Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2020-06-03 19:11:28
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 957.57 | 198.04 | 198.04 |
Net Site Energy | 957.57 | 198.04 | 198.04 |
Total Source Energy | 2661.92 | 550.54 | 550.54 |
Net Source Energy | 2661.92 | 550.54 | 550.54 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 177.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 98.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 36.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.23 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 779.60 | 177.97 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 177.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 2.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 98.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 36.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.23 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 118.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 13.49 | 36.81 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 161.24 | 36.81 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 118.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 13.49 | 36.81 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 161.24 | 36.81 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 779.603 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 779.603 | 100.00 |
Total On-Site and Utility Electric Sources | 779.603 | 100.00 |
Total Electricity End Uses | 779.603 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 58.50 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2078.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.6337 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.5069 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.5069 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-14:39 | 10-JAN-06:19 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 108027.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5902.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2868.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1777.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 55849.45 | 108027.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 108027.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 5902.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2868.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1777.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 192.92 | 0.00 | 0.00 | 0.00 |
Cooling | 7.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1507.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 313.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 116.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 83.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2469.00 | 192.92 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 39.90 | 0.00 | 0.00 | 0.00 |
Cooling | 1.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 64.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 24.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 510.64 | 39.90 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 39.90 | 0.00 | 0.00 | 0.00 |
Cooling | 1.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 64.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 24.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 510.64 | 39.90 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.907991 |
ZONE2 FINE STORAGE DIRECT AIR | 1.67 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 1.23 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 1.23 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 50623.22 |
PSZ-OFFICE HEATING COIL | 23742.84 |
PSZ-FINE STORAGE HEATING COIL | 59104.46 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 50623.22 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.907991 | 0.907991 | 0.907991 | 0.907991 | 0.907991 | 0.907991 | 1.00 | 1.00 | 0.907991 |
PSZ-FINE STORAGE | 1.67 | 1.67 | 1.67 | 1.67 | 1.67 | 1.67 | 1.00 | 1.00 | 1.67 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 0.907991 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 1.67 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.907991 | 0.907991 | 0.907991 | 0.907991 | 15030.47 | 23742.84 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 1.67 | 1.67 | 1.67 | 1.67 | 30916.59 | 59104.46 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.907990 | 0.453995 | 0.907990 | 15030.46 | 15030.47 | 7515.23 | 15030.47 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 1.67 | 0.837420 | 1.67 | 29156.39 | 30916.59 | 15458.30 | 30916.59 | 0.760696 | 0.760700 | 0.760700 | 0.760700 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.907991 | 1035.21 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.67 | 1833.12 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.634 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.707 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.507 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.507 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.507 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.066 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2518.900 | 10.634 | 503.780 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2518.900 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11853.648 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11853.648 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27263.390 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27263.390 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3263 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3263 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.4128 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.4128 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.4128 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.065 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.065 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.323 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.323 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.323 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.38866262E-07 | 0.77198350E-12 | 0.86409618E-13 | 0.0000000 |
2 | 1 | -5.2160226 | 0.42725752E-04 | -0.49098391E-04 | 0.74579932E-08 |
3 | 0 | 5.5423254 | 0.32626013 | 0.32635195 | |
4 | 2 | 0.38866262E-07 | 0.77198350E-12 | 0.86409618E-13 | 0.0000000 |
5 | 1 | -5.2160226 | 0.42725752E-04 | -0.49098391E-04 | 0.74579932E-08 |
6 | 0 | 5.5423254 | 0.32626013 | 0.32635195 | |
7 | 4 | 0.79581057E-12 | 0.97316148E-16 | -0.20714918E-14 | 0.11395926E-15 |
8 | 3 | -0.38950733E-03 | 0.29153728E-06 | -0.56547345E-04 | 0.15269480E-12 |
9 | 2 | 1.7508611 | 0.63413892E-02 | 1.1490629 | -0.74675203E-04 |
10 | 1 | -7.1137977 | 0.16376069 | -17.153076 | 0.33557628 |
11 | 0 | 5.6376123 | 0.10418388 | 16.278356 | |
12 | 4 | 0.79581057E-12 | 0.97316148E-16 | -0.20714918E-14 | 0.11395926E-15 |
13 | 3 | -0.38950733E-03 | 0.29153728E-06 | -0.56547345E-04 | 0.15269480E-12 |
14 | 2 | 1.7508611 | 0.63413892E-02 | 1.1490629 | -0.74675203E-04 |
15 | 1 | -7.1137977 | 0.16376069 | -17.153076 | 0.33557628 |
16 | 0 | 5.6376123 | 0.10418388 | 16.278356 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.8391346 | 2.8391346 | 2.8391346 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8391346 | 2.8391346 | 2.8391346 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.20714918E-14 | 0.97316148E-16 | 0.79581057E-12 | 0.11395926E-15 |
85 | 3 | -0.56547345E-04 | 0.29153728E-06 | -0.38950733E-03 | 0.15269480E-12 |
86 | 2 | 1.1490629 | 0.63413892E-02 | 1.7508611 | -0.74675203E-04 |
87 | 1 | -17.153076 | 0.16376069 | -7.1137977 | 0.33557628 |
88 | 0 | 16.278356 | 0.10418388 | 5.6376123 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 28 | 1 | VerySmooth | 2.843 | 0.395 | 0.315 | 0.401 |
2 | SKYLIGHT_U_0.6_SHGC_0.4 | 29 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 30 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9100.10402 | 10920.12483 | 0.75666 | 0.90799 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.12600 | 8.38408E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 8645.82170 | 10374.98604 | 0.24517 | 0.29421 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -4.30000 | 2.65759E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 21533.66497 | 25840.39796 | 1.39570 | 1.67484 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.40000 | 8.38408E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 22432.93568 | 26919.52282 | 0.53613 | 0.64336 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40000 | 8.38408E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 42186.01694 | 50623.22033 | 1.02665 | 1.23198 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 13085.25 | 0.90799 | 0.90799 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 9788.10 | 0.29421 | 0.29421 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 29321.60 | 1.67484 | 1.67484 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 28922.09 | 0.64336 | 0.64336 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.90799 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.67484 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.23198 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.23198 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 50623.22153 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 50623.22033 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.90799 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.90799 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.90799 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.90799 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.90799 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.90799 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.67484 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.67484 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.67484 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.67484 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.67484 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.67484 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.90799 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.67484 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.90799 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.90799 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.90799 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.90799 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.90799 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.90799 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.45400 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.90799 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 15030.45853 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 15030.47000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 7515.23500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 15030.47000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15030.47000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23742.83939 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.90799 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1035.20943 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 23742.83939 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.67484 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.67484 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.67484 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.67484 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.67484 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.67484 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.83742 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.67484 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 29156.38597 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 30916.59000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 15458.29500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 30916.59000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.76070 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.76070 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.76070 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.76070 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30916.59000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 59104.45676 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.67484 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1833.11821 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 59104.45676 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 14325.9 | 11.07 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 29616.5 | 15.21 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 16 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1382465027 | 0.1662667745 | Pass | Pass | 0.3464125756 | 2.5159208321 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.3794689427 | 0.3612698153 | Pass | Pass | 0.3417028329 | 0.8275959936 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 4.6640832554E-005 | 1.3936073590E-004 | Pass | Pass | 6.1288696044E-002 | 5.7184526879E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.312 | 0.326 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.389 | 0.413 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.389 | 0.413 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.389 | 0.413 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.312 | 0.326 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.102 | 0.395 | 0.401 | ||||||||||||
North Total or Average | 6.51 | 2.843 | 0.395 | 0.401 | ||||||||||||
Non-North Total or Average | 26.02 | 3.167 | 0.395 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.6337 | 236.88 | 2518.90 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.62 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.5069 | 1393.41 | 11853.65 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 135.00 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.5069 | 3204.84 | 27263.39 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 310.50 |
Interior Lighting Total | 8.6111 | 4835.13 | 41635.94 | 476.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 6311.00 | AstronomicalClock | - | 83.54 | 83.54 | 98.97 | |
Exterior Lighting Total | 6311.00 | 98.97 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15030.47 | 12004.24 | 3026.23 | 0.80 | 3.91 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 30916.59 | 23518.25 | 7398.34 | 0.76 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 14325.9 | 11.07 | ||||
PSZ-FINE STORAGE COOLING COIL | 29616.5 | 15.21 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 50623.22 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 23742.84 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 59104.46 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.23 | 114.46 | 92.91 | 1.00 | 3.94 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 0.91 | 1035.21 | 1140.11 | 1.00 | 1.39 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 1.67 | 1833.12 | 1094.51 | 1.00 | 1.31 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9100.10 | 10920.12 | 46.10 | 0.757 | 0.908 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23.90 | 23.90 | 0.00814 | 25.13 | 0.00838 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 21533.66 | 25840.40 | 18.54 | 1.396 | 1.675 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.70 | 26.70 | 0.00803 | 26.40 | 0.00838 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00382 | 26.40 | 0.00838 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8645.82 | 10374.99 | 43.80 | 0.245 | 0.294 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00782 | -4.30 | 0.00266 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 22432.94 | 26919.52 | 19.32 | 0.536 | 0.643 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.56 | 0.00668 | -4.30 | 0.00266 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 42186.02 | 50623.22 | 15.80 | 1.027 | 1.232 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00771 | -4.30 | 0.00266 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.91 | 0.91 | 0.29 | 0.29 | 0.9080 | 0.9080 | 0.9080 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.67 | 1.67 | 0.64 | 0.64 | 1.6748 | 1.6748 | 1.6748 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 50623.222 | 50623.222 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 50623.22 | 50623.22 | 1.231985 | -1.34 | -1.34 | 0.00370441 | 43.33 | 26.97 | 0.01600000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 10.00 | 0.00771221 | 99.9996 | 50623.22 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 15030.470 | 0.000 | 0.907990 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 15030.47 | 14585.76 | 0.907990 | 24.04 | 15.99 | 0.00816489 | 12.00 | 11.16 | 0.00800000 | 25.13 | 0.00838408 | 16.56 | 11.2650 | 23.90 | 0.00813706 | 43.6243 | 9100.10 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 23742.839 | 23742.839 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 23742.84 | 23742.84 | 0.907991 | 12.21 | 9.14 | 0.00602677 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 11.2650 | 21.10 | 0.00782236 | 49.7412 | 8645.82 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 30916.590 | 0.000 | 1.674840 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 30916.59 | 30345.53 | 1.674840 | 26.62 | 16.86 | 0.00812104 | 12.00 | 11.16 | 0.00800000 | 26.40 | 0.00838408 | 17.00 | 25.3584 | 26.70 | 0.00803167 | 36.4588 | 21533.66 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 59104.457 | 59104.457 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 59104.46 | 59104.46 | 1.674837 | 2.45 | 1.71 | 0.00402306 | 40.00 | 21.02 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 25.3584 | 15.56 | 0.00667548 | 60.2159 | 22432.94 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 50623.222 | 50623.222 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1914 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 1.231985 | 1.46775239 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 50623.22 | 50623.22 | 1.0000 | 1.46775239 | 1.231985 | -1.34 | -1.34 | 0.00370441 | 7909.5 | 43.33 | 26.97 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50623.22 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 10.00 | 0.00771221 | 10.00 | 0.00771221 | 99.9996 | 50623.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15030.470 | 0.000 | 0.907990 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0181 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 15030.47 | 14585.76 | 1.0000 | 1.08175387 | 0.907990 | 24.04 | 15.99 | 0.00816489 | 44938.9 | 12.00 | 11.16 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15030.47 | 25.13 | 0.00838408 | 16.56 | 0.10228487 | 11.2650 | 23.90 | 0.00813706 | 23.90 | 0.00813706 | 43.6243 | 9100.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23742.839 | 23742.839 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.907991 | 1.08175497 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 23742.84 | 23742.84 | 1.0000 | 1.08175497 | 0.907991 | 12.21 | 9.14 | 0.00602677 | 27478.3 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23742.84 | -4.30 | 0.00265759 | -4.30 | 0.10228487 | 11.2650 | 21.01 | 0.00782236 | 21.10 | 0.00782236 | 49.7412 | 8645.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30916.590 | 0.000 | 1.674840 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9366 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 30916.59 | 30345.53 | 1.0000 | 1.99535750 | 1.674840 | 26.62 | 16.86 | 0.00812104 | 47464.9 | 12.00 | 11.16 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30916.59 | 26.40 | 0.00838408 | 17.00 | 0.42471267 | 25.3584 | 26.70 | 0.00803167 | 26.70 | 0.00803167 | 36.4588 | 21533.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 59104.457 | 59104.457 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.674837 | 1.99535382 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 59104.46 | 59104.46 | 1.0000 | 1.99535382 | 1.674837 | 2.45 | 1.71 | 0.00402306 | 12540.3 | 40.00 | 21.02 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 59104.46 | -4.30 | 0.00265759 | -4.30 | 0.42471267 | 25.3584 | 15.56 | 0.00667548 | 15.56 | 0.00667548 | 60.2159 | 22432.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 1.67 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2124.33 | 3382.50 | 2078.17 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2124.33 | 3382.50 | 2078.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 60.00 | 0.00 | 58.50 | 0.00 |
ZONE2 FINE STORAGE | 234.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 285.33 | 0.00 | 58.50 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.344 | 0.366 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 779.60 | 5421.86 | 15-JAN-10:50 | 55849.45 | 22-JUL-14:40 |
Electricity:Building | 615.41 | 4938.86 | 01-JAN-00:10 | 45301.66 | 02-JAN-09:10 |
Electricity:Zone:ZONE1 OFFICE | 62.57 | 1027.15 | 01-JAN-00:10 | 3852.05 | 02-JAN-08:10 |
InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.62 | 453.40 | 01-JAN-00:10 | 1939.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 417.84 | 2726.34 | 01-JAN-00:10 | 31374.00 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 310.51 | 2726.34 | 01-JAN-00:10 | 23173.88 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 26.23 | 483.00 | 19-APR-05:10 | 2433.34 | 16-FEB-13:00 |
WaterSystems:Electricity | 26.23 | 483.00 | 19-APR-05:10 | 2433.34 | 16-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 26.23 | 483.00 | 19-APR-05:10 | 2433.34 | 16-FEB-13:00 |
Fans:Electricity | 36.78 | 0.00 | 02-JAN-18:40 | 2982.79 | 02-JAN-07:20 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 779.60 | 5421.86 | 15-JAN-10:50 | 55849.45 | 22-JUL-14:40 |
ElectricityPurchased:Plant | 779.60 | 5421.86 | 15-JAN-10:50 | 55849.45 | 22-JUL-14:40 |
Cogeneration:ElectricityPurchased | 779.60 | 5421.86 | 15-JAN-10:50 | 55849.45 | 22-JUL-14:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 779.60 | 5421.86 | 15-JAN-10:50 | 55849.45 | 22-JUL-14:40 |
ElectricityNet:Plant | 779.60 | 5421.86 | 15-JAN-10:50 | 55849.45 | 22-JUL-14:40 |
Cogeneration:ElectricityNet | 779.60 | 5421.86 | 15-JAN-10:50 | 55849.45 | 22-JUL-14:40 |
Electricity:HVAC | 39.00 | 0.00 | 02-JAN-18:40 | 8980.35 | 22-JUL-15:10 |
General:Fans:Electricity | 36.78 | 0.00 | 02-JAN-18:40 | 2982.79 | 02-JAN-07:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 2.22 | 0.00 | 01-JAN-00:10 | 6112.02 | 22-JUL-15:10 |
ExteriorLights:Electricity | 98.97 | 0.00 | 01-JAN-08:20 | 6311.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 98.97 | 0.00 | 01-JAN-08:20 | 6311.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 177.97 | 0.00 | 02-JAN-18:40 | 108027.98 | 10-JAN-06:20 |
Gas:HVAC | 177.97 | 0.00 | 02-JAN-18:40 | 108027.98 | 10-JAN-06:20 |
Heating:Gas | 177.97 | 0.00 | 02-JAN-18:40 | 108027.98 | 10-JAN-06:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 283.74 | 0.00 | 02-JAN-18:40 | 165685.57 | 10-JAN-06:20 |
EnergyTransfer:Building | 147.13 | 0.00 | 02-JAN-18:40 | 82345.44 | 10-JAN-06:20 |
EnergyTransfer:Zone:ZONE1 OFFICE | 34.13 | 0.00 | 01-JAN-00:10 | 17345.40 | 10-JAN-07:20 |
Heating:EnergyTransfer | 119.90 | 0.00 | 02-JAN-18:40 | 82345.44 | 10-JAN-06:20 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 26.68 | 0.00 | 01-JAN-00:10 | 17345.40 | 10-JAN-07:20 |
Cooling:EnergyTransfer | 27.22 | 0.00 | 01-JAN-00:10 | 17951.02 | 22-JUL-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 7.45 | 0.00 | 01-JAN-00:10 | 6530.44 | 21-JUL-17:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 80.46 | 0.00 | 01-JAN-00:40 | 32867.23 | 10-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 60.69 | 0.00 | 01-JAN-00:40 | 32867.23 | 10-JAN-06:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 19.77 | 0.00 | 01-JAN-00:10 | 11777.54 | 22-JUL-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 32.54 | 0.00 | 02-JAN-08:10 | 42054.71 | 30-DEC-01:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 32.54 | 0.00 | 02-JAN-08:10 | 42054.71 | 30-DEC-01:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 136.62 | 0.00 | 02-JAN-18:40 | 83340.14 | 10-JAN-06:20 |
HeatingCoils:EnergyTransfer | 127.44 | 0.00 | 02-JAN-18:40 | 83340.14 | 10-JAN-06:20 |
CoolingCoils:EnergyTransfer | 9.17 | 0.00 | 01-JAN-00:10 | 22640.89 | 22-JUL-15:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 26.676 | -7.450 | 0.000 | 0.000 | 3.992 | 30.619 | 31.946 | 7.975 | 0.000 | 0.024 | 0.000 | 0.000 | -9.606 | 0.000 | -22.601 | -61.575 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 60.687 | -19.775 | 0.000 | 0.000 | 0.000 | 135.003 | 0.000 | 0.000 | 0.000 | 0.020 | 0.000 | 0.000 | 0.000 | 0.000 | -82.036 | -93.899 |
ZONE3 BULK STORAGE | 32.538 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 310.507 | 107.336 | 16.511 | 0.000 | 0.504 | 0.000 | 0.000 | -8.874 | 0.000 | -291.277 | -167.247 |
Total Facility | 32.538 | 0.000 | 87.363 | -27.225 | 0.000 | 0.000 | 3.992 | 476.129 | 139.282 | 24.487 | 0.000 | 0.549 | 0.000 | 0.000 | -18.480 | 0.000 | -395.914 | -322.721 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 24-JUL-05:03 | 0.00 | 0.00 | 0.00 | -12634.78 | 0.00 | 0.00 | 36.21 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 12766.16 | 0.00 | -448.17 | 0.00 | -872.52 | 0.00 |
ZONE2 FINE STORAGE | 22-JUL-17:12 | 0.00 | 0.00 | 0.00 | -17892.91 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 627.20 | 16080.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-JUL-15:10 | 0.00 | 0.00 | 0.00 | -17950.65 | 0.00 | 0.00 | 357.67 | 31277.33 | 10112.62 | 5815.35 | 0.00 | 4893.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -34506.13 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 24-NOV-06:01 | 0.00 | 0.00 | 23291.63 | 0.00 | 0.00 | 0.00 | 55.78 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -346.22 | 0.00 | -373.81 | -23780.48 |
ZONE2 FINE STORAGE | 10-JAN-06:02 | 0.00 | 0.00 | 61161.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -8246.73 | -54100.51 |
ZONE3 BULK STORAGE | 30-DEC-01:00 | 42054.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -702.15 | 0.00 | -30424.76 | -15703.71 |
Total Facility | 10-JAN-06:11 | 38394.19 | 0.00 | 82199.25 | 0.00 | 0.00 | 0.00 | 59.26 | 4491.05 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1553.87 | 0.00 | -33905.24 | -92308.41 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9080 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.9080 | 0.1126 | 1.0000 | 0.1023 | 0.1126 | ||
PSZ-FINE STORAGE | 1.6748 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.6748 | 0.2536 | 1.0000 | 0.4247 | 0.2536 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9080 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.9080 | 1.0000 | 1.0000 | 0.1023 | 0.1126 | ||
PSZ-FINE STORAGE | 1.6748 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.6748 | 1.0000 | 1.0000 | 0.4247 | 0.2536 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.9080 | 0.9080 | 0.9080 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.6748 | 1.6748 | 1.6748 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9080 | 0.9080 | 0.9080 | 0.9080 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.6748 | 1.6748 | 1.6748 | 1.6748 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.9080 | 0.9080 | 0.9080 | 0.1023 | 0.3477 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.6748 | 1.6748 | 1.6748 | 0.4247 | 0.6602 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9080 | 0.9080 | 0.9080 | 0.9080 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.6748 | 1.6748 | 1.6748 | 1.6748 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:28
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 58.50 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 58.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 177.97 | 108027.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 2.22 | 6112.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 476.13 | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 98.97 | 6311.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 36.78 | 2982.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.23 | 2433.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 779.60 |
Natural Gas | 0.00 | 177.97 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 957.57 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 98.47 |
Space Heating | 0.00 |
Space Cooling | 0.46 |
Fans (All) | 7.61 |
Service Water Heating | 5.42 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 161.24 |
Subtotal | 161.24 |
Natural Gas [MJ/m2] | |
Space Heating | 36.81 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 36.81 |
Subtotal | 36.81 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 49.72 |
Space Heating | 18.59 |
Space Cooling | 0.23 |
Fans (All) | 3.84 |
Service Water Heating | 2.74 |
Receptacle Equipment | 14.55 |
Miscellaneous | 10.34 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.408185E+11 |
February | 0.000 | 0.285330E+11 |
March | 0.000 | 0.173233E+11 |
April | 0.000 | 0.358541E+10 |
May | 0.000 | 0.257127E+10 |
June | 0.000 | 0.362891E+09 |
July | 0.000 | 0.973083E+08 |
August | 0.000 | 0.396750E+08 |
September | 0.000 | 0.431228E+09 |
October | 0.000 | 0.521178E+10 |
November | 0.000 | 0.206436E+11 |
December | 0.000 | 0.583509E+11 |
Annual Sum or Average | 0.177969E+12 | |
Minimum of Months | 0.000 | 0.396750E+08 |
Maximum of Months | 0.000 | 0.583509E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.408185E+11 |
February | 0.000 | 0.285330E+11 |
March | 0.000 | 0.173233E+11 |
April | 0.000 | 0.358541E+10 |
May | 0.000 | 0.257127E+10 |
June | 0.000 | 0.362891E+09 |
July | 0.000 | 0.973083E+08 |
August | 0.000 | 0.396750E+08 |
September | 0.000 | 0.431228E+09 |
October | 0.000 | 0.521178E+10 |
November | 0.000 | 0.206436E+11 |
December | 0.000 | 0.583509E+11 |
Annual Sum or Average | 0.177969E+12 | |
Minimum of Months | 0.000 | 0.396750E+08 |
Maximum of Months | 0.000 | 0.583509E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Meter
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.408185E+11 |
February | 0.000 | 0.285330E+11 |
March | 0.000 | 0.173233E+11 |
April | 0.000 | 0.358541E+10 |
May | 0.000 | 0.257127E+10 |
June | 0.000 | 0.362891E+09 |
July | 0.000 | 0.973083E+08 |
August | 0.000 | 0.396750E+08 |
September | 0.000 | 0.431228E+09 |
October | 0.000 | 0.521178E+10 |
November | 0.000 | 0.206436E+11 |
December | 0.000 | 0.583509E+11 |
Annual Sum or Average | 0.177969E+12 | |
Minimum of Months | 0.000 | 0.396750E+08 |
Maximum of Months | 0.000 | 0.583509E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.408185E+11 |
February | 0.000 | 0.285330E+11 |
March | 0.000 | 0.173233E+11 |
April | 0.000 | 0.358541E+10 |
May | 0.000 | 0.257127E+10 |
June | 0.000 | 0.362891E+09 |
July | 0.000 | 0.973083E+08 |
August | 0.000 | 0.396750E+08 |
September | 0.000 | 0.431228E+09 |
October | 0.000 | 0.521178E+10 |
November | 0.000 | 0.206436E+11 |
December | 0.000 | 0.583509E+11 |
Annual Sum or Average | 0.177969E+12 | |
Minimum of Months | 0.000 | 0.396750E+08 |
Maximum of Months | 0.000 | 0.583509E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.408185E+11 |
February | 0.000 | 0.285330E+11 |
March | 0.000 | 0.173233E+11 |
April | 0.000 | 0.358541E+10 |
May | 0.000 | 0.257127E+10 |
June | 0.000 | 0.362891E+09 |
July | 0.000 | 0.973083E+08 |
August | 0.000 | 0.396750E+08 |
September | 0.000 | 0.431228E+09 |
October | 0.000 | 0.521178E+10 |
November | 0.000 | 0.206436E+11 |
December | 0.000 | 0.583509E+11 |
Annual Sum or Average | 0.177969E+12 | |
Minimum of Months | 0.000 | 0.396750E+08 |
Maximum of Months | 0.000 | 0.583509E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.408185E+11 |
February | 0.000 | 0.285330E+11 |
March | 0.000 | 0.173233E+11 |
April | 0.000 | 0.358541E+10 |
May | 0.000 | 0.257127E+10 |
June | 0.000 | 0.362891E+09 |
July | 0.000 | 0.973083E+08 |
August | 0.000 | 0.396750E+08 |
September | 0.000 | 0.431228E+09 |
October | 0.000 | 0.521178E+10 |
November | 0.000 | 0.206436E+11 |
December | 0.000 | 0.583509E+11 |
Annual Sum or Average | 0.177969E+12 | |
Minimum of Months | 0.000 | 0.396750E+08 |
Maximum of Months | 0.000 | 0.583509E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.408185E+11 |
February | 0.000 | 0.285330E+11 |
March | 0.000 | 0.173233E+11 |
April | 0.000 | 0.358541E+10 |
May | 0.000 | 0.257127E+10 |
June | 0.000 | 0.362891E+09 |
July | 0.000 | 0.973083E+08 |
August | 0.000 | 0.396750E+08 |
September | 0.000 | 0.431228E+09 |
October | 0.000 | 0.521178E+10 |
November | 0.000 | 0.206436E+11 |
December | 0.000 | 0.583509E+11 |
Annual Sum or Average | 0.177969E+12 | |
Minimum of Months | 0.000 | 0.396750E+08 |
Maximum of Months | 0.000 | 0.583509E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Meter
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.408185E+11 |
February | 0.000 | 0.285330E+11 |
March | 0.000 | 0.173233E+11 |
April | 0.000 | 0.358541E+10 |
May | 0.000 | 0.257127E+10 |
June | 0.000 | 0.362891E+09 |
July | 0.000 | 0.973083E+08 |
August | 0.000 | 0.396750E+08 |
September | 0.000 | 0.431228E+09 |
October | 0.000 | 0.521178E+10 |
November | 0.000 | 0.206436E+11 |
December | 0.000 | 0.583509E+11 |
Annual Sum or Average | 0.177969E+12 | |
Minimum of Months | 0.000 | 0.396750E+08 |
Maximum of Months | 0.000 | 0.583509E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Meter
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.408185E+11 |
February | 0.000 | 0.285330E+11 |
March | 0.000 | 0.173233E+11 |
April | 0.000 | 0.358541E+10 |
May | 0.000 | 0.257127E+10 |
June | 0.000 | 0.362891E+09 |
July | 0.000 | 0.973083E+08 |
August | 0.000 | 0.396750E+08 |
September | 0.000 | 0.431228E+09 |
October | 0.000 | 0.521178E+10 |
November | 0.000 | 0.206436E+11 |
December | 0.000 | 0.583509E+11 |
Annual Sum or Average | 0.177969E+12 | |
Minimum of Months | 0.000 | 0.396750E+08 |
Maximum of Months | 0.000 | 0.583509E+11 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1916245.97 | 342.64 | 21-JAN-15:50 | 6.42 | 5.37 | 0.195006E+09 | 236.59 | 10-JAN-11:09 | -1.8 | -1.8 |
February | 2908253.95 | 678.45 | 18-FEB-15:20 | 6.00 | 4.15 | 0.179413E+09 | 236.59 | 18-FEB-10:09 | 5.00 | 4.09 |
March | 5712272.88 | 708.85 | 11-MAR-16:20 | 6.33 | 3.75 | 0.210775E+09 | 249.83 | 25-MAR-13:39 | 12.67 | 9.93 |
April | 0.233305E+09 | 3202.55 | 29-APR-15:50 | 20.00 | 12.38 | 0.208409E+09 | 301.59 | 28-APR-15:09 | 20.08 | 13.46 |
May | 0.376300E+09 | 2803.10 | 25-MAY-16:00 | 18.00 | 13.89 | 0.222749E+09 | 301.60 | 25-MAY-15:09 | 17.17 | 13.55 |
June | 0.121952E+10 | 5091.53 | 13-JUN-16:00 | 26.50 | 17.68 | 0.247905E+09 | 301.60 | 13-JUN-15:39 | 26.33 | 17.73 |
July | 0.211767E+10 | 12636.32 | 24-JUL-05:03 | 13.00 | 13.00 | 0.245304E+09 | 301.62 | 31-JUL-12:09 | 18.00 | 12.00 |
August | 0.230160E+10 | 5056.16 | 19-AUG-16:00 | 20.00 | 15.65 | 0.266062E+09 | 301.60 | 19-AUG-15:00 | 20.00 | 15.65 |
September | 0.110355E+10 | 4154.87 | 13-SEP-16:00 | 23.00 | 16.21 | 0.239992E+09 | 301.60 | 28-SEP-15:50 | 15.00 | 12.56 |
October | 77110647.30 | 1390.66 | 07-OCT-16:00 | 18.00 | 9.64 | 0.204055E+09 | 301.58 | 05-OCT-15:00 | 16.00 | 9.11 |
November | 10418512.89 | 503.77 | 04-NOV-15:20 | 8.33 | 6.25 | 0.187401E+09 | 249.56 | 10-NOV-15:50 | 11.17 | 8.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.00 | 3.53 | 0.195001E+09 | 236.59 | 04-DEC-16:30 | 8.00 | 6.05 |
Annual Sum or Average | 0.745001E+10 | 0.260207E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.00 | 3.53 | 0.179413E+09 | 236.59 | -1.8 | -1.8 | ||
Maximum of Months | 0.230160E+10 | 12636.32 | 26.50 | 17.68 | 0.266062E+09 | 301.62 | 26.33 | 17.73 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121705E+10 | 4280.16 | 20-JAN-09:50 | 3.67 | 3.26 | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 | 1.45 |
February | 0.165141E+10 | 4216.01 | 23-FEB-15:00 | 4.00 | 4.00 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 5.79 |
March | 0.201663E+10 | 4087.60 | 08-MAR-13:00 | 4.00 | 2.71 | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 | 3.71 |
April | 0.199443E+10 | 8089.05 | 28-APR-06:10 | 7.72 | 6.32 | 0.00 | 0.00 | 01-APR-00:10 | 4.23 | 1.83 |
May | 0.210716E+10 | 6689.51 | 04-MAY-06:10 | 7.33 | 7.17 | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 | 8.15 |
June | 0.201258E+10 | 8436.06 | 20-JUN-06:10 | 11.50 | 9.64 | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 | 7.38 |
July | 0.220945E+10 | 17892.95 | 22-JUL-17:12 | 29.33 | 16.62 | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 | 9.95 |
August | 0.156198E+10 | 8159.34 | 01-AUG-06:10 | 13.50 | 12.18 | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 | 9.82 |
September | 0.135183E+10 | 8260.05 | 21-SEP-06:10 | 5.33 | 4.84 | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 | 10.95 |
October | 0.142570E+10 | 6120.87 | 13-OCT-06:10 | 10.00 | 10.00 | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 | 5.82 |
November | 0.141291E+10 | 3751.13 | 16-NOV-09:10 | 4.83 | 4.15 | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 | 4.28 |
December | 0.813801E+09 | 4067.16 | 30-DEC-11:30 | 3.00 | -0.3 | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 |
Annual Sum or Average | 0.197749E+11 | 0.00 | ||||||||
Minimum of Months | 0.813801E+09 | 3751.13 | 3.00 | -0.3 | 0.00 | 0.00 | 1.92 | 1.45 | ||
Maximum of Months | 0.220945E+10 | 17892.95 | 29.33 | 16.62 | 0.00 | 0.00 | 12.43 | 10.95 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.92 | 1.45 | 0.00 | 0.00 | 01-JAN-00:10 | 1.92 | 1.45 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 | 5.79 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 5.79 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 3.80 | 3.71 | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 | 3.71 |
April | 0.00 | 0.00 | 01-APR-00:05 | 4.23 | 1.83 | 0.00 | 0.00 | 01-APR-00:10 | 4.23 | 1.83 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 | 8.15 | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 | 8.15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 | 7.38 | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 | 7.38 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 | 9.95 | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 | 9.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 | 9.82 | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 | 9.82 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 | 10.95 | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 | 10.95 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 | 5.82 | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 | 5.82 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 | 4.28 | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 | 4.28 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.00 | 3.53 | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.92 | 1.45 | 0.00 | 0.00 | 1.92 | 1.45 | ||
Maximum of Months | 0.00 | 0.00 | 12.43 | 10.95 | 0.00 | 0.00 | 12.43 | 10.95 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.478801E+10 | 22953.60 | 17-JAN-06:01 | 6.07 |
February | 0.400394E+10 | 22963.03 | 22-FEB-06:01 | 6.83 |
March | 0.412293E+10 | 23118.87 | 18-MAR-05:01 | 9.00 |
April | 0.163574E+10 | 22804.16 | 10-APR-05:01 | 6.17 |
May | 0.122719E+10 | 23063.93 | 19-MAY-05:01 | 9.00 |
June | 0.262556E+09 | 22474.49 | 08-JUN-05:01 | 6.17 |
July | 83039572.76 | 22280.21 | 05-JUL-05:02 | 7.33 |
August | 45313952.77 | 3519.07 | 24-AUG-06:10 | 8.83 |
September | 0.292224E+09 | 22212.04 | 07-SEP-05:02 | 8.83 |
October | 0.182459E+10 | 23264.87 | 20-OCT-05:01 | 11.00 |
November | 0.347969E+10 | 23291.53 | 24-NOV-06:01 | 10.17 |
December | 0.491086E+10 | 22847.31 | 05-DEC-06:01 | 6.00 |
Annual Sum or Average | 0.266761E+11 | |||
Minimum of Months | 45313952.77 | 3519.07 | 6.00 | |
Maximum of Months | 0.491086E+10 | 23291.53 | 11.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122585E+11 | 61161.70 | 10-JAN-06:02 | -4.0 |
February | 0.111586E+11 | 60432.88 | 17-FEB-04:12 | -2.0 |
March | 0.669540E+10 | 59958.83 | 30-MAR-05:07 | 5.00 |
April | 0.723761E+09 | 59943.94 | 03-APR-05:08 | 3.83 |
May | 0.570781E+09 | 59964.04 | 20-MAY-05:07 | 4.50 |
June | 0.139725E+09 | 1926.57 | 22-JUN-07:00 | 12.00 |
July | 0.152438E+09 | 1960.18 | 11-JUL-06:50 | 12.83 |
August | 0.146862E+09 | 2008.57 | 19-AUG-07:00 | 12.00 |
September | 0.161958E+09 | 1939.55 | 27-SEP-07:00 | 10.00 |
October | 0.164798E+10 | 59948.66 | 31-OCT-05:06 | 7.00 |
November | 0.898898E+10 | 60472.80 | 29-NOV-04:03 | -0.8 |
December | 0.180428E+11 | 61139.67 | 30-DEC-01:22 | -2.0 |
Annual Sum or Average | 0.606879E+11 | |||
Minimum of Months | 0.139725E+09 | 1926.57 | -4.0 | |
Maximum of Months | 0.180428E+11 | 61161.70 | 12.83 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101228E+11 | 41119.97 | 10-JAN-05:52 | -4.0 |
February | 0.381931E+10 | 27147.98 | 19-FEB-22:00 | 0.00 |
March | 56453001.96 | 8607.45 | 04-MAR-06:00 | 3.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.105689E+10 | 23004.23 | 29-NOV-03:55 | -1.0 |
December | 0.174831E+11 | 42054.71 | 30-DEC-01:00 | -2.0 |
Annual Sum or Average | 0.325385E+11 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 0.174831E+11 | 42054.71 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.256100E+10 | 1939.55 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.233575E+10 | 1939.55 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.266872E+10 | 1939.55 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.252182E+10 | 1939.55 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.261486E+10 | 1939.55 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.257569E+10 | 1939.55 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.256100E+10 | 1939.55 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.266872E+10 | 1939.55 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.252182E+10 | 1939.55 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.256100E+10 | 1939.55 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.246796E+10 | 1939.55 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.256100E+10 | 1939.55 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.306193E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.233575E+10 | 1939.55 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.266872E+10 | 1939.55 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112294E+11 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102778E+11 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.118738E+11 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.111270E+11 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.115516E+11 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.114492E+11 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112294E+11 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.118738E+11 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.111270E+11 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112294E+11 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108048E+11 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112294E+11 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135003E+12 | ||||
Minimum of Months | 0.102778E+11 | 10075.60 | 0.00 | 0.00 | |
Maximum of Months | 0.118738E+11 | 10075.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.258277E+11 | 23173.88 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.236390E+11 | 23173.88 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.273097E+11 | 23173.88 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.255921E+11 | 23173.88 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.265687E+11 | 23173.88 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.263332E+11 | 23173.88 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.258277E+11 | 23173.88 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.273097E+11 | 23173.88 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.255921E+11 | 23173.88 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.258277E+11 | 23173.88 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.248511E+11 | 23173.88 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.258277E+11 | 23173.88 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.236390E+11 | 23173.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.273097E+11 | 23173.88 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235337E+10 |
February | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213792E+10 |
March | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224038E+10 |
April | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161907E+10 |
May | 0.565842E+09 | 0.261486E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3455.27 | 0.208789E+10 |
June | 0.565842E+09 | 0.257569E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6422624.85 | 0.162340E+10 |
July | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12507704.04 | 0.135841E+10 |
August | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4695141.32 | 0.127114E+10 |
September | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133498E+10 |
October | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173583E+10 |
November | 0.522316E+09 | 0.246796E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221367E+10 |
December | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262469E+10 |
Annual Sum or Average | 0.659424E+10 | 0.306193E+11 | 0.319458E+11 | 23628925.47 | 0.226007E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127114E+10 |
Maximum of Months | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12507704.04 | 0.262469E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422610E+10 |
February | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586229E+10 |
March | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377156E+10 |
April | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73354.22 | 0.417507E+10 |
May | 0.00 | 0.115516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100243E+11 |
June | 0.00 | 0.114492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1083100.10 | 0.892591E+10 |
July | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18018942.00 | 0.884323E+10 |
August | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1260267.11 | 0.740646E+10 |
September | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633932E+10 |
October | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522310E+10 |
November | 0.00 | 0.108048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697185E+10 |
December | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102670E+11 |
Annual Sum or Average | 0.135003E+12 | 20435663.43 | 0.820362E+11 | ||||||
Minimum of Months | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377156E+10 |
Maximum of Months | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18018942.00 | 0.102670E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14553035.75 | 0.886825E+10 |
February | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119471E+11 |
March | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.866954E+10 |
April | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31373282.47 | 0.122864E+11 |
May | 0.00 | 0.265687E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76804757.89 | 0.297291E+11 |
June | 0.00 | 0.263332E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120398E+09 | 0.260449E+11 |
July | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92393355.68 | 0.269383E+11 |
August | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17228654.20 | 0.237474E+11 |
September | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3491249.34 | 0.207002E+11 |
October | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164126E+11 |
November | 0.00 | 0.248511E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17940491.86 | 0.147049E+11 |
December | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8363566.29 | 0.184355E+11 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | 0.382546E+09 | 0.218484E+12 | |||||
Minimum of Months | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.866954E+10 |
Maximum of Months | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120398E+09 | 0.297291E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1939.55 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 10254.10 | 10-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1939.55 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 9474.68 | 17-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1939.55 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 8076.75 | 08-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1939.55 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 6707.34 | 20-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1939.55 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.76 | 22-MAY-15:00 | 6626.74 | 02-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1939.55 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1146.01 | 13-JUN-17:00 | 5647.83 | 08-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 1939.55 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1829.00 | 21-JUL-17:00 | 4587.62 | 05-JUL-06:10 |
August | 659.25 | 01-AUG-07:10 | 1939.55 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1132.95 | 14-AUG-17:00 | 4676.55 | 24-AUG-06:05 |
September | 659.25 | 01-SEP-07:10 | 1939.55 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 5894.81 | 20-SEP-06:05 |
October | 659.25 | 02-OCT-07:10 | 1939.55 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 7161.88 | 04-OCT-06:10 |
November | 659.25 | 01-NOV-07:10 | 1939.55 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9138.76 | 29-NOV-08:00 |
December | 659.25 | 01-DEC-08:09 | 1939.55 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 9343.48 | 29-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4587.62 | |||||
Maximum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1829.00 | 10254.10 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 14734.97 | 10-JAN-18:00 |
February | 0.00 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 9306.14 | 01-FEB-16:10 |
March | 0.00 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 14858.84 | 31-MAR-08:00 |
April | 0.00 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.32 | 30-APR-19:00 | 8644.07 | 24-APR-15:05 |
May | 0.00 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 18399.58 | 01-MAY-15:03 |
June | 0.00 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.40 | 12-JUN-18:00 | 12106.32 | 07-JUN-15:05 |
July | 0.00 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.46 | 22-JUL-15:10 | 9674.73 | 30-JUL-19:00 |
August | 0.00 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.29 | 14-AUG-18:00 | 11164.35 | 22-AUG-16:00 |
September | 0.00 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 11673.05 | 29-SEP-15:05 |
October | 0.00 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 8511.05 | 20-OCT-15:05 |
November | 0.00 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 12996.39 | 15-NOV-07:10 |
December | 0.00 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 21636.43 | 02-DEC-18:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8511.05 | |||
Maximum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.46 | 21636.43 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23173.88 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2839.77 | 29-JAN-06:00 | 31514.61 | 10-JAN-16:00 |
February | 0.00 | 23173.88 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 19871.30 | 01-FEB-16:00 |
March | 0.00 | 23173.88 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 30856.68 | 31-MAR-08:00 |
April | 0.00 | 23173.88 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1802.95 | 30-APR-19:00 | 21731.91 | 24-APR-12:10 |
May | 0.00 | 23173.88 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4345.31 | 22-MAY-15:00 | 48597.92 | 01-MAY-13:00 |
June | 0.00 | 23173.88 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5355.07 | 13-JUN-15:00 | 32127.58 | 07-JUN-15:00 |
July | 0.00 | 23173.88 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3105.72 | 22-JUL-19:00 | 27762.57 | 30-JUL-19:00 |
August | 0.00 | 23173.88 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2394.57 | 14-AUG-18:00 | 30858.63 | 22-AUG-16:00 |
September | 0.00 | 23173.88 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 565.04 | 24-SEP-16:00 | 27159.94 | 19-SEP-15:00 |
October | 0.00 | 23173.88 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 24655.54 | 01-OCT-24:00 |
November | 0.00 | 23173.88 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4776.13 | 24-NOV-12:00 | 23068.08 | 03-NOV-07:10 |
December | 0.00 | 23173.88 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4792.69 | 23-DEC-11:00 | 29038.57 | 02-DEC-17:55 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19871.30 | ||||
Maximum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 5355.07 | 48597.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 342.64 | 21-JAN-15:50 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.39 |
February | 678.45 | 18-FEB-15:20 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.43 |
March | 708.85 | 11-MAR-16:20 | 1318.50 | 3879.11 | 3825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.00 |
April | 3202.55 | 29-APR-15:50 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.05 |
May | 2803.10 | 25-MAY-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.27 |
June | 5091.53 | 13-JUN-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 235.39 | 0.00 |
July | 12636.32 | 24-JUL-05:03 | 290.07 | 2317.39 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 872.52 |
August | 5056.16 | 19-AUG-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.80 |
September | 4154.87 | 13-SEP-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.61 |
October | 1390.66 | 07-OCT-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 503.77 | 04-NOV-15:20 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.92 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 906.80 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.03 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 906.80 | 1147.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12636.32 | 1318.50 | 3879.11 | 3825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.39 | 872.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4280.16 | 20-JAN-09:50 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4216.01 | 23-FEB-15:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1860.02 |
March | 4087.60 | 08-MAR-13:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1381.22 |
April | 8089.05 | 28-APR-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6689.51 | 04-MAY-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.66 |
June | 8436.06 | 20-JUN-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1712.07 |
July | 17892.95 | 22-JUL-17:12 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 627.20 | 0.00 |
August | 8159.34 | 01-AUG-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 900.38 |
September | 8260.05 | 21-SEP-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6120.87 | 13-OCT-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3751.13 | 16-NOV-09:10 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4067.16 | 30-DEC-11:30 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3751.13 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17892.95 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 627.20 | 1860.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 8179.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3955.68 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4403.10 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 01-APR-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5106.92 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9426.33 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11302.97 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20193.36 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9531.36 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11582.98 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16619.72 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7448.80 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3318.23 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 8179.02 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20193.36 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.675647E+11 | 52335.68 | 07-JAN-08:09 | 0.408185E+11 | 108027.98 | 10-JAN-06:19 |
February | 0.608410E+11 | 50079.40 | 11-FEB-15:00 | 0.285330E+11 | 74445.09 | 18-FEB-06:10 |
March | 0.684815E+11 | 50070.80 | 02-MAR-15:09 | 0.173233E+11 | 46115.58 | 04-MAR-06:19 |
April | 0.630045E+11 | 50827.89 | 29-APR-14:00 | 0.358541E+10 | 34657.29 | 11-APR-06:10 |
May | 0.643086E+11 | 50837.55 | 22-MAY-14:00 | 0.257127E+10 | 27121.31 | 05-MAY-05:10 |
June | 0.632960E+11 | 52962.24 | 13-JUN-14:00 | 0.362891E+09 | 12330.10 | 08-JUN-06:10 |
July | 0.629466E+11 | 55849.45 | 22-JUL-14:39 | 97308316.99 | 8473.10 | 05-JUL-06:10 |
August | 0.671194E+11 | 51911.15 | 14-AUG-14:50 | 39675006.72 | 3732.47 | 24-AUG-06:19 |
September | 0.638609E+11 | 51215.67 | 13-SEP-14:00 | 0.431228E+09 | 10300.24 | 21-SEP-06:19 |
October | 0.656138E+11 | 50360.87 | 07-OCT-14:00 | 0.521178E+10 | 27542.24 | 23-OCT-05:19 |
November | 0.645194E+11 | 52183.89 | 30-NOV-16:30 | 0.206436E+11 | 75206.40 | 28-NOV-06:10 |
December | 0.680471E+11 | 52335.01 | 29-DEC-08:09 | 0.583509E+11 | 97412.77 | 28-DEC-07:10 |
Annual Sum or Average | 0.779603E+12 | 0.177969E+12 | ||||
Minimum of Months | 0.608410E+11 | 50070.80 | 39675006.72 | 3732.47 | ||
Maximum of Months | 0.684815E+11 | 55849.45 | 0.583509E+11 | 108027.98 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.396181E+11 | 0.108183E+11 | 0.115358E+11 | 0.00 | 0.334335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224915E+10 | 0.00 |
February | 0.362526E+11 | 0.890230E+10 | 0.105871E+11 | 0.00 | 0.304774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205123E+10 | 0.00 |
March | 0.418523E+11 | 0.866374E+10 | 0.123357E+11 | 0.00 | 0.331706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231271E+10 | 0.00 |
April | 0.392410E+11 | 0.717939E+10 | 0.114862E+11 | 0.00 | 0.288073E+10 | 0.00 | 0.00 | 34548411.19 | 0.00 | 0.00 | 0.00 | 0.218261E+10 | 0.00 |
May | 0.407352E+11 | 0.636149E+10 | 0.119357E+11 | 0.00 | 0.298302E+10 | 0.00 | 0.00 | 57075363.25 | 0.00 | 0.00 | 0.00 | 0.223611E+10 | 0.00 |
June | 0.403581E+11 | 0.559281E+10 | 0.118862E+11 | 0.00 | 0.295590E+10 | 0.00 | 0.00 | 0.341149E+09 | 0.00 | 0.00 | 0.00 | 0.216189E+10 | 0.00 |
July | 0.396181E+11 | 0.602827E+10 | 0.115358E+11 | 0.00 | 0.284306E+10 | 0.00 | 0.00 | 0.762400E+09 | 0.00 | 0.00 | 0.00 | 0.215898E+10 | 0.00 |
August | 0.418523E+11 | 0.694841E+10 | 0.123357E+11 | 0.00 | 0.306682E+10 | 0.00 | 0.00 | 0.705839E+09 | 0.00 | 0.00 | 0.00 | 0.221039E+10 | 0.00 |
September | 0.392410E+11 | 0.786098E+10 | 0.114862E+11 | 0.00 | 0.284183E+10 | 0.00 | 0.00 | 0.315468E+09 | 0.00 | 0.00 | 0.00 | 0.211546E+10 | 0.00 |
October | 0.396181E+11 | 0.936048E+10 | 0.115358E+11 | 0.00 | 0.291086E+10 | 0.00 | 0.00 | 4085306.22 | 0.00 | 0.00 | 0.00 | 0.218444E+10 | 0.00 |
November | 0.381239E+11 | 0.101405E+11 | 0.110862E+11 | 0.00 | 0.303699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213171E+10 | 0.00 |
December | 0.396181E+11 | 0.111099E+11 | 0.115358E+11 | 0.00 | 0.355084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223249E+10 | 0.00 |
Annual Sum or Average | 0.476129E+12 | 0.989666E+11 | 0.139282E+12 | 0.367782E+11 | 0.00 | 0.222057E+10 | 0.262272E+11 | ||||||
Minimum of Months | 0.362526E+11 | 0.559281E+10 | 0.105871E+11 | 0.00 | 0.284183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205123E+10 | 0.00 |
Maximum of Months | 0.418523E+11 | 0.111099E+11 | 0.123357E+11 | 0.00 | 0.355084E+10 | 0.00 | 0.00 | 0.762400E+09 | 0.00 | 0.00 | 0.00 | 0.231271E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.408185E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.285330E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.173233E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.358541E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.257127E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.362891E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 97308316.99 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 39675006.72 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.431228E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.521178E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.206436E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.583509E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177969E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 39675006.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.583509E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35189.04 | 02-JAN-09:09 | 6311.00 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 2982.79 | 02-JAN-07:19 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35189.04 | 01-FEB-09:09 | 6311.00 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 2982.79 | 13-FEB-07:19 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35189.04 | 01-MAR-09:09 | 6311.00 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 2868.33 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35189.04 | 01-APR-08:09 | 6311.00 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 2868.33 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35189.04 | 01-MAY-08:09 | 6311.00 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 2868.33 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35189.04 | 01-JUN-08:09 | 6311.00 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 2868.33 | 01-JUN-06:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35189.04 | 01-JUL-08:09 | 6311.00 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 2868.33 | 01-JUL-06:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35189.04 | 01-AUG-08:09 | 6311.00 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 2868.33 | 01-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35189.04 | 01-SEP-08:09 | 6311.00 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 2868.33 | 01-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35189.04 | 02-OCT-08:09 | 6311.00 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 2868.33 | 02-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35189.04 | 01-NOV-08:09 | 6311.00 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 2982.79 | 28-NOV-07:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35189.04 | 01-DEC-09:09 | 6311.00 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 2982.79 | 04-DEC-07:49 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35189.04 | 6311.00 | 10112.62 | 0.00 | 2868.33 | 0.00 | 0.00 | |||||
Maximum of Months | 35189.04 | 6311.00 | 10112.62 | 0.00 | 2982.79 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2425.45 | 30-JAN-12:30 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2433.34 | 16-FEB-12:00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2425.42 | 01-MAR-12:50 | 0.00 |
April | 895.90 | 29-APR-15:50 | 0.00 | 0.00 | 0.00 | 2362.06 | 03-APR-11:20 | 0.00 |
May | 919.05 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2267.23 | 01-MAY-11:39 | 0.00 |
June | 3280.56 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | 2136.59 | 01-JUN-11:20 | 0.00 |
July | 6112.02 | 22-JUL-15:09 | 0.00 | 0.00 | 0.00 | 2005.16 | 06-JUL-11:20 | 0.00 |
August | 2405.45 | 14-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1950.60 | 31-AUG-11:50 | 0.00 |
September | 1315.30 | 13-SEP-15:00 | 0.00 | 0.00 | 0.00 | 2014.54 | 28-SEP-11:39 | 0.00 |
October | 422.62 | 07-OCT-15:39 | 0.00 | 0.00 | 0.00 | 2128.49 | 28-OCT-11:00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2239.54 | 24-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2359.46 | 28-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1950.60 | 0.00 | ||
Maximum of Months | 6112.02 | 0.00 | 0.00 | 0.00 | 2433.34 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 52335.68 | 07-JAN-08:09 | 31277.33 | 10112.62 | 6311.00 | 0.00 | 2982.79 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 50079.40 | 11-FEB-15:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2868.33 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 50070.80 | 02-MAR-15:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2868.33 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 50827.89 | 29-APR-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2868.33 | 0.00 | 0.00 | 857.55 | 0.00 |
May | 50837.55 | 22-MAY-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2868.33 | 0.00 | 0.00 | 874.55 | 0.00 |
June | 52962.24 | 13-JUN-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2868.33 | 0.00 | 0.00 | 3006.02 | 0.00 |
July | 55849.45 | 22-JUL-14:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2868.33 | 0.00 | 0.00 | 5902.11 | 0.00 |
August | 51911.15 | 14-AUG-14:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2868.33 | 0.00 | 0.00 | 1965.49 | 0.00 |
September | 51215.67 | 13-SEP-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2868.33 | 0.00 | 0.00 | 1267.58 | 0.00 |
October | 50360.87 | 07-OCT-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 2868.33 | 0.00 | 0.00 | 407.82 | 0.00 |
November | 52183.89 | 30-NOV-16:30 | 31277.33 | 10112.62 | 6311.00 | 0.00 | 2868.33 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 52335.01 | 29-DEC-08:09 | 31277.33 | 10112.62 | 6311.00 | 0.00 | 2982.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 50070.80 | 31277.33 | 10112.62 | 0.00 | 0.00 | 2868.33 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55849.45 | 35189.04 | 10112.62 | 6311.00 | 0.00 | 2982.79 | 0.00 | 0.00 | 5902.11 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 108027.98 | 10-JAN-06:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 74445.09 | 18-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 46115.58 | 04-MAR-06:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 34657.29 | 11-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 27121.31 | 05-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 12330.10 | 08-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 8473.10 | 05-JUL-06:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 3732.47 | 24-AUG-06:19 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 10300.24 | 21-SEP-06:19 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 27542.24 | 23-OCT-05:19 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 75206.40 | 28-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 97412.77 | 28-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 3732.47 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 108027.98 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.50 | 19.32 | 8.83 | 19.65 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7.83 | 19.72 | 7.83 | 19.72 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9.00 | 19.88 | 9.00 | 19.88 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5.83 | 20.22 | 5.83 | 20.22 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4.67 | 20.34 | 4.67 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.17 | 20.41 | 0.17 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.17 | 20.52 | 0.17 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5.50 | 20.24 | 5.50 | 20.24 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7.83 | 19.96 | 7.83 | 19.96 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9.50 | 19.23 | 8.67 | 19.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.00 | 19.78 | 58.50 | 19.91 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.50 | 20.52 | 9.00 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.50 | 14.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 50.33 | 14.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18.50 | 14.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2.00 | 14.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1.83 | 14.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5.17 | 14.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 38.33 | 14.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 76.33 | 14.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 234.00 | 14.79 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 76.33 | 14.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
February | 276.00 | 21.06 | 276.00 | 21.06 | 276.00 | 21.06 |
March | 324.00 | 21.07 | 324.00 | 21.07 | 324.00 | 21.07 |
April | 300.00 | 21.70 | 206.00 | 21.16 | 206.00 | 21.16 |
May | 312.00 | 21.96 | 144.33 | 21.12 | 144.33 | 21.12 |
June | 285.17 | 23.03 | 21.00 | 21.74 | 16.50 | 21.15 |
July | 184.33 | 23.34 | 35.67 | 23.53 | 4.67 | 21.07 |
August | 226.00 | 23.47 | 10.67 | 23.90 | 0.00 | 0.00 |
September | 287.00 | 23.14 | 13.67 | 21.08 | 13.67 | 21.08 |
October | 300.00 | 21.49 | 206.50 | 21.10 | 206.50 | 21.10 |
November | 288.00 | 21.07 | 286.50 | 21.07 | 286.50 | 21.07 |
December | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
Annual Sum or Average | 3382.50 | 21.87 | 2124.33 | 21.14 | 2078.17 | 21.08 |
Minimum of Months | 184.33 | 21.05 | 10.67 | 21.05 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 23.47 | 324.00 | 23.90 | 324.00 | 21.16 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.142318E+09 | 34548411.19 | 24.00 | 0.142296E+09 | 21992.18 | 0.00 | 0.29 | 29-APR-15:50 | 0.00 | 01-APR-00:05 | 3754.28 | 29-APR-15:50 | 3754.28 | 29-APR-15:50 | 8.36 | 28-APR-10:10 | 895.90 | 29-APR-15:50 | 0.00 | 01-APR-00:05 |
May | 0.235326E+09 | 57075363.25 | 39.58 | 0.216271E+09 | 19055045.73 | 0.00 | 0.28 | 22-MAY-16:00 | 0.00 | 01-MAY-00:10 | 3860.85 | 22-MAY-16:00 | 3580.01 | 22-MAY-16:00 | 451.63 | 23-MAY-16:00 | 919.05 | 22-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.135638E+10 | 0.325730E+09 | 155.03 | 0.120147E+10 | 0.154910E+09 | 0.00 | 0.51 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 | 7133.98 | 13-JUN-16:00 | 6472.68 | 13-JUN-16:00 | 1335.32 | 27-JUN-07:30 | 1710.12 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.259879E+10 | 0.621215E+09 | 215.79 | 0.232205E+10 | 0.276744E+09 | 0.00 | 1.00 | 24-JUL-05:03 | 0.00 | 01-JUL-00:10 | 15823.62 | 24-JUL-05:03 | 13085.54 | 24-JUL-05:03 | 2738.08 | 24-JUL-05:03 | 3330.26 | 24-JUL-05:03 | 0.00 | 01-JUL-00:10 |
August | 0.293454E+10 | 0.699513E+09 | 251.81 | 0.261954E+10 | 0.315000E+09 | 0.00 | 0.48 | 14-AUG-16:00 | 0.00 | 01-AUG-00:10 | 6582.27 | 14-AUG-16:00 | 6332.81 | 14-AUG-16:00 | 988.92 | 17-AUG-12:20 | 1576.76 | 14-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.131041E+10 | 0.315468E+09 | 165.39 | 0.117860E+10 | 0.131806E+09 | 0.00 | 0.40 | 13-SEP-16:00 | 0.00 | 01-SEP-00:10 | 5636.28 | 13-SEP-16:00 | 5096.99 | 13-SEP-16:00 | 726.42 | 12-SEP-14:20 | 1315.30 | 13-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 16615368.59 | 4085306.22 | 6.67 | 16612094.93 | 3273.66 | 0.00 | 0.14 | 07-OCT-15:40 | 0.00 | 01-OCT-00:10 | 1729.98 | 07-OCT-15:40 | 1729.98 | 07-OCT-15:40 | 1.99 | 02-OCT-15:40 | 422.62 | 07-OCT-15:40 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.859438E+10 | 0.205763E+10 | 858.26 | 0.769684E+10 | 0.897541E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.293454E+10 | 0.699513E+09 | 251.81 | 0.261954E+10 | 0.315000E+09 | 0.00 | 1.00 | 0.00 | 15823.62 | 13085.54 | 2738.08 | 3330.26 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 55212288.48 | 15419674.70 | 4.00 | 48590417.87 | 6621870.61 | 0.00 | 0.20 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 | 5624.87 | 13-JUN-16:00 | 5032.05 | 13-JUN-16:00 | 712.29 | 13-JUN-15:00 | 1570.44 | 13-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.502985E+09 | 0.141186E+09 | 18.96 | 0.495723E+09 | 7262397.04 | 0.00 | 0.72 | 22-JUL-17:12 | 0.00 | 01-JUL-00:10 | 19736.65 | 22-JUL-17:12 | 19736.65 | 22-JUL-17:12 | 607.07 | 22-JUL-10:30 | 5647.83 | 22-JUL-17:12 | 0.00 | 01-JUL-00:10 |
August | 22261558.34 | 6326487.89 | 8.67 | 21799813.90 | 461744.44 | 0.00 | 0.11 | 14-AUG-16:50 | 0.00 | 01-AUG-00:10 | 2987.84 | 14-AUG-16:50 | 2987.84 | 14-AUG-16:50 | 141.99 | 14-AUG-14:50 | 862.83 | 14-AUG-16:50 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.580459E+09 | 0.162932E+09 | 31.62 | 0.566113E+09 | 14346012.09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.502985E+09 | 0.141186E+09 | 18.96 | 0.495723E+09 | 7262397.04 | 0.00 | 0.72 | 0.00 | 19736.65 | 19736.65 | 712.29 | 5647.83 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.08 | 15.38 | 31.69 | 22.23 | 132.15 | 0.00 | 0.00 | 744.00 |
February | 83.27 | 35.37 | 47.90 | 54.56 | 124.35 | 0.00 | 0.00 | 672.00 |
March | 75.05 | 14.43 | 60.62 | 39.18 | 98.08 | 0.00 | 0.00 | 744.00 |
April | 176.59 | 69.97 | 106.62 | 161.96 | 83.91 | 0.00 | 0.00 | 720.00 |
May | 207.09 | 83.94 | 123.15 | 186.77 | 72.91 | 0.00 | 0.00 | 744.00 |
June | 224.06 | 92.43 | 131.63 | 214.04 | 63.82 | 0.00 | 0.00 | 720.00 |
July | 228.20 | 100.66 | 127.55 | 224.98 | 64.34 | 0.00 | 0.00 | 744.00 |
August | 191.54 | 82.84 | 108.71 | 188.67 | 71.82 | 0.00 | 0.00 | 744.00 |
September | 155.05 | 70.08 | 84.97 | 146.82 | 84.27 | 0.00 | 0.00 | 720.00 |
October | 82.34 | 29.71 | 52.63 | 61.39 | 96.31 | 0.00 | 0.00 | 744.00 |
November | 44.57 | 13.12 | 31.45 | 20.95 | 116.77 | 0.00 | 0.00 | 720.00 |
December | 25.03 | 5.21 | 19.82 | 5.14 | 150.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 128.45 | 51.11 | 77.34 | 110.74 | 96.45 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 25.03 | 5.21 | 19.82 | 5.14 | 63.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 228.20 | 100.66 | 131.63 | 224.98 | 150.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.08 | 15.38 | 31.69 | 22.23 | 132.15 | 0.00 | 0.00 | 744.00 |
February | 83.27 | 35.37 | 47.90 | 54.56 | 124.35 | 0.00 | 0.00 | 672.00 |
March | 75.05 | 14.43 | 60.62 | 39.18 | 98.08 | 0.00 | 0.00 | 744.00 |
April | 176.59 | 69.97 | 106.62 | 161.96 | 83.91 | 0.00 | 0.00 | 720.00 |
May | 207.09 | 83.94 | 123.15 | 186.77 | 72.91 | 0.00 | 0.00 | 744.00 |
June | 224.06 | 92.43 | 131.63 | 214.04 | 63.82 | 0.00 | 0.00 | 720.00 |
July | 228.20 | 100.66 | 127.55 | 224.98 | 64.34 | 0.00 | 0.00 | 744.00 |
August | 191.54 | 82.84 | 108.71 | 188.67 | 71.82 | 0.00 | 0.00 | 744.00 |
September | 155.05 | 70.08 | 84.97 | 146.82 | 84.27 | 0.00 | 0.00 | 720.00 |
October | 82.34 | 29.71 | 52.63 | 61.39 | 96.31 | 0.00 | 0.00 | 744.00 |
November | 44.57 | 13.12 | 31.45 | 20.95 | 116.77 | 0.00 | 0.00 | 720.00 |
December | 25.03 | 5.21 | 19.82 | 5.14 | 150.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 128.45 | 51.11 | 77.34 | 110.74 | 96.45 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 25.03 | 5.21 | 19.82 | 5.14 | 63.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 228.20 | 100.66 | 131.63 | 224.98 | 150.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.74 | 0.00 | 13.74 | 0.76 | 81.61 | 0.00 | 0.00 | 744.00 |
February | 21.45 | 0.00 | 21.45 | 1.80 | 76.12 | 0.00 | 0.00 | 672.00 |
March | 29.69 | 0.00 | 29.69 | 7.65 | 59.89 | 0.00 | 0.00 | 744.00 |
April | 48.40 | 0.26 | 48.14 | 25.91 | 49.67 | 0.00 | 0.00 | 720.00 |
May | 60.68 | 3.13 | 57.55 | 29.62 | 41.16 | 0.00 | 0.00 | 744.00 |
June | 66.61 | 4.07 | 62.54 | 39.37 | 35.58 | 0.00 | 0.00 | 720.00 |
July | 63.32 | 3.57 | 59.75 | 38.66 | 35.90 | 0.00 | 0.00 | 744.00 |
August | 50.03 | 0.97 | 49.06 | 31.31 | 41.56 | 0.00 | 0.00 | 744.00 |
September | 37.93 | 0.02 | 37.91 | 21.07 | 50.30 | 0.00 | 0.00 | 720.00 |
October | 24.29 | 0.00 | 24.29 | 7.77 | 57.49 | 0.00 | 0.00 | 744.00 |
November | 14.59 | 0.00 | 14.59 | 0.96 | 70.10 | 0.00 | 0.00 | 720.00 |
December | 9.94 | 0.00 | 9.94 | 0.01 | 89.09 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 36.79 | 1.01 | 35.78 | 17.15 | 57.29 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 9.94 | 0.00 | 9.94 | 0.01 | 35.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 66.61 | 4.07 | 62.54 | 39.37 | 89.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.74 | 0.00 | 13.74 | 0.76 | 81.61 | 0.00 | 0.00 | 744.00 |
February | 21.45 | 0.00 | 21.45 | 1.80 | 76.12 | 0.00 | 0.00 | 672.00 |
March | 29.68 | 0.00 | 29.68 | 7.65 | 59.89 | 0.00 | 0.00 | 744.00 |
April | 48.39 | 0.26 | 48.13 | 25.91 | 49.67 | 0.00 | 0.00 | 720.00 |
May | 60.68 | 3.13 | 57.54 | 29.61 | 41.16 | 0.00 | 0.00 | 744.00 |
June | 66.61 | 4.07 | 62.54 | 39.37 | 35.58 | 0.00 | 0.00 | 720.00 |
July | 63.32 | 3.57 | 59.75 | 38.65 | 35.90 | 0.00 | 0.00 | 744.00 |
August | 50.03 | 0.97 | 49.06 | 31.31 | 41.56 | 0.00 | 0.00 | 744.00 |
September | 37.93 | 0.02 | 37.91 | 21.07 | 50.30 | 0.00 | 0.00 | 720.00 |
October | 24.29 | 0.00 | 24.29 | 7.77 | 57.49 | 0.00 | 0.00 | 744.00 |
November | 14.59 | 0.00 | 14.59 | 0.96 | 70.10 | 0.00 | 0.00 | 720.00 |
December | 9.94 | 0.00 | 9.94 | 0.01 | 89.09 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 36.79 | 1.01 | 35.78 | 17.15 | 57.28 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 9.94 | 0.00 | 9.94 | 0.01 | 35.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 66.61 | 4.07 | 62.54 | 39.37 | 89.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.15 | 3.40 | 10.75 | 6.37 | 30.82 | 47.00 | 0.00 | 744.00 |
February | 24.96 | 8.31 | 16.66 | 15.83 | 29.65 | 2.67 | 0.00 | 672.00 |
March | 32.21 | 5.99 | 26.22 | 26.60 | 24.08 | 1.50 | 0.00 | 744.00 |
April | 78.72 | 42.16 | 36.56 | 81.07 | 27.13 | 0.00 | 0.00 | 720.00 |
May | 94.93 | 52.74 | 42.19 | 97.47 | 24.47 | 0.00 | 0.00 | 744.00 |
June | 101.20 | 54.92 | 46.28 | 106.27 | 21.54 | 0.00 | 0.00 | 720.00 |
July | 102.65 | 60.09 | 42.56 | 107.61 | 23.92 | 0.00 | 0.00 | 744.00 |
August | 88.20 | 53.42 | 34.79 | 90.53 | 29.22 | 0.00 | 0.00 | 744.00 |
September | 63.99 | 37.85 | 26.14 | 60.42 | 33.22 | 0.00 | 0.00 | 720.00 |
October | 32.46 | 13.85 | 18.60 | 24.24 | 32.70 | 0.17 | 0.00 | 744.00 |
November | 15.64 | 4.13 | 11.51 | 7.09 | 28.83 | 3.67 | 0.00 | 720.00 |
December | 9.88 | 2.07 | 7.81 | 2.71 | 32.16 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 55.05 | 28.34 | 26.72 | 52.36 | 28.14 | 56.17 | 0.00 | 8760.00 |
Minimum of Months | 9.88 | 2.07 | 7.81 | 2.71 | 21.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.65 | 60.09 | 46.28 | 107.61 | 33.22 | 47.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.15 | 3.40 | 10.75 | 6.37 | 30.82 | 47.00 | 0.00 | 744.00 |
February | 24.96 | 8.31 | 16.66 | 15.83 | 29.65 | 2.67 | 0.00 | 672.00 |
March | 32.21 | 5.99 | 26.22 | 26.60 | 24.08 | 1.50 | 0.00 | 744.00 |
April | 78.72 | 42.16 | 36.56 | 81.07 | 27.13 | 0.00 | 0.00 | 720.00 |
May | 94.93 | 52.74 | 42.19 | 97.47 | 24.47 | 0.00 | 0.00 | 744.00 |
June | 101.20 | 54.92 | 46.28 | 106.27 | 21.54 | 0.00 | 0.00 | 720.00 |
July | 102.65 | 60.09 | 42.56 | 107.61 | 23.92 | 0.00 | 0.00 | 744.00 |
August | 88.20 | 53.42 | 34.79 | 90.53 | 29.22 | 0.00 | 0.00 | 744.00 |
September | 63.99 | 37.85 | 26.14 | 60.42 | 33.22 | 0.00 | 0.00 | 720.00 |
October | 32.46 | 13.85 | 18.60 | 24.24 | 32.70 | 0.17 | 0.00 | 744.00 |
November | 15.64 | 4.13 | 11.51 | 7.09 | 28.83 | 3.67 | 0.00 | 720.00 |
December | 9.88 | 2.07 | 7.81 | 2.71 | 32.16 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 55.05 | 28.34 | 26.72 | 52.36 | 28.14 | 56.17 | 0.00 | 8760.00 |
Minimum of Months | 9.88 | 2.07 | 7.81 | 2.71 | 21.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.65 | 60.09 | 46.28 | 107.61 | 33.22 | 47.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.15 | 3.40 | 10.75 | 6.37 | 30.82 | 47.00 | 0.00 | 744.00 |
February | 24.96 | 8.31 | 16.66 | 15.83 | 29.65 | 2.67 | 0.00 | 672.00 |
March | 32.21 | 5.99 | 26.22 | 26.60 | 24.08 | 1.50 | 0.00 | 744.00 |
April | 78.72 | 42.16 | 36.56 | 81.07 | 27.13 | 0.00 | 0.00 | 720.00 |
May | 94.93 | 52.74 | 42.19 | 97.47 | 24.47 | 0.00 | 0.00 | 744.00 |
June | 101.20 | 54.92 | 46.28 | 106.27 | 21.54 | 0.00 | 0.00 | 720.00 |
July | 102.65 | 60.09 | 42.56 | 107.61 | 23.92 | 0.00 | 0.00 | 744.00 |
August | 88.20 | 53.42 | 34.79 | 90.53 | 29.22 | 0.00 | 0.00 | 744.00 |
September | 63.99 | 37.85 | 26.14 | 60.42 | 33.22 | 0.00 | 0.00 | 720.00 |
October | 32.46 | 13.85 | 18.60 | 24.24 | 32.70 | 0.17 | 0.00 | 744.00 |
November | 15.64 | 4.13 | 11.51 | 7.09 | 28.83 | 3.67 | 0.00 | 720.00 |
December | 9.88 | 2.07 | 7.81 | 2.71 | 32.16 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 55.05 | 28.34 | 26.72 | 52.36 | 28.14 | 56.17 | 0.00 | 8760.00 |
Minimum of Months | 9.88 | 2.07 | 7.81 | 2.71 | 21.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.65 | 60.09 | 46.28 | 107.61 | 33.22 | 47.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.15 | 3.40 | 10.75 | 6.37 | 30.82 | 47.00 | 0.00 | 744.00 |
February | 24.96 | 8.31 | 16.66 | 15.83 | 29.65 | 2.67 | 0.00 | 672.00 |
March | 32.21 | 5.99 | 26.22 | 26.60 | 24.08 | 1.50 | 0.00 | 744.00 |
April | 78.72 | 42.16 | 36.56 | 81.07 | 27.13 | 0.00 | 0.00 | 720.00 |
May | 94.93 | 52.74 | 42.19 | 97.47 | 24.47 | 0.00 | 0.00 | 744.00 |
June | 101.20 | 54.92 | 46.28 | 106.27 | 21.54 | 0.00 | 0.00 | 720.00 |
July | 102.65 | 60.09 | 42.56 | 107.61 | 23.92 | 0.00 | 0.00 | 744.00 |
August | 88.20 | 53.42 | 34.79 | 90.53 | 29.22 | 0.00 | 0.00 | 744.00 |
September | 63.99 | 37.85 | 26.14 | 60.42 | 33.22 | 0.00 | 0.00 | 720.00 |
October | 32.46 | 13.85 | 18.60 | 24.24 | 32.70 | 0.17 | 0.00 | 744.00 |
November | 15.64 | 4.13 | 11.51 | 7.09 | 28.83 | 3.67 | 0.00 | 720.00 |
December | 9.88 | 2.07 | 7.81 | 2.71 | 32.16 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 55.05 | 28.34 | 26.72 | 52.36 | 28.14 | 56.17 | 0.00 | 8760.00 |
Minimum of Months | 9.88 | 2.07 | 7.81 | 2.71 | 21.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.65 | 60.09 | 46.28 | 107.61 | 33.22 | 47.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.15 | 3.40 | 10.75 | 6.37 | 30.82 | 47.00 | 0.00 | 744.00 |
February | 24.96 | 8.31 | 16.66 | 15.83 | 29.65 | 2.67 | 0.00 | 672.00 |
March | 32.21 | 5.99 | 26.22 | 26.60 | 24.08 | 1.50 | 0.00 | 744.00 |
April | 78.72 | 42.16 | 36.56 | 81.07 | 27.13 | 0.00 | 0.00 | 720.00 |
May | 94.93 | 52.74 | 42.19 | 97.47 | 24.47 | 0.00 | 0.00 | 744.00 |
June | 101.20 | 54.92 | 46.28 | 106.27 | 21.54 | 0.00 | 0.00 | 720.00 |
July | 102.65 | 60.09 | 42.56 | 107.61 | 23.92 | 0.00 | 0.00 | 744.00 |
August | 88.20 | 53.42 | 34.79 | 90.53 | 29.22 | 0.00 | 0.00 | 744.00 |
September | 63.99 | 37.85 | 26.14 | 60.42 | 33.22 | 0.00 | 0.00 | 720.00 |
October | 32.46 | 13.85 | 18.60 | 24.24 | 32.70 | 0.17 | 0.00 | 744.00 |
November | 15.64 | 4.13 | 11.51 | 7.09 | 28.83 | 3.67 | 0.00 | 720.00 |
December | 9.88 | 2.07 | 7.81 | 2.71 | 32.16 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 55.05 | 28.34 | 26.72 | 52.36 | 28.14 | 56.17 | 0.00 | 8760.00 |
Minimum of Months | 9.88 | 2.07 | 7.81 | 2.71 | 21.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.65 | 60.09 | 46.28 | 107.61 | 33.22 | 47.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.15 | 3.40 | 10.75 | 6.37 | 30.82 | 47.00 | 0.00 | 744.00 |
February | 24.96 | 8.31 | 16.66 | 15.83 | 29.65 | 2.67 | 0.00 | 672.00 |
March | 32.21 | 5.99 | 26.22 | 26.60 | 24.08 | 1.50 | 0.00 | 744.00 |
April | 78.72 | 42.16 | 36.56 | 81.07 | 27.13 | 0.00 | 0.00 | 720.00 |
May | 94.93 | 52.74 | 42.19 | 97.47 | 24.47 | 0.00 | 0.00 | 744.00 |
June | 101.20 | 54.92 | 46.28 | 106.27 | 21.54 | 0.00 | 0.00 | 720.00 |
July | 102.65 | 60.09 | 42.56 | 107.61 | 23.92 | 0.00 | 0.00 | 744.00 |
August | 88.20 | 53.42 | 34.79 | 90.53 | 29.22 | 0.00 | 0.00 | 744.00 |
September | 63.99 | 37.85 | 26.14 | 60.42 | 33.22 | 0.00 | 0.00 | 720.00 |
October | 32.46 | 13.85 | 18.60 | 24.24 | 32.70 | 0.17 | 0.00 | 744.00 |
November | 15.64 | 4.13 | 11.51 | 7.09 | 28.83 | 3.67 | 0.00 | 720.00 |
December | 9.88 | 2.07 | 7.81 | 2.71 | 32.16 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 55.05 | 28.34 | 26.72 | 52.36 | 28.14 | 56.17 | 0.00 | 8760.00 |
Minimum of Months | 9.88 | 2.07 | 7.81 | 2.71 | 21.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.65 | 60.09 | 46.28 | 107.61 | 33.22 | 47.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.15 | 3.40 | 10.75 | 6.37 | 30.82 | 47.00 | 0.00 | 744.00 |
February | 24.96 | 8.31 | 16.66 | 15.83 | 29.65 | 2.67 | 0.00 | 672.00 |
March | 32.21 | 5.99 | 26.22 | 26.60 | 24.08 | 1.50 | 0.00 | 744.00 |
April | 78.72 | 42.16 | 36.56 | 81.07 | 27.13 | 0.00 | 0.00 | 720.00 |
May | 94.93 | 52.74 | 42.19 | 97.47 | 24.47 | 0.00 | 0.00 | 744.00 |
June | 101.20 | 54.92 | 46.28 | 106.27 | 21.54 | 0.00 | 0.00 | 720.00 |
July | 102.65 | 60.09 | 42.56 | 107.61 | 23.92 | 0.00 | 0.00 | 744.00 |
August | 88.20 | 53.42 | 34.79 | 90.53 | 29.22 | 0.00 | 0.00 | 744.00 |
September | 63.99 | 37.85 | 26.14 | 60.42 | 33.22 | 0.00 | 0.00 | 720.00 |
October | 32.46 | 13.85 | 18.60 | 24.24 | 32.70 | 0.17 | 0.00 | 744.00 |
November | 15.64 | 4.13 | 11.51 | 7.09 | 28.83 | 3.67 | 0.00 | 720.00 |
December | 9.88 | 2.07 | 7.81 | 2.71 | 32.16 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 55.05 | 28.34 | 26.72 | 52.36 | 28.14 | 56.17 | 0.00 | 8760.00 |
Minimum of Months | 9.88 | 2.07 | 7.81 | 2.71 | 21.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.65 | 60.09 | 46.28 | 107.61 | 33.22 | 47.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.15 | 3.40 | 10.75 | 6.37 | 30.82 | 47.00 | 0.00 | 744.00 |
February | 24.96 | 8.31 | 16.66 | 15.83 | 29.65 | 2.67 | 0.00 | 672.00 |
March | 32.21 | 5.99 | 26.22 | 26.60 | 24.08 | 1.50 | 0.00 | 744.00 |
April | 78.72 | 42.16 | 36.56 | 81.07 | 27.13 | 0.00 | 0.00 | 720.00 |
May | 94.93 | 52.74 | 42.19 | 97.47 | 24.47 | 0.00 | 0.00 | 744.00 |
June | 101.20 | 54.92 | 46.28 | 106.27 | 21.54 | 0.00 | 0.00 | 720.00 |
July | 102.65 | 60.09 | 42.56 | 107.61 | 23.92 | 0.00 | 0.00 | 744.00 |
August | 88.20 | 53.42 | 34.79 | 90.53 | 29.22 | 0.00 | 0.00 | 744.00 |
September | 63.99 | 37.85 | 26.14 | 60.42 | 33.22 | 0.00 | 0.00 | 720.00 |
October | 32.46 | 13.85 | 18.60 | 24.24 | 32.70 | 0.17 | 0.00 | 744.00 |
November | 15.64 | 4.13 | 11.51 | 7.09 | 28.83 | 3.67 | 0.00 | 720.00 |
December | 9.88 | 2.07 | 7.81 | 2.71 | 32.16 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 55.05 | 28.34 | 26.72 | 52.36 | 28.14 | 56.17 | 0.00 | 8760.00 |
Minimum of Months | 9.88 | 2.07 | 7.81 | 2.71 | 21.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.65 | 60.09 | 46.28 | 107.61 | 33.22 | 47.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.15 | 3.40 | 10.75 | 6.37 | 30.82 | 47.00 | 0.00 | 744.00 |
February | 24.96 | 8.31 | 16.66 | 15.83 | 29.65 | 2.67 | 0.00 | 672.00 |
March | 32.21 | 5.99 | 26.22 | 26.60 | 24.08 | 1.50 | 0.00 | 744.00 |
April | 78.72 | 42.16 | 36.56 | 81.07 | 27.13 | 0.00 | 0.00 | 720.00 |
May | 94.93 | 52.74 | 42.19 | 97.47 | 24.47 | 0.00 | 0.00 | 744.00 |
June | 101.20 | 54.92 | 46.28 | 106.27 | 21.54 | 0.00 | 0.00 | 720.00 |
July | 102.65 | 60.09 | 42.56 | 107.61 | 23.92 | 0.00 | 0.00 | 744.00 |
August | 88.20 | 53.42 | 34.79 | 90.53 | 29.22 | 0.00 | 0.00 | 744.00 |
September | 63.99 | 37.85 | 26.14 | 60.42 | 33.22 | 0.00 | 0.00 | 720.00 |
October | 32.46 | 13.85 | 18.60 | 24.24 | 32.70 | 0.17 | 0.00 | 744.00 |
November | 15.64 | 4.13 | 11.51 | 7.09 | 28.83 | 3.67 | 0.00 | 720.00 |
December | 9.88 | 2.07 | 7.81 | 2.71 | 32.16 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 55.05 | 28.34 | 26.72 | 52.36 | 28.14 | 56.17 | 0.00 | 8760.00 |
Minimum of Months | 9.88 | 2.07 | 7.81 | 2.71 | 21.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.65 | 60.09 | 46.28 | 107.61 | 33.22 | 47.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.15 | 3.40 | 10.75 | 6.37 | 30.82 | 47.00 | 0.00 | 744.00 |
February | 24.96 | 8.31 | 16.66 | 15.83 | 29.65 | 2.67 | 0.00 | 672.00 |
March | 32.21 | 5.99 | 26.22 | 26.60 | 24.08 | 1.50 | 0.00 | 744.00 |
April | 78.72 | 42.16 | 36.56 | 81.07 | 27.13 | 0.00 | 0.00 | 720.00 |
May | 94.93 | 52.74 | 42.19 | 97.47 | 24.47 | 0.00 | 0.00 | 744.00 |
June | 101.20 | 54.92 | 46.28 | 106.27 | 21.54 | 0.00 | 0.00 | 720.00 |
July | 102.65 | 60.09 | 42.56 | 107.61 | 23.92 | 0.00 | 0.00 | 744.00 |
August | 88.20 | 53.42 | 34.79 | 90.53 | 29.22 | 0.00 | 0.00 | 744.00 |
September | 63.99 | 37.85 | 26.14 | 60.42 | 33.22 | 0.00 | 0.00 | 720.00 |
October | 32.46 | 13.85 | 18.60 | 24.24 | 32.70 | 0.17 | 0.00 | 744.00 |
November | 15.64 | 4.13 | 11.51 | 7.09 | 28.83 | 3.67 | 0.00 | 720.00 |
December | 9.88 | 2.07 | 7.81 | 2.71 | 32.16 | 1.17 | 0.00 | 744.00 |
Annual Sum or Average | 55.05 | 28.34 | 26.72 | 52.36 | 28.14 | 56.17 | 0.00 | 8760.00 |
Minimum of Months | 9.88 | 2.07 | 7.81 | 2.71 | 21.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 102.65 | 60.09 | 46.28 | 107.61 | 33.22 | 47.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126092E+09 | 41204924.50 | 84886801.74 | 59549164.85 | 0.353957E+09 |
February | 0.201451E+09 | 85573389.59 | 0.115877E+09 | 0.131984E+09 | 0.300816E+09 |
March | 0.201005E+09 | 38641101.58 | 0.162364E+09 | 0.104938E+09 | 0.262693E+09 |
April | 0.457729E+09 | 0.181361E+09 | 0.276368E+09 | 0.419795E+09 | 0.217491E+09 |
May | 0.554673E+09 | 0.224832E+09 | 0.329841E+09 | 0.500249E+09 | 0.195291E+09 |
June | 0.580765E+09 | 0.239577E+09 | 0.341189E+09 | 0.554791E+09 | 0.165418E+09 |
July | 0.611216E+09 | 0.269595E+09 | 0.341621E+09 | 0.602582E+09 | 0.172334E+09 |
August | 0.513028E+09 | 0.221867E+09 | 0.291161E+09 | 0.505321E+09 | 0.192353E+09 |
September | 0.401901E+09 | 0.181659E+09 | 0.220242E+09 | 0.380565E+09 | 0.218420E+09 |
October | 0.220527E+09 | 79566066.80 | 0.140961E+09 | 0.164423E+09 | 0.257969E+09 |
November | 0.115518E+09 | 34010839.60 | 81506837.19 | 54290956.51 | 0.302679E+09 |
December | 67036011.80 | 13950708.21 | 53085303.59 | 13773817.33 | 0.402294E+09 |
Annual Sum or Average | 0.405094E+10 | 0.161184E+10 | 0.243910E+10 | 0.349226E+10 | 0.304172E+10 |
Minimum of Months | 67036011.80 | 13950708.21 | 53085303.59 | 13773817.33 | 0.165418E+09 |
Maximum of Months | 0.611216E+09 | 0.269595E+09 | 0.341621E+09 | 0.602582E+09 | 0.402294E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126092E+09 | 41204924.50 | 84886801.74 | 59549164.85 | 0.353957E+09 |
February | 0.201451E+09 | 85573389.59 | 0.115877E+09 | 0.131984E+09 | 0.300816E+09 |
March | 0.201005E+09 | 38641101.58 | 0.162364E+09 | 0.104938E+09 | 0.262693E+09 |
April | 0.457729E+09 | 0.181361E+09 | 0.276368E+09 | 0.419795E+09 | 0.217491E+09 |
May | 0.554673E+09 | 0.224832E+09 | 0.329841E+09 | 0.500249E+09 | 0.195291E+09 |
June | 0.580765E+09 | 0.239577E+09 | 0.341189E+09 | 0.554791E+09 | 0.165418E+09 |
July | 0.611216E+09 | 0.269595E+09 | 0.341621E+09 | 0.602582E+09 | 0.172334E+09 |
August | 0.513028E+09 | 0.221867E+09 | 0.291161E+09 | 0.505321E+09 | 0.192353E+09 |
September | 0.401901E+09 | 0.181659E+09 | 0.220242E+09 | 0.380565E+09 | 0.218420E+09 |
October | 0.220527E+09 | 79566066.80 | 0.140961E+09 | 0.164423E+09 | 0.257969E+09 |
November | 0.115518E+09 | 34010839.60 | 81506837.19 | 54290956.51 | 0.302679E+09 |
December | 67036011.80 | 13950708.21 | 53085303.59 | 13773817.33 | 0.402294E+09 |
Annual Sum or Average | 0.405094E+10 | 0.161184E+10 | 0.243910E+10 | 0.349226E+10 | 0.304172E+10 |
Minimum of Months | 67036011.80 | 13950708.21 | 53085303.59 | 13773817.33 | 0.165418E+09 |
Maximum of Months | 0.611216E+09 | 0.269595E+09 | 0.341621E+09 | 0.602582E+09 | 0.402294E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36791156.70 | 0.00 | 36791156.70 | 2027305.89 | 0.218579E+09 |
February | 51891179.80 | 0.00 | 51891179.80 | 4360157.77 | 0.184146E+09 |
March | 79510218.25 | 1082.28 | 79509135.97 | 20496228.35 | 0.160416E+09 |
April | 0.125442E+09 | 672185.46 | 0.124770E+09 | 67149215.14 | 0.128750E+09 |
May | 0.162527E+09 | 8394302.97 | 0.154133E+09 | 79325210.53 | 0.110239E+09 |
June | 0.172646E+09 | 10541371.11 | 0.162105E+09 | 0.102050E+09 | 92232012.92 |
July | 0.169605E+09 | 9572638.44 | 0.160033E+09 | 0.103537E+09 | 96165163.05 |
August | 0.133998E+09 | 2586120.74 | 0.131412E+09 | 83855171.55 | 0.111326E+09 |
September | 98322315.72 | 57709.22 | 98264606.49 | 54616540.57 | 0.130377E+09 |
October | 65057880.40 | 0.00 | 65057880.40 | 20818715.85 | 0.153985E+09 |
November | 37829128.19 | 0.00 | 37829128.19 | 2485863.79 | 0.181695E+09 |
December | 26620254.24 | 0.00 | 26620254.24 | 25235.57 | 0.238631E+09 |
Annual Sum or Average | 0.116024E+10 | 31825410.22 | 0.112841E+10 | 0.540747E+09 | 0.180654E+10 |
Minimum of Months | 26620254.24 | 0.00 | 26620254.24 | 25235.57 | 92232012.92 |
Maximum of Months | 0.172646E+09 | 10541371.11 | 0.162105E+09 | 0.103537E+09 | 0.238631E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36789895.72 | 0.00 | 36789895.72 | 2027009.67 | 0.218579E+09 |
February | 51889446.94 | 0.00 | 51889446.94 | 4359504.40 | 0.184147E+09 |
March | 79507385.95 | 1082.23 | 79506303.72 | 20494174.49 | 0.160416E+09 |
April | 0.125438E+09 | 672153.95 | 0.124766E+09 | 67145772.98 | 0.128749E+09 |
May | 0.162522E+09 | 8393909.51 | 0.154128E+09 | 79320788.87 | 0.110239E+09 |
June | 0.172641E+09 | 10540877.02 | 0.162100E+09 | 0.102045E+09 | 92231808.80 |
July | 0.169600E+09 | 9572189.75 | 0.160028E+09 | 0.103533E+09 | 96164890.48 |
August | 0.133994E+09 | 2585999.52 | 0.131408E+09 | 83851746.32 | 0.111326E+09 |
September | 98319441.92 | 57706.52 | 98261735.41 | 54614174.96 | 0.130376E+09 |
October | 65055758.06 | 0.00 | 65055758.06 | 20817253.33 | 0.153984E+09 |
November | 37827828.36 | 0.00 | 37827828.36 | 2485472.88 | 0.181695E+09 |
December | 26619327.93 | 0.00 | 26619327.93 | 25221.52 | 0.238630E+09 |
Annual Sum or Average | 0.116020E+10 | 31823918.52 | 0.112838E+10 | 0.540719E+09 | 0.180654E+10 |
Minimum of Months | 26619327.93 | 0.00 | 26619327.93 | 25221.52 | 92231808.80 |
Maximum of Months | 0.172641E+09 | 10540877.02 | 0.162100E+09 | 0.103533E+09 | 0.238630E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37905444.23 | 9101672.39 | 28803771.84 | 17061663.57 | 82539833.32 |
February | 60393569.87 | 20098472.06 | 40295097.81 | 38300733.48 | 71730872.73 |
March | 86281033.05 | 16043003.32 | 70238029.73 | 71250936.47 | 64498352.99 |
April | 0.204044E+09 | 0.109291E+09 | 94753445.94 | 0.210130E+09 | 70333538.18 |
May | 0.254247E+09 | 0.141247E+09 | 0.113000E+09 | 0.261066E+09 | 65538719.21 |
June | 0.262301E+09 | 0.142344E+09 | 0.119957E+09 | 0.275461E+09 | 55819286.32 |
July | 0.274945E+09 | 0.160950E+09 | 0.113995E+09 | 0.288233E+09 | 64061733.32 |
August | 0.236248E+09 | 0.143067E+09 | 93180774.06 | 0.242472E+09 | 78262129.89 |
September | 0.165854E+09 | 98109706.64 | 67744235.98 | 0.156610E+09 | 86118853.03 |
October | 86938865.76 | 37109153.57 | 49829712.19 | 64928493.00 | 87584301.96 |
November | 40549651.45 | 10711270.07 | 29838381.38 | 18369413.50 | 74734466.56 |
December | 26457630.01 | 5550370.93 | 20907259.09 | 7261146.37 | 86139942.49 |
Annual Sum or Average | 0.173617E+10 | 0.893623E+09 | 0.842543E+09 | 0.165115E+10 | 0.887362E+09 |
Minimum of Months | 26457630.01 | 5550370.93 | 20907259.09 | 7261146.37 | 55819286.32 |
Maximum of Months | 0.274945E+09 | 0.160950E+09 | 0.119957E+09 | 0.288233E+09 | 87584301.96 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37905444.23 | 9101672.39 | 28803771.84 | 17061663.57 | 82539833.32 |
February | 60393569.87 | 20098472.06 | 40295097.81 | 38300733.48 | 71730872.73 |
March | 86281033.05 | 16043003.32 | 70238029.73 | 71250936.47 | 64498352.99 |
April | 0.204044E+09 | 0.109291E+09 | 94753445.94 | 0.210130E+09 | 70333538.18 |
May | 0.254247E+09 | 0.141247E+09 | 0.113000E+09 | 0.261066E+09 | 65538719.21 |
June | 0.262301E+09 | 0.142344E+09 | 0.119957E+09 | 0.275461E+09 | 55819286.32 |
July | 0.274945E+09 | 0.160950E+09 | 0.113995E+09 | 0.288233E+09 | 64061733.32 |
August | 0.236248E+09 | 0.143067E+09 | 93180774.06 | 0.242472E+09 | 78262129.89 |
September | 0.165854E+09 | 98109706.64 | 67744235.98 | 0.156610E+09 | 86118853.03 |
October | 86938865.76 | 37109153.57 | 49829712.19 | 64928493.00 | 87584301.96 |
November | 40549651.45 | 10711270.07 | 29838381.38 | 18369413.50 | 74734466.56 |
December | 26457630.01 | 5550370.93 | 20907259.09 | 7261146.37 | 86139942.49 |
Annual Sum or Average | 0.173617E+10 | 0.893623E+09 | 0.842543E+09 | 0.165115E+10 | 0.887362E+09 |
Minimum of Months | 26457630.01 | 5550370.93 | 20907259.09 | 7261146.37 | 55819286.32 |
Maximum of Months | 0.274945E+09 | 0.160950E+09 | 0.119957E+09 | 0.288233E+09 | 87584301.96 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37905444.23 | 9101672.39 | 28803771.84 | 17061663.57 | 82539833.32 |
February | 60393569.87 | 20098472.06 | 40295097.81 | 38300733.48 | 71730872.73 |
March | 86281033.05 | 16043003.32 | 70238029.73 | 71250936.47 | 64498352.99 |
April | 0.204044E+09 | 0.109291E+09 | 94753445.94 | 0.210130E+09 | 70333538.18 |
May | 0.254247E+09 | 0.141247E+09 | 0.113000E+09 | 0.261066E+09 | 65538719.21 |
June | 0.262301E+09 | 0.142344E+09 | 0.119957E+09 | 0.275461E+09 | 55819286.32 |
July | 0.274945E+09 | 0.160950E+09 | 0.113995E+09 | 0.288233E+09 | 64061733.32 |
August | 0.236248E+09 | 0.143067E+09 | 93180774.06 | 0.242472E+09 | 78262129.89 |
September | 0.165854E+09 | 98109706.64 | 67744235.98 | 0.156610E+09 | 86118853.03 |
October | 86938865.76 | 37109153.57 | 49829712.19 | 64928493.00 | 87584301.96 |
November | 40549651.45 | 10711270.07 | 29838381.38 | 18369413.50 | 74734466.56 |
December | 26457630.01 | 5550370.93 | 20907259.09 | 7261146.37 | 86139942.49 |
Annual Sum or Average | 0.173617E+10 | 0.893623E+09 | 0.842543E+09 | 0.165115E+10 | 0.887362E+09 |
Minimum of Months | 26457630.01 | 5550370.93 | 20907259.09 | 7261146.37 | 55819286.32 |
Maximum of Months | 0.274945E+09 | 0.160950E+09 | 0.119957E+09 | 0.288233E+09 | 87584301.96 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37905444.23 | 9101672.39 | 28803771.84 | 17061663.57 | 82539833.32 |
February | 60393569.87 | 20098472.06 | 40295097.81 | 38300733.48 | 71730872.73 |
March | 86281033.05 | 16043003.32 | 70238029.73 | 71250936.47 | 64498352.99 |
April | 0.204044E+09 | 0.109291E+09 | 94753445.94 | 0.210130E+09 | 70333538.18 |
May | 0.254247E+09 | 0.141247E+09 | 0.113000E+09 | 0.261066E+09 | 65538719.21 |
June | 0.262301E+09 | 0.142344E+09 | 0.119957E+09 | 0.275461E+09 | 55819286.32 |
July | 0.274945E+09 | 0.160950E+09 | 0.113995E+09 | 0.288233E+09 | 64061733.32 |
August | 0.236248E+09 | 0.143067E+09 | 93180774.06 | 0.242472E+09 | 78262129.89 |
September | 0.165854E+09 | 98109706.64 | 67744235.98 | 0.156610E+09 | 86118853.03 |
October | 86938865.76 | 37109153.57 | 49829712.19 | 64928493.00 | 87584301.96 |
November | 40549651.45 | 10711270.07 | 29838381.38 | 18369413.50 | 74734466.56 |
December | 26457630.01 | 5550370.93 | 20907259.09 | 7261146.37 | 86139942.49 |
Annual Sum or Average | 0.173617E+10 | 0.893623E+09 | 0.842543E+09 | 0.165115E+10 | 0.887362E+09 |
Minimum of Months | 26457630.01 | 5550370.93 | 20907259.09 | 7261146.37 | 55819286.32 |
Maximum of Months | 0.274945E+09 | 0.160950E+09 | 0.119957E+09 | 0.288233E+09 | 87584301.96 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37905444.23 | 9101672.39 | 28803771.84 | 17061663.57 | 82539833.32 |
February | 60393569.87 | 20098472.06 | 40295097.81 | 38300733.48 | 71730872.73 |
March | 86281033.05 | 16043003.32 | 70238029.73 | 71250936.47 | 64498352.99 |
April | 0.204044E+09 | 0.109291E+09 | 94753445.94 | 0.210130E+09 | 70333538.18 |
May | 0.254247E+09 | 0.141247E+09 | 0.113000E+09 | 0.261066E+09 | 65538719.21 |
June | 0.262301E+09 | 0.142344E+09 | 0.119957E+09 | 0.275461E+09 | 55819286.32 |
July | 0.274945E+09 | 0.160950E+09 | 0.113995E+09 | 0.288233E+09 | 64061733.32 |
August | 0.236248E+09 | 0.143067E+09 | 93180774.06 | 0.242472E+09 | 78262129.89 |
September | 0.165854E+09 | 98109706.64 | 67744235.98 | 0.156610E+09 | 86118853.03 |
October | 86938865.76 | 37109153.57 | 49829712.19 | 64928493.00 | 87584301.96 |
November | 40549651.45 | 10711270.07 | 29838381.38 | 18369413.50 | 74734466.56 |
December | 26457630.01 | 5550370.93 | 20907259.09 | 7261146.37 | 86139942.49 |
Annual Sum or Average | 0.173617E+10 | 0.893623E+09 | 0.842543E+09 | 0.165115E+10 | 0.887362E+09 |
Minimum of Months | 26457630.01 | 5550370.93 | 20907259.09 | 7261146.37 | 55819286.32 |
Maximum of Months | 0.274945E+09 | 0.160950E+09 | 0.119957E+09 | 0.288233E+09 | 87584301.96 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37905444.23 | 9101672.39 | 28803771.84 | 17061663.57 | 82539833.32 |
February | 60393569.87 | 20098472.06 | 40295097.81 | 38300733.48 | 71730872.73 |
March | 86281033.05 | 16043003.32 | 70238029.73 | 71250936.47 | 64498352.99 |
April | 0.204044E+09 | 0.109291E+09 | 94753445.94 | 0.210130E+09 | 70333538.18 |
May | 0.254247E+09 | 0.141247E+09 | 0.113000E+09 | 0.261066E+09 | 65538719.21 |
June | 0.262301E+09 | 0.142344E+09 | 0.119957E+09 | 0.275461E+09 | 55819286.32 |
July | 0.274945E+09 | 0.160950E+09 | 0.113995E+09 | 0.288233E+09 | 64061733.32 |
August | 0.236248E+09 | 0.143067E+09 | 93180774.06 | 0.242472E+09 | 78262129.89 |
September | 0.165854E+09 | 98109706.64 | 67744235.98 | 0.156610E+09 | 86118853.03 |
October | 86938865.76 | 37109153.57 | 49829712.19 | 64928493.00 | 87584301.96 |
November | 40549651.45 | 10711270.07 | 29838381.38 | 18369413.50 | 74734466.56 |
December | 26457630.01 | 5550370.93 | 20907259.09 | 7261146.37 | 86139942.49 |
Annual Sum or Average | 0.173617E+10 | 0.893623E+09 | 0.842543E+09 | 0.165115E+10 | 0.887362E+09 |
Minimum of Months | 26457630.01 | 5550370.93 | 20907259.09 | 7261146.37 | 55819286.32 |
Maximum of Months | 0.274945E+09 | 0.160950E+09 | 0.119957E+09 | 0.288233E+09 | 87584301.96 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37905444.23 | 9101672.39 | 28803771.84 | 17061663.57 | 82539833.32 |
February | 60393569.87 | 20098472.06 | 40295097.81 | 38300733.48 | 71730872.73 |
March | 86281033.05 | 16043003.32 | 70238029.73 | 71250936.47 | 64498352.99 |
April | 0.204044E+09 | 0.109291E+09 | 94753445.94 | 0.210130E+09 | 70333538.18 |
May | 0.254247E+09 | 0.141247E+09 | 0.113000E+09 | 0.261066E+09 | 65538719.21 |
June | 0.262301E+09 | 0.142344E+09 | 0.119957E+09 | 0.275461E+09 | 55819286.32 |
July | 0.274945E+09 | 0.160950E+09 | 0.113995E+09 | 0.288233E+09 | 64061733.32 |
August | 0.236248E+09 | 0.143067E+09 | 93180774.06 | 0.242472E+09 | 78262129.89 |
September | 0.165854E+09 | 98109706.64 | 67744235.98 | 0.156610E+09 | 86118853.03 |
October | 86938865.76 | 37109153.57 | 49829712.19 | 64928493.00 | 87584301.96 |
November | 40549651.45 | 10711270.07 | 29838381.38 | 18369413.50 | 74734466.56 |
December | 26457630.01 | 5550370.93 | 20907259.09 | 7261146.37 | 86139942.49 |
Annual Sum or Average | 0.173617E+10 | 0.893623E+09 | 0.842543E+09 | 0.165115E+10 | 0.887362E+09 |
Minimum of Months | 26457630.01 | 5550370.93 | 20907259.09 | 7261146.37 | 55819286.32 |
Maximum of Months | 0.274945E+09 | 0.160950E+09 | 0.119957E+09 | 0.288233E+09 | 87584301.96 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37905444.23 | 9101672.39 | 28803771.84 | 17061663.57 | 82539833.32 |
February | 60393569.87 | 20098472.06 | 40295097.81 | 38300733.48 | 71730872.73 |
March | 86281033.05 | 16043003.32 | 70238029.73 | 71250936.47 | 64498352.99 |
April | 0.204044E+09 | 0.109291E+09 | 94753445.94 | 0.210130E+09 | 70333538.18 |
May | 0.254247E+09 | 0.141247E+09 | 0.113000E+09 | 0.261066E+09 | 65538719.21 |
June | 0.262301E+09 | 0.142344E+09 | 0.119957E+09 | 0.275461E+09 | 55819286.32 |
July | 0.274945E+09 | 0.160950E+09 | 0.113995E+09 | 0.288233E+09 | 64061733.32 |
August | 0.236248E+09 | 0.143067E+09 | 93180774.06 | 0.242472E+09 | 78262129.89 |
September | 0.165854E+09 | 98109706.64 | 67744235.98 | 0.156610E+09 | 86118853.03 |
October | 86938865.76 | 37109153.57 | 49829712.19 | 64928493.00 | 87584301.96 |
November | 40549651.45 | 10711270.07 | 29838381.38 | 18369413.50 | 74734466.56 |
December | 26457630.01 | 5550370.93 | 20907259.09 | 7261146.37 | 86139942.49 |
Annual Sum or Average | 0.173617E+10 | 0.893623E+09 | 0.842543E+09 | 0.165115E+10 | 0.887362E+09 |
Minimum of Months | 26457630.01 | 5550370.93 | 20907259.09 | 7261146.37 | 55819286.32 |
Maximum of Months | 0.274945E+09 | 0.160950E+09 | 0.119957E+09 | 0.288233E+09 | 87584301.96 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37905444.23 | 9101672.39 | 28803771.84 | 17061663.57 | 82539833.32 |
February | 60393569.87 | 20098472.06 | 40295097.81 | 38300733.48 | 71730872.73 |
March | 86281033.05 | 16043003.32 | 70238029.73 | 71250936.47 | 64498352.99 |
April | 0.204044E+09 | 0.109291E+09 | 94753445.94 | 0.210130E+09 | 70333538.18 |
May | 0.254247E+09 | 0.141247E+09 | 0.113000E+09 | 0.261066E+09 | 65538719.21 |
June | 0.262301E+09 | 0.142344E+09 | 0.119957E+09 | 0.275461E+09 | 55819286.32 |
July | 0.274945E+09 | 0.160950E+09 | 0.113995E+09 | 0.288233E+09 | 64061733.32 |
August | 0.236248E+09 | 0.143067E+09 | 93180774.06 | 0.242472E+09 | 78262129.89 |
September | 0.165854E+09 | 98109706.64 | 67744235.98 | 0.156610E+09 | 86118853.03 |
October | 86938865.76 | 37109153.57 | 49829712.19 | 64928493.00 | 87584301.96 |
November | 40549651.45 | 10711270.07 | 29838381.38 | 18369413.50 | 74734466.56 |
December | 26457630.01 | 5550370.93 | 20907259.09 | 7261146.37 | 86139942.49 |
Annual Sum or Average | 0.173617E+10 | 0.893623E+09 | 0.842543E+09 | 0.165115E+10 | 0.887362E+09 |
Minimum of Months | 26457630.01 | 5550370.93 | 20907259.09 | 7261146.37 | 55819286.32 |
Maximum of Months | 0.274945E+09 | 0.160950E+09 | 0.119957E+09 | 0.288233E+09 | 87584301.96 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37905444.23 | 9101672.39 | 28803771.84 | 17061663.57 | 82539833.32 |
February | 60393569.87 | 20098472.06 | 40295097.81 | 38300733.48 | 71730872.73 |
March | 86281033.05 | 16043003.32 | 70238029.73 | 71250936.47 | 64498352.99 |
April | 0.204044E+09 | 0.109291E+09 | 94753445.94 | 0.210130E+09 | 70333538.18 |
May | 0.254247E+09 | 0.141247E+09 | 0.113000E+09 | 0.261066E+09 | 65538719.21 |
June | 0.262301E+09 | 0.142344E+09 | 0.119957E+09 | 0.275461E+09 | 55819286.32 |
July | 0.274945E+09 | 0.160950E+09 | 0.113995E+09 | 0.288233E+09 | 64061733.32 |
August | 0.236248E+09 | 0.143067E+09 | 93180774.06 | 0.242472E+09 | 78262129.89 |
September | 0.165854E+09 | 98109706.64 | 67744235.98 | 0.156610E+09 | 86118853.03 |
October | 86938865.76 | 37109153.57 | 49829712.19 | 64928493.00 | 87584301.96 |
November | 40549651.45 | 10711270.07 | 29838381.38 | 18369413.50 | 74734466.56 |
December | 26457630.01 | 5550370.93 | 20907259.09 | 7261146.37 | 86139942.49 |
Annual Sum or Average | 0.173617E+10 | 0.893623E+09 | 0.842543E+09 | 0.165115E+10 | 0.887362E+09 |
Minimum of Months | 26457630.01 | 5550370.93 | 20907259.09 | 7261146.37 | 55819286.32 |
Maximum of Months | 0.274945E+09 | 0.160950E+09 | 0.119957E+09 | 0.288233E+09 | 87584301.96 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 39.64 | 421.18 | 121.63 | 30.77 | 90.86 | 0.00 | 0.00 |
February | 106.83 | 395.04 | 209.44 | 70.75 | 138.70 | 0.00 | 0.00 |
March | 90.14 | 312.41 | 209.46 | 28.85 | 180.61 | 0.00 | 0.00 |
April | 373.36 | 264.80 | 449.98 | 140.46 | 309.52 | 0.00 | 0.00 |
May | 431.24 | 226.61 | 535.54 | 174.15 | 361.39 | 0.00 | 0.00 |
June | 505.30 | 197.28 | 581.33 | 192.99 | 388.34 | 0.00 | 0.00 |
July | 525.68 | 198.90 | 583.05 | 208.46 | 374.59 | 0.00 | 0.00 |
August | 438.64 | 225.45 | 483.14 | 167.60 | 315.54 | 0.00 | 0.00 |
September | 333.26 | 266.61 | 385.97 | 140.21 | 245.76 | 0.00 | 0.00 |
October | 135.86 | 305.15 | 213.25 | 59.41 | 153.84 | 0.00 | 0.00 |
November | 40.38 | 370.32 | 118.32 | 26.24 | 92.08 | 0.00 | 0.00 |
December | 7.98 | 476.27 | 69.93 | 10.42 | 59.52 | 0.00 | 0.00 |
Annual Sum or Average | 252.89 | 304.59 | 330.49 | 104.24 | 226.25 | 0.00 | 0.00 |
Minimum of Months | 7.98 | 197.28 | 69.93 | 10.42 | 59.52 | 0.00 | 0.00 |
Maximum of Months | 525.68 | 476.27 | 583.05 | 208.46 | 388.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 63.70 | 308.17 | 141.52 | 33.98 | 107.54 | 0.00 | 0.00 |
February | 158.32 | 296.51 | 249.64 | 83.08 | 166.56 | 0.00 | 0.00 |
March | 266.02 | 240.81 | 322.14 | 59.90 | 262.24 | 0.00 | 0.00 |
April | 810.69 | 271.35 | 787.21 | 421.65 | 365.56 | 0.00 | 0.00 |
May | 974.71 | 244.69 | 949.25 | 527.36 | 421.89 | 0.00 | 0.00 |
June | 1062.73 | 215.35 | 1011.97 | 549.17 | 462.80 | 0.00 | 0.00 |
July | 1076.14 | 239.18 | 1026.53 | 600.92 | 425.61 | 0.00 | 0.00 |
August | 905.29 | 292.20 | 882.05 | 534.15 | 347.90 | 0.00 | 0.00 |
September | 604.21 | 332.25 | 639.87 | 378.51 | 261.36 | 0.00 | 0.00 |
October | 242.42 | 327.00 | 324.59 | 138.55 | 186.04 | 0.00 | 0.00 |
November | 70.87 | 288.33 | 156.44 | 41.32 | 115.12 | 0.00 | 0.00 |
December | 27.11 | 321.61 | 98.78 | 20.72 | 78.06 | 0.00 | 0.00 |
Annual Sum or Average | 523.57 | 281.38 | 550.53 | 283.37 | 267.17 | 0.00 | 0.00 |
Minimum of Months | 27.11 | 215.35 | 98.78 | 20.72 | 78.06 | 0.00 | 0.00 |
Maximum of Months | 1076.14 | 332.25 | 1026.53 | 600.92 | 462.80 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.106182E+09 | 0.112810E+10 | 0.325765E+09 | 82409848.99 | 0.243355E+09 | 0.00 | 0.00 |
February | 0.258438E+09 | 0.955677E+09 | 0.506682E+09 | 0.171147E+09 | 0.335535E+09 | 0.00 | 0.00 |
March | 0.241419E+09 | 0.836771E+09 | 0.561028E+09 | 77284367.67 | 0.483744E+09 | 0.00 | 0.00 |
April | 0.967754E+09 | 0.686349E+09 | 0.116634E+10 | 0.364067E+09 | 0.802271E+09 | 0.00 | 0.00 |
May | 0.115503E+10 | 0.606948E+09 | 0.143439E+10 | 0.466452E+09 | 0.967942E+09 | 0.00 | 0.00 |
June | 0.130974E+10 | 0.511360E+09 | 0.150682E+10 | 0.500235E+09 | 0.100658E+10 | 0.00 | 0.00 |
July | 0.140798E+10 | 0.532744E+09 | 0.156164E+10 | 0.558335E+09 | 0.100330E+10 | 0.00 | 0.00 |
August | 0.117485E+10 | 0.603854E+09 | 0.129405E+10 | 0.448906E+09 | 0.845141E+09 | 0.00 | 0.00 |
September | 0.863815E+09 | 0.691046E+09 | 0.100044E+10 | 0.363434E+09 | 0.637010E+09 | 0.00 | 0.00 |
October | 0.363881E+09 | 0.817305E+09 | 0.571168E+09 | 0.159132E+09 | 0.412036E+09 | 0.00 | 0.00 |
November | 0.104665E+09 | 0.959860E+09 | 0.306692E+09 | 68021679.19 | 0.238671E+09 | 0.00 | 0.00 |
December | 21383346.83 | 0.127563E+10 | 0.187312E+09 | 27901416.42 | 0.159410E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.797513E+10 | 0.960565E+10 | 0.104223E+11 | 0.328733E+10 | 0.713500E+10 | 0.00 | 0.00 |
Minimum of Months | 21383346.83 | 0.511360E+09 | 0.187312E+09 | 27901416.42 | 0.159410E+09 | 0.00 | 0.00 |
Maximum of Months | 0.140798E+10 | 0.127563E+10 | 0.156164E+10 | 0.558335E+09 | 0.100658E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.170615E+09 | 0.825398E+09 | 0.379054E+09 | 91016723.91 | 0.288038E+09 | 0.00 | 0.00 |
February | 0.383006E+09 | 0.717309E+09 | 0.603936E+09 | 0.200985E+09 | 0.402951E+09 | 0.00 | 0.00 |
March | 0.712508E+09 | 0.644984E+09 | 0.862810E+09 | 0.160430E+09 | 0.702380E+09 | 0.00 | 0.00 |
April | 0.210130E+10 | 0.703335E+09 | 0.204044E+10 | 0.109291E+10 | 0.947534E+09 | 0.00 | 0.00 |
May | 0.261066E+10 | 0.655387E+09 | 0.254247E+10 | 0.141247E+10 | 0.113000E+10 | 0.00 | 0.00 |
June | 0.275461E+10 | 0.558193E+09 | 0.262301E+10 | 0.142344E+10 | 0.119957E+10 | 0.00 | 0.00 |
July | 0.288233E+10 | 0.640616E+09 | 0.274945E+10 | 0.160950E+10 | 0.113995E+10 | 0.00 | 0.00 |
August | 0.242472E+10 | 0.782621E+09 | 0.236248E+10 | 0.143067E+10 | 0.931808E+09 | 0.00 | 0.00 |
September | 0.156610E+10 | 0.861188E+09 | 0.165854E+10 | 0.981097E+09 | 0.677442E+09 | 0.00 | 0.00 |
October | 0.649285E+09 | 0.875842E+09 | 0.869389E+09 | 0.371092E+09 | 0.498297E+09 | 0.00 | 0.00 |
November | 0.183694E+09 | 0.747345E+09 | 0.405497E+09 | 0.107113E+09 | 0.298384E+09 | 0.00 | 0.00 |
December | 72610235.79 | 0.861399E+09 | 0.264576E+09 | 55503709.26 | 0.209073E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.165114E+11 | 0.887362E+10 | 0.173617E+11 | 0.893623E+10 | 0.842543E+10 | 0.00 | 0.00 |
Minimum of Months | 72610235.79 | 0.558193E+09 | 0.264576E+09 | 55503709.26 | 0.209073E+09 | 0.00 | 0.00 |
Maximum of Months | 0.288233E+10 | 0.875842E+09 | 0.274945E+10 | 0.160950E+10 | 0.119957E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.24 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -2.0 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.23 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.06 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.26 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.48 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.74 | 10.65 | 2.92 | 3.94 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.42 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.65 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.74 | 10.65 | 3.35 | 4.48 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.36 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.21 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.10 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.06 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.51 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.77 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.15 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.21 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.08 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.62 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.62 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.51 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -6.9 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.8 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.04 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.4 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -6.9 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.06 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.29 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.04 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.53 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.00 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.94 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.44 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.53 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.955989E+09 | -869201990.2 | 0.00 | 0.00 | 744.00 | 0.00 | -86786728.0 | 58.99 | 0.00 | 0.00 |
February | 0.882157E+09 | -803824440.4 | 0.00 | 0.00 | 672.00 | 0.00 | -78332971.8 | 58.99 | 0.00 | 0.00 |
March | 0.101904E+10 | -933233271.7 | 0.00 | 0.00 | 744.00 | 0.00 | -85802498.3 | 59.00 | 0.00 | 0.00 |
April | 0.930606E+09 | -850510834.1 | 0.00 | 0.00 | 720.00 | 0.00 | -80095588.9 | 58.99 | 0.00 | 0.00 |
May | 0.942720E+09 | -860905324.4 | 0.00 | 0.00 | 744.00 | 0.00 | -81814426.0 | 58.99 | 0.00 | 0.00 |
June | 0.909605E+09 | -834448190.3 | 0.00 | 0.00 | 720.00 | 0.00 | -75156516.7 | 58.99 | 0.00 | 0.00 |
July | 0.865293E+09 | -789596555.6 | 0.00 | 0.00 | 744.00 | 0.00 | -75696880.7 | 58.99 | 0.00 | 0.00 |
August | 0.916729E+09 | -841419646.8 | 0.00 | 0.00 | 744.00 | 0.00 | -75308990.9 | 58.99 | 0.00 | 0.00 |
September | 0.863319E+09 | -787975613.2 | 0.00 | 0.00 | 720.00 | 0.00 | -75343669.6 | 58.99 | 0.00 | 0.00 |
October | 0.890462E+09 | -806758366.8 | 0.00 | 0.00 | 744.00 | 0.00 | -83703238.5 | 58.99 | 0.00 | 0.00 |
November | 0.879906E+09 | -796615630.4 | 0.00 | 0.00 | 720.00 | 0.00 | -83290793.7 | 58.99 | 0.00 | 0.00 |
December | 0.938959E+09 | -851918110.4 | 0.00 | 0.00 | 744.00 | 0.00 | -87041056.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.109948E+11 | -.100264E+11 | 8760.00 | -968373359.3 | 58.99 | |||||
Minimum of Months | 0.863319E+09 | -933233271.7 | 0.00 | 0.00 | 672.00 | 0.00 | -87041056.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.101904E+10 | -787975613.2 | 0.00 | 0.00 | 744.00 | 0.00 | -75156516.7 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 195.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 217.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 215.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 417.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 410.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 396.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 234.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 171.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3515.67 | ||||||||||
Minimum of Months | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.576880E+10 | 23742.84 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.481228E+10 | 23742.84 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.489066E+10 | 23742.84 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187697E+10 | 23742.84 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135083E+10 | 23742.84 | 02-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.245403E+09 | 23742.84 | 01-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 65210747.41 | 23742.84 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 25808957.31 | 3870.34 | 24-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.290296E+09 | 23742.84 | 07-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.204756E+10 | 23742.84 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.408724E+10 | 23742.84 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.586644E+10 | 23742.84 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.313275E+11 | |||||||
Minimum of Months | 25808957.31 | 3870.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.586644E+10 | 23742.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.138072E+11 | 59104.46 | 01-JAN-16:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116868E+11 | 59104.46 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.693192E+10 | 59104.46 | 04-MAR-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.585471E+09 | 59104.46 | 03-APR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.406560E+09 | 59104.46 | 09-MAY-05:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150914E+10 | 59104.46 | 26-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.929472E+10 | 59104.46 | 15-NOV-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.196752E+11 | 59104.46 | 02-DEC-18:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.638970E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.196752E+11 | 59104.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100221E+11 | 41005.53 | 10-JAN-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.376991E+10 | 27033.51 | 19-FEB-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 54340209.78 | 8493.00 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104441E+10 | 22889.77 | 29-NOV-03:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173252E+11 | 41940.14 | 30-DEC-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.322159E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.173252E+11 | 41940.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.142318E+09 | 0.142296E+09 | 3754.28 | 29-APR-15:50 | 3754.28 | 0.00 |
May | 0.00 | 0.00 | 0.235326E+09 | 0.216271E+09 | 3860.85 | 22-MAY-16:00 | 3580.01 | 0.00 |
June | 0.00 | 0.00 | 0.135638E+10 | 0.120147E+10 | 7133.98 | 13-JUN-16:00 | 6472.68 | 0.00 |
July | 0.00 | 0.00 | 0.259879E+10 | 0.232205E+10 | 15823.62 | 24-JUL-05:03 | 13085.54 | 0.00 |
August | 0.00 | 0.00 | 0.293454E+10 | 0.261954E+10 | 6582.27 | 14-AUG-16:00 | 6332.81 | 0.00 |
September | 0.00 | 0.00 | 0.131041E+10 | 0.117860E+10 | 5636.28 | 13-SEP-16:00 | 5096.99 | 0.00 |
October | 0.00 | 0.00 | 16615368.59 | 16612094.93 | 1729.98 | 07-OCT-15:40 | 1729.98 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.859438E+10 | 0.769684E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.293454E+10 | 0.261954E+10 | 15823.62 | 13085.54 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 55212288.48 | 48590417.87 | 5624.87 | 13-JUN-16:00 | 5032.05 | 0.00 |
July | 0.00 | 0.00 | 0.502985E+09 | 0.495723E+09 | 19736.65 | 22-JUL-17:12 | 19736.65 | 0.00 |
August | 0.00 | 0.00 | 22261558.34 | 21799813.90 | 2987.84 | 14-AUG-16:50 | 2987.84 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.580459E+09 | 0.566113E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.502985E+09 | 0.495723E+09 | 19736.65 | 19736.65 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.100374E+09 | 0.03 | 114.46 | 01-JAN-00:03 | 0.08 |
February | 49049085.79 | 0.01 | 114.46 | 12-FEB-07:40 | 0.08 |
March | 2106142.63 | 0.00 | 114.46 | 04-MAR-02:00 | 0.08 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 12404493.31 | 0.00 | 114.46 | 19-NOV-24:00 | 0.08 |
December | 0.157079E+09 | 0.04 | 114.46 | 01-DEC-02:40 | 0.08 |
Annual Sum or Average | 0.321013E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.157079E+09 | 0.04 | 114.46 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.106344E+10 | 0.39 | 1035.21 | 02-JAN-07:10 | 0.95 |
February | 0.977545E+09 | 0.39 | 1035.21 | 04-FEB-15:10 | 0.94 |
March | 0.114307E+10 | 0.41 | 1035.21 | 13-MAR-07:50 | 0.95 |
April | 0.104558E+10 | 0.38 | 1035.21 | 20-APR-11:30 | 0.94 |
May | 0.108137E+10 | 0.38 | 1035.21 | 05-MAY-08:50 | 0.94 |
June | 0.106852E+10 | 0.38 | 1035.21 | 12-JUN-16:50 | 0.94 |
July | 0.102640E+10 | 0.35 | 1035.21 | 06-JUL-13:00 | 0.94 |
August | 0.110685E+10 | 0.37 | 1035.21 | 01-AUG-12:00 | 0.94 |
September | 0.102705E+10 | 0.36 | 1035.21 | 07-SEP-15:10 | 0.94 |
October | 0.104564E+10 | 0.37 | 1035.21 | 05-OCT-08:70 | 0.94 |
November | 0.101313E+10 | 0.37 | 1035.21 | 09-NOV-10:20 | 0.94 |
December | 0.106421E+10 | 0.39 | 1035.21 | 04-DEC-11:00 | 0.95 |
Annual Sum or Average | 0.126628E+11 | 0.38 | |||
Minimum of Months | 0.977545E+09 | 0.35 | 1035.21 | 0.94 | |
Maximum of Months | 0.114307E+10 | 0.41 | 1035.21 | 0.95 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.217954E+10 | 0.71 | 1833.12 | 02-JAN-09:50 | 0.91 |
February | 0.202115E+10 | 0.73 | 1833.12 | 02-FEB-08:40 | 0.91 |
March | 0.217187E+10 | 0.64 | 1833.12 | 02-MAR-07:40 | 0.91 |
April | 0.183515E+10 | 0.38 | 1833.12 | 01-APR-06:20 | 0.91 |
May | 0.190164E+10 | 0.37 | 1833.12 | 01-MAY-06:05 | 0.91 |
June | 0.188738E+10 | 0.36 | 1833.12 | 01-JUN-06:10 | 0.90 |
July | 0.181666E+10 | 0.33 | 1833.12 | 01-JUL-06:05 | 0.90 |
August | 0.195997E+10 | 0.36 | 1833.12 | 01-AUG-06:10 | 0.90 |
September | 0.181479E+10 | 0.34 | 1833.12 | 01-SEP-06:10 | 0.90 |
October | 0.186522E+10 | 0.41 | 1833.12 | 02-OCT-06:10 | 0.91 |
November | 0.201145E+10 | 0.62 | 1833.12 | 18-NOV-09:10 | 0.91 |
December | 0.232955E+10 | 0.76 | 1833.12 | 12-DEC-13:20 | 0.91 |
Annual Sum or Average | 0.237944E+11 | 0.50 | |||
Minimum of Months | 0.181479E+10 | 0.33 | 1833.12 | 0.90 | |
Maximum of Months | 0.232955E+10 | 0.76 | 1833.12 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.97 | 0.01 |
February | 2.70 | 0.00 |
March | 2.39 | 0.00 |
April | 0.72 | 1.17 |
May | 1.14 | 2.53 |
June | 2.36 | 3.43 |
July | 2.47 | 3.34 |
August | 2.67 | 3.84 |
September | 1.25 | 2.68 |
October | 1.01 | 1.17 |
November | 2.02 | 0.00 |
December | 2.94 | 0.00 |
Annual Sum or Average | 24.65 | 1.42 |
Minimum of Months | 0.72 | 0.00 |
Maximum of Months | 2.97 | 3.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.08 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.08 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.08 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.106344E+10 | 0.826280E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.977545E+09 | 0.693421E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.114307E+10 | 0.706514E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.108013E+10 | 0.271607E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.113845E+10 | 0.196931E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.139425E+10 | 0.362891E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.164762E+10 | 97308316.99 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.180636E+10 | 39675006.72 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.134252E+10 | 0.431228E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.104973E+10 | 0.297588E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.101313E+10 | 0.591085E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.106421E+10 | 0.843116E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.147205E+11 | 0.451965E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.977545E+09 | 39675006.72 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.180636E+10 | 0.843116E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.217954E+10 | 0.200281E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.202115E+10 | 0.168863E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.217187E+10 | 0.101903E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.183515E+10 | 0.869339E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.190164E+10 | 0.601955E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.190280E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.195784E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.196630E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.181479E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.186522E+10 | 0.223589E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.201145E+10 | 0.134272E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.232955E+10 | 0.282633E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.239573E+11 | 0.925024E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.181479E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.232955E+10 | 0.282633E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.106344E+10 | 0.00 | 0.576880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.977545E+09 | 0.00 | 0.481228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114307E+10 | 0.00 | 0.489066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104558E+10 | 0.142318E+09 | 0.187697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108137E+10 | 0.235326E+09 | 0.135083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.106852E+10 | 0.135638E+10 | 0.245403E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102640E+10 | 0.259879E+10 | 65210747.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110685E+10 | 0.293454E+10 | 25808957.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102705E+10 | 0.131041E+10 | 0.290296E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104564E+10 | 16615368.59 | 0.204756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101313E+10 | 0.00 | 0.408724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106421E+10 | 0.00 | 0.586644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126628E+11 | 0.859438E+10 | 0.313275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.977545E+09 | 0.00 | 25808957.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114307E+10 | 0.293454E+10 | 0.586644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.217954E+10 | 0.00 | 0.138072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202115E+10 | 0.00 | 0.116868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.217187E+10 | 0.00 | 0.693192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183515E+10 | 0.00 | 0.585471E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.190164E+10 | 0.00 | 0.406560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.188738E+10 | 55212288.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.181666E+10 | 0.502985E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.195997E+10 | 22261558.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.181479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186522E+10 | 0.00 | 0.150914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.201145E+10 | 0.00 | 0.929472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.232955E+10 | 0.00 | 0.196752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237944E+11 | 0.580459E+09 | 0.638970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.181479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.232955E+10 | 0.502985E+09 | 0.196752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.106344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.977545E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104558E+10 | 0.00 | 0.00 | 0.00 | 34548411.19 | 0.00 | 0.271607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108137E+10 | 0.00 | 0.00 | 0.00 | 57075363.25 | 0.00 | 0.196931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.106852E+10 | 0.00 | 0.00 | 0.00 | 0.325730E+09 | 0.00 | 0.362891E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102640E+10 | 0.00 | 0.00 | 0.00 | 0.621215E+09 | 0.00 | 97308316.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110685E+10 | 0.00 | 0.00 | 0.00 | 0.699513E+09 | 0.00 | 39675006.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102705E+10 | 0.00 | 0.00 | 0.00 | 0.315468E+09 | 0.00 | 0.431228E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104564E+10 | 0.00 | 0.00 | 0.00 | 4085306.22 | 0.00 | 0.297588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.843116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126628E+11 | 0.00 | 0.00 | 0.00 | 0.205763E+10 | 0.00 | 0.451965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.977545E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39675006.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114307E+10 | 0.00 | 0.00 | 0.00 | 0.699513E+09 | 0.00 | 0.843116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.217954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.217187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.869339E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.190164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.188738E+10 | 0.00 | 0.00 | 0.00 | 15419674.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.181666E+10 | 0.00 | 0.00 | 0.00 | 0.141186E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.195997E+10 | 0.00 | 0.00 | 0.00 | 6326487.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.181479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.201145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.232955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237944E+11 | 0.00 | 0.00 | 0.00 | 0.162932E+09 | 0.00 | 0.925024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.181479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.232955E+10 | 0.00 | 0.00 | 0.00 | 0.141186E+09 | 0.00 | 0.282633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 20432492.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209392E+10 | 0.00 | 0.00 | 0.14 |
February | 15685462.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183010E+10 | 0.00 | 0.00 | 0.14 |
March | 51029836.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194352E+10 | 0.00 | 0.00 | 0.15 |
April | 0.627315E+09 | 0.00 | 0.00 | 196807.75 | 411105.66 | 0.729235E+09 | 84334216.60 | 0.00 | 0.14 |
May | 0.794805E+09 | 83437.84 | 0.00 | 312778.23 | 0.00 | 0.477635E+09 | 0.141100E+09 | 0.00 | 0.14 |
June | 0.482062E+09 | 11787281.01 | 0.00 | 1606383.25 | 0.00 | 88245883.93 | 0.514203E+09 | 0.00 | 0.15 |
July | 0.203973E+09 | 17768495.29 | 0.00 | 3001534.85 | 0.00 | 29244918.14 | 0.560757E+09 | 0.00 | 0.14 |
August | 0.132605E+09 | 997243.59 | 0.00 | 3765102.64 | 0.00 | 27228120.08 | 0.552161E+09 | 0.00 | 0.15 |
September | 0.355807E+09 | 133253.60 | 0.00 | 1694349.32 | 0.00 | 0.109803E+09 | 0.472180E+09 | 0.00 | 0.14 |
October | 0.508607E+09 | 0.00 | 0.00 | 22476.76 | 0.00 | 0.855010E+09 | 29974984.50 | 0.00 | 0.14 |
November | 73835271.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161620E+10 | 0.00 | 0.00 | 0.14 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207631E+10 | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.326616E+10 | 30769711.33 | 0.00 | 10599432.81 | 411105.66 | 0.118764E+11 | 0.235471E+10 | 0.00 | 0.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27228120.08 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.794805E+09 | 17768495.29 | 0.00 | 3765102.64 | 411105.66 | 0.209392E+10 | 0.560757E+09 | 0.00 | 0.15 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.263690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219295E+10 | 0.00 | 0.00 | 0.17 |
February | 0.306463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959904E+09 | 0.00 | 0.00 | 0.18 |
March | 0.378266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524551E+09 | 0.00 | 0.00 | 0.19 |
April | 0.353497E+10 | 0.00 | 0.00 | 0.00 | 7432551.59 | 3090928.74 | 0.00 | 0.00 | 0.18 |
May | 0.363318E+10 | 0.00 | 0.00 | 0.00 | 604311.76 | 4836425.65 | 0.00 | 0.00 | 0.18 |
June | 0.342850E+10 | 0.00 | 0.00 | 101842.81 | 2285334.45 | 0.00 | 46435069.53 | 0.00 | 0.20 |
July | 0.292168E+10 | 10634602.10 | 0.00 | 619300.43 | 2001022.86 | 0.00 | 0.300386E+09 | 0.00 | 0.19 |
August | 0.285920E+10 | 0.00 | 0.00 | 228873.15 | 0.00 | 0.00 | 0.254991E+09 | 0.00 | 0.20 |
September | 0.272108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
October | 0.294148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53489617.16 | 0.00 | 0.00 | 0.18 |
November | 0.278088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766257E+09 | 0.00 | 0.00 | 0.17 |
December | 0.191840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262968E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.362235E+11 | 10634602.10 | 0.00 | 950016.39 | 12323220.65 | 0.713477E+10 | 0.601812E+09 | 0.00 | 0.18 |
Minimum of Months | 0.191840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.378266E+10 | 10634602.10 | 0.00 | 619300.43 | 7432551.59 | 0.262968E+10 | 0.300386E+09 | 0.00 | 0.20 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |