Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Honolulu Intl Arpt HI USA TMY3 WMO#=911820
Simulation Timestamp: 2020-06-03 19:11:57
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1016.34 | 210.20 | 210.20 |
Net Site Energy | 1016.34 | 210.20 | 210.20 |
Total Source Energy | 3103.79 | 641.93 | 641.93 |
Net Source Energy | 3103.79 | 641.93 | 641.93 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 55.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 135.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 63.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.70 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 961.15 | 55.19 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 55.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 135.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 12.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 50.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22.70 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 124.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 45.93 | 11.41 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 198.79 | 11.41 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 124.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 45.93 | 11.41 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 198.79 | 11.41 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 961.153 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 961.153 | 100.00 |
Total On-Site and Utility Electric Sources | 961.153 | 100.00 |
Total Electricity End Uses | 961.153 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 76.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 126.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_HI_HONOLULU
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Honolulu Intl Arpt HI USA TMY3 WMO#=911820 |
Latitude [deg] | 21.32 |
Longitude [deg] | -157.9 |
Elevation [m] | 2.00 |
Time Zone | -10.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 26.81 |
Skylight-Roof Ratio [%] | 0.58 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.6337 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.5069 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.5069 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 05-SEP-14:50 | 01-JAN-00:10 | - | - | - | 12-APR-11:00 |
Heating | 0.00 | 1750.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18340.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6286.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1682.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 71611.45 | 1750.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 1750.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 18340.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 3981.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1682.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 59.82 | 0.00 | 0.00 | 0.00 |
Cooling | 429.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1507.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 391.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 201.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 71.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3043.97 | 59.82 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 12.37 | 0.00 | 0.00 | 0.00 |
Cooling | 88.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 81.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 41.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 629.55 | 12.37 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 12.37 | 0.00 | 0.00 | 0.00 |
Cooling | 88.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 81.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 41.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 629.55 | 12.37 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.15 |
ZONE2 FINE STORAGE DIRECT AIR | 2.44 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 0.814033 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 0.814033 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 33800.34 |
PSZ-OFFICE HEATING COIL | 28674.69 |
PSZ-FINE STORAGE HEATING COIL | 111309.70 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.00 | 1.000000 | 1.15 |
PSZ-FINE STORAGE | 2.44 | 2.44 | 2.44 | 2.44 | 2.44 | 2.44 | 1.00 | 1.000000 | 2.44 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.15 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 2.44 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.15 | 1.15 | 1.15 | 1.15 | 22289.26 | 28674.69 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.44 | 2.44 | 2.44 | 2.44 | 60674.67 | 111309.70 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.15 | 0.573295 | 1.15 | 21758.09 | 22289.26 | 11144.63 | 22289.26 | 0.744072 | 0.744070 | 0.744070 | 0.744070 |
PSZ-FINE STORAGE COOLING COIL | 2.44 | 1.22 | 2.44 | 60674.70 | 60674.67 | 30337.33 | 60674.67 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.15 | 1307.24 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.44 | 2674.28 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.20 | 24.80 | 23.70 | 22.50 | 22.80 | 23.20 | 23.80 | 25.20 | 25.90 | 26.90 | 27.10 | 26.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Honolulu Intl Arpt HI USA TMY3 WMO#=911820 | 21.32 | -157.93 | -10.00 | 2.00 | 101301 | 1.2040 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.92 | 4.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.634 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.707 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.507 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.507 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.507 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.066 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2518.900 | 10.634 | 503.780 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2518.900 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11853.648 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11853.648 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27263.390 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27263.390 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
2 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
3 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
4 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
5 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
6 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
13 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
14 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
15 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
16 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.14714251E-14 | -0.15793949E-15 | 0.73826229E-12 | 0.12610148E-15 |
85 | 3 | -0.53553847E-04 | 0.48261894E-06 | -0.37015163E-03 | 0.14168247E-12 |
86 | 2 | 1.1141045 | 0.10720623E-01 | 1.7048811 | -0.70963114E-04 |
87 | 1 | -16.929564 | 0.28051356 | -7.1749370 | 0.32672988 |
88 | 0 | 16.286769 | 0.18002168 | 5.9416824 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 28 | 1 | VerySmooth | 5.832 | 0.251 | 0.110 | 0.250 |
2 | SKYLIGHT_U_1.02_SHGC_0.4 | 29 | 1 | VerySmooth | 5.779 | 0.400 | 0.232 | 0.401 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 30 | 1 | VerySmooth | 5.779 | 0.400 | 0.232 | 0.401 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.23173 | 0.20656 | 0.20656 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.23173 | 0.20656 | 0.20656 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11612.27869 | 13934.73443 | 0.95549 | 1.14659 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 31.20600 | 1.43490E-002 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 4169.71965 | 5003.66358 | 0.11064 | 0.13277 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 08:00:00 | 16.20000 | 1.15180E-002 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 31737.66517 | 38085.19820 | 2.03614 | 2.44337 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 31.20600 | 1.43490E-002 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.35393 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 16.20000 | 1.15180E-002 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 | |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 32.20000 | 1.43490E-002 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.81403 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 16.20000 | 1.15180E-002 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 17570.09 | 1.14659 | 1.14659 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 3770.42 | 0.13332 | 0.13332 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 08:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 45374.10 | 2.44337 | 2.44337 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 10191.33 | 0.35393 | 0.35393 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14659 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.44337 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.81403 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 0.81403 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 33800.34408 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 0.00000 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14659 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14659 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14659 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14659 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14659 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.14659 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.44337 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.44337 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.44337 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.44337 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.44337 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.44337 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.14659 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.44337 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14659 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14659 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14659 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14659 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.14659 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14659 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57330 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.14659 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21758.09222 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22289.26000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11144.63000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 22289.26000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74407 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74407 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74407 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74407 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22289.26000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28674.69429 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14659 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1307.23851 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28674.69429 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.44337 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.44337 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.44337 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.44337 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.44337 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.44337 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.22169 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.44337 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 60674.69580 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 60674.67000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 30337.33500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 60674.67000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 60674.67000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 111309.69692 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.44337 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2674.28087 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 111309.69692 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 21399.0 | 10.33 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 58775.5 | 13.78 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 7 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 3.8245088765E-002 | 2.7097456527E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1287102031 | 0.2047126875 | Pass | Pass | 0.1171378776 | 0.4122652748 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 4.0392123241E-002 | 3.5970075684E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 16.20 | 0.00 | 16.20 | Wetbulb [C] | 1.90 | 320.00 |
HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 32.20 | 7.10 | 23.30 | Wetbulb [C] | 6.70 | 60.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.233 | 0.240 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.233 | 0.240 | 3204.84 | 3178.03 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 5.832 | 0.251 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_1.2_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 5.832 | 0.251 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 5.832 | 0.251 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_1.2_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 5.832 | 0.251 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 1.19 | 0.00 | 2.68 | 2.68 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 1.19 | 0.00 | 2.68 | 2.68 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 1.19 | 0.00 | 2.68 | 2.68 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 1.19 | 0.00 | 2.68 | 2.68 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 1.19 | 0.00 | 2.68 | 2.68 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 1.19 | 0.00 | 2.68 | 2.68 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 1.19 | 0.00 | 2.68 | 2.68 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 1.19 | 0.00 | 2.68 | 2.68 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 1.19 | 0.00 | 2.68 | 2.68 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 1.19 | 0.00 | 2.68 | 2.68 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 44.47 | 5.800 | 0.341 | 0.341 | ||||||||||||
North Total or Average | 6.51 | 5.832 | 0.251 | 0.250 | ||||||||||||
Non-North Total or Average | 37.97 | 5.795 | 0.356 | 0.356 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.6337 | 236.88 | 2518.90 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.62 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.5069 | 1393.41 | 11853.65 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 135.00 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.5069 | 3204.84 | 27263.39 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 310.50 |
Interior Lighting Total | 8.6111 | 4835.13 | 41635.94 | 476.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.00 | AstronomicalClock | - | 83.86 | 83.86 | 123.68 | |
Exterior Lighting Total | 7857.00 | 123.68 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22289.26 | 16584.77 | 5704.49 | 0.74 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 60674.67 | 41020.93 | 19653.74 | 0.68 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 21399.0 | 10.33 | ||||
PSZ-FINE STORAGE COOLING COIL | 58775.5 | 13.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 33800.34 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28674.69 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 111309.70 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.81 | 75.63 | 92.91 | 1.00 | 4.39 | General | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.15 | 1307.24 | 1140.11 | 1.00 | 1.33 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.44 | 2674.28 | 1094.51 | 1.00 | 1.26 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11612.28 | 13934.73 | 58.83 | 0.955 | 1.147 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23.90 | 23.90 | 0.00843 | 31.21 | 0.01435 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 31737.67 | 38085.20 | 27.33 | 2.036 | 2.443 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 26.70 | 26.69 | 0.00997 | 31.21 | 0.01435 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00378 | 32.20 | 0.01435 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 4169.72 | 5003.66 | 21.12 | 0.111 | 0.133 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 08:00:00 | 20.00 | 20.00 | 0.00970 | 16.20 | 0.01152 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.354 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 0.00 | 15.56 | 0.00800 | 16.20 | 0.01152 | 0.354 | 0.00 | |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 0.00 | 10.00 | 0.01600 | 16.20 | 0.01152 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.15 | 1.15 | 0.13 | 0.13 | 1.1466 | 1.1466 | 1.1466 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.44 | 2.44 | 0.35 | 0.35 | 2.4434 | 2.4434 | 2.4434 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 33800.344 | 33800.344 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 33800.34 | 33800.34 | 0.814033 | 10.00 | 10.00 | 0.01600000 | 43.33 | 27.11 | 0.01600000 | 16.20 | 0.01151798 | 16.20 | 0.0000 | 10.00 | 0.01600000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 22289.260 | 0.000 | 1.146590 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 22289.26 | 18756.91 | 1.146590 | 24.67 | 17.07 | 0.00905338 | 12.00 | 11.25 | 0.00800000 | 31.21 | 0.01434903 | 23.03 | 10.4951 | 23.90 | 0.00843243 | 45.6701 | 11612.28 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28674.694 | 28674.694 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 08:00:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:20:00 | 28674.69 | 28674.69 | 1.146590 | 16.53 | 16.17 | 0.01134774 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 10.4951 | 20.00 | 0.00969984 | 66.5026 | 4169.72 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 60674.670 | 0.000 | 2.443370 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 60674.67 | 43598.90 | 2.443370 | 27.35 | 19.21 | 0.01060642 | 12.00 | 11.25 | 0.00800000 | 31.21 | 0.01434903 | 23.03 | 14.4852 | 26.69 | 0.00997247 | 45.6243 | 31737.67 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 111309.697 | 111309.697 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 111309.70 | 71396.72 | 2.443369 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 14.4852 | 15.56 | 0.00800000 | 72.7629 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 33800.344 | 33800.344 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.2040 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.814033 | 0.98011478 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 33800.34 | 33800.34 | 1.0000 | 0.98011478 | 0.814033 | 10.00 | 10.00 | 0.01600000 | 50360.9 | 43.33 | 27.11 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33800.34 | 16.20 | 0.01151798 | 16.20 | 0.00000000 | 0.0000 | 10.00 | 0.01600000 | 10.00 | 0.01600000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22289.260 | 0.000 | 1.146590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6698 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 22289.26 | 18756.91 | 1.0000 | 1.38052095 | 1.146590 | 24.67 | 17.07 | 0.00905338 | 47842.1 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22289.26 | 31.21 | 0.01434903 | 23.03 | 0.12033533 | 10.4951 | 23.90 | 0.00843243 | 23.90 | 0.00843243 | 45.6701 | 11612.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28674.694 | 28674.694 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.146590 | 1.38052086 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 08:00:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:20:00 | 28674.69 | 28674.69 | 1.0000 | 1.38052086 | 1.146590 | 16.53 | 16.17 | 0.01134774 | 45336.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28674.69 | 16.20 | 0.01151798 | 16.20 | 0.12033533 | 10.4951 | 19.70 | 0.00969984 | 20.00 | 0.00969984 | 66.5026 | 4169.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 60674.670 | 0.000 | 2.443370 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5568 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 60674.67 | 43598.90 | 1.0000 | 2.94187414 | 2.443370 | 27.35 | 19.21 | 0.01060642 | 54546.6 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 60674.67 | 31.21 | 0.01434903 | 23.03 | 0.35392745 | 14.4852 | 26.70 | 0.00997247 | 26.69 | 0.00997247 | 45.6243 | 31737.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 111309.697 | 111309.697 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.443369 | 2.94187302 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 111309.70 | 71396.72 | 1.0000 | 2.94187302 | 2.443369 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 111309.70 | 16.20 | 0.01151798 | 16.20 | 0.35392745 | 14.4852 | 0.00 | 0.00000000 | 15.56 | 0.00800000 | 72.7629 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3606.67 | 126.00 | 126.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 3606.67 | 126.00 | 126.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.00 | 78.17 | 0.00 | 76.50 |
ZONE2 FINE STORAGE | 0.00 | 169.50 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 247.67 | 0.00 | 76.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.414 | 0.402 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 961.15 | 5421.86 | 01-JAN-07:20 | 71611.45 | 05-SEP-14:50 |
Electricity:Building | 628.20 | 4938.86 | 01-JAN-00:10 | 47606.95 | 03-JAN-14:00 |
Electricity:Zone:ZONE1 OFFICE | 62.57 | 1027.15 | 01-JAN-00:10 | 3852.05 | 02-JAN-08:10 |
InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.62 | 453.40 | 01-JAN-00:10 | 1939.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 430.63 | 2726.34 | 01-JAN-00:10 | 33679.30 | 03-JAN-13:30 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 310.51 | 2726.34 | 01-JAN-00:10 | 23173.88 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 22.70 | 483.00 | 03-JAN-06:10 | 1727.22 | 19-JAN-12:20 |
WaterSystems:Electricity | 22.70 | 483.00 | 03-JAN-06:10 | 1727.22 | 19-JAN-12:20 |
Water Heater:WaterSystems:Electricity | 22.70 | 483.00 | 03-JAN-06:10 | 1727.22 | 19-JAN-12:20 |
Fans:Electricity | 63.61 | 0.00 | 01-JAN-00:10 | 6286.81 | 06-MAY-11:30 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 12.79 | 0.00 | 01-JAN-00:10 | 2305.29 | 03-MAY-12:50 |
Ventilation (simple):Fans:Electricity | 12.79 | 0.00 | 01-JAN-00:10 | 2305.29 | 03-MAY-12:50 |
ElectricityPurchased:Facility | 961.15 | 5421.86 | 01-JAN-07:20 | 71611.45 | 05-SEP-14:50 |
ElectricityPurchased:Plant | 961.15 | 5421.86 | 01-JAN-07:20 | 71611.45 | 05-SEP-14:50 |
Cogeneration:ElectricityPurchased | 961.15 | 5421.86 | 01-JAN-07:20 | 71611.45 | 05-SEP-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 961.15 | 5421.86 | 01-JAN-07:20 | 71611.45 | 05-SEP-14:50 |
ElectricityNet:Plant | 961.15 | 5421.86 | 01-JAN-07:20 | 71611.45 | 05-SEP-14:50 |
Cogeneration:ElectricityNet | 961.15 | 5421.86 | 01-JAN-07:20 | 71611.45 | 05-SEP-14:50 |
Electricity:HVAC | 186.57 | 0.00 | 01-JAN-00:10 | 24328.61 | 05-SEP-15:40 |
General:Fans:Electricity | 50.82 | 0.00 | 01-JAN-00:10 | 3981.52 | 13-JUN-08:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 135.75 | 0.00 | 01-JAN-00:10 | 20347.09 | 05-SEP-15:40 |
ExteriorLights:Electricity | 123.68 | 0.00 | 01-JAN-07:20 | 7857.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.68 | 0.00 | 01-JAN-07:20 | 7857.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 55.19 | 1750.00 | 03-JAN-06:10 | 1750.00 | 01-JAN-00:10 |
Gas:HVAC | 55.19 | 1750.00 | 03-JAN-06:10 | 1750.00 | 01-JAN-00:10 |
Heating:Gas | 55.19 | 1750.00 | 03-JAN-06:10 | 1750.00 | 01-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-APR-12:00 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-APR-12:00 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-APR-12:00 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-APR-12:00 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-APR-12:00 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-APR-12:00 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-APR-12:00 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 12-APR-12:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 763.59 | 0.00 | 01-JAN-00:10 | 115378.68 | 05-SEP-15:30 |
EnergyTransfer:Building | 282.88 | 0.00 | 01-JAN-00:10 | 43900.18 | 05-SEP-15:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 90.69 | 0.00 | 01-JAN-00:10 | 12819.11 | 05-SEP-05:10 |
Heating:EnergyTransfer | 0.20 | 0.00 | 01-JAN-00:10 | 1359.65 | 13-FEB-07:50 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.00 | 0.00 | 01-JAN-00:10 | 678.72 | 19-JAN-07:10 |
Cooling:EnergyTransfer | 282.67 | 0.00 | 01-JAN-00:10 | 43900.18 | 05-SEP-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 90.69 | 0.00 | 01-JAN-00:10 | 12819.11 | 05-SEP-05:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 192.18 | 0.00 | 01-JAN-00:10 | 32565.26 | 05-SEP-15:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.20 | 0.00 | 01-JAN-00:10 | 1359.65 | 13-FEB-07:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 191.98 | 0.00 | 01-JAN-00:10 | 32565.26 | 05-SEP-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 480.71 | 0.00 | 01-JAN-00:10 | 72185.63 | 05-SEP-15:40 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 480.71 | 0.00 | 01-JAN-00:10 | 72185.63 | 05-SEP-15:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.005 | -90.688 | 0.000 | 0.000 | 3.575 | 30.619 | 31.946 | 13.057 | 0.000 | 5.042 | 15.761 | 0.000 | -6.166 | 0.000 | -3.153 | -0.001 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 0.199 | -191.976 | 0.000 | 0.000 | 0.000 | 135.003 | 0.000 | 0.000 | 0.000 | 12.004 | 80.786 | 0.000 | 0.000 | 0.000 | -36.016 | 0.000 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 310.507 | 107.336 | 35.865 | 0.000 | 1.341 | 35.658 | 0.000 | -13.274 | 0.000 | -477.433 | -0.006 |
Total Facility | 0.000 | 0.000 | 0.204 | -282.663 | 0.000 | 0.000 | 3.575 | 476.129 | 139.282 | 48.922 | 0.000 | 18.386 | 132.205 | 0.000 | -19.439 | 0.000 | -516.602 | -0.008 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 07-FEB-06:01 | 0.00 | 0.00 | 0.00 | -19665.20 | 0.00 | 0.00 | 33.16 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 19852.62 | 0.00 | -740.11 | 0.00 | -633.58 | 0.00 |
ZONE2 FINE STORAGE | 30-APR-14:23 | 0.00 | 0.00 | 0.00 | -47589.11 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 1305.97 | 45097.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-JUL-16:03 | 0.00 | 0.00 | 0.00 | -56777.69 | 0.00 | 0.00 | 0.00 | 4365.11 | 573.75 | 4711.73 | 0.00 | 2120.82 | 65594.48 | 0.00 | 0.00 | 0.00 | -20588.19 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 19-JAN-07:10 | 0.00 | 0.00 | 678.66 | 0.00 | 0.00 | 0.00 | 75.26 | 1057.94 | 956.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -462.65 | 0.00 | -1841.40 | -464.06 |
ZONE2 FINE STORAGE | 13-FEB-08:40 | 0.00 | 0.00 | 1359.82 | 0.00 | 0.00 | 0.00 | 0.00 | 8890.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3720.82 | -6529.23 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 13-FEB-08:40 | -5485.56 | 5485.56 | 1359.82 | -5485.56 | 0.00 | 0.00 | 357.69 | 31277.33 | 10112.62 | 891.37 | 0.00 | 45.25 | 0.00 | 0.00 | 0.00 | 0.00 | -19033.64 | -19524.88 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1466 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.1466 | 0.1050 | 1.0000 | 0.1203 | 0.1050 | ||
PSZ-FINE STORAGE | 2.4434 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.4434 | 0.1449 | 1.0000 | 0.3539 | 0.1449 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1466 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.1466 | 1.0000 | 1.0000 | 0.1203 | 0.1050 | ||
PSZ-FINE STORAGE | 2.4434 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.4434 | 1.0000 | 1.0000 | 0.3539 | 0.1449 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.1466 | 1.1466 | 1.1466 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.4434 | 2.4434 | 2.4434 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1466 | 1.1466 | 1.1466 | 1.1466 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.4434 | 2.4434 | 2.4434 | 2.4434 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.1466 | 1.1466 | 1.1466 | 0.1203 | 0.9064 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.4434 | 2.4434 | 2.4434 | 0.3539 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1466 | 1.1466 | 1.1466 | 1.1466 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.4434 | 2.4434 | 2.4434 | 2.4434 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Honolulu Intl Arpt HI USA TMY3 WMO#=911820 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 76.50 |
Number of hours not met | 76.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 55.19 | 1750.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 135.75 | 20347.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 476.13 | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.68 | 7857.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 12.79 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 50.82 | 3981.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 22.70 | 1727.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 961.15 |
Natural Gas | 0.00 | 55.19 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1016.34 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 98.47 |
Space Heating | 0.00 |
Space Cooling | 28.08 |
Fans (All) | 13.16 |
Service Water Heating | 4.69 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 198.79 |
Subtotal | 198.79 |
Natural Gas [MJ/m2] | |
Space Heating | 11.41 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 11.41 |
Subtotal | 11.41 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 46.85 |
Space Heating | 5.43 |
Space Cooling | 13.36 |
Fans (All) | 6.26 |
Service Water Heating | 2.23 |
Receptacle Equipment | 13.70 |
Miscellaneous | 12.17 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_HI_HONOLULU
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.468720E+10 |
February | 0.000 | 0.423360E+10 |
March | 0.000 | 0.468720E+10 |
April | 0.000 | 0.453600E+10 |
May | 0.000 | 0.468720E+10 |
June | 0.000 | 0.453600E+10 |
July | 0.000 | 0.468720E+10 |
August | 0.000 | 0.468720E+10 |
September | 0.000 | 0.453600E+10 |
October | 0.000 | 0.468720E+10 |
November | 0.000 | 0.453600E+10 |
December | 0.000 | 0.468720E+10 |
Annual Sum or Average | 0.551880E+11 | |
Minimum of Months | 0.000 | 0.423360E+10 |
Maximum of Months | 0.000 | 0.468720E+10 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.579937E+10 | 19432.91 | 20-JAN-06:02 | 19.90 | 14.35 | 0.249007E+09 | 301.61 | 19-JAN-14:00 | 24.40 | 16.58 |
February | 0.584368E+10 | 19666.46 | 07-FEB-06:01 | 16.70 | 13.68 | 0.229095E+09 | 301.61 | 11-FEB-14:20 | 23.90 | 16.28 |
March | 0.705825E+10 | 18665.81 | 07-MAR-06:01 | 18.98 | 14.77 | 0.268952E+09 | 301.58 | 28-MAR-07:10 | 17.43 | 15.66 |
April | 0.683051E+10 | 18775.99 | 28-APR-05:01 | 19.50 | 16.32 | 0.249051E+09 | 301.61 | 01-APR-15:09 | 25.50 | 17.32 |
May | 0.811212E+10 | 18654.86 | 02-MAY-05:01 | 20.28 | 17.59 | 0.259047E+09 | 301.58 | 13-MAY-07:10 | 23.68 | 20.85 |
June | 0.843603E+10 | 17484.89 | 05-JUN-05:01 | 23.40 | 20.29 | 0.259060E+09 | 301.58 | 03-JUN-09:30 | 26.10 | 20.89 |
July | 0.874328E+10 | 17199.82 | 31-JUL-05:01 | 23.98 | 20.14 | 0.249121E+09 | 301.59 | 22-JUL-09:09 | 27.52 | 24.21 |
August | 0.941687E+10 | 17253.86 | 24-AUG-05:01 | 21.10 | 18.89 | 0.269048E+09 | 301.61 | 23-AUG-14:00 | 31.70 | 21.78 |
September | 0.873424E+10 | 17601.29 | 19-SEP-05:01 | 22.20 | 20.25 | 0.249129E+09 | 301.58 | 30-SEP-10:00 | 25.00 | 22.92 |
October | 0.808510E+10 | 17422.74 | 26-OCT-05:01 | 21.02 | 19.49 | 0.249099E+09 | 301.58 | 26-OCT-07:10 | 21.23 | 19.48 |
November | 0.709522E+10 | 17605.78 | 09-NOV-06:01 | 18.30 | 16.93 | 0.239109E+09 | 301.58 | 27-NOV-08:09 | 18.87 | 17.40 |
December | 0.653520E+10 | 19178.42 | 20-DEC-06:01 | 21.10 | 15.58 | 0.249043E+09 | 301.58 | 23-DEC-08:09 | 19.23 | 16.88 |
Annual Sum or Average | 0.906899E+11 | 0.301876E+10 | ||||||||
Minimum of Months | 0.579937E+10 | 17199.82 | 16.70 | 13.68 | 0.229095E+09 | 301.58 | 17.43 | 15.66 | ||
Maximum of Months | 0.941687E+10 | 19666.46 | 23.98 | 20.29 | 0.269048E+09 | 301.61 | 31.70 | 24.21 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.774571E+10 | 41305.07 | 01-JAN-14:23 | 28.90 | 22.16 | 0.00 | 0.00 | 01-JAN-00:10 | 22.75 | 19.82 |
February | 0.919328E+10 | 46678.55 | 26-FEB-16:23 | 27.50 | 19.04 | 0.00 | 0.00 | 01-FEB-00:10 | 20.60 | 15.61 |
March | 0.119361E+11 | 46042.41 | 16-MAR-17:06 | 26.60 | 19.71 | 0.00 | 0.00 | 01-MAR-00:10 | 21.18 | 19.93 |
April | 0.120096E+11 | 47592.16 | 30-APR-14:23 | 27.80 | 18.56 | 0.00 | 0.00 | 01-APR-00:10 | 22.12 | 19.67 |
May | 0.175594E+11 | 46087.31 | 30-MAY-17:08 | 26.32 | 19.22 | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 | 19.63 |
June | 0.188261E+11 | 46203.03 | 04-JUN-14:53 | 28.10 | 20.07 | 0.00 | 0.00 | 01-JUN-00:10 | 23.00 | 18.66 |
July | 0.229329E+11 | 45763.84 | 30-JUL-14:53 | 30.00 | 21.04 | 0.00 | 0.00 | 01-JUL-00:10 | 24.38 | 20.90 |
August | 0.242816E+11 | 44472.88 | 13-AUG-15:43 | 30.50 | 22.02 | 0.00 | 0.00 | 01-AUG-00:10 | 24.70 | 20.79 |
September | 0.233252E+11 | 44352.20 | 17-SEP-15:13 | 29.23 | 21.67 | 0.00 | 0.00 | 01-SEP-00:10 | 25.60 | 21.60 |
October | 0.198210E+11 | 44817.71 | 29-OCT-12:43 | 30.10 | 21.60 | 0.00 | 0.00 | 01-OCT-00:10 | 25.30 | 22.40 |
November | 0.138516E+11 | 43495.23 | 12-NOV-15:03 | 27.70 | 21.19 | 0.00 | 0.00 | 01-NOV-00:10 | 24.18 | 21.09 |
December | 0.105012E+11 | 42672.50 | 10-DEC-14:43 | 29.25 | 21.83 | 0.00 | 0.00 | 01-DEC-00:10 | 24.70 | 21.52 |
Annual Sum or Average | 0.191984E+12 | 0.00 | ||||||||
Minimum of Months | 0.774571E+10 | 41305.07 | 26.32 | 18.56 | 0.00 | 0.00 | 20.60 | 15.61 | ||
Maximum of Months | 0.242816E+11 | 47592.16 | 30.50 | 22.16 | 0.00 | 0.00 | 25.60 | 22.40 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 22.75 | 19.82 | 0.00 | 0.00 | 01-JAN-00:10 | 22.75 | 19.82 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 20.60 | 15.61 | 0.00 | 0.00 | 01-FEB-00:10 | 20.60 | 15.61 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 21.18 | 19.93 | 0.00 | 0.00 | 01-MAR-00:10 | 21.18 | 19.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.12 | 19.67 | 0.00 | 0.00 | 01-APR-00:10 | 22.12 | 19.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 | 19.63 | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 | 19.63 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 23.00 | 18.66 | 0.00 | 0.00 | 01-JUN-00:10 | 23.00 | 18.66 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 24.38 | 20.90 | 0.00 | 0.00 | 01-JUL-00:10 | 24.38 | 20.90 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 24.70 | 20.79 | 0.00 | 0.00 | 01-AUG-00:10 | 24.70 | 20.79 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 25.60 | 21.60 | 0.00 | 0.00 | 01-SEP-00:10 | 25.60 | 21.60 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.30 | 22.40 | 0.00 | 0.00 | 01-OCT-00:10 | 25.30 | 22.40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 24.18 | 21.09 | 0.00 | 0.00 | 01-NOV-00:10 | 24.18 | 21.09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.70 | 21.52 | 0.00 | 0.00 | 01-DEC-00:10 | 24.70 | 21.52 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 20.60 | 15.61 | 0.00 | 0.00 | 20.60 | 15.61 | ||
Maximum of Months | 0.00 | 0.00 | 25.60 | 22.40 | 0.00 | 0.00 | 25.60 | 22.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1944436.05 | 678.72 | 19-JAN-07:10 | 19.50 |
February | 1052024.30 | 543.15 | 15-FEB-07:10 | 17.38 |
March | 867134.09 | 540.42 | 09-MAR-07:10 | 17.07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.12 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 23.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 24.38 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 24.70 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 25.60 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 24.18 |
December | 690279.91 | 584.95 | 22-DEC-07:10 | 18.13 |
Annual Sum or Average | 4553874.36 | |||
Minimum of Months | 0.00 | 0.00 | 17.07 | |
Maximum of Months | 1944436.05 | 678.72 | 25.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 64119888.70 | 1233.55 | 11-JAN-17:50 | 22.88 |
February | 31316228.02 | 1359.65 | 13-FEB-07:50 | 23.80 |
March | 31356354.69 | 1006.54 | 03-MAR-09:00 | 23.30 |
April | 26925940.34 | 978.37 | 17-APR-06:10 | 22.80 |
May | 7497331.79 | 756.16 | 31-MAY-06:50 | 23.12 |
June | 4140616.80 | 898.76 | 10-JUN-06:10 | 24.08 |
July | 478413.01 | 797.36 | 13-JUL-06:10 | 23.58 |
August | 585888.01 | 727.39 | 09-AUG-06:10 | 25.10 |
September | 500970.09 | 489.33 | 09-SEP-06:10 | 24.50 |
October | 96092.37 | 160.15 | 25-OCT-06:10 | 21.70 |
November | 8858731.90 | 1332.36 | 17-NOV-07:15 | 23.53 |
December | 23436966.02 | 1072.05 | 19-DEC-18:00 | 22.80 |
Annual Sum or Average | 0.199313E+09 | |||
Minimum of Months | 96092.37 | 160.15 | 21.70 | |
Maximum of Months | 64119888.70 | 1359.65 | 25.10 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 22.75 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 20.60 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 21.18 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.12 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 23.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 24.38 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 24.70 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 25.60 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 24.18 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.70 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 20.60 | |
Maximum of Months | 0.00 | 0.00 | 25.60 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.256100E+10 | 1939.55 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.233575E+10 | 1939.55 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.266872E+10 | 1939.55 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.252182E+10 | 1939.55 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.261486E+10 | 1939.55 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.257569E+10 | 1939.55 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.256100E+10 | 1939.55 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.266872E+10 | 1939.55 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.252182E+10 | 1939.55 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.256100E+10 | 1939.55 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.246796E+10 | 1939.55 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.256100E+10 | 1939.55 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.306193E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.233575E+10 | 1939.55 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.266872E+10 | 1939.55 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112294E+11 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102778E+11 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.118738E+11 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.111270E+11 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.115516E+11 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.114492E+11 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112294E+11 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.118738E+11 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.111270E+11 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112294E+11 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108048E+11 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112294E+11 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135003E+12 | ||||
Minimum of Months | 0.102778E+11 | 10075.60 | 0.00 | 0.00 | |
Maximum of Months | 0.118738E+11 | 10075.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.258277E+11 | 23173.88 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.236390E+11 | 23173.88 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.273097E+11 | 23173.88 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.255921E+11 | 23173.88 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.265687E+11 | 23173.88 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.263332E+11 | 23173.88 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.258277E+11 | 23173.88 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.273097E+11 | 23173.88 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.255921E+11 | 23173.88 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.258277E+11 | 23173.88 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.248511E+11 | 23173.88 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.258277E+11 | 23173.88 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.236390E+11 | 23173.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.273097E+11 | 23173.88 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143451E+09 | 0.446282E+09 |
February | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156857E+09 | 0.319796E+09 |
March | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258426E+09 | 0.389465E+09 |
April | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280945E+09 | 0.344110E+09 |
May | 0.565842E+09 | 0.261486E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481933E+09 | 0.223927E+09 |
June | 0.565842E+09 | 0.257569E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519898E+09 | 0.201412E+09 |
July | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651518E+09 | 0.182223E+09 |
August | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776029E+09 | 0.155627E+09 |
September | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595395E+09 | 0.143907E+09 |
October | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578394E+09 | 0.174851E+09 |
November | 0.522316E+09 | 0.246796E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365482E+09 | 0.249944E+09 |
December | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233512E+09 | 0.320980E+09 |
Annual Sum or Average | 0.659424E+10 | 0.306193E+11 | 0.319458E+11 | 0.504184E+10 | 0.315253E+10 | ||||
Minimum of Months | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143451E+09 | 0.143907E+09 |
Maximum of Months | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776029E+09 | 0.446282E+09 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84748272.35 | 0.492206E+10 |
February | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80581969.44 | 0.363508E+10 |
March | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254827E+09 | 0.420404E+10 |
April | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351941E+09 | 0.411085E+10 |
May | 0.00 | 0.115516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904966E+09 | 0.262278E+10 |
June | 0.00 | 0.114492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111611E+10 | 0.258274E+10 |
July | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223626E+10 | 0.204012E+10 |
August | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250779E+10 | 0.164737E+10 |
September | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193952E+10 | 0.141862E+10 |
October | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160571E+10 | 0.153389E+10 |
November | 0.00 | 0.108048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736144E+09 | 0.327356E+10 |
December | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185063E+09 | 0.402479E+10 |
Annual Sum or Average | 0.135003E+12 | 0.120037E+11 | 0.360159E+11 | ||||||
Minimum of Months | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80581969.44 | 0.141862E+10 |
Maximum of Months | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250779E+10 | 0.492206E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24680854.84 | 0.217232E+11 |
February | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 198829.55 | 0.179491E+11 |
March | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220037E+11 |
April | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 161521.28 | 0.221877E+11 |
May | 0.00 | 0.265687E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 569333.45 | 0.160806E+11 |
June | 0.00 | 0.263332E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184831E+11 |
July | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10137132.67 | 0.166493E+11 |
August | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16957168.50 | 0.135279E+11 |
September | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14389125.47 | 0.139118E+11 |
October | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31684430.55 | 0.110091E+11 |
November | 0.00 | 0.248511E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27391.02 | 0.193386E+11 |
December | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 145269.35 | 0.209570E+11 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | 98951056.68 | 0.213821E+12 | |||||
Minimum of Months | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110091E+11 |
Maximum of Months | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31684430.55 | 0.221877E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1939.55 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1971.74 | 06-JAN-13:00 | 2273.80 | 30-JAN-07:10 |
February | 659.25 | 01-FEB-08:09 | 1939.55 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.10 | 22-FEB-13:00 | 3260.11 | 08-FEB-07:05 |
March | 659.25 | 01-MAR-08:09 | 1939.55 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1999.27 | 30-MAR-16:10 | 3062.81 | 08-MAR-07:05 |
April | 659.25 | 01-APR-07:10 | 1939.55 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1970.73 | 05-APR-12:00 | 1740.67 | 27-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1939.55 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2499.86 | 24-MAY-11:10 | 1610.20 | 23-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1939.55 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2513.38 | 29-JUN-11:10 | 485.13 | 09-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 1939.55 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2882.18 | 10-JUL-12:00 | 364.41 | 13-JUL-05:01 |
August | 659.25 | 01-AUG-07:10 | 1939.55 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3051.85 | 11-AUG-16:10 | 935.76 | 24-AUG-06:10 |
September | 659.25 | 01-SEP-07:10 | 1939.55 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3159.10 | 01-SEP-16:10 | 567.03 | 19-SEP-06:10 |
October | 659.25 | 02-OCT-07:10 | 1939.55 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2979.58 | 11-OCT-12:00 | 1708.82 | 19-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1939.55 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2478.79 | 06-NOV-13:00 | 2834.33 | 27-NOV-07:10 |
December | 659.25 | 01-DEC-08:09 | 1939.55 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2287.02 | 13-DEC-13:00 | 2207.05 | 21-DEC-07:20 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.10 | 364.41 | |||||
Maximum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 3159.10 | 3260.11 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1111.53 | 01-JAN-14:10 | 6976.77 | 11-JAN-17:00 |
February | 0.00 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1272.95 | 26-FEB-16:00 | 6557.96 | 10-FEB-18:00 |
March | 0.00 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3116.16 | 15-MAR-15:10 | 5971.08 | 22-MAR-08:00 |
April | 0.00 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3334.68 | 09-APR-13:57 | 7805.96 | 01-APR-07:20 |
May | 0.00 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4657.68 | 17-MAY-15:10 | 4125.70 | 31-MAY-21:00 |
June | 0.00 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4316.24 | 18-JUN-14:00 | 4221.97 | 13-JUN-06:20 |
July | 0.00 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6708.55 | 15-JUL-15:10 | 4042.06 | 13-JUL-06:10 |
August | 0.00 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7655.61 | 09-AUG-15:10 | 3147.18 | 03-AUG-23:00 |
September | 0.00 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8541.91 | 03-SEP-13:00 | 3387.06 | 30-SEP-06:10 |
October | 0.00 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6668.80 | 03-OCT-15:10 | 3264.19 | 19-OCT-07:00 |
November | 0.00 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5259.58 | 05-NOV-13:10 | 6924.14 | 25-NOV-18:00 |
December | 0.00 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2342.14 | 10-DEC-13:50 | 6179.99 | 20-DEC-08:40 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1111.53 | 3147.18 | |||
Maximum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8541.91 | 7805.96 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23173.88 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1631.49 | 01-JAN-14:00 | 26987.65 | 11-JAN-17:00 |
February | 0.00 | 23173.88 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 377.61 | 19-FEB-10:55 | 27363.31 | 10-FEB-16:00 |
March | 0.00 | 23173.88 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 23541.41 | 22-MAR-08:00 |
April | 0.00 | 23173.88 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 301.22 | 09-APR-13:53 | 29681.88 | 01-APR-07:20 |
May | 0.00 | 23173.88 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 756.80 | 13-MAY-13:55 | 17487.46 | 31-MAY-21:00 |
June | 0.00 | 23173.88 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 20518.22 | 13-JUN-08:00 |
July | 0.00 | 23173.88 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1182.20 | 10-JUL-12:00 | 17906.06 | 20-JUL-10:00 |
August | 0.00 | 23173.88 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1652.95 | 20-AUG-09:55 | 15285.23 | 08-AUG-07:50 |
September | 0.00 | 23173.88 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2401.91 | 03-SEP-12:45 | 18680.09 | 30-SEP-10:40 |
October | 0.00 | 23173.88 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1994.17 | 01-OCT-12:53 | 15210.02 | 30-OCT-07:50 |
November | 0.00 | 23173.88 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.33 | 05-NOV-12:52 | 24523.79 | 25-NOV-17:00 |
December | 0.00 | 23173.88 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 263.97 | 10-DEC-13:53 | 22466.90 | 20-DEC-08:30 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15210.02 | ||||
Maximum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 2401.91 | 29681.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19432.91 | 20-JAN-06:02 | 435.11 | 3476.08 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.37 |
February | 19666.46 | 07-FEB-06:01 | 507.62 | 4055.43 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 633.58 |
March | 18665.81 | 07-MAR-06:01 | 580.14 | 4634.78 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.13 |
April | 18775.99 | 28-APR-05:01 | 580.14 | 4634.78 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.50 |
May | 18654.86 | 02-MAY-05:01 | 652.66 | 5214.12 | 5163.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.41 |
June | 17484.89 | 05-JUN-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.72 |
July | 17199.82 | 31-JUL-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.54 |
August | 17253.86 | 24-AUG-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.14 |
September | 17601.29 | 19-SEP-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.03 |
October | 17422.74 | 26-OCT-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.00 |
November | 17605.78 | 09-NOV-06:01 | 580.14 | 4634.78 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 559.23 |
December | 19178.42 | 20-DEC-06:01 | 507.62 | 4055.43 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.79 |
Annual Sum or Average | |||||||||||
Minimum of Months | 17199.82 | 435.11 | 3476.08 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.00 | |
Maximum of Months | 19666.46 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 633.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 41305.07 | 01-JAN-14:23 | 0.00 | 3556.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 961.99 | 0.00 |
February | 46678.55 | 26-FEB-16:23 | 0.00 | 3556.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.98 | 0.00 |
March | 46042.41 | 16-MAR-17:06 | 0.00 | 5926.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.00 |
April | 47592.16 | 30-APR-14:23 | 0.00 | 3556.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1305.97 | 0.00 |
May | 46087.31 | 30-MAY-17:08 | 0.00 | 5926.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.08 |
June | 46203.03 | 04-JUN-14:53 | 0.00 | 3556.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.42 | 0.00 |
July | 45763.84 | 30-JUL-14:53 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2498.19 | 0.00 |
August | 44472.88 | 13-AUG-15:43 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2332.49 | 0.00 |
September | 44352.20 | 17-SEP-15:13 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1515.75 | 0.00 |
October | 44817.71 | 29-OCT-12:43 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2139.57 | 0.00 |
November | 43495.23 | 12-NOV-15:03 | 0.00 | 3556.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.53 | 0.00 |
December | 42672.50 | 10-DEC-14:43 | 0.00 | 3556.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1577.15 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 41305.07 | 0.00 | 3556.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47592.16 | 0.00 | 5926.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2498.19 | 574.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4168.82 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4951.08 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4092.04 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15386.40 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10757.51 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13159.42 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8966.21 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7173.22 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3624.19 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8616.28 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11965.14 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4360.32 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3624.19 | |
Maximum of Months | 0.00 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15386.40 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.748424E+11 | 65771.87 | 04-JAN-14:09 | 0.468720E+10 | 1750.00 | 01-JAN-00:10 |
February | 0.697623E+11 | 66528.04 | 28-FEB-13:00 | 0.423360E+10 | 1750.00 | 01-FEB-00:10 |
March | 0.801571E+11 | 67171.74 | 13-MAR-14:00 | 0.468720E+10 | 1750.00 | 01-MAR-00:10 |
April | 0.752016E+11 | 66027.07 | 24-APR-14:09 | 0.453600E+10 | 1750.00 | 01-APR-00:10 |
May | 0.818678E+11 | 67679.20 | 15-MAY-14:30 | 0.468720E+10 | 1750.00 | 01-MAY-00:10 |
June | 0.817519E+11 | 67943.10 | 29-JUN-14:20 | 0.453600E+10 | 1750.00 | 01-JUN-00:10 |
July | 0.846196E+11 | 69634.68 | 10-JUL-14:00 | 0.468720E+10 | 1750.00 | 01-JUL-00:10 |
August | 0.896242E+11 | 70409.77 | 28-AUG-13:00 | 0.468720E+10 | 1750.00 | 01-AUG-00:10 |
September | 0.850196E+11 | 71611.45 | 05-SEP-14:50 | 0.453600E+10 | 1750.00 | 01-SEP-00:10 |
October | 0.840734E+11 | 70082.49 | 02-OCT-14:30 | 0.468720E+10 | 1750.00 | 01-OCT-00:10 |
November | 0.770321E+11 | 68952.40 | 06-NOV-14:20 | 0.453600E+10 | 1750.00 | 01-NOV-00:10 |
December | 0.772009E+11 | 67064.99 | 13-DEC-14:09 | 0.468720E+10 | 1750.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.961153E+12 | 0.551880E+11 | ||||
Minimum of Months | 0.697623E+11 | 65771.87 | 0.423360E+10 | 1750.00 | ||
Maximum of Months | 0.896242E+11 | 71611.45 | 0.468720E+10 | 1750.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.396181E+11 | 0.115215E+11 | 0.115358E+11 | 0.00 | 0.408196E+10 | 0.00 | 0.00 | 0.614168E+10 | 0.00 | 0.00 | 0.00 | 0.194337E+10 | 0.00 |
February | 0.362526E+11 | 0.100554E+11 | 0.105871E+11 | 0.00 | 0.382638E+10 | 0.00 | 0.00 | 0.727962E+10 | 0.00 | 0.00 | 0.00 | 0.176118E+10 | 0.00 |
March | 0.418523E+11 | 0.106211E+11 | 0.123357E+11 | 0.00 | 0.466909E+10 | 0.00 | 0.00 | 0.870695E+10 | 0.00 | 0.00 | 0.00 | 0.197200E+10 | 0.00 |
April | 0.392410E+11 | 0.974425E+10 | 0.114862E+11 | 0.00 | 0.439443E+10 | 0.00 | 0.00 | 0.846619E+10 | 0.00 | 0.00 | 0.00 | 0.186950E+10 | 0.00 |
May | 0.407352E+11 | 0.963111E+10 | 0.119357E+11 | 0.00 | 0.557426E+10 | 0.00 | 0.00 | 0.120717E+11 | 0.00 | 0.00 | 0.00 | 0.191977E+10 | 0.00 |
June | 0.403581E+11 | 0.911255E+10 | 0.118862E+11 | 0.00 | 0.557272E+10 | 0.00 | 0.00 | 0.129602E+11 | 0.00 | 0.00 | 0.00 | 0.186219E+10 | 0.00 |
July | 0.396181E+11 | 0.947554E+10 | 0.115358E+11 | 0.00 | 0.657085E+10 | 0.00 | 0.00 | 0.155369E+11 | 0.00 | 0.00 | 0.00 | 0.188241E+10 | 0.00 |
August | 0.418523E+11 | 0.988096E+10 | 0.123357E+11 | 0.00 | 0.709817E+10 | 0.00 | 0.00 | 0.165324E+11 | 0.00 | 0.00 | 0.00 | 0.192475E+10 | 0.00 |
September | 0.392410E+11 | 0.100601E+11 | 0.114862E+11 | 0.00 | 0.646167E+10 | 0.00 | 0.00 | 0.159188E+11 | 0.00 | 0.00 | 0.00 | 0.185185E+10 | 0.00 |
October | 0.396181E+11 | 0.109087E+11 | 0.115358E+11 | 0.00 | 0.631354E+10 | 0.00 | 0.00 | 0.137859E+11 | 0.00 | 0.00 | 0.00 | 0.191138E+10 | 0.00 |
November | 0.381239E+11 | 0.110265E+11 | 0.110862E+11 | 0.00 | 0.471829E+10 | 0.00 | 0.00 | 0.102163E+11 | 0.00 | 0.00 | 0.00 | 0.186093E+10 | 0.00 |
December | 0.396181E+11 | 0.116441E+11 | 0.115358E+11 | 0.00 | 0.432847E+10 | 0.00 | 0.00 | 0.813576E+10 | 0.00 | 0.00 | 0.00 | 0.193869E+10 | 0.00 |
Annual Sum or Average | 0.476129E+12 | 0.123682E+12 | 0.139282E+12 | 0.636098E+11 | 0.00 | 0.135752E+12 | 0.226980E+11 | ||||||
Minimum of Months | 0.362526E+11 | 0.911255E+10 | 0.105871E+11 | 0.00 | 0.382638E+10 | 0.00 | 0.00 | 0.614168E+10 | 0.00 | 0.00 | 0.00 | 0.176118E+10 | 0.00 |
Maximum of Months | 0.418523E+11 | 0.116441E+11 | 0.123357E+11 | 0.00 | 0.709817E+10 | 0.00 | 0.00 | 0.165324E+11 | 0.00 | 0.00 | 0.00 | 0.197200E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.423360E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.453600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.453600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.453600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.453600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.551880E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.423360E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.468720E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35189.04 | 02-JAN-09:09 | 7857.00 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 6286.81 | 03-JAN-12:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35189.04 | 01-FEB-09:09 | 7857.00 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 6286.81 | 01-FEB-13:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35189.04 | 01-MAR-09:09 | 7857.00 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 6286.81 | 01-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35189.04 | 01-APR-08:09 | 7857.00 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 6286.81 | 04-APR-12:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35189.04 | 01-MAY-08:09 | 7857.00 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 6286.81 | 06-MAY-11:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35189.04 | 01-JUN-08:09 | 7857.00 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 6286.81 | 16-JUN-11:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35189.04 | 01-JUL-08:09 | 7857.00 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6286.81 | 01-JUL-08:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35189.04 | 01-AUG-08:09 | 7857.00 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6286.81 | 31-AUG-14:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35189.04 | 01-SEP-08:09 | 7857.00 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 6286.81 | 06-SEP-13:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35189.04 | 02-OCT-08:09 | 7857.00 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 6286.81 | 11-OCT-11:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35189.04 | 01-NOV-08:09 | 7857.00 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 6286.81 | 02-NOV-09:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35189.04 | 01-DEC-09:09 | 7857.00 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 6286.81 | 01-DEC-12:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35189.04 | 7857.00 | 10112.62 | 0.00 | 6286.81 | 0.00 | 0.00 | |||||
Maximum of Months | 35189.04 | 7857.00 | 10112.62 | 0.00 | 6286.81 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 12600.81 | 04-JAN-13:00 | 0.00 | 0.00 | 0.00 | 1727.22 | 19-JAN-12:20 | 0.00 |
February | 13241.75 | 28-FEB-13:00 | 0.00 | 0.00 | 0.00 | 1726.75 | 01-FEB-12:39 | 0.00 |
March | 14311.75 | 15-MAR-15:30 | 0.00 | 0.00 | 0.00 | 1724.01 | 01-MAR-12:00 | 0.00 |
April | 13107.29 | 10-APR-15:09 | 0.00 | 0.00 | 0.00 | 1718.60 | 01-APR-11:39 | 0.00 |
May | 15449.03 | 18-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1712.19 | 01-MAY-11:50 | 0.00 |
June | 15241.82 | 26-JUN-15:30 | 0.00 | 0.00 | 0.00 | 1706.68 | 02-JUN-11:20 | 0.00 |
July | 17553.12 | 05-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1703.43 | 03-JUL-11:39 | 0.00 |
August | 18211.19 | 09-AUG-15:09 | 0.00 | 0.00 | 0.00 | 1706.02 | 30-AUG-11:00 | 0.00 |
September | 20347.09 | 05-SEP-15:39 | 0.00 | 0.00 | 0.00 | 1711.19 | 30-SEP-11:30 | 0.00 |
October | 17636.61 | 02-OCT-15:09 | 0.00 | 0.00 | 0.00 | 1717.70 | 31-OCT-11:30 | 0.00 |
November | 16084.42 | 02-NOV-15:09 | 0.00 | 0.00 | 0.00 | 1723.21 | 30-NOV-12:00 | 0.00 |
December | 13961.28 | 13-DEC-12:00 | 0.00 | 0.00 | 0.00 | 1726.59 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12600.81 | 0.00 | 0.00 | 0.00 | 1703.43 | 0.00 | ||
Maximum of Months | 20347.09 | 0.00 | 0.00 | 0.00 | 1727.22 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 65771.87 | 04-JAN-14:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6286.81 | 0.00 | 0.00 | 12508.30 | 0.00 |
February | 66528.04 | 28-FEB-13:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6286.81 | 0.00 | 0.00 | 13241.75 | 0.00 |
March | 67171.74 | 13-MAR-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6286.81 | 0.00 | 0.00 | 13887.37 | 0.00 |
April | 66027.07 | 24-APR-14:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6286.81 | 0.00 | 0.00 | 12749.62 | 0.00 |
May | 67679.20 | 15-MAY-14:30 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6286.81 | 0.00 | 0.00 | 14415.98 | 0.00 |
June | 67943.10 | 29-JUN-14:20 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6286.81 | 0.00 | 0.00 | 14673.95 | 0.00 |
July | 69634.68 | 10-JUL-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6286.81 | 0.00 | 0.00 | 16366.29 | 0.00 |
August | 70409.77 | 28-AUG-13:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6286.81 | 0.00 | 0.00 | 17161.45 | 0.00 |
September | 71611.45 | 05-SEP-14:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6286.81 | 0.00 | 0.00 | 18340.10 | 0.00 |
October | 70082.49 | 02-OCT-14:30 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6286.81 | 0.00 | 0.00 | 16807.03 | 0.00 |
November | 68952.40 | 06-NOV-14:20 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6286.81 | 0.00 | 0.00 | 15694.92 | 0.00 |
December | 67064.99 | 13-DEC-14:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6286.81 | 0.00 | 0.00 | 13802.84 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 65771.87 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6286.81 | 0.00 | 0.00 | 12508.30 | 0.00 | |
Maximum of Months | 71611.45 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6286.81 | 0.00 | 0.00 | 18340.10 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 1750.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1750.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1750.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 1750.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 1750.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1750.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 1750.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 1750.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 1750.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 1750.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 1750.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 1750.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 1750.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 1750.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.62 | 1.50 | 24.62 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.80 | 3.83 | 24.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.66 | 3.50 | 24.66 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.75 | 5.00 | 24.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 24.82 | 8.50 | 24.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 25.01 | 8.67 | 24.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 25.22 | 8.33 | 25.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 25.08 | 9.00 | 24.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 25.08 | 8.50 | 25.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 25.05 | 8.33 | 24.85 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 24.77 | 6.50 | 24.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.63 | 4.83 | 24.63 |
Annual Sum or Average | 0.00 | 0.00 | 78.17 | 24.94 | 76.50 | 24.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.62 | 1.50 | 24.58 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 25.22 | 9.00 | 25.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.31 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.43 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.38 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.41 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.40 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.47 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 | 27.50 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 27.48 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 27.52 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 27.52 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.51 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.41 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 169.50 | 27.48 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.31 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 27.52 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 24.22 | 284.50 | 23.91 | 3.00 | 24.22 |
February | 18.83 | 24.02 | 268.50 | 23.91 | 18.83 | 24.02 |
March | 8.00 | 24.13 | 320.17 | 23.91 | 8.00 | 24.13 |
April | 1.17 | 24.59 | 300.00 | 23.92 | 1.17 | 24.59 |
May | 8.67 | 24.37 | 312.00 | 23.92 | 8.67 | 24.37 |
June | 8.00 | 24.51 | 312.00 | 23.93 | 8.00 | 24.51 |
July | 17.50 | 24.34 | 300.00 | 23.93 | 17.50 | 24.34 |
August | 12.50 | 24.48 | 324.00 | 23.93 | 12.50 | 24.48 |
September | 19.17 | 24.37 | 300.00 | 23.94 | 19.17 | 24.37 |
October | 10.83 | 24.41 | 300.00 | 23.93 | 10.83 | 24.41 |
November | 11.00 | 24.31 | 288.00 | 23.92 | 11.00 | 24.31 |
December | 7.33 | 24.24 | 297.50 | 23.92 | 7.33 | 24.24 |
Annual Sum or Average | 126.00 | 24.31 | 3606.67 | 23.92 | 126.00 | 24.31 |
Minimum of Months | 1.17 | 24.02 | 268.50 | 23.91 | 1.17 | 24.02 |
Maximum of Months | 19.17 | 24.59 | 324.00 | 23.94 | 19.17 | 24.59 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.918178E+10 | 0.242945E+10 | 288.97 | 0.724158E+10 | 0.194019E+10 | 0.00 | 1.00 | 02-JAN-06:01 | 0.00 | 01-JAN-00:10 | 27165.88 | 02-JAN-06:01 | 21036.96 | 20-JAN-06:02 | 10974.07 | 02-JAN-06:06 | 6150.20 | 02-JAN-06:01 | 0.00 | 01-JAN-00:10 |
February | 0.993292E+10 | 0.259835E+10 | 269.07 | 0.728100E+10 | 0.265192E+10 | 0.00 | 1.00 | 01-FEB-06:01 | 0.00 | 01-FEB-00:10 | 28913.19 | 18-FEB-06:01 | 20624.17 | 07-FEB-06:01 | 14964.01 | 18-FEB-06:01 | 6374.34 | 18-FEB-06:01 | 0.00 | 01-FEB-00:10 |
March | 0.113568E+11 | 0.300495E+10 | 314.53 | 0.877857E+10 | 0.257827E+10 | 0.00 | 1.00 | 01-MAR-06:01 | 0.00 | 01-MAR-00:10 | 27643.69 | 13-MAR-05:01 | 19722.42 | 08-MAR-06:02 | 11807.71 | 13-MAR-05:07 | 6216.00 | 13-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.107434E+11 | 0.285185E+10 | 293.27 | 0.846758E+10 | 0.227581E+10 | 0.00 | 1.00 | 01-APR-05:01 | 0.00 | 01-APR-00:10 | 26505.03 | 24-APR-05:01 | 19904.93 | 29-APR-05:01 | 9642.77 | 24-APR-05:05 | 6053.41 | 24-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.131819E+11 | 0.353751E+10 | 308.39 | 0.101327E+11 | 0.304915E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 27530.05 | 15-MAY-05:01 | 19696.90 | 02-MAY-05:01 | 11559.59 | 15-MAY-05:06 | 6200.66 | 15-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.138986E+11 | 0.370370E+10 | 310.38 | 0.104818E+11 | 0.341673E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 27016.98 | 14-JUN-05:01 | 18645.09 | 05-JUN-05:01 | 10644.88 | 02-JUN-05:06 | 6208.02 | 21-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.146568E+11 | 0.395516E+10 | 308.02 | 0.109312E+11 | 0.372568E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 28040.48 | 21-JUL-05:01 | 18440.68 | 31-JUL-05:01 | 12537.84 | 20-JUL-05:07 | 6346.22 | 20-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.157477E+11 | 0.428681E+10 | 327.78 | 0.118290E+11 | 0.391870E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 27521.14 | 02-AUG-05:01 | 18295.50 | 23-AUG-05:01 | 11424.86 | 02-AUG-05:07 | 6269.61 | 08-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.148366E+11 | 0.397038E+10 | 312.58 | 0.108661E+11 | 0.397053E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 28338.62 | 16-SEP-05:01 | 18668.84 | 19-SEP-05:01 | 12927.74 | 16-SEP-05:06 | 6328.43 | 11-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.136876E+11 | 0.370977E+10 | 301.59 | 0.101956E+11 | 0.349199E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 27926.60 | 10-OCT-05:01 | 18366.65 | 26-OCT-05:01 | 12001.33 | 10-OCT-05:06 | 6253.31 | 10-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.119549E+11 | 0.317549E+10 | 284.77 | 0.887914E+10 | 0.307577E+10 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 27684.87 | 06-NOV-06:01 | 18581.44 | 15-NOV-06:01 | 11894.09 | 18-NOV-06:06 | 6229.71 | 18-NOV-06:01 | 0.00 | 01-NOV-00:10 |
December | 0.108215E+11 | 0.285843E+10 | 292.24 | 0.817906E+10 | 0.264245E+10 | 0.00 | 1.00 | 01-DEC-06:01 | 0.00 | 01-DEC-00:10 | 27010.84 | 02-DEC-06:01 | 20718.21 | 20-DEC-06:01 | 10786.40 | 11-DEC-06:06 | 6153.73 | 06-DEC-06:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.150001E+12 | 0.400818E+11 | 3611.60 | 0.113263E+12 | 0.367372E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.918178E+10 | 0.242945E+10 | 269.07 | 0.724158E+10 | 0.194019E+10 | 0.00 | 1.00 | 0.00 | 26505.03 | 18295.50 | 9642.77 | 6053.41 | 0.00 | |||||||
Maximum of Months | 0.157477E+11 | 0.428681E+10 | 327.78 | 0.118290E+11 | 0.397053E+10 | 0.00 | 1.00 | 0.00 | 28913.19 | 21036.96 | 14964.01 | 6374.34 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.128836E+11 | 0.371223E+10 | 243.47 | 0.949179E+10 | 0.339180E+10 | 0.00 | 1.00 | 01-JAN-13:43 | 0.00 | 01-JAN-00:10 | 68208.32 | 01-JAN-13:43 | 45730.98 | 01-JAN-14:23 | 23062.10 | 01-JAN-13:43 | 17878.69 | 01-JAN-13:43 | 0.00 | 01-JAN-00:10 |
February | 0.165339E+11 | 0.468127E+10 | 246.69 | 0.111541E+11 | 0.537973E+10 | 0.00 | 1.00 | 19-FEB-13:03 | 0.00 | 01-FEB-00:10 | 70802.97 | 19-FEB-15:43 | 50674.47 | 26-FEB-16:23 | 27412.05 | 19-FEB-15:03 | 18047.36 | 19-FEB-13:43 | 0.00 | 01-FEB-00:10 |
March | 0.198630E+11 | 0.570200E+10 | 291.77 | 0.143853E+11 | 0.547770E+10 | 0.00 | 1.00 | 05-MAR-14:03 | 0.00 | 01-MAR-00:10 | 71093.16 | 12-MAR-13:23 | 49680.60 | 16-MAR-17:06 | 28652.05 | 12-MAR-13:23 | 18081.01 | 12-MAR-13:23 | 0.00 | 01-MAR-00:10 |
April | 0.194666E+11 | 0.561434E+10 | 283.79 | 0.144101E+11 | 0.505655E+10 | 0.00 | 1.00 | 09-APR-12:33 | 0.00 | 01-APR-00:10 | 68046.28 | 24-APR-17:10 | 52080.22 | 30-APR-14:23 | 21942.49 | 24-APR-17:10 | 17709.96 | 09-APR-12:33 | 0.00 | 01-APR-00:10 |
May | 0.293917E+11 | 0.853417E+10 | 355.19 | 0.211163E+11 | 0.827539E+10 | 0.00 | 1.00 | 05-MAY-17:10 | 0.00 | 01-MAY-00:10 | 70604.33 | 14-MAY-13:03 | 49856.46 | 30-MAY-17:08 | 27085.08 | 14-MAY-13:43 | 18049.37 | 14-MAY-14:23 | 0.00 | 01-MAY-00:10 |
June | 0.321494E+11 | 0.925654E+10 | 363.52 | 0.224873E+11 | 0.966211E+10 | 0.00 | 1.00 | 02-JUN-17:06 | 0.00 | 01-JUN-00:10 | 68826.03 | 25-JUN-10:13 | 50262.23 | 04-JUN-14:53 | 23989.46 | 27-JUN-17:43 | 17894.57 | 25-JUN-14:13 | 0.00 | 01-JUN-00:10 |
July | 0.398056E+11 | 0.115817E+11 | 411.83 | 0.273752E+11 | 0.124304E+11 | 0.00 | 1.00 | 01-JUL-17:06 | 0.00 | 01-JUL-00:10 | 74366.65 | 10-JUL-05:01 | 49470.07 | 01-JUL-17:06 | 34955.81 | 10-JUL-05:01 | 18537.42 | 23-JUL-11:03 | 0.00 | 01-JUL-00:10 |
August | 0.417904E+11 | 0.122456E+11 | 427.66 | 0.291528E+11 | 0.126376E+11 | 0.00 | 1.00 | 01-AUG-17:08 | 0.00 | 01-AUG-00:10 | 70696.59 | 01-AUG-17:43 | 48837.93 | 02-AUG-17:06 | 28302.92 | 01-AUG-17:43 | 18495.89 | 20-AUG-10:23 | 0.00 | 01-AUG-00:10 |
September | 0.414510E+11 | 0.119484E+11 | 434.63 | 0.276659E+11 | 0.137850E+11 | 0.00 | 1.00 | 01-SEP-17:06 | 0.00 | 01-SEP-00:20 | 72818.30 | 15-SEP-17:06 | 47552.69 | 28-SEP-17:06 | 32043.36 | 15-SEP-17:06 | 18775.16 | 03-SEP-13:13 | 0.00 | 01-SEP-00:10 |
October | 0.343961E+11 | 0.100761E+11 | 379.94 | 0.239360E+11 | 0.104601E+11 | 0.00 | 1.00 | 01-OCT-09:33 | 0.00 | 01-OCT-00:10 | 70197.40 | 22-OCT-14:33 | 48727.07 | 01-OCT-14:13 | 26968.33 | 22-OCT-14:33 | 18554.10 | 15-OCT-14:35 | 0.00 | 01-OCT-00:10 |
November | 0.244956E+11 | 0.704076E+10 | 302.58 | 0.168377E+11 | 0.765787E+10 | 0.00 | 1.00 | 02-NOV-17:10 | 0.00 | 01-NOV-00:10 | 69321.26 | 05-NOV-17:03 | 47687.17 | 12-NOV-15:03 | 25306.94 | 05-NOV-09:43 | 18232.65 | 05-NOV-13:45 | 0.00 | 01-NOV-00:10 |
December | 0.184864E+11 | 0.527733E+10 | 276.86 | 0.128497E+11 | 0.563670E+10 | 0.00 | 1.00 | 10-DEC-12:03 | 0.00 | 01-DEC-00:10 | 68502.18 | 10-DEC-12:03 | 46930.67 | 10-DEC-14:43 | 23541.06 | 10-DEC-12:03 | 17888.78 | 10-DEC-12:43 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.330713E+12 | 0.956704E+11 | 4017.95 | 0.230862E+12 | 0.998510E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.128836E+11 | 0.371223E+10 | 243.47 | 0.949179E+10 | 0.339180E+10 | 0.00 | 1.00 | 0.00 | 68046.28 | 45730.98 | 21942.49 | 17709.96 | 0.00 | |||||||
Maximum of Months | 0.417904E+11 | 0.122456E+11 | 434.63 | 0.291528E+11 | 0.137850E+11 | 0.00 | 1.00 | 0.00 | 74366.65 | 52080.22 | 34955.81 | 18775.16 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.58 | 13.11 | 24.47 | 89.95 | 83.82 | 0.00 | 0.00 | 744.00 |
February | 57.69 | 25.92 | 31.77 | 147.59 | 85.71 | 0.00 | 0.00 | 672.00 |
March | 63.68 | 26.43 | 37.25 | 169.52 | 81.40 | 0.00 | 0.00 | 744.00 |
April | 59.97 | 23.85 | 36.12 | 160.81 | 68.31 | 0.00 | 0.00 | 720.00 |
May | 57.03 | 20.22 | 36.81 | 167.09 | 56.87 | 0.00 | 0.00 | 744.00 |
June | 62.96 | 25.03 | 37.92 | 183.58 | 47.12 | 0.00 | 0.00 | 720.00 |
July | 63.30 | 26.94 | 36.36 | 196.99 | 40.73 | 0.00 | 0.00 | 744.00 |
August | 63.66 | 28.40 | 35.26 | 205.13 | 44.39 | 0.00 | 0.00 | 744.00 |
September | 74.79 | 33.64 | 41.15 | 230.29 | 42.64 | 0.00 | 0.00 | 720.00 |
October | 46.20 | 16.43 | 29.76 | 149.05 | 57.29 | 0.00 | 0.00 | 744.00 |
November | 44.52 | 17.86 | 26.66 | 126.26 | 63.99 | 0.00 | 0.00 | 720.00 |
December | 37.21 | 14.26 | 22.95 | 94.60 | 70.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.65 | 22.62 | 33.02 | 160.01 | 61.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 37.21 | 13.11 | 22.95 | 89.95 | 40.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 74.79 | 33.64 | 41.15 | 230.29 | 85.71 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.58 | 13.11 | 24.47 | 89.95 | 83.82 | 0.00 | 0.00 | 744.00 |
February | 57.69 | 25.92 | 31.77 | 147.59 | 85.71 | 0.00 | 0.00 | 672.00 |
March | 63.68 | 26.43 | 37.25 | 169.52 | 81.40 | 0.00 | 0.00 | 744.00 |
April | 59.97 | 23.85 | 36.12 | 160.81 | 68.31 | 0.00 | 0.00 | 720.00 |
May | 57.03 | 20.22 | 36.81 | 167.09 | 56.87 | 0.00 | 0.00 | 744.00 |
June | 62.96 | 25.03 | 37.92 | 183.58 | 47.12 | 0.00 | 0.00 | 720.00 |
July | 63.30 | 26.94 | 36.36 | 196.99 | 40.73 | 0.00 | 0.00 | 744.00 |
August | 63.66 | 28.40 | 35.26 | 205.13 | 44.39 | 0.00 | 0.00 | 744.00 |
September | 74.79 | 33.64 | 41.15 | 230.29 | 42.64 | 0.00 | 0.00 | 720.00 |
October | 46.20 | 16.43 | 29.76 | 149.05 | 57.29 | 0.00 | 0.00 | 744.00 |
November | 44.52 | 17.86 | 26.66 | 126.26 | 63.99 | 0.00 | 0.00 | 720.00 |
December | 37.21 | 14.26 | 22.95 | 94.60 | 70.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.65 | 22.62 | 33.02 | 160.01 | 61.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 37.21 | 13.11 | 22.95 | 89.95 | 40.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 74.79 | 33.64 | 41.15 | 230.29 | 85.71 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.35 | 0.00 | 12.35 | 23.47 | 50.81 | 0.00 | 0.00 | 744.00 |
February | 14.75 | 0.00 | 14.75 | 31.84 | 51.29 | 0.00 | 0.00 | 672.00 |
March | 16.86 | 0.00 | 16.85 | 38.81 | 49.21 | 0.00 | 0.00 | 744.00 |
April | 18.31 | 0.30 | 18.02 | 41.49 | 41.12 | 0.00 | 0.00 | 720.00 |
May | 23.26 | 2.77 | 20.49 | 63.86 | 33.13 | 0.00 | 0.00 | 744.00 |
June | 27.28 | 5.13 | 22.15 | 73.85 | 27.90 | 0.00 | 0.00 | 720.00 |
July | 24.91 | 3.98 | 20.93 | 74.36 | 24.09 | 0.00 | 0.00 | 744.00 |
August | 19.41 | 1.27 | 18.13 | 62.81 | 25.80 | 0.00 | 0.00 | 744.00 |
September | 17.91 | 0.03 | 17.88 | 54.11 | 25.09 | 0.00 | 0.00 | 720.00 |
October | 14.84 | 0.00 | 14.84 | 48.72 | 33.41 | 0.00 | 0.00 | 744.00 |
November | 13.37 | 0.00 | 13.37 | 34.22 | 38.04 | 0.00 | 0.00 | 720.00 |
December | 11.75 | 0.00 | 11.75 | 24.50 | 42.18 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 17.93 | 1.13 | 16.80 | 47.77 | 36.76 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 11.75 | 0.00 | 11.75 | 23.47 | 24.09 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 27.28 | 5.13 | 22.15 | 74.36 | 51.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.35 | 0.00 | 12.35 | 23.47 | 50.81 | 0.00 | 0.00 | 744.00 |
February | 14.75 | 0.00 | 14.75 | 31.84 | 51.29 | 0.00 | 0.00 | 672.00 |
March | 16.86 | 0.00 | 16.85 | 38.81 | 49.21 | 0.00 | 0.00 | 744.00 |
April | 18.31 | 0.30 | 18.01 | 41.49 | 41.12 | 0.00 | 0.00 | 720.00 |
May | 23.26 | 2.77 | 20.49 | 63.86 | 33.13 | 0.00 | 0.00 | 744.00 |
June | 27.28 | 5.13 | 22.15 | 73.85 | 27.90 | 0.00 | 0.00 | 720.00 |
July | 24.91 | 3.98 | 20.93 | 74.36 | 24.09 | 0.00 | 0.00 | 744.00 |
August | 19.41 | 1.27 | 18.13 | 62.81 | 25.80 | 0.00 | 0.00 | 744.00 |
September | 17.91 | 0.03 | 17.88 | 54.11 | 25.09 | 0.00 | 0.00 | 720.00 |
October | 14.84 | 0.00 | 14.84 | 48.72 | 33.41 | 0.00 | 0.00 | 744.00 |
November | 13.37 | 0.00 | 13.37 | 34.22 | 38.04 | 0.00 | 0.00 | 720.00 |
December | 11.75 | 0.00 | 11.75 | 24.50 | 42.18 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 17.93 | 1.13 | 16.80 | 47.76 | 36.76 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 11.75 | 0.00 | 11.75 | 23.47 | 24.09 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 27.28 | 5.13 | 22.15 | 74.36 | 51.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.43 | 29.53 | 17.90 | 75.32 | 49.09 | 6.00 | 0.00 | 744.00 |
February | 56.60 | 34.39 | 22.21 | 91.13 | 49.48 | 14.50 | 0.00 | 672.00 |
March | 67.64 | 40.88 | 26.76 | 111.40 | 48.72 | 0.17 | 0.00 | 744.00 |
April | 74.10 | 45.66 | 28.44 | 123.18 | 43.73 | 0.00 | 0.00 | 720.00 |
May | 80.25 | 50.74 | 29.51 | 137.13 | 38.64 | 0.00 | 0.00 | 744.00 |
June | 83.13 | 53.49 | 29.64 | 141.51 | 35.92 | 0.00 | 0.00 | 720.00 |
July | 84.10 | 57.42 | 26.68 | 145.74 | 32.82 | 0.00 | 0.00 | 744.00 |
August | 83.89 | 59.06 | 24.84 | 146.07 | 36.56 | 0.00 | 0.00 | 744.00 |
September | 75.63 | 47.58 | 28.04 | 130.88 | 34.84 | 0.00 | 0.00 | 720.00 |
October | 61.28 | 39.06 | 22.23 | 105.68 | 44.79 | 0.00 | 0.00 | 744.00 |
November | 51.35 | 31.05 | 20.30 | 84.22 | 44.35 | 0.00 | 0.00 | 720.00 |
December | 45.26 | 28.41 | 16.85 | 71.17 | 46.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.61 | 43.16 | 24.44 | 113.73 | 42.08 | 20.67 | 0.00 | 8760.00 |
Minimum of Months | 45.26 | 28.41 | 16.85 | 71.17 | 32.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.10 | 59.06 | 29.64 | 146.07 | 49.48 | 14.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.43 | 29.53 | 17.90 | 75.32 | 49.09 | 6.00 | 0.00 | 744.00 |
February | 56.60 | 34.39 | 22.21 | 91.13 | 49.48 | 14.50 | 0.00 | 672.00 |
March | 67.64 | 40.88 | 26.76 | 111.40 | 48.72 | 0.17 | 0.00 | 744.00 |
April | 74.10 | 45.66 | 28.44 | 123.18 | 43.73 | 0.00 | 0.00 | 720.00 |
May | 80.25 | 50.74 | 29.51 | 137.13 | 38.64 | 0.00 | 0.00 | 744.00 |
June | 83.13 | 53.49 | 29.64 | 141.51 | 35.92 | 0.00 | 0.00 | 720.00 |
July | 84.10 | 57.42 | 26.68 | 145.74 | 32.82 | 0.00 | 0.00 | 744.00 |
August | 83.89 | 59.06 | 24.84 | 146.07 | 36.56 | 0.00 | 0.00 | 744.00 |
September | 75.63 | 47.58 | 28.04 | 130.88 | 34.84 | 0.00 | 0.00 | 720.00 |
October | 61.28 | 39.06 | 22.23 | 105.68 | 44.79 | 0.00 | 0.00 | 744.00 |
November | 51.35 | 31.05 | 20.30 | 84.22 | 44.35 | 0.00 | 0.00 | 720.00 |
December | 45.26 | 28.41 | 16.85 | 71.17 | 46.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.61 | 43.16 | 24.44 | 113.73 | 42.08 | 20.67 | 0.00 | 8760.00 |
Minimum of Months | 45.26 | 28.41 | 16.85 | 71.17 | 32.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.10 | 59.06 | 29.64 | 146.07 | 49.48 | 14.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.43 | 29.53 | 17.90 | 75.32 | 49.09 | 6.00 | 0.00 | 744.00 |
February | 56.60 | 34.39 | 22.21 | 91.13 | 49.48 | 14.50 | 0.00 | 672.00 |
March | 67.64 | 40.88 | 26.76 | 111.40 | 48.72 | 0.17 | 0.00 | 744.00 |
April | 74.10 | 45.66 | 28.44 | 123.18 | 43.73 | 0.00 | 0.00 | 720.00 |
May | 80.25 | 50.74 | 29.51 | 137.13 | 38.64 | 0.00 | 0.00 | 744.00 |
June | 83.13 | 53.49 | 29.64 | 141.51 | 35.92 | 0.00 | 0.00 | 720.00 |
July | 84.10 | 57.42 | 26.68 | 145.74 | 32.82 | 0.00 | 0.00 | 744.00 |
August | 83.89 | 59.06 | 24.84 | 146.07 | 36.56 | 0.00 | 0.00 | 744.00 |
September | 75.63 | 47.58 | 28.04 | 130.88 | 34.84 | 0.00 | 0.00 | 720.00 |
October | 61.28 | 39.06 | 22.23 | 105.68 | 44.79 | 0.00 | 0.00 | 744.00 |
November | 51.35 | 31.05 | 20.30 | 84.22 | 44.35 | 0.00 | 0.00 | 720.00 |
December | 45.26 | 28.41 | 16.85 | 71.17 | 46.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.61 | 43.16 | 24.44 | 113.73 | 42.08 | 20.67 | 0.00 | 8760.00 |
Minimum of Months | 45.26 | 28.41 | 16.85 | 71.17 | 32.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.10 | 59.06 | 29.64 | 146.07 | 49.48 | 14.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.43 | 29.53 | 17.90 | 75.32 | 49.09 | 6.00 | 0.00 | 744.00 |
February | 56.60 | 34.39 | 22.21 | 91.13 | 49.48 | 14.50 | 0.00 | 672.00 |
March | 67.64 | 40.88 | 26.76 | 111.40 | 48.72 | 0.17 | 0.00 | 744.00 |
April | 74.10 | 45.66 | 28.44 | 123.18 | 43.73 | 0.00 | 0.00 | 720.00 |
May | 80.25 | 50.74 | 29.51 | 137.13 | 38.64 | 0.00 | 0.00 | 744.00 |
June | 83.13 | 53.49 | 29.64 | 141.51 | 35.92 | 0.00 | 0.00 | 720.00 |
July | 84.10 | 57.42 | 26.68 | 145.74 | 32.82 | 0.00 | 0.00 | 744.00 |
August | 83.89 | 59.06 | 24.84 | 146.07 | 36.56 | 0.00 | 0.00 | 744.00 |
September | 75.63 | 47.58 | 28.04 | 130.88 | 34.84 | 0.00 | 0.00 | 720.00 |
October | 61.28 | 39.06 | 22.23 | 105.68 | 44.79 | 0.00 | 0.00 | 744.00 |
November | 51.35 | 31.05 | 20.30 | 84.22 | 44.35 | 0.00 | 0.00 | 720.00 |
December | 45.26 | 28.41 | 16.85 | 71.17 | 46.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.61 | 43.16 | 24.44 | 113.73 | 42.08 | 20.67 | 0.00 | 8760.00 |
Minimum of Months | 45.26 | 28.41 | 16.85 | 71.17 | 32.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.10 | 59.06 | 29.64 | 146.07 | 49.48 | 14.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.43 | 29.53 | 17.90 | 75.32 | 49.09 | 6.00 | 0.00 | 744.00 |
February | 56.60 | 34.39 | 22.21 | 91.13 | 49.48 | 14.50 | 0.00 | 672.00 |
March | 67.64 | 40.88 | 26.76 | 111.40 | 48.72 | 0.17 | 0.00 | 744.00 |
April | 74.10 | 45.66 | 28.44 | 123.18 | 43.73 | 0.00 | 0.00 | 720.00 |
May | 80.25 | 50.74 | 29.51 | 137.13 | 38.64 | 0.00 | 0.00 | 744.00 |
June | 83.13 | 53.49 | 29.64 | 141.51 | 35.92 | 0.00 | 0.00 | 720.00 |
July | 84.10 | 57.42 | 26.68 | 145.74 | 32.82 | 0.00 | 0.00 | 744.00 |
August | 83.89 | 59.06 | 24.84 | 146.07 | 36.56 | 0.00 | 0.00 | 744.00 |
September | 75.63 | 47.58 | 28.04 | 130.88 | 34.84 | 0.00 | 0.00 | 720.00 |
October | 61.28 | 39.06 | 22.23 | 105.68 | 44.79 | 0.00 | 0.00 | 744.00 |
November | 51.35 | 31.05 | 20.30 | 84.22 | 44.35 | 0.00 | 0.00 | 720.00 |
December | 45.26 | 28.41 | 16.85 | 71.17 | 46.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.61 | 43.16 | 24.44 | 113.73 | 42.08 | 20.67 | 0.00 | 8760.00 |
Minimum of Months | 45.26 | 28.41 | 16.85 | 71.17 | 32.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.10 | 59.06 | 29.64 | 146.07 | 49.48 | 14.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.43 | 29.53 | 17.90 | 75.32 | 49.09 | 6.00 | 0.00 | 744.00 |
February | 56.60 | 34.39 | 22.21 | 91.13 | 49.48 | 14.50 | 0.00 | 672.00 |
March | 67.64 | 40.88 | 26.76 | 111.40 | 48.72 | 0.17 | 0.00 | 744.00 |
April | 74.10 | 45.66 | 28.44 | 123.18 | 43.73 | 0.00 | 0.00 | 720.00 |
May | 80.25 | 50.74 | 29.51 | 137.13 | 38.64 | 0.00 | 0.00 | 744.00 |
June | 83.13 | 53.49 | 29.64 | 141.51 | 35.92 | 0.00 | 0.00 | 720.00 |
July | 84.10 | 57.42 | 26.68 | 145.74 | 32.82 | 0.00 | 0.00 | 744.00 |
August | 83.89 | 59.06 | 24.84 | 146.07 | 36.56 | 0.00 | 0.00 | 744.00 |
September | 75.63 | 47.58 | 28.04 | 130.88 | 34.84 | 0.00 | 0.00 | 720.00 |
October | 61.28 | 39.06 | 22.23 | 105.68 | 44.79 | 0.00 | 0.00 | 744.00 |
November | 51.35 | 31.05 | 20.30 | 84.22 | 44.35 | 0.00 | 0.00 | 720.00 |
December | 45.26 | 28.41 | 16.85 | 71.17 | 46.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.61 | 43.16 | 24.44 | 113.73 | 42.08 | 20.67 | 0.00 | 8760.00 |
Minimum of Months | 45.26 | 28.41 | 16.85 | 71.17 | 32.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.10 | 59.06 | 29.64 | 146.07 | 49.48 | 14.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.43 | 29.53 | 17.90 | 75.32 | 49.09 | 6.00 | 0.00 | 744.00 |
February | 56.60 | 34.39 | 22.21 | 91.13 | 49.48 | 14.50 | 0.00 | 672.00 |
March | 67.64 | 40.88 | 26.76 | 111.40 | 48.72 | 0.17 | 0.00 | 744.00 |
April | 74.10 | 45.66 | 28.44 | 123.18 | 43.73 | 0.00 | 0.00 | 720.00 |
May | 80.25 | 50.74 | 29.51 | 137.13 | 38.64 | 0.00 | 0.00 | 744.00 |
June | 83.13 | 53.49 | 29.64 | 141.51 | 35.92 | 0.00 | 0.00 | 720.00 |
July | 84.10 | 57.42 | 26.68 | 145.74 | 32.82 | 0.00 | 0.00 | 744.00 |
August | 83.89 | 59.06 | 24.84 | 146.07 | 36.56 | 0.00 | 0.00 | 744.00 |
September | 75.63 | 47.58 | 28.04 | 130.88 | 34.84 | 0.00 | 0.00 | 720.00 |
October | 61.28 | 39.06 | 22.23 | 105.68 | 44.79 | 0.00 | 0.00 | 744.00 |
November | 51.35 | 31.05 | 20.30 | 84.22 | 44.35 | 0.00 | 0.00 | 720.00 |
December | 45.26 | 28.41 | 16.85 | 71.17 | 46.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.61 | 43.16 | 24.44 | 113.73 | 42.08 | 20.67 | 0.00 | 8760.00 |
Minimum of Months | 45.26 | 28.41 | 16.85 | 71.17 | 32.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.10 | 59.06 | 29.64 | 146.07 | 49.48 | 14.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.43 | 29.53 | 17.90 | 75.32 | 49.09 | 6.00 | 0.00 | 744.00 |
February | 56.60 | 34.39 | 22.21 | 91.13 | 49.48 | 14.50 | 0.00 | 672.00 |
March | 67.64 | 40.88 | 26.76 | 111.40 | 48.72 | 0.17 | 0.00 | 744.00 |
April | 74.10 | 45.66 | 28.44 | 123.18 | 43.73 | 0.00 | 0.00 | 720.00 |
May | 80.25 | 50.74 | 29.51 | 137.13 | 38.64 | 0.00 | 0.00 | 744.00 |
June | 83.13 | 53.49 | 29.64 | 141.51 | 35.92 | 0.00 | 0.00 | 720.00 |
July | 84.10 | 57.42 | 26.68 | 145.74 | 32.82 | 0.00 | 0.00 | 744.00 |
August | 83.89 | 59.06 | 24.84 | 146.07 | 36.56 | 0.00 | 0.00 | 744.00 |
September | 75.63 | 47.58 | 28.04 | 130.88 | 34.84 | 0.00 | 0.00 | 720.00 |
October | 61.28 | 39.06 | 22.23 | 105.68 | 44.79 | 0.00 | 0.00 | 744.00 |
November | 51.35 | 31.05 | 20.30 | 84.22 | 44.35 | 0.00 | 0.00 | 720.00 |
December | 45.26 | 28.41 | 16.85 | 71.17 | 46.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.61 | 43.16 | 24.44 | 113.73 | 42.08 | 20.67 | 0.00 | 8760.00 |
Minimum of Months | 45.26 | 28.41 | 16.85 | 71.17 | 32.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.10 | 59.06 | 29.64 | 146.07 | 49.48 | 14.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.43 | 29.53 | 17.90 | 75.32 | 49.09 | 6.00 | 0.00 | 744.00 |
February | 56.60 | 34.39 | 22.21 | 91.13 | 49.48 | 14.50 | 0.00 | 672.00 |
March | 67.64 | 40.88 | 26.76 | 111.40 | 48.72 | 0.17 | 0.00 | 744.00 |
April | 74.10 | 45.66 | 28.44 | 123.18 | 43.73 | 0.00 | 0.00 | 720.00 |
May | 80.25 | 50.74 | 29.51 | 137.13 | 38.64 | 0.00 | 0.00 | 744.00 |
June | 83.13 | 53.49 | 29.64 | 141.51 | 35.92 | 0.00 | 0.00 | 720.00 |
July | 84.10 | 57.42 | 26.68 | 145.74 | 32.82 | 0.00 | 0.00 | 744.00 |
August | 83.89 | 59.06 | 24.84 | 146.07 | 36.56 | 0.00 | 0.00 | 744.00 |
September | 75.63 | 47.58 | 28.04 | 130.88 | 34.84 | 0.00 | 0.00 | 720.00 |
October | 61.28 | 39.06 | 22.23 | 105.68 | 44.79 | 0.00 | 0.00 | 744.00 |
November | 51.35 | 31.05 | 20.30 | 84.22 | 44.35 | 0.00 | 0.00 | 720.00 |
December | 45.26 | 28.41 | 16.85 | 71.17 | 46.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.61 | 43.16 | 24.44 | 113.73 | 42.08 | 20.67 | 0.00 | 8760.00 |
Minimum of Months | 45.26 | 28.41 | 16.85 | 71.17 | 32.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.10 | 59.06 | 29.64 | 146.07 | 49.48 | 14.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.43 | 29.53 | 17.90 | 75.32 | 49.09 | 6.00 | 0.00 | 744.00 |
February | 56.60 | 34.39 | 22.21 | 91.13 | 49.48 | 14.50 | 0.00 | 672.00 |
March | 67.64 | 40.88 | 26.76 | 111.40 | 48.72 | 0.17 | 0.00 | 744.00 |
April | 74.10 | 45.66 | 28.44 | 123.18 | 43.73 | 0.00 | 0.00 | 720.00 |
May | 80.25 | 50.74 | 29.51 | 137.13 | 38.64 | 0.00 | 0.00 | 744.00 |
June | 83.13 | 53.49 | 29.64 | 141.51 | 35.92 | 0.00 | 0.00 | 720.00 |
July | 84.10 | 57.42 | 26.68 | 145.74 | 32.82 | 0.00 | 0.00 | 744.00 |
August | 83.89 | 59.06 | 24.84 | 146.07 | 36.56 | 0.00 | 0.00 | 744.00 |
September | 75.63 | 47.58 | 28.04 | 130.88 | 34.84 | 0.00 | 0.00 | 720.00 |
October | 61.28 | 39.06 | 22.23 | 105.68 | 44.79 | 0.00 | 0.00 | 744.00 |
November | 51.35 | 31.05 | 20.30 | 84.22 | 44.35 | 0.00 | 0.00 | 720.00 |
December | 45.26 | 28.41 | 16.85 | 71.17 | 46.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.61 | 43.16 | 24.44 | 113.73 | 42.08 | 20.67 | 0.00 | 8760.00 |
Minimum of Months | 45.26 | 28.41 | 16.85 | 71.17 | 32.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.10 | 59.06 | 29.64 | 146.07 | 49.48 | 14.50 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100652E+09 | 35123428.30 | 65528743.33 | 0.240935E+09 | 0.224496E+09 |
February | 0.139569E+09 | 62707073.55 | 76861936.63 | 0.357044E+09 | 0.207339E+09 |
March | 0.170550E+09 | 70784918.78 | 99765187.86 | 0.454039E+09 | 0.218019E+09 |
April | 0.155443E+09 | 61829141.79 | 93614026.37 | 0.416819E+09 | 0.177072E+09 |
May | 0.152748E+09 | 54159374.21 | 98588883.39 | 0.447541E+09 | 0.152328E+09 |
June | 0.163185E+09 | 64888052.64 | 98297090.31 | 0.475839E+09 | 0.122140E+09 |
July | 0.169552E+09 | 72154968.73 | 97396560.42 | 0.527608E+09 | 0.109085E+09 |
August | 0.170520E+09 | 76071518.29 | 94448204.38 | 0.549424E+09 | 0.118901E+09 |
September | 0.193856E+09 | 87182697.29 | 0.106673E+09 | 0.596913E+09 | 0.110513E+09 |
October | 0.123734E+09 | 44014127.74 | 79719829.56 | 0.399228E+09 | 0.153458E+09 |
November | 0.115402E+09 | 46292988.10 | 69108663.62 | 0.327263E+09 | 0.165851E+09 |
December | 99654494.96 | 38183108.14 | 61471386.82 | 0.253386E+09 | 0.188017E+09 |
Annual Sum or Average | 0.175486E+10 | 0.713391E+09 | 0.104147E+10 | 0.504604E+10 | 0.194722E+10 |
Minimum of Months | 99654494.96 | 35123428.30 | 61471386.82 | 0.240935E+09 | 0.109085E+09 |
Maximum of Months | 0.193856E+09 | 87182697.29 | 0.106673E+09 | 0.596913E+09 | 0.224496E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100652E+09 | 35123428.30 | 65528743.33 | 0.240935E+09 | 0.224496E+09 |
February | 0.139569E+09 | 62707073.55 | 76861936.63 | 0.357044E+09 | 0.207339E+09 |
March | 0.170550E+09 | 70784918.78 | 99765187.86 | 0.454039E+09 | 0.218019E+09 |
April | 0.155443E+09 | 61829141.79 | 93614026.37 | 0.416819E+09 | 0.177072E+09 |
May | 0.152748E+09 | 54159374.21 | 98588883.39 | 0.447541E+09 | 0.152328E+09 |
June | 0.163185E+09 | 64888052.64 | 98297090.31 | 0.475839E+09 | 0.122140E+09 |
July | 0.169552E+09 | 72154968.73 | 97396560.42 | 0.527608E+09 | 0.109085E+09 |
August | 0.170520E+09 | 76071518.29 | 94448204.38 | 0.549424E+09 | 0.118901E+09 |
September | 0.193856E+09 | 87182697.29 | 0.106673E+09 | 0.596913E+09 | 0.110513E+09 |
October | 0.123734E+09 | 44014127.74 | 79719829.56 | 0.399228E+09 | 0.153458E+09 |
November | 0.115402E+09 | 46292988.10 | 69108663.62 | 0.327263E+09 | 0.165851E+09 |
December | 99654494.96 | 38183108.14 | 61471386.82 | 0.253386E+09 | 0.188017E+09 |
Annual Sum or Average | 0.175486E+10 | 0.713391E+09 | 0.104147E+10 | 0.504604E+10 | 0.194722E+10 |
Minimum of Months | 99654494.96 | 35123428.30 | 61471386.82 | 0.240935E+09 | 0.109085E+09 |
Maximum of Months | 0.193856E+09 | 87182697.29 | 0.106673E+09 | 0.596913E+09 | 0.224496E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33080144.57 | 0.00 | 33080144.57 | 62869103.87 | 0.136090E+09 |
February | 35695166.18 | 0.00 | 35695166.18 | 77021995.27 | 0.124081E+09 |
March | 45146086.44 | 6170.68 | 45139915.76 | 0.103962E+09 | 0.131813E+09 |
April | 47470323.51 | 774548.27 | 46695775.24 | 0.107548E+09 | 0.106586E+09 |
May | 62310203.44 | 7432260.62 | 54877942.82 | 0.171053E+09 | 88735011.84 |
June | 70703773.58 | 13300481.38 | 57403292.21 | 0.191421E+09 | 72306110.64 |
July | 66720540.30 | 10657015.94 | 56063524.36 | 0.199165E+09 | 64520153.99 |
August | 51976255.69 | 3409928.06 | 48566327.64 | 0.168240E+09 | 69105933.93 |
September | 46414507.28 | 67395.19 | 46347112.08 | 0.140244E+09 | 65033677.15 |
October | 39739363.98 | 0.00 | 39739363.98 | 0.130492E+09 | 89476617.81 |
November | 34651637.58 | 0.00 | 34651637.58 | 88710894.59 | 98598419.91 |
December | 31469428.72 | 0.00 | 31469428.72 | 65609385.88 | 0.112974E+09 |
Annual Sum or Average | 0.565377E+09 | 35647800.13 | 0.529730E+09 | 0.150634E+10 | 0.115932E+10 |
Minimum of Months | 31469428.72 | 0.00 | 31469428.72 | 62869103.87 | 64520153.99 |
Maximum of Months | 70703773.58 | 13300481.38 | 57403292.21 | 0.199165E+09 | 0.136090E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33079207.10 | 0.00 | 33079207.10 | 62867499.08 | 0.136089E+09 |
February | 35694148.56 | 0.00 | 35694148.56 | 77020057.29 | 0.124080E+09 |
March | 45144818.18 | 6170.39 | 45138647.79 | 0.103959E+09 | 0.131812E+09 |
April | 47468995.48 | 774511.97 | 46694483.51 | 0.107546E+09 | 0.106585E+09 |
May | 62308277.13 | 7431912.26 | 54876364.87 | 0.171049E+09 | 88733839.21 |
June | 70701457.27 | 13299857.96 | 57401599.31 | 0.191416E+09 | 72304935.06 |
July | 66718451.47 | 10656516.43 | 56061935.05 | 0.199161E+09 | 64519059.33 |
August | 51974856.26 | 3409768.23 | 48565088.04 | 0.168237E+09 | 69104631.42 |
September | 46413249.40 | 67392.03 | 46345857.36 | 0.140242E+09 | 65032467.00 |
October | 39738276.34 | 0.00 | 39738276.34 | 0.130490E+09 | 89475045.32 |
November | 34650652.93 | 0.00 | 34650652.93 | 88709049.41 | 98597040.30 |
December | 31468542.51 | 0.00 | 31468542.51 | 65607842.67 | 0.112972E+09 |
Annual Sum or Average | 0.565361E+09 | 35646129.27 | 0.529715E+09 | 0.150630E+10 | 0.115931E+10 |
Minimum of Months | 31468542.51 | 0.00 | 31468542.51 | 62867499.08 | 64519059.33 |
Maximum of Months | 70701457.27 | 13299857.96 | 57401599.31 | 0.199161E+09 | 0.136089E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127039E+09 | 79104360.46 | 47934532.25 | 0.201734E+09 | 0.131472E+09 |
February | 0.136931E+09 | 83205189.69 | 53726008.60 | 0.220463E+09 | 0.119708E+09 |
March | 0.181167E+09 | 0.109506E+09 | 71660748.04 | 0.298362E+09 | 0.130505E+09 |
April | 0.192071E+09 | 0.118342E+09 | 73728858.51 | 0.319276E+09 | 0.113360E+09 |
May | 0.214937E+09 | 0.135890E+09 | 79046554.26 | 0.367298E+09 | 0.103495E+09 |
June | 0.215463E+09 | 0.138636E+09 | 76826634.77 | 0.366782E+09 | 93115268.47 |
July | 0.225260E+09 | 0.153799E+09 | 71461683.67 | 0.390356E+09 | 87908242.06 |
August | 0.224703E+09 | 0.158178E+09 | 66524922.46 | 0.391226E+09 | 97914630.13 |
September | 0.196030E+09 | 0.123340E+09 | 72689363.17 | 0.339246E+09 | 90317060.41 |
October | 0.164144E+09 | 0.104609E+09 | 59534500.87 | 0.283045E+09 | 0.119972E+09 |
November | 0.133090E+09 | 80468900.21 | 52620827.09 | 0.218290E+09 | 0.114965E+09 |
December | 0.121228E+09 | 76100044.61 | 45127911.00 | 0.190621E+09 | 0.124297E+09 |
Annual Sum or Average | 0.213206E+10 | 0.136118E+10 | 0.770883E+09 | 0.358670E+10 | 0.132703E+10 |
Minimum of Months | 0.121228E+09 | 76100044.61 | 45127911.00 | 0.190621E+09 | 87908242.06 |
Maximum of Months | 0.225260E+09 | 0.158178E+09 | 79046554.26 | 0.391226E+09 | 0.131472E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127039E+09 | 79104360.46 | 47934532.25 | 0.201734E+09 | 0.131472E+09 |
February | 0.136931E+09 | 83205189.69 | 53726008.60 | 0.220463E+09 | 0.119708E+09 |
March | 0.181167E+09 | 0.109506E+09 | 71660748.04 | 0.298362E+09 | 0.130505E+09 |
April | 0.192071E+09 | 0.118342E+09 | 73728858.51 | 0.319276E+09 | 0.113360E+09 |
May | 0.214937E+09 | 0.135890E+09 | 79046554.26 | 0.367298E+09 | 0.103495E+09 |
June | 0.215463E+09 | 0.138636E+09 | 76826634.77 | 0.366782E+09 | 93115268.47 |
July | 0.225260E+09 | 0.153799E+09 | 71461683.67 | 0.390356E+09 | 87908242.06 |
August | 0.224703E+09 | 0.158178E+09 | 66524922.46 | 0.391226E+09 | 97914630.13 |
September | 0.196030E+09 | 0.123340E+09 | 72689363.17 | 0.339246E+09 | 90317060.41 |
October | 0.164144E+09 | 0.104609E+09 | 59534500.87 | 0.283045E+09 | 0.119972E+09 |
November | 0.133090E+09 | 80468900.21 | 52620827.09 | 0.218290E+09 | 0.114965E+09 |
December | 0.121228E+09 | 76100044.61 | 45127911.00 | 0.190621E+09 | 0.124297E+09 |
Annual Sum or Average | 0.213206E+10 | 0.136118E+10 | 0.770883E+09 | 0.358670E+10 | 0.132703E+10 |
Minimum of Months | 0.121228E+09 | 76100044.61 | 45127911.00 | 0.190621E+09 | 87908242.06 |
Maximum of Months | 0.225260E+09 | 0.158178E+09 | 79046554.26 | 0.391226E+09 | 0.131472E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127039E+09 | 79104360.46 | 47934532.25 | 0.201734E+09 | 0.131472E+09 |
February | 0.136931E+09 | 83205189.69 | 53726008.60 | 0.220463E+09 | 0.119708E+09 |
March | 0.181167E+09 | 0.109506E+09 | 71660748.04 | 0.298362E+09 | 0.130505E+09 |
April | 0.192071E+09 | 0.118342E+09 | 73728858.51 | 0.319276E+09 | 0.113360E+09 |
May | 0.214937E+09 | 0.135890E+09 | 79046554.26 | 0.367298E+09 | 0.103495E+09 |
June | 0.215463E+09 | 0.138636E+09 | 76826634.77 | 0.366782E+09 | 93115268.47 |
July | 0.225260E+09 | 0.153799E+09 | 71461683.67 | 0.390356E+09 | 87908242.06 |
August | 0.224703E+09 | 0.158178E+09 | 66524922.46 | 0.391226E+09 | 97914630.13 |
September | 0.196030E+09 | 0.123340E+09 | 72689363.17 | 0.339246E+09 | 90317060.41 |
October | 0.164144E+09 | 0.104609E+09 | 59534500.87 | 0.283045E+09 | 0.119972E+09 |
November | 0.133090E+09 | 80468900.21 | 52620827.09 | 0.218290E+09 | 0.114965E+09 |
December | 0.121228E+09 | 76100044.61 | 45127911.00 | 0.190621E+09 | 0.124297E+09 |
Annual Sum or Average | 0.213206E+10 | 0.136118E+10 | 0.770883E+09 | 0.358670E+10 | 0.132703E+10 |
Minimum of Months | 0.121228E+09 | 76100044.61 | 45127911.00 | 0.190621E+09 | 87908242.06 |
Maximum of Months | 0.225260E+09 | 0.158178E+09 | 79046554.26 | 0.391226E+09 | 0.131472E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127039E+09 | 79104360.46 | 47934532.25 | 0.201734E+09 | 0.131472E+09 |
February | 0.136931E+09 | 83205189.69 | 53726008.60 | 0.220463E+09 | 0.119708E+09 |
March | 0.181167E+09 | 0.109506E+09 | 71660748.04 | 0.298362E+09 | 0.130505E+09 |
April | 0.192071E+09 | 0.118342E+09 | 73728858.51 | 0.319276E+09 | 0.113360E+09 |
May | 0.214937E+09 | 0.135890E+09 | 79046554.26 | 0.367298E+09 | 0.103495E+09 |
June | 0.215463E+09 | 0.138636E+09 | 76826634.77 | 0.366782E+09 | 93115268.47 |
July | 0.225260E+09 | 0.153799E+09 | 71461683.67 | 0.390356E+09 | 87908242.06 |
August | 0.224703E+09 | 0.158178E+09 | 66524922.46 | 0.391226E+09 | 97914630.13 |
September | 0.196030E+09 | 0.123340E+09 | 72689363.17 | 0.339246E+09 | 90317060.41 |
October | 0.164144E+09 | 0.104609E+09 | 59534500.87 | 0.283045E+09 | 0.119972E+09 |
November | 0.133090E+09 | 80468900.21 | 52620827.09 | 0.218290E+09 | 0.114965E+09 |
December | 0.121228E+09 | 76100044.61 | 45127911.00 | 0.190621E+09 | 0.124297E+09 |
Annual Sum or Average | 0.213206E+10 | 0.136118E+10 | 0.770883E+09 | 0.358670E+10 | 0.132703E+10 |
Minimum of Months | 0.121228E+09 | 76100044.61 | 45127911.00 | 0.190621E+09 | 87908242.06 |
Maximum of Months | 0.225260E+09 | 0.158178E+09 | 79046554.26 | 0.391226E+09 | 0.131472E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127039E+09 | 79104360.46 | 47934532.25 | 0.201734E+09 | 0.131472E+09 |
February | 0.136931E+09 | 83205189.69 | 53726008.60 | 0.220463E+09 | 0.119708E+09 |
March | 0.181167E+09 | 0.109506E+09 | 71660748.04 | 0.298362E+09 | 0.130505E+09 |
April | 0.192071E+09 | 0.118342E+09 | 73728858.51 | 0.319276E+09 | 0.113360E+09 |
May | 0.214937E+09 | 0.135890E+09 | 79046554.26 | 0.367298E+09 | 0.103495E+09 |
June | 0.215463E+09 | 0.138636E+09 | 76826634.77 | 0.366782E+09 | 93115268.47 |
July | 0.225260E+09 | 0.153799E+09 | 71461683.67 | 0.390356E+09 | 87908242.06 |
August | 0.224703E+09 | 0.158178E+09 | 66524922.46 | 0.391226E+09 | 97914630.13 |
September | 0.196030E+09 | 0.123340E+09 | 72689363.17 | 0.339246E+09 | 90317060.41 |
October | 0.164144E+09 | 0.104609E+09 | 59534500.87 | 0.283045E+09 | 0.119972E+09 |
November | 0.133090E+09 | 80468900.21 | 52620827.09 | 0.218290E+09 | 0.114965E+09 |
December | 0.121228E+09 | 76100044.61 | 45127911.00 | 0.190621E+09 | 0.124297E+09 |
Annual Sum or Average | 0.213206E+10 | 0.136118E+10 | 0.770883E+09 | 0.358670E+10 | 0.132703E+10 |
Minimum of Months | 0.121228E+09 | 76100044.61 | 45127911.00 | 0.190621E+09 | 87908242.06 |
Maximum of Months | 0.225260E+09 | 0.158178E+09 | 79046554.26 | 0.391226E+09 | 0.131472E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127039E+09 | 79104360.46 | 47934532.25 | 0.201734E+09 | 0.131472E+09 |
February | 0.136931E+09 | 83205189.69 | 53726008.60 | 0.220463E+09 | 0.119708E+09 |
March | 0.181167E+09 | 0.109506E+09 | 71660748.04 | 0.298362E+09 | 0.130505E+09 |
April | 0.192071E+09 | 0.118342E+09 | 73728858.51 | 0.319276E+09 | 0.113360E+09 |
May | 0.214937E+09 | 0.135890E+09 | 79046554.26 | 0.367298E+09 | 0.103495E+09 |
June | 0.215463E+09 | 0.138636E+09 | 76826634.77 | 0.366782E+09 | 93115268.47 |
July | 0.225260E+09 | 0.153799E+09 | 71461683.67 | 0.390356E+09 | 87908242.06 |
August | 0.224703E+09 | 0.158178E+09 | 66524922.46 | 0.391226E+09 | 97914630.13 |
September | 0.196030E+09 | 0.123340E+09 | 72689363.17 | 0.339246E+09 | 90317060.41 |
October | 0.164144E+09 | 0.104609E+09 | 59534500.87 | 0.283045E+09 | 0.119972E+09 |
November | 0.133090E+09 | 80468900.21 | 52620827.09 | 0.218290E+09 | 0.114965E+09 |
December | 0.121228E+09 | 76100044.61 | 45127911.00 | 0.190621E+09 | 0.124297E+09 |
Annual Sum or Average | 0.213206E+10 | 0.136118E+10 | 0.770883E+09 | 0.358670E+10 | 0.132703E+10 |
Minimum of Months | 0.121228E+09 | 76100044.61 | 45127911.00 | 0.190621E+09 | 87908242.06 |
Maximum of Months | 0.225260E+09 | 0.158178E+09 | 79046554.26 | 0.391226E+09 | 0.131472E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127039E+09 | 79104360.46 | 47934532.25 | 0.201734E+09 | 0.131472E+09 |
February | 0.136931E+09 | 83205189.69 | 53726008.60 | 0.220463E+09 | 0.119708E+09 |
March | 0.181167E+09 | 0.109506E+09 | 71660748.04 | 0.298362E+09 | 0.130505E+09 |
April | 0.192071E+09 | 0.118342E+09 | 73728858.51 | 0.319276E+09 | 0.113360E+09 |
May | 0.214937E+09 | 0.135890E+09 | 79046554.26 | 0.367298E+09 | 0.103495E+09 |
June | 0.215463E+09 | 0.138636E+09 | 76826634.77 | 0.366782E+09 | 93115268.47 |
July | 0.225260E+09 | 0.153799E+09 | 71461683.67 | 0.390356E+09 | 87908242.06 |
August | 0.224703E+09 | 0.158178E+09 | 66524922.46 | 0.391226E+09 | 97914630.13 |
September | 0.196030E+09 | 0.123340E+09 | 72689363.17 | 0.339246E+09 | 90317060.41 |
October | 0.164144E+09 | 0.104609E+09 | 59534500.87 | 0.283045E+09 | 0.119972E+09 |
November | 0.133090E+09 | 80468900.21 | 52620827.09 | 0.218290E+09 | 0.114965E+09 |
December | 0.121228E+09 | 76100044.61 | 45127911.00 | 0.190621E+09 | 0.124297E+09 |
Annual Sum or Average | 0.213206E+10 | 0.136118E+10 | 0.770883E+09 | 0.358670E+10 | 0.132703E+10 |
Minimum of Months | 0.121228E+09 | 76100044.61 | 45127911.00 | 0.190621E+09 | 87908242.06 |
Maximum of Months | 0.225260E+09 | 0.158178E+09 | 79046554.26 | 0.391226E+09 | 0.131472E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127039E+09 | 79104360.46 | 47934532.25 | 0.201734E+09 | 0.131472E+09 |
February | 0.136931E+09 | 83205189.69 | 53726008.60 | 0.220463E+09 | 0.119708E+09 |
March | 0.181167E+09 | 0.109506E+09 | 71660748.04 | 0.298362E+09 | 0.130505E+09 |
April | 0.192071E+09 | 0.118342E+09 | 73728858.51 | 0.319276E+09 | 0.113360E+09 |
May | 0.214937E+09 | 0.135890E+09 | 79046554.26 | 0.367298E+09 | 0.103495E+09 |
June | 0.215463E+09 | 0.138636E+09 | 76826634.77 | 0.366782E+09 | 93115268.47 |
July | 0.225260E+09 | 0.153799E+09 | 71461683.67 | 0.390356E+09 | 87908242.06 |
August | 0.224703E+09 | 0.158178E+09 | 66524922.46 | 0.391226E+09 | 97914630.13 |
September | 0.196030E+09 | 0.123340E+09 | 72689363.17 | 0.339246E+09 | 90317060.41 |
October | 0.164144E+09 | 0.104609E+09 | 59534500.87 | 0.283045E+09 | 0.119972E+09 |
November | 0.133090E+09 | 80468900.21 | 52620827.09 | 0.218290E+09 | 0.114965E+09 |
December | 0.121228E+09 | 76100044.61 | 45127911.00 | 0.190621E+09 | 0.124297E+09 |
Annual Sum or Average | 0.213206E+10 | 0.136118E+10 | 0.770883E+09 | 0.358670E+10 | 0.132703E+10 |
Minimum of Months | 0.121228E+09 | 76100044.61 | 45127911.00 | 0.190621E+09 | 87908242.06 |
Maximum of Months | 0.225260E+09 | 0.158178E+09 | 79046554.26 | 0.391226E+09 | 0.131472E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127039E+09 | 79104360.46 | 47934532.25 | 0.201734E+09 | 0.131472E+09 |
February | 0.136931E+09 | 83205189.69 | 53726008.60 | 0.220463E+09 | 0.119708E+09 |
March | 0.181167E+09 | 0.109506E+09 | 71660748.04 | 0.298362E+09 | 0.130505E+09 |
April | 0.192071E+09 | 0.118342E+09 | 73728858.51 | 0.319276E+09 | 0.113360E+09 |
May | 0.214937E+09 | 0.135890E+09 | 79046554.26 | 0.367298E+09 | 0.103495E+09 |
June | 0.215463E+09 | 0.138636E+09 | 76826634.77 | 0.366782E+09 | 93115268.47 |
July | 0.225260E+09 | 0.153799E+09 | 71461683.67 | 0.390356E+09 | 87908242.06 |
August | 0.224703E+09 | 0.158178E+09 | 66524922.46 | 0.391226E+09 | 97914630.13 |
September | 0.196030E+09 | 0.123340E+09 | 72689363.17 | 0.339246E+09 | 90317060.41 |
October | 0.164144E+09 | 0.104609E+09 | 59534500.87 | 0.283045E+09 | 0.119972E+09 |
November | 0.133090E+09 | 80468900.21 | 52620827.09 | 0.218290E+09 | 0.114965E+09 |
December | 0.121228E+09 | 76100044.61 | 45127911.00 | 0.190621E+09 | 0.124297E+09 |
Annual Sum or Average | 0.213206E+10 | 0.136118E+10 | 0.770883E+09 | 0.358670E+10 | 0.132703E+10 |
Minimum of Months | 0.121228E+09 | 76100044.61 | 45127911.00 | 0.190621E+09 | 87908242.06 |
Maximum of Months | 0.225260E+09 | 0.158178E+09 | 79046554.26 | 0.391226E+09 | 0.131472E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127039E+09 | 79104360.46 | 47934532.25 | 0.201734E+09 | 0.131472E+09 |
February | 0.136931E+09 | 83205189.69 | 53726008.60 | 0.220463E+09 | 0.119708E+09 |
March | 0.181167E+09 | 0.109506E+09 | 71660748.04 | 0.298362E+09 | 0.130505E+09 |
April | 0.192071E+09 | 0.118342E+09 | 73728858.51 | 0.319276E+09 | 0.113360E+09 |
May | 0.214937E+09 | 0.135890E+09 | 79046554.26 | 0.367298E+09 | 0.103495E+09 |
June | 0.215463E+09 | 0.138636E+09 | 76826634.77 | 0.366782E+09 | 93115268.47 |
July | 0.225260E+09 | 0.153799E+09 | 71461683.67 | 0.390356E+09 | 87908242.06 |
August | 0.224703E+09 | 0.158178E+09 | 66524922.46 | 0.391226E+09 | 97914630.13 |
September | 0.196030E+09 | 0.123340E+09 | 72689363.17 | 0.339246E+09 | 90317060.41 |
October | 0.164144E+09 | 0.104609E+09 | 59534500.87 | 0.283045E+09 | 0.119972E+09 |
November | 0.133090E+09 | 80468900.21 | 52620827.09 | 0.218290E+09 | 0.114965E+09 |
December | 0.121228E+09 | 76100044.61 | 45127911.00 | 0.190621E+09 | 0.124297E+09 |
Annual Sum or Average | 0.213206E+10 | 0.136118E+10 | 0.770883E+09 | 0.358670E+10 | 0.132703E+10 |
Minimum of Months | 0.121228E+09 | 76100044.61 | 45127911.00 | 0.190621E+09 | 87908242.06 |
Maximum of Months | 0.225260E+09 | 0.158178E+09 | 79046554.26 | 0.391226E+09 | 0.131472E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 225.43 | 267.83 | 99.86 | 26.23 | 73.63 | 0.00 | 0.00 |
February | 356.70 | 271.84 | 144.89 | 51.84 | 93.05 | 0.00 | 0.00 |
March | 414.73 | 259.29 | 161.06 | 52.86 | 108.20 | 0.00 | 0.00 |
April | 401.93 | 216.20 | 156.57 | 48.31 | 108.26 | 0.00 | 0.00 |
May | 458.78 | 176.87 | 160.59 | 45.99 | 114.60 | 0.00 | 0.00 |
June | 513.36 | 148.54 | 180.47 | 60.33 | 120.14 | 0.00 | 0.00 |
July | 541.42 | 128.36 | 176.43 | 61.84 | 114.59 | 0.00 | 0.00 |
August | 534.53 | 139.03 | 166.14 | 59.35 | 106.79 | 0.00 | 0.00 |
September | 568.28 | 134.94 | 185.39 | 67.32 | 118.07 | 0.00 | 0.00 |
October | 395.34 | 181.19 | 122.07 | 32.87 | 89.20 | 0.00 | 0.00 |
November | 320.16 | 203.24 | 115.78 | 35.72 | 80.06 | 0.00 | 0.00 |
December | 237.11 | 223.67 | 97.91 | 28.51 | 69.40 | 0.00 | 0.00 |
Annual Sum or Average | 414.05 | 195.51 | 147.15 | 47.50 | 99.64 | 0.00 | 0.00 |
Minimum of Months | 225.43 | 128.36 | 97.91 | 26.23 | 69.40 | 0.00 | 0.00 |
Maximum of Months | 568.28 | 271.84 | 185.39 | 67.32 | 120.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 753.18 | 490.86 | 474.31 | 295.34 | 178.97 | 0.00 | 0.00 |
February | 911.30 | 494.82 | 566.02 | 343.94 | 222.08 | 0.00 | 0.00 |
March | 1113.95 | 487.25 | 676.40 | 408.85 | 267.55 | 0.00 | 0.00 |
April | 1231.76 | 437.35 | 741.02 | 456.57 | 284.45 | 0.00 | 0.00 |
May | 1371.33 | 386.41 | 802.48 | 507.36 | 295.13 | 0.00 | 0.00 |
June | 1415.05 | 359.24 | 831.26 | 534.86 | 296.40 | 0.00 | 0.00 |
July | 1457.42 | 328.21 | 841.03 | 574.22 | 266.81 | 0.00 | 0.00 |
August | 1460.66 | 365.57 | 838.94 | 590.57 | 248.38 | 0.00 | 0.00 |
September | 1308.82 | 348.44 | 756.29 | 475.85 | 280.44 | 0.00 | 0.00 |
October | 1056.76 | 447.92 | 612.84 | 390.57 | 222.28 | 0.00 | 0.00 |
November | 842.16 | 443.54 | 513.46 | 310.45 | 203.01 | 0.00 | 0.00 |
December | 711.69 | 464.07 | 452.61 | 284.13 | 168.49 | 0.00 | 0.00 |
Annual Sum or Average | 1137.33 | 420.80 | 676.07 | 431.63 | 244.45 | 0.00 | 0.00 |
Minimum of Months | 711.69 | 328.21 | 452.61 | 284.13 | 168.49 | 0.00 | 0.00 |
Maximum of Months | 1460.66 | 494.82 | 841.03 | 590.57 | 296.40 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.603791E+09 | 0.717355E+09 | 0.267464E+09 | 70246856.60 | 0.197217E+09 | 0.00 | 0.00 |
February | 0.862918E+09 | 0.657628E+09 | 0.350527E+09 | 0.125414E+09 | 0.225113E+09 | 0.00 | 0.00 |
March | 0.111081E+10 | 0.694473E+09 | 0.431391E+09 | 0.141582E+09 | 0.289809E+09 | 0.00 | 0.00 |
April | 0.104181E+10 | 0.560396E+09 | 0.405826E+09 | 0.125207E+09 | 0.280618E+09 | 0.00 | 0.00 |
May | 0.122879E+10 | 0.473731E+09 | 0.430115E+09 | 0.123183E+09 | 0.306932E+09 | 0.00 | 0.00 |
June | 0.133063E+10 | 0.385007E+09 | 0.467776E+09 | 0.156376E+09 | 0.311399E+09 | 0.00 | 0.00 |
July | 0.145013E+10 | 0.343797E+09 | 0.472542E+09 | 0.165623E+09 | 0.306919E+09 | 0.00 | 0.00 |
August | 0.143169E+10 | 0.372377E+09 | 0.444991E+09 | 0.158963E+09 | 0.286028E+09 | 0.00 | 0.00 |
September | 0.147299E+10 | 0.349766E+09 | 0.480539E+09 | 0.174500E+09 | 0.306039E+09 | 0.00 | 0.00 |
October | 0.105888E+10 | 0.485312E+09 | 0.326946E+09 | 88028255.48 | 0.238917E+09 | 0.00 | 0.00 |
November | 0.829856E+09 | 0.526809E+09 | 0.300106E+09 | 92585976.19 | 0.207520E+09 | 0.00 | 0.00 |
December | 0.635080E+09 | 0.599070E+09 | 0.262247E+09 | 76366216.28 | 0.185881E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.130574E+11 | 0.616572E+10 | 0.464047E+10 | 0.149808E+10 | 0.314239E+10 | 0.00 | 0.00 |
Minimum of Months | 0.603791E+09 | 0.343797E+09 | 0.262247E+09 | 70246856.60 | 0.185881E+09 | 0.00 | 0.00 |
Maximum of Months | 0.147299E+10 | 0.717355E+09 | 0.480539E+09 | 0.174500E+09 | 0.311399E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.201732E+10 | 0.131472E+10 | 0.127039E+10 | 0.791044E+09 | 0.479345E+09 | 0.00 | 0.00 |
February | 0.220461E+10 | 0.119708E+10 | 0.136931E+10 | 0.832052E+09 | 0.537260E+09 | 0.00 | 0.00 |
March | 0.298362E+10 | 0.130505E+10 | 0.181167E+10 | 0.109506E+10 | 0.716607E+09 | 0.00 | 0.00 |
April | 0.319273E+10 | 0.113360E+10 | 0.192071E+10 | 0.118342E+10 | 0.737289E+09 | 0.00 | 0.00 |
May | 0.367298E+10 | 0.103495E+10 | 0.214937E+10 | 0.135890E+10 | 0.790466E+09 | 0.00 | 0.00 |
June | 0.366781E+10 | 0.931153E+09 | 0.215463E+10 | 0.138636E+10 | 0.768266E+09 | 0.00 | 0.00 |
July | 0.390356E+10 | 0.879077E+09 | 0.225260E+10 | 0.153799E+10 | 0.714617E+09 | 0.00 | 0.00 |
August | 0.391223E+10 | 0.979138E+09 | 0.224703E+10 | 0.158178E+10 | 0.665249E+09 | 0.00 | 0.00 |
September | 0.339245E+10 | 0.903167E+09 | 0.196030E+10 | 0.123340E+10 | 0.726894E+09 | 0.00 | 0.00 |
October | 0.283043E+10 | 0.119972E+10 | 0.164144E+10 | 0.104609E+10 | 0.595345E+09 | 0.00 | 0.00 |
November | 0.218288E+10 | 0.114965E+10 | 0.133090E+10 | 0.804689E+09 | 0.526208E+09 | 0.00 | 0.00 |
December | 0.190620E+10 | 0.124297E+10 | 0.121228E+10 | 0.761000E+09 | 0.451279E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.358668E+11 | 0.132703E+11 | 0.213206E+11 | 0.136118E+11 | 0.770883E+10 | 0.00 | 0.00 |
Minimum of Months | 0.190620E+10 | 0.879077E+09 | 0.121228E+10 | 0.761000E+09 | 0.451279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.391223E+10 | 0.131472E+10 | 0.225260E+10 | 0.158178E+10 | 0.790466E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 22.49 | 18.25 | 15.90 | 4.15 | 13.31 | 59.87 | 181.51 | 0.00 |
February | 22.80 | 19.74 | 18.20 | 3.70 | 14.21 | 74.30 | 182.84 | 0.03 |
March | 23.17 | 18.99 | 16.85 | 4.23 | 14.23 | 89.51 | 186.76 | 0.02 |
April | 23.76 | 19.01 | 16.50 | 4.83 | 14.94 | 95.22 | 199.35 | 0.00 |
May | 25.23 | 20.49 | 18.23 | 4.38 | 17.08 | 98.73 | 213.00 | 0.00 |
June | 25.87 | 20.89 | 18.70 | 5.87 | 17.20 | 99.16 | 227.55 | 0.00 |
July | 26.90 | 21.77 | 19.49 | 5.98 | 18.80 | 89.26 | 241.04 | 0.00 |
August | 27.06 | 21.88 | 19.61 | 5.21 | 18.26 | 83.09 | 253.22 | 0.00 |
September | 26.87 | 22.30 | 20.37 | 5.44 | 18.71 | 93.82 | 214.78 | 0.00 |
October | 26.22 | 21.67 | 19.68 | 3.78 | 17.26 | 74.41 | 199.79 | 0.00 |
November | 24.76 | 20.57 | 18.62 | 5.17 | 16.20 | 67.97 | 175.93 | 0.00 |
December | 23.69 | 19.64 | 17.67 | 4.42 | 14.96 | 56.37 | 177.80 | 0.00 |
Annual Sum or Average | 24.91 | 20.44 | 18.32 | 4.77 | 16.27 | 81.79 | 204.64 | 0.00 |
Minimum of Months | 22.49 | 18.25 | 15.90 | 3.70 | 13.31 | 56.37 | 175.93 | 0.00 |
Maximum of Months | 27.06 | 22.30 | 20.37 | 5.98 | 18.80 | 99.16 | 253.22 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.40 | 03-JAN-12:00 | 22.05 | 18.90 | 3.60 | 19.35 | 145.50 | 575.00 |
February | 28.90 | 19-FEB-10:00 | 22.34 | 19.40 | 3.10 | 18.28 | 204.00 | 595.50 |
March | 30.00 | 29-MAR-12:00 | 20.05 | 15.00 | 6.70 | 20.22 | 350.50 | 543.50 |
April | 30.00 | 09-APR-13:00 | 20.06 | 15.00 | 7.20 | 17.39 | 126.00 | 778.50 |
May | 31.10 | 17-MAY-13:20 | 21.31 | 16.70 | 7.87 | 22.12 | 283.17 | 716.50 |
June | 30.60 | 26-JUN-13:00 | 21.72 | 17.80 | 6.70 | 20.40 | 162.00 | 756.50 |
July | 32.20 | 09-JUL-11:00 | 23.42 | 20.00 | 6.20 | 23.49 | 235.00 | 733.00 |
August | 32.80 | 11-AUG-13:00 | 23.28 | 19.40 | 6.20 | 23.99 | 228.00 | 563.00 |
September | 33.30 | 02-SEP-12:00 | 23.47 | 19.40 | 5.70 | 23.32 | 185.00 | 789.00 |
October | 33.30 | 01-OCT-12:00 | 23.04 | 18.90 | 6.20 | 23.15 | 143.50 | 854.50 |
November | 30.60 | 03-NOV-12:00 | 22.49 | 18.90 | 7.70 | 20.57 | 148.00 | 798.50 |
December | 30.60 | 13-DEC-13:00 | 22.11 | 18.30 | 5.70 | 18.64 | 59.00 | 832.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 20.05 | 15.00 | 3.10 | 17.39 | 59.00 | 543.50 | |
Maximum of Months | 33.30 | 23.47 | 20.00 | 7.87 | 23.99 | 350.50 | 854.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.20 | 07-JAN-06:00 | 15.82 | 15.00 | 1.50 | 3.89 | 0.00 | 0.00 |
February | 13.30 | 12-FEB-06:00 | 12.64 | 12.20 | 3.10 | 0.73 | 0.00 | 0.00 |
March | 15.00 | 08-MAR-03:00 | 13.29 | 12.20 | 0.00 | 1.16 | 0.00 | 0.00 |
April | 17.80 | 22-APR-02:00 | 16.39 | 15.60 | 0.00 | 6.75 | 0.00 | 0.00 |
May | 18.90 | 23-MAY-05:00 | 17.45 | 16.70 | 2.10 | 9.33 | 110.00 | 159.50 |
June | 21.10 | 06-JUN-04:00 | 19.20 | 18.30 | 2.60 | 9.52 | 0.00 | 0.00 |
July | 22.20 | 09-JUL-03:00 | 20.00 | 18.90 | 1.50 | 11.84 | 0.00 | 0.00 |
August | 21.10 | 18-AUG-05:00 | 19.93 | 19.40 | 2.10 | 8.54 | 0.00 | 0.00 |
September | 22.20 | 19-SEP-04:00 | 20.25 | 19.40 | 2.60 | 11.84 | 0.00 | 0.00 |
October | 19.40 | 19-OCT-05:00 | 17.58 | 16.70 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 16.10 | 27-NOV-06:00 | 15.39 | 15.00 | 2.60 | 5.74 | 50.00 | 566.00 |
December | 16.70 | 26-DEC-01:00 | 15.01 | 13.90 | 2.60 | 4.31 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 12.64 | 12.20 | 0.00 | 0.73 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 20.25 | 19.40 | 3.10 | 11.84 | 110.00 | 566.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.03 | 01-JAN-15:00 | 27.80 | 21.10 | 4.10 | 20.92 | 91.00 | 199.00 |
February | 24.57 | 18-FEB-13:00 | 27.80 | 23.30 | 4.10 | 21.44 | 268.00 | 307.00 |
March | 23.81 | 13-MAR-12:00 | 27.80 | 22.20 | 5.70 | 22.47 | 468.50 | 259.00 |
April | 22.82 | 24-APR-11:00 | 28.30 | 20.60 | 4.60 | 19.87 | 357.00 | 446.00 |
May | 23.35 | 08-MAY-15:00 | 28.90 | 21.10 | 6.20 | 22.13 | 182.00 | 323.50 |
June | 23.02 | 20-JUN-13:00 | 28.90 | 20.60 | 7.70 | 21.96 | 370.50 | 346.50 |
July | 24.68 | 20-JUL-13:00 | 26.70 | 23.90 | 8.20 | 25.33 | 309.00 | 14.00 |
August | 25.47 | 19-AUG-14:00 | 31.70 | 23.30 | 5.20 | 25.33 | 229.00 | 409.00 |
September | 25.16 | 23-SEP-14:00 | 27.20 | 24.40 | 4.10 | 23.82 | 288.00 | 450.00 |
October | 24.72 | 15-OCT-13:00 | 31.70 | 22.20 | 5.20 | 22.98 | 151.50 | 527.00 |
November | 23.46 | 02-NOV-09:00 | 29.40 | 21.10 | 6.20 | 20.57 | 236.50 | 546.50 |
December | 23.69 | 03-DEC-10:00 | 26.10 | 22.80 | 6.70 | 24.50 | 251.50 | 3.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.82 | 26.10 | 20.60 | 4.10 | 19.87 | 91.00 | 3.00 | |
Maximum of Months | 25.47 | 31.70 | 24.40 | 8.20 | 25.33 | 468.50 | 546.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 01-JAN-15:00 | 27.80 | 23.03 | 4.10 | 20.92 | 91.00 | 199.00 |
February | 23.30 | 16-FEB-17:00 | 24.40 | 23.65 | 3.10 | 22.98 | 29.50 | 4.00 |
March | 22.20 | 13-MAR-10:00 | 27.20 | 23.57 | 4.60 | 21.78 | 336.00 | 148.00 |
April | 21.10 | 24-APR-23:00 | 22.80 | 21.58 | 1.50 | 18.82 | 0.00 | 0.00 |
May | 22.20 | 09-MAY-23:00 | 24.40 | 22.88 | 1.50 | 22.64 | 0.00 | 0.00 |
June | 20.80 | 09-JUN-00:10 | 22.15 | 21.03 | 3.78 | 18.14 | 0.00 | 0.00 |
July | 23.90 | 20-JUL-13:00 | 26.70 | 24.68 | 8.20 | 25.33 | 309.00 | 14.00 |
August | 23.30 | 19-AUG-14:00 | 31.70 | 25.47 | 5.20 | 25.33 | 229.00 | 409.00 |
September | 24.40 | 23-SEP-14:00 | 27.20 | 25.16 | 4.10 | 23.82 | 288.00 | 450.00 |
October | 22.80 | 24-OCT-12:00 | 26.10 | 23.69 | 4.10 | 19.70 | 259.00 | 474.50 |
November | 21.70 | 29-NOV-17:00 | 26.10 | 22.98 | 3.10 | 22.13 | 0.00 | 0.00 |
December | 22.80 | 03-DEC-10:00 | 26.10 | 23.69 | 6.70 | 24.50 | 251.50 | 3.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.80 | 22.15 | 21.03 | 1.50 | 18.14 | 0.00 | 0.00 | |
Maximum of Months | 24.40 | 31.70 | 25.47 | 8.20 | 25.33 | 336.00 | 474.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 26.59 | 31.34 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 26.78 | 37.09 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 27.35 | 43.34 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 28.17 | 47.38 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.01 | 50.82 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.64 | 52.70 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.90 | 53.08 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.71 | 53.00 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.13 | 48.47 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.31 | 39.62 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.47 | 33.78 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 26.84 | 30.10 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.25 | 43.42 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 26.59 | 30.10 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.90 | 53.08 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.650089E+09 | -578585207.4 | 0.00 | 0.00 | 744.00 | 0.00 | -71503750.9 | 58.99 | 0.00 | 0.00 |
February | 0.592712E+09 | -528528574.7 | 0.00 | 0.00 | 672.00 | 0.00 | -64183581.1 | 58.99 | 0.00 | 0.00 |
March | 0.677921E+09 | -606833576.8 | 0.00 | 0.00 | 744.00 | 0.00 | -71087815.0 | 58.99 | 0.00 | 0.00 |
April | 0.617704E+09 | -549199162.8 | 0.00 | 0.00 | 720.00 | 0.00 | -68504477.2 | 58.99 | 0.00 | 0.00 |
May | 0.625742E+09 | -555606099.9 | 0.00 | 0.00 | 744.00 | 0.00 | -70136018.1 | 58.99 | 0.00 | 0.00 |
June | 0.609969E+09 | -542159318.8 | 0.00 | 0.00 | 720.00 | 0.00 | -67810041.1 | 58.99 | 0.00 | 0.00 |
July | 0.588775E+09 | -519423338.3 | 0.00 | 0.00 | 744.00 | 0.00 | -69351325.7 | 58.99 | 0.00 | 0.00 |
August | 0.631263E+09 | -561516627.7 | 0.00 | 0.00 | 744.00 | 0.00 | -69746209.7 | 58.98 | 0.00 | 0.00 |
September | 0.599417E+09 | -532311602.9 | 0.00 | 0.00 | 720.00 | 0.00 | -67105454.8 | 58.99 | 0.00 | 0.00 |
October | 0.617950E+09 | -548228841.2 | 0.00 | 0.00 | 744.00 | 0.00 | -69721384.1 | 58.99 | 0.00 | 0.00 |
November | 0.608754E+09 | -540721848.0 | 0.00 | 0.00 | 720.00 | 0.00 | -68031916.1 | 58.99 | 0.00 | 0.00 |
December | 0.644897E+09 | -574015982.3 | 0.00 | 0.00 | 744.00 | 0.00 | -70881167.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.746519E+10 | -.663713E+10 | 8760.00 | -828063141.5 | 58.99 | |||||
Minimum of Months | 0.588775E+09 | -606833576.8 | 0.00 | 0.00 | 672.00 | 0.00 | -71503750.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.677921E+09 | -519423338.3 | 0.00 | 0.00 | 744.00 | 0.00 | -64183581.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 326.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 285.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 336.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 360.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 384.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 392.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 398.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 382.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 346.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 316.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 318.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4207.17 | ||||||||||
Minimum of Months | 285.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 398.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.918178E+10 | 0.724158E+10 | 27165.88 | 02-JAN-06:01 | 16555.48 | 0.00 |
February | 0.00 | 0.00 | 0.993292E+10 | 0.728100E+10 | 28913.19 | 18-FEB-06:01 | 13949.18 | 0.00 |
March | 0.00 | 0.00 | 0.113568E+11 | 0.877857E+10 | 27643.69 | 13-MAR-05:01 | 16225.55 | 0.00 |
April | 0.00 | 0.00 | 0.107434E+11 | 0.846758E+10 | 26505.03 | 24-APR-05:01 | 17453.12 | 0.00 |
May | 0.00 | 0.00 | 0.131819E+11 | 0.101327E+11 | 27530.05 | 15-MAY-05:01 | 16411.47 | 0.00 |
June | 0.00 | 0.00 | 0.138986E+11 | 0.104818E+11 | 27016.98 | 14-JUN-05:01 | 17164.02 | 0.00 |
July | 0.00 | 0.00 | 0.146568E+11 | 0.109312E+11 | 28040.48 | 21-JUL-05:01 | 15975.60 | 0.00 |
August | 0.00 | 0.00 | 0.157477E+11 | 0.118290E+11 | 27521.14 | 02-AUG-05:01 | 16530.50 | 0.00 |
September | 0.00 | 0.00 | 0.148366E+11 | 0.108661E+11 | 28338.62 | 16-SEP-05:01 | 15623.10 | 0.00 |
October | 0.00 | 0.00 | 0.136876E+11 | 0.101956E+11 | 27926.60 | 10-OCT-05:01 | 16277.64 | 0.00 |
November | 0.00 | 0.00 | 0.119549E+11 | 0.887914E+10 | 27684.87 | 06-NOV-06:01 | 16985.24 | 0.00 |
December | 0.00 | 0.00 | 0.108215E+11 | 0.817906E+10 | 27010.84 | 02-DEC-06:01 | 16950.37 | 0.00 |
Annual Sum or Average | 0.150001E+12 | 0.113263E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.918178E+10 | 0.724158E+10 | 26505.03 | 13949.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.157477E+11 | 0.118290E+11 | 28913.19 | 17453.12 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.128836E+11 | 0.949179E+10 | 68208.32 | 01-JAN-13:43 | 45146.21 | 0.00 |
February | 0.00 | 0.00 | 0.165339E+11 | 0.111541E+11 | 70802.97 | 19-FEB-15:43 | 43465.77 | 0.00 |
March | 0.00 | 0.00 | 0.198630E+11 | 0.143853E+11 | 71093.16 | 12-MAR-13:23 | 42441.11 | 0.00 |
April | 0.00 | 0.00 | 0.194666E+11 | 0.144101E+11 | 68046.28 | 24-APR-17:10 | 46103.79 | 0.00 |
May | 0.00 | 0.00 | 0.293917E+11 | 0.211163E+11 | 70604.33 | 14-MAY-13:03 | 43536.75 | 0.00 |
June | 0.00 | 0.00 | 0.321494E+11 | 0.224873E+11 | 68826.03 | 25-JUN-10:13 | 44859.86 | 0.00 |
July | 0.00 | 0.00 | 0.398056E+11 | 0.273752E+11 | 74366.65 | 10-JUL-05:01 | 39410.84 | 0.00 |
August | 0.00 | 0.00 | 0.417904E+11 | 0.291528E+11 | 70696.59 | 01-AUG-17:43 | 42393.68 | 0.00 |
September | 0.00 | 0.00 | 0.414510E+11 | 0.276659E+11 | 72818.30 | 15-SEP-17:06 | 40774.94 | 0.00 |
October | 0.00 | 0.00 | 0.343961E+11 | 0.239360E+11 | 70197.40 | 22-OCT-14:33 | 43229.07 | 0.00 |
November | 0.00 | 0.00 | 0.244956E+11 | 0.168377E+11 | 69321.26 | 05-NOV-17:03 | 44215.48 | 0.00 |
December | 0.00 | 0.00 | 0.184864E+11 | 0.128497E+11 | 68502.18 | 10-DEC-12:03 | 44961.12 | 0.00 |
Annual Sum or Average | 0.330713E+12 | 0.230862E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.128836E+11 | 0.949179E+10 | 68046.28 | 39410.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.417904E+11 | 0.291528E+11 | 74366.65 | 46103.79 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.131742E+10 | 0.36 | 1307.24 | 03-JAN-07:10 | 0.92 |
February | 0.121718E+10 | 0.37 | 1307.24 | 01-FEB-07:20 | 0.93 |
March | 0.142782E+10 | 0.40 | 1307.24 | 01-MAR-08:00 | 0.92 |
April | 0.132333E+10 | 0.38 | 1307.24 | 01-APR-11:00 | 0.93 |
May | 0.138732E+10 | 0.39 | 1307.24 | 01-MAY-09:00 | 0.93 |
June | 0.139277E+10 | 0.40 | 1307.24 | 06-JUN-09:27 | 0.93 |
July | 0.135204E+10 | 0.39 | 1307.24 | 05-JUL-16:20 | 0.92 |
August | 0.145510E+10 | 0.41 | 1307.24 | 05-AUG-07:50 | 0.93 |
September | 0.135644E+10 | 0.41 | 1307.24 | 01-SEP-16:30 | 0.92 |
October | 0.134138E+10 | 0.38 | 1307.24 | 02-OCT-12:00 | 0.92 |
November | 0.128022E+10 | 0.37 | 1307.24 | 08-NOV-17:50 | 0.93 |
December | 0.132473E+10 | 0.37 | 1307.24 | 04-DEC-17:40 | 0.93 |
Annual Sum or Average | 0.161758E+11 | 0.39 | |||
Minimum of Months | 0.121718E+10 | 0.36 | 1307.24 | 0.92 | |
Maximum of Months | 0.145510E+10 | 0.41 | 1307.24 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.268777E+10 | 0.35 | 2674.28 | 02-JAN-16:10 | 0.89 |
February | 0.250657E+10 | 0.37 | 2674.28 | 01-FEB-12:20 | 0.89 |
March | 0.295507E+10 | 0.40 | 2674.28 | 02-MAR-13:50 | 0.89 |
April | 0.273944E+10 | 0.39 | 2674.28 | 01-APR-13:30 | 0.89 |
May | 0.295606E+10 | 0.44 | 2674.28 | 03-MAY-07:10 | 0.88 |
June | 0.298269E+10 | 0.46 | 2674.28 | 01-JUN-14:30 | 0.89 |
July | 0.307481E+10 | 0.51 | 2674.28 | 01-JUL-07:55 | 0.89 |
August | 0.324837E+10 | 0.53 | 2674.28 | 01-AUG-07:30 | 0.88 |
September | 0.314456E+10 | 0.56 | 2674.28 | 01-SEP-06:23 | 0.88 |
October | 0.296357E+10 | 0.47 | 2674.28 | 04-OCT-09:00 | 0.89 |
November | 0.268214E+10 | 0.39 | 2674.28 | 06-NOV-07:10 | 0.88 |
December | 0.270200E+10 | 0.36 | 2674.28 | 01-DEC-10:25 | 0.89 |
Annual Sum or Average | 0.346430E+11 | 0.44 | |||
Minimum of Months | 0.250657E+10 | 0.35 | 2674.28 | 0.88 | |
Maximum of Months | 0.324837E+10 | 0.56 | 2674.28 | 0.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.81 | 0.00 |
February | 1.49 | 0.06 |
March | 2.87 | 0.08 |
April | 2.74 | 0.00 |
May | 3.28 | 0.01 |
June | 3.40 | 0.02 |
July | 3.15 | 0.00 |
August | 3.74 | 0.00 |
September | 3.30 | 0.01 |
October | 3.65 | 0.00 |
November | 1.43 | 0.02 |
December | 1.97 | 0.03 |
Annual Sum or Average | 32.82 | 0.02 |
Minimum of Months | 1.43 | 0.00 |
Maximum of Months | 3.74 | 0.08 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 1.03 | 0.00 |
June | 0.17 | 0.00 |
July | 1.50 | 0.00 |
August | 1.83 | 0.00 |
September | 0.58 | 0.00 |
October | 0.75 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 5.86 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.83 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.374687E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.381553E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.443277E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.417518E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.492483E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.509648E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.530720E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.574191E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.532682E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.505115E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.445571E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.418316E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.562576E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.374687E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.574191E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.640001E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.718783E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.865707E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.835377E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.114902E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.122392E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.146565E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.154940E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.150929E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.130397E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.972290E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.797933E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.130313E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.640001E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.154940E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.131742E+10 | 0.918178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121718E+10 | 0.993292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142782E+10 | 0.113568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132333E+10 | 0.107434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138732E+10 | 0.131819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139277E+10 | 0.138986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135204E+10 | 0.146568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145510E+10 | 0.157477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135644E+10 | 0.148366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134138E+10 | 0.136876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128022E+10 | 0.119549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132473E+10 | 0.108215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161758E+11 | 0.150001E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121718E+10 | 0.918178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145510E+10 | 0.157477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.268777E+10 | 0.128836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.250657E+10 | 0.165339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.295507E+10 | 0.198630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.273944E+10 | 0.194666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.295606E+10 | 0.293917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.298269E+10 | 0.321494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.307481E+10 | 0.398056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.324837E+10 | 0.417904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.314456E+10 | 0.414510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.296357E+10 | 0.343961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.268214E+10 | 0.244956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.270200E+10 | 0.184864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.346430E+11 | 0.330713E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.250657E+10 | 0.128836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.324837E+10 | 0.417904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.131742E+10 | 0.00 | 0.00 | 0.00 | 0.242945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121718E+10 | 0.00 | 0.00 | 0.00 | 0.259835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142782E+10 | 0.00 | 0.00 | 0.00 | 0.300495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132333E+10 | 0.00 | 0.00 | 0.00 | 0.285185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138732E+10 | 0.00 | 0.00 | 0.00 | 0.353751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139277E+10 | 0.00 | 0.00 | 0.00 | 0.370370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135204E+10 | 0.00 | 0.00 | 0.00 | 0.395516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145510E+10 | 0.00 | 0.00 | 0.00 | 0.428681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135644E+10 | 0.00 | 0.00 | 0.00 | 0.397038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134138E+10 | 0.00 | 0.00 | 0.00 | 0.370977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128022E+10 | 0.00 | 0.00 | 0.00 | 0.317549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132473E+10 | 0.00 | 0.00 | 0.00 | 0.285843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161758E+11 | 0.00 | 0.00 | 0.00 | 0.400818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.121718E+10 | 0.00 | 0.00 | 0.00 | 0.242945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145510E+10 | 0.00 | 0.00 | 0.00 | 0.428681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.268777E+10 | 0.00 | 0.00 | 0.00 | 0.371223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.250657E+10 | 0.00 | 0.00 | 0.00 | 0.468127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.295507E+10 | 0.00 | 0.00 | 0.00 | 0.570200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.273944E+10 | 0.00 | 0.00 | 0.00 | 0.561434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.295606E+10 | 0.00 | 0.00 | 0.00 | 0.853417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.298269E+10 | 0.00 | 0.00 | 0.00 | 0.925654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.307481E+10 | 0.00 | 0.00 | 0.00 | 0.115817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.324837E+10 | 0.00 | 0.00 | 0.00 | 0.122456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.314456E+10 | 0.00 | 0.00 | 0.00 | 0.119484E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.296357E+10 | 0.00 | 0.00 | 0.00 | 0.100761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.268214E+10 | 0.00 | 0.00 | 0.00 | 0.704076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.270200E+10 | 0.00 | 0.00 | 0.00 | 0.527733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.346430E+11 | 0.00 | 0.00 | 0.00 | 0.956704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.250657E+10 | 0.00 | 0.00 | 0.00 | 0.371223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.324837E+10 | 0.00 | 0.00 | 0.00 | 0.122456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1731139.87 | 0.959695E+09 | 0.00 | 3165164.92 | 110206.02 | 0.00 | 35308214.02 | 0.00 | 0.16 |
February | 4194639.37 | 0.141712E+10 | 0.00 | 2885969.76 | 0.00 | 0.00 | 18852655.74 | 0.00 | 0.17 |
March | 2124688.18 | 0.138978E+10 | 0.00 | 3422916.58 | 0.00 | 0.00 | 33200299.17 | 0.00 | 0.18 |
April | 0.00 | 0.124984E+10 | 0.00 | 3124427.13 | 0.00 | 0.00 | 13888790.26 | 0.00 | 0.17 |
May | 0.00 | 0.191248E+10 | 0.00 | 2762688.32 | 0.00 | 0.00 | 1034927.45 | 0.00 | 0.17 |
June | 0.00 | 0.203960E+10 | 0.00 | 1274193.89 | 0.00 | 0.00 | 169532.15 | 0.00 | 0.18 |
July | 0.00 | 0.236195E+10 | 0.00 | 974584.80 | 0.00 | 0.00 | 78222.12 | 0.00 | 0.17 |
August | 0.00 | 0.258872E+10 | 0.00 | 856765.17 | 0.00 | 0.00 | 2533.15 | 0.00 | 0.18 |
September | 0.00 | 0.247021E+10 | 0.00 | 800826.38 | 0.00 | 0.00 | 20419.77 | 0.00 | 0.18 |
October | 0.00 | 0.230288E+10 | 0.00 | 1875574.73 | 0.00 | 0.00 | 500690.87 | 0.00 | 0.17 |
November | 0.00 | 0.177958E+10 | 0.00 | 2636658.47 | 0.00 | 0.00 | 3381332.87 | 0.00 | 0.17 |
December | 344106.27 | 0.150221E+10 | 0.00 | 2699162.24 | 0.00 | 0.00 | 9005378.11 | 0.00 | 0.17 |
Annual Sum or Average | 8394573.69 | 0.219741E+11 | 0.00 | 26478932.39 | 110206.02 | 0.00 | 0.115443E+09 | 0.00 | 0.17 |
Minimum of Months | 0.00 | 0.959695E+09 | 0.00 | 800826.38 | 0.00 | 0.00 | 2533.15 | 0.00 | 0.16 |
Maximum of Months | 4194639.37 | 0.258872E+10 | 0.00 | 3422916.58 | 110206.02 | 0.00 | 35308214.02 | 0.00 | 0.18 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.377472E+09 | 0.126654E+10 | 0.00 | 2420124.30 | 309088.14 | 0.00 | 0.268847E+09 | 0.00 | 0.17 |
February | 0.242067E+09 | 0.210553E+10 | 0.00 | 1808444.51 | 432957.13 | 0.00 | 0.149158E+09 | 0.00 | 0.17 |
March | 0.337797E+09 | 0.197560E+10 | 0.00 | 1663609.90 | 0.00 | 0.00 | 0.161602E+09 | 0.00 | 0.18 |
April | 0.201545E+09 | 0.179980E+10 | 0.00 | 1690992.70 | 0.00 | 0.00 | 0.155292E+09 | 0.00 | 0.18 |
May | 36357304.89 | 0.351077E+10 | 0.00 | 1141651.14 | 0.00 | 0.00 | 95375984.71 | 0.00 | 0.18 |
June | 10860257.37 | 0.355367E+10 | 0.00 | 811908.02 | 0.00 | 0.00 | 55793014.32 | 0.00 | 0.19 |
July | 809207.12 | 0.474995E+10 | 0.00 | 1354928.81 | 0.00 | 0.00 | 52685505.39 | 0.00 | 0.19 |
August | 2785990.48 | 0.536770E+10 | 0.00 | 1283272.23 | 156063.39 | 0.00 | 58320560.41 | 0.00 | 0.20 |
September | 575058.32 | 0.506826E+10 | 0.00 | 792839.11 | 76553.22 | 0.00 | 28027918.50 | 0.00 | 0.20 |
October | 32322656.70 | 0.485498E+10 | 0.00 | 919794.27 | 0.00 | 0.00 | 0.115765E+09 | 0.00 | 0.18 |
November | 51294294.96 | 0.294153E+10 | 0.00 | 885677.18 | 0.00 | 0.00 | 68559794.33 | 0.00 | 0.17 |
December | 0.165187E+09 | 0.229418E+10 | 0.00 | 2021795.11 | 0.00 | 0.00 | 0.162185E+09 | 0.00 | 0.17 |
Annual Sum or Average | 0.145907E+10 | 0.394885E+11 | 0.00 | 16795037.27 | 974661.88 | 0.00 | 0.137161E+10 | 0.00 | 0.18 |
Minimum of Months | 575058.32 | 0.126654E+10 | 0.00 | 792839.11 | 0.00 | 0.00 | 28027918.50 | 0.00 | 0.17 |
Maximum of Months | 0.377472E+09 | 0.536770E+10 | 0.00 | 2420124.30 | 432957.13 | 0.00 | 0.268847E+09 | 0.00 | 0.20 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |