Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2020-06-03 19:11:54
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1915.63 | 396.19 | 396.19 |
Net Site Energy | 1915.63 | 396.19 | 396.19 |
Total Source Energy | 3143.49 | 650.13 | 650.13 |
Net Source Energy | 3143.49 | 650.13 | 650.13 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1403.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 242.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 67.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 33.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 28.24 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 512.21 | 1403.42 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1403.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 1.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 242.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 67.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 33.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 28.24 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 64.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 13.03 | 290.25 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 105.94 | 290.25 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 64.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 13.03 | 290.25 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 105.94 | 290.25 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 512.215 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 512.215 | 100.00 |
Total On-Site and Utility Electric Sources | 512.215 | 100.00 |
Total Electricity End Uses | 512.215 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 148.67 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2606.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 7.6531 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 6.6844 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.3906 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.5487 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.5487 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-JAN-15:39 | 27-FEB-08:09 | - | - | - | 27-FEB-12:09 |
Heating | 0.00 | 206032.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 18328.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5045.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2364.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2678.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 38530.22 | 206032.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 206032.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 18328.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5045.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2364.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 2678.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1521.30 | 0.00 | 0.00 | 0.00 |
Cooling | 4.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 768.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 213.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 105.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 89.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1622.18 | 1521.30 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 314.64 | 0.00 | 0.00 | 0.00 |
Cooling | 0.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 158.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 21.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 335.50 | 314.64 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 314.64 | 0.00 | 0.00 | 0.00 |
Cooling | 0.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 158.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 21.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 335.50 | 314.64 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.802739 |
ZONE2 FINE STORAGE DIRECT AIR | 1.16 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 2.04 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 2.04 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 83385.19 |
PSZ-OFFICE HEATING COIL | 25788.79 |
PSZ-FINE STORAGE HEATING COIL | 62904.36 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 83385.18 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.802739 | 0.802739 | 0.802739 | 0.802739 | 0.802739 | 0.802739 | 1.00 | 1.00 | 0.802739 |
PSZ-FINE STORAGE | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.00 | 1.00 | 1.16 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 0.802739 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 1.16 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.802739 | 0.802739 | 0.802739 | 0.802739 | 13288.18 | 25788.79 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 1.16 | 1.16 | 1.16 | 1.16 | 21762.40 | 62904.36 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.802740 | 0.401370 | 0.535160 | 13288.20 | 13288.18 | 6644.09 | 6644.09 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-FINE STORAGE COOLING COIL | 1.16 | 0.581080 | 0.774773 | 19237.87 | 21762.40 | 10881.20 | 10881.20 | 0.756006 | 0.756000 | 0.756000 | 0.756000 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.802739 | 888.76 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.16 | 1286.69 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 7.653 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 15.727 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 6.684 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.684 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 3.391 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 5.949 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1812.873 | 7.653 | 362.575 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1812.873 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 9314.091 | 6.684 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 9314.091 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 10866.440 | 3.391 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10866.440 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1685 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.1685 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.3070 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.3070 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 1.195 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1041 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.4317E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.4042E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.3070 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.935 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.935 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.158 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.158 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8365 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 9.529 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 23.09 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 24.66 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.158 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.11213371E-07 | 0.26651818E-13 | 0.48084804E-13 | 0.0000000 |
2 | 1 | -5.2160876 | 0.60803813E-04 | -0.95086230E-04 | 0.21497930E-08 |
3 | 0 | 5.3845682 | 0.16841986 | 0.16857575 | |
4 | 2 | 0.11213371E-07 | 0.26651818E-13 | 0.48084804E-13 | 0.0000000 |
5 | 1 | -5.2160876 | 0.60803813E-04 | -0.95086230E-04 | 0.21497930E-08 |
6 | 0 | 5.3845682 | 0.16841986 | 0.16857575 | |
7 | 4 | 0.81735868E-12 | -0.57156297E-16 | 0.55090832E-14 | 0.11117815E-15 |
8 | 3 | -0.39662747E-03 | 0.21866377E-06 | -0.57650539E-04 | 0.15682056E-12 |
9 | 2 | 1.7675818 | 0.47210309E-02 | 1.1617839 | -0.76040502E-04 |
10 | 1 | -7.0920383 | 0.12134871 | -17.234041 | 0.33878901 |
11 | 0 | 5.5278851 | 0.76962015E-01 | 16.275347 | |
12 | 4 | 0.81735868E-12 | -0.57156297E-16 | 0.55090832E-14 | 0.11117815E-15 |
13 | 3 | -0.39662747E-03 | 0.21866377E-06 | -0.57650539E-04 | 0.15682056E-12 |
14 | 2 | 1.7675818 | 0.47210309E-02 | 1.1617839 | -0.76040502E-04 |
15 | 1 | -7.0920383 | 0.12134871 | -17.234041 | 0.33878901 |
16 | 0 | 5.5278851 | 0.76962015E-01 | 16.275347 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009596 | 2.1009596 | 2.1009596 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009596 | 2.1009596 | 2.1009596 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.1954460 | 1.1954460 | 1.1954460 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602635 | 1.7602635 | 1.7602635 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.40943546E-08 | -0.48941433E-14 | 0.10002011E-14 | -0.40158259E-16 |
55 | 6 | 0.31272124E-05 | 0.19933103E-08 | 0.31973031E-02 | -0.26821658E-04 |
56 | 5 | -0.21335304E-03 | 0.11766416E-05 | -0.22414699 | 0.19598788E-02 |
57 | 4 | 0.48316011E-02 | 0.53476752E-04 | 4.8365802 | -0.45332602E-01 |
58 | 3 | -0.42187430E-01 | 0.42463702E-03 | -38.061149 | 0.39909293 |
59 | 2 | 0.14945981 | 0.70555311E-03 | 116.56127 | -1.4189736 |
60 | 1 | -0.21550367 | 0.21454475E-03 | -143.95282 | 2.0497880 |
61 | 0 | 0.10501452 | 0.52166033E-05 | 60.838472 | |
62 | 7 | -0.99354594E-08 | 0.85994744E-15 | -0.36446392E-14 | 0.33402613E-16 |
63 | 6 | 0.19007305E-05 | 0.85218543E-09 | 0.32020323E-02 | -0.26861330E-04 |
64 | 5 | -0.10257637E-03 | 0.49552608E-06 | -0.22441548 | 0.19622488E-02 |
65 | 4 | 0.21308868E-02 | 0.22341873E-04 | 4.8410464 | -0.45375540E-01 |
66 | 3 | -0.17974913E-01 | 0.17625076E-03 | -38.086349 | 0.39937154 |
67 | 2 | 0.62772635E-01 | 0.29099605E-03 | 116.61028 | -1.4196292 |
68 | 1 | -0.89915137E-01 | 0.87799409E-04 | -143.98166 | 2.0502620 |
69 | 0 | 0.43667207E-01 | 0.21083643E-05 | 60.838472 | |
70 | 7 | -0.10614037E-07 | 0.12466653E-14 | -0.85452615E-14 | 0.12855439E-15 |
71 | 6 | 0.18765462E-05 | 0.80237200E-09 | 0.32022472E-02 | -0.26863133E-04 |
72 | 5 | -0.98338504E-04 | 0.46542478E-06 | -0.22442766 | 0.19623563E-02 |
73 | 4 | 0.20165412E-02 | 0.20956150E-04 | 4.8412485 | -0.45377483E-01 |
74 | 3 | -0.16916006E-01 | 0.16514078E-03 | -38.087488 | 0.39938413 |
75 | 2 | 0.58934009E-01 | 0.27235831E-03 | 116.61249 | -1.4196588 |
76 | 1 | -0.84323034E-01 | 0.82076304E-04 | -143.98296 | 2.0502833 |
77 | 0 | 0.40927925E-01 | 0.19639094E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.55090832E-14 | -0.57156297E-16 | 0.81735868E-12 | 0.11117815E-15 |
85 | 3 | -0.57650539E-04 | 0.21866377E-06 | -0.39662747E-03 | 0.15682056E-12 |
86 | 2 | 1.1617839 | 0.47210309E-02 | 1.7675818 | -0.76040502E-04 |
87 | 1 | -17.234041 | 0.12134871 | -7.0920383 | 0.33878901 |
88 | 0 | 16.275347 | 0.76962015E-01 | 5.5278851 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.29_SHGC_0.45 | 28 | 1 | VerySmooth | 1.647 | 0.445 | 0.367 | 0.451 |
2 | SKYLIGHT_U_0.75_SHGC_0.6 | 29 | 1 | VerySmooth | 4.262 | 0.604 | 0.475 | 0.601 |
3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 30 | 1 | VerySmooth | 4.262 | 0.604 | 0.475 | 0.601 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 4.26414E-002 | 0.36619 | 0.44111 | 0.44111 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.85326E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.056 | 0.5354 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 3.379E-002 | 1.427E-004 | 2.202E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.494 | 3.545E-004 | 2.258E-004 | 0.602 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 2.709 | 8.453E-004 | 5.521E-004 | 0.276 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 8005.11646 | 9606.13976 | 0.66895 | 0.80274 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 25.80200 | 6.97981E-003 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10712.39576 | 12854.87491 | 0.30546 | 0.36655 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90000 | 6.45023E-005 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 14867.87892 | 17841.45471 | 0.96846 | 1.16216 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 26.89000 | 6.97982E-003 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 30562.05016 | 36674.46020 | 0.73410 | 0.88092 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | -41.90000 | 6.45023E-005 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40000 | 6.97982E-003 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 69487.65260 | 83385.18312 | 1.69941 | 2.03929 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 11627.24 | 0.80274 | 0.80274 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 15943.56 | 0.36655 | 0.36655 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 20525.97 | 1.16216 | 1.16216 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 54716.44 | 0.88092 | 0.88092 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.80274 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.16216 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.03929 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 2.03929 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 83385.18642 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 83385.18312 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.80274 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.80274 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.80274 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.80274 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.80274 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.80274 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.16216 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.16216 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.16216 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.16216 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.16216 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.16216 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.80274 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.16216 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.80274 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.80274 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.80274 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.80274 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.80274 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.80274 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.40137 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.53516 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 13288.19732 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 13288.18000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 6644.09000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 6644.09000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 13288.18000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25788.78877 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.80274 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 888.75916 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 25788.78877 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.16216 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.16216 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.16216 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.16216 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.16216 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.16216 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58108 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.77477 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 19237.87452 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 21762.40000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10881.20000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 10881.20000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.75601 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.75600 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.75600 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.75600 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21762.40000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 62904.35597 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.16216 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1286.69104 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 62904.35597 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 12665.3 | 11.88 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 20860.2 | 18.35 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 8 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.3195969275 | 0.2777272251 | Pass | Pass | 1.9332904469 | 6.7541534149 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.7272280255 | 0.6515593942 | Pass | Pass | 0.7306243126 | 0.6416255456 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 2.8594647050E-003 | 1.0578876137E-002 | Pass | Pass | 3.7692626032E-002 | 4.2382378784E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.294 | 0.307 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.294 | 0.307 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.294 | 0.307 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.294 | 0.307 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.294 | 0.307 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.294 | 0.307 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.294 | 0.307 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.165 | 0.168 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.294 | 0.307 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.294 | 0.307 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.294 | 0.307 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.165 | 0.168 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.104 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.043 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.040 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.29_SHGC_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.647 | 0.445 | 0.451 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.29_SHGC_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.647 | 0.445 | 0.451 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.647 | 0.445 | 0.451 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.647 | 0.445 | 0.451 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 2.842 | 0.517 | 0.519 | ||||||||||||
North Total or Average | 6.51 | 1.647 | 0.445 | 0.451 | ||||||||||||
Non-North Total or Average | 26.02 | 3.141 | 0.536 | 0.537 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 7.6531 | 236.88 | 1812.87 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 58.12 | 168.00 | 54.24 | 0.0000 | Y | 18.46 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 6.6844 | 1393.41 | 9314.09 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 106.08 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 3.3906 | 3204.84 | 10866.44 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 57.86 | 0.0000 | Y | 118.02 |
Interior Lighting Total | 4.5487 | 4835.13 | 21993.40 | 242.55 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous | 0.14 | 1812.87 | 262.87 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous | 0.05 | 1812.87 | 90.64 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.12 | 10866.44 | 1260.51 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 85.54 | AstronomicalClock | - | 44.84 | 44.84 | 0.72 | |
EXTERIOR_LIGHTS_B | 4959.90 | AstronomicalClock | - | 83.06 | 71.59 | 66.66 | |
Exterior Lighting Total | 5045.44 | 67.38 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 13288.18 | 10612.74 | 2675.44 | 0.80 | 4.12 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21762.40 | 16452.37 | 5310.03 | 0.76 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 12665.3 | 11.88 | ||||
PSZ-FINE STORAGE COOLING COIL | 20860.2 | 18.35 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 83385.19 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 25788.79 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 62904.36 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.04 | 189.47 | 92.91 | 1.00 | 3.57 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.80 | 888.76 | 1107.16 | 1.00 | 1.46 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.16 | 1286.69 | 1107.16 | 1.00 | 1.37 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.54 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8005.12 | 9606.14 | 40.55 | 0.669 | 0.803 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 23.90 | 23.90 | 0.00813 | 25.80 | 0.00698 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 14867.88 | 17841.45 | 12.80 | 0.968 | 1.162 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 26.70 | 26.70 | 0.00790 | 26.89 | 0.00698 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00384 | 27.40 | 0.00698 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10712.40 | 12854.87 | 54.27 | 0.305 | 0.367 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00810 | -41.90 | 0.00006 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 30562.05 | 36674.46 | 26.32 | 0.734 | 0.881 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | 15.56 | 15.56 | 0.00774 | -41.90 | 0.00006 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 69487.65 | 83385.18 | 26.02 | 1.699 | 2.039 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 9.99 | 0.00775 | -41.90 | 0.00006 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.80 | 0.80 | 0.37 | 0.37 | 0.8027 | 0.8027 | 0.8027 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.16 | 1.16 | 0.88 | 0.88 | 1.1622 | 1.1622 | 1.1622 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 83385.186 | 83385.186 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 83385.19 | 83385.19 | 2.039295 | -14.86 | -14.86 | 0.00406860 | 43.33 | 26.90 | 0.01600000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 9.99 | 0.00775004 | 100.0000 | 83385.18 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 6644.090 | 0.000 | 0.802740 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 6644.09 | 6644.09 | 0.802740 | 24.16 | 15.82 | 0.00798131 | 12.00 | 11.12 | 0.00800000 | 25.97 | 0.00697981 | 15.59 | 12.7420 | 23.90 | 0.00812624 | 43.3501 | 8002.36 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 25788.789 | 25788.789 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 25788.79 | 25788.79 | 0.802739 | 3.49 | 3.49 | 0.00585815 | 40.00 | 20.97 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 12.7420 | 21.10 | 0.00810061 | 51.2285 | 10712.40 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 10881.200 | 0.000 | 1.162160 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 10881.20 | 10881.20 | 1.162160 | 26.88 | 16.42 | 0.00756428 | 12.00 | 11.12 | 0.00800000 | 27.20 | 0.00697982 | 16.03 | 36.5451 | 26.70 | 0.00790387 | 35.7068 | 14812.96 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 62904.356 | 62904.356 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | 62904.36 | 62904.36 | 1.162156 | -12.14 | -12.14 | 0.00403696 | 40.00 | 20.97 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 36.5452 | 15.56 | 0.00773519 | 69.2987 | 30562.05 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 83385.186 | 83385.186 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1854 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 2.039295 | 2.41745993 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 83385.19 | 83385.19 | 1.0000 | 2.41745993 | 2.039295 | -14.86 | -14.86 | 0.00406860 | -4873.0 | 43.33 | 26.90 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 83385.19 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 9.99 | 0.00775004 | 9.99 | 0.00775004 | 100.0000 | 83385.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 6644.090 | 0.000 | 0.802740 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6769 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 6644.09 | 6644.09 | 1.0000 | 0.95159954 | 0.802740 | 24.16 | 15.82 | 0.00798131 | 44600.0 | 12.00 | 11.12 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6644.09 | 25.97 | 0.00697981 | 15.59 | 0.10228487 | 12.7420 | 23.90 | 0.00812761 | 23.90 | 0.00812624 | 43.3501 | 8002.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25788.789 | 25788.789 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.802739 | 0.95159799 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 25788.79 | 25788.79 | 1.0000 | 0.95159799 | 0.802739 | 3.49 | 3.49 | 0.00585815 | 18191.0 | 40.00 | 20.97 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25788.79 | -41.90 | 0.00006450 | -41.90 | 0.10228487 | 12.7420 | 21.05 | 0.00810061 | 21.10 | 0.00810061 | 51.2285 | 10712.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 10881.200 | 0.000 | 1.162160 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.9016 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 10881.20 | 10881.20 | 1.0000 | 1.37767013 | 1.162160 | 26.88 | 16.42 | 0.00756428 | 46308.0 | 12.00 | 11.12 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10881.20 | 27.20 | 0.00697982 | 16.03 | 0.42471267 | 36.5451 | 26.70 | 0.00790285 | 26.70 | 0.00790387 | 35.7068 | 14812.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 62904.356 | 62904.356 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.162156 | 1.37766525 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | 62904.36 | 62904.36 | 1.0000 | 1.37766525 | 1.162156 | -12.14 | -12.14 | 0.00403696 | -2197.0 | 40.00 | 20.97 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 62904.36 | -41.90 | 0.00006450 | -41.90 | 0.42471267 | 36.5452 | 15.56 | 0.00773519 | 15.56 | 0.00773519 | 69.2987 | 30562.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 1.16 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2686.33 | 3274.17 | 2606.50 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2686.33 | 3274.17 | 2606.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 187.50 | 0.00 | 148.67 | 0.00 |
ZONE2 FINE STORAGE | 687.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 212.00 | 0.00 | 0.00 | 0.00 |
Facility | 1004.67 | 0.00 | 148.67 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.343 | 0.361 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 512.21 | 3230.53 | 23-APR-14:00 | 38530.22 | 04-JAN-15:40 |
Electricity:Building | 381.84 | 2747.53 | 16-APR-15:00 | 28441.43 | 02-JAN-09:10 |
Electricity:Zone:ZONE1 OFFICE | 50.40 | 855.52 | 12-MAR-17:10 | 3087.86 | 02-JAN-08:10 |
InteriorLights:Electricity | 242.55 | 2173.78 | 14-APR-17:10 | 18328.81 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 18.46 | 281.77 | 12-MAR-17:10 | 1175.36 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 242.55 | 2173.78 | 14-APR-17:10 | 18328.81 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 106.08 | 931.41 | 01-JAN-00:10 | 7916.98 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 106.08 | 931.41 | 01-JAN-00:10 | 7916.98 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 225.35 | 960.59 | 05-MAR-10:50 | 17436.59 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 118.02 | 960.59 | 05-MAR-10:50 | 9236.47 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 28.24 | 483.00 | 26-JAN-08:10 | 3127.20 | 12-JAN-12:30 |
WaterSystems:Electricity | 28.24 | 483.00 | 26-JAN-08:10 | 3127.20 | 12-JAN-12:30 |
Water Heater:WaterSystems:Electricity | 28.24 | 483.00 | 26-JAN-08:10 | 3127.20 | 12-JAN-12:30 |
Fans:Electricity | 33.26 | 0.00 | 22-MAR-17:10 | 2364.92 | 03-JAN-08:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 512.21 | 3230.53 | 23-APR-14:00 | 38530.22 | 04-JAN-15:40 |
ElectricityPurchased:Plant | 512.21 | 3230.53 | 23-APR-14:00 | 38530.22 | 04-JAN-15:40 |
Cogeneration:ElectricityPurchased | 512.21 | 3230.53 | 23-APR-14:00 | 38530.22 | 04-JAN-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 512.21 | 3230.53 | 23-APR-14:00 | 38530.22 | 04-JAN-15:40 |
ElectricityNet:Plant | 512.21 | 3230.53 | 23-APR-14:00 | 38530.22 | 04-JAN-15:40 |
Cogeneration:ElectricityNet | 512.21 | 3230.53 | 23-APR-14:00 | 38530.22 | 04-JAN-15:40 |
Electricity:HVAC | 34.76 | 0.00 | 22-MAR-17:10 | 5870.53 | 21-JUL-16:00 |
General:Fans:Electricity | 33.26 | 0.00 | 22-MAR-17:10 | 2364.92 | 03-JAN-08:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1.50 | 0.00 | 01-JAN-00:10 | 3695.08 | 21-JUL-16:00 |
ExteriorLights:Electricity | 67.38 | 0.00 | 01-JAN-11:20 | 5045.44 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 67.38 | 0.00 | 01-JAN-11:20 | 5045.44 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1403.42 | 0.00 | 22-MAR-17:10 | 206032.13 | 27-FEB-08:10 |
Gas:HVAC | 1403.42 | 0.00 | 22-MAR-17:10 | 206032.13 | 27-FEB-08:10 |
Heating:Gas | 1403.42 | 0.00 | 22-MAR-17:10 | 206032.13 | 27-FEB-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-FEB-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-FEB-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-FEB-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-FEB-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-FEB-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-FEB-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-FEB-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-FEB-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2088.38 | 0.00 | 22-MAR-17:10 | 304306.38 | 29-JAN-00:30 |
EnergyTransfer:Building | 1004.45 | 0.00 | 22-MAR-17:10 | 152235.31 | 29-JAN-00:30 |
EnergyTransfer:Zone:ZONE1 OFFICE | 77.05 | 0.00 | 01-JAN-00:40 | 22502.08 | 06-FEB-07:20 |
Heating:EnergyTransfer | 986.26 | 0.00 | 22-MAR-17:10 | 152235.31 | 29-JAN-00:30 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 70.77 | 0.00 | 01-JAN-00:40 | 22502.08 | 06-FEB-07:20 |
Cooling:EnergyTransfer | 18.20 | 0.00 | 01-JAN-00:10 | 12053.51 | 21-JUL-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 6.28 | 0.00 | 01-JAN-00:10 | 6579.37 | 05-AUG-07:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 238.08 | 0.00 | 01-JAN-00:40 | 63840.55 | 29-JAN-01:00 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 226.17 | 0.00 | 01-JAN-00:40 | 63840.55 | 29-JAN-01:00 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 11.91 | 0.00 | 01-JAN-00:10 | 8659.53 | 23-JUL-14:20 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 689.32 | 0.00 | 09-FEB-12:00 | 84257.00 | 27-FEB-15:20 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 689.32 | 0.00 | 09-FEB-12:00 | 84257.00 | 27-FEB-15:20 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1083.92 | 0.00 | 22-MAR-17:10 | 163266.54 | 27-FEB-08:10 |
HeatingCoils:EnergyTransfer | 1076.73 | 0.00 | 22-MAR-17:10 | 163266.54 | 27-FEB-08:10 |
CoolingCoils:EnergyTransfer | 7.19 | 0.00 | 01-JAN-00:10 | 16282.32 | 21-JUL-16:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 70.767 | -6.284 | 0.000 | 0.000 | 4.084 | 18.458 | 31.946 | 7.564 | 0.000 | 0.042 | 0.000 | 0.000 | -13.054 | 0.000 | -39.878 | -73.643 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 226.165 | -11.913 | 0.000 | 0.000 | 0.000 | 106.079 | 0.000 | 0.000 | 0.000 | 0.038 | 0.002 | 0.000 | 0.000 | 0.000 | -93.012 | -227.357 |
ZONE3 BULK STORAGE | 689.324 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 118.018 | 107.336 | 20.317 | 0.000 | 4.442 | 0.000 | 0.000 | -21.736 | 0.000 | -476.619 | -441.082 |
Total Facility | 689.324 | 0.000 | 296.932 | -18.198 | 0.000 | 0.000 | 4.084 | 242.555 | 139.282 | 27.881 | 0.000 | 4.521 | 0.002 | 0.000 | -34.790 | 0.000 | -609.509 | -742.082 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 24-JUN-07:03 | 0.00 | 0.00 | 0.00 | -12985.48 | 0.00 | 0.00 | 328.81 | 1090.10 | 1912.50 | 87.30 | 0.00 | 0.00 | 9807.64 | 0.00 | -0.00 | 0.00 | -240.87 | 0.00 |
ZONE2 FINE STORAGE | 23-JUL-14:12 | 0.00 | 0.00 | 0.00 | -21917.60 | 0.00 | 0.00 | 0.00 | 931.41 | 0.00 | 0.00 | 0.00 | 0.00 | 21275.43 | 0.00 | -0.00 | 0.00 | -289.24 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 23-JUL-14:12 | 0.00 | 0.00 | 0.00 | -21917.60 | 0.00 | 0.00 | 0.00 | 2174.81 | 573.75 | 6223.51 | 0.00 | 301.59 | 12953.54 | 0.00 | 0.00 | 0.00 | -309.60 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 30-MAY-06:01 | 0.00 | 0.00 | 24994.78 | 0.00 | 0.00 | 0.00 | 104.81 | 577.44 | 956.25 | 272.87 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3213.05 | -23693.10 |
ZONE2 FINE STORAGE | 30-JAN-05:21 | 0.00 | 0.00 | 65231.42 | 0.00 | 0.00 | 0.00 | 0.00 | 931.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -11866.04 | -54296.79 |
ZONE3 BULK STORAGE | 26-FEB-03:45 | 84320.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1086.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1807.62 | 0.00 | -73722.66 | -9876.83 |
Total Facility | 14-MAR-05:42 | 83565.32 | 0.00 | 87603.71 | 0.00 | 0.00 | 0.00 | 58.38 | 2369.13 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2411.95 | 0.00 | -75459.78 | -98348.58 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.8027 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.8027 | 0.1274 | 1.0000 | 0.1023 | 0.1274 | ||
PSZ-FINE STORAGE | 1.1622 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.1622 | 0.3655 | 1.0000 | 0.4247 | 0.3655 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.8027 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.8027 | 1.0000 | 1.0000 | 0.1023 | 0.1274 | ||
PSZ-FINE STORAGE | 1.1622 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.1622 | 1.0000 | 1.0000 | 0.4247 | 0.3655 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.8027 | 0.8027 | 0.8027 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.1622 | 1.1622 | 1.1622 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.8027 | 0.8027 | 0.8027 | 0.8027 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.1622 | 1.1622 | 1.1622 | 1.1622 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.8027 | 0.8027 | 0.8027 | 0.1023 | 0.2790 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.1622 | 1.1622 | 1.1622 | 0.4247 | 0.4821 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.8027 | 0.8027 | 0.8027 | 0.8027 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.1622 | 1.1622 | 1.1622 | 1.1622 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:54
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 148.67 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 148.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 1403.42 | 206032.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 1.50 | 3695.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 242.55 | 18328.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 67.38 | 5045.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 33.26 | 2364.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 28.24 | 3127.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 512.21 |
Natural Gas | 0.00 | 1403.42 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1915.63 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 50.17 |
Space Heating | 0.00 |
Space Cooling | 0.31 |
Fans (All) | 6.88 |
Service Water Heating | 5.84 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 105.94 |
Subtotal | 105.94 |
Natural Gas [MJ/m2] | |
Space Heating | 290.25 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 290.25 |
Subtotal | 290.25 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.66 |
Space Heating | 73.26 |
Space Cooling | 0.08 |
Fans (All) | 1.74 |
Service Water Heating | 1.47 |
Receptacle Equipment | 7.27 |
Miscellaneous | 3.52 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3031. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.262532E+12 |
February | 0.000 | 0.224962E+12 |
March | 0.000 | 0.218320E+12 |
April | 0.000 | 0.101309E+12 |
May | 0.000 | 0.359872E+10 |
June | 0.000 | 0.989719E+08 |
July | 0.000 | 0.126218E+08 |
August | 0.000 | 0.244614E+09 |
September | 0.000 | 0.893998E+10 |
October | 0.000 | 0.127788E+12 |
November | 0.000 | 0.192806E+12 |
December | 0.000 | 0.262805E+12 |
Annual Sum or Average | 0.140342E+13 | |
Minimum of Months | 0.000 | 0.126218E+08 |
Maximum of Months | 0.000 | 0.262805E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.262532E+12 |
February | 0.000 | 0.224962E+12 |
March | 0.000 | 0.218320E+12 |
April | 0.000 | 0.101309E+12 |
May | 0.000 | 0.359872E+10 |
June | 0.000 | 0.989719E+08 |
July | 0.000 | 0.126218E+08 |
August | 0.000 | 0.244614E+09 |
September | 0.000 | 0.893998E+10 |
October | 0.000 | 0.127788E+12 |
November | 0.000 | 0.192806E+12 |
December | 0.000 | 0.262805E+12 |
Annual Sum or Average | 0.140342E+13 | |
Minimum of Months | 0.000 | 0.126218E+08 |
Maximum of Months | 0.000 | 0.262805E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Meter
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.262532E+12 |
February | 0.000 | 0.224962E+12 |
March | 0.000 | 0.218320E+12 |
April | 0.000 | 0.101309E+12 |
May | 0.000 | 0.359872E+10 |
June | 0.000 | 0.989719E+08 |
July | 0.000 | 0.126218E+08 |
August | 0.000 | 0.244614E+09 |
September | 0.000 | 0.893998E+10 |
October | 0.000 | 0.127788E+12 |
November | 0.000 | 0.192806E+12 |
December | 0.000 | 0.262805E+12 |
Annual Sum or Average | 0.140342E+13 | |
Minimum of Months | 0.000 | 0.126218E+08 |
Maximum of Months | 0.000 | 0.262805E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.262532E+12 |
February | 0.000 | 0.224962E+12 |
March | 0.000 | 0.218320E+12 |
April | 0.000 | 0.101309E+12 |
May | 0.000 | 0.359872E+10 |
June | 0.000 | 0.989719E+08 |
July | 0.000 | 0.126218E+08 |
August | 0.000 | 0.244614E+09 |
September | 0.000 | 0.893998E+10 |
October | 0.000 | 0.127788E+12 |
November | 0.000 | 0.192806E+12 |
December | 0.000 | 0.262805E+12 |
Annual Sum or Average | 0.140342E+13 | |
Minimum of Months | 0.000 | 0.126218E+08 |
Maximum of Months | 0.000 | 0.262805E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.262532E+12 |
February | 0.000 | 0.224962E+12 |
March | 0.000 | 0.218320E+12 |
April | 0.000 | 0.101309E+12 |
May | 0.000 | 0.359872E+10 |
June | 0.000 | 0.989719E+08 |
July | 0.000 | 0.126218E+08 |
August | 0.000 | 0.244614E+09 |
September | 0.000 | 0.893998E+10 |
October | 0.000 | 0.127788E+12 |
November | 0.000 | 0.192806E+12 |
December | 0.000 | 0.262805E+12 |
Annual Sum or Average | 0.140342E+13 | |
Minimum of Months | 0.000 | 0.126218E+08 |
Maximum of Months | 0.000 | 0.262805E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.262532E+12 |
February | 0.000 | 0.224962E+12 |
March | 0.000 | 0.218320E+12 |
April | 0.000 | 0.101309E+12 |
May | 0.000 | 0.359872E+10 |
June | 0.000 | 0.989719E+08 |
July | 0.000 | 0.126218E+08 |
August | 0.000 | 0.244614E+09 |
September | 0.000 | 0.893998E+10 |
October | 0.000 | 0.127788E+12 |
November | 0.000 | 0.192806E+12 |
December | 0.000 | 0.262805E+12 |
Annual Sum or Average | 0.140342E+13 | |
Minimum of Months | 0.000 | 0.126218E+08 |
Maximum of Months | 0.000 | 0.262805E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.262532E+12 |
February | 0.000 | 0.224962E+12 |
March | 0.000 | 0.218320E+12 |
April | 0.000 | 0.101309E+12 |
May | 0.000 | 0.359872E+10 |
June | 0.000 | 0.989719E+08 |
July | 0.000 | 0.126218E+08 |
August | 0.000 | 0.244614E+09 |
September | 0.000 | 0.893998E+10 |
October | 0.000 | 0.127788E+12 |
November | 0.000 | 0.192806E+12 |
December | 0.000 | 0.262805E+12 |
Annual Sum or Average | 0.140342E+13 | |
Minimum of Months | 0.000 | 0.126218E+08 |
Maximum of Months | 0.000 | 0.262805E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Meter
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.262532E+12 |
February | 0.000 | 0.224962E+12 |
March | 0.000 | 0.218320E+12 |
April | 0.000 | 0.101309E+12 |
May | 0.000 | 0.359872E+10 |
June | 0.000 | 0.989719E+08 |
July | 0.000 | 0.126218E+08 |
August | 0.000 | 0.244614E+09 |
September | 0.000 | 0.893998E+10 |
October | 0.000 | 0.127788E+12 |
November | 0.000 | 0.192806E+12 |
December | 0.000 | 0.262805E+12 |
Annual Sum or Average | 0.140342E+13 | |
Minimum of Months | 0.000 | 0.126218E+08 |
Maximum of Months | 0.000 | 0.262805E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Meter
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.262532E+12 |
February | 0.000 | 0.224962E+12 |
March | 0.000 | 0.218320E+12 |
April | 0.000 | 0.101309E+12 |
May | 0.000 | 0.359872E+10 |
June | 0.000 | 0.989719E+08 |
July | 0.000 | 0.126218E+08 |
August | 0.000 | 0.244614E+09 |
September | 0.000 | 0.893998E+10 |
October | 0.000 | 0.127788E+12 |
November | 0.000 | 0.192806E+12 |
December | 0.000 | 0.262805E+12 |
Annual Sum or Average | 0.140342E+13 | |
Minimum of Months | 0.000 | 0.126218E+08 |
Maximum of Months | 0.000 | 0.262805E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1617320.45 | 2815.11 | 21-JAN-07:05 | -9.0 | -9.2 | 0.191841E+09 | 236.59 | 21-JAN-08:20 | -7.0 | -7.3 |
February | 1995699.55 | 2531.34 | 11-FEB-08:05 | -6.0 | -6.5 | 0.177169E+09 | 236.59 | 11-FEB-08:20 | -5.9 | -6.4 |
March | 3502568.27 | 2678.57 | 25-MAR-07:05 | -12.8 | -13.4 | 0.208496E+09 | 236.60 | 18-MAR-07:19 | -1.7 | -3.1 |
April | 11102094.50 | 2865.69 | 01-APR-07:05 | -11.7 | -13.0 | 0.193721E+09 | 256.74 | 22-APR-15:00 | 15.00 | 6.58 |
May | 75243825.80 | 1974.84 | 27-MAY-07:05 | 0.10 | -0.8 | 0.211846E+09 | 301.58 | 12-MAY-15:50 | 20.00 | 9.27 |
June | 0.156715E+10 | 12985.16 | 24-JUN-07:03 | 12.70 | 12.16 | 0.252062E+09 | 330.44 | 24-JUN-07:10 | 12.70 | 12.16 |
July | 0.270187E+10 | 12970.72 | 29-JUL-07:02 | 16.88 | 12.94 | 0.247536E+09 | 344.90 | 22-JUL-07:10 | 17.48 | 13.78 |
August | 0.181485E+10 | 12941.17 | 12-AUG-07:02 | 15.00 | 10.62 | 0.259801E+09 | 344.89 | 05-AUG-07:10 | 14.18 | 12.19 |
September | 94187743.25 | 2536.11 | 30-SEP-07:05 | -5.0 | -5.5 | 0.197554E+09 | 301.58 | 02-SEP-15:39 | 16.70 | 10.54 |
October | 8704904.24 | 2901.66 | 28-OCT-07:05 | -9.3 | -10.3 | 0.193566E+09 | 236.69 | 07-OCT-07:19 | 4.63 | 3.88 |
November | 2253873.79 | 3177.96 | 18-NOV-08:05 | -11.6 | -12.0 | 0.184831E+09 | 236.59 | 04-NOV-07:19 | -8.3 | -9.7 |
December | 1788717.17 | 3343.28 | 30-DEC-08:05 | -14.2 | -14.6 | 0.191736E+09 | 236.60 | 23-DEC-08:20 | -2.4 | -3.8 |
Annual Sum or Average | 0.628427E+10 | 0.251016E+10 | ||||||||
Minimum of Months | 1617320.45 | 1974.84 | -14.2 | -14.6 | 0.177169E+09 | 236.59 | -8.3 | -9.7 | ||
Maximum of Months | 0.270187E+10 | 12985.16 | 16.88 | 12.94 | 0.259801E+09 | 344.90 | 20.00 | 13.78 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 0.166052E+09 | 4398.66 | 22-MAR-13:00 | 4.40 | 1.55 | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.1 |
April | 0.129510E+10 | 5298.34 | 24-APR-11:30 | 2.50 | -2.0 | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.2 |
May | 0.142201E+10 | 5359.41 | 16-MAY-07:03 | 3.58 | 2.19 | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.17 |
June | 0.160090E+10 | 5540.83 | 03-JUN-06:10 | 12.07 | 9.24 | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.13 |
July | 0.210313E+10 | 21918.63 | 23-JUL-14:12 | 25.20 | 15.33 | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 |
August | 0.259315E+10 | 7945.51 | 30-AUG-07:03 | 0.78 | -1.0 | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.82 |
September | 0.229428E+10 | 6818.60 | 28-SEP-08:55 | -1.1 | -1.9 | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 |
October | 0.438821E+09 | 6388.59 | 20-OCT-11:35 | -0.2 | -0.5 | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.8 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.8 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.119134E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.00 | 0.00 | -28.9 | -29.1 | ||
Maximum of Months | 0.259315E+10 | 21918.63 | 25.20 | 15.33 | 0.00 | 0.00 | 16.35 | 13.77 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -28.9 | -29.1 | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.2 | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 | 2.17 | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.13 | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.13 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.82 | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.82 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 1.42 | 0.11 | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.8 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.8 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.1 | 0.00 | 0.00 | -28.9 | -29.1 | ||
Maximum of Months | 0.00 | 0.00 | 16.35 | 13.77 | 0.00 | 0.00 | 16.35 | 13.77 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124127E+11 | 23665.29 | 19-JAN-06:01 | -2.5 |
February | 0.104348E+11 | 24067.63 | 09-FEB-06:01 | 0.00 |
March | 0.102205E+11 | 23840.72 | 22-MAR-05:01 | -1.9 |
April | 0.503069E+10 | 23964.38 | 20-APR-06:02 | 1.15 |
May | 0.129778E+10 | 24994.51 | 30-MAY-06:01 | 9.40 |
June | 81168986.00 | 14714.59 | 01-JUN-07:03 | 10.05 |
July | 10969212.83 | 12294.74 | 05-JUL-07:03 | 8.40 |
August | 0.135681E+09 | 15457.64 | 31-AUG-07:03 | -0.1 |
September | 0.214725E+10 | 24812.60 | 19-SEP-06:02 | 10.60 |
October | 0.629964E+10 | 24714.90 | 06-OCT-06:01 | 6.10 |
November | 0.105800E+11 | 23223.27 | 04-NOV-05:01 | -7.9 |
December | 0.121162E+11 | 23588.18 | 23-DEC-06:11 | -3.7 |
Annual Sum or Average | 0.707673E+11 | |||
Minimum of Months | 10969212.83 | 12294.74 | -7.9 | |
Maximum of Months | 0.124127E+11 | 24994.51 | 10.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.439695E+11 | 65231.41 | 30-JAN-05:21 | -25.6 |
February | 0.361635E+11 | 65215.00 | 26-FEB-07:21 | -25.6 |
March | 0.320350E+11 | 64889.67 | 03-MAR-03:22 | -25.3 |
April | 0.153891E+11 | 64927.99 | 02-APR-19:42 | -11.9 |
May | 0.102648E+10 | 30280.58 | 28-MAY-02:35 | 0.40 |
June | 0.151358E+09 | 1296.48 | 15-JUN-06:25 | 10.00 |
July | 0.105797E+09 | 1362.24 | 20-JUL-06:40 | 14.03 |
August | 0.149353E+09 | 1550.40 | 23-AUG-17:00 | 25.00 |
September | 0.200937E+10 | 53624.30 | 28-SEP-06:01 | -2.8 |
October | 0.194265E+11 | 64428.04 | 31-OCT-05:42 | -17.9 |
November | 0.330774E+11 | 64772.13 | 10-NOV-02:62 | -19.6 |
December | 0.426620E+11 | 64879.06 | 28-DEC-02:42 | -26.7 |
Annual Sum or Average | 0.226165E+12 | |||
Minimum of Months | 0.105797E+09 | 1296.48 | -26.7 | |
Maximum of Months | 0.439695E+11 | 65231.41 | 25.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128837E+12 | 84210.89 | 28-JAN-09:00 | -20.0 |
February | 0.113397E+12 | 84320.45 | 26-FEB-03:45 | -26.0 |
March | 0.113115E+12 | 83966.65 | 16-MAR-08:00 | -21.7 |
April | 0.530567E+11 | 83824.05 | 02-APR-06:50 | -16.6 |
May | 4045468.97 | 1592.26 | 03-MAY-03:30 | 4.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.413941E+09 | 17881.73 | 30-SEP-05:00 | -4.4 |
October | 0.637285E+11 | 83627.19 | 27-OCT-04:05 | -17.7 |
November | 0.874301E+11 | 83670.76 | 10-NOV-02:62 | -19.6 |
December | 0.129342E+12 | 84126.15 | 22-DEC-14:00 | -23.9 |
Annual Sum or Average | 0.689324E+12 | |||
Minimum of Months | 0.00 | 0.00 | -26.0 | |
Maximum of Months | 0.129342E+12 | 84320.45 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.162587E+10 | 1175.36 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.145495E+10 | 1175.36 | 01-FEB-08:09 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.159612E+10 | 1175.36 | 01-MAR-08:09 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.147719E+10 | 1146.51 | 04-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.151271E+10 | 1107.05 | 20-MAY-08:30 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.147217E+10 | 1104.69 | 08-JUN-07:30 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.148147E+10 | 1120.37 | 01-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.155575E+10 | 1116.64 | 18-AUG-15:00 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.150639E+10 | 1155.25 | 21-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.158288E+10 | 1175.36 | 03-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.156010E+10 | 1175.36 | 01-NOV-07:10 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.163201E+10 | 1175.36 | 01-DEC-08:09 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.184576E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.145495E+10 | 1104.69 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.163201E+10 | 1175.36 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.882361E+10 | 7916.98 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.807588E+10 | 7916.98 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.932993E+10 | 7916.98 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.874314E+10 | 7916.98 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.907677E+10 | 7916.98 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.899629E+10 | 7916.98 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.882361E+10 | 7916.98 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.932993E+10 | 7916.98 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.874314E+10 | 7916.98 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.882361E+10 | 7916.98 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.848998E+10 | 7916.98 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.882361E+10 | 7916.98 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106079E+12 | ||||
Minimum of Months | 0.807588E+10 | 7916.98 | 0.00 | 0.00 | |
Maximum of Months | 0.932993E+10 | 7916.98 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.102879E+11 | 9236.47 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.930290E+10 | 9236.47 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.104021E+11 | 9236.47 | 01-MAR-09:09 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.953077E+10 | 8879.33 | 01-APR-14:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.970498E+10 | 8879.33 | 02-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.948167E+10 | 8879.33 | 07-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.937530E+10 | 8879.33 | 06-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.100491E+11 | 9236.47 | 30-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.966856E+10 | 9236.47 | 18-SEP-14:30 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.100535E+11 | 9236.47 | 02-OCT-08:09 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.986691E+10 | 9236.47 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.102942E+11 | 9236.47 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.118018E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.930290E+10 | 8879.33 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.104021E+11 | 9236.47 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.162587E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586053E+10 |
February | 0.500553E+09 | 0.145495E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456586E+10 |
March | 0.587605E+09 | 0.159612E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507575E+10 |
April | 0.544079E+09 | 0.147719E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291143E+10 |
May | 0.565842E+09 | 0.151271E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153428E+10 |
June | 0.565842E+09 | 0.147217E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14024603.66 | 0.101762E+10 |
July | 0.544079E+09 | 0.148147E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22590136.98 | 0.836571E+09 |
August | 0.587605E+09 | 0.155575E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5174928.22 | 0.137266E+10 |
September | 0.544079E+09 | 0.150639E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186701E+10 |
October | 0.544079E+09 | 0.158288E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365318E+10 |
November | 0.522316E+09 | 0.156010E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534405E+10 |
December | 0.544079E+09 | 0.163201E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583937E+10 |
Annual Sum or Average | 0.659424E+10 | 0.184576E+11 | 0.319458E+11 | 41789668.85 | 0.398783E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.145495E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.836571E+09 |
Maximum of Months | 0.587605E+09 | 0.163201E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22590136.98 | 0.586053E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.882361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114950E+11 |
February | 0.00 | 0.807588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952445E+10 |
March | 0.00 | 0.932993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137257E+11 |
April | 0.00 | 0.874314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120796E+11 |
May | 0.00 | 0.907677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5925055.69 | 0.563906E+10 |
June | 0.00 | 0.899629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3555185.99 | 0.421163E+10 |
July | 0.00 | 0.882361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22987008.55 | 0.380732E+10 |
August | 0.00 | 0.932993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5443124.85 | 0.471391E+10 |
September | 0.00 | 0.874314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408290E+10 |
October | 0.00 | 0.882361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106536E+11 |
November | 0.00 | 0.848998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430582E+10 |
December | 0.00 | 0.882361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877326E+10 |
Annual Sum or Average | 0.106079E+12 | 37910375.08 | 0.930122E+11 | ||||||
Minimum of Months | 0.00 | 0.807588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380732E+10 |
Maximum of Months | 0.00 | 0.932993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22987008.55 | 0.137257E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.102879E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448105E+11 |
February | 0.00 | 0.930290E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368328E+11 |
March | 0.00 | 0.104021E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519528E+11 |
April | 0.00 | 0.953077E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151928E+09 | 0.371333E+11 |
May | 0.00 | 0.970498E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146250E+10 | 0.141712E+11 |
June | 0.00 | 0.948167E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.856977E+09 | 0.107628E+11 |
July | 0.00 | 0.937530E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393328E+09 | 0.132275E+11 |
August | 0.00 | 0.100491E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247124E+09 | 0.191774E+11 |
September | 0.00 | 0.966856E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1779012.79 | 0.157042E+11 |
October | 0.00 | 0.100535E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35162825.62 | 0.367687E+11 |
November | 0.00 | 0.986691E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171320E+11 |
December | 0.00 | 0.102942E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373456E+11 |
Annual Sum or Average | 0.118018E+12 | 0.107336E+12 | 0.314880E+10 | 0.335019E+12 | |||||
Minimum of Months | 0.00 | 0.930290E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107628E+11 |
Maximum of Months | 0.00 | 0.104021E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146250E+10 | 0.519528E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1175.36 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 24785.73 | 12-JAN-12:01 |
February | 659.25 | 01-FEB-08:09 | 1175.36 | 01-FEB-08:09 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 22172.22 | 27-FEB-07:05 |
March | 659.25 | 01-MAR-08:09 | 1175.36 | 01-MAR-08:09 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 19657.11 | 01-MAR-07:05 |
April | 659.25 | 01-APR-07:10 | 1146.51 | 04-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 16484.76 | 03-APR-06:30 |
May | 659.25 | 01-MAY-07:10 | 1107.05 | 20-MAY-08:30 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 6719.50 | 16-MAY-07:00 |
June | 659.25 | 01-JUN-07:10 | 1104.69 | 08-JUN-07:30 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 766.10 | 21-JUN-17:00 | 4715.51 | 02-JUN-06:10 |
July | 659.25 | 01-JUL-07:10 | 1120.37 | 01-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1991.59 | 21-JUL-16:10 | 5622.06 | 17-JUL-06:03 |
August | 659.25 | 01-AUG-07:10 | 1116.64 | 18-AUG-15:00 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 629.96 | 11-AUG-16:10 | 8448.83 | 31-AUG-06:10 |
September | 659.25 | 01-SEP-07:10 | 1155.25 | 21-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 9891.30 | 29-SEP-07:00 |
October | 659.25 | 02-OCT-07:10 | 1175.36 | 03-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 16472.86 | 31-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1175.36 | 01-NOV-07:10 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 19874.21 | 28-NOV-12:03 |
December | 659.25 | 01-DEC-08:09 | 1175.36 | 01-DEC-08:09 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 23012.40 | 15-DEC-12:02 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1104.69 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4715.51 | |||||
Maximum of Months | 659.25 | 1175.36 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1991.59 | 24785.73 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 7916.98 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 38917.34 | 28-JAN-17:00 |
February | 0.00 | 7916.98 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 24061.30 | 23-FEB-17:00 |
March | 0.00 | 7916.98 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 18292.65 | 25-MAR-15:10 |
April | 0.00 | 7916.98 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 20588.15 | 01-APR-18:52 |
May | 0.00 | 7916.98 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 893.38 | 30-MAY-18:00 | 10573.92 | 27-MAY-08:00 |
June | 0.00 | 7916.98 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.93 | 30-JUN-15:10 | 9293.42 | 24-JUN-21:00 |
July | 0.00 | 7916.98 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3150.72 | 21-JUL-16:00 | 5759.16 | 04-JUL-17:00 |
August | 0.00 | 7916.98 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 713.51 | 23-AUG-18:00 | 8901.48 | 29-AUG-20:00 |
September | 0.00 | 7916.98 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 5874.43 | 29-SEP-07:00 |
October | 0.00 | 7916.98 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 13656.34 | 27-OCT-06:03 |
November | 0.00 | 7916.98 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 13371.24 | 03-NOV-20:00 |
December | 0.00 | 7916.98 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 15525.65 | 21-DEC-18:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 7916.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5759.16 | |||
Maximum of Months | 0.00 | 7916.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3150.72 | 38917.34 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 9236.47 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 123756.19 | 28-JAN-15:00 |
February | 0.00 | 9236.47 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 85219.73 | 25-FEB-12:00 |
March | 0.00 | 9236.47 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 67928.28 | 25-MAR-09:00 |
April | 0.00 | 8879.33 | 01-APR-14:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4463.97 | 22-APR-16:00 | 64079.45 | 01-APR-18:52 |
May | 0.00 | 8879.33 | 02-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12459.81 | 30-MAY-18:00 | 40114.28 | 27-MAY-11:00 |
June | 0.00 | 8879.33 | 07-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10817.41 | 30-JUN-15:00 | 29636.19 | 24-JUN-21:00 |
July | 0.00 | 8879.33 | 06-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17965.94 | 21-JUL-16:00 | 18467.42 | 04-JUL-17:00 |
August | 0.00 | 9236.47 | 30-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6939.05 | 23-AUG-16:00 | 38460.45 | 31-AUG-09:00 |
September | 0.00 | 9236.47 | 18-SEP-14:30 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.30 | 17-SEP-16:00 | 18919.73 | 21-SEP-14:00 |
October | 0.00 | 9236.47 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3417.57 | 01-OCT-17:00 | 48540.28 | 31-OCT-09:00 |
November | 0.00 | 9236.47 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 49290.19 | 01-NOV-09:00 |
December | 0.00 | 9236.47 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 68748.60 | 22-DEC-14:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 8879.33 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18467.42 | ||||
Maximum of Months | 0.00 | 9236.47 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 17965.94 | 123756.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2815.11 | 21-JAN-07:05 | 1107.54 | 5128.84 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.10 |
February | 2531.34 | 11-FEB-08:05 | 2637.00 | 4701.43 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.92 |
March | 2678.57 | 25-MAR-07:05 | 2637.00 | 4467.00 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.11 |
April | 2865.69 | 01-APR-07:05 | 2637.00 | 4563.05 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 695.06 |
May | 1974.84 | 27-MAY-07:05 | 2637.00 | 4359.30 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 762.68 |
June | 12985.16 | 24-JUN-07:03 | 2637.00 | 4360.39 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.87 |
July | 12970.72 | 29-JUL-07:02 | 3296.25 | 5407.68 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.15 |
August | 12941.17 | 12-AUG-07:02 | 3296.25 | 5481.40 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.65 |
September | 2536.11 | 30-SEP-07:05 | 2637.00 | 4577.14 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.62 |
October | 2901.66 | 28-OCT-07:05 | 2637.00 | 4701.43 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 697.53 |
November | 3177.96 | 18-NOV-08:05 | 2637.00 | 4701.43 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.31 |
December | 3343.28 | 30-DEC-08:05 | 2637.00 | 4701.43 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.11 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1974.84 | 1107.54 | 4359.30 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.62 | |
Maximum of Months | 12985.16 | 3296.25 | 5481.40 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 4657.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7473.35 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 4657.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5519.22 |
March | 4398.66 | 22-MAR-13:00 | 0.00 | 7916.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5298.34 | 24-APR-11:30 | 0.00 | 7916.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 973.46 |
May | 5359.41 | 16-MAY-07:03 | 0.00 | 27942.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9137.76 |
June | 5540.83 | 03-JUN-06:10 | 0.00 | 5588.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.97 |
July | 21918.63 | 23-JUL-14:12 | 0.00 | 4657.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.24 |
August | 7945.51 | 30-AUG-07:03 | 0.00 | 27942.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4684.41 |
September | 6818.60 | 28-SEP-08:55 | 0.00 | 15833.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1804.21 |
October | 6388.59 | 20-OCT-11:35 | 0.00 | 15833.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2123.84 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 931.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6326.33 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 3725.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 931.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21918.63 | 0.00 | 27942.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9137.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 5433.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25678.08 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 5433.22 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19425.73 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 5433.22 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10063.27 |
April | 0.00 | 01-APR-00:10 | 0.00 | 1086.64 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34926.89 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 2173.29 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4220.82 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 1086.64 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2373.86 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 1086.64 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4230.59 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 1086.64 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8658.36 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 1086.64 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5852.87 |
October | 0.00 | 01-OCT-00:05 | 0.00 | 2173.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10933.48 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 1086.64 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20522.73 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 4346.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 1086.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 5433.22 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34926.89 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.479084E+11 | 38530.22 | 04-JAN-15:39 | 0.262532E+12 | 203722.91 | 30-JAN-08:09 |
February | 0.418928E+11 | 37581.17 | 02-FEB-09:30 | 0.224962E+12 | 206032.13 | 27-FEB-08:09 |
March | 0.455923E+11 | 35515.70 | 13-MAR-07:10 | 0.218320E+12 | 195700.81 | 02-MAR-08:09 |
April | 0.403486E+11 | 32975.77 | 01-APR-14:39 | 0.101309E+12 | 165352.38 | 03-APR-06:10 |
May | 0.393890E+11 | 32859.16 | 09-MAY-12:00 | 0.359872E+10 | 28013.69 | 27-MAY-07:10 |
June | 0.380582E+11 | 33647.74 | 30-JUN-14:20 | 98971944.71 | 8933.57 | 01-JUN-06:10 |
July | 0.382529E+11 | 35245.04 | 29-JUL-14:00 | 12621835.87 | 4767.21 | 05-JUL-07:10 |
August | 0.417083E+11 | 33191.09 | 10-AUG-14:00 | 0.244614E+09 | 14982.45 | 31-AUG-06:10 |
September | 0.409043E+11 | 32734.66 | 30-SEP-14:00 | 0.893998E+10 | 43330.71 | 30-SEP-04:00 |
October | 0.443413E+11 | 37563.48 | 31-OCT-08:09 | 0.127788E+12 | 173395.26 | 31-OCT-07:10 |
November | 0.451925E+11 | 38381.88 | 30-NOV-15:00 | 0.192806E+12 | 190357.24 | 29-NOV-08:09 |
December | 0.486262E+11 | 38530.13 | 29-DEC-15:39 | 0.262805E+12 | 197704.64 | 01-DEC-17:00 |
Annual Sum or Average | 0.512215E+12 | 0.140342E+13 | ||||
Minimum of Months | 0.380582E+11 | 32734.66 | 12621835.87 | 4767.21 | ||
Maximum of Months | 0.486262E+11 | 38530.22 | 0.262805E+12 | 206032.13 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.207374E+11 | 0.980215E+10 | 0.115358E+11 | 0.00 | 0.341470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241832E+10 | 0.00 |
February | 0.188337E+11 | 0.717049E+10 | 0.105871E+11 | 0.00 | 0.310018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220126E+10 | 0.00 |
March | 0.213281E+11 | 0.603320E+10 | 0.123357E+11 | 0.00 | 0.339947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249577E+10 | 0.00 |
April | 0.197511E+11 | 0.398346E+10 | 0.114862E+11 | 0.00 | 0.275701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237081E+10 | 0.00 |
May | 0.202945E+11 | 0.244938E+10 | 0.119357E+11 | 0.00 | 0.226191E+10 | 0.00 | 0.00 | 1837896.40 | 0.00 | 0.00 | 0.00 | 0.244571E+10 | 0.00 |
June | 0.199501E+11 | 0.125745E+10 | 0.118862E+11 | 0.00 | 0.223984E+10 | 0.00 | 0.00 | 0.371486E+09 | 0.00 | 0.00 | 0.00 | 0.235311E+10 | 0.00 |
July | 0.196804E+11 | 0.180722E+10 | 0.115358E+11 | 0.00 | 0.215451E+10 | 0.00 | 0.00 | 0.753906E+09 | 0.00 | 0.00 | 0.00 | 0.232114E+10 | 0.00 |
August | 0.209348E+11 | 0.336775E+10 | 0.123357E+11 | 0.00 | 0.232599E+10 | 0.00 | 0.00 | 0.374691E+09 | 0.00 | 0.00 | 0.00 | 0.236937E+10 | 0.00 |
September | 0.199181E+11 | 0.503792E+10 | 0.114862E+11 | 0.00 | 0.220417E+10 | 0.00 | 0.00 | 609083.67 | 0.00 | 0.00 | 0.00 | 0.225730E+10 | 0.00 |
October | 0.204599E+11 | 0.711696E+10 | 0.115358E+11 | 0.00 | 0.290314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232552E+10 | 0.00 |
November | 0.199170E+11 | 0.877962E+10 | 0.110862E+11 | 0.00 | 0.313307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227655E+10 | 0.00 |
December | 0.207498E+11 | 0.105711E+11 | 0.115358E+11 | 0.00 | 0.336813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240144E+10 | 0.00 |
Annual Sum or Average | 0.242555E+12 | 0.673767E+11 | 0.139282E+12 | 0.332621E+11 | 0.00 | 0.150253E+10 | 0.282363E+11 | ||||||
Minimum of Months | 0.188337E+11 | 0.125745E+10 | 0.105871E+11 | 0.00 | 0.215451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220126E+10 | 0.00 |
Maximum of Months | 0.213281E+11 | 0.105711E+11 | 0.123357E+11 | 0.00 | 0.341470E+10 | 0.00 | 0.00 | 0.753906E+09 | 0.00 | 0.00 | 0.00 | 0.249577E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.262532E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.224962E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.218320E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.101309E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.359872E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 98971944.71 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 12621835.87 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.244614E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.893998E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.127788E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.192806E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.262805E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140342E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 12621835.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.262805E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 18328.81 | 02-JAN-09:09 | 5045.44 | 01-JAN-06:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 2364.92 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 18328.81 | 01-FEB-09:09 | 5045.44 | 01-FEB-06:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 2364.92 | 01-FEB-07:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 18280.08 | 03-MAR-09:09 | 5045.44 | 01-MAR-06:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 2364.92 | 01-MAR-08:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 17927.99 | 04-APR-08:09 | 5045.44 | 01-APR-05:10 | 10112.62 | 01-APR-07:10 | 0.00 | 2364.92 | 01-APR-09:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 17903.36 | 20-MAY-08:30 | 5045.44 | 01-MAY-21:10 | 10112.62 | 01-MAY-07:10 | 0.00 | 2175.45 | 01-MAY-06:19 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 17883.92 | 07-JUN-08:09 | 5045.44 | 01-JUN-22:49 | 10112.62 | 01-JUN-07:10 | 0.00 | 2175.45 | 01-JUN-06:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 17897.29 | 29-JUL-08:00 | 5045.44 | 11-JUL-22:00 | 10112.62 | 01-JUL-07:10 | 0.00 | 2175.45 | 22-JUL-16:40 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 18262.78 | 31-AUG-08:09 | 5045.44 | 01-AUG-21:00 | 10112.62 | 01-AUG-07:10 | 0.00 | 2175.45 | 01-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 18275.79 | 30-SEP-08:09 | 5045.44 | 01-SEP-05:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 2364.92 | 30-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 18328.81 | 23-OCT-08:09 | 5045.44 | 01-OCT-05:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 2364.92 | 03-OCT-06:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 18328.81 | 01-NOV-08:09 | 5045.44 | 01-NOV-05:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 2364.92 | 01-NOV-06:49 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 18328.81 | 01-DEC-09:09 | 5045.44 | 01-DEC-06:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 2364.92 | 01-DEC-07:40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 17883.92 | 5045.44 | 10112.62 | 0.00 | 2175.45 | 0.00 | 0.00 | |||||
Maximum of Months | 18328.81 | 5045.44 | 10112.62 | 0.00 | 2364.92 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 3127.20 | 12-JAN-12:30 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 3120.89 | 24-FEB-12:00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 3120.36 | 15-MAR-11:50 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 3120.18 | 27-APR-11:09 | 0.00 |
May | 238.88 | 13-MAY-15:50 | 0.00 | 0.00 | 0.00 | 3120.34 | 06-MAY-11:30 | 0.00 |
June | 2114.93 | 30-JUN-14:00 | 0.00 | 0.00 | 0.00 | 3029.70 | 01-JUN-11:30 | 0.00 |
July | 3695.08 | 21-JUL-15:00 | 0.00 | 0.00 | 0.00 | 2878.32 | 01-JUL-11:20 | 0.00 |
August | 1392.24 | 05-AUG-07:10 | 0.00 | 0.00 | 0.00 | 2748.50 | 02-AUG-11:30 | 0.00 |
September | 168.01 | 02-SEP-15:00 | 0.00 | 0.00 | 0.00 | 2731.70 | 30-SEP-11:39 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 2842.64 | 31-OCT-11:50 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2985.17 | 29-NOV-12:39 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 3088.64 | 21-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2731.70 | 0.00 | ||
Maximum of Months | 3695.08 | 0.00 | 0.00 | 0.00 | 3127.20 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 38530.22 | 04-JAN-15:39 | 18328.81 | 10112.62 | 5045.44 | 0.00 | 2364.92 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 37581.17 | 02-FEB-09:30 | 18328.81 | 10112.62 | 5045.44 | 0.00 | 2364.92 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 35515.70 | 13-MAR-07:10 | 16310.76 | 10112.62 | 5045.44 | 0.00 | 2364.92 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32975.77 | 01-APR-14:39 | 17821.34 | 10112.62 | 0.00 | 0.00 | 2364.92 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32859.16 | 09-MAY-12:00 | 17894.03 | 10112.62 | 0.00 | 0.00 | 2175.45 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33647.74 | 30-JUN-14:20 | 17096.94 | 10112.62 | 0.00 | 0.00 | 2175.45 | 0.00 | 0.00 | 1880.96 | 0.00 |
July | 35245.04 | 29-JUL-14:00 | 17459.98 | 10112.62 | 0.00 | 0.00 | 2175.45 | 0.00 | 0.00 | 3221.99 | 0.00 |
August | 33191.09 | 10-AUG-14:00 | 17818.51 | 10112.62 | 0.00 | 0.00 | 2175.45 | 0.00 | 0.00 | 848.41 | 0.00 |
September | 32734.66 | 30-SEP-14:00 | 18204.91 | 10112.62 | 0.00 | 0.00 | 2175.45 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 37563.48 | 31-OCT-08:09 | 18328.81 | 10112.62 | 5045.44 | 0.00 | 2364.92 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 38381.88 | 30-NOV-15:00 | 18328.81 | 10112.62 | 5045.44 | 0.00 | 2364.92 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 38530.13 | 29-DEC-15:39 | 18328.81 | 10112.62 | 5045.44 | 0.00 | 2364.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 32734.66 | 16310.76 | 10112.62 | 0.00 | 0.00 | 2175.45 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38530.22 | 18328.81 | 10112.62 | 5045.44 | 0.00 | 2364.92 | 0.00 | 0.00 | 3221.99 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 203722.91 | 30-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 206032.13 | 27-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 195700.81 | 02-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 165352.38 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 28013.69 | 27-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 8933.57 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 4767.21 | 05-JUL-07:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 14982.45 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 43330.71 | 30-SEP-04:00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 173395.26 | 31-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 190357.24 | 29-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 197704.64 | 01-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 4767.21 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 206032.13 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 44.00 | 17.12 | 31.17 | 17.99 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 33.50 | 16.96 | 22.17 | 17.97 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21.83 | 17.01 | 17.50 | 17.51 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5.17 | 17.18 | 4.50 | 17.50 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.33 | 17.19 | 0.33 | 17.19 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6.00 | 17.27 | 5.00 | 17.72 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 30.33 | 17.86 | 25.67 | 18.38 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 46.33 | 18.42 | 42.33 | 18.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 187.50 | 17.52 | 148.67 | 18.19 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 46.33 | 18.42 | 42.33 | 18.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 120.33 | 14.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 102.50 | 14.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 101.83 | 14.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 57.00 | 14.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.83 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5.17 | 14.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72.00 | 14.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 112.00 | 14.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 115.50 | 14.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 687.17 | 14.41 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.33 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 100.50 | 6.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 7.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4.67 | 9.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5.67 | 9.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7.50 | 9.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 212.00 | 7.54 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.50 | 9.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.49 | 300.00 | 20.49 | 300.00 | 20.49 |
February | 276.00 | 20.57 | 276.00 | 20.57 | 276.00 | 20.57 |
March | 324.00 | 20.62 | 324.00 | 20.62 | 324.00 | 20.62 |
April | 300.00 | 20.72 | 300.00 | 20.72 | 300.00 | 20.72 |
May | 312.00 | 21.24 | 230.00 | 20.77 | 230.00 | 20.77 |
June | 256.67 | 23.28 | 13.83 | 20.57 | 13.83 | 20.57 |
July | 83.00 | 23.35 | 60.50 | 24.23 | 0.00 | 0.00 |
August | 234.50 | 23.07 | 34.33 | 22.73 | 15.00 | 20.70 |
September | 300.00 | 20.94 | 259.67 | 20.74 | 259.67 | 20.74 |
October | 300.00 | 20.71 | 300.00 | 20.71 | 300.00 | 20.71 |
November | 288.00 | 20.57 | 288.00 | 20.57 | 288.00 | 20.57 |
December | 300.00 | 20.48 | 300.00 | 20.48 | 300.00 | 20.48 |
Annual Sum or Average | 3274.17 | 21.15 | 2686.33 | 20.74 | 2606.50 | 20.63 |
Minimum of Months | 83.00 | 20.48 | 13.83 | 20.48 | 0.00 | 0.00 |
Maximum of Months | 324.00 | 23.35 | 324.00 | 24.23 | 324.00 | 20.77 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 8363841.29 | 1837896.40 | 4.67 | 8363841.29 | 0.00 | 0.00 | 0.18 | 13-MAY-15:50 | 0.00 | 01-MAY-00:05 | 1096.05 | 13-MAY-15:50 | 1096.05 | 13-MAY-15:50 | 0.00 | 13-MAY-15:00 | 238.88 | 13-MAY-15:50 | 0.00 | 01-MAY-00:05 |
June | 0.173630E+10 | 0.363802E+09 | 198.44 | 0.169127E+10 | 45024264.21 | 0.00 | 1.00 | 24-JUN-07:03 | 0.00 | 01-JUN-00:10 | 13050.53 | 24-JUN-07:03 | 13050.53 | 24-JUN-07:03 | 804.56 | 30-JUN-12:00 | 2627.95 | 24-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.315316E+10 | 0.645793E+09 | 233.12 | 0.299452E+10 | 0.158637E+09 | 0.00 | 1.00 | 15-JUL-07:02 | 0.00 | 01-JUL-00:10 | 13703.89 | 15-JUL-07:02 | 13345.98 | 29-JUL-07:02 | 1508.61 | 15-JUL-07:04 | 2747.87 | 15-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.180324E+10 | 0.373862E+09 | 188.66 | 0.172673E+10 | 76504698.46 | 0.00 | 1.00 | 05-AUG-07:02 | 0.00 | 01-AUG-00:10 | 13495.77 | 05-AUG-07:02 | 13115.97 | 12-AUG-07:02 | 782.05 | 05-AUG-07:04 | 2710.68 | 05-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 2756838.74 | 609083.67 | 1.33 | 2756838.74 | 0.00 | 0.00 | 0.12 | 02-SEP-16:00 | 0.00 | 01-SEP-00:10 | 763.16 | 02-SEP-16:00 | 763.16 | 02-SEP-16:00 | 0.00 | 01-SEP-00:10 | 168.01 | 02-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.670381E+10 | 0.138590E+10 | 626.22 | 0.642365E+10 | 0.280166E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.315316E+10 | 0.645793E+09 | 233.12 | 0.299452E+10 | 0.158637E+09 | 0.00 | 1.00 | 0.00 | 13703.89 | 13345.98 | 1508.61 | 2747.87 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 |
June | 31164557.78 | 7684606.34 | 7.00 | 30389832.73 | 774725.06 | 0.00 | 0.34 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 | 3674.83 | 30-JUN-15:00 | 3674.83 | 30-JUN-15:00 | 153.58 | 30-JUN-13:00 | 908.45 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.455134E+09 | 0.108113E+09 | 47.67 | 0.452385E+09 | 2748670.05 | 0.00 | 1.00 | 23-JUL-14:12 | 0.00 | 01-JUL-00:10 | 21906.78 | 23-JUL-14:12 | 21740.05 | 23-JUL-14:12 | 326.01 | 22-JUL-11:10 | 4879.15 | 23-JUL-14:38 | 0.00 | 01-JUL-00:10 |
August | 3446766.10 | 829497.01 | 8.00 | 3338448.76 | 108317.34 | 0.00 | 0.09 | 04-AUG-14:40 | 0.00 | 01-AUG-00:10 | 891.59 | 04-AUG-14:40 | 865.18 | 04-AUG-14:40 | 28.14 | 04-AUG-14:30 | 213.66 | 04-AUG-14:40 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.489745E+09 | 0.116627E+09 | 62.67 | 0.486113E+09 | 3631712.45 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.455134E+09 | 0.108113E+09 | 47.67 | 0.452385E+09 | 2748670.05 | 0.00 | 1.00 | 0.00 | 21906.78 | 21740.05 | 326.01 | 4879.15 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5.60 | 0.99 | 4.61 | 0.00 | 262.80 | 0.00 | 0.00 | 744.00 |
February | 33.28 | 11.72 | 21.57 | 3.99 | 221.68 | 0.00 | 0.00 | 672.00 |
March | 99.85 | 43.27 | 56.57 | 48.27 | 153.82 | 0.00 | 0.00 | 744.00 |
April | 235.11 | 121.75 | 113.36 | 210.21 | 79.32 | 0.00 | 0.00 | 720.00 |
May | 228.30 | 103.84 | 124.46 | 221.49 | 35.16 | 0.00 | 0.00 | 744.00 |
June | 250.41 | 106.74 | 143.67 | 247.80 | 23.14 | 0.00 | 0.00 | 720.00 |
July | 209.30 | 79.01 | 130.29 | 201.89 | 29.94 | 0.00 | 0.00 | 744.00 |
August | 172.54 | 73.24 | 99.31 | 158.60 | 42.76 | 0.00 | 0.00 | 744.00 |
September | 104.05 | 43.43 | 60.62 | 78.69 | 65.27 | 0.00 | 0.00 | 720.00 |
October | 40.82 | 12.28 | 28.55 | 12.32 | 134.29 | 0.00 | 0.00 | 744.00 |
November | 16.39 | 5.98 | 10.42 | 0.93 | 251.84 | 0.00 | 0.00 | 720.00 |
December | 1.47 | 0.16 | 1.31 | 0.00 | 279.81 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 116.73 | 50.30 | 66.42 | 99.07 | 131.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1.47 | 0.16 | 1.31 | 0.00 | 23.14 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 250.41 | 121.75 | 143.67 | 247.80 | 279.81 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5.60 | 0.99 | 4.61 | 0.00 | 262.80 | 0.00 | 0.00 | 744.00 |
February | 33.28 | 11.72 | 21.57 | 3.99 | 221.68 | 0.00 | 0.00 | 672.00 |
March | 99.85 | 43.27 | 56.57 | 48.27 | 153.82 | 0.00 | 0.00 | 744.00 |
April | 235.11 | 121.75 | 113.36 | 210.21 | 79.32 | 0.00 | 0.00 | 720.00 |
May | 228.30 | 103.84 | 124.46 | 221.49 | 35.16 | 0.00 | 0.00 | 744.00 |
June | 250.41 | 106.74 | 143.67 | 247.80 | 23.14 | 0.00 | 0.00 | 720.00 |
July | 209.30 | 79.01 | 130.29 | 201.89 | 29.94 | 0.00 | 0.00 | 744.00 |
August | 172.54 | 73.24 | 99.31 | 158.60 | 42.76 | 0.00 | 0.00 | 744.00 |
September | 104.05 | 43.43 | 60.62 | 78.69 | 65.27 | 0.00 | 0.00 | 720.00 |
October | 40.82 | 12.28 | 28.55 | 12.32 | 134.29 | 0.00 | 0.00 | 744.00 |
November | 16.39 | 5.98 | 10.42 | 0.93 | 251.84 | 0.00 | 0.00 | 720.00 |
December | 1.47 | 0.16 | 1.31 | 0.00 | 279.81 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 116.73 | 50.30 | 66.42 | 99.07 | 131.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1.47 | 0.16 | 1.31 | 0.00 | 23.14 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 250.41 | 121.75 | 143.67 | 247.80 | 279.81 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.35 | 0.00 | 2.35 | 0.00 | 154.48 | 0.00 | 0.00 | 744.00 |
February | 10.40 | 0.00 | 10.40 | 0.00 | 136.98 | 0.00 | 0.00 | 672.00 |
March | 27.91 | 0.01 | 27.90 | 2.08 | 98.64 | 0.00 | 0.00 | 744.00 |
April | 50.79 | 1.44 | 49.35 | 20.20 | 47.85 | 0.00 | 0.00 | 720.00 |
May | 77.93 | 12.68 | 65.25 | 56.84 | 18.25 | 0.00 | 0.00 | 744.00 |
June | 100.42 | 22.11 | 78.31 | 83.31 | 10.26 | 0.00 | 0.00 | 720.00 |
July | 84.76 | 14.02 | 70.74 | 67.93 | 14.80 | 0.00 | 0.00 | 744.00 |
August | 54.44 | 2.99 | 51.46 | 35.03 | 23.75 | 0.00 | 0.00 | 744.00 |
September | 30.26 | 0.09 | 30.17 | 11.70 | 39.70 | 0.00 | 0.00 | 720.00 |
October | 14.64 | 0.00 | 14.64 | 1.30 | 82.56 | 0.00 | 0.00 | 744.00 |
November | 4.54 | 0.00 | 4.54 | 0.00 | 151.72 | 0.00 | 0.00 | 720.00 |
December | 0.71 | 0.00 | 0.71 | 0.00 | 163.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.40 | 4.47 | 33.94 | 23.33 | 78.24 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 0.71 | 0.00 | 0.71 | 0.00 | 10.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 100.42 | 22.11 | 78.31 | 83.31 | 163.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.35 | 0.00 | 2.35 | 0.00 | 154.48 | 0.00 | 0.00 | 744.00 |
February | 10.40 | 0.00 | 10.40 | 0.00 | 136.98 | 0.00 | 0.00 | 672.00 |
March | 27.90 | 0.01 | 27.89 | 2.08 | 98.64 | 0.00 | 0.00 | 744.00 |
April | 50.79 | 1.44 | 49.35 | 20.20 | 47.85 | 0.00 | 0.00 | 720.00 |
May | 77.93 | 12.68 | 65.25 | 56.84 | 18.25 | 0.00 | 0.00 | 744.00 |
June | 100.42 | 22.11 | 78.31 | 83.30 | 10.26 | 0.00 | 0.00 | 720.00 |
July | 84.76 | 14.02 | 70.74 | 67.93 | 14.80 | 0.00 | 0.00 | 744.00 |
August | 54.44 | 2.99 | 51.46 | 35.03 | 23.75 | 0.00 | 0.00 | 744.00 |
September | 30.26 | 0.09 | 30.17 | 11.70 | 39.70 | 0.00 | 0.00 | 720.00 |
October | 14.64 | 0.00 | 14.64 | 1.30 | 82.56 | 0.00 | 0.00 | 744.00 |
November | 4.54 | 0.00 | 4.54 | 0.00 | 151.72 | 0.00 | 0.00 | 720.00 |
December | 0.71 | 0.00 | 0.71 | 0.00 | 163.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 38.40 | 4.47 | 33.94 | 23.33 | 78.24 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 0.71 | 0.00 | 0.71 | 0.00 | 10.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 100.42 | 22.11 | 78.31 | 83.30 | 163.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.80 | 0.25 | 2.54 | 0.00 | 138.11 | 0.00 | 0.00 | 744.00 |
February | 14.17 | 3.47 | 10.70 | 0.16 | 115.66 | 0.00 | 0.00 | 672.00 |
March | 49.75 | 21.16 | 28.59 | 33.66 | 77.57 | 0.00 | 0.00 | 744.00 |
April | 100.08 | 54.01 | 46.07 | 106.69 | 39.87 | 0.00 | 0.00 | 720.00 |
May | 130.57 | 74.32 | 56.25 | 154.13 | 18.89 | 0.00 | 0.00 | 744.00 |
June | 141.63 | 70.64 | 70.99 | 166.85 | 12.66 | 0.00 | 0.00 | 720.00 |
July | 127.07 | 61.47 | 65.60 | 144.96 | 18.17 | 0.00 | 0.00 | 744.00 |
August | 95.65 | 46.42 | 49.23 | 103.34 | 26.62 | 0.00 | 0.00 | 744.00 |
September | 51.67 | 20.46 | 31.21 | 48.29 | 35.95 | 0.00 | 0.00 | 720.00 |
October | 21.21 | 5.15 | 16.06 | 10.88 | 60.57 | 8.67 | 0.00 | 744.00 |
November | 5.31 | 0.44 | 4.87 | 0.00 | 136.37 | 0.00 | 0.00 | 720.00 |
December | 0.78 | 0.01 | 0.77 | 0.00 | 149.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.97 | 29.96 | 32.01 | 64.43 | 68.92 | 8.67 | 0.00 | 8760.00 |
Minimum of Months | 0.78 | 0.01 | 0.77 | 0.00 | 12.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 141.63 | 74.32 | 70.99 | 166.85 | 149.52 | 8.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.80 | 0.25 | 2.54 | 0.00 | 138.11 | 0.00 | 0.00 | 744.00 |
February | 14.17 | 3.47 | 10.70 | 0.16 | 115.66 | 0.00 | 0.00 | 672.00 |
March | 49.75 | 21.16 | 28.59 | 33.66 | 77.57 | 0.00 | 0.00 | 744.00 |
April | 100.08 | 54.01 | 46.07 | 106.69 | 39.87 | 0.00 | 0.00 | 720.00 |
May | 130.57 | 74.32 | 56.25 | 154.13 | 18.89 | 0.00 | 0.00 | 744.00 |
June | 141.63 | 70.64 | 70.99 | 166.85 | 12.66 | 0.00 | 0.00 | 720.00 |
July | 127.07 | 61.47 | 65.60 | 144.96 | 18.17 | 0.00 | 0.00 | 744.00 |
August | 95.65 | 46.42 | 49.23 | 103.34 | 26.62 | 0.00 | 0.00 | 744.00 |
September | 51.67 | 20.46 | 31.21 | 48.29 | 35.95 | 0.00 | 0.00 | 720.00 |
October | 21.21 | 5.15 | 16.06 | 10.88 | 60.57 | 8.67 | 0.00 | 744.00 |
November | 5.31 | 0.44 | 4.87 | 0.00 | 136.37 | 0.00 | 0.00 | 720.00 |
December | 0.78 | 0.01 | 0.77 | 0.00 | 149.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.97 | 29.96 | 32.01 | 64.43 | 68.92 | 8.67 | 0.00 | 8760.00 |
Minimum of Months | 0.78 | 0.01 | 0.77 | 0.00 | 12.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 141.63 | 74.32 | 70.99 | 166.85 | 149.52 | 8.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.80 | 0.25 | 2.54 | 0.00 | 138.11 | 0.00 | 0.00 | 744.00 |
February | 14.17 | 3.47 | 10.70 | 0.16 | 115.66 | 0.00 | 0.00 | 672.00 |
March | 49.75 | 21.16 | 28.59 | 33.66 | 77.57 | 0.00 | 0.00 | 744.00 |
April | 100.08 | 54.01 | 46.07 | 106.69 | 39.87 | 0.00 | 0.00 | 720.00 |
May | 130.57 | 74.32 | 56.25 | 154.13 | 18.89 | 0.00 | 0.00 | 744.00 |
June | 141.63 | 70.64 | 70.99 | 166.85 | 12.66 | 0.00 | 0.00 | 720.00 |
July | 127.07 | 61.47 | 65.60 | 144.96 | 18.17 | 0.00 | 0.00 | 744.00 |
August | 95.65 | 46.42 | 49.23 | 103.34 | 26.62 | 0.00 | 0.00 | 744.00 |
September | 51.67 | 20.46 | 31.21 | 48.29 | 35.95 | 0.00 | 0.00 | 720.00 |
October | 21.21 | 5.15 | 16.06 | 10.88 | 60.57 | 8.67 | 0.00 | 744.00 |
November | 5.31 | 0.44 | 4.87 | 0.00 | 136.37 | 0.00 | 0.00 | 720.00 |
December | 0.78 | 0.01 | 0.77 | 0.00 | 149.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.97 | 29.96 | 32.01 | 64.43 | 68.92 | 8.67 | 0.00 | 8760.00 |
Minimum of Months | 0.78 | 0.01 | 0.77 | 0.00 | 12.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 141.63 | 74.32 | 70.99 | 166.85 | 149.52 | 8.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.80 | 0.25 | 2.54 | 0.00 | 138.11 | 0.00 | 0.00 | 744.00 |
February | 14.17 | 3.47 | 10.70 | 0.16 | 115.66 | 0.00 | 0.00 | 672.00 |
March | 49.75 | 21.16 | 28.59 | 33.66 | 77.57 | 0.00 | 0.00 | 744.00 |
April | 100.08 | 54.01 | 46.07 | 106.69 | 39.87 | 0.00 | 0.00 | 720.00 |
May | 130.57 | 74.32 | 56.25 | 154.13 | 18.89 | 0.00 | 0.00 | 744.00 |
June | 141.63 | 70.64 | 70.99 | 166.85 | 12.66 | 0.00 | 0.00 | 720.00 |
July | 127.07 | 61.47 | 65.60 | 144.96 | 18.17 | 0.00 | 0.00 | 744.00 |
August | 95.65 | 46.42 | 49.23 | 103.34 | 26.62 | 0.00 | 0.00 | 744.00 |
September | 51.67 | 20.46 | 31.21 | 48.29 | 35.95 | 0.00 | 0.00 | 720.00 |
October | 21.21 | 5.15 | 16.06 | 10.88 | 60.57 | 8.67 | 0.00 | 744.00 |
November | 5.31 | 0.44 | 4.87 | 0.00 | 136.37 | 0.00 | 0.00 | 720.00 |
December | 0.78 | 0.01 | 0.77 | 0.00 | 149.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.97 | 29.96 | 32.01 | 64.43 | 68.92 | 8.67 | 0.00 | 8760.00 |
Minimum of Months | 0.78 | 0.01 | 0.77 | 0.00 | 12.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 141.63 | 74.32 | 70.99 | 166.85 | 149.52 | 8.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.80 | 0.25 | 2.54 | 0.00 | 138.11 | 0.00 | 0.00 | 744.00 |
February | 14.17 | 3.47 | 10.70 | 0.16 | 115.66 | 0.00 | 0.00 | 672.00 |
March | 49.75 | 21.16 | 28.59 | 33.66 | 77.57 | 0.00 | 0.00 | 744.00 |
April | 100.08 | 54.01 | 46.07 | 106.69 | 39.87 | 0.00 | 0.00 | 720.00 |
May | 130.57 | 74.32 | 56.25 | 154.13 | 18.89 | 0.00 | 0.00 | 744.00 |
June | 141.63 | 70.64 | 70.99 | 166.85 | 12.66 | 0.00 | 0.00 | 720.00 |
July | 127.07 | 61.47 | 65.60 | 144.96 | 18.17 | 0.00 | 0.00 | 744.00 |
August | 95.65 | 46.42 | 49.23 | 103.34 | 26.62 | 0.00 | 0.00 | 744.00 |
September | 51.67 | 20.46 | 31.21 | 48.29 | 35.95 | 0.00 | 0.00 | 720.00 |
October | 21.21 | 5.15 | 16.06 | 10.88 | 60.57 | 8.67 | 0.00 | 744.00 |
November | 5.31 | 0.44 | 4.87 | 0.00 | 136.37 | 0.00 | 0.00 | 720.00 |
December | 0.78 | 0.01 | 0.77 | 0.00 | 149.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.97 | 29.96 | 32.01 | 64.43 | 68.92 | 8.67 | 0.00 | 8760.00 |
Minimum of Months | 0.78 | 0.01 | 0.77 | 0.00 | 12.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 141.63 | 74.32 | 70.99 | 166.85 | 149.52 | 8.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.80 | 0.25 | 2.54 | 0.00 | 138.11 | 0.00 | 0.00 | 744.00 |
February | 14.17 | 3.47 | 10.70 | 0.16 | 115.66 | 0.00 | 0.00 | 672.00 |
March | 49.75 | 21.16 | 28.59 | 33.66 | 77.57 | 0.00 | 0.00 | 744.00 |
April | 100.08 | 54.01 | 46.07 | 106.69 | 39.87 | 0.00 | 0.00 | 720.00 |
May | 130.57 | 74.32 | 56.25 | 154.13 | 18.89 | 0.00 | 0.00 | 744.00 |
June | 141.63 | 70.64 | 70.99 | 166.85 | 12.66 | 0.00 | 0.00 | 720.00 |
July | 127.07 | 61.47 | 65.60 | 144.96 | 18.17 | 0.00 | 0.00 | 744.00 |
August | 95.65 | 46.42 | 49.23 | 103.34 | 26.62 | 0.00 | 0.00 | 744.00 |
September | 51.67 | 20.46 | 31.21 | 48.29 | 35.95 | 0.00 | 0.00 | 720.00 |
October | 21.21 | 5.15 | 16.06 | 10.88 | 60.57 | 8.67 | 0.00 | 744.00 |
November | 5.31 | 0.44 | 4.87 | 0.00 | 136.37 | 0.00 | 0.00 | 720.00 |
December | 0.78 | 0.01 | 0.77 | 0.00 | 149.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.97 | 29.96 | 32.01 | 64.43 | 68.92 | 8.67 | 0.00 | 8760.00 |
Minimum of Months | 0.78 | 0.01 | 0.77 | 0.00 | 12.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 141.63 | 74.32 | 70.99 | 166.85 | 149.52 | 8.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.80 | 0.25 | 2.54 | 0.00 | 138.11 | 0.00 | 0.00 | 744.00 |
February | 14.17 | 3.47 | 10.70 | 0.16 | 115.66 | 0.00 | 0.00 | 672.00 |
March | 49.75 | 21.16 | 28.59 | 33.66 | 77.57 | 0.00 | 0.00 | 744.00 |
April | 100.08 | 54.01 | 46.07 | 106.69 | 39.87 | 0.00 | 0.00 | 720.00 |
May | 130.57 | 74.32 | 56.25 | 154.13 | 18.89 | 0.00 | 0.00 | 744.00 |
June | 141.63 | 70.64 | 70.99 | 166.85 | 12.66 | 0.00 | 0.00 | 720.00 |
July | 127.07 | 61.47 | 65.60 | 144.96 | 18.17 | 0.00 | 0.00 | 744.00 |
August | 95.65 | 46.42 | 49.23 | 103.34 | 26.62 | 0.00 | 0.00 | 744.00 |
September | 51.67 | 20.46 | 31.21 | 48.29 | 35.95 | 0.00 | 0.00 | 720.00 |
October | 21.21 | 5.15 | 16.06 | 10.88 | 60.57 | 8.67 | 0.00 | 744.00 |
November | 5.31 | 0.44 | 4.87 | 0.00 | 136.37 | 0.00 | 0.00 | 720.00 |
December | 0.78 | 0.01 | 0.77 | 0.00 | 149.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.97 | 29.96 | 32.01 | 64.43 | 68.92 | 8.67 | 0.00 | 8760.00 |
Minimum of Months | 0.78 | 0.01 | 0.77 | 0.00 | 12.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 141.63 | 74.32 | 70.99 | 166.85 | 149.52 | 8.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.80 | 0.25 | 2.54 | 0.00 | 138.11 | 0.00 | 0.00 | 744.00 |
February | 14.17 | 3.47 | 10.70 | 0.16 | 115.66 | 0.00 | 0.00 | 672.00 |
March | 49.75 | 21.16 | 28.59 | 33.66 | 77.57 | 0.00 | 0.00 | 744.00 |
April | 100.08 | 54.01 | 46.07 | 106.69 | 39.87 | 0.00 | 0.00 | 720.00 |
May | 130.57 | 74.32 | 56.25 | 154.13 | 18.89 | 0.00 | 0.00 | 744.00 |
June | 141.63 | 70.64 | 70.99 | 166.85 | 12.66 | 0.00 | 0.00 | 720.00 |
July | 127.07 | 61.47 | 65.60 | 144.96 | 18.17 | 0.00 | 0.00 | 744.00 |
August | 95.65 | 46.42 | 49.23 | 103.34 | 26.62 | 0.00 | 0.00 | 744.00 |
September | 51.67 | 20.46 | 31.21 | 48.29 | 35.95 | 0.00 | 0.00 | 720.00 |
October | 21.21 | 5.15 | 16.06 | 10.88 | 60.57 | 8.67 | 0.00 | 744.00 |
November | 5.31 | 0.44 | 4.87 | 0.00 | 136.37 | 0.00 | 0.00 | 720.00 |
December | 0.78 | 0.01 | 0.77 | 0.00 | 149.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.97 | 29.96 | 32.01 | 64.43 | 68.92 | 8.67 | 0.00 | 8760.00 |
Minimum of Months | 0.78 | 0.01 | 0.77 | 0.00 | 12.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 141.63 | 74.32 | 70.99 | 166.85 | 149.52 | 8.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.80 | 0.25 | 2.54 | 0.00 | 138.11 | 0.00 | 0.00 | 744.00 |
February | 14.17 | 3.47 | 10.70 | 0.16 | 115.66 | 0.00 | 0.00 | 672.00 |
March | 49.75 | 21.16 | 28.59 | 33.66 | 77.57 | 0.00 | 0.00 | 744.00 |
April | 100.08 | 54.01 | 46.07 | 106.69 | 39.87 | 0.00 | 0.00 | 720.00 |
May | 130.57 | 74.32 | 56.25 | 154.13 | 18.89 | 0.00 | 0.00 | 744.00 |
June | 141.63 | 70.64 | 70.99 | 166.85 | 12.66 | 0.00 | 0.00 | 720.00 |
July | 127.07 | 61.47 | 65.60 | 144.96 | 18.17 | 0.00 | 0.00 | 744.00 |
August | 95.65 | 46.42 | 49.23 | 103.34 | 26.62 | 0.00 | 0.00 | 744.00 |
September | 51.67 | 20.46 | 31.21 | 48.29 | 35.95 | 0.00 | 0.00 | 720.00 |
October | 21.21 | 5.15 | 16.06 | 10.88 | 60.57 | 8.67 | 0.00 | 744.00 |
November | 5.31 | 0.44 | 4.87 | 0.00 | 136.37 | 0.00 | 0.00 | 720.00 |
December | 0.78 | 0.01 | 0.77 | 0.00 | 149.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.97 | 29.96 | 32.01 | 64.43 | 68.92 | 8.67 | 0.00 | 8760.00 |
Minimum of Months | 0.78 | 0.01 | 0.77 | 0.00 | 12.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 141.63 | 74.32 | 70.99 | 166.85 | 149.52 | 8.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.80 | 0.25 | 2.54 | 0.00 | 138.11 | 0.00 | 0.00 | 744.00 |
February | 14.17 | 3.47 | 10.70 | 0.16 | 115.66 | 0.00 | 0.00 | 672.00 |
March | 49.75 | 21.16 | 28.59 | 33.66 | 77.57 | 0.00 | 0.00 | 744.00 |
April | 100.08 | 54.01 | 46.07 | 106.69 | 39.87 | 0.00 | 0.00 | 720.00 |
May | 130.57 | 74.32 | 56.25 | 154.13 | 18.89 | 0.00 | 0.00 | 744.00 |
June | 141.63 | 70.64 | 70.99 | 166.85 | 12.66 | 0.00 | 0.00 | 720.00 |
July | 127.07 | 61.47 | 65.60 | 144.96 | 18.17 | 0.00 | 0.00 | 744.00 |
August | 95.65 | 46.42 | 49.23 | 103.34 | 26.62 | 0.00 | 0.00 | 744.00 |
September | 51.67 | 20.46 | 31.21 | 48.29 | 35.95 | 0.00 | 0.00 | 720.00 |
October | 21.21 | 5.15 | 16.06 | 10.88 | 60.57 | 8.67 | 0.00 | 744.00 |
November | 5.31 | 0.44 | 4.87 | 0.00 | 136.37 | 0.00 | 0.00 | 720.00 |
December | 0.78 | 0.01 | 0.77 | 0.00 | 149.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.97 | 29.96 | 32.01 | 64.43 | 68.92 | 8.67 | 0.00 | 8760.00 |
Minimum of Months | 0.78 | 0.01 | 0.77 | 0.00 | 12.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 141.63 | 74.32 | 70.99 | 166.85 | 149.52 | 8.67 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 14985932.57 | 2645057.14 | 12340875.43 | 0.00 | 0.703882E+09 |
February | 80519690.33 | 28344611.01 | 52175079.32 | 9651863.86 | 0.536297E+09 |
March | 0.267430E+09 | 0.115908E+09 | 0.151522E+09 | 0.129284E+09 | 0.411993E+09 |
April | 0.609402E+09 | 0.315567E+09 | 0.293835E+09 | 0.544852E+09 | 0.205608E+09 |
May | 0.611477E+09 | 0.278124E+09 | 0.333354E+09 | 0.593242E+09 | 94169586.77 |
June | 0.649058E+09 | 0.276660E+09 | 0.372398E+09 | 0.642297E+09 | 59978394.40 |
July | 0.560598E+09 | 0.211622E+09 | 0.348976E+09 | 0.540750E+09 | 80196240.82 |
August | 0.462139E+09 | 0.196154E+09 | 0.265985E+09 | 0.424788E+09 | 0.114531E+09 |
September | 0.269696E+09 | 0.112560E+09 | 0.157136E+09 | 0.203962E+09 | 0.169177E+09 |
October | 0.109342E+09 | 32877436.23 | 76464287.12 | 33004692.79 | 0.359675E+09 |
November | 42492319.69 | 15488646.91 | 27003672.78 | 2413655.66 | 0.652767E+09 |
December | 3946204.80 | 431601.16 | 3514603.63 | 0.00 | 0.749445E+09 |
Annual Sum or Average | 0.368109E+10 | 0.158638E+10 | 0.209470E+10 | 0.312424E+10 | 0.413772E+10 |
Minimum of Months | 3946204.80 | 431601.16 | 3514603.63 | 0.00 | 59978394.40 |
Maximum of Months | 0.649058E+09 | 0.315567E+09 | 0.372398E+09 | 0.642297E+09 | 0.749445E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 14985932.57 | 2645057.14 | 12340875.43 | 0.00 | 0.703882E+09 |
February | 80519690.33 | 28344611.01 | 52175079.32 | 9651863.86 | 0.536297E+09 |
March | 0.267430E+09 | 0.115908E+09 | 0.151522E+09 | 0.129284E+09 | 0.411993E+09 |
April | 0.609402E+09 | 0.315567E+09 | 0.293835E+09 | 0.544852E+09 | 0.205608E+09 |
May | 0.611477E+09 | 0.278124E+09 | 0.333354E+09 | 0.593242E+09 | 94169586.77 |
June | 0.649058E+09 | 0.276660E+09 | 0.372398E+09 | 0.642297E+09 | 59978394.40 |
July | 0.560598E+09 | 0.211622E+09 | 0.348976E+09 | 0.540750E+09 | 80196240.82 |
August | 0.462139E+09 | 0.196154E+09 | 0.265985E+09 | 0.424788E+09 | 0.114531E+09 |
September | 0.269696E+09 | 0.112560E+09 | 0.157136E+09 | 0.203962E+09 | 0.169177E+09 |
October | 0.109342E+09 | 32877436.23 | 76464287.12 | 33004692.79 | 0.359675E+09 |
November | 42492319.69 | 15488646.91 | 27003672.78 | 2413655.66 | 0.652767E+09 |
December | 3946204.80 | 431601.16 | 3514603.63 | 0.00 | 0.749445E+09 |
Annual Sum or Average | 0.368109E+10 | 0.158638E+10 | 0.209470E+10 | 0.312424E+10 | 0.413772E+10 |
Minimum of Months | 3946204.80 | 431601.16 | 3514603.63 | 0.00 | 59978394.40 |
Maximum of Months | 0.649058E+09 | 0.315567E+09 | 0.372398E+09 | 0.642297E+09 | 0.749445E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6302931.70 | 0.00 | 6302931.70 | 0.00 | 0.413761E+09 |
February | 25165683.50 | 0.00 | 25165683.50 | 0.00 | 0.331377E+09 |
March | 74741716.40 | 25577.41 | 74716138.99 | 5578397.66 | 0.264206E+09 |
April | 0.131655E+09 | 3744832.43 | 0.127910E+09 | 52365220.97 | 0.124015E+09 |
May | 0.208734E+09 | 33965646.86 | 0.174768E+09 | 0.152241E+09 | 48879448.59 |
June | 0.260300E+09 | 57319216.88 | 0.202981E+09 | 0.215932E+09 | 26599591.59 |
July | 0.227023E+09 | 37551105.56 | 0.189472E+09 | 0.181944E+09 | 39651431.40 |
August | 0.145818E+09 | 7995598.69 | 0.137822E+09 | 93818511.98 | 63611651.59 |
September | 78441280.81 | 232334.59 | 78208946.23 | 30323139.44 | 0.102914E+09 |
October | 39223333.47 | 0.00 | 39223333.47 | 3483261.28 | 0.221133E+09 |
November | 11779730.14 | 0.00 | 11779730.14 | 0.00 | 0.393255E+09 |
December | 1911978.81 | 0.00 | 1911978.81 | 0.00 | 0.437987E+09 |
Annual Sum or Average | 0.121110E+10 | 0.140834E+09 | 0.107026E+10 | 0.735686E+09 | 0.246739E+10 |
Minimum of Months | 1911978.81 | 0.00 | 1911978.81 | 0.00 | 26599591.59 |
Maximum of Months | 0.260300E+09 | 57319216.88 | 0.202981E+09 | 0.215932E+09 | 0.437987E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6302703.87 | 0.00 | 6302703.87 | 0.00 | 0.413760E+09 |
February | 25164831.48 | 0.00 | 25164831.48 | 0.00 | 0.331377E+09 |
March | 74739336.60 | 25576.21 | 74713760.39 | 5577659.54 | 0.264207E+09 |
April | 0.131651E+09 | 3744656.91 | 0.127906E+09 | 52362321.17 | 0.124015E+09 |
May | 0.208727E+09 | 33964054.85 | 0.174763E+09 | 0.152235E+09 | 48879276.93 |
June | 0.260291E+09 | 57316530.26 | 0.202974E+09 | 0.215922E+09 | 26599553.36 |
July | 0.227015E+09 | 37549345.49 | 0.189466E+09 | 0.181936E+09 | 39651427.50 |
August | 0.145813E+09 | 7995223.92 | 0.137818E+09 | 93813963.08 | 63611486.54 |
September | 78438688.88 | 232323.70 | 78206365.18 | 30321217.97 | 0.102914E+09 |
October | 39221989.80 | 0.00 | 39221989.80 | 3482913.83 | 0.221133E+09 |
November | 11779304.36 | 0.00 | 11779304.36 | 0.00 | 0.393255E+09 |
December | 1911906.67 | 0.00 | 1911906.67 | 0.00 | 0.437986E+09 |
Annual Sum or Average | 0.121106E+10 | 0.140828E+09 | 0.107023E+10 | 0.735651E+09 | 0.246739E+10 |
Minimum of Months | 1911906.67 | 0.00 | 1911906.67 | 0.00 | 26599553.36 |
Maximum of Months | 0.260291E+09 | 57316530.26 | 0.202974E+09 | 0.215922E+09 | 0.437986E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7490470.68 | 679356.78 | 6811113.89 | 0.00 | 0.369921E+09 |
February | 34272105.70 | 8386386.85 | 25885718.86 | 380303.29 | 0.279810E+09 |
March | 0.133251E+09 | 56683499.46 | 76567866.70 | 90150841.96 | 0.207753E+09 |
April | 0.259413E+09 | 0.139992E+09 | 0.119421E+09 | 0.276538E+09 | 0.103353E+09 |
May | 0.349706E+09 | 0.199048E+09 | 0.150658E+09 | 0.412817E+09 | 50599281.09 |
June | 0.367113E+09 | 0.183109E+09 | 0.184004E+09 | 0.432474E+09 | 32810776.99 |
July | 0.340337E+09 | 0.164638E+09 | 0.175699E+09 | 0.388268E+09 | 48664608.15 |
August | 0.256191E+09 | 0.124337E+09 | 0.131854E+09 | 0.276778E+09 | 71289999.19 |
September | 0.133930E+09 | 53038176.40 | 80892308.04 | 0.125171E+09 | 93186889.53 |
October | 56802044.74 | 13782522.86 | 43019521.89 | 29142259.32 | 0.162223E+09 |
November | 13774258.88 | 1138326.65 | 12635932.23 | 0.00 | 0.353464E+09 |
December | 2099864.67 | 39429.99 | 2060434.68 | 0.00 | 0.400474E+09 |
Annual Sum or Average | 0.195438E+10 | 0.944871E+09 | 0.100951E+10 | 0.203172E+10 | 0.217355E+10 |
Minimum of Months | 2099864.67 | 39429.99 | 2060434.68 | 0.00 | 32810776.99 |
Maximum of Months | 0.367113E+09 | 0.199048E+09 | 0.184004E+09 | 0.432474E+09 | 0.400474E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7490470.68 | 679356.78 | 6811113.89 | 0.00 | 0.369921E+09 |
February | 34272105.70 | 8386386.85 | 25885718.86 | 380303.29 | 0.279810E+09 |
March | 0.133251E+09 | 56683499.46 | 76567866.70 | 90150841.96 | 0.207753E+09 |
April | 0.259413E+09 | 0.139992E+09 | 0.119421E+09 | 0.276538E+09 | 0.103353E+09 |
May | 0.349706E+09 | 0.199048E+09 | 0.150658E+09 | 0.412817E+09 | 50599281.09 |
June | 0.367113E+09 | 0.183109E+09 | 0.184004E+09 | 0.432474E+09 | 32810776.99 |
July | 0.340337E+09 | 0.164638E+09 | 0.175699E+09 | 0.388268E+09 | 48664608.15 |
August | 0.256191E+09 | 0.124337E+09 | 0.131854E+09 | 0.276778E+09 | 71289999.19 |
September | 0.133930E+09 | 53038176.40 | 80892308.04 | 0.125171E+09 | 93186889.53 |
October | 56802044.74 | 13782522.86 | 43019521.89 | 29142259.32 | 0.162223E+09 |
November | 13774258.88 | 1138326.65 | 12635932.23 | 0.00 | 0.353464E+09 |
December | 2099864.67 | 39429.99 | 2060434.68 | 0.00 | 0.400474E+09 |
Annual Sum or Average | 0.195438E+10 | 0.944871E+09 | 0.100951E+10 | 0.203172E+10 | 0.217355E+10 |
Minimum of Months | 2099864.67 | 39429.99 | 2060434.68 | 0.00 | 32810776.99 |
Maximum of Months | 0.367113E+09 | 0.199048E+09 | 0.184004E+09 | 0.432474E+09 | 0.400474E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7490470.68 | 679356.78 | 6811113.89 | 0.00 | 0.369921E+09 |
February | 34272105.70 | 8386386.85 | 25885718.86 | 380303.29 | 0.279810E+09 |
March | 0.133251E+09 | 56683499.46 | 76567866.70 | 90150841.96 | 0.207753E+09 |
April | 0.259413E+09 | 0.139992E+09 | 0.119421E+09 | 0.276538E+09 | 0.103353E+09 |
May | 0.349706E+09 | 0.199048E+09 | 0.150658E+09 | 0.412817E+09 | 50599281.09 |
June | 0.367113E+09 | 0.183109E+09 | 0.184004E+09 | 0.432474E+09 | 32810776.99 |
July | 0.340337E+09 | 0.164638E+09 | 0.175699E+09 | 0.388268E+09 | 48664608.15 |
August | 0.256191E+09 | 0.124337E+09 | 0.131854E+09 | 0.276778E+09 | 71289999.19 |
September | 0.133930E+09 | 53038176.40 | 80892308.04 | 0.125171E+09 | 93186889.53 |
October | 56802044.74 | 13782522.86 | 43019521.89 | 29142259.32 | 0.162223E+09 |
November | 13774258.88 | 1138326.65 | 12635932.23 | 0.00 | 0.353464E+09 |
December | 2099864.67 | 39429.99 | 2060434.68 | 0.00 | 0.400474E+09 |
Annual Sum or Average | 0.195438E+10 | 0.944871E+09 | 0.100951E+10 | 0.203172E+10 | 0.217355E+10 |
Minimum of Months | 2099864.67 | 39429.99 | 2060434.68 | 0.00 | 32810776.99 |
Maximum of Months | 0.367113E+09 | 0.199048E+09 | 0.184004E+09 | 0.432474E+09 | 0.400474E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7490470.68 | 679356.78 | 6811113.89 | 0.00 | 0.369921E+09 |
February | 34272105.70 | 8386386.85 | 25885718.86 | 380303.29 | 0.279810E+09 |
March | 0.133251E+09 | 56683499.46 | 76567866.70 | 90150841.96 | 0.207753E+09 |
April | 0.259413E+09 | 0.139992E+09 | 0.119421E+09 | 0.276538E+09 | 0.103353E+09 |
May | 0.349706E+09 | 0.199048E+09 | 0.150658E+09 | 0.412817E+09 | 50599281.09 |
June | 0.367113E+09 | 0.183109E+09 | 0.184004E+09 | 0.432474E+09 | 32810776.99 |
July | 0.340337E+09 | 0.164638E+09 | 0.175699E+09 | 0.388268E+09 | 48664608.15 |
August | 0.256191E+09 | 0.124337E+09 | 0.131854E+09 | 0.276778E+09 | 71289999.19 |
September | 0.133930E+09 | 53038176.40 | 80892308.04 | 0.125171E+09 | 93186889.53 |
October | 56802044.74 | 13782522.86 | 43019521.89 | 29142259.32 | 0.162223E+09 |
November | 13774258.88 | 1138326.65 | 12635932.23 | 0.00 | 0.353464E+09 |
December | 2099864.67 | 39429.99 | 2060434.68 | 0.00 | 0.400474E+09 |
Annual Sum or Average | 0.195438E+10 | 0.944871E+09 | 0.100951E+10 | 0.203172E+10 | 0.217355E+10 |
Minimum of Months | 2099864.67 | 39429.99 | 2060434.68 | 0.00 | 32810776.99 |
Maximum of Months | 0.367113E+09 | 0.199048E+09 | 0.184004E+09 | 0.432474E+09 | 0.400474E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7490470.68 | 679356.78 | 6811113.89 | 0.00 | 0.369921E+09 |
February | 34272105.70 | 8386386.85 | 25885718.86 | 380303.29 | 0.279810E+09 |
March | 0.133251E+09 | 56683499.46 | 76567866.70 | 90150841.96 | 0.207753E+09 |
April | 0.259413E+09 | 0.139992E+09 | 0.119421E+09 | 0.276538E+09 | 0.103353E+09 |
May | 0.349706E+09 | 0.199048E+09 | 0.150658E+09 | 0.412817E+09 | 50599281.09 |
June | 0.367113E+09 | 0.183109E+09 | 0.184004E+09 | 0.432474E+09 | 32810776.99 |
July | 0.340337E+09 | 0.164638E+09 | 0.175699E+09 | 0.388268E+09 | 48664608.15 |
August | 0.256191E+09 | 0.124337E+09 | 0.131854E+09 | 0.276778E+09 | 71289999.19 |
September | 0.133930E+09 | 53038176.40 | 80892308.04 | 0.125171E+09 | 93186889.53 |
October | 56802044.74 | 13782522.86 | 43019521.89 | 29142259.32 | 0.162223E+09 |
November | 13774258.88 | 1138326.65 | 12635932.23 | 0.00 | 0.353464E+09 |
December | 2099864.67 | 39429.99 | 2060434.68 | 0.00 | 0.400474E+09 |
Annual Sum or Average | 0.195438E+10 | 0.944871E+09 | 0.100951E+10 | 0.203172E+10 | 0.217355E+10 |
Minimum of Months | 2099864.67 | 39429.99 | 2060434.68 | 0.00 | 32810776.99 |
Maximum of Months | 0.367113E+09 | 0.199048E+09 | 0.184004E+09 | 0.432474E+09 | 0.400474E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7490470.68 | 679356.78 | 6811113.89 | 0.00 | 0.369921E+09 |
February | 34272105.70 | 8386386.85 | 25885718.86 | 380303.29 | 0.279810E+09 |
March | 0.133251E+09 | 56683499.46 | 76567866.70 | 90150841.96 | 0.207753E+09 |
April | 0.259413E+09 | 0.139992E+09 | 0.119421E+09 | 0.276538E+09 | 0.103353E+09 |
May | 0.349706E+09 | 0.199048E+09 | 0.150658E+09 | 0.412817E+09 | 50599281.09 |
June | 0.367113E+09 | 0.183109E+09 | 0.184004E+09 | 0.432474E+09 | 32810776.99 |
July | 0.340337E+09 | 0.164638E+09 | 0.175699E+09 | 0.388268E+09 | 48664608.15 |
August | 0.256191E+09 | 0.124337E+09 | 0.131854E+09 | 0.276778E+09 | 71289999.19 |
September | 0.133930E+09 | 53038176.40 | 80892308.04 | 0.125171E+09 | 93186889.53 |
October | 56802044.74 | 13782522.86 | 43019521.89 | 29142259.32 | 0.162223E+09 |
November | 13774258.88 | 1138326.65 | 12635932.23 | 0.00 | 0.353464E+09 |
December | 2099864.67 | 39429.99 | 2060434.68 | 0.00 | 0.400474E+09 |
Annual Sum or Average | 0.195438E+10 | 0.944871E+09 | 0.100951E+10 | 0.203172E+10 | 0.217355E+10 |
Minimum of Months | 2099864.67 | 39429.99 | 2060434.68 | 0.00 | 32810776.99 |
Maximum of Months | 0.367113E+09 | 0.199048E+09 | 0.184004E+09 | 0.432474E+09 | 0.400474E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7490470.68 | 679356.78 | 6811113.89 | 0.00 | 0.369921E+09 |
February | 34272105.70 | 8386386.85 | 25885718.86 | 380303.29 | 0.279810E+09 |
March | 0.133251E+09 | 56683499.46 | 76567866.70 | 90150841.96 | 0.207753E+09 |
April | 0.259413E+09 | 0.139992E+09 | 0.119421E+09 | 0.276538E+09 | 0.103353E+09 |
May | 0.349706E+09 | 0.199048E+09 | 0.150658E+09 | 0.412817E+09 | 50599281.09 |
June | 0.367113E+09 | 0.183109E+09 | 0.184004E+09 | 0.432474E+09 | 32810776.99 |
July | 0.340337E+09 | 0.164638E+09 | 0.175699E+09 | 0.388268E+09 | 48664608.15 |
August | 0.256191E+09 | 0.124337E+09 | 0.131854E+09 | 0.276778E+09 | 71289999.19 |
September | 0.133930E+09 | 53038176.40 | 80892308.04 | 0.125171E+09 | 93186889.53 |
October | 56802044.74 | 13782522.86 | 43019521.89 | 29142259.32 | 0.162223E+09 |
November | 13774258.88 | 1138326.65 | 12635932.23 | 0.00 | 0.353464E+09 |
December | 2099864.67 | 39429.99 | 2060434.68 | 0.00 | 0.400474E+09 |
Annual Sum or Average | 0.195438E+10 | 0.944871E+09 | 0.100951E+10 | 0.203172E+10 | 0.217355E+10 |
Minimum of Months | 2099864.67 | 39429.99 | 2060434.68 | 0.00 | 32810776.99 |
Maximum of Months | 0.367113E+09 | 0.199048E+09 | 0.184004E+09 | 0.432474E+09 | 0.400474E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7490470.68 | 679356.78 | 6811113.89 | 0.00 | 0.369921E+09 |
February | 34272105.70 | 8386386.85 | 25885718.86 | 380303.29 | 0.279810E+09 |
March | 0.133251E+09 | 56683499.46 | 76567866.70 | 90150841.96 | 0.207753E+09 |
April | 0.259413E+09 | 0.139992E+09 | 0.119421E+09 | 0.276538E+09 | 0.103353E+09 |
May | 0.349706E+09 | 0.199048E+09 | 0.150658E+09 | 0.412817E+09 | 50599281.09 |
June | 0.367113E+09 | 0.183109E+09 | 0.184004E+09 | 0.432474E+09 | 32810776.99 |
July | 0.340337E+09 | 0.164638E+09 | 0.175699E+09 | 0.388268E+09 | 48664608.15 |
August | 0.256191E+09 | 0.124337E+09 | 0.131854E+09 | 0.276778E+09 | 71289999.19 |
September | 0.133930E+09 | 53038176.40 | 80892308.04 | 0.125171E+09 | 93186889.53 |
October | 56802044.74 | 13782522.86 | 43019521.89 | 29142259.32 | 0.162223E+09 |
November | 13774258.88 | 1138326.65 | 12635932.23 | 0.00 | 0.353464E+09 |
December | 2099864.67 | 39429.99 | 2060434.68 | 0.00 | 0.400474E+09 |
Annual Sum or Average | 0.195438E+10 | 0.944871E+09 | 0.100951E+10 | 0.203172E+10 | 0.217355E+10 |
Minimum of Months | 2099864.67 | 39429.99 | 2060434.68 | 0.00 | 32810776.99 |
Maximum of Months | 0.367113E+09 | 0.199048E+09 | 0.184004E+09 | 0.432474E+09 | 0.400474E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7490470.68 | 679356.78 | 6811113.89 | 0.00 | 0.369921E+09 |
February | 34272105.70 | 8386386.85 | 25885718.86 | 380303.29 | 0.279810E+09 |
March | 0.133251E+09 | 56683499.46 | 76567866.70 | 90150841.96 | 0.207753E+09 |
April | 0.259413E+09 | 0.139992E+09 | 0.119421E+09 | 0.276538E+09 | 0.103353E+09 |
May | 0.349706E+09 | 0.199048E+09 | 0.150658E+09 | 0.412817E+09 | 50599281.09 |
June | 0.367113E+09 | 0.183109E+09 | 0.184004E+09 | 0.432474E+09 | 32810776.99 |
July | 0.340337E+09 | 0.164638E+09 | 0.175699E+09 | 0.388268E+09 | 48664608.15 |
August | 0.256191E+09 | 0.124337E+09 | 0.131854E+09 | 0.276778E+09 | 71289999.19 |
September | 0.133930E+09 | 53038176.40 | 80892308.04 | 0.125171E+09 | 93186889.53 |
October | 56802044.74 | 13782522.86 | 43019521.89 | 29142259.32 | 0.162223E+09 |
November | 13774258.88 | 1138326.65 | 12635932.23 | 0.00 | 0.353464E+09 |
December | 2099864.67 | 39429.99 | 2060434.68 | 0.00 | 0.400474E+09 |
Annual Sum or Average | 0.195438E+10 | 0.944871E+09 | 0.100951E+10 | 0.203172E+10 | 0.217355E+10 |
Minimum of Months | 2099864.67 | 39429.99 | 2060434.68 | 0.00 | 32810776.99 |
Maximum of Months | 0.367113E+09 | 0.199048E+09 | 0.184004E+09 | 0.432474E+09 | 0.400474E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7490470.68 | 679356.78 | 6811113.89 | 0.00 | 0.369921E+09 |
February | 34272105.70 | 8386386.85 | 25885718.86 | 380303.29 | 0.279810E+09 |
March | 0.133251E+09 | 56683499.46 | 76567866.70 | 90150841.96 | 0.207753E+09 |
April | 0.259413E+09 | 0.139992E+09 | 0.119421E+09 | 0.276538E+09 | 0.103353E+09 |
May | 0.349706E+09 | 0.199048E+09 | 0.150658E+09 | 0.412817E+09 | 50599281.09 |
June | 0.367113E+09 | 0.183109E+09 | 0.184004E+09 | 0.432474E+09 | 32810776.99 |
July | 0.340337E+09 | 0.164638E+09 | 0.175699E+09 | 0.388268E+09 | 48664608.15 |
August | 0.256191E+09 | 0.124337E+09 | 0.131854E+09 | 0.276778E+09 | 71289999.19 |
September | 0.133930E+09 | 53038176.40 | 80892308.04 | 0.125171E+09 | 93186889.53 |
October | 56802044.74 | 13782522.86 | 43019521.89 | 29142259.32 | 0.162223E+09 |
November | 13774258.88 | 1138326.65 | 12635932.23 | 0.00 | 0.353464E+09 |
December | 2099864.67 | 39429.99 | 2060434.68 | 0.00 | 0.400474E+09 |
Annual Sum or Average | 0.195438E+10 | 0.944871E+09 | 0.100951E+10 | 0.203172E+10 | 0.217355E+10 |
Minimum of Months | 2099864.67 | 39429.99 | 2060434.68 | 0.00 | 32810776.99 |
Maximum of Months | 0.367113E+09 | 0.199048E+09 | 0.184004E+09 | 0.432474E+09 | 0.400474E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 834.56 | 15.90 | 1.98 | 13.92 | 0.00 | 0.00 |
February | 2.72 | 712.06 | 87.37 | 23.43 | 63.94 | 0.00 | 0.00 |
March | 88.72 | 492.94 | 255.50 | 86.57 | 168.93 | 0.00 | 0.00 |
April | 456.10 | 249.63 | 571.80 | 246.38 | 325.42 | 0.00 | 0.00 |
May | 548.24 | 98.39 | 612.46 | 233.04 | 379.42 | 0.00 | 0.00 |
June | 653.24 | 57.83 | 701.66 | 257.70 | 443.96 | 0.00 | 0.00 |
July | 532.14 | 81.99 | 588.12 | 186.06 | 402.06 | 0.00 | 0.00 |
August | 382.69 | 128.47 | 453.97 | 152.44 | 301.53 | 0.00 | 0.00 |
September | 177.82 | 206.99 | 268.62 | 87.03 | 181.59 | 0.00 | 0.00 |
October | 23.52 | 429.97 | 110.94 | 24.55 | 86.39 | 0.00 | 0.00 |
November | 0.64 | 805.89 | 41.88 | 11.95 | 29.93 | 0.00 | 0.00 |
December | 0.00 | 886.67 | 4.37 | 0.32 | 4.05 | 0.00 | 0.00 |
Annual Sum or Average | 239.85 | 413.95 | 310.26 | 109.54 | 200.72 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 57.83 | 4.37 | 0.32 | 4.05 | 0.00 | 0.00 |
Maximum of Months | 653.24 | 886.67 | 701.66 | 257.70 | 443.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1381.13 | 27.97 | 2.54 | 25.43 | 0.00 | 0.00 |
February | 1.57 | 1156.62 | 141.67 | 34.67 | 107.00 | 0.00 | 0.00 |
March | 336.58 | 775.66 | 497.50 | 211.63 | 285.87 | 0.00 | 0.00 |
April | 1066.89 | 398.74 | 1000.82 | 540.09 | 460.73 | 0.00 | 0.00 |
May | 1541.28 | 188.92 | 1305.65 | 743.16 | 562.49 | 0.00 | 0.00 |
June | 1668.49 | 126.58 | 1416.33 | 706.44 | 709.89 | 0.00 | 0.00 |
July | 1449.63 | 181.69 | 1270.67 | 614.69 | 655.99 | 0.00 | 0.00 |
August | 1033.37 | 266.17 | 956.51 | 464.22 | 492.29 | 0.00 | 0.00 |
September | 482.91 | 359.52 | 516.71 | 204.62 | 312.08 | 0.00 | 0.00 |
October | 108.80 | 605.67 | 212.07 | 51.46 | 160.62 | 0.00 | 0.00 |
November | 0.00 | 1363.67 | 53.14 | 4.39 | 48.75 | 0.00 | 0.00 |
December | 0.00 | 1495.20 | 7.84 | 0.15 | 7.69 | 0.00 | 0.00 |
Annual Sum or Average | 644.25 | 689.23 | 619.73 | 299.62 | 320.11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 126.58 | 7.84 | 0.15 | 7.69 | 0.00 | 0.00 |
Maximum of Months | 1668.49 | 1495.20 | 1416.33 | 743.16 | 709.89 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.223529E+10 | 42577500.72 | 5290114.29 | 37287386.43 | 0.00 | 0.00 |
February | 6579952.21 | 0.172262E+10 | 0.211370E+09 | 56689222.02 | 0.154681E+09 | 0.00 | 0.00 |
March | 0.237618E+09 | 0.132029E+10 | 0.684341E+09 | 0.231866E+09 | 0.452475E+09 | 0.00 | 0.00 |
April | 0.118222E+10 | 0.647030E+09 | 0.148211E+10 | 0.638624E+09 | 0.843485E+09 | 0.00 | 0.00 |
May | 0.146839E+10 | 0.263533E+09 | 0.164042E+10 | 0.624177E+09 | 0.101624E+10 | 0.00 | 0.00 |
June | 0.169319E+10 | 0.149894E+09 | 0.181871E+10 | 0.667956E+09 | 0.115075E+10 | 0.00 | 0.00 |
July | 0.142528E+10 | 0.219594E+09 | 0.157523E+10 | 0.498343E+09 | 0.107689E+10 | 0.00 | 0.00 |
August | 0.102501E+10 | 0.344085E+09 | 0.121591E+10 | 0.408299E+09 | 0.807610E+09 | 0.00 | 0.00 |
September | 0.460902E+09 | 0.536515E+09 | 0.696272E+09 | 0.225585E+09 | 0.470687E+09 | 0.00 | 0.00 |
October | 62993949.27 | 0.115163E+10 | 0.297129E+09 | 65754872.47 | 0.231374E+09 | 0.00 | 0.00 |
November | 1649900.30 | 0.208887E+10 | 0.108544E+09 | 30977293.81 | 77566380.06 | 0.00 | 0.00 |
December | 0.00 | 0.237486E+10 | 11716295.07 | 863202.32 | 10853092.75 | 0.00 | 0.00 |
Annual Sum or Average | 0.756383E+10 | 0.130542E+11 | 0.978432E+10 | 0.345443E+10 | 0.632990E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.149894E+09 | 11716295.07 | 863202.32 | 10853092.75 | 0.00 | 0.00 |
Maximum of Months | 0.169319E+10 | 0.237486E+10 | 0.181871E+10 | 0.667956E+09 | 0.115075E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.369921E+10 | 74904706.76 | 6793567.83 | 68111138.93 | 0.00 | 0.00 |
February | 3803032.88 | 0.279810E+10 | 0.342721E+09 | 83863868.46 | 0.258857E+09 | 0.00 | 0.00 |
March | 0.901508E+09 | 0.207752E+10 | 0.133251E+10 | 0.566835E+09 | 0.765679E+09 | 0.00 | 0.00 |
April | 0.276537E+10 | 0.103353E+10 | 0.259413E+10 | 0.139992E+10 | 0.119421E+10 | 0.00 | 0.00 |
May | 0.412817E+10 | 0.505993E+09 | 0.349706E+10 | 0.199048E+10 | 0.150658E+10 | 0.00 | 0.00 |
June | 0.432474E+10 | 0.328107E+09 | 0.367113E+10 | 0.183109E+10 | 0.184004E+10 | 0.00 | 0.00 |
July | 0.388268E+10 | 0.486646E+09 | 0.340337E+10 | 0.164638E+10 | 0.175699E+10 | 0.00 | 0.00 |
August | 0.276778E+10 | 0.712900E+09 | 0.256191E+10 | 0.124337E+10 | 0.131854E+10 | 0.00 | 0.00 |
September | 0.125171E+10 | 0.931869E+09 | 0.133930E+10 | 0.530382E+09 | 0.808923E+09 | 0.00 | 0.00 |
October | 0.291423E+09 | 0.162223E+10 | 0.568020E+09 | 0.137825E+09 | 0.430195E+09 | 0.00 | 0.00 |
November | 0.00 | 0.353464E+10 | 0.137743E+09 | 11383266.49 | 0.126359E+09 | 0.00 | 0.00 |
December | 0.00 | 0.400474E+10 | 20998646.69 | 394299.86 | 20604346.83 | 0.00 | 0.00 |
Annual Sum or Average | 0.203172E+11 | 0.217355E+11 | 0.195438E+11 | 0.944871E+10 | 0.100951E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.328107E+09 | 20998646.69 | 394299.86 | 20604346.83 | 0.00 | 0.00 |
Maximum of Months | 0.432474E+10 | 0.400474E+10 | 0.367113E+10 | 0.199048E+10 | 0.184004E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.5 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.6 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.24 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.87 | 6.41 | 3.45 | 5.65 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.84 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.69 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.46 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.84 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.6 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.5 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.58 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.01 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.76 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.27 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.32 | 11.70 | 4.67 | 18.87 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.74 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.88 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 7.99 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.5 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.0 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.5 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.32 | 11.70 | 6.20 | 18.87 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.1 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.2 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.0 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.8 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.6 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.23 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.64 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.01 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.94 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.32 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.33 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.28 | 141.00 | 225.33 |
August | 16.13 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.81 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 7.99 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.5 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.0 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.5 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.33 | 29.07 | 14.40 | 8.80 | 19.28 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.6 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.77 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.74 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.40 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.29 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.0 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.4 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.0 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.112507E+10 | -.105363E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -71435082.5 | 58.99 | 0.00 | 0.00 |
February | 0.103239E+10 | -967998483.1 | 0.00 | 0.00 | 672.00 | 0.00 | -64390547.5 | 58.99 | 0.00 | 0.00 |
March | 0.120245E+10 | -.113151E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -70930985.7 | 58.99 | 0.00 | 0.00 |
April | 0.111869E+10 | -.105105E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -67642550.8 | 58.99 | 0.00 | 0.00 |
May | 0.115209E+10 | -.108504E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -67058060.1 | 58.99 | 0.00 | 0.00 |
June | 0.110052E+10 | -.104140E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -59125188.2 | 59.00 | 0.00 | 0.00 |
July | 0.102763E+10 | -968507363.5 | 0.00 | 0.00 | 744.00 | 0.00 | -59119794.5 | 59.00 | 0.00 | 0.00 |
August | 0.107565E+10 | -.101499E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -60660485.8 | 58.97 | 0.00 | 0.00 |
September | 0.100540E+10 | -939949960.6 | 0.00 | 0.00 | 720.00 | 0.00 | -65447601.1 | 58.99 | 0.00 | 0.00 |
October | 0.103135E+10 | -960920414.6 | 0.00 | 0.00 | 744.00 | 0.00 | -70431034.1 | 59.00 | 0.00 | 0.00 |
November | 0.102503E+10 | -955932120.7 | 0.00 | 0.00 | 720.00 | 0.00 | -69096803.8 | 59.00 | 0.00 | 0.00 |
December | 0.110769E+10 | -.103624E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -71447583.7 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130040E+11 | -.122072E+11 | 8760.00 | -796785717.6 | 58.99 | |||||
Minimum of Months | 0.100540E+10 | -.113151E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -71447583.7 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.120245E+10 | -939949960.6 | 0.00 | 0.00 | 744.00 | 0.00 | -59119794.5 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 108.67 | 1.00 | 0.96 | 21-JAN-12:09 | 30.27 | 2.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 205.83 | 0.98 | 0.92 | 11-FEB-12:09 | 70.35 | 6.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 329.50 | 0.95 | 0.88 | 05-MAR-10:50 | 131.69 | 9.73 | 0.00 | 71.50 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 421.83 | 0.94 | 0.88 | 01-APR-09:50 | 162.83 | 10.60 | 0.00 | 115.17 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 545.00 | 0.93 | 0.88 | 01-MAY-07:19 | 184.02 | 10.87 | 0.00 | 213.83 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 583.50 | 0.92 | 0.88 | 01-JUN-07:49 | 563.12 | 11.15 | 0.00 | 301.83 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 562.83 | 0.93 | 0.88 | 01-JUL-08:30 | 212.15 | 11.33 | 0.00 | 262.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 467.17 | 0.93 | 0.88 | 01-AUG-06:00 | 182.92 | 11.02 | 0.00 | 179.83 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 356.33 | 0.95 | 0.88 | 01-SEP-08:09 | 136.84 | 9.92 | 0.00 | 58.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 265.50 | 0.97 | 0.88 | 01-OCT-09:00 | 97.36 | 8.07 | 0.00 | 4.67 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 135.83 | 0.99 | 0.92 | 01-NOV-13:20 | 41.66 | 3.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71.17 | 1.00 | 1.00 | 04-DEC-10:50 | 9.56 | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.94 | 208.36 | 9.71 | 0.00 | 1206.83 | ||||||
Minimum of Months | 71.17 | 0.92 | 0.88 | 9.56 | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 1.00 | 1.00 | 563.12 | 11.33 | 0.00 | 301.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.98 | 0.95 | 31-JAN-11:30 | 52.37 | 13.37 | 0.00 | 0.00 | 25.62 | 13.04 | 0.00 | 0.00 |
February | 205.83 | 0.95 | 0.89 | 28-FEB-15:20 | 123.53 | 18.47 | 25.50 | 0.00 | 64.02 | 18.20 | 12.17 | 0.00 |
March | 329.50 | 0.92 | 0.86 | 12-MAR-17:10 | 356.66 | 23.78 | 176.83 | 43.50 | 149.74 | 22.67 | 167.33 | 9.50 |
April | 421.83 | 0.90 | 0.86 | 01-APR-15:20 | 619.97 | 24.13 | 249.33 | 154.17 | 482.26 | 24.27 | 285.17 | 98.83 |
May | 545.00 | 0.90 | 0.86 | 01-MAY-16:00 | 301.92 | 20.92 | 265.67 | 135.50 | 303.54 | 21.97 | 341.00 | 96.67 |
June | 583.50 | 0.90 | 0.86 | 01-JUN-14:30 | 324.49 | 20.75 | 291.50 | 200.50 | 232.56 | 21.67 | 357.17 | 89.50 |
July | 562.83 | 0.90 | 0.86 | 02-JUL-14:50 | 313.63 | 20.74 | 262.50 | 167.17 | 287.76 | 21.68 | 323.17 | 88.50 |
August | 467.17 | 0.90 | 0.86 | 01-AUG-14:50 | 430.70 | 22.59 | 239.33 | 115.83 | 355.93 | 23.16 | 268.33 | 68.33 |
September | 356.33 | 0.92 | 0.86 | 01-SEP-15:30 | 437.27 | 24.45 | 188.50 | 59.83 | 160.09 | 22.83 | 194.83 | 14.50 |
October | 265.50 | 0.95 | 0.88 | 01-OCT-15:30 | 171.76 | 21.17 | 58.50 | 10.67 | 72.00 | 19.00 | 26.67 | 0.00 |
November | 135.83 | 0.97 | 0.93 | 06-NOV-13:30 | 72.98 | 15.53 | 0.67 | 0.00 | 37.64 | 15.17 | 0.33 | 0.00 |
December | 71.17 | 0.99 | 0.98 | 05-DEC-11:30 | 18.48 | 7.13 | 0.00 | 0.00 | 8.72 | 6.78 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.92 | 334.17 | 21.21 | 1758.33 | 887.17 | 241.79 | 21.28 | 1976.17 | 465.83 | ||
Minimum of Months | 71.17 | 0.90 | 0.86 | 18.48 | 7.13 | 0.00 | 0.00 | 8.72 | 6.78 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.99 | 0.98 | 619.97 | 24.45 | 291.50 | 200.50 | 482.26 | 24.27 | 357.17 | 98.83 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.166080E+11 | 25788.79 | 01-JAN-18:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137781E+11 | 25788.79 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133747E+11 | 25788.79 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.640482E+10 | 25788.79 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146057E+10 | 25788.79 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 66981043.69 | 16060.66 | 02-JUN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8483186.75 | 13841.62 | 05-JUL-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166220E+09 | 18028.36 | 31-AUG-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.289091E+10 | 25788.79 | 05-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.833785E+10 | 25788.79 | 02-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144312E+11 | 25788.79 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165261E+11 | 25788.79 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.940539E+11 | |||||||
Minimum of Months | 8483186.75 | 13841.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.166080E+11 | 25788.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.574573E+11 | 62904.36 | 01-JAN-00:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.464975E+11 | 62904.36 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.417567E+11 | 62904.36 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183256E+11 | 62904.36 | 01-APR-00:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.971408E+09 | 29970.64 | 28-MAY-02:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.282098E+10 | 53236.82 | 28-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.256715E+11 | 62904.36 | 13-OCT-01:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.458449E+11 | 62904.36 | 01-NOV-00:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.571639E+11 | 62904.36 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296510E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.574573E+11 | 62904.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128327E+12 | 83385.19 | 01-JAN-18:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112941E+12 | 83385.19 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112630E+12 | 83385.19 | 01-MAR-03:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.527567E+11 | 83385.19 | 01-APR-18:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2324312.81 | 1391.33 | 03-MAY-03:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.404418E+09 | 17692.23 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.633322E+11 | 83385.19 | 22-OCT-20:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.869389E+11 | 83385.19 | 09-NOV-21:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128834E+12 | 83385.19 | 01-DEC-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.686166E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.128834E+12 | 83385.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 8363841.29 | 8363841.29 | 1096.05 | 13-MAY-15:50 | 1096.05 | 0.00 |
June | 0.00 | 0.00 | 0.173630E+10 | 0.169127E+10 | 13050.53 | 24-JUN-07:03 | 13050.53 | 0.00 |
July | 0.00 | 0.00 | 0.315316E+10 | 0.299452E+10 | 13703.89 | 15-JUL-07:02 | 12365.29 | 0.00 |
August | 0.00 | 0.00 | 0.180324E+10 | 0.172673E+10 | 13495.77 | 05-AUG-07:02 | 12904.40 | 0.00 |
September | 0.00 | 0.00 | 2756838.74 | 2756838.74 | 763.16 | 02-SEP-16:00 | 763.16 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.670381E+10 | 0.642365E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.315316E+10 | 0.299452E+10 | 13703.89 | 13050.53 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 31164557.78 | 30389832.73 | 3674.83 | 30-JUN-15:00 | 3674.83 | 0.00 |
July | 0.00 | 0.00 | 0.455134E+09 | 0.452385E+09 | 21906.78 | 23-JUL-14:12 | 21740.05 | 0.00 |
August | 0.00 | 0.00 | 3446766.10 | 3338448.76 | 891.59 | 04-AUG-14:40 | 865.18 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.489745E+09 | 0.486113E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.455134E+09 | 0.452385E+09 | 21906.78 | 21740.05 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.507481E+09 | 0.08 | 189.47 | 01-JAN-00:02 | 0.08 |
February | 0.458256E+09 | 0.08 | 189.47 | 01-FEB-00:02 | 0.08 |
March | 0.485029E+09 | 0.07 | 189.47 | 01-MAR-00:02 | 0.08 |
April | 0.299342E+09 | 0.05 | 189.47 | 01-APR-00:10 | 0.08 |
May | 1705245.96 | 0.00 | 189.47 | 02-MAY-01:10 | 0.08 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 9435694.29 | 0.00 | 189.47 | 29-SEP-21:10 | 0.08 |
October | 0.395750E+09 | 0.06 | 189.47 | 01-OCT-00:05 | 0.08 |
November | 0.491111E+09 | 0.08 | 189.47 | 01-NOV-00:10 | 0.08 |
December | 0.507481E+09 | 0.08 | 189.47 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.315559E+10 | 0.04 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.507481E+09 | 0.08 | 189.47 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.989708E+09 | 0.64 | 888.76 | 01-JAN-18:42 | 0.93 |
February | 0.906522E+09 | 0.65 | 888.76 | 01-FEB-06:01 | 0.93 |
March | 0.101798E+10 | 0.56 | 888.76 | 01-MAR-06:01 | 0.93 |
April | 0.902696E+09 | 0.42 | 888.76 | 08-APR-14:50 | 0.93 |
May | 0.916249E+09 | 0.36 | 888.76 | 03-MAY-09:20 | 0.92 |
June | 0.915066E+09 | 0.36 | 888.76 | 08-JUN-16:20 | 0.92 |
July | 0.879872E+09 | 0.34 | 888.76 | 01-JUL-06:03 | 0.91 |
August | 0.950261E+09 | 0.37 | 888.76 | 08-AUG-07:40 | 0.92 |
September | 0.882139E+09 | 0.36 | 888.76 | 05-SEP-10:20 | 0.92 |
October | 0.900830E+09 | 0.40 | 888.76 | 06-OCT-15:10 | 0.92 |
November | 0.911801E+09 | 0.56 | 888.76 | 01-NOV-05:01 | 0.93 |
December | 0.975472E+09 | 0.63 | 888.76 | 01-DEC-06:01 | 0.93 |
Annual Sum or Average | 0.111486E+11 | 0.47 | |||
Minimum of Months | 0.879872E+09 | 0.34 | 888.76 | 0.91 | |
Maximum of Months | 0.101798E+10 | 0.65 | 888.76 | 0.93 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.191751E+10 | 0.82 | 1286.69 | 03-JAN-08:00 | 0.93 |
February | 0.173541E+10 | 0.81 | 1286.69 | 02-FEB-15:10 | 0.93 |
March | 0.189647E+10 | 0.80 | 1286.69 | 01-MAR-11:40 | 0.93 |
April | 0.155497E+10 | 0.68 | 1286.69 | 01-APR-13:30 | 0.93 |
May | 0.134396E+10 | 0.40 | 1286.69 | 01-MAY-06:20 | 0.92 |
June | 0.132478E+10 | 0.37 | 1286.69 | 21-JUN-15:30 | 0.92 |
July | 0.127463E+10 | 0.34 | 1286.69 | 11-JUL-14:10 | 0.92 |
August | 0.137573E+10 | 0.37 | 1286.69 | 02-AUG-13:00 | 0.92 |
September | 0.131259E+10 | 0.43 | 1286.69 | 23-SEP-09:50 | 0.92 |
October | 0.160656E+10 | 0.74 | 1286.69 | 02-OCT-10:40 | 0.92 |
November | 0.173015E+10 | 0.81 | 1286.69 | 01-NOV-14:40 | 0.93 |
December | 0.188517E+10 | 0.82 | 1286.69 | 07-DEC-07:50 | 0.93 |
Annual Sum or Average | 0.189579E+11 | 0.62 | |||
Minimum of Months | 0.127463E+10 | 0.34 | 1286.69 | 0.92 | |
Maximum of Months | 0.191751E+10 | 0.82 | 1286.69 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.49 | 0.25 |
February | 3.76 | 0.21 |
March | 4.30 | 0.07 |
April | 1.99 | 0.20 |
May | 1.81 | 3.56 |
June | 2.60 | 3.31 |
July | 3.44 | 2.52 |
August | 3.94 | 2.55 |
September | 1.60 | 2.46 |
October | 4.36 | 0.05 |
November | 4.01 | 0.16 |
December | 3.52 | 0.56 |
Annual Sum or Average | 39.82 | 1.08 |
Minimum of Months | 1.60 | 0.05 |
Maximum of Months | 4.49 | 3.56 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.22 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.32 | 0.00 |
September | 0.08 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.62 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.32 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.989708E+09 | 0.226519E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.906522E+09 | 0.190154E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.101798E+10 | 0.185725E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.902696E+09 | 0.918186E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.918087E+09 | 0.215234E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.127887E+10 | 98971944.71 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.152566E+10 | 12621835.87 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.132412E+10 | 0.244614E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.882748E+09 | 0.423047E+10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.900830E+09 | 0.117772E+11 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.911801E+09 | 0.196846E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.975472E+09 | 0.224625E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.125345E+11 | 0.130085E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.882748E+09 | 12621835.87 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.152566E+10 | 0.226519E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.191751E+10 | 0.794715E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.173541E+10 | 0.647708E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.189647E+10 | 0.589600E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.155497E+10 | 0.261811E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.134396E+10 | 0.144348E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.133246E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.138275E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.137656E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.131259E+10 | 0.420398E+10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.160656E+10 | 0.368453E+11 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.173015E+10 | 0.644475E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.188517E+10 | 0.793002E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.190746E+11 | 0.415624E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.131259E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.191751E+10 | 0.794715E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.989708E+09 | 0.00 | 0.166080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.906522E+09 | 0.00 | 0.137781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101798E+10 | 0.00 | 0.133747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.902696E+09 | 0.00 | 0.640482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.916249E+09 | 8363841.29 | 0.146057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.915066E+09 | 0.173630E+10 | 66981043.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.879872E+09 | 0.315316E+10 | 8483186.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.950261E+09 | 0.180324E+10 | 0.166220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.882139E+09 | 2756838.74 | 0.289091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.900830E+09 | 0.00 | 0.833785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.911801E+09 | 0.00 | 0.144312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.975472E+09 | 0.00 | 0.165261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111486E+11 | 0.670381E+10 | 0.940539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.879872E+09 | 0.00 | 8483186.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101798E+10 | 0.315316E+10 | 0.166080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.191751E+10 | 0.00 | 0.574573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173541E+10 | 0.00 | 0.464975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189647E+10 | 0.00 | 0.417567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155497E+10 | 0.00 | 0.183256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134396E+10 | 0.00 | 0.971408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132478E+10 | 31164557.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.127463E+10 | 0.455134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137573E+10 | 3446766.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131259E+10 | 0.00 | 0.282098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160656E+10 | 0.00 | 0.256715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173015E+10 | 0.00 | 0.458449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188517E+10 | 0.00 | 0.571639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189579E+11 | 0.489745E+09 | 0.296510E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.191751E+10 | 0.455134E+09 | 0.574573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.989708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.906522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.902696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.916249E+09 | 0.00 | 0.00 | 0.00 | 1837896.40 | 0.00 | 0.215234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.915066E+09 | 0.00 | 0.00 | 0.00 | 0.363802E+09 | 0.00 | 98971944.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.879872E+09 | 0.00 | 0.00 | 0.00 | 0.645793E+09 | 0.00 | 12621835.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.950261E+09 | 0.00 | 0.00 | 0.00 | 0.373862E+09 | 0.00 | 0.244614E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.882139E+09 | 0.00 | 0.00 | 0.00 | 609083.67 | 0.00 | 0.423047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.900830E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.911801E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.975472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111486E+11 | 0.00 | 0.00 | 0.00 | 0.138590E+10 | 0.00 | 0.130085E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.879872E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12621835.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101798E+10 | 0.00 | 0.00 | 0.00 | 0.645793E+09 | 0.00 | 0.226519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.191751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132478E+10 | 0.00 | 0.00 | 0.00 | 7684606.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.127463E+10 | 0.00 | 0.00 | 0.00 | 0.108113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137573E+10 | 0.00 | 0.00 | 0.00 | 829497.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.793002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189579E+11 | 0.00 | 0.00 | 0.00 | 0.116627E+09 | 0.00 | 0.415624E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.127463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.191751E+10 | 0.00 | 0.00 | 0.00 | 0.108113E+09 | 0.00 | 0.794715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2250543.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525564E+10 | 0.00 | 0.00 | 0.15 |
February | 3997655.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431104E+10 | 0.00 | 0.00 | 0.15 |
March | 5915824.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423411E+10 | 0.00 | 0.00 | 0.16 |
April | 53936898.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229875E+10 | 0.00 | 0.00 | 0.14 |
May | 0.537914E+09 | 0.00 | 0.00 | 5916.47 | 0.00 | 0.675530E+09 | 5354056.27 | 0.00 | 0.14 |
June | 0.310597E+09 | 5370135.74 | 0.00 | 2350080.75 | 0.00 | 27255446.93 | 0.551496E+09 | 0.00 | 0.15 |
July | 0.180040E+09 | 19451245.17 | 0.00 | 4032158.58 | 0.00 | 5370491.68 | 0.460272E+09 | 0.00 | 0.14 |
August | 0.486786E+09 | 815260.78 | 0.00 | 2820193.61 | 0.00 | 74570819.26 | 0.594274E+09 | 0.00 | 0.15 |
September | 0.404796E+09 | 0.00 | 0.00 | 4580.46 | 0.00 | 0.138886E+10 | 6032163.37 | 0.00 | 0.14 |
October | 14034885.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300994E+10 | 0.00 | 0.00 | 0.14 |
November | 5483994.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483112E+10 | 0.00 | 0.00 | 0.14 |
December | 5373934.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545612E+10 | 0.00 | 0.00 | 0.15 |
Annual Sum or Average | 0.201113E+10 | 25636641.69 | 0.00 | 9212929.88 | 0.00 | 0.315683E+11 | 0.161743E+10 | 0.00 | 0.15 |
Minimum of Months | 2250543.86 | 0.00 | 0.00 | 0.00 | 0.00 | 5370491.68 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.537914E+09 | 19451245.17 | 0.00 | 4032158.58 | 0.00 | 0.545612E+10 | 0.594274E+09 | 0.00 | 0.16 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152721E+11 | 0.00 | 0.00 | 0.17 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119188E+11 | 0.00 | 0.00 | 0.18 |
March | 0.613490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109936E+11 | 0.00 | 0.00 | 0.19 |
April | 0.254591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312707E+10 | 0.00 | 0.00 | 0.18 |
May | 0.255785E+10 | 0.00 | 0.00 | 0.00 | 33984.38 | 42394856.75 | 0.00 | 0.00 | 0.18 |
June | 0.276382E+10 | 311051.59 | 0.00 | 30761.15 | 296189.85 | 0.00 | 59233118.86 | 0.00 | 0.19 |
July | 0.234845E+10 | 24336921.69 | 0.00 | 786806.91 | 7836698.21 | 0.00 | 0.480056E+09 | 0.00 | 0.20 |
August | 0.361045E+10 | 0.00 | 0.00 | 134430.49 | 0.00 | 0.00 | 0.151168E+09 | 0.00 | 0.20 |
September | 0.387521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466541E+09 | 0.00 | 0.00 | 0.18 |
October | 0.126392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695235E+10 | 0.00 | 0.00 | 0.17 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144203E+11 | 0.00 | 0.00 | 0.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162541E+11 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.195791E+11 | 24647973.28 | 0.00 | 951998.54 | 8166872.45 | 0.794472E+11 | 0.690458E+09 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.387521E+10 | 24336921.69 | 0.00 | 786806.91 | 7836698.21 | 0.162541E+11 | 0.480056E+09 | 0.00 | 0.20 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |