Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2020-06-03 19:11:57
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1878.20 | 388.45 | 388.45 |
Net Site Energy | 1878.20 | 388.45 | 388.45 |
Total Source Energy | 3114.17 | 644.07 | 644.07 |
Net Source Energy | 3114.17 | 644.07 | 644.07 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1360.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 240.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 67.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 27.32 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 517.62 | 1360.58 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1360.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 5.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 240.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 67.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 139.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 38.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 27.32 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 63.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 14.74 | 281.39 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 107.05 | 281.39 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 63.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 14.74 | 281.39 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 107.05 | 281.39 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 517.619 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 517.619 | 100.00 |
Total On-Site and Utility Electric Sources | 517.619 | 100.00 |
Total Electricity End Uses | 517.619 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 83.00 |
Time Setpoint Not Met During Occupied Cooling | 0.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2255.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Meter |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| ELECTRIC TANK |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATERHEATINGCOIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATERFAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 7.6531 | 47.38 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 6.6844 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.3906 | 2.5587 | |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.5487 | 967.03 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.5487 | 967.03 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-JUN-14:00 | 04-JAN-17:10 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 279620.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9486.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17096.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2451.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1811.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 40958.52 | 279620.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 279620.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 9486.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 17096.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2451.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1811.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1474.87 | 0.00 | 0.00 | 0.00 |
Cooling | 18.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 760.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 212.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 441.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 120.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 86.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1639.30 | 1474.87 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 305.03 | 0.00 | 0.00 | 0.00 |
Cooling | 3.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 157.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 43.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 24.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 339.04 | 305.03 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 305.03 | 0.00 | 0.00 | 0.00 |
Cooling | 3.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 157.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 43.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 91.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 24.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 339.04 | 305.03 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.870427 |
ZONE2 FINE STORAGE DIRECT AIR | 1.34 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3UNITHEATER | 3.43 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATERFAN | 3.43 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATERHEATINGCOIL | 136351.45 |
PSZ-OFFICE HEATING COIL | 25500.21 |
PSZ-FINE STORAGE HEATING COIL | 61844.54 |
User-Specified Heating Design Capacity [W] | |
ZONE3HIRADIANT | 136351.44 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.870427 | 0.870427 | 0.870427 | 0.870427 | 0.870427 | 0.870427 | 1.00 | 1.000000 | 0.870427 |
PSZ-FINE STORAGE | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.00 | 1.00 | 1.34 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE OA CONTROLLER | 0.870427 | 0.102285 |
PSZ-FINE STORAGE OA CONTROLLER | 1.34 | 0.424713 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.870427 | 0.870427 | 0.870427 | 0.870427 | 15208.85 | 25500.21 | 40.00 | 1.00 |
PSZ-FINE_UNITARY_PACKAGE_DX | 1.34 | 1.34 | 1.34 | 1.34 | 31901.14 | 61844.54 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.870430 | 0.435215 | 0.580287 | 14800.69 | 15208.85 | 7604.43 | 7604.43 | 0.779313 | 0.779310 | 0.779310 | 0.779310 |
PSZ-FINE STORAGE COOLING COIL | 1.34 | 0.671755 | 0.895673 | 30586.59 | 31901.14 | 15950.57 | 15950.57 | 0.687311 | 0.687310 | 0.687310 | 0.687310 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.870427 | 963.70 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.34 | 1487.47 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE FRONT DOOR | |
OFFICE LEFT WALL | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | OFFICE LEFT WALL DOOR | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 5.0 | 47.376 | 2.111E-002 | 7.653 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 15.727 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 0.0 | N/A | 0.000 | 6.684 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.684 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 0.0 | N/A | 0.000 | 3.391 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 5.949 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 5.0 | 2.111E-002 | 47.376 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | BLDG_LIGHT_OFFICE_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1812.873 | 7.653 | 362.575 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1812.873 |
2 | FINE STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 9314.091 | 6.684 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 9314.091 |
3 | BULK STORAGE AREA LIGHTS | BLDG_LIGHT_STORAGE_SCH | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 10866.440 | 3.391 | N/A | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10866.440 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 1912.500 | 8.074 | 382.500 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 8200.120 | 2.559 | N/A | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1685 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.1685 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL | 19 | 3 | 4 | 0.167 | 0.3070 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL | 21 | 3 | 4 | 0.167 | 0.3070 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 32 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 33 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 35 | 1 | 1 | 0.167 | 1.195 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 36 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 37 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 38 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 39 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1041 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.4317E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.4042E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 43 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL | 44 | 3 | 4 | 0.167 | 0.3070 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 45 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.935 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.935 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.158 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.158 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8365 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 9.529 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 23.09 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 24.66 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.158 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.11213371E-07 | 0.26651818E-13 | 0.48084804E-13 | 0.0000000 |
2 | 1 | -5.2160876 | 0.60803813E-04 | -0.95086230E-04 | 0.21497930E-08 |
3 | 0 | 5.3845682 | 0.16841986 | 0.16857575 | |
4 | 2 | 0.11213371E-07 | 0.26651818E-13 | 0.48084804E-13 | 0.0000000 |
5 | 1 | -5.2160876 | 0.60803813E-04 | -0.95086230E-04 | 0.21497930E-08 |
6 | 0 | 5.3845682 | 0.16841986 | 0.16857575 | |
7 | 4 | 0.81735868E-12 | -0.57156297E-16 | 0.55090832E-14 | 0.11117815E-15 |
8 | 3 | -0.39662747E-03 | 0.21866377E-06 | -0.57650539E-04 | 0.15682056E-12 |
9 | 2 | 1.7675818 | 0.47210309E-02 | 1.1617839 | -0.76040502E-04 |
10 | 1 | -7.0920383 | 0.12134871 | -17.234041 | 0.33878901 |
11 | 0 | 5.5278851 | 0.76962015E-01 | 16.275347 | |
12 | 4 | 0.81735868E-12 | -0.57156297E-16 | 0.55090832E-14 | 0.11117815E-15 |
13 | 3 | -0.39662747E-03 | 0.21866377E-06 | -0.57650539E-04 | 0.15682056E-12 |
14 | 2 | 1.7675818 | 0.47210309E-02 | 1.1617839 | -0.76040502E-04 |
15 | 1 | -7.0920383 | 0.12134871 | -17.234041 | 0.33878901 |
16 | 0 | 5.5278851 | 0.76962015E-01 | 16.275347 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009596 | 2.1009596 | 2.1009596 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009596 | 2.1009596 | 2.1009596 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 1.1954460 | 1.1954460 | 1.1954460 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602635 | 1.7602635 | 1.7602635 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.40943546E-08 | -0.48941433E-14 | 0.10002011E-14 | -0.40158259E-16 |
55 | 6 | 0.31272124E-05 | 0.19933103E-08 | 0.31973031E-02 | -0.26821658E-04 |
56 | 5 | -0.21335304E-03 | 0.11766416E-05 | -0.22414699 | 0.19598788E-02 |
57 | 4 | 0.48316011E-02 | 0.53476752E-04 | 4.8365802 | -0.45332602E-01 |
58 | 3 | -0.42187430E-01 | 0.42463702E-03 | -38.061149 | 0.39909293 |
59 | 2 | 0.14945981 | 0.70555311E-03 | 116.56127 | -1.4189736 |
60 | 1 | -0.21550367 | 0.21454475E-03 | -143.95282 | 2.0497880 |
61 | 0 | 0.10501452 | 0.52166033E-05 | 60.838472 | |
62 | 7 | -0.99354594E-08 | 0.85994744E-15 | -0.36446392E-14 | 0.33402613E-16 |
63 | 6 | 0.19007305E-05 | 0.85218543E-09 | 0.32020323E-02 | -0.26861330E-04 |
64 | 5 | -0.10257637E-03 | 0.49552608E-06 | -0.22441548 | 0.19622488E-02 |
65 | 4 | 0.21308868E-02 | 0.22341873E-04 | 4.8410464 | -0.45375540E-01 |
66 | 3 | -0.17974913E-01 | 0.17625076E-03 | -38.086349 | 0.39937154 |
67 | 2 | 0.62772635E-01 | 0.29099605E-03 | 116.61028 | -1.4196292 |
68 | 1 | -0.89915137E-01 | 0.87799409E-04 | -143.98166 | 2.0502620 |
69 | 0 | 0.43667207E-01 | 0.21083643E-05 | 60.838472 | |
70 | 7 | -0.10614037E-07 | 0.12466653E-14 | -0.85452615E-14 | 0.12855439E-15 |
71 | 6 | 0.18765462E-05 | 0.80237200E-09 | 0.32022472E-02 | -0.26863133E-04 |
72 | 5 | -0.98338504E-04 | 0.46542478E-06 | -0.22442766 | 0.19623563E-02 |
73 | 4 | 0.20165412E-02 | 0.20956150E-04 | 4.8412485 | -0.45377483E-01 |
74 | 3 | -0.16916006E-01 | 0.16514078E-03 | -38.087488 | 0.39938413 |
75 | 2 | 0.58934009E-01 | 0.27235831E-03 | 116.61249 | -1.4196588 |
76 | 1 | -0.84323034E-01 | 0.82076304E-04 | -143.98296 | 2.0502833 |
77 | 0 | 0.40927925E-01 | 0.19639094E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | 0.55090832E-14 | -0.57156297E-16 | 0.81735868E-12 | 0.11117815E-15 |
85 | 3 | -0.57650539E-04 | 0.21866377E-06 | -0.39662747E-03 | 0.15682056E-12 |
86 | 2 | 1.1617839 | 0.47210309E-02 | 1.7675818 | -0.76040502E-04 |
87 | 1 | -17.234041 | 0.12134871 | -7.0920383 | 0.33878901 |
88 | 0 | 16.275347 | 0.76962015E-01 | 5.5278851 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.29_SHGC_0.45 | 28 | 1 | VerySmooth | 1.647 | 0.445 | 0.367 | 0.451 |
2 | SKYLIGHT_U_0.75_SHGC_0.6 | 29 | 1 | VerySmooth | 4.262 | 0.604 | 0.475 | 0.601 |
3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 30 | 1 | VerySmooth | 4.262 | 0.604 | 0.475 | 0.601 |
4 | SKYLIGHT DOUBLE CLEAR | 34 | 3 | VerySmooth | 3.715 | 0.720 | 0.644 | 0.817 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 4.26414E-002 | 0.36619 | 0.44111 | 0.44111 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.85326E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
3 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
4 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
5 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 20 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | ELECTRIC TANK | 7.5708E-002 | 6154.7 | 1.056 | 0.5354 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 5.0 | 3.379E-002 | 1.427E-004 | 2.202E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 5.0 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 0.0 | 0.494 | 3.545E-004 | 2.258E-004 | 0.602 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 2.709 | 8.453E-004 | 5.521E-004 | 0.276 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 37.760 | 1.178E-002 | N/A | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 0.0 | 0.944 | 2.945E-004 | N/A | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 8449.10490 | 10138.92589 | 0.72536 | 0.87043 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.36400 | 1.27032E-002 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10571.39632 | 12685.67558 | 0.30967 | 0.37160 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -32.70000 | 1.83376E-004 | 236.87965 | 5.00000 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 16729.43125 | 20075.31750 | 1.11959 | 1.34351 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 29.97600 | 1.27032E-002 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 37395.53817 | 44874.64581 | 0.92267 | 1.10721 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 1393.40969 | 0.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10000 | 1.27032E-002 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 | |
6 | ZONE3 BULK STORAGE | Heating | 113626.20119 | 136351.44143 | 2.85442 | 3.42530 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -32.70000 | 1.83376E-004 | 3204.84228 | 0.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 12539.34 | 0.87043 | 0.87043 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 14539.89 | 0.37160 | 0.37160 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 24551.77 | 1.34351 | 1.34351 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 55146.98 | 1.10721 | 1.10721 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.87043 |
2 | AirTerminal:SingleDuct:Uncontrolled | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.34351 |
3 | ZoneHVAC:UnitHeater | ZONE3UNITHEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.42530 |
4 | Fan:ConstantVolume | ZONE3UNITHEATERFAN | Design Size Maximum Flow Rate [m3/s] | 3.42530 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATERHEATINGCOIL | Design Size Nominal Capacity [W] | 136351.44729 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3HIRADIANT | User-Specified Heating Design Capacity [W] | 136351.44143 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.87043 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.87043 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.87043 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.87043 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.87043 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.87043 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.34351 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.34351 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.34351 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.34351 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.34351 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.34351 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.87043 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.34351 |
25 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.87043 |
26 | Controller:OutdoorAir | PSZ-OFFICE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.87043 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.87043 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.87043 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.87043 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.87043 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.43522 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.58029 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 14800.68624 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 15208.85000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 7604.42500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 7604.42500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.77931 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.77931 |
40 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.77931 |
41 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.77931 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15208.85000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25500.21430 |
44 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
45 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
46 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.87043 |
47 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 963.70061 |
48 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 25500.21430 |
49 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.34351 |
50 | Controller:OutdoorAir | PSZ-FINE STORAGE OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.34351 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.34351 |
53 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.34351 |
54 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.34351 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.34351 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67176 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.89567 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 30586.58705 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 31901.14000 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 15950.57000 |
61 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 15950.57000 |
62 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68731 |
63 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68731 |
64 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68731 |
65 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68731 |
66 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31901.14000 |
67 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 61844.53794 |
68 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
69 | AirLoopHVAC:UnitarySystem | PSZ-FINE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
70 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.34351 |
71 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1487.47404 |
72 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 61844.53794 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 14533.3 | 12.02 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 30857.1 | 17.49 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | ML KING BIRTHDAY | Holiday | InputFile | 01/16 | 1 |
3 | WASHINGTON'S BIRTHDAY | Holiday | InputFile | 02/20 | 1 |
4 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
5 | FOURTH OF JULY | Holiday | InputFile | 07/04 | 1 |
6 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
7 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
8 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
9 | THANKSGIVING DAY | Holiday | InputFile | 11/23 | 1 |
10 | CHRISTMAS DAY | Holiday | InputFile | 12/25 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 7 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.3530297251 | 0.3423225954 | Pass | Pass | 0.9177451415 | 0.8601377988 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 1.0030255360 | 0.8965267223 | Pass | Pass | 0.6431463991 | 0.6025631488 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 5.0497466413E-005 | 8.9448756962E-005 | Pass | Pass | 2.4623962005E-002 | 2.1312030508E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.294 | 0.307 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.294 | 0.307 | 39.02 | 30.56 | 0.00 | 90.00 | N |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.294 | 0.307 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL | 0.30 | 0.294 | 0.307 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.294 | 0.307 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL | 0.30 | 0.294 | 0.307 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL | 0.30 | 0.294 | 0.307 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.165 | 0.168 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.294 | 0.307 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.294 | 0.307 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL | 0.30 | 0.294 | 0.307 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.165 | 0.168 | 3204.84 | 3189.98 | 270.00 | 0.00 | |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.104 | 236.88 | 236.88 | 90.00 | 180.00 | ||
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.043 | 1156.53 | 1156.53 | 90.00 | 180.00 | ||
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.040 | 3204.84 | 3204.84 | 90.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.29_SHGC_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.647 | 0.445 | 0.451 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.29_SHGC_0.45 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.647 | 0.445 | 0.451 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | ||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.647 | 0.445 | 0.451 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.647 | 0.445 | 0.451 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | ||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 2.842 | 0.517 | 0.519 | ||||||||||||
North Total or Average | 6.51 | 1.647 | 0.445 | 0.451 | ||||||||||||
Non-North Total or Average | 26.02 | 3.141 | 0.536 | 0.537 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.014 | 1.195 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | 7.6531 | 236.88 | 1812.87 | LightsWired | BLDG_LIGHT_OFFICE_SCH | 58.12 | 168.00 | 53.47 | 0.0000 | Y | 18.20 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | 6.6844 | 1393.41 | 9314.09 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 106.08 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | 3.3906 | 3204.84 | 10866.44 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 61.98 | 168.00 | 56.77 | 0.0000 | Y | 115.80 |
Interior Lighting Total | 4.5487 | 4835.13 | 21993.40 | 240.07 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous | 0.14 | 1812.87 | 262.87 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous | 0.05 | 1812.87 | 90.64 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Stepped | 0.12 | 10866.44 | 1260.51 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 85.54 | AstronomicalClock | - | 42.55 | 42.55 | 0.68 | |
EXTERIOR_LIGHTS_B | 4959.90 | AstronomicalClock | - | 83.52 | 71.23 | 66.32 | |
Exterior Lighting Total | 5045.44 | 67.00 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15208.85 | 11852.41 | 3356.44 | 0.78 | 4.12 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31901.14 | 21925.97 | 9975.17 | 0.69 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 14533.3 | 12.02 | ||||
PSZ-FINE STORAGE COOLING COIL | 30857.1 | 17.49 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATERHEATINGCOIL | Coil:Heating:Fuel | 136351.45 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 25500.21 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 61844.54 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 3.43 | 318.25 | 92.91 | 1.00 | 3.30 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.87 | 963.70 | 1107.16 | 1.00 | 1.44 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.34 | 1487.47 | 1107.16 | 1.00 | 1.34 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
ELECTRIC TANK | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.54 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8449.10 | 10138.93 | 42.80 | 0.725 | 0.870 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00826 | 28.36 | 0.01270 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 16729.43 | 20075.32 | 14.41 | 1.120 | 1.344 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 26.70 | 26.70 | 0.00855 | 29.98 | 0.01270 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 10.00 | 0.00 | 0.00394 | 30.10 | 0.01270 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10571.40 | 12685.68 | 53.55 | 0.310 | 0.372 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00775 | -32.70 | 0.00018 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 37395.54 | 44874.65 | 32.20 | 0.923 | 1.107 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15.56 | 15.55 | 0.00644 | -32.70 | 0.00018 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 113626.20 | 136351.44 | 42.55 | 2.854 | 3.425 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 10.00 | 9.99 | 0.00796 | -32.70 | 0.00018 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.87 | 0.87 | 0.37 | 0.37 | 0.8704 | 0.8704 | 0.8704 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.34 | 1.34 | 1.11 | 1.11 | 1.3435 | 1.3435 | 1.3435 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | 136351.447 | 136351.447 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 136351.45 | 136351.45 | 3.425303 | -2.18 | -2.18 | 0.00574377 | 43.33 | 26.55 | 0.01600000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 9.99 | 0.00796215 | 99.9999 | 136351.44 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 7604.425 | 0.000 | 0.870430 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 7604.43 | 6689.93 | 0.870430 | 24.42 | 16.33 | 0.00878635 | 12.00 | 10.88 | 0.00800000 | 28.36 | 0.01270325 | 20.60 | 11.7511 | 23.90 | 0.00826479 | 42.9088 | 8449.10 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 25500.214 | 25500.214 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 25500.21 | 25500.21 | 0.870427 | 6.26 | 5.67 | 0.00567024 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 11.7511 | 21.10 | 0.00775412 | 47.7637 | 10571.40 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 15950.570 | 0.000 | 1.343510 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 15950.57 | 12618.88 | 1.343510 | 27.78 | 18.31 | 0.00986856 | 12.00 | 10.88 | 0.00800000 | 30.10 | 0.01270324 | 21.10 | 31.6122 | 26.70 | 0.00855466 | 37.5832 | 16713.57 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 61844.538 | 61844.538 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 61844.54 | 61844.54 | 1.343506 | -2.95 | -2.95 | 0.00403736 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 31.6123 | 15.55 | 0.00643567 | 56.2597 | 37395.54 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATERHEATINGCOIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3UNITHEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 136351.447 | 136351.447 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1034.5832 | 1004.8586 | 1.1539 | ZONE3UNITHEATERFAN | Fan:ConstantVolume | 3.425303 | 3.95254284 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 136351.45 | 136351.45 | 1.0000 | 3.95254284 | 3.425303 | -2.18 | -2.18 | 0.00574377 | 12146.0 | 43.33 | 26.55 | 0.01600000 | 84847.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 136351.45 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 9.99 | 0.00796215 | 9.99 | 0.00796215 | 99.9999 | 136351.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 7604.425 | 0.000 | 0.870430 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1734 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 7604.43 | 6689.93 | 1.0000 | 1.00441081 | 0.870430 | 24.42 | 16.33 | 0.00878635 | 46915.2 | 12.00 | 10.88 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7604.43 | 28.36 | 0.01270325 | 20.60 | 0.10228487 | 11.7511 | 23.90 | 0.00826479 | 23.90 | 0.00826479 | 42.9088 | 8449.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25500.214 | 25500.214 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.870427 | 1.00440710 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 25500.21 | 25500.21 | 1.0000 | 1.00440710 | 0.870427 | 6.26 | 5.67 | 0.00567024 | 20532.8 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25500.21 | -32.70 | 0.00018338 | -32.70 | 0.10228487 | 11.7511 | 21.05 | 0.00775412 | 21.10 | 0.00775412 | 47.7637 | 10571.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15950.570 | 0.000 | 1.343510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.1852 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 15950.57 | 12618.88 | 1.0000 | 1.55030958 | 1.343510 | 27.78 | 18.31 | 0.00986856 | 53099.8 | 12.00 | 10.88 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15950.57 | 30.10 | 0.01270324 | 21.10 | 0.42471267 | 31.6122 | 26.70 | 0.00855640 | 26.70 | 0.00855466 | 37.5832 | 16713.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 61844.538 | 61844.538 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.343506 | 1.55030459 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 61844.54 | 61844.54 | 1.0000 | 1.55030459 | 1.343506 | -2.95 | -2.95 | 0.00403736 | 7106.1 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61844.54 | -32.70 | 0.00018338 | -32.70 | 0.42471267 | 31.6123 | 15.56 | 0.00643567 | 15.55 | 0.00643567 | 56.2597 | 37395.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-FINE STORAGE OA CONTROLLER | DifferentialDryBulb | 0.42 | 1.34 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2865.00 | 2886.83 | 2255.50 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 |
Facility | 2865.00 | 2886.83 | 2255.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 117.67 | 0.17 | 83.00 | 0.17 |
ZONE2 FINE STORAGE | 585.50 | 1.50 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 85.50 | 0.00 | 0.00 | 0.00 |
Facility | 737.33 | 1.67 | 83.00 | 0.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.341 | 0.374 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 3.73 | 5.00 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 517.62 | 3230.53 | 16-APR-13:30 | 40958.52 | 30-JUN-15:00 |
Electricity:Building | 379.35 | 2747.53 | 02-APR-14:10 | 28431.24 | 15-NOV-16:00 |
Electricity:Zone:ZONE1 OFFICE | 50.14 | 855.52 | 19-FEB-14:30 | 3087.86 | 02-JAN-08:10 |
InteriorLights:Electricity | 240.07 | 2173.78 | 02-APR-14:10 | 18318.62 | 15-NOV-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 18.20 | 281.77 | 19-FEB-14:30 | 1175.36 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 240.07 | 2173.78 | 02-APR-14:10 | 18318.62 | 15-NOV-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 106.08 | 931.41 | 01-JAN-00:10 | 7916.98 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 106.08 | 931.41 | 01-JAN-00:10 | 7916.98 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 223.13 | 960.59 | 08-JAN-11:10 | 17436.59 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 115.80 | 960.59 | 08-JAN-11:10 | 9236.47 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 31.95 | 573.75 | 01-JAN-00:10 | 1912.50 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 139.28 | 573.75 | 01-JAN-00:10 | 10112.62 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Electricity:Plant | 27.32 | 483.00 | 03-JAN-20:40 | 3095.27 | 25-FEB-12:10 |
WaterSystems:Electricity | 27.32 | 483.00 | 03-JAN-20:40 | 3095.27 | 25-FEB-12:10 |
Water Heater:WaterSystems:Electricity | 27.32 | 483.00 | 03-JAN-20:40 | 3095.27 | 25-FEB-12:10 |
Fans:Electricity | 38.06 | 0.00 | 19-MAR-14:00 | 2769.42 | 02-JAN-07:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 517.62 | 3230.53 | 16-APR-13:30 | 40958.52 | 30-JUN-15:00 |
ElectricityPurchased:Plant | 517.62 | 3230.53 | 16-APR-13:30 | 40958.52 | 30-JUN-15:00 |
Cogeneration:ElectricityPurchased | 517.62 | 3230.53 | 16-APR-13:30 | 40958.52 | 30-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 517.62 | 3230.53 | 16-APR-13:30 | 40958.52 | 30-JUN-15:00 |
ElectricityNet:Plant | 517.62 | 3230.53 | 16-APR-13:30 | 40958.52 | 30-JUN-15:00 |
Cogeneration:ElectricityNet | 517.62 | 3230.53 | 16-APR-13:30 | 40958.52 | 30-JUN-15:00 |
Electricity:HVAC | 43.94 | 0.00 | 19-MAR-14:00 | 13428.50 | 29-JUN-16:10 |
General:Fans:Electricity | 38.06 | 0.00 | 19-MAR-14:00 | 2769.42 | 02-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 5.88 | 0.00 | 01-JAN-00:10 | 10977.32 | 29-JUN-16:10 |
ExteriorLights:Electricity | 67.00 | 0.00 | 01-JAN-08:20 | 5045.44 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 67.00 | 0.00 | 01-JAN-08:20 | 5045.44 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1360.58 | 0.00 | 19-MAR-14:00 | 279620.25 | 04-JAN-17:10 |
Gas:HVAC | 1360.58 | 0.00 | 19-MAR-14:00 | 279620.25 | 04-JAN-17:10 |
Heating:Gas | 1360.58 | 0.00 | 19-MAR-14:00 | 279620.25 | 04-JAN-17:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2105.76 | 0.00 | 19-MAR-14:00 | 425837.06 | 18-DEC-17:10 |
EnergyTransfer:Building | 1025.95 | 0.00 | 19-MAR-14:00 | 208760.28 | 04-JAN-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 65.24 | 0.00 | 01-JAN-00:40 | 22373.89 | 13-MAR-06:10 |
Heating:EnergyTransfer | 997.28 | 0.00 | 19-MAR-14:00 | 208760.28 | 04-JAN-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 52.83 | 0.00 | 01-JAN-00:40 | 22373.89 | 13-MAR-06:10 |
Cooling:EnergyTransfer | 28.67 | 0.00 | 01-JAN-00:10 | 23401.20 | 29-JUN-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 12.41 | 0.00 | 01-JAN-00:10 | 9201.15 | 29-JUN-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 212.14 | 0.00 | 01-JAN-00:40 | 61946.18 | 12-FEB-22:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 195.88 | 0.00 | 01-JAN-00:40 | 61946.18 | 12-FEB-22:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 16.26 | 0.00 | 01-JAN-00:10 | 15866.24 | 30-JUN-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 748.56 | 0.00 | 17-JAN-13:10 | 137695.42 | 18-DEC-13:30 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 748.56 | 0.00 | 17-JAN-13:10 | 137695.42 | 18-DEC-13:30 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1079.81 | 0.00 | 19-MAR-14:00 | 223696.20 | 04-JAN-17:10 |
HeatingCoils:EnergyTransfer | 1052.08 | 0.00 | 19-MAR-14:00 | 223696.20 | 04-JAN-17:10 |
CoolingCoils:EnergyTransfer | 27.73 | 0.00 | 01-JAN-00:10 | 44421.55 | 29-JUN-16:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 52.828 | -12.412 | 0.000 | 0.000 | 4.009 | 18.195 | 31.946 | 10.399 | 0.000 | 0.354 | 0.000 | 0.000 | -9.834 | 0.000 | -34.534 | -60.952 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 195.883 | -16.256 | 0.000 | 0.000 | 0.000 | 106.079 | 0.000 | 0.000 | 0.000 | 0.600 | 0.002 | 0.000 | 0.000 | 0.000 | -137.781 | -148.526 |
ZONE3 BULK STORAGE | 748.563 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 115.796 | 107.336 | 29.783 | 0.000 | 15.331 | 0.000 | 0.000 | -16.000 | 0.000 | -727.131 | -273.678 |
Total Facility | 748.563 | 0.000 | 248.711 | -28.668 | 0.000 | 0.000 | 4.009 | 240.071 | 139.282 | 40.182 | 0.000 | 16.284 | 0.002 | 0.000 | -25.834 | 0.000 | -899.446 | -483.155 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 08-JUL-07:02 | 0.00 | 0.00 | 0.00 | -14566.44 | 0.00 | 0.00 | 314.42 | 1135.19 | 1912.50 | 0.00 | 0.00 | 0.00 | 11589.55 | 0.00 | -146.97 | 0.00 | -238.25 | 0.00 |
ZONE2 FINE STORAGE | 02-JUL-14:51 | 0.00 | 0.00 | 0.00 | -28515.14 | 0.00 | 0.00 | 0.00 | 931.41 | 0.00 | 0.00 | 0.00 | 0.00 | 27583.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-JUL-14:51 | 0.00 | 0.00 | 0.00 | -28515.14 | 0.00 | 0.00 | 0.00 | 2173.78 | 573.75 | 6925.55 | 0.00 | 0.00 | 18842.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 18-APR-06:01 | 0.00 | 0.00 | 25033.98 | 0.00 | 0.00 | 0.00 | 104.41 | 614.85 | 956.25 | 41.21 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2117.57 | -24633.13 |
ZONE2 FINE STORAGE | 13-FEB-06:01 | 0.00 | 0.00 | 64920.21 | 0.00 | 0.00 | 0.00 | 0.00 | 931.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -19052.73 | -46798.89 |
ZONE3 BULK STORAGE | 18-DEC-13:30 | 137693.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8522.19 | 8200.12 | 0.00 | 0.00 | 0.00 | 19440.51 | 0.00 | -569.38 | 0.00 | -173287.08 | 0.00 |
Total Facility | 13-FEB-06:01 | 136504.87 | 0.00 | 86710.73 | 0.00 | 0.00 | 0.00 | 60.00 | 2369.13 | 2623.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2847.98 | 0.00 | -129216.48 | -96204.04 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.8704 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.8704 | 0.1175 | 1.0000 | 0.1023 | 0.1175 | ||
PSZ-FINE STORAGE | 1.3435 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.3435 | 0.3161 | 1.0000 | 0.4247 | 0.3161 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.8704 | 0.0000 | 5.0000 | 1.0000 | 0.1023 | 0.8704 | 1.0000 | 1.0000 | 0.1023 | 0.1175 | ||
PSZ-FINE STORAGE | 1.3435 | 0.0000 | 0.0000 | 1.0000 | 0.4247 | 1.3435 | 1.0000 | 1.0000 | 0.4247 | 0.3161 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 5.0000 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 0.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 5.00 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.8704 | 0.8704 | 0.8704 | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.3435 | 1.3435 | 1.3435 | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.8704 | 0.8704 | 0.8704 | 0.8704 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.3435 | 1.3435 | 1.3435 | 1.3435 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | 0.8704 | 0.8704 | 0.8704 | 0.1023 | 0.2753 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 1.3435 | 1.3435 | 1.3435 | 0.4247 | 0.3836 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.8704 | 0.8704 | 0.8704 | 0.8704 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.3435 | 1.3435 | 1.3435 | 1.3435 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:57
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 0.00 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 83.00 |
Number of hours cooling loads not met | 0.17 |
Number of hours not met | 83.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 1360.58 | 279620.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 5.88 | 10977.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 240.07 | 18318.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 67.00 | 5045.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 139.28 | 10112.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 38.06 | 2769.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 27.32 | 3095.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 139.28 | 517.62 |
Natural Gas | 0.00 | 1360.58 |
Additional | 0.00 | 0.00 |
Total | 139.28 | 1878.20 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 49.65 |
Space Heating | 0.00 |
Space Cooling | 1.22 |
Fans (All) | 7.87 |
Service Water Heating | 5.65 |
Receptacle Equipment | 28.81 |
Miscellaneous (All) | 107.05 |
Subtotal | 107.05 |
Natural Gas [MJ/m2] | |
Space Heating | 281.39 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 281.39 |
Subtotal | 281.39 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.78 |
Space Heating | 72.44 |
Space Cooling | 0.31 |
Fans (All) | 2.03 |
Service Water Heating | 1.45 |
Receptacle Equipment | 7.42 |
Miscellaneous | 3.57 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OFFICE LIGHT SCHEDULE | 3792. | 8760. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
STORAGE LIGHT SCHEDULE | 3232. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
OFFICE LIGHT WITH SENSOR SCHEDULE | 3430. | 8760. |
STORAGE LIGHT WITH SENSOR SCHEDULE | 2877. | 8760. |
OFFICE_PLUG_SCH | 4700. | 8760. |
BLDG_LIGHT_OFFICE_SCH | 3031. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 3232. | 8760. |
BLDG_OCC_SCH | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | HEATING SETPOINT WITH SB | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | OFFICE THERMOSTAT DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | FINE STORAGE THERMOSTAT DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.352495E+12 |
February | 0.000 | 0.264656E+12 |
March | 0.000 | 0.181991E+12 |
April | 0.000 | 0.616883E+11 |
May | 0.000 | 0.194497E+10 |
June | 0.000 | 0.182457E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.565687E+09 |
October | 0.000 | 0.203178E+11 |
November | 0.000 | 0.144160E+12 |
December | 0.000 | 0.332745E+12 |
Annual Sum or Average | 0.136058E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.352495E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.352495E+12 |
February | 0.000 | 0.264656E+12 |
March | 0.000 | 0.181991E+12 |
April | 0.000 | 0.616883E+11 |
May | 0.000 | 0.194497E+10 |
June | 0.000 | 0.182457E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.565687E+09 |
October | 0.000 | 0.203178E+11 |
November | 0.000 | 0.144160E+12 |
December | 0.000 | 0.332745E+12 |
Annual Sum or Average | 0.136058E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.352495E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.352495E+12 |
February | 0.000 | 0.264656E+12 |
March | 0.000 | 0.181991E+12 |
April | 0.000 | 0.616883E+11 |
May | 0.000 | 0.194497E+10 |
June | 0.000 | 0.182457E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.565687E+09 |
October | 0.000 | 0.203178E+11 |
November | 0.000 | 0.144160E+12 |
December | 0.000 | 0.332745E+12 |
Annual Sum or Average | 0.136058E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.352495E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.352495E+12 |
February | 0.000 | 0.264656E+12 |
March | 0.000 | 0.181991E+12 |
April | 0.000 | 0.616883E+11 |
May | 0.000 | 0.194497E+10 |
June | 0.000 | 0.182457E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.565687E+09 |
October | 0.000 | 0.203178E+11 |
November | 0.000 | 0.144160E+12 |
December | 0.000 | 0.332745E+12 |
Annual Sum or Average | 0.136058E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.352495E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.352495E+12 |
February | 0.000 | 0.264656E+12 |
March | 0.000 | 0.181991E+12 |
April | 0.000 | 0.616883E+11 |
May | 0.000 | 0.194497E+10 |
June | 0.000 | 0.182457E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.565687E+09 |
October | 0.000 | 0.203178E+11 |
November | 0.000 | 0.144160E+12 |
December | 0.000 | 0.332745E+12 |
Annual Sum or Average | 0.136058E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.352495E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.352495E+12 |
February | 0.000 | 0.264656E+12 |
March | 0.000 | 0.181991E+12 |
April | 0.000 | 0.616883E+11 |
May | 0.000 | 0.194497E+10 |
June | 0.000 | 0.182457E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.565687E+09 |
October | 0.000 | 0.203178E+11 |
November | 0.000 | 0.144160E+12 |
December | 0.000 | 0.332745E+12 |
Annual Sum or Average | 0.136058E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.352495E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.352495E+12 |
February | 0.000 | 0.264656E+12 |
March | 0.000 | 0.181991E+12 |
April | 0.000 | 0.616883E+11 |
May | 0.000 | 0.194497E+10 |
June | 0.000 | 0.182457E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.565687E+09 |
October | 0.000 | 0.203178E+11 |
November | 0.000 | 0.144160E+12 |
December | 0.000 | 0.332745E+12 |
Annual Sum or Average | 0.136058E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.352495E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.352495E+12 |
February | 0.000 | 0.264656E+12 |
March | 0.000 | 0.181991E+12 |
April | 0.000 | 0.616883E+11 |
May | 0.000 | 0.194497E+10 |
June | 0.000 | 0.182457E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.565687E+09 |
October | 0.000 | 0.203178E+11 |
November | 0.000 | 0.144160E+12 |
December | 0.000 | 0.332745E+12 |
Annual Sum or Average | 0.136058E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.352495E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.352495E+12 |
February | 0.000 | 0.264656E+12 |
March | 0.000 | 0.181991E+12 |
April | 0.000 | 0.616883E+11 |
May | 0.000 | 0.194497E+10 |
June | 0.000 | 0.182457E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.565687E+09 |
October | 0.000 | 0.203178E+11 |
November | 0.000 | 0.144160E+12 |
December | 0.000 | 0.332745E+12 |
Annual Sum or Average | 0.136058E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.352495E+12 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1170687.48 | 3106.90 | 21-JAN-08:05 | -22.1 | -22.3 | 0.192175E+09 | 236.59 | 19-JAN-08:20 | -3.5 | -3.6 |
February | 2822214.30 | 3160.01 | 11-FEB-08:05 | -15.5 | -15.9 | 0.177503E+09 | 236.59 | 09-FEB-08:20 | -2.4 | -2.8 |
March | 5691090.17 | 3419.79 | 11-MAR-07:05 | -15.1 | -15.4 | 0.208890E+09 | 236.60 | 28-MAR-07:19 | 2.07 | 0.53 |
April | 10238323.40 | 2157.75 | 06-APR-07:05 | -4.6 | -5.6 | 0.194810E+09 | 277.30 | 13-APR-15:00 | 20.00 | 8.07 |
May | 0.804607E+09 | 12600.47 | 27-MAY-07:03 | 17.20 | 13.07 | 0.232155E+09 | 335.42 | 27-MAY-07:10 | 17.20 | 13.07 |
June | 0.245448E+10 | 10984.49 | 29-JUN-06:03 | 23.17 | 19.91 | 0.255877E+09 | 344.89 | 28-JUN-07:10 | 23.17 | 20.19 |
July | 0.434057E+10 | 14566.46 | 08-JUL-07:02 | 13.40 | 11.19 | 0.250104E+09 | 344.89 | 29-JUL-07:10 | 22.48 | 20.27 |
August | 0.361614E+10 | 14012.23 | 05-AUG-07:02 | 15.78 | 12.68 | 0.268742E+09 | 344.89 | 05-AUG-07:10 | 15.78 | 12.68 |
September | 0.113001E+10 | 13636.80 | 02-SEP-07:02 | 13.17 | 11.14 | 0.229826E+09 | 344.89 | 02-SEP-07:10 | 13.17 | 11.14 |
October | 37692536.09 | 2212.76 | 25-OCT-07:05 | -3.2 | -3.4 | 0.196342E+09 | 301.57 | 21-OCT-15:00 | 20.00 | 11.44 |
November | 6270870.94 | 2410.73 | 10-NOV-08:05 | -8.5 | -9.4 | 0.185918E+09 | 246.40 | 01-NOV-15:00 | 17.80 | 13.25 |
December | 2960349.70 | 2807.48 | 09-DEC-08:05 | -13.5 | -13.8 | 0.192893E+09 | 236.60 | 30-DEC-08:20 | -4.5 | -5.2 |
Annual Sum or Average | 0.124127E+11 | 0.258524E+10 | ||||||||
Minimum of Months | 1170687.48 | 2157.75 | -22.1 | -22.3 | 0.177503E+09 | 236.59 | -4.5 | -5.2 | ||
Maximum of Months | 0.434057E+10 | 14566.46 | 23.17 | 19.91 | 0.268742E+09 | 344.89 | 23.17 | 20.27 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 0.106482E+09 | 3737.61 | 08-FEB-14:00 | 5.00 | -0.2 | 0.00 | 0.00 | 01-FEB-00:10 | -23.1 | -23.4 |
March | 0.521259E+09 | 6377.96 | 10-MAR-13:25 | -1.1 | -3.0 | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.2 |
April | 0.101288E+10 | 6099.75 | 05-APR-13:55 | -0.6 | -4.5 | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.37 |
May | 0.128701E+10 | 5327.22 | 20-MAY-08:20 | 6.87 | 3.68 | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.3 |
June | 0.221550E+10 | 25725.59 | 30-JUN-20:12 | 23.13 | 17.56 | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 |
July | 0.440456E+10 | 28517.25 | 02-JUL-14:51 | 22.20 | 15.61 | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.56 |
August | 0.262539E+10 | 20465.51 | 09-AUG-17:50 | 26.70 | 20.75 | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 |
September | 0.210453E+10 | 7477.78 | 06-SEP-07:03 | 4.05 | 3.63 | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 |
October | 0.161655E+10 | 7749.29 | 25-OCT-07:03 | -3.2 | -3.4 | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 |
November | 0.362123E+09 | 3508.74 | 16-NOV-11:30 | 5.25 | 0.92 | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.50 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.162563E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -21.9 | -22.1 | 0.00 | 0.00 | -23.1 | -23.4 | ||
Maximum of Months | 0.440456E+10 | 28517.25 | 26.70 | 20.75 | 0.00 | 0.00 | 19.75 | 18.15 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -23.1 | -23.4 | 0.00 | 0.00 | 01-FEB-00:10 | -23.1 | -23.4 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.3 | -3.2 | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.2 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.37 | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.37 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.3 | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.56 | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.56 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.50 | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.50 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.4 | 0.00 | 0.00 | -23.1 | -23.4 | ||
Maximum of Months | 0.00 | 0.00 | 19.75 | 18.15 | 0.00 | 0.00 | 19.75 | 18.15 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118413E+11 | 23490.39 | 19-JAN-06:01 | -3.3 |
February | 0.888365E+10 | 24114.14 | 21-FEB-06:01 | 2.80 |
March | 0.813657E+10 | 23903.63 | 28-MAR-06:01 | 1.70 |
April | 0.404123E+10 | 25033.53 | 18-APR-06:01 | 12.38 |
May | 0.806226E+09 | 24249.91 | 15-MAY-06:02 | 7.52 |
June | 36344173.86 | 12900.94 | 02-JUN-07:03 | 10.18 |
July | 9119678.97 | 837.97 | 05-JUL-06:07 | 20.60 |
August | 10342873.08 | 476.21 | 09-AUG-06:15 | 19.07 |
September | 0.335411E+09 | 24016.42 | 29-SEP-06:02 | 7.30 |
October | 0.278763E+10 | 24795.07 | 31-OCT-06:01 | 9.82 |
November | 0.555826E+10 | 24877.01 | 01-NOV-06:01 | 10.78 |
December | 0.103823E+11 | 23717.37 | 05-DEC-06:01 | -1.1 |
Annual Sum or Average | 0.528284E+11 | |||
Minimum of Months | 9119678.97 | 476.21 | -3.3 | |
Maximum of Months | 0.118413E+11 | 25033.53 | 20.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.492167E+11 | 64413.56 | 09-JAN-06:01 | -31.8 |
February | 0.364251E+11 | 64920.08 | 13-FEB-06:01 | -24.0 |
March | 0.256773E+11 | 64560.38 | 15-MAR-05:01 | -22.2 |
April | 0.105110E+11 | 63422.42 | 04-APR-19:02 | -7.3 |
May | 0.863938E+09 | 46638.15 | 01-MAY-05:01 | -3.4 |
June | 0.206635E+09 | 1929.69 | 06-JUN-13:00 | 25.60 |
July | 0.112359E+09 | 1501.63 | 17-JUL-06:25 | 13.60 |
August | 0.131571E+09 | 1558.06 | 31-AUG-07:00 | 17.20 |
September | 0.145588E+09 | 1535.14 | 27-SEP-07:00 | 6.70 |
October | 0.515080E+10 | 62202.93 | 30-OCT-05:01 | -9.9 |
November | 0.214524E+11 | 64052.28 | 25-NOV-00:02 | -15.0 |
December | 0.459902E+11 | 64640.50 | 18-DEC-06:01 | -16.4 |
Annual Sum or Average | 0.195884E+12 | |||
Minimum of Months | 0.112359E+09 | 1501.63 | -31.8 | |
Maximum of Months | 0.492167E+11 | 64920.08 | 25.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198292E+12 | 137515.27 | 04-JAN-10:00 | -28.9 |
February | 0.149823E+12 | 137465.46 | 12-FEB-22:30 | -16.1 |
March | 0.975389E+11 | 120821.45 | 15-MAR-05:00 | -22.2 |
April | 0.299194E+11 | 77279.67 | 04-APR-18:54 | -7.2 |
May | 0.219800E+09 | 14018.48 | 01-MAY-04:00 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.519389E+10 | 39696.29 | 31-OCT-20:55 | -2.2 |
November | 0.785412E+11 | 102605.07 | 25-NOV-01:51 | -15.6 |
December | 0.189036E+12 | 137695.42 | 18-DEC-13:30 | -22.8 |
Annual Sum or Average | 0.748564E+12 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.198292E+12 | 137695.42 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156419E+10 | 1175.36 | 02-JAN-08:09 | 0.267964E+10 | 1912.50 | 02-JAN-08:09 |
February | 0.139733E+10 | 1161.28 | 02-FEB-16:00 | 0.243949E+10 | 1912.50 | 01-FEB-08:09 |
March | 0.158288E+10 | 1158.86 | 13-MAR-07:10 | 0.277107E+10 | 1912.50 | 01-MAR-08:09 |
April | 0.148583E+10 | 1152.96 | 01-APR-07:10 | 0.263007E+10 | 1912.50 | 01-APR-07:10 |
May | 0.151467E+10 | 1107.16 | 19-MAY-08:30 | 0.272536E+10 | 1912.50 | 01-MAY-07:10 |
June | 0.148879E+10 | 1137.17 | 30-JUN-07:10 | 0.267579E+10 | 1912.50 | 01-JUN-07:10 |
July | 0.148754E+10 | 1135.19 | 08-JUL-07:10 | 0.267964E+10 | 1912.50 | 01-JUL-07:10 |
August | 0.155654E+10 | 1152.58 | 31-AUG-07:10 | 0.277107E+10 | 1912.50 | 01-AUG-07:10 |
September | 0.148860E+10 | 1154.02 | 19-SEP-07:10 | 0.263007E+10 | 1912.50 | 01-SEP-07:10 |
October | 0.153941E+10 | 1174.37 | 31-OCT-07:10 | 0.267964E+10 | 1912.50 | 02-OCT-07:10 |
November | 0.151113E+10 | 1175.36 | 06-NOV-16:49 | 0.258435E+10 | 1912.50 | 01-NOV-07:10 |
December | 0.157848E+10 | 1175.36 | 01-DEC-16:19 | 0.267964E+10 | 1912.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.181954E+11 | 0.319458E+11 | ||||
Minimum of Months | 0.139733E+10 | 1107.16 | 0.243949E+10 | 1912.50 | ||
Maximum of Months | 0.158288E+10 | 1175.36 | 0.277107E+10 | 1912.50 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.882361E+10 | 7916.98 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.807588E+10 | 7916.98 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.932993E+10 | 7916.98 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.874314E+10 | 7916.98 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.907677E+10 | 7916.98 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.899629E+10 | 7916.98 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.882361E+10 | 7916.98 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.932993E+10 | 7916.98 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.874314E+10 | 7916.98 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.882361E+10 | 7916.98 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.848998E+10 | 7916.98 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.882361E+10 | 7916.98 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106079E+12 | ||||
Minimum of Months | 0.807588E+10 | 7916.98 | 0.00 | 0.00 | |
Maximum of Months | 0.932993E+10 | 7916.98 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.998604E+10 | 9236.47 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.898799E+10 | 9236.47 | 01-FEB-15:20 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.102201E+11 | 9236.47 | 06-MAR-15:50 | 0.956462E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.945188E+10 | 8879.33 | 04-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.962244E+10 | 8879.33 | 06-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.950240E+10 | 8522.19 | 09-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.933579E+10 | 8522.19 | 05-JUL-09:30 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.993213E+10 | 8879.33 | 15-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.947138E+10 | 8879.33 | 01-SEP-08:09 | 0.885613E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.973389E+10 | 9236.47 | 17-OCT-14:20 | 0.885613E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.955042E+10 | 9236.47 | 02-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.100014E+11 | 9236.47 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.115796E+12 | 0.107336E+12 | ||||
Minimum of Months | 0.898799E+10 | 8522.19 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.102201E+11 | 9236.47 | 0.956462E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.544079E+09 | 0.156419E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644254E+10 |
February | 0.500553E+09 | 0.139733E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495581E+10 |
March | 0.587605E+09 | 0.158288E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442713E+10 |
April | 0.544079E+09 | 0.148583E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5183095.55 | 0.252428E+10 |
May | 0.565842E+09 | 0.151467E+10 | 0.272536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52881305.79 | 0.117721E+10 |
June | 0.565842E+09 | 0.148879E+10 | 0.267579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117668E+09 | 0.683103E+09 |
July | 0.544079E+09 | 0.148754E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113842E+09 | 0.554325E+09 |
August | 0.587605E+09 | 0.155654E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61514377.39 | 0.871511E+09 |
September | 0.544079E+09 | 0.148860E+10 | 0.263007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2720246.62 | 0.141466E+10 |
October | 0.544079E+09 | 0.153941E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226377E+10 |
November | 0.522316E+09 | 0.151113E+10 | 0.258435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344034E+10 |
December | 0.544079E+09 | 0.157848E+10 | 0.267964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577897E+10 |
Annual Sum or Average | 0.659424E+10 | 0.181954E+11 | 0.319458E+11 | 0.353809E+09 | 0.345336E+11 | ||||
Minimum of Months | 0.500553E+09 | 0.139733E+10 | 0.243949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554325E+09 |
Maximum of Months | 0.587605E+09 | 0.158288E+10 | 0.277107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117668E+09 | 0.644254E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.882361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247662E+11 |
February | 0.00 | 0.807588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206312E+11 |
March | 0.00 | 0.932993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145806E+11 |
April | 0.00 | 0.874314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108408E+09 | 0.102380E+11 |
May | 0.00 | 0.907677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129991E+09 | 0.446351E+10 |
June | 0.00 | 0.899629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181916E+09 | 0.319958E+10 |
July | 0.00 | 0.882361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133448E+09 | 0.315642E+10 |
August | 0.00 | 0.932993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36235546.67 | 0.417495E+10 |
September | 0.00 | 0.874314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3071201.27 | 0.559958E+10 |
October | 0.00 | 0.882361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6644334.65 | 0.702336E+10 |
November | 0.00 | 0.848998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148273E+11 |
December | 0.00 | 0.882361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251199E+11 |
Annual Sum or Average | 0.106079E+12 | 0.599714E+09 | 0.137781E+12 | ||||||
Minimum of Months | 0.00 | 0.807588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315642E+10 |
Maximum of Months | 0.00 | 0.932993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181916E+09 | 0.251199E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.998604E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101438E+12 |
February | 0.00 | 0.898799E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823020E+11 |
March | 0.00 | 0.102201E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2457813.47 | 0.549722E+11 |
April | 0.00 | 0.945188E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229858E+10 | 0.297061E+11 |
May | 0.00 | 0.962244E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430968E+10 | 0.113294E+11 |
June | 0.00 | 0.950240E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203878E+10 | 0.890608E+10 |
July | 0.00 | 0.933579E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380707E+09 | 0.140345E+11 |
August | 0.00 | 0.993213E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398305E+09 | 0.174415E+11 |
September | 0.00 | 0.947138E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186380E+09 | 0.220840E+11 |
October | 0.00 | 0.973389E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.994646E+09 | 0.207549E+11 |
November | 0.00 | 0.955042E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348456E+09 | 0.498693E+11 |
December | 0.00 | 0.100014E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.993543E+11 |
Annual Sum or Average | 0.115796E+12 | 0.107336E+12 | 0.109580E+11 | 0.512192E+12 | |||||
Minimum of Months | 0.00 | 0.898799E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890608E+10 |
Maximum of Months | 0.00 | 0.102201E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430968E+10 | 0.101438E+12 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 659.25 | 02-JAN-08:09 | 1175.36 | 02-JAN-08:09 | 1912.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 21552.25 | 06-JAN-07:02 |
February | 659.25 | 01-FEB-08:09 | 1161.28 | 02-FEB-16:00 | 1912.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 21097.05 | 14-FEB-07:03 |
March | 659.25 | 01-MAR-08:09 | 1158.86 | 13-MAR-07:10 | 1912.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 17671.42 | 15-MAR-07:00 |
April | 659.25 | 01-APR-07:10 | 1152.96 | 01-APR-07:10 | 1912.50 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 281.89 | 23-APR-16:00 | 12758.80 | 05-APR-06:10 |
May | 659.25 | 01-MAY-07:10 | 1107.16 | 19-MAY-08:30 | 1912.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1776.58 | 25-MAY-17:00 | 8671.56 | 01-MAY-06:10 |
June | 659.25 | 01-JUN-07:10 | 1137.17 | 30-JUN-07:10 | 1912.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3871.63 | 29-JUN-16:10 | 4265.36 | 02-JUN-06:03 |
July | 659.25 | 01-JUL-07:10 | 1135.19 | 08-JUL-07:10 | 1912.50 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1906.08 | 28-JUL-16:10 | 4649.85 | 18-JUL-06:03 |
August | 659.25 | 01-AUG-07:10 | 1152.58 | 31-AUG-07:10 | 1912.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2374.89 | 08-AUG-16:10 | 5304.08 | 25-AUG-06:03 |
September | 659.25 | 01-SEP-07:10 | 1154.02 | 19-SEP-07:10 | 1912.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 661.89 | 01-SEP-16:10 | 7366.00 | 06-SEP-06:02 |
October | 659.25 | 02-OCT-07:10 | 1174.37 | 31-OCT-07:10 | 1912.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 11672.86 | 30-OCT-07:00 |
November | 659.25 | 01-NOV-07:10 | 1175.36 | 06-NOV-16:49 | 1912.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 15278.60 | 29-NOV-07:20 |
December | 659.25 | 01-DEC-08:09 | 1175.36 | 01-DEC-16:19 | 1912.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 20474.12 | 20-DEC-07:03 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 659.25 | 1107.16 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4265.36 | |||||
Maximum of Months | 659.25 | 1175.36 | 1912.50 | 0.00 | 0.00 | 0.00 | 0.00 | 3871.63 | 21552.25 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 7916.98 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 30502.52 | 04-JAN-16:10 |
February | 0.00 | 7916.98 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 37209.08 | 12-FEB-23:00 |
March | 0.00 | 7916.98 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 22719.17 | 14-MAR-15:10 |
April | 0.00 | 7916.98 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5260.20 | 23-APR-16:00 | 18565.30 | 26-APR-15:10 |
May | 0.00 | 7916.98 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2616.86 | 10-MAY-15:10 | 8826.30 | 20-MAY-06:10 |
June | 0.00 | 7916.98 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5093.82 | 29-JUN-16:00 | 8038.52 | 09-JUN-08:00 |
July | 0.00 | 7916.98 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3483.37 | 15-JUL-15:10 | 5823.91 | 08-JUL-15:10 |
August | 0.00 | 7916.98 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2628.56 | 08-AUG-16:00 | 10755.94 | 17-AUG-15:05 |
September | 0.00 | 7916.98 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 585.27 | 24-SEP-15:00 | 9153.27 | 20-SEP-06:10 |
October | 0.00 | 7916.98 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.89 | 19-OCT-15:10 | 12212.03 | 31-OCT-17:00 |
November | 0.00 | 7916.98 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 18103.61 | 22-NOV-01:50 |
December | 0.00 | 7916.98 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 37330.06 | 18-DEC-16:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 7916.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5823.91 | |||
Maximum of Months | 0.00 | 7916.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5260.20 | 37330.06 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 9236.47 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 150291.74 | 04-JAN-12:00 |
February | 0.00 | 9236.47 | 01-FEB-15:20 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 118198.14 | 12-FEB-22:53 |
March | 0.00 | 9236.47 | 06-MAR-15:50 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 834.90 | 26-MAR-16:00 | 77046.35 | 14-MAR-15:50 |
April | 0.00 | 8879.33 | 04-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35913.62 | 23-APR-16:00 | 53577.22 | 26-APR-15:00 |
May | 0.00 | 8879.33 | 06-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24728.04 | 10-MAY-15:00 | 24105.27 | 20-MAY-07:10 |
June | 0.00 | 8522.19 | 09-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17901.75 | 29-JUN-16:00 | 31990.55 | 09-JUN-09:00 |
July | 0.00 | 8522.19 | 05-JUL-09:30 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10872.46 | 15-JUL-14:00 | 36568.24 | 03-JUL-10:55 |
August | 0.00 | 8879.33 | 15-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9555.35 | 08-AUG-16:00 | 50594.16 | 17-AUG-14:00 |
September | 0.00 | 8879.33 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7267.70 | 30-SEP-15:00 | 29616.32 | 20-SEP-07:10 |
October | 0.00 | 9236.47 | 17-OCT-14:20 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21151.57 | 19-OCT-15:00 | 34718.04 | 05-OCT-08:00 |
November | 0.00 | 9236.47 | 02-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11049.73 | 01-NOV-14:00 | 64859.34 | 25-NOV-11:00 |
December | 0.00 | 9236.47 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 135310.85 | 18-DEC-15:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 8522.19 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24105.27 | ||||
Maximum of Months | 0.00 | 9236.47 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 35913.62 | 150291.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3106.90 | 21-JAN-08:05 | 2637.00 | 4628.19 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.87 |
February | 3160.01 | 11-FEB-08:05 | 2637.00 | 4584.83 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.37 |
March | 3419.79 | 11-MAR-07:05 | 1107.54 | 4976.81 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 569.37 |
April | 2157.75 | 06-APR-07:05 | 2637.00 | 4427.42 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1800.64 |
May | 12600.47 | 27-MAY-07:03 | 2637.00 | 4158.57 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.53 |
June | 10984.49 | 29-JUN-06:03 | 553.77 | 2277.08 | 3825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 988.08 |
July | 14566.46 | 08-JUL-07:02 | 3296.25 | 5675.94 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.25 |
August | 14012.23 | 05-AUG-07:02 | 3296.25 | 5332.32 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.34 |
September | 13636.80 | 02-SEP-07:02 | 3296.25 | 5544.98 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.65 |
October | 2212.76 | 25-OCT-07:05 | 2637.00 | 4615.22 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1299.34 |
November | 2410.73 | 10-NOV-08:05 | 2637.00 | 4537.06 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2387.35 |
December | 2807.48 | 09-DEC-08:05 | 2637.00 | 4692.88 | 7650.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 770.89 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2157.75 | 553.77 | 2277.08 | 3825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.65 | |
Maximum of Months | 14566.46 | 3296.25 | 5675.94 | 9562.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2387.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 5588.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10660.90 |
February | 3737.61 | 08-FEB-14:00 | 0.00 | 7916.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 893.57 |
March | 6377.96 | 10-MAR-13:25 | 0.00 | 15833.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1774.09 |
April | 6099.75 | 05-APR-13:55 | 0.00 | 15833.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3458.67 |
May | 5327.22 | 20-MAY-08:20 | 0.00 | 7916.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2891.98 |
June | 25725.59 | 30-JUN-20:12 | 0.00 | 5588.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 632.05 |
July | 28517.25 | 02-JUL-14:51 | 0.00 | 6519.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20465.51 | 09-AUG-17:50 | 0.00 | 1862.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.67 | 0.00 |
September | 7477.78 | 06-SEP-07:03 | 0.00 | 27942.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.96 |
October | 7749.29 | 25-OCT-07:03 | 0.00 | 27942.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3508.74 | 16-NOV-11:30 | 0.00 | 7916.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1740.41 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 3725.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9500.85 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 1862.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28517.25 | 0.00 | 27942.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.67 | 10660.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 6519.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38069.61 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 6519.86 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60670.81 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 3259.93 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16079.64 |
April | 0.00 | 01-APR-00:10 | 0.00 | 1086.64 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11246.33 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 1086.64 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2605.84 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 1086.64 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7327.13 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 1086.64 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4741.76 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 1086.64 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8346.65 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 1086.64 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4268.72 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 1086.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5890.05 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 1086.64 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11237.98 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 4346.58 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31448.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 1086.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2605.84 | |
Maximum of Months | 0.00 | 0.00 | 6519.86 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60670.81 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.461922E+11 | 35912.38 | 06-JAN-08:09 | 0.352495E+12 | 279620.25 | 04-JAN-17:10 |
February | 0.411592E+11 | 33699.21 | 27-FEB-15:50 | 0.264656E+12 | 268264.44 | 13-FEB-08:09 |
March | 0.457632E+11 | 33695.93 | 06-MAR-15:00 | 0.181991E+12 | 226140.69 | 15-MAR-05:10 |
April | 0.412649E+11 | 32897.75 | 04-APR-14:50 | 0.616883E+11 | 133600.91 | 04-APR-16:00 |
May | 0.413567E+11 | 34116.77 | 25-MAY-14:50 | 0.194497E+10 | 35441.04 | 01-MAY-05:10 |
June | 0.416346E+11 | 40958.52 | 30-JUN-14:00 | 18245664.70 | 4857.65 | 02-JUN-07:10 |
July | 0.421528E+11 | 39126.45 | 15-JUL-14:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.439534E+11 | 37588.11 | 08-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.412974E+11 | 35631.30 | 01-SEP-14:50 | 0.565687E+09 | 11831.34 | 29-SEP-06:10 |
October | 0.430153E+11 | 32849.97 | 30-OCT-08:09 | 0.203178E+11 | 82910.44 | 30-OCT-07:10 |
November | 0.434755E+11 | 35863.13 | 30-NOV-16:30 | 0.144160E+12 | 181803.21 | 25-NOV-08:00 |
December | 0.463536E+11 | 35910.53 | 30-DEC-08:09 | 0.332745E+12 | 279620.25 | 18-DEC-17:10 |
Annual Sum or Average | 0.517619E+12 | 0.136058E+13 | ||||
Minimum of Months | 0.411592E+11 | 32849.97 | 0.00 | 0.00 | ||
Maximum of Months | 0.463536E+11 | 40958.52 | 0.352495E+12 | 279620.25 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.203738E+11 | 0.762554E+10 | 0.115358E+11 | 0.00 | 0.427205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238496E+10 | 0.00 |
February | 0.184612E+11 | 0.617755E+10 | 0.105871E+11 | 0.00 | 0.374238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219091E+10 | 0.00 |
March | 0.211330E+11 | 0.587579E+10 | 0.123357E+11 | 0.00 | 0.393848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248024E+10 | 0.00 |
April | 0.196808E+11 | 0.471703E+10 | 0.114862E+11 | 0.00 | 0.305582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232498E+10 | 0.00 |
May | 0.202139E+11 | 0.407649E+10 | 0.119357E+11 | 0.00 | 0.254231E+10 | 0.00 | 0.00 | 0.237671E+09 | 0.00 | 0.00 | 0.00 | 0.235058E+10 | 0.00 |
June | 0.199875E+11 | 0.353707E+10 | 0.118862E+11 | 0.00 | 0.253928E+10 | 0.00 | 0.00 | 0.144343E+10 | 0.00 | 0.00 | 0.00 | 0.224123E+10 | 0.00 |
July | 0.196469E+11 | 0.382426E+10 | 0.115358E+11 | 0.00 | 0.246754E+10 | 0.00 | 0.00 | 0.247516E+10 | 0.00 | 0.00 | 0.00 | 0.220318E+10 | 0.00 |
August | 0.208186E+11 | 0.448891E+10 | 0.123357E+11 | 0.00 | 0.262169E+10 | 0.00 | 0.00 | 0.144719E+10 | 0.00 | 0.00 | 0.00 | 0.224129E+10 | 0.00 |
September | 0.197031E+11 | 0.526194E+10 | 0.114862E+11 | 0.00 | 0.242666E+10 | 0.00 | 0.00 | 0.277066E+09 | 0.00 | 0.00 | 0.00 | 0.214242E+10 | 0.00 |
October | 0.200969E+11 | 0.644188E+10 | 0.115358E+11 | 0.00 | 0.271350E+10 | 0.00 | 0.00 | 36260.14 | 0.00 | 0.00 | 0.00 | 0.222715E+10 | 0.00 |
November | 0.195515E+11 | 0.711462E+10 | 0.110862E+11 | 0.00 | 0.352295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220013E+10 | 0.00 |
December | 0.204035E+11 | 0.785864E+10 | 0.115358E+11 | 0.00 | 0.421943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233628E+10 | 0.00 |
Annual Sum or Average | 0.240071E+12 | 0.669997E+11 | 0.139282E+12 | 0.380621E+11 | 0.00 | 0.588054E+10 | 0.273234E+11 | ||||||
Minimum of Months | 0.184612E+11 | 0.353707E+10 | 0.105871E+11 | 0.00 | 0.242666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214242E+10 | 0.00 |
Maximum of Months | 0.211330E+11 | 0.785864E+10 | 0.123357E+11 | 0.00 | 0.427205E+10 | 0.00 | 0.00 | 0.247516E+10 | 0.00 | 0.00 | 0.00 | 0.248024E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.352495E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.264656E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.181991E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.616883E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.194497E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 18245664.70 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.565687E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.203178E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.144160E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.332745E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136058E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.352495E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 18308.07 | 11-JAN-15:00 | 5045.44 | 01-JAN-06:10 | 10112.62 | 02-JAN-08:09 | 0.00 | 2769.42 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 18269.18 | 10-FEB-09:09 | 5045.44 | 01-FEB-06:10 | 10112.62 | 01-FEB-08:09 | 0.00 | 2769.42 | 01-FEB-07:19 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 18269.01 | 17-MAR-08:09 | 5045.44 | 01-MAR-06:10 | 10112.62 | 01-MAR-08:09 | 0.00 | 2769.42 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 17899.95 | 22-APR-08:09 | 5045.44 | 01-APR-05:10 | 10112.62 | 01-APR-07:10 | 0.00 | 2769.42 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 17887.83 | 06-MAY-08:09 | 5045.44 | 01-MAY-19:30 | 10112.62 | 01-MAY-07:10 | 0.00 | 2769.42 | 02-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 17558.78 | 10-JUN-08:09 | 5045.44 | 01-JUN-19:00 | 10112.62 | 01-JUN-07:10 | 0.00 | 2451.17 | 01-JUN-07:19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 17550.59 | 22-JUL-08:30 | 5045.44 | 01-JUL-20:19 | 10112.62 | 01-JUL-07:10 | 0.00 | 2451.17 | 01-JUL-10:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 17934.48 | 31-AUG-08:09 | 5045.44 | 01-AUG-19:49 | 10112.62 | 01-AUG-07:10 | 0.00 | 2451.17 | 01-AUG-08:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 17925.62 | 19-SEP-08:09 | 5045.44 | 01-SEP-05:10 | 10112.62 | 01-SEP-07:10 | 0.00 | 2451.17 | 01-SEP-09:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 18298.23 | 26-OCT-08:09 | 5045.44 | 01-OCT-05:10 | 10112.62 | 02-OCT-07:10 | 0.00 | 2769.42 | 12-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 18318.62 | 15-NOV-15:00 | 5045.44 | 01-NOV-05:10 | 10112.62 | 01-NOV-07:10 | 0.00 | 2769.42 | 02-NOV-06:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 18316.60 | 13-DEC-15:00 | 5045.44 | 01-DEC-06:10 | 10112.62 | 01-DEC-08:09 | 0.00 | 2769.42 | 01-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 17550.59 | 5045.44 | 10112.62 | 0.00 | 2451.17 | 0.00 | 0.00 | |||||
Maximum of Months | 18318.62 | 5045.44 | 10112.62 | 0.00 | 2769.42 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 3060.86 | 31-JAN-12:30 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 3095.27 | 25-FEB-12:09 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 3094.25 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 3029.19 | 01-APR-11:30 | 0.00 |
May | 2540.17 | 25-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2868.48 | 02-MAY-11:00 | 0.00 |
June | 10977.32 | 29-JUN-16:10 | 0.00 | 0.00 | 0.00 | 2640.29 | 01-JUN-11:30 | 0.00 |
July | 7812.72 | 15-JUL-15:09 | 0.00 | 0.00 | 0.00 | 2363.87 | 06-JUL-11:20 | 0.00 |
August | 6590.14 | 08-AUG-15:50 | 0.00 | 0.00 | 0.00 | 2207.23 | 02-AUG-11:09 | 0.00 |
September | 3872.13 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 | 2256.08 | 30-SEP-11:39 | 0.00 |
October | 25.13 | 21-OCT-15:00 | 0.00 | 0.00 | 0.00 | 2473.78 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2706.05 | 29-NOV-12:09 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2922.37 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2207.23 | 0.00 | ||
Maximum of Months | 10977.32 | 0.00 | 0.00 | 0.00 | 3095.27 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 35912.38 | 06-JAN-08:09 | 16310.76 | 10112.62 | 5045.44 | 0.00 | 2769.42 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 33699.21 | 27-FEB-15:50 | 18168.37 | 10112.62 | 0.00 | 0.00 | 2769.42 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33695.93 | 06-MAR-15:00 | 18168.37 | 10112.62 | 0.00 | 0.00 | 2769.42 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32897.75 | 04-APR-14:50 | 17454.09 | 10112.62 | 0.00 | 0.00 | 2769.42 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34116.77 | 25-MAY-14:50 | 17454.09 | 10112.62 | 0.00 | 0.00 | 2451.17 | 0.00 | 0.00 | 2259.18 | 0.00 |
June | 40958.52 | 30-JUN-14:00 | 17096.94 | 10112.62 | 0.00 | 0.00 | 2451.17 | 0.00 | 0.00 | 9486.20 | 0.00 |
July | 39126.45 | 15-JUL-14:30 | 17096.94 | 10112.62 | 0.00 | 0.00 | 2451.17 | 0.00 | 0.00 | 7662.71 | 0.00 |
August | 37588.11 | 08-AUG-14:00 | 17096.94 | 10112.62 | 0.00 | 0.00 | 2451.17 | 0.00 | 0.00 | 6134.09 | 0.00 |
September | 35631.30 | 01-SEP-14:50 | 17454.09 | 10112.62 | 0.00 | 0.00 | 2451.17 | 0.00 | 0.00 | 3822.49 | 0.00 |
October | 32849.97 | 30-OCT-08:09 | 18276.27 | 10112.62 | 0.00 | 0.00 | 2769.42 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 35863.13 | 30-NOV-16:30 | 16310.76 | 10112.62 | 5045.44 | 0.00 | 2769.42 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 35910.53 | 30-DEC-08:09 | 16310.76 | 10112.62 | 5045.44 | 0.00 | 2769.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 32849.97 | 16310.76 | 10112.62 | 0.00 | 0.00 | 2451.17 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40958.52 | 18276.27 | 10112.62 | 5045.44 | 0.00 | 2769.42 | 0.00 | 0.00 | 9486.20 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 279620.25 | 04-JAN-17:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 268264.44 | 13-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 226140.69 | 15-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 133600.91 | 04-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 35441.04 | 01-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 4857.65 | 02-JUN-07:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 11831.34 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 82910.44 | 30-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 181803.21 | 25-NOV-08:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 279620.25 | 18-DEC-17:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 279620.25 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 45.33 | 16.85 | 29.17 | 17.90 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21.50 | 17.02 | 16.50 | 17.63 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12.83 | 17.35 | 11.00 | 17.74 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2.33 | 17.00 | 2.00 | 17.33 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.50 | 17.15 | 0.50 | 17.15 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.17 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 17.08 | 0.33 | 17.08 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5.17 | 16.49 | 3.33 | 17.32 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 29.67 | 17.19 | 20.17 | 18.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.67 | 17.01 | 83.00 | 17.86 | 0.17 | 24.48 | 0.17 | 24.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.33 | 17.35 | 29.17 | 18.24 | 0.17 | 24.48 | 0.17 | 24.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 119.83 | 14.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 106.00 | 14.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 95.67 | 14.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 46.83 | 14.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.83 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.28 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10.17 | 14.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 85.17 | 14.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 121.00 | 14.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 585.50 | 14.33 | 0.00 | 1.50 | 27.28 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.00 | 14.98 | 0.00 | 0.00 | 1.50 | 27.28 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 47.67 | 8.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7.50 | 8.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 30.33 | 8.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85.50 | 8.41 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.67 | 8.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.51 | 300.00 | 20.51 | 300.00 | 20.51 |
February | 276.00 | 20.61 | 276.00 | 20.61 | 276.00 | 20.61 |
March | 324.00 | 20.68 | 324.00 | 20.68 | 324.00 | 20.68 |
April | 300.00 | 20.78 | 295.00 | 20.75 | 295.00 | 20.75 |
May | 277.17 | 22.10 | 128.50 | 20.96 | 118.17 | 20.69 |
June | 196.17 | 23.48 | 107.67 | 24.08 | 17.00 | 24.51 |
July | 14.67 | 24.95 | 271.83 | 24.16 | 11.83 | 25.40 |
August | 45.33 | 23.55 | 232.67 | 24.10 | 4.83 | 25.12 |
September | 265.50 | 22.54 | 72.17 | 21.72 | 51.50 | 20.78 |
October | 300.00 | 20.87 | 270.50 | 20.71 | 270.50 | 20.71 |
November | 288.00 | 20.72 | 286.67 | 20.72 | 286.67 | 20.72 |
December | 300.00 | 20.61 | 300.00 | 20.61 | 300.00 | 20.61 |
Annual Sum or Average | 2886.83 | 21.25 | 2865.00 | 21.44 | 2255.50 | 20.72 |
Minimum of Months | 14.67 | 20.51 | 72.17 | 20.51 | 4.83 | 20.51 |
Maximum of Months | 324.00 | 24.95 | 324.00 | 24.16 | 324.00 | 25.40 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | ||
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.107632E+10 | 0.227608E+09 | 96.31 | 0.968700E+09 | 0.107619E+09 | 0.00 | 1.00 | 27-MAY-07:03 | 0.00 | 01-MAY-00:10 | 15923.28 | 27-MAY-07:03 | 13397.67 | 27-MAY-07:03 | 2525.62 | 27-MAY-07:03 | 3186.52 | 27-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.379914E+10 | 0.792493E+09 | 231.09 | 0.306812E+10 | 0.731022E+09 | 0.00 | 1.00 | 24-JUN-07:02 | 0.00 | 01-JUN-00:10 | 18345.40 | 30-JUN-06:02 | 12431.97 | 29-JUN-06:03 | 7408.58 | 30-JUN-06:05 | 3676.20 | 29-JUN-16:40 | 0.00 | 01-JUN-00:10 |
July | 0.632557E+10 | 0.126834E+10 | 255.75 | 0.514193E+10 | 0.118364E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:10 | 18164.71 | 05-JUL-06:03 | 14766.93 | 08-JUL-07:02 | 7847.20 | 05-JUL-07:02 | 3520.67 | 05-JUL-06:03 | 0.00 | 01-JUL-00:10 |
August | 0.517991E+10 | 0.104053E+10 | 263.35 | 0.416723E+10 | 0.101268E+10 | 0.00 | 1.00 | 05-AUG-07:02 | 0.00 | 01-AUG-00:10 | 17383.28 | 09-AUG-07:03 | 14470.19 | 05-AUG-07:02 | 6506.13 | 09-AUG-07:03 | 3415.33 | 09-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.115953E+10 | 0.240336E+09 | 119.22 | 0.105360E+10 | 0.105928E+09 | 0.00 | 1.00 | 02-SEP-07:02 | 0.00 | 01-SEP-00:10 | 15638.91 | 02-SEP-07:02 | 13771.40 | 02-SEP-07:02 | 2058.16 | 02-SEP-07:04 | 3136.97 | 02-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 161973.05 | 36260.14 | 0.50 | 161973.05 | 0.00 | 0.00 | 0.02 | 21-OCT-16:00 | 0.00 | 01-OCT-00:10 | 112.30 | 21-OCT-16:00 | 112.30 | 21-OCT-16:00 | 0.00 | 21-OCT-16:00 | 25.13 | 21-OCT-16:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.175406E+11 | 0.356934E+10 | 966.22 | 0.143997E+11 | 0.314089E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.632557E+10 | 0.126834E+10 | 263.35 | 0.514193E+10 | 0.118364E+10 | 0.00 | 1.00 | 0.00 | 18345.40 | 14766.93 | 7847.20 | 3676.20 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 40186542.75 | 10063051.94 | 3.67 | 30495360.13 | 9691182.62 | 0.00 | 0.26 | 25-MAY-16:00 | 0.00 | 01-MAY-00:10 | 4209.76 | 25-MAY-16:00 | 3217.29 | 25-MAY-16:00 | 992.47 | 25-MAY-16:00 | 1051.46 | 25-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.281126E+10 | 0.650935E+09 | 61.00 | 0.190190E+10 | 0.909364E+09 | 0.00 | 1.00 | 28-JUN-17:12 | 0.00 | 01-JUN-00:10 | 36318.19 | 28-JUN-19:08 | 24818.36 | 28-JUN-17:12 | 13825.99 | 28-JUN-19:08 | 8455.34 | 29-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 0.538320E+10 | 0.120682E+10 | 164.24 | 0.362028E+10 | 0.176292E+10 | 0.00 | 1.00 | 02-JUL-14:51 | 0.00 | 01-JUL-00:10 | 39391.39 | 23-JUL-09:23 | 27259.00 | 24-JUL-17:10 | 20687.77 | 23-JUL-09:23 | 8425.31 | 23-JUL-10:20 | 0.00 | 01-JUL-00:10 |
August | 0.179514E+10 | 0.406655E+09 | 81.17 | 0.118506E+10 | 0.610079E+09 | 0.00 | 1.00 | 09-AUG-17:50 | 0.00 | 01-AUG-00:10 | 36511.51 | 09-AUG-17:50 | 22632.20 | 09-AUG-17:50 | 13879.31 | 09-AUG-17:50 | 8034.73 | 09-AUG-17:50 | 0.00 | 01-AUG-00:10 |
September | 0.160925E+09 | 36729404.18 | 7.67 | 0.118799E+09 | 42126176.44 | 0.00 | 0.59 | 01-SEP-15:00 | 0.00 | 01-SEP-00:10 | 10087.75 | 01-SEP-15:00 | 7887.27 | 01-SEP-15:00 | 2415.99 | 01-SEP-14:00 | 2290.36 | 01-SEP-15:00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.101907E+11 | 0.231120E+10 | 317.74 | 0.685653E+10 | 0.333418E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.538320E+10 | 0.120682E+10 | 164.24 | 0.362028E+10 | 0.176292E+10 | 0.00 | 1.00 | 0.00 | 39391.39 | 27259.00 | 20687.77 | 8455.34 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.38 | 31.44 | 42.94 | 26.99 | 212.70 | 0.00 | 0.00 | 744.00 |
February | 120.13 | 54.95 | 65.18 | 70.86 | 164.92 | 0.00 | 0.00 | 672.00 |
March | 157.83 | 80.84 | 76.99 | 118.33 | 124.08 | 0.00 | 0.00 | 744.00 |
April | 201.03 | 101.68 | 99.35 | 185.47 | 70.26 | 0.00 | 0.00 | 720.00 |
May | 247.47 | 118.04 | 129.43 | 259.79 | 41.30 | 0.00 | 0.00 | 744.00 |
June | 238.53 | 103.05 | 135.49 | 255.37 | 33.39 | 0.00 | 0.00 | 720.00 |
July | 255.15 | 118.77 | 136.38 | 274.03 | 37.92 | 0.00 | 0.00 | 744.00 |
August | 208.99 | 94.53 | 114.45 | 217.98 | 42.47 | 0.00 | 0.00 | 744.00 |
September | 163.70 | 73.32 | 90.37 | 157.06 | 56.11 | 0.00 | 0.00 | 720.00 |
October | 103.69 | 41.67 | 62.02 | 81.35 | 73.75 | 0.00 | 0.00 | 744.00 |
November | 63.34 | 21.64 | 41.70 | 29.39 | 118.61 | 0.00 | 0.00 | 720.00 |
December | 55.97 | 19.54 | 36.43 | 14.03 | 204.99 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 157.72 | 71.72 | 86.00 | 141.29 | 98.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 55.97 | 19.54 | 36.43 | 14.03 | 33.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 255.15 | 118.77 | 136.38 | 274.03 | 212.70 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.38 | 31.44 | 42.94 | 26.99 | 212.70 | 0.00 | 0.00 | 744.00 |
February | 120.13 | 54.95 | 65.18 | 70.86 | 164.92 | 0.00 | 0.00 | 672.00 |
March | 157.83 | 80.84 | 76.99 | 118.33 | 124.08 | 0.00 | 0.00 | 744.00 |
April | 201.03 | 101.68 | 99.35 | 185.47 | 70.26 | 0.00 | 0.00 | 720.00 |
May | 247.47 | 118.04 | 129.43 | 259.79 | 41.30 | 0.00 | 0.00 | 744.00 |
June | 238.53 | 103.05 | 135.49 | 255.37 | 33.39 | 0.00 | 0.00 | 720.00 |
July | 255.15 | 118.77 | 136.38 | 274.03 | 37.92 | 0.00 | 0.00 | 744.00 |
August | 208.99 | 94.53 | 114.45 | 217.98 | 42.47 | 0.00 | 0.00 | 744.00 |
September | 163.70 | 73.32 | 90.37 | 157.06 | 56.11 | 0.00 | 0.00 | 720.00 |
October | 103.69 | 41.67 | 62.02 | 81.35 | 73.75 | 0.00 | 0.00 | 744.00 |
November | 63.34 | 21.64 | 41.70 | 29.39 | 118.61 | 0.00 | 0.00 | 720.00 |
December | 55.97 | 19.54 | 36.43 | 14.03 | 204.99 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 157.72 | 71.72 | 86.00 | 141.29 | 98.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 55.97 | 19.54 | 36.43 | 14.03 | 33.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 255.15 | 118.77 | 136.38 | 274.03 | 212.70 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.35 | 0.00 | 19.35 | 0.31 | 135.29 | 0.00 | 0.00 | 744.00 |
February | 29.72 | 0.00 | 29.72 | 2.96 | 104.12 | 0.00 | 0.00 | 672.00 |
March | 36.57 | 0.00 | 36.57 | 7.25 | 76.91 | 0.00 | 0.00 | 744.00 |
April | 48.05 | 0.48 | 47.57 | 25.70 | 41.67 | 0.00 | 0.00 | 720.00 |
May | 67.54 | 3.70 | 63.84 | 54.71 | 22.94 | 0.00 | 0.00 | 744.00 |
June | 75.32 | 8.35 | 66.97 | 66.90 | 18.42 | 0.00 | 0.00 | 720.00 |
July | 71.87 | 6.16 | 65.71 | 63.18 | 20.89 | 0.00 | 0.00 | 744.00 |
August | 54.80 | 1.13 | 53.67 | 46.05 | 24.37 | 0.00 | 0.00 | 744.00 |
September | 42.58 | 0.03 | 42.55 | 29.25 | 33.31 | 0.00 | 0.00 | 720.00 |
October | 29.53 | 0.00 | 29.53 | 12.76 | 44.33 | 0.00 | 0.00 | 744.00 |
November | 19.55 | 0.00 | 19.55 | 2.18 | 73.49 | 0.00 | 0.00 | 720.00 |
December | 16.39 | 0.00 | 16.39 | 0.05 | 129.12 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 42.67 | 1.66 | 41.01 | 26.08 | 60.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 16.39 | 0.00 | 16.39 | 0.05 | 18.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 75.32 | 8.35 | 66.97 | 66.90 | 135.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.35 | 0.00 | 19.35 | 0.31 | 135.29 | 0.00 | 0.00 | 744.00 |
February | 29.72 | 0.00 | 29.72 | 2.96 | 104.12 | 0.00 | 0.00 | 672.00 |
March | 36.57 | 0.00 | 36.57 | 7.25 | 76.91 | 0.00 | 0.00 | 744.00 |
April | 48.05 | 0.48 | 47.56 | 25.70 | 41.67 | 0.00 | 0.00 | 720.00 |
May | 67.54 | 3.70 | 63.84 | 54.71 | 22.94 | 0.00 | 0.00 | 744.00 |
June | 75.32 | 8.35 | 66.97 | 66.90 | 18.42 | 0.00 | 0.00 | 720.00 |
July | 71.87 | 6.16 | 65.71 | 63.18 | 20.89 | 0.00 | 0.00 | 744.00 |
August | 54.80 | 1.13 | 53.67 | 46.05 | 24.37 | 0.00 | 0.00 | 744.00 |
September | 42.58 | 0.03 | 42.54 | 29.24 | 33.31 | 0.00 | 0.00 | 720.00 |
October | 29.53 | 0.00 | 29.53 | 12.76 | 44.33 | 0.00 | 0.00 | 744.00 |
November | 19.55 | 0.00 | 19.55 | 2.18 | 73.49 | 0.00 | 0.00 | 720.00 |
December | 16.39 | 0.00 | 16.39 | 0.05 | 129.12 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 42.67 | 1.66 | 41.01 | 26.08 | 60.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 16.39 | 0.00 | 16.39 | 0.05 | 18.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 75.32 | 8.35 | 66.97 | 66.90 | 135.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.07 | 10.86 | 20.22 | 10.27 | 109.07 | 0.00 | 0.00 | 744.00 |
February | 55.07 | 25.35 | 29.72 | 41.19 | 84.89 | 0.00 | 0.00 | 672.00 |
March | 79.36 | 44.90 | 34.46 | 75.31 | 60.15 | 0.00 | 0.00 | 744.00 |
April | 115.66 | 72.85 | 42.80 | 133.85 | 33.62 | 2.67 | 0.00 | 720.00 |
May | 141.80 | 79.62 | 62.18 | 177.09 | 21.43 | 0.00 | 0.00 | 744.00 |
June | 149.61 | 86.16 | 63.44 | 185.05 | 20.78 | 17.33 | 0.00 | 720.00 |
July | 152.94 | 91.13 | 61.81 | 182.76 | 28.57 | 3.00 | 0.00 | 744.00 |
August | 121.90 | 68.77 | 53.13 | 144.06 | 27.88 | 1.33 | 0.00 | 744.00 |
September | 88.60 | 45.88 | 42.71 | 100.10 | 32.39 | 4.50 | 0.00 | 720.00 |
October | 50.89 | 19.44 | 31.45 | 53.51 | 33.93 | 13.83 | 0.00 | 744.00 |
November | 30.39 | 9.31 | 21.08 | 21.93 | 54.82 | 12.83 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 5.06 | 102.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.94 | 46.80 | 40.14 | 94.44 | 50.73 | 55.50 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 5.06 | 20.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.94 | 91.13 | 63.44 | 185.05 | 109.07 | 17.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.07 | 10.86 | 20.22 | 10.27 | 109.07 | 0.00 | 0.00 | 744.00 |
February | 55.07 | 25.35 | 29.72 | 41.19 | 84.89 | 0.00 | 0.00 | 672.00 |
March | 79.36 | 44.90 | 34.46 | 75.31 | 60.15 | 0.00 | 0.00 | 744.00 |
April | 115.66 | 72.85 | 42.80 | 133.85 | 33.62 | 2.67 | 0.00 | 720.00 |
May | 141.80 | 79.62 | 62.18 | 177.09 | 21.43 | 0.00 | 0.00 | 744.00 |
June | 149.61 | 86.16 | 63.44 | 185.05 | 20.78 | 17.33 | 0.00 | 720.00 |
July | 152.94 | 91.13 | 61.81 | 182.76 | 28.57 | 3.00 | 0.00 | 744.00 |
August | 121.90 | 68.77 | 53.13 | 144.06 | 27.88 | 1.33 | 0.00 | 744.00 |
September | 88.60 | 45.88 | 42.71 | 100.10 | 32.39 | 4.50 | 0.00 | 720.00 |
October | 50.89 | 19.44 | 31.45 | 53.51 | 33.93 | 13.83 | 0.00 | 744.00 |
November | 30.39 | 9.31 | 21.08 | 21.93 | 54.82 | 12.83 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 5.06 | 102.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.94 | 46.80 | 40.14 | 94.44 | 50.73 | 55.50 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 5.06 | 20.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.94 | 91.13 | 63.44 | 185.05 | 109.07 | 17.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.07 | 10.86 | 20.22 | 10.27 | 109.07 | 0.00 | 0.00 | 744.00 |
February | 55.07 | 25.35 | 29.72 | 41.19 | 84.89 | 0.00 | 0.00 | 672.00 |
March | 79.36 | 44.90 | 34.46 | 75.31 | 60.15 | 0.00 | 0.00 | 744.00 |
April | 115.66 | 72.85 | 42.80 | 133.85 | 33.62 | 2.67 | 0.00 | 720.00 |
May | 141.80 | 79.62 | 62.18 | 177.09 | 21.43 | 0.00 | 0.00 | 744.00 |
June | 149.61 | 86.16 | 63.44 | 185.05 | 20.78 | 17.33 | 0.00 | 720.00 |
July | 152.94 | 91.13 | 61.81 | 182.76 | 28.57 | 3.00 | 0.00 | 744.00 |
August | 121.90 | 68.77 | 53.13 | 144.06 | 27.88 | 1.33 | 0.00 | 744.00 |
September | 88.60 | 45.88 | 42.71 | 100.10 | 32.39 | 4.50 | 0.00 | 720.00 |
October | 50.89 | 19.44 | 31.45 | 53.51 | 33.93 | 13.83 | 0.00 | 744.00 |
November | 30.39 | 9.31 | 21.08 | 21.93 | 54.82 | 12.83 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 5.06 | 102.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.94 | 46.80 | 40.14 | 94.44 | 50.73 | 55.50 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 5.06 | 20.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.94 | 91.13 | 63.44 | 185.05 | 109.07 | 17.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.07 | 10.86 | 20.22 | 10.27 | 109.07 | 0.00 | 0.00 | 744.00 |
February | 55.07 | 25.35 | 29.72 | 41.19 | 84.89 | 0.00 | 0.00 | 672.00 |
March | 79.36 | 44.90 | 34.46 | 75.31 | 60.15 | 0.00 | 0.00 | 744.00 |
April | 115.66 | 72.85 | 42.80 | 133.85 | 33.62 | 2.67 | 0.00 | 720.00 |
May | 141.80 | 79.62 | 62.18 | 177.09 | 21.43 | 0.00 | 0.00 | 744.00 |
June | 149.61 | 86.16 | 63.44 | 185.05 | 20.78 | 17.33 | 0.00 | 720.00 |
July | 152.94 | 91.13 | 61.81 | 182.76 | 28.57 | 3.00 | 0.00 | 744.00 |
August | 121.90 | 68.77 | 53.13 | 144.06 | 27.88 | 1.33 | 0.00 | 744.00 |
September | 88.60 | 45.88 | 42.71 | 100.10 | 32.39 | 4.50 | 0.00 | 720.00 |
October | 50.89 | 19.44 | 31.45 | 53.51 | 33.93 | 13.83 | 0.00 | 744.00 |
November | 30.39 | 9.31 | 21.08 | 21.93 | 54.82 | 12.83 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 5.06 | 102.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.94 | 46.80 | 40.14 | 94.44 | 50.73 | 55.50 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 5.06 | 20.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.94 | 91.13 | 63.44 | 185.05 | 109.07 | 17.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.07 | 10.86 | 20.22 | 10.27 | 109.07 | 0.00 | 0.00 | 744.00 |
February | 55.07 | 25.35 | 29.72 | 41.19 | 84.89 | 0.00 | 0.00 | 672.00 |
March | 79.36 | 44.90 | 34.46 | 75.31 | 60.15 | 0.00 | 0.00 | 744.00 |
April | 115.66 | 72.85 | 42.80 | 133.85 | 33.62 | 2.67 | 0.00 | 720.00 |
May | 141.80 | 79.62 | 62.18 | 177.09 | 21.43 | 0.00 | 0.00 | 744.00 |
June | 149.61 | 86.16 | 63.44 | 185.05 | 20.78 | 17.33 | 0.00 | 720.00 |
July | 152.94 | 91.13 | 61.81 | 182.76 | 28.57 | 3.00 | 0.00 | 744.00 |
August | 121.90 | 68.77 | 53.13 | 144.06 | 27.88 | 1.33 | 0.00 | 744.00 |
September | 88.60 | 45.88 | 42.71 | 100.10 | 32.39 | 4.50 | 0.00 | 720.00 |
October | 50.89 | 19.44 | 31.45 | 53.51 | 33.93 | 13.83 | 0.00 | 744.00 |
November | 30.39 | 9.31 | 21.08 | 21.93 | 54.82 | 12.83 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 5.06 | 102.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.94 | 46.80 | 40.14 | 94.44 | 50.73 | 55.50 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 5.06 | 20.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.94 | 91.13 | 63.44 | 185.05 | 109.07 | 17.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.07 | 10.86 | 20.22 | 10.27 | 109.07 | 0.00 | 0.00 | 744.00 |
February | 55.07 | 25.35 | 29.72 | 41.19 | 84.89 | 0.00 | 0.00 | 672.00 |
March | 79.36 | 44.90 | 34.46 | 75.31 | 60.15 | 0.00 | 0.00 | 744.00 |
April | 115.66 | 72.85 | 42.80 | 133.85 | 33.62 | 2.67 | 0.00 | 720.00 |
May | 141.80 | 79.62 | 62.18 | 177.09 | 21.43 | 0.00 | 0.00 | 744.00 |
June | 149.61 | 86.16 | 63.44 | 185.05 | 20.78 | 17.33 | 0.00 | 720.00 |
July | 152.94 | 91.13 | 61.81 | 182.76 | 28.57 | 3.00 | 0.00 | 744.00 |
August | 121.90 | 68.77 | 53.13 | 144.06 | 27.88 | 1.33 | 0.00 | 744.00 |
September | 88.60 | 45.88 | 42.71 | 100.10 | 32.39 | 4.50 | 0.00 | 720.00 |
October | 50.89 | 19.44 | 31.45 | 53.51 | 33.93 | 13.83 | 0.00 | 744.00 |
November | 30.39 | 9.31 | 21.08 | 21.93 | 54.82 | 12.83 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 5.06 | 102.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.94 | 46.80 | 40.14 | 94.44 | 50.73 | 55.50 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 5.06 | 20.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.94 | 91.13 | 63.44 | 185.05 | 109.07 | 17.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.07 | 10.86 | 20.22 | 10.27 | 109.07 | 0.00 | 0.00 | 744.00 |
February | 55.07 | 25.35 | 29.72 | 41.19 | 84.89 | 0.00 | 0.00 | 672.00 |
March | 79.36 | 44.90 | 34.46 | 75.31 | 60.15 | 0.00 | 0.00 | 744.00 |
April | 115.66 | 72.85 | 42.80 | 133.85 | 33.62 | 2.67 | 0.00 | 720.00 |
May | 141.80 | 79.62 | 62.18 | 177.09 | 21.43 | 0.00 | 0.00 | 744.00 |
June | 149.61 | 86.16 | 63.44 | 185.05 | 20.78 | 17.33 | 0.00 | 720.00 |
July | 152.94 | 91.13 | 61.81 | 182.76 | 28.57 | 3.00 | 0.00 | 744.00 |
August | 121.90 | 68.77 | 53.13 | 144.06 | 27.88 | 1.33 | 0.00 | 744.00 |
September | 88.60 | 45.88 | 42.71 | 100.10 | 32.39 | 4.50 | 0.00 | 720.00 |
October | 50.89 | 19.44 | 31.45 | 53.51 | 33.93 | 13.83 | 0.00 | 744.00 |
November | 30.39 | 9.31 | 21.08 | 21.93 | 54.82 | 12.83 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 5.06 | 102.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.94 | 46.80 | 40.14 | 94.44 | 50.73 | 55.50 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 5.06 | 20.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.94 | 91.13 | 63.44 | 185.05 | 109.07 | 17.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.07 | 10.86 | 20.22 | 10.27 | 109.07 | 0.00 | 0.00 | 744.00 |
February | 55.07 | 25.35 | 29.72 | 41.19 | 84.89 | 0.00 | 0.00 | 672.00 |
March | 79.36 | 44.90 | 34.46 | 75.31 | 60.15 | 0.00 | 0.00 | 744.00 |
April | 115.66 | 72.85 | 42.80 | 133.85 | 33.62 | 2.67 | 0.00 | 720.00 |
May | 141.80 | 79.62 | 62.18 | 177.09 | 21.43 | 0.00 | 0.00 | 744.00 |
June | 149.61 | 86.16 | 63.44 | 185.05 | 20.78 | 17.33 | 0.00 | 720.00 |
July | 152.94 | 91.13 | 61.81 | 182.76 | 28.57 | 3.00 | 0.00 | 744.00 |
August | 121.90 | 68.77 | 53.13 | 144.06 | 27.88 | 1.33 | 0.00 | 744.00 |
September | 88.60 | 45.88 | 42.71 | 100.10 | 32.39 | 4.50 | 0.00 | 720.00 |
October | 50.89 | 19.44 | 31.45 | 53.51 | 33.93 | 13.83 | 0.00 | 744.00 |
November | 30.39 | 9.31 | 21.08 | 21.93 | 54.82 | 12.83 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 5.06 | 102.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.94 | 46.80 | 40.14 | 94.44 | 50.73 | 55.50 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 5.06 | 20.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.94 | 91.13 | 63.44 | 185.05 | 109.07 | 17.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.07 | 10.86 | 20.22 | 10.27 | 109.07 | 0.00 | 0.00 | 744.00 |
February | 55.07 | 25.35 | 29.72 | 41.19 | 84.89 | 0.00 | 0.00 | 672.00 |
March | 79.36 | 44.90 | 34.46 | 75.31 | 60.15 | 0.00 | 0.00 | 744.00 |
April | 115.66 | 72.85 | 42.80 | 133.85 | 33.62 | 2.67 | 0.00 | 720.00 |
May | 141.80 | 79.62 | 62.18 | 177.09 | 21.43 | 0.00 | 0.00 | 744.00 |
June | 149.61 | 86.16 | 63.44 | 185.05 | 20.78 | 17.33 | 0.00 | 720.00 |
July | 152.94 | 91.13 | 61.81 | 182.76 | 28.57 | 3.00 | 0.00 | 744.00 |
August | 121.90 | 68.77 | 53.13 | 144.06 | 27.88 | 1.33 | 0.00 | 744.00 |
September | 88.60 | 45.88 | 42.71 | 100.10 | 32.39 | 4.50 | 0.00 | 720.00 |
October | 50.89 | 19.44 | 31.45 | 53.51 | 33.93 | 13.83 | 0.00 | 744.00 |
November | 30.39 | 9.31 | 21.08 | 21.93 | 54.82 | 12.83 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 5.06 | 102.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.94 | 46.80 | 40.14 | 94.44 | 50.73 | 55.50 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 5.06 | 20.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.94 | 91.13 | 63.44 | 185.05 | 109.07 | 17.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.07 | 10.86 | 20.22 | 10.27 | 109.07 | 0.00 | 0.00 | 744.00 |
February | 55.07 | 25.35 | 29.72 | 41.19 | 84.89 | 0.00 | 0.00 | 672.00 |
March | 79.36 | 44.90 | 34.46 | 75.31 | 60.15 | 0.00 | 0.00 | 744.00 |
April | 115.66 | 72.85 | 42.80 | 133.85 | 33.62 | 2.67 | 0.00 | 720.00 |
May | 141.80 | 79.62 | 62.18 | 177.09 | 21.43 | 0.00 | 0.00 | 744.00 |
June | 149.61 | 86.16 | 63.44 | 185.05 | 20.78 | 17.33 | 0.00 | 720.00 |
July | 152.94 | 91.13 | 61.81 | 182.76 | 28.57 | 3.00 | 0.00 | 744.00 |
August | 121.90 | 68.77 | 53.13 | 144.06 | 27.88 | 1.33 | 0.00 | 744.00 |
September | 88.60 | 45.88 | 42.71 | 100.10 | 32.39 | 4.50 | 0.00 | 720.00 |
October | 50.89 | 19.44 | 31.45 | 53.51 | 33.93 | 13.83 | 0.00 | 744.00 |
November | 30.39 | 9.31 | 21.08 | 21.93 | 54.82 | 12.83 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 5.06 | 102.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.94 | 46.80 | 40.14 | 94.44 | 50.73 | 55.50 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 5.06 | 20.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 152.94 | 91.13 | 63.44 | 185.05 | 109.07 | 17.33 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.199220E+09 | 84200599.52 | 0.115020E+09 | 72277695.26 | 0.569684E+09 |
February | 0.290627E+09 | 0.132937E+09 | 0.157690E+09 | 0.171433E+09 | 0.398973E+09 |
March | 0.422721E+09 | 0.216513E+09 | 0.206208E+09 | 0.316943E+09 | 0.332334E+09 |
April | 0.521080E+09 | 0.263555E+09 | 0.257525E+09 | 0.480730E+09 | 0.182106E+09 |
May | 0.662828E+09 | 0.316152E+09 | 0.346677E+09 | 0.695823E+09 | 0.110629E+09 |
June | 0.618278E+09 | 0.267096E+09 | 0.351182E+09 | 0.661932E+09 | 86550021.38 |
July | 0.683388E+09 | 0.318120E+09 | 0.365268E+09 | 0.733950E+09 | 0.101576E+09 |
August | 0.559747E+09 | 0.253202E+09 | 0.306545E+09 | 0.583844E+09 | 0.113759E+09 |
September | 0.424304E+09 | 0.190054E+09 | 0.234250E+09 | 0.407101E+09 | 0.145424E+09 |
October | 0.277717E+09 | 0.111601E+09 | 0.166116E+09 | 0.217880E+09 | 0.197522E+09 |
November | 0.164168E+09 | 56078618.96 | 0.108089E+09 | 76169194.99 | 0.307425E+09 |
December | 0.149911E+09 | 52342065.58 | 97568529.96 | 37569533.89 | 0.549041E+09 |
Annual Sum or Average | 0.497399E+10 | 0.226185E+10 | 0.271214E+10 | 0.445565E+10 | 0.309502E+10 |
Minimum of Months | 0.149911E+09 | 52342065.58 | 97568529.96 | 37569533.89 | 86550021.38 |
Maximum of Months | 0.683388E+09 | 0.318120E+09 | 0.365268E+09 | 0.733950E+09 | 0.569684E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.199220E+09 | 84200599.52 | 0.115020E+09 | 72277695.26 | 0.569684E+09 |
February | 0.290627E+09 | 0.132937E+09 | 0.157690E+09 | 0.171433E+09 | 0.398973E+09 |
March | 0.422721E+09 | 0.216513E+09 | 0.206208E+09 | 0.316943E+09 | 0.332334E+09 |
April | 0.521080E+09 | 0.263555E+09 | 0.257525E+09 | 0.480730E+09 | 0.182106E+09 |
May | 0.662828E+09 | 0.316152E+09 | 0.346677E+09 | 0.695823E+09 | 0.110629E+09 |
June | 0.618278E+09 | 0.267096E+09 | 0.351182E+09 | 0.661932E+09 | 86550021.38 |
July | 0.683388E+09 | 0.318120E+09 | 0.365268E+09 | 0.733950E+09 | 0.101576E+09 |
August | 0.559747E+09 | 0.253202E+09 | 0.306545E+09 | 0.583844E+09 | 0.113759E+09 |
September | 0.424304E+09 | 0.190054E+09 | 0.234250E+09 | 0.407101E+09 | 0.145424E+09 |
October | 0.277717E+09 | 0.111601E+09 | 0.166116E+09 | 0.217880E+09 | 0.197522E+09 |
November | 0.164168E+09 | 56078618.96 | 0.108089E+09 | 76169194.99 | 0.307425E+09 |
December | 0.149911E+09 | 52342065.58 | 97568529.96 | 37569533.89 | 0.549041E+09 |
Annual Sum or Average | 0.497399E+10 | 0.226185E+10 | 0.271214E+10 | 0.445565E+10 | 0.309502E+10 |
Minimum of Months | 0.149911E+09 | 52342065.58 | 97568529.96 | 37569533.89 | 86550021.38 |
Maximum of Months | 0.683388E+09 | 0.318120E+09 | 0.365268E+09 | 0.733950E+09 | 0.569684E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51817551.18 | 0.00 | 51817551.18 | 827142.47 | 0.362349E+09 |
February | 71892988.54 | 0.00 | 71892988.54 | 7167835.60 | 0.251895E+09 |
March | 97955001.62 | 7134.85 | 97947866.77 | 19424130.13 | 0.205998E+09 |
April | 0.124543E+09 | 1251817.08 | 0.123291E+09 | 66626513.63 | 0.108021E+09 |
May | 0.180904E+09 | 9914079.28 | 0.170990E+09 | 0.146530E+09 | 61435052.01 |
June | 0.195234E+09 | 21634798.88 | 0.173599E+09 | 0.173412E+09 | 47748098.72 |
July | 0.192508E+09 | 16509670.17 | 0.175998E+09 | 0.169223E+09 | 55950743.20 |
August | 0.146784E+09 | 3032136.98 | 0.143752E+09 | 0.123347E+09 | 65267882.91 |
September | 0.110360E+09 | 81490.44 | 0.110278E+09 | 75803422.27 | 86348451.43 |
October | 79100186.26 | 0.00 | 79100186.26 | 34177696.10 | 0.118733E+09 |
November | 50684853.21 | 0.00 | 50684853.21 | 5657026.72 | 0.190488E+09 |
December | 43903948.99 | 0.00 | 43903948.99 | 141671.10 | 0.345838E+09 |
Annual Sum or Average | 0.134569E+10 | 52431127.69 | 0.129326E+10 | 0.822338E+09 | 0.190007E+10 |
Minimum of Months | 43903948.99 | 0.00 | 43903948.99 | 141671.10 | 47748098.72 |
Maximum of Months | 0.195234E+09 | 21634798.88 | 0.175998E+09 | 0.173412E+09 | 0.362349E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51815840.28 | 0.00 | 51815840.28 | 826976.01 | 0.362350E+09 |
February | 71890726.48 | 0.00 | 71890726.48 | 7167088.99 | 0.251896E+09 |
March | 97952049.66 | 7134.52 | 97944915.14 | 19422507.60 | 0.205999E+09 |
April | 0.124539E+09 | 1251758.41 | 0.123288E+09 | 66623500.77 | 0.108021E+09 |
May | 0.180899E+09 | 9913614.59 | 0.170985E+09 | 0.146525E+09 | 61434749.13 |
June | 0.195227E+09 | 21633784.83 | 0.173594E+09 | 0.173406E+09 | 47747774.69 |
July | 0.192502E+09 | 16508896.34 | 0.175993E+09 | 0.169217E+09 | 55950345.01 |
August | 0.146779E+09 | 3031994.86 | 0.143747E+09 | 0.123342E+09 | 65267596.88 |
September | 0.110356E+09 | 81486.62 | 0.110275E+09 | 75800133.19 | 86348304.77 |
October | 79097548.24 | 0.00 | 79097548.24 | 34175480.48 | 0.118733E+09 |
November | 50683126.30 | 0.00 | 50683126.30 | 5656397.47 | 0.190489E+09 |
December | 43902451.79 | 0.00 | 43902451.79 | 141616.01 | 0.345839E+09 |
Annual Sum or Average | 0.134564E+10 | 52428670.17 | 0.129322E+10 | 0.822304E+09 | 0.190008E+10 |
Minimum of Months | 43902451.79 | 0.00 | 43902451.79 | 141616.01 | 47747774.69 |
Maximum of Months | 0.195227E+09 | 21633784.83 | 0.175993E+09 | 0.173406E+09 | 0.362350E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83230840.30 | 29084049.09 | 54146791.21 | 27514787.30 | 0.292131E+09 |
February | 0.133218E+09 | 61314697.29 | 71903005.34 | 99653201.12 | 0.205377E+09 |
March | 0.212563E+09 | 0.120270E+09 | 92293560.69 | 0.201698E+09 | 0.161108E+09 |
April | 0.299783E+09 | 0.188836E+09 | 0.110947E+09 | 0.346940E+09 | 87130715.89 |
May | 0.379794E+09 | 0.213258E+09 | 0.166536E+09 | 0.474307E+09 | 57391715.40 |
June | 0.387778E+09 | 0.223332E+09 | 0.164446E+09 | 0.479641E+09 | 53853284.92 |
July | 0.409647E+09 | 0.244085E+09 | 0.165562E+09 | 0.489498E+09 | 76533614.93 |
August | 0.326494E+09 | 0.184193E+09 | 0.142301E+09 | 0.385845E+09 | 74679737.25 |
September | 0.229642E+09 | 0.118926E+09 | 0.110716E+09 | 0.259462E+09 | 83961603.39 |
October | 0.136302E+09 | 52072475.95 | 84229445.37 | 0.143328E+09 | 90886094.28 |
November | 78775603.14 | 24138730.45 | 54636872.69 | 56838999.29 | 0.142101E+09 |
December | 64603296.97 | 16441331.13 | 48161965.84 | 13555688.60 | 0.274826E+09 |
Annual Sum or Average | 0.274183E+10 | 0.147595E+10 | 0.126588E+10 | 0.297828E+10 | 0.159998E+10 |
Minimum of Months | 64603296.97 | 16441331.13 | 48161965.84 | 13555688.60 | 53853284.92 |
Maximum of Months | 0.409647E+09 | 0.244085E+09 | 0.166536E+09 | 0.489498E+09 | 0.292131E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83230840.30 | 29084049.09 | 54146791.21 | 27514787.30 | 0.292131E+09 |
February | 0.133218E+09 | 61314697.29 | 71903005.34 | 99653201.12 | 0.205377E+09 |
March | 0.212563E+09 | 0.120270E+09 | 92293560.69 | 0.201698E+09 | 0.161108E+09 |
April | 0.299783E+09 | 0.188836E+09 | 0.110947E+09 | 0.346940E+09 | 87130715.89 |
May | 0.379794E+09 | 0.213258E+09 | 0.166536E+09 | 0.474307E+09 | 57391715.40 |
June | 0.387778E+09 | 0.223332E+09 | 0.164446E+09 | 0.479641E+09 | 53853284.92 |
July | 0.409647E+09 | 0.244085E+09 | 0.165562E+09 | 0.489498E+09 | 76533614.93 |
August | 0.326494E+09 | 0.184193E+09 | 0.142301E+09 | 0.385845E+09 | 74679737.25 |
September | 0.229642E+09 | 0.118926E+09 | 0.110716E+09 | 0.259462E+09 | 83961603.39 |
October | 0.136302E+09 | 52072475.95 | 84229445.37 | 0.143328E+09 | 90886094.28 |
November | 78775603.14 | 24138730.45 | 54636872.69 | 56838999.29 | 0.142101E+09 |
December | 64603296.97 | 16441331.13 | 48161965.84 | 13555688.60 | 0.274826E+09 |
Annual Sum or Average | 0.274183E+10 | 0.147595E+10 | 0.126588E+10 | 0.297828E+10 | 0.159998E+10 |
Minimum of Months | 64603296.97 | 16441331.13 | 48161965.84 | 13555688.60 | 53853284.92 |
Maximum of Months | 0.409647E+09 | 0.244085E+09 | 0.166536E+09 | 0.489498E+09 | 0.292131E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83230840.30 | 29084049.09 | 54146791.21 | 27514787.30 | 0.292131E+09 |
February | 0.133218E+09 | 61314697.29 | 71903005.34 | 99653201.12 | 0.205377E+09 |
March | 0.212563E+09 | 0.120270E+09 | 92293560.69 | 0.201698E+09 | 0.161108E+09 |
April | 0.299783E+09 | 0.188836E+09 | 0.110947E+09 | 0.346940E+09 | 87130715.89 |
May | 0.379794E+09 | 0.213258E+09 | 0.166536E+09 | 0.474307E+09 | 57391715.40 |
June | 0.387778E+09 | 0.223332E+09 | 0.164446E+09 | 0.479641E+09 | 53853284.92 |
July | 0.409647E+09 | 0.244085E+09 | 0.165562E+09 | 0.489498E+09 | 76533614.93 |
August | 0.326494E+09 | 0.184193E+09 | 0.142301E+09 | 0.385845E+09 | 74679737.25 |
September | 0.229642E+09 | 0.118926E+09 | 0.110716E+09 | 0.259462E+09 | 83961603.39 |
October | 0.136302E+09 | 52072475.95 | 84229445.37 | 0.143328E+09 | 90886094.28 |
November | 78775603.14 | 24138730.45 | 54636872.69 | 56838999.29 | 0.142101E+09 |
December | 64603296.97 | 16441331.13 | 48161965.84 | 13555688.60 | 0.274826E+09 |
Annual Sum or Average | 0.274183E+10 | 0.147595E+10 | 0.126588E+10 | 0.297828E+10 | 0.159998E+10 |
Minimum of Months | 64603296.97 | 16441331.13 | 48161965.84 | 13555688.60 | 53853284.92 |
Maximum of Months | 0.409647E+09 | 0.244085E+09 | 0.166536E+09 | 0.489498E+09 | 0.292131E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83230840.30 | 29084049.09 | 54146791.21 | 27514787.30 | 0.292131E+09 |
February | 0.133218E+09 | 61314697.29 | 71903005.34 | 99653201.12 | 0.205377E+09 |
March | 0.212563E+09 | 0.120270E+09 | 92293560.69 | 0.201698E+09 | 0.161108E+09 |
April | 0.299783E+09 | 0.188836E+09 | 0.110947E+09 | 0.346940E+09 | 87130715.89 |
May | 0.379794E+09 | 0.213258E+09 | 0.166536E+09 | 0.474307E+09 | 57391715.40 |
June | 0.387778E+09 | 0.223332E+09 | 0.164446E+09 | 0.479641E+09 | 53853284.92 |
July | 0.409647E+09 | 0.244085E+09 | 0.165562E+09 | 0.489498E+09 | 76533614.93 |
August | 0.326494E+09 | 0.184193E+09 | 0.142301E+09 | 0.385845E+09 | 74679737.25 |
September | 0.229642E+09 | 0.118926E+09 | 0.110716E+09 | 0.259462E+09 | 83961603.39 |
October | 0.136302E+09 | 52072475.95 | 84229445.37 | 0.143328E+09 | 90886094.28 |
November | 78775603.14 | 24138730.45 | 54636872.69 | 56838999.29 | 0.142101E+09 |
December | 64603296.97 | 16441331.13 | 48161965.84 | 13555688.60 | 0.274826E+09 |
Annual Sum or Average | 0.274183E+10 | 0.147595E+10 | 0.126588E+10 | 0.297828E+10 | 0.159998E+10 |
Minimum of Months | 64603296.97 | 16441331.13 | 48161965.84 | 13555688.60 | 53853284.92 |
Maximum of Months | 0.409647E+09 | 0.244085E+09 | 0.166536E+09 | 0.489498E+09 | 0.292131E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83230840.30 | 29084049.09 | 54146791.21 | 27514787.30 | 0.292131E+09 |
February | 0.133218E+09 | 61314697.29 | 71903005.34 | 99653201.12 | 0.205377E+09 |
March | 0.212563E+09 | 0.120270E+09 | 92293560.69 | 0.201698E+09 | 0.161108E+09 |
April | 0.299783E+09 | 0.188836E+09 | 0.110947E+09 | 0.346940E+09 | 87130715.89 |
May | 0.379794E+09 | 0.213258E+09 | 0.166536E+09 | 0.474307E+09 | 57391715.40 |
June | 0.387778E+09 | 0.223332E+09 | 0.164446E+09 | 0.479641E+09 | 53853284.92 |
July | 0.409647E+09 | 0.244085E+09 | 0.165562E+09 | 0.489498E+09 | 76533614.93 |
August | 0.326494E+09 | 0.184193E+09 | 0.142301E+09 | 0.385845E+09 | 74679737.25 |
September | 0.229642E+09 | 0.118926E+09 | 0.110716E+09 | 0.259462E+09 | 83961603.39 |
October | 0.136302E+09 | 52072475.95 | 84229445.37 | 0.143328E+09 | 90886094.28 |
November | 78775603.14 | 24138730.45 | 54636872.69 | 56838999.29 | 0.142101E+09 |
December | 64603296.97 | 16441331.13 | 48161965.84 | 13555688.60 | 0.274826E+09 |
Annual Sum or Average | 0.274183E+10 | 0.147595E+10 | 0.126588E+10 | 0.297828E+10 | 0.159998E+10 |
Minimum of Months | 64603296.97 | 16441331.13 | 48161965.84 | 13555688.60 | 53853284.92 |
Maximum of Months | 0.409647E+09 | 0.244085E+09 | 0.166536E+09 | 0.489498E+09 | 0.292131E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83230840.30 | 29084049.09 | 54146791.21 | 27514787.30 | 0.292131E+09 |
February | 0.133218E+09 | 61314697.29 | 71903005.34 | 99653201.12 | 0.205377E+09 |
March | 0.212563E+09 | 0.120270E+09 | 92293560.69 | 0.201698E+09 | 0.161108E+09 |
April | 0.299783E+09 | 0.188836E+09 | 0.110947E+09 | 0.346940E+09 | 87130715.89 |
May | 0.379794E+09 | 0.213258E+09 | 0.166536E+09 | 0.474307E+09 | 57391715.40 |
June | 0.387778E+09 | 0.223332E+09 | 0.164446E+09 | 0.479641E+09 | 53853284.92 |
July | 0.409647E+09 | 0.244085E+09 | 0.165562E+09 | 0.489498E+09 | 76533614.93 |
August | 0.326494E+09 | 0.184193E+09 | 0.142301E+09 | 0.385845E+09 | 74679737.25 |
September | 0.229642E+09 | 0.118926E+09 | 0.110716E+09 | 0.259462E+09 | 83961603.39 |
October | 0.136302E+09 | 52072475.95 | 84229445.37 | 0.143328E+09 | 90886094.28 |
November | 78775603.14 | 24138730.45 | 54636872.69 | 56838999.29 | 0.142101E+09 |
December | 64603296.97 | 16441331.13 | 48161965.84 | 13555688.60 | 0.274826E+09 |
Annual Sum or Average | 0.274183E+10 | 0.147595E+10 | 0.126588E+10 | 0.297828E+10 | 0.159998E+10 |
Minimum of Months | 64603296.97 | 16441331.13 | 48161965.84 | 13555688.60 | 53853284.92 |
Maximum of Months | 0.409647E+09 | 0.244085E+09 | 0.166536E+09 | 0.489498E+09 | 0.292131E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83230840.30 | 29084049.09 | 54146791.21 | 27514787.30 | 0.292131E+09 |
February | 0.133218E+09 | 61314697.29 | 71903005.34 | 99653201.12 | 0.205377E+09 |
March | 0.212563E+09 | 0.120270E+09 | 92293560.69 | 0.201698E+09 | 0.161108E+09 |
April | 0.299783E+09 | 0.188836E+09 | 0.110947E+09 | 0.346940E+09 | 87130715.89 |
May | 0.379794E+09 | 0.213258E+09 | 0.166536E+09 | 0.474307E+09 | 57391715.40 |
June | 0.387778E+09 | 0.223332E+09 | 0.164446E+09 | 0.479641E+09 | 53853284.92 |
July | 0.409647E+09 | 0.244085E+09 | 0.165562E+09 | 0.489498E+09 | 76533614.93 |
August | 0.326494E+09 | 0.184193E+09 | 0.142301E+09 | 0.385845E+09 | 74679737.25 |
September | 0.229642E+09 | 0.118926E+09 | 0.110716E+09 | 0.259462E+09 | 83961603.39 |
October | 0.136302E+09 | 52072475.95 | 84229445.37 | 0.143328E+09 | 90886094.28 |
November | 78775603.14 | 24138730.45 | 54636872.69 | 56838999.29 | 0.142101E+09 |
December | 64603296.97 | 16441331.13 | 48161965.84 | 13555688.60 | 0.274826E+09 |
Annual Sum or Average | 0.274183E+10 | 0.147595E+10 | 0.126588E+10 | 0.297828E+10 | 0.159998E+10 |
Minimum of Months | 64603296.97 | 16441331.13 | 48161965.84 | 13555688.60 | 53853284.92 |
Maximum of Months | 0.409647E+09 | 0.244085E+09 | 0.166536E+09 | 0.489498E+09 | 0.292131E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83230840.30 | 29084049.09 | 54146791.21 | 27514787.30 | 0.292131E+09 |
February | 0.133218E+09 | 61314697.29 | 71903005.34 | 99653201.12 | 0.205377E+09 |
March | 0.212563E+09 | 0.120270E+09 | 92293560.69 | 0.201698E+09 | 0.161108E+09 |
April | 0.299783E+09 | 0.188836E+09 | 0.110947E+09 | 0.346940E+09 | 87130715.89 |
May | 0.379794E+09 | 0.213258E+09 | 0.166536E+09 | 0.474307E+09 | 57391715.40 |
June | 0.387778E+09 | 0.223332E+09 | 0.164446E+09 | 0.479641E+09 | 53853284.92 |
July | 0.409647E+09 | 0.244085E+09 | 0.165562E+09 | 0.489498E+09 | 76533614.93 |
August | 0.326494E+09 | 0.184193E+09 | 0.142301E+09 | 0.385845E+09 | 74679737.25 |
September | 0.229642E+09 | 0.118926E+09 | 0.110716E+09 | 0.259462E+09 | 83961603.39 |
October | 0.136302E+09 | 52072475.95 | 84229445.37 | 0.143328E+09 | 90886094.28 |
November | 78775603.14 | 24138730.45 | 54636872.69 | 56838999.29 | 0.142101E+09 |
December | 64603296.97 | 16441331.13 | 48161965.84 | 13555688.60 | 0.274826E+09 |
Annual Sum or Average | 0.274183E+10 | 0.147595E+10 | 0.126588E+10 | 0.297828E+10 | 0.159998E+10 |
Minimum of Months | 64603296.97 | 16441331.13 | 48161965.84 | 13555688.60 | 53853284.92 |
Maximum of Months | 0.409647E+09 | 0.244085E+09 | 0.166536E+09 | 0.489498E+09 | 0.292131E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83230840.30 | 29084049.09 | 54146791.21 | 27514787.30 | 0.292131E+09 |
February | 0.133218E+09 | 61314697.29 | 71903005.34 | 99653201.12 | 0.205377E+09 |
March | 0.212563E+09 | 0.120270E+09 | 92293560.69 | 0.201698E+09 | 0.161108E+09 |
April | 0.299783E+09 | 0.188836E+09 | 0.110947E+09 | 0.346940E+09 | 87130715.89 |
May | 0.379794E+09 | 0.213258E+09 | 0.166536E+09 | 0.474307E+09 | 57391715.40 |
June | 0.387778E+09 | 0.223332E+09 | 0.164446E+09 | 0.479641E+09 | 53853284.92 |
July | 0.409647E+09 | 0.244085E+09 | 0.165562E+09 | 0.489498E+09 | 76533614.93 |
August | 0.326494E+09 | 0.184193E+09 | 0.142301E+09 | 0.385845E+09 | 74679737.25 |
September | 0.229642E+09 | 0.118926E+09 | 0.110716E+09 | 0.259462E+09 | 83961603.39 |
October | 0.136302E+09 | 52072475.95 | 84229445.37 | 0.143328E+09 | 90886094.28 |
November | 78775603.14 | 24138730.45 | 54636872.69 | 56838999.29 | 0.142101E+09 |
December | 64603296.97 | 16441331.13 | 48161965.84 | 13555688.60 | 0.274826E+09 |
Annual Sum or Average | 0.274183E+10 | 0.147595E+10 | 0.126588E+10 | 0.297828E+10 | 0.159998E+10 |
Minimum of Months | 64603296.97 | 16441331.13 | 48161965.84 | 13555688.60 | 53853284.92 |
Maximum of Months | 0.409647E+09 | 0.244085E+09 | 0.166536E+09 | 0.489498E+09 | 0.292131E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83230840.30 | 29084049.09 | 54146791.21 | 27514787.30 | 0.292131E+09 |
February | 0.133218E+09 | 61314697.29 | 71903005.34 | 99653201.12 | 0.205377E+09 |
March | 0.212563E+09 | 0.120270E+09 | 92293560.69 | 0.201698E+09 | 0.161108E+09 |
April | 0.299783E+09 | 0.188836E+09 | 0.110947E+09 | 0.346940E+09 | 87130715.89 |
May | 0.379794E+09 | 0.213258E+09 | 0.166536E+09 | 0.474307E+09 | 57391715.40 |
June | 0.387778E+09 | 0.223332E+09 | 0.164446E+09 | 0.479641E+09 | 53853284.92 |
July | 0.409647E+09 | 0.244085E+09 | 0.165562E+09 | 0.489498E+09 | 76533614.93 |
August | 0.326494E+09 | 0.184193E+09 | 0.142301E+09 | 0.385845E+09 | 74679737.25 |
September | 0.229642E+09 | 0.118926E+09 | 0.110716E+09 | 0.259462E+09 | 83961603.39 |
October | 0.136302E+09 | 52072475.95 | 84229445.37 | 0.143328E+09 | 90886094.28 |
November | 78775603.14 | 24138730.45 | 54636872.69 | 56838999.29 | 0.142101E+09 |
December | 64603296.97 | 16441331.13 | 48161965.84 | 13555688.60 | 0.274826E+09 |
Annual Sum or Average | 0.274183E+10 | 0.147595E+10 | 0.126588E+10 | 0.297828E+10 | 0.159998E+10 |
Minimum of Months | 64603296.97 | 16441331.13 | 48161965.84 | 13555688.60 | 53853284.92 |
Maximum of Months | 0.409647E+09 | 0.244085E+09 | 0.166536E+09 | 0.489498E+09 | 0.292131E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 40.13 | 681.51 | 187.45 | 62.87 | 124.58 | 0.00 | 0.00 |
February | 135.74 | 526.17 | 299.70 | 109.90 | 189.80 | 0.00 | 0.00 |
March | 243.88 | 394.70 | 388.80 | 161.68 | 227.12 | 0.00 | 0.00 |
April | 420.66 | 222.18 | 498.16 | 204.33 | 293.84 | 0.00 | 0.00 |
May | 628.18 | 127.67 | 630.03 | 243.48 | 386.55 | 0.00 | 0.00 |
June | 642.27 | 101.34 | 627.71 | 222.79 | 404.92 | 0.00 | 0.00 |
July | 672.05 | 115.27 | 654.04 | 249.87 | 404.17 | 0.00 | 0.00 |
August | 527.77 | 133.38 | 527.57 | 191.33 | 336.24 | 0.00 | 0.00 |
September | 371.62 | 177.85 | 412.55 | 146.71 | 265.84 | 0.00 | 0.00 |
October | 186.39 | 234.33 | 266.44 | 83.33 | 183.11 | 0.00 | 0.00 |
November | 57.29 | 378.34 | 165.78 | 43.27 | 122.51 | 0.00 | 0.00 |
December | 17.93 | 657.99 | 144.72 | 39.08 | 105.64 | 0.00 | 0.00 |
Annual Sum or Average | 329.76 | 311.82 | 400.79 | 146.77 | 254.02 | 0.00 | 0.00 |
Minimum of Months | 17.93 | 101.34 | 144.72 | 39.08 | 105.64 | 0.00 | 0.00 |
Maximum of Months | 672.05 | 681.51 | 654.04 | 249.87 | 404.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 102.73 | 1090.69 | 310.75 | 108.59 | 202.16 | 0.00 | 0.00 |
February | 411.93 | 848.95 | 550.67 | 253.45 | 297.22 | 0.00 | 0.00 |
March | 753.05 | 601.51 | 793.62 | 449.04 | 344.58 | 0.00 | 0.00 |
April | 1338.50 | 336.15 | 1156.57 | 728.54 | 428.04 | 0.00 | 0.00 |
May | 1770.86 | 214.28 | 1417.99 | 796.21 | 621.77 | 0.00 | 0.00 |
June | 1850.47 | 207.77 | 1496.06 | 861.62 | 634.44 | 0.00 | 0.00 |
July | 1827.57 | 285.74 | 1529.45 | 911.31 | 618.14 | 0.00 | 0.00 |
August | 1440.58 | 278.82 | 1218.99 | 687.70 | 531.29 | 0.00 | 0.00 |
September | 1001.01 | 323.93 | 885.96 | 458.82 | 427.15 | 0.00 | 0.00 |
October | 535.12 | 339.33 | 508.89 | 194.42 | 314.48 | 0.00 | 0.00 |
November | 219.29 | 548.23 | 303.92 | 93.13 | 210.79 | 0.00 | 0.00 |
December | 50.61 | 1026.08 | 241.20 | 61.38 | 179.82 | 0.00 | 0.00 |
Annual Sum or Average | 944.41 | 507.35 | 869.43 | 468.02 | 401.41 | 0.00 | 0.00 |
Minimum of Months | 50.61 | 207.77 | 241.20 | 61.38 | 179.82 | 0.00 | 0.00 |
Maximum of Months | 1850.47 | 1090.69 | 1529.45 | 911.31 | 634.44 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.107496E+09 | 0.182535E+10 | 0.502074E+09 | 0.168401E+09 | 0.333673E+09 | 0.00 | 0.00 |
February | 0.328379E+09 | 0.127292E+10 | 0.725037E+09 | 0.265874E+09 | 0.459164E+09 | 0.00 | 0.00 |
March | 0.653219E+09 | 0.105715E+10 | 0.104135E+10 | 0.433040E+09 | 0.608309E+09 | 0.00 | 0.00 |
April | 0.109034E+10 | 0.575887E+09 | 0.129124E+10 | 0.529614E+09 | 0.761628E+09 | 0.00 | 0.00 |
May | 0.168252E+10 | 0.341942E+09 | 0.168746E+10 | 0.652131E+09 | 0.103533E+10 | 0.00 | 0.00 |
June | 0.166476E+10 | 0.262674E+09 | 0.162702E+10 | 0.577460E+09 | 0.104956E+10 | 0.00 | 0.00 |
July | 0.180002E+10 | 0.308734E+09 | 0.175179E+10 | 0.669258E+09 | 0.108253E+10 | 0.00 | 0.00 |
August | 0.141357E+10 | 0.357250E+09 | 0.141306E+10 | 0.512467E+09 | 0.900589E+09 | 0.00 | 0.00 |
September | 0.963239E+09 | 0.460979E+09 | 0.106932E+10 | 0.380271E+09 | 0.689053E+09 | 0.00 | 0.00 |
October | 0.499236E+09 | 0.627632E+09 | 0.713631E+09 | 0.223202E+09 | 0.490429E+09 | 0.00 | 0.00 |
November | 0.148488E+09 | 0.980662E+09 | 0.429704E+09 | 0.112157E+09 | 0.317547E+09 | 0.00 | 0.00 |
December | 48019811.46 | 0.176236E+10 | 0.387628E+09 | 0.104684E+09 | 0.282943E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.103993E+11 | 0.983354E+10 | 0.126393E+11 | 0.462856E+10 | 0.801075E+10 | 0.00 | 0.00 |
Minimum of Months | 48019811.46 | 0.262674E+09 | 0.387628E+09 | 0.104684E+09 | 0.282943E+09 | 0.00 | 0.00 |
Maximum of Months | 0.180002E+10 | 0.182535E+10 | 0.175179E+10 | 0.669258E+09 | 0.108253E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.275147E+09 | 0.292131E+10 | 0.832308E+09 | 0.290840E+09 | 0.541468E+09 | 0.00 | 0.00 |
February | 0.996532E+09 | 0.205377E+10 | 0.133218E+10 | 0.613147E+09 | 0.719030E+09 | 0.00 | 0.00 |
March | 0.201698E+10 | 0.161108E+10 | 0.212563E+10 | 0.120270E+10 | 0.922936E+09 | 0.00 | 0.00 |
April | 0.346940E+10 | 0.871306E+09 | 0.299783E+10 | 0.188836E+10 | 0.110947E+10 | 0.00 | 0.00 |
May | 0.474307E+10 | 0.573916E+09 | 0.379794E+10 | 0.213258E+10 | 0.166536E+10 | 0.00 | 0.00 |
June | 0.479641E+10 | 0.538532E+09 | 0.387778E+10 | 0.223332E+10 | 0.164446E+10 | 0.00 | 0.00 |
July | 0.489497E+10 | 0.765336E+09 | 0.409647E+10 | 0.244085E+10 | 0.165562E+10 | 0.00 | 0.00 |
August | 0.385845E+10 | 0.746796E+09 | 0.326494E+10 | 0.184193E+10 | 0.142301E+10 | 0.00 | 0.00 |
September | 0.259462E+10 | 0.839616E+09 | 0.229642E+10 | 0.118926E+10 | 0.110716E+10 | 0.00 | 0.00 |
October | 0.143327E+10 | 0.908861E+09 | 0.136302E+10 | 0.520725E+09 | 0.842294E+09 | 0.00 | 0.00 |
November | 0.568389E+09 | 0.142101E+10 | 0.787756E+09 | 0.241387E+09 | 0.546369E+09 | 0.00 | 0.00 |
December | 0.135556E+09 | 0.274826E+10 | 0.646033E+09 | 0.164413E+09 | 0.481620E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.297828E+11 | 0.159998E+11 | 0.274183E+11 | 0.147595E+11 | 0.126588E+11 | 0.00 | 0.00 |
Minimum of Months | 0.135556E+09 | 0.538532E+09 | 0.646033E+09 | 0.164413E+09 | 0.481620E+09 | 0.00 | 0.00 |
Maximum of Months | 0.489497E+10 | 0.292131E+10 | 0.409647E+10 | 0.244085E+10 | 0.166536E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.3 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.6 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.5 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.48 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.18 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.96 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.19 | 13.59 | 3.45 | 8.98 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.33 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.48 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.07 | -2.0 | 3.82 | -8.5 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.3 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.98 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -0.9 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.85 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.46 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.93 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.24 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.70 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.34 | 23.33 | 8.07 | 19.92 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.35 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.80 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.60 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.43 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -0.9 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.34 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.3 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.0 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.61 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.6 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.4 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.33 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.46 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.93 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.90 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.70 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.75 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.35 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.70 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.4 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.75 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.24 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.06 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.90 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.75 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.35 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.22 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.16 | 3.43 | 9.18 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 06-DEC-02:00 | 0.00 | -0.0 | 3.60 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.75 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: ELECTRIC TANK
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.109149E+10 | -.102006E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -71426180.9 | 59.00 | 0.00 | 0.00 |
February | 0.102266E+10 | -958341991.7 | 0.00 | 0.00 | 672.00 | 0.00 | -64315723.0 | 59.00 | 0.00 | 0.00 |
March | 0.118648E+10 | -.111583E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -70650456.0 | 59.00 | 0.00 | 0.00 |
April | 0.107263E+10 | -.100533E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -67301006.4 | 59.00 | 0.00 | 0.00 |
May | 0.105718E+10 | -993226883.8 | 0.00 | 0.00 | 744.00 | 0.00 | -63953397.2 | 58.99 | 0.00 | 0.00 |
June | 0.988920E+09 | -930621588.0 | 0.00 | 0.00 | 720.00 | 0.00 | -58298736.1 | 58.99 | 0.00 | 0.00 |
July | 0.909445E+09 | -852034287.0 | 0.00 | 0.00 | 744.00 | 0.00 | -57411152.8 | 58.99 | 0.00 | 0.00 |
August | 0.947300E+09 | -888783931.5 | 0.00 | 0.00 | 744.00 | 0.00 | -58516381.0 | 58.99 | 0.00 | 0.00 |
September | 0.890729E+09 | -830383679.5 | 0.00 | 0.00 | 720.00 | 0.00 | -60345587.8 | 59.00 | 0.00 | 0.00 |
October | 0.933578E+09 | -864986526.1 | 0.00 | 0.00 | 744.00 | 0.00 | -68591413.7 | 58.99 | 0.00 | 0.00 |
November | 0.947782E+09 | -879474704.5 | 0.00 | 0.00 | 720.00 | 0.00 | -68307086.2 | 58.99 | 0.00 | 0.00 |
December | 0.104284E+10 | -971536987.6 | 0.00 | 0.00 | 744.00 | 0.00 | -71302607.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.120910E+11 | -.113106E+11 | 8760.00 | -780419729.2 | 59.00 | |||||
Minimum of Months | 0.890729E+09 | -.111583E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -71426180.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.118648E+10 | -830383679.5 | 0.00 | 0.00 | 744.00 | 0.00 | -57411152.8 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 243.33 | 0.95 | 0.88 | 08-JAN-11:09 | 124.08 | 8.92 | 0.00 | 45.17 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 265.33 | 0.94 | 0.88 | 02-FEB-10:00 | 154.47 | 10.20 | 0.00 | 73.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 254.17 | 0.94 | 0.88 | 02-MAR-10:39 | 167.17 | 10.48 | 0.00 | 111.67 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.33 | 0.93 | 0.88 | 01-APR-10:39 | 197.06 | 11.01 | 0.00 | 157.83 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 437.50 | 0.91 | 0.88 | 01-MAY-11:20 | 963.29 | 12.55 | 0.00 | 271.33 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401.83 | 0.91 | 0.88 | 01-JUN-07:49 | 404.91 | 12.88 | 1.83 | 284.67 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 409.17 | 0.91 | 0.88 | 01-JUL-07:49 | 1049.15 | 14.04 | 27.67 | 290.50 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 352.83 | 0.91 | 0.88 | 01-AUG-07:49 | 283.52 | 12.69 | 0.00 | 246.50 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.17 | 0.92 | 0.88 | 01-SEP-14:30 | 212.27 | 11.56 | 0.00 | 160.67 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 299.00 | 0.93 | 0.88 | 01-OCT-09:20 | 173.21 | 10.56 | 0.00 | 110.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 255.50 | 0.95 | 0.88 | 01-NOV-09:39 | 129.71 | 9.31 | 0.00 | 37.83 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 226.33 | 0.95 | 0.88 | 01-DEC-11:30 | 120.27 | 8.82 | 0.00 | 20.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3785.50 | 0.93 | 388.52 | 11.41 | 29.50 | 1809.83 | ||||||
Minimum of Months | 226.33 | 0.91 | 0.88 | 120.27 | 8.82 | 0.00 | 20.67 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 437.50 | 0.95 | 0.88 | 1049.15 | 14.04 | 27.67 | 290.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.92 | 0.87 | 31-JAN-15:09 | 276.13 | 23.18 | 134.17 | 20.00 | 112.74 | 20.84 | 108.17 | 0.00 |
February | 265.33 | 0.91 | 0.86 | 06-FEB-15:30 | 558.69 | 25.21 | 171.17 | 67.50 | 155.13 | 21.95 | 163.17 | 2.33 |
March | 254.17 | 0.90 | 0.86 | 02-MAR-14:30 | 577.64 | 24.65 | 181.17 | 89.50 | 489.14 | 25.30 | 203.17 | 46.83 |
April | 296.33 | 0.90 | 0.86 | 01-APR-12:30 | 417.46 | 22.70 | 196.17 | 107.17 | 450.19 | 23.94 | 241.00 | 71.83 |
May | 437.50 | 0.89 | 0.86 | 01-MAY-14:30 | 352.61 | 22.07 | 262.17 | 185.00 | 471.20 | 23.16 | 309.33 | 95.67 |
June | 401.83 | 0.89 | 0.86 | 01-JUN-14:50 | 384.17 | 22.27 | 256.17 | 180.83 | 466.50 | 23.47 | 319.83 | 100.17 |
July | 409.17 | 0.89 | 0.86 | 01-JUL-13:30 | 400.09 | 22.60 | 257.83 | 196.83 | 543.58 | 23.75 | 333.67 | 118.50 |
August | 352.83 | 0.89 | 0.86 | 01-AUG-13:30 | 394.38 | 22.88 | 230.17 | 159.00 | 446.36 | 23.81 | 284.00 | 94.83 |
September | 344.17 | 0.90 | 0.86 | 01-SEP-14:20 | 500.79 | 23.97 | 213.33 | 112.17 | 424.70 | 24.42 | 238.83 | 57.50 |
October | 299.00 | 0.91 | 0.86 | 01-OCT-13:00 | 355.50 | 23.43 | 171.50 | 54.83 | 150.91 | 22.11 | 171.33 | 5.83 |
November | 255.50 | 0.93 | 0.87 | 09-NOV-14:39 | 202.69 | 21.55 | 110.67 | 10.67 | 103.08 | 20.36 | 102.17 | 0.00 |
December | 226.33 | 0.93 | 0.88 | 16-DEC-14:30 | 175.38 | 20.34 | 86.33 | 0.00 | 97.47 | 20.37 | 82.50 | 0.00 |
Annual Sum or Average | 3785.50 | 0.90 | 387.69 | 22.88 | 2270.83 | 1183.50 | 353.86 | 22.96 | 2557.17 | 593.50 | ||
Minimum of Months | 226.33 | 0.89 | 0.86 | 175.38 | 20.34 | 86.33 | 0.00 | 97.47 | 20.36 | 82.50 | 0.00 | |
Maximum of Months | 437.50 | 0.93 | 0.88 | 577.64 | 25.21 | 262.17 | 196.83 | 543.58 | 25.30 | 333.67 | 118.50 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.157051E+11 | 25500.21 | 01-JAN-11:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116147E+11 | 25500.21 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104782E+11 | 25500.21 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.489696E+10 | 25500.21 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.832336E+09 | 25500.21 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12264045.32 | 14162.19 | 02-JUN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.379575E+09 | 25500.21 | 28-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.347614E+10 | 25500.21 | 03-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.704947E+10 | 25500.21 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138083E+11 | 25500.21 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.682529E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.157051E+11 | 25500.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.612813E+11 | 61844.54 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.447944E+11 | 61844.54 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.325826E+11 | 61844.54 | 01-MAR-19:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122392E+11 | 61844.54 | 01-APR-17:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.314851E+09 | 46122.29 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.605858E+10 | 61844.54 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.257871E+11 | 61844.54 | 04-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.567586E+11 | 61844.54 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239817E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.612813E+11 | 61844.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATERHEATINGCOIL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.197443E+12 | 136351.45 | 03-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149061E+12 | 136351.45 | 01-FEB-05:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.967479E+11 | 120503.21 | 15-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.295276E+11 | 76961.42 | 04-APR-18:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.209340E+09 | 13700.26 | 01-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.502688E+10 | 39378.04 | 31-OCT-20:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.778150E+11 | 102286.84 | 25-NOV-01:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188181E+12 | 136351.45 | 16-DEC-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.744012E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.197443E+12 | 136351.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.107632E+10 | 0.968700E+09 | 15923.28 | 27-MAY-07:03 | 13397.67 | 0.00 |
June | 0.00 | 0.00 | 0.379914E+10 | 0.306812E+10 | 18345.40 | 30-JUN-06:02 | 11084.44 | 0.00 |
July | 0.00 | 0.00 | 0.632557E+10 | 0.514193E+10 | 18164.71 | 05-JUL-06:03 | 10921.66 | 0.00 |
August | 0.00 | 0.00 | 0.517991E+10 | 0.416723E+10 | 17383.28 | 09-AUG-07:03 | 10877.16 | 0.00 |
September | 0.00 | 0.00 | 0.115953E+10 | 0.105360E+10 | 15638.91 | 02-SEP-07:02 | 13771.40 | 0.00 |
October | 0.00 | 0.00 | 161973.05 | 161973.05 | 112.30 | 21-OCT-16:00 | 112.30 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.175406E+11 | 0.143997E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.632557E+10 | 0.514193E+10 | 18345.40 | 13771.40 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 40186542.75 | 30495360.13 | 4209.76 | 25-MAY-16:00 | 3217.29 | 0.00 |
June | 0.00 | 0.00 | 0.281126E+10 | 0.190190E+10 | 36318.19 | 28-JUN-19:08 | 22492.20 | 0.00 |
July | 0.00 | 0.00 | 0.538320E+10 | 0.362028E+10 | 39391.39 | 23-JUL-09:23 | 18703.62 | 0.00 |
August | 0.00 | 0.00 | 0.179514E+10 | 0.118506E+10 | 36511.51 | 09-AUG-17:50 | 22632.20 | 0.00 |
September | 0.00 | 0.00 | 0.160925E+09 | 0.118799E+09 | 10087.75 | 01-SEP-15:00 | 7887.27 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.101907E+11 | 0.685653E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.538320E+10 | 0.362028E+10 | 39391.39 | 22632.20 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATERFAN
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.848763E+09 | 0.08 | 318.25 | 01-JAN-00:02 | 0.08 |
February | 0.761309E+09 | 0.08 | 318.25 | 01-FEB-00:02 | 0.08 |
March | 0.789394E+09 | 0.07 | 318.25 | 01-MAR-00:03 | 0.08 |
April | 0.390775E+09 | 0.04 | 318.25 | 01-APR-00:10 | 0.08 |
May | 10406659.94 | 0.00 | 318.25 | 01-MAY-00:10 | 0.08 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.166411E+09 | 0.02 | 318.25 | 11-OCT-21:30 | 0.08 |
November | 0.725029E+09 | 0.07 | 318.25 | 01-NOV-00:10 | 0.08 |
December | 0.852391E+09 | 0.08 | 318.25 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.454448E+10 | 0.04 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.852391E+09 | 0.08 | 318.25 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.107576E+10 | 0.66 | 963.70 | 02-JAN-16:40 | 0.95 |
February | 0.952516E+09 | 0.59 | 963.70 | 01-FEB-12:00 | 0.95 |
March | 0.107278E+10 | 0.49 | 963.70 | 01-MAR-08:00 | 0.95 |
April | 0.967190E+09 | 0.40 | 963.70 | 01-APR-16:00 | 0.95 |
May | 0.993207E+09 | 0.37 | 963.70 | 02-MAY-06:09 | 0.95 |
June | 0.992226E+09 | 0.37 | 963.70 | 01-JUN-09:40 | 0.94 |
July | 0.954064E+09 | 0.35 | 963.70 | 03-JUL-16:00 | 0.94 |
August | 0.103039E+10 | 0.37 | 963.70 | 01-AUG-08:40 | 0.94 |
September | 0.954064E+09 | 0.36 | 963.70 | 05-SEP-09:50 | 0.94 |
October | 0.957798E+09 | 0.36 | 963.70 | 02-OCT-07:30 | 0.94 |
November | 0.939343E+09 | 0.42 | 963.70 | 01-NOV-09:10 | 0.94 |
December | 0.105190E+10 | 0.61 | 963.70 | 01-DEC-15:50 | 0.95 |
Annual Sum or Average | 0.119412E+11 | 0.44 | |||
Minimum of Months | 0.939343E+09 | 0.35 | 963.70 | 0.94 | |
Maximum of Months | 0.107576E+10 | 0.66 | 963.70 | 0.95 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.234752E+10 | 0.84 | 1487.47 | 02-JAN-07:15 | 0.95 |
February | 0.202856E+10 | 0.83 | 1487.47 | 01-FEB-07:17 | 0.95 |
March | 0.207631E+10 | 0.80 | 1487.47 | 01-MAR-07:06 | 0.95 |
April | 0.169785E+10 | 0.65 | 1487.47 | 01-APR-07:08 | 0.95 |
May | 0.153870E+10 | 0.38 | 1487.47 | 01-MAY-06:06 | 0.95 |
June | 0.154705E+10 | 0.38 | 1487.47 | 21-JUN-12:10 | 0.94 |
July | 0.151347E+10 | 0.36 | 1487.47 | 01-JUL-10:30 | 0.94 |
August | 0.159130E+10 | 0.37 | 1487.47 | 01-AUG-13:10 | 0.94 |
September | 0.147260E+10 | 0.36 | 1487.47 | 01-SEP-09:50 | 0.93 |
October | 0.158929E+10 | 0.55 | 1487.47 | 04-OCT-07:50 | 0.95 |
November | 0.185858E+10 | 0.80 | 1487.47 | 02-NOV-06:05 | 0.95 |
December | 0.231514E+10 | 0.84 | 1487.47 | 01-DEC-08:00 | 0.95 |
Annual Sum or Average | 0.215764E+11 | 0.60 | |||
Minimum of Months | 0.147260E+10 | 0.36 | 1487.47 | 0.93 | |
Maximum of Months | 0.234752E+10 | 0.84 | 1487.47 | 0.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.39 | 0.31 |
February | 3.92 | 0.10 |
March | 4.68 | 0.14 |
April | 2.13 | 0.09 |
May | 2.19 | 3.67 |
June | 2.37 | 3.00 |
July | 3.03 | 0.46 |
August | 3.32 | 1.01 |
September | 2.08 | 2.90 |
October | 1.76 | 0.70 |
November | 3.80 | 0.03 |
December | 4.16 | 0.10 |
Annual Sum or Average | 37.83 | 0.80 |
Minimum of Months | 1.76 | 0.03 |
Maximum of Months | 4.68 | 3.67 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.04 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.06 | 0.00 |
August | 0.00 | 0.00 |
September | 0.08 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.18 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.08 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.107576E+10 | 0.215270E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.952516E+09 | 0.160930E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.107278E+10 | 0.147217E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.967190E+09 | 0.706044E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.122081E+10 | 0.121528E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.178472E+10 | 18245664.70 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.222240E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.207092E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.119440E+10 | 0.565687E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.957834E+09 | 0.507575E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.939343E+09 | 0.100574E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.105190E+10 | 0.190723E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.155106E+11 | 0.954068E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.939343E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.222240E+10 | 0.215270E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.234752E+10 | 0.841644E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.202856E+10 | 0.622364E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.207631E+10 | 0.463343E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.169785E+10 | 0.177183E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.154876E+10 | 0.468014E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.219798E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.272030E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.199796E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.150933E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.158929E+10 | 0.895846E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.185858E+10 | 0.368336E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.231514E+10 | 0.784462E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.238876E+11 | 0.335160E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.150933E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.272030E+10 | 0.841644E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.107576E+10 | 0.00 | 0.157051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.952516E+09 | 0.00 | 0.116147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107278E+10 | 0.00 | 0.104782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.967190E+09 | 0.00 | 0.489696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.993207E+09 | 0.107632E+10 | 0.832336E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.992226E+09 | 0.379914E+10 | 12264045.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.954064E+09 | 0.632557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.103039E+10 | 0.517991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.954064E+09 | 0.115953E+10 | 0.379575E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.957798E+09 | 161973.05 | 0.347614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.939343E+09 | 0.00 | 0.704947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105190E+10 | 0.00 | 0.138083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119412E+11 | 0.175406E+11 | 0.682529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.939343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107576E+10 | 0.632557E+10 | 0.157051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.234752E+10 | 0.00 | 0.612813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202856E+10 | 0.00 | 0.447944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207631E+10 | 0.00 | 0.325826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169785E+10 | 0.00 | 0.122392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153870E+10 | 40186542.75 | 0.314851E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154705E+10 | 0.281126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151347E+10 | 0.538320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159130E+10 | 0.179514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147260E+10 | 0.160925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158929E+10 | 0.00 | 0.605858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185858E+10 | 0.00 | 0.257871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231514E+10 | 0.00 | 0.567586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215764E+11 | 0.101907E+11 | 0.239817E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.147260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.234752E+10 | 0.538320E+10 | 0.612813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.107576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.952516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.967190E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.993207E+09 | 0.00 | 0.00 | 0.00 | 0.227608E+09 | 0.00 | 0.121528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.992226E+09 | 0.00 | 0.00 | 0.00 | 0.792493E+09 | 0.00 | 18245664.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.954064E+09 | 0.00 | 0.00 | 0.00 | 0.126834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.103039E+10 | 0.00 | 0.00 | 0.00 | 0.104053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.954064E+09 | 0.00 | 0.00 | 0.00 | 0.240336E+09 | 0.00 | 0.565687E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.957798E+09 | 0.00 | 0.00 | 0.00 | 36260.14 | 0.00 | 0.507575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.939343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119412E+11 | 0.00 | 0.00 | 0.00 | 0.356934E+10 | 0.00 | 0.954068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.939343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107576E+10 | 0.00 | 0.00 | 0.00 | 0.126834E+10 | 0.00 | 0.215270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.234752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153870E+10 | 0.00 | 0.00 | 0.00 | 10063051.94 | 0.00 | 0.468014E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154705E+10 | 0.00 | 0.00 | 0.00 | 0.650935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151347E+10 | 0.00 | 0.00 | 0.00 | 0.120682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159130E+10 | 0.00 | 0.00 | 0.00 | 0.406655E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147260E+10 | 0.00 | 0.00 | 0.00 | 36729404.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215764E+11 | 0.00 | 0.00 | 0.00 | 0.231120E+10 | 0.00 | 0.335160E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.147260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.234752E+10 | 0.00 | 0.00 | 0.00 | 0.120682E+10 | 0.00 | 0.841644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2234039.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500227E+10 | 0.00 | 0.00 | 0.15 |
February | 4574852.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373298E+10 | 0.00 | 0.00 | 0.15 |
March | 9040867.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348191E+10 | 0.00 | 0.00 | 0.15 |
April | 84398292.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182233E+10 | 0.00 | 0.00 | 0.14 |
May | 0.437120E+09 | 56864374.45 | 0.00 | 555326.28 | 87748.64 | 0.350434E+09 | 0.143877E+09 | 0.00 | 0.14 |
June | 0.186779E+09 | 0.359892E+09 | 0.00 | 1692337.09 | 371008.46 | 4998852.42 | 0.283950E+09 | 0.00 | 0.15 |
July | 60783547.91 | 0.581641E+09 | 0.00 | 2859516.03 | 132989.90 | 0.00 | 0.177405E+09 | 0.00 | 0.14 |
August | 0.135524E+09 | 0.316140E+09 | 0.00 | 2947560.97 | 0.00 | 0.00 | 0.289698E+09 | 0.00 | 0.15 |
September | 0.610251E+09 | 12509248.12 | 0.00 | 1407910.68 | 0.00 | 0.172216E+09 | 0.351669E+09 | 0.00 | 0.14 |
October | 0.231623E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152051E+10 | 0.00 | 0.00 | 0.14 |
November | 16383120.62 | 0.00 | 45164.41 | 0.00 | 0.00 | 0.248860E+10 | 0.00 | 48480.53 | 0.14 |
December | 5246840.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454093E+10 | 0.00 | 0.00 | 0.15 |
Annual Sum or Average | 0.178396E+10 | 0.132705E+10 | 45164.41 | 9462651.05 | 591747.00 | 0.231172E+11 | 0.124660E+10 | 48480.53 | 0.14 |
Minimum of Months | 2234039.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.610251E+09 | 0.581641E+09 | 45164.41 | 2947560.97 | 371008.46 | 0.500227E+10 | 0.351669E+09 | 48480.53 | 0.15 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141960E+11 | 0.00 | 0.00 | 0.17 |
February | 0.565863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.974914E+10 | 0.00 | 0.00 | 0.17 |
March | 0.165642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772237E+10 | 0.00 | 0.00 | 0.19 |
April | 0.234694E+10 | 0.00 | 0.00 | 0.00 | 4594901.03 | 0.205908E+10 | 0.00 | 0.00 | 0.18 |
May | 0.213636E+10 | 7286364.65 | 0.00 | 0.00 | 0.173915E+09 | 34276483.06 | 0.00 | 0.00 | 0.18 |
June | 0.161977E+10 | 0.691802E+09 | 0.00 | 317495.31 | 8772488.66 | 0.00 | 0.118115E+09 | 0.00 | 0.22 |
July | 0.842881E+09 | 0.100111E+10 | 0.00 | 2260697.87 | 69545.58 | 0.00 | 0.115520E+10 | 0.00 | 0.27 |
August | 0.192403E+10 | 0.328894E+09 | 0.00 | 987094.55 | 149675.97 | 0.00 | 0.691031E+09 | 0.00 | 0.25 |
September | 0.314681E+10 | 3989020.28 | 0.00 | 158290.20 | 1121559.62 | 0.00 | 66926501.40 | 0.00 | 0.19 |
October | 0.302866E+10 | 0.00 | 0.00 | 0.00 | 13491913.47 | 0.102548E+10 | 0.00 | 0.00 | 0.17 |
November | 0.120646E+10 | 0.00 | 0.00 | 0.00 | 1528476.30 | 0.528937E+10 | 0.00 | 0.00 | 0.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128607E+11 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.184742E+11 | 0.203308E+10 | 0.00 | 3723577.93 | 0.203643E+09 | 0.529364E+11 | 0.203128E+10 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.314681E+10 | 0.100111E+10 | 0.00 | 2260697.87 | 0.173915E+09 | 0.141960E+11 | 0.115520E+10 | 0.00 | 0.27 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2020-06-03 19:11:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |