Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2020-06-03 19:11:44
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1830.00 | 378.48 | 378.48 |
Net Site Energy | 1830.00 | 378.48 | 378.48 |
Total Source Energy | 3671.71 | 759.38 | 759.38 |
Net Source Energy | 3671.71 | 759.38 | 759.38 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1019.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 10.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 99.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 59.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.70 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 810.36 | 1019.63 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1019.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 10.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 99.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 1.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 57.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.70 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 118.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 19.85 | 210.88 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 167.60 | 210.88 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 118.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 19.85 | 210.88 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 167.60 | 210.88 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 810.365 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 810.365 | 100.00 |
Total On-Site and Utility Electric Sources | 810.365 | 100.00 |
Total Electricity End Uses | 810.365 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 66.00 |
Time Setpoint Not Met During Occupied Cooling | 1.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2212.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.6337 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.5069 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.5069 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-14:09 | 05-JAN-17:00 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 336668.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 13212.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6194.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1774.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 66482.87 | 336668.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 336668.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 13212.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 3888.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1774.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1105.28 | 0.00 | 0.00 | 0.00 |
Cooling | 32.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1507.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 313.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 84.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2566.43 | 1105.28 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 228.59 | 0.00 | 0.00 | 0.00 |
Cooling | 6.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 64.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 530.79 | 228.59 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 228.59 | 0.00 | 0.00 | 0.00 |
Cooling | 6.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 64.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 530.79 | 228.59 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.12 |
ZONE2 FINE STORAGE DIRECT AIR | 2.38 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 4.43 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 4.43 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 160804.04 |
PSZ-OFFICE HEATING COIL | 27822.30 |
PSZ-FINE STORAGE HEATING COIL | 81008.19 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 160804.03 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.00 | 1.00 | 1.12 |
PSZ-FINE STORAGE | 2.38 | 2.38 | 2.38 | 2.38 | 2.38 | 2.38 | 1.00 | 1.000000 | 2.38 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.12 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 2.38 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.12 | 1.12 | 1.12 | 1.12 | 18618.86 | 27822.30 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.38 | 2.38 | 2.38 | 2.38 | 46871.22 | 81008.19 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.12 | 0.562385 | 1.12 | 18618.94 | 18618.86 | 9309.43 | 18618.86 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 2.38 | 1.19 | 2.38 | 40741.25 | 46871.22 | 23435.61 | 46871.22 | 0.740225 | 0.740230 | 0.740230 | 0.740230 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.12 | 1282.36 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.38 | 2606.56 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.634 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.707 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.507 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.507 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.507 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.066 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2518.900 | 10.634 | 503.780 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2518.900 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11853.648 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11853.648 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27263.390 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27263.390 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2893 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2893 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.4128 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.4128 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1413 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.5841E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.5469E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.4128 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.457 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.457 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.323 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.323 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.998 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 17.04 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 18.21 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.323 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.87112823E-12 | 0.85080972E-17 | 0.21755189E-17 | 0.0000000 |
2 | 1 | -5.2160329 | 0.44465164E-04 | -0.55377147E-04 | 0.16700973E-12 |
3 | 0 | 5.5053245 | 0.28924715 | 0.28934699 | |
4 | 2 | 0.87112823E-12 | 0.85080972E-17 | 0.21755189E-17 | 0.0000000 |
5 | 1 | -5.2160329 | 0.44465164E-04 | -0.55377147E-04 | 0.16700973E-12 |
6 | 0 | 5.5053245 | 0.28924715 | 0.28934699 | |
7 | 4 | 0.79581057E-12 | 0.97316148E-16 | -0.20714918E-14 | 0.11395926E-15 |
8 | 3 | -0.38950733E-03 | 0.29153728E-06 | -0.56547345E-04 | 0.15269480E-12 |
9 | 2 | 1.7508611 | 0.63413892E-02 | 1.1490629 | -0.74675203E-04 |
10 | 1 | -7.1137977 | 0.16376069 | -17.153076 | 0.33557628 |
11 | 0 | 5.6376123 | 0.10418388 | 16.278356 | |
12 | 4 | 0.79581057E-12 | 0.97316148E-16 | -0.20714918E-14 | 0.11395926E-15 |
13 | 3 | -0.38950733E-03 | 0.29153728E-06 | -0.56547345E-04 | 0.15269480E-12 |
14 | 2 | 1.7508611 | 0.63413892E-02 | 1.1490629 | -0.74675203E-04 |
15 | 1 | -7.1137977 | 0.16376069 | -17.153076 | 0.33557628 |
16 | 0 | 5.6376123 | 0.10418388 | 16.278356 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.8391346 | 2.8391346 | 2.8391346 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.8391346 | 2.8391346 | 2.8391346 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.30042996E-08 | -0.19492532E-14 | 0.18571942E-14 | -0.50265421E-16 |
55 | 6 | 0.40686135E-05 | 0.27025218E-08 | 0.31944093E-02 | -0.26797382E-04 |
56 | 5 | -0.28598357E-03 | 0.15982348E-05 | -0.22398257 | 0.19584275E-02 |
57 | 4 | 0.65354345E-02 | 0.72696005E-04 | 4.8338424 | -0.45306284E-01 |
58 | 3 | -0.57256805E-01 | 0.57768437E-03 | -38.045688 | 0.39892203 |
59 | 2 | 0.20312160 | 0.96045137E-03 | 116.53119 | -1.4185711 |
60 | 1 | -0.29305691 | 0.29236276E-03 | -143.93511 | 2.0494970 |
61 | 0 | 0.14285049 | 0.70905046E-05 | 60.838472 | |
62 | 7 | -0.73310212E-08 | 0.16277859E-15 | -0.15558641E-14 | 0.17403554E-16 |
63 | 6 | 0.21213446E-05 | 0.11327280E-08 | 0.32008460E-02 | -0.26851379E-04 |
64 | 5 | -0.12816801E-03 | 0.66411688E-06 | -0.22434819 | 0.19616548E-02 |
65 | 4 | 0.27852559E-02 | 0.30072908E-04 | 4.8399282 | -0.45364789E-01 |
66 | 3 | -0.23934818E-01 | 0.23808113E-03 | -38.080046 | 0.39930184 |
67 | 2 | 0.84241938E-01 | 0.39442809E-03 | 116.59803 | -1.4194653 |
68 | 1 | -0.12110434 | 0.11951395E-03 | -143.97445 | 2.0501436 |
69 | 0 | 0.58923671E-01 | 0.28881054E-05 | 60.838472 | |
70 | 7 | -0.78336681E-08 | 0.23380828E-15 | -0.37470831E-14 | 0.17001158E-16 |
71 | 6 | 0.20573783E-05 | 0.10635783E-08 | 0.32011355E-02 | -0.26853807E-04 |
72 | 5 | -0.12166809E-03 | 0.62270931E-06 | -0.22436462 | 0.19617998E-02 |
73 | 4 | 0.26229018E-02 | 0.28177105E-04 | 4.8402013 | -0.45367414E-01 |
74 | 3 | -0.22467346E-01 | 0.22293819E-03 | -38.081586 | 0.39931887 |
75 | 2 | 0.78971204E-01 | 0.36912476E-03 | 116.60102 | -1.4195054 |
76 | 1 | -0.11345740 | 0.11176675E-03 | -143.97621 | 2.0501725 |
77 | 0 | 0.55185584E-01 | 0.26976542E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.20714918E-14 | 0.97316148E-16 | 0.79581057E-12 | 0.11395926E-15 |
85 | 3 | -0.56547345E-04 | 0.29153728E-06 | -0.38950733E-03 | 0.15269480E-12 |
86 | 2 | 1.1490629 | 0.63413892E-02 | 1.7508611 | -0.74675203E-04 |
87 | 1 | -17.153076 | 0.16376069 | -7.1137977 | 0.33557628 |
88 | 0 | 16.278356 | 0.10418388 | 5.6376123 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 28 | 1 | VerySmooth | 2.843 | 0.395 | 0.315 | 0.401 |
2 | SKYLIGHT_U_0.6_SHGC_0.4 | 29 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 30 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9964.76590 | 11957.71907 | 0.93730 | 1.12477 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.16000 | 6.26593E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 12362.21938 | 14834.66326 | 0.39696 | 0.47636 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60000 | 3.41898E-004 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 27068.37713 | 32482.05255 | 1.98458 | 2.38149 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.37333 | 6.26593E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 53923.64770 | 64708.37724 | 1.45767 | 1.74921 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40000 | 6.26594E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 134003.35518 | 160804.02621 | 3.68831 | 4.42597 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -27.60000 | 3.41898E-004 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 14950.00 | 1.12477 | 1.12477 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 14818.95 | 0.47636 | 0.47636 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 39786.25 | 2.38149 | 2.38149 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 64649.92 | 1.74921 | 1.74921 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.12477 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.38149 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 4.42597 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 4.42597 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 160804.03610 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 160804.02621 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.12477 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.12477 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.12477 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.12477 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.12477 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.12477 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.38149 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.38149 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.38149 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.38149 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.38149 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.38149 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.12477 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.38149 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.12477 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.12477 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.12477 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.12477 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.12477 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.12477 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56239 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.12477 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18618.93726 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 18618.86000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9309.43000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 18618.86000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18618.86000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27822.29707 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.12477 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1282.35627 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 27822.29707 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.38149 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.38149 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.38149 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.38149 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.38149 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.38149 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.19075 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.38149 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 40741.24953 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 46871.22000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 23435.61000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 46871.22000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74022 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74023 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74023 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74023 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 46871.22000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 81008.18971 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.38149 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2606.55540 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 81008.18971 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 17746.1 | 11.07 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 45022.1 | 13.71 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 13 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1717450527 | 0.1690962036 | Pass | Pass | 3.2542975303 | 18.1088045569 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.5661402406 | 0.5618173818 | Pass | Pass | 0.4285739492 | 0.6452035746 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.1663795106E-004 | 1.2884288878E-003 | Pass | Pass | 8.2827404939E-002 | 0.1505370652 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.389 | 0.413 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.278 | 0.289 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.389 | 0.413 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.389 | 0.413 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.389 | 0.413 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.278 | 0.289 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.141 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.058 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.055 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.843 | 0.395 | 0.401 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.5_SHGC_0.4 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.843 | 0.395 | 0.401 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.6_SHGC_0.4 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.102 | 0.395 | 0.401 | ||||||||||||
North Total or Average | 6.51 | 2.843 | 0.395 | 0.401 | ||||||||||||
Non-North Total or Average | 26.02 | 3.167 | 0.395 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.992 | 2.839 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.6337 | 236.88 | 2518.90 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.62 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.5069 | 1393.41 | 11853.65 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 135.00 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.5069 | 3204.84 | 27263.39 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 310.50 |
Interior Lighting Total | 8.6111 | 4835.13 | 41635.94 | 476.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 6311.00 | AstronomicalClock | - | 83.57 | 83.57 | 99.00 | |
Exterior Lighting Total | 6311.00 | 99.00 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18618.86 | 14870.14 | 3748.72 | 0.80 | 3.91 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 46871.22 | 34695.48 | 12175.74 | 0.74 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 17746.1 | 11.07 | ||||
PSZ-FINE STORAGE COOLING COIL | 45022.1 | 13.71 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 160804.04 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 27822.30 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 81008.19 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 4.43 | 411.22 | 92.91 | 1.00 | 3.20 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.12 | 1282.36 | 1140.11 | 1.00 | 1.33 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.38 | 2606.56 | 1094.51 | 1.00 | 1.26 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9964.77 | 11957.72 | 50.48 | 0.937 | 1.125 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00805 | 31.16 | 0.00627 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 27068.38 | 32482.05 | 23.31 | 1.985 | 2.381 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 26.70 | 26.70 | 0.00758 | 31.37 | 0.00627 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00432 | 33.40 | 0.00627 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12362.22 | 14834.66 | 62.63 | 0.397 | 0.476 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00761 | -27.60 | 0.00034 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 53923.65 | 64708.38 | 46.44 | 1.458 | 1.749 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.55 | 0.00613 | -27.60 | 0.00034 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 134003.36 | 160804.03 | 50.18 | 3.688 | 4.426 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 10.00 | 9.99 | 0.00873 | -27.60 | 0.00034 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.12 | 1.12 | 0.48 | 0.48 | 1.1248 | 1.1248 | 1.1248 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.38 | 2.38 | 1.75 | 1.75 | 2.3815 | 2.3815 | 2.3815 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 160804.036 | 160804.036 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 160804.04 | 160804.04 | 4.425975 | 1.69 | 1.69 | 0.00688182 | 43.33 | 25.35 | 0.01600000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 9.99 | 0.00873401 | 100.0000 | 160804.03 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 18618.860 | 0.000 | 1.124770 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 18618.86 | 18618.86 | 1.124770 | 24.56 | 14.68 | 0.00788389 | 12.00 | 10.08 | 0.00800000 | 31.16 | 0.00626593 | 15.56 | 9.0938 | 23.90 | 0.00804574 | 38.1351 | 9964.77 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 27822.297 | 27822.297 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 27822.30 | 27822.30 | 1.124765 | 10.60 | 7.44 | 0.00604893 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 9.0939 | 21.10 | 0.00760945 | 42.7907 | 12362.22 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 46871.220 | 0.000 | 2.381490 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 46871.22 | 46871.22 | 2.381490 | 27.90 | 15.50 | 0.00751218 | 12.00 | 10.08 | 0.00800000 | 33.40 | 0.00626594 | 16.30 | 17.8339 | 26.70 | 0.00757986 | 30.4353 | 26868.01 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 81008.190 | 81008.190 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 81008.19 | 81008.19 | 2.381491 | 5.08 | 3.25 | 0.00472293 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 17.8339 | 15.55 | 0.00612776 | 48.9268 | 53923.65 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 160804.036 | 160804.036 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.0531 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 4.425975 | 4.66117073 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 160804.04 | 160804.04 | 1.0000 | 4.66117073 | 4.425975 | 1.69 | 1.69 | 0.00688182 | 18932.9 | 43.33 | 25.35 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 160804.04 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 9.99 | 0.00873401 | 9.99 | 0.00873401 | 100.0000 | 160804.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18618.860 | 0.000 | 1.124770 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4958 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 18618.86 | 18618.86 | 1.0000 | 1.18454014 | 1.124770 | 24.56 | 14.68 | 0.00788389 | 44755.9 | 12.00 | 10.08 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18618.86 | 31.16 | 0.00626593 | 15.56 | 0.10228487 | 9.0938 | 23.90 | 0.00804574 | 23.90 | 0.00804574 | 38.1351 | 9964.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27822.297 | 27822.297 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.124765 | 1.18453540 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 27822.30 | 27822.30 | 1.0000 | 1.18453540 | 1.124765 | 10.60 | 7.44 | 0.00604893 | 25902.1 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27822.30 | -27.60 | 0.00034190 | -27.60 | 0.10228487 | 9.0939 | 21.05 | 0.00760945 | 21.10 | 0.00760945 | 42.7907 | 12362.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 46871.220 | 0.000 | 2.381490 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.8048 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 46871.22 | 46871.22 | 1.0000 | 2.50804209 | 2.381490 | 27.90 | 15.50 | 0.00751218 | 47216.5 | 12.00 | 10.08 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 46871.22 | 33.40 | 0.00626594 | 16.30 | 0.42471267 | 17.8339 | 26.70 | 0.00778512 | 26.70 | 0.00757986 | 30.4353 | 26868.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 81008.190 | 81008.190 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.381491 | 2.50804355 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 81008.19 | 81008.19 | 1.0000 | 2.50804355 | 2.381491 | 5.08 | 3.25 | 0.00472293 | 16955.9 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 81008.19 | -27.60 | 0.00034190 | -27.60 | 0.42471267 | 17.8339 | 15.55 | 0.00612776 | 15.55 | 0.00612776 | 48.9268 | 53923.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE OA CONTROLLER | DifferentialDryBulb | 0.10 | 1.12 | - | |||
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 2.38 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2527.00 | 3007.00 | 2212.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2527.00 | 3007.00 | 2212.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 132.00 | 1.00 | 66.00 | 1.00 |
ZONE2 FINE STORAGE | 626.00 | 16.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5.50 | 0.00 | 0.00 | 0.00 |
Facility | 721.83 | 17.00 | 66.00 | 1.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.620 | 0.436 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.72 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 810.36 | 5421.86 | 01-JAN-14:00 | 66482.87 | 17-JUL-14:10 |
Electricity:Building | 616.77 | 4938.86 | 01-JAN-00:10 | 47606.95 | 14-JUL-14:50 |
Electricity:Zone:ZONE1 OFFICE | 62.57 | 1027.15 | 01-JAN-00:10 | 3852.05 | 02-JAN-08:10 |
InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.62 | 453.40 | 01-JAN-00:10 | 1939.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 419.20 | 2726.34 | 01-JAN-00:10 | 33679.30 | 14-JUL-14:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 310.51 | 2726.34 | 01-JAN-00:10 | 23173.88 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 26.70 | 483.00 | 06-JAN-20:40 | 2853.97 | 17-FEB-12:50 |
WaterSystems:Electricity | 26.70 | 483.00 | 06-JAN-20:40 | 2853.97 | 17-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 26.70 | 483.00 | 06-JAN-20:40 | 2853.97 | 17-FEB-12:50 |
Fans:Electricity | 59.13 | 0.00 | 01-JAN-14:00 | 6194.21 | 15-JUL-15:50 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 1.36 | 0.00 | 01-JAN-00:10 | 2305.29 | 15-JUL-17:20 |
Ventilation (simple):Fans:Electricity | 1.36 | 0.00 | 01-JAN-00:10 | 2305.29 | 15-JUL-17:20 |
ElectricityPurchased:Facility | 810.36 | 5421.86 | 01-JAN-14:00 | 66482.87 | 17-JUL-14:10 |
ElectricityPurchased:Plant | 810.36 | 5421.86 | 01-JAN-14:00 | 66482.87 | 17-JUL-14:10 |
Cogeneration:ElectricityPurchased | 810.36 | 5421.86 | 01-JAN-14:00 | 66482.87 | 17-JUL-14:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 810.36 | 5421.86 | 01-JAN-14:00 | 66482.87 | 17-JUL-14:10 |
ElectricityNet:Plant | 810.36 | 5421.86 | 01-JAN-14:00 | 66482.87 | 17-JUL-14:10 |
Cogeneration:ElectricityNet | 810.36 | 5421.86 | 01-JAN-14:00 | 66482.87 | 17-JUL-14:10 |
Electricity:HVAC | 67.89 | 0.00 | 01-JAN-14:00 | 19606.71 | 17-JUL-16:00 |
General:Fans:Electricity | 57.77 | 0.00 | 01-JAN-14:00 | 4300.13 | 23-JAN-12:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 10.12 | 0.00 | 01-JAN-00:10 | 15717.79 | 17-JUL-16:00 |
ExteriorLights:Electricity | 99.00 | 0.00 | 01-JAN-08:20 | 6311.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 99.00 | 0.00 | 01-JAN-08:20 | 6311.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1019.63 | 0.00 | 01-JAN-13:20 | 336668.93 | 05-JAN-18:00 |
Gas:HVAC | 1019.63 | 0.00 | 01-JAN-13:20 | 336668.93 | 05-JAN-18:00 |
Heating:Gas | 1019.63 | 0.00 | 01-JAN-13:20 | 336668.93 | 05-JAN-18:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1616.04 | 0.00 | 01-JAN-14:00 | 521826.06 | 05-JAN-18:00 |
EnergyTransfer:Building | 803.87 | 0.00 | 01-JAN-14:00 | 260294.60 | 06-JAN-07:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 61.49 | 0.00 | 01-JAN-00:40 | 29339.98 | 09-JAN-07:10 |
Heating:EnergyTransfer | 766.14 | 0.00 | 01-JAN-14:00 | 260294.60 | 06-JAN-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 47.18 | 0.00 | 01-JAN-00:40 | 29339.98 | 09-JAN-07:10 |
Cooling:EnergyTransfer | 37.73 | 0.00 | 01-JAN-00:10 | 38096.52 | 17-JUL-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 14.31 | 0.00 | 01-JAN-00:10 | 11679.78 | 17-JUL-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 253.22 | 0.00 | 01-JAN-00:40 | 80492.84 | 05-JAN-19:30 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 229.81 | 0.00 | 01-JAN-00:40 | 80492.84 | 05-JAN-19:30 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 23.42 | 0.00 | 01-JAN-00:10 | 27858.55 | 17-JUL-16:00 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 489.15 | 0.00 | 01-JAN-13:30 | 162669.73 | 05-JAN-16:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 489.15 | 0.00 | 01-JAN-13:30 | 162669.73 | 05-JAN-16:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 812.17 | 0.00 | 01-JAN-13:20 | 269261.30 | 05-JAN-18:00 |
HeatingCoils:EnergyTransfer | 776.98 | 0.00 | 01-JAN-13:20 | 269261.30 | 05-JAN-18:00 |
CoolingCoils:EnergyTransfer | 35.20 | 0.00 | 01-JAN-00:10 | 48104.44 | 17-JUL-16:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 47.177 | -14.314 | 0.000 | 0.000 | 3.987 | 30.619 | 31.946 | 9.574 | 0.000 | 0.720 | 0.000 | 0.000 | -13.151 | 0.000 | -33.469 | -63.090 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 229.808 | -23.416 | 0.000 | 0.000 | 0.000 | 135.003 | 0.000 | 0.000 | 0.000 | 2.320 | 0.001 | 0.000 | 0.000 | 0.000 | -214.278 | -129.437 |
ZONE3 BULK STORAGE | 489.151 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 310.507 | 107.336 | 18.584 | 0.000 | 28.385 | 0.000 | 0.000 | -12.203 | 0.000 | -701.787 | -239.972 |
Total Facility | 489.151 | 0.000 | 276.984 | -37.729 | 0.000 | 0.000 | 3.987 | 476.129 | 139.282 | 28.158 | 0.000 | 31.425 | 0.001 | 0.000 | -25.355 | 0.000 | -949.534 | -432.499 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 12-AUG-05:01 | 0.00 | 0.00 | 0.00 | -26147.37 | 0.00 | 0.00 | 32.03 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 25776.85 | 0.00 | -607.70 | 0.00 | -206.91 | 0.00 |
ZONE2 FINE STORAGE | 17-JUL-22:31 | 0.00 | 0.00 | 0.00 | -46523.06 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 46045.08 | 0.00 | -0.00 | 0.00 | -707.38 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-JUL-22:31 | 0.00 | 0.00 | 0.00 | -46523.06 | 0.00 | 0.00 | 0.00 | 4365.11 | 2623.78 | 0.00 | 0.00 | 0.00 | 46717.55 | 0.00 | -769.35 | 0.00 | -6414.03 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 09-JAN-06:31 | 0.00 | 0.00 | 30925.88 | 0.00 | 0.00 | 0.00 | 58.29 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1640.10 | 0.00 | -3359.69 | -27137.48 |
ZONE2 FINE STORAGE | 06-JAN-06:01 | 0.00 | 0.00 | 87208.60 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -25989.17 | -62404.80 |
ZONE3 BULK STORAGE | 05-JAN-15:55 | 163017.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 28323.53 | 0.00 | -1003.52 | 0.00 | -221711.05 | 0.00 |
Total Facility | 06-JAN-06:42 | 161232.02 | 0.00 | 109098.79 | 0.00 | 0.00 | 0.00 | 46.49 | 4491.05 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3308.65 | 0.00 | -154851.23 | -119332.25 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1248 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.1248 | 0.0909 | 1.0000 | 0.1023 | 0.0909 | ||
PSZ-FINE STORAGE | 2.3815 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.3815 | 0.1783 | 1.0000 | 0.4247 | 0.1783 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1248 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 1.1248 | 1.0000 | 1.0000 | 0.1023 | 0.0909 | ||
PSZ-FINE STORAGE | 2.3815 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 2.3815 | 1.0000 | 1.0000 | 0.4247 | 0.1783 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.1248 | 1.1248 | 1.1248 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.3815 | 2.3815 | 2.3815 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1248 | 1.1248 | 1.1248 | 1.1248 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.3815 | 2.3815 | 2.3815 | 2.3815 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.1248 | 1.1248 | 1.1248 | 0.1023 | 0.2147 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.3815 | 2.3815 | 2.3815 | 0.4247 | 0.2428 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1248 | 1.1248 | 1.1248 | 1.1248 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.3815 | 2.3815 | 2.3815 | 2.3815 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:44
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 66.00 |
Number of hours cooling loads not met | 1.00 |
Number of hours not met | 67.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 1019.63 | 336668.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 10.12 | 15717.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 476.13 | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 99.00 | 6311.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 1.36 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 57.77 | 4300.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.70 | 2853.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 810.36 |
Natural Gas | 0.00 | 1019.63 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1830.00 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 98.47 |
Space Heating | 0.00 |
Space Cooling | 2.09 |
Fans (All) | 12.23 |
Service Water Heating | 5.52 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 167.60 |
Subtotal | 167.60 |
Natural Gas [MJ/m2] | |
Space Heating | 210.88 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 210.88 |
Subtotal | 210.88 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 26.02 |
Space Heating | 55.72 |
Space Cooling | 0.55 |
Fans (All) | 3.23 |
Service Water Heating | 1.46 |
Receptacle Equipment | 7.61 |
Miscellaneous | 5.41 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.328151E+12 |
February | 0.000 | 0.180740E+12 |
March | 0.000 | 0.127102E+12 |
April | 0.000 | 0.278663E+11 |
May | 0.000 | 0.204236E+11 |
June | 0.000 | 0.167767E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.237711E+08 |
September | 0.000 | 0.263096E+10 |
October | 0.000 | 0.114126E+11 |
November | 0.000 | 0.980789E+11 |
December | 0.000 | 0.223037E+12 |
Annual Sum or Average | 0.101963E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.328151E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.328151E+12 |
February | 0.000 | 0.180740E+12 |
March | 0.000 | 0.127102E+12 |
April | 0.000 | 0.278663E+11 |
May | 0.000 | 0.204236E+11 |
June | 0.000 | 0.167767E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.237711E+08 |
September | 0.000 | 0.263096E+10 |
October | 0.000 | 0.114126E+11 |
November | 0.000 | 0.980789E+11 |
December | 0.000 | 0.223037E+12 |
Annual Sum or Average | 0.101963E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.328151E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Meter
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.328151E+12 |
February | 0.000 | 0.180740E+12 |
March | 0.000 | 0.127102E+12 |
April | 0.000 | 0.278663E+11 |
May | 0.000 | 0.204236E+11 |
June | 0.000 | 0.167767E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.237711E+08 |
September | 0.000 | 0.263096E+10 |
October | 0.000 | 0.114126E+11 |
November | 0.000 | 0.980789E+11 |
December | 0.000 | 0.223037E+12 |
Annual Sum or Average | 0.101963E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.328151E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.328151E+12 |
February | 0.000 | 0.180740E+12 |
March | 0.000 | 0.127102E+12 |
April | 0.000 | 0.278663E+11 |
May | 0.000 | 0.204236E+11 |
June | 0.000 | 0.167767E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.237711E+08 |
September | 0.000 | 0.263096E+10 |
October | 0.000 | 0.114126E+11 |
November | 0.000 | 0.980789E+11 |
December | 0.000 | 0.223037E+12 |
Annual Sum or Average | 0.101963E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.328151E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.328151E+12 |
February | 0.000 | 0.180740E+12 |
March | 0.000 | 0.127102E+12 |
April | 0.000 | 0.278663E+11 |
May | 0.000 | 0.204236E+11 |
June | 0.000 | 0.167767E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.237711E+08 |
September | 0.000 | 0.263096E+10 |
October | 0.000 | 0.114126E+11 |
November | 0.000 | 0.980789E+11 |
December | 0.000 | 0.223037E+12 |
Annual Sum or Average | 0.101963E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.328151E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.328151E+12 |
February | 0.000 | 0.180740E+12 |
March | 0.000 | 0.127102E+12 |
April | 0.000 | 0.278663E+11 |
May | 0.000 | 0.204236E+11 |
June | 0.000 | 0.167767E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.237711E+08 |
September | 0.000 | 0.263096E+10 |
October | 0.000 | 0.114126E+11 |
November | 0.000 | 0.980789E+11 |
December | 0.000 | 0.223037E+12 |
Annual Sum or Average | 0.101963E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.328151E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.328151E+12 |
February | 0.000 | 0.180740E+12 |
March | 0.000 | 0.127102E+12 |
April | 0.000 | 0.278663E+11 |
May | 0.000 | 0.204236E+11 |
June | 0.000 | 0.167767E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.237711E+08 |
September | 0.000 | 0.263096E+10 |
October | 0.000 | 0.114126E+11 |
November | 0.000 | 0.980789E+11 |
December | 0.000 | 0.223037E+12 |
Annual Sum or Average | 0.101963E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.328151E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Meter
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.328151E+12 |
February | 0.000 | 0.180740E+12 |
March | 0.000 | 0.127102E+12 |
April | 0.000 | 0.278663E+11 |
May | 0.000 | 0.204236E+11 |
June | 0.000 | 0.167767E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.237711E+08 |
September | 0.000 | 0.263096E+10 |
October | 0.000 | 0.114126E+11 |
November | 0.000 | 0.980789E+11 |
December | 0.000 | 0.223037E+12 |
Annual Sum or Average | 0.101963E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.328151E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Meter
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.328151E+12 |
February | 0.000 | 0.180740E+12 |
March | 0.000 | 0.127102E+12 |
April | 0.000 | 0.278663E+11 |
May | 0.000 | 0.204236E+11 |
June | 0.000 | 0.167767E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.237711E+08 |
September | 0.000 | 0.263096E+10 |
October | 0.000 | 0.114126E+11 |
November | 0.000 | 0.980789E+11 |
December | 0.000 | 0.223037E+12 |
Annual Sum or Average | 0.101963E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.328151E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.38 | -1.1 | 0.194878E+09 | 236.59 | 11-JAN-09:20 | -8.5 | -9.8 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -12.4 | -13.8 | 0.179796E+09 | 271.04 | 27-FEB-16:10 | 17.78 | 6.89 |
March | 424687.26 | 153.50 | 01-MAR-17:00 | 7.80 | 3.21 | 0.210703E+09 | 246.13 | 02-MAR-16:10 | 10.22 | 4.58 |
April | 341943.41 | 165.35 | 25-APR-16:00 | 17.80 | 7.67 | 0.201228E+09 | 301.58 | 07-APR-14:39 | 22.23 | 9.13 |
May | 0.338086E+09 | 4146.36 | 19-MAY-16:00 | 27.80 | 14.51 | 0.223008E+09 | 301.59 | 20-MAY-10:20 | 21.47 | 13.26 |
June | 0.257270E+10 | 21964.39 | 26-JUN-05:03 | 9.87 | 8.82 | 0.253244E+09 | 301.62 | 20-JUN-10:50 | 23.43 | 14.99 |
July | 0.507454E+10 | 24432.34 | 22-JUL-05:02 | 8.77 | 7.16 | 0.248638E+09 | 301.62 | 03-JUL-12:30 | 21.20 | 14.36 |
August | 0.444195E+10 | 26147.51 | 12-AUG-05:01 | 13.07 | 6.76 | 0.267160E+09 | 301.62 | 01-AUG-12:00 | 22.20 | 14.62 |
September | 0.180244E+10 | 22838.26 | 02-SEP-05:02 | 14.40 | 8.77 | 0.233283E+09 | 301.61 | 07-SEP-10:50 | 17.62 | 16.50 |
October | 81255946.57 | 2390.48 | 18-OCT-16:00 | 24.40 | 10.99 | 0.211210E+09 | 301.59 | 16-OCT-13:39 | 21.10 | 9.67 |
November | 2431116.74 | 210.41 | 06-NOV-15:40 | 7.40 | 2.69 | 0.188726E+09 | 284.61 | 04-NOV-15:09 | 16.60 | 7.87 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -2.1 | -4.1 | 0.194946E+09 | 236.59 | 14-DEC-11:09 | -6.2 | -6.7 |
Annual Sum or Average | 0.143142E+11 | 0.260682E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -12.4 | -13.8 | 0.179796E+09 | 236.59 | -8.5 | -9.8 | ||
Maximum of Months | 0.507454E+10 | 26147.51 | 27.80 | 14.51 | 0.267160E+09 | 301.62 | 23.43 | 16.50 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14561703.47 | 896.95 | 14-JAN-10:50 | 7.85 | 3.81 | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 | -1.1 |
February | 0.122220E+09 | 3368.04 | 23-FEB-16:00 | -0.6 | -3.4 | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 | -13.8 |
March | 0.526333E+09 | 4790.10 | 25-MAR-11:00 | -0.6 | -2.6 | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.0 |
April | 0.543819E+09 | 5028.66 | 08-APR-06:10 | 8.30 | 5.01 | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.54 |
May | 0.682534E+09 | 7201.10 | 13-MAY-06:10 | 8.45 | 4.49 | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -2.9 |
June | 0.269363E+10 | 45965.74 | 25-JUN-16:01 | 24.32 | 12.86 | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.35 |
July | 0.862165E+10 | 46522.50 | 17-JUL-22:31 | 24.07 | 13.46 | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.31 |
August | 0.644436E+10 | 45425.28 | 09-AUG-20:41 | 24.55 | 12.95 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.94 |
September | 0.256147E+10 | 43534.31 | 04-SEP-19:37 | 25.33 | 14.42 | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.58 |
October | 0.706246E+09 | 5034.71 | 21-OCT-08:70 | -0.5 | -1.4 | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.93 |
November | 0.431846E+09 | 3632.95 | 20-NOV-15:00 | 2.00 | -2.6 | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.53 |
December | 67520969.08 | 2628.79 | 09-DEC-13:10 | 3.95 | 0.92 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.1 |
Annual Sum or Average | 0.234162E+11 | 0.00 | ||||||||
Minimum of Months | 14561703.47 | 896.95 | -0.6 | -3.4 | 0.00 | 0.00 | -12.4 | -13.8 | ||
Maximum of Months | 0.862165E+10 | 46522.50 | 25.33 | 14.42 | 0.00 | 0.00 | 19.45 | 13.31 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.38 | -1.1 | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 | -1.1 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -12.4 | -13.8 | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 | -13.8 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -3.0 | -4.0 | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.54 | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.54 |
May | 0.00 | 0.00 | 01-MAY-00:02 | -1.1 | -2.9 | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -2.9 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.35 | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.31 | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.31 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.94 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.94 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.58 | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.58 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.93 | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.53 | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.53 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -2.1 | -4.1 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.1 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -12.4 | -13.8 | 0.00 | 0.00 | -12.4 | -13.8 | ||
Maximum of Months | 0.00 | 0.00 | 19.45 | 13.31 | 0.00 | 0.00 | 19.45 | 13.31 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113703E+11 | 30925.79 | 09-JAN-06:31 | -27.2 |
February | 0.735768E+10 | 28618.48 | 02-FEB-06:31 | -13.5 |
March | 0.652883E+10 | 29951.26 | 03-MAR-06:41 | -12.8 |
April | 0.334711E+10 | 28305.12 | 29-APR-05:12 | -7.6 |
May | 0.235680E+10 | 28242.54 | 08-MAY-05:12 | -2.8 |
June | 0.240879E+09 | 27884.35 | 17-JUN-05:01 | 2.35 |
July | 43692058.87 | 2077.10 | 18-JUL-06:05 | 20.15 |
August | 0.106388E+09 | 5226.19 | 18-AUG-05:55 | 7.80 |
September | 0.762690E+09 | 28148.12 | 19-SEP-05:01 | 2.20 |
October | 0.202056E+10 | 28339.67 | 10-OCT-05:12 | -6.1 |
November | 0.484777E+10 | 30394.75 | 27-NOV-06:31 | -14.0 |
December | 0.819434E+10 | 29027.79 | 28-DEC-07:13 | -22.8 |
Annual Sum or Average | 0.471770E+11 | |||
Minimum of Months | 43692058.87 | 2077.10 | -27.2 | |
Maximum of Months | 0.113703E+11 | 30925.79 | 20.15 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.628465E+11 | 87208.60 | 06-JAN-06:01 | -25.1 |
February | 0.380308E+11 | 84669.45 | 17-FEB-04:01 | -0.7 |
March | 0.296783E+11 | 86262.15 | 06-MAR-06:01 | -16.3 |
April | 0.114558E+11 | 83736.85 | 29-APR-04:22 | -7.8 |
May | 0.756120E+10 | 83812.83 | 08-MAY-04:22 | -2.5 |
June | 0.427592E+09 | 2818.30 | 01-JUN-07:00 | 11.70 |
July | 0.209891E+09 | 2533.51 | 08-JUL-07:00 | 11.70 |
August | 0.329824E+09 | 2617.17 | 01-AUG-07:00 | 14.40 |
September | 0.180798E+10 | 80624.16 | 20-SEP-05:23 | 3.30 |
October | 0.611921E+10 | 82746.24 | 10-OCT-00:52 | -2.2 |
November | 0.252062E+11 | 83898.88 | 30-NOV-22:42 | -3.1 |
December | 0.461345E+11 | 84700.19 | 03-DEC-00:41 | -1.2 |
Annual Sum or Average | 0.229808E+12 | |||
Minimum of Months | 0.209891E+09 | 2533.51 | -25.1 | |
Maximum of Months | 0.628465E+11 | 87208.60 | 14.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173514E+12 | 163017.45 | 05-JAN-15:55 | -19.4 |
February | 0.897804E+11 | 119368.23 | 03-FEB-19:00 | -16.7 |
March | 0.585621E+11 | 123133.71 | 04-MAR-01:52 | -18.3 |
April | 0.522174E+10 | 53934.09 | 29-APR-04:51 | -7.8 |
May | 0.567595E+10 | 52420.49 | 08-MAY-06:00 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 0.347181E+09 | 18331.02 | 11-OCT-05:56 | 0.00 |
November | 0.434011E+11 | 108363.39 | 27-NOV-05:00 | -15.6 |
December | 0.112649E+12 | 161530.90 | 31-DEC-03:03 | -24.5 |
Annual Sum or Average | 0.489152E+12 | |||
Minimum of Months | 0.00 | 0.00 | -24.5 | |
Maximum of Months | 0.173514E+12 | 163017.45 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.256100E+10 | 1939.55 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.233575E+10 | 1939.55 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.266872E+10 | 1939.55 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.252182E+10 | 1939.55 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.261486E+10 | 1939.55 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.257569E+10 | 1939.55 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.256100E+10 | 1939.55 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.266872E+10 | 1939.55 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.252182E+10 | 1939.55 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.256100E+10 | 1939.55 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.246796E+10 | 1939.55 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.256100E+10 | 1939.55 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.306193E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.233575E+10 | 1939.55 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.266872E+10 | 1939.55 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112294E+11 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102778E+11 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.118738E+11 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.111270E+11 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.115516E+11 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.114492E+11 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112294E+11 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.118738E+11 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.111270E+11 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112294E+11 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108048E+11 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112294E+11 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135003E+12 | ||||
Minimum of Months | 0.102778E+11 | 10075.60 | 0.00 | 0.00 | |
Maximum of Months | 0.118738E+11 | 10075.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.258277E+11 | 23173.88 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.236390E+11 | 23173.88 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.273097E+11 | 23173.88 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.255921E+11 | 23173.88 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.265687E+11 | 23173.88 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.263332E+11 | 23173.88 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.258277E+11 | 23173.88 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.273097E+11 | 23173.88 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.255921E+11 | 23173.88 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.258277E+11 | 23173.88 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.248511E+11 | 23173.88 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.258277E+11 | 23173.88 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.236390E+11 | 23173.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.273097E+11 | 23173.88 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586743E+10 |
February | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418173E+10 |
March | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388763E+10 |
April | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 312625.08 | 0.240549E+10 |
May | 0.565842E+09 | 0.261486E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14475587.80 | 0.231007E+10 |
June | 0.565842E+09 | 0.257569E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125387E+09 | 0.127153E+10 |
July | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301229E+09 | 0.714934E+09 |
August | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226014E+09 | 0.102732E+10 |
September | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49941910.78 | 0.166115E+10 |
October | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2878237.84 | 0.224802E+10 |
November | 0.522316E+09 | 0.246796E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334234E+10 |
December | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455105E+10 |
Annual Sum or Average | 0.659424E+10 | 0.306193E+11 | 0.319458E+11 | 0.720238E+09 | 0.334687E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714934E+09 |
Maximum of Months | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301229E+09 | 0.586743E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383439E+11 |
February | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268131E+11 |
March | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239351E+11 |
April | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15938559.24 | 0.138881E+11 |
May | 0.00 | 0.115516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85697917.91 | 0.136164E+11 |
June | 0.00 | 0.114492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259775E+09 | 0.894434E+10 |
July | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812688E+09 | 0.672139E+10 |
August | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730331E+09 | 0.777351E+10 |
September | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351631E+09 | 0.108370E+11 |
October | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64189265.28 | 0.124666E+11 |
November | 0.00 | 0.108048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210070E+11 |
December | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299313E+11 |
Annual Sum or Average | 0.135003E+12 | 0.232025E+10 | 0.214278E+12 | ||||||
Minimum of Months | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672139E+10 |
Maximum of Months | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812688E+09 | 0.383439E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100107E+12 |
February | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701038E+09 | 0.586775E+11 |
March | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75439304.78 | 0.519515E+11 |
April | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229735E+10 | 0.268976E+11 |
May | 0.00 | 0.265687E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337143E+10 | 0.273220E+11 |
June | 0.00 | 0.263332E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130992E+10 | 0.242964E+11 |
July | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571672E+09 | 0.257208E+11 |
August | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428945E+09 | 0.303971E+11 |
September | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170939E+10 | 0.347338E+11 |
October | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239189E+10 | 0.293063E+11 |
November | 0.00 | 0.248511E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121765E+10 | 0.436611E+11 |
December | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203377E+09 | 0.686962E+11 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | 0.142781E+11 | 0.521767E+12 | |||||
Minimum of Months | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242964E+11 |
Maximum of Months | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337143E+10 | 0.100107E+12 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1939.55 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 19924.77 | 27-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1939.55 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 17452.51 | 01-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1939.55 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 15690.49 | 06-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1939.55 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.07 | 16-APR-14:00 | 8838.06 | 28-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1939.55 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1518.82 | 19-MAY-16:10 | 10476.71 | 22-MAY-06:02 |
June | 659.25 | 01-JUN-07:10 | 1939.55 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2562.09 | 29-JUN-16:10 | 6786.10 | 16-JUN-07:00 |
July | 659.25 | 01-JUL-07:10 | 1939.55 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4342.03 | 17-JUL-16:10 | 4816.26 | 05-JUL-06:03 |
August | 659.25 | 01-AUG-07:10 | 1939.55 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2950.94 | 10-AUG-17:00 | 5696.64 | 17-AUG-16:03 |
September | 659.25 | 01-SEP-07:10 | 1939.55 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1590.97 | 01-SEP-16:10 | 7184.00 | 19-SEP-06:10 |
October | 659.25 | 02-OCT-07:10 | 1939.55 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.15 | 15-OCT-14:00 | 10397.70 | 10-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1939.55 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13757.47 | 27-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1939.55 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 17880.28 | 29-DEC-08:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4816.26 | |||||
Maximum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4342.03 | 19924.77 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 70283.94 | 05-JAN-16:03 |
February | 0.00 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 37807.40 | 01-FEB-17:00 |
March | 0.00 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 32889.45 | 30-MAR-08:00 |
April | 0.00 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 822.29 | 16-APR-16:00 | 23846.50 | 28-APR-16:00 |
May | 0.00 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3355.25 | 20-MAY-16:00 | 43875.06 | 22-MAY-06:06 |
June | 0.00 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.93 | 29-JUN-15:10 | 17282.48 | 06-JUN-16:53 |
July | 0.00 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8825.48 | 25-JUL-15:10 | 12298.66 | 08-JUL-07:00 |
August | 0.00 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7596.80 | 09-AUG-17:00 | 24047.23 | 17-AUG-15:03 |
September | 0.00 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8172.99 | 02-SEP-15:10 | 21991.53 | 18-SEP-16:00 |
October | 0.00 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3393.80 | 15-OCT-14:00 | 19527.01 | 31-OCT-16:00 |
November | 0.00 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 32367.05 | 28-NOV-08:00 |
December | 0.00 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 36965.81 | 31-DEC-03:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12298.66 | |||
Maximum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8825.48 | 70283.94 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23173.88 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 173879.53 | 05-JAN-15:55 |
February | 0.00 | 23173.88 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13271.11 | 27-FEB-13:10 | 97811.43 | 01-FEB-15:00 |
March | 0.00 | 23173.88 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6625.62 | 14-MAR-12:10 | 79121.68 | 03-MAR-09:00 |
April | 0.00 | 23173.88 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25364.80 | 07-APR-12:10 | 56090.05 | 27-APR-11:00 |
May | 0.00 | 23173.88 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33570.16 | 19-MAY-16:00 | 86976.00 | 22-MAY-08:00 |
June | 0.00 | 23173.88 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15569.35 | 29-JUN-13:00 | 46525.50 | 14-JUN-08:00 |
July | 0.00 | 23173.88 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10689.45 | 13-JUL-16:00 | 39152.40 | 08-JUL-10:00 |
August | 0.00 | 23173.88 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9533.54 | 25-AUG-16:00 | 85416.55 | 17-AUG-12:05 |
September | 0.00 | 23173.88 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17387.01 | 23-SEP-14:00 | 66954.73 | 12-SEP-11:00 |
October | 0.00 | 23173.88 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25866.00 | 12-OCT-12:10 | 41784.37 | 03-OCT-09:00 |
November | 0.00 | 23173.88 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15103.04 | 17-NOV-14:00 | 73054.66 | 27-NOV-11:00 |
December | 0.00 | 23173.88 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12798.85 | 10-DEC-02:00 | 127279.42 | 27-DEC-14:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39152.40 | ||||
Maximum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 33570.16 | 173879.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1813.61 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.63 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 3173.81 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1405.05 |
March | 153.50 | 01-MAR-17:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 808.58 |
April | 165.35 | 25-APR-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.95 |
May | 4146.36 | 19-MAY-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 637.09 | 0.00 |
June | 21964.39 | 26-JUN-05:03 | 290.07 | 2317.39 | 2295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 944.01 |
July | 24432.34 | 22-JUL-05:02 | 362.59 | 2896.74 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 26147.51 | 12-AUG-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.91 |
September | 22838.26 | 02-SEP-05:02 | 362.59 | 2896.74 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.01 |
October | 2390.48 | 18-OCT-16:00 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 56.22 | 0.00 |
November | 210.41 | 06-NOV-15:40 | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 848.96 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 2720.41 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1244.11 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 1813.61 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26147.51 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 637.09 | 1405.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 896.95 | 14-JAN-10:50 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3222.05 |
February | 3368.04 | 23-FEB-16:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2347.24 |
March | 4790.10 | 25-MAR-11:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5028.66 | 08-APR-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4491.24 |
May | 7201.10 | 13-MAY-06:10 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 821.34 |
June | 45965.74 | 25-JUN-16:01 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1631.08 |
July | 46522.50 | 17-JUL-22:31 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 707.38 |
August | 45425.28 | 09-AUG-20:41 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 873.56 |
September | 43534.31 | 04-SEP-19:37 | 0.00 | 10668.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.47 |
October | 5034.71 | 21-OCT-08:70 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2872.63 |
November | 3632.95 | 20-NOV-15:00 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 947.00 |
December | 2628.79 | 09-DEC-13:10 | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1247.59 |
Annual Sum or Average | |||||||||||
Minimum of Months | 896.95 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46522.50 | 0.00 | 11853.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4491.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 10905.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7271.97 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 19084.37 | 14350.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56574.12 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 8179.02 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11640.14 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14933.19 |
May | 0.00 | 01-MAY-00:02 | 0.00 | 13631.69 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15453.48 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2410.40 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9671.23 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8557.59 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9658.95 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20419.23 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18119.19 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 16358.03 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43258.70 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2410.40 | |
Maximum of Months | 0.00 | 0.00 | 19084.37 | 14350.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56574.12 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.707764E+11 | 53669.05 | 21-JAN-08:09 | 0.328151E+12 | 336668.93 | 05-JAN-17:00 |
February | 0.632842E+11 | 51984.37 | 17-FEB-15:39 | 0.180740E+12 | 234436.73 | 01-FEB-17:00 |
March | 0.710726E+11 | 51973.34 | 03-MAR-13:00 | 0.127102E+12 | 233051.32 | 04-MAR-02:09 |
April | 0.645579E+11 | 51678.97 | 28-APR-12:00 | 0.278663E+11 | 133092.58 | 29-APR-05:10 |
May | 0.658127E+11 | 52842.12 | 20-MAY-14:00 | 0.204236E+11 | 134731.26 | 08-MAY-05:10 |
June | 0.655819E+11 | 59952.52 | 29-JUN-14:00 | 0.167767E+09 | 8375.37 | 17-JUN-05:10 |
July | 0.683534E+11 | 66482.87 | 17-JUL-14:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.714646E+11 | 65411.89 | 10-AUG-14:00 | 23771105.51 | 4878.62 | 18-AUG-06:19 |
September | 0.657318E+11 | 63627.04 | 02-SEP-14:39 | 0.263096E+10 | 39448.41 | 20-SEP-05:30 |
October | 0.667445E+11 | 53236.37 | 30-OCT-07:10 | 0.114126E+11 | 76071.31 | 11-OCT-05:00 |
November | 0.663818E+11 | 53620.90 | 30-NOV-16:49 | 0.980789E+11 | 214389.31 | 27-NOV-04:49 |
December | 0.706031E+11 | 53664.13 | 29-DEC-08:09 | 0.223037E+12 | 296456.14 | 31-DEC-02:00 |
Annual Sum or Average | 0.810365E+12 | 0.101963E+13 | ||||
Minimum of Months | 0.632842E+11 | 51678.97 | 0.00 | 0.00 | ||
Maximum of Months | 0.714646E+11 | 66482.87 | 0.328151E+12 | 336668.93 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.396181E+11 | 0.107388E+11 | 0.115358E+11 | 0.00 | 0.654530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233845E+10 | 0.00 |
February | 0.362526E+11 | 0.887200E+10 | 0.105871E+11 | 0.00 | 0.542987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214258E+10 | 0.00 |
March | 0.418523E+11 | 0.866374E+10 | 0.123357E+11 | 0.00 | 0.580451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241635E+10 | 0.00 |
April | 0.392410E+11 | 0.721347E+10 | 0.114862E+11 | 0.00 | 0.435661E+10 | 0.00 | 0.00 | 115181.47 | 0.00 | 0.00 | 0.00 | 0.226052E+10 | 0.00 |
May | 0.407352E+11 | 0.641450E+10 | 0.119357E+11 | 0.00 | 0.434704E+10 | 0.00 | 0.00 | 93844582.15 | 0.00 | 0.00 | 0.00 | 0.228640E+10 | 0.00 |
June | 0.403581E+11 | 0.566475E+10 | 0.118862E+11 | 0.00 | 0.402396E+10 | 0.00 | 0.00 | 0.147273E+10 | 0.00 | 0.00 | 0.00 | 0.217621E+10 | 0.00 |
July | 0.396181E+11 | 0.610400E+10 | 0.115358E+11 | 0.00 | 0.467297E+10 | 0.00 | 0.00 | 0.427583E+10 | 0.00 | 0.00 | 0.00 | 0.214665E+10 | 0.00 |
August | 0.418523E+11 | 0.698628E+10 | 0.123357E+11 | 0.00 | 0.488746E+10 | 0.00 | 0.00 | 0.321624E+10 | 0.00 | 0.00 | 0.00 | 0.218667E+10 | 0.00 |
September | 0.392410E+11 | 0.787234E+10 | 0.114862E+11 | 0.00 | 0.398063E+10 | 0.00 | 0.00 | 0.105226E+10 | 0.00 | 0.00 | 0.00 | 0.209937E+10 | 0.00 |
October | 0.396181E+11 | 0.933776E+10 | 0.115358E+11 | 0.00 | 0.405318E+10 | 0.00 | 0.00 | 12032545.04 | 0.00 | 0.00 | 0.00 | 0.218759E+10 | 0.00 |
November | 0.381239E+11 | 0.100951E+11 | 0.110862E+11 | 0.00 | 0.491310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216349E+10 | 0.00 |
December | 0.396181E+11 | 0.110379E+11 | 0.115358E+11 | 0.00 | 0.611509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229614E+10 | 0.00 |
Annual Sum or Average | 0.476129E+12 | 0.990007E+11 | 0.139282E+12 | 0.591297E+11 | 0.00 | 0.101231E+11 | 0.267004E+11 | ||||||
Minimum of Months | 0.362526E+11 | 0.566475E+10 | 0.105871E+11 | 0.00 | 0.398063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209937E+10 | 0.00 |
Maximum of Months | 0.418523E+11 | 0.110379E+11 | 0.123357E+11 | 0.00 | 0.654530E+10 | 0.00 | 0.00 | 0.427583E+10 | 0.00 | 0.00 | 0.00 | 0.241635E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.328151E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.180740E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.127102E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.278663E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.204236E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.167767E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 23771105.51 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.263096E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.114126E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.980789E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.223037E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101963E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.328151E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35189.04 | 02-JAN-09:09 | 6311.00 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4300.13 | 23-JAN-12:39 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35189.04 | 01-FEB-09:09 | 6311.00 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 4300.13 | 06-FEB-12:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35189.04 | 01-MAR-09:09 | 6311.00 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4300.13 | 06-MAR-12:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35189.04 | 01-APR-08:09 | 6311.00 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 4300.13 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35189.04 | 01-MAY-08:09 | 6311.00 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 4300.13 | 08-MAY-12:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35189.04 | 01-JUN-08:09 | 6311.00 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 3888.91 | 06-JUN-15:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35189.04 | 01-JUL-08:09 | 6311.00 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6194.21 | 15-JUL-15:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35189.04 | 01-AUG-08:09 | 6311.00 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6194.21 | 04-AUG-15:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35189.04 | 01-SEP-08:09 | 6311.00 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 6194.21 | 02-SEP-14:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35189.04 | 02-OCT-08:09 | 6311.00 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 4300.13 | 10-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35189.04 | 01-NOV-08:09 | 6311.00 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 4300.13 | 30-NOV-10:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35189.04 | 01-DEC-09:09 | 6311.00 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4300.13 | 01-DEC-14:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35189.04 | 6311.00 | 10112.62 | 0.00 | 3888.91 | 0.00 | 0.00 | |||||
Maximum of Months | 35189.04 | 6311.00 | 10112.62 | 0.00 | 6194.21 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2832.48 | 30-JAN-12:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2853.97 | 17-FEB-12:50 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2842.93 | 04-MAR-12:20 | 0.00 |
April | 95.72 | 07-APR-13:00 | 0.00 | 0.00 | 0.00 | 2752.35 | 01-APR-11:30 | 0.00 |
May | 2848.12 | 20-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2562.07 | 01-MAY-11:30 | 0.00 |
June | 10228.66 | 29-JUN-15:09 | 0.00 | 0.00 | 0.00 | 2273.74 | 03-JUN-11:09 | 0.00 |
July | 15717.79 | 17-JUL-15:00 | 0.00 | 0.00 | 0.00 | 2013.26 | 03-JUL-11:00 | 0.00 |
August | 12885.90 | 10-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1847.33 | 01-AUG-11:00 | 0.00 |
September | 11793.94 | 02-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1953.85 | 29-SEP-11:09 | 0.00 |
October | 903.82 | 18-OCT-15:00 | 0.00 | 0.00 | 0.00 | 2218.68 | 30-OCT-11:00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2474.30 | 28-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2704.35 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1847.33 | 0.00 | ||
Maximum of Months | 15717.79 | 0.00 | 0.00 | 0.00 | 2853.97 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 53669.05 | 21-JAN-08:09 | 31277.33 | 10112.62 | 6311.00 | 0.00 | 4300.13 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 51984.37 | 17-FEB-15:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4300.13 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 51973.34 | 03-MAR-13:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4300.13 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 51678.97 | 28-APR-12:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4300.13 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 52842.12 | 20-MAY-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3888.91 | 0.00 | 0.00 | 1812.21 | 0.00 |
June | 59952.52 | 29-JUN-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 3888.91 | 0.00 | 0.00 | 8978.88 | 0.00 |
July | 66482.87 | 17-JUL-14:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6194.21 | 0.00 | 0.00 | 13212.51 | 0.00 |
August | 65411.89 | 10-AUG-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6194.21 | 0.00 | 0.00 | 12147.66 | 0.00 |
September | 63627.04 | 02-SEP-14:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6194.21 | 0.00 | 0.00 | 10362.72 | 0.00 |
October | 53236.37 | 30-OCT-07:10 | 31277.33 | 10112.62 | 6311.00 | 0.00 | 3888.91 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 53620.90 | 30-NOV-16:49 | 31277.33 | 10112.62 | 6311.00 | 0.00 | 4300.13 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 53664.13 | 29-DEC-08:09 | 31277.33 | 10112.62 | 6311.00 | 0.00 | 4300.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 51678.97 | 31277.33 | 10112.62 | 0.00 | 0.00 | 3888.91 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 66482.87 | 35189.04 | 10112.62 | 6311.00 | 0.00 | 6194.21 | 0.00 | 0.00 | 13212.51 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 336668.93 | 05-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 234436.73 | 01-FEB-17:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 233051.32 | 04-MAR-02:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 133092.58 | 29-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 134731.26 | 08-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 8375.37 | 17-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 4878.62 | 18-AUG-06:19 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 39448.41 | 20-SEP-05:30 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 76071.31 | 11-OCT-05:00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 214389.31 | 27-NOV-04:49 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 296456.14 | 31-DEC-02:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 336668.93 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 43.83 | 15.91 | 10.83 | 19.27 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 19.17 | 16.77 | 8.50 | 19.01 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17.00 | 17.49 | 9.67 | 19.47 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8.00 | 19.67 | 7.67 | 19.87 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6.17 | 19.42 | 5.50 | 19.95 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.17 | 20.46 | 0.17 | 20.46 | 0.17 | 24.51 | 0.17 | 24.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.57 | 0.33 | 24.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.50 | 0.17 | 24.50 |
September | 1.67 | 20.21 | 1.67 | 20.21 | 0.33 | 24.51 | 0.33 | 24.51 |
October | 4.67 | 20.10 | 4.67 | 20.10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.67 | 18.33 | 8.33 | 19.69 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19.67 | 16.98 | 9.00 | 19.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 132.00 | 17.21 | 66.00 | 19.55 | 1.00 | 24.53 | 1.00 | 24.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.83 | 20.46 | 10.83 | 20.46 | 0.33 | 24.57 | 0.33 | 24.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 124.00 | 13.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 96.50 | 13.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 101.67 | 14.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 52.50 | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28.83 | 14.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.31 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.45 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.51 | 0.00 | 0.00 |
September | 5.50 | 14.81 | 0.00 | 0.00 | 3.67 | 27.49 | 0.00 | 0.00 |
October | 22.83 | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 80.67 | 14.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 113.50 | 13.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 626.00 | 14.07 | 0.00 | 16.00 | 27.47 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 124.00 | 14.81 | 0.00 | 0.00 | 6.83 | 27.51 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.50 | 8.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5.50 | 8.45 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.50 | 8.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.03 | 300.00 | 21.03 | 300.00 | 21.03 |
February | 276.00 | 21.05 | 276.00 | 21.05 | 276.00 | 21.05 |
March | 324.00 | 21.06 | 324.00 | 21.06 | 324.00 | 21.06 |
April | 300.00 | 21.37 | 264.83 | 21.15 | 264.83 | 21.15 |
May | 311.17 | 21.98 | 188.33 | 21.15 | 188.33 | 21.15 |
June | 209.67 | 23.23 | 56.17 | 23.15 | 15.00 | 21.14 |
July | 50.00 | 23.65 | 148.17 | 23.89 | 0.00 | 0.00 |
August | 120.67 | 23.47 | 82.17 | 23.87 | 0.83 | 20.98 |
September | 227.50 | 22.65 | 111.00 | 22.37 | 66.67 | 21.35 |
October | 300.00 | 21.84 | 195.67 | 21.18 | 195.67 | 21.18 |
November | 288.00 | 21.13 | 280.67 | 21.10 | 280.67 | 21.10 |
December | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
Annual Sum or Average | 3007.00 | 21.68 | 2527.00 | 21.44 | 2212.00 | 21.10 |
Minimum of Months | 50.00 | 21.03 | 56.17 | 21.03 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 23.65 | 324.00 | 23.89 | 324.00 | 21.35 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 463535.36 | 115181.47 | 1.00 | 463535.36 | 0.00 | 0.00 | 0.03 | 07-APR-14:00 | 0.00 | 01-APR-00:10 | 385.66 | 07-APR-14:00 | 385.66 | 07-APR-14:00 | 0.00 | 01-APR-00:10 | 95.72 | 07-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.353192E+09 | 88023226.95 | 49.33 | 0.352190E+09 | 1001768.49 | 0.00 | 0.38 | 20-MAY-16:00 | 0.00 | 01-MAY-00:02 | 5872.16 | 20-MAY-16:00 | 5872.16 | 20-MAY-16:00 | 103.48 | 20-MAY-11:00 | 1561.73 | 20-MAY-16:00 | 0.00 | 01-MAY-00:02 |
June | 0.240411E+10 | 0.598624E+09 | 182.52 | 0.231544E+10 | 88665493.44 | 0.00 | 1.00 | 22-JUN-05:03 | 0.00 | 01-JUN-00:10 | 17711.41 | 22-JUN-05:03 | 15527.39 | 23-JUN-05:01 | 5058.71 | 24-JUN-05:03 | 3755.84 | 22-JUN-05:03 | 0.00 | 01-JUN-00:10 |
July | 0.537024E+10 | 0.134570E+10 | 241.76 | 0.520647E+10 | 0.163771E+09 | 0.00 | 1.00 | 01-JUL-05:02 | 0.00 | 01-JUL-00:10 | 19452.57 | 19-JUL-05:01 | 17419.67 | 25-JUL-05:51 | 6779.44 | 19-JUL-05:09 | 4129.11 | 17-JUL-16:10 | 0.00 | 01-JUL-00:10 |
August | 0.430273E+10 | 0.108166E+10 | 226.97 | 0.427056E+10 | 32167263.94 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 17166.90 | 08-AUG-05:01 | 17127.93 | 11-AUG-05:15 | 3974.27 | 14-AUG-05:03 | 3636.69 | 08-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.154098E+10 | 0.378516E+09 | 112.63 | 0.142059E+10 | 0.120394E+09 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 18254.09 | 07-SEP-05:01 | 16786.34 | 05-SEP-05:01 | 6364.13 | 07-SEP-05:13 | 3868.72 | 07-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 48941422.67 | 12032545.04 | 16.33 | 48941422.67 | 0.00 | 0.00 | 0.25 | 18-OCT-16:00 | 0.00 | 01-OCT-00:10 | 3727.18 | 18-OCT-16:00 | 3727.18 | 18-OCT-16:00 | 0.00 | 01-OCT-00:10 | 903.82 | 18-OCT-16:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.140207E+11 | 0.350467E+10 | 830.54 | 0.136147E+11 | 0.406000E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.537024E+10 | 0.134570E+10 | 241.76 | 0.520647E+10 | 0.163771E+09 | 0.00 | 1.00 | 0.00 | 19452.57 | 17419.67 | 6779.44 | 4129.11 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 17943820.58 | 5821355.20 | 3.33 | 17943820.58 | 0.00 | 0.00 | 0.10 | 20-MAY-16:00 | 0.00 | 01-MAY-00:02 | 3911.34 | 20-MAY-16:00 | 3911.34 | 20-MAY-16:00 | 0.00 | 20-MAY-15:20 | 1286.40 | 20-MAY-16:00 | 0.00 | 01-MAY-00:02 |
June | 0.283878E+10 | 0.874107E+09 | 69.97 | 0.274218E+10 | 96597955.98 | 0.00 | 1.00 | 23-JUN-19:11 | 0.00 | 01-JUN-00:10 | 45189.75 | 23-JUN-19:40 | 44923.72 | 23-JUN-19:11 | 2531.83 | 21-JUN-13:00 | 12245.10 | 30-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 0.941229E+10 | 0.293013E+10 | 205.20 | 0.921510E+10 | 0.197185E+09 | 0.00 | 1.00 | 02-JUL-10:51 | 0.00 | 01-JUL-00:10 | 49335.17 | 16-JUL-10:11 | 45503.43 | 19-JUL-17:41 | 11541.66 | 16-JUL-10:16 | 13347.06 | 17-JUL-17:43 | 0.00 | 01-JUL-00:10 |
August | 0.675430E+10 | 0.213458E+10 | 156.73 | 0.672915E+10 | 25152370.99 | 0.00 | 1.00 | 03-AUG-17:17 | 0.00 | 01-AUG-00:10 | 45260.32 | 08-AUG-20:41 | 45173.74 | 08-AUG-20:41 | 2081.87 | 08-AUG-12:00 | 13167.18 | 06-AUG-15:55 | 0.00 | 01-AUG-00:10 |
September | 0.215507E+10 | 0.673746E+09 | 50.84 | 0.199935E+10 | 0.155720E+09 | 0.00 | 1.00 | 02-SEP-17:08 | 0.00 | 01-SEP-00:10 | 50310.53 | 06-SEP-17:40 | 44909.75 | 04-SEP-19:37 | 13467.24 | 06-SEP-17:40 | 12933.57 | 06-SEP-17:11 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.211784E+11 | 0.661839E+10 | 486.08 | 0.207037E+11 | 0.474655E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.941229E+10 | 0.293013E+10 | 205.20 | 0.921510E+10 | 0.197185E+09 | 0.00 | 1.00 | 0.00 | 50310.53 | 45503.43 | 13467.24 | 13347.06 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.37 | 24.52 | 35.84 | 21.12 | 278.53 | 0.00 | 0.00 | 744.00 |
February | 102.27 | 50.33 | 51.94 | 64.14 | 192.58 | 0.00 | 0.00 | 672.00 |
March | 131.29 | 48.22 | 83.07 | 87.33 | 153.38 | 0.00 | 0.00 | 744.00 |
April | 171.10 | 75.58 | 95.51 | 152.45 | 101.24 | 0.00 | 0.00 | 720.00 |
May | 211.63 | 96.52 | 115.10 | 207.14 | 81.99 | 0.00 | 0.00 | 744.00 |
June | 230.06 | 105.62 | 124.45 | 243.59 | 66.05 | 0.00 | 0.00 | 720.00 |
July | 235.92 | 119.25 | 116.68 | 270.40 | 63.46 | 0.00 | 0.00 | 744.00 |
August | 199.93 | 97.85 | 102.08 | 220.37 | 67.38 | 0.00 | 0.00 | 744.00 |
September | 160.99 | 81.35 | 79.64 | 163.47 | 84.47 | 0.00 | 0.00 | 720.00 |
October | 115.28 | 57.30 | 57.98 | 97.33 | 108.98 | 0.00 | 0.00 | 744.00 |
November | 81.47 | 40.42 | 41.05 | 51.56 | 156.18 | 0.00 | 0.00 | 720.00 |
December | 54.65 | 23.03 | 31.62 | 19.69 | 229.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 146.45 | 68.40 | 78.05 | 133.57 | 131.83 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 54.65 | 23.03 | 31.62 | 19.69 | 63.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 235.92 | 119.25 | 124.45 | 270.40 | 278.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.37 | 24.52 | 35.84 | 21.12 | 278.53 | 0.00 | 0.00 | 744.00 |
February | 102.27 | 50.33 | 51.94 | 64.14 | 192.58 | 0.00 | 0.00 | 672.00 |
March | 131.29 | 48.22 | 83.07 | 87.33 | 153.38 | 0.00 | 0.00 | 744.00 |
April | 171.10 | 75.58 | 95.51 | 152.45 | 101.24 | 0.00 | 0.00 | 720.00 |
May | 211.63 | 96.52 | 115.10 | 207.14 | 81.99 | 0.00 | 0.00 | 744.00 |
June | 230.06 | 105.62 | 124.45 | 243.59 | 66.05 | 0.00 | 0.00 | 720.00 |
July | 235.92 | 119.25 | 116.68 | 270.40 | 63.46 | 0.00 | 0.00 | 744.00 |
August | 199.93 | 97.85 | 102.08 | 220.37 | 67.38 | 0.00 | 0.00 | 744.00 |
September | 160.99 | 81.35 | 79.64 | 163.47 | 84.47 | 0.00 | 0.00 | 720.00 |
October | 115.28 | 57.30 | 57.98 | 97.33 | 108.98 | 0.00 | 0.00 | 744.00 |
November | 81.47 | 40.42 | 41.05 | 51.56 | 156.18 | 0.00 | 0.00 | 720.00 |
December | 54.65 | 23.03 | 31.62 | 19.69 | 229.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 146.45 | 68.40 | 78.05 | 133.57 | 131.83 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 54.65 | 23.03 | 31.62 | 19.69 | 63.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 235.92 | 119.25 | 124.45 | 270.40 | 278.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.83 | 0.00 | 16.83 | 0.19 | 170.21 | 0.00 | 0.00 | 744.00 |
February | 23.76 | 0.00 | 23.76 | 2.82 | 120.95 | 0.00 | 0.00 | 672.00 |
March | 38.60 | 0.00 | 38.59 | 8.83 | 92.62 | 0.00 | 0.00 | 744.00 |
April | 44.13 | 0.33 | 43.80 | 19.65 | 60.26 | 0.00 | 0.00 | 720.00 |
May | 57.74 | 3.37 | 54.36 | 34.28 | 47.06 | 0.00 | 0.00 | 744.00 |
June | 67.20 | 7.67 | 59.53 | 49.55 | 34.69 | 0.00 | 0.00 | 720.00 |
July | 61.38 | 5.66 | 55.71 | 53.97 | 33.82 | 0.00 | 0.00 | 744.00 |
August | 49.76 | 1.79 | 47.97 | 41.94 | 38.44 | 0.00 | 0.00 | 744.00 |
September | 36.93 | 0.03 | 36.89 | 25.03 | 49.74 | 0.00 | 0.00 | 720.00 |
October | 26.91 | 0.00 | 26.91 | 9.54 | 65.63 | 0.00 | 0.00 | 744.00 |
November | 18.29 | 0.00 | 18.29 | 2.39 | 97.34 | 0.00 | 0.00 | 720.00 |
December | 14.11 | 0.00 | 14.11 | 0.11 | 141.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.04 | 1.58 | 36.47 | 20.80 | 79.26 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 14.11 | 0.00 | 14.11 | 0.11 | 33.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.20 | 7.67 | 59.53 | 53.97 | 170.21 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.82 | 0.00 | 16.82 | 0.19 | 170.21 | 0.00 | 0.00 | 744.00 |
February | 23.76 | 0.00 | 23.76 | 2.82 | 120.95 | 0.00 | 0.00 | 672.00 |
March | 38.59 | 0.00 | 38.59 | 8.82 | 92.62 | 0.00 | 0.00 | 744.00 |
April | 44.13 | 0.33 | 43.80 | 19.65 | 60.26 | 0.00 | 0.00 | 720.00 |
May | 57.73 | 3.37 | 54.36 | 34.28 | 47.06 | 0.00 | 0.00 | 744.00 |
June | 67.19 | 7.67 | 59.53 | 49.55 | 34.69 | 0.00 | 0.00 | 720.00 |
July | 61.37 | 5.66 | 55.71 | 53.97 | 33.82 | 0.00 | 0.00 | 744.00 |
August | 49.76 | 1.79 | 47.97 | 41.94 | 38.44 | 0.00 | 0.00 | 744.00 |
September | 36.93 | 0.03 | 36.89 | 25.03 | 49.74 | 0.00 | 0.00 | 720.00 |
October | 26.91 | 0.00 | 26.91 | 9.54 | 65.63 | 0.00 | 0.00 | 744.00 |
November | 18.29 | 0.00 | 18.29 | 2.39 | 97.34 | 0.00 | 0.00 | 720.00 |
December | 14.11 | 0.00 | 14.11 | 0.11 | 141.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.04 | 1.58 | 36.46 | 20.80 | 79.26 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 14.11 | 0.00 | 14.11 | 0.11 | 33.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 67.19 | 7.67 | 59.53 | 53.97 | 170.21 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.71 | 7.35 | 12.35 | 3.61 | 74.27 | 0.00 | 0.00 | 744.00 |
February | 33.14 | 17.43 | 15.70 | 18.60 | 50.74 | 0.00 | 0.00 | 672.00 |
March | 56.61 | 26.71 | 29.90 | 49.81 | 39.57 | 0.00 | 0.00 | 744.00 |
April | 70.97 | 39.74 | 31.22 | 71.63 | 26.68 | 0.00 | 0.00 | 720.00 |
May | 91.82 | 52.78 | 39.05 | 100.76 | 21.70 | 0.00 | 0.00 | 744.00 |
June | 110.96 | 71.77 | 39.19 | 123.34 | 23.28 | 0.00 | 0.00 | 720.00 |
July | 114.90 | 80.87 | 34.03 | 125.98 | 29.32 | 0.00 | 0.00 | 744.00 |
August | 95.33 | 65.30 | 30.03 | 100.74 | 31.00 | 0.00 | 0.00 | 744.00 |
September | 65.27 | 41.31 | 23.97 | 65.33 | 30.25 | 0.00 | 0.00 | 720.00 |
October | 39.36 | 21.25 | 18.11 | 31.52 | 33.66 | 0.00 | 0.00 | 744.00 |
November | 23.08 | 10.53 | 12.55 | 10.65 | 42.26 | 0.00 | 0.00 | 720.00 |
December | 15.25 | 5.16 | 10.09 | 2.42 | 61.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.53 | 36.80 | 24.73 | 58.93 | 38.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.25 | 5.16 | 10.09 | 2.42 | 21.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.90 | 80.87 | 39.19 | 125.98 | 74.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.71 | 7.35 | 12.35 | 3.61 | 74.27 | 0.00 | 0.00 | 744.00 |
February | 33.14 | 17.43 | 15.70 | 18.60 | 50.74 | 0.00 | 0.00 | 672.00 |
March | 56.61 | 26.71 | 29.90 | 49.81 | 39.57 | 0.00 | 0.00 | 744.00 |
April | 70.97 | 39.74 | 31.22 | 71.63 | 26.68 | 0.00 | 0.00 | 720.00 |
May | 91.82 | 52.78 | 39.05 | 100.76 | 21.70 | 0.00 | 0.00 | 744.00 |
June | 110.96 | 71.77 | 39.19 | 123.34 | 23.28 | 0.00 | 0.00 | 720.00 |
July | 114.90 | 80.87 | 34.03 | 125.98 | 29.32 | 0.00 | 0.00 | 744.00 |
August | 95.33 | 65.30 | 30.03 | 100.74 | 31.00 | 0.00 | 0.00 | 744.00 |
September | 65.27 | 41.31 | 23.97 | 65.33 | 30.25 | 0.00 | 0.00 | 720.00 |
October | 39.36 | 21.25 | 18.11 | 31.52 | 33.66 | 0.00 | 0.00 | 744.00 |
November | 23.08 | 10.53 | 12.55 | 10.65 | 42.26 | 0.00 | 0.00 | 720.00 |
December | 15.25 | 5.16 | 10.09 | 2.42 | 61.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.53 | 36.80 | 24.73 | 58.93 | 38.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.25 | 5.16 | 10.09 | 2.42 | 21.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.90 | 80.87 | 39.19 | 125.98 | 74.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.71 | 7.35 | 12.35 | 3.61 | 74.27 | 0.00 | 0.00 | 744.00 |
February | 33.14 | 17.43 | 15.70 | 18.60 | 50.74 | 0.00 | 0.00 | 672.00 |
March | 56.61 | 26.71 | 29.90 | 49.81 | 39.57 | 0.00 | 0.00 | 744.00 |
April | 70.97 | 39.74 | 31.22 | 71.63 | 26.68 | 0.00 | 0.00 | 720.00 |
May | 91.82 | 52.78 | 39.05 | 100.76 | 21.70 | 0.00 | 0.00 | 744.00 |
June | 110.96 | 71.77 | 39.19 | 123.34 | 23.28 | 0.00 | 0.00 | 720.00 |
July | 114.90 | 80.87 | 34.03 | 125.98 | 29.32 | 0.00 | 0.00 | 744.00 |
August | 95.33 | 65.30 | 30.03 | 100.74 | 31.00 | 0.00 | 0.00 | 744.00 |
September | 65.27 | 41.31 | 23.97 | 65.33 | 30.25 | 0.00 | 0.00 | 720.00 |
October | 39.36 | 21.25 | 18.11 | 31.52 | 33.66 | 0.00 | 0.00 | 744.00 |
November | 23.08 | 10.53 | 12.55 | 10.65 | 42.26 | 0.00 | 0.00 | 720.00 |
December | 15.25 | 5.16 | 10.09 | 2.42 | 61.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.53 | 36.80 | 24.73 | 58.93 | 38.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.25 | 5.16 | 10.09 | 2.42 | 21.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.90 | 80.87 | 39.19 | 125.98 | 74.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.71 | 7.35 | 12.35 | 3.61 | 74.27 | 0.00 | 0.00 | 744.00 |
February | 33.14 | 17.43 | 15.70 | 18.60 | 50.74 | 0.00 | 0.00 | 672.00 |
March | 56.61 | 26.71 | 29.90 | 49.81 | 39.57 | 0.00 | 0.00 | 744.00 |
April | 70.97 | 39.74 | 31.22 | 71.63 | 26.68 | 0.00 | 0.00 | 720.00 |
May | 91.82 | 52.78 | 39.05 | 100.76 | 21.70 | 0.00 | 0.00 | 744.00 |
June | 110.96 | 71.77 | 39.19 | 123.34 | 23.28 | 0.00 | 0.00 | 720.00 |
July | 114.90 | 80.87 | 34.03 | 125.98 | 29.32 | 0.00 | 0.00 | 744.00 |
August | 95.33 | 65.30 | 30.03 | 100.74 | 31.00 | 0.00 | 0.00 | 744.00 |
September | 65.27 | 41.31 | 23.97 | 65.33 | 30.25 | 0.00 | 0.00 | 720.00 |
October | 39.36 | 21.25 | 18.11 | 31.52 | 33.66 | 0.00 | 0.00 | 744.00 |
November | 23.08 | 10.53 | 12.55 | 10.65 | 42.26 | 0.00 | 0.00 | 720.00 |
December | 15.25 | 5.16 | 10.09 | 2.42 | 61.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.53 | 36.80 | 24.73 | 58.93 | 38.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.25 | 5.16 | 10.09 | 2.42 | 21.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.90 | 80.87 | 39.19 | 125.98 | 74.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.71 | 7.35 | 12.35 | 3.61 | 74.27 | 0.00 | 0.00 | 744.00 |
February | 33.14 | 17.43 | 15.70 | 18.60 | 50.74 | 0.00 | 0.00 | 672.00 |
March | 56.61 | 26.71 | 29.90 | 49.81 | 39.57 | 0.00 | 0.00 | 744.00 |
April | 70.97 | 39.74 | 31.22 | 71.63 | 26.68 | 0.00 | 0.00 | 720.00 |
May | 91.82 | 52.78 | 39.05 | 100.76 | 21.70 | 0.00 | 0.00 | 744.00 |
June | 110.96 | 71.77 | 39.19 | 123.34 | 23.28 | 0.00 | 0.00 | 720.00 |
July | 114.90 | 80.87 | 34.03 | 125.98 | 29.32 | 0.00 | 0.00 | 744.00 |
August | 95.33 | 65.30 | 30.03 | 100.74 | 31.00 | 0.00 | 0.00 | 744.00 |
September | 65.27 | 41.31 | 23.97 | 65.33 | 30.25 | 0.00 | 0.00 | 720.00 |
October | 39.36 | 21.25 | 18.11 | 31.52 | 33.66 | 0.00 | 0.00 | 744.00 |
November | 23.08 | 10.53 | 12.55 | 10.65 | 42.26 | 0.00 | 0.00 | 720.00 |
December | 15.25 | 5.16 | 10.09 | 2.42 | 61.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.53 | 36.80 | 24.73 | 58.93 | 38.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.25 | 5.16 | 10.09 | 2.42 | 21.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.90 | 80.87 | 39.19 | 125.98 | 74.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.71 | 7.35 | 12.35 | 3.61 | 74.27 | 0.00 | 0.00 | 744.00 |
February | 33.14 | 17.43 | 15.70 | 18.60 | 50.74 | 0.00 | 0.00 | 672.00 |
March | 56.61 | 26.71 | 29.90 | 49.81 | 39.57 | 0.00 | 0.00 | 744.00 |
April | 70.97 | 39.74 | 31.22 | 71.63 | 26.68 | 0.00 | 0.00 | 720.00 |
May | 91.82 | 52.78 | 39.05 | 100.76 | 21.70 | 0.00 | 0.00 | 744.00 |
June | 110.96 | 71.77 | 39.19 | 123.34 | 23.28 | 0.00 | 0.00 | 720.00 |
July | 114.90 | 80.87 | 34.03 | 125.98 | 29.32 | 0.00 | 0.00 | 744.00 |
August | 95.33 | 65.30 | 30.03 | 100.74 | 31.00 | 0.00 | 0.00 | 744.00 |
September | 65.27 | 41.31 | 23.97 | 65.33 | 30.25 | 0.00 | 0.00 | 720.00 |
October | 39.36 | 21.25 | 18.11 | 31.52 | 33.66 | 0.00 | 0.00 | 744.00 |
November | 23.08 | 10.53 | 12.55 | 10.65 | 42.26 | 0.00 | 0.00 | 720.00 |
December | 15.25 | 5.16 | 10.09 | 2.42 | 61.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.53 | 36.80 | 24.73 | 58.93 | 38.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.25 | 5.16 | 10.09 | 2.42 | 21.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.90 | 80.87 | 39.19 | 125.98 | 74.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.71 | 7.35 | 12.35 | 3.61 | 74.27 | 0.00 | 0.00 | 744.00 |
February | 33.14 | 17.43 | 15.70 | 18.60 | 50.74 | 0.00 | 0.00 | 672.00 |
March | 56.61 | 26.71 | 29.90 | 49.81 | 39.57 | 0.00 | 0.00 | 744.00 |
April | 70.97 | 39.74 | 31.22 | 71.63 | 26.68 | 0.00 | 0.00 | 720.00 |
May | 91.82 | 52.78 | 39.05 | 100.76 | 21.70 | 0.00 | 0.00 | 744.00 |
June | 110.96 | 71.77 | 39.19 | 123.34 | 23.28 | 0.00 | 0.00 | 720.00 |
July | 114.90 | 80.87 | 34.03 | 125.98 | 29.32 | 0.00 | 0.00 | 744.00 |
August | 95.33 | 65.30 | 30.03 | 100.74 | 31.00 | 0.00 | 0.00 | 744.00 |
September | 65.27 | 41.31 | 23.97 | 65.33 | 30.25 | 0.00 | 0.00 | 720.00 |
October | 39.36 | 21.25 | 18.11 | 31.52 | 33.66 | 0.00 | 0.00 | 744.00 |
November | 23.08 | 10.53 | 12.55 | 10.65 | 42.26 | 0.00 | 0.00 | 720.00 |
December | 15.25 | 5.16 | 10.09 | 2.42 | 61.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.53 | 36.80 | 24.73 | 58.93 | 38.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.25 | 5.16 | 10.09 | 2.42 | 21.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.90 | 80.87 | 39.19 | 125.98 | 74.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.71 | 7.35 | 12.35 | 3.61 | 74.27 | 0.00 | 0.00 | 744.00 |
February | 33.14 | 17.43 | 15.70 | 18.60 | 50.74 | 0.00 | 0.00 | 672.00 |
March | 56.61 | 26.71 | 29.90 | 49.81 | 39.57 | 0.00 | 0.00 | 744.00 |
April | 70.97 | 39.74 | 31.22 | 71.63 | 26.68 | 0.00 | 0.00 | 720.00 |
May | 91.82 | 52.78 | 39.05 | 100.76 | 21.70 | 0.00 | 0.00 | 744.00 |
June | 110.96 | 71.77 | 39.19 | 123.34 | 23.28 | 0.00 | 0.00 | 720.00 |
July | 114.90 | 80.87 | 34.03 | 125.98 | 29.32 | 0.00 | 0.00 | 744.00 |
August | 95.33 | 65.30 | 30.03 | 100.74 | 31.00 | 0.00 | 0.00 | 744.00 |
September | 65.27 | 41.31 | 23.97 | 65.33 | 30.25 | 0.00 | 0.00 | 720.00 |
October | 39.36 | 21.25 | 18.11 | 31.52 | 33.66 | 0.00 | 0.00 | 744.00 |
November | 23.08 | 10.53 | 12.55 | 10.65 | 42.26 | 0.00 | 0.00 | 720.00 |
December | 15.25 | 5.16 | 10.09 | 2.42 | 61.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.53 | 36.80 | 24.73 | 58.93 | 38.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.25 | 5.16 | 10.09 | 2.42 | 21.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.90 | 80.87 | 39.19 | 125.98 | 74.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.71 | 7.35 | 12.35 | 3.61 | 74.27 | 0.00 | 0.00 | 744.00 |
February | 33.14 | 17.43 | 15.70 | 18.60 | 50.74 | 0.00 | 0.00 | 672.00 |
March | 56.61 | 26.71 | 29.90 | 49.81 | 39.57 | 0.00 | 0.00 | 744.00 |
April | 70.97 | 39.74 | 31.22 | 71.63 | 26.68 | 0.00 | 0.00 | 720.00 |
May | 91.82 | 52.78 | 39.05 | 100.76 | 21.70 | 0.00 | 0.00 | 744.00 |
June | 110.96 | 71.77 | 39.19 | 123.34 | 23.28 | 0.00 | 0.00 | 720.00 |
July | 114.90 | 80.87 | 34.03 | 125.98 | 29.32 | 0.00 | 0.00 | 744.00 |
August | 95.33 | 65.30 | 30.03 | 100.74 | 31.00 | 0.00 | 0.00 | 744.00 |
September | 65.27 | 41.31 | 23.97 | 65.33 | 30.25 | 0.00 | 0.00 | 720.00 |
October | 39.36 | 21.25 | 18.11 | 31.52 | 33.66 | 0.00 | 0.00 | 744.00 |
November | 23.08 | 10.53 | 12.55 | 10.65 | 42.26 | 0.00 | 0.00 | 720.00 |
December | 15.25 | 5.16 | 10.09 | 2.42 | 61.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.53 | 36.80 | 24.73 | 58.93 | 38.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.25 | 5.16 | 10.09 | 2.42 | 21.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.90 | 80.87 | 39.19 | 125.98 | 74.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.71 | 7.35 | 12.35 | 3.61 | 74.27 | 0.00 | 0.00 | 744.00 |
February | 33.14 | 17.43 | 15.70 | 18.60 | 50.74 | 0.00 | 0.00 | 672.00 |
March | 56.61 | 26.71 | 29.90 | 49.81 | 39.57 | 0.00 | 0.00 | 744.00 |
April | 70.97 | 39.74 | 31.22 | 71.63 | 26.68 | 0.00 | 0.00 | 720.00 |
May | 91.82 | 52.78 | 39.05 | 100.76 | 21.70 | 0.00 | 0.00 | 744.00 |
June | 110.96 | 71.77 | 39.19 | 123.34 | 23.28 | 0.00 | 0.00 | 720.00 |
July | 114.90 | 80.87 | 34.03 | 125.98 | 29.32 | 0.00 | 0.00 | 744.00 |
August | 95.33 | 65.30 | 30.03 | 100.74 | 31.00 | 0.00 | 0.00 | 744.00 |
September | 65.27 | 41.31 | 23.97 | 65.33 | 30.25 | 0.00 | 0.00 | 720.00 |
October | 39.36 | 21.25 | 18.11 | 31.52 | 33.66 | 0.00 | 0.00 | 744.00 |
November | 23.08 | 10.53 | 12.55 | 10.65 | 42.26 | 0.00 | 0.00 | 720.00 |
December | 15.25 | 5.16 | 10.09 | 2.42 | 61.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.53 | 36.80 | 24.73 | 58.93 | 38.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.25 | 5.16 | 10.09 | 2.42 | 21.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 114.90 | 80.87 | 39.19 | 125.98 | 74.27 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161686E+09 | 65681865.97 | 96004513.48 | 56562603.76 | 0.746004E+09 |
February | 0.247411E+09 | 0.121762E+09 | 0.125649E+09 | 0.155162E+09 | 0.465879E+09 |
March | 0.351654E+09 | 0.129165E+09 | 0.222489E+09 | 0.233914E+09 | 0.410807E+09 |
April | 0.443479E+09 | 0.195911E+09 | 0.247568E+09 | 0.395159E+09 | 0.262406E+09 |
May | 0.566819E+09 | 0.258528E+09 | 0.308290E+09 | 0.554813E+09 | 0.219596E+09 |
June | 0.596326E+09 | 0.273763E+09 | 0.322563E+09 | 0.631397E+09 | 0.171197E+09 |
July | 0.631901E+09 | 0.319397E+09 | 0.312504E+09 | 0.724247E+09 | 0.169985E+09 |
August | 0.535480E+09 | 0.262075E+09 | 0.273405E+09 | 0.590252E+09 | 0.180475E+09 |
September | 0.417296E+09 | 0.210868E+09 | 0.206428E+09 | 0.423725E+09 | 0.218934E+09 |
October | 0.308771E+09 | 0.153481E+09 | 0.155290E+09 | 0.260693E+09 | 0.291889E+09 |
November | 0.211168E+09 | 0.104778E+09 | 0.106390E+09 | 0.133633E+09 | 0.404819E+09 |
December | 0.146384E+09 | 61686720.27 | 84697559.08 | 52729422.70 | 0.615374E+09 |
Annual Sum or Average | 0.461837E+10 | 0.215710E+10 | 0.246128E+10 | 0.421229E+10 | 0.415737E+10 |
Minimum of Months | 0.146384E+09 | 61686720.27 | 84697559.08 | 52729422.70 | 0.169985E+09 |
Maximum of Months | 0.631901E+09 | 0.319397E+09 | 0.322563E+09 | 0.724247E+09 | 0.746004E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161686E+09 | 65681865.97 | 96004513.48 | 56562603.76 | 0.746004E+09 |
February | 0.247411E+09 | 0.121762E+09 | 0.125649E+09 | 0.155162E+09 | 0.465879E+09 |
March | 0.351654E+09 | 0.129165E+09 | 0.222489E+09 | 0.233914E+09 | 0.410807E+09 |
April | 0.443479E+09 | 0.195911E+09 | 0.247568E+09 | 0.395159E+09 | 0.262406E+09 |
May | 0.566819E+09 | 0.258528E+09 | 0.308290E+09 | 0.554813E+09 | 0.219596E+09 |
June | 0.596326E+09 | 0.273763E+09 | 0.322563E+09 | 0.631397E+09 | 0.171197E+09 |
July | 0.631901E+09 | 0.319397E+09 | 0.312504E+09 | 0.724247E+09 | 0.169985E+09 |
August | 0.535480E+09 | 0.262075E+09 | 0.273405E+09 | 0.590252E+09 | 0.180475E+09 |
September | 0.417296E+09 | 0.210868E+09 | 0.206428E+09 | 0.423725E+09 | 0.218934E+09 |
October | 0.308771E+09 | 0.153481E+09 | 0.155290E+09 | 0.260693E+09 | 0.291889E+09 |
November | 0.211168E+09 | 0.104778E+09 | 0.106390E+09 | 0.133633E+09 | 0.404819E+09 |
December | 0.146384E+09 | 61686720.27 | 84697559.08 | 52729422.70 | 0.615374E+09 |
Annual Sum or Average | 0.461837E+10 | 0.215710E+10 | 0.246128E+10 | 0.421229E+10 | 0.415737E+10 |
Minimum of Months | 0.146384E+09 | 61686720.27 | 84697559.08 | 52729422.70 | 0.169985E+09 |
Maximum of Months | 0.631901E+09 | 0.319397E+09 | 0.322563E+09 | 0.724247E+09 | 0.746004E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45064288.41 | 0.00 | 45064288.41 | 505303.21 | 0.455886E+09 |
February | 57470429.67 | 0.00 | 57470429.67 | 6810537.34 | 0.292612E+09 |
March | 0.103373E+09 | 5154.92 | 0.103368E+09 | 23638658.85 | 0.248078E+09 |
April | 0.114392E+09 | 857486.23 | 0.113534E+09 | 50935678.60 | 0.156200E+09 |
May | 0.154641E+09 | 9033514.49 | 0.145607E+09 | 91827609.57 | 0.126055E+09 |
June | 0.174172E+09 | 19871915.09 | 0.154300E+09 | 0.128440E+09 | 89921850.08 |
July | 0.164389E+09 | 15169360.03 | 0.149219E+09 | 0.144554E+09 | 90575087.02 |
August | 0.133290E+09 | 4794192.82 | 0.128496E+09 | 0.112343E+09 | 0.102958E+09 |
September | 95713512.75 | 81737.00 | 95631775.75 | 64887226.83 | 0.128920E+09 |
October | 72072435.85 | 0.00 | 72072435.85 | 25540531.65 | 0.175775E+09 |
November | 47415011.88 | 0.00 | 47415011.88 | 6185212.11 | 0.252316E+09 |
December | 37788945.48 | 0.00 | 37788945.48 | 293893.06 | 0.380287E+09 |
Annual Sum or Average | 0.119978E+10 | 49813360.58 | 0.114997E+10 | 0.655961E+09 | 0.249958E+10 |
Minimum of Months | 37788945.48 | 0.00 | 37788945.48 | 293893.06 | 89921850.08 |
Maximum of Months | 0.174172E+09 | 19871915.09 | 0.154300E+09 | 0.144554E+09 | 0.455886E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45062835.23 | 0.00 | 45062835.23 | 505206.43 | 0.455886E+09 |
February | 57468698.97 | 0.00 | 57468698.97 | 6810145.20 | 0.292613E+09 |
March | 0.103370E+09 | 5154.68 | 0.103365E+09 | 23636819.67 | 0.248078E+09 |
April | 0.114389E+09 | 857446.04 | 0.113531E+09 | 50933275.51 | 0.156200E+09 |
May | 0.154636E+09 | 9033091.07 | 0.145603E+09 | 91823860.72 | 0.126056E+09 |
June | 0.174167E+09 | 19870983.66 | 0.154296E+09 | 0.128436E+09 | 89921691.28 |
July | 0.164384E+09 | 15168649.02 | 0.149215E+09 | 0.144550E+09 | 90574507.63 |
August | 0.133286E+09 | 4793968.11 | 0.128492E+09 | 0.112340E+09 | 0.102958E+09 |
September | 95710774.52 | 81733.17 | 95629041.36 | 64885143.72 | 0.128920E+09 |
October | 72070253.22 | 0.00 | 72070253.22 | 25539235.26 | 0.175775E+09 |
November | 47413524.99 | 0.00 | 47413524.99 | 6184736.56 | 0.252315E+09 |
December | 37787710.35 | 0.00 | 37787710.35 | 293850.26 | 0.380287E+09 |
Annual Sum or Average | 0.119975E+10 | 49811025.76 | 0.114993E+10 | 0.655938E+09 | 0.249958E+10 |
Minimum of Months | 37787710.35 | 0.00 | 37787710.35 | 293850.26 | 89921691.28 |
Maximum of Months | 0.174167E+09 | 19870983.66 | 0.154296E+09 | 0.144550E+09 | 0.455886E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52780164.69 | 19696094.93 | 33084069.76 | 9667252.42 | 0.198915E+09 |
February | 80169482.78 | 42176459.88 | 37993022.91 | 44988683.80 | 0.122743E+09 |
March | 0.151622E+09 | 71536362.23 | 80085864.37 | 0.133421E+09 | 0.105974E+09 |
April | 0.183943E+09 | 0.103017E+09 | 80926353.75 | 0.185676E+09 | 69151539.05 |
May | 0.245940E+09 | 0.141353E+09 | 0.104587E+09 | 0.269886E+09 | 58129267.36 |
June | 0.287621E+09 | 0.186037E+09 | 0.101585E+09 | 0.319709E+09 | 60332067.45 |
July | 0.307739E+09 | 0.216594E+09 | 91144959.21 | 0.337435E+09 | 78520062.24 |
August | 0.255337E+09 | 0.174912E+09 | 80425238.16 | 0.269812E+09 | 83028342.12 |
September | 0.169191E+09 | 0.107067E+09 | 62123521.16 | 0.169325E+09 | 78414402.43 |
October | 0.105426E+09 | 56914896.08 | 48511255.61 | 84428315.46 | 90159669.24 |
November | 59812672.88 | 27291670.98 | 32521001.91 | 27603832.61 | 0.109529E+09 |
December | 40841095.77 | 13813438.40 | 27027657.37 | 6472923.00 | 0.165405E+09 |
Annual Sum or Average | 0.194042E+10 | 0.116041E+10 | 0.780014E+09 | 0.185843E+10 | 0.122030E+10 |
Minimum of Months | 40841095.77 | 13813438.40 | 27027657.37 | 6472923.00 | 58129267.36 |
Maximum of Months | 0.307739E+09 | 0.216594E+09 | 0.104587E+09 | 0.337435E+09 | 0.198915E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52780164.69 | 19696094.93 | 33084069.76 | 9667252.42 | 0.198915E+09 |
February | 80169482.78 | 42176459.88 | 37993022.91 | 44988683.80 | 0.122743E+09 |
March | 0.151622E+09 | 71536362.23 | 80085864.37 | 0.133421E+09 | 0.105974E+09 |
April | 0.183943E+09 | 0.103017E+09 | 80926353.75 | 0.185676E+09 | 69151539.05 |
May | 0.245940E+09 | 0.141353E+09 | 0.104587E+09 | 0.269886E+09 | 58129267.36 |
June | 0.287621E+09 | 0.186037E+09 | 0.101585E+09 | 0.319709E+09 | 60332067.45 |
July | 0.307739E+09 | 0.216594E+09 | 91144959.21 | 0.337435E+09 | 78520062.24 |
August | 0.255337E+09 | 0.174912E+09 | 80425238.16 | 0.269812E+09 | 83028342.12 |
September | 0.169191E+09 | 0.107067E+09 | 62123521.16 | 0.169325E+09 | 78414402.43 |
October | 0.105426E+09 | 56914896.08 | 48511255.61 | 84428315.46 | 90159669.24 |
November | 59812672.88 | 27291670.98 | 32521001.91 | 27603832.61 | 0.109529E+09 |
December | 40841095.77 | 13813438.40 | 27027657.37 | 6472923.00 | 0.165405E+09 |
Annual Sum or Average | 0.194042E+10 | 0.116041E+10 | 0.780014E+09 | 0.185843E+10 | 0.122030E+10 |
Minimum of Months | 40841095.77 | 13813438.40 | 27027657.37 | 6472923.00 | 58129267.36 |
Maximum of Months | 0.307739E+09 | 0.216594E+09 | 0.104587E+09 | 0.337435E+09 | 0.198915E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52780164.69 | 19696094.93 | 33084069.76 | 9667252.42 | 0.198915E+09 |
February | 80169482.78 | 42176459.88 | 37993022.91 | 44988683.80 | 0.122743E+09 |
March | 0.151622E+09 | 71536362.23 | 80085864.37 | 0.133421E+09 | 0.105974E+09 |
April | 0.183943E+09 | 0.103017E+09 | 80926353.75 | 0.185676E+09 | 69151539.05 |
May | 0.245940E+09 | 0.141353E+09 | 0.104587E+09 | 0.269886E+09 | 58129267.36 |
June | 0.287621E+09 | 0.186037E+09 | 0.101585E+09 | 0.319709E+09 | 60332067.45 |
July | 0.307739E+09 | 0.216594E+09 | 91144959.21 | 0.337435E+09 | 78520062.24 |
August | 0.255337E+09 | 0.174912E+09 | 80425238.16 | 0.269812E+09 | 83028342.12 |
September | 0.169191E+09 | 0.107067E+09 | 62123521.16 | 0.169325E+09 | 78414402.43 |
October | 0.105426E+09 | 56914896.08 | 48511255.61 | 84428315.46 | 90159669.24 |
November | 59812672.88 | 27291670.98 | 32521001.91 | 27603832.61 | 0.109529E+09 |
December | 40841095.77 | 13813438.40 | 27027657.37 | 6472923.00 | 0.165405E+09 |
Annual Sum or Average | 0.194042E+10 | 0.116041E+10 | 0.780014E+09 | 0.185843E+10 | 0.122030E+10 |
Minimum of Months | 40841095.77 | 13813438.40 | 27027657.37 | 6472923.00 | 58129267.36 |
Maximum of Months | 0.307739E+09 | 0.216594E+09 | 0.104587E+09 | 0.337435E+09 | 0.198915E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52780164.69 | 19696094.93 | 33084069.76 | 9667252.42 | 0.198915E+09 |
February | 80169482.78 | 42176459.88 | 37993022.91 | 44988683.80 | 0.122743E+09 |
March | 0.151622E+09 | 71536362.23 | 80085864.37 | 0.133421E+09 | 0.105974E+09 |
April | 0.183943E+09 | 0.103017E+09 | 80926353.75 | 0.185676E+09 | 69151539.05 |
May | 0.245940E+09 | 0.141353E+09 | 0.104587E+09 | 0.269886E+09 | 58129267.36 |
June | 0.287621E+09 | 0.186037E+09 | 0.101585E+09 | 0.319709E+09 | 60332067.45 |
July | 0.307739E+09 | 0.216594E+09 | 91144959.21 | 0.337435E+09 | 78520062.24 |
August | 0.255337E+09 | 0.174912E+09 | 80425238.16 | 0.269812E+09 | 83028342.12 |
September | 0.169191E+09 | 0.107067E+09 | 62123521.16 | 0.169325E+09 | 78414402.43 |
October | 0.105426E+09 | 56914896.08 | 48511255.61 | 84428315.46 | 90159669.24 |
November | 59812672.88 | 27291670.98 | 32521001.91 | 27603832.61 | 0.109529E+09 |
December | 40841095.77 | 13813438.40 | 27027657.37 | 6472923.00 | 0.165405E+09 |
Annual Sum or Average | 0.194042E+10 | 0.116041E+10 | 0.780014E+09 | 0.185843E+10 | 0.122030E+10 |
Minimum of Months | 40841095.77 | 13813438.40 | 27027657.37 | 6472923.00 | 58129267.36 |
Maximum of Months | 0.307739E+09 | 0.216594E+09 | 0.104587E+09 | 0.337435E+09 | 0.198915E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52780164.69 | 19696094.93 | 33084069.76 | 9667252.42 | 0.198915E+09 |
February | 80169482.78 | 42176459.88 | 37993022.91 | 44988683.80 | 0.122743E+09 |
March | 0.151622E+09 | 71536362.23 | 80085864.37 | 0.133421E+09 | 0.105974E+09 |
April | 0.183943E+09 | 0.103017E+09 | 80926353.75 | 0.185676E+09 | 69151539.05 |
May | 0.245940E+09 | 0.141353E+09 | 0.104587E+09 | 0.269886E+09 | 58129267.36 |
June | 0.287621E+09 | 0.186037E+09 | 0.101585E+09 | 0.319709E+09 | 60332067.45 |
July | 0.307739E+09 | 0.216594E+09 | 91144959.21 | 0.337435E+09 | 78520062.24 |
August | 0.255337E+09 | 0.174912E+09 | 80425238.16 | 0.269812E+09 | 83028342.12 |
September | 0.169191E+09 | 0.107067E+09 | 62123521.16 | 0.169325E+09 | 78414402.43 |
October | 0.105426E+09 | 56914896.08 | 48511255.61 | 84428315.46 | 90159669.24 |
November | 59812672.88 | 27291670.98 | 32521001.91 | 27603832.61 | 0.109529E+09 |
December | 40841095.77 | 13813438.40 | 27027657.37 | 6472923.00 | 0.165405E+09 |
Annual Sum or Average | 0.194042E+10 | 0.116041E+10 | 0.780014E+09 | 0.185843E+10 | 0.122030E+10 |
Minimum of Months | 40841095.77 | 13813438.40 | 27027657.37 | 6472923.00 | 58129267.36 |
Maximum of Months | 0.307739E+09 | 0.216594E+09 | 0.104587E+09 | 0.337435E+09 | 0.198915E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52780164.69 | 19696094.93 | 33084069.76 | 9667252.42 | 0.198915E+09 |
February | 80169482.78 | 42176459.88 | 37993022.91 | 44988683.80 | 0.122743E+09 |
March | 0.151622E+09 | 71536362.23 | 80085864.37 | 0.133421E+09 | 0.105974E+09 |
April | 0.183943E+09 | 0.103017E+09 | 80926353.75 | 0.185676E+09 | 69151539.05 |
May | 0.245940E+09 | 0.141353E+09 | 0.104587E+09 | 0.269886E+09 | 58129267.36 |
June | 0.287621E+09 | 0.186037E+09 | 0.101585E+09 | 0.319709E+09 | 60332067.45 |
July | 0.307739E+09 | 0.216594E+09 | 91144959.21 | 0.337435E+09 | 78520062.24 |
August | 0.255337E+09 | 0.174912E+09 | 80425238.16 | 0.269812E+09 | 83028342.12 |
September | 0.169191E+09 | 0.107067E+09 | 62123521.16 | 0.169325E+09 | 78414402.43 |
October | 0.105426E+09 | 56914896.08 | 48511255.61 | 84428315.46 | 90159669.24 |
November | 59812672.88 | 27291670.98 | 32521001.91 | 27603832.61 | 0.109529E+09 |
December | 40841095.77 | 13813438.40 | 27027657.37 | 6472923.00 | 0.165405E+09 |
Annual Sum or Average | 0.194042E+10 | 0.116041E+10 | 0.780014E+09 | 0.185843E+10 | 0.122030E+10 |
Minimum of Months | 40841095.77 | 13813438.40 | 27027657.37 | 6472923.00 | 58129267.36 |
Maximum of Months | 0.307739E+09 | 0.216594E+09 | 0.104587E+09 | 0.337435E+09 | 0.198915E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52780164.69 | 19696094.93 | 33084069.76 | 9667252.42 | 0.198915E+09 |
February | 80169482.78 | 42176459.88 | 37993022.91 | 44988683.80 | 0.122743E+09 |
March | 0.151622E+09 | 71536362.23 | 80085864.37 | 0.133421E+09 | 0.105974E+09 |
April | 0.183943E+09 | 0.103017E+09 | 80926353.75 | 0.185676E+09 | 69151539.05 |
May | 0.245940E+09 | 0.141353E+09 | 0.104587E+09 | 0.269886E+09 | 58129267.36 |
June | 0.287621E+09 | 0.186037E+09 | 0.101585E+09 | 0.319709E+09 | 60332067.45 |
July | 0.307739E+09 | 0.216594E+09 | 91144959.21 | 0.337435E+09 | 78520062.24 |
August | 0.255337E+09 | 0.174912E+09 | 80425238.16 | 0.269812E+09 | 83028342.12 |
September | 0.169191E+09 | 0.107067E+09 | 62123521.16 | 0.169325E+09 | 78414402.43 |
October | 0.105426E+09 | 56914896.08 | 48511255.61 | 84428315.46 | 90159669.24 |
November | 59812672.88 | 27291670.98 | 32521001.91 | 27603832.61 | 0.109529E+09 |
December | 40841095.77 | 13813438.40 | 27027657.37 | 6472923.00 | 0.165405E+09 |
Annual Sum or Average | 0.194042E+10 | 0.116041E+10 | 0.780014E+09 | 0.185843E+10 | 0.122030E+10 |
Minimum of Months | 40841095.77 | 13813438.40 | 27027657.37 | 6472923.00 | 58129267.36 |
Maximum of Months | 0.307739E+09 | 0.216594E+09 | 0.104587E+09 | 0.337435E+09 | 0.198915E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52780164.69 | 19696094.93 | 33084069.76 | 9667252.42 | 0.198915E+09 |
February | 80169482.78 | 42176459.88 | 37993022.91 | 44988683.80 | 0.122743E+09 |
March | 0.151622E+09 | 71536362.23 | 80085864.37 | 0.133421E+09 | 0.105974E+09 |
April | 0.183943E+09 | 0.103017E+09 | 80926353.75 | 0.185676E+09 | 69151539.05 |
May | 0.245940E+09 | 0.141353E+09 | 0.104587E+09 | 0.269886E+09 | 58129267.36 |
June | 0.287621E+09 | 0.186037E+09 | 0.101585E+09 | 0.319709E+09 | 60332067.45 |
July | 0.307739E+09 | 0.216594E+09 | 91144959.21 | 0.337435E+09 | 78520062.24 |
August | 0.255337E+09 | 0.174912E+09 | 80425238.16 | 0.269812E+09 | 83028342.12 |
September | 0.169191E+09 | 0.107067E+09 | 62123521.16 | 0.169325E+09 | 78414402.43 |
October | 0.105426E+09 | 56914896.08 | 48511255.61 | 84428315.46 | 90159669.24 |
November | 59812672.88 | 27291670.98 | 32521001.91 | 27603832.61 | 0.109529E+09 |
December | 40841095.77 | 13813438.40 | 27027657.37 | 6472923.00 | 0.165405E+09 |
Annual Sum or Average | 0.194042E+10 | 0.116041E+10 | 0.780014E+09 | 0.185843E+10 | 0.122030E+10 |
Minimum of Months | 40841095.77 | 13813438.40 | 27027657.37 | 6472923.00 | 58129267.36 |
Maximum of Months | 0.307739E+09 | 0.216594E+09 | 0.104587E+09 | 0.337435E+09 | 0.198915E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52780164.69 | 19696094.93 | 33084069.76 | 9667252.42 | 0.198915E+09 |
February | 80169482.78 | 42176459.88 | 37993022.91 | 44988683.80 | 0.122743E+09 |
March | 0.151622E+09 | 71536362.23 | 80085864.37 | 0.133421E+09 | 0.105974E+09 |
April | 0.183943E+09 | 0.103017E+09 | 80926353.75 | 0.185676E+09 | 69151539.05 |
May | 0.245940E+09 | 0.141353E+09 | 0.104587E+09 | 0.269886E+09 | 58129267.36 |
June | 0.287621E+09 | 0.186037E+09 | 0.101585E+09 | 0.319709E+09 | 60332067.45 |
July | 0.307739E+09 | 0.216594E+09 | 91144959.21 | 0.337435E+09 | 78520062.24 |
August | 0.255337E+09 | 0.174912E+09 | 80425238.16 | 0.269812E+09 | 83028342.12 |
September | 0.169191E+09 | 0.107067E+09 | 62123521.16 | 0.169325E+09 | 78414402.43 |
October | 0.105426E+09 | 56914896.08 | 48511255.61 | 84428315.46 | 90159669.24 |
November | 59812672.88 | 27291670.98 | 32521001.91 | 27603832.61 | 0.109529E+09 |
December | 40841095.77 | 13813438.40 | 27027657.37 | 6472923.00 | 0.165405E+09 |
Annual Sum or Average | 0.194042E+10 | 0.116041E+10 | 0.780014E+09 | 0.185843E+10 | 0.122030E+10 |
Minimum of Months | 40841095.77 | 13813438.40 | 27027657.37 | 6472923.00 | 58129267.36 |
Maximum of Months | 0.307739E+09 | 0.216594E+09 | 0.104587E+09 | 0.337435E+09 | 0.198915E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52780164.69 | 19696094.93 | 33084069.76 | 9667252.42 | 0.198915E+09 |
February | 80169482.78 | 42176459.88 | 37993022.91 | 44988683.80 | 0.122743E+09 |
March | 0.151622E+09 | 71536362.23 | 80085864.37 | 0.133421E+09 | 0.105974E+09 |
April | 0.183943E+09 | 0.103017E+09 | 80926353.75 | 0.185676E+09 | 69151539.05 |
May | 0.245940E+09 | 0.141353E+09 | 0.104587E+09 | 0.269886E+09 | 58129267.36 |
June | 0.287621E+09 | 0.186037E+09 | 0.101585E+09 | 0.319709E+09 | 60332067.45 |
July | 0.307739E+09 | 0.216594E+09 | 91144959.21 | 0.337435E+09 | 78520062.24 |
August | 0.255337E+09 | 0.174912E+09 | 80425238.16 | 0.269812E+09 | 83028342.12 |
September | 0.169191E+09 | 0.107067E+09 | 62123521.16 | 0.169325E+09 | 78414402.43 |
October | 0.105426E+09 | 56914896.08 | 48511255.61 | 84428315.46 | 90159669.24 |
November | 59812672.88 | 27291670.98 | 32521001.91 | 27603832.61 | 0.109529E+09 |
December | 40841095.77 | 13813438.40 | 27027657.37 | 6472923.00 | 0.165405E+09 |
Annual Sum or Average | 0.194042E+10 | 0.116041E+10 | 0.780014E+09 | 0.185843E+10 | 0.122030E+10 |
Minimum of Months | 40841095.77 | 13813438.40 | 27027657.37 | 6472923.00 | 58129267.36 |
Maximum of Months | 0.307739E+09 | 0.216594E+09 | 0.104587E+09 | 0.337435E+09 | 0.198915E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 31.66 | 886.52 | 154.38 | 49.05 | 105.34 | 0.00 | 0.00 |
February | 123.50 | 616.65 | 252.05 | 100.66 | 151.39 | 0.00 | 0.00 |
March | 187.40 | 487.08 | 339.77 | 96.45 | 243.32 | 0.00 | 0.00 |
April | 341.42 | 320.21 | 430.45 | 151.83 | 278.63 | 0.00 | 0.00 |
May | 481.47 | 256.72 | 538.72 | 199.79 | 338.93 | 0.00 | 0.00 |
June | 583.90 | 199.09 | 594.52 | 226.57 | 367.95 | 0.00 | 0.00 |
July | 646.45 | 192.27 | 594.60 | 249.82 | 344.77 | 0.00 | 0.00 |
August | 523.75 | 210.76 | 499.38 | 199.28 | 300.10 | 0.00 | 0.00 |
September | 375.29 | 266.68 | 395.84 | 162.77 | 233.07 | 0.00 | 0.00 |
October | 209.27 | 344.74 | 284.38 | 114.61 | 169.77 | 0.00 | 0.00 |
November | 97.44 | 496.60 | 199.52 | 80.85 | 118.68 | 0.00 | 0.00 |
December | 29.92 | 733.80 | 137.52 | 46.06 | 91.46 | 0.00 | 0.00 |
Annual Sum or Average | 303.58 | 417.02 | 368.98 | 139.96 | 229.02 | 0.00 | 0.00 |
Minimum of Months | 29.92 | 192.27 | 137.52 | 46.06 | 91.46 | 0.00 | 0.00 |
Maximum of Months | 646.45 | 886.52 | 594.60 | 249.82 | 367.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 36.09 | 742.66 | 197.06 | 73.54 | 123.52 | 0.00 | 0.00 |
February | 185.96 | 507.37 | 331.39 | 174.34 | 157.05 | 0.00 | 0.00 |
March | 498.14 | 395.66 | 566.09 | 267.09 | 299.01 | 0.00 | 0.00 |
April | 716.34 | 266.79 | 709.66 | 397.44 | 312.22 | 0.00 | 0.00 |
May | 1007.64 | 217.03 | 918.24 | 527.75 | 390.48 | 0.00 | 0.00 |
June | 1233.45 | 232.76 | 1109.65 | 717.73 | 391.92 | 0.00 | 0.00 |
July | 1259.84 | 293.16 | 1148.97 | 808.67 | 340.30 | 0.00 | 0.00 |
August | 1007.36 | 309.99 | 953.32 | 653.05 | 300.27 | 0.00 | 0.00 |
September | 653.26 | 302.52 | 652.74 | 413.07 | 239.67 | 0.00 | 0.00 |
October | 315.22 | 336.62 | 393.62 | 212.50 | 181.12 | 0.00 | 0.00 |
November | 106.50 | 422.57 | 230.76 | 105.29 | 125.47 | 0.00 | 0.00 |
December | 24.17 | 617.55 | 152.48 | 51.57 | 100.91 | 0.00 | 0.00 |
Annual Sum or Average | 589.30 | 386.96 | 615.30 | 367.96 | 247.34 | 0.00 | 0.00 |
Minimum of Months | 24.17 | 217.03 | 152.48 | 51.57 | 100.91 | 0.00 | 0.00 |
Maximum of Months | 1259.84 | 742.66 | 1148.97 | 808.67 | 391.92 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 84809783.70 | 0.237445E+10 | 0.413500E+09 | 0.131364E+09 | 0.282136E+09 | 0.00 | 0.00 |
February | 0.298770E+09 | 0.149181E+10 | 0.609760E+09 | 0.243524E+09 | 0.366237E+09 | 0.00 | 0.00 |
March | 0.501930E+09 | 0.130460E+10 | 0.910051E+09 | 0.258341E+09 | 0.651710E+09 | 0.00 | 0.00 |
April | 0.884957E+09 | 0.829981E+09 | 0.111574E+10 | 0.393537E+09 | 0.722201E+09 | 0.00 | 0.00 |
May | 0.128956E+10 | 0.687589E+09 | 0.144291E+10 | 0.535123E+09 | 0.907791E+09 | 0.00 | 0.00 |
June | 0.151347E+10 | 0.516035E+09 | 0.154099E+10 | 0.587270E+09 | 0.953721E+09 | 0.00 | 0.00 |
July | 0.173145E+10 | 0.514971E+09 | 0.159257E+10 | 0.669131E+09 | 0.923443E+09 | 0.00 | 0.00 |
August | 0.140281E+10 | 0.564492E+09 | 0.133754E+10 | 0.533738E+09 | 0.803798E+09 | 0.00 | 0.00 |
September | 0.972746E+09 | 0.691231E+09 | 0.102602E+10 | 0.421900E+09 | 0.604117E+09 | 0.00 | 0.00 |
October | 0.560496E+09 | 0.923358E+09 | 0.761684E+09 | 0.306962E+09 | 0.454722E+09 | 0.00 | 0.00 |
November | 0.252553E+09 | 0.128719E+10 | 0.517165E+09 | 0.209556E+09 | 0.307609E+09 | 0.00 | 0.00 |
December | 80148130.35 | 0.196542E+10 | 0.368345E+09 | 0.123373E+09 | 0.244972E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.957370E+10 | 0.131511E+11 | 0.116363E+11 | 0.441382E+10 | 0.722246E+10 | 0.00 | 0.00 |
Minimum of Months | 80148130.35 | 0.514971E+09 | 0.368345E+09 | 0.123373E+09 | 0.244972E+09 | 0.00 | 0.00 |
Maximum of Months | 0.173145E+10 | 0.237445E+10 | 0.159257E+10 | 0.669131E+09 | 0.953721E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 96672232.06 | 0.198915E+10 | 0.527802E+09 | 0.196961E+09 | 0.330841E+09 | 0.00 | 0.00 |
February | 0.449886E+09 | 0.122743E+10 | 0.801695E+09 | 0.421765E+09 | 0.379930E+09 | 0.00 | 0.00 |
March | 0.133421E+10 | 0.105974E+10 | 0.151622E+10 | 0.715364E+09 | 0.800859E+09 | 0.00 | 0.00 |
April | 0.185676E+10 | 0.691515E+09 | 0.183943E+10 | 0.103017E+10 | 0.809264E+09 | 0.00 | 0.00 |
May | 0.269886E+10 | 0.581291E+09 | 0.245940E+10 | 0.141353E+10 | 0.104587E+10 | 0.00 | 0.00 |
June | 0.319709E+10 | 0.603319E+09 | 0.287621E+10 | 0.186037E+10 | 0.101585E+10 | 0.00 | 0.00 |
July | 0.337435E+10 | 0.785199E+09 | 0.307739E+10 | 0.216594E+10 | 0.911450E+09 | 0.00 | 0.00 |
August | 0.269812E+10 | 0.830283E+09 | 0.255337E+10 | 0.174912E+10 | 0.804252E+09 | 0.00 | 0.00 |
September | 0.169325E+10 | 0.784143E+09 | 0.169191E+10 | 0.107067E+10 | 0.621235E+09 | 0.00 | 0.00 |
October | 0.844283E+09 | 0.901597E+09 | 0.105426E+10 | 0.569149E+09 | 0.485113E+09 | 0.00 | 0.00 |
November | 0.276038E+09 | 0.109529E+10 | 0.598127E+09 | 0.272917E+09 | 0.325210E+09 | 0.00 | 0.00 |
December | 64728682.37 | 0.165405E+10 | 0.408411E+09 | 0.138134E+09 | 0.270277E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.185843E+11 | 0.122030E+11 | 0.194042E+11 | 0.116041E+11 | 0.780014E+10 | 0.00 | 0.00 |
Minimum of Months | 64728682.37 | 0.581291E+09 | 0.408411E+09 | 0.138134E+09 | 0.270277E+09 | 0.00 | 0.00 |
Maximum of Months | 0.337435E+10 | 0.198915E+10 | 0.307739E+10 | 0.216594E+10 | 0.104587E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.8 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -4.9 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.8 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.37 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.04 | 4.91 | 4.56 | 5.04 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.44 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.02 | 4.61 | 4.29 | 7.18 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.07 | 4.37 | 5.43 | 3.41 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.8 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.4 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.40 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.8 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.44 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.15 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.20 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.65 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.64 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.19 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.36 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.25 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.61 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.25 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.37 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.15 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.47 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.15 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.61 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.0 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.6 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.4 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.98 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.5 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.5 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.0 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.17 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.20 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.92 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.00 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.19 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.18 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.19 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.61 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.11 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.58 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.87 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.61 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.17 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.11 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.47 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.15 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.49 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.84 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.60 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.75 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.73 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.09 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.77 | 2.10 | 4.06 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.87 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.80 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.15 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.09 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.104532E+10 | -957255930.5 | 0.00 | 0.00 | 744.00 | 0.00 | -88064123.9 | 58.99 | 0.00 | 0.00 |
February | 0.973974E+09 | -894740489.4 | 0.00 | 0.00 | 672.00 | 0.00 | -79233196.9 | 58.99 | 0.00 | 0.00 |
March | 0.112211E+10 | -.103500E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87115604.4 | 58.99 | 0.00 | 0.00 |
April | 0.100900E+10 | -926360544.4 | 0.00 | 0.00 | 720.00 | 0.00 | -82637155.1 | 58.99 | 0.00 | 0.00 |
May | 0.992555E+09 | -910524489.7 | 0.00 | 0.00 | 744.00 | 0.00 | -82030251.0 | 58.99 | 0.00 | 0.00 |
June | 0.924317E+09 | -851146197.6 | 0.00 | 0.00 | 720.00 | 0.00 | -73170350.2 | 58.99 | 0.00 | 0.00 |
July | 0.852882E+09 | -780883722.0 | 0.00 | 0.00 | 744.00 | 0.00 | -71997850.2 | 59.00 | 0.00 | 0.00 |
August | 0.892797E+09 | -819672891.0 | 0.00 | 0.00 | 744.00 | 0.00 | -73124059.0 | 58.99 | 0.00 | 0.00 |
September | 0.847049E+09 | -772423767.3 | 0.00 | 0.00 | 720.00 | 0.00 | -74625124.7 | 58.99 | 0.00 | 0.00 |
October | 0.893915E+09 | -810588127.7 | 0.00 | 0.00 | 744.00 | 0.00 | -83327099.5 | 58.99 | 0.00 | 0.00 |
November | 0.911564E+09 | -827635041.8 | 0.00 | 0.00 | 720.00 | 0.00 | -83929280.5 | 58.99 | 0.00 | 0.00 |
December | 0.100251E+10 | -914644167.1 | 0.00 | 0.00 | 744.00 | 0.00 | -87867439.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.114680E+11 | -.105009E+11 | 8760.00 | -967121534.7 | 58.99 | |||||
Minimum of Months | 0.847049E+09 | -.103500E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -88064123.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.112211E+10 | -772423767.3 | 0.00 | 0.00 | 744.00 | 0.00 | -71997850.2 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 304.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 385.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 417.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 421.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 352.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 317.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 269.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 236.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3965.83 | ||||||||||
Minimum of Months | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.127648E+11 | 27822.30 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.808510E+10 | 27822.30 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.699973E+10 | 27822.30 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.327646E+10 | 27822.30 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.223709E+10 | 27822.30 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111553E+09 | 27822.30 | 17-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15573819.23 | 5045.17 | 18-AUG-05:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.611819E+09 | 27822.30 | 13-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185734E+10 | 27822.30 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.506519E+10 | 27822.30 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.912294E+10 | 27822.30 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.501476E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.127648E+11 | 27822.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.685226E+11 | 81008.19 | 01-JAN-01:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.409545E+11 | 81008.19 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.313681E+11 | 81008.19 | 01-MAR-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.114934E+11 | 81008.19 | 01-APR-00:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.709158E+10 | 81008.19 | 01-MAY-00:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.117085E+10 | 80456.10 | 20-SEP-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.566085E+10 | 81008.19 | 08-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.259819E+11 | 81008.19 | 01-NOV-00:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.498009E+11 | 81008.19 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242045E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.685226E+11 | 81008.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.172449E+12 | 160804.04 | 05-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.889545E+11 | 118957.02 | 03-FEB-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.577987E+11 | 122722.48 | 04-MAR-01:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.507971E+10 | 53523.08 | 29-APR-04:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.556334E+10 | 52008.99 | 08-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.330814E+09 | 17919.81 | 11-OCT-05:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.429323E+11 | 107952.18 | 27-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111675E+12 | 160804.04 | 27-DEC-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.484783E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172449E+12 | 160804.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 463535.36 | 463535.36 | 385.66 | 07-APR-14:00 | 385.66 | 0.00 |
May | 0.00 | 0.00 | 0.353192E+09 | 0.352190E+09 | 5872.16 | 20-MAY-16:00 | 5872.16 | 0.00 |
June | 0.00 | 0.00 | 0.240411E+10 | 0.231544E+10 | 17711.41 | 22-JUN-05:03 | 13311.78 | 0.00 |
July | 0.00 | 0.00 | 0.537024E+10 | 0.520647E+10 | 19452.57 | 19-JUL-05:01 | 12994.92 | 0.00 |
August | 0.00 | 0.00 | 0.430273E+10 | 0.427056E+10 | 17166.90 | 08-AUG-05:01 | 16587.62 | 0.00 |
September | 0.00 | 0.00 | 0.154098E+10 | 0.142059E+10 | 18254.09 | 07-SEP-05:01 | 12074.92 | 0.00 |
October | 0.00 | 0.00 | 48941422.67 | 48941422.67 | 3727.18 | 18-OCT-16:00 | 3727.18 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.140207E+11 | 0.136147E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.537024E+10 | 0.520647E+10 | 19452.57 | 16587.62 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 17943820.58 | 17943820.58 | 3911.34 | 20-MAY-16:00 | 3911.34 | 0.00 |
June | 0.00 | 0.00 | 0.283878E+10 | 0.274218E+10 | 45189.75 | 23-JUN-19:40 | 44535.32 | 0.00 |
July | 0.00 | 0.00 | 0.941229E+10 | 0.921510E+10 | 49335.17 | 16-JUL-10:11 | 37913.09 | 0.00 |
August | 0.00 | 0.00 | 0.675430E+10 | 0.672915E+10 | 45260.32 | 08-AUG-20:41 | 45173.74 | 0.00 |
September | 0.00 | 0.00 | 0.215507E+10 | 0.199935E+10 | 50310.53 | 06-SEP-17:40 | 36843.29 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.211784E+11 | 0.207037E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.941229E+10 | 0.921510E+10 | 50310.53 | 45173.74 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.106333E+10 | 0.08 | 411.22 | 01-JAN-00:03 | 0.09 |
February | 0.823055E+09 | 0.07 | 411.22 | 01-FEB-00:01 | 0.09 |
March | 0.760036E+09 | 0.06 | 411.22 | 01-MAR-00:03 | 0.09 |
April | 0.141583E+09 | 0.01 | 411.22 | 01-APR-00:10 | 0.09 |
May | 0.112160E+09 | 0.01 | 411.22 | 01-MAY-00:02 | 0.09 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 16234938.54 | 0.00 | 411.22 | 10-OCT-04:40 | 0.09 |
November | 0.468247E+09 | 0.04 | 411.22 | 10-NOV-04:10 | 0.09 |
December | 0.972266E+09 | 0.08 | 411.22 | 01-DEC-00:02 | 0.09 |
Annual Sum or Average | 0.435691E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106333E+10 | 0.08 | 411.22 | 0.09 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143617E+10 | 0.76 | 1282.36 | 02-JAN-07:10 | 1.07 |
February | 0.125786E+10 | 0.63 | 1282.36 | 01-FEB-07:30 | 1.08 |
March | 0.144344E+10 | 0.56 | 1282.36 | 01-MAR-07:10 | 1.07 |
April | 0.130241E+10 | 0.44 | 1282.36 | 01-APR-06:10 | 1.07 |
May | 0.134737E+10 | 0.45 | 1282.36 | 01-MAY-06:20 | 1.07 |
June | 0.132497E+10 | 0.43 | 1282.36 | 05-JUN-08:30 | 1.07 |
July | 0.129164E+10 | 0.41 | 1282.36 | 01-JUL-07:20 | 1.06 |
August | 0.138845E+10 | 0.43 | 1282.36 | 01-AUG-08:15 | 1.06 |
September | 0.128374E+10 | 0.42 | 1282.36 | 30-SEP-10:00 | 1.07 |
October | 0.129018E+10 | 0.42 | 1282.36 | 12-OCT-07:50 | 1.07 |
November | 0.127384E+10 | 0.51 | 1282.36 | 08-NOV-17:30 | 1.07 |
December | 0.137460E+10 | 0.67 | 1282.36 | 06-DEC-12:20 | 1.07 |
Annual Sum or Average | 0.160147E+11 | 0.51 | |||
Minimum of Months | 0.125786E+10 | 0.41 | 1282.36 | 1.06 | |
Maximum of Months | 0.144344E+10 | 0.76 | 1282.36 | 1.08 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.404580E+10 | 0.91 | 2606.56 | 03-JAN-09:50 | 1.03 |
February | 0.334896E+10 | 0.89 | 2606.56 | 06-FEB-12:10 | 1.03 |
March | 0.360103E+10 | 0.89 | 2606.56 | 01-MAR-09:50 | 1.03 |
April | 0.291262E+10 | 0.71 | 2606.56 | 04-APR-07:10 | 1.03 |
May | 0.288752E+10 | 0.55 | 2606.56 | 04-MAY-07:20 | 1.03 |
June | 0.269899E+10 | 0.41 | 2606.56 | 06-JUN-15:10 | 1.02 |
July | 0.269877E+10 | 0.43 | 2606.56 | 01-JUL-17:00 | 1.02 |
August | 0.286295E+10 | 0.44 | 2606.56 | 01-AUG-15:00 | 1.02 |
September | 0.265747E+10 | 0.45 | 2606.56 | 01-SEP-10:50 | 1.02 |
October | 0.274677E+10 | 0.55 | 2606.56 | 04-OCT-07:40 | 1.03 |
November | 0.317101E+10 | 0.82 | 2606.56 | 03-NOV-06:40 | 1.03 |
December | 0.376822E+10 | 0.92 | 2606.56 | 01-DEC-09:10 | 1.03 |
Annual Sum or Average | 0.374001E+11 | 0.66 | |||
Minimum of Months | 0.265747E+10 | 0.41 | 2606.56 | 1.02 | |
Maximum of Months | 0.404580E+10 | 0.92 | 2606.56 | 1.03 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.37 | 0.02 |
February | 2.38 | 0.01 |
March | 3.17 | 0.01 |
April | 1.02 | 0.07 |
May | 1.05 | 0.59 |
June | 1.85 | 2.55 |
July | 3.31 | 0.33 |
August | 3.76 | 1.33 |
September | 1.52 | 0.88 |
October | 1.04 | 1.26 |
November | 1.69 | 0.00 |
December | 3.07 | 0.03 |
Annual Sum or Average | 26.23 | 0.55 |
Minimum of Months | 1.02 | 0.00 |
Maximum of Months | 3.76 | 2.55 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.26 | 0.00 |
February | 0.00 | 0.00 |
March | 0.08 | 0.00 |
April | 0.08 | 0.00 |
May | 0.08 | 0.00 |
June | 0.39 | 0.00 |
July | 2.59 | 0.00 |
August | 0.33 | 0.00 |
September | 0.22 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 4.04 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.59 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.06 | 0.00 |
July | 0.33 | 0.00 |
August | 0.43 | 0.00 |
September | 0.08 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.90 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.43 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.143617E+10 | 0.179752E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.125786E+10 | 0.115642E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.144344E+10 | 0.101245E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.130252E+10 | 0.478278E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.143539E+10 | 0.326151E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.192359E+10 | 0.167767E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.263734E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.247012E+10 | 23771105.51 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.166225E+10 | 0.901621E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.130221E+10 | 0.272291E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.127384E+10 | 0.733720E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.137460E+10 | 0.130670E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.195193E+11 | 0.719284E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.125786E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.263734E+10 | 0.179752E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.404580E+10 | 0.946149E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.334896E+10 | 0.579827E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.360103E+10 | 0.447292E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.291262E+10 | 0.167339E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.289334E+10 | 0.102079E+11 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.357310E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.562890E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.499754E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.333122E+10 | 0.172934E+10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.274677E+10 | 0.827621E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.317101E+10 | 0.370763E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.376822E+10 | 0.703763E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.440185E+11 | 0.341727E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.274677E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.562890E+10 | 0.946149E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143617E+10 | 0.00 | 0.127648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125786E+10 | 0.00 | 0.808510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144344E+10 | 0.00 | 0.699973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130241E+10 | 463535.36 | 0.327646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134737E+10 | 0.353192E+09 | 0.223709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132497E+10 | 0.240411E+10 | 0.111553E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129164E+10 | 0.537024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138845E+10 | 0.430273E+10 | 15573819.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128374E+10 | 0.154098E+10 | 0.611819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129018E+10 | 48941422.67 | 0.185734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127384E+10 | 0.00 | 0.506519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137460E+10 | 0.00 | 0.912294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160147E+11 | 0.140207E+11 | 0.501476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144344E+10 | 0.537024E+10 | 0.127648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.404580E+10 | 0.00 | 0.685226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.334896E+10 | 0.00 | 0.409545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.360103E+10 | 0.00 | 0.313681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.291262E+10 | 0.00 | 0.114934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.288752E+10 | 17943820.58 | 0.709158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.269899E+10 | 0.283878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.269877E+10 | 0.941229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.286295E+10 | 0.675430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.265747E+10 | 0.215507E+10 | 0.117085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.274677E+10 | 0.00 | 0.566085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.317101E+10 | 0.00 | 0.259819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.376822E+10 | 0.00 | 0.498009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.374001E+11 | 0.211784E+11 | 0.242045E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.265747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.404580E+10 | 0.941229E+10 | 0.685226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.143617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130241E+10 | 0.00 | 0.00 | 0.00 | 115181.47 | 0.00 | 0.478278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134737E+10 | 0.00 | 0.00 | 0.00 | 88023226.95 | 0.00 | 0.326151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132497E+10 | 0.00 | 0.00 | 0.00 | 0.598624E+09 | 0.00 | 0.167767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129164E+10 | 0.00 | 0.00 | 0.00 | 0.134570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138845E+10 | 0.00 | 0.00 | 0.00 | 0.108166E+10 | 0.00 | 23771105.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128374E+10 | 0.00 | 0.00 | 0.00 | 0.378516E+09 | 0.00 | 0.901621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129018E+10 | 0.00 | 0.00 | 0.00 | 12032545.04 | 0.00 | 0.272291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160147E+11 | 0.00 | 0.00 | 0.00 | 0.350467E+10 | 0.00 | 0.719284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.125786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144344E+10 | 0.00 | 0.00 | 0.00 | 0.134570E+10 | 0.00 | 0.179752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.404580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.946149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.334896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.360103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.291262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.288752E+10 | 0.00 | 0.00 | 0.00 | 5821355.20 | 0.00 | 0.102079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.269899E+10 | 0.00 | 0.00 | 0.00 | 0.874107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.269877E+10 | 0.00 | 0.00 | 0.00 | 0.293013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.286295E+10 | 0.00 | 0.00 | 0.00 | 0.213458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.265747E+10 | 0.00 | 0.00 | 0.00 | 0.673746E+09 | 0.00 | 0.172934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.274677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.827621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.317101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.376822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.374001E+11 | 0.00 | 0.00 | 0.00 | 0.661839E+10 | 0.00 | 0.341727E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.265747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.404580E+10 | 0.00 | 0.00 | 0.00 | 0.293013E+10 | 0.00 | 0.946149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287210E+10 | 0.00 | 0.00 | 0.12 |
February | 27543262.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200792E+10 | 0.00 | 0.00 | 0.13 |
March | 42167012.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192358E+10 | 0.00 | 0.00 | 0.13 |
April | 0.254971E+09 | 0.00 | 0.00 | 224.56 | 0.00 | 0.104232E+10 | 2059755.83 | 0.00 | 0.14 |
May | 0.376842E+09 | 5493662.74 | 594609.20 | 346749.25 | 1809535.29 | 0.648546E+09 | 0.299036E+09 | 3194.54 | 0.23 |
June | 0.225112E+09 | 93531272.30 | 0.00 | 2669086.84 | 0.00 | 10332688.53 | 0.144436E+10 | 0.00 | 0.48 |
July | 20629154.47 | 0.209141E+09 | 0.00 | 5621840.92 | 0.00 | 0.00 | 0.137355E+10 | 0.00 | 0.50 |
August | 67035152.81 | 0.149428E+09 | 0.00 | 5149821.06 | 0.00 | 2107553.99 | 0.168114E+10 | 0.00 | 0.56 |
September | 0.328220E+09 | 64590697.17 | 0.00 | 2312917.73 | 0.00 | 0.174213E+09 | 0.110553E+10 | 0.00 | 0.39 |
October | 0.521517E+09 | 1074493.82 | 0.00 | 69000.85 | 0.00 | 0.591083E+09 | 0.119558E+09 | 0.00 | 0.16 |
November | 0.137173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141775E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235400E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.200121E+10 | 0.523259E+09 | 594609.20 | 16169641.21 | 1809535.29 | 0.130440E+11 | 0.602524E+10 | 3194.54 | 0.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.521517E+09 | 0.209141E+09 | 594609.20 | 5621840.92 | 1809535.29 | 0.287210E+10 | 0.168114E+10 | 3194.54 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112327E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.923641E+10 | 0.00 | 0.00 | 0.17 |
February | 0.606650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555148E+10 | 0.00 | 0.00 | 0.17 |
March | 0.179413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375717E+10 | 0.00 | 0.00 | 0.19 |
April | 0.206610E+10 | 0.00 | 0.00 | 0.00 | 5596220.14 | 0.128597E+10 | 0.00 | 0.00 | 0.18 |
May | 0.243972E+10 | 0.00 | 0.00 | 0.00 | 30131724.41 | 0.543343E+09 | 0.00 | 0.00 | 0.18 |
June | 0.194698E+10 | 0.178993E+09 | 0.00 | 1312254.96 | 20451294.08 | 0.00 | 0.347024E+09 | 0.00 | 0.25 |
July | 0.737953E+09 | 0.500188E+09 | 0.00 | 6292408.52 | 0.00 | 0.00 | 0.169736E+10 | 0.00 | 0.37 |
August | 0.126791E+10 | 0.389650E+09 | 0.00 | 2992137.38 | 0.00 | 0.00 | 0.126308E+10 | 0.00 | 0.33 |
September | 0.189823E+10 | 0.123422E+09 | 0.00 | 956833.10 | 12833560.10 | 96997866.35 | 0.423569E+09 | 0.00 | 0.23 |
October | 0.232942E+10 | 0.00 | 0.00 | 0.00 | 14065163.21 | 0.511551E+09 | 0.00 | 0.00 | 0.18 |
November | 0.155170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264552E+10 | 0.00 | 0.00 | 0.17 |
December | 0.448977E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675818E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.172001E+11 | 0.119225E+10 | 0.00 | 11553633.96 | 83077961.94 | 0.303866E+11 | 0.373103E+10 | 0.00 | 0.22 |
Minimum of Months | 0.112327E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.243972E+10 | 0.500188E+09 | 0.00 | 6292408.52 | 30131724.41 | 0.923641E+10 | 0.169736E+10 | 0.00 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:44
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |