Table of Contents

Program Version:EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:31

Tabular Output Report in Format: HTML

Building: US+MF+CZ4B+oilfurnace+crawlspace+IECC_2018

Environment: ANNUAL ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650

Simulation Timestamp: 2021-05-12 10:31:15


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 825166.29 21.16 38.18
Net Site Energy 825166.29 21.16 38.18
Total Source Energy 1869354.78 47.93 86.50
Net Source Energy 1869354.78 47.93 86.50


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.22
Net Conditioned Building Area 21609.96
Unconditioned Building Area 17395.26


End Uses

Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 118813.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 67308.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 41293.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 18809.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299798.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 40805.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 238337.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 330767.30
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 468014.65 357151.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 330767.30
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 118813.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 67308.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 41293.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 18809.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 9418.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 4809.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 23499.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 17305.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 330767.30
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 238337.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 5.00 16.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.31
Other 13.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 21.66 16.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.31


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 2.77 9.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.48
Other 7.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 12.00 9.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.48


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 468014.653 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 468014.653 100.00
     
Total On-Site and Utility Electric Sources 468014.653 100.00
Total Electricity End Uses 468014.653 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 330767.30 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 330767.30 100.00
Total Water End Uses 330767.30 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 2148.50
Time Setpoint Not Met During Occupied Cooling 13.33
Time Not Comfortable Based on Simple ASHRAE 55-2004 651.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

HEATING AND COOLING LOADS

| CRAWLSPACE | BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

General

Value
Program Version and Build EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:31
RunPeriod ANNUAL
Weather File Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Latitude [deg] 35.04
Longitude [deg] -106.6
Elevation [ft] 5311.94
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 17103.09 6415.36 2136.19 6415.36 2136.19
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 12.43 8.29 24.89 8.29 24.89
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
CRAWLSPACE 7794.39 No Yes 19513.17 1.00 185.02 740.10 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.16 No Yes 30553.25 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6220 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6220 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6220 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6220 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
ATTIC 7802.71 No Yes 52795.56 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6220 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6220 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
Total 39005.22     286601.37   16363.00 740.10 2126.74 2126.74 0.3446 1083.48 1.6118
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.6220 600.28 2.9092
Unconditioned Total 17395.26     102861.98   1066.39 740.10 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 21-JUL-18:10 01-JAN-07:19 - - - - - - - - - - 01-JAN-08:09
Heating 0.00 76.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 42.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 12.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 4.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 50.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 10.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 221.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.20
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 121.02 297.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.20


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 76.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 42.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 12.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 4.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 2.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 5.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 9.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 25.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 8.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 1.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.20
  General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 221.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Gasoline [kBtu] Source Diesel [kBtu] Source Coal [kBtu] Source Fuel Oil No 1 [kBtu] Source Fuel Oil No 2 [kBtu] Source Propane [kBtu] Source Other Fuel 1 [kBtu] Source Other Fuel 2 [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 128794.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 213165.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 130776.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 59568.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 949462.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 129230.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 258358.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1482202.41 387152.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 5.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 9.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 6.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 43.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 5.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 11.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 68.59 17.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 3.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 5.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 24.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 3.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 6.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 38.00 9.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

ZoneHVAC:EnergyRecoveryVentilator

User-Specified Supply Air Flow Rate [ft3/min] User-Specified Exhaust Air Flow Rate [ft3/min]
ERV_UNIT1_FRONTROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT2_FRONTROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT3_FRONTROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT1_BACKROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT2_BACKROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT3_BACKROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT1_FRONTROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT2_FRONTROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT3_FRONTROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT1_BACKROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT2_BACKROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT3_BACKROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT3_BACKROW_TOPFLOOR 44.99 44.99
ERV_UNIT3_FRONTROW_TOPFLOOR 44.99 44.99
ERV_UNIT1_FRONTROW_TOPFLOOR 44.99 44.99
ERV_UNIT2_BACKROW_TOPFLOOR 44.99 44.99
ERV_UNIT2_FRONTROW_TOPFLOOR 44.99 44.99
ERV_UNIT1_BACKROW_TOPFLOOR 44.99 44.99
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

User-Specified Maximum Flow Rate [ft3/min] Design Size Maximum Flow Rate [ft3/min]
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR 44.99  
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR   530.41
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR   252.77
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR   371.44
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR   520.92
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR   254.84
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR   364.14
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR   513.02
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR   246.70
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR   378.01
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR   504.42
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR   247.30
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR   370.50
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR   546.60
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR   284.68
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR   381.64
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR   548.12
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR   292.19
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR   372.97
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

User-Specified Nominal Supply Air Flow Rate [ft3/min]
OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR 44.99
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 530.41
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 252.77
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 371.44
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 520.92
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 254.84
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 364.14
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 513.02
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 246.70
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 378.01
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 504.42
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 247.30
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 370.50
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 372.97
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 381.64
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 546.60
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 292.19
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 284.68
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 548.12
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] Sum of Air Terminal Maximum Flow Rates [ft3/min] Adjusted Heating Design Air Flow Rate [ft3/min] Adjusted Cooling Design Air Flow Rate [ft3/min] Adjusted Main Design Air Flow Rate [ft3/min] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 530.41 530.41 530.41 530.41 530.41 530.41 1.00 1.00 530.41
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 252.77 252.77 252.77 252.77 252.77 252.77 1.00 1.00 252.77
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 371.44 371.44 371.44 371.44 371.44 371.44 1.00 1.00 371.44
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 520.92 520.92 520.92 520.92 520.92 520.92 1.00 1.00 520.92
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 254.84 254.84 254.84 254.84 254.84 254.84 1.00 1.00 254.84
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 364.14 364.14 364.14 364.14 364.14 364.14 1.00 1.00 364.14
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 513.02 513.02 513.02 513.02 513.02 513.02 1.00 1.00 513.02
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 246.70 246.70 246.70 246.70 246.70 246.70 1.00 1.00 246.70
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 378.01 378.01 378.01 378.01 378.01 378.01 1.00 1.00 378.01
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 504.42 504.42 504.42 504.42 504.42 504.42 1.00 1.00 504.42
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 247.30 247.30 247.30 247.30 247.30 247.30 1.00 1.00 247.30
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 370.50 370.50 370.50 370.50 370.50 370.50 1.00 1.00 370.50
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 546.60 546.60 546.60 546.60 546.60 546.60 1.00 1.00 546.60
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 284.68 284.68 284.68 284.68 284.68 284.68 1.00 1.00 284.68
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 381.64 381.64 381.64 381.64 381.64 381.64 1.00 1.00 381.64
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 548.12 548.12 548.12 548.12 548.12 548.12 1.00 1.00 548.12
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 292.19 292.19 292.19 292.19 292.19 292.19 1.00 1.00 292.19
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 372.97 372.97 372.97 372.97 372.97 372.97 1.00 1.00 372.97
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 530.41 1.18 0.800655
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 252.77 0.561539 0.800655
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 371.44 0.825184 0.800655
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 520.92 1.16 0.800655
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 254.84 0.566146 0.800655
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 364.14 0.808954 0.800655
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 513.02 1.14 0.800655
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 246.70 0.548059 0.800655
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 378.01 0.839767 0.800655
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 504.42 1.12 0.800655
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 247.30 0.549399 0.800655
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 370.50 0.823083 0.800655
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 546.60 1.21 0.800655
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 284.68 0.632428 0.800655
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 381.64 0.847853 0.800655
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 548.12 1.22 0.800655
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 292.19 0.649112 0.800655
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 372.97 0.828570 0.800655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 530.41 530.41 530.41 1.18 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 252.77 252.77 252.77 0.561539 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 371.44 371.44 371.44 0.825184 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 520.92 520.92 520.92 1.16 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 254.84 254.84 254.84 0.566146 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 364.14 364.14 364.14 0.808954 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 513.02 513.02 513.02 1.14 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 246.70 246.70 246.70 0.548059 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 378.01 378.01 378.01 0.839767 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 504.42 504.42 504.42 1.12 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 247.30 247.30 247.30 0.549399 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 370.50 370.50 370.50 0.823083 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 546.60 546.60 546.60 1.21 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 284.68 284.68 284.68 0.632428 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 381.64 381.64 381.64 0.847853 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 548.12 548.12 548.12 1.22 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 292.19 292.19 292.19 0.649112 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 372.97 372.97 372.97 0.828570 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Water

Design Size Rated Capacity [Btu/h] Design Size Maximum Water Flow Rate [gal/min] Design Size U-Factor Times Area Value [Btu/h-F]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 25788.03 2.65 362.20
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 13426.16 1.38 182.90
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 18710.05 1.92 259.64
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 25365.50 2.60 356.08
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 13518.47 1.39 184.25
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 18384.78 1.89 254.92
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 25012.71 2.57 350.85
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 13155.59 1.35 178.86
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 19001.69 1.95 263.77
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 24629.97 2.53 345.31
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 13182.44 1.35 179.25
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 18667.32 1.92 258.93
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 26508.89 2.72 372.65
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 14846.85 1.52 203.56
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 19164.36 1.97 266.23
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR 26576.42 2.73 373.62
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR 15181.21 1.56 208.42
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR 18777.91 1.93 260.62
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
BOILER LOOP 4.80 9.60
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 2.09
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
BOILER CIRC PUMP 4.80
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [Btu/h] Design Size Design Water Flow Rate [gal/min]
CENTRAL BOILER 349898.33 35.92
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 36002.06 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
BGWALL_UPPER_LDF OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
BGWALL_UPPER_SDR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
BGWALL_UPPER_LDB OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
BGWALL_UPPER_SDL OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

Version

Version ID
1 9.5


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes No Yes Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.200 0.200


Site:GroundTemperature:BuildingSurface

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40


Site:GroundTemperature:FCfactorMethod

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 37.40 41.00 48.02 54.68 67.24 73.87 75.69 72.34 64.58 54.91 45.39 39.11


Site:GroundTemperature:Shallow

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40


Site:GroundTemperature:Deep

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {ft} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Sensor Height Above Ground {ft} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 32.810 0.140 885.870 4.921 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {ft} Standard Pressure at Elevation {psi} Standard RhoAir at Elevation
1 Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 35.04 -106.62 -7.00 5311.94 12. 0.9904


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{F} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} Fixed Default Water Mains Temperature{F}
1 Correlation NA 56.53 42.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 US+MF+CZ4B+oilfurnace+crawlspace+IECC_2018 0.000 Suburbs 4.00000E-002 0.40000 FullExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Gradient Coefficient {F/ft}
1 0.220 1213.970 0.003566


Material Details

Material Name ThermalResistance {m2-K/w} Roughness Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} Absorptance:Thermal Absorptance:Solar Absorptance:Visible
1 SHEATHING_CONSOL_LAYER 0.1351 Rough 0.0417 9.402E-002 42.764 0.280 0.9000 0.7000 0.7000
2 CEIL_CONSOL_LAYER 7.7625 Rough 1.5719 6.172E-002 2.618 0.185 0.9000 0.7000 0.7000
3 FLOOR_CONSOL_LAYER 2.8450 Rough 0.4584 4.910E-002 3.438 0.219 0.9000 0.7000 0.7000
4 BSMTWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
5 CRAWLWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
6 WALL_CONSOL_LAYER 2.4438 Rough 0.4584 5.717E-002 7.541 0.248 0.9000 0.7000 0.7000
7 VERY HIGH REFLECTIVITY SURFACE 2.1097E-006 Smooth 0.0016 237.000 168.680 0.216 0.9000 5.0000E-002 5.0000E-002
8 GYPSUMBOARD-5/16IN 5.0054E-002 Rough 0.0260 0.159 39.954 0.270 0.9000 0.4000 0.1000
9 COPPERPIPE 4.7506E-005 MediumRough 0.0625 401.000 140.026 0.200 0.9000 0.6500 0.6500
10 F08 METAL SURFACE 1.7668E-005 Smooth 0.0026 45.280 488.437 0.119 0.9000 0.7000 0.7000
11 CONCRETE_4IN 7.7356E-002 Rough 0.3330 1.312 140.014 0.111 0.9000 0.7000 0.7000
12 ASPHALT_SHINGLE 7.7448E-002 MediumRough 0.0208 8.186E-002 70.000 0.300 0.9000 0.7500 0.7000
13 WOOD_SHINGLE 0.1115 MediumSmooth 0.0417 0.114 26.600 0.390 0.9000 0.7000 0.7000
14 SLATE_SHINGLE 8.8061E-003 MediumSmooth 0.0417 1.442 100.000 0.300 0.9000 0.7000 0.7000
15 CEMENT_STUCCO 2.6422E-002 MediumSmooth 0.0625 0.721 116.464 0.210 0.9000 0.7000 0.7000
16 SYN_STUCCO 3.5237E-002 MediumSmooth 0.0100 8.650E-002 24.971 0.210 0.9000 0.7000 0.7000
17 DRYWALL_1/2IN 7.9331E-002 MediumSmooth 0.0417 0.160 50.000 0.260 0.9000 0.7000 0.7000
18 OSB_5/8IN 0.1365 MediumSmooth 0.0521 0.116 34.000 0.290 0.9000 0.7000 0.7000
19 OSB_7/16IN 9.5550E-002 MediumSmooth 0.0365 0.116 34.000 0.290 0.9000 0.7000 0.7000
20 BLOWN_R30 5.1614 MediumRough 0.6975 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
21 BLOWN_R30_TOP 2.8489 MediumRough 0.3849 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
22 PLYWOOD_3/4IN 0.1650 Rough 0.0625 0.115 34.003 0.161 0.9000 0.7000 0.7000
23 BATT_R19 7.3089 MediumRough 0.0833 3.475E-003 0.600 0.200 0.9000 0.7000 0.7000
24 LUMBER_2X4 0.7709 Rough 0.2920 0.115 32.003 0.183 0.9000 0.7000 0.7000
25 CARPET_N_PAD 0.4224 MediumSmooth 0.0833 6.013E-002 2.000 0.200 0.9000 0.7000 0.7000
26 BATT_R13 2.2936 MediumRough 0.2917 3.876E-002 0.600 0.200 0.9000 0.7000 0.7000
27 OSB_1/2IN 0.1092 MediumSmooth 0.0417 0.116 34.000 0.290 0.9000 0.7000 0.7000
28 SOIL_12IN 0.1761 Rough 1.0000 1.731 115.011 0.056 0.9000 0.7000 0.7000
29 DOOR_CONST 0.5503 Smooth 0.1300 7.201E-002 32.003 0.183 0.9000 0.7000 0.7000
30 GYP_BOARD_1/2IN 8.0130E-002 Rough 0.0417 0.159 39.954 0.270 0.9000 0.4000 0.1000
31 STD WOOD 6INCH 1.2500 MediumSmooth 0.4921 0.120 33.711 0.289 0.9000 0.7000 0.7000
32 PIPE INSULATION 0.3830 VeryRough 0.0417 3.317E-002 5.681 0.200 0.9000 0.5000 0.5000
33 MANF_WALL_AIRGAP 0.1200 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
34 BLDG_PAPER_FELT 1.0567E-002 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
35 R_HIGH 177.0000 MediumRough 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
36 CLEAR ACRYLIC PLASTIC 3.3333E-003 VerySmooth 0.0098 0.900 0.000 0.000 0.9000 0.0000 0.0000
37 DIFFUSING ACRYLIC PLASTIC 2.4444E-003 VerySmooth 0.0072 0.900 0.000 0.000 0.9000 0.0000 0.0000
38 INT_BLIND 0.0000 Rough 0.0000 0.000 0.000 0.000 0.0000 0.0000 0.0000
39 GLASS 0.3765 VerySmooth 0.1318 0.107 0.000 0.000 0.8400 0.0000 0.0000


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 LowerLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Other Side Coefficients

Name Combined convective/radiative film coefficient {Btu/h-ft2-F} User selected Constant Temperature {F} Coefficient modifying the constant temperature term Coefficient modifying the external dry bulb temperature term Coefficient modifying the ground temperature term Coefficient modifying the wind speed term {s/m} Coefficient modifying the zone air temperature term Constant Temperature Schedule Name Sinusoidal Variation Period of Sinusoidal Variation Previous Other Side Temperature Coefficient Minimum Other Side Temperature {F} Maximum Other Side Temperature {F}
1 SURFPROPOTHSDCOEFSLABAVERAGE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABAVERAGESURFACETEMP NO 24.000 0.000 N/A N/A
2 SURFPROPOTHSDCOEFSLABPERIMETER N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABPERIMETERTEMP NO 24.000 0.000 N/A N/A
3 SURFPROPOTHSDCOEFSLABCORE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABCORETEMP NO 24.000 0.000 N/A N/A


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{F}


Surface Convection Coefficient Lower Limit {Btu/h-ft2-F}


Surface Convection Coefficient Upper Limit {Btu/h-ft2-F}


1 CTF - ConductionTransferFunction 392. 0.02 176.1


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 60


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 21 186 48


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {ft} Origin Y-Coordinate {ft} Origin Z-Coordinate {ft} Centroid X-Coordinate {ft} Centroid Y-Coordinate {ft} Centroid Z-Coordinate {ft} Type Zone Multiplier Zone List Multiplier Minimum X {ft} Maximum X {ft} Minimum Y {ft} Maximum Y {ft} Minimum Z {ft} Maximum Z {ft} Ceiling Height {ft} Volume {ft3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {ft2} Exterior Gross Wall Area {ft2} Exterior Net Wall Area {ft2} Exterior Window Area {ft2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CRAWLSPACE 0.0 0.00 0.00 0.00 59.94 32.51 -0.8 1 1 1 0.00 119.89 0.00 65.10 -2.0 0.49 2.49 19513.15 TARP DOE-2 7794.37 185.05 185.05 0.00 15 0 0 Yes
2 BREEZEWAY 0.0 0.00 0.00 0.00 59.94 32.55 13.26 1 1 1 0.00 119.89 30.05 35.04 0.49 25.99 17.00 30553.07 TARP DOE-2 1798.18 0.00 0.00 0.00 4 0 0 Yes
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 4.76 1 1 1 0.00 39.96 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 4.76 1 1 1 39.96 79.93 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 4.76 1 1 1 79.93 119.89 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 4.76 1 1 1 0.00 39.96 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 4.76 1 1 1 39.96 79.93 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 4.76 1 1 1 79.93 119.89 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 13.26 1 1 1 0.00 39.96 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 13.26 1 1 1 39.96 79.93 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 13.26 1 1 1 79.93 119.89 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 13.26 1 1 1 0.00 39.96 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 13.26 1 1 1 39.96 79.93 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 13.26 1 1 1 79.93 119.89 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
15 ATTIC 0.0 -134.9 51.61 0.00 59.94 32.55 29.56 1 1 1 0.00 119.89 0.00 65.10 25.99 39.54 6.76 52795.39 TARP DOE-2 7802.66 881.33 881.33 0.00 11 0 0 Yes
16 LIVING_UNIT3_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 21.75 1 1 1 79.93 119.89 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
17 LIVING_UNIT3_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 21.75 1 1 1 79.93 119.89 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
18 LIVING_UNIT1_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 21.75 1 1 1 0.00 39.96 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
19 LIVING_UNIT2_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 21.75 1 1 1 39.96 79.93 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
20 LIVING_UNIT2_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 21.75 1 1 1 39.96 79.93 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
21 LIVING_UNIT1_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 21.75 1 1 1 0.00 39.96 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {ft2} # Occupants Area per Occupant {ft2/person} Occupant per Area {person/ft2} Interior Lighting {Btu/h-ft2} Electric Load {Btu/h-ft2} Gas Load {Btu/h-ft2} Other Load {Btu/h-ft2} Hot Water Eq {Btu/h-ft2} Steam Equipment {Btu/h-ft2} Sum Loads per Area {Btu/h-ft2} Outdoor Controlled Baseboard Heat
1 CRAWLSPACE 7794.37 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
2 BREEZEWAY 1798.18 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
15 ATTIC 7802.66 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
16 LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
17 LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
18 LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
19 LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
20 LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
21 LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Number of People {} People/Floor Area {person/ft2} Floor Area per person {ft2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
2 PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
3 PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
4 PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
5 PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
6 PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
7 PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
8 PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
9 PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
10 PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
11 PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
12 PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
13 PEOPLE_UNIT1_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
14 PEOPLE_UNIT2_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
15 PEOPLE_UNIT3_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
16 PEOPLE_UNIT1_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
17 PEOPLE_UNIT2_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
18 PEOPLE_UNIT3_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Lighting Level {Btu/h} Lights/Floor Area {Btu/h-ft2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {Btu/h} Nominal Maximum Lighting Level {Btu/h}
1 LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
2 LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
3 LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
4 LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
5 LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
6 LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
7 LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
8 LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
9 LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
10 LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
11 LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
12 LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
13 LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
14 LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
15 LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
16 LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
17 LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
18 LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
19 LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
20 LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
21 LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
22 LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
23 LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
24 LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
25 LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
26 LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
27 LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
28 LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
29 LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
30 LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
31 LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
32 LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
33 LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
34 LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
35 LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
36 LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Equipment Level {Btu/h} Equipment/Floor Area {Btu/h-ft2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {Btu/h} Nominal Maximum Equipment Level {Btu/h}
1 DISHWASHER1_FRONTROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
2 REFRIGERATOR1_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
3 CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
4 ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
5 ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
6 TELEVISION1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
7 ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
8 IECC_ADJ1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
9 DISHWASHER2_FRONTROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
10 REFRIGERATOR2_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
11 CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
12 ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
13 ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
14 TELEVISION2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
15 ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
16 IECC_ADJ2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
17 DISHWASHER3_FRONTROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
18 REFRIGERATOR3_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
19 CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
20 ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
21 ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
22 TELEVISION3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
23 ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
24 IECC_ADJ3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
25 DISHWASHER1_BACKROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
26 REFRIGERATOR1_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
27 CLOTHESWASHER1_BACKROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
28 ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
29 ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
30 TELEVISION1_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
31 ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
32 IECC_ADJ1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
33 DISHWASHER2_BACKROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
34 REFRIGERATOR2_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
35 CLOTHESWASHER2_BACKROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
36 ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
37 ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
38 TELEVISION2_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
39 ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
40 IECC_ADJ2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
41 DISHWASHER3_BACKROW_BOTTOMFLOOR DISHWASHER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
42 REFRIGERATOR3_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
43 CLOTHESWASHER3_BACKROW_BOTTOMFLOOR CLOTHESWASHER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
44 ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
45 ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
46 TELEVISION3_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
47 ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
48 IECC_ADJ3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
49 DISHWASHER1_FRONTROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
50 REFRIGERATOR1_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
51 CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
52 ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
53 ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
54 TELEVISION1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
55 ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
56 IECC_ADJ1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
57 DISHWASHER2_FRONTROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
58 REFRIGERATOR2_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
59 CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
60 ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
61 ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
62 TELEVISION2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
63 ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
64 IECC_ADJ2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
65 DISHWASHER3_FRONTROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
66 REFRIGERATOR3_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
67 CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
68 ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
69 ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
70 TELEVISION3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
71 ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
72 IECC_ADJ3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
73 DISHWASHER1_BACKROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
74 REFRIGERATOR1_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
75 CLOTHESWASHER1_BACKROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
76 ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
77 ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
78 TELEVISION1_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
79 ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
80 IECC_ADJ1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
81 DISHWASHER2_BACKROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
82 REFRIGERATOR2_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
83 CLOTHESWASHER2_BACKROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
84 ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
85 ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
86 TELEVISION2_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
87 ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
88 IECC_ADJ2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
89 DISHWASHER3_BACKROW_MIDDLEFLOOR DISHWASHER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
90 REFRIGERATOR3_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
91 CLOTHESWASHER3_BACKROW_MIDDLEFLOOR CLOTHESWASHER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
92 ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
93 ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
94 TELEVISION3_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
95 ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
96 IECC_ADJ3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
97 DISHWASHER1_FRONTROW_TOPFLOOR DISHWASHER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
98 REFRIGERATOR1_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
99 CLOTHESWASHER1_FRONTROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
100 ELECTRIC_DRYER1_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
101 ELECTRIC_RANGE1_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
102 TELEVISION1_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
103 ELECTRIC_MELS1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
104 IECC_ADJ1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
105 DISHWASHER2_FRONTROW_TOPFLOOR DISHWASHER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
106 REFRIGERATOR2_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
107 CLOTHESWASHER2_FRONTROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
108 ELECTRIC_DRYER2_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
109 ELECTRIC_RANGE2_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
110 TELEVISION2_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
111 ELECTRIC_MELS2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
112 IECC_ADJ2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
113 DISHWASHER3_FRONTROW_TOPFLOOR DISHWASHER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
114 REFRIGERATOR3_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
115 CLOTHESWASHER3_FRONTROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
116 ELECTRIC_DRYER3_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
117 ELECTRIC_RANGE3_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
118 TELEVISION3_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
119 ELECTRIC_MELS3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
120 IECC_ADJ3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
121 DISHWASHER1_BACKROW_TOPFLOOR DISHWASHER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
122 REFRIGERATOR1_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
123 CLOTHESWASHER1_BACKROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
124 ELECTRIC_DRYER1_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
125 ELECTRIC_RANGE1_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
126 TELEVISION1_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
127 ELECTRIC_MELS1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
128 IECC_ADJ1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
129 DISHWASHER2_BACKROW_TOPFLOOR DISHWASHER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
130 REFRIGERATOR2_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
131 CLOTHESWASHER2_BACKROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
132 ELECTRIC_DRYER2_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
133 ELECTRIC_RANGE2_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
134 TELEVISION2_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
135 ELECTRIC_MELS2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
136 IECC_ADJ2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
137 DISHWASHER3_BACKROW_TOPFLOOR DISHWASHER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 166.833
138 REFRIGERATOR3_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
139 CLOTHESWASHER3_BACKROW_TOPFLOOR CLOTHESWASHER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 72.311
140 ELECTRIC_DRYER3_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
141 ELECTRIC_RANGE3_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
142 TELEVISION3_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
143 ELECTRIC_MELS3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
144 IECC_ADJ3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736


Construction CTF

Construction Name Index #Layers #CTFs Time Step {Hours} ThermalConductance {Btu/h-ft2-F} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 EXTERIOR WALL 1 5 11 0.167 0.0631 0.900 0.900 0.700 0.700 MediumSmooth
2 CEILING-FLOOR-LAYER 3 1 5 0.167 0.228 0.900 0.900 0.700 0.700 Rough
3 EXTERIOR FLOOR 4 3 8 0.167 0.0513 0.900 0.900 0.700 0.700 Rough
4 INTERIOR FLOOR 5 2 4 0.167 0.300 0.900 0.900 0.700 0.700 Rough
5 INTERIOR CEILING 6 2 12 0.167 0.0225 0.900 0.900 0.700 0.700 Rough
6 ATTIC FLOOR 7 2 12 0.167 0.0225 0.900 0.900 0.700 0.700 MediumSmooth
7 INTERIORWALL 9 3 5 0.167 0.597 0.900 0.900 0.700 0.700 MediumSmooth
8 EXTERIOR ROOF 11 2 4 0.167 0.943 0.900 0.900 0.750 0.700 MediumRough
9 EXTERIOR DOOR 14 1 5 0.167 0.320 0.900 0.900 0.700 0.700 Smooth
10 GABLE_END 16 5 6 0.167 0.428 0.900 0.900 0.700 0.700 MediumSmooth
11 CRAWL WALL 24 1 5 0.167 2.28 0.900 0.900 0.700 0.700 Rough
12 iz-EXTERIOR FLOOR 25 3 8 0.167 0.0513 0.900 0.900 0.700 0.700 MediumSmooth


Material CTF Summary

Material Name Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} ThermalResistance {m2-K/w}
1 SYN_STUCCO 0.0098 0.086 24.971 0.210 0.3524E-01
2 SHEATHING_CONSOL_LAYER 0.0417 0.094 42.764 0.280 0.1351
3 OSB_7/16IN 0.0364 0.116 34.000 0.290 0.9555E-01
4 WALL_CONSOL_LAYER 0.4584 0.057 7.541 0.248 2.444
5 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
6 LUMBER_2X4 0.2920 0.115 32.003 0.183 0.7709
7 FLOOR_CONSOL_LAYER 0.4584 0.049 3.438 0.219 2.845
8 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
9 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
10 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
11 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
12 CEIL_CONSOL_LAYER 1.5719 0.062 2.618 0.185 7.762
13 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
14 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
15 CEIL_CONSOL_LAYER 1.5719 0.062 2.618 0.185 7.762
16 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
17 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
18 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
19 ASPHALT_SHINGLE 0.0207 0.082 70.000 0.300 0.7745E-01
20 OSB_1/2IN 0.0417 0.116 34.000 0.290 0.1092
21 DOOR_CONST 0.1299 0.072 32.003 0.183 0.5503
22 CEMENT_STUCCO 0.0627 0.721 116.464 0.210 0.2642E-01
23 BLDG_PAPER_FELT 0.0000 0.000 0.000 0.000 0.1057E-01
24 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
25 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
26 CONCRETE_4IN 0.3330 1.312 140.014 0.111 0.7736E-01
27 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
28 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
29 FLOOR_CONSOL_LAYER 0.4584 0.049 3.438 0.219 2.845


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


CTF

Time Outside Cross Inside Flux (except final one)
1 11 -0.54724946E-11 -0.29353179E-14 -0.58361936E-11 0.17617726E-15
2 10 0.24755928E-06 0.16971160E-13 0.58954555E-06 -0.42317085E-11
3 9 -0.21700660E-03 0.26282512E-10 -0.34360792E-03 0.18634160E-06
4 8 0.10400975E-01 0.16063655E-07 0.16710006E-01 -0.10459154E-03
5 7 -0.18466841 0.14497582E-05 -0.31678806 0.33996447E-02
6 6 1.6813335 0.30890211E-04 3.0392820 -0.45644738E-01
7 5 -8.8640021 0.19737274E-03 -16.399456 0.32465800
8 4 28.400945 0.41196590E-03 52.185337 -1.3315683
9 3 -55.684303 0.27160336E-03 -99.213599 3.2198962
10 2 64.740984 0.46773103E-04 110.17164 -4.4902555
11 1 -40.701741 0.11975386E-05 -65.686261 3.3169381
12 0 10.602230 0.29970883E-09 16.204438  
13 5 -0.10726087E-01 0.44268190E-05 -0.10726087E-01 0.97389233E-03
14 4 0.31857203 0.80150166E-03 0.31857203 -0.30727185E-01
15 3 -2.8372473 0.12516450E-01 -2.8372473 0.30041224
16 2 9.6667056 0.33176537E-01 9.6667056 -1.1584571
17 1 -13.322214 0.15207483E-01 -13.322214 1.8397512
18 0 6.2472388 0.62260140E-03 6.2472388  
19 8 0.57415395E-12 0.13118744E-13 0.10972129E-06 -0.16121901E-12
20 7 -0.11209345E-05 0.79302418E-09 -0.25702593E-04 0.31491488E-06
21 6 0.21835020E-03 0.55842834E-06 0.16732899E-02 -0.62999473E-04
22 5 -0.11788181E-01 0.43793696E-04 -0.40973943E-01 0.36016799E-02
23 4 0.21386917 0.66464187E-03 0.43752526 -0.72376639E-01
24 3 -1.3884299 0.23440260E-02 -2.2272953 0.54574706
25 2 3.6315139 0.19014595E-02 5.4333867 -1.6855834
26 1 -4.0346078 0.26548191E-03 -6.0131296 2.1907513
27 0 1.5944472 0.16612988E-05 2.4140608  
28 4 0.50405178E-13 0.16668152E-13 0.29402090E-13 -0.58636069E-16
29 3 -0.78967347E-05 0.18486376E-05 -0.51544008E-05 0.20741056E-12
30 2 0.37655193 0.34407043E-01 0.80677627E-01 -0.16328896E-04
31 1 -8.0349315 0.81344511 -1.1624309 0.21506451
32 0 8.9946927 0.48845120 2.4180636  
33 12 0.94888791E-16 -0.11237443E-15 0.21480527E-09 -0.52606005E-16
34 11 -0.44509090E-09 -0.12338758E-15 -0.11566016E-03 0.28501063E-09
35 10 0.60393314E-04 0.62564840E-13 0.62960490E-02 -0.38672578E-04
36 9 -0.20055671E-02 0.85912012E-10 -0.12885789 0.13084700E-02
37 8 0.28697042E-01 0.10381403E-07 1.3966036 -0.19129448E-01
38 7 -0.23229993 0.28493476E-06 -9.1473517 0.15872626
39 6 1.1750436 0.24973161E-05 38.552224 -0.82592201
40 5 -3.8729952 0.80040830E-05 -107.65441 2.8111251
41 4 8.4143451 0.96510929E-05 200.56463 -6.3313915
42 3 -11.897084 0.41099356E-05 -245.77565 9.3152582
43 2 10.487404 0.50788650E-06 189.69676 -8.5734564
44 1 -5.2147174 0.10902359E-07 -83.415737 4.4633233
45 0 1.1135774 0.38882120E-11 15.905642  
46 12 0.21480527E-09 -0.11237443E-15 0.94888791E-16 -0.52606005E-16
47 11 -0.11566016E-03 -0.12338758E-15 -0.44509090E-09 0.28501063E-09
48 10 0.62960490E-02 0.62564840E-13 0.60393314E-04 -0.38672578E-04
49 9 -0.12885789 0.85912012E-10 -0.20055671E-02 0.13084700E-02
50 8 1.3966036 0.10381403E-07 0.28697042E-01 -0.19129448E-01
51 7 -9.1473517 0.28493476E-06 -0.23229993 0.15872626
52 6 38.552224 0.24973161E-05 1.1750436 -0.82592201
53 5 -107.65441 0.80040830E-05 -3.8729952 2.8111251
54 4 200.56463 0.96510929E-05 8.4143451 -6.3313915
55 3 -245.77565 0.41099356E-05 -11.897084 9.3152582
56 2 189.69676 0.50788650E-06 10.487404 -8.5734564
57 1 -83.415737 0.10902359E-07 -5.2147174 4.4633233
58 0 15.905642 0.38882120E-11 1.1135774  
59 5 -0.27590492E-07 0.65241430E-08 -0.27590492E-07 0.17331255E-13
60 4 0.68608714E-03 0.11323974E-03 0.68608714E-03 -0.15705033E-07
61 3 -0.21538511 0.37821720E-01 -0.21538511 0.25667047E-03
62 2 5.0173519 0.62258424 5.0173519 -0.50236511E-01
63 1 -19.904252 0.86481321 -19.904252 0.58144210
64 0 16.688993 0.62060609E-01 16.688993  
65 4 0.75441920E-10 0.23883683E-10 0.47514224E-10 -0.69373194E-20
66 3 -0.33730907E-03 0.89366797E-04 -0.22574866E-03 0.77828620E-10
67 2 0.58624422 0.18542418 0.49024360 -0.17301269E-03
68 1 -11.299243 2.8799011 -8.6239668 0.15905732
69 0 15.219762 1.4410112 12.640375  
70 5 -0.47059848E-07 0.10808286E-07 -0.47059848E-07 0.33552267E-09
71 4 0.23241354E-03 0.64872557E-04 0.23241354E-03 -0.29116876E-05
72 3 -0.69106029E-01 0.14208819E-01 -0.69106029E-01 0.18005536E-02
73 2 1.8030591 0.23437818 1.8030591 -0.90752678E-01
74 1 -7.5310044 0.40520073 -7.5310044 0.70046896
75 0 6.5027572 0.52085640E-01 6.5027572  
76 6 0.97988530E-11 0.43917118E-12 0.24496810E-11 -0.34892153E-15
77 5 -0.75005310E-05 0.16499726E-06 -0.28271466E-05 0.19166609E-11
78 4 0.32354224E-01 0.66949565E-03 0.10283773E-01 -0.11111676E-05
79 3 -1.8201547 0.67148336E-01 -0.62076152 0.38788549E-02
80 2 21.173821 0.53241617 7.5279938 -0.97325542E-01
81 1 -64.420211 0.46601667 -21.697519 0.64629334
82 0 46.121323 0.20873329E-01 15.867130  
83 5 -0.15664505E-06 0.43005807E-07 -0.15664505E-06 0.11899247E-09
84 4 0.10791049E-02 0.34140917E-03 0.10791049E-02 -0.15677434E-05
85 3 -0.39592122 0.90314630E-01 -0.39592122 0.13116776E-02
86 2 11.651569 1.6702487 11.651569 -0.78737360E-01
87 1 -51.506798 3.1050242 -51.506798 0.66829999
88 0 45.538973 0.42297268 45.538973  
89 8 0.10972129E-06 0.13118744E-13 0.57415395E-12 -0.16121901E-12
90 7 -0.25702593E-04 0.79302418E-09 -0.11209345E-05 0.31491488E-06
91 6 0.16732899E-02 0.55842834E-06 0.21835020E-03 -0.62999473E-04
92 5 -0.40973943E-01 0.43793696E-04 -0.11788181E-01 0.36016799E-02
93 4 0.43752526 0.66464187E-03 0.21386917 -0.72376639E-01
94 3 -2.2272953 0.23440260E-02 -1.3884299 0.54574706
95 2 5.4333867 0.19014595E-02 3.6315139 -1.6855834
96 1 -6.0131296 0.26548191E-03 -4.0346078 2.1907513
97 0 2.4140608 0.16612988E-05 1.5944472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {Btu/h-ft2-F} SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 EXTERIOR WINDOW 12 1 VerySmooth 0.320 0.335 0.248 0.883
2 INTERIOR WINDOW 13 1 VerySmooth 0.320 0.335 0.248 0.883
3 WINDOW_W_BLINDS 18 2 VerySmooth 0.320 0.309 4.642E-002 0.133
4 TDD DOME 22 1 VerySmooth 1.071 0.929 0.920 0.920
5 TDD DIFFUSER 23 1 VerySmooth 1.077 0.906 0.900 0.900


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {ft} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLASS SpectralAverage   0.13182 0.24698 0.54906 0.54906 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.10671 1.00000 No
2 GLASS SpectralAverage   0.13182 0.24698 0.54906 0.54906 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.10671 1.00000 No
3 GLASS SpectralAverage   0.13182 0.24698 0.54906 0.54906 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.10671 1.00000 No
4 CLEAR ACRYLIC PLASTIC SpectralAverage   0.00984 0.92000 5.00000E-002 5.00000E-002 0.92000 5.00000E-002 5.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No
5 DIFFUSING ACRYLIC PLASTIC SpectralAverage   0.00722 0.90000 8.00000E-002 8.00000E-002 0.90000 8.00000E-002 8.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No


WindowMaterial:Blind

Material Name Slat Width {ft} Slat Separation {ft} Slat Thickness {ft} Slat Angle {deg} Slat Beam Solar Transmittance Slat Beam Solar Front Reflectance Blind To Glass Distance {ft}
1 INT_BLIND 0.0820 0.0615 0.0033 45.000 0.000 0.500 0.164


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 20 15000. SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Water Heater Information

Type Name Volume {ft3} Maximum Capacity {Btu/h} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 6.9509 36002.1 0.821 0.5868
2 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 6.9509 36002.1 0.821 0.5868
3 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 6.9509 36002.1 0.821 0.5868
4 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 6.9509 36002.1 0.821 0.5868
5 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 6.9509 36002.1 0.821 0.5868
6 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 6.9509 36002.1 0.821 0.5868
7 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 6.9509 36002.1 0.821 0.5868
8 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 6.9509 36002.1 0.821 0.5868
9 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 6.9509 36002.1 0.821 0.5868
10 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 6.9509 36002.1 0.821 0.5868
11 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 6.9509 36002.1 0.821 0.5868
12 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 6.9509 36002.1 0.821 0.5868
13 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 6.9509 36002.1 0.821 0.5868
14 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 6.9509 36002.1 0.821 0.5868
15 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 6.9509 36002.1 0.821 0.5868
16 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR 6.9509 36002.1 0.821 0.5868
17 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR 6.9509 36002.1 0.821 0.5868
18 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR 6.9509 36002.1 0.821 0.5868


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
2 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
3 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
4 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
5 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
6 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
7 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
8 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
9 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
10 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
11 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
12 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
13 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
14 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
15 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
16 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
17 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
18 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
19 ATTICVENT ALWAYS_AVAIL ATTIC 7802.66 0.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
20 CRAWLVENT ALWAYS_AVAIL CRAWLSPACE 7794.37 0.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/person Area {ft3/min-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {psi} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{F}/Schedule Maximum Indoor Temperature{F}/Schedule Delta Temperature{F}/Schedule Minimum Outdoor Temperature{F}/Schedule Maximum Outdoor Temperature{F}/Schedule Maximum WindSpeed{ft/min}
1 VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
2 VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
3 VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
4 VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
5 VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
6 VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
7 VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
8 VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
9 VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
10 VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
11 VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
12 VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
13 VENTILATION_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
14 VENTILATION_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
15 VENTILATION_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
16 VENTILATION_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
17 VENTILATION_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
18 VENTILATION_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CRAWLSPACE Mixing/Well-Stirred
2 BREEZEWAY Mixing/Well-Stirred
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
15 ATTIC Mixing/Well-Stirred
16 LIVING_UNIT3_BACKROW_TOPFLOOR Mixing/Well-Stirred
17 LIVING_UNIT3_FRONTROW_TOPFLOOR Mixing/Well-Stirred
18 LIVING_UNIT1_FRONTROW_TOPFLOOR Mixing/Well-Stirred
19 LIVING_UNIT2_BACKROW_TOPFLOOR Mixing/Well-Stirred
20 LIVING_UNIT2_FRONTROW_TOPFLOOR Mixing/Well-Stirred
21 LIVING_UNIT1_BACKROW_TOPFLOOR Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {Btu/h} User Des Load {Btu/h} Calc Des Air Flow Rate {ft3/min} User Des Air Flow Rate {ft3/min} Design Day Name Date/Time of Peak Temperature at Peak {F} Humidity Ratio at Peak {lbWater/lbDryAir} Floor Area {ft2} # Occupants Calc Outdoor Air Flow Rate {ft3/min} Calc DOAS Heat Addition Rate {Btu/h}
1 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Cooling 10258.19776 10258.19776 530.40248 530.40248 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 90.56300 0.00570 1200.55323 2.00000 44.99491 0.00000
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Heating 5779.24891 5779.24891 127.91164 127.91164 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Cooling 4888.46637 4888.46637 252.77539 252.77539 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 85.70300 0.00569 1200.55323 2.00000 44.99491 0.00000
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Heating 3983.41317 3983.41317 88.16545 88.16545 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Cooling 7183.74518 7183.74518 371.44063 371.44063 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 87.76850 0.00569 1200.55323 2.00000 44.99491 0.00000
6 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Heating 5781.79218 5781.79218 127.96799 127.96799 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
7 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Cooling 10074.63635 10074.63635 520.93214 520.93214 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 90.15800 0.00570 1200.55323 2.00000 44.99491 0.00000
8 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Heating 5782.21298 5782.21298 127.97731 127.97731 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
9 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Cooling 4928.56446 4928.56446 254.83048 254.83048 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 85.70300 0.00569 1200.55323 2.00000 44.99491 0.00000
10 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Heating 3983.80807 3983.80807 88.17414 88.17414 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
11 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Cooling 7042.44808 7042.44808 364.13131 364.13131 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 86.55350 0.00569 1200.55323 2.00000 44.99491 0.00000
12 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Heating 5779.65627 5779.65627 127.92075 127.92075 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
13 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Cooling 9921.68670 9921.68670 513.02960 513.02960 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 90.15800 0.00570 1200.55323 2.00000 44.99491 0.00000
14 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Heating 3953.35986 3953.35986 87.50317 87.50317 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
15 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Cooling 4771.08029 4771.08029 246.69488 246.69488 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 85.70300 0.00569 1200.55323 2.00000 44.99491 0.00000
16 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Heating 2165.30546 2165.30546 47.92711 47.92711 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
17 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Cooling 7310.65649 7310.65649 378.00843 378.00843 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 88.37600 0.00569 1200.55323 2.00000 44.99491 0.00000
18 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Heating 3955.65047 3955.65047 87.55380 87.55380 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
19 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Cooling 9755.40250 9755.40250 504.42790 504.42790 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 89.75300 0.00569 1200.55323 2.00000 44.99491 0.00000
20 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Heating 3955.94647 3955.94647 87.56037 87.56037 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
21 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Cooling 4782.74186 4782.74186 247.30929 247.30929 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 85.70300 0.00569 1200.55323 2.00000 44.99491 0.00000
22 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Heating 2165.51591 2165.51591 47.93177 47.93177 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
23 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Cooling 7165.40202 7165.40202 370.48724 370.48724 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 87.16100 0.00569 1200.55323 2.00000 44.99491 0.00000
24 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Heating 3953.58325 3953.58325 87.50804 87.50804 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
25 LIVING_UNIT3_BACKROW_TOPFLOOR Cooling 7213.22161 7213.22161 372.96605 372.96605 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 87.16100 0.00569 1200.55323 2.00000 44.99491 0.00000
26 LIVING_UNIT3_BACKROW_TOPFLOOR Heating 5619.92424 5619.92424 124.38537 124.38537 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
27 LIVING_UNIT3_FRONTROW_TOPFLOOR Cooling 7381.09345 7381.09345 381.65249 381.65249 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 88.37600 0.00569 1200.55323 2.00000 44.99491 0.00000
28 LIVING_UNIT3_FRONTROW_TOPFLOOR Heating 5619.67445 5619.67445 124.37986 124.37986 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
29 LIVING_UNIT1_FRONTROW_TOPFLOOR Cooling 10571.29888 10571.29888 546.61010 546.61010 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 90.15800 0.00570 1200.55323 2.00000 44.99491 0.00000
30 LIVING_UNIT1_FRONTROW_TOPFLOOR Heating 5618.04010 5618.04010 124.34363 124.34363 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
31 LIVING_UNIT2_BACKROW_TOPFLOOR Cooling 5650.81932 5650.81932 292.18217 292.18217 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 85.70300 0.00569 1200.55323 2.00000 44.99491 0.00000
32 LIVING_UNIT2_BACKROW_TOPFLOOR Heating 3823.69833 3823.69833 84.63050 84.63050 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
33 LIVING_UNIT2_FRONTROW_TOPFLOOR Cooling 5505.58112 5505.58112 284.68217 284.68217 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 85.70300 0.00569 1200.55323 2.00000 44.99491 0.00000
34 LIVING_UNIT2_FRONTROW_TOPFLOOR Heating 3821.83705 3821.83705 84.58918 84.58918 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000
35 LIVING_UNIT1_BACKROW_TOPFLOOR Cooling 10600.60475 10600.60475 548.11434 548.11434 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 89.75300 0.00569 1200.55323 2.00000 44.99491 0.00000
36 LIVING_UNIT1_BACKROW_TOPFLOOR Heating 5621.63734 5621.63734 124.42329 124.42329 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 17.78000 0.00234 1200.55323 2.00000 44.99491 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [ft3/min] User Des Air Flow Rate [ft3/min] Design Day Name Date/Time of Peak
1 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Cooling Sensible 3144.92 530.40248 530.40248 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Heating Sensible 2305.77 127.91164 127.91164 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
3 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Cooling Sensible 1537.28 252.77539 252.77539 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Heating Sensible 1787.11 88.16545 88.16545 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
5 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Cooling Sensible 2224.32 371.44063 371.44063 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Heating Sensible 2306.50 127.96799 127.96799 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
7 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Cooling Sensible 3087.16 520.93214 520.93214 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Heating Sensible 2306.62 127.97731 127.97731 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
9 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Cooling Sensible 1548.86 254.83048 254.83048 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Heating Sensible 1787.23 88.17414 88.17414 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
11 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Cooling Sensible 2169.25 364.13131 364.13131 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Heating Sensible 2305.89 127.92075 127.92075 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
13 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Cooling Sensible 3043.00 513.02960 513.02960 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Heating Sensible 1778.45 87.50317 87.50317 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
15 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Cooling Sensible 1503.39 246.69488 246.69488 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Heating Sensible 1262.04 47.92711 47.92711 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
17 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Cooling Sensible 2268.10 378.00843 378.00843 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
18 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Heating Sensible 1779.11 87.55380 87.55380 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
19 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Cooling Sensible 2990.23 504.42790 504.42790 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
20 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Heating Sensible 1779.20 87.56037 87.56037 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
21 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Cooling Sensible 1506.76 247.30929 247.30929 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
22 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Heating Sensible 1262.10 47.93177 47.93177 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
23 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Cooling Sensible 2211.89 370.48724 370.48724 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
24 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Heating Sensible 1778.52 87.50804 87.50804 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
25 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Cooling Sensible 3230.58 546.61010 546.61010 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
26 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Heating Sensible 2259.21 124.34363 124.34363 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
27 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Cooling Sensible 1715.48 284.68217 284.68217 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
28 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Heating Sensible 1740.45 84.58918 84.58918 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
29 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Cooling Sensible 2288.44 381.65249 381.65249 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
30 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Heating Sensible 2259.68 124.37986 124.37986 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
31 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Cooling Sensible 3234.29 548.11434 548.11434 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
32 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Heating Sensible 2260.25 124.42329 124.42329 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
33 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Cooling Sensible 1757.42 292.18217 292.18217 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
34 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Heating Sensible 1740.98 84.63050 84.63050 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
35 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Cooling Sensible 2225.70 372.96605 372.96605 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
36 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Heating Sensible 2259.75 124.38537 124.38537 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
2 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
3 Fan:OnOff OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
4 Fan:OnOff OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
5 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
6 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 530.40248
7 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
8 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
9 Fan:OnOff OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
10 Fan:OnOff OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
11 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
12 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 252.77539
13 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
14 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
15 Fan:OnOff OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
16 Fan:OnOff OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
17 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
18 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 371.44063
19 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
20 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
21 Fan:OnOff OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
22 Fan:OnOff OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
23 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
24 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 520.93214
25 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
26 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
27 Fan:OnOff OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
28 Fan:OnOff OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
29 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
30 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 254.83048
31 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
32 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
33 Fan:OnOff OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
34 Fan:OnOff OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
35 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
36 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 364.13131
37 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
38 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
39 Fan:OnOff OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
40 Fan:OnOff OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
41 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
42 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 513.02960
43 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
44 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
45 Fan:OnOff OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
46 Fan:OnOff OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
47 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
48 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 246.69488
49 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
50 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
51 Fan:OnOff OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
52 Fan:OnOff OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
53 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
54 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 378.00843
55 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
56 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
57 Fan:OnOff OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
58 Fan:OnOff OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
59 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
60 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 504.42790
61 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
62 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
63 Fan:OnOff OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
64 Fan:OnOff OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
65 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
66 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 247.30929
67 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
68 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
69 Fan:OnOff OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
70 Fan:OnOff OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
71 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
72 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 370.48724
73 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
74 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
75 Fan:OnOff OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
76 Fan:OnOff OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
77 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
78 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 372.96605
79 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
80 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
81 Fan:OnOff OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
82 Fan:OnOff OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
83 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
84 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 381.65249
85 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
86 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
87 Fan:OnOff OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
88 Fan:OnOff OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
89 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
90 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 546.61010
91 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
92 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
93 Fan:OnOff OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
94 Fan:OnOff OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
95 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
96 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 292.18217
97 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
98 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
99 Fan:OnOff OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
100 Fan:OnOff OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
101 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
102 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 284.68217
103 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
104 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
105 Fan:OnOff OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
106 Fan:OnOff OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
107 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
108 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 548.11434
109 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 530.40248
110 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 530.40248
111 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 530.40248
112 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 530.40248
113 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 530.40248
114 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 530.40248
115 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
116 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
117 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 252.77539
118 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 252.77539
119 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 252.77539
120 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 252.77539
121 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 252.77539
122 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 252.77539
123 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
124 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
125 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 371.44063
126 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 371.44063
127 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 371.44063
128 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 371.44063
129 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 371.44063
130 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 371.44063
131 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
132 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
133 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 520.93214
134 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 520.93214
135 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 520.93214
136 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 520.93214
137 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 520.93214
138 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 520.93214
139 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
140 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
141 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 254.83048
142 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 254.83048
143 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 254.83048
144 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 254.83048
145 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 254.83048
146 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 254.83048
147 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
148 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
149 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 364.13131
150 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 364.13131
151 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 364.13131
152 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 364.13131
153 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 364.13131
154 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 364.13131
155 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
156 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
157 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 513.02960
158 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 513.02960
159 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 513.02960
160 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 513.02960
161 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 513.02960
162 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 513.02960
163 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
164 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
165 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 246.69488
166 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 246.69488
167 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 246.69488
168 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 246.69488
169 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 246.69488
170 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 246.69488
171 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
172 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
173 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 378.00843
174 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 378.00843
175 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 378.00843
176 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 378.00843
177 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 378.00843
178 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 378.00843
179 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
180 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
181 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 504.42790
182 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 504.42790
183 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 504.42790
184 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 504.42790
185 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 504.42790
186 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 504.42790
187 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
188 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
189 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 247.30929
190 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 247.30929
191 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 247.30929
192 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 247.30929
193 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 247.30929
194 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 247.30929
195 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
196 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
197 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 370.48724
198 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 370.48724
199 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 370.48724
200 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 370.48724
201 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 370.48724
202 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 370.48724
203 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
204 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
205 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 546.61010
206 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 546.61010
207 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 546.61010
208 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 546.61010
209 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 546.61010
210 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 546.61010
211 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
212 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
213 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 284.68217
214 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 284.68217
215 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 284.68217
216 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 284.68217
217 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 284.68217
218 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 284.68217
219 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
220 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
221 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 381.65249
222 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 381.65249
223 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 381.65249
224 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 381.65249
225 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 381.65249
226 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 381.65249
227 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
228 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
229 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 548.11434
230 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 548.11434
231 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 548.11434
232 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 548.11434
233 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 548.11434
234 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 548.11434
235 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
236 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
237 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 292.18217
238 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 292.18217
239 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 292.18217
240 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 292.18217
241 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 292.18217
242 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 292.18217
243 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
244 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
245 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 372.96605
246 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 372.96605
247 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 372.96605
248 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 372.96605
249 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 372.96605
250 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 372.96605
251 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
252 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
253 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 530.40248
254 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 252.77539
255 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 371.44063
256 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 520.93214
257 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 254.83048
258 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 364.13131
259 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 513.02960
260 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 246.69488
261 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 378.00843
262 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 504.42790
263 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 247.30929
264 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 370.48724
265 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 546.61010
266 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 284.68217
267 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 381.65249
268 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 548.11434
269 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 292.18217
270 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 372.96605
271 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 530.40248
272 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.17835
273 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
274 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 530.40248
275 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 530.40248
276 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 530.40248
277 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.17835
278 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Rated Capacity [Btu/h] 25788.02746
279 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.64706
280 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 362.20294
281 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
282 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 530.40248
283 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 252.77539
284 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.56154
285 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
286 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 252.77539
287 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 252.77539
288 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 252.77539
289 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.56154
290 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Rated Capacity [Btu/h] 13426.15507
291 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Water Flow Rate [gal/min] 1.37815
292 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 182.90401
293 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
294 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 252.77539
295 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 371.44063
296 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.82518
297 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
298 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 371.44063
299 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 371.44063
300 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 371.44063
301 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.82518
302 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Rated Capacity [Btu/h] 18710.04985
303 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Water Flow Rate [gal/min] 1.92052
304 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 259.63764
305 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
306 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 371.44063
307 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 520.93214
308 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.15727
309 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
310 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 520.93214
311 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 520.93214
312 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 520.93214
313 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.15727
314 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Rated Capacity [Btu/h] 25365.49852
315 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.60369
316 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 356.08339
317 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
318 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 520.93214
319 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 254.83048
320 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.56615
321 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
322 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 254.83048
323 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 254.83048
324 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 254.83048
325 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.56615
326 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Rated Capacity [Btu/h] 13518.46963
327 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Water Flow Rate [gal/min] 1.38763
328 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 184.24666
329 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
330 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 254.83048
331 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 364.13131
332 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.80895
333 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
334 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 364.13131
335 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 364.13131
336 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 364.13131
337 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.80895
338 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Rated Capacity [Btu/h] 18384.78454
339 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Water Flow Rate [gal/min] 1.88713
340 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 254.92037
341 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
342 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 364.13131
343 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 513.02960
344 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.13971
345 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
346 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 513.02960
347 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 513.02960
348 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 513.02960
349 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.13971
350 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Rated Capacity [Btu/h] 25012.70666
351 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.56747
352 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 350.84870
353 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
354 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 513.02960
355 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 246.69488
356 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.54806
357 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
358 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 246.69488
359 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 246.69488
360 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 246.69488
361 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.54806
362 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Rated Capacity [Btu/h] 13155.58657
363 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Water Flow Rate [gal/min] 1.35038
364 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 178.85615
365 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
366 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 246.69488
367 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 378.00843
368 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.83977
369 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
370 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 378.00843
371 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 378.00843
372 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 378.00843
373 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.83977
374 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Rated Capacity [Btu/h] 19001.68854
375 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Water Flow Rate [gal/min] 1.95046
376 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 263.77320
377 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
378 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 378.00843
379 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 504.42790
380 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.12061
381 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
382 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 504.42790
383 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 504.42790
384 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 504.42790
385 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.12061
386 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Rated Capacity [Btu/h] 24629.96652
387 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.52819
388 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 345.30694
389 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
390 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 504.42790
391 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 247.30929
392 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.54940
393 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
394 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 247.30929
395 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 247.30929
396 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 247.30929
397 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.54940
398 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Rated Capacity [Btu/h] 13182.43803
399 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Water Flow Rate [gal/min] 1.35313
400 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 179.24655
401 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
402 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 247.30929
403 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 370.48724
404 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.82308
405 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
406 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 370.48724
407 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 370.48724
408 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 370.48724
409 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.82308
410 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Rated Capacity [Btu/h] 18667.31534
411 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Water Flow Rate [gal/min] 1.91614
412 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 258.92600
413 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
414 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 370.48724
415 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 546.61010
416 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.21432
417 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
418 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 546.61010
419 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 546.61010
420 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 546.61010
421 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.21432
422 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Rated Capacity [Btu/h] 26508.88951
423 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.72104
424 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 372.64651
425 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
426 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 546.61010
427 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 284.68217
428 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.63243
429 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
430 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 284.68217
431 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 284.68217
432 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 284.68217
433 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.63243
434 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Rated Capacity [Btu/h] 14846.84534
435 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Water Flow Rate [gal/min] 1.52398
436 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 203.55896
437 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
438 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 284.68217
439 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 381.65249
440 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.84785
441 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
442 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 381.65249
443 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 381.65249
444 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 381.65249
445 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.84785
446 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Rated Capacity [Btu/h] 19164.36393
447 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Water Flow Rate [gal/min] 1.96715
448 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 266.22857
449 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
450 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 381.65249
451 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 548.11434
452 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.21769
453 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
454 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 548.11434
455 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 548.11434
456 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 548.11434
457 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.21769
458 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Rated Capacity [Btu/h] 26576.41790
459 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.72799
460 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 373.62436
461 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
462 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 548.11434
463 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 292.18217
464 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.64911
465 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
466 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 292.18217
467 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 292.18217
468 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 292.18217
469 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.64911
470 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Rated Capacity [Btu/h] 15181.20714
471 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Water Flow Rate [gal/min] 1.55830
472 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 208.41631
473 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
474 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 292.18217
475 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 372.96605
476 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.82857
477 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80066
478 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 372.96605
479 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 372.96605
480 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 372.96605
481 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.82857
482 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Rated Capacity [Btu/h] 18777.91453
483 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Water Flow Rate [gal/min] 1.92749
484 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 260.62460
485 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
486 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 372.96605
487 PlantLoop BOILER LOOP Maximum Loop Flow Rate [ft3/min] 4.80021
488 PlantLoop BOILER LOOP Plant Loop Volume [ft3] 9.60276
489 Pump:VariableSpeed BOILER CIRC PUMP Design Flow Rate [ft3/min] 4.80021
490 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [Btu/h] 0.349898E+06
491 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [gal/min] 35.91588
492 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
493 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
494 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
495 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
496 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
497 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
498 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
499 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
500 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
501 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
502 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
503 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
504 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
505 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
506 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
507 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
508 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
509 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
510 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
511 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
512 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
513 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
514 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
515 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
516 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
517 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
518 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
519 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
520 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
521 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
522 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
523 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
524 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
525 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
526 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
527 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
528 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
529 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
530 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
531 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
532 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
533 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
534 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
535 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
536 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
537 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
538 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
539 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
540 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
541 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
542 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
543 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
544 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
545 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
546 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
547 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
548 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
549 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
550 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
551 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
552 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
553 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
554 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
555 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
556 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
557 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
558 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
559 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
560 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
561 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
562 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
563 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
564 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
565 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
566 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
567 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
568 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
569 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
570 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
571 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
572 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
573 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
574 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
575 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
576 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
577 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
578 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
579 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
580 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
581 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {ton} Standard Rated Net COP {Btuh/Btuh} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1.1 3.26 11.12 11.77 11.32 11.27
2 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 0.5 3.26 11.12 11.77 11.32 11.27
3 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 0.8 3.26 11.12 11.77 11.32 11.27
4 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 1.1 3.26 11.12 11.77 11.32 11.27
5 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 0.5 3.26 11.12 11.77 11.32 11.27
6 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 0.8 3.26 11.12 11.77 11.32 11.27
7 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 1.1 3.26 11.12 11.77 11.32 11.27
8 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 0.5 3.26 11.12 11.77 11.32 11.27
9 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 0.8 3.26 11.12 11.77 11.32 11.27
10 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 1.1 3.26 11.12 11.77 11.32 11.27
11 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 0.5 3.26 11.12 11.77 11.32 11.27
12 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 0.8 3.26 11.12 11.77 11.32 11.27
13 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 1.2 3.26 11.12 11.77 11.32 11.27
14 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 0.6 3.26 11.12 11.77 11.32 11.27
15 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 0.8 3.26 11.12 11.77 11.32 11.27
16 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 1.2 3.26 11.12 11.77 11.32 11.27
17 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 0.6 3.26 11.12 11.77 11.32 11.27
18 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 0.8 3.26 11.12 11.77 11.32 11.27


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {Btu/h}
1 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 27188.56
2 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 13547.52
3 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 19387.46
4 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 26723.19
5 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 13649.77
6 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 19028.55
7 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 26328.97
8 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 13242.79
9 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 19705.05
10 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 25907.49
11 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 13272.51
12 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 19336.21
13 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 27982.60
14 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 15120.11
15 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 19888.82
16 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR 28056.98
17 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR 15489.87
18 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR 19462.46


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB SizingPeriod:DesignDay 12/21 12/21 WinterDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
2 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB SizingPeriod:DesignDay 07/21 07/21 SummerDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
3 ANNUAL WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day Yes Yes No Yes Yes Clark and Allen


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 No SizingPeriod:DesignDay    
2 No SizingPeriod:DesignDay    
3 No      


Environment:WarmupDays

NumberofWarmupDays
1 6
2 6
3 25


Environment:Design Day Data

Max Dry-Bulb Temp {F} Temp Range {dC} Temp Range Ind Type Hum Ind Type Hum Ind Value at Max Temp Hum Ind Units Pressure {psi} Wind Direction {deg CW from N} Wind Speed {ft/min} Clearness Rain Snow
1 17.78 0.00 DefaultMultipliers Wetbulb -7.90 {C} 12. 0 630.0 0.00 No No
2 95.18 13.50 DefaultMultipliers Wetbulb 15.70 {C} 12. 220 866.2 0.00 No No


Environment:Design Day Misc

DayOfYear ASHRAE A Coeff ASHRAE B Coeff ASHRAE C Coeff Solar Constant-Annual Variation Eq of Time {minutes} Solar Declination Angle {deg} Solar Model
1 355 1232.8 0.1424 5.7719E-002 1.0 2.45 -24.. ASHRAEClearSky
2 202 1084.4 0.2082 0.1365 1.0 -6.23 20.6 ASHRAETau


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaF} Std Dev Warmup Temperature Difference {deltaF} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {Btu/h} Std Dev Warmup Load Difference {Btu/h} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CRAWLSPACE SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000296340 0.000247605 Pass Pass 0.000000000 0.000000000 Pass Pass
2 BREEZEWAY SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000133332 0.000049133 Pass Pass 0.000000000 0.000000000 Pass Pass
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000001599 0.000002726 Pass Pass 0.016912578 0.029743595 Pass Pass
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000013746 0.000024478 Pass Pass 0.025531720 0.044795448 Pass Pass
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000003109 0.000005358 Pass Pass 0.016903762 0.029727035 Pass Pass
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000001631 0.000002751 Pass Pass 0.016902595 0.029721473 Pass Pass
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000013665 0.000024330 Pass Pass 0.025528065 0.044781652 Pass Pass
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000003536 0.000006046 Pass Pass 0.016909640 0.029731836 Pass Pass
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000000787 0.000001348 Pass Pass 0.024763387 0.042999445 Pass Pass
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000026313 0.000098205 Pass Pass 0.052163346 0.092007185 Pass Pass
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000030401 0.000162628 Pass Pass 0.024796667 0.043146512 Pass Pass
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000003030 0.000005483 Pass Pass 0.024743618 0.042960979 Pass Pass
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000051048 0.000146731 Pass Pass 0.052223895 0.091771984 Pass Pass
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000001910 0.000003362 Pass Pass 0.024759655 0.042992127 Pass Pass
15 ATTIC SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000053555 0.000044973 Pass Pass 0.000000000 0.000000000 Pass Pass
16 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000001873 0.000002921 Pass Pass 0.016949628 0.027842846 Pass Pass
17 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000004802 0.000008010 Pass Pass 0.016951223 0.027842791 Pass Pass
18 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000001469 0.000002420 Pass Pass 0.016958015 0.027857115 Pass Pass
19 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000050992 0.000121610 Pass Pass 0.025991082 0.042691773 Pass Pass
20 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000047115 0.000115801 Pass Pass 0.025983565 0.042765527 Pass Pass
21 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 0.000001410 0.000002291 Pass Pass 0.016945169 0.027835594 Pass Pass
22 CRAWLSPACE SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.243394442 0.143444613 Pass Pass 0.000000000 0.000000000 Pass Pass
23 BREEZEWAY SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.105752827 0.057167631 Pass Pass 0.000000000 0.000000000 Pass Pass
24 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000251222 0.000993536 Pass Pass 0.099832420 0.043791574 Pass Pass
25 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000258520 0.000980034 Pass Pass 0.063805251 0.049816314 Pass Pass
26 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000235115 0.000987925 Pass Pass 0.080780770 0.082857219 Pass Pass
27 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000250948 0.000993535 Pass Pass 0.099554751 0.045174816 Pass Pass
28 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000236571 0.000976127 Pass Pass 0.063864905 0.045551577 Pass Pass
29 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000222816 0.000980538 Pass Pass 0.081006889 0.086352622 Pass Pass
30 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000246733 0.000971935 Pass Pass 0.085568820 0.037588762 Pass Pass
31 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000274905 0.000969793 Pass Pass 0.050280888 0.043070967 Pass Pass
32 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000237151 0.000964443 Pass Pass 0.069759033 0.067999430 Pass Pass
33 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000252350 0.000972505 Pass Pass 0.085353798 0.038221897 Pass Pass
34 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000255046 0.000962381 Pass Pass 0.050407610 0.040085366 Pass Pass
35 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000213635 0.000958997 Pass Pass 0.070014979 0.071097863 Pass Pass
36 ATTIC SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.591687164 0.434925798 Pass Pass 0.000000000 0.000000000 Pass Pass
37 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000215541 0.000939213 Pass Pass 0.069141082 0.069476063 Pass Pass
38 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000267782 0.000977389 Pass Pass 0.068220487 0.067271725 Pass Pass
39 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000244755 0.000957494 Pass Pass 0.085745399 0.036058958 Pass Pass
40 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000247995 0.000945910 Pass Pass 0.055690615 0.036202928 Pass Pass
41 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000254574 0.000947184 Pass Pass 0.054157509 0.040497874 Pass Pass
42 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 0.000241643 0.000956339 Pass Pass 0.086532532 0.035500372 Pass Pass
43 CRAWLSPACE RunPeriod: ANNUAL 0.344502055 0.251897575 Pass Pass 0.000000000 0.000000000 Pass Pass
44 BREEZEWAY RunPeriod: ANNUAL 0.081757328 0.057439336 Pass Pass 0.000000000 0.000000000 Pass Pass
45 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.049697144 0.091703663 Pass Pass 1.715868072 0.149796E+02 Fail Pass
46 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.057694222 0.095991093 Pass Pass 0.786219344 2.847813774 Pass Pass
47 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.077173351 0.124088385 Pass Pass 0.826043539 2.700251178 Pass Pass
48 LIVING_UNIT1_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.134000343 0.340339347 Pass Pass 2.694274498 0.139805E+02 Pass Pass
49 LIVING_UNIT2_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.035063555 0.065999428 Pass Pass 1.064722347 2.825386274 Fail Pass
50 LIVING_UNIT3_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.072333481 0.121103106 Pass Pass 0.817334053 1.523246833 Pass Pass
51 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.057548616 0.103540568 Pass Pass 0.660504460 3.269484235 Pass Pass
52 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.085123882 0.099836857 Pass Pass 1.353647451 4.015282799 Pass Pass
53 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.121132092 0.199110194 Pass Pass 0.707663374 1.551505316 Pass Pass
54 LIVING_UNIT1_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.122011414 0.256378022 Pass Pass 2.514864690 0.131121E+02 Pass Pass
55 LIVING_UNIT2_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.068714186 0.091451414 Pass Pass 1.371348718 3.222096594 Pass Pass
56 LIVING_UNIT3_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.107430556 0.163138299 Pass Pass 1.495095587 3.613016259 Fail Fail
57 ATTIC RunPeriod: ANNUAL 0.610079558 0.568451015 Pass Pass 0.000000000 0.000000000 Pass Pass
58 LIVING_UNIT3_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.051782915 0.103172820 Pass Pass 0.909119355 2.210983593 Pass Fail
59 LIVING_UNIT3_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.080853207 0.126392468 Pass Pass 0.665736010 2.618951157 Pass Pass
60 LIVING_UNIT1_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.086974414 0.126393807 Pass Pass 3.657523368 0.200441E+02 Fail Pass
61 LIVING_UNIT2_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.030713273 0.058199719 Pass Pass 1.483418416 5.804458368 Pass Pass
62 LIVING_UNIT2_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.060132410 0.092107499 Pass Pass 0.556412102 2.212807664 Fail Pass
63 LIVING_UNIT1_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.118492910 0.271302251 Pass Pass 0.876353377 2.672177674 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [kBtu] 2715782.72 349360.67 0.00 0.00 382196.96 3447353.04



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 17.78 0.00 17.78 Wetbulb [F] 629.95 0.00
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 95.18 24.30 60.26 Wetbulb [F] 866.18 220.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF CRAWL WALL 0.30 0.776 2.276 59.96 59.96 180.00 90.00 S
BGWALL_LOWER_LDF CRAWL WALL 0.30 0.893 2.276 239.83 239.83 180.00 90.00 S
BGWALL_UPPER_SDR CRAWL WALL 0.30 0.776 2.276 32.56 32.56 90.00 90.00 E
BGWALL_LOWER_SDR CRAWL WALL 0.30 0.893 2.276 130.22 130.22 90.00 90.00 E
BGWALL_UPPER_LDB CRAWL WALL 0.30 0.776 2.276 59.96 59.96 0.00 90.00 N
BGWALL_LOWER_LDB CRAWL WALL 0.30 0.893 2.276 239.83 239.83 0.00 90.00 N
BGWALL_UPPER_SDL CRAWL WALL 0.30 0.776 2.276 32.56 32.56 270.00 90.00 W
BGWALL_LOWER_SDL CRAWL WALL 0.30 0.893 2.276 130.22 130.22 270.00 90.00 W
BGFLOOR INTERIOR FLOOR 0.30 0.235 0.300 7794.39 7794.39 0.00 180.00  
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.39 599.39 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.39 599.39 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.39 599.39 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S


Opaque Interior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
iz-FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT1_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT2_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT3_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
BREEZEWAYROOF INTERIOR CEILING 0.30 0.022 0.022 599.39 599.39 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
iz-BREEZEWAYROOF ATTIC FLOOR 0.30 0.022 0.022 599.39 599.39 0.00 180.00  
iz-CEILING_UNIT3_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.335 0.883     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.335 0.883     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.335 0.883     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.335 0.883     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.335 0.883     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.335 0.883     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.335 0.883     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.335 0.883     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.335 0.883     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.335 0.883     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.335 0.883     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.335 0.883     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.335 0.883     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.335 0.883     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.335 0.883     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.335 0.883     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.335 0.883     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.335 0.883     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.335 0.883     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.335 0.883     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.335 0.883     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.335 0.883     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.335 0.883     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.335 0.883     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.335 0.883     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.335 0.883     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.335 0.883     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.335 0.883     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.335 0.883     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.335 0.883     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.320 0.335 0.883              
North Total or Average           531.68 0.320 0.335 0.883              
Non-North Total or Average           1595.05 0.320 0.335 0.883              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR


Interior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.14 0.96 0.93 1.00 0.99 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.14 0.96 0.93 1.00 0.99 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.14 0.96 0.93 1.00 0.99 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.14 0.96 0.93 1.00 0.99 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.14 0.96 0.93 1.00 0.99 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.14 0.96 0.93 1.00 0.99 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.14 0.96 0.93 1.00 0.99 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.14 0.96 0.93 1.00 0.99 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.14 0.96 0.93 1.00 0.99 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3110 43219.92 13441.11               12093.82


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 69.87 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 306.04
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
Exterior Lighting Total 1257.69           5508.71



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 349898.33 0.80    


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   14140.23 11321.45 2818.78 0.80 4.07    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   6738.47 5395.20 1343.28 0.80 4.07    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9902.21 7928.26 1973.95 0.80 4.07    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   13887.23 11118.89 2768.35 0.80 4.07    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   6793.75 5439.45 1354.30 0.80 4.07    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9707.45 7772.32 1935.13 0.80 4.07    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13676.53 10950.18 2726.34 0.80 4.07    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   6576.71 5265.68 1311.03 0.80 4.07    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10077.21 8068.37 2008.84 0.80 4.07    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13447.35 10766.69 2680.66 0.80 4.07    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   6592.79 5278.55 1314.24 0.80 4.07    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   9876.99 7908.07 1968.93 0.80 4.07    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   14571.85 11667.03 2904.82 0.80 4.07    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   7589.14 6076.28 1512.85 0.80 4.07    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   10174.24 8146.06 2028.18 0.80 4.07    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   14612.28 11699.40 2912.88 0.80 4.07    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   7789.34 6236.58 1552.76 0.80 4.07    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   9942.84 7960.79 1982.05 0.80 4.07    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   1.1 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.5 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.8 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.1 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.5 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.8 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.1 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.5 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.8 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.1 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.5 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.8 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.2 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.6 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   0.8 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.2 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.6 3.26 11.12 11.77 11.32 11.27
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   0.8 3.26 11.12 11.77 11.32 11.27
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 25788.03 27188.56 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 13426.16 13547.52 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 18710.05 19387.46 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Water 25365.50 26723.20 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Water 13518.47 13649.77 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Water 18384.78 19028.55 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 25012.71 26328.98 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 13155.59 13242.78 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 19001.69 19705.04 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Water 24629.97 25907.49 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Water 13182.44 13272.52 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Water 18667.32 19336.21 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Water 26508.89 27982.61 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Water 14846.85 15120.10 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Water 19164.36 19888.81 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Water 26576.42 28056.97 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Water 15181.21 15489.86 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Water 18777.91 19462.47 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.07 44.99 16.07 0.36 0.00 12.92 Ventilation    
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 530.41 200.07 0.38 1.00 2.09 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 252.77 95.34 0.38 1.00 3.05 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 371.44 140.10 0.38 1.00 2.47 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 520.92 196.49 0.38 1.00 2.10 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 254.84 96.12 0.38 1.00 3.03 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 364.14 137.35 0.38 1.00 2.49 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 513.02 193.51 0.38 1.00 2.12 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 246.70 93.05 0.38 1.00 3.09 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 378.01 142.58 0.38 1.00 2.44 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 504.42 190.26 0.38 1.00 2.13 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 247.30 93.28 0.38 1.00 3.09 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 370.50 139.75 0.38 1.00 2.47 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 546.60 206.17 0.38 1.00 2.06 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 284.68 107.38 0.38 1.00 2.85 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 381.64 143.95 0.38 1.00 2.43 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 548.12 206.75 0.38 1.00 2.06 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 292.19 110.21 0.38 1.00 2.80 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 372.97 140.68 0.38 1.00 2.46 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00


Pumps

Type Control Head [psi] Water Flow [gal/min] Electricity Rate [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh] End Use Subcategory
BOILER CIRC PUMP Pump:VariableSpeed Intermittent 0.00 35.915911 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.59
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.59
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.59
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.59
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.59
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.59
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.59
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.59
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.59
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.59
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.59
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.59
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.59
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.59
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.59
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.59
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.59
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.59



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 10258.20 10258.20 8.54 530.413 530.413 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 75.00 75.00 0.00822 90.56 0.00570 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4888.47 4888.47 4.07 252.766 252.766 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00847 85.70 0.00569 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 7183.75 7183.75 5.98 371.441 371.441 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 75.00 75.00 0.00814 87.77 0.00569 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 10074.64 10074.64 8.39 520.923 520.923 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 75.00 75.00 0.00823 90.16 0.00570 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4928.56 4928.56 4.11 254.840 254.840 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00847 85.70 0.00569 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 7042.45 7042.45 5.87 364.136 364.136 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 75.00 75.00 0.00815 86.55 0.00569 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9921.69 9921.69 8.26 513.019 513.019 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 75.00 75.00 0.00828 90.16 0.00570 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4771.08 4771.08 3.97 246.699 246.699 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00859 85.70 0.00569 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7310.66 7310.66 6.09 378.005 378.005 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 75.00 75.00 0.00820 88.38 0.00569 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 9755.40 9755.40 8.13 504.422 504.422 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 75.00 75.00 0.00829 89.75 0.00569 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4782.74 4782.74 3.98 247.302 247.302 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00859 85.70 0.00569 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7165.40 7165.40 5.97 370.495 370.495 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 75.00 75.00 0.00821 87.16 0.00569 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 7213.22 7213.22 6.01 372.965 372.965 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 75.00 75.00 0.00815 87.16 0.00569 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 7381.09 7381.09 6.15 381.645 381.645 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 75.00 75.00 0.00814 88.38 0.00569 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 10571.30 10571.30 8.81 546.604 546.604 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 75.00 75.00 0.00823 90.16 0.00570 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 5650.82 5650.82 4.71 292.185 292.185 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00843 85.70 0.00569 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 5505.58 5505.58 4.59 284.676 284.676 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00844 85.70 0.00569 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 10600.60 10600.60 8.83 548.120 548.120 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 75.00 75.00 0.00823 89.75 0.00569 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5779.25 5779.25 4.81 127.912 127.912 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00738 17.78 0.00234 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3983.41 3983.41 3.32 88.165 88.165 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00731 17.78 0.00234 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5781.79 5781.79 4.82 127.968 127.968 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00738 17.78 0.00234 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5782.21 5782.21 4.82 127.977 127.977 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00738 17.78 0.00234 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3983.81 3983.81 3.32 88.174 88.174 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00731 17.78 0.00234 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5779.66 5779.66 4.81 127.921 127.921 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00738 17.78 0.00234 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 3953.36 3953.36 3.29 87.503 87.503 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00790 17.78 0.00234 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2165.31 2165.31 1.80 47.927 47.927 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00822 17.78 0.00234 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 3955.65 3955.65 3.29 87.554 87.554 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00790 17.78 0.00234 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3955.95 3955.95 3.30 87.560 87.560 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00790 17.78 0.00234 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2165.52 2165.52 1.80 47.932 47.932 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00822 17.78 0.00234 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3953.58 3953.58 3.29 87.508 87.508 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00790 17.78 0.00234 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 5619.92 5619.92 4.68 124.385 124.385 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00737 17.78 0.00234 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 5619.67 5619.67 4.68 124.380 124.380 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00737 17.78 0.00234 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 5618.04 5618.04 4.68 124.344 124.344 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00737 17.78 0.00234 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 3823.70 3823.70 3.18 84.630 84.630 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00729 17.78 0.00234 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 3821.84 3821.84 3.18 84.589 84.589 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00729 17.78 0.00234 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 5621.64 5621.64 4.68 124.423 124.423 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00737 17.78 0.00234 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min] Adjusted cooling [ft3/min] Adjusted heating [ft3/min] Adjusted main [ft3/min] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 530.41 530.41 127.91 127.91 530.4129 530.4129 530.4129 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 252.77 252.77 88.17 88.17 252.7664 252.7664 252.7664 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 371.44 371.44 127.97 127.97 371.4410 371.4410 371.4410 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 520.92 520.92 127.98 127.98 520.9229 520.9229 520.9229 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 254.84 254.84 88.17 88.17 254.8398 254.8398 254.8398 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 364.14 364.14 127.92 127.92 364.1355 364.1355 364.1355 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 513.02 513.02 87.50 87.50 513.0192 513.0192 513.0192 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 246.70 246.70 47.93 47.93 246.6986 246.6986 246.6986 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 378.01 378.01 87.55 87.55 378.0055 378.0055 378.0055 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 504.42 504.42 87.56 87.56 504.4224 504.4224 504.4224 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 247.30 247.30 47.93 47.93 247.3017 247.3017 247.3017 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 370.50 370.50 87.51 87.51 370.4951 370.4951 370.4951 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 546.60 546.60 124.34 124.34 546.6036 546.6036 546.6036 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 284.68 284.68 84.59 84.59 284.6756 284.6756 284.6756 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 381.64 381.64 124.38 124.38 381.6450 381.6450 381.6450 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 548.12 548.12 124.42 124.42 548.1203 548.1203 548.1203 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 292.19 292.19 84.63 84.63 292.1854 292.1854 292.1854 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 372.97 372.97 124.39 124.39 372.9653 372.9653 372.9653 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 14140.226 11321.446 530.412928 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 15345.59 15339.52 530.412928 77.74 58.02 0.00800279 53.60 49.17 0.00800000 90.56 0.00569540 58.90 8.4830 75.00 0.00819330 36.5372 10253.25 0.00 14146.13 10273.94
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 25788.027 25788.027 530.412928 0.35378306 362.203 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 25788.03 25788.03 530.412928 67.40 52.73 0.00695502 122.00 70.83 0.00800000 17.78 0.00234317 17.78 8.4830 72.00 0.00738251 36.4640 5779.25 0.00 27186.18 27186.18
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 6738.475 5395.195 252.766405 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 7122.25 7122.25 252.766405 78.33 58.17 0.00797520 53.60 49.12 0.00797520 85.70 0.00569125 57.27 17.8010 75.00 0.00838699 37.3895 4824.62 0.00 6741.29 4896.01
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 13426.155 13426.155 252.766405 0.18419192 182.904 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 13426.16 13426.16 252.766405 62.35 49.90 0.00642653 122.00 70.83 0.00800000 17.78 0.00234317 17.78 17.8010 72.00 0.00731082 36.1135 3983.41 0.00 13542.47 13542.47
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 9902.210 7928.256 371.441027 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 10600.91 10600.91 371.441027 77.97 57.87 0.00784714 53.60 48.90 0.00784714 87.77 0.00569301 57.97 12.1136 75.00 0.00814312 36.3160 7172.84 0.00 9906.34 7194.70
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 18710.050 18710.050 371.441027 0.25668108 259.638 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 18710.05 18710.05 371.441027 65.43 51.69 0.00677226 122.00 70.83 0.00800000 17.78 0.00234317 17.78 12.1136 72.00 0.00738273 36.4651 5781.79 0.00 19383.91 19383.91
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 13887.232 11118.885 520.922895 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 15037.78 15010.75 520.922895 77.73 58.03 0.00801269 53.60 49.17 0.00800000 90.16 0.00569506 58.76 8.6376 75.00 0.00823180 36.7068 10074.64 0.00 13893.03 10090.12
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 25365.499 25365.499 520.922895 0.34798643 356.083 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 25365.50 25365.50 520.922895 67.31 52.69 0.00694747 122.00 70.83 0.00800000 17.78 0.00234317 17.78 8.6376 72.00 0.00738277 36.4653 5782.21 0.00 26720.76 26720.76
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 6793.749 5439.451 254.839818 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 7180.70 7180.70 254.839818 78.31 58.17 0.00797840 53.60 49.13 0.00797840 85.70 0.00569125 57.27 17.6562 75.00 0.00844604 37.6493 4906.04 0.00 6796.58 4936.17
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 13518.470 13518.470 254.839818 0.18545837 184.247 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 13518.47 13518.47 254.839818 62.43 49.94 0.00643377 122.00 70.83 0.00800000 17.78 0.00234317 17.78 17.6562 72.00 0.00731087 36.1137 3983.81 0.00 13644.74 13644.74
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 9707.453 7772.324 364.135544 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 10330.28 10330.28 364.135544 77.85 57.82 0.00784690 53.60 48.90 0.00784690 86.55 0.00569198 57.56 12.3567 75.00 0.00814754 36.3354 7029.08 0.00 9711.50 7053.20
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 18384.785 18384.785 364.135544 0.25221880 254.920 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 18384.78 18384.78 364.135544 65.30 51.62 0.00675985 122.00 70.83 0.00800000 17.78 0.00234317 17.78 12.3567 72.00 0.00738254 36.4642 5779.66 0.00 19024.95 19024.95
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 13676.527 10950.184 513.019173 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 14802.86 14687.17 513.019173 77.75 58.10 0.00805554 53.60 49.17 0.00800000 90.16 0.00569506 58.76 8.7706 75.00 0.00826836 36.8678 9913.56 0.00 13682.23 9937.03
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 25012.707 25012.707 513.019173 0.34314652 350.849 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 25012.71 25012.71 513.019173 67.24 53.42 0.00741068 122.00 70.83 0.00800000 17.78 0.00234317 17.78 8.7706 72.00 0.00789787 38.9748 3953.36 0.00 26332.62 26332.62
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 6576.714 5265.681 246.698621 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 6944.33 6888.73 246.698621 78.38 58.31 0.00805801 53.60 49.17 0.00800000 85.70 0.00569125 57.27 18.2388 75.00 0.00856297 38.1637 4731.14 0.00 6579.46 4778.48
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 13155.587 13155.587 246.698621 0.18048002 178.856 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 13155.59 13155.59 246.698621 62.11 51.05 0.00715073 122.00 70.83 0.00800000 17.78 0.00234317 17.78 18.2388 72.00 0.00822318 40.5583 2165.31 0.00 13242.91 13242.91
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 10077.211 8068.372 378.005490 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 10815.09 10815.09 378.005490 78.02 57.97 0.00790579 53.60 49.00 0.00790579 88.38 0.00569353 58.17 11.9033 75.00 0.00820411 36.5846 7297.52 0.00 10081.42 7321.86
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 19001.689 19001.689 378.005490 0.26068203 263.773 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 19001.69 19001.69 378.005490 65.55 52.50 0.00723670 122.00 70.83 0.00800000 17.78 0.00234317 17.78 11.9033 72.00 0.00789790 38.9749 3955.65 0.00 19706.08 19706.08
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 13447.348 10766.690 504.422433 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 14523.32 14397.35 504.422433 77.74 58.10 0.00806167 53.60 49.17 0.00800000 89.75 0.00569471 58.63 8.9201 75.00 0.00829348 36.9785 9755.40 0.00 13452.96 9770.52
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 24629.967 24629.967 504.422433 0.33789575 345.307 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 24629.97 24629.97 504.422433 67.16 53.38 0.00740241 122.00 70.83 0.00800000 17.78 0.00234317 17.78 8.9201 72.00 0.00789790 38.9750 3955.95 0.00 25910.96 25910.96
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 6592.793 5278.554 247.301740 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 6961.15 6902.38 247.301740 78.37 58.31 0.00806119 53.60 49.17 0.00800000 85.70 0.00569125 57.27 18.1944 75.00 0.00857885 38.2335 4760.55 0.00 6595.54 4790.16
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 13182.438 13182.438 247.301740 0.18084839 179.247 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 13182.44 13182.44 247.301740 62.14 51.07 0.00715332 122.00 70.83 0.00800000 17.78 0.00234317 17.78 18.1944 72.00 0.00822314 40.5581 2165.52 0.00 13272.67 13272.67
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 9876.993 7908.066 370.495122 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 10536.52 10536.52 370.495122 77.90 57.93 0.00790402 53.60 49.00 0.00790402 87.16 0.00569249 57.76 12.1446 75.00 0.00820752 36.5996 7151.31 0.00 9881.11 7176.38
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 18667.315 18667.315 370.495122 0.25609481 258.926 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 18667.32 18667.32 370.495122 65.42 52.43 0.00722328 122.00 70.83 0.00800000 17.78 0.00234317 17.78 12.1446 72.00 0.00789787 38.9748 3953.58 0.00 19337.10 19337.10
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 14571.851 11667.029 546.603577 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 15780.32 15738.43 546.603577 77.67 58.02 0.00801872 53.60 49.17 0.00800000 90.16 0.00569506 58.76 8.2317 75.00 0.00822716 36.6864 10571.30 0.00 14577.93 10587.55
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 26508.890 26508.890 546.603577 0.36367248 372.647 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 26508.89 26508.89 546.603577 67.53 52.78 0.00695399 122.00 70.83 0.00800000 17.78 0.00234317 17.78 8.2317 72.00 0.00736759 36.3912 5618.04 0.00 27980.15 27980.15
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 7589.138 6076.283 284.675574 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 8023.15 8020.05 284.675574 78.12 58.14 0.00800276 53.60 49.17 0.00800000 85.70 0.00569125 57.27 15.8057 75.00 0.00842849 37.5721 5483.86 0.00 7592.30 5514.08
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 14846.845 14846.845 284.675574 0.20368221 203.559 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 14846.85 14846.85 284.675574 63.43 50.46 0.00650652 122.00 70.83 0.00800000 17.78 0.00234317 17.78 15.8057 72.00 0.00728810 36.0025 3821.84 0.00 15115.16 15115.16
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 10174.236 8146.055 381.644978 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 10925.14 10925.14 381.644978 78.00 57.88 0.00785332 53.60 48.91 0.00785332 88.38 0.00569353 58.17 11.7897 75.00 0.00813969 36.3008 7354.27 0.00 10178.48 7392.35
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 19164.364 19164.364 381.644978 0.26291376 266.229 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 19164.36 19164.36 381.644978 65.61 51.76 0.00677536 122.00 70.83 0.00800000 17.78 0.00234317 17.78 11.7897 72.00 0.00736774 36.3919 5619.67 0.00 19885.21 19885.21
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 14612.284 11699.402 548.120268 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 15790.63 15733.30 548.120268 77.63 58.01 0.00802560 53.60 49.17 0.00800000 89.75 0.00569471 58.63 8.2090 75.00 0.00823405 36.7167 10600.60 0.00 14618.38 10616.93
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 26576.418 26576.418 548.120268 0.36459890 373.624 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 26576.42 26576.42 548.120268 67.55 52.79 0.00695544 122.00 70.83 0.00800000 17.78 0.00234317 17.78 8.2090 72.00 0.00736792 36.3928 5621.64 0.00 28054.52 28054.52
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 7789.343 6236.578 292.185439 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 8235.18 8225.53 292.185439 78.07 58.14 0.00800835 53.60 49.17 0.00800000 85.70 0.00569125 57.27 15.3995 75.00 0.00842233 37.5451 5630.69 0.00 7792.59 5659.55
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 15181.207 15181.207 292.185439 0.20826928 208.416 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 15181.21 15181.21 292.185439 63.65 50.58 0.00652683 122.00 70.83 0.00800000 17.78 0.00234317 17.78 15.3995 72.00 0.00728836 36.0038 3823.70 0.00 15484.98 15484.98
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 9942.845 7960.791 372.965295 -999. -999.00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 10612.61 10612.61 372.965295 77.89 57.84 0.00785031 53.60 48.90 0.00785031 87.16 0.00569249 57.76 12.0641 75.00 0.00814293 36.3151 7185.82 0.00 9946.99 7224.23
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 18777.915 18777.915 372.965295 0.25761210 260.625 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 18777.91 18777.91 372.965295 65.46 51.68 0.00676159 122.00 70.83 0.00800000 17.78 0.00234317 17.78 12.0641 72.00 0.00736776 36.3921 5619.92 0.00 19458.80 19458.80



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [Btu/lbm-R] Dry Air Heat Capacity [Btu/lbm-R] Standard Air Density Adjusted for Elevation [lb/ft3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [ft3/min] Supply Fan Maximum Air Mass Flow Rate [lb/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [Btu/lbm-R] Plant Fluid Density [lb/ft3] Plant Maximum Fluid Mass Flow Rate [lb/s] Plant Design Fluid Return Temperature [F] Plant Design Fluid Supply Temperature [F] Plant Design Fluid Temperature Difference [deltaF] Plant Design Capacity [Btu/h] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [F] System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h] Coil Air Mass Flow Rate at Rating Conditions [lb/s] Coil Entering Air Drybulb at Rating Conditions [F] Coil Entering Air Wetbulb at Rating Conditions [F] Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] Coil Leaving Air Drybulb at Rating Conditions [F] Coil Leaving Air Wetbulb at Rating Conditions [F] Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 14140.226 11321.446 530.412928 -999. -999.00 -999.0000 1.15587 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 530.412928 0.54663884   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 Sensible 15345.59 15339.52 0.9215 0.54663884 530.412928 77.74 58.02 0.00800279 11.0 53.60 49.17 0.00800000 7.7 -999. -999.0 -999.0 -999.0 682.632 14662.95 90.56 0.00569540 58.90 44.99498340 8.4830 75.00 0.00821667 75.00 0.00819330 36.5372 10253.25 0.00 14146.13 10273.94 0.52505074 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes Yes No 25788.027 25788.027 530.412928 0.35378306 362.203 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 530.412928 0.54663884   1.0027 62.4216 4.99445755 159.80 179.60 19.80 356940.17 7.2247 7.370149 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 25788.03 25788.03 1.0000 0.54663884 530.412928 67.40 52.73 0.00695502 8.9 122.00 70.83 0.00800000 17.0 0.36809896 140.00 120.20 19.80 0.000 25788.03 17.78 0.00234317 17.78 44.99498340 8.4830 72.00 0.00738251 72.00 0.00738251 36.4640 5779.25 0.00 27186.18 27186.18 0.54663884 61.88 53.82 0.00695502 8.2 118.71 73.03 0.00695502 15.9
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6738.475 5395.195 252.766405 -999. -999.00 -999.0000 1.16057 1.00000 0.2435 0.2400 0.0618 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 252.766405 0.26049881   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 7122.25 7122.25 0.9461 0.26049881 252.766405 78.33 58.17 0.00797520 11.0 53.60 49.12 0.00797520 7.7 -999. -999.0 -999.0 -999.0 325.306 6796.95 85.70 0.00569125 57.27 44.99498340 17.8010 75.00 0.00846981 75.00 0.00838699 37.3895 4824.62 0.00 6741.29 4896.01 0.25021107 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes Yes No 13426.155 13426.155 252.766405 0.18419192 182.904 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 252.766405 0.26049881   1.0027 62.4216 4.99445755 159.80 179.60 19.80 356940.17 3.7615 3.837159 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 13426.16 13426.16 1.0000 0.26049881 252.766405 62.35 49.90 0.00642653 7.9 122.00 70.83 0.00800000 17.0 0.19164528 140.00 120.20 19.80 0.000 13426.16 17.78 0.00234317 17.78 44.99498340 17.8010 72.00 0.00731082 72.00 0.00731082 36.1135 3983.41 0.00 13542.47 13542.47 0.26049881 61.88 52.85 0.00642653 7.9 121.34 73.11 0.00642653 15.9
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 9902.210 7928.256 371.441027 -999. -999.00 -999.0000 1.16194 1.00000 0.2435 0.2400 0.0618 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 371.441027 0.38280382   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 Sensible 10600.91 10600.91 0.9341 0.38280382 371.441027 77.97 57.87 0.00784714 10.9 53.60 48.90 0.00784714 7.6 -999. -999.0 -999.0 -999.0 478.038 10122.88 87.77 0.00569301 57.97 44.99498340 12.1136 75.00 0.00814405 75.00 0.00814312 36.3160 7172.84 0.00 9906.34 7194.70 0.36768596 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes Yes No 18710.050 18710.050 371.441027 0.25668108 259.638 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 371.441027 0.38280382   1.0027 62.4216 4.99445755 159.80 179.60 19.80 356940.17 5.2418 5.347282 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 18710.05 18710.05 1.0000 0.38280382 371.441027 65.43 51.69 0.00677226 8.6 122.00 70.83 0.00800000 17.0 0.26706773 140.00 120.20 19.80 0.000 18710.05 17.78 0.00234317 17.78 44.99498340 12.1136 72.00 0.00738273 72.00 0.00738273 36.4651 5781.79 0.00 19383.91 19383.91 0.38280382 61.88 53.48 0.00677226 8.1 119.76 73.10 0.00677226 15.9
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 13887.232 11118.885 520.922895 -999. -999.00 -999.0000 1.15682 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 520.922895 0.53685850   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 Sensible 15037.78 15010.75 0.9235 0.53685850 520.922895 77.73 58.03 0.00801269 11.0 53.60 49.17 0.00800000 7.7 -999. -999.0 -999.0 -999.0 670.418 14367.36 90.16 0.00569506 58.76 44.99498340 8.6376 75.00 0.00823180 75.00 0.00823180 36.7068 10074.64 0.00 13893.03 10090.12 0.51565665 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes Yes No 25365.499 25365.499 520.922895 0.34798643 356.083 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 520.922895 0.53685850   1.0027 62.4216 4.99445755 159.80 179.60 19.80 356940.17 7.1064 7.249391 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 25365.50 25365.50 1.0000 0.53685850 520.922895 67.31 52.69 0.00694747 8.9 122.00 70.83 0.00800000 17.0 0.36206777 140.00 120.20 19.80 0.000 25365.50 17.78 0.00234317 17.78 44.99498340 8.6376 72.00 0.00738277 72.00 0.00738277 36.4653 5782.21 0.00 26720.76 26720.76 0.53685850 61.88 53.80 0.00694747 8.2 118.76 73.03 0.00694747 15.9
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6793.749 5439.451 254.839818 -999. -999.00 -999.0000 1.16126 1.00000 0.2435 0.2400 0.0618 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 254.839818 0.26263565   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 7180.70 7180.70 0.9461 0.26263565 254.839818 78.31 58.17 0.00797840 11.0 53.60 49.13 0.00797840 7.7 -999. -999.0 -999.0 -999.0 327.974 6852.72 85.70 0.00569125 57.27 44.99498340 17.6562 75.00 0.00846881 75.00 0.00844604 37.6493 4906.04 0.00 6796.58 4936.17 0.25226353 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes Yes No 13518.470 13518.470 254.839818 0.18545837 184.247 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 254.839818 0.26263565   1.0027 62.4216 4.99445755 159.80 179.60 19.80 356940.17 3.7873 3.863542 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 13518.47 13518.47 1.0000 0.26263565 254.839818 62.43 49.94 0.00643377 7.9 122.00 70.83 0.00800000 17.0 0.19296298 140.00 120.20 19.80 0.000 13518.47 17.78 0.00234317 17.78 44.99498340 17.6562 72.00 0.00731087 72.00 0.00731087 36.1137 3983.81 0.00 13644.74 13644.74 0.26263565 61.88 52.86 0.00643377 7.9 121.30 73.11 0.00643377 15.9
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 9707.453 7772.324 364.135544 -999. -999.00 -999.0000 1.17441 1.00000 0.2435 0.2400 0.0618 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 364.135544 0.37527485   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 Sensible 10330.28 10330.28 0.9397 0.37527485 364.135544 77.85 57.82 0.00784690 10.9 53.60 48.90 0.00784690 7.6 -999. -999.0 -999.0 -999.0 468.636 9861.65 86.55 0.00569198 57.56 44.99498340 12.3567 75.00 0.00815072 75.00 0.00814754 36.3354 7029.08 0.00 9711.50 7053.20 0.36045433 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes Yes No 18384.785 18384.785 364.135544 0.25221880 254.920 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 364.135544 0.37527485   1.0027 62.4216 4.99445755 159.80 179.60 19.80 356940.17 5.1507 5.254322 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 18384.78 18384.78 1.0000 0.37527485 364.135544 65.30 51.62 0.00675985 8.5 122.00 70.83 0.00800000 17.0 0.26242488 140.00 120.20 19.80 0.000 18384.78 17.78 0.00234317 17.78 44.99498340 12.3567 72.00 0.00738254 72.00 0.00738254 36.4642 5779.66 0.00 19024.95 19024.95 0.37527485 61.88 53.46 0.00675985 8.1 119.83 73.10 0.00675985 15.9
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 13676.527 10950.184 513.019173 -999. -999.00 -999.0000 1.14739 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 513.019173 0.52871300   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 Sensible 14802.86 14687.17 0.9239 0.52871300 513.019173 77.75 58.10 0.00805554 11.0 53.60 49.17 0.00800000 7.7 -999. -999.0 -999.0 -999.0 660.246 14142.62 90.16 0.00569506 58.76 44.99498340 8.7706 75.00 0.00828247 75.00 0.00826836 36.8678 9913.56 0.00 13682.23 9937.03 0.50783283 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes Yes No 25012.707 25012.707 513.019173 0.34314652 350.849 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 513.019173 0.52871300   1.0027 62.4216 4.99445755 159.80 179.60 19.80 356940.17 7.0075 7.148564 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 25012.71 25012.71 1.0000 0.52871300 513.019173 67.24 53.42 0.00741068 9.2 122.00 70.83 0.00800000 17.0 0.35703201 140.00 120.20 19.80 0.000 25012.71 17.78 0.00234317 17.78 44.99498340 8.7706 72.00 0.00789787 72.00 0.00789787 38.9748 3953.36 0.00 26332.62 26332.62 0.52871300 61.88 54.63 0.00741068 8.5 118.75 73.59 0.00741068 16.2
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6576.714 5265.681 246.698621 -999. -999.00 -999.0000 1.14767 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 246.698621 0.25424540   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 6944.33 6888.73 0.9471 0.25424540 246.698621 78.38 58.31 0.00805801 11.1 53.60 49.17 0.00800000 7.7 -999. -999.0 -999.0 -999.0 317.497 6626.83 85.70 0.00569125 57.27 44.99498340 18.2388 75.00 0.00858598 75.00 0.00856297 38.1637 4731.14 0.00 6579.46 4778.48 0.24420463 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes Yes No 13155.587 13155.587 246.698621 0.18048002 178.856 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 246.698621 0.25424540   1.0027 62.4216 4.99445755 159.80 179.60 19.80 356940.17 3.6857 3.759831 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 13155.59 13155.59 1.0000 0.25424540 246.698621 62.11 51.05 0.00715073 8.3 122.00 70.83 0.00800000 17.0 0.18778318 140.00 120.20 19.80 0.000 13155.59 17.78 0.00234317 17.78 44.99498340 18.2388 72.00 0.00822318 72.00 0.00822318 40.5583 2165.31 0.00 13242.91 13242.91 0.25424540 61.88 54.17 0.00715073 8.3 121.38 74.00 0.00715073 16.3
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 10077.211 8068.372 378.005490 -999. -999.00 -999.0000 1.15698 1.00000 0.2435 0.2400 0.0618 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 378.005490 0.38956909   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 Sensible 10815.09 10815.09 0.9318 0.38956909 378.005490 78.02 57.97 0.00790579 10.9 53.60 49.00 0.00790579 7.6 -999. -999.0 -999.0 -999.0 486.486 10328.60 88.38 0.00569353 58.17 44.99498340 11.9033 75.00 0.00820470 75.00 0.00820411 36.5846 7297.52 0.00 10081.42 7321.86 0.37418406 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes Yes No 19001.689 19001.689 378.005490 0.26068203 263.773 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 378.005490 0.38956909   1.0027 62.4216 4.99445755 159.80 179.60 19.80 356940.17 5.3235 5.430631 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 19001.69 19001.69 1.0000 0.38956909 378.005490 65.55 52.50 0.00723670 8.9 122.00 70.83 0.00800000 17.0 0.27123058 140.00 120.20 19.80 0.000 19001.69 17.78 0.00234317 17.78 44.99498340 11.9033 72.00 0.00789790 72.00 0.00789790 38.9749 3955.65 0.00 19706.08 19706.08 0.38956909 61.88 54.32 0.00723670 8.4 119.65 73.63 0.00723670 16.2
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 13447.348 10766.690 504.422433 -999. -999.00 -999.0000 1.14920 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 504.422433 0.51985327   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 Sensible 14523.32 14397.35 0.9259 0.51985327 504.422433 77.74 58.10 0.00806167 11.0 53.60 49.17 0.00800000 7.7 -999. -999.0 -999.0 -999.0 649.182 13874.14 89.75 0.00569471 58.63 44.99498340 8.9201 75.00 0.00829348 75.00 0.00829348 36.9785 9755.40 0.00 13452.96 9770.52 0.49932300 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes Yes No 24629.967 24629.967 504.422433 0.33789575 345.307 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 504.422433 0.51985327   1.0027 62.4216 4.99445755 159.80 179.60 19.80 356940.17 6.9003 7.039178 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 24629.97 24629.97 1.0000 0.51985327 504.422433 67.16 53.38 0.00740241 9.2 122.00 70.83 0.00800000 17.0 0.35156877 140.00 120.20 19.80 0.000 24629.97 17.78 0.00234317 17.78 44.99498340 8.9201 72.00 0.00789790 72.00 0.00789790 38.9750 3955.95 0.00 25910.96 25910.96 0.51985327 61.88 54.62 0.00740241 8.5 118.79 73.60 0.00740241 16.2
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6592.793 5278.554 247.301740 -999. -999.00 -999.0000 1.14726 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 247.301740 0.25486697   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 6961.15 6902.38 0.9471 0.25486697 247.301740 78.37 58.31 0.00806119 11.1 53.60 49.17 0.00800000 7.7 -999. -999.0 -999.0 -999.0 318.273 6642.87 85.70 0.00569125 57.27 44.99498340 18.1944 75.00 0.00858829 75.00 0.00857885 38.2335 4760.55 0.00 6595.54 4790.16 0.24480165 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes Yes No 13182.438 13182.438 247.301740 0.18084839 179.247 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 247.301740 0.25486697   1.0027 62.4216 4.99445755 159.80 179.60 19.80 356940.17 3.6932 3.767505 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 13182.44 13182.44 1.0000 0.25486697 247.301740 62.14 51.07 0.00715332 8.3 122.00 70.83 0.00800000 17.0 0.18816645 140.00 120.20 19.80 0.000 13182.44 17.78 0.00234317 17.78 44.99498340 18.1944 72.00 0.00822314 72.00 0.00822314 40.5581 2165.52 0.00 13272.67 13272.67 0.25486697 61.88 54.17 0.00715332 8.3 121.37 74.00 0.00715332 16.3
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 9876.993 7908.066 370.495122 -999. -999.00 -999.0000 1.16925 1.00000 0.2435 0.2400 0.0618 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 370.495122 0.38182898   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 Sensible 10536.52 10536.52 0.9374 0.38182898 370.495122 77.90 57.93 0.00790402 10.9 53.60 49.00 0.00790402 7.6 -999. -999.0 -999.0 -999.0 476.820 10059.70 87.16 0.00569249 57.76 44.99498340 12.1446 75.00 0.00820972 75.00 0.00820752 36.5996 7151.31 0.00 9881.11 7176.38 0.36674962 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes Yes No 18667.315 18667.315 370.495122 0.25609481 258.926 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 370.495122 0.38182898   1.0027 62.4216 4.99445755 159.80 179.60 19.80 356940.17 5.2298 5.335069 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 18667.32 18667.32 1.0000 0.38182898 370.495122 65.42 52.43 0.00722328 8.8 122.00 70.83 0.00800000 17.0 0.26645773 140.00 120.20 19.80 0.000 18667.32 17.78 0.00234317 17.78 44.99498340 12.1446 72.00 0.00789787 72.00 0.00789787 38.9748 3953.58 0.00 19337.10 19337.10 0.38182898 61.88 54.30 0.00722328 8.4 119.72 73.64 0.00722328 16.2
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 14571.851 11667.029 546.603577 -999. -999.00 -999.0000 1.15826 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 546.603577 0.56332478   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 Sensible 15780.32 15738.43 0.9234 0.56332478 546.603577 77.67 58.02 0.00801872 11.0 53.60 49.17 0.00800000 7.7 -999. -999.0 -999.0 -999.0 703.469 15076.85 90.16 0.00569506 58.76 44.99498340 8.2317 75.00 0.00822716 75.00 0.00822716 36.6864 10571.30 0.00 14577.93 10587.55 0.54107771 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes Yes No 26508.890 26508.890 546.603577 0.36367248 372.647 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 546.603577 0.56332478   1.0027 62.4216 4.99445755 159.80 179.60 19.80 356940.17 7.4267 7.576169 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 26508.89 26508.89 1.0000 0.56332478 546.603577 67.53 52.78 0.00695399 9.0 122.00 70.83 0.00800000 17.0 0.37838856 140.00 120.20 19.80 0.000 26508.89 17.78 0.00234317 17.78 44.99498340 8.2317 72.00 0.00736759 72.00 0.00736759 36.3912 5618.04 0.00 27980.15 27980.15 0.56332478 61.88 53.81 0.00695399 8.2 118.64 73.01 0.00695399 15.9
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 7589.138 6076.283 284.675574 -999. -999.00 -999.0000 1.16937 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 284.675574 0.29338411   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 8023.15 8020.05 0.9459 0.29338411 284.675574 78.12 58.14 0.00800276 11.0 53.60 49.17 0.00800000 7.7 -999. -999.0 -999.0 -999.0 366.372 7656.78 85.70 0.00569125 57.27 44.99498340 15.8057 75.00 0.00843670 75.00 0.00842849 37.5721 5483.86 0.00 7592.30 5514.08 0.28179766 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes Yes No 14846.845 14846.845 284.675574 0.20368221 203.559 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 284.675574 0.29338411   1.0027 62.4216 4.99445755 159.80 179.60 19.80 356940.17 4.1595 4.243188 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 14846.85 14846.85 1.0000 0.29338411 284.675574 63.43 50.46 0.00650652 8.1 122.00 70.83 0.00800000 17.0 0.21192425 140.00 120.20 19.80 0.000 14846.85 17.78 0.00234317 17.78 44.99498340 15.8057 72.00 0.00728810 72.00 0.00728810 36.0025 3821.84 0.00 15115.16 15115.16 0.29338411 61.88 53.00 0.00650652 7.9 120.80 73.06 0.00650652 15.9
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 10174.236 8146.055 381.644978 -999. -999.00 -999.0000 1.15705 1.00000 0.2435 0.2400 0.0618 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 381.644978 0.39331992   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 Sensible 10925.14 10925.14 0.9313 0.39331992 381.644978 78.00 57.88 0.00785332 10.9 53.60 48.91 0.00785332 7.6 -999. -999.0 -999.0 -999.0 491.170 10433.97 88.38 0.00569353 58.17 44.99498340 11.7897 75.00 0.00814198 75.00 0.00813969 36.3008 7354.27 0.00 10178.48 7392.35 0.37778675 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes Yes No 19164.364 19164.364 381.644978 0.26291376 266.229 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 381.644978 0.39331992   1.0027 62.4216 4.99445755 159.80 179.60 19.80 356940.17 5.3691 5.477124 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 19164.36 19164.36 1.0000 0.39331992 381.644978 65.61 51.76 0.00677536 8.6 122.00 70.83 0.00800000 17.0 0.27355262 140.00 120.20 19.80 0.000 19164.36 17.78 0.00234317 17.78 44.99498340 11.7897 72.00 0.00736774 72.00 0.00736774 36.3919 5619.67 0.00 19885.21 19885.21 0.39331992 61.88 53.49 0.00677536 8.1 119.67 73.08 0.00677536 15.9
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 14612.284 11699.402 548.120268 -999. -999.00 -999.0000 1.16093 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 548.120268 0.56488787   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 Sensible 15790.63 15733.30 0.9254 0.56488787 548.120268 77.63 58.01 0.00802560 11.0 53.60 49.17 0.00800000 7.7 -999. -999.0 -999.0 -999.0 705.421 15085.21 89.75 0.00569471 58.63 44.99498340 8.2090 75.00 0.00823405 75.00 0.00823405 36.7167 10600.60 0.00 14618.38 10616.93 0.54257907 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes Yes No 26576.418 26576.418 548.120268 0.36459890 373.624 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 548.120268 0.56488787   1.0027 62.4216 4.99445755 159.80 179.60 19.80 356940.17 7.4456 7.595469 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 26576.42 26576.42 1.0000 0.56488787 548.120268 67.55 52.79 0.00695544 9.0 122.00 70.83 0.00800000 17.0 0.37935246 140.00 120.20 19.80 0.000 26576.42 17.78 0.00234317 17.78 44.99498340 8.2090 72.00 0.00736792 72.00 0.00736792 36.3928 5621.64 0.00 28054.52 28054.52 0.56488787 61.88 53.82 0.00695544 8.2 118.63 73.01 0.00695544 15.9
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 7789.343 6236.578 292.185439 -999. -999.00 -999.0000 1.17012 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 292.185439 0.30112371   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 8235.18 8225.53 0.9459 0.30112371 292.185439 78.07 58.14 0.00800835 11.0 53.60 49.17 0.00800000 7.7 -999. -999.0 -999.0 -999.0 376.037 7859.15 85.70 0.00569125 57.27 44.99498340 15.3995 75.00 0.00843013 75.00 0.00842233 37.5451 5630.69 0.00 7792.59 5659.55 0.28923160 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes Yes No 15181.207 15181.207 292.185439 0.20826928 208.416 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 292.185439 0.30112371   1.0027 62.4216 4.99445755 159.80 179.60 19.80 356940.17 4.2532 4.338748 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 15181.21 15181.21 1.0000 0.30112371 292.185439 63.65 50.58 0.00652683 8.2 122.00 70.83 0.00800000 17.0 0.21669694 140.00 120.20 19.80 0.000 15181.21 17.78 0.00234317 17.78 44.99498340 15.3995 72.00 0.00728836 72.00 0.00728836 36.0038 3823.70 0.00 15484.98 15484.98 0.30112371 61.88 53.04 0.00652683 7.9 120.69 73.06 0.00652683 15.9
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 9942.845 7960.791 372.965295 -999. -999.00 -999.0000 1.16907 1.00000 0.2435 0.2400 0.0618 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 372.965295 0.38437471   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 Sensible 10612.61 10612.61 0.9369 0.38437471 372.965295 77.89 57.84 0.00785031 10.9 53.60 48.90 0.00785031 7.6 -999. -999.0 -999.0 -999.0 479.999 10132.61 87.16 0.00569249 57.76 44.99498340 12.0641 75.00 0.00814634 75.00 0.00814293 36.3151 7185.82 0.00 9946.99 7224.23 0.36919482 80.00 67.00 0.01118466 13.2 57.74 56.30 0.00931636 9.1
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident HeatingDesignCapacity N/A Yes Yes Yes No 18777.915 18777.915 372.965295 0.25761210 260.625 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0618 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 372.965295 0.38437471   1.0027 62.4216 4.99445755 159.80 179.60 19.80 356940.17 5.2608 5.366677 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 18777.91 18777.91 1.0000 0.38437471 372.965295 65.46 51.68 0.00676159 8.6 122.00 70.83 0.00800000 17.0 0.26803643 140.00 120.20 19.80 0.000 18777.91 17.78 0.00234317 17.78 44.99498340 12.0641 72.00 0.00736776 72.00 0.00736776 36.3921 5619.92 0.00 19458.80 19458.80 0.38437471 61.88 53.46 0.00676159 8.1 119.75 73.08 0.00676159 15.9



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2133.17 4977.33 196.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1615.33 5314.00 103.33
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2188.83 4806.83 161.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2276.50 5563.17 559.67
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1320.17 5779.00 127.50
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2050.17 5454.50 193.83
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2273.17 4453.17 61.33
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1826.33 4618.17 28.67
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2348.17 4261.00 45.17
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2218.67 5169.83 240.17
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1502.67 5351.17 29.33
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2200.33 5054.50 47.17
LIVING_UNIT3_BACKROW_TOPFLOOR 2349.83 5100.50 89.67
LIVING_UNIT3_FRONTROW_TOPFLOOR 2419.67 4610.50 76.17
LIVING_UNIT1_FRONTROW_TOPFLOOR 2319.67 4738.33 103.17
LIVING_UNIT2_BACKROW_TOPFLOOR 1733.67 5375.50 45.83
LIVING_UNIT2_FRONTROW_TOPFLOOR 1933.33 4995.50 47.17
LIVING_UNIT1_BACKROW_TOPFLOOR 2483.83 5235.83 418.00
CRAWLSPACE 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 3305.83 5971.50 651.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 173.67 4.33 173.67 4.33
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 38.67 9.17 38.67 9.17
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 351.33 0.00 351.33 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 616.17 4.67 616.17 4.67
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 255.17 3.67 255.17 3.67
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 202.33 1.83 202.33 1.83
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 58.17 3.00 58.17 3.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 22.33 3.00 22.33 3.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 496.17 0.00 496.17 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 546.17 2.83 546.17 2.83
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 163.50 0.67 163.50 0.67
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 403.67 0.00 403.67 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 259.17 0.67 259.17 0.67
LIVING_UNIT3_FRONTROW_TOPFLOOR 380.33 0.00 380.33 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 198.83 3.17 198.83 3.17
LIVING_UNIT2_BACKROW_TOPFLOOR 150.67 1.50 150.67 1.50
LIVING_UNIT2_FRONTROW_TOPFLOOR 33.67 2.17 33.67 2.17
LIVING_UNIT1_BACKROW_TOPFLOOR 607.17 3.17 607.17 3.17
CRAWLSPACE 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 2148.50 13.33 2148.50 13.33
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.268 0.118 0.000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.268 0.104 0.000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.268 0.118 0.000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.268 0.117 0.000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.268 0.103 0.000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.268 0.117 0.000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.268 0.052 0.000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.268 0.038 0.000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.268 0.052 0.000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.268 0.052 0.000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.268 0.037 0.000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.268 0.052 0.000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.268 0.118 0.000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.268 0.118 0.000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.268 0.118 0.000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.268 0.104 0.000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.268 0.104 0.000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.268 0.117 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.260 0.000 0.000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.261 0.000 0.000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.261 0.000 0.000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.257 0.000 0.000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.260 0.000 0.000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.260 0.000 0.000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.261 0.000 0.000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.261 0.000 0.000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.261 0.000 0.000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.258 0.000 0.000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.260 0.000 0.000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.260 0.000 0.000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.260 0.000 0.000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.261 0.000 0.000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.261 0.000 0.000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.260 0.000 0.000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.261 0.000 0.000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.258 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Zone Area [ft2] Design Zone Outdoor Airflow - Voz [ft3/min] Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
Total Facility   24.79 36.00 183739.38 21609.96 0.0000 0.000


Total Outdoor Air by Zone

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Infiltration [ft3] Total Ventilation and Infiltration [ft3] Dynamic Target Ventilation - Voz-dyn [ft3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 10467630.99 34252712.68 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 9229798.71 33014880.40 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 10480509.36 34265591.04 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 10415735.59 34200817.27 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 9182072.78 32967154.47 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 10440343.69 34225425.38 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 4597608.98 28382690.66 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 3349115.82 27134197.51 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 4600651.77 28385733.45 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 4575593.87 28360675.55 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 3329310.50 27114392.19 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 4581250.71 28366332.40 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 23785081.69 0.00 23785081.69 10457242.24 34242323.93 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 23785081.69 0.00 23785081.69 10494261.18 34279342.87 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 23785081.69 0.00 23785081.69 10482789.73 34267871.42 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 23785081.69 0.00 23785081.69 9201386.64 32986468.33 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 23785081.69 0.00 23785081.69 9244713.02 33029794.71 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 23785081.69 0.00 23785081.69 10436818.44 34221900.13 23785081.69 0.00 8808.00 0.00 0.00
Total Facility 0.428131E+09 0.00 0.428131E+09 0.145567E+09 0.573698E+09 0.428131E+09 0.00 8808.00 0.00 0.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Infiltration [ft3/min] Total Ventilation and Infiltration [ft3/min] Dynamic Target Ventilation - Voz-dyn [ft3/min] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 19.8019 64.7969 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 17.4603 62.4553 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 19.8263 64.8213 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 19.7038 64.6988 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 17.3700 62.3650 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 19.7503 64.7453 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 8.6974 53.6924 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 6.3356 51.3306 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 8.7032 53.6982 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 8.6558 53.6508 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 6.2982 51.2931 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 8.6665 53.6615 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 44.9950 0.0000 44.9950 19.7823 64.7773 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 44.9950 0.0000 44.9950 19.8523 64.8473 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 44.9950 0.0000 44.9950 19.8306 64.8256 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 44.9950 0.0000 44.9950 17.4066 62.4015 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 44.9950 0.0000 44.9950 17.4885 62.4835 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 44.9950 0.0000 44.9950 19.7437 64.7386 44.9950 0.00 8808.00 0.00
Total Facility 809.9097 0.0000 809.9097 275.3733 1085.2830 809.9097 0.00 8808.00 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [ft3] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [ft3/min] Limits and Scheduled Limits [ft3/min] Economizer [ft3/min] Exhaust Flow [ft3/min] Mixed Air Flow [ft3/min] High Humidity [ft3/min] Demand Controlled Ventilation [ft3/min] Night Ventilation [ft3/min] Demand Limiting [ft3/min] Energy Management System [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

Surfaces by Class

Total Outdoors
Wall 82 58
Floor 29 4
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 60 60
Overhang 30 30
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 2011
Defaulted Fields 1548
Fields with Defaults 6437
Autosized Fields 364
Autosizable Fields 618
Autocalculated Fields 162
Autocalculatable Fields 350



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 137070.14 8123.99 03-APR-03:10 35443.34 21-JUL-18:10
Electricity:Building 99897.62 6287.72 02-JAN-03:10 18943.41 01-JAN-18:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5549.87 349.32 02-JAN-03:10 1052.41 01-JAN-18:10
InteriorLights:Electricity 12093.82 270.83 01-JAN-00:10 3939.36 01-JAN-19:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity 12093.82 270.83 01-JAN-00:10 3939.36 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5549.87 349.32 02-JAN-03:10 1052.41 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5549.87 349.32 02-JAN-03:10 1052.41 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5549.87 349.32 02-JAN-03:10 1052.41 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5549.87 349.32 02-JAN-03:10 1052.41 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5549.87 349.32 02-JAN-03:10 1052.41 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5549.87 349.32 02-JAN-03:10 1052.41 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5549.87 349.32 02-JAN-03:10 1052.41 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5549.87 349.32 02-JAN-03:10 1052.41 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5549.87 349.32 02-JAN-03:10 1052.41 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5549.87 349.32 02-JAN-03:10 1052.41 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5549.87 349.32 02-JAN-03:10 1052.41 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5549.87 349.32 02-JAN-03:10 1052.41 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5549.87 349.32 02-JAN-03:10 1052.41 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5549.87 349.32 02-JAN-03:10 1052.41 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5549.87 349.32 02-JAN-03:10 1052.41 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5549.87 349.32 02-JAN-03:10 1052.41 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5549.87 349.32 02-JAN-03:10 1052.41 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
InteriorEquipment:Electricity 87803.80 5989.14 02-JAN-04:10 15388.75 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity 2758.31 25.25 02-JAN-03:10 880.12 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity 1408.53 13.53 02-JAN-02:10 381.47 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:10 3196.73 01-JAN-11:10
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:10 3721.08 01-JAN-17:10
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:10 7929.96 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:10 526.17 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4877.99 332.73 02-JAN-04:10 854.93 01-JAN-18:10
Fans:Electricity 11950.86 578.57 04-JAN-20:00 3155.67 28-JUN-16:20
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityPurchased:Facility 137070.14 8123.99 03-APR-03:10 35443.34 21-JUL-18:10
ElectricityPurchased:Plant 137070.14 8123.99 03-APR-03:10 35443.34 21-JUL-18:10
Cogeneration:ElectricityPurchased 137070.14 8123.99 03-APR-03:10 35443.34 21-JUL-18:10
General:Cogeneration:ElectricityPurchased 137070.14 8123.99 03-APR-03:10 35443.34 21-JUL-18:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 137070.14 8123.99 03-APR-03:10 35443.34 21-JUL-18:10
ElectricityNet:Plant 137070.14 8123.99 03-APR-03:10 35443.34 21-JUL-18:10
Cogeneration:ElectricityNet 137070.14 8123.99 03-APR-03:10 35443.34 21-JUL-18:10
General:Cogeneration:ElectricityNet 137070.14 8123.99 03-APR-03:10 35443.34 21-JUL-18:10
Electricity:HVAC 31663.81 578.57 04-JAN-20:00 16271.70 28-JUN-16:10
HeatRecovery:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:HeatRecovery:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Fans:Electricity 6882.57 0.00 04-JAN-20:00 2577.10 28-JUN-16:20
Ventilation:Fans:Electricity 5068.29 578.57 01-JAN-00:10 578.57 01-JAN-00:10
ExteriorLights:Electricity 5508.71 0.00 01-JAN-06:10 1257.69 01-JAN-00:10
Exterior-Lights:ExteriorLights:Electricity 5508.71 0.00 01-JAN-06:10 1257.69 01-JAN-00:10
Garage-Lights:ExteriorLights:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 19712.95 0.00 01-JAN-00:10 13117.46 28-JUN-16:10
General:Cooling:Electricity 19712.95 0.00 01-JAN-00:10 13117.46 28-JUN-16:10
Electricity:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [therm] Natural Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 3571.52 0.00 01-JAN-13:50 297248.83 01-JAN-07:20
NaturalGas:Plant 3571.52 0.00 01-JAN-13:50 297248.83 01-JAN-07:20
Heating:NaturalGas 1188.14 0.00 01-JAN-13:50 131282.96 15-DEC-05:00
Boiler:Heating:NaturalGas 1188.14 0.00 01-JAN-13:50 131282.96 15-DEC-05:00
WaterSystems:NaturalGas 2383.38 0.00 01-JAN-00:10 221820.91 01-JAN-08:00
Water Heater:WaterSystems:NaturalGas 2383.38 0.00 01-JAN-00:10 221820.91 01-JAN-08:00


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
Water:Plant 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
WaterSystems:Water 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
Domestic Hot Water:WaterSystems:Water 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
MainsWater:Facility 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
MainsWater:Plant 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
WaterSystems:MainsWater 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
Domestic Hot Water:WaterSystems:MainsWater 44223.64 0.01 02-JAN-02:10 0.16 01-JAN-08:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 964291.77 12518.28 09-NOV-03:00 309159.42 21-JUL-18:40
EnergyTransfer:Building 359474.16 4912.40 28-MAR-12:00 135257.91 04-JUL-18:10
EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer 52048.59 0.00 01-JAN-13:50 66545.92 06-FEB-05:00
Heating:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 52048.59 0.00 01-JAN-13:50 66545.92 06-FEB-05:00
Cooling:EnergyTransfer 307425.57 0.00 01-JAN-05:20 135257.91 04-JUL-18:10
Cooling:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer 307425.57 0.00 01-JAN-05:20 135257.91 04-JUL-18:10
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 22522.99 1.79 04-NOV-19:50 11186.33 23-JUN-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 3668.74 0.00 01-JAN-10:40 5005.63 06-FEB-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 18854.25 0.00 01-JAN-00:10 11186.33 23-JUN-17:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 16125.08 0.01 03-MAR-20:40 5458.65 21-SEP-14:50
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1917.90 0.00 01-JAN-00:10 3447.15 17-JAN-08:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 14207.18 0.00 01-JAN-01:30 5458.65 21-SEP-14:50
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 22917.68 5.33 05-DEC-08:50 7858.28 21-JUL-09:50
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 3578.50 0.00 01-JAN-00:10 5060.59 06-FEB-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 19339.19 0.00 01-JAN-01:30 7858.28 21-JUL-09:50
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 19524.47 0.18 22-JAN-14:20 11157.48 13-JUN-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5085.09 0.00 01-JAN-08:50 8362.71 04-FEB-13:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 14439.39 0.00 01-JAN-00:10 11157.48 13-JUN-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 13430.73 0.84 12-FEB-13:50 5320.65 28-JUN-19:20
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3510.52 0.00 01-JAN-13:50 4203.67 06-FEB-17:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 9920.21 0.00 01-JAN-00:10 5320.65 28-JUN-19:20
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 19569.59 2.12 05-JAN-11:40 7814.08 21-JUL-09:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4919.87 0.00 01-JAN-12:40 5081.90 06-FEB-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 14649.71 0.00 01-JAN-00:10 7814.08 21-JUL-09:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 23496.83 0.39 19-APR-05:30 10968.20 20-SEP-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1630.10 0.00 01-JAN-00:10 3094.67 15-DEC-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 21866.73 0.00 01-JAN-02:50 10968.20 20-SEP-16:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 18325.68 2.11 10-NOV-17:50 5419.10 26-SEP-14:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 548.49 0.00 01-JAN-00:10 2146.63 07-FEB-02:20
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 17777.19 0.00 01-JAN-05:20 5419.10 26-SEP-14:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 24571.49 2.68 12-JAN-10:10 8005.76 17-AUG-09:50
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1724.79 0.00 01-JAN-00:10 4556.60 15-JAN-01:40
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 22846.69 0.00 01-JAN-05:20 8005.76 17-AUG-09:50
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 19545.02 0.18 15-FEB-05:50 10865.98 13-JUN-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2640.90 0.00 01-JAN-00:10 6939.65 14-DEC-13:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 16904.12 0.00 01-JAN-01:10 10865.98 13-JUN-18:10
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 13963.67 2.52 31-OCT-14:10 5088.29 04-JUL-19:10
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1239.88 0.00 01-JAN-00:10 3218.75 18-JAN-16:50
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12723.80 0.00 01-JAN-02:50 5088.29 04-JUL-19:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 20188.55 0.43 16-DEC-14:30 7839.68 21-JUL-09:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2539.75 0.00 01-JAN-00:10 3530.90 31-JAN-23:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 17648.79 0.00 01-JAN-02:50 7839.68 21-JUL-09:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 21737.17 0.14 30-JAN-13:40 7834.66 21-JUL-09:50
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4196.69 0.00 01-JAN-12:10 4723.90 15-DEC-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 17540.48 0.00 01-JAN-00:10 7834.66 21-JUL-09:50
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 24427.14 4.08 29-NOV-08:00 7987.35 21-JUL-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 3038.11 0.00 01-JAN-00:10 4689.96 15-DEC-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 21389.03 0.00 01-JAN-02:50 7987.35 21-JUL-10:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 24029.74 0.98 07-JAN-20:40 11543.30 20-AUG-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 3176.58 0.00 01-JAN-00:10 4604.52 15-DEC-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 20853.16 0.00 01-JAN-01:50 11543.30 20-AUG-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 15665.10 0.34 20-FEB-13:30 6185.11 28-JUN-19:20
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 2817.32 0.00 01-JAN-13:50 4538.09 22-DEC-10:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 12847.78 0.00 01-JAN-00:10 6185.11 28-JUN-19:20
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 18004.30 1.27 25-OCT-19:10 6052.47 21-JUL-20:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 1515.89 0.00 01-JAN-00:10 3055.42 17-JAN-08:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 16488.41 0.00 01-JAN-02:50 6052.47 21-JUL-20:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 21428.93 0.48 30-NOV-13:20 11719.03 26-JUN-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4299.47 0.00 01-JAN-00:10 7170.35 31-DEC-12:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 17129.46 0.00 01-JAN-00:20 11719.03 26-JUN-17:30
EnergyTransfer:HVAC 384823.14 0.00 02-JAN-22:20 159215.93 21-JUL-18:10
HeatRecoveryForHeating:EnergyTransfer 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRecoveryForCooling:EnergyTransfer 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatingCoils:EnergyTransfer 93697.16 0.00 01-JAN-13:50 101931.34 15-DEC-05:00
PlantLoopHeatingDemand:Facility 218640.65 1013.52 08-AUG-02:40 130422.24 15-DEC-07:10
PlantLoopHeatingDemand:HVAC 93697.16 0.00 01-JAN-13:50 101931.34 15-DEC-05:00
HeatingCoils:PlantLoopHeatingDemand 93697.16 0.00 01-JAN-13:50 101931.34 15-DEC-05:00
CoolingCoils:EnergyTransfer 291125.98 0.00 01-JAN-00:10 159215.93 21-JUL-18:10
EnergyTransfer:Plant 219994.48 1013.52 08-AUG-02:40 129603.52 15-DEC-07:10
Boilers:EnergyTransfer 95050.99 0.00 01-JAN-13:50 105026.37 15-DEC-05:00
WaterSystems:EnergyTransfer 124943.49 1013.52 08-AUG-02:40 33716.03 05-FEB-08:30
Domestic Hot Water:WaterSystems:EnergyTransfer 124943.49 1013.52 08-AUG-02:40 33716.03 05-FEB-08:30
PlantLoopHeatingDemand:Plant 124943.49 1013.52 08-AUG-02:40 33716.03 05-FEB-08:30
WaterSystems:PlantLoopHeatingDemand 124943.49 1013.52 08-AUG-02:40 33716.03 05-FEB-08:30
General:WaterSystems:PlantLoopHeatingDemand 124943.49 1013.52 08-AUG-02:40 33716.03 05-FEB-08:30
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 577.729 -515.79 6672.753 -1352.62 0.000 0.000 3003.075 2294.076 10401.374 15078.387 0.000 196.666 0.041 0.000 -5040.67 0.000 -3204.46 -7543.01
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 577.677 -518.98 4414.259 -920.15 0.000 0.000 2990.357 2294.076 10401.374 7095.256 0.000 173.089 0.044 0.000 -2027.68 0.000 -2839.71 -5797.48
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 577.678 -518.59 6117.199 -1351.45 0.000 0.000 3003.715 2294.076 10401.374 15737.264 0.000 196.729 0.008 0.000 -4873.92 0.000 -3222.24 -7776.35
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 577.768 -503.39 8747.955 -1052.24 0.000 0.000 3028.739 2294.076 10401.374 9953.668 0.000 196.655 0.000 0.000 -5130.67 0.000 -3114.42 -8275.16
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 577.972 -506.18 7280.808 -682.07 0.000 0.000 3022.196 2294.076 10401.374 1783.634 0.000 173.175 0.000 0.000 -2113.73 0.000 -2761.27 -6389.72
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 577.696 -509.15 8626.185 -1067.61 0.000 0.000 3023.674 2294.076 10401.374 10499.730 0.000 196.720 0.000 0.000 -4869.73 0.000 -3156.18 -8659.83
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 577.826 -522.96 3852.779 -1531.26 0.000 0.000 2975.905 2294.076 10401.374 14968.709 0.000 85.795 0.037 0.000 -5215.58 0.000 -1428.17 -3845.52
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 577.845 -527.23 1968.013 -1119.55 0.000 0.000 2959.100 2294.076 10401.374 7043.748 0.000 62.381 0.311 0.000 -2098.83 0.000 -1048.44 -2384.69
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 577.739 -524.45 3392.718 -1565.18 0.000 0.000 2981.305 2294.076 10401.374 15628.458 0.000 85.814 0.370 0.000 -5033.89 0.000 -1431.99 -3803.28
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 577.878 -510.72 5474.530 -1181.12 0.000 0.000 3005.971 2294.076 10401.374 9859.054 0.000 85.795 0.086 0.000 -5299.90 0.000 -1388.33 -4694.83
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 578.088 -512.06 3809.302 -809.67 0.000 0.000 3001.100 2294.076 10401.374 1756.863 0.000 62.403 0.068 0.000 -2183.71 0.000 -1013.27 -2834.87
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 577.771 -513.61 5143.023 -1221.05 0.000 0.000 3008.708 2294.076 10401.374 10405.437 0.000 85.813 0.011 0.000 -5015.24 0.000 -1397.28 -4673.84
LIVING_UNIT3_BACKROW_TOPFLOOR 577.660 -511.62 7520.585 -1274.02 0.000 0.000 3013.377 2294.076 10401.374 10408.637 0.000 195.166 0.033 0.000 -5017.59 0.000 -3183.44 -4767.80
LIVING_UNIT3_FRONTROW_TOPFLOOR 577.643 -520.40 5326.343 -1499.49 0.000 0.000 2993.333 2294.076 10401.374 15644.960 0.000 195.169 0.018 0.000 -5008.40 0.000 -3245.50 -4924.12
LIVING_UNIT1_FRONTROW_TOPFLOOR 577.726 -517.94 5831.708 -1487.88 0.000 0.000 2991.317 2294.076 10401.374 14982.274 0.000 195.133 0.015 0.000 -5182.24 0.000 -3230.18 -4775.21
LIVING_UNIT2_BACKROW_TOPFLOOR 577.932 -509.91 6153.165 -885.95 0.000 0.000 3008.410 2294.076 10401.374 1755.857 0.000 171.839 0.006 0.000 -2181.04 0.000 -2793.27 -2626.74
LIVING_UNIT2_FRONTROW_TOPFLOOR 577.833 -521.71 3697.718 -1081.22 0.000 0.000 2976.716 2294.076 10401.374 7047.852 0.000 171.820 0.056 0.000 -2084.39 0.000 -2867.19 -2967.74
LIVING_UNIT1_BACKROW_TOPFLOOR 577.762 -506.89 7690.742 -1250.14 0.000 0.000 3015.119 2294.076 10401.374 9860.820 0.000 195.131 0.041 0.000 -5289.25 0.000 -3149.57 -4497.72
CRAWLSPACE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 39195.212 119779.904 0.000 0.000 0.000 -158975.12 0.000
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 22421.501 178611.636 0.000 0.000 0.000 -201033.14 -1.41
Total Facility 10400.223 -9271.59 101719.786 -21332.68 0.000 0.000 54002.114 41293.362 187224.736 179510.609 0.000 64342.006 298392.685 0.000 -73666.45 0.000 -404483.18 -91239.31


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 23-JUN-17:30 0.00 0.07 0.00 -1.0 0.00 0.00 263.17 500.54 1655.83 8502.99 0.00 241.50 22.49 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 21-SEP-14:50 0.00 0.04 0.00 -0.5 0.00 0.00 114.96 96.26 1084.62 2786.24 0.00 104.41 1272.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 21-JUL-09:45 0.00 0.05 0.00 -0.7 0.00 0.00 115.09 96.26 1083.81 6996.00 0.00 158.72 0.00 0.00 0.00 0.00 0.00 -589.3
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 04-JUL-18:30 0.00 0.06 0.00 -1.0 0.00 0.00 423.87 673.81 1713.00 6355.35 0.00 344.86 1649.14 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 28-JUN-19:25 0.00 0.05 0.00 -0.5 0.00 0.00 425.13 746.73 1650.38 134.84 0.00 267.95 2133.45 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 21-JUL-08:57 0.00 0.04 0.00 -0.7 0.00 0.00 194.42 141.18 1145.20 7732.07 0.00 115.37 0.00 0.00 0.00 0.00 0.00 -1513.1
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 20-SEP-16:27 0.00 0.04 0.00 -1.0 0.00 0.00 140.35 359.36 1343.44 8902.98 0.00 66.11 157.34 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 26-SEP-14:25 0.00 0.02 0.00 -0.5 0.00 0.00 115.09 96.26 1084.62 3023.19 0.00 18.32 1082.22 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 17-AUG-09:50 0.00 0.03 0.00 -0.7 0.00 0.00 115.09 96.26 1083.81 7567.61 0.00 35.94 0.00 0.00 0.00 0.00 0.00 -892.1
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 13-JUN-18:10 0.00 0.05 0.00 -1.0 0.00 0.00 426.76 673.81 1713.00 7796.75 0.00 112.00 143.75 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 04-JUL-19:05 0.00 0.05 0.00 -0.5 0.00 0.00 425.87 746.73 1650.38 744.35 0.00 79.86 1454.77 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 21-JUL-08:57 0.00 0.04 0.00 -0.7 0.00 0.00 194.42 141.18 1145.20 7720.70 0.00 50.35 0.00 0.00 0.00 0.00 0.00 -1411.1
LIVING_UNIT3_BACKROW_TOPFLOOR 21-JUL-09:45 0.00 0.05 0.00 -0.7 0.00 0.00 115.09 96.26 1083.81 6471.25 0.00 157.78 0.00 0.00 0.00 0.00 0.00 -88.4
LIVING_UNIT3_FRONTROW_TOPFLOOR 21-JUL-10:00 0.00 0.05 0.00 -0.7 0.00 0.00 115.09 96.26 1083.81 6722.57 0.00 167.44 0.00 0.00 0.00 0.00 0.00 -197.4
LIVING_UNIT1_FRONTROW_TOPFLOOR 20-AUG-17:30 0.00 0.07 0.00 -1.0 0.00 0.00 263.17 500.54 1675.86 7337.53 0.00 318.50 1447.97 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 21-JUL-19:43 0.00 0.05 0.00 -0.6 0.00 0.00 425.74 746.73 1650.38 107.33 0.00 162.27 3103.60 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 21-JUL-19:57 0.00 0.05 0.00 -0.6 0.00 0.00 425.37 746.73 1650.38 94.35 0.00 146.04 3050.67 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 26-JUN-17:30 0.00 0.07 0.00 -1.0 0.00 0.00 263.17 500.54 1655.83 8474.13 0.00 416.47 408.79 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 04-JUL-18:10 0.00 1.14 0.00 -12.4 0.00 0.00 7672.71 12128.50 30834.00 54580.67 0.00 41782.60 10761.54 0.00 0.00 0.00 -22475.5 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 04-MAR-08:20 -1481.6 0.00 14219.97 0.00 0.00 0.00 218.64 141.18 1167.53 812.11 0.00 0.00 0.00 0.00 0.00 0.00 -1043.5 -14034.3
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 18-JAN-17:03 -1474.0 0.00 9321.71 0.00 0.00 0.00 308.97 500.54 1655.83 0.00 0.00 0.00 0.00 0.00 -621.1 0.00 -715.8 -8976.2
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 04-FEB-21:42 -1657.0 0.00 11025.11 0.00 0.00 0.00 556.77 564.71 1566.21 0.00 0.00 0.00 0.00 0.00 -1826.2 0.00 -891.4 -9338.3
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 22-DEC-09:40 -1810.6 0.00 16470.14 0.00 0.00 0.00 127.36 96.26 1083.81 0.00 0.00 0.00 0.00 0.00 -968.7 0.00 -1060.3 -13938.0
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 13-DEC-09:12 -1676.4 0.00 10126.06 0.00 0.00 0.00 128.99 96.26 1083.81 0.00 0.00 0.00 0.00 0.00 -300.9 0.00 -700.0 -8757.9
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 14-JAN-23:40 -1717.0 0.00 8742.42 0.00 0.00 0.00 526.25 128.34 1155.04 0.00 0.00 0.00 0.00 0.00 -1857.7 0.00 -884.0 -6093.3
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 04-MAR-09:24 -1336.3 0.00 10717.24 0.00 0.00 0.00 130.89 96.26 1112.20 2465.06 0.00 0.00 0.00 0.00 0.00 0.00 -402.2 -12783.2
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 07-FEB-02:15 -1842.2 0.00 6135.53 0.00 0.00 0.00 542.25 51.34 865.75 0.00 0.00 0.00 0.00 0.00 -827.0 0.00 -348.8 -4576.8
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 13-DEC-00:30 -1847.8 0.00 11264.49 0.00 0.00 0.00 556.67 51.34 960.66 0.00 0.00 0.00 0.00 0.00 -1958.4 0.00 -392.5 -8634.4
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 15-DEC-09:28 -1896.1 0.00 16749.77 0.00 0.00 0.00 129.26 96.26 1083.81 0.00 0.00 0.00 0.00 0.00 -1003.1 0.00 -471.7 -14688.2
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 15-DEC-09:18 -1967.3 0.00 10517.02 0.00 0.00 0.00 127.33 96.26 1083.81 0.00 0.00 0.00 0.00 0.00 -468.1 0.00 -363.6 -9025.4
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 23-NOV-03:33 -1208.5 0.00 9228.74 0.00 0.00 0.00 552.19 51.34 846.84 0.00 0.00 0.00 0.00 0.00 -1360.7 0.00 -218.2 -7891.7
LIVING_UNIT3_BACKROW_TOPFLOOR 04-APR-04:13 -1259.5 0.00 9666.49 0.00 0.00 0.00 553.41 154.01 831.04 0.00 0.00 0.00 0.00 0.00 -1462.1 0.00 -615.3 -7868.0
LIVING_UNIT3_FRONTROW_TOPFLOOR 20-DEC-22:42 -1582.1 0.00 11965.42 0.00 0.00 0.00 564.29 314.44 1333.61 0.00 0.00 0.00 0.00 0.00 -1875.0 0.00 -1516.8 -9204.0
LIVING_UNIT1_FRONTROW_TOPFLOOR 02-FEB-08:45 -1590.8 0.00 15522.59 0.00 0.00 0.00 228.23 141.18 1145.20 1776.52 0.00 0.00 0.00 0.00 0.00 0.00 -840.8 -16382.1
LIVING_UNIT2_BACKROW_TOPFLOOR 22-DEC-10:13 -1739.1 0.00 11618.39 0.00 0.00 0.00 131.55 96.26 1078.58 0.00 0.00 0.00 0.00 0.00 -311.8 0.00 -850.2 -10023.7
LIVING_UNIT2_FRONTROW_TOPFLOOR 18-JAN-17:03 -1496.8 0.00 10319.17 0.00 0.00 0.00 305.23 500.54 1655.83 0.00 0.00 0.00 0.00 0.00 -637.1 0.00 -730.7 -9916.1
LIVING_UNIT1_BACKROW_TOPFLOOR 15-DEC-09:45 -1790.7 0.00 16851.25 0.00 0.00 0.00 130.17 96.26 1083.81 0.00 0.00 0.00 0.00 0.00 -775.6 0.00 -996.4 -14598.8
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 06-FEB-05:00 -33760.0 0.00 100304.85 0.00 0.00 0.00 9472.35 2772.23 14958.72 0.00 0.00 6873.84 22104.28 0.00 -30109.1 0.00 -92617.1 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 530.4129 0.0000 2.0000 1.0000 0.0000 530.4129 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 252.7664 0.0000 2.0000 1.0000 0.0000 252.7664 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 371.4410 0.0000 2.0000 1.0000 0.0000 371.4410 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 520.9229 0.0000 2.0000 1.0000 0.0000 520.9229 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 254.8398 0.0000 2.0000 1.0000 0.0000 254.8398 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 364.1355 0.0000 2.0000 1.0000 0.0000 364.1355 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 513.0192 0.0000 2.0000 1.0000 0.0000 513.0192 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 246.6986 0.0000 2.0000 1.0000 0.0000 246.6986 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 378.0055 0.0000 2.0000 1.0000 0.0000 378.0055 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 504.4224 0.0000 2.0000 1.0000 0.0000 504.4224 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 247.3017 0.0000 2.0000 1.0000 0.0000 247.3017 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 370.4951 0.0000 2.0000 1.0000 0.0000 370.4951 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 546.6036 0.0000 2.0000 1.0000 0.0000 546.6036 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 284.6756 0.0000 2.0000 1.0000 0.0000 284.6756 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 381.6450 0.0000 2.0000 1.0000 0.0000 381.6450 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 548.1203 0.0000 2.0000 1.0000 0.0000 548.1203 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 292.1854 0.0000 2.0000 1.0000 0.0000 292.1854 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 372.9653 0.0000 2.0000 1.0000 0.0000 372.9653 0.0000 1.0000 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 530.4129 0.0000 2.0000 1.0000 0.0000 530.4129 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 252.7664 0.0000 2.0000 1.0000 0.0000 252.7664 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 371.4410 0.0000 2.0000 1.0000 0.0000 371.4410 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 520.9229 0.0000 2.0000 1.0000 0.0000 520.9229 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 254.8398 0.0000 2.0000 1.0000 0.0000 254.8398 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 364.1355 0.0000 2.0000 1.0000 0.0000 364.1355 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 513.0192 0.0000 2.0000 1.0000 0.0000 513.0192 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 246.6986 0.0000 2.0000 1.0000 0.0000 246.6986 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 378.0055 0.0000 2.0000 1.0000 0.0000 378.0055 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 504.4224 0.0000 2.0000 1.0000 0.0000 504.4224 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 247.3017 0.0000 2.0000 1.0000 0.0000 247.3017 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 370.4951 0.0000 2.0000 1.0000 0.0000 370.4951 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 546.6036 0.0000 2.0000 1.0000 0.0000 546.6036 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 284.6756 0.0000 2.0000 1.0000 0.0000 284.6756 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 381.6450 0.0000 2.0000 1.0000 0.0000 381.6450 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 548.1203 0.0000 2.0000 1.0000 0.0000 548.1203 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 292.1854 0.0000 2.0000 1.0000 0.0000 292.1854 0.0000 1.0000 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 372.9653 0.0000 2.0000 1.0000 0.0000 372.9653 0.0000 1.0000 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 530.4129 530.4129 530.4129 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 252.7664 252.7664 252.7664 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 371.4410 371.4410 371.4410 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 520.9229 520.9229 520.9229 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 254.8398 254.8398 254.8398 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 364.1355 364.1355 364.1355 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 513.0192 513.0192 513.0192 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 246.6986 246.6986 246.6986 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 378.0055 378.0055 378.0055 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 504.4224 504.4224 504.4224 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 247.3017 247.3017 247.3017 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 370.4951 370.4951 370.4951 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 372.9653 372.9653 372.9653 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 381.6450 381.6450 381.6450 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 546.6036 546.6036 546.6036 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 292.1854 292.1854 292.1854 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 284.6756 284.6756 284.6756 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 548.1203 548.1203 548.1203 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 530.4129 530.4129 530.4129 530.4129 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 252.7664 252.7664 252.7664 252.7664 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 371.4410 371.4410 371.4410 371.4410 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 520.9229 520.9229 520.9229 520.9229 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 254.8398 254.8398 254.8398 254.8398 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 364.1355 364.1355 364.1355 364.1355 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 513.0192 513.0192 513.0192 513.0192 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 246.6986 246.6986 246.6986 246.6986 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 378.0055 378.0055 378.0055 378.0055 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 504.4224 504.4224 504.4224 504.4224 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 247.3017 247.3017 247.3017 247.3017 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 370.4951 370.4951 370.4951 370.4951 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 546.6036 546.6036 546.6036 546.6036 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 284.6756 284.6756 284.6756 284.6756 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 381.6450 381.6450 381.6450 381.6450 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 548.1203 548.1203 548.1203 548.1203 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 292.1854 292.1854 292.1854 292.1854 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 372.9653 372.9653 372.9653 372.9653 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 530.4129 530.4129 530.4129 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 252.7664 252.7664 252.7664 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 371.4410 371.4410 371.4410 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 520.9229 520.9229 520.9229 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 254.8398 254.8398 254.8398 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 364.1355 364.1355 364.1355 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 513.0192 513.0192 513.0192 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 246.6986 246.6986 246.6986 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 378.0055 378.0055 378.0055 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 504.4224 504.4224 504.4224 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 247.3017 247.3017 247.3017 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 370.4951 370.4951 370.4951 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 372.9653 372.9653 372.9653 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 381.6450 381.6450 381.6450 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 546.6036 546.6036 546.6036 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 292.1854 292.1854 292.1854 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 284.6756 284.6756 284.6756 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 548.1203 548.1203 548.1203 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 530.4129 530.4129 530.4129 530.4129 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 252.7664 252.7664 252.7664 252.7664 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 371.4410 371.4410 371.4410 371.4410 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 520.9229 520.9229 520.9229 520.9229 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 254.8398 254.8398 254.8398 254.8398 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 364.1355 364.1355 364.1355 364.1355 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 513.0192 513.0192 513.0192 513.0192 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 246.6986 246.6986 246.6986 246.6986 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 378.0055 378.0055 378.0055 378.0055 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 504.4224 504.4224 504.4224 504.4224 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 247.3017 247.3017 247.3017 247.3017 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 370.4951 370.4951 370.4951 370.4951 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 546.6036 546.6036 546.6036 546.6036 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 284.6756 284.6756 284.6756 284.6756 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 381.6450 381.6450 381.6450 381.6450 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 548.1203 548.1203 548.1203 548.1203 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 292.1854 292.1854 292.1854 292.1854 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 372.9653 372.9653 372.9653 372.9653 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

Sec1.1A-General Information

Data
Weather File ANNUAL ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Total gross floor area [ft2] 39005.22
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
CRAWLSPACE 7794.39 0.00 7794.39 0.00
BREEZEWAY 1798.16 0.00 1798.16 0.00
ATTIC 7802.71 0.00 7802.71 0.00
Totals 39005.22 21609.96 17395.26  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 2148.50
Number of hours cooling loads not met 13.33
Number of hours not met 2161.83


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [kWh] Electricity Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Gasoline Use [therm] Gasoline Demand [Btu/h] Diesel Use [kBtu] Diesel Demand [Btu/h] Coal Use [kBtu] Coal Demand [Btu/h] Fuel Oil No 1 Use [kBtu] Fuel Oil No 1 Demand [Btu/h] Fuel Oil No 2 Use [kBtu] Fuel Oil No 2 Demand [Btu/h] Propane Use [kBtu] Propane Demand [Btu/h] Other Fuel 1 Use [kBtu] Other Fuel 1 Demand [Btu/h] Other Fuel 2 Use [kBtu] Other Fuel 2 Demand [Btu/h] District Cooling Use [ton-hrs] District Cooling Demand [ton] District Heating Use [kBtu] District Heating Demand [Btu/h]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 1188.14 131282.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 19712.95 13117.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- General 12093.82 3939.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Exterior-Lights 5508.71 1257.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- dishwasher 2758.31 880.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- refrigerator 12036.11 1639.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- clotheswasher 1408.53 381.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_dryer 12502.11 3196.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_range 9058.39 3721.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_mels 46926.68 7929.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- IECC_adj 3113.66 526.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 6882.57 2577.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation 5068.29 578.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 2383.38 221820.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 299798.81 468014.65
Natural Gas 0.00 357151.64
Additional 0.00 0.00
Total 299798.81 825166.29


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting (All) 0.31
Space Heating 0.00
Space Cooling 0.51
Fans (All) 0.31
Service Water Heating 0.00
Receptacle Equipment 2.25
Miscellaneous (All) 3.51
Subtotal 3.51


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.89
Service Water Heating 1.79
Miscellaneous (All) 2.68
Subtotal 2.68


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 5.00
Space Heating 14.40
Space Cooling 8.16
Fans (All) 4.95
Service Water Heating 28.88
Receptacle Equipment 36.33
Miscellaneous 2.28


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
OCCUPANCY 6031. 8760.
INTERIORLIGHTING 2852. 8760.
INTERIORLIGHTINGHE 3070. 8760.
INTERIORLIGHTINGHE_OS 2910. 8760.
INTERIORLIGHTINGHE_VS 2149. 8760.
EXTERIORLIGHTING 4380. 4380.
REFRIGERATOR 7343. 8760.
MISCPLUGLOAD 5918. 8760.
COOKINGRANGE 2434. 8760.
DHW_SCH 365. 8760.
DISHWASHER 2799. 8760.
CLOTHESWASHER 3297. 8760.
CLOTHESDRYER 3911. 8760.
SINKS 4179. 8760.
SHOWERS 2640. 8760.
BATHS 2586. 8760.
DHWDIST 4662. 8760.
SHADING_2012IECC 0. 0.
SINKSENSSCHEDULE 6025. 8760.
SINKLATSCHEDULE 2735. 8760.
SHOWERSENSSCHEDULE 4492. 8760.
SHOWERLATSCHEDULE 4268. 8760.
BATHSENSSCHEDULE 8760. 8760.
BATHLATSCHEDULE 0. 0.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [F] Days with Same 11am Value 11pm First Wednesday [F] Days with Same 11pm Value
HEATING_SCH THERMOSTAT_LIVING DUAL SP CONTROL January 72.00 365 72.00 365
COOLING_SCH THERMOSTAT_LIVING DUAL SP CONTROL July 75.00 365 75.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
CRAWLSPACE 8392.33 367.67 0.00 0.00 0.00
BREEZEWAY 7715.67 1044.33 0.00 0.00 0.00
ATTIC 7250.00 779.00 546.00 185.00 0.00
Min 7250.00 0.00 0.00 0.00 0.00
Max 8760.00 1044.33 546.00 185.00 0.00
Average 8620.86 104.33 26.00 8.81 0.00
Sum 181038.00 2191.00 546.00 185.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 9125.00 0.00 0.00 0.00 0.00
Average 7821.43 0.00 0.00 0.00 0.00
Sum 164250.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
CRAWLSPACE 8582.83 177.17 0.00 0.00 0.00
BREEZEWAY 8605.83 154.17 0.00 0.00 0.00
ATTIC 7456.17 981.83 273.17 48.83 0.00
Min 7456.17 0.00 0.00 0.00 0.00
Max 8760.00 981.83 273.17 48.83 0.00
Average 8682.13 62.53 13.01 2.33 0.00
Sum 182324.83 1313.17 273.17 48.83 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 9125.00 0.00 0.00 0.00 0.00
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 9125.00 0.00 0.00 0.00 0.00
Average 7821.43 0.00 0.00 0.00 0.00
Sum 164250.00 0.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (F) SET ≤ 12.2°C OccupantHours (F) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (F) SET > 30°C OccupantHours (F) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2021-05-12 10:31:15

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 117.111 4.974 435.590 21.149 28.217
February 134.706 6.480 329.819 15.645 26.778
March 192.139 9.456 223.550 8.935 37.203
April 344.542 18.980 64.550 2.180 35.806
May 478.111 26.053 21.715 0.617 31.145
June 625.772 43.545 3.556 0.077 44.167
July 741.833 56.766 0.000 0.000 56.766
August 732.556 52.831 0.000 0.000 52.831
September 592.850 38.628 0.000 0.000 38.628
October 394.364 23.363 101.739 3.732 36.361
November 179.889 7.290 271.880 10.313 23.886
December 107.208 3.672 435.854 20.500 24.830
           
Annual Sum or Average 4641.080 292.038 1888.253 83.150 436.617
Minimum of Months 107.208 3.672 0.000 0.000 23.886
Maximum of Months 741.833 56.766 435.854 21.149 56.766



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 119.611 2.728 389.345 7.907 12.568
February 122.639 3.119 295.621 5.829 10.213
March 184.111 4.508 207.748 3.374 9.450
April 360.822 10.657 68.136 0.944 12.058
May 511.306 16.333 23.107 0.276 16.813
June 655.906 29.354 1.667 0.016 29.380
July 744.000 41.059 0.000 0.000 41.059
August 743.333 38.206 0.000 0.000 38.206
September 651.606 28.345 0.000 0.000 28.345
October 429.747 16.457 74.072 1.235 18.030
November 193.100 4.242 218.068 3.362 8.248
December 92.014 1.517 377.409 7.363 9.673
           
Annual Sum or Average 4808.195 196.524 1655.174 30.307 234.042
Minimum of Months 92.014 1.517 0.000 0.000 8.248
Maximum of Months 744.000 41.059 389.345 7.907 41.059



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 122.157 3.444 373.133 19.890 33.514
February 136.425 4.318 273.281 14.409 28.351
March 235.122 7.985 169.361 7.817 29.213
April 425.689 18.979 41.556 1.822 27.300
May 546.687 26.828 11.333 0.438 29.581
June 649.611 44.806 0.667 0.028 45.149
July 741.833 58.072 0.000 0.000 58.072
August 733.583 53.662 0.000 0.000 53.662
September 614.583 38.362 0.000 0.000 38.362
October 440.093 22.150 66.800 3.151 33.662
November 206.947 5.641 194.222 8.862 27.197
December 86.043 1.648 348.337 18.705 30.864
           
Annual Sum or Average 4938.774 285.895 1478.690 75.121 434.927
Minimum of Months 86.043 1.648 0.000 0.000 27.197
Maximum of Months 741.833 58.072 373.133 19.890 58.072



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 6.514 0.051 484.215 26.384 53.770
February 39.967 1.033 371.206 19.145 43.783
March 122.889 3.819 299.839 11.600 34.552
April 303.292 13.924 106.458 3.239 26.345
May 475.678 23.989 32.112 0.846 27.376
June 631.892 43.478 2.778 0.064 44.000
July 741.667 55.310 0.000 0.000 55.310
August 731.486 48.371 0.000 0.000 48.371
September 577.050 29.958 0.000 0.000 29.958
October 313.819 12.531 152.764 5.285 27.107
November 30.750 0.481 349.517 14.414 38.531
December 0.000 0.000 466.954 25.983 66.603
           
Annual Sum or Average 3975.003 232.944 2265.841 106.960 495.707
Minimum of Months 0.000 0.000 0.000 0.000 26.345
Maximum of Months 741.667 55.310 484.215 26.384 66.603



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 584.071 12.860 21.703
February 6.044 0.019 467.002 9.645 16.299
March 46.222 0.387 323.997 5.033 9.533
April 276.461 6.296 96.358 1.308 8.714
May 503.872 14.544 26.981 0.310 15.286
June 659.194 29.475 0.833 0.009 29.524
July 744.000 39.862 0.000 0.000 39.862
August 743.333 34.064 0.000 0.000 34.064
September 639.211 19.922 0.000 0.000 19.922
October 295.069 6.301 137.080 2.080 10.162
November 0.667 0.001 415.449 6.962 15.424
December 0.000 0.000 644.838 13.859 19.610
           
Annual Sum or Average 3914.075 150.871 2696.609 52.066 240.103
Minimum of Months 0.000 0.000 0.000 0.000 8.714
Maximum of Months 744.000 39.862 644.838 13.859 39.862



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 611.156 28.025 34.168
February 13.250 0.134 451.810 20.390 27.106
March 124.522 1.534 231.362 9.598 22.932
April 375.583 13.381 50.417 2.057 21.723
May 536.091 24.749 11.583 0.438 27.469
June 651.333 44.673 0.667 0.025 45.030
July 741.833 56.583 0.000 0.000 56.583
August 733.250 49.444 0.000 0.000 49.444
September 608.861 30.075 0.000 0.000 30.075
October 362.672 10.463 100.594 4.124 22.466
November 3.861 0.026 380.035 14.557 25.766
December 0.000 0.000 684.537 30.187 34.350
           
Annual Sum or Average 4151.258 231.062 2522.161 109.401 397.112
Minimum of Months 0.000 0.000 0.000 0.000 21.723
Maximum of Months 741.833 56.583 684.537 30.187 56.583



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 154.694 6.456 349.575 12.884 19.802
February 187.486 8.320 259.341 9.249 19.522
March 248.056 11.518 142.088 4.437 24.588
April 417.667 22.397 32.500 0.870 28.738
May 568.169 30.151 10.783 0.241 32.011
June 679.428 46.844 0.611 0.010 47.031
July 744.000 59.790 0.000 0.000 59.790
August 744.000 56.851 0.000 0.000 56.851
September 670.972 43.217 0.000 0.000 43.217
October 461.050 26.982 59.657 1.851 31.118
November 252.570 9.854 186.046 5.413 17.442
December 167.188 5.542 353.108 12.584 18.399
           
Annual Sum or Average 5295.281 327.921 1393.711 47.539 398.509
Minimum of Months 154.694 5.542 0.000 0.000 17.442
Maximum of Months 744.000 59.790 353.108 12.884 59.790



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 174.959 4.568 251.908 3.882 9.513
February 196.238 5.073 181.283 2.690 8.614
March 270.917 6.817 69.641 1.040 8.938
April 483.922 14.456 12.989 0.167 14.845
May 629.242 20.822 2.031 0.024 20.877
June 703.833 32.809 0.000 0.000 32.809
July 744.000 43.775 0.000 0.000 43.775
August 744.000 41.877 0.000 0.000 41.877
September 714.139 33.210 0.000 0.000 33.210
October 517.667 20.641 30.578 0.448 21.321
November 300.317 7.447 82.424 1.173 9.324
December 200.363 3.778 241.918 3.619 7.995
           
Annual Sum or Average 5679.596 235.273 872.772 13.042 253.098
Minimum of Months 174.959 3.778 0.000 0.000 7.995
Maximum of Months 744.000 43.775 251.908 3.882 43.775



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 165.373 5.320 239.836 11.714 34.587
February 193.493 6.456 166.719 8.054 28.511
March 298.131 11.014 55.875 2.950 30.523
April 504.281 23.799 6.889 0.367 29.584
May 624.250 31.958 0.667 0.030 33.747
June 690.194 48.548 0.000 0.000 48.619
July 744.000 61.269 0.000 0.000 61.269
August 744.000 57.782 0.000 0.000 57.782
September 679.583 43.218 0.000 0.000 43.218
October 498.187 26.438 29.042 1.349 34.049
November 286.703 8.866 75.028 3.791 29.872
December 168.789 3.591 226.189 11.085 30.955
           
Annual Sum or Average 5596.984 328.260 800.244 39.339 462.716
Minimum of Months 165.373 3.591 0.000 0.000 28.511
Maximum of Months 744.000 61.269 239.836 11.714 61.269



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 9.681 0.067 395.186 16.438 44.175
February 63.472 1.366 288.765 11.460 35.073
March 163.583 4.970 175.657 5.433 26.239
April 382.669 16.953 43.444 1.144 23.267
May 566.822 28.125 12.264 0.264 29.774
June 683.347 46.890 0.250 0.004 46.973
July 744.000 58.402 0.000 0.000 58.402
August 744.000 52.528 0.000 0.000 52.528
September 663.828 34.585 0.000 0.000 34.585
October 377.903 15.219 83.857 2.496 23.568
November 61.486 0.787 243.934 7.943 29.139
December 0.000 0.000 408.877 17.178 52.629
           
Annual Sum or Average 4460.792 259.893 1652.234 62.360 456.352
Minimum of Months 0.000 0.000 0.000 0.000 23.267
Maximum of Months 744.000 58.402 408.877 17.178 58.402



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 453.761 7.134 15.249
February 17.000 0.108 326.460 5.060 10.305
March 92.611 0.970 135.882 1.847 4.586
April 403.592 9.229 21.356 0.284 10.075
May 620.139 18.958 2.350 0.028 19.031
June 704.667 32.993 0.000 0.000 32.993
July 744.000 42.592 0.000 0.000 42.592
August 744.000 37.867 0.000 0.000 37.867
September 712.694 24.953 0.000 0.000 24.953
October 377.333 9.051 58.412 0.806 10.664
November 20.500 0.107 223.719 3.170 7.730
December 0.000 0.000 487.318 7.817 15.703
           
Annual Sum or Average 4436.536 176.828 1709.257 26.147 231.749
Minimum of Months 0.000 0.000 0.000 0.000 4.586
Maximum of Months 744.000 42.592 487.318 7.817 42.592



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 419.193 17.783 31.920
February 33.433 0.334 286.021 12.163 25.255
March 195.322 3.259 88.972 3.971 23.332
April 488.139 17.855 10.500 0.520 23.821
May 623.708 29.872 0.833 0.035 31.700
June 691.417 48.451 0.000 0.000 48.521
July 744.000 59.822 0.000 0.000 59.822
August 744.000 53.654 0.000 0.000 53.654
September 677.194 35.057 0.000 0.000 35.057
October 433.944 14.008 41.889 1.817 22.777
November 20.250 0.191 167.892 6.986 27.170
December 0.000 0.000 480.616 19.388 34.551
           
Annual Sum or Average 4651.408 262.505 1495.916 62.663 417.581
Minimum of Months 0.000 0.000 0.000 0.000 22.777
Maximum of Months 744.000 59.822 480.616 19.388 59.822



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 115.056 4.293 381.275 19.342 32.046
February 137.367 6.087 276.521 13.690 30.545
March 201.833 9.467 172.081 6.881 36.647
April 379.192 21.017 57.953 1.796 31.367
May 533.919 29.885 20.325 0.555 32.645
June 658.417 49.034 2.056 0.037 49.569
July 744.000 63.567 0.000 0.000 63.567
August 743.028 59.440 0.000 0.000 59.440
September 647.261 43.136 0.000 0.000 43.136
October 419.883 25.034 70.025 2.820 37.116
November 193.531 7.035 203.700 8.398 29.631
December 105.297 3.061 387.359 19.113 28.569
           
Annual Sum or Average 4878.782 321.056 1571.294 72.632 474.276
Minimum of Months 105.297 3.061 0.000 0.000 28.569
Maximum of Months 744.000 63.567 387.359 19.342 63.567



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 122.833 2.397 351.989 7.134 12.077
February 130.667 3.197 260.461 5.094 9.616
March 201.306 4.961 161.835 2.578 8.720
April 412.494 13.214 43.442 0.589 14.196
May 577.856 20.683 13.264 0.162 20.951
June 686.875 35.221 0.000 0.000 35.221
July 744.000 47.917 0.000 0.000 47.917
August 744.000 44.887 0.000 0.000 44.887
September 692.972 33.411 0.000 0.000 33.411
October 468.275 18.854 57.143 0.985 20.213
November 214.472 4.531 179.154 2.814 8.090
December 92.333 1.296 350.160 6.816 9.202
           
Annual Sum or Average 5088.083 230.571 1417.449 26.172 264.501
Minimum of Months 92.333 1.296 0.000 0.000 8.090
Maximum of Months 744.000 47.917 351.989 7.134 47.917



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 118.286 2.962 340.517 16.806 32.177
February 136.340 4.195 242.636 11.792 27.199
March 246.912 8.262 127.242 5.571 28.329
April 464.025 21.396 25.833 1.046 27.819
May 592.236 30.859 4.694 0.183 32.985
June 675.694 50.127 0.000 0.000 50.439
July 744.000 64.439 0.000 0.000 64.439
August 743.333 59.882 0.000 0.000 59.882
September 661.194 42.839 0.000 0.000 42.839
October 467.275 24.007 51.769 2.314 33.513
November 218.641 5.568 162.000 6.888 25.807
December 76.069 1.315 326.808 16.084 29.255
           
Annual Sum or Average 5144.006 315.851 1281.500 60.685 454.684
Minimum of Months 76.069 1.315 0.000 0.000 25.807
Maximum of Months 744.000 64.439 340.517 16.806 64.439



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 4.806 0.027 454.340 24.111 54.020
February 52.583 1.305 338.792 16.996 43.675
March 144.750 4.929 244.577 9.147 33.244
April 350.419 17.357 74.544 2.184 28.557
May 533.729 28.679 20.500 0.541 32.006
June 661.939 49.405 2.028 0.036 49.727
July 744.000 62.918 0.000 0.000 62.918
August 743.083 56.636 0.000 0.000 56.636
September 638.769 36.796 0.000 0.000 36.796
October 355.664 15.834 117.615 4.131 29.157
November 42.250 0.646 301.863 12.292 37.811
December 0.000 0.000 441.829 24.038 68.865
           
Annual Sum or Average 4271.993 274.531 1996.088 93.475 533.411
Minimum of Months 0.000 0.000 0.000 0.000 28.557
Maximum of Months 744.000 62.918 454.340 24.111 68.865



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 543.859 11.722 20.894
February 16.250 0.141 418.590 8.454 14.041
March 87.000 1.176 237.925 3.779 8.022
April 353.181 9.796 58.419 0.824 11.213
May 569.819 19.613 15.708 0.184 19.973
June 690.472 35.725 0.000 0.000 35.725
July 744.000 47.445 0.000 0.000 47.445
August 744.000 42.315 0.000 0.000 42.315
September 687.722 27.291 0.000 0.000 27.291
October 354.881 9.816 98.660 1.610 12.381
November 9.167 0.042 356.270 5.949 11.542
December 0.000 0.000 607.475 12.812 19.458
           
Annual Sum or Average 4256.492 193.360 2336.906 45.333 270.299
Minimum of Months 0.000 0.000 0.000 0.000 8.022
Maximum of Months 744.000 47.445 607.475 12.812 47.445



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 552.853 23.426 32.291
February 25.764 0.316 394.714 16.314 25.486
March 155.181 2.876 159.169 6.447 23.353
April 436.542 17.314 28.847 1.130 23.737
May 587.875 29.574 4.861 0.183 31.516
June 676.806 50.297 0.000 0.000 50.578
July 744.000 63.605 0.000 0.000 63.605
August 743.333 57.134 0.000 0.000 57.134
September 657.472 36.841 0.000 0.000 36.841
October 398.381 14.111 70.308 2.839 24.853
November 8.222 0.040 301.508 11.039 25.190
December 0.000 0.000 637.830 25.624 32.302
           
Annual Sum or Average 4433.575 272.108 2150.091 87.003 426.885
Minimum of Months 0.000 0.000 0.000 0.000 23.353
Maximum of Months 744.000 63.605 637.830 25.624 63.605



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2180.93 0.00 0.00
February 1759.15 0.00 0.00
March 841.04 0.00 0.00
April 200.97 0.00 0.00
May 51.94 0.00 0.00
June 6.61 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 350.26 0.00 0.00
November 1008.41 0.00 0.00
December 2104.80 0.00 0.00
       
Annual Sum or Average 704.48 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2180.93 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1547.22 0.00 0.00
February 1244.18 0.00 0.00
March 601.11 0.00 0.00
April 166.00 0.00 0.00
May 44.43 0.00 0.00
June 2.67 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 224.84 0.00 0.00
November 631.44 0.00 0.00
December 1441.79 0.00 0.00
       
Annual Sum or Average 488.99 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1547.22 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2050.17 0.00 0.00
February 1620.77 0.00 0.00
March 737.13 0.00 0.00
April 168.84 0.00 0.00
May 37.17 0.00 0.00
June 2.42 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 298.35 0.00 0.00
November 865.97 0.00 0.00
December 1916.84 0.00 0.00
       
Annual Sum or Average 637.61 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2050.17 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2686.47 0.00 0.00
February 2133.54 0.00 0.00
March 1067.57 0.00 0.00
April 294.45 0.00 0.00
May 70.85 0.00 0.00
June 5.59 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 482.24 0.00 0.00
November 1389.06 0.00 0.00
December 2648.10 0.00 0.00
       
Annual Sum or Average 893.22 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2686.47 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2373.25 0.00 0.00
February 1948.37 0.00 0.00
March 859.52 0.00 0.00
April 223.58 0.00 0.00
May 48.85 0.00 0.00
June 1.46 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 357.31 0.00 0.00
November 1237.46 0.00 0.00
December 2552.44 0.00 0.00
       
Annual Sum or Average 795.51 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2552.44 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2843.50 0.00 0.00
February 2264.27 0.00 0.00
March 907.73 0.00 0.00
April 192.92 0.00 0.00
May 37.99 0.00 0.00
June 2.19 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 388.64 0.00 0.00
November 1407.39 0.00 0.00
December 3032.54 0.00 0.00
       
Annual Sum or Average 917.80 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 3032.54 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1350.51 0.00 0.00
February 1058.07 0.00 0.00
March 429.56 0.00 0.00
April 82.66 0.00 0.00
May 20.80 0.00 0.00
June 0.86 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 180.69 0.00 0.00
November 541.59 0.00 0.00
December 1313.21 0.00 0.00
       
Annual Sum or Average 412.37 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1350.51 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 778.16 0.00 0.00
February 588.74 0.00 0.00
March 192.07 0.00 0.00
April 30.19 0.00 0.00
May 3.91 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 84.67 0.00 0.00
November 226.99 0.00 0.00
December 724.36 0.00 0.00
       
Annual Sum or Average 217.75 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 778.16 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1187.56 0.00 0.00
February 891.98 0.00 0.00
March 279.03 0.00 0.00
April 33.87 0.00 0.00
May 2.57 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 128.79 0.00 0.00
November 368.68 0.00 0.00
December 1117.45 0.00 0.00
       
Annual Sum or Average 332.13 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1187.56 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1740.42 0.00 0.00
February 1330.19 0.00 0.00
March 527.78 0.00 0.00
April 110.15 0.00 0.00
May 23.45 0.00 0.00
June 0.36 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 242.99 0.00 0.00
November 800.42 0.00 0.00
December 1810.80 0.00 0.00
       
Annual Sum or Average 545.98 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1810.80 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1351.83 0.00 0.00
February 1051.18 0.00 0.00
March 327.96 0.00 0.00
April 50.29 0.00 0.00
May 4.58 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 144.56 0.00 0.00
November 580.91 0.00 0.00
December 1474.43 0.00 0.00
       
Annual Sum or Average 413.08 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1474.43 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1782.74 0.00 0.00
February 1339.52 0.00 0.00
March 379.76 0.00 0.00
April 48.71 0.00 0.00
May 3.01 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 173.52 0.00 0.00
November 676.56 0.00 0.00
December 1914.39 0.00 0.00
       
Annual Sum or Average 523.62 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1914.39 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1949.08 0.00 0.00
February 1508.78 0.00 0.00
March 634.61 0.00 0.00
April 161.36 0.00 0.00
May 45.54 0.00 0.00
June 3.06 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 263.71 0.00 0.00
November 807.87 0.00 0.00
December 1917.48 0.00 0.00
       
Annual Sum or Average 604.21 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1949.08 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1347.57 0.00 0.00
February 1049.64 0.00 0.00
March 443.81 0.00 0.00
April 99.87 0.00 0.00
May 24.86 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 173.69 0.00 0.00
November 507.23 0.00 0.00
December 1284.76 0.00 0.00
       
Annual Sum or Average 408.54 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1347.57 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1843.51 0.00 0.00
February 1414.38 0.00 0.00
March 564.74 0.00 0.00
April 104.59 0.00 0.00
May 16.89 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 236.90 0.00 0.00
November 719.58 0.00 0.00
December 1754.76 0.00 0.00
       
Annual Sum or Average 551.37 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1843.51 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2419.82 0.00 0.00
February 1872.46 0.00 0.00
March 837.53 0.00 0.00
April 197.44 0.00 0.00
May 44.90 0.00 0.00
June 3.06 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 377.02 0.00 0.00
November 1171.70 0.00 0.00
December 2418.63 0.00 0.00
       
Annual Sum or Average 774.33 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2419.82 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2094.28 0.00 0.00
February 1654.59 0.00 0.00
March 624.07 0.00 0.00
April 135.71 0.00 0.00
May 27.69 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 268.65 0.00 0.00
November 1021.19 0.00 0.00
December 2280.73 0.00 0.00
       
Annual Sum or Average 671.76 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2280.73 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2576.23 0.00 0.00
February 1971.80 0.00 0.00
March 671.02 0.00 0.00
April 116.41 0.00 0.00
May 17.50 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 296.20 0.00 0.00
November 1167.24 0.00 0.00
December 2784.51 0.00 0.00
       
Annual Sum or Average 795.70 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2784.51 0.00 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.05
March 0.00 0.00 0.07
April 0.00 0.00 0.14
May 0.00 0.00 0.18
June 0.00 0.00 0.31
July 0.00 0.00 0.39
August 0.00 0.00 0.37
September 0.00 0.00 0.28
October 0.00 0.00 0.17
November 0.00 0.00 0.05
December 0.00 0.00 0.03
       
Annual Sum or Average 0.00 0.00 0.17
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.39



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.02
March 0.00 0.00 0.03
April 0.00 0.00 0.08
May 0.00 0.00 0.11
June 0.00 0.00 0.21
July 0.00 0.00 0.30
August 0.00 0.00 0.28
September 0.00 0.00 0.21
October 0.00 0.00 0.12
November 0.00 0.00 0.03
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.12
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.30



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.03
March 0.00 0.00 0.06
April 0.00 0.00 0.14
May 0.00 0.00 0.19
June 0.00 0.00 0.33
July 0.00 0.00 0.42
August 0.00 0.00 0.39
September 0.00 0.00 0.29
October 0.00 0.00 0.16
November 0.00 0.00 0.04
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.17
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.42



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.03
April 0.00 0.00 0.10
May 0.00 0.00 0.16
June 0.00 0.00 0.31
July 0.00 0.00 0.38
August 0.00 0.00 0.34
September 0.00 0.00 0.22
October 0.00 0.00 0.09
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.14
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.38



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.04
May 0.00 0.00 0.10
June 0.00 0.00 0.21
July 0.00 0.00 0.29
August 0.00 0.00 0.25
September 0.00 0.00 0.15
October 0.00 0.00 0.04
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.29



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.10
May 0.00 0.00 0.17
June 0.00 0.00 0.33
July 0.00 0.00 0.41
August 0.00 0.00 0.36
September 0.00 0.00 0.22
October 0.00 0.00 0.07
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.14
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.41



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.07
March 0.00 0.00 0.08
April 0.00 0.00 0.16
May 0.00 0.00 0.21
June 0.00 0.00 0.33
July 0.00 0.00 0.42
August 0.00 0.00 0.40
September 0.00 0.00 0.32
October 0.00 0.00 0.19
November 0.00 0.00 0.07
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.20
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.42



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.03
February 0.00 0.00 0.04
March 0.00 0.00 0.05
April 0.00 0.00 0.11
May 0.00 0.00 0.15
June 0.00 0.00 0.24
July 0.00 0.00 0.32
August 0.00 0.00 0.31
September 0.00 0.00 0.25
October 0.00 0.00 0.15
November 0.00 0.00 0.06
December 0.00 0.00 0.03
       
Annual Sum or Average 0.00 0.00 0.15
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.32



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.05
March 0.00 0.00 0.08
April 0.00 0.00 0.17
May 0.00 0.00 0.23
June 0.00 0.00 0.36
July 0.00 0.00 0.44
August 0.00 0.00 0.42
September 0.00 0.00 0.33
October 0.00 0.00 0.19
November 0.00 0.00 0.07
December 0.00 0.00 0.03
       
Annual Sum or Average 0.00 0.00 0.20
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.44



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.03
April 0.00 0.00 0.12
May 0.00 0.00 0.19
June 0.00 0.00 0.33
July 0.00 0.00 0.41
August 0.00 0.00 0.37
September 0.00 0.00 0.25
October 0.00 0.00 0.11
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.15
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.41



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.07
May 0.00 0.00 0.13
June 0.00 0.00 0.24
July 0.00 0.00 0.31
August 0.00 0.00 0.28
September 0.00 0.00 0.19
October 0.00 0.00 0.06
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.11
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.31



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.02
April 0.00 0.00 0.13
May 0.00 0.00 0.21
June 0.00 0.00 0.36
July 0.00 0.00 0.43
August 0.00 0.00 0.39
September 0.00 0.00 0.26
October 0.00 0.00 0.10
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.16
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.43



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.03
February 0.00 0.00 0.05
March 0.00 0.00 0.07
April 0.00 0.00 0.15
May 0.00 0.00 0.21
June 0.00 0.00 0.35
July 0.00 0.00 0.44
August 0.00 0.00 0.42
September 0.00 0.00 0.32
October 0.00 0.00 0.18
November 0.00 0.00 0.05
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.19
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.44



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.03
March 0.00 0.00 0.03
April 0.00 0.00 0.10
May 0.00 0.00 0.15
June 0.00 0.00 0.26
July 0.00 0.00 0.35
August 0.00 0.00 0.33
September 0.00 0.00 0.25
October 0.00 0.00 0.14
November 0.00 0.00 0.03
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.14
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.35



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.03
March 0.00 0.00 0.06
April 0.00 0.00 0.16
May 0.00 0.00 0.22
June 0.00 0.00 0.37
July 0.00 0.00 0.47
August 0.00 0.00 0.44
September 0.00 0.00 0.32
October 0.00 0.00 0.17
November 0.00 0.00 0.04
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.19
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.47



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.03
April 0.00 0.00 0.12
May 0.00 0.00 0.20
June 0.00 0.00 0.35
July 0.00 0.00 0.44
August 0.00 0.00 0.40
September 0.00 0.00 0.27
October 0.00 0.00 0.11
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.16
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.44



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.07
May 0.00 0.00 0.14
June 0.00 0.00 0.26
July 0.00 0.00 0.34
August 0.00 0.00 0.31
September 0.00 0.00 0.20
October 0.00 0.00 0.07
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.12
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.34



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.02
April 0.00 0.00 0.12
May 0.00 0.00 0.21
June 0.00 0.00 0.37
July 0.00 0.00 0.46
August 0.00 0.00 0.42
September 0.00 0.00 0.27
October 0.00 0.00 0.10
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.17
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.46



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1397.95 1040.81
February 0.00 0.00 1408.79 947.38
March 0.00 0.00 1368.43 1018.84
April 0.00 0.00 1286.74 927.11
May 0.00 0.00 1178.03 877.08
June 0.00 0.00 1082.33 779.83
July 0.00 0.00 1019.59 759.11
August 0.00 0.00 1006.13 749.09
September 0.00 0.00 1047.92 755.04
October 0.00 0.00 1135.32 845.28
November 0.00 0.00 1240.24 893.61
December 0.00 0.00 1338.47 996.53
         
Annual Sum or Average 0.00 0.00 1208.01 10589.71
Minimum of Months 0.00 0.00 1006.13 749.09
Maximum of Months 0.00 0.00 1408.79 1040.81



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1397.91 1040.78
February 0.00 0.00 1406.48 945.83
March 0.00 0.00 1368.18 1018.65
April 0.00 0.00 1284.63 925.59
May 0.00 0.00 1176.04 875.59
June 0.00 0.00 1080.27 778.34
July 0.00 0.00 1021.61 760.61
August 0.00 0.00 1006.00 749.00
September 0.00 0.00 1045.52 753.31
October 0.00 0.00 1133.33 843.79
November 0.00 0.00 1240.18 893.57
December 0.00 0.00 1338.63 996.64
         
Annual Sum or Average 0.00 0.00 1207.10 10581.70
Minimum of Months 0.00 0.00 1006.00 749.00
Maximum of Months 0.00 0.00 1406.48 1040.78



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1397.86 1040.75
February 0.00 0.00 1408.67 947.30
March 0.00 0.00 1365.82 1016.89
April 0.00 0.00 1282.21 923.84
May 0.00 0.00 1176.00 875.57
June 0.00 0.00 1082.29 779.80
July 0.00 0.00 1021.64 760.64
August 0.00 0.00 1004.14 747.61
September 0.00 0.00 1047.84 754.98
October 0.00 0.00 1133.17 843.67
November 0.00 0.00 1240.07 893.49
December 0.00 0.00 1340.69 998.18
         
Annual Sum or Average 0.00 0.00 1207.22 10582.73
Minimum of Months 0.00 0.00 1004.14 747.61
Maximum of Months 0.00 0.00 1408.67 1040.75



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1406.96 1047.52
February 0.00 0.00 1416.45 952.53
March 0.00 0.00 1372.78 1022.07
April 0.00 0.00 1286.95 927.26
May 0.00 0.00 1178.15 877.16
June 0.00 0.00 1082.26 779.78
July 0.00 0.00 1021.67 760.66
August 0.00 0.00 1005.95 748.96
September 0.00 0.00 1045.67 753.41
October 0.00 0.00 1139.96 848.74
November 0.00 0.00 1249.32 900.15
December 0.00 0.00 1354.39 1008.38
         
Annual Sum or Average 0.00 0.00 1212.23 10626.64
Minimum of Months 0.00 0.00 1005.95 748.96
Maximum of Months 0.00 0.00 1416.45 1047.52



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1404.78 1045.90
February 0.00 0.00 1416.38 952.48
March 0.00 0.00 1374.79 1023.57
April 0.00 0.00 1286.71 927.09
May 0.00 0.00 1176.06 875.61
June 0.00 0.00 1082.34 779.84
July 0.00 0.00 1019.54 759.08
August 0.00 0.00 1006.10 749.07
September 0.00 0.00 1045.64 753.39
October 0.00 0.00 1139.72 848.55
November 0.00 0.00 1249.76 900.47
December 0.00 0.00 1347.04 1002.91
         
Annual Sum or Average 0.00 0.00 1211.24 10617.95
Minimum of Months 0.00 0.00 1006.10 749.07
Maximum of Months 0.00 0.00 1416.38 1045.90



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1404.71 1045.85
February 0.00 0.00 1413.89 950.81
March 0.00 0.00 1370.33 1020.25
April 0.00 0.00 1284.17 925.26
May 0.00 0.00 1175.84 875.44
June 0.00 0.00 1082.30 779.81
July 0.00 0.00 1019.58 759.11
August 0.00 0.00 1006.16 749.11
September 0.00 0.00 1047.82 754.97
October 0.00 0.00 1135.46 845.38
November 0.00 0.00 1251.48 901.71
December 0.00 0.00 1345.38 1001.67
         
Annual Sum or Average 0.00 0.00 1210.26 10609.37
Minimum of Months 0.00 0.00 1006.16 749.11
Maximum of Months 0.00 0.00 1413.89 1045.85



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1395.69 1039.13
February 0.00 0.00 1406.24 945.66
March 0.00 0.00 1363.83 1015.41
April 0.00 0.00 1282.39 923.98
May 0.00 0.00 1175.87 875.47
June 0.00 0.00 1080.06 778.19
July 0.00 0.00 1021.68 760.67
August 0.00 0.00 1006.02 749.01
September 0.00 0.00 1045.60 753.37
October 0.00 0.00 1131.00 842.06
November 0.00 0.00 1237.78 891.83
December 0.00 0.00 1336.37 994.96
         
Annual Sum or Average 0.00 0.00 1205.74 10569.75
Minimum of Months 0.00 0.00 1006.02 749.01
Maximum of Months 0.00 0.00 1406.24 1039.13



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1393.38 1037.41
February 0.00 0.00 1406.13 945.59
March 0.00 0.00 1361.53 1013.69
April 0.00 0.00 1279.84 922.14
May 0.00 0.00 1173.70 873.85
June 0.00 0.00 1080.30 778.37
July 0.00 0.00 1021.59 760.60
August 0.00 0.00 1006.02 749.01
September 0.00 0.00 1045.67 753.41
October 0.00 0.00 1128.87 840.48
November 0.00 0.00 1235.40 890.12
December 0.00 0.00 1334.04 993.23
         
Annual Sum or Average 0.00 0.00 1204.39 10557.90
Minimum of Months 0.00 0.00 1006.02 749.01
Maximum of Months 0.00 0.00 1406.13 1037.41



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1395.71 1039.14
February 0.00 0.00 1406.20 945.63
March 0.00 0.00 1363.57 1015.21
April 0.00 0.00 1279.75 922.07
May 0.00 0.00 1173.76 873.89
June 0.00 0.00 1080.24 778.32
July 0.00 0.00 1021.67 760.66
August 0.00 0.00 1005.99 748.99
September 0.00 0.00 1045.63 753.39
October 0.00 0.00 1130.94 842.02
November 0.00 0.00 1237.62 891.72
December 0.00 0.00 1336.22 994.85
         
Annual Sum or Average 0.00 0.00 1205.30 10565.90
Minimum of Months 0.00 0.00 1005.99 748.99
Maximum of Months 0.00 0.00 1406.20 1039.14



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1404.74 1045.87
February 0.00 0.00 1413.73 950.70
March 0.00 0.00 1368.25 1018.70
April 0.00 0.00 1284.42 925.44
May 0.00 0.00 1175.93 875.51
June 0.00 0.00 1080.07 778.20
July 0.00 0.00 1021.68 760.67
August 0.00 0.00 1006.01 749.00
September 0.00 0.00 1045.60 753.36
October 0.00 0.00 1135.36 845.31
November 0.00 0.00 1246.90 898.40
December 0.00 0.00 1350.11 1005.20
         
Annual Sum or Average 0.00 0.00 1209.91 10606.37
Minimum of Months 0.00 0.00 1006.01 749.00
Maximum of Months 0.00 0.00 1413.73 1045.87



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1404.75 1045.88
February 0.00 0.00 1413.84 950.78
March 0.00 0.00 1370.42 1020.32
April 0.00 0.00 1282.36 923.95
May 0.00 0.00 1174.00 874.07
June 0.00 0.00 1080.09 778.22
July 0.00 0.00 1021.72 760.70
August 0.00 0.00 1004.03 747.53
September 0.00 0.00 1045.60 753.37
October 0.00 0.00 1135.34 845.29
November 0.00 0.00 1249.08 899.98
December 0.00 0.00 1345.50 1001.76
         
Annual Sum or Average 0.00 0.00 1209.40 10601.84
Minimum of Months 0.00 0.00 1004.03 747.53
Maximum of Months 0.00 0.00 1413.84 1045.88



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1404.80 1045.91
February 0.00 0.00 1413.65 950.65
March 0.00 0.00 1365.95 1016.98
April 0.00 0.00 1280.02 922.27
May 0.00 0.00 1175.64 875.29
June 0.00 0.00 1080.16 778.27
July 0.00 0.00 1021.64 760.64
August 0.00 0.00 1004.16 747.63
September 0.00 0.00 1045.62 753.38
October 0.00 0.00 1133.13 843.65
November 0.00 0.00 1249.31 900.14
December 0.00 0.00 1347.34 1003.13
         
Annual Sum or Average 0.00 0.00 1208.95 10597.93
Minimum of Months 0.00 0.00 1004.16 747.63
Maximum of Months 0.00 0.00 1413.65 1045.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1397.90 1040.78
February 0.00 0.00 1408.84 947.41
March 0.00 0.00 1368.37 1018.79
April 0.00 0.00 1282.42 923.99
May 0.00 0.00 1177.86 876.95
June 0.00 0.00 1080.11 778.23
July 0.00 0.00 1021.68 760.67
August 0.00 0.00 1006.05 749.03
September 0.00 0.00 1045.47 753.27
October 0.00 0.00 1133.19 843.69
November 0.00 0.00 1242.11 894.95
December 0.00 0.00 1338.62 996.64
         
Annual Sum or Average 0.00 0.00 1207.41 10584.41
Minimum of Months 0.00 0.00 1006.05 749.03
Maximum of Months 0.00 0.00 1408.84 1040.78



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1395.72 1039.15
February 0.00 0.00 1408.70 947.32
March 0.00 0.00 1365.88 1016.93
April 0.00 0.00 1282.13 923.79
May 0.00 0.00 1173.81 873.93
June 0.00 0.00 1082.30 779.81
July 0.00 0.00 1019.57 759.10
August 0.00 0.00 1006.12 749.08
September 0.00 0.00 1045.54 753.33
October 0.00 0.00 1131.06 842.11
November 0.00 0.00 1240.02 893.45
December 0.00 0.00 1336.38 994.98
         
Annual Sum or Average 0.00 0.00 1206.11 10572.97
Minimum of Months 0.00 0.00 1006.12 749.08
Maximum of Months 0.00 0.00 1408.70 1039.15



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1397.87 1040.76
February 0.00 0.00 1408.66 947.29
March 0.00 0.00 1363.75 1015.35
April 0.00 0.00 1282.25 923.88
May 0.00 0.00 1173.61 873.79
June 0.00 0.00 1082.28 779.79
July 0.00 0.00 1019.60 759.12
August 0.00 0.00 1006.17 749.12
September 0.00 0.00 1045.62 753.38
October 0.00 0.00 1132.96 843.52
November 0.00 0.00 1240.00 893.43
December 0.00 0.00 1340.61 998.12
         
Annual Sum or Average 0.00 0.00 1206.63 10577.54
Minimum of Months 0.00 0.00 1006.17 749.12
Maximum of Months 0.00 0.00 1408.66 1040.76



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1404.90 1045.99
February 0.00 0.00 1416.27 952.41
March 0.00 0.00 1370.45 1020.34
April 0.00 0.00 1286.95 927.26
May 0.00 0.00 1176.04 875.59
June 0.00 0.00 1080.23 778.32
July 0.00 0.00 1021.60 760.61
August 0.00 0.00 1006.02 749.01
September 0.00 0.00 1045.59 753.36
October 0.00 0.00 1137.55 846.94
November 0.00 0.00 1249.23 900.08
December 0.00 0.00 1351.99 1006.59
         
Annual Sum or Average 0.00 0.00 1211.07 10616.50
Minimum of Months 0.00 0.00 1006.02 749.01
Maximum of Months 0.00 0.00 1416.27 1045.99



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1404.79 1045.90
February 0.00 0.00 1416.13 952.31
March 0.00 0.00 1370.59 1020.44
April 0.00 0.00 1282.38 923.97
May 0.00 0.00 1176.02 875.58
June 0.00 0.00 1080.11 778.23
July 0.00 0.00 1021.67 760.66
August 0.00 0.00 1005.99 748.99
September 0.00 0.00 1045.63 753.39
October 0.00 0.00 1135.48 845.40
November 0.00 0.00 1249.25 900.10
December 0.00 0.00 1347.52 1003.27
         
Annual Sum or Average 0.00 0.00 1210.13 10608.24
Minimum of Months 0.00 0.00 1005.99 748.99
Maximum of Months 0.00 0.00 1416.13 1045.90



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1404.77 1045.89
February 0.00 0.00 1413.82 950.76
March 0.00 0.00 1367.95 1018.48
April 0.00 0.00 1282.34 923.94
May 0.00 0.00 1173.58 873.76
June 0.00 0.00 1082.27 779.79
July 0.00 0.00 1021.65 760.65
August 0.00 0.00 1004.15 747.61
September 0.00 0.00 1045.57 753.34
October 0.00 0.00 1135.32 845.28
November 0.00 0.00 1249.27 900.11
December 0.00 0.00 1347.51 1003.26
         
Annual Sum or Average 0.00 0.00 1209.52 10602.87
Minimum of Months 0.00 0.00 1004.15 747.61
Maximum of Months 0.00 0.00 1413.82 1045.89



Table of Contents

Report: HEATING AND COOLING LOADS

For: CRAWLSPACE

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: BREEZEWAY

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 53.16 998.16
February 60.69 722.29
March 76.91 362.14
April 119.50 75.59
May 143.19 19.15
June 201.16 2.04
July 235.86 0.00
August 229.20 0.00
September 189.45 0.00
October 139.82 141.12
November 71.13 402.31
December 50.07 945.94
     
Annual Sum or Average 1570.14 3668.74
Minimum of Months 50.07 0.00
Maximum of Months 235.86 998.16



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 47.37 546.16
February 48.87 393.21
March 59.71 191.47
April 83.43 43.39
May 98.96 10.88
June 138.41 0.48
July 171.15 0.00
August 167.70 0.00
September 144.93 0.00
October 113.35 71.32
November 63.26 171.55
December 46.00 489.45
     
Annual Sum or Average 1183.14 1917.90
Minimum of Months 46.00 0.00
Maximum of Months 171.15 546.16



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 49.78 982.18
February 54.34 703.18
March 76.66 346.28
April 125.83 75.75
May 150.57 16.34
June 213.63 1.14
July 251.49 0.00
August 241.19 0.00
September 192.70 0.00
October 138.90 140.40
November 68.75 389.86
December 46.68 923.37
     
Annual Sum or Average 1610.52 3578.50
Minimum of Months 46.68 0.00
Maximum of Months 251.49 982.18



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 14.75 1348.93
February 22.10 950.29
March 41.99 479.34
April 91.98 109.38
May 132.62 25.12
June 201.17 1.93
July 228.65 0.00
August 206.84 0.00
September 145.51 0.00
October 80.17 206.65
November 23.13 621.67
December 13.57 1341.77
     
Annual Sum or Average 1202.48 5085.09
Minimum of Months 13.57 0.00
Maximum of Months 228.65 1348.93



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 10.65 952.80
February 13.31 684.54
March 27.67 280.00
April 58.23 59.90
May 89.16 11.40
June 138.80 0.27
July 164.13 0.00
August 145.19 0.00
September 100.07 0.00
October 53.67 111.58
November 18.71 408.29
December 6.55 1001.73
     
Annual Sum or Average 826.13 3510.52
Minimum of Months 6.55 0.00
Maximum of Months 164.13 1001.73



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 9.30 1328.30
February 14.59 940.04
March 37.73 406.09
April 95.71 83.49
May 139.64 16.62
June 213.49 0.97
July 243.91 0.00
August 218.38 0.00
September 147.75 0.00
October 74.34 173.13
November 20.97 591.72
December 4.19 1379.52
     
Annual Sum or Average 1219.99 4919.87
Minimum of Months 4.19 0.00
Maximum of Months 243.91 1379.52



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 72.36 474.55
February 80.33 329.70
March 100.13 140.92
April 143.91 22.62
May 165.68 5.11
June 217.36 0.08
July 250.51 0.00
August 248.50 0.00
September 211.59 0.00
October 164.92 57.30
November 95.18 152.49
December 70.56 447.33
     
Annual Sum or Average 1821.01 1630.10
Minimum of Months 70.56 0.00
Maximum of Months 250.51 474.55



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 75.80 168.51
February 74.43 109.53
March 87.40 48.83
April 109.69 6.55
May 123.76 0.91
June 155.53 0.00
July 185.16 0.00
August 186.41 0.00
September 169.29 0.00
October 140.87 18.91
November 96.04 48.70
December 76.07 146.56
     
Annual Sum or Average 1480.44 548.49
Minimum of Months 74.43 0.00
Maximum of Months 186.41 168.51



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 74.64 513.92
February 77.98 349.31
March 104.46 134.10
April 155.65 16.39
May 178.02 1.21
June 231.98 0.00
July 267.06 0.00
August 261.36 0.00
September 216.51 0.00
October 166.26 56.27
November 97.66 167.90
December 71.04 485.68
     
Annual Sum or Average 1902.62 1724.79
Minimum of Months 71.04 0.00
Maximum of Months 267.06 513.92



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 25.93 738.16
February 34.56 500.41
March 61.50 198.33
April 114.91 35.10
May 155.26 6.23
June 217.88 0.02
July 243.59 0.00
August 226.40 0.00
September 167.10 0.00
October 100.54 88.33
November 36.59 295.86
December 23.47 778.46
     
Annual Sum or Average 1407.74 2640.90
Minimum of Months 23.47 0.00
Maximum of Months 243.59 778.46



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 25.60 347.64
February 29.29 241.41
March 49.45 77.58
April 81.10 12.27
May 113.63 1.09
June 156.34 0.00
July 178.33 0.00
August 164.12 0.00
September 123.96 0.00
October 75.16 33.23
November 39.18 138.70
December 23.45 387.96
     
Annual Sum or Average 1059.61 1239.88
Minimum of Months 23.45 0.00
Maximum of Months 178.33 387.96



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 25.75 730.74
February 31.30 498.39
March 60.21 166.61
April 123.58 22.90
May 166.92 1.37
June 232.08 0.00
July 259.73 0.00
August 238.86 0.00
September 171.65 0.00
October 98.09 73.93
November 39.62 279.45
December 21.96 766.37
     
Annual Sum or Average 1469.75 2539.75
Minimum of Months 21.96 0.00
Maximum of Months 259.73 766.37



Table of Contents

Report: HEATING AND COOLING LOADS

For: ATTIC

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 13.99 1180.28
February 20.63 798.20
March 51.11 304.72
April 118.67 51.11
May 165.18 7.99
June 242.46 0.00
July 279.35 0.00
August 257.26 0.00
September 181.58 0.00
October 95.44 133.18
November 27.13 487.17
December 7.91 1234.04
     
Annual Sum or Average 1460.73 4196.69
Minimum of Months 7.91 0.00
Maximum of Months 279.35 1234.04



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 50.67 867.69
February 56.98 600.99
March 82.24 262.57
April 140.43 45.75
May 171.80 7.74
June 240.73 0.00
July 283.10 0.00
August 272.00 0.00
September 214.55 0.00
October 149.97 109.49
November 71.55 317.63
December 47.22 826.24
     
Annual Sum or Average 1781.23 3038.11
Minimum of Months 47.22 0.00
Maximum of Months 283.10 867.69



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 54.03 896.54
February 62.91 622.69
March 82.05 269.21
April 132.70 56.57
May 162.93 15.94
June 227.83 0.76
July 267.57 0.00
August 260.13 0.00
September 210.60 0.00
October 150.82 110.22
November 74.21 333.90
December 50.83 870.74
     
Annual Sum or Average 1736.60 3176.58
Minimum of Months 50.83 0.00
Maximum of Months 267.57 896.54



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 15.31 797.01
February 19.60 543.24
March 40.35 194.21
April 79.94 35.64
May 115.26 6.27
June 168.97 0.00
July 199.81 0.00
August 184.51 0.00
September 135.43 0.00
October 74.80 83.78
November 25.51 312.64
December 10.43 844.54
     
Annual Sum or Average 1069.93 2817.32
Minimum of Months 10.43 0.00
Maximum of Months 199.81 844.54



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 50.26 452.63
February 53.65 312.46
March 67.09 127.66
April 99.06 22.63
May 121.31 5.90
June 166.89 0.00
July 203.33 0.00
August 199.11 0.00
September 168.56 0.00
October 126.60 52.24
November 68.92 129.72
December 48.34 412.64
     
Annual Sum or Average 1373.12 1515.89
Minimum of Months 48.34 0.00
Maximum of Months 203.33 452.63



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2021-05-12 10:31:15

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 17.28 1181.41
February 26.72 808.72
March 53.02 360.64
April 112.43 69.20
May 156.56 15.54
June 229.71 0.53
July 264.03 0.00
August 245.66 0.00
September 178.09 0.00
October 99.35 157.73
November 28.40 510.53
December 15.26 1195.17
     
Annual Sum or Average 1426.50 4299.47