Table of Contents

Program Version:EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:15

Tabular Output Report in Format: HTML

Building: US+MF+CZ1AWHT+elecres+slab+IECC_2021

Environment: ANNUAL ** Honolulu Intl Arpt HI USA TMY3 WMO#=911820

Simulation Timestamp: 2021-05-12 10:15:16


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 549856.20 17.62 25.44
Net Site Energy 549856.20 17.62 25.44
Total Source Energy 1741394.59 55.79 80.58
Net Source Energy 1741394.59 55.79 80.58


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 31210.83
Net Conditioned Building Area 21609.96
Unconditioned Building Area 9600.87


End Uses

Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 266.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 131094.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 38708.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 18809.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299798.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 31193.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 29986.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 330767.30
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 549856.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 330767.30
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 266.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 131094.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 38708.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 18809.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 9418.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 4809.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 22540.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 8652.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 330767.30
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 4468.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Other 25517.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 8.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.31
Other 13.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 25.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.31


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 6.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.60
Other 9.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 17.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.60


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 549856.201 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 549856.201 100.00
     
Total On-Site and Utility Electric Sources 549856.201 100.00
Total Electricity End Uses 549856.201 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 330767.30 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 330767.30 100.00
Total Water End Uses 330767.30 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 7.33
Time Setpoint Not Met During Occupied Cooling 256.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 3347.67


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR |

HEATING AND COOLING LOADS

| BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

General

Value
Program Version and Build EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:15
RunPeriod ANNUAL
Weather File Honolulu Intl Arpt HI USA TMY3 WMO#=911820
Latitude [deg] 21.32
Longitude [deg] -157.9
Elevation [ft] 6.56
Time Zone -10.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 16177.97 6115.58 1973.41 6115.58 1973.41
Above Ground Wall Area [ft2] 16177.97 6115.58 1973.41 6115.58 1973.41
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.15 8.69 26.94 8.69 26.94
Above Ground Window-Wall Ratio [%] 13.15 8.69 26.94 8.69 26.94


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
BREEZEWAY 1798.16 No Yes 30553.25 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
ATTIC 7802.71 No Yes 52795.56 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
Total 31210.83     267088.19   16177.97 0.00 2126.74 2126.74 0.4037 866.97 2.0143
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.5831 600.28 2.9092
Unconditioned Total 9600.87     83348.81   881.37 0.00 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 13-SEP-18:10 - - - - - - - - - - - 01-JAN-08:09
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 22.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 11.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 4.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 50.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 5.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 19.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.20
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 113.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.20


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 22.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 11.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 4.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 2.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 5.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 9.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 25.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 4.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 0.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.20
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Gasoline [kBtu] Source Diesel [kBtu] Source Coal [kBtu] Source Fuel Oil No 1 [kBtu] Source Fuel Oil No 2 [kBtu] Source Propane [kBtu] Source Other Fuel 1 [kBtu] Source Other Fuel 2 [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 844.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 415174.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 122590.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 59568.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 949462.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 98788.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 94966.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1741394.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 19.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 5.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 43.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 4.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 4.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 80.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 13.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 30.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 3.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 3.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 55.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

ZoneHVAC:EnergyRecoveryVentilator

User-Specified Supply Air Flow Rate [ft3/min] User-Specified Exhaust Air Flow Rate [ft3/min]
ERV_UNIT1_FRONTROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT2_FRONTROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT3_FRONTROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT1_BACKROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT2_BACKROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT3_BACKROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT1_FRONTROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT2_FRONTROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT3_FRONTROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT1_BACKROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT2_BACKROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT3_BACKROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT3_BACKROW_TOPFLOOR 44.99 44.99
ERV_UNIT3_FRONTROW_TOPFLOOR 44.99 44.99
ERV_UNIT1_FRONTROW_TOPFLOOR 44.99 44.99
ERV_UNIT2_BACKROW_TOPFLOOR 44.99 44.99
ERV_UNIT2_FRONTROW_TOPFLOOR 44.99 44.99
ERV_UNIT1_BACKROW_TOPFLOOR 44.99 44.99
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

User-Specified Maximum Flow Rate [ft3/min] Design Size Maximum Flow Rate [ft3/min]
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR 44.99  
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR   327.49
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR   163.65
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR   234.99
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR   323.36
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR   163.96
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR   234.50
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR   353.68
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR   180.45
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR   249.99
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR   350.21
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR   180.07
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR   249.01
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR   408.45
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR   232.63
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR   271.02
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR   409.96
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR   235.10
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR   269.84
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR   160.01
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

User-Specified Nominal Supply Air Flow Rate [ft3/min]
OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR 44.99
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 327.49
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 163.65
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 234.99
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 323.36
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 163.96
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 234.50
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 353.68
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 180.45
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 249.99
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 350.21
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 180.07
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 249.01
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 269.84
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 271.02
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 408.45
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 235.10
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 232.63
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 409.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] Sum of Air Terminal Maximum Flow Rates [ft3/min] Adjusted Heating Design Air Flow Rate [ft3/min] Adjusted Cooling Design Air Flow Rate [ft3/min] Adjusted Main Design Air Flow Rate [ft3/min] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 327.49 327.49 327.49 327.49 327.49 327.49 1.00 1.00 327.49
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 163.65 163.65 163.65 163.65 163.65 163.65 1.00 1.00 163.65
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 234.99 234.99 234.99 234.99 234.99 234.99 1.00 1.00 234.99
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 323.36 323.36 323.36 323.36 323.36 323.36 1.00 1.00 323.36
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 163.96 163.96 163.96 163.96 163.96 163.96 1.00 1.00 163.96
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 234.50 234.50 234.50 234.50 234.50 234.50 1.00 1.00 234.50
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 353.68 353.68 353.68 353.68 353.68 353.68 1.00 1.00 353.68
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 180.45 180.45 180.45 180.45 180.45 180.45 1.00 1.00 180.45
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 249.99 249.99 249.99 249.99 249.99 249.99 1.00 1.00 249.99
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 350.21 350.21 350.21 350.21 350.21 350.21 1.00 1.00 350.21
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 180.07 180.07 180.07 180.07 180.07 180.07 1.00 1.00 180.07
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 249.01 249.01 249.01 249.01 249.01 249.01 1.00 1.00 249.01
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 408.45 408.45 408.45 408.45 408.45 408.45 1.00 1.00 408.45
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 232.63 232.63 232.63 232.63 232.63 232.63 1.00 1.00 232.63
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 271.02 271.02 271.02 271.02 271.02 271.02 1.00 1.00 271.02
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 409.96 409.96 409.96 409.96 409.96 409.96 1.00 1.00 409.96
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 235.10 235.10 235.10 235.10 235.10 235.10 1.00 1.00 235.10
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 269.84 269.84 269.84 269.84 269.84 269.84 1.00 1.00 269.84
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 327.49 0.931505 0.754154
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 163.65 0.535393 0.706659
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 234.99 0.707799 0.734171
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 323.36 0.922367 0.753343
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 163.96 0.536674 0.706530
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 234.50 0.704570 0.734844
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 353.68 0.955195 0.773430
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 180.45 0.553258 0.727401
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 249.99 0.715357 0.751433
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 350.21 0.945657 0.773477
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 180.07 0.552785 0.727067
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 249.01 0.711043 0.753039
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 408.45 1.11 0.771317
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 232.63 0.698573 0.734994
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 271.02 0.812940 0.735295
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 409.96 1.11 0.771521
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 235.10 0.704303 0.735639
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 269.84 0.797395 0.740398
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 327.49 327.49 327.49 2963.27 0.931505 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 163.65 163.65 163.65 2963.27 0.535393 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 234.99 234.99 234.99 2963.27 0.707799 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 323.36 323.36 323.36 2963.27 0.922367 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 163.96 163.96 163.96 2963.27 0.536674 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 234.50 234.50 234.50 2963.27 0.704570 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 353.68 353.68 353.68 2963.27 0.955195 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 180.45 180.45 180.45 2963.27 0.553258 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 249.99 249.99 249.99 2963.27 0.715357 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 350.21 350.21 350.21 2963.27 0.945657 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 180.07 180.07 180.07 2963.27 0.552785 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 249.01 249.01 249.01 2963.27 0.711043 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 408.45 408.45 408.45 2963.27 1.11 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 232.63 232.63 232.63 2963.27 0.698573 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 271.02 271.02 271.02 2963.27 0.812940 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 409.96 409.96 409.96 2963.27 1.11 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 235.10 235.10 235.10 2963.27 0.704303 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 269.84 269.84 269.84 2963.27 0.797395 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [Btu/h]
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 2963.27
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 2963.27
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 2963.27
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 2963.27
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 2963.27
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 2963.27
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 2963.27
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 2963.27
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 2963.27
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 2963.27
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 2963.27
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 2963.27
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 2963.27
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 2963.27
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 2963.27
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR 2963.27
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR 2963.27
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR 2963.27
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:HeatPump:WrappedCondenser

Evaporator air flow rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 160.01
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 160.01
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 160.01
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 160.01
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 160.01
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 160.01
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 2.09
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Stratified

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR 15354.00 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

Version

Version ID
1 9.5


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes No Yes Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.200 0.200


Site:GroundTemperature:BuildingSurface

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40


Site:GroundTemperature:FCfactorMethod

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 74.71 73.44 73.09 73.40 75.11 77.04 78.85 80.17 80.55 79.93 78.44 76.57


Site:GroundTemperature:Shallow

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40


Site:GroundTemperature:Deep

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {ft} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Sensor Height Above Ground {ft} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 32.810 0.140 885.870 4.921 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {ft} Standard Pressure at Elevation {psi} Standard RhoAir at Elevation
1 Honolulu Intl Arpt HI USA TMY3 WMO#=911820 21.32 -157.93 -10.00 6.56 15. 1.2040


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{F} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} Fixed Default Water Mains Temperature{F}
1 Correlation NA 76.86 8.28 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 US+MF+CZ1AWHT+elecres+slab+IECC_2021 0.000 Suburbs 4.00000E-002 0.40000 FullExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Gradient Coefficient {F/ft}
1 0.220 1213.970 0.003566


Material Details

Material Name ThermalResistance {m2-K/w} Roughness Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} Absorptance:Thermal Absorptance:Solar Absorptance:Visible
1 SHEATHING_CONSOL_LAYER 0.1351 Rough 0.0417 9.402E-002 42.764 0.280 0.9000 0.7000 0.7000
2 CEIL_CONSOL_LAYER 4.9646 Rough 1.0053 6.172E-002 2.618 0.185 0.9000 0.7000 0.7000
3 FLOOR_CONSOL_LAYER 1.9554E-005 Rough 0.0008 12.990 3.438 0.219 0.9000 0.7000 0.7000
4 BSMTWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
5 CRAWLWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
6 WALL_CONSOL_LAYER 1.5339 Rough 0.2917 5.796E-002 7.541 0.248 0.9000 0.7000 0.7000
7 VERY HIGH REFLECTIVITY SURFACE 2.1097E-006 Smooth 0.0016 237.000 168.680 0.216 0.9000 5.0000E-002 5.0000E-002
8 GYPSUMBOARD-5/16IN 5.0054E-002 Rough 0.0260 0.159 39.954 0.270 0.9000 0.4000 0.1000
9 COPPERPIPE 4.7506E-005 MediumRough 0.0625 401.000 140.026 0.200 0.9000 0.6500 0.6500
10 F08 METAL SURFACE 1.7668E-005 Smooth 0.0026 45.280 488.437 0.119 0.9000 0.7000 0.7000
11 CONCRETE_4IN 7.7356E-002 Rough 0.3330 1.312 140.014 0.111 0.9000 0.7000 0.7000
12 ASPHALT_SHINGLE 7.7448E-002 MediumRough 0.0208 8.186E-002 70.000 0.300 0.9000 0.7500 0.7000
13 WOOD_SHINGLE 0.1115 MediumSmooth 0.0417 0.114 26.600 0.390 0.9000 0.7000 0.7000
14 SLATE_SHINGLE 8.8061E-003 MediumSmooth 0.0417 1.442 100.000 0.300 0.9000 0.7000 0.7000
15 CEMENT_STUCCO 2.6422E-002 MediumSmooth 0.0625 0.721 116.464 0.210 0.9000 0.7000 0.7000
16 SYN_STUCCO 3.5237E-002 MediumSmooth 0.0100 8.650E-002 24.971 0.210 0.9000 0.7000 0.7000
17 DRYWALL_1/2IN 7.9331E-002 MediumSmooth 0.0417 0.160 50.000 0.260 0.9000 0.7000 0.7000
18 OSB_5/8IN 0.1365 MediumSmooth 0.0521 0.116 34.000 0.290 0.9000 0.7000 0.7000
19 OSB_7/16IN 9.5550E-002 MediumSmooth 0.0365 0.116 34.000 0.290 0.9000 0.7000 0.7000
20 BLOWN_R30 5.1614 MediumRough 0.6975 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
21 BLOWN_R30_TOP 2.8489 MediumRough 0.3849 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
22 PLYWOOD_3/4IN 0.1650 Rough 0.0625 0.115 34.003 0.161 0.9000 0.7000 0.7000
23 BATT_R19 7.3089 MediumRough 0.0833 3.475E-003 0.600 0.200 0.9000 0.7000 0.7000
24 LUMBER_2X4 0.7709 Rough 0.2920 0.115 32.003 0.183 0.9000 0.7000 0.7000
25 CARPET_N_PAD 0.4224 MediumSmooth 0.0833 6.013E-002 2.000 0.200 0.9000 0.7000 0.7000
26 BATT_R13 2.2936 MediumRough 0.2917 3.876E-002 0.600 0.200 0.9000 0.7000 0.7000
27 OSB_1/2IN 0.1092 MediumSmooth 0.0417 0.116 34.000 0.290 0.9000 0.7000 0.7000
28 SOIL_12IN 0.1761 Rough 1.0000 1.731 115.011 0.056 0.9000 0.7000 0.7000
29 DOOR_CONST 0.3522 Smooth 0.0832 7.201E-002 32.003 0.183 0.9000 0.7000 0.7000
30 GYP_BOARD_1/2IN 8.0130E-002 Rough 0.0417 0.159 39.954 0.270 0.9000 0.4000 0.1000
31 STD WOOD 6INCH 1.2500 MediumSmooth 0.4921 0.120 33.711 0.289 0.9000 0.7000 0.7000
32 PIPE INSULATION 0.3830 VeryRough 0.0417 3.317E-002 5.681 0.200 0.9000 0.5000 0.5000
33 MANF_WALL_AIRGAP 0.1200 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
34 BLDG_PAPER_FELT 1.0567E-002 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
35 R_HIGH 177.0000 MediumRough 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
36 CLEAR ACRYLIC PLASTIC 3.3333E-003 VerySmooth 0.0098 0.900 0.000 0.000 0.9000 0.0000 0.0000
37 DIFFUSING ACRYLIC PLASTIC 2.4444E-003 VerySmooth 0.0072 0.900 0.000 0.000 0.9000 0.0000 0.0000
38 INT_BLIND 0.0000 Rough 0.0000 0.000 0.000 0.000 0.0000 0.0000 0.0000
39 GLASS 0.1815 VerySmooth 0.0649 0.109 0.000 0.000 0.8400 0.0000 0.0000


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 LowerLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Other Side Coefficients

Name Combined convective/radiative film coefficient {Btu/h-ft2-F} User selected Constant Temperature {F} Coefficient modifying the constant temperature term Coefficient modifying the external dry bulb temperature term Coefficient modifying the ground temperature term Coefficient modifying the wind speed term {s/m} Coefficient modifying the zone air temperature term Constant Temperature Schedule Name Sinusoidal Variation Period of Sinusoidal Variation Previous Other Side Temperature Coefficient Minimum Other Side Temperature {F} Maximum Other Side Temperature {F}
1 SURFPROPOTHSDCOEFSLABAVERAGE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABAVERAGESURFACETEMP NO 24.000 0.000 N/A N/A
2 SURFPROPOTHSDCOEFSLABPERIMETER N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABPERIMETERTEMP NO 24.000 0.000 N/A N/A
3 SURFPROPOTHSDCOEFSLABCORE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABCORETEMP NO 24.000 0.000 N/A N/A


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{F}


Surface Convection Coefficient Lower Limit {Btu/h-ft2-F}


Surface Convection Coefficient Upper Limit {Btu/h-ft2-F}


1 CTF - ConductionTransferFunction 392. 0.02 176.1


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 60


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 20 171 48


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {ft} Origin Y-Coordinate {ft} Origin Z-Coordinate {ft} Centroid X-Coordinate {ft} Centroid Y-Coordinate {ft} Centroid Z-Coordinate {ft} Type Zone Multiplier Zone List Multiplier Minimum X {ft} Maximum X {ft} Minimum Y {ft} Maximum Y {ft} Minimum Z {ft} Maximum Z {ft} Ceiling Height {ft} Volume {ft3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {ft2} Exterior Gross Wall Area {ft2} Exterior Net Wall Area {ft2} Exterior Window Area {ft2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BREEZEWAY 0.0 0.00 0.00 0.00 59.94 32.55 13.26 1 1 1 0.00 119.89 30.05 35.04 0.49 25.99 17.00 30553.07 TARP DOE-2 1798.18 0.00 0.00 0.00 4 0 0 Yes
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 4.76 1 1 1 0.00 39.96 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 4.76 1 1 1 39.96 79.93 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
4 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 4.76 1 1 1 79.93 119.89 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
5 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 4.76 1 1 1 0.00 39.96 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
6 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 4.76 1 1 1 39.96 79.93 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
7 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 4.76 1 1 1 79.93 119.89 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
8 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 13.26 1 1 1 0.00 39.96 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
9 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 13.26 1 1 1 39.96 79.93 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
10 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 13.26 1 1 1 79.93 119.89 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
11 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 13.26 1 1 1 0.00 39.96 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
12 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 13.26 1 1 1 39.96 79.93 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
13 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 13.26 1 1 1 79.93 119.89 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
14 ATTIC 0.0 -134.9 51.61 0.00 59.94 32.55 29.56 1 1 1 0.00 119.89 0.00 65.10 25.99 39.54 6.76 52795.39 TARP DOE-2 7802.66 881.33 881.33 0.00 11 0 0 Yes
15 LIVING_UNIT3_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 21.75 1 1 1 79.93 119.89 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
16 LIVING_UNIT3_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 21.75 1 1 1 79.93 119.89 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
17 LIVING_UNIT1_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 21.75 1 1 1 0.00 39.96 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
18 LIVING_UNIT2_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 21.75 1 1 1 39.96 79.93 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
19 LIVING_UNIT2_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 21.75 1 1 1 39.96 79.93 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
20 LIVING_UNIT1_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 21.75 1 1 1 0.00 39.96 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {ft2} # Occupants Area per Occupant {ft2/person} Occupant per Area {person/ft2} Interior Lighting {Btu/h-ft2} Electric Load {Btu/h-ft2} Gas Load {Btu/h-ft2} Other Load {Btu/h-ft2} Hot Water Eq {Btu/h-ft2} Steam Equipment {Btu/h-ft2} Sum Loads per Area {Btu/h-ft2} Outdoor Controlled Baseboard Heat
1 BREEZEWAY 1798.18 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
4 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
5 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
6 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
7 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
8 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
9 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
10 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
11 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
12 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
13 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
14 ATTIC 7802.66 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
15 LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
16 LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
17 LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
18 LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
19 LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
20 LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Number of People {} People/Floor Area {person/ft2} Floor Area per person {ft2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
2 PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
3 PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
4 PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
5 PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
6 PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
7 PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
8 PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
9 PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
10 PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
11 PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
12 PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
13 PEOPLE_UNIT1_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
14 PEOPLE_UNIT2_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
15 PEOPLE_UNIT3_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
16 PEOPLE_UNIT1_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
17 PEOPLE_UNIT2_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
18 PEOPLE_UNIT3_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Lighting Level {Btu/h} Lights/Floor Area {Btu/h-ft2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {Btu/h} Nominal Maximum Lighting Level {Btu/h}
1 LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
2 LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
3 LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
4 LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
5 LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
6 LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
7 LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
8 LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
9 LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
10 LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
11 LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
12 LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
13 LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
14 LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
15 LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
16 LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
17 LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
18 LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
19 LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
20 LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
21 LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
22 LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
23 LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
24 LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
25 LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
26 LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
27 LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
28 LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
29 LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
30 LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
31 LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
32 LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
33 LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
34 LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
35 LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
36 LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Equipment Level {Btu/h} Equipment/Floor Area {Btu/h-ft2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {Btu/h} Nominal Maximum Equipment Level {Btu/h}
1 DISHWASHER1_FRONTROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
2 REFRIGERATOR1_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
3 CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
4 ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
5 ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
6 TELEVISION1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
7 ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
8 IECC_ADJ1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
9 DISHWASHER2_FRONTROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
10 REFRIGERATOR2_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
11 CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
12 ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
13 ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
14 TELEVISION2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
15 ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
16 IECC_ADJ2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
17 DISHWASHER3_FRONTROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
18 REFRIGERATOR3_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
19 CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
20 ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
21 ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
22 TELEVISION3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
23 ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
24 IECC_ADJ3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
25 DISHWASHER1_BACKROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
26 REFRIGERATOR1_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
27 CLOTHESWASHER1_BACKROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
28 ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
29 ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
30 TELEVISION1_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
31 ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
32 IECC_ADJ1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
33 DISHWASHER2_BACKROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
34 REFRIGERATOR2_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
35 CLOTHESWASHER2_BACKROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
36 ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
37 ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
38 TELEVISION2_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
39 ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
40 IECC_ADJ2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
41 DISHWASHER3_BACKROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
42 REFRIGERATOR3_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
43 CLOTHESWASHER3_BACKROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
44 ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
45 ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
46 TELEVISION3_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
47 ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
48 IECC_ADJ3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
49 DISHWASHER1_FRONTROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
50 REFRIGERATOR1_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
51 CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
52 ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
53 ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
54 TELEVISION1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
55 ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
56 IECC_ADJ1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
57 DISHWASHER2_FRONTROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
58 REFRIGERATOR2_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
59 CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
60 ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
61 ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
62 TELEVISION2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
63 ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
64 IECC_ADJ2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
65 DISHWASHER3_FRONTROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
66 REFRIGERATOR3_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
67 CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
68 ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
69 ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
70 TELEVISION3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
71 ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
72 IECC_ADJ3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
73 DISHWASHER1_BACKROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
74 REFRIGERATOR1_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
75 CLOTHESWASHER1_BACKROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
76 ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
77 ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
78 TELEVISION1_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
79 ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
80 IECC_ADJ1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
81 DISHWASHER2_BACKROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
82 REFRIGERATOR2_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
83 CLOTHESWASHER2_BACKROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
84 ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
85 ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
86 TELEVISION2_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
87 ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
88 IECC_ADJ2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
89 DISHWASHER3_BACKROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
90 REFRIGERATOR3_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
91 CLOTHESWASHER3_BACKROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
92 ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
93 ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
94 TELEVISION3_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
95 ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
96 IECC_ADJ3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
97 DISHWASHER1_FRONTROW_TOPFLOOR DISHWASHER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
98 REFRIGERATOR1_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
99 CLOTHESWASHER1_FRONTROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
100 ELECTRIC_DRYER1_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
101 ELECTRIC_RANGE1_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
102 TELEVISION1_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
103 ELECTRIC_MELS1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
104 IECC_ADJ1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
105 DISHWASHER2_FRONTROW_TOPFLOOR DISHWASHER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
106 REFRIGERATOR2_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
107 CLOTHESWASHER2_FRONTROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
108 ELECTRIC_DRYER2_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
109 ELECTRIC_RANGE2_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
110 TELEVISION2_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
111 ELECTRIC_MELS2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
112 IECC_ADJ2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
113 DISHWASHER3_FRONTROW_TOPFLOOR DISHWASHER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
114 REFRIGERATOR3_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
115 CLOTHESWASHER3_FRONTROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
116 ELECTRIC_DRYER3_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
117 ELECTRIC_RANGE3_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
118 TELEVISION3_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
119 ELECTRIC_MELS3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
120 IECC_ADJ3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
121 DISHWASHER1_BACKROW_TOPFLOOR DISHWASHER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
122 REFRIGERATOR1_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
123 CLOTHESWASHER1_BACKROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
124 ELECTRIC_DRYER1_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
125 ELECTRIC_RANGE1_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
126 TELEVISION1_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
127 ELECTRIC_MELS1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
128 IECC_ADJ1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
129 DISHWASHER2_BACKROW_TOPFLOOR DISHWASHER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
130 REFRIGERATOR2_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
131 CLOTHESWASHER2_BACKROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
132 ELECTRIC_DRYER2_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
133 ELECTRIC_RANGE2_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
134 TELEVISION2_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
135 ELECTRIC_MELS2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
136 IECC_ADJ2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
137 DISHWASHER3_BACKROW_TOPFLOOR DISHWASHER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
138 REFRIGERATOR3_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
139 CLOTHESWASHER3_BACKROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
140 ELECTRIC_DRYER3_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
141 ELECTRIC_RANGE3_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
142 TELEVISION3_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
143 ELECTRIC_MELS3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
144 IECC_ADJ3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736


Construction CTF

Construction Name Index #Layers #CTFs Time Step {Hours} ThermalConductance {Btu/h-ft2-F} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 EXTERIOR WALL 1 5 10 0.167 0.0937 0.900 0.900 0.700 0.700 MediumSmooth
2 CEILING-FLOOR-LAYER 3 1 5 0.167 0.228 0.900 0.900 0.700 0.700 Rough
3 EXTERIOR FLOOR 4 3 4 0.167 0.300 0.900 0.900 0.700 0.700 Rough
4 INTERIOR CEILING 6 2 8 0.167 0.0349 0.900 0.900 0.700 0.700 Rough
5 ATTIC FLOOR 7 2 8 0.167 0.0349 0.900 0.900 0.700 0.700 MediumSmooth
6 INTERIORWALL 9 3 5 0.167 0.597 0.900 0.900 0.700 0.700 MediumSmooth
7 EXTERIOR ROOF 11 2 4 0.167 0.943 0.900 0.900 0.750 0.700 MediumRough
8 EXTERIOR DOOR 14 1 5 0.167 0.500 0.900 0.900 0.700 0.700 Smooth
9 GABLE_END 16 5 6 0.167 0.428 0.900 0.900 0.700 0.700 MediumSmooth


Material CTF Summary

Material Name Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} ThermalResistance {m2-K/w}
1 SYN_STUCCO 0.0098 0.086 24.971 0.210 0.3524E-01
2 SHEATHING_CONSOL_LAYER 0.0417 0.094 42.764 0.280 0.1351
3 OSB_7/16IN 0.0364 0.116 34.000 0.290 0.9555E-01
4 WALL_CONSOL_LAYER 0.2917 0.058 7.541 0.248 1.534
5 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
6 LUMBER_2X4 0.2920 0.115 32.003 0.183 0.7709
7 FLOOR_CONSOL_LAYER 0.0010 12.990 3.438 0.219 0.1955E-04
8 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
9 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
10 CEIL_CONSOL_LAYER 1.0053 0.062 2.618 0.185 4.965
11 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
12 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
13 CEIL_CONSOL_LAYER 1.0053 0.062 2.618 0.185 4.965
14 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
15 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
16 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
17 ASPHALT_SHINGLE 0.0207 0.082 70.000 0.300 0.7745E-01
18 OSB_1/2IN 0.0417 0.116 34.000 0.290 0.1092
19 DOOR_CONST 0.0833 0.072 32.003 0.183 0.3522
20 CEMENT_STUCCO 0.0627 0.721 116.464 0.210 0.2642E-01
21 BLDG_PAPER_FELT 0.0000 0.000 0.000 0.000 0.1057E-01
22 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
23 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


CTF

Time Outside Cross Inside Flux (except final one)
1 10 0.53690791E-10 -0.14086767E-13 0.12185568E-09 -0.56142619E-15
2 9 -0.78969438E-07 0.37271083E-11 -0.12786746E-06 0.41607738E-10
3 8 0.15644920E-04 0.57233592E-08 0.24713380E-04 -0.42390053E-07
4 7 -0.11010334E-02 0.13458163E-05 -0.17770580E-02 0.73075693E-05
5 6 0.34256138E-01 0.71913801E-04 0.57800664E-01 -0.42770275E-03
6 5 -0.50970556 0.10561809E-02 -0.91414050 0.10365322E-01
7 4 3.8008141 0.46021679E-02 7.1669335 -0.11749215
8 3 -14.731927 0.58137860E-02 -27.604869 0.65172867
9 2 29.625503 0.18019171E-02 52.431474 -1.7640469
10 1 -28.806601 0.81323549E-04 -47.206921 2.1946319
11 0 10.602175 0.49952751E-07 16.084904  
12 5 -0.10726087E-01 0.44268190E-05 -0.10726087E-01 0.97389233E-03
13 4 0.31857203 0.80150166E-03 0.31857203 -0.30727185E-01
14 3 -2.8372473 0.12516450E-01 -2.8372473 0.30041224
15 2 9.6667056 0.33176537E-01 9.6667056 -1.1584571
16 1 -13.322214 0.15207483E-01 -13.322214 1.8397512
17 0 6.2472388 0.62260140E-03 6.2472388  
18 4 0.29631924E-13 -0.40788276E-14 0.60443234E-14 -0.77798347E-16
19 3 -0.11254351E-04 0.79669069E-06 -0.23145793E-05 0.39394231E-13
20 2 0.49771861 0.29587917E-01 0.78801895E-01 -0.76025120E-05
21 1 -8.3915550 0.80192706 -1.1535996 0.21114735
22 0 9.2367617 0.51139848 2.4177143  
23 8 -0.19955962E-17 0.73322287E-16 0.22297369E-07 0.32822528E-16
24 7 -0.41677264E-07 0.10019220E-10 -0.10904919E-01 0.29209175E-07
25 6 0.51656634E-02 0.11264243E-06 0.41501785 -0.36203283E-02
26 5 -0.90145565E-01 0.13848923E-04 -4.5221814 0.64991548E-01
27 4 0.61381812 0.20608367E-03 22.362906 -0.45855939
28 3 -2.0715279 0.66281990E-03 -57.676573 1.6179231
29 2 3.6382511 0.50785658E-03 80.070402 -3.0000438
30 1 -3.1552904 0.73826575E-04 -56.558927 2.7719184
31 0 1.0611943 0.67997522E-06 15.921725  
32 8 0.22297369E-07 0.73322287E-16 -0.19955962E-17 0.32822528E-16
33 7 -0.10904919E-01 0.10019220E-10 -0.41677264E-07 0.29209175E-07
34 6 0.41501785 0.11264243E-06 0.51656634E-02 -0.36203283E-02
35 5 -4.5221814 0.13848923E-04 -0.90145565E-01 0.64991548E-01
36 4 22.362906 0.20608367E-03 0.61381812 -0.45855939
37 3 -57.676573 0.66281990E-03 -2.0715279 1.6179231
38 2 80.070402 0.50785658E-03 3.6382511 -3.0000438
39 1 -56.558927 0.73826575E-04 -3.1552904 2.7719184
40 0 15.921725 0.67997522E-06 1.0611943  
41 5 -0.27590492E-07 0.65241430E-08 -0.27590492E-07 0.17331255E-13
42 4 0.68608714E-03 0.11323974E-03 0.68608714E-03 -0.15705033E-07
43 3 -0.21538511 0.37821720E-01 -0.21538511 0.25667047E-03
44 2 5.0173519 0.62258424 5.0173519 -0.50236511E-01
45 1 -19.904252 0.86481321 -19.904252 0.58144210
46 0 16.688993 0.62060609E-01 16.688993  
47 4 0.75441920E-10 0.23883683E-10 0.47514224E-10 -0.69373194E-20
48 3 -0.33730907E-03 0.89366797E-04 -0.22574866E-03 0.77828620E-10
49 2 0.58624422 0.18542418 0.49024360 -0.17301269E-03
50 1 -11.299243 2.8799011 -8.6239668 0.15905732
51 0 15.219762 1.4410112 12.640375  
52 5 -0.12684112E-15 0.12265365E-15 -0.12677399E-15 -0.71473824E-21
53 4 0.79178029E-08 0.61809320E-08 0.79178029E-08 -0.25173083E-13
54 3 -0.59300915E-03 0.39287166E-03 -0.59300915E-03 0.15952896E-06
55 2 0.32945260 0.15279768 0.32945260 -0.17917361E-02
56 1 -5.3454172 1.4378160 -5.3454172 0.22827165
57 0 7.2128127 0.60524857 7.2128127  
58 6 0.97988530E-11 0.43917118E-12 0.24496810E-11 -0.34892153E-15
59 5 -0.75005310E-05 0.16499726E-06 -0.28271466E-05 0.19166609E-11
60 4 0.32354224E-01 0.66949565E-03 0.10283773E-01 -0.11111676E-05
61 3 -1.8201547 0.67148336E-01 -0.62076152 0.38788549E-02
62 2 21.173821 0.53241617 7.5279938 -0.97325542E-01
63 1 -64.420211 0.46601667 -21.697519 0.64629334
64 0 46.121323 0.20873329E-01 15.867130  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {Btu/h-ft2-F} SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 EXTERIOR WINDOW 12 1 VerySmooth 0.501 0.218 0.129 0.883
2 INTERIOR WINDOW 13 1 VerySmooth 0.501 0.218 0.129 0.883
3 WINDOW_W_BLINDS 18 2 VerySmooth 0.501 0.207 2.523E-002 0.133
4 TDD DOME 22 1 VerySmooth 1.071 0.929 0.920 0.920
5 TDD DIFFUSER 23 1 VerySmooth 1.077 0.906 0.900 0.900


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {ft} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLASS SpectralAverage   0.06495 0.12813 0.64406 0.64406 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.10908 1.00000 No
2 GLASS SpectralAverage   0.06495 0.12813 0.64406 0.64406 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.10908 1.00000 No
3 GLASS SpectralAverage   0.06495 0.12813 0.64406 0.64406 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.10908 1.00000 No
4 CLEAR ACRYLIC PLASTIC SpectralAverage   0.00984 0.92000 5.00000E-002 5.00000E-002 0.92000 5.00000E-002 5.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No
5 DIFFUSING ACRYLIC PLASTIC SpectralAverage   0.00722 0.90000 8.00000E-002 8.00000E-002 0.90000 8.00000E-002 8.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No


WindowMaterial:Blind

Material Name Slat Width {ft} Slat Separation {ft} Slat Thickness {ft} Slat Angle {deg} Slat Beam Solar Transmittance Slat Beam Solar Front Reflectance Blind To Glass Distance {ft}
1 INT_BLIND 0.0820 0.0615 0.0033 45.000 0.000 0.500 0.164


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 20 15000. SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Heat Pump Water Heater Information

Type Name Volume {ft3} Maximum Capacity {Btu/h} Standard Rated Recovery Efficiency Standard Rated Energy Factor "DX Coil Total Cooling Rate {W HPWH Only}"
1 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 6.9509 4510.0 0.000 0.0000 785  
2 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 6.9509 4510.0 0.000 0.0000 785  
3 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 6.9509 4510.0 0.000 0.0000 785  
4 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 6.9509 4510.0 0.000 0.0000 785  
5 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 6.9509 4510.0 0.000 0.0000 785  
6 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 6.9509 4510.0 0.000 0.0000 785  
7 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 6.9509 4510.0 0.000 0.0000 785  
8 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 6.9509 4510.0 0.000 0.0000 785  
9 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 6.9509 4510.0 0.000 0.0000 785  
10 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 6.9509 4510.0 0.000 0.0000 785  
11 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 6.9509 4510.0 0.000 0.0000 785  
12 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 6.9509 4510.0 0.000 0.0000 785  
13 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 6.9509 4510.0 0.000 0.0000 785  
14 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 6.9509 4510.0 0.000 0.0000 785  
15 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 6.9509 4510.0 0.000 0.0000 785  
16 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_TOPFLOOR 6.9509 4510.0 0.000 0.0000 785  
17 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_TOPFLOOR 6.9509 4510.0 0.000 0.0000 785  
18 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_TOPFLOOR 6.9509 4510.0 0.000 0.0000 785  


Water Heater Stratified Node Information

Node Number Height {ft} Volume {ft3} Maximum Capacity {Btu/h} Off-Cycle UA {Btu/h-F} On-Cycle UA {Btu/h-F} Number Of Inlets Number Of Outlets
1 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
2 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
3 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
4 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
5 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
6 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
7 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
8 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
9 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
10 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
11 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
12 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
13 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
14 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
15 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
16 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
17 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
18 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
2 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
3 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
4 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
5 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
6 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
7 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
8 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
9 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
10 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
11 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
12 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
13 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
14 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
15 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
16 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
17 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
18 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
19 ATTICVENT ALWAYS_AVAIL ATTIC 7802.66 0.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/person Area {ft3/min-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {psi} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{F}/Schedule Maximum Indoor Temperature{F}/Schedule Delta Temperature{F}/Schedule Minimum Outdoor Temperature{F}/Schedule Maximum Outdoor Temperature{F}/Schedule Maximum WindSpeed{ft/min}
1 VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
2 VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
3 VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
4 VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
5 VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
6 VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
7 VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
8 VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
9 VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
10 VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
11 VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
12 VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
13 VENTILATION_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
14 VENTILATION_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
15 VENTILATION_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
16 VENTILATION_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
17 VENTILATION_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
18 VENTILATION_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BREEZEWAY Mixing/Well-Stirred
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
4 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
5 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
6 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
7 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
8 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
9 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
10 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
11 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
12 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
13 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
14 ATTIC Mixing/Well-Stirred
15 LIVING_UNIT3_BACKROW_TOPFLOOR Mixing/Well-Stirred
16 LIVING_UNIT3_FRONTROW_TOPFLOOR Mixing/Well-Stirred
17 LIVING_UNIT1_FRONTROW_TOPFLOOR Mixing/Well-Stirred
18 LIVING_UNIT2_BACKROW_TOPFLOOR Mixing/Well-Stirred
19 LIVING_UNIT2_FRONTROW_TOPFLOOR Mixing/Well-Stirred
20 LIVING_UNIT1_BACKROW_TOPFLOOR Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {Btu/h} User Des Load {Btu/h} Calc Des Air Flow Rate {ft3/min} User Des Air Flow Rate {ft3/min} Design Day Name Date/Time of Peak Temperature at Peak {F} Humidity Ratio at Peak {lbWater/lbDryAir} Floor Area {ft2} # Occupants Calc Outdoor Air Flow Rate {ft3/min} Calc DOAS Heat Addition Rate {Btu/h}
1 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Cooling 7698.96274 7698.96274 327.49996 327.49996 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 87.10579 0.01437 1200.55323 2.00000 44.99491 0.00000
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Heating 375.63868 375.63868 6.83947 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 61.16000 0.01152 1200.55323 2.00000 44.99491 0.00000
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Cooling 3847.28774 3847.28774 163.65083 163.65083 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 84.97580 0.01437 1200.55323 2.00000 44.99491 0.00000
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Heating 0.00000 0.00000 0.00000 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   61.16000 0.01152 1200.55323 2.00000 44.99491 0.00000
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Cooling 5524.45644 5524.45644 234.99997 234.99997 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:50:00 86.70110 0.01437 1200.55323 2.00000 44.99491 0.00000
6 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Heating 376.96609 376.96609 6.86364 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 61.16000 0.01152 1200.55323 2.00000 44.99491 0.00000
7 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Cooling 7601.89782 7601.89782 323.36860 323.36860 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 87.10579 0.01437 1200.55323 2.00000 44.99491 0.00000
8 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Heating 382.14202 382.14202 6.95788 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 61.16000 0.01152 1200.55323 2.00000 44.99491 0.00000
9 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Cooling 3854.50068 3854.50068 163.95782 163.95782 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 84.97580 0.01437 1200.55323 2.00000 44.99491 0.00000
10 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Heating 0.00000 0.00000 0.00000 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   61.16000 0.01152 1200.55323 2.00000 44.99491 0.00000
11 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Cooling 5512.90150 5512.90150 234.49150 234.49150 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:40:00 86.38160 0.01437 1200.55323 2.00000 44.99491 0.00000
12 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Heating 377.64429 377.64429 6.87599 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 61.16000 0.01152 1200.55323 2.00000 44.99491 0.00000
13 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Cooling 8315.09883 8315.09883 353.68640 353.68640 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 86.89280 0.01437 1200.55323 2.00000 44.99491 0.00000
14 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Heating 297.70584 297.70584 5.42053 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 61.16000 0.01152 1200.55323 2.00000 44.99491 0.00000
15 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Cooling 4242.43815 4242.43815 180.45210 180.45210 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 84.97580 0.01437 1200.55323 2.00000 44.99491 0.00000
16 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Heating 0.00000 0.00000 0.00000 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   61.16000 0.01152 1200.55323 2.00000 44.99491 0.00000
17 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Cooling 5877.34988 5877.34988 249.99997 249.99997 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:00:00 87.02060 0.01437 1200.55323 2.00000 44.99491 0.00000
18 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Heating 299.88969 299.88969 5.46030 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 61.16000 0.01152 1200.55323 2.00000 44.99491 0.00000
19 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Cooling 8233.32715 8233.32715 350.21182 350.21182 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:10:00 86.57330 0.01437 1200.55323 2.00000 44.99491 0.00000
20 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Heating 303.99429 303.99429 5.53502 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 61.16000 0.01152 1200.55323 2.00000 44.99491 0.00000
21 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Cooling 4233.48824 4233.48824 180.07159 180.07159 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 84.97580 0.01437 1200.55323 2.00000 44.99491 0.00000
22 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Heating 0.00000 0.00000 0.00000 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   61.16000 0.01152 1200.55323 2.00000 44.99491 0.00000
23 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Cooling 5854.32274 5854.32274 249.00421 249.00421 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:50:00 86.70110 0.01437 1200.55323 2.00000 44.99491 0.00000
24 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Heating 299.41948 299.41948 5.45172 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 61.16000 0.01152 1200.55323 2.00000 44.99491 0.00000
25 LIVING_UNIT3_BACKROW_TOPFLOOR Cooling 6343.67676 6343.67676 269.83047 269.83047 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:10:00 86.57330 0.01437 1200.55323 2.00000 44.99491 0.00000
26 LIVING_UNIT3_BACKROW_TOPFLOOR Heating 896.48232 896.48232 16.32307 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 61.16000 0.01152 1200.55323 2.00000 44.99491 0.00000
27 LIVING_UNIT3_FRONTROW_TOPFLOOR Cooling 6371.00050 6371.00050 271.01691 271.01691 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 89.70440 0.01437 1200.55323 2.00000 44.99491 0.00000
28 LIVING_UNIT3_FRONTROW_TOPFLOOR Heating 897.80638 897.80638 16.34718 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 61.16000 0.01152 1200.55323 2.00000 44.99491 0.00000
29 LIVING_UNIT1_FRONTROW_TOPFLOOR Cooling 9602.11601 9602.11601 408.45334 408.45334 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 86.89280 0.01437 1200.55323 2.00000 44.99491 0.00000
30 LIVING_UNIT1_FRONTROW_TOPFLOOR Heating 895.84646 895.84646 16.31150 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 61.16000 0.01152 1200.55323 2.00000 44.99491 0.00000
31 LIVING_UNIT2_BACKROW_TOPFLOOR Cooling 5526.87617 5526.87617 235.10590 235.10590 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 84.97580 0.01437 1200.55323 2.00000 44.99491 0.00000
32 LIVING_UNIT2_BACKROW_TOPFLOOR Heating 185.60239 185.60239 3.37932 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:20:00 61.16000 0.01152 1200.55323 2.00000 44.99491 0.00000
33 LIVING_UNIT2_FRONTROW_TOPFLOOR Cooling 5468.94802 5468.94802 232.62709 232.62709 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 84.97580 0.01437 1200.55323 2.00000 44.99491 0.00000
34 LIVING_UNIT2_FRONTROW_TOPFLOOR Heating 183.60706 183.60706 3.34301 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:20:00 61.16000 0.01152 1200.55323 2.00000 44.99491 0.00000
35 LIVING_UNIT1_BACKROW_TOPFLOOR Cooling 9637.63111 9637.63111 409.95758 409.95758 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 86.89280 0.01437 1200.55323 2.00000 44.99491 0.00000
36 LIVING_UNIT1_BACKROW_TOPFLOOR Heating 899.95792 899.95792 16.38635 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 61.16000 0.01152 1200.55323 2.00000 44.99491 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [ft3/min] User Des Air Flow Rate [ft3/min] Design Day Name Date/Time of Peak
1 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Cooling Sensible 2396.01 327.49996 327.49996 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
2 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Heating Sensible 868.49 44.99491 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
3 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Cooling Sensible 1253.39 163.65083 163.65083 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
4 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Heating Sensible 868.49 44.99491 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
5 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Cooling Sensible 1762.31 234.99997 234.99997 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
6 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Heating Sensible 868.49 44.99491 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
7 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Cooling Sensible 2367.98 323.36860 323.36860 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
8 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Heating Sensible 868.49 44.99491 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
9 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Cooling Sensible 1255.47 163.95782 163.95782 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
10 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Heating Sensible 868.49 44.99491 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
11 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Cooling Sensible 1754.42 234.49150 234.49150 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
12 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Heating Sensible 868.49 44.99491 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
13 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Cooling Sensible 2570.87 353.68640 353.68640 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
14 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Heating Sensible 868.49 44.99491 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
15 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Cooling Sensible 1367.48 180.45210 180.45210 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
16 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Heating Sensible 868.49 44.99491 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
17 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Cooling Sensible 1868.76 249.99997 249.99997 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
18 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Heating Sensible 868.49 44.99491 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
19 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Cooling Sensible 2542.70 350.21182 350.21182 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
20 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Heating Sensible 868.49 44.99491 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
21 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Cooling Sensible 1364.89 180.07159 180.07159 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
22 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Heating Sensible 868.49 44.99491 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
23 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Cooling Sensible 1857.55 249.00421 249.00421 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
24 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Heating Sensible 868.49 44.99491 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
25 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Cooling Sensible 2942.53 408.45334 408.45334 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
26 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Heating Sensible 868.49 44.99491 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
27 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Cooling Sensible 1721.66 232.62709 232.62709 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
28 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Heating Sensible 868.49 44.99491 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
29 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Cooling Sensible 2049.66 271.01691 271.01691 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
30 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Heating Sensible 868.49 44.99491 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
31 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Cooling Sensible 2952.78 409.95758 409.95758 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
32 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Heating Sensible 868.49 44.99491 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
33 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Cooling Sensible 1738.39 235.10590 235.10590 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
34 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Heating Sensible 868.49 44.99491 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
35 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Cooling Sensible 1997.05 269.83047 269.83047 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
36 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Heating Sensible 868.49 44.99491 44.99491 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
2 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
3 Fan:OnOff OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
4 Fan:OnOff OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
5 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
6 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 327.49996
7 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
8 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
9 Fan:OnOff OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
10 Fan:OnOff OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
11 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
12 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 163.65083
13 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
14 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
15 Fan:OnOff OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
16 Fan:OnOff OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
17 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
18 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 234.99997
19 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
20 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
21 Fan:OnOff OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
22 Fan:OnOff OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
23 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
24 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 323.36860
25 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
26 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
27 Fan:OnOff OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
28 Fan:OnOff OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
29 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
30 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 163.95782
31 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
32 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
33 Fan:OnOff OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
34 Fan:OnOff OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
35 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
36 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 234.49150
37 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
38 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
39 Fan:OnOff OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
40 Fan:OnOff OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
41 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
42 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 353.68640
43 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
44 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
45 Fan:OnOff OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
46 Fan:OnOff OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
47 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
48 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 180.45210
49 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
50 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
51 Fan:OnOff OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
52 Fan:OnOff OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
53 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
54 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 249.99997
55 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
56 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
57 Fan:OnOff OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
58 Fan:OnOff OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
59 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
60 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 350.21182
61 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
62 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
63 Fan:OnOff OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
64 Fan:OnOff OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
65 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
66 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 180.07159
67 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
68 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
69 Fan:OnOff OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
70 Fan:OnOff OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
71 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
72 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 249.00421
73 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
74 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
75 Fan:OnOff OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
76 Fan:OnOff OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
77 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
78 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 269.83047
79 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
80 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
81 Fan:OnOff OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
82 Fan:OnOff OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
83 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
84 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 271.01691
85 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
86 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
87 Fan:OnOff OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
88 Fan:OnOff OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
89 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
90 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 408.45334
91 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
92 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
93 Fan:OnOff OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
94 Fan:OnOff OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
95 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
96 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 235.10590
97 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
98 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
99 Fan:OnOff OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
100 Fan:OnOff OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
101 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
102 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 232.62709
103 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
104 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
105 Fan:OnOff OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
106 Fan:OnOff OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
107 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
108 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 409.95758
109 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 327.49996
110 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 327.49996
111 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 327.49996
112 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 327.49996
113 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 327.49996
114 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 327.49996
115 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
116 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
117 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 163.65083
118 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 163.65083
119 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 163.65083
120 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 163.65083
121 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 163.65083
122 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 163.65083
123 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
124 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
125 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 234.99997
126 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 234.99997
127 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 234.99997
128 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 234.99997
129 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 234.99997
130 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 234.99997
131 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
132 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
133 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 323.36860
134 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 323.36860
135 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 323.36860
136 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 323.36860
137 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 323.36860
138 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 323.36860
139 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
140 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
141 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 163.95782
142 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 163.95782
143 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 163.95782
144 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 163.95782
145 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 163.95782
146 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 163.95782
147 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
148 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
149 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 234.49150
150 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 234.49150
151 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 234.49150
152 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 234.49150
153 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 234.49150
154 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 234.49150
155 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
156 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
157 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 353.68640
158 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 353.68640
159 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 353.68640
160 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 353.68640
161 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 353.68640
162 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 353.68640
163 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
164 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
165 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 180.45210
166 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 180.45210
167 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 180.45210
168 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 180.45210
169 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 180.45210
170 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 180.45210
171 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
172 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
173 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 249.99997
174 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 249.99997
175 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 249.99997
176 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 249.99997
177 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 249.99997
178 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 249.99997
179 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
180 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
181 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 350.21182
182 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 350.21182
183 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 350.21182
184 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 350.21182
185 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 350.21182
186 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 350.21182
187 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
188 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
189 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 180.07159
190 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 180.07159
191 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 180.07159
192 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 180.07159
193 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 180.07159
194 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 180.07159
195 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
196 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
197 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 249.00421
198 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 249.00421
199 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 249.00421
200 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 249.00421
201 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 249.00421
202 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 249.00421
203 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
204 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
205 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 408.45334
206 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 408.45334
207 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 408.45334
208 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 408.45334
209 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 408.45334
210 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 408.45334
211 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
212 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
213 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 232.62709
214 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 232.62709
215 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 232.62709
216 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 232.62709
217 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 232.62709
218 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 232.62709
219 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
220 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
221 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 271.01691
222 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 271.01691
223 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 271.01691
224 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 271.01691
225 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 271.01691
226 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 271.01691
227 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
228 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
229 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 409.95758
230 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 409.95758
231 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 409.95758
232 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 409.95758
233 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 409.95758
234 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 409.95758
235 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
236 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
237 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 235.10590
238 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 235.10590
239 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 235.10590
240 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 235.10590
241 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 235.10590
242 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 235.10590
243 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
244 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
245 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 269.83047
246 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 269.83047
247 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 269.83047
248 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 269.83047
249 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 269.83047
250 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 269.83047
251 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
252 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
253 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 327.49996
254 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 163.65083
255 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 234.99997
256 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 323.36860
257 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 163.95782
258 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 234.49150
259 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 353.68640
260 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 180.45210
261 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 249.99997
262 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 350.21182
263 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 180.07159
264 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 249.00421
265 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 408.45334
266 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 232.62709
267 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 271.01691
268 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 409.95758
269 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 235.10590
270 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 269.83047
271 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 327.49996
272 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.93151
273 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.75415
274 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 327.49996
275 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 327.49996
276 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 327.49996
277 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 2963.27307
278 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.93151
279 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
280 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 327.49996
281 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 2963.27307
282 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 163.65083
283 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.53539
284 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70666
285 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 163.65083
286 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 163.65083
287 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 163.65083
288 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 2963.27307
289 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.53539
290 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
291 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 163.65083
292 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 2963.27307
293 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 234.99997
294 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.70780
295 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73417
296 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 234.99997
297 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 234.99997
298 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 234.99997
299 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 2963.27307
300 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.70780
301 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
302 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 234.99997
303 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 2963.27307
304 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 323.36860
305 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.92237
306 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.75334
307 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 323.36860
308 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 323.36860
309 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 323.36860
310 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 2963.27307
311 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.92237
312 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
313 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 323.36860
314 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 2963.27307
315 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 163.95782
316 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.53667
317 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70653
318 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 163.95782
319 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 163.95782
320 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 163.95782
321 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 2963.27307
322 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.53667
323 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
324 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 163.95782
325 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 2963.27307
326 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 234.49150
327 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.70457
328 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73484
329 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 234.49150
330 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 234.49150
331 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 234.49150
332 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 2963.27307
333 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.70457
334 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
335 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 234.49150
336 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 2963.27307
337 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 353.68640
338 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.95519
339 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.77343
340 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 353.68640
341 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 353.68640
342 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 353.68640
343 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 2963.27307
344 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.95519
345 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
346 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 353.68640
347 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 2963.27307
348 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 180.45210
349 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.55326
350 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.72740
351 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 180.45210
352 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 180.45210
353 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 180.45210
354 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 2963.27307
355 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.55326
356 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
357 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 180.45210
358 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 2963.27307
359 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 249.99997
360 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.71536
361 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.75143
362 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 249.99997
363 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 249.99997
364 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 249.99997
365 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 2963.27307
366 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.71536
367 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
368 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 249.99997
369 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 2963.27307
370 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 350.21182
371 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.94566
372 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.77348
373 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 350.21182
374 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 350.21182
375 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 350.21182
376 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 2963.27307
377 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.94566
378 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
379 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 350.21182
380 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 2963.27307
381 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 180.07159
382 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.55279
383 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.72707
384 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 180.07159
385 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 180.07159
386 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 180.07159
387 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 2963.27307
388 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.55279
389 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
390 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 180.07159
391 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 2963.27307
392 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 249.00421
393 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.71104
394 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.75304
395 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 249.00421
396 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 249.00421
397 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 249.00421
398 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 2963.27307
399 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.71104
400 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
401 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 249.00421
402 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 2963.27307
403 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 408.45334
404 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.11085
405 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.77132
406 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 408.45334
407 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 408.45334
408 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 408.45334
409 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 2963.27307
410 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.11085
411 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
412 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 408.45334
413 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 2963.27307
414 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 232.62709
415 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.69857
416 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73499
417 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 232.62709
418 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 232.62709
419 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 232.62709
420 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 2963.27307
421 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.69857
422 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
423 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 232.62709
424 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 2963.27307
425 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 271.01691
426 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.81294
427 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73530
428 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 271.01691
429 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 271.01691
430 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 271.01691
431 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 2963.27307
432 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.81294
433 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
434 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 271.01691
435 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 2963.27307
436 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 409.95758
437 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.11421
438 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.77152
439 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 409.95758
440 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 409.95758
441 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 409.95758
442 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 2963.27307
443 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.11421
444 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
445 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 409.95758
446 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 2963.27307
447 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 235.10590
448 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.70430
449 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73564
450 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 235.10590
451 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 235.10590
452 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 235.10590
453 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 2963.27307
454 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.70430
455 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
456 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 235.10590
457 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 2963.27307
458 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 269.83047
459 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.79739
460 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.74040
461 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 269.83047
462 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 269.83047
463 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 269.83047
464 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 2963.27307
465 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.79739
466 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
467 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 269.83047
468 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 2963.27307
469 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
470 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
471 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
472 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
473 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
474 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
475 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
476 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
477 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
478 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
479 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
480 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
481 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
482 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
483 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
484 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
485 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
486 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
487 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
488 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
489 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
490 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
491 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
492 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
493 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
494 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
495 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
496 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
497 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
498 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
499 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
500 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
501 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
502 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
503 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
504 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
505 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
506 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
507 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
508 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
509 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
510 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
511 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
512 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
513 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
514 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
515 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
516 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
517 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
518 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
519 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
520 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
521 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
522 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
523 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
524 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
525 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
526 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
527 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
528 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
529 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
530 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
531 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
532 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
533 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
534 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
535 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
536 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
537 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
538 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
539 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
540 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
541 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
542 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
543 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
544 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
545 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
546 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
547 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
548 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
549 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
550 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
551 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
552 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
553 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
554 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
555 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
556 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
557 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
558 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
559 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
560 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
561 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
562 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
563 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
564 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
565 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
566 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
567 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
568 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
569 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
570 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
571 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
572 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
573 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
574 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
575 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
576 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
577 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
578 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
579 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
580 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
581 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
582 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
583 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
584 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
585 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
586 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
587 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
588 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
589 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
590 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
591 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
592 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
593 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
594 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {ton} Standard Rated Net COP {Btuh/Btuh} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 0.9 3.41 11.65 12.35 11.87 12.12
2 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 0.5 3.49 11.91 12.64 12.15 12.56
3 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 0.7 3.45 11.76 12.47 11.99 12.30
4 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 0.9 3.41 11.65 12.36 11.88 12.13
5 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 0.5 3.49 11.91 12.64 12.15 12.56
6 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 0.7 3.44 11.75 12.47 11.98 12.30
7 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 0.9 3.38 11.54 12.24 11.76 11.95
8 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 0.5 3.45 11.79 12.51 12.02 12.36
9 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 0.7 3.42 11.66 12.37 11.89 12.14
10 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 0.9 3.38 11.54 12.24 11.76 11.95
11 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 0.5 3.46 11.79 12.51 12.03 12.36
12 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 0.7 3.42 11.65 12.36 11.88 12.13
13 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 1.1 3.39 11.56 12.25 11.78 11.97
14 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 0.7 3.44 11.75 12.47 11.98 12.29
15 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 0.8 3.44 11.75 12.46 11.98 12.29
16 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 1.1 3.39 11.56 12.25 11.78 11.97
17 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 0.7 3.44 11.75 12.46 11.98 12.29
18 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 0.8 3.43 11.72 12.43 11.95 12.24


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB SizingPeriod:DesignDay 02/21 02/21 WinterDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
2 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB SizingPeriod:DesignDay 08/21 08/21 SummerDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
3 ANNUAL WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day Yes Yes No Yes Yes Clark and Allen


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 No SizingPeriod:DesignDay    
2 No SizingPeriod:DesignDay    
3 No      


Environment:WarmupDays

NumberofWarmupDays
1 25
2 6
3 25


Environment:Design Day Data

Max Dry-Bulb Temp {F} Temp Range {dC} Temp Range Ind Type Hum Ind Type Hum Ind Value at Max Temp Hum Ind Units Pressure {psi} Wind Direction {deg CW from N} Wind Speed {ft/min} Clearness Rain Snow
1 61.16 0.00 DefaultMultipliers Wetbulb 16.20 {C} 15. 320 374.0 0.00 No No
2 89.96 7.10 DefaultMultipliers Wetbulb 23.30 {C} 15. 60 1319.0 0.00 No No


Environment:Design Day Misc

DayOfYear ASHRAE A Coeff ASHRAE B Coeff ASHRAE C Coeff Solar Constant-Annual Variation Eq of Time {minutes} Solar Declination Angle {deg} Solar Model
1 52 1214.6 0.1445 6.0579E-002 1.0 -13.80 -11. ASHRAEClearSky
2 233 1106.3 0.2000 0.1216 1.0 -3.33 12.4 ASHRAETau


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaF} Std Dev Warmup Temperature Difference {deltaF} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {Btu/h} Std Dev Warmup Load Difference {Btu/h} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BREEZEWAY SizingPeriod: HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 0.000010417 0.000006236 Pass Pass 0.000000000 0.000000000 Pass Pass
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 0.063264984 0.064123217 Pass Pass 0.234920E+02 0.265597E+03 Fail Pass
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 0.091086552 0.115612499 Pass Pass 1.621262157 5.469911605 Fail Pass
4 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 0.066214461 0.063617171 Pass Pass 3.311571100 0.250660E+02 Fail Pass
5 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 0.063390968 0.065539386 Pass Pass 3.576387978 0.207705E+02 Fail Pass
6 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 0.091753725 0.115743230 Pass Pass 1.595360675 5.434009900 Fail Pass
7 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 0.066283769 0.063667002 Pass Pass 3.089914937 0.225273E+02 Fail Pass
8 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 0.057806791 0.062143247 Pass Pass 2.770344561 0.134051E+02 Fail Pass
9 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 0.089379956 0.126253590 Pass Pass 1.658302425 3.290991761 Fail Pass
10 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 0.058099069 0.062804802 Pass Pass 2.556478542 0.128208E+02 Fail Pass
11 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 0.058803504 0.063513942 Pass Pass 1.943187425 0.981341E+01 Fail Pass
12 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 0.089696593 0.126440148 Pass Pass 1.619038195 3.265580791 Fail Pass
13 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 0.058525924 0.063208263 Pass Pass 0.137779E+02 0.132483E+03 Fail Pass
14 ATTIC SizingPeriod: HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 0.000206727 0.000180996 Pass Pass 0.000000000 0.000000000 Pass Pass
15 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 0.043501687 0.077652794 Pass Pass 2.415625187 0.122031E+02 Fail Fail
16 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 0.045775880 0.093476595 Pass Pass 1.895693633 0.100701E+02 Fail Fail
17 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 0.035463916 0.065217124 Pass Pass 2.695993401 0.168255E+02 Pass Fail
18 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 0.051358363 0.054906658 Pass Pass 2.162984945 8.854297072 Fail Pass
19 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 0.051363316 0.054847058 Pass Pass 2.169309553 8.795431216 Fail Pass
20 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 0.035616892 0.065443075 Pass Pass 2.496456768 0.151944E+02 Pass Fail
21 BREEZEWAY SizingPeriod: HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.265625448 0.153778281 Pass Pass 0.000000000 0.000000000 Pass Pass
22 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000692211 0.003921402 Pass Pass 0.084683254 0.050889329 Pass Pass
23 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.006313345 0.018821889 Pass Pass 0.058301439 0.064678164 Pass Pass
24 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000645211 0.004750970 Pass Pass 0.066131620 0.075677392 Pass Pass
25 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000746327 0.004601446 Pass Pass 0.083441797 0.051730766 Pass Pass
26 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.005291874 0.016391021 Pass Pass 0.054480729 0.057647360 Pass Pass
27 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000562075 0.004198947 Pass Pass 0.065884573 0.076751860 Pass Pass
28 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000617863 0.003449419 Pass Pass 0.079535994 0.041890331 Pass Pass
29 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.004405789 0.016177695 Pass Pass 0.050831925 0.056741105 Pass Pass
30 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000523993 0.002276818 Pass Pass 0.060075505 0.065620762 Pass Pass
31 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000739951 0.003909877 Pass Pass 0.078151691 0.042096600 Pass Pass
32 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.003740078 0.013497130 Pass Pass 0.050386495 0.051619123 Pass Pass
33 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000370667 0.001700930 Pass Pass 0.060044440 0.066478981 Pass Pass
34 ATTIC SizingPeriod: HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.341456988 0.271556557 Pass Pass 0.000000000 0.000000000 Pass Pass
35 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.004057018 0.010705060 Pass Pass 0.064187180 0.069453255 Pass Pass
36 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.001356762 0.004011727 Pass Pass 0.061507606 0.064710671 Pass Pass
37 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000362876 0.002109810 Pass Pass 0.082652715 0.038505764 Pass Pass
38 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.001657602 0.007825239 Pass Pass 0.056664015 0.038501079 Pass Pass
39 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.001708100 0.007217303 Pass Pass 0.056618772 0.040193731 Pass Pass
40 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000360150 0.001953959 Pass Pass 0.082552753 0.038094266 Pass Pass
41 BREEZEWAY RunPeriod: ANNUAL 0.304903434 0.219743960 Pass Pass 0.000000000 0.000000000 Pass Pass
42 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.050235284 0.140027017 Pass Pass 0.253759557 0.646752012 Pass Pass
43 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.044001398 0.130417286 Pass Fail 0.284017209 0.657699653 Pass Fail
44 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.030200883 0.088059334 Pass Fail 0.156497719 0.282300367 Pass Pass
45 LIVING_UNIT1_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.064860152 0.178285248 Pass Pass 0.493609105 2.136314082 Fail Pass
46 LIVING_UNIT2_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.065308417 0.181186109 Pass Pass 0.450099429 2.183222052 Pass Pass
47 LIVING_UNIT3_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.036132603 0.098966541 Pass Fail 0.212897154 0.714377438 Pass Pass
48 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.013631532 0.080834679 Pass Fail 0.173737645 0.279210987 Pass Pass
49 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.029224592 0.093267436 Pass Fail 0.115146258 0.164761430 Pass Fail
50 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.012368540 0.044288667 Pass Fail 0.143869675 0.202644982 Pass Fail
51 LIVING_UNIT1_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.030851633 0.147446231 Pass Pass 0.413129657 2.627126173 Pass Pass
52 LIVING_UNIT2_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.036215445 0.149848740 Pass Pass 0.417072809 3.095880432 Fail Pass
53 LIVING_UNIT3_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.003793021 0.018399351 Pass Fail 0.121178554 0.172317657 Pass Pass
54 ATTIC RunPeriod: ANNUAL 0.514316953 0.534666536 Pass Pass 0.000000000 0.000000000 Pass Pass
55 LIVING_UNIT3_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.007314921 0.027695742 Pass Fail 0.124024897 0.254342537 Pass Pass
56 LIVING_UNIT3_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.013147481 0.046534318 Pass Fail 0.135470282 0.266755493 Pass Fail
57 LIVING_UNIT1_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.022592454 0.101314496 Pass Fail 0.188315903 0.341749997 Pass Pass
58 LIVING_UNIT2_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.027415003 0.144977460 Pass Pass 0.393134919 2.779922256 Pass Pass
59 LIVING_UNIT2_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.015913411 0.082999937 Pass Fail 0.150895872 0.248017007 Pass Pass
60 LIVING_UNIT1_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.037433251 0.156425908 Pass Pass 0.449645223 2.574220828 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [kBtu] 2895757.84 112324.76 0.00 0.00 709063.89 3717162.87



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 61.16 0.00 61.16 Wetbulb [F] 374.03 320.00
HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 89.96 12.78 73.94 Wetbulb [F] 1318.96 60.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.226 0.300 599.39 599.39 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.226 0.300 599.39 599.39 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.226 0.300 599.39 599.39 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S


Opaque Interior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BREEZEWAYROOF INTERIOR CEILING 0.30 0.033 0.035 599.39 599.39 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.212 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.212 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.212 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.212 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.212 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.212 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
iz-BREEZEWAYROOF ATTIC FLOOR 0.30 0.033 0.035 599.39 599.39 0.00 180.00  
iz-CEILING_UNIT3_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.033 0.035 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.033 0.035 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.033 0.035 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.033 0.035 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.033 0.035 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.033 0.035 1200.55 1200.55 0.00 180.00  
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.033 0.035 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.033 0.035 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.033 0.035 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.033 0.035 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.033 0.035 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.033 0.035 1200.55 1200.55 180.00 0.00  


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.218 0.883     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.218 0.883     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.218 0.883     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.218 0.883     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.218 0.883     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.218 0.883     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.218 0.883     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.218 0.883     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.218 0.883     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.218 0.883     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.218 0.883     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.218 0.883     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.218 0.883     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.218 0.883     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.218 0.883     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.218 0.883     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.218 0.883     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.218 0.883     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.218 0.883     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.218 0.883     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.218 0.883     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.218 0.883     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.218 0.883     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.218 0.883     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.218 0.883     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.218 0.883     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.218 0.883     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.218 0.883     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.218 0.883     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.218 0.883     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.501 0.218 0.883              
North Total or Average           531.68 0.501 0.218 0.883              
Non-North Total or Average           1595.05 0.501 0.218 0.883              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR


Interior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 0.99 0.98 0.98 0.00 0.00 0.00 1.00 0.99 0.99
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 0.99 0.98 0.98 0.00 0.00 0.00 1.00 0.99 0.99
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 0.99 0.98 0.98 0.00 0.00 0.00 1.00 0.99 0.99
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 0.97 0.00 0.99 0.96 0.00 1.00 0.97 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.97 0.82 0.92 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.97 0.82 0.92 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 0.97 0.00 0.99 0.96 0.00 1.00 0.97 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.97 0.82 0.92 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 0.99 0.98 0.98 0.00 0.00 0.00 1.00 0.99 0.99
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 0.99 0.98 0.98 0.00 0.00 0.00 1.00 0.99 0.99
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 0.99 0.98 0.98 0.00 0.00 0.00 1.00 0.99 0.99
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 0.97 0.00 0.99 0.96 0.00 1.00 0.97 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.97 0.82 0.92 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.97 0.82 0.92 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 0.97 0.00 0.99 0.96 0.00 1.00 0.97 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.97 0.82 0.92 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 0.97 0.00 0.99 0.96 0.00 1.00 0.97 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.97 0.82 0.92 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 0.99 0.98 0.98 0.00 0.00 0.00 1.00 0.99 0.99
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 0.97 0.00 0.99 0.96 0.00 1.00 0.97 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 0.99 0.98 0.98 0.00 0.00 0.00 1.00 0.99 0.99
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.97 0.82 0.92 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 0.99 0.98 0.98 0.00 0.00 0.00 1.00 0.99 0.99
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.97 0.82 0.92 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.2915 43219.92 12599.76               11336.81


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
Exterior Lighting Total 1257.69           5508.71



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   11178.07 8429.99 2748.08 0.75 4.07    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   6424.71 4540.08 1884.63 0.71 4.07    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   8493.59 6235.75 2257.84 0.73 4.07    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   11068.40 8338.31 2730.09 0.75 4.07    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   6440.09 4550.12 1889.97 0.71 4.07    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   8454.84 6212.99 2241.85 0.73 4.07    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   11462.34 8865.32 2597.02 0.77 4.07    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   6639.10 4829.29 1809.81 0.73 4.07    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8584.29 6450.51 2133.77 0.75 4.07    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   11347.89 8777.33 2570.56 0.77 4.07    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   6633.42 4822.94 1810.48 0.73 4.07    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8532.51 6425.32 2107.19 0.75 4.07    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13330.25 10281.85 3048.41 0.77 4.07    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   8382.87 6161.36 2221.51 0.73 4.07    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   9755.28 7173.01 2582.27 0.74 4.07    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13370.48 10315.60 3054.88 0.77 4.07    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   8451.63 6217.35 2234.28 0.74 4.07    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   9568.74 7084.68 2484.06 0.74 4.07    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   0.9 3.41 11.65 12.35 11.87 12.12
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.5 3.49 11.91 12.64 12.15 12.56
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.7 3.45 11.76 12.47 11.99 12.30
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   0.9 3.41 11.65 12.36 11.88 12.13
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.5 3.49 11.91 12.64 12.15 12.56
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.7 3.44 11.75 12.47 11.98 12.30
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   0.9 3.38 11.54 12.24 11.76 11.95
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.5 3.45 11.79 12.51 12.02 12.36
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.7 3.42 11.66 12.37 11.89 12.14
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   0.9 3.38 11.54 12.24 11.76 11.95
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.5 3.46 11.79 12.51 12.03 12.36
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.7 3.42 11.65 12.36 11.88 12.13
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.1 3.39 11.56 12.25 11.78 11.97
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.7 3.44 11.75 12.47 11.98 12.29
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   0.8 3.44 11.75 12.46 11.98 12.29
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.1 3.39 11.56 12.25 11.78 11.97
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.7 3.44 11.75 12.46 11.98 12.29
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   0.8 3.43 11.72 12.43 11.95 12.24
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   2963.27 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   2963.27 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   2963.27 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   2963.27 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   2963.27 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   2963.27 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   2963.27 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   2963.27 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   2963.27 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   2963.27 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   2963.27 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   2963.27 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric   2963.27 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric   2963.27 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric   2963.27 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric   2963.27 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric   2963.27 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric   2963.27 1.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 327.49 123.53 0.38 1.00 2.63 General HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 163.65 61.73 0.38 1.00 4.03 General HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 234.99 88.64 0.38 1.00 3.19 General HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 323.36 121.97 0.38 1.00 2.65 General HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 163.96 61.84 0.38 1.00 4.03 General HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 234.50 88.45 0.38 1.00 3.19 General HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 353.68 133.41 0.38 1.00 2.53 General HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 180.45 68.07 0.38 1.00 3.77 General HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 249.99 94.29 0.38 1.00 3.07 General HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 350.21 132.10 0.38 1.00 2.54 General HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 180.07 67.92 0.38 1.00 3.78 General HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 249.01 93.93 0.38 1.00 3.08 General HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 408.45 154.06 0.38 1.00 2.35 General HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 232.63 87.75 0.38 1.00 3.21 General HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 271.02 102.23 0.38 1.00 2.93 General HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 409.96 154.63 0.38 1.00 2.35 General HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 235.10 88.68 0.38 1.00 3.19 General HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 269.84 101.78 0.38 1.00 2.93 General HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    


Pumps

Type Control Head [psi] Water Flow [gal/min] Electricity Rate [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh] End Use Subcategory
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4510.26 1.00 0.00 0.00
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4510.26 1.00 0.00 0.00
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4510.26 1.00 0.00 0.00
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4510.26 1.00 0.00 0.00
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4510.26 1.00 0.00 0.00
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4510.26 1.00 0.00 0.00
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4510.26 1.00 0.00 0.00
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4510.26 1.00 0.00 0.00
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4510.26 1.00 0.00 0.00
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4510.26 1.00 0.00 0.00
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4510.26 1.00 0.00 0.00
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4510.26 1.00 0.00 0.00
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4510.26 1.00 0.00 0.00
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4510.26 1.00 0.00 0.00
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4510.26 1.00 0.00 0.00
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4510.26 1.00 0.00 0.00
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4510.26 1.00 0.00 0.00
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4510.26 1.00 0.00 0.00



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 7698.96 7698.96 6.41 327.491 327.491 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 75.00 75.00 0.00904 87.11 0.01437 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3847.29 3847.29 3.20 163.651 163.651 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 75.00 75.00 0.00976 84.98 0.01437 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5524.46 5524.46 4.60 234.991 234.991 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:50:00 75.00 75.00 0.00919 86.70 0.01437 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 7601.90 7601.90 6.33 323.362 323.362 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 75.00 75.00 0.00905 87.11 0.01437 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3854.50 3854.50 3.21 163.958 163.958 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 75.00 75.00 0.00977 84.98 0.01437 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5512.90 5512.90 4.59 234.500 234.500 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:40:00 75.00 75.00 0.00920 86.38 0.01437 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8315.10 8315.10 6.93 353.684 353.684 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 75.00 75.00 0.00866 86.89 0.01437 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4242.44 4242.44 3.53 180.452 180.452 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 75.00 75.00 0.00908 84.98 0.01437 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5877.35 5877.35 4.90 249.991 249.991 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:00:00 75.00 75.00 0.00870 87.02 0.01437 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8233.33 8233.33 6.86 350.207 350.207 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:10:00 75.00 75.00 0.00867 86.57 0.01437 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4233.49 4233.49 3.53 180.072 180.072 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 75.00 75.00 0.00909 84.98 0.01437 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5854.32 5854.32 4.88 249.012 249.012 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:50:00 75.00 75.00 0.00871 86.70 0.01437 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 6343.68 6343.68 5.28 269.841 269.841 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:10:00 75.00 75.00 0.00922 86.57 0.01437 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 6371.00 6371.00 5.31 271.017 271.017 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 75.00 75.00 0.00906 89.70 0.01437 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 9602.12 9602.12 8.00 408.446 408.446 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 75.00 75.00 0.00888 86.89 0.01437 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 5526.88 5526.88 4.60 235.096 235.096 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 75.00 75.00 0.00933 84.98 0.01437 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 5468.95 5468.95 4.56 232.632 232.632 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 75.00 75.00 0.00934 84.98 0.01437 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 9637.63 9637.63 8.03 409.957 409.957 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 75.00 75.00 0.00888 86.89 0.01437 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 375.64 375.64 0.31 6.839 44.995 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 72.00 72.00 0.01350 61.16 0.01152 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.000 44.995 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   32.00 72.00 0.00800 61.16 0.01152 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 376.97 376.97 0.31 6.864 44.995 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 72.00 72.00 0.01350 61.16 0.01152 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 382.14 382.14 0.32 6.958 44.995 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 72.00 72.00 0.01348 61.16 0.01152 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.000 44.995 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   32.00 72.00 0.00800 61.16 0.01152 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 377.64 377.64 0.31 6.876 44.995 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 72.00 72.00 0.01350 61.16 0.01152 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 297.71 297.71 0.25 5.421 44.995 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 72.00 72.00 0.01584 61.16 0.01152 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.000 44.995 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   32.00 72.00 0.00800 61.16 0.01152 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 299.89 299.89 0.25 5.460 44.995 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 72.00 72.00 0.01583 61.16 0.01152 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 303.99 303.99 0.25 5.535 44.995 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 72.00 72.00 0.01582 61.16 0.01152 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.000 44.995 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   32.00 72.00 0.00800 61.16 0.01152 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 299.42 299.42 0.25 5.452 44.995 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 72.00 72.00 0.01583 61.16 0.01152 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 896.48 896.48 0.75 16.323 44.995 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 72.00 72.00 0.01188 61.16 0.01152 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 897.81 897.81 0.75 16.347 44.995 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 72.00 72.00 0.01188 61.16 0.01152 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 895.85 895.85 0.75 16.311 44.995 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 72.00 72.00 0.01188 61.16 0.01152 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 185.60 185.60 0.15 3.379 44.995 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:20:00 72.00 72.00 0.01468 61.16 0.01152 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 183.61 183.61 0.15 3.343 44.995 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:20:00 72.00 72.00 0.01469 61.16 0.01152 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 899.96 899.96 0.75 16.386 44.995 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 15:00:00 72.00 72.00 0.01187 61.16 0.01152 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min] Adjusted cooling [ft3/min] Adjusted heating [ft3/min] Adjusted main [ft3/min] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 327.49 327.49 44.99 44.99 327.4907 327.4907 327.4907 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 163.65 163.65 44.99 44.99 163.6507 163.6507 163.6507 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 234.99 234.99 44.99 44.99 234.9909 234.9909 234.9909 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 323.36 323.36 44.99 44.99 323.3620 323.3620 323.3620 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 163.96 163.96 44.99 44.99 163.9578 163.9578 163.9578 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 234.50 234.50 44.99 44.99 234.4996 234.4996 234.4996 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 353.68 353.68 44.99 44.99 353.6840 353.6840 353.6840 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 180.45 180.45 44.99 44.99 180.4521 180.4521 180.4521 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 249.99 249.99 44.99 44.99 249.9911 249.9911 249.9911 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 350.21 350.21 44.99 44.99 350.2065 350.2065 350.2065 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 180.07 180.07 44.99 44.99 180.0716 180.0716 180.0716 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 249.01 249.01 44.99 44.99 249.0118 249.0118 249.0118 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 408.45 408.45 44.99 44.99 408.4462 408.4462 408.4462 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 232.63 232.63 44.99 44.99 232.6318 232.6318 232.6318 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 271.02 271.02 44.99 44.99 271.0174 271.0174 271.0174 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 409.96 409.96 44.99 44.99 409.9570 409.9570 409.9570 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 235.10 235.10 44.99 44.99 235.0960 235.0960 235.0960 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 269.84 269.84 44.99 44.99 269.8406 269.8406 269.8406 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 11178.066 8429.986 327.490654 -999. -999.00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:40:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 11126.55 8562.19 327.490654 77.83 64.31 0.00976954 53.60 52.26 0.00800000 87.11 0.01436870 73.20 13.7393 75.00 0.00902743 48.8784 7696.97 0.00 11182.73 8427.42
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 2963.273 2963.273 -999. -999. -999.00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 2963.27 2963.27 327.490654 70.51 66.81 0.01323172 122.00 75.17 0.00800000 61.16 0.01151798 61.16 13.7393 32.00 0.00000000 0.2665 375.64 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 6424.713 4540.081 163.650727 -999. -999.00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:20:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 6107.66 4092.47 163.650727 78.91 66.45 0.01102599 53.60 52.26 0.00800000 84.98 0.01436657 72.60 27.4945 75.00 0.00971569 52.5473 3812.93 0.00 6427.39 4538.74
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 2963.273 2963.273 -999. -999. -999.00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 2963.27 2963.27 163.650727 69.02 60.00 0.00896725 122.00 75.17 0.00800000 61.16 0.01151798 61.16 27.4945 32.00 0.00000000 0.2665 0.00 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 8493.591 6235.746 234.990949 -999. -999.00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:50:00 8335.15 6119.89 234.990949 78.41 65.10 0.01018458 53.60 52.26 0.00800000 86.70 0.01436830 73.09 19.1475 75.00 0.00919041 49.7474 5514.14 0.00 8497.13 6233.12
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 2963.273 2963.273 -999. -999. -999.00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 2963.27 2963.27 234.990949 69.93 66.47 0.01312042 122.00 75.17 0.00800000 61.16 0.01151798 61.16 19.1475 32.00 0.00000000 0.2665 376.97 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 11068.401 8338.307 323.362037 -999. -999.00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 11011.60 8453.46 323.362037 77.85 64.35 0.00978937 53.60 52.26 0.00800000 87.11 0.01436870 73.20 13.9147 75.00 0.00904917 48.9945 7601.90 0.00 11073.02 8334.79
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 2963.273 2963.273 -999. -999. -999.00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 2963.27 2963.27 323.362037 70.49 66.77 0.01320951 122.00 75.17 0.00800000 61.16 0.01151798 61.16 13.9147 32.00 0.00000000 0.2665 382.14 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 6440.089 4550.118 163.957844 -999. -999.00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 6121.48 4098.45 163.957844 78.90 66.46 0.01103275 53.60 52.26 0.00800000 84.98 0.01436657 72.60 27.4430 75.00 0.00976403 52.8047 3848.02 0.00 6442.78 4548.69
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 2963.273 2963.273 -999. -999. -999.00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 2963.27 2963.27 163.957844 69.03 60.00 0.00896544 122.00 75.17 0.00800000 61.16 0.01151798 61.16 27.4430 32.00 0.00000000 0.2665 0.00 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 8454.839 6212.988 234.499587 -999. -999.00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:50:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:40:00 8283.19 6074.14 234.499587 78.35 65.09 0.01019035 53.60 52.26 0.00800000 86.38 0.01436798 73.00 19.1877 75.00 0.00919435 49.7684 5501.04 0.00 8458.37 6211.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 2963.273 2963.273 -999. -999. -999.00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 2963.27 2963.27 234.499587 69.92 66.46 0.01311803 122.00 75.17 0.00800000 61.16 0.01151798 61.16 19.1877 32.00 0.00000000 0.2665 377.64 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 11462.336 8865.318 353.683997 -999. -999.00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 11496.13 9304.76 353.683997 77.68 63.69 0.00938378 53.60 52.26 0.00800000 86.89 0.01436849 73.14 12.7218 75.00 0.00865720 46.8999 8315.10 0.00 11467.12 8860.47
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 2963.273 2963.273 -999. -999. -999.00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 2963.27 2963.27 353.683997 70.62 69.57 0.01528911 122.00 75.17 0.00800000 61.16 0.01151798 61.16 12.7218 32.00 0.00000000 0.2665 297.71 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 6639.097 4829.286 180.452082 -999. -999.00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 6411.75 4599.02 180.452082 78.65 65.49 0.01040020 53.60 52.26 0.00800000 84.98 0.01436657 72.60 24.9346 75.00 0.00908268 49.1716 4242.44 0.00 6641.87 4826.89
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 2963.273 2963.273 -999. -999. -999.00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 2963.27 2963.27 180.452082 69.30 59.96 0.00887719 122.00 75.17 0.00800000 61.16 0.01151798 61.16 24.9346 32.00 0.00000000 0.2665 0.00 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 8584.285 6450.511 249.991109 -999. -999.00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:10:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:00:00 8528.46 6632.37 249.991109 78.33 64.41 0.00972063 53.60 52.26 0.00800000 87.02 0.01436862 73.18 17.9986 75.00 0.00869661 47.1099 5875.82 0.00 8587.87 6446.14
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 2963.273 2963.273 -999. -999. -999.00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 2963.27 2963.27 249.991109 70.05 69.10 0.01505475 122.00 75.17 0.00800000 61.16 0.01151798 61.16 17.9986 32.00 0.00000000 0.2665 299.89 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 11347.886 8777.328 350.206508 -999. -999.00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:10:00 11357.71 9167.39 350.206508 77.65 63.71 0.00940247 53.60 52.26 0.00800000 86.57 0.01436817 73.05 12.8481 75.00 0.00866388 46.9356 8223.62 0.00 11352.62 8772.59
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 2963.273 2963.273 -999. -999. -999.00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 2963.27 2963.27 350.206508 70.61 69.54 0.01526294 122.00 75.17 0.00800000 61.16 0.01151798 61.16 12.8481 32.00 0.00000000 0.2665 303.99 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 6633.425 4822.942 180.071616 -999. -999.00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 6404.45 4587.91 180.071616 78.66 65.51 0.01041154 53.60 52.26 0.00800000 84.98 0.01436657 72.60 24.9873 75.00 0.00909409 49.2325 4233.49 0.00 6636.19 4820.32
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 2963.273 2963.273 -999. -999. -999.00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 2963.27 2963.27 180.071616 69.29 59.96 0.00887905 122.00 75.17 0.00800000 61.16 0.01151798 61.16 24.9873 32.00 0.00000000 0.2665 0.00 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 8532.515 6425.320 249.011794 -999. -999.00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:50:00 8462.15 6571.55 249.011794 78.28 64.40 0.00972841 53.60 52.26 0.00800000 86.70 0.01436830 73.09 18.0694 75.00 0.00870041 47.1302 5851.98 0.00 8536.08 6422.32
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 2963.273 2963.273 -999. -999. -999.00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 2963.27 2963.27 249.011794 70.04 69.09 0.01505301 122.00 75.17 0.00800000 61.16 0.01151798 61.16 18.0694 32.00 0.00000000 0.2665 299.42 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 13330.252 10281.846 408.446207 -999. -999.00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 13355.27 10647.94 408.446207 77.48 63.77 0.00948253 53.60 52.26 0.00800000 86.89 0.01436849 73.14 11.0161 75.00 0.00887765 48.0789 9602.12 0.00 13335.81 10277.08
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 2963.273 2963.273 -999. -999. -999.00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 2963.27 2963.27 408.446207 70.81 64.96 0.01184204 122.00 75.17 0.00800000 61.16 0.01151798 61.16 11.0161 32.00 0.00000000 0.2665 895.85 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 8382.872 6161.361 232.631804 -999. -999.00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 8134.92 5861.34 232.631804 78.09 65.19 0.01031444 53.60 52.26 0.00800000 84.98 0.01436657 72.60 19.3417 75.00 0.00932932 50.4887 5452.81 0.00 8386.37 6159.53
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 2963.273 2963.273 -999. -999. -999.00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 2963.27 2963.27 232.631804 69.90 67.76 0.01407381 122.00 75.17 0.00800000 61.16 0.01151798 61.16 19.3417 32.00 0.00000000 0.2665 183.61 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 9755.280 7173.013 271.017372 -999. -999.00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 9783.81 7414.22 271.017372 78.61 64.82 0.00994290 53.60 52.26 0.00800000 89.70 0.01437132 73.92 16.6023 75.00 0.00906153 49.0622 6364.30 0.00 9759.35 7171.21
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 2963.273 2963.273 -999. -999. -999.00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 2963.27 2963.27 271.017372 70.20 64.73 0.01181691 122.00 75.17 0.00800000 61.16 0.01151798 61.16 16.6023 32.00 0.00000000 0.2665 897.81 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 13370.477 10315.600 409.956998 -999. -999.00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 13397.10 10687.36 409.956998 77.47 63.76 0.00947811 53.60 52.26 0.00800000 86.89 0.01436849 73.14 10.9755 75.00 0.00887519 48.0658 9637.63 0.00 13376.06 10311.11
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 2963.273 2963.273 -999. -999. -999.00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 2963.27 2963.27 409.956998 70.81 64.95 0.01183139 122.00 75.17 0.00800000 61.16 0.01151798 61.16 10.9755 32.00 0.00000000 0.2665 899.96 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 8451.634 6217.349 235.095984 -999. -999.00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 8205.85 5924.34 235.095984 78.07 65.15 0.01029611 53.60 52.26 0.00800000 84.98 0.01436657 72.60 19.1390 75.00 0.00932021 50.4401 5512.01 0.00 8455.16 6214.23
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 2963.273 2963.273 -999. -999. -999.00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 2963.27 2963.27 235.095984 69.93 67.77 0.01407478 122.00 75.17 0.00800000 61.16 0.01151798 61.16 19.1390 32.00 0.00000000 0.2665 185.60 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 9568.741 7084.680 269.840583 -999. -999.00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:10:00 9419.99 6986.06 269.840583 78.09 64.85 0.01007884 53.60 52.26 0.00800000 86.57 0.01436817 73.05 16.6747 75.00 0.00906919 49.1030 6322.27 0.00 9572.73 7080.90
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 2963.273 2963.273 -999. -999. -999.00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 2963.27 2963.27 269.840583 70.19 64.73 0.01181971 122.00 75.17 0.00800000 61.16 0.01151798 61.16 16.6747 32.00 0.00000000 0.2665 896.48 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 4991.393 4896.557 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 4980.638 4886.006 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 4990.813 4895.988 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 4994.160 4899.271 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 4980.451 4885.823 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 4990.830 4896.005 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 5029.978 4934.409 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 5024.901 4929.428 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 5029.392 4933.834 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 5026.606 4931.100 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 5024.910 4929.437 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 5029.384 4933.826 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 4992.079 4897.229 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 4995.050 4900.144 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 4984.776 4890.065 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 4992.058 4897.209 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 4995.081 4900.174 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 4984.798 4890.087 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [Btu/lbm-R] Dry Air Heat Capacity [Btu/lbm-R] Standard Air Density Adjusted for Elevation [lb/ft3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [ft3/min] Supply Fan Maximum Air Mass Flow Rate [lb/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [Btu/lbm-R] Plant Fluid Density [lb/ft3] Plant Maximum Fluid Mass Flow Rate [lb/s] Plant Design Fluid Return Temperature [F] Plant Design Fluid Supply Temperature [F] Plant Design Fluid Temperature Difference [deltaF] Plant Design Capacity [Btu/h] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [F] System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h] Coil Air Mass Flow Rate at Rating Conditions [lb/s] Coil Entering Air Drybulb at Rating Conditions [F] Coil Entering Air Wetbulb at Rating Conditions [F] Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] Coil Leaving Air Drybulb at Rating Conditions [F] Coil Leaving Air Wetbulb at Rating Conditions [F] Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 11178.066 8429.986 327.490654 -999. -999.00 -999.0000 1.00000 1.00000 0.2443 0.2400 0.0752 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 327.490654 0.41030388   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:40:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 Sensible 11126.55 8562.19 1.0046 0.41030388 327.490654 77.83 64.31 0.00976954 12.1 53.60 52.26 0.00800000 7.7 -999. -999.0 -999.0 -999.0 421.474 10705.07 87.11 0.01436870 73.20 44.99498340 13.7393 75.00 0.00903701 75.00 0.00902743 48.8784 7696.97 0.00 11182.73 8427.42 0.39409997 80.00 67.00 0.01118466 13.2 55.67 55.65 0.00941351 8.8
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2963.273 2963.273 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0752 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 327.490654 0.41030388   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 unknown unknown HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 Sensible 2963.27 2963.27 1.0000 0.41030388 327.490654 70.51 66.81 0.01323172 13.2 122.00 75.17 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 2963.27 61.16 0.01151798 61.16 44.99498340 13.7393 72.00 0.01350468 32.00 0.00000000 0.2665 375.64 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6424.713 4540.081 163.650727 -999. -999.00 -999.0000 1.00000 1.00000 0.2449 0.2400 0.0752 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 163.650727 0.20503342   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:20:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 Sensible 6107.66 4092.47 1.0519 0.20503342 163.650727 78.91 66.45 0.01102599 13.0 53.60 52.26 0.00800000 7.7 -999. -999.0 -999.0 -999.0 210.615 5897.05 84.98 0.01436657 72.60 44.99498340 27.4945 75.00 0.00975923 75.00 0.00971569 52.5473 3812.93 0.00 6427.39 4538.74 0.19693615 80.00 67.00 0.01118466 13.2 53.75 53.71 0.00875515 8.2
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2963.273 2963.273 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0752 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 163.650727 0.20503342   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 unknown unknown HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 Sensible 2963.27 2963.27 1.0000 0.20503342 163.650727 69.02 60.00 0.00896725 10.4 122.00 75.17 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 2963.27 61.16 0.01151798 61.16 44.99498340 27.4945 72.00 0.00800000 32.00 0.00000000 0.2665 0.00 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 8493.591 6235.746 234.990949 -999. -999.00 -999.0000 1.00000 1.00000 0.2445 0.2400 0.0752 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 234.990949 0.29441358   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:50:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:50:00 Sensible 8335.15 6119.89 1.0190 0.29441358 234.990949 78.41 65.10 0.01018458 12.4 53.60 52.26 0.00800000 7.7 -999. -999.0 -999.0 -999.0 302.429 8032.72 86.70 0.01436830 73.09 44.99498340 19.1475 75.00 0.00919379 75.00 0.00919041 49.7474 5514.14 0.00 8497.13 6233.12 0.28278647 80.00 67.00 0.01118466 13.2 54.91 54.90 0.00915645 8.6
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2963.273 2963.273 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0752 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 234.990949 0.29441358   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 unknown unknown HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 Sensible 2963.27 2963.27 1.0000 0.29441358 234.990949 69.93 66.47 0.01312042 13.0 122.00 75.17 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 2963.27 61.16 0.01151798 61.16 44.99498340 19.1475 72.00 0.01349991 32.00 0.00000000 0.2665 376.97 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 11068.401 8338.307 323.362037 -999. -999.00 -999.0000 1.00000 1.00000 0.2443 0.2400 0.0752 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 323.362037 0.40513125   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 Sensible 11011.60 8453.46 1.0052 0.40513125 323.362037 77.85 64.35 0.00978937 12.1 53.60 52.26 0.00800000 7.7 -999. -999.0 -999.0 -999.0 416.161 10595.44 87.11 0.01436870 73.20 44.99498340 13.9147 75.00 0.00904917 75.00 0.00904917 48.9945 7601.90 0.00 11073.02 8334.79 0.38913162 80.00 67.00 0.01118466 13.2 55.63 55.61 0.00940201 8.8
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2963.273 2963.273 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0752 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 323.362037 0.40513125   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 unknown unknown HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 Sensible 2963.27 2963.27 1.0000 0.40513125 323.362037 70.49 66.77 0.01320951 13.1 122.00 75.17 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 2963.27 61.16 0.01151798 61.16 44.99498340 13.9147 72.00 0.01348293 32.00 0.00000000 0.2665 382.14 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6440.089 4550.118 163.957844 -999. -999.00 -999.0000 1.00000 1.00000 0.2449 0.2400 0.0752 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 163.957844 0.20541819   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 Sensible 6121.48 4098.45 1.0520 0.20541819 163.957844 78.90 66.46 0.01103275 13.0 53.60 52.26 0.00800000 7.7 -999. -999.0 -999.0 -999.0 211.011 5910.47 84.98 0.01436657 72.60 44.99498340 27.4430 75.00 0.00977182 75.00 0.00976403 52.8047 3848.02 0.00 6442.78 4548.69 0.19730573 80.00 67.00 0.01118466 13.2 53.74 53.70 0.00875272 8.2
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2963.273 2963.273 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0752 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 163.957844 0.20541819   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 unknown unknown HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 Sensible 2963.27 2963.27 1.0000 0.20541819 163.957844 69.03 60.00 0.00896544 10.4 122.00 75.17 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 2963.27 61.16 0.01151798 61.16 44.99498340 27.4430 72.00 0.00800000 32.00 0.00000000 0.2665 0.00 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 8454.839 6212.988 234.499587 -999. -999.00 -999.0000 1.00000 1.00000 0.2445 0.2400 0.0752 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 234.499587 0.29379797   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:50:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:40:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:40:00 Sensible 8283.19 6074.14 1.0207 0.29379797 234.499587 78.35 65.09 0.01019035 12.4 53.60 52.26 0.00800000 7.7 -999. -999.0 -999.0 -999.0 301.797 7981.39 86.38 0.01436798 73.00 44.99498340 19.1877 75.00 0.00919843 75.00 0.00919435 49.7684 5501.04 0.00 8458.37 6211.00 0.28219517 80.00 67.00 0.01118466 13.2 54.95 54.93 0.00916715 8.6
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2963.273 2963.273 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0752 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 234.499587 0.29379797   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 unknown unknown HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 Sensible 2963.27 2963.27 1.0000 0.29379797 234.499587 69.92 66.46 0.01311803 13.0 122.00 75.17 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 2963.27 61.16 0.01151798 61.16 44.99498340 19.1877 72.00 0.01349794 32.00 0.00000000 0.2665 377.64 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 11462.336 8865.318 353.683997 -999. -999.00 -999.0000 1.00000 1.00000 0.2442 0.2400 0.0752 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 353.683997 0.44312078   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 Sensible 11496.13 9304.76 0.9971 0.44312078 353.683997 77.68 63.69 0.00938378 11.8 53.60 52.26 0.00800000 7.7 -999. -999.0 -999.0 -999.0 455.185 11040.95 86.89 0.01436849 73.14 44.99498340 12.7218 75.00 0.00865720 75.00 0.00865720 46.8999 8315.10 0.00 11467.12 8860.47 0.42562086 80.00 67.00 0.01118466 13.2 56.33 56.29 0.00963316 9.1
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2963.273 2963.273 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0752 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 353.683997 0.44312078   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 unknown unknown HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 Sensible 2963.27 2963.27 1.0000 0.44312078 353.683997 70.62 69.57 0.01528911 14.4 122.00 75.17 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 2963.27 61.16 0.01151798 61.16 44.99498340 12.7218 72.00 0.01583879 32.00 0.00000000 0.2665 297.71 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6639.097 4829.286 180.452082 -999. -999.00 -999.0000 1.00000 1.00000 0.2446 0.2400 0.0752 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 180.452082 0.22608336   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 Sensible 6411.75 4599.02 1.0355 0.22608336 180.452082 78.65 65.49 0.01040020 12.6 53.60 52.26 0.00800000 7.7 -999. -999.0 -999.0 -999.0 232.238 6179.51 84.98 0.01436657 72.60 44.99498340 24.9346 75.00 0.00908268 75.00 0.00908268 49.1716 4242.44 0.00 6641.87 4826.89 0.21715478 80.00 67.00 0.01118466 13.2 54.70 54.65 0.00906731 8.5
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2963.273 2963.273 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0752 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 180.452082 0.22608336   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 unknown unknown HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 Sensible 2963.27 2963.27 1.0000 0.22608336 180.452082 69.30 59.96 0.00887719 10.4 122.00 75.17 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 2963.27 61.16 0.01151798 61.16 44.99498340 24.9346 72.00 0.00800000 32.00 0.00000000 0.2665 0.00 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 8584.285 6450.511 249.991109 -999. -999.00 -999.0000 1.00000 1.00000 0.2443 0.2400 0.0752 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 249.991109 0.31320686   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:10:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:10:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:00:00 Sensible 8528.46 6632.37 1.0065 0.31320686 249.991109 78.33 64.41 0.00972063 12.1 53.60 52.26 0.00800000 7.7 -999. -999.0 -999.0 -999.0 321.734 8206.73 87.02 0.01436862 73.18 44.99498340 17.9986 75.00 0.00870044 75.00 0.00869661 47.1099 5875.82 0.00 8587.87 6446.14 0.30083756 80.00 67.00 0.01118466 13.2 55.62 55.57 0.00938112 8.8
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2963.273 2963.273 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0752 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 249.991109 0.31320686   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 unknown unknown HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 Sensible 2963.27 2963.27 1.0000 0.31320686 249.991109 70.05 69.10 0.01505475 14.2 122.00 75.17 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 2963.27 61.16 0.01151798 61.16 44.99498340 17.9986 72.00 0.01583105 32.00 0.00000000 0.2665 299.89 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 11347.886 8777.328 350.206508 -999. -999.00 -999.0000 1.00000 1.00000 0.2442 0.2400 0.0752 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 350.206508 0.43876393   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:10:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:10:00 Sensible 11357.71 9167.39 0.9991 0.43876393 350.206508 77.65 63.71 0.00940247 11.8 53.60 52.26 0.00800000 7.7 -999. -999.0 -999.0 -999.0 450.709 10907.00 86.57 0.01436817 73.05 44.99498340 12.8481 75.00 0.00867042 75.00 0.00866388 46.9356 8223.62 0.00 11352.62 8772.59 0.42143607 80.00 67.00 0.01118466 13.2 56.33 56.29 0.00963375 9.1
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2963.273 2963.273 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0752 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 350.206508 0.43876393   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 unknown unknown HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 Sensible 2963.27 2963.27 1.0000 0.43876393 350.206508 70.61 69.54 0.01526294 14.4 122.00 75.17 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 2963.27 61.16 0.01151798 61.16 44.99498340 12.8481 72.00 0.01581503 32.00 0.00000000 0.2665 303.99 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6633.425 4822.942 180.071616 -999. -999.00 -999.0000 1.00000 1.00000 0.2446 0.2400 0.0752 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 180.071616 0.22560669   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 Sensible 6404.45 4587.91 1.0358 0.22560669 180.071616 78.66 65.51 0.01041154 12.6 53.60 52.26 0.00800000 7.7 -999. -999.0 -999.0 -999.0 231.749 6172.70 84.98 0.01436657 72.60 44.99498340 24.9873 75.00 0.00909409 75.00 0.00909409 49.2325 4233.49 0.00 6636.19 4820.32 0.21669693 80.00 67.00 0.01118466 13.2 54.68 54.63 0.00906178 8.5
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2963.273 2963.273 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0752 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 180.071616 0.22560669   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 unknown unknown HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 Sensible 2963.27 2963.27 1.0000 0.22560669 180.071616 69.29 59.96 0.00887905 10.4 122.00 75.17 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 2963.27 61.16 0.01151798 61.16 44.99498340 24.9873 72.00 0.00800000 32.00 0.00000000 0.2665 0.00 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 8532.515 6425.320 249.011794 -999. -999.00 -999.0000 1.00000 1.00000 0.2443 0.2400 0.0752 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 249.011794 0.31197991   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 11:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 10:50:00 Sensible 8462.15 6571.55 1.0083 0.31197991 249.011794 78.28 64.40 0.00972841 12.1 53.60 52.26 0.00800000 7.7 -999. -999.0 -999.0 -999.0 320.474 8141.67 86.70 0.01436830 73.09 44.99498340 18.0694 75.00 0.00870510 75.00 0.00870041 47.1302 5851.98 0.00 8536.08 6422.32 0.29965906 80.00 67.00 0.01118466 13.2 55.62 55.60 0.00939768 8.8
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2963.273 2963.273 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0752 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 249.011794 0.31197991   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 unknown unknown HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 Sensible 2963.27 2963.27 1.0000 0.31197991 249.011794 70.04 69.09 0.01505301 14.2 122.00 75.17 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 2963.27 61.16 0.01151798 61.16 44.99498340 18.0694 72.00 0.01583264 32.00 0.00000000 0.2665 299.42 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 13330.252 10281.846 408.446207 -999. -999.00 -999.0000 1.00000 1.00000 0.2442 0.2400 0.0752 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 408.446207 0.51173082   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 Sensible 13355.27 10647.94 0.9981 0.51173082 408.446207 77.48 63.77 0.00948253 11.8 53.60 52.26 0.00800000 7.7 -999. -999.0 -999.0 -999.0 525.663 12829.61 86.89 0.01436849 73.14 44.99498340 11.0161 75.00 0.00887765 75.00 0.00887765 48.0789 9602.12 0.00 13335.81 10277.08 0.49152132 80.00 67.00 0.01118466 13.2 56.22 56.20 0.00960817 9.0
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2963.273 2963.273 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0752 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 408.446207 0.51173082   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 unknown unknown HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 Sensible 2963.27 2963.27 1.0000 0.51173082 408.446207 70.81 64.96 0.01184204 12.4 122.00 75.17 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 2963.27 61.16 0.01151798 61.16 44.99498340 11.0161 72.00 0.01188216 32.00 0.00000000 0.2665 895.85 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 8382.872 6161.361 232.631804 -999. -999.00 -999.0000 1.00000 1.00000 0.2446 0.2400 0.0752 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 232.631804 0.29145788   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 Sensible 8134.92 5861.34 1.0305 0.29145788 232.631804 78.09 65.19 0.01031444 12.4 53.60 52.26 0.00800000 7.7 -999. -999.0 -999.0 -999.0 299.393 7835.53 84.98 0.01436657 72.60 44.99498340 19.3417 75.00 0.00934275 75.00 0.00932932 50.4887 5452.81 0.00 8386.37 6159.53 0.27994749 80.00 67.00 0.01118466 13.2 54.96 54.94 0.00916952 8.6
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2963.273 2963.273 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0752 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 232.631804 0.29145788   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 unknown unknown HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 Sensible 2963.27 2963.27 1.0000 0.29145788 232.631804 69.90 67.76 0.01407381 13.6 122.00 75.17 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 2963.27 61.16 0.01151798 61.16 44.99498340 19.3417 72.00 0.01468669 32.00 0.00000000 0.2665 183.61 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 9755.280 7173.013 271.017372 -999. -999.00 -999.0000 1.00000 1.00000 0.2444 0.2400 0.0752 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 271.017372 0.33955008   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 Sensible 9783.81 7414.22 0.9971 0.33955008 271.017372 78.61 64.82 0.00994290 12.3 53.60 52.26 0.00800000 7.7 -999. -999.0 -999.0 -999.0 348.794 9435.02 89.70 0.01437132 73.92 44.99498340 16.6023 75.00 0.00906133 75.00 0.00906153 49.0622 6364.30 0.00 9759.35 7171.21 0.32614042 80.00 67.00 0.01118466 13.2 54.98 54.95 0.00917429 8.6
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2963.273 2963.273 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0752 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 271.017372 0.33955008   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 unknown unknown HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 Sensible 2963.27 2963.27 1.0000 0.33955008 271.017372 70.20 64.73 0.01181691 12.3 122.00 75.17 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 2963.27 61.16 0.01151798 61.16 44.99498340 16.6023 72.00 0.01187642 32.00 0.00000000 0.2665 897.81 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 13370.477 10315.600 409.956998 -999. -999.00 -999.0000 1.00000 1.00000 0.2442 0.2400 0.0752 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 409.956998 0.51362365   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 Sensible 13397.10 10687.36 0.9980 0.51362365 409.956998 77.47 63.76 0.00947811 11.8 53.60 52.26 0.00800000 7.7 -999. -999.0 -999.0 -999.0 527.607 12869.49 86.89 0.01436849 73.14 44.99498340 10.9755 75.00 0.00887519 75.00 0.00887519 48.0658 9637.63 0.00 13376.06 10311.11 0.49333940 80.00 67.00 0.01118466 13.2 56.23 56.21 0.00961079 9.0
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2963.273 2963.273 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0752 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 409.956998 0.51362365   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 unknown unknown HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 Sensible 2963.27 2963.27 1.0000 0.51362365 409.956998 70.81 64.95 0.01183139 12.4 122.00 75.17 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 2963.27 61.16 0.01151798 61.16 44.99498340 10.9755 72.00 0.01187003 32.00 0.00000000 0.2665 899.96 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 8451.634 6217.349 235.095984 -999. -999.00 -999.0000 1.00000 1.00000 0.2446 0.2400 0.0752 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 235.095984 0.29454518   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 Sensible 8205.85 5924.34 1.0300 0.29454518 235.095984 78.07 65.15 0.01029611 12.4 53.60 52.26 0.00800000 7.7 -999. -999.0 -999.0 -999.0 302.564 7903.29 84.98 0.01436657 72.60 44.99498340 19.1390 75.00 0.00933267 75.00 0.00932021 50.4401 5512.01 0.00 8455.16 6214.23 0.28291287 80.00 67.00 0.01118466 13.2 55.00 54.97 0.00917803 8.6
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2963.273 2963.273 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0752 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 235.095984 0.29454518   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 unknown unknown HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 Sensible 2963.27 2963.27 1.0000 0.29454518 235.095984 69.93 67.77 0.01407478 13.6 122.00 75.17 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 2963.27 61.16 0.01151798 61.16 44.99498340 19.1390 72.00 0.01467995 32.00 0.00000000 0.2665 185.60 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 9568.741 7084.680 269.840583 -999. -999.00 -999.0000 1.00000 1.00000 0.2445 0.2400 0.0752 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 269.840583 0.33807571   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:10:00 Sensible 9419.99 6986.06 1.0158 0.33807571 269.840583 78.09 64.85 0.01007884 12.3 53.60 52.26 0.00800000 7.7 -999. -999.0 -999.0 -999.0 347.280 9072.71 86.57 0.01436817 73.05 44.99498340 16.6747 75.00 0.00922047 75.00 0.00906919 49.1030 6322.27 0.00 9572.73 7080.90 0.32472428 80.00 67.00 0.01118466 13.2 55.19 55.15 0.00924066 8.7
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2963.273 2963.273 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0752 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 269.840583 0.33807571   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 unknown unknown HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:10:00 Sensible 2963.27 2963.27 1.0000 0.33807571 269.840583 70.19 64.73 0.01181971 12.3 122.00 75.17 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 2963.27 61.16 0.01151798 61.16 44.99498340 16.6747 72.00 0.01188010 32.00 0.00000000 0.2665 896.48 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 4991.393 4896.557 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0752 HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.20047277   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 4980.638 4886.006 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0752 HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.20047277   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 4990.813 4895.988 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0752 HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.20047277   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 4994.160 4899.271 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0752 HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.20047277   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 4980.451 4885.823 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0752 HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.20047277   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 4990.830 4896.005 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0752 HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.20047277   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 5029.978 4934.409 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0752 HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.20047277   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 5024.901 4929.428 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0752 HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.20047277   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 5029.392 4933.834 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0752 HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.20047277   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 5026.606 4931.100 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0752 HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.20047277   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 5024.910 4929.437 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0752 HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.20047277   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 5029.384 4933.826 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0752 HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.20047277   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 4992.079 4897.229 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0752 HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 160.010573 0.20047277   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 4995.050 4900.144 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0752 HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 160.010573 0.20047277   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 4984.776 4890.065 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0752 HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 160.010573 0.20047277   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 4992.058 4897.209 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0752 HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 160.010573 0.20047277   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 4995.081 4900.174 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0752 HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 160.010573 0.20047277   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 4984.798 4890.087 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0752 HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 160.010573 0.20047277   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 7689.33 3291.33 2808.50
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 7389.33 2808.83 2406.83
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 7739.50 2727.83 2316.17
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 7534.00 3554.50 2999.33
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 7170.17 3279.67 2771.67
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 7585.83 2932.00 2481.83
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 7926.33 1412.83 1194.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 7756.50 668.67 542.50
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7988.33 1008.00 835.33
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 7805.17 1543.83 1283.50
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 7505.33 846.00 662.67
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7882.83 1087.83 908.67
LIVING_UNIT3_BACKROW_TOPFLOOR 7993.00 1380.50 1161.83
LIVING_UNIT3_FRONTROW_TOPFLOOR 8025.50 1308.67 1095.33
LIVING_UNIT1_FRONTROW_TOPFLOOR 7966.67 1871.17 1610.50
LIVING_UNIT2_BACKROW_TOPFLOOR 7806.67 1412.00 1182.17
LIVING_UNIT2_FRONTROW_TOPFLOOR 7930.00 1283.67 1093.67
LIVING_UNIT1_BACKROW_TOPFLOOR 7917.00 1989.33 1689.83
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 8270.00 4047.83 3347.67
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 0.00 1.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.17 46.00 0.17 46.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.33 38.67 1.33 38.67
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.67 0.00 0.67 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.50 0.33 0.50 0.33
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.67 11.33 0.67 11.33
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.50 0.00 0.50 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.17 109.50 0.17 109.50
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.33 152.67 0.33 152.67
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.17 0.00 0.17 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.33 0.00 0.33 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.33 19.83 0.33 19.83
LIVING_UNIT3_BACKROW_TOPFLOOR 1.00 60.33 1.00 60.33
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.33 150.00 0.33 150.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.67 0.00 0.67 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.33 6.67 0.33 6.67
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.50 41.00 0.50 41.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.33 0.00 0.33 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 7.33 256.83 7.33 256.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.272 0.173 0.000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.272 0.152 0.000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.272 0.173 0.000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.272 0.173 0.000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.272 0.152 0.000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.272 0.173 0.000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.271 0.076 0.000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.271 0.055 0.000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.271 0.076 0.000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.271 0.076 0.000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.271 0.055 0.000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.271 0.076 0.000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.271 0.173 0.000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.271 0.173 0.000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.271 0.173 0.000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.271 0.152 0.000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.271 0.152 0.000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.272 0.173 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.265 0.000 0.000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.265 0.000 0.000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.265 0.000 0.000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.265 0.000 0.000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.265 0.000 0.000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.265 0.000 0.000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.265 0.000 0.000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.266 0.000 0.000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.266 0.000 0.000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.265 0.000 0.000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.265 0.000 0.000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.266 0.000 0.000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.266 0.000 0.000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.265 0.000 0.000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.265 0.000 0.000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.265 0.000 0.000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.266 0.000 0.000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.265 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Zone Area [ft2] Design Zone Outdoor Airflow - Voz [ft3/min] Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
Total Facility   24.79 36.00 183739.38 21609.96 0.0000 0.000


Total Outdoor Air by Zone

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Infiltration [ft3] Total Ventilation and Infiltration [ft3] Dynamic Target Ventilation - Voz-dyn [ft3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 15117234.72 38902316.40 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 13322441.68 37107523.37 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 15118298.10 38903379.78 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 15116469.12 38901550.81 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 13323371.22 37108452.91 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 15117448.91 38902530.60 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 6628887.90 30413969.59 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 4822137.78 28607219.46 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 6628070.21 30413151.90 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 6628349.56 30413431.25 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 4822577.85 28607659.54 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 6628532.86 30413614.55 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 23785081.69 0.00 23785081.69 15132820.80 38917902.49 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 23785081.69 0.00 23785081.69 15132166.57 38917248.25 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 23785081.69 0.00 23785081.69 15132897.77 38917979.46 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 23785081.69 0.00 23785081.69 13331172.34 37116254.03 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 23785081.69 0.00 23785081.69 13330763.89 37115845.57 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 23785081.69 0.00 23785081.69 15131849.25 38916930.93 23785081.69 0.00 8808.00 0.00 0.00
Total Facility 0.428131E+09 0.00 0.428131E+09 0.210465E+09 0.638597E+09 0.428131E+09 0.00 8808.00 0.00 0.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Infiltration [ft3/min] Total Ventilation and Infiltration [ft3/min] Dynamic Target Ventilation - Voz-dyn [ft3/min] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 28.5977 73.5927 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 25.2025 70.1975 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 28.5998 73.5947 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 28.5963 73.5913 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 25.2042 70.1992 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 28.5982 73.5931 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 12.5401 57.5351 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 9.1222 54.1172 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 12.5385 57.5335 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 12.5391 57.5340 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 9.1230 54.1180 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 12.5394 57.5344 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 44.9950 0.0000 44.9950 28.6272 73.6222 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 44.9950 0.0000 44.9950 28.6260 73.6210 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 44.9950 0.0000 44.9950 28.6274 73.6224 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 44.9950 0.0000 44.9950 25.2190 70.2140 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 44.9950 0.0000 44.9950 25.2182 70.2132 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 44.9950 0.0000 44.9950 28.6254 73.6204 44.9950 0.00 8808.00 0.00
Total Facility 809.9097 0.0000 809.9097 398.1442 1208.0539 809.9097 0.00 8808.00 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [ft3] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [ft3/min] Limits and Scheduled Limits [ft3/min] Economizer [ft3/min] Exhaust Flow [ft3/min] Mixed Air Flow [ft3/min] High Humidity [ft3/min] Demand Controlled Ventilation [ft3/min] Night Ventilation [ft3/min] Demand Limiting [ft3/min] Energy Management System [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

Surfaces by Class

Total Outdoors
Wall 74 50
Floor 28 3
Roof 21 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 60 60
Overhang 30 30
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 2
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 2028
Defaulted Fields 1686
Fields with Defaults 7040
Autosized Fields 360
Autosizable Fields 612
Autocalculated Fields 185
Autocalculatable Fields 400



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 161039.54 7967.15 08-FEB-03:20 33253.45 13-SEP-18:10
Electricity:Building 99140.61 6270.77 02-JAN-03:10 18720.91 01-JAN-18:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity 11336.81 253.88 01-JAN-00:10 3692.78 01-JAN-19:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
General:InteriorLights:Electricity 11336.81 253.88 01-JAN-00:10 3692.78 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
InteriorEquipment:Electricity 87803.80 5989.14 02-JAN-04:10 15388.75 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity 2758.31 25.25 02-JAN-03:10 880.12 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity 1408.53 13.53 02-JAN-02:10 381.47 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:10 3196.73 01-JAN-11:10
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:10 3721.08 01-JAN-17:10
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:10 7929.96 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:10 526.17 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
Electricity:HVAC 47608.02 289.29 07-JAN-05:40 13641.51 03-SEP-16:20
Cooling:Electricity 38394.26 0.00 02-JAN-07:10 11530.26 03-SEP-16:20
General:Cooling:Electricity 38394.26 0.00 02-JAN-07:10 11530.26 03-SEP-16:20
Electricity:Plant 8782.20 149.40 01-JAN-00:10 9407.99 01-JAN-09:10
WaterSystems:Electricity 8782.20 149.40 01-JAN-00:10 9407.99 01-JAN-09:10
Fans:Electricity 9135.71 289.29 07-JAN-05:40 2116.45 03-SEP-15:30
General:Fans:Electricity 6601.57 0.00 07-JAN-05:40 1827.17 03-SEP-15:30
Ventilation:Fans:Electricity 2534.14 289.29 01-JAN-00:10 289.29 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityPurchased:Facility 161039.54 7967.15 08-FEB-03:20 33253.45 13-SEP-18:10
ElectricityPurchased:Plant 161039.54 7967.15 08-FEB-03:20 33253.45 13-SEP-18:10
Cogeneration:ElectricityPurchased 161039.54 7967.15 08-FEB-03:20 33253.45 13-SEP-18:10
General:Cogeneration:ElectricityPurchased 161039.54 7967.15 08-FEB-03:20 33253.45 13-SEP-18:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 161039.54 7967.15 08-FEB-03:20 33253.45 13-SEP-18:10
ElectricityNet:Plant 161039.54 7967.15 08-FEB-03:20 33253.45 13-SEP-18:10
Cogeneration:ElectricityNet 161039.54 7967.15 08-FEB-03:20 33253.45 13-SEP-18:10
General:Cogeneration:ElectricityNet 161039.54 7967.15 08-FEB-03:20 33253.45 13-SEP-18:10
HeatRecovery:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:HeatRecovery:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ExteriorLights:Electricity 5508.71 0.00 01-JAN-06:10 1257.69 01-JAN-00:10
Exterior-Lights:ExteriorLights:Electricity 5508.71 0.00 01-JAN-06:10 1257.69 01-JAN-00:10
Garage-Lights:ExteriorLights:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:Electricity 78.05 0.00 01-JAN-00:10 5327.31 12-FEB-07:00
General:Heating:Electricity 78.05 0.00 01-JAN-00:10 5327.31 12-FEB-07:00
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:Electricity 1308.75 149.40 01-JAN-00:10 149.40 01-JAN-08:00
Water Heater Parasitic:WaterSystems:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [therm] Natural Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
Water:Plant 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
WaterSystems:Water 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
Domestic Hot Water:WaterSystems:Water 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
MainsWater:Facility 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
MainsWater:Plant 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
WaterSystems:MainsWater 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
Domestic Hot Water:WaterSystems:MainsWater 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 1124321.83 8765.77 09-FEB-03:10 291080.32 03-SEP-15:30
EnergyTransfer:HVAC 641805.65 0.00 07-JAN-05:40 173027.93 03-SEP-15:30
CoolingCoils:EnergyTransfer 641539.15 0.00 07-JAN-05:40 173027.93 03-SEP-15:30
EnergyTransfer:Building 413005.11 3371.25 16-JAN-08:30 111388.05 03-SEP-15:30
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer 100.36 0.00 01-JAN-00:10 4397.27 12-FEB-07:00
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 100.36 0.00 01-JAN-00:10 4397.27 12-FEB-07:00
Cooling:EnergyTransfer 412904.76 3371.25 16-JAN-08:30 111388.05 03-SEP-15:30
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer 412904.76 3371.25 16-JAN-08:30 111388.05 03-SEP-15:30
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 19884.15 2.44 27-MAR-08:40 7622.25 22-SEP-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 9.38 0.00 01-JAN-00:10 499.18 07-JAN-03:40
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 19874.77 0.00 16-JAN-10:20 7622.25 22-SEP-16:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 15984.90 3.70 26-MAR-08:50 5437.56 03-NOV-13:40
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 7.26 0.00 01-JAN-00:10 519.67 25-MAR-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 15977.64 0.00 16-JAN-10:30 5437.56 03-NOV-13:40
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 21528.78 2.01 12-FEB-07:20 7074.19 11-OCT-14:10
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4.08 0.00 01-JAN-00:10 1059.72 22-MAR-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 21524.70 0.00 16-JAN-04:10 7074.19 11-OCT-14:10
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 17864.72 2.23 25-MAR-09:10 7412.41 05-SEP-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 16.87 0.00 01-JAN-00:10 713.66 12-FEB-09:20
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 17847.85 0.00 01-JAN-09:30 7412.41 05-SEP-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 13960.38 1.97 15-JAN-09:40 3822.87 03-SEP-14:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 16.09 0.00 01-JAN-00:10 492.82 22-DEC-07:20
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 13944.29 0.00 01-JAN-09:30 3822.87 03-SEP-14:30
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 19392.63 13.48 14-MAR-07:20 6765.25 12-AUG-09:30
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4.68 0.00 01-JAN-00:10 519.59 12-FEB-03:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 19387.96 0.00 16-JAN-10:20 6765.25 12-AUG-09:30
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 25783.41 1.02 12-FEB-07:10 8316.61 26-FEB-17:10
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2.55 0.00 01-JAN-00:10 552.05 08-MAR-08:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 25780.86 0.00 17-JAN-09:20 8316.61 26-FEB-17:10
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 21541.79 5.87 08-MAR-09:40 6931.49 22-NOV-13:50
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.97 0.00 01-JAN-00:10 253.61 29-MAR-09:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 21539.82 0.00 10-FEB-10:00 6931.49 22-NOV-13:50
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 27820.59 16.42 09-JUL-05:00 8725.73 11-OCT-14:40
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.45 0.00 01-JAN-00:10 318.33 16-JAN-06:40
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 27820.14 0.00 12-FEB-05:50 8725.73 11-OCT-14:40
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 23373.84 2.49 22-DEC-10:20 7935.35 05-SEP-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5.72 0.00 01-JAN-00:10 594.76 12-FEB-09:20
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 23368.12 0.00 01-JAN-09:30 7935.35 05-SEP-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 19076.66 1.76 08-FEB-10:20 4239.76 03-SEP-19:40
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4.65 0.00 01-JAN-00:10 375.72 28-NOV-10:40
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 19072.01 0.00 01-JAN-09:30 4239.76 03-SEP-19:40
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 25358.92 10.67 03-MAR-09:10 7250.44 19-JUL-11:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.97 0.00 01-JAN-00:10 545.33 12-FEB-04:20
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 25357.95 0.00 05-FEB-10:30 7250.44 19-JUL-11:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 28738.73 5.76 08-MAR-05:40 8158.76 02-SEP-15:20
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 2.65 0.00 01-JAN-00:10 626.97 12-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 28736.07 0.00 05-FEB-10:30 8158.76 02-SEP-15:20
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 30422.24 11.43 08-FEB-06:50 9784.41 11-OCT-14:20
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 1.90 0.00 01-JAN-00:10 854.08 12-FEB-06:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 30420.34 0.00 16-JAN-05:30 9784.41 11-OCT-14:20
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 28503.82 3.39 22-MAR-10:00 9408.53 05-SEP-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5.60 0.00 01-JAN-00:10 678.45 11-FEB-08:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 28498.22 0.00 16-JAN-05:30 9408.53 05-SEP-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 22589.07 2.37 15-FEB-09:30 5739.27 02-SEP-19:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4.68 0.00 01-JAN-00:10 374.60 28-NOV-10:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 22584.39 0.00 01-JAN-09:30 5739.27 02-SEP-19:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 24318.14 3.81 26-MAR-08:50 7217.81 03-SEP-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 2.02 0.00 01-JAN-00:10 793.51 08-FEB-07:40
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 24316.12 0.00 10-FEB-10:00 7217.81 03-SEP-16:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 26862.35 1.80 27-MAR-08:40 9400.25 05-SEP-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 8.83 0.00 01-JAN-00:10 869.78 08-MAR-05:50
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 26853.52 0.00 01-JAN-09:30 9400.25 05-SEP-17:30
HeatRecoveryForHeating:EnergyTransfer 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRecoveryForCooling:EnergyTransfer 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatingCoils:EnergyTransfer 266.50 0.00 01-JAN-00:10 18176.80 12-FEB-07:00
EnergyTransfer:Plant 69511.07 654.76 10-JUL-02:10 16962.31 22-JAN-08:50
WaterSystems:EnergyTransfer 69511.07 654.76 10-JUL-02:10 16962.31 22-JAN-08:50
Domestic Hot Water:WaterSystems:EnergyTransfer 69511.07 654.76 10-JUL-02:10 16962.31 22-JAN-08:50
PlantLoopHeatingDemand:Facility 69511.07 654.76 10-JUL-02:10 16962.31 22-JAN-08:50
PlantLoopHeatingDemand:Plant 69511.07 654.76 10-JUL-02:10 16962.31 22-JAN-08:50
WaterSystems:PlantLoopHeatingDemand 69511.07 654.76 10-JUL-02:10 16962.31 22-JAN-08:50
General:WaterSystems:PlantLoopHeatingDemand 69511.07 654.76 10-JUL-02:10 16962.31 22-JAN-08:50
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1414.956 -210.05 34.498 -1564.99 0.000 0.000 2889.729 2150.478 10401.374 9495.900 0.000 1154.912 0.000 0.000 -1191.94 0.000 -273.82 -4761.38
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1412.588 -210.88 10.782 -1237.63 0.000 0.000 2884.889 2150.478 10401.374 4029.246 0.000 1017.466 0.000 0.000 -483.86 0.000 -248.65 -3780.60
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1408.008 -216.51 26.922 -1695.18 0.000 0.000 2887.832 2150.478 10401.374 11419.700 0.000 1150.195 0.000 0.000 -1157.69 0.000 -277.15 -5054.10
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1417.256 -206.71 44.041 -1399.90 0.000 0.000 2891.137 2150.478 10401.374 7741.389 0.000 1157.708 0.000 0.000 -1182.72 0.000 -271.22 -5057.28
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1417.810 -205.97 17.386 -1073.45 0.000 0.000 2886.700 2150.478 10401.374 2233.514 0.000 1023.494 0.000 0.000 -478.75 0.000 -246.50 -4042.13
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1410.220 -213.10 24.717 -1520.59 0.000 0.000 2889.210 2150.478 10401.374 9656.523 0.000 1152.873 0.000 0.000 -1140.66 0.000 -274.80 -5451.70
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1410.725 -223.90 10.670 -2041.23 0.000 0.000 2878.832 2150.478 10401.374 9314.492 0.000 501.679 2039.496 0.000 -1379.33 0.000 -128.74 -0.07
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1406.137 -226.62 2.208 -1684.29 0.000 0.000 2876.517 2150.478 10401.374 3953.270 0.000 363.878 2441.800 0.000 -554.59 0.000 -94.84 -0.14
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1401.302 -230.70 5.028 -2203.18 0.000 0.000 2877.402 2150.478 10401.374 11194.533 0.000 498.230 2159.943 0.000 -1332.73 0.000 -129.44 -0.01
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1411.169 -220.70 11.317 -1843.33 0.000 0.000 2879.695 2150.478 10401.374 7578.279 0.000 502.282 1343.813 0.000 -1365.55 0.000 -127.99 -0.16
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1411.416 -222.34 3.426 -1483.37 0.000 0.000 2877.865 2150.478 10401.374 2175.587 0.000 365.973 1736.555 0.000 -546.12 0.000 -94.32 -0.12
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1407.021 -227.66 8.448 -2001.90 0.000 0.000 2878.322 2150.478 10401.374 9452.651 0.000 500.546 1413.356 0.000 -1310.65 0.000 -128.98 -0.16
LIVING_UNIT3_BACKROW_TOPFLOOR 1406.204 -227.11 19.090 -2284.45 0.000 0.000 2879.536 2150.478 10401.374 9343.496 0.000 1134.600 4453.708 0.000 -1335.14 0.000 -294.50 -0.17
LIVING_UNIT3_FRONTROW_TOPFLOOR 1401.739 -229.05 15.148 -2422.13 0.000 0.000 2878.861 2150.478 10401.374 11100.104 0.000 1130.732 4404.326 0.000 -1351.86 0.000 -295.44 -0.04
LIVING_UNIT1_FRONTROW_TOPFLOOR 1412.138 -221.26 22.103 -2270.98 0.000 0.000 2880.702 2150.478 10401.374 9230.988 0.000 1139.057 4379.379 0.000 -1396.34 0.000 -293.09 -0.02
LIVING_UNIT2_BACKROW_TOPFLOOR 1412.547 -221.12 8.814 -1777.64 0.000 0.000 2878.234 2150.478 10401.374 2136.403 0.000 1004.151 4827.748 0.000 -556.87 0.000 -261.79 -0.08
LIVING_UNIT2_FRONTROW_TOPFLOOR 1411.074 -223.58 5.915 -1919.24 0.000 0.000 2877.540 2150.478 10401.374 3917.022 0.000 1001.667 4792.685 0.000 -563.84 0.000 -262.82 -0.15
LIVING_UNIT1_BACKROW_TOPFLOOR 1414.584 -219.23 25.503 -2136.25 0.000 0.000 2881.540 2150.478 10401.374 7480.920 0.000 1140.036 4467.698 0.000 -1386.10 0.000 -291.33 -0.03
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 22898.895 168375.744 0.000 0.000 0.000 -191274.64 -2.75
Total Facility 25386.893 -3956.48 296.016 -32559.73 0.000 0.000 51874.544 38708.604 187224.736 131454.015 0.000 38838.375 206836.253 0.000 -18714.75 0.000 -195270.06 -28151.07


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 22-SEP-16:30 0.00 0.04 0.00 -0.7 0.00 0.00 140.35 336.87 1343.44 6157.05 0.00 435.21 0.00 0.00 0.00 0.00 0.00 -790.7
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 11-OCT-14:10 0.00 -0.2 0.00 -0.4 0.00 0.00 111.99 90.23 1084.62 2141.64 0.00 392.51 2943.42 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 11-OCT-14:10 0.00 -0.2 0.00 -0.5 0.00 0.00 112.17 90.23 1084.62 3088.85 0.00 448.91 3672.29 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 05-SEP-17:30 0.00 0.05 0.00 -0.7 0.00 0.00 263.06 469.21 1655.83 4844.72 0.00 720.59 0.00 0.00 0.00 0.00 0.00 -540.8
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 03-SEP-14:30 0.00 -0.2 0.00 -0.1 0.00 0.00 114.36 90.23 1105.69 834.88 0.00 672.11 1005.21 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 27-JUL-10:15 0.00 -0.2 0.00 -0.4 0.00 0.00 113.53 90.23 1078.58 4484.04 0.00 503.58 1033.81 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 26-FEB-17:03 0.00 0.02 0.00 -0.7 0.00 0.00 263.16 469.21 1675.86 5070.37 0.00 75.84 763.19 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 21-NOV-15:05 0.00 -0.2 0.00 -0.4 0.00 0.00 111.17 156.40 1140.63 1944.69 0.00 170.00 4062.76 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 01-JAN-14:30 0.00 -0.2 0.00 -0.5 0.00 0.00 111.96 90.23 1105.69 2898.55 0.00 102.42 4910.81 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 05-SEP-17:30 0.00 0.05 0.00 -0.7 0.00 0.00 263.17 469.21 1655.83 4797.35 0.00 315.27 434.59 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 03-SEP-19:35 0.00 0.03 0.00 -0.4 0.00 0.00 425.45 699.99 1673.39 68.80 0.00 62.71 1344.25 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 09-JUL-11:00 0.00 -0.2 0.00 -0.5 0.00 0.00 112.86 90.23 1108.25 3658.49 0.00 234.97 3285.06 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 14-OCT-13:37 0.00 -0.2 0.00 -0.6 0.00 0.00 111.47 90.23 1099.93 1858.24 0.00 362.59 5748.90 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 11-OCT-14:15 0.00 -0.2 0.00 -0.6 0.00 0.00 106.70 90.23 1084.62 2877.57 0.00 411.72 5331.58 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 05-SEP-17:30 0.00 0.05 0.00 -0.8 0.00 0.00 262.77 469.21 1655.83 4727.76 0.00 714.84 1578.34 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 02-SEP-19:30 0.00 -0.2 0.00 -0.3 0.00 0.00 424.41 699.99 1673.39 101.37 0.00 289.17 2550.46 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 11-OCT-14:10 0.00 -0.2 0.00 -0.5 0.00 0.00 111.88 90.23 1084.62 2097.46 0.00 387.25 4744.50 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 05-SEP-17:30 0.00 0.05 0.00 -0.8 0.00 0.00 263.17 469.21 1655.83 4749.78 0.00 718.11 1544.28 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 11-OCT-14:10 0.00 -3.1 0.00 -6.3 0.00 0.00 2039.11 1624.19 19523.07 49990.87 0.00 6157.63 128038.53 0.00 0.00 0.00 -95269.3 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 12-FEB-09:13 -140.9 0.00 1371.58 0.00 0.00 0.00 127.86 90.23 1112.20 1515.70 0.00 0.00 0.00 0.00 0.00 0.00 -60.7 -4016.0
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 12-FEB-09:13 -141.0 0.00 1931.76 0.00 0.00 0.00 128.25 90.23 1112.20 1195.90 0.00 0.00 0.00 0.00 0.00 0.00 -53.2 -4264.2
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 08-MAR-03:35 -1987.1 0.00 3148.29 0.00 0.00 0.00 535.83 48.12 846.84 0.00 0.00 0.00 0.00 0.00 -968.5 0.00 -234.0 -1389.5
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12-FEB-09:13 -140.6 0.00 2995.15 0.00 0.00 0.00 128.28 90.23 1112.20 549.35 0.00 0.00 0.00 0.00 0.00 0.00 -60.3 -4674.3
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12-FEB-09:13 -140.9 0.00 2076.79 0.00 0.00 0.00 127.97 90.23 1112.20 211.73 0.00 0.00 0.00 0.00 0.00 0.00 -53.4 -3424.6
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 07-JAN-03:17 -900.2 0.00 1896.46 0.00 0.00 0.00 531.07 48.12 847.91 0.00 0.00 0.00 0.00 0.00 -696.4 0.00 -152.6 -1574.3
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 08-MAR-08:10 -1749.4 0.00 3339.87 0.00 0.00 0.00 216.90 132.34 1145.20 319.89 0.00 0.00 0.00 0.00 0.00 0.00 -42.6 -3362.1
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 08-MAR-08:32 -2755.1 0.00 3248.68 0.00 0.00 0.00 216.16 132.34 1145.20 623.95 0.00 0.00 0.00 0.00 0.00 0.00 -14.1 -2597.1
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 16-JAN-06:35 -256.9 0.00 893.62 0.00 0.00 0.00 536.82 336.87 1074.44 0.00 0.00 0.00 0.00 0.00 -471.6 0.00 -59.1 -2054.2
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12-FEB-09:15 -968.1 0.00 3347.07 0.00 0.00 0.00 127.50 90.23 1112.20 543.88 0.00 0.00 0.00 0.00 0.00 0.00 -26.1 -4226.7
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 06-JAN-12:05 526.04 0.00 0.00 0.00 0.00 0.00 118.10 90.23 1082.07 630.15 0.00 90.00 0.00 0.00 0.00 0.00 0.00 -2536.6
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 26-MAR-05:55 -804.7 0.00 1893.80 0.00 0.00 0.00 540.01 300.78 917.73 0.00 0.00 0.00 0.00 0.00 -871.8 0.00 -69.3 -1906.5
LIVING_UNIT3_BACKROW_TOPFLOOR 27-NOV-06:47 -1443.8 0.00 3186.46 0.00 0.00 0.00 529.27 336.87 1074.44 0.00 0.00 0.00 0.00 0.00 -815.8 0.00 -240.2 -2627.2
LIVING_UNIT3_FRONTROW_TOPFLOOR 08-FEB-06:55 -1952.1 0.00 3206.90 0.00 0.00 0.00 531.13 336.87 1074.44 0.00 0.00 0.00 0.00 0.00 -924.4 0.00 -355.7 -1917.2
LIVING_UNIT1_FRONTROW_TOPFLOOR 08-MAR-08:34 -120.1 0.00 2457.45 0.00 0.00 0.00 215.07 132.34 1145.20 894.45 0.00 0.00 0.00 0.00 0.00 0.00 -45.1 -4679.3
LIVING_UNIT2_BACKROW_TOPFLOOR 08-MAR-07:53 -322.3 0.00 1303.72 0.00 0.00 0.00 464.98 300.78 1204.45 0.00 0.00 0.00 0.00 0.00 -45.0 0.00 -106.2 -2800.4
LIVING_UNIT2_FRONTROW_TOPFLOOR 08-FEB-07:40 -1097.9 0.00 2684.84 0.00 0.00 0.00 465.84 300.78 1204.45 247.43 0.00 0.00 0.00 0.00 0.00 0.00 -223.5 -3582.0
LIVING_UNIT1_BACKROW_TOPFLOOR 08-FEB-09:48 46.54 0.00 1842.76 0.00 0.00 0.00 127.87 90.23 1083.81 736.54 0.00 3.61 0.00 0.00 0.00 0.00 0.00 -3931.4
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 12-FEB-09:13 -5772.3 0.00 8593.19 0.00 0.00 0.00 2252.14 1624.19 20019.65 35453.67 0.00 0.00 0.00 0.00 0.00 0.00 -5265.8 -56904.8



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 327.4907 0.0000 2.0000 1.0000 0.0000 327.4907 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 163.6507 0.0000 2.0000 1.0000 0.0000 163.6507 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 234.9909 0.0000 2.0000 1.0000 0.0000 234.9909 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 323.3620 0.0000 2.0000 1.0000 0.0000 323.3620 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 163.9578 0.0000 2.0000 1.0000 0.0000 163.9578 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 234.4996 0.0000 2.0000 1.0000 0.0000 234.4996 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 353.6840 0.0000 2.0000 1.0000 0.0000 353.6840 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 180.4521 0.0000 2.0000 1.0000 0.0000 180.4521 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 249.9911 0.0000 2.0000 1.0000 0.0000 249.9911 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 350.2065 0.0000 2.0000 1.0000 0.0000 350.2065 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 180.0716 0.0000 2.0000 1.0000 0.0000 180.0716 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 249.0118 0.0000 2.0000 1.0000 0.0000 249.0118 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 408.4462 0.0000 2.0000 1.0000 0.0000 408.4462 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 232.6318 0.0000 2.0000 1.0000 0.0000 232.6318 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 271.0174 0.0000 2.0000 1.0000 0.0000 271.0174 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 409.9570 0.0000 2.0000 1.0000 0.0000 409.9570 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 235.0960 0.0000 2.0000 1.0000 0.0000 235.0960 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 269.8406 0.0000 2.0000 1.0000 0.0000 269.8406 0.0000 1.0000 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 327.4907 0.0000 2.0000 1.0000 0.0000 327.4907 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 163.6507 0.0000 2.0000 1.0000 0.0000 163.6507 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 234.9909 0.0000 2.0000 1.0000 0.0000 234.9909 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 323.3620 0.0000 2.0000 1.0000 0.0000 323.3620 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 163.9578 0.0000 2.0000 1.0000 0.0000 163.9578 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 234.4996 0.0000 2.0000 1.0000 0.0000 234.4996 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 353.6840 0.0000 2.0000 1.0000 0.0000 353.6840 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 180.4521 0.0000 2.0000 1.0000 0.0000 180.4521 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 249.9911 0.0000 2.0000 1.0000 0.0000 249.9911 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 350.2065 0.0000 2.0000 1.0000 0.0000 350.2065 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 180.0716 0.0000 2.0000 1.0000 0.0000 180.0716 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 249.0118 0.0000 2.0000 1.0000 0.0000 249.0118 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 408.4462 0.0000 2.0000 1.0000 0.0000 408.4462 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 232.6318 0.0000 2.0000 1.0000 0.0000 232.6318 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 271.0174 0.0000 2.0000 1.0000 0.0000 271.0174 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 409.9570 0.0000 2.0000 1.0000 0.0000 409.9570 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 235.0960 0.0000 2.0000 1.0000 0.0000 235.0960 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 269.8406 0.0000 2.0000 1.0000 0.0000 269.8406 0.0000 1.0000 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 327.4907 327.4907 327.4907 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 163.6507 163.6507 163.6507 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 234.9909 234.9909 234.9909 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 323.3620 323.3620 323.3620 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 163.9578 163.9578 163.9578 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 234.4996 234.4996 234.4996 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 353.6840 353.6840 353.6840 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 180.4521 180.4521 180.4521 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 249.9911 249.9911 249.9911 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 350.2065 350.2065 350.2065 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 180.0716 180.0716 180.0716 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 249.0118 249.0118 249.0118 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 269.8406 269.8406 269.8406 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 271.0174 271.0174 271.0174 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 408.4462 408.4462 408.4462 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 235.0960 235.0960 235.0960 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 232.6318 232.6318 232.6318 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 409.9570 409.9570 409.9570 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 327.4907 327.4907 327.4907 327.4907 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 163.6507 163.6507 163.6507 163.6507 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 234.9909 234.9909 234.9909 234.9909 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 323.3620 323.3620 323.3620 323.3620 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 163.9578 163.9578 163.9578 163.9578 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 234.4996 234.4996 234.4996 234.4996 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 353.6840 353.6840 353.6840 353.6840 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 180.4521 180.4521 180.4521 180.4521 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 249.9911 249.9911 249.9911 249.9911 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 350.2065 350.2065 350.2065 350.2065 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 180.0716 180.0716 180.0716 180.0716 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 249.0118 249.0118 249.0118 249.0118 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 408.4462 408.4462 408.4462 408.4462 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 232.6318 232.6318 232.6318 232.6318 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 271.0174 271.0174 271.0174 271.0174 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 409.9570 409.9570 409.9570 409.9570 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 235.0960 235.0960 235.0960 235.0960 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 269.8406 269.8406 269.8406 269.8406 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 327.4907 327.4907 327.4907 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 163.6507 163.6507 163.6507 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 234.9909 234.9909 234.9909 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 323.3620 323.3620 323.3620 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 163.9578 163.9578 163.9578 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 234.4996 234.4996 234.4996 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 353.6840 353.6840 353.6840 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 180.4521 180.4521 180.4521 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 249.9911 249.9911 249.9911 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 350.2065 350.2065 350.2065 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 180.0716 180.0716 180.0716 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 249.0118 249.0118 249.0118 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 269.8406 269.8406 269.8406 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 271.0174 271.0174 271.0174 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 408.4462 408.4462 408.4462 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 235.0960 235.0960 235.0960 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 232.6318 232.6318 232.6318 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 409.9570 409.9570 409.9570 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 327.4907 327.4907 327.4907 327.4907 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 163.6507 163.6507 163.6507 163.6507 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 234.9909 234.9909 234.9909 234.9909 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 323.3620 323.3620 323.3620 323.3620 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 163.9578 163.9578 163.9578 163.9578 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 234.4996 234.4996 234.4996 234.4996 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 353.6840 353.6840 353.6840 353.6840 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 180.4521 180.4521 180.4521 180.4521 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 249.9911 249.9911 249.9911 249.9911 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 350.2065 350.2065 350.2065 350.2065 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 180.0716 180.0716 180.0716 180.0716 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 249.0118 249.0118 249.0118 249.0118 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 408.4462 408.4462 408.4462 408.4462 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 232.6318 232.6318 232.6318 232.6318 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 271.0174 271.0174 271.0174 271.0174 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 409.9570 409.9570 409.9570 409.9570 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 235.0960 235.0960 235.0960 235.0960 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 269.8406 269.8406 269.8406 269.8406 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

Sec1.1A-General Information

Data
Weather File ANNUAL ** Honolulu Intl Arpt HI USA TMY3 WMO#=911820
Total gross floor area [ft2] 31210.83
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
BREEZEWAY 1798.16 0.00 1798.16 0.00
ATTIC 7802.71 0.00 7802.71 0.00
Totals 31210.83 21609.96 9600.87  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 7.33
Number of hours cooling loads not met 256.83
Number of hours not met 264.17


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [kWh] Electricity Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Gasoline Use [therm] Gasoline Demand [Btu/h] Diesel Use [kBtu] Diesel Demand [Btu/h] Coal Use [kBtu] Coal Demand [Btu/h] Fuel Oil No 1 Use [kBtu] Fuel Oil No 1 Demand [Btu/h] Fuel Oil No 2 Use [kBtu] Fuel Oil No 2 Demand [Btu/h] Propane Use [kBtu] Propane Demand [Btu/h] Other Fuel 1 Use [kBtu] Other Fuel 1 Demand [Btu/h] Other Fuel 2 Use [kBtu] Other Fuel 2 Demand [Btu/h] District Cooling Use [ton-hrs] District Cooling Demand [ton] District Heating Use [kBtu] District Heating Demand [Btu/h]
Heating -- General 78.05 5327.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 38394.26 11530.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- General 11336.81 3692.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Exterior-Lights 5508.71 1257.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- dishwasher 2758.31 880.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- refrigerator 12036.11 1639.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- clotheswasher 1408.53 381.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_dryer 12502.11 3196.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_range 9058.39 3721.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_mels 46926.68 7929.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- IECC_adj 3113.66 526.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 6601.57 1827.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation 2534.14 289.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 1308.75 149.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Other 7473.46 9258.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 299798.81 549856.20
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 299798.81 549856.20


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting (All) 0.36
Space Heating 0.00
Space Cooling 1.23
Fans (All) 0.29
Service Water Heating 0.28
Receptacle Equipment 2.81
Miscellaneous (All) 5.16
Subtotal 5.16


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous (All) 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 7.04
Space Heating 0.05
Space Cooling 23.84
Fans (All) 5.67
Service Water Heating 5.45
Receptacle Equipment 54.52
Miscellaneous 3.42


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
OCCUPANCY 6031. 8760.
INTERIORLIGHTING 2852. 8760.
INTERIORLIGHTINGHE 3070. 8760.
INTERIORLIGHTINGHE_OS 2910. 8760.
INTERIORLIGHTINGHE_VS 2149. 8760.
EXTERIORLIGHTING 4380. 4380.
REFRIGERATOR 7343. 8760.
MISCPLUGLOAD 5918. 8760.
COOKINGRANGE 2434. 8760.
DHW_SCH 365. 8760.
DISHWASHER 2799. 8760.
CLOTHESWASHER 3297. 8760.
CLOTHESDRYER 3911. 8760.
SINKS 4179. 8760.
SHOWERS 2640. 8760.
BATHS 2586. 8760.
DHWDIST 4662. 8760.
SHADING_2012IECC 0. 0.
SINKSENSSCHEDULE 6025. 8760.
SINKLATSCHEDULE 2735. 8760.
SHOWERSENSSCHEDULE 4492. 8760.
SHOWERLATSCHEDULE 4268. 8760.
BATHSENSSCHEDULE 8760. 8760.
BATHLATSCHEDULE 0. 0.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [F] Days with Same 11am Value 11pm First Wednesday [F] Days with Same 11pm Value
HEATING_SCH THERMOSTAT_LIVING DUAL SP CONTROL January 72.00 365 72.00 365
COOLING_SCH THERMOSTAT_LIVING DUAL SP CONTROL July 75.00 365 75.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
BREEZEWAY 4527.17 3396.00 836.83 0.00 0.00
ATTIC 5256.67 1558.33 1787.83 157.17 0.00
Min 4527.17 0.00 0.00 0.00 0.00
Max 8760.00 3396.00 1787.83 157.17 0.00
Average 8373.19 247.72 131.23 7.86 0.00
Sum 167463.83 4954.33 2624.67 157.17 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 9125.00 0.00 0.00 0.00 0.00
Average 8212.50 0.00 0.00 0.00 0.00
Sum 164250.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5908.83 2851.17 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 6250.83 2509.17 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6368.83 2391.17 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5723.17 3036.83 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5897.83 2862.17 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6209.50 2550.50 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 7460.17 1299.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8136.17 623.83 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7841.33 918.67 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 7378.00 1382.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8011.67 748.33 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7765.67 994.33 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 7508.83 1251.17 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 7583.83 1176.17 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 7042.00 1718.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 7451.17 1308.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 7540.17 1219.83 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 6970.67 1789.33 0.00 0.00 0.00
BREEZEWAY 2494.83 6235.17 30.00 0.00 0.00
ATTIC 2464.17 5176.33 1044.00 75.50 0.00
Min 2464.17 623.83 0.00 0.00 0.00
Max 8136.17 6235.17 1044.00 75.50 0.00
Average 6600.38 2102.14 53.70 3.77 0.00
Sum 132007.67 42042.83 1074.00 75.50 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4856.33 4268.67 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5516.33 3608.67 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5011.83 4113.17 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4768.17 4356.83 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5314.50 3810.50 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4862.50 4262.50 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 7230.33 1894.67 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8278.00 847.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7544.00 1581.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 7201.33 1923.67 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8232.00 893.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7447.83 1677.17 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 7033.83 2091.17 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 7139.67 1985.33 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 6678.50 2446.50 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 7469.17 1655.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 7498.33 1626.67 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 6640.17 2484.83 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8278.00 4356.83 0.00 0.00 0.00
Average 5936.14 2276.36 0.00 0.00 0.00
Sum 118722.83 45527.17 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (F) SET ≤ 12.2°C OccupantHours (F) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (F) SET > 30°C OccupantHours (F) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2021-05-12 10:15:16

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 483.378 16.041 1.944 0.210 16.252
February 461.467 17.916 9.114 0.523 18.440
March 524.389 19.264 4.275 0.330 19.594
April 573.842 17.862 0.417 0.043 17.905
May 671.800 24.470 0.000 0.000 24.470
June 686.417 31.720 0.000 0.000 31.720
July 722.083 39.137 0.000 0.000 39.137
August 718.611 40.220 0.000 0.000 40.220
September 698.544 41.666 0.000 0.000 41.666
October 695.869 32.899 0.000 0.000 32.899
November 621.347 26.252 0.528 0.057 26.309
December 601.083 21.458 1.000 0.116 21.574
           
Annual Sum or Average 7458.830 328.907 17.278 1.279 330.186
Minimum of Months 461.467 16.041 0.000 0.000 16.252
Maximum of Months 722.083 41.666 9.114 0.523 41.666



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 537.014 12.283 0.472 0.027 12.310
February 505.086 12.325 1.836 0.086 12.411
March 540.764 12.592 1.422 0.079 12.672
April 599.572 11.965 0.139 0.008 11.973
May 661.472 16.698 0.000 0.000 16.698
June 670.222 22.181 0.000 0.000 22.181
July 709.167 27.344 0.000 0.000 27.344
August 713.028 28.225 0.000 0.000 28.225
September 688.083 28.699 0.000 0.000 28.699
October 695.838 23.935 0.000 0.000 23.935
November 628.931 19.295 0.083 0.005 19.300
December 630.167 16.454 0.111 0.006 16.460
           
Annual Sum or Average 7579.344 231.995 4.064 0.211 232.207
Minimum of Months 505.086 11.965 0.000 0.000 11.973
Maximum of Months 713.028 28.699 1.836 0.086 28.699



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 513.947 17.347 1.556 0.127 17.474
February 473.578 16.638 8.028 0.319 16.958
March 540.442 18.033 4.083 0.255 18.288
April 594.783 18.588 0.000 0.000 18.588
May 693.444 26.052 0.000 0.000 26.052
June 698.222 32.031 0.000 0.000 32.031
July 728.167 38.864 0.000 0.000 38.864
August 725.278 39.879 0.000 0.000 39.879
September 702.903 38.352 0.000 0.000 38.352
October 709.569 33.595 0.000 0.000 33.595
November 635.097 25.948 0.250 0.021 25.968
December 613.361 22.076 0.250 0.016 22.092
           
Annual Sum or Average 7628.792 327.402 14.167 0.738 328.140
Minimum of Months 473.578 16.638 0.000 0.000 16.958
Maximum of Months 728.167 39.879 8.028 0.319 39.879



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 438.939 10.168 3.472 0.374 10.542
February 434.072 13.610 11.094 0.659 14.269
March 509.667 16.478 4.675 0.369 16.848
April 571.733 16.926 0.417 0.040 16.966
May 675.264 25.256 0.000 0.000 25.256
June 689.111 33.091 0.000 0.000 33.091
July 724.583 40.254 0.000 0.000 40.254
August 720.222 40.011 0.000 0.000 40.011
September 697.100 39.488 0.000 0.000 39.488
October 687.969 28.511 0.000 0.000 28.511
November 603.403 20.728 0.431 0.047 20.775
December 561.833 15.069 1.111 0.125 15.195
           
Annual Sum or Average 7313.897 299.591 21.200 1.614 301.205
Minimum of Months 434.072 10.168 0.000 0.000 10.542
Maximum of Months 724.583 40.254 11.094 0.659 40.254



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 485.628 7.136 1.353 0.070 7.206
February 474.431 8.503 3.256 0.147 8.650
March 525.506 10.150 1.525 0.089 10.239
April 598.181 11.178 0.139 0.008 11.186
May 664.319 17.440 0.000 0.000 17.440
June 675.889 23.443 0.000 0.000 23.443
July 716.056 28.407 0.000 0.000 28.407
August 714.444 28.150 0.000 0.000 28.150
September 686.003 26.953 0.000 0.000 26.953
October 679.436 20.247 0.000 0.000 20.247
November 604.236 14.581 0.083 0.005 14.586
December 595.889 10.935 0.472 0.023 10.958
           
Annual Sum or Average 7420.016 207.122 6.828 0.342 207.464
Minimum of Months 474.431 7.136 0.000 0.000 7.206
Maximum of Months 716.056 28.407 3.256 0.147 28.407



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 484.394 11.850 1.806 0.146 11.995
February 454.311 12.577 8.222 0.320 12.897
March 521.511 15.459 2.417 0.100 15.559
April 590.194 17.794 0.278 0.012 17.806
May 695.181 26.730 0.000 0.000 26.730
June 698.472 33.228 0.000 0.000 33.228
July 728.667 39.820 0.000 0.000 39.820
August 725.444 39.757 0.000 0.000 39.757
September 702.639 36.562 0.000 0.000 36.562
October 706.689 29.952 0.000 0.000 29.952
November 622.458 21.004 0.361 0.026 21.030
December 591.333 16.293 0.861 0.072 16.365
           
Annual Sum or Average 7521.294 301.026 13.944 0.676 301.702
Minimum of Months 454.311 11.850 0.000 0.000 11.995
Maximum of Months 728.667 39.820 8.222 0.320 39.820



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 621.919 24.988 0.139 0.017 25.005
February 572.850 26.535 3.139 0.273 26.808
March 627.244 28.323 1.019 0.120 28.443
April 662.972 27.218 0.000 0.000 27.218
May 705.625 34.493 0.000 0.000 34.493
June 693.111 37.486 0.000 0.000 37.486
July 724.278 44.125 0.000 0.000 44.125
August 728.047 45.090 0.000 0.000 45.090
September 703.164 46.626 0.000 0.000 46.626
October 722.341 42.429 0.000 0.000 42.429
November 666.611 35.585 0.139 0.013 35.597
December 673.389 31.283 0.000 0.000 31.283
           
Annual Sum or Average 8101.552 424.179 4.436 0.423 424.602
Minimum of Months 572.850 24.988 0.000 0.000 25.005
Maximum of Months 728.047 46.626 3.139 0.273 46.626



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 668.461 20.680 0.000 0.000 20.680
February 594.944 19.964 0.556 0.037 20.001
March 652.961 20.511 0.156 0.010 20.522
April 655.836 19.882 0.000 0.000 19.882
May 695.681 24.888 0.000 0.000 24.888
June 685.250 26.599 0.000 0.000 26.599
July 716.361 31.046 0.000 0.000 31.046
August 718.842 31.853 0.000 0.000 31.853
September 692.350 32.415 0.000 0.000 32.415
October 718.130 31.727 0.000 0.000 31.727
November 679.500 27.160 0.000 0.000 27.160
December 690.569 25.040 0.000 0.000 25.040
           
Annual Sum or Average 8168.886 311.766 0.711 0.048 311.813
Minimum of Months 594.944 19.882 0.000 0.000 19.882
Maximum of Months 718.842 32.415 0.556 0.037 32.415



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 644.597 26.251 0.167 0.010 26.261
February 581.736 24.793 1.667 0.120 24.913
March 639.161 26.713 0.083 0.008 26.720
April 679.644 27.814 0.000 0.000 27.814
May 724.222 35.874 0.000 0.000 35.874
June 705.222 37.669 0.000 0.000 37.669
July 731.917 43.796 0.000 0.000 43.796
August 728.417 44.745 0.000 0.000 44.745
September 705.917 42.873 0.000 0.000 42.873
October 736.028 42.422 0.000 0.000 42.422
November 677.097 34.709 0.000 0.000 34.709
December 691.306 31.504 0.083 0.008 31.512
           
Annual Sum or Average 8245.264 419.161 2.000 0.146 419.307
Minimum of Months 581.736 24.793 0.000 0.000 24.913
Maximum of Months 736.028 44.745 1.667 0.120 44.745



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 585.042 17.758 0.194 0.022 17.780
February 556.039 21.573 3.017 0.238 21.811
March 613.461 25.198 1.394 0.163 25.362
April 667.011 26.212 0.000 0.000 26.212
May 710.764 35.494 0.000 0.000 35.494
June 700.361 39.104 0.000 0.000 39.104
July 730.833 45.514 0.000 0.000 45.514
August 725.894 44.970 0.000 0.000 44.970
September 700.136 44.340 0.000 0.000 44.340
October 716.927 37.592 0.000 0.000 37.592
November 656.431 29.311 0.083 0.002 29.313
December 646.250 23.733 0.222 0.021 23.753
           
Annual Sum or Average 8009.150 390.799 4.911 0.446 391.245
Minimum of Months 556.039 17.758 0.000 0.000 17.780
Maximum of Months 730.833 45.514 3.017 0.238 45.514



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 634.347 14.328 0.000 0.000 14.328
February 568.228 15.420 0.917 0.055 15.474
March 632.522 17.645 0.278 0.019 17.664
April 647.539 19.008 0.000 0.000 19.008
May 694.403 25.741 0.000 0.000 25.741
June 689.722 27.985 0.000 0.000 27.985
July 721.083 32.243 0.000 0.000 32.243
August 719.256 31.717 0.000 0.000 31.717
September 690.544 30.370 0.000 0.000 30.370
October 711.677 27.593 0.000 0.000 27.593
November 652.778 21.765 0.000 0.000 21.765
December 656.000 18.499 0.000 0.000 18.499
           
Annual Sum or Average 8018.100 282.313 1.194 0.074 282.386
Minimum of Months 568.228 14.328 0.000 0.000 14.328
Maximum of Months 721.083 32.243 0.917 0.055 32.243



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 618.358 19.933 0.194 0.013 19.945
February 567.775 20.166 2.750 0.175 20.341
March 634.442 23.843 0.542 0.047 23.891
April 678.653 26.886 0.000 0.000 26.886
May 725.894 36.567 0.000 0.000 36.567
June 704.833 38.947 0.000 0.000 38.947
July 731.861 44.781 0.000 0.000 44.781
August 733.667 44.592 0.000 0.000 44.592
September 706.083 40.861 0.000 0.000 40.861
October 732.861 38.756 0.000 0.000 38.756
November 671.431 29.234 0.222 0.010 29.244
December 670.069 24.911 0.000 0.000 24.911
           
Annual Sum or Average 8175.928 389.477 3.708 0.245 389.722
Minimum of Months 567.775 19.933 0.000 0.000 19.945
Maximum of Months 733.667 44.781 2.750 0.175 44.781



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 589.567 26.310 0.722 0.095 26.405
February 551.942 28.555 6.597 0.553 29.108
March 606.658 31.070 3.086 0.294 31.364
April 660.389 30.101 0.083 0.010 30.111
May 712.764 39.660 0.000 0.000 39.660
June 700.972 42.778 0.000 0.000 42.778
July 726.333 50.770 0.000 0.000 50.770
August 730.461 51.386 0.000 0.000 51.386
September 702.994 52.379 0.000 0.000 52.379
October 721.406 47.484 0.000 0.000 47.484
November 660.764 39.141 0.083 0.011 39.152
December 667.028 33.514 0.222 0.031 33.545
           
Annual Sum or Average 8031.278 473.147 10.794 0.994 474.141
Minimum of Months 551.942 26.310 0.000 0.000 26.405
Maximum of Months 730.461 52.379 6.597 0.553 52.379



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 647.606 22.446 0.083 0.002 22.448
February 580.361 22.414 1.583 0.118 22.532
March 634.983 23.589 0.547 0.041 23.630
April 668.192 23.165 0.000 0.000 23.165
May 710.800 30.396 0.000 0.000 30.396
June 692.667 32.283 0.000 0.000 32.283
July 725.889 38.065 0.000 0.000 38.065
August 723.083 38.554 0.000 0.000 38.554
September 699.722 38.659 0.000 0.000 38.659
October 721.378 37.475 0.000 0.000 37.475
November 673.875 31.389 0.000 0.000 31.389
December 683.750 27.981 0.000 0.000 27.981
           
Annual Sum or Average 8162.306 366.415 2.214 0.161 366.576
Minimum of Months 580.361 22.414 0.000 0.000 22.448
Maximum of Months 725.889 38.659 1.583 0.118 38.659



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 612.333 26.502 0.667 0.062 26.564
February 567.544 25.720 5.250 0.317 26.036
March 624.367 28.235 1.358 0.064 28.298
April 674.908 29.461 0.000 0.000 29.461
May 726.764 39.177 0.000 0.000 39.177
June 707.306 41.065 0.000 0.000 41.065
July 733.500 48.111 0.000 0.000 48.111
August 730.750 48.677 0.000 0.000 48.677
September 709.250 46.372 0.000 0.000 46.372
October 735.231 45.474 0.000 0.000 45.474
November 675.167 36.697 0.250 0.023 36.719
December 684.389 32.462 0.083 0.008 32.470
           
Annual Sum or Average 8181.508 447.952 7.608 0.473 448.425
Minimum of Months 567.544 25.720 0.000 0.000 26.036
Maximum of Months 735.231 48.677 5.250 0.317 48.677



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 555.264 20.823 0.783 0.096 20.919
February 536.856 25.208 9.181 0.640 25.848
March 605.703 29.464 2.983 0.315 29.779
April 662.519 29.732 0.000 0.000 29.732
May 718.333 40.422 0.000 0.000 40.422
June 702.694 43.953 0.000 0.000 43.953
July 728.778 51.795 0.000 0.000 51.795
August 729.133 51.608 0.000 0.000 51.608
September 702.703 51.296 0.000 0.000 51.296
October 717.628 44.604 0.000 0.000 44.604
November 651.694 34.432 0.167 0.022 34.454
December 647.583 27.528 0.583 0.074 27.602
           
Annual Sum or Average 7958.889 450.865 13.697 1.147 452.013
Minimum of Months 536.856 20.823 0.000 0.000 20.919
Maximum of Months 729.133 51.795 9.181 0.640 51.795



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 613.694 17.347 0.000 0.000 17.347
February 565.700 19.248 2.917 0.178 19.426
March 628.625 22.068 0.708 0.059 22.127
April 663.644 22.831 0.000 0.000 22.831
May 710.514 31.135 0.000 0.000 31.135
June 695.000 33.381 0.000 0.000 33.381
July 726.306 39.058 0.000 0.000 39.058
August 727.236 38.840 0.000 0.000 38.840
September 699.503 37.744 0.000 0.000 37.744
October 716.950 34.953 0.000 0.000 34.953
November 662.792 27.127 0.000 0.000 27.127
December 658.597 22.524 0.056 0.004 22.528
           
Annual Sum or Average 8068.561 346.258 3.681 0.242 346.499
Minimum of Months 565.700 17.347 0.000 0.000 17.347
Maximum of Months 727.236 39.058 2.917 0.178 39.058



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 598.417 22.051 0.417 0.038 22.089
February 558.306 22.933 6.806 0.377 23.310
March 624.600 27.045 2.222 0.153 27.198
April 673.639 29.397 0.000 0.000 29.397
May 725.361 40.064 0.000 0.000 40.064
June 707.222 42.299 0.000 0.000 42.299
July 734.000 49.280 0.000 0.000 49.280
August 730.750 49.211 0.000 0.000 49.211
September 709.417 45.889 0.000 0.000 45.889
October 733.222 43.806 0.000 0.000 43.806
November 668.708 33.063 0.306 0.023 33.086
December 670.069 27.663 0.083 0.001 27.665
           
Annual Sum or Average 8133.712 432.701 9.833 0.592 433.294
Minimum of Months 558.306 22.051 0.000 0.000 22.089
Maximum of Months 734.000 49.280 6.806 0.377 49.280



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 6.77 0.00 0.00
February 18.68 0.00 0.00
March 10.65 0.00 0.00
April 1.42 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 1.89 0.00 0.00
December 3.73 0.00 0.00
       
Annual Sum or Average 3.50 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 18.68 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1.72 0.00 0.00
February 6.17 0.00 0.00
March 5.12 0.00 0.00
April 0.51 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.33 0.00 0.00
December 0.41 0.00 0.00
       
Annual Sum or Average 1.16 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 6.17 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5.70 0.00 0.00
February 15.89 0.00 0.00
March 11.46 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.96 0.00 0.00
December 0.71 0.00 0.00
       
Annual Sum or Average 2.82 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 15.89 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 12.21 0.00 0.00
February 23.81 0.00 0.00
March 12.06 0.00 0.00
April 1.34 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 1.58 0.00 0.00
December 4.10 0.00 0.00
       
Annual Sum or Average 4.48 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 23.81 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 4.50 0.00 0.00
February 10.48 0.00 0.00
March 5.73 0.00 0.00
April 0.54 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.34 0.00 0.00
December 1.51 0.00 0.00
       
Annual Sum or Average 1.87 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 10.48 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 6.56 0.00 0.00
February 15.95 0.00 0.00
March 4.50 0.00 0.00
April 0.58 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 1.21 0.00 0.00
December 3.24 0.00 0.00
       
Annual Sum or Average 2.59 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 15.95 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.51 0.00 0.00
February 9.02 0.00 0.00
March 3.59 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.39 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 1.07 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 9.02 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.00 0.00 0.00
February 2.42 0.00 0.00
March 0.60 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.24 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2.42 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.41 0.00 0.00
February 5.62 0.00 0.00
March 0.33 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.32 0.00 0.00
       
Annual Sum or Average 0.52 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 5.62 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.66 0.00 0.00
February 7.93 0.00 0.00
March 4.93 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.08 0.00 0.00
December 0.63 0.00 0.00
       
Annual Sum or Average 1.14 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 7.93 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.00 0.00 0.00
February 3.55 0.00 0.00
March 1.11 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.37 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 3.55 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.54 0.00 0.00
February 8.21 0.00 0.00
March 2.01 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.44 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.88 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 8.21 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2.46 0.00 0.00
February 15.82 0.00 0.00
March 7.60 0.00 0.00
April 0.27 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.29 0.00 0.00
December 0.81 0.00 0.00
       
Annual Sum or Average 2.18 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 15.82 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.08 0.00 0.00
February 5.94 0.00 0.00
March 1.86 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.62 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 5.94 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2.42 0.00 0.00
February 13.67 0.00 0.00
March 2.48 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.91 0.00 0.00
December 0.30 0.00 0.00
       
Annual Sum or Average 1.56 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 13.67 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2.47 0.00 0.00
February 18.26 0.00 0.00
March 8.12 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.59 0.00 0.00
December 1.91 0.00 0.00
       
Annual Sum or Average 2.51 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 18.26 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.00 0.00 0.00
February 8.88 0.00 0.00
March 2.65 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.19 0.00 0.00
       
Annual Sum or Average 0.92 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 8.88 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1.50 0.00 0.00
February 16.33 0.00 0.00
March 5.99 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.92 0.00 0.00
December 0.06 0.00 0.00
       
Annual Sum or Average 1.97 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 16.33 0.00 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.15
February 0.00 0.00 0.19
March 0.00 0.00 0.18
April 0.00 0.00 0.17
May 0.00 0.00 0.23
June 0.00 0.00 0.31
July 0.00 0.00 0.38
August 0.00 0.00 0.39
September 0.00 0.00 0.42
October 0.00 0.00 0.32
November 0.00 0.00 0.26
December 0.00 0.00 0.21
       
Annual Sum or Average 0.00 0.00 0.27
Minimum of Months 0.00 0.00 0.15
Maximum of Months 0.00 0.00 0.42



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.14
February 0.00 0.00 0.16
March 0.00 0.00 0.14
April 0.00 0.00 0.14
May 0.00 0.00 0.19
June 0.00 0.00 0.26
July 0.00 0.00 0.32
August 0.00 0.00 0.33
September 0.00 0.00 0.35
October 0.00 0.00 0.28
November 0.00 0.00 0.23
December 0.00 0.00 0.19
       
Annual Sum or Average 0.00 0.00 0.23
Minimum of Months 0.00 0.00 0.14
Maximum of Months 0.00 0.00 0.35



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.18
February 0.00 0.00 0.19
March 0.00 0.00 0.19
April 0.00 0.00 0.20
May 0.00 0.00 0.27
June 0.00 0.00 0.35
July 0.00 0.00 0.41
August 0.00 0.00 0.42
September 0.00 0.00 0.42
October 0.00 0.00 0.36
November 0.00 0.00 0.28
December 0.00 0.00 0.23
       
Annual Sum or Average 0.00 0.00 0.29
Minimum of Months 0.00 0.00 0.18
Maximum of Months 0.00 0.00 0.42



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.10
February 0.00 0.00 0.15
March 0.00 0.00 0.16
April 0.00 0.00 0.16
May 0.00 0.00 0.24
June 0.00 0.00 0.33
July 0.00 0.00 0.39
August 0.00 0.00 0.39
September 0.00 0.00 0.40
October 0.00 0.00 0.27
November 0.00 0.00 0.21
December 0.00 0.00 0.14
       
Annual Sum or Average 0.00 0.00 0.25
Minimum of Months 0.00 0.00 0.10
Maximum of Months 0.00 0.00 0.40



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.08
February 0.00 0.00 0.11
March 0.00 0.00 0.11
April 0.00 0.00 0.13
May 0.00 0.00 0.20
June 0.00 0.00 0.28
July 0.00 0.00 0.33
August 0.00 0.00 0.33
September 0.00 0.00 0.33
October 0.00 0.00 0.23
November 0.00 0.00 0.17
December 0.00 0.00 0.12
       
Annual Sum or Average 0.00 0.00 0.20
Minimum of Months 0.00 0.00 0.08
Maximum of Months 0.00 0.00 0.33



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.12
February 0.00 0.00 0.15
March 0.00 0.00 0.16
April 0.00 0.00 0.19
May 0.00 0.00 0.28
June 0.00 0.00 0.36
July 0.00 0.00 0.42
August 0.00 0.00 0.42
September 0.00 0.00 0.40
October 0.00 0.00 0.31
November 0.00 0.00 0.23
December 0.00 0.00 0.17
       
Annual Sum or Average 0.00 0.00 0.27
Minimum of Months 0.00 0.00 0.12
Maximum of Months 0.00 0.00 0.42



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.23
February 0.00 0.00 0.27
March 0.00 0.00 0.26
April 0.00 0.00 0.25
May 0.00 0.00 0.31
June 0.00 0.00 0.35
July 0.00 0.00 0.40
August 0.00 0.00 0.41
September 0.00 0.00 0.45
October 0.00 0.00 0.39
November 0.00 0.00 0.34
December 0.00 0.00 0.29
       
Annual Sum or Average 0.00 0.00 0.33
Minimum of Months 0.00 0.00 0.23
Maximum of Months 0.00 0.00 0.45



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.22
February 0.00 0.00 0.24
March 0.00 0.00 0.22
April 0.00 0.00 0.22
May 0.00 0.00 0.27
June 0.00 0.00 0.29
July 0.00 0.00 0.33
August 0.00 0.00 0.34
September 0.00 0.00 0.37
October 0.00 0.00 0.34
November 0.00 0.00 0.30
December 0.00 0.00 0.27
       
Annual Sum or Average 0.00 0.00 0.29
Minimum of Months 0.00 0.00 0.22
Maximum of Months 0.00 0.00 0.37



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.26
February 0.00 0.00 0.28
March 0.00 0.00 0.26
April 0.00 0.00 0.28
May 0.00 0.00 0.36
June 0.00 0.00 0.39
July 0.00 0.00 0.44
August 0.00 0.00 0.45
September 0.00 0.00 0.45
October 0.00 0.00 0.43
November 0.00 0.00 0.36
December 0.00 0.00 0.32
       
Annual Sum or Average 0.00 0.00 0.36
Minimum of Months 0.00 0.00 0.26
Maximum of Months 0.00 0.00 0.45



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.16
February 0.00 0.00 0.22
March 0.00 0.00 0.23
April 0.00 0.00 0.24
May 0.00 0.00 0.32
June 0.00 0.00 0.37
July 0.00 0.00 0.42
August 0.00 0.00 0.41
September 0.00 0.00 0.42
October 0.00 0.00 0.34
November 0.00 0.00 0.28
December 0.00 0.00 0.21
       
Annual Sum or Average 0.00 0.00 0.30
Minimum of Months 0.00 0.00 0.16
Maximum of Months 0.00 0.00 0.42



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.15
February 0.00 0.00 0.18
March 0.00 0.00 0.19
April 0.00 0.00 0.21
May 0.00 0.00 0.28
June 0.00 0.00 0.31
July 0.00 0.00 0.35
August 0.00 0.00 0.34
September 0.00 0.00 0.34
October 0.00 0.00 0.30
November 0.00 0.00 0.24
December 0.00 0.00 0.20
       
Annual Sum or Average 0.00 0.00 0.26
Minimum of Months 0.00 0.00 0.15
Maximum of Months 0.00 0.00 0.35



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.19
February 0.00 0.00 0.22
March 0.00 0.00 0.23
April 0.00 0.00 0.27
May 0.00 0.00 0.36
June 0.00 0.00 0.40
July 0.00 0.00 0.45
August 0.00 0.00 0.45
September 0.00 0.00 0.42
October 0.00 0.00 0.39
November 0.00 0.00 0.30
December 0.00 0.00 0.24
       
Annual Sum or Average 0.00 0.00 0.33
Minimum of Months 0.00 0.00 0.19
Maximum of Months 0.00 0.00 0.45



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.24
February 0.00 0.00 0.30
March 0.00 0.00 0.29
April 0.00 0.00 0.28
May 0.00 0.00 0.36
June 0.00 0.00 0.41
July 0.00 0.00 0.47
August 0.00 0.00 0.47
September 0.00 0.00 0.51
October 0.00 0.00 0.44
November 0.00 0.00 0.37
December 0.00 0.00 0.31
       
Annual Sum or Average 0.00 0.00 0.37
Minimum of Months 0.00 0.00 0.24
Maximum of Months 0.00 0.00 0.51



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.23
February 0.00 0.00 0.26
March 0.00 0.00 0.25
April 0.00 0.00 0.25
May 0.00 0.00 0.32
June 0.00 0.00 0.35
July 0.00 0.00 0.40
August 0.00 0.00 0.40
September 0.00 0.00 0.43
October 0.00 0.00 0.40
November 0.00 0.00 0.34
December 0.00 0.00 0.29
       
Annual Sum or Average 0.00 0.00 0.33
Minimum of Months 0.00 0.00 0.23
Maximum of Months 0.00 0.00 0.43



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.27
February 0.00 0.00 0.30
March 0.00 0.00 0.29
April 0.00 0.00 0.31
May 0.00 0.00 0.41
June 0.00 0.00 0.44
July 0.00 0.00 0.51
August 0.00 0.00 0.51
September 0.00 0.00 0.51
October 0.00 0.00 0.48
November 0.00 0.00 0.40
December 0.00 0.00 0.34
       
Annual Sum or Average 0.00 0.00 0.40
Minimum of Months 0.00 0.00 0.27
Maximum of Months 0.00 0.00 0.51



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.19
February 0.00 0.00 0.26
March 0.00 0.00 0.27
April 0.00 0.00 0.28
May 0.00 0.00 0.37
June 0.00 0.00 0.42
July 0.00 0.00 0.48
August 0.00 0.00 0.47
September 0.00 0.00 0.49
October 0.00 0.00 0.41
November 0.00 0.00 0.33
December 0.00 0.00 0.25
       
Annual Sum or Average 0.00 0.00 0.35
Minimum of Months 0.00 0.00 0.19
Maximum of Months 0.00 0.00 0.49



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.18
February 0.00 0.00 0.22
March 0.00 0.00 0.23
April 0.00 0.00 0.24
May 0.00 0.00 0.32
June 0.00 0.00 0.36
July 0.00 0.00 0.41
August 0.00 0.00 0.41
September 0.00 0.00 0.41
October 0.00 0.00 0.37
November 0.00 0.00 0.29
December 0.00 0.00 0.23
       
Annual Sum or Average 0.00 0.00 0.31
Minimum of Months 0.00 0.00 0.18
Maximum of Months 0.00 0.00 0.41



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.22
February 0.00 0.00 0.26
March 0.00 0.00 0.28
April 0.00 0.00 0.31
May 0.00 0.00 0.41
June 0.00 0.00 0.45
July 0.00 0.00 0.51
August 0.00 0.00 0.51
September 0.00 0.00 0.50
October 0.00 0.00 0.45
November 0.00 0.00 0.35
December 0.00 0.00 0.28
       
Annual Sum or Average 0.00 0.00 0.38
Minimum of Months 0.00 0.00 0.22
Maximum of Months 0.00 0.00 0.51



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.04
March 0.00 0.00 0.04
April 0.00 0.00 0.03
May 0.00 0.00 0.03
June 0.00 0.00 0.03
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.03
October 0.00 0.00 0.03
November 0.00 0.00 0.03
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.04



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.04
March 0.00 0.00 0.04
April 0.00 0.00 0.03
May 0.00 0.00 0.03
June 0.00 0.00 0.03
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.03
October 0.00 0.00 0.03
November 0.00 0.00 0.03
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.04



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.04
March 0.00 0.00 0.04
April 0.00 0.00 0.03
May 0.00 0.00 0.03
June 0.00 0.00 0.03
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.03
October 0.00 0.00 0.03
November 0.00 0.00 0.03
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.04



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.04
March 0.00 0.00 0.04
April 0.00 0.00 0.03
May 0.00 0.00 0.03
June 0.00 0.00 0.03
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.03
October 0.00 0.00 0.03
November 0.00 0.00 0.04
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.04



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.04
March 0.00 0.00 0.04
April 0.00 0.00 0.03
May 0.00 0.00 0.03
June 0.00 0.00 0.03
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.03
October 0.00 0.00 0.03
November 0.00 0.00 0.04
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.04



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.04
March 0.00 0.00 0.04
April 0.00 0.00 0.03
May 0.00 0.00 0.03
June 0.00 0.00 0.03
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.03
October 0.00 0.00 0.03
November 0.00 0.00 0.03
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.04



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.04
March 0.00 0.00 0.04
April 0.00 0.00 0.03
May 0.00 0.00 0.03
June 0.00 0.00 0.03
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.03
October 0.00 0.00 0.03
November 0.00 0.00 0.04
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.04



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.04
March 0.00 0.00 0.04
April 0.00 0.00 0.03
May 0.00 0.00 0.03
June 0.00 0.00 0.03
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.03
October 0.00 0.00 0.03
November 0.00 0.00 0.04
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.04



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.04
March 0.00 0.00 0.04
April 0.00 0.00 0.03
May 0.00 0.00 0.03
June 0.00 0.00 0.03
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.03
October 0.00 0.00 0.03
November 0.00 0.00 0.04
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.04



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.04
March 0.00 0.00 0.04
April 0.00 0.00 0.03
May 0.00 0.00 0.03
June 0.00 0.00 0.03
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.03
October 0.00 0.00 0.03
November 0.00 0.00 0.04
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.04



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.04
March 0.00 0.00 0.04
April 0.00 0.00 0.03
May 0.00 0.00 0.03
June 0.00 0.00 0.03
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.03
October 0.00 0.00 0.03
November 0.00 0.00 0.04
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.04



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.04
March 0.00 0.00 0.04
April 0.00 0.00 0.03
May 0.00 0.00 0.03
June 0.00 0.00 0.03
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.03
October 0.00 0.00 0.03
November 0.00 0.00 0.04
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.04



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.04
March 0.00 0.00 0.04
April 0.00 0.00 0.03
May 0.00 0.00 0.03
June 0.00 0.00 0.03
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.03
October 0.00 0.00 0.03
November 0.00 0.00 0.04
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.04



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.04
March 0.00 0.00 0.04
April 0.00 0.00 0.03
May 0.00 0.00 0.03
June 0.00 0.00 0.03
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.03
October 0.00 0.00 0.03
November 0.00 0.00 0.04
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.04



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.04
March 0.00 0.00 0.04
April 0.00 0.00 0.03
May 0.00 0.00 0.03
June 0.00 0.00 0.03
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.03
October 0.00 0.00 0.03
November 0.00 0.00 0.04
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.04



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.04
March 0.00 0.00 0.04
April 0.00 0.00 0.03
May 0.00 0.00 0.03
June 0.00 0.00 0.03
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.03
October 0.00 0.00 0.03
November 0.00 0.00 0.04
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.04



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.04
March 0.00 0.00 0.04
April 0.00 0.00 0.03
May 0.00 0.00 0.03
June 0.00 0.00 0.03
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.03
October 0.00 0.00 0.03
November 0.00 0.00 0.04
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.04



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.04
March 0.00 0.00 0.04
April 0.00 0.00 0.03
May 0.00 0.00 0.03
June 0.00 0.00 0.03
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.03
October 0.00 0.00 0.03
November 0.00 0.00 0.04
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.04



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: BREEZEWAY

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 102.19 0.84
February 101.78 2.73
March 111.75 2.59
April 100.96 0.66
May 119.26 0.55
June 152.08 0.22
July 180.20 0.17
August 186.64 0.18
September 194.78 0.14
October 154.87 0.30
November 132.60 0.49
December 118.03 0.52
     
Annual Sum or Average 1655.12 9.38
Minimum of Months 100.96 0.14
Maximum of Months 194.78 2.73



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 92.04 0.30
February 81.72 1.08
March 84.99 1.75
April 77.61 1.00
May 90.95 1.16
June 119.57 0.40
July 141.23 0.24
August 147.05 0.20
September 150.03 0.09
October 128.10 0.42
November 112.08 0.43
December 105.20 0.21
     
Annual Sum or Average 1330.58 7.26
Minimum of Months 77.61 0.09
Maximum of Months 150.03 1.75



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 117.35 0.41
February 100.58 1.64
March 111.14 1.25
April 112.08 0.01
May 139.22 0.03
June 168.34 0.08
July 197.40 0.10
August 204.45 0.08
September 192.68 0.09
October 175.49 0.03
November 142.33 0.22
December 131.46 0.12
     
Annual Sum or Average 1792.53 4.08
Minimum of Months 100.58 0.01
Maximum of Months 204.45 1.64



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 68.20 3.25
February 76.61 5.04
March 95.44 3.66
April 95.60 0.70
May 123.92 0.22
June 160.70 0.06
July 187.60 0.13
August 185.83 0.16
September 181.61 0.16
October 128.89 0.70
November 100.51 1.11
December 81.42 1.69
     
Annual Sum or Average 1486.33 16.87
Minimum of Months 68.20 0.06
Maximum of Months 187.60 5.04



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 57.78 2.78
February 56.44 3.14
March 68.73 3.03
April 72.27 1.35
May 95.62 0.80
June 128.22 0.13
July 148.69 0.12
August 146.24 0.18
September 137.05 0.25
October 102.06 1.08
November 79.97 1.36
December 68.18 1.87
     
Annual Sum or Average 1161.25 16.09
Minimum of Months 56.44 0.12
Maximum of Months 148.69 3.14



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 81.33 0.58
February 74.48 2.01
March 94.61 0.81
April 106.58 0.05
May 143.32 0.03
June 176.16 0.09
July 203.70 0.10
August 203.02 0.08
September 179.42 0.09
October 149.45 0.04
November 109.37 0.32
December 93.13 0.47
     
Annual Sum or Average 1614.58 4.68
Minimum of Months 74.48 0.03
Maximum of Months 203.70 2.01



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 149.58 0.07
February 146.84 0.97
March 159.82 0.85
April 149.15 0.18
May 170.77 0.06
June 180.91 0.04
July 204.97 0.03
August 210.09 0.10
September 219.71 0.03
October 203.98 0.06
November 181.75 0.12
December 169.39 0.04
     
Annual Sum or Average 2146.97 2.55
Minimum of Months 146.84 0.03
Maximum of Months 219.71 0.97



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 142.60 0.06
February 126.68 0.21
March 131.91 0.48
April 123.54 0.24
May 138.72 0.20
June 143.95 0.17
July 160.81 0.17
August 165.46 0.14
September 169.74 0.09
October 174.10 0.10
November 159.61 0.05
December 156.66 0.06
     
Annual Sum or Average 1793.79 1.97
Minimum of Months 123.54 0.05
Maximum of Months 174.10 0.48



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 169.31 0.08
February 146.98 0.13
March 161.29 0.03
April 164.45 0.00
May 195.66 0.00
June 199.91 0.04
July 224.80 0.02
August 230.96 0.06
September 217.80 0.02
October 226.67 0.01
November 193.36 0.03
December 185.61 0.03
     
Annual Sum or Average 2316.80 0.45
Minimum of Months 146.98 0.00
Maximum of Months 230.96 0.13



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 107.09 0.72
February 117.03 2.18
March 140.77 1.54
April 143.15 0.16
May 176.58 0.02
June 190.63 0.04
July 213.19 0.02
August 209.43 0.06
September 205.36 0.03
October 174.35 0.34
November 143.88 0.35
December 124.58 0.26
     
Annual Sum or Average 1946.04 5.72
Minimum of Months 107.09 0.02
Maximum of Months 213.19 2.18



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 98.85 0.71
February 95.38 1.19
March 112.22 1.02
April 117.38 0.29
May 144.70 0.03
June 153.77 0.05
July 169.19 0.04
August 164.74 0.08
September 155.04 0.13
October 144.34 0.40
November 121.44 0.41
December 111.22 0.32
     
Annual Sum or Average 1588.27 4.65
Minimum of Months 95.38 0.03
Maximum of Months 169.19 1.19



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 126.51 0.03
February 115.94 0.53
March 141.75 0.21
April 157.90 0.00
May 200.33 0.00
June 208.55 0.02
July 231.89 0.03
August 229.46 0.02
September 203.33 0.06
October 199.57 0.01
November 155.65 0.04
December 140.88 0.01
     
Annual Sum or Average 2111.75 0.97
Minimum of Months 115.94 0.00
Maximum of Months 231.89 0.53



Table of Contents

Report: HEATING AND COOLING LOADS

For: ATTIC

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 141.67 0.21
February 133.91 1.56
March 163.48 0.57
April 175.69 0.00
May 223.71 0.00
June 229.43 0.03
July 259.19 0.01
August 259.12 0.04
September 234.51 0.01
October 233.49 0.01
November 179.81 0.17
December 159.07 0.03
     
Annual Sum or Average 2393.07 2.65
Minimum of Months 133.91 0.00
Maximum of Months 259.19 1.56



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 174.24 0.09
February 154.98 1.28
March 173.94 0.29
April 178.34 0.00
May 220.48 0.00
June 223.81 0.04
July 254.40 0.01
August 258.96 0.04
September 241.67 0.01
October 249.97 0.01
November 207.98 0.10
December 194.56 0.02
     
Annual Sum or Average 2533.33 1.90
Minimum of Months 154.98 0.00
Maximum of Months 258.96 1.28



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 155.65 0.22
February 155.41 2.51
March 173.07 2.02
April 163.91 0.18
May 196.72 0.08
June 205.83 0.07
July 235.58 0.03
August 239.32 0.10
September 244.54 0.05
October 227.55 0.16
November 196.95 0.12
December 178.72 0.07
     
Annual Sum or Average 2373.26 5.60
Minimum of Months 155.41 0.03
Maximum of Months 244.54 2.51



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 114.26 0.65
February 113.76 1.49
March 134.61 1.09
April 135.98 0.27
May 169.04 0.05
June 175.67 0.03
July 197.50 0.02
August 195.81 0.09
September 187.63 0.10
October 180.29 0.40
November 146.27 0.31
December 129.97 0.18
     
Annual Sum or Average 1880.78 4.68
Minimum of Months 113.76 0.02
Maximum of Months 197.50 1.49



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 148.23 0.11
February 135.32 0.36
March 145.19 0.78
April 138.58 0.21
May 165.07 0.14
June 169.29 0.08
July 191.84 0.04
August 195.08 0.05
September 194.99 0.01
October 198.77 0.12
November 175.81 0.10
December 166.82 0.02
     
Annual Sum or Average 2024.99 2.02
Minimum of Months 135.32 0.01
Maximum of Months 198.77 0.78



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:15:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 123.47 1.12
February 135.21 4.06
March 163.05 2.01
April 161.38 0.20
May 200.71 0.09
June 212.17 0.04
July 241.14 0.03
August 240.14 0.10
September 237.42 0.06
October 209.67 0.36
November 168.52 0.41
December 143.42 0.34
     
Annual Sum or Average 2236.30 8.83