Program Version:EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:34
Tabular Output Report in Format: HTML
Building: US+MF+CZ5A+hp+crawlspace+IECC_2021
Environment: ANNUAL ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2021-05-12 10:34:39
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 679517.12 | 17.42 | 31.44 |
Net Site Energy | 679517.12 | 17.42 | 31.44 |
Total Source Energy | 2152030.71 | 55.17 | 99.59 |
Net Source Energy | 2152030.71 | 55.17 | 99.59 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.22 |
Net Conditioned Building Area | 21609.96 |
Unconditioned Building Area | 17395.26 |
Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 202860.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 26048.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 38708.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18809.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 299798.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 33784.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 59507.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330767.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 679517.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330767.30 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | General | 202860.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 26048.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 38708.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 18809.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 9418.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 4809.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 25131.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation | 8652.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330767.30 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 4468.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 55038.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 14.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.31 |
Other | 13.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 31.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.31 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 8.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 |
Other | 7.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 17.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 679517.118 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 679517.118 | 100.00 |
Total On-Site and Utility Electric Sources | 679517.118 | 100.00 |
Total Electricity End Uses | 679517.118 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 330767.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 330767.30 | 100.00 |
Total Water End Uses | 330767.30 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 200.67 |
Time Setpoint Not Met During Occupied Cooling | 0.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1025.67 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |COILLOADS
| MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR |WATER HEATER: LOADS
| WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR |HEATING AND COOLING LOADS
| CRAWLSPACE | BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:34 |
RunPeriod | ANNUAL |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [ft] | 705.42 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 17103.09 | 6415.36 | 2136.19 | 6415.36 | 2136.19 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 12.43 | 8.29 | 24.89 | 8.29 | 24.89 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Above Ground Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Above Ground Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
CRAWLSPACE | 7794.39 | No | Yes | 19513.17 | 1.00 | 185.02 | 740.10 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.16 | No | Yes | 30553.25 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
ATTIC | 7802.71 | No | Yes | 52795.56 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
Total | 39005.22 | 286601.37 | 16363.00 | 740.10 | 2126.74 | 2126.74 | 0.3230 | 1083.48 | 1.6118 | |||
Conditioned Total | 21609.96 | 183739.38 | 15296.60 | 0.00 | 2126.74 | 2126.74 | 0.5831 | 600.28 | 2.9092 | |||
Unconditioned Total | 17395.26 | 102861.98 | 1066.39 | 740.10 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 06-FEB-19:00 | - | - | - | - | - | - | - | - | - | - | - | 01-JAN-08:09 |
Heating | 161.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 4.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 47.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 28.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 262.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | General | 161.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 12.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 4.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 2.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 5.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 5.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 26.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation | 0.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Gasoline [kBtu] | Source Diesel [kBtu] | Source Coal [kBtu] | Source Fuel Oil No 1 [kBtu] | Source Fuel Oil No 2 [kBtu] | Source Propane [kBtu] | Source Other Fuel 1 [kBtu] | Source Other Fuel 2 [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 642459.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 82495.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 122590.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 59568.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 949462.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 106994.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 188459.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2152030.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 29.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 43.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 8.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 99.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 16.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 24.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 55.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
ZoneHVAC:EnergyRecoveryVentilatorUser-Specified Supply Air Flow Rate [ft3/min] | User-Specified Exhaust Air Flow Rate [ft3/min] | |
ERV_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT3_BACKROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT3_FRONTROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT1_FRONTROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT2_BACKROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT2_FRONTROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT1_BACKROW_TOPFLOOR | 44.99 | 44.99 |
User-Specified Maximum Flow Rate [ft3/min] | Design Size Maximum Flow Rate [ft3/min] | |
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR | 44.99 | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 389.29 | |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 172.95 | |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 299.83 | |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 373.12 | |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 168.37 | |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 283.52 | |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 384.10 | |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 174.59 | |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 304.32 | |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 368.01 | |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 168.26 | |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 286.38 | |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 395.30 | |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 189.63 | |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 305.26 | |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 388.64 | |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 191.16 | |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 288.21 | |
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR | 160.01 |
User-Specified Nominal Supply Air Flow Rate [ft3/min] | |
OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR | 44.99 |
Design Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 389.29 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 172.95 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 299.83 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 373.12 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 168.37 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 283.52 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 384.10 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 174.59 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 304.32 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 368.01 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 168.26 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 286.38 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 288.21 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 305.26 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 395.30 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 191.16 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 189.63 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 388.64 |
Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | Sum of Air Terminal Maximum Flow Rates [ft3/min] | Adjusted Heating Design Air Flow Rate [ft3/min] | Adjusted Cooling Design Air Flow Rate [ft3/min] | Adjusted Main Design Air Flow Rate [ft3/min] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 389.29 | 389.29 | 389.29 | 389.29 | 389.29 | 389.29 | 1.00 | 1.00 | 389.29 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 172.95 | 172.95 | 172.95 | 172.95 | 172.95 | 172.95 | 1.00 | 1.00 | 172.95 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 299.83 | 299.83 | 299.83 | 299.83 | 299.83 | 299.83 | 1.00 | 1.00 | 299.83 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 373.12 | 373.12 | 373.12 | 373.12 | 373.12 | 373.12 | 1.00 | 1.00 | 373.12 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 168.37 | 168.37 | 168.37 | 168.37 | 168.37 | 168.37 | 1.00 | 1.00 | 168.37 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 283.52 | 283.52 | 283.52 | 283.52 | 283.52 | 283.52 | 1.00 | 1.00 | 283.52 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 384.10 | 384.10 | 384.10 | 384.10 | 384.10 | 384.10 | 1.00 | 1.00 | 384.10 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 174.59 | 174.59 | 174.59 | 174.59 | 174.59 | 174.59 | 1.00 | 1.00 | 174.59 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 304.32 | 304.32 | 304.32 | 304.32 | 304.32 | 304.32 | 1.00 | 1.00 | 304.32 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 368.01 | 368.01 | 368.01 | 368.01 | 368.01 | 368.01 | 1.00 | 1.00 | 368.01 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 168.26 | 168.26 | 168.26 | 168.26 | 168.26 | 168.26 | 1.00 | 1.00 | 168.26 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 286.38 | 286.38 | 286.38 | 286.38 | 286.38 | 286.38 | 1.00 | 1.00 | 286.38 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 395.30 | 395.30 | 395.30 | 395.30 | 395.30 | 395.30 | 1.00 | 1.00 | 395.30 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 189.63 | 189.63 | 189.63 | 189.63 | 189.63 | 189.63 | 1.00 | 1.00 | 189.63 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 305.26 | 305.26 | 305.26 | 305.26 | 305.26 | 305.26 | 1.00 | 1.00 | 305.26 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 388.64 | 388.64 | 388.64 | 388.64 | 388.64 | 388.64 | 1.00 | 1.00 | 388.64 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 191.16 | 191.16 | 191.16 | 191.16 | 191.16 | 191.16 | 1.00 | 1.00 | 191.16 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 288.21 | 288.21 | 288.21 | 288.21 | 288.21 | 288.21 | 1.00 | 1.00 | 288.21 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 389.29 | 0.979595 | 0.800587 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 172.95 | 0.501465 | 0.746700 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 299.83 | 0.768673 | 0.794593 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 373.12 | 0.944489 | 0.800664 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 168.37 | 0.491634 | 0.744727 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 283.52 | 0.726320 | 0.794829 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 384.10 | 0.952274 | 0.800446 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 174.59 | 0.493479 | 0.755966 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 304.32 | 0.765203 | 0.800832 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 368.01 | 0.915850 | 0.800202 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 168.26 | 0.478273 | 0.754346 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 286.38 | 0.721468 | 0.800212 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 395.30 | 0.991430 | 0.800659 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 189.63 | 0.538625 | 0.754561 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 305.26 | 0.782376 | 0.794679 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 388.64 | 0.975622 | 0.800366 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 191.16 | 0.540030 | 0.756116 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 288.21 | 0.740004 | 0.794105 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Heating Capacity [Btu/h] | Nominal Cooling Capacity [ton] | Supplemental Heating Coil Nominal Capacity [Btu/h] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | 389.29 | 389.29 | 389.29 | 11755.14 | 0.979595 | 11148.96 | 1.00 |
HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | 172.95 | 172.95 | 172.95 | 6017.58 | 0.501465 | 8920.85 | 1.00 |
HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | 299.83 | 299.83 | 299.83 | 9224.07 | 0.768673 | 11136.30 | 1.00 |
HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | 373.12 | 373.12 | 373.12 | 11333.87 | 0.944489 | 11151.10 | 1.00 |
HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | 168.37 | 168.37 | 168.37 | 5899.61 | 0.491634 | 8920.85 | 1.00 |
HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | 283.52 | 283.52 | 283.52 | 8715.85 | 0.726320 | 11134.17 | 1.00 |
HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | 384.10 | 384.10 | 384.10 | 11427.29 | 0.952274 | 8668.66 | 1.00 |
HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | 174.59 | 174.59 | 174.59 | 5921.75 | 0.493479 | 6457.40 | 1.00 |
HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | 304.32 | 304.32 | 304.32 | 9182.43 | 0.765203 | 8651.19 | 1.00 |
HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | 368.01 | 368.01 | 368.01 | 10990.20 | 0.915850 | 8670.52 | 1.00 |
HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | 168.26 | 168.26 | 168.26 | 5739.28 | 0.478273 | 6457.40 | 1.00 |
HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | 286.38 | 286.38 | 286.38 | 8657.61 | 0.721468 | 8649.35 | 1.00 |
HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | 395.30 | 395.30 | 395.30 | 11897.17 | 0.991430 | 11046.61 | 1.00 |
HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | 189.63 | 189.63 | 189.63 | 6463.50 | 0.538625 | 8824.15 | 1.00 |
HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | 305.26 | 305.26 | 305.26 | 9388.52 | 0.782376 | 11026.37 | 1.00 |
HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | 388.64 | 388.64 | 388.64 | 11707.46 | 0.975622 | 11047.91 | 1.00 |
HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | 191.16 | 191.16 | 191.16 | 6480.36 | 0.540030 | 8824.15 | 1.00 |
HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | 288.21 | 288.21 | 288.21 | 8880.05 | 0.740004 | 11025.07 | 1.00 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Heating Capacity [Btu/h] | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 389.29 | 11755.14 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 172.95 | 6017.58 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 299.83 | 9224.07 |
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 373.12 | 11333.87 |
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 168.37 | 5899.61 |
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 283.52 | 8715.85 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 384.10 | 11427.29 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 174.59 | 5921.75 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 304.32 | 9182.43 |
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 368.01 | 10990.20 |
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 168.26 | 5739.28 |
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 286.38 | 8657.61 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 395.30 | 11897.17 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 189.63 | 6463.50 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 305.26 | 9388.52 |
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 388.64 | 11707.46 |
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 191.16 | 6480.36 |
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 288.21 | 8880.05 |
Design Size Nominal Capacity [Btu/h] | |
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 11148.96 |
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 8920.85 |
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 11136.30 |
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 11151.10 |
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 8920.85 |
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 11134.17 |
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 8668.66 |
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 6457.40 |
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 8651.19 |
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 8670.52 |
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 6457.40 |
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 8649.35 |
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 11046.61 |
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 8824.15 |
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 11026.37 |
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 11047.91 |
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 8824.15 |
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 11025.07 |
Evaporator air flow rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 160.01 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 2.09 |
Design Flow Rate [ft3/min] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
BGWALL_UPPER_LDF | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
BGWALL_UPPER_SDR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
BGWALL_UPPER_LDB | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
BGWALL_UPPER_SDL | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
VersionVersion ID | |
1 | 9.5 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | No | Yes | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.200 | 0.200 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 26.83 | 30.85 | 38.68 | 46.09 | 60.12 | 67.50 | 69.53 | 65.79 | 57.13 | 46.36 | 35.74 | 28.74 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {ft} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Sensor Height Above Ground {ft} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 32.810 | 0.140 | 885.870 | 4.921 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {ft} | Standard Pressure at Elevation {psi} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 705.42 | 14. | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{F} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} | Fixed Default Water Mains Temperature{F} | |
1 | Correlation | NA | 48.15 | 47.16 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | US+MF+CZ5A+hp+crawlspace+IECC_2021 | 0.000 | Suburbs | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Gradient Coefficient {F/ft} | |
1 | 0.220 | 1213.970 | 0.003566 |
Material Name | ThermalResistance {m2-K/w} | Roughness | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | Absorptance:Thermal | Absorptance:Solar | Absorptance:Visible | |
1 | SHEATHING_CONSOL_LAYER | 0.8807 | Rough | 0.1021 | 3.533E-002 | 1.255 | 0.350 | 0.9000 | 0.7000 | 0.7000 |
2 | CEIL_CONSOL_LAYER | 9.1788 | Rough | 1.8587 | 6.172E-002 | 2.618 | 0.185 | 0.9000 | 0.7000 | 0.7000 |
3 | FLOOR_CONSOL_LAYER | 4.5576 | Rough | 0.7710 | 5.155E-002 | 3.438 | 0.219 | 0.9000 | 0.7000 | 0.7000 |
4 | BSMTWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
5 | CRAWLWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
6 | WALL_CONSOL_LAYER | 2.4438 | Rough | 0.4584 | 5.717E-002 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
7 | VERY HIGH REFLECTIVITY SURFACE | 2.1097E-006 | Smooth | 0.0016 | 237.000 | 168.680 | 0.216 | 0.9000 | 5.0000E-002 | 5.0000E-002 |
8 | GYPSUMBOARD-5/16IN | 5.0054E-002 | Rough | 0.0260 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
9 | COPPERPIPE | 4.7506E-005 | MediumRough | 0.0625 | 401.000 | 140.026 | 0.200 | 0.9000 | 0.6500 | 0.6500 |
10 | F08 METAL SURFACE | 1.7668E-005 | Smooth | 0.0026 | 45.280 | 488.437 | 0.119 | 0.9000 | 0.7000 | 0.7000 |
11 | CONCRETE_4IN | 7.7356E-002 | Rough | 0.3330 | 1.312 | 140.014 | 0.111 | 0.9000 | 0.7000 | 0.7000 |
12 | ASPHALT_SHINGLE | 7.7448E-002 | MediumRough | 0.0208 | 8.186E-002 | 70.000 | 0.300 | 0.9000 | 0.7500 | 0.7000 |
13 | WOOD_SHINGLE | 0.1115 | MediumSmooth | 0.0417 | 0.114 | 26.600 | 0.390 | 0.9000 | 0.7000 | 0.7000 |
14 | SLATE_SHINGLE | 8.8061E-003 | MediumSmooth | 0.0417 | 1.442 | 100.000 | 0.300 | 0.9000 | 0.7000 | 0.7000 |
15 | CEMENT_STUCCO | 2.6422E-002 | MediumSmooth | 0.0625 | 0.721 | 116.464 | 0.210 | 0.9000 | 0.7000 | 0.7000 |
16 | SYN_STUCCO | 3.5237E-002 | MediumSmooth | 0.0100 | 8.650E-002 | 24.971 | 0.210 | 0.9000 | 0.7000 | 0.7000 |
17 | DRYWALL_1/2IN | 7.9331E-002 | MediumSmooth | 0.0417 | 0.160 | 50.000 | 0.260 | 0.9000 | 0.7000 | 0.7000 |
18 | OSB_5/8IN | 0.1365 | MediumSmooth | 0.0521 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
19 | OSB_7/16IN | 9.5550E-002 | MediumSmooth | 0.0365 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
20 | BLOWN_R30 | 5.1614 | MediumRough | 0.6975 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
21 | BLOWN_R30_TOP | 2.8489 | MediumRough | 0.3849 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
22 | PLYWOOD_3/4IN | 0.1650 | Rough | 0.0625 | 0.115 | 34.003 | 0.161 | 0.9000 | 0.7000 | 0.7000 |
23 | BATT_R19 | 7.3089 | MediumRough | 0.0833 | 3.475E-003 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
24 | LUMBER_2X4 | 0.7709 | Rough | 0.2920 | 0.115 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
25 | CARPET_N_PAD | 0.4224 | MediumSmooth | 0.0833 | 6.013E-002 | 2.000 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
26 | BATT_R13 | 2.2936 | MediumRough | 0.2917 | 3.876E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
27 | OSB_1/2IN | 0.1092 | MediumSmooth | 0.0417 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
28 | SOIL_12IN | 0.1761 | Rough | 1.0000 | 1.731 | 115.011 | 0.056 | 0.9000 | 0.7000 | 0.7000 |
29 | DOOR_CONST | 0.5870 | Smooth | 0.1387 | 7.201E-002 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
30 | GYP_BOARD_1/2IN | 8.0130E-002 | Rough | 0.0417 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
31 | STD WOOD 6INCH | 1.2500 | MediumSmooth | 0.4921 | 0.120 | 33.711 | 0.289 | 0.9000 | 0.7000 | 0.7000 |
32 | PIPE INSULATION | 0.3830 | VeryRough | 0.0417 | 3.317E-002 | 5.681 | 0.200 | 0.9000 | 0.5000 | 0.5000 |
33 | MANF_WALL_AIRGAP | 0.1200 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
34 | BLDG_PAPER_FELT | 1.0567E-002 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
35 | R_HIGH | 177.0000 | MediumRough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
36 | CLEAR ACRYLIC PLASTIC | 3.3333E-003 | VerySmooth | 0.0098 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
37 | DIFFUSING ACRYLIC PLASTIC | 2.4444E-003 | VerySmooth | 0.0072 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
38 | INT_BLIND | 0.0000 | Rough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.0000 | 0.0000 | 0.0000 |
39 | GLASS | 0.4127 | VerySmooth | 0.1373 | 0.101 | 0.000 | 0.000 | 0.8400 | 0.0000 | 0.0000 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | LowerLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Name | Combined convective/radiative film coefficient {Btu/h-ft2-F} | User selected Constant Temperature {F} | Coefficient modifying the constant temperature term | Coefficient modifying the external dry bulb temperature term | Coefficient modifying the ground temperature term | Coefficient modifying the wind speed term {s/m} | Coefficient modifying the zone air temperature term | Constant Temperature Schedule Name | Sinusoidal Variation | Period of Sinusoidal Variation | Previous Other Side Temperature Coefficient | Minimum Other Side Temperature {F} | Maximum Other Side Temperature {F} | |
1 | SURFPROPOTHSDCOEFSLABAVERAGE | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCSLABAVERAGESURFACETEMP | NO | 24.000 | 0.000 | N/A | N/A |
2 | SURFPROPOTHSDCOEFSLABPERIMETER | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCSLABPERIMETERTEMP | NO | 24.000 | 0.000 | N/A | N/A |
3 | SURFPROPOTHSDCOEFSLABCORE | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCSLABCORETEMP | NO | 24.000 | 0.000 | N/A | N/A |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{F} |
Surface Convection Coefficient Lower Limit {Btu/h-ft2-F} |
Surface Convection Coefficient Upper Limit {Btu/h-ft2-F} |
|
1 | CTF - ConductionTransferFunction | 392. | 0.02 | 176.1 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 60 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 21 | 186 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {ft} | Origin Y-Coordinate {ft} | Origin Z-Coordinate {ft} | Centroid X-Coordinate {ft} | Centroid Y-Coordinate {ft} | Centroid Z-Coordinate {ft} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {ft} | Maximum X {ft} | Minimum Y {ft} | Maximum Y {ft} | Minimum Z {ft} | Maximum Z {ft} | Ceiling Height {ft} | Volume {ft3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {ft2} | Exterior Gross Wall Area {ft2} | Exterior Net Wall Area {ft2} | Exterior Window Area {ft2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CRAWLSPACE | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.51 | -0.8 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | -2.0 | 0.49 | 2.49 | 19513.15 | TARP | DOE-2 | 7794.37 | 185.05 | 185.05 | 0.00 | 15 | 0 | 0 | Yes |
2 | BREEZEWAY | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.55 | 13.26 | 1 | 1 | 1 | 0.00 | 119.89 | 30.05 | 35.04 | 0.49 | 25.99 | 17.00 | 30553.07 | TARP | DOE-2 | 1798.18 | 0.00 | 0.00 | 0.00 | 4 | 0 | 0 | Yes |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
15 | ATTIC | 0.0 | -134.9 | 51.61 | 0.00 | 59.94 | 32.55 | 29.56 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | 25.99 | 39.54 | 6.76 | 52795.39 | TARP | DOE-2 | 7802.66 | 881.33 | 881.33 | 0.00 | 11 | 0 | 0 | Yes |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
Zone Name | Floor Area {ft2} | # Occupants | Area per Occupant {ft2/person} | Occupant per Area {person/ft2} | Interior Lighting {Btu/h-ft2} | Electric Load {Btu/h-ft2} | Gas Load {Btu/h-ft2} | Other Load {Btu/h-ft2} | Hot Water Eq {Btu/h-ft2} | Steam Equipment {Btu/h-ft2} | Sum Loads per Area {Btu/h-ft2} | Outdoor Controlled Baseboard Heat | |
1 | CRAWLSPACE | 7794.37 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
2 | BREEZEWAY | 1798.18 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
15 | ATTIC | 7802.66 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Number of People {} | People/Floor Area {person/ft2} | Floor Area per person {ft2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
2 | PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
3 | PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
4 | PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
5 | PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
6 | PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
7 | PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
8 | PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
9 | PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
10 | PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
11 | PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
12 | PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
13 | PEOPLE_UNIT1_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
14 | PEOPLE_UNIT2_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
15 | PEOPLE_UNIT3_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
16 | PEOPLE_UNIT1_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
17 | PEOPLE_UNIT2_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
18 | PEOPLE_UNIT3_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Lighting Level {Btu/h} | Lights/Floor Area {Btu/h-ft2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {Btu/h} | Nominal Maximum Lighting Level {Btu/h} | |
1 | LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
2 | LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
3 | LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
4 | LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
5 | LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
6 | LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
7 | LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
8 | LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
9 | LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
10 | LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
11 | LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
12 | LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
13 | LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
14 | LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
15 | LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
16 | LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
17 | LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
18 | LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
19 | LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
20 | LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
21 | LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
22 | LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
23 | LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
24 | LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
25 | LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
26 | LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
27 | LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
28 | LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
29 | LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
30 | LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
31 | LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
32 | LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
33 | LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
34 | LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
35 | LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
36 | LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Equipment Level {Btu/h} | Equipment/Floor Area {Btu/h-ft2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {Btu/h} | Nominal Maximum Equipment Level {Btu/h} | |
1 | DISHWASHER1_FRONTROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
2 | REFRIGERATOR1_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
3 | CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
4 | ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
5 | ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
6 | TELEVISION1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
7 | ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
8 | IECC_ADJ1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
9 | DISHWASHER2_FRONTROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
10 | REFRIGERATOR2_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
11 | CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
12 | ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
13 | ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
14 | TELEVISION2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
15 | ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
16 | IECC_ADJ2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
17 | DISHWASHER3_FRONTROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
18 | REFRIGERATOR3_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
19 | CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
20 | ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
21 | ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
22 | TELEVISION3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
23 | ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
24 | IECC_ADJ3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
25 | DISHWASHER1_BACKROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
26 | REFRIGERATOR1_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
27 | CLOTHESWASHER1_BACKROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
28 | ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
29 | ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
30 | TELEVISION1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
31 | ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
32 | IECC_ADJ1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
33 | DISHWASHER2_BACKROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
34 | REFRIGERATOR2_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
35 | CLOTHESWASHER2_BACKROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
36 | ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
37 | ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
38 | TELEVISION2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
39 | ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
40 | IECC_ADJ2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
41 | DISHWASHER3_BACKROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
42 | REFRIGERATOR3_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
43 | CLOTHESWASHER3_BACKROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
44 | ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
45 | ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
46 | TELEVISION3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
47 | ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
48 | IECC_ADJ3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
49 | DISHWASHER1_FRONTROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
50 | REFRIGERATOR1_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
51 | CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
52 | ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
53 | ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
54 | TELEVISION1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
55 | ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
56 | IECC_ADJ1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
57 | DISHWASHER2_FRONTROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
58 | REFRIGERATOR2_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
59 | CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
60 | ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
61 | ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
62 | TELEVISION2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
63 | ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
64 | IECC_ADJ2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
65 | DISHWASHER3_FRONTROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
66 | REFRIGERATOR3_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
67 | CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
68 | ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
69 | ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
70 | TELEVISION3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
71 | ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
72 | IECC_ADJ3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
73 | DISHWASHER1_BACKROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
74 | REFRIGERATOR1_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
75 | CLOTHESWASHER1_BACKROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
76 | ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
77 | ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
78 | TELEVISION1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
79 | ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
80 | IECC_ADJ1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
81 | DISHWASHER2_BACKROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
82 | REFRIGERATOR2_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
83 | CLOTHESWASHER2_BACKROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
84 | ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
85 | ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
86 | TELEVISION2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
87 | ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
88 | IECC_ADJ2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
89 | DISHWASHER3_BACKROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
90 | REFRIGERATOR3_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
91 | CLOTHESWASHER3_BACKROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
92 | ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
93 | ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
94 | TELEVISION3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
95 | ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
96 | IECC_ADJ3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
97 | DISHWASHER1_FRONTROW_TOPFLOOR | DISHWASHER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
98 | REFRIGERATOR1_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
99 | CLOTHESWASHER1_FRONTROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
100 | ELECTRIC_DRYER1_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
101 | ELECTRIC_RANGE1_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
102 | TELEVISION1_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
103 | ELECTRIC_MELS1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
104 | IECC_ADJ1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
105 | DISHWASHER2_FRONTROW_TOPFLOOR | DISHWASHER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
106 | REFRIGERATOR2_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
107 | CLOTHESWASHER2_FRONTROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
108 | ELECTRIC_DRYER2_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
109 | ELECTRIC_RANGE2_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
110 | TELEVISION2_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
111 | ELECTRIC_MELS2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
112 | IECC_ADJ2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
113 | DISHWASHER3_FRONTROW_TOPFLOOR | DISHWASHER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
114 | REFRIGERATOR3_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
115 | CLOTHESWASHER3_FRONTROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
116 | ELECTRIC_DRYER3_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
117 | ELECTRIC_RANGE3_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
118 | TELEVISION3_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
119 | ELECTRIC_MELS3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
120 | IECC_ADJ3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
121 | DISHWASHER1_BACKROW_TOPFLOOR | DISHWASHER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
122 | REFRIGERATOR1_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
123 | CLOTHESWASHER1_BACKROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
124 | ELECTRIC_DRYER1_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
125 | ELECTRIC_RANGE1_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
126 | TELEVISION1_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
127 | ELECTRIC_MELS1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
128 | IECC_ADJ1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
129 | DISHWASHER2_BACKROW_TOPFLOOR | DISHWASHER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
130 | REFRIGERATOR2_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
131 | CLOTHESWASHER2_BACKROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
132 | ELECTRIC_DRYER2_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
133 | ELECTRIC_RANGE2_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
134 | TELEVISION2_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
135 | ELECTRIC_MELS2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
136 | IECC_ADJ2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
137 | DISHWASHER3_BACKROW_TOPFLOOR | DISHWASHER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
138 | REFRIGERATOR3_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
139 | CLOTHESWASHER3_BACKROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
140 | ELECTRIC_DRYER3_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
141 | ELECTRIC_RANGE3_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
142 | TELEVISION3_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
143 | ELECTRIC_MELS3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
144 | IECC_ADJ3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
Construction Name | Index | #Layers | #CTFs | Time Step {Hours} | ThermalConductance {Btu/h-ft2-F} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | EXTERIOR WALL | 1 | 5 | 10 | 0.167 | 0.0498 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
2 | CEILING-FLOOR-LAYER | 3 | 1 | 5 | 0.167 | 0.228 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
3 | EXTERIOR FLOOR | 4 | 3 | 9 | 0.167 | 0.0342 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
4 | INTERIOR FLOOR | 5 | 2 | 4 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
5 | INTERIOR CEILING | 6 | 2 | 13 | 0.167 | 0.0190 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
6 | ATTIC FLOOR | 7 | 2 | 13 | 0.167 | 0.0190 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | INTERIORWALL | 9 | 3 | 5 | 0.167 | 0.597 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
8 | EXTERIOR ROOF | 11 | 2 | 4 | 0.167 | 0.943 | 0.900 | 0.900 | 0.750 | 0.700 | MediumRough |
9 | EXTERIOR DOOR | 14 | 1 | 5 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | GABLE_END | 16 | 5 | 6 | 0.167 | 0.428 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
11 | CRAWL WALL | 24 | 1 | 5 | 0.167 | 2.28 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
12 | iz-EXTERIOR FLOOR | 25 | 3 | 9 | 0.167 | 0.0342 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | ThermalResistance {m2-K/w} | |
1 | SYN_STUCCO | 0.0098 | 0.086 | 24.971 | 0.210 | 0.3524E-01 |
2 | SHEATHING_CONSOL_LAYER | 0.1020 | 0.035 | 1.255 | 0.350 | 0.8807 |
3 | OSB_7/16IN | 0.0364 | 0.116 | 34.000 | 0.290 | 0.9555E-01 |
4 | WALL_CONSOL_LAYER | 0.4584 | 0.057 | 7.541 | 0.248 | 2.444 |
5 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
6 | LUMBER_2X4 | 0.2920 | 0.115 | 32.003 | 0.183 | 0.7709 |
7 | FLOOR_CONSOL_LAYER | 0.7707 | 0.052 | 3.438 | 0.219 | 4.558 |
8 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
9 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
10 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
11 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
12 | CEIL_CONSOL_LAYER | 1.8587 | 0.062 | 2.618 | 0.185 | 9.179 |
13 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
14 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
15 | CEIL_CONSOL_LAYER | 1.8587 | 0.062 | 2.618 | 0.185 | 9.179 |
16 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
17 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
18 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
19 | ASPHALT_SHINGLE | 0.0207 | 0.082 | 70.000 | 0.300 | 0.7745E-01 |
20 | OSB_1/2IN | 0.0417 | 0.116 | 34.000 | 0.290 | 0.1092 |
21 | DOOR_CONST | 0.1388 | 0.072 | 32.003 | 0.183 | 0.5870 |
22 | CEMENT_STUCCO | 0.0627 | 0.721 | 116.464 | 0.210 | 0.2642E-01 |
23 | BLDG_PAPER_FELT | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1057E-01 |
24 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
25 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
26 | CONCRETE_4IN | 0.3330 | 1.312 | 140.014 | 0.111 | 0.7736E-01 |
27 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
28 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
29 | FLOOR_CONSOL_LAYER | 0.7707 | 0.052 | 3.438 | 0.219 | 4.558 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 10 | 0.51360630E-08 | -0.22035233E-13 | 0.91774209E-08 | -0.50676220E-13 |
2 | 9 | -0.14060012E-04 | 0.39159197E-12 | -0.22958088E-04 | 0.29728831E-08 |
3 | 8 | 0.28980689E-02 | 0.65531654E-09 | 0.46215968E-02 | -0.71708779E-05 |
4 | 7 | -0.65978682E-01 | 0.13350779E-06 | -0.16306378 | 0.13238707E-02 |
5 | 6 | 0.64596177 | 0.50193482E-05 | 2.1320981 | -0.28125917E-01 |
6 | 5 | -3.4215999 | 0.48298777E-04 | -13.652056 | 0.25148823 |
7 | 4 | 10.645660 | 0.13839053E-03 | 47.881148 | -1.1749737 |
8 | 3 | -19.924231 | 0.11919231E-03 | -96.040791 | 3.0621859 |
9 | 2 | 21.976583 | 0.26462555E-04 | 109.48934 | -4.4404618 |
10 | 1 | -13.118296 | 0.91387708E-06 | -65.855375 | 3.3273744 |
11 | 0 | 3.2593552 | 0.33613880E-09 | 16.204438 | |
12 | 5 | -0.10726087E-01 | 0.44268190E-05 | -0.10726087E-01 | 0.97389233E-03 |
13 | 4 | 0.31857203 | 0.80150166E-03 | 0.31857203 | -0.30727185E-01 |
14 | 3 | -2.8372473 | 0.12516450E-01 | -2.8372473 | 0.30041224 |
15 | 2 | 9.6667056 | 0.33176537E-01 | 9.6667056 | -1.1584571 |
16 | 1 | -13.322214 | 0.15207483E-01 | -13.322214 | 1.8397512 |
17 | 0 | 6.2472388 | 0.62260140E-03 | 6.2472388 | |
18 | 9 | -0.61797381E-16 | 0.10275554E-15 | -0.94176193E-10 | 0.70550100E-16 |
19 | 8 | 0.55018702E-09 | 0.40996745E-13 | 0.10446581E-03 | -0.35964092E-09 |
20 | 7 | -0.45325743E-03 | 0.10183730E-08 | -0.10651944E-01 | 0.29628111E-03 |
21 | 6 | 0.35000963E-01 | 0.28248981E-06 | 0.18262466 | -0.23007581E-01 |
22 | 5 | -0.40204458 | 0.87190144E-05 | -1.3453660 | 0.27251248 |
23 | 4 | 1.9371679 | 0.56641591E-04 | 5.2219591 | -1.3641479 |
24 | 3 | -4.7809977 | 0.95620201E-04 | -11.428910 | 3.5178846 |
25 | 2 | 6.3416706 | 0.40914426E-04 | 14.116582 | -4.8962826 |
26 | 1 | -4.2976303 | 0.32019284E-05 | -9.1505965 | 3.4916880 |
27 | 0 | 1.1674918 | 0.10995666E-07 | 2.4144591 | |
28 | 4 | 0.50405178E-13 | 0.16668152E-13 | 0.29402090E-13 | -0.58636069E-16 |
29 | 3 | -0.78967347E-05 | 0.18486376E-05 | -0.51544008E-05 | 0.20741056E-12 |
30 | 2 | 0.37655193 | 0.34407043E-01 | 0.80677627E-01 | -0.16328896E-04 |
31 | 1 | -8.0349315 | 0.81344511 | -1.1624309 | 0.21506451 |
32 | 0 | 8.9946927 | 0.48845120 | 2.4180636 | |
33 | 13 | -0.95016766E-17 | -0.11776553E-17 | -0.33255767E-09 | 0.99855310E-17 |
34 | 12 | 0.61338794E-09 | -0.58488406E-15 | 0.16056222E-03 | -0.43490528E-09 |
35 | 11 | -0.75116140E-04 | -0.12733754E-14 | -0.83172474E-02 | 0.53259175E-04 |
36 | 10 | 0.23489104E-02 | 0.19285539E-11 | 0.16199673 | -0.16913697E-02 |
37 | 9 | -0.32325933E-01 | 0.31831827E-09 | -1.7014869 | 0.23684835E-01 |
38 | 8 | 0.25799047 | 0.11552332E-07 | 11.081256 | -0.19274894 |
39 | 7 | -1.3247958 | 0.13607244E-06 | -47.903612 | 1.0115855 |
40 | 6 | 4.5908388 | 0.61202310E-06 | 142.28685 | -3.5913725 |
41 | 5 | -10.947340 | 0.11168173E-05 | -294.46769 | 8.7955522 |
42 | 4 | 17.960252 | 0.81578039E-06 | 423.45640 | -14.856181 |
43 | 3 | -19.872933 | 0.21758675E-06 | -414.30161 | 16.962607 |
44 | 2 | 14.135270 | 0.16726228E-07 | 262.68178 | -12.475847 |
45 | 1 | -5.8235685 | 0.25078833E-09 | -97.209670 | 5.3243306 |
46 | 0 | 1.0543411 | -0.72051379E-11 | 15.923944 | |
47 | 13 | -0.33255767E-09 | -0.11776553E-17 | -0.95016766E-17 | 0.99855310E-17 |
48 | 12 | 0.16056222E-03 | -0.58488406E-15 | 0.61338794E-09 | -0.43490528E-09 |
49 | 11 | -0.83172474E-02 | -0.12733754E-14 | -0.75116140E-04 | 0.53259175E-04 |
50 | 10 | 0.16199673 | 0.19285539E-11 | 0.23489104E-02 | -0.16913697E-02 |
51 | 9 | -1.7014869 | 0.31831827E-09 | -0.32325933E-01 | 0.23684835E-01 |
52 | 8 | 11.081256 | 0.11552332E-07 | 0.25799047 | -0.19274894 |
53 | 7 | -47.903612 | 0.13607244E-06 | -1.3247958 | 1.0115855 |
54 | 6 | 142.28685 | 0.61202310E-06 | 4.5908388 | -3.5913725 |
55 | 5 | -294.46769 | 0.11168173E-05 | -10.947340 | 8.7955522 |
56 | 4 | 423.45640 | 0.81578039E-06 | 17.960252 | -14.856181 |
57 | 3 | -414.30161 | 0.21758675E-06 | -19.872933 | 16.962607 |
58 | 2 | 262.68178 | 0.16726228E-07 | 14.135270 | -12.475847 |
59 | 1 | -97.209670 | 0.25078833E-09 | -5.8235685 | 5.3243306 |
60 | 0 | 15.923944 | -0.72051379E-11 | 1.0543411 | |
61 | 5 | -0.27590492E-07 | 0.65241430E-08 | -0.27590492E-07 | 0.17331255E-13 |
62 | 4 | 0.68608714E-03 | 0.11323974E-03 | 0.68608714E-03 | -0.15705033E-07 |
63 | 3 | -0.21538511 | 0.37821720E-01 | -0.21538511 | 0.25667047E-03 |
64 | 2 | 5.0173519 | 0.62258424 | 5.0173519 | -0.50236511E-01 |
65 | 1 | -19.904252 | 0.86481321 | -19.904252 | 0.58144210 |
66 | 0 | 16.688993 | 0.62060609E-01 | 16.688993 | |
67 | 4 | 0.75441920E-10 | 0.23883683E-10 | 0.47514224E-10 | -0.69373194E-20 |
68 | 3 | -0.33730907E-03 | 0.89366797E-04 | -0.22574866E-03 | 0.77828620E-10 |
69 | 2 | 0.58624422 | 0.18542418 | 0.49024360 | -0.17301269E-03 |
70 | 1 | -11.299243 | 2.8799011 | -8.6239668 | 0.15905732 |
71 | 0 | 15.219762 | 1.4410112 | 12.640375 | |
72 | 5 | -0.32935335E-06 | 0.42931990E-07 | -0.32935335E-06 | 0.47097488E-08 |
73 | 4 | 0.68052310E-03 | 0.12823787E-03 | 0.68052310E-03 | -0.14200104E-04 |
74 | 3 | -0.11535993 | 0.17375615E-01 | -0.11535993 | 0.40770076E-02 |
75 | 2 | 2.1922172 | 0.21284128 | 2.1922172 | -0.13171357 |
76 | 1 | -7.8704965 | 0.30308566 | -7.8704965 | 0.79499401 |
77 | 0 | 6.3596665 | 0.33276539E-01 | 6.3596665 | |
78 | 6 | 0.97988530E-11 | 0.43917118E-12 | 0.24496810E-11 | -0.34892153E-15 |
79 | 5 | -0.75005310E-05 | 0.16499726E-06 | -0.28271466E-05 | 0.19166609E-11 |
80 | 4 | 0.32354224E-01 | 0.66949565E-03 | 0.10283773E-01 | -0.11111676E-05 |
81 | 3 | -1.8201547 | 0.67148336E-01 | -0.62076152 | 0.38788549E-02 |
82 | 2 | 21.173821 | 0.53241617 | 7.5279938 | -0.97325542E-01 |
83 | 1 | -64.420211 | 0.46601667 | -21.697519 | 0.64629334 |
84 | 0 | 46.121323 | 0.20873329E-01 | 15.867130 | |
85 | 5 | -0.15664505E-06 | 0.43005807E-07 | -0.15664505E-06 | 0.11899247E-09 |
86 | 4 | 0.10791049E-02 | 0.34140917E-03 | 0.10791049E-02 | -0.15677434E-05 |
87 | 3 | -0.39592122 | 0.90314630E-01 | -0.39592122 | 0.13116776E-02 |
88 | 2 | 11.651569 | 1.6702487 | 11.651569 | -0.78737360E-01 |
89 | 1 | -51.506798 | 3.1050242 | -51.506798 | 0.66829999 |
90 | 0 | 45.538973 | 0.42297268 | 45.538973 | |
91 | 9 | -0.94176193E-10 | 0.10275554E-15 | -0.61797381E-16 | 0.70550100E-16 |
92 | 8 | 0.10446581E-03 | 0.40996745E-13 | 0.55018702E-09 | -0.35964092E-09 |
93 | 7 | -0.10651944E-01 | 0.10183730E-08 | -0.45325743E-03 | 0.29628111E-03 |
94 | 6 | 0.18262466 | 0.28248981E-06 | 0.35000963E-01 | -0.23007581E-01 |
95 | 5 | -1.3453660 | 0.87190144E-05 | -0.40204458 | 0.27251248 |
96 | 4 | 5.2219591 | 0.56641591E-04 | 1.9371679 | -1.3641479 |
97 | 3 | -11.428910 | 0.95620201E-04 | -4.7809977 | 3.5178846 |
98 | 2 | 14.116582 | 0.40914426E-04 | 6.3416706 | -4.8962826 |
99 | 1 | -9.1505965 | 0.32019284E-05 | -4.2976303 | 3.4916880 |
100 | 0 | 2.4144591 | 0.10995666E-07 | 1.1674918 |
Construction Name | Index | #Layers | Roughness | Conductance {Btu/h-ft2-F} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | EXTERIOR WINDOW | 12 | 1 | VerySmooth | 0.300 | 0.335 | 0.248 | 0.883 |
2 | INTERIOR WINDOW | 13 | 1 | VerySmooth | 0.300 | 0.335 | 0.248 | 0.883 |
3 | WINDOW_W_BLINDS | 18 | 2 | VerySmooth | 0.300 | 0.309 | 4.646E-002 | 0.133 |
4 | TDD DOME | 22 | 1 | VerySmooth | 1.071 | 0.929 | 0.920 | 0.920 |
5 | TDD DIFFUSER | 23 | 1 | VerySmooth | 1.077 | 0.906 | 0.900 | 0.900 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {ft} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLASS | SpectralAverage | 0.13728 | 0.24698 | 0.55113 | 0.55113 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10138 | 1.00000 | No | |
2 | GLASS | SpectralAverage | 0.13728 | 0.24698 | 0.55113 | 0.55113 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10138 | 1.00000 | No | |
3 | GLASS | SpectralAverage | 0.13728 | 0.24698 | 0.55113 | 0.55113 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10138 | 1.00000 | No | |
4 | CLEAR ACRYLIC PLASTIC | SpectralAverage | 0.00984 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No | |
5 | DIFFUSING ACRYLIC PLASTIC | SpectralAverage | 0.00722 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No |
Material Name | Slat Width {ft} | Slat Separation {ft} | Slat Thickness {ft} | Slat Angle {deg} | Slat Beam Solar Transmittance | Slat Beam Solar Front Reflectance | Blind To Glass Distance {ft} | |
1 | INT_BLIND | 0.0820 | 0.0615 | 0.0033 | 45.000 | 0.000 | 0.500 | 0.164 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000. | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {ft3} | Maximum Capacity {Btu/h} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | "DX Coil Total Cooling Rate {W | HPWH Only}" | |
1 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 6.9509 | 4465.6 | 0.000 | 0.0000 | 785 | |
2 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 6.9509 | 4465.6 | 0.000 | 0.0000 | 785 | |
3 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 6.9509 | 4465.6 | 0.000 | 0.0000 | 785 | |
4 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 6.9509 | 4465.6 | 0.000 | 0.0000 | 785 | |
5 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 6.9509 | 4465.6 | 0.000 | 0.0000 | 785 | |
6 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 6.9509 | 4465.6 | 0.000 | 0.0000 | 785 | |
7 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 6.9509 | 4465.6 | 0.000 | 0.0000 | 785 | |
8 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 6.9509 | 4465.6 | 0.000 | 0.0000 | 785 | |
9 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 6.9509 | 4465.6 | 0.000 | 0.0000 | 785 | |
10 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 6.9509 | 4465.6 | 0.000 | 0.0000 | 785 | |
11 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 6.9509 | 4465.6 | 0.000 | 0.0000 | 785 | |
12 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 6.9509 | 4465.6 | 0.000 | 0.0000 | 785 | |
13 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 6.9509 | 4465.6 | 0.000 | 0.0000 | 785 | |
14 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 6.9509 | 4465.6 | 0.000 | 0.0000 | 785 | |
15 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 6.9509 | 4465.6 | 0.000 | 0.0000 | 785 | |
16 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 6.9509 | 4465.6 | 0.000 | 0.0000 | 785 | |
17 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 6.9509 | 4465.6 | 0.000 | 0.0000 | 785 | |
18 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 6.9509 | 4465.6 | 0.000 | 0.0000 | 785 |
Node Number | Height {ft} | Volume {ft3} | Maximum Capacity {Btu/h} | Off-Cycle UA {Btu/h-F} | On-Cycle UA {Btu/h-F} | Number Of Inlets | Number Of Outlets | |
1 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
2 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
3 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
4 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
5 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
6 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
7 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
8 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
9 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
10 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
11 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
12 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
13 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
14 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
15 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
16 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
17 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
18 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
2 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
3 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
4 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
5 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
6 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
7 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
8 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
9 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
10 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
11 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
12 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
13 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
14 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
15 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
16 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
17 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
18 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
19 | ATTICVENT | ALWAYS_AVAIL | ATTIC | 7802.66 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
20 | CRAWLVENT | ALWAYS_AVAIL | CRAWLSPACE | 7794.37 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/person Area {ft3/min-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {psi} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{F}/Schedule | Maximum Indoor Temperature{F}/Schedule | Delta Temperature{F}/Schedule | Minimum Outdoor Temperature{F}/Schedule | Maximum Outdoor Temperature{F}/Schedule | Maximum WindSpeed{ft/min} | |
1 | VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
2 | VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
3 | VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
4 | VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
5 | VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
6 | VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
7 | VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
8 | VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
9 | VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
10 | VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
11 | VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
12 | VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
13 | VENTILATION_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
14 | VENTILATION_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
15 | VENTILATION_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
16 | VENTILATION_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
17 | VENTILATION_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
18 | VENTILATION_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CRAWLSPACE | Mixing/Well-Stirred |
2 | BREEZEWAY | Mixing/Well-Stirred |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
15 | ATTIC | Mixing/Well-Stirred |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {Btu/h} | User Des Load {Btu/h} | Calc Des Air Flow Rate {ft3/min} | User Des Air Flow Rate {ft3/min} | Design Day Name | Date/Time of Peak | Temperature at Peak {F} | Humidity Ratio at Peak {lbWater/lbDryAir} | Floor Area {ft2} | # Occupants | Calc Outdoor Air Flow Rate {ft3/min} | Calc DOAS Heat Addition Rate {Btu/h} | |
1 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | 8923.50241 | 8923.50241 | 389.30080 | 389.30080 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 82.80140 | 0.01336 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
2 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | 7972.48067 | 7972.48067 | 148.86163 | 148.86163 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 2.66000 | 0.00092 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
3 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | 3964.45221 | 3964.45221 | 172.95188 | 172.95188 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 80.01140 | 0.01336 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | 5711.39764 | 5711.39764 | 106.64448 | 106.64448 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 2.66000 | 0.00092 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | 6872.89502 | 6872.89502 | 299.83047 | 299.83047 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 81.43430 | 0.01336 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
6 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | 7959.63380 | 7959.63380 | 148.62180 | 148.62180 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 2.66000 | 0.00092 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
7 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | 8552.71733 | 8552.71733 | 373.11436 | 373.11436 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 82.52240 | 0.01336 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
8 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Heating | 7974.64841 | 7974.64841 | 148.90210 | 148.90210 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 2.66000 | 0.00092 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
9 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | 3859.49919 | 3859.49919 | 168.37413 | 168.37413 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 79.70450 | 0.01336 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
10 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Heating | 5711.39856 | 5711.39856 | 106.64469 | 106.64469 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 2.66000 | 0.00092 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
11 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | 6498.99219 | 6498.99219 | 283.51691 | 283.51691 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 79.70450 | 0.01336 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
12 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Heating | 7957.46985 | 7957.46985 | 148.58134 | 148.58134 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 2.66000 | 0.00092 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
13 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | 8804.65911 | 8804.65911 | 384.11012 | 384.11012 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 82.80140 | 0.01336 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
14 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | 5455.35259 | 5455.35259 | 101.86884 | 101.86884 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 2.66000 | 0.00092 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
15 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | 4002.02757 | 4002.02757 | 174.58790 | 174.58790 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 80.01140 | 0.01336 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
16 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | 3211.35973 | 3211.35973 | 59.96737 | 59.96737 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 2.66000 | 0.00092 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
17 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | 6975.99426 | 6975.99426 | 304.32200 | 304.32200 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | 81.85280 | 0.01336 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
18 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | 5437.62507 | 5437.62507 | 101.53791 | 101.53791 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 2.66000 | 0.00092 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
19 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | 8435.86875 | 8435.86875 | 368.00843 | 368.00843 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 82.10390 | 0.01336 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
20 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Heating | 5457.24093 | 5457.24093 | 101.90422 | 101.90422 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 2.66000 | 0.00092 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
21 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | 3856.94261 | 3856.94261 | 168.25930 | 168.25930 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 79.39760 | 0.01336 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
22 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Heating | 3211.36706 | 3211.36706 | 59.96758 | 59.96758 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 2.66000 | 0.00092 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
23 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | 6564.70847 | 6564.70847 | 286.37708 | 286.37708 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 80.59730 | 0.01336 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
24 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Heating | 5435.75294 | 5435.75294 | 101.50295 | 101.50295 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 2.66000 | 0.00092 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
25 | LIVING_UNIT3_BACKROW_TOPFLOOR | Cooling | 6606.41802 | 6606.41802 | 288.19912 | 288.19912 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 80.59730 | 0.01336 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
26 | LIVING_UNIT3_BACKROW_TOPFLOOR | Heating | 7846.76089 | 7846.76089 | 146.51439 | 146.51439 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 2.66000 | 0.00092 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
27 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Cooling | 6997.32011 | 6997.32011 | 305.25420 | 305.25420 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | 81.85280 | 0.01336 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
28 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Heating | 7848.07417 | 7848.07417 | 146.53875 | 146.53875 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 2.66000 | 0.00092 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
29 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Cooling | 9061.12881 | 9061.12881 | 395.29656 | 395.29656 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 82.52240 | 0.01336 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
30 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Heating | 7868.61737 | 7868.61737 | 146.92244 | 146.92244 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 2.66000 | 0.00092 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
31 | LIVING_UNIT2_BACKROW_TOPFLOOR | Cooling | 4381.71101 | 4381.71101 | 191.15612 | 191.15612 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 79.39760 | 0.01336 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
32 | LIVING_UNIT2_BACKROW_TOPFLOOR | Heating | 5613.27050 | 5613.27050 | 104.81227 | 104.81227 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 2.66000 | 0.00092 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
33 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Cooling | 4346.81741 | 4346.81741 | 189.63303 | 189.63303 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 80.01140 | 0.01336 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
34 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Heating | 5613.26975 | 5613.26975 | 104.81227 | 104.81227 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 2.66000 | 0.00092 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
35 | LIVING_UNIT1_BACKROW_TOPFLOOR | Cooling | 8908.59961 | 8908.59961 | 388.64402 | 388.64402 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 82.10390 | 0.01336 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
36 | LIVING_UNIT1_BACKROW_TOPFLOOR | Heating | 7869.93195 | 7869.93195 | 146.94702 | 146.94702 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 2.66000 | 0.00092 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [ft3/min] | User Des Air Flow Rate [ft3/min] | Design Day Name | Date/Time of Peak | |
1 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 2685.37 | 389.30080 | 389.30080 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 3267.57 | 148.86163 | 148.86163 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
3 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 1214.55 | 172.95188 | 172.95188 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 2614.55 | 106.64448 | 106.64448 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
5 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 2074.20 | 299.83047 | 299.83047 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 3263.86 | 148.62180 | 148.62180 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
7 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 2574.41 | 373.11436 | 373.11436 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Heating | Sensible | 3268.20 | 148.90210 | 148.90210 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
9 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 1179.98 | 168.37413 | 168.37413 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Heating | Sensible | 2614.55 | 106.64469 | 106.64469 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
11 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 1942.16 | 283.51691 | 283.51691 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Heating | Sensible | 3263.24 | 148.58134 | 148.58134 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
13 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2651.04 | 384.11012 | 384.11012 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 2540.64 | 101.86884 | 101.86884 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
15 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 1225.40 | 174.58790 | 174.58790 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 1892.55 | 59.96737 | 59.96737 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
17 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2109.79 | 304.32200 | 304.32200 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 2535.52 | 101.53791 | 101.53791 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
19 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 2534.84 | 368.00843 | 368.00843 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Heating | Sensible | 2541.18 | 101.90422 | 101.90422 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
21 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 1174.96 | 168.25930 | 168.25930 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
22 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Heating | Sensible | 1892.56 | 59.96758 | 59.96758 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
23 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 1973.55 | 286.37708 | 286.37708 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
24 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Heating | Sensible | 2534.98 | 101.50295 | 101.50295 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
25 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Cooling | Sensible | 2721.22 | 395.29656 | 395.29656 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
26 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Heating | Sensible | 3237.58 | 146.92244 | 146.92244 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
27 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Cooling | Sensible | 1324.96 | 189.63303 | 189.63303 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
28 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Heating | Sensible | 2586.21 | 104.81227 | 104.81227 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
29 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Cooling | Sensible | 2115.95 | 305.25420 | 305.25420 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
30 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Heating | Sensible | 3231.64 | 146.53875 | 146.53875 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
31 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Cooling | Sensible | 2671.36 | 388.64402 | 388.64402 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
32 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Heating | Sensible | 3237.96 | 146.94702 | 146.94702 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
33 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Cooling | Sensible | 1326.50 | 191.15612 | 191.15612 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
34 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Heating | Sensible | 2586.21 | 104.81227 | 104.81227 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
35 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Cooling | Sensible | 1985.60 | 288.19912 | 288.19912 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
36 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Heating | Sensible | 3231.26 | 146.51439 | 146.51439 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
2 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
3 | Fan:OnOff | OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
4 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
5 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 389.30080 |
7 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
8 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
9 | Fan:OnOff | OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
10 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
11 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 172.95188 |
13 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
14 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
15 | Fan:OnOff | OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
16 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
17 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
18 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 299.83047 |
19 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
20 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
21 | Fan:OnOff | OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
22 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
23 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
24 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 373.11436 |
25 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
26 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
27 | Fan:OnOff | OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
28 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
29 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
30 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 168.37413 |
31 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
32 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
33 | Fan:OnOff | OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
34 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
35 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
36 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 283.51691 |
37 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
38 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
39 | Fan:OnOff | OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
40 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
41 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
42 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 384.11012 |
43 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
44 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
45 | Fan:OnOff | OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
46 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
47 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
48 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 174.58790 |
49 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
50 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
51 | Fan:OnOff | OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
52 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
53 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
54 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 304.32200 |
55 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
56 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
57 | Fan:OnOff | OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
58 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
59 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
60 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 368.00843 |
61 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
62 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
63 | Fan:OnOff | OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
64 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
65 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
66 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 168.25930 |
67 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
68 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
69 | Fan:OnOff | OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
70 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
71 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
72 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 286.37708 |
73 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
74 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
75 | Fan:OnOff | OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
76 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
77 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
78 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 288.19912 |
79 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
80 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
81 | Fan:OnOff | OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
82 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
83 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
84 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 305.25420 |
85 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
86 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
87 | Fan:OnOff | OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
88 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
89 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
90 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 395.29656 |
91 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
92 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
93 | Fan:OnOff | OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
94 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
95 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
96 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 191.15612 |
97 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
98 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
99 | Fan:OnOff | OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
100 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
101 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
102 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 189.63303 |
103 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
104 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
105 | Fan:OnOff | OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
106 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
107 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
108 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 388.64402 |
109 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 389.30080 |
110 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 389.30080 |
111 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 389.30080 |
112 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 389.30080 |
113 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 389.30080 |
114 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 389.30080 |
115 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
116 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
117 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 172.95188 |
118 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 172.95188 |
119 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 172.95188 |
120 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 172.95188 |
121 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 172.95188 |
122 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 172.95188 |
123 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
124 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
125 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 299.83047 |
126 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 299.83047 |
127 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 299.83047 |
128 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 299.83047 |
129 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 299.83047 |
130 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 299.83047 |
131 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
132 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
133 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 373.11436 |
134 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 373.11436 |
135 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 373.11436 |
136 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 373.11436 |
137 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 373.11436 |
138 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 373.11436 |
139 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
140 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
141 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 168.37413 |
142 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 168.37413 |
143 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 168.37413 |
144 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 168.37413 |
145 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 168.37413 |
146 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 168.37413 |
147 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
148 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
149 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 283.51691 |
150 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 283.51691 |
151 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 283.51691 |
152 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 283.51691 |
153 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 283.51691 |
154 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 283.51691 |
155 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
156 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
157 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 384.11012 |
158 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 384.11012 |
159 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 384.11012 |
160 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 384.11012 |
161 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 384.11012 |
162 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 384.11012 |
163 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
164 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
165 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 174.58790 |
166 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 174.58790 |
167 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 174.58790 |
168 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 174.58790 |
169 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 174.58790 |
170 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 174.58790 |
171 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
172 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
173 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 304.32200 |
174 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 304.32200 |
175 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 304.32200 |
176 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 304.32200 |
177 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 304.32200 |
178 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 304.32200 |
179 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
180 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
181 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 368.00843 |
182 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 368.00843 |
183 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 368.00843 |
184 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 368.00843 |
185 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 368.00843 |
186 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 368.00843 |
187 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
188 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
189 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 168.25930 |
190 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 168.25930 |
191 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 168.25930 |
192 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 168.25930 |
193 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 168.25930 |
194 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 168.25930 |
195 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
196 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
197 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 286.37708 |
198 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 286.37708 |
199 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 286.37708 |
200 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 286.37708 |
201 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 286.37708 |
202 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 286.37708 |
203 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
204 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
205 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 395.29656 |
206 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 395.29656 |
207 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 395.29656 |
208 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 395.29656 |
209 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 395.29656 |
210 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 395.29656 |
211 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
212 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
213 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 189.63303 |
214 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 189.63303 |
215 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 189.63303 |
216 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 189.63303 |
217 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 189.63303 |
218 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 189.63303 |
219 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
220 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
221 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 305.25420 |
222 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 305.25420 |
223 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 305.25420 |
224 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 305.25420 |
225 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 305.25420 |
226 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 305.25420 |
227 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
228 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
229 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 388.64402 |
230 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 388.64402 |
231 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 388.64402 |
232 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 388.64402 |
233 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 388.64402 |
234 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 388.64402 |
235 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
236 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
237 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 191.15612 |
238 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 191.15612 |
239 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 191.15612 |
240 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 191.15612 |
241 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 191.15612 |
242 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 191.15612 |
243 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
244 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
245 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 288.19912 |
246 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 288.19912 |
247 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 288.19912 |
248 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 288.19912 |
249 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 288.19912 |
250 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 288.19912 |
251 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
253 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 389.30080 |
254 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 172.95188 |
255 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 299.83047 |
256 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 373.11436 |
257 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 168.37413 |
258 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 283.51691 |
259 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 384.11012 |
260 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 174.58790 |
261 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 304.32200 |
262 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 368.00843 |
263 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 168.25930 |
264 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 286.37708 |
265 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 395.29656 |
266 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 189.63303 |
267 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 305.25420 |
268 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 388.64402 |
269 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 191.15612 |
270 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 288.19912 |
271 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 389.30080 |
272 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.97959 |
273 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80059 |
274 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 389.30080 |
275 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 389.30080 |
276 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 389.30080 |
277 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 11755.13994 |
278 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.97959 |
279 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 11148.96317 |
280 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
281 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 389.30080 |
282 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 389.30080 |
283 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 11755.13994 |
284 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 11148.96317 |
285 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 172.95188 |
286 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.50147 |
287 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.74670 |
288 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 172.95188 |
289 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 172.95188 |
290 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 172.95188 |
291 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 6017.58134 |
292 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.50147 |
293 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 8920.85238 |
294 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
295 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 172.95188 |
296 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 172.95188 |
297 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 6017.58134 |
298 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 8920.85238 |
299 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 299.83047 |
300 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.76867 |
301 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.79459 |
302 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 299.83047 |
303 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 299.83047 |
304 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 299.83047 |
305 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 9224.07126 |
306 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.76867 |
307 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 11136.30346 |
308 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
309 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 299.83047 |
310 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 299.83047 |
311 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 9224.07126 |
312 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 11136.30346 |
313 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 373.11436 |
314 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.94449 |
315 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
316 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 373.11436 |
317 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 373.11436 |
318 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 373.11436 |
319 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 11333.86952 |
320 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.94449 |
321 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 11151.09932 |
322 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
323 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 373.11436 |
324 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 373.11436 |
325 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 11333.86952 |
326 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 11151.09932 |
327 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 168.37413 |
328 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.49163 |
329 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.74473 |
330 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 168.37413 |
331 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 168.37413 |
332 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 168.37413 |
333 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 5899.61308 |
334 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.49163 |
335 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 8920.85327 |
336 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
337 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 168.37413 |
338 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 168.37413 |
339 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 5899.61308 |
340 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 8920.85327 |
341 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 283.51691 |
342 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.72632 |
343 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.79483 |
344 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 283.51691 |
345 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 283.51691 |
346 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 283.51691 |
347 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 8715.84659 |
348 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.72632 |
349 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 11134.17106 |
350 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
351 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 283.51691 |
352 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 283.51691 |
353 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 8715.84659 |
354 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 11134.17106 |
355 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 384.11012 |
356 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.95227 |
357 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80045 |
358 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 384.11012 |
359 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 384.11012 |
360 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 384.11012 |
361 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 11427.28735 |
362 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.95227 |
363 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 8668.66030 |
364 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
365 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 384.11012 |
366 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 384.11012 |
367 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 11427.28735 |
368 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 8668.66030 |
369 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 174.58790 |
370 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.49348 |
371 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.75597 |
372 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 174.58790 |
373 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 174.58790 |
374 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 174.58790 |
375 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 5921.74996 |
376 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.49348 |
377 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 6457.39500 |
378 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
379 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 174.58790 |
380 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 174.58790 |
381 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 5921.74996 |
382 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 6457.39500 |
383 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 304.32200 |
384 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.76520 |
385 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80083 |
386 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 304.32200 |
387 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 304.32200 |
388 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 304.32200 |
389 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 9182.43391 |
390 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.76520 |
391 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 8651.19103 |
392 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
393 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 304.32200 |
394 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 304.32200 |
395 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 9182.43391 |
396 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 8651.19103 |
397 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 368.00843 |
398 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.91585 |
399 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80020 |
400 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 368.00843 |
401 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 368.00843 |
402 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 368.00843 |
403 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 10990.19718 |
404 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.91585 |
405 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 8670.52114 |
406 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
407 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 368.00843 |
408 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 368.00843 |
409 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 10990.19718 |
410 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 8670.52114 |
411 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 168.25930 |
412 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.47827 |
413 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.75435 |
414 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 168.25930 |
415 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 168.25930 |
416 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 168.25930 |
417 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 5739.27914 |
418 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.47827 |
419 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 6457.40223 |
420 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
421 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 168.25930 |
422 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 168.25930 |
423 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 5739.27914 |
424 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 6457.40223 |
425 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 286.37708 |
426 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.72147 |
427 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80021 |
428 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 286.37708 |
429 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 286.37708 |
430 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 286.37708 |
431 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 8657.61395 |
432 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.72147 |
433 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 8649.34613 |
434 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
435 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 286.37708 |
436 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 286.37708 |
437 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 8657.61395 |
438 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 8649.34613 |
439 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 395.29656 |
440 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.99143 |
441 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
442 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 395.29656 |
443 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 395.29656 |
444 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 395.29656 |
445 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 11897.16680 |
446 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.99143 |
447 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 11046.61286 |
448 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
449 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 395.29656 |
450 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 395.29656 |
451 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 11897.16680 |
452 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 11046.61286 |
453 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 189.63303 |
454 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.53862 |
455 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.75456 |
456 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 189.63303 |
457 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 189.63303 |
458 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 189.63303 |
459 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 6463.49763 |
460 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.53862 |
461 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 8824.15412 |
462 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
463 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 189.63303 |
464 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 189.63303 |
465 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 6463.49763 |
466 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 8824.15412 |
467 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 305.25420 |
468 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.78238 |
469 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.79468 |
470 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 305.25420 |
471 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 305.25420 |
472 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 305.25420 |
473 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 9388.51536 |
474 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.78238 |
475 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 11026.36895 |
476 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
477 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 305.25420 |
478 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 305.25420 |
479 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 9388.51536 |
480 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 11026.36895 |
481 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 388.64402 |
482 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.97562 |
483 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80037 |
484 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 388.64402 |
485 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 388.64402 |
486 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 388.64402 |
487 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 11707.46178 |
488 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.97562 |
489 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 11047.90829 |
490 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
491 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 388.64402 |
492 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 388.64402 |
493 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 11707.46178 |
494 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 11047.90829 |
495 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 191.15612 |
496 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.54003 |
497 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.75612 |
498 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 191.15612 |
499 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 191.15612 |
500 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 191.15612 |
501 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 6480.36090 |
502 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.54003 |
503 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 8824.15487 |
504 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
505 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 191.15612 |
506 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 191.15612 |
507 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 6480.36090 |
508 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 8824.15487 |
509 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 288.19912 |
510 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.74000 |
511 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.79410 |
512 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 288.19912 |
513 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 288.19912 |
514 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 288.19912 |
515 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 8880.05281 |
516 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.74000 |
517 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 11025.07478 |
518 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
519 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 288.19912 |
520 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 288.19912 |
521 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 8880.05281 |
522 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 11025.07478 |
523 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
524 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
525 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
526 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
527 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
528 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
529 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
530 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
531 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
532 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
533 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
534 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
535 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
536 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
537 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
538 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
539 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
540 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
541 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
542 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
543 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
544 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
545 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
546 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
547 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
548 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
549 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
550 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
551 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
552 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
553 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
554 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
555 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
556 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
557 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
558 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
559 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
560 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
561 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
562 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
563 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
564 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
565 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
566 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
567 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
568 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
569 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
570 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
571 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
572 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
573 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
574 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
575 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
576 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
577 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
578 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
579 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
580 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
581 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
582 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
583 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
584 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
585 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
586 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
587 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
588 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
589 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
590 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
591 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
592 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
593 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
594 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
595 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
596 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
597 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
598 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
599 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
600 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
601 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
602 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
603 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
604 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
605 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
606 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
607 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
608 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
609 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
610 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
611 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
612 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
613 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
614 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
615 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
616 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
617 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
618 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
619 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
620 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
621 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
622 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
623 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
624 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
625 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
626 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
627 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
628 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
629 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
630 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
631 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
632 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
633 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
634 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
635 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
636 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
637 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
638 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
639 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
640 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
641 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
642 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
643 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
644 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
645 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
646 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
647 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
648 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {ton} | Standard Rated Net COP {Btuh/Btuh} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 0.9 | 3.34 | 11.39 | 11.93 | 11.28 | 11.27 |
2 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5 | 3.42 | 11.67 | 12.24 | 11.58 | 11.71 |
3 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.7 | 3.35 | 11.43 | 11.97 | 11.32 | 11.33 |
4 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 0.9 | 3.34 | 11.40 | 11.94 | 11.29 | 11.29 |
5 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.5 | 3.43 | 11.69 | 12.26 | 11.59 | 11.73 |
6 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.7 | 3.35 | 11.42 | 11.97 | 11.32 | 11.33 |
7 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 0.9 | 3.33 | 11.36 | 11.89 | 11.25 | 11.22 |
8 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5 | 3.41 | 11.62 | 12.19 | 11.53 | 11.63 |
9 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.7 | 3.34 | 11.39 | 11.92 | 11.28 | 11.27 |
10 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 0.9 | 3.33 | 11.36 | 11.90 | 11.26 | 11.24 |
11 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.5 | 3.41 | 11.63 | 12.20 | 11.54 | 11.65 |
12 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.7 | 3.34 | 11.39 | 11.93 | 11.28 | 11.28 |
13 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 0.9 | 3.34 | 11.38 | 11.92 | 11.27 | 11.26 |
14 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.5 | 3.41 | 11.63 | 12.20 | 11.54 | 11.65 |
15 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.8 | 3.35 | 11.43 | 11.97 | 11.32 | 11.33 |
16 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 0.9 | 3.34 | 11.38 | 11.92 | 11.28 | 11.26 |
17 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.5 | 3.41 | 11.62 | 12.19 | 11.53 | 11.63 |
18 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.7 | 3.35 | 11.43 | 11.97 | 11.33 | 11.34 |
Component Type | Component Name | High Temperature Heating (net) Rating Capacity {Btu/h} | Low Temperature Heating (net) Rating Capacity {Btu/h} | HSPF {Btu/W-h} | Region Number | |
1 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 12254.2 | 6796.4 | 7.96 | 4 |
2 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 6240.2 | 3446.5 | 8.05 | 4 |
3 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 9608.5 | 5326.1 | 7.94 | 4 |
4 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 11812.3 | 6550.0 | 7.98 | 4 |
5 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 6116.4 | 3377.2 | 8.06 | 4 |
6 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 9079.3 | 5032.7 | 7.92 | 4 |
7 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 11919.5 | 6613.8 | 7.96 | 4 |
8 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 6146.4 | 3397.0 | 8.04 | 4 |
9 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 9572.7 | 5309.1 | 7.93 | 4 |
10 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 11461.9 | 6359.3 | 7.97 | 4 |
11 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 5955.6 | 3291.2 | 8.04 | 4 |
12 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 9024.7 | 5005.1 | 7.91 | 4 |
13 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 12404.0 | 6880.0 | 7.96 | 4 |
14 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 6707.7 | 3706.5 | 8.03 | 4 |
15 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 9780.2 | 5421.0 | 7.94 | 4 |
16 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 12205.7 | 6770.1 | 7.96 | 4 |
17 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 6726.4 | 3717.4 | 8.02 | 4 |
18 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 9249.6 | 5126.9 | 7.93 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | SizingPeriod:DesignDay | 01/21 | 01/21 | WinterDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
2 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | SizingPeriod:DesignDay | 07/21 | 07/21 | SummerDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
3 | ANNUAL | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | Yes | Yes | No | Yes | Yes | Clark and Allen |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | No | SizingPeriod:DesignDay | ||
2 | No | SizingPeriod:DesignDay | ||
3 | No |
NumberofWarmupDays | |
1 | 8 |
2 | 6 |
3 | 25 |
Max Dry-Bulb Temp {F} | Temp Range {dC} | Temp Range Ind Type | Hum Ind Type | Hum Ind Value at Max Temp | Hum Ind Units | Pressure {psi} | Wind Direction {deg CW from N} | Wind Speed {ft/min} | Clearness | Rain | Snow | |
1 | 2.66 | 0.00 | DefaultMultipliers | Wetbulb | -16.30 | {C} | 14. | 270 | 1004.0 | 0.00 | No | No |
2 | 86.54 | 9.30 | DefaultMultipliers | Wetbulb | 21.80 | {C} | 14. | 240 | 1122.1 | 0.00 | No | No |
DayOfYear | ASHRAE A Coeff | ASHRAE B Coeff | ASHRAE C Coeff | Solar Constant-Annual Variation | Eq of Time {minutes} | Solar Declination Angle {deg} | Solar Model | |
1 | 21 | 1229.0 | 0.1415 | 5.7310E-002 | 1.0 | -11.15 | -20. | ASHRAEClearSky |
2 | 202 | 1084.4 | 0.2082 | 0.1365 | 1.0 | -6.23 | 20.6 | ASHRAETau |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaF} | Std Dev Warmup Temperature Difference {deltaF} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {Btu/h} | Std Dev Warmup Load Difference {Btu/h} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CRAWLSPACE | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.000127132 | 0.000091048 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
2 | BREEZEWAY | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.000605345 | 0.000164210 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.000001314 | 0.000004591 | Pass | Pass | 0.010522621 | 0.020365138 | Pass | Pass |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.109972365 | 0.228435847 | Pass | Pass | 0.122352014 | 0.357066160 | Pass | Pass |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.000001318 | 0.000004748 | Pass | Pass | 0.010541093 | 0.020414643 | Pass | Pass |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.000001317 | 0.000004629 | Pass | Pass | 0.010510574 | 0.020325787 | Pass | Pass |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.118835051 | 0.240135756 | Pass | Pass | 0.133363274 | 0.396039734 | Pass | Pass |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.000062605 | 0.000504085 | Pass | Pass | 0.010577039 | 0.020369264 | Pass | Pass |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.000001033 | 0.000003309 | Pass | Pass | 0.015152379 | 0.028970590 | Pass | Pass |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.037567202 | 0.097136896 | Pass | Pass | 0.118451484 | 0.271831403 | Pass | Pass |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.000001039 | 0.000003402 | Pass | Pass | 0.015206857 | 0.029096595 | Pass | Pass |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.000001036 | 0.000003333 | Pass | Pass | 0.015129329 | 0.028944618 | Pass | Pass |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.042536052 | 0.105535334 | Pass | Pass | 0.107160980 | 0.258200682 | Pass | Pass |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.000067978 | 0.000537548 | Pass | Pass | 0.015279802 | 0.029057185 | Pass | Pass |
15 | ATTIC | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.000034947 | 0.000022075 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.000001299 | 0.000004703 | Pass | Pass | 0.010409465 | 0.018874462 | Pass | Pass |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.000001298 | 0.000004673 | Pass | Pass | 0.010403277 | 0.018871937 | Pass | Pass |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.000001296 | 0.000004522 | Pass | Pass | 0.010373907 | 0.018805033 | Pass | Pass |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.052382780 | 0.138551131 | Pass | Pass | 0.093934596 | 0.238290089 | Pass | Pass |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.056321389 | 0.147396548 | Pass | Pass | 0.096581296 | 0.245119442 | Pass | Pass |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.000001296 | 0.000004534 | Pass | Pass | 0.010376572 | 0.018801022 | Pass | Pass |
22 | CRAWLSPACE | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 0.183951290 | 0.108323039 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
23 | BREEZEWAY | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 0.042139491 | 0.023103992 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
24 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 0.009727789 | 0.061132921 | Pass | Pass | 0.143391516 | 0.295114880 | Pass | Pass |
25 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 0.014307445 | 0.082194733 | Pass | Pass | 0.108568679 | 0.268958404 | Pass | Pass |
26 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 0.000185185 | 0.000710582 | Pass | Pass | 0.085383311 | 0.084079273 | Pass | Pass |
27 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 0.008494616 | 0.053134723 | Pass | Pass | 0.139416580 | 0.263027560 | Pass | Pass |
28 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 0.015441148 | 0.078040490 | Pass | Pass | 0.120245186 | 0.286720460 | Pass | Pass |
29 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 0.000190682 | 0.000720421 | Pass | Pass | 0.085662670 | 0.089584153 | Pass | Pass |
30 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 0.007708809 | 0.046707445 | Pass | Pass | 0.119499581 | 0.214816633 | Pass | Pass |
31 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 0.011094304 | 0.070896960 | Pass | Pass | 0.101091779 | 0.309710035 | Pass | Pass |
32 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 0.000185572 | 0.000704858 | Pass | Pass | 0.075586585 | 0.069546322 | Pass | Pass |
33 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 0.006434623 | 0.038197181 | Pass | Pass | 0.115186436 | 0.186424524 | Pass | Pass |
34 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 0.011944584 | 0.065116999 | Pass | Pass | 0.104567081 | 0.315699244 | Pass | Pass |
35 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 0.000183871 | 0.000709263 | Pass | Pass | 0.075385402 | 0.074369957 | Pass | Pass |
36 | ATTIC | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 0.407143193 | 0.289341462 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
37 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 0.000177993 | 0.000691997 | Pass | Pass | 0.072831895 | 0.072694072 | Pass | Pass |
38 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 0.000181810 | 0.000691373 | Pass | Pass | 0.073562625 | 0.068062757 | Pass | Pass |
39 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 0.006458367 | 0.036530704 | Pass | Pass | 0.113496123 | 0.196209009 | Pass | Pass |
40 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 0.008506844 | 0.053274435 | Pass | Pass | 0.094346785 | 0.257946976 | Pass | Pass |
41 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 0.009403971 | 0.061053682 | Pass | Pass | 0.098400134 | 0.293985338 | Pass | Pass |
42 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 0.005312600 | 0.029121615 | Pass | Pass | 0.110861785 | 0.177454174 | Pass | Pass |
43 | CRAWLSPACE | RunPeriod: ANNUAL | 0.128249871 | 0.090463364 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
44 | BREEZEWAY | RunPeriod: ANNUAL | 0.007150252 | 0.004282763 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
45 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000105172 | 0.000309673 | Pass | Pass | 0.040854877 | 0.054989527 | Pass | Pass |
46 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000036218 | 0.000125264 | Pass | Pass | 0.056370240 | 0.098816527 | Pass | Pass |
47 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000036685 | 0.000186071 | Pass | Pass | 0.039061841 | 0.053482057 | Pass | Pass |
48 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000029592 | 0.000107531 | Pass | Pass | 0.037907685 | 0.052840289 | Pass | Pass |
49 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000040214 | 0.000130685 | Pass | Pass | 0.052005419 | 0.094752513 | Pass | Pass |
50 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000060873 | 0.000232115 | Pass | Pass | 0.036115776 | 0.051904311 | Pass | Pass |
51 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000059537 | 0.000223057 | Pass | Pass | 0.062026224 | 0.099583393 | Pass | Pass |
52 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.029772852 | 0.072206055 | Pass | Pass | 0.689314E+02 | 0.630892E+03 | Fail | Pass |
53 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000016952 | 0.000087224 | Pass | Pass | 0.058961442 | 0.096531538 | Pass | Pass |
54 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000063907 | 0.000217694 | Pass | Pass | 0.055903854 | 0.092862569 | Pass | Pass |
55 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.020301952 | 0.056911442 | Pass | Pass | 5.038622990 | 0.452444E+02 | Pass | Pass |
56 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000003593 | 0.000007578 | Pass | Pass | 0.053241068 | 0.090702508 | Pass | Pass |
57 | ATTIC | RunPeriod: ANNUAL | 0.132984117 | 0.101513550 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
58 | LIVING_UNIT3_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000058829 | 0.000243005 | Pass | Pass | 0.034309877 | 0.047980245 | Pass | Pass |
59 | LIVING_UNIT3_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000027365 | 0.000145188 | Pass | Pass | 0.036626652 | 0.049014141 | Pass | Pass |
60 | LIVING_UNIT1_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000117030 | 0.000338567 | Pass | Pass | 0.038486067 | 0.049821815 | Pass | Pass |
61 | LIVING_UNIT2_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000056735 | 0.000181442 | Pass | Pass | 0.050654573 | 0.088262054 | Pass | Pass |
62 | LIVING_UNIT2_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000058366 | 0.000189235 | Pass | Pass | 0.053927028 | 0.091484614 | Pass | Pass |
63 | LIVING_UNIT1_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000073411 | 0.000225254 | Pass | Pass | 0.035824027 | 0.048601970 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [kBtu] | 2239788.10 | 460600.10 | 0.00 | 0.00 | 15828.17 | 2716227.22 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 2.66 | 0.00 | 2.66 | Wetbulb [F] | 1003.99 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 86.54 | 16.74 | 71.24 | Wetbulb [F] | 1122.10 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | CRAWL WALL | 0.30 | 0.776 | 2.276 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_LOWER_LDF | CRAWL WALL | 0.30 | 0.893 | 2.276 | 239.83 | 239.83 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | CRAWL WALL | 0.30 | 0.776 | 2.276 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_LOWER_SDR | CRAWL WALL | 0.30 | 0.893 | 2.276 | 130.22 | 130.22 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | CRAWL WALL | 0.30 | 0.776 | 2.276 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_LOWER_LDB | CRAWL WALL | 0.30 | 0.893 | 2.276 | 239.83 | 239.83 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | CRAWL WALL | 0.30 | 0.776 | 2.276 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BGWALL_LOWER_SDL | CRAWL WALL | 0.30 | 0.893 | 2.276 | 130.22 | 130.22 | 270.00 | 90.00 | W |
BGFLOOR | INTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 7794.39 | 7794.39 | 0.00 | 180.00 | |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.39 | 599.39 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
iz-FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
BREEZEWAYROOF | INTERIOR CEILING | 0.30 | 0.018 | 0.019 | 599.39 | 599.39 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-BREEZEWAYROOF | ATTIC FLOOR | 0.30 | 0.018 | 0.019 | 599.39 | 599.39 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 180.00 | 0.00 |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.300 | 0.335 | 0.883 | ||||||||||||
North Total or Average | 531.68 | 0.300 | 0.335 | 0.883 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.300 | 0.335 | 0.883 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.93 | 0.98 | 0.97 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.93 | 0.98 | 0.97 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.93 | 0.98 | 0.97 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.95 | 0.00 | 1.00 | 0.97 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.95 | 0.00 | 1.00 | 0.97 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.93 | 0.98 | 0.97 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.93 | 0.98 | 0.97 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.93 | 0.98 | 0.97 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.95 | 0.00 | 1.00 | 0.97 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.95 | 0.00 | 1.00 | 0.97 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.95 | 0.00 | 1.00 | 0.97 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.93 | 0.98 | 0.97 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.95 | 0.00 | 1.00 | 0.97 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.93 | 0.98 | 0.97 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.93 | 0.98 | 0.97 | 1.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.2915 | 43219.92 | 12599.76 | 11336.81 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
Exterior Lighting Total | 1257.69 | 5508.71 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 11755.14 | 9411.02 | 2344.12 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 6017.58 | 4493.33 | 1524.25 | 0.75 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 9224.07 | 7329.38 | 1894.69 | 0.79 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 11333.87 | 9074.63 | 2259.24 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 5899.61 | 4393.60 | 1506.01 | 0.74 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8715.85 | 6927.61 | 1788.24 | 0.79 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 11427.29 | 9146.93 | 2280.36 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 5921.75 | 4476.64 | 1445.11 | 0.76 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9182.43 | 7353.59 | 1828.85 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10990.20 | 8794.38 | 2195.82 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 5739.28 | 4329.40 | 1409.88 | 0.75 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8657.61 | 6927.92 | 1729.69 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 11897.17 | 9525.58 | 2371.59 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 6463.50 | 4877.10 | 1586.40 | 0.75 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 9388.52 | 7460.86 | 1927.66 | 0.79 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 11707.46 | 9370.26 | 2337.20 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 6480.36 | 4899.90 | 1580.46 | 0.76 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 8880.05 | 7051.69 | 1828.36 | 0.79 | 4.07 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 0.9 | 3.34 | 11.39 | 11.93 | 11.28 | 11.27 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5 | 3.42 | 11.67 | 12.24 | 11.58 | 11.71 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.7 | 3.35 | 11.43 | 11.97 | 11.32 | 11.33 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 0.9 | 3.34 | 11.40 | 11.94 | 11.29 | 11.29 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.5 | 3.43 | 11.69 | 12.26 | 11.59 | 11.73 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.7 | 3.35 | 11.42 | 11.97 | 11.32 | 11.33 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 0.9 | 3.33 | 11.36 | 11.89 | 11.25 | 11.22 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5 | 3.41 | 11.62 | 12.19 | 11.53 | 11.63 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.7 | 3.34 | 11.39 | 11.92 | 11.28 | 11.27 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 0.9 | 3.33 | 11.36 | 11.90 | 11.26 | 11.24 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.5 | 3.41 | 11.63 | 12.20 | 11.54 | 11.65 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.7 | 3.34 | 11.39 | 11.93 | 11.28 | 11.28 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 0.9 | 3.34 | 11.38 | 11.92 | 11.27 | 11.26 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.5 | 3.41 | 11.63 | 12.20 | 11.54 | 11.65 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.8 | 3.35 | 11.43 | 11.97 | 11.32 | 11.33 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 0.9 | 3.34 | 11.38 | 11.92 | 11.28 | 11.26 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.5 | 3.41 | 11.62 | 12.19 | 11.53 | 11.63 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.7 | 3.35 | 11.43 | 11.97 | 11.33 | 11.34 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 12254.2 | 6796.4 | 7.96 | 4 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 6240.3 | 3446.3 | 8.05 | 4 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 9608.7 | 5326.0 | 7.94 | 4 |
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 11812.3 | 6550.0 | 7.98 | 4 |
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 6116.5 | 3377.3 | 8.06 | 4 |
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 9079.5 | 5032.8 | 7.92 | 4 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 11919.5 | 6613.9 | 7.96 | 4 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 6146.4 | 3396.9 | 8.04 | 4 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 9572.6 | 5309.2 | 7.93 | 4 |
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 11461.8 | 6359.1 | 7.97 | 4 |
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 5955.8 | 3291.1 | 8.04 | 4 |
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 9024.8 | 5005.1 | 7.91 | 4 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 12403.9 | 6880.1 | 7.96 | 4 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 6707.5 | 3706.5 | 8.03 | 4 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 9780.1 | 5421.0 | 7.94 | 4 |
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 12205.7 | 6770.0 | 7.96 | 4 |
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 6726.3 | 3717.5 | 8.02 | 4 |
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 9249.7 | 5126.8 | 7.93 | 4 |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 11755.14 | 3.69 | |
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 11148.96 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 6017.58 | 3.69 | |
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 8920.85 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 9224.07 | 3.69 | |
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 11136.30 | 1.00 | |
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 11333.87 | 3.69 | |
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 11151.10 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 5899.61 | 3.69 | |
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 8920.85 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 8715.85 | 3.69 | |
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 11134.17 | 1.00 | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 11427.29 | 3.69 | |
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 8668.66 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 5921.75 | 3.69 | |
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 6457.40 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 9182.43 | 3.69 | |
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 8651.19 | 1.00 | |
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 10990.20 | 3.69 | |
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 8670.52 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 5739.28 | 3.69 | |
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 6457.40 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 8657.61 | 3.69 | |
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 8649.35 | 1.00 | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 11897.17 | 3.69 | |
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 11046.61 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 6463.50 | 3.69 | |
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 8824.15 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 9388.52 | 3.69 | |
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 11026.37 | 1.00 | |
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 11707.46 | 3.69 | |
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | 11047.91 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 6480.36 | 3.69 | |
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | 8824.15 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 8880.05 | 3.69 | |
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | 11025.07 | 1.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 389.29 | 146.84 | 0.38 | 1.00 | 2.41 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 172.95 | 65.24 | 0.38 | 1.00 | 3.88 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 299.83 | 113.09 | 0.38 | 1.00 | 2.76 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 373.12 | 140.74 | 0.38 | 1.00 | 2.46 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 168.37 | 63.51 | 0.38 | 1.00 | 3.96 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 283.52 | 106.94 | 0.38 | 1.00 | 2.85 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 384.10 | 144.88 | 0.38 | 1.00 | 2.42 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 174.59 | 65.85 | 0.38 | 1.00 | 3.86 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 304.32 | 114.79 | 0.38 | 1.00 | 2.74 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 368.01 | 138.81 | 0.38 | 1.00 | 2.48 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 168.26 | 63.47 | 0.38 | 1.00 | 3.96 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 286.38 | 108.02 | 0.38 | 1.00 | 2.84 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 395.30 | 149.10 | 0.38 | 1.00 | 2.39 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 189.63 | 71.53 | 0.38 | 1.00 | 3.65 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 305.26 | 115.14 | 0.38 | 1.00 | 2.74 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 388.64 | 146.59 | 0.38 | 1.00 | 2.41 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 191.16 | 72.10 | 0.38 | 1.00 | 3.63 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 288.21 | 108.71 | 0.38 | 1.00 | 2.83 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electricity Rate [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | End Use Subcategory | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4465.96 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4465.96 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4465.96 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4465.96 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4465.96 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4465.96 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4465.96 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4465.96 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4465.96 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4465.96 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4465.96 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4465.96 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4465.96 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4465.96 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4465.96 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4465.96 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4465.96 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4465.96 | 1.00 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8923.50 | 8923.50 | 7.43 | 389.293 | 389.293 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 75.00 | 75.00 | 0.00860 | 82.80 | 0.01336 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 3964.45 | 3964.45 | 3.30 | 172.952 | 172.952 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00918 | 80.01 | 0.01336 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6872.90 | 6872.90 | 5.72 | 299.831 | 299.831 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 75.00 | 75.00 | 0.00859 | 81.43 | 0.01336 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8552.72 | 8552.72 | 7.12 | 373.118 | 373.118 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 75.00 | 75.00 | 0.00863 | 82.52 | 0.01336 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 3859.50 | 3859.50 | 3.21 | 168.374 | 168.374 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 75.00 | 75.00 | 0.00925 | 79.70 | 0.01336 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6498.99 | 6498.99 | 5.41 | 283.520 | 283.520 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 75.00 | 75.00 | 0.00863 | 79.70 | 0.01336 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8804.66 | 8804.66 | 7.33 | 384.100 | 384.100 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 75.00 | 75.00 | 0.00847 | 82.80 | 0.01336 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4002.03 | 4002.03 | 3.33 | 174.588 | 174.588 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00890 | 80.01 | 0.01336 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 6975.99 | 6975.99 | 5.81 | 304.322 | 304.322 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | 75.00 | 75.00 | 0.00841 | 81.85 | 0.01336 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8435.87 | 8435.87 | 7.03 | 368.013 | 368.013 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 75.00 | 75.00 | 0.00850 | 82.10 | 0.01336 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 3856.94 | 3856.94 | 3.21 | 168.259 | 168.259 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 75.00 | 75.00 | 0.00896 | 79.40 | 0.01336 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 6564.71 | 6564.71 | 5.47 | 286.381 | 286.381 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 75.00 | 75.00 | 0.00844 | 80.60 | 0.01336 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 6606.42 | 6606.42 | 5.50 | 288.206 | 288.206 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 75.00 | 75.00 | 0.00861 | 80.60 | 0.01336 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 6997.32 | 6997.32 | 5.83 | 305.259 | 305.259 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | 75.00 | 75.00 | 0.00858 | 81.85 | 0.01336 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 9061.13 | 9061.13 | 7.55 | 395.298 | 395.298 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 75.00 | 75.00 | 0.00860 | 82.52 | 0.01336 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 4381.71 | 4381.71 | 3.65 | 191.156 | 191.156 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 75.00 | 75.00 | 0.00911 | 79.40 | 0.01336 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 4346.82 | 4346.82 | 3.62 | 189.633 | 189.633 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00910 | 80.01 | 0.01336 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8908.60 | 8908.60 | 7.42 | 388.644 | 388.644 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 75.00 | 75.00 | 0.00862 | 82.10 | 0.01336 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 7972.48 | 7972.48 | 6.64 | 148.862 | 148.862 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00693 | 2.66 | 0.00092 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5711.40 | 5711.40 | 4.76 | 106.645 | 106.645 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00678 | 2.66 | 0.00092 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 7959.63 | 7959.63 | 6.63 | 148.622 | 148.622 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00693 | 2.66 | 0.00092 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 7974.65 | 7974.65 | 6.64 | 148.902 | 148.902 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00693 | 2.66 | 0.00092 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5711.40 | 5711.40 | 4.76 | 106.645 | 106.645 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00678 | 2.66 | 0.00092 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 7957.47 | 7957.47 | 6.63 | 148.581 | 148.581 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00693 | 2.66 | 0.00092 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5455.35 | 5455.35 | 4.54 | 101.869 | 101.869 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00749 | 2.66 | 0.00092 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 3211.36 | 3211.36 | 2.67 | 59.967 | 59.967 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00760 | 2.66 | 0.00092 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5437.63 | 5437.63 | 4.53 | 101.538 | 101.538 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00749 | 2.66 | 0.00092 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5457.24 | 5457.24 | 4.55 | 101.904 | 101.904 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00749 | 2.66 | 0.00092 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 3211.37 | 3211.37 | 2.67 | 59.968 | 59.968 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00760 | 2.66 | 0.00092 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5435.75 | 5435.75 | 4.53 | 101.503 | 101.503 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00749 | 2.66 | 0.00092 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 7846.76 | 7846.76 | 6.54 | 146.514 | 146.514 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00692 | 2.66 | 0.00092 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7848.07 | 7848.07 | 6.54 | 146.539 | 146.539 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00692 | 2.66 | 0.00092 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 7868.62 | 7868.62 | 6.55 | 146.922 | 146.922 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00692 | 2.66 | 0.00092 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 5613.27 | 5613.27 | 4.68 | 104.812 | 104.812 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00677 | 2.66 | 0.00092 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 5613.27 | 5613.27 | 4.68 | 104.812 | 104.812 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00677 | 2.66 | 0.00092 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 7869.93 | 7869.93 | 6.56 | 146.947 | 146.947 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00692 | 2.66 | 0.00092 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | Adjusted cooling [ft3/min] | Adjusted heating [ft3/min] | Adjusted main [ft3/min] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 389.29 | 389.29 | 148.86 | 148.86 | 389.2927 | 389.2927 | 389.2927 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 172.95 | 172.95 | 106.64 | 106.64 | 172.9519 | 172.9519 | 172.9519 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 299.83 | 299.83 | 148.62 | 148.62 | 299.8306 | 299.8306 | 299.8306 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 373.12 | 373.12 | 148.90 | 148.90 | 373.1180 | 373.1180 | 373.1180 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 168.37 | 168.37 | 106.64 | 106.64 | 168.3741 | 168.3741 | 168.3741 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 283.52 | 283.52 | 148.58 | 148.58 | 283.5202 | 283.5202 | 283.5202 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 384.10 | 384.10 | 101.87 | 101.87 | 384.1001 | 384.1001 | 384.1001 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 174.59 | 174.59 | 59.97 | 59.97 | 174.5878 | 174.5878 | 174.5878 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 304.32 | 304.32 | 101.54 | 101.54 | 304.3220 | 304.3220 | 304.3220 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 368.01 | 368.01 | 101.90 | 101.90 | 368.0134 | 368.0134 | 368.0134 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 168.26 | 168.26 | 59.97 | 59.97 | 168.2593 | 168.2593 | 168.2593 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 286.38 | 286.38 | 101.50 | 101.50 | 286.3806 | 286.3806 | 286.3806 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 395.30 | 395.30 | 146.92 | 146.92 | 395.2975 | 395.2975 | 395.2975 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 189.63 | 189.63 | 104.81 | 104.81 | 189.6331 | 189.6331 | 189.6331 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 305.26 | 305.26 | 146.54 | 146.54 | 305.2586 | 305.2586 | 305.2586 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 388.64 | 388.64 | 146.95 | 146.95 | 388.6443 | 388.6443 | 388.6443 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 191.16 | 191.16 | 104.81 | 104.81 | 191.1561 | 191.1561 | 191.1561 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 288.21 | 288.21 | 146.51 | 146.51 | 288.2059 | 288.2059 | 288.2059 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 11755.140 | 9411.015 | 389.292677 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 11890.18 | 9950.61 | 389.292677 | 77.10 | 62.67 | 0.00914998 | 53.60 | 51.86 | 0.00800000 | 82.80 | 0.01336327 | 70.21 | 11.5581 | 75.00 | 0.00858987 | 45.3766 | 8923.32 | 0.00 | 11753.12 | 9280.34 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 11755.140 | 11755.140 | 389.292677 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11755.14 | 11755.14 | 389.292677 | 63.98 | 52.97 | 0.00623842 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 11.5581 | 71.99 | 0.00693293 | 40.6213 | 7972.48 | 0.00 | 11770.59 | 11770.59 |
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 11148.963 | 11148.963 | -999. | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11148.96 | 11148.96 | 389.292677 | 63.98 | 52.97 | 0.00623842 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 11.5581 | 71.99 | 0.00693293 | 40.6213 | 7972.48 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 6017.581 | 4493.327 | 172.951945 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5912.68 | 4288.61 | 172.951945 | 77.50 | 64.43 | 0.01026751 | 53.60 | 51.86 | 0.00800000 | 80.01 | 0.01336053 | 69.39 | 26.0159 | 75.00 | 0.00889802 | 46.9822 | 3890.08 | 0.00 | 6016.55 | 4435.55 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 6017.581 | 6017.581 | 172.951945 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6017.58 | 6017.58 | 172.951945 | 53.96 | 46.70 | 0.00525948 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 26.0159 | 72.00 | 0.00678398 | 39.7569 | 5711.40 | 0.00 | 6025.49 | 6025.49 |
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 8920.852 | 8920.852 | -999. | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 8920.85 | 8920.85 | 172.951945 | 53.96 | 46.70 | 0.00525948 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 26.0159 | 72.00 | 0.00678398 | 39.7569 | 5711.40 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 9224.071 | 7329.383 | 299.830602 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 9262.92 | 7588.09 | 299.830602 | 77.16 | 62.93 | 0.00930529 | 53.60 | 51.86 | 0.00800000 | 81.43 | 0.01336193 | 69.81 | 15.0068 | 75.00 | 0.00858709 | 45.3616 | 6864.47 | 0.00 | 9222.49 | 7226.49 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 9224.071 | 9224.071 | 299.830602 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 9224.07 | 9224.07 | 299.830602 | 61.59 | 51.59 | 0.00603001 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 15.0068 | 71.99 | 0.00693154 | 40.6132 | 7959.63 | 0.00 | 9236.19 | 9236.19 |
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 11136.303 | 11136.303 | -999. | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11136.30 | 11136.30 | 299.830602 | 61.59 | 51.59 | 0.00603001 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 15.0068 | 71.99 | 0.00693154 | 40.6132 | 7959.63 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 11333.870 | 9074.625 | 373.117972 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 11443.48 | 9511.05 | 373.117972 | 77.10 | 62.75 | 0.00919894 | 53.60 | 51.86 | 0.00800000 | 82.52 | 0.01336300 | 70.13 | 12.0592 | 75.00 | 0.00862793 | 45.5750 | 8552.72 | 0.00 | 11331.93 | 8946.97 |
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 11333.870 | 11333.870 | 373.117972 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11333.87 | 11333.87 | 373.117972 | 63.63 | 52.78 | 0.00620852 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 12.0592 | 71.99 | 0.00693317 | 40.6226 | 7974.65 | 0.00 | 11348.76 | 11348.76 |
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 11151.099 | 11151.099 | -999. | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11151.10 | 11151.10 | 373.117972 | 63.63 | 52.78 | 0.00620852 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 12.0592 | 71.99 | 0.00693317 | 40.6226 | 7974.65 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 5899.613 | 4393.603 | 168.374148 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 5786.09 | 4155.32 | 168.374148 | 77.45 | 64.53 | 0.01034585 | 53.60 | 51.86 | 0.00800000 | 79.70 | 0.01336023 | 69.30 | 26.7232 | 75.00 | 0.00924848 | 48.8050 | 3854.49 | 0.00 | 5898.60 | 4338.85 |
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 5899.613 | 5899.613 | 168.374148 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5899.61 | 5899.61 | 168.374148 | 53.47 | 46.39 | 0.00521803 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 26.7232 | 72.00 | 0.00678398 | 39.7569 | 5711.40 | 0.00 | 5907.37 | 5907.37 |
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 8920.853 | 8920.853 | -999. | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 8920.85 | 8920.85 | 168.374148 | 53.47 | 46.39 | 0.00521803 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 26.7232 | 72.00 | 0.00678398 | 39.7569 | 5711.40 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 8715.847 | 6927.605 | 283.520193 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 8707.56 | 7047.82 | 283.520193 | 76.94 | 62.96 | 0.00938132 | 53.60 | 51.86 | 0.00800000 | 79.70 | 0.01336023 | 69.30 | 15.8701 | 75.00 | 0.00862466 | 45.5574 | 6479.81 | 0.00 | 8714.35 | 6830.51 |
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 8715.847 | 8715.847 | 283.520193 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 8715.85 | 8715.85 | 283.520193 | 60.99 | 51.24 | 0.00597795 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 15.8701 | 71.99 | 0.00693130 | 40.6118 | 7957.47 | 0.00 | 8727.30 | 8727.30 |
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 11134.171 | 11134.171 | -999. | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11134.17 | 11134.17 | 283.520193 | 60.99 | 51.24 | 0.00597795 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 15.8701 | 71.99 | 0.00693130 | 40.6118 | 7957.47 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 11427.287 | 9146.927 | 384.100083 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 11581.77 | 9847.58 | 384.100083 | 77.11 | 62.51 | 0.00903946 | 53.60 | 51.86 | 0.00800000 | 82.80 | 0.01336327 | 70.21 | 11.7144 | 75.00 | 0.00846574 | 44.7291 | 8804.66 | 0.00 | 11425.33 | 9019.88 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 11427.287 | 11427.287 | 384.100083 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11427.29 | 11427.29 | 384.100083 | 63.88 | 53.80 | 0.00672286 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 11.7144 | 72.00 | 0.00749228 | 43.8546 | 5455.35 | 0.00 | 11442.30 | 11442.30 |
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 8668.660 | 8668.660 | -999. | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 8668.66 | 8668.66 | 384.100083 | 63.88 | 53.80 | 0.00672286 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 11.7144 | 72.00 | 0.00749228 | 43.8546 | 5455.35 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 5921.750 | 4476.642 | 174.587815 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5840.21 | 4350.69 | 174.587815 | 77.49 | 64.12 | 0.01004911 | 53.60 | 51.86 | 0.00800000 | 80.01 | 0.01336053 | 69.39 | 25.7721 | 75.00 | 0.00859612 | 45.4087 | 3882.21 | 0.00 | 5920.73 | 4417.71 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 5921.750 | 5921.750 | 174.587815 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5921.75 | 5921.75 | 174.587815 | 54.13 | 48.03 | 0.00587719 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 25.7721 | 72.00 | 0.00759692 | 44.4583 | 3211.36 | 0.00 | 5929.53 | 5929.53 |
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 6457.395 | 6457.395 | -999. | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6457.40 | 6457.40 | 174.587815 | 54.13 | 48.03 | 0.00587719 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 25.7721 | 72.00 | 0.00759692 | 44.4583 | 3211.36 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 9182.434 | 7353.586 | 304.322047 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | 9257.96 | 7761.76 | 304.322047 | 77.21 | 62.70 | 0.00914203 | 53.60 | 51.86 | 0.00800000 | 81.85 | 0.01336234 | 69.93 | 14.7853 | 75.00 | 0.00840777 | 44.4264 | 6971.08 | 0.00 | 9180.86 | 7250.12 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 9182.434 | 9182.434 | 304.322047 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 9182.43 | 9182.43 | 304.322047 | 61.75 | 52.56 | 0.00651997 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 14.7853 | 72.00 | 0.00749089 | 43.8465 | 5437.63 | 0.00 | 9194.50 | 9194.50 |
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 8651.191 | 8651.191 | -999. | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 8651.19 | 8651.19 | 304.322047 | 61.75 | 52.56 | 0.00651997 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 14.7853 | 72.00 | 0.00749089 | 43.8465 | 5437.63 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 10990.197 | 8794.377 | 368.013384 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 11105.97 | 9369.62 | 368.013384 | 77.07 | 62.58 | 0.00909199 | 53.60 | 51.86 | 0.00800000 | 82.10 | 0.01336259 | 70.01 | 12.2265 | 75.00 | 0.00849712 | 44.8927 | 8435.87 | 0.00 | 10988.31 | 8671.41 |
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 10990.197 | 10990.197 | 368.013384 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 10990.20 | 10990.20 | 368.013384 | 63.52 | 53.60 | 0.00668935 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 12.2265 | 72.00 | 0.00749243 | 43.8554 | 5457.24 | 0.00 | 11004.64 | 11004.64 |
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 8670.521 | 8670.521 | -999. | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 8670.52 | 8670.52 | 368.013384 | 63.52 | 53.60 | 0.00668935 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 12.2265 | 72.00 | 0.00749243 | 43.8554 | 5457.24 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 5739.279 | 4329.401 | 168.259288 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 5646.51 | 4157.76 | 168.259288 | 77.37 | 64.20 | 0.01013396 | 53.60 | 51.86 | 0.00800000 | 79.40 | 0.01335992 | 69.21 | 26.7415 | 75.00 | 0.00896273 | 47.3178 | 3856.03 | 0.00 | 5738.29 | 4273.04 |
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 5739.279 | 5739.279 | 168.259288 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5739.28 | 5739.28 | 168.259288 | 53.46 | 47.59 | 0.00581251 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 26.7415 | 72.00 | 0.00759692 | 44.4583 | 3211.37 | 0.00 | 5746.82 | 5746.82 |
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 6457.402 | 6457.402 | -999. | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6457.40 | 6457.40 | 168.259288 | 53.46 | 47.59 | 0.00581251 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 26.7415 | 72.00 | 0.00759692 | 44.4583 | 3211.37 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 8657.614 | 6927.922 | 286.380615 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 8691.51 | 7210.50 | 286.380615 | 77.08 | 62.76 | 0.00921080 | 53.60 | 51.86 | 0.00800000 | 80.60 | 0.01336110 | 69.56 | 15.7116 | 75.00 | 0.00843312 | 44.5586 | 6550.07 | 0.00 | 8656.13 | 6831.49 |
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 8657.614 | 8657.614 | 286.380615 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 8657.61 | 8657.61 | 286.380615 | 61.10 | 52.18 | 0.00645902 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 15.7116 | 72.00 | 0.00749074 | 43.8457 | 5435.75 | 0.00 | 8668.99 | 8668.99 |
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 8649.346 | 8649.346 | -999. | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 8649.35 | 8649.35 | 286.380615 | 61.10 | 52.18 | 0.00645902 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 15.7116 | 72.00 | 0.00749074 | 43.8457 | 5435.75 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 11897.167 | 9525.578 | 395.297519 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 12027.51 | 10074.38 | 395.297519 | 77.05 | 62.65 | 0.00914185 | 53.60 | 51.86 | 0.00800000 | 82.52 | 0.01336300 | 70.13 | 11.3826 | 75.00 | 0.00859319 | 45.3940 | 9056.53 | 0.00 | 11895.13 | 9390.30 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 11897.167 | 11897.167 | 395.297519 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11897.17 | 11897.17 | 395.297519 | 64.10 | 53.02 | 0.00623844 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 11.3826 | 71.99 | 0.00692104 | 40.5524 | 7868.62 | 0.00 | 11912.80 | 11912.80 |
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 11046.613 | 11046.613 | -999. | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11046.61 | 11046.61 | 395.297519 | 64.10 | 53.02 | 0.00623844 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 11.3826 | 71.99 | 0.00692104 | 40.5524 | 7868.62 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 6463.498 | 4877.102 | 189.633103 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6370.23 | 4703.77 | 189.633103 | 77.38 | 64.17 | 0.01011241 | 53.60 | 51.86 | 0.00800000 | 80.01 | 0.01336053 | 69.39 | 23.7274 | 75.00 | 0.00885404 | 46.7531 | 4098.16 | 0.00 | 6462.39 | 4813.73 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 6463.498 | 6463.498 | 189.633103 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6463.50 | 6463.50 | 189.633103 | 55.54 | 47.68 | 0.00538059 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 23.7274 | 72.00 | 0.00676695 | 39.6582 | 5613.27 | 0.00 | 6471.99 | 6471.99 |
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 8824.154 | 8824.154 | -999. | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 8824.15 | 8824.15 | 189.633103 | 55.54 | 47.68 | 0.00538059 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 23.7274 | 72.00 | 0.00676695 | 39.6582 | 5613.27 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 9388.515 | 7460.859 | 305.258551 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | 9441.28 | 7758.58 | 305.258551 | 77.21 | 62.91 | 0.00928472 | 53.60 | 51.86 | 0.00800000 | 81.85 | 0.01336234 | 69.93 | 14.7400 | 75.00 | 0.00857804 | 45.3144 | 6974.17 | 0.00 | 9386.90 | 7356.18 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 9388.515 | 9388.515 | 305.258551 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 9388.52 | 9388.52 | 305.258551 | 61.77 | 51.68 | 0.00603515 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 14.7400 | 71.99 | 0.00691876 | 40.5391 | 7848.07 | 0.00 | 9400.85 | 9400.85 |
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 11026.369 | 11026.369 | -999. | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11026.37 | 11026.37 | 305.258551 | 61.77 | 51.68 | 0.00603515 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 14.7400 | 71.99 | 0.00691876 | 40.5391 | 7848.07 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 11707.462 | 9370.258 | 388.644337 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 11817.22 | 9863.76 | 388.644337 | 77.02 | 62.67 | 0.00916495 | 53.60 | 51.86 | 0.00800000 | 82.10 | 0.01336259 | 70.01 | 11.5774 | 75.00 | 0.00861534 | 45.5095 | 8908.60 | 0.00 | 11705.45 | 9236.97 |
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 11707.462 | 11707.462 | 388.644337 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11707.46 | 11707.46 | 388.644337 | 63.97 | 52.95 | 0.00622688 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 11.5774 | 71.99 | 0.00692119 | 40.5532 | 7869.93 | 0.00 | 11722.85 | 11722.85 |
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 11047.908 | 11047.908 | -999. | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11047.91 | 11047.91 | 388.644337 | 63.97 | 52.95 | 0.00622688 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 11.5774 | 71.99 | 0.00692119 | 40.5532 | 7869.93 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 6480.361 | 4899.904 | 191.156138 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 6381.54 | 4705.92 | 191.156138 | 77.23 | 64.12 | 0.01011100 | 53.60 | 51.86 | 0.00800000 | 79.40 | 0.01335992 | 69.21 | 23.5383 | 75.00 | 0.00912051 | 48.1394 | 4380.45 | 0.00 | 6479.25 | 4835.48 |
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 6480.361 | 6480.361 | 191.156138 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6480.36 | 6480.36 | 191.156138 | 55.68 | 47.76 | 0.00539164 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 23.5383 | 72.00 | 0.00676695 | 39.6582 | 5613.27 | 0.00 | 6488.88 | 6488.88 |
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 8824.155 | 8824.155 | -999. | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 8824.15 | 8824.15 | 191.156138 | 55.68 | 47.76 | 0.00539164 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 23.5383 | 72.00 | 0.00676695 | 39.6582 | 5613.27 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 8880.053 | 7051.693 | 288.205889 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 8892.28 | 7231.22 | 288.205889 | 77.07 | 62.97 | 0.00935380 | 53.60 | 51.86 | 0.00800000 | 80.60 | 0.01336110 | 69.56 | 15.6121 | 75.00 | 0.00860891 | 45.4753 | 6596.65 | 0.00 | 8878.53 | 6952.36 |
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 8880.053 | 8880.053 | 288.205889 | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 8880.05 | 8880.05 | 288.205889 | 61.17 | 51.32 | 0.00598274 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 15.6121 | 71.99 | 0.00691861 | 40.5383 | 7846.76 | 0.00 | 8891.72 | 8891.72 |
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 11025.075 | 11025.075 | -999. | -999. | -999.00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11025.07 | 11025.07 | 288.205889 | 61.17 | 51.32 | 0.00598274 | 122.00 | 74.60 | 0.00800000 | 2.66 | 0.00092409 | 2.66 | 15.6121 | 71.99 | 0.00691861 | 40.5383 | 7846.76 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3578.885 | 3510.886 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3552.792 | 3485.289 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3579.329 | 3511.322 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3578.973 | 3510.973 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3552.318 | 3484.824 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3579.398 | 3511.390 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3647.117 | 3577.822 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3660.395 | 3590.847 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3648.270 | 3578.953 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3647.351 | 3578.052 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3657.160 | 3587.674 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3648.524 | 3579.202 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3578.812 | 3510.815 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3554.364 | 3486.831 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3579.266 | 3511.260 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3578.849 | 3510.851 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3554.456 | 3486.922 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3579.339 | 3511.332 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [Btu/lbm-R] | Dry Air Heat Capacity [Btu/lbm-R] | Standard Air Density Adjusted for Elevation [lb/ft3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [ft3/min] | Supply Fan Maximum Air Mass Flow Rate [lb/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [Btu/lbm-R] | Plant Fluid Density [lb/ft3] | Plant Maximum Fluid Mass Flow Rate [lb/s] | Plant Design Fluid Return Temperature [F] | Plant Design Fluid Supply Temperature [F] | Plant Design Fluid Temperature Difference [deltaF] | Plant Design Capacity [Btu/h] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] | Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] | Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] | Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [F] | System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | Coil Air Mass Flow Rate at Rating Conditions [lb/s] | Coil Entering Air Drybulb at Rating Conditions [F] | Coil Entering Air Wetbulb at Rating Conditions [F] | Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] | Coil Leaving Air Drybulb at Rating Conditions [F] | Coil Leaving Air Wetbulb at Rating Conditions [F] | Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11755.140 | 9411.015 | 389.292677 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2441 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 389.292677 | 0.47554165 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | Sensible | 11890.18 | 9950.61 | 0.9886 | 0.47554165 | 389.292677 | 77.10 | 62.67 | 0.00914998 | 11.6 | 53.60 | 51.86 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 501.012 | 11389.17 | 82.80 | 0.01336327 | 70.21 | 44.99498340 | 11.5581 | 75.00 | 0.00859936 | 75.00 | 0.00858987 | 45.3766 | 8923.32 | 0.00 | 11753.12 | 9280.34 | 0.45676135 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.90 | 56.82 | 0.00981318 | 9.2 | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 11755.140 | 11755.140 | 389.292677 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 389.292677 | 0.47554165 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11755.14 | 11755.14 | 1.0000 | 0.47554165 | 389.292677 | 63.98 | 52.97 | 0.00623842 | 8.0 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11755.14 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 11.5581 | 71.99 | 0.00693293 | 71.99 | 0.00693293 | 40.6213 | 7972.48 | 0.00 | 11770.59 | 11770.59 | 0.46713868 | 70.00 | 60.00 | 0.00875166 | 10.4 | 98.70 | 69.53 | 0.00875166 | 14.3 | |
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11148.963 | 11148.963 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 389.292677 | 0.47554165 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11148.96 | 11148.96 | 1.0000 | 0.47554165 | 389.292677 | 63.98 | 52.97 | 0.00623842 | 8.0 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11148.96 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 11.5581 | 71.99 | 0.00693293 | 71.99 | 0.00693293 | 40.6213 | 7972.48 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6017.581 | 4493.327 | 172.951945 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2446 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 172.951945 | 0.21126997 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5912.68 | 4288.61 | 1.0177 | 0.21126997 | 172.951945 | 77.50 | 64.43 | 0.01026751 | 12.3 | 53.60 | 51.86 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 222.586 | 5690.09 | 80.01 | 0.01336053 | 69.39 | 44.99498340 | 26.0159 | 75.00 | 0.00917987 | 75.00 | 0.00889802 | 46.9822 | 3890.08 | 0.00 | 6016.55 | 4435.55 | 0.20292641 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.12 | 55.08 | 0.00921094 | 8.6 | |
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 6017.581 | 6017.581 | 172.951945 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 172.951945 | 0.21126997 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 6017.58 | 6017.58 | 1.0000 | 0.21126997 | 172.951945 | 53.96 | 46.70 | 0.00525948 | 6.1 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6017.58 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 26.0159 | 72.00 | 0.00678398 | 72.00 | 0.00678398 | 39.7569 | 5711.40 | 0.00 | 6025.49 | 6025.49 | 0.20753677 | 70.00 | 60.00 | 0.00875166 | 10.4 | 103.07 | 70.82 | 0.00875166 | 14.9 | |
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8920.852 | 8920.852 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 172.951945 | 0.21126997 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 8920.85 | 8920.85 | 1.0000 | 0.21126997 | 172.951945 | 53.96 | 46.70 | 0.00525948 | 6.1 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8920.85 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 26.0159 | 72.00 | 0.00678398 | 72.00 | 0.00678398 | 39.7569 | 5711.40 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9224.071 | 7329.383 | 299.830602 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2441 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 299.830602 | 0.36625898 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | Sensible | 9262.92 | 7588.09 | 0.9958 | 0.36625898 | 299.830602 | 77.16 | 62.93 | 0.00930529 | 11.7 | 53.60 | 51.86 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 385.876 | 8877.04 | 81.43 | 0.01336193 | 69.81 | 44.99498340 | 15.0068 | 75.00 | 0.00858903 | 75.00 | 0.00858709 | 45.3616 | 6864.47 | 0.00 | 9222.49 | 7226.49 | 0.35179452 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.65 | 56.61 | 0.00974730 | 9.2 | |
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 9224.071 | 9224.071 | 299.830602 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 299.830602 | 0.36625898 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 9224.07 | 9224.07 | 1.0000 | 0.36625898 | 299.830602 | 61.59 | 51.59 | 0.00603001 | 7.6 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 9224.07 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 15.0068 | 71.99 | 0.00693154 | 71.99 | 0.00693154 | 40.6132 | 7959.63 | 0.00 | 9236.19 | 9236.19 | 0.35978707 | 70.00 | 60.00 | 0.00875166 | 10.4 | 99.24 | 69.69 | 0.00875166 | 14.3 | |
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11136.303 | 11136.303 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 299.830602 | 0.36625898 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11136.30 | 11136.30 | 1.0000 | 0.36625898 | 299.830602 | 61.59 | 51.59 | 0.00603001 | 7.6 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11136.30 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 15.0068 | 71.99 | 0.00693154 | 71.99 | 0.00693154 | 40.6132 | 7959.63 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11333.870 | 9074.625 | 373.117972 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2441 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 373.117972 | 0.45578339 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | Sensible | 11443.48 | 9511.05 | 0.9904 | 0.45578339 | 373.117972 | 77.10 | 62.75 | 0.00919894 | 11.6 | 53.60 | 51.86 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 480.196 | 10963.28 | 82.52 | 0.01336300 | 70.13 | 44.99498340 | 12.0592 | 75.00 | 0.00862793 | 75.00 | 0.00862793 | 45.5750 | 8552.72 | 0.00 | 11331.93 | 8946.97 | 0.43778339 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.77 | 56.75 | 0.00980455 | 9.2 | |
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 11333.870 | 11333.870 | 373.117972 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 373.117972 | 0.45578339 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11333.87 | 11333.87 | 1.0000 | 0.45578339 | 373.117972 | 63.63 | 52.78 | 0.00620852 | 8.0 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11333.87 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 12.0592 | 71.99 | 0.00693317 | 71.99 | 0.00693317 | 40.6226 | 7974.65 | 0.00 | 11348.76 | 11348.76 | 0.44772955 | 70.00 | 60.00 | 0.00875166 | 10.4 | 98.87 | 69.58 | 0.00875166 | 14.3 | |
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11151.099 | 11151.099 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 373.117972 | 0.45578339 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11151.10 | 11151.10 | 1.0000 | 0.45578339 | 373.117972 | 63.63 | 52.78 | 0.00620852 | 8.0 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11151.10 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 12.0592 | 71.99 | 0.00693317 | 71.99 | 0.00693317 | 40.6226 | 7974.65 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5899.613 | 4393.603 | 168.374148 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2446 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 168.374148 | 0.20567795 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 5786.09 | 4155.32 | 1.0196 | 0.20567795 | 168.374148 | 77.45 | 64.53 | 0.01034585 | 12.4 | 53.60 | 51.86 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 216.694 | 5569.40 | 79.70 | 0.01336023 | 69.30 | 44.99498340 | 26.7232 | 75.00 | 0.00924654 | 75.00 | 0.00924848 | 48.8050 | 3854.49 | 0.00 | 5898.60 | 4338.85 | 0.19755523 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.00 | 54.98 | 0.00918453 | 8.6 | |
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 5899.613 | 5899.613 | 168.374148 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 168.374148 | 0.20567795 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 5899.61 | 5899.61 | 1.0000 | 0.20567795 | 168.374148 | 53.47 | 46.39 | 0.00521803 | 6.0 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5899.61 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 26.7232 | 72.00 | 0.00678398 | 72.00 | 0.00678398 | 39.7569 | 5711.40 | 0.00 | 5907.37 | 5907.37 | 0.20204356 | 70.00 | 60.00 | 0.00875166 | 10.4 | 103.30 | 70.89 | 0.00875166 | 14.9 | |
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8920.853 | 8920.853 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 168.374148 | 0.20567795 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 8920.85 | 8920.85 | 1.0000 | 0.20567795 | 168.374148 | 53.47 | 46.39 | 0.00521803 | 6.0 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8920.85 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 26.7232 | 72.00 | 0.00678398 | 72.00 | 0.00678398 | 39.7569 | 5711.40 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8715.847 | 6927.605 | 283.520193 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2442 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 283.520193 | 0.34633495 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | Sensible | 8707.56 | 7047.82 | 1.0010 | 0.34633495 | 283.520193 | 76.94 | 62.96 | 0.00938132 | 11.7 | 53.60 | 51.86 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 364.885 | 8342.68 | 79.70 | 0.01336023 | 69.30 | 44.99498340 | 15.8701 | 75.00 | 0.00863075 | 75.00 | 0.00862466 | 45.5574 | 6479.81 | 0.00 | 8714.35 | 6830.51 | 0.33265734 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.66 | 56.62 | 0.00975003 | 9.2 | |
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 8715.847 | 8715.847 | 283.520193 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 283.520193 | 0.34633495 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 8715.85 | 8715.85 | 1.0000 | 0.34633495 | 283.520193 | 60.99 | 51.24 | 0.00597795 | 7.5 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8715.85 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 15.8701 | 71.99 | 0.00693130 | 71.99 | 0.00693130 | 40.6118 | 7957.47 | 0.00 | 8727.30 | 8727.30 | 0.34021510 | 70.00 | 60.00 | 0.00875166 | 10.4 | 99.22 | 69.68 | 0.00875166 | 14.3 | |
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11134.171 | 11134.171 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 283.520193 | 0.34633495 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11134.17 | 11134.17 | 1.0000 | 0.34633495 | 283.520193 | 60.99 | 51.24 | 0.00597795 | 7.5 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11134.17 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 15.8701 | 71.99 | 0.00693130 | 71.99 | 0.00693130 | 40.6118 | 7957.47 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11427.287 | 9146.927 | 384.100083 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2440 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 384.100083 | 0.46919862 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | Sensible | 11581.77 | 9847.58 | 0.9867 | 0.46919862 | 384.100083 | 77.11 | 62.51 | 0.00903946 | 11.5 | 53.60 | 51.86 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 494.330 | 11087.44 | 82.80 | 0.01336327 | 70.21 | 44.99498340 | 11.7144 | 75.00 | 0.00846574 | 75.00 | 0.00846574 | 44.7291 | 8804.66 | 0.00 | 11425.33 | 9019.88 | 0.45066882 | 80.00 | 67.00 | 0.01118466 | 13.2 | 57.25 | 56.99 | 0.00983249 | 9.3 | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 11427.287 | 11427.287 | 384.100083 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 384.100083 | 0.46919862 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11427.29 | 11427.29 | 1.0000 | 0.46919862 | 384.100083 | 63.88 | 53.80 | 0.00672286 | 8.3 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11427.29 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 11.7144 | 72.00 | 0.00749228 | 72.00 | 0.00749228 | 43.8546 | 5455.35 | 0.00 | 11442.30 | 11442.30 | 0.46090773 | 70.00 | 60.00 | 0.00875166 | 10.4 | 98.28 | 69.40 | 0.00875166 | 14.2 | |
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8668.660 | 8668.660 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 384.100083 | 0.46919862 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 8668.66 | 8668.66 | 1.0000 | 0.46919862 | 384.100083 | 63.88 | 53.80 | 0.00672286 | 8.3 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8668.66 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 11.7144 | 72.00 | 0.00749228 | 72.00 | 0.00749228 | 43.8546 | 5455.35 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5921.750 | 4476.642 | 174.587815 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2445 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 174.587815 | 0.21326827 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5840.21 | 4350.69 | 1.0140 | 0.21326827 | 174.587815 | 77.49 | 64.12 | 0.01004911 | 12.2 | 53.60 | 51.86 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 224.691 | 5615.52 | 80.01 | 0.01336053 | 69.39 | 44.99498340 | 25.7721 | 75.00 | 0.00889938 | 75.00 | 0.00859612 | 45.4087 | 3882.21 | 0.00 | 5920.73 | 4417.71 | 0.20484579 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.46 | 55.41 | 0.00932586 | 8.8 | |
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 5921.750 | 5921.750 | 174.587815 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 174.587815 | 0.21326827 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 5921.75 | 5921.75 | 1.0000 | 0.21326827 | 174.587815 | 54.13 | 48.03 | 0.00587719 | 6.5 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5921.75 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 25.7721 | 72.00 | 0.00759692 | 72.00 | 0.00759692 | 44.4583 | 3211.36 | 0.00 | 5929.53 | 5929.53 | 0.20949976 | 70.00 | 60.00 | 0.00875166 | 10.4 | 102.24 | 70.58 | 0.00875166 | 14.7 | |
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6457.395 | 6457.395 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 174.587815 | 0.21326827 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 6457.40 | 6457.40 | 1.0000 | 0.21326827 | 174.587815 | 54.13 | 48.03 | 0.00587719 | 6.5 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6457.40 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 25.7721 | 72.00 | 0.00759692 | 72.00 | 0.00759692 | 44.4583 | 3211.36 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9182.434 | 7353.586 | 304.322047 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2441 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 304.322047 | 0.37174552 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | Sensible | 9257.96 | 7761.76 | 0.9918 | 0.37174552 | 304.322047 | 77.21 | 62.70 | 0.00914203 | 11.6 | 53.60 | 51.86 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 391.657 | 8866.31 | 81.85 | 0.01336234 | 69.93 | 44.99498340 | 14.7853 | 75.00 | 0.00840977 | 75.00 | 0.00840777 | 44.4264 | 6971.08 | 0.00 | 9180.86 | 7250.12 | 0.35706438 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.92 | 56.83 | 0.00981482 | 9.2 | |
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 9182.434 | 9182.434 | 304.322047 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 304.322047 | 0.37174552 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 9182.43 | 9182.43 | 1.0000 | 0.37174552 | 304.322047 | 61.75 | 52.56 | 0.00651997 | 7.9 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 9182.43 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 14.7853 | 72.00 | 0.00749089 | 72.00 | 0.00749089 | 43.8465 | 5437.63 | 0.00 | 9194.50 | 9194.50 | 0.36517666 | 70.00 | 60.00 | 0.00875166 | 10.4 | 98.68 | 69.52 | 0.00875166 | 14.3 | |
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8651.191 | 8651.191 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 304.322047 | 0.37174552 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 8651.19 | 8651.19 | 1.0000 | 0.37174552 | 304.322047 | 61.75 | 52.56 | 0.00651997 | 7.9 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8651.19 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 14.7853 | 72.00 | 0.00749089 | 72.00 | 0.00749089 | 43.8465 | 5437.63 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10990.197 | 8794.377 | 368.013384 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2440 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 368.013384 | 0.44954786 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | Sensible | 11105.97 | 9369.62 | 0.9896 | 0.44954786 | 368.013384 | 77.07 | 62.58 | 0.00909199 | 11.5 | 53.60 | 51.86 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 473.626 | 10632.34 | 82.10 | 0.01336259 | 70.01 | 44.99498340 | 12.2265 | 75.00 | 0.00849712 | 75.00 | 0.00849712 | 44.8927 | 8435.87 | 0.00 | 10988.31 | 8671.41 | 0.43179412 | 80.00 | 67.00 | 0.01118466 | 13.2 | 57.17 | 56.94 | 0.00982534 | 9.3 | |
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 10990.197 | 10990.197 | 368.013384 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 368.013384 | 0.44954786 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 10990.20 | 10990.20 | 1.0000 | 0.44954786 | 368.013384 | 63.52 | 53.60 | 0.00668935 | 8.3 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 10990.20 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 12.2265 | 72.00 | 0.00749243 | 72.00 | 0.00749243 | 43.8554 | 5457.24 | 0.00 | 11004.64 | 11004.64 | 0.44160421 | 70.00 | 60.00 | 0.00875166 | 10.4 | 98.38 | 69.43 | 0.00875166 | 14.2 | |
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8670.521 | 8670.521 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 368.013384 | 0.44954786 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 8670.52 | 8670.52 | 1.0000 | 0.44954786 | 368.013384 | 63.52 | 53.60 | 0.00668935 | 8.3 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8670.52 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 12.2265 | 72.00 | 0.00749243 | 72.00 | 0.00749243 | 43.8554 | 5457.24 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5739.279 | 4329.401 | 168.259288 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2445 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 168.259288 | 0.20553764 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 5646.51 | 4157.76 | 1.0164 | 0.20553764 | 168.259288 | 77.37 | 64.20 | 0.01013396 | 12.2 | 53.60 | 51.86 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 216.547 | 5429.97 | 79.40 | 0.01335992 | 69.21 | 44.99498340 | 26.7415 | 75.00 | 0.00895640 | 75.00 | 0.00896273 | 47.3178 | 3856.03 | 0.00 | 5738.29 | 4273.04 | 0.19742046 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.37 | 55.34 | 0.00930442 | 8.7 | |
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 5739.279 | 5739.279 | 168.259288 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 168.259288 | 0.20553764 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 5739.28 | 5739.28 | 1.0000 | 0.20553764 | 168.259288 | 53.46 | 47.59 | 0.00581251 | 6.4 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5739.28 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 26.7415 | 72.00 | 0.00759692 | 72.00 | 0.00759692 | 44.4583 | 3211.37 | 0.00 | 5746.82 | 5746.82 | 0.20190573 | 70.00 | 60.00 | 0.00875166 | 10.4 | 102.42 | 70.63 | 0.00875166 | 14.8 | |
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6457.402 | 6457.402 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 168.259288 | 0.20553764 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 6457.40 | 6457.40 | 1.0000 | 0.20553764 | 168.259288 | 53.46 | 47.59 | 0.00581251 | 6.4 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6457.40 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 26.7415 | 72.00 | 0.00759692 | 72.00 | 0.00759692 | 44.4583 | 3211.37 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8657.614 | 6927.922 | 286.380615 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2441 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 286.380615 | 0.34982911 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | Sensible | 8691.51 | 7210.50 | 0.9961 | 0.34982911 | 286.380615 | 77.08 | 62.76 | 0.00921080 | 11.6 | 53.60 | 51.86 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 368.567 | 8322.94 | 80.60 | 0.01336110 | 69.56 | 44.99498340 | 15.7116 | 75.00 | 0.00843717 | 75.00 | 0.00843312 | 44.5586 | 6550.07 | 0.00 | 8656.13 | 6831.49 | 0.33601350 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.89 | 56.81 | 0.00980900 | 9.2 | |
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 8657.614 | 8657.614 | 286.380615 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 286.380615 | 0.34982911 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 8657.61 | 8657.61 | 1.0000 | 0.34982911 | 286.380615 | 61.10 | 52.18 | 0.00645902 | 7.8 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8657.61 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 15.7116 | 72.00 | 0.00749074 | 72.00 | 0.00749074 | 43.8457 | 5435.75 | 0.00 | 8668.99 | 8668.99 | 0.34364752 | 70.00 | 60.00 | 0.00875166 | 10.4 | 98.73 | 69.54 | 0.00875166 | 14.3 | |
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8649.346 | 8649.346 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 286.380615 | 0.34982911 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 8649.35 | 8649.35 | 1.0000 | 0.34982911 | 286.380615 | 61.10 | 52.18 | 0.00645902 | 7.8 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8649.35 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 15.7116 | 72.00 | 0.00749074 | 72.00 | 0.00749074 | 43.8457 | 5435.75 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11897.167 | 9525.578 | 395.297519 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2441 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 395.297519 | 0.48287688 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | Sensible | 12027.51 | 10074.38 | 0.9892 | 0.48287688 | 395.297519 | 77.05 | 62.65 | 0.00914185 | 11.6 | 53.60 | 51.86 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 508.741 | 11518.77 | 82.52 | 0.01336300 | 70.13 | 44.99498340 | 11.3826 | 75.00 | 0.00859966 | 75.00 | 0.00859319 | 45.3940 | 9056.53 | 0.00 | 11895.13 | 9390.30 | 0.46380689 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.98 | 56.86 | 0.00981652 | 9.3 | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 11897.167 | 11897.167 | 395.297519 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 395.297519 | 0.48287688 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11897.17 | 11897.17 | 1.0000 | 0.48287688 | 395.297519 | 64.10 | 53.02 | 0.00623844 | 8.1 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11897.17 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 11.3826 | 71.99 | 0.00692104 | 71.99 | 0.00692104 | 40.5524 | 7868.62 | 0.00 | 11912.80 | 11912.80 | 0.47434430 | 70.00 | 60.00 | 0.00875166 | 10.4 | 98.60 | 69.50 | 0.00875166 | 14.3 | |
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11046.613 | 11046.613 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 395.297519 | 0.48287688 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11046.61 | 11046.61 | 1.0000 | 0.48287688 | 395.297519 | 64.10 | 53.02 | 0.00623844 | 8.1 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11046.61 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 11.3826 | 71.99 | 0.00692104 | 71.99 | 0.00692104 | 40.5524 | 7868.62 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6463.498 | 4877.102 | 189.633103 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2445 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 189.633103 | 0.23164689 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6370.23 | 4703.77 | 1.0146 | 0.23164689 | 189.633103 | 77.38 | 64.17 | 0.01011241 | 12.2 | 53.60 | 51.86 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 244.054 | 6126.17 | 80.01 | 0.01336053 | 69.39 | 44.99498340 | 23.7274 | 75.00 | 0.00910197 | 75.00 | 0.00885404 | 46.7531 | 4098.16 | 0.00 | 6462.39 | 4813.73 | 0.22249859 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.38 | 55.35 | 0.00930752 | 8.7 | |
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 6463.498 | 6463.498 | 189.633103 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 189.633103 | 0.23164689 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 6463.50 | 6463.50 | 1.0000 | 0.23164689 | 189.633103 | 55.54 | 47.68 | 0.00538059 | 6.4 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6463.50 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 23.7274 | 72.00 | 0.00676695 | 72.00 | 0.00676695 | 39.6582 | 5613.27 | 0.00 | 6471.99 | 6471.99 | 0.22755362 | 70.00 | 60.00 | 0.00875166 | 10.4 | 102.39 | 70.63 | 0.00875166 | 14.8 | |
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8824.154 | 8824.154 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 189.633103 | 0.23164689 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 8824.15 | 8824.15 | 1.0000 | 0.23164689 | 189.633103 | 55.54 | 47.68 | 0.00538059 | 6.4 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8824.15 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 23.7274 | 72.00 | 0.00676695 | 72.00 | 0.00676695 | 39.6582 | 5613.27 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9388.515 | 7460.859 | 305.258551 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2441 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 305.258551 | 0.37288951 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | Sensible | 9441.28 | 7758.58 | 0.9944 | 0.37288951 | 305.258551 | 77.21 | 62.91 | 0.00928472 | 11.7 | 53.60 | 51.86 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 392.862 | 9048.42 | 81.85 | 0.01336234 | 69.93 | 44.99498340 | 14.7400 | 75.00 | 0.00857977 | 75.00 | 0.00857804 | 45.3144 | 6974.17 | 0.00 | 9386.90 | 7356.18 | 0.35816319 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.65 | 56.61 | 0.00974830 | 9.2 | |
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 9388.515 | 9388.515 | 305.258551 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 305.258551 | 0.37288951 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 9388.52 | 9388.52 | 1.0000 | 0.37288951 | 305.258551 | 61.77 | 51.68 | 0.00603515 | 7.6 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 9388.52 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 14.7400 | 71.99 | 0.00691876 | 71.99 | 0.00691876 | 40.5391 | 7848.07 | 0.00 | 9400.85 | 9400.85 | 0.36630043 | 70.00 | 60.00 | 0.00875166 | 10.4 | 99.23 | 69.69 | 0.00875166 | 14.3 | |
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11026.369 | 11026.369 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 305.258551 | 0.37288951 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11026.37 | 11026.37 | 1.0000 | 0.37288951 | 305.258551 | 61.77 | 51.68 | 0.00603515 | 7.6 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11026.37 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 14.7400 | 71.99 | 0.00691876 | 71.99 | 0.00691876 | 40.5391 | 7848.07 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11707.462 | 9370.258 | 388.644337 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2441 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 388.644337 | 0.47474967 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | Sensible | 11817.22 | 9863.76 | 0.9907 | 0.47474967 | 388.644337 | 77.02 | 62.67 | 0.00916495 | 11.6 | 53.60 | 51.86 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 500.178 | 11317.04 | 82.10 | 0.01336259 | 70.01 | 44.99498340 | 11.5774 | 75.00 | 0.00861534 | 75.00 | 0.00861534 | 45.5095 | 8908.60 | 0.00 | 11705.45 | 9236.97 | 0.45600064 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.97 | 56.85 | 0.00981328 | 9.3 | |
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 11707.462 | 11707.462 | 388.644337 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 388.644337 | 0.47474967 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11707.46 | 11707.46 | 1.0000 | 0.47474967 | 388.644337 | 63.97 | 52.95 | 0.00622688 | 8.0 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11707.46 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 11.5774 | 71.99 | 0.00692119 | 71.99 | 0.00692119 | 40.5532 | 7869.93 | 0.00 | 11722.85 | 11722.85 | 0.46636069 | 70.00 | 60.00 | 0.00875166 | 10.4 | 98.63 | 69.51 | 0.00875166 | 14.3 | |
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11047.908 | 11047.908 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 388.644337 | 0.47474967 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11047.91 | 11047.91 | 1.0000 | 0.47474967 | 388.644337 | 63.97 | 52.95 | 0.00622688 | 8.0 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11047.91 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 11.5774 | 71.99 | 0.00692119 | 71.99 | 0.00692119 | 40.5532 | 7869.93 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6480.361 | 4899.904 | 191.156138 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2445 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 191.156138 | 0.23350736 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 6381.54 | 4705.92 | 1.0155 | 0.23350736 | 191.156138 | 77.23 | 64.12 | 0.01011100 | 12.2 | 53.60 | 51.86 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 246.014 | 6135.53 | 79.40 | 0.01335992 | 69.21 | 44.99498340 | 23.5383 | 75.00 | 0.00911084 | 75.00 | 0.00912051 | 48.1394 | 4380.45 | 0.00 | 6479.25 | 4835.48 | 0.22428558 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.47 | 55.42 | 0.00932800 | 8.8 | |
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 6480.361 | 6480.361 | 191.156138 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 191.156138 | 0.23350736 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 6480.36 | 6480.36 | 1.0000 | 0.23350736 | 191.156138 | 55.68 | 47.76 | 0.00539164 | 6.4 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6480.36 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 23.5383 | 72.00 | 0.00676695 | 72.00 | 0.00676695 | 39.6582 | 5613.27 | 0.00 | 6488.88 | 6488.88 | 0.22938121 | 70.00 | 60.00 | 0.00875166 | 10.4 | 102.22 | 70.57 | 0.00875166 | 14.7 | |
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8824.155 | 8824.155 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 191.156138 | 0.23350736 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 8824.15 | 8824.15 | 1.0000 | 0.23350736 | 191.156138 | 55.68 | 47.76 | 0.00539164 | 6.4 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8824.15 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 23.5383 | 72.00 | 0.00676695 | 72.00 | 0.00676695 | 39.6582 | 5613.27 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8880.053 | 7051.693 | 288.205889 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2442 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 288.205889 | 0.35205878 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | Sensible | 8892.28 | 7231.22 | 0.9986 | 0.35205878 | 288.205889 | 77.07 | 62.97 | 0.00935380 | 11.7 | 53.60 | 51.86 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 370.916 | 8521.36 | 80.60 | 0.01336110 | 69.56 | 44.99498340 | 15.6121 | 75.00 | 0.00861243 | 75.00 | 0.00860891 | 45.4753 | 6596.65 | 0.00 | 8878.53 | 6952.36 | 0.33815512 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.62 | 56.59 | 0.00974164 | 9.2 | |
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 8880.053 | 8880.053 | 288.205889 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 288.205889 | 0.35205878 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 8880.05 | 8880.05 | 1.0000 | 0.35205878 | 288.205889 | 61.17 | 51.32 | 0.00598274 | 7.5 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8880.05 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 15.6121 | 71.99 | 0.00691861 | 71.99 | 0.00691861 | 40.5383 | 7846.76 | 0.00 | 8891.72 | 8891.72 | 0.34583779 | 70.00 | 60.00 | 0.00875166 | 10.4 | 99.28 | 69.70 | 0.00875166 | 14.3 | |
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11025.075 | 11025.075 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0733 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 288.205889 | 0.35205878 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11025.07 | 11025.07 | 1.0000 | 0.35205878 | 288.205889 | 61.17 | 51.32 | 0.00598274 | 7.5 | 122.00 | 74.60 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11025.07 | 2.66 | 0.00092409 | 2.66 | 44.99498340 | 15.6121 | 71.99 | 0.00691861 | 71.99 | 0.00691861 | 40.5383 | 7846.76 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3578.885 | 3510.886 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0733 | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.19546140 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3552.792 | 3485.289 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0733 | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.19546140 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3579.329 | 3511.322 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0733 | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.19546140 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3578.973 | 3510.973 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0733 | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.19546140 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3552.318 | 3484.824 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0733 | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.19546140 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3579.398 | 3511.390 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0733 | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.19546140 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3647.117 | 3577.822 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0733 | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.19546140 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3660.395 | 3590.847 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0733 | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.19546140 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3648.270 | 3578.953 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0733 | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.19546140 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3647.351 | 3578.052 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0733 | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.19546140 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3657.160 | 3587.674 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0733 | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.19546140 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3648.524 | 3579.202 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0733 | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.19546140 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3578.812 | 3510.815 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0733 | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.19546140 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3554.364 | 3486.831 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0733 | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.19546140 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3579.266 | 3511.260 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0733 | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.19546140 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3578.849 | 3510.851 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0733 | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.19546140 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3554.456 | 3486.922 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0733 | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.19546140 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3579.339 | 3511.332 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0733 | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.19546140 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. |
Report: System Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2207.50 | 6451.00 | 710.50 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1455.33 | 6609.00 | 327.17 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2234.17 | 6337.50 | 669.83 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2217.67 | 6726.33 | 910.67 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1374.67 | 6974.00 | 445.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2163.83 | 6604.00 | 826.33 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1998.67 | 6051.33 | 255.33 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1469.67 | 6100.00 | 82.83 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2055.33 | 5935.83 | 247.50 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1856.50 | 6327.50 | 310.83 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1264.00 | 6456.67 | 93.67 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1886.33 | 6219.33 | 285.83 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 2221.83 | 6321.00 | 629.67 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 2251.17 | 6117.50 | 511.17 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 2225.33 | 6256.17 | 552.17 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1408.17 | 6582.83 | 204.33 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1528.50 | 6319.83 | 169.83 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 2214.67 | 6456.83 | 699.67 |
CRAWLSPACE | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 2939.33 | 7368.67 | 1025.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8.00 | 0.00 | 8.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 48.17 | 0.50 | 48.17 | 0.50 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 7.83 | 0.00 | 7.83 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 6.50 | 0.00 | 6.50 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 88.67 | 0.00 | 88.67 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8.17 | 0.00 | 8.17 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 10.50 | 0.00 | 10.50 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 17.33 | 0.00 | 17.33 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 7.83 | 0.00 | 7.83 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 7.33 | 0.00 | 7.33 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 23.33 | 0.00 | 23.33 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 6.17 | 0.00 | 6.17 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 6.33 | 0.00 | 6.33 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8.83 | 0.00 | 8.83 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 7.50 | 0.00 | 7.50 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 17.00 | 0.00 | 17.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 17.50 | 0.00 | 17.50 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 6.50 | 0.00 | 6.50 | 0.00 |
CRAWLSPACE | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 200.67 | 0.50 | 200.67 | 0.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.269 | 0.146 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.269 | 0.129 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.269 | 0.146 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.269 | 0.146 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.269 | 0.129 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.269 | 0.146 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.064 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.047 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.064 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.064 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.047 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.064 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.146 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.146 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.146 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.129 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.129 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.146 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.258 | 0.001 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.258 | 0.001 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.258 | 0.001 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.258 | 0.001 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.258 | 0.001 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.258 | 0.001 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.258 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.258 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.258 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.258 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.258 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.258 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.258 | 0.001 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.258 | 0.001 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.258 | 0.001 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.258 | 0.001 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.258 | 0.001 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.258 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Zone Area [ft2] | Design Zone Outdoor Airflow - Voz [ft3/min] | Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
Total Facility | 24.79 | 36.00 | 183739.38 | 21609.96 | 0.0000 | 0.000 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3] | Total Ventilation [ft3] | Infiltration [ft3] | Total Ventilation and Infiltration [ft3] | Dynamic Target Ventilation - Voz-dyn [ft3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12953023.49 | 36738105.18 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 11404601.50 | 35189683.19 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12957790.11 | 36742871.79 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12943576.73 | 36728658.42 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 11393476.00 | 35178557.69 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12948362.79 | 36733444.48 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 5680810.02 | 29465891.71 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 4131389.06 | 27916470.75 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 5682610.60 | 29467692.29 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 5676192.21 | 29461273.90 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 4127060.01 | 27912141.70 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 5678055.65 | 29463137.34 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12963804.30 | 36748885.99 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12971411.98 | 36756493.67 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12966911.75 | 36751993.44 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 11409263.35 | 35194345.04 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 11417888.27 | 35202969.96 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12959179.17 | 36744260.86 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
Total Facility | 0.428131E+09 | 0.00 | 0.428131E+09 | 0.180265E+09 | 0.608397E+09 | 0.428131E+09 | 0.00 | 8808.00 | 0.00 | 0.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Infiltration [ft3/min] | Total Ventilation and Infiltration [ft3/min] | Dynamic Target Ventilation - Voz-dyn [ft3/min] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 24.5036 | 69.4986 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 21.5744 | 66.5694 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 24.5127 | 69.5076 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 24.4858 | 69.4808 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 21.5534 | 66.5484 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 24.4948 | 69.4898 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 10.7466 | 55.7415 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 7.8155 | 52.8105 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 10.7500 | 55.7450 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 10.7378 | 55.7328 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 7.8073 | 52.8023 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 10.7414 | 55.7363 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 24.5240 | 69.5190 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 24.5384 | 69.5334 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 24.5299 | 69.5249 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 21.5833 | 66.5782 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 21.5996 | 66.5946 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 24.5153 | 69.5103 | 44.9950 | 0.00 | 8808.00 | 0.00 |
Total Facility | 809.9097 | 0.0000 | 809.9097 | 341.0137 | 1150.9234 | 809.9097 | 0.00 | 8808.00 | 0.00 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [ft3/min] | Limits and Scheduled Limits [ft3/min] | Economizer [ft3/min] | Exhaust Flow [ft3/min] | Mixed Air Flow [ft3/min] | High Humidity [ft3/min] | Demand Controlled Ventilation [ft3/min] | Night Ventilation [ft3/min] | Demand Limiting [ft3/min] | Energy Management System [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 58 |
Floor | 29 | 4 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 60 | 60 |
Overhang | 30 | 30 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 18 |
Conditioned Zones | 18 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 2058 |
Defaulted Fields | 1808 |
Fields with Defaults | 7284 |
Autosized Fields | 396 |
Autosizable Fields | 684 |
Autocalculated Fields | 197 |
Autocalculatable Fields | 421 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 199014.08 | 7967.15 | 10-MAY-03:20 | 76854.07 | 06-FEB-20:00 |
Electricity:Building | 99140.61 | 6270.77 | 02-JAN-03:10 | 18720.91 | 01-JAN-18:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity | 11336.81 | 253.88 | 01-JAN-00:10 | 3692.78 | 01-JAN-19:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity | 11336.81 | 253.88 | 01-JAN-00:10 | 3692.78 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
InteriorEquipment:Electricity | 87803.80 | 5989.14 | 02-JAN-04:10 | 15388.75 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity | 2758.31 | 25.25 | 02-JAN-03:10 | 880.12 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:10 | 1639.04 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity | 1408.53 | 13.53 | 02-JAN-02:10 | 381.47 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:10 | 3196.73 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:10 | 3721.08 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:10 | 7929.96 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:10 | 526.17 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
Electricity:HVAC | 76936.50 | 289.29 | 12-MAR-13:10 | 56654.60 | 07-FEB-07:30 |
Cooling:Electricity | 7628.94 | 0.00 | 01-JAN-00:10 | 9121.59 | 19-JUL-15:30 |
General:Cooling:Electricity | 7628.94 | 0.00 | 01-JAN-00:10 | 9121.59 | 19-JUL-15:30 |
Heating:Electricity | 59412.97 | 0.00 | 12-MAR-13:10 | 54257.33 | 07-FEB-07:30 |
General:Heating:Electricity | 59412.97 | 0.00 | 12-MAR-13:10 | 54257.33 | 07-FEB-07:30 |
Electricity:Plant | 17428.26 | 149.40 | 01-JAN-00:10 | 9057.28 | 08-APR-18:30 |
WaterSystems:Electricity | 17428.26 | 149.40 | 01-JAN-00:10 | 9057.28 | 08-APR-18:30 |
Fans:Electricity | 9894.59 | 289.29 | 12-MAR-13:10 | 2418.85 | 02-JAN-06:30 |
General:Fans:Electricity | 7360.45 | 0.00 | 12-MAR-13:10 | 2129.56 | 02-JAN-06:30 |
Ventilation:Fans:Electricity | 2534.14 | 289.29 | 01-JAN-00:10 | 289.29 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 199014.08 | 7967.15 | 10-MAY-03:20 | 76854.07 | 06-FEB-20:00 |
ElectricityPurchased:Plant | 199014.08 | 7967.15 | 10-MAY-03:20 | 76854.07 | 06-FEB-20:00 |
Cogeneration:ElectricityPurchased | 199014.08 | 7967.15 | 10-MAY-03:20 | 76854.07 | 06-FEB-20:00 |
General:Cogeneration:ElectricityPurchased | 199014.08 | 7967.15 | 10-MAY-03:20 | 76854.07 | 06-FEB-20:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 199014.08 | 7967.15 | 10-MAY-03:20 | 76854.07 | 06-FEB-20:00 |
ElectricityNet:Plant | 199014.08 | 7967.15 | 10-MAY-03:20 | 76854.07 | 06-FEB-20:00 |
Cogeneration:ElectricityNet | 199014.08 | 7967.15 | 10-MAY-03:20 | 76854.07 | 06-FEB-20:00 |
General:Cogeneration:ElectricityNet | 199014.08 | 7967.15 | 10-MAY-03:20 | 76854.07 | 06-FEB-20:00 |
HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ExteriorLights:Electricity | 5508.71 | 0.00 | 01-JAN-06:10 | 1257.69 | 01-JAN-00:10 |
Exterior-Lights:ExteriorLights:Electricity | 5508.71 | 0.00 | 01-JAN-06:10 | 1257.69 | 01-JAN-00:10 |
Garage-Lights:ExteriorLights:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:Electricity | 1308.75 | 149.40 | 01-JAN-00:10 | 149.40 | 04-JAN-09:30 |
Water Heater Parasitic:WaterSystems:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Natural Gas Annual Value [therm] | Natural Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Water:Plant | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
WaterSystems:Water | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Domestic Hot Water:WaterSystems:Water | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
MainsWater:Facility | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
MainsWater:Plant | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
WaterSystems:MainsWater | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Domestic Hot Water:WaterSystems:MainsWater | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1034622.58 | 9603.55 | 29-MAY-02:10 | 390113.71 | 07-FEB-07:30 |
EnergyTransfer:HVAC | 560112.93 | 0.00 | 12-MAR-13:10 | 246767.35 | 07-FEB-07:50 |
CoolingCoils:EnergyTransfer | 230666.28 | 0.00 | 01-JAN-00:10 | 142663.07 | 13-AUG-15:10 |
HeatingCoils:EnergyTransfer | 329446.65 | 0.00 | 12-MAR-13:10 | 202593.78 | 07-FEB-07:30 |
EnergyTransfer:Building | 325714.47 | 3574.75 | 28-APR-13:10 | 114959.57 | 06-FEB-09:10 |
EnergyTransfer:Zone:CRAWLSPACE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer | 149255.32 | 0.00 | 12-MAR-13:10 | 114959.57 | 06-FEB-09:10 |
Heating:EnergyTransfer:Zone:CRAWLSPACE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 149255.32 | 0.00 | 12-MAR-13:10 | 114959.57 | 06-FEB-09:10 |
Cooling:EnergyTransfer | 176459.15 | 0.00 | 01-JAN-00:10 | 99793.17 | 10-AUG-17:20 |
Cooling:EnergyTransfer:Zone:CRAWLSPACE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer | 176459.15 | 0.00 | 01-JAN-00:10 | 99793.17 | 10-AUG-17:20 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 21042.07 | 0.59 | 13-APR-20:00 | 8901.05 | 21-SEP-16:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 10546.84 | 0.00 | 06-JAN-14:50 | 8146.50 | 06-FEB-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 10495.22 | 0.00 | 01-JAN-00:10 | 8901.05 | 21-SEP-16:10 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 15166.39 | 0.06 | 10-OCT-03:20 | 6581.79 | 13-FEB-08:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 6878.92 | 0.00 | 06-JAN-13:30 | 6581.79 | 13-FEB-08:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8287.46 | 0.00 | 01-JAN-00:10 | 4866.45 | 21-JUL-13:50 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 20682.40 | 0.08 | 30-APR-03:00 | 8011.54 | 06-FEB-09:40 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 10340.74 | 0.00 | 15-JAN-12:00 | 8011.54 | 06-FEB-09:40 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 10341.66 | 0.00 | 01-JAN-00:10 | 6918.67 | 10-AUG-10:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 20640.27 | 0.10 | 10-JUN-04:50 | 8497.47 | 08-JUL-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12012.75 | 0.00 | 22-FEB-17:10 | 8235.92 | 06-FEB-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8627.52 | 0.00 | 01-JAN-00:10 | 8497.47 | 08-JUL-18:10 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 14758.43 | 0.20 | 25-NOV-17:20 | 6434.90 | 07-FEB-13:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8320.48 | 0.00 | 09-MAR-18:30 | 6434.90 | 07-FEB-13:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 6437.95 | 0.00 | 01-JAN-00:10 | 4361.59 | 05-JUN-22:50 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 20099.18 | 0.22 | 08-MAY-23:20 | 8078.31 | 06-FEB-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 11736.31 | 0.00 | 12-MAR-13:00 | 8078.31 | 06-FEB-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8362.88 | 0.00 | 01-JAN-00:10 | 6360.04 | 12-JUN-09:30 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 18401.41 | 0.43 | 18-APR-12:40 | 8946.42 | 21-SEP-16:20 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5818.62 | 0.00 | 05-JAN-13:40 | 5155.48 | 07-FEB-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12582.79 | 0.00 | 01-JAN-00:10 | 8946.42 | 21-SEP-16:20 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 14100.81 | 0.09 | 20-OCT-02:00 | 4910.01 | 17-OCT-20:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 3034.34 | 0.00 | 01-JAN-22:20 | 3194.07 | 07-FEB-08:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 11066.46 | 0.00 | 01-JAN-00:10 | 4910.01 | 17-OCT-20:10 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 18232.24 | 0.28 | 12-MAY-12:00 | 7031.25 | 10-AUG-10:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5681.46 | 0.00 | 05-JAN-13:10 | 5158.08 | 07-FEB-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 12550.79 | 0.00 | 01-JAN-00:10 | 7031.25 | 10-AUG-10:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 17241.84 | 0.11 | 06-SEP-04:00 | 8505.89 | 08-JUL-18:20 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 6859.57 | 0.00 | 15-JAN-15:20 | 5313.31 | 07-FEB-08:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 10382.27 | 0.00 | 01-JAN-00:10 | 8505.89 | 08-JUL-18:20 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 12475.72 | 0.13 | 16-OCT-23:00 | 5021.63 | 14-OCT-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 3809.08 | 0.00 | 11-JAN-17:10 | 3563.35 | 06-FEB-11:40 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8666.64 | 0.00 | 01-JAN-00:10 | 4507.42 | 20-APR-22:20 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 16876.77 | 0.20 | 05-SEP-04:50 | 6306.86 | 12-JUN-09:40 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 6647.31 | 0.00 | 22-FEB-21:20 | 5182.44 | 07-FEB-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 10229.46 | 0.00 | 01-JAN-00:10 | 6306.86 | 12-JUN-09:40 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 20766.31 | 1.07 | 06-NOV-03:40 | 7846.01 | 06-FEB-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 11268.43 | 0.00 | 12-MAR-13:00 | 7846.01 | 06-FEB-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 9497.88 | 0.00 | 01-JAN-00:10 | 6424.97 | 12-JUN-09:40 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 21157.56 | 0.36 | 01-NOV-18:00 | 7783.49 | 06-FEB-09:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 10042.63 | 0.00 | 15-JAN-12:20 | 7783.49 | 06-FEB-09:50 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 11114.93 | 0.00 | 01-JAN-00:10 | 6903.02 | 10-AUG-10:30 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 21517.71 | 0.54 | 25-APR-05:50 | 8873.25 | 10-AUG-17:20 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 10258.21 | 0.00 | 15-JAN-12:30 | 7930.07 | 06-FEB-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 11259.50 | 0.00 | 01-JAN-00:10 | 8873.25 | 10-AUG-17:20 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 15512.28 | 0.21 | 06-NOV-01:50 | 6539.48 | 06-FEB-09:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 7873.69 | 0.00 | 09-MAR-18:30 | 6539.48 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 7638.59 | 0.00 | 01-JAN-00:10 | 4409.47 | 06-MAY-19:10 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 15802.29 | 0.14 | 05-APR-17:50 | 6623.47 | 06-FEB-09:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 6603.56 | 0.00 | 15-JAN-12:20 | 6623.47 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 9198.73 | 0.00 | 01-JAN-00:10 | 4627.99 | 06-APR-22:20 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 21240.81 | 0.12 | 14-JUN-01:00 | 8851.12 | 10-JUL-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 11522.38 | 0.00 | 22-FEB-17:10 | 8030.37 | 07-FEB-08:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 9718.43 | 0.00 | 01-JAN-00:10 | 8851.12 | 10-JUL-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRecoveryForCooling:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Plant | 148795.18 | 1287.66 | 14-AUG-02:10 | 38579.10 | 18-FEB-08:40 |
WaterSystems:EnergyTransfer | 148795.18 | 1287.66 | 14-AUG-02:10 | 38579.10 | 18-FEB-08:40 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 148795.18 | 1287.66 | 14-AUG-02:10 | 38579.10 | 18-FEB-08:40 |
PlantLoopHeatingDemand:Facility | 148795.18 | 1287.66 | 14-AUG-02:10 | 38579.10 | 18-FEB-08:40 |
PlantLoopHeatingDemand:Plant | 148795.18 | 1287.66 | 14-AUG-02:10 | 38579.10 | 18-FEB-08:40 |
WaterSystems:PlantLoopHeatingDemand | 148795.18 | 1287.66 | 14-AUG-02:10 | 38579.10 | 18-FEB-08:40 |
General:WaterSystems:PlantLoopHeatingDemand | 148795.18 | 1287.66 | 14-AUG-02:10 | 38579.10 | 18-FEB-08:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 108.582 | -1323.65 | 21875.721 | -502.85 | 0.000 | 0.000 | 3077.341 | 2150.478 | 10401.374 | 8855.466 | 0.000 | 56.746 | 0.000 | 0.000 | -6002.56 | 0.000 | -6544.40 | -12046.07 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 110.292 | -1321.86 | 17908.446 | -296.00 | 0.000 | 0.000 | 3076.966 | 2150.478 | 10401.374 | 4084.503 | 0.000 | 50.329 | 0.000 | 0.000 | -2415.48 | 0.000 | -5754.60 | -10185.02 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 109.464 | -1326.27 | 21485.287 | -472.17 | 0.000 | 0.000 | 3077.899 | 2150.478 | 10401.374 | 8819.909 | 0.000 | 56.526 | 0.000 | 0.000 | -5901.55 | 0.000 | -6549.85 | -12053.83 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 109.523 | -1319.49 | 23974.686 | -404.28 | 0.000 | 0.000 | 3083.362 | 2150.478 | 10401.374 | 6128.251 | 0.000 | 57.160 | 0.000 | 0.000 | -6231.76 | 0.000 | -6523.13 | -12450.95 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 111.141 | -1315.62 | 20192.718 | -218.47 | 0.000 | 0.000 | 3086.053 | 2150.478 | 10401.374 | 1252.792 | 0.000 | 51.391 | 0.000 | 0.000 | -2610.26 | 0.000 | -5728.89 | -10485.46 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 109.255 | -1321.95 | 23593.939 | -371.06 | 0.000 | 0.000 | 3083.877 | 2150.478 | 10401.374 | 6046.932 | 0.000 | 56.717 | 0.000 | 0.000 | -6085.50 | 0.000 | -6529.36 | -12497.92 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 110.798 | -1330.09 | 15982.825 | -573.45 | 0.000 | 0.000 | 3062.936 | 2150.478 | 10401.374 | 8757.465 | 0.000 | 24.632 | 0.000 | 0.000 | -6174.71 | 0.000 | -2882.61 | -8575.38 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 109.902 | -1329.16 | 12170.994 | -362.46 | 0.000 | 0.000 | 3061.779 | 2150.478 | 10401.374 | 4038.328 | 0.000 | 18.016 | 0.000 | 0.000 | -2484.65 | 0.000 | -2094.11 | -7059.09 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 109.728 | -1332.30 | 15652.859 | -552.43 | 0.000 | 0.000 | 3064.318 | 2150.478 | 10401.374 | 8723.008 | 0.000 | 24.571 | 0.000 | 0.000 | -6064.68 | 0.000 | -2884.42 | -8545.29 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 109.105 | -1325.40 | 17868.568 | -465.10 | 0.000 | 0.000 | 3069.931 | 2150.478 | 10401.374 | 6056.281 | 0.000 | 24.777 | 0.000 | 0.000 | -6411.90 | 0.000 | -2871.38 | -8896.86 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 110.284 | -1322.52 | 14183.044 | -272.32 | 0.000 | 0.000 | 3071.970 | 2150.478 | 10401.374 | 1230.043 | 0.000 | 18.328 | 0.000 | 0.000 | -2686.61 | 0.000 | -2084.17 | -7243.85 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 110.262 | -1327.78 | 17535.534 | -440.03 | 0.000 | 0.000 | 3071.267 | 2150.478 | 10401.374 | 5973.501 | 0.000 | 24.604 | 0.000 | 0.000 | -6254.99 | 0.000 | -2873.93 | -8910.13 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 109.763 | -1325.90 | 22884.347 | -441.55 | 0.000 | 0.000 | 3075.537 | 2150.478 | 10401.374 | 5976.252 | 0.000 | 55.806 | 0.000 | 0.000 | -6239.84 | 0.000 | -6559.81 | -10630.30 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 109.146 | -1328.98 | 21071.024 | -524.16 | 0.000 | 0.000 | 3070.762 | 2150.478 | 10401.374 | 8730.339 | 0.000 | 55.719 | 0.000 | 0.000 | -6039.07 | 0.000 | -6576.47 | -10720.80 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 109.369 | -1326.78 | 21413.697 | -549.00 | 0.000 | 0.000 | 3069.967 | 2150.478 | 10401.374 | 8760.148 | 0.000 | 55.878 | 0.000 | 0.000 | -6147.37 | 0.000 | -6571.50 | -10717.66 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 109.797 | -1320.66 | 19416.926 | -285.91 | 0.000 | 0.000 | 3075.601 | 2150.478 | 10401.374 | 1230.967 | 0.000 | 50.132 | 0.000 | 0.000 | -2678.51 | 0.000 | -5762.37 | -8702.76 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 109.927 | -1325.43 | 17417.666 | -350.34 | 0.000 | 0.000 | 3068.746 | 2150.478 | 10401.374 | 4038.851 | 0.000 | 49.478 | 0.000 | 0.000 | -2472.68 | 0.000 | -5781.65 | -8859.43 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 110.561 | -1323.40 | 23242.005 | -471.12 | 0.000 | 0.000 | 3075.041 | 2150.478 | 10401.374 | 6053.199 | 0.000 | 56.219 | 0.000 | 0.000 | -6393.17 | 0.000 | -6553.38 | -10593.68 |
CRAWLSPACE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17682.668 | 244882.591 | 0.000 | 0.000 | 0.000 | -262565.26 | 0.000 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15642.209 | 118398.718 | 0.000 | 0.000 | 0.000 | -134040.93 | -0.42 |
Total Facility | 1976.900 | -23847.25 | 347870.284 | -7552.70 | 0.000 | 0.000 | 55323.354 | 38708.604 | 187224.736 | 104756.234 | 0.000 | 34111.908 | 363281.309 | 0.000 | -89295.28 | 0.000 | -487732.20 | -179174.89 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 21-SEP-16:10 | 0.00 | 0.02 | 0.00 | -0.8 | 0.00 | 0.00 | 140.35 | 336.87 | 1343.44 | 8266.97 | 0.00 | 35.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1222.0 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 07-MAR-19:23 | 0.00 | -0.4 | 0.00 | 0.00 | 0.00 | 0.00 | 472.44 | 699.99 | 1650.38 | 0.00 | 0.00 | 0.00 | 4590.05 | 0.00 | -846.8 | 0.00 | -1350.5 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 10-AUG-10:27 | 0.00 | 0.03 | 0.00 | -0.6 | 0.00 | 0.00 | 115.09 | 90.23 | 1078.58 | 7351.71 | 0.00 | 123.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1839.9 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 08-JUL-18:10 | 0.00 | 0.01 | 0.00 | -0.7 | 0.00 | 0.00 | 426.75 | 631.63 | 1734.73 | 7157.30 | 0.00 | 32.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1486.1 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 02-APR-20:05 | 0.00 | -0.4 | 0.00 | 0.00 | 0.00 | 0.00 | 473.10 | 699.99 | 1637.97 | 0.00 | 0.00 | 0.00 | 3630.05 | 0.00 | -568.1 | 0.00 | -914.9 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12-JUN-09:30 | 0.00 | 0.03 | 0.00 | -0.6 | 0.00 | 0.00 | 115.09 | 90.23 | 1083.81 | 6331.42 | 0.00 | 242.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1503.7 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 21-SEP-16:20 | 0.00 | -0.2 | 0.00 | -0.6 | 0.00 | 0.00 | 140.35 | 336.87 | 1343.44 | 7964.55 | 0.00 | 14.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -853.1 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 30-JAN-19:15 | 0.00 | -0.5 | 0.00 | 0.00 | 0.00 | 0.00 | 473.86 | 699.99 | 1650.38 | 0.00 | 0.00 | 0.00 | 4385.37 | 0.00 | -997.5 | 0.00 | -571.2 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 10-AUG-10:27 | 0.00 | 0.03 | 0.00 | -0.6 | 0.00 | 0.00 | 115.09 | 90.23 | 1078.58 | 7327.30 | 0.00 | 53.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1633.4 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 08-JUL-18:15 | 0.00 | 0.01 | 0.00 | -0.7 | 0.00 | 0.00 | 426.76 | 631.63 | 1734.73 | 6917.46 | 0.00 | 8.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1212.2 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 19-MAR-22:10 | 0.00 | -0.4 | 0.00 | 0.00 | 0.00 | 0.00 | 526.66 | 294.76 | 1349.09 | 0.00 | 0.00 | 0.00 | 4309.00 | 0.00 | -717.4 | 0.00 | -444.0 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 12-JUN-09:40 | 0.00 | 0.03 | 0.00 | -0.6 | 0.00 | 0.00 | 115.09 | 90.23 | 1083.81 | 6092.58 | 0.00 | 112.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1187.5 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 12-JUN-09:40 | 0.00 | 0.03 | 0.00 | -0.6 | 0.00 | 0.00 | 115.09 | 90.23 | 1083.81 | 6085.69 | 0.00 | 255.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1205.8 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 10-AUG-10:27 | 0.00 | 0.03 | 0.00 | -0.6 | 0.00 | 0.00 | 115.09 | 90.23 | 1078.58 | 7319.51 | 0.00 | 122.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1822.3 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 10-AUG-17:20 | 0.00 | -0.2 | 0.00 | -0.5 | 0.00 | 0.00 | 263.17 | 469.21 | 1655.83 | 6584.24 | 0.00 | 149.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -247.9 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 02-APR-20:10 | 0.00 | -0.4 | 0.00 | 0.00 | 0.00 | 0.00 | 472.91 | 699.99 | 1637.97 | 0.00 | 0.00 | 0.00 | 3684.66 | 0.00 | -578.3 | 0.00 | -920.8 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 07-MAR-19:13 | 0.00 | -0.4 | 0.00 | 0.00 | 0.00 | 0.00 | 472.17 | 699.99 | 1650.38 | 0.00 | 0.00 | 0.00 | 4577.47 | 0.00 | -851.8 | 0.00 | -1349.9 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 10-JUL-18:10 | 0.00 | 0.02 | 0.00 | -0.8 | 0.00 | 0.00 | 426.76 | 631.63 | 1713.00 | 6767.23 | 0.00 | 89.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -776.2 |
CRAWLSPACE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-AUG-17:20 | 0.00 | -2.2 | 0.00 | -6.1 | 0.00 | 0.00 | 4737.03 | 8445.78 | 29804.87 | 49119.73 | 0.00 | 22372.27 | 23584.13 | 0.00 | 0.00 | 0.00 | -38264.3 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 06-FEB-10:00 | -3163.4 | 0.00 | 11309.69 | 0.00 | 0.00 | 0.00 | 127.29 | 90.23 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1478.7 | 0.00 | -3582.0 | -4387.0 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 13-FEB-08:25 | -2634.8 | 0.00 | 9284.38 | 0.00 | 0.00 | 0.00 | 221.94 | 132.34 | 1145.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -743.7 | 0.00 | -2724.5 | -4680.9 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 06-FEB-09:40 | -3163.5 | 0.00 | 11174.83 | 0.00 | 0.00 | 0.00 | 127.29 | 90.23 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1584.1 | 0.00 | -3425.6 | -4303.0 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 06-FEB-10:00 | -3163.4 | 0.00 | 11399.10 | 0.00 | 0.00 | 0.00 | 127.29 | 90.23 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1631.3 | 0.00 | -3582.0 | -4323.8 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 07-FEB-13:25 | -2549.7 | 0.00 | 9054.92 | 0.00 | 0.00 | 0.00 | 132.41 | 90.23 | 1076.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -80.4 | 0.00 | -2159.4 | -5564.2 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 06-FEB-10:00 | -3163.4 | 0.00 | 11241.46 | 0.00 | 0.00 | 0.00 | 127.29 | 90.23 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1360.7 | 0.00 | -3582.0 | -4436.7 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 11-DEC-16:50 | -5552.8 | 0.00 | 13211.90 | 0.00 | 0.00 | 0.00 | 158.05 | 336.87 | 1343.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2437.2 | 0.00 | -782.5 | -6277.7 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 18-JAN-22:10 | -1794.2 | 0.00 | 8336.94 | 0.00 | 0.00 | 0.00 | 526.28 | 294.76 | 1333.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -631.7 | 0.00 | -382.1 | -7683.7 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 05-MAR-18:30 | -5446.5 | 0.00 | 12924.00 | 0.00 | 0.00 | 0.00 | 472.41 | 631.63 | 1734.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2158.1 | 0.00 | -718.7 | -7439.5 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 06-MAR-18:50 | -5605.6 | 0.00 | 13688.21 | 0.00 | 0.00 | 0.00 | 477.90 | 631.63 | 1713.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2343.8 | 0.00 | -757.9 | -7803.5 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 21-NOV-23:40 | -2345.1 | 0.00 | 8962.14 | 0.00 | 0.00 | 0.00 | 526.28 | 120.31 | 1146.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -603.6 | 0.00 | -306.5 | -7499.8 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 01-NOV-23:27 | -5008.9 | 0.00 | 12453.48 | 0.00 | 0.00 | 0.00 | 526.86 | 120.31 | 1146.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1396.7 | 0.00 | -313.7 | -7527.6 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 06-FEB-10:00 | -3163.4 | 0.00 | 11009.17 | 0.00 | 0.00 | 0.00 | 127.29 | 90.23 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1416.8 | 0.00 | -3586.2 | -4144.2 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 06-FEB-09:50 | -3163.4 | 0.00 | 10946.72 | 0.00 | 0.00 | 0.00 | 127.29 | 90.23 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1455.3 | 0.00 | -3507.5 | -4121.8 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 06-FEB-10:00 | -3163.4 | 0.00 | 11093.27 | 0.00 | 0.00 | 0.00 | 127.29 | 90.23 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1545.4 | 0.00 | -3586.2 | -4099.6 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 06-FEB-12:45 | -2976.3 | 0.00 | 10176.32 | 0.00 | 0.00 | 0.00 | 129.74 | 90.23 | 1082.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -423.4 | 0.00 | -2988.9 | -5089.7 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 06-FEB-12:45 | -2979.9 | 0.00 | 10079.90 | 0.00 | 0.00 | 0.00 | 129.45 | 90.23 | 1082.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -196.8 | 0.00 | -2993.0 | -5211.9 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 07-FEB-08:10 | -5806.0 | 0.00 | 13836.74 | 0.00 | 0.00 | 0.00 | 215.03 | 132.34 | 1145.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2323.7 | 0.00 | -3209.8 | -3989.8 |
CRAWLSPACE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-FEB-09:05 | -56749.0 | 0.00 | 172666.81 | 0.00 | 0.00 | 0.00 | 2313.40 | 1624.19 | 19508.63 | 0.00 | 0.00 | 0.00 | 56572.80 | 0.00 | -29567.7 | 0.00 | -166369.1 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 389.2927 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 389.2927 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 172.9519 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 172.9519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 299.8306 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 299.8306 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 373.1180 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 373.1180 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 168.3741 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 168.3741 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 283.5202 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 283.5202 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 384.1001 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 384.1001 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 174.5878 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 174.5878 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 304.3220 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 304.3220 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 368.0134 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 368.0134 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 168.2593 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 168.2593 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 286.3806 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 286.3806 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 395.2975 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 395.2975 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 189.6331 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 189.6331 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 305.2586 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 305.2586 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 388.6443 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 388.6443 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 191.1561 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 191.1561 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 288.2059 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 288.2059 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 389.2927 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 389.2927 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 172.9519 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 172.9519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 299.8306 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 299.8306 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 373.1180 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 373.1180 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 168.3741 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 168.3741 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 283.5202 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 283.5202 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 384.1001 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 384.1001 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 174.5878 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 174.5878 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 304.3220 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 304.3220 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 368.0134 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 368.0134 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 168.2593 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 168.2593 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 286.3806 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 286.3806 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 395.2975 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 395.2975 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 189.6331 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 189.6331 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 305.2586 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 305.2586 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 388.6443 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 388.6443 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 191.1561 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 191.1561 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 288.2059 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 288.2059 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 389.2927 | 389.2927 | 389.2927 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 172.9519 | 172.9519 | 172.9519 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 299.8306 | 299.8306 | 299.8306 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 373.1180 | 373.1180 | 373.1180 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 168.3741 | 168.3741 | 168.3741 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 283.5202 | 283.5202 | 283.5202 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 384.1001 | 384.1001 | 384.1001 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 174.5878 | 174.5878 | 174.5878 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 304.3220 | 304.3220 | 304.3220 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 368.0134 | 368.0134 | 368.0134 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 168.2593 | 168.2593 | 168.2593 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 286.3806 | 286.3806 | 286.3806 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 288.2059 | 288.2059 | 288.2059 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 305.2586 | 305.2586 | 305.2586 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 395.2975 | 395.2975 | 395.2975 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 191.1561 | 191.1561 | 191.1561 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 189.6331 | 189.6331 | 189.6331 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 388.6443 | 388.6443 | 388.6443 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 389.2927 | 389.2927 | 389.2927 | 389.2927 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 172.9519 | 172.9519 | 172.9519 | 172.9519 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 299.8306 | 299.8306 | 299.8306 | 299.8306 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 373.1180 | 373.1180 | 373.1180 | 373.1180 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 168.3741 | 168.3741 | 168.3741 | 168.3741 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 283.5202 | 283.5202 | 283.5202 | 283.5202 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 384.1001 | 384.1001 | 384.1001 | 384.1001 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 174.5878 | 174.5878 | 174.5878 | 174.5878 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 304.3220 | 304.3220 | 304.3220 | 304.3220 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 368.0134 | 368.0134 | 368.0134 | 368.0134 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 168.2593 | 168.2593 | 168.2593 | 168.2593 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 286.3806 | 286.3806 | 286.3806 | 286.3806 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 395.2975 | 395.2975 | 395.2975 | 395.2975 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 189.6331 | 189.6331 | 189.6331 | 189.6331 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 305.2586 | 305.2586 | 305.2586 | 305.2586 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 388.6443 | 388.6443 | 388.6443 | 388.6443 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 191.1561 | 191.1561 | 191.1561 | 191.1561 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 288.2059 | 288.2059 | 288.2059 | 288.2059 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 389.2927 | 389.2927 | 389.2927 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 172.9519 | 172.9519 | 172.9519 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 299.8306 | 299.8306 | 299.8306 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 373.1180 | 373.1180 | 373.1180 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 168.3741 | 168.3741 | 168.3741 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 283.5202 | 283.5202 | 283.5202 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 384.1001 | 384.1001 | 384.1001 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 174.5878 | 174.5878 | 174.5878 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 304.3220 | 304.3220 | 304.3220 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 368.0134 | 368.0134 | 368.0134 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 168.2593 | 168.2593 | 168.2593 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 286.3806 | 286.3806 | 286.3806 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 288.2059 | 288.2059 | 288.2059 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 305.2586 | 305.2586 | 305.2586 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 395.2975 | 395.2975 | 395.2975 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 191.1561 | 191.1561 | 191.1561 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 189.6331 | 189.6331 | 189.6331 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 388.6443 | 388.6443 | 388.6443 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 389.2927 | 389.2927 | 389.2927 | 389.2927 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 172.9519 | 172.9519 | 172.9519 | 172.9519 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 299.8306 | 299.8306 | 299.8306 | 299.8306 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 373.1180 | 373.1180 | 373.1180 | 373.1180 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 168.3741 | 168.3741 | 168.3741 | 168.3741 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 283.5202 | 283.5202 | 283.5202 | 283.5202 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 384.1001 | 384.1001 | 384.1001 | 384.1001 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 174.5878 | 174.5878 | 174.5878 | 174.5878 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 304.3220 | 304.3220 | 304.3220 | 304.3220 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 368.0134 | 368.0134 | 368.0134 | 368.0134 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 168.2593 | 168.2593 | 168.2593 | 168.2593 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 286.3806 | 286.3806 | 286.3806 | 286.3806 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 395.2975 | 395.2975 | 395.2975 | 395.2975 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 189.6331 | 189.6331 | 189.6331 | 189.6331 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 305.2586 | 305.2586 | 305.2586 | 305.2586 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 388.6443 | 388.6443 | 388.6443 | 388.6443 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 191.1561 | 191.1561 | 191.1561 | 191.1561 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 288.2059 | 288.2059 | 288.2059 | 288.2059 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [ft2] | 39005.22 |
Principal Heating Source | Electricity |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
CRAWLSPACE | 7794.39 | 0.00 | 7794.39 | 0.00 |
BREEZEWAY | 1798.16 | 0.00 | 1798.16 | 0.00 |
ATTIC | 7802.71 | 0.00 | 7802.71 | 0.00 |
Totals | 39005.22 | 21609.96 | 17395.26 |
Data | |
Number of hours heating loads not met | 200.67 |
Number of hours cooling loads not met | 0.50 |
Number of hours not met | 201.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [kWh] | Electricity Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Gasoline Use [therm] | Gasoline Demand [Btu/h] | Diesel Use [kBtu] | Diesel Demand [Btu/h] | Coal Use [kBtu] | Coal Demand [Btu/h] | Fuel Oil No 1 Use [kBtu] | Fuel Oil No 1 Demand [Btu/h] | Fuel Oil No 2 Use [kBtu] | Fuel Oil No 2 Demand [Btu/h] | Propane Use [kBtu] | Propane Demand [Btu/h] | Other Fuel 1 Use [kBtu] | Other Fuel 1 Demand [Btu/h] | Other Fuel 2 Use [kBtu] | Other Fuel 2 Demand [Btu/h] | District Cooling Use [ton-hrs] | District Cooling Demand [ton] | District Heating Use [kBtu] | District Heating Demand [Btu/h] | |
Heating -- General | 59412.97 | 54257.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 7628.94 | 9121.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- General | 11336.81 | 3692.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Exterior-Lights | 5508.71 | 1257.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- dishwasher | 2758.31 | 880.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- refrigerator | 12036.11 | 1639.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- clotheswasher | 1408.53 | 381.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_dryer | 12502.11 | 3196.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_range | 9058.39 | 3721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_mels | 46926.68 | 7929.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- IECC_adj | 3113.66 | 526.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 7360.45 | 2129.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation | 2534.14 | 289.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 1308.75 | 149.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Other | 16119.52 | 8907.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 299798.81 | 679517.12 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 299798.81 | 679517.12 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting (All) | 0.29 |
Space Heating | 1.52 |
Space Cooling | 0.20 |
Fans (All) | 0.25 |
Service Water Heating | 0.45 |
Receptacle Equipment | 2.25 |
Miscellaneous (All) | 5.10 |
Subtotal | 5.10 |
Natural Gas [kWh/ft2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [kBtu/ft2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.70 |
Space Heating | 29.85 |
Space Cooling | 3.83 |
Fans (All) | 4.97 |
Service Water Heating | 8.76 |
Receptacle Equipment | 44.12 |
Miscellaneous | 2.77 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OCCUPANCY | 6031. | 8760. |
INTERIORLIGHTING | 2852. | 8760. |
INTERIORLIGHTINGHE | 3070. | 8760. |
INTERIORLIGHTINGHE_OS | 2910. | 8760. |
INTERIORLIGHTINGHE_VS | 2149. | 8760. |
EXTERIORLIGHTING | 4380. | 4380. |
REFRIGERATOR | 7343. | 8760. |
MISCPLUGLOAD | 5918. | 8760. |
COOKINGRANGE | 2434. | 8760. |
DHW_SCH | 365. | 8760. |
DISHWASHER | 2799. | 8760. |
CLOTHESWASHER | 3297. | 8760. |
CLOTHESDRYER | 3911. | 8760. |
SINKS | 4179. | 8760. |
SHOWERS | 2640. | 8760. |
BATHS | 2586. | 8760. |
DHWDIST | 4662. | 8760. |
SHADING_2012IECC | 0. | 0. |
SINKSENSSCHEDULE | 6025. | 8760. |
SINKLATSCHEDULE | 2735. | 8760. |
SHOWERSENSSCHEDULE | 4492. | 8760. |
SHOWERLATSCHEDULE | 4268. | 8760. |
BATHSENSSCHEDULE | 8760. | 8760. |
BATHLATSCHEDULE | 0. | 0. |
First Object Used | Month Assumed | 11am First Wednesday [F] | Days with Same 11am Value | 11pm First Wednesday [F] | Days with Same 11pm Value | |
HEATING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | January | 72.00 | 365 | 72.00 | 365 |
COOLING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | July | 75.00 | 365 | 75.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CRAWLSPACE | 8682.33 | 77.67 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 8748.00 | 12.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 8120.17 | 489.17 | 149.67 | 1.00 | 0.00 |
Min | 8120.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 489.17 | 149.67 | 1.00 | 0.00 |
Average | 8725.26 | 27.56 | 7.13 | 0.05 | 0.00 |
Sum | 183230.50 | 578.83 | 149.67 | 1.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CRAWLSPACE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 7821.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 164250.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8580.50 | 179.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8619.17 | 140.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8600.17 | 159.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8577.83 | 182.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8608.17 | 151.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8594.17 | 165.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8670.50 | 89.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8719.33 | 40.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8675.67 | 84.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8672.50 | 87.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8717.83 | 42.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8674.50 | 85.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8658.67 | 101.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8662.00 | 98.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8644.67 | 115.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8684.83 | 75.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8690.50 | 69.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8644.50 | 115.50 | 0.00 | 0.00 | 0.00 |
CRAWLSPACE | 8368.67 | 391.33 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 7874.67 | 847.00 | 38.33 | 0.00 | 0.00 |
Min | 7874.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 847.00 | 38.33 | 0.00 | 0.00 |
Average | 8604.71 | 153.47 | 1.83 | 0.00 | 0.00 |
Sum | 180698.83 | 3222.83 | 38.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8846.33 | 278.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8927.33 | 197.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8844.00 | 281.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8840.17 | 284.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8920.83 | 204.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8837.17 | 287.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8975.67 | 149.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 9053.00 | 72.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8970.00 | 155.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8971.33 | 153.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 9049.67 | 75.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8966.83 | 158.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8944.67 | 180.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8949.50 | 175.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8937.50 | 187.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 9015.33 | 109.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 9017.67 | 107.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8939.50 | 185.50 | 0.00 | 0.00 | 0.00 |
CRAWLSPACE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 9053.00 | 287.83 | 0.00 | 0.00 | 0.00 |
Average | 7666.98 | 154.45 | 0.00 | 0.00 | 0.00 |
Sum | 161006.50 | 3243.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (F) | SET ≤ 12.2°C OccupantHours (F) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (F) | SET > 30°C OccupantHours (F) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2021-05-12 10:34:39
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 736.528 | 87.357 | 87.357 |
February | 0.000 | 0.000 | 654.361 | 79.574 | 79.574 |
March | 33.083 | 0.962 | 571.708 | 50.207 | 51.168 |
April | 69.306 | 1.760 | 421.964 | 25.707 | 27.466 |
May | 187.444 | 6.595 | 160.467 | 5.817 | 12.411 |
June | 437.611 | 19.903 | 31.375 | 1.239 | 21.142 |
July | 602.936 | 31.434 | 1.361 | 0.067 | 31.501 |
August | 532.306 | 25.402 | 5.394 | 0.203 | 25.604 |
September | 321.181 | 12.597 | 64.522 | 2.214 | 14.811 |
October | 84.028 | 2.490 | 385.900 | 19.183 | 21.673 |
November | 5.111 | 0.059 | 573.181 | 37.757 | 37.816 |
December | 0.000 | 0.000 | 734.306 | 82.823 | 82.823 |
Annual Sum or Average | 2273.006 | 101.200 | 4341.067 | 392.148 | 493.348 |
Minimum of Months | 0.000 | 0.000 | 1.361 | 0.067 | 12.411 |
Maximum of Months | 602.936 | 31.434 | 736.528 | 87.357 | 87.357 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 734.889 | 44.439 | 44.439 |
February | 0.000 | 0.000 | 655.389 | 40.316 | 40.316 |
March | 25.500 | 0.610 | 564.361 | 29.439 | 30.049 |
April | 26.056 | 0.168 | 403.139 | 16.914 | 17.082 |
May | 120.333 | 1.805 | 110.028 | 3.780 | 5.585 |
June | 393.944 | 9.945 | 25.769 | 0.864 | 10.808 |
July | 587.639 | 18.883 | 0.889 | 0.033 | 18.916 |
August | 525.931 | 15.339 | 2.122 | 0.082 | 15.421 |
September | 319.722 | 7.446 | 40.108 | 1.201 | 8.647 |
October | 74.278 | 1.252 | 322.858 | 11.809 | 13.061 |
November | 0.000 | 0.000 | 534.361 | 23.175 | 23.175 |
December | 0.000 | 0.000 | 730.361 | 42.917 | 42.917 |
Annual Sum or Average | 2073.403 | 55.447 | 4124.275 | 214.969 | 270.416 |
Minimum of Months | 0.000 | 0.000 | 0.889 | 0.033 | 5.585 |
Maximum of Months | 587.639 | 18.883 | 734.889 | 44.439 | 44.439 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 738.389 | 73.492 | 73.492 |
February | 0.000 | 0.000 | 658.208 | 66.363 | 66.363 |
March | 27.306 | 0.924 | 584.694 | 45.212 | 46.136 |
April | 66.569 | 1.206 | 406.947 | 23.564 | 24.770 |
May | 195.861 | 5.108 | 135.208 | 4.659 | 9.767 |
June | 452.653 | 17.828 | 22.097 | 0.797 | 18.625 |
July | 635.292 | 30.386 | 0.389 | 0.021 | 30.407 |
August | 556.961 | 24.412 | 2.361 | 0.069 | 24.482 |
September | 352.069 | 12.070 | 57.594 | 1.825 | 13.895 |
October | 78.667 | 2.035 | 368.347 | 17.722 | 19.757 |
November | 0.389 | 0.001 | 570.056 | 35.423 | 35.424 |
December | 0.000 | 0.000 | 735.389 | 70.736 | 70.736 |
Annual Sum or Average | 2365.767 | 93.969 | 4279.681 | 339.885 | 433.854 |
Minimum of Months | 0.000 | 0.000 | 0.389 | 0.021 | 9.767 |
Maximum of Months | 635.292 | 30.386 | 738.389 | 73.492 | 73.492 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 88.544 | 88.544 |
February | 0.000 | 0.000 | 670.583 | 80.686 | 80.686 |
March | 20.278 | 0.473 | 628.972 | 55.198 | 55.671 |
April | 30.861 | 0.487 | 478.278 | 27.999 | 28.486 |
May | 147.722 | 4.675 | 176.286 | 6.324 | 10.999 |
June | 422.764 | 18.078 | 32.172 | 1.239 | 19.317 |
July | 599.872 | 28.880 | 1.139 | 0.054 | 28.934 |
August | 514.528 | 21.606 | 5.589 | 0.202 | 21.808 |
September | 260.681 | 8.010 | 79.856 | 2.790 | 10.800 |
October | 33.528 | 0.480 | 476.333 | 22.159 | 22.639 |
November | 0.000 | 0.000 | 641.014 | 41.200 | 41.200 |
December | 0.000 | 0.000 | 744.000 | 83.502 | 83.502 |
Annual Sum or Average | 2030.233 | 82.689 | 4678.222 | 409.896 | 492.585 |
Minimum of Months | 0.000 | 0.000 | 1.139 | 0.054 | 10.800 |
Maximum of Months | 599.872 | 28.880 | 744.000 | 88.544 | 88.544 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 44.644 | 44.644 |
February | 0.000 | 0.000 | 672.000 | 40.779 | 40.779 |
March | 20.417 | 0.270 | 626.806 | 32.449 | 32.719 |
April | 0.000 | 0.000 | 490.792 | 19.484 | 19.484 |
May | 72.611 | 0.917 | 143.186 | 4.602 | 5.520 |
June | 365.139 | 8.609 | 25.944 | 0.846 | 9.454 |
July | 576.806 | 16.790 | 0.361 | 0.013 | 16.802 |
August | 495.542 | 12.167 | 2.539 | 0.090 | 12.257 |
September | 220.806 | 3.691 | 62.033 | 1.754 | 5.445 |
October | 11.500 | 0.079 | 443.222 | 14.758 | 14.837 |
November | 0.000 | 0.000 | 624.208 | 26.080 | 26.080 |
December | 0.000 | 0.000 | 744.000 | 43.337 | 43.337 |
Annual Sum or Average | 1762.819 | 42.523 | 4579.092 | 228.835 | 271.358 |
Minimum of Months | 0.000 | 0.000 | 0.361 | 0.013 | 5.445 |
Maximum of Months | 576.806 | 16.790 | 744.000 | 44.644 | 44.644 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 72.772 | 72.772 |
February | 0.000 | 0.000 | 672.000 | 66.427 | 66.427 |
March | 24.194 | 0.524 | 642.000 | 49.408 | 49.932 |
April | 12.792 | 0.126 | 469.275 | 25.942 | 26.068 |
May | 148.872 | 3.219 | 153.264 | 5.269 | 8.488 |
June | 447.917 | 16.055 | 20.861 | 0.745 | 16.800 |
July | 629.736 | 28.039 | 0.389 | 0.021 | 28.060 |
August | 540.378 | 20.797 | 2.667 | 0.078 | 20.876 |
September | 295.828 | 7.049 | 71.169 | 2.199 | 9.248 |
October | 19.556 | 0.218 | 467.747 | 20.676 | 20.894 |
November | 0.000 | 0.000 | 653.125 | 38.858 | 38.858 |
December | 0.000 | 0.000 | 744.000 | 69.893 | 69.893 |
Annual Sum or Average | 2119.272 | 76.028 | 4640.497 | 352.288 | 428.316 |
Minimum of Months | 0.000 | 0.000 | 0.389 | 0.021 | 8.488 |
Maximum of Months | 629.736 | 28.039 | 744.000 | 72.772 | 72.772 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 719.819 | 74.313 | 74.313 |
February | 0.667 | 0.003 | 626.986 | 68.064 | 68.067 |
March | 40.583 | 1.237 | 466.236 | 38.766 | 40.003 |
April | 84.389 | 2.457 | 306.383 | 18.063 | 20.520 |
May | 244.417 | 8.277 | 74.742 | 3.378 | 11.655 |
June | 494.611 | 22.666 | 13.375 | 0.606 | 23.272 |
July | 645.447 | 34.385 | 0.222 | 0.009 | 34.394 |
August | 591.681 | 28.440 | 1.136 | 0.055 | 28.495 |
September | 377.653 | 14.977 | 29.578 | 1.237 | 16.214 |
October | 105.222 | 3.215 | 268.178 | 13.621 | 16.836 |
November | 8.722 | 0.099 | 495.667 | 28.405 | 28.504 |
December | 0.000 | 0.000 | 715.444 | 69.797 | 69.797 |
Annual Sum or Average | 2593.392 | 115.756 | 3717.767 | 316.314 | 432.070 |
Minimum of Months | 0.000 | 0.000 | 0.222 | 0.009 | 11.655 |
Maximum of Months | 645.447 | 34.385 | 719.819 | 74.313 | 74.313 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 667.028 | 38.418 | 38.418 |
February | 0.000 | 0.000 | 595.514 | 35.278 | 35.278 |
March | 29.417 | 0.727 | 407.250 | 21.609 | 22.336 |
April | 50.806 | 0.488 | 227.514 | 10.539 | 11.027 |
May | 196.272 | 2.977 | 49.347 | 2.014 | 4.991 |
June | 462.819 | 12.269 | 8.514 | 0.355 | 12.624 |
July | 634.956 | 21.454 | 0.000 | 0.000 | 21.454 |
August | 597.447 | 18.083 | 0.533 | 0.022 | 18.104 |
September | 393.083 | 9.683 | 15.133 | 0.602 | 10.285 |
October | 103.278 | 1.894 | 166.583 | 7.218 | 9.112 |
November | 5.611 | 0.015 | 369.889 | 15.909 | 15.924 |
December | 0.000 | 0.000 | 653.514 | 36.658 | 36.658 |
Annual Sum or Average | 2473.689 | 67.590 | 3160.819 | 168.622 | 236.212 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 4.991 |
Maximum of Months | 634.956 | 21.454 | 667.028 | 38.418 | 38.418 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 714.500 | 65.193 | 65.193 |
February | 0.000 | 0.000 | 629.125 | 59.159 | 59.159 |
March | 36.833 | 1.101 | 468.450 | 35.398 | 36.499 |
April | 87.372 | 2.060 | 291.036 | 16.373 | 18.433 |
May | 263.139 | 7.145 | 62.783 | 2.611 | 9.755 |
June | 508.083 | 20.846 | 8.833 | 0.345 | 21.191 |
July | 671.847 | 33.476 | 0.139 | 0.006 | 33.482 |
August | 606.439 | 27.574 | 0.139 | 0.007 | 27.581 |
September | 402.833 | 14.658 | 24.692 | 0.950 | 15.608 |
October | 112.056 | 2.947 | 252.556 | 12.463 | 15.410 |
November | 7.139 | 0.048 | 492.181 | 27.139 | 27.187 |
December | 0.000 | 0.000 | 717.000 | 62.507 | 62.507 |
Annual Sum or Average | 2695.742 | 109.854 | 3661.433 | 282.151 | 392.005 |
Minimum of Months | 0.000 | 0.000 | 0.139 | 0.006 | 9.755 |
Maximum of Months | 671.847 | 33.476 | 717.000 | 65.193 | 65.193 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 741.528 | 77.803 | 77.803 |
February | 0.000 | 0.000 | 658.611 | 71.130 | 71.130 |
March | 23.611 | 0.598 | 539.264 | 44.241 | 44.839 |
April | 49.833 | 0.866 | 364.778 | 20.261 | 21.126 |
May | 200.333 | 6.052 | 84.361 | 3.768 | 9.820 |
June | 479.403 | 20.850 | 11.472 | 0.589 | 21.439 |
July | 639.006 | 31.951 | 0.042 | 0.001 | 31.952 |
August | 567.594 | 24.647 | 1.250 | 0.061 | 24.708 |
September | 310.167 | 9.887 | 39.736 | 1.593 | 11.480 |
October | 46.611 | 0.717 | 340.597 | 16.266 | 16.983 |
November | 0.000 | 0.000 | 587.264 | 32.095 | 32.095 |
December | 0.000 | 0.000 | 743.056 | 72.282 | 72.282 |
Annual Sum or Average | 2316.558 | 95.568 | 4111.958 | 340.091 | 435.659 |
Minimum of Months | 0.000 | 0.000 | 0.042 | 0.001 | 9.820 |
Maximum of Months | 639.006 | 31.951 | 743.056 | 77.803 | 77.803 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 720.986 | 40.544 | 40.544 |
February | 0.000 | 0.000 | 647.750 | 37.359 | 37.359 |
March | 23.194 | 0.352 | 520.069 | 26.381 | 26.733 |
April | 5.472 | 0.029 | 300.542 | 12.781 | 12.810 |
May | 141.656 | 1.670 | 63.764 | 2.554 | 4.224 |
June | 437.583 | 10.788 | 8.458 | 0.365 | 11.153 |
July | 624.831 | 19.406 | 0.000 | 0.000 | 19.406 |
August | 573.983 | 14.849 | 0.583 | 0.023 | 14.872 |
September | 292.417 | 5.243 | 23.217 | 0.877 | 6.120 |
October | 28.222 | 0.222 | 255.292 | 9.575 | 9.797 |
November | 0.000 | 0.000 | 469.153 | 18.908 | 18.908 |
December | 0.000 | 0.000 | 700.861 | 38.047 | 38.047 |
Annual Sum or Average | 2127.358 | 52.560 | 3710.675 | 187.414 | 239.974 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 4.224 |
Maximum of Months | 624.831 | 19.406 | 720.986 | 40.544 | 40.544 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 67.239 | 67.239 |
February | 0.000 | 0.000 | 668.333 | 61.054 | 61.054 |
March | 25.056 | 0.648 | 562.928 | 41.137 | 41.785 |
April | 37.056 | 0.351 | 342.017 | 18.406 | 18.757 |
May | 210.731 | 4.766 | 73.053 | 2.930 | 7.695 |
June | 497.700 | 19.048 | 7.625 | 0.326 | 19.374 |
July | 664.842 | 31.146 | 0.000 | 0.000 | 31.146 |
August | 594.458 | 23.892 | 0.194 | 0.010 | 23.902 |
September | 353.647 | 9.317 | 33.344 | 1.166 | 10.482 |
October | 38.806 | 0.418 | 318.111 | 14.929 | 15.346 |
November | 0.000 | 0.000 | 582.500 | 30.558 | 30.558 |
December | 0.000 | 0.000 | 744.000 | 63.330 | 63.330 |
Annual Sum or Average | 2422.294 | 89.585 | 4076.106 | 301.084 | 390.669 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 7.695 |
Maximum of Months | 664.842 | 31.146 | 744.000 | 67.239 | 67.239 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 737.611 | 88.127 | 88.127 |
February | 0.000 | 0.000 | 655.444 | 80.296 | 80.296 |
March | 32.167 | 0.968 | 567.194 | 50.083 | 51.051 |
April | 66.806 | 1.624 | 406.025 | 24.613 | 26.236 |
May | 199.972 | 6.972 | 121.750 | 4.851 | 11.823 |
June | 473.556 | 22.098 | 22.811 | 0.934 | 23.032 |
July | 637.969 | 35.016 | 0.611 | 0.025 | 35.041 |
August | 566.936 | 28.266 | 2.014 | 0.092 | 28.358 |
September | 344.972 | 13.620 | 49.522 | 1.800 | 15.420 |
October | 82.639 | 2.246 | 364.528 | 18.530 | 20.776 |
November | 1.444 | 0.006 | 570.389 | 37.368 | 37.374 |
December | 0.000 | 0.000 | 735.528 | 83.266 | 83.266 |
Annual Sum or Average | 2406.461 | 110.817 | 4233.428 | 389.984 | 500.801 |
Minimum of Months | 0.000 | 0.000 | 0.611 | 0.025 | 11.823 |
Maximum of Months | 637.969 | 35.016 | 737.611 | 88.127 | 88.127 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 736.278 | 47.916 | 47.916 |
February | 0.000 | 0.000 | 656.056 | 43.543 | 43.543 |
March | 26.833 | 0.673 | 553.125 | 30.891 | 31.565 |
April | 26.111 | 0.167 | 373.211 | 16.576 | 16.743 |
May | 148.889 | 2.309 | 84.975 | 3.142 | 5.451 |
June | 440.347 | 12.221 | 16.889 | 0.610 | 12.831 |
July | 629.886 | 22.471 | 0.000 | 0.000 | 22.471 |
August | 578.644 | 18.291 | 0.775 | 0.035 | 18.326 |
September | 352.958 | 8.695 | 28.411 | 0.975 | 9.670 |
October | 74.278 | 1.270 | 294.344 | 11.537 | 12.807 |
November | 0.000 | 0.000 | 522.264 | 23.631 | 23.631 |
December | 0.000 | 0.000 | 732.000 | 45.980 | 45.980 |
Annual Sum or Average | 2277.947 | 66.098 | 3998.328 | 224.836 | 290.934 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 5.451 |
Maximum of Months | 629.886 | 22.471 | 736.278 | 47.916 | 47.916 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 739.028 | 74.404 | 74.404 |
February | 0.000 | 0.000 | 661.222 | 67.221 | 67.221 |
March | 28.694 | 0.972 | 583.178 | 45.393 | 46.365 |
April | 66.181 | 1.166 | 387.981 | 22.583 | 23.749 |
May | 213.528 | 5.564 | 102.111 | 3.835 | 9.400 |
June | 495.764 | 20.062 | 15.181 | 0.557 | 20.619 |
July | 670.736 | 33.872 | 0.083 | 0.004 | 33.876 |
August | 594.217 | 27.226 | 0.639 | 0.023 | 27.249 |
September | 378.692 | 13.107 | 42.864 | 1.454 | 14.562 |
October | 83.528 | 1.965 | 351.331 | 17.092 | 19.058 |
November | 0.917 | 0.003 | 568.014 | 35.305 | 35.308 |
December | 0.000 | 0.000 | 737.222 | 71.404 | 71.404 |
Annual Sum or Average | 2532.256 | 103.938 | 4188.853 | 339.276 | 443.214 |
Minimum of Months | 0.000 | 0.000 | 0.083 | 0.004 | 9.400 |
Maximum of Months | 670.736 | 33.872 | 739.028 | 74.404 | 74.404 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 90.686 | 90.686 |
February | 0.000 | 0.000 | 671.083 | 82.627 | 82.627 |
March | 22.000 | 0.564 | 621.500 | 55.072 | 55.635 |
April | 34.750 | 0.586 | 445.319 | 26.496 | 27.082 |
May | 171.722 | 5.498 | 136.161 | 5.239 | 10.737 |
June | 464.722 | 20.894 | 22.042 | 0.905 | 21.799 |
July | 635.794 | 33.344 | 0.194 | 0.007 | 33.352 |
August | 557.681 | 25.502 | 2.075 | 0.084 | 25.586 |
September | 295.333 | 9.710 | 63.278 | 2.257 | 11.967 |
October | 34.694 | 0.534 | 444.972 | 21.302 | 21.836 |
November | 0.000 | 0.000 | 636.403 | 40.929 | 40.929 |
December | 0.000 | 0.000 | 744.000 | 85.115 | 85.115 |
Annual Sum or Average | 2216.697 | 96.632 | 4531.028 | 410.719 | 507.351 |
Minimum of Months | 0.000 | 0.000 | 0.194 | 0.007 | 10.737 |
Maximum of Months | 635.794 | 33.344 | 744.000 | 90.686 | 90.686 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 49.618 | 49.618 |
February | 0.000 | 0.000 | 672.000 | 45.430 | 45.430 |
March | 21.111 | 0.355 | 610.722 | 34.676 | 35.031 |
April | 2.889 | 0.007 | 444.708 | 18.952 | 18.959 |
May | 105.100 | 1.541 | 102.269 | 3.740 | 5.281 |
June | 419.514 | 11.285 | 14.242 | 0.588 | 11.873 |
July | 626.817 | 21.163 | 0.000 | 0.000 | 21.163 |
August | 557.300 | 15.985 | 0.881 | 0.039 | 16.024 |
September | 278.028 | 5.294 | 43.678 | 1.365 | 6.660 |
October | 20.944 | 0.160 | 399.792 | 14.377 | 14.537 |
November | 0.000 | 0.000 | 617.361 | 27.032 | 27.032 |
December | 0.000 | 0.000 | 744.000 | 47.696 | 47.696 |
Annual Sum or Average | 2031.703 | 55.791 | 4393.653 | 243.514 | 299.305 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 5.281 |
Maximum of Months | 626.817 | 21.163 | 744.000 | 49.618 | 49.618 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 73.408 | 73.408 |
February | 0.000 | 0.000 | 672.000 | 66.957 | 66.957 |
March | 25.306 | 0.616 | 635.472 | 48.923 | 49.539 |
April | 19.589 | 0.165 | 439.317 | 24.298 | 24.464 |
May | 175.597 | 3.967 | 112.917 | 4.124 | 8.091 |
June | 486.486 | 18.733 | 12.806 | 0.521 | 19.254 |
July | 666.056 | 32.101 | 0.139 | 0.006 | 32.108 |
August | 585.661 | 24.450 | 0.639 | 0.024 | 24.474 |
September | 333.289 | 8.788 | 51.100 | 1.683 | 10.472 |
October | 24.000 | 0.283 | 433.914 | 19.661 | 19.944 |
November | 0.000 | 0.000 | 645.472 | 38.343 | 38.343 |
December | 0.000 | 0.000 | 744.000 | 70.325 | 70.325 |
Annual Sum or Average | 2315.983 | 89.103 | 4491.775 | 348.275 | 437.378 |
Minimum of Months | 0.000 | 0.000 | 0.139 | 0.006 | 8.091 |
Maximum of Months | 666.056 | 32.101 | 744.000 | 73.408 | 73.408 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 4947.38 | 0.00 | 0.00 |
February | 4764.09 | 0.00 | 0.00 |
March | 3147.48 | 0.00 | 0.00 |
April | 1991.36 | 0.00 | 0.00 |
May | 571.40 | 0.00 | 0.00 |
June | 133.83 | 0.00 | 0.00 |
July | 7.92 | 0.00 | 0.00 |
August | 23.39 | 0.00 | 0.00 |
September | 238.28 | 0.00 | 0.00 |
October | 1538.95 | 0.00 | 0.00 |
November | 2900.25 | 0.00 | 0.00 |
December | 4736.88 | 0.00 | 0.00 |
Annual Sum or Average | 2069.81 | 0.00 | 0.00 |
Minimum of Months | 7.92 | 0.00 | 0.00 |
Maximum of Months | 4947.38 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 3015.52 | 0.00 | 0.00 |
February | 2900.36 | 0.00 | 0.00 |
March | 2254.87 | 0.00 | 0.00 |
April | 1600.80 | 0.00 | 0.00 |
May | 459.99 | 0.00 | 0.00 |
June | 115.42 | 0.00 | 0.00 |
July | 4.57 | 0.00 | 0.00 |
August | 11.58 | 0.00 | 0.00 |
September | 158.36 | 0.00 | 0.00 |
October | 1146.45 | 0.00 | 0.00 |
November | 2146.22 | 0.00 | 0.00 |
December | 2957.54 | 0.00 | 0.00 |
Annual Sum or Average | 1389.59 | 0.00 | 0.00 |
Minimum of Months | 4.57 | 0.00 | 0.00 |
Maximum of Months | 3015.52 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 4339.91 | 0.00 | 0.00 |
February | 4149.66 | 0.00 | 0.00 |
March | 2966.29 | 0.00 | 0.00 |
April | 1879.51 | 0.00 | 0.00 |
May | 461.20 | 0.00 | 0.00 |
June | 84.99 | 0.00 | 0.00 |
July | 2.46 | 0.00 | 0.00 |
August | 8.10 | 0.00 | 0.00 |
September | 198.74 | 0.00 | 0.00 |
October | 1463.61 | 0.00 | 0.00 |
November | 2830.12 | 0.00 | 0.00 |
December | 4234.85 | 0.00 | 0.00 |
Annual Sum or Average | 1873.32 | 0.00 | 0.00 |
Minimum of Months | 2.46 | 0.00 | 0.00 |
Maximum of Months | 4339.91 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 5104.59 | 0.00 | 0.00 |
February | 4929.15 | 0.00 | 0.00 |
March | 3540.19 | 0.00 | 0.00 |
April | 2225.66 | 0.00 | 0.00 |
May | 634.49 | 0.00 | 0.00 |
June | 136.50 | 0.00 | 0.00 |
July | 6.17 | 0.00 | 0.00 |
August | 23.53 | 0.00 | 0.00 |
September | 310.11 | 0.00 | 0.00 |
October | 1840.90 | 0.00 | 0.00 |
November | 3242.42 | 0.00 | 0.00 |
December | 4859.36 | 0.00 | 0.00 |
Annual Sum or Average | 2223.95 | 0.00 | 0.00 |
Minimum of Months | 6.17 | 0.00 | 0.00 |
Maximum of Months | 5104.59 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 3079.34 | 0.00 | 0.00 |
February | 2992.26 | 0.00 | 0.00 |
March | 2559.90 | 0.00 | 0.00 |
April | 1921.81 | 0.00 | 0.00 |
May | 573.86 | 0.00 | 0.00 |
June | 115.89 | 0.00 | 0.00 |
July | 1.77 | 0.00 | 0.00 |
August | 12.95 | 0.00 | 0.00 |
September | 239.02 | 0.00 | 0.00 |
October | 1505.12 | 0.00 | 0.00 |
November | 2486.91 | 0.00 | 0.00 |
December | 3038.18 | 0.00 | 0.00 |
Annual Sum or Average | 1535.88 | 0.00 | 0.00 |
Minimum of Months | 1.77 | 0.00 | 0.00 |
Maximum of Months | 3079.34 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 4348.15 | 0.00 | 0.00 |
February | 4215.67 | 0.00 | 0.00 |
March | 3308.65 | 0.00 | 0.00 |
April | 2118.30 | 0.00 | 0.00 |
May | 527.57 | 0.00 | 0.00 |
June | 79.11 | 0.00 | 0.00 |
July | 2.47 | 0.00 | 0.00 |
August | 9.16 | 0.00 | 0.00 |
September | 241.50 | 0.00 | 0.00 |
October | 1760.87 | 0.00 | 0.00 |
November | 3163.61 | 0.00 | 0.00 |
December | 4232.94 | 0.00 | 0.00 |
Annual Sum or Average | 1989.04 | 0.00 | 0.00 |
Minimum of Months | 2.47 | 0.00 | 0.00 |
Maximum of Months | 4348.15 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 4038.08 | 0.00 | 0.00 |
February | 3900.13 | 0.00 | 0.00 |
March | 2328.56 | 0.00 | 0.00 |
April | 1362.21 | 0.00 | 0.00 |
May | 331.79 | 0.00 | 0.00 |
June | 65.34 | 0.00 | 0.00 |
July | 1.02 | 0.00 | 0.00 |
August | 6.13 | 0.00 | 0.00 |
September | 132.85 | 0.00 | 0.00 |
October | 1060.03 | 0.00 | 0.00 |
November | 2110.71 | 0.00 | 0.00 |
December | 3815.05 | 0.00 | 0.00 |
Annual Sum or Average | 1584.49 | 0.00 | 0.00 |
Minimum of Months | 1.02 | 0.00 | 0.00 |
Maximum of Months | 4038.08 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 2469.31 | 0.00 | 0.00 |
February | 2392.35 | 0.00 | 0.00 |
March | 1558.90 | 0.00 | 0.00 |
April | 972.02 | 0.00 | 0.00 |
May | 243.67 | 0.00 | 0.00 |
June | 46.84 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 2.99 | 0.00 | 0.00 |
September | 79.19 | 0.00 | 0.00 |
October | 681.73 | 0.00 | 0.00 |
November | 1411.85 | 0.00 | 0.00 |
December | 2379.30 | 0.00 | 0.00 |
Annual Sum or Average | 1012.86 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2469.31 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 3674.42 | 0.00 | 0.00 |
February | 3521.17 | 0.00 | 0.00 |
March | 2205.50 | 0.00 | 0.00 |
April | 1256.50 | 0.00 | 0.00 |
May | 253.50 | 0.00 | 0.00 |
June | 35.77 | 0.00 | 0.00 |
July | 0.69 | 0.00 | 0.00 |
August | 0.85 | 0.00 | 0.00 |
September | 102.63 | 0.00 | 0.00 |
October | 987.75 | 0.00 | 0.00 |
November | 2076.44 | 0.00 | 0.00 |
December | 3553.42 | 0.00 | 0.00 |
Annual Sum or Average | 1462.17 | 0.00 | 0.00 |
Minimum of Months | 0.69 | 0.00 | 0.00 |
Maximum of Months | 3674.42 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 4298.86 | 0.00 | 0.00 |
February | 4156.80 | 0.00 | 0.00 |
March | 2713.95 | 0.00 | 0.00 |
April | 1561.54 | 0.00 | 0.00 |
May | 377.53 | 0.00 | 0.00 |
June | 64.80 | 0.00 | 0.00 |
July | 0.18 | 0.00 | 0.00 |
August | 6.97 | 0.00 | 0.00 |
September | 175.99 | 0.00 | 0.00 |
October | 1312.31 | 0.00 | 0.00 |
November | 2440.44 | 0.00 | 0.00 |
December | 4012.06 | 0.00 | 0.00 |
Annual Sum or Average | 1748.08 | 0.00 | 0.00 |
Minimum of Months | 0.18 | 0.00 | 0.00 |
Maximum of Months | 4298.86 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 2650.71 | 0.00 | 0.00 |
February | 2595.88 | 0.00 | 0.00 |
March | 1953.61 | 0.00 | 0.00 |
April | 1226.79 | 0.00 | 0.00 |
May | 317.84 | 0.00 | 0.00 |
June | 49.89 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 3.11 | 0.00 | 0.00 |
September | 119.45 | 0.00 | 0.00 |
October | 953.46 | 0.00 | 0.00 |
November | 1735.44 | 0.00 | 0.00 |
December | 2511.67 | 0.00 | 0.00 |
Annual Sum or Average | 1169.13 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2650.71 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 3852.71 | 0.00 | 0.00 |
February | 3705.00 | 0.00 | 0.00 |
March | 2617.17 | 0.00 | 0.00 |
April | 1444.77 | 0.00 | 0.00 |
May | 286.76 | 0.00 | 0.00 |
June | 33.96 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 1.12 | 0.00 | 0.00 |
September | 126.18 | 0.00 | 0.00 |
October | 1226.82 | 0.00 | 0.00 |
November | 2397.12 | 0.00 | 0.00 |
December | 3660.24 | 0.00 | 0.00 |
Annual Sum or Average | 1602.17 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3852.71 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 4967.08 | 0.00 | 0.00 |
February | 4784.78 | 0.00 | 0.00 |
March | 3116.07 | 0.00 | 0.00 |
April | 1892.26 | 0.00 | 0.00 |
May | 476.02 | 0.00 | 0.00 |
June | 100.99 | 0.00 | 0.00 |
July | 2.81 | 0.00 | 0.00 |
August | 10.54 | 0.00 | 0.00 |
September | 194.44 | 0.00 | 0.00 |
October | 1474.78 | 0.00 | 0.00 |
November | 2854.87 | 0.00 | 0.00 |
December | 4734.39 | 0.00 | 0.00 |
Annual Sum or Average | 2036.94 | 0.00 | 0.00 |
Minimum of Months | 2.81 | 0.00 | 0.00 |
Maximum of Months | 4967.08 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 3167.23 | 0.00 | 0.00 |
February | 3053.31 | 0.00 | 0.00 |
March | 2291.41 | 0.00 | 0.00 |
April | 1524.23 | 0.00 | 0.00 |
May | 374.03 | 0.00 | 0.00 |
June | 79.56 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 4.89 | 0.00 | 0.00 |
September | 126.55 | 0.00 | 0.00 |
October | 1087.30 | 0.00 | 0.00 |
November | 2127.57 | 0.00 | 0.00 |
December | 3080.51 | 0.00 | 0.00 |
Annual Sum or Average | 1401.09 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3167.23 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 4385.37 | 0.00 | 0.00 |
February | 4193.87 | 0.00 | 0.00 |
March | 2960.32 | 0.00 | 0.00 |
April | 1785.39 | 0.00 | 0.00 |
May | 377.62 | 0.00 | 0.00 |
June | 58.34 | 0.00 | 0.00 |
July | 0.47 | 0.00 | 0.00 |
August | 2.68 | 0.00 | 0.00 |
September | 158.36 | 0.00 | 0.00 |
October | 1404.60 | 0.00 | 0.00 |
November | 2809.87 | 0.00 | 0.00 |
December | 4262.25 | 0.00 | 0.00 |
Annual Sum or Average | 1854.74 | 0.00 | 0.00 |
Minimum of Months | 0.47 | 0.00 | 0.00 |
Maximum of Months | 4385.37 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 5162.98 | 0.00 | 0.00 |
February | 4983.28 | 0.00 | 0.00 |
March | 3475.26 | 0.00 | 0.00 |
April | 2070.45 | 0.00 | 0.00 |
May | 520.15 | 0.00 | 0.00 |
June | 99.21 | 0.00 | 0.00 |
July | 0.85 | 0.00 | 0.00 |
August | 9.74 | 0.00 | 0.00 |
September | 248.36 | 0.00 | 0.00 |
October | 1744.36 | 0.00 | 0.00 |
November | 3181.91 | 0.00 | 0.00 |
December | 4885.05 | 0.00 | 0.00 |
Annual Sum or Average | 2184.33 | 0.00 | 0.00 |
Minimum of Months | 0.85 | 0.00 | 0.00 |
Maximum of Months | 5162.98 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 3286.99 | 0.00 | 0.00 |
February | 3202.06 | 0.00 | 0.00 |
March | 2603.08 | 0.00 | 0.00 |
April | 1780.14 | 0.00 | 0.00 |
May | 451.77 | 0.00 | 0.00 |
June | 77.63 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 5.28 | 0.00 | 0.00 |
September | 179.54 | 0.00 | 0.00 |
October | 1401.17 | 0.00 | 0.00 |
November | 2465.93 | 0.00 | 0.00 |
December | 3202.48 | 0.00 | 0.00 |
Annual Sum or Average | 1545.83 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3286.99 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 4386.20 | 0.00 | 0.00 |
February | 4247.83 | 0.00 | 0.00 |
March | 3261.21 | 0.00 | 0.00 |
April | 1963.30 | 0.00 | 0.00 |
May | 410.07 | 0.00 | 0.00 |
June | 55.38 | 0.00 | 0.00 |
July | 0.73 | 0.00 | 0.00 |
August | 2.88 | 0.00 | 0.00 |
September | 185.67 | 0.00 | 0.00 |
October | 1666.98 | 0.00 | 0.00 |
November | 3119.74 | 0.00 | 0.00 |
December | 4255.68 | 0.00 | 0.00 |
Annual Sum or Average | 1951.12 | 0.00 | 0.00 |
Minimum of Months | 0.73 | 0.00 | 0.00 |
Maximum of Months | 4386.20 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 890.41 | 0.00 | 0.00 |
February | 1274.02 | 0.00 | 0.00 |
March | 263.95 | 0.00 | 0.00 |
April | 10.48 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.02 | 0.00 | 0.00 |
October | 2.57 | 0.00 | 0.00 |
November | 8.40 | 0.00 | 0.00 |
December | 908.37 | 0.00 | 0.00 |
Annual Sum or Average | 274.70 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1274.02 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1824.27 | 0.00 | 0.00 |
February | 2205.34 | 0.00 | 0.00 |
March | 740.44 | 0.00 | 0.00 |
April | 172.54 | 0.00 | 0.00 |
May | 15.07 | 0.00 | 0.00 |
June | 1.84 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 3.45 | 0.00 | 0.00 |
October | 77.75 | 0.00 | 0.00 |
November | 193.64 | 0.00 | 0.00 |
December | 1718.35 | 0.00 | 0.00 |
Annual Sum or Average | 571.36 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2205.34 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1500.63 | 0.00 | 0.00 |
February | 1908.67 | 0.00 | 0.00 |
March | 470.25 | 0.00 | 0.00 |
April | 37.93 | 0.00 | 0.00 |
May | 1.59 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.22 | 0.00 | 0.00 |
October | 12.72 | 0.00 | 0.00 |
November | 53.82 | 0.00 | 0.00 |
December | 1463.53 | 0.00 | 0.00 |
Annual Sum or Average | 446.88 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1908.67 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1192.28 | 0.00 | 0.00 |
February | 1569.74 | 0.00 | 0.00 |
March | 364.05 | 0.00 | 0.00 |
April | 16.88 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.08 | 0.00 | 0.00 |
October | 3.24 | 0.00 | 0.00 |
November | 10.32 | 0.00 | 0.00 |
December | 1148.97 | 0.00 | 0.00 |
Annual Sum or Average | 352.70 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1569.74 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 2224.48 | 0.00 | 0.00 |
February | 2572.32 | 0.00 | 0.00 |
March | 964.23 | 0.00 | 0.00 |
April | 186.19 | 0.00 | 0.00 |
May | 16.68 | 0.00 | 0.00 |
June | 2.81 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 3.95 | 0.00 | 0.00 |
October | 72.58 | 0.00 | 0.00 |
November | 225.80 | 0.00 | 0.00 |
December | 1997.97 | 0.00 | 0.00 |
Annual Sum or Average | 679.84 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2572.32 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1958.71 | 0.00 | 0.00 |
February | 2308.71 | 0.00 | 0.00 |
March | 637.58 | 0.00 | 0.00 |
April | 51.15 | 0.00 | 0.00 |
May | 2.44 | 0.00 | 0.00 |
June | 0.36 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.45 | 0.00 | 0.00 |
October | 16.33 | 0.00 | 0.00 |
November | 83.31 | 0.00 | 0.00 |
December | 1837.63 | 0.00 | 0.00 |
Annual Sum or Average | 566.40 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2308.71 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 353.75 | 0.00 | 0.00 |
February | 556.64 | 0.00 | 0.00 |
March | 115.50 | 0.00 | 0.00 |
April | 8.76 | 0.00 | 0.00 |
May | 0.01 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 6.34 | 0.00 | 0.00 |
November | 5.11 | 0.00 | 0.00 |
December | 403.27 | 0.00 | 0.00 |
Annual Sum or Average | 118.48 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 556.64 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 937.37 | 0.00 | 0.00 |
February | 1146.64 | 0.00 | 0.00 |
March | 450.55 | 0.00 | 0.00 |
April | 148.54 | 0.00 | 0.00 |
May | 10.80 | 0.00 | 0.00 |
June | 1.03 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 1.83 | 0.00 | 0.00 |
October | 77.09 | 0.00 | 0.00 |
November | 165.26 | 0.00 | 0.00 |
December | 881.53 | 0.00 | 0.00 |
Annual Sum or Average | 314.20 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1146.64 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 691.88 | 0.00 | 0.00 |
February | 931.03 | 0.00 | 0.00 |
March | 242.95 | 0.00 | 0.00 |
April | 35.35 | 0.00 | 0.00 |
May | 0.72 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.39 | 0.00 | 0.00 |
October | 21.42 | 0.00 | 0.00 |
November | 21.33 | 0.00 | 0.00 |
December | 695.90 | 0.00 | 0.00 |
Annual Sum or Average | 216.49 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 931.03 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 505.30 | 0.00 | 0.00 |
February | 716.08 | 0.00 | 0.00 |
March | 171.01 | 0.00 | 0.00 |
April | 9.35 | 0.00 | 0.00 |
May | 0.21 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 6.56 | 0.00 | 0.00 |
November | 5.99 | 0.00 | 0.00 |
December | 540.76 | 0.00 | 0.00 |
Annual Sum or Average | 160.14 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 716.08 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1159.33 | 0.00 | 0.00 |
February | 1368.86 | 0.00 | 0.00 |
March | 541.46 | 0.00 | 0.00 |
April | 171.01 | 0.00 | 0.00 |
May | 13.80 | 0.00 | 0.00 |
June | 1.16 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 2.77 | 0.00 | 0.00 |
October | 89.61 | 0.00 | 0.00 |
November | 177.40 | 0.00 | 0.00 |
December | 1083.66 | 0.00 | 0.00 |
Annual Sum or Average | 379.24 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1368.86 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 940.84 | 0.00 | 0.00 |
February | 1178.38 | 0.00 | 0.00 |
March | 300.70 | 0.00 | 0.00 |
April | 40.97 | 0.00 | 0.00 |
May | 1.15 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.35 | 0.00 | 0.00 |
October | 19.80 | 0.00 | 0.00 |
November | 35.21 | 0.00 | 0.00 |
December | 931.33 | 0.00 | 0.00 |
Annual Sum or Average | 283.01 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1178.38 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 828.40 | 0.00 | 0.00 |
February | 1181.84 | 0.00 | 0.00 |
March | 243.77 | 0.00 | 0.00 |
April | 8.48 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 2.18 | 0.00 | 0.00 |
November | 5.18 | 0.00 | 0.00 |
December | 855.29 | 0.00 | 0.00 |
Annual Sum or Average | 255.67 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1181.84 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1611.47 | 0.00 | 0.00 |
February | 1969.98 | 0.00 | 0.00 |
March | 627.69 | 0.00 | 0.00 |
April | 127.34 | 0.00 | 0.00 |
May | 10.02 | 0.00 | 0.00 |
June | 0.80 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 1.90 | 0.00 | 0.00 |
October | 63.35 | 0.00 | 0.00 |
November | 151.97 | 0.00 | 0.00 |
December | 1523.91 | 0.00 | 0.00 |
Annual Sum or Average | 500.13 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1969.98 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1412.24 | 0.00 | 0.00 |
February | 1795.16 | 0.00 | 0.00 |
March | 427.69 | 0.00 | 0.00 |
April | 30.02 | 0.00 | 0.00 |
May | 0.91 | 0.00 | 0.00 |
June | 0.05 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.09 | 0.00 | 0.00 |
October | 13.22 | 0.00 | 0.00 |
November | 43.61 | 0.00 | 0.00 |
December | 1379.52 | 0.00 | 0.00 |
Annual Sum or Average | 418.41 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1795.16 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1031.23 | 0.00 | 0.00 |
February | 1381.79 | 0.00 | 0.00 |
March | 306.70 | 0.00 | 0.00 |
April | 11.16 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 3.07 | 0.00 | 0.00 |
November | 7.51 | 0.00 | 0.00 |
December | 1024.19 | 0.00 | 0.00 |
Annual Sum or Average | 308.41 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1381.79 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1900.45 | 0.00 | 0.00 |
February | 2228.69 | 0.00 | 0.00 |
March | 766.32 | 0.00 | 0.00 |
April | 135.76 | 0.00 | 0.00 |
May | 12.64 | 0.00 | 0.00 |
June | 1.23 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 1.90 | 0.00 | 0.00 |
October | 65.62 | 0.00 | 0.00 |
November | 165.45 | 0.00 | 0.00 |
December | 1727.57 | 0.00 | 0.00 |
Annual Sum or Average | 575.85 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2228.69 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1828.38 | 0.00 | 0.00 |
February | 2152.02 | 0.00 | 0.00 |
March | 565.97 | 0.00 | 0.00 |
April | 42.29 | 0.00 | 0.00 |
May | 1.76 | 0.00 | 0.00 |
June | 0.03 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.31 | 0.00 | 0.00 |
October | 15.01 | 0.00 | 0.00 |
November | 67.80 | 0.00 | 0.00 |
December | 1719.19 | 0.00 | 0.00 |
Annual Sum or Average | 524.96 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2152.02 | 0.00 | 0.00 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.17 |
July | 0.00 | 0.00 | 0.27 |
August | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.27 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.10 |
July | 0.00 | 0.00 | 0.19 |
August | 0.00 | 0.00 | 0.15 |
September | 0.00 | 0.00 | 0.07 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.19 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.16 |
July | 0.00 | 0.00 | 0.26 |
August | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.00 | 0.10 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.26 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.16 |
July | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.00 | 0.18 |
September | 0.00 | 0.00 | 0.07 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.25 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.01 |
June | 0.00 | 0.00 | 0.09 |
July | 0.00 | 0.00 | 0.17 |
August | 0.00 | 0.00 | 0.12 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.17 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.14 |
July | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.00 | 0.18 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.24 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.19 |
July | 0.00 | 0.00 | 0.29 |
August | 0.00 | 0.00 | 0.23 |
September | 0.00 | 0.00 | 0.13 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.29 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.12 |
July | 0.00 | 0.00 | 0.21 |
August | 0.00 | 0.00 | 0.17 |
September | 0.00 | 0.00 | 0.09 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.21 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.18 |
July | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.23 |
September | 0.00 | 0.00 | 0.13 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.28 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.18 |
July | 0.00 | 0.00 | 0.27 |
August | 0.00 | 0.00 | 0.20 |
September | 0.00 | 0.00 | 0.08 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.27 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.11 |
July | 0.00 | 0.00 | 0.19 |
August | 0.00 | 0.00 | 0.14 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.19 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.16 |
July | 0.00 | 0.00 | 0.27 |
August | 0.00 | 0.00 | 0.20 |
September | 0.00 | 0.00 | 0.08 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.27 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.19 |
July | 0.00 | 0.00 | 0.29 |
August | 0.00 | 0.00 | 0.23 |
September | 0.00 | 0.00 | 0.12 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.29 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.12 |
July | 0.00 | 0.00 | 0.22 |
August | 0.00 | 0.00 | 0.18 |
September | 0.00 | 0.00 | 0.08 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.22 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.18 |
July | 0.00 | 0.00 | 0.29 |
August | 0.00 | 0.00 | 0.23 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.29 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.18 |
July | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.00 | 0.08 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.28 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.01 |
June | 0.00 | 0.00 | 0.11 |
July | 0.00 | 0.00 | 0.21 |
August | 0.00 | 0.00 | 0.15 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.21 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.17 |
July | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.00 | 0.08 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.28 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: CRAWLSPACE
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: BREEZEWAY
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 1.50 | 2460.92 |
February | 3.42 | 2320.53 |
March | 29.62 | 1189.47 |
April | 51.78 | 578.47 |
May | 97.43 | 126.04 |
June | 149.63 | 30.71 |
July | 183.35 | 1.54 |
August | 167.93 | 4.79 |
September | 116.73 | 55.71 |
October | 52.74 | 426.88 |
November | 18.10 | 947.18 |
December | 1.79 | 2404.61 |
Annual Sum or Average | 874.02 | 10546.84 |
Minimum of Months | 1.50 | 1.54 |
Maximum of Months | 183.35 | 2460.92 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 1.73 | 1574.18 |
February | 3.35 | 1560.16 |
March | 27.21 | 800.19 |
April | 44.23 | 402.26 |
May | 76.94 | 112.44 |
June | 103.11 | 26.31 |
July | 131.51 | 0.48 |
August | 125.13 | 1.90 |
September | 96.73 | 34.37 |
October | 54.73 | 258.91 |
November | 22.89 | 551.40 |
December | 2.59 | 1556.32 |
Annual Sum or Average | 690.16 | 6878.92 |
Minimum of Months | 1.73 | 0.48 |
Maximum of Months | 131.51 | 1574.18 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 1.03 | 2410.38 |
February | 3.10 | 2285.31 |
March | 27.34 | 1166.15 |
April | 52.61 | 555.89 |
May | 95.71 | 112.50 |
June | 142.28 | 19.19 |
July | 182.09 | 0.54 |
August | 166.14 | 1.27 |
September | 117.12 | 49.59 |
October | 53.34 | 403.37 |
November | 18.82 | 935.61 |
December | 1.65 | 2400.94 |
Annual Sum or Average | 861.23 | 10340.74 |
Minimum of Months | 1.03 | 0.54 |
Maximum of Months | 182.09 | 2410.38 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 2789.22 |
February | 0.19 | 2595.98 |
March | 15.54 | 1439.68 |
April | 35.87 | 659.20 |
May | 84.09 | 145.99 |
June | 140.00 | 30.64 |
July | 170.46 | 1.11 |
August | 147.33 | 5.25 |
September | 88.48 | 81.83 |
October | 28.59 | 513.59 |
November | 7.93 | 1094.52 |
December | 0.00 | 2655.75 |
Annual Sum or Average | 718.48 | 12012.75 |
Minimum of Months | 0.00 | 1.11 |
Maximum of Months | 170.46 | 2789.22 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 1900.44 |
February | 0.00 | 1831.92 |
March | 14.10 | 1074.04 |
April | 28.69 | 485.54 |
May | 65.44 | 137.69 |
June | 94.73 | 26.53 |
July | 118.99 | 0.33 |
August | 104.98 | 2.78 |
September | 69.12 | 52.42 |
October | 30.04 | 334.65 |
November | 10.05 | 677.93 |
December | 0.00 | 1796.20 |
Annual Sum or Average | 536.14 | 8320.48 |
Minimum of Months | 0.00 | 0.33 |
Maximum of Months | 118.99 | 1900.44 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 2742.83 |
February | 0.00 | 2562.23 |
March | 13.53 | 1424.00 |
April | 35.43 | 618.40 |
May | 81.00 | 122.14 |
June | 132.30 | 17.67 |
July | 168.75 | 0.55 |
August | 144.96 | 1.47 |
September | 86.13 | 59.26 |
October | 28.47 | 474.16 |
November | 5.87 | 1057.95 |
December | 0.00 | 2655.64 |
Annual Sum or Average | 696.44 | 11736.31 |
Minimum of Months | 0.00 | 0.55 |
Maximum of Months | 168.75 | 2742.83 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 5.12 | 1378.77 |
February | 8.95 | 1278.98 |
March | 50.13 | 654.94 |
April | 73.51 | 307.79 |
May | 118.90 | 84.61 |
June | 166.83 | 14.12 |
July | 198.71 | 0.02 |
August | 183.61 | 1.01 |
September | 133.26 | 29.22 |
October | 72.99 | 244.55 |
November | 30.02 | 482.10 |
December | 5.85 | 1342.52 |
Annual Sum or Average | 1047.87 | 5818.62 |
Minimum of Months | 5.12 | 0.02 |
Maximum of Months | 198.71 | 1378.77 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 15.28 | 640.33 |
February | 15.00 | 623.01 |
March | 56.85 | 381.38 |
April | 73.99 | 236.85 |
May | 94.17 | 56.88 |
June | 119.63 | 8.87 |
July | 146.57 | 0.04 |
August | 141.12 | 0.50 |
September | 113.47 | 15.58 |
October | 81.17 | 161.46 |
November | 48.37 | 274.06 |
December | 15.96 | 635.38 |
Annual Sum or Average | 921.59 | 3034.34 |
Minimum of Months | 15.00 | 0.04 |
Maximum of Months | 146.57 | 640.33 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 6.57 | 1345.99 |
February | 9.30 | 1250.55 |
March | 49.40 | 645.34 |
April | 75.98 | 299.06 |
May | 116.79 | 64.53 |
June | 160.44 | 6.46 |
July | 198.26 | 0.02 |
August | 182.61 | 0.14 |
September | 134.91 | 23.61 |
October | 75.33 | 239.73 |
November | 30.48 | 473.68 |
December | 5.13 | 1332.35 |
Annual Sum or Average | 1045.20 | 5681.46 |
Minimum of Months | 5.13 | 0.02 |
Maximum of Months | 198.26 | 1345.99 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.47 | 1643.18 |
February | 2.46 | 1493.22 |
March | 31.83 | 827.80 |
April | 54.52 | 343.96 |
May | 104.56 | 98.63 |
June | 157.10 | 12.53 |
July | 185.92 | 0.01 |
August | 162.83 | 1.43 |
September | 103.08 | 40.88 |
October | 46.89 | 304.70 |
November | 14.83 | 561.21 |
December | 0.12 | 1532.01 |
Annual Sum or Average | 864.61 | 6859.57 |
Minimum of Months | 0.12 | 0.01 |
Maximum of Months | 185.92 | 1643.18 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 4.06 | 817.08 |
February | 3.89 | 783.11 |
March | 31.40 | 485.64 |
April | 57.52 | 289.80 |
May | 82.06 | 75.18 |
June | 110.47 | 9.73 |
July | 134.15 | 0.19 |
August | 120.65 | 0.98 |
September | 83.71 | 24.80 |
October | 55.55 | 214.19 |
November | 31.48 | 327.78 |
December | 6.77 | 780.59 |
Annual Sum or Average | 721.74 | 3809.08 |
Minimum of Months | 3.89 | 0.19 |
Maximum of Months | 134.15 | 817.08 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 1593.71 |
February | 0.86 | 1447.02 |
March | 27.09 | 782.34 |
April | 56.79 | 335.79 |
May | 101.33 | 70.14 |
June | 150.56 | 6.96 |
July | 185.46 | 0.00 |
August | 161.52 | 0.14 |
September | 102.85 | 26.68 |
October | 48.82 | 287.89 |
November | 16.60 | 567.38 |
December | 0.00 | 1529.27 |
Annual Sum or Average | 851.89 | 6647.31 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 185.46 | 1593.71 |
Report: HEATING AND COOLING LOADS
For: ATTIC
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 2676.30 |
February | 0.00 | 2480.30 |
March | 14.82 | 1342.59 |
April | 40.18 | 547.00 |
May | 91.65 | 101.53 |
June | 148.63 | 12.46 |
July | 191.40 | 0.05 |
August | 165.76 | 0.39 |
September | 98.40 | 46.13 |
October | 33.37 | 453.02 |
November | 6.75 | 1022.78 |
December | 0.00 | 2585.87 |
Annual Sum or Average | 790.96 | 11268.43 |
Minimum of Months | 0.00 | 0.05 |
Maximum of Months | 191.40 | 2676.30 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.91 | 2380.05 |
February | 2.45 | 2233.94 |
March | 27.07 | 1124.23 |
April | 54.69 | 505.94 |
May | 102.83 | 96.86 |
June | 155.79 | 12.73 |
July | 200.84 | 0.05 |
August | 181.74 | 0.23 |
September | 124.29 | 37.42 |
October | 55.19 | 385.71 |
November | 18.51 | 908.15 |
December | 1.32 | 2357.33 |
Annual Sum or Average | 925.63 | 10042.63 |
Minimum of Months | 0.91 | 0.05 |
Maximum of Months | 200.84 | 2380.05 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 1.31 | 2429.90 |
February | 3.21 | 2272.52 |
March | 30.22 | 1157.61 |
April | 53.41 | 529.95 |
May | 104.99 | 115.36 |
June | 162.44 | 22.92 |
July | 201.61 | 0.28 |
August | 183.06 | 1.67 |
September | 123.90 | 46.30 |
October | 53.73 | 402.41 |
November | 18.20 | 917.20 |
December | 1.57 | 2362.09 |
Annual Sum or Average | 937.66 | 10258.21 |
Minimum of Months | 1.31 | 0.28 |
Maximum of Months | 201.61 | 2429.90 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 1829.78 |
February | 0.00 | 1755.11 |
March | 16.78 | 992.03 |
April | 35.96 | 429.24 |
May | 76.05 | 117.06 |
June | 111.00 | 16.56 |
July | 141.48 | 0.11 |
August | 125.89 | 1.37 |
September | 80.87 | 38.56 |
October | 36.99 | 326.19 |
November | 11.10 | 635.97 |
December | 0.00 | 1731.71 |
Annual Sum or Average | 636.12 | 7873.69 |
Minimum of Months | 0.00 | 0.11 |
Maximum of Months | 141.48 | 1829.78 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 1.46 | 1537.00 |
February | 3.15 | 1512.01 |
March | 29.16 | 767.24 |
April | 48.56 | 364.24 |
May | 84.36 | 91.58 |
June | 117.12 | 16.51 |
July | 150.70 | 0.03 |
August | 141.37 | 1.43 |
September | 105.02 | 28.40 |
October | 58.58 | 248.49 |
November | 24.34 | 526.70 |
December | 2.23 | 1509.94 |
Annual Sum or Average | 766.05 | 6603.56 |
Minimum of Months | 1.46 | 0.03 |
Maximum of Months | 150.70 | 1537.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:34:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 2720.11 |
February | 0.12 | 2511.73 |
March | 17.44 | 1365.06 |
April | 41.16 | 593.61 |
May | 94.03 | 119.94 |
June | 155.84 | 22.96 |
July | 192.56 | 0.03 |
August | 167.45 | 1.88 |
September | 99.26 | 59.01 |
October | 33.07 | 487.72 |
November | 8.40 | 1052.85 |
December | 0.00 | 2587.48 |
Annual Sum or Average | 809.33 | 11522.38 |
Minimum of Months | 0.00 | 0.03 |
Maximum of Months | 192.56 | 2720.11 |