Program Version:EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:19
Tabular Output Report in Format: HTML
Building: US+MF+CZ2B+gasfurnace+heatedbsmt+IECC_2018
Environment: ANNUAL ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2021-05-12 10:19:39
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 931049.26 | 23.87 | 31.66 |
Net Site Energy | 931049.26 | 23.87 | 31.66 |
Total Source Energy | 2073559.69 | 53.16 | 70.52 |
Net Source Energy | 2073559.69 | 53.16 | 70.52 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.22 |
Net Conditioned Building Area | 29404.35 |
Unconditioned Building Area | 9600.87 |
Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 0.00 | 50801.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 138372.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 41293.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18809.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 261700.64 | 163973.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 50771.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 205327.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330767.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 510946.85 | 420102.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330767.30 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | General | 0.00 | 50801.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 138372.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 41293.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 18809.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 9418.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 4809.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_dryer | 3888.48 | 79268.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_range | 0.00 | 67443.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_mels | 143183.64 | 17261.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 59304.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 32504.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Ventilation | 18266.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330767.30 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 205327.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 6.43 | 8.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 |
Other | 8.90 | 5.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 17.38 | 14.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 4.85 | 6.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 |
Other | 6.71 | 4.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 13.10 | 10.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 510946.850 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 510946.850 | 100.00 |
Total On-Site and Utility Electric Sources | 510946.850 | 100.00 |
Total Electricity End Uses | 510946.850 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 330767.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 330767.30 | 100.00 |
Total Water End Uses | 330767.30 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 287.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 184.67 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |COILLOADS
| MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNITHEATEDBSMT | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |HEATING AND COOLING LOADS
| HEATEDBSMT | BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:19 |
RunPeriod | ANNUAL |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [ft] | 2654.33 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Above Ground Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Above Ground Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
HEATEDBSMT | 7794.39 | Yes | Yes | 58539.52 | 1.00 | 185.02 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.16 | No | Yes | 30553.25 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 4.4634 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6220 | 600.28 | 4.4634 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 4.4634 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 4.4634 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6220 | 600.28 | 4.4634 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 4.4634 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 4.4634 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6220 | 600.28 | 4.4634 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 4.4634 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 4.4634 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6220 | 600.28 | 4.4634 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 4.4634 |
ATTIC | 7802.71 | No | Yes | 52795.56 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 4.4634 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 4.4634 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 4.4634 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6220 | 600.28 | 4.4634 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6220 | 600.28 | 4.4634 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 4.4634 |
Total | 39005.22 | 325627.71 | 16363.00 | 0.00 | 2126.74 | 2126.74 | 0.3446 | 1083.48 | 2.4729 | |||
Conditioned Total | 29404.35 | 242278.90 | 15481.63 | 0.00 | 2126.74 | 2126.74 | 0.4571 | 816.79 | 3.2803 | |||
Unconditioned Total | 9600.87 | 83348.81 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 28-JUN-19:10 | 01-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 01-JAN-08:09 |
Heating | 0.00 | 89.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 54.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 13.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 4.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 42.43 | 17.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 12.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 169.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 126.71 | 276.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | General | 0.00 | 89.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 54.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 13.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 4.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 2.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_dryer | 0.51 | 7.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_range | 0.00 | 7.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_mels | 23.39 | 2.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 9.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 10.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Ventilation | 2.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 169.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Gasoline [kBtu] | Source Diesel [kBtu] | Source Coal [kBtu] | Source Fuel Oil No 1 [kBtu] | Source Fuel Oil No 2 [kBtu] | Source Propane [kBtu] | Source Other Fuel 1 [kBtu] | Source Other Fuel 2 [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 0.00 | 55069.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 438226.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 130776.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 59568.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 828805.92 | 177746.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 160791.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 222574.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1618168.67 | 455391.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 1.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 28.19 | 6.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 7.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 55.03 | 15.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 11.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21.25 | 4.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 5.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 41.49 | 11.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
ZoneHVAC:EnergyRecoveryVentilatorUser-Specified Supply Air Flow Rate [ft3/min] | User-Specified Exhaust Air Flow Rate [ft3/min] | |
ERV_UNITHEATEDBSMT | 44.99 | 44.99 |
ERV_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT3_BACKROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT3_FRONTROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT1_FRONTROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT2_BACKROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT2_FRONTROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT1_BACKROW_TOPFLOOR | 44.99 | 44.99 |
User-Specified Maximum Flow Rate [ft3/min] | Design Size Maximum Flow Rate [ft3/min] | |
OASUPPLYFAN_UNITHEATEDBSMT | 44.99 | |
OAEXHAUSTFAN_UNITHEATEDBSMT | 44.99 | |
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR | 44.99 | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 492.96 | |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 308.08 | |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 372.00 | |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 489.23 | |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 310.30 | |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 367.21 | |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 507.70 | |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 315.84 | |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 382.98 | |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 504.41 | |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 317.95 | |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 381.25 | |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 585.56 | |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 393.66 | |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 460.82 | |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 588.90 | |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 398.83 | |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 464.85 | |
SUPPLY FAN_UNITHEATEDBSMT | 302.42 |
User-Specified Nominal Supply Air Flow Rate [ft3/min] | |
OA_HEAT_RECOVERY_UNITHEATEDBSMT | 44.99 |
OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR | 44.99 |
Design Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNITHEATEDBSMT | 302.42 |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 492.96 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 308.08 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 372.00 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 489.23 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 310.30 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 367.21 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 507.70 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 315.84 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 382.98 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 504.41 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 317.95 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 381.25 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 464.85 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 460.82 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 585.56 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 398.83 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 393.66 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 588.90 |
Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | Sum of Air Terminal Maximum Flow Rates [ft3/min] | Adjusted Heating Design Air Flow Rate [ft3/min] | Adjusted Cooling Design Air Flow Rate [ft3/min] | Adjusted Main Design Air Flow Rate [ft3/min] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 492.96 | 492.96 | 492.96 | 492.96 | 492.96 | 492.96 | 1.00 | 1.00 | 492.96 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 308.08 | 308.08 | 308.08 | 308.08 | 308.08 | 308.08 | 1.00 | 1.00 | 308.08 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 372.00 | 372.00 | 372.00 | 372.00 | 372.00 | 372.00 | 1.00 | 1.00 | 372.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 489.23 | 489.23 | 489.23 | 489.23 | 489.23 | 489.23 | 1.00 | 1.00 | 489.23 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 310.30 | 310.30 | 310.30 | 310.30 | 310.30 | 310.30 | 1.00 | 1.00 | 310.30 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 367.21 | 367.21 | 367.21 | 367.21 | 367.21 | 367.21 | 1.00 | 1.00 | 367.21 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 507.70 | 507.70 | 507.70 | 507.70 | 507.70 | 507.70 | 1.00 | 1.00 | 507.70 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 315.84 | 315.84 | 315.84 | 315.84 | 315.84 | 315.84 | 1.00 | 1.00 | 315.84 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 382.98 | 382.98 | 382.98 | 382.98 | 382.98 | 382.98 | 1.00 | 1.00 | 382.98 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 504.41 | 504.41 | 504.41 | 504.41 | 504.41 | 504.41 | 1.00 | 1.00 | 504.41 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 317.95 | 317.95 | 317.95 | 317.95 | 317.95 | 317.95 | 1.00 | 1.00 | 317.95 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 381.25 | 381.25 | 381.25 | 381.25 | 381.25 | 381.25 | 1.00 | 1.00 | 381.25 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 585.56 | 585.56 | 585.56 | 585.56 | 585.56 | 585.56 | 1.00 | 1.00 | 585.56 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 393.66 | 393.66 | 393.66 | 393.66 | 393.66 | 393.66 | 1.00 | 1.00 | 393.66 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 460.82 | 460.82 | 460.82 | 460.82 | 460.82 | 460.82 | 1.00 | 1.00 | 460.82 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 588.90 | 588.90 | 588.90 | 588.90 | 588.90 | 588.90 | 1.00 | 1.00 | 588.90 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 398.83 | 398.83 | 398.83 | 398.83 | 398.83 | 398.83 | 1.00 | 1.00 | 398.83 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 464.85 | 464.85 | 464.85 | 464.85 | 464.85 | 464.85 | 1.00 | 1.00 | 464.85 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 302.42 | 302.42 | 302.42 | 302.42 | 302.42 | 302.42 | 1.00 | 1.00 | 302.42 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 492.96 | 1.13 | 0.800420 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 308.08 | 0.718847 | 0.800044 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 372.00 | 0.919128 | 0.800573 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 489.23 | 1.11 | 0.800834 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 310.30 | 0.714038 | 0.800949 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 367.21 | 0.851323 | 0.800311 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 507.70 | 1.15 | 0.800294 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 315.84 | 0.719504 | 0.800536 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 382.98 | 0.882871 | 0.800312 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 504.41 | 1.13 | 0.800081 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 317.95 | 0.723806 | 0.800789 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 381.25 | 0.868657 | 0.800478 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 585.56 | 1.31 | 0.800838 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 393.66 | 0.879356 | 0.800643 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 460.82 | 1.05 | 0.800014 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 588.90 | 1.32 | 0.800984 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 398.83 | 0.889898 | 0.800058 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 464.85 | 1.05 | 0.800323 |
DX COOLING COIL_UNITHEATEDBSMT | 302.42 | 0.728677 | 0.800977 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Heating Capacity [Btu/h] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 492.96 | 492.96 | 492.96 | 5327.33 | 1.13 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 308.08 | 308.08 | 308.08 | 3940.24 | 0.718847 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 372.00 | 372.00 | 372.00 | 5327.24 | 0.919128 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 489.23 | 489.23 | 489.23 | 5328.32 | 1.11 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 310.30 | 310.30 | 310.30 | 3940.24 | 0.714038 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 367.21 | 367.21 | 367.21 | 5323.04 | 0.851323 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 507.70 | 507.70 | 507.70 | 4741.68 | 1.15 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 315.84 | 315.84 | 315.84 | 3940.24 | 0.719504 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 382.98 | 382.98 | 382.98 | 4743.24 | 0.882871 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 504.41 | 504.41 | 504.41 | 4743.65 | 1.13 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 317.95 | 317.95 | 317.95 | 3940.24 | 0.723806 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 381.25 | 381.25 | 381.25 | 4739.92 | 0.868657 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 585.56 | 585.56 | 585.56 | 6473.49 | 1.31 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 393.66 | 393.66 | 393.66 | 4838.16 | 0.879356 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 460.82 | 460.82 | 460.82 | 6475.51 | 1.05 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 588.90 | 588.90 | 588.90 | 6475.25 | 1.32 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 398.83 | 398.83 | 398.83 | 4837.96 | 0.889898 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 464.85 | 464.85 | 464.85 | 6473.39 | 1.05 | 1.00 |
ACANDF_UNITHEATEDBSMT | 302.42 | 302.42 | 302.42 | 11812.49 | 0.728677 | 1.00 |
Design Size Nominal Capacity [Btu/h] | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 5327.33 |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 3940.24 |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 5327.24 |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 5328.32 |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 3940.24 |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 5323.04 |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 4741.68 |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 3940.24 |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 4743.24 |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 4743.65 |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 3940.24 |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 4739.92 |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 6473.49 |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 4838.16 |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 6475.51 |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 6475.25 |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 4837.96 |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 6473.39 |
MAIN FUEL HEATING COIL_UNITHEATEDBSMT | 11812.49 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 2.09 |
Design Flow Rate [ft3/min] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
BGWALL_UPPER_LDF | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
BGWALL_UPPER_SDR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
BGWALL_UPPER_LDB | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
BGWALL_UPPER_SDL | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
VersionVersion ID | |
1 | 9.5 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | No | Yes | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.200 | 0.200 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 55.29 | 58.26 | 64.02 | 69.48 | 79.79 | 85.23 | 86.72 | 83.97 | 77.59 | 69.67 | 61.86 | 56.70 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {ft} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Sensor Height Above Ground {ft} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 32.810 | 0.140 | 885.870 | 4.921 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {ft} | Standard Pressure at Elevation {psi} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 2654.33 | 13. | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{F} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} | Fixed Default Water Mains Temperature{F} | |
1 | Correlation | NA | 70.99 | 34.74 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | US+MF+CZ2B+gasfurnace+heatedbsmt+IECC_2018 | 0.000 | Suburbs | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Gradient Coefficient {F/ft} | |
1 | 0.220 | 1213.970 | 0.003566 |
Material Name | ThermalResistance {m2-K/w} | Roughness | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | Absorptance:Thermal | Absorptance:Solar | Absorptance:Visible | |
1 | SHEATHING_CONSOL_LAYER | 0.1351 | Rough | 0.0417 | 9.402E-002 | 42.764 | 0.280 | 0.9000 | 0.7000 | 0.7000 |
2 | CEIL_CONSOL_LAYER | 6.1981 | Rough | 1.2550 | 6.172E-002 | 2.618 | 0.185 | 0.9000 | 0.7000 | 0.7000 |
3 | FLOOR_CONSOL_LAYER | 1.9554E-005 | Rough | 0.0008 | 12.990 | 3.438 | 0.219 | 0.9000 | 0.7000 | 0.7000 |
4 | BSMTWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
5 | CRAWLWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
6 | WALL_CONSOL_LAYER | 1.5339 | Rough | 0.2917 | 5.796E-002 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
7 | VERY HIGH REFLECTIVITY SURFACE | 2.1097E-006 | Smooth | 0.0016 | 237.000 | 168.680 | 0.216 | 0.9000 | 5.0000E-002 | 5.0000E-002 |
8 | GYPSUMBOARD-5/16IN | 5.0054E-002 | Rough | 0.0260 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
9 | COPPERPIPE | 4.7506E-005 | MediumRough | 0.0625 | 401.000 | 140.026 | 0.200 | 0.9000 | 0.6500 | 0.6500 |
10 | F08 METAL SURFACE | 1.7668E-005 | Smooth | 0.0026 | 45.280 | 488.437 | 0.119 | 0.9000 | 0.7000 | 0.7000 |
11 | CONCRETE_4IN | 7.7356E-002 | Rough | 0.3330 | 1.312 | 140.014 | 0.111 | 0.9000 | 0.7000 | 0.7000 |
12 | ASPHALT_SHINGLE | 7.7448E-002 | MediumRough | 0.0208 | 8.186E-002 | 70.000 | 0.300 | 0.9000 | 0.7500 | 0.7000 |
13 | WOOD_SHINGLE | 0.1115 | MediumSmooth | 0.0417 | 0.114 | 26.600 | 0.390 | 0.9000 | 0.7000 | 0.7000 |
14 | SLATE_SHINGLE | 8.8061E-003 | MediumSmooth | 0.0417 | 1.442 | 100.000 | 0.300 | 0.9000 | 0.7000 | 0.7000 |
15 | CEMENT_STUCCO | 2.6422E-002 | MediumSmooth | 0.0625 | 0.721 | 116.464 | 0.210 | 0.9000 | 0.7000 | 0.7000 |
16 | SYN_STUCCO | 3.5237E-002 | MediumSmooth | 0.0100 | 8.650E-002 | 24.971 | 0.210 | 0.9000 | 0.7000 | 0.7000 |
17 | DRYWALL_1/2IN | 7.9331E-002 | MediumSmooth | 0.0417 | 0.160 | 50.000 | 0.260 | 0.9000 | 0.7000 | 0.7000 |
18 | OSB_5/8IN | 0.1365 | MediumSmooth | 0.0521 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
19 | OSB_7/16IN | 9.5550E-002 | MediumSmooth | 0.0365 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
20 | BLOWN_R30 | 5.1614 | MediumRough | 0.6975 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
21 | BLOWN_R30_TOP | 2.8489 | MediumRough | 0.3849 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
22 | PLYWOOD_3/4IN | 0.1650 | Rough | 0.0625 | 0.115 | 34.003 | 0.161 | 0.9000 | 0.7000 | 0.7000 |
23 | BATT_R19 | 7.3089 | MediumRough | 0.0833 | 3.475E-003 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
24 | LUMBER_2X4 | 0.7709 | Rough | 0.2920 | 0.115 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
25 | CARPET_N_PAD | 0.4224 | MediumSmooth | 0.0833 | 6.013E-002 | 2.000 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
26 | BATT_R13 | 2.2936 | MediumRough | 0.2917 | 3.876E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
27 | OSB_1/2IN | 0.1092 | MediumSmooth | 0.0417 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
28 | SOIL_12IN | 0.1761 | Rough | 1.0000 | 1.731 | 115.011 | 0.056 | 0.9000 | 0.7000 | 0.7000 |
29 | DOOR_CONST | 0.4402 | Smooth | 0.1040 | 7.201E-002 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
30 | GYP_BOARD_1/2IN | 8.0130E-002 | Rough | 0.0417 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
31 | STD WOOD 6INCH | 1.2500 | MediumSmooth | 0.4921 | 0.120 | 33.711 | 0.289 | 0.9000 | 0.7000 | 0.7000 |
32 | PIPE INSULATION | 0.3830 | VeryRough | 0.0417 | 3.317E-002 | 5.681 | 0.200 | 0.9000 | 0.5000 | 0.5000 |
33 | MANF_WALL_AIRGAP | 0.1200 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
34 | BLDG_PAPER_FELT | 1.0567E-002 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
35 | R_HIGH | 177.0000 | MediumRough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
36 | CLEAR ACRYLIC PLASTIC | 3.3333E-003 | VerySmooth | 0.0098 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
37 | DIFFUSING ACRYLIC PLASTIC | 2.4444E-003 | VerySmooth | 0.0072 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
38 | INT_BLIND | 0.0000 | Rough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.0000 | 0.0000 | 0.0000 |
39 | GLASS | 0.2680 | VerySmooth | 0.1066 | 0.121 | 0.000 | 0.000 | 0.8400 | 0.0000 | 0.0000 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | LowerLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Name | Combined convective/radiative film coefficient {Btu/h-ft2-F} | User selected Constant Temperature {F} | Coefficient modifying the constant temperature term | Coefficient modifying the external dry bulb temperature term | Coefficient modifying the ground temperature term | Coefficient modifying the wind speed term {s/m} | Coefficient modifying the zone air temperature term | Constant Temperature Schedule Name | Sinusoidal Variation | Period of Sinusoidal Variation | Previous Other Side Temperature Coefficient | Minimum Other Side Temperature {F} | Maximum Other Side Temperature {F} | |
1 | SURFPROPOTHSDCOEFBASEMENTAVGWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTWALLSURFACETEMP | NO | 24.000 | 0.000 | N/A | N/A |
2 | SURFPROPOTHSDCOEFBASEMENTAVGFLOOR | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTFLOORTEMP | NO | 24.000 | 0.000 | N/A | N/A |
3 | SURFPROPOTHSDCOEFBASEMENTUPPERWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTUPPERWALLTEMP | NO | 24.000 | 0.000 | N/A | N/A |
4 | SURFPROPOTHSDCOEFBASEMENTLOWERWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTLOWERWALLTEMP | NO | 24.000 | 0.000 | N/A | N/A |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{F} |
Surface Convection Coefficient Lower Limit {Btu/h-ft2-F} |
Surface Convection Coefficient Upper Limit {Btu/h-ft2-F} |
|
1 | CTF - ConductionTransferFunction | 392. | 0.02 | 176.1 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 60 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 21 | 186 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {ft} | Origin Y-Coordinate {ft} | Origin Z-Coordinate {ft} | Centroid X-Coordinate {ft} | Centroid Y-Coordinate {ft} | Centroid Z-Coordinate {ft} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {ft} | Maximum X {ft} | Minimum Y {ft} | Maximum Y {ft} | Minimum Z {ft} | Maximum Z {ft} | Ceiling Height {ft} | Volume {ft3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {ft2} | Exterior Gross Wall Area {ft2} | Exterior Net Wall Area {ft2} | Exterior Window Area {ft2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | HEATEDBSMT | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.51 | -3.4 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | -7.0 | 0.49 | 7.51 | 58539.45 | TARP | DOE-2 | 7794.37 | 185.05 | 185.05 | 0.00 | 15 | 0 | 0 | Yes |
2 | BREEZEWAY | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.55 | 13.26 | 1 | 1 | 1 | 0.00 | 119.89 | 30.05 | 35.04 | 0.49 | 25.99 | 17.00 | 30553.07 | TARP | DOE-2 | 1798.18 | 0.00 | 0.00 | 0.00 | 4 | 0 | 0 | Yes |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
15 | ATTIC | 0.0 | -134.9 | 51.61 | 0.00 | 59.94 | 32.55 | 29.56 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | 25.99 | 39.54 | 6.76 | 52795.39 | TARP | DOE-2 | 7802.66 | 881.33 | 881.33 | 0.00 | 11 | 0 | 0 | Yes |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
Zone Name | Floor Area {ft2} | # Occupants | Area per Occupant {ft2/person} | Occupant per Area {person/ft2} | Interior Lighting {Btu/h-ft2} | Electric Load {Btu/h-ft2} | Gas Load {Btu/h-ft2} | Other Load {Btu/h-ft2} | Hot Water Eq {Btu/h-ft2} | Steam Equipment {Btu/h-ft2} | Sum Loads per Area {Btu/h-ft2} | Outdoor Controlled Baseboard Heat | |
1 | HEATEDBSMT | 7794.37 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
2 | BREEZEWAY | 1798.18 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.110 | 2.353 | 0.000 | 0.000 | 0.000 | 5.086 | No |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.110 | 2.353 | 0.000 | 0.000 | 0.000 | 5.086 | No |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.110 | 2.353 | 0.000 | 0.000 | 0.000 | 5.086 | No |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.110 | 2.353 | 0.000 | 0.000 | 0.000 | 5.086 | No |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.110 | 2.353 | 0.000 | 0.000 | 0.000 | 5.086 | No |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.110 | 2.353 | 0.000 | 0.000 | 0.000 | 5.086 | No |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.110 | 2.353 | 0.000 | 0.000 | 0.000 | 5.086 | No |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.110 | 2.353 | 0.000 | 0.000 | 0.000 | 5.086 | No |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.110 | 2.353 | 0.000 | 0.000 | 0.000 | 5.086 | No |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.110 | 2.353 | 0.000 | 0.000 | 0.000 | 5.086 | No |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.110 | 2.353 | 0.000 | 0.000 | 0.000 | 5.086 | No |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.110 | 2.353 | 0.000 | 0.000 | 0.000 | 5.086 | No |
15 | ATTIC | 7802.66 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.110 | 2.353 | 0.000 | 0.000 | 0.000 | 5.086 | No |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.110 | 2.353 | 0.000 | 0.000 | 0.000 | 5.086 | No |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.110 | 2.353 | 0.000 | 0.000 | 0.000 | 5.086 | No |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.110 | 2.353 | 0.000 | 0.000 | 0.000 | 5.086 | No |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.110 | 2.353 | 0.000 | 0.000 | 0.000 | 5.086 | No |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.110 | 2.353 | 0.000 | 0.000 | 0.000 | 5.086 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Number of People {} | People/Floor Area {person/ft2} | Floor Area per person {ft2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
2 | PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
3 | PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
4 | PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
5 | PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
6 | PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
7 | PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
8 | PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
9 | PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
10 | PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
11 | PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
12 | PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
13 | PEOPLE_UNIT1_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
14 | PEOPLE_UNIT2_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
15 | PEOPLE_UNIT3_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
16 | PEOPLE_UNIT1_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
17 | PEOPLE_UNIT2_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
18 | PEOPLE_UNIT3_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Lighting Level {Btu/h} | Lights/Floor Area {Btu/h-ft2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {Btu/h} | Nominal Maximum Lighting Level {Btu/h} | |
1 | LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
2 | LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
3 | LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
4 | LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
5 | LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
6 | LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
7 | LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
8 | LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
9 | LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
10 | LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
11 | LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
12 | LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
13 | LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
14 | LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
15 | LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
16 | LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
17 | LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
18 | LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
19 | LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
20 | LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
21 | LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
22 | LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
23 | LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
24 | LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
25 | LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
26 | LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
27 | LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
28 | LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
29 | LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
30 | LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
31 | LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
32 | LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
33 | LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
34 | LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
35 | LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
36 | LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Equipment Level {Btu/h} | Equipment/Floor Area {Btu/h-ft2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {Btu/h} | Nominal Maximum Equipment Level {Btu/h} | |
1 | DISHWASHER1_FRONTROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
2 | REFRIGERATOR1_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
3 | CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
4 | GAS_DRYER1_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
5 | GAS_RANGE1_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
6 | TELEVISION1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
7 | GAS_MELS1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
8 | IECC_ADJ1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
9 | DISHWASHER2_FRONTROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
10 | REFRIGERATOR2_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
11 | CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
12 | GAS_DRYER2_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
13 | GAS_RANGE2_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
14 | TELEVISION2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
15 | GAS_MELS2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
16 | IECC_ADJ2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
17 | DISHWASHER3_FRONTROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
18 | REFRIGERATOR3_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
19 | CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
20 | GAS_DRYER3_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
21 | GAS_RANGE3_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
22 | TELEVISION3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
23 | GAS_MELS3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
24 | IECC_ADJ3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
25 | DISHWASHER1_BACKROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
26 | REFRIGERATOR1_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
27 | CLOTHESWASHER1_BACKROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
28 | GAS_DRYER1_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
29 | GAS_RANGE1_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
30 | TELEVISION1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
31 | GAS_MELS1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
32 | IECC_ADJ1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
33 | DISHWASHER2_BACKROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
34 | REFRIGERATOR2_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
35 | CLOTHESWASHER2_BACKROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
36 | GAS_DRYER2_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
37 | GAS_RANGE2_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
38 | TELEVISION2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
39 | GAS_MELS2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
40 | IECC_ADJ2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
41 | DISHWASHER3_BACKROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
42 | REFRIGERATOR3_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
43 | CLOTHESWASHER3_BACKROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
44 | GAS_DRYER3_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
45 | GAS_RANGE3_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
46 | TELEVISION3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
47 | GAS_MELS3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
48 | IECC_ADJ3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
49 | DISHWASHER1_FRONTROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
50 | REFRIGERATOR1_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
51 | CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
52 | GAS_DRYER1_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
53 | GAS_RANGE1_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
54 | TELEVISION1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
55 | GAS_MELS1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
56 | IECC_ADJ1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
57 | DISHWASHER2_FRONTROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
58 | REFRIGERATOR2_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
59 | CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
60 | GAS_DRYER2_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
61 | GAS_RANGE2_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
62 | TELEVISION2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
63 | GAS_MELS2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
64 | IECC_ADJ2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
65 | DISHWASHER3_FRONTROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
66 | REFRIGERATOR3_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
67 | CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
68 | GAS_DRYER3_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
69 | GAS_RANGE3_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
70 | TELEVISION3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
71 | GAS_MELS3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
72 | IECC_ADJ3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
73 | DISHWASHER1_BACKROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
74 | REFRIGERATOR1_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
75 | CLOTHESWASHER1_BACKROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
76 | GAS_DRYER1_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
77 | GAS_RANGE1_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
78 | TELEVISION1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
79 | GAS_MELS1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
80 | IECC_ADJ1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
81 | DISHWASHER2_BACKROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
82 | REFRIGERATOR2_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
83 | CLOTHESWASHER2_BACKROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
84 | GAS_DRYER2_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
85 | GAS_RANGE2_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
86 | TELEVISION2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
87 | GAS_MELS2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
88 | IECC_ADJ2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
89 | DISHWASHER3_BACKROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
90 | REFRIGERATOR3_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
91 | CLOTHESWASHER3_BACKROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
92 | GAS_DRYER3_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
93 | GAS_RANGE3_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
94 | TELEVISION3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
95 | GAS_MELS3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
96 | IECC_ADJ3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
97 | DISHWASHER1_FRONTROW_TOPFLOOR | DISHWASHER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
98 | REFRIGERATOR1_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
99 | CLOTHESWASHER1_FRONTROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
100 | GAS_DRYER1_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
101 | GAS_RANGE1_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
102 | TELEVISION1_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
103 | GAS_MELS1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
104 | IECC_ADJ1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
105 | DISHWASHER2_FRONTROW_TOPFLOOR | DISHWASHER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
106 | REFRIGERATOR2_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
107 | CLOTHESWASHER2_FRONTROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
108 | GAS_DRYER2_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
109 | GAS_RANGE2_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
110 | TELEVISION2_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
111 | GAS_MELS2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
112 | IECC_ADJ2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
113 | DISHWASHER3_FRONTROW_TOPFLOOR | DISHWASHER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
114 | REFRIGERATOR3_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
115 | CLOTHESWASHER3_FRONTROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
116 | GAS_DRYER3_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
117 | GAS_RANGE3_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
118 | TELEVISION3_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
119 | GAS_MELS3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
120 | IECC_ADJ3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
121 | DISHWASHER1_BACKROW_TOPFLOOR | DISHWASHER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
122 | REFRIGERATOR1_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
123 | CLOTHESWASHER1_BACKROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
124 | GAS_DRYER1_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
125 | GAS_RANGE1_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
126 | TELEVISION1_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
127 | GAS_MELS1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
128 | IECC_ADJ1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
129 | DISHWASHER2_BACKROW_TOPFLOOR | DISHWASHER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
130 | REFRIGERATOR2_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
131 | CLOTHESWASHER2_BACKROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
132 | GAS_DRYER2_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
133 | GAS_RANGE2_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
134 | TELEVISION2_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
135 | GAS_MELS2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
136 | IECC_ADJ2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
137 | DISHWASHER3_BACKROW_TOPFLOOR | DISHWASHER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
138 | REFRIGERATOR3_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
139 | CLOTHESWASHER3_BACKROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
140 | GAS_DRYER3_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
141 | GAS_RANGE3_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
142 | TELEVISION3_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
143 | GAS_MELS3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
144 | IECC_ADJ3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Equipment Level {Btu/h} | Equipment/Floor Area {Btu/h-ft2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {Btu/h} | Nominal Maximum Equipment Level {Btu/h} | |
1 | GAS_DRYER1_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
2 | GAS_RANGE1_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
3 | GAS_MELS1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
4 | GAS_DRYER2_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
5 | GAS_RANGE2_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
6 | GAS_MELS2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
7 | GAS_DRYER3_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
8 | GAS_RANGE3_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
9 | GAS_MELS3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
10 | GAS_DRYER1_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
11 | GAS_RANGE1_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
12 | GAS_MELS1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
13 | GAS_DRYER2_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
14 | GAS_RANGE2_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
15 | GAS_MELS2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
16 | GAS_DRYER3_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
17 | GAS_RANGE3_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
18 | GAS_MELS3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
19 | GAS_DRYER1_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
20 | GAS_RANGE1_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
21 | GAS_MELS1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
22 | GAS_DRYER2_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
23 | GAS_RANGE2_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
24 | GAS_MELS2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
25 | GAS_DRYER3_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
26 | GAS_RANGE3_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
27 | GAS_MELS3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
28 | GAS_DRYER1_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
29 | GAS_RANGE1_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
30 | GAS_MELS1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
31 | GAS_DRYER2_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
32 | GAS_RANGE2_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
33 | GAS_MELS2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
34 | GAS_DRYER3_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
35 | GAS_RANGE3_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
36 | GAS_MELS3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
37 | GAS_DRYER1_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
38 | GAS_RANGE1_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
39 | GAS_MELS1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
40 | GAS_DRYER2_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
41 | GAS_RANGE2_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
42 | GAS_MELS2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
43 | GAS_DRYER3_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
44 | GAS_RANGE3_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
45 | GAS_MELS3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
46 | GAS_DRYER1_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
47 | GAS_RANGE1_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
48 | GAS_MELS1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
49 | GAS_DRYER2_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
50 | GAS_RANGE2_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
51 | GAS_MELS2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
52 | GAS_DRYER3_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
53 | GAS_RANGE3_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
54 | GAS_MELS3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
Construction Name | Index | #Layers | #CTFs | Time Step {Hours} | ThermalConductance {Btu/h-ft2-F} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | EXTERIOR WALL | 1 | 5 | 10 | 0.167 | 0.0937 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
2 | CEILING-FLOOR-LAYER | 3 | 1 | 5 | 0.167 | 0.228 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
3 | EXTERIOR FLOOR | 4 | 3 | 4 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
4 | INTERIOR CEILING | 6 | 2 | 10 | 0.167 | 0.0281 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
5 | ATTIC FLOOR | 7 | 2 | 10 | 0.167 | 0.0281 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | INTERIORWALL | 9 | 3 | 5 | 0.167 | 0.597 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | EXTERIOR ROOF | 11 | 2 | 4 | 0.167 | 0.943 | 0.900 | 0.900 | 0.750 | 0.700 | MediumRough |
8 | EXTERIOR DOOR | 14 | 1 | 5 | 0.167 | 0.400 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | GABLE_END | 16 | 5 | 6 | 0.167 | 0.428 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
10 | BASEMENT WALL | 24 | 3 | 4 | 0.167 | 0.534 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
11 | iz-EXTERIOR FLOOR | 25 | 3 | 4 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | ThermalResistance {m2-K/w} | |
1 | SYN_STUCCO | 0.0098 | 0.086 | 24.971 | 0.210 | 0.3524E-01 |
2 | SHEATHING_CONSOL_LAYER | 0.0417 | 0.094 | 42.764 | 0.280 | 0.1351 |
3 | OSB_7/16IN | 0.0364 | 0.116 | 34.000 | 0.290 | 0.9555E-01 |
4 | WALL_CONSOL_LAYER | 0.2917 | 0.058 | 7.541 | 0.248 | 1.534 |
5 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
6 | LUMBER_2X4 | 0.2920 | 0.115 | 32.003 | 0.183 | 0.7709 |
7 | FLOOR_CONSOL_LAYER | 0.0010 | 12.990 | 3.438 | 0.219 | 0.1955E-04 |
8 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
9 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
10 | CEIL_CONSOL_LAYER | 1.2550 | 0.062 | 2.618 | 0.185 | 6.198 |
11 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
12 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
13 | CEIL_CONSOL_LAYER | 1.2550 | 0.062 | 2.618 | 0.185 | 6.198 |
14 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
15 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
16 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
17 | ASPHALT_SHINGLE | 0.0207 | 0.082 | 70.000 | 0.300 | 0.7745E-01 |
18 | OSB_1/2IN | 0.0417 | 0.116 | 34.000 | 0.290 | 0.1092 |
19 | DOOR_CONST | 0.1040 | 0.072 | 32.003 | 0.183 | 0.4402 |
20 | CEMENT_STUCCO | 0.0627 | 0.721 | 116.464 | 0.210 | 0.2642E-01 |
21 | BLDG_PAPER_FELT | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1057E-01 |
22 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
23 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
24 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
25 | BSMTWALL_CONSOL_LAYER | 0.0010 | 10.844 | 7.541 | 0.248 | 0.2342E-04 |
26 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
27 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
28 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
29 | FLOOR_CONSOL_LAYER | 0.0010 | 12.990 | 3.438 | 0.219 | 0.1955E-04 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 10 | 0.53690791E-10 | -0.14086767E-13 | 0.12185568E-09 | -0.56142619E-15 |
2 | 9 | -0.78969438E-07 | 0.37271083E-11 | -0.12786746E-06 | 0.41607738E-10 |
3 | 8 | 0.15644920E-04 | 0.57233592E-08 | 0.24713380E-04 | -0.42390053E-07 |
4 | 7 | -0.11010334E-02 | 0.13458163E-05 | -0.17770580E-02 | 0.73075693E-05 |
5 | 6 | 0.34256138E-01 | 0.71913801E-04 | 0.57800664E-01 | -0.42770275E-03 |
6 | 5 | -0.50970556 | 0.10561809E-02 | -0.91414050 | 0.10365322E-01 |
7 | 4 | 3.8008141 | 0.46021679E-02 | 7.1669335 | -0.11749215 |
8 | 3 | -14.731927 | 0.58137860E-02 | -27.604869 | 0.65172867 |
9 | 2 | 29.625503 | 0.18019171E-02 | 52.431474 | -1.7640469 |
10 | 1 | -28.806601 | 0.81323549E-04 | -47.206921 | 2.1946319 |
11 | 0 | 10.602175 | 0.49952751E-07 | 16.084904 | |
12 | 5 | -0.10726087E-01 | 0.44268190E-05 | -0.10726087E-01 | 0.97389233E-03 |
13 | 4 | 0.31857203 | 0.80150166E-03 | 0.31857203 | -0.30727185E-01 |
14 | 3 | -2.8372473 | 0.12516450E-01 | -2.8372473 | 0.30041224 |
15 | 2 | 9.6667056 | 0.33176537E-01 | 9.6667056 | -1.1584571 |
16 | 1 | -13.322214 | 0.15207483E-01 | -13.322214 | 1.8397512 |
17 | 0 | 6.2472388 | 0.62260140E-03 | 6.2472388 | |
18 | 4 | 0.29631924E-13 | -0.40788276E-14 | 0.60443234E-14 | -0.77798347E-16 |
19 | 3 | -0.11254351E-04 | 0.79669069E-06 | -0.23145793E-05 | 0.39394231E-13 |
20 | 2 | 0.49771861 | 0.29587917E-01 | 0.78801895E-01 | -0.76025120E-05 |
21 | 1 | -8.3915550 | 0.80192706 | -1.1535996 | 0.21114735 |
22 | 0 | 9.2367617 | 0.51139848 | 2.4177143 | |
23 | 10 | 0.25332408E-17 | -0.22101509E-14 | 0.15157692E-08 | 0.28211904E-17 |
24 | 9 | -0.31506112E-08 | -0.26974675E-14 | -0.81843868E-03 | 0.20118786E-08 |
25 | 8 | 0.42861811E-03 | 0.11354105E-09 | 0.39097097E-01 | -0.27370296E-03 |
26 | 7 | -0.11368907E-01 | 0.51842634E-07 | -0.64553953 | 0.74324363E-02 |
27 | 6 | 0.12484615 | 0.25047115E-05 | 5.3130581 | -0.83937451E-01 |
28 | 5 | -0.73775399 | 0.27964547E-04 | -24.889648 | 0.51283867 |
29 | 4 | 2.5553417 | 0.92755650E-04 | 70.144414 | -1.8477174 |
30 | 3 | -5.2989438 | 0.96002462E-04 | -120.51707 | 4.0111012 |
31 | 2 | 6.4233118 | 0.27752742E-04 | 123.06129 | -5.1209931 |
32 | 1 | -4.1707712 | 0.15163054E-05 | -68.409714 | 3.5199891 |
33 | 0 | 1.1151582 | 0.34288690E-08 | 15.905180 | |
34 | 10 | 0.15157692E-08 | -0.22101509E-14 | 0.25332408E-17 | 0.28211904E-17 |
35 | 9 | -0.81843868E-03 | -0.26974675E-14 | -0.31506112E-08 | 0.20118786E-08 |
36 | 8 | 0.39097097E-01 | 0.11354105E-09 | 0.42861811E-03 | -0.27370296E-03 |
37 | 7 | -0.64553953 | 0.51842634E-07 | -0.11368907E-01 | 0.74324363E-02 |
38 | 6 | 5.3130581 | 0.25047115E-05 | 0.12484615 | -0.83937451E-01 |
39 | 5 | -24.889648 | 0.27964547E-04 | -0.73775399 | 0.51283867 |
40 | 4 | 70.144414 | 0.92755650E-04 | 2.5553417 | -1.8477174 |
41 | 3 | -120.51707 | 0.96002462E-04 | -5.2989438 | 4.0111012 |
42 | 2 | 123.06129 | 0.27752742E-04 | 6.4233118 | -5.1209931 |
43 | 1 | -68.409714 | 0.15163054E-05 | -4.1707712 | 3.5199891 |
44 | 0 | 15.905180 | 0.34288690E-08 | 1.1151582 | |
45 | 5 | -0.27590492E-07 | 0.65241430E-08 | -0.27590492E-07 | 0.17331255E-13 |
46 | 4 | 0.68608714E-03 | 0.11323974E-03 | 0.68608714E-03 | -0.15705033E-07 |
47 | 3 | -0.21538511 | 0.37821720E-01 | -0.21538511 | 0.25667047E-03 |
48 | 2 | 5.0173519 | 0.62258424 | 5.0173519 | -0.50236511E-01 |
49 | 1 | -19.904252 | 0.86481321 | -19.904252 | 0.58144210 |
50 | 0 | 16.688993 | 0.62060609E-01 | 16.688993 | |
51 | 4 | 0.75441920E-10 | 0.23883683E-10 | 0.47514224E-10 | -0.69373194E-20 |
52 | 3 | -0.33730907E-03 | 0.89366797E-04 | -0.22574866E-03 | 0.77828620E-10 |
53 | 2 | 0.58624422 | 0.18542418 | 0.49024360 | -0.17301269E-03 |
54 | 1 | -11.299243 | 2.8799011 | -8.6239668 | 0.15905732 |
55 | 0 | 15.219762 | 1.4410112 | 12.640375 | |
56 | 5 | -0.14496306E-10 | 0.10482472E-10 | -0.14496306E-10 | 0.15719123E-14 |
57 | 4 | 0.30894845E-05 | 0.19631753E-05 | 0.30894845E-05 | -0.20134377E-08 |
58 | 3 | -0.87121421E-02 | 0.40108201E-02 | -0.87121421E-02 | 0.45430501E-04 |
59 | 2 | 0.83777567 | 0.24056749 | 0.83777567 | -0.18447090E-01 |
60 | 1 | -6.4029859 | 0.89203954 | -6.4029859 | 0.42787762 |
61 | 0 | 6.9152593 | 0.20472012 | 6.9152593 | |
62 | 6 | 0.97988530E-11 | 0.43917118E-12 | 0.24496810E-11 | -0.34892153E-15 |
63 | 5 | -0.75005310E-05 | 0.16499726E-06 | -0.28271466E-05 | 0.19166609E-11 |
64 | 4 | 0.32354224E-01 | 0.66949565E-03 | 0.10283773E-01 | -0.11111676E-05 |
65 | 3 | -1.8201547 | 0.67148336E-01 | -0.62076152 | 0.38788549E-02 |
66 | 2 | 21.173821 | 0.53241617 | 7.5279938 | -0.97325542E-01 |
67 | 1 | -64.420211 | 0.46601667 | -21.697519 | 0.64629334 |
68 | 0 | 46.121323 | 0.20873329E-01 | 15.867130 | |
69 | 4 | 0.69987904E-07 | 0.26228811E-07 | 0.69987904E-07 | -0.89457852E-14 |
70 | 3 | -0.30987589E-02 | 0.10225415E-02 | -0.30987589E-02 | 0.11234143E-06 |
71 | 2 | 0.81559891 | 0.24124884 | 0.81559891 | -0.23762713E-02 |
72 | 1 | -7.9329461 | 1.4912083 | -7.9329461 | 0.29351368 |
73 | 0 | 9.2684202 | 0.41449462 | 9.2684202 | |
74 | 4 | 0.60443234E-14 | -0.40788276E-14 | 0.29631924E-13 | -0.77798347E-16 |
75 | 3 | -0.23145793E-05 | 0.79669069E-06 | -0.11254351E-04 | 0.39394231E-13 |
76 | 2 | 0.78801895E-01 | 0.29587917E-01 | 0.49771861 | -0.76025120E-05 |
77 | 1 | -1.1535996 | 0.80192706 | -8.3915550 | 0.21114735 |
78 | 0 | 2.4177143 | 0.51139848 | 9.2367617 |
Construction Name | Index | #Layers | Roughness | Conductance {Btu/h-ft2-F} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | EXTERIOR WINDOW | 12 | 1 | VerySmooth | 0.400 | 0.217 | 0.129 | 0.883 |
2 | INTERIOR WINDOW | 13 | 1 | VerySmooth | 0.400 | 0.217 | 0.129 | 0.883 |
3 | WINDOW_W_BLINDS | 18 | 2 | VerySmooth | 0.400 | 0.207 | 2.538E-002 | 0.133 |
4 | TDD DOME | 22 | 1 | VerySmooth | 1.071 | 0.929 | 0.920 | 0.920 |
5 | TDD DIFFUSER | 23 | 1 | VerySmooth | 1.077 | 0.906 | 0.900 | 0.900 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {ft} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLASS | SpectralAverage | 0.10662 | 0.12813 | 0.65606 | 0.65606 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.12126 | 1.00000 | No | |
2 | GLASS | SpectralAverage | 0.10662 | 0.12813 | 0.65606 | 0.65606 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.12126 | 1.00000 | No | |
3 | GLASS | SpectralAverage | 0.10662 | 0.12813 | 0.65606 | 0.65606 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.12126 | 1.00000 | No | |
4 | CLEAR ACRYLIC PLASTIC | SpectralAverage | 0.00984 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No | |
5 | DIFFUSING ACRYLIC PLASTIC | SpectralAverage | 0.00722 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No |
Material Name | Slat Width {ft} | Slat Separation {ft} | Slat Thickness {ft} | Slat Angle {deg} | Slat Beam Solar Transmittance | Slat Beam Solar Front Reflectance | Blind To Glass Distance {ft} | |
1 | INT_BLIND | 0.0820 | 0.0615 | 0.0033 | 45.000 | 0.000 | 0.500 | 0.164 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000. | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {ft3} | Maximum Capacity {Btu/h} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 5.3474 | 36002.1 | 0.821 | 0.5540 |
2 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 5.3474 | 36002.1 | 0.821 | 0.5540 |
3 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 5.3474 | 36002.1 | 0.821 | 0.5540 |
4 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 5.3474 | 36002.1 | 0.821 | 0.5540 |
5 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 5.3474 | 36002.1 | 0.821 | 0.5540 |
6 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 5.3474 | 36002.1 | 0.821 | 0.5540 |
7 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 5.3474 | 36002.1 | 0.821 | 0.5540 |
8 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 5.3474 | 36002.1 | 0.821 | 0.5540 |
9 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 5.3474 | 36002.1 | 0.821 | 0.5540 |
10 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 5.3474 | 36002.1 | 0.821 | 0.5540 |
11 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 5.3474 | 36002.1 | 0.821 | 0.5540 |
12 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 5.3474 | 36002.1 | 0.821 | 0.5540 |
13 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 5.3474 | 36002.1 | 0.821 | 0.5540 |
14 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 5.3474 | 36002.1 | 0.821 | 0.5540 |
15 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 5.3474 | 36002.1 | 0.821 | 0.5540 |
16 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 5.3474 | 36002.1 | 0.821 | 0.5540 |
17 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 5.3474 | 36002.1 | 0.821 | 0.5540 |
18 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 5.3474 | 36002.1 | 0.821 | 0.5540 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
2 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
3 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
4 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
5 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
6 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
7 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
8 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
9 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
10 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
11 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
12 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
13 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
14 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
15 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
16 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
17 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
18 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
19 | ATTICVENT | ALWAYS_AVAIL | ATTIC | 7802.66 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/person Area {ft3/min-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {psi} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{F}/Schedule | Maximum Indoor Temperature{F}/Schedule | Delta Temperature{F}/Schedule | Minimum Outdoor Temperature{F}/Schedule | Maximum Outdoor Temperature{F}/Schedule | Maximum WindSpeed{ft/min} | |
1 | VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
2 | VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
3 | VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
4 | VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
5 | VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
6 | VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
7 | VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
8 | VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
9 | VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
10 | VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
11 | VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
12 | VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
13 | VENTILATION_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
14 | VENTILATION_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
15 | VENTILATION_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
16 | VENTILATION_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
17 | VENTILATION_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
18 | VENTILATION_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
19 | VENTILATION_UNITHEATEDBSMT | ALWAYS_OFF | HEATEDBSMT | 7794.37 | 0.0 | 0.000 | 0.000 | N/A | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | HEATEDBSMT | Mixing/Well-Stirred |
2 | BREEZEWAY | Mixing/Well-Stirred |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
15 | ATTIC | Mixing/Well-Stirred |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {Btu/h} | User Des Load {Btu/h} | Calc Des Air Flow Rate {ft3/min} | User Des Air Flow Rate {ft3/min} | Design Day Name | Date/Time of Peak | Temperature at Peak {F} | Humidity Ratio at Peak {lbWater/lbDryAir} | Floor Area {ft2} | # Occupants | Calc Outdoor Air Flow Rate {ft3/min} | Calc DOAS Heat Addition Rate {Btu/h} | |
1 | HEATEDBSMT | Cooling | 6454.61988 | 6454.61988 | 302.41522 | 302.41522 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 100.49239 | 0.00563 | 7794.38637 | 0.00000 | 44.99491 | 0.00000 |
2 | HEATEDBSMT | Heating | 10232.43306 | 10232.43306 | 205.18980 | 205.18980 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 32.90000 | 0.00432 | 7794.38637 | 0.00000 | 44.99491 | 0.00000 |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | 10523.47246 | 10523.47246 | 492.96604 | 492.96604 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 100.49239 | 0.00563 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
4 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | 3651.48108 | 3651.48108 | 73.22054 | 73.22054 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
5 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | 6576.59479 | 6576.59479 | 308.07199 | 308.07199 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 97.89890 | 0.00562 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
6 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | 2131.43252 | 2131.43252 | 42.74046 | 44.99491 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
7 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | 7941.37326 | 7941.37326 | 371.99148 | 371.99148 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 105.44000 | 0.00563 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
8 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | 3651.38943 | 3651.38943 | 73.21863 | 73.21863 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
9 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | 10443.85276 | 10443.85276 | 489.23723 | 489.23723 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 99.69440 | 0.00563 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
10 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Heating | 3652.48588 | 3652.48588 | 73.24067 | 73.24067 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
11 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | 6624.13616 | 6624.13616 | 310.29657 | 310.29657 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 96.70190 | 0.00562 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
12 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Heating | 2129.77118 | 2129.77118 | 42.70720 | 44.99491 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
13 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | 7839.07392 | 7839.07392 | 367.20334 | 367.20334 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 99.09590 | 0.00563 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
14 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Heating | 3647.12505 | 3647.12505 | 73.13304 | 73.13304 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
15 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | 10837.96783 | 10837.96783 | 507.71180 | 507.71180 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 99.69440 | 0.00563 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
16 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | 3057.09365 | 3057.09365 | 61.30381 | 61.30381 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
17 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | 6742.19365 | 6742.19365 | 315.84742 | 315.84742 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 96.10340 | 0.00562 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
18 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | 1413.95668 | 1413.95668 | 28.35466 | 44.99491 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
19 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | 8175.59692 | 8175.59692 | 382.98724 | 382.98724 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 99.09590 | 0.00563 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
20 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | 3058.67669 | 3058.67669 | 61.33559 | 61.33559 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
21 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | 10767.58503 | 10767.58503 | 504.40672 | 504.40672 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 99.09590 | 0.00563 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
22 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Heating | 3059.09309 | 3059.09309 | 61.34385 | 61.34385 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
23 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | 6787.27306 | 6787.27306 | 317.94488 | 317.94488 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 96.10340 | 0.00562 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
24 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Heating | 1413.24300 | 1413.24300 | 28.34025 | 44.99491 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
25 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | 8138.53824 | 8138.53824 | 381.24995 | 381.24995 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 97.89890 | 0.00562 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
26 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Heating | 3055.30560 | 3055.30560 | 61.26800 | 61.26800 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
27 | LIVING_UNIT3_BACKROW_TOPFLOOR | Cooling | 9923.41245 | 9923.41245 | 464.85164 | 464.85164 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 98.49740 | 0.00563 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
28 | LIVING_UNIT3_BACKROW_TOPFLOOR | Heating | 4814.48701 | 4814.48701 | 96.54109 | 96.54109 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
29 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Cooling | 9837.36314 | 9837.36314 | 460.82621 | 460.82621 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 99.09590 | 0.00563 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
30 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Heating | 4816.64025 | 4816.64025 | 96.58431 | 96.58431 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
31 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Cooling | 12500.29549 | 12500.29549 | 585.57196 | 585.57196 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 99.69440 | 0.00563 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
32 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Heating | 4814.58459 | 4814.58459 | 96.54300 | 96.54300 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
33 | LIVING_UNIT2_BACKROW_TOPFLOOR | Cooling | 8513.94838 | 8513.94838 | 398.83470 | 398.83470 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 96.10340 | 0.00562 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
34 | LIVING_UNIT2_BACKROW_TOPFLOOR | Heating | 3154.85455 | 3154.85455 | 63.26249 | 63.26249 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
35 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Cooling | 8403.54159 | 8403.54159 | 393.66520 | 393.66520 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 96.10340 | 0.00562 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
36 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Heating | 3155.05654 | 3155.05654 | 63.26652 | 63.26652 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
37 | LIVING_UNIT1_BACKROW_TOPFLOOR | Cooling | 12571.61728 | 12571.61728 | 588.89823 | 588.89823 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 99.69440 | 0.00563 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
38 | LIVING_UNIT1_BACKROW_TOPFLOOR | Heating | 4816.37043 | 4816.37043 | 96.57880 | 96.57880 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 32.90000 | 0.00432 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [ft3/min] | User Des Air Flow Rate [ft3/min] | Design Day Name | Date/Time of Peak | |
1 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 3369.18 | 492.96604 | 492.96604 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 1561.35 | 73.22054 | 73.22054 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
3 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 2195.86 | 308.07199 | 308.07199 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 1154.82 | 44.99491 | 44.99491 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
5 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 2687.69 | 371.99148 | 371.99148 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 1561.33 | 73.21863 | 73.21863 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
7 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 3335.85 | 489.23723 | 489.23723 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Heating | Sensible | 1561.64 | 73.24067 | 73.24067 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
9 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 2194.07 | 310.29657 | 310.29657 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Heating | Sensible | 1154.82 | 44.99491 | 44.99491 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 2575.93 | 367.20334 | 367.20334 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Heating | Sensible | 1560.09 | 73.13304 | 73.13304 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
13 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 3449.66 | 507.71180 | 507.71180 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 1389.71 | 61.30381 | 61.30381 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
15 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2220.41 | 315.84742 | 315.84742 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 1154.82 | 44.99491 | 44.99491 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
17 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2673.11 | 382.98724 | 382.98724 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 1390.16 | 61.33559 | 61.33559 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
19 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 3421.57 | 504.40672 | 504.40672 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Heating | Sensible | 1390.29 | 61.34385 | 61.34385 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
21 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 2233.43 | 317.94488 | 317.94488 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
22 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Heating | Sensible | 1154.82 | 44.99491 | 44.99491 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
23 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 2646.89 | 381.24995 | 381.24995 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
