Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2020-06-03 19:11:56
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1211.76 | 250.62 | 250.62 |
Net Site Energy | 1211.76 | 250.62 | 250.62 |
Total Source Energy | 3140.23 | 649.46 | 649.46 |
Net Source Energy | 3140.23 | 649.46 | 649.46 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 334.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 39.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 73.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.23 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 876.95 | 334.81 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 334.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 39.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 6.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 67.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25.23 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 124.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 28.56 | 69.25 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 181.37 | 69.25 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 124.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 28.56 | 69.25 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 181.37 | 69.25 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 876.947 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 876.947 | 100.00 |
Total On-Site and Utility Electric Sources | 876.947 | 100.00 |
Total Electricity End Uses | 876.947 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 41.00 |
Time Setpoint Not Met During Occupied Cooling | 2.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1421.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.6337 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.5069 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.5069 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-14:39 | 16-JAN-17:49 | - | - | - | 19-JUN-11:30 |
Heating | 0.00 | 176462.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 19767.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7433.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1723.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 74225.73 | 176462.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 176462.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 19767.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 5128.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1723.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 362.93 | 0.00 | 0.00 | 0.00 |
Cooling | 125.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1507.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 390.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 231.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 79.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2777.29 | 362.93 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 75.06 | 0.00 | 0.00 | 0.00 |
Cooling | 25.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 47.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 574.40 | 75.06 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 75.06 | 0.00 | 0.00 | 0.00 |
Cooling | 25.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 47.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 574.40 | 75.06 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.33 |
ZONE2 FINE STORAGE DIRECT AIR | 3.30 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 2.67 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 2.67 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 91236.12 |
PSZ-OFFICE HEATING COIL | 28601.49 |
PSZ-FINE STORAGE HEATING COIL | 88473.51 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 91236.11 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.33 | 1.33 | 1.33 | 1.33 | 1.33 | 1.33 | 1.00 | 1.00 | 1.33 |
PSZ-FINE STORAGE | 3.30 | 3.30 | 3.30 | 3.30 | 3.30 | 3.30 | 1.00 | 1.000000 | 3.30 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.33 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 3.30 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.33 | 1.33 | 1.33 | 1.33 | 22061.55 | 28601.49 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 3.30 | 3.30 | 3.30 | 3.30 | 63015.77 | 88473.51 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.33 | 0.666370 | 1.33 | 22061.58 | 22061.55 | 11030.77 | 22061.55 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 3.30 | 1.65 | 3.30 | 54990.38 | 63015.77 | 31507.88 | 63015.77 | 0.749425 | 0.749420 | 0.749420 | 0.749420 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.33 | 1519.47 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 3.30 | 3608.62 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.634 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.707 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.507 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.507 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.507 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.066 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2518.900 | 10.634 | 503.780 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2518.900 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11853.648 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11853.648 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27263.390 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27263.390 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
5 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
6 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
13 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
14 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
15 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
16 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.14714251E-14 | -0.15793949E-15 | 0.73826229E-12 | 0.12610148E-15 |
85 | 3 | -0.53553847E-04 | 0.48261894E-06 | -0.37015163E-03 | 0.14168247E-12 |
86 | 2 | 1.1141045 | 0.10720623E-01 | 1.7048811 | -0.70963114E-04 |
87 | 1 | -16.929564 | 0.28051356 | -7.1749370 | 0.32672988 |
88 | 0 | 16.286769 | 0.18002168 | 5.9416824 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.52_SHGC_0.4 | 28 | 1 | VerySmooth | 2.956 | 0.395 | 0.315 | 0.401 |
2 | SKYLIGHT_U_0.6_SHGC_0.4 | 29 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 30 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.66926E-002 | 0.31435 | 0.46310 | 0.46310 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 9.92378E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11103.99802 | 13324.79763 | 1.11062 | 1.33274 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.65324E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10140.38719 | 12168.46463 | 0.34616 | 0.41539 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90000 | 2.34317E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 35242.31210 | 42290.77452 | 2.74753 | 3.29704 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10000 | 5.65324E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 38039.66539 | 45647.59847 | 1.09349 | 1.31219 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10000 | 5.65324E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 76030.09440 | 91236.11328 | 2.22556 | 2.67067 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | -7.90000 | 2.34317E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 16898.45 | 1.33274 | 1.33274 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 11301.03 | 0.41539 | 0.41539 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 51195.84 | 3.29704 | 3.29704 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 40185.13 | 1.31219 | 1.31219 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.33274 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.29704 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.67067 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 2.67067 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 91236.11748 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 91236.11328 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.33274 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.33274 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.33274 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.33274 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.33274 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.33274 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.29704 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.29704 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.29704 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 3.29704 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.29704 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 3.29704 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.33274 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 3.29704 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.33274 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.33274 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.33274 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.33274 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.33274 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.33274 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.66637 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.33274 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22061.57921 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22061.55000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11030.77500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 22061.55000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22061.55000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28601.48853 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.33274 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1519.46796 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28601.48853 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.29704 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.29704 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.29704 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.29704 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.29704 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.29704 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.64852 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.29704 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 54990.37968 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 63015.77000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 31507.88500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 63015.77000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74942 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74942 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74942 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74942 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 63015.77000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 88473.50650 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.29704 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3608.62479 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 88473.50650 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 21027.4 | 10.08 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 60456.0 | 13.20 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 17 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1160732588 | 0.1331727824 | Pass | Pass | 0.2183157742 | 1.6916307161 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.4328486116 | 0.5193532752 | Pass | Pass | 2.4154354550 | 22.1352875192 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 4.5853708168E-002 | 5.4964924247E-002 | Pass | Pass | 4.6457851231E-002 | 0.1304403504 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.369 | 0.389 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.52_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.956 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.52_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.956 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.52_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.956 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.52_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.956 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.164 | 0.395 | 0.401 | ||||||||||||
North Total or Average | 6.51 | 2.956 | 0.395 | 0.401 | ||||||||||||
Non-North Total or Average | 26.02 | 3.216 | 0.395 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.6337 | 236.88 | 2518.90 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.62 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.5069 | 1393.41 | 11853.65 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 135.00 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.5069 | 3204.84 | 27263.39 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 310.50 |
Interior Lighting Total | 8.6111 | 4835.13 | 41635.94 | 476.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.00 | AstronomicalClock | - | 83.71 | 83.71 | 123.46 | |
Exterior Lighting Total | 7857.00 | 123.46 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22061.55 | 17619.68 | 4441.87 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 63015.77 | 47225.28 | 15790.49 | 0.75 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 21027.4 | 10.08 | ||||
PSZ-FINE STORAGE COOLING COIL | 60456.0 | 13.20 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 91236.12 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28601.49 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 88473.51 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.67 | 248.13 | 92.91 | 1.00 | 3.42 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.33 | 1519.47 | 1140.11 | 1.00 | 1.30 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 3.30 | 3608.62 | 1094.51 | 1.00 | 1.23 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11104.00 | 13324.80 | 56.25 | 1.111 | 1.333 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00803 | 33.21 | 0.00565 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 35242.31 | 42290.77 | 30.35 | 2.748 | 3.297 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26.70 | 26.70 | 0.00781 | 35.10 | 0.00565 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00460 | 35.10 | 0.00565 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10140.39 | 12168.46 | 51.37 | 0.346 | 0.415 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00765 | -7.90 | 0.00234 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 38039.67 | 45647.60 | 32.76 | 1.093 | 1.312 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15.56 | 15.55 | 0.00620 | -7.90 | 0.00234 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 76030.09 | 91236.11 | 28.47 | 2.226 | 2.671 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 10.00 | 9.99 | 0.00930 | -7.90 | 0.00234 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.33 | 1.33 | 0.42 | 0.42 | 1.3327 | 1.3327 | 1.3327 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.30 | 3.30 | 1.31 | 1.31 | 3.2970 | 3.2970 | 3.2970 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 91236.117 | 91236.117 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 91236.12 | 91236.12 | 2.670669 | 4.54 | 4.54 | 0.00717953 | 43.33 | 24.55 | 0.01600000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 9.99 | 0.00930001 | 100.0000 | 91236.11 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 22061.550 | 0.000 | 1.332740 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 22061.55 | 22061.55 | 1.332740 | 24.74 | 14.05 | 0.00781676 | 12.00 | 9.53 | 0.00800000 | 33.21 | 0.00565324 | 15.09 | 9.0292 | 23.90 | 0.00803150 | 35.8008 | 11104.00 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28601.489 | 28601.489 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 28601.49 | 28601.49 | 1.332738 | 12.66 | 7.89 | 0.00611023 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 9.0292 | 21.10 | 0.00764659 | 40.4350 | 10140.39 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 63015.770 | 0.000 | 3.297040 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 63015.77 | 63015.77 | 3.297040 | 27.60 | 14.81 | 0.00757439 | 12.00 | 9.53 | 0.00800000 | 35.10 | 0.00565324 | 15.70 | 10.7347 | 26.70 | 0.00780542 | 29.4642 | 35242.31 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 88473.507 | 88473.507 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 88473.51 | 88473.51 | 3.297037 | 9.23 | 5.34 | 0.00516215 | 40.00 | 18.88 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 10.7347 | 15.55 | 0.00620332 | 46.5656 | 38039.67 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 91236.117 | 91236.117 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 0.9904 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 2.670669 | 2.64505418 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 91236.12 | 91236.12 | 1.0000 | 2.64505418 | 2.670669 | 4.54 | 4.54 | 0.00717953 | 22577.4 | 43.33 | 24.55 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 91236.12 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 9.99 | 0.00930001 | 9.99 | 0.00930001 | 100.0000 | 91236.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22061.550 | 0.000 | 1.332740 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3710 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 22061.55 | 22061.55 | 1.0000 | 1.31995755 | 1.332740 | 24.74 | 14.05 | 0.00781676 | 44768.9 | 12.00 | 9.53 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22061.55 | 33.21 | 0.00565324 | 15.09 | 0.12033533 | 9.0292 | 23.90 | 0.00803150 | 23.90 | 0.00803150 | 35.8008 | 11104.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28601.489 | 28601.489 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.332738 | 1.31995573 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 28601.49 | 28601.49 | 1.0000 | 1.31995573 | 1.332738 | 12.66 | 7.89 | 0.00611023 | 28150.0 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28601.49 | -7.90 | 0.00234317 | -7.90 | 0.12033533 | 9.0292 | 21.05 | 0.00764659 | 21.10 | 0.00764659 | 40.4350 | 10140.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 63015.770 | 0.000 | 3.297040 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.9204 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 63015.77 | 63015.77 | 1.0000 | 3.26541774 | 3.297040 | 27.60 | 14.81 | 0.00757439 | 47067.7 | 12.00 | 9.53 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 63015.77 | 35.10 | 0.00565324 | 15.70 | 0.35392745 | 10.7347 | 26.70 | 0.00780542 | 26.70 | 0.00780542 | 29.4642 | 35242.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 88473.507 | 88473.507 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 3.297037 | 3.26541448 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 88473.51 | 88473.51 | 1.0000 | 3.26541448 | 3.297037 | 9.23 | 5.34 | 0.00516215 | 22271.9 | 40.00 | 18.88 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 88473.51 | -7.90 | 0.00234317 | -7.90 | 0.35392745 | 10.7347 | 15.55 | 0.00620332 | 15.55 | 0.00620332 | 46.5656 | 38039.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE OA CONTROLLER | DifferentialDryBulb | 0.12 | 1.33 | - | |||
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.35 | 3.30 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2467.33 | 2281.17 | 1421.67 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2467.33 | 2281.17 | 1421.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 45.83 | 3.50 | 41.00 | 2.83 |
ZONE2 FINE STORAGE | 344.83 | 63.17 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 379.33 | 66.67 | 41.00 | 2.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.910 | 0.393 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 876.95 | 5421.86 | 01-JAN-09:20 | 74225.73 | 22-JUL-14:40 |
Electricity:Building | 621.53 | 4938.86 | 01-JAN-00:10 | 47606.95 | 07-JUN-13:20 |
Electricity:Zone:ZONE1 OFFICE | 62.57 | 1027.15 | 01-JAN-00:10 | 3852.05 | 02-JAN-08:10 |
InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.62 | 453.40 | 01-JAN-00:10 | 1939.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 423.96 | 2726.34 | 01-JAN-00:10 | 33679.30 | 07-JUN-13:20 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 310.51 | 2726.34 | 01-JAN-00:10 | 23173.88 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 25.23 | 483.00 | 16-JAN-18:20 | 2363.06 | 10-FEB-12:50 |
WaterSystems:Electricity | 25.23 | 483.00 | 16-JAN-18:20 | 2363.06 | 10-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 25.23 | 483.00 | 16-JAN-18:20 | 2363.06 | 10-FEB-12:50 |
Fans:Electricity | 73.21 | 0.00 | 01-JAN-09:20 | 7433.39 | 22-JUN-16:20 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 6.12 | 0.00 | 01-JAN-00:10 | 2305.29 | 28-JUN-14:50 |
Ventilation (simple):Fans:Electricity | 6.12 | 0.00 | 01-JAN-00:10 | 2305.29 | 28-JUN-14:50 |
ElectricityPurchased:Facility | 876.95 | 5421.86 | 01-JAN-09:20 | 74225.73 | 22-JUL-14:40 |
ElectricityPurchased:Plant | 876.95 | 5421.86 | 01-JAN-09:20 | 74225.73 | 22-JUL-14:40 |
Cogeneration:ElectricityPurchased | 876.95 | 5421.86 | 01-JAN-09:20 | 74225.73 | 22-JUL-14:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 876.95 | 5421.86 | 01-JAN-09:20 | 74225.73 | 22-JUL-14:40 |
ElectricityNet:Plant | 876.95 | 5421.86 | 01-JAN-09:20 | 74225.73 | 22-JUL-14:40 |
Cogeneration:ElectricityNet | 876.95 | 5421.86 | 01-JAN-09:20 | 74225.73 | 22-JUL-14:40 |
Electricity:HVAC | 106.73 | 0.00 | 01-JAN-09:20 | 26319.32 | 22-JUL-15:10 |
General:Fans:Electricity | 67.09 | 0.00 | 01-JAN-09:20 | 5376.23 | 15-DEC-09:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 39.65 | 0.00 | 01-JAN-00:10 | 21191.22 | 22-JUL-15:10 |
ExteriorLights:Electricity | 123.46 | 0.00 | 01-JAN-07:20 | 7857.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.46 | 0.00 | 01-JAN-07:20 | 7857.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 334.81 | 3750.00 | 14-MAY-12:40 | 176462.53 | 16-JAN-17:50 |
Gas:HVAC | 334.81 | 3750.00 | 14-MAY-12:40 | 176462.53 | 16-JAN-17:50 |
Heating:Gas | 334.81 | 3750.00 | 14-MAY-12:40 | 176462.53 | 16-JAN-17:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-11:30 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-11:30 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-11:30 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-11:30 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-11:30 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-11:30 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-11:30 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 19-JUN-11:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 576.98 | 0.00 | 01-JAN-09:20 | 273141.86 | 16-JAN-17:50 |
EnergyTransfer:Building | 286.03 | 0.00 | 01-JAN-09:20 | 137343.42 | 16-JAN-17:50 |
EnergyTransfer:Zone:ZONE1 OFFICE | 53.08 | 0.00 | 01-JAN-00:10 | 18392.19 | 06-FEB-06:10 |
Heating:EnergyTransfer | 169.74 | 0.00 | 01-JAN-09:20 | 137343.42 | 16-JAN-17:50 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 18.84 | 0.00 | 01-JAN-00:10 | 18392.19 | 06-FEB-06:10 |
Cooling:EnergyTransfer | 116.29 | 0.00 | 01-JAN-00:10 | 50538.86 | 22-JUL-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 34.24 | 0.00 | 01-JAN-00:10 | 12983.95 | 21-JUL-17:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 165.36 | 0.00 | 01-JAN-00:40 | 53533.77 | 16-JAN-17:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 83.32 | 0.00 | 01-JAN-00:40 | 53533.77 | 16-JAN-17:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 82.04 | 0.00 | 01-JAN-00:10 | 40296.55 | 22-JUL-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 67.58 | 0.00 | 01-JAN-08:30 | 85987.92 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 67.58 | 0.00 | 01-JAN-08:30 | 85987.92 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 290.95 | 0.00 | 01-JAN-09:20 | 135798.44 | 16-JAN-17:50 |
HeatingCoils:EnergyTransfer | 159.37 | 0.00 | 01-JAN-09:20 | 135798.44 | 16-JAN-17:50 |
CoolingCoils:EnergyTransfer | 131.58 | 0.00 | 01-JAN-00:10 | 61392.11 | 22-JUL-15:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 18.839 | -34.243 | 0.000 | 0.000 | 3.830 | 30.619 | 31.946 | 13.879 | 0.000 | 1.786 | 0.000 | 0.000 | -9.363 | 0.000 | -17.243 | -40.051 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 83.319 | -82.037 | 0.000 | 0.000 | 0.000 | 135.003 | 0.000 | 0.000 | 0.000 | 5.198 | 0.001 | 0.000 | 0.000 | 0.000 | -100.288 | -41.195 |
ZONE3 BULK STORAGE | 67.581 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 310.507 | 107.336 | 29.366 | 0.000 | 14.751 | 0.001 | 0.000 | -10.766 | 0.000 | -442.236 | -76.540 |
Total Facility | 67.581 | 0.000 | 102.158 | -116.280 | 0.000 | 0.000 | 3.830 | 476.129 | 139.282 | 43.245 | 0.000 | 21.736 | 0.002 | 0.000 | -20.128 | 0.000 | -559.766 | -157.787 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 19-JUN-05:02 | 0.00 | 0.00 | 0.00 | -29330.48 | 0.00 | 0.00 | 33.15 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 29335.56 | 0.00 | -377.51 | 0.00 | -813.81 | 0.00 |
ZONE2 FINE STORAGE | 18-JUN-07:51 | 0.00 | 0.00 | 0.00 | -62270.68 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 61085.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-AUG-18:01 | 0.00 | 0.00 | 0.00 | -74239.23 | 0.00 | 0.00 | 0.00 | 4365.11 | 573.75 | 1310.02 | 0.00 | 1170.94 | 102457.30 | 0.00 | 0.00 | 0.00 | -35637.88 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 17-JAN-06:11 | 0.00 | 0.00 | 29581.43 | 0.00 | 0.00 | 0.00 | 46.49 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -853.61 | 0.00 | -2450.64 | -27476.77 |
ZONE2 FINE STORAGE | 24-DEC-06:12 | 0.00 | 0.00 | 91598.73 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -11600.32 | -81183.77 |
ZONE3 BULK STORAGE | 14-DEC-04:00 | 85977.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -705.31 | 0.00 | -84196.47 | -5852.07 |
Total Facility | 06-FEB-06:01 | 62189.82 | 0.00 | 118381.86 | 0.00 | 0.00 | 0.00 | 58.01 | 4491.05 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1654.44 | 0.00 | -57836.44 | -128253.64 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3327 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.3327 | 0.0903 | 1.0000 | 0.1203 | 0.0903 | ||
PSZ-FINE STORAGE | 3.2970 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 3.2970 | 0.1073 | 1.0000 | 0.3539 | 0.1073 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.3327 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.3327 | 1.0000 | 1.0000 | 0.1203 | 0.0903 | ||
PSZ-FINE STORAGE | 3.2970 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 3.2970 | 1.0000 | 1.0000 | 0.3539 | 0.1073 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.3327 | 1.3327 | 1.3327 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.2970 | 3.2970 | 3.2970 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3327 | 1.3327 | 1.3327 | 1.3327 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 3.2970 | 3.2970 | 3.2970 | 3.2970 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.3327 | 1.3327 | 1.3327 | 0.1203 | 0.2897 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 3.2970 | 3.2970 | 3.2970 | 0.3539 | 0.2697 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.3327 | 1.3327 | 1.3327 | 1.3327 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 3.2970 | 3.2970 | 3.2970 | 3.2970 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:56
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 41.00 |
Number of hours cooling loads not met | 2.83 |
Number of hours not met | 43.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 334.81 | 176462.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 39.65 | 21191.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 476.13 | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.46 | 7857.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 6.12 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 67.09 | 5376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 25.23 | 2363.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 876.95 |
Natural Gas | 0.00 | 334.81 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1211.76 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 98.47 |
Space Heating | 0.00 |
Space Cooling | 8.20 |
Fans (All) | 15.14 |
Service Water Heating | 5.22 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 181.37 |
Subtotal | 181.37 |
Natural Gas [MJ/m2] | |
Space Heating | 69.25 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 69.25 |
Subtotal | 69.25 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 39.29 |
Space Heating | 27.63 |
Space Cooling | 3.27 |
Fans (All) | 6.04 |
Service Water Heating | 2.08 |
Receptacle Equipment | 11.49 |
Miscellaneous | 10.19 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.819063E+11 |
February | 0.000 | 0.588865E+11 |
March | 0.000 | 0.238415E+11 |
April | 0.000 | 0.108853E+11 |
May | 0.000 | 0.101511E+11 |
June | 0.000 | 0.972145E+10 |
July | 0.000 | 0.100440E+11 |
August | 0.000 | 0.100440E+11 |
September | 0.000 | 0.972090E+10 |
October | 0.000 | 0.112826E+11 |
November | 0.000 | 0.228287E+11 |
December | 0.000 | 0.754976E+11 |
Annual Sum or Average | 0.334810E+12 | |
Minimum of Months | 0.000 | 0.972090E+10 |
Maximum of Months | 0.000 | 0.819063E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.819063E+11 |
February | 0.000 | 0.588865E+11 |
March | 0.000 | 0.238415E+11 |
April | 0.000 | 0.108853E+11 |
May | 0.000 | 0.101511E+11 |
June | 0.000 | 0.972145E+10 |
July | 0.000 | 0.100440E+11 |
August | 0.000 | 0.100440E+11 |
September | 0.000 | 0.972090E+10 |
October | 0.000 | 0.112826E+11 |
November | 0.000 | 0.228287E+11 |
December | 0.000 | 0.754976E+11 |
Annual Sum or Average | 0.334810E+12 | |
Minimum of Months | 0.000 | 0.972090E+10 |
Maximum of Months | 0.000 | 0.819063E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.819063E+11 |
February | 0.000 | 0.588865E+11 |
March | 0.000 | 0.238415E+11 |
April | 0.000 | 0.108853E+11 |
May | 0.000 | 0.101511E+11 |
June | 0.000 | 0.972145E+10 |
July | 0.000 | 0.100440E+11 |
August | 0.000 | 0.100440E+11 |
September | 0.000 | 0.972090E+10 |
October | 0.000 | 0.112826E+11 |
November | 0.000 | 0.228287E+11 |
December | 0.000 | 0.754976E+11 |
Annual Sum or Average | 0.334810E+12 | |
Minimum of Months | 0.000 | 0.972090E+10 |
Maximum of Months | 0.000 | 0.819063E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.819063E+11 |
February | 0.000 | 0.588865E+11 |
March | 0.000 | 0.238415E+11 |
April | 0.000 | 0.108853E+11 |
May | 0.000 | 0.101511E+11 |
June | 0.000 | 0.972145E+10 |
July | 0.000 | 0.100440E+11 |
August | 0.000 | 0.100440E+11 |
September | 0.000 | 0.972090E+10 |
October | 0.000 | 0.112826E+11 |
November | 0.000 | 0.228287E+11 |
December | 0.000 | 0.754976E+11 |
Annual Sum or Average | 0.334810E+12 | |
Minimum of Months | 0.000 | 0.972090E+10 |
Maximum of Months | 0.000 | 0.819063E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.819063E+11 |
February | 0.000 | 0.588865E+11 |
March | 0.000 | 0.238415E+11 |
April | 0.000 | 0.108853E+11 |
May | 0.000 | 0.101511E+11 |
June | 0.000 | 0.972145E+10 |
July | 0.000 | 0.100440E+11 |
August | 0.000 | 0.100440E+11 |
September | 0.000 | 0.972090E+10 |
October | 0.000 | 0.112826E+11 |
November | 0.000 | 0.228287E+11 |
December | 0.000 | 0.754976E+11 |
Annual Sum or Average | 0.334810E+12 | |
Minimum of Months | 0.000 | 0.972090E+10 |
Maximum of Months | 0.000 | 0.819063E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.819063E+11 |
February | 0.000 | 0.588865E+11 |
March | 0.000 | 0.238415E+11 |
April | 0.000 | 0.108853E+11 |
May | 0.000 | 0.101511E+11 |
June | 0.000 | 0.972145E+10 |
July | 0.000 | 0.100440E+11 |
August | 0.000 | 0.100440E+11 |
September | 0.000 | 0.972090E+10 |
October | 0.000 | 0.112826E+11 |
November | 0.000 | 0.228287E+11 |
December | 0.000 | 0.754976E+11 |
Annual Sum or Average | 0.334810E+12 | |
Minimum of Months | 0.000 | 0.972090E+10 |
Maximum of Months | 0.000 | 0.819063E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.819063E+11 |
February | 0.000 | 0.588865E+11 |
March | 0.000 | 0.238415E+11 |
April | 0.000 | 0.108853E+11 |
May | 0.000 | 0.101511E+11 |
June | 0.000 | 0.972145E+10 |
July | 0.000 | 0.100440E+11 |
August | 0.000 | 0.100440E+11 |
September | 0.000 | 0.972090E+10 |
October | 0.000 | 0.112826E+11 |
November | 0.000 | 0.228287E+11 |
December | 0.000 | 0.754976E+11 |
Annual Sum or Average | 0.334810E+12 | |
Minimum of Months | 0.000 | 0.972090E+10 |
Maximum of Months | 0.000 | 0.819063E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.819063E+11 |
February | 0.000 | 0.588865E+11 |
March | 0.000 | 0.238415E+11 |
April | 0.000 | 0.108853E+11 |
May | 0.000 | 0.101511E+11 |
June | 0.000 | 0.972145E+10 |
July | 0.000 | 0.100440E+11 |
August | 0.000 | 0.100440E+11 |
September | 0.000 | 0.972090E+10 |
October | 0.000 | 0.112826E+11 |
November | 0.000 | 0.228287E+11 |
December | 0.000 | 0.754976E+11 |
Annual Sum or Average | 0.334810E+12 | |
Minimum of Months | 0.000 | 0.972090E+10 |
Maximum of Months | 0.000 | 0.819063E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.819063E+11 |
February | 0.000 | 0.588865E+11 |
March | 0.000 | 0.238415E+11 |
April | 0.000 | 0.108853E+11 |
May | 0.000 | 0.101511E+11 |
June | 0.000 | 0.972145E+10 |
July | 0.000 | 0.100440E+11 |
August | 0.000 | 0.100440E+11 |
September | 0.000 | 0.972090E+10 |
October | 0.000 | 0.112826E+11 |
November | 0.000 | 0.228287E+11 |
December | 0.000 | 0.754976E+11 |
Annual Sum or Average | 0.334810E+12 | |
Minimum of Months | 0.000 | 0.972090E+10 |
Maximum of Months | 0.000 | 0.819063E+11 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 938169.38 | 194.02 | 06-JAN-17:00 | 5.60 | 0.63 | 0.198393E+09 | 286.30 | 05-JAN-16:10 | 15.63 | 6.61 |
February | 17774905.94 | 1158.71 | 15-FEB-16:30 | 16.95 | 6.15 | 0.185375E+09 | 301.58 | 13-FEB-15:50 | 21.60 | 7.23 |
March | 39489143.84 | 1540.21 | 08-MAR-16:40 | 22.40 | 8.49 | 0.227971E+09 | 301.59 | 27-MAR-15:00 | 18.90 | 7.40 |
April | 0.117693E+10 | 5171.74 | 13-APR-16:00 | 25.60 | 10.04 | 0.234335E+09 | 301.59 | 17-APR-13:50 | 24.13 | 9.50 |
May | 0.303085E+10 | 23082.12 | 19-MAY-05:03 | 16.78 | 9.40 | 0.254863E+09 | 301.64 | 23-MAY-14:39 | 16.83 | 13.83 |
June | 0.635790E+10 | 29329.94 | 19-JUN-05:02 | 12.57 | 5.14 | 0.258652E+09 | 301.61 | 29-JUN-08:09 | 29.50 | 17.96 |
July | 0.782360E+10 | 24533.17 | 21-JUL-05:01 | 20.37 | 11.71 | 0.248876E+09 | 301.61 | 29-JUL-12:00 | 31.10 | 18.94 |
August | 0.781261E+10 | 24565.74 | 19-AUG-05:01 | 19.22 | 11.91 | 0.268808E+09 | 301.65 | 28-AUG-14:09 | 23.40 | 17.49 |
September | 0.551032E+10 | 27620.28 | 21-SEP-05:02 | 13.22 | 7.02 | 0.248909E+09 | 301.61 | 22-SEP-10:50 | 24.13 | 14.41 |
October | 0.239384E+10 | 27030.53 | 06-OCT-05:02 | 12.80 | 7.62 | 0.237614E+09 | 301.61 | 07-OCT-14:09 | 23.98 | 14.16 |
November | 67606661.78 | 2122.48 | 02-NOV-15:50 | 16.78 | 9.69 | 0.203224E+09 | 301.58 | 24-NOV-16:30 | 14.45 | 4.53 |
December | 12853832.49 | 323.92 | 05-DEC-15:30 | 6.10 | 0.20 | 0.196943E+09 | 289.86 | 02-DEC-15:00 | 11.10 | 3.04 |
Annual Sum or Average | 0.342447E+11 | 0.276396E+10 | ||||||||
Minimum of Months | 938169.38 | 194.02 | 5.60 | 0.20 | 0.185375E+09 | 286.30 | 11.10 | 3.04 | ||
Maximum of Months | 0.782360E+10 | 29329.94 | 25.60 | 11.91 | 0.268808E+09 | 301.65 | 31.10 | 18.94 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.213001E+09 | 2395.53 | 20-JAN-13:00 | -0.6 | -0.8 | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.0 |
February | 0.240312E+09 | 2147.42 | 06-FEB-11:00 | 0.60 | -3.3 | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.1 |
March | 76186457.77 | 1866.92 | 10-MAR-09:15 | 5.17 | 0.19 | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.6 |
April | 0.432496E+09 | 7547.22 | 28-APR-14:10 | 24.50 | 10.28 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.83 |
May | 0.391907E+10 | 59329.72 | 21-MAY-11:11 | 24.97 | 13.21 | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.90 |
June | 0.167964E+11 | 62266.39 | 18-JUN-07:51 | 22.80 | 11.49 | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.94 |
July | 0.247559E+11 | 61062.44 | 22-JUL-00:01 | 24.13 | 13.31 | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.89 |
August | 0.216277E+11 | 60142.37 | 16-AUG-21:31 | 24.47 | 13.25 | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.85 |
September | 0.106101E+11 | 59191.26 | 17-SEP-16:41 | 24.50 | 13.74 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.45 |
October | 0.256291E+10 | 61782.02 | 01-OCT-10:21 | 22.50 | 13.07 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.87 |
November | 0.289250E+09 | 6175.89 | 08-NOV-07:10 | 10.50 | 4.85 | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.31 |
December | 0.518517E+09 | 3189.27 | 21-DEC-09:50 | -3.6 | -5.1 | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.83 |
Annual Sum or Average | 0.820419E+11 | 0.00 | ||||||||
Minimum of Months | 76186457.77 | 1866.92 | -3.6 | -5.1 | 0.00 | 0.00 | -3.2 | -5.1 | ||
Maximum of Months | 0.247559E+11 | 62266.39 | 24.97 | 13.74 | 0.00 | 0.00 | 21.95 | 16.85 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 2.30 | -1.0 | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -3.2 | -5.1 | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 2.47 | -0.6 | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.83 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.83 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.90 | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.94 | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.94 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.89 | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.89 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.85 | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.45 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.45 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.87 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.87 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.31 | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.31 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.83 | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.83 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.2 | -5.1 | 0.00 | 0.00 | -3.2 | -5.1 | ||
Maximum of Months | 0.00 | 0.00 | 21.95 | 16.85 | 0.00 | 0.00 | 21.95 | 16.85 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.468785E+10 | 29581.44 | 17-JAN-06:11 | -3.5 |
February | 0.374046E+10 | 29122.67 | 06-FEB-06:01 | -4.6 |
March | 0.254521E+10 | 29138.94 | 06-MAR-06:12 | -2.4 |
April | 0.681939E+09 | 28946.27 | 07-APR-05:01 | 4.22 |
May | 0.206028E+09 | 28466.93 | 05-MAY-05:01 | 5.68 |
June | 35784087.69 | 2613.85 | 30-JUN-06:05 | 19.78 |
July | 11338764.80 | 2429.81 | 03-JUL-06:05 | 20.28 |
August | 10765245.39 | 2602.08 | 16-AUG-06:05 | 18.58 |
September | 41750465.39 | 3430.95 | 15-SEP-06:05 | 18.98 |
October | 0.560444E+09 | 28966.09 | 26-OCT-05:01 | -2.5 |
November | 0.193669E+10 | 29345.14 | 25-NOV-06:42 | 1.10 |
December | 0.438083E+10 | 29270.09 | 14-DEC-06:12 | -3.5 |
Annual Sum or Average | 0.188391E+11 | |||
Minimum of Months | 10765245.39 | 2429.81 | -4.6 | |
Maximum of Months | 0.468785E+10 | 29581.44 | 20.28 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238810E+11 | 91560.01 | 17-JAN-22:02 | -1.6 |
February | 0.174729E+11 | 91426.34 | 05-FEB-04:42 | -3.6 |
March | 0.787953E+10 | 90090.39 | 04-MAR-00:02 | 1.60 |
April | 0.143254E+10 | 46886.07 | 07-APR-23:53 | 3.90 |
May | 0.620134E+09 | 3743.66 | 04-MAY-06:50 | 6.52 |
June | 0.265925E+09 | 3375.21 | 24-JUN-06:13 | 19.97 |
July | 93666853.89 | 3405.98 | 17-JUL-06:13 | 19.07 |
August | 0.202088E+09 | 3446.80 | 28-AUG-06:12 | 16.13 |
September | 0.352033E+09 | 3948.68 | 01-SEP-07:00 | 18.90 |
October | 0.106840E+10 | 52289.48 | 26-OCT-04:13 | -2.8 |
November | 0.783612E+10 | 91411.27 | 26-NOV-05:02 | 1.02 |
December | 0.222144E+11 | 91598.87 | 24-DEC-06:12 | -3.1 |
Annual Sum or Average | 0.833187E+11 | |||
Minimum of Months | 93666853.89 | 3375.21 | -3.6 | |
Maximum of Months | 0.238810E+11 | 91598.87 | 19.97 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262639E+11 | 85735.91 | 16-JAN-18:00 | -1.7 |
February | 0.170076E+11 | 75335.19 | 05-FEB-02:00 | -2.8 |
March | 0.118549E+10 | 29737.29 | 04-MAR-05:53 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.411332E+09 | 18881.36 | 26-NOV-06:50 | 0.10 |
December | 0.227133E+11 | 85987.92 | 14-DEC-04:00 | -1.1 |
Annual Sum or Average | 0.675816E+11 | |||
Minimum of Months | 0.00 | 0.00 | -2.8 | |
Maximum of Months | 0.262639E+11 | 85987.92 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.256100E+10 | 1939.55 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.233575E+10 | 1939.55 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.266872E+10 | 1939.55 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.252182E+10 | 1939.55 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.261486E+10 | 1939.55 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.257569E+10 | 1939.55 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.256100E+10 | 1939.55 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.266872E+10 | 1939.55 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.252182E+10 | 1939.55 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.256100E+10 | 1939.55 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.246796E+10 | 1939.55 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.256100E+10 | 1939.55 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.306193E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.233575E+10 | 1939.55 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.266872E+10 | 1939.55 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112294E+11 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102778E+11 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.118738E+11 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.111270E+11 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.115516E+11 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.114492E+11 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112294E+11 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.118738E+11 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.111270E+11 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112294E+11 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108048E+11 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112294E+11 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135003E+12 | ||||
Minimum of Months | 0.102778E+11 | 10075.60 | 0.00 | 0.00 | |
Maximum of Months | 0.118738E+11 | 10075.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.258277E+11 | 23173.88 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.236390E+11 | 23173.88 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.273097E+11 | 23173.88 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.255921E+11 | 23173.88 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.265687E+11 | 23173.88 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.263332E+11 | 23173.88 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.258277E+11 | 23173.88 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.273097E+11 | 23173.88 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.255921E+11 | 23173.88 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.258277E+11 | 23173.88 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.248511E+11 | 23173.88 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.258277E+11 | 23173.88 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.236390E+11 | 23173.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.273097E+11 | 23173.88 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266925E+10 |
February | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228026E+10 |
March | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204752E+10 |
April | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14325431.05 | 0.130478E+10 |
May | 0.565842E+09 | 0.261486E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85725604.32 | 0.106577E+10 |
June | 0.565842E+09 | 0.257569E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502701E+09 | 0.510466E+09 |
July | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564838E+09 | 0.256523E+09 |
August | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417514E+09 | 0.421107E+09 |
September | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168473E+09 | 0.623400E+09 |
October | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32690832.73 | 0.138081E+10 |
November | 0.522316E+09 | 0.246796E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203500E+10 |
December | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264768E+10 |
Annual Sum or Average | 0.659424E+10 | 0.306193E+11 | 0.319458E+11 | 0.178627E+10 | 0.172426E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256523E+09 |
Maximum of Months | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564838E+09 | 0.266925E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137677E+11 |
February | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128093E+11 |
March | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8035.77 | 0.112598E+11 |
April | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13286879.55 | 0.817561E+10 |
May | 0.00 | 0.115516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166099E+09 | 0.760003E+10 |
June | 0.00 | 0.114492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161436E+10 | 0.453959E+10 |
July | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209069E+10 | 0.282009E+10 |
August | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107535E+10 | 0.396352E+10 |
September | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226949E+09 | 0.511973E+10 |
October | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11697492.21 | 0.788814E+10 |
November | 0.00 | 0.108048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100192E+11 |
December | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123249E+11 |
Annual Sum or Average | 0.135003E+12 | 0.519843E+10 | 0.100288E+12 | ||||||
Minimum of Months | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282009E+10 |
Maximum of Months | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209069E+10 | 0.137677E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133861E+09 | 0.275923E+11 |
February | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324220E+09 | 0.260281E+11 |
March | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790237E+09 | 0.233877E+11 |
April | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.911510E+09 | 0.208907E+11 |
May | 0.00 | 0.265687E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599245E+09 | 0.253638E+11 |
June | 0.00 | 0.263332E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317725E+09 | 0.188948E+11 |
July | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201491E+09 | 0.151795E+11 |
August | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27397524.53 | 0.194976E+11 |
September | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5433534.99 | 0.215748E+11 |
October | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85689963.65 | 0.278556E+11 |
November | 0.00 | 0.248511E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11915069.04 | 0.242658E+11 |
December | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7959347.63 | 0.257596E+11 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | 0.341668E+10 | 0.276290E+12 | |||||
Minimum of Months | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5433534.99 | 0.151795E+11 |
Maximum of Months | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.911510E+09 | 0.278556E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1939.55 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 10066.12 | 17-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1939.55 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 9647.10 | 06-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1939.55 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 7893.42 | 10-MAR-07:03 |
April | 659.25 | 01-APR-07:10 | 1939.55 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 717.10 | 13-APR-17:00 | 6358.87 | 06-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1939.55 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2139.16 | 19-MAY-17:00 | 5611.03 | 05-MAY-07:00 |
June | 659.25 | 01-JUN-07:10 | 1939.55 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4413.50 | 28-JUN-16:10 | 4542.78 | 09-JUN-06:03 |
July | 659.25 | 01-JUL-07:10 | 1939.55 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4200.96 | 21-JUL-17:00 | 1797.28 | 28-JUL-06:05 |
August | 659.25 | 01-AUG-07:10 | 1939.55 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3391.49 | 01-AUG-16:10 | 3314.58 | 31-AUG-06:10 |
September | 659.25 | 01-SEP-07:10 | 1939.55 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2159.66 | 20-SEP-17:00 | 4103.57 | 27-SEP-06:01 |
October | 659.25 | 02-OCT-07:10 | 1939.55 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.22 | 06-OCT-16:10 | 7999.96 | 27-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1939.55 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 8494.59 | 27-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1939.55 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9874.12 | 15-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1797.28 | |||||
Maximum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4413.50 | 10066.12 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 30193.83 | 16-JAN-18:00 |
February | 0.00 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 23777.12 | 05-FEB-01:00 |
March | 0.00 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.39 | 12-MAR-17:00 | 24261.37 | 14-MAR-07:00 |
April | 0.00 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1167.20 | 01-APR-17:30 | 26096.43 | 15-APR-15:03 |
May | 0.00 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4340.46 | 19-MAY-15:10 | 16705.06 | 04-MAY-07:00 |
June | 0.00 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11027.52 | 17-JUN-16:00 | 11351.83 | 01-JUN-17:00 |
July | 0.00 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9405.60 | 04-JUL-15:08 | 7463.59 | 15-JUL-19:00 |
August | 0.00 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6348.70 | 02-AUG-17:00 | 8341.66 | 25-AUG-19:55 |
September | 0.00 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3038.22 | 03-SEP-14:50 | 10589.09 | 07-SEP-15:10 |
October | 0.00 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1044.61 | 01-OCT-16:00 | 26004.15 | 24-OCT-15:02 |
November | 0.00 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 21806.27 | 26-NOV-06:00 |
December | 0.00 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 31862.34 | 14-DEC-04:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7463.59 | |||
Maximum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11027.52 | 31862.34 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23173.88 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6900.47 | 24-JAN-15:00 | 60122.00 | 17-JAN-08:70 |
February | 0.00 | 23173.88 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12225.81 | 14-FEB-17:00 | 47681.10 | 05-FEB-01:40 |
March | 0.00 | 23173.88 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14805.41 | 08-MAR-17:00 | 48032.19 | 21-MAR-10:55 |
April | 0.00 | 23173.88 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12726.36 | 01-APR-17:00 | 71473.70 | 15-APR-12:05 |
May | 0.00 | 23173.88 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7208.14 | 07-MAY-17:00 | 53553.00 | 05-MAY-08:00 |
June | 0.00 | 23173.88 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5495.11 | 06-JUN-16:00 | 35538.86 | 08-JUN-12:05 |
July | 0.00 | 23173.88 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3662.44 | 04-JUL-16:51 | 30253.74 | 15-JUL-19:00 |
August | 0.00 | 23173.88 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1004.60 | 20-AUG-17:00 | 32617.83 | 22-AUG-21:00 |
September | 0.00 | 23173.88 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1001.01 | 03-SEP-13:42 | 35784.45 | 07-SEP-15:00 |
October | 0.00 | 23173.88 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9200.46 | 31-OCT-15:00 | 75161.34 | 24-OCT-15:00 |
November | 0.00 | 23173.88 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3494.66 | 09-NOV-14:00 | 43011.78 | 03-NOV-21:25 |
December | 0.00 | 23173.88 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2706.77 | 24-DEC-15:00 | 61927.96 | 14-DEC-04:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1001.01 | 30253.74 | ||||
Maximum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 14805.41 | 75161.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 194.02 | 06-JAN-17:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 985.87 |
February | 1158.71 | 15-FEB-16:30 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 511.67 |
March | 1540.21 | 08-MAR-16:40 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.85 |
April | 5171.74 | 13-APR-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 145.16 | 0.00 |
May | 23082.12 | 19-MAY-05:03 | 217.55 | 1738.04 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.74 |
June | 29329.94 | 19-JUN-05:02 | 435.11 | 3476.08 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813.81 |
July | 24533.17 | 21-JUL-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.26 |
August | 24565.74 | 19-AUG-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.14 |
September | 27620.28 | 21-SEP-05:02 | 362.59 | 2896.74 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 679.91 |
October | 27030.53 | 06-OCT-05:02 | 362.59 | 2896.74 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.07 |
November | 2122.48 | 02-NOV-15:50 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.10 |
December | 323.92 | 05-DEC-15:30 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 723.63 |
Annual Sum or Average | |||||||||||
Minimum of Months | 194.02 | 217.55 | 1738.04 | 1721.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29329.94 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 145.16 | 985.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2395.53 | 20-JAN-13:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2744.92 |
February | 2147.42 | 06-FEB-11:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.34 |
March | 1866.92 | 10-MAR-09:15 | 0.00 | 20151.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3518.77 |
April | 7547.22 | 28-APR-14:10 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 781.72 |
May | 59329.72 | 21-MAY-11:11 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 870.32 |
June | 62266.39 | 18-JUN-07:51 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 61062.44 | 22-JUL-00:01 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 901.83 |
August | 60142.37 | 16-AUG-21:31 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 613.67 |
September | 59191.26 | 17-SEP-16:41 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.18 |
October | 61782.02 | 01-OCT-10:21 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 886.90 |
November | 6175.89 | 08-NOV-07:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2392.38 |
December | 3189.27 | 21-DEC-09:50 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1866.92 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 62266.39 | 0.00 | 20151.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3518.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 13631.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11650.24 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 13631.69 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20266.92 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3684.25 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5522.27 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11564.78 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12092.18 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10210.93 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8550.21 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9602.50 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9027.95 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3436.59 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4547.48 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3436.59 | |
Maximum of Months | 0.00 | 0.00 | 13631.69 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20266.92 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.720289E+11 | 52440.13 | 17-JAN-11:50 | 0.819063E+11 | 176462.53 | 16-JAN-17:49 |
February | 0.649196E+11 | 52516.78 | 14-FEB-15:00 | 0.588865E+11 | 159561.59 | 05-FEB-01:30 |
March | 0.729648E+11 | 52728.48 | 08-MAR-15:00 | 0.238415E+11 | 99881.12 | 04-MAR-06:10 |
April | 0.676705E+11 | 55860.03 | 28-APR-14:50 | 0.108853E+11 | 30578.96 | 08-APR-05:19 |
May | 0.709230E+11 | 61934.51 | 19-MAY-14:00 | 0.101511E+11 | 11809.26 | 05-MAY-05:10 |
June | 0.781419E+11 | 73936.36 | 28-JUN-14:00 | 0.972145E+10 | 5348.06 | 17-JUN-05:49 |
July | 0.822962E+11 | 74225.73 | 22-JUL-14:39 | 0.100440E+11 | 3750.00 | 01-JUL-00:10 |
August | 0.836854E+11 | 70170.12 | 01-AUG-14:00 | 0.100440E+11 | 3750.00 | 01-AUG-00:10 |
September | 0.732286E+11 | 67009.40 | 02-SEP-14:00 | 0.972090E+10 | 5257.77 | 30-SEP-05:49 |
October | 0.707465E+11 | 63366.08 | 06-OCT-14:00 | 0.112826E+11 | 37003.34 | 26-OCT-05:10 |
November | 0.681806E+11 | 55983.93 | 30-NOV-16:00 | 0.228287E+11 | 76828.12 | 26-NOV-06:30 |
December | 0.721609E+11 | 56234.87 | 14-DEC-16:00 | 0.754976E+11 | 171011.26 | 14-DEC-03:00 |
Annual Sum or Average | 0.876947E+12 | 0.334810E+12 | ||||
Minimum of Months | 0.649196E+11 | 52440.13 | 0.972090E+10 | 3750.00 | ||
Maximum of Months | 0.836854E+11 | 74225.73 | 0.819063E+11 | 176462.53 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.396181E+11 | 0.123041E+11 | 0.115358E+11 | 0.00 | 0.633817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223278E+10 | 0.00 |
February | 0.362526E+11 | 0.104797E+11 | 0.105871E+11 | 0.00 | 0.556400E+10 | 0.00 | 0.00 | 960312.66 | 0.00 | 0.00 | 0.00 | 0.203530E+10 | 0.00 |
March | 0.418523E+11 | 0.106871E+11 | 0.123357E+11 | 0.00 | 0.580860E+10 | 0.00 | 0.00 | 3879918.92 | 0.00 | 0.00 | 0.00 | 0.227725E+10 | 0.00 |
April | 0.392410E+11 | 0.940483E+10 | 0.114862E+11 | 0.00 | 0.510186E+10 | 0.00 | 0.00 | 0.316792E+09 | 0.00 | 0.00 | 0.00 | 0.211983E+10 | 0.00 |
May | 0.407352E+11 | 0.891927E+10 | 0.119357E+11 | 0.00 | 0.532181E+10 | 0.00 | 0.00 | 0.187702E+10 | 0.00 | 0.00 | 0.00 | 0.213397E+10 | 0.00 |
June | 0.403581E+11 | 0.820742E+10 | 0.118862E+11 | 0.00 | 0.717369E+10 | 0.00 | 0.00 | 0.848715E+10 | 0.00 | 0.00 | 0.00 | 0.202944E+10 | 0.00 |
July | 0.396181E+11 | 0.870241E+10 | 0.115358E+11 | 0.00 | 0.803533E+10 | 0.00 | 0.00 | 0.123915E+11 | 0.00 | 0.00 | 0.00 | 0.201306E+10 | 0.00 |
August | 0.418523E+11 | 0.935769E+10 | 0.123357E+11 | 0.00 | 0.762664E+10 | 0.00 | 0.00 | 0.104585E+11 | 0.00 | 0.00 | 0.00 | 0.205465E+10 | 0.00 |
September | 0.392410E+11 | 0.994696E+10 | 0.114862E+11 | 0.00 | 0.560940E+10 | 0.00 | 0.00 | 0.495991E+10 | 0.00 | 0.00 | 0.00 | 0.198517E+10 | 0.00 |
October | 0.396181E+11 | 0.112292E+11 | 0.115358E+11 | 0.00 | 0.513330E+10 | 0.00 | 0.00 | 0.114964E+10 | 0.00 | 0.00 | 0.00 | 0.208045E+10 | 0.00 |
November | 0.381239E+11 | 0.116865E+11 | 0.110862E+11 | 0.00 | 0.521498E+10 | 0.00 | 0.00 | 1026.11 | 0.00 | 0.00 | 0.00 | 0.206898E+10 | 0.00 |
December | 0.396181E+11 | 0.125303E+11 | 0.115358E+11 | 0.00 | 0.627847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219814E+10 | 0.00 |
Annual Sum or Average | 0.476129E+12 | 0.123455E+12 | 0.139282E+12 | 0.732062E+11 | 0.00 | 0.396453E+11 | 0.252290E+11 | ||||||
Minimum of Months | 0.362526E+11 | 0.820742E+10 | 0.105871E+11 | 0.00 | 0.510186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198517E+10 | 0.00 |
Maximum of Months | 0.418523E+11 | 0.125303E+11 | 0.123357E+11 | 0.00 | 0.803533E+10 | 0.00 | 0.00 | 0.123915E+11 | 0.00 | 0.00 | 0.00 | 0.227725E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.819063E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.588865E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.238415E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.108853E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.101511E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.972145E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.100440E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.100440E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.972090E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.112826E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.228287E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.754976E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.334810E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.972090E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.819063E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35189.04 | 02-JAN-09:09 | 7857.00 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 5376.23 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35189.04 | 01-FEB-09:09 | 7857.00 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 5376.23 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35189.04 | 01-MAR-09:09 | 7857.00 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 5376.23 | 04-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35189.04 | 01-APR-08:09 | 7857.00 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 5128.09 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35189.04 | 01-MAY-08:09 | 7857.00 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 5128.09 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35189.04 | 01-JUN-08:09 | 7857.00 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 7433.39 | 22-JUN-16:19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35189.04 | 01-JUL-08:09 | 7857.00 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 7433.39 | 26-JUL-16:19 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35189.04 | 01-AUG-08:09 | 7857.00 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 7433.39 | 01-AUG-09:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35189.04 | 01-SEP-08:09 | 7857.00 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 7433.39 | 22-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35189.04 | 02-OCT-08:09 | 7857.00 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 7433.39 | 06-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35189.04 | 01-NOV-08:09 | 7857.00 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 5376.23 | 28-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35189.04 | 01-DEC-09:09 | 7857.00 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 5376.23 | 15-DEC-08:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35189.04 | 7857.00 | 10112.62 | 0.00 | 5128.09 | 0.00 | 0.00 | |||||
Maximum of Months | 35189.04 | 7857.00 | 10112.62 | 0.00 | 7433.39 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2359.75 | 31-JAN-12:09 | 0.00 |
February | 279.63 | 14-FEB-15:00 | 0.00 | 0.00 | 0.00 | 2363.06 | 10-FEB-12:50 | 0.00 |
March | 496.88 | 08-MAR-15:00 | 0.00 | 0.00 | 0.00 | 2323.70 | 01-MAR-12:20 | 0.00 |
April | 3658.51 | 28-APR-14:50 | 0.00 | 0.00 | 0.00 | 2134.76 | 01-APR-11:00 | 0.00 |
May | 10434.04 | 19-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1808.32 | 01-MAY-11:50 | 0.00 |
June | 20735.26 | 28-JUN-16:10 | 0.00 | 0.00 | 0.00 | 1781.84 | 01-JUN-11:09 | 0.00 |
July | 21191.22 | 22-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1762.87 | 01-JUL-11:09 | 0.00 |
August | 16701.43 | 01-AUG-15:50 | 0.00 | 0.00 | 0.00 | 1756.58 | 31-AUG-11:39 | 0.00 |
September | 12730.24 | 02-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1771.64 | 30-SEP-11:00 | 0.00 |
October | 8919.56 | 02-OCT-14:39 | 0.00 | 0.00 | 0.00 | 1795.36 | 31-OCT-11:30 | 0.00 |
November | 0.18 | 02-NOV-14:00 | 0.00 | 0.00 | 0.00 | 2004.15 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2228.09 | 27-DEC-12:39 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1756.58 | 0.00 | ||
Maximum of Months | 21191.22 | 0.00 | 0.00 | 0.00 | 2363.06 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 52440.13 | 17-JAN-11:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 5376.23 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52516.78 | 14-FEB-15:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 5128.09 | 0.00 | 0.00 | 279.63 | 0.00 |
March | 52728.48 | 08-MAR-15:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 5128.09 | 0.00 | 0.00 | 496.88 | 0.00 |
April | 55860.03 | 28-APR-14:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 5128.09 | 0.00 | 0.00 | 3658.51 | 0.00 |
May | 61934.51 | 19-MAY-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 5128.09 | 0.00 | 0.00 | 9748.49 | 0.00 |
June | 73936.36 | 28-JUN-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 7433.39 | 0.00 | 0.00 | 19469.73 | 0.00 |
July | 74225.73 | 22-JUL-14:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 7433.39 | 0.00 | 0.00 | 19767.05 | 0.00 |
August | 70170.12 | 01-AUG-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 7433.39 | 0.00 | 0.00 | 15712.45 | 0.00 |
September | 67009.40 | 02-SEP-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 7433.39 | 0.00 | 0.00 | 12548.23 | 0.00 |
October | 63366.08 | 06-OCT-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 7433.39 | 0.00 | 0.00 | 8889.27 | 0.00 |
November | 55983.93 | 30-NOV-16:00 | 31277.33 | 10112.62 | 7857.00 | 0.00 | 5128.09 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 56234.87 | 14-DEC-16:00 | 31277.33 | 10112.62 | 7857.00 | 0.00 | 5376.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 52440.13 | 31277.33 | 10112.62 | 0.00 | 0.00 | 5128.09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 74225.73 | 35189.04 | 10112.62 | 7857.00 | 0.00 | 7433.39 | 0.00 | 0.00 | 19767.05 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 176462.53 | 16-JAN-17:49 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 159561.59 | 05-FEB-01:30 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 99881.12 | 04-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 30578.96 | 08-APR-05:19 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 11809.26 | 05-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 5348.06 | 17-JUN-05:49 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 3750.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 3750.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 5257.77 | 30-SEP-05:49 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 37003.34 | 26-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 76828.12 | 26-NOV-06:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 171011.26 | 14-DEC-03:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 3750.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 176462.53 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.17 | 18.47 | 9.00 | 19.30 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9.33 | 18.63 | 7.50 | 19.52 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7.17 | 19.79 | 7.00 | 19.91 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2.00 | 20.19 | 2.00 | 20.19 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.33 | 20.40 | 0.33 | 20.40 | 0.17 | 24.49 | 0.17 | 24.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.97 | 0.50 | 24.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 26.11 | 0.83 | 24.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.71 | 0.33 | 24.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.59 | 0.67 | 24.48 |
October | 1.33 | 20.17 | 1.33 | 20.17 | 0.33 | 24.58 | 0.33 | 24.58 |
November | 5.50 | 19.99 | 5.50 | 19.99 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9.00 | 19.18 | 8.33 | 19.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45.83 | 19.17 | 41.00 | 19.66 | 3.50 | 25.61 | 2.83 | 24.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.17 | 20.40 | 9.00 | 20.40 | 1.17 | 26.11 | 0.83 | 24.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 98.50 | 14.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 73.50 | 14.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33.50 | 14.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2.17 | 14.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.33 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.71 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 27.82 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.70 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.61 | 0.00 | 0.00 |
October | 1.67 | 14.85 | 0.00 | 0.00 | 1.00 | 27.51 | 0.00 | 0.00 |
November | 35.67 | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 99.83 | 14.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 344.83 | 14.43 | 0.00 | 63.17 | 27.73 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 99.83 | 14.85 | 0.00 | 0.00 | 24.83 | 27.82 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.19 | 292.00 | 21.15 | 292.00 | 21.15 |
February | 276.00 | 21.36 | 241.50 | 21.12 | 241.50 | 21.12 |
March | 324.00 | 21.83 | 227.17 | 21.21 | 227.17 | 21.21 |
April | 297.17 | 22.94 | 84.17 | 21.27 | 84.17 | 21.27 |
May | 200.83 | 23.39 | 25.83 | 22.30 | 15.67 | 21.27 |
June | 35.67 | 23.62 | 184.00 | 23.89 | 0.00 | 0.00 |
July | 13.83 | 23.90 | 293.17 | 23.87 | 13.33 | 23.92 |
August | 14.50 | 23.76 | 314.17 | 23.88 | 12.17 | 23.91 |
September | 25.50 | 23.80 | 212.67 | 23.89 | 4.67 | 23.90 |
October | 205.67 | 22.84 | 112.33 | 22.68 | 50.67 | 21.20 |
November | 288.00 | 21.82 | 190.00 | 21.20 | 190.00 | 21.20 |
December | 300.00 | 21.14 | 290.33 | 21.09 | 290.33 | 21.09 |
Annual Sum or Average | 2281.17 | 22.05 | 2467.33 | 22.35 | 1421.67 | 21.22 |
Minimum of Months | 13.83 | 21.14 | 25.83 | 21.09 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 23.90 | 314.17 | 23.89 | 292.00 | 23.92 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 3468557.47 | 960312.66 | 6.17 | 3468557.47 | 0.00 | 0.00 | 0.06 | 14-FEB-16:00 | 0.00 | 01-FEB-00:02 | 1012.68 | 14-FEB-16:00 | 1012.68 | 14-FEB-16:00 | 0.00 | 01-FEB-00:02 | 279.63 | 14-FEB-16:00 | 0.00 | 01-FEB-00:02 |
March | 14094366.39 | 3879918.92 | 17.50 | 14094366.39 | 0.00 | 0.00 | 0.10 | 08-MAR-16:00 | 0.00 | 01-MAR-00:05 | 1811.86 | 08-MAR-16:00 | 1811.86 | 08-MAR-16:00 | 0.00 | 01-MAR-00:05 | 496.88 | 08-MAR-16:00 | 0.00 | 01-MAR-00:05 |
April | 0.980926E+09 | 0.265666E+09 | 121.00 | 0.980926E+09 | 10.32 | 0.00 | 0.38 | 13-APR-16:00 | 0.00 | 01-APR-00:10 | 6895.75 | 13-APR-16:00 | 6895.75 | 13-APR-16:00 | 0.01 | 15-APR-08:30 | 1874.59 | 13-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.277655E+10 | 0.761270E+09 | 191.53 | 0.276556E+10 | 10988176.66 | 0.00 | 1.00 | 19-MAY-05:03 | 0.00 | 01-MAY-00:10 | 20587.41 | 22-MAY-05:03 | 20294.96 | 19-MAY-05:03 | 4065.85 | 22-MAY-05:03 | 4878.17 | 22-MAY-05:03 | 0.00 | 01-MAY-00:10 |
June | 0.747630E+10 | 0.219166E+10 | 262.62 | 0.734831E+10 | 0.127984E+09 | 0.00 | 1.00 | 07-JUN-05:01 | 0.00 | 01-JUN-00:10 | 22208.62 | 29-JUN-05:01 | 20383.42 | 29-JUN-05:01 | 5336.30 | 24-JUN-05:08 | 5476.78 | 28-JUN-16:10 | 0.00 | 01-JUN-00:10 |
July | 0.105397E+11 | 0.301034E+10 | 287.60 | 0.951241E+10 | 0.102724E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 23107.79 | 01-JUL-05:01 | 20603.01 | 22-JUL-05:01 | 10086.11 | 01-JUL-05:30 | 5440.57 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.997671E+10 | 0.277581E+10 | 293.34 | 0.893268E+10 | 0.104404E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 23449.37 | 14-AUG-05:01 | 22221.66 | 13-AUG-17:51 | 10953.66 | 26-AUG-05:45 | 5829.53 | 13-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 0.596514E+10 | 0.162971E+10 | 234.72 | 0.557846E+10 | 0.386678E+09 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 22368.94 | 05-SEP-05:01 | 21614.44 | 04-SEP-17:04 | 9745.80 | 06-SEP-05:02 | 5505.14 | 04-SEP-17:04 | 0.00 | 01-SEP-00:10 |
October | 0.191278E+10 | 0.514657E+09 | 146.62 | 0.183192E+10 | 80863472.69 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 20854.45 | 02-OCT-05:01 | 18936.14 | 06-OCT-05:02 | 5434.53 | 03-OCT-05:03 | 4943.19 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 3683.58 | 1026.11 | 7.61 | 3683.58 | 0.00 | 0.00 | 0.00 | 02-NOV-15:00 | 0.00 | 01-NOV-00:10 | 0.64 | 02-NOV-15:00 | 0.64 | 02-NOV-15:00 | 0.00 | 02-NOV-13:50 | 0.18 | 02-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.396456E+11 | 0.111540E+11 | 1568.71 | 0.369678E+11 | 0.267779E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.105397E+11 | 0.301034E+10 | 293.34 | 0.951241E+10 | 0.104404E+10 | 0.00 | 1.00 | 0.00 | 23449.37 | 22221.66 | 10953.66 | 5829.53 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.171252E+09 | 51126815.07 | 21.17 | 0.171252E+09 | 0.00 | 0.00 | 0.13 | 28-APR-14:40 | 0.00 | 01-APR-00:10 | 6474.45 | 28-APR-14:40 | 6474.45 | 28-APR-14:40 | 0.00 | 13-APR-15:30 | 1910.23 | 28-APR-14:40 | 0.00 | 01-APR-00:10 |
May | 0.372064E+10 | 0.111575E+10 | 124.78 | 0.371559E+10 | 5050088.01 | 0.00 | 1.00 | 14-MAY-12:11 | 0.00 | 01-MAY-00:10 | 61559.77 | 28-MAY-12:21 | 59565.68 | 21-MAY-11:11 | 5606.30 | 28-MAY-12:28 | 15880.37 | 29-MAY-14:51 | 0.00 | 01-MAY-00:10 |
June | 0.195073E+11 | 0.629549E+10 | 267.34 | 0.193458E+11 | 0.161477E+09 | 0.00 | 1.00 | 03-JUN-17:23 | 0.00 | 01-JUN-00:10 | 63487.77 | 25-JUN-07:58 | 60336.30 | 28-JUN-23:10 | 9986.53 | 25-JUN-07:58 | 17956.11 | 25-JUN-15:43 | 0.00 | 01-JUN-00:10 |
July | 0.299273E+11 | 0.938117E+10 | 332.76 | 0.280811E+11 | 0.184628E+10 | 0.00 | 1.00 | 01-JUL-17:12 | 0.00 | 01-JUL-00:10 | 70181.80 | 01-JUL-17:12 | 60164.16 | 25-JUL-17:41 | 30571.74 | 01-JUL-17:12 | 18345.28 | 23-JUL-14:12 | 0.00 | 01-JUL-00:10 |
August | 0.252049E+11 | 0.768266E+10 | 307.60 | 0.235010E+11 | 0.170388E+10 | 0.00 | 1.00 | 01-AUG-17:05 | 0.00 | 01-AUG-00:10 | 69693.06 | 13-AUG-09:11 | 60671.27 | 06-AUG-11:21 | 28767.75 | 13-AUG-09:00 | 17902.07 | 20-AUG-15:02 | 0.00 | 01-AUG-00:10 |
September | 0.112392E+11 | 0.333020E+10 | 193.59 | 0.107143E+11 | 0.524890E+09 | 0.00 | 1.00 | 01-SEP-17:08 | 0.00 | 01-SEP-00:10 | 65515.59 | 04-SEP-10:31 | 60412.78 | 03-SEP-09:41 | 16674.09 | 10-SEP-11:11 | 17362.61 | 03-SEP-13:42 | 0.00 | 01-SEP-00:10 |
October | 0.216261E+10 | 0.634981E+09 | 63.66 | 0.211310E+10 | 49515255.90 | 0.00 | 1.00 | 01-OCT-10:21 | 0.00 | 01-OCT-00:10 | 60628.00 | 01-OCT-11:10 | 59939.92 | 01-OCT-13:01 | 3438.31 | 01-OCT-10:21 | 16268.83 | 01-OCT-13:41 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.919332E+11 | 0.284914E+11 | 1310.90 | 0.876421E+11 | 0.429109E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.299273E+11 | 0.938117E+10 | 332.76 | 0.280811E+11 | 0.184628E+10 | 0.00 | 1.00 | 0.00 | 70181.80 | 60671.27 | 30571.74 | 18345.28 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 125.88 | 71.74 | 54.15 | 98.95 | 153.20 | 0.00 | 0.00 | 744.00 |
February | 161.61 | 93.17 | 68.44 | 142.74 | 135.97 | 0.00 | 0.00 | 672.00 |
March | 181.25 | 96.51 | 84.74 | 175.78 | 103.28 | 0.00 | 0.00 | 744.00 |
April | 230.92 | 122.73 | 108.18 | 237.49 | 76.53 | 0.00 | 0.00 | 720.00 |
May | 220.04 | 113.67 | 106.36 | 233.62 | 66.42 | 0.00 | 0.00 | 744.00 |
June | 234.54 | 130.68 | 103.86 | 283.65 | 54.07 | 0.00 | 0.00 | 720.00 |
July | 211.95 | 103.72 | 108.23 | 263.26 | 40.94 | 0.00 | 0.00 | 744.00 |
August | 216.35 | 99.89 | 116.46 | 258.54 | 46.32 | 0.00 | 0.00 | 744.00 |
September | 196.32 | 103.64 | 92.68 | 219.34 | 69.84 | 0.00 | 0.00 | 720.00 |
October | 178.83 | 111.08 | 67.74 | 179.99 | 103.42 | 0.00 | 0.00 | 744.00 |
November | 140.28 | 82.43 | 57.85 | 118.53 | 121.40 | 0.00 | 0.00 | 720.00 |
December | 121.36 | 76.05 | 45.32 | 91.41 | 159.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 184.97 | 100.40 | 84.57 | 192.10 | 94.07 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 121.36 | 71.74 | 45.32 | 91.41 | 40.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 234.54 | 130.68 | 116.46 | 283.65 | 159.80 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 125.88 | 71.74 | 54.15 | 98.95 | 153.20 | 0.00 | 0.00 | 744.00 |
February | 161.61 | 93.17 | 68.44 | 142.74 | 135.97 | 0.00 | 0.00 | 672.00 |
March | 181.25 | 96.51 | 84.74 | 175.78 | 103.28 | 0.00 | 0.00 | 744.00 |
April | 230.92 | 122.73 | 108.18 | 237.49 | 76.53 | 0.00 | 0.00 | 720.00 |
May | 220.04 | 113.67 | 106.36 | 233.62 | 66.42 | 0.00 | 0.00 | 744.00 |
June | 234.54 | 130.68 | 103.86 | 283.65 | 54.07 | 0.00 | 0.00 | 720.00 |
July | 211.95 | 103.72 | 108.23 | 263.26 | 40.94 | 0.00 | 0.00 | 744.00 |
August | 216.35 | 99.89 | 116.46 | 258.54 | 46.32 | 0.00 | 0.00 | 744.00 |
September | 196.32 | 103.64 | 92.68 | 219.34 | 69.84 | 0.00 | 0.00 | 720.00 |
October | 178.83 | 111.08 | 67.74 | 179.99 | 103.42 | 0.00 | 0.00 | 744.00 |
November | 140.28 | 82.43 | 57.85 | 118.53 | 121.40 | 0.00 | 0.00 | 720.00 |
December | 121.36 | 76.05 | 45.32 | 91.41 | 159.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 184.97 | 100.40 | 84.57 | 192.10 | 94.07 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 121.36 | 71.74 | 45.32 | 91.41 | 40.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 234.54 | 130.68 | 116.46 | 283.65 | 159.80 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.74 | 0.00 | 25.74 | 3.97 | 93.95 | 0.00 | 0.00 | 744.00 |
February | 32.17 | 0.00 | 32.17 | 9.35 | 82.66 | 0.00 | 0.00 | 672.00 |
March | 40.58 | 0.00 | 40.58 | 22.26 | 61.88 | 0.00 | 0.00 | 744.00 |
April | 51.58 | 0.53 | 51.04 | 33.47 | 44.99 | 0.00 | 0.00 | 720.00 |
May | 56.07 | 3.69 | 52.38 | 41.10 | 37.68 | 0.00 | 0.00 | 744.00 |
June | 63.59 | 10.43 | 53.16 | 62.27 | 28.93 | 0.00 | 0.00 | 720.00 |
July | 58.22 | 4.72 | 53.50 | 67.01 | 22.74 | 0.00 | 0.00 | 744.00 |
August | 54.34 | 1.41 | 52.93 | 57.88 | 26.09 | 0.00 | 0.00 | 744.00 |
September | 43.32 | 0.03 | 43.30 | 38.29 | 41.11 | 0.00 | 0.00 | 720.00 |
October | 32.30 | 0.00 | 32.30 | 15.70 | 62.17 | 0.00 | 0.00 | 744.00 |
November | 27.43 | 0.00 | 27.43 | 5.56 | 74.99 | 0.00 | 0.00 | 720.00 |
December | 21.91 | 0.00 | 21.91 | 0.95 | 100.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 42.31 | 1.74 | 40.57 | 29.93 | 56.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.91 | 0.00 | 21.91 | 0.95 | 22.74 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 63.59 | 10.43 | 53.50 | 67.01 | 100.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.74 | 0.00 | 25.74 | 3.97 | 93.95 | 0.00 | 0.00 | 744.00 |
February | 32.16 | 0.00 | 32.16 | 9.35 | 82.65 | 0.00 | 0.00 | 672.00 |
March | 40.58 | 0.00 | 40.58 | 22.26 | 61.88 | 0.00 | 0.00 | 744.00 |
April | 51.58 | 0.53 | 51.04 | 33.47 | 44.98 | 0.00 | 0.00 | 720.00 |
May | 56.07 | 3.69 | 52.38 | 41.10 | 37.68 | 0.00 | 0.00 | 744.00 |
June | 63.59 | 10.43 | 53.16 | 62.27 | 28.93 | 0.00 | 0.00 | 720.00 |
July | 58.22 | 4.72 | 53.50 | 67.01 | 22.74 | 0.00 | 0.00 | 744.00 |
August | 54.34 | 1.41 | 52.93 | 57.88 | 26.09 | 0.00 | 0.00 | 744.00 |
September | 43.32 | 0.03 | 43.30 | 38.29 | 41.11 | 0.00 | 0.00 | 720.00 |
October | 32.30 | 0.00 | 32.30 | 15.70 | 62.17 | 0.00 | 0.00 | 744.00 |
November | 27.43 | 0.00 | 27.43 | 5.56 | 74.99 | 0.00 | 0.00 | 720.00 |
December | 21.90 | 0.00 | 21.90 | 0.95 | 100.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 42.31 | 1.74 | 40.57 | 29.93 | 56.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.90 | 0.00 | 21.90 | 0.95 | 22.74 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 63.59 | 10.43 | 53.50 | 67.01 | 100.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.23 | 30.43 | 14.80 | 36.56 | 42.33 | 0.00 | 0.00 | 744.00 |
February | 62.65 | 44.32 | 18.33 | 59.89 | 37.54 | 0.00 | 0.00 | 672.00 |
March | 82.79 | 57.55 | 25.24 | 88.38 | 31.66 | 0.00 | 0.00 | 744.00 |
April | 112.15 | 81.14 | 31.01 | 123.42 | 29.62 | 0.00 | 0.00 | 720.00 |
May | 122.65 | 93.11 | 29.54 | 137.99 | 29.27 | 0.00 | 0.00 | 744.00 |
June | 130.08 | 103.12 | 26.96 | 148.96 | 29.18 | 0.00 | 0.00 | 720.00 |
July | 126.67 | 95.96 | 30.71 | 147.43 | 26.00 | 0.00 | 0.00 | 744.00 |
August | 118.32 | 85.53 | 32.78 | 134.50 | 26.22 | 0.00 | 0.00 | 744.00 |
September | 95.75 | 70.27 | 25.48 | 103.55 | 33.54 | 0.00 | 0.00 | 720.00 |
October | 71.42 | 55.40 | 16.01 | 68.26 | 41.58 | 0.00 | 0.00 | 744.00 |
November | 49.31 | 34.31 | 15.00 | 40.14 | 38.45 | 0.00 | 0.00 | 720.00 |
December | 39.59 | 29.15 | 10.44 | 26.58 | 44.35 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 88.16 | 65.12 | 23.05 | 93.12 | 34.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 39.59 | 29.15 | 10.44 | 26.58 | 26.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.08 | 103.12 | 32.78 | 148.96 | 44.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.23 | 30.43 | 14.80 | 36.56 | 42.33 | 0.00 | 0.00 | 744.00 |
February | 62.65 | 44.32 | 18.33 | 59.89 | 37.54 | 0.00 | 0.00 | 672.00 |
March | 82.79 | 57.55 | 25.24 | 88.38 | 31.66 | 0.00 | 0.00 | 744.00 |
April | 112.15 | 81.14 | 31.01 | 123.42 | 29.62 | 0.00 | 0.00 | 720.00 |
May | 122.65 | 93.11 | 29.54 | 137.99 | 29.27 | 0.00 | 0.00 | 744.00 |
June | 130.08 | 103.12 | 26.96 | 148.96 | 29.18 | 0.00 | 0.00 | 720.00 |
July | 126.67 | 95.96 | 30.71 | 147.43 | 26.00 | 0.00 | 0.00 | 744.00 |
August | 118.32 | 85.53 | 32.78 | 134.50 | 26.22 | 0.00 | 0.00 | 744.00 |
September | 95.75 | 70.27 | 25.48 | 103.55 | 33.54 | 0.00 | 0.00 | 720.00 |
October | 71.42 | 55.40 | 16.01 | 68.26 | 41.58 | 0.00 | 0.00 | 744.00 |
November | 49.31 | 34.31 | 15.00 | 40.14 | 38.45 | 0.00 | 0.00 | 720.00 |
December | 39.59 | 29.15 | 10.44 | 26.58 | 44.35 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 88.16 | 65.12 | 23.05 | 93.12 | 34.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 39.59 | 29.15 | 10.44 | 26.58 | 26.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.08 | 103.12 | 32.78 | 148.96 | 44.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.23 | 30.43 | 14.80 | 36.56 | 42.33 | 0.00 | 0.00 | 744.00 |
February | 62.65 | 44.32 | 18.33 | 59.89 | 37.54 | 0.00 | 0.00 | 672.00 |
March | 82.79 | 57.55 | 25.24 | 88.38 | 31.66 | 0.00 | 0.00 | 744.00 |
April | 112.15 | 81.14 | 31.01 | 123.42 | 29.62 | 0.00 | 0.00 | 720.00 |
May | 122.65 | 93.11 | 29.54 | 137.99 | 29.27 | 0.00 | 0.00 | 744.00 |
June | 130.08 | 103.12 | 26.96 | 148.96 | 29.18 | 0.00 | 0.00 | 720.00 |
July | 126.67 | 95.96 | 30.71 | 147.43 | 26.00 | 0.00 | 0.00 | 744.00 |
August | 118.32 | 85.53 | 32.78 | 134.50 | 26.22 | 0.00 | 0.00 | 744.00 |
September | 95.75 | 70.27 | 25.48 | 103.55 | 33.54 | 0.00 | 0.00 | 720.00 |
October | 71.42 | 55.40 | 16.01 | 68.26 | 41.58 | 0.00 | 0.00 | 744.00 |
November | 49.31 | 34.31 | 15.00 | 40.14 | 38.45 | 0.00 | 0.00 | 720.00 |
December | 39.59 | 29.15 | 10.44 | 26.58 | 44.35 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 88.16 | 65.12 | 23.05 | 93.12 | 34.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 39.59 | 29.15 | 10.44 | 26.58 | 26.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.08 | 103.12 | 32.78 | 148.96 | 44.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.23 | 30.43 | 14.80 | 36.56 | 42.33 | 0.00 | 0.00 | 744.00 |
February | 62.65 | 44.32 | 18.33 | 59.89 | 37.54 | 0.00 | 0.00 | 672.00 |
March | 82.79 | 57.55 | 25.24 | 88.38 | 31.66 | 0.00 | 0.00 | 744.00 |
April | 112.15 | 81.14 | 31.01 | 123.42 | 29.62 | 0.00 | 0.00 | 720.00 |
May | 122.65 | 93.11 | 29.54 | 137.99 | 29.27 | 0.00 | 0.00 | 744.00 |
June | 130.08 | 103.12 | 26.96 | 148.96 | 29.18 | 0.00 | 0.00 | 720.00 |
July | 126.67 | 95.96 | 30.71 | 147.43 | 26.00 | 0.00 | 0.00 | 744.00 |
August | 118.32 | 85.53 | 32.78 | 134.50 | 26.22 | 0.00 | 0.00 | 744.00 |
September | 95.75 | 70.27 | 25.48 | 103.55 | 33.54 | 0.00 | 0.00 | 720.00 |
October | 71.42 | 55.40 | 16.01 | 68.26 | 41.58 | 0.00 | 0.00 | 744.00 |
November | 49.31 | 34.31 | 15.00 | 40.14 | 38.45 | 0.00 | 0.00 | 720.00 |
December | 39.59 | 29.15 | 10.44 | 26.58 | 44.35 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 88.16 | 65.12 | 23.05 | 93.12 | 34.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 39.59 | 29.15 | 10.44 | 26.58 | 26.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.08 | 103.12 | 32.78 | 148.96 | 44.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.23 | 30.43 | 14.80 | 36.56 | 42.33 | 0.00 | 0.00 | 744.00 |
February | 62.65 | 44.32 | 18.33 | 59.89 | 37.54 | 0.00 | 0.00 | 672.00 |
March | 82.79 | 57.55 | 25.24 | 88.38 | 31.66 | 0.00 | 0.00 | 744.00 |
April | 112.15 | 81.14 | 31.01 | 123.42 | 29.62 | 0.00 | 0.00 | 720.00 |
May | 122.65 | 93.11 | 29.54 | 137.99 | 29.27 | 0.00 | 0.00 | 744.00 |
June | 130.08 | 103.12 | 26.96 | 148.96 | 29.18 | 0.00 | 0.00 | 720.00 |
July | 126.67 | 95.96 | 30.71 | 147.43 | 26.00 | 0.00 | 0.00 | 744.00 |
August | 118.32 | 85.53 | 32.78 | 134.50 | 26.22 | 0.00 | 0.00 | 744.00 |
September | 95.75 | 70.27 | 25.48 | 103.55 | 33.54 | 0.00 | 0.00 | 720.00 |
October | 71.42 | 55.40 | 16.01 | 68.26 | 41.58 | 0.00 | 0.00 | 744.00 |
November | 49.31 | 34.31 | 15.00 | 40.14 | 38.45 | 0.00 | 0.00 | 720.00 |
December | 39.59 | 29.15 | 10.44 | 26.58 | 44.35 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 88.16 | 65.12 | 23.05 | 93.12 | 34.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 39.59 | 29.15 | 10.44 | 26.58 | 26.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.08 | 103.12 | 32.78 | 148.96 | 44.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.23 | 30.43 | 14.80 | 36.56 | 42.33 | 0.00 | 0.00 | 744.00 |
February | 62.65 | 44.32 | 18.33 | 59.89 | 37.54 | 0.00 | 0.00 | 672.00 |
March | 82.79 | 57.55 | 25.24 | 88.38 | 31.66 | 0.00 | 0.00 | 744.00 |
April | 112.15 | 81.14 | 31.01 | 123.42 | 29.62 | 0.00 | 0.00 | 720.00 |
May | 122.65 | 93.11 | 29.54 | 137.99 | 29.27 | 0.00 | 0.00 | 744.00 |
June | 130.08 | 103.12 | 26.96 | 148.96 | 29.18 | 0.00 | 0.00 | 720.00 |
July | 126.67 | 95.96 | 30.71 | 147.43 | 26.00 | 0.00 | 0.00 | 744.00 |
August | 118.32 | 85.53 | 32.78 | 134.50 | 26.22 | 0.00 | 0.00 | 744.00 |
September | 95.75 | 70.27 | 25.48 | 103.55 | 33.54 | 0.00 | 0.00 | 720.00 |
October | 71.42 | 55.40 | 16.01 | 68.26 | 41.58 | 0.00 | 0.00 | 744.00 |
November | 49.31 | 34.31 | 15.00 | 40.14 | 38.45 | 0.00 | 0.00 | 720.00 |
December | 39.59 | 29.15 | 10.44 | 26.58 | 44.35 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 88.16 | 65.12 | 23.05 | 93.12 | 34.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 39.59 | 29.15 | 10.44 | 26.58 | 26.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.08 | 103.12 | 32.78 | 148.96 | 44.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.23 | 30.43 | 14.80 | 36.56 | 42.33 | 0.00 | 0.00 | 744.00 |
February | 62.65 | 44.32 | 18.33 | 59.89 | 37.54 | 0.00 | 0.00 | 672.00 |
March | 82.79 | 57.55 | 25.24 | 88.38 | 31.66 | 0.00 | 0.00 | 744.00 |
April | 112.15 | 81.14 | 31.01 | 123.42 | 29.62 | 0.00 | 0.00 | 720.00 |
May | 122.65 | 93.11 | 29.54 | 137.99 | 29.27 | 0.00 | 0.00 | 744.00 |
June | 130.08 | 103.12 | 26.96 | 148.96 | 29.18 | 0.00 | 0.00 | 720.00 |
July | 126.67 | 95.96 | 30.71 | 147.43 | 26.00 | 0.00 | 0.00 | 744.00 |
August | 118.32 | 85.53 | 32.78 | 134.50 | 26.22 | 0.00 | 0.00 | 744.00 |
September | 95.75 | 70.27 | 25.48 | 103.55 | 33.54 | 0.00 | 0.00 | 720.00 |
October | 71.42 | 55.40 | 16.01 | 68.26 | 41.58 | 0.00 | 0.00 | 744.00 |
November | 49.31 | 34.31 | 15.00 | 40.14 | 38.45 | 0.00 | 0.00 | 720.00 |
December | 39.59 | 29.15 | 10.44 | 26.58 | 44.35 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 88.16 | 65.12 | 23.05 | 93.12 | 34.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 39.59 | 29.15 | 10.44 | 26.58 | 26.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.08 | 103.12 | 32.78 | 148.96 | 44.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.23 | 30.43 | 14.80 | 36.56 | 42.33 | 0.00 | 0.00 | 744.00 |
February | 62.65 | 44.32 | 18.33 | 59.89 | 37.54 | 0.00 | 0.00 | 672.00 |
March | 82.79 | 57.55 | 25.24 | 88.38 | 31.66 | 0.00 | 0.00 | 744.00 |
April | 112.15 | 81.14 | 31.01 | 123.42 | 29.62 | 0.00 | 0.00 | 720.00 |
May | 122.65 | 93.11 | 29.54 | 137.99 | 29.27 | 0.00 | 0.00 | 744.00 |
June | 130.08 | 103.12 | 26.96 | 148.96 | 29.18 | 0.00 | 0.00 | 720.00 |
July | 126.67 | 95.96 | 30.71 | 147.43 | 26.00 | 0.00 | 0.00 | 744.00 |
August | 118.32 | 85.53 | 32.78 | 134.50 | 26.22 | 0.00 | 0.00 | 744.00 |
September | 95.75 | 70.27 | 25.48 | 103.55 | 33.54 | 0.00 | 0.00 | 720.00 |
October | 71.42 | 55.40 | 16.01 | 68.26 | 41.58 | 0.00 | 0.00 | 744.00 |
November | 49.31 | 34.31 | 15.00 | 40.14 | 38.45 | 0.00 | 0.00 | 720.00 |
December | 39.59 | 29.15 | 10.44 | 26.58 | 44.35 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 88.16 | 65.12 | 23.05 | 93.12 | 34.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 39.59 | 29.15 | 10.44 | 26.58 | 26.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.08 | 103.12 | 32.78 | 148.96 | 44.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.23 | 30.43 | 14.80 | 36.56 | 42.33 | 0.00 | 0.00 | 744.00 |
February | 62.65 | 44.32 | 18.33 | 59.89 | 37.54 | 0.00 | 0.00 | 672.00 |
March | 82.79 | 57.55 | 25.24 | 88.38 | 31.66 | 0.00 | 0.00 | 744.00 |
April | 112.15 | 81.14 | 31.01 | 123.42 | 29.62 | 0.00 | 0.00 | 720.00 |
May | 122.65 | 93.11 | 29.54 | 137.99 | 29.27 | 0.00 | 0.00 | 744.00 |
June | 130.08 | 103.12 | 26.96 | 148.96 | 29.18 | 0.00 | 0.00 | 720.00 |
July | 126.67 | 95.96 | 30.71 | 147.43 | 26.00 | 0.00 | 0.00 | 744.00 |
August | 118.32 | 85.53 | 32.78 | 134.50 | 26.22 | 0.00 | 0.00 | 744.00 |
September | 95.75 | 70.27 | 25.48 | 103.55 | 33.54 | 0.00 | 0.00 | 720.00 |
October | 71.42 | 55.40 | 16.01 | 68.26 | 41.58 | 0.00 | 0.00 | 744.00 |
November | 49.31 | 34.31 | 15.00 | 40.14 | 38.45 | 0.00 | 0.00 | 720.00 |
December | 39.59 | 29.15 | 10.44 | 26.58 | 44.35 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 88.16 | 65.12 | 23.05 | 93.12 | 34.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 39.59 | 29.15 | 10.44 | 26.58 | 26.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.08 | 103.12 | 32.78 | 148.96 | 44.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 45.23 | 30.43 | 14.80 | 36.56 | 42.33 | 0.00 | 0.00 | 744.00 |
February | 62.65 | 44.32 | 18.33 | 59.89 | 37.54 | 0.00 | 0.00 | 672.00 |
March | 82.79 | 57.55 | 25.24 | 88.38 | 31.66 | 0.00 | 0.00 | 744.00 |
April | 112.15 | 81.14 | 31.01 | 123.42 | 29.62 | 0.00 | 0.00 | 720.00 |
May | 122.65 | 93.11 | 29.54 | 137.99 | 29.27 | 0.00 | 0.00 | 744.00 |
June | 130.08 | 103.12 | 26.96 | 148.96 | 29.18 | 0.00 | 0.00 | 720.00 |
July | 126.67 | 95.96 | 30.71 | 147.43 | 26.00 | 0.00 | 0.00 | 744.00 |
August | 118.32 | 85.53 | 32.78 | 134.50 | 26.22 | 0.00 | 0.00 | 744.00 |
September | 95.75 | 70.27 | 25.48 | 103.55 | 33.54 | 0.00 | 0.00 | 720.00 |
October | 71.42 | 55.40 | 16.01 | 68.26 | 41.58 | 0.00 | 0.00 | 744.00 |
November | 49.31 | 34.31 | 15.00 | 40.14 | 38.45 | 0.00 | 0.00 | 720.00 |
December | 39.59 | 29.15 | 10.44 | 26.58 | 44.35 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 88.16 | 65.12 | 23.05 | 93.12 | 34.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 39.59 | 29.15 | 10.44 | 26.58 | 26.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 130.08 | 103.12 | 32.78 | 148.96 | 44.35 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.337166E+09 | 0.192143E+09 | 0.145023E+09 | 0.265037E+09 | 0.410337E+09 |
February | 0.390959E+09 | 0.225397E+09 | 0.165563E+09 | 0.345306E+09 | 0.328933E+09 |
March | 0.485470E+09 | 0.258489E+09 | 0.226980E+09 | 0.470819E+09 | 0.276614E+09 |
April | 0.598536E+09 | 0.318125E+09 | 0.280411E+09 | 0.615583E+09 | 0.198358E+09 |
May | 0.589345E+09 | 0.304465E+09 | 0.284879E+09 | 0.625740E+09 | 0.177898E+09 |
June | 0.607938E+09 | 0.338724E+09 | 0.269214E+09 | 0.735226E+09 | 0.140160E+09 |
July | 0.567688E+09 | 0.277808E+09 | 0.289880E+09 | 0.705127E+09 | 0.109650E+09 |
August | 0.579472E+09 | 0.267546E+09 | 0.311926E+09 | 0.692482E+09 | 0.124070E+09 |
September | 0.508869E+09 | 0.268630E+09 | 0.240239E+09 | 0.568521E+09 | 0.181017E+09 |
October | 0.478967E+09 | 0.297520E+09 | 0.181446E+09 | 0.482092E+09 | 0.277009E+09 |
November | 0.363617E+09 | 0.213661E+09 | 0.149956E+09 | 0.307241E+09 | 0.314661E+09 |
December | 0.325057E+09 | 0.203680E+09 | 0.121377E+09 | 0.244840E+09 | 0.428007E+09 |
Annual Sum or Average | 0.583308E+10 | 0.316619E+10 | 0.266690E+10 | 0.605801E+10 | 0.296671E+10 |
Minimum of Months | 0.325057E+09 | 0.192143E+09 | 0.121377E+09 | 0.244840E+09 | 0.109650E+09 |
Maximum of Months | 0.607938E+09 | 0.338724E+09 | 0.311926E+09 | 0.735226E+09 | 0.428007E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.337166E+09 | 0.192143E+09 | 0.145023E+09 | 0.265037E+09 | 0.410337E+09 |
February | 0.390959E+09 | 0.225397E+09 | 0.165563E+09 | 0.345306E+09 | 0.328933E+09 |
March | 0.485470E+09 | 0.258489E+09 | 0.226980E+09 | 0.470819E+09 | 0.276614E+09 |
April | 0.598536E+09 | 0.318125E+09 | 0.280411E+09 | 0.615583E+09 | 0.198358E+09 |
May | 0.589345E+09 | 0.304465E+09 | 0.284879E+09 | 0.625740E+09 | 0.177898E+09 |
June | 0.607938E+09 | 0.338724E+09 | 0.269214E+09 | 0.735226E+09 | 0.140160E+09 |
July | 0.567688E+09 | 0.277808E+09 | 0.289880E+09 | 0.705127E+09 | 0.109650E+09 |
August | 0.579472E+09 | 0.267546E+09 | 0.311926E+09 | 0.692482E+09 | 0.124070E+09 |
September | 0.508869E+09 | 0.268630E+09 | 0.240239E+09 | 0.568521E+09 | 0.181017E+09 |
October | 0.478967E+09 | 0.297520E+09 | 0.181446E+09 | 0.482092E+09 | 0.277009E+09 |
November | 0.363617E+09 | 0.213661E+09 | 0.149956E+09 | 0.307241E+09 | 0.314661E+09 |
December | 0.325057E+09 | 0.203680E+09 | 0.121377E+09 | 0.244840E+09 | 0.428007E+09 |
Annual Sum or Average | 0.583308E+10 | 0.316619E+10 | 0.266690E+10 | 0.605801E+10 | 0.296671E+10 |
Minimum of Months | 0.325057E+09 | 0.192143E+09 | 0.121377E+09 | 0.244840E+09 | 0.109650E+09 |
Maximum of Months | 0.607938E+09 | 0.338724E+09 | 0.311926E+09 | 0.735226E+09 | 0.428007E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68931094.17 | 0.00 | 68931094.17 | 10625169.84 | 0.251625E+09 |
February | 77814968.69 | 0.00 | 77814968.69 | 22631287.84 | 0.199959E+09 |
March | 0.108700E+09 | 10134.22 | 0.108690E+09 | 59611890.50 | 0.165753E+09 |
April | 0.133686E+09 | 1379548.00 | 0.132306E+09 | 86755962.87 | 0.116601E+09 |
May | 0.150189E+09 | 9895483.65 | 0.140293E+09 | 0.110095E+09 | 0.100928E+09 |
June | 0.164824E+09 | 27026120.96 | 0.137798E+09 | 0.161412E+09 | 74988333.72 |
July | 0.155934E+09 | 12629418.14 | 0.143305E+09 | 0.179480E+09 | 60894407.93 |
August | 0.145539E+09 | 3774478.35 | 0.141764E+09 | 0.155036E+09 | 69886514.99 |
September | 0.112298E+09 | 65597.29 | 0.112232E+09 | 99242738.68 | 0.106552E+09 |
October | 86520339.15 | 0.00 | 86520339.15 | 42063134.50 | 0.166506E+09 |
November | 71106036.44 | 0.00 | 71106036.44 | 14413416.54 | 0.194379E+09 |
December | 58670776.91 | 0.00 | 58670776.91 | 2532865.28 | 0.268890E+09 |
Annual Sum or Average | 0.133421E+10 | 54780780.61 | 0.127943E+10 | 0.943899E+09 | 0.177696E+10 |
Minimum of Months | 58670776.91 | 0.00 | 58670776.91 | 2532865.28 | 60894407.93 |
Maximum of Months | 0.164824E+09 | 27026120.96 | 0.143305E+09 | 0.179480E+09 | 0.268890E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68929217.15 | 0.00 | 68929217.15 | 10624438.75 | 0.251624E+09 |
February | 77812936.66 | 0.00 | 77812936.66 | 22630135.83 | 0.199959E+09 |
March | 0.108697E+09 | 10133.75 | 0.108687E+09 | 59609676.26 | 0.165752E+09 |
April | 0.133683E+09 | 1379483.34 | 0.132303E+09 | 86753359.00 | 0.116600E+09 |
May | 0.150185E+09 | 9895019.83 | 0.140290E+09 | 0.110092E+09 | 0.100927E+09 |
June | 0.164819E+09 | 27024854.21 | 0.137795E+09 | 0.161408E+09 | 74987477.92 |
July | 0.155930E+09 | 12628826.18 | 0.143301E+09 | 0.179476E+09 | 60893603.92 |
August | 0.145535E+09 | 3774301.43 | 0.141761E+09 | 0.155033E+09 | 69885808.16 |
September | 0.112295E+09 | 65594.22 | 0.112229E+09 | 99240422.41 | 0.106551E+09 |
October | 86518266.99 | 0.00 | 86518266.99 | 42061948.94 | 0.166505E+09 |
November | 71104140.86 | 0.00 | 71104140.86 | 14412440.82 | 0.194379E+09 |
December | 58669292.31 | 0.00 | 58669292.31 | 2532589.76 | 0.268889E+09 |
Annual Sum or Average | 0.133418E+10 | 54778212.96 | 0.127940E+10 | 0.943875E+09 | 0.177695E+10 |
Minimum of Months | 58669292.31 | 0.00 | 58669292.31 | 2532589.76 | 60893603.92 |
Maximum of Months | 0.164819E+09 | 27024854.21 | 0.143301E+09 | 0.179476E+09 | 0.268889E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121148E+09 | 81510555.90 | 39637924.05 | 97926658.93 | 0.113390E+09 |
February | 0.151551E+09 | 0.107215E+09 | 44336622.51 | 0.144874E+09 | 90821004.62 |
March | 0.221749E+09 | 0.154149E+09 | 67599804.72 | 0.236729E+09 | 84807568.66 |
April | 0.290699E+09 | 0.210321E+09 | 80377735.84 | 0.319907E+09 | 76778300.35 |
May | 0.328518E+09 | 0.249391E+09 | 79127325.63 | 0.369592E+09 | 78400962.93 |
June | 0.337166E+09 | 0.267292E+09 | 69873425.29 | 0.386097E+09 | 75628087.84 |
July | 0.339260E+09 | 0.257009E+09 | 82251489.17 | 0.394878E+09 | 69638163.68 |
August | 0.316898E+09 | 0.229089E+09 | 87808519.44 | 0.360233E+09 | 70237600.90 |
September | 0.248183E+09 | 0.182141E+09 | 66042866.25 | 0.268400E+09 | 86930900.03 |
October | 0.191287E+09 | 0.148397E+09 | 42890376.68 | 0.182826E+09 | 0.111379E+09 |
November | 0.127818E+09 | 88938177.66 | 38879950.26 | 0.104033E+09 | 99661279.39 |
December | 0.106026E+09 | 78068651.04 | 27957119.65 | 71180590.93 | 0.118795E+09 |
Annual Sum or Average | 0.278030E+10 | 0.205352E+10 | 0.726783E+09 | 0.293668E+10 | 0.107647E+10 |
Minimum of Months | 0.106026E+09 | 78068651.04 | 27957119.65 | 71180590.93 | 69638163.68 |
Maximum of Months | 0.339260E+09 | 0.267292E+09 | 87808519.44 | 0.394878E+09 | 0.118795E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121148E+09 | 81510555.90 | 39637924.05 | 97926658.93 | 0.113390E+09 |
February | 0.151551E+09 | 0.107215E+09 | 44336622.51 | 0.144874E+09 | 90821004.62 |
March | 0.221749E+09 | 0.154149E+09 | 67599804.72 | 0.236729E+09 | 84807568.66 |
April | 0.290699E+09 | 0.210321E+09 | 80377735.84 | 0.319907E+09 | 76778300.35 |
May | 0.328518E+09 | 0.249391E+09 | 79127325.63 | 0.369592E+09 | 78400962.93 |
June | 0.337166E+09 | 0.267292E+09 | 69873425.29 | 0.386097E+09 | 75628087.84 |
July | 0.339260E+09 | 0.257009E+09 | 82251489.17 | 0.394878E+09 | 69638163.68 |
August | 0.316898E+09 | 0.229089E+09 | 87808519.44 | 0.360233E+09 | 70237600.90 |
September | 0.248183E+09 | 0.182141E+09 | 66042866.25 | 0.268400E+09 | 86930900.03 |
October | 0.191287E+09 | 0.148397E+09 | 42890376.68 | 0.182826E+09 | 0.111379E+09 |
November | 0.127818E+09 | 88938177.66 | 38879950.26 | 0.104033E+09 | 99661279.39 |
December | 0.106026E+09 | 78068651.04 | 27957119.65 | 71180590.93 | 0.118795E+09 |
Annual Sum or Average | 0.278030E+10 | 0.205352E+10 | 0.726783E+09 | 0.293668E+10 | 0.107647E+10 |
Minimum of Months | 0.106026E+09 | 78068651.04 | 27957119.65 | 71180590.93 | 69638163.68 |
Maximum of Months | 0.339260E+09 | 0.267292E+09 | 87808519.44 | 0.394878E+09 | 0.118795E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121148E+09 | 81510555.90 | 39637924.05 | 97926658.93 | 0.113390E+09 |
February | 0.151551E+09 | 0.107215E+09 | 44336622.51 | 0.144874E+09 | 90821004.62 |
March | 0.221749E+09 | 0.154149E+09 | 67599804.72 | 0.236729E+09 | 84807568.66 |
April | 0.290699E+09 | 0.210321E+09 | 80377735.84 | 0.319907E+09 | 76778300.35 |
May | 0.328518E+09 | 0.249391E+09 | 79127325.63 | 0.369592E+09 | 78400962.93 |
June | 0.337166E+09 | 0.267292E+09 | 69873425.29 | 0.386097E+09 | 75628087.84 |
July | 0.339260E+09 | 0.257009E+09 | 82251489.17 | 0.394878E+09 | 69638163.68 |
August | 0.316898E+09 | 0.229089E+09 | 87808519.44 | 0.360233E+09 | 70237600.90 |
September | 0.248183E+09 | 0.182141E+09 | 66042866.25 | 0.268400E+09 | 86930900.03 |
October | 0.191287E+09 | 0.148397E+09 | 42890376.68 | 0.182826E+09 | 0.111379E+09 |
November | 0.127818E+09 | 88938177.66 | 38879950.26 | 0.104033E+09 | 99661279.39 |
December | 0.106026E+09 | 78068651.04 | 27957119.65 | 71180590.93 | 0.118795E+09 |
Annual Sum or Average | 0.278030E+10 | 0.205352E+10 | 0.726783E+09 | 0.293668E+10 | 0.107647E+10 |
Minimum of Months | 0.106026E+09 | 78068651.04 | 27957119.65 | 71180590.93 | 69638163.68 |
Maximum of Months | 0.339260E+09 | 0.267292E+09 | 87808519.44 | 0.394878E+09 | 0.118795E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121148E+09 | 81510555.90 | 39637924.05 | 97926658.93 | 0.113390E+09 |
February | 0.151551E+09 | 0.107215E+09 | 44336622.51 | 0.144874E+09 | 90821004.62 |
March | 0.221749E+09 | 0.154149E+09 | 67599804.72 | 0.236729E+09 | 84807568.66 |
April | 0.290699E+09 | 0.210321E+09 | 80377735.84 | 0.319907E+09 | 76778300.35 |
May | 0.328518E+09 | 0.249391E+09 | 79127325.63 | 0.369592E+09 | 78400962.93 |
June | 0.337166E+09 | 0.267292E+09 | 69873425.29 | 0.386097E+09 | 75628087.84 |
July | 0.339260E+09 | 0.257009E+09 | 82251489.17 | 0.394878E+09 | 69638163.68 |
August | 0.316898E+09 | 0.229089E+09 | 87808519.44 | 0.360233E+09 | 70237600.90 |
September | 0.248183E+09 | 0.182141E+09 | 66042866.25 | 0.268400E+09 | 86930900.03 |
October | 0.191287E+09 | 0.148397E+09 | 42890376.68 | 0.182826E+09 | 0.111379E+09 |
November | 0.127818E+09 | 88938177.66 | 38879950.26 | 0.104033E+09 | 99661279.39 |
December | 0.106026E+09 | 78068651.04 | 27957119.65 | 71180590.93 | 0.118795E+09 |
Annual Sum or Average | 0.278030E+10 | 0.205352E+10 | 0.726783E+09 | 0.293668E+10 | 0.107647E+10 |
Minimum of Months | 0.106026E+09 | 78068651.04 | 27957119.65 | 71180590.93 | 69638163.68 |
Maximum of Months | 0.339260E+09 | 0.267292E+09 | 87808519.44 | 0.394878E+09 | 0.118795E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121148E+09 | 81510555.90 | 39637924.05 | 97926658.93 | 0.113390E+09 |
February | 0.151551E+09 | 0.107215E+09 | 44336622.51 | 0.144874E+09 | 90821004.62 |
March | 0.221749E+09 | 0.154149E+09 | 67599804.72 | 0.236729E+09 | 84807568.66 |
April | 0.290699E+09 | 0.210321E+09 | 80377735.84 | 0.319907E+09 | 76778300.35 |
May | 0.328518E+09 | 0.249391E+09 | 79127325.63 | 0.369592E+09 | 78400962.93 |
June | 0.337166E+09 | 0.267292E+09 | 69873425.29 | 0.386097E+09 | 75628087.84 |
July | 0.339260E+09 | 0.257009E+09 | 82251489.17 | 0.394878E+09 | 69638163.68 |
August | 0.316898E+09 | 0.229089E+09 | 87808519.44 | 0.360233E+09 | 70237600.90 |
September | 0.248183E+09 | 0.182141E+09 | 66042866.25 | 0.268400E+09 | 86930900.03 |
October | 0.191287E+09 | 0.148397E+09 | 42890376.68 | 0.182826E+09 | 0.111379E+09 |
November | 0.127818E+09 | 88938177.66 | 38879950.26 | 0.104033E+09 | 99661279.39 |
December | 0.106026E+09 | 78068651.04 | 27957119.65 | 71180590.93 | 0.118795E+09 |
Annual Sum or Average | 0.278030E+10 | 0.205352E+10 | 0.726783E+09 | 0.293668E+10 | 0.107647E+10 |
Minimum of Months | 0.106026E+09 | 78068651.04 | 27957119.65 | 71180590.93 | 69638163.68 |
Maximum of Months | 0.339260E+09 | 0.267292E+09 | 87808519.44 | 0.394878E+09 | 0.118795E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121148E+09 | 81510555.90 | 39637924.05 | 97926658.93 | 0.113390E+09 |
February | 0.151551E+09 | 0.107215E+09 | 44336622.51 | 0.144874E+09 | 90821004.62 |
March | 0.221749E+09 | 0.154149E+09 | 67599804.72 | 0.236729E+09 | 84807568.66 |
April | 0.290699E+09 | 0.210321E+09 | 80377735.84 | 0.319907E+09 | 76778300.35 |
May | 0.328518E+09 | 0.249391E+09 | 79127325.63 | 0.369592E+09 | 78400962.93 |
June | 0.337166E+09 | 0.267292E+09 | 69873425.29 | 0.386097E+09 | 75628087.84 |
July | 0.339260E+09 | 0.257009E+09 | 82251489.17 | 0.394878E+09 | 69638163.68 |
August | 0.316898E+09 | 0.229089E+09 | 87808519.44 | 0.360233E+09 | 70237600.90 |
September | 0.248183E+09 | 0.182141E+09 | 66042866.25 | 0.268400E+09 | 86930900.03 |
October | 0.191287E+09 | 0.148397E+09 | 42890376.68 | 0.182826E+09 | 0.111379E+09 |
November | 0.127818E+09 | 88938177.66 | 38879950.26 | 0.104033E+09 | 99661279.39 |
December | 0.106026E+09 | 78068651.04 | 27957119.65 | 71180590.93 | 0.118795E+09 |
Annual Sum or Average | 0.278030E+10 | 0.205352E+10 | 0.726783E+09 | 0.293668E+10 | 0.107647E+10 |
Minimum of Months | 0.106026E+09 | 78068651.04 | 27957119.65 | 71180590.93 | 69638163.68 |
Maximum of Months | 0.339260E+09 | 0.267292E+09 | 87808519.44 | 0.394878E+09 | 0.118795E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121148E+09 | 81510555.90 | 39637924.05 | 97926658.93 | 0.113390E+09 |
February | 0.151551E+09 | 0.107215E+09 | 44336622.51 | 0.144874E+09 | 90821004.62 |
March | 0.221749E+09 | 0.154149E+09 | 67599804.72 | 0.236729E+09 | 84807568.66 |
April | 0.290699E+09 | 0.210321E+09 | 80377735.84 | 0.319907E+09 | 76778300.35 |
May | 0.328518E+09 | 0.249391E+09 | 79127325.63 | 0.369592E+09 | 78400962.93 |
June | 0.337166E+09 | 0.267292E+09 | 69873425.29 | 0.386097E+09 | 75628087.84 |
July | 0.339260E+09 | 0.257009E+09 | 82251489.17 | 0.394878E+09 | 69638163.68 |
August | 0.316898E+09 | 0.229089E+09 | 87808519.44 | 0.360233E+09 | 70237600.90 |
September | 0.248183E+09 | 0.182141E+09 | 66042866.25 | 0.268400E+09 | 86930900.03 |
October | 0.191287E+09 | 0.148397E+09 | 42890376.68 | 0.182826E+09 | 0.111379E+09 |
November | 0.127818E+09 | 88938177.66 | 38879950.26 | 0.104033E+09 | 99661279.39 |
December | 0.106026E+09 | 78068651.04 | 27957119.65 | 71180590.93 | 0.118795E+09 |
Annual Sum or Average | 0.278030E+10 | 0.205352E+10 | 0.726783E+09 | 0.293668E+10 | 0.107647E+10 |
Minimum of Months | 0.106026E+09 | 78068651.04 | 27957119.65 | 71180590.93 | 69638163.68 |
Maximum of Months | 0.339260E+09 | 0.267292E+09 | 87808519.44 | 0.394878E+09 | 0.118795E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121148E+09 | 81510555.90 | 39637924.05 | 97926658.93 | 0.113390E+09 |
February | 0.151551E+09 | 0.107215E+09 | 44336622.51 | 0.144874E+09 | 90821004.62 |
March | 0.221749E+09 | 0.154149E+09 | 67599804.72 | 0.236729E+09 | 84807568.66 |
April | 0.290699E+09 | 0.210321E+09 | 80377735.84 | 0.319907E+09 | 76778300.35 |
May | 0.328518E+09 | 0.249391E+09 | 79127325.63 | 0.369592E+09 | 78400962.93 |
June | 0.337166E+09 | 0.267292E+09 | 69873425.29 | 0.386097E+09 | 75628087.84 |
July | 0.339260E+09 | 0.257009E+09 | 82251489.17 | 0.394878E+09 | 69638163.68 |
August | 0.316898E+09 | 0.229089E+09 | 87808519.44 | 0.360233E+09 | 70237600.90 |
September | 0.248183E+09 | 0.182141E+09 | 66042866.25 | 0.268400E+09 | 86930900.03 |
October | 0.191287E+09 | 0.148397E+09 | 42890376.68 | 0.182826E+09 | 0.111379E+09 |
November | 0.127818E+09 | 88938177.66 | 38879950.26 | 0.104033E+09 | 99661279.39 |
December | 0.106026E+09 | 78068651.04 | 27957119.65 | 71180590.93 | 0.118795E+09 |
Annual Sum or Average | 0.278030E+10 | 0.205352E+10 | 0.726783E+09 | 0.293668E+10 | 0.107647E+10 |
Minimum of Months | 0.106026E+09 | 78068651.04 | 27957119.65 | 71180590.93 | 69638163.68 |
Maximum of Months | 0.339260E+09 | 0.267292E+09 | 87808519.44 | 0.394878E+09 | 0.118795E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121148E+09 | 81510555.90 | 39637924.05 | 97926658.93 | 0.113390E+09 |
February | 0.151551E+09 | 0.107215E+09 | 44336622.51 | 0.144874E+09 | 90821004.62 |
March | 0.221749E+09 | 0.154149E+09 | 67599804.72 | 0.236729E+09 | 84807568.66 |
April | 0.290699E+09 | 0.210321E+09 | 80377735.84 | 0.319907E+09 | 76778300.35 |
May | 0.328518E+09 | 0.249391E+09 | 79127325.63 | 0.369592E+09 | 78400962.93 |
June | 0.337166E+09 | 0.267292E+09 | 69873425.29 | 0.386097E+09 | 75628087.84 |
July | 0.339260E+09 | 0.257009E+09 | 82251489.17 | 0.394878E+09 | 69638163.68 |
August | 0.316898E+09 | 0.229089E+09 | 87808519.44 | 0.360233E+09 | 70237600.90 |
September | 0.248183E+09 | 0.182141E+09 | 66042866.25 | 0.268400E+09 | 86930900.03 |
October | 0.191287E+09 | 0.148397E+09 | 42890376.68 | 0.182826E+09 | 0.111379E+09 |
November | 0.127818E+09 | 88938177.66 | 38879950.26 | 0.104033E+09 | 99661279.39 |
December | 0.106026E+09 | 78068651.04 | 27957119.65 | 71180590.93 | 0.118795E+09 |
Annual Sum or Average | 0.278030E+10 | 0.205352E+10 | 0.726783E+09 | 0.293668E+10 | 0.107647E+10 |
Minimum of Months | 0.106026E+09 | 78068651.04 | 27957119.65 | 71180590.93 | 69638163.68 |
Maximum of Months | 0.339260E+09 | 0.267292E+09 | 87808519.44 | 0.394878E+09 | 0.118795E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121148E+09 | 81510555.90 | 39637924.05 | 97926658.93 | 0.113390E+09 |
February | 0.151551E+09 | 0.107215E+09 | 44336622.51 | 0.144874E+09 | 90821004.62 |
March | 0.221749E+09 | 0.154149E+09 | 67599804.72 | 0.236729E+09 | 84807568.66 |
April | 0.290699E+09 | 0.210321E+09 | 80377735.84 | 0.319907E+09 | 76778300.35 |
May | 0.328518E+09 | 0.249391E+09 | 79127325.63 | 0.369592E+09 | 78400962.93 |
June | 0.337166E+09 | 0.267292E+09 | 69873425.29 | 0.386097E+09 | 75628087.84 |
July | 0.339260E+09 | 0.257009E+09 | 82251489.17 | 0.394878E+09 | 69638163.68 |
August | 0.316898E+09 | 0.229089E+09 | 87808519.44 | 0.360233E+09 | 70237600.90 |
September | 0.248183E+09 | 0.182141E+09 | 66042866.25 | 0.268400E+09 | 86930900.03 |
October | 0.191287E+09 | 0.148397E+09 | 42890376.68 | 0.182826E+09 | 0.111379E+09 |
November | 0.127818E+09 | 88938177.66 | 38879950.26 | 0.104033E+09 | 99661279.39 |
December | 0.106026E+09 | 78068651.04 | 27957119.65 | 71180590.93 | 0.118795E+09 |
Annual Sum or Average | 0.278030E+10 | 0.205352E+10 | 0.726783E+09 | 0.293668E+10 | 0.107647E+10 |
Minimum of Months | 0.106026E+09 | 78068651.04 | 27957119.65 | 71180590.93 | 69638163.68 |
Maximum of Months | 0.339260E+09 | 0.267292E+09 | 87808519.44 | 0.394878E+09 | 0.118795E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 198.75 | 487.21 | 303.24 | 143.48 | 159.76 | 0.00 | 0.00 |
February | 298.34 | 431.40 | 387.54 | 186.34 | 201.20 | 0.00 | 0.00 |
March | 393.23 | 327.47 | 443.67 | 193.03 | 250.65 | 0.00 | 0.00 |
April | 539.72 | 240.81 | 564.98 | 246.53 | 318.45 | 0.00 | 0.00 |
May | 548.16 | 206.90 | 552.22 | 234.74 | 317.48 | 0.00 | 0.00 |
June | 688.97 | 163.13 | 596.27 | 282.21 | 314.05 | 0.00 | 0.00 |
July | 659.41 | 126.21 | 540.34 | 216.87 | 323.46 | 0.00 | 0.00 |
August | 632.43 | 144.41 | 541.37 | 202.60 | 338.78 | 0.00 | 0.00 |
September | 514.54 | 221.18 | 479.29 | 207.33 | 271.97 | 0.00 | 0.00 |
October | 387.90 | 327.69 | 422.26 | 222.16 | 200.09 | 0.00 | 0.00 |
November | 241.28 | 385.87 | 335.43 | 164.86 | 170.57 | 0.00 | 0.00 |
December | 172.01 | 507.68 | 286.53 | 152.09 | 134.44 | 0.00 | 0.00 |
Annual Sum or Average | 440.10 | 296.89 | 454.55 | 204.27 | 250.27 | 0.00 | 0.00 |
Minimum of Months | 172.01 | 126.21 | 286.53 | 143.48 | 134.44 | 0.00 | 0.00 |
Maximum of Months | 688.97 | 507.68 | 596.27 | 282.21 | 338.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 365.62 | 423.35 | 452.32 | 304.33 | 147.99 | 0.00 | 0.00 |
February | 598.85 | 375.42 | 626.45 | 443.18 | 183.27 | 0.00 | 0.00 |
March | 883.84 | 316.63 | 827.92 | 575.53 | 252.39 | 0.00 | 0.00 |
April | 1234.21 | 296.21 | 1121.52 | 811.42 | 310.10 | 0.00 | 0.00 |
May | 1379.90 | 292.72 | 1226.55 | 931.12 | 295.43 | 0.00 | 0.00 |
June | 1489.57 | 291.77 | 1300.79 | 1031.22 | 269.57 | 0.00 | 0.00 |
July | 1474.30 | 260.00 | 1266.65 | 959.56 | 307.09 | 0.00 | 0.00 |
August | 1344.96 | 262.24 | 1183.16 | 855.32 | 327.84 | 0.00 | 0.00 |
September | 1035.49 | 335.38 | 957.50 | 702.70 | 254.80 | 0.00 | 0.00 |
October | 682.59 | 415.84 | 714.18 | 554.05 | 160.13 | 0.00 | 0.00 |
November | 401.36 | 384.50 | 493.13 | 343.13 | 150.00 | 0.00 | 0.00 |
December | 265.76 | 443.53 | 395.85 | 291.47 | 104.38 | 0.00 | 0.00 |
Annual Sum or Average | 931.21 | 341.35 | 881.63 | 651.17 | 230.46 | 0.00 | 0.00 |
Minimum of Months | 265.76 | 260.00 | 395.85 | 291.47 | 104.38 | 0.00 | 0.00 |
Maximum of Months | 1489.57 | 443.53 | 1300.79 | 1031.22 | 327.84 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.532333E+09 | 0.130493E+10 | 0.812193E+09 | 0.384287E+09 | 0.427906E+09 | 0.00 | 0.00 |
February | 0.721741E+09 | 0.104365E+10 | 0.937547E+09 | 0.450793E+09 | 0.486754E+09 | 0.00 | 0.00 |
March | 0.105322E+10 | 0.877091E+09 | 0.118834E+10 | 0.516998E+09 | 0.671338E+09 | 0.00 | 0.00 |
April | 0.139895E+10 | 0.624189E+09 | 0.146444E+10 | 0.639009E+09 | 0.825431E+09 | 0.00 | 0.00 |
May | 0.146819E+10 | 0.554172E+09 | 0.147906E+10 | 0.628721E+09 | 0.850341E+09 | 0.00 | 0.00 |
June | 0.178581E+10 | 0.422833E+09 | 0.154552E+10 | 0.731499E+09 | 0.814020E+09 | 0.00 | 0.00 |
July | 0.176617E+10 | 0.338044E+09 | 0.144724E+10 | 0.580874E+09 | 0.866367E+09 | 0.00 | 0.00 |
August | 0.169391E+10 | 0.386787E+09 | 0.145002E+10 | 0.542640E+09 | 0.907378E+09 | 0.00 | 0.00 |
September | 0.133370E+10 | 0.573309E+09 | 0.124233E+10 | 0.537390E+09 | 0.704939E+09 | 0.00 | 0.00 |
October | 0.103896E+10 | 0.877676E+09 | 0.113097E+10 | 0.595040E+09 | 0.535931E+09 | 0.00 | 0.00 |
November | 0.625401E+09 | 0.100017E+10 | 0.869445E+09 | 0.427323E+09 | 0.442122E+09 | 0.00 | 0.00 |
December | 0.460714E+09 | 0.135976E+10 | 0.767455E+09 | 0.407361E+09 | 0.360094E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.138791E+11 | 0.936262E+10 | 0.143346E+11 | 0.644194E+10 | 0.789262E+10 | 0.00 | 0.00 |
Minimum of Months | 0.460714E+09 | 0.338044E+09 | 0.767455E+09 | 0.384287E+09 | 0.360094E+09 | 0.00 | 0.00 |
Maximum of Months | 0.178581E+10 | 0.135976E+10 | 0.154552E+10 | 0.731499E+09 | 0.907378E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.979266E+09 | 0.113390E+10 | 0.121148E+10 | 0.815106E+09 | 0.396379E+09 | 0.00 | 0.00 |
February | 0.144874E+10 | 0.908210E+09 | 0.151551E+10 | 0.107215E+10 | 0.443366E+09 | 0.00 | 0.00 |
March | 0.236728E+10 | 0.848075E+09 | 0.221749E+10 | 0.154149E+10 | 0.675998E+09 | 0.00 | 0.00 |
April | 0.319907E+10 | 0.767783E+09 | 0.290699E+10 | 0.210321E+10 | 0.803777E+09 | 0.00 | 0.00 |
May | 0.369592E+10 | 0.784009E+09 | 0.328518E+10 | 0.249391E+10 | 0.791273E+09 | 0.00 | 0.00 |
June | 0.386097E+10 | 0.756278E+09 | 0.337166E+10 | 0.267292E+10 | 0.698734E+09 | 0.00 | 0.00 |
July | 0.394878E+10 | 0.696380E+09 | 0.339260E+10 | 0.257009E+10 | 0.822515E+09 | 0.00 | 0.00 |
August | 0.360233E+10 | 0.702375E+09 | 0.316898E+10 | 0.229089E+10 | 0.878085E+09 | 0.00 | 0.00 |
September | 0.268400E+10 | 0.869309E+09 | 0.248183E+10 | 0.182141E+10 | 0.660429E+09 | 0.00 | 0.00 |
October | 0.182825E+10 | 0.111379E+10 | 0.191287E+10 | 0.148397E+10 | 0.428904E+09 | 0.00 | 0.00 |
November | 0.104033E+10 | 0.996613E+09 | 0.127818E+10 | 0.889382E+09 | 0.388800E+09 | 0.00 | 0.00 |
December | 0.711806E+09 | 0.118795E+10 | 0.106026E+10 | 0.780687E+09 | 0.279571E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.293667E+11 | 0.107647E+11 | 0.278030E+11 | 0.205352E+11 | 0.726783E+10 | 0.00 | 0.00 |
Minimum of Months | 0.711806E+09 | 0.696380E+09 | 0.106026E+10 | 0.780687E+09 | 0.279571E+09 | 0.00 | 0.00 |
Maximum of Months | 0.394878E+10 | 0.118795E+10 | 0.339260E+10 | 0.267292E+10 | 0.878085E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.2 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.20 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.66 | -5.5 | 4.72 | -6.1 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.69 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.40 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.39 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.11 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.38 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.86 | 7.70 | 3.48 | 8.21 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.78 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.0 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.53 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.0 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.11 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.80 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.83 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.65 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.28 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.68 | -1.5 | 8.93 | 13.33 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.11 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.67 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.27 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.73 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.23 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.79 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 3.99 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 3.99 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.73 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.1 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.6 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.2 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -0.7 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.53 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.76 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.7 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -11.9 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -11.9 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.82 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.83 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.65 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.92 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.05 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.75 | 167.00 | 0.00 |
June | 18.16 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.19 | 01-JUL-00:00 | 21.20 | 13.50 | 3.60 | 17.57 | 0.00 | 0.00 |
August | 19.17 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.18 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.15 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.79 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.90 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.90 | 12.80 | -10.0 | 2.10 | -0.1 | 0.00 | 0.00 | |
Maximum of Months | 19.19 | 31.70 | 15.60 | 13.40 | 19.17 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.71 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.78 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.70 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.04 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.58 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.03 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.37 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.04 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.939373E+09 | -852339439.0 | 0.00 | 0.00 | 744.00 | 0.00 | -87033940.2 | 58.99 | 0.00 | 0.00 |
February | 0.866940E+09 | -789007453.9 | 0.00 | 0.00 | 672.00 | 0.00 | -77932815.8 | 58.99 | 0.00 | 0.00 |
March | 0.983289E+09 | -899389702.1 | 0.00 | 0.00 | 744.00 | 0.00 | -83899078.8 | 58.99 | 0.00 | 0.00 |
April | 0.867558E+09 | -791274085.8 | 0.00 | 0.00 | 720.00 | 0.00 | -76284316.2 | 58.99 | 0.00 | 0.00 |
May | 0.840304E+09 | -765535717.1 | 0.00 | 0.00 | 744.00 | 0.00 | -74768538.3 | 58.99 | 0.00 | 0.00 |
June | 0.777277E+09 | -708011199.7 | 0.00 | 0.00 | 720.00 | 0.00 | -69265611.0 | 58.99 | 0.00 | 0.00 |
July | 0.719586E+09 | -649625881.7 | 0.00 | 0.00 | 744.00 | 0.00 | -69959687.6 | 58.99 | 0.00 | 0.00 |
August | 0.760671E+09 | -690146679.1 | 0.00 | 0.00 | 744.00 | 0.00 | -70524227.3 | 58.99 | 0.00 | 0.00 |
September | 0.733181E+09 | -663772916.5 | 0.00 | 0.00 | 720.00 | 0.00 | -69407845.5 | 58.99 | 0.00 | 0.00 |
October | 0.787094E+09 | -710548361.7 | 0.00 | 0.00 | 744.00 | 0.00 | -76545300.3 | 58.99 | 0.00 | 0.00 |
November | 0.816936E+09 | -735513902.1 | 0.00 | 0.00 | 720.00 | 0.00 | -81422266.7 | 59.00 | 0.00 | 0.00 |
December | 0.904122E+09 | -817172581.5 | 0.00 | 0.00 | 744.00 | 0.00 | -86949280.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.999633E+10 | -.907234E+10 | 8760.00 | -923992908.1 | 58.99 | |||||
Minimum of Months | 0.719586E+09 | -899389702.1 | 0.00 | 0.00 | 672.00 | 0.00 | -87033940.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.983289E+09 | -649625881.7 | 0.00 | 0.00 | 744.00 | 0.00 | -69265611.0 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 301.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 282.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 381.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 378.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 395.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 359.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 329.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 284.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4149.83 | ||||||||||
Minimum of Months | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.476074E+10 | 28601.49 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.370776E+10 | 28601.49 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.211704E+10 | 28601.49 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.470981E+09 | 28601.49 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 71865283.42 | 28601.49 | 05-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 939497.65 | 2082.75 | 17-JUN-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 588916.81 | 1963.06 | 30-SEP-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.442386E+09 | 28601.49 | 25-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174402E+10 | 28601.49 | 04-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.466367E+10 | 28601.49 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179800E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.476074E+10 | 28601.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.229072E+11 | 88473.51 | 01-JAN-01:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164161E+11 | 88473.51 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.626576E+10 | 88473.51 | 03-MAR-22:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.315260E+09 | 46097.58 | 07-APR-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.386936E+09 | 51606.08 | 26-OCT-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.679721E+10 | 88473.51 | 06-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.215123E+11 | 88473.51 | 03-DEC-18:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.746008E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.229072E+11 | 88473.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.259687E+11 | 85487.78 | 16-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168343E+11 | 75087.05 | 05-FEB-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116350E+10 | 29489.15 | 04-MAR-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.400561E+09 | 18633.22 | 26-NOV-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.224233E+11 | 85739.76 | 14-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.667903E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.259687E+11 | 85739.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 3468557.47 | 3468557.47 | 1012.68 | 14-FEB-16:00 | 1012.68 | 0.00 |
March | 0.00 | 0.00 | 14094366.39 | 14094366.39 | 1811.86 | 08-MAR-16:00 | 1811.86 | 0.00 |
April | 0.00 | 0.00 | 0.980926E+09 | 0.980926E+09 | 6895.75 | 13-APR-16:00 | 6895.75 | 0.00 |
May | 0.00 | 0.00 | 0.277655E+10 | 0.276556E+10 | 20587.41 | 22-MAY-05:03 | 16521.57 | 0.00 |
June | 0.00 | 0.00 | 0.747630E+10 | 0.734831E+10 | 22208.62 | 29-JUN-05:01 | 20383.42 | 0.00 |
July | 0.00 | 0.00 | 0.105397E+11 | 0.951241E+10 | 23107.79 | 01-JUL-05:01 | 13752.96 | 0.00 |
August | 0.00 | 0.00 | 0.997671E+10 | 0.893268E+10 | 23449.37 | 14-AUG-05:01 | 13820.55 | 0.00 |
September | 0.00 | 0.00 | 0.596514E+10 | 0.557846E+10 | 22368.94 | 05-SEP-05:01 | 13037.79 | 0.00 |
October | 0.00 | 0.00 | 0.191278E+10 | 0.183192E+10 | 20854.45 | 02-OCT-05:01 | 16711.98 | 0.00 |
November | 0.00 | 0.00 | 3683.58 | 3683.58 | 0.64 | 02-NOV-15:00 | 0.64 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.396456E+11 | 0.369678E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.105397E+11 | 0.951241E+10 | 23449.37 | 20383.42 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.171252E+09 | 0.171252E+09 | 6474.45 | 28-APR-14:40 | 6474.45 | 0.00 |
May | 0.00 | 0.00 | 0.372064E+10 | 0.371559E+10 | 61559.77 | 28-MAY-12:21 | 56063.30 | 0.00 |
June | 0.00 | 0.00 | 0.195073E+11 | 0.193458E+11 | 63487.77 | 25-JUN-07:58 | 53501.24 | 0.00 |
July | 0.00 | 0.00 | 0.299273E+11 | 0.280811E+11 | 70181.80 | 01-JUL-17:12 | 39610.06 | 0.00 |
August | 0.00 | 0.00 | 0.252049E+11 | 0.235010E+11 | 69693.06 | 13-AUG-09:11 | 45993.63 | 0.00 |
September | 0.00 | 0.00 | 0.112392E+11 | 0.107143E+11 | 65515.59 | 04-SEP-10:31 | 50411.60 | 0.00 |
October | 0.00 | 0.00 | 0.216261E+10 | 0.211310E+10 | 60628.00 | 01-OCT-11:10 | 58415.78 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.919332E+11 | 0.876421E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.299273E+11 | 0.280811E+11 | 70181.80 | 58415.78 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.294147E+09 | 0.04 | 248.13 | 01-JAN-00:02 | 0.09 |
February | 0.172189E+09 | 0.03 | 248.13 | 01-FEB-00:02 | 0.09 |
March | 21885334.03 | 0.00 | 248.13 | 01-MAR-04:03 | 0.09 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 10570467.46 | 0.00 | 248.13 | 26-NOV-04:50 | 0.09 |
December | 0.288487E+09 | 0.04 | 248.13 | 03-DEC-18:54 | 0.09 |
Annual Sum or Average | 0.787279E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.294147E+09 | 0.04 | 248.13 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156700E+10 | 0.52 | 1519.47 | 02-JAN-08:20 | 1.14 |
February | 0.143724E+10 | 0.51 | 1519.47 | 02-FEB-08:70 | 1.14 |
March | 0.166150E+10 | 0.49 | 1519.47 | 02-MAR-07:20 | 1.14 |
April | 0.151414E+10 | 0.45 | 1519.47 | 05-APR-06:20 | 1.14 |
May | 0.156815E+10 | 0.44 | 1519.47 | 02-MAY-06:40 | 1.14 |
June | 0.159891E+10 | 0.47 | 1519.47 | 01-JUN-13:20 | 1.13 |
July | 0.156173E+10 | 0.45 | 1519.47 | 01-JUL-08:50 | 1.12 |
August | 0.168269E+10 | 0.48 | 1519.47 | 11-AUG-08:30 | 1.12 |
September | 0.153096E+10 | 0.45 | 1519.47 | 05-SEP-09:00 | 1.12 |
October | 0.151405E+10 | 0.43 | 1519.47 | 02-OCT-07:40 | 1.13 |
November | 0.147105E+10 | 0.45 | 1519.47 | 01-NOV-15:00 | 1.13 |
December | 0.155411E+10 | 0.48 | 1519.47 | 04-DEC-12:20 | 1.14 |
Annual Sum or Average | 0.186615E+11 | 0.47 | |||
Minimum of Months | 0.143724E+10 | 0.43 | 1519.47 | 1.12 | |
Maximum of Months | 0.168269E+10 | 0.52 | 1519.47 | 1.14 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.447703E+10 | 0.90 | 3608.62 | 31-JAN-17:40 | 1.10 |
February | 0.395458E+10 | 0.84 | 3608.62 | 01-FEB-07:30 | 1.10 |
March | 0.412521E+10 | 0.67 | 3608.62 | 01-MAR-08:70 | 1.09 |
April | 0.358772E+10 | 0.43 | 3608.62 | 07-APR-06:05 | 1.10 |
May | 0.375366E+10 | 0.44 | 3608.62 | 19-MAY-12:30 | 1.09 |
June | 0.399881E+10 | 0.53 | 3608.62 | 16-JUN-09:30 | 1.09 |
July | 0.407439E+10 | 0.55 | 3608.62 | 14-JUL-09:45 | 1.08 |
August | 0.420370E+10 | 0.54 | 3608.62 | 05-AUG-09:00 | 1.08 |
September | 0.368623E+10 | 0.44 | 3608.62 | 01-SEP-10:57 | 1.08 |
October | 0.360761E+10 | 0.43 | 3608.62 | 04-OCT-12:40 | 1.09 |
November | 0.373335E+10 | 0.68 | 3608.62 | 04-NOV-06:05 | 1.09 |
December | 0.443588E+10 | 0.91 | 3608.62 | 15-DEC-09:00 | 1.10 |
Annual Sum or Average | 0.476382E+11 | 0.61 | |||
Minimum of Months | 0.358772E+10 | 0.43 | 3608.62 | 1.08 | |
Maximum of Months | 0.447703E+10 | 0.91 | 3608.62 | 1.10 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.71 | 0.06 |
February | 1.45 | 0.03 |
March | 0.79 | 0.70 |
April | 1.21 | 1.70 |
May | 2.50 | 1.45 |
June | 4.05 | 0.24 |
July | 4.86 | 0.28 |
August | 4.36 | 0.23 |
September | 2.85 | 0.14 |
October | 2.18 | 0.82 |
November | 2.00 | 1.47 |
December | 2.44 | 0.05 |
Annual Sum or Average | 31.40 | 0.48 |
Minimum of Months | 0.79 | 0.03 |
Maximum of Months | 4.86 | 1.70 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.08 | 0.00 |
March | 0.00 | 0.00 |
April | 0.08 | 0.00 |
May | 1.36 | 0.00 |
June | 2.16 | 0.00 |
July | 3.70 | 0.00 |
August | 2.46 | 0.00 |
September | 2.98 | 0.00 |
October | 0.62 | 0.00 |
November | 0.00 | 0.00 |
December | 0.04 | 0.00 |
Annual Sum or Average | 13.49 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.70 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 2.53 | 0.00 |
July | 7.71 | 0.00 |
August | 5.66 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 15.89 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 7.71 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.156700E+10 | 0.691673E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.143820E+10 | 0.539908E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.166538E+10 | 0.308657E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.177980E+10 | 0.694459E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.232942E+10 | 0.107149E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.379057E+10 | 1448078.08 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.457207E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.445850E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.316067E+10 | 904659.74 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.202871E+10 | 0.652800E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.147105E+10 | 0.255291E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.155411E+10 | 0.678387E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.298155E+11 | 0.261959E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.143820E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.457207E+10 | 0.691673E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.447703E+10 | 0.332448E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.395458E+10 | 0.238654E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.412521E+10 | 0.929062E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.363885E+10 | 0.470854E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.486941E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.102943E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.134556E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.118864E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.701643E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.424259E+10 | 0.585828E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.373335E+10 | 0.100668E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.443588E+10 | 0.312970E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.761295E+11 | 0.108821E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.363885E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.134556E+11 | 0.332448E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156700E+10 | 0.00 | 0.476074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143724E+10 | 3468557.47 | 0.370776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166150E+10 | 14094366.39 | 0.211704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151414E+10 | 0.980926E+09 | 0.470981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156815E+10 | 0.277655E+10 | 71865283.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159891E+10 | 0.747630E+10 | 939497.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156173E+10 | 0.105397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.168269E+10 | 0.997671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153096E+10 | 0.596514E+10 | 588916.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151405E+10 | 0.191278E+10 | 0.442386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147105E+10 | 3683.58 | 0.174402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155411E+10 | 0.00 | 0.466367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186615E+11 | 0.396456E+11 | 0.179800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.168269E+10 | 0.105397E+11 | 0.476074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.447703E+10 | 0.00 | 0.229072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.395458E+10 | 0.00 | 0.164161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.412521E+10 | 0.00 | 0.626576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.358772E+10 | 0.171252E+09 | 0.315260E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.375366E+10 | 0.372064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.399881E+10 | 0.195073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.407439E+10 | 0.299273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.420370E+10 | 0.252049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.368623E+10 | 0.112392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.360761E+10 | 0.216261E+10 | 0.386936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373335E+10 | 0.00 | 0.679721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.443588E+10 | 0.00 | 0.215123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.476382E+11 | 0.919332E+11 | 0.746008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.358772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.447703E+10 | 0.299273E+11 | 0.229072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.156700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143724E+10 | 0.00 | 0.00 | 0.00 | 960312.66 | 0.00 | 0.539908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166150E+10 | 0.00 | 0.00 | 0.00 | 3879918.92 | 0.00 | 0.308657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151414E+10 | 0.00 | 0.00 | 0.00 | 0.265666E+09 | 0.00 | 0.694459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156815E+10 | 0.00 | 0.00 | 0.00 | 0.761270E+09 | 0.00 | 0.107149E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159891E+10 | 0.00 | 0.00 | 0.00 | 0.219166E+10 | 0.00 | 1448078.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156173E+10 | 0.00 | 0.00 | 0.00 | 0.301034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.168269E+10 | 0.00 | 0.00 | 0.00 | 0.277581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153096E+10 | 0.00 | 0.00 | 0.00 | 0.162971E+10 | 0.00 | 904659.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151405E+10 | 0.00 | 0.00 | 0.00 | 0.514657E+09 | 0.00 | 0.652800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147105E+10 | 0.00 | 0.00 | 0.00 | 1026.11 | 0.00 | 0.255291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186615E+11 | 0.00 | 0.00 | 0.00 | 0.111540E+11 | 0.00 | 0.261959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.143724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.168269E+10 | 0.00 | 0.00 | 0.00 | 0.301034E+10 | 0.00 | 0.691673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.447703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.395458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.412521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.358772E+10 | 0.00 | 0.00 | 0.00 | 51126815.07 | 0.00 | 0.470854E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.375366E+10 | 0.00 | 0.00 | 0.00 | 0.111575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.399881E+10 | 0.00 | 0.00 | 0.00 | 0.629549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.407439E+10 | 0.00 | 0.00 | 0.00 | 0.938117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.420370E+10 | 0.00 | 0.00 | 0.00 | 0.768266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.368623E+10 | 0.00 | 0.00 | 0.00 | 0.333020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.360761E+10 | 0.00 | 0.00 | 0.00 | 0.634981E+09 | 0.00 | 0.585828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.443588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.476382E+11 | 0.00 | 0.00 | 0.00 | 0.284914E+11 | 0.00 | 0.108821E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.358772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.447703E+10 | 0.00 | 0.00 | 0.00 | 0.938117E+10 | 0.00 | 0.332448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.273745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142475E+10 | 0.00 | 0.00 | 0.14 |
February | 0.264257E+09 | 0.00 | 0.00 | 25560.31 | 0.00 | 0.117583E+10 | 58223398.75 | 0.00 | 0.17 |
March | 0.554526E+09 | 0.00 | 0.00 | 64936.80 | 0.00 | 0.650225E+09 | 0.170820E+09 | 0.00 | 0.20 |
April | 0.440187E+09 | 4998378.49 | 0.00 | 1525414.75 | 0.00 | 97593297.46 | 0.111975E+10 | 0.00 | 0.44 |
May | 0.167901E+09 | 41190960.59 | 0.00 | 3389964.64 | 0.00 | 10286578.99 | 0.174966E+10 | 0.00 | 0.59 |
June | 15354184.19 | 0.370482E+09 | 0.00 | 5099244.89 | 0.00 | 0.00 | 0.104052E+10 | 0.00 | 0.54 |
July | 105806.59 | 0.855765E+09 | 0.00 | 6737732.82 | 464993.76 | 0.00 | 0.178104E+09 | 0.00 | 0.41 |
August | 7443381.67 | 0.639654E+09 | 0.00 | 7706780.09 | 150129.75 | 0.00 | 0.673599E+09 | 0.00 | 0.57 |
September | 17383456.81 | 0.155173E+09 | 0.00 | 5637518.47 | 0.00 | 0.00 | 0.143408E+10 | 0.00 | 0.64 |
October | 0.331168E+09 | 21419814.47 | 0.00 | 3407660.93 | 0.00 | 0.144982E+09 | 0.163787E+10 | 0.00 | 0.52 |
November | 0.734938E+09 | 0.00 | 0.00 | 65097.87 | 0.00 | 0.577282E+09 | 0.110249E+09 | 0.00 | 0.15 |
December | 0.281039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165057E+10 | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.308805E+10 | 0.208868E+10 | 0.00 | 33659911.56 | 615123.51 | 0.573151E+10 | 0.817287E+10 | 0.00 | 0.38 |
Minimum of Months | 105806.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.734938E+09 | 0.855765E+09 | 0.00 | 7706780.09 | 464993.76 | 0.165057E+10 | 0.174966E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.213553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124911E+10 | 0.00 | 0.00 | 0.14 |
February | 0.220199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714039E+09 | 0.00 | 0.00 | 0.15 |
March | 0.219485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209234E+09 | 0.00 | 0.00 | 0.16 |
April | 0.202560E+10 | 0.00 | 0.00 | 491006.37 | 883559.62 | 0.00 | 0.473902E+09 | 0.00 | 0.24 |
May | 0.129782E+10 | 33264082.95 | 0.00 | 4753759.93 | 2375114.10 | 0.00 | 0.210164E+10 | 0.00 | 0.41 |
June | 0.392178E+09 | 0.730964E+09 | 0.00 | 6660428.74 | 0.00 | 0.00 | 0.170040E+10 | 0.00 | 0.40 |
July | 38099911.12 | 0.143523E+10 | 0.00 | 8405604.87 | 0.00 | 0.00 | 0.135353E+10 | 0.00 | 0.42 |
August | 0.128518E+09 | 0.968463E+09 | 0.00 | 12233991.84 | 0.00 | 0.00 | 0.225890E+10 | 0.00 | 0.53 |
September | 0.401682E+09 | 0.148302E+09 | 0.00 | 12625995.77 | 0.00 | 0.00 | 0.275410E+10 | 0.00 | 0.54 |
October | 0.203612E+10 | 5240809.01 | 0.00 | 4060539.96 | 0.00 | 42643116.82 | 0.125490E+10 | 0.00 | 0.30 |
November | 0.267111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147980E+09 | 0.00 | 0.00 | 0.14 |
December | 0.288018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111074E+10 | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.184037E+11 | 0.332147E+10 | 0.00 | 49231327.49 | 3258673.71 | 0.347375E+10 | 0.118974E+11 | 0.00 | 0.30 |
Minimum of Months | 38099911.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.288018E+10 | 0.143523E+10 | 0.00 | 12625995.77 | 2375114.10 | 0.124911E+10 | 0.275410E+10 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |