Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2020-06-03 19:11:19
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1049.98 | 217.16 | 217.16 |
Net Site Energy | 1049.98 | 217.16 | 217.16 |
Total Source Energy | 3121.82 | 645.65 | 645.65 |
Net Source Energy | 3121.82 | 645.65 | 645.65 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 97.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 120.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 123.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 69.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 23.38 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 952.30 | 97.68 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 97.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 120.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 476.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 123.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 13.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 55.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 23.38 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 124.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 44.14 | 20.20 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 196.95 | 20.20 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 124.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 44.14 | 20.20 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 196.95 | 20.20 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 952.299 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 952.299 | 100.00 |
Total On-Site and Utility Electric Sources | 952.299 | 100.00 |
Total Electricity End Uses | 952.299 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 3.00 |
Time Setpoint Not Met During Occupied Cooling | 51.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 435.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 15.45 |
Skylight-Roof Ratio [%] | 0.34 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 10.6337 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 8.5069 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 8.5069 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 8.6111 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-AUG-14:00 | 06-FEB-07:10 | - | - | - | 13-JUL-11:39 |
Heating | 0.00 | 36810.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 21658.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6654.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1680.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 75295.13 | 36810.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 36810.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 21658.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4349.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1680.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 105.89 | 0.00 | 0.00 | 0.00 |
Cooling | 381.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1507.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 391.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 220.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 74.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3015.93 | 105.89 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 21.90 | 0.00 | 0.00 | 0.00 |
Cooling | 78.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 45.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 623.75 | 21.90 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 21.90 | 0.00 | 0.00 | 0.00 |
Cooling | 78.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 311.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 80.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 45.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 623.75 | 21.90 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.13 |
ZONE2 FINE STORAGE DIRECT AIR | 2.79 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 0.814033 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 0.814033 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 33778.87 |
PSZ-OFFICE HEATING COIL | 28386.85 |
PSZ-FINE STORAGE HEATING COIL | 87263.28 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 31224.15 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.13 | 1.13 | 1.13 | 1.13 | 1.13 | 1.13 | 1.00 | 1.00 | 1.13 |
PSZ-FINE STORAGE | 2.79 | 2.79 | 2.79 | 2.79 | 2.79 | 2.79 | 1.00 | 1.00 | 2.79 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 1.13 | 0.120335 |
PSZ-FINE STORAGE OA CONTROLLER | 2.79 | 0.353927 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.13 | 1.13 | 1.13 | 1.13 | 22978.76 | 28386.85 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 2.79 | 2.79 | 2.79 | 2.79 | 68710.25 | 87263.28 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.13 | 0.566245 | 1.13 | 22452.53 | 22978.76 | 11489.38 | 22978.76 | 0.730944 | 0.730940 | 0.730940 | 0.730940 |
PSZ-FINE STORAGE COOLING COIL | 2.79 | 1.40 | 2.79 | 65895.80 | 68710.25 | 34355.12 | 68710.25 | 0.678510 | 0.678510 | 0.678510 | 0.678510 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.13 | 1291.17 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.79 | 3058.44 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 10.634 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.707 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 8.507 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.507 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 8.507 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 11.066 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 2518.900 | 10.634 | 503.780 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2518.900 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 11853.648 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11853.648 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 27263.390 | 8.507 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 27263.390 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3888 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.6999 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.572 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
2 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
3 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
4 | 2 | 0.20482715E-10 | 0.21205973E-14 | 0.31184805E-15 | 0.0000000 |
5 | 1 | -5.2160080 | 0.41303701E-04 | -0.41204219E-04 | 0.97833724E-11 |
6 | 0 | 5.6048073 | 0.38875791 | 0.38884042 | |
7 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
8 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
9 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
10 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
11 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
12 | 4 | 0.73826229E-12 | -0.15793949E-15 | 0.14714251E-14 | 0.12610148E-15 |
13 | 3 | -0.37015163E-03 | 0.48261894E-06 | -0.53553847E-04 | 0.14168247E-12 |
14 | 2 | 1.7048811 | 0.10720623E-01 | 1.1141045 | -0.70963114E-04 |
15 | 1 | -7.1749370 | 0.28051356 | -16.929564 | 0.32672988 |
16 | 0 | 5.9416824 | 0.18002168 | 16.286769 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.14714251E-14 | -0.15793949E-15 | 0.73826229E-12 | 0.12610148E-15 |
85 | 3 | -0.53553847E-04 | 0.48261894E-06 | -0.37015163E-03 | 0.14168247E-12 |
86 | 2 | 1.1141045 | 0.10720623E-01 | 1.7048811 | -0.70963114E-04 |
87 | 1 | -16.929564 | 0.28051356 | -7.1749370 | 0.32672988 |
88 | 0 | 16.286769 | 0.18002168 | 5.9416824 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.73_SHGC_0.25 | 28 | 1 | VerySmooth | 4.149 | 0.255 | 0.127 | 0.250 |
2 | SKYLIGHT_U_1.02_SHGC_0.4 | 29 | 1 | VerySmooth | 5.779 | 0.400 | 0.232 | 0.401 |
3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 30 | 1 | VerySmooth | 5.779 | 0.400 | 0.232 | 0.401 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.12629 | 0.51106 | 0.51106 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 2.73817E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.23173 | 0.20656 | 0.20656 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.23173 | 0.20656 | 0.20656 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.055 | 0.5308 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 6.083E-002 | 2.568E-004 | 3.964E-004 | 0.217 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.889 | 6.381E-004 | 4.064E-004 | 1.084 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 3.431 | 1.071E-003 | 6.993E-004 | 0.350 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11461.74989 | 13754.09987 | 0.94375 | 1.13249 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65138E-002 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 7730.20027 | 9276.24033 | 0.21700 | 0.26040 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 4.60000 | 5.25715E-003 | 236.87965 | 5.00000 | 0.12034 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 36277.25590 | 43532.70708 | 2.32863 | 2.79436 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 33.90000 | 1.65138E-002 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 18902.44115 | 22682.92937 | 0.44733 | 0.53680 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 1393.40969 | 0.00000 | 0.35393 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.81403 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90000 | 1.65138E-002 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 26020.12239 | 31224.14687 | 0.62706 | 0.81403 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 3204.84228 | 0.00000 | 0.81403 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 17586.26 | 1.13249 | 1.13249 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 8365.74 | 0.26040 | 0.26040 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 52737.25 | 2.79436 | 2.79436 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 20551.65 | 0.53680 | 0.53680 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.13249 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.79436 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.81403 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 0.81403 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 33778.87156 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 31224.14687 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.13249 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.13249 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.13249 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.13249 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.13249 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.13249 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.79436 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.79436 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.79436 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.79436 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.79436 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.79436 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.13249 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.79436 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.13249 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.12034 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.13249 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.13249 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.13249 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.13249 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.13249 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56625 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.13249 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22452.53455 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22978.76000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11489.38000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 22978.76000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73094 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73094 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73094 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73094 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22978.76000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28386.84641 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.13249 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1291.16800 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 28386.84641 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.79436 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.35393 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.79436 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.79436 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.79436 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.79436 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.79436 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.39718 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.79436 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 65895.80177 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 68710.25000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 34355.12500 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 68710.25000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67851 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67851 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67851 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67851 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 68710.25000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 87263.27702 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.79436 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 3058.43757 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 87263.27702 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 22099.3 | 10.39 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 66538.3 | 13.44 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 6 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.6773682682E-002 | 3.6697642119E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1053446848 | 0.1423534704 | Pass | Pass | 8.7488106297E-002 | 0.6435910216 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 4.7677923132E-002 | 4.0232347112E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.634 | 0.700 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.369 | 0.389 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.634 | 0.700 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.369 | 0.389 | 3204.84 | 3189.39 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.73_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 4.149 | 0.255 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.73_SHGC_0.25 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 4.149 | 0.255 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.73_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 4.149 | 0.255 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.73_SHGC_0.25 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 4.149 | 0.255 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 0.06 | 0.00 | 1.55 | 1.55 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 0.06 | 0.00 | 1.55 | 1.55 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 0.06 | 0.00 | 1.55 | 1.55 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 0.06 | 0.00 | 1.55 | 1.55 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 0.06 | 0.00 | 1.55 | 1.55 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 0.06 | 0.00 | 1.55 | 1.55 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 0.06 | 0.00 | 1.55 | 1.55 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 0.06 | 0.00 | 1.55 | 1.55 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 0.06 | 0.00 | 1.55 | 1.55 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.4 | 1.49 | 0.06 | 0.00 | 1.55 | 1.55 | 5.779 | 0.400 | 0.401 | 283.913 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 33.12 | 4.910 | 0.323 | 0.320 | ||||||||||||
North Total or Average | 6.51 | 4.149 | 0.255 | 0.250 | ||||||||||||
Non-North Total or Average | 26.61 | 5.096 | 0.339 | 0.338 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 10.6337 | 236.88 | 2518.90 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.62 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 8.5069 | 1393.41 | 11853.65 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 135.00 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 8.5069 | 3204.84 | 27263.39 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 310.50 |
Interior Lighting Total | 8.6111 | 4835.13 | 41635.94 | 476.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7857.00 | AstronomicalClock | - | 83.73 | 83.73 | 123.48 | |
Exterior Lighting Total | 7857.00 | 123.48 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22978.76 | 16796.09 | 6182.67 | 0.73 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 68710.25 | 46620.59 | 22089.66 | 0.68 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 22099.3 | 10.39 | ||||
PSZ-FINE STORAGE COOLING COIL | 66538.3 | 13.44 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 33778.87 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 28386.85 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 87263.28 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.81 | 75.63 | 92.91 | 1.00 | 4.39 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.55 | 622.50 | 1.13 | 1291.17 | 1140.11 | 1.00 | 1.33 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.57 | 622.50 | 2.79 | 3058.44 | 1094.51 | 1.00 | 1.24 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11461.75 | 13754.10 | 58.06 | 0.944 | 1.132 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23.90 | 23.90 | 0.00832 | 32.79 | 0.01651 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 36277.26 | 43532.71 | 31.24 | 2.329 | 2.794 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.70 | 26.70 | 0.00859 | 33.90 | 0.01651 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.814 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00378 | 33.90 | 0.01651 | 0.814 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 7730.20 | 9276.24 | 39.16 | 0.217 | 0.260 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00777 | 4.60 | 0.00526 | 0.120 | 0.00 |
ZONE2 FINE STORAGE | 18902.44 | 22682.93 | 16.28 | 0.447 | 0.537 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.56 | 0.00678 | 4.60 | 0.00526 | 0.354 | 0.00 |
ZONE3 BULK STORAGE | 26020.12 | 31224.15 | 9.74 | 0.627 | 0.814 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00764 | 4.60 | 0.00526 | 0.814 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.13 | 1.13 | 0.26 | 0.26 | 1.1325 | 1.1325 | 1.1325 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.79 | 2.79 | 0.54 | 0.54 | 2.7944 | 2.7944 | 2.7944 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 33778.872 | 33778.872 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 33778.87 | 33778.87 | 0.814033 | 4.60 | 4.60 | 0.00525715 | 43.33 | 27.10 | 0.01600000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 10.00 | 0.00763650 | 99.9999 | 31224.15 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 22978.760 | 0.000 | 1.132490 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 22978.76 | 19001.56 | 1.132490 | 24.84 | 17.24 | 0.00918648 | 12.00 | 11.25 | 0.00800000 | 32.79 | 0.01651377 | 24.82 | 10.6257 | 23.90 | 0.00831534 | 45.0110 | 11461.75 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 28386.846 | 28386.846 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 28386.85 | 28386.85 | 1.132494 | 13.43 | 10.40 | 0.00660615 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 10.6257 | 21.10 | 0.00776514 | 49.8710 | 7730.20 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 68710.250 | 0.000 | 2.794360 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 68710.25 | 55615.24 | 2.794360 | 27.61 | 18.50 | 0.00959221 | 12.00 | 11.25 | 0.00800000 | 33.90 | 0.01651378 | 25.10 | 12.6658 | 26.70 | 0.00858839 | 39.3420 | 35118.03 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 87263.277 | 87263.277 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 87263.28 | 87263.28 | 2.794356 | 8.33 | 7.12 | 0.00577489 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 12.6658 | 15.56 | 0.00677693 | 61.7238 | 18902.44 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 33778.872 | 33778.872 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.2032 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.814033 | 0.97941773 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 33778.87 | 33778.87 | 1.0000 | 0.97941773 | 0.814033 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 43.33 | 27.10 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33778.87 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 10.00 | 0.00763650 | 10.00 | 0.00763650 | 99.9999 | 31224.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22978.760 | 0.000 | 1.132490 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9172 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 22978.76 | 19001.56 | 1.0000 | 1.36257448 | 1.132490 | 24.84 | 17.24 | 0.00918648 | 48363.5 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22978.76 | 32.79 | 0.01651377 | 24.82 | 0.12033533 | 10.6257 | 23.90 | 0.00831534 | 23.90 | 0.00831534 | 45.0110 | 11461.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28386.846 | 28386.846 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.132494 | 1.36257970 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 28386.85 | 28386.85 | 1.0000 | 1.36257970 | 1.132494 | 13.43 | 10.40 | 0.00660615 | 30178.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28386.85 | 4.60 | 0.00525715 | 4.60 | 0.12033533 | 10.6257 | 21.01 | 0.00776514 | 21.10 | 0.00776514 | 49.8710 | 7730.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 68710.250 | 0.000 | 2.794360 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.6714 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 68710.25 | 55615.24 | 1.0000 | 3.36208145 | 2.794360 | 27.61 | 18.50 | 0.00959221 | 52225.6 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 68710.25 | 33.90 | 0.01651378 | 25.10 | 0.35392745 | 12.6658 | 26.70 | 0.00858839 | 26.70 | 0.00858839 | 39.3420 | 35118.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 87263.277 | 87263.277 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.794356 | 3.36207617 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 87263.28 | 87263.28 | 1.0000 | 3.36207617 | 2.794356 | 8.33 | 7.12 | 0.00577489 | 22905.6 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87263.28 | 4.60 | 0.00525715 | 4.60 | 0.35392745 | 12.6658 | 15.56 | 0.00677693 | 15.56 | 0.00677693 | 61.7238 | 18902.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2607.33 | 1180.67 | 435.50 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2607.33 | 1180.67 | 435.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 3.00 | 54.67 | 3.00 | 51.50 |
ZONE2 FINE STORAGE | 1.00 | 173.67 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 4.00 | 228.33 | 3.00 | 51.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.410 | 0.369 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.74 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 952.30 | 5421.86 | 01-JAN-07:30 | 75295.13 | 03-AUG-15:00 |
Electricity:Building | 629.22 | 4938.86 | 01-JAN-00:10 | 47606.95 | 14-APR-14:20 |
Electricity:Zone:ZONE1 OFFICE | 62.57 | 1027.15 | 01-JAN-00:10 | 3852.05 | 02-JAN-08:10 |
InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.62 | 453.40 | 01-JAN-00:10 | 1939.55 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 476.13 | 4365.11 | 01-JAN-00:10 | 35189.04 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 135.00 | 1185.36 | 01-JAN-00:10 | 10075.60 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 431.66 | 2726.34 | 01-JAN-00:10 | 33679.30 | 14-APR-13:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 310.51 | 2726.34 | 01-JAN-00:10 | 23173.88 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 23.38 | 483.00 | 11-JAN-06:10 | 1774.94 | 23-JAN-12:20 |
WaterSystems:Electricity | 23.38 | 483.00 | 11-JAN-06:10 | 1774.94 | 23-JAN-12:20 |
Water Heater:WaterSystems:Electricity | 23.38 | 483.00 | 11-JAN-06:10 | 1774.94 | 23-JAN-12:20 |
Fans:Electricity | 69.62 | 0.00 | 01-JAN-00:10 | 6654.90 | 18-SEP-08:30 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 13.81 | 0.00 | 01-JAN-00:10 | 2305.29 | 07-MAY-14:30 |
Ventilation (simple):Fans:Electricity | 13.81 | 0.00 | 01-JAN-00:10 | 2305.29 | 07-MAY-14:30 |
ElectricityPurchased:Facility | 952.30 | 5421.86 | 01-JAN-07:30 | 75295.13 | 03-AUG-15:00 |
ElectricityPurchased:Plant | 952.30 | 5421.86 | 01-JAN-07:30 | 75295.13 | 03-AUG-15:00 |
Cogeneration:ElectricityPurchased | 952.30 | 5421.86 | 01-JAN-07:30 | 75295.13 | 03-AUG-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 952.30 | 5421.86 | 01-JAN-07:30 | 75295.13 | 03-AUG-15:00 |
ElectricityNet:Plant | 952.30 | 5421.86 | 01-JAN-07:30 | 75295.13 | 03-AUG-15:00 |
Cogeneration:ElectricityNet | 952.30 | 5421.86 | 01-JAN-07:30 | 75295.13 | 03-AUG-15:00 |
Electricity:HVAC | 176.21 | 0.00 | 01-JAN-00:10 | 28202.91 | 03-AUG-16:10 |
General:Fans:Electricity | 55.81 | 0.00 | 01-JAN-00:10 | 4349.61 | 02-JAN-10:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 120.40 | 0.00 | 01-JAN-00:10 | 23853.30 | 03-AUG-16:10 |
ExteriorLights:Electricity | 123.48 | 0.00 | 01-JAN-07:30 | 7857.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 123.48 | 0.00 | 01-JAN-07:30 | 7857.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 97.68 | 3000.00 | 30-MAR-05:10 | 36810.04 | 06-FEB-07:10 |
Gas:HVAC | 97.68 | 3000.00 | 30-MAR-05:10 | 36810.04 | 06-FEB-07:10 |
Heating:Gas | 97.68 | 3000.00 | 30-MAR-05:10 | 36810.04 | 06-FEB-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 666.71 | 0.00 | 01-JAN-00:10 | 127159.42 | 03-AUG-16:10 |
EnergyTransfer:Building | 242.60 | 0.00 | 01-JAN-00:10 | 49120.54 | 03-AUG-16:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 70.29 | 0.00 | 01-JAN-00:10 | 13792.30 | 11-SEP-05:10 |
Heating:EnergyTransfer | 3.72 | 0.00 | 01-JAN-00:10 | 20350.23 | 10-JAN-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 1.65 | 0.00 | 01-JAN-00:10 | 11988.99 | 06-FEB-06:10 |
Cooling:EnergyTransfer | 238.88 | 0.00 | 01-JAN-00:10 | 49120.54 | 03-AUG-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 68.63 | 0.00 | 01-JAN-00:10 | 13792.30 | 11-SEP-05:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 172.31 | 0.00 | 01-JAN-00:10 | 37877.69 | 03-AUG-15:30 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 2.06 | 0.00 | 01-JAN-00:10 | 18916.34 | 05-FEB-07:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 170.25 | 0.00 | 01-JAN-00:10 | 37877.69 | 03-AUG-15:30 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 424.12 | 0.00 | 01-JAN-00:10 | 78038.88 | 03-AUG-16:10 |
HeatingCoils:EnergyTransfer | 2.09 | 0.00 | 01-JAN-00:10 | 23331.58 | 10-JAN-07:10 |
CoolingCoils:EnergyTransfer | 422.03 | 0.00 | 01-JAN-00:10 | 78038.88 | 03-AUG-16:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 1.654 | -68.633 | 0.000 | 0.000 | 3.621 | 30.619 | 31.946 | 10.932 | 0.000 | 3.873 | 0.164 | 0.000 | -6.796 | 0.000 | -7.382 | -0.000 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 2.061 | -170.235 | 0.000 | 0.000 | 0.000 | 135.003 | 0.000 | 0.000 | 0.000 | 7.608 | 73.957 | 0.000 | 0.000 | 0.000 | -48.394 | -0.000 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 310.507 | 107.336 | 32.618 | 0.000 | 6.724 | 32.666 | 0.000 | -11.226 | 0.000 | -478.625 | -0.032 |
Total Facility | 0.000 | 0.000 | 3.715 | -238.868 | 0.000 | 0.000 | 3.621 | 476.129 | 139.282 | 43.551 | 0.000 | 18.205 | 106.787 | 0.000 | -18.022 | 0.000 | -534.400 | -0.032 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 27-OCT-05:02 | 0.00 | 0.00 | 0.00 | -21269.42 | 0.00 | 0.00 | 33.88 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 21677.95 | 0.00 | -681.89 | 0.00 | -913.61 | 0.00 |
ZONE2 FINE STORAGE | 01-OCT-14:53 | 0.00 | 0.00 | 0.00 | -57489.15 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 153.68 | 56150.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-JUN-14:53 | 0.00 | 0.00 | 0.00 | -58523.49 | 0.00 | 0.00 | 0.00 | 4365.11 | 573.75 | 6856.83 | 0.00 | 6609.16 | 40118.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 07-FEB-06:01 | 0.00 | 0.00 | 27205.35 | 0.00 | 0.00 | 0.00 | 52.67 | 579.35 | 573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -611.85 | 0.00 | -901.13 | -26898.13 |
ZONE2 FINE STORAGE | 21-DEC-06:01 | 0.00 | 0.00 | 56950.94 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -6012.89 | -52123.41 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-DEC-06:01 | 0.00 | 0.00 | 83092.00 | 0.00 | 0.00 | 0.00 | 52.82 | 4491.05 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2453.04 | 0.00 | -34906.13 | -52900.49 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1325 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.1325 | 0.1063 | 1.0000 | 0.1203 | 0.1063 | ||
PSZ-FINE STORAGE | 2.7944 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.7944 | 0.1267 | 1.0000 | 0.3539 | 0.1267 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1325 | 0.0000 | 5.0000 | 1.0000 | 0.1203 | 1.1325 | 1.0000 | 1.0000 | 0.1203 | 0.1063 | ||
PSZ-FINE STORAGE | 2.7944 | 0.0000 | 0.0000 | 1.0000 | 0.3539 | 2.7944 | 1.0000 | 1.0000 | 0.3539 | 0.1267 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000508 | 236.88 | 0.1203 | 1.0000 | 0.1203 | 1.000 | 0.1203 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000254 | 1393.41 | 0.3539 | 1.0000 | 0.3539 | 1.000 | 0.3539 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000508 | 236.8796 | 0.1203 | 0.1203 | 0.1203 |
PSZ-FINE STORAGE | 0.00 | 0.000254 | 1393.4097 | 0.3539 | 0.3539 | 0.3539 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.1325 | 1.1325 | 1.1325 | 0.1203 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.7944 | 2.7944 | 2.7944 | 0.3539 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1325 | 1.1325 | 1.1325 | 1.1325 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.7944 | 2.7944 | 2.7944 | 2.7944 | 0.3539 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 1.1325 | 1.1325 | 1.1325 | 0.1203 | 0.4621 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 2.7944 | 2.7944 | 2.7944 | 0.3539 | 0.6593 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1325 | 1.1325 | 1.1325 | 1.1325 | 0.1203 | 1.0000 |
PSZ-FINE STORAGE | 2.7944 | 2.7944 | 2.7944 | 2.7944 | 0.3539 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:19
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 3.00 |
Number of hours cooling loads not met | 51.50 |
Number of hours not met | 54.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 97.68 | 36810.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 120.40 | 23853.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 476.13 | 35189.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 123.48 | 7857.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 13.81 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 55.81 | 4349.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 23.38 | 1774.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 952.30 |
Natural Gas | 0.00 | 97.68 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1049.98 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 98.47 |
Space Heating | 0.00 |
Space Cooling | 24.90 |
Fans (All) | 14.40 |
Service Water Heating | 4.84 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 196.95 |
Subtotal | 196.95 |
Natural Gas [MJ/m2] | |
Space Heating | 20.20 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 20.20 |
Subtotal | 20.20 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 45.35 |
Space Heating | 9.30 |
Space Cooling | 11.47 |
Fans (All) | 6.63 |
Service Water Heating | 2.23 |
Receptacle Equipment | 13.27 |
Miscellaneous | 11.76 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3430. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.918599E+10 |
February | 0.000 | 0.811810E+10 |
March | 0.000 | 0.844531E+10 |
April | 0.000 | 0.777892E+10 |
May | 0.000 | 0.803520E+10 |
June | 0.000 | 0.777600E+10 |
July | 0.000 | 0.803520E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.777600E+10 |
October | 0.000 | 0.803520E+10 |
November | 0.000 | 0.781449E+10 |
December | 0.000 | 0.864741E+10 |
Annual Sum or Average | 0.976830E+11 | |
Minimum of Months | 0.000 | 0.777600E+10 |
Maximum of Months | 0.000 | 0.918599E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.918599E+10 |
February | 0.000 | 0.811810E+10 |
March | 0.000 | 0.844531E+10 |
April | 0.000 | 0.777892E+10 |
May | 0.000 | 0.803520E+10 |
June | 0.000 | 0.777600E+10 |
July | 0.000 | 0.803520E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.777600E+10 |
October | 0.000 | 0.803520E+10 |
November | 0.000 | 0.781449E+10 |
December | 0.000 | 0.864741E+10 |
Annual Sum or Average | 0.976830E+11 | |
Minimum of Months | 0.000 | 0.777600E+10 |
Maximum of Months | 0.000 | 0.918599E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.918599E+10 |
February | 0.000 | 0.811810E+10 |
March | 0.000 | 0.844531E+10 |
April | 0.000 | 0.777892E+10 |
May | 0.000 | 0.803520E+10 |
June | 0.000 | 0.777600E+10 |
July | 0.000 | 0.803520E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.777600E+10 |
October | 0.000 | 0.803520E+10 |
November | 0.000 | 0.781449E+10 |
December | 0.000 | 0.864741E+10 |
Annual Sum or Average | 0.976830E+11 | |
Minimum of Months | 0.000 | 0.777600E+10 |
Maximum of Months | 0.000 | 0.918599E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.918599E+10 |
February | 0.000 | 0.811810E+10 |
March | 0.000 | 0.844531E+10 |
April | 0.000 | 0.777892E+10 |
May | 0.000 | 0.803520E+10 |
June | 0.000 | 0.777600E+10 |
July | 0.000 | 0.803520E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.777600E+10 |
October | 0.000 | 0.803520E+10 |
November | 0.000 | 0.781449E+10 |
December | 0.000 | 0.864741E+10 |
Annual Sum or Average | 0.976830E+11 | |
Minimum of Months | 0.000 | 0.777600E+10 |
Maximum of Months | 0.000 | 0.918599E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.918599E+10 |
February | 0.000 | 0.811810E+10 |
March | 0.000 | 0.844531E+10 |
April | 0.000 | 0.777892E+10 |
May | 0.000 | 0.803520E+10 |
June | 0.000 | 0.777600E+10 |
July | 0.000 | 0.803520E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.777600E+10 |
October | 0.000 | 0.803520E+10 |
November | 0.000 | 0.781449E+10 |
December | 0.000 | 0.864741E+10 |
Annual Sum or Average | 0.976830E+11 | |
Minimum of Months | 0.000 | 0.777600E+10 |
Maximum of Months | 0.000 | 0.918599E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.918599E+10 |
February | 0.000 | 0.811810E+10 |
March | 0.000 | 0.844531E+10 |
April | 0.000 | 0.777892E+10 |
May | 0.000 | 0.803520E+10 |
June | 0.000 | 0.777600E+10 |
July | 0.000 | 0.803520E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.777600E+10 |
October | 0.000 | 0.803520E+10 |
November | 0.000 | 0.781449E+10 |
December | 0.000 | 0.864741E+10 |
Annual Sum or Average | 0.976830E+11 | |
Minimum of Months | 0.000 | 0.777600E+10 |
Maximum of Months | 0.000 | 0.918599E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.918599E+10 |
February | 0.000 | 0.811810E+10 |
March | 0.000 | 0.844531E+10 |
April | 0.000 | 0.777892E+10 |
May | 0.000 | 0.803520E+10 |
June | 0.000 | 0.777600E+10 |
July | 0.000 | 0.803520E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.777600E+10 |
October | 0.000 | 0.803520E+10 |
November | 0.000 | 0.781449E+10 |
December | 0.000 | 0.864741E+10 |
Annual Sum or Average | 0.976830E+11 | |
Minimum of Months | 0.000 | 0.777600E+10 |
Maximum of Months | 0.000 | 0.918599E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.918599E+10 |
February | 0.000 | 0.811810E+10 |
March | 0.000 | 0.844531E+10 |
April | 0.000 | 0.777892E+10 |
May | 0.000 | 0.803520E+10 |
June | 0.000 | 0.777600E+10 |
July | 0.000 | 0.803520E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.777600E+10 |
October | 0.000 | 0.803520E+10 |
November | 0.000 | 0.781449E+10 |
December | 0.000 | 0.864741E+10 |
Annual Sum or Average | 0.976830E+11 | |
Minimum of Months | 0.000 | 0.777600E+10 |
Maximum of Months | 0.000 | 0.918599E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.918599E+10 |
February | 0.000 | 0.811810E+10 |
March | 0.000 | 0.844531E+10 |
April | 0.000 | 0.777892E+10 |
May | 0.000 | 0.803520E+10 |
June | 0.000 | 0.777600E+10 |
July | 0.000 | 0.803520E+10 |
August | 0.000 | 0.803520E+10 |
September | 0.000 | 0.777600E+10 |
October | 0.000 | 0.803520E+10 |
November | 0.000 | 0.781449E+10 |
December | 0.000 | 0.864741E+10 |
Annual Sum or Average | 0.976830E+11 | |
Minimum of Months | 0.000 | 0.777600E+10 |
Maximum of Months | 0.000 | 0.918599E+10 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132174E+10 | 16996.14 | 02-JAN-06:02 | 16.00 | 15.39 | 0.233153E+09 | 301.60 | 28-JAN-16:00 | 22.00 | 14.38 |
February | 0.192888E+10 | 17180.86 | 27-FEB-06:02 | 17.70 | 17.70 | 0.220401E+09 | 302.98 | 07-FEB-13:50 | 17.67 | 12.18 |
March | 0.281964E+10 | 16339.63 | 30-MAR-05:01 | 20.83 | 19.77 | 0.260298E+09 | 304.45 | 06-MAR-08:09 | 20.08 | 18.36 |
April | 0.513699E+10 | 20949.04 | 18-APR-05:02 | 17.10 | 15.03 | 0.248478E+09 | 301.60 | 17-APR-09:20 | 19.03 | 12.04 |
May | 0.831073E+10 | 18011.98 | 05-MAY-05:01 | 23.30 | 20.65 | 0.259061E+09 | 301.58 | 13-MAY-13:30 | 26.95 | 23.26 |
June | 0.885150E+10 | 18170.20 | 14-JUN-05:01 | 25.00 | 22.88 | 0.259077E+09 | 301.61 | 12-JUN-15:09 | 32.88 | 21.47 |
July | 0.875718E+10 | 16714.10 | 19-JUL-05:01 | 27.12 | 24.30 | 0.249134E+09 | 301.58 | 08-JUL-13:09 | 33.57 | 24.71 |
August | 0.952567E+10 | 19234.99 | 31-AUG-05:01 | 24.13 | 22.97 | 0.269060E+09 | 301.59 | 30-AUG-15:30 | 34.50 | 23.19 |
September | 0.817162E+10 | 17402.12 | 01-SEP-05:01 | 24.42 | 23.28 | 0.249117E+09 | 301.58 | 09-SEP-07:10 | 25.68 | 23.64 |
October | 0.736942E+10 | 21269.87 | 27-OCT-05:02 | 15.00 | 7.94 | 0.249027E+09 | 301.61 | 17-OCT-15:50 | 23.93 | 16.53 |
November | 0.395682E+10 | 17911.37 | 06-NOV-06:01 | 18.80 | 17.70 | 0.237604E+09 | 301.60 | 17-NOV-16:00 | 22.20 | 14.69 |
December | 0.248473E+10 | 15369.62 | 16-DEC-06:01 | 20.83 | 19.18 | 0.238912E+09 | 301.59 | 05-DEC-16:10 | 17.83 | 12.11 |
Annual Sum or Average | 0.686349E+11 | 0.297332E+10 | ||||||||
Minimum of Months | 0.132174E+10 | 15369.62 | 15.00 | 7.94 | 0.220401E+09 | 301.58 | 17.67 | 12.04 | ||
Maximum of Months | 0.952567E+10 | 21269.87 | 27.12 | 24.30 | 0.269060E+09 | 304.45 | 34.50 | 24.71 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103153E+10 | 26027.42 | 01-JAN-14:15 | 25.67 | 18.11 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.190890E+10 | 24400.97 | 26-FEB-14:25 | 26.35 | 19.91 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.270792E+10 | 27903.58 | 26-MAR-14:35 | 25.87 | 20.06 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.965400E+10 | 54413.32 | 21-APR-17:06 | 29.90 | 20.06 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.233980E+11 | 55107.52 | 03-MAY-17:42 | 31.20 | 21.90 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.274918E+11 | 54501.25 | 12-JUN-17:05 | 32.02 | 21.32 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.286440E+11 | 52366.73 | 12-JUL-17:08 | 23.90 | 22.65 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.283325E+11 | 52066.51 | 30-AUG-17:42 | 33.73 | 23.71 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.217348E+11 | 51808.20 | 22-SEP-17:06 | 30.32 | 21.05 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.181991E+11 | 57490.68 | 01-OCT-14:53 | 28.00 | 18.51 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.445179E+10 | 50152.22 | 05-NOV-14:13 | 27.20 | 20.50 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.269207E+10 | 22502.72 | 10-DEC-14:45 | 27.83 | 20.04 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.170246E+12 | 0.00 | ||||||||
Minimum of Months | 0.103153E+10 | 22502.72 | 23.90 | 18.11 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.286440E+11 | 57490.68 | 33.73 | 23.71 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 | 23.10 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 14.12 | 12.36 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 24.22 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.626220E+09 | 27134.43 | 11-JAN-06:01 | 8.00 |
February | 0.362594E+09 | 27205.33 | 07-FEB-06:01 | 8.62 |
March | 0.270393E+09 | 26960.54 | 13-MAR-05:01 | 6.68 |
April | 12961523.19 | 1691.01 | 11-APR-06:30 | 10.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 4032351.14 | 652.63 | 31-OCT-06:10 | 18.00 |
November | 35397282.73 | 4742.48 | 15-NOV-07:10 | 7.80 |
December | 0.342803E+09 | 26762.65 | 22-DEC-06:02 | 10.00 |
Annual Sum or Average | 0.165440E+10 | |||
Minimum of Months | 0.00 | 0.00 | 6.68 | |
Maximum of Months | 0.626220E+09 | 27205.33 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.545423E+09 | 21954.15 | 10-JAN-05:50 | 2.67 |
February | 0.591383E+09 | 56749.02 | 05-FEB-07:43 | -3.4 |
March | 0.310203E+09 | 15235.80 | 12-MAR-06:55 | 6.60 |
April | 39348711.05 | 961.23 | 01-APR-06:50 | 20.60 |
May | 2602811.48 | 1955.68 | 01-MAY-06:05 | 25.18 |
June | 4428203.34 | 2118.97 | 15-JUN-06:07 | 25.37 |
July | 896148.80 | 2266.02 | 18-JUL-06:05 | 24.27 |
August | 1461008.31 | 1340.33 | 16-AUG-06:10 | 23.92 |
September | 2266199.46 | 2086.62 | 01-SEP-06:05 | 23.83 |
October | 29756471.07 | 1158.14 | 21-OCT-06:10 | 23.95 |
November | 0.214169E+09 | 2349.10 | 24-NOV-16:10 | 23.43 |
December | 0.318987E+09 | 56950.94 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.206092E+10 | |||
Minimum of Months | 896148.80 | 961.23 | -3.4 | |
Maximum of Months | 0.591383E+09 | 56950.94 | 25.37 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.256100E+10 | 1939.55 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.233575E+10 | 1939.55 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.266872E+10 | 1939.55 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.252182E+10 | 1939.55 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.261486E+10 | 1939.55 | 01-MAY-07:10 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.257569E+10 | 1939.55 | 01-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.256100E+10 | 1939.55 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.266872E+10 | 1939.55 | 01-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.252182E+10 | 1939.55 | 01-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.256100E+10 | 1939.55 | 02-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.246796E+10 | 1939.55 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.256100E+10 | 1939.55 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.306193E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.233575E+10 | 1939.55 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.266872E+10 | 1939.55 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112294E+11 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102778E+11 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.118738E+11 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.111270E+11 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.115516E+11 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.114492E+11 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112294E+11 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.118738E+11 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.111270E+11 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112294E+11 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108048E+11 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112294E+11 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135003E+12 | ||||
Minimum of Months | 0.102778E+11 | 10075.60 | 0.00 | 0.00 | |
Maximum of Months | 0.118738E+11 | 10075.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.258277E+11 | 23173.88 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.236390E+11 | 23173.88 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.273097E+11 | 23173.88 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.255921E+11 | 23173.88 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.265687E+11 | 23173.88 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.263332E+11 | 23173.88 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.258277E+11 | 23173.88 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.273097E+11 | 23173.88 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.255921E+11 | 23173.88 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.258277E+11 | 23173.88 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.248511E+11 | 23173.88 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.258277E+11 | 23173.88 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.236390E+11 | 23173.88 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.273097E+11 | 23173.88 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13438864.32 | 0.157815E+10 |
February | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22723908.41 | 0.106248E+10 |
March | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59112076.43 | 0.122438E+10 |
April | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181776E+09 | 0.502952E+09 |
May | 0.565842E+09 | 0.261486E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.603852E+09 | 92812917.31 |
June | 0.565842E+09 | 0.257569E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708524E+09 | 73453638.50 |
July | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640638E+09 | 55078811.45 |
August | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716307E+09 | 0.106290E+09 |
September | 0.544079E+09 | 0.252182E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381168E+09 | 0.156013E+09 |
October | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401747E+09 | 0.419168E+09 |
November | 0.522316E+09 | 0.246796E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97971529.71 | 0.778683E+09 |
December | 0.544079E+09 | 0.256100E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46174240.85 | 0.133216E+10 |
Annual Sum or Average | 0.659424E+10 | 0.306193E+11 | 0.319458E+11 | 0.387343E+10 | 0.738162E+10 | ||||
Minimum of Months | 0.500553E+09 | 0.233575E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13438864.32 | 55078811.45 |
Maximum of Months | 0.587605E+09 | 0.266872E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716307E+09 | 0.157815E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9616715.45 | 0.816610E+10 |
February | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10973463.52 | 0.611661E+10 |
March | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27615568.22 | 0.756718E+10 |
April | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204723E+09 | 0.405817E+10 |
May | 0.00 | 0.115516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106298E+10 | 0.125045E+10 |
June | 0.00 | 0.114492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122992E+10 | 0.807801E+09 |
July | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148396E+10 | 0.492337E+09 |
August | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158181E+10 | 0.119961E+10 |
September | 0.00 | 0.111270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103462E+10 | 0.184663E+10 |
October | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.888677E+09 | 0.408606E+10 |
November | 0.00 | 0.108048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47605707.48 | 0.527701E+10 |
December | 0.00 | 0.112294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25633468.50 | 0.752600E+10 |
Annual Sum or Average | 0.135003E+12 | 0.760813E+10 | 0.483939E+11 | ||||||
Minimum of Months | 0.00 | 0.102778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9616715.45 | 0.492337E+09 |
Maximum of Months | 0.00 | 0.118738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158181E+10 | 0.816610E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358928E+09 | 0.256506E+11 |
February | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307691E+09 | 0.184886E+11 |
March | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190008E+09 | 0.249327E+11 |
April | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3024804.29 | 0.165751E+11 |
May | 0.00 | 0.265687E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16676527.62 | 0.100927E+11 |
June | 0.00 | 0.263332E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6882276.44 | 0.659936E+10 |
July | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18586824.79 | 0.590787E+10 |
August | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52611557.82 | 0.956936E+10 |
September | 0.00 | 0.255921E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59636954.22 | 0.124577E+11 |
October | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5287269.66 | 0.214617E+11 |
November | 0.00 | 0.248511E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41472781.22 | 0.196291E+11 |
December | 0.00 | 0.258277E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158101E+09 | 0.263362E+11 |
Annual Sum or Average | 0.310507E+12 | 0.107336E+12 | 0.121891E+10 | 0.197701E+12 | |||||
Minimum of Months | 0.00 | 0.236390E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3024804.29 | 0.590787E+10 |
Maximum of Months | 0.00 | 0.273097E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358928E+09 | 0.263362E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1939.55 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 736.47 | 02-JAN-13:00 | 8344.88 | 05-JAN-08:00 |
February | 659.25 | 01-FEB-08:09 | 1939.55 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1617.72 | 02-FEB-13:00 | 7818.21 | 17-FEB-07:10 |
March | 659.25 | 01-MAR-08:09 | 1939.55 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1566.19 | 30-MAR-12:00 | 8432.22 | 09-MAR-07:10 |
April | 659.25 | 01-APR-07:10 | 1939.55 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3032.11 | 28-APR-16:10 | 5075.46 | 11-APR-06:03 |
May | 659.25 | 01-MAY-07:10 | 1939.55 | 01-MAY-07:10 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3331.88 | 10-MAY-16:10 | 678.40 | 02-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1939.55 | 01-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3438.85 | 28-JUN-16:10 | 975.63 | 07-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 1939.55 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4086.43 | 21-JUL-16:10 | 368.69 | 13-JUL-11:10 |
August | 659.25 | 01-AUG-07:10 | 1939.55 | 01-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4402.85 | 03-AUG-16:10 | 803.06 | 16-AUG-17:00 |
September | 659.25 | 01-SEP-07:10 | 1939.55 | 01-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3052.54 | 06-SEP-16:10 | 1571.67 | 07-SEP-17:00 |
October | 659.25 | 02-OCT-07:10 | 1939.55 | 02-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3257.34 | 05-OCT-17:00 | 3884.88 | 27-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1939.55 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1925.63 | 02-NOV-12:00 | 5424.39 | 09-NOV-07:03 |
December | 659.25 | 01-DEC-08:09 | 1939.55 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1472.79 | 13-DEC-13:00 | 8536.55 | 20-DEC-08:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 736.47 | 368.69 | |||||
Maximum of Months | 659.25 | 1939.55 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4402.85 | 8536.55 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 10075.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.41 | 16-JAN-15:00 | 14573.12 | 03-JAN-09:00 |
February | 0.00 | 10075.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 897.07 | 20-FEB-15:00 | 18019.76 | 16-FEB-18:00 |
March | 0.00 | 10075.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1617.98 | 27-MAR-15:10 | 15366.30 | 09-MAR-09:00 |
April | 0.00 | 10075.60 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4486.61 | 28-APR-15:10 | 11870.15 | 15-APR-17:00 |
May | 0.00 | 10075.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4826.74 | 18-MAY-16:35 | 3644.06 | 05-MAY-06:10 |
June | 0.00 | 10075.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6649.86 | 08-JUN-15:10 | 4504.85 | 06-JUN-20:00 |
July | 0.00 | 10075.60 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6094.78 | 06-JUL-15:10 | 2455.37 | 30-JUL-11:10 |
August | 0.00 | 10075.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7681.70 | 03-AUG-16:40 | 4745.23 | 25-AUG-24:00 |
September | 0.00 | 10075.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7366.44 | 09-SEP-17:00 | 4715.76 | 19-SEP-19:00 |
October | 0.00 | 10075.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6844.00 | 09-OCT-14:00 | 10474.70 | 27-OCT-08:00 |
November | 0.00 | 10075.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1599.66 | 02-NOV-15:10 | 10879.24 | 09-NOV-07:03 |
December | 0.00 | 10075.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 954.11 | 13-DEC-16:10 | 12400.83 | 30-DEC-16:05 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.41 | 2455.37 | |||
Maximum of Months | 0.00 | 10075.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7681.70 | 18019.76 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 23173.88 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5478.34 | 16-JAN-15:00 | 47646.70 | 03-JAN-09:00 |
February | 0.00 | 23173.88 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8872.19 | 02-FEB-13:10 | 54774.07 | 04-FEB-11:00 |
March | 0.00 | 23173.88 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4950.70 | 26-MAR-13:55 | 52772.11 | 09-MAR-09:00 |
April | 0.00 | 23173.88 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1146.51 | 15-APR-12:00 | 34613.06 | 01-APR-16:00 |
May | 0.00 | 23173.88 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1775.57 | 27-MAY-13:53 | 26222.18 | 26-MAY-15:00 |
June | 0.00 | 23173.88 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 678.77 | 25-JUN-12:52 | 20406.23 | 01-JUN-13:00 |
July | 0.00 | 23173.88 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1839.79 | 02-JUL-10:45 | 25957.72 | 31-JUL-11:00 |
August | 0.00 | 23173.88 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2236.58 | 20-AUG-13:55 | 19151.43 | 25-AUG-24:00 |
September | 0.00 | 23173.88 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2035.74 | 09-SEP-17:00 | 21030.48 | 14-SEP-17:55 |
October | 0.00 | 23173.88 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1189.63 | 08-OCT-13:43 | 40745.63 | 27-OCT-11:00 |
November | 0.00 | 23173.88 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4224.91 | 28-NOV-13:10 | 37029.90 | 09-NOV-08:10 |
December | 0.00 | 23173.88 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3025.45 | 13-DEC-15:00 | 46840.79 | 19-DEC-12:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 678.77 | 19151.43 | ||||
Maximum of Months | 0.00 | 23173.88 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 8872.19 | 54774.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16996.14 | 02-JAN-06:02 | 435.11 | 3476.08 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563.08 |
February | 17180.86 | 27-FEB-06:02 | 362.59 | 2896.74 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 354.27 |
March | 16339.63 | 30-MAR-05:01 | 507.62 | 4055.43 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.29 |
April | 20949.04 | 18-APR-05:02 | 362.59 | 2896.74 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.78 |
May | 18011.98 | 05-MAY-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.34 |
June | 18170.20 | 14-JUN-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.19 |
July | 16714.10 | 19-JUL-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.58 |
August | 19234.99 | 31-AUG-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.41 |
September | 17402.12 | 01-SEP-05:01 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.90 |
October | 21269.87 | 27-OCT-05:02 | 435.11 | 3476.08 | 3442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 913.61 |
November | 17911.37 | 06-NOV-06:01 | 652.66 | 5214.12 | 5163.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.70 |
December | 15369.62 | 16-DEC-06:01 | 507.62 | 4055.43 | 4016.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.89 |
Annual Sum or Average | |||||||||||
Minimum of Months | 15369.62 | 362.59 | 2896.74 | 2868.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.58 | |
Maximum of Months | 21269.87 | 725.17 | 5793.47 | 5737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 913.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26027.42 | 01-JAN-14:15 | 0.00 | 2370.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.20 |
February | 24400.97 | 26-FEB-14:25 | 0.00 | 2370.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.91 |
March | 27903.58 | 26-MAR-14:35 | 0.00 | 2370.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.84 |
April | 54413.32 | 21-APR-17:06 | 0.00 | 5926.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.25 | 0.00 |
May | 55107.52 | 03-MAY-17:42 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 54501.25 | 12-JUN-17:05 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 849.29 | 0.00 |
July | 52366.73 | 12-JUL-17:08 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.56 |
August | 52066.51 | 30-AUG-17:42 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 664.57 | 0.00 |
September | 51808.20 | 22-SEP-17:06 | 0.00 | 5926.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1695.99 | 0.00 |
October | 57490.68 | 01-OCT-14:53 | 0.00 | 4741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.68 | 0.00 |
November | 50152.22 | 05-NOV-14:13 | 0.00 | 3556.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.33 | 0.00 |
December | 22502.72 | 10-DEC-14:45 | 0.00 | 2370.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.41 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 22502.72 | 0.00 | 2370.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 57490.68 | 0.00 | 7112.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1695.99 | 517.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8249.72 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3613.16 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6599.40 |
April | 0.00 | 01-APR-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7312.79 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4699.54 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3033.13 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2836.22 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4659.64 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.25 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9571.08 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4404.39 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 2726.34 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9390.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 2726.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.25 | |
Maximum of Months | 0.00 | 0.00 | 5452.68 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9571.08 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.701990E+11 | 58848.72 | 19-JAN-15:09 | 0.918599E+10 | 36740.04 | 10-JAN-07:10 |
February | 0.646037E+11 | 60946.01 | 27-FEB-15:09 | 0.811810E+10 | 36810.04 | 06-FEB-07:10 |
March | 0.740984E+11 | 61771.77 | 28-MAR-12:09 | 0.844531E+10 | 18551.34 | 09-MAR-07:10 |
April | 0.738303E+11 | 71381.40 | 28-APR-14:00 | 0.777892E+10 | 6102.96 | 11-APR-06:30 |
May | 0.871470E+11 | 72047.52 | 25-MAY-14:09 | 0.803520E+10 | 3000.00 | 01-MAY-00:10 |
June | 0.888449E+11 | 73799.73 | 28-JUN-14:39 | 0.777600E+10 | 3000.00 | 01-JUN-00:10 |
July | 0.900267E+11 | 74781.66 | 19-JUL-13:09 | 0.803520E+10 | 3000.00 | 01-JUL-00:10 |
August | 0.934378E+11 | 75295.13 | 03-AUG-14:00 | 0.803520E+10 | 3000.00 | 01-AUG-00:10 |
September | 0.847937E+11 | 72957.05 | 09-SEP-14:50 | 0.777600E+10 | 3000.00 | 01-SEP-00:10 |
October | 0.828421E+11 | 73698.60 | 07-OCT-12:00 | 0.803520E+10 | 3000.00 | 01-OCT-00:10 |
November | 0.706408E+11 | 68225.04 | 02-NOV-14:30 | 0.781449E+10 | 9302.44 | 15-NOV-07:19 |
December | 0.718346E+11 | 63835.89 | 15-DEC-13:00 | 0.864741E+10 | 31511.92 | 21-DEC-07:19 |
Annual Sum or Average | 0.952299E+12 | 0.976830E+11 | ||||
Minimum of Months | 0.646037E+11 | 58848.72 | 0.777600E+10 | 3000.00 | ||
Maximum of Months | 0.934378E+11 | 75295.13 | 0.918599E+10 | 36810.04 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.396181E+11 | 0.118609E+11 | 0.115358E+11 | 0.00 | 0.432445E+10 | 0.00 | 0.00 | 0.799490E+09 | 0.00 | 0.00 | 0.00 | 0.206025E+10 | 0.00 |
February | 0.362526E+11 | 0.102440E+11 | 0.105871E+11 | 0.00 | 0.398337E+10 | 0.00 | 0.00 | 0.167124E+10 | 0.00 | 0.00 | 0.00 | 0.186542E+10 | 0.00 |
March | 0.418523E+11 | 0.106352E+11 | 0.123357E+11 | 0.00 | 0.466755E+10 | 0.00 | 0.00 | 0.253278E+10 | 0.00 | 0.00 | 0.00 | 0.207492E+10 | 0.00 |
April | 0.392410E+11 | 0.960754E+10 | 0.114862E+11 | 0.00 | 0.478754E+10 | 0.00 | 0.00 | 0.677197E+10 | 0.00 | 0.00 | 0.00 | 0.193610E+10 | 0.00 |
May | 0.407352E+11 | 0.931055E+10 | 0.119357E+11 | 0.00 | 0.708123E+10 | 0.00 | 0.00 | 0.161260E+11 | 0.00 | 0.00 | 0.00 | 0.195829E+10 | 0.00 |
June | 0.403581E+11 | 0.867413E+10 | 0.118862E+11 | 0.00 | 0.778466E+10 | 0.00 | 0.00 | 0.182669E+11 | 0.00 | 0.00 | 0.00 | 0.187502E+10 | 0.00 |
July | 0.396181E+11 | 0.914083E+10 | 0.115358E+11 | 0.00 | 0.799536E+10 | 0.00 | 0.00 | 0.198547E+11 | 0.00 | 0.00 | 0.00 | 0.188192E+10 | 0.00 |
August | 0.418523E+11 | 0.964054E+10 | 0.123357E+11 | 0.00 | 0.791595E+10 | 0.00 | 0.00 | 0.197657E+11 | 0.00 | 0.00 | 0.00 | 0.192770E+10 | 0.00 |
September | 0.392410E+11 | 0.100035E+11 | 0.114862E+11 | 0.00 | 0.654525E+10 | 0.00 | 0.00 | 0.156471E+11 | 0.00 | 0.00 | 0.00 | 0.187056E+10 | 0.00 |
October | 0.396181E+11 | 0.110548E+11 | 0.115358E+11 | 0.00 | 0.595346E+10 | 0.00 | 0.00 | 0.127224E+11 | 0.00 | 0.00 | 0.00 | 0.195753E+10 | 0.00 |
November | 0.381239E+11 | 0.112952E+11 | 0.110862E+11 | 0.00 | 0.426130E+10 | 0.00 | 0.00 | 0.393945E+10 | 0.00 | 0.00 | 0.00 | 0.193464E+10 | 0.00 |
December | 0.396181E+11 | 0.120165E+11 | 0.115358E+11 | 0.00 | 0.432104E+10 | 0.00 | 0.00 | 0.230210E+10 | 0.00 | 0.00 | 0.00 | 0.204106E+10 | 0.00 |
Annual Sum or Average | 0.476129E+12 | 0.123484E+12 | 0.139282E+12 | 0.696212E+11 | 0.00 | 0.120400E+12 | 0.233834E+11 | ||||||
Minimum of Months | 0.362526E+11 | 0.867413E+10 | 0.105871E+11 | 0.00 | 0.398337E+10 | 0.00 | 0.00 | 0.799490E+09 | 0.00 | 0.00 | 0.00 | 0.186542E+10 | 0.00 |
Maximum of Months | 0.418523E+11 | 0.120165E+11 | 0.123357E+11 | 0.00 | 0.799536E+10 | 0.00 | 0.00 | 0.198547E+11 | 0.00 | 0.00 | 0.00 | 0.207492E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.918599E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.811810E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.844531E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.777892E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.803520E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.777600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.803520E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.803520E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.777600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.803520E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.781449E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.864741E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.976830E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.777600E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.918599E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35189.04 | 02-JAN-09:09 | 7857.00 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 4349.61 | 02-JAN-10:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 35189.04 | 01-FEB-09:09 | 7857.00 | 01-FEB-00:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 4349.61 | 01-FEB-13:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 35189.04 | 01-MAR-09:09 | 7857.00 | 01-MAR-00:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 4349.61 | 02-MAR-11:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35189.04 | 01-APR-08:09 | 7857.00 | 01-APR-00:10 | 10112.62 | 01-APR-07:10 | 0.00 | 6654.90 | 14-APR-14:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 35189.04 | 01-MAY-08:09 | 7857.00 | 01-MAY-00:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 6654.90 | 01-MAY-09:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 35189.04 | 01-JUN-08:09 | 7857.00 | 01-JUN-00:10 | 10112.62 | 01-JUN-07:10 | 0.00 | 6654.90 | 01-JUN-13:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 35189.04 | 01-JUL-08:09 | 7857.00 | 01-JUL-00:10 | 10112.62 | 01-JUL-07:10 | 0.00 | 6654.90 | 01-JUL-08:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 35189.04 | 01-AUG-08:09 | 7857.00 | 01-AUG-00:10 | 10112.62 | 01-AUG-07:10 | 0.00 | 6654.90 | 01-AUG-09:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 35189.04 | 01-SEP-08:09 | 7857.00 | 01-SEP-00:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 6654.90 | 18-SEP-08:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 35189.04 | 02-OCT-08:09 | 7857.00 | 01-OCT-00:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 6654.90 | 02-OCT-16:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 35189.04 | 01-NOV-08:09 | 7857.00 | 01-NOV-00:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 6654.90 | 03-NOV-14:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 35189.04 | 01-DEC-09:09 | 7857.00 | 01-DEC-00:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 4349.61 | 01-DEC-11:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 35189.04 | 7857.00 | 10112.62 | 0.00 | 4349.61 | 0.00 | 0.00 | |||||
Maximum of Months | 35189.04 | 7857.00 | 10112.62 | 0.00 | 6654.90 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 7469.36 | 19-JAN-14:00 | 0.00 | 0.00 | 0.00 | 1774.94 | 23-JAN-12:20 | 0.00 |
February | 9607.26 | 27-FEB-14:00 | 0.00 | 0.00 | 0.00 | 1774.11 | 01-FEB-12:00 | 0.00 |
March | 10693.29 | 28-MAR-11:00 | 0.00 | 0.00 | 0.00 | 1767.04 | 01-MAR-12:39 | 0.00 |
April | 18678.92 | 28-APR-15:39 | 0.00 | 0.00 | 0.00 | 1751.35 | 01-APR-11:09 | 0.00 |
May | 18959.77 | 25-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1733.11 | 01-MAY-11:50 | 0.00 |
June | 21280.22 | 28-JUN-15:30 | 0.00 | 0.00 | 0.00 | 1715.90 | 01-JUN-11:30 | 0.00 |
July | 22054.53 | 18-JUL-15:50 | 0.00 | 0.00 | 0.00 | 1705.18 | 01-JUL-11:30 | 0.00 |
August | 23853.30 | 03-AUG-16:10 | 0.00 | 0.00 | 0.00 | 1709.50 | 31-AUG-11:20 | 0.00 |
September | 22872.17 | 09-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1723.34 | 30-SEP-11:00 | 0.00 |
October | 21159.80 | 06-OCT-11:00 | 0.00 | 0.00 | 0.00 | 1742.12 | 31-OCT-11:39 | 0.00 |
November | 14580.88 | 07-NOV-12:00 | 0.00 | 0.00 | 0.00 | 1759.59 | 30-NOV-12:20 | 0.00 |
December | 12451.28 | 15-DEC-13:00 | 0.00 | 0.00 | 0.00 | 1771.61 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7469.36 | 0.00 | 0.00 | 0.00 | 1705.18 | 0.00 | ||
Maximum of Months | 23853.30 | 0.00 | 0.00 | 0.00 | 1774.94 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 58848.72 | 19-JAN-15:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4349.61 | 0.00 | 0.00 | 7457.18 | 0.00 |
February | 60946.01 | 27-FEB-15:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4349.61 | 0.00 | 0.00 | 9559.68 | 0.00 |
March | 61771.77 | 28-MAR-12:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4349.61 | 0.00 | 0.00 | 10397.51 | 0.00 |
April | 71381.40 | 28-APR-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6654.90 | 0.00 | 0.00 | 17718.13 | 0.00 |
May | 72047.52 | 25-MAY-14:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6654.90 | 0.00 | 0.00 | 18397.02 | 0.00 |
June | 73799.73 | 28-JUN-14:39 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6654.90 | 0.00 | 0.00 | 20160.81 | 0.00 |
July | 74781.66 | 19-JUL-13:09 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6654.90 | 0.00 | 0.00 | 21167.35 | 0.00 |
August | 75295.13 | 03-AUG-14:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6654.90 | 0.00 | 0.00 | 21658.55 | 0.00 |
September | 72957.05 | 09-SEP-14:50 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6654.90 | 0.00 | 0.00 | 19312.18 | 0.00 |
October | 73698.60 | 07-OCT-12:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6654.90 | 0.00 | 0.00 | 20041.54 | 0.00 |
November | 68225.04 | 02-NOV-14:30 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6654.90 | 0.00 | 0.00 | 14554.06 | 0.00 |
December | 63835.89 | 15-DEC-13:00 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4349.61 | 0.00 | 0.00 | 12451.28 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 58848.72 | 35189.04 | 10112.62 | 0.00 | 0.00 | 4349.61 | 0.00 | 0.00 | 7457.18 | 0.00 | |
Maximum of Months | 75295.13 | 35189.04 | 10112.62 | 0.00 | 0.00 | 6654.90 | 0.00 | 0.00 | 21658.55 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 36740.04 | 10-JAN-07:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 36810.04 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 18551.34 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 6102.96 | 11-APR-06:30 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 3000.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 3000.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 3000.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 3000.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 3000.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 3000.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 9302.44 | 15-NOV-07:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 31511.92 | 21-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 3000.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 36810.04 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 20.40 | 1.50 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.67 | 20.32 | 0.67 | 20.32 | 0.17 | 24.52 | 0.17 | 24.52 |
March | 0.67 | 20.40 | 0.67 | 20.40 | 0.17 | 24.48 | 0.17 | 24.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.61 | 1.33 | 24.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 24.97 | 8.50 | 24.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 25.14 | 8.50 | 24.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 25.61 | 8.17 | 25.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 25.38 | 9.17 | 25.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 25.53 | 8.50 | 25.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 25.26 | 6.00 | 24.99 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.61 | 1.00 | 24.61 |
December | 0.17 | 20.16 | 0.17 | 20.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.00 | 20.37 | 3.00 | 20.37 | 54.67 | 25.29 | 51.50 | 25.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 20.40 | 1.50 | 20.40 | 9.67 | 25.61 | 9.17 | 25.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.00 | 0.00 |
February | 1.00 | 14.92 | 0.00 | 0.00 | 0.17 | 27.30 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.45 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 27.55 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 28.50 | 27.56 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 27.58 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 27.54 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 27.63 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 27.60 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.33 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 14.92 | 0.00 | 173.67 | 27.57 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 14.92 | 0.00 | 0.00 | 36.33 | 27.63 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 248.67 | 22.69 | 102.50 | 22.25 | 69.83 | 21.48 |
February | 173.17 | 22.89 | 102.50 | 23.03 | 38.33 | 21.57 |
March | 179.17 | 22.94 | 127.67 | 23.28 | 33.33 | 21.54 |
April | 42.67 | 23.58 | 217.17 | 23.91 | 8.50 | 24.01 |
May | 30.83 | 24.15 | 312.00 | 23.93 | 30.83 | 24.15 |
June | 31.00 | 24.15 | 312.00 | 23.93 | 31.00 | 24.15 |
July | 46.50 | 24.14 | 300.00 | 23.94 | 46.50 | 24.14 |
August | 51.17 | 24.14 | 324.00 | 23.94 | 51.17 | 24.14 |
September | 42.33 | 24.13 | 300.00 | 23.94 | 42.33 | 24.13 |
October | 35.83 | 24.05 | 265.67 | 23.93 | 26.50 | 24.13 |
November | 95.33 | 23.45 | 121.83 | 23.91 | 10.50 | 23.98 |
December | 204.00 | 22.91 | 122.00 | 23.21 | 46.67 | 22.10 |
Annual Sum or Average | 1180.67 | 23.18 | 2607.33 | 23.76 | 435.50 | 23.06 |
Minimum of Months | 30.83 | 22.69 | 102.50 | 22.25 | 8.50 | 21.48 |
Maximum of Months | 248.67 | 24.15 | 324.00 | 23.94 | 69.83 | 24.15 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.204801E+10 | 0.544634E+09 | 135.36 | 0.152861E+10 | 0.519404E+09 | 0.00 | 1.00 | 02-JAN-06:02 | 0.00 | 01-JAN-00:10 | 25550.92 | 02-JAN-06:02 | 17823.20 | 02-JAN-06:02 | 8624.76 | 20-JAN-06:03 | 5948.13 | 02-JAN-06:02 | 0.00 | 01-JAN-00:10 |
February | 0.321870E+10 | 0.853856E+09 | 166.43 | 0.237723E+10 | 0.841478E+09 | 0.00 | 1.00 | 03-FEB-06:03 | 0.00 | 01-FEB-00:10 | 27022.24 | 03-FEB-06:03 | 18512.32 | 27-FEB-06:02 | 12287.17 | 03-FEB-06:03 | 6194.10 | 03-FEB-06:03 | 0.00 | 01-FEB-00:10 |
March | 0.460086E+10 | 0.122294E+10 | 217.37 | 0.350853E+10 | 0.109233E+10 | 0.00 | 1.00 | 01-MAR-06:03 | 0.00 | 01-MAR-00:10 | 27196.39 | 07-MAR-06:02 | 17647.17 | 30-MAR-05:01 | 11686.38 | 07-MAR-06:02 | 6221.06 | 07-MAR-06:02 | 0.00 | 01-MAR-00:10 |
April | 0.835784E+10 | 0.224183E+10 | 273.66 | 0.644553E+10 | 0.191231E+10 | 0.00 | 1.00 | 01-APR-05:02 | 0.00 | 01-APR-00:10 | 28037.04 | 29-APR-05:01 | 22538.17 | 18-APR-05:02 | 11577.93 | 29-APR-05:05 | 6344.79 | 29-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.149455E+11 | 0.405095E+10 | 314.69 | 0.105759E+11 | 0.436964E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 29766.99 | 23-MAY-05:01 | 19248.89 | 05-MAY-05:01 | 15202.18 | 23-MAY-05:02 | 6604.94 | 24-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.159436E+11 | 0.435550E+10 | 314.71 | 0.112764E+11 | 0.466725E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 29361.58 | 05-JUN-05:01 | 19580.54 | 14-JUN-05:01 | 13465.73 | 05-JUN-05:06 | 6518.41 | 05-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.164785E+11 | 0.445311E+10 | 307.57 | 0.111066E+11 | 0.537193E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:05 | 29859.20 | 31-JUL-05:01 | 18336.90 | 19-JUL-05:01 | 15257.15 | 03-JUL-05:05 | 6642.95 | 03-JUL-05:01 | 0.00 | 01-JUL-00:05 |
August | 0.176372E+11 | 0.473913E+10 | 328.93 | 0.119904E+11 | 0.564683E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 29901.75 | 11-AUG-05:01 | 20567.37 | 31-AUG-05:01 | 15102.27 | 11-AUG-05:04 | 6642.95 | 14-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.150877E+11 | 0.397916E+10 | 311.00 | 0.101767E+11 | 0.491100E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 29989.71 | 05-SEP-05:01 | 18703.86 | 01-SEP-05:01 | 15918.75 | 05-SEP-05:03 | 6957.57 | 10-SEP-11:32 | 0.00 | 01-SEP-00:10 |
October | 0.127401E+11 | 0.339755E+10 | 297.63 | 0.911447E+10 | 0.362565E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 29802.13 | 23-OCT-05:01 | 22266.08 | 27-OCT-05:02 | 15029.22 | 25-OCT-05:05 | 6655.35 | 25-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.643753E+10 | 0.170647E+10 | 246.18 | 0.491393E+10 | 0.152360E+10 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 28301.41 | 02-NOV-05:01 | 18681.68 | 06-NOV-06:01 | 13205.11 | 08-NOV-06:02 | 6381.53 | 02-NOV-05:01 | 0.00 | 01-NOV-00:10 |
December | 0.404087E+10 | 0.107160E+10 | 179.24 | 0.300075E+10 | 0.104012E+10 | 0.00 | 1.00 | 11-DEC-06:02 | 0.00 | 01-DEC-00:10 | 27583.18 | 15-DEC-06:01 | 16533.76 | 16-DEC-06:01 | 11814.07 | 15-DEC-06:04 | 6279.30 | 15-DEC-06:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.121537E+12 | 0.326167E+11 | 3092.78 | 0.860150E+11 | 0.355215E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.204801E+10 | 0.544634E+09 | 135.36 | 0.152861E+10 | 0.519404E+09 | 0.00 | 1.00 | 0.00 | 25550.92 | 16533.76 | 8624.76 | 5948.13 | 0.00 | |||||||
Maximum of Months | 0.176372E+11 | 0.473913E+10 | 328.93 | 0.119904E+11 | 0.564683E+10 | 0.00 | 1.00 | 0.00 | 29989.71 | 22538.17 | 15918.75 | 6957.57 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.885280E+09 | 0.254856E+09 | 27.58 | 0.592903E+09 | 0.292377E+09 | 0.00 | 0.56 | 01-JAN-14:15 | 0.00 | 01-JAN-00:10 | 34646.96 | 01-JAN-14:15 | 28158.00 | 01-JAN-14:15 | 6671.49 | 01-JAN-13:00 | 10176.39 | 01-JAN-14:15 | 0.00 | 01-JAN-00:10 |
February | 0.286254E+10 | 0.817383E+09 | 61.17 | 0.197716E+10 | 0.885371E+09 | 0.00 | 0.55 | 26-FEB-14:25 | 0.00 | 01-FEB-00:10 | 34167.00 | 26-FEB-14:25 | 26592.71 | 26-FEB-14:25 | 7574.29 | 26-FEB-14:25 | 10136.42 | 26-FEB-14:25 | 0.00 | 01-FEB-00:10 |
March | 0.456504E+10 | 0.130984E+10 | 100.25 | 0.312260E+10 | 0.144244E+10 | 0.00 | 0.62 | 26-MAR-14:35 | 0.00 | 01-MAR-00:10 | 40112.06 | 26-MAR-14:35 | 30381.01 | 26-MAR-14:35 | 9731.05 | 26-MAR-14:35 | 11524.25 | 26-MAR-14:35 | 0.00 | 01-MAR-00:10 |
April | 0.155994E+11 | 0.453014E+10 | 231.71 | 0.116217E+11 | 0.397770E+10 | 0.00 | 1.00 | 21-APR-17:06 | 0.00 | 01-APR-00:10 | 79562.73 | 29-APR-17:43 | 60453.40 | 21-APR-17:06 | 29915.76 | 29-APR-17:43 | 20338.50 | 28-APR-17:06 | 0.00 | 01-APR-00:10 |
May | 0.409629E+11 | 0.120750E+11 | 418.54 | 0.284152E+11 | 0.125477E+11 | 0.00 | 1.00 | 02-MAY-17:06 | 0.00 | 01-MAY-00:10 | 84882.62 | 23-MAY-17:10 | 60573.07 | 03-MAY-17:42 | 40669.16 | 23-MAY-17:10 | 21168.56 | 28-MAY-09:13 | 0.00 | 01-MAY-00:10 |
June | 0.469200E+11 | 0.139114E+11 | 455.00 | 0.330881E+11 | 0.138319E+11 | 0.00 | 1.00 | 01-JUN-17:06 | 0.00 | 01-JUN-00:10 | 83010.85 | 17-JUN-05:09 | 60622.57 | 11-JUN-14:53 | 36860.51 | 17-JUN-05:09 | 20945.53 | 20-JUN-17:08 | 0.00 | 01-JUN-00:10 |
July | 0.524332E+11 | 0.154016E+11 | 500.70 | 0.343758E+11 | 0.180574E+11 | 0.00 | 1.00 | 01-JUL-17:08 | 0.00 | 01-JUL-00:23 | 87361.08 | 26-JUL-05:01 | 55997.23 | 12-JUL-17:08 | 46465.14 | 26-JUL-05:01 | 21360.57 | 02-JUL-11:13 | 0.00 | 01-JUL-00:05 |
August | 0.513733E+11 | 0.150265E+11 | 484.63 | 0.340431E+11 | 0.173302E+11 | 0.00 | 1.00 | 01-AUG-17:06 | 0.00 | 01-AUG-00:10 | 85150.98 | 05-AUG-05:05 | 58067.48 | 30-AUG-17:42 | 41544.14 | 05-AUG-05:05 | 21490.40 | 20-AUG-13:43 | 0.00 | 01-AUG-00:10 |
September | 0.405144E+11 | 0.116680E+11 | 401.88 | 0.261106E+11 | 0.144038E+11 | 0.00 | 1.00 | 01-SEP-17:06 | 0.00 | 01-SEP-00:10 | 84256.78 | 04-SEP-10:03 | 57487.14 | 22-SEP-17:06 | 40191.02 | 04-SEP-10:03 | 22027.41 | 09-SEP-22:23 | 0.00 | 01-SEP-00:10 |
October | 0.322900E+11 | 0.932488E+10 | 337.27 | 0.216779E+11 | 0.106121E+11 | 0.00 | 1.00 | 01-OCT-12:13 | 0.00 | 01-OCT-00:10 | 87682.36 | 25-OCT-05:01 | 61422.93 | 01-OCT-14:53 | 49497.55 | 25-OCT-05:01 | 21632.67 | 08-OCT-13:43 | 0.00 | 01-OCT-00:10 |
November | 0.779436E+10 | 0.223298E+10 | 146.24 | 0.542023E+10 | 0.237414E+10 | 0.00 | 1.00 | 05-NOV-13:33 | 0.00 | 01-NOV-00:10 | 76114.01 | 05-NOV-13:33 | 55161.89 | 05-NOV-14:13 | 24400.56 | 03-NOV-17:10 | 19635.99 | 05-NOV-13:33 | 0.00 | 01-NOV-00:10 |
December | 0.429456E+10 | 0.123050E+10 | 77.67 | 0.288348E+10 | 0.141108E+10 | 0.00 | 0.53 | 10-DEC-14:45 | 0.00 | 01-DEC-00:10 | 33451.76 | 10-DEC-14:45 | 24903.10 | 10-DEC-14:45 | 10831.10 | 15-DEC-12:00 | 10146.01 | 10-DEC-14:45 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.300495E+12 | 0.877831E+11 | 3242.62 | 0.203329E+12 | 0.971662E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.885280E+09 | 0.254856E+09 | 27.58 | 0.592903E+09 | 0.292377E+09 | 0.00 | 0.53 | 0.00 | 33451.76 | 24903.10 | 6671.49 | 10136.42 | 0.00 | |||||||
Maximum of Months | 0.524332E+11 | 0.154016E+11 | 500.70 | 0.343758E+11 | 0.180574E+11 | 0.00 | 1.00 | 0.00 | 87682.36 | 61422.93 | 49497.55 | 22027.41 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 59.34 | 32.09 | 27.25 | 94.62 | 122.61 | 1.83 | 0.00 | 744.00 |
February | 67.08 | 33.92 | 33.16 | 111.10 | 106.14 | 0.00 | 0.00 | 672.00 |
March | 66.11 | 29.20 | 36.91 | 114.36 | 96.95 | 0.00 | 0.00 | 744.00 |
April | 81.85 | 37.45 | 44.40 | 160.08 | 71.77 | 0.00 | 0.00 | 720.00 |
May | 68.39 | 22.25 | 46.14 | 166.64 | 31.16 | 0.00 | 0.00 | 744.00 |
June | 76.02 | 26.70 | 49.33 | 190.74 | 29.09 | 0.00 | 0.00 | 720.00 |
July | 69.37 | 19.27 | 50.10 | 170.32 | 23.79 | 0.00 | 0.00 | 744.00 |
August | 70.03 | 21.32 | 48.70 | 174.18 | 30.02 | 0.00 | 0.00 | 744.00 |
September | 64.51 | 22.10 | 42.42 | 149.96 | 38.28 | 0.00 | 0.00 | 720.00 |
October | 65.91 | 28.38 | 37.53 | 147.27 | 55.85 | 0.00 | 0.00 | 744.00 |
November | 56.77 | 28.58 | 28.18 | 100.59 | 96.96 | 0.00 | 0.00 | 720.00 |
December | 54.67 | 29.15 | 25.52 | 90.61 | 113.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.63 | 27.47 | 39.16 | 139.31 | 67.83 | 1.83 | 0.00 | 8760.00 |
Minimum of Months | 54.67 | 19.27 | 25.52 | 90.61 | 23.79 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.85 | 37.45 | 50.10 | 190.74 | 122.61 | 1.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 59.34 | 32.09 | 27.25 | 94.62 | 122.61 | 1.83 | 0.00 | 744.00 |
February | 67.08 | 33.92 | 33.16 | 111.10 | 106.14 | 0.00 | 0.00 | 672.00 |
March | 66.11 | 29.20 | 36.91 | 114.36 | 96.95 | 0.00 | 0.00 | 744.00 |
April | 81.85 | 37.45 | 44.40 | 160.08 | 71.77 | 0.00 | 0.00 | 720.00 |
May | 68.39 | 22.25 | 46.14 | 166.64 | 31.16 | 0.00 | 0.00 | 744.00 |
June | 76.02 | 26.70 | 49.33 | 190.74 | 29.09 | 0.00 | 0.00 | 720.00 |
July | 69.37 | 19.27 | 50.10 | 170.32 | 23.79 | 0.00 | 0.00 | 744.00 |
August | 70.03 | 21.32 | 48.70 | 174.18 | 30.02 | 0.00 | 0.00 | 744.00 |
September | 64.51 | 22.10 | 42.42 | 149.96 | 38.28 | 0.00 | 0.00 | 720.00 |
October | 65.91 | 28.38 | 37.53 | 147.27 | 55.85 | 0.00 | 0.00 | 744.00 |
November | 56.77 | 28.58 | 28.18 | 100.59 | 96.96 | 0.00 | 0.00 | 720.00 |
December | 54.67 | 29.15 | 25.52 | 90.61 | 113.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.63 | 27.47 | 39.16 | 139.31 | 67.83 | 1.83 | 0.00 | 8760.00 |
Minimum of Months | 54.67 | 19.27 | 25.52 | 90.61 | 23.79 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.85 | 37.45 | 50.10 | 190.74 | 122.61 | 1.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.64 | 0.00 | 12.64 | 10.38 | 77.70 | 2.00 | 0.00 | 744.00 |
February | 14.91 | 0.00 | 14.91 | 13.95 | 66.27 | 0.00 | 0.00 | 672.00 |
March | 17.31 | 0.00 | 17.31 | 20.30 | 59.35 | 0.00 | 0.00 | 744.00 |
April | 20.52 | 0.17 | 20.35 | 31.16 | 43.40 | 0.00 | 0.00 | 720.00 |
May | 23.40 | 1.10 | 22.30 | 55.90 | 17.65 | 0.00 | 0.00 | 744.00 |
June | 26.66 | 2.18 | 24.48 | 66.89 | 16.52 | 0.00 | 0.00 | 720.00 |
July | 25.75 | 1.19 | 24.56 | 63.64 | 13.69 | 0.00 | 0.00 | 744.00 |
August | 23.02 | 0.31 | 22.71 | 58.51 | 17.24 | 0.00 | 0.00 | 744.00 |
September | 19.76 | 0.01 | 19.75 | 45.04 | 22.70 | 0.00 | 0.00 | 720.00 |
October | 17.16 | 0.00 | 17.16 | 35.35 | 33.79 | 0.00 | 0.00 | 744.00 |
November | 13.03 | 0.00 | 13.03 | 14.18 | 59.76 | 0.00 | 0.00 | 720.00 |
December | 11.75 | 0.00 | 11.75 | 10.34 | 71.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 18.84 | 0.41 | 18.43 | 35.61 | 41.51 | 2.00 | 0.00 | 8760.00 |
Minimum of Months | 11.75 | 0.00 | 11.75 | 10.34 | 13.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 26.66 | 2.18 | 24.56 | 66.89 | 77.70 | 2.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.64 | 0.00 | 12.64 | 10.38 | 77.70 | 2.00 | 0.00 | 744.00 |
February | 14.91 | 0.00 | 14.91 | 13.95 | 66.27 | 0.00 | 0.00 | 672.00 |
March | 17.31 | 0.00 | 17.30 | 20.30 | 59.35 | 0.00 | 0.00 | 744.00 |
April | 20.52 | 0.17 | 20.35 | 31.16 | 43.40 | 0.00 | 0.00 | 720.00 |
May | 23.40 | 1.10 | 22.30 | 55.90 | 17.65 | 0.00 | 0.00 | 744.00 |
June | 26.66 | 2.18 | 24.48 | 66.89 | 16.52 | 0.00 | 0.00 | 720.00 |
July | 25.75 | 1.19 | 24.56 | 63.64 | 13.69 | 0.00 | 0.00 | 744.00 |
August | 23.02 | 0.31 | 22.71 | 58.51 | 17.24 | 0.00 | 0.00 | 744.00 |
September | 19.76 | 0.01 | 19.75 | 45.04 | 22.70 | 0.00 | 0.00 | 720.00 |
October | 17.16 | 0.00 | 17.16 | 35.35 | 33.79 | 0.00 | 0.00 | 744.00 |
November | 13.03 | 0.00 | 13.03 | 14.18 | 59.75 | 0.00 | 0.00 | 720.00 |
December | 11.75 | 0.00 | 11.75 | 10.34 | 71.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 18.84 | 0.41 | 18.43 | 35.60 | 41.51 | 2.00 | 0.00 | 8760.00 |
Minimum of Months | 11.75 | 0.00 | 11.75 | 10.34 | 13.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 26.66 | 2.18 | 24.56 | 66.89 | 77.70 | 2.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.88 | 29.44 | 14.44 | 68.84 | 47.36 | 63.17 | 0.00 | 744.00 |
February | 55.35 | 37.99 | 17.35 | 88.86 | 42.19 | 105.67 | 0.00 | 672.00 |
March | 60.70 | 37.80 | 22.90 | 98.77 | 40.66 | 22.50 | 0.00 | 744.00 |
April | 76.99 | 50.00 | 26.98 | 126.79 | 38.89 | 2.00 | 0.00 | 720.00 |
May | 73.80 | 42.09 | 31.72 | 127.09 | 25.85 | 1.17 | 0.00 | 744.00 |
June | 81.45 | 46.96 | 34.49 | 143.75 | 25.38 | 3.50 | 0.00 | 720.00 |
July | 75.88 | 38.97 | 36.91 | 131.12 | 22.85 | 7.83 | 0.00 | 744.00 |
August | 70.91 | 35.49 | 35.42 | 123.57 | 25.25 | 14.50 | 0.00 | 744.00 |
September | 60.54 | 30.13 | 30.41 | 102.19 | 29.28 | 2.00 | 0.00 | 720.00 |
October | 57.58 | 34.20 | 23.38 | 97.13 | 34.78 | 21.67 | 0.00 | 744.00 |
November | 46.82 | 32.01 | 14.81 | 71.95 | 47.35 | 28.00 | 0.00 | 720.00 |
December | 39.84 | 26.37 | 13.47 | 60.75 | 47.81 | 31.83 | 0.00 | 744.00 |
Annual Sum or Average | 61.98 | 36.75 | 25.24 | 103.44 | 35.59 | 303.83 | 0.00 | 8760.00 |
Minimum of Months | 39.84 | 26.37 | 13.47 | 60.75 | 22.85 | 1.17 | 0.00 | 672.00 |
Maximum of Months | 81.45 | 50.00 | 36.91 | 143.75 | 47.81 | 105.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.88 | 29.44 | 14.44 | 68.84 | 47.36 | 63.17 | 0.00 | 744.00 |
February | 55.35 | 37.99 | 17.35 | 88.86 | 42.19 | 105.67 | 0.00 | 672.00 |
March | 60.70 | 37.80 | 22.90 | 98.77 | 40.66 | 22.50 | 0.00 | 744.00 |
April | 76.99 | 50.00 | 26.98 | 126.79 | 38.89 | 2.00 | 0.00 | 720.00 |
May | 73.80 | 42.09 | 31.72 | 127.09 | 25.85 | 1.17 | 0.00 | 744.00 |
June | 81.45 | 46.96 | 34.49 | 143.75 | 25.38 | 3.50 | 0.00 | 720.00 |
July | 75.88 | 38.97 | 36.91 | 131.12 | 22.85 | 7.83 | 0.00 | 744.00 |
August | 70.91 | 35.49 | 35.42 | 123.57 | 25.25 | 14.50 | 0.00 | 744.00 |
September | 60.54 | 30.13 | 30.41 | 102.19 | 29.28 | 2.00 | 0.00 | 720.00 |
October | 57.58 | 34.20 | 23.38 | 97.13 | 34.78 | 21.67 | 0.00 | 744.00 |
November | 46.82 | 32.01 | 14.81 | 71.95 | 47.35 | 28.00 | 0.00 | 720.00 |
December | 39.84 | 26.37 | 13.47 | 60.75 | 47.81 | 31.83 | 0.00 | 744.00 |
Annual Sum or Average | 61.98 | 36.75 | 25.24 | 103.44 | 35.59 | 303.83 | 0.00 | 8760.00 |
Minimum of Months | 39.84 | 26.37 | 13.47 | 60.75 | 22.85 | 1.17 | 0.00 | 672.00 |
Maximum of Months | 81.45 | 50.00 | 36.91 | 143.75 | 47.81 | 105.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.88 | 29.44 | 14.44 | 68.84 | 47.36 | 63.17 | 0.00 | 744.00 |
February | 55.35 | 37.99 | 17.35 | 88.86 | 42.19 | 105.67 | 0.00 | 672.00 |
March | 60.70 | 37.80 | 22.90 | 98.77 | 40.66 | 22.50 | 0.00 | 744.00 |
April | 76.99 | 50.00 | 26.98 | 126.79 | 38.89 | 2.00 | 0.00 | 720.00 |
May | 73.80 | 42.09 | 31.72 | 127.09 | 25.85 | 1.17 | 0.00 | 744.00 |
June | 81.45 | 46.96 | 34.49 | 143.75 | 25.38 | 3.50 | 0.00 | 720.00 |
July | 75.88 | 38.97 | 36.91 | 131.12 | 22.85 | 7.83 | 0.00 | 744.00 |
August | 70.91 | 35.49 | 35.42 | 123.57 | 25.25 | 14.50 | 0.00 | 744.00 |
September | 60.54 | 30.13 | 30.41 | 102.19 | 29.28 | 2.00 | 0.00 | 720.00 |
October | 57.58 | 34.20 | 23.38 | 97.13 | 34.78 | 21.67 | 0.00 | 744.00 |
November | 46.82 | 32.01 | 14.81 | 71.95 | 47.35 | 28.00 | 0.00 | 720.00 |
December | 39.84 | 26.37 | 13.47 | 60.75 | 47.81 | 31.83 | 0.00 | 744.00 |
Annual Sum or Average | 61.98 | 36.75 | 25.24 | 103.44 | 35.59 | 303.83 | 0.00 | 8760.00 |
Minimum of Months | 39.84 | 26.37 | 13.47 | 60.75 | 22.85 | 1.17 | 0.00 | 672.00 |
Maximum of Months | 81.45 | 50.00 | 36.91 | 143.75 | 47.81 | 105.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.88 | 29.44 | 14.44 | 68.84 | 47.36 | 63.17 | 0.00 | 744.00 |
February | 55.35 | 37.99 | 17.35 | 88.86 | 42.19 | 105.67 | 0.00 | 672.00 |
March | 60.70 | 37.80 | 22.90 | 98.77 | 40.66 | 22.50 | 0.00 | 744.00 |
April | 76.99 | 50.00 | 26.98 | 126.79 | 38.89 | 2.00 | 0.00 | 720.00 |
May | 73.80 | 42.09 | 31.72 | 127.09 | 25.85 | 1.17 | 0.00 | 744.00 |
June | 81.45 | 46.96 | 34.49 | 143.75 | 25.38 | 3.50 | 0.00 | 720.00 |
July | 75.88 | 38.97 | 36.91 | 131.12 | 22.85 | 7.83 | 0.00 | 744.00 |
August | 70.91 | 35.49 | 35.42 | 123.57 | 25.25 | 14.50 | 0.00 | 744.00 |
September | 60.54 | 30.13 | 30.41 | 102.19 | 29.28 | 2.00 | 0.00 | 720.00 |
October | 57.58 | 34.20 | 23.38 | 97.13 | 34.78 | 21.67 | 0.00 | 744.00 |
November | 46.82 | 32.01 | 14.81 | 71.95 | 47.35 | 28.00 | 0.00 | 720.00 |
December | 39.84 | 26.37 | 13.47 | 60.75 | 47.81 | 31.83 | 0.00 | 744.00 |
Annual Sum or Average | 61.98 | 36.75 | 25.24 | 103.44 | 35.59 | 303.83 | 0.00 | 8760.00 |
Minimum of Months | 39.84 | 26.37 | 13.47 | 60.75 | 22.85 | 1.17 | 0.00 | 672.00 |
Maximum of Months | 81.45 | 50.00 | 36.91 | 143.75 | 47.81 | 105.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.88 | 29.44 | 14.44 | 68.84 | 47.36 | 63.17 | 0.00 | 744.00 |
February | 55.35 | 37.99 | 17.35 | 88.86 | 42.19 | 105.67 | 0.00 | 672.00 |
March | 60.70 | 37.80 | 22.90 | 98.77 | 40.66 | 22.50 | 0.00 | 744.00 |
April | 76.99 | 50.00 | 26.98 | 126.79 | 38.89 | 2.00 | 0.00 | 720.00 |
May | 73.80 | 42.09 | 31.72 | 127.09 | 25.85 | 1.17 | 0.00 | 744.00 |
June | 81.45 | 46.96 | 34.49 | 143.75 | 25.38 | 3.50 | 0.00 | 720.00 |
July | 75.88 | 38.97 | 36.91 | 131.12 | 22.85 | 7.83 | 0.00 | 744.00 |
August | 70.91 | 35.49 | 35.42 | 123.57 | 25.25 | 14.50 | 0.00 | 744.00 |
September | 60.54 | 30.13 | 30.41 | 102.19 | 29.28 | 2.00 | 0.00 | 720.00 |
October | 57.58 | 34.20 | 23.38 | 97.13 | 34.78 | 21.67 | 0.00 | 744.00 |
November | 46.82 | 32.01 | 14.81 | 71.95 | 47.35 | 28.00 | 0.00 | 720.00 |
December | 39.84 | 26.37 | 13.47 | 60.75 | 47.81 | 31.83 | 0.00 | 744.00 |
Annual Sum or Average | 61.98 | 36.75 | 25.24 | 103.44 | 35.59 | 303.83 | 0.00 | 8760.00 |
Minimum of Months | 39.84 | 26.37 | 13.47 | 60.75 | 22.85 | 1.17 | 0.00 | 672.00 |
Maximum of Months | 81.45 | 50.00 | 36.91 | 143.75 | 47.81 | 105.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.88 | 29.44 | 14.44 | 68.84 | 47.36 | 63.17 | 0.00 | 744.00 |
February | 55.35 | 37.99 | 17.35 | 88.86 | 42.19 | 105.67 | 0.00 | 672.00 |
March | 60.70 | 37.80 | 22.90 | 98.77 | 40.66 | 22.50 | 0.00 | 744.00 |
April | 76.99 | 50.00 | 26.98 | 126.79 | 38.89 | 2.00 | 0.00 | 720.00 |
May | 73.80 | 42.09 | 31.72 | 127.09 | 25.85 | 1.17 | 0.00 | 744.00 |
June | 81.45 | 46.96 | 34.49 | 143.75 | 25.38 | 3.50 | 0.00 | 720.00 |
July | 75.88 | 38.97 | 36.91 | 131.12 | 22.85 | 7.83 | 0.00 | 744.00 |
August | 70.91 | 35.49 | 35.42 | 123.57 | 25.25 | 14.50 | 0.00 | 744.00 |
September | 60.54 | 30.13 | 30.41 | 102.19 | 29.28 | 2.00 | 0.00 | 720.00 |
October | 57.58 | 34.20 | 23.38 | 97.13 | 34.78 | 21.67 | 0.00 | 744.00 |
November | 46.82 | 32.01 | 14.81 | 71.95 | 47.35 | 28.00 | 0.00 | 720.00 |
December | 39.84 | 26.37 | 13.47 | 60.75 | 47.81 | 31.83 | 0.00 | 744.00 |
Annual Sum or Average | 61.98 | 36.75 | 25.24 | 103.44 | 35.59 | 303.83 | 0.00 | 8760.00 |
Minimum of Months | 39.84 | 26.37 | 13.47 | 60.75 | 22.85 | 1.17 | 0.00 | 672.00 |
Maximum of Months | 81.45 | 50.00 | 36.91 | 143.75 | 47.81 | 105.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.88 | 29.44 | 14.44 | 68.84 | 47.36 | 63.17 | 0.00 | 744.00 |
February | 55.35 | 37.99 | 17.35 | 88.86 | 42.19 | 105.67 | 0.00 | 672.00 |
March | 60.70 | 37.80 | 22.90 | 98.77 | 40.66 | 22.50 | 0.00 | 744.00 |
April | 76.99 | 50.00 | 26.98 | 126.79 | 38.89 | 2.00 | 0.00 | 720.00 |
May | 73.80 | 42.09 | 31.72 | 127.09 | 25.85 | 1.17 | 0.00 | 744.00 |
June | 81.45 | 46.96 | 34.49 | 143.75 | 25.38 | 3.50 | 0.00 | 720.00 |
July | 75.88 | 38.97 | 36.91 | 131.12 | 22.85 | 7.83 | 0.00 | 744.00 |
August | 70.91 | 35.49 | 35.42 | 123.57 | 25.25 | 14.50 | 0.00 | 744.00 |
September | 60.54 | 30.13 | 30.41 | 102.19 | 29.28 | 2.00 | 0.00 | 720.00 |
October | 57.58 | 34.20 | 23.38 | 97.13 | 34.78 | 21.67 | 0.00 | 744.00 |
November | 46.82 | 32.01 | 14.81 | 71.95 | 47.35 | 28.00 | 0.00 | 720.00 |
December | 39.84 | 26.37 | 13.47 | 60.75 | 47.81 | 31.83 | 0.00 | 744.00 |
Annual Sum or Average | 61.98 | 36.75 | 25.24 | 103.44 | 35.59 | 303.83 | 0.00 | 8760.00 |
Minimum of Months | 39.84 | 26.37 | 13.47 | 60.75 | 22.85 | 1.17 | 0.00 | 672.00 |
Maximum of Months | 81.45 | 50.00 | 36.91 | 143.75 | 47.81 | 105.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.88 | 29.44 | 14.44 | 68.84 | 47.36 | 63.17 | 0.00 | 744.00 |
February | 55.35 | 37.99 | 17.35 | 88.86 | 42.19 | 105.67 | 0.00 | 672.00 |
March | 60.70 | 37.80 | 22.90 | 98.77 | 40.66 | 22.50 | 0.00 | 744.00 |
April | 76.99 | 50.00 | 26.98 | 126.79 | 38.89 | 2.00 | 0.00 | 720.00 |
May | 73.80 | 42.09 | 31.72 | 127.09 | 25.85 | 1.17 | 0.00 | 744.00 |
June | 81.45 | 46.96 | 34.49 | 143.75 | 25.38 | 3.50 | 0.00 | 720.00 |
July | 75.88 | 38.97 | 36.91 | 131.12 | 22.85 | 7.83 | 0.00 | 744.00 |
August | 70.91 | 35.49 | 35.42 | 123.57 | 25.25 | 14.50 | 0.00 | 744.00 |
September | 60.54 | 30.13 | 30.41 | 102.19 | 29.28 | 2.00 | 0.00 | 720.00 |
October | 57.58 | 34.20 | 23.38 | 97.13 | 34.78 | 21.67 | 0.00 | 744.00 |
November | 46.82 | 32.01 | 14.81 | 71.95 | 47.35 | 28.00 | 0.00 | 720.00 |
December | 39.84 | 26.37 | 13.47 | 60.75 | 47.81 | 31.83 | 0.00 | 744.00 |
Annual Sum or Average | 61.98 | 36.75 | 25.24 | 103.44 | 35.59 | 303.83 | 0.00 | 8760.00 |
Minimum of Months | 39.84 | 26.37 | 13.47 | 60.75 | 22.85 | 1.17 | 0.00 | 672.00 |
Maximum of Months | 81.45 | 50.00 | 36.91 | 143.75 | 47.81 | 105.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.88 | 29.44 | 14.44 | 68.84 | 47.36 | 63.17 | 0.00 | 744.00 |
February | 55.35 | 37.99 | 17.35 | 88.86 | 42.19 | 105.67 | 0.00 | 672.00 |
March | 60.70 | 37.80 | 22.90 | 98.77 | 40.66 | 22.50 | 0.00 | 744.00 |
April | 76.99 | 50.00 | 26.98 | 126.79 | 38.89 | 2.00 | 0.00 | 720.00 |
May | 73.80 | 42.09 | 31.72 | 127.09 | 25.85 | 1.17 | 0.00 | 744.00 |
June | 81.45 | 46.96 | 34.49 | 143.75 | 25.38 | 3.50 | 0.00 | 720.00 |
July | 75.88 | 38.97 | 36.91 | 131.12 | 22.85 | 7.83 | 0.00 | 744.00 |
August | 70.91 | 35.49 | 35.42 | 123.57 | 25.25 | 14.50 | 0.00 | 744.00 |
September | 60.54 | 30.13 | 30.41 | 102.19 | 29.28 | 2.00 | 0.00 | 720.00 |
October | 57.58 | 34.20 | 23.38 | 97.13 | 34.78 | 21.67 | 0.00 | 744.00 |
November | 46.82 | 32.01 | 14.81 | 71.95 | 47.35 | 28.00 | 0.00 | 720.00 |
December | 39.84 | 26.37 | 13.47 | 60.75 | 47.81 | 31.83 | 0.00 | 744.00 |
Annual Sum or Average | 61.98 | 36.75 | 25.24 | 103.44 | 35.59 | 303.83 | 0.00 | 8760.00 |
Minimum of Months | 39.84 | 26.37 | 13.47 | 60.75 | 22.85 | 1.17 | 0.00 | 672.00 |
Maximum of Months | 81.45 | 50.00 | 36.91 | 143.75 | 47.81 | 105.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.88 | 29.44 | 14.44 | 68.84 | 47.36 | 63.17 | 0.00 | 744.00 |
February | 55.35 | 37.99 | 17.35 | 88.86 | 42.19 | 105.67 | 0.00 | 672.00 |
March | 60.70 | 37.80 | 22.90 | 98.77 | 40.66 | 22.50 | 0.00 | 744.00 |
April | 76.99 | 50.00 | 26.98 | 126.79 | 38.89 | 2.00 | 0.00 | 720.00 |
May | 73.80 | 42.09 | 31.72 | 127.09 | 25.85 | 1.17 | 0.00 | 744.00 |
June | 81.45 | 46.96 | 34.49 | 143.75 | 25.38 | 3.50 | 0.00 | 720.00 |
July | 75.88 | 38.97 | 36.91 | 131.12 | 22.85 | 7.83 | 0.00 | 744.00 |
August | 70.91 | 35.49 | 35.42 | 123.57 | 25.25 | 14.50 | 0.00 | 744.00 |
September | 60.54 | 30.13 | 30.41 | 102.19 | 29.28 | 2.00 | 0.00 | 720.00 |
October | 57.58 | 34.20 | 23.38 | 97.13 | 34.78 | 21.67 | 0.00 | 744.00 |
November | 46.82 | 32.01 | 14.81 | 71.95 | 47.35 | 28.00 | 0.00 | 720.00 |
December | 39.84 | 26.37 | 13.47 | 60.75 | 47.81 | 31.83 | 0.00 | 744.00 |
Annual Sum or Average | 61.98 | 36.75 | 25.24 | 103.44 | 35.59 | 303.83 | 0.00 | 8760.00 |
Minimum of Months | 39.84 | 26.37 | 13.47 | 60.75 | 22.85 | 1.17 | 0.00 | 672.00 |
Maximum of Months | 81.45 | 50.00 | 36.91 | 143.75 | 47.81 | 105.67 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158942E+09 | 85956566.93 | 72985498.66 | 0.253441E+09 | 0.328411E+09 |
February | 0.162283E+09 | 82058444.83 | 80224115.42 | 0.268781E+09 | 0.256765E+09 |
March | 0.177070E+09 | 78203010.93 | 98866754.38 | 0.306297E+09 | 0.259662E+09 |
April | 0.212156E+09 | 97063708.52 | 0.115092E+09 | 0.414916E+09 | 0.186023E+09 |
May | 0.183181E+09 | 59591310.41 | 0.123590E+09 | 0.446320E+09 | 83454271.37 |
June | 0.197048E+09 | 69196449.51 | 0.127852E+09 | 0.494386E+09 | 75395709.81 |
July | 0.185795E+09 | 51610424.16 | 0.134184E+09 | 0.456184E+09 | 63721322.24 |
August | 0.187557E+09 | 57111991.93 | 0.130445E+09 | 0.466532E+09 | 80402104.58 |
September | 0.167220E+09 | 57270784.81 | 0.109949E+09 | 0.388688E+09 | 99220208.65 |
October | 0.176532E+09 | 76024645.26 | 0.100507E+09 | 0.394453E+09 | 0.149597E+09 |
November | 0.147137E+09 | 74088443.52 | 73048996.70 | 0.260718E+09 | 0.251316E+09 |
December | 0.146426E+09 | 78083806.79 | 68341911.33 | 0.242683E+09 | 0.304974E+09 |
Annual Sum or Average | 0.210135E+10 | 0.866260E+09 | 0.123509E+10 | 0.439340E+10 | 0.213894E+10 |
Minimum of Months | 0.146426E+09 | 51610424.16 | 68341911.33 | 0.242683E+09 | 63721322.24 |
Maximum of Months | 0.212156E+09 | 97063708.52 | 0.134184E+09 | 0.494386E+09 | 0.328411E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158942E+09 | 85956566.93 | 72985498.66 | 0.253441E+09 | 0.328411E+09 |
February | 0.162283E+09 | 82058444.83 | 80224115.42 | 0.268781E+09 | 0.256765E+09 |
March | 0.177070E+09 | 78203010.93 | 98866754.38 | 0.306297E+09 | 0.259662E+09 |
April | 0.212156E+09 | 97063708.52 | 0.115092E+09 | 0.414916E+09 | 0.186023E+09 |
May | 0.183181E+09 | 59591310.41 | 0.123590E+09 | 0.446320E+09 | 83454271.37 |
June | 0.197048E+09 | 69196449.51 | 0.127852E+09 | 0.494386E+09 | 75395709.81 |
July | 0.185795E+09 | 51610424.16 | 0.134184E+09 | 0.456184E+09 | 63721322.24 |
August | 0.187557E+09 | 57111991.93 | 0.130445E+09 | 0.466532E+09 | 80402104.58 |
September | 0.167220E+09 | 57270784.81 | 0.109949E+09 | 0.388688E+09 | 99220208.65 |
October | 0.176532E+09 | 76024645.26 | 0.100507E+09 | 0.394453E+09 | 0.149597E+09 |
November | 0.147137E+09 | 74088443.52 | 73048996.70 | 0.260718E+09 | 0.251316E+09 |
December | 0.146426E+09 | 78083806.79 | 68341911.33 | 0.242683E+09 | 0.304974E+09 |
Annual Sum or Average | 0.210135E+10 | 0.866260E+09 | 0.123509E+10 | 0.439340E+10 | 0.213894E+10 |
Minimum of Months | 0.146426E+09 | 51610424.16 | 68341911.33 | 0.242683E+09 | 63721322.24 |
Maximum of Months | 0.212156E+09 | 97063708.52 | 0.134184E+09 | 0.494386E+09 | 0.328411E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33861408.58 | 0.00 | 33861408.58 | 27798156.62 | 0.208116E+09 |
February | 36082321.66 | 0.00 | 36082321.66 | 33758459.00 | 0.160312E+09 |
March | 46354484.78 | 3575.08 | 46350909.71 | 54380857.06 | 0.158959E+09 |
April | 53198617.36 | 441072.73 | 52757544.64 | 80776080.97 | 0.112505E+09 |
May | 62679542.69 | 2951194.12 | 59728348.57 | 0.149717E+09 | 47270350.39 |
June | 69097649.92 | 5642484.26 | 63455165.66 | 0.173379E+09 | 42808804.05 |
July | 68960463.16 | 3179366.13 | 65781097.03 | 0.170453E+09 | 36663983.51 |
August | 61645724.73 | 829306.48 | 60816418.25 | 0.156709E+09 | 46169848.14 |
September | 51209845.83 | 15623.79 | 51194222.04 | 0.116740E+09 | 58830129.87 |
October | 45957508.77 | 0.00 | 45957508.77 | 94674698.61 | 90496061.61 |
November | 33763655.28 | 0.00 | 33763655.28 | 36765528.95 | 0.154886E+09 |
December | 31478029.14 | 0.00 | 31478029.14 | 27693697.85 | 0.192027E+09 |
Annual Sum or Average | 0.594289E+09 | 13062622.59 | 0.581227E+09 | 0.112284E+10 | 0.130904E+10 |
Minimum of Months | 31478029.14 | 0.00 | 31478029.14 | 27693697.85 | 36663983.51 |
Maximum of Months | 69097649.92 | 5642484.26 | 65781097.03 | 0.173379E+09 | 0.208116E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33860475.71 | 0.00 | 33860475.71 | 27797218.81 | 0.208115E+09 |
February | 36081361.95 | 0.00 | 36081361.95 | 33757532.33 | 0.160311E+09 |
March | 46353172.74 | 3574.91 | 46349597.83 | 54379253.67 | 0.158959E+09 |
April | 53197174.13 | 441052.05 | 52756122.07 | 80774112.95 | 0.112504E+09 |
May | 62677642.39 | 2951055.80 | 59726586.59 | 0.149714E+09 | 47269592.28 |
June | 69095517.18 | 5642219.79 | 63453297.39 | 0.173375E+09 | 42808014.82 |
July | 68958301.19 | 3179217.11 | 65779084.08 | 0.170449E+09 | 36663190.88 |
August | 61643840.91 | 829267.61 | 60814573.31 | 0.156705E+09 | 46169080.65 |
September | 51208284.33 | 15623.05 | 51192661.28 | 0.116737E+09 | 58829310.15 |
October | 45956183.62 | 0.00 | 45956183.62 | 94672536.46 | 90495208.67 |
November | 33762741.30 | 0.00 | 33762741.30 | 36764549.05 | 0.154884E+09 |
December | 31477154.35 | 0.00 | 31477154.35 | 27692906.84 | 0.192026E+09 |
Annual Sum or Average | 0.594272E+09 | 13062010.32 | 0.581210E+09 | 0.112282E+10 | 0.130903E+10 |
Minimum of Months | 31477154.35 | 0.00 | 31477154.35 | 27692906.84 | 36663190.88 |
Maximum of Months | 69095517.18 | 5642219.79 | 65779084.08 | 0.173375E+09 | 0.208115E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117541E+09 | 78865132.61 | 38675439.19 | 0.184390E+09 | 0.126861E+09 |
February | 0.133897E+09 | 91911783.94 | 41985034.95 | 0.214965E+09 | 0.102063E+09 |
March | 0.162574E+09 | 0.101242E+09 | 61332179.13 | 0.264538E+09 | 0.108907E+09 |
April | 0.199551E+09 | 0.129607E+09 | 69944062.53 | 0.328634E+09 | 0.100806E+09 |
May | 0.197678E+09 | 0.112732E+09 | 84945709.35 | 0.340399E+09 | 69240819.88 |
June | 0.211128E+09 | 0.121718E+09 | 89409373.27 | 0.372607E+09 | 65785267.52 |
July | 0.203250E+09 | 0.104386E+09 | 98864058.96 | 0.351196E+09 | 61188339.46 |
August | 0.189933E+09 | 95058865.74 | 94874118.80 | 0.330982E+09 | 67634050.32 |
September | 0.156912E+09 | 78098578.46 | 78813253.77 | 0.264870E+09 | 75882263.41 |
October | 0.154223E+09 | 91589178.83 | 62634099.71 | 0.260152E+09 | 93156471.23 |
November | 0.121358E+09 | 82962602.10 | 38395687.19 | 0.186496E+09 | 0.122742E+09 |
December | 0.106712E+09 | 70621859.57 | 36089792.90 | 0.162703E+09 | 0.128053E+09 |
Annual Sum or Average | 0.195476E+10 | 0.115879E+10 | 0.795963E+09 | 0.326193E+10 | 0.112232E+10 |
Minimum of Months | 0.106712E+09 | 70621859.57 | 36089792.90 | 0.162703E+09 | 61188339.46 |
Maximum of Months | 0.211128E+09 | 0.129607E+09 | 98864058.96 | 0.372607E+09 | 0.128053E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117541E+09 | 78865132.61 | 38675439.19 | 0.184390E+09 | 0.126861E+09 |
February | 0.133897E+09 | 91911783.94 | 41985034.95 | 0.214965E+09 | 0.102063E+09 |
March | 0.162574E+09 | 0.101242E+09 | 61332179.13 | 0.264538E+09 | 0.108907E+09 |
April | 0.199551E+09 | 0.129607E+09 | 69944062.53 | 0.328634E+09 | 0.100806E+09 |
May | 0.197678E+09 | 0.112732E+09 | 84945709.35 | 0.340399E+09 | 69240819.88 |
June | 0.211128E+09 | 0.121718E+09 | 89409373.27 | 0.372607E+09 | 65785267.52 |
July | 0.203250E+09 | 0.104386E+09 | 98864058.96 | 0.351196E+09 | 61188339.46 |
August | 0.189933E+09 | 95058865.74 | 94874118.80 | 0.330982E+09 | 67634050.32 |
September | 0.156912E+09 | 78098578.46 | 78813253.77 | 0.264870E+09 | 75882263.41 |
October | 0.154223E+09 | 91589178.83 | 62634099.71 | 0.260152E+09 | 93156471.23 |
November | 0.121358E+09 | 82962602.10 | 38395687.19 | 0.186496E+09 | 0.122742E+09 |
December | 0.106712E+09 | 70621859.57 | 36089792.90 | 0.162703E+09 | 0.128053E+09 |
Annual Sum or Average | 0.195476E+10 | 0.115879E+10 | 0.795963E+09 | 0.326193E+10 | 0.112232E+10 |
Minimum of Months | 0.106712E+09 | 70621859.57 | 36089792.90 | 0.162703E+09 | 61188339.46 |
Maximum of Months | 0.211128E+09 | 0.129607E+09 | 98864058.96 | 0.372607E+09 | 0.128053E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117541E+09 | 78865132.61 | 38675439.19 | 0.184390E+09 | 0.126861E+09 |
February | 0.133897E+09 | 91911783.94 | 41985034.95 | 0.214965E+09 | 0.102063E+09 |
March | 0.162574E+09 | 0.101242E+09 | 61332179.13 | 0.264538E+09 | 0.108907E+09 |
April | 0.199551E+09 | 0.129607E+09 | 69944062.53 | 0.328634E+09 | 0.100806E+09 |
May | 0.197678E+09 | 0.112732E+09 | 84945709.35 | 0.340399E+09 | 69240819.88 |
June | 0.211128E+09 | 0.121718E+09 | 89409373.27 | 0.372607E+09 | 65785267.52 |
July | 0.203250E+09 | 0.104386E+09 | 98864058.96 | 0.351196E+09 | 61188339.46 |
August | 0.189933E+09 | 95058865.74 | 94874118.80 | 0.330982E+09 | 67634050.32 |
September | 0.156912E+09 | 78098578.46 | 78813253.77 | 0.264870E+09 | 75882263.41 |
October | 0.154223E+09 | 91589178.83 | 62634099.71 | 0.260152E+09 | 93156471.23 |
November | 0.121358E+09 | 82962602.10 | 38395687.19 | 0.186496E+09 | 0.122742E+09 |
December | 0.106712E+09 | 70621859.57 | 36089792.90 | 0.162703E+09 | 0.128053E+09 |
Annual Sum or Average | 0.195476E+10 | 0.115879E+10 | 0.795963E+09 | 0.326193E+10 | 0.112232E+10 |
Minimum of Months | 0.106712E+09 | 70621859.57 | 36089792.90 | 0.162703E+09 | 61188339.46 |
Maximum of Months | 0.211128E+09 | 0.129607E+09 | 98864058.96 | 0.372607E+09 | 0.128053E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117541E+09 | 78865132.61 | 38675439.19 | 0.184390E+09 | 0.126861E+09 |
February | 0.133897E+09 | 91911783.94 | 41985034.95 | 0.214965E+09 | 0.102063E+09 |
March | 0.162574E+09 | 0.101242E+09 | 61332179.13 | 0.264538E+09 | 0.108907E+09 |
April | 0.199551E+09 | 0.129607E+09 | 69944062.53 | 0.328634E+09 | 0.100806E+09 |
May | 0.197678E+09 | 0.112732E+09 | 84945709.35 | 0.340399E+09 | 69240819.88 |
June | 0.211128E+09 | 0.121718E+09 | 89409373.27 | 0.372607E+09 | 65785267.52 |
July | 0.203250E+09 | 0.104386E+09 | 98864058.96 | 0.351196E+09 | 61188339.46 |
August | 0.189933E+09 | 95058865.74 | 94874118.80 | 0.330982E+09 | 67634050.32 |
September | 0.156912E+09 | 78098578.46 | 78813253.77 | 0.264870E+09 | 75882263.41 |
October | 0.154223E+09 | 91589178.83 | 62634099.71 | 0.260152E+09 | 93156471.23 |
November | 0.121358E+09 | 82962602.10 | 38395687.19 | 0.186496E+09 | 0.122742E+09 |
December | 0.106712E+09 | 70621859.57 | 36089792.90 | 0.162703E+09 | 0.128053E+09 |
Annual Sum or Average | 0.195476E+10 | 0.115879E+10 | 0.795963E+09 | 0.326193E+10 | 0.112232E+10 |
Minimum of Months | 0.106712E+09 | 70621859.57 | 36089792.90 | 0.162703E+09 | 61188339.46 |
Maximum of Months | 0.211128E+09 | 0.129607E+09 | 98864058.96 | 0.372607E+09 | 0.128053E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117541E+09 | 78865132.61 | 38675439.19 | 0.184390E+09 | 0.126861E+09 |
February | 0.133897E+09 | 91911783.94 | 41985034.95 | 0.214965E+09 | 0.102063E+09 |
March | 0.162574E+09 | 0.101242E+09 | 61332179.13 | 0.264538E+09 | 0.108907E+09 |
April | 0.199551E+09 | 0.129607E+09 | 69944062.53 | 0.328634E+09 | 0.100806E+09 |
May | 0.197678E+09 | 0.112732E+09 | 84945709.35 | 0.340399E+09 | 69240819.88 |
June | 0.211128E+09 | 0.121718E+09 | 89409373.27 | 0.372607E+09 | 65785267.52 |
July | 0.203250E+09 | 0.104386E+09 | 98864058.96 | 0.351196E+09 | 61188339.46 |
August | 0.189933E+09 | 95058865.74 | 94874118.80 | 0.330982E+09 | 67634050.32 |
September | 0.156912E+09 | 78098578.46 | 78813253.77 | 0.264870E+09 | 75882263.41 |
October | 0.154223E+09 | 91589178.83 | 62634099.71 | 0.260152E+09 | 93156471.23 |
November | 0.121358E+09 | 82962602.10 | 38395687.19 | 0.186496E+09 | 0.122742E+09 |
December | 0.106712E+09 | 70621859.57 | 36089792.90 | 0.162703E+09 | 0.128053E+09 |
Annual Sum or Average | 0.195476E+10 | 0.115879E+10 | 0.795963E+09 | 0.326193E+10 | 0.112232E+10 |
Minimum of Months | 0.106712E+09 | 70621859.57 | 36089792.90 | 0.162703E+09 | 61188339.46 |
Maximum of Months | 0.211128E+09 | 0.129607E+09 | 98864058.96 | 0.372607E+09 | 0.128053E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117541E+09 | 78865132.61 | 38675439.19 | 0.184390E+09 | 0.126861E+09 |
February | 0.133897E+09 | 91911783.94 | 41985034.95 | 0.214965E+09 | 0.102063E+09 |
March | 0.162574E+09 | 0.101242E+09 | 61332179.13 | 0.264538E+09 | 0.108907E+09 |
April | 0.199551E+09 | 0.129607E+09 | 69944062.53 | 0.328634E+09 | 0.100806E+09 |
May | 0.197678E+09 | 0.112732E+09 | 84945709.35 | 0.340399E+09 | 69240819.88 |
June | 0.211128E+09 | 0.121718E+09 | 89409373.27 | 0.372607E+09 | 65785267.52 |
July | 0.203250E+09 | 0.104386E+09 | 98864058.96 | 0.351196E+09 | 61188339.46 |
August | 0.189933E+09 | 95058865.74 | 94874118.80 | 0.330982E+09 | 67634050.32 |
September | 0.156912E+09 | 78098578.46 | 78813253.77 | 0.264870E+09 | 75882263.41 |
October | 0.154223E+09 | 91589178.83 | 62634099.71 | 0.260152E+09 | 93156471.23 |
November | 0.121358E+09 | 82962602.10 | 38395687.19 | 0.186496E+09 | 0.122742E+09 |
December | 0.106712E+09 | 70621859.57 | 36089792.90 | 0.162703E+09 | 0.128053E+09 |
Annual Sum or Average | 0.195476E+10 | 0.115879E+10 | 0.795963E+09 | 0.326193E+10 | 0.112232E+10 |
Minimum of Months | 0.106712E+09 | 70621859.57 | 36089792.90 | 0.162703E+09 | 61188339.46 |
Maximum of Months | 0.211128E+09 | 0.129607E+09 | 98864058.96 | 0.372607E+09 | 0.128053E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117541E+09 | 78865132.61 | 38675439.19 | 0.184390E+09 | 0.126861E+09 |
February | 0.133897E+09 | 91911783.94 | 41985034.95 | 0.214965E+09 | 0.102063E+09 |
March | 0.162574E+09 | 0.101242E+09 | 61332179.13 | 0.264538E+09 | 0.108907E+09 |
April | 0.199551E+09 | 0.129607E+09 | 69944062.53 | 0.328634E+09 | 0.100806E+09 |
May | 0.197678E+09 | 0.112732E+09 | 84945709.35 | 0.340399E+09 | 69240819.88 |
June | 0.211128E+09 | 0.121718E+09 | 89409373.27 | 0.372607E+09 | 65785267.52 |
July | 0.203250E+09 | 0.104386E+09 | 98864058.96 | 0.351196E+09 | 61188339.46 |
August | 0.189933E+09 | 95058865.74 | 94874118.80 | 0.330982E+09 | 67634050.32 |
September | 0.156912E+09 | 78098578.46 | 78813253.77 | 0.264870E+09 | 75882263.41 |
October | 0.154223E+09 | 91589178.83 | 62634099.71 | 0.260152E+09 | 93156471.23 |
November | 0.121358E+09 | 82962602.10 | 38395687.19 | 0.186496E+09 | 0.122742E+09 |
December | 0.106712E+09 | 70621859.57 | 36089792.90 | 0.162703E+09 | 0.128053E+09 |
Annual Sum or Average | 0.195476E+10 | 0.115879E+10 | 0.795963E+09 | 0.326193E+10 | 0.112232E+10 |
Minimum of Months | 0.106712E+09 | 70621859.57 | 36089792.90 | 0.162703E+09 | 61188339.46 |
Maximum of Months | 0.211128E+09 | 0.129607E+09 | 98864058.96 | 0.372607E+09 | 0.128053E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117541E+09 | 78865132.61 | 38675439.19 | 0.184390E+09 | 0.126861E+09 |
February | 0.133897E+09 | 91911783.94 | 41985034.95 | 0.214965E+09 | 0.102063E+09 |
March | 0.162574E+09 | 0.101242E+09 | 61332179.13 | 0.264538E+09 | 0.108907E+09 |
April | 0.199551E+09 | 0.129607E+09 | 69944062.53 | 0.328634E+09 | 0.100806E+09 |
May | 0.197678E+09 | 0.112732E+09 | 84945709.35 | 0.340399E+09 | 69240819.88 |
June | 0.211128E+09 | 0.121718E+09 | 89409373.27 | 0.372607E+09 | 65785267.52 |
July | 0.203250E+09 | 0.104386E+09 | 98864058.96 | 0.351196E+09 | 61188339.46 |
August | 0.189933E+09 | 95058865.74 | 94874118.80 | 0.330982E+09 | 67634050.32 |
September | 0.156912E+09 | 78098578.46 | 78813253.77 | 0.264870E+09 | 75882263.41 |
October | 0.154223E+09 | 91589178.83 | 62634099.71 | 0.260152E+09 | 93156471.23 |
November | 0.121358E+09 | 82962602.10 | 38395687.19 | 0.186496E+09 | 0.122742E+09 |
December | 0.106712E+09 | 70621859.57 | 36089792.90 | 0.162703E+09 | 0.128053E+09 |
Annual Sum or Average | 0.195476E+10 | 0.115879E+10 | 0.795963E+09 | 0.326193E+10 | 0.112232E+10 |
Minimum of Months | 0.106712E+09 | 70621859.57 | 36089792.90 | 0.162703E+09 | 61188339.46 |
Maximum of Months | 0.211128E+09 | 0.129607E+09 | 98864058.96 | 0.372607E+09 | 0.128053E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117541E+09 | 78865132.61 | 38675439.19 | 0.184390E+09 | 0.126861E+09 |
February | 0.133897E+09 | 91911783.94 | 41985034.95 | 0.214965E+09 | 0.102063E+09 |
March | 0.162574E+09 | 0.101242E+09 | 61332179.13 | 0.264538E+09 | 0.108907E+09 |
April | 0.199551E+09 | 0.129607E+09 | 69944062.53 | 0.328634E+09 | 0.100806E+09 |
May | 0.197678E+09 | 0.112732E+09 | 84945709.35 | 0.340399E+09 | 69240819.88 |
June | 0.211128E+09 | 0.121718E+09 | 89409373.27 | 0.372607E+09 | 65785267.52 |
July | 0.203250E+09 | 0.104386E+09 | 98864058.96 | 0.351196E+09 | 61188339.46 |
August | 0.189933E+09 | 95058865.74 | 94874118.80 | 0.330982E+09 | 67634050.32 |
September | 0.156912E+09 | 78098578.46 | 78813253.77 | 0.264870E+09 | 75882263.41 |
October | 0.154223E+09 | 91589178.83 | 62634099.71 | 0.260152E+09 | 93156471.23 |
November | 0.121358E+09 | 82962602.10 | 38395687.19 | 0.186496E+09 | 0.122742E+09 |
December | 0.106712E+09 | 70621859.57 | 36089792.90 | 0.162703E+09 | 0.128053E+09 |
Annual Sum or Average | 0.195476E+10 | 0.115879E+10 | 0.795963E+09 | 0.326193E+10 | 0.112232E+10 |
Minimum of Months | 0.106712E+09 | 70621859.57 | 36089792.90 | 0.162703E+09 | 61188339.46 |
Maximum of Months | 0.211128E+09 | 0.129607E+09 | 98864058.96 | 0.372607E+09 | 0.128053E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117541E+09 | 78865132.61 | 38675439.19 | 0.184390E+09 | 0.126861E+09 |
February | 0.133897E+09 | 91911783.94 | 41985034.95 | 0.214965E+09 | 0.102063E+09 |
March | 0.162574E+09 | 0.101242E+09 | 61332179.13 | 0.264538E+09 | 0.108907E+09 |
April | 0.199551E+09 | 0.129607E+09 | 69944062.53 | 0.328634E+09 | 0.100806E+09 |
May | 0.197678E+09 | 0.112732E+09 | 84945709.35 | 0.340399E+09 | 69240819.88 |
June | 0.211128E+09 | 0.121718E+09 | 89409373.27 | 0.372607E+09 | 65785267.52 |
July | 0.203250E+09 | 0.104386E+09 | 98864058.96 | 0.351196E+09 | 61188339.46 |
August | 0.189933E+09 | 95058865.74 | 94874118.80 | 0.330982E+09 | 67634050.32 |
September | 0.156912E+09 | 78098578.46 | 78813253.77 | 0.264870E+09 | 75882263.41 |
October | 0.154223E+09 | 91589178.83 | 62634099.71 | 0.260152E+09 | 93156471.23 |
November | 0.121358E+09 | 82962602.10 | 38395687.19 | 0.186496E+09 | 0.122742E+09 |
December | 0.106712E+09 | 70621859.57 | 36089792.90 | 0.162703E+09 | 0.128053E+09 |
Annual Sum or Average | 0.195476E+10 | 0.115879E+10 | 0.795963E+09 | 0.326193E+10 | 0.112232E+10 |
Minimum of Months | 0.106712E+09 | 70621859.57 | 36089792.90 | 0.162703E+09 | 61188339.46 |
Maximum of Months | 0.211128E+09 | 0.129607E+09 | 98864058.96 | 0.372607E+09 | 0.128053E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 200.36 | 390.99 | 143.97 | 64.19 | 79.78 | 0.00 | 0.00 |
February | 243.01 | 337.70 | 163.99 | 67.84 | 96.15 | 0.00 | 0.00 |
March | 265.64 | 308.91 | 166.83 | 58.40 | 108.44 | 0.00 | 0.00 |
April | 379.76 | 227.62 | 204.75 | 75.24 | 129.51 | 0.00 | 0.00 |
May | 444.47 | 97.02 | 183.59 | 46.70 | 136.89 | 0.00 | 0.00 |
June | 514.54 | 90.49 | 205.36 | 57.75 | 147.61 | 0.00 | 0.00 |
July | 467.44 | 74.48 | 190.23 | 40.91 | 149.32 | 0.00 | 0.00 |
August | 465.08 | 94.22 | 186.08 | 43.27 | 142.82 | 0.00 | 0.00 |
September | 389.57 | 121.54 | 168.54 | 44.20 | 124.34 | 0.00 | 0.00 |
October | 364.11 | 178.16 | 166.14 | 56.77 | 109.37 | 0.00 | 0.00 |
November | 224.77 | 308.66 | 139.58 | 57.17 | 82.42 | 0.00 | 0.00 |
December | 195.09 | 364.31 | 132.84 | 58.31 | 74.54 | 0.00 | 0.00 |
Annual Sum or Average | 346.66 | 215.49 | 170.96 | 55.77 | 115.19 | 0.00 | 0.00 |
Minimum of Months | 195.09 | 74.48 | 132.84 | 40.91 | 74.54 | 0.00 | 0.00 |
Maximum of Months | 514.54 | 390.99 | 205.36 | 75.24 | 149.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 688.43 | 473.64 | 438.85 | 294.45 | 144.40 | 0.00 | 0.00 |
February | 888.58 | 421.89 | 553.48 | 379.93 | 173.55 | 0.00 | 0.00 |
March | 987.67 | 406.61 | 606.98 | 377.99 | 228.99 | 0.00 | 0.00 |
April | 1267.88 | 388.91 | 769.87 | 500.03 | 269.85 | 0.00 | 0.00 |
May | 1270.91 | 258.51 | 738.04 | 420.89 | 317.15 | 0.00 | 0.00 |
June | 1437.53 | 253.80 | 814.54 | 469.59 | 344.94 | 0.00 | 0.00 |
July | 1311.21 | 228.45 | 758.85 | 389.73 | 369.12 | 0.00 | 0.00 |
August | 1235.74 | 252.51 | 709.13 | 354.91 | 354.22 | 0.00 | 0.00 |
September | 1021.87 | 292.76 | 605.37 | 301.31 | 304.06 | 0.00 | 0.00 |
October | 971.30 | 347.81 | 575.80 | 341.95 | 233.85 | 0.00 | 0.00 |
November | 719.50 | 473.54 | 468.20 | 320.07 | 148.13 | 0.00 | 0.00 |
December | 607.46 | 478.10 | 398.42 | 263.67 | 134.74 | 0.00 | 0.00 |
Annual Sum or Average | 1034.35 | 355.88 | 619.85 | 367.45 | 252.40 | 0.00 | 0.00 |
Minimum of Months | 607.46 | 228.45 | 398.42 | 263.67 | 134.74 | 0.00 | 0.00 |
Maximum of Months | 1437.53 | 478.10 | 814.54 | 500.03 | 369.12 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.536652E+09 | 0.104723E+10 | 0.385606E+09 | 0.171913E+09 | 0.213693E+09 | 0.00 | 0.00 |
February | 0.587888E+09 | 0.816963E+09 | 0.396729E+09 | 0.164117E+09 | 0.232612E+09 | 0.00 | 0.00 |
March | 0.711503E+09 | 0.827391E+09 | 0.446847E+09 | 0.156413E+09 | 0.290434E+09 | 0.00 | 0.00 |
April | 0.984330E+09 | 0.590002E+09 | 0.530708E+09 | 0.195010E+09 | 0.335699E+09 | 0.00 | 0.00 |
May | 0.119047E+10 | 0.259849E+09 | 0.491720E+09 | 0.125085E+09 | 0.366635E+09 | 0.00 | 0.00 |
June | 0.133368E+10 | 0.234561E+09 | 0.532290E+09 | 0.149678E+09 | 0.382613E+09 | 0.00 | 0.00 |
July | 0.125200E+10 | 0.199496E+09 | 0.509508E+09 | 0.109579E+09 | 0.399929E+09 | 0.00 | 0.00 |
August | 0.124568E+10 | 0.252348E+09 | 0.498403E+09 | 0.115883E+09 | 0.382520E+09 | 0.00 | 0.00 |
September | 0.100978E+10 | 0.315023E+09 | 0.436859E+09 | 0.114573E+09 | 0.322286E+09 | 0.00 | 0.00 |
October | 0.975240E+09 | 0.477171E+09 | 0.444977E+09 | 0.152049E+09 | 0.292928E+09 | 0.00 | 0.00 |
November | 0.582603E+09 | 0.800038E+09 | 0.361801E+09 | 0.148177E+09 | 0.213624E+09 | 0.00 | 0.00 |
December | 0.522527E+09 | 0.975774E+09 | 0.355807E+09 | 0.156168E+09 | 0.199639E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109323E+11 | 0.679584E+10 | 0.539126E+10 | 0.175864E+10 | 0.363261E+10 | 0.00 | 0.00 |
Minimum of Months | 0.522527E+09 | 0.199496E+09 | 0.355807E+09 | 0.109579E+09 | 0.199639E+09 | 0.00 | 0.00 |
Maximum of Months | 0.133368E+10 | 0.104723E+10 | 0.532290E+09 | 0.195010E+09 | 0.399929E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.184389E+10 | 0.126860E+10 | 0.117541E+10 | 0.788651E+09 | 0.386754E+09 | 0.00 | 0.00 |
February | 0.214965E+10 | 0.102063E+10 | 0.133897E+10 | 0.919118E+09 | 0.419850E+09 | 0.00 | 0.00 |
March | 0.264538E+10 | 0.108907E+10 | 0.162574E+10 | 0.101242E+10 | 0.613322E+09 | 0.00 | 0.00 |
April | 0.328634E+10 | 0.100806E+10 | 0.199551E+10 | 0.129607E+10 | 0.699441E+09 | 0.00 | 0.00 |
May | 0.340399E+10 | 0.692404E+09 | 0.197678E+10 | 0.112732E+10 | 0.849457E+09 | 0.00 | 0.00 |
June | 0.372607E+10 | 0.657846E+09 | 0.211128E+10 | 0.121718E+10 | 0.894094E+09 | 0.00 | 0.00 |
July | 0.351196E+10 | 0.611883E+09 | 0.203250E+10 | 0.104386E+10 | 0.988641E+09 | 0.00 | 0.00 |
August | 0.330982E+10 | 0.676336E+09 | 0.189933E+10 | 0.950589E+09 | 0.948741E+09 | 0.00 | 0.00 |
September | 0.264870E+10 | 0.758823E+09 | 0.156912E+10 | 0.780986E+09 | 0.788133E+09 | 0.00 | 0.00 |
October | 0.260152E+10 | 0.931565E+09 | 0.154223E+10 | 0.915892E+09 | 0.626341E+09 | 0.00 | 0.00 |
November | 0.186496E+10 | 0.122741E+10 | 0.121358E+10 | 0.829626E+09 | 0.383957E+09 | 0.00 | 0.00 |
December | 0.162701E+10 | 0.128053E+10 | 0.106712E+10 | 0.706219E+09 | 0.360898E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.326193E+11 | 0.112232E+11 | 0.195476E+11 | 0.115879E+11 | 0.795963E+10 | 0.00 | 0.00 |
Minimum of Months | 0.162701E+10 | 0.611883E+09 | 0.106712E+10 | 0.706219E+09 | 0.360898E+09 | 0.00 | 0.00 |
Maximum of Months | 0.372607E+10 | 0.128053E+10 | 0.211128E+10 | 0.129607E+10 | 0.988641E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.01 | 8.64 | 3.24 | 3.12 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.57 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.53 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.81 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.36 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.89 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.01 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.46 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.87 | 10.53 | 3.17 | 6.00 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.01 | 8.64 | 2.44 | 3.12 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.65 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.77 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.86 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.04 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.75 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.93 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.95 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.72 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.63 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.03 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.82 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.65 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.63 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.2 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -1.8 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.94 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.57 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 17.99 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.55 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.11 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.8 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.2 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.10 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.48 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.76 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.54 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.83 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.16 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.78 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.48 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.10 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.54 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.08 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.78 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.766733E+09 | -688260612.0 | 0.00 | 0.00 | 744.00 | 0.00 | -78472433.5 | 58.99 | 0.00 | 0.00 |
February | 0.696999E+09 | -627185404.5 | 0.00 | 0.00 | 672.00 | 0.00 | -69813611.5 | 58.99 | 0.00 | 0.00 |
March | 0.780792E+09 | -705012853.1 | 0.00 | 0.00 | 744.00 | 0.00 | -75779600.2 | 58.99 | 0.00 | 0.00 |
April | 0.684481E+09 | -614744674.3 | 0.00 | 0.00 | 720.00 | 0.00 | -69736281.0 | 58.99 | 0.00 | 0.00 |
May | 0.664227E+09 | -594410593.0 | 0.00 | 0.00 | 744.00 | 0.00 | -69816392.2 | 58.99 | 0.00 | 0.00 |
June | 0.622780E+09 | -555351124.8 | 0.00 | 0.00 | 720.00 | 0.00 | -67428883.0 | 58.99 | 0.00 | 0.00 |
July | 0.588552E+09 | -519492944.1 | 0.00 | 0.00 | 744.00 | 0.00 | -69059129.1 | 58.99 | 0.00 | 0.00 |
August | 0.633527E+09 | -564074523.5 | 0.00 | 0.00 | 744.00 | 0.00 | -69452778.7 | 58.98 | 0.00 | 0.00 |
September | 0.618837E+09 | -551540174.9 | 0.00 | 0.00 | 720.00 | 0.00 | -67297083.0 | 58.99 | 0.00 | 0.00 |
October | 0.663715E+09 | -593487002.6 | 0.00 | 0.00 | 744.00 | 0.00 | -70227778.9 | 58.99 | 0.00 | 0.00 |
November | 0.682384E+09 | -611316297.7 | 0.00 | 0.00 | 720.00 | 0.00 | -71067532.3 | 58.99 | 0.00 | 0.00 |
December | 0.747432E+09 | -671018786.5 | 0.00 | 0.00 | 744.00 | 0.00 | -76413171.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.815046E+10 | -.729589E+10 | 8760.00 | -854564674.3 | 58.99 | |||||
Minimum of Months | 0.588552E+09 | -705012853.1 | 0.00 | 0.00 | 672.00 | 0.00 | -78472433.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.780792E+09 | -519492944.1 | 0.00 | 0.00 | 744.00 | 0.00 | -67297083.0 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 307.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 295.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 353.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 390.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 380.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 342.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 330.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 308.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4027.67 | ||||||||||
Minimum of Months | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.672737E+09 | 28386.85 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.361069E+09 | 28386.85 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.272109E+09 | 28386.85 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1890759.49 | 2021.25 | 11-APR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 25235866.69 | 5348.48 | 15-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.380783E+09 | 28386.85 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171382E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.672737E+09 | 28386.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110467E+09 | 22980.58 | 10-JAN-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.222179E+09 | 61748.55 | 05-FEB-07:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6216466.40 | 15551.07 | 12-MAR-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33798339.06 | 60147.99 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.372661E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.222179E+09 | 61748.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.204801E+10 | 0.152861E+10 | 25550.92 | 02-JAN-06:02 | 17823.20 | 0.00 |
February | 0.00 | 0.00 | 0.321870E+10 | 0.237723E+10 | 27022.24 | 03-FEB-06:03 | 14735.08 | 0.00 |
March | 0.00 | 0.00 | 0.460086E+10 | 0.350853E+10 | 27196.39 | 07-MAR-06:02 | 15510.01 | 0.00 |
April | 0.00 | 0.00 | 0.835784E+10 | 0.644553E+10 | 28037.04 | 29-APR-05:01 | 16801.60 | 0.00 |
May | 0.00 | 0.00 | 0.149455E+11 | 0.105759E+11 | 29766.99 | 23-MAY-05:01 | 14571.66 | 0.00 |
June | 0.00 | 0.00 | 0.159436E+11 | 0.112764E+11 | 29361.58 | 05-JUN-05:01 | 16098.16 | 0.00 |
July | 0.00 | 0.00 | 0.164785E+11 | 0.111066E+11 | 29859.20 | 31-JUL-05:01 | 14868.65 | 0.00 |
August | 0.00 | 0.00 | 0.176372E+11 | 0.119904E+11 | 29901.75 | 11-AUG-05:01 | 14893.30 | 0.00 |
September | 0.00 | 0.00 | 0.150877E+11 | 0.101767E+11 | 29989.71 | 05-SEP-05:01 | 14398.36 | 0.00 |
October | 0.00 | 0.00 | 0.127401E+11 | 0.911447E+10 | 29802.13 | 23-OCT-05:01 | 15398.59 | 0.00 |
November | 0.00 | 0.00 | 0.643753E+10 | 0.491393E+10 | 28301.41 | 02-NOV-05:01 | 16011.84 | 0.00 |
December | 0.00 | 0.00 | 0.404087E+10 | 0.300075E+10 | 27583.18 | 15-DEC-06:01 | 15962.68 | 0.00 |
Annual Sum or Average | 0.121537E+12 | 0.860150E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.204801E+10 | 0.152861E+10 | 25550.92 | 14398.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.176372E+11 | 0.119904E+11 | 29989.71 | 17823.20 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.885280E+09 | 0.592903E+09 | 34646.96 | 01-JAN-14:15 | 28158.00 | 0.00 |
February | 0.00 | 0.00 | 0.286254E+10 | 0.197716E+10 | 34167.00 | 26-FEB-14:25 | 26592.71 | 0.00 |
March | 0.00 | 0.00 | 0.456504E+10 | 0.312260E+10 | 40112.06 | 26-MAR-14:35 | 30381.01 | 0.00 |
April | 0.00 | 0.00 | 0.155994E+11 | 0.116217E+11 | 79562.73 | 29-APR-17:43 | 49646.96 | 0.00 |
May | 0.00 | 0.00 | 0.409629E+11 | 0.284152E+11 | 84882.62 | 23-MAY-17:10 | 44213.46 | 0.00 |
June | 0.00 | 0.00 | 0.469200E+11 | 0.330881E+11 | 83010.85 | 17-JUN-05:09 | 46150.34 | 0.00 |
July | 0.00 | 0.00 | 0.524332E+11 | 0.343758E+11 | 87361.08 | 26-JUL-05:01 | 40895.94 | 0.00 |
August | 0.00 | 0.00 | 0.513733E+11 | 0.340431E+11 | 85150.98 | 05-AUG-05:05 | 43606.85 | 0.00 |
September | 0.00 | 0.00 | 0.405144E+11 | 0.261106E+11 | 84256.78 | 04-SEP-10:03 | 44065.76 | 0.00 |
October | 0.00 | 0.00 | 0.322900E+11 | 0.216779E+11 | 87682.36 | 25-OCT-05:01 | 38184.81 | 0.00 |
November | 0.00 | 0.00 | 0.779436E+10 | 0.542023E+10 | 76114.01 | 05-NOV-13:33 | 54327.57 | 0.00 |
December | 0.00 | 0.00 | 0.429456E+10 | 0.288348E+10 | 33451.76 | 10-DEC-14:45 | 24903.10 | 0.00 |
Annual Sum or Average | 0.300495E+12 | 0.203329E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.885280E+09 | 0.592903E+09 | 33451.76 | 24903.10 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.524332E+11 | 0.343758E+11 | 87682.36 | 54327.57 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.128743E+10 | 0.36 | 1291.17 | 07-JAN-16:30 | 0.93 |
February | 0.118260E+10 | 0.36 | 1291.17 | 04-FEB-14:00 | 0.94 |
March | 0.138762E+10 | 0.38 | 1291.17 | 02-MAR-11:30 | 0.93 |
April | 0.129399E+10 | 0.37 | 1291.17 | 01-APR-06:20 | 0.92 |
May | 0.138161E+10 | 0.39 | 1291.17 | 01-MAY-06:05 | 0.92 |
June | 0.138338E+10 | 0.41 | 1291.17 | 01-JUN-06:20 | 0.92 |
July | 0.134102E+10 | 0.39 | 1291.17 | 01-JUL-06:05 | 0.92 |
August | 0.144474E+10 | 0.41 | 1291.17 | 01-AUG-06:20 | 0.92 |
September | 0.134182E+10 | 0.40 | 1291.17 | 01-SEP-06:03 | 0.92 |
October | 0.132349E+10 | 0.38 | 1291.17 | 02-OCT-06:20 | 0.93 |
November | 0.123697E+10 | 0.35 | 1291.17 | 16-NOV-07:10 | 0.94 |
December | 0.128715E+10 | 0.35 | 1291.17 | 19-DEC-07:40 | 0.93 |
Annual Sum or Average | 0.158918E+11 | 0.38 | |||
Minimum of Months | 0.118260E+10 | 0.35 | 1291.17 | 0.92 | |
Maximum of Months | 0.144474E+10 | 0.41 | 1291.17 | 0.94 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.303703E+10 | 0.34 | 3058.44 | 19-JAN-13:10 | 0.88 |
February | 0.280077E+10 | 0.35 | 3058.44 | 22-FEB-15:20 | 0.89 |
March | 0.327994E+10 | 0.36 | 3058.44 | 04-MAR-11:30 | 0.89 |
April | 0.310296E+10 | 0.38 | 3058.44 | 04-APR-15:40 | 0.89 |
May | 0.356978E+10 | 0.52 | 3058.44 | 01-MAY-13:40 | 0.89 |
June | 0.367339E+10 | 0.59 | 3058.44 | 01-JUN-14:30 | 0.89 |
July | 0.377080E+10 | 0.63 | 3058.44 | 03-JUL-14:40 | 0.89 |
August | 0.386950E+10 | 0.60 | 3058.44 | 01-AUG-07:00 | 0.88 |
September | 0.348966E+10 | 0.51 | 3058.44 | 01-SEP-08:50 | 0.89 |
October | 0.335525E+10 | 0.46 | 3058.44 | 02-OCT-16:20 | 0.89 |
November | 0.293265E+10 | 0.34 | 3058.44 | 01-NOV-15:00 | 0.89 |
December | 0.303389E+10 | 0.33 | 3058.44 | 01-DEC-15:20 | 0.89 |
Annual Sum or Average | 0.399156E+11 | 0.45 | |||
Minimum of Months | 0.280077E+10 | 0.33 | 3058.44 | 0.88 | |
Maximum of Months | 0.386950E+10 | 0.63 | 3058.44 | 0.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.98 | 2.24 |
February | 0.88 | 2.42 |
March | 1.99 | 1.88 |
April | 2.74 | 1.01 |
May | 3.11 | 0.00 |
June | 3.91 | 0.01 |
July | 3.71 | 0.01 |
August | 4.23 | 0.03 |
September | 3.58 | 0.02 |
October | 3.36 | 0.07 |
November | 1.37 | 1.68 |
December | 2.14 | 1.95 |
Annual Sum or Average | 31.98 | 0.56 |
Minimum of Months | 0.88 | 0.00 |
Maximum of Months | 4.23 | 2.42 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.08 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.03 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.11 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.08 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 4.35 | 0.00 |
June | 7.00 | 0.00 |
July | 7.76 | 0.00 |
August | 6.67 | 0.00 |
September | 4.87 | 0.00 |
October | 1.35 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 32.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 7.76 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.183206E+10 | 0.982342E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.203646E+10 | 0.527169E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.261055E+10 | 0.400632E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.353581E+10 | 2916772.54 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.543256E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.573888E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.579413E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.618388E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.532099E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.472104E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.294344E+10 | 38488135.63 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.235875E+10 | 0.560684E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.485085E+11 | 0.251223E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.183206E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.618388E+10 | 0.982342E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.329188E+10 | 0.168449E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.361815E+10 | 0.333329E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.458978E+10 | 9473308.29 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.763311E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.156448E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.175847E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.191724E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.188960E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.151576E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.126801E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.516563E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.426439E+10 | 51529135.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.127699E+12 | 0.562780E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.329188E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.191724E+11 | 0.333329E+09 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.128743E+10 | 0.204801E+10 | 0.672737E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118260E+10 | 0.321870E+10 | 0.361069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138762E+10 | 0.460086E+10 | 0.272109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129399E+10 | 0.835784E+10 | 1890759.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138161E+10 | 0.149455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138338E+10 | 0.159436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134102E+10 | 0.164785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144474E+10 | 0.176372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134182E+10 | 0.150877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132349E+10 | 0.127401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123697E+10 | 0.643753E+10 | 25235866.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128715E+10 | 0.404087E+10 | 0.380783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158918E+11 | 0.121537E+12 | 0.171382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118260E+10 | 0.204801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144474E+10 | 0.176372E+11 | 0.672737E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.303703E+10 | 0.885280E+09 | 0.110467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.280077E+10 | 0.286254E+10 | 0.222179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.327994E+10 | 0.456504E+10 | 6216466.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.310296E+10 | 0.155994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.356978E+10 | 0.409629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.367339E+10 | 0.469200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.377080E+10 | 0.524332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.386950E+10 | 0.513733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.348966E+10 | 0.405144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.335525E+10 | 0.322900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.293265E+10 | 0.779436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.303389E+10 | 0.429456E+10 | 33798339.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.399156E+11 | 0.300495E+12 | 0.372661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.280077E+10 | 0.885280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.386950E+10 | 0.524332E+11 | 0.222179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.128743E+10 | 0.00 | 0.00 | 0.00 | 0.544634E+09 | 0.00 | 0.982342E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118260E+10 | 0.00 | 0.00 | 0.00 | 0.853856E+09 | 0.00 | 0.527169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138762E+10 | 0.00 | 0.00 | 0.00 | 0.122294E+10 | 0.00 | 0.400632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129399E+10 | 0.00 | 0.00 | 0.00 | 0.224183E+10 | 0.00 | 2916772.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138161E+10 | 0.00 | 0.00 | 0.00 | 0.405095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138338E+10 | 0.00 | 0.00 | 0.00 | 0.435550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134102E+10 | 0.00 | 0.00 | 0.00 | 0.445311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144474E+10 | 0.00 | 0.00 | 0.00 | 0.473913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134182E+10 | 0.00 | 0.00 | 0.00 | 0.397916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132349E+10 | 0.00 | 0.00 | 0.00 | 0.339755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123697E+10 | 0.00 | 0.00 | 0.00 | 0.170647E+10 | 0.00 | 38488135.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128715E+10 | 0.00 | 0.00 | 0.00 | 0.107160E+10 | 0.00 | 0.560684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158918E+11 | 0.00 | 0.00 | 0.00 | 0.326167E+11 | 0.00 | 0.251223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.118260E+10 | 0.00 | 0.00 | 0.00 | 0.544634E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144474E+10 | 0.00 | 0.00 | 0.00 | 0.473913E+10 | 0.00 | 0.982342E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.303703E+10 | 0.00 | 0.00 | 0.00 | 0.254856E+09 | 0.00 | 0.168449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.280077E+10 | 0.00 | 0.00 | 0.00 | 0.817383E+09 | 0.00 | 0.333329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.327994E+10 | 0.00 | 0.00 | 0.00 | 0.130984E+10 | 0.00 | 9473308.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.310296E+10 | 0.00 | 0.00 | 0.00 | 0.453014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.356978E+10 | 0.00 | 0.00 | 0.00 | 0.120750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.367339E+10 | 0.00 | 0.00 | 0.00 | 0.139114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.377080E+10 | 0.00 | 0.00 | 0.00 | 0.154016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.386950E+10 | 0.00 | 0.00 | 0.00 | 0.150265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.348966E+10 | 0.00 | 0.00 | 0.00 | 0.116680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.335525E+10 | 0.00 | 0.00 | 0.00 | 0.932488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.293265E+10 | 0.00 | 0.00 | 0.00 | 0.223298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.303389E+10 | 0.00 | 0.00 | 0.00 | 0.123050E+10 | 0.00 | 51529135.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.399156E+11 | 0.00 | 0.00 | 0.00 | 0.877831E+11 | 0.00 | 0.562780E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.280077E+10 | 0.00 | 0.00 | 0.00 | 0.254856E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.386950E+10 | 0.00 | 0.00 | 0.00 | 0.154016E+11 | 0.00 | 0.333329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.577117E+09 | 0.187765E+09 | 0.00 | 966957.57 | 0.00 | 0.255357E+09 | 0.342791E+09 | 0.00 | 0.16 |
February | 0.334794E+09 | 0.324528E+09 | 0.00 | 970325.21 | 149834.37 | 0.131058E+09 | 0.251446E+09 | 0.00 | 0.16 |
March | 0.361205E+09 | 0.502785E+09 | 0.00 | 1628639.00 | 279874.50 | 99367187.81 | 0.301642E+09 | 0.00 | 0.18 |
April | 42523917.80 | 0.103474E+10 | 0.00 | 1935390.99 | 313074.32 | 2649600.72 | 0.116263E+09 | 0.00 | 0.17 |
May | 0.00 | 0.286480E+10 | 0.00 | 160480.94 | 0.00 | 0.00 | 17426.33 | 0.00 | 0.18 |
June | 0.00 | 0.325780E+10 | 0.00 | 422268.25 | 0.00 | 0.00 | 38468.86 | 0.00 | 0.18 |
July | 0.00 | 0.364161E+10 | 0.00 | 182126.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
August | 0.00 | 0.361587E+10 | 0.00 | 128755.91 | 0.00 | 0.00 | 27565.11 | 0.00 | 0.18 |
September | 0.00 | 0.297537E+10 | 0.00 | 485870.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
October | 18510159.56 | 0.223371E+10 | 0.00 | 3100403.33 | 0.00 | 0.00 | 0.136020E+09 | 0.00 | 0.17 |
November | 97583347.05 | 0.747715E+09 | 0.00 | 2546864.43 | 689482.92 | 22782971.99 | 0.253166E+09 | 0.00 | 0.16 |
December | 0.469957E+09 | 0.518612E+09 | 2436.28 | 1198098.75 | 202280.75 | 0.168392E+09 | 0.229694E+09 | 19098.58 | 0.16 |
Annual Sum or Average | 0.190169E+10 | 0.219053E+11 | 2436.28 | 13726182.15 | 1634546.86 | 0.679607E+09 | 0.163111E+10 | 19098.58 | 0.17 |
Minimum of Months | 0.00 | 0.187765E+09 | 0.00 | 128755.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.577117E+09 | 0.364161E+10 | 2436.28 | 3100403.33 | 689482.92 | 0.255357E+09 | 0.342791E+09 | 19098.58 | 0.18 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.272299E+10 | 49216195.55 | 0.00 | 144419.77 | 4497400.89 | 37403331.28 | 6101855.96 | 0.00 | 0.16 |
February | 0.191491E+10 | 0.276398E+09 | 0.00 | 292648.64 | 2030273.18 | 37331547.58 | 37511779.25 | 0.00 | 0.17 |
March | 0.212730E+10 | 0.520059E+09 | 0.00 | 510334.16 | 2162943.28 | 285198.40 | 0.106571E+09 | 0.00 | 0.18 |
April | 0.653162E+09 | 0.169363E+10 | 0.00 | 2760021.20 | 0.00 | 0.00 | 0.443997E+09 | 0.00 | 0.17 |
May | 2193509.72 | 0.639791E+10 | 0.00 | 331201.76 | 1725301.21 | 0.00 | 17009085.83 | 0.00 | 0.19 |
June | 7254669.05 | 0.844454E+10 | 0.00 | 183333.44 | 1038017.49 | 0.00 | 15052498.85 | 0.00 | 0.20 |
July | 0.00 | 0.978286E+10 | 0.00 | 49639.65 | 1803732.34 | 0.00 | 1193037.28 | 0.00 | 0.20 |
August | 2914290.12 | 0.892785E+10 | 0.00 | 206390.85 | 0.00 | 0.00 | 12495045.00 | 0.00 | 0.21 |
September | 6223399.35 | 0.671473E+10 | 0.00 | 448627.13 | 1022249.40 | 0.00 | 55737633.63 | 0.00 | 0.20 |
October | 0.399894E+09 | 0.471201E+10 | 0.00 | 3095008.21 | 0.00 | 0.00 | 0.237117E+09 | 0.00 | 0.18 |
November | 0.120489E+10 | 0.112692E+10 | 0.00 | 1507352.76 | 5706803.35 | 0.00 | 0.366068E+09 | 0.00 | 0.16 |
December | 0.214904E+10 | 0.589253E+09 | 0.00 | 426723.52 | 11143103.59 | 21504765.65 | 57679703.74 | 0.00 | 0.16 |
Annual Sum or Average | 0.111908E+11 | 0.492354E+11 | 0.00 | 9955701.11 | 31129824.73 | 96524842.91 | 0.135653E+10 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 49216195.55 | 0.00 | 49639.65 | 0.00 | 0.00 | 1193037.28 | 0.00 | 0.16 |
Maximum of Months | 0.272299E+10 | 0.978286E+10 | 0.00 | 3095008.21 | 11143103.59 | 37403331.28 | 0.443997E+09 | 0.00 | 0.21 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |