Table of Contents

Program Version:EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:27

Tabular Output Report in Format: HTML

Building: US+MF+CZ3B+hp+crawlspace+IECC_2021

Environment: ANNUAL ** El Paso International Ap Ut TX USA TMY3 WMO#=722700

Simulation Timestamp: 2021-05-12 10:27:07


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 546276.17 14.01 25.28
Net Site Energy 546276.17 14.01 25.28
Total Source Energy 1730056.64 44.35 80.06
Net Source Energy 1730056.64 44.35 80.06


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.22
Net Conditioned Building Area 21609.96
Unconditioned Building Area 17395.26


End Uses

Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 48727.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 65059.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 38708.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 18809.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299798.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 29550.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 45622.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 330767.30
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 546276.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 330767.30
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 48727.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 65059.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 38708.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 18809.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 9418.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 4809.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 20897.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 8652.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 330767.30
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 4468.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Other 41154.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 8.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.31
Other 13.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 25.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.31


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 4.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.48
Other 7.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 14.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.48


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 546276.175 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 546276.175 100.00
     
Total On-Site and Utility Electric Sources 546276.175 100.00
Total Electricity End Uses 546276.175 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 330767.30 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 330767.30 100.00
Total Water End Uses 330767.30 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 119.00
Time Setpoint Not Met During Occupied Cooling 85.67
Time Not Comfortable Based on Simple ASHRAE 55-2004 463.67


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR |

HEATING AND COOLING LOADS

| CRAWLSPACE | BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

General

Value
Program Version and Build EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:27
RunPeriod ANNUAL
Weather File El Paso International Ap Ut TX USA TMY3 WMO#=722700
Latitude [deg] 31.77
Longitude [deg] -106.5
Elevation [ft] 3891.27
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 17103.09 6415.36 2136.19 6415.36 2136.19
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 12.43 8.29 24.89 8.29 24.89
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
CRAWLSPACE 7794.39 No Yes 19513.17 1.00 185.02 740.10 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.16 No Yes 30553.25 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
ATTIC 7802.71 No Yes 52795.56 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
Total 39005.22     286601.37   16363.00 740.10 2126.74 2126.74 0.3230 1083.48 1.6118
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.5831 600.28 2.9092
Unconditioned Total 17395.26     102861.98   1066.39 740.10 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 27-DEC-07:10 - - - - - - - - - - - 01-JAN-08:09
Heating 91.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 5.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 33.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 8.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.20
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 164.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.20


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 91.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 5.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 0.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 4.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 3.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 3.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 19.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 7.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 0.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.20
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Gasoline [kBtu] Source Diesel [kBtu] Source Coal [kBtu] Source Fuel Oil No 1 [kBtu] Source Fuel Oil No 2 [kBtu] Source Propane [kBtu] Source Other Fuel 1 [kBtu] Source Other Fuel 2 [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 154319.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 206042.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 122590.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 59568.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 949462.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 93586.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 144486.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1730056.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 7.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 9.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 5.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 43.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 4.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 6.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 80.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 3.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 5.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 24.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 3.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 44.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

ZoneHVAC:EnergyRecoveryVentilator

User-Specified Supply Air Flow Rate [ft3/min] User-Specified Exhaust Air Flow Rate [ft3/min]
ERV_UNIT1_FRONTROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT2_FRONTROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT3_FRONTROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT1_BACKROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT2_BACKROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT3_BACKROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT1_FRONTROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT2_FRONTROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT3_FRONTROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT1_BACKROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT2_BACKROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT3_BACKROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT3_BACKROW_TOPFLOOR 44.99 44.99
ERV_UNIT3_FRONTROW_TOPFLOOR 44.99 44.99
ERV_UNIT1_FRONTROW_TOPFLOOR 44.99 44.99
ERV_UNIT2_BACKROW_TOPFLOOR 44.99 44.99
ERV_UNIT2_FRONTROW_TOPFLOOR 44.99 44.99
ERV_UNIT1_BACKROW_TOPFLOOR 44.99 44.99
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

User-Specified Maximum Flow Rate [ft3/min] Design Size Maximum Flow Rate [ft3/min]
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR 44.99  
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR   397.58
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR   235.16
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR   282.99
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR   392.30
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR   234.13
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR   280.86
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR   376.02
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR   220.53
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR   270.74
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR   371.46
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR   219.34
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR   267.77
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR   418.21
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR   265.39
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR   313.00
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR   421.12
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR   268.84
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR   317.41
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR   160.01
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

User-Specified Nominal Supply Air Flow Rate [ft3/min]
OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR 44.99
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 397.58
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 235.16
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 282.99
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 392.30
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 234.13
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 280.86
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 376.02
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 220.53
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 270.74
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 371.46
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 219.34
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 267.77
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 317.41
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 313.00
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 418.21
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 268.84
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 265.39
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 421.12
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] Sum of Air Terminal Maximum Flow Rates [ft3/min] Adjusted Heating Design Air Flow Rate [ft3/min] Adjusted Cooling Design Air Flow Rate [ft3/min] Adjusted Main Design Air Flow Rate [ft3/min] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 397.58 397.58 397.58 397.58 397.58 397.58 1.00 1.00 397.58
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 235.16 235.16 235.16 235.16 235.16 235.16 1.00 1.00 235.16
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 282.99 282.99 282.99 282.99 282.99 282.99 1.00 1.00 282.99
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 392.30 392.30 392.30 392.30 392.30 392.30 1.00 1.00 392.30
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 234.13 234.13 234.13 234.13 234.13 234.13 1.00 1.00 234.13
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 280.86 280.86 280.86 280.86 280.86 280.86 1.00 1.00 280.86
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 376.02 376.02 376.02 376.02 376.02 376.02 1.00 1.00 376.02
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 220.53 220.53 220.53 220.53 220.53 220.53 1.00 1.00 220.53
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 270.74 270.74 270.74 270.74 270.74 270.74 1.00 1.00 270.74
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 371.46 371.46 371.46 371.46 371.46 371.46 1.00 1.00 371.46
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 219.34 219.34 219.34 219.34 219.34 219.34 1.00 1.00 219.34
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 267.77 267.77 267.77 267.77 267.77 267.77 1.00 1.00 267.77
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 418.21 418.21 418.21 418.21 418.21 418.21 1.00 1.00 418.21
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 265.39 265.39 265.39 265.39 265.39 265.39 1.00 1.00 265.39
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 313.00 313.00 313.00 313.00 313.00 313.00 1.00 1.00 313.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 421.12 421.12 421.12 421.12 421.12 421.12 1.00 1.00 421.12
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 268.84 268.84 268.84 268.84 268.84 268.84 1.00 1.00 268.84
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 317.41 317.41 317.41 317.41 317.41 317.41 1.00 1.00 317.41
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 397.58 0.887823 0.800765
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 235.16 0.530271 0.800221
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 282.99 0.646859 0.800321
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 392.30 0.875722 0.800891
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 234.13 0.528191 0.800044
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 280.86 0.636840 0.800218
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 376.02 0.845926 0.800062
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 220.53 0.504385 0.800107
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 270.74 0.611692 0.800517
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 371.46 0.834903 0.800392
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 219.34 0.502044 0.800846
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 267.77 0.611269 0.800795
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 418.21 0.929508 0.800491
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 265.39 0.592138 0.800072
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 313.00 0.700581 0.800912
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 421.12 0.935548 0.800655
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 268.84 0.599171 0.800473
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 317.41 0.709661 0.800315
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:AirToAir

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Supplemental Heating Coil Nominal Capacity [Btu/h] Fraction of Supply Air Flow That Goes Through the Controlling Zone
HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR 397.58 397.58 397.58 10653.87 0.887823 7210.94 1.00
HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR 235.16 235.16 235.16 6363.25 0.530271 5666.97 1.00
HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR 282.99 282.99 282.99 7762.31 0.646859 7211.63 1.00
HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR 392.30 392.30 392.30 10508.66 0.875722 7214.78 1.00
HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR 234.13 234.13 234.13 6338.30 0.528191 5668.32 1.00
HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR 280.86 280.86 280.86 7642.08 0.636840 7210.36 1.00
HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR 376.02 376.02 376.02 10151.12 0.845926 5642.09 1.00
HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR 220.53 220.53 220.53 6052.62 0.504385 4197.57 1.00
HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR 270.74 270.74 270.74 7340.31 0.611692 5644.04 1.00
HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR 371.46 371.46 371.46 10018.84 0.834903 5644.88 1.00
HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR 219.34 219.34 219.34 6024.52 0.502044 4197.57 1.00
HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR 267.77 267.77 267.77 7335.23 0.611269 5642.09 1.00
HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR 418.21 418.21 418.21 11154.10 0.929508 7129.04 1.00
HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR 265.39 265.39 265.39 7105.66 0.592138 5590.19 1.00
HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR 313.00 313.00 313.00 8406.97 0.700581 7131.29 1.00
HEAT PUMP_UNIT1_BACKROW_TOPFLOOR 421.12 421.12 421.12 11226.58 0.935548 7130.96 1.00
HEAT PUMP_UNIT2_BACKROW_TOPFLOOR 268.84 268.84 268.84 7190.06 0.599171 5590.39 1.00
HEAT PUMP_UNIT3_BACKROW_TOPFLOOR 317.41 317.41 317.41 8515.94 0.709661 7129.76 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Heating Capacity [Btu/h]
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 397.58 10653.87
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 235.16 6363.25
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 282.99 7762.31
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 392.30 10508.66
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 234.13 6338.30
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 280.86 7642.08
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 376.02 10151.12
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 220.53 6052.62
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 270.74 7340.31
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 371.46 10018.84
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 219.34 6024.52
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 267.77 7335.23
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 418.21 11154.10
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 265.39 7105.66
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 313.00 8406.97
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR 421.12 11226.58
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR 268.84 7190.06
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR 317.41 8515.94
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [Btu/h]
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 7210.94
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 5666.97
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 7211.63
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 7214.78
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 5668.32
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 7210.36
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 5642.09
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 4197.57
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 5644.04
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 5644.88
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 4197.57
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 5642.09
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 7129.04
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 5590.19
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 7131.29
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR 7130.96
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR 5590.39
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR 7129.76
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:HeatPump:WrappedCondenser

Evaporator air flow rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 160.01
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 160.01
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 160.01
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 160.01
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 160.01
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 160.01
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 2.09
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Stratified

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR 15354.00 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
BGWALL_UPPER_LDF OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
BGWALL_UPPER_SDR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
BGWALL_UPPER_LDB OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
BGWALL_UPPER_SDL OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

Version

Version ID
1 9.5


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes No Yes Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.200 0.200


Site:GroundTemperature:BuildingSurface

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40


Site:GroundTemperature:FCfactorMethod

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 54.59 48.72 47.12 48.51 56.43 65.30 73.65 79.68 81.45 78.62 71.78 63.16


Site:GroundTemperature:Shallow

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40


Site:GroundTemperature:Deep

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {ft} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Sensor Height Above Ground {ft} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 32.810 0.140 885.870 4.921 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {ft} Standard Pressure at Elevation {psi} Standard RhoAir at Elevation
1 El Paso International Ap Ut TX USA TMY3 WMO#=722700 31.77 -106.50 -7.00 3891.27 13. 1.0443


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{F} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} Fixed Default Water Mains Temperature{F}
1 Correlation NA 64.29 37.98 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 US+MF+CZ3B+hp+crawlspace+IECC_2021 0.000 Suburbs 4.00000E-002 0.40000 FullExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Gradient Coefficient {F/ft}
1 0.220 1213.970 0.003566


Material Details

Material Name ThermalResistance {m2-K/w} Roughness Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} Absorptance:Thermal Absorptance:Solar Absorptance:Visible
1 SHEATHING_CONSOL_LAYER 0.1351 Rough 0.0417 9.402E-002 42.764 0.280 0.9000 0.7000 0.7000
2 CEIL_CONSOL_LAYER 7.7625 Rough 1.5719 6.172E-002 2.618 0.185 0.9000 0.7000 0.7000
3 FLOOR_CONSOL_LAYER 2.8450 Rough 0.4584 4.910E-002 3.438 0.219 0.9000 0.7000 0.7000
4 BSMTWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
5 CRAWLWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
6 WALL_CONSOL_LAYER 2.4438 Rough 0.4584 5.717E-002 7.541 0.248 0.9000 0.7000 0.7000
7 VERY HIGH REFLECTIVITY SURFACE 2.1097E-006 Smooth 0.0016 237.000 168.680 0.216 0.9000 5.0000E-002 5.0000E-002
8 GYPSUMBOARD-5/16IN 5.0054E-002 Rough 0.0260 0.159 39.954 0.270 0.9000 0.4000 0.1000
9 COPPERPIPE 4.7506E-005 MediumRough 0.0625 401.000 140.026 0.200 0.9000 0.6500 0.6500
10 F08 METAL SURFACE 1.7668E-005 Smooth 0.0026 45.280 488.437 0.119 0.9000 0.7000 0.7000
11 CONCRETE_4IN 7.7356E-002 Rough 0.3330 1.312 140.014 0.111 0.9000 0.7000 0.7000
12 ASPHALT_SHINGLE 7.7448E-002 MediumRough 0.0208 8.186E-002 70.000 0.300 0.9000 0.7500 0.7000
13 WOOD_SHINGLE 0.1115 MediumSmooth 0.0417 0.114 26.600 0.390 0.9000 0.7000 0.7000
14 SLATE_SHINGLE 8.8061E-003 MediumSmooth 0.0417 1.442 100.000 0.300 0.9000 0.7000 0.7000
15 CEMENT_STUCCO 2.6422E-002 MediumSmooth 0.0625 0.721 116.464 0.210 0.9000 0.7000 0.7000
16 SYN_STUCCO 3.5237E-002 MediumSmooth 0.0100 8.650E-002 24.971 0.210 0.9000 0.7000 0.7000
17 DRYWALL_1/2IN 7.9331E-002 MediumSmooth 0.0417 0.160 50.000 0.260 0.9000 0.7000 0.7000
18 OSB_5/8IN 0.1365 MediumSmooth 0.0521 0.116 34.000 0.290 0.9000 0.7000 0.7000
19 OSB_7/16IN 9.5550E-002 MediumSmooth 0.0365 0.116 34.000 0.290 0.9000 0.7000 0.7000
20 BLOWN_R30 5.1614 MediumRough 0.6975 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
21 BLOWN_R30_TOP 2.8489 MediumRough 0.3849 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
22 PLYWOOD_3/4IN 0.1650 Rough 0.0625 0.115 34.003 0.161 0.9000 0.7000 0.7000
23 BATT_R19 7.3089 MediumRough 0.0833 3.475E-003 0.600 0.200 0.9000 0.7000 0.7000
24 LUMBER_2X4 0.7709 Rough 0.2920 0.115 32.003 0.183 0.9000 0.7000 0.7000
25 CARPET_N_PAD 0.4224 MediumSmooth 0.0833 6.013E-002 2.000 0.200 0.9000 0.7000 0.7000
26 BATT_R13 2.2936 MediumRough 0.2917 3.876E-002 0.600 0.200 0.9000 0.7000 0.7000
27 OSB_1/2IN 0.1092 MediumSmooth 0.0417 0.116 34.000 0.290 0.9000 0.7000 0.7000
28 SOIL_12IN 0.1761 Rough 1.0000 1.731 115.011 0.056 0.9000 0.7000 0.7000
29 DOOR_CONST 0.5870 Smooth 0.1387 7.201E-002 32.003 0.183 0.9000 0.7000 0.7000
30 GYP_BOARD_1/2IN 8.0130E-002 Rough 0.0417 0.159 39.954 0.270 0.9000 0.4000 0.1000
31 STD WOOD 6INCH 1.2500 MediumSmooth 0.4921 0.120 33.711 0.289 0.9000 0.7000 0.7000
32 PIPE INSULATION 0.3830 VeryRough 0.0417 3.317E-002 5.681 0.200 0.9000 0.5000 0.5000
33 MANF_WALL_AIRGAP 0.1200 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
34 BLDG_PAPER_FELT 1.0567E-002 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
35 R_HIGH 177.0000 MediumRough 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
36 CLEAR ACRYLIC PLASTIC 3.3333E-003 VerySmooth 0.0098 0.900 0.000 0.000 0.9000 0.0000 0.0000
37 DIFFUSING ACRYLIC PLASTIC 2.4444E-003 VerySmooth 0.0072 0.900 0.000 0.000 0.9000 0.0000 0.0000
38 INT_BLIND 0.0000 Rough 0.0000 0.000 0.000 0.000 0.0000 0.0000 0.0000
39 GLASS 0.4127 VerySmooth 0.1373 0.101 0.000 0.000 0.8400 0.0000 0.0000


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 LowerLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Other Side Coefficients

Name Combined convective/radiative film coefficient {Btu/h-ft2-F} User selected Constant Temperature {F} Coefficient modifying the constant temperature term Coefficient modifying the external dry bulb temperature term Coefficient modifying the ground temperature term Coefficient modifying the wind speed term {s/m} Coefficient modifying the zone air temperature term Constant Temperature Schedule Name Sinusoidal Variation Period of Sinusoidal Variation Previous Other Side Temperature Coefficient Minimum Other Side Temperature {F} Maximum Other Side Temperature {F}
1 SURFPROPOTHSDCOEFSLABAVERAGE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABAVERAGESURFACETEMP NO 24.000 0.000 N/A N/A
2 SURFPROPOTHSDCOEFSLABPERIMETER N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABPERIMETERTEMP NO 24.000 0.000 N/A N/A
3 SURFPROPOTHSDCOEFSLABCORE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABCORETEMP NO 24.000 0.000 N/A N/A


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{F}


Surface Convection Coefficient Lower Limit {Btu/h-ft2-F}


Surface Convection Coefficient Upper Limit {Btu/h-ft2-F}


1 CTF - ConductionTransferFunction 392. 0.02 176.1


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 60


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 21 186 48


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {ft} Origin Y-Coordinate {ft} Origin Z-Coordinate {ft} Centroid X-Coordinate {ft} Centroid Y-Coordinate {ft} Centroid Z-Coordinate {ft} Type Zone Multiplier Zone List Multiplier Minimum X {ft} Maximum X {ft} Minimum Y {ft} Maximum Y {ft} Minimum Z {ft} Maximum Z {ft} Ceiling Height {ft} Volume {ft3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {ft2} Exterior Gross Wall Area {ft2} Exterior Net Wall Area {ft2} Exterior Window Area {ft2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CRAWLSPACE 0.0 0.00 0.00 0.00 59.94 32.51 -0.8 1 1 1 0.00 119.89 0.00 65.10 -2.0 0.49 2.49 19513.15 TARP DOE-2 7794.37 185.05 185.05 0.00 15 0 0 Yes
2 BREEZEWAY 0.0 0.00 0.00 0.00 59.94 32.55 13.26 1 1 1 0.00 119.89 30.05 35.04 0.49 25.99 17.00 30553.07 TARP DOE-2 1798.18 0.00 0.00 0.00 4 0 0 Yes
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 4.76 1 1 1 0.00 39.96 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 4.76 1 1 1 39.96 79.93 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 4.76 1 1 1 79.93 119.89 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 4.76 1 1 1 0.00 39.96 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 4.76 1 1 1 39.96 79.93 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 4.76 1 1 1 79.93 119.89 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 13.26 1 1 1 0.00 39.96 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 13.26 1 1 1 39.96 79.93 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 13.26 1 1 1 79.93 119.89 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 13.26 1 1 1 0.00 39.96 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 13.26 1 1 1 39.96 79.93 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 13.26 1 1 1 79.93 119.89 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
15 ATTIC 0.0 -134.9 51.61 0.00 59.94 32.55 29.56 1 1 1 0.00 119.89 0.00 65.10 25.99 39.54 6.76 52795.39 TARP DOE-2 7802.66 881.33 881.33 0.00 11 0 0 Yes
16 LIVING_UNIT3_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 21.75 1 1 1 79.93 119.89 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
17 LIVING_UNIT3_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 21.75 1 1 1 79.93 119.89 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
18 LIVING_UNIT1_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 21.75 1 1 1 0.00 39.96 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
19 LIVING_UNIT2_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 21.75 1 1 1 39.96 79.93 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
20 LIVING_UNIT2_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 21.75 1 1 1 39.96 79.93 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
21 LIVING_UNIT1_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 21.75 1 1 1 0.00 39.96 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {ft2} # Occupants Area per Occupant {ft2/person} Occupant per Area {person/ft2} Interior Lighting {Btu/h-ft2} Electric Load {Btu/h-ft2} Gas Load {Btu/h-ft2} Other Load {Btu/h-ft2} Hot Water Eq {Btu/h-ft2} Steam Equipment {Btu/h-ft2} Sum Loads per Area {Btu/h-ft2} Outdoor Controlled Baseboard Heat
1 CRAWLSPACE 7794.37 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
2 BREEZEWAY 1798.18 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
15 ATTIC 7802.66 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
16 LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
17 LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
18 LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
19 LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
20 LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
21 LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Number of People {} People/Floor Area {person/ft2} Floor Area per person {ft2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
2 PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
3 PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
4 PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
5 PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
6 PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
7 PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
8 PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
9 PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
10 PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
11 PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
12 PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
13 PEOPLE_UNIT1_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
14 PEOPLE_UNIT2_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
15 PEOPLE_UNIT3_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
16 PEOPLE_UNIT1_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
17 PEOPLE_UNIT2_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
18 PEOPLE_UNIT3_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Lighting Level {Btu/h} Lights/Floor Area {Btu/h-ft2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {Btu/h} Nominal Maximum Lighting Level {Btu/h}
1 LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
2 LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
3 LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
4 LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
5 LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
6 LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
7 LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
8 LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
9 LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
10 LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
11 LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
12 LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
13 LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
14 LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
15 LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
16 LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
17 LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
18 LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
19 LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
20 LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
21 LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
22 LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
23 LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
24 LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
25 LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
26 LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
27 LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
28 LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
29 LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
30 LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
31 LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
32 LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
33 LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
34 LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
35 LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
36 LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Equipment Level {Btu/h} Equipment/Floor Area {Btu/h-ft2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {Btu/h} Nominal Maximum Equipment Level {Btu/h}
1 DISHWASHER1_FRONTROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
2 REFRIGERATOR1_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
3 CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
4 ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
5 ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
6 TELEVISION1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
7 ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
8 IECC_ADJ1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
9 DISHWASHER2_FRONTROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
10 REFRIGERATOR2_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
11 CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
12 ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
13 ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
14 TELEVISION2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
15 ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
16 IECC_ADJ2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
17 DISHWASHER3_FRONTROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
18 REFRIGERATOR3_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
19 CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
20 ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
21 ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
22 TELEVISION3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
23 ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
24 IECC_ADJ3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
25 DISHWASHER1_BACKROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
26 REFRIGERATOR1_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
27 CLOTHESWASHER1_BACKROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
28 ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
29 ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
30 TELEVISION1_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
31 ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
32 IECC_ADJ1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
33 DISHWASHER2_BACKROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
34 REFRIGERATOR2_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
35 CLOTHESWASHER2_BACKROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
36 ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
37 ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
38 TELEVISION2_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
39 ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
40 IECC_ADJ2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
41 DISHWASHER3_BACKROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
42 REFRIGERATOR3_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
43 CLOTHESWASHER3_BACKROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
44 ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
45 ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
46 TELEVISION3_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
47 ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
48 IECC_ADJ3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
49 DISHWASHER1_FRONTROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
50 REFRIGERATOR1_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
51 CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
52 ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
53 ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
54 TELEVISION1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
55 ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
56 IECC_ADJ1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
57 DISHWASHER2_FRONTROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
58 REFRIGERATOR2_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
59 CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
60 ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
61 ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
62 TELEVISION2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
63 ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
64 IECC_ADJ2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
65 DISHWASHER3_FRONTROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
66 REFRIGERATOR3_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
67 CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
68 ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
69 ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
70 TELEVISION3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
71 ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
72 IECC_ADJ3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
73 DISHWASHER1_BACKROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
74 REFRIGERATOR1_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
75 CLOTHESWASHER1_BACKROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
76 ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
77 ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
78 TELEVISION1_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
79 ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
80 IECC_ADJ1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
81 DISHWASHER2_BACKROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
82 REFRIGERATOR2_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
83 CLOTHESWASHER2_BACKROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
84 ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
85 ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
86 TELEVISION2_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
87 ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
88 IECC_ADJ2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
89 DISHWASHER3_BACKROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
90 REFRIGERATOR3_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
91 CLOTHESWASHER3_BACKROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
92 ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
93 ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
94 TELEVISION3_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
95 ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
96 IECC_ADJ3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
97 DISHWASHER1_FRONTROW_TOPFLOOR DISHWASHER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
98 REFRIGERATOR1_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
99 CLOTHESWASHER1_FRONTROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
100 ELECTRIC_DRYER1_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
101 ELECTRIC_RANGE1_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
102 TELEVISION1_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
103 ELECTRIC_MELS1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
104 IECC_ADJ1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
105 DISHWASHER2_FRONTROW_TOPFLOOR DISHWASHER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
106 REFRIGERATOR2_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
107 CLOTHESWASHER2_FRONTROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
108 ELECTRIC_DRYER2_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
109 ELECTRIC_RANGE2_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
110 TELEVISION2_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
111 ELECTRIC_MELS2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
112 IECC_ADJ2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
113 DISHWASHER3_FRONTROW_TOPFLOOR DISHWASHER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
114 REFRIGERATOR3_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
115 CLOTHESWASHER3_FRONTROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
116 ELECTRIC_DRYER3_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
117 ELECTRIC_RANGE3_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
118 TELEVISION3_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
119 ELECTRIC_MELS3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
120 IECC_ADJ3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
121 DISHWASHER1_BACKROW_TOPFLOOR DISHWASHER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
122 REFRIGERATOR1_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
123 CLOTHESWASHER1_BACKROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
124 ELECTRIC_DRYER1_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
125 ELECTRIC_RANGE1_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
126 TELEVISION1_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
127 ELECTRIC_MELS1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
128 IECC_ADJ1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
129 DISHWASHER2_BACKROW_TOPFLOOR DISHWASHER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
130 REFRIGERATOR2_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
131 CLOTHESWASHER2_BACKROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
132 ELECTRIC_DRYER2_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
133 ELECTRIC_RANGE2_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
134 TELEVISION2_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
135 ELECTRIC_MELS2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
136 IECC_ADJ2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
137 DISHWASHER3_BACKROW_TOPFLOOR DISHWASHER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
138 REFRIGERATOR3_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
139 CLOTHESWASHER3_BACKROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
140 ELECTRIC_DRYER3_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
141 ELECTRIC_RANGE3_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
142 TELEVISION3_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
143 ELECTRIC_MELS3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
144 IECC_ADJ3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736


Construction CTF

Construction Name Index #Layers #CTFs Time Step {Hours} ThermalConductance {Btu/h-ft2-F} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 EXTERIOR WALL 1 5 11 0.167 0.0631 0.900 0.900 0.700 0.700 MediumSmooth
2 CEILING-FLOOR-LAYER 3 1 5 0.167 0.228 0.900 0.900 0.700 0.700 Rough
3 EXTERIOR FLOOR 4 3 8 0.167 0.0513 0.900 0.900 0.700 0.700 Rough
4 INTERIOR FLOOR 5 2 4 0.167 0.300 0.900 0.900 0.700 0.700 Rough
5 INTERIOR CEILING 6 2 12 0.167 0.0225 0.900 0.900 0.700 0.700 Rough
6 ATTIC FLOOR 7 2 12 0.167 0.0225 0.900 0.900 0.700 0.700 MediumSmooth
7 INTERIORWALL 9 3 5 0.167 0.597 0.900 0.900 0.700 0.700 MediumSmooth
8 EXTERIOR ROOF 11 2 4 0.167 0.943 0.900 0.900 0.750 0.700 MediumRough
9 EXTERIOR DOOR 14 1 5 0.167 0.300 0.900 0.900 0.700 0.700 Smooth
10 GABLE_END 16 5 6 0.167 0.428 0.900 0.900 0.700 0.700 MediumSmooth
11 CRAWL WALL 24 1 5 0.167 2.28 0.900 0.900 0.700 0.700 Rough
12 iz-EXTERIOR FLOOR 25 3 8 0.167 0.0513 0.900 0.900 0.700 0.700 MediumSmooth


Material CTF Summary

Material Name Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} ThermalResistance {m2-K/w}
1 SYN_STUCCO 0.0098 0.086 24.971 0.210 0.3524E-01
2 SHEATHING_CONSOL_LAYER 0.0417 0.094 42.764 0.280 0.1351
3 OSB_7/16IN 0.0364 0.116 34.000 0.290 0.9555E-01
4 WALL_CONSOL_LAYER 0.4584 0.057 7.541 0.248 2.444
5 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
6 LUMBER_2X4 0.2920 0.115 32.003 0.183 0.7709
7 FLOOR_CONSOL_LAYER 0.4584 0.049 3.438 0.219 2.845
8 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
9 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
10 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
11 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
12 CEIL_CONSOL_LAYER 1.5719 0.062 2.618 0.185 7.762
13 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
14 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
15 CEIL_CONSOL_LAYER 1.5719 0.062 2.618 0.185 7.762
16 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
17 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
18 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
19 ASPHALT_SHINGLE 0.0207 0.082 70.000 0.300 0.7745E-01
20 OSB_1/2IN 0.0417 0.116 34.000 0.290 0.1092
21 DOOR_CONST 0.1388 0.072 32.003 0.183 0.5870
22 CEMENT_STUCCO 0.0627 0.721 116.464 0.210 0.2642E-01
23 BLDG_PAPER_FELT 0.0000 0.000 0.000 0.000 0.1057E-01
24 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
25 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
26 CONCRETE_4IN 0.3330 1.312 140.014 0.111 0.7736E-01
27 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
28 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
29 FLOOR_CONSOL_LAYER 0.4584 0.049 3.438 0.219 2.845


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


CTF

Time Outside Cross Inside Flux (except final one)
1 11 -0.54724946E-11 -0.29353179E-14 -0.58361936E-11 0.17617726E-15
2 10 0.24755928E-06 0.16971160E-13 0.58954555E-06 -0.42317085E-11
3 9 -0.21700660E-03 0.26282512E-10 -0.34360792E-03 0.18634160E-06
4 8 0.10400975E-01 0.16063655E-07 0.16710006E-01 -0.10459154E-03
5 7 -0.18466841 0.14497582E-05 -0.31678806 0.33996447E-02
6 6 1.6813335 0.30890211E-04 3.0392820 -0.45644738E-01
7 5 -8.8640021 0.19737274E-03 -16.399456 0.32465800
8 4 28.400945 0.41196590E-03 52.185337 -1.3315683
9 3 -55.684303 0.27160336E-03 -99.213599 3.2198962
10 2 64.740984 0.46773103E-04 110.17164 -4.4902555
11 1 -40.701741 0.11975386E-05 -65.686261 3.3169381
12 0 10.602230 0.29970883E-09 16.204438  
13 5 -0.10726087E-01 0.44268190E-05 -0.10726087E-01 0.97389233E-03
14 4 0.31857203 0.80150166E-03 0.31857203 -0.30727185E-01
15 3 -2.8372473 0.12516450E-01 -2.8372473 0.30041224
16 2 9.6667056 0.33176537E-01 9.6667056 -1.1584571
17 1 -13.322214 0.15207483E-01 -13.322214 1.8397512
18 0 6.2472388 0.62260140E-03 6.2472388  
19 8 0.57415395E-12 0.13118744E-13 0.10972129E-06 -0.16121901E-12
20 7 -0.11209345E-05 0.79302418E-09 -0.25702593E-04 0.31491488E-06
21 6 0.21835020E-03 0.55842834E-06 0.16732899E-02 -0.62999473E-04
22 5 -0.11788181E-01 0.43793696E-04 -0.40973943E-01 0.36016799E-02
23 4 0.21386917 0.66464187E-03 0.43752526 -0.72376639E-01
24 3 -1.3884299 0.23440260E-02 -2.2272953 0.54574706
25 2 3.6315139 0.19014595E-02 5.4333867 -1.6855834
26 1 -4.0346078 0.26548191E-03 -6.0131296 2.1907513
27 0 1.5944472 0.16612988E-05 2.4140608  
28 4 0.50405178E-13 0.16668152E-13 0.29402090E-13 -0.58636069E-16
29 3 -0.78967347E-05 0.18486376E-05 -0.51544008E-05 0.20741056E-12
30 2 0.37655193 0.34407043E-01 0.80677627E-01 -0.16328896E-04
31 1 -8.0349315 0.81344511 -1.1624309 0.21506451
32 0 8.9946927 0.48845120 2.4180636  
33 12 0.94888791E-16 -0.11237443E-15 0.21480527E-09 -0.52606005E-16
34 11 -0.44509090E-09 -0.12338758E-15 -0.11566016E-03 0.28501063E-09
35 10 0.60393314E-04 0.62564840E-13 0.62960490E-02 -0.38672578E-04
36 9 -0.20055671E-02 0.85912012E-10 -0.12885789 0.13084700E-02
37 8 0.28697042E-01 0.10381403E-07 1.3966036 -0.19129448E-01
38 7 -0.23229993 0.28493476E-06 -9.1473517 0.15872626
39 6 1.1750436 0.24973161E-05 38.552224 -0.82592201
40 5 -3.8729952 0.80040830E-05 -107.65441 2.8111251
41 4 8.4143451 0.96510929E-05 200.56463 -6.3313915
42 3 -11.897084 0.41099356E-05 -245.77565 9.3152582
43 2 10.487404 0.50788650E-06 189.69676 -8.5734564
44 1 -5.2147174 0.10902359E-07 -83.415737 4.4633233
45 0 1.1135774 0.38882120E-11 15.905642  
46 12 0.21480527E-09 -0.11237443E-15 0.94888791E-16 -0.52606005E-16
47 11 -0.11566016E-03 -0.12338758E-15 -0.44509090E-09 0.28501063E-09
48 10 0.62960490E-02 0.62564840E-13 0.60393314E-04 -0.38672578E-04
49 9 -0.12885789 0.85912012E-10 -0.20055671E-02 0.13084700E-02
50 8 1.3966036 0.10381403E-07 0.28697042E-01 -0.19129448E-01
51 7 -9.1473517 0.28493476E-06 -0.23229993 0.15872626
52 6 38.552224 0.24973161E-05 1.1750436 -0.82592201
53 5 -107.65441 0.80040830E-05 -3.8729952 2.8111251
54 4 200.56463 0.96510929E-05 8.4143451 -6.3313915
55 3 -245.77565 0.41099356E-05 -11.897084 9.3152582
56 2 189.69676 0.50788650E-06 10.487404 -8.5734564
57 1 -83.415737 0.10902359E-07 -5.2147174 4.4633233
58 0 15.905642 0.38882120E-11 1.1135774  
59 5 -0.27590492E-07 0.65241430E-08 -0.27590492E-07 0.17331255E-13
60 4 0.68608714E-03 0.11323974E-03 0.68608714E-03 -0.15705033E-07
61 3 -0.21538511 0.37821720E-01 -0.21538511 0.25667047E-03
62 2 5.0173519 0.62258424 5.0173519 -0.50236511E-01
63 1 -19.904252 0.86481321 -19.904252 0.58144210
64 0 16.688993 0.62060609E-01 16.688993  
65 4 0.75441920E-10 0.23883683E-10 0.47514224E-10 -0.69373194E-20
66 3 -0.33730907E-03 0.89366797E-04 -0.22574866E-03 0.77828620E-10
67 2 0.58624422 0.18542418 0.49024360 -0.17301269E-03
68 1 -11.299243 2.8799011 -8.6239668 0.15905732
69 0 15.219762 1.4410112 12.640375  
70 5 -0.32935335E-06 0.42931990E-07 -0.32935335E-06 0.47097488E-08
71 4 0.68052310E-03 0.12823787E-03 0.68052310E-03 -0.14200104E-04
72 3 -0.11535993 0.17375615E-01 -0.11535993 0.40770076E-02
73 2 2.1922172 0.21284128 2.1922172 -0.13171357
74 1 -7.8704965 0.30308566 -7.8704965 0.79499401
75 0 6.3596665 0.33276539E-01 6.3596665  
76 6 0.97988530E-11 0.43917118E-12 0.24496810E-11 -0.34892153E-15
77 5 -0.75005310E-05 0.16499726E-06 -0.28271466E-05 0.19166609E-11
78 4 0.32354224E-01 0.66949565E-03 0.10283773E-01 -0.11111676E-05
79 3 -1.8201547 0.67148336E-01 -0.62076152 0.38788549E-02
80 2 21.173821 0.53241617 7.5279938 -0.97325542E-01
81 1 -64.420211 0.46601667 -21.697519 0.64629334
82 0 46.121323 0.20873329E-01 15.867130  
83 5 -0.15664505E-06 0.43005807E-07 -0.15664505E-06 0.11899247E-09
84 4 0.10791049E-02 0.34140917E-03 0.10791049E-02 -0.15677434E-05
85 3 -0.39592122 0.90314630E-01 -0.39592122 0.13116776E-02
86 2 11.651569 1.6702487 11.651569 -0.78737360E-01
87 1 -51.506798 3.1050242 -51.506798 0.66829999
88 0 45.538973 0.42297268 45.538973  
89 8 0.10972129E-06 0.13118744E-13 0.57415395E-12 -0.16121901E-12
90 7 -0.25702593E-04 0.79302418E-09 -0.11209345E-05 0.31491488E-06
91 6 0.16732899E-02 0.55842834E-06 0.21835020E-03 -0.62999473E-04
92 5 -0.40973943E-01 0.43793696E-04 -0.11788181E-01 0.36016799E-02
93 4 0.43752526 0.66464187E-03 0.21386917 -0.72376639E-01
94 3 -2.2272953 0.23440260E-02 -1.3884299 0.54574706
95 2 5.4333867 0.19014595E-02 3.6315139 -1.6855834
96 1 -6.0131296 0.26548191E-03 -4.0346078 2.1907513
97 0 2.4140608 0.16612988E-05 1.5944472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {Btu/h-ft2-F} SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 EXTERIOR WINDOW 12 1 VerySmooth 0.300 0.217 0.129 0.883
2 INTERIOR WINDOW 13 1 VerySmooth 0.300 0.217 0.129 0.883
3 WINDOW_W_BLINDS 18 2 VerySmooth 0.300 0.208 2.552E-002 0.133
4 TDD DOME 22 1 VerySmooth 1.071 0.929 0.920 0.920
5 TDD DIFFUSER 23 1 VerySmooth 1.077 0.906 0.900 0.900


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {ft} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLASS SpectralAverage   0.13728 0.12813 0.66698 0.66698 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.10138 1.00000 No
2 GLASS SpectralAverage   0.13728 0.12813 0.66698 0.66698 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.10138 1.00000 No
3 GLASS SpectralAverage   0.13728 0.12813 0.66698 0.66698 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.10138 1.00000 No
4 CLEAR ACRYLIC PLASTIC SpectralAverage   0.00984 0.92000 5.00000E-002 5.00000E-002 0.92000 5.00000E-002 5.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No
5 DIFFUSING ACRYLIC PLASTIC SpectralAverage   0.00722 0.90000 8.00000E-002 8.00000E-002 0.90000 8.00000E-002 8.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No


WindowMaterial:Blind

Material Name Slat Width {ft} Slat Separation {ft} Slat Thickness {ft} Slat Angle {deg} Slat Beam Solar Transmittance Slat Beam Solar Front Reflectance Blind To Glass Distance {ft}
1 INT_BLIND 0.0820 0.0615 0.0033 45.000 0.000 0.500 0.164


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 20 15000. SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Heat Pump Water Heater Information

Type Name Volume {ft3} Maximum Capacity {Btu/h} Standard Rated Recovery Efficiency Standard Rated Energy Factor "DX Coil Total Cooling Rate {W HPWH Only}"
1 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 6.9509 4259.9 0.000 0.0000 785  
2 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 6.9509 4259.9 0.000 0.0000 785  
3 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 6.9509 4259.9 0.000 0.0000 785  
4 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 6.9509 4259.9 0.000 0.0000 785  
5 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 6.9509 4259.9 0.000 0.0000 785  
6 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 6.9509 4259.9 0.000 0.0000 785  
7 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 6.9509 4259.9 0.000 0.0000 785  
8 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 6.9509 4259.9 0.000 0.0000 785  
9 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 6.9509 4259.9 0.000 0.0000 785  
10 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 6.9509 4259.9 0.000 0.0000 785  
11 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 6.9509 4259.9 0.000 0.0000 785  
12 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 6.9509 4259.9 0.000 0.0000 785  
13 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 6.9509 4259.9 0.000 0.0000 785  
14 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 6.9509 4259.9 0.000 0.0000 785  
15 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 6.9509 4259.9 0.000 0.0000 785  
16 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_TOPFLOOR 6.9509 4259.9 0.000 0.0000 785  
17 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_TOPFLOOR 6.9509 4259.9 0.000 0.0000 785  
18 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_TOPFLOOR 6.9509 4259.9 0.000 0.0000 785  


Water Heater Stratified Node Information

Node Number Height {ft} Volume {ft3} Maximum Capacity {Btu/h} Off-Cycle UA {Btu/h-F} On-Cycle UA {Btu/h-F} Number Of Inlets Number Of Outlets
1 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
2 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
3 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
4 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
5 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
6 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
7 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
8 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
9 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
10 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
11 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
12 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
13 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
14 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
15 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
16 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
17 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1
18 1 5.2299 6.9509 0.000 2.9246 2.9246 1 1


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
2 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
3 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
4 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
5 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
6 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
7 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
8 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
9 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
10 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
11 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
12 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
13 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
14 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
15 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
16 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
17 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
18 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
19 ATTICVENT ALWAYS_AVAIL ATTIC 7802.66 0.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
20 CRAWLVENT ALWAYS_AVAIL CRAWLSPACE 7794.37 0.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/person Area {ft3/min-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {psi} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{F}/Schedule Maximum Indoor Temperature{F}/Schedule Delta Temperature{F}/Schedule Minimum Outdoor Temperature{F}/Schedule Maximum Outdoor Temperature{F}/Schedule Maximum WindSpeed{ft/min}
1 VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
2 VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
3 VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
4 VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
5 VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
6 VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
7 VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
8 VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
9 VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
10 VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
11 VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
12 VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
13 VENTILATION_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
14 VENTILATION_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
15 VENTILATION_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
16 VENTILATION_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
17 VENTILATION_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
18 VENTILATION_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CRAWLSPACE Mixing/Well-Stirred
2 BREEZEWAY Mixing/Well-Stirred
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
15 ATTIC Mixing/Well-Stirred
16 LIVING_UNIT3_BACKROW_TOPFLOOR Mixing/Well-Stirred
17 LIVING_UNIT3_FRONTROW_TOPFLOOR Mixing/Well-Stirred
18 LIVING_UNIT1_FRONTROW_TOPFLOOR Mixing/Well-Stirred
19 LIVING_UNIT2_BACKROW_TOPFLOOR Mixing/Well-Stirred
20 LIVING_UNIT2_FRONTROW_TOPFLOOR Mixing/Well-Stirred
21 LIVING_UNIT1_BACKROW_TOPFLOOR Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {Btu/h} User Des Load {Btu/h} Calc Des Air Flow Rate {ft3/min} User Des Air Flow Rate {ft3/min} Design Day Name Date/Time of Peak Temperature at Peak {F} Humidity Ratio at Peak {lbWater/lbDryAir} Floor Area {ft2} # Occupants Calc Outdoor Air Flow Rate {ft3/min} Calc DOAS Heat Addition Rate {Btu/h}
1 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Cooling 8107.86255 8107.86255 397.58470 397.58470 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 96.52401 0.00687 1200.55323 2.00000 44.99491 0.00000
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Heating 5201.51904 5201.51904 109.18177 109.18177 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Cooling 4795.62049 4795.62049 235.16946 235.16946 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 91.45400 0.00686 1200.55323 2.00000 44.99491 0.00000
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Heating 3634.70486 3634.70486 76.29448 76.29448 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Cooling 5770.92602 5770.92602 282.98725 282.98725 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 95.74399 0.00687 1200.55323 2.00000 44.99491 0.00000
6 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Heating 5202.21396 5202.21396 109.19638 109.19638 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
7 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Cooling 8000.08992 8000.08992 392.28809 392.28809 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 96.13400 0.00687 1200.55323 2.00000 44.99491 0.00000
8 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Heating 5205.41513 5205.41513 109.26355 109.26355 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
9 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Cooling 4774.48499 4774.48499 234.13133 234.13133 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 91.45400 0.00686 1200.55323 2.00000 44.99491 0.00000
10 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Heating 3636.07416 3636.07416 76.32308 76.32308 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
11 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Cooling 5727.58870 5727.58870 280.86861 280.86861 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 94.37900 0.00687 1200.55323 2.00000 44.99491 0.00000
12 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Heating 5200.92320 5200.92320 109.16927 109.16927 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
13 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Cooling 7668.11502 7668.11502 376.01690 376.01690 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 96.13400 0.00687 1200.55323 2.00000 44.99491 0.00000
14 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Heating 3609.39628 3609.39628 75.76524 75.76524 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
15 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Cooling 4497.10229 4497.10229 220.52963 220.52963 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 91.45400 0.00686 1200.55323 2.00000 44.99491 0.00000
16 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Heating 2055.80445 2055.80445 43.15423 44.99491 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
17 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Cooling 5521.29635 5521.29635 270.74149 270.74149 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 95.19800 0.00687 1200.55323 2.00000 44.99491 0.00000
18 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Heating 3611.38182 3611.38182 75.80698 75.80698 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
19 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Cooling 7575.06432 7575.06432 371.46182 371.46182 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 95.74399 0.00687 1200.55323 2.00000 44.99491 0.00000
20 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Heating 3612.22749 3612.22749 75.82478 75.82478 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
21 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Cooling 4472.95195 4472.95195 219.34319 219.34319 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 91.45400 0.00686 1200.55323 2.00000 44.99491 0.00000
22 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Heating 2056.24931 2056.24931 43.16355 44.99491 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
23 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Cooling 5460.62110 5460.62110 267.77539 267.77539 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 93.79400 0.00687 1200.55323 2.00000 44.99491 0.00000
24 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Heating 3609.40239 3609.40239 75.76546 75.76546 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
25 LIVING_UNIT3_BACKROW_TOPFLOOR Cooling 6472.84467 6472.84467 317.41521 317.41521 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 93.79400 0.00687 1200.55323 2.00000 44.99491 0.00000
26 LIVING_UNIT3_BACKROW_TOPFLOOR Heating 5119.13712 5119.13712 107.45253 107.45253 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
27 LIVING_UNIT3_FRONTROW_TOPFLOOR Cooling 6382.97126 6382.97126 313.00844 313.00844 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 93.79400 0.00687 1200.55323 2.00000 44.99491 0.00000
28 LIVING_UNIT3_FRONTROW_TOPFLOOR Heating 5120.69350 5120.69350 107.48516 107.48516 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
29 LIVING_UNIT1_FRONTROW_TOPFLOOR Cooling 8528.58822 8528.58822 418.22029 418.22029 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 96.13400 0.00687 1200.55323 2.00000 44.99491 0.00000
30 LIVING_UNIT1_FRONTROW_TOPFLOOR Heating 5118.40401 5118.40401 107.43706 107.43706 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
31 LIVING_UNIT2_BACKROW_TOPFLOOR Cooling 5482.34360 5482.34360 268.83471 268.83471 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 91.45400 0.00686 1200.55323 2.00000 44.99491 0.00000
32 LIVING_UNIT2_BACKROW_TOPFLOOR Heating 3556.99407 3556.99407 74.66313 74.66313 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
33 LIVING_UNIT2_FRONTROW_TOPFLOOR Cooling 5412.06783 5412.06783 265.40251 265.40251 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 91.45400 0.00686 1200.55323 2.00000 44.99491 0.00000
34 LIVING_UNIT2_FRONTROW_TOPFLOOR Heating 3556.79556 3556.79556 74.65910 74.65910 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
35 LIVING_UNIT1_BACKROW_TOPFLOOR Cooling 8587.83657 8587.83657 421.12283 421.12283 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 95.74399 0.00687 1200.55323 2.00000 44.99491 0.00000
36 LIVING_UNIT1_BACKROW_TOPFLOOR Heating 5120.35448 5120.35448 107.47795 107.47795 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [ft3/min] User Des Air Flow Rate [ft3/min] Design Day Name Date/Time of Peak
1 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Cooling Sensible 2607.75 397.58470 397.58470 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Heating Sensible 2113.41 109.18177 109.18177 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
3 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Cooling Sensible 1588.52 235.16946 235.16946 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Heating Sensible 1660.89 76.29448 76.29448 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
5 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Cooling Sensible 1923.27 282.98725 282.98725 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Heating Sensible 2113.61 109.19638 109.19638 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
7 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Cooling Sensible 2571.80 392.28809 392.28809 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Heating Sensible 2114.53 109.26355 109.26355 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
9 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Cooling Sensible 1582.42 234.13133 234.13133 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Heating Sensible 1661.29 76.32308 76.32308 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
11 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Cooling Sensible 1893.86 280.86861 280.86861 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Heating Sensible 2113.23 109.16927 109.16927 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
13 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Cooling Sensible 2475.94 376.01690 376.01690 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Heating Sensible 1653.60 75.76524 75.76524 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
15 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Cooling Sensible 1502.33 220.52963 220.52963 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Heating Sensible 1230.24 44.99491 44.99491 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00
17 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Cooling Sensible 1844.43 270.74149 270.74149 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
18 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Heating Sensible 1654.17 75.80698 75.80698 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
19 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Cooling Sensible 2444.24 371.46182 371.46182 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
20 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Heating Sensible 1654.42 75.82478 75.82478 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
21 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Cooling Sensible 1495.35 219.34319 219.34319 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
22 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Heating Sensible 1230.24 44.99491 44.99491 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00
23 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Cooling Sensible 1809.52 267.77539 267.77539 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
24 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Heating Sensible 1653.60 75.76546 75.76546 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
25 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Cooling Sensible 2724.41 418.22029 418.22029 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
26 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Heating Sensible 2089.40 107.43706 107.43706 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
27 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Cooling Sensible 1766.53 265.40251 265.40251 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
28 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Heating Sensible 1638.39 74.65910 74.65910 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
29 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Cooling Sensible 2075.86 313.00844 313.00844 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
30 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Heating Sensible 2090.06 107.48516 107.48516 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
31 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Cooling Sensible 2736.69 421.12283 421.12283 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
32 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Heating Sensible 2089.96 107.47795 107.47795 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
33 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Cooling Sensible 1786.82 268.83471 268.83471 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
34 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Heating Sensible 1638.45 74.66313 74.66313 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
35 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Cooling Sensible 2101.81 317.41521 317.41521 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
36 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Heating Sensible 2089.61 107.45253 107.45253 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
2 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
3 Fan:OnOff OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
4 Fan:OnOff OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
5 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
6 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 397.58470
7 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
8 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
9 Fan:OnOff OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
10 Fan:OnOff OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
11 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
12 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 235.16946
13 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
14 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
15 Fan:OnOff OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
16 Fan:OnOff OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
17 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
18 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 282.98725
19 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
20 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
21 Fan:OnOff OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
22 Fan:OnOff OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
23 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
24 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 392.28809
25 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
26 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
27 Fan:OnOff OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
28 Fan:OnOff OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
29 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
30 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 234.13133
31 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
32 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
33 Fan:OnOff OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
34 Fan:OnOff OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
35 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
36 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 280.86861
37 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
38 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
39 Fan:OnOff OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
40 Fan:OnOff OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
41 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
42 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 376.01690
43 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
44 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
45 Fan:OnOff OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
46 Fan:OnOff OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
47 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
48 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 220.52963
49 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
50 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
51 Fan:OnOff OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
52 Fan:OnOff OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
53 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
54 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 270.74149
55 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
56 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
57 Fan:OnOff OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
58 Fan:OnOff OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
59 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
60 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 371.46182
61 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
62 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
63 Fan:OnOff OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
64 Fan:OnOff OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
65 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
66 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 219.34319
67 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
68 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
69 Fan:OnOff OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
70 Fan:OnOff OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
71 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
72 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 267.77539
73 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
74 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
75 Fan:OnOff OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
76 Fan:OnOff OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
77 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
78 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 317.41521
79 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
80 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
81 Fan:OnOff OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
82 Fan:OnOff OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
83 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
84 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 313.00844
85 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
86 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
87 Fan:OnOff OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
88 Fan:OnOff OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
89 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
90 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 418.22029
91 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
92 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
93 Fan:OnOff OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
94 Fan:OnOff OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
95 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
96 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 268.83471
97 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
98 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
99 Fan:OnOff OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
100 Fan:OnOff OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
101 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
102 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 265.40251
103 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
104 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
105 Fan:OnOff OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
106 Fan:OnOff OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
107 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
108 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 421.12283
109 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 397.58470
110 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 397.58470
111 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 397.58470
112 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 397.58470
113 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 397.58470
114 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 397.58470
115 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
116 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
117 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 235.16946
118 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 235.16946
119 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 235.16946
120 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 235.16946
121 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 235.16946
122 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 235.16946
123 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
124 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
125 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 282.98725
126 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 282.98725
127 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 282.98725
128 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 282.98725
129 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 282.98725
130 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 282.98725
131 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
132 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
133 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 392.28809
134 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 392.28809
135 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 392.28809
136 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 392.28809
137 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 392.28809
138 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 392.28809
139 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
140 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
141 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 234.13133
142 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 234.13133
143 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 234.13133
144 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 234.13133
145 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 234.13133
146 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 234.13133
147 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
148 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
149 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 280.86861
150 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 280.86861
151 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 280.86861
152 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 280.86861
153 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 280.86861
154 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 280.86861
155 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
156 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
157 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 376.01690
158 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 376.01690
159 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 376.01690
160 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 376.01690
161 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 376.01690
162 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 376.01690
163 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
164 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
165 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 220.52963
166 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 220.52963
167 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 220.52963
168 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 220.52963
169 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 220.52963
170 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 220.52963
171 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
172 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
173 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 270.74149
174 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 270.74149
175 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 270.74149
176 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 270.74149
177 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 270.74149
178 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 270.74149
179 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
180 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
181 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 371.46182
182 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 371.46182
183 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 371.46182
184 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 371.46182
185 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 371.46182
186 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 371.46182
187 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
188 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
189 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 219.34319
190 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 219.34319
191 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 219.34319
192 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 219.34319
193 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 219.34319
194 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 219.34319
195 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
196 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
197 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 267.77539
198 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 267.77539
199 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 267.77539
200 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 267.77539
201 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 267.77539
202 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 267.77539
203 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
204 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
205 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 418.22029
206 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 418.22029
207 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 418.22029
208 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 418.22029
209 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 418.22029
210 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 418.22029
211 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
212 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
213 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 265.40251
214 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 265.40251
215 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 265.40251
216 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 265.40251
217 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 265.40251
218 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 265.40251
219 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
220 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
221 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 313.00844
222 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 313.00844
223 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 313.00844
224 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 313.00844
225 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 313.00844
226 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 313.00844
227 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
228 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
229 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 421.12283
230 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 421.12283
231 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 421.12283
232 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 421.12283
233 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 421.12283
234 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 421.12283
235 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
236 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
237 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 268.83471
238 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 268.83471
239 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 268.83471
240 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 268.83471
241 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 268.83471
242 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 268.83471
243 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
244 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
245 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 317.41521
246 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 317.41521
247 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 317.41521
248 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 317.41521
249 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 317.41521
250 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 317.41521
251 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
252 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
253 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 397.58470
254 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 235.16946
255 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 282.98725
256 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 392.28809
257 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 234.13133
258 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 280.86861
259 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 376.01690
260 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 220.52963
261 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 270.74149
262 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 371.46182
263 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 219.34319
264 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 267.77539
265 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 418.22029
266 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 265.40251
267 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 313.00844
268 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 421.12283
269 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 268.83471
270 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 317.41521
271 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 397.58470
272 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.88782
273 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80077
274 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 397.58470
275 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 397.58470
276 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 397.58470
277 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 10653.87351
278 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.88782
279 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 7210.94223
280 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
281 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 397.58470
282 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 397.58470
283 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 10653.87351
284 Coil:Heating:Electric SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 7210.94223
285 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 235.16946
286 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.53027
287 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80022
288 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 235.16946
289 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 235.16946
290 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 235.16946
291 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 6363.24908
292 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.53027
293 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 5666.96787
294 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
295 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 235.16946
296 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 235.16946
297 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 6363.24908
298 Coil:Heating:Electric SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 5666.96787
299 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 282.98725
300 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.64686
301 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80032
302 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 282.98725
303 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 282.98725
304 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 282.98725
305 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 7762.31283
306 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.64686
307 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 7211.62702
308 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
309 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 282.98725
310 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 282.98725
311 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 7762.31283
312 Coil:Heating:Electric SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 7211.62702
313 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 392.28809
314 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.87572
315 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80089
316 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 392.28809
317 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 392.28809
318 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 392.28809
319 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 10508.66097
320 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.87572
321 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 7214.78158
322 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
323 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 392.28809
324 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 392.28809
325 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 10508.66097
326 Coil:Heating:Electric SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 7214.78158
327 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 234.13133
328 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.52819
329 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80004
330 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 234.13133
331 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 234.13133
332 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 234.13133
333 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 6338.29610
334 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.52819
335 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 5668.31722
336 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
337 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 234.13133
338 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 234.13133
339 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 6338.29610
340 Coil:Heating:Electric SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 5668.31722
341 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 280.86861
342 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.63684
343 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80022
344 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 280.86861
345 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 280.86861
346 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 280.86861
347 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 7642.07566
348 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.63684
349 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 7210.35506
350 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
351 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 280.86861
352 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 280.86861
353 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 7642.07566
354 Coil:Heating:Electric SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 7210.35506
355 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 376.01690
356 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.84593
357 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80006
358 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 376.01690
359 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 376.01690
360 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 376.01690
361 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 10151.11831
362 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.84593
363 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 5642.08777
364 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
365 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 376.01690
366 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 376.01690
367 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 10151.11831
368 Coil:Heating:Electric SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 5642.08777
369 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 220.52963
370 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.50439
371 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80011
372 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 220.52963
373 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 220.52963
374 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 220.52963
375 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 6052.62087
376 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.50439
377 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 4197.56735
378 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
379 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 220.52963
380 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 220.52963
381 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 6052.62087
382 Coil:Heating:Electric SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 4197.56735
383 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 270.74149
384 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.61169
385 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80052
386 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 270.74149
387 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 270.74149
388 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 270.74149
389 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 7340.30561
390 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.61169
391 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 5644.04442
392 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
393 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 270.74149
394 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 270.74149
395 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 7340.30561
396 Coil:Heating:Electric SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 5644.04442
397 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 371.46182
398 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.83490
399 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80039
400 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 371.46182
401 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 371.46182
402 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 371.46182
403 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 10018.83917
404 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.83490
405 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 5644.87776
406 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
407 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 371.46182
408 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 371.46182
409 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 10018.83917
410 Coil:Heating:Electric SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 5644.87776
411 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 219.34319
412 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.50204
413 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80085
414 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 219.34319
415 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 219.34319
416 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 219.34319
417 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 6024.52350
418 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.50204
419 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 4197.56735
420 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
421 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 219.34319
422 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 219.34319
423 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 6024.52350
424 Coil:Heating:Electric SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 4197.56735
425 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 267.77539
426 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.61127
427 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80080
428 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 267.77539
429 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 267.77539
430 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 267.77539
431 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 7335.23426
432 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.61127
433 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 5642.09381
434 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
435 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 267.77539
436 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 267.77539
437 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 7335.23426
438 Coil:Heating:Electric SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 5642.09381
439 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 418.22029
440 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.92951
441 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80049
442 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 418.22029
443 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 418.22029
444 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 418.22029
445 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 11154.10154
446 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.92951
447 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 7129.03792
448 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
449 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 418.22029
450 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 418.22029
451 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 11154.10154
452 Coil:Heating:Electric SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 7129.03792
453 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 265.40251
454 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.59214
455 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80007
456 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 265.40251
457 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 265.40251
458 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 265.40251
459 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 7105.65808
460 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.59214
461 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 5590.19354
462 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
463 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 265.40251
464 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 265.40251
465 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 7105.65808
466 Coil:Heating:Electric SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 5590.19354
467 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 313.00844
468 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.70058
469 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80091
470 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 313.00844
471 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 313.00844
472 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 313.00844
473 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 8406.97140
474 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.70058
475 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 7131.29403
476 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
477 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 313.00844
478 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 313.00844
479 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 8406.97140
480 Coil:Heating:Electric SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 7131.29403
481 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 421.12283
482 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.93555
483 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
484 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 421.12283
485 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 421.12283
486 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 421.12283
487 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 11226.58112
488 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.93555
489 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_TOPFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 7130.95997
490 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
491 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 421.12283
492 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 421.12283
493 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 11226.58112
494 Coil:Heating:Electric SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 7130.95997
495 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 268.83471
496 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.59917
497 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80047
498 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 268.83471
499 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 268.83471
500 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 268.83471
501 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 7190.05748
502 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.59917
503 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_TOPFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 5590.38915
504 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
505 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 268.83471
506 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 268.83471
507 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 7190.05748
508 Coil:Heating:Electric SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 5590.38915
509 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 317.41521
510 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.70966
511 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80032
512 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 317.41521
513 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 317.41521
514 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 317.41521
515 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 8515.93669
516 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.70966
517 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_TOPFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 7129.76031
518 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
519 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 317.41521
520 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 317.41521
521 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 8515.93669
522 Coil:Heating:Electric SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 7129.76031
523 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
524 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
525 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
526 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
527 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
528 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
529 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
530 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
531 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
532 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
533 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
534 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
535 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
536 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
537 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
538 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
539 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
540 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
541 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
542 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
543 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
544 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
545 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
546 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
547 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
548 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
549 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
550 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
551 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
552 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
553 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
554 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
555 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
556 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
557 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
558 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
559 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
560 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
561 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
562 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
563 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
564 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
565 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
566 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
567 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
568 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
569 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
570 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
571 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
572 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
573 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
574 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
575 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
576 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
577 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
578 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
579 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
580 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
581 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
582 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
583 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
584 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
585 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
586 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
587 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
588 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
589 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
590 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
591 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
592 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
593 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
594 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
595 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
596 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
597 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
598 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
599 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
600 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
601 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
602 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
603 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
604 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
605 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
606 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
607 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
608 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
609 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
610 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
611 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
612 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
613 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
614 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
615 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
616 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
617 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
618 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
619 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
620 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
621 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
622 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
623 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
624 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
625 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
626 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
627 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
628 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
629 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
630 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
631 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
632 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
633 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
634 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
635 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
636 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
637 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
638 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
639 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
640 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
641 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
642 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
643 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
644 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
645 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
646 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
647 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
648 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {ton} Standard Rated Net COP {Btuh/Btuh} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 0.8 3.26 11.12 11.63 11.00 10.88
2 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 0.5 3.27 11.14 11.66 11.03 10.91
3 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 0.6 3.28 11.18 11.69 11.06 10.96
4 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 0.8 3.26 11.12 11.63 11.00 10.88
5 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 0.5 3.27 11.15 11.66 11.03 10.92
6 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 0.6 3.27 11.16 11.67 11.04 10.93
7 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 0.8 3.26 11.14 11.65 11.02 10.91
8 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 0.5 3.28 11.18 11.69 11.06 10.96
9 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 0.6 3.27 11.15 11.66 11.03 10.92
10 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 0.8 3.26 11.14 11.65 11.02 10.90
11 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 0.5 3.28 11.18 11.70 11.06 10.96
12 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 0.6 3.27 11.17 11.69 11.06 10.96
13 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 0.9 3.26 11.11 11.62 10.99 10.87
14 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 0.6 3.26 11.12 11.63 11.00 10.88
15 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 0.7 3.26 11.13 11.64 11.01 10.89
16 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 0.9 3.26 11.11 11.62 10.99 10.86
17 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 0.6 3.26 11.12 11.63 11.00 10.88
18 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 0.7 3.26 11.12 11.64 11.01 10.89


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {Btu/h} Low Temperature Heating (net) Rating Capacity {Btu/h} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 11162.0 6215.3 7.91 4
2 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 6664.0 3709.5 7.88 4
3 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 8124.3 4520.2 7.75 4
4 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 11009.8 6130.7 7.91 4
5 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 6637.7 3694.9 7.88 4
6 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 8001.1 4453.0 7.73 4
7 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 10631.8 5918.5 7.90 4
8 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 6334.7 3524.3 7.90 4
9 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 7686.2 4278.3 7.69 4
10 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 10493.6 5842.0 7.89 4
11 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 6305.0 3507.9 7.90 4
12 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 7677.7 4271.8 7.69 4
13 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 11688.5 6509.8 7.89 4
14 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 7444.6 4145.6 7.83 4
15 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 8807.1 4903.7 7.84 4
16 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR 11764.6 6552.1 7.89 4
17 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR 7533.7 4195.4 7.66 4
18 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR 8921.7 4967.5 7.84 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB SizingPeriod:DesignDay 12/21 12/21 WinterDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
2 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB SizingPeriod:DesignDay 07/21 07/21 SummerDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
3 ANNUAL WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day Yes Yes No Yes Yes Clark and Allen


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 No SizingPeriod:DesignDay    
2 No SizingPeriod:DesignDay    
3 No      


Environment:WarmupDays

NumberofWarmupDays
1 6
2 25
3 25


Environment:Design Day Data

Max Dry-Bulb Temp {F} Temp Range {dC} Temp Range Ind Type Hum Ind Type Hum Ind Value at Max Temp Hum Ind Units Pressure {psi} Wind Direction {deg CW from N} Wind Speed {ft/min} Clearness Rain Snow
1 22.64 0.00 DefaultMultipliers Wetbulb -5.20 {C} 13. 20 433.1 0.00 No No
2 100.58 13.00 DefaultMultipliers Wetbulb 18.10 {C} 13. 280 767.8 0.00 No No


Environment:Design Day Misc

DayOfYear ASHRAE A Coeff ASHRAE B Coeff ASHRAE C Coeff Solar Constant-Annual Variation Eq of Time {minutes} Solar Declination Angle {deg} Solar Model
1 355 1232.8 0.1424 5.7719E-002 1.0 2.45 -24.. ASHRAEClearSky
2 202 1084.4 0.2082 0.1365 1.0 -6.23 20.6 ASHRAETau


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaF} Std Dev Warmup Temperature Difference {deltaF} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {Btu/h} Std Dev Warmup Load Difference {Btu/h} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CRAWLSPACE SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000302472 0.000253893 Pass Pass 0.000000000 0.000000000 Pass Pass
2 BREEZEWAY SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000136942 0.000049688 Pass Pass 0.000000000 0.000000000 Pass Pass
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.016478944 0.032582909 Pass Pass
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.024558467 0.048420592 Pass Pass
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.016477375 0.032579714 Pass Pass
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.016466404 0.032557644 Pass Pass
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.024549122 0.048401339 Pass Pass
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.016482338 0.032589490 Pass Pass
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000060454 0.000220434 Pass Pass 0.023851290 0.046835797 Pass Pass
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000025196 0.000103895 Pass Pass 0.048635057 0.094880104 Pass Pass
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.023844851 0.046508772 Pass Pass
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000046654 0.000178481 Pass Pass 0.023829906 0.046739038 Pass Pass
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000036997 0.000150585 Pass Pass 0.048742523 0.095123543 Pass Pass
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.023859948 0.046538617 Pass Pass
15 ATTIC SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000066488 0.000054708 Pass Pass 0.000000000 0.000000000 Pass Pass
16 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.016293137 0.030174827 Pass Pass
17 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.016287987 0.030165097 Pass Pass
18 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.016295829 0.030186158 Pass Pass
19 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.024422771 0.045202909 Pass Pass
20 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.024424597 0.045206210 Pass Pass
21 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000611 0.000004813 Pass Pass 0.016289062 0.030164545 Pass Pass
22 CRAWLSPACE SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.232827413 0.137968632 Pass Pass 0.000000000 0.000000000 Pass Pass
23 BREEZEWAY SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.103066769 0.056402314 Pass Pass 0.000000000 0.000000000 Pass Pass
24 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.005697604 0.022849569 Pass Pass 0.078252726 0.039921398 Pass Pass
25 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.014024170 0.039380349 Pass Pass 0.086717260 0.227191534 Pass Pass
26 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.020290488 0.070569179 Pass Fail 0.070466880 0.082793364 Pass Fail
27 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.005459228 0.021170892 Pass Pass 0.076880943 0.037816131 Pass Pass
28 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.011273770 0.034232818 Pass Pass 0.085128690 0.226436720 Pass Pass
29 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.014571115 0.048836228 Pass Fail 0.068961089 0.075683283 Pass Fail
30 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.004415143 0.017444666 Pass Pass 0.067780820 0.033489287 Pass Pass
31 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.009588503 0.028943731 Pass Pass 0.074602019 0.216542431 Pass Fail
32 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.022009265 0.073633355 Pass Pass 0.063587665 0.078759629 Pass Pass
33 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.004291566 0.016033771 Pass Pass 0.067458853 0.033158851 Pass Pass
34 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.007854877 0.024446280 Pass Pass 0.068358237 0.173112997 Pass Fail
35 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.013852970 0.042747871 Pass Pass 0.061088436 0.068738976 Pass Pass
36 ATTIC SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.592902689 0.451146689 Pass Pass 0.000000000 0.000000000 Pass Pass
37 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.009857937 0.030359077 Pass Pass 0.057355626 0.052657026 Pass Pass
38 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.015514467 0.051834904 Pass Pass 0.060529774 0.067529146 Pass Fail
39 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.004617774 0.017668829 Pass Pass 0.067661738 0.030856442 Pass Pass
40 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.005633184 0.015121343 Pass Pass 0.050989613 0.040115115 Pass Pass
41 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.006217786 0.016736438 Pass Pass 0.051033600 0.044730604 Pass Pass
42 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.004388496 0.015873611 Pass Pass 0.067336119 0.031321997 Pass Pass
43 CRAWLSPACE RunPeriod: ANNUAL 0.293893352 0.191823315 Pass Pass 0.000000000 0.000000000 Pass Pass
44 BREEZEWAY RunPeriod: ANNUAL 0.063832591 0.039053745 Pass Pass 0.000000000 0.000000000 Pass Pass
45 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.128639373 0.223356142 Pass Pass 1.738713825 6.623930986 Fail Fail
46 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.141961768 0.244993994 Pass Pass 2.183179013 7.911821607 Fail Pass
47 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.168763669 0.271990625 Pass Pass 3.869905353 0.278504E+02 Fail Pass
48 LIVING_UNIT1_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.079053510 0.179077332 Pass Pass 1.091777846 2.971759498 Fail Pass
49 LIVING_UNIT2_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.068867957 0.116457020 Pass Pass 3.103120446 0.136867E+02 Pass Pass
50 LIVING_UNIT3_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.056985927 0.083666567 Pass Pass 2.307787274 0.920081E+01 Fail Pass
51 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.112255213 0.205394721 Pass Pass 1.063985496 3.316207029 Fail Pass
52 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.178046395 0.245636690 Pass Pass 1.319817150 3.476692795 Fail Pass
53 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.169052282 0.288185931 Pass Pass 0.847399639 2.639808502 Fail Pass
54 LIVING_UNIT1_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.126222480 0.231786851 Pass Pass 0.873578118 2.043386869 Fail Fail
55 LIVING_UNIT2_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.128584263 0.134662347 Pass Pass 1.566321564 3.556574705 Fail Pass
56 LIVING_UNIT3_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.078562385 0.113323393 Pass Pass 2.374948070 0.147705E+02 Fail Pass
57 ATTIC RunPeriod: ANNUAL 0.535185909 0.458674444 Pass Pass 0.000000000 0.000000000 Pass Pass
58 LIVING_UNIT3_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.056537326 0.089497704 Pass Pass 1.152044861 2.569820744 Fail Pass
59 LIVING_UNIT3_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.157970116 0.269210714 Pass Pass 1.323003517 4.893664802 Fail Fail
60 LIVING_UNIT1_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.116450654 0.224363082 Pass Pass 1.149342882 3.823923645 Fail Pass
61 LIVING_UNIT2_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.071532989 0.113392205 Pass Pass 1.345921739 3.324179645 Fail Pass
62 LIVING_UNIT2_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.177911132 0.251295883 Pass Pass 1.260439128 3.175900431 Fail Pass
63 LIVING_UNIT1_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.090178248 0.207957744 Pass Pass 1.739044808 0.108927E+02 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [kBtu] 2719554.73 233182.29 0.00 0.00 295899.19 3248653.12



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 22.64 0.00 22.64 Wetbulb [F] 433.09 20.00
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 100.58 23.40 64.58 Wetbulb [F] 767.75 280.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF CRAWL WALL 0.30 0.776 2.276 59.96 59.96 180.00 90.00 S
BGWALL_LOWER_LDF CRAWL WALL 0.30 0.893 2.276 239.83 239.83 180.00 90.00 S
BGWALL_UPPER_SDR CRAWL WALL 0.30 0.776 2.276 32.56 32.56 90.00 90.00 E
BGWALL_LOWER_SDR CRAWL WALL 0.30 0.893 2.276 130.22 130.22 90.00 90.00 E
BGWALL_UPPER_LDB CRAWL WALL 0.30 0.776 2.276 59.96 59.96 0.00 90.00 N
BGWALL_LOWER_LDB CRAWL WALL 0.30 0.893 2.276 239.83 239.83 0.00 90.00 N
BGWALL_UPPER_SDL CRAWL WALL 0.30 0.776 2.276 32.56 32.56 270.00 90.00 W
BGWALL_LOWER_SDL CRAWL WALL 0.30 0.893 2.276 130.22 130.22 270.00 90.00 W
BGFLOOR INTERIOR FLOOR 0.30 0.235 0.300 7794.39 7794.39 0.00 180.00  
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.39 599.39 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.39 599.39 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.39 599.39 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S


Opaque Interior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
iz-FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT1_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT2_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT3_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
BREEZEWAYROOF INTERIOR CEILING 0.30 0.022 0.022 599.39 599.39 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
iz-BREEZEWAYROOF ATTIC FLOOR 0.30 0.022 0.022 599.39 599.39 0.00 180.00  
iz-CEILING_UNIT3_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.217 0.883     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.217 0.883     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.217 0.883     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.217 0.883     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.217 0.883     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.217 0.883     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.217 0.883     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.217 0.883     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.217 0.883     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.217 0.883     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.217 0.883     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.217 0.883     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.217 0.883     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.217 0.883     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.217 0.883     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.217 0.883     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.217 0.883     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.217 0.883     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.217 0.883     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.217 0.883     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.217 0.883     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.217 0.883     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.217 0.883     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.217 0.883     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.217 0.883     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.217 0.883     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.217 0.883     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.217 0.883     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.300 0.217 0.883     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.300 0.217 0.883     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.300 0.217 0.883              
North Total or Average           531.68 0.300 0.217 0.883              
Non-North Total or Average           1595.05 0.300 0.217 0.883              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR


Interior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.2915 43219.92 12599.76               11336.81


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
Exterior Lighting Total 1257.69           5508.71



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10653.87 8531.25 2122.62 0.80 4.07    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   6363.25 5092.00 1271.25 0.80 4.07    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   7762.31 6212.34 1549.97 0.80 4.07    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10508.66 8416.29 2092.37 0.80 4.07    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   6338.30 5070.92 1267.38 0.80 4.07    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   7642.08 6115.33 1526.75 0.80 4.07    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10151.12 8121.53 2029.59 0.80 4.07    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   6052.62 4842.74 1209.88 0.80 4.07    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   7340.31 5876.04 1464.27 0.80 4.07    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10018.84 8019.00 1999.84 0.80 4.07    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   6024.52 4824.71 1199.81 0.80 4.07    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   7335.23 5874.02 1461.21 0.80 4.07    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11154.10 8928.76 2225.34 0.80 4.07    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   7105.66 5685.04 1420.62 0.80 4.07    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   8406.97 6733.25 1673.72 0.80 4.07    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11226.58 8988.62 2237.96 0.80 4.07    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   7190.06 5755.44 1434.61 0.80 4.07    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   8515.94 6815.44 1700.50 0.80 4.07    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   0.8 3.26 11.12 11.63 11.00 10.88
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.5 3.27 11.14 11.66 11.03 10.91
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.6 3.28 11.18 11.69 11.06 10.96
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   0.8 3.26 11.12 11.63 11.00 10.88
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.5 3.27 11.15 11.66 11.03 10.92
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.6 3.27 11.16 11.67 11.04 10.93
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   0.8 3.26 11.14 11.65 11.02 10.91
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.5 3.28 11.18 11.69 11.06 10.96
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.6 3.27 11.15 11.66 11.03 10.92
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   0.8 3.26 11.14 11.65 11.02 10.90
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.5 3.28 11.18 11.70 11.06 10.96
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.6 3.27 11.17 11.69 11.06 10.96
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   0.9 3.26 11.11 11.62 10.99 10.87
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.6 3.26 11.12 11.63 11.00 10.88
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   0.7 3.26 11.13 11.64 11.01 10.89
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   0.9 3.26 11.11 11.62 10.99 10.86
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.6 3.26 11.12 11.63 11.00 10.88
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   0.7 3.26 11.12 11.64 11.01 10.89
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 11161.9 6215.4 7.91 4
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 6663.8 3709.4 7.88 4
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 8124.1 4520.2 7.75 4
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 11010.0 6130.8 7.91 4
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 6637.6 3694.7 7.88 4
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 8001.1 4452.9 7.73 4
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 10631.7 5918.6 7.90 4
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 6334.6 3524.4 7.90 4
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 7686.4 4278.3 7.69 4
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 10493.6 5841.9 7.89 4
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 6305.0 3507.8 7.90 4
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 7677.6 4271.9 7.69 4
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 11688.5 6509.7 7.89 4
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 7444.8 4145.7 7.83 4
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 8807.0 4903.7 7.84 4
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 11764.6 6552.2 7.89 4
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 7533.6 4195.3 7.66 4
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 8921.6 4967.7 7.84 4
ANSI/AHRI ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   10653.87 3.69
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   7210.94 1.00
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   6363.25 3.69
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   5666.97 1.00
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   7762.31 3.69
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   7211.63 1.00
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   10508.66 3.69
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   7214.78 1.00
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   6338.30 3.69
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   5668.32 1.00
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   7642.08 3.69
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   7210.36 1.00
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   10151.12 3.69
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   5642.09 1.00
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   6052.62 3.69
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   4197.57 1.00
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   7340.31 3.69
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   5644.04 1.00
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   10018.84 3.69
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   5644.88 1.00
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   6024.52 3.69
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   4197.57 1.00
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   7335.23 3.69
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   5642.09 1.00
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   11154.10 3.69
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric   7129.04 1.00
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   7105.66 3.69
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric   5590.19 1.00
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   8406.97 3.69
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric   7131.29 1.00
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   11226.58 3.69
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric   7130.96 1.00
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   7190.06 3.69
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric   5590.39 1.00
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   8515.94 3.69
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric   7129.76 1.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3319.56 3.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.03 44.99 8.04 0.18 0.00 17.66 Ventilation    
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 397.58 149.97 0.38 1.00 2.38 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 235.16 88.70 0.38 1.00 3.19 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 282.99 106.74 0.38 1.00 2.86 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 392.30 147.97 0.38 1.00 2.40 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 234.13 88.31 0.38 1.00 3.19 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 280.86 105.94 0.38 1.00 2.87 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 376.02 141.83 0.38 1.00 2.45 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 220.53 83.18 0.38 1.00 3.31 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 270.74 102.12 0.38 1.00 2.93 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 371.46 140.11 0.38 1.00 2.47 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 219.34 82.73 0.38 1.00 3.33 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 267.77 101.00 0.38 1.00 2.95 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 418.21 157.75 0.38 1.00 2.32 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 265.39 100.10 0.38 1.00 2.96 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 313.00 118.06 0.38 1.00 2.70 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 421.12 158.84 0.38 1.00 2.32 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 268.84 101.40 0.38 1.00 2.94 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 317.41 119.72 0.38 1.00 2.68 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    


Pumps

Type Control Head [psi] Water Flow [gal/min] Electricity Rate [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh] End Use Subcategory
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4259.89 1.00 0.00 0.00
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4259.89 1.00 0.00 0.00
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4259.89 1.00 0.00 0.00
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4259.89 1.00 0.00 0.00
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4259.89 1.00 0.00 0.00
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4259.89 1.00 0.00 0.00
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4259.89 1.00 0.00 0.00
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4259.89 1.00 0.00 0.00
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4259.89 1.00 0.00 0.00
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4259.89 1.00 0.00 0.00
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4259.89 1.00 0.00 0.00
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4259.89 1.00 0.00 0.00
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4259.89 1.00 0.00 0.00
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4259.89 1.00 0.00 0.00
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4259.89 1.00 0.00 0.00
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4259.89 1.00 0.00 0.00
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4259.89 1.00 0.00 0.00
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.95 4259.89 1.00 0.00 0.00



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8107.86 8107.86 6.75 397.582 397.582 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 75.00 75.00 0.00826 96.52 0.00687 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4795.62 4795.62 3.99 235.163 235.163 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00854 91.45 0.00686 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5770.93 5770.93 4.81 282.987 282.987 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 75.00 75.00 0.00834 95.74 0.00687 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8000.09 8000.09 6.66 392.298 392.298 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 75.00 75.00 0.00828 96.13 0.00687 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4774.49 4774.49 3.98 234.127 234.127 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00854 91.45 0.00686 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5727.59 5727.59 4.77 280.862 280.862 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 75.00 75.00 0.00840 94.38 0.00687 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 7668.12 7668.12 6.39 376.021 376.021 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 75.00 75.00 0.00832 96.13 0.00687 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4497.10 4497.10 3.75 220.526 220.526 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00864 91.45 0.00686 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5521.30 5521.30 4.60 270.745 270.745 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 75.00 75.00 0.00827 95.20 0.00687 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 7575.06 7575.06 6.31 371.458 371.458 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 75.00 75.00 0.00834 95.74 0.00687 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4472.95 4472.95 3.73 219.341 219.341 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00864 91.45 0.00686 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5460.62 5460.62 4.55 267.772 267.772 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 75.00 75.00 0.00848 93.79 0.00687 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 6472.84 6472.84 5.39 317.408 317.408 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 75.00 75.00 0.00839 93.79 0.00687 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 6382.97 6382.97 5.32 313.001 313.001 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 75.00 75.00 0.00839 93.79 0.00687 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8528.59 8528.59 7.10 418.214 418.214 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 75.00 75.00 0.00827 96.13 0.00687 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 5482.34 5482.34 4.57 268.838 268.838 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00849 91.45 0.00686 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 5412.07 5412.07 4.51 265.392 265.392 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00850 91.45 0.00686 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8587.84 8587.84 7.15 421.119 421.119 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 75.00 75.00 0.00828 95.74 0.00687 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5201.52 5201.52 4.33 109.182 109.182 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00747 22.64 0.00281 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3634.70 3634.70 3.03 76.294 76.294 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00743 22.64 0.00281 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5202.21 5202.21 4.33 109.196 109.196 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00747 22.64 0.00281 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5205.42 5205.42 4.34 109.264 109.264 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00747 22.64 0.00281 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3636.07 3636.07 3.03 76.323 76.323 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00743 22.64 0.00281 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5200.92 5200.92 4.33 109.169 109.169 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00746 22.64 0.00281 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 3609.40 3609.40 3.01 75.765 75.765 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00799 22.64 0.00281 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2055.80 2055.80 1.71 43.154 44.995 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00839 22.64 0.00281 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 3611.38 3611.38 3.01 75.807 75.807 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00799 22.64 0.00281 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3612.23 3612.23 3.01 75.825 75.825 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00799 22.64 0.00281 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2056.25 2056.25 1.71 43.164 44.995 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00839 22.64 0.00281 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3609.40 3609.40 3.01 75.765 75.765 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00799 22.64 0.00281 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 5119.14 5119.14 4.26 107.453 107.453 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00746 22.64 0.00281 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 5120.69 5120.69 4.27 107.485 107.485 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00746 22.64 0.00281 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 5118.40 5118.40 4.26 107.437 107.437 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00746 22.64 0.00281 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 3556.99 3556.99 2.96 74.663 74.663 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00742 22.64 0.00281 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 3556.80 3556.80 2.96 74.659 74.659 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00742 22.64 0.00281 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 5120.35 5120.35 4.26 107.478 107.478 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00746 22.64 0.00281 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min] Adjusted cooling [ft3/min] Adjusted heating [ft3/min] Adjusted main [ft3/min] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 397.58 397.58 109.18 109.18 397.5825 397.5825 397.5825 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 235.16 235.16 76.29 76.29 235.1630 235.1630 235.1630 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 282.99 282.99 109.20 109.20 282.9869 282.9869 282.9869 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 392.30 392.30 109.26 109.26 392.2980 392.2980 392.2980 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 234.13 234.13 76.32 76.32 234.1266 234.1266 234.1266 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 280.86 280.86 109.17 109.17 280.8624 280.8624 280.8624 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 376.02 376.02 75.77 75.77 376.0209 376.0209 376.0209 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 220.53 220.53 44.99 44.99 220.5255 220.5255 220.5255 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 270.74 270.74 75.81 75.81 270.7447 270.7447 270.7447 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 371.46 371.46 75.82 75.82 371.4581 371.4581 371.4581 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 219.34 219.34 44.99 44.99 219.3413 219.3413 219.3413 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 267.77 267.77 75.77 75.77 267.7723 267.7723 267.7723 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 418.21 418.21 107.44 107.44 418.2139 418.2139 418.2139 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 265.39 265.39 74.66 74.66 265.3919 265.3919 265.3919 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 313.00 313.00 107.49 107.49 313.0005 313.0005 313.0005 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 421.12 421.12 107.48 107.48 421.1194 421.1194 421.1194 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 268.84 268.84 74.66 74.66 268.8381 268.8381 268.8381 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 317.41 317.41 107.45 107.45 317.4077 317.4077 317.4077 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 10653.874 8531.254 397.582455 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 12035.30 11867.56 397.582455 78.79 59.50 0.00809845 53.60 50.01 0.00800000 96.52 0.00686787 63.47 11.3171 75.00 0.00823025 38.6980 8102.04 0.00 10652.05 7933.26
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 10653.874 10653.874 397.582455 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 10653.87 10653.87 397.582455 66.41 53.24 0.00693802 122.00 72.00 0.00800000 22.64 0.00280840 22.64 11.3171 72.00 0.00746501 38.8732 5201.52 0.00 10667.87 10667.87
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 7210.942 7210.942 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7210.94 7210.94 397.582455 66.41 53.24 0.00693802 122.00 72.00 0.00800000 22.64 0.00280840 22.64 11.3171 72.00 0.00746501 38.8732 5201.52 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 6363.249 5092.003 235.162988 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 6931.22 6725.09 235.162988 79.50 59.91 0.00821829 53.60 50.01 0.00800000 91.45 0.00686340 61.87 19.1335 75.00 0.00848083 39.8605 4724.31 0.00 6362.16 4735.85
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 6363.249 6363.249 235.162988 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 6363.25 6363.25 235.162988 62.55 51.05 0.00654386 122.00 72.00 0.00800000 22.64 0.00280840 22.64 19.1335 72.00 0.00742770 38.6806 3634.70 0.00 6371.61 6371.61
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 5666.968 5666.968 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 5666.97 5666.97 235.162988 62.55 51.05 0.00654386 122.00 72.00 0.00800000 22.64 0.00280840 22.64 19.1335 72.00 0.00742770 38.6806 3634.70 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 7762.313 6212.340 282.986943 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 8682.58 8552.70 282.986943 79.65 59.80 0.00810865 53.60 50.01 0.00800000 95.74 0.00686719 63.23 15.9000 75.00 0.00820206 38.5671 5752.46 0.00 7760.98 5777.87
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 7762.313 7762.313 282.986943 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7762.31 7762.31 282.986943 64.15 52.00 0.00672466 122.00 72.00 0.00800000 22.64 0.00280840 22.64 15.9000 72.00 0.00746507 38.8735 5202.21 0.00 7772.51 7772.51
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 7211.627 7211.627 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7211.63 7211.63 282.986943 64.15 52.00 0.00672466 122.00 72.00 0.00800000 22.64 0.00280840 22.64 15.9000 72.00 0.00746507 38.8735 5202.21 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 10508.661 8416.292 392.297975 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 11837.28 11644.04 392.297975 78.77 59.52 0.00811556 53.60 50.01 0.00800000 96.13 0.00686752 63.35 11.4696 75.00 0.00825722 38.8232 7996.63 0.00 10506.86 7826.14
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 10508.661 10508.661 392.297975 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 10508.66 10508.66 392.297975 66.34 53.19 0.00693120 122.00 72.00 0.00800000 22.64 0.00280840 22.64 11.4696 72.00 0.00746533 38.8748 5205.42 0.00 10522.47 10522.47
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 7214.782 7214.782 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7214.78 7214.78 392.297975 66.34 53.19 0.00693120 122.00 72.00 0.00800000 22.64 0.00280840 22.64 11.4696 72.00 0.00746533 38.8748 5205.42 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 6338.296 5070.915 234.126581 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 6903.49 6697.87 234.126581 79.51 59.92 0.00821874 53.60 50.01 0.00800000 91.45 0.00686340 61.87 19.2182 75.00 0.00850244 39.9607 4733.54 0.00 6337.21 4716.41
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 6338.296 6338.296 234.126581 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 6338.30 6338.30 234.126581 62.51 51.03 0.00654008 122.00 72.00 0.00800000 22.64 0.00280840 22.64 19.2182 72.00 0.00742786 38.6814 3636.07 0.00 6346.63 6346.63
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 5668.317 5668.317 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 5668.32 5668.32 234.126581 62.51 51.03 0.00654008 122.00 72.00 0.00800000 22.64 0.00280840 22.64 19.2182 72.00 0.00742786 38.6814 3636.07 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 7642.076 6115.326 280.862396 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 8477.29 8300.47 280.862396 79.45 59.80 0.00815152 53.60 50.01 0.00800000 94.38 0.00686598 62.80 16.0203 75.00 0.00836625 39.3290 5709.96 0.00 7640.76 5687.70
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 7642.076 7642.076 280.862396 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7642.08 7642.08 280.862396 64.09 51.96 0.00671897 122.00 72.00 0.00800000 22.64 0.00280840 22.64 16.0203 72.00 0.00746496 38.8729 5200.92 0.00 7652.12 7652.12
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 7210.355 7210.355 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7210.36 7210.36 280.862396 64.09 51.96 0.00671897 122.00 72.00 0.00800000 22.64 0.00280840 22.64 16.0203 72.00 0.00746496 38.8729 5200.92 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 10151.118 8121.527 376.020883 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 11419.91 11186.87 376.020883 78.88 59.60 0.00814553 53.60 50.01 0.00800000 96.13 0.00686752 63.35 11.9661 75.00 0.00829876 39.0161 7662.39 0.00 10149.38 7553.64
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 10151.118 10151.118 376.020883 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 10151.12 10151.12 376.020883 66.09 53.84 0.00737313 122.00 72.00 0.00800000 22.64 0.00280840 22.64 11.9661 72.00 0.00799359 41.5882 3609.40 0.00 10164.46 10164.46
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 5642.088 5642.088 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 5642.09 5642.09 376.020883 66.09 53.84 0.00737313 122.00 72.00 0.00800000 22.64 0.00280840 22.64 11.9661 72.00 0.00799359 41.5882 3609.40 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 6052.621 4842.744 220.525504 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 6578.13 6336.03 220.525504 79.71 60.06 0.00827389 53.60 50.01 0.00800000 91.45 0.00686340 61.87 20.4035 75.00 0.00863544 40.5774 4497.10 0.00 6051.58 4504.24
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 6052.621 6052.621 220.525504 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 6052.62 6052.62 220.525504 61.93 52.03 0.00724831 122.00 72.00 0.00800000 22.64 0.00280840 22.64 20.4035 72.00 0.00963172 49.9784 1236.75 0.00 6060.57 6060.57
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 4197.567 4197.567 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 4197.57 4197.57 220.525504 61.93 52.03 0.00724831 122.00 72.00 0.00800000 22.64 0.00280840 22.64 20.4035 72.00 0.00963172 49.9784 1236.75 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 7340.306 5876.040 270.744703 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 8193.41 8148.77 270.744703 79.71 59.72 0.00803927 53.60 50.01 0.00800000 95.20 0.00686670 63.06 16.6190 75.00 0.00825829 38.8283 5491.12 0.00 7339.05 5464.77
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 7340.306 7340.306 270.744703 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7340.31 7340.31 270.744703 63.80 52.56 0.00713184 122.00 72.00 0.00800000 22.64 0.00280840 22.64 16.6190 72.00 0.00799357 41.5881 3611.38 0.00 7349.95 7349.95
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 5644.044 5644.044 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 5644.04 5644.04 270.744703 63.80 52.56 0.00713184 122.00 72.00 0.00800000 22.64 0.00280840 22.64 16.6190 72.00 0.00799357 41.5881 3611.38 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 10018.839 8018.999 371.458072 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 11240.44 10989.27 371.458072 78.86 59.61 0.00815959 53.60 50.01 0.00800000 95.74 0.00686719 63.23 12.1131 75.00 0.00832180 39.1229 7569.42 0.00 10017.12 7457.76
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 10018.839 10018.839 371.458072 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 10018.84 10018.84 371.458072 66.02 53.80 0.00736547 122.00 72.00 0.00800000 22.64 0.00280840 22.64 12.1131 72.00 0.00799355 41.5880 3612.23 0.00 10032.01 10032.01
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 5644.878 5644.878 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 5644.88 5644.88 371.458072 66.02 53.80 0.00736547 122.00 72.00 0.00800000 22.64 0.00280840 22.64 12.1131 72.00 0.00799355 41.5880 3612.23 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 6024.523 4824.715 219.341274 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 6546.82 6304.85 219.341274 79.72 60.07 0.00827524 53.60 50.01 0.00800000 91.45 0.00686340 61.87 20.5137 75.00 0.00862892 40.5472 4449.46 0.00 6023.49 4486.86
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 6024.523 6024.523 219.341274 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 6024.52 6024.52 219.341274 61.87 52.00 0.00724206 122.00 72.00 0.00800000 22.64 0.00280840 22.64 20.5137 72.00 0.00963140 49.9767 1237.19 0.00 6032.44 6032.44
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 4197.567 4197.567 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 4197.57 4197.57 219.341274 61.87 52.00 0.00724206 122.00 72.00 0.00800000 22.64 0.00280840 22.64 20.5137 72.00 0.00963140 49.9767 1237.19 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 7335.234 5874.022 267.772340 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 8095.73 7862.84 267.772340 79.51 59.90 0.00821101 53.60 50.01 0.00800000 93.79 0.00686546 62.61 16.8034 75.00 0.00844610 39.6995 5441.14 0.00 7333.98 5462.73
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 7335.234 7335.234 267.772340 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7335.23 7335.23 267.772340 63.71 52.50 0.00712230 122.00 72.00 0.00800000 22.64 0.00280840 22.64 16.8034 72.00 0.00799359 41.5882 3609.40 0.00 7344.87 7344.87
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 5642.094 5642.094 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 5642.09 5642.09 267.772340 63.71 52.50 0.00712230 122.00 72.00 0.00800000 22.64 0.00280840 22.64 16.8034 72.00 0.00799359 41.5882 3609.40 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 11154.102 8928.759 418.213856 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 12573.76 12362.75 418.213856 78.62 59.47 0.00811829 53.60 50.01 0.00800000 96.13 0.00686752 63.35 10.7588 75.00 0.00826908 38.8782 8528.59 0.00 11152.19 8303.07
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 11154.102 11154.102 418.213856 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 11154.10 11154.10 418.213856 66.69 53.37 0.00695729 122.00 72.00 0.00800000 22.64 0.00280840 22.64 10.7588 72.00 0.00745748 38.8344 5118.40 0.00 11168.76 11168.76
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 7129.038 7129.038 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7129.04 7129.04 418.213856 66.69 53.37 0.00695729 122.00 72.00 0.00800000 22.64 0.00280840 22.64 10.7588 72.00 0.00745748 38.8344 5118.40 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 7105.658 5685.038 265.391938 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 7753.22 7517.15 265.391938 79.14 59.80 0.00822119 53.60 50.01 0.00800000 91.45 0.00686340 61.87 16.9542 75.00 0.00849838 39.9420 5412.07 0.00 7104.44 5287.26
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 7105.658 7105.658 265.391938 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7105.66 7105.66 265.391938 63.63 51.64 0.00663629 122.00 72.00 0.00800000 22.64 0.00280840 22.64 16.9542 72.00 0.00741777 38.6295 3556.80 0.00 7115.00 7115.00
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 5590.194 5590.194 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 5590.19 5590.19 265.391938 63.63 51.64 0.00663629 122.00 72.00 0.00800000 22.64 0.00280840 22.64 16.9542 72.00 0.00741777 38.6295 3556.80 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 8406.971 6733.247 313.000524 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 9308.76 9086.52 313.000524 79.05 59.69 0.00817180 53.60 50.01 0.00800000 93.79 0.00686546 62.61 14.3754 75.00 0.00832800 39.1515 6340.60 0.00 8405.53 6261.20
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 8406.971 8406.971 313.000524 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 8406.97 8406.97 313.000524 64.90 52.40 0.00678932 122.00 72.00 0.00800000 22.64 0.00280840 22.64 14.3754 72.00 0.00745768 38.8354 5120.69 0.00 8418.02 8418.02
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 7131.294 7131.294 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7131.29 7131.29 313.000524 64.90 52.40 0.00678932 122.00 72.00 0.00800000 22.64 0.00280840 22.64 14.3754 72.00 0.00745768 38.8354 5120.69 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 11226.581 8988.621 421.119429 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 12623.99 12388.92 421.119429 78.57 59.47 0.00813126 53.60 50.01 0.00800000 95.74 0.00686719 63.23 10.6846 75.00 0.00826840 38.8750 8576.70 0.00 11224.66 8358.42
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 11226.581 11226.581 421.119429 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 11226.58 11226.58 421.119429 66.72 53.39 0.00696089 122.00 72.00 0.00800000 22.64 0.00280840 22.64 10.6846 72.00 0.00745765 38.8353 5120.35 0.00 11241.33 11241.33
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 7130.960 7130.960 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7130.96 7130.96 421.119429 66.72 53.39 0.00696089 122.00 72.00 0.00800000 22.64 0.00280840 22.64 10.6846 72.00 0.00745765 38.8353 5120.35 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 7190.057 5755.444 268.838067 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 7846.70 7607.44 268.838067 79.10 59.78 0.00822127 53.60 50.01 0.00800000 91.45 0.00686340 61.87 16.7368 75.00 0.00848619 39.8854 5461.41 0.00 7188.82 5352.26
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 7190.057 7190.057 268.838067 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7190.06 7190.06 268.838067 63.74 51.70 0.00664633 122.00 72.00 0.00800000 22.64 0.00280840 22.64 16.7368 72.00 0.00741780 38.6297 3556.99 0.00 7199.51 7199.51
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 5590.389 5590.389 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 5590.39 5590.39 268.838067 63.74 51.70 0.00664633 122.00 72.00 0.00800000 22.64 0.00280840 22.64 16.7368 72.00 0.00741780 38.6297 3556.99 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 8515.937 6815.436 317.407670 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 9431.15 9205.17 317.407670 79.01 59.68 0.00817224 53.60 50.01 0.00800000 93.79 0.00686546 62.61 14.1758 75.00 0.00835734 39.2877 6445.83 0.00 8514.48 6338.34
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 8515.937 8515.937 317.407670 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 8515.94 8515.94 317.407670 65.00 52.45 0.00679849 122.00 72.00 0.00800000 22.64 0.00280840 22.64 14.1758 72.00 0.00745754 38.8347 5119.14 0.00 8527.13 8527.13
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 7129.760 7129.760 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7129.76 7129.76 317.407670 65.00 52.45 0.00679849 122.00 72.00 0.00800000 22.64 0.00280840 22.64 14.1758 72.00 0.00745754 38.8347 5119.14 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3609.791 3541.205 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3622.153 3553.332 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3611.041 3542.431 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3609.851 3541.264 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3622.165 3553.344 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3611.062 3542.452 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3667.520 3597.838 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3684.762 3614.751 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3668.648 3598.944 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3667.519 3597.836 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3684.772 3614.761 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3668.705 3599.000 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3609.520 3540.939 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3621.754 3552.941 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3610.673 3542.070 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3609.495 3540.914 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3621.714 3552.901 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3610.626 3542.024 400.423678 -999. -999.00 unknown unknown unknown unknown 3319.56 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [Btu/lbm-R] Dry Air Heat Capacity [Btu/lbm-R] Standard Air Density Adjusted for Elevation [lb/ft3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [ft3/min] Supply Fan Maximum Air Mass Flow Rate [lb/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [Btu/lbm-R] Plant Fluid Density [lb/ft3] Plant Maximum Fluid Mass Flow Rate [lb/s] Plant Design Fluid Return Temperature [F] Plant Design Fluid Supply Temperature [F] Plant Design Fluid Temperature Difference [deltaF] Plant Design Capacity [Btu/h] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [F] System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h] Coil Air Mass Flow Rate at Rating Conditions [lb/s] Coil Entering Air Drybulb at Rating Conditions [F] Coil Entering Air Wetbulb at Rating Conditions [F] Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] Coil Leaving Air Drybulb at Rating Conditions [F] Coil Leaving Air Wetbulb at Rating Conditions [F] Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 10653.874 8531.254 397.582455 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 397.582455 0.43205351   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 Sensible 12035.30 11867.56 0.8852 0.43205351 397.582455 78.79 59.50 0.00809845 11.2 53.60 50.01 0.00800000 7.7 -999. -999.0 -999.0 -999.0 511.681 11523.62 96.52 0.00686787 63.47 44.99498340 11.3171 75.00 0.00825549 75.00 0.00823025 38.6980 8102.04 0.00 10652.05 7933.26 0.41499067 80.00 67.00 0.01118466 13.2 58.26 56.86 0.00952496 9.3
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 10653.874 10653.874 397.582455 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 397.582455 0.43205351   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 10653.87 10653.87 1.0000 0.43205351 397.582455 66.41 53.24 0.00693802 8.8 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 10653.87 22.64 0.00280840 22.64 44.99498340 11.3171 72.00 0.00746501 72.00 0.00746501 38.8732 5201.52 0.00 10667.87 10667.87 0.42441899 70.00 60.00 0.00875166 10.4 98.63 69.51 0.00875166 14.3
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 7210.942 7210.942 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 397.582455 0.43205351   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7210.94 7210.94 1.0000 0.43205351 397.582455 66.41 53.24 0.00693802 8.8 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7210.94 22.64 0.00280840 22.64 44.99498340 11.3171 72.00 0.00746501 72.00 0.00746501 38.8732 5201.52 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6363.249 5092.003 235.162988 -999. -999.00 -999.0000 1.00000 1.00000 0.2437 0.2400 0.0652 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 235.162988 0.25555201   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 6931.22 6725.09 0.9181 0.25555201 235.162988 79.50 59.91 0.00821829 11.3 53.60 50.01 0.00800000 7.7 -999. -999.0 -999.0 -999.0 302.650 6628.57 91.45 0.00686340 61.87 44.99498340 19.1335 75.00 0.00853887 75.00 0.00848083 39.8605 4724.31 0.00 6362.16 4735.85 0.24545964 80.00 67.00 0.01118466 13.2 58.05 56.75 0.00950618 9.2
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6363.249 6363.249 235.162988 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 235.162988 0.25555201   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 6363.25 6363.25 1.0000 0.25555201 235.162988 62.55 51.05 0.00654386 8.0 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 6363.25 22.64 0.00280840 22.64 44.99498340 19.1335 72.00 0.00742770 72.00 0.00742770 38.6806 3634.70 0.00 6371.61 6371.61 0.25103633 70.00 60.00 0.00875166 10.4 98.91 69.59 0.00875166 14.3
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5666.968 5666.968 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 235.162988 0.25555201   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 5666.97 5666.97 1.0000 0.25555201 235.162988 62.55 51.05 0.00654386 8.0 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 5666.97 22.64 0.00280840 22.64 44.99498340 19.1335 72.00 0.00742770 72.00 0.00742770 38.6806 3634.70 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 7762.313 6212.340 282.986943 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 282.986943 0.30752238   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 Sensible 8682.58 8552.70 0.8940 0.30752238 282.986943 79.65 59.80 0.00810865 11.3 53.60 50.01 0.00800000 7.7 -999. -999.0 -999.0 -999.0 364.199 8318.38 95.74 0.00686719 63.23 44.99498340 15.9000 75.00 0.00834336 75.00 0.00820206 38.5671 5752.46 0.00 7760.98 5777.87 0.29537757 80.00 67.00 0.01118466 13.2 57.75 56.59 0.00948383 9.2
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 7762.313 7762.313 282.986943 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 282.986943 0.30752238   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7762.31 7762.31 1.0000 0.30752238 282.986943 64.15 52.00 0.00672466 8.4 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7762.31 22.64 0.00280840 22.64 44.99498340 15.9000 72.00 0.00746507 72.00 0.00746507 38.8735 5202.21 0.00 7772.51 7772.51 0.30208837 70.00 60.00 0.00875166 10.4 99.31 69.71 0.00875166 14.3
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 7211.627 7211.627 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 282.986943 0.30752238   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7211.63 7211.63 1.0000 0.30752238 282.986943 64.15 52.00 0.00672466 8.4 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7211.63 22.64 0.00280840 22.64 44.99498340 15.9000 72.00 0.00746507 72.00 0.00746507 38.8735 5202.21 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 10508.661 8416.292 392.297975 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 392.297975 0.42631086   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 Sensible 11837.28 11644.04 0.8878 0.42631086 392.297975 78.77 59.52 0.00811556 11.2 53.60 50.01 0.00800000 7.7 -999. -999.0 -999.0 -999.0 504.880 11332.40 96.13 0.00686752 63.35 44.99498340 11.4696 75.00 0.00827724 75.00 0.00825722 38.8232 7996.63 0.00 10506.86 7826.14 0.40947481 80.00 67.00 0.01118466 13.2 58.26 56.86 0.00952616 9.3
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 10508.661 10508.661 392.297975 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 392.297975 0.42631086   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 10508.66 10508.66 1.0000 0.42631086 392.297975 66.34 53.19 0.00693120 8.8 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 10508.66 22.64 0.00280840 22.64 44.99498340 11.4696 72.00 0.00746533 72.00 0.00746533 38.8748 5205.42 0.00 10522.47 10522.47 0.41877782 70.00 60.00 0.00875166 10.4 98.62 69.50 0.00875166 14.3
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 7214.782 7214.782 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 392.297975 0.42631086   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7214.78 7214.78 1.0000 0.42631086 392.297975 66.34 53.19 0.00693120 8.8 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7214.78 22.64 0.00280840 22.64 44.99498340 11.4696 72.00 0.00746533 72.00 0.00746533 38.8748 5205.42 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6338.296 5070.915 234.126581 -999. -999.00 -999.0000 1.00000 1.00000 0.2437 0.2400 0.0652 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 234.126581 0.25442574   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 6903.49 6697.87 0.9181 0.25442574 234.126581 79.51 59.92 0.00821874 11.3 53.60 50.01 0.00800000 7.7 -999. -999.0 -999.0 -999.0 301.317 6602.18 91.45 0.00686340 61.87 44.99498340 19.2182 75.00 0.00854118 75.00 0.00850244 39.9607 4733.54 0.00 6337.21 4716.41 0.24437785 80.00 67.00 0.01118466 13.2 58.05 56.74 0.00950447 9.2
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6338.296 6338.296 234.126581 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 234.126581 0.25442574   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 6338.30 6338.30 1.0000 0.25442574 234.126581 62.51 51.03 0.00654008 8.0 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 6338.30 22.64 0.00280840 22.64 44.99498340 19.2182 72.00 0.00742786 72.00 0.00742786 38.6814 3636.07 0.00 6346.63 6346.63 0.24992996 70.00 60.00 0.00875166 10.4 98.92 69.60 0.00875166 14.3
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5668.317 5668.317 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 234.126581 0.25442574   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 5668.32 5668.32 1.0000 0.25442574 234.126581 62.51 51.03 0.00654008 8.0 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 5668.32 22.64 0.00280840 22.64 44.99498340 19.2182 72.00 0.00742786 72.00 0.00742786 38.6814 3636.07 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 7642.076 6115.326 280.862396 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 280.862396 0.30521363   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 Sensible 8477.29 8300.47 0.9015 0.30521363 280.862396 79.45 59.80 0.00815152 11.3 53.60 50.01 0.00800000 7.7 -999. -999.0 -999.0 -999.0 361.465 8115.83 94.38 0.00686598 62.80 44.99498340 16.0203 75.00 0.00839675 75.00 0.00836625 39.3290 5709.96 0.00 7640.76 5687.70 0.29316000 80.00 67.00 0.01118466 13.2 57.93 56.69 0.00949692 9.2
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 7642.076 7642.076 280.862396 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 280.862396 0.30521363   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7642.08 7642.08 1.0000 0.30521363 280.862396 64.09 51.96 0.00671897 8.3 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7642.08 22.64 0.00280840 22.64 44.99498340 16.0203 72.00 0.00746496 72.00 0.00746496 38.8729 5200.92 0.00 7652.12 7652.12 0.29982041 70.00 60.00 0.00875166 10.4 99.07 69.64 0.00875166 14.3
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 7210.355 7210.355 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 280.862396 0.30521363   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7210.36 7210.36 1.0000 0.30521363 280.862396 64.09 51.96 0.00671897 8.3 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7210.36 22.64 0.00280840 22.64 44.99498340 16.0203 72.00 0.00746496 72.00 0.00746496 38.8729 5200.92 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 10151.118 8121.527 376.020883 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 376.020883 0.40862252   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 Sensible 11419.91 11186.87 0.8889 0.40862252 376.020883 78.88 59.60 0.00814553 11.2 53.60 50.01 0.00800000 7.7 -999. -999.0 -999.0 -999.0 483.932 10935.98 96.13 0.00686752 63.35 44.99498340 11.9661 75.00 0.00831925 75.00 0.00829876 39.0161 7662.39 0.00 10149.38 7553.64 0.39248502 80.00 67.00 0.01118466 13.2 58.11 56.78 0.00950922 9.2
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 10151.118 10151.118 376.020883 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 376.020883 0.40862252   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 10151.12 10151.12 1.0000 0.40862252 376.020883 66.09 53.84 0.00737313 9.0 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 10151.12 22.64 0.00280840 22.64 44.99498340 11.9661 72.00 0.00799359 72.00 0.00799359 41.5882 3609.40 0.00 10164.46 10164.46 0.40140203 70.00 60.00 0.00875166 10.4 98.84 69.57 0.00875166 14.3
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5642.088 5642.088 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 376.020883 0.40862252   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 5642.09 5642.09 1.0000 0.40862252 376.020883 66.09 53.84 0.00737313 9.0 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 5642.09 22.64 0.00280840 22.64 44.99498340 11.9661 72.00 0.00799359 72.00 0.00799359 41.5882 3609.40 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6052.621 4842.744 220.525504 -999. -999.00 -999.0000 1.00000 1.00000 0.2437 0.2400 0.0652 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 220.525504 0.23964543   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 6578.13 6336.03 0.9201 0.23964543 220.525504 79.71 60.06 0.00827389 11.4 53.60 50.01 0.00800000 7.7 -999. -999.0 -999.0 -999.0 283.812 6294.32 91.45 0.00686340 61.87 44.99498340 20.4035 75.00 0.00863544 75.00 0.00863544 40.5774 4497.10 0.00 6051.58 4504.24 0.23018125 80.00 67.00 0.01118466 13.2 57.74 56.58 0.00948168 9.2
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6052.621 6052.621 220.525504 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 220.525504 0.23964543   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 6052.62 6052.62 1.0000 0.23964543 220.525504 61.93 52.03 0.00724831 8.4 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 6052.62 22.64 0.00280840 22.64 44.99498340 20.4035 72.00 0.00838642 72.00 0.00963172 49.9784 1236.75 0.00 6060.57 6060.57 0.23541082 70.00 60.00 0.00875166 10.4 99.32 69.72 0.00875166 14.3
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 4197.567 4197.567 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 220.525504 0.23964543   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 4197.57 4197.57 1.0000 0.23964543 220.525504 61.93 52.03 0.00724831 8.4 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 4197.57 22.64 0.00280840 22.64 44.99498340 20.4035 72.00 0.00838642 72.00 0.00963172 49.9784 1236.75 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 7340.306 5876.040 270.744703 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 270.744703 0.29421872   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 Sensible 8193.41 8148.77 0.8959 0.29421872 270.744703 79.71 59.72 0.00803927 11.3 53.60 50.01 0.00800000 7.7 -999. -999.0 -999.0 -999.0 348.443 7844.97 95.20 0.00686670 63.06 44.99498340 16.6190 75.00 0.00827298 75.00 0.00825829 38.8283 5491.12 0.00 7339.05 5464.77 0.28259930 80.00 67.00 0.01118466 13.2 58.00 56.73 0.00950449 9.2
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 7340.306 7340.306 270.744703 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 270.744703 0.29421872   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7340.31 7340.31 1.0000 0.29421872 270.744703 63.80 52.56 0.00713184 8.6 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7340.31 22.64 0.00280840 22.64 44.99498340 16.6190 72.00 0.00799357 72.00 0.00799357 41.5881 3611.38 0.00 7349.95 7349.95 0.28901978 70.00 60.00 0.00875166 10.4 98.97 69.61 0.00875166 14.3
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5644.044 5644.044 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 270.744703 0.29421872   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 5644.04 5644.04 1.0000 0.29421872 270.744703 63.80 52.56 0.00713184 8.6 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 5644.04 22.64 0.00280840 22.64 44.99498340 16.6190 72.00 0.00799357 72.00 0.00799357 41.5881 3611.38 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 10018.839 8018.999 371.458072 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 371.458072 0.40366410   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 Sensible 11240.44 10989.27 0.8913 0.40366410 371.458072 78.86 59.61 0.00815959 11.2 53.60 50.01 0.00800000 7.7 -999. -999.0 -999.0 -999.0 478.060 10762.38 95.74 0.00686719 63.23 44.99498340 12.1131 75.00 0.00833771 75.00 0.00832180 39.1229 7569.42 0.00 10017.12 7457.76 0.38772242 80.00 67.00 0.01118466 13.2 58.12 56.79 0.00951240 9.2
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 10018.839 10018.839 371.458072 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 371.458072 0.40366410   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 10018.84 10018.84 1.0000 0.40366410 371.458072 66.02 53.80 0.00736547 9.0 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 10018.84 22.64 0.00280840 22.64 44.99498340 12.1131 72.00 0.00799355 72.00 0.00799355 41.5880 3612.23 0.00 10032.01 10032.01 0.39653123 70.00 60.00 0.00875166 10.4 98.82 69.56 0.00875166 14.3
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5644.878 5644.878 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 371.458072 0.40366410   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 5644.88 5644.88 1.0000 0.40366410 371.458072 66.02 53.80 0.00736547 9.0 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 5644.88 22.64 0.00280840 22.64 44.99498340 12.1131 72.00 0.00799355 72.00 0.00799355 41.5880 3612.23 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6024.523 4824.715 219.341274 -999. -999.00 -999.0000 1.00000 1.00000 0.2437 0.2400 0.0652 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 219.341274 0.23835853   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 6546.82 6304.85 0.9202 0.23835853 219.341274 79.72 60.07 0.00827524 11.4 53.60 50.01 0.00800000 7.7 -999. -999.0 -999.0 -999.0 282.288 6264.53 91.45 0.00686340 61.87 44.99498340 20.5137 75.00 0.00863960 75.00 0.00862892 40.5472 4449.46 0.00 6023.49 4486.86 0.22894517 80.00 67.00 0.01118466 13.2 57.71 56.58 0.00948434 9.2
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6024.523 6024.523 219.341274 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 219.341274 0.23835853   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 6024.52 6024.52 1.0000 0.23835853 219.341274 61.87 52.00 0.00724206 8.4 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 6024.52 22.64 0.00280840 22.64 44.99498340 20.5137 72.00 0.00838629 72.00 0.00963140 49.9767 1237.19 0.00 6032.44 6032.44 0.23414666 70.00 60.00 0.00875166 10.4 99.34 69.72 0.00875166 14.4
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 4197.567 4197.567 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 219.341274 0.23835853   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 4197.57 4197.57 1.0000 0.23835853 219.341274 61.87 52.00 0.00724206 8.4 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 4197.57 22.64 0.00280840 22.64 44.99498340 20.5137 72.00 0.00838629 72.00 0.00963140 49.9767 1237.19 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 7335.234 5874.022 267.772340 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 267.772340 0.29098865   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 Sensible 8095.73 7862.84 0.9061 0.29098865 267.772340 79.51 59.90 0.00821101 11.3 53.60 50.01 0.00800000 7.7 -999. -999.0 -999.0 -999.0 344.618 7751.11 93.79 0.00686546 62.61 44.99498340 16.8034 75.00 0.00848278 75.00 0.00844610 39.6995 5441.14 0.00 7333.98 5462.73 0.27949679 80.00 67.00 0.01118466 13.2 57.77 56.61 0.00948858 9.2
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 7335.234 7335.234 267.772340 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 267.772340 0.29098865   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7335.23 7335.23 1.0000 0.29098865 267.772340 63.71 52.50 0.00712230 8.5 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7335.23 22.64 0.00280840 22.64 44.99498340 16.8034 72.00 0.00799359 72.00 0.00799359 41.5882 3609.40 0.00 7344.87 7344.87 0.28584679 70.00 60.00 0.00875166 10.4 99.27 69.70 0.00875166 14.3
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5642.094 5642.094 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 267.772340 0.29098865   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 5642.09 5642.09 1.0000 0.29098865 267.772340 63.71 52.50 0.00712230 8.5 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 5642.09 22.64 0.00280840 22.64 44.99498340 16.8034 72.00 0.00799359 72.00 0.00799359 41.5882 3609.40 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 11154.102 8928.759 418.213856 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 418.213856 0.45447369   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 Sensible 12573.76 12362.75 0.8871 0.45447369 418.213856 78.62 59.47 0.00811829 11.2 53.60 50.01 0.00800000 7.7 -999. -999.0 -999.0 -999.0 538.233 12035.53 96.13 0.00686752 63.35 44.99498340 10.7588 75.00 0.00826908 75.00 0.00826908 38.8782 8528.59 0.00 11152.19 8303.07 0.43652542 80.00 67.00 0.01118466 13.2 58.37 56.91 0.00953120 9.3
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 11154.102 11154.102 418.213856 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 418.213856 0.45447369   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 11154.10 11154.10 1.0000 0.45447369 418.213856 66.69 53.37 0.00695729 8.8 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 11154.10 22.64 0.00280840 22.64 44.99498340 10.7588 72.00 0.00745748 72.00 0.00745748 38.8344 5118.40 0.00 11168.76 11168.76 0.44644300 70.00 60.00 0.00875166 10.4 98.49 69.47 0.00875166 14.2
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 7129.038 7129.038 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 418.213856 0.45447369   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7129.04 7129.04 1.0000 0.45447369 418.213856 66.69 53.37 0.00695729 8.8 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7129.04 22.64 0.00280840 22.64 44.99498340 10.7588 72.00 0.00745748 72.00 0.00745748 38.8344 5118.40 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 7105.658 5685.038 265.391938 -999. -999.00 -999.0000 1.00000 1.00000 0.2437 0.2400 0.0652 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 265.391938 0.28840186   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 7753.22 7517.15 0.9165 0.28840186 265.391938 79.14 59.80 0.00822119 11.3 53.60 50.01 0.00800000 7.7 -999. -999.0 -999.0 -999.0 341.554 7411.66 91.45 0.00686340 61.87 44.99498340 16.9542 75.00 0.00849838 75.00 0.00849838 39.9420 5412.07 0.00 7104.44 5287.26 0.27701217 80.00 67.00 0.01118466 13.2 58.29 56.87 0.00952282 9.3
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 7105.658 7105.658 265.391938 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 265.391938 0.28840186   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7105.66 7105.66 1.0000 0.28840186 265.391938 63.63 51.64 0.00663629 8.2 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7105.66 22.64 0.00280840 22.64 44.99498340 16.9542 72.00 0.00741777 72.00 0.00741777 38.6295 3556.80 0.00 7115.00 7115.00 0.28330571 70.00 60.00 0.00875166 10.4 98.60 69.50 0.00875166 14.3
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5590.194 5590.194 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 265.391938 0.28840186   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 5590.19 5590.19 1.0000 0.28840186 265.391938 63.63 51.64 0.00663629 8.2 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 5590.19 22.64 0.00280840 22.64 44.99498340 16.9542 72.00 0.00741777 72.00 0.00741777 38.6295 3556.80 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 8406.971 6733.247 313.000524 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 313.000524 0.34013819   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 Sensible 9308.76 9086.52 0.9031 0.34013819 313.000524 79.05 59.69 0.00817180 11.2 53.60 50.01 0.00800000 7.7 -999. -999.0 -999.0 -999.0 402.826 8905.93 93.79 0.00686546 62.61 44.99498340 14.3754 75.00 0.00839111 75.00 0.00832800 39.1515 6340.60 0.00 8405.53 6261.20 0.32670530 80.00 67.00 0.01118466 13.2 58.20 56.83 0.00952191 9.2
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 8406.971 8406.971 313.000524 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 313.000524 0.34013819   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 8406.97 8406.97 1.0000 0.34013819 313.000524 64.90 52.40 0.00678932 8.5 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 8406.97 22.64 0.00280840 22.64 44.99498340 14.3754 72.00 0.00745768 72.00 0.00745768 38.8354 5120.69 0.00 8418.02 8418.02 0.33412784 70.00 60.00 0.00875166 10.4 98.70 69.53 0.00875166 14.3
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 7131.294 7131.294 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 313.000524 0.34013819   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7131.29 7131.29 1.0000 0.34013819 313.000524 64.90 52.40 0.00678932 8.5 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7131.29 22.64 0.00280840 22.64 44.99498340 14.3754 72.00 0.00745768 72.00 0.00745768 38.8354 5120.69 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 11226.581 8988.621 421.119429 -999. -999.00 -999.0000 1.00193 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 421.119429 0.45763118   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 Sensible 12623.99 12388.92 0.8893 0.45763118 421.119429 78.57 59.47 0.00813126 11.2 53.60 50.01 0.00800000 7.7 -999. -999.0 -999.0 -999.0 541.973 12082.02 95.74 0.00686719 63.23 44.99498340 10.6846 75.00 0.00828247 75.00 0.00826840 38.8750 8576.70 0.00 11224.66 8358.42 0.43955821 80.00 67.00 0.01118466 13.2 58.37 56.92 0.00953274 9.3
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 11226.581 11226.581 421.119429 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 421.119429 0.45763118   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 11226.58 11226.58 1.0000 0.45763118 421.119429 66.72 53.39 0.00696089 8.8 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 11226.58 22.64 0.00280840 22.64 44.99498340 10.6846 72.00 0.00745765 72.00 0.00745765 38.8353 5120.35 0.00 11241.33 11241.33 0.44954470 70.00 60.00 0.00875166 10.4 98.48 69.46 0.00875166 14.2
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 7130.960 7130.960 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 421.119429 0.45763118   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7130.96 7130.96 1.0000 0.45763118 421.119429 66.72 53.39 0.00696089 8.8 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7130.96 22.64 0.00280840 22.64 44.99498340 10.6846 72.00 0.00745765 72.00 0.00745765 38.8353 5120.35 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 7190.057 5755.444 268.838067 -999. -999.00 -999.0000 1.00000 1.00000 0.2437 0.2400 0.0652 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 268.838067 0.29214677   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 7846.70 7607.44 0.9163 0.29214677 268.838067 79.10 59.78 0.00822127 11.3 53.60 50.01 0.00800000 7.7 -999. -999.0 -999.0 -999.0 345.990 7500.71 91.45 0.00686340 61.87 44.99498340 16.7368 75.00 0.00849421 75.00 0.00848619 39.8854 5461.41 0.00 7188.82 5352.26 0.28060918 80.00 67.00 0.01118466 13.2 58.31 56.88 0.00952662 9.3
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 7190.057 7190.057 268.838067 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 268.838067 0.29214677   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7190.06 7190.06 1.0000 0.29214677 268.838067 63.74 51.70 0.00664633 8.3 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7190.06 22.64 0.00280840 22.64 44.99498340 16.7368 72.00 0.00741780 72.00 0.00741780 38.6297 3556.99 0.00 7199.51 7199.51 0.28698445 70.00 60.00 0.00875166 10.4 98.57 69.49 0.00875166 14.2
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5590.389 5590.389 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 268.838067 0.29214677   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 5590.39 5590.39 1.0000 0.29214677 268.838067 63.74 51.70 0.00664633 8.3 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 5590.39 22.64 0.00280840 22.64 44.99498340 16.7368 72.00 0.00741780 72.00 0.00741780 38.6297 3556.99 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 8515.937 6815.436 317.407670 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 317.407670 0.34492744   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 Sensible 9431.15 9205.17 0.9030 0.34492744 317.407670 79.01 59.68 0.00817224 11.2 53.60 50.01 0.00800000 7.7 -999. -999.0 -999.0 -999.0 408.498 9022.65 93.79 0.00686546 62.61 44.99498340 14.1758 75.00 0.00838808 75.00 0.00835734 39.2877 6445.83 0.00 8514.48 6338.34 0.33130542 80.00 67.00 0.01118466 13.2 58.24 56.85 0.00952067 9.2
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 8515.937 8515.937 317.407670 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 317.407670 0.34492744   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 8515.94 8515.94 1.0000 0.34492744 317.407670 65.00 52.45 0.00679849 8.5 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 8515.94 22.64 0.00280840 22.64 44.99498340 14.1758 72.00 0.00745754 72.00 0.00745754 38.8347 5119.14 0.00 8527.13 8527.13 0.33883247 70.00 60.00 0.00875166 10.4 98.66 69.52 0.00875166 14.3
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 7129.760 7129.760 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 317.407670 0.34492744   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7129.76 7129.76 1.0000 0.34492744 317.407670 65.00 52.45 0.00679849 8.5 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7129.76 22.64 0.00280840 22.64 44.99498340 14.1758 72.00 0.00745754 72.00 0.00745754 38.8347 5119.14 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3609.791 3541.205 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0652 HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.17388376   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3622.153 3553.332 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0652 HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.17388376   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3611.041 3542.431 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0652 HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.17388376   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3609.851 3541.264 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0652 HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.17388376   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3622.165 3553.344 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0652 HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.17388376   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3611.062 3542.452 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0652 HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.17388376   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3667.520 3597.838 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0652 HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.17388376   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3684.762 3614.751 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0652 HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.17388376   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3668.648 3598.944 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0652 HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.17388376   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3667.519 3597.836 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0652 HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.17388376   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3684.772 3614.761 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0652 HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.17388376   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3668.705 3599.000 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0652 HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.17388376   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3609.520 3540.939 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0652 HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 160.010573 0.17388376   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3621.754 3552.941 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0652 HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 160.010573 0.17388376   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3610.673 3542.070 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0652 HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 160.010573 0.17388376   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3609.495 3540.914 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0652 HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 160.010573 0.17388376   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3621.714 3552.901 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0652 HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 160.010573 0.17388376   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3610.626 3542.024 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0652 HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 160.010573 0.17388376   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3319.56 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3319.56 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2707.67 4918.50 360.67
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2277.83 5247.17 360.50
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2729.50 4819.50 315.50
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2554.83 5369.67 379.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2099.50 5653.83 383.83
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2590.00 5256.83 335.67
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2911.33 4420.83 227.50
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2479.33 4701.67 213.17
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2930.83 4335.00 196.17
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2736.50 4954.67 233.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2280.17 5158.50 222.67
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2757.83 4840.00 204.83
LIVING_UNIT3_BACKROW_TOPFLOOR 2877.83 4818.33 213.33
LIVING_UNIT3_FRONTROW_TOPFLOOR 2983.17 4497.17 206.67
LIVING_UNIT1_FRONTROW_TOPFLOOR 2962.00 4587.33 235.67
LIVING_UNIT2_BACKROW_TOPFLOOR 2489.17 5130.17 236.17
LIVING_UNIT2_FRONTROW_TOPFLOOR 2594.17 4817.67 225.83
LIVING_UNIT1_BACKROW_TOPFLOOR 2842.50 4937.67 245.17
CRAWLSPACE 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 3323.33 5896.50 463.67
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8.67 17.83 8.67 17.83
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 9.33 24.00 9.33 24.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 11.17 31.17 11.17 31.17
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 9.00 19.17 9.00 19.17
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 7.17 29.17 7.17 29.17
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6.83 29.50 6.83 29.50
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8.33 20.17 8.33 20.17
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 10.33 16.50 10.33 16.50
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8.67 48.67 8.67 48.67
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 6.67 21.00 6.67 21.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 10.67 22.50 10.67 22.50
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 12.33 34.50 12.33 34.50
LIVING_UNIT3_BACKROW_TOPFLOOR 8.83 22.17 8.83 22.17
LIVING_UNIT3_FRONTROW_TOPFLOOR 9.67 33.00 9.67 33.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8.00 17.50 8.00 17.50
LIVING_UNIT2_BACKROW_TOPFLOOR 9.33 23.00 9.33 23.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 10.00 21.83 10.00 21.83
LIVING_UNIT1_BACKROW_TOPFLOOR 6.00 18.17 6.00 18.17
CRAWLSPACE 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 119.00 85.67 119.00 85.67
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.269 0.106 0.000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.269 0.093 0.000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.269 0.106 0.000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.269 0.106 0.000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.269 0.093 0.000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.269 0.106 0.000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.269 0.047 0.000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.269 0.034 0.000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.269 0.047 0.000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.269 0.046 0.000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.269 0.034 0.000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.269 0.046 0.000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.269 0.106 0.000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.269 0.106 0.000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.269 0.106 0.000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.269 0.093 0.000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.269 0.094 0.000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.269 0.106 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.262 0.000 0.000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.262 0.000 0.000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.262 0.000 0.000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.262 0.000 0.000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.262 0.000 0.000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.262 0.000 0.000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.262 0.000 0.000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.262 0.000 0.000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.262 0.000 0.000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.262 0.000 0.000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.262 0.000 0.000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.262 0.000 0.000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.262 0.000 0.000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.262 0.000 0.000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.262 0.000 0.000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.262 0.000 0.000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.262 0.000 0.000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.262 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Zone Area [ft2] Design Zone Outdoor Airflow - Voz [ft3/min] Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
Total Facility   24.79 36.00 183739.38 21609.96 0.0000 0.000


Total Outdoor Air by Zone

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Infiltration [ft3] Total Ventilation and Infiltration [ft3] Dynamic Target Ventilation - Voz-dyn [ft3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 9378088.06 33163169.75 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 8261548.69 32046630.38 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 9382261.98 33167343.67 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 9352554.57 33137636.26 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 8231442.90 32016524.59 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 9350743.36 33135825.05 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 4117691.12 27902772.81 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 2997413.79 26782495.48 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 4119930.41 27905012.09 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 4104815.72 27889897.41 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 2983970.06 26769051.75 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 4103548.12 27888629.81 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 23785081.69 0.00 23785081.69 9370350.28 33155431.96 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 23785081.69 0.00 23785081.69 9397467.68 33182549.37 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 23785081.69 0.00 23785081.69 9393120.49 33178202.17 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 23785081.69 0.00 23785081.69 8249509.56 32034591.25 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 23785081.69 0.00 23785081.69 8275737.69 32060819.38 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 23785081.69 0.00 23785081.69 9371266.63 33156348.32 23785081.69 0.00 8808.00 0.00 0.00
Total Facility 0.428131E+09 0.00 0.428131E+09 0.130441E+09 0.558573E+09 0.428131E+09 0.00 8808.00 0.00 0.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Infiltration [ft3/min] Total Ventilation and Infiltration [ft3/min] Dynamic Target Ventilation - Voz-dyn [ft3/min] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 17.7408 62.7358 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 15.6286 60.6236 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 17.7487 62.7437 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 17.6925 62.6875 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 15.5717 60.5667 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 17.6891 62.6841 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 7.7896 52.7845 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 5.6703 50.6653 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 7.7938 52.7888 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 7.7652 52.7602 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 5.6449 50.6399 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 7.7628 52.7578 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 44.9950 0.0000 44.9950 17.7262 62.7212 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 44.9950 0.0000 44.9950 17.7775 62.7725 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 44.9950 0.0000 44.9950 17.7693 62.7642 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 44.9950 0.0000 44.9950 15.6059 60.6008 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 44.9950 0.0000 44.9950 15.6555 60.6505 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 44.9950 0.0000 44.9950 17.7279 62.7229 44.9950 0.00 8808.00 0.00
Total Facility 809.9097 0.0000 809.9097 246.7602 1056.6699 809.9097 0.00 8808.00 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [ft3] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [ft3/min] Limits and Scheduled Limits [ft3/min] Economizer [ft3/min] Exhaust Flow [ft3/min] Mixed Air Flow [ft3/min] High Humidity [ft3/min] Demand Controlled Ventilation [ft3/min] Night Ventilation [ft3/min] Demand Limiting [ft3/min] Energy Management System [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

Surfaces by Class

Total Outdoors
Wall 82 58
Floor 29 4
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 60 60
Overhang 30 30
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 2058
Defaulted Fields 1808
Fields with Defaults 7284
Autosized Fields 396
Autosizable Fields 684
Autocalculated Fields 197
Autocalculatable Fields 421



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 159991.04 7967.15 07-MAR-03:10 48039.13 27-DEC-07:10
Electricity:Building 99140.61 6270.77 02-JAN-03:10 18720.91 01-JAN-18:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity 11336.81 253.88 01-JAN-00:10 3692.78 01-JAN-19:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
General:InteriorLights:Electricity 11336.81 253.88 01-JAN-00:10 3692.78 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5507.81 348.38 02-JAN-03:10 1040.05 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
InteriorEquipment:Electricity 87803.80 5989.14 02-JAN-04:10 15388.75 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity 2758.31 25.25 02-JAN-03:10 880.12 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity 1408.53 13.53 02-JAN-02:10 381.47 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:10 3196.73 01-JAN-11:10
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:10 3721.08 01-JAN-17:10
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:10 7929.96 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:10 526.17 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
Electricity:HVAC 41979.97 289.29 03-JAN-23:20 29421.22 27-DEC-07:00
Cooling:Electricity 19054.27 0.00 01-JAN-00:10 10751.54 01-JUL-17:00
General:Cooling:Electricity 19054.27 0.00 01-JAN-00:10 10751.54 01-JUL-17:00
Heating:Electricity 14271.08 0.00 01-JAN-17:50 26892.32 27-DEC-07:00
General:Heating:Electricity 14271.08 0.00 01-JAN-17:50 26892.32 27-DEC-07:00
Electricity:Plant 13361.76 149.40 19-JUN-15:30 9110.14 24-MAY-09:00
WaterSystems:Electricity 13361.76 149.40 19-JUN-15:30 9110.14 24-MAY-09:00
Fans:Electricity 8654.61 289.29 01-JAN-21:50 2573.92 07-JAN-07:00
General:Fans:Electricity 6120.47 0.00 01-JAN-21:50 2284.63 07-JAN-07:00
Ventilation:Fans:Electricity 2534.14 289.29 01-JAN-00:10 289.29 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityPurchased:Facility 159991.04 7967.15 07-MAR-03:10 48039.13 27-DEC-07:10
ElectricityPurchased:Plant 159991.04 7967.15 07-MAR-03:10 48039.13 27-DEC-07:10
Cogeneration:ElectricityPurchased 159991.04 7967.15 07-MAR-03:10 48039.13 27-DEC-07:10
General:Cogeneration:ElectricityPurchased 159991.04 7967.15 07-MAR-03:10 48039.13 27-DEC-07:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 159991.04 7967.15 07-MAR-03:10 48039.13 27-DEC-07:10
ElectricityNet:Plant 159991.04 7967.15 07-MAR-03:10 48039.13 27-DEC-07:10
Cogeneration:ElectricityNet 159991.04 7967.15 07-MAR-03:10 48039.13 27-DEC-07:10
General:Cogeneration:ElectricityNet 159991.04 7967.15 07-MAR-03:10 48039.13 27-DEC-07:10
HeatRecovery:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:HeatRecovery:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ExteriorLights:Electricity 5508.71 0.00 01-JAN-06:10 1257.69 01-JAN-00:10
Exterior-Lights:ExteriorLights:Electricity 5508.71 0.00 01-JAN-06:10 1257.69 01-JAN-00:10
Garage-Lights:ExteriorLights:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:Electricity 1308.75 149.40 19-JUN-15:30 149.40 01-JAN-08:50
Water Heater Parasitic:WaterSystems:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [therm] Natural Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
Water:Plant 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
WaterSystems:Water 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
Domestic Hot Water:WaterSystems:Water 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
MainsWater:Facility 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
MainsWater:Plant 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
WaterSystems:MainsWater 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
Domestic Hot Water:WaterSystems:MainsWater 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 891832.14 9237.28 24-NOV-02:10 279008.60 14-JUN-18:40
EnergyTransfer:HVAC 444285.63 0.00 01-JAN-21:50 176393.56 28-NOV-06:20
CoolingCoils:EnergyTransfer 354759.13 0.00 01-JAN-00:10 145766.17 14-JUN-18:40
HeatingCoils:EnergyTransfer 89526.50 0.00 01-JAN-17:50 128087.26 27-DEC-07:00
EnergyTransfer:Building 343372.09 1156.24 03-MAY-10:40 120104.10 14-JUN-18:40
EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer 35323.30 0.00 01-JAN-17:50 54312.58 27-DEC-07:10
Heating:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 35323.30 0.00 01-JAN-17:50 54312.58 27-DEC-07:10
Cooling:EnergyTransfer 308048.79 0.00 01-JAN-07:40 120104.10 14-JUN-18:40
Cooling:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer 308048.79 0.00 01-JAN-07:40 120104.10 14-JUN-18:40
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 20774.44 0.12 31-JAN-03:40 10155.13 05-JUN-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2505.77 0.00 01-JAN-00:20 4032.00 27-DEC-07:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 18268.67 0.00 01-JAN-00:10 10155.13 05-JUN-17:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 15979.25 0.96 22-NOV-04:50 5817.09 02-JUN-19:10
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1436.28 0.00 01-JAN-00:10 3206.60 12-JAN-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 14542.96 0.00 01-JAN-01:10 5817.09 02-JUN-19:10
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 20464.14 0.42 15-NOV-04:20 6940.73 15-JUN-19:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2305.55 0.00 01-JAN-00:20 4020.84 27-DEC-07:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 18158.58 0.00 01-JAN-00:10 6940.73 15-JUN-19:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 18792.87 0.24 07-DEC-22:50 10356.18 05-JUN-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 3541.06 0.00 01-JAN-13:30 4125.38 27-DEC-08:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 15251.81 0.00 01-JAN-00:10 10356.18 05-JUN-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 13827.26 0.74 14-JAN-22:00 5910.57 14-JUN-19:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2367.43 0.00 01-JAN-00:20 3012.65 10-DEC-01:40
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 11459.84 0.00 01-JAN-00:10 5910.57 14-JUN-19:00
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 18014.60 0.02 22-DEC-21:40 7999.95 14-JUN-18:40
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 3091.23 0.00 01-JAN-13:10 4081.23 28-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 14923.37 0.00 01-JAN-00:10 7999.95 14-JUN-18:40
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 21703.38 0.04 18-NOV-06:20 8766.35 15-JUN-17:20
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1191.89 0.00 01-JAN-00:10 2943.45 04-NOV-08:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 20511.49 0.00 01-JAN-02:00 8766.35 15-JUN-17:20
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 17828.66 0.30 04-JAN-08:10 5157.45 02-JUL-20:50
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 660.49 0.00 01-JAN-00:10 2677.79 30-NOV-07:50
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 17168.17 0.00 01-JAN-04:40 5157.45 02-JUL-20:50
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 21686.59 0.42 17-JAN-00:50 6985.20 15-JUN-16:10
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1111.61 0.00 01-JAN-00:10 3163.96 12-JAN-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 20574.98 0.00 01-JAN-01:30 6985.20 15-JUN-16:10
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 18967.22 0.02 24-OCT-03:30 9154.69 14-JUN-18:40
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1824.11 0.00 01-JAN-00:10 3054.39 27-MAR-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 17143.11 0.00 01-JAN-00:20 9154.69 14-JUN-18:40
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 14901.00 0.34 17-FEB-02:40 5534.90 14-JUN-18:20
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1153.51 0.00 01-JAN-00:10 3076.45 19-NOV-08:20
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 13747.49 0.00 01-JAN-00:40 5534.90 14-JUN-18:20
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 18787.99 0.20 18-JAN-00:10 7178.30 14-JUN-18:20
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1642.82 0.00 01-JAN-00:20 3107.32 04-DEC-23:20
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 17145.17 0.00 01-JAN-00:10 7178.30 14-JUN-18:20
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 20617.16 1.00 31-JAN-08:30 8185.13 15-JUN-19:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 2571.33 0.00 01-JAN-13:10 3868.26 27-DEC-07:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 18045.83 0.00 01-JAN-00:10 8185.13 15-JUN-19:00
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 22463.49 0.09 01-DEC-23:50 7579.69 15-JUN-19:10
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 1906.98 0.00 01-JAN-00:10 3860.46 27-DEC-07:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 20556.51 0.00 01-JAN-00:20 7579.69 15-JUN-19:10
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 22657.98 0.16 14-OCT-08:30 10298.74 05-JUN-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 2074.17 0.00 01-JAN-00:10 3854.88 27-DEC-07:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 20583.81 0.00 01-JAN-00:40 10298.74 05-JUN-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 16453.07 0.26 03-MAR-03:20 6713.46 14-JUN-18:40
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 1854.41 0.00 01-JAN-00:10 3199.99 01-MAR-22:20
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 14598.65 0.00 01-JAN-00:20 6713.46 14-JUN-18:40
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 18235.31 0.42 15-JAN-21:10 6622.79 02-JUL-21:40
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 1145.30 0.00 01-JAN-00:10 2855.61 12-JAN-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 17090.01 0.00 01-JAN-04:20 6622.79 02-JUL-21:40
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 21217.69 0.13 20-MAR-02:20 10485.76 05-JUN-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 2939.37 0.00 01-JAN-13:20 3983.00 27-DEC-08:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 18278.31 0.00 01-JAN-00:10 10485.76 05-JUN-17:30
HeatRecoveryForHeating:EnergyTransfer 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRecoveryForCooling:EnergyTransfer 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Plant 104174.41 779.64 07-AUG-02:10 29453.76 29-JAN-09:00
WaterSystems:EnergyTransfer 104174.41 779.64 07-AUG-02:10 29453.76 29-JAN-09:00
Domestic Hot Water:WaterSystems:EnergyTransfer 104174.41 779.64 07-AUG-02:10 29453.76 29-JAN-09:00
PlantLoopHeatingDemand:Facility 104174.41 779.64 07-AUG-02:10 29453.76 29-JAN-09:00
PlantLoopHeatingDemand:Plant 104174.41 779.64 07-AUG-02:10 29453.76 29-JAN-09:00
WaterSystems:PlantLoopHeatingDemand 104174.41 779.64 07-AUG-02:10 29453.76 29-JAN-09:00
General:WaterSystems:PlantLoopHeatingDemand 104174.41 779.64 07-AUG-02:10 29453.76 29-JAN-09:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 910.909 -698.50 5994.601 -1189.27 0.000 0.000 2994.902 2150.478 10401.374 10659.803 0.000 390.492 0.249 0.000 -3407.70 0.000 -1991.35 -5435.11
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 911.915 -697.54 4429.570 -838.79 0.000 0.000 2990.757 2150.478 10401.374 4688.490 0.000 344.618 0.130 0.000 -1364.66 0.000 -1754.52 -4349.83
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 909.351 -701.18 5446.082 -1148.29 0.000 0.000 2995.671 2150.478 10401.374 10690.634 0.000 389.185 0.102 0.000 -3287.88 0.000 -1995.07 -5491.35
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 911.670 -691.78 7888.786 -1016.35 0.000 0.000 3009.586 2150.478 10401.374 7546.809 0.000 391.433 0.000 0.000 -3488.94 0.000 -1954.49 -6345.48
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 913.394 -688.78 6657.229 -698.89 0.000 0.000 3011.374 2150.478 10401.374 1463.022 0.000 346.390 0.000 0.000 -1431.18 0.000 -1713.05 -5135.96
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 910.464 -693.48 7435.376 -986.90 0.000 0.000 3012.378 2150.478 10401.374 7501.971 0.000 389.841 0.000 0.000 -3278.11 0.000 -1952.15 -6393.61
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 910.952 -705.08 3811.447 -1297.08 0.000 0.000 2974.889 2150.478 10401.374 10586.226 0.000 170.241 0.095 0.000 -3519.08 0.000 -887.99 -2556.52
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 912.264 -705.83 2434.880 -947.64 0.000 0.000 2966.592 2150.478 10401.374 4652.757 0.000 124.046 0.318 0.000 -1409.80 0.000 -649.33 -1728.41
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 908.798 -707.90 3387.254 -1270.73 0.000 0.000 2975.955 2150.478 10401.374 10609.631 0.000 169.669 0.158 0.000 -3392.00 0.000 -890.92 -2560.79
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 912.451 -697.67 5354.389 -1099.95 0.000 0.000 2992.915 2150.478 10401.374 7493.322 0.000 170.530 0.075 0.000 -3599.97 0.000 -869.02 -3420.60
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 913.289 -694.89 4172.312 -777.43 0.000 0.000 2993.733 2150.478 10401.374 1447.736 0.000 124.562 0.059 0.000 -1477.51 0.000 -629.63 -2416.73
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 910.035 -698.82 4995.242 -1083.96 0.000 0.000 2997.660 2150.478 10401.374 7437.120 0.000 169.944 0.037 0.000 -3375.44 0.000 -867.42 -3411.32
LIVING_UNIT3_BACKROW_TOPFLOOR 910.839 -698.34 6458.913 -1204.08 0.000 0.000 2999.391 2150.478 10401.374 7424.368 0.000 386.667 0.000 0.000 -3385.19 0.000 -1979.92 -2522.61
LIVING_UNIT3_FRONTROW_TOPFLOOR 908.707 -704.71 4797.079 -1323.54 0.000 0.000 2984.381 2150.478 10401.374 10611.918 0.000 386.307 0.006 0.000 -3378.65 0.000 -2017.86 -2488.39
LIVING_UNIT1_FRONTROW_TOPFLOOR 912.598 -702.30 5277.318 -1354.62 0.000 0.000 2983.463 2150.478 10401.374 10582.299 0.000 387.283 0.098 0.000 -3501.60 0.000 -2013.56 -2480.08
LIVING_UNIT2_BACKROW_TOPFLOOR 912.566 -694.79 5571.260 -906.49 0.000 0.000 2996.321 2150.478 10401.374 1441.991 0.000 342.546 0.119 0.000 -1479.07 0.000 -1740.20 -1369.15
LIVING_UNIT2_FRONTROW_TOPFLOOR 911.977 -702.28 3748.182 -1013.65 0.000 0.000 2977.545 2150.478 10401.374 4650.811 0.000 341.508 0.139 0.000 -1402.03 0.000 -1777.69 -1397.26
LIVING_UNIT1_BACKROW_TOPFLOOR 913.155 -696.75 6856.266 -1227.66 0.000 0.000 2996.465 2150.478 10401.374 7472.920 0.000 388.019 0.006 0.000 -3598.66 0.000 -1981.33 -2490.29
CRAWLSPACE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 69093.808 22568.242 0.000 0.000 0.000 -91662.05 -1.21
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 25943.977 182419.691 0.000 0.000 0.000 -208363.67 -0.61
Total Facility 16405.336 -12580.61 94716.186 -19385.31 0.000 0.000 53853.978 38708.604 187224.736 126961.827 0.000 100451.067 204989.525 0.000 -49777.45 0.000 -327691.21 -61995.32


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 05-JUN-17:25 0.00 -0.2 0.00 -0.7 0.00 0.00 250.03 469.21 1655.83 4624.65 0.00 543.76 3238.82 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 02-JUN-19:05 0.00 -0.2 0.00 -0.4 0.00 0.00 412.77 699.99 1650.38 231.57 0.00 363.26 4169.48 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 15-JUN-19:03 0.00 -0.2 0.00 -0.5 0.00 0.00 421.39 699.99 1650.38 461.96 0.00 301.03 4999.86 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 16-JUN-18:10 0.00 -0.2 0.00 -0.7 0.00 0.00 408.58 631.63 1713.00 4070.23 0.00 302.74 3611.54 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 02-JUN-19:05 0.00 -0.2 0.00 -0.4 0.00 0.00 414.65 699.99 1650.38 224.43 0.00 365.33 4040.66 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 02-JUN-19:10 0.00 -0.2 0.00 -0.5 0.00 0.00 414.42 699.99 1650.38 552.17 0.00 414.95 4520.29 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 14-JUN-18:30 0.00 -0.2 0.00 -0.7 0.00 0.00 409.23 631.63 1713.00 1874.98 0.00 222.20 5265.04 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 14-JUN-18:15 0.00 -0.2 0.00 -0.4 0.00 0.00 415.27 631.63 1713.00 422.20 0.00 170.55 3496.73 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 02-JUN-19:10 0.00 -0.2 0.00 -0.5 0.00 0.00 414.05 699.99 1650.38 580.00 0.00 181.35 4653.21 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 14-JUN-18:30 0.00 -0.2 0.00 -0.6 0.00 0.00 404.58 631.63 1713.00 2086.46 0.00 218.97 5002.90 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 14-JUN-18:15 0.00 -0.2 0.00 -0.4 0.00 0.00 412.36 631.63 1713.00 693.51 0.00 169.00 3234.66 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 01-JUL-17:26 0.00 -0.2 0.00 -0.5 0.00 0.00 257.05 469.21 1675.86 1483.53 0.00 166.52 4005.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 15-JUN-19:03 0.00 -0.2 0.00 -0.6 0.00 0.00 426.06 699.99 1650.38 473.16 0.00 304.38 5573.93 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 15-JUN-19:03 0.00 -0.2 0.00 -0.6 0.00 0.00 421.26 699.99 1650.38 468.06 0.00 299.56 5505.84 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 15-JUN-19:10 0.00 -0.2 0.00 -0.7 0.00 0.00 408.93 699.99 1650.38 423.15 0.00 296.90 7683.47 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 14-JUN-18:30 0.00 -0.2 0.00 -0.5 0.00 0.00 409.68 631.63 1713.00 599.57 0.00 443.62 4001.55 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 02-JUN-19:05 0.00 -0.2 0.00 -0.5 0.00 0.00 415.10 699.99 1650.38 239.08 0.00 364.13 4571.64 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 16-JUN-18:10 0.00 -0.2 0.00 -0.7 0.00 0.00 413.80 631.63 1713.00 4066.31 0.00 307.19 4133.06 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 05-JUN-17:25 0.00 -0.4 0.00 -9.9 0.00 0.00 4599.24 8445.78 29804.87 42976.57 0.00 55374.94 15964.29 0.00 0.00 0.00 -33513.1 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 09-FEB-23:20 -4336.1 0.00 10824.53 0.00 0.00 0.00 528.94 120.31 1146.27 0.00 0.00 0.00 0.00 0.00 -1646.4 0.00 -795.7 -5841.8
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 12-JAN-06:50 -4549.1 0.00 10857.88 0.00 0.00 0.00 530.46 336.87 1074.44 0.00 0.00 0.00 0.00 0.00 -499.7 0.00 -439.7 -7311.1
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 08-JAN-22:47 -4422.8 0.00 11012.39 0.00 0.00 0.00 527.02 294.76 1349.09 0.00 0.00 0.00 0.00 0.00 -1361.6 0.00 -579.5 -6819.4
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 03-DEC-21:10 -4594.9 0.00 11209.45 0.00 0.00 0.00 531.89 529.36 1566.21 0.00 0.00 0.00 0.00 0.00 -1396.9 0.00 -608.7 -7236.4
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 14-DEC-00:38 -4368.9 0.00 10903.26 0.00 0.00 0.00 526.36 48.12 960.66 0.00 0.00 0.00 0.00 0.00 -471.3 0.00 -467.1 -7131.1
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 02-JAN-23:08 -4570.3 0.00 11349.40 0.00 0.00 0.00 528.52 120.31 1146.27 0.00 0.00 0.00 0.00 0.00 -1269.0 0.00 -529.0 -6776.2
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 18-JAN-02:38 -4444.7 0.00 11047.58 0.00 0.00 0.00 526.32 48.12 865.75 0.00 0.00 0.00 0.00 0.00 -1101.7 0.00 -186.2 -6755.1
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 26-FEB-09:18 -4096.2 0.00 10074.05 0.00 0.00 0.00 127.40 90.23 1112.20 0.00 0.00 0.00 0.00 0.00 -250.2 0.00 -177.7 -6879.8
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12-JAN-06:23 -4564.2 0.00 11266.57 0.00 0.00 0.00 535.33 336.87 1074.44 0.00 0.00 0.00 0.00 0.00 -1205.1 0.00 -207.8 -7236.1
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 27-MAR-07:03 -4499.3 0.00 10626.41 0.00 0.00 0.00 474.72 300.78 1204.45 0.00 0.00 0.00 0.00 0.00 -1028.9 0.00 -498.1 -6580.0
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 13-DEC-07:08 -4294.4 0.00 10401.72 0.00 0.00 0.00 464.80 300.78 1204.45 0.00 0.00 0.00 0.00 0.00 -421.5 0.00 -148.3 -7507.5
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 23-JAN-09:25 -4503.6 0.00 10864.94 0.00 0.00 0.00 127.29 90.23 1083.81 2762.46 0.00 0.00 0.00 0.00 0.00 0.00 -290.8 -10134.4
LIVING_UNIT3_BACKROW_TOPFLOOR 28-MAR-23:47 -4323.5 0.00 10607.59 0.00 0.00 0.00 526.93 120.31 1146.27 0.00 0.00 0.00 0.00 0.00 -1421.1 0.00 -580.6 -6076.0
LIVING_UNIT3_FRONTROW_TOPFLOOR 10-DEC-01:47 -4389.0 0.00 10880.76 0.00 0.00 0.00 526.61 48.12 892.75 0.00 0.00 0.00 0.00 0.00 -1374.2 0.00 -539.1 -6045.9
LIVING_UNIT1_FRONTROW_TOPFLOOR 05-NOV-01:47 -4298.3 0.00 10606.06 0.00 0.00 0.00 526.38 48.12 892.75 0.00 0.00 0.00 0.00 0.00 -1280.6 0.00 -538.0 -5956.4
LIVING_UNIT2_BACKROW_TOPFLOOR 13-JAN-03:47 -4593.3 0.00 10948.39 0.00 0.00 0.00 527.46 48.12 846.84 0.00 0.00 0.00 0.00 0.00 -568.5 0.00 -577.0 -6632.0
LIVING_UNIT2_FRONTROW_TOPFLOOR 05-FEB-04:08 -4473.2 0.00 10664.71 0.00 0.00 0.00 526.36 144.37 832.97 0.00 0.00 0.00 0.00 0.00 -627.8 0.00 -627.8 -6439.7
LIVING_UNIT1_BACKROW_TOPFLOOR 10-DEC-01:03 -4474.1 0.00 10965.73 0.00 0.00 0.00 534.59 48.12 892.75 0.00 0.00 0.00 0.00 0.00 -1350.9 0.00 -539.6 -6076.6
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 28-NOV-20:20 -76957.0 0.00 127941.94 0.00 0.00 0.00 8557.81 12599.76 29085.71 0.00 0.00 1952.47 0.00 0.00 -13977.2 0.00 -29369.8 -59833.6



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 397.5825 0.0000 2.0000 1.0000 0.0000 397.5825 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 235.1630 0.0000 2.0000 1.0000 0.0000 235.1630 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 282.9869 0.0000 2.0000 1.0000 0.0000 282.9869 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 392.2980 0.0000 2.0000 1.0000 0.0000 392.2980 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 234.1266 0.0000 2.0000 1.0000 0.0000 234.1266 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 280.8624 0.0000 2.0000 1.0000 0.0000 280.8624 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 376.0209 0.0000 2.0000 1.0000 0.0000 376.0209 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 220.5255 0.0000 2.0000 1.0000 0.0000 220.5255 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 270.7447 0.0000 2.0000 1.0000 0.0000 270.7447 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 371.4581 0.0000 2.0000 1.0000 0.0000 371.4581 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 219.3413 0.0000 2.0000 1.0000 0.0000 219.3413 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 267.7723 0.0000 2.0000 1.0000 0.0000 267.7723 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 418.2139 0.0000 2.0000 1.0000 0.0000 418.2139 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 265.3919 0.0000 2.0000 1.0000 0.0000 265.3919 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 313.0005 0.0000 2.0000 1.0000 0.0000 313.0005 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 421.1194 0.0000 2.0000 1.0000 0.0000 421.1194 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 268.8381 0.0000 2.0000 1.0000 0.0000 268.8381 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 317.4077 0.0000 2.0000 1.0000 0.0000 317.4077 0.0000 1.0000 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 397.5825 0.0000 2.0000 1.0000 0.0000 397.5825 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 235.1630 0.0000 2.0000 1.0000 0.0000 235.1630 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 282.9869 0.0000 2.0000 1.0000 0.0000 282.9869 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 392.2980 0.0000 2.0000 1.0000 0.0000 392.2980 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 234.1266 0.0000 2.0000 1.0000 0.0000 234.1266 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 280.8624 0.0000 2.0000 1.0000 0.0000 280.8624 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 376.0209 0.0000 2.0000 1.0000 0.0000 376.0209 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 220.5255 0.0000 2.0000 1.0000 0.0000 220.5255 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 270.7447 0.0000 2.0000 1.0000 0.0000 270.7447 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 371.4581 0.0000 2.0000 1.0000 0.0000 371.4581 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 219.3413 0.0000 2.0000 1.0000 0.0000 219.3413 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 267.7723 0.0000 2.0000 1.0000 0.0000 267.7723 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 418.2139 0.0000 2.0000 1.0000 0.0000 418.2139 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 265.3919 0.0000 2.0000 1.0000 0.0000 265.3919 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 313.0005 0.0000 2.0000 1.0000 0.0000 313.0005 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 421.1194 0.0000 2.0000 1.0000 0.0000 421.1194 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 268.8381 0.0000 2.0000 1.0000 0.0000 268.8381 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 317.4077 0.0000 2.0000 1.0000 0.0000 317.4077 0.0000 1.0000 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 397.5825 397.5825 397.5825 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 235.1630 235.1630 235.1630 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 282.9869 282.9869 282.9869 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 392.2980 392.2980 392.2980 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 234.1266 234.1266 234.1266 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 280.8624 280.8624 280.8624 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 376.0209 376.0209 376.0209 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 220.5255 220.5255 220.5255 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 270.7447 270.7447 270.7447 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 371.4581 371.4581 371.4581 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 219.3413 219.3413 219.3413 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 267.7723 267.7723 267.7723 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 317.4077 317.4077 317.4077 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 313.0005 313.0005 313.0005 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 418.2139 418.2139 418.2139 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 268.8381 268.8381 268.8381 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 265.3919 265.3919 265.3919 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 421.1194 421.1194 421.1194 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 397.5825 397.5825 397.5825 397.5825 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 235.1630 235.1630 235.1630 235.1630 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 282.9869 282.9869 282.9869 282.9869 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 392.2980 392.2980 392.2980 392.2980 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 234.1266 234.1266 234.1266 234.1266 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 280.8624 280.8624 280.8624 280.8624 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 376.0209 376.0209 376.0209 376.0209 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 220.5255 220.5255 220.5255 220.5255 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 270.7447 270.7447 270.7447 270.7447 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 371.4581 371.4581 371.4581 371.4581 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 219.3413 219.3413 219.3413 219.3413 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 267.7723 267.7723 267.7723 267.7723 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 418.2139 418.2139 418.2139 418.2139 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 265.3919 265.3919 265.3919 265.3919 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 313.0005 313.0005 313.0005 313.0005 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 421.1194 421.1194 421.1194 421.1194 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 268.8381 268.8381 268.8381 268.8381 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 317.4077 317.4077 317.4077 317.4077 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 397.5825 397.5825 397.5825 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 235.1630 235.1630 235.1630 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 282.9869 282.9869 282.9869 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 392.2980 392.2980 392.2980 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 234.1266 234.1266 234.1266 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 280.8624 280.8624 280.8624 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 376.0209 376.0209 376.0209 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 220.5255 220.5255 220.5255 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 270.7447 270.7447 270.7447 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 371.4581 371.4581 371.4581 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 219.3413 219.3413 219.3413 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 267.7723 267.7723 267.7723 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 317.4077 317.4077 317.4077 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 313.0005 313.0005 313.0005 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 418.2139 418.2139 418.2139 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 268.8381 268.8381 268.8381 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 265.3919 265.3919 265.3919 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 421.1194 421.1194 421.1194 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 397.5825 397.5825 397.5825 397.5825 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 235.1630 235.1630 235.1630 235.1630 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 282.9869 282.9869 282.9869 282.9869 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 392.2980 392.2980 392.2980 392.2980 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 234.1266 234.1266 234.1266 234.1266 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 280.8624 280.8624 280.8624 280.8624 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 376.0209 376.0209 376.0209 376.0209 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 220.5255 220.5255 220.5255 220.5255 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 270.7447 270.7447 270.7447 270.7447 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 371.4581 371.4581 371.4581 371.4581 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 219.3413 219.3413 219.3413 219.3413 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 267.7723 267.7723 267.7723 267.7723 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 418.2139 418.2139 418.2139 418.2139 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 265.3919 265.3919 265.3919 265.3919 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 313.0005 313.0005 313.0005 313.0005 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 421.1194 421.1194 421.1194 421.1194 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 268.8381 268.8381 268.8381 268.8381 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 317.4077 317.4077 317.4077 317.4077 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

Sec1.1A-General Information

Data
Weather File ANNUAL ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Total gross floor area [ft2] 39005.22
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
CRAWLSPACE 7794.39 0.00 7794.39 0.00
BREEZEWAY 1798.16 0.00 1798.16 0.00
ATTIC 7802.71 0.00 7802.71 0.00
Totals 39005.22 21609.96 17395.26  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 119.00
Number of hours cooling loads not met 85.67
Number of hours not met 204.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [kWh] Electricity Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Gasoline Use [therm] Gasoline Demand [Btu/h] Diesel Use [kBtu] Diesel Demand [Btu/h] Coal Use [kBtu] Coal Demand [Btu/h] Fuel Oil No 1 Use [kBtu] Fuel Oil No 1 Demand [Btu/h] Fuel Oil No 2 Use [kBtu] Fuel Oil No 2 Demand [Btu/h] Propane Use [kBtu] Propane Demand [Btu/h] Other Fuel 1 Use [kBtu] Other Fuel 1 Demand [Btu/h] Other Fuel 2 Use [kBtu] Other Fuel 2 Demand [Btu/h] District Cooling Use [ton-hrs] District Cooling Demand [ton] District Heating Use [kBtu] District Heating Demand [Btu/h]
Heating -- General 14271.08 26892.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 19054.27 10751.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- General 11336.81 3692.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Exterior-Lights 5508.71 1257.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- dishwasher 2758.31 880.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- refrigerator 12036.11 1639.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- clotheswasher 1408.53 381.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_dryer 12502.11 3196.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_range 9058.39 3721.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_mels 46926.68 7929.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- IECC_adj 3113.66 526.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 6120.47 2284.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation 2534.14 289.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 1308.75 149.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Other 12053.01 8960.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 299798.81 546276.17
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 299798.81 546276.17


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting (All) 0.29
Space Heating 0.37
Space Cooling 0.49
Fans (All) 0.22
Service Water Heating 0.34
Receptacle Equipment 2.25
Miscellaneous (All) 4.10
Subtotal 4.10


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous (All) 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 7.09
Space Heating 8.92
Space Cooling 11.91
Fans (All) 5.41
Service Water Heating 8.35
Receptacle Equipment 54.88
Miscellaneous 3.44


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
OCCUPANCY 6031. 8760.
INTERIORLIGHTING 2852. 8760.
INTERIORLIGHTINGHE 3070. 8760.
INTERIORLIGHTINGHE_OS 2910. 8760.
INTERIORLIGHTINGHE_VS 2149. 8760.
EXTERIORLIGHTING 4380. 4380.
REFRIGERATOR 7343. 8760.
MISCPLUGLOAD 5918. 8760.
COOKINGRANGE 2434. 8760.
DHW_SCH 365. 8760.
DISHWASHER 2799. 8760.
CLOTHESWASHER 3297. 8760.
CLOTHESDRYER 3911. 8760.
SINKS 4179. 8760.
SHOWERS 2640. 8760.
BATHS 2586. 8760.
DHWDIST 4662. 8760.
SHADING_2012IECC 0. 0.
SINKSENSSCHEDULE 6025. 8760.
SINKLATSCHEDULE 2735. 8760.
SHOWERSENSSCHEDULE 4492. 8760.
SHOWERLATSCHEDULE 4268. 8760.
BATHSENSSCHEDULE 8760. 8760.
BATHLATSCHEDULE 0. 0.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [F] Days with Same 11am Value 11pm First Wednesday [F] Days with Same 11pm Value
HEATING_SCH THERMOSTAT_LIVING DUAL SP CONTROL January 72.00 365 72.00 365
COOLING_SCH THERMOSTAT_LIVING DUAL SP CONTROL July 75.00 365 75.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
CRAWLSPACE 7919.83 840.17 0.00 0.00 0.00
BREEZEWAY 6289.17 2350.83 120.00 0.00 0.00
ATTIC 6580.83 1003.17 791.83 384.17 0.00
Min 6289.17 0.00 0.00 0.00 0.00
Max 8760.00 2350.83 791.83 384.17 0.00
Average 8498.56 199.72 43.42 18.29 0.00
Sum 178469.83 4194.17 911.83 384.17 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 9125.00 0.00 0.00 0.00 0.00
Average 7821.43 0.00 0.00 0.00 0.00
Sum 164250.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8706.17 53.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8710.33 49.67 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8714.67 45.33 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8706.67 53.33 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8710.33 49.67 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8712.17 47.83 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8737.83 22.17 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8740.33 19.67 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8740.50 19.50 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8737.67 22.33 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8741.50 18.50 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8740.83 19.17 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8741.83 18.17 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8739.83 20.17 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8734.83 25.17 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8740.17 19.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8739.50 20.50 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8735.67 24.33 0.00 0.00 0.00
CRAWLSPACE 7981.50 778.50 0.00 0.00 0.00
BREEZEWAY 7592.50 1167.50 0.00 0.00 0.00
ATTIC 6701.83 1442.33 438.00 174.17 3.67
Min 6701.83 18.17 0.00 0.00 0.00
Max 8741.83 1442.33 438.00 174.17 3.67
Average 8543.17 187.50 20.86 8.29 0.17
Sum 179406.67 3937.50 438.00 174.17 3.67


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 9044.17 80.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 9054.67 70.33 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 9046.83 78.17 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 9044.00 81.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 9053.67 71.33 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 9043.67 81.33 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9093.83 31.17 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 9100.50 24.50 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 9093.00 32.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 9092.83 32.17 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 9100.83 24.17 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 9093.67 31.33 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 9094.33 30.67 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 9090.83 34.17 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 9090.83 34.17 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 9100.50 24.50 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 9100.17 24.83 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 9091.00 34.00 0.00 0.00 0.00
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 9100.83 81.33 0.00 0.00 0.00
Average 7782.35 39.08 0.00 0.00 0.00
Sum 163429.33 820.67 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (F) SET ≤ 12.2°C OccupantHours (F) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (F) SET > 30°C OccupantHours (F) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2021-05-12 10:27:07

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 76.486 1.922 418.361 24.795 26.716
February 107.306 3.833 307.504 17.768 21.601
March 176.056 6.579 274.158 12.812 19.391
April 372.225 18.427 71.049 2.731 21.158
May 572.033 31.603 6.625 0.268 31.871
June 671.814 45.611 0.000 0.000 45.611
July 709.239 49.975 0.000 0.000 49.975
August 689.306 43.495 0.000 0.000 43.495
September 592.111 35.032 4.681 0.169 35.200
October 389.537 19.668 53.073 1.722 21.390
November 164.292 6.501 287.058 14.622 21.122
December 66.597 1.310 437.219 30.718 32.028
           
Annual Sum or Average 4587.001 263.955 1859.729 105.604 369.559
Minimum of Months 66.597 1.310 0.000 0.000 19.391
Maximum of Months 709.239 49.975 437.219 30.718 49.975



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 52.722 0.628 359.842 17.197 17.824
February 89.944 2.076 245.188 12.170 14.246
March 146.708 2.905 209.073 8.912 11.817
April 353.936 11.399 49.689 1.845 13.244
May 578.714 21.278 3.556 0.154 21.432
June 665.913 32.592 0.000 0.000 32.592
July 704.425 37.192 0.000 0.000 37.192
August 692.292 32.526 0.000 0.000 32.526
September 616.637 26.015 1.458 0.083 26.098
October 383.494 14.001 24.844 0.938 14.940
November 161.431 3.842 224.181 9.922 13.763
December 35.583 0.330 377.058 21.049 21.379
           
Annual Sum or Average 4481.800 184.785 1494.889 72.269 257.054
Minimum of Months 35.583 0.330 0.000 0.000 11.817
Maximum of Months 704.425 37.192 377.058 21.049 37.192



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 45.861 0.683 397.923 22.127 22.810
February 102.014 2.697 271.102 14.804 17.501
March 183.803 4.682 227.594 10.526 15.208
April 413.064 16.752 46.019 1.716 18.468
May 618.800 30.156 2.167 0.085 30.241
June 698.089 44.089 0.000 0.000 44.089
July 726.972 48.414 0.000 0.000 48.414
August 708.939 42.122 0.000 0.000 42.122
September 616.543 33.519 2.519 0.074 33.594
October 399.728 17.294 47.433 1.324 18.618
November 162.628 4.769 266.733 12.968 17.736
December 34.139 0.374 412.450 27.088 27.463
           
Annual Sum or Average 4710.579 245.553 1673.942 90.711 336.264
Minimum of Months 34.139 0.374 0.000 0.000 15.208
Maximum of Months 726.972 48.414 412.450 27.088 48.414



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 1.389 0.002 559.958 31.979 31.981
February 40.583 0.762 405.433 22.354 23.116
March 118.083 2.893 335.461 15.157 18.050
April 346.192 15.138 84.214 3.089 18.227
May 570.042 30.693 6.456 0.262 30.955
June 673.708 45.802 0.000 0.000 45.802
July 710.261 49.660 0.000 0.000 49.660
August 683.919 41.038 0.000 0.000 41.038
September 569.575 28.965 5.444 0.208 29.173
October 307.606 11.976 77.076 2.348 14.324
November 69.167 1.247 389.050 18.838 20.085
December 0.000 0.000 584.458 39.140 39.140
           
Annual Sum or Average 4090.525 228.176 2447.551 133.375 361.550
Minimum of Months 0.000 0.000 0.000 0.000 14.324
Maximum of Months 710.261 49.660 584.458 39.140 49.660



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 580.194 25.039 25.039
February 15.556 0.090 400.553 17.277 17.366
March 46.139 0.468 316.211 11.864 12.333
April 314.369 8.522 64.422 2.241 10.763
May 572.564 20.464 3.139 0.143 20.607
June 666.869 32.839 0.000 0.000 32.839
July 704.850 36.918 0.000 0.000 36.918
August 684.142 30.126 0.000 0.000 30.126
September 581.035 20.002 2.422 0.108 20.111
October 276.222 6.589 47.156 1.648 8.238
November 17.472 0.202 377.275 14.685 14.887
December 0.000 0.000 613.139 29.842 29.842
           
Annual Sum or Average 3879.217 156.219 2404.511 102.847 259.066
Minimum of Months 0.000 0.000 0.000 0.000 8.238
Maximum of Months 704.850 36.918 613.139 29.842 36.918



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 626.894 29.999 29.999
February 25.861 0.243 400.584 19.560 19.802
March 88.375 1.206 280.916 12.862 14.068
April 371.730 13.452 52.100 1.922 15.374
May 621.031 29.508 1.972 0.075 29.583
June 701.611 44.557 0.000 0.000 44.557
July 729.167 48.408 0.000 0.000 48.408
August 703.708 40.073 0.000 0.000 40.073
September 601.529 27.866 3.125 0.101 27.967
October 330.809 9.505 63.986 1.771 11.276
November 30.819 0.426 382.539 17.326 17.751
December 0.000 0.000 652.128 36.059 36.059
           
Annual Sum or Average 4204.640 215.243 2464.245 119.675 334.918
Minimum of Months 0.000 0.000 0.000 0.000 11.276
Maximum of Months 729.167 48.408 652.128 36.059 48.408



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 106.417 2.816 315.764 16.647 19.463
February 140.306 4.779 212.184 11.508 16.287
March 218.528 7.964 159.992 7.774 15.738
April 433.333 20.415 34.492 1.365 21.780
May 627.419 33.730 1.478 0.072 33.802
June 681.133 46.554 0.000 0.000 46.554
July 715.803 51.274 0.000 0.000 51.274
August 707.883 45.682 0.000 0.000 45.682
September 639.970 38.088 0.767 0.039 38.126
October 449.350 22.393 19.264 0.831 23.224
November 206.958 8.114 192.181 9.128 17.242
December 91.931 2.081 341.508 21.157 23.238
           
Annual Sum or Average 5019.031 283.890 1277.630 68.521 352.411
Minimum of Months 91.931 2.081 0.000 0.000 15.738
Maximum of Months 715.803 51.274 341.508 21.157 51.274



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 96.278 1.400 195.190 9.555 10.955
February 132.722 2.950 122.581 6.456 9.406
March 192.667 4.183 88.430 4.413 8.595
April 444.572 13.430 15.906 0.717 14.147
May 630.597 23.364 0.628 0.031 23.395
June 669.747 33.245 0.000 0.000 33.245
July 706.706 38.124 0.000 0.000 38.124
August 700.272 34.305 0.000 0.000 34.305
September 644.701 28.907 0.428 0.020 28.927
October 486.122 16.914 6.608 0.332 17.246
November 217.625 5.675 103.425 4.880 10.555
December 83.639 1.015 226.661 12.290 13.305
           
Annual Sum or Average 5005.648 203.511 759.858 38.695 242.206
Minimum of Months 83.639 1.015 0.000 0.000 8.595
Maximum of Months 706.706 38.124 226.661 12.290 38.124



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 84.861 1.404 286.554 14.764 16.168
February 138.264 3.849 180.717 9.593 13.443
March 220.989 6.471 124.697 6.143 12.614
April 483.492 19.798 19.486 0.737 20.535
May 671.372 33.333 0.278 0.017 33.350
June 703.775 45.907 0.000 0.000 45.907
July 732.472 50.407 0.000 0.000 50.407
August 724.072 44.997 0.000 0.000 44.997
September 662.846 37.223 0.278 0.016 37.239
October 475.616 20.647 15.878 0.645 21.292
November 222.072 6.769 172.117 8.104 14.873
December 72.556 1.013 311.486 18.825 19.838
           
Annual Sum or Average 5192.387 271.818 1111.490 58.845 330.662
Minimum of Months 72.556 1.013 0.000 0.000 12.614
Maximum of Months 732.472 50.407 311.486 18.825 50.407



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 4.194 0.017 457.028 22.757 22.773
February 55.833 1.006 306.170 15.483 16.489
March 149.556 3.738 217.256 9.519 13.257
April 404.747 17.008 42.760 1.625 18.633
May 625.858 32.886 1.214 0.062 32.948
June 683.000 46.779 0.000 0.000 46.779
July 717.217 51.011 0.000 0.000 51.011
August 703.208 43.331 0.000 0.000 43.331
September 623.037 32.137 1.458 0.078 32.215
October 366.379 14.134 26.013 1.088 15.222
November 95.569 1.691 288.664 12.665 14.356
December 0.000 0.000 498.986 28.626 28.626
           
Annual Sum or Average 4428.599 243.739 1839.548 91.901 335.640
Minimum of Months 0.000 0.000 0.000 0.000 13.257
Maximum of Months 717.217 51.011 498.986 28.626 51.011



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 395.169 16.158 16.158
February 28.000 0.234 245.879 10.804 11.038
March 94.944 0.951 151.806 6.523 7.473
April 387.972 10.218 21.807 0.916 11.134
May 627.806 22.588 0.586 0.028 22.616
June 669.161 33.469 0.000 0.000 33.469
July 707.044 37.838 0.000 0.000 37.838
August 694.203 32.001 0.000 0.000 32.001
September 614.551 23.049 0.556 0.030 23.079
October 374.580 8.691 14.283 0.665 9.356
November 43.056 0.415 208.567 8.435 8.849
December 0.000 0.000 451.961 20.026 20.026
           
Annual Sum or Average 4241.317 169.455 1490.614 63.583 233.038
Minimum of Months 0.000 0.000 0.000 0.000 7.473
Maximum of Months 707.044 37.838 451.961 20.026 37.838



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 464.346 21.432 21.432
February 40.778 0.489 273.455 13.354 13.843
March 130.417 2.103 167.054 7.789 9.892
April 452.421 16.018 22.222 0.819 16.836
May 670.508 32.146 0.278 0.017 32.162
June 703.856 45.614 0.000 0.000 45.614
July 732.750 49.593 0.000 0.000 49.593
August 721.339 42.283 0.000 0.000 42.283
September 650.718 31.168 0.236 0.008 31.176
October 388.242 12.086 20.794 0.716 12.802
November 56.639 0.785 260.197 11.452 12.237
December 0.000 0.000 520.069 26.567 26.567
           
Annual Sum or Average 4547.667 232.284 1728.653 82.154 314.438
Minimum of Months 0.000 0.000 0.000 0.000 9.892
Maximum of Months 732.750 49.593 520.069 26.567 49.593



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 76.792 1.701 393.636 22.845 24.546
February 110.292 3.840 275.979 15.995 19.836
March 189.986 7.006 230.222 10.842 17.848
April 417.289 21.213 51.285 2.012 23.225
May 615.825 36.588 2.611 0.113 36.700
June 683.711 52.295 0.000 0.000 52.295
July 716.756 57.327 0.000 0.000 57.327
August 705.042 50.272 0.000 0.000 50.272
September 634.070 40.636 1.989 0.093 40.729
October 432.436 22.356 32.410 1.131 23.487
November 183.347 6.824 256.169 13.043 19.868
December 61.167 1.076 415.683 28.845 29.921
           
Annual Sum or Average 4826.712 301.135 1659.985 94.918 396.053
Minimum of Months 61.167 1.076 0.000 0.000 17.848
Maximum of Months 716.756 57.327 415.683 28.845 57.327



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 53.500 0.636 314.889 15.742 16.378
February 98.833 2.283 204.740 10.830 13.113
March 164.667 3.541 157.712 7.352 10.893
April 417.800 14.396 32.102 1.212 15.608
May 627.686 26.526 1.072 0.050 26.575
June 676.497 39.337 0.000 0.000 39.337
July 712.972 44.641 0.000 0.000 44.641
August 702.003 39.397 0.000 0.000 39.397
September 641.254 31.949 0.656 0.037 31.986
October 443.883 17.103 11.942 0.543 17.646
November 178.653 4.514 181.283 8.464 12.978
December 34.139 0.277 346.572 19.844 20.121
           
Annual Sum or Average 4751.887 224.602 1250.969 64.073 288.675
Minimum of Months 34.139 0.277 0.000 0.000 10.893
Maximum of Months 712.972 44.641 346.572 19.844 44.641



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 43.056 0.615 372.146 21.031 21.646
February 107.836 2.927 237.937 13.563 16.490
March 188.564 5.311 182.167 9.086 14.397
April 466.534 20.204 30.078 1.196 21.400
May 662.286 35.974 0.417 0.023 35.997
June 705.828 51.505 0.000 0.000 51.505
July 732.361 56.458 0.000 0.000 56.458
August 722.633 49.555 0.000 0.000 49.555
September 658.267 39.740 0.778 0.027 39.767
October 455.505 20.427 30.061 0.982 21.409
November 180.019 5.252 238.264 11.729 16.981
December 30.889 0.280 393.997 26.451 26.731
           
Annual Sum or Average 4953.778 288.248 1485.845 84.087 372.335
Minimum of Months 30.889 0.280 0.000 0.000 14.397
Maximum of Months 732.361 56.458 393.997 26.451 56.458



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 3.222 0.025 515.819 29.260 29.285
February 58.111 1.230 354.092 19.881 21.112
March 143.528 4.155 279.794 12.612 16.766
April 401.817 19.131 60.338 2.208 21.339
May 613.642 36.216 2.403 0.105 36.322
June 684.006 52.695 0.000 0.000 52.695
July 717.356 57.453 0.000 0.000 57.453
August 704.042 49.039 0.000 0.000 49.039
September 623.230 36.914 2.361 0.106 37.020
October 360.222 16.149 44.606 1.533 17.682
November 93.139 1.944 340.783 16.599 18.543
December 0.000 0.000 544.000 36.515 36.515
           
Annual Sum or Average 4402.313 274.950 2144.197 118.821 393.771
Minimum of Months 0.000 0.000 0.000 0.000 16.766
Maximum of Months 717.356 57.453 544.000 36.515 57.453



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 511.417 22.930 22.930
February 30.597 0.351 327.267 15.187 15.538
March 93.583 1.328 222.108 9.306 10.635
April 386.947 12.516 40.774 1.455 13.971
May 625.481 26.221 1.039 0.048 26.269
June 676.342 39.782 0.000 0.000 39.782
July 713.028 44.817 0.000 0.000 44.817
August 699.658 38.215 0.000 0.000 38.215
September 623.292 28.218 0.778 0.047 28.265
October 355.676 10.872 21.623 0.911 11.784
November 43.056 0.516 304.142 12.636 13.151
December 0.000 0.000 559.181 28.247 28.247
           
Annual Sum or Average 4247.660 202.836 1988.328 90.767 293.604
Minimum of Months 0.000 0.000 0.000 0.000 10.635
Maximum of Months 713.028 44.817 559.181 28.247 44.817



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 557.844 28.105 28.105
February 42.097 0.591 336.248 17.831 18.422
March 120.861 2.404 225.540 10.723 13.127
April 435.733 17.988 33.328 1.276 19.264
May 662.714 35.681 0.417 0.023 35.704
June 706.828 51.996 0.000 0.000 51.996
July 733.444 56.658 0.000 0.000 56.658
August 719.694 48.488 0.000 0.000 48.488
September 651.683 36.195 1.228 0.036 36.231
October 390.596 13.921 37.619 1.224 15.145
November 56.278 0.845 324.592 15.396 16.241
December 0.000 0.000 597.525 34.741 34.741
           
Annual Sum or Average 4519.929 264.767 2114.341 109.355 374.121
Minimum of Months 0.000 0.000 0.000 0.000 13.127
Maximum of Months 733.444 56.658 597.525 34.741 56.658



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1757.50 0.00 0.00
February 1394.67 0.00 0.00
March 989.96 0.00 0.00
April 253.26 0.00 0.00
May 28.14 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 17.81 0.00 0.00
October 165.17 0.00 0.00
November 1113.66 0.00 0.00
December 1997.33 0.00 0.00
       
Annual Sum or Average 640.20 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1997.33 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1272.65 0.00 0.00
February 996.13 0.00 0.00
March 726.92 0.00 0.00
April 180.29 0.00 0.00
May 17.15 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 8.92 0.00 0.00
October 95.66 0.00 0.00
November 786.12 0.00 0.00
December 1423.16 0.00 0.00
       
Annual Sum or Average 456.86 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1423.16 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1641.92 0.00 0.00
February 1206.40 0.00 0.00
March 827.19 0.00 0.00
April 155.74 0.00 0.00
May 8.87 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 7.62 0.00 0.00
October 127.48 0.00 0.00
November 1022.57 0.00 0.00
December 1843.21 0.00 0.00
       
Annual Sum or Average 567.85 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1843.21 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2370.30 0.00 0.00
February 1835.48 0.00 0.00
March 1203.58 0.00 0.00
April 292.46 0.00 0.00
May 27.58 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 22.32 0.00 0.00
October 230.50 0.00 0.00
November 1507.61 0.00 0.00
December 2689.20 0.00 0.00
       
Annual Sum or Average 844.44 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2689.20 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1975.56 0.00 0.00
February 1514.40 0.00 0.00
March 1004.89 0.00 0.00
April 225.16 0.00 0.00
May 16.02 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 12.45 0.00 0.00
October 172.98 0.00 0.00
November 1249.11 0.00 0.00
December 2184.54 0.00 0.00
       
Annual Sum or Average 693.09 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2184.54 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2323.55 0.00 0.00
February 1665.87 0.00 0.00
March 1033.00 0.00 0.00
April 176.19 0.00 0.00
May 7.74 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 10.21 0.00 0.00
October 171.66 0.00 0.00
November 1428.31 0.00 0.00
December 2594.57 0.00 0.00
       
Annual Sum or Average 781.18 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2594.57 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1169.36 0.00 0.00
February 892.51 0.00 0.00
March 599.24 0.00 0.00
April 127.10 0.00 0.00
May 7.81 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 4.57 0.00 0.00
October 81.58 0.00 0.00
November 687.98 0.00 0.00
December 1353.61 0.00 0.00
       
Annual Sum or Average 408.60 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1353.61 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 715.43 0.00 0.00
February 529.65 0.00 0.00
March 368.54 0.00 0.00
April 72.18 0.00 0.00
May 3.58 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 2.29 0.00 0.00
October 34.90 0.00 0.00
November 394.21 0.00 0.00
December 825.67 0.00 0.00
       
Annual Sum or Average 244.61 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 825.67 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1053.37 0.00 0.00
February 748.61 0.00 0.00
March 466.29 0.00 0.00
April 63.62 0.00 0.00
May 1.79 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 1.66 0.00 0.00
October 63.41 0.00 0.00
November 620.40 0.00 0.00
December 1225.09 0.00 0.00
       
Annual Sum or Average 352.44 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1225.09 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1672.87 0.00 0.00
February 1259.42 0.00 0.00
March 755.12 0.00 0.00
April 155.10 0.00 0.00
May 6.65 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 8.52 0.00 0.00
October 110.43 0.00 0.00
November 1011.46 0.00 0.00
December 1946.41 0.00 0.00
       
Annual Sum or Average 574.66 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1946.41 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1293.77 0.00 0.00
February 958.65 0.00 0.00
March 569.41 0.00 0.00
April 95.85 0.00 0.00
May 3.26 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 3.39 0.00 0.00
October 73.08 0.00 0.00
November 735.50 0.00 0.00
December 1474.16 0.00 0.00
       
Annual Sum or Average 432.08 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1474.16 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1644.35 0.00 0.00
February 1117.78 0.00 0.00
March 612.14 0.00 0.00
April 72.59 0.00 0.00
May 1.78 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.88 0.00 0.00
October 71.05 0.00 0.00
November 934.71 0.00 0.00
December 1883.27 0.00 0.00
       
Annual Sum or Average 526.39 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1883.27 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1598.84 0.00 0.00
February 1234.20 0.00 0.00
March 824.89 0.00 0.00
April 183.97 0.00 0.00
May 11.87 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 9.76 0.00 0.00
October 108.42 0.00 0.00
November 978.32 0.00 0.00
December 1851.01 0.00 0.00
       
Annual Sum or Average 564.29 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1851.01 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1142.23 0.00 0.00
February 863.33 0.00 0.00
March 586.42 0.00 0.00
April 115.52 0.00 0.00
May 5.47 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 4.08 0.00 0.00
October 54.53 0.00 0.00
November 653.85 0.00 0.00
December 1307.15 0.00 0.00
       
Annual Sum or Average 392.73 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1307.15 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1507.39 0.00 0.00
February 1059.00 0.00 0.00
March 684.04 0.00 0.00
April 103.17 0.00 0.00
May 2.33 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 2.62 0.00 0.00
October 93.38 0.00 0.00
November 889.14 0.00 0.00
December 1735.44 0.00 0.00
       
Annual Sum or Average 504.66 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1735.44 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2130.06 0.00 0.00
February 1596.17 0.00 0.00
March 980.66 0.00 0.00
April 204.93 0.00 0.00
May 11.07 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 11.25 0.00 0.00
October 150.84 0.00 0.00
November 1304.58 0.00 0.00
December 2463.87 0.00 0.00
       
Annual Sum or Average 734.65 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2463.87 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1752.09 0.00 0.00
February 1279.22 0.00 0.00
March 764.65 0.00 0.00
April 140.48 0.00 0.00
May 5.23 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 5.38 0.00 0.00
October 95.79 0.00 0.00
November 1037.84 0.00 0.00
December 1998.82 0.00 0.00
       
Annual Sum or Average 587.51 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1998.82 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2105.60 0.00 0.00
February 1454.07 0.00 0.00
March 823.58 0.00 0.00
April 110.82 0.00 0.00
May 2.31 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 3.48 0.00 0.00
October 116.82 0.00 0.00
November 1219.82 0.00 0.00
December 2412.78 0.00 0.00
       
Annual Sum or Average 685.02 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2412.78 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5.89 0.00 0.00
February 9.46 0.00 0.00
March 2.66 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 2.14 0.00 0.00
December 24.94 0.00 0.00
       
Annual Sum or Average 3.75 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 24.94 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 62.07 0.00 0.00
February 54.57 0.00 0.00
March 21.24 0.00 0.00
April 0.96 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.02 0.00 0.00
October 1.71 0.00 0.00
November 19.26 0.00 0.00
December 103.76 0.00 0.00
       
Annual Sum or Average 21.88 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 103.76 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 51.33 0.00 0.00
February 47.27 0.00 0.00
March 17.10 0.00 0.00
April 0.24 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.20 0.00 0.00
November 12.55 0.00 0.00
December 105.36 0.00 0.00
       
Annual Sum or Average 19.45 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 105.36 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 9.45 0.00 0.00
February 11.90 0.00 0.00
March 2.72 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 1.32 0.00 0.00
December 31.76 0.00 0.00
       
Annual Sum or Average 4.75 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 31.76 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 80.84 0.00 0.00
February 66.62 0.00 0.00
March 20.63 0.00 0.00
April 1.79 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 1.39 0.00 0.00
November 22.32 0.00 0.00
December 140.25 0.00 0.00
       
Annual Sum or Average 27.74 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 140.25 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 59.87 0.00 0.00
February 54.84 0.00 0.00
March 17.25 0.00 0.00
April 0.26 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.10 0.00 0.00
November 10.71 0.00 0.00
December 116.84 0.00 0.00
       
Annual Sum or Average 21.59 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 116.84 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1.03 0.00 0.00
February 4.12 0.00 0.00
March 0.71 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 1.05 0.00 0.00
December 5.36 0.00 0.00
       
Annual Sum or Average 1.01 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 5.36 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 57.36 0.00 0.00
February 52.24 0.00 0.00
March 19.52 0.00 0.00
April 2.93 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.17 0.00 0.00
November 33.16 0.00 0.00
December 77.97 0.00 0.00
       
Annual Sum or Average 20.14 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 77.97 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 34.22 0.00 0.00
February 31.02 0.00 0.00
March 14.00 0.00 0.00
April 0.83 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.26 0.00 0.00
November 14.71 0.00 0.00
December 57.32 0.00 0.00
       
Annual Sum or Average 12.64 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 57.32 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2.92 0.00 0.00
February 4.70 0.00 0.00
March 2.27 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.58 0.00 0.00
December 12.11 0.00 0.00
       
Annual Sum or Average 1.88 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 12.11 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 57.21 0.00 0.00
February 50.04 0.00 0.00
March 24.01 0.00 0.00
April 2.74 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.34 0.00 0.00
November 37.98 0.00 0.00
December 87.08 0.00 0.00
       
Annual Sum or Average 21.51 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 87.08 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 35.54 0.00 0.00
February 28.99 0.00 0.00
March 13.27 0.00 0.00
April 0.08 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.75 0.00 0.00
November 14.62 0.00 0.00
December 65.74 0.00 0.00
       
Annual Sum or Average 13.22 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 65.74 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 3.04 0.00 0.00
February 3.39 0.00 0.00
March 1.10 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.78 0.00 0.00
December 14.53 0.00 0.00
       
Annual Sum or Average 1.91 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 14.53 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 31.60 0.00 0.00
February 24.86 0.00 0.00
March 11.85 0.00 0.00
April 0.58 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.27 0.00 0.00
November 11.19 0.00 0.00
December 57.79 0.00 0.00
       
Annual Sum or Average 11.50 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 57.79 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 30.04 0.00 0.00
February 30.60 0.00 0.00
March 6.84 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 6.38 0.00 0.00
December 60.82 0.00 0.00
       
Annual Sum or Average 11.17 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 60.82 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 3.95 0.00 0.00
February 4.80 0.00 0.00
March 1.27 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 1.06 0.00 0.00
December 18.75 0.00 0.00
       
Annual Sum or Average 2.49 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 18.75 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 36.94 0.00 0.00
February 34.56 0.00 0.00
March 14.79 0.00 0.00
April 0.20 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.67 0.00 0.00
November 8.56 0.00 0.00
December 76.07 0.00 0.00
       
Annual Sum or Average 14.28 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 76.07 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 30.49 0.00 0.00
February 23.13 0.00 0.00
March 7.34 0.00 0.00
April 0.05 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 4.19 0.00 0.00
December 60.78 0.00 0.00
       
Annual Sum or Average 10.50 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 60.78 0.00 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.03
March 0.00 0.00 0.04
April 0.00 0.00 0.13
May 0.00 0.00 0.22
June 0.00 0.00 0.32
July 0.00 0.00 0.36
August 0.00 0.00 0.31
September 0.00 0.00 0.26
October 0.00 0.00 0.14
November 0.00 0.00 0.05
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.16
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.36



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.02
March 0.00 0.00 0.02
April 0.00 0.00 0.08
May 0.00 0.00 0.15
June 0.00 0.00 0.24
July 0.00 0.00 0.28
August 0.00 0.00 0.24
September 0.00 0.00 0.20
October 0.00 0.00 0.10
November 0.00 0.00 0.03
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.11
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.28



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.02
March 0.00 0.00 0.03
April 0.00 0.00 0.12
May 0.00 0.00 0.21
June 0.00 0.00 0.33
July 0.00 0.00 0.37
August 0.00 0.00 0.31
September 0.00 0.00 0.26
October 0.00 0.00 0.13
November 0.00 0.00 0.03
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.15
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.37



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.02
April 0.00 0.00 0.11
May 0.00 0.00 0.21
June 0.00 0.00 0.32
July 0.00 0.00 0.36
August 0.00 0.00 0.29
September 0.00 0.00 0.21
October 0.00 0.00 0.08
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.14
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.36



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.06
May 0.00 0.00 0.14
June 0.00 0.00 0.24
July 0.00 0.00 0.28
August 0.00 0.00 0.22
September 0.00 0.00 0.15
October 0.00 0.00 0.05
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.28



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.10
May 0.00 0.00 0.21
June 0.00 0.00 0.33
July 0.00 0.00 0.36
August 0.00 0.00 0.29
September 0.00 0.00 0.21
October 0.00 0.00 0.07
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.13
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.36



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.04
March 0.00 0.00 0.05
April 0.00 0.00 0.14
May 0.00 0.00 0.23
June 0.00 0.00 0.33
July 0.00 0.00 0.37
August 0.00 0.00 0.33
September 0.00 0.00 0.28
October 0.00 0.00 0.16
November 0.00 0.00 0.06
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.17
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.37



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.02
March 0.00 0.00 0.03
April 0.00 0.00 0.10
May 0.00 0.00 0.17
June 0.00 0.00 0.25
July 0.00 0.00 0.29
August 0.00 0.00 0.26
September 0.00 0.00 0.22
October 0.00 0.00 0.13
November 0.00 0.00 0.04
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.13
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.29



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.03
March 0.00 0.00 0.04
April 0.00 0.00 0.14
May 0.00 0.00 0.24
June 0.00 0.00 0.34
July 0.00 0.00 0.38
August 0.00 0.00 0.33
September 0.00 0.00 0.29
October 0.00 0.00 0.15
November 0.00 0.00 0.05
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.17
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.38



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.02
April 0.00 0.00 0.12
May 0.00 0.00 0.23
June 0.00 0.00 0.33
July 0.00 0.00 0.37
August 0.00 0.00 0.31
September 0.00 0.00 0.24
October 0.00 0.00 0.10
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.15
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.37



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.07
May 0.00 0.00 0.16
June 0.00 0.00 0.25
July 0.00 0.00 0.29
August 0.00 0.00 0.24
September 0.00 0.00 0.18
October 0.00 0.00 0.06
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.11
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.29



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.12
May 0.00 0.00 0.23
June 0.00 0.00 0.34
July 0.00 0.00 0.38
August 0.00 0.00 0.31
September 0.00 0.00 0.24
October 0.00 0.00 0.09
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.14
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.38



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.03
March 0.00 0.00 0.05
April 0.00 0.00 0.15
May 0.00 0.00 0.25
June 0.00 0.00 0.37
July 0.00 0.00 0.41
August 0.00 0.00 0.36
September 0.00 0.00 0.30
October 0.00 0.00 0.16
November 0.00 0.00 0.05
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.18
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.41



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.02
March 0.00 0.00 0.02
April 0.00 0.00 0.10
May 0.00 0.00 0.18
June 0.00 0.00 0.28
July 0.00 0.00 0.33
August 0.00 0.00 0.29
September 0.00 0.00 0.24
October 0.00 0.00 0.12
November 0.00 0.00 0.03
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.14
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.33



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.02
March 0.00 0.00 0.04
April 0.00 0.00 0.14
May 0.00 0.00 0.25
June 0.00 0.00 0.37
July 0.00 0.00 0.42
August 0.00 0.00 0.36
September 0.00 0.00 0.30
October 0.00 0.00 0.15
November 0.00 0.00 0.04
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.18
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.42



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.03
April 0.00 0.00 0.13
May 0.00 0.00 0.25
June 0.00 0.00 0.37
July 0.00 0.00 0.41
August 0.00 0.00 0.35
September 0.00 0.00 0.27
October 0.00 0.00 0.11
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.16
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.41



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.09
May 0.00 0.00 0.18
June 0.00 0.00 0.29
July 0.00 0.00 0.33
August 0.00 0.00 0.28
September 0.00 0.00 0.21
October 0.00 0.00 0.08
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.12
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.33



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.02
April 0.00 0.00 0.13
May 0.00 0.00 0.25
June 0.00 0.00 0.38
July 0.00 0.00 0.42
August 0.00 0.00 0.35
September 0.00 0.00 0.27
October 0.00 0.00 0.10
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.16
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.42



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.05
March 0.00 0.00 0.05
April 0.00 0.00 0.05
May 0.00 0.00 0.04
June 0.00 0.00 0.04
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.04
October 0.00 0.00 0.04
November 0.00 0.00 0.05
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.05



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.05
March 0.00 0.00 0.05
April 0.00 0.00 0.05
May 0.00 0.00 0.04
June 0.00 0.00 0.04
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.04
October 0.00 0.00 0.04
November 0.00 0.00 0.05
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.05



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.05
March 0.00 0.00 0.05
April 0.00 0.00 0.05
May 0.00 0.00 0.04
June 0.00 0.00 0.04
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.04
October 0.00 0.00 0.04
November 0.00 0.00 0.05
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.05



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.05
March 0.00 0.00 0.05
April 0.00 0.00 0.05
May 0.00 0.00 0.04
June 0.00 0.00 0.04
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.04
October 0.00 0.00 0.04
November 0.00 0.00 0.05
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.05



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.05
March 0.00 0.00 0.05
April 0.00 0.00 0.05
May 0.00 0.00 0.04
June 0.00 0.00 0.04
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.04
October 0.00 0.00 0.04
November 0.00 0.00 0.05
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.05



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.05
March 0.00 0.00 0.05
April 0.00 0.00 0.05
May 0.00 0.00 0.04
June 0.00 0.00 0.04
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.04
October 0.00 0.00 0.04
November 0.00 0.00 0.05
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.05



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.05
March 0.00 0.00 0.05
April 0.00 0.00 0.05
May 0.00 0.00 0.04
June 0.00 0.00 0.04
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.04
October 0.00 0.00 0.04
November 0.00 0.00 0.05
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.05



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.05
March 0.00 0.00 0.05
April 0.00 0.00 0.05
May 0.00 0.00 0.04
June 0.00 0.00 0.04
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.04
October 0.00 0.00 0.04
November 0.00 0.00 0.05
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.05



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.05
March 0.00 0.00 0.05
April 0.00 0.00 0.05
May 0.00 0.00 0.04
June 0.00 0.00 0.04
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.04
October 0.00 0.00 0.04
November 0.00 0.00 0.05
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.05



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.05
March 0.00 0.00 0.05
April 0.00 0.00 0.05
May 0.00 0.00 0.04
June 0.00 0.00 0.04
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.04
October 0.00 0.00 0.04
November 0.00 0.00 0.05
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.05



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.05
March 0.00 0.00 0.05
April 0.00 0.00 0.05
May 0.00 0.00 0.04
June 0.00 0.00 0.04
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.04
October 0.00 0.00 0.04
November 0.00 0.00 0.05
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.05



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.05
March 0.00 0.00 0.05
April 0.00 0.00 0.05
May 0.00 0.00 0.04
June 0.00 0.00 0.04
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.04
October 0.00 0.00 0.04
November 0.00 0.00 0.05
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.05



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.05
March 0.00 0.00 0.05
April 0.00 0.00 0.05
May 0.00 0.00 0.04
June 0.00 0.00 0.04
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.04
October 0.00 0.00 0.04
November 0.00 0.00 0.05
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.05



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.05
March 0.00 0.00 0.05
April 0.00 0.00 0.05
May 0.00 0.00 0.04
June 0.00 0.00 0.04
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.04
October 0.00 0.00 0.04
November 0.00 0.00 0.05
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.05



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.05
March 0.00 0.00 0.05
April 0.00 0.00 0.05
May 0.00 0.00 0.04
June 0.00 0.00 0.04
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.04
October 0.00 0.00 0.04
November 0.00 0.00 0.05
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.05



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.05
March 0.00 0.00 0.05
April 0.00 0.00 0.05
May 0.00 0.00 0.04
June 0.00 0.00 0.04
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.04
October 0.00 0.00 0.04
November 0.00 0.00 0.05
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.05



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.05
March 0.00 0.00 0.05
April 0.00 0.00 0.05
May 0.00 0.00 0.04
June 0.00 0.00 0.04
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.04
October 0.00 0.00 0.04
November 0.00 0.00 0.05
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.05



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.05
March 0.00 0.00 0.05
April 0.00 0.00 0.05
May 0.00 0.00 0.04
June 0.00 0.00 0.04
July 0.00 0.00 0.03
August 0.00 0.00 0.03
September 0.00 0.00 0.04
October 0.00 0.00 0.04
November 0.00 0.00 0.05
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.05



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00
         
Annual Sum or Average 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: CRAWLSPACE

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: BREEZEWAY

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 48.02 597.89
February 55.39 413.28
March 74.32 294.72
April 126.40 67.53
May 172.60 7.15
June 212.34 0.43
July 210.18 0.16
August 198.05 0.13
September 176.19 4.59
October 131.71 38.12
November 72.74 347.27
December 43.45 734.50
     
Annual Sum or Average 1521.37 2505.77
Minimum of Months 43.45 0.13
Maximum of Months 212.34 734.50



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 48.29 329.27
February 54.21 241.31
March 63.92 183.83
April 96.33 40.57
May 125.87 4.26
June 155.54 0.56
July 156.87 0.32
August 150.79 0.36
September 136.48 2.15
October 109.27 21.14
November 67.52 193.73
December 45.99 418.79
     
Annual Sum or Average 1211.10 1436.28
Minimum of Months 45.99 0.32
Maximum of Months 156.87 418.79



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 44.36 563.63
February 56.24 372.75
March 72.70 257.78
April 125.98 45.51
May 172.13 1.75
June 215.24 0.01
July 213.63 0.01
August 200.38 0.00
September 175.36 1.36
October 125.15 29.13
November 68.96 328.57
December 42.07 705.05
     
Annual Sum or Average 1512.20 2305.55
Minimum of Months 42.07 0.00
Maximum of Months 215.24 705.05



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 20.07 866.72
February 28.01 584.71
March 48.71 374.49
April 108.59 79.94
May 168.13 6.66
June 213.45 0.31
July 208.64 0.10
August 185.85 0.15
September 145.90 6.77
October 90.78 59.92
November 34.54 503.60
December 17.47 1057.69
     
Annual Sum or Average 1270.14 3541.06
Minimum of Months 17.47 0.10
Maximum of Months 213.45 1057.69



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 18.13 581.79
February 25.11 393.56
March 38.38 245.59
April 79.93 55.20
May 121.85 4.26
June 156.91 0.48
July 155.48 0.27
August 138.55 0.58
September 105.71 4.11
October 68.33 39.40
November 30.07 328.59
December 15.91 713.58
     
Annual Sum or Average 954.35 2367.43
Minimum of Months 15.91 0.27
Maximum of Months 156.91 713.58



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 12.40 773.42
February 26.09 499.94
March 46.87 322.68
April 107.38 49.76
May 167.53 1.67
June 216.13 0.01
July 211.71 0.03
August 187.85 0.03
September 143.98 2.45
October 82.17 36.84
November 30.63 450.91
December 10.05 953.49
     
Annual Sum or Average 1242.78 3091.23
Minimum of Months 10.05 0.01
Maximum of Months 216.13 953.49



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 65.79 282.65
February 72.78 195.30
March 95.53 143.58
April 142.37 27.35
May 185.54 1.43
June 219.24 0.23
July 219.95 0.04
August 210.48 0.07
September 192.82 0.97
October 150.29 18.20
November 92.93 158.69
December 60.41 363.37
     
Annual Sum or Average 1708.15 1191.89
Minimum of Months 60.41 0.04
Maximum of Months 219.95 363.37



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 75.42 155.06
February 77.22 114.73
March 87.00 85.84
April 113.09 16.90
May 139.10 1.27
June 161.76 0.26
July 165.77 0.16
August 162.66 0.16
September 153.62 0.33
October 128.57 7.00
November 94.13 99.16
December 71.38 179.62
     
Annual Sum or Average 1429.73 660.49
Minimum of Months 71.38 0.16
Maximum of Months 165.77 179.62



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 63.58 270.11
February 74.49 176.93
March 94.96 125.05
April 144.46 14.58
May 187.65 0.39
June 223.06 0.00
July 223.52 0.01
August 213.63 0.00
September 193.01 0.20
October 144.81 14.40
November 90.81 162.25
December 59.45 347.69
     
Annual Sum or Average 1713.44 1111.61
Minimum of Months 59.45 0.00
Maximum of Months 223.52 347.69



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 32.09 451.28
February 40.83 301.69
March 66.84 181.33
April 123.96 32.95
May 181.29 1.23
June 220.45 0.14
July 218.57 0.03
August 198.47 0.08
September 162.38 2.19
October 107.06 26.75
November 48.32 255.05
December 27.37 571.40
     
Annual Sum or Average 1427.64 1824.11
Minimum of Months 27.37 0.03
Maximum of Months 220.45 571.40



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 38.74 271.14
February 43.96 194.96
March 61.01 137.50
April 95.49 24.03
May 135.21 1.44
June 163.24 0.19
July 164.52 0.09
August 150.63 0.26
September 122.59 1.43
October 84.30 17.46
November 51.41 181.88
December 33.76 323.13
     
Annual Sum or Average 1144.86 1153.51
Minimum of Months 33.76 0.09
Maximum of Months 164.52 323.13



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 30.03 430.36
February 42.11 262.25
March 65.85 154.35
April 125.30 15.30
May 183.19 0.39
June 224.19 0.00
July 221.99 0.01
August 201.32 0.00
September 162.18 0.04
October 100.55 16.06
November 46.43 237.19
December 24.65 526.87
     
Annual Sum or Average 1427.81 1642.82
Minimum of Months 24.65 0.00
Maximum of Months 224.19 526.87



Table of Contents

Report: HEATING AND COOLING LOADS

For: ATTIC

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 20.06 674.20
February 34.54 405.98
March 59.67 233.49
April 131.14 29.76
May 195.37 0.49
June 248.12 0.00
July 246.76 0.00
August 224.68 0.00
September 181.87 0.39
October 105.73 25.67
November 39.45 365.74
December 15.41 835.60
     
Annual Sum or Average 1502.81 2571.33
Minimum of Months 15.41 0.00
Maximum of Months 248.12 835.60



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 47.17 480.30
February 60.97 305.40
March 80.26 194.87
April 142.83 26.66
May 197.37 0.50
June 246.39 0.00
July 246.59 0.00
August 231.22 0.00
September 201.24 0.44
October 139.90 19.38
November 74.20 264.28
December 43.76 615.16
     
Annual Sum or Average 1711.90 1906.98
Minimum of Months 43.76 0.00
Maximum of Months 246.59 615.16



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 50.11 508.55
February 59.03 338.58
March 81.14 221.44
April 142.06 44.27
May 196.34 2.47
June 243.02 0.09
July 243.12 0.02
August 228.48 0.05
September 201.52 1.87
October 146.32 22.91
November 77.49 283.58
December 45.55 650.33
     
Annual Sum or Average 1714.17 2074.17
Minimum of Months 45.55 0.02
Maximum of Months 243.12 650.33



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 25.40 461.06
February 34.81 303.82
March 54.46 190.85
April 102.39 28.83
May 148.72 1.38
June 187.92 0.22
July 189.79 0.03
August 174.76 0.18
September 143.68 1.84
October 92.43 25.21
November 40.20 256.35
December 21.19 584.64
     
Annual Sum or Average 1215.74 1854.41
Minimum of Months 21.19 0.03
Maximum of Months 189.79 584.64



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 54.15 272.27
February 60.28 186.88
March 73.70 145.33
April 113.24 24.03
May 150.46 1.31
June 186.04 0.27
July 189.40 0.08
August 181.19 0.15
September 162.90 0.85
October 125.52 13.43
November 76.34 156.58
December 50.00 344.13
     
Annual Sum or Average 1423.22 1145.30
Minimum of Months 50.00 0.08
Maximum of Months 189.40 344.13



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:27:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 25.69 738.98
February 36.24 479.96
March 61.66 278.85
April 130.69 49.30
May 194.43 2.38
June 244.81 0.07
July 243.44 0.02
August 222.09 0.07
September 182.70 2.62
October 113.82 36.98
November 43.90 417.50
December 22.69 932.65
     
Annual Sum or Average 1522.18 2939.37
Minimum of Months 22.69 0.02