24 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Heating | Sensible | 1389.19 | 61.26800 | 61.26800 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
25 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Cooling | Sensible | 3929.67 | 585.57196 | 585.57196 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
26 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Heating | Sensible | 1897.27 | 96.54300 | 96.54300 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
27 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Cooling | Sensible | 2700.14 | 393.66520 | 393.66520 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
28 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Heating | Sensible | 1417.98 | 63.26652 | 63.26652 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
29 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Cooling | Sensible | 3152.96 | 460.82621 | 460.82621 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
30 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Heating | Sensible | 1897.86 | 96.58431 | 96.58431 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
31 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Cooling | Sensible | 3950.26 | 588.89823 | 588.89823 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
32 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Heating | Sensible | 1897.79 | 96.57880 | 96.57880 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
33 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Cooling | Sensible | 2732.02 | 398.83470 | 398.83470 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
34 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Heating | Sensible | 1417.92 | 63.26249 | 63.26249 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
35 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Cooling | Sensible | 3170.05 | 464.85164 | 464.85164 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
36 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Heating | Sensible | 1897.24 | 96.54109 | 96.54109 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
37 | CENTRAL SYSTEM_UNITHEATEDBSMT | Cooling | Sensible | 2194.59 | 302.41522 | 302.41522 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
38 | CENTRAL SYSTEM_UNITHEATEDBSMT | Heating | Sensible | 3462.04 | 205.18980 | 205.18980 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNITHEATEDBSMT | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
2 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNITHEATEDBSMT | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
3 | Fan:OnOff | OASUPPLYFAN_UNITHEATEDBSMT | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
4 | Fan:OnOff | OAEXHAUSTFAN_UNITHEATEDBSMT | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
5 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNITHEATEDBSMT | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNITHEATEDBSMT | Design Size Maximum Air Flow Rate [ft3/min] | 302.41522 |
7 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
8 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
9 | Fan:OnOff | OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
10 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
11 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 492.96604 |
13 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
14 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
15 | Fan:OnOff | OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
16 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
17 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
18 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 308.07199 |
19 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
20 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
21 | Fan:OnOff | OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
22 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
23 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
24 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 371.99148 |
25 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
26 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
27 | Fan:OnOff | OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
28 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
29 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
30 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 489.23723 |
31 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
32 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
33 | Fan:OnOff | OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
34 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
35 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
36 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 310.29657 |
37 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
38 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
39 | Fan:OnOff | OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
40 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
41 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
42 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 367.20334 |
43 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
44 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
45 | Fan:OnOff | OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
46 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
47 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
48 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 507.71180 |
49 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
50 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
51 | Fan:OnOff | OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
52 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
53 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
54 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 315.84742 |
55 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
56 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
57 | Fan:OnOff | OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
58 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
59 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
60 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 382.98724 |
61 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
62 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
63 | Fan:OnOff | OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
64 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
65 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
66 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 504.40672 |
67 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
68 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
69 | Fan:OnOff | OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
70 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
71 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
72 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 317.94488 |
73 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
74 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
75 | Fan:OnOff | OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
76 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
77 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
78 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 381.24995 |
79 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
80 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
81 | Fan:OnOff | OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
82 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
83 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
84 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 464.85164 |
85 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
86 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
87 | Fan:OnOff | OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
88 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
89 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
90 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 460.82621 |
91 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
92 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
93 | Fan:OnOff | OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
94 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
95 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
96 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 585.57196 |
97 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
98 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
99 | Fan:OnOff | OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
100 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
101 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
102 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 398.83470 |
103 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
104 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
105 | Fan:OnOff | OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
106 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
107 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
108 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 393.66520 |
109 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
110 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
111 | Fan:OnOff | OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
112 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
113 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 588.89823 |
115 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 492.96604 |
116 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 492.96604 |
117 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 492.96604 |
118 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 492.96604 |
119 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 492.96604 |
120 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 492.96604 |
121 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
122 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
123 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 308.07199 |
124 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 308.07199 |
125 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 308.07199 |
126 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 308.07199 |
127 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 308.07199 |
128 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 308.07199 |
129 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
130 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
131 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 371.99148 |
132 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 371.99148 |
133 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 371.99148 |
134 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 371.99148 |
135 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 371.99148 |
136 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 371.99148 |
137 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
138 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
139 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 489.23723 |
140 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 489.23723 |
141 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 489.23723 |
142 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 489.23723 |
143 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 489.23723 |
144 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 489.23723 |
145 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
146 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
147 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 310.29657 |
148 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 310.29657 |
149 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 310.29657 |
150 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 310.29657 |
151 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 310.29657 |
152 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 310.29657 |
153 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
154 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
155 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 367.20334 |
156 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 367.20334 |
157 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 367.20334 |
158 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 367.20334 |
159 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 367.20334 |
160 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 367.20334 |
161 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
162 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
163 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 507.71180 |
164 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 507.71180 |
165 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 507.71180 |
166 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 507.71180 |
167 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 507.71180 |
168 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 507.71180 |
169 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
170 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
171 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 315.84742 |
172 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 315.84742 |
173 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 315.84742 |
174 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 315.84742 |
175 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 315.84742 |
176 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 315.84742 |
177 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
178 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
179 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 382.98724 |
180 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 382.98724 |
181 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 382.98724 |
182 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 382.98724 |
183 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 382.98724 |
184 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 382.98724 |
185 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
186 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
187 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 504.40672 |
188 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 504.40672 |
189 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 504.40672 |
190 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 504.40672 |
191 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 504.40672 |
192 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 504.40672 |
193 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
194 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
195 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 317.94488 |
196 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 317.94488 |
197 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 317.94488 |
198 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 317.94488 |
199 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 317.94488 |
200 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 317.94488 |
201 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
202 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
203 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 381.24995 |
204 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 381.24995 |
205 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 381.24995 |
206 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 381.24995 |
207 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 381.24995 |
208 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 381.24995 |
209 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
210 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
211 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 585.57196 |
212 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 585.57196 |
213 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 585.57196 |
214 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 585.57196 |
215 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 585.57196 |
216 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 585.57196 |
217 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
218 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
219 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 393.66520 |
220 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 393.66520 |
221 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 393.66520 |
222 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 393.66520 |
223 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 393.66520 |
224 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 393.66520 |
225 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
226 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
227 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 460.82621 |
228 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 460.82621 |
229 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 460.82621 |
230 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 460.82621 |
231 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 460.82621 |
232 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 460.82621 |
233 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
234 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
235 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 588.89823 |
236 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 588.89823 |
237 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 588.89823 |
238 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 588.89823 |
239 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 588.89823 |
240 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 588.89823 |
241 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
242 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
243 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 398.83470 |
244 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 398.83470 |
245 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 398.83470 |
246 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 398.83470 |
247 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 398.83470 |
248 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 398.83470 |
249 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
251 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 464.85164 |
252 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 464.85164 |
253 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 464.85164 |
254 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 464.85164 |
255 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 464.85164 |
256 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 464.85164 |
257 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
259 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 302.41522 |
260 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 302.41522 |
261 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 302.41522 |
262 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Adjusted Heating Design Air Flow Rate [ft3/min] | 302.41522 |
263 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Adjusted Cooling Design Air Flow Rate [ft3/min] | 302.41522 |
264 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Adjusted Main Design Air Flow Rate [ft3/min] | 302.41522 |
265 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 492.96604 |
268 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 308.07199 |
269 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 371.99148 |
270 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 489.23723 |
271 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 310.29657 |
272 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 367.20334 |
273 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 507.71180 |
274 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 315.84742 |
275 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 382.98724 |
276 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 504.40672 |
277 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 317.94488 |
278 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 381.24995 |
279 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 585.57196 |
280 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 393.66520 |
281 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 460.82621 |
282 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 588.89823 |
283 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 398.83470 |
284 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 464.85164 |
285 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Design Supply Air Flow Rate [ft3/min] | 302.41522 |
286 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 492.96604 |
287 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.12651 |
288 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80042 |
289 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 492.96604 |
290 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 492.96604 |
291 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 492.96604 |
292 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 5327.33200 |
293 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 1.12651 |
294 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
295 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 492.96604 |
296 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 5327.33200 |
297 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 308.07199 |
298 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.71885 |
299 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80004 |
300 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 308.07199 |
301 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 308.07199 |
302 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 308.07199 |
303 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 3940.23973 |
304 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.71885 |
305 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
306 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 308.07199 |
307 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 3940.23973 |
308 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 371.99148 |
309 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.91913 |
310 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80057 |
311 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 371.99148 |
312 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 371.99148 |
313 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 371.99148 |
314 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 5327.24165 |
315 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.91913 |
316 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
317 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 371.99148 |
318 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 5327.24165 |
319 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 489.23723 |
320 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.11049 |
321 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80083 |
322 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 489.23723 |
323 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 489.23723 |
324 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 489.23723 |
325 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 5328.32213 |
326 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 1.11049 |
327 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
328 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 489.23723 |
329 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 5328.32213 |
330 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 310.29657 |
331 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.71404 |
332 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80095 |
333 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 310.29657 |
334 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 310.29657 |
335 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 310.29657 |
336 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 3940.23973 |
337 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.71404 |
338 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
339 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 310.29657 |
340 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 3940.23973 |
341 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 367.20334 |
342 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.85132 |
343 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80031 |
344 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 367.20334 |
345 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 367.20334 |
346 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 367.20334 |
347 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 5323.03943 |
348 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.85132 |
349 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
350 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 367.20334 |
351 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 5323.03943 |
352 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 507.71180 |
353 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.14776 |
354 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80029 |
355 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 507.71180 |
356 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 507.71180 |
357 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 507.71180 |
358 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 4741.68243 |
359 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 1.14776 |
360 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
361 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 507.71180 |
362 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 4741.68243 |
363 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 315.84742 |
364 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.71950 |
365 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80054 |
366 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 315.84742 |
367 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 315.84742 |
368 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 315.84742 |
369 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 3940.23973 |
370 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.71950 |
371 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
372 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 315.84742 |
373 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 3940.23973 |
374 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 382.98724 |
375 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.88287 |
376 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80031 |
377 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 382.98724 |
378 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 382.98724 |
379 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 382.98724 |
380 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 4743.24240 |
381 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.88287 |
382 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
383 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 382.98724 |
384 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 4743.24240 |
385 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 504.40672 |
386 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.13469 |
387 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80008 |
388 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 504.40672 |
389 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 504.40672 |
390 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 504.40672 |
391 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 4743.65273 |
392 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 1.13469 |
393 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
394 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 504.40672 |
395 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 4743.65273 |
396 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 317.94488 |
397 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.72381 |
398 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80079 |
399 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 317.94488 |
400 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 317.94488 |
401 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 317.94488 |
402 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 3940.23973 |
403 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.72381 |
404 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
405 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 317.94488 |
406 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 3940.23973 |
407 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 381.24995 |
408 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.86866 |
409 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80048 |
410 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 381.24995 |
411 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 381.24995 |
412 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 381.24995 |
413 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 4739.92044 |
414 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.86866 |
415 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
416 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 381.24995 |
417 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 4739.92044 |
418 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 585.57196 |
419 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.31092 |
420 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80084 |
421 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 585.57196 |
422 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 585.57196 |
423 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 585.57196 |
424 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 6473.48865 |
425 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.31092 |
426 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
427 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 585.57196 |
428 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 6473.48865 |
429 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 393.66520 |
430 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.87936 |
431 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80064 |
432 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 393.66520 |
433 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 393.66520 |
434 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 393.66520 |
435 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 4838.15537 |
436 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.87936 |
437 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
438 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 393.66520 |
439 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 4838.15537 |
440 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 460.82621 |
441 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.04548 |
442 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80001 |
443 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 460.82621 |
444 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 460.82621 |
445 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 460.82621 |
446 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 6475.51436 |
447 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.04548 |
448 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
449 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 460.82621 |
450 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 6475.51436 |
451 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 588.89823 |
452 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.31787 |
453 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80098 |
454 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 588.89823 |
455 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 588.89823 |
456 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 588.89823 |
457 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 6475.24846 |
458 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.31787 |
459 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
460 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 588.89823 |
461 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 6475.24846 |
462 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 398.83470 |
463 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.88990 |
464 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80006 |
465 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 398.83470 |
466 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 398.83470 |
467 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 398.83470 |
468 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 4837.95628 |
469 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.88990 |
470 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
471 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 398.83470 |
472 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 4837.95628 |
473 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 464.85164 |
474 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.04790 |
475 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80032 |
476 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 464.85164 |
477 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 464.85164 |
478 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 464.85164 |
479 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 6473.39250 |
480 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.04790 |
481 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
482 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 464.85164 |
483 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 6473.39250 |
484 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNITHEATEDBSMT | Design Size Rated Air Flow Rate [ft3/min] | 302.41522 |
485 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNITHEATEDBSMT | Design Size Gross Rated Total Cooling Capacity [ton] | 0.72868 |
486 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNITHEATEDBSMT | Design Size Gross Rated Sensible Heat Ratio | 0.80098 |
487 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Supply Air Flow Rate [ft3/min] | 302.41522 |
488 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Supply Air Flow Rate During Heating Operation [ft3/min] | 302.41522 |
489 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Supply Air Flow Rate During Cooling Operation [ft3/min] | 302.41522 |
490 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Nominal Heating Capacity [Btu/h] | 11812.49484 |
491 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Nominal Cooling Capacity [ton] | 0.72868 |
492 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
493 | Fan:OnOff | SUPPLY FAN_UNITHEATEDBSMT | Design Size Maximum Flow Rate [ft3/min] | 302.41522 |
494 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNITHEATEDBSMT | Design Size Nominal Capacity [Btu/h] | 11812.49484 |
495 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
496 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
497 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
498 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
499 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
500 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
501 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
502 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
503 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
504 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
505 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
506 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
507 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
508 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
509 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
510 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
511 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
512 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
513 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
514 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
515 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
516 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
517 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
518 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
519 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
520 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
521 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
522 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
523 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
524 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
525 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
526 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
527 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
528 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
529 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
530 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
531 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
532 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
533 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
534 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
535 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
536 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
537 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
538 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
539 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
540 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
541 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
542 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
543 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
544 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
545 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
546 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
547 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
548 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
549 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
550 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
551 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
552 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
553 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
554 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
555 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
556 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
557 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
558 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
559 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
560 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
561 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
562 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
563 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
564 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
565 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
566 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
567 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
568 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
569 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
570 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
571 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
572 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
573 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
574 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
575 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
576 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
577 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
578 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
579 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
580 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
581 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
582 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
583 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
584 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {ton} | Standard Rated Net COP {Btuh/Btuh} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.1 | 3.28 | 11.18 | 11.84 | 11.38 | 11.37 |
2 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.7 | 3.29 | 11.23 | 11.90 | 11.43 | 11.45 |
3 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.9 | 3.33 | 11.36 | 12.03 | 11.57 | 11.65 |
4 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.1 | 3.27 | 11.17 | 11.83 | 11.37 | 11.35 |
5 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.7 | 3.28 | 11.20 | 11.86 | 11.40 | 11.40 |
6 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.8 | 3.29 | 11.22 | 11.88 | 11.42 | 11.43 |
7 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.1 | 3.27 | 11.16 | 11.82 | 11.36 | 11.34 |
8 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.7 | 3.28 | 11.18 | 11.84 | 11.38 | 11.36 |
9 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.8 | 3.28 | 11.20 | 11.87 | 11.41 | 11.41 |
10 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.1 | 3.27 | 11.15 | 11.80 | 11.35 | 11.32 |
11 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.7 | 3.28 | 11.18 | 11.83 | 11.38 | 11.36 |
12 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.8 | 3.28 | 11.18 | 11.84 | 11.38 | 11.36 |
13 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.2 | 3.26 | 11.14 | 11.79 | 11.33 | 11.30 |
14 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.8 | 3.26 | 11.13 | 11.79 | 11.33 | 11.29 |
15 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.0 | 3.27 | 11.17 | 11.83 | 11.37 | 11.35 |
16 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.3 | 3.26 | 11.14 | 11.79 | 11.33 | 11.30 |
17 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.8 | 3.26 | 11.13 | 11.78 | 11.33 | 11.29 |
18 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.0 | 3.27 | 11.15 | 11.81 | 11.35 | 11.33 |
19 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNITHEATEDBSMT | 0.7 | 3.31 | 11.30 | 11.97 | 11.51 | 11.56 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | SizingPeriod:DesignDay | 12/21 | 12/21 | WinterDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
2 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | SizingPeriod:DesignDay | 07/21 | 07/21 | SummerDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
3 | ANNUAL | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | Yes | Yes | No | Yes | Yes | Clark and Allen |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | No | SizingPeriod:DesignDay | ||
2 | No | SizingPeriod:DesignDay | ||
3 | No |
NumberofWarmupDays | |
1 | 6 |
2 | 6 |
3 | 6 |
Max Dry-Bulb Temp {F} | Temp Range {dC} | Temp Range Ind Type | Hum Ind Type | Hum Ind Value at Max Temp | Hum Ind Units | Pressure {psi} | Wind Direction {deg CW from N} | Wind Speed {ft/min} | Clearness | Rain | Snow | |
1 | 32.90 | 0.00 | DefaultMultipliers | Wetbulb | 0.50 | {C} | 13. | 140 | 413.4 | 0.00 | No | No |
2 | 105.44 | 13.30 | DefaultMultipliers | Wetbulb | 18.50 | {C} | 13. | 310 | 944.9 | 0.00 | No | No |
DayOfYear | ASHRAE A Coeff | ASHRAE B Coeff | ASHRAE C Coeff | Solar Constant-Annual Variation | Eq of Time {minutes} | Solar Declination Angle {deg} | Solar Model | |
1 | 355 | 1232.8 | 0.1424 | 5.7719E-002 | 1.0 | 2.45 | -24.. | ASHRAEClearSky |
2 | 202 | 1084.4 | 0.2082 | 0.1365 | 1.0 | -6.23 | 20.6 | ASHRAETau |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaF} | Std Dev Warmup Temperature Difference {deltaF} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {Btu/h} | Std Dev Warmup Load Difference {Btu/h} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | HEATEDBSMT | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.006492904 | 0.006678034 | Pass | Pass |
2 | BREEZEWAY | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000006511 | 0.000003650 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.034115291 | 0.056477957 | Pass | Pass |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.067367802 | 0.118555323 | Pass | Pass |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.034119075 | 0.056484476 | Pass | Pass |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.034102066 | 0.056454967 | Pass | Pass |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.067434186 | 0.118682567 | Pass | Pass |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.034162368 | 0.056560214 | Pass | Pass |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.042932666 | 0.069486293 | Pass | Pass |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.230308738 | 0.468793854 | Pass | Pass |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.042906155 | 0.069439621 | Pass | Pass |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.042896238 | 0.069422667 | Pass | Pass |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.231307623 | 0.471132328 | Pass | Pass |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.042964483 | 0.069541964 | Pass | Pass |
15 | ATTIC | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000159213 | 0.000125786 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.025339580 | 0.037638027 | Pass | Pass |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.025327119 | 0.037618533 | Pass | Pass |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.025339028 | 0.037637186 | Pass | Pass |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.041398400 | 0.063397847 | Pass | Pass |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.041395039 | 0.063392200 | Pass | Pass |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.025328787 | 0.037621173 | Pass | Pass |
22 | HEATEDBSMT | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.004634080 | 0.011175434 | Pass | Pass | 0.049080737 | 0.057998473 | Pass | Pass |
23 | BREEZEWAY | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.397911529 | 0.231845729 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
24 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.011657795 | 0.034292399 | Pass | Pass | 0.066789828 | 0.037794803 | Pass | Pass |
25 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.013535263 | 0.029178090 | Pass | Pass | 0.048544951 | 0.035562051 | Pass | Pass |
26 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.009355669 | 0.019009652 | Pass | Pass | 0.055423491 | 0.053107692 | Pass | Pass |
27 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.011436346 | 0.035574464 | Pass | Pass | 0.065986369 | 0.036623620 | Pass | Pass |
28 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.011877668 | 0.029020728 | Pass | Pass | 0.047779130 | 0.033935505 | Pass | Pass |
29 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.016663713 | 0.033046391 | Pass | Pass | 0.055489799 | 0.054654250 | Pass | Pass |
30 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.010328197 | 0.032032762 | Pass | Pass | 0.062840145 | 0.031882289 | Pass | Pass |
31 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.013256685 | 0.026122802 | Pass | Pass | 0.044887626 | 0.032932096 | Pass | Pass |
32 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.019478669 | 0.033901051 | Pass | Pass | 0.052041958 | 0.046929240 | Pass | Pass |
33 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.009763246 | 0.032264905 | Pass | Pass | 0.062072858 | 0.030655140 | Pass | Pass |
34 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.010178034 | 0.024446268 | Pass | Pass | 0.044410639 | 0.029768662 | Pass | Pass |
35 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.017003613 | 0.031737461 | Pass | Pass | 0.051683455 | 0.047624197 | Pass | Pass |
36 | ATTIC | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.556609618 | 0.411943020 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
37 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.015383813 | 0.033216220 | Pass | Pass | 0.052592787 | 0.045974490 | Pass | Pass |
38 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.016941903 | 0.034343259 | Pass | Pass | 0.053091533 | 0.045592638 | Pass | Pass |
39 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.010265571 | 0.032117259 | Pass | Pass | 0.064216044 | 0.030119940 | Pass | Pass |
40 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.011610000 | 0.026423487 | Pass | Pass | 0.049059448 | 0.028643542 | Pass | Pass |
41 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.013151888 | 0.027180875 | Pass | Pass | 0.048982994 | 0.031052241 | Pass | Pass |
42 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 0.009664321 | 0.031509534 | Pass | Pass | 0.064375613 | 0.029085991 | Pass | Pass |
43 | HEATEDBSMT | RunPeriod: ANNUAL | 0.000000023 | 0.000000059 | Pass | Pass | 0.086680514 | 0.063734524 | Pass | Pass |
44 | BREEZEWAY | RunPeriod: ANNUAL | 0.327651988 | 0.203455011 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
45 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.062773251 | 0.111314180 | Pass | Pass | 0.432350648 | 0.989581381 | Pass | Pass |
46 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.095926297 | 0.147442015 | Pass | Pass | 3.757274262 | 0.385400E+02 | Pass | Pass |
47 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.063204081 | 0.107740226 | Pass | Pass | 0.765691034 | 2.529685997 | Pass | Pass |
48 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.065424437 | 0.112732297 | Pass | Pass | 0.796549898 | 3.722017628 | Pass | Pass |
49 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.040946957 | 0.072147646 | Pass | Pass | 1.053609648 | 4.815813032 | Pass | Pass |
50 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.041478030 | 0.087987015 | Pass | Pass | 0.923174291 | 2.723476300 | Pass | Pass |
51 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.080681344 | 0.133706949 | Pass | Pass | 0.852249937 | 3.488594930 | Pass | Pass |
52 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.149320098 | 0.178202387 | Pass | Pass | 0.479809661 | 1.052510285 | Pass | Pass |
53 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.078234859 | 0.127073078 | Pass | Pass | 1.697680926 | 0.101598E+02 | Pass | Pass |
54 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.077112525 | 0.127757997 | Pass | Pass | 1.534326316 | 0.975045E+01 | Pass | Pass |
55 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.145766590 | 0.169971842 | Pass | Pass | 0.173199E+02 | 0.196393E+03 | Pass | Pass |
56 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.041479377 | 0.069044820 | Pass | Pass | 8.158745977 | 0.585071E+02 | Pass | Pass |
57 | ATTIC | RunPeriod: ANNUAL | 0.538172730 | 0.402562062 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
58 | LIVING_UNIT3_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.042211889 | 0.085647252 | Pass | Pass | 0.961103748 | 3.342067103 | Pass | Pass |
59 | LIVING_UNIT3_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.051271844 | 0.089912872 | Pass | Pass | 0.101123E+02 | 0.114548E+03 | Pass | Pass |
60 | LIVING_UNIT1_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.060988098 | 0.117488775 | Pass | Pass | 1.415301816 | 0.114560E+02 | Pass | Pass |
61 | LIVING_UNIT2_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.060879616 | 0.100167675 | Pass | Pass | 1.169216196 | 5.496831793 | Pass | Pass |
62 | LIVING_UNIT2_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.078997399 | 0.125329769 | Pass | Pass | 1.200623154 | 5.063922748 | Pass | Pass |
63 | LIVING_UNIT1_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.056342162 | 0.103535587 | Pass | Pass | 0.369561310 | 0.912798264 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [kBtu] | 2428205.94 | 187261.48 | 0.00 | 0.00 | 701033.11 | 3316512.52 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 32.90 | 0.00 | 32.90 | Wetbulb [F] | 413.41 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 105.44 | 23.94 | 65.30 | Wetbulb [F] | 944.93 | 310.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_LOWER_LDF | BASEMENT WALL | 0.30 | 0.332 | 0.534 | 839.40 | 839.40 | 180.00 | 90.00 | S |
BGWALL_LOWER_SDR | BASEMENT WALL | 0.30 | 0.332 | 0.534 | 455.77 | 455.77 | 90.00 | 90.00 | E |
BGWALL_LOWER_LDB | BASEMENT WALL | 0.30 | 0.332 | 0.534 | 839.40 | 839.40 | 0.00 | 90.00 | N |
BGWALL_LOWER_SDL | BASEMENT WALL | 0.30 | 0.332 | 0.534 | 455.77 | 455.77 | 270.00 | 90.00 | W |
BGFLOOR | EXTERIOR FLOOR | 0.30 | 0.212 | 0.300 | 7794.39 | 7794.39 | 0.00 | 180.00 | |
iz-FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
BREEZEWAYROOF | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 599.39 | 599.39 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-BREEZEWAYROOF | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 599.39 | 599.39 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.400 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.400 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.400 | 0.217 | 0.883 | ||||||||||||
North Total or Average | 531.68 | 0.400 | 0.217 | 0.883 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.400 | 0.217 | 0.883 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.298 | 0.400 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.90 | 1.00 | 0.99 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.90 | 1.00 | 0.99 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.90 | 1.00 | 0.99 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.96 | 0.00 | 1.00 | 0.97 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.96 | 0.00 | 1.00 | 0.97 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.90 | 1.00 | 0.99 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.90 | 1.00 | 0.99 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.90 | 1.00 | 0.99 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.96 | 0.00 | 1.00 | 0.97 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.96 | 0.00 | 1.00 | 0.97 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.96 | 0.00 | 1.00 | 0.97 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.90 | 1.00 | 0.99 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.96 | 0.00 | 1.00 | 0.97 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.90 | 1.00 | 0.99 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.90 | 1.00 | 0.99 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3110 | 43219.92 | 13441.11 | 12093.82 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
Exterior Lighting Total | 1257.69 | 5508.71 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 13518.07 | 10820.14 | 2697.93 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8626.16 | 6901.31 | 1724.86 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 11029.54 | 8829.95 | 2199.59 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 13325.83 | 10671.79 | 2654.05 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8568.46 | 6862.90 | 1705.56 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 10215.87 | 8175.87 | 2040.00 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 13773.09 | 11022.52 | 2750.57 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8634.05 | 6911.87 | 1722.18 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10594.45 | 8478.86 | 2115.59 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 13616.30 | 10894.15 | 2722.15 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8685.67 | 6955.38 | 1730.28 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10423.88 | 8344.08 | 2079.80 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 15731.02 | 12598.00 | 3133.02 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10552.27 | 8448.60 | 2103.67 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12545.76 | 10036.78 | 2508.98 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 15814.43 | 12667.11 | 3147.32 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10678.77 | 8543.64 | 2135.13 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12574.84 | 10063.94 | 2510.90 | 0.80 | 4.07 | |||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | 8744.12 | 7003.84 | 1740.28 | 0.80 | 4.07 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.1 | 3.28 | 11.18 | 11.84 | 11.38 | 11.37 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.7 | 3.29 | 11.23 | 11.90 | 11.43 | 11.45 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.9 | 3.33 | 11.36 | 12.03 | 11.57 | 11.65 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.1 | 3.27 | 11.17 | 11.83 | 11.37 | 11.35 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.7 | 3.28 | 11.20 | 11.86 | 11.40 | 11.40 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.8 | 3.29 | 11.22 | 11.88 | 11.42 | 11.43 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.1 | 3.27 | 11.16 | 11.82 | 11.36 | 11.34 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.7 | 3.28 | 11.18 | 11.84 | 11.38 | 11.36 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.8 | 3.28 | 11.20 | 11.87 | 11.41 | 11.41 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.1 | 3.27 | 11.15 | 11.80 | 11.35 | 11.32 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.7 | 3.28 | 11.18 | 11.83 | 11.38 | 11.36 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.8 | 3.28 | 11.18 | 11.84 | 11.38 | 11.36 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.2 | 3.26 | 11.14 | 11.79 | 11.33 | 11.30 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.8 | 3.26 | 11.13 | 11.79 | 11.33 | 11.29 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.0 | 3.27 | 11.17 | 11.83 | 11.37 | 11.35 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.3 | 3.26 | 11.14 | 11.79 | 11.33 | 11.30 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.8 | 3.26 | 11.13 | 11.78 | 11.33 | 11.29 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.0 | 3.27 | 11.15 | 11.81 | 11.35 | 11.33 | |
DX COOLING COIL_UNITHEATEDBSMT | 0.7 | 3.31 | 11.30 | 11.97 | 11.51 | 11.56 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | 5327.33 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | 3940.24 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | 5327.24 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | 5328.32 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | 3940.24 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | 5323.04 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | 4741.68 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | 3940.24 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | 4743.24 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | 4743.65 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | 3940.24 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | 4739.92 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | 6473.49 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | 4838.16 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | 6475.51 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Fuel | 6475.25 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Fuel | 4837.96 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Fuel | 6473.39 | 0.80 | |
MAIN FUEL HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Fuel | 11812.49 | 0.80 |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
OASUPPLYFAN_UNITHEATEDBSMT | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNITHEATEDBSMT | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 492.96 | 185.94 | 0.38 | 1.00 | 2.15 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 308.08 | 116.20 | 0.38 | 1.00 | 2.72 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 372.00 | 140.32 | 0.38 | 1.00 | 2.46 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 489.23 | 184.53 | 0.38 | 1.00 | 2.16 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 310.30 | 117.04 | 0.38 | 1.00 | 2.71 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 367.21 | 138.51 | 0.38 | 1.00 | 2.48 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 507.70 | 191.50 | 0.38 | 1.00 | 2.13 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 315.84 | 119.13 | 0.38 | 1.00 | 2.69 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 382.98 | 144.46 | 0.38 | 1.00 | 2.43 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 504.41 | 190.26 | 0.38 | 1.00 | 2.13 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 317.95 | 119.93 | 0.38 | 1.00 | 2.68 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 381.25 | 143.80 | 0.38 | 1.00 | 2.43 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 585.56 | 220.87 | 0.38 | 1.00 | 2.00 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 393.66 | 148.49 | 0.38 | 1.00 | 2.39 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 460.82 | 173.82 | 0.38 | 1.00 | 2.22 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 588.90 | 222.13 | 0.38 | 1.00 | 2.00 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 398.83 | 150.44 | 0.38 | 1.00 | 2.38 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 464.85 | 175.34 | 0.38 | 1.00 | 2.21 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 0.50 | 0.06 | 302.42 | 114.07 | 0.38 | 1.00 | 2.75 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
Type | Control | Head [psi] | Water Flow [gal/min] | Electricity Rate [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | End Use Subcategory | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.55 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.55 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.55 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.55 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.55 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.55 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.55 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.55 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.55 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.55 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 10523.47 | 10523.47 | 8.77 | 492.959 | 492.959 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 75.00 | 75.00 | 0.00811 | 100.49 | 0.00563 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 6576.59 | 6576.59 | 5.48 | 308.075 | 308.075 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 75.00 | 75.00 | 0.00818 | 97.90 | 0.00562 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 7941.37 | 7941.37 | 6.61 | 371.999 | 371.999 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 75.00 | 75.00 | 0.00801 | 105.44 | 0.00563 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 10443.85 | 10443.85 | 8.70 | 489.231 | 489.231 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 75.00 | 75.00 | 0.00812 | 99.69 | 0.00563 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 6624.14 | 6624.14 | 5.52 | 310.303 | 310.303 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 75.00 | 75.00 | 0.00821 | 96.70 | 0.00562 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 7839.07 | 7839.07 | 6.53 | 367.213 | 367.213 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 75.00 | 75.00 | 0.00812 | 99.10 | 0.00563 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 10837.97 | 10837.97 | 9.03 | 507.702 | 507.702 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 75.00 | 75.00 | 0.00821 | 99.69 | 0.00563 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 6742.19 | 6742.19 | 5.62 | 315.838 | 315.838 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00837 | 96.10 | 0.00562 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8175.60 | 8175.60 | 6.81 | 382.984 | 382.984 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 75.00 | 75.00 | 0.00824 | 99.10 | 0.00563 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 10767.59 | 10767.59 | 8.97 | 504.406 | 504.406 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 75.00 | 75.00 | 0.00821 | 99.10 | 0.00563 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 6787.27 | 6787.27 | 5.65 | 317.950 | 317.950 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00836 | 96.10 | 0.00562 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8138.54 | 8138.54 | 6.78 | 381.249 | 381.249 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 75.00 | 75.00 | 0.00827 | 97.90 | 0.00562 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 9923.41 | 9923.41 | 8.27 | 464.853 | 464.853 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 75.00 | 75.00 | 0.00813 | 98.50 | 0.00563 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 9837.36 | 9837.36 | 8.19 | 460.822 | 460.822 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 75.00 | 75.00 | 0.00812 | 99.10 | 0.00563 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 12500.30 | 12500.30 | 10.41 | 585.563 | 585.563 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 75.00 | 75.00 | 0.00811 | 99.69 | 0.00563 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8513.95 | 8513.95 | 7.09 | 398.831 | 398.831 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00820 | 96.10 | 0.00562 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8403.54 | 8403.54 | 7.00 | 393.659 | 393.659 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00820 | 96.10 | 0.00562 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 12571.62 | 12571.62 | 10.47 | 588.904 | 588.904 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 75.00 | 75.00 | 0.00811 | 99.69 | 0.00563 | 44.995 | 0.00 |
HEATEDBSMT | 6454.62 | 6454.62 | 0.83 | 302.415 | 302.415 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 75.00 | 75.00 | 0.00800 | 100.49 | 0.00563 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 3651.48 | 3651.48 | 3.04 | 73.220 | 73.220 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 72.00 | 72.00 | 0.00734 | 32.90 | 0.00432 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 2131.43 | 2131.43 | 1.78 | 42.741 | 44.995 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 72.00 | 72.00 | 0.00729 | 32.90 | 0.00432 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 3651.39 | 3651.39 | 3.04 | 73.219 | 73.219 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 72.00 | 72.00 | 0.00734 | 32.90 | 0.00432 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 3652.49 | 3652.49 | 3.04 | 73.241 | 73.241 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 72.00 | 72.00 | 0.00734 | 32.90 | 0.00432 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2129.77 | 2129.77 | 1.77 | 42.707 | 44.995 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 72.00 | 72.00 | 0.00729 | 32.90 | 0.00432 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 3647.13 | 3647.13 | 3.04 | 73.133 | 73.133 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 72.00 | 72.00 | 0.00734 | 32.90 | 0.00432 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 3057.09 | 3057.09 | 2.55 | 61.304 | 61.304 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 72.00 | 0.00808 | 32.90 | 0.00432 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1413.96 | 1413.96 | 1.18 | 28.355 | 44.995 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 72.00 | 72.00 | 0.00906 | 32.90 | 0.00432 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 3058.68 | 3058.68 | 2.55 | 61.336 | 61.336 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 72.00 | 0.00808 | 32.90 | 0.00432 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 3059.09 | 3059.09 | 2.55 | 61.344 | 61.344 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 72.00 | 0.00808 | 32.90 | 0.00432 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1413.24 | 1413.24 | 1.18 | 28.340 | 44.995 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 72.00 | 72.00 | 0.00906 | 32.90 | 0.00432 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 3055.31 | 3055.31 | 2.54 | 61.268 | 61.268 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 72.00 | 0.00808 | 32.90 | 0.00432 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 4814.49 | 4814.49 | 4.01 | 96.541 | 96.541 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 72.00 | 72.00 | 0.00744 | 32.90 | 0.00432 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 4816.64 | 4816.64 | 4.01 | 96.584 | 96.584 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 72.00 | 72.00 | 0.00744 | 32.90 | 0.00432 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 4814.58 | 4814.58 | 4.01 | 96.543 | 96.543 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 72.00 | 72.00 | 0.00744 | 32.90 | 0.00432 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 3154.85 | 3154.85 | 2.63 | 63.262 | 63.262 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 72.00 | 72.00 | 0.00742 | 32.90 | 0.00432 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 3155.06 | 3155.06 | 2.63 | 63.267 | 63.267 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 72.00 | 72.00 | 0.00742 | 32.90 | 0.00432 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 4816.37 | 4816.37 | 4.01 | 96.579 | 96.579 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 72.00 | 72.00 | 0.00744 | 32.90 | 0.00432 | 44.995 | 0.00 |
HEATEDBSMT | 10232.43 | 10232.43 | 1.31 | 205.190 | 205.190 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 72.00 | 72.00 | 0.00800 | 32.90 | 0.00432 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | Adjusted cooling [ft3/min] | Adjusted heating [ft3/min] | Adjusted main [ft3/min] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 492.96 | 492.96 | 73.22 | 73.22 | 492.9591 | 492.9591 | 492.9591 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 308.08 | 308.08 | 44.99 | 44.99 | 308.0754 | 308.0754 | 308.0754 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 372.00 | 372.00 | 73.22 | 73.22 | 371.9986 | 371.9986 | 371.9986 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 489.23 | 489.23 | 73.24 | 73.24 | 489.2311 | 489.2311 | 489.2311 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 310.30 | 310.30 | 44.99 | 44.99 | 310.3030 | 310.3030 | 310.3030 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 367.21 | 367.21 | 73.13 | 73.13 | 367.2134 | 367.2134 | 367.2134 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 507.70 | 507.70 | 61.30 | 61.30 | 507.7019 | 507.7019 | 507.7019 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 315.84 | 315.84 | 44.99 | 44.99 | 315.8382 | 315.8382 | 315.8382 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 382.98 | 382.98 | 61.34 | 61.34 | 382.9842 | 382.9842 | 382.9842 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 504.41 | 504.41 | 61.34 | 61.34 | 504.4058 | 504.4058 | 504.4058 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 317.95 | 317.95 | 44.99 | 44.99 | 317.9500 | 317.9500 | 317.9500 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 381.25 | 381.25 | 61.27 | 61.27 | 381.2487 | 381.2487 | 381.2487 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 585.56 | 585.56 | 96.54 | 96.54 | 585.5633 | 585.5633 | 585.5633 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 393.66 | 393.66 | 63.27 | 63.27 | 393.6587 | 393.6587 | 393.6587 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 460.82 | 460.82 | 96.58 | 96.58 | 460.8215 | 460.8215 | 460.8215 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 588.90 | 588.90 | 96.58 | 96.58 | 588.9043 | 588.9043 | 588.9043 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 398.83 | 398.83 | 63.26 | 63.26 | 398.8306 | 398.8306 | 398.8306 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 464.85 | 464.85 | 96.54 | 96.54 | 464.8531 | 464.8531 | 464.8531 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 302.42 | 302.42 | 205.19 | 205.19 | 302.4152 | 302.4152 | 302.4152 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 13518.068 | 10820.137 | 492.959099 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 15289.77 | 15289.77 | 492.959099 | 78.62 | 59.96 | 0.00787956 | 53.60 | 50.52 | 0.00787956 | 100.49 | 0.00562683 | 63.90 | 9.1275 | 75.00 | 0.00809575 | 39.8545 | 10508.85 | 0.00 | 13523.71 | 10292.06 |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 5327.332 | 5327.332 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 5327.33 | 5327.33 | 492.959099 | 68.43 | 54.99 | 0.00706291 | 122.00 | 73.02 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 9.1275 | 72.00 | 0.00733886 | 40.0120 | 3651.48 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 8626.164 | 6901.309 | 308.075445 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 9590.97 | 9590.97 | 308.075445 | 79.64 | 60.20 | 0.00780747 | 53.60 | 50.39 | 0.00780747 | 97.90 | 0.00562460 | 63.07 | 14.6052 | 75.00 | 0.00815062 | 40.1213 | 6559.54 | 0.00 | 8629.76 | 6564.43 |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 3940.240 | 3940.240 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 3940.24 | 3940.24 | 308.075445 | 66.29 | 53.81 | 0.00685341 | 122.00 | 73.02 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 14.6052 | 72.00 | 0.00764735 | 41.6718 | 1429.41 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 11029.543 | 8829.949 | 371.998563 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 12827.26 | 12827.26 | 371.998563 | 79.97 | 60.19 | 0.00772272 | 53.60 | 50.24 | 0.00772272 | 105.44 | 0.00563111 | 65.44 | 12.0955 | 75.00 | 0.00801052 | 39.4397 | 7941.37 | 0.00 | 11034.15 | 8398.07 |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 5327.242 | 5327.242 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 5327.24 | 5327.24 | 371.998563 | 67.27 | 54.40 | 0.00697318 | 122.00 | 73.02 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 12.0955 | 72.00 | 0.00733885 | 40.0120 | 3651.39 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 13325.834 | 10671.786 | 489.231104 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 15003.10 | 15003.10 | 489.231104 | 78.56 | 59.96 | 0.00788635 | 53.60 | 50.54 | 0.00788635 | 99.69 | 0.00562614 | 63.65 | 9.1971 | 75.00 | 0.00811153 | 39.9313 | 10436.19 | 0.00 | 13331.39 | 10150.22 |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 5328.322 | 5328.322 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 5328.32 | 5328.32 | 489.231104 | 68.40 | 54.98 | 0.00706091 | 122.00 | 73.02 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 9.1971 | 72.00 | 0.00733897 | 40.0126 | 3652.49 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 8568.460 | 6862.902 | 310.303049 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 9463.53 | 9463.53 | 310.303049 | 79.44 | 60.18 | 0.00783311 | 53.60 | 50.44 | 0.00783311 | 96.70 | 0.00562358 | 62.68 | 14.5003 | 75.00 | 0.00818040 | 40.2660 | 6599.72 | 0.00 | 8572.03 | 6527.44 |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 3940.240 | 3940.240 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 3940.24 | 3940.24 | 310.303049 | 66.33 | 53.83 | 0.00685630 | 122.00 | 73.02 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 14.5003 | 72.00 | 0.00764709 | 41.6704 | 1427.66 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 10215.874 | 8175.874 | 367.213361 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 11449.62 | 11449.62 | 367.213361 | 79.24 | 60.08 | 0.00781578 | 53.60 | 50.41 | 0.00781578 | 99.10 | 0.00562563 | 63.46 | 12.2531 | 75.00 | 0.00811423 | 39.9444 | 7821.63 | 0.00 | 10220.14 | 7776.76 |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 5323.039 | 5323.039 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 5323.04 | 5323.04 | 367.213361 | 67.21 | 54.36 | 0.00696801 | 122.00 | 73.02 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 12.2531 | 72.00 | 0.00733839 | 40.0095 | 3647.13 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 13773.089 | 11022.518 | 507.701941 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 15492.85 | 15492.85 | 507.701941 | 78.48 | 60.07 | 0.00797825 | 53.60 | 50.70 | 0.00797825 | 99.69 | 0.00562614 | 63.65 | 8.8625 | 75.00 | 0.00820325 | 40.3774 | 10823.64 | 0.00 | 13778.84 | 10484.56 |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 4741.682 | 4741.682 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 4741.68 | 4741.68 | 507.701941 | 68.54 | 56.16 | 0.00774800 | 122.00 | 73.02 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 8.8625 | 72.00 | 0.00808177 | 44.0078 | 3057.09 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 8634.051 | 6911.871 | 315.838209 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 9489.53 | 9489.53 | 315.838209 | 79.30 | 60.34 | 0.00797440 | 53.60 | 50.69 | 0.00797440 | 96.10 | 0.00562306 | 62.49 | 14.2462 | 75.00 | 0.00833045 | 40.9952 | 6693.50 | 0.00 | 8637.65 | 6574.41 |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 3940.240 | 3940.240 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 3940.24 | 3940.24 | 315.838209 | 66.43 | 56.41 | 0.00838314 | 122.00 | 73.02 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 14.2462 | 72.00 | 0.01000269 | 54.3010 | 564.31 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 10594.448 | 8478.861 | 382.984220 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 11860.30 | 11860.30 | 382.984220 | 79.12 | 60.22 | 0.00793489 | 53.60 | 50.62 | 0.00793489 | 99.10 | 0.00562563 | 63.46 | 11.7485 | 75.00 | 0.00813241 | 40.0329 | 8091.44 | 0.00 | 10598.87 | 8065.10 |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 4743.242 | 4743.242 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 4743.24 | 4743.24 | 382.984220 | 67.41 | 55.56 | 0.00763921 | 122.00 | 73.02 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 11.7485 | 72.00 | 0.00808166 | 44.0072 | 3058.68 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 13616.305 | 10894.150 | 504.405811 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 15263.99 | 15263.98 | 504.405811 | 78.44 | 60.06 | 0.00798200 | 53.60 | 50.71 | 0.00798200 | 99.10 | 0.00562563 | 63.46 | 8.9204 | 75.00 | 0.00820755 | 40.3983 | 10759.08 | 0.00 | 13621.99 | 10362.60 |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 4743.653 | 4743.653 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 4743.65 | 4743.65 | 504.405811 | 68.51 | 56.15 | 0.00774569 | 122.00 | 73.02 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 8.9204 | 72.00 | 0.00808164 | 44.0071 | 3059.09 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 8685.669 | 6955.385 | 317.950021 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 9546.61 | 9546.61 | 317.950021 | 79.28 | 60.33 | 0.00797619 | 53.60 | 50.70 | 0.00797619 | 96.10 | 0.00562306 | 62.49 | 14.1516 | 75.00 | 0.00835618 | 41.1202 | 6764.68 | 0.00 | 8689.29 | 6615.54 |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 3940.240 | 3940.240 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 3940.24 | 3940.24 | 317.950021 | 66.47 | 56.43 | 0.00838816 | 122.00 | 73.02 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 14.1516 | 72.00 | 0.01000342 | 54.3050 | 563.58 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 10423.881 | 8344.083 | 381.248720 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 11589.30 | 11589.30 | 381.248720 | 78.99 | 60.21 | 0.00795716 | 53.60 | 50.66 | 0.00795716 | 97.90 | 0.00562460 | 63.07 | 11.8020 | 75.00 | 0.00824312 | 40.5711 | 8121.60 | 0.00 | 10428.23 | 7936.76 |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 4739.920 | 4739.920 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 4739.92 | 4739.92 | 381.248720 | 67.39 | 55.55 | 0.00763740 | 122.00 | 73.02 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 11.8020 | 72.00 | 0.00808190 | 44.0085 | 3055.31 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 15731.018 | 12597.997 | 585.563265 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 17721.32 | 17721.32 | 585.563265 | 78.19 | 59.88 | 0.00792336 | 53.60 | 50.60 | 0.00792336 | 99.69 | 0.00562614 | 63.65 | 7.6841 | 75.00 | 0.00811457 | 39.9461 | 12500.30 | 0.00 | 15737.58 | 11981.52 |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 6473.489 | 6473.489 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 6473.49 | 6473.49 | 585.563265 | 68.99 | 55.44 | 0.00720352 | 122.00 | 73.02 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 7.6841 | 72.00 | 0.00744390 | 40.5781 | 4814.58 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 10552.269 | 8448.598 | 393.658696 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11629.09 | 11629.09 | 393.658696 | 78.70 | 60.03 | 0.00790479 | 53.60 | 50.57 | 0.00790479 | 96.10 | 0.00562306 | 62.49 | 11.4299 | 75.00 | 0.00817188 | 40.2246 | 8361.32 | 0.00 | 10556.67 | 8035.30 |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 4838.155 | 4838.155 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 4838.16 | 4838.16 | 393.658696 | 67.53 | 54.65 | 0.00706315 | 122.00 | 73.02 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 11.4299 | 72.00 | 0.00741772 | 40.4364 | 3155.06 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 12545.756 | 10036.776 | 460.821532 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 14073.95 | 14073.95 | 460.821532 | 78.64 | 59.97 | 0.00787740 | 53.60 | 50.52 | 0.00787740 | 99.10 | 0.00562563 | 63.46 | 9.7641 | 75.00 | 0.00811541 | 39.9501 | 9825.73 | 0.00 | 12550.99 | 9547.44 |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 6475.514 | 6475.514 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 6475.51 | 6475.51 | 460.821532 | 68.18 | 55.02 | 0.00713859 | 122.00 | 73.02 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 9.7641 | 72.00 | 0.00744406 | 40.5789 | 4816.64 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 15814.432 | 12667.111 | 588.904266 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 17815.59 | 17815.59 | 588.904266 | 78.18 | 59.88 | 0.00792439 | 53.60 | 50.60 | 0.00792439 | 99.69 | 0.00562614 | 63.65 | 7.6405 | 75.00 | 0.00811451 | 39.9458 | 12571.62 | 0.00 | 15821.03 | 12046.94 |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 6475.248 | 6475.248 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 6475.25 | 6475.25 | 588.904266 | 69.01 | 55.45 | 0.00720501 | 122.00 | 73.02 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 7.6405 | 72.00 | 0.00744404 | 40.5788 | 4816.37 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 10678.774 | 8543.641 | 398.830649 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11769.13 | 11769.13 | 398.830649 | 78.67 | 60.03 | 0.00790777 | 53.60 | 50.57 | 0.00790777 | 96.10 | 0.00562306 | 62.49 | 11.2817 | 75.00 | 0.00818391 | 40.2832 | 8490.81 | 0.00 | 10683.23 | 8126.42 |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 4837.956 | 4837.956 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 4837.96 | 4837.96 | 398.830649 | 67.59 | 54.68 | 0.00706773 | 122.00 | 73.02 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 11.2817 | 72.00 | 0.00741770 | 40.4363 | 3154.85 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 12574.843 | 10063.939 | 464.853100 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 14058.61 | 14058.61 | 464.853100 | 78.57 | 59.96 | 0.00788954 | 53.60 | 50.54 | 0.00788954 | 98.50 | 0.00562512 | 63.26 | 9.6794 | 75.00 | 0.00811536 | 39.9499 | 9890.96 | 0.00 | 12580.09 | 9572.62 |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 6473.392 | 6473.392 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 6473.39 | 6473.39 | 464.853100 | 68.21 | 55.04 | 0.00714109 | 122.00 | 73.02 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 9.6794 | 72.00 | 0.00744390 | 40.5781 | 4814.49 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | 8744.122 | 7003.842 | 302.415218 | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 9877.91 | 9877.91 | 302.415218 | 80.08 | 60.12 | 0.00764691 | 53.60 | 50.10 | 0.00764691 | 100.49 | 0.00562683 | 63.90 | 14.8785 | 75.00 | 0.00800000 | 39.3891 | 6365.89 | 0.00 | 8747.77 | 6661.58 |
MAIN FUEL HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | 11812.495 | 11812.495 | -999. | -999. | -999.00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 11812.49 | 11812.49 | 302.415218 | 66.18 | 54.78 | 0.00745181 | 122.00 | 73.02 | 0.00800000 | 32.90 | 0.00431558 | 32.90 | 14.8785 | 72.00 | 0.00800000 | 43.5685 | 10232.43 | 0.00 | -999.0 | -999.0 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [Btu/lbm-R] | Dry Air Heat Capacity [Btu/lbm-R] | Standard Air Density Adjusted for Elevation [lb/ft3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [ft3/min] | Supply Fan Maximum Air Mass Flow Rate [lb/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [Btu/lbm-R] | Plant Fluid Density [lb/ft3] | Plant Maximum Fluid Mass Flow Rate [lb/s] | Plant Design Fluid Return Temperature [F] | Plant Design Fluid Supply Temperature [F] | Plant Design Fluid Temperature Difference [deltaF] | Plant Design Capacity [Btu/h] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] | Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] | Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] | Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [F] | System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | Coil Air Mass Flow Rate at Rating Conditions [lb/s] | Coil Entering Air Drybulb at Rating Conditions [F] | Coil Entering Air Wetbulb at Rating Conditions [F] | Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] | Coil Leaving Air Drybulb at Rating Conditions [F] | Coil Leaving Air Wetbulb at Rating Conditions [F] | Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 13518.068 | 10820.137 | 492.959099 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 492.959099 | 0.56076393 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | Sensible | 15289.77 | 15289.77 | 0.8841 | 0.56076393 | 492.959099 | 78.62 | 59.96 | 0.00787956 | 11.0 | 53.60 | 50.52 | 0.00787956 | 7.6 | -999. | -999.0 | -999.0 | -999.0 | 634.429 | 14655.34 | 100.49 | 0.00562683 | 63.90 | 44.99498340 | 9.1275 | 75.00 | 0.00810584 | 75.00 | 0.00809575 | 39.8545 | 10508.85 | 0.00 | 13523.71 | 10292.06 | 0.53861799 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.27 | 57.10 | 0.00966469 | 9.3 | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5327.332 | 5327.332 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 492.959099 | 0.56076393 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | Sensible | 5327.33 | 5327.33 | 1.0000 | 0.56076393 | 492.959099 | 68.43 | 54.99 | 0.00706291 | 9.1 | 122.00 | 73.02 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5327.33 | 32.90 | 0.00431558 | 32.90 | 44.99498340 | 9.1275 | 72.00 | 0.00733886 | 72.00 | 0.00733886 | 40.0120 | 3651.48 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8626.164 | 6901.309 | 308.075445 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 308.075445 | 0.35045016 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | Sensible | 9590.97 | 9590.97 | 0.8994 | 0.35045016 | 308.075445 | 79.64 | 60.20 | 0.00780747 | 11.1 | 53.60 | 50.39 | 0.00780747 | 7.6 | -999. | -999.0 | -999.0 | -999.0 | 396.487 | 9194.48 | 97.90 | 0.00562460 | 63.07 | 44.99498340 | 14.6052 | 75.00 | 0.00818081 | 75.00 | 0.00815062 | 40.1213 | 6559.54 | 0.00 | 8629.76 | 6564.43 | 0.33661003 | 80.00 | 67.00 | 0.01118466 | 13.2 | 57.82 | 56.87 | 0.00963029 | 9.3 | |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 3940.240 | 3940.240 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 308.075445 | 0.35045016 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 3940.24 | 3940.24 | 1.0000 | 0.35045016 | 308.075445 | 66.29 | 53.81 | 0.00685341 | 8.7 | 122.00 | 73.02 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3940.24 | 32.90 | 0.00431558 | 32.90 | 44.99498340 | 14.6052 | 72.00 | 0.00728746 | 72.00 | 0.00764735 | 41.6718 | 1429.41 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11029.543 | 8829.949 | 371.998563 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2434 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 371.998563 | 0.42316569 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 12827.26 | 12827.26 | 0.8599 | 0.42316569 | 371.998563 | 79.97 | 60.19 | 0.00772272 | 11.1 | 53.60 | 50.24 | 0.00772272 | 7.5 | -999. | -999.0 | -999.0 | -999.0 | 478.755 | 12348.51 | 105.44 | 0.00563111 | 65.44 | 44.99498340 | 12.0955 | 75.00 | 0.00801052 | 75.00 | 0.00801052 | 39.4397 | 7941.37 | 0.00 | 11034.15 | 8398.07 | 0.40645384 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.50 | 56.20 | 0.00954166 | 9.0 | |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5327.242 | 5327.242 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 371.998563 | 0.42316569 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | Sensible | 5327.24 | 5327.24 | 1.0000 | 0.42316569 | 371.998563 | 67.27 | 54.40 | 0.00697318 | 8.9 | 122.00 | 73.02 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5327.24 | 32.90 | 0.00431558 | 32.90 | 44.99498340 | 12.0955 | 72.00 | 0.00733885 | 72.00 | 0.00733885 | 40.0120 | 3651.39 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 13325.834 | 10671.786 | 489.231104 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 489.231104 | 0.55652316 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | Sensible | 15003.10 | 15003.10 | 0.8882 | 0.55652316 | 489.231104 | 78.56 | 59.96 | 0.00788635 | 11.0 | 53.60 | 50.54 | 0.00788635 | 7.6 | -999. | -999.0 | -999.0 | -999.0 | 629.631 | 14373.47 | 99.69 | 0.00562614 | 63.65 | 44.99498340 | 9.1971 | 75.00 | 0.00811528 | 75.00 | 0.00811153 | 39.9313 | 10436.19 | 0.00 | 13331.39 | 10150.22 | 0.53454470 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.41 | 57.17 | 0.00967703 | 9.4 | |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5328.322 | 5328.322 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 489.231104 | 0.55652316 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | Sensible | 5328.32 | 5328.32 | 1.0000 | 0.55652316 | 489.231104 | 68.40 | 54.98 | 0.00706091 | 9.1 | 122.00 | 73.02 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5328.32 | 32.90 | 0.00431558 | 32.90 | 44.99498340 | 9.1971 | 72.00 | 0.00733897 | 72.00 | 0.00733897 | 40.0126 | 3652.49 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8568.460 | 6862.902 | 310.303049 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 310.303049 | 0.35298417 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 9463.53 | 9463.53 | 0.9054 | 0.35298417 | 310.303049 | 79.44 | 60.18 | 0.00783311 | 11.1 | 53.60 | 50.44 | 0.00783311 | 7.6 | -999. | -999.0 | -999.0 | -999.0 | 399.354 | 9064.18 | 96.70 | 0.00562358 | 62.68 | 44.99498340 | 14.5003 | 75.00 | 0.00820784 | 75.00 | 0.00818040 | 40.2660 | 6599.72 | 0.00 | 8572.03 | 6527.44 | 0.33904396 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.11 | 57.02 | 0.00965694 | 9.3 | |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 3940.240 | 3940.240 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 310.303049 | 0.35298417 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 3940.24 | 3940.24 | 1.0000 | 0.35298417 | 310.303049 | 66.33 | 53.83 | 0.00685630 | 8.7 | 122.00 | 73.02 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3940.24 | 32.90 | 0.00431558 | 32.90 | 44.99498340 | 14.5003 | 72.00 | 0.00728719 | 72.00 | 0.00764709 | 41.6704 | 1427.66 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10215.874 | 8175.874 | 367.213361 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 367.213361 | 0.41772230 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | Sensible | 11449.62 | 11449.62 | 0.8922 | 0.41772230 | 367.213361 | 79.24 | 60.08 | 0.00781578 | 11.1 | 53.60 | 50.41 | 0.00781578 | 7.6 | -999. | -999.0 | -999.0 | -999.0 | 472.597 | 10977.02 | 99.10 | 0.00562563 | 63.46 | 44.99498340 | 12.2531 | 75.00 | 0.00812161 | 75.00 | 0.00811423 | 39.9444 | 7821.63 | 0.00 | 10220.14 | 7776.76 | 0.40122542 | 80.00 | 67.00 | 0.01118466 | 13.2 | 57.96 | 56.94 | 0.00964191 | 9.3 | |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5323.039 | 5323.039 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 367.213361 | 0.41772230 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | Sensible | 5323.04 | 5323.04 | 1.0000 | 0.41772230 | 367.213361 | 67.21 | 54.36 | 0.00696801 | 8.9 | 122.00 | 73.02 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5323.04 | 32.90 | 0.00431558 | 32.90 | 44.99498340 | 12.2531 | 72.00 | 0.00733839 | 72.00 | 0.00733839 | 40.0095 | 3647.13 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 13773.089 | 11022.518 | 507.701941 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 507.701941 | 0.57753460 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | Sensible | 15492.85 | 15492.85 | 0.8890 | 0.57753460 | 507.701941 | 78.48 | 60.07 | 0.00797825 | 11.1 | 53.60 | 50.70 | 0.00797825 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 653.403 | 14839.45 | 99.69 | 0.00562614 | 63.65 | 44.99498340 | 8.8625 | 75.00 | 0.00820697 | 75.00 | 0.00820325 | 40.3774 | 10823.64 | 0.00 | 13778.84 | 10484.56 | 0.55472635 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.51 | 57.22 | 0.00968022 | 9.4 | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 4741.682 | 4741.682 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 507.701941 | 0.57753460 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | Sensible | 4741.68 | 4741.68 | 1.0000 | 0.57753460 | 507.701941 | 68.54 | 56.16 | 0.00774800 | 9.6 | 122.00 | 73.02 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 4741.68 | 32.90 | 0.00431558 | 32.90 | 44.99498340 | 8.8625 | 72.00 | 0.00808177 | 72.00 | 0.00808177 | 44.0078 | 3057.09 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8634.051 | 6911.871 | 315.838209 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 315.838209 | 0.35928067 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 9489.53 | 9489.53 | 0.9099 | 0.35928067 | 315.838209 | 79.30 | 60.34 | 0.00797440 | 11.2 | 53.60 | 50.69 | 0.00797440 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 406.478 | 9083.05 | 96.10 | 0.00562306 | 62.49 | 44.99498340 | 14.2462 | 75.00 | 0.00836502 | 75.00 | 0.00833045 | 40.9952 | 6693.50 | 0.00 | 8637.65 | 6574.41 | 0.34509180 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.34 | 57.14 | 0.00967002 | 9.4 | |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 3940.240 | 3940.240 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 315.838209 | 0.35928067 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 3940.24 | 3940.24 | 1.0000 | 0.35928067 | 315.838209 | 66.43 | 56.41 | 0.00838314 | 9.7 | 122.00 | 73.02 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3940.24 | 32.90 | 0.00431558 | 32.90 | 44.99498340 | 14.2462 | 72.00 | 0.00905888 | 72.00 | 0.01000269 | 54.3010 | 564.31 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10594.448 | 8478.861 | 382.984220 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 382.984220 | 0.43566238 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | Sensible | 11860.30 | 11860.30 | 0.8933 | 0.43566238 | 382.984220 | 79.12 | 60.22 | 0.00793489 | 11.1 | 53.60 | 50.62 | 0.00793489 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 492.894 | 11367.41 | 99.10 | 0.00562563 | 63.46 | 44.99498340 | 11.7485 | 75.00 | 0.00824231 | 75.00 | 0.00813241 | 40.0329 | 8091.44 | 0.00 | 10598.87 | 8065.10 | 0.41845701 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.08 | 57.00 | 0.00965072 | 9.3 | |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 4743.242 | 4743.242 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 382.984220 | 0.43566238 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | Sensible | 4743.24 | 4743.24 | 1.0000 | 0.43566238 | 382.984220 | 67.41 | 55.56 | 0.00763921 | 9.4 | 122.00 | 73.02 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 4743.24 | 32.90 | 0.00431558 | 32.90 | 44.99498340 | 11.7485 | 72.00 | 0.00808166 | 72.00 | 0.00808166 | 44.0072 | 3058.68 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 13616.305 | 10894.150 | 504.405811 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 504.405811 | 0.57378510 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | Sensible | 15263.99 | 15263.98 | 0.8921 | 0.57378510 | 504.405811 | 78.44 | 60.06 | 0.00798200 | 11.1 | 53.60 | 50.71 | 0.00798200 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 649.161 | 14614.82 | 99.10 | 0.00562563 | 63.46 | 44.99498340 | 8.9204 | 75.00 | 0.00821279 | 75.00 | 0.00820755 | 40.3983 | 10759.08 | 0.00 | 13621.99 | 10362.60 | 0.55112492 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.62 | 57.27 | 0.00968643 | 9.4 | |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 4743.653 | 4743.653 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 504.405811 | 0.57378510 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | Sensible | 4743.65 | 4743.65 | 1.0000 | 0.57378510 | 504.405811 | 68.51 | 56.15 | 0.00774569 | 9.6 | 122.00 | 73.02 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 4743.65 | 32.90 | 0.00431558 | 32.90 | 44.99498340 | 8.9204 | 72.00 | 0.00808164 | 72.00 | 0.00808164 | 44.0071 | 3059.09 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8685.669 | 6955.385 | 317.950021 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 317.950021 | 0.36168295 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 9546.61 | 9546.61 | 0.9098 | 0.36168295 | 317.950021 | 79.28 | 60.33 | 0.00797619 | 11.2 | 53.60 | 50.70 | 0.00797619 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 409.196 | 9137.42 | 96.10 | 0.00562306 | 62.49 | 44.99498340 | 14.1516 | 75.00 | 0.00836409 | 75.00 | 0.00835618 | 41.1202 | 6764.68 | 0.00 | 8689.29 | 6615.54 | 0.34739921 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.35 | 57.14 | 0.00967242 | 9.4 | |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 3940.240 | 3940.240 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 317.950021 | 0.36168295 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 3940.24 | 3940.24 | 1.0000 | 0.36168295 | 317.950021 | 66.47 | 56.43 | 0.00838816 | 9.7 | 122.00 | 73.02 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3940.24 | 32.90 | 0.00431558 | 32.90 | 44.99498340 | 14.1516 | 72.00 | 0.00905950 | 72.00 | 0.01000342 | 54.3050 | 563.58 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10423.881 | 8344.083 | 381.248720 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 381.248720 | 0.43368817 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | Sensible | 11589.30 | 11589.30 | 0.8994 | 0.43368817 | 381.248720 | 78.99 | 60.21 | 0.00795716 | 11.1 | 53.60 | 50.66 | 0.00795716 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 490.660 | 11098.64 | 97.90 | 0.00562460 | 63.07 | 44.99498340 | 11.8020 | 75.00 | 0.00826928 | 75.00 | 0.00824312 | 40.5711 | 8121.60 | 0.00 | 10428.23 | 7936.76 | 0.41656077 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.33 | 57.13 | 0.00966946 | 9.4 | |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 4739.920 | 4739.920 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 381.248720 | 0.43368817 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | Sensible | 4739.92 | 4739.92 | 1.0000 | 0.43368817 | 381.248720 | 67.39 | 55.55 | 0.00763740 | 9.3 | 122.00 | 73.02 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 4739.92 | 32.90 | 0.00431558 | 32.90 | 44.99498340 | 11.8020 | 72.00 | 0.00808190 | 72.00 | 0.00808190 | 44.0085 | 3055.31 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 15731.018 | 12597.997 | 585.563265 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 585.563265 | 0.66610548 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | Sensible | 17721.32 | 17721.32 | 0.8877 | 0.66610548 | 585.563265 | 78.19 | 59.88 | 0.00792336 | 11.0 | 53.60 | 50.60 | 0.00792336 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 753.609 | 16967.71 | 99.69 | 0.00562614 | 63.65 | 44.99498340 | 7.6841 | 75.00 | 0.00811457 | 75.00 | 0.00811457 | 39.9461 | 12500.30 | 0.00 | 15737.58 | 11981.52 | 0.63979935 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.71 | 57.32 | 0.00969742 | 9.4 | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6473.489 | 6473.489 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 585.563265 | 0.66610548 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | Sensible | 6473.49 | 6473.49 | 1.0000 | 0.66610548 | 585.563265 | 68.99 | 55.44 | 0.00720352 | 9.3 | 122.00 | 73.02 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6473.49 | 32.90 | 0.00431558 | 32.90 | 44.99498340 | 7.6841 | 72.00 | 0.00744390 | 72.00 | 0.00744390 | 40.5781 | 4814.58 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10552.269 | 8448.598 | 393.658696 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 393.658696 | 0.44780510 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11629.09 | 11629.09 | 0.9074 | 0.44780510 | 393.658696 | 78.70 | 60.03 | 0.00790479 | 11.0 | 53.60 | 50.57 | 0.00790479 | 7.6 | -999. | -999.0 | -999.0 | -999.0 | 506.631 | 11122.46 | 96.10 | 0.00562306 | 62.49 | 44.99498340 | 11.4299 | 75.00 | 0.00819925 | 75.00 | 0.00817188 | 40.2246 | 8361.32 | 0.00 | 10556.67 | 8035.30 | 0.43012018 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.76 | 57.35 | 0.00969962 | 9.4 | |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 4838.155 | 4838.155 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 393.658696 | 0.44780510 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | Sensible | 4838.16 | 4838.16 | 1.0000 | 0.44780510 | 393.658696 | 67.53 | 54.65 | 0.00706315 | 9.0 | 122.00 | 73.02 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 4838.16 | 32.90 | 0.00431558 | 32.90 | 44.99498340 | 11.4299 | 72.00 | 0.00741772 | 72.00 | 0.00741772 | 40.4364 | 3155.06 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12545.756 | 10036.776 | 460.821532 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 460.821532 | 0.52420595 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | Sensible | 14073.95 | 14073.95 | 0.8914 | 0.52420595 | 460.821532 | 78.64 | 59.97 | 0.00787740 | 11.0 | 53.60 | 50.52 | 0.00787740 | 7.6 | -999. | -999.0 | -999.0 | -999.0 | 593.069 | 13480.89 | 99.10 | 0.00562563 | 63.46 | 44.99498340 | 9.7641 | 75.00 | 0.00812105 | 75.00 | 0.00811541 | 39.9501 | 9825.73 | 0.00 | 12550.99 | 9547.44 | 0.50350378 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.44 | 57.18 | 0.00967345 | 9.4 | |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6475.514 | 6475.514 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 460.821532 | 0.52420595 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | Sensible | 6475.51 | 6475.51 | 1.0000 | 0.52420595 | 460.821532 | 68.18 | 55.02 | 0.00713859 | 9.2 | 122.00 | 73.02 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6475.51 | 32.90 | 0.00431558 | 32.90 | 44.99498340 | 9.7641 | 72.00 | 0.00744406 | 72.00 | 0.00744406 | 40.5789 | 4816.64 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 15814.432 | 12667.111 | 588.904266 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 588.904266 | 0.66990602 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | Sensible | 17815.59 | 17815.59 | 0.8877 | 0.66990602 | 588.904266 | 78.18 | 59.88 | 0.00792439 | 11.0 | 53.60 | 50.60 | 0.00792439 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 757.909 | 17057.68 | 99.69 | 0.00562614 | 63.65 | 44.99498340 | 7.6405 | 75.00 | 0.00811451 | 75.00 | 0.00811451 | 39.9458 | 12571.62 | 0.00 | 15821.03 | 12046.94 | 0.64344980 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.71 | 57.33 | 0.00969876 | 9.4 | |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6475.248 | 6475.248 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 588.904266 | 0.66990602 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | Sensible | 6475.25 | 6475.25 | 1.0000 | 0.66990602 | 588.904266 | 69.01 | 55.45 | 0.00720501 | 9.3 | 122.00 | 73.02 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6475.25 | 32.90 | 0.00431558 | 32.90 | 44.99498340 | 7.6405 | 72.00 | 0.00744404 | 72.00 | 0.00744404 | 40.5788 | 4816.37 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10678.774 | 8543.641 | 398.830649 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 398.830649 | 0.45368843 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11769.13 | 11769.13 | 0.9074 | 0.45368843 | 398.830649 | 78.67 | 60.03 | 0.00790777 | 11.0 | 53.60 | 50.57 | 0.00790777 | 7.6 | -999. | -999.0 | -999.0 | -999.0 | 513.288 | 11255.85 | 96.10 | 0.00562306 | 62.49 | 44.99498340 | 11.2817 | 75.00 | 0.00819830 | 75.00 | 0.00818391 | 40.2832 | 8490.81 | 0.00 | 10683.23 | 8126.42 | 0.43577117 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.80 | 57.36 | 0.00969827 | 9.4 | |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 4837.956 | 4837.956 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 398.830649 | 0.45368843 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | Sensible | 4837.96 | 4837.96 | 1.0000 | 0.45368843 | 398.830649 | 67.59 | 54.68 | 0.00706773 | 9.0 | 122.00 | 73.02 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 4837.96 | 32.90 | 0.00431558 | 32.90 | 44.99498340 | 11.2817 | 72.00 | 0.00741770 | 72.00 | 0.00741770 | 40.4363 | 3154.85 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12574.843 | 10063.939 | 464.853100 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 464.853100 | 0.52879205 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | Sensible | 14058.61 | 14058.61 | 0.8945 | 0.52879205 | 464.853100 | 78.57 | 59.96 | 0.00788954 | 11.0 | 53.60 | 50.54 | 0.00788954 | 7.6 | -999. | -999.0 | -999.0 | -999.0 | 598.257 | 13460.35 | 98.50 | 0.00562512 | 63.26 | 44.99498340 | 9.6794 | 75.00 | 0.00813221 | 75.00 | 0.00811536 | 39.9499 | 9890.96 | 0.00 | 12580.09 | 9572.62 | 0.50790876 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.57 | 57.25 | 0.00968460 | 9.4 | |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6473.392 | 6473.392 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 464.853100 | 0.52879205 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | Sensible | 6473.39 | 6473.39 | 1.0000 | 0.52879205 | 464.853100 | 68.21 | 55.04 | 0.00714109 | 9.2 | 122.00 | 73.02 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6473.39 | 32.90 | 0.00431558 | 32.90 | 44.99498340 | 9.6794 | 72.00 | 0.00744390 | 72.00 | 0.00744390 | 40.5781 | 4814.49 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | HEATEDBSMT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8744.122 | 7003.842 | 302.415218 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2434 | 0.2400 | 0.0682 | SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 302.415218 | 0.34401139 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | Sensible | 9877.91 | 9877.91 | 0.8852 | 0.34401139 | 302.415218 | 80.08 | 60.12 | 0.00764691 | 11.1 | 53.60 | 50.10 | 0.00764691 | 7.5 | -999. | -999.0 | -999.0 | -999.0 | 389.203 | 9488.71 | 100.49 | 0.00562683 | 63.90 | 44.99498340 | 14.8785 | 75.00 | 0.00800000 | 75.00 | 0.00800000 | 39.3891 | 6365.89 | 0.00 | 8747.77 | 6661.58 | 0.33042554 | 80.00 | 67.00 | 0.01118466 | 13.2 | 57.07 | 56.50 | 0.00958520 | 9.1 | |
MAIN FUEL HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | HEATEDBSMT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11812.495 | 11812.495 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0682 | SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 302.415218 | 0.34401139 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 11812.49 | 11812.49 | 1.0000 | 0.34401139 | 302.415218 | 66.18 | 54.78 | 0.00745181 | 9.1 | 122.00 | 73.02 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11812.49 | 32.90 | 0.00431558 | 32.90 | 44.99498340 | 14.8785 | 72.00 | 0.00800000 | 72.00 | 0.00800000 | 43.5685 | 10232.43 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. |
Report: System Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2454.83 | 4083.17 | 140.17 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1967.00 | 4147.17 | 120.67 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2307.17 | 3810.33 | 141.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2220.83 | 4678.17 | 148.50 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1857.33 | 5083.33 | 128.83 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2177.33 | 4598.50 | 142.33 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2933.33 | 3371.00 | 76.33 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2256.17 | 3134.50 | 61.33 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2806.17 | 3053.17 | 75.83 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2560.33 | 3965.17 | 82.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2052.50 | 4101.33 | 68.67 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2533.33 | 3868.17 | 86.83 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 2711.50 | 3803.67 | 111.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 2865.33 | 3252.17 | 101.17 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 3031.17 | 3561.50 | 106.83 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 2246.17 | 4041.33 | 87.17 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 2383.00 | 3419.67 | 82.17 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 2786.17 | 3965.83 | 119.67 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 3441.67 | 5275.83 | 184.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 90.50 | 0.00 | 90.50 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 143.50 | 0.00 | 143.50 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 60.17 | 0.00 | 60.17 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.67 | 0.00 | 90.67 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 104.17 | 0.00 | 104.17 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 116.17 | 0.00 | 116.17 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 88.17 | 0.00 | 88.17 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 153.17 | 0.00 | 153.17 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 197.33 | 0.00 | 197.33 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 84.00 | 0.00 | 84.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 93.83 | 0.00 | 93.83 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 119.33 | 0.00 | 119.33 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 113.50 | 0.00 | 113.50 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 137.17 | 0.00 | 137.17 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 86.67 | 0.00 | 86.67 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 112.33 | 0.00 | 112.33 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 133.00 | 0.00 | 133.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 84.67 | 0.00 | 84.67 |
HEATEDBSMT | 0.00 | 34.67 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 287.50 | 0.00 | 287.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.155 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.137 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.155 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.155 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.136 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.155 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.068 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.050 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.068 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.068 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.050 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.068 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.155 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.155 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.155 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.137 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.137 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.155 | 0.000 | 0.000 |
HEATEDBSMT | 58539.52 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.264 | 0.001 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.264 | 0.001 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.264 | 0.001 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.264 | 0.001 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.264 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.264 | 0.001 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.264 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.264 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.264 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.264 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.264 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.264 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.264 | 0.001 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.264 | 0.001 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.264 | 0.001 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.264 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.264 | 0.001 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.264 | 0.000 | 0.000 | 0.000 |
HEATEDBSMT | 58539.52 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Zone Area [ft2] | Design Zone Outdoor Airflow - Voz [ft3/min] | Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 58539.52 | 7794.39 | 0.0000 | 0.000 | |
Total Facility | 24.79 | 36.00 | 242278.90 | 29404.35 | 0.0000 | 0.000 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3] | Total Ventilation [ft3] | Infiltration [ft3] | Total Ventilation and Infiltration [ft3] | Dynamic Target Ventilation - Voz-dyn [ft3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 13673203.86 | 37458285.55 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12063599.45 | 35848681.13 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 13690328.59 | 37475410.28 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 13640909.61 | 37425991.30 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12029190.62 | 35814272.30 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 13663620.24 | 37448701.93 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 6005422.94 | 29790504.62 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 4379769.22 | 28164850.91 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 6011230.69 | 29796312.38 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 5991667.85 | 29776749.54 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 4368698.43 | 28153780.12 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 6002631.88 | 29787713.56 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 13685635.75 | 37470717.44 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 13707593.82 | 37492675.51 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 13691098.38 | 37476180.07 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12053961.73 | 35839043.42 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12082006.61 | 35867088.30 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 13664890.73 | 37449972.41 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
HEATEDBSMT | 23785081.69 | 0.00 | 23785081.69 | 0.00 | 23785081.69 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 8808.00 |
Total Facility | 0.451917E+09 | 0.00 | 0.451917E+09 | 0.190405E+09 | 0.642322E+09 | 0.451917E+09 | 0.00 | 8808.00 | 0.00 | 8808.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Infiltration [ft3/min] | Total Ventilation and Infiltration [ft3/min] | Dynamic Target Ventilation - Voz-dyn [ft3/min] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 25.8660 | 70.8610 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.8211 | 67.8161 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 25.8984 | 70.8934 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 25.8049 | 70.7999 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.7560 | 67.7510 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 25.8479 | 70.8429 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 11.3606 | 56.3556 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 8.2853 | 53.2803 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 11.3716 | 56.3666 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 11.3346 | 56.3296 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 8.2644 | 53.2594 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 11.3554 | 56.3503 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 25.8895 | 70.8845 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 25.9311 | 70.9261 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 25.8999 | 70.8949 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.8029 | 67.7978 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.8559 | 67.8509 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 25.8503 | 70.8453 | 44.9950 | 0.00 | 8808.00 | 0.00 |
Total Facility | 809.9097 | 0.0000 | 809.9097 | 360.1960 | 1170.1057 | 809.9097 | 0.00 | 8808.00 | 0.00 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [ft3/min] | Limits and Scheduled Limits [ft3/min] | Economizer [ft3/min] | Exhaust Flow [ft3/min] | Mixed Air Flow [ft3/min] | High Humidity [ft3/min] | Demand Controlled Ventilation [ft3/min] | Night Ventilation [ft3/min] | Demand Limiting [ft3/min] | Energy Management System [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 54 |
Floor | 29 | 3 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 60 | 60 |
Overhang | 30 | 30 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 19 |
Conditioned Zones | 19 |
Unconditioned Zones | 2 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 2049 |
Defaulted Fields | 1627 |
Fields with Defaults | 6721 |
Autosized Fields | 338 |
Autosizable Fields | 600 |
Autocalculated Fields | 161 |
Autocalculatable Fields | 349 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 149643.94 | 8514.35 | 01-MAR-12:10 | 37111.67 | 28-JUN-19:10 |
Electricity:Building | 88739.59 | 6995.45 | 02-JAN-03:10 | 16626.98 | 01-JAN-20:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4929.98 | 388.64 | 02-JAN-03:10 | 923.72 | 01-JAN-20:10 |
InteriorLights:Electricity | 12093.82 | 270.83 | 01-JAN-00:10 | 3939.36 | 01-JAN-19:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
General:InteriorLights:Electricity | 12093.82 | 270.83 | 01-JAN-00:10 | 3939.36 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4929.98 | 388.64 | 02-JAN-03:10 | 923.72 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4929.98 | 388.64 | 02-JAN-03:10 | 923.72 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4929.98 | 388.64 | 02-JAN-03:10 | 923.72 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4929.98 | 388.64 | 02-JAN-03:10 | 923.72 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4929.98 | 388.64 | 02-JAN-03:10 | 923.72 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4929.98 | 388.64 | 02-JAN-03:10 | 923.72 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4929.98 | 388.64 | 02-JAN-03:10 | 923.72 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4929.98 | 388.64 | 02-JAN-03:10 | 923.72 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4929.98 | 388.64 | 02-JAN-03:10 | 923.72 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4929.98 | 388.64 | 02-JAN-03:10 | 923.72 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4929.98 | 388.64 | 02-JAN-03:10 | 923.72 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4929.98 | 388.64 | 02-JAN-03:10 | 923.72 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4929.98 | 388.64 | 02-JAN-03:10 | 923.72 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4929.98 | 388.64 | 02-JAN-03:10 | 923.72 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4929.98 | 388.64 | 02-JAN-03:10 | 923.72 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4929.98 | 388.64 | 02-JAN-03:10 | 923.72 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4929.98 | 388.64 | 02-JAN-03:10 | 923.72 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
InteriorEquipment:Electricity | 76645.77 | 6518.84 | 02-JAN-04:10 | 12687.62 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4258.10 | 362.16 | 02-JAN-04:10 | 704.87 | 01-JAN-20:10 |
dishwasher:InteriorEquipment:Electricity | 2758.31 | 25.25 | 02-JAN-03:10 | 880.12 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:10 | 1639.04 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity | 1408.53 | 13.53 | 02-JAN-02:10 | 381.47 | 01-JAN-09:10 |
gas_dryer:InteriorEquipment:Electricity | 1138.84 | 5.81 | 02-JAN-03:10 | 291.20 | 01-JAN-11:10 |
gas_range:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
gas_mels:InteriorEquipment:Electricity | 41935.01 | 3663.85 | 01-JAN-09:10 | 7086.44 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity | 17368.96 | 1517.52 | 01-JAN-09:10 | 2935.11 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4258.10 | 362.16 | 02-JAN-04:10 | 704.87 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4258.10 | 362.16 | 02-JAN-04:10 | 704.87 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4258.10 | 362.16 | 02-JAN-04:10 | 704.87 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4258.10 | 362.16 | 02-JAN-04:10 | 704.87 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4258.10 | 362.16 | 02-JAN-04:10 | 704.87 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4258.10 | 362.16 | 02-JAN-04:10 | 704.87 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4258.10 | 362.16 | 02-JAN-04:10 | 704.87 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4258.10 | 362.16 | 02-JAN-04:10 | 704.87 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4258.10 | 362.16 | 02-JAN-04:10 | 704.87 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4258.10 | 362.16 | 02-JAN-04:10 | 704.87 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4258.10 | 362.16 | 02-JAN-04:10 | 704.87 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4258.10 | 362.16 | 02-JAN-04:10 | 704.87 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4258.10 | 362.16 | 02-JAN-04:10 | 704.87 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4258.10 | 362.16 | 02-JAN-04:10 | 704.87 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4258.10 | 362.16 | 02-JAN-04:10 | 704.87 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4258.10 | 362.16 | 02-JAN-04:10 | 704.87 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4258.10 | 362.16 | 02-JAN-04:10 | 704.87 | 01-JAN-20:10 |
Fans:Electricity | 14869.60 | 610.71 | 08-OCT-05:40 | 3607.49 | 02-JUN-17:00 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 149643.94 | 8514.35 | 01-MAR-12:10 | 37111.67 | 28-JUN-19:10 |
ElectricityPurchased:Plant | 149643.94 | 8514.35 | 01-MAR-12:10 | 37111.67 | 28-JUN-19:10 |
Cogeneration:ElectricityPurchased | 149643.94 | 8514.35 | 01-MAR-12:10 | 37111.67 | 28-JUN-19:10 |
General:Cogeneration:ElectricityPurchased | 149643.94 | 8514.35 | 01-MAR-12:10 | 37111.67 | 28-JUN-19:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 149643.94 | 8514.35 | 01-MAR-12:10 | 37111.67 | 28-JUN-19:10 |
ElectricityNet:Plant | 149643.94 | 8514.35 | 01-MAR-12:10 | 37111.67 | 28-JUN-19:10 |
Cogeneration:ElectricityNet | 149643.94 | 8514.35 | 01-MAR-12:10 | 37111.67 | 28-JUN-19:10 |
General:Cogeneration:ElectricityNet | 149643.94 | 8514.35 | 01-MAR-12:10 | 37111.67 | 28-JUN-19:10 |
Electricity:HVAC | 55395.64 | 610.71 | 08-OCT-05:40 | 19925.74 | 28-JUN-17:00 |
HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Fans:Electricity | 9519.74 | 0.00 | 08-OCT-05:40 | 2996.78 | 02-JUN-17:00 |
Ventilation:Fans:Electricity | 5349.86 | 610.71 | 01-JAN-00:10 | 610.71 | 01-JAN-00:10 |
ExteriorLights:Electricity | 5508.71 | 0.00 | 01-JAN-06:10 | 1257.69 | 01-JAN-00:10 |
Exterior-Lights:ExteriorLights:Electricity | 5508.71 | 0.00 | 01-JAN-06:10 | 1257.69 | 01-JAN-00:10 |
Garage-Lights:ExteriorLights:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 40526.04 | 0.00 | 01-JAN-00:10 | 16318.24 | 28-JUN-17:00 |
General:Cooling:Electricity | 40526.04 | 0.00 | 01-JAN-00:10 | 16318.24 | 28-JUN-17:00 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Natural Gas Annual Value [therm] | Natural Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4201.02 | 2644.47 | 01-MAY-03:10 | 276739.17 | 01-JAN-07:10 |
NaturalGas:Building | 1639.73 | 2644.47 | 02-JAN-03:10 | 43735.22 | 01-JAN-17:10 |
NaturalGas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas | 1639.73 | 2644.47 | 02-JAN-03:10 | 43735.22 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
gas_dryer:InteriorEquipment:NaturalGas | 792.69 | 403.80 | 02-JAN-03:10 | 20254.25 | 01-JAN-11:10 |
gas_range:InteriorEquipment:NaturalGas | 674.43 | 651.88 | 01-JAN-02:10 | 27685.38 | 01-JAN-17:10 |
gas_mels:InteriorEquipment:NaturalGas | 172.61 | 1507.04 | 01-JAN-09:10 | 2914.85 | 01-JAN-20:10 |
NaturalGas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
NaturalGas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
NaturalGas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
NaturalGas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
NaturalGas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
NaturalGas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
NaturalGas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
NaturalGas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
NaturalGas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
NaturalGas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
NaturalGas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
NaturalGas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
NaturalGas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
NaturalGas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
NaturalGas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
NaturalGas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
NaturalGas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
NaturalGas:HVAC | 508.02 | 0.00 | 03-JAN-15:40 | 116910.68 | 07-DEC-06:00 |
Heating:NaturalGas | 508.02 | 0.00 | 03-JAN-15:40 | 116910.68 | 07-DEC-06:00 |
General:Heating:NaturalGas | 508.02 | 0.00 | 03-JAN-15:40 | 116910.68 | 07-DEC-06:00 |
NaturalGas:Plant | 2053.27 | 0.00 | 01-JAN-00:10 | 169316.29 | 01-JAN-08:30 |
WaterSystems:NaturalGas | 2053.27 | 0.00 | 01-JAN-00:10 | 169316.29 | 01-JAN-08:30 |
Water Heater:WaterSystems:NaturalGas | 2053.27 | 0.00 | 01-JAN-00:10 | 169316.29 | 01-JAN-08:30 |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Water:Plant | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
WaterSystems:Water | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Domestic Hot Water:WaterSystems:Water | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
MainsWater:Facility | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
MainsWater:Plant | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
WaterSystems:MainsWater | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Domestic Hot Water:WaterSystems:MainsWater | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1200438.44 | 13842.19 | 14-OCT-04:00 | 376220.76 | 16-JUL-18:40 |
EnergyTransfer:Building | 522193.82 | 3510.15 | 27-OCT-10:00 | 164602.20 | 19-JUN-18:40 |
EnergyTransfer:Zone:HEATEDBSMT | 27774.78 | 0.56 | 15-APR-22:20 | 10290.65 | 07-DEC-05:10 |
Heating:EnergyTransfer | 27839.25 | 0.00 | 03-JAN-16:50 | 68469.74 | 07-DEC-06:00 |
Heating:EnergyTransfer:Zone:HEATEDBSMT | 15448.16 | 0.00 | 03-JAN-16:50 | 10290.65 | 07-DEC-05:10 |
General:Heating:EnergyTransfer | 27839.25 | 0.00 | 03-JAN-16:50 | 68469.74 | 07-DEC-06:00 |
Cooling:EnergyTransfer | 494354.57 | 0.00 | 01-JAN-03:20 | 164602.20 | 19-JUN-18:40 |
Cooling:EnergyTransfer:Zone:HEATEDBSMT | 12326.62 | 0.00 | 01-JAN-00:10 | 6592.79 | 16-JUL-18:40 |
General:Cooling:EnergyTransfer | 494354.57 | 0.00 | 01-JAN-03:20 | 164602.20 | 19-JUN-18:40 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 27748.52 | 0.76 | 09-NOV-04:40 | 10525.24 | 09-JUN-18:20 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 976.90 | 0.00 | 01-JAN-11:10 | 3789.88 | 07-DEC-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 26771.62 | 0.00 | 01-JAN-00:10 | 10525.24 | 09-JUN-18:20 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 22709.83 | 0.02 | 26-FEB-03:10 | 6563.42 | 27-AUG-20:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 352.73 | 0.00 | 01-JAN-00:10 | 2316.77 | 01-JAN-02:40 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 22357.11 | 0.00 | 01-JAN-00:20 | 6563.42 | 27-AUG-20:00 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 27862.92 | 0.00 | 23-MAR-02:10 | 8209.56 | 22-JUL-18:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 887.38 | 0.00 | 01-JAN-10:10 | 3817.22 | 07-DEC-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 26975.55 | 0.00 | 01-JAN-00:10 | 8209.56 | 22-JUL-18:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 24306.07 | 0.73 | 23-DEC-00:50 | 10542.42 | 12-JUN-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1202.31 | 0.00 | 01-JAN-13:40 | 3880.51 | 07-DEC-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 23103.76 | 0.00 | 01-JAN-00:10 | 10542.42 | 12-JUN-18:10 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 19097.00 | 0.01 | 25-NOV-11:00 | 6556.61 | 28-JUN-21:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 470.22 | 0.00 | 01-JAN-14:10 | 2344.07 | 24-NOV-00:50 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 18626.78 | 0.00 | 01-JAN-00:10 | 6556.61 | 28-JUN-21:50 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 24074.14 | 0.25 | 09-DEC-22:30 | 7802.61 | 19-JUN-19:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 997.39 | 0.00 | 01-JAN-13:30 | 3931.95 | 07-DEC-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 23076.75 | 0.00 | 01-JAN-00:10 | 7802.61 | 19-JUN-19:10 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 31437.38 | 0.87 | 13-FEB-02:20 | 10860.88 | 14-APR-18:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 432.56 | 0.00 | 01-JAN-00:10 | 2837.93 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 31004.82 | 0.00 | 01-JAN-00:50 | 10860.88 | 14-APR-18:00 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 26592.71 | 0.16 | 13-JAN-05:20 | 6944.74 | 26-AUG-20:40 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 76.37 | 0.00 | 01-JAN-00:10 | 2045.21 | 08-DEC-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 26516.34 | 0.00 | 01-JAN-02:50 | 6944.74 | 26-AUG-20:40 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 31773.73 | 0.68 | 13-FEB-05:40 | 8237.04 | 26-AUG-19:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 373.57 | 0.00 | 01-JAN-00:10 | 2871.93 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 31400.16 | 0.00 | 01-JAN-00:50 | 8237.04 | 26-AUG-19:50 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 27258.75 | 0.06 | 13-MAR-05:50 | 10840.90 | 12-JUN-18:20 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 601.72 | 0.00 | 01-JAN-00:10 | 2967.59 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 26657.03 | 0.00 | 01-JAN-00:20 | 10840.90 | 12-JUN-18:20 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 22090.36 | 0.78 | 01-JAN-07:10 | 6829.49 | 28-JUN-22:40 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 138.13 | 0.00 | 01-JAN-00:10 | 2142.04 | 16-DEC-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 21952.23 | 0.00 | 01-JAN-01:30 | 6829.49 | 28-JUN-22:40 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 27312.48 | 0.02 | 21-APR-04:50 | 8226.02 | 28-JUN-22:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 458.36 | 0.00 | 01-JAN-00:10 | 3051.15 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 26854.12 | 0.00 | 01-JAN-00:20 | 8226.02 | 28-JUN-22:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 30655.78 | 0.07 | 31-MAR-02:50 | 9925.45 | 28-JUN-21:40 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 1096.17 | 0.00 | 01-JAN-14:10 | 4875.48 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 29559.62 | 0.00 | 01-JAN-00:10 | 9925.45 | 28-JUN-21:40 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 33642.75 | 0.16 | 09-MAR-07:20 | 9851.01 | 26-AUG-19:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 936.45 | 0.00 | 01-JAN-11:00 | 4720.07 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 32706.30 | 0.00 | 01-JAN-00:10 | 9851.01 | 26-AUG-19:50 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 33531.75 | 0.07 | 15-FEB-07:00 | 12482.73 | 14-APR-17:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 1091.02 | 0.00 | 01-JAN-00:20 | 4684.35 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 32440.74 | 0.00 | 01-JAN-00:10 | 12482.73 | 14-APR-17:50 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 25211.80 | 0.13 | 23-NOV-22:20 | 8455.32 | 28-JUN-22:20 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 535.03 | 0.00 | 01-JAN-00:20 | 2986.50 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 24676.77 | 0.00 | 01-JAN-00:10 | 8455.32 | 28-JUN-22:20 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 28227.42 | 0.50 | 05-MAR-07:10 | 8511.74 | 26-AUG-20:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 362.23 | 0.00 | 01-JAN-00:10 | 2782.41 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 27865.19 | 0.00 | 01-JAN-01:00 | 8511.74 | 26-AUG-20:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 30885.65 | 0.29 | 23-NOV-23:20 | 12509.36 | 09-JUN-18:40 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 1402.58 | 0.00 | 01-JAN-14:00 | 4827.99 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 29483.07 | 0.00 | 01-JAN-00:10 | 12509.36 | 09-JUN-18:40 |
EnergyTransfer:HVAC | 593141.42 | 0.00 | 08-OCT-05:40 | 207763.52 | 16-JUL-18:40 |
HeatRecoveryForHeating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRecoveryForCooling:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatingCoils:EnergyTransfer | 40641.48 | 0.00 | 03-JAN-15:40 | 93528.55 | 07-DEC-06:00 |
CoolingCoils:EnergyTransfer | 552499.95 | 0.00 | 01-JAN-00:10 | 207763.52 | 16-JUL-18:40 |
EnergyTransfer:Plant | 85103.20 | 569.37 | 24-JUL-02:10 | 25390.19 | 22-JAN-09:00 |
WaterSystems:EnergyTransfer | 85103.20 | 569.37 | 24-JUL-02:10 | 25390.19 | 22-JAN-09:00 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 85103.20 | 569.37 | 24-JUL-02:10 | 25390.19 | 22-JAN-09:00 |
PlantLoopHeatingDemand:Facility | 85103.20 | 569.37 | 24-JUL-02:10 | 25390.19 | 22-JAN-09:00 |
PlantLoopHeatingDemand:Plant | 85103.20 | 569.37 | 24-JUL-02:10 | 25390.19 | 22-JAN-09:00 |
WaterSystems:PlantLoopHeatingDemand | 85103.20 | 569.37 | 24-JUL-02:10 | 25390.19 | 22-JAN-09:00 |
General:WaterSystems:PlantLoopHeatingDemand | 85103.20 | 569.37 | 24-JUL-02:10 | 25390.19 | 22-JAN-09:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2163.522 | -246.71 | 2054.402 | -2252.67 | 0.000 | 0.000 | 2950.915 | 2294.076 | 14464.809 | 11695.571 | 0.000 | 1275.741 | 0.094 | 0.000 | -3393.29 | 0.000 | -1974.57 | -1518.49 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 2162.246 | -250.41 | 915.201 | -1838.35 | 0.000 | 0.000 | 2936.840 | 2294.076 | 14464.809 | 5149.368 | 0.000 | 1122.145 | 0.020 | 0.000 | -1371.75 | 0.000 | -1768.57 | -822.49 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2165.937 | -248.72 | 1849.702 | -2258.25 | 0.000 | 0.000 | 2949.781 | 2294.076 | 14464.809 | 12031.687 | 0.000 | 1278.364 | 0.007 | 0.000 | -3253.35 | 0.000 | -1991.42 | -1685.77 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2163.842 | -243.08 | 2422.687 | -1962.78 | 0.000 | 0.000 | 2957.082 | 2294.076 | 14464.809 | 8600.266 | 0.000 | 1275.496 | 0.015 | 0.000 | -3502.29 | 0.000 | -1944.88 | -2243.04 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2163.812 | -245.67 | 1170.680 | -1544.06 | 0.000 | 0.000 | 2945.514 | 2294.076 | 14464.809 | 1926.539 | 0.000 | 1123.181 | 0.160 | 0.000 | -1445.71 | 0.000 | -1732.82 | -1418.94 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2162.461 | -245.40 | 2057.972 | -1944.79 | 0.000 | 0.000 | 2955.973 | 2294.076 | 14464.809 | 8819.251 | 0.000 | 1274.727 | 0.000 | 0.000 | -3247.52 | 0.000 | -1960.43 | -2521.47 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2164.422 | -252.11 | 1034.135 | -2560.25 | 0.000 | 0.000 | 2928.620 | 2294.076 | 14464.809 | 11610.167 | 0.000 | 557.459 | 3171.127 | 0.000 | -3564.34 | 0.000 | -889.59 | -0.30 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2162.411 | -257.73 | 251.069 | -2145.13 | 0.000 | 0.000 | 2907.657 | 2294.076 | 14464.809 | 5109.891 | 0.000 | 404.806 | 3368.749 | 0.000 | -1445.24 | 0.000 | -664.69 | -0.05 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2159.886 | -254.01 | 892.409 | -2584.01 | 0.000 | 0.000 | 2926.589 | 2294.076 | 14464.809 | 11919.717 | 0.000 | 555.690 | 3176.522 | 0.000 | -3414.16 | 0.000 | -896.60 | -0.12 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2164.948 | -248.58 | 1357.846 | -2214.63 | 0.000 | 0.000 | 2934.719 | 2294.076 | 14464.809 | 8544.743 | 0.000 | 557.444 | 1801.660 | 0.000 | -3665.21 | 0.000 | -876.82 | -0.04 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2165.133 | -253.39 | 418.843 | -1778.44 | 0.000 | 0.000 | 2916.249 | 2294.076 | 14464.809 | 1914.087 | 0.000 | 405.523 | 1989.946 | 0.000 | -1517.99 | 0.000 | -652.49 | -0.03 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2162.841 | -251.22 | 1078.803 | -2216.92 | 0.000 | 0.000 | 2933.176 | 2294.076 | 14464.809 | 8737.633 | 0.000 | 556.819 | 1695.127 | 0.000 | -3400.95 | 0.000 | -884.86 | -0.19 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 2162.130 | -248.02 | 2093.476 | -2476.75 | 0.000 | 0.000 | 2942.496 | 2294.076 | 14464.809 | 8699.138 | 0.000 | 1267.840 | 4191.751 | 0.000 | -3399.39 | 0.000 | -1997.18 | -0.05 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 2161.198 | -250.84 | 1817.525 | -2726.22 | 0.000 | 0.000 | 2936.620 | 2294.076 | 14464.809 | 11897.494 | 0.000 | 1266.987 | 4332.387 | 0.000 | -3399.72 | 0.000 | -2022.74 | -0.12 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 2163.512 | -248.82 | 2081.074 | -2715.40 | 0.000 | 0.000 | 2938.634 | 2294.076 | 14464.809 | 11584.712 | 0.000 | 1269.039 | 4348.780 | 0.000 | -3543.53 | 0.000 | -2006.71 | -0.06 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 2163.443 | -249.27 | 1195.826 | -2040.96 | 0.000 | 0.000 | 2929.924 | 2294.076 | 14464.809 | 1897.816 | 0.000 | 1116.991 | 4722.254 | 0.000 | -1509.79 | 0.000 | -1774.22 | -0.07 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 2161.924 | -252.99 | 867.454 | -2289.68 | 0.000 | 0.000 | 2922.803 | 2294.076 | 14464.809 | 5100.060 | 0.000 | 1116.132 | 4841.958 | 0.000 | -1434.82 | 0.000 | -1801.95 | -0.04 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 2164.570 | -245.97 | 2516.063 | -2482.31 | 0.000 | 0.000 | 2943.745 | 2294.076 | 14464.809 | 8490.820 | 0.000 | 1269.237 | 4250.970 | 0.000 | -3649.25 | 0.000 | -1983.80 | -0.07 |
HEATEDBSMT | 2237.092 | -225.73 | 17521.677 | -1159.78 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.973 | 0.000 | 0.000 | 0.000 | 0.000 | -3121.55 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 29589.886 | 169228.614 | 0.000 | 0.000 | 0.000 | -198818.50 | -1.48 |
Total Facility | 41175.328 | -4718.66 | 43596.843 | -41191.38 | 0.000 | 0.000 | 52857.337 | 41293.362 | 260366.561 | 143728.959 | 0.000 | 47283.508 | 211121.114 | 0.000 | -50158.32 | 0.000 | -226642.85 | -13334.37 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 19-MAY-17:25 | 0.00 | 0.08 | 0.00 | -1.0 | 0.00 | 0.00 | 263.17 | 500.54 | 2748.57 | 6180.70 | 0.00 | 719.92 | 114.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 26-AUG-19:53 | 0.00 | 0.07 | 0.00 | -0.6 | 0.00 | 0.00 | 424.57 | 746.73 | 2338.18 | 146.41 | 0.00 | 287.84 | 2666.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 28-JUN-20:15 | 0.00 | 0.09 | 0.00 | -0.8 | 0.00 | 0.00 | 425.80 | 746.73 | 2154.96 | 767.09 | 0.00 | 612.91 | 3523.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12-JUN-18:10 | 0.00 | 0.07 | 0.00 | -0.9 | 0.00 | 0.00 | 426.76 | 673.81 | 2654.19 | 5609.51 | 0.00 | 709.49 | 468.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 23-JUN-19:35 | 0.00 | 0.07 | 0.00 | -0.6 | 0.00 | 0.00 | 424.65 | 746.73 | 2306.41 | 232.68 | 0.00 | 644.48 | 2209.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 28-JUN-21:20 | 0.00 | 0.07 | 0.00 | -0.7 | 0.00 | 0.00 | 470.25 | 564.71 | 2023.51 | 553.64 | 0.00 | 467.77 | 3728.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 14-APR-18:03 | 0.00 | 0.07 | 0.00 | -1.0 | 0.00 | 0.00 | 426.16 | 673.81 | 2654.19 | 3826.67 | 0.00 | 274.71 | 3068.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 25-AUG-21:23 | 0.00 | 0.05 | 0.00 | -0.6 | 0.00 | 0.00 | 475.66 | 564.71 | 2023.51 | 63.33 | 0.00 | 73.11 | 3848.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 25-AUG-20:27 | 0.00 | 0.07 | 0.00 | -0.8 | 0.00 | 0.00 | 423.77 | 746.73 | 2154.96 | 394.67 | 0.00 | 160.17 | 4386.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 12-JUN-18:25 | 0.00 | 0.07 | 0.00 | -1.0 | 0.00 | 0.00 | 426.55 | 673.81 | 2654.19 | 5181.28 | 0.00 | 279.73 | 1635.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 28-JUN-22:40 | 0.00 | 0.06 | 0.00 | -0.6 | 0.00 | 0.00 | 471.70 | 314.44 | 1714.26 | 145.71 | 0.00 | 98.09 | 4090.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 28-JUN-22:00 | 0.00 | 0.07 | 0.00 | -0.8 | 0.00 | 0.00 | 468.77 | 564.71 | 2023.51 | 371.53 | 0.00 | 141.12 | 4663.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 28-JUN-21:45 | 0.00 | 0.07 | 0.00 | -0.9 | 0.00 | 0.00 | 471.86 | 564.71 | 2023.51 | 391.35 | 0.00 | 354.33 | 6148.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 26-AUG-19:47 | 0.00 | 0.07 | 0.00 | -0.9 | 0.00 | 0.00 | 423.16 | 746.73 | 2338.18 | 355.48 | 0.00 | 354.27 | 5664.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 14-APR-17:47 | 0.00 | 0.07 | 0.00 | -1.1 | 0.00 | 0.00 | 262.55 | 500.54 | 2748.57 | 4847.45 | 0.00 | 666.90 | 3459.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 28-JUN-22:20 | 0.00 | 0.06 | 0.00 | -0.8 | 0.00 | 0.00 | 471.03 | 314.44 | 1714.26 | 139.29 | 0.00 | 278.40 | 5548.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 26-AUG-20:35 | 0.00 | 0.05 | 0.00 | -0.8 | 0.00 | 0.00 | 426.16 | 746.73 | 2186.10 | 68.83 | 0.00 | 215.58 | 4956.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 09-JUN-18:40 | 0.00 | 0.07 | 0.00 | -1.1 | 0.00 | 0.00 | 424.36 | 673.81 | 2654.19 | 4308.96 | 0.00 | 660.81 | 3789.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 16-JUL-18:32 | 0.00 | 0.05 | 0.00 | -0.6 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6596.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 19-JUN-18:45 | 0.00 | 1.53 | 0.00 | -15.3 | 0.00 | 0.00 | 7589.71 | 12128.50 | 47775.42 | 34135.42 | 0.00 | 12405.23 | 73821.50 | 0.00 | 0.00 | 0.00 | -23137.2 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 07-DEC-05:00 | -1808.5 | 0.00 | 5598.35 | 0.00 | 0.00 | 0.00 | 526.24 | 154.01 | 1036.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2187.0 | 0.00 | -1591.1 | -1728.0 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 25-MAR-05:55 | -1460.7 | 0.00 | 3829.95 | 0.00 | 0.00 | 0.00 | 530.89 | 320.86 | 1162.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -716.7 | 0.00 | -977.2 | -2689.8 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 07-DEC-05:00 | -1808.5 | 0.00 | 5625.67 | 0.00 | 0.00 | 0.00 | 526.24 | 154.01 | 1036.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2188.3 | 0.00 | -1591.1 | -1754.1 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 07-DEC-05:00 | -1808.5 | 0.00 | 5688.97 | 0.00 | 0.00 | 0.00 | 526.24 | 154.01 | 1036.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2183.3 | 0.00 | -1591.1 | -1822.3 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 25-MAR-05:55 | -1460.7 | 0.00 | 3933.65 | 0.00 | 0.00 | 0.00 | 531.12 | 320.86 | 1162.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -717.3 | 0.00 | -977.0 | -2793.3 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 07-DEC-05:00 | -1808.5 | 0.00 | 5740.39 | 0.00 | 0.00 | 0.00 | 526.24 | 154.01 | 1036.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2183.9 | 0.00 | -1591.1 | -1873.1 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 07-DEC-06:00 | -1801.7 | 0.00 | 4639.60 | 0.00 | 0.00 | 0.00 | 526.24 | 320.86 | 1158.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2192.1 | 0.00 | -693.2 | -1958.3 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 08-DEC-08:10 | -1388.8 | 0.00 | 3808.83 | 0.00 | 0.00 | 0.00 | 216.71 | 141.18 | 1612.72 | 425.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -319.6 | -4496.2 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 07-DEC-06:00 | -1801.7 | 0.00 | 4673.57 | 0.00 | 0.00 | 0.00 | 526.24 | 320.86 | 1158.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2197.2 | 0.00 | -693.2 | -1987.1 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 07-DEC-06:00 | -1801.7 | 0.00 | 4769.24 | 0.00 | 0.00 | 0.00 | 526.24 | 320.86 | 1158.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2184.3 | 0.00 | -693.2 | -2095.7 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 16-DEC-08:65 | -1509.3 | 0.00 | 4311.21 | 0.00 | 0.00 | 0.00 | 217.32 | 141.18 | 1643.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -622.9 | 0.00 | -347.0 | -3834.0 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 07-DEC-06:00 | -1801.6 | 0.00 | 4852.76 | 0.00 | 0.00 | 0.00 | 526.24 | 320.86 | 1158.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2188.4 | 0.00 | -693.2 | -2175.1 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 07-DEC-06:00 | -1800.5 | 0.00 | 6675.93 | 0.00 | 0.00 | 0.00 | 526.24 | 320.86 | 1158.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2174.1 | 0.00 | -1584.5 | -3122.5 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 07-DEC-06:00 | -1800.5 | 0.00 | 6520.51 | 0.00 | 0.00 | 0.00 | 526.24 | 320.86 | 1158.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2183.7 | 0.00 | -1584.5 | -2957.4 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 07-DEC-06:00 | -1800.5 | 0.00 | 6484.81 | 0.00 | 0.00 | 0.00 | 526.24 | 320.86 | 1158.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2176.4 | 0.00 | -1584.5 | -2929.0 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 07-DEC-06:00 | -1800.6 | 0.00 | 4787.14 | 0.00 | 0.00 | 0.00 | 526.24 | 320.86 | 1158.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -883.6 | 0.00 | -1395.3 | -2713.2 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 07-DEC-06:00 | -1800.7 | 0.00 | 4583.06 | 0.00 | 0.00 | 0.00 | 526.24 | 320.86 | 1158.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -891.6 | 0.00 | -1395.3 | -2501.1 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 07-DEC-06:00 | -1800.5 | 0.00 | 6628.45 | 0.00 | 0.00 | 0.00 | 526.24 | 320.86 | 1158.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2167.7 | 0.00 | -1584.5 | -3081.3 |
HEATEDBSMT | 07-DEC-05:10 | -1804.8 | 0.00 | 12095.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10290.6 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-DEC-06:00 | -34215.0 | 0.00 | 102684.49 | 0.00 | 0.00 | 0.00 | 9472.36 | 5775.48 | 20853.01 | 0.00 | 0.00 | 10367.47 | 0.00 | 0.00 | -31482.0 | 0.00 | -22018.9 | -61436.9 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 492.9591 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 492.9591 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 308.0754 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 308.0754 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 371.9986 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 371.9986 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 489.2311 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 489.2311 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 310.3030 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 310.3030 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 367.2134 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 367.2134 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 507.7019 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 507.7019 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 315.8382 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 315.8382 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 382.9842 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 382.9842 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 504.4058 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 504.4058 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 317.9500 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 317.9500 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 381.2487 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 381.2487 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 585.5633 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 585.5633 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 393.6587 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 393.6587 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 460.8215 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 460.8215 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 588.9043 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 588.9043 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 398.8306 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 398.8306 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 464.8531 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 464.8531 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNITHEATEDBSMT | 302.4152 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 302.4152 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 492.9591 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 492.9591 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 308.0754 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 308.0754 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 371.9986 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 371.9986 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 489.2311 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 489.2311 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 310.3030 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 310.3030 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 367.2134 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 367.2134 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 507.7019 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 507.7019 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 315.8382 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 315.8382 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 382.9842 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 382.9842 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 504.4058 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 504.4058 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 317.9500 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 317.9500 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 381.2487 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 381.2487 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 585.5633 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 585.5633 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 393.6587 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 393.6587 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 460.8215 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 460.8215 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 588.9043 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 588.9043 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 398.8306 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 398.8306 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 464.8531 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 464.8531 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNITHEATEDBSMT | 302.4152 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 302.4152 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 0.000000 | 0.0000 | 0.000000 | 7794.39 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.000000 | 7794.3864 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 492.9591 | 492.9591 | 492.9591 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 308.0754 | 308.0754 | 308.0754 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 371.9986 | 371.9986 | 371.9986 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 489.2311 | 489.2311 | 489.2311 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 310.3030 | 310.3030 | 310.3030 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 367.2134 | 367.2134 | 367.2134 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 507.7019 | 507.7019 | 507.7019 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 315.8382 | 315.8382 | 315.8382 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 382.9842 | 382.9842 | 382.9842 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 504.4058 | 504.4058 | 504.4058 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 317.9500 | 317.9500 | 317.9500 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 381.2487 | 381.2487 | 381.2487 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 464.8531 | 464.8531 | 464.8531 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 460.8215 | 460.8215 | 460.8215 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 585.5633 | 585.5633 | 585.5633 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 398.8306 | 398.8306 | 398.8306 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 393.6587 | 393.6587 | 393.6587 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 588.9043 | 588.9043 | 588.9043 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 302.4152 | 302.4152 | 302.4152 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 492.9591 | 492.9591 | 492.9591 | 492.9591 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 308.0754 | 308.0754 | 308.0754 | 308.0754 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 371.9986 | 371.9986 | 371.9986 | 371.9986 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 489.2311 | 489.2311 | 489.2311 | 489.2311 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 310.3030 | 310.3030 | 310.3030 | 310.3030 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 367.2134 | 367.2134 | 367.2134 | 367.2134 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 507.7019 | 507.7019 | 507.7019 | 507.7019 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 315.8382 | 315.8382 | 315.8382 | 315.8382 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 382.9842 | 382.9842 | 382.9842 | 382.9842 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 504.4058 | 504.4058 | 504.4058 | 504.4058 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 317.9500 | 317.9500 | 317.9500 | 317.9500 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 381.2487 | 381.2487 | 381.2487 | 381.2487 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 585.5633 | 585.5633 | 585.5633 | 585.5633 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 393.6587 | 393.6587 | 393.6587 | 393.6587 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 460.8215 | 460.8215 | 460.8215 | 460.8215 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 588.9043 | 588.9043 | 588.9043 | 588.9043 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 398.8306 | 398.8306 | 398.8306 | 398.8306 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 464.8531 | 464.8531 | 464.8531 | 464.8531 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 302.4152 | 302.4152 | 302.4152 | 302.4152 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 492.9591 | 492.9591 | 492.9591 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 308.0754 | 308.0754 | 308.0754 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 371.9986 | 371.9986 | 371.9986 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 489.2311 | 489.2311 | 489.2311 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 310.3030 | 310.3030 | 310.3030 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 367.2134 | 367.2134 | 367.2134 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 507.7019 | 507.7019 | 507.7019 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 315.8382 | 315.8382 | 315.8382 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 382.9842 | 382.9842 | 382.9842 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 504.4058 | 504.4058 | 504.4058 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 317.9500 | 317.9500 | 317.9500 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 381.2487 | 381.2487 | 381.2487 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 464.8531 | 464.8531 | 464.8531 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 460.8215 | 460.8215 | 460.8215 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 585.5633 | 585.5633 | 585.5633 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 398.8306 | 398.8306 | 398.8306 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 393.6587 | 393.6587 | 393.6587 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 588.9043 | 588.9043 | 588.9043 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 302.4152 | 302.4152 | 302.4152 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 492.9591 | 492.9591 | 492.9591 | 492.9591 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 308.0754 | 308.0754 | 308.0754 | 308.0754 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 371.9986 | 371.9986 | 371.9986 | 371.9986 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 489.2311 | 489.2311 | 489.2311 | 489.2311 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 310.3030 | 310.3030 | 310.3030 | 310.3030 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 367.2134 | 367.2134 | 367.2134 | 367.2134 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 507.7019 | 507.7019 | 507.7019 | 507.7019 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 315.8382 | 315.8382 | 315.8382 | 315.8382 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 382.9842 | 382.9842 | 382.9842 | 382.9842 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 504.4058 | 504.4058 | 504.4058 | 504.4058 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 317.9500 | 317.9500 | 317.9500 | 317.9500 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 381.2487 | 381.2487 | 381.2487 | 381.2487 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 585.5633 | 585.5633 | 585.5633 | 585.5633 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 393.6587 | 393.6587 | 393.6587 | 393.6587 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 460.8215 | 460.8215 | 460.8215 | 460.8215 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 588.9043 | 588.9043 | 588.9043 | 588.9043 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 398.8306 | 398.8306 | 398.8306 | 398.8306 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 464.8531 | 464.8531 | 464.8531 | 464.8531 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 302.4152 | 302.4152 | 302.4152 | 302.4152 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [ft2] | 39005.22 |
Principal Heating Source | Natural Gas |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
HEATEDBSMT | 7794.39 | 7794.39 | 0.00 | 0.00 |
BREEZEWAY | 1798.16 | 0.00 | 1798.16 | 0.00 |
ATTIC | 7802.71 | 0.00 | 7802.71 | 0.00 |
Totals | 39005.22 | 29404.35 | 9600.87 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 287.50 |
Number of hours not met | 287.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [kWh] | Electricity Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Gasoline Use [therm] | Gasoline Demand [Btu/h] | Diesel Use [kBtu] | Diesel Demand [Btu/h] | Coal Use [kBtu] | Coal Demand [Btu/h] | Fuel Oil No 1 Use [kBtu] | Fuel Oil No 1 Demand [Btu/h] | Fuel Oil No 2 Use [kBtu] | Fuel Oil No 2 Demand [Btu/h] | Propane Use [kBtu] | Propane Demand [Btu/h] | Other Fuel 1 Use [kBtu] | Other Fuel 1 Demand [Btu/h] | Other Fuel 2 Use [kBtu] | Other Fuel 2 Demand [Btu/h] | District Cooling Use [ton-hrs] | District Cooling Demand [ton] | District Heating Use [kBtu] | District Heating Demand [Btu/h] | |
Heating -- General | 0.00 | 0.00 | 508.02 | 116910.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 40526.04 | 16318.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- General | 12093.82 | 3939.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Exterior-Lights | 5508.71 | 1257.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- dishwasher | 2758.31 | 880.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- refrigerator | 12036.11 | 1639.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- clotheswasher | 1408.53 | 381.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- gas_dryer | 1138.84 | 291.20 | 792.69 | 20254.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- gas_range | 0.00 | 0.00 | 674.43 | 27685.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- gas_mels | 41935.01 | 7086.44 | 172.61 | 2914.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- IECC_adj | 17368.96 | 2935.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 9519.74 | 2996.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation | 5349.86 | 610.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 2053.27 | 169316.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 261700.64 | 510946.85 |
Natural Gas | 163973.19 | 420102.41 |
Additional | 0.00 | 0.00 |
Total | 425673.83 | 931049.26 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting (All) | 0.31 |
Space Heating | 0.00 |
Space Cooling | 1.04 |
Fans (All) | 0.38 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1.97 |
Miscellaneous (All) | 3.84 |
Subtotal | 3.84 |
Natural Gas [kWh/ft2] | |
Space Heating | 0.38 |
Service Water Heating | 1.54 |
Miscellaneous (All) | 3.15 |
Subtotal | 3.15 |
Additional [kBtu/ft2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 4.44 |
Space Heating | 5.46 |
Space Cooling | 14.86 |
Fans (All) | 5.45 |
Service Water Heating | 22.05 |
Receptacle Equipment | 45.72 |
Miscellaneous | 2.02 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OCCUPANCY | 6031. | 8760. |
INTERIORLIGHTING | 2852. | 8760. |
INTERIORLIGHTINGHE | 3070. | 8760. |
INTERIORLIGHTINGHE_OS | 2910. | 8760. |
INTERIORLIGHTINGHE_VS | 2149. | 8760. |
EXTERIORLIGHTING | 4380. | 4380. |
REFRIGERATOR | 7343. | 8760. |
MISCPLUGLOAD | 5918. | 8760. |
COOKINGRANGE | 2434. | 8760. |
DHW_SCH | 365. | 8760. |
DISHWASHER | 2799. | 8760. |
CLOTHESWASHER | 3297. | 8760. |
CLOTHESDRYER | 3911. | 8760. |
SINKS | 4179. | 8760. |
SHOWERS | 2640. | 8760. |
BATHS | 2586. | 8760. |
DHWDIST | 4662. | 8760. |
SHADING_2012IECC | 0. | 0. |
SINKSENSSCHEDULE | 6025. | 8760. |
SINKLATSCHEDULE | 2735. | 8760. |
SHOWERSENSSCHEDULE | 4492. | 8760. |
SHOWERLATSCHEDULE | 4268. | 8760. |
BATHSENSSCHEDULE | 8760. | 8760. |
BATHLATSCHEDULE | 0. | 0. |
First Object Used | Month Assumed | 11am First Wednesday [F] | Days with Same 11am Value | 11pm First Wednesday [F] | Days with Same 11pm Value | |
HEATING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | January | 72.00 | 365 | 72.00 | 365 |
COOLING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | July | 75.00 | 365 | 75.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 5596.00 | 1793.33 | 1302.67 | 68.00 | 0.00 |
ATTIC | 5793.67 | 1341.50 | 1009.00 | 615.83 | 0.00 |
Min | 5596.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1793.33 | 1302.67 | 615.83 | 0.00 |
Average | 8468.08 | 149.28 | 110.08 | 32.56 | 0.00 |
Sum | 177829.67 | 3134.83 | 2311.67 | 683.83 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 7821.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 164250.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8713.67 | 46.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8721.67 | 38.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8709.17 | 50.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8712.83 | 47.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8718.50 | 41.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8704.83 | 55.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8739.67 | 20.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8739.17 | 20.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8739.17 | 20.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8738.67 | 21.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8731.33 | 28.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8732.50 | 27.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8733.00 | 27.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8740.33 | 19.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8741.17 | 18.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8732.50 | 27.50 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 6491.17 | 2098.67 | 170.17 | 0.00 | 0.00 |
ATTIC | 6033.33 | 1878.50 | 535.67 | 273.83 | 38.67 |
Min | 6033.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2098.67 | 535.67 | 273.83 | 38.67 |
Average | 8497.75 | 213.76 | 33.61 | 13.04 | 1.84 |
Sum | 178452.67 | 4489.00 | 705.83 | 273.83 | 38.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 9067.83 | 57.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 9082.67 | 42.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9062.17 | 62.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9067.50 | 57.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 9080.67 | 44.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 9059.33 | 65.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9106.17 | 18.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9105.17 | 19.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9105.50 | 19.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9104.50 | 20.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 9095.67 | 29.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 9096.67 | 28.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 9097.67 | 27.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 9106.50 | 18.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 9107.17 | 17.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 9097.33 | 27.67 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 9125.00 | 65.67 | 0.00 | 0.00 | 0.00 |
Average | 7794.88 | 26.55 | 0.00 | 0.00 | 0.00 |
Sum | 163692.50 | 557.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (F) | SET ≤ 12.2°C OccupantHours (F) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (F) | SET > 30°C OccupantHours (F) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2021-05-12 10:19:39
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 332.011 | 18.482 | 194.036 | 11.669 | 30.151 |
February | 196.583 | 6.597 | 193.758 | 10.870 | 17.467 |
March | 316.514 | 13.914 | 167.385 | 10.430 | 24.344 |
April | 557.847 | 38.847 | 8.667 | 0.346 | 39.193 |
May | 713.844 | 53.069 | 0.000 | 0.000 | 53.069 |
June | 720.000 | 72.107 | 0.000 | 0.000 | 72.107 |
July | 744.000 | 73.731 | 0.000 | 0.000 | 73.731 |
August | 744.000 | 71.360 | 0.000 | 0.000 | 71.360 |
September | 719.833 | 61.603 | 0.000 | 0.000 | 61.603 |
October | 560.114 | 37.406 | 31.847 | 1.615 | 39.021 |
November | 347.425 | 17.509 | 131.217 | 7.918 | 25.428 |
December | 258.967 | 11.642 | 270.817 | 21.461 | 33.103 |
Annual Sum or Average | 6211.139 | 476.268 | 997.727 | 64.309 | 540.576 |
Minimum of Months | 196.583 | 6.597 | 0.000 | 0.000 | 17.467 |
Maximum of Months | 744.000 | 73.731 | 270.817 | 21.461 | 73.731 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 367.056 | 14.749 | 85.919 | 4.274 | 19.022 |
February | 226.053 | 5.161 | 81.889 | 3.844 | 9.005 |
March | 347.889 | 10.183 | 80.867 | 4.124 | 14.308 |
April | 605.203 | 28.708 | 1.639 | 0.058 | 28.766 |
May | 733.169 | 40.617 | 0.000 | 0.000 | 40.617 |
June | 720.000 | 54.548 | 0.000 | 0.000 | 54.548 |
July | 744.000 | 58.262 | 0.000 | 0.000 | 58.262 |
August | 744.000 | 56.896 | 0.000 | 0.000 | 56.896 |
September | 720.000 | 50.435 | 0.000 | 0.000 | 50.435 |
October | 606.369 | 31.245 | 6.256 | 0.257 | 31.502 |
November | 392.175 | 14.155 | 56.742 | 2.772 | 16.927 |
December | 292.978 | 9.551 | 161.139 | 9.483 | 19.034 |
Annual Sum or Average | 6498.892 | 374.508 | 474.451 | 24.813 | 399.321 |
Minimum of Months | 226.053 | 5.161 | 0.000 | 0.000 | 9.005 |
Maximum of Months | 744.000 | 58.262 | 161.139 | 9.483 | 58.262 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 362.166 | 15.521 | 169.650 | 8.245 | 23.766 |
February | 224.578 | 5.732 | 164.667 | 7.426 | 13.158 |
March | 355.319 | 11.968 | 139.908 | 7.064 | 19.031 |
April | 589.631 | 35.270 | 6.250 | 0.213 | 35.483 |
May | 718.222 | 48.892 | 0.000 | 0.000 | 48.892 |
June | 720.000 | 66.069 | 0.000 | 0.000 | 66.069 |
July | 744.000 | 68.344 | 0.000 | 0.000 | 68.344 |
August | 744.000 | 65.980 | 0.000 | 0.000 | 65.980 |
September | 719.833 | 56.392 | 0.000 | 0.000 | 56.392 |
October | 581.914 | 34.215 | 25.472 | 1.063 | 35.278 |
November | 373.246 | 14.617 | 112.250 | 5.473 | 20.090 |
December | 281.586 | 9.573 | 242.297 | 15.367 | 24.940 |
Annual Sum or Average | 6414.495 | 432.573 | 860.494 | 44.850 | 477.423 |
Minimum of Months | 224.578 | 5.732 | 0.000 | 0.000 | 13.158 |
Maximum of Months | 744.000 | 68.344 | 242.297 | 15.367 | 68.344 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 248.236 | 8.420 | 238.614 | 13.816 | 22.236 |
February | 118.806 | 2.252 | 237.081 | 13.008 | 15.260 |
March | 277.139 | 9.825 | 185.833 | 11.092 | 20.917 |
April | 553.636 | 34.709 | 8.411 | 0.336 | 35.045 |
May | 715.164 | 52.351 | 0.000 | 0.000 | 52.351 |
June | 720.000 | 72.949 | 0.000 | 0.000 | 72.949 |
July | 744.000 | 73.822 | 0.000 | 0.000 | 73.822 |
August | 744.000 | 69.435 | 0.000 | 0.000 | 69.435 |
September | 719.833 | 57.612 | 0.000 | 0.000 | 57.612 |
October | 534.169 | 29.360 | 39.092 | 1.886 | 31.246 |
November | 277.694 | 9.187 | 165.542 | 9.573 | 18.760 |
December | 152.750 | 3.621 | 335.081 | 25.552 | 29.172 |
Annual Sum or Average | 5805.428 | 423.543 | 1209.653 | 75.263 | 498.806 |
Minimum of Months | 118.806 | 2.252 | 0.000 | 0.000 | 15.260 |
Maximum of Months | 744.000 | 73.822 | 335.081 | 25.552 | 73.822 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 258.444 | 4.538 | 116.904 | 5.555 | 10.094 |
February | 98.028 | 0.953 | 119.925 | 5.197 | 6.150 |
March | 284.375 | 6.194 | 93.733 | 4.569 | 10.763 |
April | 601.511 | 24.821 | 1.556 | 0.056 | 24.878 |
May | 733.542 | 40.259 | 0.000 | 0.000 | 40.259 |
June | 720.000 | 55.843 | 0.000 | 0.000 | 55.843 |
July | 744.000 | 58.839 | 0.000 | 0.000 | 58.839 |
August | 744.000 | 55.600 | 0.000 | 0.000 | 55.600 |
September | 720.000 | 46.952 | 0.000 | 0.000 | 46.952 |
October | 577.444 | 23.343 | 8.475 | 0.344 | 23.687 |
November | 292.000 | 5.720 | 80.669 | 3.810 | 9.530 |
December | 134.528 | 1.719 | 220.519 | 12.353 | 14.072 |
Annual Sum or Average | 5907.872 | 324.783 | 641.781 | 31.885 | 356.668 |
Minimum of Months | 98.028 | 0.953 | 0.000 | 0.000 | 6.150 |
Maximum of Months | 744.000 | 58.839 | 220.519 | 12.353 | 58.839 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 288.253 | 5.620 | 188.342 | 9.099 | 14.719 |
February | 115.394 | 1.180 | 185.625 | 8.160 | 9.340 |
March | 317.850 | 8.191 | 144.478 | 7.212 | 15.403 |
April | 588.894 | 33.218 | 6.250 | 0.213 | 33.431 |
May | 719.361 | 50.792 | 0.000 | 0.000 | 50.792 |
June | 720.000 | 69.852 | 0.000 | 0.000 | 69.852 |
July | 744.000 | 71.830 | 0.000 | 0.000 | 71.830 |
August | 744.000 | 67.566 | 0.000 | 0.000 | 67.566 |
September | 719.833 | 55.717 | 0.000 | 0.000 | 55.717 |
October | 566.856 | 28.123 | 25.806 | 1.091 | 29.214 |
November | 298.042 | 6.627 | 129.153 | 6.170 | 12.797 |
December | 143.611 | 2.029 | 281.656 | 17.381 | 19.411 |
Annual Sum or Average | 5966.094 | 400.747 | 961.308 | 49.326 | 450.073 |
Minimum of Months | 115.394 | 1.180 | 0.000 | 0.000 | 9.340 |
Maximum of Months | 744.000 | 71.830 | 281.656 | 17.381 | 71.830 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 397.422 | 24.292 | 92.239 | 6.126 | 30.418 |
February | 257.958 | 10.442 | 94.744 | 5.772 | 16.214 |
March | 394.653 | 19.553 | 80.569 | 5.558 | 25.111 |
April | 640.794 | 47.751 | 1.381 | 0.063 | 47.815 |
May | 734.275 | 58.963 | 0.000 | 0.000 | 58.963 |
June | 720.000 | 76.952 | 0.000 | 0.000 | 76.952 |
July | 744.000 | 78.311 | 0.000 | 0.000 | 78.311 |
August | 744.000 | 76.331 | 0.000 | 0.000 | 76.331 |
September | 720.000 | 66.593 | 0.000 | 0.000 | 66.593 |
October | 596.533 | 42.028 | 13.050 | 0.799 | 42.827 |
November | 436.964 | 23.496 | 61.661 | 4.234 | 27.730 |
December | 318.125 | 15.985 | 177.492 | 14.540 | 30.525 |
Annual Sum or Average | 6704.725 | 540.697 | 521.136 | 37.094 | 577.790 |
Minimum of Months | 257.958 | 10.442 | 0.000 | 0.000 | 16.214 |
Maximum of Months | 744.000 | 78.311 | 177.492 | 14.540 | 78.311 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 458.453 | 21.379 | 14.558 | 0.759 | 22.138 |
February | 327.153 | 9.913 | 19.167 | 0.810 | 10.723 |
March | 463.167 | 16.498 | 20.611 | 1.055 | 17.553 |
April | 689.486 | 37.651 | 0.000 | 0.000 | 37.651 |
May | 744.000 | 45.905 | 0.000 | 0.000 | 45.905 |
June | 720.000 | 58.320 | 0.000 | 0.000 | 58.320 |
July | 744.000 | 62.158 | 0.000 | 0.000 | 62.158 |
August | 744.000 | 61.155 | 0.000 | 0.000 | 61.155 |
September | 720.000 | 54.926 | 0.000 | 0.000 | 54.926 |
October | 656.572 | 36.314 | 0.417 | 0.013 | 36.327 |
November | 509.167 | 21.227 | 11.236 | 0.615 | 21.842 |
December | 378.258 | 14.758 | 64.828 | 3.746 | 18.504 |
Annual Sum or Average | 7154.256 | 440.205 | 130.817 | 6.998 | 447.204 |
Minimum of Months | 327.153 | 9.913 | 0.000 | 0.000 | 10.723 |
Maximum of Months | 744.000 | 62.158 | 64.828 | 3.746 | 62.158 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 428.388 | 22.473 | 75.333 | 4.144 | 26.617 |
February | 289.925 | 10.400 | 76.125 | 3.749 | 14.149 |
March | 438.075 | 18.782 | 61.467 | 3.515 | 22.296 |
April | 657.794 | 46.452 | 0.917 | 0.036 | 46.488 |
May | 736.000 | 57.587 | 0.000 | 0.000 | 57.587 |
June | 720.000 | 74.000 | 0.000 | 0.000 | 74.000 |
July | 744.000 | 76.555 | 0.000 | 0.000 | 76.555 |
August | 744.000 | 74.057 | 0.000 | 0.000 | 74.057 |
September | 720.000 | 64.252 | 0.000 | 0.000 | 64.252 |
October | 617.556 | 40.950 | 10.250 | 0.490 | 41.439 |
November | 462.305 | 21.594 | 50.097 | 2.794 | 24.388 |
December | 348.289 | 14.734 | 152.683 | 10.128 | 24.862 |
Annual Sum or Average | 6906.333 | 521.836 | 426.872 | 24.855 | 546.691 |
Minimum of Months | 289.925 | 10.400 | 0.000 | 0.000 | 14.149 |
Maximum of Months | 744.000 | 76.555 | 152.683 | 10.128 | 76.555 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 316.250 | 12.046 | 134.539 | 8.209 | 20.255 |
February | 186.417 | 4.536 | 135.319 | 7.781 | 12.317 |
March | 355.292 | 14.578 | 95.975 | 6.166 | 20.745 |
April | 636.867 | 43.245 | 1.347 | 0.062 | 43.306 |
May | 734.658 | 58.180 | 0.000 | 0.000 | 58.180 |
June | 720.000 | 77.819 | 0.000 | 0.000 | 77.819 |
July | 744.000 | 78.341 | 0.000 | 0.000 | 78.341 |
August | 744.000 | 74.168 | 0.000 | 0.000 | 74.168 |
September | 720.000 | 62.221 | 0.000 | 0.000 | 62.221 |
October | 568.444 | 33.030 | 22.036 | 1.110 | 34.140 |
November | 368.167 | 13.397 | 93.256 | 5.876 | 19.273 |
December | 204.722 | 5.592 | 245.317 | 19.084 | 24.675 |
Annual Sum or Average | 6298.817 | 477.153 | 727.789 | 48.288 | 525.440 |
Minimum of Months | 186.417 | 4.536 | 0.000 | 0.000 | 12.317 |
Maximum of Months | 744.000 | 78.341 | 245.317 | 19.084 | 78.341 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 353.194 | 8.378 | 34.964 | 1.547 | 9.925 |
February | 218.058 | 3.474 | 39.083 | 1.583 | 5.057 |
March | 410.639 | 11.209 | 26.702 | 1.278 | 12.486 |
April | 688.528 | 33.064 | 0.000 | 0.000 | 33.064 |
May | 744.000 | 45.023 | 0.000 | 0.000 | 45.023 |
June | 720.000 | 59.114 | 0.000 | 0.000 | 59.114 |
July | 744.000 | 62.049 | 0.000 | 0.000 | 62.049 |
August | 744.000 | 59.031 | 0.000 | 0.000 | 59.031 |
September | 720.000 | 50.554 | 0.000 | 0.000 | 50.554 |
October | 628.056 | 27.043 | 1.669 | 0.051 | 27.094 |
November | 423.239 | 10.481 | 26.567 | 1.230 | 11.711 |
December | 210.250 | 3.733 | 113.106 | 6.010 | 9.743 |
Annual Sum or Average | 6603.964 | 373.153 | 242.091 | 11.699 | 384.852 |
Minimum of Months | 210.250 | 3.474 | 0.000 | 0.000 | 5.057 |
Maximum of Months | 744.000 | 62.049 | 113.106 | 6.010 | 62.049 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 364.939 | 9.675 | 96.025 | 5.100 | 14.774 |
February | 215.892 | 3.687 | 89.194 | 4.435 | 8.122 |
March | 410.508 | 13.558 | 66.058 | 3.716 | 17.274 |
April | 657.036 | 42.496 | 0.833 | 0.034 | 42.529 |
May | 736.167 | 57.154 | 0.000 | 0.000 | 57.154 |
June | 720.000 | 75.219 | 0.000 | 0.000 | 75.219 |
July | 744.000 | 77.039 | 0.000 | 0.000 | 77.039 |
August | 744.000 | 72.868 | 0.000 | 0.000 | 72.868 |
September | 720.000 | 60.734 | 0.000 | 0.000 | 60.734 |
October | 605.356 | 32.334 | 12.806 | 0.555 | 32.889 |
November | 405.533 | 11.119 | 63.403 | 3.508 | 14.627 |
December | 206.722 | 3.937 | 190.417 | 12.547 | 16.485 |
Annual Sum or Average | 6530.153 | 459.820 | 518.736 | 29.894 | 489.714 |
Minimum of Months | 206.722 | 3.687 | 0.000 | 0.000 | 8.122 |
Maximum of Months | 744.000 | 77.039 | 190.417 | 12.547 | 77.039 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 356.275 | 23.149 | 176.183 | 11.041 | 34.190 |
February | 218.917 | 9.148 | 185.011 | 10.735 | 19.882 |
March | 354.450 | 19.248 | 148.011 | 9.537 | 28.785 |
April | 610.814 | 51.676 | 4.617 | 0.186 | 51.863 |
May | 722.181 | 64.953 | 0.000 | 0.000 | 64.953 |
June | 720.000 | 87.507 | 0.000 | 0.000 | 87.507 |
July | 744.000 | 88.775 | 0.000 | 0.000 | 88.775 |
August | 744.000 | 85.523 | 0.000 | 0.000 | 85.523 |
September | 719.500 | 73.225 | 0.000 | 0.000 | 73.225 |
October | 560.825 | 43.106 | 43.625 | 2.216 | 45.322 |
November | 382.436 | 22.227 | 123.625 | 7.883 | 30.110 |
December | 279.275 | 14.316 | 256.961 | 22.148 | 36.464 |
Annual Sum or Average | 6412.672 | 582.854 | 938.033 | 63.746 | 646.600 |
Minimum of Months | 218.917 | 9.148 | 0.000 | 0.000 | 19.882 |
Maximum of Months | 744.000 | 88.775 | 256.961 | 22.148 | 88.775 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 402.700 | 20.165 | 71.633 | 3.722 | 23.887 |
February | 261.103 | 8.298 | 75.661 | 3.671 | 11.969 |
March | 396.972 | 16.079 | 70.931 | 3.682 | 19.760 |
April | 659.292 | 41.872 | 0.681 | 0.022 | 41.894 |
May | 738.125 | 52.429 | 0.000 | 0.000 | 52.429 |
June | 720.000 | 69.475 | 0.000 | 0.000 | 69.475 |
July | 744.000 | 73.340 | 0.000 | 0.000 | 73.340 |
August | 744.000 | 71.213 | 0.000 | 0.000 | 71.213 |
September | 720.000 | 62.424 | 0.000 | 0.000 | 62.424 |
October | 605.958 | 37.542 | 9.306 | 0.418 | 37.960 |
November | 448.008 | 19.829 | 50.414 | 2.727 | 22.556 |
December | 318.708 | 12.848 | 155.514 | 10.064 | 22.912 |
Annual Sum or Average | 6758.867 | 485.513 | 434.139 | 24.305 | 509.817 |
Minimum of Months | 261.103 | 8.298 | 0.000 | 0.000 | 11.969 |
Maximum of Months | 744.000 | 73.340 | 155.514 | 10.064 | 73.340 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 389.211 | 21.197 | 148.317 | 7.840 | 29.037 |
February | 250.742 | 8.794 | 152.931 | 7.384 | 16.177 |
March | 391.625 | 18.192 | 115.381 | 6.373 | 24.566 |
April | 636.189 | 50.589 | 2.917 | 0.112 | 50.701 |
May | 727.583 | 64.006 | 0.000 | 0.000 | 64.006 |
June | 720.000 | 85.120 | 0.000 | 0.000 | 85.120 |
July | 744.000 | 87.647 | 0.000 | 0.000 | 87.647 |
August | 744.000 | 84.192 | 0.000 | 0.000 | 84.192 |
September | 719.500 | 71.639 | 0.000 | 0.000 | 71.639 |
October | 586.278 | 42.212 | 32.250 | 1.417 | 43.629 |
November | 406.722 | 20.240 | 104.000 | 5.493 | 25.733 |
December | 299.106 | 12.842 | 228.075 | 16.176 | 29.017 |
Annual Sum or Average | 6614.956 | 566.669 | 783.869 | 44.795 | 611.464 |
Minimum of Months | 250.742 | 8.794 | 0.000 | 0.000 | 16.177 |
Maximum of Months | 744.000 | 87.647 | 228.075 | 16.176 | 87.647 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 290.667 | 13.294 | 219.733 | 13.718 | 27.012 |
February | 165.639 | 4.909 | 224.761 | 13.212 | 18.121 |
March | 331.139 | 16.242 | 162.542 | 10.286 | 26.528 |
April | 608.058 | 49.339 | 4.583 | 0.187 | 49.526 |
May | 723.528 | 64.760 | 0.000 | 0.000 | 64.760 |
June | 720.000 | 88.361 | 0.000 | 0.000 | 88.361 |
July | 744.000 | 89.040 | 0.000 | 0.000 | 89.040 |
August | 744.000 | 84.496 | 0.000 | 0.000 | 84.496 |
September | 719.500 | 70.644 | 0.000 | 0.000 | 70.644 |
October | 538.075 | 36.532 | 56.353 | 2.716 | 39.247 |
November | 325.333 | 14.228 | 158.406 | 9.982 | 24.211 |
December | 189.472 | 6.146 | 319.811 | 27.305 | 33.451 |
Annual Sum or Average | 6099.411 | 537.992 | 1146.189 | 77.406 | 615.397 |
Minimum of Months | 165.639 | 4.909 | 0.000 | 0.000 | 18.121 |
Maximum of Months | 744.000 | 89.040 | 319.811 | 27.305 | 89.040 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 319.750 | 9.567 | 115.019 | 5.527 | 15.094 |
February | 185.278 | 3.658 | 118.714 | 5.369 | 9.027 |
March | 363.386 | 12.894 | 81.350 | 4.139 | 17.033 |
April | 657.264 | 39.588 | 0.681 | 0.022 | 39.610 |
May | 738.347 | 52.340 | 0.000 | 0.000 | 52.340 |
June | 720.000 | 70.483 | 0.000 | 0.000 | 70.483 |
July | 744.000 | 73.771 | 0.000 | 0.000 | 73.771 |
August | 744.000 | 70.373 | 0.000 | 0.000 | 70.373 |
September | 720.000 | 59.975 | 0.000 | 0.000 | 59.975 |
October | 578.819 | 30.738 | 15.831 | 0.636 | 31.374 |
November | 375.194 | 11.205 | 80.864 | 4.094 | 15.299 |
December | 185.528 | 4.174 | 225.900 | 14.048 | 18.221 |
Annual Sum or Average | 6331.567 | 438.766 | 638.358 | 33.835 | 472.600 |
Minimum of Months | 185.278 | 3.658 | 0.000 | 0.000 | 9.027 |
Maximum of Months | 744.000 | 73.771 | 225.900 | 14.048 | 73.771 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 326.653 | 10.746 | 173.347 | 9.217 | 19.964 |
February | 183.161 | 4.010 | 176.675 | 8.503 | 12.513 |
March | 369.889 | 15.095 | 122.536 | 6.700 | 21.795 |
April | 635.300 | 48.672 | 3.083 | 0.115 | 48.787 |
May | 728.097 | 64.185 | 0.000 | 0.000 | 64.185 |
June | 720.000 | 86.403 | 0.000 | 0.000 | 86.403 |
July | 744.000 | 88.404 | 0.000 | 0.000 | 88.404 |
August | 744.000 | 83.755 | 0.000 | 0.000 | 83.755 |
September | 719.500 | 69.645 | 0.000 | 0.000 | 69.645 |
October | 568.186 | 35.817 | 34.267 | 1.539 | 37.356 |
November | 351.453 | 11.822 | 123.489 | 6.586 | 18.409 |
December | 184.750 | 4.417 | 277.178 | 19.340 | 23.757 |
Annual Sum or Average | 6274.989 | 522.971 | 910.575 | 52.001 | 574.972 |
Minimum of Months | 183.161 | 4.010 | 0.000 | 0.000 | 12.513 |
Maximum of Months | 744.000 | 88.404 | 277.178 | 19.340 | 88.404 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNITHEATEDBSMT
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 699.139 | 30.144 | 30.144 |
February | 0.000 | 0.000 | 672.000 | 38.838 | 38.838 |
March | 0.000 | 0.000 | 725.625 | 31.310 | 31.310 |
April | 0.000 | 0.000 | 272.653 | 4.507 | 4.507 |
May | 501.578 | 18.360 | 0.167 | 0.000 | 18.360 |
June | 720.000 | 56.038 | 0.000 | 0.000 | 56.038 |
July | 744.000 | 56.131 | 0.000 | 0.000 | 56.131 |
August | 744.000 | 52.936 | 0.000 | 0.000 | 52.936 |
September | 716.833 | 37.149 | 0.000 | 0.000 | 37.149 |
October | 332.186 | 10.031 | 0.000 | 0.000 | 10.031 |
November | 0.000 | 0.000 | 554.139 | 16.361 | 16.361 |
December | 0.000 | 0.000 | 742.667 | 42.528 | 42.528 |
Annual Sum or Average | 3758.597 | 230.645 | 3666.389 | 163.687 | 394.332 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 4.507 |
Maximum of Months | 744.000 | 56.131 | 742.667 | 42.528 | 56.131 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 449.36 | 0.00 | 0.00 |
February | 463.43 | 0.00 | 0.00 |
March | 401.64 | 0.00 | 0.00 |
April | 13.75 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 62.19 | 0.00 | 0.00 |
November | 315.09 | 0.00 | 0.00 |
December | 826.45 | 0.00 | 0.00 |
Annual Sum or Average | 210.33 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 826.45 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 194.78 | 0.00 | 0.00 |
February | 193.98 | 0.00 | 0.00 |
March | 187.96 | 0.00 | 0.00 |
April | 2.73 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 11.72 | 0.00 | 0.00 |
November | 130.57 | 0.00 | 0.00 |
December | 432.18 | 0.00 | 0.00 |
Annual Sum or Average | 96.05 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 432.18 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 420.74 | 0.00 | 0.00 |
February | 419.54 | 0.00 | 0.00 |
March | 360.45 | 0.00 | 0.00 |
April | 11.23 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 54.22 | 0.00 | 0.00 |
November | 288.62 | 0.00 | 0.00 |
December | 784.15 | 0.00 | 0.00 |
Annual Sum or Average | 194.38 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 784.15 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 536.19 | 0.00 | 0.00 |
February | 558.93 | 0.00 | 0.00 |
March | 430.49 | 0.00 | 0.00 |
April | 13.49 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 73.20 | 0.00 | 0.00 |
November | 383.89 | 0.00 | 0.00 |
December | 991.66 | 0.00 | 0.00 |
Annual Sum or Average | 248.08 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 991.66 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 251.37 | 0.00 | 0.00 |
February | 260.37 | 0.00 | 0.00 |
March | 206.73 | 0.00 | 0.00 |
April | 2.64 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 15.58 | 0.00 | 0.00 |
November | 178.12 | 0.00 | 0.00 |
December | 558.95 | 0.00 | 0.00 |
Annual Sum or Average | 122.53 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 558.95 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 469.98 | 0.00 | 0.00 |
February | 466.69 | 0.00 | 0.00 |
March | 372.51 | 0.00 | 0.00 |
April | 11.36 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 56.35 | 0.00 | 0.00 |
November | 329.33 | 0.00 | 0.00 |
December | 897.81 | 0.00 | 0.00 |
Annual Sum or Average | 216.39 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 897.81 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 203.88 | 0.00 | 0.00 |
February | 212.69 | 0.00 | 0.00 |
March | 184.98 | 0.00 | 0.00 |
April | 2.18 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 26.59 | 0.00 | 0.00 |
November | 145.62 | 0.00 | 0.00 |
December | 483.90 | 0.00 | 0.00 |
Annual Sum or Average | 104.85 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 483.90 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 33.75 | 0.00 | 0.00 |
February | 39.87 | 0.00 | 0.00 |
March | 46.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.58 | 0.00 | 0.00 |
November | 28.25 | 0.00 | 0.00 |
December | 166.53 | 0.00 | 0.00 |
Annual Sum or Average | 26.42 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 166.53 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 182.88 | 0.00 | 0.00 |
February | 183.18 | 0.00 | 0.00 |
March | 155.11 | 0.00 | 0.00 |
April | 1.65 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 21.61 | 0.00 | 0.00 |
November | 127.42 | 0.00 | 0.00 |
December | 446.97 | 0.00 | 0.00 |
Annual Sum or Average | 93.16 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 446.97 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 275.10 | 0.00 | 0.00 |
February | 288.71 | 0.00 | 0.00 |
March | 206.64 | 0.00 | 0.00 |
April | 2.13 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 37.20 | 0.00 | 0.00 |
November | 203.47 | 0.00 | 0.00 |
December | 639.52 | 0.00 | 0.00 |
Annual Sum or Average | 137.44 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 639.52 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 68.30 | 0.00 | 0.00 |
February | 77.39 | 0.00 | 0.00 |
March | 56.42 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 2.27 | 0.00 | 0.00 |
November | 56.15 | 0.00 | 0.00 |
December | 265.40 | 0.00 | 0.00 |
Annual Sum or Average | 43.88 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 265.40 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 225.92 | 0.00 | 0.00 |
February | 217.52 | 0.00 | 0.00 |
March | 164.62 | 0.00 | 0.00 |
April | 1.54 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 24.57 | 0.00 | 0.00 |
November | 160.60 | 0.00 | 0.00 |
December | 555.88 | 0.00 | 0.00 |
Annual Sum or Average | 112.48 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 555.88 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 434.95 | 0.00 | 0.00 |
February | 468.18 | 0.00 | 0.00 |
March | 375.69 | 0.00 | 0.00 |
April | 7.59 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 87.29 | 0.00 | 0.00 |
November | 320.88 | 0.00 | 0.00 |
December | 872.51 | 0.00 | 0.00 |
Annual Sum or Average | 213.28 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 872.51 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 162.99 | 0.00 | 0.00 |
February | 178.01 | 0.00 | 0.00 |
March | 161.23 | 0.00 | 0.00 |
April | 1.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 18.29 | 0.00 | 0.00 |
November | 123.40 | 0.00 | 0.00 |
December | 440.73 | 0.00 | 0.00 |
Annual Sum or Average | 90.40 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 440.73 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 392.58 | 0.00 | 0.00 |
February | 409.34 | 0.00 | 0.00 |
March | 319.14 | 0.00 | 0.00 |
April | 5.78 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 70.96 | 0.00 | 0.00 |
November | 284.22 | 0.00 | 0.00 |
December | 809.96 | 0.00 | 0.00 |
Annual Sum or Average | 190.50 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 809.96 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 537.48 | 0.00 | 0.00 |
February | 573.12 | 0.00 | 0.00 |
March | 403.01 | 0.00 | 0.00 |
April | 7.57 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 106.40 | 0.00 | 0.00 |
November | 404.16 | 0.00 | 0.00 |
December | 1069.84 | 0.00 | 0.00 |
Annual Sum or Average | 257.58 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1069.84 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 238.93 | 0.00 | 0.00 |
February | 256.92 | 0.00 | 0.00 |
March | 178.92 | 0.00 | 0.00 |
April | 0.97 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 27.49 | 0.00 | 0.00 |
November | 182.87 | 0.00 | 0.00 |
December | 607.22 | 0.00 | 0.00 |
Annual Sum or Average | 124.21 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 607.22 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 457.39 | 0.00 | 0.00 |
February | 467.14 | 0.00 | 0.00 |
March | 332.49 | 0.00 | 0.00 |
April | 5.89 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 76.39 | 0.00 | 0.00 |
November | 337.72 | 0.00 | 0.00 |
December | 959.69 | 0.00 | 0.00 |
Annual Sum or Average | 219.16 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 959.69 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNITHEATEDBSMT
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 4195.62 | 0.00 | 0.00 |
February | 5984.91 | 0.00 | 0.00 |
March | 4357.92 | 0.00 | 0.00 |
April | 648.17 | 0.00 | 0.00 |
May | 0.04 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 2353.17 | 0.00 | 0.00 |
December | 5919.45 | 0.00 | 0.00 |
Annual Sum or Average | 1935.02 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5984.91 | 0.00 | 0.00 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.13 |
February | 0.00 | 0.00 | 0.05 |
March | 0.00 | 0.00 | 0.10 |
April | 0.00 | 0.00 | 0.28 |
May | 0.00 | 0.00 | 0.37 |
June | 0.00 | 0.00 | 0.51 |
July | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.00 | 0.46 |
October | 0.00 | 0.00 | 0.27 |
November | 0.00 | 0.00 | 0.13 |
December | 0.00 | 0.00 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.53 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.11 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.21 |
May | 0.00 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.00 | 0.40 |
October | 0.00 | 0.00 | 0.23 |
November | 0.00 | 0.00 | 0.11 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.24 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.44 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.05 |
March | 0.00 | 0.00 | 0.09 |
April | 0.00 | 0.00 | 0.28 |
May | 0.00 | 0.00 | 0.37 |
June | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.00 | 0.52 |
September | 0.00 | 0.00 | 0.47 |
October | 0.00 | 0.00 | 0.27 |
November | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.54 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.02 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.25 |
May | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.00 | 0.52 |
August | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.00 | 0.42 |
October | 0.00 | 0.00 | 0.21 |
November | 0.00 | 0.00 | 0.07 |
December | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.25 |
Minimum of Months | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.00 | 0.00 | 0.52 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.03 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.18 |
May | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.00 | 0.36 |
October | 0.00 | 0.00 | 0.17 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.20 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.44 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.24 |
May | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.00 | 0.43 |
October | 0.00 | 0.00 | 0.20 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.25 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.54 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.18 |
February | 0.00 | 0.00 | 0.09 |
March | 0.00 | 0.00 | 0.14 |
April | 0.00 | 0.00 | 0.35 |
May | 0.00 | 0.00 | 0.41 |
June | 0.00 | 0.00 | 0.54 |
July | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.00 | 0.49 |
October | 0.00 | 0.00 | 0.30 |
November | 0.00 | 0.00 | 0.18 |
December | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.00 | 0.09 |
Maximum of Months | 0.00 | 0.00 | 0.55 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.16 |
February | 0.00 | 0.00 | 0.08 |
March | 0.00 | 0.00 | 0.12 |
April | 0.00 | 0.00 | 0.28 |
May | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.00 | 0.42 |
October | 0.00 | 0.00 | 0.27 |
November | 0.00 | 0.00 | 0.17 |
December | 0.00 | 0.00 | 0.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.27 |
Minimum of Months | 0.00 | 0.00 | 0.08 |
Maximum of Months | 0.00 | 0.00 | 0.46 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.17 |
February | 0.00 | 0.00 | 0.09 |
March | 0.00 | 0.00 | 0.14 |
April | 0.00 | 0.00 | 0.35 |
May | 0.00 | 0.00 | 0.41 |
June | 0.00 | 0.00 | 0.55 |
July | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.00 | 0.55 |
September | 0.00 | 0.00 | 0.50 |
October | 0.00 | 0.00 | 0.30 |
November | 0.00 | 0.00 | 0.17 |
December | 0.00 | 0.00 | 0.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.09 |
Maximum of Months | 0.00 | 0.00 | 0.57 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.08 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.10 |
April | 0.00 | 0.00 | 0.31 |
May | 0.00 | 0.00 | 0.40 |
June | 0.00 | 0.00 | 0.55 |
July | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.00 | 0.52 |
September | 0.00 | 0.00 | 0.46 |
October | 0.00 | 0.00 | 0.23 |
November | 0.00 | 0.00 | 0.10 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.55 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.08 |
April | 0.00 | 0.00 | 0.24 |
May | 0.00 | 0.00 | 0.32 |
June | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.00 | 0.39 |
October | 0.00 | 0.00 | 0.19 |
November | 0.00 | 0.00 | 0.08 |
December | 0.00 | 0.00 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.23 |
Minimum of Months | 0.00 | 0.00 | 0.03 |
Maximum of Months | 0.00 | 0.00 | 0.46 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.10 |
April | 0.00 | 0.00 | 0.31 |
May | 0.00 | 0.00 | 0.41 |
June | 0.00 | 0.00 | 0.55 |
July | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.00 | 0.46 |
October | 0.00 | 0.00 | 0.23 |
November | 0.00 | 0.00 | 0.08 |
December | 0.00 | 0.00 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 0.00 | 0.03 |
Maximum of Months | 0.00 | 0.00 | 0.57 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.16 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.14 |
April | 0.00 | 0.00 | 0.37 |
May | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.00 | 0.62 |
August | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.00 | 0.53 |
October | 0.00 | 0.00 | 0.30 |
November | 0.00 | 0.00 | 0.16 |
December | 0.00 | 0.00 | 0.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.07 |
Maximum of Months | 0.00 | 0.00 | 0.62 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.14 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.11 |
April | 0.00 | 0.00 | 0.30 |
May | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.00 | 0.47 |
October | 0.00 | 0.00 | 0.27 |
November | 0.00 | 0.00 | 0.15 |
December | 0.00 | 0.00 | 0.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.07 |
Maximum of Months | 0.00 | 0.00 | 0.53 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.15 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.13 |
April | 0.00 | 0.00 | 0.37 |
May | 0.00 | 0.00 | 0.45 |
June | 0.00 | 0.00 | 0.62 |
July | 0.00 | 0.00 | 0.64 |
August | 0.00 | 0.00 | 0.61 |
September | 0.00 | 0.00 | 0.54 |
October | 0.00 | 0.00 | 0.30 |
November | 0.00 | 0.00 | 0.15 |
December | 0.00 | 0.00 | 0.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.07 |
Maximum of Months | 0.00 | 0.00 | 0.64 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.09 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.11 |
April | 0.00 | 0.00 | 0.35 |
May | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.00 | 0.62 |
July | 0.00 | 0.00 | 0.62 |
August | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.00 | 0.51 |
October | 0.00 | 0.00 | 0.25 |
November | 0.00 | 0.00 | 0.10 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.62 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.09 |
April | 0.00 | 0.00 | 0.28 |
May | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.00 | 0.50 |
July | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.00 | 0.45 |
October | 0.00 | 0.00 | 0.22 |
November | 0.00 | 0.00 | 0.08 |
December | 0.00 | 0.00 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.26 |
Minimum of Months | 0.00 | 0.00 | 0.03 |
Maximum of Months | 0.00 | 0.00 | 0.53 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.11 |
April | 0.00 | 0.00 | 0.35 |
May | 0.00 | 0.00 | 0.45 |
June | 0.00 | 0.00 | 0.62 |
July | 0.00 | 0.00 | 0.64 |
August | 0.00 | 0.00 | 0.61 |
September | 0.00 | 0.00 | 0.52 |
October | 0.00 | 0.00 | 0.25 |
November | 0.00 | 0.00 | 0.09 |
December | 0.00 | 0.00 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.00 | 0.03 |
Maximum of Months | 0.00 | 0.00 | 0.64 |
Report: COILLOADS
For: DX COOLING COIL_UNITHEATEDBSMT
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.13 |
June | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.00 | 0.40 |
September | 0.00 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.07 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.43 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1249.37 | 930.19 |
February | 0.00 | 0.00 | 1241.34 | 834.77 |
March | 0.00 | 0.00 | 1176.65 | 876.05 |
April | 0.00 | 0.00 | 1070.27 | 771.14 |
May | 0.00 | 0.00 | 961.07 | 715.55 |
June | 0.00 | 0.00 | 875.07 | 630.50 |
July | 0.00 | 0.00 | 835.91 | 622.36 |
August | 0.00 | 0.00 | 847.63 | 631.08 |
September | 0.00 | 0.00 | 910.07 | 655.72 |
October | 0.00 | 0.00 | 1012.12 | 753.55 |
November | 0.00 | 0.00 | 1124.78 | 810.41 |
December | 0.00 | 0.00 | 1212.96 | 903.08 |
Annual Sum or Average | 0.00 | 0.00 | 1042.00 | 9134.40 |
Minimum of Months | 0.00 | 0.00 | 835.91 | 622.36 |
Maximum of Months | 0.00 | 0.00 | 1249.37 | 930.19 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1247.67 | 928.92 |
February | 0.00 | 0.00 | 1239.40 | 833.47 |
March | 0.00 | 0.00 | 1173.22 | 873.49 |
April | 0.00 | 0.00 | 1068.34 | 769.75 |
May | 0.00 | 0.00 | 961.00 | 715.49 |
June | 0.00 | 0.00 | 875.11 | 630.52 |
July | 0.00 | 0.00 | 835.93 | 622.37 |
August | 0.00 | 0.00 | 846.07 | 629.92 |
September | 0.00 | 0.00 | 911.72 | 656.91 |
October | 0.00 | 0.00 | 1010.34 | 752.23 |
November | 0.00 | 0.00 | 1119.62 | 806.70 |
December | 0.00 | 0.00 | 1212.85 | 903.00 |
Annual Sum or Average | 0.00 | 0.00 | 1040.68 | 9122.78 |
Minimum of Months | 0.00 | 0.00 | 835.93 | 622.37 |
Maximum of Months | 0.00 | 0.00 | 1247.67 | 928.92 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1247.56 | 928.85 |
February | 0.00 | 0.00 | 1241.28 | 834.73 |
March | 0.00 | 0.00 | 1173.26 | 873.52 |
April | 0.00 | 0.00 | 1070.02 | 770.96 |
May | 0.00 | 0.00 | 961.07 | 715.55 |
June | 0.00 | 0.00 | 876.81 | 631.75 |
July | 0.00 | 0.00 | 835.92 | 622.37 |
August | 0.00 | 0.00 | 846.05 | 629.91 |
September | 0.00 | 0.00 | 911.74 | 656.92 |
October | 0.00 | 0.00 | 1012.02 | 753.48 |
November | 0.00 | 0.00 | 1121.47 | 808.03 |
December | 0.00 | 0.00 | 1213.03 | 903.13 |
Annual Sum or Average | 0.00 | 0.00 | 1041.41 | 9129.19 |
Minimum of Months | 0.00 | 0.00 | 835.92 | 622.37 |
Maximum of Months | 0.00 | 0.00 | 1247.56 | 928.85 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1253.02 | 932.91 |
February | 0.00 | 0.00 | 1245.37 | 837.48 |
March | 0.00 | 0.00 | 1176.75 | 876.12 |
April | 0.00 | 0.00 | 1070.03 | 770.97 |
May | 0.00 | 0.00 | 961.08 | 715.55 |
June | 0.00 | 0.00 | 876.77 | 631.73 |
July | 0.00 | 0.00 | 835.91 | 622.36 |
August | 0.00 | 0.00 | 846.06 | 629.92 |
September | 0.00 | 0.00 | 911.73 | 656.91 |
October | 0.00 | 0.00 | 1012.22 | 753.62 |
November | 0.00 | 0.00 | 1126.64 | 811.76 |
December | 0.00 | 0.00 | 1218.13 | 906.93 |
Annual Sum or Average | 0.00 | 0.00 | 1043.35 | 9146.26 |
Minimum of Months | 0.00 | 0.00 | 835.91 | 622.36 |
Maximum of Months | 0.00 | 0.00 | 1253.02 | 932.91 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1251.23 | 931.58 |
February | 0.00 | 0.00 | 1243.49 | 836.22 |
March | 0.00 | 0.00 | 1175.07 | 874.87 |
April | 0.00 | 0.00 | 1070.08 | 771.00 |
May | 0.00 | 0.00 | 959.50 | 714.38 |
June | 0.00 | 0.00 | 876.80 | 631.75 |
July | 0.00 | 0.00 | 835.93 | 622.37 |
August | 0.00 | 0.00 | 846.02 | 629.89 |
September | 0.00 | 0.00 | 911.72 | 656.91 |
October | 0.00 | 0.00 | 1010.41 | 752.28 |
November | 0.00 | 0.00 | 1124.84 | 810.46 |
December | 0.00 | 0.00 | 1218.23 | 907.00 |
Annual Sum or Average | 0.00 | 0.00 | 1042.49 | 9138.70 |
Minimum of Months | 0.00 | 0.00 | 835.93 | 622.37 |
Maximum of Months | 0.00 | 0.00 | 1251.23 | 931.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1249.87 | 930.57 |
February | 0.00 | 0.00 | 1244.84 | 837.12 |
March | 0.00 | 0.00 | 1174.85 | 874.71 |
April | 0.00 | 0.00 | 1068.48 | 769.85 |
May | 0.00 | 0.00 | 961.09 | 715.56 |
June | 0.00 | 0.00 | 876.78 | 631.73 |
July | 0.00 | 0.00 | 835.91 | 622.36 |
August | 0.00 | 0.00 | 846.04 | 629.90 |
September | 0.00 | 0.00 | 911.71 | 656.90 |
October | 0.00 | 0.00 | 1011.55 | 753.13 |
November | 0.00 | 0.00 | 1123.84 | 809.74 |
December | 0.00 | 0.00 | 1218.05 | 906.87 |
Annual Sum or Average | 0.00 | 0.00 | 1042.46 | 9138.43 |
Minimum of Months | 0.00 | 0.00 | 835.91 | 622.36 |
Maximum of Months | 0.00 | 0.00 | 1249.87 | 930.57 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1245.77 | 927.51 |
February | 0.00 | 0.00 | 1237.58 | 832.24 |
March | 0.00 | 0.00 | 1171.66 | 872.33 |
April | 0.00 | 0.00 | 1068.41 | 769.80 |
May | 0.00 | 0.00 | 959.51 | 714.38 |
June | 0.00 | 0.00 | 876.79 | 631.74 |
July | 0.00 | 0.00 | 835.89 | 622.35 |
August | 0.00 | 0.00 | 846.08 | 629.93 |
September | 0.00 | 0.00 | 911.75 | 656.93 |
October | 0.00 | 0.00 | 1010.46 | 752.31 |
November | 0.00 | 0.00 | 1119.76 | 806.80 |
December | 0.00 | 0.00 | 1211.29 | 901.84 |
Annual Sum or Average | 0.00 | 0.00 | 1040.15 | 9118.16 |
Minimum of Months | 0.00 | 0.00 | 835.89 | 622.35 |
Maximum of Months | 0.00 | 0.00 | 1245.77 | 927.51 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1240.89 | 923.88 |
February | 0.00 | 0.00 | 1231.97 | 828.47 |
March | 0.00 | 0.00 | 1168.23 | 869.78 |
April | 0.00 | 0.00 | 1066.56 | 768.47 |
May | 0.00 | 0.00 | 961.02 | 715.51 |
June | 0.00 | 0.00 | 875.12 | 630.53 |
July | 0.00 | 0.00 | 837.53 | 623.56 |
August | 0.00 | 0.00 | 845.98 | 629.86 |
September | 0.00 | 0.00 | 910.00 | 655.66 |
October | 0.00 | 0.00 | 1008.74 | 751.03 |
November | 0.00 | 0.00 | 1116.14 | 804.19 |
December | 0.00 | 0.00 | 1206.30 | 898.12 |
Annual Sum or Average | 0.00 | 0.00 | 1037.97 | 9099.07 |
Minimum of Months | 0.00 | 0.00 | 837.53 | 623.56 |
Maximum of Months | 0.00 | 0.00 | 1240.89 | 923.88 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1244.31 | 926.42 |
February | 0.00 | 0.00 | 1235.61 | 830.92 |
March | 0.00 | 0.00 | 1169.82 | 870.96 |
April | 0.00 | 0.00 | 1068.40 | 769.79 |
May | 0.00 | 0.00 | 961.03 | 715.51 |
June | 0.00 | 0.00 | 875.10 | 630.52 |
July | 0.00 | 0.00 | 835.90 | 622.35 |
August | 0.00 | 0.00 | 845.97 | 629.85 |
September | 0.00 | 0.00 | 910.04 | 655.69 |
October | 0.00 | 0.00 | 1010.43 | 752.29 |
November | 0.00 | 0.00 | 1117.92 | 805.47 |
December | 0.00 | 0.00 | 1209.70 | 900.65 |
Annual Sum or Average | 0.00 | 0.00 | 1039.27 | 9110.44 |
Minimum of Months | 0.00 | 0.00 | 835.90 | 622.35 |
Maximum of Months | 0.00 | 0.00 | 1244.31 | 926.42 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1249.52 | 930.30 |
February | 0.00 | 0.00 | 1239.69 | 833.66 |
March | 0.00 | 0.00 | 1173.33 | 873.58 |
April | 0.00 | 0.00 | 1068.38 | 769.78 |
May | 0.00 | 0.00 | 961.01 | 715.50 |
June | 0.00 | 0.00 | 875.07 | 630.50 |
July | 0.00 | 0.00 | 835.93 | 622.37 |
August | 0.00 | 0.00 | 847.66 | 631.11 |
September | 0.00 | 0.00 | 910.07 | 655.72 |
October | 0.00 | 0.00 | 1012.10 | 753.54 |
November | 0.00 | 0.00 | 1121.50 | 808.05 |
December | 0.00 | 0.00 | 1216.39 | 905.64 |
Annual Sum or Average | 0.00 | 0.00 | 1041.47 | 9129.75 |
Minimum of Months | 0.00 | 0.00 | 835.93 | 622.37 |
Maximum of Months | 0.00 | 0.00 | 1249.52 | 930.30 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1245.60 | 927.38 |
February | 0.00 | 0.00 | 1236.33 | 831.40 |
March | 0.00 | 0.00 | 1168.44 | 869.94 |
April | 0.00 | 0.00 | 1066.61 | 768.51 |
May | 0.00 | 0.00 | 961.09 | 715.56 |
June | 0.00 | 0.00 | 876.82 | 631.76 |
July | 0.00 | 0.00 | 835.89 | 622.34 |
August | 0.00 | 0.00 | 846.03 | 629.89 |
September | 0.00 | 0.00 | 911.75 | 656.93 |
October | 0.00 | 0.00 | 1008.80 | 751.08 |
November | 0.00 | 0.00 | 1119.72 | 806.77 |
December | 0.00 | 0.00 | 1213.12 | 903.20 |
Annual Sum or Average | 0.00 | 0.00 | 1039.76 | 9114.75 |
Minimum of Months | 0.00 | 0.00 | 835.89 | 622.34 |
Maximum of Months | 0.00 | 0.00 | 1245.60 | 927.38 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1246.02 | 927.70 |
February | 0.00 | 0.00 | 1239.38 | 833.46 |
March | 0.00 | 0.00 | 1169.90 | 871.03 |
April | 0.00 | 0.00 | 1068.26 | 769.70 |
May | 0.00 | 0.00 | 959.67 | 714.50 |
June | 0.00 | 0.00 | 875.09 | 630.51 |
July | 0.00 | 0.00 | 835.90 | 622.35 |
August | 0.00 | 0.00 | 847.67 | 631.12 |
September | 0.00 | 0.00 | 911.74 | 656.92 |
October | 0.00 | 0.00 | 1010.38 | 752.26 |
November | 0.00 | 0.00 | 1119.73 | 806.77 |
December | 0.00 | 0.00 | 1214.60 | 904.30 |
Annual Sum or Average | 0.00 | 0.00 | 1040.43 | 9120.60 |
Minimum of Months | 0.00 | 0.00 | 835.90 | 622.35 |
Maximum of Months | 0.00 | 0.00 | 1246.02 | 927.70 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1247.63 | 928.89 |
February | 0.00 | 0.00 | 1241.51 | 834.88 |
March | 0.00 | 0.00 | 1173.31 | 873.56 |
April | 0.00 | 0.00 | 1068.32 | 769.74 |
May | 0.00 | 0.00 | 961.02 | 715.50 |
June | 0.00 | 0.00 | 875.14 | 630.55 |
July | 0.00 | 0.00 | 837.50 | 623.54 |
August | 0.00 | 0.00 | 846.03 | 629.90 |
September | 0.00 | 0.00 | 911.74 | 656.92 |
October | 0.00 | 0.00 | 1012.15 | 753.57 |
November | 0.00 | 0.00 | 1121.42 | 808.00 |
December | 0.00 | 0.00 | 1213.02 | 903.13 |
Annual Sum or Average | 0.00 | 0.00 | 1041.29 | 9128.18 |
Minimum of Months | 0.00 | 0.00 | 837.50 | 623.54 |
Maximum of Months | 0.00 | 0.00 | 1247.63 | 928.89 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1244.51 | 926.57 |
February | 0.00 | 0.00 | 1237.74 | 832.35 |
March | 0.00 | 0.00 | 1169.95 | 871.06 |
April | 0.00 | 0.00 | 1068.41 | 769.80 |
May | 0.00 | 0.00 | 961.00 | 715.49 |
June | 0.00 | 0.00 | 875.09 | 630.51 |
July | 0.00 | 0.00 | 835.88 | 622.33 |
August | 0.00 | 0.00 | 846.01 | 629.88 |
September | 0.00 | 0.00 | 911.74 | 656.92 |
October | 0.00 | 0.00 | 1010.32 | 752.21 |
November | 0.00 | 0.00 | 1117.91 | 805.46 |
December | 0.00 | 0.00 | 1211.38 | 901.91 |
Annual Sum or Average | 0.00 | 0.00 | 1039.73 | 9114.50 |
Minimum of Months | 0.00 | 0.00 | 835.88 | 622.33 |
Maximum of Months | 0.00 | 0.00 | 1244.51 | 926.57 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1245.80 | 927.53 |
February | 0.00 | 0.00 | 1239.58 | 833.59 |
March | 0.00 | 0.00 | 1171.50 | 872.22 |
April | 0.00 | 0.00 | 1068.39 | 769.79 |
May | 0.00 | 0.00 | 961.00 | 715.49 |
June | 0.00 | 0.00 | 875.12 | 630.54 |
July | 0.00 | 0.00 | 835.91 | 622.36 |
August | 0.00 | 0.00 | 847.66 | 631.11 |
September | 0.00 | 0.00 | 910.03 | 655.69 |
October | 0.00 | 0.00 | 1012.08 | 753.53 |
November | 0.00 | 0.00 | 1119.63 | 806.70 |
December | 0.00 | 0.00 | 1212.93 | 903.06 |
Annual Sum or Average | 0.00 | 0.00 | 1040.54 | 9121.59 |
Minimum of Months | 0.00 | 0.00 | 835.91 | 622.36 |
Maximum of Months | 0.00 | 0.00 | 1245.80 | 927.53 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1251.24 | 931.58 |
February | 0.00 | 0.00 | 1243.12 | 835.97 |
March | 0.00 | 0.00 | 1173.49 | 873.70 |
April | 0.00 | 0.00 | 1070.15 | 771.06 |
May | 0.00 | 0.00 | 959.48 | 714.36 |
June | 0.00 | 0.00 | 876.75 | 631.71 |
July | 0.00 | 0.00 | 835.87 | 622.33 |
August | 0.00 | 0.00 | 847.67 | 631.11 |
September | 0.00 | 0.00 | 910.05 | 655.70 |
October | 0.00 | 0.00 | 1013.77 | 754.78 |
November | 0.00 | 0.00 | 1123.29 | 809.34 |
December | 0.00 | 0.00 | 1216.41 | 905.65 |
Annual Sum or Average | 0.00 | 0.00 | 1042.33 | 9137.29 |
Minimum of Months | 0.00 | 0.00 | 835.87 | 622.33 |
Maximum of Months | 0.00 | 0.00 | 1251.24 | 931.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1247.82 | 929.04 |
February | 0.00 | 0.00 | 1241.32 | 834.76 |
March | 0.00 | 0.00 | 1171.68 | 872.35 |
April | 0.00 | 0.00 | 1066.56 | 768.47 |
May | 0.00 | 0.00 | 961.09 | 715.56 |
June | 0.00 | 0.00 | 875.15 | 630.55 |
July | 0.00 | 0.00 | 837.52 | 623.56 |
August | 0.00 | 0.00 | 846.05 | 629.91 |
September | 0.00 | 0.00 | 911.74 | 656.92 |
October | 0.00 | 0.00 | 1010.41 | 752.28 |
November | 0.00 | 0.00 | 1121.48 | 808.04 |
December | 0.00 | 0.00 | 1216.46 | 905.69 |
Annual Sum or Average | 0.00 | 0.00 | 1041.17 | 9127.11 |
Minimum of Months | 0.00 | 0.00 | 837.52 | 623.56 |
Maximum of Months | 0.00 | 0.00 | 1247.82 | 929.04 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1247.91 | 929.10 |
February | 0.00 | 0.00 | 1241.42 | 834.82 |
March | 0.00 | 0.00 | 1173.20 | 873.48 |
April | 0.00 | 0.00 | 1068.40 | 769.79 |
May | 0.00 | 0.00 | 961.06 | 715.53 |
June | 0.00 | 0.00 | 875.04 | 630.47 |
July | 0.00 | 0.00 | 835.89 | 622.35 |
August | 0.00 | 0.00 | 847.68 | 631.12 |
September | 0.00 | 0.00 | 910.03 | 655.69 |
October | 0.00 | 0.00 | 1012.01 | 753.47 |
November | 0.00 | 0.00 | 1123.14 | 809.24 |
December | 0.00 | 0.00 | 1216.38 | 905.63 |
Annual Sum or Average | 0.00 | 0.00 | 1041.58 | 9130.70 |
Minimum of Months | 0.00 | 0.00 | 835.89 | 622.35 |
Maximum of Months | 0.00 | 0.00 | 1247.91 | 929.10 |
Report: HEATING AND COOLING LOADS
For: HEATEDBSMT
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 2825.43 |
February | 0.00 | 3679.19 |
March | 0.00 | 2985.65 |
April | 0.39 | 568.41 |
May | 73.77 | 0.94 |
June | 255.13 | 0.00 |
July | 246.12 | 0.00 |
August | 232.62 | 0.00 |
September | 158.05 | 0.00 |
October | 59.10 | 1.74 |
November | 1.36 | 1410.57 |
December | 0.00 | 3976.24 |
Annual Sum or Average | 1026.53 | 15448.16 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 255.13 | 3976.24 |
Report: HEATING AND COOLING LOADS
For: BREEZEWAY
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 114.53 | 170.27 |
February | 59.83 | 152.94 |
March | 89.41 | 157.44 |
April | 189.17 | 3.49 |
May | 243.38 | 0.00 |
June | 310.15 | 0.00 |
July | 296.05 | 0.00 |
August | 288.78 | 0.00 |
September | 256.34 | 0.00 |
October | 189.45 | 18.93 |
November | 109.21 | 115.29 |
December | 83.18 | 358.53 |
Annual Sum or Average | 2229.48 | 976.90 |
Minimum of Months | 59.83 | 0.00 |
Maximum of Months | 310.15 | 358.53 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 107.51 | 61.65 |
February | 62.38 | 53.59 |
March | 79.50 | 58.91 |
April | 144.47 | 0.49 |
May | 190.09 | 0.00 |
June | 236.86 | 0.00 |
July | 237.18 | 0.00 |
August | 234.08 | 0.00 |
September | 215.71 | 0.00 |
October | 168.58 | 2.35 |
November | 101.15 | 37.15 |
December | 84.33 | 138.58 |
Annual Sum or Average | 1861.85 | 352.73 |
Minimum of Months | 62.38 | 0.00 |
Maximum of Months | 237.18 | 138.58 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 107.85 | 157.09 |
February | 59.98 | 138.00 |
March | 86.63 | 135.42 |
April | 188.02 | 3.05 |
May | 247.26 | 0.00 |
June | 316.14 | 0.00 |
July | 307.65 | 0.00 |
August | 298.76 | 0.00 |
September | 261.14 | 0.00 |
October | 191.43 | 17.16 |
November | 102.55 | 104.71 |
December | 79.04 | 331.95 |
Annual Sum or Average | 2246.46 | 887.38 |
Minimum of Months | 59.98 | 0.00 |
Maximum of Months | 316.14 | 331.95 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 58.80 | 215.56 |
February | 34.30 | 193.46 |
March | 66.74 | 170.18 |
April | 165.92 | 3.52 |
May | 237.69 | 0.00 |
June | 312.51 | 0.00 |
July | 294.17 | 0.00 |
August | 275.95 | 0.00 |
September | 232.84 | 0.00 |
October | 144.89 | 23.19 |
November | 63.19 | 146.76 |
December | 37.03 | 449.64 |
Annual Sum or Average | 1924.03 | 1202.31 |
Minimum of Months | 34.30 | 0.00 |
Maximum of Months | 312.51 | 449.64 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 49.63 | 83.36 |
February | 37.06 | 71.48 |
March | 56.85 | 64.79 |
April | 120.86 | 0.49 |
May | 184.69 | 0.00 |
June | 239.96 | 0.00 |
July | 235.73 | 0.00 |
August | 221.79 | 0.00 |
September | 191.75 | 0.00 |
October | 121.99 | 3.52 |
November | 53.61 | 54.52 |
December | 37.27 | 192.07 |
Annual Sum or Average | 1551.19 | 470.22 |
Minimum of Months | 37.06 | 0.00 |
Maximum of Months | 239.96 | 192.07 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 48.27 | 179.30 |
February | 32.48 | 152.87 |
March | 62.13 | 140.55 |
April | 164.13 | 3.13 |
May | 241.35 | 0.00 |
June | 316.26 | 0.00 |
July | 304.48 | 0.00 |
August | 284.72 | 0.00 |
September | 237.04 | 0.00 |
October | 145.07 | 18.54 |
November | 53.85 | 120.03 |
December | 32.00 | 382.97 |
Annual Sum or Average | 1921.78 | 997.39 |
Minimum of Months | 32.00 | 0.00 |
Maximum of Months | 316.26 | 382.97 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 153.50 | 69.42 |
February | 87.47 | 60.03 |
March | 125.52 | 64.06 |
April | 234.44 | 0.43 |
May | 270.78 | 0.00 |
June | 331.03 | 0.00 |
July | 316.44 | 0.00 |
August | 311.09 | 0.00 |
September | 279.12 | 0.00 |
October | 213.03 | 8.58 |
November | 144.83 | 48.37 |
December | 114.76 | 181.66 |
Annual Sum or Average | 2582.01 | 432.56 |
Minimum of Months | 87.47 | 0.00 |
Maximum of Months | 331.03 | 181.66 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 149.62 | 8.59 |
February | 92.93 | 7.15 |
March | 118.15 | 11.68 |
April | 189.52 | 0.00 |
May | 213.41 | 0.00 |
June | 250.44 | 0.00 |
July | 251.99 | 0.00 |
August | 250.94 | 0.00 |
September | 234.48 | 0.00 |
October | 192.79 | 0.03 |
November | 141.13 | 6.79 |
December | 122.82 | 42.14 |
Annual Sum or Average | 2208.22 | 76.37 |
Minimum of Months | 92.93 | 0.00 |
Maximum of Months | 251.99 | 42.14 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 148.79 | 62.02 |
February | 90.03 | 51.14 |
March | 125.69 | 49.69 |
April | 237.14 | 0.33 |
May | 276.66 | 0.00 |
June | 335.59 | 0.00 |
July | 328.70 | 0.00 |
August | 319.75 | 0.00 |
September | 283.90 | 0.00 |
October | 216.73 | 6.36 |
November | 139.44 | 41.46 |
December | 112.52 | 162.57 |
Annual Sum or Average | 2614.93 | 373.57 |
Minimum of Months | 90.03 | 0.00 |
Maximum of Months | 335.59 | 162.57 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 85.64 | 100.55 |
February | 53.68 | 86.06 |
March | 98.09 | 71.40 |
April | 209.12 | 0.43 |
May | 265.07 | 0.00 |
June | 334.03 | 0.00 |
July | 314.70 | 0.00 |
August | 297.40 | 0.00 |
September | 253.92 | 0.00 |
October | 163.59 | 10.79 |
November | 89.20 | 72.30 |
December | 55.49 | 260.20 |
Annual Sum or Average | 2219.94 | 601.72 |
Minimum of Months | 53.68 | 0.00 |
Maximum of Months | 334.03 | 260.20 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 77.03 | 17.73 |
February | 57.09 | 16.57 |
March | 89.29 | 14.13 |
April | 163.51 | 0.00 |
May | 207.92 | 0.00 |
June | 254.42 | 0.00 |
July | 250.66 | 0.00 |
August | 237.81 | 0.00 |
September | 208.89 | 0.00 |
October | 140.88 | 0.22 |
November | 81.66 | 14.07 |
December | 58.98 | 75.42 |
Annual Sum or Average | 1828.13 | 138.13 |
Minimum of Months | 57.09 | 0.00 |
Maximum of Months | 254.42 | 75.42 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 76.48 | 74.90 |
February | 52.96 | 62.64 |
March | 96.15 | 52.48 |
April | 211.40 | 0.32 |
May | 270.59 | 0.00 |
June | 338.50 | 0.00 |
July | 326.85 | 0.00 |
August | 307.60 | 0.00 |
September | 259.07 | 0.00 |
October | 165.61 | 6.20 |
November | 80.78 | 53.32 |
December | 50.36 | 208.50 |
Annual Sum or Average | 2236.35 | 458.36 |
Minimum of Months | 50.36 | 0.00 |
Maximum of Months | 338.50 | 208.50 |
Report: HEATING AND COOLING LOADS
For: ATTIC
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 74.47 | 188.21 |
February | 47.14 | 163.96 |
March | 97.73 | 131.46 |
April | 238.04 | 1.55 |
May | 298.97 | 0.00 |
June | 385.39 | 0.00 |
July | 372.02 | 0.00 |
August | 351.63 | 0.00 |
September | 295.22 | 0.00 |
October | 177.66 | 27.23 |
November | 78.45 | 134.53 |
December | 44.95 | 449.23 |
Annual Sum or Average | 2461.66 | 1096.17 |
Minimum of Months | 44.95 | 0.00 |
Maximum of Months | 385.39 | 449.23 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 131.71 | 156.94 |
February | 73.86 | 142.85 |
March | 115.14 | 126.84 |
April | 250.79 | 1.58 |
May | 300.58 | 0.00 |
June | 381.49 | 0.00 |
July | 371.34 | 0.00 |
August | 357.81 | 0.00 |
September | 309.47 | 0.00 |
October | 214.04 | 24.64 |
November | 124.44 | 110.72 |
December | 93.04 | 372.88 |
Annual Sum or Average | 2723.70 | 936.45 |
Minimum of Months | 73.86 | 0.00 |
Maximum of Months | 381.49 | 372.88 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 138.13 | 180.40 |
February | 72.93 | 168.36 |
March | 116.92 | 159.43 |
April | 249.54 | 2.20 |
May | 295.57 | 0.00 |
June | 376.95 | 0.00 |
July | 359.19 | 0.00 |
August | 347.88 | 0.00 |
September | 304.17 | 0.00 |
October | 211.58 | 31.34 |
November | 131.20 | 130.42 |
December | 97.52 | 418.86 |
Annual Sum or Average | 2701.59 | 1091.02 |
Minimum of Months | 72.93 | 0.00 |
Maximum of Months | 376.95 | 418.86 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 75.04 | 85.10 |
February | 50.82 | 74.91 |
March | 91.26 | 60.65 |
April | 191.50 | 0.17 |
May | 237.23 | 0.00 |
June | 301.27 | 0.00 |
July | 296.16 | 0.00 |
August | 282.56 | 0.00 |
September | 245.87 | 0.00 |
October | 153.72 | 7.97 |
November | 79.28 | 64.02 |
December | 50.32 | 242.21 |
Annual Sum or Average | 2055.02 | 535.03 |
Minimum of Months | 50.32 | 0.00 |
Maximum of Months | 301.27 | 242.21 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 133.28 | 53.28 |
February | 77.74 | 50.56 |
March | 108.51 | 52.56 |
April | 204.34 | 0.17 |
May | 238.53 | 0.00 |
June | 296.84 | 0.00 |
July | 295.15 | 0.00 |
August | 288.60 | 0.00 |
September | 260.31 | 0.00 |
October | 190.78 | 5.11 |
November | 126.16 | 39.89 |
December | 100.31 | 160.67 |
Annual Sum or Average | 2320.55 | 362.23 |
Minimum of Months | 77.74 | 0.00 |
Maximum of Months | 296.84 | 160.67 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 84.97 | 244.41 |
February | 48.72 | 220.27 |
March | 100.68 | 174.56 |
April | 237.01 | 2.29 |
May | 294.15 | 0.00 |
June | 380.99 | 0.00 |
July | 360.03 | 0.00 |
August | 341.86 | 0.00 |
September | 290.17 | 0.00 |
October | 176.55 | 40.49 |
November | 88.10 | 177.16 |
December | 52.05 | 543.39 |
Annual Sum or Average | 2455.28 | 1402.58 |
Minimum of Months | 48.72 | 0.00 |
Maximum of Months | 380.99 | 543.39 |