Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2020-06-03 19:11:27
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1520.64 | 314.50 | 314.50 |
Net Site Energy | 1520.64 | 314.50 | 314.50 |
Total Source Energy | 3422.47 | 707.83 | 707.83 |
Net Source Energy | 3422.47 | 707.83 | 707.83 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 668.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 64.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.05 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 851.71 | 668.93 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 668.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 22.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 3.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 61.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.05 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 124.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 23.35 | 138.35 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 176.15 | 138.35 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 124.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 23.35 | 138.35 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 176.15 | 138.35 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 851.705 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 851.705 | 100.00 |
Total On-Site and Utility Electric Sources | 851.705 | 100.00 |
Total Electricity End Uses | 851.705 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 51.33 |
Time Setpoint Not Met During Occupied Cooling | 2.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1756.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.6337 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.5069 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.5069 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUN-14:00 | 21-DEC-17:00 | - | - | - | 20-JUL-11:50 |
Heating | 0.00 | 275331.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 16557.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6747.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1764.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 70371.60 | 275331.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 275331.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 16557.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4442.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1764.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 725.12 | 0.00 | 0.00 | 0.00 |
Cooling | 70.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1507.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 390.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 204.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 82.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2697.35 | 725.12 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 149.97 | 0.00 | 0.00 | 0.00 |
Cooling | 14.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 557.87 | 149.97 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 149.97 | 0.00 | 0.00 | 0.00 |
Cooling | 14.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 557.87 | 149.97 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.19 |
ZONE2 FINE STORAGE DIRECT AIR | 2.82 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 3.48 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 3.48 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 117187.49 |
PSZ-OFFICE HEATING COIL | 26734.84 |
PSZ-FINE STORAGE HEATING COIL | 79342.45 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 117187.48 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.19 | 1.19 | 1.19 | 1.19 | 1.19 | 1.19 | 1.00 | 1.00 | 1.19 |
PSZ-FINE STORAGE | 2.82 | 2.82 | 2.82 | 2.82 | 2.82 | 2.82 | 1.00 | 1.00 | 2.82 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.19 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 2.82 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.19 | 1.19 | 1.19 | 1.19 | 19683.29 | 26734.84 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.82 | 2.82 | 2.82 | 2.82 | 52813.18 | 79342.45 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.19 | 0.594535 | 1.19 | 19683.33 | 19683.29 | 9841.65 | 19683.29 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 2.82 | 1.41 | 2.82 | 46683.66 | 52813.18 | 26406.59 | 52813.18 | 0.755985 | 0.755980 | 0.755980 | 0.755980 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.19 | 1355.67 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.82 | 3086.68 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.634 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.707 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.507 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.507 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.507 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.066 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2518.900 | 10.634 | 503.780 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2518.900 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11853.648 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11853.648 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27263.390 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27263.390 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.3378 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.3378 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.3378 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.861 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.861 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.861 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
5 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
6 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
7 | 4 | 0.81105908E-12 | -0.61566660E-16 | 0.53970606E-14 | 0.11182789E-15 |
8 | 3 | -0.39455327E-03 | 0.24003309E-06 | -0.57329053E-04 | 0.15561420E-12 |
9 | 2 | 1.7627212 | 0.51935632E-02 | 1.1580856 | -0.75642783E-04 |
10 | 1 | -7.0983380 | 0.13367505 | -17.210522 | 0.33785533 |
11 | 0 | 5.5597362 | 0.84856002E-01 | 16.276219 | |
12 | 4 | 0.81105908E-12 | -0.61566660E-16 | 0.53970606E-14 | 0.11182789E-15 |
13 | 3 | -0.39455327E-03 | 0.24003309E-06 | -0.57329053E-04 | 0.15561420E-12 |
14 | 2 | 1.7627212 | 0.51935632E-02 | 1.1580856 | -0.75642783E-04 |
15 | 1 | -7.0983380 | 0.13367505 | -17.210522 | 0.33785533 |
16 | 0 | 5.5597362 | 0.84856002E-01 | 16.276219 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.53970606E-14 | -0.61566660E-16 | 0.81105908E-12 | 0.11182789E-15 |
85 | 3 | -0.57329053E-04 | 0.24003309E-06 | -0.39455327E-03 | 0.15561420E-12 |
86 | 2 | 1.1580856 | 0.51935632E-02 | 1.7627212 | -0.75642783E-04 |
87 | 1 | -17.210522 | 0.13367505 | -7.0983380 | 0.33785533 |
88 | 0 | 16.276219 | 0.84856002E-01 | 5.5597362 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 28 | 1 | VerySmooth | 2.843 | 0.395 | 0.315 | 0.401 |
2 | SKYLIGHT_U_0.6_SHGC_0.4 | 29 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 30 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9777.18946 | 11732.62735 | 0.99089 | 1.18907 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.43030E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10298.54778 | 12358.25734 | 0.35624 | 0.42749 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -17.90000 | 9.55238E-004 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 29749.95150 | 35699.94180 | 2.35013 | 2.82016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.90000 | 5.43030E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 42586.47816 | 51103.77379 | 1.24042 | 1.48850 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90000 | 5.43030E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 97656.23620 | 117187.48345 | 2.89638 | 3.47565 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | -17.90000 | 9.55238E-004 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 14834.56 | 1.18907 | 1.18907 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 12560.17 | 0.42749 | 0.42749 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 43222.42 | 2.82016 | 2.82016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 47368.96 | 1.48850 | 1.48850 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.18907 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.82016 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.47565 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 3.47565 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 117187.48794 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 117187.48345 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.18907 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.18907 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.18907 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.18907 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.18907 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.18907 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.82016 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.82016 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.82016 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.82016 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.82016 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.82016 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.18907 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.82016 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.18907 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.18907 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.18907 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.18907 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.18907 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.18907 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.59454 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.18907 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 19683.33057 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 19683.29000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9841.64500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 19683.29000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19683.29000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26734.84352 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.18907 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1355.66743 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26734.84352 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.82016 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.82016 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.82016 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.82016 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.82016 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.82016 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.41008 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.82016 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 46683.66165 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 52813.18000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 26406.59000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 52813.18000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.75599 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.75598 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.75598 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.75598 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 52813.18000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 79342.44871 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.82016 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3086.67653 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 79342.44871 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 18760.6 | 10.08 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 50623.9 | 13.38 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 14 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1446044719 | 0.1555682904 | Pass | Pass | 0.7554688721 | 3.5223204378 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.5036468733 | 0.5412629324 | Pass | Pass | 1.2875175721 | 3.1068106894 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 5.1193888959E-003 | 1.3073102709E-002 | Pass | Pass | 7.0891418758E-002 | 0.1948187699 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.322 | 0.338 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.322 | 0.338 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.322 | 0.338 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.322 | 0.338 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.369 | 0.389 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.102 | 0.395 | 0.401 | ||||||||||||
North Total or Average | 6.51 | 2.843 | 0.395 | 0.401 | ||||||||||||
Non-North Total or Average | 26.02 | 3.167 | 0.395 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.6337 | 236.88 | 2518.90 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.62 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.5069 | 1393.41 | 11853.65 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 135.00 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.5069 | 3204.84 | 27263.39 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 310.50 |
Interior Lighting Total | 8.6111 | 4835.13 | 41635.94 | 476.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.00 | AstronomicalClock | - | 83.67 | 83.67 | 123.40 | |
Exterior Lighting Total | 7857.00 | 123.40 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19683.29 | 15720.26 | 3963.03 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 52813.18 | 39925.71 | 12887.47 | 0.76 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 18760.6 | 10.08 | ||||
PSZ-FINE STORAGE COOLING COIL | 50623.9 | 13.38 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 117187.49 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26734.84 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 79342.45 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 3.48 | 322.92 | 92.91 | 1.00 | 3.29 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.19 | 1355.67 | 1140.11 | 1.00 | 1.32 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.82 | 3086.68 | 1094.51 | 1.00 | 1.24 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9777.19 | 11732.63 | 49.53 | 0.991 | 1.189 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00805 | 31.83 | 0.00543 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 29749.95 | 35699.94 | 25.62 | 2.350 | 2.820 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 26.70 | 26.70 | 0.00779 | 33.90 | 0.00543 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00466 | 33.90 | 0.00543 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10298.55 | 12358.26 | 52.17 | 0.356 | 0.427 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00765 | -17.90 | 0.00096 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 42586.48 | 51103.77 | 36.68 | 1.240 | 1.489 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15.56 | 15.55 | 0.00623 | -17.90 | 0.00096 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 97656.24 | 117187.48 | 36.57 | 2.896 | 3.476 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 10.00 | 9.99 | 0.00942 | -17.90 | 0.00096 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.19 | 1.19 | 0.43 | 0.43 | 1.1891 | 1.1891 | 1.1891 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.82 | 2.82 | 1.49 | 1.49 | 2.8202 | 2.8202 | 2.8202 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 117187.488 | 117187.488 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 117187.49 | 117187.49 | 3.475654 | 3.46 | 3.46 | 0.00743973 | 43.33 | 24.38 | 0.01600000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 9.99 | 0.00942296 | 100.0000 | 117187.48 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 19683.290 | 0.000 | 1.189070 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 19683.29 | 19683.29 | 1.189070 | 24.70 | 13.88 | 0.00778129 | 12.00 | 9.41 | 0.00800000 | 31.83 | 0.00543030 | 14.32 | 10.1201 | 23.90 | 0.00804600 | 35.3950 | 9777.19 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26734.844 | 26734.844 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 26734.84 | 26734.84 | 1.189067 | 10.09 | 6.30 | 0.00576492 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 10.1201 | 21.10 | 0.00764922 | 39.9190 | 10298.55 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 52813.180 | 0.000 | 2.820160 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 52813.18 | 52813.18 | 2.820160 | 27.60 | 14.61 | 0.00749780 | 12.00 | 9.41 | 0.00800000 | 33.90 | 0.00543030 | 15.00 | 12.5499 | 26.70 | 0.00779451 | 29.0383 | 29749.95 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 79342.449 | 79342.449 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 79342.45 | 79342.45 | 2.820156 | 7.60 | 4.26 | 0.00497834 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 12.5499 | 15.55 | 0.00623333 | 46.1781 | 42586.48 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 117187.488 | 117187.488 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 0.9774 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 3.475654 | 3.39723527 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 117187.49 | 117187.49 | 1.0000 | 3.39723527 | 3.475654 | 3.46 | 3.46 | 0.00743973 | 22129.9 | 43.33 | 24.38 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 117187.49 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 9.99 | 0.00942296 | 9.99 | 0.00942296 | 100.0000 | 117187.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19683.290 | 0.000 | 1.189070 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3050 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 19683.29 | 19683.29 | 1.0000 | 1.16224174 | 1.189070 | 24.70 | 13.88 | 0.00778129 | 44639.5 | 12.00 | 9.41 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19683.29 | 31.83 | 0.00543030 | 14.32 | 0.12033533 | 10.1201 | 23.90 | 0.00804600 | 23.90 | 0.00804600 | 35.3950 | 9777.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26734.844 | 26734.844 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.189067 | 1.16223914 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 26734.84 | 26734.84 | 1.0000 | 1.16223914 | 1.189067 | 10.09 | 6.30 | 0.00576492 | 24660.6 | 40.00 | 18.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26734.84 | -17.90 | 0.00095524 | -17.90 | 0.12033533 | 10.1201 | 21.05 | 0.00764922 | 21.10 | 0.00764922 | 39.9190 | 10298.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 52813.180 | 0.000 | 2.820160 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.7780 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 52813.18 | 52813.18 | 1.0000 | 2.75653046 | 2.820160 | 27.60 | 14.61 | 0.00749780 | 46874.1 | 12.00 | 9.41 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52813.18 | 33.90 | 0.00543030 | 15.00 | 0.35392745 | 12.5499 | 26.70 | 0.00779451 | 26.70 | 0.00779451 | 29.0383 | 29749.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 79342.449 | 79342.449 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.820156 | 2.75652681 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 79342.45 | 79342.45 | 1.0000 | 2.75652681 | 2.820156 | 7.60 | 4.26 | 0.00497834 | 20157.3 | 40.00 | 18.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 79342.45 | -17.90 | 0.00095524 | -17.90 | 0.35392745 | 12.5499 | 15.55 | 0.00623333 | 15.55 | 0.00623333 | 46.1781 | 42586.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE OA CONTROLLER | DifferentialDryBulb | 0.12 | 1.19 | - | |||
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.35 | 2.82 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2329.00 | 2591.83 | 1756.67 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2329.00 | 2591.83 | 1756.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 71.67 | 2.33 | 51.33 | 2.33 |
ZONE2 FINE STORAGE | 483.67 | 28.17 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 14.00 | 0.00 | 0.00 | 0.00 |
Facility | 540.50 | 30.50 | 51.33 | 2.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.767 | 0.401 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 851.71 | 5421.86 | 01-JAN-10:00 | 70371.60 | 26-JUN-15:00 |
Electricity:Building | 619.03 | 4938.86 | 01-JAN-00:10 | 47606.95 | 12-JUN-12:50 |
Electricity:Zone:ZONE1 OFFICE | 62.57 | 1027.15 | 01-JAN-00:10 | 3852.05 | 02-JAN-08:10 |
InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.62 | 453.40 | 01-JAN-00:10 | 1939.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 421.46 | 2726.34 | 01-JAN-00:10 | 33679.30 | 12-JUN-12:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 310.51 | 2726.34 | 01-JAN-00:10 | 23173.88 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 26.05 | 483.00 | 05-JAN-06:30 | 2604.56 | 13-FEB-13:00 |
WaterSystems:Electricity | 26.05 | 483.00 | 05-JAN-06:30 | 2604.56 | 13-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 26.05 | 483.00 | 05-JAN-06:30 | 2604.56 | 13-FEB-13:00 |
Fans:Electricity | 64.71 | 0.00 | 01-JAN-10:00 | 6747.64 | 26-JUN-09:50 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 3.62 | 0.00 | 01-JAN-00:10 | 2305.29 | 26-JUN-09:50 |
Ventilation (simple):Fans:Electricity | 3.62 | 0.00 | 01-JAN-00:10 | 2305.29 | 26-JUN-09:50 |
ElectricityPurchased:Facility | 851.71 | 5421.86 | 01-JAN-10:00 | 70371.60 | 26-JUN-15:00 |
ElectricityPurchased:Plant | 851.71 | 5421.86 | 01-JAN-10:00 | 70371.60 | 26-JUN-15:00 |
Cogeneration:ElectricityPurchased | 851.71 | 5421.86 | 01-JAN-10:00 | 70371.60 | 26-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 851.71 | 5421.86 | 01-JAN-10:00 | 70371.60 | 26-JUN-15:00 |
ElectricityNet:Plant | 851.71 | 5421.86 | 01-JAN-10:00 | 70371.60 | 26-JUN-15:00 |
Cogeneration:ElectricityNet | 851.71 | 5421.86 | 01-JAN-10:00 | 70371.60 | 26-JUN-15:00 |
Electricity:HVAC | 83.23 | 0.00 | 01-JAN-10:00 | 22060.05 | 26-JUN-15:10 |
General:Fans:Electricity | 61.09 | 0.00 | 01-JAN-10:00 | 4765.27 | 02-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 22.14 | 0.00 | 01-JAN-00:10 | 17617.70 | 26-JUN-15:10 |
ExteriorLights:Electricity | 123.40 | 0.00 | 01-JAN-07:30 | 7857.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.40 | 0.00 | 01-JAN-07:30 | 7857.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 668.93 | 4750.00 | 08-JUN-17:20 | 275331.67 | 21-DEC-18:00 |
Gas:HVAC | 668.93 | 4750.00 | 08-JUN-17:20 | 275331.67 | 21-DEC-18:00 |
Heating:Gas | 668.93 | 4750.00 | 08-JUN-17:20 | 275331.67 | 21-DEC-18:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUL-11:50 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUL-11:50 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUL-11:50 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUL-11:50 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUL-11:50 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUL-11:50 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUL-11:50 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUL-11:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 935.47 | 0.00 | 01-JAN-10:00 | 422163.44 | 21-DEC-18:00 |
EnergyTransfer:Building | 467.42 | 0.00 | 01-JAN-10:00 | 208083.15 | 23-DEC-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 52.53 | 0.00 | 01-JAN-00:10 | 24300.07 | 20-DEC-07:10 |
Heating:EnergyTransfer | 399.73 | 0.00 | 01-JAN-10:00 | 208083.15 | 23-DEC-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 29.09 | 0.00 | 01-JAN-00:10 | 24300.07 | 20-DEC-07:10 |
Cooling:EnergyTransfer | 67.69 | 0.00 | 01-JAN-00:10 | 37835.30 | 26-JUN-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 23.44 | 0.00 | 01-JAN-00:10 | 11228.59 | 26-JUN-17:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 185.42 | 0.00 | 01-JAN-00:40 | 78108.17 | 19-MAR-07:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 141.17 | 0.00 | 01-JAN-00:40 | 78108.17 | 19-MAR-07:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 44.25 | 0.00 | 01-JAN-00:10 | 28789.62 | 26-JUN-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 229.47 | 0.00 | 01-JAN-09:40 | 118439.42 | 21-DEC-18:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 229.47 | 0.00 | 01-JAN-09:40 | 118439.42 | 21-DEC-18:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 468.05 | 0.00 | 01-JAN-10:00 | 217318.54 | 21-DEC-18:00 |
HeatingCoils:EnergyTransfer | 395.00 | 0.00 | 01-JAN-10:00 | 217318.54 | 21-DEC-18:00 |
CoolingCoils:EnergyTransfer | 73.05 | 0.00 | 01-JAN-00:10 | 48512.64 | 26-JUN-15:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 29.085 | -23.442 | 0.000 | 0.000 | 3.894 | 30.619 | 31.946 | 11.541 | 0.000 | 1.329 | 0.000 | 0.000 | -11.486 | 0.000 | -22.933 | -50.553 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 141.174 | -44.244 | 0.000 | 0.000 | 0.000 | 135.003 | 0.000 | 0.000 | 0.000 | 3.366 | 0.000 | 0.000 | 0.000 | 0.000 | -139.113 | -96.186 |
ZONE3 BULK STORAGE | 229.470 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 310.507 | 107.336 | 23.118 | 0.000 | 25.720 | 0.000 | 0.000 | -11.345 | 0.000 | -503.865 | -180.940 |
Total Facility | 229.470 | 0.000 | 170.258 | -67.686 | 0.000 | 0.000 | 3.894 | 476.129 | 139.282 | 34.659 | 0.000 | 30.415 | 0.000 | 0.000 | -22.831 | 0.000 | -665.911 | -327.680 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 17-AUG-05:01 | 0.00 | 0.00 | 0.00 | -27136.99 | 0.00 | 0.00 | 32.29 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 27213.91 | 0.00 | -612.01 | 0.00 | -650.30 | 0.00 |
ZONE2 FINE STORAGE | 13-AUG-16:51 | 0.00 | 0.00 | 0.00 | -54288.22 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 54574.17 | 0.00 | -0.00 | 0.00 | -1471.31 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 13-AUG-16:51 | 0.00 | 0.00 | 0.00 | -54288.22 | 0.00 | 0.00 | 0.00 | 4365.11 | 573.75 | 3452.44 | 0.00 | 0.00 | 55786.11 | 0.00 | 0.00 | 0.00 | -9889.18 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 15-APR-05:31 | 0.00 | 0.00 | 28321.24 | 0.00 | 0.00 | 0.00 | 53.56 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -886.52 | 0.00 | -1275.84 | -27365.53 |
ZONE2 FINE STORAGE | 23-DEC-06:01 | 0.00 | 0.00 | 86213.83 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -22817.19 | -64582.00 |
ZONE3 BULK STORAGE | 21-DEC-18:00 | 118437.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16358.03 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1434.35 | 0.00 | -114945.39 | -20466.02 |
Total Facility | 23-DEC-06:01 | 117765.64 | 0.00 | 114122.36 | 0.00 | 0.00 | 0.00 | 60.57 | 4491.05 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2887.07 | 0.00 | -111098.06 | -125078.26 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1891 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.1891 | 0.1012 | 1.0000 | 0.1203 | 0.1012 | ||
PSZ-FINE STORAGE | 2.8202 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.8202 | 0.1255 | 1.0000 | 0.3539 | 0.1255 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1891 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.1891 | 1.0000 | 1.0000 | 0.1203 | 0.1012 | ||
PSZ-FINE STORAGE | 2.8202 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.8202 | 1.0000 | 1.0000 | 0.3539 | 0.1255 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.1891 | 1.1891 | 1.1891 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.8202 | 2.8202 | 2.8202 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1891 | 1.1891 | 1.1891 | 1.1891 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.8202 | 2.8202 | 2.8202 | 2.8202 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.1891 | 1.1891 | 1.1891 | 0.1203 | 0.2815 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.8202 | 2.8202 | 2.8202 | 0.3539 | 0.2378 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1891 | 1.1891 | 1.1891 | 1.1891 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.8202 | 2.8202 | 2.8202 | 2.8202 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:27
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 51.33 |
Number of hours cooling loads not met | 2.33 |
Number of hours not met | 53.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 668.93 | 275331.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 22.14 | 17617.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 476.13 | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.40 | 7857.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 3.62 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 61.09 | 4765.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.05 | 2604.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 851.71 |
Natural Gas | 0.00 | 668.93 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1520.64 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 98.47 |
Space Heating | 0.00 |
Space Cooling | 4.58 |
Fans (All) | 13.38 |
Service Water Heating | 5.39 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 176.15 |
Subtotal | 176.15 |
Natural Gas [MJ/m2] | |
Space Heating | 138.35 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 138.35 |
Subtotal | 138.35 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 31.31 |
Space Heating | 43.99 |
Space Cooling | 1.46 |
Fans (All) | 4.26 |
Service Water Heating | 1.71 |
Receptacle Equipment | 9.16 |
Miscellaneous | 8.12 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.897655E+11 |
February | 0.000 | 0.118294E+12 |
March | 0.000 | 0.764866E+11 |
April | 0.000 | 0.522358E+11 |
May | 0.000 | 0.150800E+11 |
June | 0.000 | 0.123134E+11 |
July | 0.000 | 0.127224E+11 |
August | 0.000 | 0.127239E+11 |
September | 0.000 | 0.123673E+11 |
October | 0.000 | 0.350831E+11 |
November | 0.000 | 0.609310E+11 |
December | 0.000 | 0.170927E+12 |
Annual Sum or Average | 0.668930E+12 | |
Minimum of Months | 0.000 | 0.123134E+11 |
Maximum of Months | 0.000 | 0.170927E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.897655E+11 |
February | 0.000 | 0.118294E+12 |
March | 0.000 | 0.764866E+11 |
April | 0.000 | 0.522358E+11 |
May | 0.000 | 0.150800E+11 |
June | 0.000 | 0.123134E+11 |
July | 0.000 | 0.127224E+11 |
August | 0.000 | 0.127239E+11 |
September | 0.000 | 0.123673E+11 |
October | 0.000 | 0.350831E+11 |
November | 0.000 | 0.609310E+11 |
December | 0.000 | 0.170927E+12 |
Annual Sum or Average | 0.668930E+12 | |
Minimum of Months | 0.000 | 0.123134E+11 |
Maximum of Months | 0.000 | 0.170927E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.897655E+11 |
February | 0.000 | 0.118294E+12 |
March | 0.000 | 0.764866E+11 |
April | 0.000 | 0.522358E+11 |
May | 0.000 | 0.150800E+11 |
June | 0.000 | 0.123134E+11 |
July | 0.000 | 0.127224E+11 |
August | 0.000 | 0.127239E+11 |
September | 0.000 | 0.123673E+11 |
October | 0.000 | 0.350831E+11 |
November | 0.000 | 0.609310E+11 |
December | 0.000 | 0.170927E+12 |
Annual Sum or Average | 0.668930E+12 | |
Minimum of Months | 0.000 | 0.123134E+11 |
Maximum of Months | 0.000 | 0.170927E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.897655E+11 |
February | 0.000 | 0.118294E+12 |
March | 0.000 | 0.764866E+11 |
April | 0.000 | 0.522358E+11 |
May | 0.000 | 0.150800E+11 |
June | 0.000 | 0.123134E+11 |
July | 0.000 | 0.127224E+11 |
August | 0.000 | 0.127239E+11 |
September | 0.000 | 0.123673E+11 |
October | 0.000 | 0.350831E+11 |
November | 0.000 | 0.609310E+11 |
December | 0.000 | 0.170927E+12 |
Annual Sum or Average | 0.668930E+12 | |
Minimum of Months | 0.000 | 0.123134E+11 |
Maximum of Months | 0.000 | 0.170927E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.897655E+11 |
February | 0.000 | 0.118294E+12 |
March | 0.000 | 0.764866E+11 |
April | 0.000 | 0.522358E+11 |
May | 0.000 | 0.150800E+11 |
June | 0.000 | 0.123134E+11 |
July | 0.000 | 0.127224E+11 |
August | 0.000 | 0.127239E+11 |
September | 0.000 | 0.123673E+11 |
October | 0.000 | 0.350831E+11 |
November | 0.000 | 0.609310E+11 |
December | 0.000 | 0.170927E+12 |
Annual Sum or Average | 0.668930E+12 | |
Minimum of Months | 0.000 | 0.123134E+11 |
Maximum of Months | 0.000 | 0.170927E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.897655E+11 |
February | 0.000 | 0.118294E+12 |
March | 0.000 | 0.764866E+11 |
April | 0.000 | 0.522358E+11 |
May | 0.000 | 0.150800E+11 |
June | 0.000 | 0.123134E+11 |
July | 0.000 | 0.127224E+11 |
August | 0.000 | 0.127239E+11 |
September | 0.000 | 0.123673E+11 |
October | 0.000 | 0.350831E+11 |
November | 0.000 | 0.609310E+11 |
December | 0.000 | 0.170927E+12 |
Annual Sum or Average | 0.668930E+12 | |
Minimum of Months | 0.000 | 0.123134E+11 |
Maximum of Months | 0.000 | 0.170927E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.897655E+11 |
February | 0.000 | 0.118294E+12 |
March | 0.000 | 0.764866E+11 |
April | 0.000 | 0.522358E+11 |
May | 0.000 | 0.150800E+11 |
June | 0.000 | 0.123134E+11 |
July | 0.000 | 0.127224E+11 |
August | 0.000 | 0.127239E+11 |
September | 0.000 | 0.123673E+11 |
October | 0.000 | 0.350831E+11 |
November | 0.000 | 0.609310E+11 |
December | 0.000 | 0.170927E+12 |
Annual Sum or Average | 0.668930E+12 | |
Minimum of Months | 0.000 | 0.123134E+11 |
Maximum of Months | 0.000 | 0.170927E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.897655E+11 |
February | 0.000 | 0.118294E+12 |
March | 0.000 | 0.764866E+11 |
April | 0.000 | 0.522358E+11 |
May | 0.000 | 0.150800E+11 |
June | 0.000 | 0.123134E+11 |
July | 0.000 | 0.127224E+11 |
August | 0.000 | 0.127239E+11 |
September | 0.000 | 0.123673E+11 |
October | 0.000 | 0.350831E+11 |
November | 0.000 | 0.609310E+11 |
December | 0.000 | 0.170927E+12 |
Annual Sum or Average | 0.668930E+12 | |
Minimum of Months | 0.000 | 0.123134E+11 |
Maximum of Months | 0.000 | 0.170927E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.897655E+11 |
February | 0.000 | 0.118294E+12 |
March | 0.000 | 0.764866E+11 |
April | 0.000 | 0.522358E+11 |
May | 0.000 | 0.150800E+11 |
June | 0.000 | 0.123134E+11 |
July | 0.000 | 0.127224E+11 |
August | 0.000 | 0.127239E+11 |
September | 0.000 | 0.123673E+11 |
October | 0.000 | 0.350831E+11 |
November | 0.000 | 0.609310E+11 |
December | 0.000 | 0.170927E+12 |
Annual Sum or Average | 0.668930E+12 | |
Minimum of Months | 0.000 | 0.123134E+11 |
Maximum of Months | 0.000 | 0.170927E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8961222.95 | 362.82 | 26-JAN-17:00 | 6.00 | 1.82 | 0.199106E+09 | 301.58 | 20-JAN-16:10 | 17.00 | 7.16 |
February | 1810878.18 | 281.85 | 23-FEB-16:25 | 6.50 | 3.11 | 0.181306E+09 | 300.09 | 18-FEB-15:20 | 18.67 | 7.79 |
March | 90451554.21 | 2384.90 | 15-MAR-16:00 | 19.00 | 5.34 | 0.222125E+09 | 301.59 | 13-MAR-13:30 | 22.50 | 6.90 |
April | 39917439.80 | 1013.92 | 08-APR-16:00 | 16.00 | 5.14 | 0.207948E+09 | 301.59 | 07-APR-13:00 | 21.00 | 7.91 |
May | 0.114531E+10 | 4380.86 | 31-MAY-16:00 | 28.00 | 14.84 | 0.246474E+09 | 301.60 | 18-MAY-15:00 | 19.00 | 11.40 |
June | 0.552667E+10 | 24969.90 | 28-JUN-05:01 | 15.27 | 6.81 | 0.258786E+09 | 301.64 | 20-JUN-14:09 | 23.67 | 16.46 |
July | 0.563245E+10 | 23609.09 | 13-JUL-05:02 | 12.67 | 7.94 | 0.248909E+09 | 301.66 | 31-JUL-15:30 | 21.00 | 17.66 |
August | 0.601182E+10 | 27139.48 | 17-AUG-05:01 | 12.00 | 4.86 | 0.268842E+09 | 301.70 | 05-AUG-14:50 | 21.17 | 18.24 |
September | 0.426774E+10 | 23663.99 | 08-SEP-05:02 | 12.62 | 7.89 | 0.247440E+09 | 301.72 | 30-SEP-15:09 | 17.20 | 13.64 |
October | 0.645291E+09 | 4528.36 | 11-OCT-15:20 | 25.33 | 9.14 | 0.222681E+09 | 301.59 | 20-OCT-12:09 | 20.00 | 5.75 |
November | 66789389.99 | 1470.94 | 07-NOV-15:30 | 21.50 | 7.23 | 0.197492E+09 | 301.59 | 09-NOV-13:09 | 20.00 | 8.87 |
December | 5828990.84 | 591.89 | 16-DEC-16:25 | 4.00 | 0.10 | 0.198647E+09 | 301.58 | 02-DEC-15:09 | 21.33 | 7.59 |
Annual Sum or Average | 0.234431E+11 | 0.269976E+10 | ||||||||
Minimum of Months | 1810878.18 | 281.85 | 4.00 | 0.10 | 0.181306E+09 | 300.09 | 17.00 | 5.75 | ||
Maximum of Months | 0.601182E+10 | 27139.48 | 28.00 | 14.84 | 0.268842E+09 | 301.72 | 23.67 | 18.24 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.466023E+09 | 3319.90 | 11-JAN-11:00 | -1.0 | -1.0 | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 | -1.6 |
February | 0.423703E+09 | 3254.48 | 01-FEB-12:50 | -2.0 | -4.1 | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 | -5.3 |
March | 0.249899E+09 | 5300.35 | 14-MAR-06:10 | 7.33 | 0.90 | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 | -1.1 |
April | 0.287475E+09 | 2908.64 | 22-APR-08:20 | 0.00 | -0.2 | 0.00 | 0.00 | 01-APR-00:10 | 5.90 | 2.09 |
May | 0.216693E+09 | 8159.96 | 09-MAY-06:10 | 5.50 | 2.39 | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 | 4.75 |
June | 0.118191E+11 | 51240.39 | 18-JUN-15:51 | 22.20 | 13.07 | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 | 11.25 |
July | 0.124487E+11 | 52257.45 | 04-JUL-11:11 | 23.67 | 12.68 | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 | 10.88 |
August | 0.120122E+11 | 54288.83 | 13-AUG-16:51 | 22.00 | 9.76 | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 | 15.42 |
September | 0.532603E+10 | 49087.25 | 17-SEP-12:01 | 24.68 | 10.54 | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 | 10.63 |
October | 0.397670E+09 | 5538.17 | 19-OCT-06:10 | 3.17 | -1.2 | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 | 8.02 |
November | 0.385819E+09 | 5830.78 | 08-NOV-07:10 | 8.33 | 2.33 | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 | -5.7 |
December | 0.212311E+09 | 2870.39 | 06-DEC-14:00 | -1.0 | -3.0 | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 | -0.3 |
Annual Sum or Average | 0.442456E+11 | 0.00 | ||||||||
Minimum of Months | 0.212311E+09 | 2870.39 | -2.0 | -4.1 | 0.00 | 0.00 | -5.7 | -5.7 | ||
Maximum of Months | 0.124487E+11 | 54288.83 | 24.68 | 13.07 | 0.00 | 0.00 | 22.27 | 15.42 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.50 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 | -1.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -5.3 | -5.3 | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.1 | -1.1 | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 | 2.09 | 0.00 | 0.00 | 01-APR-00:10 | 5.90 | 2.09 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 | 4.75 | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 | 4.75 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 | 11.25 | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 | 11.25 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 | 10.88 | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 | 10.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 | 15.42 | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 | 15.42 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 | 10.63 | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 | 10.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 | 8.02 | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 | 8.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 | -5.7 | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 2.77 | -0.3 | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 | -0.3 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -5.7 | -5.7 | 0.00 | 0.00 | -5.7 | -5.7 | ||
Maximum of Months | 0.00 | 0.00 | 22.27 | 15.42 | 0.00 | 0.00 | 22.27 | 15.42 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.485805E+10 | 27356.51 | 02-JAN-06:12 | -2.7 |
February | 0.514380E+10 | 27592.95 | 06-FEB-06:22 | -10.0 |
March | 0.414214E+10 | 28299.75 | 04-MAR-06:41 | -10.0 |
April | 0.290438E+10 | 28321.03 | 15-APR-05:31 | -5.0 |
May | 0.731437E+09 | 27112.68 | 03-MAY-05:01 | 1.17 |
June | 27257412.34 | 2246.64 | 27-JUN-06:05 | 20.78 |
July | 12746930.03 | 1692.23 | 31-JUL-06:04 | 16.33 |
August | 30442078.23 | 3478.72 | 14-AUG-06:00 | 17.00 |
September | 0.103098E+09 | 7022.86 | 22-SEP-06:10 | -1.4 |
October | 0.189449E+10 | 27353.55 | 30-OCT-05:22 | -10.0 |
November | 0.335195E+10 | 27407.48 | 30-NOV-06:12 | -12.0 |
December | 0.588527E+10 | 27956.85 | 05-DEC-06:42 | -3.0 |
Annual Sum or Average | 0.290851E+11 | |||
Minimum of Months | 12746930.03 | 1692.23 | -12.0 | |
Maximum of Months | 0.588527E+10 | 28321.03 | 20.78 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.209010E+11 | 82283.11 | 16-JAN-03:02 | -10.0 |
February | 0.257478E+11 | 83184.76 | 08-FEB-06:01 | -5.8 |
March | 0.188661E+11 | 82375.22 | 28-MAR-00:22 | -4.5 |
April | 0.138950E+11 | 82516.94 | 16-APR-14:22 | -2.5 |
May | 0.234612E+10 | 81031.12 | 02-MAY-05:52 | 0.00 |
June | 0.272952E+09 | 2931.31 | 27-JUN-06:12 | 21.07 |
July | 0.225172E+09 | 2966.82 | 21-JUL-06:12 | 18.00 |
August | 0.268746E+09 | 3104.90 | 24-AUG-07:00 | 15.00 |
September | 0.478481E+09 | 3117.04 | 22-SEP-07:00 | 0.00 |
October | 0.792368E+10 | 82305.81 | 29-OCT-23:02 | -8.0 |
November | 0.145935E+11 | 82269.35 | 02-NOV-05:42 | -9.0 |
December | 0.356558E+11 | 86213.67 | 23-DEC-06:01 | -22.1 |
Annual Sum or Average | 0.141174E+12 | |||
Minimum of Months | 0.225172E+09 | 2931.31 | -22.1 | |
Maximum of Months | 0.356558E+11 | 86213.67 | 21.07 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324686E+11 | 68531.59 | 05-JAN-19:51 | -17.0 |
February | 0.509479E+11 | 104104.58 | 12-FEB-05:51 | -19.0 |
March | 0.258327E+11 | 117829.67 | 19-MAR-06:50 | -15.2 |
April | 0.140148E+11 | 66075.84 | 16-APR-16:00 | -3.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.703875E+10 | 61962.73 | 31-OCT-24:00 | -5.8 |
November | 0.185010E+11 | 100006.75 | 30-NOV-05:51 | -12.0 |
December | 0.806671E+11 | 118439.42 | 21-DEC-18:00 | -22.0 |
Annual Sum or Average | 0.229471E+12 | |||
Minimum of Months | 0.00 | 0.00 | -22.0 | |
Maximum of Months | 0.806671E+11 | 118439.42 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.256100E+10 | 1939.55 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.233575E+10 | 1939.55 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.266872E+10 | 1939.55 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.252182E+10 | 1939.55 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.261486E+10 | 1939.55 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.257569E+10 | 1939.55 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.256100E+10 | 1939.55 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.266872E+10 | 1939.55 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.252182E+10 | 1939.55 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.256100E+10 | 1939.55 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.246796E+10 | 1939.55 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.256100E+10 | 1939.55 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.306193E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.233575E+10 | 1939.55 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.266872E+10 | 1939.55 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112294E+11 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102778E+11 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.118738E+11 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.111270E+11 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.115516E+11 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.114492E+11 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112294E+11 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.118738E+11 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.111270E+11 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112294E+11 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108048E+11 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112294E+11 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135003E+12 | ||||
Minimum of Months | 0.102778E+11 | 10075.60 | 0.00 | 0.00 | |
Maximum of Months | 0.118738E+11 | 10075.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.258277E+11 | 23173.88 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.236390E+11 | 23173.88 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.273097E+11 | 23173.88 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.255921E+11 | 23173.88 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.265687E+11 | 23173.88 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.263332E+11 | 23173.88 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.258277E+11 | 23173.88 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.273097E+11 | 23173.88 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.255921E+11 | 23173.88 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.258277E+11 | 23173.88 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.248511E+11 | 23173.88 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.258277E+11 | 23173.88 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.236390E+11 | 23173.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.273097E+11 | 23173.88 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254582E+10 |
February | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291891E+10 |
March | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2938.44 | 0.272695E+10 |
April | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231491E+10 |
May | 0.565842E+09 | 0.261486E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30315438.97 | 0.138588E+10 |
June | 0.565842E+09 | 0.257569E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422155E+09 | 0.516023E+09 |
July | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352079E+09 | 0.504183E+09 |
August | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362071E+09 | 0.619941E+09 |
September | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158011E+09 | 0.899493E+09 |
October | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4174839.88 | 0.231037E+10 |
November | 0.522316E+09 | 0.246796E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48749.25 | 0.254865E+10 |
December | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364192E+10 |
Annual Sum or Average | 0.659424E+10 | 0.306193E+11 | 0.319458E+11 | 0.132886E+10 | 0.229330E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504183E+09 |
Maximum of Months | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422155E+09 | 0.364192E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101685E+11 |
February | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163913E+11 |
March | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169864E+11 |
April | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161939E+11 |
May | 0.00 | 0.115516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18696074.29 | 0.879295E+10 |
June | 0.00 | 0.114492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113887E+10 | 0.502140E+10 |
July | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120317E+10 | 0.515283E+10 |
August | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748513E+09 | 0.529088E+10 |
September | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253283E+09 | 0.728740E+10 |
October | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81584.49 | 0.128901E+11 |
November | 0.00 | 0.108048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1972466.75 | 0.115753E+11 |
December | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1522368.21 | 0.233617E+11 |
Annual Sum or Average | 0.135003E+12 | 0.336611E+10 | 0.139113E+12 | ||||||
Minimum of Months | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502140E+10 |
Maximum of Months | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120317E+10 | 0.233617E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431499E+09 | 0.221966E+11 |
February | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333923E+09 | 0.371627E+11 |
March | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.668617E+09 | 0.367775E+11 |
April | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167264E+10 | 0.329052E+11 |
May | 0.00 | 0.265687E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177502E+10 | 0.204869E+11 |
June | 0.00 | 0.263332E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111727E+10 | 0.187357E+11 |
July | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221595E+09 | 0.233057E+11 |
August | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121903E+09 | 0.228100E+11 |
September | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382605E+09 | 0.272957E+11 |
October | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113454E+09 | 0.360254E+11 |
November | 0.00 | 0.248511E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473805E+09 | 0.264888E+11 |
December | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107209E+10 | 0.545309E+11 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | 0.838443E+10 | 0.358721E+12 | |||||
Minimum of Months | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113454E+09 | 0.187357E+11 |
Maximum of Months | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177502E+10 | 0.545309E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1939.55 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 13172.11 | 05-JAN-18:00 |
February | 659.25 | 01-FEB-08:09 | 1939.55 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 10938.95 | 13-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1939.55 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.90 | 14-MAR-13:00 | 10129.63 | 02-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1939.55 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 10347.53 | 17-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1939.55 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1261.18 | 31-MAY-16:10 | 7706.63 | 02-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1939.55 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4265.25 | 26-JUN-17:00 | 4596.95 | 09-JUN-06:02 |
July | 659.25 | 01-JUL-07:10 | 1939.55 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3442.82 | 17-JUL-12:00 | 4282.45 | 03-JUL-06:03 |
August | 659.25 | 01-AUG-07:10 | 1939.55 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3770.87 | 16-AUG-16:10 | 3729.90 | 23-AUG-06:01 |
September | 659.25 | 01-SEP-07:10 | 1939.55 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2207.81 | 12-SEP-16:10 | 7980.45 | 21-SEP-16:02 |
October | 659.25 | 02-OCT-07:10 | 1939.55 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.13 | 10-OCT-17:00 | 10625.91 | 30-OCT-06:10 |
November | 659.25 | 01-NOV-07:10 | 1939.55 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 | 05-NOV-13:40 | 11725.51 | 29-NOV-18:00 |
December | 659.25 | 01-DEC-08:09 | 1939.55 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 17207.68 | 21-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3729.90 | |||||
Maximum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4265.25 | 17207.68 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 16234.92 | 07-JAN-08:00 |
February | 0.00 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 23769.50 | 11-FEB-16:10 |
March | 0.00 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 44226.52 | 19-MAR-07:10 |
April | 0.00 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 31858.22 | 14-APR-07:00 |
May | 0.00 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 859.07 | 31-MAY-16:00 | 17380.01 | 02-MAY-06:10 |
June | 0.00 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7965.00 | 06-JUN-16:40 | 12470.91 | 20-JUN-16:55 |
July | 0.00 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7791.60 | 15-JUL-15:10 | 9133.67 | 03-JUL-03:00 |
August | 0.00 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8271.63 | 02-AUG-16:00 | 10768.13 | 29-AUG-16:00 |
September | 0.00 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4134.32 | 09-SEP-15:10 | 23202.59 | 21-SEP-15:03 |
October | 0.00 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.69 | 11-OCT-14:00 | 22486.42 | 29-OCT-18:51 |
November | 0.00 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.22 | 05-NOV-15:00 | 27452.42 | 01-NOV-07:00 |
December | 0.00 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.74 | 01-DEC-14:00 | 43386.58 | 21-DEC-18:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9133.67 | |||
Maximum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8271.63 | 44226.52 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23173.88 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8299.91 | 19-JAN-14:00 | 42205.35 | 07-JAN-12:00 |
February | 0.00 | 23173.88 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9539.96 | 18-FEB-14:00 | 73653.16 | 11-FEB-15:00 |
March | 0.00 | 23173.88 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9784.11 | 31-MAR-14:00 | 107041.01 | 19-MAR-06:51 |
April | 0.00 | 23173.88 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18979.14 | 07-APR-16:00 | 61505.31 | 14-APR-07:10 |
May | 0.00 | 23173.88 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13312.70 | 04-MAY-15:00 | 58379.68 | 26-MAY-10:55 |
June | 0.00 | 23173.88 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15334.31 | 06-JUN-14:00 | 36218.79 | 20-JUN-16:55 |
July | 0.00 | 23173.88 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3587.52 | 16-JUL-12:00 | 33044.37 | 03-JUL-03:00 |
August | 0.00 | 23173.88 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3208.74 | 02-AUG-12:55 | 38874.33 | 29-AUG-16:00 |
September | 0.00 | 23173.88 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9770.67 | 26-SEP-12:10 | 71945.65 | 21-SEP-14:50 |
October | 0.00 | 23173.88 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5698.48 | 11-OCT-14:00 | 59950.27 | 03-OCT-14:55 |
November | 0.00 | 23173.88 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10208.42 | 07-NOV-14:00 | 60486.25 | 01-NOV-10:00 |
December | 0.00 | 23173.88 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24499.97 | 02-DEC-12:00 | 92832.12 | 21-DEC-18:53 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 3208.74 | 33044.37 | ||||
Maximum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 24499.97 | 107041.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 362.82 | 26-JAN-17:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 858.99 |
February | 281.85 | 23-FEB-16:25 | 1318.50 | 3879.11 | 3825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1403.79 |
March | 2384.90 | 15-MAR-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.18 |
April | 1013.92 | 08-APR-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.43 |
May | 4380.86 | 31-MAY-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 325.30 | 0.00 |
June | 24969.90 | 28-JUN-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 634.07 |
July | 23609.09 | 13-JUL-05:02 | 362.59 | 2896.74 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 805.96 |
August | 27139.48 | 17-AUG-05:01 | 507.62 | 4055.43 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.30 |
September | 23663.99 | 08-SEP-05:02 | 362.59 | 2896.74 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813.21 |
October | 4528.36 | 11-OCT-15:20 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 124.16 | 0.00 |
November | 1470.94 | 07-NOV-15:30 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.68 |
December | 591.89 | 16-DEC-16:25 | 1318.50 | 3879.11 | 3825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 763.86 |
Annual Sum or Average | |||||||||||
Minimum of Months | 281.85 | 362.59 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27139.48 | 1318.50 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 325.30 | 1403.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3319.90 | 11-JAN-11:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.97 |
February | 3254.48 | 01-FEB-12:50 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2375.56 |
March | 5300.35 | 14-MAR-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4701.98 |
April | 2908.64 | 22-APR-08:20 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5291.99 |
May | 8159.96 | 09-MAY-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5372.86 |
June | 51240.39 | 18-JUN-15:51 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1311.74 |
July | 52257.45 | 04-JUL-11:11 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549.41 |
August | 54288.83 | 13-AUG-16:51 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1471.31 |
September | 49087.25 | 17-SEP-12:01 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.84 |
October | 5538.17 | 19-OCT-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2992.89 |
November | 5830.78 | 08-NOV-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2666.60 |
December | 2870.39 | 06-DEC-14:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2207.90 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2870.39 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.84 | |
Maximum of Months | 54288.83 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5372.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 10905.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3543.93 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 10905.36 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11946.39 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 8179.02 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10723.77 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4917.93 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7493.39 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5092.75 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12224.45 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14884.12 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8125.09 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13426.75 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36506.45 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 10905.36 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12130.94 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3543.93 | |
Maximum of Months | 0.00 | 0.00 | 10905.36 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36506.45 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.716894E+11 | 55632.66 | 05-JAN-16:49 | 0.897655E+11 | 149500.63 | 06-JAN-06:19 |
February | 0.650541E+11 | 52166.08 | 11-FEB-13:00 | 0.118294E+12 | 200500.82 | 12-FEB-06:10 |
March | 0.730353E+11 | 52342.66 | 14-MAR-14:20 | 0.764866E+11 | 253347.38 | 19-MAR-07:10 |
April | 0.672834E+11 | 51838.29 | 03-APR-10:20 | 0.522358E+11 | 148677.85 | 16-APR-15:50 |
May | 0.684470E+11 | 55111.65 | 17-MAY-13:39 | 0.150800E+11 | 56769.54 | 02-MAY-05:00 |
June | 0.740393E+11 | 70371.60 | 26-JUN-14:00 | 0.123134E+11 | 6054.97 | 28-JUN-05:19 |
July | 0.740853E+11 | 67481.45 | 17-JUL-13:39 | 0.127224E+11 | 4750.00 | 01-JUL-00:10 |
August | 0.775131E+11 | 68283.22 | 16-AUG-13:00 | 0.127239E+11 | 7168.38 | 14-AUG-05:00 |
September | 0.702812E+11 | 63911.70 | 09-SEP-12:50 | 0.123673E+11 | 12842.20 | 22-SEP-06:19 |
October | 0.694767E+11 | 54410.40 | 11-OCT-14:20 | 0.350831E+11 | 131560.57 | 31-OCT-23:49 |
November | 0.682616E+11 | 55626.62 | 29-NOV-16:40 | 0.609310E+11 | 209747.02 | 30-NOV-06:10 |
December | 0.725391E+11 | 55630.89 | 23-DEC-16:49 | 0.170927E+12 | 275331.67 | 21-DEC-17:00 |
Annual Sum or Average | 0.851705E+12 | 0.668930E+12 | ||||
Minimum of Months | 0.650541E+11 | 51838.29 | 0.123134E+11 | 4750.00 | ||
Maximum of Months | 0.775131E+11 | 70371.60 | 0.170927E+12 | 275331.67 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.396181E+11 | 0.126765E+11 | 0.115358E+11 | 0.00 | 0.557725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228178E+10 | 0.00 |
February | 0.362526E+11 | 0.106729E+11 | 0.105871E+11 | 0.00 | 0.545552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208590E+10 | 0.00 |
March | 0.418523E+11 | 0.107201E+11 | 0.123357E+11 | 0.00 | 0.577035E+10 | 0.00 | 0.00 | 12657845.40 | 0.00 | 0.00 | 0.00 | 0.234424E+10 | 0.00 |
April | 0.392410E+11 | 0.926340E+10 | 0.114862E+11 | 0.00 | 0.509669E+10 | 0.00 | 0.00 | 213641.63 | 0.00 | 0.00 | 0.00 | 0.219595E+10 | 0.00 |
May | 0.407352E+11 | 0.860813E+10 | 0.119357E+11 | 0.00 | 0.462677E+10 | 0.00 | 0.00 | 0.322238E+09 | 0.00 | 0.00 | 0.00 | 0.221895E+10 | 0.00 |
June | 0.403581E+11 | 0.782086E+10 | 0.118862E+11 | 0.00 | 0.566267E+10 | 0.00 | 0.00 | 0.619620E+10 | 0.00 | 0.00 | 0.00 | 0.211538E+10 | 0.00 |
July | 0.396181E+11 | 0.831113E+10 | 0.115358E+11 | 0.00 | 0.597880E+10 | 0.00 | 0.00 | 0.654416E+10 | 0.00 | 0.00 | 0.00 | 0.209732E+10 | 0.00 |
August | 0.418523E+11 | 0.914555E+10 | 0.123357E+11 | 0.00 | 0.595503E+10 | 0.00 | 0.00 | 0.608541E+10 | 0.00 | 0.00 | 0.00 | 0.213915E+10 | 0.00 |
September | 0.392410E+11 | 0.989039E+10 | 0.114862E+11 | 0.00 | 0.472219E+10 | 0.00 | 0.00 | 0.288546E+10 | 0.00 | 0.00 | 0.00 | 0.205594E+10 | 0.00 |
October | 0.396181E+11 | 0.113659E+11 | 0.115358E+11 | 0.00 | 0.472352E+10 | 0.00 | 0.00 | 87569723.25 | 0.00 | 0.00 | 0.00 | 0.214576E+10 | 0.00 |
November | 0.381239E+11 | 0.119788E+11 | 0.110862E+11 | 0.00 | 0.495015E+10 | 0.00 | 0.00 | 1745104.22 | 0.00 | 0.00 | 0.00 | 0.212075E+10 | 0.00 |
December | 0.396181E+11 | 0.129499E+11 | 0.115358E+11 | 0.00 | 0.618857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224672E+10 | 0.00 |
Annual Sum or Average | 0.476129E+12 | 0.123404E+12 | 0.139282E+12 | 0.647075E+11 | 0.00 | 0.221356E+11 | 0.260478E+11 | ||||||
Minimum of Months | 0.362526E+11 | 0.782086E+10 | 0.105871E+11 | 0.00 | 0.462677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205594E+10 | 0.00 |
Maximum of Months | 0.418523E+11 | 0.129499E+11 | 0.123357E+11 | 0.00 | 0.618857E+10 | 0.00 | 0.00 | 0.654416E+10 | 0.00 | 0.00 | 0.00 | 0.234424E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.897655E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.118294E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.764866E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.522358E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.150800E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.123134E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.127224E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.127239E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.123673E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.350831E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.609310E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.170927E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.668930E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.123134E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.170927E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35189.04 | 02-JAN-09:09 | 7857.00 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4765.27 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35189.04 | 01-FEB-09:09 | 7857.00 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 4765.27 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35189.04 | 01-MAR-09:09 | 7857.00 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4765.27 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35189.04 | 01-APR-08:09 | 7857.00 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 4765.27 | 03-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35189.04 | 01-MAY-08:09 | 7857.00 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 4442.34 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35189.04 | 01-JUN-08:09 | 7857.00 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 6747.64 | 26-JUN-09:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35189.04 | 01-JUL-08:09 | 7857.00 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6747.64 | 10-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35189.04 | 01-AUG-08:09 | 7857.00 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6747.64 | 07-AUG-10:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35189.04 | 01-SEP-08:09 | 7857.00 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 6747.64 | 07-SEP-13:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35189.04 | 02-OCT-08:09 | 7857.00 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 4765.27 | 30-OCT-06:19 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35189.04 | 01-NOV-08:09 | 7857.00 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 4765.27 | 01-NOV-06:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35189.04 | 01-DEC-09:09 | 7857.00 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4765.27 | 05-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35189.04 | 7857.00 | 10112.62 | 0.00 | 4442.34 | 0.00 | 0.00 | |||||
Maximum of Months | 35189.04 | 7857.00 | 10112.62 | 0.00 | 6747.64 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2593.62 | 31-JAN-12:20 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2604.56 | 13-FEB-12:00 | 0.00 |
March | 645.57 | 13-MAR-15:00 | 0.00 | 0.00 | 0.00 | 2586.95 | 02-MAR-12:09 | 0.00 |
April | 111.03 | 20-APR-12:00 | 0.00 | 0.00 | 0.00 | 2470.79 | 01-APR-11:39 | 0.00 |
May | 3620.16 | 17-MAY-13:39 | 0.00 | 0.00 | 0.00 | 2260.47 | 01-MAY-11:50 | 0.00 |
June | 17617.70 | 26-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1972.70 | 01-JUN-11:00 | 0.00 |
July | 14596.91 | 15-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1799.00 | 03-JUL-11:50 | 0.00 |
August | 14634.56 | 16-AUG-16:10 | 0.00 | 0.00 | 0.00 | 1789.31 | 30-AUG-11:09 | 0.00 |
September | 10129.48 | 09-SEP-12:00 | 0.00 | 0.00 | 0.00 | 1800.90 | 30-SEP-11:09 | 0.00 |
October | 2926.40 | 11-OCT-14:09 | 0.00 | 0.00 | 0.00 | 1972.30 | 27-OCT-11:20 | 0.00 |
November | 311.13 | 07-NOV-14:00 | 0.00 | 0.00 | 0.00 | 2274.32 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2479.32 | 30-DEC-12:50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1789.31 | 0.00 | ||
Maximum of Months | 17617.70 | 0.00 | 0.00 | 0.00 | 2604.56 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 55632.66 | 05-JAN-16:49 | 31277.33 | 10112.62 | 7857.00 | 0.00 | 4765.27 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52166.08 | 11-FEB-13:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4765.27 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 52342.66 | 14-MAR-14:20 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4442.34 | 0.00 | 0.00 | 562.69 | 0.00 |
April | 51838.29 | 03-APR-10:20 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4765.27 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 55111.65 | 17-MAY-13:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4442.34 | 0.00 | 0.00 | 3620.16 | 0.00 |
June | 70371.60 | 26-JUN-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6747.64 | 0.00 | 0.00 | 16557.97 | 0.00 |
July | 67481.45 | 17-JUL-13:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6747.64 | 0.00 | 0.00 | 13711.11 | 0.00 |
August | 68283.22 | 16-AUG-13:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6747.64 | 0.00 | 0.00 | 14516.41 | 0.00 |
September | 63911.70 | 09-SEP-12:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6747.64 | 0.00 | 0.00 | 10107.83 | 0.00 |
October | 54410.40 | 11-OCT-14:20 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4442.34 | 0.00 | 0.00 | 2897.82 | 0.00 |
November | 55626.62 | 29-NOV-16:40 | 31277.33 | 10112.62 | 7857.00 | 0.00 | 4765.27 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 55630.89 | 23-DEC-16:49 | 31277.33 | 10112.62 | 7857.00 | 0.00 | 4765.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 51838.29 | 31277.33 | 10112.62 | 0.00 | 0.00 | 4442.34 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 70371.60 | 35189.04 | 10112.62 | 7857.00 | 0.00 | 6747.64 | 0.00 | 0.00 | 16557.97 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 149500.63 | 06-JAN-06:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 200500.82 | 12-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 253347.38 | 19-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 148677.85 | 16-APR-15:50 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 56769.54 | 02-MAY-05:00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 6054.97 | 28-JUN-05:19 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 4750.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 7168.38 | 14-AUG-05:00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 12842.20 | 22-SEP-06:19 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 131560.57 | 31-OCT-23:49 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 209747.02 | 30-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 275331.67 | 21-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 4750.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 275331.67 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.00 | 19.24 | 8.17 | 19.68 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13.50 | 17.55 | 8.50 | 19.05 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10.83 | 18.14 | 7.50 | 19.56 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7.33 | 19.08 | 6.33 | 19.73 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1.83 | 20.06 | 1.83 | 20.06 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.55 | 1.17 | 24.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.57 | 0.50 | 24.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.52 | 0.50 | 24.52 |
September | 0.17 | 20.47 | 0.17 | 20.47 | 0.17 | 24.46 | 0.17 | 24.46 |
October | 4.50 | 19.07 | 3.83 | 19.78 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.67 | 19.53 | 6.33 | 19.77 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17.83 | 17.18 | 8.67 | 19.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 71.67 | 18.27 | 51.33 | 19.58 | 2.33 | 24.54 | 2.33 | 24.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 17.83 | 20.47 | 8.67 | 20.47 | 1.17 | 24.57 | 1.17 | 24.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 83.33 | 14.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 85.17 | 14.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 69.67 | 14.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 53.33 | 14.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6.83 | 14.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.54 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.52 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.45 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.45 | 0.00 | 0.00 |
October | 27.00 | 14.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 55.67 | 14.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 102.67 | 13.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 483.67 | 14.23 | 0.00 | 28.17 | 27.50 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.67 | 14.65 | 0.00 | 0.00 | 12.17 | 27.54 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14.00 | 8.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14.00 | 8.87 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.00 | 8.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.24 | 281.00 | 21.12 | 281.00 | 21.12 |
February | 276.00 | 21.13 | 266.00 | 21.06 | 266.00 | 21.06 |
March | 324.00 | 21.56 | 258.83 | 21.13 | 258.83 | 21.13 |
April | 300.00 | 21.67 | 218.17 | 21.14 | 218.17 | 21.14 |
May | 307.17 | 23.02 | 58.00 | 21.17 | 58.00 | 21.17 |
June | 38.67 | 23.74 | 142.00 | 23.90 | 2.50 | 23.90 |
July | 31.33 | 23.83 | 200.83 | 23.89 | 23.50 | 23.91 |
August | 14.83 | 23.78 | 191.50 | 23.89 | 5.17 | 23.90 |
September | 111.83 | 23.51 | 73.17 | 23.74 | 4.00 | 21.05 |
October | 300.00 | 22.36 | 126.83 | 21.14 | 126.83 | 21.14 |
November | 288.00 | 21.54 | 226.50 | 21.13 | 226.50 | 21.13 |
December | 300.00 | 21.22 | 286.17 | 21.12 | 286.17 | 21.12 |
Annual Sum or Average | 2591.83 | 21.87 | 2329.00 | 21.84 | 1756.67 | 21.17 |
Minimum of Months | 14.83 | 21.13 | 58.00 | 21.06 | 2.50 | 21.05 |
Maximum of Months | 324.00 | 23.83 | 286.17 | 23.90 | 286.17 | 23.91 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 46223365.52 | 12657845.40 | 17.42 | 46223365.52 | 0.00 | 0.00 | 0.15 | 13-MAR-16:00 | 0.00 | 01-MAR-00:03 | 2371.08 | 13-MAR-16:00 | 2371.08 | 13-MAR-16:00 | 0.00 | 13-MAR-14:20 | 645.57 | 13-MAR-16:00 | 0.00 | 01-MAR-00:03 |
April | 769145.88 | 213641.63 | 8.42 | 769145.88 | 0.00 | 0.00 | 0.03 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 400.14 | 20-APR-13:00 | 400.14 | 20-APR-13:00 | 0.00 | 07-APR-14:40 | 111.03 | 20-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.982587E+09 | 0.271504E+09 | 128.22 | 0.980958E+09 | 1629612.44 | 0.00 | 0.38 | 31-MAY-16:00 | 0.00 | 01-MAY-00:10 | 6227.61 | 31-MAY-16:00 | 6227.61 | 31-MAY-16:00 | 147.16 | 30-MAY-16:00 | 1777.62 | 31-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.659446E+10 | 0.189325E+10 | 266.22 | 0.633225E+10 | 0.262213E+09 | 0.00 | 1.00 | 06-JUN-05:03 | 0.00 | 01-JUN-00:10 | 20065.05 | 21-JUN-05:50 | 18107.13 | 07-JUN-05:03 | 8712.17 | 21-JUN-05:50 | 4797.08 | 26-JUN-16:10 | 0.00 | 01-JUN-00:10 |
July | 0.699201E+10 | 0.197766E+10 | 261.07 | 0.655735E+10 | 0.434667E+09 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 20501.92 | 28-JUL-05:01 | 18107.13 | 01-JUL-05:06 | 9503.81 | 28-JUL-05:50 | 4830.82 | 28-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.677164E+10 | 0.192157E+10 | 270.41 | 0.649025E+10 | 0.281391E+09 | 0.00 | 1.00 | 01-AUG-05:03 | 0.00 | 01-AUG-00:10 | 20584.37 | 04-AUG-05:01 | 18107.13 | 02-AUG-05:03 | 9996.18 | 04-AUG-05:15 | 4847.54 | 04-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.427805E+10 | 0.118501E+10 | 224.36 | 0.424025E+10 | 37794113.28 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 | 18179.82 | 13-SEP-05:01 | 18160.31 | 13-SEP-05:41 | 5037.12 | 01-SEP-05:02 | 4305.59 | 13-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.293192E+09 | 79733874.11 | 67.00 | 0.293192E+09 | 1.00 | 0.00 | 0.38 | 11-OCT-15:10 | 0.00 | 01-OCT-00:10 | 6091.53 | 11-OCT-15:10 | 6091.53 | 11-OCT-15:10 | 0.00 | 03-OCT-14:30 | 1664.17 | 11-OCT-14:50 | 0.00 | 01-OCT-00:10 |
November | 6317626.55 | 1745104.22 | 6.50 | 6317626.55 | 0.00 | 0.00 | 0.07 | 07-NOV-15:00 | 0.00 | 01-NOV-00:10 | 1129.21 | 07-NOV-15:00 | 1129.21 | 07-NOV-15:00 | 0.00 | 07-NOV-14:30 | 311.13 | 07-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.259652E+11 | 0.734334E+10 | 1249.61 | 0.249476E+11 | 0.101770E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.699201E+10 | 0.197766E+10 | 270.41 | 0.655735E+10 | 0.434667E+09 | 0.00 | 1.00 | 0.00 | 20584.37 | 18160.31 | 9996.18 | 4847.54 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.161063E+09 | 50734325.57 | 16.67 | 0.161063E+09 | 0.00 | 0.00 | 0.15 | 17-MAY-13:40 | 0.00 | 01-MAY-00:10 | 5941.32 | 17-MAY-13:40 | 5941.32 | 17-MAY-13:40 | 0.00 | 17-MAY-13:30 | 1915.32 | 17-MAY-13:40 | 0.00 | 01-MAY-00:10 |
June | 0.135341E+11 | 0.430295E+10 | 252.29 | 0.132050E+11 | 0.329179E+09 | 0.00 | 1.00 | 06-JUN-18:31 | 0.00 | 01-JUN-00:10 | 57622.98 | 18-JUN-09:41 | 50449.35 | 08-JUN-18:10 | 19549.87 | 18-JUN-09:46 | 14931.89 | 26-JUN-17:42 | 0.00 | 01-JUN-00:10 |
July | 0.145011E+11 | 0.456650E+10 | 255.76 | 0.140947E+11 | 0.406402E+09 | 0.00 | 1.00 | 01-JUL-17:06 | 0.00 | 01-JUL-00:10 | 59143.48 | 30-JUL-11:10 | 50118.19 | 18-JUL-19:11 | 23006.96 | 30-JUL-11:10 | 14946.44 | 30-JUL-12:32 | 0.00 | 01-JUL-00:10 |
August | 0.133530E+11 | 0.416385E+10 | 252.69 | 0.131083E+11 | 0.244720E+09 | 0.00 | 1.00 | 02-AUG-18:01 | 0.00 | 01-AUG-00:10 | 54468.45 | 03-AUG-17:41 | 50593.98 | 06-AUG-15:10 | 12769.45 | 03-AUG-18:10 | 14625.11 | 16-AUG-17:06 | 0.00 | 01-AUG-00:10 |
September | 0.550919E+10 | 0.170045E+10 | 156.56 | 0.549305E+10 | 16138008.94 | 0.00 | 1.00 | 02-SEP-17:12 | 0.00 | 01-SEP-00:10 | 50985.04 | 03-SEP-14:01 | 50242.30 | 03-SEP-14:51 | 1999.67 | 03-SEP-14:07 | 13777.07 | 10-SEP-12:13 | 0.00 | 01-SEP-00:10 |
October | 25428798.53 | 7835849.13 | 2.50 | 25428798.53 | 0.00 | 0.00 | 0.10 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 | 4177.39 | 11-OCT-14:00 | 4177.39 | 11-OCT-14:00 | 0.00 | 11-OCT-14:10 | 1296.48 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.470839E+11 | 0.147923E+11 | 936.46 | 0.460875E+11 | 0.996439E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.145011E+11 | 0.456650E+10 | 255.76 | 0.140947E+11 | 0.406402E+09 | 0.00 | 1.00 | 0.00 | 59143.48 | 50593.98 | 23006.96 | 14946.44 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.19 | 74.23 | 42.96 | 92.14 | 167.33 | 0.00 | 0.00 | 744.00 |
February | 142.26 | 88.41 | 53.85 | 114.28 | 171.71 | 0.00 | 0.00 | 672.00 |
March | 165.84 | 91.58 | 74.27 | 148.90 | 128.06 | 0.00 | 0.00 | 744.00 |
April | 155.43 | 65.56 | 89.87 | 132.41 | 111.04 | 0.00 | 0.00 | 720.00 |
May | 190.53 | 67.13 | 123.40 | 189.86 | 71.13 | 0.00 | 0.00 | 744.00 |
June | 233.29 | 112.34 | 120.95 | 276.94 | 53.68 | 0.00 | 0.00 | 720.00 |
July | 189.76 | 69.39 | 120.37 | 222.90 | 51.19 | 0.00 | 0.00 | 744.00 |
August | 198.61 | 98.26 | 100.35 | 230.75 | 58.33 | 0.00 | 0.00 | 744.00 |
September | 176.35 | 84.77 | 91.58 | 193.55 | 81.78 | 0.00 | 0.00 | 720.00 |
October | 147.44 | 84.12 | 63.32 | 136.40 | 140.56 | 0.00 | 0.00 | 744.00 |
November | 121.18 | 73.51 | 47.67 | 99.21 | 156.05 | 0.00 | 0.00 | 720.00 |
December | 98.00 | 57.88 | 40.11 | 68.02 | 196.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 161.37 | 80.50 | 80.87 | 158.96 | 115.32 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 98.00 | 57.88 | 40.11 | 68.02 | 51.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 233.29 | 112.34 | 123.40 | 276.94 | 196.50 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.19 | 74.23 | 42.96 | 92.14 | 167.33 | 0.00 | 0.00 | 744.00 |
February | 142.26 | 88.41 | 53.85 | 114.28 | 171.71 | 0.00 | 0.00 | 672.00 |
March | 165.84 | 91.58 | 74.27 | 148.90 | 128.06 | 0.00 | 0.00 | 744.00 |
April | 155.43 | 65.56 | 89.87 | 132.41 | 111.04 | 0.00 | 0.00 | 720.00 |
May | 190.53 | 67.13 | 123.40 | 189.86 | 71.13 | 0.00 | 0.00 | 744.00 |
June | 233.29 | 112.34 | 120.95 | 276.94 | 53.68 | 0.00 | 0.00 | 720.00 |
July | 189.76 | 69.39 | 120.37 | 222.90 | 51.19 | 0.00 | 0.00 | 744.00 |
August | 198.61 | 98.26 | 100.35 | 230.75 | 58.33 | 0.00 | 0.00 | 744.00 |
September | 176.35 | 84.77 | 91.58 | 193.55 | 81.78 | 0.00 | 0.00 | 720.00 |
October | 147.44 | 84.12 | 63.32 | 136.40 | 140.56 | 0.00 | 0.00 | 744.00 |
November | 121.18 | 73.51 | 47.67 | 99.21 | 156.05 | 0.00 | 0.00 | 720.00 |
December | 98.00 | 57.88 | 40.11 | 68.02 | 196.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 161.37 | 80.50 | 80.87 | 158.96 | 115.32 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 98.00 | 57.88 | 40.11 | 68.02 | 51.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 233.29 | 112.34 | 123.40 | 276.94 | 196.50 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.54 | 0.00 | 20.54 | 2.97 | 104.59 | 0.00 | 0.00 | 744.00 |
February | 25.82 | 0.00 | 25.82 | 3.66 | 106.93 | 0.00 | 0.00 | 672.00 |
March | 35.14 | 0.00 | 35.14 | 12.92 | 78.30 | 0.00 | 0.00 | 744.00 |
April | 44.14 | 0.27 | 43.87 | 20.18 | 66.35 | 0.00 | 0.00 | 720.00 |
May | 60.32 | 2.02 | 58.31 | 44.66 | 40.36 | 0.00 | 0.00 | 744.00 |
June | 65.98 | 7.22 | 58.76 | 65.63 | 28.67 | 0.00 | 0.00 | 720.00 |
July | 62.62 | 4.14 | 58.48 | 65.47 | 28.07 | 0.00 | 0.00 | 744.00 |
August | 49.95 | 1.36 | 48.59 | 49.80 | 33.73 | 0.00 | 0.00 | 744.00 |
September | 41.82 | 0.03 | 41.80 | 36.74 | 47.92 | 0.00 | 0.00 | 720.00 |
October | 29.93 | 0.00 | 29.93 | 11.56 | 84.65 | 0.00 | 0.00 | 744.00 |
November | 22.72 | 0.00 | 22.72 | 4.77 | 95.93 | 0.00 | 0.00 | 720.00 |
December | 19.22 | 0.00 | 19.22 | 2.68 | 122.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 39.92 | 1.26 | 38.67 | 26.89 | 69.66 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.22 | 0.00 | 19.22 | 2.68 | 28.07 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.98 | 7.22 | 58.76 | 65.63 | 122.76 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.54 | 0.00 | 20.54 | 2.97 | 104.59 | 0.00 | 0.00 | 744.00 |
February | 25.82 | 0.00 | 25.82 | 3.66 | 106.93 | 0.00 | 0.00 | 672.00 |
March | 35.14 | 0.00 | 35.14 | 12.92 | 78.30 | 0.00 | 0.00 | 744.00 |
April | 44.14 | 0.27 | 43.87 | 20.18 | 66.35 | 0.00 | 0.00 | 720.00 |
May | 60.32 | 2.02 | 58.30 | 44.66 | 40.36 | 0.00 | 0.00 | 744.00 |
June | 65.98 | 7.22 | 58.76 | 65.62 | 28.67 | 0.00 | 0.00 | 720.00 |
July | 62.62 | 4.14 | 58.48 | 65.47 | 28.07 | 0.00 | 0.00 | 744.00 |
August | 49.95 | 1.36 | 48.59 | 49.80 | 33.73 | 0.00 | 0.00 | 744.00 |
September | 41.82 | 0.03 | 41.79 | 36.74 | 47.92 | 0.00 | 0.00 | 720.00 |
October | 29.93 | 0.00 | 29.93 | 11.56 | 84.65 | 0.00 | 0.00 | 744.00 |
November | 22.72 | 0.00 | 22.72 | 4.77 | 95.93 | 0.00 | 0.00 | 720.00 |
December | 19.22 | 0.00 | 19.22 | 2.68 | 122.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 39.92 | 1.26 | 38.67 | 26.89 | 69.66 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.22 | 0.00 | 19.22 | 2.68 | 28.07 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 65.98 | 7.22 | 58.76 | 65.62 | 122.76 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.13 | 23.62 | 10.51 | 21.70 | 45.46 | 0.00 | 0.00 | 744.00 |
February | 51.99 | 39.61 | 12.38 | 44.43 | 45.59 | 0.00 | 0.00 | 672.00 |
March | 69.30 | 48.52 | 20.79 | 69.74 | 33.19 | 0.00 | 0.00 | 744.00 |
April | 75.64 | 44.51 | 31.13 | 78.87 | 26.97 | 0.00 | 0.00 | 720.00 |
May | 96.99 | 52.25 | 44.74 | 107.74 | 22.99 | 0.00 | 0.00 | 744.00 |
June | 122.05 | 85.82 | 36.23 | 139.30 | 26.78 | 0.00 | 0.00 | 720.00 |
July | 105.51 | 63.46 | 42.05 | 116.69 | 27.71 | 0.00 | 0.00 | 744.00 |
August | 104.95 | 75.39 | 29.56 | 116.26 | 30.11 | 0.00 | 0.00 | 744.00 |
September | 81.71 | 54.89 | 26.82 | 85.40 | 36.33 | 0.00 | 0.00 | 720.00 |
October | 57.35 | 40.39 | 16.96 | 52.38 | 43.88 | 0.00 | 0.00 | 744.00 |
November | 39.99 | 28.31 | 11.68 | 31.03 | 40.07 | 0.00 | 0.00 | 720.00 |
December | 28.56 | 18.12 | 10.44 | 14.68 | 53.08 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.43 | 47.92 | 24.52 | 73.31 | 35.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.56 | 18.12 | 10.44 | 14.68 | 22.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 122.05 | 85.82 | 44.74 | 139.30 | 53.08 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.13 | 23.62 | 10.51 | 21.70 | 45.46 | 0.00 | 0.00 | 744.00 |
February | 51.99 | 39.61 | 12.38 | 44.43 | 45.59 | 0.00 | 0.00 | 672.00 |
March | 69.30 | 48.52 | 20.79 | 69.74 | 33.19 | 0.00 | 0.00 | 744.00 |
April | 75.64 | 44.51 | 31.13 | 78.87 | 26.97 | 0.00 | 0.00 | 720.00 |
May | 96.99 | 52.25 | 44.74 | 107.74 | 22.99 | 0.00 | 0.00 | 744.00 |
June | 122.05 | 85.82 | 36.23 | 139.30 | 26.78 | 0.00 | 0.00 | 720.00 |
July | 105.51 | 63.46 | 42.05 | 116.69 | 27.71 | 0.00 | 0.00 | 744.00 |
August | 104.95 | 75.39 | 29.56 | 116.26 | 30.11 | 0.00 | 0.00 | 744.00 |
September | 81.71 | 54.89 | 26.82 | 85.40 | 36.33 | 0.00 | 0.00 | 720.00 |
October | 57.35 | 40.39 | 16.96 | 52.38 | 43.88 | 0.00 | 0.00 | 744.00 |
November | 39.99 | 28.31 | 11.68 | 31.03 | 40.07 | 0.00 | 0.00 | 720.00 |
December | 28.56 | 18.12 | 10.44 | 14.68 | 53.08 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.43 | 47.92 | 24.52 | 73.31 | 35.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.56 | 18.12 | 10.44 | 14.68 | 22.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 122.05 | 85.82 | 44.74 | 139.30 | 53.08 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.13 | 23.62 | 10.51 | 21.70 | 45.46 | 0.00 | 0.00 | 744.00 |
February | 51.99 | 39.61 | 12.38 | 44.43 | 45.59 | 0.00 | 0.00 | 672.00 |
March | 69.30 | 48.52 | 20.79 | 69.74 | 33.19 | 0.00 | 0.00 | 744.00 |
April | 75.64 | 44.51 | 31.13 | 78.87 | 26.97 | 0.00 | 0.00 | 720.00 |
May | 96.99 | 52.25 | 44.74 | 107.74 | 22.99 | 0.00 | 0.00 | 744.00 |
June | 122.05 | 85.82 | 36.23 | 139.30 | 26.78 | 0.00 | 0.00 | 720.00 |
July | 105.51 | 63.46 | 42.05 | 116.69 | 27.71 | 0.00 | 0.00 | 744.00 |
August | 104.95 | 75.39 | 29.56 | 116.26 | 30.11 | 0.00 | 0.00 | 744.00 |
September | 81.71 | 54.89 | 26.82 | 85.40 | 36.33 | 0.00 | 0.00 | 720.00 |
October | 57.35 | 40.39 | 16.96 | 52.38 | 43.88 | 0.00 | 0.00 | 744.00 |
November | 39.99 | 28.31 | 11.68 | 31.03 | 40.07 | 0.00 | 0.00 | 720.00 |
December | 28.56 | 18.12 | 10.44 | 14.68 | 53.08 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.43 | 47.92 | 24.52 | 73.31 | 35.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.56 | 18.12 | 10.44 | 14.68 | 22.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 122.05 | 85.82 | 44.74 | 139.30 | 53.08 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.13 | 23.62 | 10.51 | 21.70 | 45.46 | 0.00 | 0.00 | 744.00 |
February | 51.99 | 39.61 | 12.38 | 44.43 | 45.59 | 0.00 | 0.00 | 672.00 |
March | 69.30 | 48.52 | 20.79 | 69.74 | 33.19 | 0.00 | 0.00 | 744.00 |
April | 75.64 | 44.51 | 31.13 | 78.87 | 26.97 | 0.00 | 0.00 | 720.00 |
May | 96.99 | 52.25 | 44.74 | 107.74 | 22.99 | 0.00 | 0.00 | 744.00 |
June | 122.05 | 85.82 | 36.23 | 139.30 | 26.78 | 0.00 | 0.00 | 720.00 |
July | 105.51 | 63.46 | 42.05 | 116.69 | 27.71 | 0.00 | 0.00 | 744.00 |
August | 104.95 | 75.39 | 29.56 | 116.26 | 30.11 | 0.00 | 0.00 | 744.00 |
September | 81.71 | 54.89 | 26.82 | 85.40 | 36.33 | 0.00 | 0.00 | 720.00 |
October | 57.35 | 40.39 | 16.96 | 52.38 | 43.88 | 0.00 | 0.00 | 744.00 |
November | 39.99 | 28.31 | 11.68 | 31.03 | 40.07 | 0.00 | 0.00 | 720.00 |
December | 28.56 | 18.12 | 10.44 | 14.68 | 53.08 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.43 | 47.92 | 24.52 | 73.31 | 35.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.56 | 18.12 | 10.44 | 14.68 | 22.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 122.05 | 85.82 | 44.74 | 139.30 | 53.08 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.13 | 23.62 | 10.51 | 21.70 | 45.46 | 0.00 | 0.00 | 744.00 |
February | 51.99 | 39.61 | 12.38 | 44.43 | 45.59 | 0.00 | 0.00 | 672.00 |
March | 69.30 | 48.52 | 20.79 | 69.74 | 33.19 | 0.00 | 0.00 | 744.00 |
April | 75.64 | 44.51 | 31.13 | 78.87 | 26.97 | 0.00 | 0.00 | 720.00 |
May | 96.99 | 52.25 | 44.74 | 107.74 | 22.99 | 0.00 | 0.00 | 744.00 |
June | 122.05 | 85.82 | 36.23 | 139.30 | 26.78 | 0.00 | 0.00 | 720.00 |
July | 105.51 | 63.46 | 42.05 | 116.69 | 27.71 | 0.00 | 0.00 | 744.00 |
August | 104.95 | 75.39 | 29.56 | 116.26 | 30.11 | 0.00 | 0.00 | 744.00 |
September | 81.71 | 54.89 | 26.82 | 85.40 | 36.33 | 0.00 | 0.00 | 720.00 |
October | 57.35 | 40.39 | 16.96 | 52.38 | 43.88 | 0.00 | 0.00 | 744.00 |
November | 39.99 | 28.31 | 11.68 | 31.03 | 40.07 | 0.00 | 0.00 | 720.00 |
December | 28.56 | 18.12 | 10.44 | 14.68 | 53.08 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.43 | 47.92 | 24.52 | 73.31 | 35.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.56 | 18.12 | 10.44 | 14.68 | 22.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 122.05 | 85.82 | 44.74 | 139.30 | 53.08 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.13 | 23.62 | 10.51 | 21.70 | 45.46 | 0.00 | 0.00 | 744.00 |
February | 51.99 | 39.61 | 12.38 | 44.43 | 45.59 | 0.00 | 0.00 | 672.00 |
March | 69.30 | 48.52 | 20.79 | 69.74 | 33.19 | 0.00 | 0.00 | 744.00 |
April | 75.64 | 44.51 | 31.13 | 78.87 | 26.97 | 0.00 | 0.00 | 720.00 |
May | 96.99 | 52.25 | 44.74 | 107.74 | 22.99 | 0.00 | 0.00 | 744.00 |
June | 122.05 | 85.82 | 36.23 | 139.30 | 26.78 | 0.00 | 0.00 | 720.00 |
July | 105.51 | 63.46 | 42.05 | 116.69 | 27.71 | 0.00 | 0.00 | 744.00 |
August | 104.95 | 75.39 | 29.56 | 116.26 | 30.11 | 0.00 | 0.00 | 744.00 |
September | 81.71 | 54.89 | 26.82 | 85.40 | 36.33 | 0.00 | 0.00 | 720.00 |
October | 57.35 | 40.39 | 16.96 | 52.38 | 43.88 | 0.00 | 0.00 | 744.00 |
November | 39.99 | 28.31 | 11.68 | 31.03 | 40.07 | 0.00 | 0.00 | 720.00 |
December | 28.56 | 18.12 | 10.44 | 14.68 | 53.08 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.43 | 47.92 | 24.52 | 73.31 | 35.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.56 | 18.12 | 10.44 | 14.68 | 22.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 122.05 | 85.82 | 44.74 | 139.30 | 53.08 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.13 | 23.62 | 10.51 | 21.70 | 45.46 | 0.00 | 0.00 | 744.00 |
February | 51.99 | 39.61 | 12.38 | 44.43 | 45.59 | 0.00 | 0.00 | 672.00 |
March | 69.30 | 48.52 | 20.79 | 69.74 | 33.19 | 0.00 | 0.00 | 744.00 |
April | 75.64 | 44.51 | 31.13 | 78.87 | 26.97 | 0.00 | 0.00 | 720.00 |
May | 96.99 | 52.25 | 44.74 | 107.74 | 22.99 | 0.00 | 0.00 | 744.00 |
June | 122.05 | 85.82 | 36.23 | 139.30 | 26.78 | 0.00 | 0.00 | 720.00 |
July | 105.51 | 63.46 | 42.05 | 116.69 | 27.71 | 0.00 | 0.00 | 744.00 |
August | 104.95 | 75.39 | 29.56 | 116.26 | 30.11 | 0.00 | 0.00 | 744.00 |
September | 81.71 | 54.89 | 26.82 | 85.40 | 36.33 | 0.00 | 0.00 | 720.00 |
October | 57.35 | 40.39 | 16.96 | 52.38 | 43.88 | 0.00 | 0.00 | 744.00 |
November | 39.99 | 28.31 | 11.68 | 31.03 | 40.07 | 0.00 | 0.00 | 720.00 |
December | 28.56 | 18.12 | 10.44 | 14.68 | 53.08 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.43 | 47.92 | 24.52 | 73.31 | 35.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.56 | 18.12 | 10.44 | 14.68 | 22.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 122.05 | 85.82 | 44.74 | 139.30 | 53.08 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.13 | 23.62 | 10.51 | 21.70 | 45.46 | 0.00 | 0.00 | 744.00 |
February | 51.99 | 39.61 | 12.38 | 44.43 | 45.59 | 0.00 | 0.00 | 672.00 |
March | 69.30 | 48.52 | 20.79 | 69.74 | 33.19 | 0.00 | 0.00 | 744.00 |
April | 75.64 | 44.51 | 31.13 | 78.87 | 26.97 | 0.00 | 0.00 | 720.00 |
May | 96.99 | 52.25 | 44.74 | 107.74 | 22.99 | 0.00 | 0.00 | 744.00 |
June | 122.05 | 85.82 | 36.23 | 139.30 | 26.78 | 0.00 | 0.00 | 720.00 |
July | 105.51 | 63.46 | 42.05 | 116.69 | 27.71 | 0.00 | 0.00 | 744.00 |
August | 104.95 | 75.39 | 29.56 | 116.26 | 30.11 | 0.00 | 0.00 | 744.00 |
September | 81.71 | 54.89 | 26.82 | 85.40 | 36.33 | 0.00 | 0.00 | 720.00 |
October | 57.35 | 40.39 | 16.96 | 52.38 | 43.88 | 0.00 | 0.00 | 744.00 |
November | 39.99 | 28.31 | 11.68 | 31.03 | 40.07 | 0.00 | 0.00 | 720.00 |
December | 28.56 | 18.12 | 10.44 | 14.68 | 53.08 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.43 | 47.92 | 24.52 | 73.31 | 35.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.56 | 18.12 | 10.44 | 14.68 | 22.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 122.05 | 85.82 | 44.74 | 139.30 | 53.08 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.13 | 23.62 | 10.51 | 21.70 | 45.46 | 0.00 | 0.00 | 744.00 |
February | 51.99 | 39.61 | 12.38 | 44.43 | 45.59 | 0.00 | 0.00 | 672.00 |
March | 69.30 | 48.52 | 20.79 | 69.74 | 33.19 | 0.00 | 0.00 | 744.00 |
April | 75.64 | 44.51 | 31.13 | 78.87 | 26.97 | 0.00 | 0.00 | 720.00 |
May | 96.99 | 52.25 | 44.74 | 107.74 | 22.99 | 0.00 | 0.00 | 744.00 |
June | 122.05 | 85.82 | 36.23 | 139.30 | 26.78 | 0.00 | 0.00 | 720.00 |
July | 105.51 | 63.46 | 42.05 | 116.69 | 27.71 | 0.00 | 0.00 | 744.00 |
August | 104.95 | 75.39 | 29.56 | 116.26 | 30.11 | 0.00 | 0.00 | 744.00 |
September | 81.71 | 54.89 | 26.82 | 85.40 | 36.33 | 0.00 | 0.00 | 720.00 |
October | 57.35 | 40.39 | 16.96 | 52.38 | 43.88 | 0.00 | 0.00 | 744.00 |
November | 39.99 | 28.31 | 11.68 | 31.03 | 40.07 | 0.00 | 0.00 | 720.00 |
December | 28.56 | 18.12 | 10.44 | 14.68 | 53.08 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.43 | 47.92 | 24.52 | 73.31 | 35.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.56 | 18.12 | 10.44 | 14.68 | 22.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 122.05 | 85.82 | 44.74 | 139.30 | 53.08 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.13 | 23.62 | 10.51 | 21.70 | 45.46 | 0.00 | 0.00 | 744.00 |
February | 51.99 | 39.61 | 12.38 | 44.43 | 45.59 | 0.00 | 0.00 | 672.00 |
March | 69.30 | 48.52 | 20.79 | 69.74 | 33.19 | 0.00 | 0.00 | 744.00 |
April | 75.64 | 44.51 | 31.13 | 78.87 | 26.97 | 0.00 | 0.00 | 720.00 |
May | 96.99 | 52.25 | 44.74 | 107.74 | 22.99 | 0.00 | 0.00 | 744.00 |
June | 122.05 | 85.82 | 36.23 | 139.30 | 26.78 | 0.00 | 0.00 | 720.00 |
July | 105.51 | 63.46 | 42.05 | 116.69 | 27.71 | 0.00 | 0.00 | 744.00 |
August | 104.95 | 75.39 | 29.56 | 116.26 | 30.11 | 0.00 | 0.00 | 744.00 |
September | 81.71 | 54.89 | 26.82 | 85.40 | 36.33 | 0.00 | 0.00 | 720.00 |
October | 57.35 | 40.39 | 16.96 | 52.38 | 43.88 | 0.00 | 0.00 | 744.00 |
November | 39.99 | 28.31 | 11.68 | 31.03 | 40.07 | 0.00 | 0.00 | 720.00 |
December | 28.56 | 18.12 | 10.44 | 14.68 | 53.08 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 72.43 | 47.92 | 24.52 | 73.31 | 35.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.56 | 18.12 | 10.44 | 14.68 | 22.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 122.05 | 85.82 | 44.74 | 139.30 | 53.08 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.313868E+09 | 0.198807E+09 | 0.115061E+09 | 0.246796E+09 | 0.448177E+09 |
February | 0.344146E+09 | 0.213871E+09 | 0.130275E+09 | 0.276473E+09 | 0.415399E+09 |
March | 0.444193E+09 | 0.245280E+09 | 0.198914E+09 | 0.398806E+09 | 0.343000E+09 |
April | 0.402878E+09 | 0.169944E+09 | 0.232934E+09 | 0.343209E+09 | 0.287803E+09 |
May | 0.510310E+09 | 0.179799E+09 | 0.330511E+09 | 0.508534E+09 | 0.190527E+09 |
June | 0.604696E+09 | 0.291189E+09 | 0.313507E+09 | 0.717829E+09 | 0.139135E+09 |
July | 0.508259E+09 | 0.185865E+09 | 0.322394E+09 | 0.597016E+09 | 0.137106E+09 |
August | 0.531945E+09 | 0.263177E+09 | 0.268767E+09 | 0.618040E+09 | 0.156219E+09 |
September | 0.457101E+09 | 0.219725E+09 | 0.237376E+09 | 0.501693E+09 | 0.211975E+09 |
October | 0.394910E+09 | 0.225307E+09 | 0.169604E+09 | 0.365337E+09 | 0.376474E+09 |
November | 0.314097E+09 | 0.190530E+09 | 0.123567E+09 | 0.257150E+09 | 0.404472E+09 |
December | 0.262470E+09 | 0.155032E+09 | 0.107439E+09 | 0.182177E+09 | 0.526319E+09 |
Annual Sum or Average | 0.508887E+10 | 0.253853E+10 | 0.255035E+10 | 0.501306E+10 | 0.363661E+10 |
Minimum of Months | 0.262470E+09 | 0.155032E+09 | 0.107439E+09 | 0.182177E+09 | 0.137106E+09 |
Maximum of Months | 0.604696E+09 | 0.291189E+09 | 0.330511E+09 | 0.717829E+09 | 0.526319E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.313868E+09 | 0.198807E+09 | 0.115061E+09 | 0.246796E+09 | 0.448177E+09 |
February | 0.344146E+09 | 0.213871E+09 | 0.130275E+09 | 0.276473E+09 | 0.415399E+09 |
March | 0.444193E+09 | 0.245280E+09 | 0.198914E+09 | 0.398806E+09 | 0.343000E+09 |
April | 0.402878E+09 | 0.169944E+09 | 0.232934E+09 | 0.343209E+09 | 0.287803E+09 |
May | 0.510310E+09 | 0.179799E+09 | 0.330511E+09 | 0.508534E+09 | 0.190527E+09 |
June | 0.604696E+09 | 0.291189E+09 | 0.313507E+09 | 0.717829E+09 | 0.139135E+09 |
July | 0.508259E+09 | 0.185865E+09 | 0.322394E+09 | 0.597016E+09 | 0.137106E+09 |
August | 0.531945E+09 | 0.263177E+09 | 0.268767E+09 | 0.618040E+09 | 0.156219E+09 |
September | 0.457101E+09 | 0.219725E+09 | 0.237376E+09 | 0.501693E+09 | 0.211975E+09 |
October | 0.394910E+09 | 0.225307E+09 | 0.169604E+09 | 0.365337E+09 | 0.376474E+09 |
November | 0.314097E+09 | 0.190530E+09 | 0.123567E+09 | 0.257150E+09 | 0.404472E+09 |
December | 0.262470E+09 | 0.155032E+09 | 0.107439E+09 | 0.182177E+09 | 0.526319E+09 |
Annual Sum or Average | 0.508887E+10 | 0.253853E+10 | 0.255035E+10 | 0.501306E+10 | 0.363661E+10 |
Minimum of Months | 0.262470E+09 | 0.155032E+09 | 0.107439E+09 | 0.182177E+09 | 0.137106E+09 |
Maximum of Months | 0.604696E+09 | 0.291189E+09 | 0.330511E+09 | 0.717829E+09 | 0.526319E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55018621.59 | 0.00 | 55018621.59 | 7962012.74 | 0.280140E+09 |
February | 62459731.04 | 0.00 | 62459731.04 | 8847771.64 | 0.258675E+09 |
March | 94128251.80 | 9847.52 | 94118404.28 | 34594558.81 | 0.209722E+09 |
April | 0.114403E+09 | 698430.09 | 0.113705E+09 | 52310972.16 | 0.171983E+09 |
May | 0.161569E+09 | 5404391.79 | 0.156165E+09 | 0.119621E+09 | 0.108094E+09 |
June | 0.171018E+09 | 18707452.67 | 0.152311E+09 | 0.170104E+09 | 74320719.91 |
July | 0.167722E+09 | 11096722.75 | 0.156626E+09 | 0.175351E+09 | 75186284.73 |
August | 0.133788E+09 | 3638746.47 | 0.130149E+09 | 0.133392E+09 | 90346804.78 |
September | 0.108405E+09 | 69344.68 | 0.108335E+09 | 95232377.65 | 0.124216E+09 |
October | 80163923.72 | 0.00 | 80163923.72 | 30972378.06 | 0.226723E+09 |
November | 58891529.51 | 0.00 | 58891529.51 | 12367258.77 | 0.248640E+09 |
December | 51476761.10 | 0.00 | 51476761.10 | 7168749.86 | 0.328810E+09 |
Annual Sum or Average | 0.125904E+10 | 39624935.98 | 0.121942E+10 | 0.847923E+09 | 0.219686E+10 |
Minimum of Months | 51476761.10 | 0.00 | 51476761.10 | 7168749.86 | 74320719.91 |
Maximum of Months | 0.171018E+09 | 18707452.67 | 0.156626E+09 | 0.175351E+09 | 0.328810E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55017169.59 | 0.00 | 55017169.59 | 7961571.56 | 0.280140E+09 |
February | 62458191.40 | 0.00 | 62458191.40 | 8847364.78 | 0.258675E+09 |
March | 94125710.99 | 9847.06 | 94115863.93 | 34593164.41 | 0.209722E+09 |
April | 0.114400E+09 | 698397.35 | 0.113701E+09 | 52308672.33 | 0.171983E+09 |
May | 0.161564E+09 | 5404138.48 | 0.156160E+09 | 0.119616E+09 | 0.108094E+09 |
June | 0.171013E+09 | 18706575.83 | 0.152307E+09 | 0.170099E+09 | 74320076.24 |
July | 0.167717E+09 | 11096202.63 | 0.156621E+09 | 0.175346E+09 | 75185753.46 |
August | 0.133784E+09 | 3638575.92 | 0.130146E+09 | 0.133389E+09 | 90346183.89 |
September | 0.108402E+09 | 69341.43 | 0.108332E+09 | 95229932.42 | 0.124215E+09 |
October | 80161779.29 | 0.00 | 80161779.29 | 30971267.29 | 0.226723E+09 |
November | 58889979.65 | 0.00 | 58889979.65 | 12366749.10 | 0.248640E+09 |
December | 51475321.56 | 0.00 | 51475321.56 | 7168494.79 | 0.328810E+09 |
Annual Sum or Average | 0.125901E+10 | 39623078.71 | 0.121939E+10 | 0.847898E+09 | 0.219685E+10 |
Minimum of Months | 51475321.56 | 0.00 | 51475321.56 | 7168494.79 | 74320076.24 |
Maximum of Months | 0.171013E+09 | 18706575.83 | 0.156621E+09 | 0.175346E+09 | 0.328810E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91406748.52 | 63267129.23 | 28139619.29 | 58124168.86 | 0.121767E+09 |
February | 0.125771E+09 | 95826578.75 | 29944849.16 | 0.107478E+09 | 0.110292E+09 |
March | 0.185626E+09 | 0.129954E+09 | 55671958.13 | 0.186795E+09 | 88888625.41 |
April | 0.196061E+09 | 0.115364E+09 | 80696581.29 | 0.204424E+09 | 69901929.53 |
May | 0.259777E+09 | 0.139940E+09 | 0.119837E+09 | 0.288583E+09 | 61582250.64 |
June | 0.316352E+09 | 0.222441E+09 | 93911177.73 | 0.361056E+09 | 69408520.55 |
July | 0.282585E+09 | 0.169970E+09 | 0.112615E+09 | 0.312531E+09 | 74218710.93 |
August | 0.281099E+09 | 0.201932E+09 | 79166509.83 | 0.311382E+09 | 80634364.02 |
September | 0.211791E+09 | 0.142283E+09 | 69507741.14 | 0.221361E+09 | 94173722.15 |
October | 0.153606E+09 | 0.108176E+09 | 45429937.38 | 0.140301E+09 | 0.117523E+09 |
November | 0.103663E+09 | 73387760.52 | 30274928.23 | 80429578.71 | 0.103857E+09 |
December | 76493684.02 | 48527968.33 | 27965715.69 | 39324518.09 | 0.142160E+09 |
Annual Sum or Average | 0.228423E+10 | 0.151107E+10 | 0.773161E+09 | 0.231179E+10 | 0.113441E+10 |
Minimum of Months | 76493684.02 | 48527968.33 | 27965715.69 | 39324518.09 | 61582250.64 |
Maximum of Months | 0.316352E+09 | 0.222441E+09 | 0.119837E+09 | 0.361056E+09 | 0.142160E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91406748.52 | 63267129.23 | 28139619.29 | 58124168.86 | 0.121767E+09 |
February | 0.125771E+09 | 95826578.75 | 29944849.16 | 0.107478E+09 | 0.110292E+09 |
March | 0.185626E+09 | 0.129954E+09 | 55671958.13 | 0.186795E+09 | 88888625.41 |
April | 0.196061E+09 | 0.115364E+09 | 80696581.29 | 0.204424E+09 | 69901929.53 |
May | 0.259777E+09 | 0.139940E+09 | 0.119837E+09 | 0.288583E+09 | 61582250.64 |
June | 0.316352E+09 | 0.222441E+09 | 93911177.73 | 0.361056E+09 | 69408520.55 |
July | 0.282585E+09 | 0.169970E+09 | 0.112615E+09 | 0.312531E+09 | 74218710.93 |
August | 0.281099E+09 | 0.201932E+09 | 79166509.83 | 0.311382E+09 | 80634364.02 |
September | 0.211791E+09 | 0.142283E+09 | 69507741.14 | 0.221361E+09 | 94173722.15 |
October | 0.153606E+09 | 0.108176E+09 | 45429937.38 | 0.140301E+09 | 0.117523E+09 |
November | 0.103663E+09 | 73387760.52 | 30274928.23 | 80429578.71 | 0.103857E+09 |
December | 76493684.02 | 48527968.33 | 27965715.69 | 39324518.09 | 0.142160E+09 |
Annual Sum or Average | 0.228423E+10 | 0.151107E+10 | 0.773161E+09 | 0.231179E+10 | 0.113441E+10 |
Minimum of Months | 76493684.02 | 48527968.33 | 27965715.69 | 39324518.09 | 61582250.64 |
Maximum of Months | 0.316352E+09 | 0.222441E+09 | 0.119837E+09 | 0.361056E+09 | 0.142160E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91406748.52 | 63267129.23 | 28139619.29 | 58124168.86 | 0.121767E+09 |
February | 0.125771E+09 | 95826578.75 | 29944849.16 | 0.107478E+09 | 0.110292E+09 |
March | 0.185626E+09 | 0.129954E+09 | 55671958.13 | 0.186795E+09 | 88888625.41 |
April | 0.196061E+09 | 0.115364E+09 | 80696581.29 | 0.204424E+09 | 69901929.53 |
May | 0.259777E+09 | 0.139940E+09 | 0.119837E+09 | 0.288583E+09 | 61582250.64 |
June | 0.316352E+09 | 0.222441E+09 | 93911177.73 | 0.361056E+09 | 69408520.55 |
July | 0.282585E+09 | 0.169970E+09 | 0.112615E+09 | 0.312531E+09 | 74218710.93 |
August | 0.281099E+09 | 0.201932E+09 | 79166509.83 | 0.311382E+09 | 80634364.02 |
September | 0.211791E+09 | 0.142283E+09 | 69507741.14 | 0.221361E+09 | 94173722.15 |
October | 0.153606E+09 | 0.108176E+09 | 45429937.38 | 0.140301E+09 | 0.117523E+09 |
November | 0.103663E+09 | 73387760.52 | 30274928.23 | 80429578.71 | 0.103857E+09 |
December | 76493684.02 | 48527968.33 | 27965715.69 | 39324518.09 | 0.142160E+09 |
Annual Sum or Average | 0.228423E+10 | 0.151107E+10 | 0.773161E+09 | 0.231179E+10 | 0.113441E+10 |
Minimum of Months | 76493684.02 | 48527968.33 | 27965715.69 | 39324518.09 | 61582250.64 |
Maximum of Months | 0.316352E+09 | 0.222441E+09 | 0.119837E+09 | 0.361056E+09 | 0.142160E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91406748.52 | 63267129.23 | 28139619.29 | 58124168.86 | 0.121767E+09 |
February | 0.125771E+09 | 95826578.75 | 29944849.16 | 0.107478E+09 | 0.110292E+09 |
March | 0.185626E+09 | 0.129954E+09 | 55671958.13 | 0.186795E+09 | 88888625.41 |
April | 0.196061E+09 | 0.115364E+09 | 80696581.29 | 0.204424E+09 | 69901929.53 |
May | 0.259777E+09 | 0.139940E+09 | 0.119837E+09 | 0.288583E+09 | 61582250.64 |
June | 0.316352E+09 | 0.222441E+09 | 93911177.73 | 0.361056E+09 | 69408520.55 |
July | 0.282585E+09 | 0.169970E+09 | 0.112615E+09 | 0.312531E+09 | 74218710.93 |
August | 0.281099E+09 | 0.201932E+09 | 79166509.83 | 0.311382E+09 | 80634364.02 |
September | 0.211791E+09 | 0.142283E+09 | 69507741.14 | 0.221361E+09 | 94173722.15 |
October | 0.153606E+09 | 0.108176E+09 | 45429937.38 | 0.140301E+09 | 0.117523E+09 |
November | 0.103663E+09 | 73387760.52 | 30274928.23 | 80429578.71 | 0.103857E+09 |
December | 76493684.02 | 48527968.33 | 27965715.69 | 39324518.09 | 0.142160E+09 |
Annual Sum or Average | 0.228423E+10 | 0.151107E+10 | 0.773161E+09 | 0.231179E+10 | 0.113441E+10 |
Minimum of Months | 76493684.02 | 48527968.33 | 27965715.69 | 39324518.09 | 61582250.64 |
Maximum of Months | 0.316352E+09 | 0.222441E+09 | 0.119837E+09 | 0.361056E+09 | 0.142160E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91406748.52 | 63267129.23 | 28139619.29 | 58124168.86 | 0.121767E+09 |
February | 0.125771E+09 | 95826578.75 | 29944849.16 | 0.107478E+09 | 0.110292E+09 |
March | 0.185626E+09 | 0.129954E+09 | 55671958.13 | 0.186795E+09 | 88888625.41 |
April | 0.196061E+09 | 0.115364E+09 | 80696581.29 | 0.204424E+09 | 69901929.53 |
May | 0.259777E+09 | 0.139940E+09 | 0.119837E+09 | 0.288583E+09 | 61582250.64 |
June | 0.316352E+09 | 0.222441E+09 | 93911177.73 | 0.361056E+09 | 69408520.55 |
July | 0.282585E+09 | 0.169970E+09 | 0.112615E+09 | 0.312531E+09 | 74218710.93 |
August | 0.281099E+09 | 0.201932E+09 | 79166509.83 | 0.311382E+09 | 80634364.02 |
September | 0.211791E+09 | 0.142283E+09 | 69507741.14 | 0.221361E+09 | 94173722.15 |
October | 0.153606E+09 | 0.108176E+09 | 45429937.38 | 0.140301E+09 | 0.117523E+09 |
November | 0.103663E+09 | 73387760.52 | 30274928.23 | 80429578.71 | 0.103857E+09 |
December | 76493684.02 | 48527968.33 | 27965715.69 | 39324518.09 | 0.142160E+09 |
Annual Sum or Average | 0.228423E+10 | 0.151107E+10 | 0.773161E+09 | 0.231179E+10 | 0.113441E+10 |
Minimum of Months | 76493684.02 | 48527968.33 | 27965715.69 | 39324518.09 | 61582250.64 |
Maximum of Months | 0.316352E+09 | 0.222441E+09 | 0.119837E+09 | 0.361056E+09 | 0.142160E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91406748.52 | 63267129.23 | 28139619.29 | 58124168.86 | 0.121767E+09 |
February | 0.125771E+09 | 95826578.75 | 29944849.16 | 0.107478E+09 | 0.110292E+09 |
March | 0.185626E+09 | 0.129954E+09 | 55671958.13 | 0.186795E+09 | 88888625.41 |
April | 0.196061E+09 | 0.115364E+09 | 80696581.29 | 0.204424E+09 | 69901929.53 |
May | 0.259777E+09 | 0.139940E+09 | 0.119837E+09 | 0.288583E+09 | 61582250.64 |
June | 0.316352E+09 | 0.222441E+09 | 93911177.73 | 0.361056E+09 | 69408520.55 |
July | 0.282585E+09 | 0.169970E+09 | 0.112615E+09 | 0.312531E+09 | 74218710.93 |
August | 0.281099E+09 | 0.201932E+09 | 79166509.83 | 0.311382E+09 | 80634364.02 |
September | 0.211791E+09 | 0.142283E+09 | 69507741.14 | 0.221361E+09 | 94173722.15 |
October | 0.153606E+09 | 0.108176E+09 | 45429937.38 | 0.140301E+09 | 0.117523E+09 |
November | 0.103663E+09 | 73387760.52 | 30274928.23 | 80429578.71 | 0.103857E+09 |
December | 76493684.02 | 48527968.33 | 27965715.69 | 39324518.09 | 0.142160E+09 |
Annual Sum or Average | 0.228423E+10 | 0.151107E+10 | 0.773161E+09 | 0.231179E+10 | 0.113441E+10 |
Minimum of Months | 76493684.02 | 48527968.33 | 27965715.69 | 39324518.09 | 61582250.64 |
Maximum of Months | 0.316352E+09 | 0.222441E+09 | 0.119837E+09 | 0.361056E+09 | 0.142160E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91406748.52 | 63267129.23 | 28139619.29 | 58124168.86 | 0.121767E+09 |
February | 0.125771E+09 | 95826578.75 | 29944849.16 | 0.107478E+09 | 0.110292E+09 |
March | 0.185626E+09 | 0.129954E+09 | 55671958.13 | 0.186795E+09 | 88888625.41 |
April | 0.196061E+09 | 0.115364E+09 | 80696581.29 | 0.204424E+09 | 69901929.53 |
May | 0.259777E+09 | 0.139940E+09 | 0.119837E+09 | 0.288583E+09 | 61582250.64 |
June | 0.316352E+09 | 0.222441E+09 | 93911177.73 | 0.361056E+09 | 69408520.55 |
July | 0.282585E+09 | 0.169970E+09 | 0.112615E+09 | 0.312531E+09 | 74218710.93 |
August | 0.281099E+09 | 0.201932E+09 | 79166509.83 | 0.311382E+09 | 80634364.02 |
September | 0.211791E+09 | 0.142283E+09 | 69507741.14 | 0.221361E+09 | 94173722.15 |
October | 0.153606E+09 | 0.108176E+09 | 45429937.38 | 0.140301E+09 | 0.117523E+09 |
November | 0.103663E+09 | 73387760.52 | 30274928.23 | 80429578.71 | 0.103857E+09 |
December | 76493684.02 | 48527968.33 | 27965715.69 | 39324518.09 | 0.142160E+09 |
Annual Sum or Average | 0.228423E+10 | 0.151107E+10 | 0.773161E+09 | 0.231179E+10 | 0.113441E+10 |
Minimum of Months | 76493684.02 | 48527968.33 | 27965715.69 | 39324518.09 | 61582250.64 |
Maximum of Months | 0.316352E+09 | 0.222441E+09 | 0.119837E+09 | 0.361056E+09 | 0.142160E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91406748.52 | 63267129.23 | 28139619.29 | 58124168.86 | 0.121767E+09 |
February | 0.125771E+09 | 95826578.75 | 29944849.16 | 0.107478E+09 | 0.110292E+09 |
March | 0.185626E+09 | 0.129954E+09 | 55671958.13 | 0.186795E+09 | 88888625.41 |
April | 0.196061E+09 | 0.115364E+09 | 80696581.29 | 0.204424E+09 | 69901929.53 |
May | 0.259777E+09 | 0.139940E+09 | 0.119837E+09 | 0.288583E+09 | 61582250.64 |
June | 0.316352E+09 | 0.222441E+09 | 93911177.73 | 0.361056E+09 | 69408520.55 |
July | 0.282585E+09 | 0.169970E+09 | 0.112615E+09 | 0.312531E+09 | 74218710.93 |
August | 0.281099E+09 | 0.201932E+09 | 79166509.83 | 0.311382E+09 | 80634364.02 |
September | 0.211791E+09 | 0.142283E+09 | 69507741.14 | 0.221361E+09 | 94173722.15 |
October | 0.153606E+09 | 0.108176E+09 | 45429937.38 | 0.140301E+09 | 0.117523E+09 |
November | 0.103663E+09 | 73387760.52 | 30274928.23 | 80429578.71 | 0.103857E+09 |
December | 76493684.02 | 48527968.33 | 27965715.69 | 39324518.09 | 0.142160E+09 |
Annual Sum or Average | 0.228423E+10 | 0.151107E+10 | 0.773161E+09 | 0.231179E+10 | 0.113441E+10 |
Minimum of Months | 76493684.02 | 48527968.33 | 27965715.69 | 39324518.09 | 61582250.64 |
Maximum of Months | 0.316352E+09 | 0.222441E+09 | 0.119837E+09 | 0.361056E+09 | 0.142160E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91406748.52 | 63267129.23 | 28139619.29 | 58124168.86 | 0.121767E+09 |
February | 0.125771E+09 | 95826578.75 | 29944849.16 | 0.107478E+09 | 0.110292E+09 |
March | 0.185626E+09 | 0.129954E+09 | 55671958.13 | 0.186795E+09 | 88888625.41 |
April | 0.196061E+09 | 0.115364E+09 | 80696581.29 | 0.204424E+09 | 69901929.53 |
May | 0.259777E+09 | 0.139940E+09 | 0.119837E+09 | 0.288583E+09 | 61582250.64 |
June | 0.316352E+09 | 0.222441E+09 | 93911177.73 | 0.361056E+09 | 69408520.55 |
July | 0.282585E+09 | 0.169970E+09 | 0.112615E+09 | 0.312531E+09 | 74218710.93 |
August | 0.281099E+09 | 0.201932E+09 | 79166509.83 | 0.311382E+09 | 80634364.02 |
September | 0.211791E+09 | 0.142283E+09 | 69507741.14 | 0.221361E+09 | 94173722.15 |
October | 0.153606E+09 | 0.108176E+09 | 45429937.38 | 0.140301E+09 | 0.117523E+09 |
November | 0.103663E+09 | 73387760.52 | 30274928.23 | 80429578.71 | 0.103857E+09 |
December | 76493684.02 | 48527968.33 | 27965715.69 | 39324518.09 | 0.142160E+09 |
Annual Sum or Average | 0.228423E+10 | 0.151107E+10 | 0.773161E+09 | 0.231179E+10 | 0.113441E+10 |
Minimum of Months | 76493684.02 | 48527968.33 | 27965715.69 | 39324518.09 | 61582250.64 |
Maximum of Months | 0.316352E+09 | 0.222441E+09 | 0.119837E+09 | 0.361056E+09 | 0.142160E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91406748.52 | 63267129.23 | 28139619.29 | 58124168.86 | 0.121767E+09 |
February | 0.125771E+09 | 95826578.75 | 29944849.16 | 0.107478E+09 | 0.110292E+09 |
March | 0.185626E+09 | 0.129954E+09 | 55671958.13 | 0.186795E+09 | 88888625.41 |
April | 0.196061E+09 | 0.115364E+09 | 80696581.29 | 0.204424E+09 | 69901929.53 |
May | 0.259777E+09 | 0.139940E+09 | 0.119837E+09 | 0.288583E+09 | 61582250.64 |
June | 0.316352E+09 | 0.222441E+09 | 93911177.73 | 0.361056E+09 | 69408520.55 |
July | 0.282585E+09 | 0.169970E+09 | 0.112615E+09 | 0.312531E+09 | 74218710.93 |
August | 0.281099E+09 | 0.201932E+09 | 79166509.83 | 0.311382E+09 | 80634364.02 |
September | 0.211791E+09 | 0.142283E+09 | 69507741.14 | 0.221361E+09 | 94173722.15 |
October | 0.153606E+09 | 0.108176E+09 | 45429937.38 | 0.140301E+09 | 0.117523E+09 |
November | 0.103663E+09 | 73387760.52 | 30274928.23 | 80429578.71 | 0.103857E+09 |
December | 76493684.02 | 48527968.33 | 27965715.69 | 39324518.09 | 0.142160E+09 |
Annual Sum or Average | 0.228423E+10 | 0.151107E+10 | 0.773161E+09 | 0.231179E+10 | 0.113441E+10 |
Minimum of Months | 76493684.02 | 48527968.33 | 27965715.69 | 39324518.09 | 61582250.64 |
Maximum of Months | 0.316352E+09 | 0.222441E+09 | 0.119837E+09 | 0.361056E+09 | 0.142160E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 177.20 | 530.81 | 275.45 | 148.45 | 127.00 | 0.00 | 0.00 |
February | 221.66 | 543.05 | 336.15 | 176.81 | 159.34 | 0.00 | 0.00 |
March | 317.84 | 406.94 | 401.97 | 183.16 | 218.81 | 0.00 | 0.00 |
April | 302.24 | 351.82 | 399.14 | 131.67 | 267.47 | 0.00 | 0.00 |
May | 467.83 | 221.76 | 501.70 | 138.29 | 363.41 | 0.00 | 0.00 |
June | 682.85 | 162.42 | 598.54 | 239.12 | 359.43 | 0.00 | 0.00 |
July | 575.37 | 157.15 | 504.76 | 147.07 | 357.69 | 0.00 | 0.00 |
August | 560.17 | 183.18 | 497.11 | 199.24 | 297.88 | 0.00 | 0.00 |
September | 459.23 | 258.05 | 436.35 | 169.59 | 266.75 | 0.00 | 0.00 |
October | 292.05 | 446.53 | 354.74 | 168.24 | 186.50 | 0.00 | 0.00 |
November | 198.09 | 494.08 | 287.80 | 147.01 | 140.79 | 0.00 | 0.00 |
December | 128.84 | 625.99 | 234.43 | 115.76 | 118.66 | 0.00 | 0.00 |
Annual Sum or Average | 365.96 | 364.22 | 402.58 | 163.51 | 239.08 | 0.00 | 0.00 |
Minimum of Months | 128.84 | 157.15 | 234.43 | 115.76 | 118.66 | 0.00 | 0.00 |
Maximum of Months | 682.85 | 625.99 | 598.54 | 239.12 | 363.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 217.01 | 454.63 | 341.27 | 236.21 | 105.06 | 0.00 | 0.00 |
February | 444.27 | 455.90 | 519.89 | 396.11 | 123.78 | 0.00 | 0.00 |
March | 697.41 | 331.87 | 693.05 | 485.19 | 207.86 | 0.00 | 0.00 |
April | 788.67 | 269.68 | 756.41 | 445.08 | 311.33 | 0.00 | 0.00 |
May | 1077.44 | 229.92 | 969.90 | 522.48 | 447.42 | 0.00 | 0.00 |
June | 1392.96 | 267.78 | 1220.49 | 858.18 | 362.31 | 0.00 | 0.00 |
July | 1166.86 | 277.10 | 1055.05 | 634.60 | 420.46 | 0.00 | 0.00 |
August | 1162.57 | 301.05 | 1049.50 | 753.93 | 295.57 | 0.00 | 0.00 |
September | 854.02 | 363.32 | 817.09 | 548.93 | 268.16 | 0.00 | 0.00 |
October | 523.82 | 438.78 | 573.50 | 403.88 | 169.62 | 0.00 | 0.00 |
November | 310.30 | 400.68 | 399.93 | 283.13 | 116.80 | 0.00 | 0.00 |
December | 146.82 | 530.76 | 285.59 | 181.18 | 104.41 | 0.00 | 0.00 |
Annual Sum or Average | 733.06 | 359.72 | 724.32 | 479.16 | 245.17 | 0.00 | 0.00 |
Minimum of Months | 146.82 | 229.92 | 285.59 | 181.18 | 104.41 | 0.00 | 0.00 |
Maximum of Months | 1392.96 | 530.76 | 1220.49 | 858.18 | 447.42 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.474613E+09 | 0.142173E+10 | 0.737773E+09 | 0.397615E+09 | 0.340158E+09 | 0.00 | 0.00 |
February | 0.536240E+09 | 0.131375E+10 | 0.813210E+09 | 0.427741E+09 | 0.385469E+09 | 0.00 | 0.00 |
March | 0.851315E+09 | 0.108996E+10 | 0.107664E+10 | 0.490580E+09 | 0.586061E+09 | 0.00 | 0.00 |
April | 0.783396E+09 | 0.911930E+09 | 0.103456E+10 | 0.341285E+09 | 0.693273E+09 | 0.00 | 0.00 |
May | 0.125304E+10 | 0.593975E+09 | 0.134375E+10 | 0.370407E+09 | 0.973347E+09 | 0.00 | 0.00 |
June | 0.176994E+10 | 0.420992E+09 | 0.155142E+10 | 0.619793E+09 | 0.931631E+09 | 0.00 | 0.00 |
July | 0.154106E+10 | 0.420915E+09 | 0.135196E+10 | 0.393923E+09 | 0.958034E+09 | 0.00 | 0.00 |
August | 0.150037E+10 | 0.490635E+09 | 0.133146E+10 | 0.533631E+09 | 0.797830E+09 | 0.00 | 0.00 |
September | 0.119033E+10 | 0.668859E+09 | 0.113101E+10 | 0.439588E+09 | 0.691421E+09 | 0.00 | 0.00 |
October | 0.782218E+09 | 0.119599E+10 | 0.950147E+09 | 0.450613E+09 | 0.499533E+09 | 0.00 | 0.00 |
November | 0.513457E+09 | 0.128065E+10 | 0.745975E+09 | 0.381059E+09 | 0.364915E+09 | 0.00 | 0.00 |
December | 0.345072E+09 | 0.167664E+10 | 0.627893E+09 | 0.310064E+09 | 0.317829E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115410E+11 | 0.114860E+11 | 0.126958E+11 | 0.515630E+10 | 0.753950E+10 | 0.00 | 0.00 |
Minimum of Months | 0.345072E+09 | 0.420915E+09 | 0.627893E+09 | 0.310064E+09 | 0.317829E+09 | 0.00 | 0.00 |
Maximum of Months | 0.176994E+10 | 0.167664E+10 | 0.155142E+10 | 0.619793E+09 | 0.973347E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.581241E+09 | 0.121767E+10 | 0.914067E+09 | 0.632671E+09 | 0.281396E+09 | 0.00 | 0.00 |
February | 0.107478E+10 | 0.110292E+10 | 0.125771E+10 | 0.958266E+09 | 0.299448E+09 | 0.00 | 0.00 |
March | 0.186795E+10 | 0.888885E+09 | 0.185626E+10 | 0.129954E+10 | 0.556720E+09 | 0.00 | 0.00 |
April | 0.204424E+10 | 0.699019E+09 | 0.196061E+10 | 0.115364E+10 | 0.806966E+09 | 0.00 | 0.00 |
May | 0.288583E+10 | 0.615821E+09 | 0.259777E+10 | 0.139940E+10 | 0.119837E+10 | 0.00 | 0.00 |
June | 0.361056E+10 | 0.694083E+09 | 0.316352E+10 | 0.222441E+10 | 0.939112E+09 | 0.00 | 0.00 |
July | 0.312531E+10 | 0.742186E+09 | 0.282585E+10 | 0.169970E+10 | 0.112615E+10 | 0.00 | 0.00 |
August | 0.311382E+10 | 0.806343E+09 | 0.281099E+10 | 0.201932E+10 | 0.791665E+09 | 0.00 | 0.00 |
September | 0.221361E+10 | 0.941737E+09 | 0.211791E+10 | 0.142283E+10 | 0.695077E+09 | 0.00 | 0.00 |
October | 0.140301E+10 | 0.117523E+10 | 0.153606E+10 | 0.108176E+10 | 0.454299E+09 | 0.00 | 0.00 |
November | 0.804295E+09 | 0.103857E+10 | 0.103663E+10 | 0.733878E+09 | 0.302749E+09 | 0.00 | 0.00 |
December | 0.393240E+09 | 0.142160E+10 | 0.764937E+09 | 0.485280E+09 | 0.279657E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.231179E+11 | 0.113441E+11 | 0.228423E+11 | 0.151107E+11 | 0.773161E+10 | 0.00 | 0.00 |
Minimum of Months | 0.393240E+09 | 0.615821E+09 | 0.764937E+09 | 0.485280E+09 | 0.279657E+09 | 0.00 | 0.00 |
Maximum of Months | 0.361056E+10 | 0.142160E+10 | 0.316352E+10 | 0.222441E+10 | 0.119837E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.40 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.31 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.51 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.44 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.23 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.78 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.33 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.32 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.39 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.23 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.93 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.71 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.86 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.46 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.89 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.59 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.86 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.32 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.01 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.69 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.06 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.90 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.93 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.32 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.3 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.44 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.29 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.21 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.8 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.21 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.52 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.95 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 7.98 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.48 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.84 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.63 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.73 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.79 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.51 | 196.33 | 4.00 |
September | 14.93 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.69 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.31 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.90 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.52 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.73 | 29.40 | 16.00 | 9.80 | 20.51 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.48 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.72 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.63 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.91 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.89 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.39 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.05 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.05 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.63 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.988386E+09 | -901550700.6 | 0.00 | 0.00 | 744.00 | 0.00 | -86834824.9 | 58.99 | 0.00 | 0.00 |
February | 0.917021E+09 | -838399061.5 | 0.00 | 0.00 | 672.00 | 0.00 | -78622016.3 | 58.99 | 0.00 | 0.00 |
March | 0.105062E+10 | -965493835.4 | 0.00 | 0.00 | 744.00 | 0.00 | -85121687.4 | 59.00 | 0.00 | 0.00 |
April | 0.943790E+09 | -861665965.1 | 0.00 | 0.00 | 720.00 | 0.00 | -82123721.1 | 58.99 | 0.00 | 0.00 |
May | 0.925337E+09 | -846619705.1 | 0.00 | 0.00 | 744.00 | 0.00 | -78716947.9 | 58.99 | 0.00 | 0.00 |
June | 0.863379E+09 | -793580768.8 | 0.00 | 0.00 | 720.00 | 0.00 | -69798040.9 | 59.00 | 0.00 | 0.00 |
July | 0.803599E+09 | -732131840.8 | 0.00 | 0.00 | 744.00 | 0.00 | -71467551.7 | 58.99 | 0.00 | 0.00 |
August | 0.845330E+09 | -773651725.8 | 0.00 | 0.00 | 744.00 | 0.00 | -71678672.1 | 58.99 | 0.00 | 0.00 |
September | 0.803955E+09 | -733153657.9 | 0.00 | 0.00 | 720.00 | 0.00 | -70801638.5 | 58.99 | 0.00 | 0.00 |
October | 0.852132E+09 | -771153082.7 | 0.00 | 0.00 | 744.00 | 0.00 | -80978824.2 | 58.99 | 0.00 | 0.00 |
November | 0.868904E+09 | -786522883.5 | 0.00 | 0.00 | 720.00 | 0.00 | -82381559.8 | 58.99 | 0.00 | 0.00 |
December | 0.952897E+09 | -866022178.6 | 0.00 | 0.00 | 744.00 | 0.00 | -86874913.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.108153E+11 | -.986995E+10 | 8760.00 | -945400397.7 | 58.99 | |||||
Minimum of Months | 0.803599E+09 | -965493835.4 | 0.00 | 0.00 | 672.00 | 0.00 | -86874913.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.105062E+10 | -732131840.8 | 0.00 | 0.00 | 744.00 | 0.00 | -69798040.9 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 245.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 415.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 421.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 430.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 394.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 354.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 262.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 257.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 251.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3902.00 | ||||||||||
Minimum of Months | 245.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 430.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.527667E+10 | 26734.84 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.562146E+10 | 26734.84 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.430591E+10 | 26734.84 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.286439E+10 | 26734.84 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.524818E+09 | 26734.84 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 899325.71 | 1696.87 | 28-JUN-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 956342.29 | 3187.81 | 14-AUG-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 36799648.02 | 7515.28 | 21-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.198112E+10 | 26734.84 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.365194E+10 | 26734.84 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.652937E+10 | 26734.84 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307943E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.652937E+10 | 26734.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.208033E+11 | 79342.45 | 01-JAN-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.257091E+11 | 79342.45 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183095E+11 | 79342.45 | 01-MAR-03:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129903E+11 | 79342.45 | 01-APR-19:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108422E+10 | 79342.45 | 02-MAY-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.755125E+10 | 79342.45 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144062E+11 | 79342.45 | 01-NOV-00:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.360727E+11 | 79342.45 | 01-DEC-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136927E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.360727E+11 | 79342.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.320785E+11 | 68209.28 | 05-JAN-19:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.504947E+11 | 103781.68 | 12-FEB-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.254982E+11 | 117187.49 | 19-MAR-06:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138462E+11 | 65753.44 | 16-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.696725E+10 | 61639.83 | 31-OCT-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182967E+11 | 99684.09 | 30-NOV-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.800950E+11 | 117187.49 | 21-DEC-17:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227277E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.800950E+11 | 117187.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 46223365.52 | 46223365.52 | 2371.08 | 13-MAR-16:00 | 2371.08 | 0.00 |
April | 0.00 | 0.00 | 769145.88 | 769145.88 | 400.14 | 20-APR-13:00 | 400.14 | 0.00 |
May | 0.00 | 0.00 | 0.982587E+09 | 0.980958E+09 | 6227.61 | 31-MAY-16:00 | 6227.61 | 0.00 |
June | 0.00 | 0.00 | 0.659446E+10 | 0.633225E+10 | 20065.05 | 21-JUN-05:50 | 11352.88 | 0.00 |
July | 0.00 | 0.00 | 0.699201E+10 | 0.655735E+10 | 20501.92 | 28-JUL-05:01 | 11089.20 | 0.00 |
August | 0.00 | 0.00 | 0.677164E+10 | 0.649025E+10 | 20584.37 | 04-AUG-05:01 | 10808.51 | 0.00 |
September | 0.00 | 0.00 | 0.427805E+10 | 0.424025E+10 | 18179.82 | 13-SEP-05:01 | 17669.64 | 0.00 |
October | 0.00 | 0.00 | 0.293192E+09 | 0.293192E+09 | 6091.53 | 11-OCT-15:10 | 6091.53 | 0.00 |
November | 0.00 | 0.00 | 6317626.55 | 6317626.55 | 1129.21 | 07-NOV-15:00 | 1129.21 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.259652E+11 | 0.249476E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.699201E+10 | 0.655735E+10 | 20584.37 | 17669.64 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.161063E+09 | 0.161063E+09 | 5941.32 | 17-MAY-13:40 | 5941.32 | 0.00 |
June | 0.00 | 0.00 | 0.135341E+11 | 0.132050E+11 | 57622.98 | 18-JUN-09:41 | 38179.16 | 0.00 |
July | 0.00 | 0.00 | 0.145011E+11 | 0.140947E+11 | 59143.48 | 30-JUL-11:10 | 36136.52 | 0.00 |
August | 0.00 | 0.00 | 0.133530E+11 | 0.131083E+11 | 54468.45 | 03-AUG-17:41 | 42124.62 | 0.00 |
September | 0.00 | 0.00 | 0.550919E+10 | 0.549305E+10 | 50985.04 | 03-SEP-14:01 | 49122.05 | 0.00 |
October | 0.00 | 0.00 | 25428798.53 | 25428798.53 | 4177.39 | 11-OCT-14:00 | 4177.39 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.470839E+11 | 0.460875E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.145011E+11 | 0.140947E+11 | 59143.48 | 49122.05 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.388753E+09 | 0.04 | 322.92 | 01-JAN-00:03 | 0.09 |
February | 0.451830E+09 | 0.05 | 322.92 | 01-FEB-00:03 | 0.09 |
March | 0.333177E+09 | 0.04 | 322.92 | 01-MAR-01:10 | 0.09 |
April | 0.167982E+09 | 0.02 | 322.92 | 01-APR-19:05 | 0.09 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 71301751.66 | 0.01 | 322.92 | 29-OCT-08:70 | 0.09 |
November | 0.203591E+09 | 0.02 | 322.92 | 01-NOV-00:10 | 0.09 |
December | 0.570885E+09 | 0.06 | 322.92 | 01-DEC-00:03 | 0.09 |
Annual Sum or Average | 0.218752E+10 | 0.02 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.570885E+09 | 0.06 | 322.92 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140158E+10 | 0.55 | 1355.67 | 13-JAN-14:10 | 1.16 |
February | 0.130313E+10 | 0.61 | 1355.67 | 03-FEB-16:20 | 1.15 |
March | 0.150257E+10 | 0.56 | 1355.67 | 03-MAR-09:10 | 1.16 |
April | 0.138367E+10 | 0.52 | 1355.67 | 11-APR-11:00 | 1.15 |
May | 0.140436E+10 | 0.46 | 1355.67 | 03-MAY-08:30 | 1.15 |
June | 0.141601E+10 | 0.47 | 1355.67 | 12-JUN-09:10 | 1.15 |
July | 0.137433E+10 | 0.44 | 1355.67 | 15-JUL-06:20 | 1.14 |
August | 0.148175E+10 | 0.47 | 1355.67 | 05-AUG-09:15 | 1.14 |
September | 0.136066E+10 | 0.45 | 1355.67 | 01-SEP-08:30 | 1.14 |
October | 0.136015E+10 | 0.46 | 1355.67 | 10-OCT-08:40 | 1.15 |
November | 0.132246E+10 | 0.47 | 1355.67 | 10-NOV-14:10 | 1.15 |
December | 0.142519E+10 | 0.61 | 1355.67 | 01-DEC-09:25 | 1.15 |
Annual Sum or Average | 0.167359E+11 | 0.50 | |||
Minimum of Months | 0.130313E+10 | 0.44 | 1355.67 | 1.14 | |
Maximum of Months | 0.150257E+10 | 0.61 | 1355.67 | 1.16 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.378692E+10 | 0.89 | 3086.68 | 02-JAN-07:10 | 1.11 |
February | 0.370056E+10 | 0.91 | 3086.68 | 01-FEB-11:30 | 1.11 |
March | 0.393460E+10 | 0.80 | 3086.68 | 02-MAR-09:20 | 1.11 |
April | 0.354504E+10 | 0.76 | 3086.68 | 01-APR-11:40 | 1.11 |
May | 0.322241E+10 | 0.46 | 3086.68 | 16-MAY-14:40 | 1.10 |
June | 0.332183E+10 | 0.50 | 3086.68 | 01-JUN-16:00 | 1.10 |
July | 0.323846E+10 | 0.48 | 3086.68 | 03-JUL-14:12 | 1.10 |
August | 0.340878E+10 | 0.48 | 3086.68 | 05-AUG-09:20 | 1.09 |
September | 0.310179E+10 | 0.44 | 3086.68 | 07-SEP-10:10 | 1.10 |
October | 0.329207E+10 | 0.56 | 3086.68 | 11-OCT-13:00 | 1.11 |
November | 0.342410E+10 | 0.77 | 3086.68 | 01-NOV-11:20 | 1.11 |
December | 0.419249E+10 | 0.93 | 3086.68 | 04-DEC-08:70 | 1.11 |
Annual Sum or Average | 0.421691E+11 | 0.66 | |||
Minimum of Months | 0.310179E+10 | 0.44 | 3086.68 | 1.09 | |
Maximum of Months | 0.419249E+10 | 0.93 | 3086.68 | 1.11 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.04 | 0.07 |
February | 2.41 | 0.06 |
March | 2.04 | 0.26 |
April | 1.19 | 0.47 |
May | 1.51 | 2.92 |
June | 3.60 | 0.22 |
July | 3.16 | 0.21 |
August | 3.09 | 0.16 |
September | 2.07 | 0.52 |
October | 1.56 | 1.37 |
November | 1.99 | 0.20 |
December | 1.86 | 0.07 |
Annual Sum or Average | 27.53 | 0.42 |
Minimum of Months | 1.19 | 0.06 |
Maximum of Months | 3.60 | 2.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.04 | 0.00 |
April | 0.08 | 0.00 |
May | 0.08 | 0.00 |
June | 1.76 | 0.00 |
July | 0.97 | 0.00 |
August | 2.13 | 0.00 |
September | 1.12 | 0.00 |
October | 0.14 | 0.00 |
November | 0.00 | 0.00 |
December | 0.08 | 0.00 |
Annual Sum or Average | 6.42 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.13 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 1.14 | 0.00 |
July | 1.76 | 0.00 |
August | 0.72 | 0.00 |
September | 0.14 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 3.76 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.76 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.140158E+10 | 0.762283E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.130313E+10 | 0.813412E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.151523E+10 | 0.626619E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.138388E+10 | 0.417193E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.167586E+10 | 0.768361E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.330926E+10 | 1385443.63 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.335199E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.340332E+10 | 1451030.37 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.254566E+10 | 55306757.92 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.143988E+10 | 0.286470E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.132420E+10 | 0.527668E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.142519E+10 | 0.933204E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.240792E+11 | 0.444950E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.130313E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.340332E+10 | 0.933204E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.378692E+10 | 0.302429E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.370056E+10 | 0.369992E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.393460E+10 | 0.263572E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.354504E+10 | 0.188416E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.327314E+10 | 0.158923E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.762478E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.780496E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.757263E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.480224E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.329990E+10 | 0.109869E+11 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.342410E+10 | 0.209967E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.419249E+10 | 0.510533E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.569614E+11 | 0.197067E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.327314E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.780496E+10 | 0.510533E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140158E+10 | 0.00 | 0.527667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130313E+10 | 0.00 | 0.562146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150257E+10 | 46223365.52 | 0.430591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138367E+10 | 769145.88 | 0.286439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140436E+10 | 0.982587E+09 | 0.524818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141601E+10 | 0.659446E+10 | 899325.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137433E+10 | 0.699201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148175E+10 | 0.677164E+10 | 956342.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136066E+10 | 0.427805E+10 | 36799648.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136015E+10 | 0.293192E+09 | 0.198112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132246E+10 | 6317626.55 | 0.365194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142519E+10 | 0.00 | 0.652937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167359E+11 | 0.259652E+11 | 0.307943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150257E+10 | 0.699201E+10 | 0.652937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.378692E+10 | 0.00 | 0.208033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.370056E+10 | 0.00 | 0.257091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.393460E+10 | 0.00 | 0.183095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.354504E+10 | 0.00 | 0.129903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.322241E+10 | 0.161063E+09 | 0.108422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.332183E+10 | 0.135341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.323846E+10 | 0.145011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.340878E+10 | 0.133530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.310179E+10 | 0.550919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.329207E+10 | 25428798.53 | 0.755125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.342410E+10 | 0.00 | 0.144062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.419249E+10 | 0.00 | 0.360727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421691E+11 | 0.470839E+11 | 0.136927E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.310179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.419249E+10 | 0.145011E+11 | 0.360727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.140158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.813412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150257E+10 | 0.00 | 0.00 | 0.00 | 12657845.40 | 0.00 | 0.626619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138367E+10 | 0.00 | 0.00 | 0.00 | 213641.63 | 0.00 | 0.417193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140436E+10 | 0.00 | 0.00 | 0.00 | 0.271504E+09 | 0.00 | 0.768361E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141601E+10 | 0.00 | 0.00 | 0.00 | 0.189325E+10 | 0.00 | 1385443.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137433E+10 | 0.00 | 0.00 | 0.00 | 0.197766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148175E+10 | 0.00 | 0.00 | 0.00 | 0.192157E+10 | 0.00 | 1451030.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136066E+10 | 0.00 | 0.00 | 0.00 | 0.118501E+10 | 0.00 | 55306757.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136015E+10 | 0.00 | 0.00 | 0.00 | 79733874.11 | 0.00 | 0.286470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132246E+10 | 0.00 | 0.00 | 0.00 | 1745104.22 | 0.00 | 0.527668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.933204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167359E+11 | 0.00 | 0.00 | 0.00 | 0.734334E+10 | 0.00 | 0.444950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.130313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150257E+10 | 0.00 | 0.00 | 0.00 | 0.197766E+10 | 0.00 | 0.933204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.378692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.370056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.393460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.354504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.322241E+10 | 0.00 | 0.00 | 0.00 | 50734325.57 | 0.00 | 0.158923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.332183E+10 | 0.00 | 0.00 | 0.00 | 0.430295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.323846E+10 | 0.00 | 0.00 | 0.00 | 0.456650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.340878E+10 | 0.00 | 0.00 | 0.00 | 0.416385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.310179E+10 | 0.00 | 0.00 | 0.00 | 0.170045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.329207E+10 | 0.00 | 0.00 | 0.00 | 7835849.13 | 0.00 | 0.109869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.342410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.419249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421691E+11 | 0.00 | 0.00 | 0.00 | 0.147923E+11 | 0.00 | 0.197067E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.310179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.419249E+10 | 0.00 | 0.00 | 0.00 | 0.456650E+10 | 0.00 | 0.510533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.198822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169671E+10 | 0.00 | 0.00 | 0.15 |
February | 0.101043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173852E+10 | 0.00 | 0.00 | 0.15 |
March | 0.312045E+09 | 0.00 | 0.00 | 127719.53 | 0.00 | 0.134859E+10 | 0.152747E+09 | 0.00 | 0.21 |
April | 0.402493E+09 | 0.00 | 0.00 | 43092.09 | 0.00 | 0.951497E+09 | 0.108677E+09 | 0.00 | 0.18 |
May | 0.317405E+09 | 17043503.20 | 0.00 | 1477275.76 | 0.00 | 0.116660E+09 | 0.111056E+10 | 0.00 | 0.42 |
June | 10551935.40 | 0.364456E+09 | 0.00 | 4319666.03 | 0.00 | 0.00 | 0.954342E+09 | 0.00 | 0.51 |
July | 8431470.08 | 0.425040E+09 | 0.00 | 4966681.60 | 66944.40 | 0.00 | 0.686274E+09 | 0.00 | 0.47 |
August | 21159205.23 | 0.335001E+09 | 0.00 | 6198805.03 | 0.00 | 0.00 | 0.137160E+10 | 0.00 | 0.53 |
September | 77276495.64 | 0.106264E+09 | 0.00 | 4877035.10 | 0.00 | 7752229.20 | 0.150101E+10 | 0.00 | 0.59 |
October | 0.555182E+09 | 1662152.31 | 0.00 | 827687.67 | 0.00 | 0.611091E+09 | 0.790936E+09 | 0.00 | 0.29 |
November | 0.386978E+09 | 0.00 | 0.00 | 73268.85 | 0.00 | 0.124274E+10 | 0.126261E+09 | 0.00 | 0.18 |
December | 0.159487E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197621E+10 | 0.00 | 0.00 | 0.15 |
Annual Sum or Average | 0.255087E+10 | 0.124947E+10 | 0.00 | 22911231.66 | 66944.40 | 0.968978E+10 | 0.680240E+10 | 0.00 | 0.32 |
Minimum of Months | 8431470.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
Maximum of Months | 0.555182E+09 | 0.425040E+09 | 0.00 | 6198805.03 | 66944.40 | 0.197621E+10 | 0.150101E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.196437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194177E+10 | 0.00 | 0.00 | 0.14 |
February | 0.179894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203500E+10 | 0.00 | 0.00 | 0.15 |
March | 0.180809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161398E+10 | 0.00 | 0.00 | 0.16 |
April | 0.191408E+10 | 0.00 | 0.00 | 0.00 | 10126.79 | 0.769423E+09 | 0.00 | 0.00 | 0.15 |
May | 0.186057E+10 | 11008511.08 | 0.00 | 54675.93 | 7349535.32 | 31399446.42 | 67937508.71 | 0.00 | 0.17 |
June | 0.283704E+09 | 0.648175E+09 | 0.00 | 6939618.62 | 0.00 | 0.00 | 0.196812E+10 | 0.00 | 0.43 |
July | 0.221257E+09 | 0.620656E+09 | 0.00 | 7639544.01 | 0.00 | 0.00 | 0.160092E+10 | 0.00 | 0.39 |
August | 0.353441E+09 | 0.556256E+09 | 0.00 | 10417068.87 | 498995.57 | 0.00 | 0.262680E+10 | 0.00 | 0.40 |
September | 0.814174E+09 | 0.162819E+09 | 0.00 | 4648513.21 | 2589487.62 | 0.00 | 0.186720E+10 | 0.00 | 0.35 |
October | 0.227181E+10 | 10609.88 | 0.00 | 7327.13 | 0.00 | 0.924573E+09 | 3540225.78 | 0.00 | 0.15 |
November | 0.201176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143694E+10 | 0.00 | 0.00 | 0.14 |
December | 0.135766E+10 | 0.00 | 0.00 | 0.00 | 2430196.69 | 0.314543E+10 | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.166599E+11 | 0.199893E+10 | 0.00 | 29706747.77 | 12878341.99 | 0.118985E+11 | 0.813450E+10 | 0.00 | 0.23 |
Minimum of Months | 0.221257E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.227181E+10 | 0.648175E+09 | 0.00 | 10417068.87 | 7349535.32 | 0.314543E+10 | 0.262680E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |