | 6505626.43 | 58109684.79 |
Maximum of Months | 0.307739E+09 | 0.216594E+09 | 0.104587E+09 | 0.336832E+09 | 0.198280E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52780164.69 | 19696094.93 | 33084069.76 | 9706391.55 | 0.198280E+09 |
February | 80169482.78 | 42176459.88 | 37993022.91 | 45021072.50 | 0.122244E+09 |
March | 0.151622E+09 | 71536362.23 | 80085864.37 | 0.133396E+09 | 0.105527E+09 |
April | 0.183943E+09 | 0.103017E+09 | 80926353.75 | 0.185824E+09 | 68276020.20 |
May | 0.245940E+09 | 0.141353E+09 | 0.104587E+09 | 0.269191E+09 | 58109684.79 |
June | 0.287621E+09 | 0.186037E+09 | 0.101585E+09 | 0.318804E+09 | 60403786.05 |
July | 0.307739E+09 | 0.216594E+09 | 91144959.21 | 0.336832E+09 | 78246322.69 |
August | 0.255337E+09 | 0.174912E+09 | 80425238.16 | 0.269784E+09 | 82143737.96 |
September | 0.169191E+09 | 0.107067E+09 | 62123521.16 | 0.169266E+09 | 77678718.28 |
October | 0.105426E+09 | 56914896.08 | 48511255.61 | 84569540.87 | 89110946.80 |
November | 59812672.88 | 27291670.98 | 32521001.91 | 27750694.02 | 0.108639E+09 |
December | 40841095.77 | 13813438.40 | 27027657.37 | 6505626.43 | 0.164807E+09 |
Annual Sum or Average | 0.194042E+10 | 0.116041E+10 | 0.780014E+09 | 0.185665E+10 | 0.121347E+10 |
Minimum of Months | 40841095.77 | 13813438.40 | 27027657.37 | 6505626.43 | 58109684.79 |
Maximum of Months | 0.307739E+09 | 0.216594E+09 | 0.104587E+09 | 0.336832E+09 | 0.198280E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52780164.69 | 19696094.93 | 33084069.76 | 9706391.55 | 0.198280E+09 |
February | 80169482.78 | 42176459.88 | 37993022.91 | 45021072.50 | 0.122244E+09 |
March | 0.151622E+09 | 71536362.23 | 80085864.37 | 0.133396E+09 | 0.105527E+09 |
April | 0.183943E+09 | 0.103017E+09 | 80926353.75 | 0.185824E+09 | 68276020.20 |
May | 0.245940E+09 | 0.141353E+09 | 0.104587E+09 | 0.269191E+09 | 58109684.79 |
June | 0.287621E+09 | 0.186037E+09 | 0.101585E+09 | 0.318804E+09 | 60403786.05 |
July | 0.307739E+09 | 0.216594E+09 | 91144959.21 | 0.336832E+09 | 78246322.69 |
August | 0.255337E+09 | 0.174912E+09 | 80425238.16 | 0.269784E+09 | 82143737.96 |
September | 0.169191E+09 | 0.107067E+09 | 62123521.16 | 0.169266E+09 | 77678718.28 |
October | 0.105426E+09 | 56914896.08 | 48511255.61 | 84569540.87 | 89110946.80 |
November | 59812672.88 | 27291670.98 | 32521001.91 | 27750694.02 | 0.108639E+09 |
December | 40841095.77 | 13813438.40 | 27027657.37 | 6505626.43 | 0.164807E+09 |
Annual Sum or Average | 0.194042E+10 | 0.116041E+10 | 0.780014E+09 | 0.185665E+10 | 0.121347E+10 |
Minimum of Months | 40841095.77 | 13813438.40 | 27027657.37 | 6505626.43 | 58109684.79 |
Maximum of Months | 0.307739E+09 | 0.216594E+09 | 0.104587E+09 | 0.336832E+09 | 0.198280E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 31.77 | 885.15 | 154.38 | 49.05 | 105.34 | 0.00 | 0.00 |
February | 124.04 | 614.26 | 252.05 | 100.66 | 151.39 | 0.00 | 0.00 |
March | 188.33 | 483.12 | 339.77 | 96.45 | 243.32 | 0.00 | 0.00 |
April | 344.29 | 313.72 | 430.45 | 151.83 | 278.63 | 0.00 | 0.00 |
May | 483.69 | 253.05 | 538.72 | 199.79 | 338.93 | 0.00 | 0.00 |
June | 587.41 | 194.57 | 594.52 | 226.57 | 367.95 | 0.00 | 0.00 |
July | 649.48 | 187.73 | 594.60 | 249.82 | 344.77 | 0.00 | 0.00 |
August | 526.00 | 206.52 | 499.38 | 199.28 | 300.10 | 0.00 | 0.00 |
September | 376.06 | 264.57 | 395.84 | 162.77 | 233.07 | 0.00 | 0.00 |
October | 209.30 | 344.73 | 284.38 | 114.61 | 169.77 | 0.00 | 0.00 |
November | 97.37 | 497.37 | 199.52 | 80.85 | 118.68 | 0.00 | 0.00 |
December | 29.96 | 733.50 | 137.52 | 46.06 | 91.46 | 0.00 | 0.00 |
Annual Sum or Average | 304.94 | 414.29 | 368.98 | 139.96 | 229.02 | 0.00 | 0.00 |
Minimum of Months | 29.96 | 187.73 | 137.52 | 46.06 | 91.46 | 0.00 | 0.00 |
Maximum of Months | 649.48 | 885.15 | 594.60 | 249.82 | 367.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 36.24 | 740.29 | 197.06 | 73.54 | 123.52 | 0.00 | 0.00 |
February | 186.10 | 505.31 | 331.39 | 174.34 | 157.05 | 0.00 | 0.00 |
March | 498.04 | 393.99 | 566.09 | 267.09 | 299.01 | 0.00 | 0.00 |
April | 716.91 | 263.41 | 709.66 | 397.44 | 312.22 | 0.00 | 0.00 |
May | 1005.05 | 216.96 | 918.24 | 527.75 | 390.48 | 0.00 | 0.00 |
June | 1229.95 | 233.04 | 1109.65 | 717.73 | 391.92 | 0.00 | 0.00 |
July | 1257.59 | 292.14 | 1148.97 | 808.67 | 340.30 | 0.00 | 0.00 |
August | 1007.26 | 306.69 | 953.32 | 653.05 | 300.27 | 0.00 | 0.00 |
September | 653.03 | 299.69 | 652.74 | 413.07 | 239.67 | 0.00 | 0.00 |
October | 315.75 | 332.70 | 393.62 | 212.50 | 181.12 | 0.00 | 0.00 |
November | 107.06 | 419.13 | 230.76 | 105.29 | 125.47 | 0.00 | 0.00 |
December | 24.29 | 615.32 | 152.48 | 51.57 | 100.91 | 0.00 | 0.00 |
Annual Sum or Average | 588.74 | 384.79 | 615.30 | 367.96 | 247.34 | 0.00 | 0.00 |
Minimum of Months | 24.29 | 216.96 | 152.48 | 51.57 | 100.91 | 0.00 | 0.00 |
Maximum of Months | 1257.59 | 740.29 | 1148.97 | 808.67 | 391.92 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 85079650.33 | 0.237079E+10 | 0.413500E+09 | 0.131364E+09 | 0.282136E+09 | 0.00 | 0.00 |
February | 0.300088E+09 | 0.148602E+10 | 0.609760E+09 | 0.243524E+09 | 0.366237E+09 | 0.00 | 0.00 |
March | 0.504423E+09 | 0.129399E+10 | 0.910051E+09 | 0.258341E+09 | 0.651710E+09 | 0.00 | 0.00 |
April | 0.892403E+09 | 0.813158E+09 | 0.111574E+10 | 0.393537E+09 | 0.722201E+09 | 0.00 | 0.00 |
May | 0.129552E+10 | 0.677775E+09 | 0.144291E+10 | 0.535123E+09 | 0.907791E+09 | 0.00 | 0.00 |
June | 0.152258E+10 | 0.504326E+09 | 0.154099E+10 | 0.587270E+09 | 0.953721E+09 | 0.00 | 0.00 |
July | 0.173957E+10 | 0.502803E+09 | 0.159257E+10 | 0.669131E+09 | 0.923443E+09 | 0.00 | 0.00 |
August | 0.140883E+10 | 0.553153E+09 | 0.133754E+10 | 0.533738E+09 | 0.803798E+09 | 0.00 | 0.00 |
September | 0.974741E+09 | 0.685767E+09 | 0.102602E+10 | 0.421900E+09 | 0.604117E+09 | 0.00 | 0.00 |
October | 0.560580E+09 | 0.923326E+09 | 0.761684E+09 | 0.306962E+09 | 0.454722E+09 | 0.00 | 0.00 |
November | 0.252371E+09 | 0.128920E+10 | 0.517165E+09 | 0.209556E+09 | 0.307609E+09 | 0.00 | 0.00 |
December | 80257383.68 | 0.196461E+10 | 0.368345E+09 | 0.123373E+09 | 0.244972E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.961645E+10 | 0.130649E+11 | 0.116363E+11 | 0.441382E+10 | 0.722246E+10 | 0.00 | 0.00 |
Minimum of Months | 80257383.68 | 0.502803E+09 | 0.368345E+09 | 0.123373E+09 | 0.244972E+09 | 0.00 | 0.00 |
Maximum of Months | 0.173957E+10 | 0.237079E+10 | 0.159257E+10 | 0.669131E+09 | 0.953721E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 97063915.50 | 0.198280E+10 | 0.527802E+09 | 0.196961E+09 | 0.330841E+09 | 0.00 | 0.00 |
February | 0.450210E+09 | 0.122244E+10 | 0.801695E+09 | 0.421765E+09 | 0.379930E+09 | 0.00 | 0.00 |
March | 0.133396E+10 | 0.105527E+10 | 0.151622E+10 | 0.715364E+09 | 0.800859E+09 | 0.00 | 0.00 |
April | 0.185824E+10 | 0.682759E+09 | 0.183943E+10 | 0.103017E+10 | 0.809264E+09 | 0.00 | 0.00 |
May | 0.269191E+10 | 0.581097E+09 | 0.245940E+10 | 0.141353E+10 | 0.104587E+10 | 0.00 | 0.00 |
June | 0.318804E+10 | 0.604038E+09 | 0.287621E+10 | 0.186037E+10 | 0.101585E+10 | 0.00 | 0.00 |
July | 0.336832E+10 | 0.782461E+09 | 0.307739E+10 | 0.216594E+10 | 0.911450E+09 | 0.00 | 0.00 |
August | 0.269784E+10 | 0.821434E+09 | 0.255337E+10 | 0.174912E+10 | 0.804252E+09 | 0.00 | 0.00 |
September | 0.169265E+10 | 0.776787E+09 | 0.169191E+10 | 0.107067E+10 | 0.621235E+09 | 0.00 | 0.00 |
October | 0.845695E+09 | 0.891109E+09 | 0.105426E+10 | 0.569149E+09 | 0.485113E+09 | 0.00 | 0.00 |
November | 0.277507E+09 | 0.108639E+10 | 0.598127E+09 | 0.272917E+09 | 0.325210E+09 | 0.00 | 0.00 |
December | 65055152.18 | 0.164807E+10 | 0.408411E+09 | 0.138134E+09 | 0.270277E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.185665E+11 | 0.121347E+11 | 0.194042E+11 | 0.116041E+11 | 0.780014E+10 | 0.00 | 0.00 |
Minimum of Months | 65055152.18 | 0.581097E+09 | 0.408411E+09 | 0.138134E+09 | 0.270277E+09 | 0.00 | 0.00 |
Maximum of Months | 0.336832E+10 | 0.198280E+10 | 0.307739E+10 | 0.216594E+10 | 0.104587E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.8 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -4.9 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.8 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.37 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.04 | 4.91 | 4.56 | 5.04 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.44 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.02 | 4.61 | 4.29 | 7.18 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.07 | 4.37 | 5.43 | 3.41 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.8 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.4 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.40 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.8 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.44 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.15 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.20 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.65 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.64 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.19 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.36 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.25 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.61 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.25 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.37 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.15 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.47 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.15 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.61 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.0 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.6 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.4 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.98 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.5 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.5 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.0 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.17 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.20 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.92 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.00 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.19 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.18 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.19 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.61 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.11 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.58 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.87 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.61 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.17 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.11 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.47 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.15 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.49 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.84 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.60 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.75 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.73 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.09 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.77 | 2.10 | 4.06 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.87 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.80 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.15 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.09 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.104534E+10 | -957254804.0 | 0.00 | 0.00 | 744.00 | 0.00 | -88081423.7 | 58.99 | 0.00 | 0.00 |
February | 0.974004E+09 | -894741042.6 | 0.00 | 0.00 | 672.00 | 0.00 | -79262571.1 | 58.99 | 0.00 | 0.00 |
March | 0.112224E+10 | -.103500E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87240453.9 | 58.99 | 0.00 | 0.00 |
April | 0.100934E+10 | -926363347.0 | 0.00 | 0.00 | 720.00 | 0.00 | -82973105.9 | 58.99 | 0.00 | 0.00 |
May | 0.992790E+09 | -910532863.2 | 0.00 | 0.00 | 744.00 | 0.00 | -82257499.9 | 58.99 | 0.00 | 0.00 |
June | 0.924612E+09 | -851145866.4 | 0.00 | 0.00 | 720.00 | 0.00 | -73466456.1 | 58.99 | 0.00 | 0.00 |
July | 0.853157E+09 | -780888033.2 | 0.00 | 0.00 | 744.00 | 0.00 | -72268606.8 | 58.99 | 0.00 | 0.00 |
August | 0.893034E+09 | -819665296.8 | 0.00 | 0.00 | 744.00 | 0.00 | -73368250.0 | 58.99 | 0.00 | 0.00 |
September | 0.847171E+09 | -772426792.5 | 0.00 | 0.00 | 720.00 | 0.00 | -74743805.7 | 58.99 | 0.00 | 0.00 |
October | 0.893943E+09 | -810586646.3 | 0.00 | 0.00 | 744.00 | 0.00 | -83356094.6 | 58.99 | 0.00 | 0.00 |
November | 0.911549E+09 | -827634442.6 | 0.00 | 0.00 | 720.00 | 0.00 | -83914208.6 | 58.99 | 0.00 | 0.00 |
December | 0.100252E+10 | -914644513.4 | 0.00 | 0.00 | 744.00 | 0.00 | -87878251.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.114697E+11 | -.105009E+11 | 8760.00 | -968810727.8 | 58.99 | |||||
Minimum of Months | 0.847171E+09 | -.103500E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -88081423.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.112224E+10 | -772426792.5 | 0.00 | 0.00 | 744.00 | 0.00 | -72268606.8 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 304.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 385.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 417.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 421.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 352.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 317.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 269.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 236.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3965.83 | ||||||||||
Minimum of Months | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.133244E+11 | 28082.48 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.868788E+10 | 28082.48 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.762964E+10 | 28082.48 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.373905E+10 | 28082.48 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.246731E+10 | 28082.48 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137838E+09 | 28082.48 | 17-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23866707.23 | 8682.47 | 18-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.661553E+09 | 28082.48 | 13-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.196639E+10 | 28082.48 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.526465E+10 | 28082.48 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.951935E+10 | 28082.48 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.534219E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.133244E+11 | 28082.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.707005E+11 | 81581.77 | 01-JAN-01:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.421281E+11 | 81581.77 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.327678E+11 | 81581.77 | 01-MAR-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125726E+11 | 81581.77 | 01-APR-00:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.739755E+10 | 81581.77 | 01-MAY-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.123973E+10 | 81581.77 | 20-SEP-03:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.609049E+10 | 81581.77 | 08-OCT-03:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.272896E+11 | 81581.77 | 01-NOV-00:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.517861E+11 | 81581.77 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.251973E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.707005E+11 | 81581.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.182519E+12 | 171176.92 | 05-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.952269E+11 | 124375.50 | 03-FEB-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.628066E+11 | 128118.18 | 04-MAR-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.658926E+10 | 58971.61 | 29-APR-04:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.611434E+10 | 54155.74 | 08-MAY-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.558320E+09 | 22057.64 | 11-OCT-05:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.462418E+11 | 112829.91 | 27-NOV-04:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119288E+12 | 171176.92 | 31-DEC-02:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.519344E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.182519E+12 | 171176.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.338527E+09 | 0.337630E+09 | 5795.58 | 20-MAY-16:00 | 5795.58 | 0.00 |
June | 0.00 | 0.00 | 0.231748E+10 | 0.223033E+10 | 17175.36 | 22-JUN-05:03 | 12879.73 | 0.00 |
July | 0.00 | 0.00 | 0.519099E+10 | 0.503494E+10 | 18869.82 | 19-JUL-05:01 | 12562.72 | 0.00 |
August | 0.00 | 0.00 | 0.417574E+10 | 0.414551E+10 | 16646.65 | 08-AUG-05:01 | 16063.60 | 0.00 |
September | 0.00 | 0.00 | 0.150712E+10 | 0.138974E+10 | 17708.07 | 07-SEP-05:01 | 11677.14 | 0.00 |
October | 0.00 | 0.00 | 49239133.48 | 49239133.48 | 3665.95 | 18-OCT-16:00 | 3665.95 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.135791E+11 | 0.131874E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.519099E+10 | 0.503494E+10 | 18869.82 | 16063.60 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 39019063.85 | 39019063.85 | 4952.69 | 20-MAY-16:00 | 4952.69 | 0.00 |
June | 0.00 | 0.00 | 0.317293E+10 | 0.306207E+10 | 51243.62 | 22-JUN-18:11 | 41550.37 | 0.00 |
July | 0.00 | 0.00 | 0.100193E+11 | 0.982043E+10 | 51580.38 | 16-JUL-09:51 | 38892.89 | 0.00 |
August | 0.00 | 0.00 | 0.712437E+10 | 0.709970E+10 | 46708.00 | 07-AUG-19:50 | 46708.00 | 0.00 |
September | 0.00 | 0.00 | 0.225875E+10 | 0.209795E+10 | 52675.56 | 06-SEP-17:40 | 38768.44 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.226144E+11 | 0.221192E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.100193E+11 | 0.982043E+10 | 52675.56 | 46708.00 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.113483E+10 | 0.08 | 437.74 | 01-JAN-00:03 | 0.09 |
February | 0.881863E+09 | 0.07 | 437.74 | 01-FEB-00:01 | 0.09 |
March | 0.826932E+09 | 0.06 | 437.74 | 01-MAR-00:03 | 0.09 |
April | 0.188676E+09 | 0.01 | 437.74 | 01-APR-00:10 | 0.09 |
May | 0.129666E+09 | 0.01 | 437.74 | 01-MAY-00:05 | 0.09 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 22193225.88 | 0.00 | 437.74 | 10-OCT-04:00 | 0.09 |
November | 0.513049E+09 | 0.04 | 437.74 | 10-NOV-02:58 | 0.09 |
December | 0.104091E+10 | 0.08 | 437.74 | 01-DEC-00:02 | 0.09 |
Annual Sum or Average | 0.473812E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113483E+10 | 0.08 | 437.74 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139312E+10 | 0.77 | 1244.32 | 02-JAN-06:01 | 1.07 |
February | 0.122637E+10 | 0.65 | 1244.32 | 01-FEB-06:01 | 1.07 |
March | 0.140492E+10 | 0.57 | 1244.32 | 28-MAR-10:50 | 1.07 |
April | 0.126662E+10 | 0.45 | 1244.32 | 12-APR-08:00 | 1.07 |
May | 0.130821E+10 | 0.45 | 1244.32 | 01-MAY-05:01 | 1.07 |
June | 0.128483E+10 | 0.43 | 1244.32 | 10-JUN-10:40 | 1.07 |
July | 0.124870E+10 | 0.40 | 1244.32 | 12-JUL-08:40 | 1.07 |
August | 0.134524E+10 | 0.43 | 1244.32 | 26-AUG-07:30 | 1.07 |
September | 0.124556E+10 | 0.42 | 1244.32 | 19-SEP-14:00 | 1.07 |
October | 0.125187E+10 | 0.42 | 1244.32 | 02-OCT-05:01 | 1.07 |
November | 0.123412E+10 | 0.50 | 1244.32 | 06-NOV-10:10 | 1.07 |
December | 0.133257E+10 | 0.67 | 1244.32 | 19-DEC-16:00 | 1.07 |
Annual Sum or Average | 0.155421E+11 | 0.51 | |||
Minimum of Months | 0.122637E+10 | 0.40 | 1244.32 | 1.07 | |
Maximum of Months | 0.140492E+10 | 0.77 | 1244.32 | 1.07 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.436868E+10 | 0.91 | 2767.57 | 02-JAN-12:00 | 1.03 |
February | 0.360108E+10 | 0.90 | 2767.57 | 08-FEB-10:00 | 1.03 |
March | 0.388246E+10 | 0.89 | 2767.57 | 03-MAR-14:10 | 1.03 |
April | 0.313394E+10 | 0.73 | 2767.57 | 04-APR-06:10 | 1.03 |
May | 0.308010E+10 | 0.56 | 2767.57 | 03-MAY-06:30 | 1.03 |
June | 0.286694E+10 | 0.41 | 2767.57 | 20-JUN-16:20 | 1.01 |
July | 0.286357E+10 | 0.43 | 2767.57 | 03-JUL-09:40 | 1.02 |
August | 0.303696E+10 | 0.44 | 2767.57 | 02-AUG-14:10 | 1.02 |
September | 0.282427E+10 | 0.45 | 2767.57 | 05-SEP-15:10 | 1.02 |
October | 0.293315E+10 | 0.56 | 2767.57 | 04-OCT-07:00 | 1.03 |
November | 0.341730E+10 | 0.83 | 2767.57 | 02-NOV-09:10 | 1.03 |
December | 0.407135E+10 | 0.92 | 2767.57 | 02-DEC-09:00 | 1.03 |
Annual Sum or Average | 0.400798E+11 | 0.67 | |||
Minimum of Months | 0.282427E+10 | 0.41 | 2767.57 | 1.01 | |
Maximum of Months | 0.436868E+10 | 0.92 | 2767.57 | 1.03 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.77 | 0.00 |
February | 2.77 | 0.00 |
March | 2.42 | 0.02 |
April | 1.10 | 0.16 |
May | 0.96 | 0.17 |
June | 1.67 | 2.32 |
July | 3.43 | 0.52 |
August | 3.50 | 1.10 |
September | 1.64 | 1.11 |
October | 0.82 | 1.14 |
November | 1.67 | 0.01 |
December | 2.59 | 0.00 |
Annual Sum or Average | 25.32 | 0.50 |
Minimum of Months | 0.82 | 0.00 |
Maximum of Months | 3.50 | 2.32 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.17 | 0.00 |
February | 0.00 | 0.00 |
March | 0.17 | 0.00 |
April | 0.00 | 0.00 |
May | 0.25 | 0.00 |
June | 0.67 | 0.00 |
July | 2.40 | 0.00 |
August | 0.46 | 0.00 |
September | 0.17 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 4.28 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.40 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.08 | 0.00 |
July | 0.10 | 0.00 |
August | 0.76 | 0.00 |
September | 0.08 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 1.03 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.76 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.139312E+10 | 0.187343E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.122637E+10 | 0.124055E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.140492E+10 | 0.110253E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.126662E+10 | 0.545414E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.141313E+10 | 0.359744E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.200224E+10 | 0.207028E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.286606E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.265030E+10 | 36266828.93 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.170545E+10 | 0.975983E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.126690E+10 | 0.288624E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.123412E+10 | 0.762810E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.133257E+10 | 0.136196E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.197618E+11 | 0.765698E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.122637E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.286606E+10 | 0.187343E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.436868E+10 | 0.982816E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.360108E+10 | 0.600760E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.388246E+10 | 0.470543E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.313394E+10 | 0.184138E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.309264E+10 | 0.107432E+11 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.384017E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.597762E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.528723E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.353090E+10 | 0.184152E+10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.293315E+10 | 0.896954E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.341730E+10 | 0.392169E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.407135E+10 | 0.736650E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.471365E+11 | 0.358262E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.293315E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.597762E+10 | 0.982816E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.139312E+10 | 0.00 | 0.133244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122637E+10 | 0.00 | 0.868788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140492E+10 | 0.00 | 0.762964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126662E+10 | 0.00 | 0.373905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130821E+10 | 0.338527E+09 | 0.246731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128483E+10 | 0.231748E+10 | 0.137838E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.124870E+10 | 0.519099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134524E+10 | 0.417574E+10 | 23866707.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124556E+10 | 0.150712E+10 | 0.661553E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125187E+10 | 49239133.48 | 0.196639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123412E+10 | 0.00 | 0.526465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133257E+10 | 0.00 | 0.951935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155421E+11 | 0.135791E+11 | 0.534219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140492E+10 | 0.519099E+10 | 0.133244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.436868E+10 | 0.00 | 0.707005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.360108E+10 | 0.00 | 0.421281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388246E+10 | 0.00 | 0.327678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.313394E+10 | 0.00 | 0.125726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.308010E+10 | 39019063.85 | 0.739755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.286694E+10 | 0.317293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.286357E+10 | 0.100193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.303696E+10 | 0.712437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.282427E+10 | 0.225875E+10 | 0.123973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.293315E+10 | 0.00 | 0.609049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.341730E+10 | 0.00 | 0.272896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.407135E+10 | 0.00 | 0.517861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.400798E+11 | 0.226144E+11 | 0.251973E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.282427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.436868E+10 | 0.100193E+11 | 0.707005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.139312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130821E+10 | 0.00 | 0.00 | 0.00 | 0.104913E+09 | 0.00 | 0.359744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128483E+10 | 0.00 | 0.00 | 0.00 | 0.717408E+09 | 0.00 | 0.207028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.124870E+10 | 0.00 | 0.00 | 0.00 | 0.161736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134524E+10 | 0.00 | 0.00 | 0.00 | 0.130506E+10 | 0.00 | 36266828.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124556E+10 | 0.00 | 0.00 | 0.00 | 0.459891E+09 | 0.00 | 0.975983E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125187E+10 | 0.00 | 0.00 | 0.00 | 15036325.69 | 0.00 | 0.288624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155421E+11 | 0.00 | 0.00 | 0.00 | 0.421967E+10 | 0.00 | 0.765698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.122637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140492E+10 | 0.00 | 0.00 | 0.00 | 0.161736E+10 | 0.00 | 0.187343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.436868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.360108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.313394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.308010E+10 | 0.00 | 0.00 | 0.00 | 12532122.88 | 0.00 | 0.107432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.286694E+10 | 0.00 | 0.00 | 0.00 | 0.973230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.286357E+10 | 0.00 | 0.00 | 0.00 | 0.311405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.303696E+10 | 0.00 | 0.00 | 0.00 | 0.225027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.282427E+10 | 0.00 | 0.00 | 0.00 | 0.706637E+09 | 0.00 | 0.184152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.293315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.896954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.341730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.407135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.400798E+11 | 0.00 | 0.00 | 0.00 | 0.705671E+10 | 0.00 | 0.358262E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.282427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.436868E+10 | 0.00 | 0.00 | 0.00 | 0.311405E+10 | 0.00 | 0.982816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337341E+10 | 0.00 | 0.00 | 0.14 |
February | 28762610.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235977E+10 | 0.00 | 0.00 | 0.15 |
March | 21476358.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228526E+10 | 0.00 | 0.00 | 0.16 |
April | 0.244952E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125837E+10 | 0.00 | 0.00 | 0.15 |
May | 0.406142E+09 | 6926728.53 | 979841.86 | 306355.59 | 1699294.89 | 0.789637E+09 | 0.262326E+09 | 4337.32 | 0.24 |
June | 0.281194E+09 | 0.108889E+09 | 0.00 | 2364235.64 | 0.00 | 12622991.03 | 0.131912E+10 | 0.00 | 0.47 |
July | 23538383.43 | 0.245136E+09 | 0.00 | 5152200.28 | 0.00 | 0.00 | 0.128858E+10 | 0.00 | 0.49 |
August | 85030850.43 | 0.178671E+09 | 0.00 | 4712748.01 | 0.00 | 6241843.91 | 0.158753E+10 | 0.00 | 0.55 |
September | 0.384660E+09 | 74158604.72 | 0.00 | 2185239.23 | 0.00 | 0.207583E+09 | 0.104981E+10 | 0.00 | 0.39 |
October | 0.602589E+09 | 1246098.48 | 0.00 | 67406.49 | 0.00 | 0.696136E+09 | 0.106971E+09 | 0.00 | 0.18 |
November | 0.154267E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166755E+10 | 0.00 | 0.00 | 0.14 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276431E+10 | 0.00 | 0.00 | 0.15 |
Annual Sum or Average | 0.223261E+10 | 0.615028E+09 | 979841.86 | 14788185.25 | 1699294.89 | 0.154209E+11 | 0.561434E+10 | 4337.32 | 0.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.602589E+09 | 0.245136E+09 | 979841.86 | 5152200.28 | 1699294.89 | 0.337341E+10 | 0.158753E+10 | 4337.32 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 84015528.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770478E+10 | 0.00 | 0.00 | 0.14 |
February | 0.495684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464008E+10 | 0.00 | 0.00 | 0.15 |
March | 0.152762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312416E+10 | 0.00 | 0.00 | 0.16 |
April | 0.173503E+10 | 0.00 | 0.00 | 0.00 | 3940633.90 | 0.109968E+10 | 0.00 | 0.00 | 0.15 |
May | 0.212483E+10 | 1432114.94 | 0.00 | 0.00 | 19515493.36 | 0.464470E+09 | 0.00 | 0.00 | 0.15 |
June | 0.167640E+10 | 0.169682E+09 | 0.00 | 1624473.81 | 6284776.78 | 0.00 | 0.442617E+09 | 0.00 | 0.24 |
July | 0.587772E+09 | 0.415354E+09 | 0.00 | 7234429.54 | 0.00 | 0.00 | 0.189548E+10 | 0.00 | 0.37 |
August | 0.102892E+10 | 0.322402E+09 | 0.00 | 3167504.93 | 0.00 | 0.00 | 0.145135E+10 | 0.00 | 0.33 |
September | 0.159678E+10 | 0.113009E+09 | 0.00 | 1039583.58 | 7316882.85 | 79482629.96 | 0.474220E+09 | 0.00 | 0.21 |
October | 0.196515E+10 | 0.00 | 0.00 | 0.00 | 10490173.07 | 0.439057E+09 | 0.00 | 0.00 | 0.15 |
November | 0.129487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222252E+10 | 0.00 | 0.00 | 0.14 |
December | 0.317234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.568759E+10 | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.144343E+11 | 0.102188E+10 | 0.00 | 13065991.86 | 47547959.96 | 0.254618E+11 | 0.426367E+10 | 0.00 | 0.19 |
Minimum of Months | 84015528.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.212483E+10 | 0.415354E+09 | 0.00 | 7234429.54 | 19515493.36 | 0.770478E+10 | 0.189548E+10 | 0.00 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |