Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2020-06-03 19:11:27
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 980.98 | 202.89 | 202.89 |
Net Site Energy | 980.98 | 202.89 | 202.89 |
Total Source Energy | 3101.62 | 641.48 | 641.48 |
Net Source Energy | 3101.62 | 641.48 | 641.48 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 111.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 99.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 129.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 23.43 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 978.51 | 2.47 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 2.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 111.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 99.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 21.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 107.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 23.43 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 119.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 54.57 | 0.51 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 202.38 | 0.51 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 119.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 54.57 | 0.51 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 202.38 | 0.51 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 978.513 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 978.513 | 100.00 |
Total On-Site and Utility Electric Sources | 978.513 | 100.00 |
Total Electricity End Uses | 978.513 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 3.50 |
Time Setpoint Not Met During Occupied Cooling | 24.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 197.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.6337 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.5069 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.5069 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-14:00 | 02-JAN-06:10 | - | - | - | 11-OCT-11:30 |
Heating | 0.00 | 30928.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 26146.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10595.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1674.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 83718.78 | 30928.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 30928.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 26146.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 8290.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1674.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2.67 | 0.00 | 0.00 | 0.00 |
Cooling | 352.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1507.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 314.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 409.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 74.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3098.95 | 2.67 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.55 | 0.00 | 0.00 | 0.00 |
Cooling | 72.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 84.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 640.92 | 0.55 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.55 | 0.00 | 0.00 | 0.00 |
Cooling | 72.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 84.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 640.92 | 0.55 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.30 |
ZONE2 FINE STORAGE DIRECT AIR | 3.57 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 1.05 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 1.05 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 39686.16 |
PSZ-OFFICE HEATING COIL | 29406.46 |
PSZ-FINE STORAGE HEATING COIL | 102799.66 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 39686.16 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.00 | 1.00 | 1.30 |
PSZ-FINE STORAGE | 3.57 | 3.57 | 3.57 | 3.57 | 3.57 | 3.57 | 1.00 | 1.00 | 3.57 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.30 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 3.57 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.30 | 1.30 | 1.30 | 1.30 | 23211.14 | 29406.46 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 3.57 | 3.57 | 3.57 | 3.57 | 78070.68 | 102799.66 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.30 | 0.649555 | 1.30 | 21740.04 | 23211.14 | 11605.57 | 23211.14 | 0.771629 | 0.771630 | 0.771630 | 0.771630 |
PSZ-FINE STORAGE COOLING COIL | 3.57 | 1.78 | 3.57 | 66090.03 | 78070.68 | 39035.34 | 78070.68 | 0.709069 | 0.709070 | 0.709070 | 0.709070 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.30 | 1481.13 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.57 | 6809.35 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.634 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.707 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.507 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.507 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.507 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.066 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2518.900 | 10.634 | 503.780 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2518.900 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11853.648 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11853.648 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27263.390 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27263.390 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3263 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3263 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.5669 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.5669 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.5669 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.065 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.065 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.665 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.665 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.665 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.38866262E-07 | 0.77198350E-12 | 0.86409618E-13 | 0.0000000 |
2 | 1 | -5.2160226 | 0.42725752E-04 | -0.49098391E-04 | 0.74579932E-08 |
3 | 0 | 5.5423254 | 0.32626013 | 0.32635195 | |
4 | 2 | 0.38866262E-07 | 0.77198350E-12 | 0.86409618E-13 | 0.0000000 |
5 | 1 | -5.2160226 | 0.42725752E-04 | -0.49098391E-04 | 0.74579932E-08 |
6 | 0 | 5.5423254 | 0.32626013 | 0.32635195 | |
7 | 4 | 0.76473447E-12 | 0.16134122E-15 | -0.23523330E-14 | 0.11950429E-15 |
8 | 3 | -0.37912003E-03 | 0.39537906E-06 | -0.54939862E-04 | 0.14674673E-12 |
9 | 2 | 1.7262835 | 0.86963410E-02 | 1.1303724 | -0.72683208E-04 |
10 | 1 | -7.1462370 | 0.22614561 | -17.033763 | 0.33084980 |
11 | 0 | 5.7997145 | 0.14453958 | 16.282827 | |
12 | 4 | 0.76473447E-12 | 0.16134122E-15 | -0.23523330E-14 | 0.11950429E-15 |
13 | 3 | -0.37912003E-03 | 0.39537906E-06 | -0.54939862E-04 | 0.14674673E-12 |
14 | 2 | 1.7262835 | 0.86963410E-02 | 1.1303724 | -0.72683208E-04 |
15 | 1 | -7.1462370 | 0.22614561 | -17.033763 | 0.33084980 |
16 | 0 | 5.7997145 | 0.14453958 | 16.282827 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.23523330E-14 | 0.16134122E-15 | 0.76473447E-12 | 0.11950429E-15 |
85 | 3 | -0.54939862E-04 | 0.39537906E-06 | -0.37912003E-03 | 0.14674673E-12 |
86 | 2 | 1.1303724 | 0.86963410E-02 | 1.7262835 | -0.72683208E-04 |
87 | 1 | -17.033763 | 0.22614561 | -7.1462370 | 0.33084980 |
88 | 0 | 16.282827 | 0.14453958 | 5.7997145 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.73_SHGC_0.25 | 28 | 1 | VerySmooth | 4.149 | 0.255 | 0.127 | 0.250 |
2 | SKYLIGHT_U_0.75_SHGC_0.35 | 29 | 1 | VerySmooth | 4.262 | 0.355 | 0.203 | 0.351 |
3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 30 | 1 | VerySmooth | 4.262 | 0.355 | 0.203 | 0.351 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.12629 | 0.51106 | 0.51106 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 2.73817E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.20312 | 0.36283 | 0.36283 | 0.35000 | 0.14371 | 0.19477 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.20312 | 0.36283 | 0.36283 | 0.35000 | 0.14371 | 0.19477 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11947.22706 | 14336.67247 | 1.08259 | 1.29911 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.57864E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 7875.25025 | 9450.30030 | 0.24337 | 0.29205 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 0.50000 | 4.31558E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 42087.18059 | 50504.61671 | 2.97253 | 3.56704 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.57864E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 20185.51136 | 24222.61363 | 0.52574 | 0.63089 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80000 | 5.57864E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 33071.79816 | 39686.15779 | 0.87715 | 1.05258 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 18671.71 | 1.29911 | 1.29911 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 8397.10 | 0.29205 | 0.29205 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 63314.83 | 3.56704 | 3.56704 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 23964.61 | 0.63089 | 0.63089 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.29911 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.56704 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.05258 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.05258 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 39686.15849 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 39686.15779 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.29911 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.29911 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.29911 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.29911 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.29911 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.29911 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.56704 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.56704 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.56704 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.56704 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.56704 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.56704 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.29911 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.56704 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.29911 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.29911 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.29911 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.29911 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.29911 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.29911 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.64956 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.29911 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21740.04047 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 23211.14000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11605.57000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 23211.14000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.77163 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.77163 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.77163 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.77163 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23211.14000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29406.46324 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.29911 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1481.13242 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 29406.46324 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.56704 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.56704 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.56704 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.56704 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.56704 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.56704 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.78352 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.56704 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 66090.02873 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 78070.68000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 39035.34000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 78070.68000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70907 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70907 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70907 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70907 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 78070.68000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 102799.66080 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.56704 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 6809.34540 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 102799.66080 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 22202.8 | 10.20 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 75299.7 | 12.67 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 10 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 5.6108600861E-002 | 3.9538158628E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.2601136907 | 0.3131094273 | Pass | Pass | 0.1457449711 | 0.6945286041 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 5.2520100683E-002 | 4.0169823101E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.523 | 0.567 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.523 | 0.567 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.523 | 0.567 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.523 | 0.567 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.523 | 0.567 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.523 | 0.567 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.523 | 0.567 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.312 | 0.326 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.523 | 0.567 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.523 | 0.567 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.523 | 0.567 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.312 | 0.326 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.73_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 4.149 | 0.255 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.73_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 4.149 | 0.255 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.73_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 4.149 | 0.255 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.73_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 4.149 | 0.255 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.351 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 4.201 | 0.301 | 0.296 | ||||||||||||
North Total or Average | 6.51 | 4.149 | 0.255 | 0.250 | ||||||||||||
Non-North Total or Average | 26.02 | 4.213 | 0.312 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.6337 | 236.88 | 2518.90 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.62 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.5069 | 1393.41 | 11853.65 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 135.00 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.5069 | 3204.84 | 27263.39 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 310.50 |
Interior Lighting Total | 8.6111 | 4835.13 | 41635.94 | 476.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 6311.00 | AstronomicalClock | - | 83.79 | 83.79 | 99.26 | |
Exterior Lighting Total | 6311.00 | 99.26 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23211.14 | 17910.41 | 5300.73 | 0.77 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 78070.68 | 55357.58 | 22713.10 | 0.71 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 22202.8 | 10.20 | ||||
PSZ-FINE STORAGE COOLING COIL | 75299.7 | 12.67 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 39686.16 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 29406.46 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 102799.66 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.05 | 97.80 | 92.91 | 1.00 | 4.10 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.30 | 1481.13 | 1140.11 | 1.00 | 1.30 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 1110.54 | 3.57 | 6809.35 | 1908.96 | 1.00 | 1.14 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11947.23 | 14336.67 | 60.52 | 1.083 | 1.299 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00801 | 38.94 | 0.00558 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 42087.18 | 50504.62 | 36.25 | 2.973 | 3.567 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 26.70 | 26.70 | 0.00756 | 38.94 | 0.00558 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00416 | 40.80 | 0.00558 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7875.25 | 9450.30 | 39.89 | 0.243 | 0.292 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00777 | 0.50 | 0.00432 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 20185.51 | 24222.61 | 17.38 | 0.526 | 0.631 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15.56 | 15.56 | 0.00664 | 0.50 | 0.00432 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 33071.80 | 39686.16 | 12.38 | 0.877 | 1.053 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00841 | 0.50 | 0.00432 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.30 | 1.30 | 0.29 | 0.29 | 1.2991 | 1.2991 | 1.2991 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.57 | 3.57 | 0.63 | 0.63 | 3.5670 | 3.5670 | 3.5670 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 39686.158 | 39686.158 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 39686.16 | 39686.16 | 1.052583 | 1.18 | 1.18 | 0.00461056 | 43.33 | 25.84 | 0.01600000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 10.00 | 0.00841478 | 100.0000 | 39686.16 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 23211.140 | 0.000 | 1.299110 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23211.14 | 23211.14 | 1.299110 | 25.08 | 15.19 | 0.00782273 | 12.00 | 10.41 | 0.00800000 | 38.94 | 0.00557864 | 17.93 | 7.8735 | 23.90 | 0.00801451 | 39.4335 | 11947.23 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 29406.463 | 29406.463 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 29406.46 | 29406.46 | 1.299114 | 13.83 | 9.70 | 0.00655970 | 40.00 | 20.03 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 7.8734 | 21.10 | 0.00776930 | 45.3368 | 7875.25 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 78070.680 | 0.000 | 3.567040 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 78070.68 | 78070.68 | 3.567040 | 28.16 | 15.82 | 0.00732204 | 12.00 | 10.41 | 0.00800000 | 38.94 | 0.00557864 | 17.93 | 11.9066 | 26.70 | 0.00755768 | 31.5003 | 42087.18 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 102799.661 | 102799.661 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 102799.66 | 102799.66 | 3.567036 | 5.42 | 4.13 | 0.00507479 | 40.00 | 20.03 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 11.9066 | 15.56 | 0.00663867 | 54.9522 | 20185.51 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 39686.158 | 39686.158 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.0932 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 1.052583 | 1.15067768 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 39686.16 | 39686.16 | 1.0000 | 1.15067768 | 1.052583 | 1.18 | 1.18 | 0.00461056 | 12730.0 | 43.33 | 25.84 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39686.16 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 10.00 | 0.00841478 | 10.00 | 0.00841478 | 100.0000 | 39686.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23211.140 | 0.000 | 1.299110 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3821 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23211.14 | 23211.14 | 1.0000 | 1.42017954 | 1.299110 | 25.08 | 15.19 | 0.00782273 | 45134.2 | 12.00 | 10.41 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23211.14 | 38.94 | 0.00557864 | 17.93 | 0.10228487 | 7.8735 | 23.90 | 0.00801451 | 23.90 | 0.00801451 | 39.4335 | 11947.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29406.463 | 29406.463 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.299114 | 1.42018362 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 29406.46 | 29406.46 | 1.0000 | 1.42018362 | 1.299114 | 13.83 | 9.70 | 0.00655970 | 30466.9 | 40.00 | 20.03 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29406.46 | 0.50 | 0.00431558 | 0.50 | 0.10228487 | 7.8734 | 21.01 | 0.00776930 | 21.10 | 0.00776930 | 45.3368 | 7875.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 78070.680 | 0.000 | 3.567040 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4513 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 78070.68 | 78070.68 | 1.0000 | 3.89946750 | 3.567040 | 28.16 | 15.82 | 0.00732204 | 46989.8 | 12.00 | 10.41 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 78070.68 | 38.94 | 0.00557864 | 17.93 | 0.42471267 | 11.9066 | 26.70 | 0.00755768 | 26.70 | 0.00755768 | 31.5003 | 42087.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 102799.661 | 102799.661 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.567036 | 3.89946364 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 102799.66 | 102799.66 | 1.0000 | 3.89946364 | 3.567036 | 5.42 | 4.13 | 0.00507479 | 18190.1 | 40.00 | 20.03 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 102799.66 | 0.50 | 0.00431558 | 0.50 | 0.42471267 | 11.9066 | 15.56 | 0.00663867 | 15.56 | 0.00663867 | 54.9522 | 20185.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE OA CONTROLLER | DifferentialDryBulb | 0.10 | 1.30 | - | |||
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 3.57 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 1571.33 | 1585.17 | 197.50 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 1571.33 | 1585.17 | 197.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 3.50 | 31.17 | 3.50 | 24.00 |
ZONE2 FINE STORAGE | 3.50 | 228.67 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 7.00 | 258.83 | 3.50 | 24.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.960 | 0.375 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 978.51 | 5421.86 | 01-JAN-08:00 | 83718.78 | 28-JUN-15:00 |
Electricity:Building | 637.12 | 4938.86 | 01-JAN-00:10 | 47606.95 | 10-APR-12:50 |
Electricity:Zone:ZONE1 OFFICE | 62.57 | 1027.15 | 01-JAN-00:10 | 3852.05 | 02-JAN-08:10 |
InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.62 | 453.40 | 01-JAN-00:10 | 1939.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 439.56 | 2726.34 | 01-JAN-00:10 | 33679.30 | 10-APR-12:20 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 310.51 | 2726.34 | 01-JAN-00:10 | 23173.88 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 23.43 | 483.00 | 15-APR-18:10 | 1789.39 | 23-JAN-12:40 |
WaterSystems:Electricity | 23.43 | 483.00 | 15-APR-18:10 | 1789.39 | 23-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 23.43 | 483.00 | 15-APR-18:10 | 1789.39 | 23-JAN-12:40 |
Fans:Electricity | 129.19 | 0.00 | 01-JAN-00:40 | 10595.77 | 10-APR-15:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 21.71 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-MAY-12:50 |
Ventilation (simple):Fans:Electricity | 21.71 | 0.00 | 01-JAN-00:10 | 2305.29 | 14-MAY-12:50 |
ElectricityPurchased:Facility | 978.51 | 5421.86 | 08-OCT-10:50 | 83718.78 | 28-JUN-15:00 |
ElectricityPurchased:Plant | 978.51 | 5421.86 | 08-OCT-10:50 | 83718.78 | 28-JUN-15:00 |
Cogeneration:ElectricityPurchased | 978.51 | 5421.86 | 08-OCT-10:50 | 83718.78 | 28-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 978.51 | 5421.86 | 08-OCT-10:50 | 83718.78 | 28-JUN-15:00 |
ElectricityNet:Plant | 978.51 | 5421.86 | 08-OCT-10:50 | 83718.78 | 28-JUN-15:00 |
Cogeneration:ElectricityNet | 978.51 | 5421.86 | 08-OCT-10:50 | 83718.78 | 28-JUN-15:00 |
Electricity:HVAC | 218.70 | 0.00 | 01-JAN-00:40 | 38475.47 | 30-JUN-16:10 |
General:Fans:Electricity | 107.47 | 0.00 | 01-JAN-00:40 | 8290.48 | 10-JAN-14:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 111.23 | 0.00 | 01-JAN-00:10 | 30184.99 | 30-JUN-16:10 |
ExteriorLights:Electricity | 99.26 | 0.00 | 01-JAN-07:30 | 6311.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 99.26 | 0.00 | 01-JAN-07:30 | 6311.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 2.47 | 0.00 | 01-JAN-00:40 | 30928.07 | 02-JAN-06:10 |
Gas:HVAC | 2.47 | 0.00 | 01-JAN-00:40 | 30928.07 | 02-JAN-06:10 |
Heating:Gas | 2.47 | 0.00 | 01-JAN-00:40 | 30928.07 | 02-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 11-OCT-11:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 613.53 | 0.00 | 01-JAN-00:40 | 147020.09 | 30-JUN-16:10 |
EnergyTransfer:Building | 272.48 | 0.00 | 01-JAN-00:40 | 65086.23 | 30-JUN-16:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 69.15 | 0.00 | 01-JAN-00:10 | 15251.80 | 30-JUN-16:10 |
Heating:EnergyTransfer | 20.16 | 0.00 | 01-JAN-00:40 | 26097.49 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 2.27 | 0.00 | 01-JAN-00:10 | 14190.51 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 252.32 | 0.00 | 01-JAN-00:10 | 65086.23 | 30-JUN-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 66.88 | 0.00 | 01-JAN-00:10 | 15251.80 | 30-JUN-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 203.33 | 0.00 | 01-JAN-00:40 | 51303.63 | 30-JUN-16:00 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 17.89 | 0.00 | 01-JAN-00:40 | 19639.12 | 01-JAN-07:30 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 185.44 | 0.00 | 01-JAN-00:10 | 51303.63 | 30-JUN-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 341.06 | 0.00 | 01-JAN-00:40 | 81933.86 | 30-JUN-16:10 |
HeatingCoils:EnergyTransfer | 1.66 | 0.00 | 01-JAN-00:40 | 22429.04 | 02-JAN-06:10 |
CoolingCoils:EnergyTransfer | 339.40 | 0.00 | 01-JAN-00:10 | 81933.86 | 30-JUN-16:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 2.269 | -66.878 | 0.000 | 0.000 | 3.613 | 30.619 | 31.946 | 13.586 | 0.000 | 6.008 | 0.000 | 0.000 | -8.615 | 0.000 | -7.992 | -4.557 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 17.890 | -185.431 | 0.000 | 0.000 | 0.000 | 135.003 | 0.000 | 0.000 | 0.000 | 24.584 | 58.663 | 0.000 | 0.000 | 0.000 | -50.708 | -0.000 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 310.507 | 107.336 | 30.663 | 0.000 | 82.099 | 0.003 | 0.000 | -11.979 | 0.000 | -501.895 | -16.732 |
Total Facility | 0.000 | 0.000 | 20.159 | -252.309 | 0.000 | 0.000 | 3.613 | 476.129 | 139.282 | 44.250 | 0.000 | 112.691 | 58.666 | 0.000 | -20.594 | 0.000 | -560.594 | -21.289 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | -30884.05 | 0.00 | 0.00 | 33.00 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 31354.32 | 0.00 | -828.31 | 0.00 | -828.05 | 0.00 |
ZONE2 FINE STORAGE | 16-APR-11:01 | 0.00 | 0.00 | 0.00 | -76112.40 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 77647.15 | 0.00 | -0.00 | 0.00 | -2720.12 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 20-SEP-05:03 | 0.00 | 0.00 | 0.00 | -92122.19 | 0.00 | 0.00 | 26.05 | 4491.05 | 2623.78 | 0.00 | 0.00 | 0.00 | 86647.24 | 0.00 | -825.69 | 0.00 | -840.24 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 02-JAN-06:01 | 0.00 | 0.00 | 29709.39 | 0.00 | 0.00 | 0.00 | 57.21 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -687.84 | 0.00 | -772.60 | -29459.27 |
ZONE2 FINE STORAGE | 01-JAN-07:23 | 0.00 | 0.00 | 58917.54 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -6258.40 | -53844.51 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 01-JAN-07:23 | 0.00 | 0.00 | 58917.54 | 0.00 | 0.00 | 0.00 | 0.00 | 4365.11 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1655.18 | 0.00 | -25647.75 | -36553.46 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2991 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.2991 | 0.0787 | 1.0000 | 0.1023 | 0.0787 | ||
PSZ-FINE STORAGE | 3.5670 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 3.5670 | 0.1191 | 1.0000 | 0.4247 | 0.1191 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2991 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.2991 | 1.0000 | 1.0000 | 0.1023 | 0.0787 | ||
PSZ-FINE STORAGE | 3.5670 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 3.5670 | 1.0000 | 1.0000 | 0.4247 | 0.1191 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.2991 | 1.2991 | 1.2991 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.5670 | 3.5670 | 3.5670 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2991 | 1.2991 | 1.2991 | 1.2991 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.5670 | 3.5670 | 3.5670 | 3.5670 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.2991 | 1.2991 | 1.2991 | 0.1023 | 0.3502 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.5670 | 3.5670 | 3.5670 | 0.4247 | 0.6732 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2991 | 1.2991 | 1.2991 | 1.2991 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 3.5670 | 3.5670 | 3.5670 | 3.5670 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 3.50 |
Number of hours cooling loads not met | 24.00 |
Number of hours not met | 27.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 2.47 | 30928.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 111.23 | 30184.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 476.13 | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 99.26 | 6311.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 21.71 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 107.47 | 8290.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 23.43 | 1789.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 978.51 |
Natural Gas | 0.00 | 2.47 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 980.98 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 98.47 |
Space Heating | 0.00 |
Space Cooling | 23.00 |
Fans (All) | 26.72 |
Service Water Heating | 4.85 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 202.38 |
Subtotal | 202.38 |
Natural Gas [MJ/m2] | |
Space Heating | 0.51 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.51 |
Subtotal | 0.51 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 48.54 |
Space Heating | 0.25 |
Space Cooling | 11.34 |
Fans (All) | 13.17 |
Service Water Heating | 2.39 |
Receptacle Equipment | 14.20 |
Miscellaneous | 10.12 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.107935E+10 |
February | 0.000 | 0.351280E+09 |
March | 0.000 | 0.308156E+09 |
April | 0.000 | 1029964.508 |
May | 0.000 | 3639870.858 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 5971819.650 |
November | 0.000 | 0.574087E+08 |
December | 0.000 | 0.658441E+09 |
Annual Sum or Average | 0.246528E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.107935E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.107935E+10 |
February | 0.000 | 0.351280E+09 |
March | 0.000 | 0.308156E+09 |
April | 0.000 | 1029964.508 |
May | 0.000 | 3639870.858 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 5971819.650 |
November | 0.000 | 0.574087E+08 |
December | 0.000 | 0.658441E+09 |
Annual Sum or Average | 0.246528E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.107935E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.107935E+10 |
February | 0.000 | 0.351280E+09 |
March | 0.000 | 0.308156E+09 |
April | 0.000 | 1029964.508 |
May | 0.000 | 3639870.858 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 5971819.650 |
November | 0.000 | 0.574087E+08 |
December | 0.000 | 0.658441E+09 |
Annual Sum or Average | 0.246528E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.107935E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.107935E+10 |
February | 0.000 | 0.351280E+09 |
March | 0.000 | 0.308156E+09 |
April | 0.000 | 1029964.508 |
May | 0.000 | 3639870.858 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 5971819.650 |
November | 0.000 | 0.574087E+08 |
December | 0.000 | 0.658441E+09 |
Annual Sum or Average | 0.246528E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.107935E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.107935E+10 |
February | 0.000 | 0.351280E+09 |
March | 0.000 | 0.308156E+09 |
April | 0.000 | 1029964.508 |
May | 0.000 | 3639870.858 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 5971819.650 |
November | 0.000 | 0.574087E+08 |
December | 0.000 | 0.658441E+09 |
Annual Sum or Average | 0.246528E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.107935E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.107935E+10 |
February | 0.000 | 0.351280E+09 |
March | 0.000 | 0.308156E+09 |
April | 0.000 | 1029964.508 |
May | 0.000 | 3639870.858 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 5971819.650 |
November | 0.000 | 0.574087E+08 |
December | 0.000 | 0.658441E+09 |
Annual Sum or Average | 0.246528E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.107935E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.107935E+10 |
February | 0.000 | 0.351280E+09 |
March | 0.000 | 0.308156E+09 |
April | 0.000 | 1029964.508 |
May | 0.000 | 3639870.858 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 5971819.650 |
November | 0.000 | 0.574087E+08 |
December | 0.000 | 0.658441E+09 |
Annual Sum or Average | 0.246528E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.107935E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.107935E+10 |
February | 0.000 | 0.351280E+09 |
March | 0.000 | 0.308156E+09 |
April | 0.000 | 1029964.508 |
May | 0.000 | 3639870.858 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 5971819.650 |
November | 0.000 | 0.574087E+08 |
December | 0.000 | 0.658441E+09 |
Annual Sum or Average | 0.246528E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.107935E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.107935E+10 |
February | 0.000 | 0.351280E+09 |
March | 0.000 | 0.308156E+09 |
April | 0.000 | 1029964.508 |
May | 0.000 | 3639870.858 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 5971819.650 |
November | 0.000 | 0.574087E+08 |
December | 0.000 | 0.658441E+09 |
Annual Sum or Average | 0.246528E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.107935E+10 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179633E+10 | 5422.85 | 31-JAN-16:30 | 29.00 | 10.69 | 0.241760E+09 | 301.60 | 10-JAN-16:10 | 21.00 | 10.83 |
February | 0.815698E+09 | 3928.52 | 25-FEB-17:00 | 17.00 | 8.56 | 0.220702E+09 | 301.60 | 18-FEB-15:00 | 22.00 | 14.05 |
March | 0.212358E+10 | 6208.99 | 18-MAR-16:00 | 27.20 | 11.06 | 0.263005E+09 | 301.61 | 17-MAR-09:00 | 21.60 | 14.23 |
April | 0.599517E+10 | 30229.56 | 19-APR-05:02 | 12.83 | 4.66 | 0.248797E+09 | 301.60 | 15-APR-07:00 | 24.00 | 14.02 |
May | 0.785077E+10 | 30882.75 | 01-MAY-05:02 | 13.00 | 4.56 | 0.258824E+09 | 301.60 | 17-MAY-07:19 | 24.33 | 11.56 |
June | 0.101401E+11 | 28381.18 | 21-JUN-05:01 | 18.00 | 8.27 | 0.259008E+09 | 301.61 | 30-JUN-07:40 | 30.33 | 19.44 |
July | 0.973439E+10 | 27995.47 | 01-JUL-05:01 | 18.83 | 6.86 | 0.249150E+09 | 301.62 | 15-JUL-13:39 | 33.67 | 21.34 |
August | 0.101856E+11 | 26784.74 | 24-AUG-05:01 | 19.83 | 9.67 | 0.269041E+09 | 301.61 | 12-AUG-12:09 | 35.17 | 21.72 |
September | 0.881497E+10 | 26271.53 | 16-SEP-05:01 | 19.90 | 12.46 | 0.249040E+09 | 301.62 | 02-SEP-15:50 | 32.47 | 21.13 |
October | 0.558242E+10 | 29841.13 | 19-OCT-05:02 | 14.00 | 6.83 | 0.248267E+09 | 301.62 | 07-OCT-08:50 | 25.38 | 17.97 |
November | 0.277718E+10 | 22907.55 | 02-NOV-05:03 | 16.00 | 11.78 | 0.236571E+09 | 301.66 | 10-NOV-16:49 | 22.50 | 13.09 |
December | 0.106301E+10 | 4492.01 | 22-DEC-16:30 | 24.50 | 9.77 | 0.237220E+09 | 301.59 | 26-DEC-16:10 | 23.00 | 10.72 |
Annual Sum or Average | 0.668792E+11 | 0.298139E+10 | ||||||||
Minimum of Months | 0.815698E+09 | 3928.52 | 12.83 | 4.56 | 0.220702E+09 | 301.59 | 21.00 | 10.72 | ||
Maximum of Months | 0.101856E+11 | 30882.75 | 29.00 | 12.46 | 0.269041E+09 | 301.66 | 35.17 | 21.72 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113835E+09 | 3647.44 | 31-JAN-16:00 | 29.00 | 10.69 | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 | 1.80 |
February | 1347144.05 | 2107.82 | 10-FEB-07:10 | 16.17 | 8.82 | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.41 |
March | 0.725994E+09 | 10767.83 | 18-MAR-15:00 | 27.20 | 12.50 | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.82 |
April | 0.142781E+11 | 76115.49 | 16-APR-11:01 | 22.17 | 12.81 | 0.00 | 0.00 | 01-APR-00:10 | 15.28 | 7.32 |
May | 0.230674E+11 | 67749.17 | 29-MAY-08:41 | 25.50 | 11.09 | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 | 7.15 |
June | 0.386497E+11 | 71939.30 | 23-JUN-00:11 | 24.67 | 13.03 | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 | 11.06 |
July | 0.368912E+11 | 72848.96 | 05-JUL-02:61 | 23.83 | 11.74 | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 | 14.57 |
August | 0.337046E+11 | 72758.61 | 23-AUG-01:11 | 24.67 | 13.46 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.33 |
September | 0.261870E+11 | 72958.15 | 15-SEP-22:21 | 24.40 | 13.39 | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 | 16.64 |
October | 0.106146E+11 | 75293.84 | 08-OCT-12:11 | 23.33 | 13.25 | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 | 15.49 |
November | 0.118771E+10 | 13013.61 | 01-NOV-15:10 | 28.83 | 16.09 | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 | 10.25 |
December | 16090839.37 | 6302.71 | 09-DEC-07:10 | 8.17 | 0.69 | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.96 |
Annual Sum or Average | 0.185438E+12 | 0.00 | ||||||||
Minimum of Months | 1347144.05 | 2107.82 | 8.17 | 0.69 | 0.00 | 0.00 | 4.27 | 1.80 | ||
Maximum of Months | 0.386497E+11 | 76115.49 | 29.00 | 16.09 | 0.00 | 0.00 | 29.40 | 18.33 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 | 1.80 | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 | 1.80 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.41 | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.41 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.82 | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.82 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 | 7.32 | 0.00 | 0.00 | 01-APR-00:10 | 15.28 | 7.32 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 | 7.15 | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 | 7.15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 | 11.06 | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 | 11.06 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.73 | 14.57 | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 | 14.57 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.33 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.33 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 | 16.64 | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 | 16.64 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 | 15.49 | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 | 15.49 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 | 10.25 | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 | 10.25 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.96 | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.96 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.27 | 1.80 | 0.00 | 0.00 | 4.27 | 1.80 | ||
Maximum of Months | 0.00 | 0.00 | 29.40 | 18.33 | 0.00 | 0.00 | 29.40 | 18.33 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.439207E+09 | 29709.40 | 02-JAN-06:01 | 4.33 |
February | 0.474239E+09 | 28963.38 | 13-FEB-06:02 | 8.00 |
March | 0.384806E+09 | 28999.59 | 27-MAR-05:02 | 2.52 |
April | 43396606.04 | 3044.56 | 26-APR-06:05 | 19.50 |
May | 13438567.45 | 4706.31 | 27-MAY-05:50 | 15.83 |
June | 432231.91 | 660.51 | 01-JUN-06:03 | 22.50 |
July | 152013.04 | 961.92 | 01-JUL-06:01 | 18.83 |
August | 274463.55 | 1062.60 | 25-AUG-06:02 | 21.67 |
September | 3167632.54 | 2633.31 | 16-SEP-06:05 | 19.58 |
October | 66442773.99 | 4860.53 | 21-OCT-05:50 | 16.17 |
November | 0.160238E+09 | 7248.68 | 24-NOV-06:13 | 3.33 |
December | 0.683543E+09 | 29591.13 | 18-DEC-06:01 | 3.83 |
Annual Sum or Average | 0.226934E+10 | |||
Minimum of Months | 152013.04 | 660.51 | 2.52 | |
Maximum of Months | 0.683543E+09 | 29709.40 | 22.50 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405256E+10 | 58917.37 | 01-JAN-07:23 | 1.00 |
February | 0.293078E+10 | 6549.97 | 11-FEB-08:00 | 15.00 |
March | 0.317093E+10 | 7098.80 | 16-MAR-07:00 | 12.70 |
April | 0.726166E+09 | 6561.03 | 05-APR-07:00 | 17.00 |
May | 0.278536E+09 | 6663.21 | 03-MAY-06:35 | 19.33 |
June | 9406707.56 | 6393.39 | 21-JUN-06:01 | 19.17 |
July | 4647722.00 | 6535.03 | 29-JUL-06:21 | 21.50 |
August | 8276746.16 | 6252.81 | 25-AUG-06:02 | 21.67 |
September | 0.108435E+09 | 6594.72 | 29-SEP-06:11 | 20.87 |
October | 0.899472E+09 | 6962.34 | 20-OCT-07:00 | 15.00 |
November | 0.215608E+10 | 6853.32 | 24-NOV-07:50 | 6.50 |
December | 0.354491E+10 | 23126.14 | 07-DEC-06:33 | 0.33 |
Annual Sum or Average | 0.178902E+11 | |||
Minimum of Months | 4647722.00 | 6252.81 | 0.33 | |
Maximum of Months | 0.405256E+10 | 58917.37 | 21.67 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.256100E+10 | 1939.55 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.233575E+10 | 1939.55 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.266872E+10 | 1939.55 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.252182E+10 | 1939.55 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.261486E+10 | 1939.55 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.257569E+10 | 1939.55 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.256100E+10 | 1939.55 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.266872E+10 | 1939.55 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.252182E+10 | 1939.55 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.256100E+10 | 1939.55 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.246796E+10 | 1939.55 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.256100E+10 | 1939.55 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.306193E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.233575E+10 | 1939.55 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.266872E+10 | 1939.55 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112294E+11 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102778E+11 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.118738E+11 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.111270E+11 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.115516E+11 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.114492E+11 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112294E+11 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.118738E+11 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.111270E+11 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112294E+11 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108048E+11 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112294E+11 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135003E+12 | ||||
Minimum of Months | 0.102778E+11 | 10075.60 | 0.00 | 0.00 | |
Maximum of Months | 0.118738E+11 | 10075.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.258277E+11 | 23173.88 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.236390E+11 | 23173.88 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.273097E+11 | 23173.88 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.255921E+11 | 23173.88 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.265687E+11 | 23173.88 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.263332E+11 | 23173.88 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.258277E+11 | 23173.88 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.273097E+11 | 23173.88 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.255921E+11 | 23173.88 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.258277E+11 | 23173.88 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.248511E+11 | 23173.88 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.258277E+11 | 23173.88 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.236390E+11 | 23173.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.273097E+11 | 23173.88 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16831675.39 | 0.108572E+10 |
February | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129021E+10 |
March | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51189937.28 | 0.125575E+10 |
April | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441691E+09 | 0.465042E+09 |
May | 0.565842E+09 | 0.261486E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.786079E+09 | 0.250888E+09 |
June | 0.565842E+09 | 0.257569E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137375E+10 | 66149677.77 |
July | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110697E+10 | 64506145.41 |
August | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109601E+10 | 0.100484E+09 |
September | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766026E+09 | 0.182364E+09 |
October | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331456E+09 | 0.731388E+09 |
November | 0.522316E+09 | 0.246796E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36132703.05 | 0.109470E+10 |
December | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1970779.84 | 0.140443E+10 |
Annual Sum or Average | 0.659424E+10 | 0.306193E+11 | 0.319458E+11 | 0.600810E+10 | 0.799163E+10 | ||||
Minimum of Months | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64506145.41 |
Maximum of Months | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137375E+10 | 0.140443E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9484772.58 | 0.690156E+10 |
February | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620561E+10 |
March | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30583511.67 | 0.810929E+10 |
April | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140753E+10 | 0.357628E+10 |
May | 0.00 | 0.115516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315597E+10 | 0.221666E+10 |
June | 0.00 | 0.114492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670793E+10 | 0.699129E+09 |
July | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565599E+10 | 0.646538E+09 |
August | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386757E+10 | 0.104546E+10 |
September | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282730E+10 | 0.178278E+10 |
October | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900027E+09 | 0.542886E+10 |
November | 0.00 | 0.108048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16756594.34 | 0.741649E+10 |
December | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4835797.79 | 0.667933E+10 |
Annual Sum or Average | 0.135003E+12 | 0.245840E+11 | 0.507080E+11 | ||||||
Minimum of Months | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646538E+09 |
Maximum of Months | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670793E+10 | 0.810929E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130225E+10 | 0.147799E+11 |
February | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172577E+11 |
March | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546612E+09 | 0.219922E+11 |
April | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122657E+10 | 0.149830E+11 |
May | 0.00 | 0.265687E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278900E+09 | 0.114994E+11 |
June | 0.00 | 0.263332E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109430E+10 | 0.506959E+10 |
July | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.810222E+09 | 0.589017E+10 |
August | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611484E+09 | 0.762969E+10 |
September | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293796E+09 | 0.107353E+11 |
October | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133852E+09 | 0.228717E+11 |
November | 0.00 | 0.248511E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190077E+09 | 0.222101E+11 |
December | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315997E+09 | 0.175450E+11 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | 0.680405E+10 | 0.172464E+12 | |||||
Minimum of Months | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506959E+10 |
Maximum of Months | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130225E+10 | 0.228717E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1939.55 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1465.12 | 31-JAN-17:10 | 5803.01 | 12-JAN-07:03 |
February | 659.25 | 01-FEB-08:09 | 1939.55 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5963.94 | 01-FEB-08:00 |
March | 659.25 | 01-MAR-08:09 | 1939.55 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1650.75 | 16-MAR-16:10 | 7179.39 | 27-MAR-06:05 |
April | 659.25 | 01-APR-07:10 | 1939.55 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3698.63 | 14-APR-16:10 | 5153.54 | 21-APR-06:02 |
May | 659.25 | 01-MAY-07:10 | 1939.55 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4513.11 | 31-MAY-16:10 | 3663.78 | 01-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1939.55 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6440.47 | 30-JUN-16:10 | 1637.87 | 21-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 1939.55 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5701.12 | 20-JUL-17:00 | 619.14 | 27-JUL-06:10 |
August | 659.25 | 01-AUG-07:10 | 1939.55 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5962.75 | 25-AUG-17:00 | 1572.85 | 24-AUG-06:10 |
September | 659.25 | 01-SEP-07:10 | 1939.55 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4961.32 | 08-SEP-16:10 | 2462.44 | 22-SEP-06:03 |
October | 659.25 | 02-OCT-07:10 | 1939.55 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3737.23 | 06-OCT-16:10 | 6414.22 | 25-OCT-06:02 |
November | 659.25 | 01-NOV-07:10 | 1939.55 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1352.39 | 01-NOV-16:10 | 6035.20 | 24-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1939.55 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 114.96 | 21-DEC-15:00 | 7582.14 | 06-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.14 | |||||
Maximum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 6440.47 | 7582.14 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 769.22 | 31-JAN-16:10 | 9507.48 | 11-JAN-08:00 |
February | 0.00 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 12743.75 | 02-FEB-16:55 |
March | 0.00 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1363.17 | 16-MAR-16:00 | 12025.61 | 11-MAR-16:05 |
April | 0.00 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7661.63 | 10-APR-16:00 | 8272.93 | 21-APR-06:10 |
May | 0.00 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10607.56 | 10-MAY-16:00 | 5906.01 | 23-MAY-06:10 |
June | 0.00 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20468.04 | 30-JUN-16:00 | 3915.56 | 13-JUN-06:10 |
July | 0.00 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20676.70 | 22-JUL-16:00 | 5067.81 | 26-JUL-24:00 |
August | 0.00 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14381.49 | 12-AUG-16:00 | 10628.89 | 28-AUG-16:52 |
September | 0.00 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12089.49 | 01-SEP-16:00 | 6041.40 | 15-SEP-07:00 |
October | 0.00 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7770.31 | 10-OCT-15:10 | 11426.26 | 22-OCT-14:00 |
November | 0.00 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1102.96 | 01-NOV-15:40 | 11943.54 | 22-NOV-16:05 |
December | 0.00 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.21 | 25-DEC-16:00 | 10627.24 | 07-DEC-08:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3915.56 | |||
Maximum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20676.70 | 12743.75 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23173.88 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17182.39 | 06-JAN-13:10 | 20502.81 | 11-JAN-08:10 |
February | 0.00 | 23173.88 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 32914.78 | 02-FEB-12:00 |
March | 0.00 | 23173.88 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11417.76 | 15-MAR-13:00 | 29929.23 | 24-MAR-14:00 |
April | 0.00 | 23173.88 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16963.18 | 01-APR-15:00 | 25823.19 | 20-APR-11:00 |
May | 0.00 | 23173.88 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3054.32 | 20-MAY-14:00 | 21099.74 | 23-MAY-05:00 |
June | 0.00 | 23173.88 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5301.99 | 02-JUN-15:00 | 14535.41 | 13-JUN-06:00 |
July | 0.00 | 23173.88 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4198.78 | 17-JUL-15:00 | 24247.83 | 17-JUL-19:51 |
August | 0.00 | 23173.88 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3838.15 | 25-AUG-16:00 | 35590.39 | 28-AUG-17:00 |
September | 0.00 | 23173.88 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3916.20 | 17-SEP-11:55 | 23198.72 | 03-SEP-05:00 |
October | 0.00 | 23173.88 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3264.75 | 15-OCT-11:55 | 47675.42 | 07-OCT-15:00 |
November | 0.00 | 23173.88 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5869.90 | 19-NOV-15:00 | 47759.44 | 22-NOV-11:55 |
December | 0.00 | 23173.88 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6366.55 | 21-DEC-14:00 | 28217.73 | 07-DEC-08:70 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14535.41 | ||||
Maximum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 17182.39 | 47759.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5422.85 | 31-JAN-16:30 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 326.98 | 0.00 |
February | 3928.52 | 25-FEB-17:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.31 |
March | 6208.99 | 18-MAR-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 46.36 | 0.00 |
April | 30229.56 | 19-APR-05:02 | 362.59 | 2896.74 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 756.28 |
May | 30882.75 | 01-MAY-05:02 | 435.11 | 3476.08 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 828.05 |
June | 28381.18 | 21-JUN-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.11 |
July | 27995.47 | 01-JUL-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.47 |
August | 26784.74 | 24-AUG-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.30 |
September | 26271.53 | 16-SEP-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.14 |
October | 29841.13 | 19-OCT-05:02 | 435.11 | 3476.08 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 750.43 |
November | 22907.55 | 02-NOV-05:03 | 290.07 | 2317.39 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.31 |
December | 4492.01 | 22-DEC-16:30 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 34.24 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3928.52 | 290.07 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30882.75 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 326.98 | 828.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3647.44 | 31-JAN-16:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.69 | 0.00 |
February | 2107.82 | 10-FEB-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1762.71 |
March | 10767.83 | 18-MAR-15:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.20 | 0.00 |
April | 76115.49 | 16-APR-11:01 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2720.12 |
May | 67749.17 | 29-MAY-08:41 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 536.26 |
June | 71939.30 | 23-JUN-00:11 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 602.89 |
July | 72848.96 | 05-JUL-02:61 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 745.63 |
August | 72758.61 | 23-AUG-01:11 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 697.40 |
September | 72958.15 | 15-SEP-22:21 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 696.54 |
October | 75293.84 | 08-OCT-12:11 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1100.74 |
November | 13013.61 | 01-NOV-15:10 | 0.00 | 8890.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1020.33 | 0.00 |
December | 6302.71 | 09-DEC-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3676.78 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2107.82 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76115.49 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1020.33 | 3676.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 8179.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13176.54 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9563.50 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7363.45 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6089.92 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8298.28 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3219.59 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3347.29 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1166.04 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2822.60 |
October | 0.00 | 01-OCT-00:05 | 0.00 | 5452.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4572.48 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5071.89 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8642.04 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1166.04 | |
Maximum of Months | 0.00 | 0.00 | 8179.02 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13176.54 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.717825E+11 | 61233.94 | 31-JAN-15:00 | 0.107935E+10 | 30928.07 | 02-JAN-06:10 |
February | 0.646466E+11 | 56121.09 | 18-FEB-15:09 | 0.351280E+09 | 7752.43 | 13-FEB-06:10 |
March | 0.746203E+11 | 62728.61 | 18-MAR-14:50 | 0.308156E+09 | 9998.26 | 27-MAR-06:10 |
April | 0.782650E+11 | 74259.03 | 14-APR-14:00 | 1029964.51 | 1137.47 | 29-APR-05:19 |
May | 0.873851E+11 | 76168.88 | 20-MAY-14:09 | 3639870.86 | 3262.99 | 27-MAY-05:49 |
June | 0.982266E+11 | 83718.78 | 28-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.968401E+11 | 80772.00 | 19-JUL-13:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.990473E+11 | 81049.80 | 25-AUG-14:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.889501E+11 | 77974.10 | 08-SEP-14:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.779560E+11 | 75403.59 | 02-OCT-13:00 | 5971819.65 | 3362.35 | 21-OCT-05:49 |
November | 0.693077E+11 | 64767.24 | 01-NOV-14:00 | 57408737.68 | 6124.37 | 24-NOV-07:30 |
December | 0.714854E+11 | 57394.30 | 22-DEC-14:00 | 0.658441E+09 | 15103.61 | 18-DEC-07:10 |
Annual Sum or Average | 0.978513E+12 | 0.246528E+10 | ||||
Minimum of Months | 0.646466E+11 | 56121.09 | 0.00 | 0.00 | ||
Maximum of Months | 0.990473E+11 | 83718.78 | 0.107935E+10 | 30928.07 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.396181E+11 | 0.972020E+10 | 0.115358E+11 | 0.00 | 0.824942E+10 | 0.00 | 0.00 | 0.567525E+09 | 0.00 | 0.00 | 0.00 | 0.209143E+10 | 0.00 |
February | 0.362526E+11 | 0.833809E+10 | 0.105871E+11 | 0.00 | 0.755447E+10 | 0.00 | 0.00 | 18876726.76 | 0.00 | 0.00 | 0.00 | 0.189542E+10 | 0.00 |
March | 0.418523E+11 | 0.857286E+10 | 0.123357E+11 | 0.00 | 0.886682E+10 | 0.00 | 0.00 | 0.893674E+09 | 0.00 | 0.00 | 0.00 | 0.209895E+10 | 0.00 |
April | 0.392410E+11 | 0.762243E+10 | 0.114862E+11 | 0.00 | 0.975894E+10 | 0.00 | 0.00 | 0.821228E+10 | 0.00 | 0.00 | 0.00 | 0.194411E+10 | 0.00 |
May | 0.407352E+11 | 0.729678E+10 | 0.119357E+11 | 0.00 | 0.122504E+11 | 0.00 | 0.00 | 0.132157E+11 | 0.00 | 0.00 | 0.00 | 0.195132E+10 | 0.00 |
June | 0.403581E+11 | 0.681967E+10 | 0.118862E+11 | 0.00 | 0.150236E+11 | 0.00 | 0.00 | 0.222845E+11 | 0.00 | 0.00 | 0.00 | 0.185457E+10 | 0.00 |
July | 0.396181E+11 | 0.713774E+10 | 0.115358E+11 | 0.00 | 0.148634E+11 | 0.00 | 0.00 | 0.218285E+11 | 0.00 | 0.00 | 0.00 | 0.185658E+10 | 0.00 |
August | 0.418523E+11 | 0.761485E+10 | 0.123357E+11 | 0.00 | 0.145811E+11 | 0.00 | 0.00 | 0.207617E+11 | 0.00 | 0.00 | 0.00 | 0.190171E+10 | 0.00 |
September | 0.392410E+11 | 0.799730E+10 | 0.114862E+11 | 0.00 | 0.123693E+11 | 0.00 | 0.00 | 0.160002E+11 | 0.00 | 0.00 | 0.00 | 0.185619E+10 | 0.00 |
October | 0.396181E+11 | 0.896667E+10 | 0.115358E+11 | 0.00 | 0.957198E+10 | 0.00 | 0.00 | 0.630520E+10 | 0.00 | 0.00 | 0.00 | 0.195826E+10 | 0.00 |
November | 0.381239E+11 | 0.926581E+10 | 0.110862E+11 | 0.00 | 0.788218E+10 | 0.00 | 0.00 | 0.100013E+10 | 0.00 | 0.00 | 0.00 | 0.194943E+10 | 0.00 |
December | 0.396181E+11 | 0.990575E+10 | 0.115358E+11 | 0.00 | 0.821575E+10 | 0.00 | 0.00 | 0.140487E+09 | 0.00 | 0.00 | 0.00 | 0.206954E+10 | 0.00 |
Annual Sum or Average | 0.476129E+12 | 0.992581E+11 | 0.139282E+12 | 0.129187E+12 | 0.00 | 0.111229E+12 | 0.234275E+11 | ||||||
Minimum of Months | 0.362526E+11 | 0.681967E+10 | 0.105871E+11 | 0.00 | 0.755447E+10 | 0.00 | 0.00 | 18876726.76 | 0.00 | 0.00 | 0.00 | 0.185457E+10 | 0.00 |
Maximum of Months | 0.418523E+11 | 0.990575E+10 | 0.123357E+11 | 0.00 | 0.150236E+11 | 0.00 | 0.00 | 0.222845E+11 | 0.00 | 0.00 | 0.00 | 0.209895E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.107935E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.351280E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.308156E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 1029964.51 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 3639870.86 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 5971819.65 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 57408737.68 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.658441E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246528E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.107935E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35189.04 | 02-JAN-09:09 | 6311.00 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 8290.48 | 10-JAN-14:39 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35189.04 | 01-FEB-09:09 | 6311.00 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 8290.48 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35189.04 | 01-MAR-09:09 | 6311.00 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 8290.48 | 09-MAR-13:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35189.04 | 01-APR-08:09 | 6311.00 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 10595.77 | 10-APR-15:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35189.04 | 01-MAY-08:09 | 6311.00 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 10595.77 | 01-MAY-14:39 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35189.04 | 01-JUN-08:09 | 6311.00 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 10595.77 | 01-JUN-07:49 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35189.04 | 01-JUL-08:09 | 6311.00 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 10595.77 | 01-JUL-10:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35189.04 | 01-AUG-08:09 | 6311.00 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 10595.77 | 01-AUG-09:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35189.04 | 01-SEP-08:09 | 6311.00 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 10595.77 | 01-SEP-08:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35189.04 | 02-OCT-08:09 | 6311.00 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 10595.77 | 02-OCT-08:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35189.04 | 01-NOV-08:09 | 6311.00 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 8290.48 | 01-NOV-10:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35189.04 | 01-DEC-09:09 | 6311.00 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 8290.48 | 22-DEC-14:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35189.04 | 6311.00 | 10112.62 | 0.00 | 8290.48 | 0.00 | 0.00 | |||||
Maximum of Months | 35189.04 | 6311.00 | 10112.62 | 0.00 | 10595.77 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 5892.95 | 31-JAN-16:10 | 0.00 | 0.00 | 0.00 | 1789.39 | 23-JAN-12:39 | 0.00 |
February | 793.88 | 18-FEB-14:39 | 0.00 | 0.00 | 0.00 | 1788.29 | 01-FEB-12:09 | 0.00 |
March | 7634.74 | 18-MAR-14:00 | 0.00 | 0.00 | 0.00 | 1778.66 | 02-MAR-12:20 | 0.00 |
April | 17643.94 | 14-APR-16:10 | 0.00 | 0.00 | 0.00 | 1758.18 | 01-APR-11:50 | 0.00 |
May | 20543.88 | 18-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1733.34 | 01-MAY-11:00 | 0.00 |
June | 30184.99 | 30-JUN-16:10 | 0.00 | 0.00 | 0.00 | 1710.30 | 01-JUN-11:39 | 0.00 |
July | 26586.15 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1695.83 | 01-JUL-11:39 | 0.00 |
August | 26892.06 | 25-AUG-16:10 | 0.00 | 0.00 | 0.00 | 1701.36 | 31-AUG-11:00 | 0.00 |
September | 23005.36 | 08-SEP-16:10 | 0.00 | 0.00 | 0.00 | 1719.92 | 30-SEP-11:50 | 0.00 |
October | 18873.29 | 06-OCT-15:09 | 0.00 | 0.00 | 0.00 | 1744.95 | 31-OCT-11:09 | 0.00 |
November | 9458.75 | 01-NOV-14:00 | 0.00 | 0.00 | 0.00 | 1768.44 | 30-NOV-12:09 | 0.00 |
December | 2088.90 | 22-DEC-14:00 | 0.00 | 0.00 | 0.00 | 1784.19 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 793.88 | 0.00 | 0.00 | 0.00 | 1695.83 | 0.00 | ||
Maximum of Months | 30184.99 | 0.00 | 0.00 | 0.00 | 1789.39 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 61233.94 | 31-JAN-15:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 8290.48 | 0.00 | 0.00 | 5889.70 | 0.00 |
February | 56121.09 | 18-FEB-15:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 8290.48 | 0.00 | 0.00 | 780.10 | 0.00 |
March | 62728.61 | 18-MAR-14:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 8290.48 | 0.00 | 0.00 | 7516.05 | 0.00 |
April | 74259.03 | 14-APR-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 10595.77 | 0.00 | 0.00 | 16644.25 | 0.00 |
May | 76168.88 | 20-MAY-14:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 10595.77 | 0.00 | 0.00 | 18578.37 | 0.00 |
June | 83718.78 | 28-JUN-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 10595.77 | 0.00 | 0.00 | 26146.95 | 0.00 |
July | 80772.00 | 19-JUL-13:30 | 35189.04 | 10112.62 | 0.00 | 0.00 | 10595.77 | 0.00 | 0.00 | 23224.12 | 0.00 |
August | 81049.80 | 25-AUG-14:30 | 35189.04 | 10112.62 | 0.00 | 0.00 | 10595.77 | 0.00 | 0.00 | 23476.09 | 0.00 |
September | 77974.10 | 08-SEP-14:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 10595.77 | 0.00 | 0.00 | 20394.69 | 0.00 |
October | 75403.59 | 02-OCT-13:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 10595.77 | 0.00 | 0.00 | 17835.42 | 0.00 |
November | 64767.24 | 01-NOV-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 8290.48 | 0.00 | 0.00 | 9458.75 | 0.00 |
December | 57394.30 | 22-DEC-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 8290.48 | 0.00 | 0.00 | 2088.90 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 56121.09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 8290.48 | 0.00 | 0.00 | 780.10 | 0.00 | |
Maximum of Months | 83718.78 | 35189.04 | 10112.62 | 0.00 | 0.00 | 10595.77 | 0.00 | 0.00 | 26146.95 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 30928.07 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 7752.43 | 13-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 9998.26 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 1137.47 | 29-APR-05:19 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 3262.99 | 27-MAY-05:49 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 3362.35 | 21-OCT-05:49 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 6124.37 | 24-NOV-07:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 15103.61 | 18-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 30928.07 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 20.25 | 1.00 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.54 | 0.17 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.83 | 20.47 | 0.83 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.90 | 0.50 | 24.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 28.16 | 0.17 | 24.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 26.49 | 4.17 | 24.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.43 | 6.83 | 25.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 25.93 | 6.83 | 24.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 25.03 | 4.50 | 24.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.71 | 0.83 | 24.83 |
November | 0.17 | 20.46 | 0.17 | 20.46 | 0.17 | 24.52 | 0.17 | 24.52 |
December | 1.33 | 20.33 | 1.33 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.50 | 20.36 | 3.50 | 20.36 | 31.17 | 26.08 | 24.00 | 24.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.54 | 1.33 | 20.54 | 9.50 | 28.16 | 6.83 | 25.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 14.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.56 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 27.69 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 51.17 | 27.87 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 57.50 | 27.78 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 42.00 | 27.71 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 27.61 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.54 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.50 | 14.84 | 0.00 | 228.67 | 27.73 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.50 | 14.84 | 0.00 | 0.00 | 57.50 | 27.87 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 298.33 | 23.27 | 30.33 | 21.22 | 30.33 | 21.22 |
February | 276.00 | 23.16 | 25.50 | 21.13 | 25.50 | 21.13 |
March | 284.83 | 23.33 | 22.50 | 21.23 | 21.83 | 21.15 |
April | 79.17 | 23.80 | 51.83 | 23.90 | 0.00 | 0.00 |
May | 22.50 | 23.55 | 74.67 | 23.90 | 0.00 | 0.00 |
June | 3.00 | 24.21 | 249.83 | 23.91 | 1.67 | 24.74 |
July | 7.00 | 24.50 | 283.83 | 23.93 | 6.67 | 24.52 |
August | 8.00 | 24.36 | 313.33 | 23.92 | 7.83 | 24.37 |
September | 6.00 | 24.29 | 292.67 | 23.90 | 5.67 | 24.35 |
October | 100.50 | 23.65 | 105.00 | 23.90 | 1.00 | 24.32 |
November | 199.83 | 23.51 | 53.67 | 23.24 | 28.83 | 22.69 |
December | 300.00 | 23.04 | 68.17 | 21.28 | 68.17 | 21.28 |
Annual Sum or Average | 1585.17 | 23.32 | 1571.33 | 23.64 | 197.50 | 21.81 |
Minimum of Months | 3.00 | 23.04 | 22.50 | 21.13 | 0.00 | 0.00 |
Maximum of Months | 300.00 | 24.50 | 313.33 | 23.93 | 68.17 | 24.74 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.154814E+10 | 0.423180E+09 | 167.25 | 0.154814E+10 | 1604.97 | 0.00 | 0.41 | 31-JAN-16:30 | 0.00 | 01-JAN-00:03 | 7477.57 | 31-JAN-16:30 | 7477.57 | 31-JAN-16:30 | 0.33 | 09-JAN-11:50 | 2180.49 | 31-JAN-16:30 | 0.00 | 01-JAN-00:03 |
February | 68788993.82 | 18876726.76 | 81.33 | 65000988.66 | 3788005.16 | 0.00 | 0.15 | 18-FEB-14:40 | 0.00 | 01-FEB-00:10 | 2912.28 | 18-FEB-14:40 | 2641.04 | 18-FEB-15:00 | 368.39 | 18-FEB-14:00 | 793.88 | 18-FEB-14:40 | 0.00 | 01-FEB-00:10 |
March | 0.162961E+10 | 0.450474E+09 | 178.14 | 0.162258E+10 | 7032506.81 | 0.00 | 0.42 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 8059.59 | 18-MAR-16:00 | 8059.59 | 18-MAR-16:00 | 439.95 | 18-MAR-10:00 | 2254.02 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.694476E+10 | 0.200490E+10 | 253.79 | 0.694426E+10 | 491237.82 | 0.00 | 1.00 | 03-APR-05:03 | 0.00 | 01-APR-00:10 | 21677.25 | 25-APR-05:01 | 21677.25 | 25-APR-05:01 | 2120.60 | 17-APR-05:02 | 5132.66 | 25-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.955508E+10 | 0.283907E+10 | 291.17 | 0.955508E+10 | 0.00 | 0.00 | 1.00 | 01-MAY-05:02 | 0.00 | 01-MAY-00:10 | 22098.75 | 29-MAY-19:11 | 22098.75 | 29-MAY-19:11 | 0.00 | 11-MAY-05:01 | 5863.38 | 29-MAY-19:11 | 0.00 | 01-MAY-00:10 |
June | 0.128352E+11 | 0.411119E+10 | 330.38 | 0.128216E+11 | 13536720.84 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 23069.53 | 30-JUN-05:01 | 23069.53 | 30-JUN-05:01 | 1058.04 | 17-JUN-17:00 | 6655.47 | 28-JUN-16:20 | 0.00 | 01-JUN-00:10 |
July | 0.133449E+11 | 0.405713E+10 | 328.44 | 0.122541E+11 | 0.109079E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:05 | 28082.59 | 14-JUL-05:01 | 23210.26 | 31-JUL-05:01 | 14124.83 | 14-JUL-05:07 | 6431.01 | 23-JUL-17:00 | 0.00 | 01-JUL-00:05 |
August | 0.140692E+11 | 0.425450E+10 | 333.72 | 0.127989E+11 | 0.127026E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 26723.34 | 01-AUG-05:01 | 23317.52 | 16-AUG-05:02 | 11695.28 | 04-AUG-05:56 | 6443.63 | 13-AUG-15:51 | 0.00 | 01-AUG-00:10 |
September | 0.120068E+11 | 0.350899E+10 | 294.58 | 0.108233E+11 | 0.118345E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:05 | 26984.37 | 02-SEP-05:01 | 22859.97 | 20-SEP-05:01 | 12362.90 | 05-SEP-05:56 | 6369.04 | 10-SEP-18:11 | 0.00 | 01-SEP-00:05 |
October | 0.600280E+10 | 0.170728E+10 | 240.80 | 0.576351E+10 | 0.239293E+09 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:05 | 25693.02 | 03-OCT-05:01 | 21828.83 | 02-OCT-05:01 | 9953.42 | 03-OCT-05:49 | 5987.44 | 03-OCT-05:01 | 0.00 | 01-OCT-00:05 |
November | 0.190966E+10 | 0.520592E+09 | 179.64 | 0.185639E+10 | 53267240.53 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 22435.48 | 01-NOV-05:01 | 19096.04 | 01-NOV-05:01 | 5717.03 | 03-NOV-05:02 | 5317.69 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 |
December | 0.512344E+09 | 0.139219E+09 | 110.25 | 0.512343E+09 | 93.70 | 0.00 | 0.32 | 22-DEC-16:30 | 0.00 | 01-DEC-00:10 | 6040.42 | 22-DEC-16:30 | 6040.42 | 22-DEC-16:30 | 0.04 | 13-DEC-12:00 | 1621.88 | 22-DEC-16:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.804271E+11 | 0.240354E+11 | 2789.48 | 0.765652E+11 | 0.386192E+10 | 0.00 | ||||||||||||||
Minimum of Months | 68788993.82 | 18876726.76 | 81.33 | 65000988.66 | 0.00 | 0.00 | 0.15 | 0.00 | 2912.28 | 2641.04 | 0.00 | 793.88 | 0.00 | |||||||
Maximum of Months | 0.140692E+11 | 0.425450E+10 | 333.72 | 0.128216E+11 | 0.127026E+10 | 0.00 | 1.00 | 0.00 | 28082.59 | 23317.52 | 14124.83 | 6655.47 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.457744E+09 | 0.144345E+09 | 35.33 | 0.457744E+09 | 0.00 | 0.00 | 0.19 | 31-JAN-16:00 | 0.00 | 01-JAN-00:03 | 11532.07 | 31-JAN-16:00 | 11532.07 | 31-JAN-16:00 | 0.00 | 24-JAN-15:10 | 3768.94 | 31-JAN-16:00 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.142118E+10 | 0.443200E+09 | 54.33 | 0.141869E+10 | 2485358.32 | 0.00 | 0.28 | 18-MAR-15:00 | 0.00 | 01-MAR-00:10 | 17812.35 | 18-MAR-15:00 | 17812.35 | 18-MAR-15:00 | 421.12 | 18-MAR-11:30 | 5516.25 | 18-MAR-15:00 | 0.00 | 01-MAR-00:10 |
April | 0.190569E+11 | 0.620738E+10 | 271.82 | 0.190548E+11 | 2136779.32 | 0.00 | 1.00 | 07-APR-17:31 | 0.00 | 01-APR-00:10 | 74905.51 | 16-APR-16:40 | 74905.51 | 16-APR-16:40 | 3010.87 | 16-APR-11:01 | 21904.66 | 14-APR-17:05 | 0.00 | 01-APR-00:10 |
May | 0.308396E+11 | 0.103766E+11 | 365.20 | 0.308396E+11 | 0.00 | 0.00 | 1.00 | 01-MAY-19:21 | 0.00 | 01-MAY-00:10 | 75266.60 | 10-MAY-23:00 | 75266.60 | 10-MAY-23:00 | 0.00 | 02-MAY-20:01 | 22478.23 | 15-MAY-17:05 | 0.00 | 01-MAY-00:10 |
June | 0.508680E+11 | 0.181733E+11 | 476.55 | 0.507939E+11 | 74057821.97 | 0.00 | 1.00 | 01-JUN-17:05 | 0.00 | 01-JUN-00:10 | 77729.63 | 18-JUN-05:41 | 75674.54 | 04-JUN-07:11 | 9216.32 | 17-JUN-17:07 | 24871.27 | 17-JUN-17:42 | 0.00 | 01-JUN-00:10 |
July | 0.528619E+11 | 0.177714E+11 | 491.04 | 0.483541E+11 | 0.450779E+10 | 0.00 | 1.00 | 01-JUL-00:21 | 0.00 | 01-JUL-00:15 | 96692.96 | 14-JUL-00:41 | 75353.66 | 08-JUL-04:21 | 54090.01 | 14-JUL-01:10 | 24321.72 | 20-JUL-17:42 | 0.00 | 01-JUL-00:05 |
August | 0.491887E+11 | 0.165072E+11 | 461.43 | 0.448814E+11 | 0.430737E+10 | 0.00 | 1.00 | 01-AUG-02:21 | 0.00 | 01-AUG-00:15 | 93234.48 | 09-AUG-20:10 | 75833.71 | 31-AUG-03:30 | 41517.60 | 09-AUG-17:55 | 24561.05 | 13-AUG-14:02 | 0.00 | 01-AUG-00:10 |
September | 0.384416E+11 | 0.124912E+11 | 380.45 | 0.347351E+11 | 0.370642E+10 | 0.00 | 1.00 | 01-SEP-01:11 | 0.00 | 01-SEP-00:05 | 95318.17 | 04-SEP-08:40 | 75880.28 | 30-SEP-20:30 | 50414.34 | 04-SEP-07:51 | 23721.46 | 04-SEP-09:51 | 0.00 | 01-SEP-00:05 |
October | 0.142724E+11 | 0.459792E+10 | 216.19 | 0.136140E+11 | 0.658467E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:05 | 89522.67 | 03-OCT-01:57 | 75746.96 | 09-OCT-10:11 | 35965.99 | 03-OCT-01:57 | 23618.97 | 01-OCT-12:43 | 0.00 | 01-OCT-00:05 |
November | 0.155810E+10 | 0.479538E+09 | 80.17 | 0.151439E+10 | 43708095.47 | 0.00 | 0.32 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 | 21511.74 | 01-NOV-14:50 | 20906.63 | 01-NOV-15:00 | 1717.82 | 01-NOV-11:30 | 6775.05 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 4059445.44 | 1268080.74 | 1.50 | 4059445.44 | 0.00 | 0.00 | 0.03 | 22-DEC-15:00 | 0.00 | 01-DEC-00:10 | 1711.93 | 22-DEC-15:00 | 1711.93 | 22-DEC-15:00 | 0.00 | 01-DEC-00:10 | 536.83 | 22-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.258970E+12 | 0.871934E+11 | 2834.01 | 0.245668E+12 | 0.133024E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.528619E+11 | 0.181733E+11 | 491.04 | 0.507939E+11 | 0.450779E+10 | 0.00 | 1.00 | 0.00 | 96692.96 | 75880.28 | 54090.01 | 24871.27 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.06 | 41.85 | 25.21 | 124.58 | 130.41 | 0.00 | 0.00 | 744.00 |
February | 53.81 | 25.97 | 27.84 | 77.08 | 125.57 | 0.00 | 0.00 | 672.00 |
March | 71.51 | 34.12 | 37.38 | 121.58 | 114.55 | 0.00 | 0.00 | 744.00 |
April | 108.91 | 61.82 | 47.09 | 239.72 | 79.52 | 0.00 | 0.00 | 720.00 |
May | 109.53 | 61.10 | 48.42 | 258.99 | 61.43 | 0.00 | 0.00 | 744.00 |
June | 116.31 | 68.23 | 48.08 | 319.81 | 30.61 | 0.00 | 0.00 | 720.00 |
July | 84.82 | 39.49 | 45.33 | 236.04 | 26.42 | 0.00 | 0.00 | 744.00 |
August | 80.97 | 40.55 | 40.42 | 226.35 | 32.69 | 0.00 | 0.00 | 744.00 |
September | 70.62 | 29.63 | 40.99 | 184.01 | 43.47 | 0.00 | 0.00 | 720.00 |
October | 72.15 | 41.17 | 30.98 | 147.25 | 103.59 | 0.00 | 0.00 | 744.00 |
November | 66.35 | 39.95 | 26.39 | 114.97 | 135.77 | 0.00 | 0.00 | 720.00 |
December | 53.97 | 30.85 | 23.12 | 85.78 | 159.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.76 | 42.96 | 36.80 | 178.44 | 86.79 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.81 | 25.97 | 23.12 | 77.08 | 26.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 116.31 | 68.23 | 48.42 | 319.81 | 159.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.06 | 41.85 | 25.21 | 124.58 | 130.41 | 0.00 | 0.00 | 744.00 |
February | 53.81 | 25.97 | 27.84 | 77.08 | 125.57 | 0.00 | 0.00 | 672.00 |
March | 71.51 | 34.12 | 37.38 | 121.58 | 114.55 | 0.00 | 0.00 | 744.00 |
April | 108.91 | 61.82 | 47.09 | 239.72 | 79.52 | 0.00 | 0.00 | 720.00 |
May | 109.53 | 61.10 | 48.42 | 258.99 | 61.43 | 0.00 | 0.00 | 744.00 |
June | 116.31 | 68.23 | 48.08 | 319.81 | 30.61 | 0.00 | 0.00 | 720.00 |
July | 84.82 | 39.49 | 45.33 | 236.04 | 26.42 | 0.00 | 0.00 | 744.00 |
August | 80.97 | 40.55 | 40.42 | 226.35 | 32.69 | 0.00 | 0.00 | 744.00 |
September | 70.62 | 29.63 | 40.99 | 184.01 | 43.47 | 0.00 | 0.00 | 720.00 |
October | 72.15 | 41.17 | 30.98 | 147.25 | 103.59 | 0.00 | 0.00 | 744.00 |
November | 66.35 | 39.95 | 26.39 | 114.97 | 135.77 | 0.00 | 0.00 | 720.00 |
December | 53.97 | 30.85 | 23.12 | 85.78 | 159.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 79.76 | 42.96 | 36.80 | 178.44 | 86.79 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.81 | 25.97 | 23.12 | 77.08 | 26.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 116.31 | 68.23 | 48.42 | 319.81 | 159.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.49 | 0.00 | 11.49 | 9.81 | 77.35 | 0.00 | 0.00 | 744.00 |
February | 13.09 | 0.00 | 13.09 | 6.08 | 76.15 | 0.00 | 0.00 | 672.00 |
March | 17.40 | 0.00 | 17.40 | 18.41 | 69.39 | 0.00 | 0.00 | 744.00 |
April | 21.37 | 0.39 | 20.98 | 41.35 | 46.24 | 0.00 | 0.00 | 720.00 |
May | 25.55 | 2.67 | 22.88 | 55.88 | 32.83 | 0.00 | 0.00 | 744.00 |
June | 29.64 | 6.06 | 23.58 | 91.81 | 16.14 | 0.00 | 0.00 | 720.00 |
July | 25.01 | 2.98 | 22.03 | 77.77 | 14.46 | 0.00 | 0.00 | 744.00 |
August | 20.07 | 0.69 | 19.38 | 66.25 | 18.59 | 0.00 | 0.00 | 744.00 |
September | 18.74 | 0.02 | 18.73 | 54.33 | 25.23 | 0.00 | 0.00 | 720.00 |
October | 14.49 | 0.00 | 14.49 | 22.98 | 61.70 | 0.00 | 0.00 | 744.00 |
November | 12.07 | 0.00 | 12.07 | 8.18 | 81.38 | 0.00 | 0.00 | 720.00 |
December | 10.73 | 0.00 | 10.73 | 5.18 | 95.67 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 18.32 | 1.07 | 17.25 | 38.32 | 51.16 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 10.73 | 0.00 | 10.73 | 5.18 | 14.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 29.64 | 6.06 | 23.58 | 91.81 | 95.67 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.49 | 0.00 | 11.49 | 9.81 | 77.35 | 0.00 | 0.00 | 744.00 |
February | 13.09 | 0.00 | 13.09 | 6.08 | 76.15 | 0.00 | 0.00 | 672.00 |
March | 17.40 | 0.00 | 17.40 | 18.41 | 69.39 | 0.00 | 0.00 | 744.00 |
April | 21.37 | 0.39 | 20.98 | 41.35 | 46.24 | 0.00 | 0.00 | 720.00 |
May | 25.55 | 2.67 | 22.87 | 55.88 | 32.83 | 0.00 | 0.00 | 744.00 |
June | 29.64 | 6.06 | 23.58 | 91.81 | 16.14 | 0.00 | 0.00 | 720.00 |
July | 25.01 | 2.98 | 22.03 | 77.77 | 14.46 | 0.00 | 0.00 | 744.00 |
August | 20.07 | 0.69 | 19.38 | 66.25 | 18.59 | 0.00 | 0.00 | 744.00 |
September | 18.74 | 0.02 | 18.72 | 54.33 | 25.23 | 0.00 | 0.00 | 720.00 |
October | 14.49 | 0.00 | 14.49 | 22.98 | 61.70 | 0.00 | 0.00 | 744.00 |
November | 12.07 | 0.00 | 12.07 | 8.18 | 81.38 | 0.00 | 0.00 | 720.00 |
December | 10.73 | 0.00 | 10.73 | 5.18 | 95.67 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 18.32 | 1.07 | 17.25 | 38.32 | 51.16 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 10.73 | 0.00 | 10.73 | 5.18 | 14.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 29.64 | 6.06 | 23.58 | 91.81 | 95.67 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.49 | 29.67 | 8.82 | 57.48 | 43.20 | 1.00 | 0.00 | 744.00 |
February | 37.63 | 24.17 | 13.46 | 53.33 | 36.94 | 0.00 | 0.00 | 672.00 |
March | 53.39 | 34.19 | 19.20 | 82.99 | 37.96 | 0.00 | 0.00 | 744.00 |
April | 82.59 | 63.84 | 18.75 | 135.36 | 40.22 | 0.00 | 0.00 | 720.00 |
May | 90.96 | 71.50 | 19.47 | 148.97 | 39.84 | 0.00 | 0.00 | 744.00 |
June | 95.81 | 78.40 | 17.42 | 163.19 | 30.48 | 0.00 | 0.00 | 720.00 |
July | 77.61 | 56.27 | 21.34 | 131.65 | 23.54 | 0.00 | 0.00 | 744.00 |
August | 71.52 | 52.93 | 18.58 | 122.28 | 28.11 | 0.00 | 0.00 | 744.00 |
September | 57.48 | 36.12 | 21.36 | 95.33 | 28.96 | 0.00 | 0.00 | 720.00 |
October | 51.12 | 38.43 | 12.68 | 76.36 | 48.09 | 0.00 | 0.00 | 744.00 |
November | 37.78 | 27.30 | 10.48 | 52.26 | 46.78 | 0.00 | 0.00 | 720.00 |
December | 33.25 | 24.26 | 8.99 | 45.22 | 51.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.74 | 44.85 | 15.89 | 97.23 | 37.98 | 1.00 | 0.00 | 8760.00 |
Minimum of Months | 33.25 | 24.17 | 8.82 | 45.22 | 23.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.81 | 78.40 | 21.36 | 163.19 | 51.32 | 1.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.49 | 29.67 | 8.82 | 57.48 | 43.20 | 1.00 | 0.00 | 744.00 |
February | 37.63 | 24.17 | 13.46 | 53.33 | 36.94 | 0.00 | 0.00 | 672.00 |
March | 53.39 | 34.19 | 19.20 | 82.99 | 37.96 | 0.00 | 0.00 | 744.00 |
April | 82.59 | 63.84 | 18.75 | 135.36 | 40.22 | 0.00 | 0.00 | 720.00 |
May | 90.96 | 71.50 | 19.47 | 148.97 | 39.84 | 0.00 | 0.00 | 744.00 |
June | 95.81 | 78.40 | 17.42 | 163.19 | 30.48 | 0.00 | 0.00 | 720.00 |
July | 77.61 | 56.27 | 21.34 | 131.65 | 23.54 | 0.00 | 0.00 | 744.00 |
August | 71.52 | 52.93 | 18.58 | 122.28 | 28.11 | 0.00 | 0.00 | 744.00 |
September | 57.48 | 36.12 | 21.36 | 95.33 | 28.96 | 0.00 | 0.00 | 720.00 |
October | 51.12 | 38.43 | 12.68 | 76.36 | 48.09 | 0.00 | 0.00 | 744.00 |
November | 37.78 | 27.30 | 10.48 | 52.26 | 46.78 | 0.00 | 0.00 | 720.00 |
December | 33.25 | 24.26 | 8.99 | 45.22 | 51.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.74 | 44.85 | 15.89 | 97.23 | 37.98 | 1.00 | 0.00 | 8760.00 |
Minimum of Months | 33.25 | 24.17 | 8.82 | 45.22 | 23.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.81 | 78.40 | 21.36 | 163.19 | 51.32 | 1.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.49 | 29.67 | 8.82 | 57.48 | 43.20 | 1.00 | 0.00 | 744.00 |
February | 37.63 | 24.17 | 13.46 | 53.33 | 36.94 | 0.00 | 0.00 | 672.00 |
March | 53.39 | 34.19 | 19.20 | 82.99 | 37.96 | 0.00 | 0.00 | 744.00 |
April | 82.59 | 63.84 | 18.75 | 135.36 | 40.22 | 0.00 | 0.00 | 720.00 |
May | 90.96 | 71.50 | 19.47 | 148.97 | 39.84 | 0.00 | 0.00 | 744.00 |
June | 95.81 | 78.40 | 17.42 | 163.19 | 30.48 | 0.00 | 0.00 | 720.00 |
July | 77.61 | 56.27 | 21.34 | 131.65 | 23.54 | 0.00 | 0.00 | 744.00 |
August | 71.52 | 52.93 | 18.58 | 122.28 | 28.11 | 0.00 | 0.00 | 744.00 |
September | 57.48 | 36.12 | 21.36 | 95.33 | 28.96 | 0.00 | 0.00 | 720.00 |
October | 51.12 | 38.43 | 12.68 | 76.36 | 48.09 | 0.00 | 0.00 | 744.00 |
November | 37.78 | 27.30 | 10.48 | 52.26 | 46.78 | 0.00 | 0.00 | 720.00 |
December | 33.25 | 24.26 | 8.99 | 45.22 | 51.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.74 | 44.85 | 15.89 | 97.23 | 37.98 | 1.00 | 0.00 | 8760.00 |
Minimum of Months | 33.25 | 24.17 | 8.82 | 45.22 | 23.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.81 | 78.40 | 21.36 | 163.19 | 51.32 | 1.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.49 | 29.67 | 8.82 | 57.48 | 43.20 | 1.00 | 0.00 | 744.00 |
February | 37.63 | 24.17 | 13.46 | 53.33 | 36.94 | 0.00 | 0.00 | 672.00 |
March | 53.39 | 34.19 | 19.20 | 82.99 | 37.96 | 0.00 | 0.00 | 744.00 |
April | 82.59 | 63.84 | 18.75 | 135.36 | 40.22 | 0.00 | 0.00 | 720.00 |
May | 90.96 | 71.50 | 19.47 | 148.97 | 39.84 | 0.00 | 0.00 | 744.00 |
June | 95.81 | 78.40 | 17.42 | 163.19 | 30.48 | 0.00 | 0.00 | 720.00 |
July | 77.61 | 56.27 | 21.34 | 131.65 | 23.54 | 0.00 | 0.00 | 744.00 |
August | 71.52 | 52.93 | 18.58 | 122.28 | 28.11 | 0.00 | 0.00 | 744.00 |
September | 57.48 | 36.12 | 21.36 | 95.33 | 28.96 | 0.00 | 0.00 | 720.00 |
October | 51.12 | 38.43 | 12.68 | 76.36 | 48.09 | 0.00 | 0.00 | 744.00 |
November | 37.78 | 27.30 | 10.48 | 52.26 | 46.78 | 0.00 | 0.00 | 720.00 |
December | 33.25 | 24.26 | 8.99 | 45.22 | 51.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.74 | 44.85 | 15.89 | 97.23 | 37.98 | 1.00 | 0.00 | 8760.00 |
Minimum of Months | 33.25 | 24.17 | 8.82 | 45.22 | 23.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.81 | 78.40 | 21.36 | 163.19 | 51.32 | 1.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.49 | 29.67 | 8.82 | 57.48 | 43.20 | 1.00 | 0.00 | 744.00 |
February | 37.63 | 24.17 | 13.46 | 53.33 | 36.94 | 0.00 | 0.00 | 672.00 |
March | 53.39 | 34.19 | 19.20 | 82.99 | 37.96 | 0.00 | 0.00 | 744.00 |
April | 82.59 | 63.84 | 18.75 | 135.36 | 40.22 | 0.00 | 0.00 | 720.00 |
May | 90.96 | 71.50 | 19.47 | 148.97 | 39.84 | 0.00 | 0.00 | 744.00 |
June | 95.81 | 78.40 | 17.42 | 163.19 | 30.48 | 0.00 | 0.00 | 720.00 |
July | 77.61 | 56.27 | 21.34 | 131.65 | 23.54 | 0.00 | 0.00 | 744.00 |
August | 71.52 | 52.93 | 18.58 | 122.28 | 28.11 | 0.00 | 0.00 | 744.00 |
September | 57.48 | 36.12 | 21.36 | 95.33 | 28.96 | 0.00 | 0.00 | 720.00 |
October | 51.12 | 38.43 | 12.68 | 76.36 | 48.09 | 0.00 | 0.00 | 744.00 |
November | 37.78 | 27.30 | 10.48 | 52.26 | 46.78 | 0.00 | 0.00 | 720.00 |
December | 33.25 | 24.26 | 8.99 | 45.22 | 51.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.74 | 44.85 | 15.89 | 97.23 | 37.98 | 1.00 | 0.00 | 8760.00 |
Minimum of Months | 33.25 | 24.17 | 8.82 | 45.22 | 23.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.81 | 78.40 | 21.36 | 163.19 | 51.32 | 1.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.49 | 29.67 | 8.82 | 57.48 | 43.20 | 1.00 | 0.00 | 744.00 |
February | 37.63 | 24.17 | 13.46 | 53.33 | 36.94 | 0.00 | 0.00 | 672.00 |
March | 53.39 | 34.19 | 19.20 | 82.99 | 37.96 | 0.00 | 0.00 | 744.00 |
April | 82.59 | 63.84 | 18.75 | 135.36 | 40.22 | 0.00 | 0.00 | 720.00 |
May | 90.96 | 71.50 | 19.47 | 148.97 | 39.84 | 0.00 | 0.00 | 744.00 |
June | 95.81 | 78.40 | 17.42 | 163.19 | 30.48 | 0.00 | 0.00 | 720.00 |
July | 77.61 | 56.27 | 21.34 | 131.65 | 23.54 | 0.00 | 0.00 | 744.00 |
August | 71.52 | 52.93 | 18.58 | 122.28 | 28.11 | 0.00 | 0.00 | 744.00 |
September | 57.48 | 36.12 | 21.36 | 95.33 | 28.96 | 0.00 | 0.00 | 720.00 |
October | 51.12 | 38.43 | 12.68 | 76.36 | 48.09 | 0.00 | 0.00 | 744.00 |
November | 37.78 | 27.30 | 10.48 | 52.26 | 46.78 | 0.00 | 0.00 | 720.00 |
December | 33.25 | 24.26 | 8.99 | 45.22 | 51.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.74 | 44.85 | 15.89 | 97.23 | 37.98 | 1.00 | 0.00 | 8760.00 |
Minimum of Months | 33.25 | 24.17 | 8.82 | 45.22 | 23.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.81 | 78.40 | 21.36 | 163.19 | 51.32 | 1.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.49 | 29.67 | 8.82 | 57.48 | 43.20 | 1.00 | 0.00 | 744.00 |
February | 37.63 | 24.17 | 13.46 | 53.33 | 36.94 | 0.00 | 0.00 | 672.00 |
March | 53.39 | 34.19 | 19.20 | 82.99 | 37.96 | 0.00 | 0.00 | 744.00 |
April | 82.59 | 63.84 | 18.75 | 135.36 | 40.22 | 0.00 | 0.00 | 720.00 |
May | 90.96 | 71.50 | 19.47 | 148.97 | 39.84 | 0.00 | 0.00 | 744.00 |
June | 95.81 | 78.40 | 17.42 | 163.19 | 30.48 | 0.00 | 0.00 | 720.00 |
July | 77.61 | 56.27 | 21.34 | 131.65 | 23.54 | 0.00 | 0.00 | 744.00 |
August | 71.52 | 52.93 | 18.58 | 122.28 | 28.11 | 0.00 | 0.00 | 744.00 |
September | 57.48 | 36.12 | 21.36 | 95.33 | 28.96 | 0.00 | 0.00 | 720.00 |
October | 51.12 | 38.43 | 12.68 | 76.36 | 48.09 | 0.00 | 0.00 | 744.00 |
November | 37.78 | 27.30 | 10.48 | 52.26 | 46.78 | 0.00 | 0.00 | 720.00 |
December | 33.25 | 24.26 | 8.99 | 45.22 | 51.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.74 | 44.85 | 15.89 | 97.23 | 37.98 | 1.00 | 0.00 | 8760.00 |
Minimum of Months | 33.25 | 24.17 | 8.82 | 45.22 | 23.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.81 | 78.40 | 21.36 | 163.19 | 51.32 | 1.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.49 | 29.67 | 8.82 | 57.48 | 43.20 | 1.00 | 0.00 | 744.00 |
February | 37.63 | 24.17 | 13.46 | 53.33 | 36.94 | 0.00 | 0.00 | 672.00 |
March | 53.39 | 34.19 | 19.20 | 82.99 | 37.96 | 0.00 | 0.00 | 744.00 |
April | 82.59 | 63.84 | 18.75 | 135.36 | 40.22 | 0.00 | 0.00 | 720.00 |
May | 90.96 | 71.50 | 19.47 | 148.97 | 39.84 | 0.00 | 0.00 | 744.00 |
June | 95.81 | 78.40 | 17.42 | 163.19 | 30.48 | 0.00 | 0.00 | 720.00 |
July | 77.61 | 56.27 | 21.34 | 131.65 | 23.54 | 0.00 | 0.00 | 744.00 |
August | 71.52 | 52.93 | 18.58 | 122.28 | 28.11 | 0.00 | 0.00 | 744.00 |
September | 57.48 | 36.12 | 21.36 | 95.33 | 28.96 | 0.00 | 0.00 | 720.00 |
October | 51.12 | 38.43 | 12.68 | 76.36 | 48.09 | 0.00 | 0.00 | 744.00 |
November | 37.78 | 27.30 | 10.48 | 52.26 | 46.78 | 0.00 | 0.00 | 720.00 |
December | 33.25 | 24.26 | 8.99 | 45.22 | 51.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.74 | 44.85 | 15.89 | 97.23 | 37.98 | 1.00 | 0.00 | 8760.00 |
Minimum of Months | 33.25 | 24.17 | 8.82 | 45.22 | 23.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.81 | 78.40 | 21.36 | 163.19 | 51.32 | 1.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.49 | 29.67 | 8.82 | 57.48 | 43.20 | 1.00 | 0.00 | 744.00 |
February | 37.63 | 24.17 | 13.46 | 53.33 | 36.94 | 0.00 | 0.00 | 672.00 |
March | 53.39 | 34.19 | 19.20 | 82.99 | 37.96 | 0.00 | 0.00 | 744.00 |
April | 82.59 | 63.84 | 18.75 | 135.36 | 40.22 | 0.00 | 0.00 | 720.00 |
May | 90.96 | 71.50 | 19.47 | 148.97 | 39.84 | 0.00 | 0.00 | 744.00 |
June | 95.81 | 78.40 | 17.42 | 163.19 | 30.48 | 0.00 | 0.00 | 720.00 |
July | 77.61 | 56.27 | 21.34 | 131.65 | 23.54 | 0.00 | 0.00 | 744.00 |
August | 71.52 | 52.93 | 18.58 | 122.28 | 28.11 | 0.00 | 0.00 | 744.00 |
September | 57.48 | 36.12 | 21.36 | 95.33 | 28.96 | 0.00 | 0.00 | 720.00 |
October | 51.12 | 38.43 | 12.68 | 76.36 | 48.09 | 0.00 | 0.00 | 744.00 |
November | 37.78 | 27.30 | 10.48 | 52.26 | 46.78 | 0.00 | 0.00 | 720.00 |
December | 33.25 | 24.26 | 8.99 | 45.22 | 51.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.74 | 44.85 | 15.89 | 97.23 | 37.98 | 1.00 | 0.00 | 8760.00 |
Minimum of Months | 33.25 | 24.17 | 8.82 | 45.22 | 23.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.81 | 78.40 | 21.36 | 163.19 | 51.32 | 1.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.49 | 29.67 | 8.82 | 57.48 | 43.20 | 1.00 | 0.00 | 744.00 |
February | 37.63 | 24.17 | 13.46 | 53.33 | 36.94 | 0.00 | 0.00 | 672.00 |
March | 53.39 | 34.19 | 19.20 | 82.99 | 37.96 | 0.00 | 0.00 | 744.00 |
April | 82.59 | 63.84 | 18.75 | 135.36 | 40.22 | 0.00 | 0.00 | 720.00 |
May | 90.96 | 71.50 | 19.47 | 148.97 | 39.84 | 0.00 | 0.00 | 744.00 |
June | 95.81 | 78.40 | 17.42 | 163.19 | 30.48 | 0.00 | 0.00 | 720.00 |
July | 77.61 | 56.27 | 21.34 | 131.65 | 23.54 | 0.00 | 0.00 | 744.00 |
August | 71.52 | 52.93 | 18.58 | 122.28 | 28.11 | 0.00 | 0.00 | 744.00 |
September | 57.48 | 36.12 | 21.36 | 95.33 | 28.96 | 0.00 | 0.00 | 720.00 |
October | 51.12 | 38.43 | 12.68 | 76.36 | 48.09 | 0.00 | 0.00 | 744.00 |
November | 37.78 | 27.30 | 10.48 | 52.26 | 46.78 | 0.00 | 0.00 | 720.00 |
December | 33.25 | 24.26 | 8.99 | 45.22 | 51.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.74 | 44.85 | 15.89 | 97.23 | 37.98 | 1.00 | 0.00 | 8760.00 |
Minimum of Months | 33.25 | 24.17 | 8.82 | 45.22 | 23.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 95.81 | 78.40 | 21.36 | 163.19 | 51.32 | 1.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179603E+09 | 0.112089E+09 | 67514421.63 | 0.333664E+09 | 0.349277E+09 |
February | 0.130182E+09 | 62831055.64 | 67350566.25 | 0.186478E+09 | 0.303777E+09 |
March | 0.191521E+09 | 91389976.21 | 0.100131E+09 | 0.325640E+09 | 0.306803E+09 |
April | 0.282307E+09 | 0.160249E+09 | 0.122058E+09 | 0.621343E+09 | 0.206124E+09 |
May | 0.293354E+09 | 0.163656E+09 | 0.129698E+09 | 0.693682E+09 | 0.164531E+09 |
June | 0.301473E+09 | 0.176848E+09 | 0.124625E+09 | 0.828936E+09 | 79332680.75 |
July | 0.227188E+09 | 0.105777E+09 | 0.121411E+09 | 0.632201E+09 | 70758048.05 |
August | 0.216871E+09 | 0.108613E+09 | 0.108257E+09 | 0.606260E+09 | 87549273.88 |
September | 0.183050E+09 | 76805181.63 | 0.106245E+09 | 0.476961E+09 | 0.112668E+09 |
October | 0.193244E+09 | 0.110274E+09 | 82969504.49 | 0.394386E+09 | 0.277463E+09 |
November | 0.171969E+09 | 0.103561E+09 | 68407713.34 | 0.297989E+09 | 0.351923E+09 |
December | 0.144551E+09 | 82632481.39 | 61918727.12 | 0.229756E+09 | 0.426652E+09 |
Annual Sum or Average | 0.251531E+10 | 0.135473E+10 | 0.116059E+10 | 0.562730E+10 | 0.273686E+10 |
Minimum of Months | 0.130182E+09 | 62831055.64 | 61918727.12 | 0.186478E+09 | 70758048.05 |
Maximum of Months | 0.301473E+09 | 0.176848E+09 | 0.129698E+09 | 0.828936E+09 | 0.426652E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179603E+09 | 0.112089E+09 | 67514421.63 | 0.333664E+09 | 0.349277E+09 |
February | 0.130182E+09 | 62831055.64 | 67350566.25 | 0.186478E+09 | 0.303777E+09 |
March | 0.191521E+09 | 91389976.21 | 0.100131E+09 | 0.325640E+09 | 0.306803E+09 |
April | 0.282307E+09 | 0.160249E+09 | 0.122058E+09 | 0.621343E+09 | 0.206124E+09 |
May | 0.293354E+09 | 0.163656E+09 | 0.129698E+09 | 0.693682E+09 | 0.164531E+09 |
June | 0.301473E+09 | 0.176848E+09 | 0.124625E+09 | 0.828936E+09 | 79332680.75 |
July | 0.227188E+09 | 0.105777E+09 | 0.121411E+09 | 0.632201E+09 | 70758048.05 |
August | 0.216871E+09 | 0.108613E+09 | 0.108257E+09 | 0.606260E+09 | 87549273.88 |
September | 0.183050E+09 | 76805181.63 | 0.106245E+09 | 0.476961E+09 | 0.112668E+09 |
October | 0.193244E+09 | 0.110274E+09 | 82969504.49 | 0.394386E+09 | 0.277463E+09 |
November | 0.171969E+09 | 0.103561E+09 | 68407713.34 | 0.297989E+09 | 0.351923E+09 |
December | 0.144551E+09 | 82632481.39 | 61918727.12 | 0.229756E+09 | 0.426652E+09 |
Annual Sum or Average | 0.251531E+10 | 0.135473E+10 | 0.116059E+10 | 0.562730E+10 | 0.273686E+10 |
Minimum of Months | 0.130182E+09 | 62831055.64 | 61918727.12 | 0.186478E+09 | 70758048.05 |
Maximum of Months | 0.301473E+09 | 0.176848E+09 | 0.129698E+09 | 0.828936E+09 | 0.426652E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 30770965.37 | 0.00 | 30770965.37 | 26263429.91 | 0.207185E+09 |
February | 31669539.27 | 0.00 | 31669539.27 | 14712761.18 | 0.184221E+09 |
March | 46614272.89 | 8632.97 | 46605639.92 | 49311253.86 | 0.185861E+09 |
April | 55398365.83 | 1006680.94 | 54391684.89 | 0.107181E+09 | 0.119866E+09 |
May | 68432653.84 | 7163623.99 | 61269029.85 | 0.149678E+09 | 87929549.48 |
June | 76833198.10 | 15701221.24 | 61131976.86 | 0.237982E+09 | 41847206.12 |
July | 66989102.56 | 7986459.08 | 59002643.49 | 0.208303E+09 | 38724901.73 |
August | 53760328.09 | 1861133.21 | 51899194.88 | 0.177456E+09 | 49796371.98 |
September | 48580604.36 | 44468.42 | 48536135.94 | 0.140816E+09 | 65389566.38 |
October | 38806286.25 | 0.00 | 38806286.25 | 61542776.18 | 0.165262E+09 |
November | 31289761.01 | 0.00 | 31289761.01 | 21202443.11 | 0.210948E+09 |
December | 28742904.03 | 0.00 | 28742904.03 | 13871858.31 | 0.256239E+09 |
Annual Sum or Average | 0.577888E+09 | 33772219.84 | 0.544116E+09 | 0.120832E+10 | 0.161327E+10 |
Minimum of Months | 28742904.03 | 0.00 | 28742904.03 | 13871858.31 | 38724901.73 |
Maximum of Months | 76833198.10 | 15701221.24 | 61269029.85 | 0.237982E+09 | 0.256239E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 30770213.30 | 0.00 | 30770213.30 | 26263043.74 | 0.207183E+09 |
February | 31668652.25 | 0.00 | 31668652.25 | 14711946.79 | 0.184220E+09 |
March | 46612966.78 | 8632.56 | 46604334.22 | 49309715.32 | 0.185860E+09 |
April | 55397071.44 | 1006633.75 | 54390437.69 | 0.107180E+09 | 0.119864E+09 |
May | 68430899.39 | 7163288.22 | 61267611.18 | 0.149676E+09 | 87927909.51 |
June | 76831077.74 | 15700485.30 | 61130592.44 | 0.237980E+09 | 41845982.19 |
July | 66987209.68 | 7986084.74 | 59001124.94 | 0.208300E+09 | 38724068.51 |
August | 53758958.59 | 1861045.98 | 51897912.61 | 0.177455E+09 | 49795262.12 |
September | 48579240.77 | 44466.34 | 48534774.44 | 0.140815E+09 | 65388408.32 |
October | 38805333.58 | 0.00 | 38805333.58 | 61542084.97 | 0.165260E+09 |
November | 31288949.63 | 0.00 | 31288949.63 | 21201907.14 | 0.210947E+09 |
December | 28742162.58 | 0.00 | 28742162.58 | 13871509.47 | 0.256237E+09 |
Annual Sum or Average | 0.577873E+09 | 33770636.89 | 0.544102E+09 | 0.120831E+10 | 0.161325E+10 |
Minimum of Months | 28742162.58 | 0.00 | 28742162.58 | 13871509.47 | 38724068.51 |
Maximum of Months | 76831077.74 | 15700485.30 | 61267611.18 | 0.237980E+09 | 0.256237E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.103082E+09 | 79462926.51 | 23619182.19 | 0.153942E+09 | 0.115714E+09 |
February | 91042068.29 | 58479144.86 | 32562923.43 | 0.129008E+09 | 89372865.20 |
March | 0.142988E+09 | 91569246.98 | 51418329.49 | 0.222287E+09 | 0.101662E+09 |
April | 0.214084E+09 | 0.165482E+09 | 48601812.18 | 0.350860E+09 | 0.104247E+09 |
May | 0.243634E+09 | 0.191494E+09 | 52139374.70 | 0.398998E+09 | 0.106721E+09 |
June | 0.248349E+09 | 0.203207E+09 | 45142365.77 | 0.422976E+09 | 79004894.35 |
July | 0.207878E+09 | 0.150726E+09 | 57152024.37 | 0.352616E+09 | 63041830.47 |
August | 0.191551E+09 | 0.141774E+09 | 49776931.23 | 0.327503E+09 | 75298131.57 |
September | 0.148982E+09 | 93619932.19 | 55362182.11 | 0.247092E+09 | 75068682.64 |
October | 0.136908E+09 | 0.102941E+09 | 33966505.46 | 0.204532E+09 | 0.128796E+09 |
November | 97919632.94 | 70763218.51 | 27156414.42 | 0.135468E+09 | 0.121258E+09 |
December | 89051171.91 | 64971100.86 | 24080071.05 | 0.121112E+09 | 0.137450E+09 |
Annual Sum or Average | 0.191547E+10 | 0.141449E+10 | 0.500978E+09 | 0.306639E+10 | 0.119763E+10 |
Minimum of Months | 89051171.91 | 58479144.86 | 23619182.19 | 0.121112E+09 | 63041830.47 |
Maximum of Months | 0.248349E+09 | 0.203207E+09 | 57152024.37 | 0.422976E+09 | 0.137450E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.103082E+09 | 79462926.51 | 23619182.19 | 0.153942E+09 | 0.115714E+09 |
February | 91042068.29 | 58479144.86 | 32562923.43 | 0.129008E+09 | 89372865.20 |
March | 0.142988E+09 | 91569246.98 | 51418329.49 | 0.222287E+09 | 0.101662E+09 |
April | 0.214084E+09 | 0.165482E+09 | 48601812.18 | 0.350860E+09 | 0.104247E+09 |
May | 0.243634E+09 | 0.191494E+09 | 52139374.70 | 0.398998E+09 | 0.106721E+09 |
June | 0.248349E+09 | 0.203207E+09 | 45142365.77 | 0.422976E+09 | 79004894.35 |
July | 0.207878E+09 | 0.150726E+09 | 57152024.37 | 0.352616E+09 | 63041830.47 |
August | 0.191551E+09 | 0.141774E+09 | 49776931.23 | 0.327503E+09 | 75298131.57 |
September | 0.148982E+09 | 93619932.19 | 55362182.11 | 0.247092E+09 | 75068682.64 |
October | 0.136908E+09 | 0.102941E+09 | 33966505.46 | 0.204532E+09 | 0.128796E+09 |
November | 97919632.94 | 70763218.51 | 27156414.42 | 0.135468E+09 | 0.121258E+09 |
December | 89051171.91 | 64971100.86 | 24080071.05 | 0.121112E+09 | 0.137450E+09 |
Annual Sum or Average | 0.191547E+10 | 0.141449E+10 | 0.500978E+09 | 0.306639E+10 | 0.119763E+10 |
Minimum of Months | 89051171.91 | 58479144.86 | 23619182.19 | 0.121112E+09 | 63041830.47 |
Maximum of Months | 0.248349E+09 | 0.203207E+09 | 57152024.37 | 0.422976E+09 | 0.137450E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.103082E+09 | 79462926.51 | 23619182.19 | 0.153942E+09 | 0.115714E+09 |
February | 91042068.29 | 58479144.86 | 32562923.43 | 0.129008E+09 | 89372865.20 |
March | 0.142988E+09 | 91569246.98 | 51418329.49 | 0.222287E+09 | 0.101662E+09 |
April | 0.214084E+09 | 0.165482E+09 | 48601812.18 | 0.350860E+09 | 0.104247E+09 |
May | 0.243634E+09 | 0.191494E+09 | 52139374.70 | 0.398998E+09 | 0.106721E+09 |
June | 0.248349E+09 | 0.203207E+09 | 45142365.77 | 0.422976E+09 | 79004894.35 |
July | 0.207878E+09 | 0.150726E+09 | 57152024.37 | 0.352616E+09 | 63041830.47 |
August | 0.191551E+09 | 0.141774E+09 | 49776931.23 | 0.327503E+09 | 75298131.57 |
September | 0.148982E+09 | 93619932.19 | 55362182.11 | 0.247092E+09 | 75068682.64 |
October | 0.136908E+09 | 0.102941E+09 | 33966505.46 | 0.204532E+09 | 0.128796E+09 |
November | 97919632.94 | 70763218.51 | 27156414.42 | 0.135468E+09 | 0.121258E+09 |
December | 89051171.91 | 64971100.86 | 24080071.05 | 0.121112E+09 | 0.137450E+09 |
Annual Sum or Average | 0.191547E+10 | 0.141449E+10 | 0.500978E+09 | 0.306639E+10 | 0.119763E+10 |
Minimum of Months | 89051171.91 | 58479144.86 | 23619182.19 | 0.121112E+09 | 63041830.47 |
Maximum of Months | 0.248349E+09 | 0.203207E+09 | 57152024.37 | 0.422976E+09 | 0.137450E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.103082E+09 | 79462926.51 | 23619182.19 | 0.153942E+09 | 0.115714E+09 |
February | 91042068.29 | 58479144.86 | 32562923.43 | 0.129008E+09 | 89372865.20 |
March | 0.142988E+09 | 91569246.98 | 51418329.49 | 0.222287E+09 | 0.101662E+09 |
April | 0.214084E+09 | 0.165482E+09 | 48601812.18 | 0.350860E+09 | 0.104247E+09 |
May | 0.243634E+09 | 0.191494E+09 | 52139374.70 | 0.398998E+09 | 0.106721E+09 |
June | 0.248349E+09 | 0.203207E+09 | 45142365.77 | 0.422976E+09 | 79004894.35 |
July | 0.207878E+09 | 0.150726E+09 | 57152024.37 | 0.352616E+09 | 63041830.47 |
August | 0.191551E+09 | 0.141774E+09 | 49776931.23 | 0.327503E+09 | 75298131.57 |
September | 0.148982E+09 | 93619932.19 | 55362182.11 | 0.247092E+09 | 75068682.64 |
October | 0.136908E+09 | 0.102941E+09 | 33966505.46 | 0.204532E+09 | 0.128796E+09 |
November | 97919632.94 | 70763218.51 | 27156414.42 | 0.135468E+09 | 0.121258E+09 |
December | 89051171.91 | 64971100.86 | 24080071.05 | 0.121112E+09 | 0.137450E+09 |
Annual Sum or Average | 0.191547E+10 | 0.141449E+10 | 0.500978E+09 | 0.306639E+10 | 0.119763E+10 |
Minimum of Months | 89051171.91 | 58479144.86 | 23619182.19 | 0.121112E+09 | 63041830.47 |
Maximum of Months | 0.248349E+09 | 0.203207E+09 | 57152024.37 | 0.422976E+09 | 0.137450E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.103082E+09 | 79462926.51 | 23619182.19 | 0.153942E+09 | 0.115714E+09 |
February | 91042068.29 | 58479144.86 | 32562923.43 | 0.129008E+09 | 89372865.20 |
March | 0.142988E+09 | 91569246.98 | 51418329.49 | 0.222287E+09 | 0.101662E+09 |
April | 0.214084E+09 | 0.165482E+09 | 48601812.18 | 0.350860E+09 | 0.104247E+09 |
May | 0.243634E+09 | 0.191494E+09 | 52139374.70 | 0.398998E+09 | 0.106721E+09 |
June | 0.248349E+09 | 0.203207E+09 | 45142365.77 | 0.422976E+09 | 79004894.35 |
July | 0.207878E+09 | 0.150726E+09 | 57152024.37 | 0.352616E+09 | 63041830.47 |
August | 0.191551E+09 | 0.141774E+09 | 49776931.23 | 0.327503E+09 | 75298131.57 |
September | 0.148982E+09 | 93619932.19 | 55362182.11 | 0.247092E+09 | 75068682.64 |
October | 0.136908E+09 | 0.102941E+09 | 33966505.46 | 0.204532E+09 | 0.128796E+09 |
November | 97919632.94 | 70763218.51 | 27156414.42 | 0.135468E+09 | 0.121258E+09 |
December | 89051171.91 | 64971100.86 | 24080071.05 | 0.121112E+09 | 0.137450E+09 |
Annual Sum or Average | 0.191547E+10 | 0.141449E+10 | 0.500978E+09 | 0.306639E+10 | 0.119763E+10 |
Minimum of Months | 89051171.91 | 58479144.86 | 23619182.19 | 0.121112E+09 | 63041830.47 |
Maximum of Months | 0.248349E+09 | 0.203207E+09 | 57152024.37 | 0.422976E+09 | 0.137450E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.103082E+09 | 79462926.51 | 23619182.19 | 0.153942E+09 | 0.115714E+09 |
February | 91042068.29 | 58479144.86 | 32562923.43 | 0.129008E+09 | 89372865.20 |
March | 0.142988E+09 | 91569246.98 | 51418329.49 | 0.222287E+09 | 0.101662E+09 |
April | 0.214084E+09 | 0.165482E+09 | 48601812.18 | 0.350860E+09 | 0.104247E+09 |
May | 0.243634E+09 | 0.191494E+09 | 52139374.70 | 0.398998E+09 | 0.106721E+09 |
June | 0.248349E+09 | 0.203207E+09 | 45142365.77 | 0.422976E+09 | 79004894.35 |
July | 0.207878E+09 | 0.150726E+09 | 57152024.37 | 0.352616E+09 | 63041830.47 |
August | 0.191551E+09 | 0.141774E+09 | 49776931.23 | 0.327503E+09 | 75298131.57 |
September | 0.148982E+09 | 93619932.19 | 55362182.11 | 0.247092E+09 | 75068682.64 |
October | 0.136908E+09 | 0.102941E+09 | 33966505.46 | 0.204532E+09 | 0.128796E+09 |
November | 97919632.94 | 70763218.51 | 27156414.42 | 0.135468E+09 | 0.121258E+09 |
December | 89051171.91 | 64971100.86 | 24080071.05 | 0.121112E+09 | 0.137450E+09 |
Annual Sum or Average | 0.191547E+10 | 0.141449E+10 | 0.500978E+09 | 0.306639E+10 | 0.119763E+10 |
Minimum of Months | 89051171.91 | 58479144.86 | 23619182.19 | 0.121112E+09 | 63041830.47 |
Maximum of Months | 0.248349E+09 | 0.203207E+09 | 57152024.37 | 0.422976E+09 | 0.137450E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.103082E+09 | 79462926.51 | 23619182.19 | 0.153942E+09 | 0.115714E+09 |
February | 91042068.29 | 58479144.86 | 32562923.43 | 0.129008E+09 | 89372865.20 |
March | 0.142988E+09 | 91569246.98 | 51418329.49 | 0.222287E+09 | 0.101662E+09 |
April | 0.214084E+09 | 0.165482E+09 | 48601812.18 | 0.350860E+09 | 0.104247E+09 |
May | 0.243634E+09 | 0.191494E+09 | 52139374.70 | 0.398998E+09 | 0.106721E+09 |
June | 0.248349E+09 | 0.203207E+09 | 45142365.77 | 0.422976E+09 | 79004894.35 |
July | 0.207878E+09 | 0.150726E+09 | 57152024.37 | 0.352616E+09 | 63041830.47 |
August | 0.191551E+09 | 0.141774E+09 | 49776931.23 | 0.327503E+09 | 75298131.57 |
September | 0.148982E+09 | 93619932.19 | 55362182.11 | 0.247092E+09 | 75068682.64 |
October | 0.136908E+09 | 0.102941E+09 | 33966505.46 | 0.204532E+09 | 0.128796E+09 |
November | 97919632.94 | 70763218.51 | 27156414.42 | 0.135468E+09 | 0.121258E+09 |
December | 89051171.91 | 64971100.86 | 24080071.05 | 0.121112E+09 | 0.137450E+09 |
Annual Sum or Average | 0.191547E+10 | 0.141449E+10 | 0.500978E+09 | 0.306639E+10 | 0.119763E+10 |
Minimum of Months | 89051171.91 | 58479144.86 | 23619182.19 | 0.121112E+09 | 63041830.47 |
Maximum of Months | 0.248349E+09 | 0.203207E+09 | 57152024.37 | 0.422976E+09 | 0.137450E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.103082E+09 | 79462926.51 | 23619182.19 | 0.153942E+09 | 0.115714E+09 |
February | 91042068.29 | 58479144.86 | 32562923.43 | 0.129008E+09 | 89372865.20 |
March | 0.142988E+09 | 91569246.98 | 51418329.49 | 0.222287E+09 | 0.101662E+09 |
April | 0.214084E+09 | 0.165482E+09 | 48601812.18 | 0.350860E+09 | 0.104247E+09 |
May | 0.243634E+09 | 0.191494E+09 | 52139374.70 | 0.398998E+09 | 0.106721E+09 |
June | 0.248349E+09 | 0.203207E+09 | 45142365.77 | 0.422976E+09 | 79004894.35 |
July | 0.207878E+09 | 0.150726E+09 | 57152024.37 | 0.352616E+09 | 63041830.47 |
August | 0.191551E+09 | 0.141774E+09 | 49776931.23 | 0.327503E+09 | 75298131.57 |
September | 0.148982E+09 | 93619932.19 | 55362182.11 | 0.247092E+09 | 75068682.64 |
October | 0.136908E+09 | 0.102941E+09 | 33966505.46 | 0.204532E+09 | 0.128796E+09 |
November | 97919632.94 | 70763218.51 | 27156414.42 | 0.135468E+09 | 0.121258E+09 |
December | 89051171.91 | 64971100.86 | 24080071.05 | 0.121112E+09 | 0.137450E+09 |
Annual Sum or Average | 0.191547E+10 | 0.141449E+10 | 0.500978E+09 | 0.306639E+10 | 0.119763E+10 |
Minimum of Months | 89051171.91 | 58479144.86 | 23619182.19 | 0.121112E+09 | 63041830.47 |
Maximum of Months | 0.248349E+09 | 0.203207E+09 | 57152024.37 | 0.422976E+09 | 0.137450E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.103082E+09 | 79462926.51 | 23619182.19 | 0.153942E+09 | 0.115714E+09 |
February | 91042068.29 | 58479144.86 | 32562923.43 | 0.129008E+09 | 89372865.20 |
March | 0.142988E+09 | 91569246.98 | 51418329.49 | 0.222287E+09 | 0.101662E+09 |
April | 0.214084E+09 | 0.165482E+09 | 48601812.18 | 0.350860E+09 | 0.104247E+09 |
May | 0.243634E+09 | 0.191494E+09 | 52139374.70 | 0.398998E+09 | 0.106721E+09 |
June | 0.248349E+09 | 0.203207E+09 | 45142365.77 | 0.422976E+09 | 79004894.35 |
July | 0.207878E+09 | 0.150726E+09 | 57152024.37 | 0.352616E+09 | 63041830.47 |
August | 0.191551E+09 | 0.141774E+09 | 49776931.23 | 0.327503E+09 | 75298131.57 |
September | 0.148982E+09 | 93619932.19 | 55362182.11 | 0.247092E+09 | 75068682.64 |
October | 0.136908E+09 | 0.102941E+09 | 33966505.46 | 0.204532E+09 | 0.128796E+09 |
November | 97919632.94 | 70763218.51 | 27156414.42 | 0.135468E+09 | 0.121258E+09 |
December | 89051171.91 | 64971100.86 | 24080071.05 | 0.121112E+09 | 0.137450E+09 |
Annual Sum or Average | 0.191547E+10 | 0.141449E+10 | 0.500978E+09 | 0.306639E+10 | 0.119763E+10 |
Minimum of Months | 89051171.91 | 58479144.86 | 23619182.19 | 0.121112E+09 | 63041830.47 |
Maximum of Months | 0.248349E+09 | 0.203207E+09 | 57152024.37 | 0.422976E+09 | 0.137450E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.103082E+09 | 79462926.51 | 23619182.19 | 0.153942E+09 | 0.115714E+09 |
February | 91042068.29 | 58479144.86 | 32562923.43 | 0.129008E+09 | 89372865.20 |
March | 0.142988E+09 | 91569246.98 | 51418329.49 | 0.222287E+09 | 0.101662E+09 |
April | 0.214084E+09 | 0.165482E+09 | 48601812.18 | 0.350860E+09 | 0.104247E+09 |
May | 0.243634E+09 | 0.191494E+09 | 52139374.70 | 0.398998E+09 | 0.106721E+09 |
June | 0.248349E+09 | 0.203207E+09 | 45142365.77 | 0.422976E+09 | 79004894.35 |
July | 0.207878E+09 | 0.150726E+09 | 57152024.37 | 0.352616E+09 | 63041830.47 |
August | 0.191551E+09 | 0.141774E+09 | 49776931.23 | 0.327503E+09 | 75298131.57 |
September | 0.148982E+09 | 93619932.19 | 55362182.11 | 0.247092E+09 | 75068682.64 |
October | 0.136908E+09 | 0.102941E+09 | 33966505.46 | 0.204532E+09 | 0.128796E+09 |
November | 97919632.94 | 70763218.51 | 27156414.42 | 0.135468E+09 | 0.121258E+09 |
December | 89051171.91 | 64971100.86 | 24080071.05 | 0.121112E+09 | 0.137450E+09 |
Annual Sum or Average | 0.191547E+10 | 0.141449E+10 | 0.500978E+09 | 0.306639E+10 | 0.119763E+10 |
Minimum of Months | 89051171.91 | 58479144.86 | 23619182.19 | 0.121112E+09 | 63041830.47 |
Maximum of Months | 0.248349E+09 | 0.203207E+09 | 57152024.37 | 0.422976E+09 | 0.137450E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 266.04 | 412.79 | 157.09 | 83.70 | 73.39 | 0.00 | 0.00 |
February | 161.62 | 398.72 | 133.81 | 51.94 | 81.86 | 0.00 | 0.00 |
March | 275.12 | 363.01 | 177.82 | 68.25 | 109.57 | 0.00 | 0.00 |
April | 561.37 | 250.77 | 260.57 | 124.43 | 136.15 | 0.00 | 0.00 |
May | 628.44 | 187.20 | 270.15 | 127.55 | 142.60 | 0.00 | 0.00 |
June | 820.00 | 90.27 | 291.90 | 148.57 | 143.33 | 0.00 | 0.00 |
July | 625.98 | 80.11 | 219.67 | 84.95 | 134.72 | 0.00 | 0.00 |
August | 584.79 | 102.14 | 202.08 | 82.49 | 119.59 | 0.00 | 0.00 |
September | 476.63 | 137.34 | 178.73 | 59.30 | 119.43 | 0.00 | 0.00 |
October | 337.83 | 327.97 | 173.27 | 82.34 | 90.93 | 0.00 | 0.00 |
November | 241.42 | 429.44 | 156.84 | 79.91 | 76.93 | 0.00 | 0.00 |
December | 176.66 | 504.67 | 129.40 | 61.70 | 67.70 | 0.00 | 0.00 |
Annual Sum or Average | 430.82 | 273.19 | 196.17 | 88.06 | 108.11 | 0.00 | 0.00 |
Minimum of Months | 161.62 | 80.11 | 129.40 | 51.94 | 67.70 | 0.00 | 0.00 |
Maximum of Months | 820.00 | 504.67 | 291.90 | 148.57 | 143.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 574.75 | 432.02 | 384.86 | 296.68 | 88.18 | 0.00 | 0.00 |
February | 533.27 | 369.43 | 376.33 | 241.73 | 134.60 | 0.00 | 0.00 |
March | 829.92 | 379.56 | 533.85 | 341.88 | 191.97 | 0.00 | 0.00 |
April | 1353.63 | 402.19 | 825.94 | 638.44 | 187.51 | 0.00 | 0.00 |
May | 1489.69 | 398.45 | 909.62 | 714.96 | 194.67 | 0.00 | 0.00 |
June | 1631.85 | 304.80 | 958.14 | 783.98 | 174.16 | 0.00 | 0.00 |
July | 1316.52 | 235.37 | 776.13 | 562.74 | 213.38 | 0.00 | 0.00 |
August | 1222.76 | 281.13 | 715.17 | 529.33 | 185.85 | 0.00 | 0.00 |
September | 953.29 | 289.61 | 574.78 | 361.19 | 213.59 | 0.00 | 0.00 |
October | 763.63 | 480.87 | 511.16 | 384.34 | 126.82 | 0.00 | 0.00 |
November | 522.64 | 467.82 | 377.78 | 273.01 | 104.77 | 0.00 | 0.00 |
December | 452.18 | 513.18 | 332.48 | 242.57 | 89.90 | 0.00 | 0.00 |
Annual Sum or Average | 972.35 | 379.77 | 607.39 | 448.53 | 158.86 | 0.00 | 0.00 |
Minimum of Months | 452.18 | 235.37 | 332.48 | 241.73 | 88.18 | 0.00 | 0.00 |
Maximum of Months | 1631.85 | 513.18 | 958.14 | 783.98 | 213.59 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.712555E+09 | 0.110562E+10 | 0.420748E+09 | 0.224178E+09 | 0.196570E+09 | 0.00 | 0.00 |
February | 0.390982E+09 | 0.964595E+09 | 0.323701E+09 | 0.125662E+09 | 0.198039E+09 | 0.00 | 0.00 |
March | 0.736870E+09 | 0.972296E+09 | 0.476270E+09 | 0.182797E+09 | 0.293473E+09 | 0.00 | 0.00 |
April | 0.145507E+10 | 0.649999E+09 | 0.675410E+09 | 0.322512E+09 | 0.352898E+09 | 0.00 | 0.00 |
May | 0.168321E+10 | 0.501409E+09 | 0.723572E+09 | 0.341639E+09 | 0.381933E+09 | 0.00 | 0.00 |
June | 0.212545E+10 | 0.233970E+09 | 0.756611E+09 | 0.385099E+09 | 0.371512E+09 | 0.00 | 0.00 |
July | 0.167661E+10 | 0.214572E+09 | 0.588352E+09 | 0.227527E+09 | 0.360826E+09 | 0.00 | 0.00 |
August | 0.156631E+10 | 0.273570E+09 | 0.541261E+09 | 0.220949E+09 | 0.320312E+09 | 0.00 | 0.00 |
September | 0.123541E+10 | 0.355976E+09 | 0.463261E+09 | 0.153699E+09 | 0.309561E+09 | 0.00 | 0.00 |
October | 0.904851E+09 | 0.878443E+09 | 0.464099E+09 | 0.220549E+09 | 0.243551E+09 | 0.00 | 0.00 |
November | 0.625755E+09 | 0.111311E+10 | 0.406517E+09 | 0.207122E+09 | 0.199394E+09 | 0.00 | 0.00 |
December | 0.473173E+09 | 0.135170E+10 | 0.346587E+09 | 0.165265E+09 | 0.181323E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135862E+11 | 0.861526E+10 | 0.618639E+10 | 0.277700E+10 | 0.340939E+10 | 0.00 | 0.00 |
Minimum of Months | 0.390982E+09 | 0.214572E+09 | 0.323701E+09 | 0.125662E+09 | 0.181323E+09 | 0.00 | 0.00 |
Maximum of Months | 0.212545E+10 | 0.135170E+10 | 0.756611E+09 | 0.385099E+09 | 0.381933E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.153941E+10 | 0.115714E+10 | 0.103082E+10 | 0.794629E+09 | 0.236192E+09 | 0.00 | 0.00 |
February | 0.129008E+10 | 0.893727E+09 | 0.910421E+09 | 0.584791E+09 | 0.325629E+09 | 0.00 | 0.00 |
March | 0.222287E+10 | 0.101662E+10 | 0.142988E+10 | 0.915692E+09 | 0.514183E+09 | 0.00 | 0.00 |
April | 0.350860E+10 | 0.104247E+10 | 0.214084E+10 | 0.165482E+10 | 0.486018E+09 | 0.00 | 0.00 |
May | 0.398998E+10 | 0.106721E+10 | 0.243634E+10 | 0.191494E+10 | 0.521394E+09 | 0.00 | 0.00 |
June | 0.422976E+10 | 0.790048E+09 | 0.248349E+10 | 0.203207E+10 | 0.451424E+09 | 0.00 | 0.00 |
July | 0.352616E+10 | 0.630416E+09 | 0.207878E+10 | 0.150726E+10 | 0.571520E+09 | 0.00 | 0.00 |
August | 0.327503E+10 | 0.752980E+09 | 0.191551E+10 | 0.141774E+10 | 0.497769E+09 | 0.00 | 0.00 |
September | 0.247092E+10 | 0.750682E+09 | 0.148982E+10 | 0.936199E+09 | 0.553622E+09 | 0.00 | 0.00 |
October | 0.204532E+10 | 0.128796E+10 | 0.136908E+10 | 0.102941E+10 | 0.339665E+09 | 0.00 | 0.00 |
November | 0.135468E+10 | 0.121258E+10 | 0.979196E+09 | 0.707632E+09 | 0.271564E+09 | 0.00 | 0.00 |
December | 0.121111E+10 | 0.137450E+10 | 0.890512E+09 | 0.649711E+09 | 0.240801E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.306639E+11 | 0.119763E+11 | 0.191547E+11 | 0.141449E+11 | 0.500978E+10 | 0.00 | 0.00 |
Minimum of Months | 0.121111E+10 | 0.630416E+09 | 0.890512E+09 | 0.584791E+09 | 0.236192E+09 | 0.00 | 0.00 |
Maximum of Months | 0.422976E+10 | 0.137450E+10 | 0.248349E+10 | 0.203207E+10 | 0.571520E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.45 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.34 | 6.24 | 2.64 | 2.52 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.66 | 1.96 | 3.53 | 3.01 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.11 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.03 | -4.9 | 3.62 | 8.59 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.25 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.97 | 9.86 | 3.72 | 19.27 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.13 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.57 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.96 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.79 | 1.49 | 3.02 | 1.82 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.26 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.55 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.26 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.13 | 11.45 | 3.72 | 19.27 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.69 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.41 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.76 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.53 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.53 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.69 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.36 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.22 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.78 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 18.97 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.17 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.86 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.69 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.78 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.1 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.58 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.2 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.39 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.95 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.22 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.50 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.01 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.46 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.3 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.3 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.3 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.01 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.72 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.16 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.67 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.53 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.15 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.10 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.17 | 16-AUG-10:50 | 34.50 | 17.17 | 2.27 | 23.90 | 134.33 | 837.00 |
September | 22.21 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.52 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.04 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.04 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.15 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.72 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.69 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 13.98 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.74 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.15 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.10 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.16 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.15 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.798290E+09 | -720550711.0 | 0.00 | 0.00 | 744.00 | 0.00 | -77739756.9 | 58.99 | 0.00 | 0.00 |
February | 0.726420E+09 | -655399958.3 | 0.00 | 0.00 | 672.00 | 0.00 | -71020079.3 | 58.99 | 0.00 | 0.00 |
March | 0.805176E+09 | -728653554.5 | 0.00 | 0.00 | 744.00 | 0.00 | -76522308.0 | 58.99 | 0.00 | 0.00 |
April | 0.692078E+09 | -623088534.6 | 0.00 | 0.00 | 720.00 | 0.00 | -68989368.6 | 58.99 | 0.00 | 0.00 |
May | 0.657939E+09 | -587767795.1 | 0.00 | 0.00 | 744.00 | 0.00 | -70170893.2 | 58.98 | 0.00 | 0.00 |
June | 0.602389E+09 | -535587729.4 | 0.00 | 0.00 | 720.00 | 0.00 | -66801681.4 | 58.99 | 0.00 | 0.00 |
July | 0.562722E+09 | -494119218.7 | 0.00 | 0.00 | 744.00 | 0.00 | -68602530.0 | 58.99 | 0.00 | 0.00 |
August | 0.607849E+09 | -538562528.9 | 0.00 | 0.00 | 744.00 | 0.00 | -69286621.0 | 58.99 | 0.00 | 0.00 |
September | 0.604059E+09 | -536999352.7 | 0.00 | 0.00 | 720.00 | 0.00 | -67059386.6 | 58.99 | 0.00 | 0.00 |
October | 0.664466E+09 | -592711876.1 | 0.00 | 0.00 | 744.00 | 0.00 | -71754071.5 | 58.99 | 0.00 | 0.00 |
November | 0.697532E+09 | -624744097.2 | 0.00 | 0.00 | 720.00 | 0.00 | -72788201.7 | 58.99 | 0.00 | 0.00 |
December | 0.775899E+09 | -697057610.1 | 0.00 | 0.00 | 744.00 | 0.00 | -78841813.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.819482E+10 | -.733524E+10 | 8760.00 | -859576711.8 | 58.99 | |||||
Minimum of Months | 0.562722E+09 | -728653554.5 | 0.00 | 0.00 | 672.00 | 0.00 | -78841813.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.805176E+09 | -494119218.7 | 0.00 | 0.00 | 744.00 | 0.00 | -66801681.4 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 309.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 380.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 403.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 399.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 361.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 350.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 348.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 288.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 290.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4135.50 | ||||||||||
Minimum of Months | 241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.234147E+09 | 29406.46 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.234422E+09 | 29406.46 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204954E+09 | 29406.46 | 27-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 666269.11 | 1474.21 | 29-APR-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2409521.34 | 4330.39 | 27-MAY-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3913027.81 | 4467.26 | 21-OCT-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 37637596.80 | 7044.22 | 24-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.428449E+09 | 29406.46 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114660E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.428449E+09 | 29406.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.495269E+09 | 56627.69 | 01-JAN-07:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16356415.10 | 21829.85 | 07-DEC-06:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.511626E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.495269E+09 | 56627.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.154814E+10 | 0.154814E+10 | 7477.57 | 31-JAN-16:30 | 7477.57 | 0.00 |
February | 0.00 | 0.00 | 68788993.82 | 65000988.66 | 2912.28 | 18-FEB-14:40 | 2623.69 | 0.00 |
March | 0.00 | 0.00 | 0.162961E+10 | 0.162258E+10 | 8059.59 | 18-MAR-16:00 | 8059.59 | 0.00 |
April | 0.00 | 0.00 | 0.694476E+10 | 0.694426E+10 | 21677.25 | 25-APR-05:01 | 21677.25 | 0.00 |
May | 0.00 | 0.00 | 0.955508E+10 | 0.955508E+10 | 22098.75 | 29-MAY-19:11 | 22098.75 | 0.00 |
June | 0.00 | 0.00 | 0.128352E+11 | 0.128216E+11 | 23069.53 | 30-JUN-05:01 | 23069.53 | 0.00 |
July | 0.00 | 0.00 | 0.133449E+11 | 0.122541E+11 | 28082.59 | 14-JUL-05:01 | 14538.44 | 0.00 |
August | 0.00 | 0.00 | 0.140692E+11 | 0.127989E+11 | 26723.34 | 01-AUG-05:01 | 16818.28 | 0.00 |
September | 0.00 | 0.00 | 0.120068E+11 | 0.108233E+11 | 26984.37 | 02-SEP-05:01 | 17016.19 | 0.00 |
October | 0.00 | 0.00 | 0.600280E+10 | 0.576351E+10 | 25693.02 | 03-OCT-05:01 | 16495.24 | 0.00 |
November | 0.00 | 0.00 | 0.190966E+10 | 0.185639E+10 | 22435.48 | 01-NOV-05:01 | 19096.04 | 0.00 |
December | 0.00 | 0.00 | 0.512344E+09 | 0.512343E+09 | 6040.42 | 22-DEC-16:30 | 6040.42 | 0.00 |
Annual Sum or Average | 0.804271E+11 | 0.765652E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 68788993.82 | 65000988.66 | 2912.28 | 2623.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.140692E+11 | 0.128216E+11 | 28082.59 | 23069.53 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.457744E+09 | 0.457744E+09 | 11532.07 | 31-JAN-16:00 | 11532.07 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.142118E+10 | 0.141869E+10 | 17812.35 | 18-MAR-15:00 | 17812.35 | 0.00 |
April | 0.00 | 0.00 | 0.190569E+11 | 0.190548E+11 | 74905.51 | 16-APR-16:40 | 74905.51 | 0.00 |
May | 0.00 | 0.00 | 0.308396E+11 | 0.308396E+11 | 75266.60 | 10-MAY-23:00 | 75266.60 | 0.00 |
June | 0.00 | 0.00 | 0.508680E+11 | 0.507939E+11 | 77729.63 | 18-JUN-05:41 | 73064.23 | 0.00 |
July | 0.00 | 0.00 | 0.528619E+11 | 0.483541E+11 | 96692.96 | 14-JUL-00:41 | 43014.82 | 0.00 |
August | 0.00 | 0.00 | 0.491887E+11 | 0.448814E+11 | 93234.48 | 09-AUG-20:10 | 51786.82 | 0.00 |
September | 0.00 | 0.00 | 0.384416E+11 | 0.347351E+11 | 95318.17 | 04-SEP-08:40 | 47094.75 | 0.00 |
October | 0.00 | 0.00 | 0.142724E+11 | 0.136140E+11 | 89522.67 | 03-OCT-01:57 | 53556.67 | 0.00 |
November | 0.00 | 0.00 | 0.155810E+10 | 0.151439E+10 | 21511.74 | 01-NOV-14:50 | 20794.80 | 0.00 |
December | 0.00 | 0.00 | 4059445.44 | 4059445.44 | 1711.93 | 22-DEC-15:00 | 1711.93 | 0.00 |
Annual Sum or Average | 0.258970E+12 | 0.245668E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.528619E+11 | 0.507939E+11 | 96692.96 | 75266.60 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146982E+10 | 0.39 | 1481.13 | 02-JAN-07:50 | 1.03 |
February | 0.135252E+10 | 0.40 | 1481.13 | 01-FEB-10:50 | 1.03 |
March | 0.158627E+10 | 0.42 | 1481.13 | 01-MAR-16:20 | 1.02 |
April | 0.149001E+10 | 0.41 | 1481.13 | 04-APR-08:10 | 1.03 |
May | 0.157712E+10 | 0.43 | 1481.13 | 02-MAY-09:30 | 1.03 |
June | 0.159544E+10 | 0.48 | 1481.13 | 01-JUN-06:25 | 1.03 |
July | 0.154319E+10 | 0.46 | 1481.13 | 07-JUL-16:10 | 1.03 |
August | 0.165524E+10 | 0.47 | 1481.13 | 01-AUG-06:50 | 1.02 |
September | 0.152573E+10 | 0.43 | 1481.13 | 01-SEP-06:05 | 1.02 |
October | 0.149237E+10 | 0.39 | 1481.13 | 02-OCT-07:00 | 1.02 |
November | 0.141058E+10 | 0.38 | 1481.13 | 01-NOV-13:00 | 1.02 |
December | 0.147329E+10 | 0.40 | 1481.13 | 01-DEC-13:40 | 1.03 |
Annual Sum or Average | 0.181716E+11 | 0.42 | |||
Minimum of Months | 0.135252E+10 | 0.38 | 1481.13 | 1.02 | |
Maximum of Months | 0.165524E+10 | 0.48 | 1481.13 | 1.03 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.677960E+10 | 0.67 | 6809.35 | 31-JAN-12:50 | 1.73 |
February | 0.620195E+10 | 0.65 | 6809.35 | 01-FEB-07:03 | 1.72 |
March | 0.728055E+10 | 0.69 | 6809.35 | 10-MAR-16:40 | 1.72 |
April | 0.711266E+10 | 0.81 | 6809.35 | 01-APR-14:40 | 1.73 |
May | 0.781732E+10 | 0.95 | 6809.35 | 01-MAY-11:53 | 1.73 |
June | 0.875945E+10 | 1.20 | 6809.35 | 02-JUN-10:40 | 1.73 |
July | 0.863137E+10 | 1.19 | 6809.35 | 01-JUL-07:03 | 1.73 |
August | 0.870928E+10 | 1.12 | 6809.35 | 01-AUG-11:50 | 1.71 |
September | 0.775219E+10 | 0.99 | 6809.35 | 02-SEP-06:30 | 1.69 |
October | 0.704324E+10 | 0.74 | 6809.35 | 02-OCT-09:10 | 1.71 |
November | 0.647160E+10 | 0.63 | 6809.35 | 01-NOV-10:30 | 1.71 |
December | 0.674247E+10 | 0.64 | 6809.35 | 18-DEC-07:05 | 1.73 |
Annual Sum or Average | 0.893017E+11 | 0.86 | |||
Minimum of Months | 0.620195E+10 | 0.63 | 6809.35 | 1.69 | |
Maximum of Months | 0.875945E+10 | 1.20 | 6809.35 | 1.73 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.42 | 3.32 |
February | 0.50 | 1.29 |
March | 1.19 | 2.28 |
April | 3.55 | 0.25 |
May | 4.59 | 0.15 |
June | 6.75 | 0.08 |
July | 3.81 | 0.05 |
August | 6.86 | 0.20 |
September | 5.37 | 0.25 |
October | 3.83 | 0.59 |
November | 0.79 | 2.94 |
December | 0.42 | 0.97 |
Annual Sum or Average | 38.09 | 0.39 |
Minimum of Months | 0.42 | 0.05 |
Maximum of Months | 6.86 | 3.32 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 2.08 | 0.00 |
February | 0.58 | 0.00 |
March | 0.50 | 0.00 |
April | 2.49 | 0.00 |
May | 3.36 | 0.00 |
June | 7.09 | 0.00 |
July | 8.43 | 0.00 |
August | 9.00 | 0.00 |
September | 6.47 | 0.00 |
October | 3.21 | 0.00 |
November | 1.31 | 0.00 |
December | 0.58 | 0.00 |
Annual Sum or Average | 45.11 | |
Minimum of Months | 0.50 | 0.00 |
Maximum of Months | 9.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 1.06 | 0.00 |
May | 4.79 | 0.00 |
June | 10.57 | 0.00 |
July | 12.20 | 0.00 |
August | 11.88 | 0.00 |
September | 9.63 | 0.00 |
October | 1.53 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 51.65 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 12.20 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.189300E+10 | 0.346923E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.137140E+10 | 0.351280E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.203675E+10 | 0.308156E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.349491E+10 | 1029964.51 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.441619E+10 | 3639870.86 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.570663E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.560032E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.590974E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.503472E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.319965E+10 | 5971819.65 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.193117E+10 | 57408737.68 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.161251E+10 | 0.633474E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.422070E+11 | 0.170788E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.137140E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.590974E+10 | 0.633474E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.692394E+10 | 0.732431E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.620195E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.772375E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.133200E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.181939E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.269327E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.264028E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.252165E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.202434E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.116412E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.695114E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.674373E+10 | 24967101.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.176495E+12 | 0.757398E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.620195E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.269327E+11 | 0.732431E+09 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146982E+10 | 0.154814E+10 | 0.234147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135252E+10 | 68788993.82 | 0.234422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158627E+10 | 0.162961E+10 | 0.204954E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149001E+10 | 0.694476E+10 | 666269.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157712E+10 | 0.955508E+10 | 2409521.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159544E+10 | 0.128352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154319E+10 | 0.133449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165524E+10 | 0.140692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152573E+10 | 0.120068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149237E+10 | 0.600280E+10 | 3913027.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141058E+10 | 0.190966E+10 | 37637596.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147329E+10 | 0.512344E+09 | 0.428449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181716E+11 | 0.804271E+11 | 0.114660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135252E+10 | 68788993.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.165524E+10 | 0.140692E+11 | 0.428449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.677960E+10 | 0.457744E+09 | 0.495269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.620195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.728055E+10 | 0.142118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.711266E+10 | 0.190569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.781732E+10 | 0.308396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.875945E+10 | 0.508680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.863137E+10 | 0.528619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.870928E+10 | 0.491887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.775219E+10 | 0.384416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.704324E+10 | 0.142724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.647160E+10 | 0.155810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.674247E+10 | 4059445.44 | 16356415.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.893017E+11 | 0.258970E+12 | 0.511626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.620195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.875945E+10 | 0.528619E+11 | 0.495269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.146982E+10 | 0.00 | 0.00 | 0.00 | 0.423180E+09 | 0.00 | 0.346923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135252E+10 | 0.00 | 0.00 | 0.00 | 18876726.76 | 0.00 | 0.351280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158627E+10 | 0.00 | 0.00 | 0.00 | 0.450474E+09 | 0.00 | 0.308156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149001E+10 | 0.00 | 0.00 | 0.00 | 0.200490E+10 | 0.00 | 1029964.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157712E+10 | 0.00 | 0.00 | 0.00 | 0.283907E+10 | 0.00 | 3639870.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159544E+10 | 0.00 | 0.00 | 0.00 | 0.411119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154319E+10 | 0.00 | 0.00 | 0.00 | 0.405713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165524E+10 | 0.00 | 0.00 | 0.00 | 0.425450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152573E+10 | 0.00 | 0.00 | 0.00 | 0.350899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149237E+10 | 0.00 | 0.00 | 0.00 | 0.170728E+10 | 0.00 | 5971819.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141058E+10 | 0.00 | 0.00 | 0.00 | 0.520592E+09 | 0.00 | 57408737.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147329E+10 | 0.00 | 0.00 | 0.00 | 0.139219E+09 | 0.00 | 0.633474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181716E+11 | 0.00 | 0.00 | 0.00 | 0.240354E+11 | 0.00 | 0.170788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.135252E+10 | 0.00 | 0.00 | 0.00 | 18876726.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.165524E+10 | 0.00 | 0.00 | 0.00 | 0.425450E+10 | 0.00 | 0.633474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.677960E+10 | 0.00 | 0.00 | 0.00 | 0.144345E+09 | 0.00 | 0.732431E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.620195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.728055E+10 | 0.00 | 0.00 | 0.00 | 0.443200E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.711266E+10 | 0.00 | 0.00 | 0.00 | 0.620738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.781732E+10 | 0.00 | 0.00 | 0.00 | 0.103766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.875945E+10 | 0.00 | 0.00 | 0.00 | 0.181733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.863137E+10 | 0.00 | 0.00 | 0.00 | 0.177714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.870928E+10 | 0.00 | 0.00 | 0.00 | 0.165072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.775219E+10 | 0.00 | 0.00 | 0.00 | 0.124912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.704324E+10 | 0.00 | 0.00 | 0.00 | 0.459792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.647160E+10 | 0.00 | 0.00 | 0.00 | 0.479538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.674247E+10 | 0.00 | 0.00 | 0.00 | 1268080.74 | 0.00 | 24967101.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.893017E+11 | 0.00 | 0.00 | 0.00 | 0.871934E+11 | 0.00 | 0.757398E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.620195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.875945E+10 | 0.00 | 0.00 | 0.00 | 0.181733E+11 | 0.00 | 0.732431E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.199844E+09 | 8082305.12 | 0.00 | 2525626.21 | 0.00 | 16010689.91 | 0.150138E+10 | 0.00 | 0.56 |
February | 0.394122E+09 | 0.00 | 0.00 | 1370130.38 | 0.00 | 0.00 | 0.163745E+10 | 0.00 | 0.39 |
March | 0.207864E+09 | 29300307.42 | 0.00 | 2692122.39 | 0.00 | 2101503.47 | 0.192677E+10 | 0.00 | 0.58 |
April | 21974700.16 | 0.293687E+09 | 0.00 | 5037783.42 | 0.00 | 0.00 | 0.950791E+09 | 0.00 | 0.41 |
May | 3910207.34 | 0.510593E+09 | 0.00 | 7051227.50 | 0.00 | 0.00 | 0.539301E+09 | 0.00 | 0.34 |
June | 0.00 | 0.105882E+10 | 0.00 | 6721853.47 | 1233712.85 | 0.00 | 0.101916E+09 | 0.00 | 0.20 |
July | 0.00 | 0.135928E+10 | 0.00 | 3922071.47 | 0.00 | 0.00 | 40320043.09 | 0.00 | 0.17 |
August | 0.00 | 0.150393E+10 | 0.00 | 6132153.55 | 0.00 | 0.00 | 53802466.63 | 0.00 | 0.23 |
September | 0.00 | 0.113852E+10 | 0.00 | 6273277.88 | 108221.41 | 0.00 | 0.157503E+09 | 0.00 | 0.30 |
October | 32798760.07 | 0.324247E+09 | 0.00 | 5575012.15 | 0.00 | 0.00 | 0.156829E+10 | 0.00 | 0.54 |
November | 86908108.86 | 36154261.00 | 0.00 | 3710933.30 | 0.00 | 0.00 | 0.233255E+10 | 0.00 | 0.63 |
December | 0.416193E+09 | 366054.55 | 0.00 | 1692109.86 | 177469.15 | 27285197.74 | 0.146718E+10 | 0.00 | 0.44 |
Annual Sum or Average | 0.136362E+10 | 0.626297E+10 | 0.00 | 52704301.58 | 1519403.42 | 45397391.13 | 0.122773E+11 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1370130.38 | 0.00 | 0.00 | 40320043.09 | 0.00 | 0.17 |
Maximum of Months | 0.416193E+09 | 0.150393E+10 | 0.00 | 7051227.50 | 1233712.85 | 27285197.74 | 0.233255E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.248987E+10 | 6291174.60 | 0.00 | 127492.19 | 323705.35 | 2611041.02 | 0.316610E+09 | 0.00 | 0.29 |
February | 0.324363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
March | 0.269059E+10 | 32535907.79 | 0.00 | 750181.74 | 5603692.02 | 0.00 | 0.656074E+09 | 0.00 | 0.32 |
April | 0.381642E+09 | 0.804058E+09 | 0.00 | 7579467.47 | 693600.89 | 0.00 | 0.217740E+10 | 0.00 | 0.46 |
May | 0.211087E+09 | 0.158005E+10 | 0.00 | 5941730.63 | 0.00 | 0.00 | 0.148303E+10 | 0.00 | 0.41 |
June | 15819978.79 | 0.358241E+10 | 0.00 | 3619955.24 | 0.00 | 0.00 | 0.491069E+09 | 0.00 | 0.32 |
July | 16638087.30 | 0.459643E+10 | 0.00 | 2119596.45 | 0.00 | 0.00 | 0.263101E+09 | 0.00 | 0.33 |
August | 37483787.94 | 0.483316E+10 | 0.00 | 3063113.19 | 699825.36 | 0.00 | 0.580953E+09 | 0.00 | 0.41 |
September | 0.136865E+09 | 0.325045E+10 | 0.00 | 4518100.22 | 1059193.11 | 0.00 | 0.950662E+09 | 0.00 | 0.44 |
October | 0.106587E+10 | 0.790397E+09 | 0.00 | 4822574.86 | 0.00 | 0.00 | 0.256926E+10 | 0.00 | 0.49 |
November | 0.224528E+10 | 25340250.43 | 0.00 | 1334098.08 | 0.00 | 0.00 | 0.174263E+10 | 0.00 | 0.37 |
December | 0.299646E+10 | 0.00 | 0.00 | 0.00 | 7663146.02 | 0.00 | 0.00 | 0.00 | 0.19 |
Annual Sum or Average | 0.155312E+11 | 0.195011E+11 | 0.00 | 33876310.08 | 16043162.76 | 2611041.02 | 0.112308E+11 | 0.00 | 0.35 |
Minimum of Months | 15819978.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
Maximum of Months | 0.324363E+10 | 0.483316E+10 | 0.00 | 7579467.47 | 7663146.02 | 2611041.02 | 0.256926E+10 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |