Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2020-06-03 19:11:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1140.34 | 235.85 | 235.85 |
Net Site Energy | 1140.34 | 235.85 | 235.85 |
Total Source Energy | 2931.83 | 606.36 | 606.36 |
Net Source Energy | 2931.83 | 606.36 | 606.36 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 326.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.78 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 814.07 | 326.28 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 326.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 6.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 42.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25.78 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 123.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 15.60 | 67.48 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 168.36 | 67.48 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 123.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 15.60 | 67.48 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 168.36 | 67.48 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 814.067 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 814.067 | 100.00 |
Total On-Site and Utility Electric Sources | 814.067 | 100.00 |
Total Electricity End Uses | 814.067 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 48.67 |
Time Setpoint Not Met During Occupied Cooling | 0.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1814.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.6337 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.5069 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.5069 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-14:00 | 19-FEB-07:10 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 140206.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 10034.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3288.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1756.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 60381.02 | 140206.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 140206.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 10034.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 3288.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1756.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 353.68 | 0.00 | 0.00 | 0.00 |
Cooling | 21.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1507.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 390.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 135.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 81.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2578.15 | 353.68 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 73.15 | 0.00 | 0.00 | 0.00 |
Cooling | 4.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 533.21 | 73.15 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 73.15 | 0.00 | 0.00 | 0.00 |
Cooling | 4.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 533.21 | 73.15 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.950086 |
ZONE2 FINE STORAGE DIRECT AIR | 2.01 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 2.15 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 2.15 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 88021.48 |
PSZ-OFFICE HEATING COIL | 25099.05 |
PSZ-FINE STORAGE HEATING COIL | 67077.37 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 88021.48 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.950086 | 0.950086 | 0.950086 | 0.950086 | 0.950086 | 0.950086 | 1.00 | 1.00 | 0.950086 |
PSZ-FINE STORAGE | 2.01 | 2.01 | 2.01 | 2.01 | 2.01 | 2.01 | 1.00 | 1.00 | 2.01 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 0.950086 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 2.01 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.950086 | 0.950086 | 0.950086 | 0.950086 | 15727.30 | 25099.05 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.01 | 2.01 | 2.01 | 2.01 | 39825.53 | 67077.37 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.950090 | 0.475045 | 0.950090 | 15727.36 | 15727.30 | 7863.65 | 15727.30 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 2.01 | 1.01 | 2.01 | 37686.12 | 39825.53 | 19912.76 | 39825.53 | 0.738844 | 0.738840 | 0.738840 | 0.738840 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.950086 | 1083.20 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.01 | 2204.85 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.634 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.707 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.507 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.507 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.507 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.066 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2518.900 | 10.634 | 503.780 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2518.900 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11853.648 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11853.648 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27263.390 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27263.390 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.3378 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.3378 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.3378 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.861 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.861 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.861 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
5 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
6 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
7 | 4 | 0.81105908E-12 | -0.61566660E-16 | 0.53970606E-14 | 0.11182789E-15 |
8 | 3 | -0.39455327E-03 | 0.24003309E-06 | -0.57329053E-04 | 0.15561420E-12 |
9 | 2 | 1.7627212 | 0.51935632E-02 | 1.1580856 | -0.75642783E-04 |
10 | 1 | -7.0983380 | 0.13367505 | -17.210522 | 0.33785533 |
11 | 0 | 5.5597362 | 0.84856002E-01 | 16.276219 | |
12 | 4 | 0.81105908E-12 | -0.61566660E-16 | 0.53970606E-14 | 0.11182789E-15 |
13 | 3 | -0.39455327E-03 | 0.24003309E-06 | -0.57329053E-04 | 0.15561420E-12 |
14 | 2 | 1.7627212 | 0.51935632E-02 | 1.1580856 | -0.75642783E-04 |
15 | 1 | -7.0983380 | 0.13367505 | -17.210522 | 0.33785533 |
16 | 0 | 5.5597362 | 0.84856002E-01 | 16.276219 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.53970606E-14 | -0.61566660E-16 | 0.81105908E-12 | 0.11182789E-15 |
85 | 3 | -0.57329053E-04 | 0.24003309E-06 | -0.39455327E-03 | 0.15561420E-12 |
86 | 2 | 1.1580856 | 0.51935632E-02 | 1.7627212 | -0.75642783E-04 |
87 | 1 | -17.210522 | 0.13367505 | -7.0983380 | 0.33785533 |
88 | 0 | 16.276219 | 0.84856002E-01 | 5.5597362 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.52_SHGC_0.4 | 28 | 1 | VerySmooth | 2.956 | 0.395 | 0.315 | 0.401 |
2 | SKYLIGHT_U_0.6_SHGC_0.4 | 29 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 30 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.66926E-002 | 0.31435 | 0.46310 | 0.46310 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 9.92378E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9486.81128 | 11384.17354 | 0.79174 | 0.95009 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.79438E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 9173.04750 | 11007.65700 | 0.26110 | 0.31332 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -4.20000 | 2.69032E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 25804.72837 | 30965.67405 | 1.67873 | 2.01447 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 29.40000 | 8.79438E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 34812.91717 | 41775.50060 | 0.83498 | 1.00198 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40000 | 8.79438E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 73351.23391 | 88021.48069 | 1.79154 | 2.14984 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | -4.20000 | 2.69032E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 14065.31 | 0.95009 | 0.95009 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 10706.21 | 0.31332 | 0.31332 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 36460.11 | 2.01447 | 2.01447 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 37554.99 | 1.00198 | 1.00198 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.95009 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.01447 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.14984 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 2.14984 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 88021.48336 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 88021.48069 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.95009 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.95009 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.95009 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.95009 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.95009 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.95009 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.01447 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.01447 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.01447 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.01447 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.01447 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.01447 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.95009 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.01447 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.95009 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.95009 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.95009 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.95009 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.95009 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.95009 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47505 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.95009 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 15727.36302 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 15727.30000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 7863.65000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 15727.30000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15727.30000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25099.05385 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.95009 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1083.20283 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 25099.05385 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.01447 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.01447 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.01447 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.01447 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.01447 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.01447 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.00724 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.01447 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 37686.11843 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 39825.53000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 19912.76500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 39825.53000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73884 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73884 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73884 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73884 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 39825.53000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 67077.37153 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.01447 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2204.85120 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 67077.37153 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 14990.1 | 9.21 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 38261.3 | 13.69 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 14 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1534692933 | 0.1694416178 | Pass | Pass | 7.5855660217E-002 | 0.3568975286 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.4732891824 | 0.4395496987 | Pass | Pass | 0.4004264274 | 0.6053377688 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 2.6625378617E-005 | 3.9241651333E-005 | Pass | Pass | 6.2468807269E-002 | 7.2399403685E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.322 | 0.338 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.322 | 0.338 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.322 | 0.338 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.369 | 0.389 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.52_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.956 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.52_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.956 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.52_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.956 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.52_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.956 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.164 | 0.395 | 0.401 | ||||||||||||
North Total or Average | 6.51 | 2.956 | 0.395 | 0.401 | ||||||||||||
Non-North Total or Average | 26.02 | 3.216 | 0.395 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.6337 | 236.88 | 2518.90 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.62 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.5069 | 1393.41 | 11853.65 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 135.00 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.5069 | 3204.84 | 27263.39 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 310.50 |
Interior Lighting Total | 8.6111 | 4835.13 | 41635.94 | 476.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.00 | AstronomicalClock | - | 83.55 | 83.55 | 123.22 | |
Exterior Lighting Total | 7857.00 | 123.22 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15727.30 | 12560.77 | 3166.53 | 0.80 | 3.15 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 39825.53 | 29424.69 | 10400.84 | 0.74 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 14990.1 | 9.21 | ||||
PSZ-FINE STORAGE COOLING COIL | 38261.3 | 13.69 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 88021.48 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 25099.05 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 67077.37 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.15 | 199.74 | 92.91 | 1.00 | 3.54 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 0.95 | 1083.20 | 1140.11 | 1.00 | 1.37 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.01 | 2204.85 | 1094.51 | 1.00 | 1.28 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9486.81 | 11384.17 | 48.06 | 0.792 | 0.950 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23.90 | 23.90 | 0.00815 | 27.94 | 0.00879 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 25804.73 | 30965.67 | 22.22 | 1.679 | 2.014 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 26.70 | 26.70 | 0.00810 | 29.40 | 0.00879 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00383 | 29.40 | 0.00879 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9173.05 | 11007.66 | 46.47 | 0.261 | 0.313 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00726 | -4.20 | 0.00269 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 34812.92 | 41775.50 | 29.98 | 0.835 | 1.002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15.56 | 15.55 | 0.00562 | -4.20 | 0.00269 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 73351.23 | 88021.48 | 27.47 | 1.792 | 2.150 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 10.00 | 9.99 | 0.00774 | -4.20 | 0.00269 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.95 | 0.95 | 0.31 | 0.31 | 0.9501 | 0.9501 | 0.9501 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.01 | 2.01 | 1.00 | 1.00 | 2.0145 | 2.0145 | 2.0145 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 88021.483 | 88021.483 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 88021.48 | 88021.48 | 2.149844 | 4.62 | 4.62 | 0.00582767 | 43.33 | 26.92 | 0.01600000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 9.99 | 0.00773955 | 99.9999 | 88021.48 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 15727.300 | 0.000 | 0.950090 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 15727.30 | 15093.36 | 0.950090 | 24.41 | 16.14 | 0.00823430 | 12.00 | 11.13 | 0.00800000 | 27.94 | 0.00879438 | 17.82 | 12.6657 | 23.90 | 0.00815308 | 43.5487 | 9486.81 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 25099.054 | 25099.054 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 25099.05 | 25099.05 | 0.950086 | 11.35 | 8.13 | 0.00550656 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 12.6657 | 21.10 | 0.00726260 | 46.0579 | 9173.05 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 39825.530 | 0.000 | 2.014470 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 39825.53 | 38544.06 | 2.014470 | 27.17 | 17.09 | 0.00822180 | 12.00 | 11.13 | 0.00800000 | 29.40 | 0.00879438 | 18.30 | 17.5693 | 26.70 | 0.00809976 | 36.6292 | 25804.73 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 67077.372 | 67077.372 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 67077.37 | 67077.37 | 2.014472 | 8.58 | 5.69 | 0.00458706 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 17.5692 | 15.55 | 0.00562294 | 50.6364 | 34812.92 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 88021.483 | 88021.483 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1870 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 2.149844 | 2.55184464 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 88021.48 | 88021.48 | 1.0000 | 2.55184464 | 2.149844 | 4.62 | 4.62 | 0.00582767 | 19266.0 | 43.33 | 26.92 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 88021.48 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 9.99 | 0.00773955 | 9.99 | 0.00773955 | 99.9999 | 88021.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15727.300 | 0.000 | 0.950090 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1472 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 15727.30 | 15093.36 | 1.0000 | 1.12774807 | 0.950090 | 24.41 | 16.14 | 0.00823430 | 45497.1 | 12.00 | 11.13 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15727.30 | 27.94 | 0.00879438 | 17.82 | 0.12033533 | 12.6657 | 23.90 | 0.00815308 | 23.90 | 0.00815308 | 43.5487 | 9486.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25099.054 | 25099.054 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.950086 | 1.12774372 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 25099.05 | 25099.05 | 1.0000 | 1.12774372 | 0.950086 | 11.35 | 8.13 | 0.00550656 | 25295.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25099.05 | -4.20 | 0.00269032 | -4.20 | 0.12033533 | 12.6657 | 21.05 | 0.00726260 | 21.10 | 0.00726260 | 46.0579 | 9173.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 39825.530 | 0.000 | 2.014470 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1239 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 39825.53 | 38544.06 | 1.0000 | 2.39115732 | 2.014470 | 27.17 | 17.09 | 0.00822180 | 48283.2 | 12.00 | 11.13 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39825.53 | 29.40 | 0.00879438 | 18.30 | 0.35392745 | 17.5693 | 26.70 | 0.00809976 | 26.70 | 0.00809976 | 36.6292 | 25804.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 67077.372 | 67077.372 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.014472 | 2.39116027 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 67077.37 | 67077.37 | 1.0000 | 2.39116027 | 2.014472 | 8.58 | 5.69 | 0.00458706 | 20163.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 67077.37 | -4.20 | 0.00269032 | -4.20 | 0.35392745 | 17.5692 | 15.55 | 0.00562294 | 15.55 | 0.00562294 | 50.6364 | 34812.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.35 | 2.01 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2099.17 | 2967.17 | 1814.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2099.17 | 2967.17 | 1814.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 52.00 | 0.50 | 48.67 | 0.50 |
ZONE2 FINE STORAGE | 337.33 | 1.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 377.00 | 1.50 | 48.67 | 0.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.405 | 0.396 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 814.07 | 5421.86 | 22-JAN-12:00 | 60381.02 | 10-AUG-15:00 |
Electricity:Building | 615.44 | 4938.86 | 01-JAN-00:10 | 45301.66 | 02-JAN-09:10 |
Electricity:Zone:ZONE1 OFFICE | 62.57 | 1027.15 | 01-JAN-00:10 | 3852.05 | 02-JAN-08:10 |
InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.62 | 453.40 | 01-JAN-00:10 | 1939.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 417.88 | 2726.34 | 01-JAN-00:10 | 31374.00 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 310.51 | 2726.34 | 01-JAN-00:10 | 23173.88 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 25.78 | 483.00 | 28-FEB-06:10 | 2336.65 | 10-FEB-12:20 |
WaterSystems:Electricity | 25.78 | 483.00 | 28-FEB-06:10 | 2336.65 | 10-FEB-12:20 |
Water Heater:WaterSystems:Electricity | 25.78 | 483.00 | 28-FEB-06:10 | 2336.65 | 10-FEB-12:20 |
Fans:Electricity | 42.93 | 0.00 | 02-JAN-18:40 | 5593.35 | 10-AUG-15:20 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.03 | 0.00 | 01-JAN-00:10 | 2305.29 | 10-AUG-17:20 |
Ventilation (simple):Fans:Electricity | 0.03 | 0.00 | 01-JAN-00:10 | 2305.29 | 10-AUG-17:20 |
ElectricityPurchased:Facility | 814.07 | 5421.86 | 22-JAN-12:00 | 60381.02 | 10-AUG-15:00 |
ElectricityPurchased:Plant | 814.07 | 5421.86 | 22-JAN-12:00 | 60381.02 | 10-AUG-15:00 |
Cogeneration:ElectricityPurchased | 814.07 | 5421.86 | 22-JAN-12:00 | 60381.02 | 10-AUG-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 814.07 | 5421.86 | 22-JAN-12:00 | 60381.02 | 10-AUG-15:00 |
ElectricityNet:Plant | 814.07 | 5421.86 | 22-JAN-12:00 | 60381.02 | 10-AUG-15:00 |
Cogeneration:ElectricityNet | 814.07 | 5421.86 | 22-JAN-12:00 | 60381.02 | 10-AUG-15:00 |
Electricity:HVAC | 49.62 | 0.00 | 02-JAN-18:40 | 13513.97 | 10-AUG-15:10 |
General:Fans:Electricity | 42.90 | 0.00 | 02-JAN-18:40 | 3487.80 | 07-JAN-10:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 6.72 | 0.00 | 01-JAN-00:10 | 10225.91 | 10-AUG-15:10 |
ExteriorLights:Electricity | 123.22 | 0.00 | 01-JAN-08:10 | 7857.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.22 | 0.00 | 01-JAN-08:10 | 7857.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 326.28 | 3000.00 | 23-JUL-13:10 | 140206.93 | 19-FEB-07:10 |
Gas:HVAC | 326.28 | 3000.00 | 23-JUL-13:10 | 140206.93 | 19-FEB-07:10 |
Heating:Gas | 326.28 | 3000.00 | 23-JUL-13:10 | 140206.93 | 19-FEB-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 386.86 | 0.00 | 02-JAN-18:40 | 216332.77 | 19-FEB-06:10 |
EnergyTransfer:Building | 194.87 | 0.00 | 02-JAN-18:40 | 108594.19 | 19-FEB-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 36.56 | 0.00 | 01-JAN-00:40 | 17319.77 | 17-JAN-06:10 |
Heating:EnergyTransfer | 165.29 | 0.00 | 02-JAN-18:40 | 108594.19 | 19-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 23.38 | 0.00 | 01-JAN-00:40 | 17319.77 | 17-JAN-06:10 |
Cooling:EnergyTransfer | 29.59 | 0.00 | 01-JAN-00:10 | 25961.26 | 10-AUG-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 13.18 | 0.00 | 01-JAN-00:10 | 9073.66 | 10-AUG-17:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 94.13 | 0.00 | 01-JAN-00:40 | 41145.43 | 19-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 77.72 | 0.00 | 01-JAN-00:40 | 41145.43 | 19-FEB-06:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 16.41 | 0.00 | 01-JAN-00:10 | 18425.79 | 10-AUG-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 64.19 | 0.00 | 02-JAN-08:10 | 68539.91 | 19-FEB-07:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 64.19 | 0.00 | 02-JAN-08:10 | 68539.91 | 19-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 191.99 | 0.00 | 02-JAN-18:40 | 107738.58 | 19-FEB-06:10 |
HeatingCoils:EnergyTransfer | 169.16 | 0.00 | 02-JAN-18:40 | 107738.58 | 19-FEB-06:10 |
CoolingCoils:EnergyTransfer | 22.83 | 0.00 | 01-JAN-00:10 | 33912.22 | 10-AUG-15:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 23.384 | -13.176 | 0.000 | 0.000 | 3.950 | 30.619 | 31.946 | 8.112 | 0.000 | 0.209 | 0.000 | 0.000 | -8.965 | 0.000 | -23.350 | -52.730 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 77.715 | -16.411 | 0.000 | 0.000 | 0.000 | 135.003 | 0.000 | 0.000 | 0.000 | 0.338 | 0.003 | 0.000 | 0.000 | 0.000 | -120.685 | -75.960 |
ZONE3 BULK STORAGE | 64.186 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 310.507 | 107.336 | 16.678 | 0.000 | 3.855 | 0.000 | 0.000 | -7.764 | 0.000 | -380.147 | -114.651 |
Total Facility | 64.186 | 0.000 | 101.099 | -29.587 | 0.000 | 0.000 | 3.950 | 476.129 | 139.282 | 24.791 | 0.000 | 4.402 | 0.003 | 0.000 | -16.729 | 0.000 | -524.182 | -243.341 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 24-JUL-05:01 | 0.00 | 0.00 | 0.00 | -15448.52 | 0.00 | 0.00 | 33.17 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 15003.44 | 0.00 | -221.12 | 0.00 | -520.07 | 0.00 |
ZONE2 FINE STORAGE | 08-AUG-18:41 | 0.00 | 0.00 | 0.00 | -38010.18 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 37161.21 | 0.00 | -0.00 | 0.00 | -336.40 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 08-AUG-18:41 | 0.00 | 0.00 | 0.00 | -38010.18 | 0.00 | 0.00 | 0.00 | 4365.11 | 2623.78 | 1554.26 | 0.00 | 0.00 | 31663.54 | 0.00 | -211.32 | 0.00 | -1985.20 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 24-FEB-06:01 | 0.00 | 0.00 | 24937.20 | 0.00 | 0.00 | 0.00 | 54.78 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -169.45 | 0.00 | -393.99 | -25581.65 |
ZONE2 FINE STORAGE | 19-FEB-06:02 | 0.00 | 0.00 | 70263.09 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -13776.66 | -57671.80 |
ZONE3 BULK STORAGE | 19-FEB-07:00 | 68539.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -792.44 | 0.00 | -48130.33 | -22343.13 |
Total Facility | 19-FEB-06:02 | 66065.78 | 0.00 | 71645.31 | 0.00 | 0.00 | 0.00 | 0.00 | 4365.11 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1759.21 | 0.00 | -59706.60 | -81184.13 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9501 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 0.9501 | 0.1267 | 1.0000 | 0.1203 | 0.1267 | ||
PSZ-FINE STORAGE | 2.0145 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.0145 | 0.1757 | 1.0000 | 0.3539 | 0.1757 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9501 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 0.9501 | 1.0000 | 1.0000 | 0.1203 | 0.1267 | ||
PSZ-FINE STORAGE | 2.0145 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.0145 | 1.0000 | 1.0000 | 0.3539 | 0.1757 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.9501 | 0.9501 | 0.9501 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.0145 | 2.0145 | 2.0145 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9501 | 0.9501 | 0.9501 | 0.9501 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.0145 | 2.0145 | 2.0145 | 2.0145 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.9501 | 0.9501 | 0.9501 | 0.1203 | 0.3841 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.0145 | 2.0145 | 2.0145 | 0.3539 | 0.3532 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9501 | 0.9501 | 0.9501 | 0.9501 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.0145 | 2.0145 | 2.0145 | 2.0145 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:43
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 48.67 |
Number of hours cooling loads not met | 0.50 |
Number of hours not met | 49.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 326.28 | 140206.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 6.72 | 10225.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 476.13 | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.22 | 7857.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.03 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 42.90 | 3487.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 25.78 | 2336.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 814.07 |
Natural Gas | 0.00 | 326.28 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1140.34 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 98.47 |
Space Heating | 0.00 |
Space Cooling | 1.39 |
Fans (All) | 8.88 |
Service Water Heating | 5.33 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 168.36 |
Subtotal | 168.36 |
Natural Gas [MJ/m2] | |
Space Heating | 67.48 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 67.48 |
Subtotal | 67.48 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 41.75 |
Space Heating | 28.61 |
Space Cooling | 0.59 |
Fans (All) | 3.77 |
Service Water Heating | 2.26 |
Receptacle Equipment | 12.21 |
Miscellaneous | 10.81 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.842576E+11 |
February | 0.000 | 0.623122E+11 |
March | 0.000 | 0.243037E+11 |
April | 0.000 | 0.140635E+11 |
May | 0.000 | 0.878931E+10 |
June | 0.000 | 0.796600E+10 |
July | 0.000 | 0.803830E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.790517E+10 |
October | 0.000 | 0.118145E+11 |
November | 0.000 | 0.280738E+11 |
December | 0.000 | 0.607162E+11 |
Annual Sum or Average | 0.326275E+12 | |
Minimum of Months | 0.000 | 0.790517E+10 |
Maximum of Months | 0.000 | 0.842576E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.842576E+11 |
February | 0.000 | 0.623122E+11 |
March | 0.000 | 0.243037E+11 |
April | 0.000 | 0.140635E+11 |
May | 0.000 | 0.878931E+10 |
June | 0.000 | 0.796600E+10 |
July | 0.000 | 0.803830E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.790517E+10 |
October | 0.000 | 0.118145E+11 |
November | 0.000 | 0.280738E+11 |
December | 0.000 | 0.607162E+11 |
Annual Sum or Average | 0.326275E+12 | |
Minimum of Months | 0.000 | 0.790517E+10 |
Maximum of Months | 0.000 | 0.842576E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.842576E+11 |
February | 0.000 | 0.623122E+11 |
March | 0.000 | 0.243037E+11 |
April | 0.000 | 0.140635E+11 |
May | 0.000 | 0.878931E+10 |
June | 0.000 | 0.796600E+10 |
July | 0.000 | 0.803830E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.790517E+10 |
October | 0.000 | 0.118145E+11 |
November | 0.000 | 0.280738E+11 |
December | 0.000 | 0.607162E+11 |
Annual Sum or Average | 0.326275E+12 | |
Minimum of Months | 0.000 | 0.790517E+10 |
Maximum of Months | 0.000 | 0.842576E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.842576E+11 |
February | 0.000 | 0.623122E+11 |
March | 0.000 | 0.243037E+11 |
April | 0.000 | 0.140635E+11 |
May | 0.000 | 0.878931E+10 |
June | 0.000 | 0.796600E+10 |
July | 0.000 | 0.803830E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.790517E+10 |
October | 0.000 | 0.118145E+11 |
November | 0.000 | 0.280738E+11 |
December | 0.000 | 0.607162E+11 |
Annual Sum or Average | 0.326275E+12 | |
Minimum of Months | 0.000 | 0.790517E+10 |
Maximum of Months | 0.000 | 0.842576E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.842576E+11 |
February | 0.000 | 0.623122E+11 |
March | 0.000 | 0.243037E+11 |
April | 0.000 | 0.140635E+11 |
May | 0.000 | 0.878931E+10 |
June | 0.000 | 0.796600E+10 |
July | 0.000 | 0.803830E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.790517E+10 |
October | 0.000 | 0.118145E+11 |
November | 0.000 | 0.280738E+11 |
December | 0.000 | 0.607162E+11 |
Annual Sum or Average | 0.326275E+12 | |
Minimum of Months | 0.000 | 0.790517E+10 |
Maximum of Months | 0.000 | 0.842576E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.842576E+11 |
February | 0.000 | 0.623122E+11 |
March | 0.000 | 0.243037E+11 |
April | 0.000 | 0.140635E+11 |
May | 0.000 | 0.878931E+10 |
June | 0.000 | 0.796600E+10 |
July | 0.000 | 0.803830E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.790517E+10 |
October | 0.000 | 0.118145E+11 |
November | 0.000 | 0.280738E+11 |
December | 0.000 | 0.607162E+11 |
Annual Sum or Average | 0.326275E+12 | |
Minimum of Months | 0.000 | 0.790517E+10 |
Maximum of Months | 0.000 | 0.842576E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.842576E+11 |
February | 0.000 | 0.623122E+11 |
March | 0.000 | 0.243037E+11 |
April | 0.000 | 0.140635E+11 |
May | 0.000 | 0.878931E+10 |
June | 0.000 | 0.796600E+10 |
July | 0.000 | 0.803830E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.790517E+10 |
October | 0.000 | 0.118145E+11 |
November | 0.000 | 0.280738E+11 |
December | 0.000 | 0.607162E+11 |
Annual Sum or Average | 0.326275E+12 | |
Minimum of Months | 0.000 | 0.790517E+10 |
Maximum of Months | 0.000 | 0.842576E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.842576E+11 |
February | 0.000 | 0.623122E+11 |
March | 0.000 | 0.243037E+11 |
April | 0.000 | 0.140635E+11 |
May | 0.000 | 0.878931E+10 |
June | 0.000 | 0.796600E+10 |
July | 0.000 | 0.803830E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.790517E+10 |
October | 0.000 | 0.118145E+11 |
November | 0.000 | 0.280738E+11 |
December | 0.000 | 0.607162E+11 |
Annual Sum or Average | 0.326275E+12 | |
Minimum of Months | 0.000 | 0.790517E+10 |
Maximum of Months | 0.000 | 0.842576E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.842576E+11 |
February | 0.000 | 0.623122E+11 |
March | 0.000 | 0.243037E+11 |
April | 0.000 | 0.140635E+11 |
May | 0.000 | 0.878931E+10 |
June | 0.000 | 0.796600E+10 |
July | 0.000 | 0.803830E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.790517E+10 |
October | 0.000 | 0.118145E+11 |
November | 0.000 | 0.280738E+11 |
December | 0.000 | 0.607162E+11 |
Annual Sum or Average | 0.326275E+12 | |
Minimum of Months | 0.000 | 0.790517E+10 |
Maximum of Months | 0.000 | 0.842576E+11 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 | 4.99 | 0.195006E+09 | 236.59 | 09-JAN-08:20 | 0.20 | -0.8 |
February | 4368286.87 | 336.09 | 28-FEB-11:50 | 11.60 | 10.40 | 0.180333E+09 | 283.83 | 27-FEB-16:10 | 19.32 | 12.37 |
March | 46661100.65 | 739.54 | 11-MAR-15:00 | 8.30 | 7.17 | 0.213122E+09 | 299.13 | 18-MAR-15:00 | 20.60 | 10.40 |
April | 0.253264E+09 | 3382.74 | 27-APR-16:00 | 27.20 | 16.88 | 0.207545E+09 | 301.59 | 29-APR-15:09 | 21.83 | 15.10 |
May | 0.926513E+09 | 4323.13 | 15-MAY-16:00 | 23.90 | 12.83 | 0.240786E+09 | 301.60 | 04-MAY-13:09 | 22.48 | 15.27 |
June | 0.195084E+10 | 5942.37 | 28-JUN-16:00 | 26.10 | 16.27 | 0.253190E+09 | 301.60 | 10-JUN-10:30 | 20.00 | 14.78 |
July | 0.345636E+10 | 15448.53 | 24-JUL-05:01 | 15.87 | 13.14 | 0.247675E+09 | 301.61 | 25-JUL-15:00 | 23.90 | 17.57 |
August | 0.411023E+10 | 15336.84 | 15-AUG-05:02 | 13.05 | 11.44 | 0.267804E+09 | 301.60 | 25-AUG-14:39 | 26.73 | 18.79 |
September | 0.208771E+10 | 13878.65 | 15-SEP-05:03 | 11.60 | 11.30 | 0.243683E+09 | 301.60 | 12-SEP-15:00 | 24.40 | 17.02 |
October | 0.297314E+09 | 2868.45 | 04-OCT-16:00 | 21.10 | 11.38 | 0.210743E+09 | 301.59 | 07-OCT-13:09 | 17.20 | 12.17 |
November | 40896141.51 | 900.87 | 04-NOV-15:50 | 20.18 | 15.91 | 0.189296E+09 | 301.58 | 04-NOV-14:09 | 21.10 | 15.93 |
December | 1490978.28 | 298.38 | 02-DEC-15:10 | 11.52 | 5.35 | 0.195017E+09 | 236.90 | 02-DEC-15:09 | 11.52 | 5.35 |
Annual Sum or Average | 0.131756E+11 | 0.264420E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | 5.92 | 4.99 | 0.180333E+09 | 236.59 | 0.20 | -0.8 | ||
Maximum of Months | 0.411023E+10 | 15448.53 | 27.20 | 16.88 | 0.267804E+09 | 301.61 | 26.73 | 18.79 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.372503E+09 | 3020.88 | 07-JAN-14:00 | 2.80 | 1.90 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.466775E+09 | 4642.66 | 28-FEB-07:10 | 10.60 | 9.78 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.829872E+09 | 4901.01 | 11-MAR-07:10 | 10.00 | 9.66 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.709566E+09 | 7259.50 | 27-APR-06:10 | 11.88 | 9.03 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.974140E+09 | 7787.60 | 11-MAY-06:10 | 5.97 | 5.05 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.134308E+10 | 9824.43 | 28-JUN-15:00 | 26.10 | 15.52 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.384113E+10 | 37841.44 | 23-JUL-12:11 | 24.97 | 16.25 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.452220E+10 | 38010.41 | 08-AUG-18:41 | 26.33 | 16.07 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.163395E+10 | 9507.74 | 14-SEP-14:30 | 23.90 | 17.02 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.589646E+09 | 4825.76 | 14-OCT-06:10 | 8.90 | 7.91 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.582147E+09 | 4352.51 | 07-NOV-07:10 | 11.70 | 9.90 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.546070E+09 | 3370.09 | 06-DEC-12:00 | 3.30 | 3.23 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.164111E+11 | 0.00 | ||||||||
Minimum of Months | 0.372503E+09 | 3020.88 | 2.80 | 1.90 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.452220E+10 | 38010.41 | 26.33 | 17.02 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 | 4.99 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 | 6.66 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 | 3.48 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.00 | 0.00 | 17.17 | 13.74 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.516834E+10 | 24454.82 | 11-JAN-06:01 | 9.90 |
February | 0.398614E+10 | 24937.24 | 24-FEB-06:01 | 13.90 |
March | 0.310696E+10 | 24483.37 | 08-MAR-06:01 | 10.18 |
April | 0.171191E+10 | 24242.39 | 10-APR-05:01 | 8.80 |
May | 0.465134E+09 | 23753.50 | 30-MAY-05:02 | 10.60 |
June | 0.126185E+09 | 6150.40 | 01-JUN-06:05 | 10.18 |
July | 5554617.79 | 1096.17 | 05-JUL-06:30 | 13.30 |
August | 4778578.27 | 446.42 | 30-AUG-06:10 | 17.05 |
September | 81055522.60 | 6969.19 | 28-SEP-06:05 | 8.40 |
October | 0.125551E+10 | 24473.41 | 23-OCT-05:01 | 10.60 |
November | 0.305008E+10 | 24729.69 | 27-NOV-06:01 | 11.70 |
December | 0.442269E+10 | 24552.61 | 16-DEC-06:01 | 10.60 |
Annual Sum or Average | 0.233843E+11 | |||
Minimum of Months | 4778578.27 | 446.42 | 8.40 | |
Maximum of Months | 0.516834E+10 | 24937.24 | 17.05 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.219732E+11 | 69475.14 | 14-JAN-20:42 | 0.68 |
February | 0.160062E+11 | 70262.55 | 19-FEB-06:02 | -5.5 |
March | 0.759262E+10 | 68397.10 | 24-MAR-05:53 | 1.70 |
April | 0.266804E+10 | 68097.96 | 11-APR-04:03 | 5.10 |
May | 0.255016E+09 | 2414.16 | 17-MAY-07:00 | 8.90 |
June | 0.225286E+09 | 2279.81 | 13-JUN-07:00 | 11.70 |
July | 0.170159E+09 | 2250.96 | 10-JUL-06:25 | 13.05 |
August | 0.204624E+09 | 2467.08 | 31-AUG-07:00 | 14.00 |
September | 0.197002E+09 | 2408.97 | 27-SEP-07:00 | 8.90 |
October | 0.136832E+10 | 52664.93 | 31-OCT-20:33 | 7.20 |
November | 0.930909E+10 | 68451.71 | 29-NOV-22:42 | 5.00 |
December | 0.177457E+11 | 68437.37 | 26-DEC-19:23 | 5.00 |
Annual Sum or Average | 0.777152E+11 | |||
Minimum of Months | 0.170159E+09 | 2250.96 | -5.5 | |
Maximum of Months | 0.219732E+11 | 70262.55 | 14.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.279680E+11 | 46640.15 | 15-JAN-01:52 | -1.7 |
February | 0.200652E+11 | 68540.48 | 19-FEB-07:00 | -5.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.104765E+10 | 22455.47 | 29-NOV-21:00 | 5.00 |
December | 0.151058E+11 | 36300.60 | 22-DEC-23:00 | 1.10 |
Annual Sum or Average | 0.641866E+11 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.279680E+11 | 68540.48 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.256100E+10 | 1939.55 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.233575E+10 | 1939.55 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.266872E+10 | 1939.55 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.252182E+10 | 1939.55 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.261486E+10 | 1939.55 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.257569E+10 | 1939.55 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.256100E+10 | 1939.55 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.266872E+10 | 1939.55 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.252182E+10 | 1939.55 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.256100E+10 | 1939.55 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.246796E+10 | 1939.55 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.256100E+10 | 1939.55 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.306193E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.233575E+10 | 1939.55 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.266872E+10 | 1939.55 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112294E+11 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102778E+11 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.118738E+11 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.111270E+11 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.115516E+11 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.114492E+11 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112294E+11 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.118738E+11 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.111270E+11 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112294E+11 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108048E+11 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112294E+11 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135003E+12 | ||||
Minimum of Months | 0.102778E+11 | 10075.60 | 0.00 | 0.00 | |
Maximum of Months | 0.118738E+11 | 10075.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.258277E+11 | 23173.88 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.236390E+11 | 23173.88 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.273097E+11 | 23173.88 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.255921E+11 | 23173.88 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.265687E+11 | 23173.88 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.263332E+11 | 23173.88 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.258277E+11 | 23173.88 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.273097E+11 | 23173.88 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.255921E+11 | 23173.88 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.258277E+11 | 23173.88 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.248511E+11 | 23173.88 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.258277E+11 | 23173.88 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.236390E+11 | 23173.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.273097E+11 | 23173.88 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296789E+10 |
February | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248774E+10 |
March | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246199E+10 |
April | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10748355.01 | 0.193863E+10 |
May | 0.565842E+09 | 0.261486E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1143501.04 | 0.177548E+10 |
June | 0.565842E+09 | 0.257569E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8774476.91 | 0.147373E+10 |
July | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50083974.47 | 0.108300E+10 |
August | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136217E+09 | 0.102798E+10 |
September | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2004001.56 | 0.117024E+10 |
October | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187437E+10 |
November | 0.522316E+09 | 0.246796E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238933E+10 |
December | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269977E+10 |
Annual Sum or Average | 0.659424E+10 | 0.306193E+11 | 0.319458E+11 | 0.208972E+09 | 0.233502E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102798E+10 |
Maximum of Months | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136217E+09 | 0.296789E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149530E+11 |
February | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126413E+11 |
March | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110449E+11 |
April | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100626E+09 | 0.989155E+10 |
May | 0.00 | 0.115516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998746E+10 |
June | 0.00 | 0.114492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.948542E+10 |
July | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59467930.80 | 0.853729E+10 |
August | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178035E+09 | 0.776694E+10 |
September | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549939E+10 |
October | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.859225E+10 |
November | 0.00 | 0.108048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101148E+11 |
December | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121706E+11 |
Annual Sum or Average | 0.135003E+12 | 0.338130E+09 | 0.120685E+12 | ||||||
Minimum of Months | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549939E+10 |
Maximum of Months | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178035E+09 | 0.149530E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83231341.47 | 0.253377E+11 |
February | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353599E+09 | 0.218611E+11 |
March | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251559E+09 | 0.222237E+11 |
April | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139478E+10 | 0.223344E+11 |
May | 0.00 | 0.265687E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121297E+09 | 0.285016E+11 |
June | 0.00 | 0.263332E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7781218.64 | 0.267483E+11 |
July | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70050657.23 | 0.271264E+11 |
August | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225688E+09 | 0.280508E+11 |
September | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198482E+11 |
October | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250644E+11 |
November | 0.00 | 0.248511E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70976678.78 | 0.193726E+11 |
December | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29521588.96 | 0.189075E+11 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | 0.260848E+10 | 0.285377E+12 | |||||
Minimum of Months | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189075E+11 |
Maximum of Months | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139478E+10 | 0.285016E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1939.55 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9252.74 | 06-JAN-07:10 |
February | 659.25 | 01-FEB-08:09 | 1939.55 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 8842.40 | 09-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1939.55 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 8463.14 | 24-MAR-06:10 |
April | 659.25 | 01-APR-07:10 | 1939.55 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1168.54 | 27-APR-16:10 | 7567.11 | 19-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1939.55 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.65 | 05-MAY-16:10 | 6256.41 | 18-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1939.55 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1034.86 | 28-JUN-17:00 | 4777.43 | 13-JUN-11:03 |
July | 659.25 | 01-JUL-07:10 | 1939.55 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1864.70 | 31-JUL-16:10 | 4281.69 | 12-JUL-06:03 |
August | 659.25 | 01-AUG-07:10 | 1939.55 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2809.14 | 10-AUG-17:00 | 4945.88 | 01-AUG-06:03 |
September | 659.25 | 01-SEP-07:10 | 1939.55 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.83 | 14-SEP-17:00 | 4806.05 | 27-SEP-07:00 |
October | 659.25 | 02-OCT-07:10 | 1939.55 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 6148.14 | 16-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1939.55 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7966.93 | 24-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1939.55 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 9160.45 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4281.69 | |||||
Maximum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2809.14 | 9252.74 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 20718.50 | 28-JAN-08:00 |
February | 0.00 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 17959.39 | 13-FEB-08:00 |
March | 0.00 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 16377.80 | 24-MAR-06:10 |
April | 0.00 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4614.86 | 01-APR-16:00 | 13781.94 | 08-APR-07:00 |
May | 0.00 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 16069.02 | 10-MAY-15:05 |
June | 0.00 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 14026.37 | 13-JUN-03:00 |
July | 0.00 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2082.77 | 24-JUL-15:10 | 10193.40 | 03-JUL-15:05 |
August | 0.00 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3590.71 | 08-AUG-17:00 | 13147.68 | 11-AUG-04:00 |
September | 0.00 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 10509.75 | 26-SEP-15:10 |
October | 0.00 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 12592.00 | 31-OCT-19:57 |
November | 0.00 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 19433.92 | 29-NOV-18:00 |
December | 0.00 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 14389.65 | 22-DEC-21:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10193.40 | |||
Maximum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4614.86 | 20718.50 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23173.88 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7551.76 | 11-JAN-14:00 | 29089.76 | 14-JAN-19:52 |
February | 0.00 | 23173.88 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6025.93 | 27-FEB-15:00 | 36638.89 | 13-FEB-11:00 |
March | 0.00 | 23173.88 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10922.50 | 18-MAR-16:00 | 35524.46 | 22-MAR-09:00 |
April | 0.00 | 23173.88 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33419.44 | 01-APR-16:00 | 27806.12 | 18-APR-16:00 |
May | 0.00 | 23173.88 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2953.73 | 14-MAY-15:00 | 38488.56 | 10-MAY-15:00 |
June | 0.00 | 23173.88 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1153.08 | 20-JUN-17:00 | 41686.65 | 13-JUN-10:00 |
July | 0.00 | 23173.88 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3573.91 | 23-JUL-14:00 | 28454.35 | 03-JUL-16:00 |
August | 0.00 | 23173.88 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4948.69 | 29-AUG-18:00 | 40933.72 | 11-AUG-04:00 |
September | 0.00 | 23173.88 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 31661.88 | 26-SEP-15:40 |
October | 0.00 | 23173.88 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 24378.59 | 14-OCT-11:00 |
November | 0.00 | 23173.88 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6163.29 | 27-NOV-02:55 | 26891.05 | 29-NOV-14:00 |
December | 0.00 | 23173.88 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6391.66 | 14-DEC-12:00 | 37342.04 | 26-DEC-14:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24378.59 | ||||
Maximum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 33419.44 | 41686.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1813.61 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.30 |
February | 336.09 | 28-FEB-11:50 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.99 |
March | 739.54 | 11-MAR-15:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.25 |
April | 3382.74 | 27-APR-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 296.34 | 0.00 |
May | 4323.13 | 15-MAY-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
June | 5942.37 | 28-JUN-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 210.36 | 0.00 |
July | 15448.53 | 24-JUL-05:01 | 507.62 | 4055.43 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 520.07 |
August | 15336.84 | 15-AUG-05:02 | 435.11 | 3476.08 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 790.46 |
September | 13878.65 | 15-SEP-05:03 | 290.07 | 2317.39 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 667.39 |
October | 2868.45 | 04-OCT-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.12 |
November | 900.87 | 04-NOV-15:50 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.57 |
December | 298.38 | 02-DEC-15:10 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.07 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 1813.61 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15448.53 | 659.25 | 4055.43 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 296.34 | 790.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3020.88 | 07-JAN-14:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2060.72 |
February | 4642.66 | 28-FEB-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2031.45 |
March | 4901.01 | 11-MAR-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2756.01 |
April | 7259.50 | 27-APR-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.64 |
May | 7787.60 | 11-MAY-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6580.11 |
June | 9824.43 | 28-JUN-15:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.45 |
July | 37841.44 | 23-JUL-12:11 | 0.00 | 9482.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1460.96 |
August | 38010.41 | 08-AUG-18:41 | 0.00 | 9482.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.40 |
September | 9507.74 | 14-SEP-14:30 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570.18 |
October | 4825.76 | 14-OCT-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4167.89 |
November | 4352.51 | 07-NOV-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4959.51 |
December | 3370.09 | 06-DEC-12:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1438.53 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3020.88 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.45 | |
Maximum of Months | 38010.41 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6580.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 10905.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13224.71 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5120.88 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10047.84 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7422.25 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16769.19 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5721.00 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8038.21 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10857.16 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13449.73 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8206.43 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10143.01 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 8179.02 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5487.34 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5120.88 | |
Maximum of Months | 0.00 | 0.00 | 10905.36 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16769.19 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.710759E+11 | 54350.34 | 18-JAN-16:00 | 0.842576E+11 | 110506.85 | 09-JAN-06:10 |
February | 0.636474E+11 | 50595.74 | 16-FEB-15:09 | 0.623122E+11 | 140206.93 | 19-FEB-07:10 |
March | 0.710435E+11 | 50394.43 | 01-MAR-13:09 | 0.243037E+11 | 53079.29 | 24-MAR-05:00 |
April | 0.652873E+11 | 51768.21 | 27-APR-14:00 | 0.140635E+11 | 44585.63 | 19-APR-05:10 |
May | 0.664928E+11 | 52014.88 | 06-MAY-14:00 | 0.878931E+10 | 15430.98 | 18-MAY-06:10 |
June | 0.654886E+11 | 55228.21 | 28-JUN-14:30 | 0.796600E+10 | 9871.47 | 07-JUN-06:10 |
July | 0.660827E+11 | 59275.45 | 24-JUL-14:39 | 0.803830E+10 | 4744.27 | 05-JUL-06:30 |
August | 0.714804E+11 | 60381.02 | 10-AUG-14:00 | 0.803520E+10 | 3000.00 | 01-AUG-00:10 |
September | 0.666292E+11 | 55015.23 | 14-SEP-14:30 | 0.790517E+10 | 11860.36 | 28-SEP-06:10 |
October | 0.682862E+11 | 51398.36 | 04-OCT-14:50 | 0.118145E+11 | 30020.22 | 30-OCT-05:00 |
November | 0.673527E+11 | 54205.75 | 29-NOV-16:49 | 0.280738E+11 | 68680.99 | 29-NOV-22:49 |
December | 0.712002E+11 | 54348.71 | 26-DEC-16:30 | 0.607162E+11 | 84111.15 | 26-DEC-07:00 |
Annual Sum or Average | 0.814067E+12 | 0.326275E+12 | ||||
Minimum of Months | 0.636474E+11 | 50394.43 | 0.790517E+10 | 3000.00 | ||
Maximum of Months | 0.714804E+11 | 60381.02 | 0.842576E+11 | 140206.93 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.396181E+11 | 0.133978E+11 | 0.115358E+11 | 0.00 | 0.429477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222950E+10 | 0.00 |
February | 0.362526E+11 | 0.110454E+11 | 0.105871E+11 | 0.00 | 0.373074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203155E+10 | 0.00 |
March | 0.418523E+11 | 0.107814E+11 | 0.123357E+11 | 0.00 | 0.378771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228643E+10 | 0.00 |
April | 0.392410E+11 | 0.898055E+10 | 0.114862E+11 | 0.00 | 0.335538E+10 | 0.00 | 0.00 | 71767250.65 | 0.00 | 0.00 | 0.00 | 0.215237E+10 | 0.00 |
May | 0.407352E+11 | 0.797643E+10 | 0.119357E+11 | 0.00 | 0.339097E+10 | 0.00 | 0.00 | 0.261478E+09 | 0.00 | 0.00 | 0.00 | 0.219295E+10 | 0.00 |
June | 0.403581E+11 | 0.701944E+10 | 0.118862E+11 | 0.00 | 0.338583E+10 | 0.00 | 0.00 | 0.726396E+09 | 0.00 | 0.00 | 0.00 | 0.211270E+10 | 0.00 |
July | 0.396181E+11 | 0.757572E+10 | 0.115358E+11 | 0.00 | 0.328233E+10 | 0.00 | 0.00 | 0.196476E+10 | 0.00 | 0.00 | 0.00 | 0.210603E+10 | 0.00 |
August | 0.418523E+11 | 0.869770E+10 | 0.123357E+11 | 0.00 | 0.358170E+10 | 0.00 | 0.00 | 0.285901E+10 | 0.00 | 0.00 | 0.00 | 0.215407E+10 | 0.00 |
September | 0.392410E+11 | 0.980082E+10 | 0.114862E+11 | 0.00 | 0.325644E+10 | 0.00 | 0.00 | 0.777624E+09 | 0.00 | 0.00 | 0.00 | 0.206711E+10 | 0.00 |
October | 0.396181E+11 | 0.116299E+11 | 0.115358E+11 | 0.00 | 0.330733E+10 | 0.00 | 0.00 | 51912121.67 | 0.00 | 0.00 | 0.00 | 0.214310E+10 | 0.00 |
November | 0.381239E+11 | 0.125728E+11 | 0.110862E+11 | 0.00 | 0.346431E+10 | 0.00 | 0.00 | 4540538.77 | 0.00 | 0.00 | 0.00 | 0.210088E+10 | 0.00 |
December | 0.396181E+11 | 0.137419E+11 | 0.115358E+11 | 0.00 | 0.409692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220751E+10 | 0.00 |
Annual Sum or Average | 0.476129E+12 | 0.123220E+12 | 0.139282E+12 | 0.429345E+11 | 0.00 | 0.671749E+10 | 0.257842E+11 | ||||||
Minimum of Months | 0.362526E+11 | 0.701944E+10 | 0.105871E+11 | 0.00 | 0.325644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203155E+10 | 0.00 |
Maximum of Months | 0.418523E+11 | 0.137419E+11 | 0.123357E+11 | 0.00 | 0.429477E+10 | 0.00 | 0.00 | 0.285901E+10 | 0.00 | 0.00 | 0.00 | 0.228643E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.842576E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.623122E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.243037E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.140635E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.878931E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.796600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.803830E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.803520E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.790517E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.118145E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.280738E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.607162E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.326275E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.790517E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.842576E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35189.04 | 02-JAN-09:09 | 7857.00 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 3487.80 | 02-JAN-07:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35189.04 | 01-FEB-09:09 | 7857.00 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 3487.80 | 06-FEB-07:19 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35189.04 | 01-MAR-09:09 | 7857.00 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 3288.05 | 03-MAR-07:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35189.04 | 01-APR-08:09 | 7857.00 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 3288.05 | 08-APR-07:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35189.04 | 01-MAY-08:09 | 7857.00 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 3288.05 | 15-MAY-13:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35189.04 | 01-JUN-08:09 | 7857.00 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 3288.05 | 21-JUN-14:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35189.04 | 01-JUL-08:09 | 7857.00 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 3288.05 | 06-JUL-14:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35189.04 | 01-AUG-08:09 | 7857.00 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 5593.35 | 10-AUG-15:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35189.04 | 01-SEP-08:09 | 7857.00 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 3288.05 | 11-SEP-14:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35189.04 | 02-OCT-08:09 | 7857.00 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 3288.05 | 30-OCT-07:19 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35189.04 | 01-NOV-08:09 | 7857.00 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 3487.80 | 29-NOV-16:40 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35189.04 | 01-DEC-09:09 | 7857.00 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 3487.80 | 01-DEC-07:19 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35189.04 | 7857.00 | 10112.62 | 0.00 | 3288.05 | 0.00 | 0.00 | |||||
Maximum of Months | 35189.04 | 7857.00 | 10112.62 | 0.00 | 5593.35 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2330.30 | 31-JAN-12:09 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2336.65 | 10-FEB-12:20 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2318.92 | 02-MAR-12:00 | 0.00 |
April | 1598.19 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 | 2219.62 | 04-APR-11:50 | 0.00 |
May | 1642.01 | 06-MAY-14:00 | 0.00 | 0.00 | 0.00 | 2077.17 | 01-MAY-11:09 | 0.00 |
June | 5289.69 | 28-JUN-14:00 | 0.00 | 0.00 | 0.00 | 1883.19 | 02-JUN-11:00 | 0.00 |
July | 9189.61 | 24-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1800.82 | 01-JUL-11:09 | 0.00 |
August | 10225.91 | 10-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1794.71 | 28-AUG-11:30 | 0.00 |
September | 4665.30 | 14-SEP-14:30 | 0.00 | 0.00 | 0.00 | 1802.80 | 29-SEP-11:20 | 0.00 |
October | 1064.33 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 1935.08 | 30-OCT-11:50 | 0.00 |
November | 558.02 | 04-NOV-15:30 | 0.00 | 0.00 | 0.00 | 2117.04 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2256.62 | 30-DEC-12:50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1794.71 | 0.00 | ||
Maximum of Months | 10225.91 | 0.00 | 0.00 | 0.00 | 2336.65 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 54350.34 | 18-JAN-16:00 | 31277.33 | 10112.62 | 7857.00 | 0.00 | 3487.80 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 50595.74 | 16-FEB-15:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3487.80 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 50394.43 | 01-MAR-13:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3288.05 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 51768.21 | 27-APR-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3288.05 | 0.00 | 0.00 | 1503.38 | 0.00 |
May | 52014.88 | 06-MAY-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3288.05 | 0.00 | 0.00 | 1642.01 | 0.00 |
June | 55228.21 | 28-JUN-14:30 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3288.05 | 0.00 | 0.00 | 4875.59 | 0.00 |
July | 59275.45 | 24-JUL-14:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3288.05 | 0.00 | 0.00 | 8928.39 | 0.00 |
August | 60381.02 | 10-AUG-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3288.05 | 0.00 | 0.00 | 10034.54 | 0.00 |
September | 55015.23 | 14-SEP-14:30 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3288.05 | 0.00 | 0.00 | 4665.30 | 0.00 |
October | 51398.36 | 04-OCT-14:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3288.05 | 0.00 | 0.00 | 1043.50 | 0.00 |
November | 54205.75 | 29-NOV-16:49 | 31277.33 | 10112.62 | 7857.00 | 0.00 | 3487.80 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 54348.71 | 26-DEC-16:30 | 31277.33 | 10112.62 | 7857.00 | 0.00 | 3487.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 50394.43 | 31277.33 | 10112.62 | 0.00 | 0.00 | 3288.05 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 60381.02 | 35189.04 | 10112.62 | 7857.00 | 0.00 | 3487.80 | 0.00 | 0.00 | 10034.54 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 110506.85 | 09-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 140206.93 | 19-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 53079.29 | 24-MAR-05:00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 44585.63 | 19-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 15430.98 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 9871.47 | 07-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 4744.27 | 05-JUL-06:30 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 3000.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 11860.36 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 30020.22 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 68680.99 | 29-NOV-22:49 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 84111.15 | 26-DEC-07:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 3000.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 140206.93 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.67 | 19.02 | 8.33 | 19.66 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9.00 | 18.97 | 7.50 | 19.77 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8.00 | 19.99 | 8.00 | 19.99 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5.33 | 20.14 | 5.33 | 20.14 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.83 | 20.48 | 0.83 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.33 | 20.50 | 0.33 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.54 | 0.17 | 24.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.51 | 0.33 | 24.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3.33 | 20.29 | 3.33 | 20.29 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.50 | 20.03 | 6.50 | 20.03 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9.00 | 19.54 | 8.50 | 19.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.00 | 19.61 | 48.67 | 19.92 | 0.50 | 24.52 | 0.50 | 24.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.67 | 20.50 | 8.50 | 20.50 | 0.33 | 24.54 | 0.33 | 24.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 101.50 | 14.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 68.33 | 14.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28.00 | 14.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9.00 | 14.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.29 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.28 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4.33 | 14.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 40.83 | 14.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 85.33 | 14.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 337.33 | 14.72 | 0.00 | 1.00 | 27.28 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.50 | 14.95 | 0.00 | 0.00 | 0.50 | 27.29 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.06 | 300.00 | 21.06 | 300.00 | 21.06 |
February | 276.00 | 21.11 | 263.83 | 21.06 | 263.83 | 21.06 |
March | 324.00 | 21.18 | 301.50 | 21.10 | 301.50 | 21.10 |
April | 300.00 | 21.66 | 197.33 | 21.12 | 197.33 | 21.12 |
May | 294.83 | 22.71 | 38.67 | 21.10 | 38.67 | 21.10 |
June | 231.83 | 23.25 | 8.00 | 23.66 | 0.67 | 21.01 |
July | 90.33 | 23.47 | 98.17 | 23.90 | 0.00 | 0.00 |
August | 61.83 | 23.41 | 149.17 | 23.90 | 0.00 | 0.00 |
September | 200.33 | 23.25 | 31.17 | 23.83 | 0.67 | 20.85 |
October | 300.00 | 21.80 | 153.83 | 21.10 | 153.83 | 21.10 |
November | 288.00 | 21.17 | 257.50 | 21.08 | 257.50 | 21.08 |
December | 300.00 | 21.06 | 300.00 | 21.06 | 300.00 | 21.06 |
Annual Sum or Average | 2967.17 | 21.83 | 2099.17 | 21.46 | 1814.00 | 21.08 |
Minimum of Months | 61.83 | 21.06 | 8.00 | 21.06 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 23.47 | 301.50 | 23.90 | 301.50 | 21.12 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.235440E+09 | 71767250.65 | 25.58 | 0.223201E+09 | 12238130.39 | 0.00 | 0.37 | 27-APR-16:00 | 0.00 | 01-APR-00:10 | 5161.25 | 27-APR-16:00 | 4953.79 | 27-APR-16:00 | 390.52 | 28-APR-12:50 | 1598.19 | 27-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.875565E+09 | 0.261476E+09 | 107.08 | 0.817077E+09 | 58487904.07 | 0.00 | 0.39 | 15-MAY-16:00 | 0.00 | 01-MAY-00:10 | 5649.35 | 06-MAY-15:00 | 5405.22 | 15-MAY-16:00 | 691.76 | 06-MAY-13:20 | 1642.01 | 06-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.217641E+10 | 0.647755E+09 | 203.17 | 0.208181E+10 | 94592369.48 | 0.00 | 0.52 | 28-JUN-16:00 | 0.00 | 01-JUN-00:10 | 7422.62 | 28-JUN-16:00 | 7348.12 | 28-JUN-16:00 | 690.50 | 12-JUN-14:30 | 2202.74 | 28-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.430302E+10 | 0.126575E+10 | 250.13 | 0.391896E+10 | 0.384054E+09 | 0.00 | 1.00 | 24-JUL-05:01 | 0.00 | 01-JUL-00:10 | 16635.08 | 31-JUL-05:02 | 15738.79 | 24-JUL-05:01 | 2658.01 | 26-JUL-05:03 | 4348.15 | 31-JUL-05:02 | 0.00 | 01-JUL-00:10 |
August | 0.538669E+10 | 0.159278E+10 | 276.12 | 0.479367E+10 | 0.593016E+09 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 16836.64 | 25-AUG-05:02 | 15502.25 | 09-AUG-05:02 | 3065.59 | 26-AUG-05:03 | 4391.93 | 25-AUG-05:02 | 0.00 | 01-AUG-00:10 |
September | 0.240021E+10 | 0.707936E+09 | 196.26 | 0.213076E+10 | 0.269450E+09 | 0.00 | 1.00 | 14-SEP-05:03 | 0.00 | 01-SEP-00:10 | 16272.71 | 14-SEP-05:03 | 14085.47 | 14-SEP-05:03 | 2187.23 | 14-SEP-05:03 | 4266.82 | 14-SEP-05:03 | 0.00 | 01-SEP-00:10 |
October | 0.171437E+09 | 51912121.67 | 30.00 | 0.169740E+09 | 1697610.93 | 0.00 | 0.27 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3576.80 | 04-OCT-15:00 | 3576.80 | 04-OCT-15:00 | 66.24 | 07-OCT-16:00 | 1064.33 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 15014115.11 | 4540538.77 | 2.83 | 12142674.10 | 2871441.00 | 0.00 | 0.13 | 04-NOV-15:30 | 0.00 | 01-NOV-00:10 | 1849.49 | 04-NOV-15:30 | 1501.17 | 04-NOV-15:00 | 349.98 | 04-NOV-15:30 | 558.02 | 04-NOV-15:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.155638E+11 | 0.460392E+10 | 1091.18 | 0.141474E+11 | 0.141641E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.538669E+10 | 0.159278E+10 | 276.12 | 0.479367E+10 | 0.593016E+09 | 0.00 | 1.00 | 0.00 | 16836.64 | 15738.79 | 3065.59 | 4391.93 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 5371.58 | 1581.17 | 2.33 | 4885.78 | 485.81 | 0.00 | 0.00 | 06-MAY-13:40 | 0.00 | 01-MAY-00:10 | 1.06 | 06-MAY-13:40 | 0.88 | 15-MAY-15:00 | 0.21 | 06-MAY-13:40 | 0.31 | 06-MAY-13:40 | 0.00 | 01-MAY-00:10 |
June | 0.269073E+09 | 78640660.35 | 28.00 | 0.257537E+09 | 11536585.40 | 0.00 | 0.31 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 | 11003.72 | 28-JUN-15:00 | 11003.72 | 28-JUN-15:00 | 561.80 | 28-JUN-12:50 | 3218.31 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.241785E+10 | 0.699006E+09 | 103.35 | 0.213122E+10 | 0.286632E+09 | 0.00 | 1.00 | 20-JUL-17:12 | 0.00 | 01-JUL-00:10 | 43599.85 | 27-JUL-17:12 | 39549.63 | 23-JUL-17:10 | 10904.53 | 27-JUL-17:23 | 11053.06 | 31-JUL-17:10 | 0.00 | 01-JUL-00:10 |
August | 0.433513E+10 | 0.126624E+10 | 117.81 | 0.383636E+10 | 0.498772E+09 | 0.00 | 1.00 | 08-AUG-17:10 | 0.00 | 01-AUG-00:10 | 42707.88 | 13-AUG-13:42 | 39711.23 | 08-AUG-18:41 | 8249.98 | 13-AUG-11:07 | 11205.43 | 10-AUG-17:08 | 0.00 | 01-AUG-00:10 |
September | 0.242279E+09 | 69688227.65 | 26.67 | 0.190942E+09 | 51337022.50 | 0.00 | 0.24 | 14-SEP-14:30 | 0.00 | 01-SEP-00:10 | 8834.67 | 14-SEP-14:30 | 6993.35 | 14-SEP-14:30 | 1972.63 | 14-SEP-13:40 | 2496.67 | 14-SEP-14:30 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.726433E+10 | 0.211357E+10 | 278.16 | 0.641606E+10 | 0.848279E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.433513E+10 | 0.126624E+10 | 117.81 | 0.383636E+10 | 0.498772E+09 | 0.00 | 1.00 | 0.00 | 43599.85 | 39711.23 | 10904.53 | 11205.43 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.15 | 11.92 | 28.22 | 11.31 | 135.97 | 0.00 | 0.00 | 744.00 |
February | 71.32 | 26.57 | 44.76 | 40.30 | 115.09 | 0.00 | 0.00 | 672.00 |
March | 100.46 | 33.94 | 66.52 | 72.51 | 90.64 | 0.00 | 0.00 | 744.00 |
April | 152.51 | 58.19 | 94.32 | 136.89 | 73.25 | 0.00 | 0.00 | 720.00 |
May | 196.69 | 79.98 | 116.71 | 188.35 | 69.98 | 0.00 | 0.00 | 744.00 |
June | 189.10 | 73.42 | 115.68 | 178.09 | 61.43 | 0.00 | 0.00 | 720.00 |
July | 234.01 | 123.17 | 110.84 | 246.52 | 62.68 | 0.00 | 0.00 | 744.00 |
August | 193.20 | 98.54 | 94.66 | 206.07 | 63.30 | 0.00 | 0.00 | 744.00 |
September | 157.93 | 75.98 | 81.95 | 151.95 | 80.82 | 0.00 | 0.00 | 720.00 |
October | 89.94 | 36.79 | 53.14 | 70.06 | 85.25 | 0.00 | 0.00 | 744.00 |
November | 44.75 | 12.75 | 32.00 | 19.44 | 104.85 | 0.00 | 0.00 | 720.00 |
December | 37.97 | 13.32 | 24.65 | 15.25 | 136.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 126.00 | 53.92 | 72.08 | 111.87 | 89.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 37.97 | 11.92 | 24.65 | 11.31 | 61.43 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 234.01 | 123.17 | 116.71 | 246.52 | 136.62 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.15 | 11.92 | 28.22 | 11.31 | 135.97 | 0.00 | 0.00 | 744.00 |
February | 71.32 | 26.57 | 44.76 | 40.30 | 115.09 | 0.00 | 0.00 | 672.00 |
March | 100.46 | 33.94 | 66.52 | 72.51 | 90.64 | 0.00 | 0.00 | 744.00 |
April | 152.51 | 58.19 | 94.32 | 136.89 | 73.25 | 0.00 | 0.00 | 720.00 |
May | 196.69 | 79.98 | 116.71 | 188.35 | 69.98 | 0.00 | 0.00 | 744.00 |
June | 189.10 | 73.42 | 115.68 | 178.09 | 61.43 | 0.00 | 0.00 | 720.00 |
July | 234.01 | 123.17 | 110.84 | 246.52 | 62.68 | 0.00 | 0.00 | 744.00 |
August | 193.20 | 98.54 | 94.66 | 206.07 | 63.30 | 0.00 | 0.00 | 744.00 |
September | 157.93 | 75.98 | 81.95 | 151.95 | 80.82 | 0.00 | 0.00 | 720.00 |
October | 89.94 | 36.79 | 53.14 | 70.06 | 85.25 | 0.00 | 0.00 | 744.00 |
November | 44.75 | 12.75 | 32.00 | 19.44 | 104.85 | 0.00 | 0.00 | 720.00 |
December | 37.97 | 13.32 | 24.65 | 15.25 | 136.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 126.00 | 53.92 | 72.08 | 111.87 | 89.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 37.97 | 11.92 | 24.65 | 11.31 | 61.43 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 234.01 | 123.17 | 116.71 | 246.52 | 136.62 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.76 | 0.00 | 13.76 | 0.28 | 83.56 | 0.00 | 0.00 | 744.00 |
February | 21.40 | 0.00 | 21.40 | 3.30 | 71.66 | 0.00 | 0.00 | 672.00 |
March | 31.54 | 0.00 | 31.54 | 10.84 | 54.81 | 0.00 | 0.00 | 744.00 |
April | 44.70 | 0.21 | 44.48 | 25.41 | 42.97 | 0.00 | 0.00 | 720.00 |
May | 57.39 | 1.67 | 55.72 | 36.15 | 40.02 | 0.00 | 0.00 | 744.00 |
June | 60.37 | 3.97 | 56.40 | 37.98 | 33.92 | 0.00 | 0.00 | 720.00 |
July | 57.43 | 4.51 | 52.91 | 38.84 | 34.89 | 0.00 | 0.00 | 744.00 |
August | 46.65 | 1.42 | 45.23 | 34.36 | 36.07 | 0.00 | 0.00 | 744.00 |
September | 36.10 | 0.02 | 36.08 | 18.61 | 48.27 | 0.00 | 0.00 | 720.00 |
October | 24.72 | 0.00 | 24.72 | 8.55 | 51.06 | 0.00 | 0.00 | 744.00 |
November | 15.57 | 0.00 | 15.57 | 1.68 | 63.90 | 0.00 | 0.00 | 720.00 |
December | 11.69 | 0.00 | 11.69 | 0.17 | 82.97 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 35.18 | 0.99 | 34.19 | 18.10 | 53.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 11.69 | 0.00 | 11.69 | 0.17 | 33.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 60.37 | 4.51 | 56.40 | 38.84 | 83.56 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.75 | 0.00 | 13.75 | 0.28 | 83.56 | 0.00 | 0.00 | 744.00 |
February | 21.40 | 0.00 | 21.40 | 3.30 | 71.66 | 0.00 | 0.00 | 672.00 |
March | 31.54 | 0.00 | 31.54 | 10.84 | 54.81 | 0.00 | 0.00 | 744.00 |
April | 44.70 | 0.21 | 44.48 | 25.41 | 42.97 | 0.00 | 0.00 | 720.00 |
May | 57.39 | 1.67 | 55.71 | 36.15 | 40.02 | 0.00 | 0.00 | 744.00 |
June | 60.37 | 3.97 | 56.40 | 37.98 | 33.92 | 0.00 | 0.00 | 720.00 |
July | 57.42 | 4.51 | 52.91 | 38.84 | 34.89 | 0.00 | 0.00 | 744.00 |
August | 46.65 | 1.42 | 45.23 | 34.36 | 36.07 | 0.00 | 0.00 | 744.00 |
September | 36.10 | 0.02 | 36.08 | 18.61 | 48.27 | 0.00 | 0.00 | 720.00 |
October | 24.72 | 0.00 | 24.72 | 8.55 | 51.06 | 0.00 | 0.00 | 744.00 |
November | 15.57 | 0.00 | 15.57 | 1.68 | 63.90 | 0.00 | 0.00 | 720.00 |
December | 11.69 | 0.00 | 11.69 | 0.17 | 82.97 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 35.18 | 0.99 | 34.19 | 18.10 | 53.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 11.69 | 0.00 | 11.69 | 0.17 | 33.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 60.37 | 4.51 | 56.40 | 38.84 | 83.56 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.94 | 2.72 | 11.22 | 6.14 | 27.70 | 0.00 | 0.00 | 744.00 |
February | 24.94 | 8.29 | 16.66 | 17.01 | 25.43 | 25.67 | 0.00 | 672.00 |
March | 43.67 | 18.74 | 24.93 | 40.24 | 22.26 | 0.00 | 0.00 | 744.00 |
April | 69.54 | 35.42 | 34.13 | 72.84 | 19.73 | 0.00 | 0.00 | 720.00 |
May | 90.34 | 46.61 | 43.73 | 96.14 | 22.07 | 0.00 | 0.00 | 744.00 |
June | 98.99 | 58.09 | 40.90 | 106.43 | 20.39 | 0.00 | 0.00 | 720.00 |
July | 103.26 | 68.17 | 35.09 | 112.03 | 23.54 | 0.00 | 0.00 | 744.00 |
August | 82.81 | 52.68 | 30.12 | 85.95 | 26.07 | 0.00 | 0.00 | 744.00 |
September | 58.23 | 32.34 | 25.89 | 53.28 | 30.94 | 0.00 | 0.00 | 720.00 |
October | 34.37 | 16.05 | 18.32 | 27.85 | 26.61 | 0.00 | 0.00 | 744.00 |
November | 16.75 | 4.10 | 12.65 | 9.58 | 22.98 | 9.33 | 0.00 | 720.00 |
December | 12.04 | 2.90 | 9.14 | 4.66 | 27.63 | 8.17 | 0.00 | 744.00 |
Annual Sum or Average | 54.24 | 28.97 | 25.27 | 52.89 | 24.62 | 43.17 | 0.00 | 8760.00 |
Minimum of Months | 12.04 | 2.72 | 9.14 | 4.66 | 19.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.26 | 68.17 | 43.73 | 112.03 | 30.94 | 25.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.94 | 2.72 | 11.22 | 6.14 | 27.70 | 0.00 | 0.00 | 744.00 |
February | 24.94 | 8.29 | 16.66 | 17.01 | 25.43 | 25.67 | 0.00 | 672.00 |
March | 43.67 | 18.74 | 24.93 | 40.24 | 22.26 | 0.00 | 0.00 | 744.00 |
April | 69.54 | 35.42 | 34.13 | 72.84 | 19.73 | 0.00 | 0.00 | 720.00 |
May | 90.34 | 46.61 | 43.73 | 96.14 | 22.07 | 0.00 | 0.00 | 744.00 |
June | 98.99 | 58.09 | 40.90 | 106.43 | 20.39 | 0.00 | 0.00 | 720.00 |
July | 103.26 | 68.17 | 35.09 | 112.03 | 23.54 | 0.00 | 0.00 | 744.00 |
August | 82.81 | 52.68 | 30.12 | 85.95 | 26.07 | 0.00 | 0.00 | 744.00 |
September | 58.23 | 32.34 | 25.89 | 53.28 | 30.94 | 0.00 | 0.00 | 720.00 |
October | 34.37 | 16.05 | 18.32 | 27.85 | 26.61 | 0.00 | 0.00 | 744.00 |
November | 16.75 | 4.10 | 12.65 | 9.58 | 22.98 | 9.33 | 0.00 | 720.00 |
December | 12.04 | 2.90 | 9.14 | 4.66 | 27.63 | 8.17 | 0.00 | 744.00 |
Annual Sum or Average | 54.24 | 28.97 | 25.27 | 52.89 | 24.62 | 43.17 | 0.00 | 8760.00 |
Minimum of Months | 12.04 | 2.72 | 9.14 | 4.66 | 19.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.26 | 68.17 | 43.73 | 112.03 | 30.94 | 25.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.94 | 2.72 | 11.22 | 6.14 | 27.70 | 0.00 | 0.00 | 744.00 |
February | 24.94 | 8.29 | 16.66 | 17.01 | 25.43 | 25.67 | 0.00 | 672.00 |
March | 43.67 | 18.74 | 24.93 | 40.24 | 22.26 | 0.00 | 0.00 | 744.00 |
April | 69.54 | 35.42 | 34.13 | 72.84 | 19.73 | 0.00 | 0.00 | 720.00 |
May | 90.34 | 46.61 | 43.73 | 96.14 | 22.07 | 0.00 | 0.00 | 744.00 |
June | 98.99 | 58.09 | 40.90 | 106.43 | 20.39 | 0.00 | 0.00 | 720.00 |
July | 103.26 | 68.17 | 35.09 | 112.03 | 23.54 | 0.00 | 0.00 | 744.00 |
August | 82.81 | 52.68 | 30.12 | 85.95 | 26.07 | 0.00 | 0.00 | 744.00 |
September | 58.23 | 32.34 | 25.89 | 53.28 | 30.94 | 0.00 | 0.00 | 720.00 |
October | 34.37 | 16.05 | 18.32 | 27.85 | 26.61 | 0.00 | 0.00 | 744.00 |
November | 16.75 | 4.10 | 12.65 | 9.58 | 22.98 | 9.33 | 0.00 | 720.00 |
December | 12.04 | 2.90 | 9.14 | 4.66 | 27.63 | 8.17 | 0.00 | 744.00 |
Annual Sum or Average | 54.24 | 28.97 | 25.27 | 52.89 | 24.62 | 43.17 | 0.00 | 8760.00 |
Minimum of Months | 12.04 | 2.72 | 9.14 | 4.66 | 19.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.26 | 68.17 | 43.73 | 112.03 | 30.94 | 25.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.94 | 2.72 | 11.22 | 6.14 | 27.70 | 0.00 | 0.00 | 744.00 |
February | 24.94 | 8.29 | 16.66 | 17.01 | 25.43 | 25.67 | 0.00 | 672.00 |
March | 43.67 | 18.74 | 24.93 | 40.24 | 22.26 | 0.00 | 0.00 | 744.00 |
April | 69.54 | 35.42 | 34.13 | 72.84 | 19.73 | 0.00 | 0.00 | 720.00 |
May | 90.34 | 46.61 | 43.73 | 96.14 | 22.07 | 0.00 | 0.00 | 744.00 |
June | 98.99 | 58.09 | 40.90 | 106.43 | 20.39 | 0.00 | 0.00 | 720.00 |
July | 103.26 | 68.17 | 35.09 | 112.03 | 23.54 | 0.00 | 0.00 | 744.00 |
August | 82.81 | 52.68 | 30.12 | 85.95 | 26.07 | 0.00 | 0.00 | 744.00 |
September | 58.23 | 32.34 | 25.89 | 53.28 | 30.94 | 0.00 | 0.00 | 720.00 |
October | 34.37 | 16.05 | 18.32 | 27.85 | 26.61 | 0.00 | 0.00 | 744.00 |
November | 16.75 | 4.10 | 12.65 | 9.58 | 22.98 | 9.33 | 0.00 | 720.00 |
December | 12.04 | 2.90 | 9.14 | 4.66 | 27.63 | 8.17 | 0.00 | 744.00 |
Annual Sum or Average | 54.24 | 28.97 | 25.27 | 52.89 | 24.62 | 43.17 | 0.00 | 8760.00 |
Minimum of Months | 12.04 | 2.72 | 9.14 | 4.66 | 19.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.26 | 68.17 | 43.73 | 112.03 | 30.94 | 25.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.94 | 2.72 | 11.22 | 6.14 | 27.70 | 0.00 | 0.00 | 744.00 |
February | 24.94 | 8.29 | 16.66 | 17.01 | 25.43 | 25.67 | 0.00 | 672.00 |
March | 43.67 | 18.74 | 24.93 | 40.24 | 22.26 | 0.00 | 0.00 | 744.00 |
April | 69.54 | 35.42 | 34.13 | 72.84 | 19.73 | 0.00 | 0.00 | 720.00 |
May | 90.34 | 46.61 | 43.73 | 96.14 | 22.07 | 0.00 | 0.00 | 744.00 |
June | 98.99 | 58.09 | 40.90 | 106.43 | 20.39 | 0.00 | 0.00 | 720.00 |
July | 103.26 | 68.17 | 35.09 | 112.03 | 23.54 | 0.00 | 0.00 | 744.00 |
August | 82.81 | 52.68 | 30.12 | 85.95 | 26.07 | 0.00 | 0.00 | 744.00 |
September | 58.23 | 32.34 | 25.89 | 53.28 | 30.94 | 0.00 | 0.00 | 720.00 |
October | 34.37 | 16.05 | 18.32 | 27.85 | 26.61 | 0.00 | 0.00 | 744.00 |
November | 16.75 | 4.10 | 12.65 | 9.58 | 22.98 | 9.33 | 0.00 | 720.00 |
December | 12.04 | 2.90 | 9.14 | 4.66 | 27.63 | 8.17 | 0.00 | 744.00 |
Annual Sum or Average | 54.24 | 28.97 | 25.27 | 52.89 | 24.62 | 43.17 | 0.00 | 8760.00 |
Minimum of Months | 12.04 | 2.72 | 9.14 | 4.66 | 19.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.26 | 68.17 | 43.73 | 112.03 | 30.94 | 25.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.94 | 2.72 | 11.22 | 6.14 | 27.70 | 0.00 | 0.00 | 744.00 |
February | 24.94 | 8.29 | 16.66 | 17.01 | 25.43 | 25.67 | 0.00 | 672.00 |
March | 43.67 | 18.74 | 24.93 | 40.24 | 22.26 | 0.00 | 0.00 | 744.00 |
April | 69.54 | 35.42 | 34.13 | 72.84 | 19.73 | 0.00 | 0.00 | 720.00 |
May | 90.34 | 46.61 | 43.73 | 96.14 | 22.07 | 0.00 | 0.00 | 744.00 |
June | 98.99 | 58.09 | 40.90 | 106.43 | 20.39 | 0.00 | 0.00 | 720.00 |
July | 103.26 | 68.17 | 35.09 | 112.03 | 23.54 | 0.00 | 0.00 | 744.00 |
August | 82.81 | 52.68 | 30.12 | 85.95 | 26.07 | 0.00 | 0.00 | 744.00 |
September | 58.23 | 32.34 | 25.89 | 53.28 | 30.94 | 0.00 | 0.00 | 720.00 |
October | 34.37 | 16.05 | 18.32 | 27.85 | 26.61 | 0.00 | 0.00 | 744.00 |
November | 16.75 | 4.10 | 12.65 | 9.58 | 22.98 | 9.33 | 0.00 | 720.00 |
December | 12.04 | 2.90 | 9.14 | 4.66 | 27.63 | 8.17 | 0.00 | 744.00 |
Annual Sum or Average | 54.24 | 28.97 | 25.27 | 52.89 | 24.62 | 43.17 | 0.00 | 8760.00 |
Minimum of Months | 12.04 | 2.72 | 9.14 | 4.66 | 19.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.26 | 68.17 | 43.73 | 112.03 | 30.94 | 25.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.94 | 2.72 | 11.22 | 6.14 | 27.70 | 0.00 | 0.00 | 744.00 |
February | 24.94 | 8.29 | 16.66 | 17.01 | 25.43 | 25.67 | 0.00 | 672.00 |
March | 43.67 | 18.74 | 24.93 | 40.24 | 22.26 | 0.00 | 0.00 | 744.00 |
April | 69.54 | 35.42 | 34.13 | 72.84 | 19.73 | 0.00 | 0.00 | 720.00 |
May | 90.34 | 46.61 | 43.73 | 96.14 | 22.07 | 0.00 | 0.00 | 744.00 |
June | 98.99 | 58.09 | 40.90 | 106.43 | 20.39 | 0.00 | 0.00 | 720.00 |
July | 103.26 | 68.17 | 35.09 | 112.03 | 23.54 | 0.00 | 0.00 | 744.00 |
August | 82.81 | 52.68 | 30.12 | 85.95 | 26.07 | 0.00 | 0.00 | 744.00 |
September | 58.23 | 32.34 | 25.89 | 53.28 | 30.94 | 0.00 | 0.00 | 720.00 |
October | 34.37 | 16.05 | 18.32 | 27.85 | 26.61 | 0.00 | 0.00 | 744.00 |
November | 16.75 | 4.10 | 12.65 | 9.58 | 22.98 | 9.33 | 0.00 | 720.00 |
December | 12.04 | 2.90 | 9.14 | 4.66 | 27.63 | 8.17 | 0.00 | 744.00 |
Annual Sum or Average | 54.24 | 28.97 | 25.27 | 52.89 | 24.62 | 43.17 | 0.00 | 8760.00 |
Minimum of Months | 12.04 | 2.72 | 9.14 | 4.66 | 19.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.26 | 68.17 | 43.73 | 112.03 | 30.94 | 25.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.94 | 2.72 | 11.22 | 6.14 | 27.70 | 0.00 | 0.00 | 744.00 |
February | 24.94 | 8.29 | 16.66 | 17.01 | 25.43 | 25.67 | 0.00 | 672.00 |
March | 43.67 | 18.74 | 24.93 | 40.24 | 22.26 | 0.00 | 0.00 | 744.00 |
April | 69.54 | 35.42 | 34.13 | 72.84 | 19.73 | 0.00 | 0.00 | 720.00 |
May | 90.34 | 46.61 | 43.73 | 96.14 | 22.07 | 0.00 | 0.00 | 744.00 |
June | 98.99 | 58.09 | 40.90 | 106.43 | 20.39 | 0.00 | 0.00 | 720.00 |
July | 103.26 | 68.17 | 35.09 | 112.03 | 23.54 | 0.00 | 0.00 | 744.00 |
August | 82.81 | 52.68 | 30.12 | 85.95 | 26.07 | 0.00 | 0.00 | 744.00 |
September | 58.23 | 32.34 | 25.89 | 53.28 | 30.94 | 0.00 | 0.00 | 720.00 |
October | 34.37 | 16.05 | 18.32 | 27.85 | 26.61 | 0.00 | 0.00 | 744.00 |
November | 16.75 | 4.10 | 12.65 | 9.58 | 22.98 | 9.33 | 0.00 | 720.00 |
December | 12.04 | 2.90 | 9.14 | 4.66 | 27.63 | 8.17 | 0.00 | 744.00 |
Annual Sum or Average | 54.24 | 28.97 | 25.27 | 52.89 | 24.62 | 43.17 | 0.00 | 8760.00 |
Minimum of Months | 12.04 | 2.72 | 9.14 | 4.66 | 19.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.26 | 68.17 | 43.73 | 112.03 | 30.94 | 25.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.94 | 2.72 | 11.22 | 6.14 | 27.70 | 0.00 | 0.00 | 744.00 |
February | 24.94 | 8.29 | 16.66 | 17.01 | 25.43 | 25.67 | 0.00 | 672.00 |
March | 43.67 | 18.74 | 24.93 | 40.24 | 22.26 | 0.00 | 0.00 | 744.00 |
April | 69.54 | 35.42 | 34.13 | 72.84 | 19.73 | 0.00 | 0.00 | 720.00 |
May | 90.34 | 46.61 | 43.73 | 96.14 | 22.07 | 0.00 | 0.00 | 744.00 |
June | 98.99 | 58.09 | 40.90 | 106.43 | 20.39 | 0.00 | 0.00 | 720.00 |
July | 103.26 | 68.17 | 35.09 | 112.03 | 23.54 | 0.00 | 0.00 | 744.00 |
August | 82.81 | 52.68 | 30.12 | 85.95 | 26.07 | 0.00 | 0.00 | 744.00 |
September | 58.23 | 32.34 | 25.89 | 53.28 | 30.94 | 0.00 | 0.00 | 720.00 |
October | 34.37 | 16.05 | 18.32 | 27.85 | 26.61 | 0.00 | 0.00 | 744.00 |
November | 16.75 | 4.10 | 12.65 | 9.58 | 22.98 | 9.33 | 0.00 | 720.00 |
December | 12.04 | 2.90 | 9.14 | 4.66 | 27.63 | 8.17 | 0.00 | 744.00 |
Annual Sum or Average | 54.24 | 28.97 | 25.27 | 52.89 | 24.62 | 43.17 | 0.00 | 8760.00 |
Minimum of Months | 12.04 | 2.72 | 9.14 | 4.66 | 19.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.26 | 68.17 | 43.73 | 112.03 | 30.94 | 25.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.94 | 2.72 | 11.22 | 6.14 | 27.70 | 0.00 | 0.00 | 744.00 |
February | 24.94 | 8.29 | 16.66 | 17.01 | 25.43 | 25.67 | 0.00 | 672.00 |
March | 43.67 | 18.74 | 24.93 | 40.24 | 22.26 | 0.00 | 0.00 | 744.00 |
April | 69.54 | 35.42 | 34.13 | 72.84 | 19.73 | 0.00 | 0.00 | 720.00 |
May | 90.34 | 46.61 | 43.73 | 96.14 | 22.07 | 0.00 | 0.00 | 744.00 |
June | 98.99 | 58.09 | 40.90 | 106.43 | 20.39 | 0.00 | 0.00 | 720.00 |
July | 103.26 | 68.17 | 35.09 | 112.03 | 23.54 | 0.00 | 0.00 | 744.00 |
August | 82.81 | 52.68 | 30.12 | 85.95 | 26.07 | 0.00 | 0.00 | 744.00 |
September | 58.23 | 32.34 | 25.89 | 53.28 | 30.94 | 0.00 | 0.00 | 720.00 |
October | 34.37 | 16.05 | 18.32 | 27.85 | 26.61 | 0.00 | 0.00 | 744.00 |
November | 16.75 | 4.10 | 12.65 | 9.58 | 22.98 | 9.33 | 0.00 | 720.00 |
December | 12.04 | 2.90 | 9.14 | 4.66 | 27.63 | 8.17 | 0.00 | 744.00 |
Annual Sum or Average | 54.24 | 28.97 | 25.27 | 52.89 | 24.62 | 43.17 | 0.00 | 8760.00 |
Minimum of Months | 12.04 | 2.72 | 9.14 | 4.66 | 19.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.26 | 68.17 | 43.73 | 112.03 | 30.94 | 25.67 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107530E+09 | 31932813.31 | 75597140.08 | 30285988.50 | 0.364192E+09 |
February | 0.172548E+09 | 64274480.72 | 0.108273E+09 | 97486898.80 | 0.278428E+09 |
March | 0.269085E+09 | 90916379.26 | 0.178169E+09 | 0.194217E+09 | 0.242759E+09 |
April | 0.395301E+09 | 0.150836E+09 | 0.244465E+09 | 0.354823E+09 | 0.189859E+09 |
May | 0.526813E+09 | 0.214221E+09 | 0.312592E+09 | 0.504481E+09 | 0.187432E+09 |
June | 0.490142E+09 | 0.190293E+09 | 0.299849E+09 | 0.461615E+09 | 0.159225E+09 |
July | 0.626759E+09 | 0.329887E+09 | 0.296872E+09 | 0.660287E+09 | 0.167870E+09 |
August | 0.517457E+09 | 0.263931E+09 | 0.253526E+09 | 0.551934E+09 | 0.169543E+09 |
September | 0.409354E+09 | 0.196946E+09 | 0.212407E+09 | 0.393855E+09 | 0.209483E+09 |
October | 0.240883E+09 | 98546732.52 | 0.142336E+09 | 0.187643E+09 | 0.228337E+09 |
November | 0.115997E+09 | 33047661.25 | 82949087.15 | 50381536.98 | 0.271773E+09 |
December | 0.101696E+09 | 35678686.50 | 66017323.83 | 40835183.22 | 0.365932E+09 |
Annual Sum or Average | 0.397356E+10 | 0.170051E+10 | 0.227305E+10 | 0.352784E+10 | 0.283483E+10 |
Minimum of Months | 0.101696E+09 | 31932813.31 | 66017323.83 | 30285988.50 | 0.159225E+09 |
Maximum of Months | 0.626759E+09 | 0.329887E+09 | 0.312592E+09 | 0.660287E+09 | 0.365932E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107530E+09 | 31932813.31 | 75597140.08 | 30285988.50 | 0.364192E+09 |
February | 0.172548E+09 | 64274480.72 | 0.108273E+09 | 97486898.80 | 0.278428E+09 |
March | 0.269085E+09 | 90916379.26 | 0.178169E+09 | 0.194217E+09 | 0.242759E+09 |
April | 0.395301E+09 | 0.150836E+09 | 0.244465E+09 | 0.354823E+09 | 0.189859E+09 |
May | 0.526813E+09 | 0.214221E+09 | 0.312592E+09 | 0.504481E+09 | 0.187432E+09 |
June | 0.490142E+09 | 0.190293E+09 | 0.299849E+09 | 0.461615E+09 | 0.159225E+09 |
July | 0.626759E+09 | 0.329887E+09 | 0.296872E+09 | 0.660287E+09 | 0.167870E+09 |
August | 0.517457E+09 | 0.263931E+09 | 0.253526E+09 | 0.551934E+09 | 0.169543E+09 |
September | 0.409354E+09 | 0.196946E+09 | 0.212407E+09 | 0.393855E+09 | 0.209483E+09 |
October | 0.240883E+09 | 98546732.52 | 0.142336E+09 | 0.187643E+09 | 0.228337E+09 |
November | 0.115997E+09 | 33047661.25 | 82949087.15 | 50381536.98 | 0.271773E+09 |
December | 0.101696E+09 | 35678686.50 | 66017323.83 | 40835183.22 | 0.365932E+09 |
Annual Sum or Average | 0.397356E+10 | 0.170051E+10 | 0.227305E+10 | 0.352784E+10 | 0.283483E+10 |
Minimum of Months | 0.101696E+09 | 31932813.31 | 66017323.83 | 30285988.50 | 0.159225E+09 |
Maximum of Months | 0.626759E+09 | 0.329887E+09 | 0.312592E+09 | 0.660287E+09 | 0.365932E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36842037.10 | 0.00 | 36842037.10 | 740867.45 | 0.223795E+09 |
February | 51779429.29 | 0.00 | 51779429.29 | 7993830.05 | 0.173357E+09 |
March | 84474702.76 | 1613.93 | 84473088.83 | 29043796.73 | 0.146805E+09 |
April | 0.115855E+09 | 556829.82 | 0.115298E+09 | 65873292.69 | 0.111385E+09 |
May | 0.153715E+09 | 4484182.11 | 0.149231E+09 | 96830271.30 | 0.107180E+09 |
June | 0.156481E+09 | 10281295.54 | 0.146200E+09 | 98444266.66 | 87924904.31 |
July | 0.153810E+09 | 12086982.54 | 0.141723E+09 | 0.104030E+09 | 93443674.62 |
August | 0.124946E+09 | 3796729.99 | 0.121149E+09 | 92041650.58 | 96609899.90 |
September | 93576000.29 | 59143.22 | 93516857.08 | 48244509.72 | 0.125129E+09 |
October | 66218358.03 | 0.00 | 66218358.03 | 22898088.17 | 0.136756E+09 |
November | 40365490.15 | 0.00 | 40365490.15 | 4345401.18 | 0.165630E+09 |
December | 31306230.85 | 0.00 | 31306230.85 | 451373.70 | 0.222224E+09 |
Annual Sum or Average | 0.110937E+10 | 31266777.14 | 0.107810E+10 | 0.570937E+09 | 0.169024E+10 |
Minimum of Months | 31306230.85 | 0.00 | 31306230.85 | 451373.70 | 87924904.31 |
Maximum of Months | 0.156481E+09 | 12086982.54 | 0.149231E+09 | 0.104030E+09 | 0.223795E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36840747.14 | 0.00 | 36840747.14 | 740738.77 | 0.223796E+09 |
February | 51777702.37 | 0.00 | 51777702.37 | 7993173.92 | 0.173358E+09 |
March | 84471960.57 | 1613.86 | 84470346.71 | 29041793.00 | 0.146805E+09 |
April | 0.115851E+09 | 556803.72 | 0.115294E+09 | 65870165.47 | 0.111384E+09 |
May | 0.153710E+09 | 4483971.93 | 0.149226E+09 | 96825857.18 | 0.107180E+09 |
June | 0.156476E+09 | 10280813.64 | 0.146196E+09 | 98439891.73 | 87924732.10 |
July | 0.153805E+09 | 12086416.00 | 0.141719E+09 | 0.104026E+09 | 93443499.67 |
August | 0.124942E+09 | 3796552.03 | 0.121145E+09 | 92038613.91 | 96609578.13 |
September | 93573172.24 | 59140.44 | 93514031.80 | 48242187.27 | 0.125128E+09 |
October | 66216244.03 | 0.00 | 66216244.03 | 22896556.86 | 0.136755E+09 |
November | 40364087.23 | 0.00 | 40364087.23 | 4344929.97 | 0.165630E+09 |
December | 31305150.45 | 0.00 | 31305150.45 | 451312.80 | 0.222224E+09 |
Annual Sum or Average | 0.110933E+10 | 31265311.63 | 0.107807E+10 | 0.570911E+09 | 0.169024E+10 |
Minimum of Months | 31305150.45 | 0.00 | 31305150.45 | 451312.80 | 87924732.10 |
Maximum of Months | 0.156476E+09 | 12086416.00 | 0.149226E+09 | 0.104026E+09 | 0.223796E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37338545.83 | 7289164.64 | 30049381.18 | 16447890.96 | 74194535.95 |
February | 60337538.71 | 20043618.21 | 40293920.50 | 41139068.07 | 61516399.91 |
March | 0.116969E+09 | 50199886.07 | 66769444.36 | 0.107784E+09 | 59621665.52 |
April | 0.180251E+09 | 91796712.14 | 88454369.30 | 0.188812E+09 | 51140753.49 |
May | 0.241978E+09 | 0.124846E+09 | 0.117132E+09 | 0.257505E+09 | 59116948.63 |
June | 0.256573E+09 | 0.150567E+09 | 0.106006E+09 | 0.275863E+09 | 52843380.43 |
July | 0.276571E+09 | 0.182598E+09 | 93972880.80 | 0.300057E+09 | 63058985.59 |
August | 0.221787E+09 | 0.141109E+09 | 80678481.64 | 0.230201E+09 | 69829344.63 |
September | 0.150926E+09 | 83827044.47 | 67098812.38 | 0.138114E+09 | 80202509.40 |
October | 92069048.84 | 42992934.59 | 49076114.25 | 74599722.07 | 71280232.82 |
November | 43407313.17 | 10621967.01 | 32785346.16 | 24836384.64 | 59572526.89 |
December | 32255910.17 | 7771725.19 | 24484184.97 | 12475211.37 | 74011710.48 |
Annual Sum or Average | 0.171046E+10 | 0.913663E+09 | 0.796800E+09 | 0.166783E+10 | 0.776389E+09 |
Minimum of Months | 32255910.17 | 7289164.64 | 24484184.97 | 12475211.37 | 51140753.49 |
Maximum of Months | 0.276571E+09 | 0.182598E+09 | 0.117132E+09 | 0.300057E+09 | 80202509.40 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37338545.83 | 7289164.64 | 30049381.18 | 16447890.96 | 74194535.95 |
February | 60337538.71 | 20043618.21 | 40293920.50 | 41139068.07 | 61516399.91 |
March | 0.116969E+09 | 50199886.07 | 66769444.36 | 0.107784E+09 | 59621665.52 |
April | 0.180251E+09 | 91796712.14 | 88454369.30 | 0.188812E+09 | 51140753.49 |
May | 0.241978E+09 | 0.124846E+09 | 0.117132E+09 | 0.257505E+09 | 59116948.63 |
June | 0.256573E+09 | 0.150567E+09 | 0.106006E+09 | 0.275863E+09 | 52843380.43 |
July | 0.276571E+09 | 0.182598E+09 | 93972880.80 | 0.300057E+09 | 63058985.59 |
August | 0.221787E+09 | 0.141109E+09 | 80678481.64 | 0.230201E+09 | 69829344.63 |
September | 0.150926E+09 | 83827044.47 | 67098812.38 | 0.138114E+09 | 80202509.40 |
October | 92069048.84 | 42992934.59 | 49076114.25 | 74599722.07 | 71280232.82 |
November | 43407313.17 | 10621967.01 | 32785346.16 | 24836384.64 | 59572526.89 |
December | 32255910.17 | 7771725.19 | 24484184.97 | 12475211.37 | 74011710.48 |
Annual Sum or Average | 0.171046E+10 | 0.913663E+09 | 0.796800E+09 | 0.166783E+10 | 0.776389E+09 |
Minimum of Months | 32255910.17 | 7289164.64 | 24484184.97 | 12475211.37 | 51140753.49 |
Maximum of Months | 0.276571E+09 | 0.182598E+09 | 0.117132E+09 | 0.300057E+09 | 80202509.40 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37338545.83 | 7289164.64 | 30049381.18 | 16447890.96 | 74194535.95 |
February | 60337538.71 | 20043618.21 | 40293920.50 | 41139068.07 | 61516399.91 |
March | 0.116969E+09 | 50199886.07 | 66769444.36 | 0.107784E+09 | 59621665.52 |
April | 0.180251E+09 | 91796712.14 | 88454369.30 | 0.188812E+09 | 51140753.49 |
May | 0.241978E+09 | 0.124846E+09 | 0.117132E+09 | 0.257505E+09 | 59116948.63 |
June | 0.256573E+09 | 0.150567E+09 | 0.106006E+09 | 0.275863E+09 | 52843380.43 |
July | 0.276571E+09 | 0.182598E+09 | 93972880.80 | 0.300057E+09 | 63058985.59 |
August | 0.221787E+09 | 0.141109E+09 | 80678481.64 | 0.230201E+09 | 69829344.63 |
September | 0.150926E+09 | 83827044.47 | 67098812.38 | 0.138114E+09 | 80202509.40 |
October | 92069048.84 | 42992934.59 | 49076114.25 | 74599722.07 | 71280232.82 |
November | 43407313.17 | 10621967.01 | 32785346.16 | 24836384.64 | 59572526.89 |
December | 32255910.17 | 7771725.19 | 24484184.97 | 12475211.37 | 74011710.48 |
Annual Sum or Average | 0.171046E+10 | 0.913663E+09 | 0.796800E+09 | 0.166783E+10 | 0.776389E+09 |
Minimum of Months | 32255910.17 | 7289164.64 | 24484184.97 | 12475211.37 | 51140753.49 |
Maximum of Months | 0.276571E+09 | 0.182598E+09 | 0.117132E+09 | 0.300057E+09 | 80202509.40 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37338545.83 | 7289164.64 | 30049381.18 | 16447890.96 | 74194535.95 |
February | 60337538.71 | 20043618.21 | 40293920.50 | 41139068.07 | 61516399.91 |
March | 0.116969E+09 | 50199886.07 | 66769444.36 | 0.107784E+09 | 59621665.52 |
April | 0.180251E+09 | 91796712.14 | 88454369.30 | 0.188812E+09 | 51140753.49 |
May | 0.241978E+09 | 0.124846E+09 | 0.117132E+09 | 0.257505E+09 | 59116948.63 |
June | 0.256573E+09 | 0.150567E+09 | 0.106006E+09 | 0.275863E+09 | 52843380.43 |
July | 0.276571E+09 | 0.182598E+09 | 93972880.80 | 0.300057E+09 | 63058985.59 |
August | 0.221787E+09 | 0.141109E+09 | 80678481.64 | 0.230201E+09 | 69829344.63 |
September | 0.150926E+09 | 83827044.47 | 67098812.38 | 0.138114E+09 | 80202509.40 |
October | 92069048.84 | 42992934.59 | 49076114.25 | 74599722.07 | 71280232.82 |
November | 43407313.17 | 10621967.01 | 32785346.16 | 24836384.64 | 59572526.89 |
December | 32255910.17 | 7771725.19 | 24484184.97 | 12475211.37 | 74011710.48 |
Annual Sum or Average | 0.171046E+10 | 0.913663E+09 | 0.796800E+09 | 0.166783E+10 | 0.776389E+09 |
Minimum of Months | 32255910.17 | 7289164.64 | 24484184.97 | 12475211.37 | 51140753.49 |
Maximum of Months | 0.276571E+09 | 0.182598E+09 | 0.117132E+09 | 0.300057E+09 | 80202509.40 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37338545.83 | 7289164.64 | 30049381.18 | 16447890.96 | 74194535.95 |
February | 60337538.71 | 20043618.21 | 40293920.50 | 41139068.07 | 61516399.91 |
March | 0.116969E+09 | 50199886.07 | 66769444.36 | 0.107784E+09 | 59621665.52 |
April | 0.180251E+09 | 91796712.14 | 88454369.30 | 0.188812E+09 | 51140753.49 |
May | 0.241978E+09 | 0.124846E+09 | 0.117132E+09 | 0.257505E+09 | 59116948.63 |
June | 0.256573E+09 | 0.150567E+09 | 0.106006E+09 | 0.275863E+09 | 52843380.43 |
July | 0.276571E+09 | 0.182598E+09 | 93972880.80 | 0.300057E+09 | 63058985.59 |
August | 0.221787E+09 | 0.141109E+09 | 80678481.64 | 0.230201E+09 | 69829344.63 |
September | 0.150926E+09 | 83827044.47 | 67098812.38 | 0.138114E+09 | 80202509.40 |
October | 92069048.84 | 42992934.59 | 49076114.25 | 74599722.07 | 71280232.82 |
November | 43407313.17 | 10621967.01 | 32785346.16 | 24836384.64 | 59572526.89 |
December | 32255910.17 | 7771725.19 | 24484184.97 | 12475211.37 | 74011710.48 |
Annual Sum or Average | 0.171046E+10 | 0.913663E+09 | 0.796800E+09 | 0.166783E+10 | 0.776389E+09 |
Minimum of Months | 32255910.17 | 7289164.64 | 24484184.97 | 12475211.37 | 51140753.49 |
Maximum of Months | 0.276571E+09 | 0.182598E+09 | 0.117132E+09 | 0.300057E+09 | 80202509.40 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37338545.83 | 7289164.64 | 30049381.18 | 16447890.96 | 74194535.95 |
February | 60337538.71 | 20043618.21 | 40293920.50 | 41139068.07 | 61516399.91 |
March | 0.116969E+09 | 50199886.07 | 66769444.36 | 0.107784E+09 | 59621665.52 |
April | 0.180251E+09 | 91796712.14 | 88454369.30 | 0.188812E+09 | 51140753.49 |
May | 0.241978E+09 | 0.124846E+09 | 0.117132E+09 | 0.257505E+09 | 59116948.63 |
June | 0.256573E+09 | 0.150567E+09 | 0.106006E+09 | 0.275863E+09 | 52843380.43 |
July | 0.276571E+09 | 0.182598E+09 | 93972880.80 | 0.300057E+09 | 63058985.59 |
August | 0.221787E+09 | 0.141109E+09 | 80678481.64 | 0.230201E+09 | 69829344.63 |
September | 0.150926E+09 | 83827044.47 | 67098812.38 | 0.138114E+09 | 80202509.40 |
October | 92069048.84 | 42992934.59 | 49076114.25 | 74599722.07 | 71280232.82 |
November | 43407313.17 | 10621967.01 | 32785346.16 | 24836384.64 | 59572526.89 |
December | 32255910.17 | 7771725.19 | 24484184.97 | 12475211.37 | 74011710.48 |
Annual Sum or Average | 0.171046E+10 | 0.913663E+09 | 0.796800E+09 | 0.166783E+10 | 0.776389E+09 |
Minimum of Months | 32255910.17 | 7289164.64 | 24484184.97 | 12475211.37 | 51140753.49 |
Maximum of Months | 0.276571E+09 | 0.182598E+09 | 0.117132E+09 | 0.300057E+09 | 80202509.40 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37338545.83 | 7289164.64 | 30049381.18 | 16447890.96 | 74194535.95 |
February | 60337538.71 | 20043618.21 | 40293920.50 | 41139068.07 | 61516399.91 |
March | 0.116969E+09 | 50199886.07 | 66769444.36 | 0.107784E+09 | 59621665.52 |
April | 0.180251E+09 | 91796712.14 | 88454369.30 | 0.188812E+09 | 51140753.49 |
May | 0.241978E+09 | 0.124846E+09 | 0.117132E+09 | 0.257505E+09 | 59116948.63 |
June | 0.256573E+09 | 0.150567E+09 | 0.106006E+09 | 0.275863E+09 | 52843380.43 |
July | 0.276571E+09 | 0.182598E+09 | 93972880.80 | 0.300057E+09 | 63058985.59 |
August | 0.221787E+09 | 0.141109E+09 | 80678481.64 | 0.230201E+09 | 69829344.63 |
September | 0.150926E+09 | 83827044.47 | 67098812.38 | 0.138114E+09 | 80202509.40 |
October | 92069048.84 | 42992934.59 | 49076114.25 | 74599722.07 | 71280232.82 |
November | 43407313.17 | 10621967.01 | 32785346.16 | 24836384.64 | 59572526.89 |
December | 32255910.17 | 7771725.19 | 24484184.97 | 12475211.37 | 74011710.48 |
Annual Sum or Average | 0.171046E+10 | 0.913663E+09 | 0.796800E+09 | 0.166783E+10 | 0.776389E+09 |
Minimum of Months | 32255910.17 | 7289164.64 | 24484184.97 | 12475211.37 | 51140753.49 |
Maximum of Months | 0.276571E+09 | 0.182598E+09 | 0.117132E+09 | 0.300057E+09 | 80202509.40 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37338545.83 | 7289164.64 | 30049381.18 | 16447890.96 | 74194535.95 |
February | 60337538.71 | 20043618.21 | 40293920.50 | 41139068.07 | 61516399.91 |
March | 0.116969E+09 | 50199886.07 | 66769444.36 | 0.107784E+09 | 59621665.52 |
April | 0.180251E+09 | 91796712.14 | 88454369.30 | 0.188812E+09 | 51140753.49 |
May | 0.241978E+09 | 0.124846E+09 | 0.117132E+09 | 0.257505E+09 | 59116948.63 |
June | 0.256573E+09 | 0.150567E+09 | 0.106006E+09 | 0.275863E+09 | 52843380.43 |
July | 0.276571E+09 | 0.182598E+09 | 93972880.80 | 0.300057E+09 | 63058985.59 |
August | 0.221787E+09 | 0.141109E+09 | 80678481.64 | 0.230201E+09 | 69829344.63 |
September | 0.150926E+09 | 83827044.47 | 67098812.38 | 0.138114E+09 | 80202509.40 |
October | 92069048.84 | 42992934.59 | 49076114.25 | 74599722.07 | 71280232.82 |
November | 43407313.17 | 10621967.01 | 32785346.16 | 24836384.64 | 59572526.89 |
December | 32255910.17 | 7771725.19 | 24484184.97 | 12475211.37 | 74011710.48 |
Annual Sum or Average | 0.171046E+10 | 0.913663E+09 | 0.796800E+09 | 0.166783E+10 | 0.776389E+09 |
Minimum of Months | 32255910.17 | 7289164.64 | 24484184.97 | 12475211.37 | 51140753.49 |
Maximum of Months | 0.276571E+09 | 0.182598E+09 | 0.117132E+09 | 0.300057E+09 | 80202509.40 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37338545.83 | 7289164.64 | 30049381.18 | 16447890.96 | 74194535.95 |
February | 60337538.71 | 20043618.21 | 40293920.50 | 41139068.07 | 61516399.91 |
March | 0.116969E+09 | 50199886.07 | 66769444.36 | 0.107784E+09 | 59621665.52 |
April | 0.180251E+09 | 91796712.14 | 88454369.30 | 0.188812E+09 | 51140753.49 |
May | 0.241978E+09 | 0.124846E+09 | 0.117132E+09 | 0.257505E+09 | 59116948.63 |
June | 0.256573E+09 | 0.150567E+09 | 0.106006E+09 | 0.275863E+09 | 52843380.43 |
July | 0.276571E+09 | 0.182598E+09 | 93972880.80 | 0.300057E+09 | 63058985.59 |
August | 0.221787E+09 | 0.141109E+09 | 80678481.64 | 0.230201E+09 | 69829344.63 |
September | 0.150926E+09 | 83827044.47 | 67098812.38 | 0.138114E+09 | 80202509.40 |
October | 92069048.84 | 42992934.59 | 49076114.25 | 74599722.07 | 71280232.82 |
November | 43407313.17 | 10621967.01 | 32785346.16 | 24836384.64 | 59572526.89 |
December | 32255910.17 | 7771725.19 | 24484184.97 | 12475211.37 | 74011710.48 |
Annual Sum or Average | 0.171046E+10 | 0.913663E+09 | 0.796800E+09 | 0.166783E+10 | 0.776389E+09 |
Minimum of Months | 32255910.17 | 7289164.64 | 24484184.97 | 12475211.37 | 51140753.49 |
Maximum of Months | 0.276571E+09 | 0.182598E+09 | 0.117132E+09 | 0.300057E+09 | 80202509.40 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37338545.83 | 7289164.64 | 30049381.18 | 16447890.96 | 74194535.95 |
February | 60337538.71 | 20043618.21 | 40293920.50 | 41139068.07 | 61516399.91 |
March | 0.116969E+09 | 50199886.07 | 66769444.36 | 0.107784E+09 | 59621665.52 |
April | 0.180251E+09 | 91796712.14 | 88454369.30 | 0.188812E+09 | 51140753.49 |
May | 0.241978E+09 | 0.124846E+09 | 0.117132E+09 | 0.257505E+09 | 59116948.63 |
June | 0.256573E+09 | 0.150567E+09 | 0.106006E+09 | 0.275863E+09 | 52843380.43 |
July | 0.276571E+09 | 0.182598E+09 | 93972880.80 | 0.300057E+09 | 63058985.59 |
August | 0.221787E+09 | 0.141109E+09 | 80678481.64 | 0.230201E+09 | 69829344.63 |
September | 0.150926E+09 | 83827044.47 | 67098812.38 | 0.138114E+09 | 80202509.40 |
October | 92069048.84 | 42992934.59 | 49076114.25 | 74599722.07 | 71280232.82 |
November | 43407313.17 | 10621967.01 | 32785346.16 | 24836384.64 | 59572526.89 |
December | 32255910.17 | 7771725.19 | 24484184.97 | 12475211.37 | 74011710.48 |
Annual Sum or Average | 0.171046E+10 | 0.913663E+09 | 0.796800E+09 | 0.166783E+10 | 0.776389E+09 |
Minimum of Months | 32255910.17 | 7289164.64 | 24484184.97 | 12475211.37 | 51140753.49 |
Maximum of Months | 0.276571E+09 | 0.182598E+09 | 0.117132E+09 | 0.300057E+09 | 80202509.40 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 17.98 | 433.87 | 107.80 | 23.84 | 83.96 | 0.00 | 0.00 |
February | 81.51 | 367.81 | 185.45 | 53.14 | 132.32 | 0.00 | 0.00 |
March | 163.74 | 287.92 | 264.01 | 67.89 | 196.12 | 0.00 | 0.00 |
April | 323.15 | 230.98 | 394.41 | 116.82 | 277.59 | 0.00 | 0.00 |
May | 448.19 | 219.17 | 508.16 | 163.31 | 344.85 | 0.00 | 0.00 |
June | 430.61 | 189.17 | 498.94 | 154.76 | 344.17 | 0.00 | 0.00 |
July | 569.94 | 194.34 | 582.86 | 255.36 | 327.50 | 0.00 | 0.00 |
August | 480.13 | 198.00 | 479.69 | 199.92 | 279.77 | 0.00 | 0.00 |
September | 339.04 | 256.10 | 388.06 | 152.01 | 236.05 | 0.00 | 0.00 |
October | 154.48 | 269.89 | 229.32 | 73.59 | 155.73 | 0.00 | 0.00 |
November | 38.99 | 334.26 | 120.65 | 25.50 | 95.15 | 0.00 | 0.00 |
December | 25.44 | 433.80 | 99.31 | 26.64 | 72.67 | 0.00 | 0.00 |
Annual Sum or Average | 257.24 | 284.28 | 322.36 | 109.83 | 212.53 | 0.00 | 0.00 |
Minimum of Months | 17.98 | 189.17 | 99.31 | 23.84 | 72.67 | 0.00 | 0.00 |
Maximum of Months | 569.94 | 433.87 | 582.86 | 255.36 | 344.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 61.41 | 277.01 | 139.41 | 27.21 | 112.19 | 0.00 | 0.00 |
February | 170.05 | 254.28 | 249.41 | 82.85 | 166.56 | 0.00 | 0.00 |
March | 402.42 | 222.60 | 436.71 | 187.42 | 249.29 | 0.00 | 0.00 |
April | 728.44 | 197.30 | 695.41 | 354.15 | 341.26 | 0.00 | 0.00 |
May | 961.42 | 220.72 | 903.44 | 466.12 | 437.32 | 0.00 | 0.00 |
June | 1064.28 | 203.87 | 989.86 | 580.89 | 408.97 | 0.00 | 0.00 |
July | 1120.29 | 235.44 | 1032.60 | 681.74 | 350.85 | 0.00 | 0.00 |
August | 859.47 | 260.71 | 828.06 | 526.84 | 301.22 | 0.00 | 0.00 |
September | 532.85 | 309.42 | 582.28 | 323.41 | 258.87 | 0.00 | 0.00 |
October | 278.52 | 266.13 | 343.75 | 160.52 | 183.23 | 0.00 | 0.00 |
November | 95.82 | 229.83 | 167.47 | 40.98 | 126.49 | 0.00 | 0.00 |
December | 46.58 | 276.33 | 120.43 | 29.02 | 91.41 | 0.00 | 0.00 |
Annual Sum or Average | 528.87 | 246.19 | 542.38 | 289.72 | 252.66 | 0.00 | 0.00 |
Minimum of Months | 46.58 | 197.30 | 120.43 | 27.21 | 91.41 | 0.00 | 0.00 |
Maximum of Months | 1120.29 | 309.42 | 1032.60 | 681.74 | 437.32 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 48148413.72 | 0.116207E+10 | 0.288743E+09 | 63865626.63 | 0.224877E+09 | 0.00 | 0.00 |
February | 0.197188E+09 | 0.889799E+09 | 0.448653E+09 | 0.128549E+09 | 0.320104E+09 | 0.00 | 0.00 |
March | 0.438560E+09 | 0.771168E+09 | 0.707117E+09 | 0.181836E+09 | 0.525281E+09 | 0.00 | 0.00 |
April | 0.837603E+09 | 0.598701E+09 | 0.102231E+10 | 0.302786E+09 | 0.719522E+09 | 0.00 | 0.00 |
May | 0.120043E+10 | 0.587035E+09 | 0.136105E+10 | 0.437411E+09 | 0.923642E+09 | 0.00 | 0.00 |
June | 0.111614E+10 | 0.490325E+09 | 0.129324E+10 | 0.401147E+09 | 0.892095E+09 | 0.00 | 0.00 |
July | 0.152653E+10 | 0.520530E+09 | 0.156113E+10 | 0.683948E+09 | 0.877185E+09 | 0.00 | 0.00 |
August | 0.128597E+10 | 0.530328E+09 | 0.128480E+10 | 0.535455E+09 | 0.749346E+09 | 0.00 | 0.00 |
September | 0.878786E+09 | 0.663813E+09 | 0.100586E+10 | 0.394011E+09 | 0.611846E+09 | 0.00 | 0.00 |
October | 0.413768E+09 | 0.722871E+09 | 0.614200E+09 | 0.197093E+09 | 0.417107E+09 | 0.00 | 0.00 |
November | 0.101051E+09 | 0.866402E+09 | 0.312723E+09 | 66095322.50 | 0.246628E+09 | 0.00 | 0.00 |
December | 68148080.62 | 0.116189E+10 | 0.266003E+09 | 71357373.01 | 0.194646E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.811232E+10 | 0.896493E+10 | 0.101658E+11 | 0.346355E+10 | 0.670228E+10 | 0.00 | 0.00 |
Minimum of Months | 48148413.72 | 0.490325E+09 | 0.266003E+09 | 63865626.63 | 0.194646E+09 | 0.00 | 0.00 |
Maximum of Months | 0.152653E+10 | 0.116207E+10 | 0.156113E+10 | 0.683948E+09 | 0.923642E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.164478E+09 | 0.741945E+09 | 0.373385E+09 | 72891646.44 | 0.300494E+09 | 0.00 | 0.00 |
February | 0.411390E+09 | 0.615164E+09 | 0.603375E+09 | 0.200436E+09 | 0.402939E+09 | 0.00 | 0.00 |
March | 0.107784E+10 | 0.596217E+09 | 0.116969E+10 | 0.501999E+09 | 0.667694E+09 | 0.00 | 0.00 |
April | 0.188812E+10 | 0.511405E+09 | 0.180251E+10 | 0.917967E+09 | 0.884544E+09 | 0.00 | 0.00 |
May | 0.257505E+10 | 0.591169E+09 | 0.241978E+10 | 0.124846E+10 | 0.117132E+10 | 0.00 | 0.00 |
June | 0.275863E+10 | 0.528432E+09 | 0.256573E+10 | 0.150567E+10 | 0.106006E+10 | 0.00 | 0.00 |
July | 0.300057E+10 | 0.630590E+09 | 0.276571E+10 | 0.182598E+10 | 0.939729E+09 | 0.00 | 0.00 |
August | 0.230201E+10 | 0.698293E+09 | 0.221787E+10 | 0.141109E+10 | 0.806785E+09 | 0.00 | 0.00 |
September | 0.138113E+10 | 0.802024E+09 | 0.150926E+10 | 0.838270E+09 | 0.670988E+09 | 0.00 | 0.00 |
October | 0.745997E+09 | 0.712802E+09 | 0.920690E+09 | 0.429929E+09 | 0.490761E+09 | 0.00 | 0.00 |
November | 0.248363E+09 | 0.595725E+09 | 0.434073E+09 | 0.106220E+09 | 0.327853E+09 | 0.00 | 0.00 |
December | 0.124751E+09 | 0.740117E+09 | 0.322559E+09 | 77717251.95 | 0.244842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.166783E+11 | 0.776388E+10 | 0.171046E+11 | 0.913663E+10 | 0.796800E+10 | 0.00 | 0.00 |
Minimum of Months | 0.124751E+09 | 0.511405E+09 | 0.322559E+09 | 72891646.44 | 0.244842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.300057E+10 | 0.802024E+09 | 0.276571E+10 | 0.182598E+10 | 0.117132E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.11 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.09 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.03 | 5.25 | 4.23 | 1.21 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.01 | 7.49 | 3.85 | 3.74 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.79 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.40 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.56 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.54 | 10.74 | 2.23 | 5.46 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.18 | 7.19 | 4.02 | 2.09 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.12 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.11 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.56 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.48 | 7.20 | 8.40 | 3.88 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.15 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.40 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.20 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.35 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.72 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.76 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.67 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.67 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.47 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.93 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.42 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.42 | 0.00 | 0.00 | 3.88 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.76 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -1.9 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.18 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.56 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.56 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.48 | 11-JAN-21:00 | 11.10 | 10.00 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 12.41 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.44 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.27 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.57 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.72 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.16 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.12 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.96 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.04 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.70 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.48 | 11.10 | 6.70 | 0.00 | 6.35 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 28.90 | 15.70 | 6.70 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.48 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.34 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.09 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.76 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.92 | 2.10 | 6.88 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.00 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.09 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.935997E+09 | -848753304.3 | 0.00 | 0.00 | 744.00 | 0.00 | -87243275.5 | 58.99 | 0.00 | 0.00 |
February | 0.863364E+09 | -785129384.6 | 0.00 | 0.00 | 672.00 | 0.00 | -78234621.9 | 58.99 | 0.00 | 0.00 |
March | 0.992464E+09 | -907308431.3 | 0.00 | 0.00 | 744.00 | 0.00 | -85155391.0 | 58.99 | 0.00 | 0.00 |
April | 0.900005E+09 | -819642396.4 | 0.00 | 0.00 | 720.00 | 0.00 | -80362119.2 | 59.00 | 0.00 | 0.00 |
May | 0.899615E+09 | -820651724.4 | 0.00 | 0.00 | 744.00 | 0.00 | -78963462.2 | 58.99 | 0.00 | 0.00 |
June | 0.860217E+09 | -786761514.6 | 0.00 | 0.00 | 720.00 | 0.00 | -73455512.2 | 59.00 | 0.00 | 0.00 |
July | 0.812704E+09 | -739282240.2 | 0.00 | 0.00 | 744.00 | 0.00 | -73422022.8 | 58.99 | 0.00 | 0.00 |
August | 0.860444E+09 | -787244550.3 | 0.00 | 0.00 | 744.00 | 0.00 | -73199057.1 | 58.99 | 0.00 | 0.00 |
September | 0.814572E+09 | -741670033.1 | 0.00 | 0.00 | 720.00 | 0.00 | -72901524.4 | 58.99 | 0.00 | 0.00 |
October | 0.849469E+09 | -767228747.1 | 0.00 | 0.00 | 744.00 | 0.00 | -82240116.9 | 58.99 | 0.00 | 0.00 |
November | 0.848886E+09 | -766214869.9 | 0.00 | 0.00 | 720.00 | 0.00 | -82671020.1 | 58.99 | 0.00 | 0.00 |
December | 0.913944E+09 | -827201329.6 | 0.00 | 0.00 | 744.00 | 0.00 | -86742554.6 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105517E+11 | -.959709E+10 | 8760.00 | -954590677.8 | 58.99 | |||||
Minimum of Months | 0.812704E+09 | -907308431.3 | 0.00 | 0.00 | 672.00 | 0.00 | -87243275.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.992464E+09 | -739282240.2 | 0.00 | 0.00 | 744.00 | 0.00 | -72901524.4 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 237.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 301.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 242.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | ||||||||||
Minimum of Months | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.641355E+10 | 25099.05 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.489267E+10 | 25099.05 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.374751E+10 | 25099.05 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.200657E+10 | 25099.05 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.511372E+09 | 25099.05 | 11-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125544E+09 | 7052.82 | 01-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2000087.18 | 1128.89 | 05-JUL-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85420382.02 | 8155.37 | 28-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144946E+10 | 25099.05 | 11-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.372775E+10 | 25099.05 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.552147E+10 | 25099.05 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.284833E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.641355E+10 | 25099.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.228142E+11 | 67077.37 | 01-JAN-00:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163277E+11 | 67077.37 | 07-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.733425E+10 | 67077.37 | 04-MAR-22:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.228322E+10 | 67077.37 | 11-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110342E+10 | 52193.12 | 31-OCT-20:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.927724E+10 | 67077.37 | 14-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181990E+11 | 67077.37 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.773390E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.228142E+11 | 67077.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.276286E+11 | 46440.45 | 15-JAN-01:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198518E+11 | 68340.74 | 19-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102697E+10 | 22255.67 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148331E+11 | 36100.85 | 22-DEC-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.633405E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.276286E+11 | 68340.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.235440E+09 | 0.223201E+09 | 5161.25 | 27-APR-16:00 | 4953.79 | 0.00 |
May | 0.00 | 0.00 | 0.875565E+09 | 0.817077E+09 | 5649.35 | 06-MAY-15:00 | 4983.52 | 0.00 |
June | 0.00 | 0.00 | 0.217641E+10 | 0.208181E+10 | 7422.62 | 28-JUN-16:00 | 7348.12 | 0.00 |
July | 0.00 | 0.00 | 0.430302E+10 | 0.391896E+10 | 16635.08 | 31-JUL-05:02 | 14550.48 | 0.00 |
August | 0.00 | 0.00 | 0.538669E+10 | 0.479367E+10 | 16836.64 | 25-AUG-05:02 | 14145.84 | 0.00 |
September | 0.00 | 0.00 | 0.240021E+10 | 0.213076E+10 | 16272.71 | 14-SEP-05:03 | 14085.47 | 0.00 |
October | 0.00 | 0.00 | 0.171437E+09 | 0.169740E+09 | 3576.80 | 04-OCT-15:00 | 3576.80 | 0.00 |
November | 0.00 | 0.00 | 15014115.11 | 12142674.10 | 1849.49 | 04-NOV-15:30 | 1499.50 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.155638E+11 | 0.141474E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.538669E+10 | 0.479367E+10 | 16836.64 | 14550.48 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 5371.58 | 4885.78 | 1.06 | 06-MAY-13:40 | 0.84 | 0.00 |
June | 0.00 | 0.00 | 0.269073E+09 | 0.257537E+09 | 11003.72 | 28-JUN-15:00 | 11003.72 | 0.00 |
July | 0.00 | 0.00 | 0.241785E+10 | 0.213122E+10 | 43599.85 | 27-JUL-17:12 | 32913.19 | 0.00 |
August | 0.00 | 0.00 | 0.433513E+10 | 0.383636E+10 | 42707.88 | 13-AUG-13:42 | 35554.31 | 0.00 |
September | 0.00 | 0.00 | 0.242279E+09 | 0.190942E+09 | 8834.67 | 14-SEP-14:30 | 6993.35 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.726433E+10 | 0.641606E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.433513E+10 | 0.383636E+10 | 43599.85 | 35554.31 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.338576E+09 | 0.05 | 199.74 | 01-JAN-00:03 | 0.08 |
February | 0.212746E+09 | 0.03 | 199.74 | 01-FEB-00:05 | 0.08 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 20413728.43 | 0.00 | 199.74 | 23-NOV-22:50 | 0.08 |
December | 0.271940E+09 | 0.04 | 199.74 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.843676E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.338576E+09 | 0.05 | 199.74 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.111875E+10 | 0.41 | 1083.20 | 02-JAN-07:50 | 0.95 |
February | 0.102481E+10 | 0.41 | 1083.20 | 01-FEB-07:10 | 0.95 |
March | 0.119046E+10 | 0.41 | 1083.20 | 25-MAR-12:30 | 0.95 |
April | 0.109417E+10 | 0.38 | 1083.20 | 17-APR-14:10 | 0.95 |
May | 0.112086E+10 | 0.37 | 1083.20 | 22-MAY-13:30 | 0.95 |
June | 0.111571E+10 | 0.38 | 1083.20 | 01-JUN-06:05 | 0.94 |
July | 0.107640E+10 | 0.35 | 1083.20 | 26-JUL-07:10 | 0.94 |
August | 0.116610E+10 | 0.38 | 1083.20 | 01-AUG-07:17 | 0.94 |
September | 0.107364E+10 | 0.36 | 1083.20 | 26-SEP-10:30 | 0.94 |
October | 0.108702E+10 | 0.37 | 1083.20 | 19-OCT-09:50 | 0.94 |
November | 0.105637E+10 | 0.37 | 1083.20 | 08-NOV-13:20 | 0.94 |
December | 0.110745E+10 | 0.38 | 1083.20 | 29-DEC-14:20 | 0.94 |
Annual Sum or Average | 0.132317E+11 | 0.38 | |||
Minimum of Months | 0.102481E+10 | 0.35 | 1083.20 | 0.94 | |
Maximum of Months | 0.119046E+10 | 0.41 | 1083.20 | 0.95 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.283745E+10 | 0.77 | 2204.85 | 02-JAN-07:30 | 0.91 |
February | 0.249318E+10 | 0.71 | 2204.85 | 01-FEB-09:00 | 0.91 |
March | 0.259725E+10 | 0.61 | 2204.85 | 03-MAR-07:30 | 0.91 |
April | 0.226121E+10 | 0.43 | 2204.85 | 01-APR-07:20 | 0.91 |
May | 0.227011E+10 | 0.35 | 2204.85 | 15-MAY-13:50 | 0.91 |
June | 0.227011E+10 | 0.36 | 2204.85 | 10-JUN-12:50 | 0.91 |
July | 0.220593E+10 | 0.34 | 2204.85 | 06-JUL-14:20 | 0.91 |
August | 0.238310E+10 | 0.37 | 2204.85 | 05-AUG-14:20 | 0.91 |
September | 0.218280E+10 | 0.35 | 2204.85 | 11-SEP-14:50 | 0.90 |
October | 0.222031E+10 | 0.38 | 2204.85 | 30-OCT-06:10 | 0.91 |
November | 0.238753E+10 | 0.62 | 2204.85 | 09-NOV-17:40 | 0.91 |
December | 0.271753E+10 | 0.75 | 2204.85 | 01-DEC-07:20 | 0.91 |
Annual Sum or Average | 0.288265E+11 | 0.50 | |||
Minimum of Months | 0.218280E+10 | 0.34 | 2204.85 | 0.90 | |
Maximum of Months | 0.283745E+10 | 0.77 | 2204.85 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.15 | 0.00 |
February | 2.08 | 0.00 |
March | 1.11 | 0.12 |
April | 0.92 | 1.62 |
May | 1.89 | 2.29 |
June | 1.97 | 2.73 |
July | 3.03 | 1.87 |
August | 2.70 | 1.18 |
September | 2.57 | 2.95 |
October | 0.99 | 1.04 |
November | 2.23 | 0.00 |
December | 2.05 | 0.00 |
Annual Sum or Average | 23.68 | 1.21 |
Minimum of Months | 0.92 | 0.00 |
Maximum of Months | 3.03 | 2.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.08 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.63 | 0.00 |
August | 0.47 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 1.19 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.63 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.111875E+10 | 0.925505E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.102481E+10 | 0.705649E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.119046E+10 | 0.543634E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.116594E+10 | 0.291073E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.138233E+10 | 0.754109E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.176347E+10 | 0.190004E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.234215E+10 | 3101776.26 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.275887E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.178158E+10 | 0.129165E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.113893E+10 | 0.212649E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.106091E+10 | 0.541995E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.110745E+10 | 0.798209E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.178357E+11 | 0.412635E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.102481E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.275887E+10 | 0.925505E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.283745E+10 | 0.330464E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.249318E+10 | 0.236252E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.259725E+10 | 0.108322E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.226121E+10 | 0.337674E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.227012E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.234876E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.290493E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.364934E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.225249E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.222031E+10 | 0.165279E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.238753E+10 | 0.136170E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.271753E+10 | 0.264876E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.309401E+11 | 0.112638E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.222031E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.364934E+10 | 0.330464E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.111875E+10 | 0.00 | 0.641355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102481E+10 | 0.00 | 0.489267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119046E+10 | 0.00 | 0.374751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109417E+10 | 0.235440E+09 | 0.200657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112086E+10 | 0.875565E+09 | 0.511372E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111571E+10 | 0.217641E+10 | 0.125544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.107640E+10 | 0.430302E+10 | 2000087.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116610E+10 | 0.538669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107364E+10 | 0.240021E+10 | 85420382.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108702E+10 | 0.171437E+09 | 0.144946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105637E+10 | 15014115.11 | 0.372775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110745E+10 | 0.00 | 0.552147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132317E+11 | 0.155638E+11 | 0.284833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.102481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119046E+10 | 0.538669E+10 | 0.641355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.283745E+10 | 0.00 | 0.228142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.249318E+10 | 0.00 | 0.163277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.259725E+10 | 0.00 | 0.733425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.226121E+10 | 0.00 | 0.228322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.227011E+10 | 5371.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.227011E+10 | 0.269073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.220593E+10 | 0.241785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.238310E+10 | 0.433513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.218280E+10 | 0.242279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.222031E+10 | 0.00 | 0.110342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.238753E+10 | 0.00 | 0.927724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271753E+10 | 0.00 | 0.181990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288265E+11 | 0.726433E+10 | 0.773390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.218280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.283745E+10 | 0.433513E+10 | 0.228142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.111875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109417E+10 | 0.00 | 0.00 | 0.00 | 71767250.65 | 0.00 | 0.291073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112086E+10 | 0.00 | 0.00 | 0.00 | 0.261476E+09 | 0.00 | 0.754109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111571E+10 | 0.00 | 0.00 | 0.00 | 0.647755E+09 | 0.00 | 0.190004E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.107640E+10 | 0.00 | 0.00 | 0.00 | 0.126575E+10 | 0.00 | 3101776.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116610E+10 | 0.00 | 0.00 | 0.00 | 0.159278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107364E+10 | 0.00 | 0.00 | 0.00 | 0.707936E+09 | 0.00 | 0.129165E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108702E+10 | 0.00 | 0.00 | 0.00 | 51912121.67 | 0.00 | 0.212649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105637E+10 | 0.00 | 0.00 | 0.00 | 4540538.77 | 0.00 | 0.541995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.798209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132317E+11 | 0.00 | 0.00 | 0.00 | 0.460392E+10 | 0.00 | 0.412635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.102481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119046E+10 | 0.00 | 0.00 | 0.00 | 0.159278E+10 | 0.00 | 0.925505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.283745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.249318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.259725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.226121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.227011E+10 | 0.00 | 0.00 | 0.00 | 1581.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.227011E+10 | 0.00 | 0.00 | 0.00 | 78640660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.220593E+10 | 0.00 | 0.00 | 0.00 | 0.699006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.238310E+10 | 0.00 | 0.00 | 0.00 | 0.126624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.218280E+10 | 0.00 | 0.00 | 0.00 | 69688227.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.222031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.238753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288265E+11 | 0.00 | 0.00 | 0.00 | 0.211357E+10 | 0.00 | 0.112638E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.218280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.283745E+10 | 0.00 | 0.00 | 0.00 | 0.126624E+10 | 0.00 | 0.330464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242551E+10 | 0.00 | 0.00 | 0.17 |
February | 68686051.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192908E+10 | 0.00 | 0.00 | 0.17 |
March | 0.355681E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161487E+10 | 0.00 | 0.00 | 0.18 |
April | 0.622533E+09 | 8270851.41 | 0.00 | 158406.96 | 95879.47 | 0.837575E+09 | 41438444.47 | 0.00 | 0.17 |
May | 0.777146E+09 | 7578745.44 | 0.00 | 1047735.34 | 0.00 | 0.188615E+09 | 0.372165E+09 | 0.00 | 0.17 |
June | 0.345659E+09 | 3941716.69 | 0.00 | 3011201.97 | 0.00 | 60524601.34 | 0.670754E+09 | 0.00 | 0.17 |
July | 0.116788E+09 | 88849297.48 | 0.00 | 4262258.45 | 0.00 | 5911821.58 | 0.493467E+09 | 0.00 | 0.16 |
August | 0.111968E+09 | 0.207355E+09 | 0.00 | 4354083.77 | 0.00 | 0.00 | 0.427494E+09 | 0.00 | 0.18 |
September | 0.332593E+09 | 21866504.39 | 0.00 | 2688862.82 | 0.00 | 55819948.52 | 0.644292E+09 | 0.00 | 0.17 |
October | 0.737609E+09 | 0.00 | 0.00 | 258965.59 | 0.00 | 0.642704E+09 | 0.120642E+09 | 0.00 | 0.16 |
November | 0.228858E+09 | 0.00 | 0.00 | 9654.11 | 0.00 | 0.158989E+10 | 4542837.89 | 0.00 | 0.16 |
December | 16473106.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226076E+10 | 0.00 | 0.00 | 0.16 |
Annual Sum or Average | 0.371399E+10 | 0.337862E+09 | 0.00 | 15791169.00 | 95879.47 | 0.116113E+11 | 0.277480E+10 | 0.00 | 0.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.777146E+09 | 0.207355E+09 | 0.00 | 4354083.77 | 95879.47 | 0.242551E+10 | 0.670754E+09 | 0.00 | 0.18 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.134829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246666E+10 | 0.00 | 0.00 | 0.14 |
February | 0.163848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147067E+10 | 0.00 | 0.00 | 0.15 |
March | 0.259634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425367E+09 | 0.00 | 0.00 | 0.16 |
April | 0.239578E+10 | 0.00 | 0.00 | 0.00 | 36408626.32 | 88096959.55 | 0.00 | 0.00 | 0.15 |
May | 0.277503E+10 | 0.00 | 0.00 | 18406.70 | 0.00 | 0.00 | 47185703.58 | 0.00 | 0.16 |
June | 0.251153E+10 | 3968370.51 | 0.00 | 802446.90 | 22589.87 | 0.00 | 0.575266E+09 | 0.00 | 0.21 |
July | 0.144493E+10 | 91937677.73 | 0.00 | 3622944.87 | 0.00 | 0.00 | 0.201515E+10 | 0.00 | 0.30 |
August | 0.152877E+10 | 0.249351E+09 | 0.00 | 2785669.72 | 0.00 | 0.00 | 0.123228E+10 | 0.00 | 0.28 |
September | 0.246347E+10 | 0.00 | 0.00 | 1097630.76 | 0.00 | 0.00 | 0.767020E+09 | 0.00 | 0.21 |
October | 0.239608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52748029.33 | 0.00 | 0.00 | 0.15 |
November | 0.195987E+10 | 0.00 | 0.00 | 0.00 | 209075.00 | 0.804463E+09 | 0.00 | 0.00 | 0.14 |
December | 0.158800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190917E+10 | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.246466E+11 | 0.345257E+09 | 0.00 | 8327098.95 | 36640291.18 | 0.721718E+10 | 0.463691E+10 | 0.00 | 0.18 |
Minimum of Months | 0.134829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.277503E+10 | 0.249351E+09 | 0.00 | 3622944.87 | 36408626.32 | 0.246666E+10 | 0.201515E+10 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |