Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2020-06-03 19:11:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1224.49 | 253.25 | 253.25 |
Net Site Energy | 1224.49 | 253.25 | 253.25 |
Total Source Energy | 3730.17 | 771.47 | 771.47 |
Net Source Energy | 3730.17 | 771.47 | 771.47 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 70.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 238.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 153.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.07 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1153.54 | 70.96 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 70.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 238.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 37.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 116.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22.07 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 124.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 85.72 | 14.68 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 238.57 | 14.68 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 124.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 85.72 | 14.68 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 238.57 | 14.68 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1153.536 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1153.536 | 100.00 |
Total On-Site and Utility Electric Sources | 1153.536 | 100.00 |
Total Electricity End Uses | 1153.536 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 74.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 225.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 26.81 |
Skylight-Roof Ratio [%] | 0.58 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.6337 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.5069 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.5069 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:30 | 02-JAN-07:30 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 3255.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 39306.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 31277.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10718.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1566.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 92981.63 | 3255.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 3255.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 39306.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 31277.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 8413.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1566.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 76.92 | 0.00 | 0.00 | 0.00 |
Cooling | 755.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1507.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 391.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 487.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 69.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3653.25 | 76.92 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 15.91 | 0.00 | 0.00 | 0.00 |
Cooling | 156.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 81.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 100.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 755.56 | 15.91 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 15.91 | 0.00 | 0.00 | 0.00 |
Cooling | 156.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 81.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 100.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 755.56 | 15.91 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.32 |
ZONE2 FINE STORAGE DIRECT AIR | 3.62 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 0.814033 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 0.814033 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 33788.32 |
PSZ-OFFICE HEATING COIL | 31412.27 |
PSZ-FINE STORAGE HEATING COIL | 108271.26 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.32 | 1.32 | 1.32 | 1.32 | 1.32 | 1.32 | 1.00 | 1.00 | 1.32 |
PSZ-FINE STORAGE | 3.62 | 3.62 | 3.62 | 3.62 | 3.62 | 3.62 | 1.00 | 1.00 | 3.62 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.32 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 3.62 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.32 | 1.32 | 1.32 | 1.32 | 27767.74 | 31412.27 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 3.62 | 3.62 | 3.62 | 3.62 | 89931.65 | 108271.26 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.32 | 0.657820 | 1.32 | 27083.24 | 27767.74 | 13883.87 | 27767.74 | 0.719356 | 0.719360 | 0.719360 | 0.719360 |
PSZ-FINE STORAGE COOLING COIL | 3.62 | 1.81 | 3.62 | 87066.75 | 89931.65 | 44965.82 | 89931.65 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.32 | 1499.98 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.62 | 6913.41 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.634 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.707 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.507 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.507 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.507 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.066 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2518.900 | 10.634 | 503.780 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2518.900 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11853.648 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11853.648 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27263.390 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27263.390 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
2 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
3 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
4 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
5 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
6 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
13 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
14 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
15 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
16 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.14714251E-14 | -0.15793949E-15 | 0.73826229E-12 | 0.12610148E-15 |
85 | 3 | -0.53553847E-04 | 0.48261894E-06 | -0.37015163E-03 | 0.14168247E-12 |
86 | 2 | 1.1141045 | 0.10720623E-01 | 1.7048811 | -0.70963114E-04 |
87 | 1 | -16.929564 | 0.28051356 | -7.1749370 | 0.32672988 |
88 | 0 | 16.286769 | 0.18002168 | 5.9416824 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 28 | 1 | VerySmooth | 5.832 | 0.251 | 0.110 | 0.250 |
2 | SKYLIGHT_U_1.02_SHGC_0.4 | 29 | 1 | VerySmooth | 5.779 | 0.400 | 0.232 | 0.401 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 30 | 1 | VerySmooth | 5.779 | 0.400 | 0.232 | 0.401 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.23173 | 0.20656 | 0.20656 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.23173 | 0.20656 | 0.20656 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 13320.48321 | 15984.57985 | 1.09637 | 1.31564 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 41.44200 | 1.07356E-002 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 5350.94602 | 6421.13523 | 0.14995 | 0.17994 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 12.70000 | 9.15345E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 47034.89093 | 56441.86912 | 3.01796 | 3.62155 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 41.44200 | 1.07356E-002 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 4091.19471 | 4909.43365 | 9.67904E-002 | 0.35393 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 07:40:00 | 12.70000 | 9.15345E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80000 | 1.07356E-002 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.81403 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70000 | 9.15345E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 21497.81 | 1.31564 | 1.31564 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 5341.37 | 0.17994 | 0.17994 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 70690.88 | 3.62155 | 3.62155 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 11685.90 | 0.35393 | 0.35393 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.31564 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.62155 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.81403 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 0.81403 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 33788.32305 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 0.00000 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.31564 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.31564 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.31564 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.31564 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.31564 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.31564 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.62155 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.62155 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.62155 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.62155 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.62155 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.62155 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.31564 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.62155 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.31564 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.31564 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.31564 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.31564 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.31564 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.31564 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65782 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.31564 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 27083.23808 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 27767.74000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13883.87000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 27767.74000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.71936 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.71936 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.71936 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.71936 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27767.74000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31412.27443 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.31564 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1499.97796 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 31412.27443 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.62155 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.62155 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.62155 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.62155 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.62155 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.62155 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.81078 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.62155 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 87066.75009 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 89931.65000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 44965.82500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 89931.65000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 89931.65000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 108271.26049 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.62155 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 6913.40509 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 108271.26049 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 26745.9 | 10.44 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 87116.7 | 12.96 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 6 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 3.6457378440E-002 | 2.1723035941E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 4.9927516420E-002 | 3.7389072902E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.5916417690E-002 | 2.5694832624E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.233 | 0.240 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.233 | 0.240 | 3204.84 | 3178.03 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 5.832 | 0.251 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_1.2_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 5.832 | 0.251 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 5.832 | 0.251 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 5.832 | 0.251 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 1.19 | 0.00 | 2.68 | 2.68 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 1.19 | 0.00 | 2.68 | 2.68 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 1.19 | 0.00 | 2.68 | 2.68 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 1.19 | 0.00 | 2.68 | 2.68 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 1.19 | 0.00 | 2.68 | 2.68 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 1.19 | 0.00 | 2.68 | 2.68 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 1.19 | 0.00 | 2.68 | 2.68 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 1.19 | 0.00 | 2.68 | 2.68 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 1.19 | 0.00 | 2.68 | 2.68 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 1.19 | 0.00 | 2.68 | 2.68 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 44.47 | 5.800 | 0.341 | 0.341 | ||||||||||||
North Total or Average | 6.51 | 5.832 | 0.251 | 0.250 | ||||||||||||
Non-North Total or Average | 37.97 | 5.795 | 0.356 | 0.356 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.6337 | 236.88 | 2518.90 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.62 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.5069 | 1393.41 | 11853.65 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 135.00 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.5069 | 3204.84 | 27263.39 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 310.50 |
Interior Lighting Total | 8.6111 | 4835.13 | 41635.94 | 476.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.00 | AstronomicalClock | - | 83.85 | 83.85 | 123.67 | |
Exterior Lighting Total | 7857.00 | 123.67 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27767.74 | 19975.00 | 7792.74 | 0.72 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 89931.65 | 60800.99 | 29130.66 | 0.68 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 26745.9 | 10.44 | ||||
PSZ-FINE STORAGE COOLING COIL | 87116.7 | 12.96 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 33788.32 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 31412.27 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 108271.26 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.81 | 75.63 | 92.91 | 1.00 | 4.39 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.32 | 1499.98 | 1140.11 | 1.00 | 1.30 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 1110.54 | 3.62 | 6913.41 | 1908.96 | 1.00 | 1.14 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 13320.48 | 15984.58 | 67.48 | 1.096 | 1.316 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23.90 | 23.90 | 0.00818 | 41.44 | 0.01074 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 47034.89 | 56441.87 | 40.51 | 3.018 | 3.622 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 26.70 | 26.70 | 0.00850 | 41.44 | 0.01074 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00378 | 42.80 | 0.01074 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 5350.95 | 6421.14 | 27.11 | 0.150 | 0.180 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00856 | 12.70 | 0.00915 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 4091.19 | 4909.43 | 3.52 | 0.097 | 0.354 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 07:40:00 | 15.56 | 15.56 | 0.00884 | 12.70 | 0.00915 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 0.00 | 10.00 | 0.01600 | 12.70 | 0.00915 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.32 | 1.32 | 0.18 | 0.18 | 1.3156 | 1.3156 | 1.3156 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.62 | 3.62 | 0.35 | 0.35 | 3.6215 | 3.6215 | 3.6215 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 33788.323 | 33788.323 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 33788.32 | 33788.32 | 0.814033 | 10.00 | 10.00 | 0.01600000 | 43.33 | 27.10 | 0.01600000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 10.00 | 0.01600000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 27767.740 | 0.000 | 1.315640 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27767.74 | 25964.04 | 1.315640 | 25.52 | 16.82 | 0.00841214 | 12.00 | 11.25 | 0.00800000 | 41.57 | 0.01073558 | 23.47 | 9.1465 | 23.90 | 0.00818105 | 44.3082 | 13320.48 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 31412.274 | 31412.274 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 31412.27 | 31412.27 | 1.315643 | 15.46 | 13.60 | 0.00895559 | 40.00 | 21.14 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 9.1465 | 21.10 | 0.00855609 | 54.8956 | 5350.95 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 89931.650 | 0.000 | 3.621550 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 89931.65 | 81483.29 | 3.621550 | 28.14 | 17.98 | 0.00872254 | 12.00 | 11.25 | 0.00800000 | 41.44 | 0.01073558 | 23.44 | 9.7728 | 26.70 | 0.00850450 | 38.9768 | 47034.89 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 108271.260 | 108271.260 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:50:00 | 108271.26 | 108271.26 | 3.621548 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.14 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 9.7728 | 15.56 | 0.00883524 | 80.2239 | 3911.03 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 33788.323 | 33788.323 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.2036 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.814033 | 0.97976621 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 33788.32 | 33788.32 | 1.0000 | 0.97976621 | 0.814033 | 10.00 | 10.00 | 0.01600000 | 50360.9 | 43.33 | 27.10 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33788.32 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 10.00 | 0.01600000 | 10.00 | 0.01600000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27767.740 | 0.000 | 1.315640 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4777 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27767.74 | 25964.04 | 1.0000 | 1.58349770 | 1.315640 | 25.52 | 16.82 | 0.00841214 | 47077.2 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27767.74 | 41.57 | 0.01073558 | 23.47 | 0.12033533 | 9.1465 | 23.90 | 0.00817811 | 23.90 | 0.00818105 | 44.3082 | 13320.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31412.274 | 31412.274 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.315643 | 1.58350170 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 31412.27 | 31412.27 | 1.0000 | 1.58350170 | 1.315643 | 15.46 | 13.60 | 0.00895559 | 38185.2 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31412.27 | 12.70 | 0.00915345 | 12.70 | 0.12033533 | 9.1465 | 21.02 | 0.00855609 | 21.10 | 0.00855609 | 54.8956 | 5350.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 89931.650 | 0.000 | 3.621550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0548 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 89931.65 | 81483.29 | 1.0000 | 4.35887941 | 3.621550 | 28.14 | 17.98 | 0.00872254 | 50546.3 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89931.65 | 41.44 | 0.01073558 | 23.44 | 0.35392745 | 9.7728 | 26.70 | 0.00850450 | 26.70 | 0.00850450 | 38.9768 | 47034.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 108271.260 | 108271.260 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.621548 | 4.35887645 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:50:00 | 108271.26 | 108271.26 | 1.0000 | 4.35887645 | 3.621548 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 108271.26 | 12.70 | 0.00915345 | 12.70 | 0.35392745 | 9.7728 | 15.56 | 0.00884222 | 15.56 | 0.00883524 | 80.2239 | 3911.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3265.67 | 309.17 | 225.50 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 3265.67 | 309.17 | 225.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.00 | 98.17 | 0.00 | 74.83 |
ZONE2 FINE STORAGE | 0.00 | 479.67 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 569.33 | 0.00 | 74.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.416 | 0.376 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1153.54 | 5421.86 | 01-JAN-07:10 | 92981.63 | 10-AUG-15:30 |
Electricity:Building | 652.74 | 4938.86 | 01-JAN-00:10 | 47606.95 | 06-FEB-13:50 |
Electricity:Zone:ZONE1 OFFICE | 62.57 | 1027.15 | 01-JAN-00:10 | 3852.05 | 02-JAN-08:10 |
InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.62 | 453.40 | 01-JAN-00:10 | 1939.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 455.17 | 2726.34 | 01-JAN-00:10 | 33679.30 | 06-FEB-13:40 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 310.51 | 2726.34 | 01-JAN-00:10 | 23173.88 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 22.07 | 483.00 | 08-FEB-06:10 | 1740.30 | 12-JAN-12:10 |
WaterSystems:Electricity | 22.07 | 483.00 | 08-FEB-06:10 | 1740.30 | 12-JAN-12:10 |
Water Heater:WaterSystems:Electricity | 22.07 | 483.00 | 08-FEB-06:10 | 1740.30 | 12-JAN-12:10 |
Fans:Electricity | 153.97 | 0.00 | 01-JAN-00:10 | 10718.68 | 28-APR-13:20 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 37.33 | 0.00 | 01-JAN-00:10 | 2305.29 | 08-FEB-14:50 |
Ventilation (simple):Fans:Electricity | 37.33 | 0.00 | 01-JAN-00:10 | 2305.29 | 08-FEB-14:50 |
ElectricityPurchased:Facility | 1153.54 | 5421.86 | 01-JAN-07:10 | 92981.63 | 10-AUG-15:30 |
ElectricityPurchased:Plant | 1153.54 | 5421.86 | 01-JAN-07:10 | 92981.63 | 10-AUG-15:30 |
Cogeneration:ElectricityPurchased | 1153.54 | 5421.86 | 01-JAN-07:10 | 92981.63 | 10-AUG-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1153.54 | 5421.86 | 01-JAN-07:10 | 92981.63 | 10-AUG-15:30 |
ElectricityNet:Plant | 1153.54 | 5421.86 | 01-JAN-07:10 | 92981.63 | 10-AUG-15:30 |
Cogeneration:ElectricityNet | 1153.54 | 5421.86 | 01-JAN-07:10 | 92981.63 | 10-AUG-15:30 |
Electricity:HVAC | 355.05 | 0.00 | 01-JAN-00:10 | 48818.86 | 10-AUG-16:10 |
General:Fans:Electricity | 116.64 | 0.00 | 01-JAN-00:10 | 8413.38 | 02-JAN-13:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 238.42 | 0.00 | 01-JAN-00:10 | 40405.47 | 10-AUG-16:10 |
ExteriorLights:Electricity | 123.67 | 0.00 | 01-JAN-07:10 | 7857.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.67 | 0.00 | 01-JAN-07:10 | 7857.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 70.96 | 2250.00 | 08-FEB-06:10 | 3255.95 | 02-JAN-07:30 |
Gas:HVAC | 70.96 | 2250.00 | 08-FEB-06:10 | 3255.95 | 02-JAN-07:30 |
Heating:Gas | 70.96 | 2250.00 | 08-FEB-06:10 | 3255.95 | 02-JAN-07:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1158.45 | 0.00 | 01-JAN-00:10 | 181259.47 | 10-AUG-16:10 |
EnergyTransfer:Building | 411.55 | 0.00 | 01-JAN-00:10 | 65770.19 | 21-MAY-13:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 104.83 | 0.00 | 01-JAN-00:10 | 17153.50 | 21-JUL-12:00 |
Heating:EnergyTransfer | 2.98 | 0.00 | 01-JAN-00:10 | 5657.89 | 10-JAN-18:00 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.06 | 0.00 | 01-JAN-00:10 | 1074.88 | 02-JAN-07:30 |
Cooling:EnergyTransfer | 408.57 | 0.00 | 01-JAN-00:10 | 65770.19 | 21-MAY-13:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 104.76 | 0.00 | 01-JAN-00:10 | 17153.50 | 21-JUL-12:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 306.72 | 0.00 | 01-JAN-00:10 | 62619.46 | 21-MAY-13:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 2.92 | 0.00 | 01-JAN-00:10 | 5657.89 | 10-JAN-18:00 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 303.80 | 0.00 | 01-JAN-00:10 | 62619.46 | 21-MAY-13:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 746.90 | 0.00 | 01-JAN-00:10 | 130516.14 | 22-AUG-17:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 647.13 | 02-JAN-07:30 |
CoolingCoils:EnergyTransfer | 746.90 | 0.00 | 01-JAN-00:10 | 130516.14 | 22-AUG-17:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.064 | -104.762 | 0.000 | 0.000 | 3.576 | 30.619 | 31.946 | 17.167 | 0.000 | 11.105 | 17.983 | 0.000 | -5.046 | 0.000 | -2.651 | -0.000 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 2.918 | -303.802 | 0.000 | 0.000 | 0.000 | 135.003 | 0.000 | 0.000 | 0.000 | 52.252 | 135.109 | 0.000 | 0.000 | 0.000 | -21.479 | -0.004 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 310.507 | 107.336 | 32.266 | 0.000 | 105.456 | 22.145 | 0.000 | -14.099 | 0.000 | -563.612 | -0.004 |
Total Facility | 0.000 | 0.000 | 2.981 | -408.564 | 0.000 | 0.000 | 3.576 | 476.129 | 139.282 | 49.433 | 0.000 | 168.813 | 175.237 | 0.000 | -19.145 | 0.000 | -587.742 | -0.008 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 26-APR-05:01 | 0.00 | 0.00 | 0.00 | -26372.59 | 0.00 | 0.00 | 28.35 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 25863.37 | 0.00 | -468.93 | 0.00 | -203.30 | 0.00 |
ZONE2 FINE STORAGE | 23-APR-14:02 | 0.00 | 0.00 | 0.00 | -74126.89 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 3408.47 | 69533.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-JUL-05:01 | 0.00 | 0.00 | 0.00 | -86484.17 | 0.00 | 0.00 | 21.39 | 4491.05 | 2623.78 | 8.75 | 0.00 | 2578.08 | 170441.50 | 0.00 | -658.16 | 0.00 | -93022.23 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 02-JAN-07:30 | 0.00 | 0.00 | 1074.77 | 0.00 | 0.00 | 0.00 | 88.23 | 1057.94 | 956.25 | 0.00 | 0.00 | 0.00 | 441.22 | 0.00 | -572.82 | 0.00 | -3045.59 | 0.00 |
ZONE2 FINE STORAGE | 16-MAY-06:04 | 0.00 | 0.00 | 5712.82 | 0.00 | 0.00 | 0.00 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -857.81 | -11967.20 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-MAY-06:04 | -5166.38 | 5166.38 | 5712.82 | -5166.38 | 0.00 | 0.00 | 75.11 | 24528.16 | 3006.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -819.94 | 0.00 | -5640.11 | -21695.95 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3156 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.3156 | 0.0915 | 1.0000 | 0.1203 | 0.0915 | ||
PSZ-FINE STORAGE | 3.6215 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 3.6215 | 0.0977 | 1.0000 | 0.3539 | 0.0977 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3156 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.3156 | 1.0000 | 1.0000 | 0.1203 | 0.0915 | ||
PSZ-FINE STORAGE | 3.6215 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 3.6215 | 1.0000 | 1.0000 | 0.3539 | 0.0977 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.3156 | 1.3156 | 1.3156 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.6215 | 3.6215 | 3.6215 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3156 | 1.3156 | 1.3156 | 1.3156 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 3.6215 | 3.6215 | 3.6215 | 3.6215 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.3156 | 1.3156 | 1.3156 | 0.1203 | 0.6688 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.6215 | 3.6215 | 3.6215 | 0.3539 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3156 | 1.3156 | 1.3156 | 1.3156 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 3.6215 | 3.6215 | 3.6215 | 3.6215 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:42
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 74.83 |
Number of hours not met | 74.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 70.96 | 3255.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 238.42 | 40405.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 476.13 | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.67 | 7857.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 37.33 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 116.64 | 8413.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 22.07 | 1740.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 1153.54 |
Natural Gas | 0.00 | 70.96 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1224.49 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 98.47 |
Space Heating | 0.00 |
Space Cooling | 49.31 |
Fans (All) | 31.84 |
Service Water Heating | 4.57 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 238.57 |
Subtotal | 238.57 |
Natural Gas [MJ/m2] | |
Space Heating | 14.68 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 14.68 |
Subtotal | 14.68 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 38.88 |
Space Heating | 5.79 |
Space Cooling | 19.47 |
Fans (All) | 12.57 |
Service Water Heating | 1.80 |
Receptacle Equipment | 11.37 |
Miscellaneous | 10.10 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.602853E+10 |
February | 0.000 | 0.544320E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583200E+10 |
December | 0.000 | 0.602640E+10 |
Annual Sum or Average | 0.709581E+11 | |
Minimum of Months | 0.000 | 0.544320E+10 |
Maximum of Months | 0.000 | 0.602853E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.602853E+10 |
February | 0.000 | 0.544320E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583200E+10 |
December | 0.000 | 0.602640E+10 |
Annual Sum or Average | 0.709581E+11 | |
Minimum of Months | 0.000 | 0.544320E+10 |
Maximum of Months | 0.000 | 0.602853E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Meter
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.602853E+10 |
February | 0.000 | 0.544320E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583200E+10 |
December | 0.000 | 0.602640E+10 |
Annual Sum or Average | 0.709581E+11 | |
Minimum of Months | 0.000 | 0.544320E+10 |
Maximum of Months | 0.000 | 0.602853E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.602853E+10 |
February | 0.000 | 0.544320E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583200E+10 |
December | 0.000 | 0.602640E+10 |
Annual Sum or Average | 0.709581E+11 | |
Minimum of Months | 0.000 | 0.544320E+10 |
Maximum of Months | 0.000 | 0.602853E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.602853E+10 |
February | 0.000 | 0.544320E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583200E+10 |
December | 0.000 | 0.602640E+10 |
Annual Sum or Average | 0.709581E+11 | |
Minimum of Months | 0.000 | 0.544320E+10 |
Maximum of Months | 0.000 | 0.602853E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.602853E+10 |
February | 0.000 | 0.544320E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583200E+10 |
December | 0.000 | 0.602640E+10 |
Annual Sum or Average | 0.709581E+11 | |
Minimum of Months | 0.000 | 0.544320E+10 |
Maximum of Months | 0.000 | 0.602853E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.602853E+10 |
February | 0.000 | 0.544320E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583200E+10 |
December | 0.000 | 0.602640E+10 |
Annual Sum or Average | 0.709581E+11 | |
Minimum of Months | 0.000 | 0.544320E+10 |
Maximum of Months | 0.000 | 0.602853E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Meter
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.602853E+10 |
February | 0.000 | 0.544320E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583200E+10 |
December | 0.000 | 0.602640E+10 |
Annual Sum or Average | 0.709581E+11 | |
Minimum of Months | 0.000 | 0.544320E+10 |
Maximum of Months | 0.000 | 0.602853E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Meter
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.602853E+10 |
February | 0.000 | 0.544320E+10 |
March | 0.000 | 0.602640E+10 |
April | 0.000 | 0.583200E+10 |
May | 0.000 | 0.602640E+10 |
June | 0.000 | 0.583200E+10 |
July | 0.000 | 0.602640E+10 |
August | 0.000 | 0.602640E+10 |
September | 0.000 | 0.583200E+10 |
October | 0.000 | 0.602640E+10 |
November | 0.000 | 0.583200E+10 |
December | 0.000 | 0.602640E+10 |
Annual Sum or Average | 0.709581E+11 | |
Minimum of Months | 0.000 | 0.544320E+10 |
Maximum of Months | 0.000 | 0.602853E+10 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.391841E+10 | 21278.89 | 25-JAN-06:02 | 17.88 | 14.28 | 0.248133E+09 | 301.62 | 28-JAN-15:30 | 25.25 | 17.91 |
February | 0.454637E+10 | 23380.84 | 11-FEB-06:02 | 18.50 | 13.71 | 0.228792E+09 | 301.62 | 15-FEB-14:09 | 25.67 | 18.26 |
March | 0.659223E+10 | 25891.92 | 28-MAR-05:01 | 25.67 | 14.72 | 0.268901E+09 | 301.71 | 10-MAR-08:09 | 18.33 | 15.58 |
April | 0.765480E+10 | 26373.19 | 26-APR-05:01 | 23.17 | 12.09 | 0.249083E+09 | 301.64 | 28-APR-13:00 | 35.00 | 23.20 |
May | 0.105314E+11 | 25794.79 | 11-MAY-05:01 | 28.00 | 16.04 | 0.259133E+09 | 301.64 | 20-MAY-15:00 | 36.00 | 23.70 |
June | 0.114333E+11 | 23859.81 | 16-JUN-05:01 | 28.17 | 20.45 | 0.259160E+09 | 301.95 | 09-JUN-12:09 | 39.90 | 27.61 |
July | 0.122480E+11 | 23360.61 | 03-JUL-05:01 | 28.83 | 16.80 | 0.249269E+09 | 308.46 | 17-JUL-12:09 | 38.05 | 29.48 |
August | 0.135054E+11 | 20871.27 | 07-AUG-05:01 | 32.82 | 23.14 | 0.269322E+09 | 314.36 | 10-AUG-12:09 | 42.17 | 28.02 |
September | 0.112261E+11 | 20482.30 | 05-SEP-05:01 | 30.17 | 24.65 | 0.249202E+09 | 301.82 | 07-SEP-12:09 | 38.78 | 28.15 |
October | 0.989694E+10 | 25588.91 | 20-OCT-05:01 | 23.17 | 16.22 | 0.249171E+09 | 301.63 | 02-OCT-15:50 | 34.15 | 23.08 |
November | 0.771102E+10 | 24054.56 | 18-NOV-06:01 | 20.08 | 15.99 | 0.239141E+09 | 301.62 | 06-NOV-14:20 | 32.67 | 20.85 |
December | 0.549915E+10 | 23898.25 | 13-DEC-06:01 | 15.02 | 12.68 | 0.248908E+09 | 301.61 | 01-DEC-13:09 | 28.17 | 18.16 |
Annual Sum or Average | 0.104763E+12 | 0.301821E+10 | ||||||||
Minimum of Months | 0.391841E+10 | 20482.30 | 15.02 | 12.09 | 0.228792E+09 | 301.61 | 18.33 | 15.58 | ||
Maximum of Months | 0.135054E+11 | 26373.19 | 32.82 | 24.65 | 0.269322E+09 | 314.36 | 42.17 | 29.48 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199827E+10 | 13288.92 | 29-JAN-14:55 | 25.00 | 19.61 | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.83 |
February | 0.441771E+10 | 58635.18 | 05-FEB-14:43 | 31.93 | 19.35 | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.58 |
March | 0.103300E+11 | 73435.68 | 26-MAR-13:53 | 33.00 | 18.33 | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.45 |
April | 0.184793E+11 | 74130.00 | 23-APR-14:02 | 32.00 | 18.38 | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 |
May | 0.352569E+11 | 70304.22 | 10-MAY-17:42 | 36.17 | 20.06 | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 | 23.55 |
June | 0.407791E+11 | 69659.32 | 15-JUN-18:23 | 35.50 | 21.40 | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.23 |
July | 0.489059E+11 | 68457.50 | 20-JUL-21:42 | 38.18 | 18.75 | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.01 |
August | 0.516178E+11 | 64513.61 | 06-AUG-08:23 | 36.50 | 23.30 | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 |
September | 0.397685E+11 | 61490.68 | 04-SEP-17:02 | 39.67 | 23.30 | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.03 |
October | 0.301217E+11 | 72299.60 | 29-OCT-15:32 | 32.00 | 19.83 | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 |
November | 0.162156E+11 | 71020.22 | 05-NOV-12:23 | 33.70 | 19.08 | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.16 |
December | 0.591407E+10 | 48281.94 | 03-DEC-13:13 | 28.87 | 18.92 | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.62 |
Annual Sum or Average | 0.303805E+12 | 0.00 | ||||||||
Minimum of Months | 0.199827E+10 | 13288.92 | 25.00 | 18.33 | 0.00 | 0.00 | 15.70 | 12.83 | ||
Maximum of Months | 0.516178E+11 | 74130.00 | 39.67 | 23.30 | 0.00 | 0.00 | 33.23 | 28.28 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.83 | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.58 | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.58 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.45 | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.45 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 | 23.55 | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 | 23.55 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.23 | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.23 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.01 | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.01 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.03 | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 | 21.16 | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.16 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.62 | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.62 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 15.70 | 12.83 | 0.00 | 0.00 | 15.70 | 12.83 | ||
Maximum of Months | 0.00 | 0.00 | 33.23 | 28.28 | 0.00 | 0.00 | 33.23 | 28.28 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26930190.44 | 1074.88 | 02-JAN-07:30 | 13.00 |
February | 16953289.92 | 740.15 | 13-FEB-07:15 | 13.47 |
March | 9481933.23 | 719.90 | 17-MAR-06:10 | 16.83 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 10316567.76 | 720.43 | 28-DEC-07:10 | 14.75 |
Annual Sum or Average | 63681981.36 | |||
Minimum of Months | 0.00 | 0.00 | 13.00 | |
Maximum of Months | 26930190.44 | 1074.88 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128483E+10 | 5657.89 | 10-JAN-18:00 | 22.50 |
February | 0.667665E+09 | 5102.33 | 15-FEB-08:00 | 23.20 |
March | 0.363790E+09 | 5080.87 | 01-MAR-07:05 | 24.17 |
April | 0.103919E+09 | 4274.55 | 10-APR-06:05 | 22.73 |
May | 1534260.19 | 5713.53 | 16-MAY-06:04 | 23.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 475289.04 | 3960.74 | 25-SEP-06:04 | 23.23 |
October | 1651465.63 | 5091.83 | 07-OCT-06:05 | 24.53 |
November | 39793296.68 | 3667.24 | 29-NOV-07:05 | 20.67 |
December | 0.453919E+09 | 4763.33 | 16-DEC-18:00 | 21.00 |
Annual Sum or Average | 0.291758E+10 | |||
Minimum of Months | 0.00 | 0.00 | 20.67 | |
Maximum of Months | 0.128483E+10 | 5713.53 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.256100E+10 | 1939.55 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.233575E+10 | 1939.55 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.266872E+10 | 1939.55 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.252182E+10 | 1939.55 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.261486E+10 | 1939.55 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.257569E+10 | 1939.55 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.256100E+10 | 1939.55 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.266872E+10 | 1939.55 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.252182E+10 | 1939.55 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.256100E+10 | 1939.55 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.246796E+10 | 1939.55 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.256100E+10 | 1939.55 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.306193E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.233575E+10 | 1939.55 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.266872E+10 | 1939.55 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112294E+11 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102778E+11 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.118738E+11 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.111270E+11 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.115516E+11 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.114492E+11 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112294E+11 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.118738E+11 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.111270E+11 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112294E+11 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108048E+11 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112294E+11 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135003E+12 | ||||
Minimum of Months | 0.102778E+11 | 10075.60 | 0.00 | 0.00 | |
Maximum of Months | 0.118738E+11 | 10075.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.258277E+11 | 23173.88 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.236390E+11 | 23173.88 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.273097E+11 | 23173.88 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.255921E+11 | 23173.88 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.265687E+11 | 23173.88 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.263332E+11 | 23173.88 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.258277E+11 | 23173.88 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.273097E+11 | 23173.88 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.255921E+11 | 23173.88 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.258277E+11 | 23173.88 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.248511E+11 | 23173.88 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.258277E+11 | 23173.88 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.236390E+11 | 23173.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.273097E+11 | 23173.88 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8793321.07 | 0.743798E+09 |
February | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94054726.79 | 0.567311E+09 |
March | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334395E+09 | 0.382974E+09 |
April | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636587E+09 | 0.170741E+09 |
May | 0.565842E+09 | 0.261486E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137952E+10 | 28926240.87 |
June | 0.565842E+09 | 0.257569E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167932E+10 | 7991158.02 |
July | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186233E+10 | 120104.06 |
August | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210618E+10 | 58876.41 |
September | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145083E+10 | 8530423.39 |
October | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998040E+09 | 38748876.03 |
November | 0.522316E+09 | 0.246796E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480799E+09 | 0.196398E+09 |
December | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73979884.35 | 0.505776E+09 |
Annual Sum or Average | 0.659424E+10 | 0.306193E+11 | 0.319458E+11 | 0.111048E+11 | 0.265137E+10 | ||||
Minimum of Months | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8793321.07 | 58876.41 |
Maximum of Months | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210618E+10 | 0.743798E+09 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2930369.61 | 0.511554E+10 |
February | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205715E+09 | 0.508923E+10 |
March | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779906E+09 | 0.333027E+10 |
April | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214698E+10 | 0.151459E+10 |
May | 0.00 | 0.115516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628892E+10 | 0.213336E+09 |
June | 0.00 | 0.114492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.828774E+10 | 52978317.13 |
July | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108711E+11 | 0.00 |
August | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110126E+11 | 0.00 |
September | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736673E+10 | 43369542.85 |
October | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409937E+10 | 0.382725E+09 |
November | 0.00 | 0.108048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113729E+10 | 0.158733E+10 |
December | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52769483.31 | 0.414971E+10 |
Annual Sum or Average | 0.135003E+12 | 0.522520E+11 | 0.214791E+11 | ||||||
Minimum of Months | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2930369.61 | 0.00 |
Maximum of Months | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110126E+11 | 0.511554E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23329502.35 | 0.156350E+11 |
February | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265640E+09 | 0.192509E+11 |
March | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487884E+09 | 0.164926E+11 |
April | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266373E+09 | 0.978571E+10 |
May | 0.00 | 0.265687E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905993E+09 | 0.278443E+10 |
June | 0.00 | 0.263332E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.931663E+09 | 0.246473E+10 |
July | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.872423E+09 | 0.191370E+10 |
August | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678296E+09 | 0.222078E+10 |
September | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533735E+09 | 0.233252E+10 |
October | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242632E+09 | 0.410051E+10 |
November | 0.00 | 0.248511E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16911731.30 | 0.976307E+10 |
December | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10976021.64 | 0.184298E+11 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | 0.523586E+10 | 0.105174E+12 | |||||
Minimum of Months | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10976021.64 | 0.191370E+10 |
Maximum of Months | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.931663E+09 | 0.192509E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1939.55 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1282.89 | 23-JAN-13:00 | 4523.07 | 19-JAN-07:05 |
February | 659.25 | 01-FEB-08:09 | 1939.55 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2566.29 | 07-FEB-13:00 | 4006.84 | 13-FEB-07:05 |
March | 659.25 | 01-MAR-08:09 | 1939.55 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5013.52 | 27-MAR-11:10 | 3426.78 | 07-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1939.55 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6049.03 | 28-APR-12:00 | 2665.06 | 05-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1939.55 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5817.04 | 09-MAY-12:00 | 1262.54 | 01-MAY-06:03 |
June | 659.25 | 01-JUN-07:10 | 1939.55 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6965.50 | 09-JUN-16:10 | 311.05 | 07-JUN-05:01 |
July | 659.25 | 01-JUL-07:10 | 1939.55 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7273.16 | 21-JUL-12:00 | 16.78 | 03-JUL-05:01 |
August | 659.25 | 01-AUG-07:10 | 1939.55 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7444.69 | 16-AUG-12:00 | 8.70 | 27-AUG-06:00 |
September | 659.25 | 01-SEP-07:10 | 1939.55 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5784.88 | 05-SEP-16:10 | 373.25 | 25-SEP-05:01 |
October | 659.25 | 02-OCT-07:10 | 1939.55 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4844.84 | 19-OCT-16:10 | 706.70 | 30-OCT-06:10 |
November | 659.25 | 01-NOV-07:10 | 1939.55 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3187.30 | 01-NOV-16:10 | 2647.32 | 22-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1939.55 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1532.42 | 01-DEC-13:00 | 3714.11 | 18-DEC-07:05 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1282.89 | 8.70 | |||||
Maximum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 7444.69 | 4523.07 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.41 | 23-JAN-14:00 | 8707.18 | 19-JAN-09:00 |
February | 0.00 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5595.89 | 05-FEB-14:47 | 10064.15 | 10-FEB-18:00 |
March | 0.00 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10794.68 | 01-MAR-16:10 | 8053.46 | 25-MAR-09:00 |
April | 0.00 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14831.53 | 28-APR-15:10 | 5349.16 | 04-APR-07:00 |
May | 0.00 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39542.18 | 21-MAY-12:51 | 2684.43 | 01-MAY-07:10 |
June | 0.00 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20899.61 | 09-JUN-15:40 | 1876.65 | 07-JUN-06:10 |
July | 0.00 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20954.48 | 14-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17709.11 | 10-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15336.18 | 02-SEP-16:00 | 1130.53 | 25-SEP-05:40 |
October | 0.00 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16319.68 | 19-OCT-15:10 | 3497.07 | 21-OCT-07:00 |
November | 0.00 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6029.90 | 01-NOV-15:10 | 4624.76 | 22-NOV-07:10 |
December | 0.00 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1959.90 | 10-DEC-12:20 | 7471.42 | 16-DEC-08:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.41 | 0.00 | |||
Maximum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39542.18 | 10064.15 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23173.88 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2813.67 | 23-JAN-13:10 | 25998.06 | 19-JAN-09:30 |
February | 0.00 | 23173.88 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8947.58 | 05-FEB-15:00 | 30495.31 | 10-FEB-16:00 |
March | 0.00 | 23173.88 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18956.17 | 01-MAR-11:00 | 60779.37 | 25-MAR-08:45 |
April | 0.00 | 23173.88 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5545.94 | 25-APR-07:53 | 18314.06 | 04-APR-07:10 |
May | 0.00 | 23173.88 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9794.54 | 21-MAY-12:51 | 12808.11 | 01-MAY-07:50 |
June | 0.00 | 23173.88 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6701.41 | 09-JUN-15:00 | 9255.60 | 07-JUN-05:55 |
July | 0.00 | 23173.88 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6755.13 | 15-JUL-09:55 | 4242.70 | 16-JUL-16:52 |
August | 0.00 | 23173.88 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8587.46 | 16-AUG-10:55 | 7026.10 | 10-AUG-20:52 |
September | 0.00 | 23173.88 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4206.26 | 26-SEP-11:00 | 7808.94 | 23-SEP-07:20 |
October | 0.00 | 23173.88 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4128.65 | 19-OCT-14:00 | 15785.01 | 21-OCT-07:10 |
November | 0.00 | 23173.88 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1053.23 | 05-NOV-10:53 | 13923.83 | 22-NOV-06:01 |
December | 0.00 | 23173.88 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1626.87 | 10-DEC-12:00 | 46511.67 | 15-DEC-11:55 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1053.23 | 4242.70 | ||||
Maximum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 18956.17 | 60779.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21278.89 | 25-JAN-06:02 | 435.11 | 3476.08 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 575.63 |
February | 23380.84 | 11-FEB-06:02 | 362.59 | 2896.74 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.93 |
March | 25891.92 | 28-MAR-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.02 |
April | 26373.19 | 26-APR-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.30 |
May | 25794.79 | 11-MAY-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.95 |
June | 23859.81 | 16-JUN-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 |
July | 23360.61 | 03-JUL-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.78 |
August | 20871.27 | 07-AUG-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 239.96 | 0.00 |
September | 20482.30 | 05-SEP-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 62.28 | 0.00 |
October | 25588.91 | 20-OCT-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.27 |
November | 24054.56 | 18-NOV-06:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.08 |
December | 23898.25 | 13-DEC-06:01 | 507.62 | 4055.43 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 721.81 |
Annual Sum or Average | |||||||||||
Minimum of Months | 20482.30 | 362.59 | 2896.74 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26373.19 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 239.96 | 721.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13288.92 | 29-JAN-14:55 | 0.00 | 2370.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 646.06 |
February | 58635.18 | 05-FEB-14:43 | 0.00 | 3556.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5131.34 | 0.00 |
March | 73435.68 | 26-MAR-13:53 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4494.06 | 0.00 |
April | 74130.00 | 23-APR-14:02 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3408.47 | 0.00 |
May | 70304.22 | 10-MAY-17:42 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4008.01 | 0.00 |
June | 69659.32 | 15-JUN-18:23 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4751.37 | 0.00 |
July | 68457.50 | 20-JUL-21:42 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5936.50 | 0.00 |
August | 64513.61 | 06-AUG-08:23 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2199.04 | 0.00 |
September | 61490.68 | 04-SEP-17:02 | 0.00 | 5926.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9863.77 | 0.00 |
October | 72299.60 | 29-OCT-15:32 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3875.61 | 0.00 |
November | 71020.22 | 05-NOV-12:23 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2949.63 | 0.00 |
December | 48281.94 | 03-DEC-13:13 | 0.00 | 3556.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 760.56 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 13288.92 | 0.00 | 2370.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 74130.00 | 0.00 | 5926.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9863.77 | 646.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1976.58 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6259.43 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5102.65 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4229.13 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2072.98 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.77 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.38 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.77 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1782.95 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 883.22 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2311.62 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8367.36 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.77 | |
Maximum of Months | 0.00 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8367.36 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.765545E+11 | 63671.20 | 23-JAN-13:00 | 0.602853E+10 | 3255.95 | 02-JAN-07:30 |
February | 0.715221E+11 | 71295.69 | 07-FEB-13:20 | 0.544320E+10 | 2250.00 | 01-FEB-00:10 |
March | 0.852054E+11 | 75558.01 | 27-MAR-10:00 | 0.602640E+10 | 2250.00 | 01-MAR-00:10 |
April | 0.867303E+11 | 79290.96 | 28-APR-12:20 | 0.583200E+10 | 2250.00 | 01-APR-00:10 |
May | 0.104110E+12 | 83499.33 | 31-MAY-14:39 | 0.602640E+10 | 2250.00 | 01-MAY-00:10 |
June | 0.110724E+12 | 88217.75 | 09-JUN-14:20 | 0.583200E+10 | 2250.00 | 01-JUN-00:10 |
July | 0.118311E+12 | 90608.16 | 14-JUL-13:00 | 0.602640E+10 | 2250.00 | 01-JUL-00:10 |
August | 0.125451E+12 | 92981.63 | 10-AUG-15:30 | 0.602640E+10 | 2250.00 | 01-AUG-00:10 |
September | 0.110030E+12 | 85796.65 | 08-SEP-14:50 | 0.583200E+10 | 2250.00 | 01-SEP-00:10 |
October | 0.100216E+12 | 81810.62 | 07-OCT-13:00 | 0.602640E+10 | 2250.00 | 01-OCT-00:10 |
November | 0.850198E+11 | 78544.66 | 01-NOV-13:00 | 0.583200E+10 | 2250.00 | 01-NOV-00:10 |
December | 0.796609E+11 | 69235.30 | 04-DEC-13:09 | 0.602640E+10 | 2250.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.115354E+13 | 0.709581E+11 | ||||
Minimum of Months | 0.715221E+11 | 63671.20 | 0.544320E+10 | 2250.00 | ||
Maximum of Months | 0.125451E+12 | 92981.63 | 0.602853E+10 | 3255.95 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.396181E+11 | 0.117148E+11 | 0.115358E+11 | 0.00 | 0.833843E+10 | 0.00 | 0.00 | 0.337176E+10 | 0.00 | 0.00 | 0.00 | 0.197563E+10 | 0.00 |
February | 0.362526E+11 | 0.101638E+11 | 0.105871E+11 | 0.00 | 0.777318E+10 | 0.00 | 0.00 | 0.496762E+10 | 0.00 | 0.00 | 0.00 | 0.177780E+10 | 0.00 |
March | 0.418523E+11 | 0.106447E+11 | 0.123357E+11 | 0.00 | 0.973777E+10 | 0.00 | 0.00 | 0.867902E+10 | 0.00 | 0.00 | 0.00 | 0.195597E+10 | 0.00 |
April | 0.392410E+11 | 0.965468E+10 | 0.114862E+11 | 0.00 | 0.109375E+11 | 0.00 | 0.00 | 0.135977E+11 | 0.00 | 0.00 | 0.00 | 0.181320E+10 | 0.00 |
May | 0.407352E+11 | 0.945669E+10 | 0.119357E+11 | 0.00 | 0.154677E+11 | 0.00 | 0.00 | 0.246957E+11 | 0.00 | 0.00 | 0.00 | 0.181927E+10 | 0.00 |
June | 0.403581E+11 | 0.890984E+10 | 0.118862E+11 | 0.00 | 0.166921E+11 | 0.00 | 0.00 | 0.311457E+11 | 0.00 | 0.00 | 0.00 | 0.173249E+10 | 0.00 |
July | 0.396181E+11 | 0.929640E+10 | 0.115358E+11 | 0.00 | 0.177729E+11 | 0.00 | 0.00 | 0.383393E+11 | 0.00 | 0.00 | 0.00 | 0.174894E+10 | 0.00 |
August | 0.418523E+11 | 0.974425E+10 | 0.123357E+11 | 0.00 | 0.183980E+11 | 0.00 | 0.00 | 0.413231E+11 | 0.00 | 0.00 | 0.00 | 0.179730E+10 | 0.00 |
September | 0.392410E+11 | 0.100177E+11 | 0.114862E+11 | 0.00 | 0.163459E+11 | 0.00 | 0.00 | 0.311727E+11 | 0.00 | 0.00 | 0.00 | 0.176626E+10 | 0.00 |
October | 0.396181E+11 | 0.109935E+11 | 0.115358E+11 | 0.00 | 0.140593E+11 | 0.00 | 0.00 | 0.221414E+11 | 0.00 | 0.00 | 0.00 | 0.186816E+10 | 0.00 |
November | 0.381239E+11 | 0.111915E+11 | 0.110862E+11 | 0.00 | 0.999326E+10 | 0.00 | 0.00 | 0.127685E+11 | 0.00 | 0.00 | 0.00 | 0.185633E+10 | 0.00 |
December | 0.396181E+11 | 0.118798E+11 | 0.115358E+11 | 0.00 | 0.844900E+10 | 0.00 | 0.00 | 0.621619E+10 | 0.00 | 0.00 | 0.00 | 0.196205E+10 | 0.00 |
Annual Sum or Average | 0.476129E+12 | 0.123668E+12 | 0.139282E+12 | 0.153965E+12 | 0.00 | 0.238419E+12 | 0.220734E+11 | ||||||
Minimum of Months | 0.362526E+11 | 0.890984E+10 | 0.105871E+11 | 0.00 | 0.777318E+10 | 0.00 | 0.00 | 0.337176E+10 | 0.00 | 0.00 | 0.00 | 0.173249E+10 | 0.00 |
Maximum of Months | 0.418523E+11 | 0.118798E+11 | 0.123357E+11 | 0.00 | 0.183980E+11 | 0.00 | 0.00 | 0.413231E+11 | 0.00 | 0.00 | 0.00 | 0.197563E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.602853E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.544320E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.583200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.602640E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.709581E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.544320E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.602853E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35189.04 | 02-JAN-09:09 | 7857.00 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 8413.38 | 02-JAN-13:50 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35189.04 | 01-FEB-09:09 | 7857.00 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 10718.68 | 06-FEB-13:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35189.04 | 01-MAR-09:09 | 7857.00 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 10718.68 | 01-MAR-11:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35189.04 | 01-APR-08:09 | 7857.00 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 10718.68 | 01-APR-10:39 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35189.04 | 01-MAY-08:09 | 7857.00 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 10718.68 | 01-MAY-09:39 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35189.04 | 01-JUN-08:09 | 7857.00 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 10718.68 | 01-JUN-06:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35189.04 | 01-JUL-08:09 | 7857.00 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 10718.68 | 01-JUL-06:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35189.04 | 01-AUG-08:09 | 7857.00 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 10718.68 | 01-AUG-06:19 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35189.04 | 01-SEP-08:09 | 7857.00 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 10718.68 | 01-SEP-06:19 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35189.04 | 02-OCT-08:09 | 7857.00 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 10718.68 | 02-OCT-07:40 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35189.04 | 01-NOV-08:09 | 7857.00 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 10718.68 | 01-NOV-09:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35189.04 | 01-DEC-09:09 | 7857.00 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 10718.68 | 01-DEC-12:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35189.04 | 7857.00 | 10112.62 | 0.00 | 8413.38 | 0.00 | 0.00 | |||||
Maximum of Months | 35189.04 | 7857.00 | 10112.62 | 0.00 | 10718.68 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 8268.65 | 23-JAN-13:50 | 0.00 | 0.00 | 0.00 | 1740.30 | 12-JAN-12:09 | 0.00 |
February | 13999.14 | 07-FEB-12:00 | 0.00 | 0.00 | 0.00 | 1737.45 | 01-FEB-12:00 | 0.00 |
March | 19052.94 | 27-MAR-11:30 | 0.00 | 0.00 | 0.00 | 1725.28 | 01-MAR-12:00 | 0.00 |
April | 24390.41 | 28-APR-15:09 | 0.00 | 0.00 | 0.00 | 1704.07 | 01-APR-11:50 | 0.00 |
May | 30568.24 | 21-MAY-13:09 | 0.00 | 0.00 | 0.00 | 1681.83 | 01-MAY-11:00 | 0.00 |
June | 35427.41 | 09-JUN-16:10 | 0.00 | 0.00 | 0.00 | 1663.20 | 01-JUN-11:50 | 0.00 |
July | 36697.48 | 14-JUL-16:10 | 0.00 | 0.00 | 0.00 | 1654.29 | 31-JUL-11:20 | 0.00 |
August | 40405.47 | 10-AUG-16:10 | 0.00 | 0.00 | 0.00 | 1666.09 | 31-AUG-11:20 | 0.00 |
September | 31925.58 | 12-SEP-16:10 | 0.00 | 0.00 | 0.00 | 1685.31 | 30-SEP-11:39 | 0.00 |
October | 25774.68 | 07-OCT-15:50 | 0.00 | 0.00 | 0.00 | 1708.33 | 31-OCT-11:30 | 0.00 |
November | 21559.72 | 01-NOV-15:39 | 0.00 | 0.00 | 0.00 | 1728.05 | 30-NOV-12:09 | 0.00 |
December | 12668.15 | 04-DEC-12:00 | 0.00 | 0.00 | 0.00 | 1739.09 | 30-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8268.65 | 0.00 | 0.00 | 0.00 | 1654.29 | 0.00 | ||
Maximum of Months | 40405.47 | 0.00 | 0.00 | 0.00 | 1740.30 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 63671.20 | 23-JAN-13:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 8413.38 | 0.00 | 0.00 | 8245.20 | 0.00 |
February | 71295.69 | 07-FEB-13:20 | 35189.04 | 10112.62 | 0.00 | 0.00 | 10718.68 | 0.00 | 0.00 | 13567.87 | 0.00 |
March | 75558.01 | 27-MAR-10:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 10718.68 | 0.00 | 0.00 | 17876.13 | 0.00 |
April | 79290.96 | 28-APR-12:20 | 35189.04 | 10112.62 | 0.00 | 0.00 | 10718.68 | 0.00 | 0.00 | 21606.91 | 0.00 |
May | 83499.33 | 31-MAY-14:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 10718.68 | 0.00 | 0.00 | 25832.67 | 0.00 |
June | 88217.75 | 09-JUN-14:20 | 35189.04 | 10112.62 | 0.00 | 0.00 | 10718.68 | 0.00 | 0.00 | 30554.61 | 0.00 |
July | 90608.16 | 14-JUL-13:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 10718.68 | 0.00 | 0.00 | 33161.32 | 0.00 |
August | 92981.63 | 10-AUG-15:30 | 31277.33 | 10112.62 | 0.00 | 0.00 | 10718.68 | 0.00 | 0.00 | 39306.41 | 0.00 |
September | 85796.65 | 08-SEP-14:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 10718.68 | 0.00 | 0.00 | 28124.36 | 0.00 |
October | 81810.62 | 07-OCT-13:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 10718.68 | 0.00 | 0.00 | 24141.58 | 0.00 |
November | 78544.66 | 01-NOV-13:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 10718.68 | 0.00 | 0.00 | 20862.18 | 0.00 |
December | 69235.30 | 04-DEC-13:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 10718.68 | 0.00 | 0.00 | 12385.77 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 63671.20 | 31277.33 | 10112.62 | 0.00 | 0.00 | 8413.38 | 0.00 | 0.00 | 8245.20 | 0.00 | |
Maximum of Months | 92981.63 | 35189.04 | 10112.62 | 0.00 | 0.00 | 10718.68 | 0.00 | 0.00 | 39306.41 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 3255.95 | 02-JAN-07:30 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 2250.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 2250.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 2250.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 2250.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 2250.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 2250.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 2250.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 2250.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 2250.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 2250.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 2250.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 2250.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 3255.95 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.61 | 0.17 | 24.61 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.50 | 0.67 | 24.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.04 | 1.83 | 24.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 24.79 | 5.50 | 24.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 25.54 | 8.67 | 25.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 25.84 | 9.17 | 25.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 27.50 | 10.00 | 25.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.22 | 13.17 | 25.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 26.69 | 9.17 | 25.40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 25.84 | 8.50 | 25.11 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 24.98 | 6.83 | 24.74 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.54 | 1.17 | 24.54 |
Annual Sum or Average | 0.00 | 0.00 | 98.17 | 26.35 | 74.83 | 25.21 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.50 | 0.17 | 24.50 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.50 | 13.17 | 25.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.26 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.45 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.45 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 27.51 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 48.00 | 27.68 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 65.67 | 27.65 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 107.17 | 27.74 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 106.83 | 27.73 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 71.00 | 27.64 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 38.33 | 27.59 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.45 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.32 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 479.67 | 27.67 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.26 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 107.17 | 27.74 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 58.33 | 23.48 | 125.33 | 23.90 | 0.00 | 0.00 |
February | 16.33 | 23.46 | 188.83 | 23.90 | 0.50 | 24.17 |
March | 4.83 | 23.86 | 268.00 | 23.91 | 0.67 | 24.55 |
April | 3.33 | 24.42 | 298.33 | 23.92 | 3.33 | 24.42 |
May | 11.67 | 24.47 | 312.00 | 23.93 | 11.67 | 24.47 |
June | 33.83 | 24.27 | 312.00 | 23.95 | 33.83 | 24.27 |
July | 54.50 | 24.24 | 300.00 | 23.96 | 54.50 | 24.24 |
August | 59.33 | 24.28 | 324.00 | 23.98 | 59.33 | 24.28 |
September | 40.67 | 24.27 | 300.00 | 23.95 | 40.67 | 24.27 |
October | 15.00 | 24.37 | 300.00 | 23.94 | 15.00 | 24.37 |
November | 5.50 | 24.47 | 288.00 | 23.92 | 5.50 | 24.47 |
December | 5.83 | 23.67 | 249.17 | 23.91 | 0.50 | 24.44 |
Annual Sum or Average | 309.17 | 24.07 | 3265.67 | 23.93 | 225.50 | 24.29 |
Minimum of Months | 3.33 | 23.46 | 125.33 | 23.90 | 0.00 | 0.00 |
Maximum of Months | 59.33 | 24.47 | 324.00 | 23.98 | 59.33 | 24.55 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.585329E+10 | 0.156332E+10 | 259.67 | 0.496401E+10 | 0.889284E+09 | 0.00 | 1.00 | 23-JAN-06:02 | 0.00 | 01-JAN-00:10 | 31761.80 | 30-JAN-06:01 | 23083.80 | 25-JAN-06:02 | 10493.27 | 30-JAN-06:02 | 7340.81 | 30-JAN-06:01 | 0.00 | 01-JAN-00:10 |
February | 0.695517E+10 | 0.187364E+10 | 249.13 | 0.578665E+10 | 0.116852E+10 | 0.00 | 1.00 | 04-FEB-06:02 | 0.00 | 01-FEB-00:10 | 33054.80 | 09-FEB-06:01 | 25780.06 | 11-FEB-06:02 | 12575.63 | 09-FEB-06:03 | 7546.58 | 09-FEB-06:01 | 0.00 | 01-FEB-00:10 |
March | 0.978051E+10 | 0.270028E+10 | 307.53 | 0.841122E+10 | 0.136929E+10 | 0.00 | 1.00 | 01-MAR-06:01 | 0.00 | 01-MAR-00:10 | 32820.25 | 29-MAR-05:01 | 28163.71 | 28-MAR-05:01 | 12372.92 | 29-MAR-05:04 | 7510.80 | 29-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.117081E+11 | 0.336302E+10 | 298.30 | 0.992490E+10 | 0.178318E+10 | 0.00 | 1.00 | 01-APR-05:01 | 0.00 | 01-APR-00:10 | 33493.81 | 10-APR-05:01 | 28352.12 | 26-APR-05:01 | 13299.08 | 10-APR-05:04 | 7611.73 | 10-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.164613E+11 | 0.501403E+10 | 338.45 | 0.137441E+11 | 0.271726E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:05 | 35117.36 | 24-MAY-05:01 | 28293.78 | 11-MAY-05:01 | 16462.44 | 24-MAY-05:05 | 8019.06 | 23-MAY-05:01 | 0.00 | 01-MAY-00:05 |
June | 0.196456E+11 | 0.599265E+10 | 336.26 | 0.149874E+11 | 0.465819E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 35581.77 | 08-JUN-05:01 | 26262.64 | 16-JUN-05:01 | 18279.14 | 19-JUN-05:06 | 8469.21 | 09-JUN-12:00 | 0.00 | 01-JUN-00:10 |
July | 0.223064E+11 | 0.687874E+10 | 372.77 | 0.160782E+11 | 0.622816E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 34666.18 | 06-JUL-05:01 | 25910.77 | 22-JUL-05:01 | 18836.90 | 06-JUL-05:07 | 8971.88 | 30-JUL-14:11 | 0.00 | 01-JUL-00:10 |
August | 0.248544E+11 | 0.765001E+10 | 401.10 | 0.176794E+11 | 0.717494E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 34666.18 | 31-AUG-05:01 | 23690.54 | 07-AUG-05:01 | 19185.00 | 23-AUG-05:09 | 8853.97 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 0.200895E+11 | 0.597524E+10 | 343.45 | 0.145833E+11 | 0.550616E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 36016.58 | 25-SEP-05:01 | 22854.37 | 05-SEP-05:01 | 18345.03 | 09-SEP-05:06 | 8418.79 | 07-SEP-12:00 | 0.00 | 01-SEP-00:10 |
October | 0.163869E+11 | 0.471880E+10 | 324.35 | 0.126699E+11 | 0.371701E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 35632.06 | 07-OCT-05:01 | 27441.28 | 20-OCT-05:01 | 17606.19 | 02-OCT-05:04 | 8055.74 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.124006E+11 | 0.342275E+10 | 286.24 | 0.977578E+10 | 0.262480E+10 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:05 | 34548.50 | 03-NOV-05:01 | 25448.82 | 18-NOV-06:01 | 14657.02 | 03-NOV-05:06 | 7758.53 | 03-NOV-05:01 | 0.00 | 01-NOV-00:05 |
December | 0.844573E+10 | 0.225400E+10 | 280.20 | 0.689330E+10 | 0.155244E+10 | 0.00 | 1.00 | 01-DEC-06:01 | 0.00 | 01-DEC-00:10 | 32655.61 | 06-DEC-06:01 | 25199.96 | 13-DEC-06:01 | 12526.25 | 06-DEC-06:04 | 7485.27 | 06-DEC-06:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.174887E+12 | 0.514065E+11 | 3797.47 | 0.135498E+12 | 0.393892E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.585329E+10 | 0.156332E+10 | 249.13 | 0.496401E+10 | 0.889284E+09 | 0.00 | 1.00 | 0.00 | 31761.80 | 22854.37 | 10493.27 | 7340.81 | 0.00 | |||||||
Maximum of Months | 0.248544E+11 | 0.765001E+10 | 401.10 | 0.176794E+11 | 0.717494E+10 | 0.00 | 1.00 | 0.00 | 36016.58 | 28352.12 | 19185.00 | 8971.88 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.615601E+10 | 0.180844E+10 | 184.50 | 0.509826E+10 | 0.105775E+10 | 0.00 | 0.27 | 29-JAN-14:55 | 0.00 | 01-JAN-00:10 | 22608.35 | 29-JAN-14:55 | 17600.21 | 28-JAN-14:00 | 7195.18 | 29-JAN-14:55 | 6907.53 | 29-JAN-14:55 | 0.00 | 01-JAN-00:10 |
February | 0.103376E+11 | 0.309398E+10 | 210.81 | 0.854899E+10 | 0.178863E+10 | 0.00 | 0.90 | 05-FEB-14:43 | 0.00 | 01-FEB-00:10 | 77695.59 | 05-FEB-14:43 | 69489.22 | 05-FEB-14:43 | 9338.67 | 07-FEB-16:25 | 23523.87 | 05-FEB-14:43 | 0.00 | 01-FEB-00:10 |
March | 0.194090E+11 | 0.597874E+10 | 293.52 | 0.167265E+11 | 0.268248E+10 | 0.00 | 1.00 | 26-MAR-13:53 | 0.00 | 01-MAR-00:10 | 86226.60 | 26-MAR-14:32 | 85062.20 | 26-MAR-13:53 | 18376.84 | 28-MAR-17:10 | 26026.52 | 26-MAR-13:53 | 0.00 | 01-MAR-00:10 |
April | 0.320315E+11 | 0.102347E+11 | 369.40 | 0.268757E+11 | 0.515583E+10 | 0.00 | 1.00 | 02-APR-14:02 | 0.00 | 01-APR-00:10 | 105771.89 | 30-APR-17:53 | 85611.16 | 23-APR-13:23 | 43894.05 | 30-APR-17:53 | 28764.96 | 30-APR-11:53 | 0.00 | 01-APR-00:10 |
May | 0.586149E+11 | 0.196817E+11 | 547.21 | 0.480730E+11 | 0.105419E+11 | 0.00 | 1.00 | 03-MAY-17:06 | 0.00 | 01-MAY-00:05 | 107247.51 | 27-MAY-05:10 | 84227.26 | 07-MAY-12:43 | 44858.83 | 24-MAY-19:03 | 30346.23 | 31-MAY-17:42 | 0.00 | 01-MAY-00:05 |
June | 0.756047E+11 | 0.251530E+11 | 574.41 | 0.553048E+11 | 0.202999E+11 | 0.00 | 1.00 | 01-JUN-17:05 | 0.00 | 01-JUN-00:15 | 114654.94 | 08-JUN-05:08 | 82087.38 | 15-JUN-18:23 | 59501.58 | 08-JUN-05:08 | 30531.15 | 04-JUN-13:43 | 0.00 | 01-JUN-00:10 |
July | 0.935997E+11 | 0.314605E+11 | 606.49 | 0.656849E+11 | 0.279147E+11 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:15 | 110900.12 | 06-JUL-05:01 | 81850.99 | 20-JUL-21:42 | 55871.67 | 04-JUL-23:03 | 31213.69 | 30-JUL-13:42 | 0.00 | 01-JUL-00:10 |
August | 0.100677E+12 | 0.336731E+11 | 613.50 | 0.694014E+11 | 0.312760E+11 | 0.00 | 1.00 | 01-AUG-00:23 | 0.00 | 01-AUG-00:13 | 111279.36 | 08-AUG-05:01 | 76843.49 | 06-AUG-08:23 | 60845.69 | 08-AUG-05:01 | 31774.55 | 10-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.773377E+11 | 0.251975E+11 | 571.42 | 0.537788E+11 | 0.235589E+11 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:13 | 115262.06 | 23-SEP-05:10 | 77700.16 | 04-SEP-17:02 | 61586.78 | 23-SEP-05:10 | 30519.90 | 04-SEP-14:22 | 0.00 | 01-SEP-00:10 |
October | 0.544310E+11 | 0.174226E+11 | 522.67 | 0.411808E+11 | 0.132502E+11 | 0.00 | 1.00 | 01-OCT-09:43 | 0.00 | 01-OCT-00:15 | 112969.98 | 02-OCT-05:06 | 84077.54 | 09-OCT-16:23 | 56968.08 | 02-OCT-05:06 | 29160.01 | 01-OCT-19:43 | 0.00 | 01-OCT-00:10 |
November | 0.303972E+11 | 0.934579E+10 | 349.21 | 0.238140E+11 | 0.658321E+10 | 0.00 | 1.00 | 01-NOV-17:06 | 0.00 | 01-NOV-00:15 | 100662.50 | 01-NOV-17:06 | 82654.98 | 05-NOV-12:23 | 35090.55 | 01-NOV-17:06 | 28136.40 | 01-NOV-17:06 | 0.00 | 01-NOV-00:05 |
December | 0.134192E+11 | 0.396220E+10 | 246.64 | 0.107739E+11 | 0.264534E+10 | 0.00 | 0.77 | 03-DEC-13:13 | 0.00 | 01-DEC-00:10 | 66862.31 | 03-DEC-13:13 | 56122.15 | 03-DEC-13:13 | 10740.16 | 03-DEC-13:13 | 19742.36 | 03-DEC-13:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.572016E+12 | 0.187012E+12 | 5089.79 | 0.425261E+12 | 0.146755E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.615601E+10 | 0.180844E+10 | 184.50 | 0.509826E+10 | 0.105775E+10 | 0.00 | 0.27 | 0.00 | 22608.35 | 17600.21 | 7195.18 | 6907.53 | 0.00 | |||||||
Maximum of Months | 0.100677E+12 | 0.336731E+11 | 613.50 | 0.694014E+11 | 0.312760E+11 | 0.00 | 1.00 | 0.00 | 115262.06 | 85611.16 | 61586.78 | 31774.55 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.78 | 12.39 | 30.39 | 80.75 | 115.16 | 0.00 | 0.00 | 744.00 |
February | 48.77 | 14.03 | 34.74 | 104.71 | 101.11 | 0.00 | 0.00 | 672.00 |
March | 57.55 | 17.05 | 40.49 | 147.35 | 81.09 | 0.00 | 0.00 | 744.00 |
April | 62.65 | 17.46 | 45.19 | 194.13 | 57.38 | 0.00 | 0.00 | 720.00 |
May | 68.30 | 20.39 | 47.91 | 265.32 | 20.98 | 0.00 | 0.00 | 744.00 |
June | 70.71 | 22.33 | 48.38 | 291.13 | 9.40 | 0.00 | 0.00 | 720.00 |
July | 65.01 | 18.70 | 46.30 | 310.02 | 1.36 | 0.00 | 0.00 | 744.00 |
August | 66.35 | 20.06 | 46.28 | 317.88 | 0.92 | 0.00 | 0.00 | 744.00 |
September | 63.22 | 19.83 | 43.39 | 257.14 | 12.59 | 0.00 | 0.00 | 720.00 |
October | 56.25 | 18.17 | 38.08 | 196.55 | 34.89 | 0.00 | 0.00 | 744.00 |
November | 48.49 | 15.93 | 32.56 | 137.10 | 71.03 | 0.00 | 0.00 | 720.00 |
December | 40.66 | 12.43 | 28.24 | 85.86 | 105.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 57.59 | 17.41 | 40.18 | 199.54 | 50.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 40.66 | 12.39 | 28.24 | 80.75 | 0.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 70.71 | 22.33 | 48.38 | 317.88 | 115.16 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.78 | 12.39 | 30.39 | 80.75 | 115.16 | 0.00 | 0.00 | 744.00 |
February | 48.77 | 14.03 | 34.74 | 104.71 | 101.11 | 0.00 | 0.00 | 672.00 |
March | 57.55 | 17.05 | 40.49 | 147.35 | 81.09 | 0.00 | 0.00 | 744.00 |
April | 62.65 | 17.46 | 45.19 | 194.13 | 57.38 | 0.00 | 0.00 | 720.00 |
May | 68.30 | 20.39 | 47.91 | 265.32 | 20.98 | 0.00 | 0.00 | 744.00 |
June | 70.71 | 22.33 | 48.38 | 291.13 | 9.40 | 0.00 | 0.00 | 720.00 |
July | 65.01 | 18.70 | 46.30 | 310.02 | 1.36 | 0.00 | 0.00 | 744.00 |
August | 66.35 | 20.06 | 46.28 | 317.88 | 0.92 | 0.00 | 0.00 | 744.00 |
September | 63.22 | 19.83 | 43.39 | 257.14 | 12.59 | 0.00 | 0.00 | 720.00 |
October | 56.25 | 18.17 | 38.08 | 196.55 | 34.89 | 0.00 | 0.00 | 744.00 |
November | 48.49 | 15.93 | 32.56 | 137.10 | 71.03 | 0.00 | 0.00 | 720.00 |
December | 40.66 | 12.43 | 28.24 | 85.86 | 105.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 57.59 | 17.41 | 40.18 | 199.54 | 50.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 40.66 | 12.39 | 28.24 | 80.75 | 0.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 70.71 | 22.33 | 48.38 | 317.88 | 115.16 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.98 | 0.00 | 13.98 | 17.79 | 68.64 | 0.00 | 0.00 | 744.00 |
February | 16.03 | 0.00 | 16.03 | 26.73 | 60.40 | 0.00 | 0.00 | 672.00 |
March | 18.41 | 0.00 | 18.41 | 42.42 | 47.82 | 0.00 | 0.00 | 744.00 |
April | 20.81 | 0.10 | 20.72 | 66.57 | 33.08 | 0.00 | 0.00 | 720.00 |
May | 23.70 | 1.03 | 22.67 | 105.01 | 11.52 | 0.00 | 0.00 | 744.00 |
June | 25.44 | 1.84 | 23.60 | 121.27 | 5.56 | 0.00 | 0.00 | 720.00 |
July | 23.22 | 0.93 | 22.28 | 136.22 | 0.82 | 0.00 | 0.00 | 744.00 |
August | 21.53 | 0.34 | 21.18 | 133.48 | 0.45 | 0.00 | 0.00 | 744.00 |
September | 19.46 | 0.01 | 19.45 | 97.29 | 7.11 | 0.00 | 0.00 | 720.00 |
October | 17.24 | 0.00 | 17.24 | 67.63 | 20.12 | 0.00 | 0.00 | 744.00 |
November | 14.80 | 0.00 | 14.80 | 40.04 | 41.34 | 0.00 | 0.00 | 720.00 |
December | 13.05 | 0.00 | 13.05 | 20.08 | 62.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 18.98 | 0.36 | 18.63 | 73.16 | 29.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.05 | 0.00 | 13.05 | 17.79 | 0.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 25.44 | 1.84 | 23.60 | 136.22 | 68.64 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.98 | 0.00 | 13.98 | 17.79 | 68.64 | 0.00 | 0.00 | 744.00 |
February | 16.03 | 0.00 | 16.03 | 26.72 | 60.40 | 0.00 | 0.00 | 672.00 |
March | 18.41 | 0.00 | 18.41 | 42.42 | 47.82 | 0.00 | 0.00 | 744.00 |
April | 20.81 | 0.10 | 20.71 | 66.57 | 33.07 | 0.00 | 0.00 | 720.00 |
May | 23.70 | 1.03 | 22.67 | 105.01 | 11.52 | 0.00 | 0.00 | 744.00 |
June | 25.44 | 1.84 | 23.60 | 121.27 | 5.56 | 0.00 | 0.00 | 720.00 |
July | 23.21 | 0.93 | 22.28 | 136.22 | 0.82 | 0.00 | 0.00 | 744.00 |
August | 21.52 | 0.34 | 21.18 | 133.48 | 0.45 | 0.00 | 0.00 | 744.00 |
September | 19.46 | 0.01 | 19.45 | 97.29 | 7.11 | 0.00 | 0.00 | 720.00 |
October | 17.24 | 0.00 | 17.24 | 67.63 | 20.11 | 0.00 | 0.00 | 744.00 |
November | 14.80 | 0.00 | 14.80 | 40.04 | 41.34 | 0.00 | 0.00 | 720.00 |
December | 13.05 | 0.00 | 13.05 | 20.08 | 62.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 18.98 | 0.36 | 18.63 | 73.16 | 29.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.05 | 0.00 | 13.05 | 17.79 | 0.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 25.44 | 1.84 | 23.60 | 136.22 | 68.64 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.25 | 15.45 | 24.81 | 58.75 | 55.80 | 3.50 | 0.00 | 744.00 |
February | 48.80 | 19.95 | 28.84 | 73.12 | 54.49 | 0.00 | 0.00 | 672.00 |
March | 58.97 | 24.74 | 34.23 | 92.46 | 53.51 | 0.00 | 0.00 | 744.00 |
April | 69.49 | 30.78 | 38.71 | 115.49 | 48.10 | 1.17 | 0.00 | 720.00 |
May | 78.85 | 38.31 | 40.54 | 136.65 | 34.56 | 2.00 | 0.00 | 744.00 |
June | 82.19 | 41.77 | 40.42 | 142.35 | 33.13 | 8.17 | 0.00 | 720.00 |
July | 79.72 | 40.42 | 39.30 | 140.38 | 29.60 | 1.83 | 0.00 | 744.00 |
August | 75.94 | 37.29 | 38.65 | 132.24 | 30.52 | 3.50 | 0.00 | 744.00 |
September | 68.17 | 32.69 | 35.48 | 117.56 | 35.45 | 21.00 | 0.00 | 720.00 |
October | 57.39 | 26.96 | 30.43 | 95.44 | 43.16 | 31.17 | 0.00 | 744.00 |
November | 45.62 | 19.97 | 25.65 | 69.79 | 56.54 | 0.00 | 0.00 | 720.00 |
December | 37.40 | 14.55 | 22.85 | 51.93 | 62.04 | 4.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.96 | 28.61 | 33.34 | 102.32 | 44.68 | 76.33 | 0.00 | 8760.00 |
Minimum of Months | 37.40 | 14.55 | 22.85 | 51.93 | 29.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.19 | 41.77 | 40.54 | 142.35 | 62.04 | 31.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.25 | 15.45 | 24.81 | 58.75 | 55.80 | 3.50 | 0.00 | 744.00 |
February | 48.80 | 19.95 | 28.84 | 73.12 | 54.49 | 0.00 | 0.00 | 672.00 |
March | 58.97 | 24.74 | 34.23 | 92.46 | 53.51 | 0.00 | 0.00 | 744.00 |
April | 69.49 | 30.78 | 38.71 | 115.49 | 48.10 | 1.17 | 0.00 | 720.00 |
May | 78.85 | 38.31 | 40.54 | 136.65 | 34.56 | 2.00 | 0.00 | 744.00 |
June | 82.19 | 41.77 | 40.42 | 142.35 | 33.13 | 8.17 | 0.00 | 720.00 |
July | 79.72 | 40.42 | 39.30 | 140.38 | 29.60 | 1.83 | 0.00 | 744.00 |
August | 75.94 | 37.29 | 38.65 | 132.24 | 30.52 | 3.50 | 0.00 | 744.00 |
September | 68.17 | 32.69 | 35.48 | 117.56 | 35.45 | 21.00 | 0.00 | 720.00 |
October | 57.39 | 26.96 | 30.43 | 95.44 | 43.16 | 31.17 | 0.00 | 744.00 |
November | 45.62 | 19.97 | 25.65 | 69.79 | 56.54 | 0.00 | 0.00 | 720.00 |
December | 37.40 | 14.55 | 22.85 | 51.93 | 62.04 | 4.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.96 | 28.61 | 33.34 | 102.32 | 44.68 | 76.33 | 0.00 | 8760.00 |
Minimum of Months | 37.40 | 14.55 | 22.85 | 51.93 | 29.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.19 | 41.77 | 40.54 | 142.35 | 62.04 | 31.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.25 | 15.45 | 24.81 | 58.75 | 55.80 | 3.50 | 0.00 | 744.00 |
February | 48.80 | 19.95 | 28.84 | 73.12 | 54.49 | 0.00 | 0.00 | 672.00 |
March | 58.97 | 24.74 | 34.23 | 92.46 | 53.51 | 0.00 | 0.00 | 744.00 |
April | 69.49 | 30.78 | 38.71 | 115.49 | 48.10 | 1.17 | 0.00 | 720.00 |
May | 78.85 | 38.31 | 40.54 | 136.65 | 34.56 | 2.00 | 0.00 | 744.00 |
June | 82.19 | 41.77 | 40.42 | 142.35 | 33.13 | 8.17 | 0.00 | 720.00 |
July | 79.72 | 40.42 | 39.30 | 140.38 | 29.60 | 1.83 | 0.00 | 744.00 |
August | 75.94 | 37.29 | 38.65 | 132.24 | 30.52 | 3.50 | 0.00 | 744.00 |
September | 68.17 | 32.69 | 35.48 | 117.56 | 35.45 | 21.00 | 0.00 | 720.00 |
October | 57.39 | 26.96 | 30.43 | 95.44 | 43.16 | 31.17 | 0.00 | 744.00 |
November | 45.62 | 19.97 | 25.65 | 69.79 | 56.54 | 0.00 | 0.00 | 720.00 |
December | 37.40 | 14.55 | 22.85 | 51.93 | 62.04 | 4.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.96 | 28.61 | 33.34 | 102.32 | 44.68 | 76.33 | 0.00 | 8760.00 |
Minimum of Months | 37.40 | 14.55 | 22.85 | 51.93 | 29.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.19 | 41.77 | 40.54 | 142.35 | 62.04 | 31.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.25 | 15.45 | 24.81 | 58.75 | 55.80 | 3.50 | 0.00 | 744.00 |
February | 48.80 | 19.95 | 28.84 | 73.12 | 54.49 | 0.00 | 0.00 | 672.00 |
March | 58.97 | 24.74 | 34.23 | 92.46 | 53.51 | 0.00 | 0.00 | 744.00 |
April | 69.49 | 30.78 | 38.71 | 115.49 | 48.10 | 1.17 | 0.00 | 720.00 |
May | 78.85 | 38.31 | 40.54 | 136.65 | 34.56 | 2.00 | 0.00 | 744.00 |
June | 82.19 | 41.77 | 40.42 | 142.35 | 33.13 | 8.17 | 0.00 | 720.00 |
July | 79.72 | 40.42 | 39.30 | 140.38 | 29.60 | 1.83 | 0.00 | 744.00 |
August | 75.94 | 37.29 | 38.65 | 132.24 | 30.52 | 3.50 | 0.00 | 744.00 |
September | 68.17 | 32.69 | 35.48 | 117.56 | 35.45 | 21.00 | 0.00 | 720.00 |
October | 57.39 | 26.96 | 30.43 | 95.44 | 43.16 | 31.17 | 0.00 | 744.00 |
November | 45.62 | 19.97 | 25.65 | 69.79 | 56.54 | 0.00 | 0.00 | 720.00 |
December | 37.40 | 14.55 | 22.85 | 51.93 | 62.04 | 4.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.96 | 28.61 | 33.34 | 102.32 | 44.68 | 76.33 | 0.00 | 8760.00 |
Minimum of Months | 37.40 | 14.55 | 22.85 | 51.93 | 29.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.19 | 41.77 | 40.54 | 142.35 | 62.04 | 31.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.25 | 15.45 | 24.81 | 58.75 | 55.80 | 3.50 | 0.00 | 744.00 |
February | 48.80 | 19.95 | 28.84 | 73.12 | 54.49 | 0.00 | 0.00 | 672.00 |
March | 58.97 | 24.74 | 34.23 | 92.46 | 53.51 | 0.00 | 0.00 | 744.00 |
April | 69.49 | 30.78 | 38.71 | 115.49 | 48.10 | 1.17 | 0.00 | 720.00 |
May | 78.85 | 38.31 | 40.54 | 136.65 | 34.56 | 2.00 | 0.00 | 744.00 |
June | 82.19 | 41.77 | 40.42 | 142.35 | 33.13 | 8.17 | 0.00 | 720.00 |
July | 79.72 | 40.42 | 39.30 | 140.38 | 29.60 | 1.83 | 0.00 | 744.00 |
August | 75.94 | 37.29 | 38.65 | 132.24 | 30.52 | 3.50 | 0.00 | 744.00 |
September | 68.17 | 32.69 | 35.48 | 117.56 | 35.45 | 21.00 | 0.00 | 720.00 |
October | 57.39 | 26.96 | 30.43 | 95.44 | 43.16 | 31.17 | 0.00 | 744.00 |
November | 45.62 | 19.97 | 25.65 | 69.79 | 56.54 | 0.00 | 0.00 | 720.00 |
December | 37.40 | 14.55 | 22.85 | 51.93 | 62.04 | 4.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.96 | 28.61 | 33.34 | 102.32 | 44.68 | 76.33 | 0.00 | 8760.00 |
Minimum of Months | 37.40 | 14.55 | 22.85 | 51.93 | 29.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.19 | 41.77 | 40.54 | 142.35 | 62.04 | 31.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.25 | 15.45 | 24.81 | 58.75 | 55.80 | 3.50 | 0.00 | 744.00 |
February | 48.80 | 19.95 | 28.84 | 73.12 | 54.49 | 0.00 | 0.00 | 672.00 |
March | 58.97 | 24.74 | 34.23 | 92.46 | 53.51 | 0.00 | 0.00 | 744.00 |
April | 69.49 | 30.78 | 38.71 | 115.49 | 48.10 | 1.17 | 0.00 | 720.00 |
May | 78.85 | 38.31 | 40.54 | 136.65 | 34.56 | 2.00 | 0.00 | 744.00 |
June | 82.19 | 41.77 | 40.42 | 142.35 | 33.13 | 8.17 | 0.00 | 720.00 |
July | 79.72 | 40.42 | 39.30 | 140.38 | 29.60 | 1.83 | 0.00 | 744.00 |
August | 75.94 | 37.29 | 38.65 | 132.24 | 30.52 | 3.50 | 0.00 | 744.00 |
September | 68.17 | 32.69 | 35.48 | 117.56 | 35.45 | 21.00 | 0.00 | 720.00 |
October | 57.39 | 26.96 | 30.43 | 95.44 | 43.16 | 31.17 | 0.00 | 744.00 |
November | 45.62 | 19.97 | 25.65 | 69.79 | 56.54 | 0.00 | 0.00 | 720.00 |
December | 37.40 | 14.55 | 22.85 | 51.93 | 62.04 | 4.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.96 | 28.61 | 33.34 | 102.32 | 44.68 | 76.33 | 0.00 | 8760.00 |
Minimum of Months | 37.40 | 14.55 | 22.85 | 51.93 | 29.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.19 | 41.77 | 40.54 | 142.35 | 62.04 | 31.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.25 | 15.45 | 24.81 | 58.75 | 55.80 | 3.50 | 0.00 | 744.00 |
February | 48.80 | 19.95 | 28.84 | 73.12 | 54.49 | 0.00 | 0.00 | 672.00 |
March | 58.97 | 24.74 | 34.23 | 92.46 | 53.51 | 0.00 | 0.00 | 744.00 |
April | 69.49 | 30.78 | 38.71 | 115.49 | 48.10 | 1.17 | 0.00 | 720.00 |
May | 78.85 | 38.31 | 40.54 | 136.65 | 34.56 | 2.00 | 0.00 | 744.00 |
June | 82.19 | 41.77 | 40.42 | 142.35 | 33.13 | 8.17 | 0.00 | 720.00 |
July | 79.72 | 40.42 | 39.30 | 140.38 | 29.60 | 1.83 | 0.00 | 744.00 |
August | 75.94 | 37.29 | 38.65 | 132.24 | 30.52 | 3.50 | 0.00 | 744.00 |
September | 68.17 | 32.69 | 35.48 | 117.56 | 35.45 | 21.00 | 0.00 | 720.00 |
October | 57.39 | 26.96 | 30.43 | 95.44 | 43.16 | 31.17 | 0.00 | 744.00 |
November | 45.62 | 19.97 | 25.65 | 69.79 | 56.54 | 0.00 | 0.00 | 720.00 |
December | 37.40 | 14.55 | 22.85 | 51.93 | 62.04 | 4.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.96 | 28.61 | 33.34 | 102.32 | 44.68 | 76.33 | 0.00 | 8760.00 |
Minimum of Months | 37.40 | 14.55 | 22.85 | 51.93 | 29.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.19 | 41.77 | 40.54 | 142.35 | 62.04 | 31.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.25 | 15.45 | 24.81 | 58.75 | 55.80 | 3.50 | 0.00 | 744.00 |
February | 48.80 | 19.95 | 28.84 | 73.12 | 54.49 | 0.00 | 0.00 | 672.00 |
March | 58.97 | 24.74 | 34.23 | 92.46 | 53.51 | 0.00 | 0.00 | 744.00 |
April | 69.49 | 30.78 | 38.71 | 115.49 | 48.10 | 1.17 | 0.00 | 720.00 |
May | 78.85 | 38.31 | 40.54 | 136.65 | 34.56 | 2.00 | 0.00 | 744.00 |
June | 82.19 | 41.77 | 40.42 | 142.35 | 33.13 | 8.17 | 0.00 | 720.00 |
July | 79.72 | 40.42 | 39.30 | 140.38 | 29.60 | 1.83 | 0.00 | 744.00 |
August | 75.94 | 37.29 | 38.65 | 132.24 | 30.52 | 3.50 | 0.00 | 744.00 |
September | 68.17 | 32.69 | 35.48 | 117.56 | 35.45 | 21.00 | 0.00 | 720.00 |
October | 57.39 | 26.96 | 30.43 | 95.44 | 43.16 | 31.17 | 0.00 | 744.00 |
November | 45.62 | 19.97 | 25.65 | 69.79 | 56.54 | 0.00 | 0.00 | 720.00 |
December | 37.40 | 14.55 | 22.85 | 51.93 | 62.04 | 4.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.96 | 28.61 | 33.34 | 102.32 | 44.68 | 76.33 | 0.00 | 8760.00 |
Minimum of Months | 37.40 | 14.55 | 22.85 | 51.93 | 29.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.19 | 41.77 | 40.54 | 142.35 | 62.04 | 31.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.25 | 15.45 | 24.81 | 58.75 | 55.80 | 3.50 | 0.00 | 744.00 |
February | 48.80 | 19.95 | 28.84 | 73.12 | 54.49 | 0.00 | 0.00 | 672.00 |
March | 58.97 | 24.74 | 34.23 | 92.46 | 53.51 | 0.00 | 0.00 | 744.00 |
April | 69.49 | 30.78 | 38.71 | 115.49 | 48.10 | 1.17 | 0.00 | 720.00 |
May | 78.85 | 38.31 | 40.54 | 136.65 | 34.56 | 2.00 | 0.00 | 744.00 |
June | 82.19 | 41.77 | 40.42 | 142.35 | 33.13 | 8.17 | 0.00 | 720.00 |
July | 79.72 | 40.42 | 39.30 | 140.38 | 29.60 | 1.83 | 0.00 | 744.00 |
August | 75.94 | 37.29 | 38.65 | 132.24 | 30.52 | 3.50 | 0.00 | 744.00 |
September | 68.17 | 32.69 | 35.48 | 117.56 | 35.45 | 21.00 | 0.00 | 720.00 |
October | 57.39 | 26.96 | 30.43 | 95.44 | 43.16 | 31.17 | 0.00 | 744.00 |
November | 45.62 | 19.97 | 25.65 | 69.79 | 56.54 | 0.00 | 0.00 | 720.00 |
December | 37.40 | 14.55 | 22.85 | 51.93 | 62.04 | 4.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.96 | 28.61 | 33.34 | 102.32 | 44.68 | 76.33 | 0.00 | 8760.00 |
Minimum of Months | 37.40 | 14.55 | 22.85 | 51.93 | 29.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.19 | 41.77 | 40.54 | 142.35 | 62.04 | 31.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.25 | 15.45 | 24.81 | 58.75 | 55.80 | 3.50 | 0.00 | 744.00 |
February | 48.80 | 19.95 | 28.84 | 73.12 | 54.49 | 0.00 | 0.00 | 672.00 |
March | 58.97 | 24.74 | 34.23 | 92.46 | 53.51 | 0.00 | 0.00 | 744.00 |
April | 69.49 | 30.78 | 38.71 | 115.49 | 48.10 | 1.17 | 0.00 | 720.00 |
May | 78.85 | 38.31 | 40.54 | 136.65 | 34.56 | 2.00 | 0.00 | 744.00 |
June | 82.19 | 41.77 | 40.42 | 142.35 | 33.13 | 8.17 | 0.00 | 720.00 |
July | 79.72 | 40.42 | 39.30 | 140.38 | 29.60 | 1.83 | 0.00 | 744.00 |
August | 75.94 | 37.29 | 38.65 | 132.24 | 30.52 | 3.50 | 0.00 | 744.00 |
September | 68.17 | 32.69 | 35.48 | 117.56 | 35.45 | 21.00 | 0.00 | 720.00 |
October | 57.39 | 26.96 | 30.43 | 95.44 | 43.16 | 31.17 | 0.00 | 744.00 |
November | 45.62 | 19.97 | 25.65 | 69.79 | 56.54 | 0.00 | 0.00 | 720.00 |
December | 37.40 | 14.55 | 22.85 | 51.93 | 62.04 | 4.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.96 | 28.61 | 33.34 | 102.32 | 44.68 | 76.33 | 0.00 | 8760.00 |
Minimum of Months | 37.40 | 14.55 | 22.85 | 51.93 | 29.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 82.19 | 41.77 | 40.54 | 142.35 | 62.04 | 31.17 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114575E+09 | 33179113.69 | 81395552.52 | 0.216291E+09 | 0.308434E+09 |
February | 0.117986E+09 | 33949881.44 | 84035784.78 | 0.253311E+09 | 0.244606E+09 |
March | 0.154131E+09 | 45669996.63 | 0.108461E+09 | 0.394658E+09 | 0.217193E+09 |
April | 0.162394E+09 | 45253894.09 | 0.117140E+09 | 0.503182E+09 | 0.148729E+09 |
May | 0.182938E+09 | 54607052.75 | 0.128331E+09 | 0.710642E+09 | 56183594.10 |
June | 0.183273E+09 | 57879065.84 | 0.125393E+09 | 0.754599E+09 | 24372927.20 |
July | 0.174120E+09 | 50098162.79 | 0.124022E+09 | 0.830366E+09 | 3649260.70 |
August | 0.177703E+09 | 53737567.12 | 0.123966E+09 | 0.851421E+09 | 2474531.25 |
September | 0.163873E+09 | 51409043.10 | 0.112464E+09 | 0.666510E+09 | 32642599.46 |
October | 0.150669E+09 | 48679733.69 | 0.101989E+09 | 0.526446E+09 | 93442379.23 |
November | 0.125683E+09 | 41286177.73 | 84396591.08 | 0.355373E+09 | 0.184100E+09 |
December | 0.108915E+09 | 33287399.47 | 75627364.87 | 0.229976E+09 | 0.283362E+09 |
Annual Sum or Average | 0.181626E+10 | 0.549037E+09 | 0.126722E+10 | 0.629277E+10 | 0.159919E+10 |
Minimum of Months | 0.108915E+09 | 33179113.69 | 75627364.87 | 0.216291E+09 | 2474531.25 |
Maximum of Months | 0.183273E+09 | 57879065.84 | 0.128331E+09 | 0.851421E+09 | 0.308434E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114575E+09 | 33179113.69 | 81395552.52 | 0.216291E+09 | 0.308434E+09 |
February | 0.117986E+09 | 33949881.44 | 84035784.78 | 0.253311E+09 | 0.244606E+09 |
March | 0.154131E+09 | 45669996.63 | 0.108461E+09 | 0.394658E+09 | 0.217193E+09 |
April | 0.162394E+09 | 45253894.09 | 0.117140E+09 | 0.503182E+09 | 0.148729E+09 |
May | 0.182938E+09 | 54607052.75 | 0.128331E+09 | 0.710642E+09 | 56183594.10 |
June | 0.183273E+09 | 57879065.84 | 0.125393E+09 | 0.754599E+09 | 24372927.20 |
July | 0.174120E+09 | 50098162.79 | 0.124022E+09 | 0.830366E+09 | 3649260.70 |
August | 0.177703E+09 | 53737567.12 | 0.123966E+09 | 0.851421E+09 | 2474531.25 |
September | 0.163873E+09 | 51409043.10 | 0.112464E+09 | 0.666510E+09 | 32642599.46 |
October | 0.150669E+09 | 48679733.69 | 0.101989E+09 | 0.526446E+09 | 93442379.23 |
November | 0.125683E+09 | 41286177.73 | 84396591.08 | 0.355373E+09 | 0.184100E+09 |
December | 0.108915E+09 | 33287399.47 | 75627364.87 | 0.229976E+09 | 0.283362E+09 |
Annual Sum or Average | 0.181626E+10 | 0.549037E+09 | 0.126722E+10 | 0.629277E+10 | 0.159919E+10 |
Minimum of Months | 0.108915E+09 | 33179113.69 | 75627364.87 | 0.216291E+09 | 2474531.25 |
Maximum of Months | 0.183273E+09 | 57879065.84 | 0.128331E+09 | 0.851421E+09 | 0.308434E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37447190.06 | 0.00 | 37447190.06 | 47642797.94 | 0.183849E+09 |
February | 38771160.50 | 0.00 | 38771160.50 | 64655314.23 | 0.146113E+09 |
March | 49317108.11 | 4220.58 | 49312887.53 | 0.113614E+09 | 0.128087E+09 |
April | 53944514.41 | 251104.59 | 53693409.82 | 0.172556E+09 | 85731065.99 |
May | 63470648.29 | 2762554.17 | 60708094.12 | 0.281263E+09 | 30862867.78 |
June | 65945518.42 | 4778059.02 | 61167459.39 | 0.314330E+09 | 14400966.57 |
July | 62180791.15 | 2501244.32 | 59679546.83 | 0.364861E+09 | 2186125.75 |
August | 57654044.63 | 921352.80 | 56732691.83 | 0.357508E+09 | 1206077.39 |
September | 50433376.11 | 23185.52 | 50410190.59 | 0.252183E+09 | 18438687.11 |
October | 46178622.83 | 0.00 | 46178622.83 | 0.181130E+09 | 53877344.23 |
November | 38364536.89 | 0.00 | 38364536.89 | 0.103774E+09 | 0.107142E+09 |
December | 34952106.77 | 0.00 | 34952106.77 | 53772660.68 | 0.168501E+09 |
Annual Sum or Average | 0.598660E+09 | 11241721.00 | 0.587418E+09 | 0.230729E+10 | 0.940395E+09 |
Minimum of Months | 34952106.77 | 0.00 | 34952106.77 | 47642797.94 | 1206077.39 |
Maximum of Months | 65945518.42 | 4778059.02 | 61167459.39 | 0.364861E+09 | 0.183849E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37445961.09 | 0.00 | 37445961.09 | 47640739.06 | 0.183847E+09 |
February | 38769911.79 | 0.00 | 38769911.79 | 64653106.21 | 0.146111E+09 |
March | 49315544.25 | 4220.38 | 49311323.86 | 0.113611E+09 | 0.128085E+09 |
April | 53942836.16 | 251092.82 | 53691743.34 | 0.172553E+09 | 85729371.51 |
May | 63468659.53 | 2762424.68 | 60706234.84 | 0.281259E+09 | 30861663.01 |
June | 65943419.39 | 4777835.07 | 61165584.32 | 0.314326E+09 | 14400075.59 |
July | 62178868.18 | 2501127.08 | 59677741.09 | 0.364859E+09 | 2185862.61 |
August | 57652292.29 | 921309.62 | 56730982.67 | 0.357506E+09 | 1205900.78 |
September | 50431845.07 | 23184.43 | 50408660.64 | 0.252181E+09 | 18437725.39 |
October | 46177190.70 | 0.00 | 46177190.70 | 0.181128E+09 | 53875543.49 |
November | 38363313.08 | 0.00 | 38363313.08 | 0.103772E+09 | 0.107140E+09 |
December | 34950959.33 | 0.00 | 34950959.33 | 53770734.85 | 0.168499E+09 |
Annual Sum or Average | 0.598641E+09 | 11241194.08 | 0.587400E+09 | 0.230726E+10 | 0.940380E+09 |
Minimum of Months | 34950959.33 | 0.00 | 34950959.33 | 47640739.06 | 1205900.78 |
Maximum of Months | 65943419.39 | 4777835.07 | 61165584.32 | 0.364859E+09 | 0.183847E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107819E+09 | 41369860.16 | 66448936.37 | 0.157362E+09 | 0.149446E+09 |
February | 0.118046E+09 | 48269844.49 | 69776341.61 | 0.176891E+09 | 0.131830E+09 |
March | 0.157941E+09 | 66265555.59 | 91675596.32 | 0.247650E+09 | 0.143319E+09 |
April | 0.180125E+09 | 79782118.56 | 0.100343E+09 | 0.299360E+09 | 0.124680E+09 |
May | 0.211189E+09 | 0.102618E+09 | 0.108571E+09 | 0.366001E+09 | 92562054.67 |
June | 0.213033E+09 | 0.108266E+09 | 0.104768E+09 | 0.368969E+09 | 85882849.55 |
July | 0.213525E+09 | 0.108252E+09 | 0.105273E+09 | 0.375982E+09 | 79275612.75 |
August | 0.203396E+09 | 99868562.69 | 0.103527E+09 | 0.354190E+09 | 81753936.02 |
September | 0.176693E+09 | 84731425.41 | 91961203.47 | 0.304727E+09 | 91881980.12 |
October | 0.153711E+09 | 72201907.61 | 81509074.62 | 0.255635E+09 | 0.115613E+09 |
November | 0.118258E+09 | 51765167.39 | 66492744.63 | 0.180900E+09 | 0.146545E+09 |
December | 0.100176E+09 | 38968866.36 | 61206902.60 | 0.139085E+09 | 0.166181E+09 |
Annual Sum or Average | 0.195391E+10 | 0.902359E+09 | 0.105155E+10 | 0.322675E+10 | 0.140897E+10 |
Minimum of Months | 0.100176E+09 | 38968866.36 | 61206902.60 | 0.139085E+09 | 79275612.75 |
Maximum of Months | 0.213525E+09 | 0.108266E+09 | 0.108571E+09 | 0.375982E+09 | 0.166181E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107819E+09 | 41369860.16 | 66448936.37 | 0.157362E+09 | 0.149446E+09 |
February | 0.118046E+09 | 48269844.49 | 69776341.61 | 0.176891E+09 | 0.131830E+09 |
March | 0.157941E+09 | 66265555.59 | 91675596.32 | 0.247650E+09 | 0.143319E+09 |
April | 0.180125E+09 | 79782118.56 | 0.100343E+09 | 0.299360E+09 | 0.124680E+09 |
May | 0.211189E+09 | 0.102618E+09 | 0.108571E+09 | 0.366001E+09 | 92562054.67 |
June | 0.213033E+09 | 0.108266E+09 | 0.104768E+09 | 0.368969E+09 | 85882849.55 |
July | 0.213525E+09 | 0.108252E+09 | 0.105273E+09 | 0.375982E+09 | 79275612.75 |
August | 0.203396E+09 | 99868562.69 | 0.103527E+09 | 0.354190E+09 | 81753936.02 |
September | 0.176693E+09 | 84731425.41 | 91961203.47 | 0.304727E+09 | 91881980.12 |
October | 0.153711E+09 | 72201907.61 | 81509074.62 | 0.255635E+09 | 0.115613E+09 |
November | 0.118258E+09 | 51765167.39 | 66492744.63 | 0.180900E+09 | 0.146545E+09 |
December | 0.100176E+09 | 38968866.36 | 61206902.60 | 0.139085E+09 | 0.166181E+09 |
Annual Sum or Average | 0.195391E+10 | 0.902359E+09 | 0.105155E+10 | 0.322675E+10 | 0.140897E+10 |
Minimum of Months | 0.100176E+09 | 38968866.36 | 61206902.60 | 0.139085E+09 | 79275612.75 |
Maximum of Months | 0.213525E+09 | 0.108266E+09 | 0.108571E+09 | 0.375982E+09 | 0.166181E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107819E+09 | 41369860.16 | 66448936.37 | 0.157362E+09 | 0.149446E+09 |
February | 0.118046E+09 | 48269844.49 | 69776341.61 | 0.176891E+09 | 0.131830E+09 |
March | 0.157941E+09 | 66265555.59 | 91675596.32 | 0.247650E+09 | 0.143319E+09 |
April | 0.180125E+09 | 79782118.56 | 0.100343E+09 | 0.299360E+09 | 0.124680E+09 |
May | 0.211189E+09 | 0.102618E+09 | 0.108571E+09 | 0.366001E+09 | 92562054.67 |
June | 0.213033E+09 | 0.108266E+09 | 0.104768E+09 | 0.368969E+09 | 85882849.55 |
July | 0.213525E+09 | 0.108252E+09 | 0.105273E+09 | 0.375982E+09 | 79275612.75 |
August | 0.203396E+09 | 99868562.69 | 0.103527E+09 | 0.354190E+09 | 81753936.02 |
September | 0.176693E+09 | 84731425.41 | 91961203.47 | 0.304727E+09 | 91881980.12 |
October | 0.153711E+09 | 72201907.61 | 81509074.62 | 0.255635E+09 | 0.115613E+09 |
November | 0.118258E+09 | 51765167.39 | 66492744.63 | 0.180900E+09 | 0.146545E+09 |
December | 0.100176E+09 | 38968866.36 | 61206902.60 | 0.139085E+09 | 0.166181E+09 |
Annual Sum or Average | 0.195391E+10 | 0.902359E+09 | 0.105155E+10 | 0.322675E+10 | 0.140897E+10 |
Minimum of Months | 0.100176E+09 | 38968866.36 | 61206902.60 | 0.139085E+09 | 79275612.75 |
Maximum of Months | 0.213525E+09 | 0.108266E+09 | 0.108571E+09 | 0.375982E+09 | 0.166181E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107819E+09 | 41369860.16 | 66448936.37 | 0.157362E+09 | 0.149446E+09 |
February | 0.118046E+09 | 48269844.49 | 69776341.61 | 0.176891E+09 | 0.131830E+09 |
March | 0.157941E+09 | 66265555.59 | 91675596.32 | 0.247650E+09 | 0.143319E+09 |
April | 0.180125E+09 | 79782118.56 | 0.100343E+09 | 0.299360E+09 | 0.124680E+09 |
May | 0.211189E+09 | 0.102618E+09 | 0.108571E+09 | 0.366001E+09 | 92562054.67 |
June | 0.213033E+09 | 0.108266E+09 | 0.104768E+09 | 0.368969E+09 | 85882849.55 |
July | 0.213525E+09 | 0.108252E+09 | 0.105273E+09 | 0.375982E+09 | 79275612.75 |
August | 0.203396E+09 | 99868562.69 | 0.103527E+09 | 0.354190E+09 | 81753936.02 |
September | 0.176693E+09 | 84731425.41 | 91961203.47 | 0.304727E+09 | 91881980.12 |
October | 0.153711E+09 | 72201907.61 | 81509074.62 | 0.255635E+09 | 0.115613E+09 |
November | 0.118258E+09 | 51765167.39 | 66492744.63 | 0.180900E+09 | 0.146545E+09 |
December | 0.100176E+09 | 38968866.36 | 61206902.60 | 0.139085E+09 | 0.166181E+09 |
Annual Sum or Average | 0.195391E+10 | 0.902359E+09 | 0.105155E+10 | 0.322675E+10 | 0.140897E+10 |
Minimum of Months | 0.100176E+09 | 38968866.36 | 61206902.60 | 0.139085E+09 | 79275612.75 |
Maximum of Months | 0.213525E+09 | 0.108266E+09 | 0.108571E+09 | 0.375982E+09 | 0.166181E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107819E+09 | 41369860.16 | 66448936.37 | 0.157362E+09 | 0.149446E+09 |
February | 0.118046E+09 | 48269844.49 | 69776341.61 | 0.176891E+09 | 0.131830E+09 |
March | 0.157941E+09 | 66265555.59 | 91675596.32 | 0.247650E+09 | 0.143319E+09 |
April | 0.180125E+09 | 79782118.56 | 0.100343E+09 | 0.299360E+09 | 0.124680E+09 |
May | 0.211189E+09 | 0.102618E+09 | 0.108571E+09 | 0.366001E+09 | 92562054.67 |
June | 0.213033E+09 | 0.108266E+09 | 0.104768E+09 | 0.368969E+09 | 85882849.55 |
July | 0.213525E+09 | 0.108252E+09 | 0.105273E+09 | 0.375982E+09 | 79275612.75 |
August | 0.203396E+09 | 99868562.69 | 0.103527E+09 | 0.354190E+09 | 81753936.02 |
September | 0.176693E+09 | 84731425.41 | 91961203.47 | 0.304727E+09 | 91881980.12 |
October | 0.153711E+09 | 72201907.61 | 81509074.62 | 0.255635E+09 | 0.115613E+09 |
November | 0.118258E+09 | 51765167.39 | 66492744.63 | 0.180900E+09 | 0.146545E+09 |
December | 0.100176E+09 | 38968866.36 | 61206902.60 | 0.139085E+09 | 0.166181E+09 |
Annual Sum or Average | 0.195391E+10 | 0.902359E+09 | 0.105155E+10 | 0.322675E+10 | 0.140897E+10 |
Minimum of Months | 0.100176E+09 | 38968866.36 | 61206902.60 | 0.139085E+09 | 79275612.75 |
Maximum of Months | 0.213525E+09 | 0.108266E+09 | 0.108571E+09 | 0.375982E+09 | 0.166181E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107819E+09 | 41369860.16 | 66448936.37 | 0.157362E+09 | 0.149446E+09 |
February | 0.118046E+09 | 48269844.49 | 69776341.61 | 0.176891E+09 | 0.131830E+09 |
March | 0.157941E+09 | 66265555.59 | 91675596.32 | 0.247650E+09 | 0.143319E+09 |
April | 0.180125E+09 | 79782118.56 | 0.100343E+09 | 0.299360E+09 | 0.124680E+09 |
May | 0.211189E+09 | 0.102618E+09 | 0.108571E+09 | 0.366001E+09 | 92562054.67 |
June | 0.213033E+09 | 0.108266E+09 | 0.104768E+09 | 0.368969E+09 | 85882849.55 |
July | 0.213525E+09 | 0.108252E+09 | 0.105273E+09 | 0.375982E+09 | 79275612.75 |
August | 0.203396E+09 | 99868562.69 | 0.103527E+09 | 0.354190E+09 | 81753936.02 |
September | 0.176693E+09 | 84731425.41 | 91961203.47 | 0.304727E+09 | 91881980.12 |
October | 0.153711E+09 | 72201907.61 | 81509074.62 | 0.255635E+09 | 0.115613E+09 |
November | 0.118258E+09 | 51765167.39 | 66492744.63 | 0.180900E+09 | 0.146545E+09 |
December | 0.100176E+09 | 38968866.36 | 61206902.60 | 0.139085E+09 | 0.166181E+09 |
Annual Sum or Average | 0.195391E+10 | 0.902359E+09 | 0.105155E+10 | 0.322675E+10 | 0.140897E+10 |
Minimum of Months | 0.100176E+09 | 38968866.36 | 61206902.60 | 0.139085E+09 | 79275612.75 |
Maximum of Months | 0.213525E+09 | 0.108266E+09 | 0.108571E+09 | 0.375982E+09 | 0.166181E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107819E+09 | 41369860.16 | 66448936.37 | 0.157362E+09 | 0.149446E+09 |
February | 0.118046E+09 | 48269844.49 | 69776341.61 | 0.176891E+09 | 0.131830E+09 |
March | 0.157941E+09 | 66265555.59 | 91675596.32 | 0.247650E+09 | 0.143319E+09 |
April | 0.180125E+09 | 79782118.56 | 0.100343E+09 | 0.299360E+09 | 0.124680E+09 |
May | 0.211189E+09 | 0.102618E+09 | 0.108571E+09 | 0.366001E+09 | 92562054.67 |
June | 0.213033E+09 | 0.108266E+09 | 0.104768E+09 | 0.368969E+09 | 85882849.55 |
July | 0.213525E+09 | 0.108252E+09 | 0.105273E+09 | 0.375982E+09 | 79275612.75 |
August | 0.203396E+09 | 99868562.69 | 0.103527E+09 | 0.354190E+09 | 81753936.02 |
September | 0.176693E+09 | 84731425.41 | 91961203.47 | 0.304727E+09 | 91881980.12 |
October | 0.153711E+09 | 72201907.61 | 81509074.62 | 0.255635E+09 | 0.115613E+09 |
November | 0.118258E+09 | 51765167.39 | 66492744.63 | 0.180900E+09 | 0.146545E+09 |
December | 0.100176E+09 | 38968866.36 | 61206902.60 | 0.139085E+09 | 0.166181E+09 |
Annual Sum or Average | 0.195391E+10 | 0.902359E+09 | 0.105155E+10 | 0.322675E+10 | 0.140897E+10 |
Minimum of Months | 0.100176E+09 | 38968866.36 | 61206902.60 | 0.139085E+09 | 79275612.75 |
Maximum of Months | 0.213525E+09 | 0.108266E+09 | 0.108571E+09 | 0.375982E+09 | 0.166181E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107819E+09 | 41369860.16 | 66448936.37 | 0.157362E+09 | 0.149446E+09 |
February | 0.118046E+09 | 48269844.49 | 69776341.61 | 0.176891E+09 | 0.131830E+09 |
March | 0.157941E+09 | 66265555.59 | 91675596.32 | 0.247650E+09 | 0.143319E+09 |
April | 0.180125E+09 | 79782118.56 | 0.100343E+09 | 0.299360E+09 | 0.124680E+09 |
May | 0.211189E+09 | 0.102618E+09 | 0.108571E+09 | 0.366001E+09 | 92562054.67 |
June | 0.213033E+09 | 0.108266E+09 | 0.104768E+09 | 0.368969E+09 | 85882849.55 |
July | 0.213525E+09 | 0.108252E+09 | 0.105273E+09 | 0.375982E+09 | 79275612.75 |
August | 0.203396E+09 | 99868562.69 | 0.103527E+09 | 0.354190E+09 | 81753936.02 |
September | 0.176693E+09 | 84731425.41 | 91961203.47 | 0.304727E+09 | 91881980.12 |
October | 0.153711E+09 | 72201907.61 | 81509074.62 | 0.255635E+09 | 0.115613E+09 |
November | 0.118258E+09 | 51765167.39 | 66492744.63 | 0.180900E+09 | 0.146545E+09 |
December | 0.100176E+09 | 38968866.36 | 61206902.60 | 0.139085E+09 | 0.166181E+09 |
Annual Sum or Average | 0.195391E+10 | 0.902359E+09 | 0.105155E+10 | 0.322675E+10 | 0.140897E+10 |
Minimum of Months | 0.100176E+09 | 38968866.36 | 61206902.60 | 0.139085E+09 | 79275612.75 |
Maximum of Months | 0.213525E+09 | 0.108266E+09 | 0.108571E+09 | 0.375982E+09 | 0.166181E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107819E+09 | 41369860.16 | 66448936.37 | 0.157362E+09 | 0.149446E+09 |
February | 0.118046E+09 | 48269844.49 | 69776341.61 | 0.176891E+09 | 0.131830E+09 |
March | 0.157941E+09 | 66265555.59 | 91675596.32 | 0.247650E+09 | 0.143319E+09 |
April | 0.180125E+09 | 79782118.56 | 0.100343E+09 | 0.299360E+09 | 0.124680E+09 |
May | 0.211189E+09 | 0.102618E+09 | 0.108571E+09 | 0.366001E+09 | 92562054.67 |
June | 0.213033E+09 | 0.108266E+09 | 0.104768E+09 | 0.368969E+09 | 85882849.55 |
July | 0.213525E+09 | 0.108252E+09 | 0.105273E+09 | 0.375982E+09 | 79275612.75 |
August | 0.203396E+09 | 99868562.69 | 0.103527E+09 | 0.354190E+09 | 81753936.02 |
September | 0.176693E+09 | 84731425.41 | 91961203.47 | 0.304727E+09 | 91881980.12 |
October | 0.153711E+09 | 72201907.61 | 81509074.62 | 0.255635E+09 | 0.115613E+09 |
November | 0.118258E+09 | 51765167.39 | 66492744.63 | 0.180900E+09 | 0.146545E+09 |
December | 0.100176E+09 | 38968866.36 | 61206902.60 | 0.139085E+09 | 0.166181E+09 |
Annual Sum or Average | 0.195391E+10 | 0.902359E+09 | 0.105155E+10 | 0.322675E+10 | 0.140897E+10 |
Minimum of Months | 0.100176E+09 | 38968866.36 | 61206902.60 | 0.139085E+09 | 79275612.75 |
Maximum of Months | 0.213525E+09 | 0.108266E+09 | 0.108571E+09 | 0.375982E+09 | 0.166181E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107819E+09 | 41369860.16 | 66448936.37 | 0.157362E+09 | 0.149446E+09 |
February | 0.118046E+09 | 48269844.49 | 69776341.61 | 0.176891E+09 | 0.131830E+09 |
March | 0.157941E+09 | 66265555.59 | 91675596.32 | 0.247650E+09 | 0.143319E+09 |
April | 0.180125E+09 | 79782118.56 | 0.100343E+09 | 0.299360E+09 | 0.124680E+09 |
May | 0.211189E+09 | 0.102618E+09 | 0.108571E+09 | 0.366001E+09 | 92562054.67 |
June | 0.213033E+09 | 0.108266E+09 | 0.104768E+09 | 0.368969E+09 | 85882849.55 |
July | 0.213525E+09 | 0.108252E+09 | 0.105273E+09 | 0.375982E+09 | 79275612.75 |
August | 0.203396E+09 | 99868562.69 | 0.103527E+09 | 0.354190E+09 | 81753936.02 |
September | 0.176693E+09 | 84731425.41 | 91961203.47 | 0.304727E+09 | 91881980.12 |
October | 0.153711E+09 | 72201907.61 | 81509074.62 | 0.255635E+09 | 0.115613E+09 |
November | 0.118258E+09 | 51765167.39 | 66492744.63 | 0.180900E+09 | 0.146545E+09 |
December | 0.100176E+09 | 38968866.36 | 61206902.60 | 0.139085E+09 | 0.166181E+09 |
Annual Sum or Average | 0.195391E+10 | 0.902359E+09 | 0.105155E+10 | 0.322675E+10 | 0.140897E+10 |
Minimum of Months | 0.100176E+09 | 38968866.36 | 61206902.60 | 0.139085E+09 | 79275612.75 |
Maximum of Months | 0.213525E+09 | 0.108266E+09 | 0.108571E+09 | 0.375982E+09 | 0.166181E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 192.99 | 363.50 | 113.52 | 24.78 | 88.74 | 0.00 | 0.00 |
February | 259.97 | 320.12 | 129.59 | 28.07 | 101.53 | 0.00 | 0.00 |
March | 377.88 | 256.17 | 151.92 | 34.11 | 117.81 | 0.00 | 0.00 |
April | 521.05 | 180.56 | 166.93 | 35.11 | 131.82 | 0.00 | 0.00 |
May | 740.23 | 64.56 | 184.00 | 42.84 | 141.16 | 0.00 | 0.00 |
June | 824.50 | 29.63 | 192.30 | 48.35 | 143.95 | 0.00 | 0.00 |
July | 892.43 | 4.30 | 176.45 | 39.28 | 137.17 | 0.00 | 0.00 |
August | 902.70 | 2.72 | 175.74 | 40.81 | 134.93 | 0.00 | 0.00 |
September | 708.83 | 39.37 | 165.36 | 39.69 | 125.67 | 0.00 | 0.00 |
October | 528.33 | 109.98 | 146.99 | 36.35 | 110.64 | 0.00 | 0.00 |
November | 353.86 | 224.30 | 126.58 | 31.86 | 94.72 | 0.00 | 0.00 |
December | 209.54 | 335.08 | 107.43 | 24.86 | 82.57 | 0.00 | 0.00 |
Annual Sum or Average | 544.37 | 160.01 | 153.15 | 35.53 | 117.62 | 0.00 | 0.00 |
Minimum of Months | 192.99 | 2.72 | 107.43 | 24.78 | 82.57 | 0.00 | 0.00 |
Maximum of Months | 902.70 | 363.50 | 192.30 | 48.35 | 143.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 587.52 | 557.97 | 402.55 | 154.46 | 248.09 | 0.00 | 0.00 |
February | 731.19 | 544.93 | 487.96 | 199.53 | 288.43 | 0.00 | 0.00 |
March | 924.62 | 535.09 | 589.68 | 247.41 | 342.28 | 0.00 | 0.00 |
April | 1154.93 | 481.01 | 694.93 | 307.80 | 387.12 | 0.00 | 0.00 |
May | 1366.49 | 345.58 | 788.49 | 383.13 | 405.36 | 0.00 | 0.00 |
June | 1423.49 | 331.33 | 821.89 | 417.69 | 404.20 | 0.00 | 0.00 |
July | 1403.76 | 295.98 | 797.21 | 404.17 | 393.04 | 0.00 | 0.00 |
August | 1322.39 | 305.23 | 759.39 | 372.87 | 386.53 | 0.00 | 0.00 |
September | 1175.64 | 354.48 | 681.68 | 326.90 | 354.79 | 0.00 | 0.00 |
October | 954.43 | 431.65 | 573.89 | 269.57 | 304.32 | 0.00 | 0.00 |
November | 697.91 | 565.38 | 456.24 | 199.71 | 256.53 | 0.00 | 0.00 |
December | 519.28 | 620.45 | 374.01 | 145.49 | 228.52 | 0.00 | 0.00 |
Annual Sum or Average | 1023.19 | 446.78 | 619.58 | 286.14 | 333.44 | 0.00 | 0.00 |
Minimum of Months | 519.28 | 295.98 | 374.01 | 145.49 | 228.52 | 0.00 | 0.00 |
Maximum of Months | 1423.49 | 620.45 | 821.89 | 417.69 | 405.36 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.516906E+09 | 0.973604E+09 | 0.304042E+09 | 66358227.38 | 0.237684E+09 | 0.00 | 0.00 |
February | 0.628924E+09 | 0.774427E+09 | 0.313512E+09 | 67899762.88 | 0.245613E+09 | 0.00 | 0.00 |
March | 0.101211E+10 | 0.686131E+09 | 0.406895E+09 | 91348434.22 | 0.315547E+09 | 0.00 | 0.00 |
April | 0.135057E+10 | 0.468018E+09 | 0.432675E+09 | 91009985.58 | 0.341665E+09 | 0.00 | 0.00 |
May | 0.198263E+10 | 0.172918E+09 | 0.492815E+09 | 0.114739E+09 | 0.378076E+09 | 0.00 | 0.00 |
June | 0.213710E+10 | 76792277.24 | 0.498434E+09 | 0.125314E+09 | 0.373120E+09 | 0.00 | 0.00 |
July | 0.239029E+10 | 11508248.48 | 0.472600E+09 | 0.105199E+09 | 0.367401E+09 | 0.00 | 0.00 |
August | 0.241779E+10 | 7292760.35 | 0.470713E+09 | 0.109318E+09 | 0.361395E+09 | 0.00 | 0.00 |
September | 0.183728E+10 | 0.102056E+09 | 0.428611E+09 | 0.102864E+09 | 0.325746E+09 | 0.00 | 0.00 |
October | 0.141509E+10 | 0.294578E+09 | 0.393693E+09 | 97359467.38 | 0.296334E+09 | 0.00 | 0.00 |
November | 0.917193E+09 | 0.581383E+09 | 0.328093E+09 | 82572355.45 | 0.245521E+09 | 0.00 | 0.00 |
December | 0.561243E+09 | 0.897472E+09 | 0.287733E+09 | 66574798.94 | 0.221158E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.171671E+11 | 0.504618E+10 | 0.482982E+10 | 0.112056E+10 | 0.370926E+10 | 0.00 | 0.00 |
Minimum of Months | 0.516906E+09 | 7292760.35 | 0.287733E+09 | 66358227.38 | 0.221158E+09 | 0.00 | 0.00 |
Maximum of Months | 0.241779E+10 | 0.973604E+09 | 0.498434E+09 | 0.125314E+09 | 0.378076E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.157362E+10 | 0.149446E+10 | 0.107819E+10 | 0.413699E+09 | 0.664489E+09 | 0.00 | 0.00 |
February | 0.176891E+10 | 0.131830E+10 | 0.118046E+10 | 0.482698E+09 | 0.697763E+09 | 0.00 | 0.00 |
March | 0.247650E+10 | 0.143319E+10 | 0.157941E+10 | 0.662656E+09 | 0.916756E+09 | 0.00 | 0.00 |
April | 0.299358E+10 | 0.124678E+10 | 0.180125E+10 | 0.797821E+09 | 0.100343E+10 | 0.00 | 0.00 |
May | 0.366001E+10 | 0.925603E+09 | 0.211189E+10 | 0.102618E+10 | 0.108571E+10 | 0.00 | 0.00 |
June | 0.368968E+10 | 0.858808E+09 | 0.213033E+10 | 0.108266E+10 | 0.104768E+10 | 0.00 | 0.00 |
July | 0.375982E+10 | 0.792755E+09 | 0.213525E+10 | 0.108252E+10 | 0.105273E+10 | 0.00 | 0.00 |
August | 0.354190E+10 | 0.817539E+09 | 0.203396E+10 | 0.998686E+09 | 0.103527E+10 | 0.00 | 0.00 |
September | 0.304727E+10 | 0.918816E+09 | 0.176693E+10 | 0.847314E+09 | 0.919612E+09 | 0.00 | 0.00 |
October | 0.255635E+10 | 0.115613E+10 | 0.153711E+10 | 0.722019E+09 | 0.815091E+09 | 0.00 | 0.00 |
November | 0.180900E+10 | 0.146545E+10 | 0.118258E+10 | 0.517652E+09 | 0.664927E+09 | 0.00 | 0.00 |
December | 0.139084E+10 | 0.166181E+10 | 0.100176E+10 | 0.389689E+09 | 0.612069E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.322675E+11 | 0.140896E+11 | 0.195391E+11 | 0.902359E+10 | 0.105155E+11 | 0.00 | 0.00 |
Minimum of Months | 0.139084E+10 | 0.792755E+09 | 0.100176E+10 | 0.389689E+09 | 0.612069E+09 | 0.00 | 0.00 |
Maximum of Months | 0.375982E+10 | 0.166181E+10 | 0.213525E+10 | 0.108266E+10 | 0.108571E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.73 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.25 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.73 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.16 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.89 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.77 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.47 | 23.16 | 3.85 | 24.13 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.01 | 24.10 | 3.89 | 24.32 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.67 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.65 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.61 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.83 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.01 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.73 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.01 | 24.10 | 3.95 | 24.32 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.53 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.25 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.80 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.14 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.72 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.53 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 21.97 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.35 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.39 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.78 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.12 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.02 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.53 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.35 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.44 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.73 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.73 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.04 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.94 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.23 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.43 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.81 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.81 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.94 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.20 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.04 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.10 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.85 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.13 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.23 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.13 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.20 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.10 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.85 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.09 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.85 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.682115E+09 | -608898085.7 | 0.00 | 0.00 | 744.00 | 0.00 | -73216894.4 | 58.99 | 0.00 | 0.00 |
February | 0.609140E+09 | -543788024.4 | 0.00 | 0.00 | 672.00 | 0.00 | -65351899.0 | 58.99 | 0.00 | 0.00 |
March | 0.662313E+09 | -590813935.9 | 0.00 | 0.00 | 744.00 | 0.00 | -71498873.7 | 58.99 | 0.00 | 0.00 |
April | 0.561025E+09 | -493202029.7 | 0.00 | 0.00 | 720.00 | 0.00 | -67823011.7 | 58.99 | 0.00 | 0.00 |
May | 0.525545E+09 | -456699457.7 | 0.00 | 0.00 | 744.00 | 0.00 | -68845274.6 | 58.98 | 0.00 | 0.00 |
June | 0.480312E+09 | -413934604.7 | 0.00 | 0.00 | 720.00 | 0.00 | -66377272.2 | 58.98 | 0.00 | 0.00 |
July | 0.455525E+09 | -387623170.8 | 0.00 | 0.00 | 744.00 | 0.00 | -67902265.9 | 58.99 | 0.00 | 0.00 |
August | 0.503571E+09 | -435309073.0 | 0.00 | 0.00 | 744.00 | 0.00 | -68261935.8 | 58.99 | 0.00 | 0.00 |
September | 0.514301E+09 | -448170330.2 | 0.00 | 0.00 | 720.00 | 0.00 | -66130606.6 | 58.99 | 0.00 | 0.00 |
October | 0.573856E+09 | -505175202.1 | 0.00 | 0.00 | 744.00 | 0.00 | -68681079.7 | 58.99 | 0.00 | 0.00 |
November | 0.604229E+09 | -536752895.7 | 0.00 | 0.00 | 720.00 | 0.00 | -67475715.3 | 58.99 | 0.00 | 0.00 |
December | 0.668498E+09 | -596891517.7 | 0.00 | 0.00 | 744.00 | 0.00 | -71606442.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.684043E+10 | -.601726E+10 | 8760.00 | -823171271.8 | 58.99 | |||||
Minimum of Months | 0.455525E+09 | -608898085.7 | 0.00 | 0.00 | 672.00 | 0.00 | -73216894.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.682115E+09 | -387623170.8 | 0.00 | 0.00 | 744.00 | 0.00 | -65351899.0 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 325.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 375.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 403.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 405.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 395.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 358.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 351.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 319.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4323.33 | ||||||||||
Minimum of Months | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1369097.79 | 647.13 | 02-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1369097.79 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1369097.79 | 647.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.585329E+10 | 0.496401E+10 | 31761.80 | 30-JAN-06:01 | 21440.14 | 0.00 |
February | 0.00 | 0.00 | 0.695517E+10 | 0.578665E+10 | 33054.80 | 09-FEB-06:01 | 20724.57 | 0.00 |
March | 0.00 | 0.00 | 0.978051E+10 | 0.841122E+10 | 32820.25 | 29-MAR-05:01 | 20949.24 | 0.00 |
April | 0.00 | 0.00 | 0.117081E+11 | 0.992490E+10 | 33493.81 | 10-APR-05:01 | 20511.66 | 0.00 |
May | 0.00 | 0.00 | 0.164613E+11 | 0.137441E+11 | 35117.36 | 24-MAY-05:01 | 18874.64 | 0.00 |
June | 0.00 | 0.00 | 0.196456E+11 | 0.149874E+11 | 35581.77 | 08-JUN-05:01 | 18460.96 | 0.00 |
July | 0.00 | 0.00 | 0.223064E+11 | 0.160782E+11 | 34666.18 | 06-JUL-05:01 | 16938.62 | 0.00 |
August | 0.00 | 0.00 | 0.248544E+11 | 0.176794E+11 | 34666.18 | 31-AUG-05:01 | 17510.81 | 0.00 |
September | 0.00 | 0.00 | 0.200895E+11 | 0.145833E+11 | 36016.58 | 25-SEP-05:01 | 19144.89 | 0.00 |
October | 0.00 | 0.00 | 0.163869E+11 | 0.126699E+11 | 35632.06 | 07-OCT-05:01 | 18795.45 | 0.00 |
November | 0.00 | 0.00 | 0.124006E+11 | 0.977578E+10 | 34548.50 | 03-NOV-05:01 | 20377.91 | 0.00 |
December | 0.00 | 0.00 | 0.844573E+10 | 0.689330E+10 | 32655.61 | 06-DEC-06:01 | 20431.25 | 0.00 |
Annual Sum or Average | 0.174887E+12 | 0.135498E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.585329E+10 | 0.496401E+10 | 31761.80 | 16938.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.248544E+11 | 0.176794E+11 | 36016.58 | 21440.14 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.615601E+10 | 0.509826E+10 | 22608.35 | 29-JAN-14:55 | 15413.16 | 0.00 |
February | 0.00 | 0.00 | 0.103376E+11 | 0.854899E+10 | 77695.59 | 05-FEB-14:43 | 69489.22 | 0.00 |
March | 0.00 | 0.00 | 0.194090E+11 | 0.167265E+11 | 86226.60 | 26-MAR-14:32 | 84898.03 | 0.00 |
April | 0.00 | 0.00 | 0.320315E+11 | 0.268757E+11 | 105771.89 | 30-APR-17:53 | 61877.84 | 0.00 |
May | 0.00 | 0.00 | 0.586149E+11 | 0.480730E+11 | 107247.51 | 27-MAY-05:10 | 63907.88 | 0.00 |
June | 0.00 | 0.00 | 0.756047E+11 | 0.553048E+11 | 114654.94 | 08-JUN-05:08 | 55153.36 | 0.00 |
July | 0.00 | 0.00 | 0.935997E+11 | 0.656849E+11 | 110900.12 | 06-JUL-05:01 | 55839.39 | 0.00 |
August | 0.00 | 0.00 | 0.100677E+12 | 0.694014E+11 | 111279.36 | 08-AUG-05:01 | 50433.67 | 0.00 |
September | 0.00 | 0.00 | 0.773377E+11 | 0.537788E+11 | 115262.06 | 23-SEP-05:10 | 53675.27 | 0.00 |
October | 0.00 | 0.00 | 0.544310E+11 | 0.411808E+11 | 112969.98 | 02-OCT-05:06 | 56001.90 | 0.00 |
November | 0.00 | 0.00 | 0.303972E+11 | 0.238140E+11 | 100662.50 | 01-NOV-17:06 | 65571.95 | 0.00 |
December | 0.00 | 0.00 | 0.134192E+11 | 0.107739E+11 | 66862.31 | 03-DEC-13:13 | 56122.15 | 0.00 |
Annual Sum or Average | 0.572016E+12 | 0.425261E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.615601E+10 | 0.509826E+10 | 22608.35 | 15413.16 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.100677E+12 | 0.694014E+11 | 115262.06 | 84898.03 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149140E+10 | 0.35 | 1499.98 | 02-JAN-09:00 | 0.93 |
February | 0.137771E+10 | 0.36 | 1499.98 | 01-FEB-08:20 | 0.93 |
March | 0.162602E+10 | 0.39 | 1499.98 | 02-MAR-08:00 | 0.93 |
April | 0.151742E+10 | 0.39 | 1499.98 | 01-APR-09:20 | 0.93 |
May | 0.161609E+10 | 0.43 | 1499.98 | 03-MAY-07:12 | 0.93 |
June | 0.163303E+10 | 0.44 | 1499.98 | 08-JUN-14:50 | 0.92 |
July | 0.162404E+10 | 0.48 | 1499.98 | 05-JUL-08:20 | 0.92 |
August | 0.175201E+10 | 0.51 | 1499.98 | 01-AUG-10:30 | 0.93 |
September | 0.159221E+10 | 0.45 | 1499.98 | 05-SEP-12:20 | 0.93 |
October | 0.155741E+10 | 0.41 | 1499.98 | 30-OCT-06:25 | 0.93 |
November | 0.146228E+10 | 0.37 | 1499.98 | 02-NOV-06:27 | 0.92 |
December | 0.150370E+10 | 0.36 | 1499.98 | 02-DEC-08:70 | 0.93 |
Annual Sum or Average | 0.187533E+11 | 0.41 | |||
Minimum of Months | 0.137771E+10 | 0.35 | 1499.98 | 0.92 | |
Maximum of Months | 0.175201E+10 | 0.51 | 1499.98 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.684703E+10 | 0.58 | 6913.41 | 03-JAN-11:40 | 1.56 |
February | 0.632584E+10 | 0.60 | 6913.41 | 01-FEB-16:40 | 1.55 |
March | 0.751037E+10 | 0.69 | 6913.41 | 01-MAR-17:40 | 1.55 |
April | 0.737308E+10 | 0.84 | 6913.41 | 01-APR-07:40 | 1.55 |
May | 0.876658E+10 | 1.21 | 6913.41 | 01-MAY-06:03 | 1.54 |
June | 0.928939E+10 | 1.31 | 6913.41 | 02-JUN-09:00 | 1.56 |
July | 0.997439E+10 | 1.33 | 6913.41 | 15-JUL-10:10 | 1.55 |
August | 0.104715E+11 | 1.34 | 6913.41 | 05-AUG-15:50 | 1.54 |
September | 0.916530E+10 | 1.30 | 6913.41 | 07-SEP-06:40 | 1.54 |
October | 0.830028E+10 | 1.16 | 6913.41 | 02-OCT-09:40 | 1.55 |
November | 0.697148E+10 | 0.79 | 6913.41 | 02-NOV-06:50 | 1.54 |
December | 0.688767E+10 | 0.60 | 6913.41 | 07-DEC-09:10 | 1.55 |
Annual Sum or Average | 0.978829E+11 | 0.98 | |||
Minimum of Months | 0.632584E+10 | 0.58 | 6913.41 | 1.54 | |
Maximum of Months | 0.104715E+11 | 1.34 | 6913.41 | 1.56 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.24 | 2.19 |
February | 1.26 | 0.33 |
March | 3.27 | 0.21 |
April | 3.37 | 0.01 |
May | 4.46 | 0.00 |
June | 5.50 | 0.01 |
July | 5.42 | 0.02 |
August | 5.92 | 0.03 |
September | 4.48 | 0.01 |
October | 3.53 | 0.00 |
November | 2.74 | 0.03 |
December | 2.04 | 0.17 |
Annual Sum or Average | 43.23 | 0.11 |
Minimum of Months | 1.24 | 0.00 |
Maximum of Months | 5.92 | 2.19 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.05 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.05 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.05 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.33 | 0.00 |
April | 2.64 | 0.00 |
May | 9.79 | 0.00 |
June | 2.27 | 0.00 |
July | 0.28 | 0.00 |
August | 0.29 | 0.00 |
September | 4.62 | 0.00 |
October | 9.42 | 0.00 |
November | 0.58 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 30.22 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 9.79 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.305472E+10 | 2129441.52 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.325136E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.432630E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.488044E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.663013E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.762568E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.850279E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.940202E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.756745E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.627621E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.488503E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.375770E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.701598E+11 | 2129441.52 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.305472E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.940202E+10 | 2129441.52 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.865548E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.941982E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.134891E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.176078E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.284483E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.344424E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.414349E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.441445E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.343628E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.257229E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.163173E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.108499E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.284895E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.865548E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.441445E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149140E+10 | 0.585329E+10 | 1369097.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137771E+10 | 0.695517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162602E+10 | 0.978051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151742E+10 | 0.117081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161609E+10 | 0.164613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163303E+10 | 0.196456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162404E+10 | 0.223064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.175201E+10 | 0.248544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159221E+10 | 0.200895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155741E+10 | 0.163869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146228E+10 | 0.124006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150370E+10 | 0.844573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187533E+11 | 0.174887E+12 | 1369097.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137771E+10 | 0.585329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.175201E+10 | 0.248544E+11 | 1369097.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.684703E+10 | 0.615601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.632584E+10 | 0.103376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.751037E+10 | 0.194090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.737308E+10 | 0.320315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.876658E+10 | 0.586149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.928939E+10 | 0.756047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.997439E+10 | 0.935997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.104715E+11 | 0.100677E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.916530E+10 | 0.773377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.830028E+10 | 0.544310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.697148E+10 | 0.303972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.688767E+10 | 0.134192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.978829E+11 | 0.572016E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.632584E+10 | 0.615601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.104715E+11 | 0.100677E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.149140E+10 | 0.00 | 0.00 | 0.00 | 0.156332E+10 | 0.00 | 2129441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137771E+10 | 0.00 | 0.00 | 0.00 | 0.187364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162602E+10 | 0.00 | 0.00 | 0.00 | 0.270028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151742E+10 | 0.00 | 0.00 | 0.00 | 0.336302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161609E+10 | 0.00 | 0.00 | 0.00 | 0.501403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163303E+10 | 0.00 | 0.00 | 0.00 | 0.599265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162404E+10 | 0.00 | 0.00 | 0.00 | 0.687874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.175201E+10 | 0.00 | 0.00 | 0.00 | 0.765001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159221E+10 | 0.00 | 0.00 | 0.00 | 0.597524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155741E+10 | 0.00 | 0.00 | 0.00 | 0.471880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146228E+10 | 0.00 | 0.00 | 0.00 | 0.342275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150370E+10 | 0.00 | 0.00 | 0.00 | 0.225400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187533E+11 | 0.00 | 0.00 | 0.00 | 0.514065E+11 | 0.00 | 2129441.52 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.137771E+10 | 0.00 | 0.00 | 0.00 | 0.156332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.175201E+10 | 0.00 | 0.00 | 0.00 | 0.765001E+10 | 0.00 | 2129441.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.684703E+10 | 0.00 | 0.00 | 0.00 | 0.180844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.632584E+10 | 0.00 | 0.00 | 0.00 | 0.309398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.751037E+10 | 0.00 | 0.00 | 0.00 | 0.597874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.737308E+10 | 0.00 | 0.00 | 0.00 | 0.102347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.876658E+10 | 0.00 | 0.00 | 0.00 | 0.196817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.928939E+10 | 0.00 | 0.00 | 0.00 | 0.251530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.997439E+10 | 0.00 | 0.00 | 0.00 | 0.314605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.104715E+11 | 0.00 | 0.00 | 0.00 | 0.336731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.916530E+10 | 0.00 | 0.00 | 0.00 | 0.251975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.830028E+10 | 0.00 | 0.00 | 0.00 | 0.174226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.697148E+10 | 0.00 | 0.00 | 0.00 | 0.934579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.688767E+10 | 0.00 | 0.00 | 0.00 | 0.396220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.978829E+11 | 0.00 | 0.00 | 0.00 | 0.187012E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.632584E+10 | 0.00 | 0.00 | 0.00 | 0.180844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.104715E+11 | 0.00 | 0.00 | 0.00 | 0.336731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.102049E+09 | 0.255515E+09 | 0.00 | 3300204.29 | 0.00 | 3132623.67 | 0.255429E+09 | 0.00 | 0.16 |
February | 56370626.69 | 0.456164E+09 | 0.00 | 2621797.20 | 0.00 | 0.00 | 0.109776E+09 | 0.00 | 0.17 |
March | 29172081.52 | 0.841894E+09 | 0.00 | 4392458.52 | 0.00 | 0.00 | 95031566.93 | 0.00 | 0.18 |
April | 0.00 | 0.146993E+10 | 0.00 | 5133719.24 | 0.00 | 0.00 | 44726554.48 | 0.00 | 0.17 |
May | 0.00 | 0.264847E+10 | 0.00 | 2777276.52 | 0.00 | 0.00 | 3977090.86 | 0.00 | 0.18 |
June | 0.00 | 0.389440E+10 | 0.00 | 1055407.51 | 0.00 | 0.00 | 310211.30 | 0.00 | 0.19 |
July | 0.00 | 0.507116E+10 | 0.00 | 1228842.20 | 0.00 | 0.00 | 531218.47 | 0.00 | 0.18 |
August | 0.00 | 0.569648E+10 | 0.00 | 6158.43 | 0.00 | 0.00 | 3624.35 | 0.00 | 0.19 |
September | 0.00 | 0.421455E+10 | 0.00 | 916997.45 | 0.00 | 0.00 | 596912.51 | 0.00 | 0.18 |
October | 0.00 | 0.280281E+10 | 0.00 | 1356920.96 | 0.00 | 0.00 | 4289405.08 | 0.00 | 0.17 |
November | 0.00 | 0.171189E+10 | 0.00 | 3191528.10 | 0.00 | 0.00 | 10058263.37 | 0.00 | 0.16 |
December | 37674837.22 | 0.671759E+09 | 0.00 | 3858518.82 | 0.00 | 0.00 | 0.102043E+09 | 0.00 | 0.16 |
Annual Sum or Average | 0.225267E+09 | 0.297350E+11 | 0.00 | 29839829.25 | 0.00 | 3132623.67 | 0.626773E+09 | 0.00 | 0.17 |
Minimum of Months | 0.00 | 0.255515E+09 | 0.00 | 6158.43 | 0.00 | 0.00 | 3624.35 | 0.00 | 0.16 |
Maximum of Months | 0.102049E+09 | 0.569648E+10 | 0.00 | 5133719.24 | 0.00 | 3132623.67 | 0.255429E+09 | 0.00 | 0.19 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.137237E+10 | 0.125976E+09 | 0.00 | 2170829.17 | 2125174.12 | 0.00 | 0.489868E+09 | 0.00 | 0.16 |
February | 0.765051E+09 | 0.460039E+09 | 0.00 | 2702588.97 | 2361825.83 | 0.00 | 0.448995E+09 | 0.00 | 0.17 |
March | 0.526726E+09 | 0.132471E+10 | 0.00 | 3895731.56 | 140734.77 | 0.00 | 0.393405E+09 | 0.00 | 0.18 |
April | 0.202965E+09 | 0.302501E+10 | 0.00 | 2929084.66 | 0.00 | 0.00 | 0.309059E+09 | 0.00 | 0.18 |
May | 402557.32 | 0.724116E+10 | 0.00 | 1733076.94 | 0.00 | 0.00 | 65833666.58 | 0.00 | 0.21 |
June | 0.00 | 0.114470E+11 | 0.00 | 350938.91 | 0.00 | 0.00 | 7754559.83 | 0.00 | 0.23 |
July | 0.00 | 0.164136E+11 | 0.00 | 429975.42 | 0.00 | 0.00 | 1441270.50 | 0.00 | 0.24 |
August | 0.00 | 0.181023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
September | 0.00 | 0.125647E+11 | 0.00 | 147466.20 | 200282.43 | 0.00 | 1723760.45 | 0.00 | 0.23 |
October | 0.00 | 0.713323E+10 | 0.00 | 1638317.54 | 1654122.34 | 0.00 | 61771676.23 | 0.00 | 0.20 |
November | 76421599.51 | 0.335059E+10 | 0.00 | 1182413.61 | 0.00 | 0.00 | 0.137047E+09 | 0.00 | 0.17 |
December | 0.649117E+09 | 0.842814E+09 | 0.00 | 3109030.40 | 71595.57 | 0.00 | 0.458235E+09 | 0.00 | 0.17 |
Annual Sum or Average | 0.359305E+10 | 0.820311E+11 | 0.00 | 20289453.37 | 6553735.07 | 0.00 | 0.237513E+10 | 0.00 | 0.20 |
Minimum of Months | 0.00 | 0.125976E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.137237E+10 | 0.181023E+11 | 0.00 | 3895731.56 | 2361825.83 | 0.00 | 0.489868E+09 | 0.00 | 0.25 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |