Program Version:EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:30
Tabular Output Report in Format: HTML
Building: US+MF+CZ3C+oilfurnace+heatedbsmt+IECC_2015
Environment: ANNUAL ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2021-05-12 10:30:51
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 683974.59 | 17.54 | 23.26 |
Net Site Energy | 683974.59 | 17.54 | 23.26 |
Total Source Energy | 1646837.03 | 42.22 | 56.01 |
Net Source Energy | 1646837.03 | 42.22 | 56.01 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.22 |
Net Conditioned Building Area | 29404.35 |
Unconditioned Building Area | 9600.87 |
Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 0.00 | 26462.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 41087.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 44251.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18809.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 299798.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 30719.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 222846.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330767.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 434665.66 | 249308.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330767.30 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 26462.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 41087.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 44251.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 18809.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 9418.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 4809.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 12452.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Ventilation | 18266.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330767.30 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 222846.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 2.44 | 8.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 |
Other | 10.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 14.78 | 8.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1.84 | 6.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 |
Other | 7.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 11.14 | 6.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 434665.661 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 434665.661 | 100.00 |
Total On-Site and Utility Electric Sources | 434665.661 | 100.00 |
Total Electricity End Uses | 434665.661 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 330767.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 330767.30 | 100.00 |
Total Water End Uses | 330767.30 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1321.00 |
Time Setpoint Not Met During Occupied Cooling | 60.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 476.83 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |COILLOADS
| MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | MAIN WATER HEATING COIL_UNITHEATEDBSMT | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |HEATING AND COOLING LOADS
| HEATEDBSMT | BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:30 |
RunPeriod | ANNUAL |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [ft] | 521.68 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Above Ground Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Above Ground Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
HEATEDBSMT | 7794.39 | Yes | Yes | 58539.52 | 1.00 | 185.02 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.16 | No | Yes | 30553.25 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
ATTIC | 7802.71 | No | Yes | 52795.56 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
Total | 39005.22 | 325627.71 | 16363.00 | 0.00 | 2126.74 | 2126.74 | 0.3693 | 1083.48 | 1.6118 | |||
Conditioned Total | 29404.35 | 242278.90 | 15481.63 | 0.00 | 2126.74 | 2126.74 | 0.4899 | 816.79 | 2.1381 | |||
Unconditioned Total | 9600.87 | 83348.81 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 29-SEP-18:00 | 01-JAN-06:40 | - | - | - | - | - | - | - | - | - | - | 01-JAN-08:09 |
Heating | 0.00 | 34.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 23.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 13.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 4.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 50.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 218.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 99.38 | 252.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 34.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 23.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 13.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 4.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 2.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 5.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 9.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 25.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 5.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Ventilation | 2.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 218.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Gasoline [kBtu] | Source Diesel [kBtu] | Source Coal [kBtu] | Source Fuel Oil No 1 [kBtu] | Source Fuel Oil No 2 [kBtu] | Source Propane [kBtu] | Source Other Fuel 1 [kBtu] | Source Other Fuel 2 [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 0.00 | 28684.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 130123.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 140144.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 59568.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 949462.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 97287.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 241565.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1376586.15 | 270250.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 0.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 32.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 46.82 | 9.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 0.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 24.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 6.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 35.29 | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
ZoneHVAC:EnergyRecoveryVentilatorUser-Specified Supply Air Flow Rate [ft3/min] | User-Specified Exhaust Air Flow Rate [ft3/min] | |
ERV_UNITHEATEDBSMT | 44.99 | 44.99 |
ERV_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT3_BACKROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT3_FRONTROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT1_FRONTROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT2_BACKROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT2_FRONTROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT1_BACKROW_TOPFLOOR | 44.99 | 44.99 |
User-Specified Maximum Flow Rate [ft3/min] | Design Size Maximum Flow Rate [ft3/min] | |
OASUPPLYFAN_UNITHEATEDBSMT | 44.99 | |
OAEXHAUSTFAN_UNITHEATEDBSMT | 44.99 | |
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR | 44.99 | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 292.92 | |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 156.11 | |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 208.49 | |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 275.21 | |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 144.83 | |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 196.78 | |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 323.72 | |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 181.00 | |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 234.99 | |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 304.08 | |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 167.79 | |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 220.33 | |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 361.46 | |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 218.77 | |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 246.94 | |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 356.45 | |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 216.14 | |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 237.79 | |
SUPPLY FAN_UNITHEATEDBSMT | 144.80 |
User-Specified Nominal Supply Air Flow Rate [ft3/min] | |
OA_HEAT_RECOVERY_UNITHEATEDBSMT | 44.99 |
OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR | 44.99 |
Design Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNITHEATEDBSMT | 144.80 |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 292.92 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 156.11 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 208.49 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 275.21 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 144.83 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 196.78 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 323.72 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 181.00 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 234.99 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 304.08 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 167.79 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 220.33 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 237.79 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 246.94 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 361.46 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 216.14 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 218.77 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 356.45 |
Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | Sum of Air Terminal Maximum Flow Rates [ft3/min] | Adjusted Heating Design Air Flow Rate [ft3/min] | Adjusted Cooling Design Air Flow Rate [ft3/min] | Adjusted Main Design Air Flow Rate [ft3/min] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 292.92 | 292.92 | 292.92 | 292.92 | 292.92 | 292.92 | 1.00 | 1.00 | 292.92 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 156.11 | 156.11 | 156.11 | 156.11 | 156.11 | 156.11 | 1.00 | 1.00 | 156.11 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 208.49 | 208.49 | 208.49 | 208.49 | 208.49 | 208.49 | 1.00 | 1.00 | 208.49 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 275.21 | 275.21 | 275.21 | 275.21 | 275.21 | 275.21 | 1.00 | 1.00 | 275.21 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 144.83 | 144.83 | 144.83 | 144.83 | 144.83 | 144.83 | 1.00 | 1.00 | 144.83 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 196.78 | 196.78 | 196.78 | 196.78 | 196.78 | 196.78 | 1.00 | 1.00 | 196.78 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 323.72 | 323.72 | 323.72 | 323.72 | 323.72 | 323.72 | 1.00 | 1.00 | 323.72 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 181.00 | 181.00 | 181.00 | 181.00 | 181.00 | 181.00 | 1.00 | 1.00 | 181.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 234.99 | 234.99 | 234.99 | 234.99 | 234.99 | 234.99 | 1.00 | 1.00 | 234.99 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 304.08 | 304.08 | 304.08 | 304.08 | 304.08 | 304.08 | 1.00 | 1.00 | 304.08 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 167.79 | 167.79 | 167.79 | 167.79 | 167.79 | 167.79 | 1.00 | 1.00 | 167.79 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 220.33 | 220.33 | 220.33 | 220.33 | 220.33 | 220.33 | 1.00 | 1.00 | 220.33 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 361.46 | 361.46 | 361.46 | 361.46 | 361.46 | 361.46 | 1.00 | 1.00 | 361.46 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 218.77 | 218.77 | 218.77 | 218.77 | 218.77 | 218.77 | 1.00 | 1.00 | 218.77 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 246.94 | 246.94 | 246.94 | 246.94 | 246.94 | 246.94 | 1.00 | 1.00 | 246.94 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 356.45 | 356.45 | 356.45 | 356.45 | 356.45 | 356.45 | 1.00 | 1.00 | 356.45 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 216.14 | 216.14 | 216.14 | 216.14 | 216.14 | 216.14 | 1.00 | 1.00 | 216.14 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 237.79 | 237.79 | 237.79 | 237.79 | 237.79 | 237.79 | 1.00 | 1.00 | 237.79 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 144.80 | 144.80 | 144.80 | 144.80 | 144.80 | 144.80 | 1.00 | 1.00 | 144.80 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 292.92 | 0.671434 | 0.800324 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 156.11 | 0.369992 | 0.800610 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 208.49 | 0.471815 | 0.800916 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 275.21 | 0.633018 | 0.800104 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 144.83 | 0.345978 | 0.800908 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 196.78 | 0.439276 | 0.800884 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 323.72 | 0.735727 | 0.800386 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 181.00 | 0.424202 | 0.800512 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 234.99 | 0.530571 | 0.800749 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 304.08 | 0.694889 | 0.800419 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 167.79 | 0.389899 | 0.800488 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 220.33 | 0.490182 | 0.800131 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 361.46 | 0.815023 | 0.800233 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 218.77 | 0.503294 | 0.800034 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 246.94 | 0.585093 | 0.800725 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 356.45 | 0.805090 | 0.800623 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 216.14 | 0.497819 | 0.800626 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 237.79 | 0.549581 | 0.800397 |
DX COOLING COIL_UNITHEATEDBSMT | 144.80 | 0.450354 | 0.722611 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 292.92 | 292.92 | 292.92 | 0.671434 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 156.11 | 156.11 | 156.11 | 0.369992 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 208.49 | 208.49 | 208.49 | 0.471815 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 275.21 | 275.21 | 275.21 | 0.633018 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 144.83 | 144.83 | 144.83 | 0.345978 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 196.78 | 196.78 | 196.78 | 0.439276 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 323.72 | 323.72 | 323.72 | 0.735727 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 181.00 | 181.00 | 181.00 | 0.424202 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 234.99 | 234.99 | 234.99 | 0.530571 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 304.08 | 304.08 | 304.08 | 0.694889 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 167.79 | 167.79 | 167.79 | 0.389899 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 220.33 | 220.33 | 220.33 | 0.490182 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 361.46 | 361.46 | 361.46 | 0.815023 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 218.77 | 218.77 | 218.77 | 0.503294 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 246.94 | 246.94 | 246.94 | 0.585093 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 356.45 | 356.45 | 356.45 | 0.805090 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 216.14 | 216.14 | 216.14 | 0.497819 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 237.79 | 237.79 | 237.79 | 0.549581 | 1.00 |
ACANDF_UNITHEATEDBSMT | 144.80 | 144.80 | 144.80 | 0.450354 | 1.00 |
Design Size Rated Capacity [Btu/h] | Design Size Maximum Water Flow Rate [gal/min] | Design Size U-Factor Times Area Value [Btu/h-F] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 17146.26 | 1.76 | 240.00 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 9878.19 | 1.01 | 134.56 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 12660.85 | 1.30 | 174.98 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 16205.71 | 1.66 | 226.38 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 9279.12 | 0.952471 | 125.85 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 12038.96 | 1.24 | 165.96 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 18782.52 | 1.93 | 263.55 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 11200.66 | 1.15 | 153.48 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 14068.65 | 1.44 | 195.31 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 17739.06 | 1.82 | 248.45 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 10498.60 | 1.08 | 143.31 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 13289.97 | 1.36 | 184.03 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 20787.34 | 2.13 | 292.72 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 13207.22 | 1.36 | 182.91 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 14703.87 | 1.51 | 204.62 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 20521.35 | 2.11 | 288.87 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 13067.59 | 1.34 | 180.88 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 14217.61 | 1.46 | 197.57 |
MAIN WATER HEATING COIL_UNITHEATEDBSMT | 9277.53 | 0.952308 | 125.83 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
BOILER LOOP | 3.68 | 7.37 |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 2.09 |
Design Flow Rate [ft3/min] | |
BOILER CIRC PUMP | 3.68 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Design Size Nominal Capacity [Btu/h] | Design Size Design Water Flow Rate [gal/min] | |
CENTRAL BOILER | 268571.08 | 27.57 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
BGWALL_UPPER_LDF | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
BGWALL_UPPER_SDR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
BGWALL_UPPER_LDB | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
BGWALL_UPPER_SDL | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
VersionVersion ID | |
1 | 9.5 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | No | Yes | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.200 | 0.200 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 55.60 | 55.08 | 55.99 | 57.42 | 61.12 | 63.99 | 65.91 | 66.51 | 65.50 | 63.28 | 60.31 | 57.54 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {ft} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Sensor Height Above Ground {ft} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 32.810 | 0.140 | 885.870 | 4.921 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {ft} | Standard Pressure at Elevation {psi} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 521.68 | 14. | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{F} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} | Fixed Default Water Mains Temperature{F} | |
1 | Correlation | NA | 60.80 | 12.78 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | US+MF+CZ3C+oilfurnace+heatedbsmt+IECC_2015 | 0.000 | Suburbs | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Gradient Coefficient {F/ft} | |
1 | 0.220 | 1213.970 | 0.003566 |
Material Name | ThermalResistance {m2-K/w} | Roughness | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | Absorptance:Thermal | Absorptance:Solar | Absorptance:Visible | |
1 | SHEATHING_CONSOL_LAYER | 0.1351 | Rough | 0.0417 | 9.402E-002 | 42.764 | 0.280 | 0.9000 | 0.7000 | 0.7000 |
2 | CEIL_CONSOL_LAYER | 6.1981 | Rough | 1.2550 | 6.172E-002 | 2.618 | 0.185 | 0.9000 | 0.7000 | 0.7000 |
3 | FLOOR_CONSOL_LAYER | 1.9554E-005 | Rough | 0.0008 | 12.990 | 3.438 | 0.219 | 0.9000 | 0.7000 | 0.7000 |
4 | BSMTWALL_CONSOL_LAYER | 1.5339 | Rough | 0.2917 | 5.796E-002 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
5 | CRAWLWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
6 | WALL_CONSOL_LAYER | 2.4438 | Rough | 0.4584 | 5.717E-002 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
7 | VERY HIGH REFLECTIVITY SURFACE | 2.1097E-006 | Smooth | 0.0016 | 237.000 | 168.680 | 0.216 | 0.9000 | 5.0000E-002 | 5.0000E-002 |
8 | GYPSUMBOARD-5/16IN | 5.0054E-002 | Rough | 0.0260 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
9 | COPPERPIPE | 4.7506E-005 | MediumRough | 0.0625 | 401.000 | 140.026 | 0.200 | 0.9000 | 0.6500 | 0.6500 |
10 | F08 METAL SURFACE | 1.7668E-005 | Smooth | 0.0026 | 45.280 | 488.437 | 0.119 | 0.9000 | 0.7000 | 0.7000 |
11 | CONCRETE_4IN | 7.7356E-002 | Rough | 0.3330 | 1.312 | 140.014 | 0.111 | 0.9000 | 0.7000 | 0.7000 |
12 | ASPHALT_SHINGLE | 7.7448E-002 | MediumRough | 0.0208 | 8.186E-002 | 70.000 | 0.300 | 0.9000 | 0.7500 | 0.7000 |
13 | WOOD_SHINGLE | 0.1115 | MediumSmooth | 0.0417 | 0.114 | 26.600 | 0.390 | 0.9000 | 0.7000 | 0.7000 |
14 | SLATE_SHINGLE | 8.8061E-003 | MediumSmooth | 0.0417 | 1.442 | 100.000 | 0.300 | 0.9000 | 0.7000 | 0.7000 |
15 | CEMENT_STUCCO | 2.6422E-002 | MediumSmooth | 0.0625 | 0.721 | 116.464 | 0.210 | 0.9000 | 0.7000 | 0.7000 |
16 | SYN_STUCCO | 3.5237E-002 | MediumSmooth | 0.0100 | 8.650E-002 | 24.971 | 0.210 | 0.9000 | 0.7000 | 0.7000 |
17 | DRYWALL_1/2IN | 7.9331E-002 | MediumSmooth | 0.0417 | 0.160 | 50.000 | 0.260 | 0.9000 | 0.7000 | 0.7000 |
18 | OSB_5/8IN | 0.1365 | MediumSmooth | 0.0521 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
19 | OSB_7/16IN | 9.5550E-002 | MediumSmooth | 0.0365 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
20 | BLOWN_R30 | 5.1614 | MediumRough | 0.6975 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
21 | BLOWN_R30_TOP | 2.8489 | MediumRough | 0.3849 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
22 | PLYWOOD_3/4IN | 0.1650 | Rough | 0.0625 | 0.115 | 34.003 | 0.161 | 0.9000 | 0.7000 | 0.7000 |
23 | BATT_R19 | 7.3089 | MediumRough | 0.0833 | 3.475E-003 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
24 | LUMBER_2X4 | 0.7709 | Rough | 0.2920 | 0.115 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
25 | CARPET_N_PAD | 0.4224 | MediumSmooth | 0.0833 | 6.013E-002 | 2.000 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
26 | BATT_R13 | 2.2936 | MediumRough | 0.2917 | 3.876E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
27 | OSB_1/2IN | 0.1092 | MediumSmooth | 0.0417 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
28 | SOIL_12IN | 0.1761 | Rough | 1.0000 | 1.731 | 115.011 | 0.056 | 0.9000 | 0.7000 | 0.7000 |
29 | DOOR_CONST | 0.5031 | Smooth | 0.1189 | 7.201E-002 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
30 | GYP_BOARD_1/2IN | 8.0130E-002 | Rough | 0.0417 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
31 | STD WOOD 6INCH | 1.2500 | MediumSmooth | 0.4921 | 0.120 | 33.711 | 0.289 | 0.9000 | 0.7000 | 0.7000 |
32 | PIPE INSULATION | 0.3830 | VeryRough | 0.0417 | 3.317E-002 | 5.681 | 0.200 | 0.9000 | 0.5000 | 0.5000 |
33 | MANF_WALL_AIRGAP | 0.1200 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
34 | BLDG_PAPER_FELT | 1.0567E-002 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
35 | R_HIGH | 177.0000 | MediumRough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
36 | CLEAR ACRYLIC PLASTIC | 3.3333E-003 | VerySmooth | 0.0098 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
37 | DIFFUSING ACRYLIC PLASTIC | 2.4444E-003 | VerySmooth | 0.0072 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
38 | INT_BLIND | 0.0000 | Rough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.0000 | 0.0000 | 0.0000 |
39 | GLASS | 0.3300 | VerySmooth | 0.1230 | 0.114 | 0.000 | 0.000 | 0.8400 | 0.0000 | 0.0000 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | LowerLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Name | Combined convective/radiative film coefficient {Btu/h-ft2-F} | User selected Constant Temperature {F} | Coefficient modifying the constant temperature term | Coefficient modifying the external dry bulb temperature term | Coefficient modifying the ground temperature term | Coefficient modifying the wind speed term {s/m} | Coefficient modifying the zone air temperature term | Constant Temperature Schedule Name | Sinusoidal Variation | Period of Sinusoidal Variation | Previous Other Side Temperature Coefficient | Minimum Other Side Temperature {F} | Maximum Other Side Temperature {F} | |
1 | SURFPROPOTHSDCOEFBASEMENTAVGWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTWALLSURFACETEMP | NO | 24.000 | 0.000 | N/A | N/A |
2 | SURFPROPOTHSDCOEFBASEMENTAVGFLOOR | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTFLOORTEMP | NO | 24.000 | 0.000 | N/A | N/A |
3 | SURFPROPOTHSDCOEFBASEMENTUPPERWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTUPPERWALLTEMP | NO | 24.000 | 0.000 | N/A | N/A |
4 | SURFPROPOTHSDCOEFBASEMENTLOWERWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTLOWERWALLTEMP | NO | 24.000 | 0.000 | N/A | N/A |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{F} |
Surface Convection Coefficient Lower Limit {Btu/h-ft2-F} |
Surface Convection Coefficient Upper Limit {Btu/h-ft2-F} |
|
1 | CTF - ConductionTransferFunction | 392. | 0.02 | 176.1 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 60 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 21 | 186 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {ft} | Origin Y-Coordinate {ft} | Origin Z-Coordinate {ft} | Centroid X-Coordinate {ft} | Centroid Y-Coordinate {ft} | Centroid Z-Coordinate {ft} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {ft} | Maximum X {ft} | Minimum Y {ft} | Maximum Y {ft} | Minimum Z {ft} | Maximum Z {ft} | Ceiling Height {ft} | Volume {ft3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {ft2} | Exterior Gross Wall Area {ft2} | Exterior Net Wall Area {ft2} | Exterior Window Area {ft2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | HEATEDBSMT | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.51 | -3.4 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | -7.0 | 0.49 | 7.51 | 58539.45 | TARP | DOE-2 | 7794.37 | 185.05 | 185.05 | 0.00 | 15 | 0 | 0 | Yes |
2 | BREEZEWAY | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.55 | 13.26 | 1 | 1 | 1 | 0.00 | 119.89 | 30.05 | 35.04 | 0.49 | 25.99 | 17.00 | 30553.07 | TARP | DOE-2 | 1798.18 | 0.00 | 0.00 | 0.00 | 4 | 0 | 0 | Yes |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
15 | ATTIC | 0.0 | -134.9 | 51.61 | 0.00 | 59.94 | 32.55 | 29.56 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | 25.99 | 39.54 | 6.76 | 52795.39 | TARP | DOE-2 | 7802.66 | 881.33 | 881.33 | 0.00 | 11 | 0 | 0 | Yes |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
Zone Name | Floor Area {ft2} | # Occupants | Area per Occupant {ft2/person} | Occupant per Area {person/ft2} | Interior Lighting {Btu/h-ft2} | Electric Load {Btu/h-ft2} | Gas Load {Btu/h-ft2} | Other Load {Btu/h-ft2} | Hot Water Eq {Btu/h-ft2} | Steam Equipment {Btu/h-ft2} | Sum Loads per Area {Btu/h-ft2} | Outdoor Controlled Baseboard Heat | |
1 | HEATEDBSMT | 7794.37 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
2 | BREEZEWAY | 1798.18 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
15 | ATTIC | 7802.66 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Number of People {} | People/Floor Area {person/ft2} | Floor Area per person {ft2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
2 | PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
3 | PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
4 | PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
5 | PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
6 | PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
7 | PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
8 | PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
9 | PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
10 | PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
11 | PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
12 | PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
13 | PEOPLE_UNIT1_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
14 | PEOPLE_UNIT2_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
15 | PEOPLE_UNIT3_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
16 | PEOPLE_UNIT1_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
17 | PEOPLE_UNIT2_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
18 | PEOPLE_UNIT3_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Lighting Level {Btu/h} | Lights/Floor Area {Btu/h-ft2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {Btu/h} | Nominal Maximum Lighting Level {Btu/h} | |
1 | LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
2 | LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
3 | LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
4 | LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
5 | LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
6 | LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
7 | LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
8 | LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
9 | LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
10 | LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
11 | LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
12 | LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
13 | LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
14 | LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
15 | LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
16 | LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
17 | LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
18 | LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
19 | LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
20 | LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
21 | LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
22 | LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
23 | LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
24 | LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
25 | LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
26 | LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
27 | LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
28 | LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
29 | LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
30 | LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
31 | LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
32 | LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
33 | LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
34 | LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
35 | LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
36 | LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Equipment Level {Btu/h} | Equipment/Floor Area {Btu/h-ft2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {Btu/h} | Nominal Maximum Equipment Level {Btu/h} | |
1 | DISHWASHER1_FRONTROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
2 | REFRIGERATOR1_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
3 | CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
4 | ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
5 | ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
6 | TELEVISION1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
7 | ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
8 | IECC_ADJ1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
9 | DISHWASHER2_FRONTROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
10 | REFRIGERATOR2_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
11 | CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
12 | ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
13 | ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
14 | TELEVISION2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
15 | ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
16 | IECC_ADJ2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
17 | DISHWASHER3_FRONTROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
18 | REFRIGERATOR3_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
19 | CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
20 | ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
21 | ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
22 | TELEVISION3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
23 | ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
24 | IECC_ADJ3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
25 | DISHWASHER1_BACKROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
26 | REFRIGERATOR1_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
27 | CLOTHESWASHER1_BACKROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
28 | ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
29 | ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
30 | TELEVISION1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
31 | ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
32 | IECC_ADJ1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
33 | DISHWASHER2_BACKROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
34 | REFRIGERATOR2_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
35 | CLOTHESWASHER2_BACKROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
36 | ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
37 | ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
38 | TELEVISION2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
39 | ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
40 | IECC_ADJ2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
41 | DISHWASHER3_BACKROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
42 | REFRIGERATOR3_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
43 | CLOTHESWASHER3_BACKROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
44 | ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
45 | ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
46 | TELEVISION3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
47 | ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
48 | IECC_ADJ3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
49 | DISHWASHER1_FRONTROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
50 | REFRIGERATOR1_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
51 | CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
52 | ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
53 | ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
54 | TELEVISION1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
55 | ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
56 | IECC_ADJ1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
57 | DISHWASHER2_FRONTROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
58 | REFRIGERATOR2_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
59 | CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
60 | ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
61 | ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
62 | TELEVISION2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
63 | ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
64 | IECC_ADJ2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
65 | DISHWASHER3_FRONTROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
66 | REFRIGERATOR3_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
67 | CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
68 | ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
69 | ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
70 | TELEVISION3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
71 | ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
72 | IECC_ADJ3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
73 | DISHWASHER1_BACKROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
74 | REFRIGERATOR1_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
75 | CLOTHESWASHER1_BACKROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
76 | ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
77 | ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
78 | TELEVISION1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
79 | ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
80 | IECC_ADJ1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
81 | DISHWASHER2_BACKROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
82 | REFRIGERATOR2_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
83 | CLOTHESWASHER2_BACKROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
84 | ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
85 | ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
86 | TELEVISION2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
87 | ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
88 | IECC_ADJ2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
89 | DISHWASHER3_BACKROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
90 | REFRIGERATOR3_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
91 | CLOTHESWASHER3_BACKROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
92 | ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
93 | ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
94 | TELEVISION3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
95 | ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
96 | IECC_ADJ3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
97 | DISHWASHER1_FRONTROW_TOPFLOOR | DISHWASHER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
98 | REFRIGERATOR1_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
99 | CLOTHESWASHER1_FRONTROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
100 | ELECTRIC_DRYER1_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
101 | ELECTRIC_RANGE1_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
102 | TELEVISION1_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
103 | ELECTRIC_MELS1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
104 | IECC_ADJ1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
105 | DISHWASHER2_FRONTROW_TOPFLOOR | DISHWASHER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
106 | REFRIGERATOR2_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
107 | CLOTHESWASHER2_FRONTROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
108 | ELECTRIC_DRYER2_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
109 | ELECTRIC_RANGE2_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
110 | TELEVISION2_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
111 | ELECTRIC_MELS2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
112 | IECC_ADJ2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
113 | DISHWASHER3_FRONTROW_TOPFLOOR | DISHWASHER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
114 | REFRIGERATOR3_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
115 | CLOTHESWASHER3_FRONTROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
116 | ELECTRIC_DRYER3_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
117 | ELECTRIC_RANGE3_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
118 | TELEVISION3_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
119 | ELECTRIC_MELS3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
120 | IECC_ADJ3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
121 | DISHWASHER1_BACKROW_TOPFLOOR | DISHWASHER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
122 | REFRIGERATOR1_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
123 | CLOTHESWASHER1_BACKROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
124 | ELECTRIC_DRYER1_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
125 | ELECTRIC_RANGE1_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
126 | TELEVISION1_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
127 | ELECTRIC_MELS1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
128 | IECC_ADJ1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
129 | DISHWASHER2_BACKROW_TOPFLOOR | DISHWASHER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
130 | REFRIGERATOR2_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
131 | CLOTHESWASHER2_BACKROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
132 | ELECTRIC_DRYER2_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
133 | ELECTRIC_RANGE2_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
134 | TELEVISION2_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
135 | ELECTRIC_MELS2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
136 | IECC_ADJ2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
137 | DISHWASHER3_BACKROW_TOPFLOOR | DISHWASHER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
138 | REFRIGERATOR3_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
139 | CLOTHESWASHER3_BACKROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
140 | ELECTRIC_DRYER3_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
141 | ELECTRIC_RANGE3_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
142 | TELEVISION3_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
143 | ELECTRIC_MELS3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
144 | IECC_ADJ3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
Construction Name | Index | #Layers | #CTFs | Time Step {Hours} | ThermalConductance {Btu/h-ft2-F} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | EXTERIOR WALL | 1 | 5 | 11 | 0.167 | 0.0631 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
2 | CEILING-FLOOR-LAYER | 3 | 1 | 5 | 0.167 | 0.228 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
3 | EXTERIOR FLOOR | 4 | 3 | 4 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
4 | INTERIOR CEILING | 6 | 2 | 10 | 0.167 | 0.0281 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
5 | ATTIC FLOOR | 7 | 2 | 10 | 0.167 | 0.0281 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | INTERIORWALL | 9 | 3 | 5 | 0.167 | 0.597 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | EXTERIOR ROOF | 11 | 2 | 4 | 0.167 | 0.943 | 0.900 | 0.900 | 0.750 | 0.700 | MediumRough |
8 | EXTERIOR DOOR | 14 | 1 | 5 | 0.167 | 0.350 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | GABLE_END | 16 | 5 | 6 | 0.167 | 0.428 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
10 | BASEMENT WALL | 24 | 3 | 9 | 0.167 | 0.0945 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
11 | iz-EXTERIOR FLOOR | 25 | 3 | 4 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | ThermalResistance {m2-K/w} | |
1 | SYN_STUCCO | 0.0098 | 0.086 | 24.971 | 0.210 | 0.3524E-01 |
2 | SHEATHING_CONSOL_LAYER | 0.0417 | 0.094 | 42.764 | 0.280 | 0.1351 |
3 | OSB_7/16IN | 0.0364 | 0.116 | 34.000 | 0.290 | 0.9555E-01 |
4 | WALL_CONSOL_LAYER | 0.4584 | 0.057 | 7.541 | 0.248 | 2.444 |
5 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
6 | LUMBER_2X4 | 0.2920 | 0.115 | 32.003 | 0.183 | 0.7709 |
7 | FLOOR_CONSOL_LAYER | 0.0010 | 12.990 | 3.438 | 0.219 | 0.1955E-04 |
8 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
9 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
10 | CEIL_CONSOL_LAYER | 1.2550 | 0.062 | 2.618 | 0.185 | 6.198 |
11 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
12 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
13 | CEIL_CONSOL_LAYER | 1.2550 | 0.062 | 2.618 | 0.185 | 6.198 |
14 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
15 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
16 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
17 | ASPHALT_SHINGLE | 0.0207 | 0.082 | 70.000 | 0.300 | 0.7745E-01 |
18 | OSB_1/2IN | 0.0417 | 0.116 | 34.000 | 0.290 | 0.1092 |
19 | DOOR_CONST | 0.1188 | 0.072 | 32.003 | 0.183 | 0.5031 |
20 | CEMENT_STUCCO | 0.0627 | 0.721 | 116.464 | 0.210 | 0.2642E-01 |
21 | BLDG_PAPER_FELT | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1057E-01 |
22 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
23 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
24 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
25 | BSMTWALL_CONSOL_LAYER | 0.2917 | 0.058 | 7.541 | 0.248 | 1.534 |
26 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
27 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
28 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
29 | FLOOR_CONSOL_LAYER | 0.0010 | 12.990 | 3.438 | 0.219 | 0.1955E-04 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 11 | -0.54724946E-11 | -0.29353179E-14 | -0.58361936E-11 | 0.17617726E-15 |
2 | 10 | 0.24755928E-06 | 0.16971160E-13 | 0.58954555E-06 | -0.42317085E-11 |
3 | 9 | -0.21700660E-03 | 0.26282512E-10 | -0.34360792E-03 | 0.18634160E-06 |
4 | 8 | 0.10400975E-01 | 0.16063655E-07 | 0.16710006E-01 | -0.10459154E-03 |
5 | 7 | -0.18466841 | 0.14497582E-05 | -0.31678806 | 0.33996447E-02 |
6 | 6 | 1.6813335 | 0.30890211E-04 | 3.0392820 | -0.45644738E-01 |
7 | 5 | -8.8640021 | 0.19737274E-03 | -16.399456 | 0.32465800 |
8 | 4 | 28.400945 | 0.41196590E-03 | 52.185337 | -1.3315683 |
9 | 3 | -55.684303 | 0.27160336E-03 | -99.213599 | 3.2198962 |
10 | 2 | 64.740984 | 0.46773103E-04 | 110.17164 | -4.4902555 |
11 | 1 | -40.701741 | 0.11975386E-05 | -65.686261 | 3.3169381 |
12 | 0 | 10.602230 | 0.29970883E-09 | 16.204438 | |
13 | 5 | -0.10726087E-01 | 0.44268190E-05 | -0.10726087E-01 | 0.97389233E-03 |
14 | 4 | 0.31857203 | 0.80150166E-03 | 0.31857203 | -0.30727185E-01 |
15 | 3 | -2.8372473 | 0.12516450E-01 | -2.8372473 | 0.30041224 |
16 | 2 | 9.6667056 | 0.33176537E-01 | 9.6667056 | -1.1584571 |
17 | 1 | -13.322214 | 0.15207483E-01 | -13.322214 | 1.8397512 |
18 | 0 | 6.2472388 | 0.62260140E-03 | 6.2472388 | |
19 | 4 | 0.29631924E-13 | -0.40788276E-14 | 0.60443234E-14 | -0.77798347E-16 |
20 | 3 | -0.11254351E-04 | 0.79669069E-06 | -0.23145793E-05 | 0.39394231E-13 |
21 | 2 | 0.49771861 | 0.29587917E-01 | 0.78801895E-01 | -0.76025120E-05 |
22 | 1 | -8.3915550 | 0.80192706 | -1.1535996 | 0.21114735 |
23 | 0 | 9.2367617 | 0.51139848 | 2.4177143 | |
24 | 10 | 0.25332408E-17 | -0.22101509E-14 | 0.15157692E-08 | 0.28211904E-17 |
25 | 9 | -0.31506112E-08 | -0.26974675E-14 | -0.81843868E-03 | 0.20118786E-08 |
26 | 8 | 0.42861811E-03 | 0.11354105E-09 | 0.39097097E-01 | -0.27370296E-03 |
27 | 7 | -0.11368907E-01 | 0.51842634E-07 | -0.64553953 | 0.74324363E-02 |
28 | 6 | 0.12484615 | 0.25047115E-05 | 5.3130581 | -0.83937451E-01 |
29 | 5 | -0.73775399 | 0.27964547E-04 | -24.889648 | 0.51283867 |
30 | 4 | 2.5553417 | 0.92755650E-04 | 70.144414 | -1.8477174 |
31 | 3 | -5.2989438 | 0.96002462E-04 | -120.51707 | 4.0111012 |
32 | 2 | 6.4233118 | 0.27752742E-04 | 123.06129 | -5.1209931 |
33 | 1 | -4.1707712 | 0.15163054E-05 | -68.409714 | 3.5199891 |
34 | 0 | 1.1151582 | 0.34288690E-08 | 15.905180 | |
35 | 10 | 0.15157692E-08 | -0.22101509E-14 | 0.25332408E-17 | 0.28211904E-17 |
36 | 9 | -0.81843868E-03 | -0.26974675E-14 | -0.31506112E-08 | 0.20118786E-08 |
37 | 8 | 0.39097097E-01 | 0.11354105E-09 | 0.42861811E-03 | -0.27370296E-03 |
38 | 7 | -0.64553953 | 0.51842634E-07 | -0.11368907E-01 | 0.74324363E-02 |
39 | 6 | 5.3130581 | 0.25047115E-05 | 0.12484615 | -0.83937451E-01 |
40 | 5 | -24.889648 | 0.27964547E-04 | -0.73775399 | 0.51283867 |
41 | 4 | 70.144414 | 0.92755650E-04 | 2.5553417 | -1.8477174 |
42 | 3 | -120.51707 | 0.96002462E-04 | -5.2989438 | 4.0111012 |
43 | 2 | 123.06129 | 0.27752742E-04 | 6.4233118 | -5.1209931 |
44 | 1 | -68.409714 | 0.15163054E-05 | -4.1707712 | 3.5199891 |
45 | 0 | 15.905180 | 0.34288690E-08 | 1.1151582 | |
46 | 5 | -0.27590492E-07 | 0.65241430E-08 | -0.27590492E-07 | 0.17331255E-13 |
47 | 4 | 0.68608714E-03 | 0.11323974E-03 | 0.68608714E-03 | -0.15705033E-07 |
48 | 3 | -0.21538511 | 0.37821720E-01 | -0.21538511 | 0.25667047E-03 |
49 | 2 | 5.0173519 | 0.62258424 | 5.0173519 | -0.50236511E-01 |
50 | 1 | -19.904252 | 0.86481321 | -19.904252 | 0.58144210 |
51 | 0 | 16.688993 | 0.62060609E-01 | 16.688993 | |
52 | 4 | 0.75441920E-10 | 0.23883683E-10 | 0.47514224E-10 | -0.69373194E-20 |
53 | 3 | -0.33730907E-03 | 0.89366797E-04 | -0.22574866E-03 | 0.77828620E-10 |
54 | 2 | 0.58624422 | 0.18542418 | 0.49024360 | -0.17301269E-03 |
55 | 1 | -11.299243 | 2.8799011 | -8.6239668 | 0.15905732 |
56 | 0 | 15.219762 | 1.4410112 | 12.640375 | |
57 | 5 | -0.24423608E-08 | 0.10315694E-08 | -0.24423608E-08 | 0.46347327E-11 |
58 | 4 | 0.46481418E-04 | 0.19988510E-04 | 0.46481418E-04 | -0.22728163E-06 |
59 | 3 | -0.31887091E-01 | 0.95525843E-02 | -0.31887091E-01 | 0.49135354E-03 |
60 | 2 | 1.3495466 | 0.25081638 | 1.3495466 | -0.51058024E-01 |
61 | 1 | -7.0688408 | 0.57876498 | -7.0688408 | 0.58136590 |
62 | 0 | 6.6836766 | 0.93387740E-01 | 6.6836766 | |
63 | 6 | 0.97988530E-11 | 0.43917118E-12 | 0.24496810E-11 | -0.34892153E-15 |
64 | 5 | -0.75005310E-05 | 0.16499726E-06 | -0.28271466E-05 | 0.19166609E-11 |
65 | 4 | 0.32354224E-01 | 0.66949565E-03 | 0.10283773E-01 | -0.11111676E-05 |
66 | 3 | -1.8201547 | 0.67148336E-01 | -0.62076152 | 0.38788549E-02 |
67 | 2 | 21.173821 | 0.53241617 | 7.5279938 | -0.97325542E-01 |
68 | 1 | -64.420211 | 0.46601667 | -21.697519 | 0.64629334 |
69 | 0 | 46.121323 | 0.20873329E-01 | 15.867130 | |
70 | 9 | -0.80897332E-10 | 0.25083726E-14 | -0.80897339E-10 | 0.53193778E-14 |
71 | 8 | 0.39289009E-06 | 0.32343632E-10 | 0.39289009E-06 | -0.68074193E-10 |
72 | 7 | -0.79073148E-04 | 0.55832398E-07 | -0.79073148E-04 | 0.21386430E-06 |
73 | 6 | 0.50623992E-02 | 0.12454124E-04 | 0.50623992E-02 | -0.38648400E-04 |
74 | 5 | -0.13087289 | 0.53594127E-03 | -0.13087289 | 0.20673172E-02 |
75 | 4 | 1.5051005 | 0.55237945E-02 | 1.5051005 | -0.39966152E-01 |
76 | 3 | -8.0002312 | 0.14646655E-01 | -8.0002312 | 0.31995340 |
77 | 2 | 19.971617 | 0.92139765E-02 | 19.971617 | -1.1487826 |
78 | 1 | -22.455378 | 0.94314545E-03 | -22.455378 | 1.8092119 |
79 | 0 | 9.1356600 | 0.28983972E-05 | 9.1356600 | |
80 | 4 | 0.60443234E-14 | -0.40788276E-14 | 0.29631924E-13 | -0.77798347E-16 |
81 | 3 | -0.23145793E-05 | 0.79669069E-06 | -0.11254351E-04 | 0.39394231E-13 |
82 | 2 | 0.78801895E-01 | 0.29587917E-01 | 0.49771861 | -0.76025120E-05 |
83 | 1 | -1.1535996 | 0.80192706 | -8.3915550 | 0.21114735 |
84 | 0 | 2.4177143 | 0.51139848 | 9.2367617 |
Construction Name | Index | #Layers | Roughness | Conductance {Btu/h-ft2-F} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | EXTERIOR WINDOW | 12 | 1 | VerySmooth | 0.350 | 0.217 | 0.129 | 0.883 |
2 | INTERIOR WINDOW | 13 | 1 | VerySmooth | 0.350 | 0.217 | 0.129 | 0.883 |
3 | WINDOW_W_BLINDS | 18 | 2 | VerySmooth | 0.350 | 0.208 | 2.545E-002 | 0.133 |
4 | TDD DOME | 22 | 1 | VerySmooth | 1.071 | 0.929 | 0.920 | 0.920 |
5 | TDD DIFFUSER | 23 | 1 | VerySmooth | 1.077 | 0.906 | 0.900 | 0.900 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {ft} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLASS | SpectralAverage | 0.12304 | 0.12813 | 0.66165 | 0.66165 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.11365 | 1.00000 | No | |
2 | GLASS | SpectralAverage | 0.12304 | 0.12813 | 0.66165 | 0.66165 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.11365 | 1.00000 | No | |
3 | GLASS | SpectralAverage | 0.12304 | 0.12813 | 0.66165 | 0.66165 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.11365 | 1.00000 | No | |
4 | CLEAR ACRYLIC PLASTIC | SpectralAverage | 0.00984 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No | |
5 | DIFFUSING ACRYLIC PLASTIC | SpectralAverage | 0.00722 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No |
Material Name | Slat Width {ft} | Slat Separation {ft} | Slat Thickness {ft} | Slat Angle {deg} | Slat Beam Solar Transmittance | Slat Beam Solar Front Reflectance | Blind To Glass Distance {ft} | |
1 | INT_BLIND | 0.0820 | 0.0615 | 0.0033 | 45.000 | 0.000 | 0.500 | 0.164 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000. | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {ft3} | Maximum Capacity {Btu/h} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
2 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
3 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
4 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
5 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
6 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
7 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
8 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
9 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
10 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
11 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
12 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
13 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
14 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
15 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
16 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
17 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
18 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
2 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
3 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
4 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
5 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
6 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
7 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
8 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
9 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
10 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
11 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
12 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
13 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
14 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
15 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
16 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
17 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
18 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
19 | ATTICVENT | ALWAYS_AVAIL | ATTIC | 7802.66 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/person Area {ft3/min-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {psi} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{F}/Schedule | Maximum Indoor Temperature{F}/Schedule | Delta Temperature{F}/Schedule | Minimum Outdoor Temperature{F}/Schedule | Maximum Outdoor Temperature{F}/Schedule | Maximum WindSpeed{ft/min} | |
1 | VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
2 | VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
3 | VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
4 | VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
5 | VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
6 | VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
7 | VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
8 | VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
9 | VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
10 | VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
11 | VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
12 | VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
13 | VENTILATION_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
14 | VENTILATION_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
15 | VENTILATION_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
16 | VENTILATION_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
17 | VENTILATION_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
18 | VENTILATION_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
19 | VENTILATION_UNITHEATEDBSMT | ALWAYS_OFF | HEATEDBSMT | 7794.37 | 0.0 | 0.000 | 0.000 | N/A | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | HEATEDBSMT | Mixing/Well-Stirred |
2 | BREEZEWAY | Mixing/Well-Stirred |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
15 | ATTIC | Mixing/Well-Stirred |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {Btu/h} | User Des Load {Btu/h} | Calc Des Air Flow Rate {ft3/min} | User Des Air Flow Rate {ft3/min} | Design Day Name | Date/Time of Peak | Temperature at Peak {F} | Humidity Ratio at Peak {lbWater/lbDryAir} | Floor Area {ft2} | # Occupants | Calc Outdoor Air Flow Rate {ft3/min} | Calc DOAS Heat Addition Rate {Btu/h} | |
1 | HEATEDBSMT | Cooling | 0.00000 | 0.00000 | 0.00000 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 88.34000 | 0.00823 | 7794.38637 | 0.00000 | 44.99491 | 0.00000 | |
2 | HEATEDBSMT | Heating | 7805.97575 | 7805.97575 | 144.79892 | 144.79892 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:10:00 | 38.84000 | 0.00506 | 7794.38637 | 0.00000 | 44.99491 | 0.00000 |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | 6759.60686 | 6759.60686 | 292.92369 | 292.92369 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 86.09720 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
4 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | 2206.25048 | 2206.25048 | 40.92521 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
5 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | 3602.36002 | 3602.36002 | 156.10570 | 156.10570 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 82.09220 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
6 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | 1144.74463 | 1144.74463 | 21.23474 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
7 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | 4811.18231 | 4811.18231 | 208.48557 | 208.48557 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 82.65290 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
8 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | 2209.23353 | 2209.23353 | 40.98050 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
9 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | 6351.03129 | 6351.03129 | 275.21183 | 275.21183 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 85.83021 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
10 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Heating | 2208.69115 | 2208.69115 | 40.97055 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
11 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | 3342.13285 | 3342.13285 | 144.82901 | 144.82901 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 82.09220 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
12 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Heating | 1144.72842 | 1144.72842 | 21.23453 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
13 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | 4541.03104 | 4541.03104 | 196.77921 | 196.77921 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 80.89070 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
14 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Heating | 2206.73417 | 2206.73417 | 40.93410 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
15 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | 7470.50569 | 7470.50569 | 323.72877 | 323.72877 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 85.56319 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
16 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | 1859.11364 | 1859.11364 | 34.48665 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
17 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | 4176.91458 | 4176.91458 | 181.00400 | 181.00400 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 82.09220 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
18 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | 703.15257 | 703.15257 | 13.04371 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
19 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | 5422.81232 | 5422.81232 | 234.99997 | 234.99997 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 83.45390 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
20 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | 1863.24492 | 1863.24492 | 34.56334 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
21 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | 7017.21238 | 7017.21238 | 304.08894 | 304.08894 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 85.29620 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
22 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Heating | 1862.43918 | 1862.43918 | 34.54830 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
23 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | 3871.90873 | 3871.90873 | 167.78811 | 167.78811 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:40:00 | 80.91739 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
24 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Heating | 704.00847 | 704.00847 | 13.05960 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
25 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | 5084.55114 | 5084.55114 | 220.33896 | 220.33896 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 81.34461 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
26 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Heating | 1861.60429 | 1861.60429 | 34.53283 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
27 | LIVING_UNIT3_BACKROW_TOPFLOOR | Cooling | 5487.34968 | 5487.34968 | 237.79658 | 237.79658 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:20:00 | 83.69420 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
28 | LIVING_UNIT3_BACKROW_TOPFLOOR | Heating | 3106.48826 | 3106.48826 | 57.62415 | 57.62415 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
29 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Cooling | 5698.59104 | 5698.59104 | 246.94912 | 246.94912 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 88.34000 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
30 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Heating | 3108.32988 | 3108.32988 | 57.65847 | 57.65847 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
31 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Cooling | 8341.24024 | 8341.24024 | 361.46182 | 361.46182 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 85.56319 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
32 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Heating | 3104.28028 | 3104.28028 | 57.58326 | 57.58326 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
33 | LIVING_UNIT2_BACKROW_TOPFLOOR | Cooling | 4987.78450 | 4987.78450 | 216.14404 | 216.14404 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 82.09220 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
34 | LIVING_UNIT2_BACKROW_TOPFLOOR | Heating | 1929.61289 | 1929.61289 | 35.79385 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
35 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Cooling | 5048.44065 | 5048.44065 | 218.77116 | 218.77116 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 82.09220 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
36 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Heating | 1929.56048 | 1929.56048 | 35.79279 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
37 | LIVING_UNIT1_BACKROW_TOPFLOOR | Cooling | 8225.68096 | 8225.68096 | 356.44063 | 356.44063 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 85.29620 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
38 | LIVING_UNIT1_BACKROW_TOPFLOOR | Heating | 3106.09615 | 3106.09615 | 57.61694 | 57.61694 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [ft3/min] | User Des Air Flow Rate [ft3/min] | Design Day Name | Date/Time of Peak | |
1 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 2107.41 | 292.92369 | 292.92369 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 1165.17 | 44.99491 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 1139.60 | 156.10570 | 156.10570 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 1165.17 | 44.99491 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
5 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 1496.52 | 208.48557 | 208.48557 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 1165.17 | 44.99491 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
7 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 1985.68 | 275.21183 | 275.21183 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Heating | Sensible | 1165.17 | 44.99491 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 1064.46 | 144.82901 | 144.82901 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Heating | Sensible | 1165.17 | 44.99491 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 1393.82 | 196.77921 | 196.77921 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Heating | Sensible | 1165.17 | 44.99491 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2305.21 | 323.72877 | 323.72877 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 1165.17 | 44.99491 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 1305.51 | 181.00400 | 181.00400 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 1165.17 | 44.99491 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
17 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 1684.36 | 234.99997 | 234.99997 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 1165.17 | 44.99491 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
19 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 2170.57 | 304.08894 | 304.08894 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Heating | Sensible | 1165.17 | 44.99491 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
21 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 1200.98 | 167.78811 | 167.78811 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
22 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Heating | Sensible | 1165.17 | 44.99491 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
23 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 1557.12 | 220.33896 | 220.33896 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
24 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Heating | Sensible | 1165.17 | 44.99491 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
25 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Cooling | Sensible | 2556.64 | 361.46182 | 361.46182 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
26 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Heating | Sensible | 1361.17 | 57.58326 | 57.58326 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
27 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Cooling | Sensible | 1557.18 | 218.77116 | 218.77116 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
28 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Heating | Sensible | 1165.17 | 44.99491 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
29 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Cooling | Sensible | 1832.45 | 246.94912 | 246.94912 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
30 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Heating | Sensible | 1362.34 | 57.65847 | 57.65847 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
31 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Cooling | Sensible | 2519.53 | 356.44063 | 356.44063 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
32 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Heating | Sensible | 1361.69 | 57.61694 | 57.61694 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
33 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Cooling | Sensible | 1539.66 | 216.14404 | 216.14404 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
34 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Heating | Sensible | 1165.17 | 44.99491 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
35 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Cooling | Sensible | 1706.36 | 237.79658 | 237.79658 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
36 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Heating | Sensible | 1361.80 | 57.62415 | 57.62415 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
37 | CENTRAL SYSTEM_UNITHEATEDBSMT | Cooling | Sensible | 486.75 | 44.99491 | 44.99491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
38 | CENTRAL SYSTEM_UNITHEATEDBSMT | Heating | Sensible | 2719.09 | 144.79892 | 144.79892 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNITHEATEDBSMT | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
2 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNITHEATEDBSMT | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
3 | Fan:OnOff | OASUPPLYFAN_UNITHEATEDBSMT | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
4 | Fan:OnOff | OAEXHAUSTFAN_UNITHEATEDBSMT | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
5 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNITHEATEDBSMT | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNITHEATEDBSMT | Design Size Maximum Air Flow Rate [ft3/min] | 144.79892 |
7 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
8 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
9 | Fan:OnOff | OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
10 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
11 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 292.92369 |
13 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
14 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
15 | Fan:OnOff | OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
16 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
17 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
18 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 156.10570 |
19 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
20 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
21 | Fan:OnOff | OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
22 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
23 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
24 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 208.48557 |
25 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
26 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
27 | Fan:OnOff | OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
28 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
29 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
30 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 275.21183 |
31 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
32 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
33 | Fan:OnOff | OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
34 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
35 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
36 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 144.82901 |
37 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
38 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
39 | Fan:OnOff | OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
40 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
41 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
42 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 196.77921 |
43 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
44 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
45 | Fan:OnOff | OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
46 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
47 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
48 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 323.72877 |
49 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
50 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
51 | Fan:OnOff | OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
52 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
53 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
54 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 181.00400 |
55 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
56 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
57 | Fan:OnOff | OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
58 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
59 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
60 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 234.99997 |
61 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
62 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
63 | Fan:OnOff | OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
64 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
65 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
66 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 304.08894 |
67 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
68 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
69 | Fan:OnOff | OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
70 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
71 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
72 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 167.78811 |
73 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
74 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
75 | Fan:OnOff | OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
76 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
77 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
78 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 220.33896 |
79 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
80 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
81 | Fan:OnOff | OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
82 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
83 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
84 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 237.79658 |
85 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
86 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
87 | Fan:OnOff | OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
88 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
89 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
90 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 246.94912 |
91 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
92 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
93 | Fan:OnOff | OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
94 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
95 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
96 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 361.46182 |
97 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
98 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
99 | Fan:OnOff | OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
100 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
101 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
102 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 216.14404 |
103 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
104 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
105 | Fan:OnOff | OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
106 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
107 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
108 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 218.77116 |
109 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
110 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
111 | Fan:OnOff | OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
112 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
113 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 356.44063 |
115 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 292.92369 |
116 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 292.92369 |
117 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 292.92369 |
118 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 292.92369 |
119 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 292.92369 |
120 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 292.92369 |
121 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
122 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
123 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 156.10570 |
124 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 156.10570 |
125 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 156.10570 |
126 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 156.10570 |
127 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 156.10570 |
128 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 156.10570 |
129 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
130 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
131 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 208.48557 |
132 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 208.48557 |
133 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 208.48557 |
134 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 208.48557 |
135 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 208.48557 |
136 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 208.48557 |
137 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
138 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
139 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 275.21183 |
140 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 275.21183 |
141 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 275.21183 |
142 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 275.21183 |
143 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 275.21183 |
144 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 275.21183 |
145 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
146 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
147 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 144.82901 |
148 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 144.82901 |
149 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 144.82901 |
150 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 144.82901 |
151 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 144.82901 |
152 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 144.82901 |
153 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
154 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
155 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 196.77921 |
156 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 196.77921 |
157 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 196.77921 |
158 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 196.77921 |
159 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 196.77921 |
160 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 196.77921 |
161 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
162 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
163 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 323.72877 |
164 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 323.72877 |
165 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 323.72877 |
166 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 323.72877 |
167 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 323.72877 |
168 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 323.72877 |
169 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
170 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
171 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 181.00400 |
172 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 181.00400 |
173 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 181.00400 |
174 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 181.00400 |
175 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 181.00400 |
176 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 181.00400 |
177 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
178 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
179 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 234.99997 |
180 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 234.99997 |
181 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 234.99997 |
182 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 234.99997 |
183 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 234.99997 |
184 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 234.99997 |
185 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
186 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
187 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 304.08894 |
188 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 304.08894 |
189 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 304.08894 |
190 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 304.08894 |
191 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 304.08894 |
192 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 304.08894 |
193 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
194 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
195 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 167.78811 |
196 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 167.78811 |
197 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 167.78811 |
198 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 167.78811 |
199 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 167.78811 |
200 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 167.78811 |
201 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
202 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
203 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 220.33896 |
204 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 220.33896 |
205 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 220.33896 |
206 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 220.33896 |
207 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 220.33896 |
208 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 220.33896 |
209 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
210 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
211 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 361.46182 |
212 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 361.46182 |
213 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 361.46182 |
214 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 361.46182 |
215 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 361.46182 |
216 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 361.46182 |
217 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
218 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
219 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 218.77116 |
220 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 218.77116 |
221 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 218.77116 |
222 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 218.77116 |
223 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 218.77116 |
224 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 218.77116 |
225 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
226 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
227 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 246.94912 |
228 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 246.94912 |
229 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 246.94912 |
230 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 246.94912 |
231 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 246.94912 |
232 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 246.94912 |
233 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
234 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
235 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 356.44063 |
236 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 356.44063 |
237 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 356.44063 |
238 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 356.44063 |
239 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 356.44063 |
240 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 356.44063 |
241 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
242 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
243 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 216.14404 |
244 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 216.14404 |
245 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 216.14404 |
246 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 216.14404 |
247 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 216.14404 |
248 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 216.14404 |
249 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
251 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 237.79658 |
252 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 237.79658 |
253 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 237.79658 |
254 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 237.79658 |
255 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 237.79658 |
256 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 237.79658 |
257 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
259 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 144.79892 |
260 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 144.79892 |
261 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 144.79892 |
262 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Adjusted Heating Design Air Flow Rate [ft3/min] | 144.79892 |
263 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Adjusted Cooling Design Air Flow Rate [ft3/min] | 144.79892 |
264 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Adjusted Main Design Air Flow Rate [ft3/min] | 144.79892 |
265 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 292.92369 |
268 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 156.10570 |
269 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 208.48557 |
270 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 275.21183 |
271 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 144.82901 |
272 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 196.77921 |
273 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 323.72877 |
274 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 181.00400 |
275 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 234.99997 |
276 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 304.08894 |
277 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 167.78811 |
278 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 220.33896 |
279 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 361.46182 |
280 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 218.77116 |
281 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 246.94912 |
282 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 356.44063 |
283 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 216.14404 |
284 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 237.79658 |
285 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Design Supply Air Flow Rate [ft3/min] | 144.79892 |
286 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 292.92369 |
287 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.67143 |
288 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80032 |
289 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 292.92369 |
290 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 292.92369 |
291 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 292.92369 |
292 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.67143 |
293 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 17146.26242 |
294 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.76000 |
295 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 240.00331 |
296 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
297 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 292.92369 |
298 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 156.10570 |
299 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.36999 |
300 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80061 |
301 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 156.10570 |
302 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 156.10570 |
303 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 156.10570 |
304 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.36999 |
305 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 9878.18513 |
306 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.01396 |
307 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 134.56165 |
308 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
309 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 156.10570 |
310 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 208.48557 |
311 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.47182 |
312 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80092 |
313 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 208.48557 |
314 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 208.48557 |
315 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 208.48557 |
316 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.47182 |
317 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 12660.85473 |
318 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.29959 |
319 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 174.98184 |
320 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
321 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 208.48557 |
322 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 275.21183 |
323 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.63302 |
324 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80010 |
325 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 275.21183 |
326 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 275.21183 |
327 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 275.21183 |
328 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.63302 |
329 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 16205.71398 |
330 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.66346 |
331 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 226.38006 |
332 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
333 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 275.21183 |
334 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 144.82901 |
335 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.34598 |
336 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80091 |
337 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 144.82901 |
338 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 144.82901 |
339 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 144.82901 |
340 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.34598 |
341 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 9279.12320 |
342 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 0.95247 |
343 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 125.84988 |
344 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
345 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 144.82901 |
346 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 196.77921 |
347 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.43928 |
348 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80088 |
349 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 196.77921 |
350 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 196.77921 |
351 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 196.77921 |
352 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.43928 |
353 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 12038.96164 |
354 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.23576 |
355 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 165.95973 |
356 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
357 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 196.77921 |
358 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 323.72877 |
359 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.73573 |
360 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80039 |
361 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 323.72877 |
362 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 323.72877 |
363 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 323.72877 |
364 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.73573 |
365 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 18782.51923 |
366 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.92797 |
367 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 263.55171 |
368 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
369 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 323.72877 |
370 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 181.00400 |
371 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.42420 |
372 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80051 |
373 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 181.00400 |
374 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 181.00400 |
375 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 181.00400 |
376 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.42420 |
377 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 11200.65985 |
378 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.14971 |
379 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 153.47773 |
380 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
381 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 181.00400 |
382 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 234.99997 |
383 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.53057 |
384 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80075 |
385 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 234.99997 |
386 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 234.99997 |
387 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 234.99997 |
388 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.53057 |
389 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 14068.65132 |
390 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.44410 |
391 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 195.30875 |
392 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
393 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 234.99997 |
394 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 304.08894 |
395 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.69489 |
396 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80042 |
397 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 304.08894 |
398 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 304.08894 |
399 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 304.08894 |
400 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.69489 |
401 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 17739.05842 |
402 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.82086 |
403 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 248.45184 |
404 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
405 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 304.08894 |
406 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 167.78811 |
407 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.38990 |
408 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80049 |
409 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 167.78811 |
410 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 167.78811 |
411 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 167.78811 |
412 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.38990 |
413 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 10498.60154 |
414 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.07765 |
415 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 143.30685 |
416 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
417 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 167.78811 |
418 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 220.33896 |
419 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.49018 |
420 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80013 |
421 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 220.33896 |
422 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 220.33896 |
423 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 220.33896 |
424 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.49018 |
425 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 13289.97263 |
426 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.36417 |
427 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 184.02624 |
428 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
429 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 220.33896 |
430 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 361.46182 |
431 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.81502 |
432 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80023 |
433 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 361.46182 |
434 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 361.46182 |
435 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 361.46182 |
436 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.81502 |
437 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 20787.34441 |
438 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.13376 |
439 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 292.71631 |
440 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
441 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 361.46182 |
442 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 218.77116 |
443 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.50329 |
444 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80003 |
445 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 218.77116 |
446 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 218.77116 |
447 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 218.77116 |
448 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.50329 |
449 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 13207.22262 |
450 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.35568 |
451 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 182.90834 |
452 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
453 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 218.77116 |
454 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 246.94912 |
455 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.58509 |
456 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80072 |
457 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 246.94912 |
458 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 246.94912 |
459 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 246.94912 |
460 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.58509 |
461 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 14703.86964 |
462 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.50930 |
463 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 204.61724 |
464 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
465 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 246.94912 |
466 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 356.44063 |
467 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.80509 |
468 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80062 |
469 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 356.44063 |
470 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 356.44063 |
471 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 356.44063 |
472 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.80509 |
473 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 20521.35001 |
474 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.10645 |
475 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 288.86611 |
476 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
477 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 356.44063 |
478 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 216.14404 |
479 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.49782 |
480 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80063 |
481 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 216.14404 |
482 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 216.14404 |
483 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 216.14404 |
484 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.49782 |
485 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 13067.58796 |
486 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.34135 |
487 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 180.88362 |
488 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
489 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 216.14404 |
490 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 237.79658 |
491 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.54958 |
492 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80040 |
493 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 237.79658 |
494 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 237.79658 |
495 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 237.79658 |
496 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.54958 |
497 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 14217.60982 |
498 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.45939 |
499 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 197.56972 |
500 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
501 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 237.79658 |
502 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNITHEATEDBSMT | Design Size Rated Air Flow Rate [ft3/min] | 144.79892 |
503 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNITHEATEDBSMT | Design Size Gross Rated Total Cooling Capacity [ton] | 0.45035 |
504 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNITHEATEDBSMT | Design Size Gross Rated Sensible Heat Ratio | 0.72261 |
505 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Supply Air Flow Rate [ft3/min] | 144.79892 |
506 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Supply Air Flow Rate During Heating Operation [ft3/min] | 144.79892 |
507 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Supply Air Flow Rate During Cooling Operation [ft3/min] | 144.79892 |
508 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Nominal Cooling Capacity [ton] | 0.45035 |
509 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNITHEATEDBSMT | Design Size Rated Capacity [Btu/h] | 9277.52662 |
510 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNITHEATEDBSMT | Design Size Maximum Water Flow Rate [gal/min] | 0.95231 |
511 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNITHEATEDBSMT | Design Size U-Factor Times Area Value [Btu/h-F] | 125.82833 |
512 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
513 | Fan:OnOff | SUPPLY FAN_UNITHEATEDBSMT | Design Size Maximum Flow Rate [ft3/min] | 144.79892 |
514 | PlantLoop | BOILER LOOP | Maximum Loop Flow Rate [ft3/min] | 3.68449 |
515 | PlantLoop | BOILER LOOP | Plant Loop Volume [ft3] | 7.37090 |
516 | Pump:VariableSpeed | BOILER CIRC PUMP | Design Flow Rate [ft3/min] | 3.68449 |
517 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [Btu/h] | 0.268571E+06 |
518 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [gal/min] | 27.56790 |
519 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
520 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
521 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
522 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
523 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
524 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
525 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
526 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
527 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
528 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
529 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
530 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
531 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
532 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
533 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
534 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
535 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
536 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
537 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
538 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
539 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
540 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
541 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
542 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
543 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
544 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
545 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
546 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
547 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
548 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
549 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
550 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
551 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
552 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
553 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
554 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
555 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
556 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
557 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
558 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
559 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
560 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
561 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
562 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
563 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
564 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
565 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
566 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
567 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
568 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
569 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
570 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
571 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
572 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
573 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
574 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
575 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
576 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
577 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
578 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
579 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
580 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
581 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
582 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
583 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
584 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
585 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
586 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
587 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
588 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
589 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
590 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
591 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
592 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
593 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
594 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
595 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
596 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
597 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
598 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
599 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
600 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
601 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
602 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
603 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
604 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
605 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
606 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
607 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
608 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {ton} | Standard Rated Net COP {Btuh/Btuh} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 0.6 | 3.28 | 11.19 | 11.85 | 11.39 | 11.39 |
2 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4 | 3.30 | 11.27 | 11.93 | 11.47 | 11.50 |
3 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.5 | 3.27 | 11.16 | 11.82 | 11.36 | 11.34 |
4 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 0.6 | 3.28 | 11.20 | 11.86 | 11.40 | 11.40 |
5 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.3 | 3.31 | 11.28 | 11.95 | 11.49 | 11.53 |
6 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.4 | 3.26 | 11.13 | 11.78 | 11.33 | 11.29 |
7 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 0.7 | 3.27 | 11.17 | 11.83 | 11.37 | 11.36 |
8 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.4 | 3.29 | 11.24 | 11.91 | 11.44 | 11.46 |
9 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.5 | 3.27 | 11.16 | 11.81 | 11.36 | 11.33 |
10 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 0.7 | 3.28 | 11.18 | 11.84 | 11.38 | 11.37 |
11 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.4 | 3.29 | 11.22 | 11.89 | 11.42 | 11.43 |
12 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.5 | 3.26 | 11.12 | 11.78 | 11.32 | 11.28 |
13 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 0.8 | 3.27 | 11.15 | 11.81 | 11.35 | 11.33 |
14 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.5 | 3.28 | 11.20 | 11.86 | 11.40 | 11.40 |
15 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.6 | 3.30 | 11.27 | 11.93 | 11.47 | 11.50 |
16 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 0.8 | 3.27 | 11.16 | 11.81 | 11.36 | 11.33 |
17 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.5 | 3.28 | 11.20 | 11.86 | 11.40 | 11.40 |
18 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.5 | 3.29 | 11.21 | 11.87 | 11.41 | 11.42 |
19 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNITHEATEDBSMT | 0.4 | 3.46 | 11.81 | 12.54 | 12.05 | 12.40 |
Component Type | Name | Nominal Total Capacity {Btu/h} | |
1 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 17984.04 |
2 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 9965.56 |
3 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 13040.49 |
4 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 16948.36 |
5 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 9302.31 |
6 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 12354.20 |
7 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 19778.37 |
8 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 11414.06 |
9 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 14589.00 |
10 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 18630.30 |
11 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 10639.40 |
12 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 13730.78 |
13 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 21990.95 |
14 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 13643.29 |
15 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 15293.78 |
16 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 21698.31 |
17 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 13489.31 |
18 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 14757.89 |
19 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNITHEATEDBSMT | 9300.60 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | SizingPeriod:DesignDay | 12/21 | 12/21 | WinterDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
2 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | SizingPeriod:DesignDay | 08/21 | 08/21 | SummerDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
3 | ANNUAL | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | Yes | Yes | No | Yes | Yes | Clark and Allen |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | No | SizingPeriod:DesignDay | ||
2 | No | SizingPeriod:DesignDay | ||
3 | No |
NumberofWarmupDays | |
1 | 6 |
2 | 6 |
3 | 25 |
Max Dry-Bulb Temp {F} | Temp Range {dC} | Temp Range Ind Type | Hum Ind Type | Hum Ind Value at Max Temp | Hum Ind Units | Pressure {psi} | Wind Direction {deg CW from N} | Wind Speed {ft/min} | Clearness | Rain | Snow | |
1 | 38.84 | 0.00 | DefaultMultipliers | Wetbulb | 3.80 | {C} | 14. | 120 | 590.6 | 0.00 | No | No |
2 | 88.34 | 8.90 | DefaultMultipliers | Wetbulb | 18.40 | {C} | 14. | 280 | 807.1 | 0.00 | No | No |
DayOfYear | ASHRAE A Coeff | ASHRAE B Coeff | ASHRAE C Coeff | Solar Constant-Annual Variation | Eq of Time {minutes} | Solar Declination Angle {deg} | Solar Model | |
1 | 355 | 1232.8 | 0.1424 | 5.7719E-002 | 1.0 | 2.45 | -24.. | ASHRAEClearSky |
2 | 233 | 1106.3 | 0.2000 | 0.1216 | 1.0 | -3.33 | 12.4 | ASHRAETau |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaF} | Std Dev Warmup Temperature Difference {deltaF} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {Btu/h} | Std Dev Warmup Load Difference {Btu/h} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | HEATEDBSMT | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.005263385 | 0.004514218 | Pass | Pass | 0.000465204 | 0.000416564 | Pass | Pass |
2 | BREEZEWAY | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.000004201 | 0.000002527 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.000023596 | 0.000042014 | Pass | Pass | 0.046606182 | 0.083624321 | Pass | Pass |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.000045498 | 0.000038878 | Pass | Pass | 0.135896827 | 0.266611386 | Pass | Pass |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.000026846 | 0.000060500 | Pass | Pass | 0.046673506 | 0.083376499 | Pass | Pass |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.000023247 | 0.000041331 | Pass | Pass | 0.046543771 | 0.083507456 | Pass | Pass |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.000041086 | 0.000076127 | Pass | Pass | 0.135876415 | 0.266493665 | Pass | Pass |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.000009867 | 0.000015539 | Pass | Pass | 0.046648020 | 0.083558071 | Pass | Pass |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.000007766 | 0.000010008 | Pass | Pass | 0.064528132 | 0.113121781 | Pass | Pass |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.063213788 | 0.110019578 | Pass | Pass | 5.579871597 | 0.409406E+02 | Pass | Pass |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.094452552 | 0.158730659 | Pass | Pass | 0.896977095 | 1.464890543 | Pass | Pass |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.000015127 | 0.000026585 | Pass | Pass | 0.064393310 | 0.112877902 | Pass | Pass |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.063244905 | 0.110057434 | Pass | Pass | 5.124743814 | 0.356119E+02 | Pass | Pass |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.095558146 | 0.160624040 | Pass | Pass | 0.887757476 | 1.449089919 | Pass | Pass |
15 | ATTIC | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.000106078 | 0.000095122 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.000021037 | 0.000037257 | Pass | Pass | 0.033321354 | 0.054222275 | Pass | Pass |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.000004539 | 0.000007245 | Pass | Pass | 0.033292288 | 0.054204415 | Pass | Pass |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.000032748 | 0.000078079 | Pass | Pass | 0.033245237 | 0.054187366 | Pass | Pass |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.000029561 | 0.000043139 | Pass | Pass | 0.062841982 | 0.103843036 | Pass | Pass |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.000030961 | 0.000046412 | Pass | Pass | 0.062818666 | 0.103714654 | Pass | Pass |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.000002364 | 0.000003527 | Pass | Pass | 0.033240692 | 0.054264416 | Pass | Pass |
22 | HEATEDBSMT | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.022327676 | 0.011622749 | Pass | Pass | 0.761423665 | 2.218609778 | Pass | Pass |
23 | BREEZEWAY | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.314646611 | 0.186682274 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
24 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.005657361 | 0.019186516 | Pass | Pass | 0.086608770 | 0.051288620 | Pass | Pass |
25 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.007605362 | 0.014886315 | Pass | Pass | 0.054901346 | 0.052474370 | Pass | Pass |
26 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.006857801 | 0.011989088 | Pass | Pass | 0.070801590 | 0.081538381 | Pass | Pass |
27 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.005651963 | 0.019234610 | Pass | Pass | 0.085162705 | 0.053704436 | Pass | Pass |
28 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.004702624 | 0.012656448 | Pass | Pass | 0.053736720 | 0.051467596 | Pass | Pass |
29 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.003110769 | 0.009890471 | Pass | Pass | 0.070267324 | 0.082190873 | Pass | Pass |
30 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.004854432 | 0.016699410 | Pass | Pass | 0.072639134 | 0.040894926 | Pass | Pass |
31 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.004376763 | 0.012313864 | Pass | Pass | 0.045506876 | 0.040378261 | Pass | Pass |
32 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.006106990 | 0.011743498 | Pass | Pass | 0.058629827 | 0.064062258 | Pass | Pass |
33 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.004669255 | 0.016879203 | Pass | Pass | 0.070856362 | 0.042137870 | Pass | Pass |
34 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.004604799 | 0.012284775 | Pass | Pass | 0.042150546 | 0.041509115 | Pass | Pass |
35 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.003439139 | 0.009931050 | Pass | Pass | 0.057733161 | 0.064589338 | Pass | Pass |
36 | ATTIC | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.457080660 | 0.363295741 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
37 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.006800884 | 0.013596224 | Pass | Pass | 0.059575638 | 0.064213465 | Pass | Pass |
38 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.005441551 | 0.010493754 | Pass | Pass | 0.060286347 | 0.064160059 | Pass | Pass |
39 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.004796062 | 0.016705394 | Pass | Pass | 0.077746697 | 0.041136552 | Pass | Pass |
40 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.004337923 | 0.011792589 | Pass | Pass | 0.052888464 | 0.039754871 | Pass | Pass |
41 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.004449497 | 0.012691776 | Pass | Pass | 0.052800124 | 0.041602710 | Pass | Pass |
42 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.004660963 | 0.016514670 | Pass | Pass | 0.077898129 | 0.040659998 | Pass | Pass |
43 | HEATEDBSMT | RunPeriod: ANNUAL | 0.095182433 | 0.092093323 | Pass | Pass | 5.085432418 | 0.103589E+02 | Pass | Pass |
44 | BREEZEWAY | RunPeriod: ANNUAL | 0.128663803 | 0.111753757 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
45 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.050152130 | 0.072867712 | Pass | Pass | 2.324168854 | 0.107537E+02 | Fail | Pass |
46 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.090136242 | 0.100002700 | Pass | Pass | 0.921393742 | 2.578557045 | Fail | Pass |
47 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.123090019 | 0.154138444 | Pass | Pass | 0.598529247 | 1.212836741 | Fail | Pass |
48 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.083806661 | 0.102527313 | Pass | Pass | 1.216115471 | 2.741014815 | Fail | Fail |
49 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.109771165 | 0.099819102 | Pass | Pass | 1.883679643 | 4.827481435 | Pass | Pass |
50 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.134170667 | 0.137691091 | Pass | Pass | 2.184194535 | 5.441636478 | Fail | Pass |
51 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.079151320 | 0.088131436 | Pass | Pass | 1.730700920 | 7.761560038 | Fail | Pass |
52 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.065067415 | 0.066458523 | Pass | Pass | 0.087644873 | 0.352879213 | Fail | Pass |
53 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.109820716 | 0.179541207 | Pass | Pass | 0.218389007 | 0.739804187 | Pass | Pass |
54 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.086841704 | 0.128035841 | Pass | Pass | 3.267071667 | 0.245278E+02 | Fail | Pass |
55 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.093224106 | 0.095715742 | Pass | Pass | 0.132907E+02 | 0.150849E+03 | Fail | Pass |
56 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.109453467 | 0.175328835 | Pass | Pass | 1.129555249 | 3.203648747 | Pass | Pass |
57 | ATTIC | RunPeriod: ANNUAL | 0.285607703 | 0.318335914 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
58 | LIVING_UNIT3_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.096021746 | 0.143778768 | Pass | Pass | 1.810589702 | 0.911178E+01 | Fail | Pass |
59 | LIVING_UNIT3_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.122139241 | 0.160403240 | Pass | Pass | 1.004495061 | 2.625905608 | Fail | Pass |
60 | LIVING_UNIT1_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.095039551 | 0.129391184 | Pass | Pass | 2.078390435 | 7.014277625 | Pass | Pass |
61 | LIVING_UNIT2_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.075470964 | 0.090919706 | Pass | Pass | 3.980763063 | 0.171395E+02 | Fail | Pass |
62 | LIVING_UNIT2_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.094577960 | 0.098060516 | Pass | Pass | 1.822783988 | 0.924501E+01 | Pass | Pass |
63 | LIVING_UNIT1_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.069604969 | 0.113628598 | Pass | Pass | 2.129808374 | 6.925668009 | Fail | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [kBtu] | 2842985.83 | 222365.38 | 0.00 | 0.00 | 245089.71 | 3310448.16 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 38.84 | 0.00 | 38.84 | Wetbulb [F] | 590.58 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 88.34 | 16.02 | 65.12 | Wetbulb [F] | 807.13 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_LOWER_LDF | BASEMENT WALL | 0.30 | 0.085 | 0.094 | 839.40 | 839.40 | 180.00 | 90.00 | S |
BGWALL_LOWER_SDR | BASEMENT WALL | 0.30 | 0.085 | 0.094 | 455.77 | 455.77 | 90.00 | 90.00 | E |
BGWALL_LOWER_LDB | BASEMENT WALL | 0.30 | 0.085 | 0.094 | 839.40 | 839.40 | 0.00 | 90.00 | N |
BGWALL_LOWER_SDL | BASEMENT WALL | 0.30 | 0.085 | 0.094 | 455.77 | 455.77 | 270.00 | 90.00 | W |
BGFLOOR | EXTERIOR FLOOR | 0.30 | 0.212 | 0.300 | 7794.39 | 7794.39 | 0.00 | 180.00 | |
iz-FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
BREEZEWAYROOF | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 599.39 | 599.39 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-BREEZEWAYROOF | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 599.39 | 599.39 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.350 | 0.217 | 0.883 | ||||||||||||
North Total or Average | 531.68 | 0.350 | 0.217 | 0.883 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.350 | 0.217 | 0.883 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.12 | 0.95 | 0.79 | 1.00 | 0.99 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.12 | 0.95 | 0.79 | 1.00 | 0.99 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.12 | 0.95 | 0.79 | 1.00 | 0.99 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 0.99 | 0.92 | 0.00 | 0.99 | 0.78 | 0.00 | 1.00 | 0.67 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 0.99 | 0.92 | 0.00 | 0.99 | 0.78 | 0.00 | 1.00 | 0.67 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.12 | 0.95 | 0.79 | 1.00 | 0.99 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.12 | 0.95 | 0.79 | 1.00 | 0.99 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.12 | 0.95 | 0.79 | 1.00 | 0.99 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 0.99 | 0.92 | 0.00 | 0.99 | 0.78 | 0.00 | 1.00 | 0.67 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 0.99 | 0.92 | 0.00 | 0.99 | 0.78 | 0.00 | 1.00 | 0.67 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 0.99 | 0.92 | 0.00 | 0.99 | 0.78 | 0.00 | 1.00 | 0.67 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.12 | 0.95 | 0.79 | 1.00 | 0.99 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 0.99 | 0.92 | 0.00 | 0.99 | 0.78 | 0.00 | 1.00 | 0.67 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.12 | 0.95 | 0.79 | 1.00 | 0.99 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.12 | 0.95 | 0.79 | 1.00 | 0.99 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3333 | 43219.92 | 14404.00 | 12960.20 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
Exterior Lighting Total | 1257.69 | 5508.71 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 268571.08 | 0.80 |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8057.21 | 6448.38 | 1608.84 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 4439.91 | 3554.64 | 885.27 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 5661.78 | 4534.61 | 1127.17 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 7596.22 | 6077.76 | 1518.46 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 4151.74 | 3325.16 | 826.58 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 5271.31 | 4221.71 | 1049.60 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8828.72 | 7066.39 | 1762.34 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 5090.42 | 4074.94 | 1015.48 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 6366.86 | 5098.25 | 1268.60 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8338.67 | 6674.43 | 1664.24 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 4678.79 | 3745.32 | 933.47 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 5882.19 | 4706.52 | 1175.67 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 9780.28 | 7826.51 | 1953.78 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 6039.52 | 4831.83 | 1207.70 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 7021.12 | 5621.99 | 1399.13 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 9661.08 | 7734.88 | 1926.20 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 5973.83 | 4782.80 | 1191.03 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 6594.98 | 5278.60 | 1316.38 | 0.80 | 4.07 | |||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | 5404.25 | 3905.17 | 1499.08 | 0.72 | 4.07 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 0.6 | 3.28 | 11.19 | 11.85 | 11.39 | 11.39 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4 | 3.30 | 11.27 | 11.93 | 11.47 | 11.50 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.5 | 3.27 | 11.16 | 11.82 | 11.36 | 11.34 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 0.6 | 3.28 | 11.20 | 11.86 | 11.40 | 11.40 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.3 | 3.31 | 11.28 | 11.95 | 11.49 | 11.53 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.4 | 3.26 | 11.13 | 11.78 | 11.33 | 11.29 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 0.7 | 3.27 | 11.17 | 11.83 | 11.37 | 11.36 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.4 | 3.29 | 11.24 | 11.91 | 11.44 | 11.46 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.5 | 3.27 | 11.16 | 11.81 | 11.36 | 11.33 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 0.7 | 3.28 | 11.18 | 11.84 | 11.38 | 11.37 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.4 | 3.29 | 11.22 | 11.89 | 11.42 | 11.43 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.5 | 3.26 | 11.12 | 11.78 | 11.32 | 11.28 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 0.8 | 3.27 | 11.15 | 11.81 | 11.35 | 11.33 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.5 | 3.28 | 11.20 | 11.86 | 11.40 | 11.40 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.6 | 3.30 | 11.27 | 11.93 | 11.47 | 11.50 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 0.8 | 3.27 | 11.16 | 11.81 | 11.36 | 11.33 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.5 | 3.28 | 11.20 | 11.86 | 11.40 | 11.40 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.5 | 3.29 | 11.21 | 11.87 | 11.41 | 11.42 | |
DX COOLING COIL_UNITHEATEDBSMT | 0.4 | 3.46 | 11.81 | 12.54 | 12.05 | 12.40 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 17146.26 | 17984.04 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 9878.19 | 9965.56 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 12660.85 | 13040.50 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 16205.71 | 16948.36 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 9279.12 | 9302.29 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 12038.96 | 12354.22 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 18782.52 | 19778.36 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 11200.66 | 11414.06 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 14068.65 | 14588.99 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 17739.06 | 18630.30 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 10498.60 | 10639.39 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 13289.97 | 13730.79 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | 20787.34 | 21990.94 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | 13207.22 | 13643.31 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | 14703.87 | 15293.77 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | 20521.35 | 21698.31 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | 13067.59 | 13489.31 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | 14217.61 | 14757.88 | - |
MAIN WATER HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Water | 9277.53 | 9300.60 | - |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
OASUPPLYFAN_UNITHEATEDBSMT | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNITHEATEDBSMT | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 292.92 | 110.49 | 0.38 | 1.00 | 2.80 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 156.11 | 58.88 | 0.38 | 1.00 | 4.17 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 208.49 | 78.64 | 0.38 | 1.00 | 3.43 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 275.21 | 103.81 | 0.38 | 1.00 | 2.90 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 144.83 | 54.63 | 0.38 | 1.00 | 4.40 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 196.78 | 74.22 | 0.38 | 1.00 | 3.57 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 323.72 | 122.11 | 0.38 | 1.00 | 2.65 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 181.00 | 68.27 | 0.38 | 1.00 | 3.77 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 234.99 | 88.64 | 0.38 | 1.00 | 3.19 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 304.08 | 114.70 | 0.38 | 1.00 | 2.74 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 167.79 | 63.29 | 0.38 | 1.00 | 3.97 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 220.33 | 83.11 | 0.38 | 1.00 | 3.32 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 361.46 | 136.34 | 0.38 | 1.00 | 2.50 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 218.77 | 82.52 | 0.38 | 1.00 | 3.33 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 246.94 | 93.14 | 0.38 | 1.00 | 3.09 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 356.45 | 134.45 | 0.38 | 1.00 | 2.52 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 216.14 | 81.53 | 0.38 | 1.00 | 3.36 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 237.79 | 89.69 | 0.38 | 1.00 | 3.16 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 0.50 | 0.06 | 144.80 | 54.62 | 0.38 | 1.00 | 4.40 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:10:00 |
Type | Control | Head [psi] | Water Flow [gal/min] | Electricity Rate [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | End Use Subcategory | |
BOILER CIRC PUMP | Pump:VariableSpeed | Intermittent | 0.00 | 27.567937 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 6759.61 | 6759.61 | 5.63 | 292.918 | 292.918 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 75.00 | 75.00 | 0.00831 | 86.10 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 3602.36 | 3602.36 | 3.00 | 156.106 | 156.106 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 75.00 | 75.00 | 0.00875 | 82.09 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4811.18 | 4811.18 | 4.01 | 208.486 | 208.486 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 75.00 | 75.00 | 0.00838 | 82.65 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 6351.03 | 6351.03 | 5.29 | 275.213 | 275.213 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 75.00 | 75.00 | 0.00833 | 85.83 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 3342.13 | 3342.13 | 2.78 | 144.829 | 144.829 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 75.00 | 75.00 | 0.00880 | 82.09 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4541.03 | 4541.03 | 3.78 | 196.779 | 196.779 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 75.00 | 75.00 | 0.00844 | 80.89 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 7470.51 | 7470.51 | 6.22 | 323.725 | 323.725 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 75.00 | 75.00 | 0.00833 | 85.56 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4176.91 | 4176.91 | 3.48 | 181.004 | 181.004 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 75.00 | 75.00 | 0.00870 | 82.09 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5422.81 | 5422.81 | 4.52 | 234.990 | 234.990 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 75.00 | 75.00 | 0.00833 | 83.45 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 7017.21 | 7017.21 | 5.84 | 304.082 | 304.082 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 75.00 | 75.00 | 0.00837 | 85.30 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 3871.91 | 3871.91 | 3.23 | 167.788 | 167.788 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:40:00 | 75.00 | 75.00 | 0.00874 | 80.92 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5084.55 | 5084.55 | 4.24 | 220.332 | 220.332 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 75.00 | 75.00 | 0.00840 | 81.34 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 5487.35 | 5487.35 | 4.57 | 237.789 | 237.789 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:20:00 | 75.00 | 75.00 | 0.00850 | 83.69 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 5698.59 | 5698.59 | 4.75 | 246.943 | 246.943 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 75.00 | 75.00 | 0.00829 | 88.34 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8341.24 | 8341.24 | 6.95 | 361.457 | 361.457 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 75.00 | 75.00 | 0.00831 | 85.56 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 4987.78 | 4987.78 | 4.15 | 216.143 | 216.143 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 75.00 | 75.00 | 0.00860 | 82.09 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 5048.44 | 5048.44 | 4.21 | 218.771 | 218.771 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 75.00 | 75.00 | 0.00859 | 82.09 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8225.68 | 8225.68 | 6.85 | 356.450 | 356.450 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 75.00 | 75.00 | 0.00833 | 85.30 | 0.00823 | 44.995 | 0.00 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.000 | 44.995 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 74.44 | 75.00 | 0.00822 | 88.34 | 0.00823 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2206.25 | 2206.25 | 1.84 | 40.925 | 44.995 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00781 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1144.74 | 1144.74 | 0.95 | 21.235 | 44.995 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00802 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2209.23 | 2209.23 | 1.84 | 40.981 | 44.995 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00781 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2208.69 | 2208.69 | 1.84 | 40.970 | 44.995 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00781 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1144.73 | 1144.73 | 0.95 | 21.234 | 44.995 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00802 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2206.73 | 2206.73 | 1.84 | 40.934 | 44.995 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00781 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1859.11 | 1859.11 | 1.55 | 34.487 | 44.995 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00864 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 703.15 | 703.15 | 0.59 | 13.044 | 44.995 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.01112 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1863.24 | 1863.24 | 1.55 | 34.563 | 44.995 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00864 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1862.44 | 1862.44 | 1.55 | 34.548 | 44.995 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00864 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 704.01 | 704.01 | 0.59 | 13.060 | 44.995 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.01112 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1861.60 | 1861.60 | 1.55 | 34.533 | 44.995 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00864 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 3106.49 | 3106.49 | 2.59 | 57.624 | 57.624 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00783 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 3108.33 | 3108.33 | 2.59 | 57.658 | 57.658 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00783 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 3104.28 | 3104.28 | 2.59 | 57.583 | 57.583 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00783 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1929.61 | 1929.61 | 1.61 | 35.794 | 44.995 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00794 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1929.56 | 1929.56 | 1.61 | 35.793 | 44.995 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00794 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 3106.10 | 3106.10 | 2.59 | 57.617 | 57.617 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00783 | 38.84 | 0.00506 | 44.995 | 0.00 |
HEATEDBSMT | 7805.98 | 7805.98 | 1.00 | 144.799 | 144.799 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:10:00 | 72.00 | 72.00 | 0.00800 | 38.84 | 0.00506 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | Adjusted cooling [ft3/min] | Adjusted heating [ft3/min] | Adjusted main [ft3/min] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 292.92 | 292.92 | 44.99 | 44.99 | 292.9182 | 292.9182 | 292.9182 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 156.11 | 156.11 | 44.99 | 44.99 | 156.1057 | 156.1057 | 156.1057 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 208.49 | 208.49 | 44.99 | 44.99 | 208.4856 | 208.4856 | 208.4856 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 275.21 | 275.21 | 44.99 | 44.99 | 275.2134 | 275.2134 | 275.2134 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 144.83 | 144.83 | 44.99 | 44.99 | 144.8290 | 144.8290 | 144.8290 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 196.78 | 196.78 | 44.99 | 44.99 | 196.7792 | 196.7792 | 196.7792 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 323.72 | 323.72 | 44.99 | 44.99 | 323.7248 | 323.7248 | 323.7248 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 181.00 | 181.00 | 44.99 | 44.99 | 181.0040 | 181.0040 | 181.0040 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 234.99 | 234.99 | 44.99 | 44.99 | 234.9898 | 234.9898 | 234.9898 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 304.08 | 304.08 | 44.99 | 44.99 | 304.0824 | 304.0824 | 304.0824 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 167.79 | 167.79 | 44.99 | 44.99 | 167.7881 | 167.7881 | 167.7881 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 220.33 | 220.33 | 44.99 | 44.99 | 220.3318 | 220.3318 | 220.3318 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 361.46 | 361.46 | 57.58 | 57.58 | 361.4569 | 361.4569 | 361.4569 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 218.77 | 218.77 | 44.99 | 44.99 | 218.7710 | 218.7710 | 218.7710 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 246.94 | 246.94 | 57.66 | 57.66 | 246.9427 | 246.9427 | 246.9427 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 356.45 | 356.45 | 57.62 | 57.62 | 356.4499 | 356.4499 | 356.4499 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 216.14 | 216.14 | 44.99 | 44.99 | 216.1426 | 216.1426 | 216.1426 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 237.79 | 237.79 | 57.62 | 57.62 | 237.7895 | 237.7895 | 237.7895 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 44.99 | 44.99 | 144.80 | 144.80 | 144.7989 | 144.7989 | 144.7989 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 8057.214 | 6448.377 | 292.918180 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 8243.92 | 7853.31 | 292.918180 | 77.90 | 61.79 | 0.00830019 | 53.60 | 51.97 | 0.00800000 | 86.10 | 0.00823151 | 64.47 | 15.3609 | 75.00 | 0.00830869 | 44.2031 | 6756.62 | 0.00 | 8060.58 | 6381.33 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 17146.262 | 17146.262 | 292.918180 | 0.23522765 | 240.003 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17146.26 | 17146.26 | 292.918180 | 66.91 | 56.28 | 0.00738851 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | 15.3609 | 72.00 | 0.00851843 | 50.1090 | 1473.85 | 0.00 | 17996.81 | 17996.81 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 4439.910 | 3554.636 | 156.105711 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 4413.33 | 4019.59 | 156.105711 | 78.24 | 62.36 | 0.00859848 | 53.60 | 51.97 | 0.00800000 | 82.09 | 0.00822799 | 63.13 | 28.8234 | 75.00 | 0.00871751 | 46.3485 | 3567.88 | 0.00 | 4441.76 | 3518.39 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 9878.185 | 9878.185 | 156.105711 | 0.13551771 | 134.562 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9878.19 | 9878.19 | 156.105711 | 62.44 | 54.12 | 0.00716844 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | 28.8234 | 72.00 | 0.00904665 | 53.1721 | 372.03 | 0.00 | 9971.89 | 9971.89 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 5661.782 | 4534.611 | 208.485586 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 5681.02 | 5368.77 | 208.485586 | 77.84 | 61.85 | 0.00835033 | 53.60 | 51.97 | 0.00800000 | 82.65 | 0.00822848 | 63.32 | 21.5818 | 75.00 | 0.00837164 | 44.5335 | 4802.89 | 0.00 | 5664.14 | 4487.15 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 12660.855 | 12660.855 | 208.485586 | 0.17369285 | 174.982 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 12660.85 | 12660.85 | 208.485586 | 64.84 | 55.17 | 0.00721729 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | 21.5818 | 72.00 | 0.00851796 | 50.1063 | 1476.85 | 0.00 | 13048.87 | 13048.87 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 7596.218 | 6077.762 | 275.213447 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 7756.24 | 7369.15 | 275.213447 | 77.96 | 61.84 | 0.00831778 | 53.60 | 51.97 | 0.00800000 | 85.83 | 0.00823127 | 64.38 | 16.3491 | 75.00 | 0.00833469 | 44.3396 | 6351.03 | 0.00 | 7599.39 | 6014.65 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 16205.714 | 16205.714 | 275.213447 | 0.22232437 | 226.380 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 16205.71 | 16205.71 | 275.213447 | 66.58 | 56.11 | 0.00736134 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | 16.3491 | 72.00 | 0.00851805 | 50.1068 | 1476.29 | 0.00 | 16960.22 | 16960.22 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 4151.737 | 3325.158 | 144.829000 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 4122.29 | 3744.52 | 144.829000 | 78.40 | 62.45 | 0.00861991 | 53.60 | 51.97 | 0.00800000 | 82.09 | 0.00822799 | 63.13 | 31.0677 | 75.00 | 0.00879655 | 46.7629 | 3342.13 | 0.00 | 4153.47 | 3290.89 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 9279.123 | 9279.123 | 144.829000 | 0.12729925 | 125.850 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9279.12 | 9279.12 | 144.829000 | 61.70 | 53.70 | 0.00710190 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | 31.0677 | 72.00 | 0.00904665 | 53.1721 | 372.07 | 0.00 | 9307.93 | 9307.93 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 5271.312 | 4221.709 | 196.779171 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 5242.46 | 4921.94 | 196.779171 | 77.54 | 61.80 | 0.00838789 | 53.60 | 51.97 | 0.00800000 | 80.89 | 0.00822694 | 62.72 | 22.8657 | 75.00 | 0.00842771 | 44.8277 | 4529.19 | 0.00 | 5273.51 | 4177.20 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 12038.962 | 12038.962 | 196.779171 | 0.16516116 | 165.960 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 12038.96 | 12038.96 | 196.779171 | 64.42 | 54.94 | 0.00718191 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | 22.8657 | 72.00 | 0.00851836 | 50.1086 | 1474.35 | 0.00 | 12361.97 | 12361.97 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 8828.724 | 7066.386 | 323.724786 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 9013.20 | 8563.06 | 323.724786 | 77.66 | 61.73 | 0.00831452 | 53.60 | 51.97 | 0.00800000 | 85.56 | 0.00823104 | 64.30 | 13.8991 | 75.00 | 0.00830443 | 44.1808 | 7461.10 | 0.00 | 8832.41 | 6992.84 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 18782.519 | 18782.519 | 323.724786 | 0.25767528 | 263.552 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 18782.52 | 18782.52 | 323.724786 | 67.39 | 57.73 | 0.00814341 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | 13.8991 | 72.00 | 0.00993127 | 58.2877 | 1005.66 | 0.00 | 19799.68 | 19799.68 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 5090.422 | 4074.943 | 181.004048 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 5067.94 | 4624.24 | 181.004048 | 77.95 | 62.24 | 0.00858030 | 53.60 | 51.97 | 0.00800000 | 82.09 | 0.00822799 | 63.13 | 24.8586 | 75.00 | 0.00869685 | 46.2403 | 4176.91 | 0.00 | 5092.55 | 4032.15 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 11200.660 | 11200.660 | 181.004048 | 0.15366060 | 153.478 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 11200.66 | 11200.66 | 181.004048 | 63.76 | 58.77 | 0.00961309 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | 24.8586 | 32.00 | 0.00000000 | 0.2615 | 703.15 | 0.00 | 11435.59 | 11435.59 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 6366.855 | 5098.251 | 234.989791 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 6421.41 | 6102.54 | 234.989791 | 77.81 | 61.79 | 0.00831436 | 53.60 | 51.97 | 0.00800000 | 83.45 | 0.00822918 | 63.59 | 19.1476 | 75.00 | 0.00832226 | 44.2742 | 5397.69 | 0.00 | 6369.51 | 5044.92 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 14068.651 | 14068.651 | 234.989791 | 0.19300625 | 195.309 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 14068.65 | 14068.65 | 234.989791 | 65.65 | 56.75 | 0.00795385 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | 19.1476 | 72.00 | 0.00992750 | 58.2659 | 1009.82 | 0.00 | 14603.69 | 14603.69 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 8338.667 | 6674.428 | 304.082424 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 8493.47 | 8028.36 | 304.082424 | 77.72 | 61.80 | 0.00834734 | 53.60 | 51.97 | 0.00800000 | 85.30 | 0.00823080 | 64.21 | 14.7970 | 75.00 | 0.00834197 | 44.3779 | 7007.60 | 0.00 | 8342.15 | 6604.99 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 17739.058 | 17739.058 | 304.082424 | 0.24336015 | 248.452 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17739.06 | 17739.06 | 304.082424 | 67.09 | 57.56 | 0.00810996 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | 14.7970 | 72.00 | 0.00992832 | 58.2707 | 1008.96 | 0.00 | 18650.15 | 18650.15 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 4678.791 | 3745.317 | 167.788136 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:40:00 | 4630.24 | 4208.06 | 167.788136 | 77.78 | 62.21 | 0.00860288 | 53.60 | 51.97 | 0.00800000 | 80.92 | 0.00822696 | 62.73 | 26.8165 | 75.00 | 0.00874521 | 46.4939 | 3865.89 | 0.00 | 4680.74 | 3706.19 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 10498.602 | 10498.602 | 167.788136 | 0.14402914 | 143.307 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10498.60 | 10498.60 | 167.788136 | 63.11 | 58.33 | 0.00949143 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | 26.8165 | 32.00 | 0.00000000 | 0.2615 | 704.01 | 0.00 | 10658.95 | 10658.95 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 5882.190 | 4706.523 | 220.331756 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 5868.39 | 5532.23 | 220.331756 | 77.49 | 61.75 | 0.00836125 | 53.60 | 51.97 | 0.00800000 | 81.34 | 0.00822733 | 62.87 | 20.4215 | 75.00 | 0.00836885 | 44.5189 | 5055.13 | 0.00 | 5884.64 | 4657.14 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 13289.973 | 13289.973 | 220.331756 | 0.18232364 | 184.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 13289.97 | 13289.97 | 220.331756 | 65.23 | 56.51 | 0.00790882 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | 20.4215 | 72.00 | 0.00992901 | 58.2747 | 1008.19 | 0.00 | 13744.38 | 13744.38 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 9780.281 | 7826.506 | 361.456929 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 9994.01 | 9518.72 | 361.456929 | 77.51 | 61.65 | 0.00829707 | 53.60 | 51.97 | 0.00800000 | 85.56 | 0.00823104 | 64.30 | 12.4482 | 75.00 | 0.00830646 | 44.1915 | 8341.24 | 0.00 | 9784.36 | 7744.97 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 20787.344 | 20787.344 | 361.456929 | 0.28517925 | 292.716 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 20787.34 | 20787.34 | 361.456929 | 67.87 | 56.82 | 0.00748555 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | 12.4482 | 72.00 | 0.00783064 | 46.1148 | 3104.28 | 0.00 | 22007.40 | 22007.40 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 6039.524 | 4831.826 | 218.771040 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 6027.69 | 5545.97 | 218.771040 | 77.65 | 62.04 | 0.00851950 | 53.60 | 51.97 | 0.00800000 | 82.09 | 0.00822799 | 63.13 | 20.5672 | 75.00 | 0.00859498 | 45.7060 | 5048.44 | 0.00 | 6042.04 | 4781.68 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 13207.223 | 13207.223 | 218.771040 | 0.18118841 | 182.908 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 13207.22 | 13207.22 | 218.771040 | 65.18 | 55.54 | 0.00735089 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | 20.5672 | 72.00 | 0.00880458 | 51.7687 | 1039.94 | 0.00 | 13652.95 | 13652.95 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 7021.121 | 5621.987 | 246.942720 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 7255.08 | 6941.10 | 246.942720 | 78.62 | 62.02 | 0.00828022 | 53.60 | 51.97 | 0.00800000 | 88.34 | 0.00823349 | 65.21 | 18.2208 | 75.00 | 0.00829064 | 44.1085 | 5698.59 | 0.00 | 7024.05 | 5564.65 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 14703.870 | 14703.870 | 246.942720 | 0.20172074 | 204.617 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 14703.87 | 14703.87 | 246.942720 | 65.96 | 55.80 | 0.00732560 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | 18.2208 | 72.00 | 0.00783074 | 46.1153 | 3108.33 | 0.00 | 15304.28 | 15304.28 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 9661.084 | 7734.883 | 356.449899 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 9854.29 | 9350.68 | 356.449899 | 77.49 | 61.68 | 0.00832025 | 53.60 | 51.97 | 0.00800000 | 85.30 | 0.00823080 | 64.21 | 12.6231 | 75.00 | 0.00830940 | 44.2070 | 8217.83 | 0.00 | 9665.11 | 7654.07 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 20521.350 | 20521.350 | 356.449899 | 0.28153010 | 288.866 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 20521.35 | 20521.35 | 356.449899 | 67.81 | 56.79 | 0.00748074 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | 12.6231 | 72.00 | 0.00783068 | 46.1150 | 3106.10 | 0.00 | 21714.51 | 21714.51 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 5973.831 | 4782.804 | 216.142569 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 5961.23 | 5481.81 | 216.142569 | 77.67 | 62.05 | 0.00852342 | 53.60 | 51.97 | 0.00800000 | 82.09 | 0.00822799 | 63.13 | 20.8173 | 75.00 | 0.00859220 | 45.6914 | 4968.82 | 0.00 | 5976.32 | 4732.93 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 13067.588 | 13067.588 | 216.142569 | 0.17927277 | 180.884 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 13067.59 | 13067.59 | 216.142569 | 65.10 | 55.49 | 0.00734367 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | 20.8173 | 72.00 | 0.00880458 | 51.7686 | 1040.02 | 0.00 | 13498.81 | 13498.81 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 6594.977 | 5278.597 | 237.789455 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:20:00 | 6642.53 | 6178.02 | 237.789455 | 77.84 | 62.01 | 0.00845279 | 53.60 | 51.97 | 0.00800000 | 83.69 | 0.00822939 | 63.67 | 18.9222 | 75.00 | 0.00847466 | 45.0745 | 5474.47 | 0.00 | 6597.73 | 5223.60 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 14217.610 | 14217.610 | 237.789455 | 0.19504980 | 197.570 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 14217.61 | 14217.61 | 237.789455 | 65.73 | 55.68 | 0.00730612 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | 18.9222 | 72.00 | 0.00783069 | 46.1151 | 3106.49 | 0.00 | 14767.90 | 14767.90 |
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | 5404.248 | 3905.169 | 144.798852 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 5313.07 | 5172.34 | 144.798852 | 89.53 | 65.59 | 0.00823349 | 53.60 | 51.97 | 0.00800000 | 88.34 | 0.00823349 | 65.21 | 31.0741 | 74.44 | 0.00822186 | 44.5663 | 0.00 | 0.00 | 5406.50 | 3871.17 |
MAIN WATER HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | 9277.527 | 9277.527 | 144.798852 | 0.12727735 | 125.828 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:10:00 | 9277.53 | 9277.53 | 144.798852 | 61.70 | 53.67 | 0.00708593 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | 31.0741 | 72.00 | 0.00800000 | 47.0989 | 7805.98 | 0.00 | 9306.15 | 9306.15 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [Btu/lbm-R] | Dry Air Heat Capacity [Btu/lbm-R] | Standard Air Density Adjusted for Elevation [lb/ft3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [ft3/min] | Supply Fan Maximum Air Mass Flow Rate [lb/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [Btu/lbm-R] | Plant Fluid Density [lb/ft3] | Plant Maximum Fluid Mass Flow Rate [lb/s] | Plant Design Fluid Return Temperature [F] | Plant Design Fluid Supply Temperature [F] | Plant Design Fluid Temperature Difference [deltaF] | Plant Design Capacity [Btu/h] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] | Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] | Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] | Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [F] | System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | Coil Air Mass Flow Rate at Rating Conditions [lb/s] | Coil Entering Air Drybulb at Rating Conditions [F] | Coil Entering Air Wetbulb at Rating Conditions [F] | Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] | Coil Leaving Air Drybulb at Rating Conditions [F] | Coil Leaving Air Wetbulb at Rating Conditions [F] | Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8057.214 | 6448.377 | 292.918180 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2437 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 292.918180 | 0.36020881 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | Sensible | 8243.92 | 7853.31 | 0.9774 | 0.36020881 | 292.918180 | 77.90 | 61.79 | 0.00830019 | 11.2 | 53.60 | 51.97 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 376.980 | 7866.94 | 86.10 | 0.00823151 | 64.47 | 44.99498340 | 15.3609 | 75.00 | 0.00831265 | 75.00 | 0.00830869 | 44.2031 | 6756.62 | 0.00 | 8060.58 | 6381.33 | 0.34598328 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.04 | 57.88 | 0.00995510 | 9.6 | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 17146.262 | 17146.262 | 292.918180 | 0.23522765 | 240.003 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 292.918180 | 0.36020881 | 1.0027 | 62.4216 | 3.83359033 | 159.80 | 179.60 | 19.80 | 273976.17 | 6.2583 | 6.384255 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 17146.26 | 17146.26 | 1.0000 | 0.36020881 | 292.918180 | 66.91 | 56.28 | 0.00738851 | 9.1 | 122.00 | 74.75 | 0.00800000 | 17.0 | 0.24474618 | 140.00 | 120.20 | 19.80 | 0.000 | 17146.26 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | 15.3609 | 72.00 | 0.00781139 | 72.00 | 0.00851843 | 50.1090 | 1473.85 | 0.00 | 17996.81 | 17996.81 | 0.36020881 | 61.88 | 54.59 | 0.00738851 | 8.5 | 118.93 | 73.62 | 0.00738851 | 16.2 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4439.910 | 3554.636 | 156.105711 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2438 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 156.105711 | 0.19196710 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 4413.33 | 4019.59 | 1.0060 | 0.19196710 | 156.105711 | 78.24 | 62.36 | 0.00859848 | 11.4 | 53.60 | 51.97 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 200.905 | 4212.42 | 82.09 | 0.00822799 | 63.13 | 44.99498340 | 28.8234 | 75.00 | 0.00874851 | 75.00 | 0.00871751 | 46.3485 | 3567.88 | 0.00 | 4441.76 | 3518.39 | 0.18438585 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.31 | 57.54 | 0.00991601 | 9.5 | |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 9878.185 | 9878.185 | 156.105711 | 0.13551771 | 134.562 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 156.105711 | 0.19196710 | 1.0027 | 62.4216 | 3.83359033 | 159.80 | 179.60 | 19.80 | 273976.17 | 3.6055 | 3.678052 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9878.19 | 9878.19 | 1.0000 | 0.19196710 | 156.105711 | 62.44 | 54.12 | 0.00716844 | 8.4 | 122.00 | 74.75 | 0.00800000 | 17.0 | 0.14100146 | 140.00 | 120.20 | 19.80 | 0.000 | 9878.19 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | 28.8234 | 72.00 | 0.00802289 | 72.00 | 0.00904665 | 53.1721 | 372.03 | 0.00 | 9971.89 | 9971.89 | 0.19196710 | 61.88 | 54.20 | 0.00716844 | 8.3 | 121.22 | 73.98 | 0.00716844 | 16.3 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5661.782 | 4534.611 | 208.485586 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2437 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 208.485586 | 0.25637994 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | Sensible | 5681.02 | 5368.77 | 0.9966 | 0.25637994 | 208.485586 | 77.84 | 61.85 | 0.00835033 | 11.2 | 53.60 | 51.97 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 268.317 | 5412.70 | 82.65 | 0.00822848 | 63.32 | 44.99498340 | 21.5818 | 75.00 | 0.00838387 | 75.00 | 0.00837164 | 44.5335 | 4802.89 | 0.00 | 5664.14 | 4487.15 | 0.24625487 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.29 | 58.01 | 0.00997384 | 9.7 | |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 12660.855 | 12660.855 | 208.485586 | 0.17369285 | 174.982 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 208.485586 | 0.25637994 | 1.0027 | 62.4216 | 3.83359033 | 159.80 | 179.60 | 19.80 | 273976.17 | 4.6212 | 4.714154 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 12660.85 | 12660.85 | 1.0000 | 0.25637994 | 208.485586 | 64.84 | 55.17 | 0.00721729 | 8.7 | 122.00 | 74.75 | 0.00800000 | 17.0 | 0.18072136 | 140.00 | 120.20 | 19.80 | 0.000 | 12660.85 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | 21.5818 | 72.00 | 0.00781145 | 72.00 | 0.00851796 | 50.1063 | 1476.85 | 0.00 | 13048.87 | 13048.87 | 0.25637994 | 61.88 | 54.29 | 0.00721729 | 8.3 | 120.01 | 73.71 | 0.00721729 | 16.2 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7596.218 | 6077.762 | 275.213447 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2437 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 275.213447 | 0.33843685 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | Sensible | 7756.24 | 7369.15 | 0.9794 | 0.33843685 | 275.213447 | 77.96 | 61.84 | 0.00831778 | 11.2 | 53.60 | 51.97 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 354.195 | 7402.04 | 85.83 | 0.00823127 | 64.38 | 44.99498340 | 16.3491 | 75.00 | 0.00833469 | 75.00 | 0.00833469 | 44.3396 | 6351.03 | 0.00 | 7599.39 | 6014.65 | 0.32507116 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.97 | 57.85 | 0.00994965 | 9.6 | |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 16205.714 | 16205.714 | 275.213447 | 0.22232437 | 226.380 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 275.213447 | 0.33843685 | 1.0027 | 62.4216 | 3.83359033 | 159.80 | 179.60 | 19.80 | 273976.17 | 5.9150 | 6.034050 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 16205.71 | 16205.71 | 1.0000 | 0.33843685 | 275.213447 | 66.58 | 56.11 | 0.00736134 | 9.1 | 122.00 | 74.75 | 0.00800000 | 17.0 | 0.23132077 | 140.00 | 120.20 | 19.80 | 0.000 | 16205.71 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | 16.3491 | 72.00 | 0.00781144 | 72.00 | 0.00851805 | 50.1068 | 1476.29 | 0.00 | 16960.22 | 16960.22 | 0.33843685 | 61.88 | 54.55 | 0.00736134 | 8.4 | 119.10 | 73.63 | 0.00736134 | 16.2 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4151.737 | 3325.158 | 144.829000 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2438 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 144.829000 | 0.17809984 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 4122.29 | 3744.52 | 1.0071 | 0.17809984 | 144.829000 | 78.40 | 62.45 | 0.00861991 | 11.4 | 53.60 | 51.97 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 186.392 | 3935.89 | 82.09 | 0.00822799 | 63.13 | 44.99498340 | 31.0677 | 75.00 | 0.00879655 | 75.00 | 0.00879655 | 46.7629 | 3342.13 | 0.00 | 4153.47 | 3290.89 | 0.17106624 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.13 | 57.45 | 0.00990726 | 9.5 | |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 9279.123 | 9279.123 | 144.829000 | 0.12729925 | 125.850 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 144.829000 | 0.17809984 | 1.0027 | 62.4216 | 3.83359033 | 159.80 | 179.60 | 19.80 | 273976.17 | 3.3868 | 3.454997 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9279.12 | 9279.12 | 1.0000 | 0.17809984 | 144.829000 | 61.70 | 53.70 | 0.00710190 | 8.3 | 122.00 | 74.75 | 0.00800000 | 17.0 | 0.13245044 | 140.00 | 120.20 | 19.80 | 0.000 | 9279.12 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | 31.0677 | 72.00 | 0.00802289 | 72.00 | 0.00904665 | 53.1721 | 372.07 | 0.00 | 9307.93 | 9307.93 | 0.17809984 | 61.88 | 54.08 | 0.00710190 | 8.3 | 121.59 | 74.00 | 0.00710190 | 16.3 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5271.312 | 4221.709 | 196.779171 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2437 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 196.779171 | 0.24198427 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | Sensible | 5242.46 | 4921.94 | 1.0055 | 0.24198427 | 196.779171 | 77.54 | 61.80 | 0.00838789 | 11.2 | 53.60 | 51.97 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 253.251 | 4989.21 | 80.89 | 0.00822694 | 62.72 | 44.99498340 | 22.8657 | 75.00 | 0.00843560 | 75.00 | 0.00842771 | 44.8277 | 4529.19 | 0.00 | 5273.51 | 4177.20 | 0.23242772 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.58 | 58.14 | 0.00998974 | 9.7 | |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 12038.962 | 12038.962 | 196.779171 | 0.16516116 | 165.960 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 196.779171 | 0.24198427 | 1.0027 | 62.4216 | 3.83359033 | 159.80 | 179.60 | 19.80 | 273976.17 | 4.3942 | 4.482598 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 12038.96 | 12038.96 | 1.0000 | 0.24198427 | 196.779171 | 64.42 | 54.94 | 0.00718191 | 8.7 | 122.00 | 74.75 | 0.00800000 | 17.0 | 0.17184444 | 140.00 | 120.20 | 19.80 | 0.000 | 12038.96 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | 22.8657 | 72.00 | 0.00781140 | 72.00 | 0.00851836 | 50.1086 | 1474.35 | 0.00 | 12361.97 | 12361.97 | 0.24198427 | 61.88 | 54.22 | 0.00718191 | 8.3 | 120.23 | 73.73 | 0.00718191 | 16.2 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8828.724 | 7066.386 | 323.724786 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2437 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 323.724786 | 0.39809246 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | Sensible | 9013.20 | 8563.06 | 0.9795 | 0.39809246 | 323.724786 | 77.66 | 61.73 | 0.00831452 | 11.1 | 53.60 | 51.97 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 416.628 | 8596.57 | 85.56 | 0.00823104 | 64.30 | 44.99498340 | 13.8991 | 75.00 | 0.00832800 | 75.00 | 0.00830443 | 44.1808 | 7461.10 | 0.00 | 8832.41 | 6992.84 | 0.38237082 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.22 | 57.97 | 0.00996589 | 9.6 | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 18782.519 | 18782.519 | 323.724786 | 0.25767528 | 263.552 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 323.724786 | 0.39809246 | 1.0027 | 62.4216 | 3.83359033 | 159.80 | 179.60 | 19.80 | 273976.17 | 6.8555 | 6.993500 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 18782.52 | 18782.52 | 1.0000 | 0.39809246 | 323.724786 | 67.39 | 57.73 | 0.00814341 | 9.7 | 122.00 | 74.75 | 0.00800000 | 17.0 | 0.26810216 | 140.00 | 120.20 | 19.80 | 0.000 | 18782.52 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | 13.8991 | 72.00 | 0.00864141 | 72.00 | 0.00993127 | 58.2877 | 1005.66 | 0.00 | 19799.68 | 19799.68 | 0.39809246 | 61.88 | 55.92 | 0.00814341 | 8.9 | 118.59 | 74.43 | 0.00814341 | 16.6 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5090.422 | 4074.943 | 181.004048 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2438 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 181.004048 | 0.22258520 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 5067.94 | 4624.24 | 1.0044 | 0.22258520 | 181.004048 | 77.95 | 62.24 | 0.00858030 | 11.3 | 53.60 | 51.97 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 232.949 | 4834.99 | 82.09 | 0.00822799 | 63.13 | 44.99498340 | 24.8586 | 75.00 | 0.00869685 | 75.00 | 0.00869685 | 46.2403 | 4176.91 | 0.00 | 5092.55 | 4032.15 | 0.21379477 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.56 | 57.65 | 0.00992816 | 9.5 | |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 11200.660 | 11200.660 | 181.004048 | 0.15366060 | 153.478 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 181.004048 | 0.22258520 | 1.0027 | 62.4216 | 3.83359033 | 159.80 | 179.60 | 19.80 | 273976.17 | 4.0882 | 4.170464 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 11200.66 | 11200.66 | 1.0000 | 0.22258520 | 181.004048 | 63.76 | 58.77 | 0.00961309 | 10.1 | 122.00 | 74.75 | 0.00800000 | 17.0 | 0.15987850 | 140.00 | 120.20 | 19.80 | 0.000 | 11200.66 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | 24.8586 | 72.00 | 0.01111988 | 32.00 | 0.00000000 | 0.2615 | 703.15 | 0.00 | 11435.59 | 11435.59 | 0.22258520 | 61.88 | 58.40 | 0.00961309 | 9.8 | 120.31 | 76.58 | 0.00961309 | 17.7 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6366.855 | 5098.251 | 234.989791 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2437 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 234.989791 | 0.28897282 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | Sensible | 6421.41 | 6102.54 | 0.9915 | 0.28897282 | 234.989791 | 77.81 | 61.79 | 0.00831436 | 11.2 | 53.60 | 51.97 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 302.427 | 6118.98 | 83.45 | 0.00822918 | 63.59 | 44.99498340 | 19.1476 | 75.00 | 0.00833453 | 75.00 | 0.00832226 | 44.2742 | 5397.69 | 0.00 | 6369.51 | 5044.92 | 0.27756058 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.34 | 58.03 | 0.00997569 | 9.7 | |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 14068.651 | 14068.651 | 234.989791 | 0.19300625 | 195.309 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 234.989791 | 0.28897282 | 1.0027 | 62.4216 | 3.83359033 | 159.80 | 179.60 | 19.80 | 273976.17 | 5.1350 | 5.238335 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 14068.65 | 14068.65 | 1.0000 | 0.28897282 | 234.989791 | 65.65 | 56.75 | 0.00795385 | 9.3 | 122.00 | 74.75 | 0.00800000 | 17.0 | 0.20081629 | 140.00 | 120.20 | 19.80 | 0.000 | 14068.65 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | 19.1476 | 72.00 | 0.00863955 | 72.00 | 0.00992750 | 58.2659 | 1009.82 | 0.00 | 14603.69 | 14603.69 | 0.28897282 | 61.88 | 55.59 | 0.00795385 | 8.8 | 119.52 | 74.46 | 0.00795385 | 16.6 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8338.667 | 6674.428 | 304.082424 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2437 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 304.082424 | 0.37393776 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | Sensible | 8493.47 | 8028.36 | 0.9818 | 0.37393776 | 304.082424 | 77.72 | 61.80 | 0.00834734 | 11.2 | 53.60 | 51.97 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 391.348 | 8102.12 | 85.30 | 0.00823080 | 64.21 | 44.99498340 | 14.7970 | 75.00 | 0.00836757 | 75.00 | 0.00834197 | 44.3779 | 7007.60 | 0.00 | 8342.15 | 6604.99 | 0.35917004 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.10 | 57.91 | 0.00995939 | 9.6 | |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 17739.058 | 17739.058 | 304.082424 | 0.24336015 | 248.452 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 304.082424 | 0.37393776 | 1.0027 | 62.4216 | 3.83359033 | 159.80 | 179.60 | 19.80 | 273976.17 | 6.4747 | 6.604977 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 17739.06 | 17739.06 | 1.0000 | 0.37393776 | 304.082424 | 67.09 | 57.56 | 0.00810996 | 9.6 | 122.00 | 74.75 | 0.00800000 | 17.0 | 0.25320777 | 140.00 | 120.20 | 19.80 | 0.000 | 17739.06 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | 14.7970 | 72.00 | 0.00863991 | 72.00 | 0.00992832 | 58.2707 | 1008.96 | 0.00 | 18650.15 | 18650.15 | 0.37393776 | 61.88 | 55.86 | 0.00810996 | 8.9 | 118.75 | 74.43 | 0.00810996 | 16.6 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4678.791 | 3745.317 | 167.788136 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2438 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 167.788136 | 0.20633326 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:40:00 | Sensible | 4630.24 | 4208.06 | 1.0105 | 0.20633326 | 167.788136 | 77.78 | 62.21 | 0.00860288 | 11.3 | 53.60 | 51.97 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 215.940 | 4414.30 | 80.92 | 0.00822696 | 62.73 | 44.99498340 | 26.8165 | 75.00 | 0.00874063 | 75.00 | 0.00874521 | 46.4939 | 3865.89 | 0.00 | 4680.74 | 3706.19 | 0.19818466 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.75 | 57.74 | 0.00993891 | 9.6 | |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 10498.602 | 10498.602 | 167.788136 | 0.14402914 | 143.307 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 167.788136 | 0.20633326 | 1.0027 | 62.4216 | 3.83359033 | 159.80 | 179.60 | 19.80 | 273976.17 | 3.8319 | 3.909059 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10498.60 | 10498.60 | 1.0000 | 0.20633326 | 167.788136 | 63.11 | 58.33 | 0.00949143 | 9.9 | 122.00 | 74.75 | 0.00800000 | 17.0 | 0.14985730 | 140.00 | 120.20 | 19.80 | 0.000 | 10498.60 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | 26.8165 | 72.00 | 0.01111580 | 32.00 | 0.00000000 | 0.2615 | 704.01 | 0.00 | 10658.95 | 10658.95 | 0.20633326 | 61.88 | 58.20 | 0.00949143 | 9.7 | 120.64 | 76.53 | 0.00949143 | 17.7 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5882.190 | 4706.523 | 220.331756 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2437 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 220.331756 | 0.27094747 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | Sensible | 5868.39 | 5532.23 | 1.0024 | 0.27094747 | 220.331756 | 77.49 | 61.75 | 0.00836125 | 11.2 | 53.60 | 51.97 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 283.563 | 5584.83 | 81.34 | 0.00822733 | 62.87 | 44.99498340 | 20.4215 | 75.00 | 0.00839562 | 75.00 | 0.00836885 | 44.5189 | 5055.13 | 0.00 | 5884.64 | 4657.14 | 0.26024709 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.66 | 58.18 | 0.00998977 | 9.7 | |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 13289.973 | 13289.973 | 220.331756 | 0.18232364 | 184.026 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 220.331756 | 0.27094747 | 1.0027 | 62.4216 | 3.83359033 | 159.80 | 179.60 | 19.80 | 273976.17 | 4.8508 | 4.948401 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 13289.97 | 13289.97 | 1.0000 | 0.27094747 | 220.331756 | 65.23 | 56.51 | 0.00790882 | 9.2 | 122.00 | 74.75 | 0.00800000 | 17.0 | 0.18970141 | 140.00 | 120.20 | 19.80 | 0.000 | 13289.97 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | 20.4215 | 72.00 | 0.00864029 | 72.00 | 0.00992901 | 58.2747 | 1008.19 | 0.00 | 13744.38 | 13744.38 | 0.27094747 | 61.88 | 55.51 | 0.00790882 | 8.8 | 119.75 | 74.46 | 0.00790882 | 16.6 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9780.281 | 7826.506 | 361.456929 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2437 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 361.456929 | 0.44449262 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | Sensible | 9994.01 | 9518.72 | 0.9786 | 0.44449262 | 361.456929 | 77.51 | 61.65 | 0.00829707 | 11.1 | 53.60 | 51.97 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 465.188 | 9528.82 | 85.56 | 0.00823104 | 64.30 | 44.99498340 | 12.4482 | 75.00 | 0.00830646 | 75.00 | 0.00830646 | 44.1915 | 8341.24 | 0.00 | 9784.36 | 7744.97 | 0.42693852 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.38 | 58.04 | 0.00997454 | 9.7 | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 20787.344 | 20787.344 | 361.456929 | 0.28517925 | 292.716 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 361.456929 | 0.44449262 | 1.0027 | 62.4216 | 3.83359033 | 159.80 | 179.60 | 19.80 | 273976.17 | 7.5873 | 7.739979 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 20787.34 | 20787.34 | 1.0000 | 0.44449262 | 361.456929 | 67.87 | 56.82 | 0.00748555 | 9.3 | 122.00 | 74.75 | 0.00800000 | 17.0 | 0.29671908 | 140.00 | 120.20 | 19.80 | 0.000 | 20787.34 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | 12.4482 | 72.00 | 0.00783064 | 72.00 | 0.00783064 | 46.1148 | 3104.28 | 0.00 | 22007.40 | 22007.40 | 0.44449262 | 61.88 | 54.77 | 0.00748555 | 8.5 | 118.40 | 73.59 | 0.00748555 | 16.2 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6039.524 | 4831.826 | 218.771040 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2438 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 218.771040 | 0.26902822 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 6027.69 | 5545.97 | 1.0020 | 0.26902822 | 218.771040 | 77.65 | 62.04 | 0.00851950 | 11.3 | 53.60 | 51.97 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 281.554 | 5746.13 | 82.09 | 0.00822799 | 63.13 | 44.99498340 | 20.5672 | 75.00 | 0.00859498 | 75.00 | 0.00859498 | 45.7060 | 5048.44 | 0.00 | 6042.04 | 4781.68 | 0.25840364 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.97 | 57.84 | 0.00994902 | 9.6 | |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 13207.223 | 13207.223 | 218.771040 | 0.18118841 | 182.908 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 218.771040 | 0.26902822 | 1.0027 | 62.4216 | 3.83359033 | 159.80 | 179.60 | 19.80 | 273976.17 | 4.8206 | 4.917589 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 13207.22 | 13207.22 | 1.0000 | 0.26902822 | 218.771040 | 65.18 | 55.54 | 0.00735089 | 8.9 | 122.00 | 74.75 | 0.00800000 | 17.0 | 0.18852023 | 140.00 | 120.20 | 19.80 | 0.000 | 13207.22 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | 20.5672 | 72.00 | 0.00794446 | 72.00 | 0.00880458 | 51.7687 | 1039.94 | 0.00 | 13652.95 | 13652.95 | 0.26902822 | 61.88 | 54.53 | 0.00735089 | 8.4 | 119.83 | 73.82 | 0.00735089 | 16.3 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7021.121 | 5621.987 | 246.942720 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2437 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 246.942720 | 0.30367164 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | Sensible | 7255.08 | 6941.10 | 0.9678 | 0.30367164 | 246.942720 | 78.62 | 62.02 | 0.00828022 | 11.3 | 53.60 | 51.97 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 317.811 | 6937.27 | 88.34 | 0.00823349 | 65.21 | 44.99498340 | 18.2208 | 75.00 | 0.00829064 | 75.00 | 0.00829064 | 44.1085 | 5698.59 | 0.00 | 7024.05 | 5564.65 | 0.29167890 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.32 | 57.54 | 0.00991712 | 9.5 | |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 14703.870 | 14703.870 | 246.942720 | 0.20172074 | 204.617 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 246.942720 | 0.30367164 | 1.0027 | 62.4216 | 3.83359033 | 159.80 | 179.60 | 19.80 | 273976.17 | 5.3668 | 5.474852 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 14703.87 | 14703.87 | 1.0000 | 0.30367164 | 246.942720 | 65.96 | 55.80 | 0.00732560 | 9.0 | 122.00 | 74.75 | 0.00800000 | 17.0 | 0.20988341 | 140.00 | 120.20 | 19.80 | 0.000 | 14703.87 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | 18.2208 | 72.00 | 0.00783074 | 72.00 | 0.00783074 | 46.1153 | 3108.33 | 0.00 | 15304.28 | 15304.28 | 0.30367164 | 61.88 | 54.48 | 0.00732560 | 8.4 | 119.43 | 73.68 | 0.00732560 | 16.2 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9661.084 | 7734.883 | 356.449899 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2437 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 356.449899 | 0.43833535 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | Sensible | 9854.29 | 9350.68 | 0.9804 | 0.43833535 | 356.449899 | 77.49 | 61.68 | 0.00832025 | 11.1 | 53.60 | 51.97 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 458.744 | 9395.55 | 85.30 | 0.00823080 | 64.21 | 44.99498340 | 12.6231 | 75.00 | 0.00833317 | 75.00 | 0.00830940 | 44.2070 | 8217.83 | 0.00 | 9665.11 | 7654.07 | 0.42102442 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.34 | 58.03 | 0.00997460 | 9.7 | |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 20521.350 | 20521.350 | 356.449899 | 0.28153010 | 288.866 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 356.449899 | 0.43833535 | 1.0027 | 62.4216 | 3.83359033 | 159.80 | 179.60 | 19.80 | 273976.17 | 7.4902 | 7.640938 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 20521.35 | 20521.35 | 1.0000 | 0.43833535 | 356.449899 | 67.81 | 56.79 | 0.00748074 | 9.3 | 122.00 | 74.75 | 0.00800000 | 17.0 | 0.29292227 | 140.00 | 120.20 | 19.80 | 0.000 | 20521.35 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | 12.6231 | 72.00 | 0.00783068 | 72.00 | 0.00783068 | 46.1150 | 3106.10 | 0.00 | 21714.51 | 21714.51 | 0.43833535 | 61.88 | 54.76 | 0.00748074 | 8.5 | 118.43 | 73.59 | 0.00748074 | 16.2 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5973.831 | 4782.804 | 216.142569 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2438 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 216.142569 | 0.26579592 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 5961.23 | 5481.81 | 1.0021 | 0.26579592 | 216.142569 | 77.67 | 62.05 | 0.00852342 | 11.3 | 53.60 | 51.97 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 278.171 | 5683.06 | 82.09 | 0.00822799 | 63.13 | 44.99498340 | 20.8173 | 75.00 | 0.00860109 | 75.00 | 0.00859220 | 45.6914 | 4968.82 | 0.00 | 5976.32 | 4732.93 | 0.25529899 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.93 | 57.83 | 0.00995084 | 9.6 | |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 13067.588 | 13067.588 | 216.142569 | 0.17927277 | 180.884 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 216.142569 | 0.26579592 | 1.0027 | 62.4216 | 3.83359033 | 159.80 | 179.60 | 19.80 | 273976.17 | 4.7696 | 4.865598 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 13067.59 | 13067.59 | 1.0000 | 0.26579592 | 216.142569 | 65.10 | 55.49 | 0.00734367 | 8.9 | 122.00 | 74.75 | 0.00800000 | 17.0 | 0.18652708 | 140.00 | 120.20 | 19.80 | 0.000 | 13067.59 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | 20.8173 | 72.00 | 0.00794446 | 72.00 | 0.00880458 | 51.7686 | 1040.02 | 0.00 | 13498.81 | 13498.81 | 0.26579592 | 61.88 | 54.51 | 0.00734367 | 8.4 | 119.87 | 73.82 | 0.00734367 | 16.3 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6594.977 | 5278.597 | 237.789455 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2438 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 237.789455 | 0.29241564 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:20:00 | Sensible | 6642.53 | 6178.02 | 0.9928 | 0.29241564 | 237.789455 | 77.84 | 62.01 | 0.00845279 | 11.3 | 53.60 | 51.97 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 306.031 | 6336.50 | 83.69 | 0.00822939 | 63.67 | 44.99498340 | 18.9222 | 75.00 | 0.00850493 | 75.00 | 0.00847466 | 45.0745 | 5474.47 | 0.00 | 6597.73 | 5223.60 | 0.28086743 | 80.00 | 67.00 | 0.01118466 | 13.2 | 58.86 | 57.80 | 0.00994524 | 9.6 | |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 14217.610 | 14217.610 | 237.789455 | 0.19504980 | 197.570 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 237.789455 | 0.29241564 | 1.0027 | 62.4216 | 3.83359033 | 159.80 | 179.60 | 19.80 | 273976.17 | 5.1894 | 5.293798 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 14217.61 | 14217.61 | 1.0000 | 0.29241564 | 237.789455 | 65.73 | 55.68 | 0.00730612 | 8.9 | 122.00 | 74.75 | 0.00800000 | 17.0 | 0.20294252 | 140.00 | 120.20 | 19.80 | 0.000 | 14217.61 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | 18.9222 | 72.00 | 0.00783069 | 72.00 | 0.00783069 | 46.1151 | 3106.49 | 0.00 | 14767.90 | 14767.90 | 0.29241564 | 61.88 | 54.45 | 0.00730612 | 8.4 | 119.55 | 73.69 | 0.00730612 | 16.2 | |
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | HEATEDBSMT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5404.248 | 3905.169 | 144.798852 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2437 | 0.2400 | 0.0738 | SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 144.798852 | 0.17806277 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 5313.07 | 5172.34 | 1.0172 | 0.17806277 | 144.798852 | 89.53 | 65.59 | 0.00823349 | 12.7 | 53.60 | 51.97 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 186.353 | 5126.72 | 88.34 | 0.00823349 | 65.21 | 44.99498340 | 31.0741 | 75.00 | 0.00822186 | 74.44 | 0.00822186 | 44.5663 | 0.00 | 0.00 | 5406.50 | 3871.17 | 0.17103063 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.23 | 54.18 | 0.00891049 | 8.3 | |
MAIN WATER HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | HEATEDBSMT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 9277.527 | 9277.527 | 144.798852 | 0.12727735 | 125.828 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 144.798852 | 0.17806277 | 1.0027 | 62.4216 | 3.83359033 | 159.80 | 179.60 | 19.80 | 273976.17 | 3.3863 | 3.454403 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:10:00 | Sensible | 9277.53 | 9277.53 | 1.0000 | 0.17806277 | 144.798852 | 61.70 | 53.67 | 0.00708593 | 8.2 | 122.00 | 74.75 | 0.00800000 | 17.0 | 0.13242765 | 140.00 | 120.20 | 19.80 | 0.000 | 9277.53 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | 31.0741 | 72.00 | 0.00800000 | 72.00 | 0.00800000 | 47.0989 | 7805.98 | 0.00 | 9306.15 | 9306.15 | 0.17806277 | 61.88 | 54.05 | 0.00708593 | 8.3 | 121.59 | 73.98 | 0.00708593 | 16.3 |
Report: System Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2375.67 | 4634.00 | 414.17 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1884.17 | 4281.50 | 320.50 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2184.00 | 4454.17 | 357.50 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2076.83 | 5321.50 | 427.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1664.83 | 5204.00 | 335.33 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1891.17 | 5264.17 | 362.17 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2799.83 | 3247.50 | 115.83 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2401.00 | 2584.33 | 9.33 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2721.67 | 2954.33 | 93.17 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2363.00 | 4050.50 | 118.50 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1964.17 | 3726.83 | 10.33 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2254.33 | 3897.67 | 97.17 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 2475.17 | 4300.00 | 191.33 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 2806.00 | 3568.33 | 192.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 2826.33 | 3861.00 | 240.33 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 2248.50 | 4101.17 | 103.83 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 2558.17 | 3257.83 | 108.83 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 2520.83 | 4457.50 | 247.33 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 3432.17 | 5833.83 | 476.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.33 | 16.67 | 0.33 | 16.67 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 13.00 | 46.67 | 13.00 | 46.67 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 402.33 | 48.67 | 402.33 | 48.67 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 285.17 | 0.67 | 285.17 | 0.67 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 42.50 | 0.67 | 42.50 | 0.67 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 459.00 | 15.00 | 459.00 | 15.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8.33 | 13.17 | 8.33 | 13.17 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.17 | 46.00 | 1.17 | 46.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 275.33 | 51.50 | 275.33 | 51.50 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 158.17 | 0.00 | 158.17 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 6.33 | 0.00 | 6.33 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 350.17 | 11.17 | 350.17 | 11.17 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 320.33 | 15.33 | 320.33 | 15.33 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 307.83 | 42.83 | 307.83 | 42.83 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 123.33 | 9.83 | 123.33 | 9.83 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 9.67 | 0.67 | 9.67 | 0.67 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 6.83 | 32.67 | 6.83 | 32.67 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 226.67 | 0.83 | 226.67 | 0.83 |
HEATEDBSMT | 3231.17 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 3264.50 | 60.83 | 1321.00 | 60.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.088 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.078 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.088 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.088 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.077 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.088 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.039 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.271 | 0.028 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.039 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.039 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.271 | 0.028 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.039 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.088 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.089 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.089 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.078 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.078 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.088 | 0.000 | 0.000 |
HEATEDBSMT | 58539.52 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.263 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.263 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.263 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.263 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.263 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.263 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.264 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.263 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.263 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.263 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.263 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.263 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.263 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.263 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.263 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.263 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
HEATEDBSMT | 58539.52 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Zone Area [ft2] | Design Zone Outdoor Airflow - Voz [ft3/min] | Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 58539.52 | 7794.39 | 0.0000 | 0.000 | |
Total Facility | 24.79 | 36.00 | 242278.90 | 29404.35 | 0.0000 | 0.000 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3] | Total Ventilation [ft3] | Infiltration [ft3] | Total Ventilation and Infiltration [ft3] | Dynamic Target Ventilation - Voz-dyn [ft3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 7765816.58 | 31550898.27 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 6860872.36 | 30645954.05 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 7772477.11 | 31557558.80 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 7728925.45 | 31514007.14 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 6821142.73 | 30606224.42 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 7736521.58 | 31521603.26 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 3427063.59 | 27212145.28 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 2502948.25 | 26288029.94 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 3429566.32 | 27214648.01 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 3414083.03 | 27199164.72 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 2491871.23 | 26276952.91 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 3418147.72 | 27203229.41 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 7786472.86 | 31571554.55 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 7811146.51 | 31596228.20 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 7800058.58 | 31585140.27 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 6871387.38 | 30656469.07 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 6898858.24 | 30683939.93 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 7774302.85 | 31559384.54 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
HEATEDBSMT | 23785081.69 | 0.00 | 23785081.69 | 0.00 | 23785081.69 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 8808.00 |
Total Facility | 0.451917E+09 | 0.00 | 0.451917E+09 | 0.108312E+09 | 0.560228E+09 | 0.451917E+09 | 0.00 | 8808.00 | 0.00 | 8808.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Infiltration [ft3/min] | Total Ventilation and Infiltration [ft3/min] | Dynamic Target Ventilation - Voz-dyn [ft3/min] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 14.6908 | 59.6858 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 12.9789 | 57.9739 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 14.7034 | 59.6984 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 14.6211 | 59.6160 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 12.9038 | 57.8988 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 14.6354 | 59.6304 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 6.4831 | 51.4781 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 4.7349 | 49.7299 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 6.4878 | 51.4828 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 6.4585 | 51.4535 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 4.7140 | 49.7089 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 6.4662 | 51.4612 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 14.7299 | 59.7249 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 14.7766 | 59.7716 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 14.7556 | 59.7506 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 12.9988 | 57.9938 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 13.0508 | 58.0458 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 14.7069 | 59.7019 | 44.9950 | 0.00 | 8808.00 | 0.00 |
Total Facility | 809.9097 | 0.0000 | 809.9097 | 204.8966 | 1014.8063 | 809.9097 | 0.00 | 8808.00 | 0.00 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [ft3/min] | Limits and Scheduled Limits [ft3/min] | Economizer [ft3/min] | Exhaust Flow [ft3/min] | Mixed Air Flow [ft3/min] | High Humidity [ft3/min] | Demand Controlled Ventilation [ft3/min] | Night Ventilation [ft3/min] | Demand Limiting [ft3/min] | Energy Management System [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 54 |
Floor | 29 | 3 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 60 | 60 |
Overhang | 30 | 30 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 19 |
Conditioned Zones | 19 |
Unconditioned Zones | 2 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 2039 |
Defaulted Fields | 1583 |
Fields with Defaults | 6565 |
Autosized Fields | 380 |
Autosizable Fields | 644 |
Autocalculated Fields | 162 |
Autocalculatable Fields | 350 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 127303.03 | 8175.53 | 05-JUN-03:10 | 29106.53 | 29-SEP-19:00 |
Electricity:Building | 100764.00 | 6307.12 | 02-JAN-03:10 | 19198.06 | 01-JAN-18:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity | 12960.20 | 290.23 | 01-JAN-00:10 | 4221.57 | 01-JAN-19:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
General:InteriorLights:Electricity | 12960.20 | 290.23 | 01-JAN-00:10 | 4221.57 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
InteriorEquipment:Electricity | 87803.80 | 5989.14 | 02-JAN-04:10 | 15388.75 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity | 2758.31 | 25.25 | 02-JAN-03:10 | 880.12 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:10 | 1639.04 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity | 1408.53 | 13.53 | 02-JAN-02:10 | 381.47 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:10 | 3196.73 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:10 | 3721.08 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:10 | 7929.96 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:10 | 526.17 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
Fans:Electricity | 8996.87 | 610.71 | 04-JUN-04:30 | 2271.08 | 29-SEP-15:20 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 127303.03 | 8175.53 | 05-JUN-03:10 | 29106.53 | 29-SEP-19:00 |
ElectricityPurchased:Plant | 127303.03 | 8175.53 | 05-JUN-03:10 | 29106.53 | 29-SEP-19:00 |
Cogeneration:ElectricityPurchased | 127303.03 | 8175.53 | 05-JUN-03:10 | 29106.53 | 29-SEP-19:00 |
General:Cogeneration:ElectricityPurchased | 127303.03 | 8175.53 | 05-JUN-03:10 | 29106.53 | 29-SEP-19:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 127303.03 | 8175.53 | 05-JUN-03:10 | 29106.53 | 29-SEP-19:00 |
ElectricityNet:Plant | 127303.03 | 8175.53 | 05-JUN-03:10 | 29106.53 | 29-SEP-19:00 |
Cogeneration:ElectricityNet | 127303.03 | 8175.53 | 05-JUN-03:10 | 29106.53 | 29-SEP-19:00 |
General:Cogeneration:ElectricityNet | 127303.03 | 8175.53 | 05-JUN-03:10 | 29106.53 | 29-SEP-19:00 |
Electricity:HVAC | 21030.32 | 610.71 | 04-JUN-04:30 | 10487.42 | 29-SEP-15:20 |
HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Fans:Electricity | 3647.01 | 0.00 | 04-JUN-04:30 | 1660.37 | 29-SEP-15:20 |
Ventilation:Fans:Electricity | 5349.86 | 610.71 | 01-JAN-00:10 | 610.71 | 04-JAN-09:10 |
ExteriorLights:Electricity | 5508.71 | 0.00 | 01-JAN-06:10 | 1257.69 | 01-JAN-00:10 |
Exterior-Lights:ExteriorLights:Electricity | 5508.71 | 0.00 | 01-JAN-06:10 | 1257.69 | 01-JAN-00:10 |
Garage-Lights:ExteriorLights:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 12033.45 | 0.00 | 01-JAN-00:10 | 8217.28 | 29-SEP-14:50 |
General:Cooling:Electricity | 12033.45 | 0.00 | 01-JAN-00:10 | 8217.28 | 29-SEP-14:50 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Natural Gas Annual Value [therm] | Natural Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2493.09 | 0.00 | 01-JAN-12:50 | 252343.46 | 01-JAN-06:40 |
NaturalGas:Plant | 2493.09 | 0.00 | 01-JAN-12:50 | 252343.46 | 01-JAN-06:40 |
Heating:NaturalGas | 264.62 | 0.00 | 01-JAN-12:50 | 76877.27 | 03-JAN-04:20 |
Boiler:Heating:NaturalGas | 264.62 | 0.00 | 01-JAN-12:50 | 76877.27 | 03-JAN-04:20 |
WaterSystems:NaturalGas | 2228.47 | 0.00 | 01-JAN-00:10 | 219996.43 | 01-JAN-08:30 |
Water Heater:WaterSystems:NaturalGas | 2228.47 | 0.00 | 01-JAN-00:10 | 219996.43 | 01-JAN-08:30 |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Water:Plant | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
WaterSystems:Water | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Domestic Hot Water:WaterSystems:Water | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
MainsWater:Facility | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
MainsWater:Plant | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
WaterSystems:MainsWater | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Domestic Hot Water:WaterSystems:MainsWater | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 609827.88 | 8586.80 | 18-DEC-03:00 | 226504.45 | 29-SEP-17:10 |
EnergyTransfer:Building | 255949.92 | 2885.03 | 15-JAN-09:10 | 98304.49 | 29-SEP-17:10 |
EnergyTransfer:Zone:HEATEDBSMT | 9818.16 | 0.05 | 02-OCT-13:30 | 5015.50 | 14-JAN-10:50 |
Heating:EnergyTransfer | 13351.24 | 0.00 | 01-JAN-12:50 | 33764.73 | 03-JAN-04:10 |
Heating:EnergyTransfer:Zone:HEATEDBSMT | 7391.58 | 0.00 | 01-JAN-00:30 | 5015.50 | 14-JAN-10:50 |
General:Heating:EnergyTransfer | 13351.24 | 0.00 | 01-JAN-12:50 | 33764.73 | 03-JAN-04:10 |
Cooling:EnergyTransfer | 242598.68 | 0.00 | 03-JAN-04:20 | 98304.49 | 29-SEP-17:10 |
Cooling:EnergyTransfer:Zone:HEATEDBSMT | 2426.58 | 0.00 | 01-JAN-00:10 | 1221.22 | 14-OCT-14:00 |
General:Cooling:EnergyTransfer | 242598.68 | 0.00 | 03-JAN-04:20 | 98304.49 | 29-SEP-17:10 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 13318.92 | 0.89 | 29-NOV-03:50 | 7184.75 | 17-OCT-16:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 447.97 | 0.00 | 01-JAN-09:30 | 1790.95 | 30-MAR-04:50 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 12870.95 | 0.00 | 01-JAN-00:10 | 7184.75 | 17-OCT-16:10 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 11011.67 | 0.13 | 28-JAN-01:20 | 4379.54 | 14-OCT-18:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 173.36 | 0.00 | 01-JAN-00:10 | 1228.09 | 08-MAR-01:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 10838.31 | 0.00 | 01-JAN-02:40 | 4379.54 | 14-OCT-18:50 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12864.73 | 3.08 | 22-APR-11:40 | 5129.35 | 16-OCT-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 531.65 | 0.00 | 01-JAN-00:10 | 2717.61 | 24-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12333.08 | 0.00 | 01-JAN-02:40 | 5129.35 | 16-OCT-17:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 10980.23 | 0.25 | 23-NOV-05:40 | 6145.57 | 29-SEP-16:40 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 654.05 | 0.00 | 01-JAN-07:10 | 3191.52 | 13-DEC-07:50 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 10326.18 | 0.00 | 01-JAN-00:10 | 6145.57 | 29-SEP-16:40 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8657.05 | 0.90 | 27-NOV-12:40 | 3351.11 | 29-SEP-18:20 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 288.77 | 0.00 | 01-JAN-00:50 | 1718.81 | 30-MAR-07:20 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8368.29 | 0.00 | 01-JAN-00:10 | 3351.11 | 29-SEP-18:20 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 10380.07 | 1.66 | 17-DEC-12:10 | 4295.77 | 30-SEP-09:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 663.89 | 0.00 | 01-JAN-02:40 | 2667.79 | 20-DEC-05:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 9716.18 | 0.00 | 01-JAN-00:10 | 4295.77 | 30-SEP-09:00 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 17659.77 | 0.41 | 06-FEB-07:00 | 7971.57 | 17-OCT-16:20 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 142.63 | 0.00 | 01-JAN-00:10 | 1931.00 | 30-MAR-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 17517.14 | 0.00 | 01-JAN-02:10 | 7971.57 | 17-OCT-16:20 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 15543.61 | 2.32 | 29-MAR-08:20 | 5082.76 | 14-OCT-19:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 24.37 | 0.00 | 01-JAN-00:10 | 1433.29 | 30-MAR-02:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 15519.24 | 0.00 | 03-JAN-04:20 | 5082.76 | 14-OCT-19:00 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 17089.93 | 74.83 | 29-MAR-11:50 | 6112.45 | 16-OCT-18:40 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 127.36 | 0.00 | 01-JAN-00:10 | 3232.55 | 03-JAN-02:20 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 16962.57 | 0.00 | 03-JAN-04:20 | 6112.45 | 16-OCT-18:40 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 14170.30 | 1.23 | 01-FEB-09:20 | 6803.32 | 29-SEP-16:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 238.27 | 0.00 | 01-JAN-00:10 | 2486.30 | 11-JAN-07:40 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 13932.02 | 0.00 | 01-JAN-01:00 | 6803.32 | 29-SEP-16:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 11900.20 | 0.62 | 27-NOV-12:10 | 3954.99 | 29-SEP-19:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 77.85 | 0.00 | 01-JAN-00:10 | 1437.71 | 03-JAN-02:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 11822.35 | 0.00 | 01-JAN-05:30 | 3954.99 | 29-SEP-19:30 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 13525.19 | 9.53 | 13-JAN-11:30 | 4959.17 | 29-SEP-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 237.84 | 0.00 | 01-JAN-00:10 | 3020.11 | 03-JAN-02:20 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 13287.36 | 0.00 | 01-JAN-05:30 | 4959.17 | 29-SEP-17:30 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 13906.06 | 0.28 | 27-FEB-15:50 | 5884.45 | 29-SEP-18:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 563.90 | 0.00 | 01-JAN-00:10 | 3672.17 | 03-JAN-02:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 13342.17 | 0.00 | 01-JAN-02:40 | 5884.45 | 29-SEP-18:00 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 16484.61 | 7.15 | 13-DEC-08:00 | 6727.44 | 16-OCT-18:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 420.49 | 0.00 | 01-JAN-00:10 | 3768.72 | 03-JAN-02:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 16064.12 | 0.00 | 01-JAN-04:50 | 6727.44 | 16-OCT-18:30 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 17123.67 | 0.18 | 24-DEC-03:20 | 8600.53 | 15-OCT-16:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 409.60 | 0.00 | 01-JAN-00:10 | 3461.85 | 03-JAN-04:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 16714.07 | 0.00 | 01-JAN-01:00 | 8600.53 | 15-OCT-16:50 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 12129.05 | 0.18 | 22-FEB-04:50 | 5187.87 | 29-SEP-18:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 245.18 | 0.00 | 01-JAN-00:10 | 2099.93 | 28-JAN-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 11883.87 | 0.00 | 01-JAN-02:40 | 5187.87 | 29-SEP-18:00 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 14783.66 | 0.46 | 26-MAR-03:40 | 5916.22 | 14-OCT-18:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 133.04 | 0.00 | 01-JAN-00:10 | 1675.80 | 03-JAN-03:20 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 14650.62 | 0.00 | 01-JAN-04:50 | 5916.22 | 14-OCT-18:50 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 14603.04 | 0.26 | 11-FEB-01:20 | 8103.07 | 29-SEP-16:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 579.46 | 0.00 | 01-JAN-01:40 | 3248.54 | 13-DEC-08:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 14023.59 | 0.00 | 01-JAN-00:10 | 8103.07 | 29-SEP-16:50 |
EnergyTransfer:HVAC | 219510.04 | 0.00 | 01-JAN-12:50 | 114965.00 | 29-SEP-16:30 |
HeatRecoveryForHeating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRecoveryForCooling:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatingCoils:EnergyTransfer | 20799.96 | 0.00 | 01-JAN-12:50 | 60803.39 | 03-JAN-04:20 |
PlantLoopHeatingDemand:Facility | 133998.21 | 1109.13 | 04-AUG-03:00 | 79473.53 | 08-JAN-06:50 |
PlantLoopHeatingDemand:HVAC | 20799.96 | 0.00 | 01-JAN-12:50 | 60803.39 | 03-JAN-04:20 |
HeatingCoils:PlantLoopHeatingDemand | 20799.96 | 0.00 | 01-JAN-12:50 | 60803.39 | 03-JAN-04:20 |
CoolingCoils:EnergyTransfer | 198710.08 | 0.00 | 01-JAN-00:10 | 114965.00 | 29-SEP-16:30 |
EnergyTransfer:Plant | 134367.92 | 1109.13 | 04-AUG-03:00 | 81397.38 | 08-JAN-06:50 |
Boilers:EnergyTransfer | 21169.68 | 0.00 | 01-JAN-12:50 | 61501.81 | 03-JAN-04:20 |
WaterSystems:EnergyTransfer | 113198.24 | 1109.13 | 04-AUG-03:00 | 26695.95 | 04-FEB-08:50 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 113198.24 | 1109.13 | 04-AUG-03:00 | 26695.95 | 04-FEB-08:50 |
PlantLoopHeatingDemand:Plant | 113198.24 | 1109.13 | 04-AUG-03:00 | 26695.95 | 04-FEB-08:50 |
WaterSystems:PlantLoopHeatingDemand | 113198.24 | 1109.13 | 04-AUG-03:00 | 26695.95 | 04-FEB-08:50 |
General:WaterSystems:PlantLoopHeatingDemand | 113198.24 | 1109.13 | 04-AUG-03:00 | 26695.95 | 04-FEB-08:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 87.905 | -437.01 | 1374.814 | -719.36 | 0.000 | 0.000 | 2985.001 | 2458.419 | 10401.374 | 9216.950 | 0.000 | 22.431 | 0.000 | 0.000 | -4074.70 | 0.000 | -1916.71 | -6669.82 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 85.041 | -442.80 | 566.671 | -499.62 | 0.000 | 0.000 | 2963.194 | 2458.419 | 10401.374 | 4060.177 | 0.000 | 18.704 | 0.016 | 0.000 | -1675.48 | 0.000 | -1713.61 | -5847.81 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 83.956 | -438.32 | 1101.268 | -643.18 | 0.000 | 0.000 | 2987.791 | 2458.419 | 10401.374 | 8593.060 | 0.000 | 20.667 | 0.181 | 0.000 | -3996.65 | 0.000 | -1920.44 | -6742.75 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 90.454 | -428.71 | 1590.468 | -516.74 | 0.000 | 0.000 | 3002.536 | 2458.419 | 10401.374 | 6270.980 | 0.000 | 22.989 | 0.000 | 0.000 | -4095.76 | 0.000 | -1873.00 | -6515.43 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 90.030 | -432.17 | 861.000 | -319.88 | 0.000 | 0.000 | 2985.950 | 2458.419 | 10401.374 | 1010.970 | 0.000 | 20.181 | 0.000 | 0.000 | -1690.23 | 0.000 | -1663.80 | -5443.33 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 87.968 | -429.76 | 1385.398 | -446.80 | 0.000 | 0.000 | 3007.493 | 2458.419 | 10401.374 | 5579.720 | 0.000 | 22.414 | 0.000 | 0.000 | -3941.99 | 0.000 | -1874.26 | -6600.85 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 88.100 | -449.60 | 459.483 | -1042.91 | 0.000 | 0.000 | 2939.779 | 2458.419 | 10401.374 | 9079.177 | 0.000 | 9.795 | 0.035 | 0.000 | -4308.14 | 0.000 | -872.06 | -2333.85 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 85.567 | -457.76 | 89.949 | -847.24 | 0.000 | 0.000 | 2911.079 | 2458.419 | 10401.374 | 3999.173 | 0.000 | 6.813 | 0.014 | 0.000 | -1773.64 | 0.000 | -648.74 | -1859.57 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 83.961 | -450.93 | 308.341 | -983.75 | 0.000 | 0.000 | 2941.007 | 2458.419 | 10401.374 | 8461.822 | 0.000 | 9.025 | 0.125 | 0.000 | -4223.78 | 0.000 | -873.84 | -2338.75 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 89.723 | -442.89 | 650.794 | -759.17 | 0.000 | 0.000 | 2953.988 | 2458.419 | 10401.374 | 6155.590 | 0.000 | 9.956 | 0.012 | 0.000 | -4325.98 | 0.000 | -856.22 | -3103.39 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 89.266 | -449.37 | 234.612 | -555.66 | 0.000 | 0.000 | 2929.864 | 2458.419 | 10401.374 | 970.676 | 0.000 | 7.222 | 0.003 | 0.000 | -1788.48 | 0.000 | -633.82 | -2600.74 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 88.095 | -444.47 | 513.100 | -692.33 | 0.000 | 0.000 | 2958.524 | 2458.419 | 10401.374 | 5463.902 | 0.000 | 9.779 | 0.206 | 0.000 | -4163.17 | 0.000 | -857.72 | -3221.55 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 87.951 | -439.04 | 1137.824 | -727.19 | 0.000 | 0.000 | 2974.560 | 2458.419 | 10401.374 | 5471.976 | 0.000 | 22.090 | 0.017 | 0.000 | -4154.88 | 0.000 | -1936.38 | -2458.84 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 85.030 | -444.91 | 839.047 | -934.82 | 0.000 | 0.000 | 2960.792 | 2458.419 | 10401.374 | 8473.986 | 0.000 | 20.911 | 0.132 | 0.000 | -4194.29 | 0.000 | -1968.35 | -2509.15 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 88.344 | -442.62 | 1006.404 | -1006.35 | 0.000 | 0.000 | 2960.910 | 2458.419 | 10401.374 | 9080.424 | 0.000 | 22.268 | 0.131 | 0.000 | -4266.53 | 0.000 | -1959.67 | -2392.75 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 89.985 | -443.31 | 705.029 | -592.14 | 0.000 | 0.000 | 2948.630 | 2458.419 | 10401.374 | 972.241 | 0.000 | 19.880 | 0.013 | 0.000 | -1780.04 | 0.000 | -1728.47 | -1653.32 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 86.686 | -450.67 | 401.397 | -798.97 | 0.000 | 0.000 | 2933.116 | 2458.419 | 10401.374 | 4001.334 | 0.000 | 19.069 | 0.076 | 0.000 | -1759.47 | 0.000 | -1763.51 | -1772.72 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 90.811 | -436.89 | 1356.524 | -803.24 | 0.000 | 0.000 | 2971.934 | 2458.419 | 10401.374 | 6144.216 | 0.000 | 22.685 | 0.000 | 0.000 | -4296.98 | 0.000 | -1929.74 | -2327.81 |
HEATEDBSMT | 136.681 | -361.57 | 9190.076 | -1.67 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -4964.99 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 25896.837 | 196969.604 | 0.000 | 0.000 | 0.000 | -222866.44 | -0.98 |
Total Facility | 1715.554 | -8322.77 | 23772.200 | -12891.00 | 0.000 | 0.000 | 53316.147 | 44251.534 | 187224.736 | 103006.375 | 0.000 | 26203.717 | 196970.566 | 0.000 | -60510.20 | 0.000 | -249856.77 | -71358.40 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 17-OCT-16:12 | 0.00 | 0.02 | 0.00 | -0.6 | 0.00 | 0.00 | 139.74 | 385.11 | 1343.44 | 4287.93 | 0.00 | 38.58 | 1145.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 14-OCT-18:53 | 0.00 | -0.0 | 0.00 | -0.4 | 0.00 | 0.00 | 426.22 | 722.08 | 1734.73 | 0.00 | 0.00 | 0.00 | 1747.13 | 0.00 | -191.5 | 0.00 | -17.2 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 16-OCT-17:37 | 0.00 | 0.01 | 0.00 | -0.4 | 0.00 | 0.00 | 261.64 | 536.40 | 1655.83 | 0.00 | 0.00 | 13.10 | 2968.90 | 0.00 | -248.8 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 29-SEP-16:35 | 0.00 | 0.05 | 0.00 | -0.6 | 0.00 | 0.00 | 139.52 | 385.11 | 1343.44 | 3316.20 | 0.00 | 177.04 | 813.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 29-SEP-18:20 | 0.00 | 0.03 | 0.00 | -0.3 | 0.00 | 0.00 | 426.76 | 722.08 | 1713.00 | 1.11 | 0.00 | 51.38 | 437.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 30-SEP-08:57 | 0.00 | 0.03 | 0.00 | -0.4 | 0.00 | 0.00 | 194.42 | 151.29 | 1167.53 | 4293.17 | 0.00 | 73.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1582.5 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 17-OCT-16:22 | 0.00 | 0.01 | 0.00 | -0.7 | 0.00 | 0.00 | 140.35 | 385.11 | 1343.44 | 3828.68 | 0.00 | 8.84 | 2516.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 14-OCT-18:53 | 0.00 | -0.0 | 0.00 | -0.4 | 0.00 | 0.00 | 418.41 | 722.08 | 1734.73 | 0.00 | 0.00 | 0.00 | 2431.33 | 0.00 | -207.9 | 0.00 | -7.7 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 15-OCT-17:53 | 0.00 | -0.0 | 0.00 | -0.5 | 0.00 | 0.00 | 261.88 | 536.40 | 1675.86 | 0.00 | 0.00 | 0.00 | 4137.62 | 0.00 | -465.8 | 0.00 | -3.2 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 29-SEP-16:25 | 0.00 | 0.06 | 0.00 | -0.6 | 0.00 | 0.00 | 139.96 | 385.11 | 1343.44 | 3729.01 | 0.00 | 84.75 | 1125.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 29-SEP-19:35 | 0.00 | 0.02 | 0.00 | -0.4 | 0.00 | 0.00 | 426.17 | 800.22 | 1650.38 | 0.00 | 0.00 | 8.69 | 1159.94 | 0.00 | -63.4 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 29-SEP-17:33 | 0.00 | 0.03 | 0.00 | -0.5 | 0.00 | 0.00 | 262.57 | 536.40 | 1655.83 | 12.73 | 0.00 | 33.74 | 2498.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 29-SEP-17:53 | 0.00 | 0.02 | 0.00 | -0.5 | 0.00 | 0.00 | 254.77 | 536.40 | 1655.83 | 0.00 | 0.00 | 39.93 | 3544.80 | 0.00 | -129.1 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 15-OCT-17:53 | 0.00 | -0.0 | 0.00 | -0.6 | 0.00 | 0.00 | 263.05 | 536.40 | 1675.86 | 0.00 | 0.00 | 0.00 | 4781.20 | 0.00 | -479.2 | 0.00 | -6.7 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 15-OCT-16:50 | 0.00 | 0.03 | 0.00 | -0.7 | 0.00 | 0.00 | 138.65 | 385.11 | 1363.24 | 2634.68 | 0.00 | 77.63 | 4006.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 29-SEP-17:53 | 0.00 | 0.03 | 0.00 | -0.5 | 0.00 | 0.00 | 262.57 | 536.40 | 1655.83 | 0.00 | 0.00 | 42.80 | 2735.58 | 0.00 | -29.5 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 14-OCT-18:53 | 0.00 | -0.0 | 0.00 | -0.5 | 0.00 | 0.00 | 426.33 | 722.08 | 1734.73 | 0.00 | 0.00 | 0.00 | 3307.60 | 0.00 | -210.2 | 0.00 | -17.5 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 29-SEP-16:43 | 0.00 | 0.05 | 0.00 | -0.7 | 0.00 | 0.00 | 139.33 | 385.11 | 1343.44 | 2822.99 | 0.00 | 158.76 | 3265.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 29-SEP-15:05 | 0.00 | 0.07 | 0.00 | -0.2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1833.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-SEP-17:07 | 0.00 | 0.80 | 0.00 | -9.0 | 0.00 | 0.00 | 4573.15 | 9655.18 | 29804.87 | 14398.82 | 0.00 | 1593.58 | 59682.13 | 0.00 | 0.00 | 0.00 | -21283.9 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 31-MAR-01:23 | -1314.7 | 0.00 | 3956.22 | 0.00 | 0.00 | 0.00 | 534.03 | 55.02 | 890.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1360.4 | 0.00 | -589.7 | -2170.7 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 29-JAN-03:23 | -1144.5 | 0.00 | 4040.75 | 0.00 | 0.00 | 0.00 | 536.10 | 55.02 | 847.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -436.8 | 0.00 | -366.4 | -3532.0 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 24-DEC-03:55 | -1443.8 | 0.00 | 6878.99 | 0.00 | 0.00 | 0.00 | 541.89 | 55.02 | 847.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1306.1 | 0.00 | -579.6 | -4994.3 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 03-JAN-08:13 | -1131.8 | 0.00 | 8588.14 | 0.00 | 0.00 | 0.00 | 222.13 | 151.29 | 1145.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -699.9 | 0.00 | -437.5 | -7837.6 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 29-MAR-17:40 | -1135.1 | 0.00 | 5364.77 | 0.00 | 0.00 | 0.00 | 299.89 | 536.40 | 1655.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -437.0 | 0.00 | -358.1 | -5926.7 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 08-JAN-03:55 | -1530.0 | 0.00 | 6455.57 | 0.00 | 0.00 | 0.00 | 535.00 | 55.02 | 847.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1529.4 | 0.00 | -665.8 | -4168.3 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 08-MAR-08:10 | -1037.1 | 0.00 | 7059.68 | 0.00 | 0.00 | 0.00 | 219.21 | 151.29 | 1145.20 | 500.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -195.6 | -7843.0 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 30-MAR-02:25 | -1518.1 | 0.00 | 4384.76 | 0.00 | 0.00 | 0.00 | 536.07 | 55.02 | 865.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -627.1 | 0.00 | -249.6 | -3446.7 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 03-JAN-02:20 | -1538.5 | 0.00 | 8003.36 | 0.00 | 0.00 | 0.00 | 556.86 | 55.02 | 865.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1599.3 | 0.00 | -335.3 | -6007.9 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 03-JAN-08:18 | -1142.6 | 0.00 | 9289.04 | 0.00 | 0.00 | 0.00 | 218.26 | 151.29 | 1145.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -714.5 | 0.00 | -193.8 | -8752.8 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 08-JAN-07:57 | -1354.6 | 0.00 | 5496.62 | 0.00 | 0.00 | 0.00 | 471.41 | 343.85 | 1218.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -420.3 | 0.00 | -178.5 | -5577.2 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 03-JAN-02:15 | -1556.4 | 0.00 | 7596.66 | 0.00 | 0.00 | 0.00 | 543.52 | 55.02 | 865.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1587.0 | 0.00 | -342.2 | -5575.4 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 03-JAN-02:00 | -1610.3 | 0.00 | 8954.34 | 0.00 | 0.00 | 0.00 | 530.63 | 55.02 | 890.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1648.9 | 0.00 | -820.4 | -6350.6 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 03-JAN-02:10 | -1584.5 | 0.00 | 9121.65 | 0.00 | 0.00 | 0.00 | 535.55 | 55.02 | 865.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1642.7 | 0.00 | -800.1 | -6550.7 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 08-MAR-07:33 | -1176.5 | 0.00 | 9587.10 | 0.00 | 0.00 | 0.00 | 482.42 | 343.85 | 1204.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -69.9 | 0.00 | -529.0 | -9842.4 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 03-DEC-08:17 | -976.7 | 0.00 | 5254.73 | 0.00 | 0.00 | 0.00 | 217.29 | 151.29 | 1167.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -190.9 | 0.00 | -332.4 | -5290.8 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 08-MAR-07:23 | -1226.1 | 0.00 | 5317.89 | 0.00 | 0.00 | 0.00 | 471.69 | 343.85 | 1204.45 | 190.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -490.4 | -5811.7 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 03-JAN-08:23 | -1091.2 | 0.00 | 10182.23 | 0.00 | 0.00 | 0.00 | 220.00 | 151.29 | 1145.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -586.7 | 0.00 | -417.0 | -9603.8 |
HEATEDBSMT | 14-JAN-10:40 | 368.14 | 0.00 | 4756.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5124.6 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-JAN-04:10 | -29193.5 | 0.00 | 70098.54 | 0.00 | 0.00 | 0.00 | 9492.78 | 2970.83 | 14958.72 | 0.00 | 0.00 | 5682.46 | 0.00 | 0.00 | -22790.4 | 0.00 | -10561.3 | -40658.1 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 292.9182 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 292.9182 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 156.1057 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 156.1057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 208.4856 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 208.4856 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 275.2134 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 275.2134 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 144.8290 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 144.8290 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 196.7792 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 196.7792 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 323.7248 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 323.7248 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 181.0040 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 181.0040 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 234.9898 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 234.9898 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 304.0824 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 304.0824 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 167.7881 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 167.7881 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 220.3318 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 220.3318 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 361.4569 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 361.4569 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 218.7710 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 218.7710 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 246.9427 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 246.9427 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 356.4499 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 356.4499 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 216.1426 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 216.1426 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 237.7895 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 237.7895 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNITHEATEDBSMT | 144.7989 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 144.7989 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 292.9182 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 292.9182 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 156.1057 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 156.1057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 208.4856 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 208.4856 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 275.2134 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 275.2134 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 144.8290 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 144.8290 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 196.7792 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 196.7792 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 323.7248 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 323.7248 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 181.0040 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 181.0040 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 234.9898 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 234.9898 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 304.0824 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 304.0824 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 167.7881 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 167.7881 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 220.3318 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 220.3318 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 361.4569 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 361.4569 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 218.7710 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 218.7710 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 246.9427 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 246.9427 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 356.4499 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 356.4499 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 216.1426 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 216.1426 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 237.7895 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 237.7895 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNITHEATEDBSMT | 144.7989 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 144.7989 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 0.000000 | 0.0000 | 0.000000 | 7794.39 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.000000 | 7794.3864 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 292.9182 | 292.9182 | 292.9182 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 156.1057 | 156.1057 | 156.1057 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 208.4856 | 208.4856 | 208.4856 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 275.2134 | 275.2134 | 275.2134 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 144.8290 | 144.8290 | 144.8290 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 196.7792 | 196.7792 | 196.7792 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 323.7248 | 323.7248 | 323.7248 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 181.0040 | 181.0040 | 181.0040 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 234.9898 | 234.9898 | 234.9898 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 304.0824 | 304.0824 | 304.0824 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 167.7881 | 167.7881 | 167.7881 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 220.3318 | 220.3318 | 220.3318 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 237.7895 | 237.7895 | 237.7895 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 246.9427 | 246.9427 | 246.9427 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 361.4569 | 361.4569 | 361.4569 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 216.1426 | 216.1426 | 216.1426 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 218.7710 | 218.7710 | 218.7710 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 356.4499 | 356.4499 | 356.4499 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 144.7989 | 144.7989 | 144.7989 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 292.9182 | 292.9182 | 292.9182 | 292.9182 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 156.1057 | 156.1057 | 156.1057 | 156.1057 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 208.4856 | 208.4856 | 208.4856 | 208.4856 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 275.2134 | 275.2134 | 275.2134 | 275.2134 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 144.8290 | 144.8290 | 144.8290 | 144.8290 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 196.7792 | 196.7792 | 196.7792 | 196.7792 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 323.7248 | 323.7248 | 323.7248 | 323.7248 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 181.0040 | 181.0040 | 181.0040 | 181.0040 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 234.9898 | 234.9898 | 234.9898 | 234.9898 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 304.0824 | 304.0824 | 304.0824 | 304.0824 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 167.7881 | 167.7881 | 167.7881 | 167.7881 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 220.3318 | 220.3318 | 220.3318 | 220.3318 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 361.4569 | 361.4569 | 361.4569 | 361.4569 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 218.7710 | 218.7710 | 218.7710 | 218.7710 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 246.9427 | 246.9427 | 246.9427 | 246.9427 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 356.4499 | 356.4499 | 356.4499 | 356.4499 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 216.1426 | 216.1426 | 216.1426 | 216.1426 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 237.7895 | 237.7895 | 237.7895 | 237.7895 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 144.7989 | 144.7989 | 144.7989 | 144.7989 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 292.9182 | 292.9182 | 292.9182 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 156.1057 | 156.1057 | 156.1057 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 208.4856 | 208.4856 | 208.4856 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 275.2134 | 275.2134 | 275.2134 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 144.8290 | 144.8290 | 144.8290 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 196.7792 | 196.7792 | 196.7792 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 323.7248 | 323.7248 | 323.7248 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 181.0040 | 181.0040 | 181.0040 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 234.9898 | 234.9898 | 234.9898 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 304.0824 | 304.0824 | 304.0824 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 167.7881 | 167.7881 | 167.7881 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 220.3318 | 220.3318 | 220.3318 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 237.7895 | 237.7895 | 237.7895 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 246.9427 | 246.9427 | 246.9427 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 361.4569 | 361.4569 | 361.4569 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 216.1426 | 216.1426 | 216.1426 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 218.7710 | 218.7710 | 218.7710 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 356.4499 | 356.4499 | 356.4499 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 144.7989 | 144.7989 | 144.7989 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 292.9182 | 292.9182 | 292.9182 | 292.9182 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 156.1057 | 156.1057 | 156.1057 | 156.1057 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 208.4856 | 208.4856 | 208.4856 | 208.4856 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 275.2134 | 275.2134 | 275.2134 | 275.2134 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 144.8290 | 144.8290 | 144.8290 | 144.8290 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 196.7792 | 196.7792 | 196.7792 | 196.7792 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 323.7248 | 323.7248 | 323.7248 | 323.7248 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 181.0040 | 181.0040 | 181.0040 | 181.0040 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 234.9898 | 234.9898 | 234.9898 | 234.9898 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 304.0824 | 304.0824 | 304.0824 | 304.0824 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 167.7881 | 167.7881 | 167.7881 | 167.7881 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 220.3318 | 220.3318 | 220.3318 | 220.3318 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 361.4569 | 361.4569 | 361.4569 | 361.4569 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 218.7710 | 218.7710 | 218.7710 | 218.7710 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 246.9427 | 246.9427 | 246.9427 | 246.9427 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 356.4499 | 356.4499 | 356.4499 | 356.4499 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 216.1426 | 216.1426 | 216.1426 | 216.1426 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 237.7895 | 237.7895 | 237.7895 | 237.7895 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 144.7989 | 144.7989 | 144.7989 | 144.7989 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [ft2] | 39005.22 |
Principal Heating Source | Natural Gas |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
HEATEDBSMT | 7794.39 | 7794.39 | 0.00 | 0.00 |
BREEZEWAY | 1798.16 | 0.00 | 1798.16 | 0.00 |
ATTIC | 7802.71 | 0.00 | 7802.71 | 0.00 |
Totals | 39005.22 | 29404.35 | 9600.87 |
Data | |
Number of hours heating loads not met | 1321.00 |
Number of hours cooling loads not met | 60.83 |
Number of hours not met | 1381.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [kWh] | Electricity Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Gasoline Use [therm] | Gasoline Demand [Btu/h] | Diesel Use [kBtu] | Diesel Demand [Btu/h] | Coal Use [kBtu] | Coal Demand [Btu/h] | Fuel Oil No 1 Use [kBtu] | Fuel Oil No 1 Demand [Btu/h] | Fuel Oil No 2 Use [kBtu] | Fuel Oil No 2 Demand [Btu/h] | Propane Use [kBtu] | Propane Demand [Btu/h] | Other Fuel 1 Use [kBtu] | Other Fuel 1 Demand [Btu/h] | Other Fuel 2 Use [kBtu] | Other Fuel 2 Demand [Btu/h] | District Cooling Use [ton-hrs] | District Cooling Demand [ton] | District Heating Use [kBtu] | District Heating Demand [Btu/h] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 264.62 | 76877.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 12033.45 | 8217.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- General | 12960.20 | 4221.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Exterior-Lights | 5508.71 | 1257.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- dishwasher | 2758.31 | 880.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- refrigerator | 12036.11 | 1639.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- clotheswasher | 1408.53 | 381.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_dryer | 12502.11 | 3196.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_range | 9058.39 | 3721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_mels | 46926.68 | 7929.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- IECC_adj | 3113.66 | 526.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 3647.01 | 1660.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation | 5349.86 | 610.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 2228.47 | 219996.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 299798.81 | 434665.66 |
Natural Gas | 0.00 | 249308.93 |
Additional | 0.00 | 0.00 |
Total | 299798.81 | 683974.59 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting (All) | 0.33 |
Space Heating | 0.00 |
Space Cooling | 0.31 |
Fans (All) | 0.23 |
Service Water Heating | 0.00 |
Receptacle Equipment | 2.25 |
Miscellaneous (All) | 3.26 |
Subtotal | 3.26 |
Natural Gas [kWh/ft2] | |
Space Heating | 0.20 |
Service Water Heating | 1.67 |
Miscellaneous (All) | 1.87 |
Subtotal | 1.87 |
Additional [kBtu/ft2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.47 |
Space Heating | 3.87 |
Space Cooling | 6.01 |
Fans (All) | 4.49 |
Service Water Heating | 32.58 |
Receptacle Equipment | 43.83 |
Miscellaneous | 2.75 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OCCUPANCY | 6031. | 8760. |
INTERIORLIGHTING | 2852. | 8760. |
INTERIORLIGHTINGHE | 3070. | 8760. |
INTERIORLIGHTINGHE_OS | 2910. | 8760. |
INTERIORLIGHTINGHE_VS | 2149. | 8760. |
EXTERIORLIGHTING | 4380. | 4380. |
REFRIGERATOR | 7343. | 8760. |
MISCPLUGLOAD | 5918. | 8760. |
COOKINGRANGE | 2434. | 8760. |
DHW_SCH | 365. | 8760. |
DISHWASHER | 2799. | 8760. |
CLOTHESWASHER | 3297. | 8760. |
CLOTHESDRYER | 3911. | 8760. |
SINKS | 4179. | 8760. |
SHOWERS | 2640. | 8760. |
BATHS | 2586. | 8760. |
DHWDIST | 4662. | 8760. |
SHADING_2012IECC | 0. | 0. |
SINKSENSSCHEDULE | 6025. | 8760. |
SINKLATSCHEDULE | 2735. | 8760. |
SHOWERSENSSCHEDULE | 4492. | 8760. |
SHOWERLATSCHEDULE | 4268. | 8760. |
BATHSENSSCHEDULE | 8760. | 8760. |
BATHLATSCHEDULE | 0. | 0. |
First Object Used | Month Assumed | 11am First Wednesday [F] | Days with Same 11am Value | 11pm First Wednesday [F] | Days with Same 11pm Value | |
HEATING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | January | 72.00 | 365 | 72.00 | 365 |
COOLING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | July | 75.00 | 365 | 75.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 8175.33 | 560.67 | 24.00 | 0.00 | 0.00 |
ATTIC | 7438.50 | 1071.00 | 247.00 | 3.50 | 0.00 |
Min | 7438.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1071.00 | 247.00 | 3.50 | 0.00 |
Average | 8669.23 | 77.70 | 12.90 | 0.17 | 0.00 |
Sum | 182053.83 | 1631.67 | 271.00 | 3.50 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 7821.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 164250.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8423.33 | 336.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8510.83 | 249.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8471.67 | 288.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8412.33 | 347.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8504.00 | 256.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8465.67 | 294.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8710.17 | 49.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8753.50 | 6.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8714.50 | 45.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8709.00 | 51.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8753.50 | 6.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8713.50 | 46.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8626.83 | 133.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8624.00 | 136.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8583.67 | 176.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8716.33 | 43.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8715.83 | 44.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8581.33 | 178.67 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 8728.83 | 31.17 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 8561.17 | 198.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 7378.83 | 1340.83 | 40.33 | 0.00 | 0.00 |
Min | 7378.83 | 6.50 | 0.00 | 0.00 | 0.00 |
Max | 8753.50 | 1340.83 | 40.33 | 0.00 | 0.00 |
Average | 8555.18 | 202.90 | 1.92 | 0.00 | 0.00 |
Sum | 179658.83 | 4260.83 | 40.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8643.67 | 481.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8778.33 | 346.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8609.67 | 515.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8631.50 | 493.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8774.67 | 350.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8601.17 | 523.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9054.50 | 70.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 9117.50 | 7.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9045.67 | 79.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9055.33 | 69.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 9117.67 | 7.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9043.33 | 81.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8900.50 | 224.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8892.67 | 232.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8906.33 | 218.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 9082.50 | 42.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 9076.00 | 49.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8905.33 | 219.67 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 9117.67 | 523.83 | 0.00 | 0.00 | 0.00 |
Average | 7630.30 | 191.13 | 0.00 | 0.00 | 0.00 |
Sum | 160236.33 | 4013.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (F) | SET ≤ 12.2°C OccupantHours (F) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (F) | SET > 30°C OccupantHours (F) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2021-05-12 10:30:51
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 236.653 | 5.999 | 170.206 | 4.874 | 10.920 |
February | 166.153 | 4.226 | 155.122 | 3.723 | 8.092 |
March | 156.556 | 4.534 | 206.869 | 5.566 | 10.167 |
April | 290.583 | 9.328 | 61.758 | 1.341 | 10.731 |
May | 338.786 | 9.725 | 18.575 | 0.453 | 10.281 |
June | 489.889 | 15.722 | 0.000 | 0.000 | 15.731 |
July | 647.431 | 24.024 | 0.000 | 0.000 | 24.024 |
August | 660.425 | 25.852 | 0.000 | 0.000 | 25.852 |
September | 526.231 | 20.362 | 0.000 | 0.000 | 20.362 |
October | 536.556 | 20.852 | 7.111 | 0.158 | 21.222 |
November | 270.994 | 7.465 | 92.236 | 2.218 | 9.711 |
December | 242.725 | 7.049 | 159.222 | 4.333 | 11.400 |
Annual Sum or Average | 4562.981 | 155.138 | 871.100 | 22.667 | 178.493 |
Minimum of Months | 156.556 | 4.226 | 0.000 | 0.000 | 8.092 |
Maximum of Months | 660.425 | 25.852 | 206.869 | 5.566 | 25.852 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 273.156 | 4.363 | 73.597 | 0.985 | 5.643 |
February | 182.028 | 2.576 | 53.983 | 0.630 | 3.677 |
March | 152.875 | 2.258 | 102.547 | 1.219 | 4.596 |
April | 293.236 | 4.538 | 13.028 | 0.133 | 4.947 |
May | 364.653 | 5.033 | 1.694 | 0.022 | 5.109 |
June | 560.697 | 9.872 | 0.000 | 0.000 | 9.872 |
July | 718.750 | 16.524 | 0.000 | 0.000 | 16.524 |
August | 718.444 | 18.743 | 0.000 | 0.000 | 18.743 |
September | 618.989 | 15.070 | 0.000 | 0.000 | 15.070 |
October | 594.508 | 16.483 | 0.083 | 0.001 | 16.484 |
November | 309.261 | 5.375 | 23.806 | 0.291 | 5.923 |
December | 282.289 | 5.237 | 65.381 | 0.825 | 6.541 |
Annual Sum or Average | 5068.886 | 106.072 | 334.119 | 4.105 | 113.128 |
Minimum of Months | 152.875 | 2.258 | 0.000 | 0.000 | 3.677 |
Maximum of Months | 718.750 | 18.743 | 102.547 | 1.219 | 18.743 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 248.933 | 5.341 | 72.931 | 2.905 | 15.707 |
February | 175.244 | 3.335 | 60.708 | 2.313 | 14.459 |
March | 166.490 | 3.617 | 101.500 | 3.392 | 16.277 |
April | 322.133 | 7.744 | 12.722 | 0.446 | 14.433 |
May | 388.208 | 8.116 | 3.194 | 0.180 | 10.581 |
June | 502.497 | 14.100 | 0.000 | 0.000 | 14.100 |
July | 634.375 | 22.825 | 0.000 | 0.000 | 22.825 |
August | 659.444 | 25.051 | 0.000 | 0.000 | 25.051 |
September | 534.150 | 18.408 | 0.000 | 0.000 | 18.421 |
October | 558.875 | 19.442 | 0.083 | 0.006 | 20.640 |
November | 283.889 | 6.206 | 30.583 | 1.397 | 13.512 |
December | 251.414 | 6.215 | 72.472 | 2.931 | 16.200 |
Annual Sum or Average | 4725.654 | 140.399 | 354.194 | 13.570 | 202.207 |
Minimum of Months | 166.490 | 3.335 | 0.000 | 0.000 | 10.581 |
Maximum of Months | 659.444 | 25.051 | 101.500 | 3.392 | 25.051 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 84.417 | 1.291 | 159.072 | 4.590 | 16.741 |
February | 65.333 | 0.882 | 129.633 | 3.165 | 13.047 |
March | 95.333 | 1.799 | 158.925 | 4.108 | 16.523 |
April | 242.583 | 6.339 | 44.328 | 0.884 | 10.984 |
May | 332.978 | 8.889 | 11.917 | 0.252 | 10.172 |
June | 497.967 | 15.595 | 0.000 | 0.000 | 15.595 |
July | 652.347 | 23.309 | 0.000 | 0.000 | 23.309 |
August | 658.164 | 23.085 | 0.000 | 0.000 | 23.085 |
September | 508.022 | 15.781 | 0.083 | 0.009 | 15.789 |
October | 503.611 | 14.580 | 7.042 | 0.136 | 15.319 |
November | 129.944 | 1.893 | 76.661 | 1.950 | 11.051 |
December | 102.944 | 1.538 | 144.861 | 4.212 | 16.364 |
Annual Sum or Average | 3873.644 | 114.980 | 732.522 | 19.305 | 187.980 |
Minimum of Months | 65.333 | 0.882 | 0.000 | 0.000 | 10.172 |
Maximum of Months | 658.164 | 23.309 | 159.072 | 4.590 | 23.309 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 80.972 | 0.774 | 136.419 | 1.726 | 3.655 |
February | 19.000 | 0.080 | 87.564 | 1.008 | 2.506 |
March | 47.083 | 0.265 | 131.144 | 1.567 | 3.579 |
April | 201.056 | 1.861 | 14.686 | 0.146 | 2.314 |
May | 354.681 | 4.262 | 1.056 | 0.015 | 4.309 |
June | 571.633 | 9.795 | 0.000 | 0.000 | 9.795 |
July | 721.375 | 15.847 | 0.000 | 0.000 | 15.847 |
August | 716.528 | 16.030 | 0.000 | 0.000 | 16.030 |
September | 602.439 | 10.582 | 0.000 | 0.000 | 10.582 |
October | 561.814 | 10.526 | 0.083 | 0.001 | 10.527 |
November | 91.875 | 0.626 | 41.169 | 0.485 | 1.580 |
December | 82.986 | 0.638 | 118.381 | 1.434 | 3.468 |
Annual Sum or Average | 4051.442 | 71.286 | 530.502 | 6.383 | 84.194 |
Minimum of Months | 19.000 | 0.080 | 0.000 | 0.000 | 1.580 |
Maximum of Months | 721.375 | 16.030 | 136.419 | 1.726 | 16.030 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 82.472 | 1.061 | 115.350 | 4.060 | 13.169 |
February | 27.333 | 0.214 | 85.442 | 2.914 | 12.536 |
March | 85.570 | 1.006 | 120.056 | 3.841 | 14.440 |
April | 268.019 | 4.580 | 14.528 | 0.486 | 11.398 |
May | 385.792 | 7.357 | 2.972 | 0.171 | 9.643 |
June | 509.981 | 14.234 | 0.000 | 0.000 | 14.234 |
July | 640.389 | 22.478 | 0.000 | 0.000 | 22.478 |
August | 657.028 | 22.722 | 0.000 | 0.000 | 22.722 |
September | 524.178 | 14.132 | 0.000 | 0.000 | 14.182 |
October | 544.033 | 13.448 | 0.083 | 0.006 | 14.704 |
November | 92.631 | 0.909 | 38.181 | 1.550 | 9.134 |
December | 96.097 | 1.031 | 106.794 | 3.805 | 13.393 |
Annual Sum or Average | 3913.523 | 103.171 | 483.406 | 16.833 | 172.032 |
Minimum of Months | 27.333 | 0.214 | 0.000 | 0.000 | 9.134 |
Maximum of Months | 657.028 | 22.722 | 120.056 | 4.060 | 22.722 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 347.314 | 11.010 | 65.492 | 1.741 | 13.996 |
February | 267.319 | 7.971 | 38.417 | 0.856 | 10.051 |
March | 241.111 | 8.029 | 67.153 | 1.652 | 12.185 |
April | 411.863 | 15.563 | 3.361 | 0.079 | 15.883 |
May | 449.833 | 14.704 | 1.861 | 0.045 | 15.016 |
June | 617.117 | 22.096 | 0.000 | 0.000 | 22.096 |
July | 733.167 | 31.577 | 0.000 | 0.000 | 31.577 |
August | 731.386 | 33.257 | 0.000 | 0.000 | 33.257 |
September | 649.008 | 26.808 | 0.000 | 0.000 | 26.808 |
October | 618.919 | 26.828 | 0.250 | 0.004 | 26.879 |
November | 385.239 | 12.797 | 17.097 | 0.396 | 13.961 |
December | 361.611 | 12.074 | 53.386 | 1.324 | 14.542 |
Annual Sum or Average | 5813.888 | 222.714 | 247.017 | 6.097 | 236.252 |
Minimum of Months | 241.111 | 7.971 | 0.000 | 0.000 | 10.051 |
Maximum of Months | 733.167 | 33.257 | 67.153 | 1.741 | 33.257 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 435.764 | 10.176 | 19.278 | 0.244 | 10.630 |
February | 314.583 | 6.657 | 4.583 | 0.047 | 6.854 |
March | 284.272 | 5.778 | 19.500 | 0.257 | 6.381 |
April | 480.372 | 10.825 | 0.528 | 0.006 | 10.835 |
May | 541.792 | 10.166 | 0.000 | 0.000 | 10.166 |
June | 687.714 | 16.235 | 0.000 | 0.000 | 16.235 |
July | 743.500 | 23.393 | 0.000 | 0.000 | 23.393 |
August | 744.000 | 25.594 | 0.000 | 0.000 | 25.594 |
September | 701.208 | 21.631 | 0.000 | 0.000 | 21.631 |
October | 675.931 | 22.794 | 0.000 | 0.000 | 22.794 |
November | 469.390 | 11.436 | 0.625 | 0.006 | 11.442 |
December | 440.944 | 11.068 | 9.847 | 0.112 | 11.303 |
Annual Sum or Average | 6519.471 | 175.754 | 54.361 | 0.672 | 177.258 |
Minimum of Months | 284.272 | 5.778 | 0.000 | 0.000 | 6.381 |
Maximum of Months | 744.000 | 25.594 | 19.500 | 0.257 | 25.594 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 377.931 | 10.669 | 17.361 | 0.813 | 17.895 |
February | 279.444 | 7.244 | 5.264 | 0.225 | 14.110 |
March | 270.354 | 7.444 | 18.097 | 0.739 | 15.775 |
April | 456.972 | 14.722 | 0.556 | 0.031 | 15.314 |
May | 493.326 | 13.522 | 0.083 | 0.007 | 14.046 |
June | 627.000 | 20.448 | 0.000 | 0.000 | 20.448 |
July | 728.889 | 30.100 | 0.000 | 0.000 | 30.100 |
August | 728.778 | 32.282 | 0.000 | 0.000 | 32.282 |
September | 646.847 | 24.645 | 0.000 | 0.000 | 24.645 |
October | 631.494 | 25.503 | 0.000 | 0.000 | 25.570 |
November | 416.212 | 11.806 | 0.625 | 0.039 | 15.525 |
December | 389.039 | 11.427 | 7.986 | 0.418 | 19.167 |
Annual Sum or Average | 6046.286 | 209.812 | 49.972 | 2.273 | 244.876 |
Minimum of Months | 270.354 | 7.244 | 0.000 | 0.000 | 14.046 |
Maximum of Months | 728.889 | 32.282 | 18.097 | 0.813 | 32.282 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 174.264 | 2.997 | 76.239 | 2.044 | 13.969 |
February | 163.944 | 2.580 | 44.750 | 0.969 | 8.022 |
March | 179.333 | 3.985 | 62.460 | 1.537 | 10.946 |
April | 373.377 | 11.658 | 3.444 | 0.073 | 12.317 |
May | 447.292 | 13.734 | 1.667 | 0.036 | 13.879 |
June | 623.606 | 21.984 | 0.000 | 0.000 | 21.984 |
July | 733.625 | 30.763 | 0.000 | 0.000 | 30.763 |
August | 729.969 | 30.197 | 0.000 | 0.000 | 30.197 |
September | 638.767 | 21.625 | 0.000 | 0.000 | 21.625 |
October | 585.508 | 19.435 | 0.333 | 0.013 | 19.540 |
November | 265.050 | 4.502 | 24.689 | 0.595 | 8.561 |
December | 191.069 | 3.219 | 72.150 | 1.696 | 12.970 |
Annual Sum or Average | 5105.805 | 166.679 | 285.732 | 6.963 | 204.773 |
Minimum of Months | 163.944 | 2.580 | 0.000 | 0.000 | 8.022 |
Maximum of Months | 733.625 | 30.763 | 76.239 | 2.044 | 30.763 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 191.903 | 2.493 | 46.875 | 0.622 | 3.770 |
February | 144.292 | 1.275 | 15.544 | 0.159 | 1.811 |
March | 161.500 | 1.920 | 33.412 | 0.433 | 3.099 |
April | 430.365 | 6.897 | 1.056 | 0.013 | 6.920 |
May | 541.353 | 9.399 | 0.000 | 0.000 | 9.399 |
June | 692.883 | 16.450 | 0.000 | 0.000 | 16.450 |
July | 743.833 | 22.984 | 0.000 | 0.000 | 22.984 |
August | 744.000 | 22.974 | 0.000 | 0.000 | 22.974 |
September | 696.383 | 16.842 | 0.000 | 0.000 | 16.842 |
October | 650.850 | 15.846 | 0.000 | 0.000 | 15.846 |
November | 265.389 | 2.914 | 3.808 | 0.040 | 3.032 |
December | 211.167 | 2.358 | 34.667 | 0.419 | 3.205 |
Annual Sum or Average | 5473.918 | 122.352 | 135.362 | 1.685 | 126.331 |
Minimum of Months | 144.292 | 1.275 | 0.000 | 0.000 | 1.811 |
Maximum of Months | 744.000 | 22.984 | 46.875 | 0.622 | 22.984 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 160.144 | 2.704 | 38.492 | 1.818 | 11.668 |
February | 152.278 | 1.449 | 15.322 | 0.606 | 9.193 |
March | 181.175 | 3.242 | 32.472 | 1.311 | 12.213 |
April | 441.744 | 10.871 | 1.056 | 0.050 | 11.632 |
May | 493.618 | 12.815 | 0.083 | 0.007 | 13.272 |
June | 632.019 | 20.737 | 0.000 | 0.000 | 20.737 |
July | 730.694 | 29.851 | 0.000 | 0.000 | 29.851 |
August | 727.694 | 29.888 | 0.000 | 0.000 | 29.888 |
September | 639.933 | 20.042 | 0.000 | 0.000 | 20.042 |
October | 616.794 | 18.694 | 0.000 | 0.000 | 18.846 |
November | 240.047 | 2.971 | 4.569 | 0.267 | 8.005 |
December | 185.111 | 2.742 | 27.444 | 1.300 | 12.905 |
Annual Sum or Average | 5201.254 | 156.005 | 119.439 | 5.358 | 198.251 |
Minimum of Months | 152.278 | 1.449 | 0.000 | 0.000 | 8.005 |
Maximum of Months | 730.694 | 29.888 | 38.492 | 1.818 | 29.888 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 304.750 | 9.696 | 79.411 | 3.153 | 20.800 |
February | 214.153 | 6.946 | 74.142 | 2.256 | 15.737 |
March | 211.472 | 7.530 | 92.811 | 3.229 | 21.334 |
April | 368.889 | 15.555 | 8.017 | 0.286 | 19.553 |
May | 389.133 | 14.391 | 3.867 | 0.112 | 17.283 |
June | 547.322 | 22.204 | 0.000 | 0.000 | 22.204 |
July | 698.917 | 32.567 | 0.000 | 0.000 | 32.567 |
August | 693.928 | 34.041 | 0.000 | 0.000 | 34.041 |
September | 567.294 | 26.348 | 0.083 | 0.011 | 26.360 |
October | 555.650 | 26.273 | 1.083 | 0.041 | 28.120 |
November | 336.069 | 11.390 | 42.792 | 1.388 | 17.341 |
December | 312.325 | 10.621 | 86.950 | 2.856 | 19.697 |
Annual Sum or Average | 5199.903 | 217.562 | 389.156 | 13.332 | 275.037 |
Minimum of Months | 211.472 | 6.946 | 0.000 | 0.000 | 15.737 |
Maximum of Months | 698.917 | 34.041 | 92.811 | 3.229 | 34.041 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 359.694 | 8.704 | 55.914 | 0.844 | 10.283 |
February | 254.903 | 5.600 | 34.694 | 0.434 | 6.448 |
March | 228.375 | 5.310 | 72.665 | 0.993 | 7.256 |
April | 409.938 | 10.829 | 2.136 | 0.029 | 10.874 |
May | 434.611 | 9.730 | 1.194 | 0.013 | 9.750 |
June | 615.831 | 16.312 | 0.000 | 0.000 | 16.312 |
July | 732.694 | 24.746 | 0.000 | 0.000 | 24.746 |
August | 735.067 | 26.773 | 0.000 | 0.000 | 26.773 |
September | 653.611 | 21.264 | 0.000 | 0.000 | 21.264 |
October | 632.506 | 22.439 | 0.000 | 0.000 | 22.439 |
November | 391.531 | 9.884 | 11.333 | 0.151 | 10.216 |
December | 372.139 | 9.473 | 46.239 | 0.624 | 10.507 |
Annual Sum or Average | 5820.900 | 171.066 | 224.177 | 3.088 | 176.869 |
Minimum of Months | 228.375 | 5.310 | 0.000 | 0.000 | 6.448 |
Maximum of Months | 735.067 | 26.773 | 72.665 | 0.993 | 26.773 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 328.875 | 8.577 | 54.494 | 2.083 | 17.463 |
February | 228.733 | 5.729 | 38.303 | 1.502 | 14.914 |
March | 229.355 | 6.339 | 72.778 | 2.591 | 16.936 |
April | 420.683 | 13.500 | 3.167 | 0.190 | 16.340 |
May | 440.236 | 12.065 | 2.500 | 0.175 | 13.583 |
June | 564.369 | 19.288 | 0.000 | 0.000 | 19.288 |
July | 696.014 | 29.370 | 0.000 | 0.000 | 29.370 |
August | 697.542 | 31.238 | 0.000 | 0.000 | 31.238 |
September | 576.086 | 22.818 | 0.000 | 0.000 | 22.834 |
October | 580.869 | 23.455 | 0.083 | 0.008 | 24.756 |
November | 364.928 | 9.540 | 14.653 | 0.768 | 16.242 |
December | 335.125 | 9.181 | 46.028 | 1.793 | 18.785 |
Annual Sum or Average | 5462.816 | 191.100 | 232.006 | 9.111 | 241.749 |
Minimum of Months | 228.733 | 5.729 | 0.000 | 0.000 | 13.583 |
Maximum of Months | 697.542 | 31.238 | 72.778 | 2.591 | 31.238 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 166.556 | 3.306 | 131.506 | 4.453 | 19.837 |
February | 143.000 | 2.844 | 98.575 | 2.693 | 13.990 |
March | 170.417 | 4.840 | 119.961 | 3.475 | 17.978 |
April | 342.556 | 13.321 | 16.497 | 0.360 | 15.750 |
May | 384.500 | 14.001 | 7.311 | 0.176 | 15.594 |
June | 553.100 | 22.365 | 0.000 | 0.000 | 22.365 |
July | 701.194 | 32.372 | 0.000 | 0.000 | 32.372 |
August | 693.972 | 32.408 | 0.000 | 0.000 | 32.408 |
September | 555.953 | 23.059 | 0.083 | 0.011 | 23.092 |
October | 524.017 | 20.616 | 6.572 | 0.138 | 21.783 |
November | 238.056 | 4.767 | 65.542 | 1.792 | 14.362 |
December | 171.278 | 3.484 | 123.994 | 4.027 | 19.414 |
Annual Sum or Average | 4644.597 | 177.382 | 570.042 | 17.124 | 248.947 |
Minimum of Months | 143.000 | 2.844 | 0.000 | 0.000 | 13.990 |
Maximum of Months | 701.194 | 32.408 | 131.506 | 4.453 | 32.408 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 153.500 | 2.615 | 131.861 | 1.737 | 5.130 |
February | 128.917 | 1.442 | 66.800 | 0.762 | 3.101 |
March | 156.917 | 2.689 | 98.920 | 1.305 | 5.236 |
April | 375.105 | 8.542 | 2.861 | 0.037 | 8.594 |
May | 430.028 | 9.367 | 0.528 | 0.006 | 9.387 |
June | 622.786 | 16.540 | 0.000 | 0.000 | 16.540 |
July | 733.639 | 24.620 | 0.000 | 0.000 | 24.620 |
August | 735.042 | 25.214 | 0.000 | 0.000 | 25.214 |
September | 644.756 | 18.021 | 0.000 | 0.000 | 18.021 |
October | 600.208 | 16.760 | 0.083 | 0.001 | 16.760 |
November | 221.169 | 3.021 | 30.361 | 0.359 | 3.625 |
December | 173.264 | 2.449 | 111.206 | 1.396 | 4.860 |
Annual Sum or Average | 4975.330 | 131.279 | 442.620 | 5.603 | 141.088 |
Minimum of Months | 128.917 | 1.442 | 0.000 | 0.000 | 3.101 |
Maximum of Months | 735.042 | 25.214 | 131.861 | 1.737 | 25.214 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 152.561 | 2.735 | 106.150 | 3.905 | 12.982 |
February | 132.528 | 1.613 | 65.719 | 2.556 | 12.208 |
March | 179.900 | 3.747 | 94.219 | 3.301 | 14.497 |
April | 406.894 | 11.557 | 4.194 | 0.248 | 14.520 |
May | 440.119 | 11.974 | 1.972 | 0.161 | 13.486 |
June | 567.881 | 19.939 | 0.000 | 0.000 | 19.939 |
July | 697.917 | 29.894 | 0.000 | 0.000 | 29.894 |
August | 696.319 | 30.497 | 0.000 | 0.000 | 30.497 |
September | 569.508 | 20.318 | 0.083 | 0.007 | 20.355 |
October | 566.417 | 18.565 | 0.167 | 0.013 | 19.981 |
November | 209.236 | 3.028 | 30.764 | 1.582 | 10.749 |
December | 164.694 | 2.728 | 98.772 | 3.842 | 13.885 |
Annual Sum or Average | 4783.975 | 156.595 | 402.042 | 15.615 | 212.992 |
Minimum of Months | 132.528 | 1.613 | 0.000 | 0.000 | 10.749 |
Maximum of Months | 697.917 | 30.497 | 106.150 | 3.905 | 30.497 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNITHEATEDBSMT
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 351.242 | 16.038 | 37.490 |
February | 0.000 | 0.000 | 312.694 | 14.419 | 34.043 |
March | 0.000 | 0.000 | 379.708 | 17.305 | 37.202 |
April | 0.000 | 0.000 | 472.064 | 16.745 | 30.287 |
May | 0.000 | 0.000 | 30.811 | 0.786 | 13.712 |
June | 0.000 | 0.000 | 0.428 | 0.014 | 1.888 |
July | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 6.444 | 0.124 | 0.417 | 0.012 | 0.604 |
October | 8.611 | 0.150 | 8.583 | 0.162 | 2.227 |
November | 0.000 | 0.000 | 344.000 | 10.485 | 30.842 |
December | 0.000 | 0.000 | 367.228 | 15.679 | 36.257 |
Annual Sum or Average | 15.056 | 0.274 | 2267.175 | 91.644 | 224.551 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Maximum of Months | 8.611 | 0.150 | 472.064 | 17.305 | 37.490 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 387.35 | 0.00 | 0.00 |
February | 308.79 | 0.00 | 0.00 |
March | 429.59 | 0.00 | 0.00 |
April | 101.59 | 0.00 | 0.00 |
May | 33.70 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 11.88 | 0.00 | 0.00 |
November | 173.56 | 0.00 | 0.00 |
December | 338.22 | 0.00 | 0.00 |
Annual Sum or Average | 148.28 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 429.59 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 182.49 | 0.00 | 0.00 |
February | 120.28 | 0.00 | 0.00 |
March | 213.86 | 0.00 | 0.00 |
April | 22.85 | 0.00 | 0.00 |
May | 3.86 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.15 | 0.00 | 0.00 |
November | 51.81 | 0.00 | 0.00 |
December | 149.06 | 0.00 | 0.00 |
Annual Sum or Average | 62.03 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 213.86 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 284.27 | 0.00 | 0.00 |
February | 199.39 | 0.00 | 0.00 |
March | 319.82 | 0.00 | 0.00 |
April | 40.04 | 0.00 | 0.00 |
May | 8.17 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.63 | 0.00 | 0.00 |
November | 102.27 | 0.00 | 0.00 |
December | 253.79 | 0.00 | 0.00 |
Annual Sum or Average | 100.60 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 319.82 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 435.48 | 0.00 | 0.00 |
February | 316.73 | 0.00 | 0.00 |
March | 405.84 | 0.00 | 0.00 |
April | 84.69 | 0.00 | 0.00 |
May | 24.27 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.01 | 0.00 | 0.00 |
October | 12.91 | 0.00 | 0.00 |
November | 175.31 | 0.00 | 0.00 |
December | 379.72 | 0.00 | 0.00 |
Annual Sum or Average | 152.53 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 435.48 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 301.06 | 0.00 | 0.00 |
February | 187.57 | 0.00 | 0.00 |
March | 267.18 | 0.00 | 0.00 |
April | 25.98 | 0.00 | 0.00 |
May | 2.69 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.18 | 0.00 | 0.00 |
November | 84.27 | 0.00 | 0.00 |
December | 250.68 | 0.00 | 0.00 |
Annual Sum or Average | 93.25 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 301.06 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 396.04 | 0.00 | 0.00 |
February | 272.29 | 0.00 | 0.00 |
March | 363.73 | 0.00 | 0.00 |
April | 44.16 | 0.00 | 0.00 |
May | 7.14 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.64 | 0.00 | 0.00 |
November | 132.87 | 0.00 | 0.00 |
December | 348.22 | 0.00 | 0.00 |
Annual Sum or Average | 130.20 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 396.04 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 162.49 | 0.00 | 0.00 |
February | 83.51 | 0.00 | 0.00 |
March | 151.15 | 0.00 | 0.00 |
April | 7.29 | 0.00 | 0.00 |
May | 3.16 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.36 | 0.00 | 0.00 |
November | 36.83 | 0.00 | 0.00 |
December | 121.58 | 0.00 | 0.00 |
Annual Sum or Average | 47.30 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.49 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 41.05 | 0.00 | 0.00 |
February | 8.85 | 0.00 | 0.00 |
March | 45.94 | 0.00 | 0.00 |
April | 1.08 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 1.19 | 0.00 | 0.00 |
December | 18.32 | 0.00 | 0.00 |
Annual Sum or Average | 9.81 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.94 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 93.13 | 0.00 | 0.00 |
February | 25.79 | 0.00 | 0.00 |
March | 80.39 | 0.00 | 0.00 |
April | 2.68 | 0.00 | 0.00 |
May | 0.04 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 4.48 | 0.00 | 0.00 |
December | 46.57 | 0.00 | 0.00 |
Annual Sum or Average | 21.26 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 93.13 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 211.23 | 0.00 | 0.00 |
February | 104.79 | 0.00 | 0.00 |
March | 162.13 | 0.00 | 0.00 |
April | 7.92 | 0.00 | 0.00 |
May | 2.81 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.45 | 0.00 | 0.00 |
November | 53.56 | 0.00 | 0.00 |
December | 166.62 | 0.00 | 0.00 |
Annual Sum or Average | 59.23 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 211.23 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 111.54 | 0.00 | 0.00 |
February | 29.73 | 0.00 | 0.00 |
March | 77.01 | 0.00 | 0.00 |
April | 2.38 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 7.16 | 0.00 | 0.00 |
December | 72.45 | 0.00 | 0.00 |
Annual Sum or Average | 25.23 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 111.54 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 174.20 | 0.00 | 0.00 |
February | 59.00 | 0.00 | 0.00 |
March | 126.15 | 0.00 | 0.00 |
April | 4.89 | 0.00 | 0.00 |
May | 0.04 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 17.39 | 0.00 | 0.00 |
December | 114.49 | 0.00 | 0.00 |
Annual Sum or Average | 41.59 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 174.20 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 281.13 | 0.00 | 0.00 |
February | 183.35 | 0.00 | 0.00 |
March | 268.32 | 0.00 | 0.00 |
April | 17.15 | 0.00 | 0.00 |
May | 8.91 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.01 | 0.00 | 0.00 |
October | 2.61 | 0.00 | 0.00 |
November | 97.59 | 0.00 | 0.00 |
December | 245.50 | 0.00 | 0.00 |
Annual Sum or Average | 91.99 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 281.13 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 144.13 | 0.00 | 0.00 |
February | 76.61 | 0.00 | 0.00 |
March | 163.00 | 0.00 | 0.00 |
April | 4.88 | 0.00 | 0.00 |
May | 2.09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 25.66 | 0.00 | 0.00 |
December | 104.68 | 0.00 | 0.00 |
Annual Sum or Average | 43.54 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.00 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 243.24 | 0.00 | 0.00 |
February | 141.96 | 0.00 | 0.00 |
March | 249.58 | 0.00 | 0.00 |
April | 8.02 | 0.00 | 0.00 |
May | 5.27 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.05 | 0.00 | 0.00 |
November | 61.05 | 0.00 | 0.00 |
December | 192.27 | 0.00 | 0.00 |
Annual Sum or Average | 75.20 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 249.58 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 398.72 | 0.00 | 0.00 |
February | 244.94 | 0.00 | 0.00 |
March | 331.39 | 0.00 | 0.00 |
April | 32.91 | 0.00 | 0.00 |
May | 15.83 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.01 | 0.00 | 0.00 |
October | 13.05 | 0.00 | 0.00 |
November | 142.57 | 0.00 | 0.00 |
December | 338.79 | 0.00 | 0.00 |
Annual Sum or Average | 126.45 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 398.72 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 284.96 | 0.00 | 0.00 |
February | 131.59 | 0.00 | 0.00 |
March | 209.84 | 0.00 | 0.00 |
April | 6.15 | 0.00 | 0.00 |
May | 1.04 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.13 | 0.00 | 0.00 |
November | 58.95 | 0.00 | 0.00 |
December | 224.09 | 0.00 | 0.00 |
Annual Sum or Average | 76.60 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 284.96 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 371.59 | 0.00 | 0.00 |
February | 194.34 | 0.00 | 0.00 |
March | 292.96 | 0.00 | 0.00 |
April | 9.48 | 0.00 | 0.00 |
May | 3.50 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.01 | 0.00 | 0.00 |
October | 0.75 | 0.00 | 0.00 |
November | 96.71 | 0.00 | 0.00 |
December | 311.95 | 0.00 | 0.00 |
Annual Sum or Average | 106.93 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 371.59 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNITHEATEDBSMT
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 2000.15 | 0.00 | 0.00 |
February | 1957.86 | 0.00 | 0.00 |
March | 2153.86 | 0.00 | 0.00 |
April | 2038.83 | 0.00 | 0.00 |
May | 106.39 | 0.00 | 0.00 |
June | 1.77 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 1.60 | 0.00 | 0.00 |
October | 25.12 | 0.00 | 0.00 |
November | 1375.80 | 0.00 | 0.00 |
December | 1949.90 | 0.00 | 0.00 |
Annual Sum or Average | 960.71 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2153.86 | 0.00 | 0.00 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.05 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.08 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.13 |
July | 0.00 | 0.00 | 0.19 |
August | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.00 | 0.17 |
October | 0.00 | 0.00 | 0.16 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.21 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.03 |
February | 0.00 | 0.00 | 0.02 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.08 |
July | 0.00 | 0.00 | 0.14 |
August | 0.00 | 0.00 | 0.16 |
September | 0.00 | 0.00 | 0.13 |
October | 0.00 | 0.00 | 0.14 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.00 | 0.00 | 0.16 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.11 |
July | 0.00 | 0.00 | 0.19 |
August | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.00 | 0.15 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.09 |
Minimum of Months | 0.00 | 0.00 | 0.03 |
Maximum of Months | 0.00 | 0.00 | 0.21 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.13 |
July | 0.00 | 0.00 | 0.19 |
August | 0.00 | 0.00 | 0.19 |
September | 0.00 | 0.00 | 0.13 |
October | 0.00 | 0.00 | 0.11 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.19 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.08 |
July | 0.00 | 0.00 | 0.14 |
August | 0.00 | 0.00 | 0.14 |
September | 0.00 | 0.00 | 0.09 |
October | 0.00 | 0.00 | 0.09 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.14 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.12 |
July | 0.00 | 0.00 | 0.18 |
August | 0.00 | 0.00 | 0.18 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.10 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.18 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.08 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.13 |
May | 0.00 | 0.00 | 0.11 |
June | 0.00 | 0.00 | 0.18 |
July | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.00 | 0.22 |
October | 0.00 | 0.00 | 0.21 |
November | 0.00 | 0.00 | 0.10 |
December | 0.00 | 0.00 | 0.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.27 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.08 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.09 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.14 |
July | 0.00 | 0.00 | 0.20 |
August | 0.00 | 0.00 | 0.22 |
September | 0.00 | 0.00 | 0.19 |
October | 0.00 | 0.00 | 0.19 |
November | 0.00 | 0.00 | 0.10 |
December | 0.00 | 0.00 | 0.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.22 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.08 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.12 |
May | 0.00 | 0.00 | 0.10 |
June | 0.00 | 0.00 | 0.17 |
July | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.00 | 0.26 |
September | 0.00 | 0.00 | 0.20 |
October | 0.00 | 0.00 | 0.20 |
November | 0.00 | 0.00 | 0.09 |
December | 0.00 | 0.00 | 0.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.14 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.26 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.02 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.09 |
May | 0.00 | 0.00 | 0.11 |
June | 0.00 | 0.00 | 0.18 |
July | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.00 | 0.24 |
September | 0.00 | 0.00 | 0.18 |
October | 0.00 | 0.00 | 0.15 |
November | 0.00 | 0.00 | 0.03 |
December | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.11 |
Minimum of Months | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.00 | 0.00 | 0.25 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.14 |
July | 0.00 | 0.00 | 0.19 |
August | 0.00 | 0.00 | 0.19 |
September | 0.00 | 0.00 | 0.14 |
October | 0.00 | 0.00 | 0.13 |
November | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.09 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.19 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.09 |
May | 0.00 | 0.00 | 0.10 |
June | 0.00 | 0.00 | 0.17 |
July | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.00 | 0.24 |
September | 0.00 | 0.00 | 0.16 |
October | 0.00 | 0.00 | 0.14 |
November | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.24 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.12 |
May | 0.00 | 0.00 | 0.11 |
June | 0.00 | 0.00 | 0.18 |
July | 0.00 | 0.00 | 0.26 |
August | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.00 | 0.21 |
October | 0.00 | 0.00 | 0.20 |
November | 0.00 | 0.00 | 0.09 |
December | 0.00 | 0.00 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.14 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.27 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.05 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.09 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.14 |
July | 0.00 | 0.00 | 0.20 |
August | 0.00 | 0.00 | 0.22 |
September | 0.00 | 0.00 | 0.18 |
October | 0.00 | 0.00 | 0.18 |
November | 0.00 | 0.00 | 0.08 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.22 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.05 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.11 |
May | 0.00 | 0.00 | 0.10 |
June | 0.00 | 0.00 | 0.16 |
July | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.00 | 0.20 |
October | 0.00 | 0.00 | 0.19 |
November | 0.00 | 0.00 | 0.08 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.13 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.27 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.02 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.11 |
May | 0.00 | 0.00 | 0.11 |
June | 0.00 | 0.00 | 0.18 |
July | 0.00 | 0.00 | 0.26 |
August | 0.00 | 0.00 | 0.26 |
September | 0.00 | 0.00 | 0.19 |
October | 0.00 | 0.00 | 0.16 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.00 | 0.00 | 0.26 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.14 |
July | 0.00 | 0.00 | 0.20 |
August | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.00 | 0.13 |
November | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.09 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.21 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.09 |
May | 0.00 | 0.00 | 0.09 |
June | 0.00 | 0.00 | 0.17 |
July | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.00 | 0.25 |
September | 0.00 | 0.00 | 0.17 |
October | 0.00 | 0.00 | 0.15 |
November | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.11 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.25 |
Report: COILLOADS
For: DX COOLING COIL_UNITHEATEDBSMT
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1195.96 | 890.42 |
February | 0.00 | 0.00 | 1202.50 | 808.66 |
March | 0.00 | 0.00 | 1186.90 | 883.68 |
April | 0.00 | 0.00 | 1156.23 | 833.07 |
May | 0.00 | 0.00 | 1117.39 | 831.93 |
June | 0.00 | 0.00 | 1084.60 | 781.47 |
July | 0.00 | 0.00 | 1063.99 | 792.17 |
August | 0.00 | 0.00 | 1059.51 | 788.84 |
September | 0.00 | 0.00 | 1077.83 | 776.59 |
October | 0.00 | 0.00 | 1108.40 | 825.23 |
November | 0.00 | 0.00 | 1146.96 | 826.40 |
December | 0.00 | 0.00 | 1180.08 | 878.60 |
Annual Sum or Average | 0.00 | 0.00 | 1131.28 | 9917.06 |
Minimum of Months | 0.00 | 0.00 | 1059.51 | 776.59 |
Maximum of Months | 0.00 | 0.00 | 1202.50 | 890.42 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1193.88 | 888.88 |
February | 0.00 | 0.00 | 1200.25 | 807.14 |
March | 0.00 | 0.00 | 1186.77 | 883.58 |
April | 0.00 | 0.00 | 1154.07 | 831.52 |
May | 0.00 | 0.00 | 1115.28 | 830.36 |
June | 0.00 | 0.00 | 1082.28 | 779.80 |
July | 0.00 | 0.00 | 1063.97 | 792.16 |
August | 0.00 | 0.00 | 1059.50 | 788.83 |
September | 0.00 | 0.00 | 1077.70 | 776.49 |
October | 0.00 | 0.00 | 1104.11 | 822.04 |
November | 0.00 | 0.00 | 1144.68 | 824.75 |
December | 0.00 | 0.00 | 1177.98 | 877.04 |
Annual Sum or Average | 0.00 | 0.00 | 1129.63 | 9902.58 |
Minimum of Months | 0.00 | 0.00 | 1059.50 | 776.49 |
Maximum of Months | 0.00 | 0.00 | 1200.25 | 888.88 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1195.93 | 890.40 |
February | 0.00 | 0.00 | 1200.06 | 807.01 |
March | 0.00 | 0.00 | 1189.04 | 885.27 |
April | 0.00 | 0.00 | 1153.92 | 831.41 |
May | 0.00 | 0.00 | 1117.34 | 831.89 |
June | 0.00 | 0.00 | 1082.25 | 779.77 |
July | 0.00 | 0.00 | 1066.19 | 793.81 |
August | 0.00 | 0.00 | 1059.61 | 788.91 |
September | 0.00 | 0.00 | 1077.76 | 776.54 |
October | 0.00 | 0.00 | 1106.30 | 823.67 |
November | 0.00 | 0.00 | 1146.95 | 826.39 |
December | 0.00 | 0.00 | 1178.18 | 877.19 |
Annual Sum or Average | 0.00 | 0.00 | 1130.73 | 9912.26 |
Minimum of Months | 0.00 | 0.00 | 1059.61 | 776.54 |
Maximum of Months | 0.00 | 0.00 | 1200.06 | 890.40 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1202.80 | 895.52 |
February | 0.00 | 0.00 | 1205.13 | 810.42 |
March | 0.00 | 0.00 | 1191.27 | 886.93 |
April | 0.00 | 0.00 | 1158.46 | 834.68 |
May | 0.00 | 0.00 | 1117.42 | 831.95 |
June | 0.00 | 0.00 | 1082.33 | 779.83 |
July | 0.00 | 0.00 | 1066.10 | 793.74 |
August | 0.00 | 0.00 | 1059.48 | 788.82 |
September | 0.00 | 0.00 | 1077.88 | 776.63 |
October | 0.00 | 0.00 | 1108.49 | 825.30 |
November | 0.00 | 0.00 | 1151.46 | 829.64 |
December | 0.00 | 0.00 | 1187.11 | 883.83 |
Annual Sum or Average | 0.00 | 0.00 | 1133.59 | 9937.29 |
Minimum of Months | 0.00 | 0.00 | 1059.48 | 776.63 |
Maximum of Months | 0.00 | 0.00 | 1205.13 | 895.52 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1202.91 | 895.60 |
February | 0.00 | 0.00 | 1205.15 | 810.44 |
March | 0.00 | 0.00 | 1191.24 | 886.91 |
April | 0.00 | 0.00 | 1156.34 | 833.16 |
May | 0.00 | 0.00 | 1115.32 | 830.39 |
June | 0.00 | 0.00 | 1082.32 | 779.82 |
July | 0.00 | 0.00 | 1063.95 | 792.14 |
August | 0.00 | 0.00 | 1059.52 | 788.84 |
September | 0.00 | 0.00 | 1077.70 | 776.50 |
October | 0.00 | 0.00 | 1106.36 | 823.72 |
November | 0.00 | 0.00 | 1151.48 | 829.65 |
December | 0.00 | 0.00 | 1184.85 | 882.15 |
Annual Sum or Average | 0.00 | 0.00 | 1132.68 | 9929.31 |
Minimum of Months | 0.00 | 0.00 | 1059.52 | 776.50 |
Maximum of Months | 0.00 | 0.00 | 1205.15 | 895.60 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1202.73 | 895.47 |
February | 0.00 | 0.00 | 1207.40 | 811.95 |
March | 0.00 | 0.00 | 1189.11 | 885.33 |
April | 0.00 | 0.00 | 1156.22 | 833.07 |
May | 0.00 | 0.00 | 1117.34 | 831.89 |
June | 0.00 | 0.00 | 1082.43 | 779.90 |
July | 0.00 | 0.00 | 1064.00 | 792.18 |
August | 0.00 | 0.00 | 1061.70 | 790.46 |
September | 0.00 | 0.00 | 1077.67 | 776.47 |
October | 0.00 | 0.00 | 1106.30 | 823.67 |
November | 0.00 | 0.00 | 1151.58 | 829.73 |
December | 0.00 | 0.00 | 1189.03 | 885.27 |
Annual Sum or Average | 0.00 | 0.00 | 1133.37 | 9935.38 |
Minimum of Months | 0.00 | 0.00 | 1061.70 | 776.47 |
Maximum of Months | 0.00 | 0.00 | 1207.40 | 895.47 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1191.57 | 887.16 |
February | 0.00 | 0.00 | 1195.36 | 803.85 |
March | 0.00 | 0.00 | 1182.53 | 880.43 |
April | 0.00 | 0.00 | 1149.47 | 828.21 |
May | 0.00 | 0.00 | 1113.05 | 828.69 |
June | 0.00 | 0.00 | 1082.33 | 779.83 |
July | 0.00 | 0.00 | 1063.93 | 792.13 |
August | 0.00 | 0.00 | 1059.50 | 788.83 |
September | 0.00 | 0.00 | 1077.81 | 776.57 |
October | 0.00 | 0.00 | 1104.07 | 822.01 |
November | 0.00 | 0.00 | 1142.45 | 823.15 |
December | 0.00 | 0.00 | 1175.67 | 875.32 |
Annual Sum or Average | 0.00 | 0.00 | 1127.76 | 9886.18 |
Minimum of Months | 0.00 | 0.00 | 1059.50 | 776.57 |
Maximum of Months | 0.00 | 0.00 | 1195.36 | 887.16 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1187.44 | 884.08 |
February | 0.00 | 0.00 | 1192.79 | 802.12 |
March | 0.00 | 0.00 | 1178.08 | 877.11 |
April | 0.00 | 0.00 | 1147.12 | 826.51 |
May | 0.00 | 0.00 | 1110.85 | 827.06 |
June | 0.00 | 0.00 | 1080.05 | 778.19 |
July | 0.00 | 0.00 | 1063.99 | 792.17 |
August | 0.00 | 0.00 | 1061.41 | 790.25 |
September | 0.00 | 0.00 | 1075.85 | 775.16 |
October | 0.00 | 0.00 | 1102.08 | 820.53 |
November | 0.00 | 0.00 | 1140.12 | 821.47 |
December | 0.00 | 0.00 | 1171.60 | 872.29 |
Annual Sum or Average | 0.00 | 0.00 | 1125.57 | 9866.95 |
Minimum of Months | 0.00 | 0.00 | 1061.41 | 775.16 |
Maximum of Months | 0.00 | 0.00 | 1192.79 | 884.08 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1191.57 | 887.15 |
February | 0.00 | 0.00 | 1195.25 | 803.78 |
March | 0.00 | 0.00 | 1180.19 | 878.69 |
April | 0.00 | 0.00 | 1149.36 | 828.12 |
May | 0.00 | 0.00 | 1112.86 | 828.56 |
June | 0.00 | 0.00 | 1082.29 | 779.80 |
July | 0.00 | 0.00 | 1063.97 | 792.16 |
August | 0.00 | 0.00 | 1059.49 | 788.82 |
September | 0.00 | 0.00 | 1077.74 | 776.52 |
October | 0.00 | 0.00 | 1102.07 | 820.52 |
November | 0.00 | 0.00 | 1142.49 | 823.18 |
December | 0.00 | 0.00 | 1175.86 | 875.46 |
Annual Sum or Average | 0.00 | 0.00 | 1127.37 | 9882.76 |
Minimum of Months | 0.00 | 0.00 | 1059.49 | 776.52 |
Maximum of Months | 0.00 | 0.00 | 1195.25 | 887.15 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1196.24 | 890.63 |
February | 0.00 | 0.00 | 1200.32 | 807.18 |
March | 0.00 | 0.00 | 1184.74 | 882.07 |
April | 0.00 | 0.00 | 1151.77 | 829.86 |
May | 0.00 | 0.00 | 1113.13 | 828.75 |
June | 0.00 | 0.00 | 1080.10 | 778.22 |
July | 0.00 | 0.00 | 1066.14 | 793.77 |
August | 0.00 | 0.00 | 1059.54 | 788.86 |
September | 0.00 | 0.00 | 1075.58 | 774.97 |
October | 0.00 | 0.00 | 1106.31 | 823.68 |
November | 0.00 | 0.00 | 1146.93 | 826.37 |
December | 0.00 | 0.00 | 1180.18 | 878.67 |
Annual Sum or Average | 0.00 | 0.00 | 1129.68 | 9903.04 |
Minimum of Months | 0.00 | 0.00 | 1059.54 | 774.97 |
Maximum of Months | 0.00 | 0.00 | 1200.32 | 890.63 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1196.07 | 890.51 |
February | 0.00 | 0.00 | 1195.52 | 803.96 |
March | 0.00 | 0.00 | 1182.29 | 880.25 |
April | 0.00 | 0.00 | 1147.25 | 826.61 |
May | 0.00 | 0.00 | 1110.93 | 827.12 |
June | 0.00 | 0.00 | 1082.13 | 779.69 |
July | 0.00 | 0.00 | 1064.20 | 792.33 |
August | 0.00 | 0.00 | 1059.60 | 788.90 |
September | 0.00 | 0.00 | 1075.59 | 774.97 |
October | 0.00 | 0.00 | 1104.13 | 822.06 |
November | 0.00 | 0.00 | 1142.53 | 823.21 |
December | 0.00 | 0.00 | 1180.16 | 878.66 |
Annual Sum or Average | 0.00 | 0.00 | 1128.00 | 9888.25 |
Minimum of Months | 0.00 | 0.00 | 1059.60 | 774.97 |
Maximum of Months | 0.00 | 0.00 | 1196.07 | 890.51 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1196.03 | 890.48 |
February | 0.00 | 0.00 | 1200.28 | 807.16 |
March | 0.00 | 0.00 | 1182.39 | 880.32 |
April | 0.00 | 0.00 | 1151.56 | 829.71 |
May | 0.00 | 0.00 | 1112.99 | 828.65 |
June | 0.00 | 0.00 | 1080.19 | 778.29 |
July | 0.00 | 0.00 | 1063.94 | 792.13 |
August | 0.00 | 0.00 | 1059.49 | 788.82 |
September | 0.00 | 0.00 | 1077.84 | 776.59 |
October | 0.00 | 0.00 | 1104.05 | 822.00 |
November | 0.00 | 0.00 | 1144.83 | 824.86 |
December | 0.00 | 0.00 | 1182.54 | 880.44 |
Annual Sum or Average | 0.00 | 0.00 | 1129.27 | 9899.45 |
Minimum of Months | 0.00 | 0.00 | 1059.49 | 776.59 |
Maximum of Months | 0.00 | 0.00 | 1200.28 | 890.48 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1193.97 | 888.94 |
February | 0.00 | 0.00 | 1197.69 | 805.42 |
March | 0.00 | 0.00 | 1184.52 | 881.91 |
April | 0.00 | 0.00 | 1153.91 | 831.41 |
May | 0.00 | 0.00 | 1117.44 | 831.97 |
June | 0.00 | 0.00 | 1082.50 | 779.95 |
July | 0.00 | 0.00 | 1063.96 | 792.14 |
August | 0.00 | 0.00 | 1059.57 | 788.88 |
September | 0.00 | 0.00 | 1077.79 | 776.56 |
October | 0.00 | 0.00 | 1106.30 | 823.67 |
November | 0.00 | 0.00 | 1144.68 | 824.76 |
December | 0.00 | 0.00 | 1177.98 | 877.04 |
Annual Sum or Average | 0.00 | 0.00 | 1129.64 | 9902.64 |
Minimum of Months | 0.00 | 0.00 | 1059.57 | 776.56 |
Maximum of Months | 0.00 | 0.00 | 1197.69 | 888.94 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1191.59 | 887.17 |
February | 0.00 | 0.00 | 1195.25 | 803.78 |
March | 0.00 | 0.00 | 1180.19 | 878.69 |
April | 0.00 | 0.00 | 1151.72 | 829.82 |
May | 0.00 | 0.00 | 1113.12 | 828.75 |
June | 0.00 | 0.00 | 1080.24 | 778.33 |
July | 0.00 | 0.00 | 1064.02 | 792.19 |
August | 0.00 | 0.00 | 1059.53 | 788.85 |
September | 0.00 | 0.00 | 1077.86 | 776.61 |
October | 0.00 | 0.00 | 1104.19 | 822.10 |
November | 0.00 | 0.00 | 1142.44 | 823.14 |
December | 0.00 | 0.00 | 1173.61 | 873.79 |
Annual Sum or Average | 0.00 | 0.00 | 1127.42 | 9883.21 |
Minimum of Months | 0.00 | 0.00 | 1059.53 | 776.61 |
Maximum of Months | 0.00 | 0.00 | 1195.25 | 887.17 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1193.79 | 888.81 |
February | 0.00 | 0.00 | 1197.81 | 805.50 |
March | 0.00 | 0.00 | 1182.51 | 880.41 |
April | 0.00 | 0.00 | 1151.75 | 829.85 |
May | 0.00 | 0.00 | 1115.14 | 830.25 |
June | 0.00 | 0.00 | 1082.50 | 779.96 |
July | 0.00 | 0.00 | 1064.00 | 792.18 |
August | 0.00 | 0.00 | 1061.70 | 790.47 |
September | 0.00 | 0.00 | 1075.52 | 774.92 |
October | 0.00 | 0.00 | 1106.22 | 823.61 |
November | 0.00 | 0.00 | 1144.65 | 824.74 |
December | 0.00 | 0.00 | 1178.01 | 877.06 |
Annual Sum or Average | 0.00 | 0.00 | 1129.08 | 9897.75 |
Minimum of Months | 0.00 | 0.00 | 1061.70 | 774.92 |
Maximum of Months | 0.00 | 0.00 | 1197.81 | 888.81 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1198.23 | 892.11 |
February | 0.00 | 0.00 | 1202.81 | 808.86 |
March | 0.00 | 0.00 | 1186.85 | 883.64 |
April | 0.00 | 0.00 | 1153.99 | 831.46 |
May | 0.00 | 0.00 | 1115.28 | 830.36 |
June | 0.00 | 0.00 | 1082.48 | 779.94 |
July | 0.00 | 0.00 | 1064.00 | 792.18 |
August | 0.00 | 0.00 | 1059.57 | 788.88 |
September | 0.00 | 0.00 | 1077.79 | 776.56 |
October | 0.00 | 0.00 | 1108.47 | 825.29 |
November | 0.00 | 0.00 | 1149.30 | 828.09 |
December | 0.00 | 0.00 | 1182.57 | 880.46 |
Annual Sum or Average | 0.00 | 0.00 | 1131.37 | 9917.81 |
Minimum of Months | 0.00 | 0.00 | 1059.57 | 776.56 |
Maximum of Months | 0.00 | 0.00 | 1202.81 | 892.11 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1196.13 | 890.55 |
February | 0.00 | 0.00 | 1200.38 | 807.23 |
March | 0.00 | 0.00 | 1184.69 | 882.04 |
April | 0.00 | 0.00 | 1149.46 | 828.20 |
May | 0.00 | 0.00 | 1115.14 | 830.26 |
June | 0.00 | 0.00 | 1080.28 | 778.35 |
July | 0.00 | 0.00 | 1063.92 | 792.12 |
August | 0.00 | 0.00 | 1059.52 | 788.84 |
September | 0.00 | 0.00 | 1077.84 | 776.59 |
October | 0.00 | 0.00 | 1104.20 | 822.11 |
November | 0.00 | 0.00 | 1146.99 | 826.42 |
December | 0.00 | 0.00 | 1182.42 | 880.34 |
Annual Sum or Average | 0.00 | 0.00 | 1129.68 | 9903.05 |
Minimum of Months | 0.00 | 0.00 | 1059.52 | 776.59 |
Maximum of Months | 0.00 | 0.00 | 1200.38 | 890.55 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1198.13 | 892.04 |
February | 0.00 | 0.00 | 1200.25 | 807.14 |
March | 0.00 | 0.00 | 1186.99 | 883.75 |
April | 0.00 | 0.00 | 1151.57 | 829.72 |
May | 0.00 | 0.00 | 1115.20 | 830.30 |
June | 0.00 | 0.00 | 1082.46 | 779.92 |
July | 0.00 | 0.00 | 1063.97 | 792.15 |
August | 0.00 | 0.00 | 1059.50 | 788.82 |
September | 0.00 | 0.00 | 1077.83 | 776.59 |
October | 0.00 | 0.00 | 1106.24 | 823.63 |
November | 0.00 | 0.00 | 1147.06 | 826.47 |
December | 0.00 | 0.00 | 1184.61 | 881.98 |
Annual Sum or Average | 0.00 | 0.00 | 1130.76 | 9912.50 |
Minimum of Months | 0.00 | 0.00 | 1059.50 | 776.59 |
Maximum of Months | 0.00 | 0.00 | 1200.25 | 892.04 |
Report: HEATING AND COOLING LOADS
For: HEATEDBSMT
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 13.20 | 1292.98 |
February | 11.39 | 1141.09 |
March | 13.94 | 1381.33 |
April | 8.82 | 1321.85 |
May | 27.65 | 58.39 |
June | 23.31 | 5.08 |
July | 17.77 | 17.80 |
August | 17.10 | 20.19 |
September | 22.15 | 16.26 |
October | 21.52 | 43.83 |
November | 12.30 | 825.78 |
December | 12.93 | 1266.99 |
Annual Sum or Average | 202.08 | 7391.58 |
Minimum of Months | 8.82 | 5.08 |
Maximum of Months | 27.65 | 1381.33 |
Report: HEATING AND COOLING LOADS
For: BREEZEWAY
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 62.91 | 105.05 |
February | 52.52 | 67.57 |
March | 55.40 | 118.98 |
April | 78.02 | 22.15 |
May | 83.64 | 7.82 |
June | 100.00 | 0.00 |
July | 125.79 | 0.00 |
August | 132.04 | 0.00 |
September | 117.80 | 0.00 |
October | 122.51 | 2.18 |
November | 72.25 | 37.75 |
December | 68.99 | 86.48 |
Annual Sum or Average | 1071.86 | 447.97 |
Minimum of Months | 52.52 | 0.00 |
Maximum of Months | 132.04 | 118.98 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 65.00 | 45.73 |
February | 52.90 | 27.82 |
March | 52.84 | 46.82 |
April | 58.86 | 4.00 |
May | 63.19 | 1.13 |
June | 73.33 | 0.00 |
July | 92.79 | 0.00 |
August | 101.78 | 0.00 |
September | 95.67 | 0.00 |
October | 106.91 | 0.02 |
November | 69.22 | 12.06 |
December | 70.09 | 35.77 |
Annual Sum or Average | 902.59 | 173.36 |
Minimum of Months | 52.84 | 0.00 |
Maximum of Months | 106.91 | 46.82 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 66.10 | 129.28 |
February | 52.78 | 82.85 |
March | 56.49 | 134.12 |
April | 71.41 | 17.62 |
May | 75.77 | 3.98 |
June | 91.19 | 0.00 |
July | 119.61 | 0.00 |
August | 128.47 | 0.00 |
September | 108.34 | 0.00 |
October | 116.82 | 0.38 |
November | 69.50 | 47.40 |
December | 70.58 | 116.01 |
Annual Sum or Average | 1027.07 | 531.65 |
Minimum of Months | 52.78 | 0.00 |
Maximum of Months | 128.47 | 134.12 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 36.10 | 167.85 |
February | 33.99 | 100.56 |
March | 41.72 | 145.63 |
April | 62.98 | 24.18 |
May | 79.96 | 6.28 |
June | 100.02 | 0.00 |
July | 123.02 | 0.00 |
August | 118.66 | 0.00 |
September | 94.74 | 0.00 |
October | 88.90 | 3.05 |
November | 42.24 | 59.97 |
December | 37.61 | 146.53 |
Annual Sum or Average | 859.94 | 654.05 |
Minimum of Months | 33.99 | 0.00 |
Maximum of Months | 123.02 | 167.85 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 38.72 | 81.31 |
February | 35.68 | 46.62 |
March | 39.75 | 65.27 |
April | 45.28 | 5.24 |
May | 59.65 | 0.89 |
June | 73.63 | 0.00 |
July | 90.32 | 0.00 |
August | 88.36 | 0.00 |
September | 72.46 | 0.00 |
October | 73.30 | 0.05 |
November | 41.25 | 22.02 |
December | 38.50 | 67.36 |
Annual Sum or Average | 696.89 | 288.77 |
Minimum of Months | 35.68 | 0.00 |
Maximum of Months | 90.32 | 81.31 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 38.34 | 169.78 |
February | 33.72 | 109.06 |
March | 41.09 | 149.41 |
April | 55.16 | 18.93 |
May | 71.62 | 3.49 |
June | 91.16 | 0.00 |
July | 116.71 | 0.00 |
August | 114.86 | 0.00 |
September | 85.22 | 0.00 |
October | 82.96 | 0.39 |
November | 40.34 | 60.73 |
December | 37.96 | 152.09 |
Annual Sum or Average | 809.14 | 663.89 |
Minimum of Months | 33.72 | 0.00 |
Maximum of Months | 116.71 | 169.78 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 98.67 | 43.82 |
February | 81.81 | 18.92 |
March | 85.01 | 37.32 |
April | 114.44 | 1.82 |
May | 110.02 | 0.51 |
June | 130.25 | 0.00 |
July | 160.77 | 0.00 |
August | 166.25 | 0.00 |
September | 148.22 | 0.00 |
October | 152.09 | 0.03 |
November | 105.96 | 8.90 |
December | 105.30 | 31.31 |
Annual Sum or Average | 1458.79 | 142.63 |
Minimum of Months | 81.81 | 0.00 |
Maximum of Months | 166.25 | 43.82 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 103.28 | 8.11 |
February | 80.68 | 1.34 |
March | 80.95 | 11.17 |
April | 93.26 | 0.18 |
May | 89.59 | 0.00 |
June | 103.89 | 0.00 |
July | 125.51 | 0.00 |
August | 134.54 | 0.00 |
September | 127.67 | 0.00 |
October | 139.29 | 0.00 |
November | 104.73 | 0.11 |
December | 109.00 | 3.46 |
Annual Sum or Average | 1292.41 | 24.37 |
Minimum of Months | 80.68 | 0.00 |
Maximum of Months | 139.29 | 11.17 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 100.63 | 47.40 |
February | 79.32 | 12.32 |
March | 85.32 | 38.79 |
April | 110.12 | 1.36 |
May | 103.74 | 0.00 |
June | 121.88 | 0.00 |
July | 154.69 | 0.00 |
August | 163.42 | 0.00 |
September | 138.71 | 0.00 |
October | 147.72 | 0.00 |
November | 102.07 | 2.50 |
December | 104.98 | 24.98 |
Annual Sum or Average | 1412.60 | 127.36 |
Minimum of Months | 79.32 | 0.00 |
Maximum of Months | 163.42 | 47.40 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 53.85 | 81.42 |
February | 51.61 | 29.02 |
March | 63.55 | 54.58 |
April | 94.39 | 2.22 |
May | 105.79 | 0.40 |
June | 130.82 | 0.00 |
July | 158.11 | 0.00 |
August | 151.61 | 0.00 |
September | 121.91 | 0.00 |
October | 112.73 | 0.15 |
November | 61.12 | 16.05 |
December | 54.73 | 54.43 |
Annual Sum or Average | 1160.23 | 238.27 |
Minimum of Months | 51.61 | 0.00 |
Maximum of Months | 158.11 | 81.42 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 57.17 | 31.63 |
February | 49.73 | 5.28 |
March | 58.54 | 19.93 |
April | 72.35 | 0.60 |
May | 85.43 | 0.00 |
June | 104.82 | 0.00 |
July | 123.09 | 0.00 |
August | 119.71 | 0.00 |
September | 100.76 | 0.00 |
October | 98.53 | 0.00 |
November | 57.51 | 1.71 |
December | 56.90 | 18.70 |
Annual Sum or Average | 984.54 | 77.85 |
Minimum of Months | 49.73 | 0.00 |
Maximum of Months | 123.09 | 31.63 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 55.41 | 85.63 |
February | 47.65 | 25.77 |
March | 61.55 | 58.45 |
April | 88.98 | 2.40 |
May | 99.28 | 0.00 |
June | 122.31 | 0.00 |
July | 151.85 | 0.00 |
August | 148.54 | 0.00 |
September | 112.47 | 0.00 |
October | 108.15 | 0.00 |
November | 55.20 | 8.64 |
December | 55.16 | 56.95 |
Annual Sum or Average | 1106.54 | 237.84 |
Minimum of Months | 47.65 | 0.00 |
Maximum of Months | 151.85 | 85.63 |
Report: HEATING AND COOLING LOADS
For: ATTIC
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 49.84 | 166.33 |
February | 44.12 | 79.54 |
March | 58.92 | 125.40 |
April | 93.65 | 4.03 |
May | 96.77 | 1.86 |
June | 122.12 | 0.00 |
July | 157.30 | 0.00 |
August | 157.11 | 0.00 |
September | 118.08 | 0.00 |
October | 110.75 | 0.43 |
November | 52.93 | 46.13 |
December | 49.51 | 140.18 |
Annual Sum or Average | 1111.10 | 563.90 |
Minimum of Months | 44.12 | 0.00 |
Maximum of Months | 157.30 | 166.33 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 87.11 | 116.52 |
February | 69.09 | 62.43 |
March | 75.33 | 110.82 |
April | 106.00 | 3.56 |
May | 98.69 | 2.63 |
June | 120.88 | 0.00 |
July | 157.85 | 0.00 |
August | 165.16 | 0.00 |
September | 134.88 | 0.00 |
October | 141.87 | 0.00 |
November | 90.09 | 30.93 |
December | 90.80 | 93.60 |
Annual Sum or Average | 1337.78 | 420.49 |
Minimum of Months | 69.09 | 0.00 |
Maximum of Months | 165.16 | 116.52 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 87.03 | 119.86 |
February | 70.84 | 55.36 |
March | 76.58 | 103.48 |
April | 111.74 | 5.46 |
May | 106.41 | 3.14 |
June | 129.98 | 0.00 |
July | 164.29 | 0.00 |
August | 168.40 | 0.00 |
September | 144.49 | 0.00 |
October | 146.53 | 0.95 |
November | 94.03 | 29.76 |
December | 91.60 | 91.59 |
Annual Sum or Average | 1391.91 | 409.60 |
Minimum of Months | 70.84 | 0.00 |
Maximum of Months | 168.40 | 119.86 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 50.18 | 80.98 |
February | 45.77 | 30.22 |
March | 55.71 | 54.40 |
April | 79.52 | 1.68 |
May | 84.21 | 0.23 |
June | 104.17 | 0.00 |
July | 128.84 | 0.00 |
August | 128.67 | 0.00 |
September | 105.84 | 0.00 |
October | 101.53 | 0.17 |
November | 54.98 | 16.05 |
December | 50.25 | 61.45 |
Annual Sum or Average | 989.66 | 245.18 |
Minimum of Months | 45.77 | 0.00 |
Maximum of Months | 128.84 | 80.98 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 89.02 | 39.80 |
February | 70.66 | 17.90 |
March | 71.73 | 41.79 |
April | 91.36 | 1.29 |
May | 85.82 | 0.41 |
June | 102.72 | 0.00 |
July | 129.19 | 0.00 |
August | 136.68 | 0.00 |
September | 122.87 | 0.00 |
October | 133.23 | 0.00 |
November | 92.90 | 6.58 |
December | 93.90 | 25.28 |
Annual Sum or Average | 1220.07 | 133.04 |
Minimum of Months | 70.66 | 0.00 |
Maximum of Months | 136.68 | 41.79 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:30:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 48.68 | 168.29 |
February | 46.85 | 79.88 |
March | 60.62 | 125.80 |
April | 100.15 | 9.32 |
May | 104.79 | 4.44 |
June | 131.27 | 0.00 |
July | 163.82 | 0.00 |
August | 160.51 | 0.00 |
September | 127.87 | 0.00 |
October | 116.25 | 4.38 |
November | 57.25 | 48.26 |
December | 49.81 | 139.09 |
Annual Sum or Average | 1167.85 | 579.46 |